Knick VariTrans P 27000 Universal Isolated Signal Conditioner Owner Manual
Add to My manuals12 Pages
Knick VariTrans P 27000 universal isolators are designed for galvanic isolation and conversion of input signals from 0 ... ± 200 V to output signals from ±0 ... 10 V or ± 0 ... 20 mA. They feature linear signal transmission, broad-range mains adapter for powering with voltages from 20 to 253 V AC/DC, and pluggable screw clamp terminals for easy connection. These isolators are commonly used in industrial settings for electrical isolation, signal conversion, and data transmission in various applications such as process control, automation, and measurement systems.
advertisement
VariTrans® P 27000-S008
Universal Isolators
TA-251.101-KNE01 20111128
1. Safety Information
The warning symbol on the device (exclamation point in triangle) means: Observe instructions!
Warning! Protection against electric shock
For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!
Caution!
Be sure to take protective measures against electrostatic discharge
(ESD) when handling the devices!
Caution!
The VariTrans® P 27000 universal isolators must be installed only by qualified and specially trained personnel authorized by the operating company.
Do not connect the device to power supply before it is professionally installed.
Do not change the measuring range during operation. Observe the national codes and regulations during installation and selection of cables and lines.
Equipment shall be provided with a means for disconnecting it from each operating energy supply source. The disconnecting means shall disconnect all current-carrying conductors. (It must be easily accessible and clearly identifiable by the operator.)
Mains supply must be protected by a fuse of 20 A max.
2
Warning! EXPLOSION HAZARD
Do not connect/disconnect equipment unless power has been removed or the area is known to be non-hazardous.
Warning! EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Conditions for safe use (Haz. Loc.)
For the use in hazardous locations, this equipment is to be installed into suitable enclosure, providing a degree of protection not less than IP 54.
Devices containing user accessible switches and/or potentiometers: the device must be installed into an end-use enclosure with tool removable cover.
3
2. Intended Use
The special models P 27000-S008 universal isolators are used for galvanic isolation and conversion of input signals from 0 ... ± 200 V to output signals from ±0 ... 10 V or ± 0 ... 20 mA. The calibrated output signal range is selected via
DIP switches. Signal transmission is linear. By means of the broad-range mains adapter, the units can be powered by voltages from 20 to 253 V AC/DC.
Connection is made using pluggable screw clamp terminals.
Warning against misuse
Do not operate the device outside the conditions specified by the manufacturer, as this might result in hazards to operators or malfunction of the equipment.
3. Configuration
3.1 Tools
A screwdriver with a width of 2.5 mm is required to open and adjust the unit and to connect the wires to the screw clamp terminals.
4
3.2 Opening the unit
Disengage the top part of the housing on both sides using the screwdriver.
Pull out the top part of the housing and the electronics section until they lock.
3.3 Settings
Adjust the output range using DIP switches
S1, S2 and S3 as shown in the tables or on the rating plate.
Input Output S1 S2 S3
1 X 1 2 3 4 5 1 2 3
0 ... ± 200 V 0 ... ± 10 V OFF OFF OFF OFF ON ON ON ON ON OFF
0 ... ± 200 V 0 ... ± 20 mA ON OFF OFF OFF ON ON ON OFF OFF OFF
5
4. Mounting
The universal isolators are mounted on standard TS 35 rails.
5. Electrical Connection
Terminal assignments
1 Do not connect
2 Do not connect
3 Input +
4 Input -
5 Output +
6 Output -
7 Power supply
8 Power supply
Wire cross-section max. 2,5 mm
2
Multi-wire connection max. 1 mm
2
(two wires with same cross-section)
AWG 30-12, tightening torque 0.7 Nm
Wiring has to be suitable for a temperature of min. 75 °C
Warning!
For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!
5.1 Power supply
22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz, 2.5 VA,
(overvoltage category II)
6
6. Dimensions
111
Fixed screw clamp terminals
Metal lock for fastening on top-hat rail
7
7. Declarations, Certificates and Approvals
CE marking
The EU Declaration of Conformity is included in the documentation.
The Statement of Conformity for ATEX Zone 2 apparatus is included in the documentation.
Open-type Process Control Equipment also listed
Proc. Contr. Eq. for Use in Haz. Loc.
File: E340287, E308146, E340288
GL
Certificate No. 42 843 - 02 HH
Environmental Category: D
Test Standard: Regulations of the Performance of Type Tests, Part 1
EN 61010-1
8. Order Information
Adjustable Device Order No.
Pluggable screw clamp terminals
P 27000 H1-S008
8
P 27000-S008 Universal Isolator
9. Technical Data
Input data
Voltage input
Overload
Voltage input
Output data
Output
Load
for output current
for output voltage
Offset error
Residual ripple
General data
Gain error
Temperature coefficient
2)
Cutoff frequency
Test voltage
Working voltage
3)
(basic insulation)
± 0 ... 200 V limited by 256 V suppressor diode, max. permissible continuous current ≤ 3 mA
0 ... ± 10 V, 0 ... ± 20 mA calibrated selection
≤12 V 1) (600 Ω at 20 mA)
≤10 mA (1 kΩ at 10 V)
20 µA / 10 mV approx. 20 mV rms
< 0.08 % meas. value typical additional error for AC (45 ... 65 Hz sinus)
0.05 % meas. value
< 50 ppm/K of final value approx. 20 kHz
5 kV~ input against output
4 kV~ output against power supply
1 kV~for overvoltage category II and pollution degree 2 to EN 61010-1
For applications with high working voltages, take precautions to prevent accidental contact and make sure that there is sufficient distance to adjacent devices or sufficient insulation between them.
9
Protection against electric shock
Construction
Protection
Weight
3)
EMC
4)
Surge withstand
Ambient temperature
Ambient conditions
Power supply
Protective separation to EN 61140 by reinforced insulation according to EN 61010-1 up to 600 V AC/DC across input and output for overvoltage category II and pollution degree 2, up to 300 V AC/DC across output and ower supply for overvoltage category II and pollution degree 2.
For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance to adjacent devices or sufficient insulation between them.
2004/108/EC
EN 61326
EN 61326/A1
5 kV, 1.2/50 μs, to IEC 255-4
Operation
Transport and storage
-10 to +70 °C
-40 to +85 °C
Stationary application, weather-protected
Relative air humidity 5 ... 95 %, no condensation
Barometric pressure: 70 ... 106 kPa, altitude up to 2000 m
Water or wind-driven precipitation (rain, snow, hail) excluded
22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz; 2.5 VA,
(overvoltage category II)
Modular housing with pluggable screw clamp terminals, see dimension drawing
IP 20 approx. 150 g
10
Explosion protection Europe:
USA:
Canada:
II 3G Ex nA IIC T4 Gc X
Class I Div.2 GRP A,B,C,D T4
Class I Zone 2 AEx nA IIC T4
Class I Zone 2 Ex nA IIC T4 X
Class I Div.2 GRP A,B,C,D T4
1) Higher output load on request
2) Average TC in specified operating temperature range -10 ˚C ... +70 ˚C.
3) cULus certification: Working voltage (basic insulation) up to 600 V, working voltage (reinforced insulation) up to 300 V across input and output, each for overvoltage category II and pollution degree 2
4) Slight deviations are possible while there is interference
11
Knick Elektronische Messgeräte
GmbH & Co. KG
Beuckestraße 22
D-14163 Berlin
Phone: +49 (0)30 - 801 91 - 0
Fax: +49 (0)30 - 801 91 - 200
Internet: http://www.knick.de
Email: [email protected]
12