Fire Detection Systems
Product Catalog 2011-2012
Valid from July 2011
Fire Detection Systems
ESSER FLEXS
TIKLAYIN
Content
1
General Details 3 - 6
1
Introduction3
Representative Offices of Honeywell Life Safety Austria
4
General Information
5-6
2
3
Control Panels
7 - 32
IQ8Control
System 8000
Extinguishing System
8 - 22
23 - 28
29 - 32
Power Supply 2
3
4
33 - 38
5
Power Supply Units
Voltage Converters
Batteries (rechargeable)
Display and Operating Units
4
LED/LCD Indicator Panel
Fire Brigade
39 - 46
7
40 - 41
42 - 46
8
47 - 50
Alarm Communications
51 - 60
10
52
53 - 54
55 - 57
58 - 60
11
Analogue Transmission Devices
ISDN Dialling Devices
Accessories
Alarm Receiver
7
6
Fire Service Key Box
5
6
34 - 35
36
37 - 38
Network Technology
9
12
61 - 71
13
essernet
62 - 66
Multiprotocol Gateway
67 - 70
IGIS-LOOP71
8
Management Systems
14
73 - 86
15
WINMAGplus
74 - 84
WINMAGLite85
Difference between WINMAGLite and WINMAGplus
86
9
Automatic Detectors
87 - 121
Series IQ8Quad (Intelligent Addressable)
Detectors for Hazardous Areas
Base Series IQ8Quad
Accessories
88 - 100
101 - 105
106
107 - 121
16
17
1
Content
10 Manual Call Points
Large Design - ABS
Large Design - Aluminium
Large Design - Accessories
Small Design - ABS
Special Design
123 - 146
124
128
130
135
143
-
127
129
134
142
146
11 esserbus Transponders
147 - 158
12 Wireless Component
159 - 166
13 Detectors for Special Applications
167 - 210
Flame and Heat Detectors
168 - 173
Air Duct Detectors
174 - 176
Line Heat Detectors
177 - 186
Line Smoke Detectors
187 - 192
Aspirating Smoke Detectors
193 - 209
Accessories210
14 Alarm Devices
211 - 234
IQ8Alarm
Conventional
Remote Indicators
212 - 222
223 - 231
232 - 234
15 Door Release System
Automatic Door Systems
Door Holding Magnets
16 Installation & Service
Installation Accessories
Housings
17 Appendix
235 - 244
236 - 237
238 - 244
245 - 252
245 - 250
251 - 252
253 - 272
Planning Guide for Loop Installation
Load Factor Calculation
Order Form WINMAG
255
Order Information for Alarm Signaling Devices IQ8Quad / IQ8Alarm
Order Information for Individual Combination of Languages
Additional Languages for Individual Combination
Order Form for Individual Combination of Languages
Order Form Multiprotocoll Gateway
261
Part Number Index
263
Index
266
2
www.hls-austria.com
-
-
253
254
256
257
258
259
260
262
265
272
1
Introduction
Dear business partners,
you are looking at your personal issue of our 2011 product catalog. We would be happy
if you could take the time to assure yourself of our comprehensive product range. Your
satisfaction has been our top priority ever since our company was founded. Because of
this, all changes and innovations made meet our basic principle to only offer products
of maximum quality at a good price-performance ratio to you.
2
The high level of customer satisfaction which we have maintained for years now is
represented by renowned references from all over the world such as:
4
3
5
6
7
Vnukovo Airport, Moscow, Russia • Sheraton Voyager Antalya Hotel, Turkey • Prague Motorway, Czech Republic
8
The success of these extraordinary projects is tied closely to your success. We would
therefore like to further extend our cooperation together with you under the motto
"Safety is a matter of partnership". Use this possibility of talking to us and tell us your
suggestions and wishes so we can build the future together in this more and more
difficult market environment.
9
Please visit our website www.hls-austria.com and find all information for downloading.
10
We are looking forward to our continued mutual success!
Your Honeywell Life Safety Austria Team
11
12
13
14
15
16
17
3
Representative Offices of Honeywell Life Safety Austria
Headquarters
Honeywell Life Safety Austria GmbH
Lemböckgasse 49
1230 Vienna, Austria
Phone:+43 1 600 6030
Fax: +43 1 600 6030-900
E-mail: [email protected]
Internet: www.hls-austria.com
Czech Republic / Slovakia
Representative Office of Honeywell Life Safety
Austria GmbH
V Parku 2326/18
148 00 Prague 4 - Chodov, Czech Republic
Phone: +420 242 442 280
Fax: +420 242 442-119
E-mail: [email protected]
Internet: www.hls-czech.com
Poland
Representative Office of Honeywell Life Safety
Austria GmbH
Ul.Marynarska 15, bud. New City
02-674 Warsaw, Poland
Phone: +48 22 313 09 70
Fax: +48 22 313 09 79
E-mail: [email protected]
Internet: www.hls-poland.com
Romania
Honeywell Life Safety Romania S.R.L.
Salcâmilor str. 2 bis
305500 Lugoj, Romania
Phone: +40 256 35 00 00
Fax: +40 256 35 49 53
E-mail: [email protected]
Internet: www.hls-romania.com
Russia
Representative Office of Honeywell Life Safety
Austria GmbH
8th floor, Kievskaya str., 7
121059 Moscow, Russia
Phone: +7 495 231 26 92
Fax: +7 495 795 08 81
E-mail: [email protected]
Internet: www.hls-russia.com
Ukraine
Representative Office of Honeywell Life Safety
Austria GmbH
Office Center „IRVA“, Block A
Radyscheva str. 10/14
03680 Kiev, Ukraine
Phone: +380 44 351 15 50
Fax: +380 44 351 15 51
E-mail: [email protected]
Internet: www.hls-russia.com
Turkey
Representative Office of Honeywell Life Safety
Austria GmbH
Bağdat Caddesi No: 418/A Akör Apt. D: 9
34740 Suadiye Kadıköy/Istanbul, Turkey
Phone: +90 216 410 61 41
Fax: +90 216 410 43 97
E-mail: [email protected]
Internet: www.hls-turkey.com
4
www.hls-austria.com
Honeywell Life Safety Romania S.R.L.
Floreasca Business Park
169A Calea Floreasca, Building A, 2nd Floor, District 1
014459 Bucharest, Romania
Phone: +40 31 224 36 10
Fax: +40 21 204 81 65
E-mail: [email protected]
Internet: www.hls-romania.com
Extensions
1
The list below provides a brief explanation of various extensions used in this product guide.
2
acc.
= according to
approx. =approximately
ARS
= aspirating detector
CCTV
= closed circuit TV
CPU
= central processing unit
CTC
= center to center
DB
=database
DFD
= series 9100
DIBT
= German Institut for
Technical Approvals
DIL
= dual in line
DIN0
= German Institut for
Standardization
DIP
= dual in parallel
DKC
= display keyboard card
DRS
= digital receiving station
DU
= Depth Unit
EDD
= series 9000
EDP
= Esser Data Protocol
EL
= Line voltage
EN
= European Norm
EOL resistor= end-of-line resistor
Ex
= explosion proof
FACP
= fire alarm control panel
FAS
= fire alarm system
FBF
= firepanel for Fire Brigade
FD = fire detection
FDC
= fire detection panel
FDOP
= fire brigade panel
FDS
= fire detection system
FSA
= door release system
HU
= used for 19 inch rack e.g. "6HU"
1 HU = 44.45mm
I/O
= input/ output
IC
= integrated circuit
IDS
= intruder detection system
IDT
= intelligent display terminal
IP
= ingress protection rating
IR
=infrared
LAN
= local area network
LCD
= liquid cristal display
LED
= light emitting diode
LF
= low frequency
LPCB
= Loss Prevention Certification
Board
LRS
= high sensitivity aspiration
detector
MCP
= manual call point
MFAB
= master box
MM
=micromodule
NC
= normally closed contact
NO
= normally open contact
OMF
= operating module front
PAM
= series 9200
pcb
= printed circuit board
pcs.
=pieces
PLC
= programmable logic control
PM
= delay and verify functions
POROM = programmable read only
memory
PTB
= National Institute of Natural
and Engineering Sciences
RAM
= random access memory
RIP
= remote indicating panel
ROR
= rate-of-rise heat detector
SHV
= smoke heat ventilation
module
SMD
= surface mounted
technology
SOC
= switch-on control
SZI
= single zone indicator
TAL
= technical alarm module
TM
= coincidence detection
USB
= universal serial bus
UV
=ultra-violet
VDE
= Association for Electrical,
Electronic and Information
Technologies
VdS
= Association of German
Property Insurance
Companies
VGA
= video graphics array
VPP
= voltage peak-peak
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
5
Abbreviations
=
=
=
List of contents which the part number includes
Information, important notice
such as special versions, dependencies etc.
Packing unit Notice regarding the packing unit:
1. The item will only be sold in packing unit.
2. The number of items, which have to be ordered, always refers to the number of packing unit rather than the number of single items.
3. The price stated in the catalogue is always the respective price for the packing unit. It is not the price for the
single item.
Example item number 701040 (spare glass pane):
Packing unit: 10 items. An order of 3 items, for instance, would be equivalent to an order of 3 packing units.
This would correspond to 30 items of spare glass pane, which have been ordered.
What happens, if the phase-out date of a product is reached?
1.We guarantee to supply you for up to five years if all related components are available and the legal regulations permit this.
2.Manufacturing-stop date is five years after the phase-out date. No matter whether we are able to manufacture the items, we
will stop manufacturing them.
3.After stopping manufacturing, as far as it is possible for us, we will try to repair the product for further two years.
4.As long as stock is available, the products can be ordered further with the same part number, as far as this is legally permissible.
5.As soon as the products are no longer available in our main-warehouse, we supply you with products of our service and repair
warehouse. In this case it can be a repaired product, however as good as new. Also here we must consider the actual legal
regulations.
Ingress Protection rating
Degrees of protection against solid foreign
objects indicated by the first characteristic
numeral
First characteristic brief numeral description:
0Non-protected
1
Protected against solid foreign
objects of 50 mm diameter and greater
2
Protected against solid foreign
objects of 12,5 mm diameter and greater
3
Protected against solid foreign
objects of 2,5 mm diameter and greater
4
Protected against solid foreign
objects of 1,0 mm diameter and greater
5Dust-protected
6Dust-tight
6
www.hls-austria.com
Degrees of protection against liquid foreign objects
indicated by the second characteristic numeral
Second characteristic brief numeral discription:
0Non-protected
1 Protected against vertically falling water
drops
2
Protected against vertically falling water
drops when enclosure tilted up to 15°
3
4
5
Protected against spraying water
6
Protected against powerful water jets
7
Protected against the effects of temporary
immersion in water
8
Protected against the effects of continuous
immersion in water
Protected against splashing water
Protected against water jets
1
2
3
4
5
6
7
8
9
10
Control Panels
IQ8Control
8-22
11
System 8000
23-28
Extinguishing System
29-32 12
13
14
15
16
17
7
Control Panels
IQ8Control
IQ8Control C / Intelligent Addressable
Features
• Max. two micromodules
• Max. two esserbus analog loop modules
• Short circuit and open circuit resistant loop opera­
tion
• Loop installation with I-Y(ST)Y 0.8 mm cable for a ​
maximum length of 3.5 km
• Up to 127 esserbus devices (fire detectors ​
•
•
•
•
•
•
•
•
•
•
•
•
•
•
respectively manual call points)/detector zones ​
per loop
Up to 32 esserbus transponders per loop/​
operation of wireless components (see chapter ​
10)
Operation types TM and PM as per DIN VDE 0833 ​
- 2 to avoid unwanted alarms being triggered
Fire brigade operating panel and alarm transmis­
sion unit interface on the peripheral module
Three common relays, freely programmable, ​
monitored, floating for up to 24 V DC/1A (on the ​
peripheral module)
TTY or RS 485, RS 232 interface
Integration in the short circuit and open circuit ​
resistant essernet network with up to 31 fire ​
detection panels depends on transmission rate
Connection to graphical supervisor WINMAG via ​
serial essernet interface (SEI)
Operating panel with alphanumerical display
4 x 40 backlit LCD display
Event memory for up to 10,000 events
All System 8000 micromodules are compatible
Printer interface for internal printer
Two batteries with monitoring circuit
Monitored input for external power supply unit
Additional features for powered loop
• Max. 2 analog powered loop modules
• BUS powered, synchronously controlled, acoustic ​
alarm signalling devices as per DIN EN 54-3 with ​
alarm tone as per DIN 33404
• Up to 48 powered loop base sounders (series ​
9200) per loop
• Up to 32 powered loop IQ8Alarm per loop
• Up to 48 IQ8Quad with alarm device per loop
Approval:
VdS, CNBOP, BOSEC
The IQ8Control C as an efficient fire alarm control panel for the property supervision of ​
small to mid-sized objects facilitates simultaneous detection, control and alarm signaling ​
both on the analogous ring as well as on the spur.
Within the multifunctional IQ8Control C panel, the operation type (powered-loop or non-​
powered-loop) can be selected via a jumper located on the control panel power supply unit.
Depending on which loop operation type has been selected, the respective loop module/​
modules are required.
Technical Data
Rated voltage
Rated frequency
Rated current
Quiescent current
Current consumtion for ext. devices
Battery capacity
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
CE certificate
230 V AC
50 ... 60 Hz
0.35 A (standard); 0,7 A (powered loop)
approx. 215 mA (basic configuration without operating ​
unit)
approx. 230 mA (basic configuration with operating ​
unit)
2 A
2 x 12 Ah, 2 x 24 Ah in extension housing
-5 °C ... 45 °C
-5 °C ... 50 °C
IP30
ABS, 10% glass fibre reinforced, V - 0
grey, similar to Pantone 538
approx. 6.5 kg
W: 450 mm H: 320 mm D: 185 mm
0786-CPD-20827
- The IQ8Control fire detection panels are fully compatible with FACP 8000 panels within ​
essernet applications
- FACP 8000 micromodules are also compatible with IQ8Control devices
- Housing form and colour comply with the FACP 8000 generation
- The IQ8Control panels can only be programmed with the tools 8000 software solution (part no. ​
789861) and the field bus interface (part no. 789862.10) or directly via USB with the RS-232 ​
interface (part no. 769828), with the field bus interface or the RS232 interface.
Combined with 808619 or 808619.10 FSA transponders, the control panel can be used to ​
control automatic door arrester systems in compliance with the German institute for ​
construction engineering (DIBt: Deutsches Institut für Bautechnik).
external equipment
12V DC
Fibre optic converter
essernet
Loop length max. 1 km
esserbus-PLus
Loop length max. 3.5 km
(with repeater max. 3 km)
IQ8Control C
IQ8Control C
Repeater
esserbus transponder
Management System
WINMAG
Connection example
8
www.hls-austria.com
Control Panels
IQ8Control
1
IQ8Control C Design and Order Diagram
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
9
Control Panels
Control Panels
808003
IQ8Control
¬qq$N­
Fire alarm panel IQ8Control C
Basic design.
1
The operating front must be ordered separately and is not included in the price.
Housing with standard rear panel and front frame for operating panel fronts, interface board, ​
power supply module, system software.
¬qrHU­
808139
Fire alarm panel IQ8Control C for 19" cabinet
As 808003 but 19" version (7 HU) for upright cabinet installation.
1
The operating front must be ordered separately and is not included in the price.
FACP 808003 IQ8Control C, including 19" installation frame and flat cable for 19" installation ​
750707.
10
www.hls-austria.com
Control Panels
IQ8Control
Accessories FACP IQ8Control C
1
789300
2
¬o~!]­
Battery extension housing
Extension housing for additional batteries.
1
Technical Data
Ambient temperature
Storage temperature
Type of protection
Housing
Weight
Dimensions
3
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30
ABS plastic, 10% glass fibre reinforced, V - 0
approx. 5 kg (without battery)
W: 450 mm H: 320 mm D: 185 mm
4
Batteries are not included and must be ordered separately.
5
Housing complete with battery rear panel, connecting cable for battery, mounting positions for 2 ​
x 12V/24Ah batteries. Neutral front and material for attaching to the existing panel housing, ​
battery connecting cables, 800 mm.
6
Assembling the housing parts IQ8Control
Take off the
4 standard covers.
Insert the
2 connecting elements.
7
Put the 2 housings
on top of each other
and push them together.
8
9
10
1.
2.
3.
11
¬o~"`­
Connection between the central housing and the extension housing
789301
12
Extension housing for batteries and SZI 192 detector zones
Technical Data
1
Quiescent current
Current consumption
Ambient temperature
Type of protection
Housing
Color
Weight
Dimensions
13
approx. 5 mA
1.5 mA when LED activated
-5 °C ... 45 °C
IP30
ABS plastic, 10% glass fibre reinforced, V - 0
grey, similar to Pantone 538
approx. 5.5 kg (without battery)
W: 450 mm H: 320 mm D: 185 mm
14
15
This housing cannot be used if an operating module front with single zone indicator unit for 64 ​
zones is already fitted. Batteries are not included and must be ordered separately.
A single zone indicator unit can only be used in connection with an operating module front.
16
Housing complete with battery rear panel, connecting cable for batteries, mounting positions for ​
2 x 12V/24Ah batteries, single zone indicator front for 192 detector zones and material for ​
attaching to the existing panel housing.
17
11
Control Panels
789302
¬o~#c­
IQ8Control
Extension housing for SZI 192 detector zones
The housing can be used to mount additional modules, e.g. an esserbus transponder.
1
Technical Data
Quiescent current
Current consumption
Ambient temperature
Type of protection
Housing
Color
Weight
Dimensions
approx. 5 mA
1.5 mA when LED activated
-5 °C ... 45 °C
IP30
ABS plastic, 10% glass fibre reinforced, V - 0
grey, similar to Pantone 538
approx. 5 kg
W: 450 mm H: 320 mm D: 185 mm
This housing cannot be used if an operating module front with single zone indicator unit for 64 ​
zones is already fitted. A SZI unit can only be used in combination with an operating module ​
front.
Housing complete with standard rear panel, single zone indicator front for 192 detector zones ​
and material for attaching to the existing panel housing.
12
www.hls-austria.com
Control Panels
IQ8Control
1
IQ8Control M / Intelligent Addressable
Features
Approval:
VdS, CNBOP, BOSEC
2
• Max. five micromodules, with peripheral module ​
VdS-system recognition: S 294050
• Max. seven esserbus analog loops, with extension ​
The IQ8Control M as an efficient fire alarm control panel for the property supervision of ​
mid-sized to large objects, facilitates simultaneous detection, control and alarm signalling ​
both on the analogous ring as well as on on the spur.
The loop operation type of the panel (powered-loop or non-powered-loop) can be selected ​
via a jumper located on the power supply card.
Depending on which loop operation type has been selected, the respective analog module/​
modules should be used.
772477
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
module 772476
Short circuit and open circuit tolerant loop opera­
tion
Loop installation with I-Y(ST)Y 0.8 mm cable for a ​
maximum length of 3.5 km
Up to 127 esserbus devices (fire detectors ​
respectively manual call points)/detector zones ​
per loop
Up to 32 esserbus transponders per loop/​
operation of wireless components (see chapter ​
10)
Operation types TM and PM as per DIN VDE 0833 ​
- 2 to avoid unwanted alarms being triggered
Fire brigade operating panel and transmission ​
interface on the peripheral module
Three common relays, freely programmable, ​
monitored, floating for up to 24 V DC/1A (on the ​
peripheral module)
TTY or RS485 or RS 232 interface
Integration in the short circuit and open circuit ​
resistant essernet network with up to 31 fire ​
detection panels depends on transmission rate
Connection to graphical supervisor WINMAG via ​
serial essernet interface (SEI)
Operating panel with alphanumerical display
4 x 40 backlit LCD display
Event memory for up to 10,000 events
All Systems 8000 micromodules are compatible
Printer interface for internal printer
Two batteries with monitoring circuit
Monitored input for external power supply unit
Additional features for powered loop
• Max. 6 analog powered loops and expandable up ​
to 124 power loops
• BUS supplied, synchronously controlled, acoustic ​
alarm signalling devices as per DIN EN 54 - 3 with ​
alarm tone as per DIN 33404
• Up to 48 powered loop base sounders (series ​
9200) per loop
• Up to 32 powered loop IQ8Alarm per loop
• Up to 48 IQ8Quad with alarm device per loop
3
4
5
Technical Data
Rated voltage
Rated frequency
Rated current
Output voltage
Quiescent current
Current consumtion for ext. devices
Battery capacity
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
CE certificate
230 V AC
50 ... 60 Hz
0.35 A (standard); 0,7 A (powered loop)
12 V DC
approx. 215 mA (basic configuration without operating ​
unit)
approx. 230 mA (basic configuration with operating ​
unit)
2 A
max. 2 x 12 V/24 Ah
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30
ABS, 10% glass fibre reinforced, V - 0
grey, similar to Pantone 538
approx. 11.5 kg
W: 450 mm H: 640 mm D: 185 mm
0786-CPD-20827
6
7
8
9
10
- The IQ8Control fire detection panels are fully compatible with FACP 8000 panels
- FACP 8000 micromodules are also compatible with IQ8Control devices
- Housing form and colour comply with the FACP 8000 generation
- The IQ8Control generation can only be programmed with the tools 8000 software solution ​(part
no. 789861) and the field bus interface (part no. 789862.10) or directly via USB with the ​RS-232
interface (part no. 769828), with the field bus interface or RS232 interface.
11
12
Combined with the 4 zone/2 relay-transponder 808619 or 808619.10, the control panel can be ​
used to control automatic door arrester systems in compliance with the German institute for ​
building technology (DIBt: Deutsches Institut für Bautechnik).
13
external equipment
12V DC
Fibre optic converter
14
essernet
Loop length max. 1 km
(with repeater max. 3 km)
esserbus-PLus
Loop length max. 3.5 km
IQ8Control C
Repeater
15
IQ8Control M
Managementsystem
WINMAG
16
esserbus transponder
17
Application example
13
Control Panels
IQ8Control M Design and Order Diagram (Basic Design)
14
www.hls-austria.com
IQ8Control
Control Panels
Control Panels
808004
IQ8Control
1
¬qq%Q­
2
FACP IQ8Control M
Basic design.
1
The operating front must be ordered separately and is not included in the price.
3
Housing with rear panel and front frame for operating panel fronts, interface board, power ​
supply module and system software.
4
5
¬qs4¤­
808219
FACP IQ8Control M for 19" cabinet
6
As 808004 but 19" version (7HU) for upright cabinet installation.
1
The operating front must be ordered separately and is not included in the price.
7
FACP IQ8Control M 808004, including 19" mounting frame and flat cable for 19" installation ​
750707.
8
9
10
11
12
13
14
15
16
17
15
Control Panels
IQ8Control
IQ8Control C/M
IQ8Control C/M Operating Fronts
Features
• alphanumerical display
• 4 x 40 backlit LCD display
ESSER - front (786001, 786101, 786301, 786401, 786501, 786801 and 786901) is also ​
available with the respective country specification - except the special versions. When ordering, ​
please fill in the last two digits with the specific language code.
The German version of the standard operating front C/M would have the part no. 7860-01.
For the Dutch version, the number would have to be changed to 7860-08.
(Not all variants are available in all languages. Please contact your sales representative for ​
details)
01 German (Germany)
02 English
03 Italian
04 Portuguese
05 Polish
06 Spanish
07 German (Austria)
08 Dutch
09 Czech
10 Russian
11 Hungarian
12 Danish
13 Swedish
14 Croatian
15 French (France)
16 Slovakian
17 French (Switzerland)
18 Romanian
20 Turkish
21 Greece
22 Flemish (Belgium - Dutch)
23 Walloon (Belgium - French)
25 Arabic / English
52 Chinese
¬o]#!­
786002
Operating module front - English
1
¬o^##­
786102
Operating front with SZI for 64 detector zones - English
1
16
www.hls-austria.com
Control Panels
¬oe#1­
IQ8Control
1
Operating front with printer, w/o take-up reel - English
786802
Printer included
2
1
3
4
¬o`#'­
Operating front for printer, with take-up reel - English
786302
5
No printer included
6
1
Accessories
784892 Printer kit with paper take-up reel
7
¬oa#)­
8
Operating module front with 1/4 VGA display - English
786402
9
1
10
11
¬ob#+­
12
Operating module front 1/4 VGA and SZI for 64 zones - English
786502
13
1
14
15
¬of#3­
16
Operating module front with 1/4 VGA display and printer - English
786902
Printer included
17
1
17
Control Panels
IQ8Control
¬o]!¤­
SZI front for 192 detector zones
786000
Technical Data
1
Quiescent current
Current consumption
approx. 5 mA
single zone indication: per actuated LED 1.5mA
Including insertable foils with country-specific versions
¬o^!¦­
Filler panel front, neutral for IQ8Control C/M
786100
1
¬oq~%­
19” rack mounting kit for SZI 192 detector zones
788093
7 HU for upright cabinet mounting.
1
Technical Data
Quiescent current
Current consumption
approx. 5 mA
1.5 mA per actuated LED
772445 mounting frame
786000 SZI front for 192 detector zones, including insertable foils with country-specific versions
18
www.hls-austria.com
Control Panels
IQ8Control
Control Panel Modules for IQ8Control C/M
1
772479
2
¬n9pX­
Peripheral module
1
The peripheral module contains a fire brigade operating panel interface as well as a alarm ​
transmission unit interface and three freely programmable, optionally monitored or up to ​
24V DC floating common relays. The peripheral module can only be used on system ​
terminal 1 of the control panel interface board.
3
Technical Data
Quiescent current
4
approx. 15 mA
Only one 772477/78/79 module can be plugged onto the interface board.
¬n9nR­
772477
5
Peripheral module with one additional micromodule slot
As 772479 but with one additional micromodule slot. The peripheral module can only be ​
used on system terminal 1 of the control panel interface board.
6
1
Technical Data
Quiescent current
7
approx. 15 mA (without micromodule)
Only one 772477/78/79 module can be plugged onto the basic module.
¬n9oU­
772478
8
Extension module with one additional micromodule slot
9
The extension module is plugged onto the interface board of the control panel. The exten­
sion module can only be used on system terminal 1 of the control panel interface board.
1
Technical Data
Quiescent current
10
approx. 5 mA (without micromodule)
Only one 772477/78/79 module can be plugged onto the interface board.
¬n9mO­
772476
11
Extension module with 3 additional micromodule slots
12
The extension module is plugged onto the interface board of the control panel. This exten­
sion module can be used on plug connectors 1 and 2 of the basic control panel module.
1
Technical Data
Quiescent current
13
approx. 10 mA (without micromodule)
The 772476 extension module can only be used in the IQ8Control C/M fire alarm panel.
14
15
16
17
19
Control Panels
IQ8Control
Accessories for IQ8Control C/M
¬oQI­
Printer kit with paper take-up reel for IQ8Control C/M
784892
40 characters, printer with fixed print head.
1
When the printer is installed in the FACP IQ8Control C, the battery case, including toroidal ​
transformer, must be replaced by the mounting rack. The batteries and the toroidal transformer ​
must be installed in an additional extension housing, either 789300 or 789301.
Mounting frame complete with Part No. 736234 plain text thermal printer including winder and ​
end-of-paper recognition.
Accessories
736235 Printer paper for printer 736233 / 736234
¬j_D¥­
Printer paper for printer 736233 / 736234
736235
Printer paper for part no. 736233 printer without paper take-up reel and for part no. ​
736234 printer with take-up reel.
1
Technical Data
Dimensions
L: 2500 mm W: 58 mm
¬o~$f­
Extension housing
789303
1
The standard extension housing can be used to mount additional modules, e.g. esserbus ​
transponders. In one housing can be installed up to 6 esserbus transponders (808613.10,
808613.20, 808613.30, 808614.10 and/or 808623) or 4 esserbus transponders
(808610.10 and/or 808611.10).
Technical Data
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30
ABS plastic, 10% glass fibre reinforced, V - 0
grey, similar to Pantone 538
approx. 5 kg
W: 450 mm H: 320 mm D: 185 mm
Housing complete with standard rear panel, neutral front and material for attaching to the ​
existing control panel housing.
Assembling the housing parts IQ8Control
Take off the
4 standard covers.
1.
Insert the
2 connecting elements.
2.
Connection between the central housing and the extension housing
20
www.hls-austria.com
Put the 2 housings
on top of each other
and push them together.
3.
Control Panels
772445
¬n9NY­
IQ8Control
1
Mounting frame 19" IQ8Control C/M
Mounting frame incl. installation material and 1,20 m flat cable
2
1
3
4
5
¬qQq'­
804880
Kit DCF77 radio time module for IQ8Control & FlexES control
1
6
Used in conjunction with the Kit DCF77 allows radio reception of the DCF77 time signal ​
(CET and CEST time). The DCF77 time signal is sent from a German central transmission ​
point in Frankfurt/Main and Mainflingen and can be received at a distance of up to approx. ​
2.000 km.
By connecting the Kit DCF77 to the fire alarm system IQ8Control or FlexES control, the ​
system time will be automatically set to this time signal. This applies to stand-alone fire ​
alarm control panel.
7
8
Each fire alarm control panel (FACP) or essernet network must only be connected to a single ​
DCF77 time master.
9
10
11
12
13
14
15
16
17
21
Control Panels
IQ8Control
Micromodules for IQ8Control C/M
¬oLs§/E1n­
784382.D0
Analog loop module
Single loop circuit module for up to 127 Series 9200/IQ8Quad intelligent fire detectors or ​
bus devices, divisible into 127 zones.
1
Technical Data
Quiescent current
¬qLs§/E1p­
804382.D0
approx. 25 mA
Analog loop module powered loop
1
Single loop circuit module for up to 127 bus devices. Series 9200/IQ8Quad intelligent fire ​
detectors and esserbus transponders (part no. 80xxxx) or addressable sounders and ​
powered loop base sounders.
Powered loop compatible only with IQ8Control.
¬oLv*­
784385
Master box interface module
Single master box interface module for activating and processing acknowledgement ​
signals from master boxes; programmable as constant or pulsed master box activation.
1
Technical Data
¬n1g-­
Quiescent current
771670
approx. 15 mA
Master box interface module
As 784385, but for potential-free triggering.
Technical Data
1
Quiescent current
¬oQK£­
784842
approx. 15 mA
RS 232/TTY serial interface module
Serial interface module with optional RS 232 or TTY typ, for operating external devices ​
such as external printers, printers, modems for remote diagnosis.
1
Technical Data
Quiescent current
¬ol?,­
787530
approx. 35 mA (RS 232)
approx. 55 mA (TTY)
4-relay module
1
4-relay module with freely programmable output functions, each of which can operate as ​
an NC or NO contact (not monitored) for potential-free activation.
Technical Data
Quiescent current
Contact load relay
¬[email protected]/­
787531
approx. 10 mA
max. 30 V DC / 1 A
3-relay module
3-relay module with output functions which can be programmed either as NC or NO ​
contacts, 3 x latching "monitored" relay outputs.
1
Technical Data
Quiescent current
Contact load relay
¬olA2­
787532
approx. 5 mA
max. 30 V DC / 1 A
3-relay common fault module
3-relay module with pre-set functions such as common fault, 2 x freely programmable ​
monitored relay outputs.
1
22
www.hls-austria.com
Technical Data
Quiescent current
Contact load relay
approx. 15 mA
max. 30 V DC / 1 A
Control Panels
System 8000
1
Accessories for System 8000 and IQ8
¬m|`F­
769163
2
Upright cabinet
With full view glass and swiveling lever lock (PHZ) for housing of the System 8000 and ​
IQ8Control as 19“ rackmount. Cabinet rack with welded 100 mm base, with drill holes for ​
floor installation.
Removable rear and side walls, cable inlet in top with bristles and cover plate. 40 HE ​
hinged frame for integration of operating unit and facing with dummy plates.
1
3
4
Technical Data
Weight
Dimensions
approx. 150 kg
W: 800 mm H: 2000 mm D: 600 mm
5
Upright cabinet not suitable for the releasing control equipment 788014, 788015, 788024, ​
788025.
6
Incl. 1 x 584925 door contact
¬m|aI­
769164
Upright cabinet including mounting
7
As 769163 but completely premounted at the factory for integrating a fire alarm control ​
panel.
¬kA-j­
8
Spare key 1D009 for FACP
743212
For upright cabinets 769163 and 769164.
9
Two keys
1
10
11
¬kANf­
743245
Lever lock - type 17 for key no. 801
12
Two keys and one cylinder lock.
13
1
14
¬m¦/*­
769914
15
Spare key 801 for FACP
16
For fire alarm panels 2001, IQ8Control C/M, 8000 M/C, 8007, 8008, for operating panel, ​
printer and housing.
1
Two keys.
17
23
Control Panels
743248
System 8000
¬kAQo­
Lever lock - type for key no. 901
Two keys and one cylinder lock.
1
¬m¦0-­
769915
Spare key 901 for FACP
For fire alarm panels 2001, IQ8Control C/M, 8000 C/M, 8008 for operating panel, printer ​
and housing.
1
Two keys.
¬kI?I­
744030
Dummy cover 19", 2 HU
For covering free installation space in upright cabinets and wall cabinets, 2 HU.
1
Technical Data
Material
Color
sheet steel
grey similar to Pantone 538
One height unit (HU) covers 44.45 mm.
¬kI<@­
744027
Dummy cover 19", 3 HU
As 744030, but 3 HU.
1
Technical Data
Color
24
www.hls-austria.com
grey similar to Pantone 538
Control Panels
744028
¬kI=C­
System 8000
1
Dummy cover 19", 5 HU
As 744030, but 5 HU.
2
1
3
4
¬kI>F­
744029
Dummy cover 19", 9 HU
5
As 744030, but 9 HU.
6
1
7
8
9
10
11
12
13
14
15
16
17
25
Control Panels
System 8000
Maintenance and Test Equipment
¬o¥^P­
789861
tools 8000 programming software
Convenient Windows programming software CD for programming the fire alarm panels ​
belonging to Series 8000 C/M, 8008, IQ8Control, Gateway, FlexES control extended
supplementary text in ​¼ VGA display and ABIGA.
For programming, the 789862.10 field bus interface is required.
System requirements:
- FACP 8000 C/M, FACP 8008 or IQ8Control C/M as of software version V2.20
- PC/Notebook as of Windows 98 SE, Vista and Windows 7, but no Windows NT (no USB
support)
- Recommended configuration: 128 MB RAM, 500 MHz CPU
This software is also to be used for the LCD panels 785101 and 785103.
¬o¥]§/21(­
789860.10
tools 8000 PLus equipment starter kit
Complete package for programming of the fire alarm control panels 8007, 8000C/M, 8008, ​
gateway, ABIGA and IQControl via PC or Notebook.
1
The field bus interface is used as a programming interface between the FACP and the PC/​
notebook.
Furthermore the field bus interface facilitates the direct connection of a ring bus to the ​
convenient monitoring of a finished installation and the elimination of possible cabling mistakes.
789861
789862.10
789863
789864
789866
Programming software for system 8000 and IQ8Control
Field bus and control panel interface PLus
USB cable
Serial connecting cable
Serial programming cable for USB field bus and panel interface for 8010
Accessories
BME2Z002 Switched-mode power supply with cylindrical plug
Control Panel
USB
Field bus interface
esserbus-PLus
Loop length max. 3,5 km
esserbus-transponder
Application example
26
www.hls-austria.com
Control Panels
789862.10
System 8000
¬o¥_§/21.­
1
Field bus interface PLus
1
Interface for the programming of the fire alarm control panels 8007, 8000C/M, 8008, ​
gateway, ABIGA and IQ8Control or for the direct field-side connection of a single installed ​
analog loop. With the optional switched-mode power supply BME2Z002, bus-supplied ​
alarm signaling equipment can be tested independently from the control panel via the ​
direct connection to the field bus interface 789862.10. (V1.12 or above of programming ​
software tools 8000 is required)
2
3
Technical Data
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
5 °C ... 45 °C
0 °C ... 50 °C
IP40
plastic, PS (Polystyrene)
white, similar to RAL 9010; grey, similar to RAL 7035
approx. 300 g
W: 68 mm H: 30 mm D: 135 mm
4
5
Connecting cables 789863, 789864 and 789866 are not included in delivery.
6
Windows NT does not support any USB interface. Therefore the use of the programming ​
software tools 8000 is possible under Windows NT only with the usage of programming ​
interface RS 232 (part no. 769828).
7
One interface and two 6-pin plugs.
Accessories
8
BME2Z002 Switched-mode power supply with cylindrical plug
9
USB
10
Power supply for bus supplied
alarm signalling devices
11
Field bus interface
EFI-Plus
12
esserbus-PLus
Loop length max. 3,5 km
esserbus-transponder
13
¬o¥`V­
Application example
789863
14
USB cable A/B for 789862 field bus & panel interface
For connecting service PC / laptop with the tools 8000 field bus and panel interface.
1
15
Technical Data
Cable length
1.8 m
16
17
27
Control Panels
System 8000
¬o¥c_­
Serial programming cable for USB field bus and panel interface for 8010
789866
Connecting lead for programming the extinguishing control panel 8010.
1
Fieldbus interface
USB
Connecting cable, Part-No. 789866
esserbus
Extinguishing panel 8010
¬o¥aY­
789864
Serial connecting cable for 789862
For connecting the field bus interface to panels 8007, 8000C/M, 8008, Gateway, ABIGA and ​
IQ8Control. With 4-pin special plug for the control panel.
1
Technical Data
Cable length
1.9 m
«CNF3[1138­
BME2Z002
Switched-mode power supply with cylindrical plug
Technical Data
1
28
www.hls-austria.com
Output voltage
12 V DC
Control Panels
Extinguishing System
1
Extinguishing System 8010 Wall Mounting
Approval:
VdS
2
1
Features
Control device with integrated fire detection module for an extinguishing area in accord­
ance with VdS 2496 and EN 12094-1. The extinguishing panel 8010 is an electronic control ​
device for extinguishing systems with integrated fire detection module, compatible with ​
Series 9200 and IQ8Quad detectors. It is additionally provided with respective detection ​
zones for manual alarm, post flooding and emergency stop as well as two zones for extin­
guishing system fault. Complex control functions can be realised by using the 13 control ​
groups (relays). Up to 8 extinguishing areas on the esserbus of the fire detection system ​
communication transponders (optional). Respectively max. 16 communication transpon­
ders per FACP 8000 C/M or IQ8Control 8000 or IQ8Control can be networked via the ​
808615
• 1 Extinguishing area for max. 1.600 m² acc. to ​
Technical Data
•
Rated voltage
Rated frequency
Rated current
Battery capacity
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
CE certificate
•
•
•
•
•
•
•
•
•
•
•
VdS
8 detector zones for up to 30 Series 9200 and ​
IQ8Quad automatic detectors each (for two-​
detector dependency up to 25 detectors)
1 zone for manual alarm
1 zone for emergency stop
1 zone for post flooding
1 zone for extinguishing system fault
1 zone for blocking extinguishing system
1 control input for buzzer OFF
1 control input for control panel reset
8 relays, monitored or floating 30V DC/2A
3 relays, floating 30V DC/2A
2 mains voltage relays, floating 230V AC/2A
All outputs are provided with fuses
3
4
5
230 V AC
50 ... 60 Hz
0.7 A
2 x 12 V / 24 Ah
-5 °C ... 45 °C
-10 °C ... 50
IP30
sheet steel approx. 1.25 mm
grey, similar to RAL 7035; blue, similar to RAL 5003
approx. 18.3 kg (without battery)
W: 488 mm H: 625 mm D: 210 mm
0786-CPD-20223
6
7
8
The free programming software can be downloaded from our website (downloads section).
9
Accessories
Indicating and operating unit 788400 (stand alone operation mode required), 788615 esserbus ​
communication transponder, control zone indicator and 788016 alarm counter.
10
11
esserbus
Loop length max. 3.5 km
Extinguishing
panel 8010
IQ8Control
Monitoring
Module
Extinguishing Agent
Tank
Valve
12
Selector
Valve
13
¬oq-g­
¬oq.j­
Application example
788012.40
788013.40
Extinguishing panel 8010, Series 4 w/o operating unit
14
15
Extinguishing panel 8010, Series 4 with operating unit - German
As 788012.40 but with 788400 operating unit.
16
17
29
Control Panels
Extinguishing System
Extinguishing Control Panel 8010 - Rack Mounting (3 HU)
Features
• 8 detector zones for up to 30 Series 9200 or ​
IQ8Quad automatic fire detectors per detector ​
zone (max. 25 detectors in two-detector depend­
ency)
• 1 detector zone manual alarm
• 1 detector zone emergency stop
• 1 detector zone post flooding
• 1 detector zone blocked extinguishing system
• 1 control input buzzer off
• 1 control input reset control panel
• 8 monitorable relays 30V DC /2A
• 3 floating relays 30V DC /2A
• 2 relays for mains voltage 230V (connection at the​
back)
• Each output is protected by fuses
• Electronically controlled exhauster control
Operating unit:
• 13 LED-indication with inscription fields for indic­
ating activated outputs
• Mechanical alarm counter
• LED display to indicate the detector zone status
• LED collective display
• Keypad can be intuitively handled
• Key operated switch for keypad activation
• Emergency current supply 2 batteries 12V/12Ah ​
(not supplied as standard)
Extinguishing panel as per EN 12094-1 for extinguishing zone control in compliance with ​
VdS 2496, with integrated fire detection unit and optional convenient operating and indic­
ating panel.
The slide-in concept enables space-saving, ergonomic integration into a 19-inch housing ​
for installation heights of only 3 height units (13.34 cm). Peripherals are connected at the ​
back of the housing via plug-in cable connections to accessible connection terminals, ​
allowing convenient installation within the housing before the insert is integrated. With the ​
communication transponder (part no. 808615), a maximum of eight extinguishing control ​
panels can be networked on one esserbus or powered loop in fire alarm systems FACP ​
8000 or IQ8Control. Via the programming interface plugged to the front, the extinguishing ​
panel settings can be adjusted to the specific requirements and information can be trans­
ferred for visulaising to the master fire alarm system via the loop.
Technical Data
Rated voltage
Rated frequency
Rated current
Battery capacity
Ambient temperature
Storage temperature
Type of protection
Housing
Dimensions
CE certificate
230 V AC
50 ... 60 Hz
0.7 A
2 x 12 V DC / 12 Ah
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30
sheet steel
W: 483 mm H: 132 mm D: 403 mm (without grip)
0786-CPD-20223
The use of heavy duty rails from the respective cabinet manufacturer is recommended for ​
installation in 19-inch upright cabinets.
Special
Connection module
incl. connection cable
(Part No. 788653
or 788654)
Fire alarm and
extinguishing
panel
No.1 to No.5
Power supply 230 V
Installation of multiple extinguishing panels in one upright cabinet
30
www.hls-austria.com
Control Panels
¬oq/§/51/HCE­
788014.40.GB
Extinguishing System
1
ECP 8010 Series 4 with operating unit - ESSER, English
Approval:
1
VdS
2
Accessories
788653 Terminal card for panel 8010 in 19-inch technology (3 HU), 1 m
788654 Terminal card for panel 8010 in 19-inch technology (3 HU), 2 m
¬oq/§/51/D[C­
¬oq/§/51/TL=­
¬oq/§/51/QM,­
¬oq/§/51/SP\­
¬oq0§/51]­
788014.40.CZ
3
4
ECP 8010 Series 4 with operating unit - ESSER, Czech
As 788014.40.GB, but Czech.
788014.40.SK
5
ECP 8010 Series 4 with operating unit - ESSER, Slovakian
As 788014.40.GB, but Slovakian.
788014.40.PL
6
ECP 8010 Series 4 with operating unit - ESSER, Polish
7
As 788014.40.GB, but Polish.
788014.40.RO
ECP 8010 Series 4 with operating unit - ESSER, Romanian
8
As 788014.40.GB, but Romanian.
788015.40
9
ECP 8010 Series 4 w/o operating unit - ESSER
Approval:
1
VdS
10
Accessories
788653 Terminal card for panel 8010 in 19-inch technology (3 HU), 1 m
788654 Terminal card for panel 8010 in 19-inch technology (3 HU), 2 m
11
12
Accessories
788653
¬owV©­
13
Terminal card for panel 8010
1
Length of plug-in connection cables: 1 m
14
2 x 50-pin connection cable 1m D-Sub50
1 x terminal card for top hat rail or C-rail mounting with D-Sub pin connectors
1 x terminal card for top hat rail or C-rail mounting with D-Sub multipoint connectors
15
¬owW#­
788654
16
Terminal card for panel 8010 in 19-inch technology, 2 m
As 788653, but plug-in connection cable with 2 m length.
17
1
31
Control Panels
Extinguishing System
Options for Extinguishing Control Panel 8010
¬ou!K­
Indicating and operating panel for extinguishing panel 8010 - ​German
788400
Integrated detector zone indication, can be set to status indication for control outputs. LED ​
for relevant extinguishing system function indication.
1
¬ou"N­
¬ou#Q­
¬ou%W­
¬oq1s­
Indicating and operating panel for extinguishing panel 8010 - English
788401
As 788400, but English.
1
788402
Indicating and operating panel for extinguishing panel 8010 - Polish
As 788400, but Polish.
Indicating and operating panel for extinguishing panel 8010 - Czech
788404
As 788400, but Czech.
788016
Panel 8010-option with control group indicator and alarm counter
1
Additional LEDs for indicating activated control outputs and mechanical alarm counter. The ​
indicators are mounted to the second recess of the 8010 releasing control equipment. The ​
PCB connection cable is connected to the 788400 indicating and operating panel.
Foil with German description
¬oq8!­
788023
Multiple-sector interface in housing
1
For the formation of multiple-sector control, up to four extinguishing panels 8010 can be ​
networked via a multiple-sector interface (part no. 788023).The cascading of a max. of 2 ​
multiple-sector interface is possible for multi-sector control of a max. of extinguishing ​
panels 8010.
next multisector interface
Control valve
32
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Power Supply
Power Supply Units
Voltage Converters
Batteries (rechargeable)
34-35
36
11
37-38 12
13
14
15
16
17
33
Power Supply
Power Supply Units
Power Supply - Housing Version
The power supply ZSP135-DR is dedicated to work in fire detection and building
automation ​systems. It is a source of guaranteed 24V voltage. It is manufactured as a wall
box with a ​lock. It has a space inside to mount two batteries. The controller protects the
internal b​ attery bank against too low discharge by means of the built-in disconnect device.
The p​ ower supply complies with the norm EN 54- 4/A1, A2 and EN 12101-10.
1
Application:
- components of fire alarm systems
- actuators of smoke extraction systems and fire and smoke dampers
- fire alarm control panels
- devices of industrial automation
Features
• light indication of the state of the power supply
• floating mode with temperature compensation
• equalize charging of the battery with the charging ​
•
•
•
•
•
•
•
current limitation
detection of low and high voltage of the battery
detection of a battery circuit break
electronic low voltage disconnect of the battery
monitoring of output fuses
continuous testing of the rectifier’s operation
monitoring of the internal temperature
visual and remote indication of alarm
960000.10.GB
Technical Data
Rated voltage
Output voltage
Operating temperature
230 V AC
24 V DC
-25°C ... 55°C (up to 75°C for max. 2h)
¬£!!§/HC+­
External power supply 2 A / 24 V DC / 17 Ah EN 54-4
Batteries for power supplies ZSP135-DR should be ordered separately.(compatible battery: ​
765741).
Technical Data
Output current
Battery capacity
Type of protection
Weight
960001.10.GB
max.2 A
max. 17 Ah
IP43
approx. 18 kg (incl. batteries)
¬£!"§/HC.­
External power supply 3 A / 24 V DC / 17 Ah EN54-4
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765741).
Technical Data
Output current
Battery capacity
Type of protection
Weight
960002.10.GB
max.3 A
max. 17 Ah
IP43
approx. 18 kg (incl. batteries)
¬£!#§/HC1­
External power supply 3 A / 24 V DC / 28 Ah EN 54-4
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765751).
Technical Data
Output current
Battery capacity
Type of protection
Weight
34
www.hls-austria.com
max.3 A
max. 28 Ah
IP43
approx. 28.3 kg (incl. batteries)
Power Supply
960003.10.GB
¬£!$§/HC4­
Power Supply Units
1
External power supply 5 A / 24 V DC / 17 Ah EN 54-4
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765741)
2
Technical Data
Output current
Battery capacity
Type of protection
Weight
960004.10.GB
max.5 A
max. 17 Ah
IP43
approx. 18 kg (incl. batteries)
3
4
¬£!%§/HC7­
External power supply 5 A / 24 V DC / 28 Ah EN 54-4
5
Batteries for power supplies ZSP135-DR should be ordered separately. (compatible
battery: ​765751)
Technical Data
Output current
Battery capacity
Type of protection
Weight
960005.10.GB
6
max.5 A
max. 28 Ah
IP43
approx. 28.3 kg (incl. batteries)
7
¬£!&§/HC:­
8
External power supply 5 A / 24 V DC / 40 Ah EN 54-4
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765752)
9
Technical Data
Output current
Battery capacity
Type of protection
Weight
960006.10.GB
10
max.5 A
max. 40 Ah
IP43
approx. 42.3 kg (incl. batteries)
11
¬£!'§/HC=­
External power supply 7 A / 24 V DC / 28 Ah EN 54-4
12
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765751)
13
Technical Data
Output current
Battery capacity
Type of protection
Weight
960007.10.GB
max.7 A
max. 28 Ah
IP43
approx. 28.3 kg (incl. batteries)
14
¬£!(§/[email protected]­
15
External power supply 7 A / 24 V DC / 40 Ah EN 54-4
16
Batteries for power supplies ZSP135-DR should be ordered separately.
(compatible battery: 765752)
Technical Data
Output current
Battery capacity
Type of protection
Weight
17
max.7 A
max. 40 Ah
IP43
approx. 42.3 kg (incl. batteries)
35
Power Supply
781335
¬o.D&­
Voltage Converters
DC / DC converter 12 V / 24 V DC
Approval:
VdS
This converter generates 24 V as power supply for special detectors. The input voltage of ​
12 V is taken from the fire alarm control panel or an external 12 V power supply. Mounted ​
inside the FACP (mounting kit 788605), this module can supply up to 4 special detectors ​
with a maximum current of 125 mA each or 1 special detector with 500 mA. This module ​
can be integrated in cabinets 120240, 788600 and 788601. Please pay attention to the ​
primary current consumption (12 V) in case of mains failure.
1
Technical Data
Operating voltage
Output voltage
Output current
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions pre-text
Features
• Each output is separately fused
¬o.E)­
781336
9 ... 15 V DC
24 V DC ± 10%
max. 500 mA (4 x 125 mA)
-10 °C ... 50 °C
-15 °C ... 55 °C
IP40 (housing)
approx. 150 g
DC / DC converter output voltage
Approval:
VdS
This converter generates 12 V as "electrically isolated" power supply for one special ​
detector. The input voltage of 12 V is taken from the fire alarm control panel or an external ​
power supply. This module can be integrated in cabinets 120240, 788600, 788601, and ​
788603. Please pay attention to the primary current consumption (12 V) in case of mains ​
failure.
1
Technical Data
Features
• Direct current potentials are electrically isolated
• Voltage interface, for instance, for operating ​
transponders connected to a extinguishing control ​
panel 8010 Series 3 configured for 12 V DC oper­
ation
• Suitable for max 1.5 mm² connection terminals
• Short circuit resilient
Operating voltage
Output voltage
Output current
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions pre-text
The module can also be used in in explosion zones for the galvanic separation of the esserbus ​
voltage supply.
¬o.F,­
781337
10 ... 28 V DC
12 V DC ± 10%
max. 800 mA
-10 °C ... 50 °C
-15 °C ... 55 °C
IP40 (housing)
approx. 70 g
DC / DC converter output voltage 24 V DC
Approval:
1
VdS
This converter generates 24 V as power supply for one special detector. The input voltage ​
of 12 V is taken from the fire alarm control panel or an external power supply. This module ​
can be integrated in cabinets 120240, 788600, 788601, and 788603. Please pay attention ​
to the primary current consumption (12 V) in case of mains failure.
Technical Data
Features
• Direct current potentials are electrically isolated
• Suitable for max 1.5 mm² connection terminals
• Short circuit resilient
36
www.hls-austria.com
Operating voltage
Output voltage
Output current
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions pre-text
10 ... 28 V DC
24 V DC ± 10%
max. 400 mA
-10 °C ... 50 °C
-15 °C ... 55 °C
IP40 (housing)
approx. 70 g
Power Supply
Batteries (rechargeable)
1
The listed lead storage accumulators are maintenance-free, sealed electrolyte batteries. ​
They are relatively position-independent (should not be charged upside-down), deep-​
cycled, cycle-resistant and long-lasting (4 to 5 years). Charge voltage at an ambient ​
temperature of +20°C: 12 V DC (6 x 2.3 V per cell) 13.8 volts, this can be subject to toler­
ances.
2
The battery technical data sheets can be made available via the KBC on request or option­
ally can be seen via the download area on the Internet.
3
The batteries comply with the VDE 0833-1 regulations for hazard alarm systems and are VdS ​
approved.
According to the VdS guidelines, the batteries must be replaced every four years. This is not the ​
case if the approval certificate contains other information.
Please note that batteries must be obtained from the same manufacturer with the same ​
manufacturing date and the same capacity.
018001
018002
018004
018011
4
¬"q"`­
¬"q#c­
¬"q%i­
¬"q,~­
5
Battery 12 V DC / 1.2 Ah capacity
6
Battery 12 V DC / 2.1 Ah capacity
7
Battery 12 V DC / 7 Ah capacity
8
Battery 12 V DC / 12 Ah capacity
9
2 x Fast-On Adapters from 6.3 mm to 4.3 mm
018006
¬"q'o­
10
Battery 12 V DC / 24 Ah capacity
2 x Fast-On Adapters from M6 to 6.3 mm each 2 x M5 hexagon head cap screws, washers and ​
snap rings.
018007
11
¬"q(r­
Battery 12 V DC / 15 Ah capacity
12
2 x Fast-On Adapters from M6 to 6.3mm each 2 x M5 hexagon head cap screws, washers and ​
snap rings.
018009
¬"q)u­
13
Battery 12 V DC / 38 Ah capacity
14
2 x Fast-On Adapters from M6 to 6.3mm each 2 x M6 hexagon head cap screws, 4 x washers ​
and snap rings.
018010
¬"q+­
15
Battery 12V DC / 65 Ah capacity
2 x Fast-On Adapters from M6 to 6.3mm each 2 x M6 hexagon head cap screws, 4 x washers ​
and snap rings.
16
17
37
Power Supply
Accessories
785753
Batteries (rechargeable)
¬oZVM­
Accumulator / battery kit
Terminals for the connection of batteries with a minimum capacity of 12 Ah.
1
¬"qT(­
018051
9 V alkaline-manganese battery
1
¬qX¤h­
805597
3.6V lithium battery
1
4 lithium batteries for use in wireless detector base (part no. 805593.10), wireless gateway ​
for detectors (part no. 805594.10) and wireless universal interface (part no. 805601.10/​
805602.10).
4 pcs
38
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Display and Operating Units
LED Indicator Panel
40-41
Fire Brigade
42-46
11
12
13
14
15
16
17
39
Display and Operating Units
¬mP?­
764790
LED Indicator Panel
Standard LED remote indicator panel - ESSER
Approval:
1
VdS
Additional indicator for up to 32 alarm, trouble or collective signals. Connection via an ​
integrated 32-pin terminal strip. The indicator is controlled via relay contacts or semicon­
ductor outputs with positive-guided contacts in the hazard detection system. With key for ​
lamp testing, integrated buzzer and easy-to-maintain terminal card. Elegant plastic ​
housing for surface mounting.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Display
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
10 ... 15 V DC
approx. 1 mA
approx.380 mA (incl. 32 LED & buzzer)
32 LED, red
max. 1.5mm²
-5 °C ... 50 °C
-25 °C ... 75 °C
≤ 95% (w/o condensation)
IP40
ABS plastic
white, similar to RAL 9003; front blue, similar to RAL ​
5003
approx. 1000 g
W: 270 mm H: 221 mm D: 71 mm
This indicator panel is not suitable for application as an initial warning device for the fire brigade.
¬qP|F­
804791
Loop LED remote indicator panel for 32 messages - ESSER
Approval:
1
VdS
As 764790 but with integrated and wired esserbus transponder 32 LED's for operation as a ​
remote indicating panel for the esserbus. For connection to the esserbus and powered loop ​
in fire alarm systems 8000 and IQ8Control.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Display
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
10 ... 15 V DC
approx. 1 mA
approx.380 mA (incl. 32 LED & buzzer)
32 LED, red
1.5 mm²
-5 °C ... 50 °C
-25 °C ... 75 °C
≤ 95% (w/o condensation)
IP40
ABS plastic
white, similar to RAL 9003; front blue, similar to RAL ​
5003
approx. 1000 g
W: 270 mm H: 221 mm D: 71 mm
Isolator (part no. 788612) not included, please order separately.
This indicator panel is not suitable for application as an initial warning device for the fire brigade.
40
www.hls-austria.com
Display and Operating Units
¬oT$y­
1
LCD indicator panel - ESSER, German
785103
The LCD indicator panel 785103 is used as an add-on device for the remote display of ​
FACP status information of the System 8000 IQ8Control relating to detectors and detector ​
zones.
Event messages are displayed via LED collective indicators and on the 2-line LCD display ​
with the associated detector zone number and a programmable additional text. Each ​
message is signalled via the built-in buzzer. The buzzer can be acknowledged by pressing a ​
button.
Up to 31 LCD indicator panels can be operated on an RS 485 bus, either directly on the RS ​
485 interface of the basic card of FACP 8007/8000C/8000M/IQ8Control or using a ​common
1
Features
• Display of zone and detector status information
• of the FACP with additional text
• Event memory for 200 messages
• Free programming up to a max. of 4,000 addi­
•
•
•
•
•
•
LCD Indicator Panel
tional texts, each with 2 x 20 characters
Sequential message interrogation via scroll keys
Monitoring of the serial interface
Internal buzzer, can be switched off via key
Function test of the display elements
Potential-free relay, programmable for the
modes deactivated, fault, intermittent operation, ​
ON-OFF operation
2
3
4
RS 485 converter (e.g. RS 232/RS 485 converter 764852) on another serial interface (e.g. ​
RS 232). In connection with panel 8008, only possible with RS 232/TTY micromodule ​
(784842) and RS 232/RS 485 converter (764852).
The additional texts are programmed using the tools 8000 software package and a service ​
PC connected via the 769862.10 programming interface.
5
Technical Data
Operating voltage
Quiescent current
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
6
8.5 ... 14 V DC
approx. 30 mA
30 V DC / 1A
potential free
0 °C ... 45 °C
0 °C ... 50 °C
IP30
plastic (ABS)
white, similar to RAL 9001
approx. 750 g
W: 206 mm H: 177 mm D: 48.5 mm
7
8
9
This indicator panel cannot be used as an initial warning device for the fire brigade.
785101
¬oT"s­
¬oT(§­
¬oT*$­
¬oT.0­
¬oT06­
10
LCD indicator panel - ESSER, English
As 785103, but without relay output. With English lettering.
785107
11
LCD indicator panel - ESSER, Polish
As 785103, but without relay output. Wirh Polish lettering.
785109
785113
12
LCD-Indicator Panel - ESSER, Czech
As 785103, but without relay output. With Czech lettering.
13
LCD indicator panel - ESSER, Hungarian
14
As 785103, but without relay output. With Hungarian lettering.
785115
15
LCD indicator panel - ESSER, Turkish
As 785103, but without relay output. With Turkish lettering.
16
17
41
Display and Operating Units
Fire Brigade
Fire Brigade Operating Panels
¬oP+¨­
784710
Fire brigade operating panel - Germany
Approval:
1
VdS
The fire department operating unit (in accordance with DIN 14661) is an additional device ​
for fire detection systems that contains transmission units to the fire department. The ​
essential display and operating elements of the fire alarm control panel are located on the ​
fire department operating unit (FDOU). The fire department can handle all necessary alarm ​
measures via the FDOU – so they do not need any special introduction to the control panel.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
10.5 ... 30 V DC
approx. 18 mA
approx.75 mA
0 °C ... 50
-10 °C ... 60
IP30
sheet steel
grey, similar to RAL 7032
approx. 3.4 kg
W: 255 mm H: 185 mm D: 58 mm
This fire department operating unit is not compatible with the FlexES control!
The fire brigade operating panel is supplied without locking cylinder (DIN 18252). It should be ​
acquired in accordance with the guidelines provided by the regional fire brigade.
¬mQ37­
764818
Fire brigade operating panel (FBF-Ö) - Austria
1
Fire brigade operating panel in compliance with ÖNORM F 3031 (2004)
- Plain text display with 2 lines and 16 characters for each line, illuminated
- 3 signals can be collectively indicated per LED (in operation, alarm, fault / deactivation)
- 2 optional status LED (BFS extinguishing system actuation)
- 3 buttons for FACP feedback
- Direct programming at the fire brigade operating panel via serial interface
- The additional text is displayed when using the shortcut deactivation + fault.
Technical Data
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
10.5 ... 30 V DC
50 mA (with lighting)
40 mA (w/o lighting)
0 °C ... 50
-10 °C ... 60
IP30
sheet steel
red, similar to RAL 3000
approx. 2.5 kg
W: 205 mm H: 300 mm D: 60 mm
This fire department operating unit is not compatible with the FlexES control!
42
www.hls-austria.com
Display and Operating Units
Fire Brigade
1
LCD Indicator Panels
¬oPL¤­
784743
2
Fire department indicating panel FAT3000
Approval:
1
ser.- IF
UB
ESPA 4.4.4
RS 232
Telephone system
or
Pager
FACP
VdS
Microprocessor-controlled fire department indicating panel in compliance with DIN 14662 ​
as an additional indicator for fire alarm panels. Serial connection to the fire alarm panel via ​
variable interfaces TTY, DUAL RS 485, RS232 and ESPA 4.4.4 (on board), conventional a​ nd
redundant activation, plain text display with 4 x 20 characters, collective LED indication ​
(alarm, trouble, deactivation). Simple handling with 4 buttons (buzzer OFF/level/scroll ​
buttons). Additional text (> 5000 texts) can be programmed using a PC with serial interface ​
connection, event memory, redundancy via loop structure for up to 16 FAT, power supply ​
and signalling pathway are monitored to prevent short or open circuits, full functional ​
range during breakdown of one circuit. The ESPA interface enables direct connection of ​
telecommunication and paging systems.
3
Technical Data
6
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
4
5
8 ... 30 V DC
approx. 65 mA
approx.125 mA
0 °C ... 50 °C
-10 °C ... 60 °C
IP30
sheet steel
grey, similar to RAL 7032
approx. 3.5 kg
W: 255 mm H: 185 mm D: 58 mm
7
8
9
The module can only be used when combined with a System 8000 or IQ8Control fire alarm ​
panel.
Programming software "FatProgWin" is included.
10
¬oPL§/QM?­
¬oPL§/D[S­
¬oPM§­
784743.PL
Fire department indicating panel FAT3000 - Polish
784743.CZ
As 784743, but Polish.
11
Fire department indicating panel FAT3000 - Czech
12
As 784743, but Czech.
784744
13
Adapter module ADP-N3E
1
Microprocessor-controlled module for installation in System 8000 or IQ8Control fire alarm ​
panels. In compliance with DIN 14675, the TTY interface can be used for redundant trans­
mission when the adaptor is connected and when the fire department indicating panel ​
FAT3000 is used for initially informing the fire department. Additional text (> 4000 texts) ​
can be programmed using a PC with serial interface connection.
14
15
Technical Data
Features
• Inout: TTY from the internal FACP interface
• Output: DUAL RS 485 to the FAT interface
Operating voltage
Quiescent current @ 12 V DC
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Weight
Dimensions
8 ... 30 V DC
approx. 30 mA
30 V DC/1 A
max 2 x 0.8 mm²
0 °C ... 50 °C
-10 °C ... 60 °C
approx. 100 g
W: 80 mm H: 150 mm D: 30 mm
16
17
The top hat rail module (part no. 788652) and the Module housing for snap-on mounting rail ​
(part no. 788603.10) can be used for installation. The interface is compatible with FAT3000 ​
(784743). Power is supplied by the fire alarm panel or an external power supply unit. Maximum ​
data line length: 800 m.
43
Display and Operating Units
Fire Brigade
¬oPCg­
Adapter module ADP-N3S
784734
1
Same as 784744, but for the integration of another fire detection system into an existing ​
redundant FAT 3000 bus in an ADP-N3E adaptor module. Unlike the ADP-N3E, the ADP-​
N3S does not provide power supply for redundant operation.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Weight
Dimensions
8 ... 30 V DC
approx. 40 mA
30 V DC/1 A
max 2 x 0.8 mm²
0 °C ... 50 °C
-10 °C ... 60 °C
approx. 100 g
W: 80 mm H: 150 mm D: 30 mm
¬oPV9­
Adapter module ADP-PRS-422
784753
1
Additional module for connecting a paging system to a Series 8000 / IQ8Control fire alarm ​
system with ADP-N3E. To connect the paging system via an electrically isolated RS232 ​
interface, an ADP-PRS-422 is used.
This adapter is not compatible with the FlexES control!
RS 232, max.
line length
15 m
FACP with adapter pcb
Part No. 784744
RS 422, max.
line length
1.000 m
Nurse call
system
Adapter module ADP- PRS-422
Part No. 784753
¬oPW<­
Connection example
Adapter module ADP-PRS-232
784754
1
The adapter module is an additional module suitable for electrically isolated connection of a​
paging system to a FAT 3000. The FAT 3000 programming interface (RS232 terminal) is ​
used for communication with the paging system. If an electrically isolated connection ​
between the FAT and the paging system is required, an ADP-PRS-232 must be used addi­
tionally.
The ADP PRS-422 module can also be used to connect a PC to the serial interface 784847.
RS 232, max.
line length
15 m
Fire department
indicating panel
FAT3000 Part No. 784743
Connection example
44
www.hls-austria.com
RS 232, max.
line length
15 m
Adapter module
ADP- PRS-232
Part No. 784754
Nurse call
system
Display and Operating Units
Fire Brigade
1
Plain Text Indicator and Operating Panels
¬oP:L­
2
FB inform./operating system, A4 horizonal, individual ​locking - German
784725
1
Sheet steel housing with two leaves for surface mount or flush mount installation with ​
central leaf opening for both door leaves. The right-hand housing door can be individually ​
opened by means of a built-in CL1 lock. Door opening through fire brigade locking ​
(suitable for half profile cylinder installation). In the left-hand half of the housing, a 784743 ​
fire service indicator panel and a fire service operating panel 784710 are installed. The ​
housing is designed for receiving a transmission unit or a manual call point. The fire ​
service indicator panel is actuated via the serial interface in the control panel. The fireser­
vice operating panel is connected to the control panel interface. A maximum of 2 x 100 ​
DIN A4 / horizonal layout fire brigade route maps can be integrated.
3
4
5
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
10 ... 30 V DC
approx. 50 mA
approx.180 mA
0 °C ... 50 °C
-10 °C ... 60 °C
IP30
sheet steel
red, similar to RAL 3000
approx. 15 kg
W: 710 mm H: 560 mm D: 100 mm
6
7
8
Only in combination with the System 8000, IQ8Control fire detection panels. For redundant ​
operation, redundancy module ADP-N3E (Part No. 784744) is required.
9
Double-leaf sheet steel housing
Fire service indicating panel 784743
Fire service operating panel 784710
10
¬oP:§/QMp­
¬oP;O­
784725.PL
FB inform./operating system, A4 horizonal, individual ​locking - Polish
784726
As 784726, but Polish.
11
FB inform./operating system, A3 horizonal, individual ​locking - German
12
As 784725 but for a maximum of 80 DIN A3 fire brigade route maps (transverse).
1
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
13
10 ... 30 V DC
approx. 50 mA
approx.180 mA
0 °C ... 50 °C
-10 °C ... 60 °C
IP30
sheet steel
red, similar to RAL 3000
approx. 17 kg
W: 830 mm H: 560 mm D: 100 mm
14
15
16
Only in combination with System 8000 and IQ8Control fire alarm panels.
For redundant operation, the redundancy module ADP-N3E (Part No. 784744) is required.
784726.PL
¬oP;§/QMs­
17
FB inform./operating system, A3 horizonal, individual ​locking - Polish
As 784726, but Polish.
45
Display and Operating Units
Fire Brigade
Accessories
¬mQ£S­
Emergency file depot, DIN A4 horizontal for 10 pcs. routing c
​ ards - German
764896
1
On the back of every emergency file depot are 4 holes and on the front side 4 bracket ​
hooks. For the installation on any underground are to set out 4 flat head screws (max. ​
4mm Ø). The first emergency file depot is hooked up on the screws. Every new emergency ​
file depot is mounted to the four latches and snaps in behind a metal lug 8see example of ​
use). Each single emergency file deposit is mounted end-stackable on the last one so that ​
the required emergency file number can be selected on the spot.
Technical Data
Color
Weight
Dimensions
red, similar to RAL 3000
approx. 730 g
W: 310 mm H: 212 mm D: 12 mm
¬[email protected]^­
Application example with three staggered emergency file deposits.
784731
Route map housing for DIN-A3 expansion
Sheet steel housing for surface or flush mounting. Option to open door through fire ​
department access lock: prepared for semi-cylinder insertion.
1
1 folder for 100 fire brigade route maps, A3
Door labeling: “Feuerwehrlaufkarten”
¬oPAa­
784732
Route map housing for DIN-A4 expansion
Sheet steel housing for surface or flush mounting. Option to open door through fire ​
department access lock: prepared for semi-cylinder insertion.
1
2 folder for 100 fire brigade route maps, A4
Door labeling: “Feuerwehrlaufkarten”
46
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Emergency Key Box
Fire Service Key Box
48-50
11
12
13
14
15
16
17
47
Emergency Key Box
Fire Service Key Box
For locking type information, please refer to the technical activation requirements provided by ​
the respective fire brigade.
¬oXyK­
785588
Fire service key box FSKB type 2003
Approval:
VdS
The fire service key box type 2003 is designed and approved in compliance with the VdS ​
Loss Prevention GmbH guidelines. It serves as a anti-theft device for forgery proof key ​
storage. When an alarm is triggered by a fire detection system (FDS) or an intrusion detec­
tion system (IDS), the outer door of the FSKB is released for opening after an acknowledg­
ment signal has been sent from the transmission unit. Flush mounted installation, opera­
tion and maintenance must comply with the VdS guidelines. The FSKB is provided with a ​
convertible lock for fire brigade locking.
1
Technical Data
Features
• Improved removal mechanism
• Built-in voltage converter for 12 / 24V operation
Operating voltage
Current consumption @ 12 V DC
Current consumption @ 24 V DC
Type of protection
Weight
Dimensions
12 ... 24 V DC
approx. 330 mA
approx. 150 mA
IP44
approx. 14 kg
W: 190 mm H: 170 mm D: 157 mm
Convertible lock and frame plate
¬oXzN­
785589
Fire service key box FSKB type 2003 PZ
As 785588 but prepared for profiled cylinder integration on site.
785590
Fire service key box type 2003 with tamper protection
1
Fire department key depository (FDKD) according to DIN 14675 Class 3 VdS-approved. ​
The all-round tamper protection facilitates protection from unauthorized access.
Keys easy to reach due to innovative swivel mechanism of the key depository. The modular ​
design facilitates quick implementation of maintenance. All modules are equipped with ​
plug connectors and therefore no welding is necessary on site. 12 or 24 V operation via ​
integrated voltage converter.
The key depository is already pre-installed when ordered in combination with corres­
ponding column.
Technical Data
Operating voltage
Weight
Dimensions
12 ... 24 V DC
approx. 14 kg
W: 190 mm H: 170 mm D: 157 mm
Inner door including KRUSE VdS "switch lock" (G 10 50 01), frame plate, mounting flange, 10 m ​
connection cable, auxiliary cylinder for key depository KRUSE key seal, heavy-duty dowel and ​
mounting instructions.
¬oSo#­
785078
Key box adapter SDA 3000
Approval:
1
VdS
Adapter for connecting a fire service key box FSD 2000/FSD 2000B/FSD Typ 2003 to a fire ​
alarm control panel.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Connection terminal
Type of protection
Dimensions
48
www.hls-austria.com
10 ... 42 V DC
approx. 35 mA
max. 1.5 mm²
IP30
W: 150 mm H: 180 mm D: 45 mm
Emergency Key Box
784790
¬oPA­
Fire Service Key Box
1
Release element PZ
Approval:
1
VdS
2
The release element (FSE) serves as an additional unlocking element for opening the fire ​
service key box via fire alarms manually actuated by the fire brigade, e.g. for fire or ​
flooding caused by a burst pipe. Suitable for flush mounting or installation in columns, for ​
integration of a 17mm profiled cylinder with a length of 35mm including a 10m connection ​
line.
3
Technical Data
Dimensions
¬oP|D­
784791
4
W: 80 mm H: 80 mm D: 70 mm
Release element K
Approval:
1
5
VdS
The release element (FSE) serves as an additional unlocking element for opening the fire ​
service key box via fire alarms manually actuated by the fire brigade, e.g. for fire or ​
flooding caused by a burst pipe. Fully provided with special fire brigade locking cylinder ​
including cover escutcheon with dust protection plate, for flush mounted installation.
6
7
Technical Data
Rosette
Dimensions
¬oXW­
785592
44 mm
Ø: 38 mm D: 80 mm
8
Stainless steel column for FSKB type 2003
1
Stainless steel column for type 2003 fire service key box installation including standard ​
frame plate. Rain protection cover, flash lamp as well as fixing for release element installa­
tion (FSE, FSE-PZ) or key-operated switch are optionally available.
9
Technical Data
10
Housing
Weight
Dimensions
sheet steel
approx. 30 kg (only column)
approx. 46 kg (incl. FSD)
W: 350 mm H: 1295 mm D: 237 mm
11
1x FSKB column
1x cover
1x fixing plate
4x threaded bolt M12 x 1.240mm
8x nuts M12
785591
12
13
Stainless steel column with cover monitoring
1
Quick mounting hollow column with cover monitoring for Fire Department Key Depository ​
2003 with all-round tamper protection.
In accordance with DIN 14675 following the VdS. To be used in difficult installation condi­
tions. Removable back wall facilitates fast and easy mounting of fire department key ​
depository and release element (FSE). Fixed base plate for installation on the base using ​
heavy-duty bolts (included). Exchangeable holder for FSE Type KRUSE or PZ above the fire ​
department key depository for better mounting. High-quality stainless steel with polished ​
surface for a distinguished look and weather protection. Polished cover sides facilitate ​
drainage of splash water. Cover fixtures equipped with vandal proof clip lock. Terminal box ​
with cover contact for secure wiring within the column. Comprehensive mounting material ​
included. Fire department key depository and FSE are pre-installed in the column when ​
ordered together.
14
15
16
17
Technical Data
Weight
Dimensions
approx. 32 kg
W: 350 mm H: 1295 mm D: 237 mm
49
Emergency Key Box
785594
Fire Service Key Box
¬oX¡]­
Flash lamp, premounted on sheet steel column
1
The coloured dome in accordance with the local fire brigade TAB in vandal proof design ​
and suitable for weather resistant outdoor application. Complete version including bulb and​
anti twist device. Pre-mounted on top of the 785592 sheet steel column.
Technical Data
Operating voltage
Current consumption @ 12 V DC
Current consumption @ 24 V DC
Frequency of flash
Lighting energy
Type of protection
Dimensions
12 ... 24 V DC
approx. 250 mA
approx. 125 mA
ca. 1 Hz
2J
IP65
Ø: 77 mm H: 50 mm
Order only in combination with the 785592 stainless steel column.
Accessories
785596
¬oX£c­
Rain protection cover for FSKB 2003
1
785597
¬oX¤f­
Premounting for freestanding key box
FSKB and optional modules are included.
Fire service key box as well as the optional devices are completely mounted to the stainless ​
steel column.
Only service. The column, FSKB and all other optional devices (FSE, orientation lamp) must be ​
ordered separately.
50
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Alarm Communications
Analogue Transmission Devices
52
ISDN Dialling Devices
53-54
Accessories
55-57
Alarm Receiver
58-60
11
12
13
14
15
16
17
51
Alarm Communications
Analogue Transmission Devices
¬&n![­
057700
PSTN communication module DS 8800
Approval:
1
G 193803 VdS (IDT)
Transmission of digital information to TELIM-compatible alarm receivers, *ecity/Euro call ​
option.
Technical Data
Features
• 8 transmission channels
• BZT approval no A 106906D for application in ​
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
52
main stations of the public telephone network, ​
within private branch exchange systems in fault ​
switching status and in exchange lines, not ​
capable of direct dialling, upstream of private ​
branch exchange systems
Routine call with weekly programme
Remote maintenance and remote parameterisa­
tion
Real-time clock with date
Programmable delayed detector zones
Programmable blocking periods via real-time ​
clock
Event memory with time and date
Storage capacity for eight call numbers
An identification number can be individually alloc­
ated to every call number
Five different user types programmable: digital ​
receiving station, omniport receiver, ”Eurosignal” ​
European paging service, "Cityruf” regional paging ​
service (tone), ”Cityruf” regional paging service ​
(numeric)
Eight different dialling sequences with different ​
priority classes
Free design of the dialling cycles, which can be ​
individually selected for every dialling sequence
Option of automatic or manual switch between ​
standard and daylight savings
Permanent monitoring of connected remote trans­
mission
Direct remote interrogation or remote interroga­
tion by call-back for digital transmission
Potential-free output for various signalling func­
tions
Free allocation of signal types to every detector ​
zone (armed, disarmed, alarm, etc.)
The user carries out direct input and monitoring ​
of the application-limited data via the intelligent ​
programming unit with its alphanumeric display
Positive drive output for integration into the ​
positive drive condition of intrusion detection ​
systems
Operating voltage monitoring with report trans­
mission
www.hls-austria.com
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Dimensions
10.5 ... 15 V DC
approx. 40 mA
approx.80 mA
-5 °C ... 45 °C
-25 °C ... 70 °C
W: 215 mm H: 123 mm D: 30 mm
Telephone connecting cable
Accessories
057530.10
018002
057701
057711
Power supply / charging unit 12 V DC / 7.2 Ah
12 V DC / 2.0 Ah battery
DS 8800 additional housing ZG 0
DS 8800 additional housing ZG 1
Alarm Communications
¬&mS!­
057650.10
ISDN Dialling Devices
1
DS 7600 ISDN communication module with speech function
Approval:
1
G 106801 (IDT); VSÖ W 070427/39 E
2
Alarm transmission via ISDN, suitable for connection to ISDN phone lines(multipoint or ​
point-to-point connections).
Interface for connection to GSM networks (with RFW 2000). Includes ISDN connecting ​
cable
3
Technical Data
Features
• Can be used on an ISDN multi-device connection ​
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
and ISDN system connection (PTP, PTMP)
Active, galvanically and functionally decoupled ​
ISDN-S0-BUS for downstream ISDN devices
Serial interface S1 according to VdS 2463 and ​
VdS 2465
Parallel interface S1 of 8 inputs according to VdS ​
2463 (freely programmable inputs)
2 potential-free outputs for positive drive, ​
signaling or camera activation
80 additional monitored and freely programmable ​
inputs and outputs can be set up
Non-volatile parameter and event memory (at ​
least 1,000 entries)
Real-time clock with battery-backup
Freely configurable dialing sequences for different ​
event types
Transmission via the ISDN-B channel (VdS 2465, ​
TELIM, V.110)
Transmission via the ISDN-D channel (X.31), 4 ​
online or demand-controlled connections
SMS transmission, paging, voice messages and ​
remote control function via ISDN-B channel
Speech transmission by predefined message texts ​
(in German) and DTMF recognition without any ​
additional extensions
Up to 4 individual texts with up to 3 sec record­
able through ISDN phone
GSM data connections (V.110) with RFW 2000 ​
(optional extension)
SMS and email transmission via GSM with RFW ​
2000 (optional extension)
Simultaneous use of all transmission types and ​
transmission channels possible
20 telephone numbers, 4 dial-up access numbers ​
for X.31 and 5 email addresses programmable
Permanent monitoring transmission paths and ​
system states including recording
Integrated protocol analyzer for service purposes
Intelligent anti-block function for ISDN with ​
protection of emergency call connection
Telephone number check and password prompt ​
for remote access
Remote control function via voice or DTMF
Voice supported user guidance for remote access ​
and remote control over the telephone
Parameterization via WINFEM Advanced (USB or ​
remote access) or via panel
Direct connection of a GPS antenna and transmis­
sion of the site coordinates possible
Operating voltage
Quiescent current @ 12 V DC
Current consumption stand-by #2
Ambient temperature
Storage temperature
Dimensions
4
10.5 ... 15 V DC
approx. 100 mA
< 100 mA
-10 °C ... 50 °C
-25 °C ... 70 °C
L: 158 mm W: 112 mm (PC Board)
5
Accessories
6
057631 Sheet steel housing ZG 0
057632 Sheet steel housing ZG 1 with space for power supply unit and battery
057530.10 Power supply/charging unit 12 V DC / 7.2 Ah
018002 12 V DC / 2.0 Ah battery
7
8
9
10
11
12
Example of application
13
14
15
16
17
53
Alarm Communications
ISDN Dialling Devices
¬&mT$­
DS 7700 ISDN/IP communication module, with speech ​transmission
057651.10
Approval:
1
G 106801 VdS (IDT); VSÖ W 070427/38 E
Information transmission via ISDN and/or IP network, suitable for connection to ISDN ​
phone lines (multipoint or point-to-point connections).
Ethernet interface for connection to IP networks, interface for connection to GSM networks ​
(in connection with RFW 2000). Incl. ISDN connecting cable.
Technical Data
Features
• Full functionality with ISDN multipoint connection ​
and ISDN point-to-point connection (PTP, PTMP)
• Alarm transmission, remote control and remote ​
parameterization via IP networks
• Active, galvanically and functionally decoupled ​
ISDN-S0-BUS for downstream ISDN devices
• Ethernet interface for connection to IP networks
• Serial interface S1 according to VdS 2463 and ​
VdS 2465
Operating voltage
Quiescent current @ 12 V DC
Current consumption stand-by #2
Ambient temperature
Storage temperature
Dimensions
Accessories
057631 Sheet steel housing ZG 0
057632 Sheet steel housing ZG 1 with room for power supply unit and accumulator
057530.10 Power supply/charger unit 12 V DC / 7.2 Ah
018004 12 V DC / 6.5 Ah accumulator
• Parallel interface S1 with 8 inputs according to ​
VdS 2463 (freely programmable inputs)
• 2 potential-free outputs for positive drive, coer­
civeness, signaling or camera activation
• 80 additional monitored and freely programmable ​
inputs and outputs can be set up
• Non-volatile parameter and event memory (at ​
least 1,000 entries)
• Battery-backup real-time clock,
• Freely configurable dialing sequences for different ​
event types
• Transmission via the ISDN-B channel (VdS 2465, ​
TELIM, V.110)
• Transmission via the ISDN-D channel (X.31), 4 ​
online or demand-controlled connections
• SMS transmission, paging, voice messages and ​
remote control function via ISDN-B channel
• Speech transmission by predefined message texts ​
•
•
•
•
•
•
•
•
•
•
•
•
•
54
(in German) and DTMF recognition without any ​
additional extensions
Up to 4 individual texts with up to 3 sec record­
able through ISDN phone
GSM data connection (V.110) with RFW 2000 ​
(optional extension)
SMS and email transmission via GSM with RFW ​
2000 (optional extension)
Simultaneous use of all transmission types and ​
transmission channels possible
20 telephone numbers, 4 dial-up access numbers ​
for X.31 and 5 email addresses programmable
Permanent monitoring of the transmission paths ​
and system states including recording
Integrated protocol analyzer for service purposes
Intelligent anti-block function for ISDN with ​
protection for emergency call connection
Telephone number check and password prompt ​
for remote access
Remote control function via voice or DTMF
Voice controlled user guidance for remote access ​
and remote control over the telephone
Parameterization via WINFEM Advanced (USB or ​
remote access) or via panel
Direct connection of a GPS antenna and transmis­
sion of the site coordinates possible
www.hls-austria.com
10.5 ... 15 V DC
approx. 160 mA
< 160 mA
-10 °C ... 50 °C
-25 °C ... 70 °C
L: 158 mm W: 112 mm (PC Board)
Application example
Alarm Communications
Accessories
¬&n"^­
1
Additional housing ZG 0 for DS 8800
057701
Housing provided with swivel door made of 2-mm steel sheet, powder-coated. Lock can be ​
sealed.
2
1
Technical Data
Color
Dimensions
grey, similar to RAL 9002
W: 230 mm H: 150 mm D: 90 mm
3
No room for emergency power supply
4
¬&n,|­
Additional housing ZG 1 for DS 8800
057711
5
Housing provided with swivel door made of 2-mm steel sheet, powder-coated. Lock can be ​
sealed.
6
1
Technical Data
Color
Dimensions
grey, similar to RAL 9002
W: 300 mm H: 186 mm D: 125 mm
7
Room for emergency power supply 057530.10 and 1 accumulator 018002.10 or 018004.10.
¬&[email protected]­
8
Additional housing ZG 0 for ISDN communication modules
057631
9
Technical Data
1
Housing
Color
Dimensions
with swiveling door 2 mm sheet steel, oven enameled
grey, similar to RAL 9002
W: 230 mm H: 155 mm D: 90 mm
10
No room for emergency power supply
11
¬&mAR­
12
Additional housing ZG 1 for ISDN communication module
057632
Technical Data
1
Housing
Color
Dimensions
13
with swiveling door 2 mm sheet steel, oven enameled
grey, similar to RAL 9002
W: 300 mm H: 186 mm D: 125 mm
14
Room for emergency power supply 057530.10 and 1 accumulator 018002.10 or 018004.10.
15
¬&l?§/21%­
16
Power supply / charging unit 12 V DC / 7.2 Ah
057530.10
Approval:
1
G 190702 (IDT), class A; VSÖ P 070427/79
17
Fully electronic, voltage-stabilised and current-limited power supply unit/charger for ​
redundancy standby operation with accumulator monitoring, designed for an accumulator ​
capacity of up to 7.2 Ah.
Technical Data
Battery capacity
Dimensions
max. 1 accumulator lockable
L: 140 mm W: 60 mm
55
Alarm Communications
¬&oO¢­
057846
Accessories
ISDN connection lead with two western connectors, 1.5 m
1
¬&oS%­
057850
ISDN terminal box
For connection to two separate exchange lines.
1
¬&mX0­
057655
FDS connection board for transmission device
1
Features
• Interface according to DIN 14675 and VdS ​
2463Inputs for transmission of alarm indications ​
from fire alarm systems
• For use in fire alarm systems with 12V DC or 24V ​
DC power supply voltage
56
www.hls-austria.com
The optional ATS adapter for fire panels provides an interface for fire alarm systems ​
according to DIN 14675, appendix B and VdS 2463. The adapter permits the transmission ​
of fire and fault notifications from fire alarm panels by means of DS 7700 / DS 7600.
Alarm Communications
Accessories
¬&mBU­
057633
1
Installation frame for transmission units and transponders
Installation frame specially designed for 8000C/M and IQ8Control C/M fire alarm panels ​
(IQ8Control C only with extension housing).
2
1
Technical Data
Dimensions
W: 280 mm H: 130 mm D: 25 mm
3
1 x Installation frame, 1 x Insulation foil and installation material
4
5
6
7
8
Application example
9
10
11
12
13
14
15
16
17
57
Alarm Communications
Alarm Receiver
DEZ 9000 Alarm Receiver
Features
Approval:
• up to 8 network access options
• Receiver modules for ISDN or TELIM-compatible ​
transmission systems
• Connection via X.25/X.31 (ISDN D channel) or ​
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
TCP/IP (Ethernet) allows a permanently active ​
virtual connection to the connected premises
Receiver module for TCP/IP (Ethernet) can be ​
integrated
VdS-compliant encryption of the transmission for ​
premises connected via TCP/IP
Receiver module for Datex-P can be integrated
4x40-digit alphanumeric LC display
40-digit heat transfer printer
Different interface protocols for downstream ​
control centre DIN 66019 (TSS 31)
Configuration via control centre or via directly ​
connectable PC keyboard
Comfortable PC user interface including control ​
centre functions (DEZ-WIN) included in the ​
delivery (upload/download)
Runs under Windows 9X/ NT / 2000 / XP
Remote control of fault detectors/transmission ​
devices possible
Automatic remote inquiry (status inquiry)
Stand-alone or 19" model
Event memory having a minimum capacity of 20 ​
events/premises
Separate event memory for system activities, ​
history memory
User-definable text macros
Extensive configuration options (printer, buzzer, ​
routine call monitoring)
Independent routine call monitoring possible
Extensive statistics and diagnosis functions
Reception via GSM networks D1 and D2 (in ​
connection with ISDN receiver module and GSM ​
adapter)
G 196801 VdS (IDT) (Alarm receiver)
The alarm receiver DEZ 9000 is used for message reception, registration and processing of ​
alarms, faults and test messages from hazard and fault detection systems. The control ​
panel has been designed as front end computer and "services concentrator" for a down­
stream remote control centre. If no control centre is available, the DEZ 9000 can be used ​
as universal reception computer. Owing to the option of connecting an external computer ​
(PC), a comfortable operating and configuration software having selected control centre ​
functions is available in the form of the "DEZ-WIN" Windows program.
A 40-digit alphanumeric heat transfer printer for recording is available as a standard ​
feature. This allows the operator continuous documentation of events that are not recorded ​
by the downstream control centre or of events whose printout is absolutely necessary.
Its modular structure and performance makes the DEZ 9000 a device component that also ​
meets the requirements resulting from the modern transmission media (e.g. ISDN) and ​
complex information processing. The hardware requirements for receiving messages from ​
GSM networks are provided by means of the RFW-2000 E (057580) module.
The RFW-2000 E essentially consists of a radio terminal and suitable connection compon­
ents, installed in a steel sheet housing ZG 2, on which the required antenna has also been ​
mounted. The RFW-2000 E is connected to the GSM/V.110 adapter included in the delivery, ​
which can be plugged into an existing ISDN receiver module.
If a connection in accordance with VdS, in order to provide a replacement path on the ​
control centre side, is not required, the RFW-2000 E module does not have to be used. In ​
this case, the GSM/V.110 adapter (057572) is sufficient for receiving alarms via GSM ​
networks. It is plugged into an existing ISDN receiver module.
Optional IP receiver modules allow the premises to be monitored to be connected to the ​
DEZ 9000 via private or public IP networks. The transmission method used is the protocol ​
"VdS 2465 for TCP/IP" required by the VdS.
Technical Data
Operating voltage
Ambient temperature
Storage temperature
Type of protection
Dimensions
10.5 ... 15 V DC
-5 °C ... 45 °C
-25 °C ... 70 °C
IP30
W: 488 mm H: 272 mm D: 230 mm
DEZ 9000 part no. 057880
ISDN
GSM network
GSM / V110 adapter part no.057572
RWF-2000 E part no. 057580
ISDN receiver module part no.057885
¬&oq¡­
Planning example
057880
DEZ 9000 Alarm receiver in housing
In the housing, 4 receiver modules, power supply/charger unit, for example 010690.01 and 2 ​
accumulators 6.5 Ah can be integrated.
1
40-digit heat transfer printer; 2 MB memory card; serial interface for connecting a remote ​
control centre or an external computer (PC); includes "DEZ-WIN" PC user interface.
58
www.hls-austria.com
Alarm Communications
¬&or¤­
Alarm Receiver
1
DEZ 9000 19" front panel, 6 HU, installation in a 19" housing
057881
When assembled in a 19" housing, its full capacity can be achieved by incorporating 8 receiver ​
modules.
2
1
40-digit heat transfer printer; 2 MB memory card; serial interface for connecting a remote ​
control centre or an external computer (PC); includes "DEZ-WIN" PC user interface.
3
4
Accessories
¬&ou$­
5
2MB RAM extension for DEZ 9000
057884
6
Required for more than 500 buildings
1
7
8
¬&ov'­
9
ISDN receiver module for DEZ 9000
057885
Receiver module for ISDN network access.
1
10
ISDN connecting cable
11
12
059200
¬&!y­
13
Software update for DEZ 9000 - German
14
059201
¬&"|­
15
Software update for DEZ ISDN receiver module - German
16
17
59
Alarm Communications
¬&os§­
057882
Alarm Receiver
19" assembly plate
The assembly plate allows 4 receiver modules (6 HU) to be integrated in a 19" cabinet.
1
60
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Network Technology
essernet
62-66
Multiprotocol Gateway
67-70
IGIS-LOOP
11
71
12
13
14
15
16
17
61
Network Technology
essernet
The essernet is a short circuit and open circuit resistant 2-wire backbone for networking ​
fire detection and intrusion detection panels from ESSER''s product range. The essernet ​
permits both hierarchy-restricted and hierarchy-free programming of panels. The essernet ​
has been tested and approved by the VdS. The hardware components are listed in the ​
respective equipment approvals of the fire detection panels.
Up to 31 panels can be networked with each other in a ring loop. Superior functions and ​
functions covering different panels can be programmed. The status of the entire system ​
can be read off on anything from one to all panels as desired. Likewise, the system can be ​
operated entirely from one panel.
Networking can be carried out via a simple telecommunication cable, e.g. IY-ST-Y 2 x 0.8 ​
mm, with 784840 or using a data cable, e.g. IBM type 1 as well as CAT5 cable, with ​
784841. With the essernet repeaters, cable distances of up to 3000 m between two panels ​
are possible. An optical waveguide fibre is possible with the converters, which are listed ​
below.
Third-party or management systems (e.g. WINMAGplus) can be connected via the serial ​
essernet interface.
LWL Converter
Serial
essernetInterface
(SEI)
esserbus
Transponder
esserbus-PLus
Loop lenght max. 3.5 km
WINMAG
essernet
Loop lenght max. 1 km
(with Repeater / Fibre
optic converter max. 3 km)
Fire Extinguishing
Panel 8010
Repeater
LCD
Indicator Panel
FDOP
¬oQI§/21V­
Application example
784840.10
essernet module, 62.5 kBd
1
Network interface module for up to 16 network users (e.g. panels respectively SEI). ​
Protocol: similar to DIN 19245 - 1 (Profibus). Topology: loop structure, short circuit and ​
open circuit resistant.
Technical Data
Quiescent current @ 12 V DC
Cable
Cable length
¬oQJ§/21Y­
784841.10
approx. 150 mA
telecommunications cable I Y (St) Y n x 2 x 0.8 mm
1000 m (max. between 2 users)
essernet module, 500 kBd
Network interface module same as 784840 essernet loop module, but for a maximum of ​
31 network users (e.g. panels respectively SEI).
1
Technical Data
Quiescent current @ 12 V DC
Cable
Cable length
62
www.hls-austria.com
approx. 150 mA
IBM type 1,2,6 or similar
1000 m (IBM Typ1 max. between 2 users)
Network Technology
¬oQb_­
essernet
11
essernet repeater, 62.5 kBd
784865
Approval:
1
VdS
22
The essernet repeater increases the maximum distance between two fire alarm control ​
panels in the essernet by up to 1000 m. Standard telephone cables can be used as connec­
tion leads. Two repeaters can be operated in line.
33
Technical Data
Operating voltage
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
Cable
Type of protection
Housing
Color
Weight
Dimensions
¬oQL¦­
8 ... 18 V DC
approx. 100 mA
-10 °C ... 70 °C
-20 °C ... 80 °C
telecommunications cable IY(St)Y n x 2 x 0.8 mm
IP65
die-cast aluminium
grey
approx. 520 g
W: 125 mm H: 60 mm D: 80 mm
44
55
66
essernet repeater, 500 kBd
784843
Approval:
1
77
VdS
As 784865 but with 500kBd baud rate. IBM type 1, type 2 or type 6 cables can be used as ​
connection leads.
88
Technical Data
Operating voltage
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
Cable
Type of protection
Housing
Color
Weight
Dimensions
8 ... 18 V DC
approx. 100 mA
-10 °C ... 70 °C
-20 °C ... 80 °C
IBM-Typ 1, -Typ 2 or -Typ 6
IP65
die-cast aluminium
grey
approx. 520 g
W: 125 mm H: 60 mm D: 80 mm
99
10
11
The respective 784841 essernet module must be ordered separately.
¬oQM§/21b­
12
essernet switch
784844.10
1
The essernet changeover switch allows the uninterruptable redundant changeover between ​
trunk and spare line, if the essernet data line is disturbed. The switch is powered over the ​
fire alarm control panel.
13
Technical Data
Operating voltage
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
14
8 ... 18 V DC
approx. 60 mA
-10 °C ... 70 °C
-20 °C ... 80 °C
IP65
die-cast aluminium
grey
approx. 730 g
W: 175 mm H: 60 mm D: 80 mm
15
16
17
63
Network Technology
essernet
¬oP`W­
Fibre optic converter for essernet, multi-mode with F-ST male c
​ onnection
784763
Fitted on locking device for C-rail mounting. Depending on the glass fibre used, distances ​
of up to 3 km are possible. Suitable for 50/125 µm and 62.5/125 µm multi-mode fibres.
1
Technical Data
Operating voltage
Current consumption @ 12 V DC
Application temperature
Storage temperature
Type of protection
Weight
9 ... 30 V DC
approx. 100 mA
-40 °C ... 85 °C
-55 °C ... 125 °C
IP40
approx. 100 g
Prefabricated connecting cable included for connection to the essernet module in the FACP.
¬oPaZ­
​ onnection
Fibre optic converter for essernet, multi-mode with F-SMA male c
784764
As 784763, but with F-SMA male connection.
1
Technical Data
Operating voltage
Current consumption @ 12 V DC
Application temperature
Storage temperature
Type of protection
Weight
9 ... 30 V DC
approx. 100 mA
-40 °C ... 85 °C
-55 °C ... 125 °C
IP40
approx. 100 g
Including prefabricated connection line for connection to the essernet module in the FACP.
¬oPb]­
Fibre optic converter for essernet, single-mode
784765
1
Fitted on locking device for snap-on mounting. Interface converter electrical/optical for RS ​
485 field bus networks; repeater function; for fused quartz-fibre optics, electrical full/half ​
duplex operation; long range version.
Technical Data
Operating voltage
Application temperature
Storage temperature
Type of protection
Housing
Material
Fixation
Weight
Power consumption
Dimensions
¬oPc`­
784766
18 ... 32 V DC (typ. 24 VDC)
-25 °C ... 60 °C
-25 °C ... 70 °C
IP30
die-cast zinc
zinc fondu
mounting rail or mounting plate
approx. 650 g
3.4 W
W: 40 mm H: 140 mm D: 90 mm
Fibre optic converter for essernet, single-mode
1
The fiber optic converter for essernet, required to connect two single-mode fibers, must be
installed directly into the fire control panel’s housing. This is done by mounting it directly
to the top-hat rail without any further mounting fixtures.
Technical Data
Operating voltage
Current consumption @ 12 V DC
Current consumption @ 24 V DC
Application temperature
Storage temperature
Type of protection
Material
Fixation
Weight
Dimensions
64
www.hls-austria.com
9 ... 30 V DC
approx. 70 mA
approx. 35 mA
-5 °C ... 50 °C
-10 °C ... 55 °C
IP40
aluminum
mounting rail or mounting plate
approx. 200 g
W: 55 mm H: 24 mm D: 105 mm
Network Technology
784855
1
essernet
¬oQXA­
Serial essernet interface EDP, unidirectional
1
The serial essernet interface can be used as a gateway to link remote computers that ​
support the ESSER data protocol (EDP). The EDP version (unidirectional) is only provided ​
with information from the essernet, remote control is not possible.The unit includes a slot ​
for an essernet module and is therefore a fully functional unit within the short circuit and ​
open circuit resistant essernet.
2
3
Technical Data
Features
• Serial data rate 19.2kBd
• RS 485 interface on-board
Operating voltage
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
10.5 ... 28 V DC
approx. 60 mA
-5 °C ... 50 °C
-10 °C ... 50 °C
4
The essernet micromodule and the interface module are not included and must be ordered ​
separately in accordance with the required essernet type and the serial transmission standard.
5
Accessories
788606
772386
772387
784840
784841
¬oQYD­
784856
6
Housing kit
Interface-module RS 232 / V24
Interface-module TTY / CL 20 mA
essernet micromodule, 62.5 kBd
essernet micromodule, 500 kBd
7
Serial essernet interface EDP, bidirectional
8
As 784855 but bidirectional with remote control options e.g. for the connection to a BMS ​
building management system.
9
1
Technical Data
Operating voltage
Current consumption @ 12 V DC
Application temperature
Storage temperature
10.5 ... 28 V DC
approx. 60 mA
-5 °C ... 50 °C
-10 °C ... 50 °C
10
The essernet micromodule and the interface module are not included and must be ordered ​
separately, depending on the type of essernet and the serial transmission mode.
Features
• Serial data rate 19.2kBd
• RS 485 interface on Board
Accessories
788606
772386
772387
784840
784841
¬oQ\M­
784859
11
Housing kit
Interface-module RS 232 / V24
Interface-module TTY / CL 20 mA
essernet micromodule
essernet micromodule 500 kBd
12
13
8000 FACP remote serial essernet interface
1
Features
• RS 485 interface on board
The serial essernet interface is a router for interfacing an 8000 fire alarm panel over relat­
ively large distances. Information from the connected fire alarm panel is received via a ​
router/router link and made available in the host essernet.
It has a slot for an essernet loop module and is thus an integral device in the short circuit ​
and open circuit resistant essernet. For remote function, you can use the integrated RS 485 ​
interface.
14
The essernet micromodule and the interface module are not included and must be ordered ​
separately, depending on the type of essernet and the serial transmission mode.
16
15
770432 SEI setup
17
Accessories
788606
772386
772387
784840
784841
Housing kit
Interface-module RS 232 / V24
Interface-module TTY / CL 20 mA
essernet micromodule
essernet micromodule 500 kBd
65
Network Technology
784847
essernet
¬oQP)­
Serial interface for WINMAGplus / WINMAGLite
1
Interface suitable for serially connecting one 800X/IQ8Control fire alarm panels to
WINMAGplus/WINMAGLite. The module is plugged to the essernet slot in the control
panel. As a result, essernet operation is disabled.
For PC connection, the RS 232 isolator module 784754 is required.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
10.5 ... 15 V DC
approx. 85 mA
The control panel is connected to the PC via the RS 232 cable for a maximum distance of 1,000
m, which is not supplied as standard.
Accessories
784754 Adapter module ADP-PRS-232
Accessories
¬ow'a­
Housing kit
788606
Housing for the serial essernet interface.
1
Technical Data
Type of protection
Housing
Color
Dimensions
¬n8wk­
Interface module RS232 / V24
772386
For the serial essernet interface.
1
¬n8xn­
Interface module TTY / CL 20 mA
772387
For the serial essernet interface.
1
66
www.hls-austria.com
IP31
ABS plastic
white, similar to RAL 9003; front blue, similar to RAL ​
5003
W: 270 mm H: 221 mm D: 71 mm
Network Technology
1
Multiprotocol Gateway
1
Gateway for protocol conversion of the essernet data protocol into different standard software ​
protocols.
The multiprotocol gateways are a group of devices which have been specially optimized for ​
the conversion of the essernet data protocol to/into standard software protocols. The focus ​
here is especially the communication with higher-priority building services management ​
systems as well as with devices by other manufacturers. Device configuration is carried ​
out based on one text file per protocol driver as well as one other text file which sets the ​
connections between essernet object statuses to those of another protocol. This is advant­
ageous as it allows for easy revision with small changes, especially when the naming ​
conventions are adhered to in the target protocol. The basic configuration is created under ​
specification of the target protocol by conversion of project data export of the program­
ming software 'tools 8000' which results in a format that can be loaded by the gateway. ​
The gateway is equipped with an access-restricted web user-interface with independent ​
user management. This facilitates the upload of project data, remote diagnostics, status ​
query of all data points and if the corresponding ESSER modules are used switching via ​
the gateway without additional software. Hardware with different performance levels is ​
available for varying project requirements. Thus it is possible to chose the most cost-effi­
cient model according to the type of target protocol and number of connections required ​
from the essernet data protocol into the selected target protocol.
2
3
4
5
6
We offer a number of gateway services. These services cover everything from calculating ​
data points to selecting suitable hardware, from creating loadable project planning for the ​
gateways to designing project-specific macros, as well as on site start-up. Gateway ​
support training is offered once the gateways are installed. This training includes mainten­
ance or expansion/reprogramming within the object, e.g. when a system has been ​
expanded and the new data points need to be transmitted into the target protocol.
7
8
A serial essernet interface (SEI) (uni-directional or bi-directional) as well as an RS232/ V24 ​
interface module is needed for the connection of the multiprotocol gateways to the ​
essernet. If a FlexES FACP is used in the essernet it is possible to use the internal RS485 ​
interface for connection if the RS485/RS232 interface converter is also applied. Switching ​
functions such as turning individual detectors or whole detector zones on and off are ​
possible if the internal interface of the FlexES or a bi-directional SEI is used for the gateway ​
connection. In addition to the driver for the essernet protocol, delivery includes one of the ​
drivers listed on the order sheet at the end of the catalogue in standard software protocols. ​
The multiprotocol gateway is designed for 230 V.
9
10
11
ESSER Data Protocol (EDP) to:
BACnet Client or Server
OPC Server
MODBUS IP EIB
Instabus LONTalk
12
13
14
15
16
17
67
Network Technology
Multiprotocol Gateway
If a gateway is used for the EDP connection over an OPC server, the OPC-DCOM communication ​
for the server component requires a networked PC with Windows XP or higher. This OPC server ​
component is included in this gateway model.
Additional hardware for the connection of the standard software protocol, as specified in the ​
order, is included in the delivery of the respective gateway variant.
For ordering the multiprotocol gateway, please be referred to the order form at the end of the ​
catalog.
Accessories
784855
784856
772386
788606
Serial essernet interface EDP, unidirectional
Serial essernet interface EDP, bidirectional
Interface module RS232 / V24
Housing kit
Gateway
Modbus IP
Building Management
System
Modbus
Network
RS435 / RS232 converter
Serial essernet
interface
Communication
Transponder
Extinguishing
Control Panel
Serial Connection
Ethernet
Application example
68
www.hls-austria.com
essernet
esserbus
Network Technology
Multiprotocol Gateway
1
MPG DP500
1
The Multiprotocol Gateway DP500 is suitable for usage in small objects in which only a ​
small number of detection points must be transmitted. The maximum number of detection ​
points is 330 indicating and 200 indicating and switching. Here, a fire detector is valid as a ​
detection point. Because of its small dimensions and the integrated mounting rail supports,​
this device can be easily mounted into existing housing.
2
3
Technical Data
Features
Interfaces:
• 1 x RS485 BACnet MS/TP (B+, A-, AGND, screen)
• 1 x RS232 Rx, Tx, GND, RTS,CTS
• 1 x serial port RS232 9-pin fully allocated
• 1 x RJ45 10/100 Base-T
• 1 x USB
CPU:
• ATMEL ARM9 200 MHz
• RAM 32 MB SDRAM
• Memory: 256MB Flash-RAM
• Operating system: Linux real-time
Indicators
• Power LED, green
• RxD LED, yellow
• TxD LED, yellow
• Status LED, multi-color
• Network media LED, orange
• Network activity LED, green
• 1 x digital input
• 1 x digital output (relay 1250W)
• Internal temperature sensor
• Network-bias resistors, 560 Ohm (DIP switches)
• Network-termination resistors 120 Ohm (DIP ​
switch)
Rated voltage
Rated frequency
Operating voltage
Output voltage
Power consumption
Output current
Ambient temperature
Fixation
Air humidity
Weight
Dimensions
4
100 - 240 V AC (power supply)
47 ... 63 Hz (power supply)
12 ... 26 V DC
24 V DC (power supply)
8W
2,5 A (power supply)
0 °C ... 50 °C
top hat rail mounting support
20% to 80% , non-condensing
approx. 400 g
approx. 0.6 kg (power supply)
W: 168 mm H: 33 mm D: 76 mm
W: 78 mm H: 93 mm D: 67 mm (power supply)
5
6
7
This device is not expandable via an internal card. One RS-485 interface is already integrated.
8
Multiprotocol Gateway, power supply, cross-over data cable, serial connection cable
9
10
11
12
MPG DP7500
The Multiprotocol Gateway DP7500 is suitable for usage in mid-sized objects. The ​
maximum number of detection points is 5000 indicating and 3000 indicating and ​
switching. One fire detector counts here as a detection point. This device is ready for rear ​
wall mounting and can be integrated into existing upright cabinets.
13
Features
Technical Data
14
Interface:
• 4 x RS232 9-pol (optional Com4 RS485 optoisol­
ated)
• 1 x RJ45 100/10 Base-T
• 1 x RJ45 1Gbit Base-T
• 4 x USB
Rated voltage
Rated frequency
Operating voltage
Output voltage
Power consumption
Output current
Ambient temperature
Fixation
1
• CPU: Pentium M 800MHz
• RAM: 512MB DDR-RAM
• Memory: 40GB HD, optional DiscOnChip
• Operating system: QNX
Air humidity
Weight
Dimensions
100 ... 240 V AC (power supply)
47 ... 63 Hz (power supply)
10 ... 30 V DC
24 V DC (power supply)
40 W
2,5 A (power supply)
5 °C ... 50 °C
back plane mounting
back plane mounting (power supply)
5% to 90%, non-condensing
approx. 3000 g
approx. 0.6 kg (power supply)
W: 292 mm H: 81 mm D: 145 mm
W: 78 mm H: 93 mm D: 67 mm (power supply)
15
16
17
Multiprotocol Gateway, power supply, cross-over data cable, serial connection cable
69
Network Technology
Multiprotocol Gateway
MPG DP35000
1
The Multiprotocol Gateway DP35000 is suitable for usage in large objects. The maximum ​
number of detection points is 23,000 indicating and 14,000 indicating and switching. One ​
fire detector counts here as a detection point. This device is constructed for upright ​
cabinets with a 19” slide-in unit and requires 4 rack units of free space for mounting.
Technical Data
Features
Interfaces:
• 2 x RS232 9-pol
• 1 x RJ45 100/10 Base-T
• 4 x USB
• CPU: Intel PIII 1100MHz MMX™
• RAM: 256MB SDRAM
• Memory: 64MB non-volatile medium (Flash)
• Operating system: QNX
70
www.hls-austria.com
Rated voltage
Rated frequency
Power consumption
Display
Ambient temperature
Fixation
Air humidity
Weight
Dimensions
230 V AC
50 ... 60 Hz
300 W
Power LED and status LED
0 °C ... 45 °C
19" slide-in unit
20% to 80%, non-condensing
approx. 8000 g
W: 483 mm H: 178 mm D: 281 mm
Integrated power supply
Multiprotocol Gateway, cross-over data cable, serial connector cable
Network Technology
788609
1
IGIS-LOOP
¬ow*j­
IGIS-LOOP-Controller kit for FACP 8000M, IQ8Control M
1
For operating the 8000M, IQ8Control M fire alarm control panel in the IGIS-LOOP system ​
network. Complete kit with IGIS-LOOP micromodule, connection cable and IGIS-LOOP ​
controller, pre-mounted on a carrier plate, ready for installation and for connection to the ​
FACP 8000M, IQ8Control M.
2
Technical Data
Operating voltage
Quiescent current @ 12 V DC
3
10.5 ... 15 V DC
approx. 85 mA (adapter micromodul)
approx. 200 mA (IGIS-Loop Controller)
4
The number of System 8000, IQ8Control as well as IACP 5008 / 5008C control panels depends ​
on the system load, which must be calculated. Please contact our technical marketing ​
department for system load calculation.
5
1 x 784847 IGIS-LOOP adapter module
1 x 750725 Connecting cable IBB for Backbone
1 x 013330 IGIS-LOOP controller
1 x 742417 PCB mounting rail
6
¬o~&l­
IGIS-LOOP-Controller kit for FACP 8000C, IQ8Control C or EMZ 5
​ 008C
789305
1
7
For operating 8000C and IQ8Control fire alarm control panels and/or 5008C intruder alarm ​
panel in the IGIS-LOOP system network. Complete kit with IGIS-LOOP adapter micro­
module, connection cable and IGIS-LOOP controller, mounted in extension housing, ready ​
for connection to a FACP 8000C, IQ8Control or an intrusion alarm panel 5008C.
8
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Battery capacity
Type of protection
Housing
Color
Weight
Dimensions
9
10.5 ... 15 V DC
approx. 85 mA (adapter micromodul)
approx. 200 mA (IGIS-Loop Controller)
max. 2x 12 V DC/24 Ah
IP30
ABS, 10% glass fibre-reinforced, V -0
grey, similar to RAL 9002
approx. 5000 g
W: 450 mm H: 320 mm D: 185 mm
10
11
The number of System 8000, IQ8Control as well as IACP 5008 / 5008C control panels depends ​
on the system load, which must be calculated. Please contact our technical marketing ​
department for system load calculation.
12
1 x 789300 Battery extension housing
1 x 784847 IGIS-LOOP adapter module
1 x 750725 Connecting cable IBB for Backbone
1 x 013330 IGIS-LOOP controller
1 x 742417 PCB mounting rail
13
¬oQP)­
784847
1
Serial interface for WINMAGplus / WINMAGLite
14
Interface suitable for serially connecting one 800X/IQ8Control fire alarm panels to ​
WINMAGplus/WINMAGLite. The module is plugged to the essernet slot in the control ​
panel. As a result, essernet operation is disabled.
For PC connection, the RS 232 isolator module 784754 is required.
15
Technical Data
Operating voltage
Quiescent current @ 12 V DC
16
10.5 ... 15 V DC
approx. 85 mA
The control panel is connected to the PC via the RS 232 cable for a maximum distance of ​
1,000m, which is not supplied as standard.
17
Accessories
784754 Adapter module ADP-PRS-232
71
72
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Management Systems
WINMAGplus
74-84
WINMAGLite
85
Difference between WINMAGLite and WINMGplus
86 12
11
13
14
15
16
17
73
Management Systems
WINMAGplus
Windows management system for hazard detection systems
1
Features
• Compatible with Windows XP Professional SP2, ​
Windows of 2003 servers and Windows Vista
• Modular construction and freely programmable
• Direct control of the network devices
• List of measures to be taken for fire-fighting ​
forces
• Individual allocation of usage rights - priority ​
scheduling
• Integrated simulation-functions
• Extensive recording of events and operations
• Visualization of messages
• Up to 12 active graphics simultaneously repres­
entable
• Integration of video sequences possible
• Information output via Windows print manager to ​
multiple printers etc.
• Time program/calendar function
• Integrated database standard
• Activation of other programs from WINMAGplus ​
possible
• Efficient programming language (SIAS) for ​
customer-specific adjustment of interface and ​
processes in case of alarm
• Remote control possible via modem (optional)
• 10 printers per workstation possible
• Multiple monitors can be used. 4 of 8 screens ​
may be selected.
WINMAGplus has been specially developed to meet the requirements of managing and ​
integrated hazard detection systems on a single PC platform. WINMAGplus simultan­
eously manages and displays graphically a number of security applications, using a ​
common user interface including: fire detection technology; voice alarm public address; ​
intrusion detection technology; access control technology; video technology; rescue route ​
technology/escape door control, personnel protection systems and locating systems as ​
well as fence monitoring systems. Apart from security systems, a multitude of building ​
management control systems such as lighting, elevator control and fault detection ​
systems as well as door/gate/barrier control systems can be managed and graphically ​
displayed.
Database and user interface are designed in line with current standards: messages are ​
displayed both graphically and in text format. WINMAGplus offers various application ​
options, ranging from clearly displayed messages to active control of all detection devices. ​
Based on our security networks IGIS-Loop and essernet, WINMAGplus is not only a highly ​
professional system but also the best possible integrated visual data and management ​
solution.
Program:
Thanks to its modular design, WINMAGplus offers suitable software for systems of any ​
size and type of application, ranging from WINMAGplus basic package for single-station ​
systems with one subsection being connected to the WINMAGplus multi-station system ​
with multiple subsections being connected. Licensing enables the program options ​
purchased and it legitimises program use. A dongle is acquired together with a licence. The ​
dongle must be plugged into a parallel interface or into a USB port of the WINMAGplus ​
computer. With multi-station systems, every computer that is networked must be equipped ​
with a dongle. Workstations that are not networked do not need a dongle. The licence is for ​
one version level (until version 7). If updating is effected to versions prior to V6.0 to V10.0 ​
and later versions, you automatically receive a dongle. If the dongle is removed during ​
operation, WINMAGplus runs for max. 72 hours in online mode.
Our services for installers:
Our WINMAGplus services include everything from entering alarm points to generating ​
diagrams. First of all, operators are made familiar with WINMAGplus. Then we work out t​he
specifications together with the customer and develop SIAS programs. We design ​
complete application packages and train your personnel. Until the final acceptance, we ​
offer support for all installation processes and assist you during daily operation via a ​
remote maintenance tool if required.
Interfaces, drivers:
Besides our security system drivers included in our product catalogue, we offer a variety of ​
drivers for all kinds of trades and manufacturers. Due to the continuously rising number of ​
drivers, the current list of drivers can be requested when required. If the driver you need is ​
not available, we will develop a driver geared to your requirements. Alternatively, all instru­
ments can be connected via the standard OPC interface. This is an international standard, ​
which is supported by a multitude of manufacturers irrespective of their product lines. For ​
developing your own drivers, we can provide you with the connection server and a ​
developer’s package. Thus, individual WINMAGplus drivers can be created.
Hardware and software requirements:
Pentium 3 GHz or higher, minimum 512 MB RAM, minimum 1 GB of hard disk space, XGA ​
graphics card with minimum 4 MB video memory, monitor with min. 1024x768 pixels, sound ​
card with external speakers, Windows XP Professional SP 2 and Windows 2003 Server, Internet ​
Explorer version 6.0 or higher.
To order WINMAGplus licenses, please use the order form found in the back of the catalog.
74
www.hls-austria.com
Management Systems
013610
¬"E+§/21e­
WINMAGplus
1
Control center software CD WINMAGplus basic kit
WINMAGplus control centre software CD for hazard detection systems, licence not ​
included, compatible with Windows XP Professional SP2.With the aid of this basic soft­
ware and the corresponding licenses, hazard detection systems can be operated and ​
managed via PC.Hazard reports are indicated in text form and graphically. In this way, the ​
PC can also be used as an electronic emergency control point. As of WINMAG version 10, ​
this version can be used as an upgrade (only for existing WINMAG versions 6 or older).
2
3
For demonstration purposes only, the WINMAGplus basic version operates without a licence as ​
afull version for a total of twenty 8-hour days, after which the programme switches to offline ​
mode. After expirary of the test time, all connections to all components are cut off. Starting in ​
offline mode does not reduce the number of test runs.The demo mode is a full-function editing ​
environment. All components function except the online communication. Each process can also ​
be tested in demo mode through simulation and all editing functions can be used.
4
Please use order form printed in the catalog.
5
You can also download this software free of charge from our protected download area at ​
www.hls-austria.com.
Basic Licences
013631
6
7
¬"[email protected]§/21=­
Basic license for WINMAGplus USB port
8
This basic licence is used to activate the basic software package/demo version to operate ​
as unrestricted visualising software for server workstations and for network clients. For ​
interfacing control panels to server workstations, further licences are required (see 013601 ​
– 013606, 013608, 013611, 013613, 013625).
9
Please use order form printed in the catalog.
Dongle for USB port
013630
10
¬"E?§/21:­
Basic license for WINMAGplus parallel port
11
Basic licence for WINMAGplus control centre software including dongle for the parallel ​
port.
This basic licence is used to activate the basic software package/demo version to operate ​
as unrestricted visualising software for server workstations and for network clients. For ​
interfacing control panels to server workstations, further licences are required (see 013601 ​
– 013606, 013608, 013611-013613, 013625).
12
13
Please use order form printed in the catalog.
Dongle for parallel port
013633
¬"EB§/21C­
14
Basic license for USB port 3 month duration
Dongle with USB port for licencing of the software. The data medium contains the licence ​
information as well as the activation of the program options FDS, AC, FT and video.
15
The term is restricted to 3 months.
16
A one-time extension for a further 3 months is possible (part no. 013634).
Please use order form printed in the catalog.
17
Dongle for parallel port and license disk
75
Management Systems
WINMAGplus
Upgrade Package
013634
¬"EC§/21F­
Basic license extension for USB port
Licence file for extending the duration of 013633 an additional 3 months (only possible ​
once).
Please use order form printed in the catalog.
License disk
013616
¬"E1§/21w­
WINMAG upgrade to WINMAGplus
Upgrade of a WINMAG installation from version 6 onto the newest WINMAGplus control ​
center software.
For updating WINMAG V1 - 5 please use part no. 013617 in order form.
Please use order form printed in the catalog.
License file
013617
¬"E2§/21z­
WINMAG installation upgrade as of version 6
WINMAG installation upgrade to the most recent WINMAGplus control centre software ​
version
An existing WINMAG as of version 6 can be upgraded to the most recent WINMAGplus ​
control centre software version. For each installation with dongle (each connected PC) an ​
upgrade version must be separately ordered.
Please indicate the basic licence number when ordering!
Please use order form printed in the catalog.
Extension Licences
013609
¬"E*§/21b­
WINMAGplus control centre software - subsequent upgrade
This order number serves as an auxiliary number for a subsequent optional extension or ​
(e.g. additional client or subsequent connection of video systems) to an existing WINMAG ​
installation from V 6.0. to V10 and WINMAGplus. The appropriate licences must be o​ rdered
separately. The dongle need not be submitted.
Note on the respective licences:
In each case only one licence is necessary in order to connect an unlimited number of control ​
panels to a PC. These licences may be separately (subsequently) ordered only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be indicated.
Please use order form printed in the catalog.
¬oP^Q­
This article must be indicated during expansion and is not charged for.
013601
WINMAGplus licence - intrusion detection technology
Licence option for WINMAG/WINMAGplus basic software. Required if intrusion detection ​
systems are connected to WINMAG.
This licence may be ordered separately (subsequently) only in conjunction with the auxiliary ​
number 013609. The update number of the basic licence must be included when ordering. The ​
license is used for connection of the Honeywell intrusion detection systems MB/HB, 5008.
Please use the attached order form.
76
www.hls-austria.com
Management Systems
013626
¬"E;§/21.­
WINMAGplus
1
WINMAGplus licence - fire detection technology
Licence option for WINMAG/WINMAGplus basic software. Required if fire detection ​
systems are connected to WINMAG.
2
This licence may be ordered separately (as subsequent optional upgrade) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering. The license is used for connection of the Honeywell IQ8Control, system 8000 ​
1024 and 1016 fire detection systems.
3
Please use order form printed in the catalog.
013603
¬"E$§/21P­
4
WINMAGplus license - access control
Licence option for WINMAG/WINMAGplus basic software. Required if access control ​
system devices are to be connected to WINMAG (e.g. ACS 2 and ACS 8). MultiAccess and/​
or IQ MultiAccess software package is also required.
5
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering. The licence is used for the connection of the Honeywell ACS and (IQ) ​
MultiAccess access control systems.
6
7
¬"E%§/21S­
Please use the attached order form.
013604
WINMAGplus licence - video technology
8
Licence option for WINMAG/Winmagplus basic software. Required if video technology ​
equipment is to be operated via WINMAG. The crossbars can execute such commands as ​
pan, zoom, tilt, select monitor etc., depending on the model. The following video crossbars ​
are currently supported: Ernitec M 500 and M 1000; Honeywell MaxPRO 32; Philips LTC ​
8x00; Fusion series II / III; Geutebrück Vicrosoft; Geutebrück Multiscope; Honeywell ​
Fusion; contact your supplier for additional brands.
013605
9
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
10
Please use the attached order form.
11
¬"E&§/21V­
WINMAGplus licence - rescue route technology / escape door ​control
12
Licence option for WINMAG/Winmagplus basic software. Required if rescue route techno­
logy/escape door control equipment (only Honeywell Security) is to be operated via ​
WINMAG.
The status of escape doors is graphically displayed.
13
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering. The licence is used for connecting Honeywell rescue route technology/escape ​
door control equipment.
14
¬"E8§/21%­
Please use the attached order form.
013623
15
WINMAGplus licence - interfacing DEZ 9000
Option for connecting the DEZ 9000 remote control unit to the WINMAG/WINMAGplus ​
system. The connection also enables the installation of applications working on the basis ​
of VdS- 2465 transmission protocols to the WINMAG system.
16
Please use order form printed in the catalog.
17
77
Management Systems
013608
¬"E)§/21_­
WINMAGplus
WINMAGplus licence - RTD
Licence option for WINMAG/WINMAGplus basic licence. Enables operation of WINMAG via ​
modem, using DS 7600 and DGA 2400 to ESSER IDT (HB and MB series) and fire detec­
tion systems (1024 series).
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
Please use the attached order form.
Connection Server
013606
¬"E'§/21Y­
WINMAGplus licence connection server
Licence option for WINMAG/WINMAGplus basic software. Connection Server is a software ​
module that enables the connection of a 3rd party device to WINMAG. Connection Server ​
offers a convenient interface with which data and control commands can be exchanged bi-​
directionally in detection point format using WINMAG.
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
¬"E(§/21\­
Please use the attached order form.
013607
Connection server developers kit
This developers kit can be used to programme WINMAG/WINMAGplus connections to t​hird
party devices. The package contains the connection server developers kit including f​ull
documentation plus a one day training in Albstadt.
Please use the attached order form.
Dongle for USB port and license file
OPC
013590
¬"D§/21§­
Universal gateway for PC
Gateway software as a standalone solution for the allocation of data points on host control ​
centre systems via OPC, ESPA 4.4.4.
Hardware and software requirements:
Pentium 3 GHz or higher, min. 512 MB RAM , min. 1 GB hard disk, XGA graphics card with min. ​
4 MB video memory, monitor with 1024 x 768 pixels or more, sound card with external ​
speakers, Windows XP Professional SP2 and Windows 2003 Server, Windows Vista, Internet ​
Explorer 6.0 or higher.
Part no. 013590 may only be ordered in connection with part no. 013618.
¬"E3§/21­
Please use order form printed in the catalog.
013618
Data points package
Package of 500 data points for project-related allocation of OPC tags, ESPA data points, ​
etc.
The data points package can only be ordered in connection with the licence 013590 universal ​
gateway for PC and/or licence 013611 OPC server.
Please use order form printed in the catalog.
78
www.hls-austria.com
Management Systems
013611
¬"E,§/21h­
WINMAGplus
1
WINMAGplus licence – OPC server
Option for WINMAG/WINMAGplus basic software. Required if WINMAGplus is to act as an ​
OPC server.
2
The OPC server licence can only be ordered in conjunction with the 013618 licence. This licence ​
may be ordered separately (as a subsequent optional update) only in conjunction with the ​
auxiliary number 013609. The update number of the basic licence must be included when ​
ordering.
3
¬"E-§/21k­
Please use the attached order form.
013612
4
WINMAGplus licence – OPC client
Option for WINMAG/WINMAGplus basic licence. This is required if WINMAG is to display ​
data from devices with OPC interfaces.
5
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
6
Please use the attached order form.
7
8
9
10
11
12
13
14
15
16
17
79
Management Systems
Options
WINMAGplus
¬"C&§/21R­
Hardware Option TCP / IP converter, Ethernet RS232 / RS485
013405.10
This hardware option is used for the connection of an remote essernet via a (for example) ​
companies-wide Ethernet LAN to a WINMAGplus control centre via TCP/IP. Through this, ​
the device is used as a protocol converter between the SEI contained on the essernet and ​
the WINMAGplus control centre available in the Ethernet LAN.
1
Technical Data
Features
• Serial interface: RS232, RS422 or RS485 (2- and ​
•
•
•
•
•
•
•
4-wire), configurable via software
Transmission speed: 300 bauds to max. 230 ​
kbaud configurable via software
Serial connection: D-Sub 25, socket
Ethernet interface: 10Base-T/100Base-TX
Transmission speed: 10/100/auto Mbit, configur­
able via software
Mode of transmission: half- /full-duplex or auto­
matic, configurable via software
Network access: RJ45
Supported protocol: ARP, UDP, TCP, ICMP, ​
Telenet, TFTP, AutoIP, DHCP, HTTP, SNMP, TCP, ​
UDP and Telnet, TFTP
013613
Operating voltage
Power consumption
Storage temperature
Type of protection
Housing
Weight
Dimensions
9 ... 30 V DC
1,5 Watt, maximum
-40 °C ... 85 °C
IP30
Metall
approx. 200 g
W: 90 mm H: 64 mm D: 23 mm
System requirements for operation and software configuration: Windows® 2000 / XP.
Management system
essernet
RS232
SEI
Ethernet
TCP/IP converter
¬"E.§/21n­
Option - notification
Licence option for WINMAG/WINMAGplus basic licence. Required if SMS (text message), ​
fax or e-mail are to be sent from WINMAG.
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering. An ISDN connection (S0) as well as an ISDN card are required for the n​ otification
function.
Please use the attached order form.
013650
¬"ES§/21v­
Option – escalation
Option for the WINMAG/WINMAGplus basic licence. Required if short text messages ​
dispatched by WINMAG are to be acknowledged. Without acknowledgment, pre-​
programmed escalation plans can be activated.
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering. For the escalation licence, the 013613 notification licence is required. A PC ​
sound card is required for this function.
¬"ET§/21y­
Please use the attached order form.
013651
Option – DTMF control option
Option for the WINMAG/WINMAGplus basic licence. Facilitates the execution of control ​
sequences via dual tone multi frequency (DTMF). With this, for example, it is possible to ​
switch system outputs connected to WINMAG on or off via mobile phone.
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
Please use the attached order form.
80
www.hls-austria.com
Management Systems
013652
¬"EU§/21|­
WINMAGplus
1
Option – ability for customized interface rights (client-side)
Option for the WINMAG/WINMAGplus basic licence, allowing individual assignment of ​
interfaces and rights to several operators.
2
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
3
¬"E]§/21-­
Please use the attached order form.
013660
Option – WEBX
4
Licence option for the basic WINMAG/WINMAGplus licence, allowing display of all system ​
statuses via Internet or Intranet, using standard browsers (max. 5).
5
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
6
¬"E9§/21(­
Please use the attached order form.
013624
Option – redundance
7
Option for redundant connection of essernet and IGIS-Loop security networks to the ​
WINMAG server. Interface operation for redundant networks is based on master/backup ​
operation and prevents data loss in WINMAG objects in case of disruption of network ​
connections caused by cable defects or COM port failure.
8
Please use order form printed in the catalog.
013625
¬"E:§/21+­
9
Option – client
Licence option for WINMAG/WINMAGplus basic licence. Enables operation of one client ​
station in a computer network with one server workstation. The licence must be installed at ​
the server workstation. Clients require only the WINMAG software to be installed. One ​
WINMAG client licence is needed per client.
10
11
This licence may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
¬"EV§/21¡­
12
Please use order form printed in the catalog.
013653
WINMAGplus – 4-monitor support option
13
Option for WINMAGplus basic licence. Enables the allocation of 4 monitors from a choice ​
of 8 monitors. This option only works with WINMAGplus.
This option requires a special graphics card with up to 8 outputs in the WINMAG hardware.
14
This option must be ordered per workstation which uses the multi-monitor option.
15
16
17
81
Management Systems
¬"EX§/21§­
013655
WINMAGplus
WINMAGplus – AutoCAD option
Option for WINMAGplus basic licence. Enables the placement of detectors and groups ​
directly from ACAD LT. The drawings are saved as dxf files. The detectors/groups are ​
placed as hyperlinks in the ACAD drawing and stored. When importing these ACAD draw­
ings into WINMAGplus, the symbols of the disciplines are automatically placed onto the ​
correct position in the drawing. An ACAD licence must be provided by the customer.
This option only works with WINMAGplus.
¬"E/§/21q­
013614
WINMAGplus – OEM option
1
Option for WINMAGplus basic software for customizing WINMAGplus to individual ​
customer-specific wishes.
May cause changes to symbols/text and the front end.
These licences may be ordered separately (as a subsequent optional update) only in conjunction ​
with the auxiliary number 013609. The update number of the basic licence must be included ​
when ordering.
Please use order form printed in the catalog.
82
www.hls-austria.com
Management Systems
WINMAGplus
1
Application Example
1.
WINMAGplus single station system with a essernet connection
2
FACP
3
max. 1000 m
max. 15 m
Serial
essernet
interface
WINMAGplus control centre
4
essernet
max. 1000 m
5
6
FACP
WINMAGplus software requirements:
1 x CD WINMAGplus control centre software
1 x Basic licence WINMAGplus control centre software
1 x Licence fire detection technology
7
Part No. 013610.10
Part No. 013631.10
Part No. 013626.10
8
2.
WINMAGplus multi station system - one server and two clients
with a essernet connection
9
FACP
max. 1000 m
max. 1000 m
10
WINMAGplus server
max. 100 m
max. 15 m
FACP
Serial
essernet
interface
11
essernet
12
max. 1000 m
FACP
LAN
13
14
15
WINMAGplus client 1
WINMAGplus software requirements:
1 x CD WINMAGplus control centre software
1 x Basic licence WINMAGplus control centre software
1 x Licence fire detection technology
2 x Licence WINMAGplus client
16
WINMAGplus client 2
17
Part No. 013610.10
Part No. 013631.10
Part No. 013626.10
Part No. 013625.10
83
Management Systems
WINMAGplus
Application Example
3.
FACP
WINMAGplus multi station system - one server and two clients
with a multi subsection connection
IAP
max. 15 m
Video technology
crossbar or digital
video recorder e. g.
WINMAGplus server
max. 100 m
IGIS-Loop
IGIS-LOOP
controller
IAP
LAN
WINMAGplus client 1
WINMAGplus client 2
WINMAGplus software requirements:
1 x CD WINMAGplus control centre software
1 x Basic licence WINMAGplus control centre software
1 x Licence intrusion detection technology
1 x Licence fire detection technology
1 x Licence access control technology
1 x Licence video technology
2 x Licence WINMAGplus client
Part No. 013610.10
Part No. 013631.10
Part No. 013601.10
Part No. 013626.10
Part No. 013603.10
Part No. 013604.10
Part No. 013625.10
ACS 2 plus
Access control
IQMultiAccess
4.
FACP
WINMAGplus multi station system - 1 main server,
1 redundance server, 3 client workstations
- with a essernet connection
max. 15 m
max. 100 m
WINMAGplus server 1
Serial
essernet
interfaces
max. 15 m
FACP
essernet
WINMAGplus server 2
LAN
FACP
WINMAGplus client 1
WINMAGplus software requirements:
Server 1
1 x CD WINMAGplus control centre software
1 x Basic licence WINMAGplus control centre software
1 x Licence fire detection technology
4 x Licence WINMAGplus client
1 x Licence option redundance
84
www.hls-austria.com
WINMAGplus client 2
Part No. 013610.10
Part No. 013631.10
Part No. 013602.10
Part No. 013625.10
Part No. 013624.10
WINMAGplus client 3
Server 2
1 x Basic licence WINMAGplus control centre software
Part No. 013631.10
1 x Licence fire detection technology
Part No. 013610.10
Management Systems
WINMAGLite
1
FAP
or
IAP
or
Access
Control
Digital Recorder
Fusion e. g.
2
3
WINMAGLite
¬"ED§/21I­
Application example
013635
Features
WINMAGLite is a cost effective first step to hazard detection systems management. Ease of​
operability as well as pre-defined, practical central control panel and detection point types ​
facilitate the commissioning and operation of WINMAGLite.
5
WINMAGLite is perfect for small systems for which no expansions or connection of further ​
hazard detection control panels are planned in the near future. Thus, the Lite version is ​
perfectly suitable for a broad range of applications, even for WINMAG professionals.
6
• Visualising and controlling of only one hazard ​
Especially small objects can be professionally secured due to a combination of hazard ​
detection system with the Honeywell video management systems of Honeywell VisiOprime. ​
WINMAGLite provides the user with almost all basic WINMAG functions. Unlike the full ​
version, this version can initially connect only one hazard detection central control panel.
•
The user has access to pre-defined programs which can automatically be adjusted via a ​
text editor to the respective situation on site.
• Cost-effective management software for hazard ​
detection systems
•
•
•
•
•
•
•
•
•
•
•
•
•
4
WINMAGLite with USB dongle
detection central control panel (FDS, VAPA, IDS, ​
RRT, AC)
Visualising and controlling of VisiOprime or ​
Fusion video management systems
Management of up to 500 detection points
Processing of up to 100 status reports per second
Processing of up to 100 macro processes
Connection of log and alarm printers
Information display via monitor and/or printer ​
(Windows standard printer)
Adjustable programme background
Flexible, window-oriented graphics
Display and location of detectors in diagrams
Status information indicators
Pre-defined alarm reports
Simulation function
Extensive event and operation logging
Users possible
7
8
The alarm stack which was implemented in previous WINMAG versions is replaced t​hrough
symbols displayed in the top bar which indicate alarms. The new feature improves ​overall
clarity so that the user can react more quickly in the case of an alarm.
9
Hardware and software requirements:
Pentium processor 3 GHz or higher, min. 512 MB RAM , min. 1 GB hard disk, XGA graphics card ​
with min. 4 MB video memory, monitor with 1024 x 768 pixels or more, sound card with ​
external speakers, Windows XP Professional SP2 and Windows 2003 Server, Internet Explorer ​
6.0 or higher.
10
11
Please use order form printed in the catalog.
Training for this product is offered. Please contact our training department.
12
Basic CD control centre software package WINMAG (013610)
Accessories
13
Please take note that one serial interface for WINMAGLite, part no. 784847 is needed.
013636
¬"EE§/21L­
WINMAGLite upgrade to WINMAGplus full version
14
If the WINMAGLite system limits have been reached, an upgrade to the full version of ​
Winmagplus is possible, since both systems have access to the same database. WINMAG ​
options are not part of the upgrade and must be ordered separately.
15
WINMAGplus options are not included in the upgraded version and must be ordered separately.
Please use order form printed in the catalog.
16
17
85
Management Systems
Difference between WINMAGLite and WINMGplus
Differences between WINMAGLite and WINMAGplus
WINMAGLite is the inexpensive starter version of the hazard detection system management WINMAG plus with reduced
performance. It is used for visualisation and control of a single hazard detection control unit. The following table shows the most
important performance features of both programs.
In this comparison you can see, whether WINMAGLite is sufficient for an application or WINMAG plus must be used.
The data structure of WINMAG Lite and WINMAG plus is identical, it is possible to change from one version to the other.
Item No.
Interfaces
I/O points per object
Setting of I/O points
Special I/O Types
Event display
Meta data
Alarm stack
User
Tool bars
SIAS-Programs
SIAS-language volumes
Alarm display
Alarm criteria
Graphics
Supported monitors
Number of graphics
Graphics displayable at once
Symbol actions
Creating special symbols
Multi station functions
Mandantory
Timer programs
State monitoring
Printer allocation
Licensing
System configuration list
86
www.hls-austria.com
WINMAGLite
013635
1 hazard detection control + any
Fusion/Visioprime video devices
500
individual
yes
yes
yes
not available
3 predefined, renamable
predefined
predefined, no special programs
no individual programming
counter and popups with individual text
predefined
identical to WINMAGplus, but without
- multi-monitor
- AutoCAD
2
unlimited
13
predefined list
no
no
no
no
no
1
dongle without options
WINMAGplus
013630/13631+ Options
as desired, depending on options
32000
individual
yes
yes
yes
yes
unlimited, free definable
configurable
configurable, extensible
full
identical to WINMAGLite, in addition
alarm programs with alarm stacks
configurable
several formats like
- bmp, jpg, png, emf, wmf
- AutoCAD-Integration (optional)
4 from 8 (optional)
unlimited
48
configurable, special functions
yes
yes
yes
yes
yes
15
dongle with options
1
2
3
4
5
6
7
8
9
10
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
Detectors for Hazardous Areas
Base Series IQ8Quad
Accessories
88-100
101-105
11
106 12
107-121
13
14
15
16
17
87
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
Automatic intelligent fire detectors with high reliability, used for premises and items of ​
property with medium and high concentration of valuable assets.
Detector series IQ8Quad features, system advantages
designed for optimal operation on System 8000 and IQ8Control fire alarm systems
with multisensor detectors for the detection of all types of fires, even under the most diffi­
cult operating conditions
detector with and without loop isolator
Different options of installation
-wiring in loop and spur combination, e.g.
-maximum number of detectors with cable lengths of up to 3500 m with installation cable ​
for fire detection, e.g. cables I-Y(St)Yn x 2 x 0.8 mm
-up to 127 detectors and detector zones per loop installation
-up to 32 detectors per zone
Easy commissioning
-automatic detector addressing
-fixed address assignment of detector location, even after detectors have been replaced or ​
added
-localization of wire breaks and short circuits on loop
-detector-LED used as alarm indicator and as an indicator for detectors in service
-adaptation to changing operating conditions
-dedicated LED for indicating operation (green LED)
-disconnection of individual detectors, detector zones and detection areas
-disconnection of individual sensors or several sensors at once within a multisensor ​
detector; either manually or depending on programmed time of the day
Automatic adaptation to varying environmental conditions
-compensation of changing levels of air pressure, humidity, smoke concentration ​
according to the double chamber principle
-electronic compensation of long-term influences like aging or pollution
Reliable detection
-constant alarm sensitivity of multisensor detector for all types of fire
-large signal to noise ratio due to the special design of the sensors and the electronics to ​
suppress electromagnetic interference
Reliable false alarm suppression
-high immunity against false alarms by means of timed evaluation of different sensor ​
criteria
-signal patterns not typical for fires are eliminated by using special filter algorithms
-automatic self-monitoring of detector electronics
-continuous loop monitoring even during short-circuits through isolating the relevant ​
segment
-automatic monitoring of all sensors to guarantee operational capacity and correct condi­
tion.
Increased operating reliability
-short-circuit and wire break tolerant through monitoring from both ends of the loop
-alarm decision inside detector
-fail-safe circuit activated if communication fails
Maintenance
-automatic maintenance request
-heat detector identification through a black circle on the light transmission plate
-multisensor gas detector identification through a golden loop on the circle transmission ​
plate
-operating time-, alarm- and fault counter in each detector
-automatic, cyclic loop check
-complete status interrogation from the control panel
-interrogation of operating data from all detectors on loop via standard service PC and ​
detector interface
Comprehensive range of accessories
-standard detector base and relay base
-base adapter for ceiling mounting
-dust cover for fire detector or detector base
-kit for suspended ceiling mounting
-RF base
88
www.hls-austria.com
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
1
Detector without Integrated Alarm Devices
Technical Data
117
62
Fire detector with base
2
Operating voltage
Alarm current w/o communication curtain
Air speed
Storage temperature
Air Humidity
Type of protection
Material
Color
Weight
Dimensions
8 ... 42 V DC
approx. 18 mA
0 ... 25.4 m/s
-25 °C ... 75 °C
< 95 % (non-condensing)
IP43 (with base + option)
ABS plastic
white, similar to RAL 9010
approx. 110 g
Ø: 117 mm H: 49 mm (62 mm incl. base)
3
4
5
Special-colour on demand
The detector base is not supplied as standard
The detectors part no. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are ​
approved in the scope of the DIBt system authorization for the operation with an Automatic Door ​
System.
6
Accessories: 767800 mounting bracket
¬q6h=­
802171
7
Fixed heat detector IQ8Quad
Approval:
1
VdS, BOSEC
8
Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of ​
fires with strong heat generation. Intelligent fire detector with decentralised intelligence, ​
automatic function self-test, CPU failure mode, alarm and operating data memory, alarm ​
indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be ​
connected.
9
10
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 40 μA
30
max. 7.5 m
-20 °C ... 50 °C
EN 54 - 5 A1S / -17
11
12
Special marking for heat detector on the light pipe: black ring.
¬q6nO­
802177
Fixed heat detector class B IQ8Quad
Approval:
1
13
VdS
As 802171, but for increased operating temperature according to EN 54-5 Class B.
14
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 40 μA
30
max. 6 m
-20 °C ... 65 °C
EN 54-5 BS / -17
15
16
Special marking for heat detector on the light pipe: black ring.
17
89
Automatic Detectors
¬q7h?­
Series IQ8Quad (Intelligent Addressable)
Rate-of-rise heat detector IQ8Quad
802271
Approval:
1
VdS, BOSEC
Automatic heat detector with fast semiconductor sensor to guarantee reliable detection of ​
fires with rapidly rising temperatures and integrated fixed temperature function for the ​
detection of fires with slowly rising temperatures. Intelligent fire detector with decentral­
ised intelligence, automatic function self-test, CPU failure mode, alarm and operating data ​
memory, alarm indicator, soft-addressing and operating indication.
The detector is provided with an integrated isolator. A parallel detector indicator can be ​
connected.
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 40 μA
30
max. 7.5 m
-20 °C ... 50 °C
EN 54-5 A1 / -17
Special marking for heat detector on the light pipe: black ring.
¬q8hA­
Optical smoke detector IQ8Quad
802371
Approval:
1
VdS, BOSEC
Optical smoke detector to guarantee safe and early detection of fire. Intelligent fire detector ​
with decentralised intelligence, automatic function self-test, CPU failure mode, alarm and ​
operating data memory, alarm indicator, soft-addressing and operating indication. The ​
detector is provided with an integrated isolator. A parallel detector indicator can be ​
connected.
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
¬q8lM­
approx. 50 μA
110
max. 12 m
-20 °C ... 72 °C
EN 54-7 / -17
OTblue multisensor detector IQ8Quad
802375
Approval:
1
VdS
Multisensor with integrated optical detector and heat detector. The optical measurement ​
chamber is provided with a newly developed sensor technology, enabling the detection of ​
open fires, smouldering fires and fires with high heat generation. Especially for open fires, ​
the classical ionisation technology implemented in ionisation detectors is replaced by the ​
new detection technology. The detector is capable of identifying the TF1 and TF6 test fires ​
described in the EN 54-9:1982 specification.
The OTblue multisensor is an intelligent detector with time-related signal analysis, signal ​
correlation of the sensor data, decentralised intelligence, automatic function self-test, CPU ​
failure mode, automatic adaptation to environmental conditions, alarm and operating data ​
memory, alarm indicator and soft-addressing.
The detector is provided with an integrated isolator and a parallel detector indicator can be ​
connected.
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
90
www.hls-austria.com
approx. 50 μA
110
max. 12 m
-20 °C ... 50 °C
EN 54-7/-5 A2 /-17, CEA 4021
Automatic Detectors
802373
¬q8jG­
Series IQ8Quad (Intelligent Addressable)
1
OT multisensor detector IQ8Quad
Approval:
1
VdS
2
Multisensor detector with integrated optical detector and heat detector, with time-​
controlled signal analysis and weighted data combination of both detector functions for ​
detecting smouldering fires and fires with extreme heat generation. Intelligent detector with​
decentralised intelligence, self function test, CPU redundancy mode, automatic adaptation ​
to the environments, alarm and operating data storage, alarm indication and soft ​
addressing.
The loop isolator is integrated in the detector. A parallel detector indicator is additionally ​
attachable.
3
4
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
¬q8kJ­
approx. 50 μA
110
max. 12 m
-20 °C ... 50 °C
EN 54-7/-5 A2 /-17, CEA 4021
5
6
O2T multisensor IQ8Quad
802374
Approval:
1
7
VdS, BOSEC
Multisensor detector provided with two built-in optical smoke sensors with different ​
scattered light angles as well as additional heat detector sensor evaluation to guarantee the ​
detection of different types of fire from smouldering fires to open fires with constant sens­
itivity level. Smoke sensor signal identification to ensure smoke classification and reduc­
tion of deceptive alarms caused, for instance, by water vapour or dust.
Because of its excellent detection characteristics, the detector is also able to identify the ​
standardized TF1 and TF6 test fires. The O²T multisensor detector is also suitable for ​
applications with higher temperatures of up to +65 °C. The detector is provided with an ​
integrated isolator. A parallel detector indicator can be connected.
8
9
10
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
¬q9jI­
802473
approx. 60 μA
110
max. 12 m
-20 °C ... 65 °C
EN 54-7/-5 B /-17, CEA 4021
11
12
OTG multisensor (CO) IQ8Quad
Approval:
1
13
VdS
Multisensor detector with integrated smoke detector, heat detector and gas sensor (CO) for ​
preventive and early detection of fires ranging from smouldering fires to open fires through ​
combined evaluation of scattered light, temperature and gas. An alarm is actuated at ​
carbon monoxide (CO) concentration levels that are life-threatening for humans. The ​
detector is provided with an integrated isolator. A parallel detector indicator can be ​
connected.
14
15
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 65 μA
110
max. 12 m
-20 °C ... 50 °C
EN 54-7/-5 A2 /-17, CEA 4021
16
17
In the course of installation, we recommend testing the integrated CO sensor with our CO test ​
gas (part no. 805583) or CO capsule (part no. 805553).
Programmable CO-alarm-thresholds: 10-150 ppm.
Gas sensors (CO) mainly react to the carbon monoxide arising from a fire (CO). They have, ​
however, also a cross sensitivity to other gases, as for example hydrogen (H2), acetylene (C2H2) ​
or nitric oxide (NO).
Special marking for gas detector on the light pipe: black ring.
91
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
O2T Detector with Integrated Alarm Devices
Features
Detection
• The reliable O²T multisensor principle for ​
consistent response performance at the highest ​
level of security against false alarms
Flash lamp
• Loop powered - no need for external power ​
supply
• No additional short address
• Automatic synchronization of various IQ8Quad ​
alarm signaling devices
• High flash energy
• Loop powered - no need for external power ​
supply
• No additional short address
• Automatic synchronization of various IQ8Quad ​
alarm signaling devices
• Maximum sound level: 92 dB (A) at 1 m
• Maximum sound pressure can be set
• Multiple signal patterns can be combined to one ​
signal
• Signal pattern and repetition rates can be set
• 20 different signal tones, incl. DIN-tone
Speech massage with sounder
• Loop powered - no need for external power ​
supply
• No additional short address
• Automatic synchronization of various IQ8Quad ​
alarm signaling devices
• Maximum sound level: 92 dB (A) at 1 m
• Maximum sound pressure can be set
• Multiple signal patterns can be combined to one ​
signal
• Signal pattern and repetition rates can be set
• 20 different signal tones, incl. DIN-tone
• Speech messages can be played in up to 5 ​
languages
• 5 alarm messages per languages are prepro­
grammed
The IQ8Quad smoke detectors with built-in alarm device incorporate up to 4 different func­
tionalities (detect, flash, sound, and/or speech) depending on the type (O²T/F, O²T/So, O²T/​
Sp, O²T/FSp) of detector.
- fire detection as per EN 54-7
- integrated heat sensor as per EN 54-5
- optical alarm via flash lamp
- acoustic alarm via sounder as per as per EN 54-3
- acoustic alarm speech messages
Detection
Multisensor detectors with two built-in optical smoke sensors with different scattered light ​
angles as well as additional heat detector sensor evaluation for detecting everything from ​
smouldering fires to open fires with consistent response performance. Smoke sensor ​
signal identification to ensure smoke classification and reduction of false alarms caused, ​
for instance, by water vapour or dust. Each detector is provided with an integrated isolator.
Alarm signaling
The alarm signaling device is activated by the control panel. No further short address ​
needs to be allocated. It is programmed with tools 8000 as of software version 1.05.
Alarm tone / speech message programming
For detectors with speech message and/or alarm tone function with up to five language ​
options, up to 4 signals can be programmed. Two signals are reserved for alarm signaling ​
and evacuation in the case of fire. Two further signals can be programmed for other events.​
Each signal can consist of up to four signal components, enabling one signal to be ​
programmed as a DIN tone combined with subsequent speech messages in three different ​
languages.
Alarm tones can be chosen from a table with various tone types. For application in schools, ​
a break signal to signify the breaks between class can be activated.
Four different speech messages, each in three languages, are available:
- "An incident has been reported in the building. Please await further instructions.”
- "Attention” please. This is an emergency. Please leave the building by the nearest
available exit.”
- "This is a fire alarm. Please leave the building immediately by the nearest available exit.”
- “This is a test message. No action is required. “
When the basic setting is selected, signals / signal components can be continuously ​
repeated until the signalling function is interrupted by the control panel. They can also be ​
programmed with a repetition rate of one to three times. Thus, the break signal in schools ​
can be deliberately set to only one repetition. In the same way, the total signal can be set to ​
continuous repetition, with the DIN tone being played only once while subsequent speech ​
messages are played up to three times.
Sound pressure programming
The sound level [dB (A)] can be set to eight levels, from approximately 64dB (A) to approx­
imately 92dB (A).
All the security you need in one housing with four functions detection, flasher, sounder and ​
speech alarm.
92
www.hls-austria.com
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
1
All IQ8Quad detectors with built-in alarm devices can only be operated on the powered loop. For ​
physical reasons, an increased sound level leads to a higher current consumption rate of the ​
alarm device, the respective load factor must be considered when calculating the maximum ​
number on the loop. Altogether up to 127 bus devices per loop can still be connected.
Please consider that an extra training is required when dealing with IQ8Quad with a built-in ​
alarm device. The training includes installation planning and commisioning techniques. For ​
further information take a look at our training brochure. Information concerning the calculation ​
can be found in the "Project Planning Support“ chapter.
signal 1
(evacuation)
sequence 1
sequence 2
sequence 3
sequence 4
signal 2
(alarm)
sequence 1
sequence 2
sequence 3
sequence 4
signal 3
(event 1)
sequence 1
sequence 2
sequence 3
sequence 4
signal 4
(event 2)
sequence 1
sequence 2
sequence 3
sequence 4
2
3
4
5
6
Signals
7
8
9
10
11
12
13
14
15
16
17
93
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
O2T Detector with Integrated Alarm Devices
Country code
acc. to ISO
3166 -Alpha-2
Language
code acc.
to ISO 639-1 Evacuation 1
de
Germany
(DE)
en
Great Britain
(GB)
fr
France
(FR)
es
Spain
(ES)
it
Italy
(IT)
Evacuation 2
Alarm
Test-message
All-Clear
Dies ist ein
Feueralarm. Bitte
verlassen Sie das
Gebäude umgehend über die
nächsten Fluchtwege. Die Feuerwehr ist alarmiert.
Achtung, Achtung!
Dies ist eine Gefahrenmeldung. Bitte
verlassen Sie das
Gebäude über die
nächsten
Ausgänge.
Achtung, im Gebäude ist eine
Gefahrensituation
gemeldet worden.
Bitte bleiben Sie
ruhig, und warten
Sie auf weitere
Anweisungen.
Dies ist eine
Testdurchsage.
Die Gefahrensituation
ist jetzt behoben. Wir
entschuldigen uns
für jegliche
Unannehmlichkeiten.
This is a fire alarm.
Please leave the
building immediately by the nearest
available exit.
Attention please.
This is an emergency. Please leave the
building by the
nearest available exit.
An incident has
been reported in the
building. Please
await further
instructions.
This is a test
message.
No action is
required.
The emergency is
now cancelled. We
apologize for any
inconvenience.
Ceci est une alarme
incendie,veuillez
évacuer
immédiatement les
locaux par la sortie
la plus proche.
Votre attention s'il
vous plaît, ceci est
une alarme. Veuillez
évacuer les locaux
par la sortie la plus
proche.
Un incident est
signalé dans le
batiment. Merci de
garder votre calme
et attendez les
prochaines
instructions.
Ceci est un test.
L'alarme est à
présent annulée.
Veuillez nous excuser
pour le désagrément.
Esto es una alarma
de incendio.
Abandonen
por favor el edificio
inmediatamente
por la salida de
evacuación
más cercana.
Atención. Esto es
una emergencia.
Por favor
abandonen el
edificio por la
salida de
evacuación
más cercana.
Atención, se ha
reportado un
incidente
en el edificio.
Aguarden por favor
otras instrucciones.
Esto es un
mensaje
de prueba.
No se requiere
ninguna acción.
La emergencia ha
sido cancelada.
Pedimos disculpas
por las molestias
causadas.
Attenzione.
Allarme incendio.
Abbandonare
l'edificio tramite
l'uscita di
emergenza più
vicina.
Attenzione.
Allarme in corso.
Vi preghiamo di
recarvi presso
l'uscita di
emergenza più
vicina.
Attenzione.
E' stato rilevato un
allarme.Ulteriori
disposizioni vi
verranno
comunicate
appena possibile.
Attenzione.
E' in corso una
prova di allarme.
Non è richiesta
alcuna azione.
Attenzione. Cessato
allarme.La situazione
di normalità è stata
ripristinata.
Standard speech messages of IQ8Quad detectors and IQ8Alarm
No.
Description
Frequency
1
School bell
complex
2
FP 1063.1 Telecoms
BS 5839 Pt1
Alternating 800 / 970 Hz at 2 Hz
3
BS 5839 Pt1
Alternating 800 / 970 Hz at 1 Hz
f
4
BS 5839 Pt1
Intermittent 970 Hz at 1 Hz 0.5 sec.
f
5
BS 5839 Pt1
Intermittent 2850 Hz at 1 Hz 0.5 sec.
f
6
BS 5839 Pt1
Intermittent 970 Hz 1/4 sec. ON - 1 sec. OFF
f
7
BS 5839 Pt1
Continious 970 Hz
f
8
BS 5839 Pt1
Sweep tone 800 Hz tp 970 Hz at 7 Hz
f
9
BS 5839 Pt1
Sweep tone 800 Hz to 970 Hz at 1 Hz
f
10
DIN Tone
DIN 33404 Part 3
1200 - 500 Hz at 1 Hz
f
11
French fire sound
554 Hz / 100 ms + 440 Hz / 400 ms + 10 %
f
12
NL - Slow Whoop
500 Hz - 1200 Hz at 3.5 sec. break of 0.5 sec.
f
13
US - Horn
Continious 485 Hz
f
14
US - Horn with
Temporal Pattern
Intermittent 485 Hz
(0,5 sec. ON; 0.5 sec. OFF; 3 times; 1.5 sec. OFF; Repeat)
f
15
US - March
Time
Alternating 485 Hz
(0,25 sec. ON; 0.25 sec. OFF; Repeat)
f
16
US - Slow
Whoop
Sweep tone 500 Hz to 1200 Hz
(4.0 sec. ON; 0.5 sec. OFF; Repeat)
f
17
US - Siren
f
18
US - Hi/Lo
Sweep tone 600 Hz to 1200 Hz
(1,0 sec. ON, Repeat)
Alternating 100 Hz / 800 Hz
(0.25 sec. ON; Alternate; 0.25 sec. ON; Alternate; Repeat)
19
US - NFPA
Whoop
IMO
GA-Signal
Sweep tone 422 Hz to 775 Hz
(upwards sweep 0.85 sec.; 3 times; 1 sec. OFF; Repeat)
Intermittent 800 Hz (1,0 sec. ON; 1,0 sec.
OFF: 7 times; 2.0 sec. ON: 2.0 sec. OFF; Repeat)
f
20
IQ8Quad detector and IQ8Alarm tone table
94
Pulse rate
www.hls-austria.com
complex
0,25 sec.
f
0,25 sec.
t
0,5 sec.
0,5 sec.
t
0,5 sec.
1,5 sec.
0,5 sec.
t
0,5 sec.
1,5 sec.
0,5 sec.
0,25 sec.
t
1,0 sec.
t
t
10 ms
t
1,0 sec.
t
1,0 sec.
t
0,1 sec.
0,4 sec.
t
3,5 sec. 0,5 sec.
t
t
0,5 sec.
1,5 sec.
0,5 sec.
t
0,25 sec.
0,25 sec.
t
4,0 sec. 0,5 sec.
t
1,0 sec.
t
f
0,25 sec.
0,25 sec.
0,85 sec.
t
1,0 sec.
t
f
1,0 sec.
1,0 sec.
t
Automatic Detectors
Series IQ8Quad (Intelligent Addressable)
1
Detector with Integrated Alarm Devices
Technical Data
117
65
Fire detector with base
Operating voltage
Area to be monitored
Height to be monitored
Air speed
Application temperature
Storage temperature
Air humidity
Type of protection
Material
Color
Weight
Detector specification
Dimensions
2
8 ... 42 V DC
110
max. 12 m
0 ... 25.4 m/s
-20 °C ... 65 °C
-25 °C ... 75 °C
≤ 95% (ohne Betauung)
IP42
ABS plastic
white, similar to RAL 9010
approx. 145 g
En 54-7/5 B, CEA 4021
Ø: 117 mm H: 59 mm
3
4
5
Detector bases are not supplied as standard.
The 769836 demo package is available for presentations. Further data can be viewed in the ​
accessories section for automatic detectors. For calculating the battery capacity of fire alarm ​
control panels, the detector data "quiescent current @ FACP battery" can be added.
6
Special-colours on demand!
7
It is not possible to use the detector base with relay contact (part no. 805591).
IQ8Control C
8
9
flash
signal
speech
10
11
esserbus-PLus
Loop length max. 3.5 km
12
13
speech
esserbus transponder
14
flash
sound
speech
15
Application example
16
17
95
Automatic Detectors
802382
Series IQ8Quad (Intelligent Addressable)
O/So optical smoke detector IQ8Quad
Approval:
1
VdS
O/So optical smoke detector IQ8Quad with integrated sounder
Scatter smoke detector for safe and early detection of smouldering fires with light smoke ​
generation. Intelligent detector with decentralised intelligence, automatic function self-test, ​
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and ​
operating indication. The detector is provided with a loop isolator.
Along with smoke detection components, the detector is provided with a built-in sounder.
Technical Data
Quiescent current @ 19 V DC
Load factor
Sound level
Detector specification
approx. 80 μA
2
max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
EN54-7, EN 54-17
Not suitable for application in relay base 805591!
¬q8te­
O2T/F multisensor IQ8Quad
802383
Approval:
1
VdS
O²T/F multisensor IQ8Quad with integrated flasher
In addition to smoke detection with the conventional O²T multisensor technology, the ​
detector is provided with a built-in flash lamp.
Technical Data
Quiescent current @ 19 V DC
Quiescent current @ FACP battery
Load factor
Lighting energy
Strength of light
Signal flashing lamp
approx. 75 μA
approx. 400 μA
2
ca. 3 J
max. 15,8 cd peak / 2,63 cd effective
red
Not suitable for application in relay base 805591!
96
www.hls-austria.com
Automatic Detectors
¬q8uh­
Series IQ8Quad (Intelligent Addressable)
1
O2T/So multisensor IQ8Quad
802384
Approval:
1
VdS
O²T/So multisensor IQ8Quad with integrated sounder
2
In addition to smoke detection with the conventional O²T multisensor technology, the ​
detector is provided with a built-in alarm signalling device. The sound level can be set to ​
eight different levels.
3
Technical Data
Quiescent current @ 19 V DC
Quiescent current @ FACP battery
Load factor
Sound level
Specification
approx. 80 μA
approx. 450 μA
2
max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
EN 54-3 acoustic signalling device
4
5
Not suitable for application in relay base 805591!
6
¬q8wn­
7
O2T/Sp multisensor IQ8Quad
802386
Approval:
1
8
VdS
O²T/Sp multisensor IQ8Quad with integrated sounder and speech
In addition to smoke detection with conventional O²T multisensor technology, the detector ​
is provided with a built-in voice alarm device. It can be set to eight different levels.
9
Technical Data
10
Quiescent current @ 19 V DC
Quiescent current @ FACP battery
Load factor
Sound level
Specification
approx. 90 μA
approx. 500 μA
3
max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)
11
12
Not suitable for application in relay base 805591!
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
13
14
15
16
17
97
Automatic Detectors
¬q8w§/TW::)­
O2T/Sp multisensor IQ8Quad / customized version
802386.SV99
Approval:
1
VdS
As 802386, but customized version.
¬q8w§/TW:9©­
O2T/Sp multisensor IQ8Quad / special language
802386.SV98
Approval:
1
98
Series IQ8Quad (Intelligent Addressable)
www.hls-austria.com
VdS
As 802386, but special language.
Automatic Detectors
¬q8vk­
Series IQ8Quad (Intelligent Addressable)
1
O2T/FSp multisensor IQ8Quad
802385
Approval:
1
VdS
2
O²T/FSp multisensor IQ8Quad with integrated flasher, sounder and speech
In addition to smoke detection with the conventional O²T multisensor technology, the ​
detector is provided with a built-in voice alarm device. It can be set to eight different levels.
3
Technical Data
Quiescent current @ 19 V DC
Quiescent current @ FACP battery
Load factor
Sound level
Lighting energy
Strength of light
Signal flashing lamp
Specification
approx. 90 μA
approx. 500 μA
3
max. 92 dB (A), +/- 2 db (A) @ 1m for DIN tone
ca. 3 J
max. 15,8 cd peak / 2,63 cd effective
red
EN 54-3 acoustic signalling device
EN 54-3 acoustic speech signalling device (Q2/2011)
4
5
6
Not suitable for application in relay base 805591!
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
7
¬q8v§/TW:9¦­
O2T/FSp multisensor detector IQ8Quad with composition of other ​languages
802385.SV98
Approval:
1
8
VdS
As with 802385, but with an individual combination of national languages.
9
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the ​
appendix.
10
Cancellations or returns are not possible.
Not suitable for application in relay base 805591!
11
Programmed with an individual combination of up to 5 national languages.
12
13
14
15
16
17
99
Automatic Detectors
¬q8v§/TW::&­
Series IQ8Quad (Intelligent Addressable)
O2T/FSp multisensor detector IQ8Quad as customized version
802385.SV99
Approval:
1
VdS
As 802385, but with individual text and/or sounds. The max. recording time per device is ​
169 seconds.
When ordering, please note the "Ordering information for IQ8Quad and IQ8Alarm" printed in the ​
appendix.
Costs for the recording of customer-specific texts and/or tones can be obtained by request.
Cancellations or returns are not possible.
Not suitable for application in relay base 805591!
Programmed according to customer specifications.
100
www.hls-austria.com
Automatic Detectors
Detectors for Hazardous Areas
1
IQ8Quad Ex (i) Explosion-Proof Series
Technical Data
117
62
Fire detector with base
2
Operating voltage
Alarm current @ 9 V DC
Max. Input Voltage (Ui)
Max. Output current (Io)
Max. Input current (Ii)
Max. internal capacity (Ci)
Air speed
Ambient temperature (Ta)
Storage temperature
Ex-category
Explosion protection
Type of protection
Material
Color
Weight
EC-type examination certificate
Dimensions
8 ... 42 V DC
typ. 18 mA
21 V DC
10 mA
252 mA
1nF
0 ... 25.4 m/s
-20 °C ... 70 °C
-25 °C ... 75 °C
II 2G (with Ex-Barrier Part No. 804744 or 764744)
Ex ib IIC T4
IP43 (incl. base + option)
ABS
white, similar to RAL 9010
approx. 110 g
TÜV 09 ATEX 554910
Ø: 117 mm H: 49 mm (62 mm incl. base)
3
4
5
6
Detector bases are not supplied as standard.
Additional detectors for the explosion zones can be found in the chapters manual call points and ​
special detectors. Detailed information about installation and operation can be found in the ​
documentation part no. 798920.
7
8
All of the following IQ8Quad explosion-proof fire detectors must be operated with the 805590 ​
base. In the case of operation in standard zones, no individual addressing is possible!
For usage in zone 1 and zone 2 in case of operation
- with individual addressing the Ex-Barrier part no. 804744,
- in conventional zones the Ex-Barrier part no. 764744 must be used!
9
The Ex-Barrier separates intrinsically safe and non-intrinsically safe circuits before the explosion ​
prone area to be monitored (explosion zone).
10
Accessories
767800 mounting bracket
11
Individual addressable operating
Zone 1
12
esserbus / esserbus-PLus
Ex area: IIC T2
13
Ex-Barrier (Part No. 804744)
Conventional operating
14
Zone 1
esserbus / esserbus-PLus
15
external power supply
Ex-Barrier (Part No. 764744)
Ex area: IIC T2
16
esserbus transponder 4 zone / 2 relay
Application example
17
101
Automatic Detectors
¬qAh§/FY"­
803271.EX
Detectors for Hazardous Areas
IQ8Quad rate-of-rise detector Ex (i)
Approval:
1
G 209223
Automatic heat detector with quick semiconductor sensor for the reliable recognition of ​
fires with fast rate of temperature rise as well as integrated fixed temperature heat function ​
for the recognition of fires with slow temperature rise. Intelligent fire detector with decent­
ralized intelligence, automatic function self-test, emergency mode, storage of alarm and ​
operating data, alarm display. Soft addressing and separate operational display is only ​
possible when operating an esserbus / esserbus-PLus IQ8Quad detector without loop isol­
ator, especially for usage in explosion zones. Operation with individual addressing at Ex-​
Barrier 804744 and as standard detector at Ex-Barrier 764744.
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 40 μA
max. 30m²
max. 7.5 m
-20 °C ... 50 °C
EN 54-5 A1R : 2002
Special marking for heat detector on light pipe: black ring
Accessories
805590 Standard detector base for IQ8Quad
¬qBh§/FY$­
803371.EX
IQ8Quad optical smoke detector Ex (i)
Approval:
1
G 209224
Scattered-light smoke detector for reliable early recognition of fires. Intelligent fire detector ​
with decentralized intelligence, automatic function self-test, emergency mode, storage of ​
alarm and operating data, alarm display. Soft addressing and separate operational display ​
is only possible when operating an esserbus / esserbus-PLus IQ8Quad detector without ​
loop isolator, especially for usage in explosion zones. Operation with individual addressing ​
at Ex-Barrier 804744 and as standard detector at Ex-Barrier 764744.
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
approx. 50 μA
max. 110m²
max. 12 m
-20 °C ... 70 °C
EN 54-7 : 2006
Accessories
805590 Standard detector base for IQ8Quad
102
www.hls-austria.com
Automatic Detectors
¬qBk§/FY-­
Detectors for Hazardous Areas
1
IQ8Quad O2T intelligent detector Ex (i)
803374.EX
Approval:
1
G 209225
2
Intelligent detector with two integrated optical smoke sensors with different scattered-light ​
angles as well as additional heat detector sensor evaluation for the recognition of smoul­
dering fires up to open fires with uniform characteristics. Comparison of the heat sensor ​
signals for smoke classification and reduction of deceptive alarms, e.g. from steam or ​
dust. Due to its excellent detection characteristics, the detector is also able to recognize ​
TF1 and TF6 test fires, described in the standards. The O²T intelligent detector is also suit­
able for a higher operating temperature of up to +65 °C. Intelligent fire detector with ​
decentralized intelligence, automatic function self-test, emergency mode, storage of alarm ​
and operating data, alarm display. Soft addressing and separate operational display is only ​
possible when operating an esserbus / esserbus-PLus IQ8Quad detector without loop isol­
ator, especially for usage in explosion zones. Operation with individual addressing at Ex-​
Barrier 804744 and as standard detector at Ex-Barrier 764744.
3
4
5
Technical Data
Quiescent current @ 19 V DC
Area to be monitored
Height to be monitored
Application temperature
Detector specification
6
approx. 60 μA
max. 110m²
max. 12 m
-20 °C ... 65 °C
EN 54-7:2006 / -5B:2000 / A1:2002, CEA 4021
7
Accessories
805590 Standard detector base for IQ8Quad
Ex-Accessories
804744
8
¬qPM©­
9
Ex-Barrier for intrinsic safe detectors series IQ8Quad Ex (i)
1
Design certificate BAS 00 ATEX 7087
10
Ex-Barrier for the operation of intrinsically safe IQ8Quad Ex (i) series detectors directly on ​
the esserbus/esserbus PLus with individual addressing in connection with the detector ​
base 805590.
11
Technical Data
Ambient temperature
Type of protection
Weight
CE certificate
Dimensions
-20 °C ... 60 °C
IP20
approx. 100 g
(CPD) EN 54-18:2005
W: 20 mm H: 107 mm D: 115 mm
12
13
A safety barrier does not replace an overvoltage protection according to IEC 801, DIN VDE 0185 ​
and 0855.
14
You can find more detailed information on the installation and the operation for IQ8Quad Ex (i) ​
Series detectors in the documentation part no. 798920.
Individual addressable operating
15
Zone 1
esserbus / esserbus-PLus
16
Ex area: IIC T2
Ex-Barrier (Part No. 804744)
17
Application example
103
Automatic Detectors
Detectors for Hazardous Areas
¬mPM¥­
Ex-Barrier for intrinsic safe of detectors series IQ8Quad Ex (i) and ​9100
764744
Design certificate BAS01 ATEX 7005
1
Ex-Barrier for the operation of intrinsically safe IQ8Quad Ex (i) series detectors in connec­
tion with the detector base 805590 as well as the 9100 Ex (i) series in connection with the ​
detector base 781590.
Technical Data
Dimensions
W: 12.5 mm H: 115 mm D: 110 mm
A safety barrier does not replace an overvoltage protection according to IEC 801,
DIN VDE 0185 and 0855.
VdS approval is not required.
You can find more detailed information on the installation and the operation in the ​
documentation
- part no. 798920 for IQ8Quad Ex (i) Series detectors
- part no. 798913 for 9100 Ex (i) Series detectors.
Conventional operating
Zone 1
esserbus / esserbus-PLus
external power supply
Ex-Barier (Part No. 764744)
Ex area: IIC T2
esserbus transponder 4 zone / 2 relay
¬mPN¨­
Application example
764745
Isolation and assembly block for safety barrier
For insulated (earth-free) mounting of 764744 barriers onto standard hat rail.
1
Isolation block
Part No. 764745
Ex barrier
ground
Hatrail
104
www.hls-austria.com
Automatic Detectors
764752
1
¬mPU4­
Detectors for Hazardous Areas
Housing for Ex-Barrier
1
Polyester housing for the insatallation of up to max. 10 Ex Barriers with integrated inside ​
mounting rail. Also for operational application under extreme environmental conditions ​
suitable.
2
Technical Data
Type of protection
Housing
Color
Dimensions
3
IP66
glass-fiber reinforced polyester
grey, similar to RAL 7000
W: 255 mm H: 160 mm D: 250 mm
4
Mounting material
Features
• Chemically resilient
• Temperature resilient
• Flame retardant
• Noncorrosive
• Sea water resistant
• Nonhalogen, UV resistant
764754
5
6
¬mPW:­
7
Threaded cable connection for housing 764752
Threaded cable connection for housing 764752.
1
8
Technical Data
Ambient temperature
Type of protection
Material
Color
Cable diameter
-20 °C ... 95 °C
IP66
Polyamid
blue, similar to RAL 9005
8 mm
9
10
11
12
13
14
15
16
17
105
Automatic Detectors
805590
Base Series IQ8Quad
¬qXS­
Standard detector base for IQ8Quad
Standard IQ8Quad detector base for the series IQ8Quad. When removing the detector, the ​
loop is automatically closed. The base features a protective function against detector ​
removal, which can be used if required.
1
Technical Data
Features
• A lot of space for wire connection
• Automatic closing of the loop bus wiring system ​
for detector extraction
• Detectos extraction locking is inclosed in the base
Connection terminal
Application temperature
Storage temperature
Air Humidity
Material
Color
Weight
Dimensions
Ø 0.6 mm to 2 mm²
-20 °C ... 72 °C
-25 °C ... 75 °C
< 95 % (non-condensing)
ABS
white, similar to RAL 9010
approx. 60 g
Ø: 117 mm H: 24 mm (incl. detector 62 mm)
Cable entry on the side or through the bottom plate.
Wago clamps for looping in wires, e.g. type 243-204 (Ø 0.5 mm - Ø 1.0 mm) or 273-104 (0.75 ​
mm² - 2.5 mm²) can be mounted on the detector base.
¬qX|V­
805591
Detector base with relay contact for IQ8Quad
IQ8Quad detector base with relay contact output. Contact: floating NO or NC contact ​
selectable via jumper. Settings on site: NO contact.
1
Technical Data
Current consumption
Contact load relay
Connection terminal
Application temperature
Storage temperature
Air Humidity
Material
Color
Weight
Dimensions
5 µA (w/o detector, active relay )
30 V DC / 1 A
Ø 0.6 mm to 2 mm²
-20 °C ... 72 °C
-25 °C ... 75 °C
< 95 % (non-condensing)
ABS
white, similar to RAL 9010
approx. 60 g
Ø: 117 mm H: 24 mm (incl. detector 62 mm)
Cable entry on the side or through the bottom plate.
Wago clamps for looping in wires, e.g. type 243-204 (Ø 0.5 mm - 1.0 mm) or 273-104 (0.75 ​
mm2 - 2.5 mm2) can be mounted on the detector base.
Not suitable for application with IQ8Quad with integrated alarm device type 802383, 802384, ​
802385 and 802386 as well as 802385.SVxx and 802386.SVxx!
106
www.hls-austria.com
Automatic Detectors
Accessories
1
Accessories series IQ8Quad
¬qXyM­
2
Detector cover for IQ8Quad without built-in alarm sounder
805588
The cover plate protects the IQ8Quad detector against contamination during construction ​
or renovation works.
3
1
The detector covers can only be used for IQ8Quad fire detectors without built-in alarm sounder! ​
Application only for detector types with part nos: 802171, 802271, 802371, 802374, 802375 ​
and 802473.
4
50 pcs
5
¬qXxJ­
Base cover for IQ8Quad
805587
6
The cover plate protects the IQ8Quad detector base against contamination during ​
construction or renovation works.
1
50 pcs
7
8
¬qXzP­
Detector cover for IQ8Quad with built-in alarm sounder
805589
9
The cover plate protects the IQ8Quad detector against contamination during construction ​
or renovation works.
10
1
The detector covers can only be used for IQ8Quad fire detectors with built-in alarm sounder! ​
Application only for detector types with part nos: 802283, 802384, 802386 and 802385.
50 pcs
11
¬qXh£­
805571
12
Flush mount kit for base IQ8Quad
13
Adapter for installation in ceilings and for mounting the detector bases IQ8Quad (part nos. ​
805590 and 805591) to the bottom side of false ceilings.
1
Technical Data
Ambient temperature
Storage temperature
Type of protection
Material
Color
Weight
Dimensions
14
-20 °C ... 72 °C
-25 °C ... 72 °C
IP40
ABS, plastic
white, similar to RAL 9010
approx. 165 g (with surface ring)
Ø: 175 mm H: 60 mm
15
16
17
107
Automatic Detectors
Accessories
¬qXk#­
4inch trim ring and snap-in mounting clips for IQ8Quad detector b
​ ase
805574
Snap-in mounting clips and trim ring for base installation, e.g. for installation on 4” elec­
trical boxes.
1
Technical Data
Material
Color
Dimensions
ABS plastic
white, similar to RAL 9010
Ø: 155 mm H: 19 mm (outside)
1 x trim ring and 2 x snap-in mounting clips
¬qXm)­
Application example
805576
Label plate for detector base IQ8Quad
Before or after the installation of the detector, the label plate can be inserted at the side slot ​
of the IQ8Quad detector base.
1
For identification purposes the detector can be provided with the detector address and detector ​
zone for ceilings with a maximum height of 3 m.
A label can be attached to the inscription field. Blank labels can be marked when using a PC, e.g. ​
SIGEL part no. LP725-white (58 x 18 mm) or other suppliers of writing materials or other ​
suppliers of writing materials.
There is a help file in the download area for creating the printing material.
Applicable for base 805590/91 with 805570; for 805593, 805594.
Not to be used for base 805590/91 in combination with 805571, 805572, 805573, 805574.
10 pcs
Application example
108
www.hls-austria.com
Automatic Detectors
Accessories
¬qXn,­
1
Mounting adapter for intermediate ceilings
805577
1
The mounting adapter is used for the quick and secure attachment of bases of the IQ8Quad ​
detector series, 9x00, IQ8Alarm & alarm signalling devices, parallel detector indicators, ​
etc. to suspended ceiling systems. It saves the usage of special hollow cavity fasteners, ​
since the mounting screws of the bases are screwed directly into the slots of the mounting ​
adapter. The mounting adapter offers additional advantages in the fixing of the cables, ​
rigid/flexible cable inlays and threaded cable connections.
2
3
Technical Data
Material
4
ABS
10 pieces
5
All measurements in mm
39,0
2,8 31,0
44,0
49,0
6
10,0
40,0
23,0
7
99,0
21,5
8
9
10
11
¬mo!=­
Application examples for fixing of the cables, rigid/flexible cable inlays and threaded cable connections
12
Mounting bracket for lintel installation
767800
Mounting bracket for all bases/detectors of the IQ8Quad group, series 9x00, RAS 2103 and ​
for IQ8Alarm & all alarm devices.
13
1
The distance between the mounting holes is 6 cm and the diameter is approx. 5 mm.
14
Technical Data
Color
white, similar to RAL 9010
Mounting bracket and material
15
¬qXg~­
IP43 protection for detector base IQ8Quad, flat design
805570
1
16
For installation in environments with a dust and humidity. The IP protection protects the ​
IQ8Quad detector base against dust and humidity. It increases the protection level to IP43. ​
For easy mounting to the base, the IP protection is provided with an adhesive film.
17
Technical Data
Type of protection
Material
IP43
SBR/NR
10 pcs
109
Automatic Detectors
Accessories
¬qXi¦­
IP43 moisture-proof surface-mounted base adapter aP for I​Q8Quad detector base
805572
1
The damp location base adapter was specifically designed for surface mount installation by ​
means of cable conduits. The adapter is provided with three 20 mm (diameter) cable ​
entries.
The built-in seal protects the adapter against condensed water.
Technical Data
Type of protection
Material
IP43
PC
3 x screw connections are included
58,5
58,5
43,6
29,8
40,0
43,6
2,6
2,0
17,0
20,0
145,0
117,0
6,0
6,0
60,0
3,0 ø
15,5
117,0
8,4
6,4
17,8
115,0
5,5 ø
26,0
26,0
2,0
16,0
¬qXj©­
Dimension drawing
805573
IP43 protection for IQ8Quad detector bases, deep design
As 805570 but as universal protection. Additionally, the seal prevents humidity from ​
entering at the sides.
1
Technical Data
Type of protection
Material
Color
5 pcs
110
www.hls-austria.com
IP43
rubber
white, similar to RAL 9010
Automatic Detectors
805560
1
¬qX]`
Accessories
EMC shield for IQ8Quad detector base
1
In fire alarm systems where a high electromagnetic interference/EMI load (e.g. by fluores­
cent lamps or electrical control devices) must be expected it is recommended to mount the ​
EMI-Module in the standard detector base (part no. 805590) of the corresponding fire ​
alarm detectors.
2
The EMI-Module must only be operated in conjunction with standard IQ8Quad detector base ​
(without relay board) and only for detectors without integrated alarm devices (part no. 802382 ​
to 802386, incl. adapted variants).
3
10 pcs
4
5
¬m¥Ej­
769836
6
Demo case for IQ8Quad detector with integrated alarm device
Demo case with a built-in IQ8Quad detector with integrated alarm device for demonstrating ​
the whole range of multisensor functionalities.
7
1
Take note that a notebook is necessary for the startup and for the presentation.
8
The power supply of the detector is provided by the notebook only via the attached USB-cable.
Please note that this is only a demo detector. Therefore, it is not suitable for monitoring rooms ​
or facilities.
9
Software is available as free download on our service-homepage.
Only one 802385 demo IQ8Quad detector O²T/FSp with base, flush mount kit, USB cable, ​
installation CD.
10
11
12
13
14
15
16
17
111
Automatic Detectors
Accessories
Accessories for Several Detector Series
¬qXq5­
805580
Detector removal tool
1
It is suitable for removing Series 9x00 as well as IQ8Quad detectors. Through optional ​
adaptation of the suction cup in the respective insertion on the detector removal tool, the ​
IQ8Quad detector covers (part nos. 805588 + 805589) and the base covers for IQ8Quad ​
(part no. 805587) can be attached as well as removed. The detector removal tool can be ​
adapted to the telescope rod part no. 060426 and 060427 as well as with 805581 to ​
769813.
Snap on detector removal tool, then spin clockwise and remove the detector.
¬qXr8­
Application example
805581
Adapter for ESSER pole (part no. 769813)
The adapter for the 769813 pole is designed for attaching the 805580 detector removal ​
tool and the 805582 smoke detector tester.
1
112
www.hls-austria.com
Automatic Detectors
Accessories
¬qXwG­
1
Carrying bag for test equipment including cover for telescopic r​ ods
805586
The carrying bag has many pockets and compartments in which the ESSER smoke alarm ​
testers, test gas bottles, all cables and other maintenance accessories can be stored. So ​
everything you need for maintenance can always be found in one place. The upholstered, ​
adjustable shoulder strap ensures a very easy and comfortable transport. An additional ​
advantage: the bag protects equipment from dirt and moisture.
1
2
3
Technical Data
Dimensions
W: 480 mm H: 420 mm D: 260 mm (carrying bag)
4
1 x carrying bag and 1 x cover for telescopic rods/extensions
Features
5
• Exterior lid with Velcro fastening transportation ​
straps for telescopic rod and extensions
• Inside lid with 2 storage compartments for battery ​
6
backs 060431
• Inside compartment with up to three optional ​
dividers
• Big front pocket, with up to two optional dividers
• Wide shoulder strap with sliding shoulder pad and ​
additional handles
• Cover with carrying strap for up to 4 telescopic ​
rods 060427 and/or extensions 060426
7
Capacity of the
protective
carrying bag:
2 x battery baton
1 x telescopic rod
8
3 x smoke detector tester
9
10
Front pocket for charger,
test gas, etc.
Up to 4 telescopic rods
in a special cover
11
12
¬'%<¤­
Capacity of the transport bag
060427
13
Plastic telescopic rod
Extendable detector pull-down pole made of glass-fibre reinforced plastic for adapting the ​
805580 detector removal tool as well as testers with part nos. 060429 and 805582.
14
1
Technical Data
Material
Dimensions
Fiberglass
L: 4500 mm
15
16
Features
• Length of 1.26m in retracted state
• 4 segments, lockable
17
113
Automatic Detectors
060426
Accessories
¬'%;¡­
Plastic telescopic extension
1
Telescopic extension for plastic telescopic rod (part no. 060427). Up to 3 telescopic exten­
sions can be attached to the telescopic rod. The maximum height that can be reached is ​
increased to 9 m.
Technical Data
Material
Dimensions
Features
• Easy helpful for daily maintenance of high ceilings
• Stable construction
• Important for attaching and releasing detectors
• Extremely high level of flexural strength due to ​
fiber-plastic composite material
• Totalock TM for easy and secure locking
114
www.hls-austria.com
Fiberglass
L: 1130 mm
Automatic Detectors
805551
¬qXTE­
Features
• Generation of smoke, heat and CO in a single test ​
•
•
•
•
•
•
•
•
•
1
Multi-stimulus detector tester
1
•
Accessories
unit
Clearing cycle of the detector via integrated ventil­
ator for better reset
Simultaneous or sequential testing with various ​
stimuli
Suitable for single and multi-criteria detectors
Suitable for smoke-, heat- and gas- (CO) ​
detectors
Targeted heat rays provide fast activation of heat ​
sensors (up to 90°C/194°F, and/or adjustable up ​
to 100°C/212°F)
Test activation via infrared barrier, no mechanical ​
triggering, no ceiling contact necessary
Easy, fast and efficient testing, as changing of ​
testing device is not necessary
Multilingual and user-friendly menu control
Battery operated portable device
Environmentally friendly and safe through usage ​
of test cartridges instead of test gas cans
Detector tester kit Testifire 2001 for the functional testing of point-type fire detectors with ​
various sensors. The activating stimuli for smoke, heat and CO (carbon monoxide) are ​
generated in this testing unit. Thus the changing of test tools for different types of ​
detectors is no longer necessary.
All fire detector types can be tested with only one test instrument. The test tool is suitable ​
for all optical smoke detectors, ionization detectors, CO detectors and heat detectors. It ​
facilitates fast and effective testing of single and intelligent multi-sensor detectors. So ​
testing of the different sensors can be carried out one after another or for all at the same ​
time.
The required stimuli are generated on demand at the time of test from the corresponding ​
capsule (smoke or CO). Pressurized gas cans are no longer being used.
The selection of the testing stimuli, as well as their combination and sequence are menu ​
driven via keypad and are represented on the display (multilingual). So e.g. simultaneous ​
or sequential testing, or also a combination thereof, can be easily programmed and then ​
carried out at the detector. The activation of the testing device occurs automatically, as ​
soon as the detector interrupts the light barrier integrated in the device. If necessary, a ​
clearing phase can be chosen between the respective testing criteria that enables the ​
stimuli to be blown out of the detector immediately for the next test by the integrated vent­
ilator.
The respectively active criterion is represented by a multi-coloured LED indicator and is ​
clearly recognizable even from large distances. The fill-level of the respective test r​ esources
capsules can be shown in the display. Warnings are indicated automatically e.g. i​f a
​ ith
capsule is nearly empty. The capsules offer much higher test capacities in comparison w
aerosol cans.
The power supply of the testing head occurs via Ni-MH batteries (metal hydride batteries) ​
in the adapter between testing head and telescopic rod. Charging of the battery occurs with ​
the charger optionally via adapter (100-230 V AC) or via 12 V DC input (vehicle cigarette ​
lighter).
Suitable for IQ8Quad and 9x00 detector series.
2
3
4
5
6
7
8
9
Technical Data
Battery charging
Heat detector response threshold
Ambient temperature
Storage temperature
Air Humidity
10
75-90 minutes
up to 90°C adjustable up to 100°C
5 °C ... 45 °C
-10 °C ... 50 °C
< 85 % (non-condensing)
11
Detector tester kit Testifire 2001 consist of:
Testing head, smoke capsule, CO capsule, 2 Ni-MH battery packs, charger
12
Accessories
805552
805553
060426
060427
060431
Smoke capsule for Multi-stimulus detector tester 805550/51
CO capsule for Multi-stimulus detector tester 805551 (Testifire TC3)
Plastic telescopic extension
Plastic telescopic rod
Spare battery baton
Menu
Smoke
Heat
CO
Status
13
14
Smoke 1
Heat 1
CO
Menu
Example of testing
with only one stimuli
Example of a
simultaneous testing
(smoke + heat at the
same time)
Smoke 1
Heat 2
CO 3
Smoke 1
Heat 1
CO 2
Menu
Status
Example of sequential
testing (all criteria
successively)
Menu
15
Status
16
17
Status
Example of
combination of
simultaneous and
sequential testing)
Selection of different test criteria displayed
115
Automatic Detectors
805550
Accessories
¬qXSB­
Multi-stimulus detector tester TF1001
Detector tester Testfire 1001 as 805551, but for testing of detectors with smoke and heat ​
sensors.
1
Technical Data
Battery charging
Heat detector response threshold
Ambient temperature
Storage temperature
Air humidity
Detector tester kit Testifire 1001 consist of:
Testing head, smoke capsule, 2 Ni-MH battery packs, charger
Features
• Creation of smoke and heat with one single test ​
•
•
•
•
•
•
•
•
•
•
device
Desmoking of detector via an integrated fan for ​
fast resetting
Simultaneous or successive testing with different ​
activating materials
Suitable for single criterion and multi-criterion ​
detectors
Suitable for smoke and heat detectors
Targeted heat radiation facilitates quick activation ​
of the thermal sensors (up to 90°C/194°F and/or ​
can be switched up to 100°C/212°F)
Test activation through infrared barrier, no mech­
anical triggering, ceiling contact not necessary
Quick, easy and efficient testing since there is no ​
need to exchange test device
Multilingual and user-friendly menu
Portable battery-powered device
Environmentally friendly and safe through usage ​
of test cartridges instead of test gas cans
Accessories
805552
060426
060427
060431
¬qXUH­
805552
Smoke capsule for Multi-stimulus detector tester 805550/51
Plastic telescopic extension
Plastic telescopic rod
Spare battery baton
Smoke capsule for multi-stimulus detector tester 805550/51
1
Features
• Non-flammable, non toxis materials
• Production of test gas only during the testing
• Does not cause any residue in the sensor ​
chamber
• Suitable for optical and ionization detectors
• No test gas storage under pressure – no ​
dangerous good
• More productivity than the spray can
116
75-90 minutes
up to 90°C adjustable up to 100°C
5 °C ... 45 °C
-10 °C ... 50 °C
90%
www.hls-austria.com
Replacement smoke capsule (Testifire TS3) for the testing of smoke detectors series ​
IQ8Quad and 9x00 with optical and/or ionisation sensors. Suitable for the multi-stimulus ​
detector tester 805550/51.
Automatic Detectors
805553
Accessories
¬qXVK­
1
CO capsule for multi-stimulus detector tester 805551
1
Replacement CO capsule (Testifire TC3) for the testing of detectors with carbon monoxide ​
sensors (CO). Especially suited for the IQ8Quad OTG multisensor detector 802473 (with ​
CO sensor). Suitable for the multi-stimulus detector tester 805551.
2
The IQ8Quad OTG multisensor detector (CO) 802473 is generally tested either
-with the test gas 060430.10, suitable for the smoke detector tester 805582, or
-with 805552, suitable for the muli-stimulus detector tester 805551.
3
The 802473 is VdS-approved as a smoke detector, the CO test gas is required for the additional ​
triggering of the electrochemical CO gas cell.
4
Features
• Non-flammable CO activating-material
• Generation of small amounts of CO
• Generation of CO during testing only
• No storing of pressurized CO - no dangerous ​
5
• More productivity than the spray can
6
good
¬qXs;­
Smoke detector tester
805582
1
7
The smoke detector tester is designed for electric function control for the IQ8Quad and ​
Series9x00 detectors. After an aerosol has been released, the operation capacity of the ​
measuring chamber can be tested by using the transceiver. The smoke detector tester is ​
adapted to the rod (part no. 060427).
8
The telescopic rod is not supplied as standard.
Accessories
9
060426 Plasitc telescopic extension
060427 Plastic telescopic rod
¬'%?§/21f­
10
Test gas for smoke detecetor tester 805582
060430.10
For IQ8Quad and series 9x00 detectors, suitable for smoke detector tester 805582.
1
11
Technical Data
Content
250 ml (per bottle)
12
Not suitable for Series 9000, 9100 and 9200 ionisation smoke detectors.
Please take note that this item has to be handled as dangerous good (aerosols, non-flammable, ​
UN1950)
13
¬qXt>­
14
CO test gas for smoke detector tester 805582
805583
Test gas for testing carbon monoxide CO-detectors. Specifically designed for the OTG ​
multisensor (CO) IQ8Quad 802473, suitable for smoke detector tester 805582.
15
1
Technical Data
Content
250 ml (per bottle)
16
The OTG multisensor detector (CO) IQ8Quad (part no. 802473) should only be tested in ​
connection with test gas 060430.10 suitable for smoke detector tester 805582. Detector 802473 ​
has been approved as smoke detector by VdS and the CO test gas is used to additionally trigger ​
the electrochemical CO-gas cell.
Please take note that this item has to be handled as dangerous good (aerosols, non-flammable, ​
UN1950)
17
117
Automatic Detectors
060429
Accessories
¬'%>!­
Test head for heat detector together with battery and charger
Technical Data
Battery charging
Ambient temperature
Storage temperature
Air Humidity
1
75-90 minutes (if completely discharged)
5 °C ... 45 °C
-10 °C ... 50 °C
< 85 % (non-condensing)
Test head, 2 battery batons, charger
Accessories
060426 Telescopic extension
060427 Plastic telescopic rod
060431 Spare battery baton
Features
• Mains cable is not required for testing
• Power supply with rechargeable NiMH battery in ​
the adapter of the telescopic rod
• Time based termination of testing after 120 ​
•
•
•
•
•
•
seconds in order to prevent any heat related ​
damages of the detectors
Detector head is switched off after not being used ​
for 5 minutes
Adjustable inclination angle of detector head for ​
an optimal orientation towards the object which ​
has to be tested
Testing height up to 6 metres with telescopic rod ​
and up to 9 metres with its extension device
Excess-current protection for the battery
Display of operating status of the detector head ​
with Duo-LED (red/green)
Battery can be charged via mains supply or via ​
cigarette lighter in vehicles
¬'%@'­
060431
Spare battery baton
Replacement battery pack (NiMH) for Test Head 060429 and 805551.
1
¬m¥g§/31J­
769870.20
Smoke detector tester
1
Smoke detector tester allows fast and reliable functionality testing for Series IQ8Quad and ​
9x00 smoke detectors. Through reduced mechanically controlled actuation pressure, ​
suspended installed detectors can also be tested. Control electronics guarantee a defined ​
spray impulse. Spray can and batteries can be easily replaced.
Technical Data
Operating voltage
Testing capacity
Telescopic rod 769813 is required.
Substitute for 769870.10!
1 x test gas 769070
2 x 9V batteries 018051
1 x bellow for IQ8Quad and 9x00
Accessories
769070 Test gas
018051 9 V battery
118
www.hls-austria.com
2 x 9 V batteries
approx. 2000 applications / can
Automatic Detectors
Accessories
¬m¥h§/31M­
769871.20
1
Conversion kit for smoke detector tester 769870
1
The conversion kit (part no. 769871.20) is used to convert the smoke detector tester (part ​
no. 769870 and 769870.10) to test the functions of IQ8Quad and 9x00 smoke detectors.
The conversion kit includes special contact fields to test smoke detectors and the associ­
ated expansion bellows.
2
Substitute for 769871!
3
1 x bellow for Series IQ8Quad and Series 9x00
1 x contact spring
3 x fixing screws
4
¬mgY­
Test gas for smoke detector testers 769870.10 and 769870
769070
5
For series 9x00 and IQ8Quad detectors.
1
6
Technical Data
Content
150 ml (per bottle)
CFC-free test gas, suitable for approx. 2000 applications.
Please take note that this item has to be handled as dangerous good (aerosols, flammable, ​
UN1950).
7
¬m¥.%­
8
Telescopic rod
769813
9
For smoke detector tester 769870.20 (length 3.75 m, three pieces, locking devices).
1
Technical Data
Dimensions
¬m¥/(­
L: 3750 mm
10
Extension pole
769814
11
For smoke detector tester 769870.20, detector removal tool 769804 and telescopic rod ​
769813 (length 4 m, two pieces, locking devices).
12
1
Technical Data
Dimensions
L: 4000 mm
13
14
15
16
17
119
Automatic Detectors
781482
Accessories
¬o/sN­
Kit for suspended installation
1
Kit for detector bases 781590, 805590, 805591 and 801593 for suspended installation ​
with pendulum stabiliser, cable entry at the top, pull relief by means of PG cable entry ​
including junction box with terminals. The detector height can be adjusted individually ​
depending on the cable length to bridge over the heat cushion below the ceiling.
Technical Data
Material
Installation
Color
Dimensions
ABS plastic
attached to the zone cable
white, similar to RAL 9010
Ø: 84 mm H: 15 mm (aluminium-stabiliser)
It is not possible to use telescopic rods.
Not suitable for Series 3000.
as shown
Heat cushion: Smoke-free area
Filled with smoke:
Detection guaranteed
6-pole terminal
inside
Cable entry with cord grip
Standard detector cable
Gap between screws suitable
for detector series
78xxxx and 80xxxx
Detector base can be equipped with
IP protection 805570 or 805573
¬mqw­
769080
Smoke pellets for testing purposes
1
Pellets for the generation of dense bright smoke. To charge detectors with smoke for ​
testing purposes and verification of air flow. The pellets are lit with an open flame (e.g. ​
matches, lighter etc.). Extinguishing is not necessary. Please ensure the use of a non-​
flammable base. After ignition the pellet will burn to complete ash (without formation of ​
flames).
Without oil
6 pcs. smoke pellets
Features
• 40 sec. burning-time per smoke pellet
• 18 m³ smoke produced per smoke pellet
120
www.hls-austria.com
Automatic Detectors
781550
Accessories
¬o0SW­
1
Protective cage
Protective cage for detectors. Steel basket for protection from damage and also
unauthorized disconnection of the d​ etector.
1
2
Technical Data
Material
Color
Dimensions
steel with paint coating
white, similar to RAL 9010
Ø: 140 mm H: 115 mm
3
Can be used with all bases, also for wireless base and wireless gateway.
4
5
6
7
8
9
Application example with IQ8Wireless detector base and IQ8Alarm
10
11
12
13
14
15
16
17
121
122
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Manual Call Points
Large Design - ABS
124-127
Large Design - Aluminium
128-129
Large Design - Accessories
130-134 12
Small Design - ABS
135-142
11
13
Special Design
143-146
14
15
16
17
123
Manual Call Points
1
Features
Large Design - ABS
The advanced generation of manual call points with fragile element meets the latest multi­
cultural requirements of the EN 54 - 11 standards as type B (double action). The elegant ​
detector housing, available in 5 different RAL colours, is provided with a pictogram, which ​
is easy to comprehend for foreign people, illiterates as well as children.
Depending on individual requirements, optional labelling foils can be used which can easily ​
replace the pictogram without special tools. The triggering element is protected by a pane ​
of glass and is indicated by arrows.
If required, optional labelling foils can be used, which can easily replace the pictogram. The ​
triggering element is protected by a glass pane and is indicated by arrows. The innovative ​
manual call points can be tested by using the service key to activate the triggering mech­
anism, which is hidden by a faceplate. Clever design structures allow easy installation.
• Slimline design
• Plug-in connection clamps
• Optional terminal clamps
• 2 x cable entries on top, at the bottom and on the ​
Type B definition - double action in accordance with EN 54-11 § 3.4.2
(excerpt taken from EN standard):
Manual fire alarm unit, for which the alarm status cannot be set until an alarm is additionally ​
triggered by the user after the fragile element has been broken or its position has been changed.
rear panel
• Fixing on standard flush mounted installation box
• Test function via manual call point service key
• Detectors that are not ready for operation can be ​
marked with the "out of order" label by reversing ​
the enclosed operating front foil
MCP out of order
Easy to maintain the change of condition
by turning the operating foil.
MCP ready for use
Application example
Electronic Modules
1
The manual call points consist of a housing and an electronic module, each of the two ​
parts must be ordered separately.
Not all possible combinations of electronic modules and housings are approved by VdS. When ​
using the manual call point as a fire detector for manual actuation in compliance with the EN 54-​
11 standards, a red housing together with the provided pictogram must be used. When using ​
the manual call point in heat exhaust or extinguishing system areas, the appropriate housing ​
colour must be chosen in compliance with the correct standards.
Wago clamps for looping in wires, e.g. type 273-100 (0.5 mm² -1.5 mm²) or
273-104 (0.75 mm² - 2.5 mm²) can be mounted on the detector base.
Electronic Modules Standard
Technical Data
1
Operating voltage
Alarm current @ 9 V DC
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Weight
Detector specification
Dimensions
124
www.hls-austria.com
8 ... 30 V DC
typ. 9 mA
10 detectors per zone (according to VdS)
LED, red
max. 2,5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP44 (in housing), IP55 (with accessory)
PC ASA plastic
approx. 236 g (with housing)
EN 54-11, Typ B
W: 133 mm H: 133 mm D: 36 mm
Manual Call Points
¬qR!n­
Large Design - ABS
1
Conventional MCP electronic module
804900
Approval:
1
VdS, CNBOP
2
With alarm indicator, suitable for connection to a standard detector zone.
In combination with the yellow housing (part no. 704902), the electronic module is approved as ​
an electronic control unit for gas extinguishing systems.
3
The 804900 electronic module with yellow housing conforms to the EN 12094-3 standard and ​
can be used as electronic control unit for gas extinguishing systems in dry, non-hazardous ​
industrial premises.
¬qR"q­
804901
4
Conventional MCP electronic module with second microswitch
Approval:
1
5
VdS, CNBOP
As 804900 but with second and potential-free relay contact.
6
Technical Data
Contact load
30 V DC / 1 A
7
In combination with the yellow housing (part no. 704902), the electronic module is approved as ​
an electronic control unit for gas extinguishing systems.
The 804901 electronic module with yellow housing conforms to the EN 12094-3 standard and ​
can be used as electronic control unit for gas extinguishing systems in dry, non-hazardous ​
industrial premises.
¬qR#t­
8
9
Conventional MCP electronic module w/o snap-on function
804902
Approval:
1
VdS with blue housing 704901
10
As in 804900 but without snap-on function.
This electronic module is only approved as an electric stop push-button for gas extinguishing ​
systems only when combined with the blue housing (part no. 704901). The electronic module ​
804902 with blue housing complies with the EN 12094-3 standard and therefore it can be used ​
as an electric stop push-button for gas extinguishing systems in dry, non-hazardous branches.
11
In case the manual call point is used as a "house alarm" push-button, pre-printed labels are ​
provided in the manual call point package.
12
13
14
15
16
17
125
Manual Call Points
Large Design - ABS
Electronic Modules IQ8MCP
Technical Data
1
Operating voltage
Quiescent current @ 19 V DC
Alarm current w/o communication curtain
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Weight
Detector specification
Dimensions
¬qR&­
804905
8 ... 42 V DC
approx. 45 μA
approx. 18 mA
10 detectors per zone, 127 detectors/loop (according to​
VdS)
LED, red
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP44 (in housing), IP55 (with accessory)
PC ASA plastic
approx. 236 g (in housing)
pr EN 54-11, type B
W: 133 mm H: 133 mm D: 36 mm
IQ8MCP electronic module
Approval:
1
Addressable electronic module suitable for use in the esserbus and powered loop with ​
alarm latch and alarm indicator. Optional connection for conventional MCP. Without BUS ​
connection, the detector operates as conventional MCP. Built-in loop isolator in the manual ​
call point.
¬qR'¢­
804906
VdS, CNBOP
IQ8MCP electronic module w/o isolator but with relay
Approval:
1
VdS
As 804905 but with relay, without loop isolator and without connection for standard ​
manual call point.
The relay output is activated with the triggering of this detector. The relay output can be ​
programmed in the System 8000 and IQ8Control fire alarm control panel customer data as ​
a control group.
Technical Data
Contact load relay
126
www.hls-austria.com
30 V DC / 1 A
Manual Call Points
Large Design - ABS
1
Plastic Housing - Large Design
Housing for electronic module 80490x.
2
1
Technical Data
Type of protection
Housing
Installation
Weight
Dimensions
IP44
ASA plastic
surface mount
approx. 83 g (w/o electronic module)
W: 133 mm H: 133 mm D: 36 mm
3
4
Housing with glass pane (704910)
Plastic key (769910)
Accessories
704910
769910
769911
769916
704917
704911
704900
¬gR!d­
5
Spare glass for manual call points
Plastic spare key
Metal key for large MCP
Service key
Option IP55 shrink sleeve for large MCP 80490x
Universal foil for large MCP housing ABS
6
7
Housing with glass pane, red, similar to RAL 3020
8
Technical Data
Dimensions
W: 133 mm H: 133 mm D: 36 mm
The red manual call point housing is only available with the pictogram (as shown) in compliance ​
with EN 54-11.
9
Please note that in compliance with EN54-11 the labelling must come with the burning house ​
symbol.
10
Pictogram according to EN54-11
Pictogram according to EN54-11
704901
¬gR"g­
11
Housing with glass pane, blue, similar to RAL 5015
The 804902 electronic module in a blue housing complies with the EN 12094-3 and thus can be ​
applied as electronic stop button for gas extinguishing systems in dry, non-hazardous ​
production sites.
12
For different use such as application as "HOUSE ALARM" push button, ready-made labels are ​
provided.
13
Labelling foil set (white) for various international applications.
704902
¬gR#j­
14
Housing with glass pane, yellow, similar to RAL 1021
The 804900 or 804901 electronic module in a yellow housing 704902 complies with the EN ​
12094-3 and thus can be applied as electronic control module for gas extinguishing systems in ​
dry, non-hazardous production sites.
15
For different use such as application as "HOUSE ALARM" push button, ready-made labels are ​
available.
16
Labelling foil set (black) for various international applications.
704903
¬gR$m­
¬gR%p­
17
Housing with glass pane, orange, similar to RAL 2011
Labelling foil set (black) for various international applications.
704904
Housing with glass pane, green, similar to RAL 6002
Labelling foil set (white) for various international applications.
127
Manual Call Points
Large Design - Aluminium
Both housing and electronic module need to be ordered. Not all possible combinations of ​
electronic modules and housings are approved by VdS. The approved combinations are listed in ​
the VdS approval field for the corresponding electronic module.
Electronic Modules
Electronic Module Series 9000
¬gMn§/21N­
704477.10
MCP electronic module Series 9000 with second micro-switch
Approval:
1
VdS with housing 704801.10
printed with pictograms in accordance with EN 54-11
Technical Data
Operating voltage
Alarm current @ 9 V DC
Contact load
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
Detector specification
Dimensions
8 ... 30 V DC
typ. 9 mA
30 V DC/1A
10 detectors per zone (according to VdS)
LED, red
0,6 ... 1,5 mm²
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (with housing)
IP54 (with housing and option 704070)
approx. 100 g (w/o housing)
EN 54-11, type B
W: 95 mm H: 95 mm D: 25 mm
Electronic Module Series 9200
¬qMj§/21L­
804473.10
MCP electronic module Series 9200 with zone isolator
Approval:
1
VdS with housing 704801.10
printed with pictograms in accordance with EN 54-11
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current @ 9 V DC
Alarm current w/o communication curtain
Contact load
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
Detector specification
Dimensions
128
www.hls-austria.com
8 ... 42 V DC
approx. 45 μA
typ. 9 mA
approx. 18 mA
30 V DC/1A
10/zone, 127/loop (VdS)
LED, red
0,6 ... 1,5 mm²
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (with housing)
IP54 (with housing and option 704070)
approx. 100 g (w/o housing)
EN 54-11, type B
W: 95 mm H: 95 mm D: 25 mm
Manual Call Points
Large Design - Aluminium
1
Aluminium Die-Cast Housings
Technical Data
2
1
Material
Installation
Weight
Dimensions
aluminium, die-cast
surface mount
approx. 600 g
W: 126 mm H: 126 mm D: 42 mm
3
red = similar to RAL 3000; blue = similar to RAL 5009; yellow = similar to RAL 1018
4
Key: 769910, 769911 (accessory)
Housing with glass pane and plastic key, fixing material, 1 x multilingual "out of order" paper ​
insert, 2 x cable entries, 2 x dummy plugs
¬gQ"§/[email protected]­
5
MCP housing with glass in compliance with EN 54-11, red
704801.10
printed with pictograms in accordance with EN54-11
1
6
Technical Data
Color
red, similar to RAL 3000
7
8
704804
¬gQ%n­
9
MCP housing with glass printed: house alarm-ESSER, red
Technical Data
¬gQW6­
red, similar to RAL 3000
¬gQkr­
blue, similar to RAL 5009
Color
704854
10
MCP housing with glass printed: house alarm-ESSER, blue
11
Technical Data
Color
704874
12
MCP housing with glass printed: house alarm-ESSER, yellow
13
14
15
16
17
129
Manual Call Points
Large Design - Accessories
¬gR+¤­
Spare glass pane for MCP housings 70490x, 7048xx and 761694
704910
Spare glass pane for detector housings large design 70490x, 7048xx, 761694 and 761697 ​
in compliance with EN 54-11.
1
Technical Data
Dimensions
W: 80 mm H: 80 mm
10 pcs
¬g+I'­
Spare glass pane red for MCP housings 7047xx and 7048xx
701040
Spare glass pane, printed with red circle segments (similar to RAL 3000) for all 7047xx ​
and 7048xx manual call points (large design).
1
Technical Data
Dimensions
W: 80 mm H: 80 mm
10 multilingual "out of order" paper labels are included.
10 pcs
¬m¦6?­
"Out of order" sign, multilingual for large MCP
769921
Plastic sign for all 7047xx, 7048xx and 70490x manual call points (large design).
1
Technical Data
Dimensions
W: 80 mm H: 80 mm
¬gR0*­
Operating panel foil for large manual call point 80490x, neutral
704915
1
Replacement operating panel foil, neutral without logo, for large design 80490x manual call​
points in resistant plastic design. The foil is designed as a double-sided insert. Comple­
menting the standards-compliant symbolism for manual fire alarms according to EN 54-11 ​
(type B), it contains a symbol on the back for the removal from service of the alarm and is ​
easily accessible at all times for possible maintenance operations.The out-of-order repres­
entation occurs via an internationally understandable construction worker symbol and ​
multilingual text.
Technical Data
Material
Dimensions
PP (0.3 mm)
W: 72 mm H: 75.7 mm
10 pcs.
MCP “Out of Order”
Application example
130
www.hls-austria.com
Easy to maintain the change of condition
by turning the operating foil.
MCP ready for use
Manual Call Points
704917
Large Design - Accessories
¬gR20­
1
Option IP55 shrink sleeve for large MCP 80490x
10 shrink sleeves for clamp terminals to increase protection class to IP55.
2
10 pcs
1
3
4
5
6
¬gR,§­
704911
IP44
IP55
7
Foil for front face w. universal text for large MCP ABS 70490x
AMOK-ALARM
1
Emergency Stop
Système d'extinction à gaz
Sistema de extinción
Sistema de extinção
9
Transparent foil with white lettering.
Gas extinguishing system
Arrêt d'urgence
PARO EMERGENCIA PARAGEM EMERGÊNCIA
8
Universal, punched foil set (transparent with white imprint) for the labelling field, different ​
from the standard version.
POZAR
10 pcs
10
BLUSSING BLOKKEREN
Knop ingedrukt houden
¬gR-!­
11
Foil for front face w. universal text for large MCP ABS, black l​ettering
704912
As 704911 but with black imprint.
1
12
10 pcs
13
14
¬gIgV­
704070
15
IP54 kit for large manual call points 7048xx
Cable entries to increase protection class from IP43 to IP54 for manual call points in die-​
cast aluminium housings (7048xx).
16
1
Technical Data
Material
Color
Cable diameter
PS
grey, similar to RAL 7035
6 mm
17
as shown
131
Manual Call Points
¬m¦+§­
Large Design - Accessories
Plastic key for large MCP
769910
Plastic key type D for all manual call points (large design).
1
Please note that for activating the test functionality of electronic modules (part no. 80490x), the ​
service key 769916 is required.
¬m¦,!­
Metal key for large MCP
769911
Metal key type D for all detector housings (large design).
1
Please note that for activating the test functionality of electronic modules (part no. 8049xx), the ​
service key 769916 is required.
¬m¦10­
Service key for electronic module (part no. 80490x)
769916
With this metal service key, the test functionality of the manual call point is activated and ​
reset by authorised persons only.
1
The key is suitable for all electronic modules with part nos. 80490x from index 05 and ​
yellow locking.
¬o1sR­
Weather protective cover, red for MCP housings 7047/48xx
781682
Protective housing with protruding roof edge, for all 7047xx and 7048xx detector housing ​
for increased mechanical protection as well as for protection from bad weather conditions.
1
Technical Data
Material
Color
Dimensions
PVC
red, similar to RAL 3000
W: 135 mm H: 153 mm D: 62 mm
Please mention for the manual call point, large design plastic (f.e. IQ8MCP), the protection cover ​
part no. 781693 and the accordant accessories.
Weather protective cover and mounting material
132
www.hls-austria.com
Manual Call Points
781692
¬o1p­
Large Design - Accessories
1
Weather protective cover, blue for MCP-housings 7047/48xx
Protective cover similar to 781682.
1
2
Technical Data
Color
blue, similar to RAL 5009
Weather protective cover and mounting material
3
4
¬o1¡v­
781694
Protective cover for manual call points - ESSER, English
5
As 781693, but ESSER, English
1
This protective cover prevents false alarms, without hampering real alarms. This device consists ​
of a rack and a lid, made of transparent polycarbonate.
It prevents inadvertent activation, vandalism, dust and water from triggering false alarms. The ​
protective cover is suitable for all manual call points.
6
Accessory for installation
7
8
9
¬o1¥¤­
Application example
781698
10
Surface spacer for protective cover
11
The spacer is required for surface mount wiring.
1
Technical Data
Weight
Dimensions
approx. 510 g
W: 180 mm H: 260 mm D: 50 mm
12
Accessory for installation
13
14
15
16
17
133
Manual Call Points
781699
Large Design - Accessories
¬o1¦§­
IP55 kit for protective cover
Mounting kit - self-adhesive sealing kit for protective cover (781693) and an increased ​
protection level from IP44 to IP55.
1
781699
781698
78169x
Application example
134
www.hls-austria.com
Manual Call Points
Small Design - ABS
88
1
The new generation of manual call points meets the latest multicultural requirements of the ​
EN 54 - 11 standards as type A (Single Action). The elegant housing is provided with a ​
pictogram, which can be understood by children as well as in an international context.
Depending on individual requirements, the pictogram can be easily replaced by optional ​
labelling field foils without using additional tools for removal. The actuation field is marked ​
by arrows pointing towards it. The innovative manual call points can be tested by using the ​
key to activate the triggering mechanism, which is hidden by a faceplate. Smart housing ​
and terminal design enables easy installation.
1
7
21
2
3
When replacing the glass pane by the optionally available plastic pane with resettable function ​
the MCP can be reset from the outside with the key!
4
For the surface mounting of the MCP the surface mount base 704980 is to be ordered ​
separately, if the cable wasn't layed about a standard flush mount wall socket.
88
Features
Type a definition - single action in accordance with EN 54-11 § 3.4.1
(excerpt taken from EN standard):
5
Manual fire alarm unit, for which the alarm status is automatically set (additional alarm ​
triggering is not required) after the fragile element has been broken or its position has been ​
changed.
6
Vertical connection mode
Horizontal connection mode
• Slimline design
• Plug-in connection terminals (two direction)
• Optional terminal terminals
• Triple key function (test, open, reset)
7
8
9
Snap-on positions / connection terminal
Complete MCP
804970
¬qRgr­
10
Conventional MCP, red housing with glass pane - ESSER
Approval:
1
11
VdS, CNBOP
Including housing and alarm indicator. For connection to a conventional detection zone.
12
Technical Data
Operating voltage
Quiescent current @ 9 V DC
Alarm current @ 9 V DC
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
8 ... 30 V DC
approx. 0 μA
typ. 9 mA
10 detectors per zone (according to VdS)
red LED and yellow actuation indicator
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43, IP55 with cover 704965
PC ASA plastic
red, similar to RAL 3020
approx. 110 g
EN 54-11, type A
W: 88 mm H: 88 mm D: 21 mm
13
14
15
16
1 x glass pane 704960
1 x key 704966
1 x multilingual paper labels with "Out of order" pictogram.
17
Accessories
704980 Surface mount housing
135
Manual Call Points
804971
¬qRhu­
Small Design - ABS
IQ8 MCP, red housing with glass pane - ESSER
Approval:
1
VdS, CNBOP
Suitable for esserbus and powered loop connection, with soft address coding, alarm latch ​
and alarm indicator. Conventional detectors can be connected to input of the MCP. Without ​
BUS communication, the detector operates as conventional MCP. Detector housing is ​
included.
Built in isolators maintaining loop integrity.
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current w/o communication curtain
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
8 ... 42 V DC
approx. 45 μA
approx. 18 mA
max. 127 detectors per loop (according to VdS)
red LED and yellow actuation indicator
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43, IP55 with cover 704965
PC ASA plastic
red, similar to RAL 3020
approx. 110 g
EN 54-11, type A
W: 88 mm H: 88 mm D: 21 mm
W: 88 mm H: 88 mm D: 57 mm (with surface mount ​
housing)
1 x glass pane 704960
1 x key 704966
1 x multilingual paper labels with "Out of order" pictogram
Accessories
704980 Surface mount housing
¬qRj­
804973
IQ8 MCP, red housing with plastic pane - ESSER
Approval:
1
VdS
As 804971 but with plastic triggering element, which supports easy reset after an alarm ​
has been triggered without having to replace the broken element (glass pane).
Typically applied in clean rooms as for example in food processing industries.
Technical Data
Operating voltage
Alarm current w/o communication curtain
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
8 ... 42 V DC
approx. 18 mA
max. 127 MCP per loop
red LED 1 / yellow tab
max. 2.5mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in housing)
ASA plastic
red, similar to RAL 3020
approx. 110 g
EN 54-11, type A
B: W: 88 mm H: H: 88 mm T: D: 21 mm
B: W: 88 mm H: H: 88 mm T: D: 57 mm (with surface ​
mount housing)
see application example in Part No. 704964
1x plastic operating panel 704964
1x key 704966
1x multilingual paper insert with "Out of Order" pictogram included
Accessories
704980 Surface mount housing
136
www.hls-austria.com
Manual Call Points
Small Design - ABS
Electronic Modules - Small Design
1
804950
2
¬qRS6­
Conventional MCP electronic module with glass - ESSER
Approval:
VdS
3
With alarm indicator, for the connection to a standard detector zone.
1
Technical Data
Operating voltage
Quiescent current @ 9 V DC
Alarm current @ 9 V DC
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
Detector specification
Dimensions
8 ... 30 V DC
approx. 0 μA
typ. 9 mA
max. 10 detectors per loop (as per VdS)
LED, red and yellow flag
max. 2,5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in Housing), IP55 with cover 704965
approx. 78 g
EN 54-11, type A
W: 88 mm H: 88 mm D: 21 mm
W: 88 mm H: 88 mm D: 57 mm (with surface mount ​
housing)
4
5
6
7
1 x spare glass pane 704960
1 x multilingual paper labels with "Out of order" pictogram
¬qRT9­
8
Standard MCP electronic module with glass, with 2nd micro-switch - ESSER
804951
Approval:
9
VdS
as 804950, but with second floating micro-switch
1
10
Technical Data
Operating voltage
Quiescent current @ 9 V DC
Alarm current @ 9 V DC
Contact load relay
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
¬qRXE­
804955
8 ... 30 V DC
approx. 0 μA
typ. 9 mA
30 V DC / 1 A
max. 10 detectors per loop (as per VdS)
LED, red and yellow flag
max. 2,5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in Housing), IP55 with cover 704965
approx. 78 g
11
12
13
IQ8MCP electronic module with glass - ESSER
Approval:
1
14
VdS
As 804971 but without housing.
15
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current w/o communication curtain
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
Detector specification
Dimensions
8 ... 42 V DC
approx. 45 μA
approx. 18 mA
max. 127 detectors per loop (as per VdS)
LED, red and yellow flag
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in Housing), IP55 with cover 704965
approx. 78 g
EN 54-11, type A
W: 88 mm H: 88 mm D: 21 mm
16
17
1 x spare glass pane 704960
1 x multilingual paper labels with "Out of order" pictogram
137
Manual Call Points
¬qRYH­
Small Design - ABS
IQ8MCP electronic module with glass, without isolator, with relay - ESSER
804956
Approval:
1
VdS
As 804955, but with relay and without loop isolator or connection possibility for standard ​
manual call points. The relay output is activated by the triggering of this detector. The relay ​
output can be programmed in the IQ8Control and System 8000 fire alarm control panel ​
customer data as a control group.
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current w/o communication curtain
Contact load
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Weight
138
www.hls-austria.com
8 ... 42 V DC
approx. 45 μA
approx. 18 mA
30 V DC / 1 A
max. 127 detectors per loop (as per VdS)
LED, red and yellow flag
max. 2,5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in Housing), IP55 with cover 704965
approx. 78 g
Manual Call Points
Small Design - ABS
1
Plastic Housing - Small Design
Housing for electronic modules 80495x
2
1
Technical Data
Type of protection
Housing
Installation
Weight
Dimensions
IP43, IP55 with 704965
PC ASA plasic housing
surface mount
approx. 33 g
W: 88 mm H: 88 mm D: 21 mm
3
4
1 x key 704966
704950
¬gRS,­
Housing for small MCP, red, similar to RAL 3020
5
The red manual call point housing is available only with the pictogram (as shown) according to ​
EN 54-11.
6
Please note that according to EN54-11, the label for the MCP must include the symbol of the ​
burning house.
7
8
¬gRT/­
Pictogram according to EN54-11
704951
9
Housing for small MCP, blue, similar to RAL 5015
Labelling foil set (white) for various international applications.
10
Accessories
704981
704952
¬gRU2­
11
Housing for small MCP, yellow, similar to RAL 1021
Labelling foil set (black) for various international applications.
12
Accessories
704982
704953
¬gRV5­
13
Housing for small MCP, orange, similar to RAL 2011
Labelling foil set (black) for various international applications.
14
Accessories
704983
704954
¬gRW8­
15
Housing for small MCP, green, similar to RAL 6002
Labelling foil set (white) for various international applications.
16
Accessories
704984
704955
¬gRX;­
17
Housing for small MCP, grey, similar to RAL 7035
Approval:
VdS
Labelling foil set (black) for various international applications.
Accessories
704985
139
Manual Call Points
Small Design - ABS
Sourface Mount Housing - Small Design
1
The surface mount housing serves as cable entry for surface mount cabling. With integ­
rated support for shielding.
Technical Data
Dimensions
W: 88 mm H: 88 mm D: 36 mm
mounting material
704980
¬gRq¨­
Surface mount housing for small MCP, red, similar to RAL 3020
Red, for manual call points 804970, 804971 and 804973, for small design Electronic ​
Modules 804950/51, 804955/56 with housing 704950.
Matériel de montage
704981
¬gRr"­
¬gRs%­
Surface mount housing for small MCP, blue, similar to RAL 5015
Blue, for small design Electronic Modules 804950/51, 804955/56 with Housing 704951.
704982
Surface mount housing for small MCP, yellow, similar to RAL 1021
Yellow, for small design Electronic Modules 804950/51, 804955/56 with Housing 704952.
704983
¬gRt(­
¬gRu+­
¬gRv.­
Surface mount housing for small MCP, orange, similar to RAL ​2011
Orange, for small design Electronic Modules 804950/51, 804955/56 with Housing 704953.
704984
Surface mount housing for small MCP, green, similar to RAL 6002
Green, for small design Electronic Modules 804950/51, 804955/56 with Housing 704954.
704985
Surface mount housing for small MCP, grey, similar to RAL 7035
Grey, for small design Electronic Modules 804950/51, 804955/56 with Housing 704955.
140
www.hls-austria.com
Manual Call Points
Small Design - ABS
Small Design - Accessories
1
704960
2
¬gR]J­
Spare glass pane for small MCP, EN54 - ESSER
Spare glass pane with white sticked on foil and printed pictogram in compliance with EN ​
54-11 (type A). Suitable for small MCP''s.
3
1
Technical Data
Dimensions
W: 56 mm H: 49.5 mm D: 1.85 mm
4
To indicate that the detector is "out- of-order" the operator has to turn round the element, which ​
has on the reverse side a corresponding pictogram.
10 pcs
5
¬gRlw­
704975
Spare glass pane for small MCP, EN54 - neutral
6
Spare glass pane with white stick on foil and printed with pictogram according to EN 54-11 ​
(type A), for small manual call points, without logo.
1
7
Technical Data
Dimensions
W: 56 mm H: 49.5 mm D: 1.85 mm
To indicate that the detector is "out- of-order" the operator has to turn round the element, which ​
has on the reverse side a corresponding pictogram.
8
10 pieces
¬gRaV­
704964
9
Plastic pane, resettable function, for small MCP - ESSER
10
Resettable, white, for small manual call points. Typically applied, for instance, in food ​
processing industries or in clean rooms.
1
To indicate that the detector is "out- of-order" the operator has to turn round the paper inlay, ​
which has on the reverse side the same pictogram as above shown.
11
10 pcs
12
13
2
1
Release
the MCP
Released
MCP
Resetting
the MCP
14
MCP ready
for operation
¬gR^M­
Application example
704961
15
Foil for front face w. universal text for small MCP, white lettering
Universal, punched foil set (transparent with white imprint) for the labelling field, different ​
from the standard pictogram.
16
1
IQ8TAL
IQ8FCT T A L
Transparent foil with white lettering!
17
10 units
Emergency Stop
Gas extinguishing system
Arrêt d'urgence
Système d'extinction à gaz
GENERAL
ALARM
PARO EMERGENCIA PARAGEM EMERGÊNCIA
Sistema de extinción
Sistema de extinção
AMOK-ALARM
POZAR
141
Manual Call Points
704965
Small Design - ABS
¬gRbY­
Protective kit for MCP and TAL, transparent
Transparent, suitable for small MCP''s. The cover serves as a protection to prevent inad­
vertent activation and to protect from high humidity.
1
Technical Data
Type of protection
Material
IP55
plastic cover, transparent
Abdeckung und zwei Neoprenabdichtungen
Application example: Manual call point with mounted cover
¬gRc\­
704966
Plastic spare key for small MCP
Plastic key, red, suitable for small manual alarm units.
1
10 pcs
¬gRd_­
704967
Mounting frame for small MCP, red and white
The mounting frame is useful for mounting MCP's on different international flush mount ​
boxes.
1
Technical Data
Color
Dimensions
Rouge, similaire à RAL 3020 ou blanc
W: 132 mm H: 132 mm D: 8 mm
2 x fastening screws are included (red and white)
Application example: Mounting frame with small MCP
142
www.hls-austria.com
Manual Call Points
761630
1
Special Design
¬m1?¤­
LF-manual activation point low frequency
1
Manual activation point designed according to EN54-11 type B (double action) for manu­
ally triggering of hazard alarms. The device offers low-frequency data transmission over ​
long distances of up to 20 km for monitoring passive third-party detectors and activation ​
via terminal card 772180.
2
Technical Data
Operating voltage
Contact load
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
3
18 ... 30 V DC
microswitch: max. 30 V DC / 1A
10 detectors per zone (according to VdS)
LED red
0,6 mm ... 1,5 mm²
-30 °C ... 70 °C
0.0 ... 0.0
-35 °C ... 75 °C
IP43, IP54 with kit 704070
aluminium die-cast
red, similar to RAL 3000
approx. 700 g
W: 126 mm H: 126 mm D: 42 mm
4
5
6
To operate the 761630, terminal card 772180 is required.
7
This LF Manual Call Point must not be operated as a fire alarm detector for fire alarm systems in ​
accordance to the standard EN54-11. It is suitable only for operation in Hazard alarm systems as ​
release device!
8
To indicate that the detector is "out- of-order" the operator has to insert the paper inlay, which ​
has a corresponding pictogram and wording.
9
1 x glass pane 704910
1 x plastic key 769910
1 x fixing material
1 x "out of order" sign
2 x cable entries
2 x dummy plugs
10
Accessories
11
704910 Spare glass pane, no imprint
¬n6qU­
772180
Terminal card for LF-manual call point 761630
12
Terminal card for LF-manual call point 761630, with indicators for alarm (red), wire break ​
(yellow) and short circuit (yellow). Suitable for mounting on standard mounting rails.
13
1
Technical Data
Operating voltage
Quiescent current
Alarm current
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
24 V DC
approx. 5 mA
20 mA
LED red
0,6 mm ... 1,5 mm²
0 °C ... 50 °C
-5 °C ... 55 °C
IP30
ABS plastic
grey
approx. 300 g
W: 20 mm H: 85 mm D: 55 mm
14
15
16
17
143
Manual Call Points
761694
Special Design
¬m1¡t­
Manual call point Series 9200 addressable, IP66
Addressable manual call point in conformity with EN 54-11 Type B with loop isolator for ​
manually triggering fire alarms or hazard alarms. For out-door application or application in ​
damp environments.
1
Technical Data
Operating voltage
Quiescent current @ 19 V DC
No. of detector/zone
Alarm display
Connection terminal
Application temperature
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
8 ... 42 V DC
approx. 45 μA
max. 10 (according to VdS), 127 / loop
LED, red
max. 1,5 mm²
-20 °C ... 70 °C
0.0 ... 0.0
-25 °C ... 75 °C
IP66
PC-plastic
red, similar to RAL 3000
approx. 475 g
W: 135 mm H: 135 mm D: 61 mm
Please take note, our part no. 769910 and 769911 can be used as spare keys.
Substitute for 761695.
To indicate that the detector is "out- of-order" the operator has to insert the paper inlay, which ​
has a corresponding pictogram and wording.
1 x glass 704910
1 x key and “out of order” sign respectively “Außer Betrieb”
Accessories
704910 Spare glass for MCP
769910 Plastic key for large MCP
769911 Metal key for large MCP
¬g]?m­
706030
Manual call point conventional, IP67, small housing, red
1
Features
• Sealed to IP67
• Unique ‚plug and play’ installation concept
• Anti-tamper facility
• Enhanced aesthetics and compact design
• Approved to EN 54-11
The outdoor MCP is an IP67 sealed product. The enhanced environmental protection ​
allows the unit to be installed in many external environments where water and dirt are likely​
to be present, making it a true waterproof and outdoor product.
The manual call point has a unique ‘plug and play’ concept designed specifically to reduce ​
installation time. The product utilizes a special terminal block, where all initial installation ​
cabling is terminated. This terminal block is then simply connected to the back of the MCP. ​
The housing is supplied with three standard 20mm knock outs for cable entries, accom­
modating all types of surface wiring installations.
The MCP also helps to preserve the integrity of the overall system as illegal removal of the ​
product lid will result in the call point operating and the system going in to alarm.
Technical Data
Application temperature
Storage temperature
Air Humidity
Type of protection
Material
Weight
Detector specification
Dimensions
Accessories
706031 Spare glass pane (5 pcs)
706032 Spare key
706033 Plastic cover
144
www.hls-austria.com
-30 °C ... 70 °C
-30 °C ... 70 °C
< 95 % non condensing
IP67
PC/ABS
approx. 240 g
EN 54-11
W: 97.5 mm H: 93 mm D: 71 mm
Manual Call Points
Special Design
Manual Call Point for Hazardous Areas
1
761697
2
¬m1¤­
Ex manual call point conventional, IP66
Approval:
1
VdS, PTB 97 ATEX 3197
Conventional manual call point in conformity with EN 54-11 Type B for the manual actu­
ation of a fire alarm and/or a hazard alarm, as a detector for usage in explosion-hazardous ​
areas both inside and outside.
3
The operating front foil has been designed as a double-sided insert. Complementary to the ​
symbolism conforming to the standards for manual call points in compliance with EN 54-​
11 (Type B), it has a symbol and multilingual text on the back for the ‘out of order’ status ​
of the detector and is always available for possible maintenance work.
4
5
The labelling foil of the manual call point also has a double-sided design. In compliance ​
with EN 54-11, they contain the standard symbol of a burning house. On the back, the ​
symbol is supplemented with the word “FIRE” (multilingual).
6
Technical Data
Operating voltage
Alarm current
No. of detector/zone
Connection terminal
Application temperature
12 ... 24 V DC
approx. 9 mA
max. 10 detectors per Zone (according to VdS)
0,6 mm ... 4 mm²
-55 °C ... 65 °C
-55 °C ... 85 °C (T5)
-55 °C ... 85 °C
II 2G
Ex e d mb IIC T6, T5
IP66
Glass fiber reinforced polyester resin
red, similar to RAL 3000
approx. 1800 g
DIN 14678 Form K
W: 136 mm H: 138 mm D: 88 mm
Storage temperature
Ex-category
Explosion protection
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
7
8
9
10
Substitute for 761696.
11
Please note, an allen key (size 4) is needed for opening and resetting the MCP, and is not ​
included in the scope of delivery.
12
incl. 1 x glass pane 704910, 1 x kit of double-sided operating front foil (with “out of order” on ​
the back), 1 x kit of double-sided labelling foil (multilingual)
Accessories
13
704910 Spare glass pane for MCP-housings
Out of
Order
fuera
de servicio
Außer
Betrieb
hors
service
FEUER
FIRE
FEU
FUEGO
14
15
Feuerwehr
16
17
Operating front foils and labelling foils
145
Manual Call Points
¬g]?§/FY<­
706030.EX
Ex manual call point conventional, IP67, small housing, red
1
Features
• Sealed to IP67
• Unique ‚plug and play’ installation concept
• Anti-tamper facility
• Enhanced aesthetics and compact design
• Approved to EN 54-11
The Ex MCP is build especially for installation in hazardous areas. It is intended for outdoor ​
use within intrinsically safe systems using suitable barriers.
The outdoor MCP is an IP67 sealed product. The enhanced environmental protection ​
allows the unit to be installed in many external environments where water and dirt are likely​
to be present, making it a true waterproof and outdoor product.
The manual call point has a unique ‘plug and play’ concept designed specifically to reduce ​
installation time. The product utilizes a special terminal block, where all initial installation ​
cabling is terminated. This terminal block is then simply connected to the back of the MCP. ​
The housing is supplied with three standard 20mm knock outs for cable entries, accom­
modating all types of surface wiring installations.
The MCP also helps to preserve the integrity of the overall system as illegal removal of the ​
product lid will result in the call point operating and the system going in to alarm.
Technical Data
Application temperature
Storage temperature
Ex-category
Explosion protection
Air Humidity
Type of protection
Material
Weight
Detector specification
Dimensions
Accessories
706031 Spare glass plane (5 pcs)
706032 Spare key
706033 Plastic cover
764744 Ex-barrier
146
Special Design
www.hls-austria.com
-25 °C ... 70 °C
-25 °C ... 70 °C
II 1GD
Ex ia IIC, T4 Ga
< 93 % ±3% non condensing
IP67
PC/ABS
approx. 350 g
EN 54-11
W: 97.5 mm H: 93 mm D: 71 mm
1
2
3
4
5
6
7
8
9
10
Transponders
esserbus
148-158
11
12
13
14
15
16
17
147
Transponders
esserbus
Professional fire detection systems are expected to provide more than reliable fire detec­
tion and signaling alarms to the fire department. Over time, the continuous progress in ​
technical units has led to many improvements in monitoring and control systems. At the ​
same time the specifications of the European standards are becoming more and more ​
demanding. These complex requirements towards control and monitoring of individual ​
parts of a unit was reason enough to redesign our assortment of esserbus transponders.
Essentially the new assortment consists of the so-called "alarm transponder" which is used ​
for both the connection of non-addressable detectors (point-type detectors, manual ​
detectors and special detectors) as well as for the operation of conventional alarm ​
signaling devices (signaling devices, signal flasher and combination alarm signaling ​
devices). Monitoring of the lines in accordance with the latest standards is ensured via ​
"EOL modules" (end-of-line modules).
The second part is formed by the "FCT" (fire control transponder) and the IQ8TAL being ​
loop-powered input and output transponders with a contact input and a floating relay ​
output for monitoring of contacts and transmission of technical alarms for equipment ​
monitoring.
These modules are for interfacing to other disciplines which are not a part of the fire detec­
tion system itself. Thanks to their intelligent concept they significantly expand the range of ​
monitoring and control functions as part of the building management.
148
www.hls-austria.com
Transponders
808623
¬qw8/
esserbus
1
esserbus alarm transponder
Approval:
VdS
2
The esserbus transponder functions as a device on the multifunctional primary line. The ​
connection of automatic standard detectors, manual call points (non-addressable) as well ​
as special detectors is possible. In addition, two programmable relay outputs are also ​
available.
1
3
Monitoring via the EOL terminating devices (part no. 808624/808626) is required for the ​
connection of fire detectors and for the controlling of alarm signaling devices. The ​
enclosed resistors can be used to connect the floating contacts.
Features
• Conventional connection of standard fire ​detectors
•
•
•
•
and signaling devices
Loop monitoring in compliance with EN 54-13
Integrated line isolator
Programmable relay outputs
Programmable relay reset function
4
The overall planning for the alarm signaling devices to be connected is carried out via a ​
calculation tool which is a component of the tools 8000 programming software (Version V ​
1.15 and above).
5
The esserbus alarm transponder requires an external voltage supply. An optional Voltage ​
Converter (part no. 781336) is also required for 12V DC operation. The esserbus alarm ​
transponder external voltage supply can be monitored during operation.
6
The EOL-I terminating device (part no. 808626) is to be used for standard-compliant ​
monitoring of detector zone inputs. The EOL-O (part no. 808624) is to be used for ​
standard-compliant monitoring of connected alarm signaling devices.
7
Technical Data
Rated voltage
Operating voltage
Quiescent current @ 12 V DC
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
CE certificate
Dimensions
8
8 V DC, max. 42 V DC
10 ... 28 V DC
approx. 12 mA
max. 120 mA @ 12 V DC
30 V DC / 1 A
10 °C ... 50 °C
25 °C ... 75 °C
IP40 (in housing)
approx. 28 g
0786-CPD-20947
W: 82 mm H: 72 mm D: 20 mm
9
10
11
Installation Accessory Pack
Accessories
¬qw92
808624
788603.10
788600
788650.10
788601
788651.10
788612
781336
808624
808626
12
Module housing for snap-on mounting rail
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
Loop isolator for transponder
DC/DC converter output voltage
EOL-O Terminating Device
EOL-I Terminating Device
13
14
15
EOL-O terminating device
The EOL-O terminating device is mounted on the last control input device in the detector ​
zone and is used to monitor alarm signaling devices.
16
1
17
Features
• Used for monitoring of control outputs with ​
conventional alarm signaling devices being ​
connected
• Additionally recognizes creeping interruptions and ​
short-circuits
• Loop monitoring in compliance with EN 54-13
149
Transponders
¬qw;8
808626
esserbus
EOL-I terminating device
The EOL-I terminating device is mounted on the last device in the detector zone and is ​
used to monitor detector zone inputs.
1
Features
• Used for monitoring of detector zone inputs with ​
standard fire detectors being connected
• Additionally recognizes creeping interruptions and ​
short-circuits
• Loop monitoring in compliance with EN 54-13
¬qw!§/341`­
808600.230
esserbus transponder FCT Set 230 V
Approval:
1
Features
• 230 V AC operation with optional function monit­
•
•
•
•
•
•
•
•
oring
Comprehensive fail-safe function during failure of ​
the loop or mains voltage
Freely programmable relays
Monitored outputs for monitoring of external ​
devices
Time-dependent control of relay outputs
Optional: relay outputs with programmable ​
impulse lengths
Reduction of amount of data via selectable soft­
ware function
Integrated loop isolator
Optional IP protection base for usage in difficult ​
ambient conditions
VdS
The FCT is used for the monitoring and operation of fire control systems such as ventila­
tion, pressure monitor pumps, extinguishing agent sprinklers, elevators and many more. ​
Time-dependent machine shutdowns can be carried out via two freely programmable ​
relays. The pluggable modules (up to two electronic modules can be connected) are each
equipped ​with a contact input for operational feedback.
The comprehensive "fail-safe" function ensures that the transponder maintains full func­
tionality and remains a self-sufficient activation device even if the fire alarm control panel ​
or field bus fails.
Using the 230 V version the mains voltage can be switched directly and be simultaneously ​
used to power the transponder. It is also possible to indirectly monitor the function of the ​
mains voltage using internal logic.
The FCT essentially requires an external voltage supply. For the operation on 12 V DC the ​
optional voltage converter (Part No. 781336) is required.
The esserbus transponder FCT 12-24 V or 230 V is used as a loop device for the IQ8Con­
trol or FlexES control fire alarm control panels. The tools 8000 programming software (as ​
of version V1.15.1) is necessary for the start-up.
Technical Data
Rated voltage
Rated frequency
Rated current
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Type of protection
CE certificate
1 x FCT control module
1 x FCT electronic module
1 x surface mounted housing
150
www.hls-austria.com
230 V AC
50 ... 60 Hz
0.01 A
30 V DC / 4 A, 230 V AC / 4 A
max. 2,5 mm²
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30 (in housing)
IP55 (with IP-base composition 788655)
0786-CPD-20991
Transponders
808600.24
¬qw!§/35N­
esserbus
1
esserbus transponder FCT Set 12 - 24 V
Approval:
1
VdS
Rated voltage
Operating voltage
Rated frequency
Rated current
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Type of protection
¬owX&­
CE certificate
788655
2
Technical Data
10 ... 30 V DC / 10 ... 24 V AC
10 ... 30 V DC
50 ... 60 Hz
0.2 A
30 V DC / 4 A, 230 V AC / 4 A
max. 2,5 mm²
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30 (in housing)
IP55 (with IP-base composition 788655)
0786-CPD-20991
3
4
5
IP base adapter for FCT
6
IP base adapter for extreme environmental conditions.
1
Technical Data
Type of protection
7
IP55
8
9
¬qRr,­
804981
IQ8FCT electronic module
10
Pluggable electronic module for FCT expansion with another monitoring contact input.
1
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current
No. of detector/zone
Operation indicator
Alarm display
Connection terminal
¬qRq)­
804980
11
8 ... 42 V DC
approx. 45 μA
approx. 9 mA
max. 127 per loop
green LED
red LED
max. 2,5 mm² (AWG 26-14)
12
13
IQ8TAL electronic module
14
As 804981 but with TAL functionality (1 input / 1 output)
1
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current
No. of detector/zone
Operation indicator
Alarm display
Connection terminal
15
8 ... 42 V DC
approx. 45 μA
approx. 9 mA
max. 127 per loop
green LED
red LED
max. 2,5 mm² (AWG 26-14)
16
17
151
Transponders
808610.10
esserbus
¬qw+§/21J­
esserbus transponder 12 relays (8bit)
Approval:
1
VdS, CNBOP, BOSEC
The esserbus transponder works as a loop device on the multi-functional primary line. ​
With the 12 x relay module, it is possible to expand the number of exits per control unit. ​
Depending on the control unit, It can be integrated or used with fire detectors in mixed ​
operation. Max. of 32 esserbus transponders can be connected on one loop. The esserbus ​
transponder can be optionally extended by adding the additional isolator board 788612. ​
esserbus transponder voltage supply: via the multi-functional primary line. The esserbus ​
transponder can be wired with an external switching voltage of 12V DC or 24V DC for the ​
K1 to K12 relays. The external voltage supply of the transponder can be programmed to be ​
monitored in the customer data in the operating mode. In the “floating” operating mode, ​
no external switching voltage of the relays is necessary. 11 relays are freely programmable, ​
the 12th relay is exported as locking contact. The maximum line length from the ​
transponder to the external device is up to 1000 m.
Technical Data
Operating voltage
Current consumption @ 12 V DC
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
10 ... 28 V DC
approx. 3 mA
30 V DC / 1 A (max. 3 A each transponder)
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 110 g
W: 150 mm H: 82 mm D: 20 mm
Accessories
788612
788600
788650.10
788601
788651.10
¬qw,§/21M­
808611.10
Loop isolator PCB
Surface mounting housing grey, similar to RAL 7035
Surface mounting housing white, similar to RAL 9003
Flush mounting housing grey, similar to RAL 7035
Flush mounting housing white, similar to RAL 9003
esserbus transponder 32 LED
Approval:
1
VdS, CNBOP, BOSEC
The esserbus transponder works as a loop device on the multi-functional primary line. 32 ​
outputs for direct LED control (e.g. indicator) are found on this esserbus transponder ​
module. There is one terminal screw per output on the switching mechanism. The outputs ​
can be used for positive or negative signals (programming required). Max. of 32 esserbus ​
transponders can be connected on one loop. The module can be extended by adding the ​
additional isolator board 788612. esserbus transponder voltage supply: via the multi-func­
tional primary line. The esserbus transponder requires an external switching voltage of 10 ​
V DC to 15 V DC.
The external voltage supply of the transponder can be programmed to be monitored in ​
operating mode. The maximum line length from the transponder to the external device is ​
up to 100 m.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 3 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 95 g
W: 150 mm H: 820 mm D: 20 mm
Accessories
788612
788600
788650.10
788601
788651.10
152
www.hls-austria.com
Loop isolator PCB
Surface mounting housing grey, similar to RAL 7035
Surface mounting housing white, similar to RAL 9003
Flush mounting housing grey, similar to RAL 7035
Flush mounting housing white, similar to RAL 9003
Transponders
808613.30
esserbus
¬qw.§/41_­
1
esserbus transponder SST
Approval:
1
VdS
2
esserbus transponder Standard interface EXTINGUISHING for connection of extinguishing ​
systems to the fire detection system.
An external switching voltage of 12 V DC or 24 V DC can be connected to the esserbus ​
transponder. The voltage converter (part no. 781336) is required for 12 V DC operation. ​
The transponder’s external voltage supply can be programmed with supervision in oper­
ating mode.
3
4
Technical Data
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 10 mA
max. 120 mA
30 V DC / 1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
5
6
7
1 x additional equipment pack with 3,3 k and 680 R terminating resistor for SST
Accessories
788603.10
788600
788650.10
788601
788651.10
788612
781336
¬qw/§/21V­
808614.10
Module housing for C-mounting bar or top hat rail mounting
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
Loop isolator PCB
DC/DC converter output voltage
8
9
10
esserbus transponder 1 IN
Approval:
1
VdS, CNBOP, BOSEC
11
The esserbus transponder works as a lbus device on the multifunctional loop.
Conventional automatic detectors and manual alarm units can be connected without ​
addressing:
- up to 31 esserbus transponders 1 zone / 2 relays on one multifunctional primary loop
- up to 30 conventional detectors per zone without SOC
- up to 10 conventional detectors per zone with SOC
- up to 10 non-automatic or technical alarm devices per zone
12
13
External power supply is required for transponder operation. Optional voltage monitoring.
14
Technical Data
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 3 mA
max 120 mA
30 V DC / 1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
15
16
17
Plug terminals are included
Phase-out date: 01.01.2011
Accessories
788603.10 Module housing for C-mounting bar or top hat rail mounting
788612
Loop isolator PCB
153
Transponders
808615
esserbus
¬qw0~­
esserbus communication transponder
With this esserbus transponder the extinguishing relay output 8010 can be integrated on ​
the bus of panel 8000 or IQ8Control, thus enabling several extinguishing zones to be ​
networked with each other. On each bus, a maximum of eight 8010 extinguishing relay ​
outputs can be operated and respectively a maximum of 16 communication transponder ​
per FACP8000 C/M or IQ8Control. All indicators and controls can be activated from the fire ​
alarm panel. The communication transponder occupies one address on the esserbus.
1
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 3 mA
approx. 28 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 28 g
W: 72 mm H: 65 mm D: 20 mm
Mounting: in the housing of the 8010 extinguishing realy output
including loop isolator PCB (788612)
¬qw4§/21e­
808619.10
esserbus FSA transponder for door release application
Approval:
1
Features
• Usage of series 9200 intelligent detectors (such ​
•
•
•
•
•
•
154
as OT, OTI, O²T detectors) as FSA detectors is ​
possible
Connection of IQ8Quad O detectors (part no. ​
802371), TD Detectors (part no. 802271), OT ​
detectors (part no. 802373) and O²T detectors ​
(part no. 802374) (DIBt-approved) as FSA ​
detectors is possible
FSA detectors programmable as devices in the ​
loop
Status indicator of door arrester system to the fire ​
alarm control panel
Actuation of the locking device also via the auto­
matic fire detectors in non-FSA operation
Stand-alone operation of the FSA transponders is ​
possible
Usage of IQ8Quad O detectors (part no. 803371), ​
TD detectors (part no. 803271) and O²T detectors ​
(part no. 803374) in stand-alone operation of the ​
FSA transponders to the standard detector group ​
is possible
www.hls-austria.com
VdS
The transponder is suitable for usage for various applications: in stand-alone operation or ​
on the esserbus. In esserbus operation, the Series 9200 automatic fire detectors and those ​
of the IQ8Quad family (see feautures for types) can be used as detectors in door arrester ​
systems (FSA). In FSA transponder loop operation, the door arrester system status is ​
indicated on the fire alarm control panel.
For stand-alone operation, detectors of the IQ8Quad family are supported without loop ​
isolator (see features for types).
Up to a maximum of 31 IQ8Quad detectors per detector group input can be connected ​
without isolator, depending on object conditions.
For operation, the transponder requires an external supply voltage. It is possible to monitor ​
this voltage.
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
8 ... 42 V DC
10 ... 28 V DC
approx. 6 mA (from UB ext)
max. 28 mA (from UB ext)
max. 30 V DC/1 A or 48 V DC/0,5 A
-5 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 70 g
W: 72 mm H: 65 mm D: 20 mm (PC Board)
Corresponding connection examples for FSA transponder operation in stand-alone operation or ​
as a device in the fire detection system 8000 can be found in the chapter containing automatic ​
door release systems.
Accessories
788612
788603.10
788600
788650.10
788601
788651.10
808625
Loop isolator PCB
Module housing for C-mounting bar or top hat rail mounting
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
EOL-Z
Transponders
808622
esserbus
¬qw7,­
1
esserbus transponder for UniVario
Approval:
1
VdS
2
The esserbus transponder works as a loop device on the multifunctional primary line.
Input transponder with 4 monitored contact inputs for the activation of detectors from the ​
UniVario family of products. Two floating relay contacts for controlling functions are addi­
tionally available.
3
- max. 31 esserbus transponders on a multifunctional primary line
- max. 1 detector from the UniVario family of products per zone
4
Technical Data
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 6 mA
max. 120 mA
30 V DC / 1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
5
6
7
2 x EOL-Z (part no. 808625)
Accessories
788612
788600
788650.10
788601
788651.10
¬qw?§/21¨­
808630.10
Loop isolator PCB
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
8
9
Refurbishment zone transponder RZT 8000
Approval:
1
10
VdS
The refurbishment zone transponder is a stand-alone participant on the esserbus for the ​
fire alarm system 8000 and IQ8Control fire alarm control panels. Individual automatic fire ​
detectors and manual call points (conventional technology) from other manufacturers can ​
be connected to the 4 zone inputs. The voltage of all 4 zones can be configured to 24 V via ​
the internal DC/DC module. An additional reset module is not required to operate third-​
party detectors.
11
12
Technical Data
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Weight
Dimensions
13
10.5 ... 13.8 V DC
max. 1250 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
approx. 150 g
W: 150 mm H: 82 mm D: 20 mm
14
Whether or not a connection is possible must be individually checked in advance by the t​echnical
sales department.
15
Accessories
788612
788600
788601
788650.10
788651.10
Loop isolator PCB
Housing surface mount, grey
Housing flush mount, grey
Housing surface mount, white
Housing flush mount, white
16
17
155
Transponders
808631.10
esserbus
¬[email protected]§/21"­
Refurbishment zone transponder (RZT) / 12 V - ESSER
As 808630.10, but rated voltage is 12 V DC, not configurable.
1
Technical Data
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Weight
Dimensions
10.5 ... 13.8 V DC
max. 1250 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
approx. 150 g
W: 150 mm H: 82 mm D: 20 mm
Accessories
788600
788650
788601
788651
788605
788602
788603
esserbus transponder housing aP grey
esserbus transponder housing aP white
esserbus transponder housing uP grey
esserbus transponder housing uP white
Installation kit
C-rail
Module housing
Accessories esserbus Transponders
¬ow-s­
788612
Loop isolator for transponders
Loop isolator PCB to be mounted on esserbus transponders. To isolate short circuit failure ​
and wire break on the loop.
1
Technical Data
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
¬qw:5­
808625
EOL-Z Module for detector groups
1
156
6 V DC
3 µA
-20 °C ... 50 °C
-20 °C ... 75 °C
IP50 (with housing)
approx. 10 g
W: 32 mm H: 20 mm D: 10 mm
www.hls-austria.com
Terminating device for the monitoring of standard-inputs when using esserbus transpon­
ders (part no. 808613.20, 808622, 808619.10).
The zener diode is sealed in the housing of the end-of-line (EOL) module.
Transponders
esserbus
1
Technical Alarm Modules
¬qQfm­
804869
2
IQ8TAM technical alarm module for snap-on mounting
Approval:
VdS
3
The technical alarm module IQ8TAM is a bus device of the fire alarm system 8000 for ​
recognition, transmission and individual display of technical alarms.
1
Each IQ8TAM includes an integrated loop isolator, which opens in case of loop short circuit ​
to isolate the part of the loop between two loop isolators. A single wire break does not ​
effect the loop and all devices remain in operation. The module does not require external ​
voltage supply, as voltage is supplied by the field bus.
4
5
Technical Data
Operating voltage
Alarm display
Connection terminal
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
8 ... 42 V DC
LED, red
max. 1,5 mm²
-20 °C ... 70 °C
-30 °C ... 75 °C
IP30
PA 66 - plastic
grey, similar to RAL 7035
approx. 87 g
W: 25 mm H: 112 mm D: 99 mm
6
7
8
The module can either be mounted in an appropriate installation position in the housing of the ​
fire alarm panel or, for example, on a C-rail of a switch cabinet. Each module can be individually ​
connected or cascaded directly snap-on or on side connector block.
9
incl. 4 screw clamps and 1 resistor
10
11
12
¬qQgp­
Alarm and monitoring module for IQ8TAM
1
13
An external, monitored contact can be connected to the terminals of the IQ8TAM technical ​
alarm module for C-rail mounting with part no. 804869. In case of contact activation, the ​
address and the programmed additional text of the corresponding IQ8TAM technical alarm ​
module will be displayed.
14
For contact monitoring, the alarm and monitoring module for IQ8TAM (part no. 804870) is ​
required.
15
The max. cable length to the connected module must not exceed 250 meters!
16
10K
804870
1K
17
e.g.
pressure controller
IQ8TAM, max. 250 m line length
Inside wiring diagram for alarm and monitoring module
157
Transponders
804868
¬qQej­
esserbus
IQ8TAL technical alarm module
Approval:
1
VdS
The IQ8TAL Technical Alarm Module is a full-fledged loop device of the IQ8Control fire ​
detection system and it facilitates the detection and forwarding of technical alarms.
The IQ8TAL is equipped with an integrated loop isolator, a contact input and a relay output. ​
The relay can be optionally configured as a normally-closed contact or as a normally-open ​
contact. The IQ8TAL does not need a separate voltage supply.
In order to increase the IP protection class, the optional IP protection kit (Part No. 704965) ​
can be used.
Features
• One contact input and one floating relay output
• Voltage supply via the field bus
• Test and reset function
• Higher IP protection
• Programmable inverse monitoring functionality of ​
•
•
•
•
the contact input (1k resistance latent/10k resist­
ance fire)
Powered by the FACP
Total cable length of the external contact up to ​
500 m
Integrated loop isolator
Up to 127 IQ8TAL per ring loop
The functionality of the Technical Alarm Module can be tested with the included key and the​
alarm status can be reset directly at the IQ8TAL.
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Contact load relay
Operation indicator
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
8 ... 42 V DC
approx. 45 μA
30 V DC / 1 A
green LED
red LED
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP43 (in housing)
IP55 (with optional IP Kit 704965)
PC/ASA plastic
blue, similar to RAL 5015
approx. 110 g
W: 88 mm H: 88 mm D: 21 mm
W: 88 mm H: 88 mm D: 57 mm (with surface-mounted ​
housing)
Please note that for surface mounting the mount housing (part no. 704981) must be used. ​
Compatible with all IQ8 Control systems with firmware V3.08 and tools 8000 V1.14 or superior.
2 x 10 k (terminating), 1x 10 k pre-assembled, and the rest included as additional package
1 x 1 k (alarm),
1 x 6 k 8 (inverse operation)
Accessories
704965 MCP Cover for small housing, transparent
704981 Surface mount housing for small MCP, blue
804867
IQ8FCT
1
Same as IQ8TAL 804868, but with additional FCT software functionality.
The FCT is used for the monitoring and operation of fire control systems such as ventila­
tion, pressure monitor pumps, extinguishing agent sprinklers, elevators and many more. ​
Time-dependent machine shutdowns can be carried out via one freely programmable ​relay.
Technical Data
Storage temperature
Type of protection
Weight
CE certificate
Features
• Runtime monitoring
• Monitoring 2 states with an input
• Steady or impulsive triggering of relay output
• Monitored outputs for monitoring of external ​
devices
• Integrated loop isolator
158
www.hls-austria.com
-30 °C ... 75 °C
IP43 (in housing)
approx. 110 g
0786 – CPD – 20792
Accessories
704965 MCP Cover for small housing, transparent
704985 Surface mount housing for small MCP, grey
1
2
3
4
5
6
7
8
9
10
Wireless Component
Wireless Modules
160-166
11
12
13
14
15
16
17
159
Wireless Component
Features
Radiocommunication transmission features
• Interference-proof transmission via dual band ​
with frequency hopping
• Bi-directional data traffic
• Permanent automatic interference monitoring of ​
transmission path
• In case of interferences, automatic modification of ​
frequency band and radiocommunication channel
• Band blocking detection
• High transmission range (in the open air: max. ​
300 m)
• Automatic interference detection due to low field ​
strength levels
Wireless Modules
The following wireless modules are only compatible with IQ8Control panel. Communica­tion
between the RF devices is set up via a dual band transmission mode. The RF-​technology
applys frequency hopping to enable highest transmission security. In case of ​interference,
the frequency band and the radiocommunication channels are automatically ​modified. If
the entire band and the receiver are blocked due to high interference level, a f​ault signal is
transmitted to the fire alarm panel. Thus, secure and reliable wireless trans­mission is
provided.
The transmission range in open air is up to 300 m. Inside the building, the transmission ​
range varies, depending on building structure, wall thickness or use of concrete steel.
IQ8Wireless radio technology facilitates the cable-free connection of IQ8Quad automatic ​
fire detectors (with and without alarm signaling devices), manual call points and the ​
IQ8Alarm alarm signaling device to the IQ8Control fire alarm system.
Already existing fire alarm systems can be expanded using the wireless technology or ​
complete fire alarm systems can be realised for smaller objects with wireless components ​
as well.
The allocation of the wireless components to a wireless transponder or wireless gateway ​
takes place via the tools 8000 programming software.
The status of the batteries is checked automatically and their necessary replacement is ​
displayed early on as a detector failure on the fire alarm control panel and/or the wireless ​
transponder*.
The optimal installation site as well as the maximum possible transmission distance can be ​
conveniently and quickly transmitted via the tools 8000’s integrated field strength meas­
urement.
* during allocation of the wireless components via wireless transponder
Please take into account that the use of wireless components requires an extra training, covering ​
project planning and commissioning. For further information see our training brochure.
These devices were designed, produced and labelled for operation within the countries of the ​
European Union (EU) in accordance with the current EU standards and requirements. In case the ​
device is installed outside of the EU, national guidelines and requirements must be taken into ​
consideration.
For further information, please contact your local sales representative.
Using components like IQ8Alarm and IQ8Quad with intergrated alarm devices the esserbus PLus ​
is needed.
max. 32 wireless detectors
max. 10 control groups
12V DC
esserbus-PLus
max.
10 wireless
call points
Connection example
160
www.hls-austria.com
Wireless Component
¬qX~§/217­
805593.10
Wireless Modules
1
IQ8Wireless detector base
Approval:
VdS
2
With the IQ8Wireless base, the wireless component is located in the base onto which the ​
respective fire detectors is placed. The wireless base facilitates the connection of the ​
IQ8Quad TM, TD, O, O2T and OTG detectors via a wireless transmission line to the
esser­bus/esserbus-PLus and integrates them via wireless transponder or wireless gateway
into ​the fire alarm system.
A maximum of 32 radio bases per wireless transponder and/or 10 per radio gateway can ​
be allocated.
1
3
4
Technical Data
Wireless base
135 mm
43,5
mm
Wireless base with Detector
86
mm
Features
The wireless detector base suitable for
• Fixed heat detector (802171, 802177)
• Rate-of-rise heat detector (802271, 803271)
• Optical smoke detector (802371, 803371)
• O²T multisensor (802374, 803374)
• OTG multisensor (802473)
The wireless detector base features
• Individual detector identification on the control ​
panel
• Regular functionality check for each detector ​
(alarm and operation display on the detector)
• Alarm and fault transmission in accordance with ​
EN 54-2
• Easy detector or battery replacement with d​ etector
removal tool
• Fault signal when the mounted wireless base and ​
the inserted detector are removed
• Permanent monitoring of battery voltage
Operating voltage
Current consumption
Battery operating time
Range inside
Range outside
Frequency band 1
Frequency band 2
Transmitter power
Sensitivity
Data transmission speed
Application temperature
Storage temperature
Air Humidity
Type of protection
Material
Color
Weight
Specification
Dimensions
4 x 3,6 V batteries
approx. 50 µA
approx. 2 years*
max. 30 m
max. 300 m
433 MHz with 20 channels
868 MHz with 5 channels
10 mW
-100 dB
19,2 Kbit/s
-5 °C ... 55 °C
-20 °C ... 70 °C (w/o batteries)
25 °C bis -10 °C (with batteries)
< 95 % (non-condensing)
IP42
ABS-V0
white, similar to RAL 9010
approx. 315 g (incl. batteries)
EN 54-25 submitted
Ø: 135 mm H: 49 mm (with detector H: 88 mm)
5
6
7
8
9
10
The batteries to be used are components of the device approval according to EN 54 and are ​
specified by the manufacturer. With the IQ8Wireless radio components, only the approved ​
batteries with part no. 805597 may be used. Use of batteries other than those specified by us ​
automatically voids the product’s device approval (VdS-approval) and may not be used for ​
example in Germany in fire alarm systems under legal building regulations.
11
*The battery operating time is dependent on the type of detector/device used, as well as the ​
application temperature and additional surrounding conditions. It can be substantially restricted ​
by increased current consumption of the wireless devices in the case of alarm, wireless ​
interference or poor transmission, or even possibly through contact resistance at the contacts. ​
Please note important instructions for usage of batteries in FB 798941.
12
4x 3.6V lithium batteries 805597 and 1x standard detector base for IQ8Quad 805590 with an ​
additional factory-installed wire jumper
13
Accessories
805597 4 x 3.6V lithium batteries
14
15
16
17
161
Wireless Component
¬qX¡§/21:­
805594.10
IQ8Wireless gateway for devices
Approval:
1
Wireless base
135 mm
43,5
mm
Wireless base with Detector
86
mm
Features
• The wireless gateway can be mounted between ​
•
•
•
•
•
•
•
•
•
•
•
•
•
Wireless Modules
detector base and IQ8Quad detector. No additional ​
wiring required
Suitable for IQ8Quad detectors w/o alarm devices
Wireless communication with up to 10 users
Maximum 10 wireless bases
Maximum 10 wireless interfaces with IQ8MCP ​
manual call points
Maximum 10 control groups for wireless interface ​
with IQ8Quad/IQ8Alarm alarm signaling devices
All wireless devices are integrated as individually ​
addressable on the esserbus / esserbus-PLus
esserbus integration of all radiocommunication ​
devices as individually addressable users
The radiocommunication devices can be allocated ​
in up to 10 detector zones
Up to 9 wireless gateways per loop
Alarm and trouble transmission in accordance ​
with EN 54-2
Easy detector or battery replacement via detector ​
removal tool
Trouble signal when removing the gateway and ​
the detector
Permanent monitoring of battery voltage
VdS
This wireless gateway is especially designed for convenient and time-saving expansion of ​
an already existing IQ8Control fire detection system. By removing a detector already ​
installed on the loop and adding the wireless gateway to the standard IQ8 detector base, up​
to 10 additional fire detectors equipped with wireless detector bases or 10 addressable ​
manual call points can be added to the existing system. Up to 10 components with alarm ​
signaling functions – IQ8Alarm alarm signalling devices and/or IQ8Quad fire alarms with ​
integrated alarm signaling device – can be connected per wireless gateway via the ​
universal wireless interface. And all this without any additional cabling. Depending on the ​
surrounding conditions, the wireless transmission can reach up to 200m. The wireless ​
gateway must fundamentally be operated with an IQ8Quad detector. It integrates the intelli­
gent IQ8 wireless components into the esserbus or esserbus-PLus via the wireless base or ​
wireless interface, thus making these components fully individually addressable loop ​
devices.
Up to 9 wireless gateway can be operated on the loop. Each wireless gateway reduces the ​
maximum number of esserbus devices by 12 pieces.
Technical Data
Operating voltage
Voltage supply
Current consumption
Battery operating time
Range inside
Range outside
Frequency band 1
Frequency band 2
Transmitter power
Sensitivity
Data transmission speed
Application temperature
Storage temperature
Air humidity
Type of protection
Material
Color
Weight
Specification
Dimensions
8 ... 42 V DC
4 x 3.6 V lithium battery
400 µA to max. 2,5 mA
approx. 3 years*
max. 20 m
max. 200 m
433 MHz with 20 channels
868 MHz with 5 channels
10 mW
-100 dB
19,2 Kbit/s
-5 °C ... 55 °C
-20 °C ... 70 °C (w/o batteries)
25 °C bis -10 °C (with batteries)
≤ 95% (w/o condensation)
IP42
ABS
white, similar to RAL 9010
approx. 265 g (incl. batteries)
EN 54-25 submitted
Ø: 135 mm H: 49 mm (with detector H: 88 mm)
The standard detector base version IQ8Quad 805590 is not included in the RF gateway package.
The batteries to be used are components of the device approval according to EN 54 and are ​
specified by the manufacturer. With the IQ8Wireless radio components, only the approved ​
batteries with part no. 805597 may be used. Use of batteries other than those specified by us ​
automatically voids the product’s device approval (VdS-approval) and may not be used for ​
example in Germany in fire alarm systems under legal building regulations.
*The battery operating time is dependent on the type of detector/device used, as well as the ​
application temperature and additional surrounding conditions. It can be substantially restricted ​
by increased current consumption of the wireless devices in the case of alarm, wireless ​
interference or poor transmission, or even possibly through contact resistance at the contacts. ​
Please note important instructions for usage of batteries in FB 798941.
4x 3.6V lithium batteries
162
www.hls-austria.com
Wireless Component
¬qX¢§/21=­
805595.10
1
136
mm
280
mm
144
mm
39
mm
Features
• RF communication with up to 32 users
• maximum 32 wireless bases
• maximum 10 wireless interfaces with IQ8MCP ​
manual call points
• maximum 10 control groups for wireless interface ​
•
•
•
•
•
•
1
IQ8Wireless transponder for devices, wall mount
Approval:
200 mm
Wireless Modules
with IQ8Quad/IQ8Alarm alarm signaling devices
esserbus integration of all RF. Devices as individu­
ally addressable users
The RF devices can be assigned in up to 32 ​
detector zones
Alarm and fault transmission in accordance with ​
EN 54-2
Connection to esserbus of IQ8Control panel as ​
bus device as well as to a conventional detector ​
zones
Stand-alone operation
Potential-free outputs for common fault and ​
common fire
VdS
This wireless transponder is designed for wall mounting. The wireless transponder ​
communicates with to to 32 other wireless devices. These can be wireless of various types ​
from intelligent automatic fire detectors or wireless interfaces with manual call points and/​
or alarm signaling devices of the IQ8-family. Using the System IQ8Control, the wireless ​
transponder integrates the intelligent automatic detectors (with and without alarm ​signaling
devices), manual call point and alarm generator IQ8Alarm in the esserbus / ​esserbus-PLus
via the wireless base and/or wireless interface. The detector base allows e​ sserbus
integration of intelligent automatic detectors as bus devices with individual a​ ddressing via
the transponder. Up to 10 transponders can be operated on one loop. The t​ransponder can
be linked with the loop as well as with a conventional detector zone or it c​ an be operated as
a stand-alone unit. Potential-free outputs for common fault and c​ ommon fire are available.
For system 8000 the transponder for RF devices can only be ​connected by using a
potential-free relay to 4IN/2Out or 1IN transponder, because it is not ​compatible with panel
8000 and it cannot be used as bus device.
2
The transponder needs an external supply voltage for operation.
6
3
4
5
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current @ 12 V DC
Range inside
Range outside
Frequency band 1
Frequency band 2
Transmitter power
Sensitivity
Data transmission speed
Contact load relay
Application temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Specification
Dimensions
7
9 ... 30 V DC
approx. 17 mA
approx.18 mA
max. 30 m
max. 300 m
433 MHz with 20 channels
868 MHz with 5 channels
10 mW
-100 dB
19,2 Kbit/s
30 V DC / 1A
-5 °C ... 55 °C
-10 °C ... 60 °C
≤ 95% (w/o condensation)
IP42
ASA + PC
white, similar to RAL 9010
approx. 250 g
EN 54-25 submitted
W: 200 mm H: 280 mm D: 39 mm (with detector H: 88 ​
mm)
8
9
10
11
12
The external power supply of the IQ8Wireless transponder can come from the fire alarm control ​
panel or from an external power unit.
13
The voltage for the wireless transponder can be supplied by the fire alarm control panel or an ​
external power supply. An individual, separately protected supply line is to be installed for the ​
voltage supply. The external voltage supply is monitored by the wireless transponder. If the ​
wireless transponder is installed as a device on the IQ8Control fire detection system analogue ​
loop, a disturbance is transmitted to the fire detection control unit via the loop and is indicated ​
there.
14
15
16
17
163
Wireless Component
Wireless Modules
¬qY"§/21Z­
805601.10
IQ8Wireless universal interface w/o cover, red
Approval:
1
VdS
The radio interface allows the IQ8 manual call point (small or large design) to be connected ​
on the wireless esserbus-PLus.
The radio interface connects the intelligent IQ8 manual call point to the esserbus/powered ​
loop via the IQ8wireless transponder or the IQ8wireless gateway. Thus, the devices are ​
automatically converted into individually addressable loop devices.
Technical Data
Features
Radio interface suitable for:
• IQ8 manual call point - electronic module, large ​
design (part no. 804905/ 804906)
• IQ8 manual call point – complete package, small ​
design (part no. 804971)
• IQ8 manual call point - electronic module, small ​
design (part no. 804955), only with mounting ​
frame (part no. 704967)
• IQ8Quad detectors (with and without alarm ​
signaling devices)
• IQ8Alarm alarm signalling device (part no. ​
8073xx)
Radio interface features:
• The IQ8 components are individually identified on ​
the fire alarm control panel
• Regular functionality performance checks of IQ8 ​
components
• Fault signal when the IQ8 components are ​
removed from the fire alarm control panel
• Operating mode display directly at the IQ8 manual ​
call point and IQ8Quad detector
• Alarm and fault message transmission in compli­
ance with EN 54-2
• Easy detector removal and battery replacement ​
using multifunctional key
• Remote operation of IQ8 components possible ​
(max. 3 meters) via 2-wire line
• Constant battery status monitoring
• Early battery replacement notification at the fire ​
alarm control panel
Operating voltage
Current consumption
Battery operating time
Range inside
Range outside
Frequency band 1
Frequency band 2
Transmitter power
Sensitivity
Data transmission speed
Application temperature
Storage temperature
Air humidity
Type of protection
Material
Color
Weight
Specification
Dimensions
4 x 3,6 V batteries
approx. 30 μA
approx. 2 years*
max. 30 m
max. 300 m
433 MHz with 20 channels
868 MHz with 5 channels
10 mW
-100 dB
19,2 Kbit/s
-5 °C ... 55 °C
-20 °C ... 70 °C (w/o batteries)
25 °C bis -10 °C (with batteries)
≤ 95% (w/o condensation)
IP42
PC/ASA plastic
red, similar to RAL 3020
approx. 285 g (incl. batteries, without attachment)
EN 54-25 submitted
W: 135 mm H: 135 mm D: 20 mm (without a​ ttachment)
Only use small manual call points with mounting frame part no. 704967.
The batteries to be used are components of the device approval according to EN 54 and are ​
specified by the manufacturer. With the IQ8Wireless radio components, only the approved ​
batteries with part no. 805597 may be used. Use of batteries other than those specified by us ​
automatically voids the product’s device approval (VdS-approval) and may not be used for ​
example in Germany in fire alarm systems under legal building regulations.
*The battery operating time is dependent on the type of detector/device used, as well as the ​
application temperature and additional surrounding conditions. It can be substantially restricted ​
by increased current consumption of the wireless devices in the case of alarm, wireless ​
interference or poor transmission, or even possibly through contact resistance at the contacts. ​
Please note important instructions for usage of batteries in FB 798941.
4 x lithium battery 3.6V (part no. 805597)
805601/ -02
704967
Application example for large MCP
164
www.hls-austria.com
Wireless Component
¬qY#§/21]­
805602.10
Wireless Modules
1
IQ8Wireless universal interface w/o cover, white
Approval:
1
VdS
2
as 805601, but
Technical Data
Operating voltage
Current consumption
Battery operating time
Range inside
Range outside
Frequency band 1
Frequency band 2
Transmitter power
Sensitivity
Data transmission speed
Application temperature
Storage temperature
3
4 x 3,6 V batteries
approx. 30 μA
approx. 2 years*
max. 30 m
max. 300 m
433 MHz with 20 channels
868 MHz with 5 channels
10 mW
-100 dB
19,2 Kbit/s
-5 °C ... 55 °C
-20 °C ... 70 °C (w/o batteries)
25 °C bis -10 °C (with batteries)
≤ 95% (w/o condensation)
IP42
PC/ASA plastic
white, similar to RAL 9010
approx. 285 g (incl. batteries, without attachment)
EN 54-25 submitted
W: 135 mm H: 135 mm D: 20 mm (without a​ ttachment)
Air humidity
Type of protection
Material
Color
Weight
Specification
Dimensions
4
5
6
7
8
*The battery operating time is dependent on the type of detector/device used, as well as the ​
application temperature and additional surrounding conditions. It can be substantially restricted ​
by increased current consumption of the wireless devices in the case of alarm, wireless ​
interference or poor transmission, or even possibly through contact resistance at the contacts. ​
Please note important instructions for usage of batteries in FB 798941.
9
¬qY$§­
805603
10
IQ8Wireless mounting frames for IQ8Alarm, red and white
The mounting frame is used for the mounting of the IQ8Alarm alarm signaling devices onto​
the IQ8Wireless wireless interface 805601/805602.
11
1
Technical Data
Color
red, similar to RAL 3020
white, similar to RAL 9010
approx. 64 g
W: 133 mm H: 133 mm D: 21 mm
Weight
Dimensions
12
13
14
=
+
+
15
IQWireless interface +
IQ8Alarm
IQWireless interface
805601 (red) or
805602 (white)
Mounting frames
805603
IQ8Alarm devices
8072xx or 8073xx
16
Application example
17
165
Wireless Component
Wireless Modules
¬qY%!­
805604
IQ8Wireless mounting frame for IQ8Quad detectors, white
The mounting frame is used for the mounting of the IQ8Quad fire detector with or without ​
integrated alarm signaling device onto the IQ8Wireless wireless interface 805602.
1
Technical Data
Color
red, similar to RAL 3020
white, similar to RAL 9010
approx. 41 g
W: 133 mm H: 133 mm D: 21 mm
Weight
Dimensions
=
IQWireless interface +
IQ8Quad detector with
integrated alarm device
+
IQWireless interface
805602
+
Mounting frame
805604
+
Standard detector base
805590
IQ8Quad detector
with integrated
alarm device
80238x
¬qY&$­
Application example
805605
IQ8Wireless cover for wireless interface, red and white
1
For applications in which the IQ8 components are not to be directly mounted (remote ​
connection) on the IQ8Wireless wireless interface 805601/805602, the wireless interface ​
can be used with the filler panel.
Technical Data
Color
red, similar to RAL 3020
white, similar to RAL 9010
approx. 33 g
W: 133 mm H: 133 mm D: 8 mm
Weight
Dimensions
1 x red cover plate
1 x white cover plate
Range: max.
300m (open air)
max. 10 IQ8Wireless MCP
12V DC
esserbus - PLus
Loop length max. 3.5 km
IQ8Control C
Remote mode of
IQ8MCP with IQ8Wireless
Interface (max. 3m)
12V DC
Range: max.
300m (open air)
Application example
166
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Detectors for Special Applications
Flame and Heat Detectors
168-173
Air Duct Detectors
174-176
Line Heat Detectors
177-186 12
Line Smoke Detectors
187-192
11
13
Aspirating Smoke Detectors
Accessories
193-209
210 14
15
16
17
167
Detectors for Special Applications
Flame Detectors
782313
¬o8._­
Flame and Heat Detectors
UV Flame detector UniVario Type FMX5000UV - ESSER
Approval:
1
VdS
UV flame detector for the recognition of fast developing fires with flame formation. Opera­
tion, fault and fire statuses are displayed via LEDs on the detector. The supply voltage and ​
the linking takes place directly via the standard detector zone
at the esserbus transponder (part no. 808622). Resetting of the detector is also carried out ​
directly via the esserbus transponder (part no. 808622).
Technical Data
Features
• Direct linking and voltage supply via standard ​
•
•
•
•
detector group at the esserbus transponder (part ​
no. 808622)
Base installation and alignment via included ​
mounting bracket (part no. 783312)
High IP protection for indoor and outdoor usage
Operation and fault status displayed on the ​
detector
Self-monitoring via internal sensors
Operating voltage
Quiescent current @ 9 V DC
Alarm current @ 9 V DC
Area to be monitored
Height to be monitored
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
9 V DC
approx. 500 μA
typ. 15 mA
max. 676m²
max. 45 m
-20 °C ... 80 °C
-40 °C ... 85 °C
≤ 95% (w/o condensation)
IP67
Die-cast aluminium
red, similar to RAL 3000
approx. 945 g (incl. base and bracket))
W: 130 mm H: 140 mm D: 92 mm
Detector and standard base, mounting bracket
min. 10 x 10 cm
Max. mounting
height 45 m
Detection area
max. 66 x 66 cm
Min. 1,5 m
Max. detection area 50 meter distance
782315
3fold-IR-Flame detector UniVario - ESSER
1
UniVario threefold IR flame detector ESSER 3-channel infrared flame detector for recogni­
tion of quickly developing fires with flame development. Optical windows of the IR sensors ​
are fully monitored. The detector achieves a high level of resistance towards disturbance ​
variables via 3-channel infrared evaluation. Voltage supply and connection occur directly ​
via the standard detector zone at the esserbus Transponder. The detector is also reset ​
directly via the esserbus Transponder.
Technical Data
Features
• 3-channel infrared flame detector
• High level of protection against disturbance vari­
•
•
•
•
168
ables thanks to optimized hardware and develop­
ment of special algorithms
Maximum level of response sensitivity according ​
to EN54-10, Class 1
Detection range up to 50 m
Monitoring surface up to 650 m2
Each optical channel has separate functional ​
monitoring
www.hls-austria.com
Operating voltage
Quiescent current
Alarm current @ 9 V DC
Area to be monitored
Height to be monitored
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
9 V DC
approx. 2.3 mA
typ. 15 mA
676
max. 45 m
-20 °C ... 80 °C
-40 °C ... 85 °C
≤ 95% (w/o condensation)
IP67
Die-cast aluminium
red, similar to RAL 3000
approx. 991 g (incl. base and bracket))
W: 130 mm H: 140 mm D: 92 mm
Attention detector base is not included!
Detectors for Special Applications
Heat Sensor
782310
Flame and Heat Detectors
1
¬o8+V­
2
Heat detector UniVario - ESSER
For detection of open fires with fast development of heat. For usage in polluted industrial ​
environments, in potentially explosive areas, interior and exterior areas. Voltage supply and​
connection occur directly via the standard detector zone at the esserbus transponder (part ​
no. 808622). The detector is also reset directly via the esserbus transponder.
1
3
Technical Data
Features
• Microcontroller functional monitoring of heat ​
•
•
•
•
•
sensors as well as software and hardware
Quick fire detection with high level of protection ​
against false alarms
Comparison to typical false variables using intelli­
gent evaluation algorithms
High level of electromagnetic compatibility
Various mounting possibilities
Oil-tight and high level IP67 protection class as ​
well as resistance to impact and vibration
Operating voltage
Quiescent current
Alarm current @ 9 V DC
Storage temperature
Air humidity
Type of protection
Housing
Color
Dimensions
4
9 V DC
approx. 0.15 mA
typ. 15 mA
-40 °C ... 85 °C
≤ 95% (w/o condensation)
IP67
Die-cast aluminium
red, similar to RAL 3000
W: 130 mm H: 140 mm D: 85 mm
5
6
Detector base is not supplied!
7
8
¬o8#>­
782302
Heat detector UniVario 200 mm - ESSER
9
Same as 782310 but with sensor rod length of 200 mm.
1
Technical Data
Quiescent current
Ambient temperature
10
approx. 0.25 mA
-20 °C ... 400 °C
11
Detector base is not supplied!
782303
12
¬o8$A­
Heat detector UniVario 400 mm - ESSER
13
Same as 782302 but with sensor rod length of 400 mm.
Detector base is not supplied!
782304
¬o8%D­
14
Heat detector UniVario 600 mm - ESSER
Same as 782302 but with sensor rod length of 600 mm.
15
Detector base is not supplied!
16
17
169
Detectors for Special Applications
¬o8'J­
Flame and Heat Detectors
Heat detector UniVario Flex 2 m - ESSER
782306
Same as 782310 but with sensor tube for installation in areas with poor accessibility such ​
as shafts and canals.
1
Technical Data
Ambient temperature
-20 °C ... 400 °C
Detector base is not supplied!
¬o8(M­
782307
Heat detector UniVario Flex 6 m - ESSER
Same as 782306 but with sensor tube length of 6 m.
Detector base is not supplied!
¬o8)P­
782308
Heat detector UniVario Flex 9 m - ESSER
Same as 782306 but with sensor tube length of 9 m.
Detector base is not supplied!
Accessories
783312
¬oB-p­
Mounting bracket for UniVario Flame Detector
Mounting bracket for alignment of the UV flame detector (part no. 782313).
1
¬oB.s­
783313
UniVario MX5000.ESSER standard base
Standard detector base for detectors of the UniVario product family.
1
170
www.hls-austria.com
Detectors for Special Applications
Flame and Heat Detectors
1
Explosion-Proof Detectors
¬m.PH­
761347
2
IR flame detector (ex) X 9800
Approval:
1
VdS
3
The pressure-proof, fully enclosed infrared flame detector particularly distinguishes itself ​
through reliable operation in difficult conditions. An integrated LED and three relays ​
provide information regarding the state of operation, failure, and alarm. Contamination ​
resistance and heated optics to prevent condensation and formation of ice also allow for ​
external operation. Typical areas of application are turbines, petrochemistry and the auto­
motive industry.
4
Activation on the loop and resetting take place via the esserbus transponder 808613.10. ​
Activation on a conventional line occurs via the reset module 781332. This device requires ​
a separate voltage supply of 24 V DC.
Features
• Visual range: 90°
• Maintenance with magnets, no test lamp required
• Status display directly at the detector via 3-colour ​
LED for operation, fault and alarm
• Actuation and resetting via esserbus transponder ​
808613.10 in loop operation
5
Technical Data
Operating voltage
Display
Height to be monitored
Ambient temperature
Storage temperature
Ex-category
Explosion protection
Type of protection
Housing
Weight
Detector specification
EC-type examination certificate
Dimensions
6
24 V DC
max. 25 m
max. 20 m
-40 °C ... 75 °C
-55 °C ... 85 °C
II 2 GD
EEx d IIC T5-T6, T86°C
IP66
Die-cast aluminium
approx. 2.7 kg (+ 6,0 kg fixture)
EN 54-10, Class 1
DEMKO 02 ATEX 132195
Ø: 122 mm H: 246 mm
7
8
9
Please note: for mounting of the holder, a 14 mm allen key is necessary and is not included in ​
delivery.
10
Mounting bracket
11
12
13
14
15
16
17
171
Detectors for Special Applications
¬m.QK­
761348
Flame and Heat Detectors
UV flame detector (ex) X 2200
Approval:
1
Features
• Visual range: 90°
• Maintenance with magnets, no test lamp required
• Status display directly at the detector via 3-colour ​
LED for operation, fault and alarm
• Actuation and resetting via esserbus transponder ​
808613.10 in loop operation
VdS
The pressure-proof, fully enclosed ultraviolet flame detector possesses automatic optical ​
self-monitoring that allows any application under difficult conditions. An LED provides ​
information regarding the state of operation, failure and alarm. Three relays (fire, failure ​
and additional alarm) are integrated for connection to a fire detection system. Contamina­
tion resistance and heated optics to prevent condensation and formation of ice also allow ​
for external operation. Typical areas of application are turbines, munitions depots, natural ​
gas depots and aircraft hangers.
Activation on the loop and resetting take place via the esserbus transponder 808613.10. ​
Activation on a conventional line occurs via the reset module 781332. This device requires ​
a separate voltage supply of 24 V DC.
Technical Data
Operating voltage
Display
Height to be monitored
Ambient temperature
Storage temperature
Ex-category
Explosion protection
Type of protection
Housing
Weight
Detector specification
EC-type examination certificate
Dimensions
24 V DC
max.25 m
max. 20 m
-40 °C ... 75 °C
-55 °C ... 85 °C
II 2 GD
EEx d IIC T5-T6, T86°C
IP66
Die-cast aluminium
approx. 2.7 kg (+ 6,0 kg fixture)
EN 54-10, Class 1
DEMKO 02 ATEX 132195
Ø: 112 mm H: 246 mm
Please note: for mounting of the holder, a 14 mm allen key is necessary and is not included in ​
delivery.
Mounting bracket
172
www.hls-austria.com
Detectors for Special Applications
¬m.RN­
761349
Flame and Heat Detectors
1
UV/IR flame detector (ex) X 5200
Approval:
VdS
2
Since it can be mounted, the pressure-proof, fully enclosed combination ultraviolet/infrared​
flame detector, enables UV and IR transmitters to monitor the same danger zone with a ​
visual angle of 90°. Triggering occurs only by activation of the IR and UV sensors. An LED ​
provides information regarding the state of operation, failure and alarm. Three relays (fire, ​
failure and additional alarm) are integrated for connection to a fire detection system. ​
Contamination resistance and heated optics to prevent condensation and formation of ice ​
also allow for external operation. Typical areas of application are turbines, munitions ​
depots, natural gas depots and aircraft hangers.
1
Features
• Visual range: 90°
• Maintenance with magnets, no test lamp required
• Status display directly at the detector via 3-colour ​
LED for operation, fault and alarm
• Actuation and resetting via esserbus transponder ​
808613.10 in loop operation
3
4
Activation on the loop and resetting take place via the esserbus transponder 808613.10. ​
Activation on a conventional line occurs via the reset module 781332. This device requires ​
a separate voltage supply of 24 V DC.
5
Technical Data
Operating voltage
Display
Height to be monitored
Ambient temperature
Storage temperature
Ex-category
Explosion protection
Type of protection
Housing
Weight
Detector specification
EC-type examination certificate
Dimensions
24 V DC
max. 25 m
max. 20 m
-40 °C ... 75 °C
-55 °C ... 85 °C
II 2 GD
EEx d IIC T5-T6, T86°C
IP66
Die-cast aluminium
approx. 2.7 kg (+ 6,0 kg fixture)
EN 54-10, Class 1
DEMKO 02 ATEX 132195
Ø: 122 mm H: 246 mm
6
7
8
9
Please note: for mounting of the holder, a 14 mm allen key is necessary and is not included in ​
delivery.
10
Mounting bracket
¬o.1T­
781316
1
IR flame detector 3501 (ex)
11
The flame detector FMX 3501 analyses three physical indicators in the infrared part of the ​
optical spectrum. Because of integrated complex electronics, it is possible to record and ​
handle the specific fire signals. Then a signal will be sent to the fire alarm unit.
The flame detectors FMX 3511 and FMX 3501 Ex are designed to detect open, smokeless ​
and smoke forming flames, which result from firm or fluid organic materials like gas, oil ​
products, plastic, wood etc.
12
13
Technical Data
Features
• For operation in explosion-hazard zones 1 use ​
intrinsic flame detectors
• Connection to certified intrinsically safe detection ​
lines only (safety barriers)
• EX Class EEX ib II CT6 to 40° C ambient
temperature
• EEX ib II CT4 to 80° C ambient temperature
Operating voltage
Ambient temperature
Air humidity
Type of protection
Housing
Color
Weight
7.6 ... 15 V DC
-25 °C ... 80 °C
≤ 95% (w/o condensation)
IP65
Aluminium housing
blue, similar to RAL 5009
approx. 0.75 kg
14
Flame detector complete with mounting device swivel mount with.
16
15
17
173
Detectors for Special Applications
Air Duct Detectors
¬o/[email protected]­
781443
Venturi air duct module for IQ8Quad OTblue-LKM (802379)
1
Ventilation air duct module for usage of the OTblue-LKM 802379 air duct smoke detector ​
in combination with Venturi tubes 781446, 781447 or 781448. The module is mounted on ​
the outside of the air ducts.
The Venturi tube enters the duct and leads the air out of the duct through the detection ​
chamber of the detector back to the duct and finally back into the duct. During operation, ​
the detector and the alarm LED is visible so that an external parallel detector indicator is ​
not required.
The housing need not be opened for maintenance purposes. Inspection of the detector can ​
be quickly easily performed via a separate opening in the front of the housing.
Technical Data
Features
• Single-tube air analysis system based on the ​
Venturi principle
• Optimum utilisation of air flow velocity through ​
new Venturi tube design
Type of protection
Housing
Color
Weight
Dimensions
• Integrated maintenance opening in the front cover ​
IP54
ABS plastic
grey
approx. 800 g
W: 180 mm H: 235 mm D: 183 mm
Construction kit includes pipe gasket and cap. The following items are not included: IQ8Quad ​
OTblue LKM or detector base as well as the Venturi tube or filter cartridge.
so that air duct smoke detector can be tested
• Suitable for air duct widths from 0.6 to 2.8 m
• Integrated air flow display
Correct diameter
calculation dh:
Correct assembly site
Turnaround of
Airflow
H
Airflow
W
d h = 2 x Hx W
H+W
5d
Air intake e.g.
Air outlet e.g.
Airflow
D
dh = D
Application example with detector
174
www.hls-austria.com
5d
5d
Mounting on air ducts with
mounting kit part no.781449
Detectors for Special Applications
Accessories
802379
Air Duct Detectors
1
¬q8pY­
2
IQ8Quad OTblue-LKM
Approval:
1
VdS
3
Specially addressable IQ8Quad multicriteria detector for application as air duct smoke ​
detector in construction kit 781443. The detection methods are based on state-of-the-art ​
sensor technology that enables the detection of open fires, smouldering fires and fires with ​
intense heat generation. In addition to that, extremely small particles can be detected ​
without using ionisation detectors. The loop isolator is integrated in the detector.
4
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Application temperature
Storage temperature
Type of protection
Housing
Weight
Detector specification
Specification
Dimensions
5
9 ... 42 V DC
approx. 50 μA
-20 °C ... 50 °C
-25 °C ... 75 °C
IP43 (with base + option)
ABS plastic, white, similar to RAL 9010
approx. 110 g
EN 54-7
EN 54-7/-17, CEA 4021
Ø: 117 mm H: 62 mm (incl. base)
6
7
Only suitable for application in air duct construction set 781443.
8
¬o/MC­
Filter cartridge for air duct module 781443
781444
9
For use in unclean environmental conditions.
1
10
11
¬o/OI­
12
Venturi tube 0.6 m for IQ8Quad air duct construction set 781443
781446
Venturi tube 0.6 m for application with air duct construction set 781443 between 140 mm ​
and 600 mm.
13
1
Technical Data
Material
14
Aluminium
Required borehole in the duct: 38 mm
¬o/PL­
15
Venturi tube 1.5 m for IQ8Quad air duct construction set 781443
781447
Venturi tube 1.5 m for application with air duct construction set 781443 between 600 mm ​
and 1400 mm.
16
1
Technical Data
Material
17
Aluminium
Required borehole in the duct: 38 mm
Venturi tube, plastic gasket and rubber seal
175
Detectors for Special Applications
Air Duct Detectors
¬o/QO­
781448
Venturi tube 2.8 m for IQ8Quad air duct construction set 781443
Venturi tube 2.8 m for application with air duct construction set 781443 between 1400 mm ​
and 2700 mm.
1
Technical Data
Material
Aluminium
Required borehole in the duct: 38 mm
Venturi tube, plastic gasket and rubber seal
¬o/RR­
781449
Mounting set for round and insulated air ducts
Mounting set for mounting the 781443 air duct construction set to round and / or insulated ​
air ducts.
1
Venturi tube, plastic gasket and rubber seal
¬o/NF­
781445
Weather protection housing for air duct construction set 781443
1
Protects the air duct detector in difficult environmental conditions such as during use in ​
outside areas.
The weather resistant housing can be subsequently fixed above the already mounted and ​
installed air duct module 781443.
Technical Data
Type of protection
Material
Weight
Dimensions
Opened condition
176
www.hls-austria.com
IP65
galvanised steel
approx. 1800 g
Ø: 282 mm H: 280 mm
Detectors for Special Applications
Line Heat Detector
761290
Line Heat Detectors
1
¬m-`­
2
Line heat detector LWM-1
Approval:
1
Features
• Maximum sensor length of 300 m
• Resistant against mechanical and chemical ​
impact, corrosion, humidity and dust
• Calibration switch setting
• VdS approval as per EN 54-5 A1 applicable up to ​
7.5 m ceiling height
VdS
Operating voltage
Current consumption @ 24 V DC
Quiescent current @ 24 V DC
Starting current @ 24 V DC
Current consumption in the case of failure
Display
A2, B and C
using special sensor cables
• Applicable for to 7.50 m ceiling height
• 2 floating relay contacts for fire and fault disturb­
ances
• Separate reset input for resetting via esserbus ​
transponder 808613.10 during loop operation
4
5
Technical Data
• Early fire detection with heat detector classes A1, ​
• High chemical and / or mechanical resilience by ​
3
The LWM-1 enables early detection of fires or overheating. It is specifically designed for ​
application in narrow rooms or rough environmental conditions. The system consists of an ​
LWM-1 evaluation unit and a special sensor cable, which must be selected according to the ​
type of application. The actuation on the loop and the resetting function is carried out via ​
the esserbus transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24V DC for the galvanic separation of D.C. voltage ​
potentials and the voltage converter 781337 is to be used in order to avoid ground faults.
Range
Temperature range
Type of protection
Material
Color
Weight
Maximum sensor length
Dimensions
10 ... 30 V DC
approx. 25 mA (DIFF- or MAX-alarm)
approx. 25 mA
< 100 mA
max. 15 mA
LED green: in operation, permanent light; LED red: ​
alarm diff., permanent light, locked; LED red: alarm ​
max., permanent light, locked; LED yellow: fault, ​
flashing light, locked
max. 300 m
-20 °C ... 50 °C
IP65
ABS plastic
grey, similar to RAL 7035
approx. 550 g
max. 300 m
W: 200 mm H: 120 mm D: 80 mm
6
7
8
9
10
The fastening clamp for mounting the line heat detector can be purchased at wholesale. For ​
application in Ex areas pls. read the explanation in the manual.
esserbus
Transponder
11
Monitored Area
12
esserbus /
esserbus-PLus
13
24 V DC
Application example
14
15
16
17
177
Detectors for Special Applications
Accessories
761243
Line Heat Detectors
¬m-L:­
Termination link set for sensor cable
The set contains four links for one end point.
1
¬m-M=­
761244
Connection link set for sensor cable
The set contains six links for one interconnection point.
1
¬[email protected]­
761245
Sensor cable blue (PVC)
Sensor cable for use in non aggressive atmosphere, but with high humidity for the 761260 ​
and 761290 line heat detector.
1
Technical Data
Dimensions
Ø: 3.15 mm
The price stated is the price per meter. Order quantity at least 5 m or a multiple thereof.
¬m-OC­
761246
Sensor cable black
Sensor cable with nylon cover for protection against acids and bases for the 761260 and ​
761290 line heat detector.
1
Technical Data
Dimensions
Ø: 4.8 mm
The price stated is the price per meter. Order quantity at least 5 m or a multiple thereof.
¬m-PF­
761247
Sensor cable black, with steel braiding
1
For reducing the mechanical loading of the cable under extreme conditions for the line type ​
heat detector 761260 and 761290, the sensor cable is additionally protected by a stainless ​
steel braid.
Technical Data
Dimensions
Ø: 5.8 mm
The price stated is the price per meter. Order quantity at least 5 m or a multiple thereof. ​
Cancellations or returns are not possible.
970301
¬¤$"&­
Ex-i terminal box for 970300
Ex-i terminal box for 970300 SD Series surge protection systems. Holds up to 24 ​
terminals.
1 x M32 for cable diameter 12-21 mm (24 x Ex-i)
12 x M20 for cable diameter 5.5-13 mm (12 x PE/PA)
178
www.hls-austria.com
Detectors for Special Applications
¬¤)
970302
1
Line Heat Detectors
1
Cable turnbuckle for floating roof tank
The cable turnbuckle for floating roof tank allows to obtain continuity of electrical connec­
tion between heat detection line and fire alarm control panel. The cable turnbuckle, ​
installed on the border of the tank body and connected to the start/end of line box located ​
on the roof, follows the movement of the roof coiling and uncoiling the cable as the tank’s ​
roof rises and falls. The mechanism is enclosed within a stainless steel cabinet. Connection ​
cable is chemical and temperature resistant.
The unit can be installed both in vertical or horizontal position.
A removable plate allows the inspection of the state of the spring and its maintenance ​
without removing the unit from its work position.
2
3
4
Technical Data
Operating voltage
Type of protection
Material
Weight
Dimensions
300 V DC
IP42
stainless steel (box), carbon steel (spring)
approx. 25 kg
W: 400 mm H: 400 mm D: 150 mm
5
6
Heat sensing cable and start/end of line box (907303) are not included.
The cable must be flame retardant, chemical and temperature resistant.
Max. 4 conductors 1mm².
7
1 x stainless steel box incl. removable rain shield
¬¤$$,­
970303
8
Start/end of line box for LWM-1
The start/end of line box installed on the floating roof forms the connection between the ​
sensor cable and the cable turnbuckle.
9
1
Technical Data
Ambient temperature
Explosion protection
Type of protection
Material
Color
Dimensions
-20 °C ... 40 °C
ATEX II 2G EEx e II
IP66
glass reinforced polyester (housing), stainless steel ​
(screws)
black (with blue label)
W: 122 mm H: 119 mm D: 91 mm
10
11
Heat sensing cable and cable turnbuckle (907302) are not included.
12
13
14
15
16
17
179
Detectors for Special Applications
Line Heat Detectors
Intelligent Linear Heat Detector
Evaluation Unit
Approval:
VdS
1
The DTS system (distributed temperature sensing) has the capacity to not only detect fires ​
quickly, but to also detect individual fires precisely within a few meters. This is done unaf­
fected by wind, because not only convective but also radiant heat is determined. Addition­
ally the size and fire spread direction can be monitored over a longer period, because the ​
sensor cable is able to withstand temperatures up to 750°C without loosing monitoring ​
capability.
The system can be easily integrated into existing management platforms (e.g. SCADA ​
systems) by either communicating directly over Ethernet (TCP/IP) using SCPI (standard ​
commands for programmable instruments), or Modbus.
Features
• Temperature monitoring with FO cable (Part No. ​
Technical Data
•
•
•
•
•
Operating voltage
Power consumption
Ambient temperature
Storage temperature
Air Humidity
Weight
Dimensions
•
•
970150 or 970153)
2 sensor channels per evaluation unit
Single and loop configuration possible
Up to 256 freely configurable alarm zones
Up to 5 alarm parameters per zone
Configuration of „negative“ alerts, which can also ​
be used for ice warnings
Fiber break detection and location
Automatic fiber break recovery
970120
970121
970122
970123
970124
180
www.hls-austria.com
¬¤"5[­
¬¤"6^­
¬¤"7a­
¬¤"8d­
¬¤"9g­
Evaluation unit DTS - 1 km
Evaluation unit DTS - 2 km
Evaluation unit DTS - 3 km
Evaluation unit DTS - 4 km
Evaluation unit DTS - 8 km
10 ... 30 V DC
15 W @ 20 °C
-10 °C ... 60 °C
-40 °C ... 80 °C
< 95 %
approx. 9 kg
W: 448 mm H: 88 mm D: 364 mm 2 HU, 19"
Detectors for Special Applications
Accessories
970130
Line Heat Detectors
1
¬¤"?y­
¬¤"@|­
¬¤"D!­
Optional 2nd channel for evaluation unit DTS
2
For connection of a second heat detection cable to the DTS evaluation unit.
970131
3
I/O connection set
Cable set to connect relay output to fire alarm control panel.
970135
4
DTS interface box
The DTS system can easily be integrated into SCADA systems, direct process control or ​
external connections to fire control panels. The DTS interface box provides access via the ​
Modbus protocol RS 232, RS 422 and RS 485, as well as TCP/IP. Through a virtual host ​
concept the data is available for each sensor (channel) as a Modbus unit. Meaning only ​
one unit is required even for multiple channel operation. 10000 register holdings and 3000 ​
register coil definitions can be assigned flexibly to each Modbus unit.
1
5
6
Technical Data
Features
• Modbus:
• Entire temperature trace data
• Independent alarm parameter per zone
• Several status conditions such as fiber break
Operating voltage
Ambient temperature
Storage temperature
Air humidity
Weight
Dimensions
7
12 ... 48 V DC
-10 °C ... 60 °C
-20 °C ... 80 °C
5% to 95% (non condensing)
approx. 200 g
W: 111 mm H: 77 mm D: 26 mm
8
9
• LAN: Ethernet 10/100 Mbps, RJ 45
• Serial Interface: RS-232/422/485, DB9 male
10
¬¤"E$­
970136
Relay controller set
1
11
If the application requires driving more than the embedded 20 relay outputs of the DTS ​
instrument, the relay controller sets should be used. In combination with the DTS interface ​
box it is capable of controlling up to 256 additional relay outputs per channel. Each relay ​
output can be assigned flexibly to any defined alarm condition.
12
Technical Data
Operating voltage
Current consumption @ 24 V DC
Ambient temperature
Storage temperature
Air humidity
Weight
Dimensions
24 V DC
approx. 350 mA (Controller)
0 °C ... 55 °C
-25 °C ... 85 °C
5% to 95% (non condensing)
approx. 200 g
W: 55 mm H: 100 mm D: 70 mm (Controller)
13
14
1 x power supply
1 x pre-programmed relay controller
1 x digital output module
1 x end module
8 x relays with accessories for easy wiring
970137
15
¬¤"F'­
16
DTS extension set
The DTS Extension Set adds another digital output module and 8 relays. For example, to ​
offer 48 relays, 1 relay controller and 5 DTS Extension Sets would be necessary.
17
Technical Data
Operating voltage
Current consumption @ 24 V DC
Ambient temperature
Storage temperature
Air humidity
24 V DC
approx. 25 mA (each IO card/relay)
0 °C ... 55 °C
-25 °C ... 85 °C
5% to 95% (non condensing)
181
Detectors for Special Applications
Line Heat Detectors
¬¤"I0­
970140
Steel anchor with plastic clamp for DTS cables
Self-locking plastic cable clamps with zinc-plated steel anchor, ideal for installation on ​
concrete walls and ceilings. With this mounting solution the sensor cable is fast and ​
securely installed. This plastic cable clamp provides excellent resistance against corrosive ​
and chemical atmospheres as well as an uncritical characteristic relating to fire (halogen ​
free). The plastic cable clamp in combination with the metal free cable is especially suitable ​
for use in rail tunnels where metal free components are often required.
To fix the clamps on the concrete a special concrete dowel type is used. The metal dowel is ​
an anchor made of steel, which is placed into a drilled hole and anchored by deformation-​
controlled expansion. The anchor may be deployed in structures subject to dry internal ​
conditions and also in structures subject to external atmospheric exposure in humid ​
internal conditions or in other particular aggressive conditions e.g. immersion in seawater, ​
chloride atmosphere or atmosphere with chemical pollution (e.g. in desulphurization plants ​
or road tunnels where de-icing materials are used).
1
Features
• For indoor and outdoor applications
• Applicable for dynamic loads
• UV-stabilized: 5 times better than PA6/PA66
• Very low moisture absorption
• High chemical resistance
• Halogen free as per IEC-Norm 754-2
Technical Data
Ambient temperature
Type
Material
Color
Dimensions
-40 °C ... 110 °C
K6 x 30/15
polyamide (clamp),
zinc plated steel (anchor)
dark grey, similar to RAL 7001(clamp)
Ø: 6 mm L: 61 mm (metal anchor)
Please note: for mounting of the anchor, one setting tool (Part No. 970144) is necessary and is ​
not included in delivery.
Other anchor lengths on request.
100 x plastic clamps
100 x anchor
1 x SDS drill
¬¤"J3­
970141
Stainless steel anchor with plastic clamp for DTS cable
As 970140 but with stainless steel anchor.
1
Technical Data
Type
Material
Dimensions
K6 x 30/15
stainless steel (anchor)
Ø: 6 mm L: 61 mm (metal anchor)
100 x plastic clamps
100 x anchors
1 x SDS drill
¬¤"K6­
970142
Steel anchor with steel clamp for DTS cables
As 970140 but with steel clamp, protected by rubber. The steel clamp complies with DIN ​
3016
1
Technical Data
Material
100 x steel clamps
100 x anchors
1 x SDS drill
182
www.hls-austria.com
steel zinc plated with rubber protection
(clamp)
Detectors for Special Applications
Line Heat Detectors
¬¤"L9­
1
Stainless steel anchor with stainless steel clamp for DTS cables
970143
As 970142 but with stainless steel anchor and clamp.
1
2
Technical Data
Type
Material
Dimensions
K6 x 30/15
stainless steel with rubber protection
(clamp)
Ø: 6 mm L: 61 mm (metal anchor)
3
100 x steel clamps
100 x anchors
1 x SDS drill
4
¬¤"M<­
Setting tool for anchor installation
970144
5
To fix the metal anchor it is necessary to have one setting tool.
1 x setting tool
6
7
8
9
10
¬¤"N?­
¬¤"OB­
¬¤"PE­
¬¤"SN­
11
Micro splice-box for DTS FO cable
970145
12
Splice-box IP67 for DTS FO cable, steel
970146
13
14
Splice-box IP66 for DTS FO cable, stainless steel
970147
15
FO sensor cable DTS safety FRNC
970150
1
Fast responding sensor cable with tight buffered fiber. Compact dimensions, high flexibility ​
and good bending behaviour. High tensile strength by Aramid yarns. The cable has a ​
halogen-free and flame-retardant cable sheath.
16
Technical Data
Material
Weight
17
FRNC outer sheath, Armid fibers, thight-buffered fibers
approx. 17 kg
Sensor cable will be delivered in requested length.
183
Detectors for Special Applications
Line Heat Detectors
¬¤"TQ­
Sensor cable connectors for FO cable 970150
970151
To reduce deployment cost and tim, we are optionally offering preassembled pig tails. This ​
enable quick and easy onsite installation, with no need to organize a fusion splicer, splice ​
box to get the sensing cable connected to the DTS instrument. Pig tails are supplied with ​
E2000 8° angled connectors. For safe transportation and installation the connectors and ​
pig tails are covered by a flexible tube to ensure proper protection.
¬¤"UT­
¬¤"VW­
Terminators for FO cable 970150
970152
FO sensor cable steel FRNC
970153
1
Fast responding sensor cable armoured, with stainless steel loose tubes and outer sheath. ​
High permissible tensile strength, high crush resistance. Longitudinally and laterally water­
tight. Excellent rodent protection. The cable has a halogen-free and flame retardant cable ​
sheath.
Technical Data
Material
Weight
FRNC outer sheath, stainless steel wires, gel-free ​
stainless steel loose tube, fibres with primary coating
approx. 25 kg
Sensor cable will be delivered in requested length.
¬¤"WZ­
¬¤"X]­
¬¤"]l­
Sensor cable connectors for FO cable 970153
970154
As 970151 but for FO sensor cable steel FRNC (Art. No. 970153).
Terminators for FO cable 970153
970155
E2000 APC 8° pigtail
970160
E2000 8° angled connectors with a 5 m pigtail offered to splice the sensing cables.
1
¬¤"^o­
E2000 APC adapter to connect two connectors 970160
970161
Used to connect two E2000 APC (Art. No. 970160) connectors.
1
184
www.hls-austria.com
Detectors for Special Applications
¬¤"b­
970165
Line Heat Detectors
1
Cutting tool for FO steel sensor cable 970153
Recommended to cut the stainless steel tube, to properly remove the cable sheath and ​
splicing the pigtail to the sensing fiber.
2
1
3
970170
4
¬¤"g#­
Cable drum for FO sensor cable 970150 or 970153
5
6
7
8
9
10
11
12
13
14
15
16
17
185
Detectors for Special Applications
Line Heat Detectors
Conventional Line Heat Detector
¬¤"!¨­
970100
Sensor cable EPC
The sensor cable EPC consists of a durable flame retardant vinyl outer jacket. It features ​
low moisture absorption, resistance to many common chemicals, and excellent flexibility at ​
low temperatures. Sensor cable for use in non aggressive atmosphere, but with high ​
humidity. Can be connected directly to the refurbishment transponder 80863x.10.
NOT EN 54 compliant.
1
Technical Data
Response temperature
Ambient temperature
68 °C
< 38 °C
Will be delivered in a 152 m roll.
¬¤"""­
970101
Sensor cable EPC
As 970100, but different alarm and ambient temperature.
NOT EN 54 compliant.
Technical Data
Response temperature
Ambient temperature
¬¤"#%­
970102
88 °C
< 66 °C
Sensor cable EPC
As 970100, but different alarm and ambient temperature.
NOT EN 54 compliant.
Technical Data
Response temperature
Ambient temperature
¬¤"$(­
970103
88 °C
< 79 °C
Sensor cable EPC
As 970100, but different alarm and ambient temperature.
NOT EN 54 compliant.
Technical Data
Response temperature
Ambient temperature
¬¤"%+­
970104
138 °C
< 93 °C
Sensor cable EPC
As 970100, but different alarm and ambient temperature.
NOT EN 54 compliant.
Technical Data
Response temperature
Ambient temperature
¬¤"%+­
970105
180 °C
< 105 °C
Sensor cable EPR
1
The sensor cable EPR contains of an extrudent flame retardant jacket of polypropylene ​
elastomer with a spezial UV stabilizer added to enhance weathering performance. It is ​
intended for a wide range of industrial applications and is characterized by high resiliency ​
and good abrasion resistance.
NOT EN 54 compliant.
Technical Data
Response temperature
Ambient temperature
Will be delivered in a 152 m roll.
186
www.hls-austria.com
68 °C
< 38 °C
Detectors for Special Applications
Line Smoke Detectors
1
Fireray
¬m.0O­
761315
2
Fireray 50 RV, with one prism
Approval:
1
Features
• A compact housing
• Maximum range 5 m to 50 m
• Robust construction
• Complies with EN 54-12 standard
• Actuation and resetting is carried out via the ​
esserbus transponder 808613.10 during loop ​
operation
VdS
The detector consists of an infrared transmitter and receiver. The signal is reflected by a ​
prism and analysed by the receiving element. Signal reaching the threshold will trigger an ​
alarm.
3
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
4
5
The Fireray is installed approx. 0.3 to 0.8 m underneath the ceiling and its reflector with ​
same ceiling distance opposite. There should be no reflecting obstacles in the transmission ​
zone (approx. 2 degrees).
6
Technical Data
Operating voltage
Quiescent current @ 24 V DC
Contact load
Range
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
10.2 ... 30 V DC
approx. 4 mA
max. 30 V DC / 1 A
5 to 50 m
-30 °C ... 55 °C
-35 °C ... 60 °C
lP50
ABS plastic, flame resistant
grey, similar to RAL 7035
approx. 670 g
EN 54-12
W: 210 mm H: 117 mm D: 120 mm
7
8
9
10
1 prism 761322
esserbus®
Transponder
esserbus® /
esserbus®-PLus
Monitored Area
11
1 retro mirror
24 V DC
12
Operating range: 5 up to 50 m
13
Application example
14
15
16
17
187
Detectors for Special Applications
¬m.1R­
761316
Line Smoke Detectors
Fireray 100 RV, with four prisms
Approval:
1
VdS
The detector consists of the infrared transmitter and receiver. The signal is reflected by a ​
prism and analysed by the receiving element. Signal reaching the threshold will trigger an ​
alarm.
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
Features
• One compact housing
• Maximum range 50 m to 100 m
• Robust construction
• Complies with EN 54-12 standard
• Actuation and resetting is carried out via the ​
esserbus transponder 808613.10 during loop ​
operation
The Fireray is installed approx. 0.3 to 0.8 m underneath the ceiling and its reflector with ​
same ceiling distance opposite. There should be no reflecting obstacles in the transmis­
sion zone (approx. 2 degrees).
Technical Data
Operating voltage
Quiescent current @ 24 V DC
Contact load
Range
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Detector specification
Dimensions
4 prisms 761323
188
www.hls-austria.com
10.2 ... 30 V DC
approx. 4 mA
max. 30 V DC / 1 A
50 to 100 m
-30 °C ... 55 °C
-35 °C ... 60 °C
lP50
ABS plastic, flame resistant
grey, similar to RAL 7035
approx. 670 g
EN 54-12
W: 210 mm H: 117 mm D: 120 mm
Detectors for Special Applications
Line Smoke Detectors
¬m.6a­
761321
1
Fireray 2000
Approval:
1
VdS
Consisting of transmitter, receiver and remote evaluation unit for light and dark smoke.
2
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
3
Technical Data
Features
• Coverage: 10 to max. 100 m
• Width of monitored area: max. 13 m (as per VdS)
• Height of monitored area: max. 12 m
• Area to be monitored: max. 1300 m²
• Automatic compensation for pollution and ageing ​
by 15-step gain control
• Rugged metal housing
• Floating contacts for alarm and trouble
• Test output for calibration and service
• Actuation and resetting is carried out via the ​
esserbus transponder 808613.10 during loop ​
operation
Operating voltage
Relays
Quiescent current @ 24 V DC
Alarm current @ 24 V DC
Contact load
Ambient temperature
Storage temperature
Type of protection
Response sensibility
Housing
Color
Weight
Detector specification
Dimensions
4
11.5 ... 28 V DC
1 x TROUBLE, potential-free change over contact
1 x ALARM, potential-free change over contact
approx. 14 mA
approx. 22 mA
max. 30V DC / 1A
-20 °C ... 55 °C
-25 °C ... 60 °C
lP50
25 %, 35 %, 50 % adjustable
sheet steel
grey, similar to RAL 7035
approx. 2140 g (Evaluating unit)
approx. 0.54 kg (Transmitter/Receiver)
prEN 54-12
W: 210 mm H: 265 mm D: 85 mm
Ø: 60 mm L: 102 mm (Receiver/Transmitter)
5
6
7
8
2 x mounting brackets, 4 x screws, 4 x grommets, 1 x test filter
esserbus
Transponder
Monitored Area
10
Transmitter
esserbus /
esserbus-PLus
9
Receiver
11
24 V DC
Operating range: up to 100 m
Application example
12
phase-out date: 31.12.2011
13
14
15
16
17
189
Detectors for Special Applications
Line Smoke Detectors
¬m.2U­
761317
Fireray 5000, line smoke detector, incl. controller, 100 m
The Fireray 5000 combines an infrared-transmitter and a receiver in one device. The trans­
mission signal is reflected in a prism and tested on smoke by the receiving unit. The trans­
mitting/receiving unit contains an actuator which always keeps the IR-ray in the optimal ​
position also when the case, e.g. is moved through the change of seasons.
1
Technical Data
Features
• Remote system controller
• LASER assisted alignment
• Automatic contamination compensation
• Automatic IR-alignment
Operating voltage
Operating current - low current mode
Operating current - high current mode
Delay to alarm
Delay to Fault
Range
Operating temperature
Storage temperature
Type of protection
Contact rating
Cable lenght - system controller to detector
Dimensions (W x H x D)
Weight
¬m.2§/61H­
761317.50
14 ... 28 V DC (System controller)
8 ... 12 mA (typ 10)
48 ... 52 mA (typ 50)
2 ... 30 s
2 ... 30 s
5 ... 10 m
-20 °C ... 50 °C
-40 °C ... 85 °C
IP54
0.1 ... 500 mA
max. 100 m
200 x 235 x 71 mm (System controller)
134 x 135 x 134 mm (Detector, incl. "easy fit" base)
134 x 134 x 70.5 mm (Universal bracket)
105 x 100 x 9.5 mm (Mirror)
0.9 kg (System controller)
0.5 kg (Detector, incl. "easy fit" base)
0.2 kg (Universal bracket)
0.07 kg (Mirror)
Fireray 5000, line smoke detector, incl. controller, 50 m
Same as 761317, but with a range of 50 m.
1
¬m.3§!L­
761318
Fireray Eexd, Beam detector for EX areas
Explosion proof infrared beam smoke detector.
1
Consisting of transmitter, receiver, and remote evaluation unit for light and dark smoke.
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
Technical Data
Features
• Low current consumption
• Automatic self check drift compensation
• 3 x selectable sensitivity/threshold levels
• Remote/low level control equipment (safe area)
Operating voltage
Quiescent current @ 24 V DC
Range
Ambient temperature
Explosion protection
Type of protection
Weight
Dimensions
190
www.hls-austria.com
11.5 ... 28 V DC
approx. 8 mA
10 ... 100 m
-20 °C ... 55 °C (non-condensing)
ATEX Certified - II 2 G EEx d IIB T6
IP67 (transmitter/receiver)
approx. 4 kg (transmitter/receiver)
approx. 1.1 kg (evaluating unit)
W: 124 mm H: 121 mm D: 124 mm (Sensor)
W: 210 mm H: 260 mm D: 88 mm (evaluation unit)
Detectors for Special Applications
Accessories Fireray
761322
Line Smoke Detectors
1
¬m.7d­
2
1 prism for Fireray
Technical Data
1
Range
Dimensions
3
5 to 25 m when Fireray 2000 and up to 50 m when ​
Fireray 50 RV
W: 100 mm H: 100 mm
The LRMX mirrors can be used.
4
5
¬m.8g­
4 prisms for Fireray
761323
6
The prisms are mounted on an aluminium mounting plate.
1
Technical Data
Range
Dimensions
7
25 to 35 m when Fireray 2000 and up to 100 m when ​
Fireray 100 RV
W: 245 mm H: 245 mm
8
The LRMX mirrors can be used.
9
¬m.9j­
9 prisms for Fireray 2000
761324
10
The prisms are mounted on an aluminium mounting plate.
1
Technical Data
Range
Dimensions
11
35 to 45m when Fireray 2000
W: 345 mm H: 345 mm
12
¬m/I§!!)­
13
Plate for 1 prism
761440
Prism plate for 1 prisms for use with bracket 761314
1
14
Technical Data
Weight
approx. 150 g
15
Prism is not included!
16
17
191
Detectors for Special Applications
Line Smoke Detectors
¬m/J§!,­
761441
Plate for 4 prism
Prism plate for 4 prisms for use with bracket 761314
1
Technical Data
Weight
approx. 300 g
Prism is not included!
¬m.-F­
761312
Ceiling pendant mount for Fireray
Ceiling pendant mount for F2000, F5000, F50RV, F100RV and universal bracket 761314
1
Technical Data
Weight
approx. 3400 g
¬m..§!=­
761313
Wall bracket for Fireray Eexd
Technical Data
1
Weight
approx. 1600 g
Fireray Eexd is not included!
¬m./§[email protected]­
761314
Univ. bracket for F5000 or prism plate 761440/761441
Universal bracket for a F5000 detector head or prism plate 761440 or 761441
1
Technical Data
Weight
192
www.hls-austria.com
approx. 300 g
Detectors for Special Applications
Aspirating Smoke Detectors
LRS Conventional Technology
1
761519
2
¬m04_­
LaserFOCUS aspirating sytem - ESSER, multilingual
Approval:
1
VdS
3
Active stand-alone detection system based on laser technology for the early detection of ​
fires in small areas.
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
4
5
Technical Data
Features
• Plug & play function (simple installation and ​
•
•
•
•
•
•
•
•
•
commissioning)
Laser based smoke detection
Programmable alarm threshold value
Two-level air filtering
Integrated bargraph display
Integrated debugging function
Event memory for up to 18,000 events
Relay output: 3 changeover relays
Actuation and resetting is carried out via the ​
esserbus transponder 808613.10 during loop ​
operation
Feature: Stand-alone system
Operating voltage
Current consumption @ 24 V DC
Quiescent current @ 24 V DC
Alarm current @ 24 V DC
Area to be monitored
Ambient temperature
Air humidity
Type of protection
Weight
CE certificate
Specification
Dimensions
18 ... 30 V DC
approx. 245 mA
approx. 220 mA
approx. 295 mA
max. 250m²
0 °C ... 40 °C
5% to 95% without condensation
IP30
approx. 2000 g
0832-CPD-0771
EN 54-20 class A, B, C
W: 255 mm H: 185 mm D: 90 mm
6
7
8
9
10
11
12
13
14
15
16
17
193
Detectors for Special Applications
¬m9'J­
762406
Aspirating Smoke Detectors
LRS compact aspirating system - ESSER, English
Approval:
1
VdS
Active early fire detection system using laser technology.
The actuation on the loop and the resetting function is carried out via the esserbus ​
transponder 808613.10.
Actuation on a conventional line is carried out via the reset module 781332. The device ​
requires a separate voltage supply of 24 V DC.
Connection via the 781332 / 781333 reset module (System 8000 / IQ8Control) and with ​
additional 24V supply voltage.
Features
• Adjustable sensitivity from 0,005% / m up to 20% ​
/ m obscuration
• 3 programmable alarm thresholds (alarm, pre ​
alarm, main alarm).
• For an increased protection from false alarms, all ​
•
•
•
•
•
•
•
•
•
•
194
alarm thresholds can be given a time window of 0 ​
– 60 sec
2 fault levels (maintenance, fault)
3 potential-free contacts (switching capacity 30V ​
DC / 2A) consisting of 1 potential-free changeover ​
contact and 2 potential-free switching contacts
Filter and air stream monitoring for easier main­
tenance
Event memory for up to 12,000 events
For use with an extraction tube with a total length ​
of max. 80 m (2 x 50 m)
Automatic learning function for determining ​
optimum sensitivity level (the units remain oper­
ative during this learning phase)
Adjustments can be made by means of a PC in ​
combination with 797595 CD ROM with Software ​
VConfig PRO and ASPIRE Windows software and ​
a standard interface cable w/o interface (modules ​
are not supplied as standard)
Main alarm, pre alarm, trouble and operation ​
status are indicated on the front panel
”ASPIRE” , 797595 CD ROM with Software ​
VConfig PRO and ASPIRE PC software for extrac­
tion tube
Actuation and resetting is carried out via the ​
esserbus transponder 808613.10 during loop ​
operation
www.hls-austria.com
Accessories
797595 CD ROM with Software VConfig PRO and ASPIRE
Detectors for Special Applications
¬m9(M­
762407
Aspirating Smoke Detectors
1
LRS compact / net aspirating system - ESSER, English
Approval:
1
VdS
2
As 761515, but with networking functionality
Connection via the 781332 / 781333 reset module (System 8000 / IQ8Control) and with ​
additional 24V supply voltage.
3
4
Features
5
• Adjustment by means of programming unit LRS ​
200 (761504) / 210 (761505) or PC with PC inter­
face LRS 300 (761506) and 797595 CD ROM with ​
Software VConfig PRO and ASPIRE Windows ​
software (modules are not supplied as standard)
• The environmental conditions may be ​
compensated by using an additional reference ​
detector
• Integration of up to 99 detector units via the ​
proprietary “VESDAnet™” bus system
• Indicating and operating panel can be connected ​
via the VESDAnet™ (761501, 761507)
6
7
8
9
10
11
12
13
14
15
16
17
195
Detectors for Special Applications
Aspirating Smoke Detectors
Accessories LRS Conventional Technology
¬m02Y­
761517
VESDAnet™ connection box
1
This connection box enables external devices to be connected to the VESDANet™. For ​
example, a handheld programmer or a PC can be connected in conjunction with the PC ​
interface to program the system.
The LRS 300 PC-Interface (761506) is also required.
¬m0'8­
761506
LRS 300 PC-Interface
Used as an alternative to the programming unit. All components on the VESDAnet™can be ​
programmed via the interface.
1
Technical Data
Current consumption
Dimensions
70 mA
W: 190 mm H: 100 mm D: 40 mm
The two required connectors are included.
¬m0-J­
761512
Spare filter for VESDA aspirating smoke systems
1
Two-stage filter for detector units LRS 100 (761500) / LRS S700 (761502) / LRS compact ​
(761515)/ LRS compact / net (761516)/ LRS compact/EB(801519)/Laser Focus (761519).
¬m0*A­
761509
Filter for LRS aspirating system
External filter for LRS aspirating system for extremely polluted environments.
1
Technical Data
Color
Dimensions
¬m9";­
762401
grey
W: 206 mm H: 59 mm D: 33 mm
Indicator and operating module LRS 110 - Esser, English
Approval:
1
VdS
For displaying the current smoke density and the alarm level of the LRS 100 detector unit ​
and the LRS compact/net. In addition, the alarm and fault status are shown by LEDs. ​
Different functions e.g. buzzer off and reset can be controlled via the key pad. The unit is ​
also equipped with 7 freely configurable, floating contacts.
As the LRS compact/net recognises up to three alarm states, the LED''s for main alarm 1 and ​
main alarm 2 are activated jointly.
For flush mounting, order kit with part no. 761511 separately.
Programming via interfaced network.
196
www.hls-austria.com
Detectors for Special Applications
Aspirating Smoke Detectors
Titanus EB Aspirating Smoke Detection
1
Features
2
• Highest application flexibility through modular ​
The Top Sens EB is also available on request with a special fan for usage in sound-sensitive ​
areas. This unit's sound level can be reduced to 23 dB (A) in normal operation using this model.
design
• Direct connection to the esserbus/esserbus-Plus ​
(powered loop)
configuration at delivery
esserbus / esserbus-PLus
• Parameters for response sensitivity can be ​
•
•
•
•
Loop length max. 3.5 km
configured at the detector module
Up to 180m duct length per duct
Up to 24 suction vents
Two-detector dependency can be set up in compli­
ance with VdS guidelines
Parallel detector indicator (Part No 801824) can ​
be connected
3
Smoke
aspirating
system
• Easy commissioning through pre-set system ​
4
24 V DC
5
Manufacturer-configured for
operation with one pipe
801515.10
801521.10
X
X
Manufacturer-configured for
operation with two pipes
801522.10
801531.10
801532.10
X
X
781521.10
781531.10
X
X
"Info alarm" display at the unit
and at the fire alarm panel
X
X
X
"Pre-alarm" display at the unit
and at the fire alarm panel
X
X
X
"Fire alarm" display at the unit
and at the fire alarm panel
X
X
X
X
X
X
X
"Fault" display at the unit and
at the fire alarm panel
X
X
X
X
X
X
X
X
X
Bargraph
6
X
Plug-and-play commissioning
X
Direct connection to the
esserbus/powered loop
X
X
X
X
X
Operating temperature range
from -10°C to +55°C
X
X
X
X
X
Operating temperature range
from -40°C to +60°C
7
8
X
9
X
X
X
X
10
* Titanus Pro Sens EB and Titanus Top Sens EB for extreme temperature environments
(frozen storages e.g.) and accessories are available on request.
11
Application example
12
13
14
15
16
17
197
Detectors for Special Applications
¬q00§/212­
801515.10
Aspirating Smoke Detectors
Compact unit Titanus Pro Sens EB
Approval:
VdS
Active system for the early detection of fires. It serves as room and furnishing protection ​
and can be directly connected to the esserbus / powered loop. The compact aspirating ​
smoke detection system Titanus Pro Sens EB is completely supplied with detector module ​
DM-TP-50L. Plug & Play operation for fast and simple commissioning through pre-​
programmed standard functions and pre-configured detector modules.
1
Technical Data
Features
• Fire and fault indication directly at the unit and at ​
Operating voltage
Current consumption
Quiescent current @ 24 V DC
Contact load relay
Sound level
the fire alarm control panel
• Fast commissioning through automatic initialising ​
process and plug & play operation
• Air flow monitoring for detecting pipe burst or ​
tube blocking
• Protection against disturbances when imple­
mented LOGIC SENS function is activated
• Integrated and pre-configured detector module ​
(part no. 801523.10)
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
CE certificate
Specification
Dimensions
14 ... 30 V DC
of the reset PCB max. 20 mA
approx. 275 mA (w/o reset PCB)
30 V DC/1 A max. 24 W
approx. 45 dB(A) (with sound absorber part no. ​
801543)
max. 1.5 mm²
-20 °C ... 60 °C
-25 °C ... 65 °C
≤ 95% w/o condensation
IP20
ABS plastic
white, similar to RAL 9018
approx. 1350 g
0786-CPD-20791
EN 54-20
W: 200 mm H: 292 mm D: 113 mm
Isolator not included with delivery, can be optionally ordered under part no. 788612.
Pre-configured Titanus Pro Sens EB basic device including esserbus transponder and reset PC ​
board as well as the Titanus Pro Sens EB front foil and pre-configured detector module DM-TP-​
50L.
¬q06§/21D­
801521.10
Basic unit Titanus Pro Sens EB
Approval:
1
VdS
Basic unit for wall mounting, ready to accommodate a DM-TP-xx detector module. The ​
Titanus Pro Sens EB can be directly connected to the esserbus / powered loop. The unit is ​
supplied with front foil for single-tube operation.
Technical Data
Features
• Pre-configured for connecting a DM-TP-xx ​
•
•
•
•
detector module
Optical status display for alarm and fault indica­
tion at the front foil
Extendable for integrating up to two DM-TP-xx ​
detector modules to connect a second tube
Ports for two suction tubes with outside diameter ​
of 25 mm
Port for air return tube
Operating voltage
Current consumption
Quiescent current @ 24 V DC
Contact load relay
Sound level
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
CE certificate
Specification
Dimensions
14 ... 30 V DC
of the reset PCB max. 20 mA
approx. 275 mA (w/o reset PCB)
30 V DC/1 A max. 24 W
approx. 45 dB(A) (with sound absorber part no. ​
801543)
max. 1,5 mm²
-20 °C ... 60 °C
-25 °C ... 65 °C
≤ 95% w/o condensation
IP20
ABS plastic
white, similar to RAL 9018
approx. 1350 g
0786-CPD-20791
EN 54-20
W: 200 mm H: 292 mm D: 113 mm
Isolator not included with delivery, can be optionally ordered under part no. 788612.
Pre-configured Titanus Pro Sens 1 EB, the basic unit includes an esserbus transponder, a reset ​
PCB and the Titanus Pro Sens EB front foil.
198
www.hls-austria.com
Detectors for Special Applications
¬q07§/21G­
801522.10
Aspirating Smoke Detectors
1
Basic unit Titanus Pro Sens 2 EB
Approval:
VdS
2
Basic unit for wall mounting, ready for receiving up to two detector modules DM-TP-xx. ​
The Titanus Pro Sens 2 EB can be directly connected to the esserbus / powered loop. The ​
device is supplied with front foil for two-tube operation.
1
3
Technical Data
Operating voltage
Current consumption
Quiescent current @ 24 V DC
Contact load relay
Sound level
Features
• Pre-configured for integrating up to two detector ​
•
•
•
•
modules DM-TP-xx to connect two tubes
Optical status display for alarm and fault indica­
tion at the front foil
Ports for two suction tubes with an outside ​
diameter of 25 mm
Port for air return tube
Possible two-detection-dependency as per VdS ​
directive
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
CE certificate
Specification
Dimensions
14 ... 30 V DC
of the reset PCB max. 20 mA
approx. 295 mA (w/o reset PCB)
30 V DC/1 A max. 24 W
approx. 45 dB(A) (with sound absorber part no. ​
801543)
max. 1.5 mm²
-20 °C ... 60 °C
-25 °C ... 65 °C
≤ 95% w/o condensation
IP20
ABS plastic
white, similar to RAL 9018
approx. 1350 g
0786-CPD-20791
EN 54-20
W: 200 mm H: 292 mm D: 113 mm
4
5
6
7
8
Isolator not included with delivery, can be optionally ordered under part no. 788612.
Pre-configured basic device Titanus Pro Sens 2 EB including an esserbus transponder, a reset ​
PCB and the front foil Titanus Pro Sens 2 EB.
¬[email protected]§/21b­
801531.10
Basic unit Titanus Top Sens EB
Approval:
1
Features
• Pre-configured for connecting a detector module ​
DM-TT-xx
• Optical status display for information alarm, pre-​
•
•
•
•
•
9
alarm, main alarm and fault indication at the front ​
foil
Extendable for integrating up to two detector ​
modules DM-TT-xx to connect a second tube
Integrated bargraph display to optically indicate ​
the current smoke level
Ports for two suction tubes with an outside ​
diameter of 25 mm
Port for air return tube
Possible two-detection-dependency as per VdS ​
directive
10
VdS
Basic unit for wall mounting, ready for receiving a detector module DM-TT-xx. It is ​
provided with three alarm levels for information alarm, pre-alarm and main alarm as well ​
as with a bargraph display to indicate the specific smoke density. The Titanus Pro Sens EB ​
can be directly connected to the esserbus / powered loop.
The device is supplied with front foil for single-tube operation.
11
Technical Data
12
Operating voltage
Current consumption
Quiescent current @ 24 V DC
Contact load relay
Sound level
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
14 ... 30 V DC
of the resre PCB max. 20 mA
approx. 260 mA (w/o reset PCB)
30 V DC/1 A max. 24 W
approx. 45 dB(A) (with sound absorber part no. ​
801543)
max. 1,5 mm²
-20 °C ... 60 °C
-25 °C ... 65 °C
≤ 95% w/o condensation
IP20
ABS plastic
white, similar to RAL 9018
approx. 1350 g
W: 200 mm H: 292 mm D: 113 mm
13
14
15
16
Isolator not included with delivery, can be optionally ordered under part no. 788612.
Pre-configured basic unit Titanus Top Sens EB including esserbus transponder, reset PCB and ​
front foil Titanus Top Sens 1 EB.
17
199
Detectors for Special Applications
¬q0A§/21e­
801532.10
Aspirating Smoke Detectors
Basic unit Titanus Top Sens 2 EB
Approval:
VdS
Basic device for wall mounting, pre-configured to receive up to two DM-TT-xx detector ​
modules.
The Titanus top Sens 2 EB is directly connectable to the esserbus/esserbus-Plus. The ​
device is shipped equipped with the front foil for the double tube operation.
1
Technical Data
Operating voltage
Current consumption
Quiescent current @ 24 V DC
Contact load relay
Sound level
Features
• Pre-configured for usage with two DM-TT-xx ​
detector modules
• Optical status display for information alarm, pre-​
alarm, main alarm and fault indication
• Integrated bar graph display to optically indicate ​
the current smoke level
• Ports for two suction tubes with an outside ​
diameter of 25 mm
• Port for air return tube
• Possible two-detection-dependency as per VdS ​
directive
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Type of protection
Housing
Color
Weight
Dimensions
14 ... 30 V DC
of the reset PCB max. 20 mA
approx. 275 mA (w/o reset PCB)
30 V DC/1 A max. 24 W
approx. 45 dB(A) (with sound absorber part no. ​
801543)
max. 1,5 mm²
-20 °C ... 60 °C
-25 °C ... 65 °C
≤ 95% w/o condensation
IP20
ABS plastic
white, similar to RAL 9018
approx. 1350 g
W: 200 mm H: 292 mm D: 113 mm
Isolator not included with delivery, can be optionally ordered under part no. 788612.
Pre-configured Titanus Top Sens 2 EB basic device contains 2 esserbus transponders, two reset ​
PC boards and the Titanus Top Sens 2 EB front foil.
Detector Modul for Titanus Pro Sens EB Aspirating Smoke Detection
¬q08§/21J­
801523.10
Detector module 0,5 % / m Typ DM-TP-50
Detector module for application in Titanus Pro Sens EB aspirating smoke detection​
systems (part nos. 801515.10, 801521.10, 801522.10) with a response sensitivity of
0.5 % l​ight opacity / m.
Early fire detection via HPLS technology. Installation into Titanus Pro Sens EB systems ​
without tools and adjustable via DIL switch on the outside of the detector module. The ​
parameterisation option allows sensitivity adjustments for the aspirating smoke detection ​
system.
1
Technical Data
Ambient temperature
Housing
Weight
Features
-20 °C ... 60 °C
ABS plastic
approx. 100 g
• Response sensitivity adjustable at the module
• Fast commissioning through automatic initialising ​
process
• Status display for status and fault diagnosis
• Installation into Titanus Pro Sens EB without tools
• Air flow monitoring for detecting pipe burst and ​
¬q09§/21M­
tube blockage
801524.10
Detector module 0.10 % / m DM-TP-10L
As 801523.10 but with raised response sensitivity of 0.10 % light opacity / m.
1
Technical Data
Ambient temperature
Housing
Weight
200
www.hls-austria.com
-20 °C ... 60 °C
ABS plastic
approx. 100 g
Detectors for Special Applications
¬q0:§/21P­
801525.10
Aspirating Smoke Detectors
1
Detector module 0.015 % / m DM-TP-01L
As 801524.10 but with raised response sensitivity of 0.015 % light opacity / m.
1
2
Technical Data
Ambient temperature
Housing
Weight
-20 °C ... 60 °C
ABS plastic
approx. 100 g
3
4
Detector Module for Titanus Top Sens EB Aspirating Smoke Detection
5
¬q0B§/21h­
801533.10
Detector module 0.5 % / m DM-TT-50L
1
6
Detector module for application in Titanus Top Sens aspirating smoke detection systems ​
(part nos. 801531.10, 801532.10) with a response sensitivity of 0.5 % light opacity / m. ​
Early fire detection via HPLS technology. Installation into Titanus Top Sens EB systems ​
without using any tools and adjustable via DIL switch on the outside of the detector ​
module. The parameter setting option allows sensitivity adjustments for the aspirating ​
smoke detection system.
7
8
Technical Data
Ambient temperature
Housing
Weight
¬q0C§/21k­
801534.10
-20 °C ... 60 °C
ABS plastic
approx. 100 g
9
Detector module 0.10 % / m DM-TT-10L
10
As 801533.10 but with a raised response sensitivity of 0.10 % light opacity / m.
1
Technical Data
Ambient temperature
Housing
Weight
11
-20 °C ... 60 °C
ABS plastic
approx. 100 g
12
¬q0D§/21n­
801535.10
13
Detector module 0.015 % / m DM-TT-01L
As 801534.10 but with a raised response sensitivity of 0.015 % light opacity / m.
1
14
Technical Data
Ambient temperature
Housing
Weight
-20 °C ... 60 °C
ABS plastic
approx. 100 g
15
16
17
201
Detectors for Special Applications
Aspirating Smoke Detectors
Accessories
¬q0LD­
Sound absorber for Titanus EB aspirating smoke detection s
​ ystems
801543.10
1
Sound absorber for redusing sound levels in Titanus EB aspirating smoke detection ​
systems for sound-sensitive applications. The sound absorber is connected to the tube ​
outlet and reduces the sound level during operation by up to 10 dB(A).
Installation either directly at the air release or with 10 cm maximum distance from the air ​
release.
Technical Data
Application temperature
Material
Color
Weight
Dimensions
-30 °C ... 60 °C
ABS plastic
grey, similar to RAL 7035
approx. 454 g
W: 122 mm H: 194 mm D: 96 mm
Aspirating
smoke
detector
Sound
absorber
End cap
¬q0M§/21"­
Application example
801544.10
Air filter for aspirating smoke detectors
Air filter for usage in areas with interfering environmental influences e.g. dust.
1
Technical Data
Application temperature
Material
Color
Dimensions
-30 °C ... 60 °C
ABS plastic
grey, similar to RAL 7035
W: 122 mm H: 194 mm D: 96 mm
Including filter cartridges (1 x 60 ppi, 1 x 45 ppi and 1 x 25 ppi)
¬q1%8­
801604
Replacement air filter pads for 801544
Replacement cartridge for air filters (801544), consisting of one fine, medium and coarse ​
filter pad each.
1
Filter cartridges (1 x 60 ppi, 1 x 45 ppi, 1 x 25 ppi)
1 Set
202
www.hls-austria.com
Detectors for Special Applications
¬q1!,­
Aspirating Smoke Detectors
1
Special filter
801600
Special filter for use in areas with extreme pollution.
2
Technical Data
1
Dimensions
L: 418 mm
3
Features
4
• Filter cartridge filters particles up to a size of 7.5 ​
μm
• Housing resistant to different organic and inor­
ganic chemicals, fuels and hot water
¬q1&;­
5
Replacement filter element for 801600
801605
6
Technical Data
1
Application temperature
Material
Dimensions
-20 °C ... 60 °C
Polypropylen
Ø: 64 mm L: 254 mm
7
8
¬q0I;­
9
Device holder for aspirating smoke detection systems Titanus EB
801540
Device holder for mounting aspirating smoke detection systems to frames or for self-​
supporting mounting.
10
1
Technical Data
Weight
Dimensions
approx. 1160 g
L: 92 mm W: 432 mm
11
¬q0J>­
12
Reset PCB for Titanus EB
801541
PCB for resetting the Titanus Pro Sens EB and the Titanus Top Sens EB aspirating smoke ​
detection system via the fire alarm control panel.
13
1
Technical Data
Current consumption
Dimensions
5 to 50 mA
L: 45 mm W: 57 mm
14
Phase-out date: 01.01.2011
15
¬q0KA­
Back-flow valve for Titanus EB
801542
1
16
Valve for cleaning the tubing system through air purging via compressed air. In systems ​
with air purging, the non-return valve is mounted at the end of the tubing branch and ​
prevents a build-up of dirt particles at the end of the tube.
17
Technical Data
Color
dark grey
203
Detectors for Special Applications
¬q0PP­
Aspirating Smoke Detectors
Front foil Titanus Pro Sens 2 EB
801547
Front foil for indicating alarms when using two detector modules
1
¬q0QS­
Front foil Titanus Top Sens 2 EB
801548
Front foil for indicating staged alarm modes and smoke density levels when using two ​
detector modules.
1
¬q0RV­
Diagnostics tool for Titanus EB
801549
Diagnostics tool for Titanus EB aspirating smoke detector systems for reading the meas­
urement data and device configurations as well as for localization of faults.
1
Diagnostics interface, connecting cable and diagnostic software
204
www.hls-austria.com
Detectors for Special Applications
Aspirating Smoke Detectors
Accessories for Aspiration Smoke System
1
761520.10
2
¬m05§/21=­
Pipe (ABS), diameter 25 mm
Length = 3 m
1
10 Pcs.
3
¬m06§/[email protected]­
761521.10
4
90° bend (PVC) for 25 mm pipe
10 Pcs.
5
1
6
7
¬m07§/21C­
8
90° angle (PVC) for 25 mm pipe
761522.10
10 Pcs.
9
1
10
11
¬m08§/21F­
45° angle (PVC) for 25 mm pipe
761523.10
12
10 Pcs.
13
1
14
15
¬m09§/21I­
T-Piece (PVC) for 25 mm pipe
761524.10
16
10 Pcs.
1
17
205
Detectors for Special Applications
Aspirating Smoke Detectors
¬m0:§/21L­
761525.10
Sleeve (PVC) for 25 mm pipe
10 Pcs.
1
¬m0;§/21O­
761526.10
End cap (PVC) for 25 mm pipe
10 Pcs.
1
¬m0L§/21¤­
761543.10
Corrugated polyester hose
This article will be charged per meter.
1
¬m0RR­
761549
Ceiling lead-through adapter ABS
For 761542.10
1
¬m0K§/21¡­
Suctions hose set for 25 mm pipe
761542.10
For flexible installation in object surveillance or suspended ceilings.
1
Technical Data
Dimensions
L: 3000 mm
All components are pre-mounted and glued.
1 x T piece (761524), 3 m corrugated polyester hose, (761543), 1 x ceiling lead-through adapter ​
with threaded joint
T-piece
False
ceiling
Suspended ceiling
Monitoring of room
206
www.hls-austria.com
Pipe
Polyester hose
Aspirator sampling
assembly
Detectors for Special Applications
¬q1#2­
801602
Aspirating Smoke Detectors
1
Three-way ball valve
For manual disconnection of aspirating smoke detectors from connected piping system ​
during the blow cleaning process.
2
1
Technical Data
Application temperature
Material
Dimensions
-40 °C ... 50 °C
PVC
L: 131 mm
3
includes three transition screw joints for connection to a 25 mm piping system
4
¬q1'>­
801606
1
Condensate trap for aspirating smoke detectors
5
Condensate trap with sintered metal filter for separation and absorption of condensed ​
liquids, used for protecting aspirating smoke detectors including threaded cable connec­
tion and mounting bracket.
6
Technical Data
Ambient temperature
Material
Color
Weight
Dimensions
7
0 °C ... 80 °C
ABS
light grey
approx. 620 g
W: 68 mm H: 300 mm D: 36 mm
8
Features
9
• Plastic housing with manual outlet valve
• Plug connectors for attaching to a piping system
¬m0D(­
761535
10
Adhesive, 0.5 kg can
Adhesive for connecting ABS and PVC pipes.
11
1
12
13
¬m0E+­
761536
PVC detergente, 1 L can
14
Detergente for cleaning PVC pipes and fittings before glueing.
15
1
16
17
207
Detectors for Special Applications
¬m0F§/21p­
761537.10
Aspirating Smoke Detectors
Mounting clip for 25 mm pipe
100 Pcs.
1
¬m0O§/21$­
761546.10
Pipe cutter for PVC / ABS pipes
Pipe cutter for plastic pipes 6-35 mm
¬m0PL­
761547
Labels-sampling points wrap round
The labels-sampling points wrap round serves for the marking of the intake points of the ​
PVC/ABS pipe.
1
Please note the Labels-Sampling Points Wrap Round are not use for tapering the intake points.
Roll with 200 labels.
¬q0SY­
801550
Banderole for suction reducing foil
Banderole for securing the suction-reducing foils on the tubing system. The red marking is ​
used for the localization of the detector points in the object.
1
10 Pcs.
208
www.hls-austria.com
Detectors for Special Applications
Aspirating Smoke Detectors
Aspiration Reducing Films
1
801551
Aspiration reducing film sheet, 2,0 mm
2
Aspiration reducing film sheet, 2.5 mm
3
Aspiration reducing film sheet, 3.0 mm
4
801552
801553
801554
801555
801556
801557
801558
801559
801560
801561
801562
801563
801564
801565
801566
801567
¬q0T\­
¬q0U_­
¬q0Vb­
¬q0We­
¬q0Xh­
¬q0Yk­
¬q0Zn­
¬q0[q­
¬q0\t­
¬q0]w­
¬q0^z­
¬q0_­
¬q0`¢­
¬q0a¥­
¬q0b¨­
¬q0c"­
¬q0d%­
Aspiration reducing film sheet, 3.2 mm
5
Aspiration reducing film sheet, 3.4 mm
6
Aspiration reducing film sheet, 3.6 mm
7
Apiration reducing film sheet, 3.8 mm
8
Aspiration reducing film sheet, 4.0 mm
9
Aspiration reducing film sheet, 4.2 mm
10
Aspiration reducing film sheet, 4.4 mm
11
Aspiration reducing film sheet, 4.6 mm
12
Aspiration reducing film sheet, 5.0 mm
13
Aspiration reducing film sheet, 5.2 mm
14
Aspiration reducing film sheet, 5.6 mm
15
Aspiration reducing film sheet, 6,0 mm
16
Apiration reducing film sheet, 6.8 mm
17
Apiration reducing film sheet, 7.0 mm
209
Detectors for Special Applications
Accessories
¬o.A¦­
781332
Reset module for hat rail mounting
1
Module for connecting a third-party detector (with floating relay contact for alarm and ​
fault) on a conventional primary loop. Remote reset function can be controlled via the relay ​
contact on the reset module. Total power consumption depends on the detectors that are ​
connected. The following detector types can be connected: high sensitivity aspirating ​
smoke detection system, flame detectors, Fireray, line type heat and smoke detectors etc.
Technical Data
Operating voltage
Quiescent current
Current consumption @ 12 V DC
Current consumption @ 24 V DC
Contact load relay
Dimensions
10.5 ... 28 V DC
approx. 0.5 mA (out of detectorzone)
approx. 1 mA (Relay active: 35 mA)
approx. 10 mA (Relay active: 55 mA)
30 V DC / 1 A
W: 37 mm H: 107 mm D: 13 mm (PC-Board)
Version: Module housing for hat rail mounting.
¬o.B©­
Phase-out date: 01.01.2011
781333
Reset module with mounting bracket for Fireray 2000
Reset module as in 781332 including mounting accessories for installation in Fireray 2000 ​
evaluation unit (part no. 761321).
1
Reset module including bracket and mounting material.
Phase-out date: 01.01.2011
210
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Alarm Devices
IQ8Alarm
212-222
Conventional
223-231
Remote Indicators
232-234 12
11
13
14
15
16
17
211
Alarm Devices
IQ8Alarm
IQ8Alarm enables IQ8Quad detector application with integrated alarm signalling and other ​
advantages. No matter whether multilingual speech alarm, flexible signal combination or ​
user-friendly programming interfaces, all these features are also available when using ​
IQ8Alarm.
The IQ8Alarm range offers distinct advantages, which will surely convince every user in the ​
blink of an eye.
Advantages with IQ8Alarm at one glance:
Simple programming enabled by a standardised programming interface for all IQ8Systems ​
(IQ8Quad + IQ8Alarm) alarm signalling devices
Voltage supply on the loop
Time-tested, unobtrusive design
Signalling device in compliance with EN 54 with 20 different signalling tones including DIN ​
tone in compliance with DIN 33404-3
On the following pages, you will find more detailed information about IQ8Alarm features.
212
www.hls-austria.com
Alarm Devices
IQ8Alarm
1
IQ8Alarm
Country code
acc. to ISO
3166 -Alpha-2
Language
code acc.
to ISO 639-1 Evacuation 1
de
Germany
(DE)
en
Great Britain
(GB)
fr
France
(FR)
es
Spain
(ES)
it
Italy
(IT)
Evacuation 2
Alarm
Dies ist ein
Feueralarm. Bitte
verlassen Sie das
Gebäude umgehend über die
nächsten Fluchtwege. Die Feuerwehr ist alarmiert.
Achtung, Achtung!
Dies ist eine Gefahrenmeldung. Bitte
verlassen Sie das
Gebäude über die
nächsten
Ausgänge.
Achtung, im Gebäude ist eine
Gefahrensituation
gemeldet worden.
Bitte bleiben Sie
ruhig, und warten
Sie auf weitere
Anweisungen.
This is a fire alarm.
Please leave the
building immediately by the nearest
available exit.
Attention please.
This is an emergency. Please leave the
building by the
nearest available exit.
An incident has
been reported in the
building. Please
await further
instructions.
Ceci est une alarme
incendie,veuillez
évacuer
immédiatement les
locaux par la sortie
la plus proche.
Votre attention s'il
vous plaît, ceci est
une alarme. Veuillez
évacuer les locaux
par la sortie la plus
proche.
Un incident est
signalé dans le
batiment. Merci de
garder votre calme
et attendez les
prochaines
instructions.
Esto es una alarma
de incendio.
Abandonen
por favor el edificio
inmediatamente
por la salida de
evacuación
más cercana.
Atención. Esto es
una emergencia.
Por favor
abandonen el
edificio por la
salida de
evacuación
más cercana.
Attenzione.
Allarme incendio.
Abbandonare
l'edificio tramite
l'uscita di
emergenza più
vicina.
Attenzione.
Allarme in corso.
Vi preghiamo di
recarvi presso
l'uscita di
emergenza più
vicina.
2
Test-message
All-Clear
Dies ist eine
Testdurchsage.
Die Gefahrensituation
ist jetzt behoben. Wir
entschuldigen uns
für jegliche
Unannehmlichkeiten.
This is a test
message.
No action is
required.
The emergency is
now cancelled. We
apologize for any
inconvenience.
3
4
5
Ceci est un test.
L'alarme est à
présent annulée.
Veuillez nous excuser
pour le désagrément.
Atención, se ha
reportado un
incidente
en el edificio.
Aguarden por favor
otras instrucciones.
Esto es un
mensaje
de prueba.
No se requiere
ninguna acción.
La emergencia ha
sido cancelada.
Pedimos disculpas
por las molestias
causadas.
Attenzione.
E' stato rilevato un
allarme.Ulteriori
disposizioni vi
verranno
comunicate
appena possibile.
Attenzione.
E' in corso una
prova di allarme.
Non è richiesta
alcuna azione.
6
7
8
Attenzione. Cessato
allarme.La situazione
di normalità è stata
ripristinata.
9
10
Standard speech messages of IQ8Quad detectors and IQ8Alarm
No.
Description
Frequency
Pulse rate
1
School bell
complex
2
FP 1063.1 Telecoms
BS 5839 Pt1
Alternating 800 / 970 Hz at 2 Hz
3
BS 5839 Pt1
Alternating 800 / 970 Hz at 1 Hz
f
4
BS 5839 Pt1
Intermittent 970 Hz at 1 Hz 0.5 sec.
f
5
BS 5839 Pt1
Intermittent 2850 Hz at 1 Hz 0.5 sec.
f
f
0,25 sec.
0,25 sec.
6
BS 5839 Pt1
Intermittent 970 Hz 1/4 sec. ON - 1 sec. OFF
f
7
BS 5839 Pt1
Continious 970 Hz
f
8
BS 5839 Pt1
Sweep tone 800 Hz tp 970 Hz at 7 Hz
f
9
BS 5839 Pt1
Sweep tone 800 Hz to 970 Hz at 1 Hz
f
10
DIN Tone
DIN 33404 Part 3
1200 - 500 Hz at 1 Hz
f
11
French fire sound
554 Hz / 100 ms + 440 Hz / 400 ms + 10 %
f
12
NL - Slow Whoop
500 Hz - 1200 Hz at 3.5 sec. break of 0.5 sec.
f
13
US - Horn
Continious 485 Hz
f
14
US - Horn with
Temporal Pattern
Intermittent 485 Hz
(0,5 sec. ON; 0.5 sec. OFF; 3 times; 1.5 sec. OFF; Repeat)
f
15
US - March
Time
Alternating 485 Hz
(0,25 sec. ON; 0.25 sec. OFF; Repeat)
f
16
US - Slow
Whoop
Sweep tone 500 Hz to 1200 Hz
(4.0 sec. ON; 0.5 sec. OFF; Repeat)
f
17
US - Siren
18
US - Hi/Lo
Sweep tone 600 Hz to 1200 Hz
(1,0 sec. ON, Repeat)
Alternating 100 Hz / 800 Hz
(0.25 sec. ON; Alternate; 0.25 sec. ON; Alternate; Repeat)
19
US - NFPA
Whoop
IMO
GA-Signal
Sweep tone 422 Hz to 775 Hz
(upwards sweep 0.85 sec.; 3 times; 1 sec. OFF; Repeat)
Intermittent 800 Hz (1,0 sec. ON; 1,0 sec.
OFF: 7 times; 2.0 sec. ON: 2.0 sec. OFF; Repeat)
20
11
complex
t
0,5 sec.
0,5 sec.
0,5 sec.
0,5 sec.
0,5 sec.
0,5 sec.
0,25 sec.
12
t
1,5 sec.
t
1,5 sec.
1,0 sec.
t
13
t
t
10 ms
t
14
1,0 sec.
t
1,0 sec.
t
0,1 sec.
0,4 sec.
t
3,5 sec. 0,5 sec.
15
t
t
0,5 sec.
1,5 sec.
0,5 sec.
f
f
f
f
t
16
0,25 sec.
0,25 sec.
t
4,0 sec. 0,5 sec.
t
1,0 sec.
17
t
0,25 sec.
0,25 sec.
0,85 sec.
1,0 sec.
1,0 sec.
t
1,0 sec.
t
t
IQ8Quad detector and IQ8Alarm tone table
213
Alarm Devices
Features
• Completely bus supplied alarm device
• Powered loop compatible
• 5 different signaling device types - acoustic - ​
•
•
•
•
optical- acoustic / optical- acoustic / optical- ​
acoustic / optical / speech
Multilingual speech alarm in 5 different languages
Alarm signaling, evacuation, and test alarm can be ​
respectively programmed in different languages
Up to 32 alarm devices for each powered loop
Each alarm device with built-in isolator
Acoustic alarm signaling:
• Acoustic pressure up to 99 dB(A) @ 1 m
• Volume programmable in 8 steps via tools 8000
• 20 different signaling tones, including DIN tone
• Speech alarm, 5 pre-programmed alarm texts and ​
other country-typical alarm signals
Optical alarm signaling:
• Flash intensity equivalent to 3W Xenon flash light
• Light intensity: max. 3.87cd effective, max. 24cd ​
peak
IQ8Alarm
IQ8Alarm alarm signaling devices represent a more sophisticated version replacing our ​
powered loop products. On the whole, there are 5 different alarm signaling product groups:
- Sounders
- Speech alarm
- Alarm devices with combined acoustic and optical alarm signaling
- Alarm devices with combined acoustic and optical alarm signaling with speech alarm
- Optical alarm signaling devices
How to define the maximum number of alarm signaling devices foe connection to the same ​
primary loop:
In case of mixed operation of various alarm signaling types and bases connected to the ​
same primary loop, the maximum number depends on the loop length. Each individual ​
load factor must be added up, since the load factor defines the respective current ​
consumption for each alarm device during alarm.
For IQ8Alarm application, the load factor depends on the alarm device type (see technical ​
data).
Please consider our examples and tables shown in the „Project Planning Support“ section.
The total load factor for one primary loop is not permitted to exceed the maximum value of ​
96. Altogether up to 127 bus devices per loop can still be connected.
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Quiescent current @ FACP battery
Load factor
Frequency of flash
Lighting energy
Strength of light
Ambient temperature
Type of protection
Housing
Weight
Specification
Dimensions
8 ... 42 V DC (via powered loop)
approx. 55 μA
approx. 300 μA
3
ca. 1 Hz
approx. 3 J
max. 24,4 cd peak/ 4,1 cd effektiv (red flash)
-10 °C ... 50 °C
IP30
(IP65 with socket 806201 / 806202)
ABS plastic
approx. 300 g
EN 54-3 acoustic signaling device
EN 54-3 acoustic speech signaling device (Q2/2011)
Ø: 112 mm D: 75 mm
Ø: 112 mm D: 90 mm (with IP65 socket)
IQ8Control with powered loop functionality.
The system can only be programmed when using the tools 8000 editor.
- Admissible maximum loop length
- Admissible maximum number of single alarm device types
- Maximum number of 127 bus devices for each loop
Systems requirements:
FACP IQ8Control Version 3.04 with the programming software tools 8000 Version 1.09!
Attention - an operation with the FACP''S 8000 C/M is not possible!!!
For upgrading 8000 C/M control units, IQ8Lumivox signaling devices must be used. If required, ​
please contact our returns department.
For checking the battery capacity of fire alarm control units, the value „quiescent current @ ​FACP
battery“ can be added.
214
www.hls-austria.com
Alarm Devices
IQ8Alarm
IQ8Alarm Acustical Alarm Devices
1
807205
2
¬qi&D­
IQ8Alarm sounder, white
Approval:
1
VdS
3
Addressable, completely bus supplied and short circuit / open circuit resilient alarm ​
signaling device in compliance with EN 54-3 with up to 20 different programmable ​
signaling tones including DIN tone in accordance with DIN 33404 Part 3 for acoustic alarm ​
signaling. The volume can be set to 8 different levels. Its flat design enables optimum ​
adaptation to the environments. It is made of shock and scratch resistant plastic. Option­
ally, bases 806201 and 806202 with side cable entry and weatherproof protection can be ​
installed.
4
5
Technical Data
Quiescent current @ FACP battery
Load factor
Color
Specification
approx. 300 μA
3
white, similar to RAL 9010
EN 54-3 acoustic signaling device
6
Accessories
7
806201 IP65 base, white
¬qi'G­
807206
8
IQ8Alarm sounder, red
Approval:
1
9
VdS
As in 807205, but red
10
Technical Data
Quiescent current @ FACP battery
Load factor
Color
approx. 300 μA
3
red, similar to RAL 3020
11
Accessories
806202 IP65 base, red
12
13
14
15
16
17
215
Alarm Devices
807322
¬qj7y­
IQ8Alarm
IQ8Alarm speech alarm, white
Approval:
1
VdS
As in 807205, but with additional speech alarm function.
Technical Data
Quiescent current @ FACP battery
Load factor
Color
Specification
approx. 300 μA
3
white, similar to RAL 9010
EN 54-3 acoustic signaling device
EN 54-3 acousitc speech signaling device (Q2/2011)
Accessories
806201 IP65 base, white
¬qjA0­
807332
IQ8Alarm speech alarm, red
Approval:
1
VdS
As in 807322, but red
Technical Data
Quiescent current @ FACP battery
Load factor
Color
Accessories
806202 IP65 base, red
216
www.hls-austria.com
approx. 300 μA
3
red, similar to RAL 3020
Alarm Devices
807322.SV99
¬qj7§/TW::4­
IQ8Alarm
1
IQ8Alarm speech alarm, white
Same as 807322 but with individual text and/or sound.
1
2
When ordering, please note the “ordering information for IQ8Quad and IQ8Alarm” printed in the ​
appendix.
Costs for the recording of customer-specific texts and/or tones can be obtained on request.
3
Cancellations or returns are not possible.
Programmed according to customer specifications.
4
Accessories
806201 IP65 base, white
5
6
7
¬qj7§/TW:9+­
807322.SV98
IQ8Alarm speech alarm, white
8
Same as 807322 but with individual selection of language.
1
When ordering, please note the "ordering information for IQ8Quad and IQ8Alarm" printed in the ​
appendix.
9
Cancellations or returns are not possible.
Programmed with an individual selection of up to 5 national languages
10
Accessories
806201 IP65 base, white
11
12
13
14
15
16
17
217
Alarm Devices
807332.SV99
¬qjA§/TW::R­
IQ8Alarm speech alarm, red - customized version
As 807332, but customized version.
1
Accessories
806202 IP65 base, red
¬qjA§/TW:9I­
807332.SV98
IQ8Alarm speech alarm, red - special language
As 807332, but special language.
1
Accessories
806202 IP65 base, red
218
www.hls-austria.com
IQ8Alarm
Alarm Devices
IQ8Alarm
IQ8Alarm Combined Alarm and Speech Signallng Device
1
807224
2
¬qi9­
IQ8Alarm combined alarm signaling device
Approval:
1
VdS
3
Addressable, completely bus supplied and short circuit / open circuit resilient alarm ​
signaling device in compliance with EN 54-3 with up to 20 different programmable ​
signaling tones including DIN tone in accordance with DIN 33404 Part 3 for acoustic and ​
optical alarm signaling. The volume can be set to 8 different levels. Its flat design enables ​
optimum adaptation to the environments. It is made of shock and scratch resistant plastic. ​
Optionally, bases 806201 and 806202 with side cable entry and weatherproof protection ​
(IP65) can be installed.
4
5
Technical Data
Quiescent current @ FACP battery
Load factor
Color
Specification
approx. 300 μA
3
red, similar to RAL 3020
EN 54-3 acoustic signaling device
6
Accessories
806202 IP65 base, red
7
IQ8Alarm combined speech alarm
8
¬qjiA­
807372
Approval:
1
VdS
As in 807224, but with programmed speech alarm for powered loop connection.
9
Technical Data
Operating voltage
Quiescent current @ FACP battery
Load factor
Frequency of flash
Ambient temperature
Type of protection
Specification
8 ... 42 V DC (via powered loop)
approx. 300 μA
3
ca. 1 Hz
-10 °C ... 50 °C
IP30
EN 54-3 acoustic signaling device
EN 54-3 acoustic speech signalling device (Q2/2011)
10
11
12
IQ8Control with esserbus Plus functionality. Programming is only possible with the tools 8000 ​
software.
Please note: the max. allowable loop length; the max. allowable number of individual types of ​
alarm signaling devices; the max. number of a total of 127 devices per loop
13
Systems requirements: FACP IQ8Control Version 3.04 with programming software tools 8000 ​
Version 1.09!
14
Please note - operation with the FACP's 8000 C/M is not possible!!!
IQ8Lumivox signaling devices must be used when upgrading 8000 C/M control units. If ​
required, please contact our returns department.
15
For checking battery capacity of fire alarm control units, the value "quiescent current @ FACP ​
battery" can be added.
16
Programmed with 5 standard national languages (DE/GB/FR/ES/IT).
Accessories
806202 IP65 base, red
17
219
Alarm Devices
¬qji§/TW:9Z­
IQ8Alarm
IQ8Alarm combined speech alarm with composition of other ​languages
807372.SV98
Approval:
1
VdS
As with 807372, but with an individual combination of national languages.
Technical Data
Quiescent current @ FACP battery
Load factor
approx. 300 μA
3
When ordering, please note the "ordering information for IQ8Quad and IQ8Alarm alarm signaling ​
devices" printed in the appendix.
Please take not that no cancellations or returns accepted.
Programmed with an individual combination of up to 5 national languages.
Accessories
806202 IP65 base, red
¬qji§/TW::c­
807372.SV99
IQ8Alarm combined speech alarm as customized version
Approval:
1
VdS
As 807372, but with individual texts and/or sounds. The max. recording time per device is ​
169 seconds.
Technical Data
Quiescent current @ FACP battery
Load factor
approx. 300 μA
3
When ordering, please note the "ordering information for IQ8Quad and IQ8Alarm" printed in the ​
appendix.
Costs for the recording of customer-specific texts and/or tones can be obtained by request.
Please take not that no cancellations or returns accepted.
Programmed in accordance with customized combination.
Accessories
806202 IP65 base, red
220
www.hls-austria.com
Alarm Devices
IQ8Alarm
IQ8Alarm optical alarm signalling devices
1
807212
2
¬qi-Y­
IQ8Alarm optical alarm signaling device, amber
Approval:
1
VdS
Addressable, completely bus supplied and short circuit / open circuit resilient alarm ​
signaling device for optical alarm signaling. Its flat and unobtrusive design enables ​
optimum adaptation to the environments.
3
Technical Data
4
Quiescent current @ FACP battery
Load factor
Frequency of flash
Lighting energy
Strength of light
Color
approx. 300 μA
3
ca. 1 Hz
approx. 3 J
max. 24cd peak/3,87 cd effctive
base: white, similar RAL 9010
5
6
Accessories
806201 IP65 base, white
¬qi.\­
807213
7
IQ8Alarm optical alarm signaling device / tranparent, blue, green
Approval:
1
VdS
8
As in 807212, but transparent, blue and green.
Technical Data
Quiescent current @ FACP battery
Load factor
Strength of light
Color
9
approx. 300 μA
3
transparent: max. 17,39 cd peak/2,16 cd effektiv
blue: max 5,06 cd peak/0,62 cd effektiv
green: max. 2,72 cd peak/0,33 cd effektiv
base: white, similar RAL 9010
10
Accessories
11
806201 IP65 base, white
¬qi/_­
807214
12
IQ8Alarm optical alarm signaling device, red
Approval:
1
13
VdS
As in 807212, but red
14
Technical Data
Quiescent current @ FACP battery
Load factor
Strength of light
Color
approx. 300 μA
3
max. 20.91 cd peak/3.41cd effective
cap: red
15
Accessories
16
806202 IP65 base, red
17
221
Alarm Devices
Accessories
806201
IQ8Alarm
¬q_"$­
Base IP65 for IQ8Alarm, white
Base, white, for IQ8Alarm device with protection type IP65 and surface mount cable ​entry.
1
Technical Data
Type of protection
Color
IP65
white, similar to RAL 9010
¬q_#'­
806202
Base IP65 for IQ8Alarm, red
Base, red, for IQ8Alarm device with protection type IP65 and surface mount cable entry.
1
Technical Data
Type of protection
Color
222
www.hls-austria.com
IP65
red, similar to RAL 3020
Alarm Devices
Conventional
1
Audible Alarm Devices
¬m_:h­
766225
2
Shallow base sounder, red
Approval:
VdS
3
The alarm signaling device offers a selection of 32 acoustic signals including the DIN ​
German standard as well as additional country-specific acoustic signals.
1
The configuration is carried out via a five-pin DIL-switch. Up to two different acoustic ​
signals can be activated.
4
The volume can be continuously adjusted via a potentiometer.
5
Technical Data
Features
• Flat design
• Suitable for 12 and 24 V DC operating voltage
• Low amount of alarm current
Operating voltage
Alarm current @ 12 V DC
Starting current
Ambient temperature
Type of protection
Housing
Color
Dimensions
9 ... 15 V DC
approx.3 mA
ca. 30 mA
-25 °C ... 70 °C
IP65 with 766237
ABS V0
red, similar to RAL 3001
Ø: 93 mm H: 63 mm
Ø: 93 mm H: 91 mm (incl. base 766237/38)
6
7
8
Not suitable for using outside or in humid environments.
Please use therefore the optional bases with side cable entry (part no. 766237 or 766238).
9
Accessories
766237 IP65 base, red
¬m_;k­
766226
10
Sounder with low-profile base, white
Approval:
1
VdS
11
The alarm signaling device offers a selection of 32 acoustic signals including the DIN ​
German standard as well as additional country-specific acoustic signals.
12
The configuration is carried out via a five-pin DIL-switch. Up to two different acoustic ​
signals can be activated.
The volume can be continuously adjusted via a potentiometer.
13
Technical Data
Features
• Flat design
• Suitable for 12 and 24 V DC operating voltage
• Low amount of alarm current
Operating voltage
Alarm current @ 12 V DC
Starting current
Ambient temperature
Type of protection
Housing
Color
Dimensions
14
9 ... 15 V DC
approx.3 mA
ca. 30 mA
-25 °C ... 70 °C
IP65 with 766237
ABS V0
white, similar to RAL 9010
Ø: 93 mm H: 63 mm
Ø: 93 mm H: 91 mm (incl. base part.-no. 766237/​
766238)
15
16
Not suitable for using outside or in humid environments.
17
Please use therefore the optional bases with side cable entry (part no. 766237 or 766238).
Accessories
766238 IP65 base, white
223
Alarm Devices
766239
Conventional
¬m_H+­
Sounder, red
As per DIN 33404 - 3 and EN 457. 32 programmable signaling tones, can be selected via ​
DIL-switch (two tones each), volume control via potentiometer.
1
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Quiescent current @ 24 V DC
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
¬m_^m­
766261
9 ... 28 V DC
approx. 8 mA
approx. 5 mA
-10 °C ... 55 °C
-25 °C ... 70 °C
IP21C
ABS
red, similar to RAL 3001
W: 108 mm H: 91 mm
Signal base
Approval:
1
VdS
Alarm sounder as per DIN 33404, - 3 and EN 457 to be mounted below detector base with ​
relay output for automatic detector series 9x00; with 28 programmable signaling tones, ​
can be selected via five-pole DIL switch (two tones out of 28 can be programmed), volume ​
control via potentiometer.
Technical Data
Operating voltage
Current consumption @ 12 V DC
Starting current
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
Accessories
766262 Cover plate for signal base
224
www.hls-austria.com
10 ... 28 V DC
approx. 5 mA (10 mA for DIN-Tone)
ca. 30 mA
-40 °C ... 80 °C
-45 °C ... 85 °C
IP54
ABS plastic
white, similar to RAL 9010
approx. 150 g
Ø: 111 mm H: 26 mm
Alarm Devices
Accessories
766262
Conventional
1
¬m__p­
2
Cover plate for 766261 signal base
For covering the connection when operated without detector.
1
3
Technical Data
Color
white, similar to RAL 9010
Cover plate and one screw
4
¬m_F%­
766237
Base with side cable entry, red
5
For alarm sounder 766225, 766226, flashlights 766410, 766411, 766412, 766413, 766414 ​
and combined alarm device 766240 including rubber seal.
1
Technical Data
Type of protection
Color
Dimensions
6
IP65
red, similar to RAL 3001
Ø: 94 mm H: 47 mm
7
Rubber seal and two screws
¬m_G(­
766238
8
Base with side cable entry, white
For 766236 alarm sounder but white.
1
9
Technical Data
Type of protection
Color
Dimensions
IP65
white, similar to RAL 9003
Ø: 94 mm H: 47 mm
10
Rubber seal and two screws
11
¬m_?w­
766230
12
Base with side cable entry, red
For alarm sounder 766225, 766226, flashlights 766410, 766411, 766412, 766413, ​
766414, combined alarm devices 766240, 766240.20 including rubber seal.
13
1
Technical Data
Type of protection
Color
IP65
red, similar to RAL 3001
14
Rubber seal and two screws
15
16
17
225
Alarm Devices
Explosion-Proof
045040
Conventional
¬%SI5­
Ex signaling device DS10, 12 V DC, 107 dB(A)
Approval:
VdS (FDT)
The sound generator is especially suitable for hazardous industrial areas (zone 2 and 22). ​
The robust aluminum die-cast housing is resistant to chemicals and environmental factors. ​
The DS10 complies with the technical requirements of DIN 33404 - 3 "hazard signals for ​
workplaces".
1
Technical Data
Features
• 9 tone sequences can be programmed:
• Continuous tone
• Alternating tone
• Intermittent tone
• Siren
• Fire alarm (different national regulations taken ​
into account)
Operating voltage
Current consumption
Sound level
Ambient temperature
Storage temperature
Air humidity
Ex-category
Explosion protection
Type of protection
Material
Color
Weight
Specification
Dimensions
10 ... 14 V DC
typ. 300 mA
106 dB(A) @ 1 m
-25 °C ... 55 °C
-40 °C ... 70 °C
≤ 90%
II 3GD
EEx nA II T4
IP56
aluminium die cast
red, similar to RAL 3000
approx. 1800 g
EN 54-3
W: 150 mm H: 150 mm D: 119 mm
According to the conformity declaration, the alarm devices can be used in zones 2 and 22.
¬m_VU­
766253
Ex Sounder 12 V DC, 110 dB(A)
KEMA 99 ATEX 7906 design certificate
1
The ex sounder is especially suitable for application in hazardous areas at industrial work­
places category 2G or 3G (formerly zones 1 and 2) and complies with the technical ​
requirements of DIN 33404 - 3. The robust aluminium die-cast housing is resistant to ​
chemicals and environmental factors.
Technical Data
Features
• 32 tone sequences can be programmed:
• Quartz controlled sound synchronisation
• ATEX approved
• LM6 aluminium die-cast housing
• Self-extinguishing aluminium cone, similar to UL ​
94 VO
226
www.hls-austria.com
Operating voltage
Current consumption
Sound level
Ambient temperature
Storage temperature
Air humidity
Explosion protection
Type of protection
Material
Color
Weight
EC-type examination certificate
Dimensions
12 V DC
typ. 195 mA; 170 mA bei DIN-Ton
110 dB(A) ± 3 dB @ 1 m (depending on signalling type)
-50 °C ... 55 °C
-50 °C ... 70 °C
≤ 90 %
II 2G EEx d IIC T4
IP67
aluminium die cast LM6
red, similar to RAL 3000
approx. 3160 g
KEMA 99ATEX 7906
Ø: 181 mm L: 263 mm
Alarm Devices
Conventional
Optical Alarm Devices
1
Conventional
2
766303
¬m`$(­
Flashing light 12 V DC, amber
3
Technical Data
1
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
12 V DC
350 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
4
5
6
7
Wall bracket included.
¬m`%+­
766304
Flashing light 24 V DC, amber
8
As 766303 but 24 V DC operating voltage.
1
Technical Data
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
9
24 V DC
250 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
10
11
12
Wall bracket included.
¬m`&.­
766305
13
Flashing light 12 V DC, red
As 766303 but red.
1
14
Technical Data
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
12 V DC
350 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
15
16
17
227
Alarm Devices
766306
Conventional
¬m`'1­
Flashing light 24 V DC, red
As 766303 but 24 V DC operating voltage and red cap.
1
Technical Data
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
¬m`(4­
766307
24 V DC
250 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
Flashing light 12 V DC, green
As 766303 but green.
1
Technical Data
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
¬m`)7­
766308
12 V DC
350 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
Flashing light 24 V DC, green
As 766303, but 24 V DC operating voltage and red cap.
1
Technical Data
Operating voltage
Alarm current
Frequency of flash
Lighting energy
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
228
www.hls-austria.com
24 V DC
250 mA
ca. 1 Hz
approx. 4 J
-20 °C ... 50 °C
-25 °C ... 55 °C
IP54
ABS plastic
grey, similar to RAL 7035
approx. 360 g
Ø: 108 mm H: 133 mm
Alarm Devices
766410
¬ma+?­
Conventional
1
Optical alarm signaling device, red
Approval:
1
VdS
2
Technical Data
Operating voltage
Current consumption @ 24 V DC
Frequency of flash
Strength of light
Application temperature
Type of protection
Material
Weight
Dimensions
9 ... 60 V DC
approx. 88 mA
ca. 1 Hz
5 Cd
-25 °C ... 70 °C
IP65 with 766237
base ABS
cup PC
approx. 150 g
Ø: 94 mm H: 67 mm (incl. base)
3
4
5
Not suitable for using outside or in humid environments.
Please use the optional bases with side cable entry (part no. 766237 or 766238).
6
Accessories
IP65 base red, 766237
Mounting bracket 767800
¬ma,B­
766411
7
Optical alarm signalling device, amber
Approval:
1
8
VdS
As 766410, but amber colour.
9
Technical Data
Operating voltage
Current consumption @ 24 V DC
Frequency of flash
Strength of light
Application temperature
Type of protection
Material
Weight
Dimensions
9 ... 60 V DC
approx. 88 mA
ca. 1 Hz
10 Cd
-25 °C ... 70 °C
IP21C
base ABS
cup PC
approx. 150 g
Ø: 94 mm H: 67 mm (incl. base)
10
11
12
Accessories
IP65 base white, 766238
Mounting bracket 767800
13
14
15
16
17
229
Alarm Devices
766412
¬ma-E­
Conventional
Optical alarm signalling device, green
Approval:
1
VdS
As 766410, but green colour.
Technical Data
Operating voltage
Current consumption @ 24 V DC
Frequency of flash
Strength of light
Application temperature
Type of protection
Material
Weight
Dimensions
9 ... 60 V DC
approx. 88 mA
ca. 1 Hz
10 Cd
-25 °C ... 70 °C
IP21C
base ABS
cup PC
approx. 150 g
Ø: 94 mm H: 67 mm (incl. base)
Accessories
IP65 base white, 766238
Mounting bracket 767800
¬ma.H­
766413
Optical alarm signalling device, blue
As 766410, but blue colour and without VdS-approval.
1
Technical Data
Operating voltage
Current consumption @ 24 V DC
Frequency of flash
Strength of light
Application temperature
Type of protection
Material
Weight
Dimensions
9 ... 60 V DC
approx. 88 mA
ca. 1 Hz
7 Cd
-25 °C ... 70 °C
IP21C
base ABS
cup PC
approx. 150 g
Ø: 94 mm H: 67 mm (incl. base)
Accessories
IP65 base white, 766238
Mounting bracket 767800
¬ma/K­
766414
Optical alarm signalling device, transparent
Approval:
1
VdS
As 766410, but transparent colour.
Technical Data
Operating voltage
Current consumption @ 24 V DC
Frequency of flash
Strength of light
Application temperature
Type of protection
Material
Weight
Dimensions
Accessories
IP65 base white, 766238
Mounting bracket 767800
230
www.hls-austria.com
9 ... 60 V DC
approx. 88 mA
ca. 1 Hz
22 Cd
-25 °C ... 70 °C
IP21C
base ABS
cup PC
approx. 150 g
Ø: 94 mm H: 67 mm (incl. base)
Alarm Devices
Conventional
Combined Alarm Devices
1
Conventional
2
766240
¬m_I.­
Combined alarm device 12 V DC, red
1
3
Alarm device as per DIN 33404-3 and EN 457.
For indoor and outdoor installation (with 766237). Alarm sounder and flashing light may ​
be activated separately. Floating tone going by 1 HZ beat between 1200 and 500 HZ (DIN ​
tone).
4
Technical Data
Operating voltage
Alarm current @ 12 V DC
Frequency of flash
Lighting energy
Strength of light
Ambient temperature
Storage temperature
Type of protection
Material
Color
Weight
Dimensions
5
9 ... 15 V DC
approx.100 mA (flash lamp)
ca. 1 Hz
0.7 J
10 cd
-10 °C ... 55 °C
-15 °C ... 60 °C
IP54, IP65 (with 766237 without clips)
ABS plastic (UV-stabilised)
red, similar to RAL 3001
approx. 350 g
Ø: 93 mm H: 92 mm
Ø: 93 mm H: 120 mm (incl. base)
6
7
8
Also available with cable entry at the side, possible with 766237 (see accessories).
9
Accessories
IP65 base red, 766237
Mounting bracket 767800
¬m_I§/21p­
766240.10
10
Combined alarm device 24 V DC, red, Asserta type
1
Asserta sounder beacons is designed to cope with harsh environments requiring protection​
to IP66 and is compliant to EN54-3. 32 different alarm tones can be selected. Alarm ​
sounder and flashing light may be activated separately.
11
Technical Data
Lighting energy
Type of protection
Material
Color
12
2,5 J
IP66
ABS (UV-stabilised)/Polycarbonat
red, similar to RAL 3001
13
¬m_I§/31v­
766240.20
1
Combined alarm device 24 V DC, red
14
The device is compliant to EN54-3. For indoor and outdoor installation (with optional base ​
766237 or 766230). 32 different alarm tones can be selected. Alarm sounder and flashing ​
light may be activated separately.
15
Technical Data
Sound level
Lighting energy
Type of protection
Material
Color
16
98 dB bei 24 V DC
ca. 0,7 J
IP54, IP65 (with 766237 or 766230)
ABS (UV-stabilised)/Polycarbonat
red, similar to RAL 3001
17
231
Alarm Devices
Features
• Shapely, light-weight and compact design
• Prism with all around visible LEDs
Remote Indicators
These indicators are used primarily for signaling alarms of smoke detectors installed above ​
suspended ceilings, between floors or in other inaccessible locations. The indicators have ​
an elegant plastic housing with a clearly visible illuminated field.
Cable length of the Remote Indicators to detector base or voltage supply max. 100 m.
¬o3%:­
781804
Remote indicator for conventional detector series 9000, red
Red prism is illuminated by 4 pulsed LEDs.
1
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current
Frequency of flash
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
6 ... 12 V DC
approx. 0.005 mA
approx. 9 mA
ca. 1.5 Hz
-20 °C ... 70 °C
-35 °C ... 85 °C
IP40
ABS plastic
white, similar to RAL 9010
W: 85 mm H: 82 mm D: 27 mm
Operation only with conventional automatic fire detectors series 9000 and
standard detector base 781590.
- Adapter module (Part No. 781487) required
- max. 3 indicators per detector / max. 3 detectors per indicator
- max. 60 remote indicators per zone (with max. 20 detectors)
- each additional detector, decrease 3 remote indicators
(e.g. 21 detectors -> max. 57 remote indicators
30 detectors -> max. 30 remote indicators).
¬o3/X­
781814
Remote indicator for detector series 9000, 9200 and IQ8Quad
Red prism is - down to the activation - continuously or pulsed illuminated by 3 LEDs.
1
Technical Data
Operating voltage
Current consumption
Alarm display
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
1.8 V DC
ca. 9 mA
3 red LEDs
-20 °C ... 70 °C
-35 °C ... 85 °C
IP40
ABS plastic
white, similar to RAL 9010
W: 85 mm H: 82 mm D: 27 mm
- Standard detector base 781590 and adapter module 781487 required
- Max. 2 detectors per indicator / max. 2 indicator per detector
- Remote indicator lits continuously if activated.
- Standard detector base 781590 or base 801593 required for series 9200 detectors
- Standard base 805590 required for series IQ8Quad
- 1 remote indicator per detector
- Indicator flashes if activated (Pulse frequency approx.1 Hz)
232
www.hls-austria.com
Alarm Devices
¬q39x­
Remote Indicators
1
Remote indicator for addressable detector series 9200 and ​IQ8Quad
801824
Red prism is illuminated by 4 pulsed LEDs for operation on esserbus and esserbus-Plus.
1
2
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Alarm current
Frequency of flash
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
8 ... 42 V DC
approx. 0.007 mA
150 µA
ca. 1.5 Hz
-20 °C ... 70 °C (pulsed)
-35 °C ... 85 °C
IP40
ABS
white, similar to RAL 9010
W: 85 mm H: 82 mm D: 27 mm
3
4
5
Detectors series 9200 / IQ8Quad
• Standard detector base 781590 or base 801593 required for
series 9200 detectors
• Standard base 805590 required for series IQ8Quad
• max. 3 indicator per detector
• max. 103 remote indicators per loop
6
¬q3:­
801825
7
Remote indicator for series 9200 and IQ8Quad, blue
A blue prism is illuminated by 4 pulsed LEDs. Connection via three-wire cable.
1
8
Technical Data
Operating voltage
Quiescent current
Alarm current
Frequency of flash
Connection terminal
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
14 ... 42 V DC
approx. 0.007 mA
approx. 150 μA
ca. 1.5 Hz
0.6 mm to max. 1.5 mm²
-20 °C ... 70 °C
-35 °C ... 85 °C
IP40
ABS plastic
white, similar to RAL 9010
approx. 60 g
W: 85 mm H: 82 mm D: 27 mm
9
10
11
Automatic Fire Detectors series 9200 / IQ8Quad
• Standard detector base 781590 or base 801593 required for series 9200 detectors
• Standard detector base 805590 required for series IQ8Quad detectors
• Max. 3 indicators per detector / max. 2 detectors per indicator
• Max. 103 remote indicators per analog loop
• Do not connect remote indicator to detector base 781593
• Cable length to detector base or voltage supply max. 100m
12
Manual Call Point Series 9200
• Electronic module 804472.10 (for activating a LED remote indicator)
14
13
15
16
17
233
Alarm Devices
Conventional
043150
Remote Indicators
¬%@S-­
Remote indicator, flashing, green
1
In an elegant plastic housing and provided with a clearly visible illuminated field with 4 ​
LED, programmable flashing mode or sustained signal. Connection without screw ​
terminals.
Technical Data
Operating voltage
Alarm current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Color
Dimensions
Accessories
796231
10 ... 24 V DC
approx.10 mA
-10 °C ... 70 °C
-25 °C ... 70 °C
IP40
grey-white, similar to RAL 9002
W: 85 mm H: 85 mm D: 38.5 mm
¬[email protected]­
Label / marker ring for parallel detector indicator
For marking 761803 and 761813 remote indicators as per DIN 14623. Plastic, red, self-​
adhesive
1
Technical Data
Dimensions
100 Pcs.
234
www.hls-austria.com
Ø: 50 mm (outside)
Ø: 10 mm (inside)
1
2
3
4
5
6
7
8
9
10
Door Release System
Automatic Door Systems
236-237
Door Holding Magnets
238-244
11
12
13
14
15
16
17
235
Door Release System
Automatic Door Systems
Automatic door systems for the demarcation of buildings and objects in closed fire ​
compartments for the protection of people and valuables.
Automatic door systems consist of triggering devices and locking devices.
In the event of a fire, the signals created by the automatic triggering device cause the ​
release of the locking device. The actuation by the manual triggering device also leads to a ​
release of the locking device.
The fire doors close and prevent the spreading of fires and of any present smoke to ​
bordering areas of the building. In this way, fire and dangerous fire aerosols are contained ​
and human life as well as valuables are protected.
The locking device consists of e.g. clamping magnet with corresponding anchor plate and/​
or of an automatic door closer. The triggering device consists of the smoke protection ​
switch, fire detector and release key (manual triggering device).
In terms of building authorities, automatic door systems are subject to the Deutschen ​
Institut for Bautechnik in Berlin and need a system authorization (for this, see certificates ​
of approval from the DIBt).
Arrester system for fire barriers
Authorization number: Z-6.5-430
System SAL 9000 FSA Smoke Heat Ventilation Module
Authorization number: Z.-6.5-1457
System 8000 FSA system authorization
Authorization number: Z-6.5-1764
System IQ8FSA 8619 system authorization
Authorization number: Z-6.5-1759
System 8000 FSA Plus system authorization
Authorization number: Z-6.5-1808
For stand-alone operation in connection with FSA transponder (part no. 808619.10) IQ8Quad ​
detectors can be used as arrester system detectors without loop isolators (part no. 803371, ​
803271, 803374).
236
www.hls-austria.com
Door Release System
Automatic Door Systems
1
Connection Example
2
3
RAS 2103 and
Standard Fire Detector
series 9000
RAS 2103 and
Standard Fire Detector
series 9000
4
Power supply
5
Ankerplatte
Release key
6
Anchor plate
Holding magnet
7
8
RAS 2103 Smoke Heat Ventilation Module
as a stand alone solution with two
standard fire detectors
9
10
FSA transponder
11
12
Power supply
IQ8Quad without
integrated isolator
(type 803xxx)
IQ8Quad without
integrated isolator
(type 803xxx)
13
Ankerplatte
Release key
Anchor plate
14
Holding magnet
15
FSA transponder
as a stand alone solution with two
standard fire detectors without isolator
16
17
237
Door Release System
Door Holding Magnets
Holding Magnets 400 N
£"5Z,
960120
1
Door magnet 24 V with release button and flexible anchor
Release button changeable to the left or the right from the base. Cable mounting is ​
possible from behind the unit, as well as through the base, the left or the right side using ​
included grommets.
In combination with angled mounting plates the unit can be installed to either the floor or ​
the wall.
Integrated reverse-polarity protection included (Freewheeling diode and spark-arresting ​
diode).
Tested according to EN1155
Without PG Connection
Technical Data
Operating voltage
Type of protection
Dimensions
¬£"6]­
24 V DC
IP54 (magnet); IP42 (connection)
W: 85 mm H: 110 mm D: 38 mm
Door magnet 24 V with distance pipe, 175 mm
960121
1
Magnet rotary head is fully rotational by the customer and is thus suitable for both floor ​
and wall installations. Customer may shorten distance pipe as necessary.
Integrated reverse-polarity protection included (Freewheeling diode and spark-arresting ​
diode).
Wall clearance: 175 mm
Floor clearance: 150 m
Technical Data
Operating voltage
Type of protection
Dimensions
¬£"7`­
24 V DC
IP54
W: 90 mm H: 80 mm Distance: 150/175 mm
Door magnet 24 V with distance pipe, 325 mm
960122
As 960121, but with wall distance 325 mm and floor distance 300 mm.
1
¬£"8c­
Door magnet 24 V with distance pipe, 475 mm
960123
As 960121, but with wall distance 475 mm and floor distance 450 mm.
1
238
www.hls-austria.com
Door Release System
Door Holding Magnets
¬£"9f­
960124
1
Door magnet 24 V without release button, incl. flexible anchor
1
Version with terminal clamp and installation plate.
Integrated reverse-polarity protection included (Freewheeling diode and spark-arresting ​
diode).
2
Technical Data
Operating voltage
Type of protection
Dimensions
24 V DC
IP54
W: 55 mm H: 55 mm D: 33 mm
3
4
¬£"<o­
960127
Wall and floor angle for door magnet 960120, 150 mm
5
This angle is specially intended for use with 960120 and thus allows floor or wall installa­
tion by means of distance pipe.
1
6
7
¬£"=r­
960128
8
Wall and floor angle for door magnet 960120, 300 mm
As 960127, but with 300 mm pipe length.
9
1
10
11
¬£">u­
960129
1
Floor-mounting base for door magnet 960120
12
This base is especially for 960120. Thus a parallel floor installation is possible. The magnet ​
can either be installed within the side panels (to protect from vandalism) or adjacent to the ​
side panels (standard). Due to the increased gauge of steel used, this base is suitable for ​
heavy use (schools etc).
13
14
15
16
17
239
Door Release System
Door Holding Magnets
Holding Magnets 490 N
¬£"!§­
960100
Wall-mounted door magnet 24 V with release button
The wall-mounted direct current door magnet keeps fire doors open.
1
Technical Data
Operating voltage
Dimensions
24 V DC
W: 85 mm H: 120 mm D: 38 mm
delivery without anchorplate
¬£""!­
960101
Floor-mounted door magnet 24 V with release button
1
Floor-mounted door magnet made out of plastic material with 30% glass fiber content and ​
release button.
Integrated inverse-polarity protection (Freewheeling diode and spark-arresting diode).
Tested according to EN 1155
Technical Data
Operating voltage
Type of protection
Material
Dimensions
¬£"#$­
960102
24 V DC
IP65
PA6, 30% GF
W: 121 mm H: 121 mm D: 86 mm
Floor-mounted door magnet 24 V with release button
1
The plastic rotary head of the door magnet is fully rotational by the costumer and is thus ​
suitable for floor, ceiling and wall installations.
Integrated inverse-polarity protection (Freewheeling diode and spark-arresting diode).
Tested according to EN 1155
Wall clearance: 175 mm
Floor clearance: 150 mm
Technical Data
Operating voltage
Type of protection
Dimensions
¬£"$'­
960103
24 V DC
IP65
W: 70 mm H: 70 mm
Door magnet 24 V without release button
Door magnet for wall-mounting with mounting plate and free litz wire.
Integrated inverse-polarity protection (Freewheeling diode and spark-arresting diode)
1
Tested according to EN 1155
Technical Data
Operating voltage
Type of protection
Dimensions
240
www.hls-austria.com
24 V DC
IP65
Ø: 50 mm W: 55 mm H: 55 mm D: 5 mm
Door Release System
For Ex-Area
767153
Door Holding Magnets
1
¬mhVg­
Ex holding magnet
2
Technical Data
1
Ambient temperature
Ex-category
Explosion protection
Type of protection
EC-type examination certificate
0 °C ... 35 °C
II 2G
EExme II T6
IP54
TÜV01 ATEX 1778 X
3
4
The anchor plate is not supplied as standard.
approx. 40
M 20x1,5
5
approx. 24
Grounding
7
Ø70
117
24
8
110
75
6
8
117
130
approx. 140
approx. 9,5
approx. 106
9
Dimension Drawing
Anchor Plates
960109
10
¬£"*9­
11
Fixed anchor plate for door magnets 960100-960103
1
The door-mounted anchor plate electromagnetically connects the magnetic clamp with the ​
door. The anchor plate is flexible mounted on the mounting plate and thus can balance out ​
any oblique angles (max. 5°). The diameter of the plate is larger that the diameter of the ​
magnet. The holding surface is grounded and protected against corrosion with zinc ​
coating.
12
13
Technical Data
Dimensions
Ø: 55 mm W: 55 mm H: 55 mm D: 18 mm
14
¬£"+<­
960110
15
Flexible anchor plate for door magnets 960100-960103
1
The flexible anchor plate is designed for doors with an angle. The anchor plate is 60° ​
adjustable and fixable in each direction through an articulated joint. The surface is ​
grounded and protected against corrosion.
16
Technical Data
Dimensions
17
Ø: 55 mm W: 55 mm H: 55 mm D: 50 mm
241
Door Release System
Door Holding Magnets
Door Closer
DIBt approved for:
Fire door module RAS 2103 : Z-6.5-1457
Automatic door arrester systems for fire barriers: Z-6.5-430
Fire detection system 8000 FSA: Z-6.5-1764
FSA-transponder: Z-6.5-1759
¬mh8t­
Door closer, hold-open size 2-5
767123
Slide bar with integrated, electromechanical hold-open device. Opening angle (80° to 130°) ​
and adjustable release force.
1
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
24 V DC
1.4 W
silver
approx. 3.5 kg
L: 275 mm W: 53 mm H: 60 mm
¬[email protected]­
Door closer, hold-open size 5-7
767140
As 767123 but with maximum door width of 1600 mm.
1
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
24 V DC
1.4 W
silver
approx. 5.2 kg
L: 285 mm W: 62 mm H: 71 mm
Please not that the manufacturer recommends applying external holding magnets when using ​
door closer sizes 5 –7 instead of applying an integrated hold-open device within the door closer.
¬mh>¨­
Door closer, hold-open and co-ordinator size 2-5
767129
1
Guide rail door closer TS 93 GSR-EMF 2 (BG), EN 2-5, for a two-panel door in contour ​
design with tapered opening angle for easy door opening, with closing sequence control G-​
GSR-EMF 2, with integrated electromechanical hold-open device in both leading and ​
trailing panel, mounting on the hinge, silver.
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
¬mh7q­
24 V DC
1.4 W
silver
approx. 3.5 kg
L: 275 mm W: 53 mm H: 60 mm
Door closer, hold-open and co-ordinator size 2-5
767122
As 767129 but maximum door width of 1600 mm.
1
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
24 V DC
1.4 W
silver
approx. 3.5 kg
L: 275 mm W: 53 mm H: 60 mm
Please not that the manufacturer recommends applying external holding magnets when using ​
door closer sizes 5 –7 instead of applying an integrated hold-open device within the door closer.
242
www.hls-austria.com
Door Release System
¬mh?"­
767130
Door Holding Magnets
1
Door closer, co-ordinator size 5-7
As 767129 but with hold open device integrated in the stationary wing.
1
2
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
24 V DC
1.4 W
silver
approx. 5.2 kg
L: 285 mm W: 62 mm H: 71 mm
3
Please not that the manufacturer recommends applying external holding magnets when using ​
door closer sizes 5 –7 instead of applying an integrated hold-open device within the door closer.
4
¬[email protected]%­
767131
Door closer, co-ordinator size 2-5
1
5
Guide rail door closer TS 93 GSR-EMF 2 (BG), EN 2-5, for a two-panel door in contour ​
design with tapered opening angle for easy door opening, with closing sequence control G-​
GSR-EMF 2, with integrated electromechanical hold-open device in both leading and ​
trailing panel, mounting on the opposite hinge, silver.
6
Technical Data
Operating voltage
Power consumption
Color
Weight
Dimensions
Accessories
767120
7
24 V DC
1.4 W
silver
approx. 3.5 kg
L: 275 mm W: 53 mm H: 60 mm
8
9
¬mh5k­
Mounting plate for door closer with door closer control
10
For mounting the slide bar to doorframes, where direct mounting is not suitable.
1
2x mounting plate
11
12
¬mh6n­
767121
13
Mounting plate for door closer without door closer control
For mounting the slide bar to doorframes, where direct mounting is not suitable.
14
1
15
16
17
243
Door Release System
¬mo!=­
767800
Door Holding Magnets
Mounting bracket for lintel installation
Mounting bracket for all bases/detectors of the IQ8Quad group, series 9x00, RAS 2103 and ​
for IQ8Alarm & all alarm devices.
1
The distance between the mounting holes is 6 cm and the diameter is approx. 5 mm.
Technical Data
Color
white, similar to RAL 9010
Mounting bracket and material
244
www.hls-austria.com
1
2
3
4
5
6
7
8
9
10
Installation & Service
Installation Accessories
245-250
Housings
251-252
11
12
13
14
15
16
17
245
Installation & Service
Surge Protection
Installation Accessories
¬mP)~­
Surge protection for network and low-frequency signal loop
764708
Technical Data
Rated voltage
Rated current
Connection terminal
Ambient temperature
Type of protection
Housing
Dimensions
1
500 V AC
2A
4 mm²
-20 °C ... 60 °C
IP20
PA
W: 17.5 mm H: 90 mm D: 46 mm
A surge protection is required for each control panel. Per loop are two surge protection needed.
Please note that no VdS approval is required for surge protection.
¬mP8D­
LAN-surge protection for snap-on mounting rail
764723
Surge protection for essernet 500 kBd.
1
Technical Data
Rated voltage
Rated current
Ambient temperature
Type of protection
Dimensions
12 V DC
0.45 A
-40 °C ... 85 °C
IP20
W: 17.5 mm H: 90 mm D: 66 mm
Two LAN surge protection modules are required for each control panel. Per loop is one surge ​
protection needed.
Please note that no VdS approval is required for surge protection.
Features
• Two twin wires can be connected with one surge ​
protection module
1 x basis module surge protection PT2x2-BE
1 x protection plug PT2x2-HF-12DC-ST
4 x shield fast connection SSA 5-10
Surge protection device for Line heat detector LWM-1 (761290)
970300
1
The SD Series is a range of surge protection devices combining unparalleled packing dens­
ities, application versatility, proven reliable hybrid circuitry, simple installation and optional ​
‘loop disconnect’ (a feature which allows commissioning and maintenance to be carried ​
out without removal of the surge protection device). The exceptionally high packing dens­
ities are the consequence of an ultra slim ‘footprints’ which can thus double up as feedback​
terminals. One simple manual operation clamps modules securely onto DIN rail, which ​
automatically provides the essential high-integrity earth connection.
To be used in conjunction with 970301 Ex-I terminal box.
Features
• Range of ATEX Certified, intrinsically safe surge ​
•
•
•
•
•
•
246
protectors
Ultra-slim space saving design; easy installation
Multistage hybrid protection circuitry - 20 kA ​
maximum surge current
Range of voltage ratings - to suit all process I/O ​
applications
Low resistance version
10 year product warranty
Standard: EN 50014:1997, EN 50020:2002, EN ​
50284:1999
www.hls-austria.com
Technical Data
Ambient temperature
Storage temperature
Type of protection
Weight
-40 °C ... 80 °C
-10 °C ... 80 °C
Full hybrid line to line, Each line to screen/ground
approx. 70 g
Installation & Service
Installation Accessories
Protection Against Lightning
1
764707
2
¬mP(­
IP65 TG40 protective housing for 764708 and 764723
Aluminium housing with pre-mounted rail. Four cable screw connections and one earthing ​
screw on the outside of the housing. Cover fixing with four rustproof, captive screws.
3
1
Technical Data
Type of protection
Dimensions
IP65
W: 160 mm H: 134 mm D: 120 mm
4
5
¬mP+¦­
764710
IP65 TG60 protective housing for 764708 and 764723
6
As 764707 but 9 DU.
Technical Data
1
Type of protection
Dimensions
7
IP65
W: 200 mm H: 200 mm D: 120 mm
8
9
Junction Box Module
¬G5I¤­
382040
10
8-fuse card
Approval:
1
11
VdS
Fuse card with 8 x 0.5 A fuses for individual power supply protection of each area, zone ​
and component. It can be used with all Esser mains units, fire and intrusion detection ​
panels.
12
Technical Data
Contact load
Connection terminal
Ambient temperature
Storage temperature
Air humidity
Weight
Dimensions
30 V DC / 1 A
0,6 mm to max. 1,5 mm²
-5 °C ... 50 °C
-25 °C ... 75 °C
≤ 95 % (without condensation)
approx. 85 g
W: 65 mm H: 72 mm D: 15 mm
13
14
Possible installation in housings: 120240, 120242, 120244, 788600, 788601, 788650, ​
788650.10, 788651, 788651.10, 788603 and 788603.10
15
16
17
247
Installation & Service
Interface Converters
764852
Installation Accessories
¬mQU6­
Converter RS 232 / RS 485
For converting an interface signal from RS 232 to RS 485 and vice versa. Suitable for C-rail ​
mounting.
1
Technical Data
Operating voltage
Current consumption @ 12 V DC
Housing
Weight
Dimensions
24 ... 12 V DC /AC
approx. 85 mA
plastic small-design housing
approx. 500 g (incl. power supply)
W: 105 mm H: 75 mm D: 22 mm
1 x interface RS232/RS485 Industry,
1 x power supply unit
Features
• RS485 2 and 4 wire compatible
• RS485 automatic mode
• No re-configuration of transmission parameters ​
required
• Min. 1 kV electrical isolation
• Top hat rail housing according to DIN EN 50022-​
35
• Suitable as "non-intelligent" converter for
• RS485 field buses (e.g. profibus, CS31, etc.) <> ​
¬mQX?­
RS232
764855
Converter RS 232 / TTY
1
When using this converter as, for example, a current-loop line driver (amplifier), a printer ​
with a serial or parallel interface or a fire alarm panel or an intruder alarm panel can be ​
operated in a distance of up to 1000 m from the management system.
Technical Data
Dimensions
W: 105 mm H: 75 mm D: 22 mm
Please note that two RS 232 / TTY converters are required for each connection.
Features
• RS-232 data rate up to 128 kbps
• TX, RX Active/Passive selectable
• 20 or 60 mA selectable
• DTE/DCE device setting selectable
• TD/RD LED indicators
• Power LED indicator
Accessories
050510
1 x converter RS232
1 x serial connecting plug
1 x parallel connection plug
1 x power supply unit
¬&&+P­
Network interference suppression filter type 2VK3
The mains interference suppression filter is intended for later installation in all mains-oper­
ated devices in which problems due to HF power failure arise.
1
Technical Data
Rated voltage
Rated current
Rated frequency
Ambient temperature
Dimensions
115 V - 250 V AC
2A
50 ... 60 Hz
-10 °C ... 40 °C
W: 52.6 mm H: 46 mm D: 23.1 mm (without flange)
Mains interference suppression filter and terminal block
248
www.hls-austria.com
Installation & Service
Installation Accessories
¬(%Sa­
1
Additional relay 12 V DC
070450
Small PCB with relay, connection terminals, two changeover contacts.
2
1
3
4
¬ml+U­
Control relay for top-hat rail mounting
767510
5
Technical Data
1
Operating voltage
Contact load relay
Ambient temperature
12 V DC
250 V AC / DC, 6 A
-20 °C ... 55 °C
6
7
¬ow#U­
8
Top-hat rail
788602
9
Technical Data
1
Dimensions
L: 400 mm
10
Mounting kit
¬owU¦­
Mounting rail for FACP 8000 C/M and IQ8Control C/M housing
788652
1
11
The top hat rail installation kit can be retrofitted into the IQ8Control unit housing. The hat ​
rail is fitted to the mounting board via two screws. A maximum of two 788603 module ​
housings (option) can be mounted to the control unit housing.
12
Technical Data
Dimensions
L: 35 mm W: 175 mm (standard-snap-on mounting ​
rail)
13
Mounting rail and accessories
14
15
16
Application example
17
249
Installation & Service
Installation Accessories
¬ow$§/213­
788603.10
Module housing for snap-on mounting rail
For snap-on mounting rail of esserbus transponders resp. with 82 x 72 mm PCB size. ​
Angled cable entry.
1
Technical Data
Material
Color
plastic
green
1x UM-profile and 2x side panels
¬ow&^­
Application example
788605
Mounting kit
Mounting kit required for mounting esserbus transponders in extension housings.
1
4 x spacer bolts and 2 x fixing screws
¬gJPz­
704147
IP67 cable gland M12 with nut
Polyamid cable gland to increase the protection level.
1
Technical Data
Material
Color
Polyamid
blue
¬gJQ­
704148
IP67 cable gland M16 with nut
Polyamid cable gland to increase the protection level.
1
Technical Data
Material
Color
250
www.hls-austria.com
Polyamid
blue
Installation & Service
Housings
1
Housings
¬ow!O­
2
Housing surface mount, grey
788600
Small distributor housing for housing esserbus transponders and the 10-pin distributor ​
terminal 382030.
3
1
The following esserbus transponder types can be used:
- 2 esserbus transponders each of dimensions (W x H x D) 82 x 72 x 20 mm
- 1 esserbus transponder of dimensions (W x H x D) 150 x 820 x 20 mm
4
Technical Data
Type of protection
Material
Color
Dimensions
¬ow"R­
IP40
ABS
grey, similar to RAL 7035
W: 189 mm H: 131 mm D: 47 mm
5
6
Housing flush mount, grey
788601
Same as 788600, but as flush-mounted version.
1
7
Technical Data
Type of protection
Material
Color
Dimensions
IP40
ABS
grey, similar to RAL 7035
W: 189 mm H: 131 mm D: 47 mm
W: 207 mm H: 149 mm (cover)
8
9
¬owS§/21Y­
10
Housing surface mount, white
788650.10
Same as 788600, but white.
1
11
Technical Data
Type of protection
Material
Color
Dimensions
IP40
ABS
white, similar to RAL 9003
W: 189 mm H: 131 mm D: 47 mm
12
13
¬owT§/21\­
Housing flush mount, white
788651.10
14
Same as 788601, but white.
1
Technical Data
Type of protection
Material
Color
Dimensions
15
IP40
ABS
white, similar to RAL 9003
W: 189 mm H: 131 mm D: 47 mm
W: 207 mm H: 149 mm (cover)
16
17
251
Installation & Service
Housings
Fire Protection Housing F30
¬oq?6­
788030
Fire protection housing F30 RO
The fire protection casing allows for the installation of a fire alarm control panel from the ​
series IQ8Control in accordance with MLAR and LAR requirements of the different federal ​
states. The duration of the functional integrity of the electrical circuit systems for security ​
technology systems must account for at least 30 minutes for:
1
- fire detection systems including the corresponding transmission systems
- systems that alarm and issue directives to visitors and employees, in as much as these ​
systems must be effective in cases of fire.
Features
• Fire resistance F30, certified in accordance with ​
DIN 4102 part 2
• Functional integrity of over 30 minutes, in accord­
ance with DIN 4102 part 12
• Fire load insulation of over 30 minutes in accord­
ance with DIN 4102 part 11
• Protection type conforming IP41
• Smoke-proof
• Surface mounted
• Integrated mounting rail system for FACP IQ8Con­
trol
• Locking via pivoting lever without locking cylinder
• Cable chute for bundle inlet above
• Push rod fastener with 2 point interlock
• Mounting straps
• Building material surface coating A2 non-​
combustible in accordance with DIN 4102 part 1
• Colour light grey (other colours available for an ​
additional charge)
• Ventilation system includes active ventilation and ​
IQ8Control C or M fire detection systems required by building laws that can be operated by ​
an esserbus-Plus warning device can be operated in this fire protection housing in accord­
ance with DIN4102 part 2 with approval according to DIBT. The housing is a component of ​
the VdS device approval and, as an approved distributor, supplies power to the warning ​
device for over 30 minutes. Other housings do not fulfill the approval requirements and ​
may not be used. In addition, the electro-housing fulfills fire load insulation requirements ​
in accordance with §40 paragraph 2 of the MBO, as an IQ8Control FACP can be used for ​
necessary emergency and evacuation exits as well. Should the interior of the housing ​
ignite, the air intake openings will automatically close and a cold desmoking will be ​
prevented. At most, an IQ8Control C or IQ8Control M FACP including transmission device ​
may be built into the electro-housing. As operation level 1 cannot be reached in accordance​
with EN54-2, an FAT can be necessary for initial information after consultation with the ​
responsible fire department. It is to be assured that the fire protection housing door always ​
remains closed during normal operation.
Technical Data
Type of protection
Color
IP41
light grey (other colors available for an additional ​
charge)
approx. 164 kg
Weight
Mounting material, sealing kit and chute material incl. base 805590, without detector
thermal shutter release
• Weight approx. 164 kg
Front view
1324
mm
Side view
Top view
340
mm
1200
mm
500 mm
624 mm
¬[email protected]­
Dimensions illustration
788031
Fire protection housing F30 LO
Same as 788030, but door hinge left.
252
www.hls-austria.com
434 mm
Planning Guide for Loop Installation
1
This is a planning guide for loop-powered alarm devices.
The alarm current of each alarm device is defined as load factor. When added up, the total load factor defines the
loop length and the maximum number of alarm devices.
2
The maximum load factor of all alarm devices may not exceed 96. Altogether up to 127 bus devices per loop can still
be connected. The "Load factor" download file for easier load factor calculation is available within our customer section at http://www.hls-austria.com.
3
Load factors:
Part No. 802382 802383 802384 802385 802386 807205 807206 807212 807213 807214 807224 807322 807332 807372 806282 Type of alarm signalling device O/So optical smoke detector IQ8Quad O2T/F multisensor IQ8Quad with integr. flash O2T/So multisensor IQ8Quad with integr. sounder O2T/FSp multisensor IQ8Quad with integr. flash, sounder and speech
O2T/SpSo multisensor IQ8Quad with integr. sounder and speech Sounder IQ8Alarm, Housing: white Sounder IQ8Alarm, Housing: red Optical alert device IQ8Alarm, Housing: white, lens: amber Optical alert device IQ8Alarm, Housing: white, lens: white, blue, green Optical alert device IQ8Alarm, Housing: red, lens: red Combi sounder IQ8Alarm, Housing: red, Lens: red Speech alarm unit IQ8Alarm, Housing: white Speech alarm unit IQ8Alarm, Housing: red Combi speech alarm unit IQ8Alarm, Housing: red, lens: red Addressable base sounder esserbus-PLus Load factor
2
2
2
3
3
3
3
3
3
3
3
3
3
3
2
4
5
6
7
8
Table 1.1: Maximum loop length depending on the total load factor
Maximum powered loop length
up to 700 m
up to 800 m
up to 900 m
up to 1000 m
up to 1100 m
up to 1300 m
up to 1500 m
up to 1700 m
up to 2000 m
up to 2500 m
up to 3000 m up to 3500 m
9
total load factor
91 ... 96
85 ... 90
79 ... 84
73 ... 78
67 ... 72
61 ... 66
55 ... 60
49 ... 54
43 ... 48
37 ... 42
31 ... 36
1 ... 30
10
11
12
13
14
15
16
17
253
Load Factor Calculation
Example 1:
How many IQ8Alarm alarm signalling devices with load factor 3.0 can be connected to one analog loop?
96 (max. total load factor): 3.0 (load factor) = up to 32 IQ8Alarm devices can be connected
to each loop depending on the loop length (up to 700m)
Example 2:
Various types of alarm signalling devices are connected to one loop:
Load factor
4 x 807205 alarm devices with load factor 3,0 = 4 x 3,0 = 12
+
27 x O2T/So multisensor IQ8Quad (802384) with load factor 2,0 = 27 x 2,0 = 54
total load factor = 66
As shown in table 1.1, the maximum loop length for a total load factor of 66 is 1300m (at a wire gauge 0,8mm).
Example 3:
For alarm signalling with sounder, 25 x 802384 IQ8Quad O²T/So
detectors are installed - each in one office. What is the maximum loop length?
Load factor for one 802384 IQ8Quad O²T/So detector = 2 (load factor)
25 IQ8Quad O²T/So x 2 (load factor) = 50 (total load factor)
As shown in table 1.1, the maximum loop length is 1700m (at a wire gauge 0,8mm).
254
www.hls-austria.com
OA-No.
Order Form WINMAGplus / WINMAG Lite
Telefax master
Honeywell Life Safety Austria GmbH
Lemböckgasse 49
A-1230 Vienna
1
Fax +43 (0)1 600 60 30 - 900
2
3
1. Licence data
Please fill in the form for data collection
End user data (data must be entered: min. 8, max. 45 characters) 4
Name:
5
Street:
Town/City/Country:
Object:
6
Installer data: (data must be entered: min. 3, max. 45 characters)
7
Name:
Street:
8
Town/City/Country:
Contact person:
9
Entry of data optional: (max. 12 characters)
Phone:
10
Fax:
Email: (max. 45 characters)
(Please note that with completing this field, you agree that the licensing file will be sent via E-Mail.)
11
2.Ordering
One of the following must be selected.
2.1 WINMAG control centre software basic package (select options on page 2)
1 x 013610 WINMAGplus basic package
1 x 013635 WINMAG Lite
12
13
2.2 WINMAGplus retrofitting of options (select options on page 2)
1 x 013609 retrofitting of options from V6.0
14
2.3 WINMAG Upgrade - Please enter the license/update number.
1 x 013620 Upgrade GEMAG – Installation (MS-DOS) to WINMAGplus
or
1 x 013632 Upgrade WINMAG to WINMAGplus
for USB interface
for Parallel interface 16
Update No.:
17
1 x 013636 WINMAG Lite Upgrade to WINMAGplus basic version
15
Update No:
1 x 013645 WINMAG dongle CrossDate from parallel to USB port
Update No:
255
Order from WINMAGplus - Part 2
Telefax master
3. Options a basic license is required for each connection)
Multi-station / distributed PCs
Computer
Computer
Computer Part No.
Designation
013630
Basic licence (parallel Port1) )
013631
Basic licence (USB Port1) )
013633
Basic licence, including dongle for USB port
(3 month runtime version)
013590
Universal Gateway for Workstations (USB Port1) )
013601
Licence intrusion detection technology
013626
Licence fire detection technology
013603
Licence access control technology
013604
Licence CCTV technology
013605
Licence escape door control
013606
Licence Connection Server
013607
Connection server developers kit
013608
013609
Licence - WINMAGplus remote data transmission
WINMAGplus control centre software post installation upgrade
013611
Licence OPC-Server
013612
Licence OPC-Client
013613
Licence Notification
013614
Licence OEM
013618
Licence 500 OPC/BacNet Datapoints
013619
WINMAG license HeiTel video
013620
WINMAG license MaxPRO VMS67890
013623
Licence interfacing DEZ 9000
013624
Option redundance
013625
Licence - WINMAGplus client
013629
013634
WINMAG license Geutebrueck Video
One-time basic licence for USB port (extension of 3 month)
for Part No. 013633
013640.10
WINMAGplus control centre software - remote-access kit
013643
Option Connecting Galaxy IAS
013650
Licence Escalation
013651
Licence DTMF
013652
Licence Customied rights
013653
Licence Multi Screen
013655
Licence AutoCAD
013660
Licence WEBX
Updatenumber3) (for Winmag Version > Version 6)
One of the listed Part Numbers has to be chosen
Number of PC’s, to which network data is given
3)
The update number is given by the info dialog window, or up from version 8, from the textfile lizenzinfo.txt
1)
2)
Date/Signature
256
www.hls-austria.com
Order Information for Alarm Signaling Devices IQ8Quad and IQ8Alarm
1
The IQ8Quad O²T/FSp Multi-sensor Detector (Part No. 802385 and 802386) and the IQ8Alarm "Combi" Speech Alarm (Part
No. 807372 and 807332) can also be ordered with a different combination of languages.
The following five languages are the programmed standard for these speech alarms. The respective languages are assigned with the five standard speech announcements for the IQ8Quad (Part No. 802385 and 802386) and the IQ8Alarm
(Part No. 807372 and 807332).
Country code Language
acc. to ISO
code acc.
3166 -Alpha-2 to ISO
Evacuation 1
639-1
de
Deutschland
(DE)
en
England
(GB)
fr
Frankreich
(FR)
es
Spanien
(ES)
it
Italien
(IT)
2
3
Evacuation 2
Alarm
Test-message
All-Clear
Dies ist ein
Feueralarm. Bitte
verlassen Sie das
Gebäude umgehend über die
nächsten Fluchtwege. Die Feuerwehr ist alarmiert.
Achtung, Achtung!
Dies ist eine Gefahrenmeldung. Bitte
verlassen Sie das
Gebäude über die
nächsten
Ausgänge.
Achtung, im Gebäude ist eine
Gefahrensituation
gemeldet worden.
Bitte bleiben Sie
ruhig, und warten
Sie auf weitere
Anweisungen.
Dies ist eine
Testdurchsage.
This is a fire alarm.
Please leave the
building immediately by the nearest
available exit.
Attention please.
This is an emergency. Please leave the
building by the
nearest available exit.
An incident has
been reported in the
building. Please
await further
instructions.
This is a test
message.
No action is
required.
The emergency is
now cancelled. We
apologize for any
inconvenience.
Ceci est une alarme
incendie,veuillez
évacuer
immédiatement les
locaux par la sortie
la plus proche.
Votre attention s'il
vous plaît, ceci est
une alarme. Veuillez
évacuer les locaux
par la sortie la plus
proche.
Un incident est
signalé dans le
batiment. Merci de
garder votre calme
et attendez les
prochaines
instructions.
Ceci est un test.
L'alarme est à
présent annulée.
Veuillez nous excuser
pour le désagrément.
Esto es una alarma
de incendio.
Abandonen
por favor el edificio
inmediatamente
por la salida de
evacuación
más cercana.
Atención. Esto es
una emergencia.
Por favor
abandonen el
edificio por la
salida de
evacuación
más cercana.
Atención, se ha
reportado un
incidente
en el edificio.
Aguarden por favor
otras instrucciones.
Esto es un
mensaje
de prueba.
No se requiere
ninguna acción.
La emergencia ha
sido cancelada.
Pedimos disculpas
por las molestias
causadas.
Attenzione.
Allarme incendio.
Abbandonare
l'edificio tramite
l'uscita di
emergenza più
vicina.
Attenzione.
Allarme in corso.
Vi preghiamo di
recarvi presso
l'uscita di
emergenza più
vicina.
Attenzione.
E' stato rilevato un
allarme.Ulteriori
disposizioni vi
verranno
comunicate
appena possibile.
Attenzione.
E' in corso una
prova di allarme.
Non è richiesta
alcuna azione.
Attenzione. Cessato
allarme.La situazione
di normalità è stata
ripristinata.
Die Gefahrensituation
ist jetzt behoben. Wir
entschuldigen uns
für jegliche
Unannehmlichkeiten.
4
5
6
7
8
9
10
11
12
13
14
15
16
17
257
Order Information for Individual Combination of Languages
Up to five languages can be provided per alarm signaling device.
Other combinations of languages can be ordered in accordance with the following order form.
The delivery time is four weeks. Please note that returns or cancellations are not possible.
Order numbers for individual combination of languages:
IQ8Quad O²T/FSp Multi-sensor Detector IQ8Alarm "Combi" Speech Alarm 802385.SV98 + 802386.SV98
807372.SV98 + 807332.SV98
Description:
Individual combination of languages
802385.SV98 / 807372.SV98
802385.SV98
NL_nl
GB_en
DE_de
TR_tr
RU_ru
_____
For example:
Phrase 1 Phrase 6 Phrase 11 Phrase 16 Phrase 21 -
5
10
15
20
25
NL_nl
GB_en
DE_de
TR_tr
RU_ru
The message type per language is always the
same unless indicated otherwise in the chart:
"Additional languages for individual combination”:
1 Evacuation 1
2 Evacuation 2
3 Alarm
4 Test-Message
5 All Clear signal
Order Information: Customized Combination
In case you should need individual texts differing from the standard speech messages, additional signal tones or other languages which are not listed in the order form, please contact the technical sales consultant in your area.
Order numbers for individual programming of speech announcements / signal tones:
IQ8Quad O²T/FSp Multi-sensor Detector IQ8Alarm "Combi" Speech Alarm 802385.SV99 + 802386.SV99
807372.SV99 + 807332.SV99
Description:
Individual combination of customer-specific
special texts / special tones 802385.SV99 / 807372.SV99
802385.SV99
NL_nl
GB_en
DE_de
TR_tr
RU_ru
Extra
For example:
Phrase 1 Phrase 6 Phrase 11 Phrase 16 Phrase 21 Phrase 26 -
5
10
15
20
25
31
NL_nl
GB_en
DE_de
TR_tr
RU_ru
Extra
(customer specific special texts / special tones)
Information about delivery time and price of recording special texts and special tones available upon request. Please note
that the maximum recording time is 169 seconds. Also please note that returns or cancellations are not possible.
The programming of speech and/or tone data is carried out at the factory according to your specifications. The programming of the customer data is carried out via the tools 8000programming software. Please take a look at the relevant instructions in the online help.
258
www.hls-austria.com
Additional Languages for Individual Combination
1
Country code
acc. to ISO
3166 -Alpha-2
CN
Language
code acc.
to ISO
639-1
Evacuation 1
Evacuation 2
Alarm
Test-message
All-Clear
Et varsel om brand bliver
undersøgt. Afvent nærmere
besked.
Dette er en testmelding.
Normal tilstand er
genoprettet. Faren er
overstået.
2
zh
China
Mandarin
DK
Brandalarmen er aktiveret.
Forlad bygningen. Anvend
de opmærkede flugtveje.
Elevatorerne må ikke
benyttes.
fi
Huomio, kiinteistössä on havaittu
automaattinen paloilmoitus. Poistu
rakennuksesta käyttäen ohjattuja
reittejä. Hissien käyttö on kielletty.
Huomio, turvallisuussyistä
Huomio, paloilmoitin on ilmoittanut
kiinteistöstä on poistuttava
mahdollisesta vaaratilanteesta.
välittömästi. Käytä ohjattuja reittejä. Tutkimme asiaa ja annamme
pian lisätietoja.
Paloilmoitinjärjestelmää
testataan.
Palohälytys on ohi. Tilanne
on palautunut normaaliksi.
el
Αυτό είναι ένα μήνυμα συναγερμού
για πυρκαγιά. Παρακαλώ
εγκαταλείψτε το κτίριο αμέσωσ
από τισ εξόδουσ κινδύνου. Η
πυροσβεστική έχει ειδοποιηθεί.
Προσοχή, προσοχή! Αυτό είναι
ένα μήνυμα για κατάσταση
κινδύνου. Παρακαλώ εγκαταλείψτε
το κτίριο από τισ επόμενεσ εξόδουσ.
Προσοχή στο κτίριο υπάρχει
κατάσταση κινδύνου. Παρακαλώ
παραμείνετε ψύχραιμοι και περιμένετε
επόμενεσ οδηγίεσ.
Αυτή είναι μια δοκιμαστική
ανακοίνωση.
Η κατάσταση κινδύνου έχει
αρθεί. Ζητούμε συγγνώμη
για τυχόν δυσάρεστεσ
καταστάσεισ που προκλήθηκαν.
nl
Attentie,
er is een brandalarm.
Verlaat het gebouw via de
dichtstbijzijnde uitgang.
Attentie,
er is een calamiteit.
Verlaat het gebouw via de
dichtstbijzijnde uitgang.
Attentie,
er volgt een blussing,
verlaat de ruimte.
Dit is een testalarm,
dit is een testalarm.
Einde alarmmelding,
einde alarmmelding.
ca
Aixó es una alarma d´incendi.
Siusplau abandonin l´edifici
inmediatament per la sortida
d´evacuació més propera.
Atenció. Aixó es una emergencia.
Siusplau abandonin l´edifici per la
sortida d´evacuació més propera.
Atenció. S´ha notificat un
incident a l´edifici. Siusplau,
esperin altres instruccions.
Aixó es un missatge
de prova. No es
requereix cap acció.
L´alarma ha estat
cancel.lada. Preguem
disculpin les molesties.
hu
Ovo je pozarni alarm. Molimo
odmah napustite objekt koristeci
najblizi izlaz za nuzdu. Vatrogasna
postaja je alarmirana.
Pozor! Pozor! Ovo je priopcenje o
neposrednoj opasnosti. Molimo
odmah napustite objekt koristeci
najblizi izlaz za nuzdu.
Pozor! U objektu je prijavljena
opasnost. Molimo ostanite
mirni i pricekajte daljnje
upute.
Ovo je probno
priopcenje. Nikakve
mjere nisu neophodne.
Opasnost je prestala.
Ispricavamo se radi
eventualnih neugodnosti.
no
Brannalarmen er utløst. Forlat
bygget. Bruk de oppmerkede
rømningsveier. Heisene må ikke
brukes.
Et automatisk varsel om brann blir
undersøkt. Avvent nærmere beskjed.
Dette er en testmelding.
Normal tilstand er
gjenopprettet. Faren over.
pl
Uwaga! Wystąpił alarm pożarowy.
Proszę natychmiast opuścić
budynek najbliższym dostępnym
wyjściem ewakuacyjnym.
Proszę o uwagę! To jest komunikat
alarmowy. Proszę opuścić budynek
najbliższym dostępnym wyjściem
ewakuacyjnym.
Uwaga. W budynku wystąpiło
zdarzenie alarmowe. Proszę spokojnie
oczekiwać dalszych instrukcji.
To jest komunikat testowy.
Nie są wymagane żadne
działania.
Stan alarmu został odwołany.
Przepraszamy za wszelkie
niedogodności i utrudnienia.
pt
Isto é um alarme de incêndio.
Por favor abandonem o edifício
imediatamente pela saída de
evacuação mais próxima.
Atenção. Isto é uma emergência.
Por favor abandonem o edifício
pela saída de emergência mais
próxima.
Atenção, ocorreu um incidente no
edifício. Por favor aguardem mais
instruções.
Atenção, isto é apenas um
ensaio
O alarme foi cancelado. Queiram
desculpar o inconveniente.
ro
Atenţiune, atenţiune! S-a declanşat
o alarmă de incendiu. Vă rugăm
părăsiţi imediat clădirea pe cea mai
apropiată cale de evacuare.
Alarma a fost transmisă la pompieri.
Atenţiune! Acesta este un mesaj de Atenţiune. În clădire a fost semnalat
urgenţă. Vă rugăm părăsiţi clădirea un incident. Vă rugăm să vă păstraţi
pe cea mai apropiată cale de ieşire. calmul şi să aşteptaţi noi instrucţiuni.
Situaţia de urgenţă a luat
sfârşit. Ne cerem scuze
pentru eventualele
inconveniente.
Acesta este un mesaj de test.
ru
Внимание. Пожарная тревога.
Пожалуйста покиньте помещение
через ближайшие аварийные
выходы.
Внимание. Это предупреждение о
пожарной опасности. Пожалуйста
покиньте помещение через
ближайшие выходы.
Отмена пожарной тревоги.
Ситуация нормализовалась.
Извините за причинённые
неудобства.
Тестовое сообщение. Идет
проверка системы
пожарной сигнализации.
sv
Brandlarmet är utlöst. Utrymm
byggnaden. Använd de uppmärkta
utrymningsvägarna. Hissar får inte
användas.
Tekniskt prov av brandlarmet.
Normal tilstånd är återupprättat.
Faran är över.
sk
Toto je požiarny poplach. Opusťte
prosim okamžite budovu najbližším
núdzovým východom!
Pozor, hrozí nebezpečenstvo.
Opusťte prosim budovu
najbližším núdzovým
východom!
V budove bola vyhlásená
pohotovosť. Počkajte prosim
na ďalšie pokyny.
Toto je testovacie
hlásenie. Nie je
potrebne naň
reagovať.
Pohotovosť bola
odvolaná.Ospravedlňujeme
sa za pripadne ťažkosti.
cs
Toto je požární poplach.
Prosím, opusťte okamžitě
budovu nejbližším únikovým
východem.
Pozor, hrozí nebezpečí.
Prosím, opusťte budovu
nejbližším únikovým
východem.
V budově byla vyhlášena
pohotovost. Prosím, vyčkejte
dalších instrukcí.
Toto je testovací
hlášení. Není třeba na
něj reagovat.
Pohotovost je nyní
odvolána. Omlouváme se
za případné obtíže.
tr
Dikkat ! Dikkat ! Acil
Yangın Uyarısı. Lütfen
dirhal binayı boşaltın.
Acil bir durum var. Lütfen
binayı en yakın çıkış
noktasından terkedin.
Bu bir yangın uyarısıdır. Bu
bir yangın uyarısıdır.
Talimatlar için beklemede
kalın. Talimatlar için beklemede
kalın.
Yangın uyarısı test
edilmektedir. Bir şey
yapmanız gerekmiyor.
Bir şey yapmanız
gerekmiyor.
Tehlike geçmiştir. Tehlike
geçmiştir. Bir şey yapmanız
gerekmiyor.
hu
Tűzriadó! Kérem, azonnal
hagyják el az épületet az
Önökhöz legközelebb eső
kijáraton!
Figyelem! Vészhelyzet!
Kérem, azonnal hagyják el
az épületet az Önökhöz
legközelebb eső kijáraton!
Az épületben váratlan esemény
történt. További utasításig
kérem várjanak!
Ez egy tesztüzenet.
Vészhelyzet törölve. Az
esetleges
kellemetlenségekért
elnézésüket kérjük.
Denmark
FI
Finland
GR
Greece
NL
Netherlands
ES
Catalonia
HU
Croatia
NO
Norway
PL
Poland
PT
Portugal
RO
Romania
RU
Russia
SE
Sweden
SK
Slovakia
CZ
Czech
Republic
TR
3
da
Hungary
5
6
7
8
9
10
11
12
13
Внимание. Поступило
предупреждение о пожарной
опасности. Пожалуйста сохраняйте
спокойствие и ждите дальнейшей
информации.
Ett automatiskt varsel om brand blir
undersökt. Invänta närmare besked.
14
15
Turkey
HU
4
16
17
259
Order Form for Individual Combination of Languages
Telefax master
Fax +43 (0)1 600 60 30 - 900
Honeywell Life Safety Austria GmbH
Lemböckgasse 49
A-1230 Vienna
1. Customer Data
Please fill out the following form for the registration of these data.
Company: Customer ID:
Street:
Zip Code/City:
Contact Person:
E-mail:
Telephone: Fax: Object:
Order Number / Order Text:
Novar Order Number:
2. Type / Amount
802385.SV98
807372.SV98
Amount 802386.SV98 Amount Amount 807332.S98
Country Code according to Speech ISO 3166
Code according to
ISO 639-1
CN
CZ
DE
DK
ES
ES
FI
FR
GB
GR
HU
HR
IT
NL
NO
PL
PT
RO
RU
SE
SK
TR
zh
cs
de
da
ca
es
fi
fr
en
el
h
hr
it
nl
no
pl
pt
ro
ru
sv
sk
tr
3. Languages
Languages max. 5 languages Chinese Mandarin
Czech German Danish Catalan
Spanish Finnish
French
English Greek
Hungarian Croatian Italian
Dutch Norwegian
Polish Portuguese Romanian Russian
Swedish Slovak
Turkish
Repeat Orders or Additions
For repeat orders or additions please give the Order No. or
the serial number of the detector with special languages.
Date/Signature
260
www.hls-austria.com
Order number:
Serial number:
Amount
OA No.
Order Form Multi Protocol Gateway
Telefax master
Honeywell Life Safety Austria GmbH
Lemböckgasse 49
1230 Vienna, Austria
1
Fax +43 (0)1 600 60 30-900
2
1. Project Data
3
Please fill in the form for data collection
End user data (entries compulsory: min. 8, max. 45 characters)
4
Name:
Street:
5
Town/City/Country:
Object:
6
Installer data: (entries compulsory: min. 3, max. 45 characters)
Customer number:
Name:
7
Street:
Town/City/Country:
8
Contact person:
Entry of data optional (max. 12 characters):
9
Phone:
Fax:
E mail (max. 45 characters):
2.Gateways
(A part number always consists of hardware, data points and driver!)
Multi Protocol Gateway DP 500
Part. No.
Protocol Option
785000
Esser -> BACnet Client 785001
Esser -> BACnet Server 785002
Esser -> EIB/Instabus 785003
Esser -> LONTalk 785004
Esser -> Modbus IP 785006
Esser -> OPC Server 785007
Esser -> Customized driver with hardware
Driver: 785008
Esser -> Customized driver
Driver:
Multi Protocol Gateway DP 1500
Part. No.
Protocol Option
785009
785010
785011
785012
785013
785015
785016
785017
10
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Driver:
Esser ->
Driver:
11
Quantity
12
13
14
15
Quantity
16
BACnet Client BACnet Server EIB/Instabus LONTalk Modbus IP OPC Server Customized driver with hardware
17
Customized driver
261
OA No.
Multi Protocol Gateway DP 7500
Telefax master
Part. No.
Protocol Option
785018
Esser -> BACnet Client 785019
Esser -> BACnet Server 785020
Esser -> EIB/Instabus 785021
Esser -> LONTalk 785022
Esser -> Modbus IP 785024
Esser -> OPC Server 785025
Esser -> Customized driver with hardware
Driver:
785026
Esser -> Customized driver
Driver:
Multi Protocol Gateway DP 35000
Part. No.
Protocol Option
785027
785028
785029
785030
785031
785033
785034
785035
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Esser ->
Driver:
Esser ->
Driver:
Quantity
Quantity
BACnet Client BACnet Server EIB/Instabus LONTalk Modbus IP OPC Server customized driver with hardware1
customized driver1
Customized driver: Please state, if you selected.
1
3.Options
Additional Protocol Driver MPG2
Part. No.
Protocol Option
785045
785046
785047
Project ID:
2
With additional hardware
Driver:
With additional hardware Kat. 1
Driver:
With additonal hardware Kat. 2
Driver:
Additional protocol driver: Please state, if you selected.
Hardware extensions always require the project ID!
Customized Project Planning MPG3
Project Option
Up to 1000 data points
Up to 3000 data points
Up to 15000 data points
More than 15000 data points
Project data (e.g. tools 8000 data of the FACP) for the MPG project planning to be supplied
by the customer.
3
Date/Signature
262
www.hls-austria.com
Quantity
Quantity
Part Number Index
Part No. Page
Part No. Page
Part No. Page
Part No. Page
013405.10
013590
013601
013603
013604
013605
013606
013607
013608
013609
013610
013611
013612
013613
013614
013616
013617
013618
013623
013624
013625
013626
013630
013631
013633
013634
013635
013636
013650
013651
013652
013653
013655
013660
018001
018002
018004
018006
018007
018009
018010
018011
018051
043150
045040
050510
057530.10
057631
057632
057633
057650.10
057651.10
057655
057700
057701
057711
057846
057850
057880
057881
057882
057884
057885
059200
059201
060426
060427
060429
060430.10
060431
070450
382040
701040
704070
704147
704148
704477.10
704801.10
704804
704854
704874
704900
704901
704902
704903
704904
704910
704911
704912
704915
704917
704950
704951
704952
704953
704954
704955
704960
704961
704964
704965
704966
704967
704975
704980
704981
704982
704983
704984
704985
706030
706030.EX
736235
743212
743245
743248
744027
744028
744029
744030
761243
761244
761245
761246
761247
761290
761312
761313
761314
761315
761316
761317
761317.50
761318
761321
761322
761323
761324
761347
761348
761349
761440
761441
761506
761509
761512
761517
761519
761520.10
761521.10
761522.10
761523.10
761524.10
761525.10
761526.10
761535
761536
761537.10
761542.10
761543.10
761546.10
761547
761549
761630
761694
761697
762401
762406
762407
764707
764708
764710
764723
764744
764745
764752
764754
764790
764818
764852
764855
764896
766225
766226
766230
766237
766238
766239
766240
766240.10
766240.20
766253
766261
766262
766303
766304
766305
766306
766307
766308
766410
766411
766412
766413
766414
767120
767121
767122
767123
767129
767130
767131
80
78
76
77
77
77
78
78
78
76
75
79
79
80
82
76
76
78
77
81
81
77
75
75
75
76
85
85
80
80
81
81
82
81
37
37
37
37
37
37
37
37
38
234
226
248
55
55
55
57
53
54
56
52
55
55
56
56
58
59
60
59
59
59
59
114
113
118
117
118
249
247
130
131
250
250
128
129
129
129
129
127
127
127
127
127
130
131
131
130
131
139
139
139
139
139
139
141
141
141
142
142
142
141
140
140
140
140
140
140
144
146
20
23
23
24
24
25
25
24
178
178
178
178
178
177
192
192
192
187
188
190
190
190
189
191
191
191
171
172
173
191
192
196
196
196
196
193
205
205
205
205
205
206
206
207
207
208
206
1
206
208
208
206
143
144
145
196
194
195
247
246
247
246
104
104
105
105
40
42
248
248
46
223
223
225
225
225
224
231
231
231
226
224
225
227
227
227
228
228
228
229
229
230
230
230
243
243
242
242
242
243
243
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
263
Part Number Index
264
Part No. Page
Part No. Page
Part No. Page
Part No. Page
767140
767153
767510
767800
769070
769080
769163
769164
769813
769814
769836
769870.20
769871.20
769910
769911
769914
769915
769916
769921
771670
772180
772386
772387
772445
772476
772477
772478
772479
781316
781332
781333
781335
781336
781337
781443
781444
781445
781446
781447
781448
781449
781482
781550
781682
781692
781694
781698
781699
781804
781814
782302
782303
782304
782306
782307
782308
782310
782313
782315
783312
783313
784382.D0
784385
784710
784725
784725.PL
784726
784726.PL
784731
784732
784734
784743
784743.CZ
784743.PL
784744
784753
784754
784763
784764
784765
784766
784790
784791
784840.10
784841.10
784842
784843
784844.10
784847
784855
784856
784859
784865
784892
785078
785101
785103
785107
785109
785113
785115
785588
785589
785590
785591
785592
785594
785596
785597
785753
786000
786002
786100
786102
786302
786402
786502
786802
786902
787530
787531
787532
788012.40
788013.40
788014.40.CZ
788014.40.GB
788014.40.PL
788014.40.RO
788014.40.SK
788015.40
788016
788023
788030
788031
788093
788400
788401
788402
788404
788600
788601
788602
788603.10
788605
788606
788609
788612
788650.10
788651.10
788652
788653
788654
788655
789300
789301
789302
789303
789305
789860.10
789861
789862.10
789863
789864
789866
796231
801515.10
801521.10
801522.10
801523.10
801524.10
801525.10
801531.10
801532.10
801533.10
801534.10
801535.10
801540
801541
801542
801543.10
801544.10
801547
801548
801549
801550
801551
801552
801553
801554
801555
801556
801557
801558
801559
801560
801561
801562
801563
801564
801565
801566
801567
801600
801602
801604
801605
801606
801824
801825
802171
802177
802271
www.hls-austria.com
242
241
249
109;244
119
120
23
23
119
119
111
118
119
132
132
23
24
132
130
22
143
66
66
21
19
19
19
19
173
210
210
36
36
36
174
175
176
175
175
176
176
120
121
132
133
133
133
134
232
232
169
169
169
170
170
170
169
168
168
170
170
22
22
42
45
45
45
45
46
46
44
43
43
43
43
44
44
64
64
64
64
49
49
62
62
22
63
63
66;71
65
65
65
63
20
48
41
41
41
41
41
41
48
48
48
49
49
50
50
50
38
18
16
18
16
17
17
17
17
17
22
22
22
29
29
31
31
31
31
31
31
32
32
252
252
18
32
32
32
32
251
251
249
250
250
66
71
156
251
251
249
31
31
151
11
11
12
20
71
26
26
27
27
28
28
234
198
198
199
200
200
201
199
200
201
201
201
203
203
203
202
202
204
204
204
208
209
209
209
209
209
209
209
209
209
209
209
209
209
209
209
209
209
203
207
202
203
207
233
233
89
89
90
Part Number Index
Part No. Page
Part No. Page
Part No. Page
Part No. Page
802371
802373
802374
802375
802379
802382
802383
802384
802385
802385.SV98
802385.SV99
802386
802386.SV98
802386.SV99
802473
803271.EX
803371.EX
803374.EX
804382.D0
804473.10
804744
804791
804867
804868
804869
804870
804880
804900
804901
804902
804905
804906
804950
804951
804955
804956
804970
804971
804973
804980
804981
805550
805551
805552
805553
805560
805570
805571
805572
805573
805574
805576
805577
805580
805581
805582
805583
805586
805587
805588
805589
805590
805591
805593.10
805594.10
805595.10
805597
805601.10
805602.10
805603
805604
805605
806201
806202
807205
807206
807212
807213
807214
807224
807322
807322.SV98
807322.SV99
807332
807332.SV98
807332.SV99
807372
807372.SV98
807372.SV99
808003
808004
808139
808219
808600.230
808610.10
808611.10
808613.30
808614.10
808615
808619.10
808622
808623
808624
808625
808626
808630.10
808631.10
960000.10.GB
960001.10.GB
960002.10.GB
960003.10.GB
960004.10.GB
960005.10.GB
960006.10.GB
960007.10.GB
960100
960101
960102
960103
960109
960110
960120
960121
960122
960123
960124
960127
960128
960129
970100
970101
970102
970103
970104
970105
970120
970121
970122
970123
970124
970130
970131
970135
970136
970137
970140
970141
970142
970143
970144
970145
970146
970147
970150
970151
970152
970153
970154
970155
970160
970161
970165
970170
970300
970301
970302
970303
BME2Z002
90
91
91
90
175
96
96
97
99
99
100
97
98
98
91
102
102
103
22
128
103
40
158
158
157
157
21
125
125
125
126
126
137
137
137
138
135
136
136
151
151
116
115
116
117
111
109
107
110
110
108
108
109
112
112
117
117
113
107
107
107
106
106
161
162
163
38
164
165
165
166
166
222
222
215
215
221
221
221
219
216
217
217
216
218
218
219
220
220
10
15
10
15
150
152
152
153
153
154
154
155
149
149
156
150
155
156
34
34
34
35
35
35
35
35
240
240
240
240
241
241
238
238
238
238
239
239
239
239
186
186
186
186
186
186
180
180
180
180
180
181
181
181
181
181
182
182
182
183
183
183
183
183
183
184
184
184
184
184
1
184
184
185
185
246
178
179
179
28
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
265
Index
Keyword
Page
A
Accumulator / battery kit
38
E2000 APC adapter to connect two connectors 970160 184
Adapter for ESSER pole (part no. 769813)
112
Adapter module ADP-N3E
43
Adapter module ADP-N3S
44
Adapter module ADP-PRS-232
44
Adapter module ADP-PRS-422
44
Additional housing ZG 0 for DS 8800
55
Additional housing ZG 0 for ISDN communication modules
55
Additional housing ZG 1 for DS 8800
55
Additional housing ZG 1 for ISDN communication module 55
Additional relay 12 V DC
249
Adhesive, 0.5 kg can
207
Air filter for aspirating smoke detectors
202
Alarm and monitoring module for IQ8TAM
157
Analog loop module
22
Analog loop module powered loop
22
Apiration reducing film sheet, 3.8 mm
209
Apiration reducing film sheet, 6.8 mm
209
Apiration reducing film sheet, 7.0 mm
209
Aspiration reducing film sheet, 2,0 mm
209
Aspiration reducing film sheet, 2.5 mm
209
Aspiration reducing film sheet, 3.0 mm
209
Aspiration reducing film sheet, 3.2 mm
209
Aspiration reducing film sheet, 3.4 mm
209
Aspiration reducing film sheet, 3.6 mm
209
Aspiration reducing film sheet, 4.0 mm
209
Aspiration reducing film sheet, 4.2 mm
209
Aspiration reducing film sheet, 4.4 mm
209
Aspiration reducing film sheet, 4.6 mm
209
Aspiration reducing film sheet, 5.0 mm
209
Aspiration reducing film sheet, 5.2 mm
209
Aspiration reducing film sheet, 5.6 mm
209
Aspiration reducing film sheet, 6,0 mm
209
19" assembly plate
60
B
Back-flow valve for Titanus EB
Banderole for suction reducing foil
Base cover for IQ8Quad
Base IP65 for IQ8Alarm, red
Base IP65 for IQ8Alarm, white
Base with side cable entry, red
Base with side cable entry, white
Basic license extension for USB port
Basic license for USB port 3 month duration
Basic license for WINMAGplus parallel port
Basic license for WINMAGplus USB port
Basic unit Titanus Pro Sens 2 EB
Basic unit Titanus Pro Sens EB
266
www.hls-austria.com
203
208
107
222
222
225
225
76
75
75
75
199
198
Keyword
Basic unit Titanus Top Sens 2 EB
Basic unit Titanus Top Sens EB
3.6V lithium battery
9 V alkaline-manganese battery
Battery 12 V DC / 1.2 Ah capacity
Battery 12 V DC / 2.1 Ah capacity
Battery 12 V DC / 7 Ah capacity
Battery 12 V DC / 12 Ah capacity
Battery 12 V DC / 15 Ah capacity
Battery 12 V DC / 24 Ah capacity
Battery 12 V DC / 38 Ah capacity
Battery 12V DC / 65 Ah capacity
Battery extension housing
BME2Z002
Page
200
199
38
38
37
37
37
37
37
37
37
37
11
28
C
Cable drum for FO sensor cable 970150 or 970153 185
Cable turnbuckle for floating roof tank
179
Carrying bag for test equipment including cover for tele113
scopic rods
Ceiling lead-through adapter ABS
206
Ceiling pendant mount for Fireray
192
CO capsule for multi-stimulus detector tester 805551 117
Combined alarm device 12 V DC, red
231
Combined alarm device 24 V DC, red
231
Combined alarm device 24 V DC, red, Asserta type 231
3-relay common fault module
22
Compact unit Titanus Pro Sens EB
198
Condensate trap for aspirating smoke detectors
207
Connection link set for sensor cable
178
Connection server developers kit
78
Control center software CD WINMAGplus basic kit
75
Control relay for top-hat rail mounting
249
Conventional MCP electronic module
125
Conventional MCP electronic module with glass - ESSER 137
Conventional MCP electronic module with second microswitch
125
Conventional MCP electronic module w/o snap-on function
125
Conventional MCP, red housing with glass pane - ESSER 135
Conversion kit for smoke detector tester 769870
119
Converter RS 232 / RS 485
248
Converter RS 232 / TTY
248
Corrugated polyester hose
206
CO test gas for smoke detector tester 805582
117
225
Cover plate for 766261 signal base
Cutting tool for FO steel sensor cable 970153
185
D
Data points package
DC / DC converter 12 V / 24 V DC
DC / DC converter output voltage
DC / DC converter output voltage 24 V DC
78
36
36
36
Index
Keyword
Page
Demo case for IQ8Quad detector with integrated alarm
device
111
Detector base with relay contact for IQ8Quad
106
Detector cover for IQ8Quad with built-in alarm sounder 107
Detector cover for IQ8Quad without built-in alarm sounder 107
Detector module 0.5 % / m DM-TT-50L
201
Detector module 0,5 % / m Typ DM-TP-50
200
Detector module 0.10 % / m DM-TP-10L
200
Detector module 0.10 % / m DM-TT-10L
201
Detector module 0.015 % / m DM-TP-01L
201
Detector module 0.015 % / m DM-TT-01L
201
Detector removal tool
112
Device holder for aspirating smoke detection systems
Titanus EB
203
DEZ 9000 19" front panel, 6 HU, installation in a 19"
housing
59
58
DEZ 9000 Alarm receiver in housing
Diagnostics tool for Titanus EB
204
Door closer, co-ordinator size 2-5
243
Door closer, co-ordinator size 5-7
243
Door closer, hold-open and co-ordinator size 2-5
242
Door closer, hold-open size 2-5
242
Door closer, hold-open size 5-7
242
Door magnet 24 V with distance pipe, 175 mm
238
Door magnet 24 V with distance pipe, 325 mm
238
Door magnet 24 V with distance pipe, 475 mm
238
Door magnet 24 V without release button
240
Door magnet 24 V without release button, incl. flexible
239
anchor
Door magnet 24 V with release button and flexible anchor 238
DS 7600 ISDN communication module with speech func53
tion
DS 7700 ISDN/IP communication module, with speech
transmission
54
DTS extension set
181
DTS interface box
Dummy cover 19", 2
Dummy cover 19", 3
Dummy cover 19", 5
Dummy cover 19", 9
HU
HU
HU
HU
181
24
24
25
25
E
ECP 8010 Series 4 with operating unit - ESSER, Czech 31
ECP 8010 Series 4 with operating unit - ESSER, English 31
ECP 8010 Series 4 with operating unit - ESSER, Polish 31
ECP 8010 Series 4 with operating unit - ESSER, Romanian
31
ECP 8010 Series 4 with operating unit - ESSER, Slovakian 31
ECP 8010 Series 4 w/o operating unit - ESSER
31
Keyword
1
Page
EMC shield for IQ8Quad detector base
111
Emergency file depot, DIN A4 horizontal for 10 pcs. routing cards - German
46
End cap (PVC) for 25 mm pipe
206
EOL-I terminating device
150
EOL-O terminating device
149
EOL-Z Module for detector groups
156
esserbus alarm transponder
149
esserbus communication transponder
154
esserbus FSA transponder for door release application 154
esserbus transponder 1 IN
153
esserbus transponder 12 relays (8bit)
152
esserbus transponder 32 LED
152
esserbus transponder FCT Set 12 - 24 V
151
esserbus transponder FCT Set 230 V
150
esserbus transponder for UniVario
155
esserbus transponder SST
153
essernet module, 62.5 kBd
62
essernet module, 500 kBd
62
essernet repeater, 62.5 kBd
63
essernet repeater, 500 kBd
63
essernet switch
63
2
3
4
5
6
7
8
9
Evaluation unit DTS - 1 km
180
Evaluation unit DTS - 2 km
180
Evaluation unit DTS - 3 km
180
Evaluation unit DTS - 4 km
180
Evaluation unit DTS - 8 km
180
Ex-Barrier for intrinsic safe detectors series IQ8Quad Ex (i)
103
Ex-Barrier for intrinsic safe of detectors series IQ8Quad Ex
(i) and 9100
104
Ex holding magnet
241
Ex-i terminal box for 970300
178
Ex manual call point conventional, IP66
145
Ex manual call point conventional, IP67, small housing,
red
146
226
Ex signaling device DS10, 12 V DC, 107 dB(A)
Ex Sounder 12 V DC, 110 dB(A)
226
Extension housing
20
Extension housing for batteries and SZI 192 detector
zones
11
Extension housing for SZI 192 detector zones
12
Extension module with 3 additional micromodule slots 19
Extension module with one additional micromodule slot 19
Extension pole
119
2MB RAM extension for DEZ 9000
59
External power supply 2 A / 24 V DC / 17 Ah EN 54-4 34
External power supply 3 A / 24 V DC / 17 Ah EN54-4 34
External power supply 3 A / 24 V DC / 28 Ah EN 54-4 34
External power supply 5 A / 24 V DC / 17 Ah EN 54-4 35
External power supply 5 A / 24 V DC / 28 Ah EN 54-4 35
External power supply 5 A / 24 V DC / 40 Ah EN 54-4 35
10
11
12
13
14
15
16
17
267
Index
Keyword
Page
External power supply 7 A / 24 V DC / 28 Ah EN 54-4
External power supply 7 A / 24 V DC / 40 Ah EN 54-4
Extinguishing panel 8010, Series 4 with operating unit German
Extinguishing panel 8010, Series 4 w/o operating unit
35
35
29
29
F
FACP IQ8Control M
15
FACP IQ8Control M for 19" cabinet
15
FB inform./operating system, A3 horizonal, individual locking - German
45
FB inform./operating system, A4 horizonal, individual locking - German
45
FB inform./operating system, A4 horizonal, individual locking - Polish
45
FDS connection board for transmission device
56
Fibre optic converter for essernet, multi-mode with F-SMA
male connection
64
Fibre optic converter for essernet, multi-mode with F-ST
64
male connection
Fibre optic converter for essernet, single-mode
64
Field bus interface PLus
27
Filler panel front, neutral for IQ8Control C/M
18
Filter cartridge for air duct module 781443
175
Filter for LRS aspirating system
196
Fire alarm panel IQ8Control C
10
Fire alarm panel IQ8Control C for 19" cabinet
10
Fire brigade operating panel (FBF-Ö) - Austria
42
Fire brigade operating panel - Germany
42
Fire department indicating panel FAT3000
43
Fire department indicating panel FAT3000 - Czech
43
Fire department indicating panel FAT3000 - Polish
43
Fire protection housing F30 LO
252
Fire protection housing F30 RO
252
Fireray 50 RV, with one prism
187
Fireray 100 RV, with four prisms
188
Fireray 2000
189
Fireray 5000, line smoke detector, incl. controller, 50 m
190
Fireray 5000, line smoke detector, incl. controller, 100 m 190
Fireray Eexd, Beam detector for EX areas
190
Fire service key box FSKB type 2003
48
Fire service key box FSKB type 2003 PZ
48
Fire service key box type 2003 with tamper protection 48
Fixed anchor plate for door magnets 960100-960103 241
Fixed heat detector class B IQ8Quad
89
Fixed heat detector IQ8Quad
89
Flashing light 12 V DC, amber
227
Flashing light 12 V DC, green
228
Flashing light 12 V DC, red
227
Flashing light 24 V DC, amber
227
Flashing light 24 V DC, green
228
Flashing light 24 V DC, red
228
268
www.hls-austria.com
Keyword
Page
Flash lamp, premounted on sheet steel column
50
Flexible anchor plate for door magnets 960100-960103 241
Floor-mounted door magnet 24 V with release button 240
Floor-mounting base for door magnet 960120
239
Flush mount kit for base IQ8Quad
107
Foil for front face w. universal text for large MCP ABS
70490x
131
Foil for front face w. universal text for large MCP ABS,
black lettering
131
Foil for front face w. universal text for small MCP, white lettering
141
FO sensor cable DTS safety FRNC
183
FO sensor cable steel FRNC
184
Front foil Titanus Pro Sens 2 EB
204
Front foil Titanus Top Sens 2 EB
204
8-fuse card
247
H
Hardware Option TCP / IP converter, Ethernet RS232 /
RS485
Heat detector UniVario 200 mm - ESSER
Heat detector UniVario 400 mm - ESSER
Heat detector UniVario 600 mm - ESSER
Heat detector UniVario - ESSER
Heat detector UniVario Flex 2 m - ESSER
Heat detector UniVario Flex 6 m - ESSER
Heat detector UniVario Flex 9 m - ESSER
Housing flush mount, grey
Housing flush mount, white
Housing for Ex-Barrier
Housing for small MCP, blue, similar to RAL 5015
Housing for small MCP, green, similar to RAL 6002
Housing for small MCP, grey, similar to RAL 7035
Housing for small MCP, orange, similar to RAL 2011
Housing for small MCP, red, similar to RAL 3020
Housing for small MCP, yellow, similar to RAL 1021
Housing kit
Housing surface mount, grey
Housing surface mount, white
Housing with glass pane, blue, similar to RAL 5015
Housing with glass pane, green, similar to RAL 6002
Housing with glass pane, orange, similar to RAL 2011
Housing with glass pane, red, similar to RAL 3020
Housing with glass pane, yellow, similar to RAL 1021
80
169
169
169
169
170
170
170
251
251
105
139
139
139
139
139
139
66
251
251
127
127
127
127
127
I
IGIS-LOOP-Controller kit for FACP 8000C, IQ8Control C or
71
EMZ 5008C
IGIS-LOOP-Controller kit for FACP 8000M, IQ8Control M 71
Indicating and operating panel for extinguishing panel
8010 - Czech
32
Indicating and operating panel for extinguishing panel
8010 - English
32
Index
Keyword
Page
Indicating and operating panel for extinguishing panel
8010 - German
32
Indicating and operating panel for extinguishing panel
8010 - Polish
32
Indicator and operating module LRS 110 - Esser, English 196
Installation frame for transmission units and transponders 57
Interface module RS232 / V24
66
Interface module TTY / CL 20 mA
66
I/O connection set
181
IP43 moisture-proof surface-mounted base adapter aP for
IQ8Quad detector base
110
IP43 protection for detector base IQ8Quad, flat design
109
IP43 protection for IQ8Quad detector bases, deep design 110
IP54 kit for large manual call points 7048xx
131
IP55 kit for protective cover
134
IP65 TG40 protective housing for 764708 and 764723 247
IP65 TG60 protective housing for 764708 and 764723 247
IP67 cable gland M12 with nut
250
IP67 cable gland M16 with nut
250
IP base adapter for FCT
151
IQ8Alarm combined alarm signaling device
219
IQ8Alarm combined speech alarm
219
IQ8Alarm combined speech alarm as customized version 220
IQ8Alarm combined speech alarm with composition of
other languages
220
IQ8Alarm optical alarm signaling device, amber
221
IQ8Alarm optical alarm signaling device, red
221
IQ8Alarm optical alarm signaling device / tranparent, blue,
green
221
IQ8Alarm sounder, red
215
IQ8Alarm sounder, white
215
IQ8Alarm speech alarm, red
216
218
IQ8Alarm speech alarm, red - customized version
IQ8Alarm speech alarm, red - special language
218
IQ8Alarm speech alarm, white
216;217
IQ8Alarm speech alarm, white
217
IQ8FCT
158
IQ8FCT electronic module
151
IQ8MCP electronic module
126
IQ8MCP electronic module with glass - ESSER
137
IQ8MCP electronic module with glass, without isolator, with
relay - ESSER
138
IQ8MCP electronic module w/o isolator but with relay 126
IQ8 MCP, red housing with glass pane - ESSER
136
IQ8 MCP, red housing with plastic pane - ESSER
136
IQ8Quad O2T intelligent detector Ex (i)
103
IQ8Quad optical smoke detector Ex (i)
102
IQ8Quad OTblue-LKM
175
Keyword
1
Page
IQ8Quad rate-of-rise detector Ex (i)
102
IQ8TAL electronic module
151
IQ8TAL technical alarm module
158
IQ8TAM technical alarm module for snap-on mounting
157
IQ8Wireless cover for wireless interface, red and white
166
IQ8Wireless detector base
161
IQ8Wireless gateway for devices
162
IQ8Wireless mounting frames for IQ8Alarm, red and white 165
IQ8Wireless transponder for devices, wall mount
163
IQ8Wireless universal interface w/o cover, red
164
IQ8Wireless universal interface w/o cover, white
165
3fold-IR-Flame detector UniVario - ESSER
168
IR flame detector 3501 (ex)
173
IR flame detector (ex) X 9800
171
ISDN connection lead with two western connectors, 1.5 m 56
ISDN receiver module for DEZ 9000
59
ISDN terminal box
56
Isolation and assembly block for safety barrier
104
2
3
4
5
6
7
8
9
K
Key box adapter SDA 3000
48
Kit DCF77 radio time module for IQ8Control & FlexES
control
21
Kit for suspended installation
120
L
Label / marker ring for parallel detector indicator
10
11
234
108
208
246
193
41
41
41
41
41
41
23
24
143
177
156
Label plate for detector base IQ8Quad
Labels-sampling points wrap round
LAN-surge protection for snap-on mounting rail
LaserFOCUS aspirating sytem - ESSER, multilingual
LCD-Indicator Panel - ESSER, Czech
LCD indicator panel - ESSER, English
LCD indicator panel - ESSER, German
LCD indicator panel - ESSER, Hungarian
LCD indicator panel - ESSER, Polish
LCD indicator panel - ESSER, Turkish
Lever lock - type 17 for key no. 801
Lever lock - type for key no. 901
LF-manual activation point low frequency
Line heat detector LWM-1
Loop isolator for transponders
Loop LED remote indicator panel for 32 messages ESSER
40
LRS 300 PC-Interface
196
LRS compact aspirating system - ESSER, English
194
LRS compact / net aspirating system - ESSER, English
195
12
13
14
15
16
17
269
Index
Keyword
Page
M
Manual call point conventional, IP67, small housing, red 144
Manual call point Series 9200 addressable, IP66
144
Master box interface module
22
MCP electronic module Series 9000 with second microswitch
128
MCP electronic module Series 9200 with zone isolator
128
MCP housing with glass in compliance with EN 54-11, red 129
MCP housing with glass printed: house alarm-ESSER, blue
129
MCP housing with glass printed: house alarm-ESSER, red 129
MCP housing with glass printed: house alarm-ESSER,
yellow
129
Metal key for large MCP
132
183
Micro splice-box for DTS FO cable
Module housing for snap-on mounting rail
250
19” rack mounting kit for SZI 192 detector zones
18
Mounting adapter for intermediate ceilings
109
Mounting bracket for lintel installation
109;244
Mounting bracket for UniVario Flame Detector
170
Mounting clip for 25 mm pipe
208
Mounting frame 19" IQ8Control C/M
21
Mounting frame for small MCP, red and white
142
Mounting kit
250
Mounting plate for door closer with door closer control
243
Mounting plate for door closer without door closer control 243
Mounting rail for FACP 8000 C/M and IQ8Control C/M
249
housing
Mounting set for round and insulated air ducts
176
MPG DP500
69
MPG DP7500
69
MPG DP35000
70
Multiple-sector interface in housing
32
Multi-stimulus detector tester
115
Multi-stimulus detector tester TF1001
116
N
Network interference suppression filter type 2VK3
248
O
O2T/F multisensor IQ8Quad
96
O2T/FSp multisensor detector IQ8Quad as customized
version
100
O2T/FSp multisensor detector IQ8Quad with composition
of other languages
99
O2T/FSp multisensor IQ8Quad
99
O2T multisensor IQ8Quad
91
O2T/So multisensor IQ8Quad
97
O2T/Sp multisensor IQ8Quad
97
270
www.hls-austria.com
Keyword
Page
O2T/Sp multisensor IQ8Quad / customized version
98
O2T/Sp multisensor IQ8Quad / special language
98
Operating front for printer, with take-up reel - English 17
Operating front with printer, w/o take-up reel - English 17
Operating front with SZI for 64 detector zones - English 16
Operating module front 1/4 VGA and SZI for 64 zones English
17
Operating module front - English
16
Operating module front with 1/4 VGA display and printer English
17
Operating module front with 1/4 VGA display - English 17
Operating panel foil for large manual call point 80490x,
neutral
130
Optical alarm signaling device, red
229
Optical alarm signalling device, amber
229
Optical alarm signalling device, blue
230
Optical alarm signalling device, green
230
Optical alarm signalling device, transparent
230
Optical smoke detector IQ8Quad
90
Option – ability for customized interface rights (client-side)
81
Optional 2nd channel for evaluation unit DTS
181
Option – client
81
Option – DTMF control option
80
Option – escalation
80
Option IP55 shrink sleeve for large MCP 80490x
131
Option - notification
80
Option – redundance
81
Option – WEBX
81
O/So optical smoke detector IQ8Quad
96
OTblue multisensor detector IQ8Quad
90
OTG multisensor (CO) IQ8Quad
91
OT multisensor detector IQ8Quad
91
"Out of order" sign, multilingual for large MCP
130
P
Panel 8010-option with control group indicator and alarm
counter
32
Peripheral module
19
Peripheral module with one additional micromodule slot 19
E2000 APC 8° pigtail
184
45° angle (PVC) for 25 mm pipe
205
90° angle (PVC) for 25 mm pipe
205
90° bend (PVC) for 25 mm pipe
205
Pipe (ABS), diameter 25 mm
205
208
Pipe cutter for PVC / ABS pipes
Plastic key for large MCP
132
Plastic pane, resettable function, for small MCP - ESSER 141
Plastic spare key for small MCP
142
Plastic telescopic extension
114
Plastic telescopic rod
113
Index
Keyword
Page
Plate for 1 prism
191
Plate for 4 prism
192
Power supply / charging unit 12 V DC / 7.2 Ah
55
Premounting for freestanding key box
50
Printer kit with paper take-up reel for IQ8Control C/M 20
Printer paper for printer 736233 / 736234
20
1 prism for Fireray
191
4 prisms for Fireray
191
9 prisms for Fireray 2000
191
Protective cage
121
Protective cover for manual call points - ESSER, English 133
Protective kit for MCP and TAL, transparent
142
PSTN communication module DS 8800
52
PVC detergente, 1 L can
207
R
50
Rain protection cover for FSKB 2003
Rate-of-rise heat detector IQ8Quad
90
Refurbishment zone transponder (RZT) / 12 V - ESSER 156
155
Refurbishment zone transponder RZT 8000
3-relay module
22
4-relay module
22
Relay controller set
181
Release element K
49
Release element PZ
49
Remote indicator, flashing, green
234
Remote indicator for addressable detector series 9200
233
and IQ8Quad
Remote indicator for conventional detector series 9000,
red
232
Remote indicator for detector series 9000, 9200 and
IQ8Quad
232
Remote indicator for series 9200 and IQ8Quad, blue 233
Replacement air filter pads for 801544
202
Replacement filter element for 801600
203
Reset module for hat rail mounting
210
Reset module with mounting bracket for Fireray 2000 210
Reset PCB for Titanus EB
203
Route map housing for DIN-A3 expansion
46
Route map housing for DIN-A4 expansion
46
RS 232/TTY serial interface module
22
S
Sensor cable black
Sensor cable black, with steel braiding
Sensor cable blue (PVC)
Sensor cable connectors for FO cable 970150
Sensor cable connectors for FO cable 970153
Sensor cable EPC
Sensor cable EPR
8000 FACP remote serial essernet interface
Serial connecting cable for 789862
Serial essernet interface EDP, bidirectional
178
178
178
184
184
186
186
65
28
65
Keyword
1
Page
Serial essernet interface EDP, unidirectional
65
Serial interface for WINMAGplus / WINMAGLite
66;71
Serial programming cable for USB field bus and panel
interface for 8010
28
Service key for electronic module (part no. 80490x) 132
Setting tool for anchor installation
183
Shallow base sounder, red
223
Signal base
224
Sleeve (PVC) for 25 mm pipe
206
Smoke capsule for multi-stimulus detector tester
805550/51
116
Smoke detector tester
117
Smoke pellets for testing purposes
120
Software update for DEZ 9000 - German
59
Software update for DEZ ISDN receiver module - German 59
Sound absorber for Titanus EB aspirating smoke detection
systems
202
Sounder, red
224
Sounder with low-profile base, white
223
Spare battery baton
118
Spare filter for VESDA aspirating smoke systems
196
Spare glass pane for MCP housings 70490x, 7048xx and
761694
130
Spare glass pane for small MCP, EN54 - ESSER
141
Spare glass pane for small MCP, EN54 - neutral
141
Spare glass pane red for MCP housings 7047xx and
7048xx
130
Spare key 1D009 for FACP
23
Spare key 801 for FACP
23
Spare key 901 for FACP
24
2
3
4
5
6
7
8
9
10
11
12
Special filter
203
Splice-box IP66 for DTS FO cable, stainless steel
183
Splice-box IP67 for DTS FO cable, steel
183
Stainless steel anchor with plastic clamp for DTS cable 182
Stainless steel anchor with stainless steel clamp for DTS
183
cables
Stainless steel column for FSKB type 2003
49
Stainless steel column with cover monitoring
49
Standard detector base for IQ8Quad
106
Standard LED remote indicator panel - ESSER
40
Standard MCP electronic module with glass, with 2nd
137
micro-switch - ESSER
Start/end of line box for LWM-1
179
Steel anchor with plastic clamp for DTS cables
182
Steel anchor with steel clamp for DTS cables
182
Suctions hose set for 25 mm pipe
206
Surface mount housing for small MCP, blue, similar to RAL
140
5015
Surface mount housing for small MCP, green, similar to
140
RAL 6002
13
14
15
16
17
271
Index
Keyword
Page
Surface mount housing for small MCP, grey, similar to RAL
7035
140
Surface mount housing for small MCP, orange, similar to
RAL 2011
140
Surface mount housing for small MCP, red, similar to RAL
3020
140
Surface mount housing for small MCP, yellow, similar to
RAL 1021
140
Surface spacer for protective cover
133
Surge protection device for Line heat detector LWM-1
(761290)
246
Surge protection for network and low-frequency signal
loop
246
Switched-mode power supply with cylindrical plug
28
SZI front for 192 detector zones
18
T
Telescopic rod
119
Terminal card for LF-manual call point 761630
143
31
Terminal card for panel 8010
Terminal card for panel 8010 in 19-inch technology, 2 m 31
178
Termination link set for sensor cable
Terminators for FO cable 970150
184
Terminators for FO cable 970153
184
Test gas for smoke detecetor tester 805582
117
Test gas for smoke detector testers 769870.10 and
119
769870
Test head for heat detector together with battery and
118
charger
Threaded cable connection for housing 764752
105
Three-way ball valve
207
tools 8000 PLus equipment starter kit
26
tools 8000 programming software
26
Top-hat rail
249
T-Piece (PVC) for 25 mm pipe
205
4inch trim ring and snap-in mounting clips for IQ8Quad
detector base
108
U
UniVario MX5000.ESSER standard base
170
Univ. bracket for F5000 or prism plate 761440/761441
192
Universal gateway for PC
78
Upright cabinet
23
Upright cabinet including mounting
23
USB cable A/B for 789862 field bus & panel interface 27
UV flame detector (ex) X 2200
172
UV Flame detector UniVario Type FMX5000UV - ESSER
168
UV/IR flame detector (ex) X 5200
173
V
Venturi air duct module for IQ8Quad OTblue-LKM
(802379)
174
272
www.hls-austria.com
Keyword
Page
Venturi tube 0.6 m for IQ8Quad air duct construction set
781443
175
Venturi tube 1.5 m for IQ8Quad air duct construction set
781443
175
Venturi tube 2.8 m for IQ8Quad air duct construction set
781443
176
VESDAnet™ connection box
196
W
Wall and floor angle for door magnet 960120, 150 mm
239
Wall and floor angle for door magnet 960120, 300 mm
239
Wall bracket for Fireray Eexd
192
Wall-mounted door magnet 24 V with release button 240
Weather protection housing for air duct construction set
781443
176
Weather protective cover, blue for MCP-housings
7047/48xx
133
Weather protective cover, red for MCP housings 7047/48xx
132
WINMAG installation upgrade as of version 6
76
WINMAGLite upgrade to WINMAGplus full version
85
WINMAGLite with USB dongle
85
WINMAGplus – 4-monitor support option
81
WINMAGplus – AutoCAD option
82
WINMAGplus control centre software - subsequent upgra76
de
WINMAGplus licence connection server
78
WINMAGplus licence - fire detection technology
77
WINMAGplus licence - interfacing DEZ 9000
77
WINMAGplus licence - intrusion detection technology 76
WINMAGplus licence – OPC client
79
WINMAGplus licence – OPC server
79
WINMAGplus licence - rescue route technology / escape
77
door control
WINMAGplus licence - RTD
78
WINMAGplus licence - video technology
77
WINMAGplus license - access control
77
WINMAGplus – OEM option
WINMAG upgrade to WINMAGplus
82
76
Honeywell Life Safety Austria GmbH
Lemböckgasse 49, 1230 Vienna, Austria
Phone: +43 1 600 60 30
Fax:
+43 1 600 60 30-900
Internet:www.hls-austria.com
E-Mail: [email protected]
Part No. 054581.AT.G0
July 2011
Subject to change without notice
©2011 Honeywell International Inc.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement