Allen-Bradley E300 Electronic Overload Relay User Manual
Below you will find brief information for Electronic Overload Relay E300. This manual is for the E300 Electronic Overload Relay that provides comprehensive motor protection, including overload, ground fault, phase loss, under voltage, over voltage, jam, stall, and more. The E300 can be used in a variety of applications including industrial, commercial, and residential. It is an easy-to-use device with features that include simplified wiring, modular design, and optional expansion modules.
PDF
Download
Document
Advertisement
Advertisement
User Manual E300 Electronic Overload Relay Bul. 193/592 Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Table of Contents Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Chapter 1 Product Overview Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modular Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Simplified Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operator Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Module Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Add-On Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Expansion I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Operator Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Optional Expansion Bus Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . Protection Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Current-Based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground Fault Current-based Protection. . . . . . . . . . . . . . . . . . . . . . . . Voltage- and Power-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . Applications: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 13 13 14 14 15 15 15 15 16 16 16 16 17 17 18 18 19 19 20 20 21 21 21 21 22 Chapter 2 Installation and Wiring Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unpacking/Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Storing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Base Relay Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Module to Sensing Module Assembly . . . . . . . . . . . . . . . . . . . . . . Communication Module to Control Module Assembly . . . . . . . . . . . . . Expansion Bus Peripherals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Bus Digital and Analog I/O Modules and Power Supply Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Bus Operator Station Installation . . . . . . . . . . . . . . . . . . . . . . . Expansion Bus Network Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rockwell Automation Publication 193-UM015C-EN-P - December 2014 23 23 23 23 24 24 25 26 27 28 28 28 30 3 Table of Contents Starter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIN Rail / Panel Mount Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Bus Peripherals Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Digital Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Analog Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Short-Circuit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuse Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Typical Motor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Line Current Transformer Application . . . . . . . . . . . . . . . . . . . . Current Transformer Ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Full-Voltage Non-Reversing Starter (with Network Control). . . . . Full-Voltage Reversing Starter (with Network Control). . . . . . . . . . 31 34 35 37 37 38 40 41 43 44 44 46 47 48 48 52 52 53 Chapter 3 Diagnostic Station Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Navigation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Displaying a Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter Group Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Linear List Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Editing a Configuration Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Editing a Numeric Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Editing a Bit Enumerated Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable Display Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Display Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Stopping the Display Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Automatic Trip and Warning Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 55 55 56 57 58 59 59 59 60 60 60 61 62 Chapter 4 System Operation and Configuration Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Device Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Administration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Run Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Invalid Configuration Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Option Match . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Enable Option Match Protection Trip (Parameter 186). . . . . . . . . . Enable Option Match Protection Warning (Parameter 192) . . . . . 4 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 63 63 64 64 65 65 66 67 68 Table of Contents Control Module Type (Parameter 221) . . . . . . . . . . . . . . . . . . . . . . . . 68 Sensing Module Type (Parameter 222) . . . . . . . . . . . . . . . . . . . . . . . . . 69 Communication Module Type (Parameter 223) . . . . . . . . . . . . . . . . 69 Operator Station Type (Parameter 224) . . . . . . . . . . . . . . . . . . . . . . . . 70 Digital I/O Expansion Module 1 Type (Parameter 225) . . . . . . . . . 70 Digital I/O Expansion Module 2 Type (Parameter 226) . . . . . . . . . 71 Digital I/O Expansion Module 3 Type (Parameter 227) . . . . . . . . . 71 Digital I/O Expansion Module 4 Type (Parameter 228) . . . . . . . . . 71 Analog I/O Expansion Module 1 Type (Parameter 229) . . . . . . . . . 72 Analog I/O Expansion Module 2 Type (Parameter 230) . . . . . . . . . 73 Analog I/O Expansion Module 3 Type (Parameter 231) . . . . . . . . . 73 Analog I/O Expansion Module 4 Type (Parameter 232) . . . . . . . . . 74 Option Match Action (Parameter 233) . . . . . . . . . . . . . . . . . . . . . . . . 74 Security Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Device Configuration Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Device Reset Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Firmware Update Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Security Configuration Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 I/O Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Input Pt00 Assignment (Parameter 196) . . . . . . . . . . . . . . . . . . . . . . . 76 Input Pt01 Assignment (Parameter 197) . . . . . . . . . . . . . . . . . . . . . . . 77 Input Pt02 Assignment (Parameter 198) . . . . . . . . . . . . . . . . . . . . . . . 77 Input Pt03 Assignment (Parameter 199) . . . . . . . . . . . . . . . . . . . . . . . 78 Input Pt04 Assignment (Parameter 200) . . . . . . . . . . . . . . . . . . . . . . . 78 Input Pt05 Assignment (Parameter 201) . . . . . . . . . . . . . . . . . . . . . . . 79 Output Pt00 Assignment (Parameter 202) . . . . . . . . . . . . . . . . . . . . . 80 Output Pt01 Assignment (Parameter 203) . . . . . . . . . . . . . . . . . . . . . 81 Output Pt02 Assignment (Parameter 204) . . . . . . . . . . . . . . . . . . . . . 82 Expansion Bus Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Expansion Bus Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Expansion Bus Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Emergency Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Diagnostic Station User-defined Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 User-defined Screen 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 User-defined Screen 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 User-defined Screen 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 User-defined Screen 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Display Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Analog I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Analog Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Analog Output Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Update Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Analog Module 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Analog Module 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Analog Module 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 Analog Module 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Introduction to Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 5 Table of Contents Chapter 5 Operating Modes Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Overload (Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Monitor (Custom) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 Chapter 6 Protective Trip and Warning Functions 6 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phase Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground Fault Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Stall Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Jam Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Underload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Imbalance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Line Under Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Line Over Current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Line Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage-based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Under Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Over Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Imbalance Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phase Rotation Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frequency Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Real Power (kW) Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reactive Power (kVAR) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . Apparent Power (kVA) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Factor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control-Based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operator Station Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start Inhibit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Option Match. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Bus Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nonvolatile Storage Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Mode Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rockwell Automation Publication 193-UM015C-EN-P - December 2014 129 129 132 139 141 148 150 153 156 160 169 177 184 187 190 193 196 198 204 206 213 226 232 245 247 248 249 250 253 255 256 256 256 256 257 259 261 268 276 283 Table of Contents Chapter 7 Commands Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear Operating Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear History Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear %TCU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear kWh. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear kVARh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear kVAh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear Max kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear Max kVAR Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear Max kVA Demand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clear All. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293 293 293 294 299 300 300 300 300 301 301 301 302 302 302 Chapter 8 Metering and Diagnostics Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Percent Thermal Capacity Utilized . . . . . . . . . . . . . . . . . . . . . . . . . . . Time to Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time To Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Trip Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Warning Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Warning Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Status 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Status 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operator Station Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device Status 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device Status 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Firmware Revision Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sensing Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operator Station ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion Digital Module ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starts Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starts Available. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time to Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rockwell Automation Publication 193-UM015C-EN-P - December 2014 305 305 305 306 306 307 308 309 309 310 310 311 311 312 312 313 314 315 316 316 316 317 317 318 318 319 319 319 7 Table of Contents Year . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Month . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Day. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Minute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Second. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Invalid Configuration Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Invalid Configuration Cause. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mismatch Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3 Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Average Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3 Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Average Percent FLA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ground Fault Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Current Imbalance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1-L2 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2-L3 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Average L-L Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3-N Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Average L-N Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phase Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3 Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3 Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L3 Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L2 Power Factor Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 320 320 320 321 321 322 322 322 323 323 323 324 324 324 325 325 326 326 326 327 327 327 328 328 329 329 329 330 330 331 331 331 331 332 332 332 333 333 334 334 334 335 335 336 336 337 337 Table of Contents L3 Power Factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Total Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Energy Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kWh 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kWh 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kWh 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kWh 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kWh 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Consumed 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Consumed 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Consumed 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Consumed 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Consumed 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Generated 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Generated 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Generated 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Generated 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Generated 10-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Net 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Net 106. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Net 103. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Net 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVARh Net 10-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAh 109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAh 106 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAh 103 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAh 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAh 10-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Max kW Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVAR Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Max kVAR Demand. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . kVA Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Max kVA Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Module 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip / Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Snapshot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Snapshot L1-L2 Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Snapshot L2-L3 Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Snapshot L3-L1 Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip Snapshot Total Real Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rockwell Automation Publication 193-UM015C-EN-P - December 2014 337 338 338 338 339 339 340 340 340 341 341 342 342 342 343 343 344 344 344 345 345 346 346 346 347 347 348 348 348 349 349 349 349 350 350 350 352 354 355 357 357 361 366 366 366 366 367 9 Table of Contents Trip Snapshot Total Reactive Power . . . . . . . . . . . . . . . . . . . . . . . . . . 367 Trip Snapshot Total Apparent Power . . . . . . . . . . . . . . . . . . . . . . . . . 367 Trip Snapshot Total Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368 Chapter 9 EtherNet/IP Communications Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 Network Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 Determining Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371 Setting the IP Network Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372 EtherNet/IP Node Address Selection Switches. . . . . . . . . . . . . . . . . 372 Assign Network Parameters via the BOOTP/ DHCP Utility. . . . 373 Assign Network Parameters Via a Web Browser and MAC Scanner Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 Other Factors to Consider When Assigning Network пЂ Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375 Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376 Web Server Security and System Password . . . . . . . . . . . . . . . . . . . . . 376 Permanently Enabling the Web Server. . . . . . . . . . . . . . . . . . . . . . . . . 378 Duplicate IP Address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 Behavior of Modules With Duplicate IP Addresses . . . . . . . . . . . . . 379 DNS Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380 Electronic Data Sheet (EDS) File Installation . . . . . . . . . . . . . . . . . . . . . . 380 Download the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 View and Configure Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384 Viewing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384 Editing Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 Automation Controller Communications . . . . . . . . . . . . . . . . . . . . . . . . . 387 I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387 Logix Configuration with Add-on Profile. . . . . . . . . . . . . . . . . . . . . . 388 Logix Configuration with a Generic Profile . . . . . . . . . . . . . . . . . . . . 393 E-mail/Text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398 E-mail Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399 Text Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401 Chapter 10 Firmware Updates 10 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403 Firmware Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403 Updating Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404 E300 Firmware Update Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410 Control Module Boot Code Firmware Update . . . . . . . . . . . . . . . . . 411 Control Module Application Code Firmware Update . . . . . . . . . . 414 Control Module Uncompressed EtherNet/IP EDS File Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Table of Contents Control Module Compressed EtherNet/IP EDS File Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419 Control Module Compressed DeviceNet EDS File Firmware пЂ Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421 Completed Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424 Chapter 11 Troubleshooting Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Advisory LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip/Warn LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Resetting a Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Trip/Warn LED Troubleshooting Procedures. . . . . . . . . . . . . . . . . . . . . 425 425 425 426 428 428 Appendix A Specifications Electrical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Low Voltage Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electromagnetic Compatibility Specifications . . . . . . . . . . . . . . . . . . . . . Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protection Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431 433 434 435 436 437 437 437 Appendix B Parameter List Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439 Appendix C EtherNet/IP Information Common Industrial Protocol (CIP) Objects . . . . . . . . . . . . . . . . . . . . . . Identity Object — CLASS CODE 0x0001 . . . . . . . . . . . . . . . . . . . . Message Router — CLASS CODE 0x0002 . . . . . . . . . . . . . . . . . . . . Assembly Object — CLASS CODE 0x0004 . . . . . . . . . . . . . . . . . . . Instance 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instance 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instance 120 - Configuration Assembly Revision 2 . . . . . . . . . . . . . Instance 120 - Configuration Assembly Revision 1 . . . . . . . . . . . . . Instance 144 – Default Consumed Assembly . . . . . . . . . . . . . . . . . . Instance 198 - Current Diagnostics Produced Assembly . . . . . . . . Instance 199 - All Diagnostics Produced Assembly . . . . . . . . . . . . . Connection Object — CLASS CODE 0x0005 . . . . . . . . . . . . . . . . Discrete Input Point Object — CLASS CODE 0x0008 . . . . . . . . Discrete Output Point Object — CLASS CODE 0x0009 . . . . . . Analog Input Point Object — CLASS CODE 0x000A . . . . . . . . . Parameter Object — CLASS CODE 0x000F . . . . . . . . . . . . . . . . . . Parameter Group Object — CLASS CODE 0x0010 . . . . . . . . . . . Rockwell Automation Publication 193-UM015C-EN-P - December 2014 481 482 484 484 485 486 486 496 496 496 498 500 503 504 506 507 508 11 Table of Contents Discrete Output Group Object — CLASS CODE 0x001E . . . . . Control Supervisor Object — CLASS CODE 0x0029 . . . . . . . . . . Overload Object — CLASS CODE 0x002c . . . . . . . . . . . . . . . . . . . Base Energy Object — CLASS CODE 0x004E. . . . . . . . . . . . . . . . . Electrical Energy Object — CLASS CODE 0x004F . . . . . . . . . . . . Wall Clock Time Object — CLASS CODE 0x008B . . . . . . . . . . . DPI Fault Object — CLASS CODE 0x0097. . . . . . . . . . . . . . . . . . . DPI Warning Object — CLASS CODE 0x0098 . . . . . . . . . . . . . . . MCC Object — CLASS CODE 0x00C2. . . . . . . . . . . . . . . . . . . . . . 12 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 508 509 510 510 512 514 515 519 522 Chapter 1 Product Overview Overview The E300в„ў Electronic Overload Relay is a microprocessor-based electronic overload relay that is designed to help protect three-phase or single-phase AC electric induction motors that are rated from 0.5…65,000 A. Its modular design, communication options, diagnostic information, simplified wiring, and integration into Logix makes the E300 the ideal overload for motor control applications in an automation system. The E300 Electronic Overload Relay provides flexibility, reduces engineering time, and maximizes uptime for important motor starter applications. Modular Design You can select the specific options that you need for your motor starter application. The E300 Electronic Overload Relay consists of three modules: sensing, control, and communications. You can customize each of the three with accessories to tailor the electronic motor overload for your application’s exact needs. • Wide current range • Sensing capabilities (Current, Ground Fault Current, and/or Voltage) • Expansion I/O • Operator interfaces Communication Options You can select from multiple communication options that integrate with Logixbased control systems. Developers can easily add the E300 Electronic Overload Relay to Logix-based control systems using Integrated Architecture tools like Add-on Profiles, Add-on Instructions, and Faceplates. • EtherNet/IP (DLR) • DeviceNet Rockwell Automation Publication 193-UM015C-EN-P - December 2014 13 Chapter 1 Product Overview Diagnostic Information The E300 Electronic Overload Relay provides a wide variety of diagnostic information to monitor motor performance, proactively alert you to possible motor issues, or identify the reason for an unplanned shutdown. Information includes: • Voltage, Current, and Energy • Trip / Warning Histories • % Thermal Capacity Utilization • Time to Trip • Time to Reset • Operational Hours • Number of Starts • Trip Snapshot Simplified Wiring The E300 Electronic Overload Relay provides an easy means to mount to both IEC and NEMA Allen-Bradley contactors. A contactor coil adapter is available for the 100-C contactor, which allows the you to create a functional motor starter with only two control wires. 14 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Product Overview Catalog Number Explanation Chapter 1 E300 Electronic Overload Relay modules have their own catalog number. Sensing Module 193 - ESM - VIG - 30A - C23пЂ 592 Bulletin Number Module Type Sensing Module Type Sensing Current Range 193 IEC Overload RelayпЂ 592 NEMA Overload Relay ESM Sensing Module VIG Current, Ground Fault Current, пЂ Voltage, and PowerпЂ IG Current and Ground Fault CurrentпЂ I Current 30A 60A 100A 200A 0.5…30 AпЂ 6…60 AпЂ 10…100 AпЂ 20…200 A Sensing Module Mounting Style C23 C55 C97 D180 S2 S3 S4 T E3T P CT Mounts to 100-C09…-C23 ContactorпЂ Mounts to 100-C30…-C55 ContactorпЂ Mounts to 100-C60…-C97 ContactorпЂ Mounts to 100-D115…-D180 ContactorпЂ Mounts to Bulletin 500 NEMA Size 0-2 ContactorпЂ Mounts to Bulletin 500 NEMA Size 3 ContactorпЂ Mounts to Bulletin 500 NEMA Size 4 ContactorпЂ DIN Rail / Panel Mount with Power TerminalsпЂ Replacement DIN Rail / Panel Mount with Power Terminals for an E3 Plus Panel Mount AdapterпЂ DIN Rail / Panel Mount with Pass-thru Power ConductorsпЂ DIN Rail / Panel Mount with Pass-thru Power Conductors (used with External CTs) Control Module 193 - EIO - 43 - 120 Bulletin Number Module Type I/O Count Control Voltage 193 IEC Overload Relay EIO I/O Only Control ModuleпЂ EIOGP I/O and Protection Control Module пЂ (External Ground Fault SensingпЂ and PTC) 63 43 42 22 24D 24V DCпЂ 120 110…120V AC, 50/60 HzпЂ 240 220…240V AC, 50/60 H 6 Inputs / 3 Relay OutputsпЂ 4 Inputs / 3 Relay OutputsпЂ 4 Inputs / 2 Relay OutputsпЂ 2 Inputs / 2 Relay Outputs Communication Module 193 - ECM - ETR Bulletin Number Module Type Communication Type 193 IEC Overload Relay ECM Communication Module ETR EtherNet/IP with Dual Ethernet PortsпЂ DNT DeviceNet Rockwell Automation Publication 193-UM015C-EN-P - December 2014 15 Chapter 1 Product Overview Digital Expansion Module 193 - EXP - DIO - 42 - 120 Bulletin Number Module Type 193 IEC Overload Relay EXP Expansion Module DIO Digital I/O I/O Type I/O Count Communication Type 42 4 Inputs / 2 Relay Outputs 120 110…120V AC, 50/60 Hz InputsпЂ 240 220…240V AC, 50/60 Hz InputsпЂ 24D 24V DC Inputs Analog Expansion Module 193 - EXP - AIO - 31 Bulletin Number Module Type 193 IEC Overload Relay EXP Expansion Module AIO Analog I/O I/O Type I/O Count 31 3 Universal Analog Inputs / 1 Analog Output Operator Station 193 - EOS - SCS Bulletin Number Module Type I/O Type 193 IEC Overload Relay EOS Operator Station SCS Starter Control StationпЂ SDS Starter Diagnostic Station Power Supply 193 - EXP - PS - AC Bulletin Number Module Type 193 IEC Overload Relay EXP Expansion Module PS Expansion Bus Power Supply 16 Function Type Supply Voltage AC 110-240V AC, 50/60Hz control voltageпЂ DC 24V DC control voltage Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Product Overview Module Description Chapter 1 The E300 Electronic Overload Relay is comprised of three modules. All three modules are required to make a functional overload relay. • Sensing Module • Control Module • Communication Module Sensing Module Figure 1 - Sensing Module The sensing module electronically samples data about the current, voltage, power, and energy that are consumed by the electric motor internal to the module. You can choose from one of three varieties of the sensing modules depending on the motor diagnostic information that is needed for the motor protection application: • Current Sensing • Current and Ground Fault Current Sensing • Current, Ground Fault Current, Voltage, and Power Sensing The current ranges for each of three varieties of sensing module are as follows: • 0.5…30 A • 6…60 A • 10…100 A • 20…200 A You can choose how the sensing module mechanically mounts inside the electrical enclosure. The following mounting mechanisms are available for the sensing module. • Mount to the load side of an Allen-Bradley Bulletin 100 IEC Contactor • Mount to the load side of an Allen-Bradley Bulletin 500 NEMA Contactor • DIN Rail / Panel Mount with power terminals • Replacement DIN Rail / Panel Mount with power terminals for an Allen-Bradley E3 Plus panel mount adapter • DIN Rail / Panel Mount with pass-thru power conductors Rockwell Automation Publication 193-UM015C-EN-P - December 2014 17 Chapter 1 Product Overview Control Module Figure 2 - Control Module The control module is the heart of the E300 Electronic Overload Relay and can attach to any sensing module. The control module performs all protection and motor control algorithms and contains the native I/O for the system. The control module has two varieties: • I/O only • I/O and protection (PTC and External Ground Fault Current Sensing) The control module is offered in three control voltages: • 110…120V AC, 50/60Hz • 220…240V AC, 50/60Hz • 24V DC External control voltage is required to power the E300 Electronic Overload Relay and activate the digital inputs. Communication Module Figure 3 - Communication Module The communication module allows the E300 Electronic Overload Relay to be integrated into an automation system, and it can attach to any control module. All communication modules allow you to set the node address with rotary turn 18 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Product Overview Chapter 1 dials, and it provides diagnostic status indicators to provide system status at the panel. The E300 Electronic Overload Relay supports two network protocols: • EtherNet/IP • DeviceNet The E300 EtherNet/IP Communication Module has two RJ45 connectors that function as a switch. You can daisy chain multiple E300 Electronic Overload Relays with Ethernet cable, and the module supports a Device Level Ring (DLR). Optional Add-On Modules Optional Expansion I/O The E300 Electronic Overload Relay allows you to add more digital and analog I/O to the system via the E300 Electronic Overload Relay Expansion Bus if the native I/O count is not sufficient for the application on the base relay. You can add up to four more Digital I/O Expansion Modules that have four inputs (120V AC, 240V AC, or 24V DC) and two relay outputs. You can also add up to four more Analog I/O Expansion Modules, which have three independent universal analog inputs and one isolated analog output. The Analog I/O Expansion Modules require Control Module firmware v3.000 or higher. The independent universal analog inputs can accept the following signals: • 4…20 mA • 0…20 mA • 0…10V DC • 1…5V DC • 0…5V DC • RTD Sensors (Pt 385, Pt 3916, Cu 426, Ni 618, Ni 672, and NiFe 518) • Resistance (150 пЃ—, 750 пЃ—, 3000 пЃ—, and 6000 пЃ—) The isolated analog output can be programmed to reference a traditional analog signal (4…20 mA, 0…20 mA, 0…10V DC, 1…5V, or 0…10V) to represent the following diagnostic values: • Average %FLA • %TCU • Ground Fault Current • Current Imbalance • Average L-L Voltage • Voltage Imbalance • Total kW • Total kVAR • Total kVA • Total Power Factor • User-defined Value Rockwell Automation Publication 193-UM015C-EN-P - December 2014 19 Chapter 1 Product Overview Optional Operator Station Figure 4 - Operator Stations Power LED Escape Power LED Trip / Warn LED Up Trip / Warn LED Select LO C REM AL OT E Start Forward / Speed 1 Start Reverse / Speed 2 0 Local / Remote ESC RES ET LO C REM AL OT E Start Forward / Speed 1 Stop Reset Start Reverse / Speed 2 SEL ECT 0 Local / Remote Enter RES ET Down Stop Control Station Diagnostic Station Reset The E300 Electronic Overload Relay offers you the capability to add one operator interface to the Expansion Bus. You can choose between two types of operator stations: Control Station or a Diagnostic Station. Both types of operator stations mount into a standard 22 mm push button knockout, and they provide diagnostic status indicators that allow you to view the status of the E300 Electronic Overload Relay from the outside of an electrical enclosure. Both operator stations provide push buttons that can be used for motor control logic, and they both can be used to upload and download parameter configuration data from the base relay. The Diagnostic Station contains a display and navigation buttons that allows you to view and edit parameters in the base relay. The Diagnostic Station requires Control Module firmware v3.000 or higher. Optional Expansion Bus Power Supply Figure 5 - Expansion Bus Power Supply The E300 Electronic Overload Relay expansion bus provides enough current to operate a system that has (1) Digital Expansion Module and (1) Operator Station. An E300 Electronic Overload Relay system that contains more expansion modules needs supplemental current for the Expansion Bus. The E300 Electronic Overload Relay offers you two types of Expansion Bus Power Supplies: AC (110…240V AC, 50/60 Hz) and DC (24V DC). One Expansion 20 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Product Overview Chapter 1 Bus Power Supply supplies enough current for a fully loaded E300 Electronic Overload Relay Expansion Bus (four Digital Expansion Modules, four Analog Expansion Modules, and one Operator Station). Protection Features Standard Current-Based Protection All versions of the E300 Electronic Overload Relay provide the following motor protection functions: • Thermal Overload (51) • Phase Loss • Current Imbalance (46) • Undercurrent – load loss (37) • Overcurrent – load jam (48) • Overcurrent – load stall • Start Inhibit (66) Ground Fault Current-based Protection The E300 Electronic Overload Relay sensing modules and control modules with a ground fault current option provides the following motor protection function: • Ground Fault – zero sequence method (50N) Voltage- and Power-based Protection The E300 Electronic Overload Relay sensing modules with voltage sensing provides the following motor protection functions: • Undervoltage (27) • Overvoltage (59) • Phase Reversal (47) – voltage-based • Over and Under Frequency (81) – voltage-based • Voltage Imbalance (46) • Over and Under Power (37) • Over and Under Leading/Lagging Power Factor (55) • Over and Under Reactive Power Generated • Over and Under Reactive Power Consumed • Over and Under Apparent Power Rockwell Automation Publication 193-UM015C-EN-P - December 2014 21 Chapter 1 Product Overview Applications: 22 The E300 Electronic Overload Relay can be used with the following across the line starter applications: • Non-reversing starter • Reversing starter • Wye (Star) / Delta starter • Two-speed motors • Low and medium voltage with two or three potential transformers • With or without Phase current transformers • With or without zero-sequence core balanced current transformer Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 2 Installation and Wiring Introduction This chapter provides instructions for receiving, unpacking, inspecting, and storing the E300в„ў Electronic Overload Relay. Assembly, installation, and wiring instructions for common applications are also included in this chapter. Receiving It is your responsibility to thoroughly inspect the equipment before accepting the shipment from the freight company. Check the item(s) received against the purchase order. If any items are damaged, it is your responsibility not to accept delivery until the freight agent has noted the damage on the freight bill. If any concealed damage is found during unpacking, it is again your responsibility to notify the freight agent. The shipping container must be left intact and the freight agent should be requested to make a visual inspection of the equipment. Unpacking/Inspecting Remove all packing material from around the E300 Electronic Overload Relay. After unpacking, check the item’s nameplate catalog number against the purchase order. Storing The E300 Electronic Overload Relay should remain in its shipping container before installation. If you will not use the equipment immediately, you must store it according to the following instructions to maintain warranty coverage: • Store in a clean, dry location. • Store within an ambient temperature range пЂ of -40…+85 В°C (-40…+185 В°F). • Store within a relative humidity range of 0…95%, non-condensing. • Do not store where the device could be exposed to a corrosive atmosphere. • Do not store in a construction area. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 23 Chapter 2 Installation and Wiring General Precautions If the E300 Electronic Overload Relay is being deployed in an environment with an ambient temperature greater than 30 В°C (86 В°F), please see the Environmental Specifications on page 434 for the appropriate temperature derating. In addition to the specific precautions listed throughout this manual, the following general statements must be observed. ATTENTION: The E300 Electronic Overload Relay contains electrostatic discharge (ESD) sensitive parts and assemblies. Status control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, see Allen-Bradley publication 8000-SB001_-en-p, “Guarding Against Electrostatic Damage”, or any other applicable ESD protection handbook. ATTENTION: An incorrectly applied or installed E300 Electronic Overload Relay can result in damage to the components or reduction in product life. Wiring or application errors (for example, incorrectly calculating the FLA setting, supplying incorrect or inadequate supply voltage, connecting an external supply voltage to the thermistor terminals, or operating or storing in excessive ambient temperatures) may result in malfunction of the E300 Electronic Overload Relay. ATTENTION: Only personnel familiar with the E300 Electronic Overload Relay and associated machinery should plan to install, start up, and maintain the system. Failure to comply may result in personal injury or equipment damage. ATTENTION: The purpose of this user manual is to serve as a guide for proper installation. The National Electrical Code (NEC) and any other governing regional or local code overrules this information. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the E300 Electronic Overload Relay or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation. ATTENTION: The earth ground terminal of the E300 Electronic Overload Relay shall be connected to a solid earth ground via a low-impedance connection. Base Relay Assembly 24 The following section illustrates the E300 Electronic Overload Relay base relay assembly instructions. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Any E300 Control Module can connect to any E300 Sensing Module. The following illustrations show the steps that are required to make this connection. Control Module to Sensing Module Assembly Figure 6 - Control Module to Sensing Module Assembly 2 1 3 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 25 Chapter 2 Installation and Wiring Any E300 Communication Module can connect to any E300 Control Module. The illustrations below show the steps required to make this connection. Communication Module to Control Module Assembly Figure 7 - Communication Module to Control Module Assembly 2 3 1 26 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 The E300 Electronic Overload Relay offers a range of Expansion Digital and Analog I/O modules that simply connect to the E300 Electronic Overload Relay’s Expansion Bus. Expansion Bus Peripherals Figure 8 - Expansion Bus Peripherals Removable I/O Terminals Panel Mount Hole DIN Rail Mount Status LED Color Description Off No power applied Blinking Green Module OK with no connection Green Module OK and active Red Error Detected Digital Module Number Selector Number Description Panel Mount Hole D3 4 D2 D4T D D1 T T D3 D1 2T D Expansion Bus Out D1 - D4 Module number Module number with D1T - D4T expansion bus terminating resistor applied Analog Module Number Selector Number Description A1 - A4 Module number Module number with A1T - A4T expansion bus terminating resistor applied Note: If the expansion bus does not have an operator station, then the last expansion module number must be set to terminated. Expansion Bus In You can also add one of the two available operator stations to the end of the Expansion Bus. Figure 9 - Expansion Operator Stations Power LED Escape Power LED Trip / Warn LED Up Trip / Warn LED Select Start Forward / Speed 1 LO C REM AL OT E Start Reverse / Speed 2 0 ESC RES ET Local / Remote Start Forward / Speed 1 Stop LO C REM AL OT E Start Reverse / Speed 2 Reset SEL ECT 0 Local / Remote Enter RES ET Down Stop Control Station Diagnostic Station Reset The following illustrations show how to mount and connect the E300 Electronic Overload Relay expansion bus I/O modules, expansion power supplies, and operator stations. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 27 Chapter 2 Installation and Wiring Expansion Bus Digital and Analog I/O Modules and Power Supply Installation Figure 10 - Expansion Bus Digital and Analog I/O Modules and Power Supply 1 Click 2 Expansion Bus Operator Station Installation Figure 11 - Expansion Bus Operator Station 22 mm 2 1.7 N.m (15 lb-in) ESC SEL ECT LO C REM AL OT E 1 0 800F-AW2 RES ET 3 Expansion Bus Network Installation 28 The E300 Electronic Overload Relay supports up to (4) Expansion Digital I/O modules, (4) Expansion Analog I/O modules, and (1) Operation Station. The E300 Base Relay can supply enough power for (1) Expansion Digital I/O module and (1) Operator Station. Any other combination of E300 Expansion Bus Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 peripherals requires an Expansion Bus Power Supply, which connects as the first module on the Expansion Bus. Set the module number dial of the Expansion Digital Module to a unique digital module number (D1-D4). If the Expansion Digital Module is the last device on the Expansion Bus, set the module number to the value that enables the internal terminating resistor (D1T-D4T). A power cycle is required when changes are made to the module number dial. Set the module number dial of the Expansion Analog Module to a unique analog module number (A1-A4). If the Expansion Analog Module is the last device on the Expansion Bus, set the module number to the value that enables the internal terminating resistor (A1T-A4T). A power cycle is required when changes are made to the module number dial. Connect the E300 Base Relay to the Expansion Module’s Input Port using the supplied Expansion Bus cable. Add the next Expansion Module by connecting the supplied Expansion Bus cable to the Output Port of the previous Expansion Module and into the Input Port of the additional Expansion Module. The Operator Station is the last device on the E300 Expansion Bus; it only has an Input Port with an internal Expansion Bus terminating resistor. If the user-supplied Expansion Bus cable is not long enough for the installation, 1-meter (Cat. No. 193-EXP-CBL-1M) and 3-meter (Cat. No. 193-EXP-CBL-3M) Expansion Bus cables are available as accessories. The E300 expansion bus can support a maximum distance of 5 meters (16 ft.). Figure 12 - Expansion Bus Network Installation ESC LO C REM AL OT E 1 2 SEL ECT 0 RES ET Click Rockwell Automation Publication 193-UM015C-EN-P - December 2014 29 Chapter 2 Installation and Wiring Starter Assembly The following illustrations show how to assemble an E300 Electronic Overload Relay as a motor starter with an Allen-Bradley Bulletin 100-C contactor. 100-C09…-C55 Starter Assembly Installation The starter assembly installation instructions are for use with E300 Sensing Module catalog numbers 193-ESM-___-___-C23 and 193-ESM-___-___-C55 Figure 13 - 100-C09…-C55 Starter Assembly Installation 5 - 7 lb-in 6 9 - 22 lb-in 5 IN1 IN0 A2 R04 R 03 A 1 4 2 3 7 -11 lb-in 1 30 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Starter Dimensions Figure 14 - E300 Sensing Module 193-ESM-___-__-C23 with 100-C09…-C23 Contactor 87 (3.40) 45 (1.76) 35 (1.37) n 5 (0.18) 190 (7.49) 60 (2.3 (ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE) 67 (2.65) 37 (1.47) FROM CONTACTOR MTG. HOLE 152 (5.98) 122 (4.81) 122 (4.78) 29 (1.14) FROM CONTACTOR MTG. HOLE Figure 15 - E300 Sensing Module 193-ESM-___-__-C55 with 100-C30…-C37 Contactor 45 (1.76) 104 (4.10) 190 (7.49) (ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE) 35 (1.374) n 5 (0.18) 60 (2.36) 67 (2.65) 37 (1.48) FROM CONTACTOR MTG. HOLE 152 (5.98) 122 (4.81) 29 (1.13) FROM CONTACTOR MTG. HOLE 122 (4.78) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 31 Chapter 2 Installation and Wiring Figure 16 - E300 Sensing Module 193-ESM-___-__-C55 with 100-C43…-C55 Contactor 107 (4.21) 54 (2.12) 45 (1.75) n 5 (0.18) 60 (2. 190 (7.49) (ADD 5 mm (0.19 in.) FOR CONTACTOR COIL ON LINE SIDE) 67 (2.65) 37 (1.48) FROM CONTACTOR MTG. HOLE 152 (5.98) 34 (1.34) FROM CONTACTOR MTG. HOLE 122 (4.82) 45 (1.76) Figure 17 - E300 Sensing Module 193-ESM-___-__-C97 with 100-C60…-C97 Contactor 4.97 (126.2) 2.82 (71.6) 0.21 (5.4) 3.98 (101) 9.26 (235.1) (ADD 0.24 FOR CONTACTOR COIL ON LINE SIDE) 3.60 (91.6) 1.71 (43.5) FROM CONTACTOR MTG. HOLE 6.99 (177.6) 5.10 129.5) 1.53 (38.9) 32 FROM CONTACTOR MTG. HOLE 2.165 (55) 5.32 (135.2) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Figure 18 - E300 Sensing Module 592-ESM-___-__-S2 with NEMA Contactor Size 0 and Size 1 90 (3.56) n 6 (0.22) 180 (7.06) 157 (6.17) 249 (9.78) 12 (0.46) 125 (4.91) 35 (1.38) 70 (2.75) Figure 19 - E300 Sensing Module 592-ESM-___-__-S2 with NEMA Contactor Size 2 100 (3.94) n 6 (0.22) 184 (7.24) 219 (8.63) 276 (10.85) 12 (0.46) 125 (4.91) 40 (1.58) 80 (3.15) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 33 Chapter 2 Installation and Wiring Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. DIN Rail / Panel Mount Dimensions Figure 20 - E300 Sensing Module 193-ESM-___-30A-E3T and 193-ESM-___-60A-E3T 30 (1.18) 126 (4.94) 45 (1.764) 6 (0.24) 9 (0.33) 46 (1.81) 4 (0.16) q 148 (5.83) 135 (5.32) 4 (0.14) 6 (0.217) 101 (3.96) 4 (0.154) n 5 (0.17) 8 (0.30) Figure 21 - E300 Sensing Module 193-ESM-___-30A-T and 193-ESM-___-60A-T SHOWN WITH PANEL MOUNT FEET ACCESSORY 0.45 (11.35) n 0.189 (4.8) 1.53 (39) 5.32 (135) WITH MTG. FEET 0.18 (4.5) 1.19 (30.1) q 1.76 (45) 4.58 (116.2) W/O MTG. FEET 4.88 (124) Mount feet accessory Cat. No.: 140M-C-N45 34 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 4.921 (125) 0.197 (5) Installation and Wiring Chapter 2 Figure 22 - E300 Sensing Module 193-ESM-___-100A-E3T 2.82 (71.6) 0.70 (17.7) 1.62 (41.2) 5.51 (139.9) 2.36 (60) 0.22 (5.5) 5.12 (130) q 3.02 (76.6) 1.63 (41.4) 5.57 (141.5) Expansion Bus Peripherals Dimensions 0.16 (4.05) Approximate dimensions are shown in millimeters. Dimensions are not intended to be used for manufacturing purposes. Figure 23 - E300 Digital Expansion Module 193-EXP-DIO-___ 22.5 (0.89) 98 (3.86) 87 (3.43) 2 x 4.5 (0.18) dia. 80.75 (3.18) 120 (4.73) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 35 Chapter 2 Installation and Wiring Figure 24 - E300 Expansion Analog Module 193-EXP-AIO 22.5 (0.89) 98 (3.86) 2 x 4.5 (0.18) dia. 87 (3.43) 80.75 (3.18) 120 (4.73) Figure 25 - E300 Expansion Power Supply 193-EXP-PS-___ 45 (1.77) 98 87 (3.86) (3.43) 4x 4.5 (0.18) dia 80.75 (3.18) 12 (0.47) 36 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 120 (4.73) Installation and Wiring Chapter 2 Figure 26 - E300 Starter Control Station 193-EOS-SCS 100 (3.94) 18.5 (0.73) 22.5 (0.89) dia. 13.5 (0.53) 45 (1.77) Figure 27 - E300 Starter Diagnostic Station 193-EOS-SDS 18.5 (0.73) 100 (3.94) 22.5 (0.89) dia. 13.5 (0.53) 70 (2.76) Terminals Sensing Module Table 1 - E300 Sensing Module Wire Size and Torque Specifications Cat. No. Wire Type 193-ESM-_ _ _-30A-_ _ _ 193-ESM-_ _ _-60A-_ _ _ 592-ESM-_ _ _-30A-_ _ _ 592-ESM-_ _ _-60A-_ _ _ 193-ESM-_ _ _-100A-_ _ _ 592-ESM-_ _ _-100A-_ _ _ Single #14…6 AWG 22 lb-in. #12…1 AWG 35 lb-in. Multiple #10…6 AWG 30 lb-in. #6…2 AWG 35 lb-in. Single 2.5…16 mm2 2.5 N•m 4…35 mm2 4 N•m Multiple 6…10 mm2 3.4 N•m 4…25 mm2 4 N•m Single 2.5…25 mm2 2.5 N•m 4…50 mm2 4 N•m Multiple 6…16 mm2 3.4 N•m 4…35 mm2 4 N•m Conductor Torque Stranded/Solid [AWG] Flexible-Stranded with Ferrule Metric Coarse-Stranded/Solid Metric Rockwell Automation Publication 193-UM015C-EN-P - December 2014 37 Chapter 2 Installation and Wiring Control Module Figure 28 - E300 Control Module Terminal Designations 193-EIO-63- _ _ _ A1 R13 R14 A1 193-EIOGP-42- _ _ _ A1 A2 I N2 IN3 IN4 R13 R14 193-EIO-43- _ _ _ R13 R14 A1 A2 R23 R24 2 IN 3 IT 1 IT 2 S2 193-EIOGP-22- _ _ _ IN3 Power / PTC Terminals R13 R14 S1 A1 A2 IT1 IT2 S2 Communication Module Latch Expansion Bus Connector Relay / Ground Fault Terminals 38 S1 A1 IN2 2 IN IN5 R23 R24 A1 A1 A IN1 IN0 A2 R04 R03 Sensing Module Latch Rockwell Automation Publication 193-UM015C-EN-P - December 2014 A1 Input / Output Terminals Installation and Wiring Chapter 2 Table 2 - E300 Control Module Wire Size and Torque Specifications Wire Type Conductor Torque Stranded/Solid [AWG] Single Multiple (stranded only) Single Flexible-Stranded with Ferrule Metric Multiple Single Coarse-Stranded/Solid Metric Cat. No. 193-EIO-_ _-_ _ _ 193-EIOGP-_ _-_ _ _ 24...12 AWG 24...16 AWG 5 lb-in 0.25…2.5 mm2 0.5...0.75 mm2 0.55 N•m 0.2...2.5 mm2 0.2...1.5 mm2 0.55 N•m Multiple Figure 29 - Control Module Wiring 193-EIO-_ _-_ _ _ A1 R03 A2 R04 IN0 193-EIOGP-_ _-_ _ _ A1 R03 IN1 A2 R04 IN0 IN1 RELAY 0 RELAY 0 Additional Inputs for 193-EIO-63-_ _ _ RELAY 1 A1 A1 (+) A2 IN2 (-) IN3 IN4 IN5 PE R13 Additional Inputs for 193-EIOGP-42-_ _ _ RELAY 1 RELAY 2 R14 R23 R24 A1 A1 (+) A2 IN2 (-) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 IN3 IT1 PTC IT2 PE R13 R14 Ground Fault S1 S2 +t 39 Chapter 2 Installation and Wiring Expansion Digital Module Figure 30 - E300 Expansion Digital Module Terminal Designations R04 R14 RC3 RS2 IN2 IN3 IN0 IN1 INC Table 3 - E300 Expansion Digital Module Wire Size and Torque Specifications Wire Type Stranded/Solid [AWG] Flexible-Stranded with Ferrule Metric Coarse-Stranded/Solid Metric 40 Conductor Torque Cat. No. 193-EXP-DIO-42-_ _ _ Single 24...12 AWG Multiple (stranded only) 24...16 AWG 5 lb-in Single 0.25…2.5 mm2 Multiple 0.5...0.75 mm2 0.55 N•m Single 0.2...2.5 mm2 Multiple 0.2...1.5 mm2 0.55 N•m Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Figure 31 - E300 Expansion Digital Module Wiring Diagram R04 R14 RC3 + Source - IN0 IN1 IN2 IN3 INC Expansion Analog Module Figure 32 - E300 Expansion Analog Module Terminal Designations OUT+OUT- IN2+ IN2- RS2 IN1+ IN1- RS1 IN0+ IN0- RS0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 41 Chapter 2 Installation and Wiring Table 4 - E300 Expansion Analog Module Wire Size and Torque Specifications Wire Type Conductor Torque Single Multiple (stranded only) Single Stranded/Solid [AWG] Flexible-Stranded with Ferrule Metric Multiple Single Coarse-Stranded/Solid Metric Multiple Cat. No. 193-EXP-AIO-31 24...12 AWG 24...16 AWG 5 lb-in 0.25…2.5 mm2 0.5...0.75 mm2 0.55 N•m 0.2...2.5 mm2 0.2...1.5 mm2 0.55 N•m Figure 33 - E300 Expansion Analog I/O Modules 193-EXP-AIO-__ Analog Current Input + 24V DC Power Supply - Current Input Device INx+ Analog Voltage Input +V INx+ -V INx- INx- 3 Wire RTD 2 Wire RTD/Resistance INx+ INxAnalog Voltage or Current Output + Out+ Device Out- 42 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 INx+ INxRSx Installation and Wiring Chapter 2 Expansion Power Supply Figure 34 - E300 Expansion Power Supply Terminal Designations A1 A2 Table 5 - E300 Expansion Power Supply Wire Size and Torque Specifications Wire Type Conductor Torque Stranded/Solid [AWG] Flexible-Stranded with Ferrule Metric Coarse-Stranded/Solid Metric Single Multiple (stranded only) Single Multiple (stranded only) Single Multiple (stranded only) Cat. No. 193-EXP-PS-_ _ 24...12 AWG 24...16 AWG 5 lb-in 0.25…2.5 mm2 0.5...0.75 mm2 0.55 N•m 0.2...2.5 mm2 0.2...1.5 mm2 0.55 N•m Figure 35 - E300 Expansion Power Supply Wiring Diagram + Source - A1 A2 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 43 Chapter 2 Installation and Wiring Grounding The following grounding recommendations are provided to help ensure EMC requirements during installation. • The earth ground terminal of the E300 Electronic Overload Relay shall be connected to a solid earth ground via a low-impedance connection. • Wire the green shield wire of the Cat. No. 193-ECM-ETR into the earth ground terminal of the E300 control module. • Installations employing an external ground fault sensor shall ground the cable shield at the sensor with no connection made at the E300 Electronic Overload Relay. • The PTC thermistor cable shield shall be grounded at the E300 Electronic Overload Relay with no connection made at the opposite end. Short-Circuit Ratings The E300 Electronic Overload Relay is suitable for use on circuits capable of delivering not more than the RMS symmetrical amperes listed in the following tables. Table 6 - Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 Overload Relay with Sensing Module Cat. No. 193-ESM-___-30A-C23 193-ESM-___-30A-C55 193-ESM-___-30A-E3T 193-ESM-___-30A-P 193-ESM-___-30A-T 193-ESM-VIG-30A-CT 592-ESM-___-30A-S2 193-ESM-___-60A-C55 193-ESM-___-60A-E3T 193-ESM-___-60A-P 193-ESM-___-60A-T 592-ESM-___-60A-S2 193-ESM-___-100A-C97 193-ESM-___-100A-E3T 193-ESM-___-100A-T 592-ESM-___-100A-S3 44 Max. Available Fault Current [A] Maximum Voltage [V] 5,000 600 10,000 600 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Table 7 - Short Circuit Ratings per EN60947-4-1 Overload Relay with Sensing Module Cat. No. 193-ESM-___-30A-C23 193-ESM-___-30A-C55 193-ESM-___-30A-E3T 193-ESM-___-30A-P 193-ESM-___-30A-T 193-ESM-VIG-30A-CT 592-ESM-___-30A-S2 193-ESM-___-60A-C55 193-ESM-___-60A-E3T 193-ESM-___-60A-P 193-ESM-___-60A-T 592-ESM-___-60A-S2 193-ESM-___-100A-C97 193-ESM-___-100A-E3T 193-ESM-___-100A-T 592-ESM-___-100A-S3 Prospective ShortCircuit Current, Ir [A] Conditional Short-Circuit Current, Iq [A] Maximum Voltage [V] 3,000 100,000 690 5,000 100,000 690 Table 8 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C and 100-D IEC contactors that are protected by fuses Overload Relay with Sensing Module Cat. No. 193-ESM-___-30A-C23 193-ESM-___-30A-C55, пЂ 193-ESM-___-60A-C55 193-ESM-___-100A-C97 Contactor Cat. No. Max. Starter FLC [A] 100-C09 100-C12 100-C16 100-C23 100-C30 100-C37 100-C43 100-C55 100-C72 100-C85 100-C97 9 12 16 23 30 37 43 55 72 85 97 Max. Available Fault Current [A] 100,000 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Max. Voltage [V] Class C or JJ fuse [A] 600 20 20 30 30 50 50 70 80 100 150 200 45 Chapter 2 Installation and Wiring Table 9 - Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C IEC contactors that are protected by Bul. 140U-D circuit breakers Overload Relay with Sensing Module Cat. No. Contactor Cat. No. Max. Starter FLC[A] 100-C09 100-C12 100-C16 100-C23 100-C09 100-C12 100-C16 100-C23 100-C09 100-C12 100-C16 100-C23 9 12 16 23 9 12 16 23 9 12 16 23 193-ESM-___-30A-C23 193-ESM-___-30A-C23 193-ESM-___-30A-C23 Max. Available Fault Current [A] Max. Voltage [V] Max. Circuit Breaker Cat. No. 140U-D6D3- 65,000 480Y/277V C30 (30 A) 35,000 600Y/347V C30 (30 A) 5,000 600Y/347V C30 (30 A) Table 10 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 500 line NEMA contactors that are protected by fuses Overload Relay with Sensing Module Cat. No. Contactor Size Max. Starter FLC [A] 592-ESM-___-30A-S2 00 9 592-ESM-___-30A-S2 0 18 592-ESM-___-30A-S2 1 27 592-ESM-___-60A-S2 2 45 592-ESM-___-100A-S3 3 90 Fuse Coordination Max. Available Fault Current [A] Max. Voltage [V] 100,000 600 240 600 240 600 240 600 240 600 Max. UL Fuse [A] R J — 20 30 30 30 30 60 100 30 50 100 200 60 100 200 350 100 200 The following tables list Type I and Type II Fuse Coordination when used with Bulletin 100-C and 100-D and Bulletin 500 NEMA Size 00… 2 Contactors. ATTENTION: Select the motor branch circuit protection that complies with the NEC and any other governing regional or local codes. 46 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Table 11 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors per EN60947-4-1 Overload Relay with Sensing Module Cat. No. 193-ESM-___-30A-C23 193-ESM-___-30A-C55, пЂ 193-ESM-___-60A-C55 193-ESM-___-100A-C97 Contactor Cat. Max. Starter No. FLC[A] 100-C09 9 100-C12 12 100-C16 16 100-C23 23 100-C30 30 100-C37 37 100-C43 43 100-C55 55 100-C72 72 100-C85 85 100-C97 97 Prospective Short-Circuit Current, Ir [A] Conditional ShortCircuit Current, Iq [A] 1000 100,000 3,000 5,000 Max. Voltage Type I Class J or Type II Class J [V] CC Fuse [A] or CC Fuse [A] 20 15 20 20 30 30 40 40 50 50 600 50 50 70 70 80 80 100 100 150 150 200 200 Table 12 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors пЂ per EN60947-4-1 Overload Relay with Sensing Module Cat. No. 592-ESM-___-30A-S2 592-ESM-___-30A-S2 592-ESM-___-60A-S2 592-ESM-___-100A-S3 Contactor Size Max. Starter FLC[A] 0 1 2 3 18 27 45 90 Prospective ShortCircuit Current, Ir [A] 3,000 5,000 Conditional Short- Max. Voltage Type I Class J Type II Class J Circuit Current, Iq [V] Fuse [A] Fuse [A] [A] 30 30 30 30 100,000 600 60 60 200 200 Typical Motor Connections ATTENTION: When working on energized circuits, DO NOT rely on voltage and current information that is provided by the E300 Electronic Overload Relay for personal safety. Always use a portable voltage or current measurement device to measure the signal locally. Three-Phase Direct On-Line (DOL) and Single-Phase Full-voltage The following wiring diagram illustrates the E300 Electronic Overload Relay typical motor connections in a three-phase DOL and single-phase full-voltage applications. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 47 Chapter 2 Installation and Wiring Figure 36 - E300 DOL and Single-Phase Full-voltage Connections Three-Phase Direct-On-Line S.C.P.D. L1 L3 L2 Single-Phase Full-Voltage S.C.P.D. E300 2/T1 E300 6/T3 4/T2 T1 T2 T3 M External Line Current Transformer Application L2 L1 2/T1 4/T2 6/T3 T1 T2 M Current Transformer Ratio The following E300 Electronic Overload Relay sensing module catalog numbers can be used with step down current transformers: • 193-ESM-IG-30A-E3T • 193-ESM-IG-30A-T • 193-ESM-IG-30A-P • 193-ESM-I-30A-E3T • 193-ESM-I-30A-T • 193-ESM-I-30A-P • 193-ESM-VIG-30A-CT CT Primary (Parameter 263) and CT Secondary (Parameter 264) allows you to identify the turns ratio of the step down current transformers in use. Based on these two configuration parameters, the E300 Electronic Overload Relay will automatically adjust the measured current. Use the primary current for your FLA settings. 48 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Installation and Wiring Chapter 2 Table 13 - CT Primary (Parameter 263) CT Primary (Parameter 263) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 5 1 65535 UINT 2 1 Amps Table 14 - CT Secondary (Parameter 264) CT Secondary (Parameter 264) Default Value 5 Minimum Value 1 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Amps ATTENTION: Improper configuration of the CT Ratio parameters can make the E300 Electronic Overload Relay report inaccurate motor operational data and possible motor damage. IMPORTANT The E300 Electronic Overload Relay trip on a configuration fault when the FLA setting is outside of the legal range of the selected CT Ratio settings. The TRIP/ WARN LED status indicator flashes red 3-long, 8-short blinking pattern. You shall (1) provide one CT for each motor phase and shall (2) connect the CT’s secondary leads to the appropriate sensing module power terminals. The CTs shall be selected to be capable of providing the required VA to the secondary load, which includes the E300 Sensing Module burden of 0.1 VA at the rated secondary current and the wiring burden. Finally, the CT shall (1) be rated for Protective Relaying to accommodate the high inrush currents associated with motor startup and shall (2) be accurate to within ≤±2% over its normal operating range. Typical CT ratings include: • ANSI USA • CSA (Canada) • IEC (Europe) • Class C5 BO.1 • Class 10L5 • 5 VA Class SP10 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 49 Chapter 2 Installation and Wiring ATTENTION: The improper selection of a current transformer can result in the E300 Electronic Overload Relay reporting inaccurate motor operational data and possible motor damage. The selected current transformer must be rated for protective relaying applications. Figure 37 - External Current Transformer Connection IEC NEMA L1 L2 L1 L3 L3 L2 K1 L1/1 L2/3 L3/5 L1/1 L2/3 L3/5 E300 Primary Current Transformers T1/2 T2/4 T3/6 E300 Primary Current Transformers T1/2 T2/4 T3/6 T1 M T2 T3 M The E300 Electronic Overload Relay voltage-based sensing modules support a wide variety of power systems. Table 15 lists the power systems supported by the specific sensing module. Table 15 - Supported Power Systems Catalog Number Connection Type Power System Single Phase 193-ESM-VIG-__-__пЂ 592-ESM-VIG-__-__ Direct Delta Wye Grounded B Phase Delta Single Phase Direct Wye Grounded B Phase Delta 193-ESM-VIG-30A-CT 3 PT 2 PT 50 Delta Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Delta Wye Single Phase Open Delta Installation and Wiring Chapter 2 Voltage Mode Voltage Mode (Parameter 252) determines the method for how voltage is monitored E300 Electronic Overload Relay. Select the connection type for the appropriate power system. Table 16 - Voltage Mode (Parameter 352) Default Value 0 = Delta direct or with PTs 0 = Delta direct or with PTs 1 = Wye direct or with PTs Range 2 = Delta with Delta to Wye PTs 3 = Wye with Delta to Wye PTs 4 = Delta with Wye to Delta PTs 5 = Wye with Wye to Delta PTs Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Potential (Voltage) Transformer Ratio The E300 Electronic Overload Relay sensing module catalog number 193-ESM-VIG-30A-CT can be used with step down potential (voltage) transformers. PT Primary (Parameter 353) and PT Secondary (Parameter 354) allows you to identify the turns ratio of the step down potential (voltage) transformers in use. The E300 Electronic Overload Relay will automatically adjust the measured voltage based on these two configuration parameters. Use the primary voltage for your voltage protection settings. Table 17 - PT Primary (Parameter 353) Default Value 480 Minimum Value 1 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Amps Table 18 - PT Secondary (Parameter 354) Default Value 480 Minimum Value 165535 Maximum Value Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Amps Rockwell Automation Publication 193-UM015C-EN-P - December 2014 51 Chapter 2 Installation and Wiring Control Circuits ATTENTION: Do not exceed the ratings of the E300 Electronic Overload Relay’s output and trip relay. If the coil current or voltage of the contactor exceeds the overload relay’s ratings, an interposing relay must be used. ATTENTION: When the power is applied to the E300 Electronic Overload Relay’s A1 and A2 terminals, the N.O. relay contact that is assigned as a Trip Relay closes after approximately 2 seconds if no trip condition exists. ATTENTION: More control circuit protection may be required. See the applicable electrical codes. The E300 Electronic Overload Relay can provide motor control logic for many different types of motor starters (see Chapter 5 for more information on Operating Modes). By default, the E300 is configured for the Overload-Network operating mode. The following wiring diagrams are typical control circuits for Non-Reversing and Reversing Motor starters that use the Overload-Network operating mode when Relay 0 (terminals R03 and R04) is configured to be a normally closed Trip Relay. Full-Voltage Non-Reversing Starter (with Network Control) Figure 38 - NEMA Nomenclature Relay 0 Configured as a Trip Relay 1 Relay 1 R13 R14 A1 M A2 R03 1 Contact shown with supply voltage applied. 52 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 R04 Installation and Wiring Chapter 2 Figure 39 - CENELEC Nomenclature L1 Relay 1 R13 R14 Relay 0 Configured as a Trip Relay 2 R03 R04 A1 K A2 N 2 Contact shown with supply voltage applied. Full-Voltage Reversing Starter (with Network Control) Figure 40 - NEMA Nomenclature Relay 0 Configured as a Trip Relay 1 Relay 1 REV R13 R14 A1 FOR A2 95 96 Relay 2 FOR R23 R24 A1 REV A2 1 Contact shown with supply voltage applied. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 53 Chapter 2 Installation and Wiring Figure 41 - CENELEC Nomenclature L1 Relay 0 Configured as a 2 Trip Relay R03 R04 Relay 1 R13 R23 Relay 2 R24 R14 K1 K2 A1 K1 A2 A1 K2 A2 2 Contact shown with supply voltage applied. N 54 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 3 Diagnostic Station Introduction The E300 Electronic Overload Relay supports a Diagnostic Station on the E300 Expansion Bus (requires Control Module firmware v3.000 and higher). The Diagnostic Station allows you to view any E300 parameter and edit any configuration parameter. This chapter explains the Diagnostic Station’s navigation keys, how to view a parameter, how to edit a configuration parameter, and the Diagnostic Station’s programmable display sequence. Navigation Keys The E300 Diagnostic Station has five navigation keys that are used to navigate through the Diagnostic Station’s display menu system and edit configuration parameters. Key Displaying a Parameter Name Description Up Arrow Down Arrow Scroll through the display parameters or groups. Increment or decrement values. Escape Back one step in the navigation menu. Cancel a change to a configuration parameter value Select Select the next bit when viewing a bit enumerated parameter. Select the next digit when editing a configuration value. Select the next bit when editing a bit enumerated parameter. Enter Start the navigation menu. Advance one step in the navigation menu. Display the description for a bit enumerated parameter. Edit a configuration parameter value. Save the change to the configuration parameter value. The E300 Diagnostic Station allows you to view parameters using a group menu system or by a linear list. To start the navigation menu, press the key. The menu prompts you to view parameters by groups, parameters in a linear list, or E300 system information. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 55 Chapter 3 Diagnostic Station Parameter Group Navigation To start the navigation menu, press the key. Use the select the Groups navigation method and press Use the or keys to . or keys to select the parameter group to display and press or keys to view the parameters that are associated with that . Use the group. When viewing a bit enumerated parameter, press each bit. Press Press 56 to view the next bit. Press to view the description of to return to the parameter. to return to the parameter group navigation system. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Diagnostic Station Chapter 3 If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence. Linear List Navigation To start the navigation menu, press the key. Use the select the Linear List navigation method and press Use the and press Use the or and keys to . keys to select the parameter number to display . or keys to view the next sequential parameter. When viewing a bit enumerated parameter, press each bit. Press or to view the next bit. Press Rockwell Automation Publication 193-UM015C-EN-P - December 2014 to view the description of to return to the parameter. 57 Chapter 3 Diagnostic Station Press to return to the linear list navigation system. If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence. System Info The E300 Diagnostic Station can display firmware revision information, view the time and date of the E300 virtual clock, and edit the time and date of the E300 virtual clock. To view E300 system information, start the navigation menu by pressing key. Use the or keys to select System Info and press . Use the or keys to view the E300 system information. To edit the system date or time, press keys to select the new value. Press to save the new system values or press restore the previous system values. 58 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 to modify the value. Use the or to select the next system value. Press to cancel the modification and Diagnostic Station Press Chapter 3 to return to the navigation menu. If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence. Editing Parameters Editing a Configuration Parameter The E300 Diagnostic Station allows you to edit configuration parameters using a group menu system or by a linear list. To start the navigation menu, press the key. You will be prompted to view parameters by groups, parameters in a linear list, or E300 system information. Choose the appropriate method and navigate to the parameter to be modified. Editing a Numeric Parameter To edit a configuration parameter, press the the or values or press Press key to modify the value. Use keys to select the new value. Press to save the new system to cancel the modification and restore the previous value. to return to the navigation menu. If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 59 Chapter 3 Diagnostic Station Editing a Bit Enumerated Parameter When editing a bit enumerated parameter, press the description of each bit. Use the or key to view the keys to select the new bit value. Press to edit the next bit. Press to save the new value or press cancel the modification and restore the previous value. Press to to return to the navigation menu. If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence. Programmable Display Sequence Display Sequence The E300 Diagnostic Station sequentially displays up to seven screens every five seconds. • Three-phase current • Three-phase voltage • Total power • User-defined screen 1 • User-defined screen 2 • User-defined screen 3 • User-defined screen 4 The three-phase voltage and total power screens are only included in the sequence when the E300 Electronic Overload Relay has a voltage, current, and ground fault current (VIG)-based Sensing Module. 60 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Diagnostic Station Chapter 3 The user-defined screens allow you to select up to two parameters per screen. Refer to Diagnostic Station User-defined Screens on page 86 to configure the Screen# and Parameter# (Parameters 428…435). If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the Diagnostic Station will automatically cancel any editing modifications, restore the previous value, and return to its programmable display sequence. Stopping the Display Sequence To stop the display sequence, press sequence through the displays. Press sequence. . Use the or keys to manually to return to the automatic display If you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station automatically returns to its programmable display sequence. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 61 Chapter 3 Diagnostic Station Automatic Trip and Warning Screens When the E300 Electronic Overload Relay is in a trip or warning state, the E300 Diagnostic Station automatically displays the trip or warning event. Press any of the navigation keys ( the automatic display sequence. , , , , or ) to return to When the trip or warning event clears, the E300 Diagnostic Station automatically returns to its programmable display sequence. If a different parameter is displayed and you do not press any navigation keys for a period that is Defined by Display Timeout (Parameter 436), then the E300 Diagnostic Station will automatically return to the trip or warning screen if the trip or warning event is not cleared. 62 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 4 System Operation and Configuration Introduction This chapter provides instructions for operating and configuring an E300 Electronic Overload Relay system. Settings for Device Modes, Option Match, Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an introduction to Operating Modes are included in this chapter. Device Modes The E300 Electronic Overload Relay has five device modes to validate configuration of the device and limit when you can configure the E300 Electronic Overload Relay, perform a firmware update, and issue commands. • Administration Mode • Operation Mode • Run Mode • Test Mode • Invalid Configuration Mode Administration Mode Administration Mode is a maintenance mode for the E300 Electronic Overload Relay, which allows you to configure parameters, modify security policies, enable web servers (see page 378 to enable the EtherNet/IP web server), perform firmware updates, and issue commands. Follow these steps to enter into Administration Mode: 1. Set the rotary dials on the E300 Communication Module to the following values – For EtherNet/IP set the rotary dials to 0-0-0 – For DeviceNet set the rotary dials to 7-7 2. Cycle power on the E300 Electronic Overload Relay After commissioning activities and maintenance tasks are completed, return the E300 Electronic Overload Relay back to Operation or Run Mode by setting the rotary dials of the E300 communication module back to its previous positions and cycle power. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 63 Chapter 4 System Operation and Configuration Operation Mode Operation Mode is a standby mode for the E300 Electronic Overload Relay in which the E300 is ready to help protect an electric motor and no electrical current has been detected. You can modify configuration parameters, update firmware, and issue commands if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations will be flashing green and bit 14 in Device Status 0 (Parameter 20) is set to 1 when the device is in Operation Mode. Table 19 - Operation Mode Bit Function Detail — Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Trip Present X X X X X X X X X X X X X Warning Present Invalid Configuration Current Present GFCurrent Present Voltage Present Emergency Start Enabled DeviceLogix Enabled Feedback Timeout Enabled Operator Station Present Voltage Sensing Present Intern Ground Fault Sensing Present Extern Ground Fault Sensing Present PTC Sensing X Ready Reserved Run Mode Run Mode is an active mode for the E300 Electronic Overload Relay in which the E300 is sensing electrical current and is actively protecting an electric motor. Only non-motor protection configuration parameters can be modified if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations will be solid green and bits 3, 4, and/or 5 in Device Status 0 (Parameter 20) are set to 1 when the device is in Run Mode. 64 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Trip Present X X X X X X X X X X X X X Warning Present Invalid Configuration Current Present GFCurrent Present Voltage Present Emergency Start Enabled DeviceLogix Enabled Feedback Timeout Enabled Operator Station Present Voltage Sensing Present Intern Ground Fault Sensing Present Extern Ground Fault Sensing Present PTC Sensing X Ready Reserved Test Mode Test Mode is used by installers of motor control centers who are testing and commissioning motor starters with an automation system. A digital input of the E300 Electronic Overload Relay is assigned to monitor the motor control center enclosure’s Test Position. The Input Assignments (Parameters 196…201) are described later in this chapter. Anyone commissioning motor starters in an automation system can put their motor control center enclosure into the Test Position to activate Test Mode and verify that the digital inputs and relay outputs of the E300 Electronic Overload Relay are operating properly with the motor starter without energizing power to the motor. If the E300 Electronic Overload Relay senses current or voltage in Test Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip. Invalid Configuration Mode Invalid Configuration Mode is an active mode for the E300 Electronic Overload Relay in which the E300 is in a tripped state due to invalid configuration data. Invalid Configuration Parameter (Parameter 38) indicates the parameter number that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies the reason for Invalid Configuration Mode. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 65 Chapter 4 System Operation and Configuration Table 21 - Invalid Configuration Cause (Parameter 39) Code 0 1 2 3 4 5 Description No Error Value over maximum value Value under minimum value Illegal value L3 Current detected (for single-phase applications) CopyCat error The Trip/Warn LED on the Communication Module and Operator Stations will be flashing a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration Mode. Table 22 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Trip Present X X X X X X X X X X X X X Warning Present Invalid Configuration Current Present GFCurrent Present Voltage Present Emergency Start Enabled DeviceLogix Enabled Feedback Timeout Enabled Operator Station Present Voltage Sensing Present Intern Ground Fault Sensing Present Extern Ground Fault Sensing Present PTC Sensing X Ready Reserved To return to Operation/Run Mode, place a valid configuration value in the parameter identified by Invalid Configuration Parameter (Parameter 38) and Invalid Configuration Cause (Parameter 39). Reset the trip state of the E300 Electronic Overload Relay by pressing the blue reset button on the Communication Module, via network communications, with the internal web server of the EtherNet/IP communications module, or by an assigned digital input. Option Match 66 Due to the modular nature of the E300 Electronic Overload Relay, you can enable the Option Match feature to ensure that the options that were expected for the motor protection application are the ones that are present on the E300 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Electronic Overload Relay system. You can configure an option mismatch to cause a protection trip or provide a warning within the E300. Enable Option Match Protection Trip (Parameter 186) To enable the E300 Electronic Overload Relay’s Option Match feature to cause a protection trip in the event of an option mismatch, place a (1) in bit position 8 of Parameter 186 (Control Trip Enable). You can select the specific option match features to cause a protection trip in Parameter 233 (Option Match Action). Table 23 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable (Parameter 186) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X X X X X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Function Test Trip Enable PTC Trip Enable DeviceLogix Trip Enable Operator Station Trip Enable Remote Trip Enable Blocked Start Trip Enable Hardware Fault Trip Enable Configuration Trip Enable Option Match Trip Enable Feedback Timeout Trip Enable Expansion Bus Trip Enable Reserved Reserved Nonvolatile Memory Trip Enable Ready Reserved 67 Chapter 4 System Operation and Configuration Enable Option Match Protection Warning (Parameter 192) To enable the E300 Electronic Overload Relay’s Option Match feature to cause a warning in the event of an option mismatch, place a (1) in bit position 8 of Parameter 192 (Control Warning Enable). You can select the specific option match features to cause a warning in Parameter 233 (Option Match Action). Table 24 - Enable Option Match Protection Warning Bit Function Detail— Control Warning Enable (Parameter 192) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 X X X X X X 1 0 Function Reserved Reserved DeviceLogix Warning Enable Reserved Reserved Reserved Reserved Reserved Option Match Warning Enable Feedback Timeout Warning Enable Expansion Bus Warning Enable Number Of Starts Warning Enable Operating Hours Warning Enable Reserved Control Module Type (Parameter 221) The E300 Electronic Overload Relay offers six different control modules. Place the value of the expected control module into Parameter 221. A value of (0) disables the Option Match feature for the control module. Table 25 - Control Module Type (Parameter 221) Code 0 1 2 3 4 5 6 68 Description Ignore 6 Inputs, 24V DC / 3 Relay Outputs 4 Inputs, 110-120V AC 50/60Hz / 3 Relay Outputs 4 Inputs, 220-240V AC 50/60Hz / 3 Relay Outputs 4 Inputs, 24V DC / 2 Relay Outputs / External Ground Fault / PTC 2 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs / External Ground Fault / PTC 2 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs / External Ground Fault / PTC Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Control Module Cat. No. — 193-EIO-63-24D 193-EIO-43-120 193-EIO-43-240 193-EIOGP-42-24D 193-EIOGP-22-120 193-EIOGP-22-240 System Operation and Configuration Chapter 4 Sensing Module Type (Parameter 222) The E300 Electronic Overload Relay offers 12 different sensing modules. Place the value of the expected sensing module into Parameter 222. A value of (0) disables the Option Match feature for the sensing module. Table 26 - Sensing Module Type (Parameter 222) Code 0 1 2 3 4 5 6 7 8 9 10 11 12 Description Ignore Voltage / Current 0.5…30 A / Ground Fault Voltage / Current 6…60 A / Ground Fault Voltage / Current 10…100 A / Ground Fault Voltage / Current 20…200 A / Ground Fault Current 0.5…30 A / Ground Fault Current 6…60 A / Ground Fault Current 10…100 A / Ground Fault Current 20…200 A / Ground Fault Current 0.5…30 A Current 6…60 A Current 10…100 A Current 20…200 A Sensing Module Cat. No. — 193-ESM-VIG-30A-__ or 592-ESM-VIG-30A-__ 193-ESM-VIG-60A-__ or 592-ESM-VIG-60A-__ 193-ESM-VIG-100A-__ or 592-ESM-VIG-100A-__ 193-ESM-VIG-200A-__ or 592-ESM-VIG-200A-__ 193-ESM-IG-30A-__ or 592-ESM-IG-30A-__ 193-ESM-IG-60A-__ or 592-ESM-IG-60A-__ 193-ESM-IG-100A-__ or 592-ESM-IG-100A-__ 193-ESM-IG-200A-__ or 592-ESM-IG-200A-__ 193-ESM-I-30A-__ or 592--ESM-I-30A-__ 193-ESM-I-60A-__ or 592--ESM-I-60A-__ 193-ESM-I-100A-__ or 592--ESM-I-100A-__ 193-ESM-I-200A-__ or 592--ESM-I-200A-__ Communication Module Type (Parameter 223) The E300 Electronic Overload Relay offers two different communication modules. Place the value of the expected communication module into Parameter 223. A value of (0) disables the Option Match feature for the communication module. Table 27 - Communication Module Type (Parameter 223) Code 0 1 2 Description Ignore EtherNet/IP with Dual Port Switch supporting DLR DeviceNet Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Communication Module Cat. No. — 193-ECM-ETR 193-ECM-DNT 69 Chapter 4 System Operation and Configuration Operator Station Type (Parameter 224) The E300 Electronic Overload Relay offers two different types of operator stations. Place the value of the expected operator station into Parameter 224. A value of (0) disables the Option Match feature for the operator station. A value of (1), “No Operator Station”, makes the operator station not allowed on the Expansion Bus and prevents you from connecting an operator station to the E300 Electronic Overload Relay system. Table 28 - Operator Station Type (Parameter 224) Code 0 1 2 3 Description Ignore No Operator Station (Operator Station Not Allowed) Control Station Diagnostic Station with LCD Operator Station Cat. No. — — 193-EOS-SCS 193-EOS-SDS Digital I/O Expansion Module 1 Type (Parameter 225) The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 1. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 1 into Parameter 225. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 1 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 1 to the E300 Electronic Overload Relay system. Table 29 - Digital I/O Expansion Module 1 Type (Parameter 225) Code 0 1 2 3 4 70 Description Ignore No Digital I/O Expansion Module (Digital I/O Expansion Module Not Allowed) 4 Inputs, 24V DC / 2 Relay Outputs 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Digital I/O Expansion Module Cat. No. — — 193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240 System Operation and Configuration Chapter 4 Digital I/O Expansion Module 2 Type (Parameter 226) The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 2. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 2 into Parameter 226. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 2 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 2 to the E300 Electronic Overload Relay system. Table 30 - Digital I/O Expansion Module 2 Type (Parameter 226) Code 0 1 2 3 4 Description Ignore No Digital I/O Expansion Module (Digital I/O Expansion Module Not Allowed) 4 Inputs, 24V DC / 2 Relay Outputs 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs Digital I/O Expansion Module Cat. No. — — 193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240 Digital I/O Expansion Module 3 Type (Parameter 227) The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 3. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 3 into Parameter 227. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 3 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 3 to the E300 Electronic Overload Relay system. Table 31 - Digital I/O Expansion Module 3 Type (Parameter 227) Code 0 1 2 3 4 Description Ignore No Digital I/O Expansion Module (Digital I/O Expansion Module Not Allowed) 4 Inputs, 24V DC / 2 Relay Outputs 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs Digital I/O Expansion Module Cat. No. — — 193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240 Digital I/O Expansion Module 4 Type (Parameter 228) The E300 Electronic Overload Relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Rockwell Automation Publication 193-UM015C-EN-P - December 2014 71 Chapter 4 System Operation and Configuration Digital I/O expansion module set to Digital Module 4. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 4 into Parameter 228. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module ”, makes the Digital I/O expansion module set to Digital Module 4 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 4 to the E300 Electronic Overload Relay system. Table 32 - Digital I/O Expansion Module 4 Type (Parameter 228) Code 0 1 2 3 4 Description Ignore No Digital I/O Expansion Module (Digital I/O Expansion Module Not Allowed) 4 Inputs, 24V DC / 2 Relay Outputs 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs Digital I/O Expansion Module Cat. No. — — 193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240 Analog I/O Expansion Module 1 Type (Parameter 229) The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 1. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 1 into Parameter 229. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 1 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 1 to the E300 Electronic Overload Relay system. Table 33 - Analog I/O Expansion Module 1 Type (Parameter 229) Code 0 1 2 72 Description Ignore No Analog I/O Expansion Module (Analog I/O Expansion Module Not Allowed) 3 Universal Analog Inputs / 1 Analog Output Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Analog I/O Expansion Module Cat. No. — — 193-EXP-AIO-31 System Operation and Configuration Chapter 4 Analog I/O Expansion Module 2 Type (Parameter 230) The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 2. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 2 into Parameter 230. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 2 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 2 to the E300 Electronic Overload Relay system. Table 34 - Analog I/O Expansion Module 2 Type (Parameter 230) Code 0 1 2 Description Ignore No Analog I/O Expansion Module (Analog I/O Expansion Module Not Allowed) 3 Universal Analog Inputs / 1 Analog Output Analog I/O Expansion Module Cat. No. — — 193-EXP-AIO-31 Analog I/O Expansion Module 3 Type (Parameter 231) The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 3. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 3 into Parameter 231. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 3 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 3 to the E300 Electronic Overload Relay system. Table 35 - Analog I/O Expansion Module 3 Type (Parameter 231) Code 0 1 2 Description Ignore No Analog I/O Expansion Module (Analog I/O Expansion Module Not Allowed) 3 Universal Analog Inputs / 1 Analog Output Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Analog I/O Expansion Module Cat. No. — — 193-EXP-AIO-31 73 Chapter 4 System Operation and Configuration Analog I/O Expansion Module 4 Type (Parameter 232) The E300 Electronic Overload Relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 4. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 4 into Parameter 232. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 4 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 4 to the E300 Electronic Overload Relay system. Table 36 - Analog I/O Expansion Module 4 Type (Parameter 232) Code 0 Description Ignore No Analog I/O Expansion Module (Analog I/O Expansion Module Not Allowed) 3 Universal Analog Inputs / 1 Analog Output 1 2 Analog I/O Expansion Module Cat. No. — — 193-EXP-AIO-31 Option Match Action (Parameter 233) The Option Match feature for the E300 Electronic Overload Relay allows you to specify an action when there is an option mismatch – Protection Trip or Warning. Place a (0) in the appropriate bit position for a warning, and place a (1) in the appropriate bit position to cause a protection trip if there is an option mismatch. Table 37 - Option Match Action (Parameter 233) Bit Function Detail Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X X X X X X X X X X X 74 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Function Control Module Mismatch Action Sensing Module Mismatch Action Communication Module Mismatch Action Operator Station Mismatch Action Digital Module 1 Mismatch Action Digital Module 2 Mismatch Action Digital Module 3 Mismatch Action Digital Module 4 Mismatch Action Analog Module 1 Mismatch Action Analog Module 2 Mismatch Action Analog Module 3 Mismatch Action Analog Module 4 Mismatch Action System Operation and Configuration Chapter 4 The E300 Electronic Overload Relay has a security policy that can be used to prevent anyone with malicious intent to potentially damage a motor or piece of equipment. By default, you can only modify the security policy when the E300 Electronic Overload Relay is in Administration Mode (see page 63 to learn how to enable Administration Mode). Security Policy Table 38 - Security Policy (Parameter 211) Bit Function Detail Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X X X Function Device Configuration Enable Device Reset Enable Firmware Update Enable Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Security Policy Config Enable Device Configuration Policy The Device Configuration Policy allows you to send external message instructions via a communications network to write values to configuration parameters. When this policy is disabled, all external message instructions with configuration data will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode. Device Reset Policy The Device Reset Policy allows you to send external message instruction via a communications network to perform a soft device reset when the E300 Electronic Overload Relay is in Operation Mode. When this policy is disabled, all external reset message instructions will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 75 Chapter 4 System Operation and Configuration Firmware Update Policy The Firmware Update Policy allows you to update the internal firmware of the communication module and control module via ControlFlash when the E300 Electronic Overload Relay is in Operation Mode. When this policy is disabled, firmware updates will return a communications error when the E300 Electronic Overload Relay is in Operation Mode or Run Mode. Security Configuration Policy The Security Configuration Policy allows you to modify the Security Policy of the E300 Electronic Overload Relay in Operation Mode. When this policy is disabled, the Security Policy can only be modified when the E300 Electronic Overload Relay is in Administration Mode. I/O Assignments The E300 Electronic Overload Relay has native digital inputs and relay outputs in the Control Module. This I/O can be assign to dedicated functions. the following sections list the function assignments for the available Control Module I/O. Input Pt00 Assignment (Parameter 196) Input Pt00 Assignment (Parameter 196) allows you to assign this digital input for the following functions: Table 39 - Input Pt00 Assignment (Parameter 196) Value 76 Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Input Pt01 Assignment (Parameter 197) Input Pt01 Assignment (Parameter 197) allows you to assign this digital input for the following functions: Table 40 - Input Pt01 Assignment (Parameter 197) Value Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Input Pt02 Assignment (Parameter 198) Input Pt02 Assignment (Parameter 198) allows you to assign this digital input for the following functions: Table 41 - Input Pt02 Assignment (Parameter 198) Value Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Rockwell Automation Publication 193-UM015C-EN-P - December 2014 77 Chapter 4 System Operation and Configuration Input Pt03 Assignment (Parameter 199) Input Pt03 Assignment (Parameter 199) allows you to assign this digital input for the following functions: Table 42 - Input Pt03 Assignment (Parameter 199) Value Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Input Pt04 Assignment (Parameter 200) Input Pt04 Assignment (Parameter 200) allows you to assign this digital input for the following functions: Table 43 - Input Pt04 Assignment (Parameter 200) Value 78 Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Input Pt05 Assignment (Parameter 201) Input Pt05 Assignment (Parameter 201) allows you to assign this digital input for the following functions: Table 44 - Input Pt05 Assignment (Parameter 201) Value Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command 6 Test Mode Enable Test Mode monitoring 7 L1 Line Loss Arm Activate L1 Line Loss Protection 8 L2 Line Loss Arm Activate L2 Line Loss Protection 9 L3 Line Loss Arm Activate L3 Line Loss Protection 10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection 11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection 12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection 13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection Rockwell Automation Publication 193-UM015C-EN-P - December 2014 79 Chapter 4 System Operation and Configuration Output Pt00 Assignment (Parameter 202) Output Pt00 Assignment (Parameter 202) allows you to assign this relay output for the following functions: Table 45 - Output Pt00 Assignment (Parameter 202) Value 0 Assignment Normal 1 Trip Relay 2 Control Relay 3 Trip Alarm 4 Warning Alarm 5 Monitor L1 Trip Relay(1) 6 Monitor L2 Trip Relay(1) 7 Monitor L3 Trip Relay(1) 8 Monitor L1 Control Relay(1) 9 Monitor L2 Control Relay(1) 10 Monitor L3 Control Relay(1) Description Function as a relay output Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued. Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued. Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears. Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. (1) Requires Control Module firmware v3.000 or higher 80 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Output Pt01 Assignment (Parameter 203) Output Pt01 Assignment (Parameter 203) allows you to assign this relay output for the following functions: Table 46 - Output Pt01 Assignment (Parameter 203) Value 0 Assignment Normal 1 Trip Relay 2 Control Relay 3 Trip Alarm 4 Warning Alarm 5 Monitor L1 Trip Relay(1) 6 Monitor L2 Trip Relay(1) 7 Monitor L3 Trip Relay(1) 8 Monitor L1 Control Relay(1) 9 Monitor L2 Control Relay(1) 10 Monitor L3 Control Relay(1) Description Function as a relay output Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued. Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued. Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears. Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. (1) Requires Control Module firmware v3.000 or higher Rockwell Automation Publication 193-UM015C-EN-P - December 2014 81 Chapter 4 System Operation and Configuration Output Pt02 Assignment (Parameter 204) Output Pt02 Assignment (Parameter 204) allows you to assign this relay output for the following functions: Table 47 - Output Pt02 Assignment (Parameter 204) Value 0 Assignment Normal 1 Trip Relay 2 Control Relay 3 Trip Alarm 4 Warning Alarm 5 Monitor L1 Trip Relay(1) 6 Monitor L2 Trip Relay(1) 7 Monitor L3 Trip Relay(1) 8 Monitor L1 Control Relay(1) 9 Monitor L2 Control Relay(1) 10 Monitor L3 Control Relay(1) Description Function as a relay output Function as a normally closed contact until the E300 is in a tripped state in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 enters into a tripped state the Control Relay opens and remains open until a trip reset is issued. Function as a normally open contact until the E300 is in a tripped state in which the relay closes. The Trip Alarm remains closed until a trip reset is issued. Function as a normally open contact until the E300 is in a protection warning state in which the relay closes. The Warning Alarm remains closed until the protection warning clears. Function as a normally closed contact until the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a normally closed contact until the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss in which the relay opens. The Trip Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L1 Under Current, L1 Over Current, or L1 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L2 Under Current, L2 Over Current, or L2 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. Function as a combination Normal and Trip Relay. The Control Relay is in a normally open state until the relay is commanded to close by communications or via a DeviceLogix program. When the E300 is in a tripped state for a L3 Under Current, L3 Over Current, or L3 Line Loss, the relay opens. The Control Relay remains open until a trip reset is issued. (1) Requires Control Module firmware v3.000 or higher Table 48 - Activate FLA2 with Output Relay (Parameter 209) Activate FLA2 with Output Relay (Parameter 209) allows you to activate the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms when the assigned output relay is in an energized state. Table 49 - Activate FLA2 with Output Relay (Parameter 209) Value 0 1 2 3 Expansion Bus Fault 82 Description Disable Pt00 Output Pt01 Output Pt02 Output The E300 Electronic Overload Relay’s expansion bus can be used to expand the I/O capabilities of the E300 Electronic Overload Relay with the addition of digital and analog expansion I/O modules. The Expansion Bus Fault allows you to have the E300 Electronic Overload Relay go into a Trip or Warning state when Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 established Expansion Bus communications is disrupted between the Control Module and any digital and analog expansion I/O modules. The Expansion Bus Fault is used when the Option Match feature is not enabled for the digital and/or analog expansion I/O modules. The Expansion Bus Fault only monitors for communication disruptions between the Control Module and digital and/or analog expansion I/O modules. Expansion bus communication disruptions between the Control Module and Operator Station do not affect the Expansion Bus fault. Expansion Bus Trip Expansion Bus Trip is enabled by setting Control Trip Enable (Parameter 186) bit 10 to 1. When communications is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E300 Electronic Overload Relay will go into a tripped state in which the Trip/Warn LED on the Communication Module and Operator station will blink a red 3 long and 11 short blinking pattern. Table 50 - Expansion Bus Trip Bit Function Detail— Control Trip Enable (Parameter 186) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X X X X X X X X X X X X Function Test Trip Enable PTC Trip Enable DeviceLogix Trip Enable Operator Station Trip Enable Remote Trip Enable Blocked Start Trip Enable Hardware Fault Trip Enable Configuration Trip Enable Option Match Trip Enable Feedback Timeout Trip Enable Expansion Bus Trip Enable Reserved Reserved Nonvolatile Memory Trip Enable Ready Reserved To return to Operation/Run Mode, verify that the expansion bus cables are properly plugged into the Bus In and Bus Out ports of all of the expansion modules. When all of the expansion I/O modules’ status LEDs are solid green, reset the trip state of the E300 Electronic Overload Relay by pressing the blue reset button on the Communication Module, via network communications, with the internal web server of the EtherNet/IP communications module, or by an assigned digital input. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 83 Chapter 4 System Operation and Configuration Expansion Bus Warning Expansion Bus Warning is enabled by setting Control Warning Enable (Parameter 192) bit 10 to 1. When communications is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E300 Electronic Overload Relay will go into a warning state in which the Trip/Warn LED on the Communication Module and Operator station will blink a yellow 3 long and 11 short blinking pattern. Table 51 - Expansion Bus Warning Bit Function Detail— Control Warning Enable (Parameter 192) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function Reserved X X X PTC Warning Enable DeviceLogix Warning Enable Operator Station Warning Enable Reserved Reserved Reserved Reserved X X Option Match Warning Enable Feedback Timeout Warning Enable X Expansion Bus Warning Enable X Number Of Starts Warning Enable X Operating Hours Warning Enable Reserved To return to Operation/Run Mode, verify that the expansion bus cables are properly plugged into the Bus In and Bus Out ports of all of the expansion modules. When all of the expansion I/O modules’ status LEDs are solid green, the warning state of the E300 Electronic Overload Relay will automatically clear. Emergency Start In an emergency, it may be necessary to start a motor even if a protection fault or a communication fault exists. The trip condition may be the result of a thermal overload condition or the number of starts exceeded its configuration. These conditions can be overridden using the Emergency Start feature of the E300 Electronic Overload Relay. IMPORTANT Activating Emergency Start inhibits overload and blocked start protection. Running in this mode can cause equipment overheating and fire. To enable the Emergency Start feature in the E300 Electronic Overload Relay set the Emergency Start Enable (Parameter 216) to Enable. 84 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 52 - Emergency Start (Parameter 216) Value 0 1 Description Disable Enable Configure one of the Ptxx Input Assignments (Parameters 196…201) to Emergency Start and activate the corresponding digital input. Table 53 - Emergency Start Input PTXX Assignment (Parameters 196…201) Value Assignment Description 0 Normal Function as a digital input 1 Trip Reset Reset the E300 when it is in a tripped state 2 Remote Trip Force the E300 to go into a tripped state 3 Activate FLA2 Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms 4 Force Snapshot Force the E300 to update its Snapshot log 5 Emergency Start Issue an Emergency Start command You can also use a network command to activate the Emergency Start feature. For the EtherNet/IP communications module, you would set the Emergency Start bit to 1 in Output Assembly 144. See EtherNet/IP Communications on page 369 for more information on EtherNet/IP communications. When the Emergency Start feature is active, the following actions occur in the E300 Electronic Overload Relay: • Protection trips are ignored • Output relays configured as Trip Relays are put into closed state • Normal operation resumes with any Normal or Control Relay assigned output relay • The Emergency Start Active bit is set to 1 in Device Status 0 (Parameter 20) bit 6 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 85 Chapter 4 System Operation and Configuration Table 54 - Emergency Start Bit Function Detail— Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 X X X X X X X X X X X X X X X Diagnostic Station Userdefined Screens Function Trip Present Warning Present Invalid Configuration Current Present GFCurrent Present Voltage Present Emergency Start Enabled DeviceLogix Enabled Feedback Timeout Enabled Operator Station Present Voltage Sensing Present Intern Ground Fault Sensing Present Extern Ground Fault Sensing Present PTC Sensing Ready Reserved The E300 Electronic Overload Relay’s Diagnostic Station has four user-defined screens that are part of the Diagnostic Station’s display sequence in which you can define up to two parameters per screen. User-defined Screen 1 User-defined Screen 1 – Parameter 1 User-defined Screen 1 - Parameter 1 (Parameter 428) is the E300 parameter number to display for the first parameter in user-defined screen 1. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 55 - Screen 1 - Parameter 1 (Parameter 428) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1 0 560 UINT 2 1 В User-defined Screen 1 – Parameter 2 User-defined Screen 1 - Parameter 2 (Parameter 429) is the E300 parameter number to display for the second parameter in user-defined screen 1. You can select one of the 560 available E300 Electronic Overload Relay parameters. 86 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 56 - Screen 1 - Parameter 2 (Parameter 429) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 50 0 560 UINT 2 1 В User-defined Screen 2 User-defined Screen 2 – Parameter 1 User-defined Screen 2 - Parameter 1 (Parameter 430) is the E300 parameter number to display for the first parameter in user-defined screen 2. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 57 - Screen 2 - Parameter 1 (Parameter 430) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 2 0 560 UINT 2 1 В User-defined Screen 2 – Parameter 2 User-defined Screen 2 - Parameter 2 (Parameter 431) is the E300 parameter number to display for the second parameter in user-defined screen 2. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 58 - Screen 2 - Parameter 2 (Parameter 431) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 3 0 560 UINT 2 1 В Rockwell Automation Publication 193-UM015C-EN-P - December 2014 87 Chapter 4 System Operation and Configuration User-defined Screen 3 User-defined Screen 3 – Parameter 1 User-defined Screen 3 - Parameter 1 (Parameter 432) is the E300 parameter number to display for the first parameter in user-defined screen 3. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 59 - Screen 3 - Parameter 1 (Parameter 432) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 51 0 560 UINT 2 1 В User-defined Screen 3 – Parameter 2 User-defined Screen 3 - Parameter 2 (Parameter 433) is the E300 parameter number to display for the second parameter in user-defined screen 3. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 60 - Screen 3 - Parameter 2 (Parameter 433) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 52 0 560 UINT 2 1 В User-defined Screen 4 User-defined Screen 4 – Parameter 1 User-defined Screen 4 - Parameter 1 (Parameter 434) is the E300 parameter number to display for the first parameter in user-defined screen 4. You can select one of the 560 available E300 Electronic Overload Relay parameters. Table 61 - Screen 4 - Parameter 1 (Parameter 434) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 88 38 0 560 UINT 2 1 В Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 User-defined Screen 4 – Parameter 2 User-defined Screen 4 - Parameter 2 (Parameter 435) is the E300 parameter number to display for the second parameter in user-defined screen 4. You can select one of the 560 available E300 Electronic Overload Relay parameters. ScreenВ 4 ‐ ParameterВ 2В (ParameterВ 435) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 39 0 560 UINT 2 1 В Display Timeout Display Timeout (Parameter 436) defines the time duration in which there is no display navigation activity, and the E300 Diagnostic Station returns to its normal display sequence. Any configuration parameters that were left in an edit state will be canceled. A value of zero disables the display timeout function. Table 62 - Display Timeout (Parameter 436) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 300 0 65535 UINT 2 1 Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 89 Chapter 4 System Operation and Configuration Analog I/O Expansion Modules The E300 Electronic Overload Relay supports up to four Analog I/O Expansion Modules on the E300 Expansion Bus. The E300 Analog Expansion Module has three independent universal inputs and one analog output. Analog Input Channels The universal analog inputs can accept the following analog signals: • Current – 4…20 mA – 0…20 mA • Voltage – 0…10V DC – 1…5V DC – 0…5V DC • 2-Wire or 3-Wire RTD Sensors – 100 О©, 200 О©, 500 О©, 1000 О© Pt 385 – 100 О©, 200 О©, 500 О©, 1000 О© Pt 3916 – 10 О© Cu 426 – 100 О© Ni 618 – 120 О© Ni 672 – 604О© NiFe 518 • Resistance – 0…150 О© – 0…750 О© – 0…3000 О© – 0…6000 О© (PTC and NTC Sensors) The analog inputs can report data in four different formats. Table 63 through Table 66 display the data ranges for all of the available analog input types for the four available data formats. Table 63 - Analog Input Data Format for Current Input Type Input Range Input Value 4…20 mA 0…20 mA 90 21.00 mA 20.00 mA 4.00 mA 3.00 mA 21.00 mA 20.00 mA 0.00 mA 0.00 mA Condition High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit Engineering Units 21000 20000 4000 3000 21000 20000 0 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Engineering Units x 10 2100 2000 400 300 2100 2000 0 0 Raw / Proportional 32767 32767 -32768 -32768 32767 32767 -32768 -32768 PID 17407 16383 0 -1024 17202 16383 0 0 System Operation and Configuration Chapter 4 Table 64 - Analog Input Data Format for Voltage Input Type Input Range Input Value 0…10 V DC 1…5 V DC 0…5V DC 10.50V DC 10.00V DC 0.00V DC 0.00V DC 5.25V DC 5.00V DC 1.00V DC 0.50V DC 5.25V DC 5.00V DC 0.00V DC 0.00V DC Condition High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit Engineering Units 10500 10000 0 0 5250 5000 1000 500 5250 5000 0 0 Engineering Units x 10 1050 1000 0 0 525 500 100 50 525 500 0 0 Raw / Proportional 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 PID 17202 16383 0 0 17407 16383 0 -2048 17202 16383 0 0 Table 65 - Analog Input Data Format for RTD Input Type Input Range Input Value RTD пЂ 100 О©, 200 О©, 500 О©, 1000 О© Pt 385 RTD пЂ 100 О©, 200 О©, 500 О©, 1000 О© Pt 3916 RTD пЂ 10 О© Cu 426 RTD пЂ 100 О© Ni 618 850.0 В°C 850.0 В°C -200.0 В°C -200.0 В°C 1562.0 В°F 1562.0 В°F -328.0 В°F -328.0 В°F 630.0 В°C 630.0 В°C -200.0 В°C -200.0 В°C 1166.0 В°F 1166.0 В°F -328.0 В°F -328.0 В°F 260.0 В°C 260.0 В°C -100.0 В°C -100.0 В°C 500.0 В°F 500.0 В°F -148.0 В°F -148.0 В°F 260.0 В°C 260.0 В°C -100.0 В°C -100.0 В°C 500.0 В°F 500.0 В°F -148.0 В°F -148.0 В°F Condition High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit Engineering Units 8500 8500 -2000 -2000 15620 15620 -3280 -3280 6300 6300 -2000 -2000 11660 11660 -3280 -3280 2600 2600 -1000 -1000 5000 5000 -1480 -1480 2600 2600 -1000 -1000 5000 5000 -1480 -1480 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Engineering Units x 10 850 850 -200 -200 1562 1562 -328 -328 630 630 -200 -200 1166 1166 -328 -328 260 260 -100 -100 500 500 -148 -148 260 260 -100 -100 500 500 -148 -148 Raw / Proportional 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 PID 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 91 Chapter 4 System Operation and Configuration Input Range Input Value Condition 260.0 В°C 260.0 В°C -80.0 В°C -80.0 В°C RTD пЂ 120 О© Ni 672 500.0 В°F 500.0 В°F -112.0 В°F -112.0 В°F 200.0 В°C 200.0 В°C -100.0 В°C RTD пЂ -100.0 В°C 100 О© NiFe 392.0 В°F 518 392.0 В°F -148.0 В°F -148.0 В°F High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit Engineering Units 2600 2600 -800 -800 5000 5000 -1120 -1120 2000 2000 -1000 -1000 3920 3920 -1480 -1480 Engineering Units x 10 260 260 -80 -80 500 500 -112 -112 200 200 -100 -100 392 392 -148 -148 Raw / Proportional 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 PID 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 Table 66 - Analog Input Data Format for Resistance Input Type 150.00 О© 150.00 О© 0.00 О© 0.00 О© 750.0 О© 750.0 О© 0.0 О© 0.0 О© 3000.0 О© 3000.0 О© 0.0 О© 0.0 О© High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit Engineering Units 15000 15000 0 0 7500 7500 0 0 30000 30000 0 0 6000 О© High Limit 6000 600 32767 16383 6000 О© High Range 6000 600 32767 16383 0О© Low Range 0 0 -32768 0 0О© Low Limit 0 0 -32768 0 Input Range Input Value Resistance пЂ 0-150 О© Resistance пЂ 0-750 О© Resistance пЂ 0-3000 О© Resistance пЂ 0-6000 О©пЂ (PTC / NTC) Condition Engineering Units x 10 1500 1500 0 0 750 750 0 0 3000 3000 0 0 Raw / Proportional 32767 32767 -32768 -32768 32767 32767 -32768 -32768 32767 32767 -32768 -32768 16383 16383 0 0 16383 16383 0 0 16383 16383 0 0 PID Analog Output Channel The isolated analog output can be programmed to provide one of the following analog output signal types: • Current – 4…20 mA – 0…20 mA 92 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 • Voltage – 0…10V DC – 1…5V DC – 0…5V DC The analog outputs can report data as a percent of range. Table 67 and Table 68 display the data ranges for all of the available analog output types. Table 67 - Analog Output Data Format for Current Output Type Output Range 4…20 mA 0…20 mA Output Signal 21.000 mA 20.000 mA 4.000 mA 3.000 mA 21.00 mA 20.00 mA 0.00 mA 0.00 mA Condition High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit % Range 106.25% 100.00% 0.00% -6.25% 105.00% 100.00% 0.00% 0.00% Table 68 - Analog Output Data Format for Voltage Output Type Output Range 0…10 V DC 1…5 V DC 0…5 V DC Output Value 10.50V DC 10.00V DC 0.00V DC 0.00V DC 5.25V DC 5.00V DC 1.00V DC 0.50V DC 5.25V DC 5.00V DC 0.00V DC 0.00V DC Condition High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit High Limit High Range Low Range Low Limit % Range 105.00% 100.00% 0.00% 0.00% 106.25% 100.00% 0.00% -6.25% 105.00% 100.00% 0.00% 0.00% The analog output can be used to communicate E300 diagnostic information via an analog signal to distributed control systems, programmable logic controllers, or panel-mounted analog meters. The analog output can represent one of the following E300 diagnostic parameters: • Average %FLA • %TCU • Ground Fault Current • Current Imbalance • Average L-L Voltage • Voltage Imbalance • Total kW • Total kVAR • Total kVA Rockwell Automation Publication 193-UM015C-EN-P - December 2014 93 Chapter 4 System Operation and Configuration • Total Power Factor • User-defined Value Table 69 - Analog Output Selection Type Output Selection Average % FLA Scaled Average % FLA % TCU Ground Fault Current Internal, 0.50…5.00 A External, 0.02…0.10 A External, 0.10…0.50 A External, 0.20…1.00 A External, 1.00…5.00 A Current Imbalance Average L-L Voltage Voltage Imbalance Total kW Total kVAR Total kVA Total Power Factor User-defined Value Low Range 0% 0% 0% High Range 100% 200% 100% 0.50 A 0.02 A 0.10 A 0.20 A 1.00 A 0% 0V 0% 0 kW 5.25V DC 5.00V DC -50% (Lagging) -32768 5.00 A 0.10 A 0.50 A 1.00 A 5.00 A 100% (PT Primary) V 100% (FLA1 x PT Primary x 1.732) V (FLA1 x PT Primary x 1.732) V (FLA1 x PT Primary x 1.732) V +50% (Leading) 32767 Update Rate Analog Input Channels The performance for the input channels of the E300 Analog I/O Expansion Module is dependent on the filter setting for each channel. The total scan time for the input channels of the module is determined by adding the conversion time for all enabled input channels. Table 70 - Analog Input Channel Conversion Time Input Type Current, Voltage, пЂ 2-Wire RTD, Resistance 3-Wire RTD Filter Frequency 17 Hz 4 Hz 62 Hz 470 Hz 17 Hz 4 Hz 62 Hz 470 Hz Conversion Time 153 ms 512 ms 65 ms 37 ms 306 ms 1024 ms 130 ms 74 ms Example: • Channel 00 is configured for a 3-wire RTD and 4 Hz filter (conversion time = 1024 ms). • Channel 01 is configured for 17Hz voltage (conversion time = 153 ms). • Channel 02 is configured for 62Hz current (conversion time = 65 ms). 94 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 The E300 Analog I/O Expansion Module input channel scan time will be 1242 ms (1024+153+65). Analog Output Channel The E300 Analog I/O Expansion Module output channel update rate is 10 ms. Analog Module 1 Analog Module 1 – Input Channel 00 Type Analog Module 1 – Input Channel 00 Type (Parameter 437) defines the type of analog signal that Input Channel 00 of Analog Module 1 will be monitoring. Table 71 - Analog Module 1 – Input Channel 00 Type (Parameter 437) Value Assignment Description 0 Disabled Disable the analog input 1 4To20mA Read an analog current signal from 4…20 mA 2 0To20mA Read an analog current signal from 0…20 mA 3 0To10Volts Read an analog voltage signal from 0…10 V DC 4 1To5Volts Read an analog voltage signal from 1…5 V DC 5 0To5Volts Read an analog voltage signal from 0…5 V DC 6 100Pt385 Read a 100 О© Pt 385 RTD Sensor 7 200Pt385 Read a 200 О© Pt 385 RTD Sensor 8 500Pt385 Read a 500 О© Pt 385 RTD Sensor 9 1000Pt385 Read a 1000 О© Pt 385 RTD Sensor 10 100Pt3916 Read a 100 О© Pt 3916 RTD Sensor 11 200Pt3916 Read a 200 О© Pt 3916 RTD Sensor 12 500Pt3916 Read a 500 О© Pt 3916 RTD Sensor 13 1000Pt3916 Read a 1000 О© Pt 3916 RTD Sensor 14 10Cu426 Read a 10 О© Cu 426 RTD Sensor 15 100Ni618 Read a 100 О© Ni 618 RTD Sensor 16 120Ni672 Read a 120 О© Ni 672 RTD Sensor 17 604NiFe518 Read a 604О© NiFe 518 RTD Sensor 18 150ohm Read a resistance signal from 0…150 О© 19 750ohm Read a resistance signal from 0…750 О© 20 3000ohm Read a resistance signal from 0…3000 О© 21 6000ohm Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 1 – Input Channel 00 Format Analog Module 1 – Input Channel 00 Format (Parameter 438) defines the data format for how the analog reading is reported. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 95 Chapter 4 System Operation and Configuration Table 72 - Analog Module 1 – Input Channel 00 Format (Parameter 438) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…+32767) Scaled for PID (0…16383) Analog Module 1 – Input Channel 00 Temperature Unit Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439) defines the temperate unit for RTD sensor readings. Table 73 - Analog Module 1 – Input Channel 00 Temperature Unit (Parameter 439) Value Assignment Description 0 DegreesC Report RTD Temperature Data in В°C 1 DegreesF Report RTD Temperature Data in В°F Analog Module 1 – Input Channel 00 Filter Frequency Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440) defines update rate for the analog module’s input channels. Table 74 - Analog Module 1 – Input Channel 00 Filter Frequency (Parameter 440) Value Assignment Description 0 17 Hz Analog to Digital Conversion Update Frequency of 17 Hz 1 4 Hz Analog to Digital Conversion Update Frequency of 4 Hz 2 62 Hz Analog to Digital Conversion Update Frequency of 62 Hz 3 470 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 1 – Input Channel 00 Open Circuit State Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 75 - Analog Module 1 – Input Channel 00 Open Circuit State (Parameter 441) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 1 – Input Channel 00 RTD Type Enable Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. 96 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 76 - Analog Module 1 – Input Channel 00 RTD Type Enable (Parameter 442) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 1 – Input Channel 01 Type Analog Module 1 – Input Channel 01 Type (Parameter 446) defines the type of analog signal that Input Channel 01 of Analog Module 1 will be monitoring. Table 77 - Analog Module 1 – Input Channel 01 Type (Parameter 446) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 1 – Input Channel 01 Format Analog Module 1 – Input Channel 01 Format (Parameter 447) defines the data format for howthe analog reading is reported. Table 78 - Analog Module 1 – Input Channel 01 Format (Parameter 447) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…+32767) Scaled for PID (0…16383) AnalogВ ModuleВ 1 – InputВ ChannelВ 01В TemperatureВ Unit Rockwell Automation Publication 193-UM015C-EN-P - December 2014 97 Chapter 4 System Operation and Configuration Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448) defines the temperate unit for RTD sensor readings. Table 79 - Analog Module 1 – Input Channel 01 Temperature Unit (Parameter 448) Value 0 1 Assignment DegreesC DegreesF Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F Analog Module 1 – Input Channel 01 Filter Frequency Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449) defines update rate for the analog module’s input channels. Table 80 - Analog Module 1 – Input Channel 01 Filter Frequency (Parameter 449) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 1 – Input Channel 01 Open Circuit State Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 81 - Analog Module 1 – Input Channel 01 Open Circuit State (Parameter 450) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 1 – Input Channel 01 RTD Type Enable Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 82 - Analog Module 1 – Input Channel 01 RTD Type Enable (Parameter 451) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 1 – Input Channel 02 Type Analog Module 1 – Input Channel 02 Type (Parameter 455) defines the type of analog signal that Input Channel 02 of Analog Module 1 will be monitoring. 98 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 83 - Analog Module 1 – Input Channel 02 Type (Parameter 455) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 1 – Input Channel 02 Format Analog Module 1 – Input Channel 02 Format (Parameter 456) defines the data format for how the analog reading is reported. Table 84 - Analog Module 1 – Input Channel 02 Format (Parameter 456) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…32767) Scaled for PID (0 …16383) Analog Module 1 – Input Channel 02 Temperature Unit Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457) defines the temperate unit for RTD sensor readings. Table 85 - Analog Module 1 – Input Channel 02 Temperature Unit (Parameter 457) Value 0 1 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F 99 Chapter 4 System Operation and Configuration Analog Module 1 – Input Channel 02 Filter Frequency Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458) defines update rate for the analog module’s input channels. Table 86 - Analog Module 1 – Input Channel 02 Filter Frequency (Parameter 458) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 1 – Input Channel 02 Open Circuit State Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 87 - Analog Module 1 – Input Channel 02 Open Circuit State (Parameter 459) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 1 – Input Channel 02 RTD Type Enable Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 88 - Analog Module 1 – Input Channel 02 RTD Type Enable (Parameter 460) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor AnalogВ ModuleВ 1 – OutputВ ChannelВ 00В Type Analog Module 1 – Output Channel 00 Type (Parameter 464) defines the type of analog signal that Output Channel 00 of Analog Module 1 will be providing. Table 89 - Analog Module 1 – Output Channel 00 Type (Parameter 464) Value 0 1 2 3 4 5 100 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Disable the analog input Provide an analog current signal from 4…20 mA Provide an analog current signal from 0…20 mA Provide an analog voltage signal from 0…10 V DC Provide an analog voltage signal from 1…5 V DC Provide an analog voltage signal from 0…5 V DC System Operation and Configuration Chapter 4 Analog Module 1 – Output Channel 00 Selection Analog Module 1 – Output Channel 00 Selection (Parameter 465) defines the E300 Electronic Overload Relay parameter that Output Channel 00 will be representing. Table 90 - Analog Module 1 – Output Channel 00 Selection (Parameter 465) Value 0 1 2 3 4 5 6 7 8 9 10 11 Assignment AveragePCTFLA ScaledAvgPctFLA PercentTCU GFCurrent CurrentImbalance AvgLLVoltage VoltLLImbalance TotalkW TotalkVA Total kVAR TotalPF UserDLXData Description Average %FLA (0…100%) Scaled Average %FLA (0…200%) %TCU (0…100%) Ground Fault Current (Ground Fault Type Range) Current Imbalance (0…100%) Average L-L Voltage (0…PT Primary) Voltage Imbalance (0…100%) Total kW (0…FLA x PT Primary x 1.732) Total kVA (0…FLA x PT Primary x 1.732) Total kVAR (0…FLA x PT Primary x 1.732) Total Power Factor (-50% Lagging…+50% Leading) User-defined Value (-32768…32767) Analog Module 1 – Output Channel 00 Expansion Bus Fault Action Analog Module 1 – Output Channel 00 Expansion Bus Fault Action (Parameter 466) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when there is an E300 Expansion Bus fault. Table 91 - Analog Module 1 – Output Channel 00 Expansion Bus Fault Action (Parameter 466) Value 0 1 2 3 Assignment Zero Maximum Minimum HoldLastState Description Provide an analog signal of zero Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the last known analog signal Analog Module 1 – Output Channel 00 Protection Fault Action Analog Module 1 – Output Channel 00 Expansion Bus Fault Action (Parameter 467) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when the E300 is in a tripped state. Table 92 - Analog Module 1 – Output Channel 00 Protection Fault Action (Parameter 467) Value 0 1 2 3 Assignment Ignore Maximum Minimum HoldLastState Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Continue providing the appropriate analog signal Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the analog signal at the time of the fault 101 Chapter 4 System Operation and Configuration Analog Module 2 Analog Module 2 – Input Channel 00 Type Analog Module 2 – Input Channel 00 Type (Parameter 468) defines the type of analog signal that Input Channel 00 of Analog Module 2 will be monitoring. Table 93 - Analog Module 2 – Input Channel 00 Type (Parameter 468) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 2 – Input Channel 00 Format Analog Module 2 – Input Channel 00 Format (Parameter 469) defines the data format for how the analog reading is reported. Table 94 - Analog Module 2 – Input Channel 00 Format (Parameter 469) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768 - 32767) Scaled for PID (0 - 16383) Analog Module 2 – Input Channel 00 Temperature Unit Analog Module 2 – Input Channel 00 Temperature Unit (Parameter 470) defines the temperate unit for RTD sensor readings. 102 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 95 - Analog Module 2 – Input Channel 00 Temperature Unit (Parameter 470) Value 0 1 Assignment DegreesC DegreesF Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F Analog Module 2 – Input Channel 00 Filter Frequency Analog Module 2 – Input Channel 00 Filter Frequency (Parameter 471) defines update rate for the analog module’s input channels. Table 96 - Analog Module 2 – Input Channel 00 Filter Frequency (Parameter 471) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 2 – Input Channel 00 Open Circuit State Analog Module 2 – Input Channel 00 Open Circuit State (Parameter 472) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 97 - Analog Module 2 – Input Channel 00 Open Circuit State (Parameter 472) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 2 – Input Channel 00 RTD Type Enable Analog Module 2 – Input Channel 00 RTD Type Enable (Parameter 473) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 98 - Analog Module 2 – Input Channel 00 RTD Type Enable (Parameter 473) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 2 – Input Channel 01 Type Analog Module 2 – Input Channel 01 Type (Parameter 477) defines the type of analog signal that Input Channel 01 of Analog Module 2 will be monitoring. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 103 Chapter 4 System Operation and Configuration Table 99 - Analog Module 2 – Input Channel 01 Type (Parameter 477) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 2 – Input Channel 01 Format Analog Module 2 – Input Channel 01 Format (Parameter 478) defines the data format for how the analog reading is reported. Table 100 - Analog Module 2 – Input Channel 01 Format (Parameter 478) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…32767) Scaled for PID (0…16383) Analog Module 2 – Input Channel 01 Temperature Unit Analog Module 2 – Input Channel 01 Temperature Unit (Parameter 479) defines the temperate unit for RTD sensor readings. Table 101 - Analog Module 2 – Input Channel 01 Temperature Unit (Parameter 479) Value 0 1 104 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F System Operation and Configuration Chapter 4 Analog Module 2 – Input Channel 01 Filter Frequency Analog Module 2 – Input Channel 01 Filter Frequency (Parameter 480) defines update rate for the analog module’s input channels. Table 102 - Analog Module 2 – Input Channel 01 Filter Frequency (Parameter 480) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 2 – Input Channel 01 Open Circuit State Analog Module 2 – Input Channel 01 Open Circuit State (Parameter 481) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 103 - Analog Module 2 – Input Channel 01 Open Circuit State (Parameter 481) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 2 – Input Channel 01 RTD Type Enable Analog Module 2 – Input Channel 01 RTD Type Enable (Parameter 482) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 104 - Analog Module 2 – Input Channel 01 RTD Type Enable (Parameter 482) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 2 – Input Channel 02 Type Analog Module 2 – Input Channel 02 Type (Parameter 486) defines the type of analog signal that Input Channel 02 of Analog Module 2 will be monitoring. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 105 Chapter 4 System Operation and Configuration Table 105 - Analog Module 2 – Input Channel 02 Type (Parameter 486) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 2 – Input Channel 02 Format Analog Module 2 – Input Channel 02 Format (Parameter 487) defines the data format for how the analog reading is reported. Table 106 - Analog Module 2 – Input Channel 02 Format (Parameter 487) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768 …32767) Scaled for PID (0…16383) Analog Module 2 – Input Channel 02 Temperature Unit Analog Module 2 – Input Channel 02 Temperature Unit (Parameter 488) defines the temperate unit for RTD sensor readings. Table 107 - Analog Module 2 – Input Channel 02 Temperature Unit (Parameter 488) Value 0 1 106 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F System Operation and Configuration Chapter 4 Analog Module 2 – Input Channel 02 Filter Frequency Analog Module 2 – Input Channel 02 Filter Frequency (Parameter 489) defines update rate for the analog module’s input channels. Table 108 - Analog Module 2 – Input Channel 02 Filter Frequency (Parameter 489) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 2 – Input Channel 02 Open Circuit State Analog Module 2 – Input Channel 02 Open Circuit State (Parameter 490) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 109 - Analog Module 2 – Input Channel 02 Open Circuit State (Parameter 490) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 2 – Input Channel 02 RTD Type Enable Analog Module 2 – Input Channel 02 RTD Type Enable (Parameter 491) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 110 - Analog Module 2 – Input Channel 02 RTD Type Enable (Parameter 491) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 2 – Output Channel 00 Type Analog Module 2 – Output Channel 00 Type (Parameter 464) defines the type of analog signal that Output Channel 00 of Analog Module 2 will be providing. Table 111 - Analog Module 2 – Output Channel 00 Type (Parameter 495) Value 0 1 2 3 4 5 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Disable the analog input Provide an analog current signal from 4…20 mA Provide an analog current signal from 0…20 mA Provide an analog voltage signal from 0…10 V DC Provide an analog voltage signal from 1…5 V DC Provide an analog voltage signal from 0…5 V DC 107 Chapter 4 System Operation and Configuration Analog Module 2 – Output Channel 00 Selection Analog Module 2 – Output Channel 00 Selection (Parameter 496) defines the E300 Electronic Overload Relay parameter that Output Channel 00 will be representing. Table 112 - Analog Module 2 – Output Channel 00 Selection (Parameter 496) Value 0 1 2 3 4 5 6 7 8 9 10 11 Assignment AveragePCTFLA ScaledAvgPctFLA PercentTCU GFCurrent CurrentImbalance AvgLLVoltage VoltLLImbalance TotalkW TotalkVA Total kVAR TotalPF UserDLXData Description Average %FLA (0…100%) Scaled Average %FLA (0…200%) %TCU (0…100%) Ground Fault Current (Ground Fault Type Range) Current Imbalance (0…100%) Average L-L Voltage (0… PT Primary) Voltage Imbalance (0… 100%) Total kW (0…FLA x PT Primary x 1.732) Total kVA (0…FLA x PT Primary x 1.732) Total kVAR (0…FLA x PT Primary x 1.732) Total Power Factor (-50% Lagging…+50% Leading) User-defined Value (-32768… 32767) Analog Module 2 – Output Channel 00 Expansion Bus Fault Action Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter 497) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when there is an E300 Expansion Bus fault. Table 113 - Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter 497) Value 0 1 2 3 Assignment Zero Maximum Minimum HoldLastState Description Provide an analog signal of zero Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the last known analog signal Analog Module 2 – Output Channel 00 Protection Fault Action Analog Module 2 – Output Channel 00 Expansion Bus Fault Action (Parameter 498) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when the E300 is in a tripped state. Table 114 - Analog Module 2 – Output Channel 00 Protection Fault Action (Parameter 498) Value 0 1 2 3 108 Assignment Ignore Maximum Minimum HoldLastState Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Continue providing the appropriate analog signal Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the analog signal at the time of the fault System Operation and Configuration Chapter 4 Analog Module 3 Analog Module 3 – Input Channel 00 Type Analog Module 3 – Input Channel 00 Type (Parameter 499) defines the type of analog signal that Input Channel 00 of Analog Module 3 will be monitoring. Table 115 - Analog Module 3 – Input Channel 00 Type (Parameter 499) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 3 – Input Channel 00 Format Analog Module 3 – Input Channel 00 Format (Parameter 500) defines the data format for how the analog reading is reported. Table 116 - Analog Module 3 – Input Channel 00 Format (Parameter 500) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…32767) Scaled for PID (0 …16383) Analog Module 3 – Input Channel 00 Temperature Unit Analog Module 3 – Input Channel 00 Temperature Unit (Parameter 501) defines the temperate unit for RTD sensor readings. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 109 Chapter 4 System Operation and Configuration Table 117 - Analog Module 3 – Input Channel 00 Temperature Unit (Parameter 501) Value 0 1 Assignment DegreesC DegreesF Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F Analog Module 3 – Input Channel 00 Filter Frequency Analog Module 3 – Input Channel 00 Filter Frequency (Parameter 502) defines update rate for the analog module’s input channels. Table 118 - Analog Module 3 – Input Channel 00 Filter Frequency (Parameter 502) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 3 – Input Channel 00 Open Circuit State Analog Module 3 – Input Channel 00 Open Circuit State (Parameter 503) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 119 - Analog Module 3 – Input Channel 00 Open Circuit State (Parameter 503) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 3 – Input Channel 00 RTD Type Enable Analog Module 3 – Input Channel 00 RTD Type Enable (Parameter 504) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 120 - Analog Module 3 – Input Channel 00 RTD Type Enable (Parameter 504) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 3 – Input Channel 01 Type Analog Module 3 – Input Channel 01 Type (Parameter 508) defines the type of analog signal that Input Channel 01 of Analog Module 3 will be monitoring. 110 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 121 - Analog Module 3 – Input Channel 01 Type (Parameter 508) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 3 – Input Channel 01 Format Analog Module 3 – Input Channel 01 Format (Parameter 509) defines the data format for how the analog reading is reported. Table 122 - Analog Module 3 – Input Channel 01 Format (Parameter 509) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…32767) Scaled for PID (0…16383) Analog Module 3 – Input Channel 01 Temperature Unit Analog Module 3 – Input Channel 01 Temperature Unit (Parameter 510) defines the temperate unit for RTD sensor readings. Table 123 - Analog Module 3 – Input Channel 01 Temperature Unit (Parameter 510) Value 0 1 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F 111 Chapter 4 System Operation and Configuration Analog Module 3 – Input Channel 01 Filter Frequency Analog Module 3 – Input Channel 01 Filter Frequency (Parameter 511) defines update rate for the analog module’s input channels. Table 124 - Analog Module 3 – Input Channel 01 Filter Frequency (Parameter 511) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 3 – Input Channel 01 Open Circuit State Analog Module 3 – Input Channel 01 Open Circuit State (Parameter 512) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 125 - Analog Module 3 – Input Channel 01 Open Circuit State (Parameter 512) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 3 – Input Channel 01 RTD Type Enable Analog Module 3 – Input Channel 01 RTD Type Enable (Parameter 513) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 126 - Analog Module 3 – Input Channel 01 RTD Type Enable (Parameter 513) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 3 – Input Channel 02 Type Analog Module 3 – Input Channel 02 Type (Parameter 517) defines the type of analog signal that Input Channel 02 of Analog Module 3 will be monitoring. 112 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 127 - Analog Module 3 – Input Channel 02 Type (Parameter 517) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 3 – Input Channel 02 Format Analog Module 3 – Input Channel 02 Format (Parameter 518) defines the data format for how the analog reading is reported. Table 128 - Analog Module 3 – Input Channel 02 Format (Parameter 518) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…32767) Scaled for PID (0…16383) Analog Module 3 – Input Channel 02 Temperature Unit Analog Module 3 – Input Channel 02 Temperature Unit (Parameter 519) defines the temperate unit for RTD sensor readings. Table 129 - Analog Module 3 – Input Channel 02 Temperature Unit (Parameter 519) Value 0 1 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F 113 Chapter 4 System Operation and Configuration Analog Module 3 – Input Channel 02 Filter Frequency Analog Module 3 – Input Channel 02 Filter Frequency (Parameter 520) defines update rate for the analog module’s input channels. Table 130 - Analog Module 3 – Input Channel 02 Filter Frequency (Parameter 520) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 3 – Input Channel 02 Open Circuit State Analog Module 3 – Input Channel 02 Open Circuit State (Parameter 521) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 131 - Analog Module 3 – Input Channel 02 Open Circuit State (Parameter 521) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 3 – Input Channel 02 RTD Type Enable Analog Module 3 – Input Channel 02 RTD Type Enable (Parameter 522) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 132 - Analog Module 3 – Input Channel 02 RTD Type Enable (Parameter 522) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 3 – Output Channel 00 Type Analog Module 3 – Output Channel 00 Type (Parameter 526) defines the type of analog signal that Output Channel 00 of Analog Module 3 will be providing. Table 133 - Analog Module 3 – Output Channel 00 Type (Parameter 526) Value 0 1 2 3 4 5 114 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Disable the analog input Provide an analog current signal from 4…20 mA Provide an analog current signal from 0…20 mA Provide an analog voltage signal from 0…10 V DC Provide an analog voltage signal from 1…5 V DC Provide an analog voltage signal from 0…5 V DC System Operation and Configuration Chapter 4 Analog Module 3 – Output Channel 00 Selection Analog Module 3 – Output Channel 00 Selection (Parameter 527) defines the E300 Electronic Overload Relay parameter that Output Channel 00 will be representing. Table 134 - Analog Module 3 – Output Channel 00 Selection (Parameter 527) Value 0 1 2 3 4 5 6 7 8 9 10 11 Assignment AveragePCTFLA ScaledAvgPctFLA PercentTCU GFCurrent CurrentImbalance AvgLLVoltage VoltLLImbalance TotalkW TotalkVA Total kVAR TotalPF UserDLXData Description Average %FLA (0…100%) Scaled Average %FLA (0…200%) %TCU (0…100%) Ground Fault Current (Ground Fault Type Range) Current Imbalance (0…100%) Average L-L Voltage (0…PT Primary) Voltage Imbalance (0 …100%) Total kW (0…FLA x PT Primary x 1.732) Total kVA (0…FLA x PT Primary x 1.732) Total kVAR (0…FLA x PT Primary x 1.732) Total Power Factor (-50% Lagging…+50% Leading) User-defined Value (-32768 …+32767) Analog Module 3 – Output Channel 00 Expansion Bus Fault Action Analog Module 3 – Output Channel 00 Expansion Bus Fault Action (Parameter 528) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when there is an E300 Expansion Bus fault. Table 135 - Analog Module 3 – Output Channel 00 Expansion Bus Fault Action (Parameter 528) Value 0 1 2 3 Assignment Zero Maximum Minimum HoldLastState Description Provide an analog signal of zero Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the last known analog signal Analog Module 3 – Output Channel 00 Protection Fault Action Analog Module 3 – Output Channel 00 Expansion Bus Fault Action (Parameter 529) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when the E300 is in a tripped state. Table 136 - Analog Module 3 – Output Channel 00 Protection Fault Action (Parameter 529) Value 0 1 2 3 Assignment Ignore Maximum Minimum HoldLastState Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Continue providing the appropriate analog signal Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the analog signal at the time of the fault 115 Chapter 4 System Operation and Configuration Analog Module 4 Analog Module 4 – Input Channel 00 Type Analog Module 4 – Input Channel 00 Type (Parameter 530) defines the type of analog signal that Input Channel 00 of Analog Module 4 will be monitoring. Table 137 - Analog Module 4 – Input Channel 00 Type (Parameter 530) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 4 – Input Channel 00 Format Analog Module 4 – Input Channel 00 Format (Parameter 531) defines the data format for how the analog reading is reported. Table 138 - Analog Module 4 – Input Channel 00 Format (Parameter 531) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…+32767) Scaled for PID (0…16383) Analog Module 4 – Input Channel 00 Temperature Unit Analog Module 4 – Input Channel 00 Temperature Unit (Parameter 532) defines the temperate unit for RTD sensor readings. 116 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Table 139 - Analog Module 4 – Input Channel 00 Temperature Unit (Parameter 532) Value 0 1 Assignment DegreesC DegreesF Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F Analog Module 4 – Input Channel 00 Filter Frequency Analog Module 4 – Input Channel 00 Filter Frequency (Parameter 533) defines update rate for the analog module’s input channels. Table 140 - Analog Module 4 – Input Channel 00 Filter Frequency (Parameter 533) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 4 – Input Channel 00 Open Circuit State Analog Module 4 – Input Channel 00 Open Circuit State (Parameter 534) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 141 - Analog Module 4 – Input Channel 00 Open Circuit State (Parameter 534) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 4 – Input Channel 00 RTD Type Enable Analog Module 4 – Input Channel 00 RTD Type Enable (Parameter 535) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 142 - Analog Module 4 – Input Channel 00 RTD Type Enable (Parameter 535) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 4 – Input Channel 01 Type Analog Module 4 – Input Channel 01 Type (Parameter 539) defines the type of analog signal that Input Channel 01 of Analog Module 4 will be monitoring. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 117 Chapter 4 System Operation and Configuration Table 143 - Analog Module 4 – Input Channel 01 Type (Parameter 539) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 4 – Input Channel 01 Format Analog Module 4 – Input Channel 01 Format (Parameter 540) defines the data format for how the analog reading is reported. Table 144 - Analog Module 4 – Input Channel 01 Format (Parameter 540) Value 0 1 2 3 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…+32767) Scaled for PID (0…16383) Analog Module 4 – Input Channel 01 Temperature Unit Analog Module 4 – Input Channel 01 Temperature Unit (Parameter 541) defines the temperate unit for RTD sensor readings. Table 145 - Analog Module 4 – Input Channel 01 Temperature Unit (Parameter 541) Value 0 1 118 Assignment DegreesC DegreesF Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F System Operation and Configuration Chapter 4 Analog Module 4 – Input Channel 01 Filter Frequency Analog Module 4 – Input Channel 01 Filter Frequency (Parameter 542) defines update rate for the analog module’s input channels. Table 146 - Analog Module 4 – Input Channel 00 Filter Frequency (Parameter 542) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 4 – Input Channel 01 Open Circuit State Analog Module 4 – Input Channel 01 Open Circuit State (Parameter 543) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 147 - Analog Module 4 – Input Channel 01 Open Circuit State (Parameter 543) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 4 – Input Channel 01 RTD Type Enable Analog Module 4 – Input Channel 01 RTD Type Enable (Parameter 544) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 148 - Analog Module 4 – Input Channel 01 RTD Type Enable (Parameter 544) Value 0 1 Assignment 3-Wire 2-Wire Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor 119 Chapter 4 System Operation and Configuration Analog Module 4 – Input Channel 02 Type Analog Module 4 – Input Channel 02 Type (Parameter 548) defines the type of analog signal that Input Channel 02 of Analog Module 4 will be monitoring. Table 149 - Analog Module 4 – Input Channel 02 Type (Parameter 548) Value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts 100Pt385 200Pt385 500Pt385 1000Pt385 100Pt3916 200Pt3916 500Pt3916 1000Pt3916 10Cu426 100Ni618 120Ni672 604NiFe518 150ohm 750ohm 3000ohm 21 6000ohm Description Disable the analog input Read an analog current signal from 4…20 mA Read an analog current signal from 0…20 mA Read an analog voltage signal from 0…10 V DC Read an analog voltage signal from 1…5 V DC Read an analog voltage signal from 0…5 V DC Read a 100 О© Pt 385 RTD Sensor Read a 200 О© Pt 385 RTD Sensor Read a 500 О© Pt 385 RTD Sensor Read a 1000 О© Pt 385 RTD Sensor Read a 100 О© Pt 3916 RTD Sensor Read a 200 О© Pt 3916 RTD Sensor Read a 500 О© Pt 3916 RTD Sensor Read a 1000 О© Pt 3916 RTD Sensor Read a 10 О© Cu 426 RTD Sensor Read a 100 О© Ni 618 RTD Sensor Read a 120 О© Ni 672 RTD Sensor Read a 604 О© NiFe 518 RTD Sensor Read a resistance signal from 0…150 О© Read a resistance signal from 0…750 О© Read a resistance signal from 0…3000 О© Read a resistance signal from 0…6000 О©. This setting can be used with PTC and NTC sensors. Analog Module 4 – Input Channel 02 Format Analog Module 4 – Input Channel 02 Format (Parameter 549) defines the data format for how the analog reading is reported. Table 150 - Analog Module 4 – Input Channel 02 Format (Parameter 549) Value 0 1 2 3 120 Assignment EngUnits EngUnitsTimes10 RawProportional ScaledForPID Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Description Engineering Units (mA, V, В°C, В°F, or О©) Engineering Units x 10 (mA, V, В°C, В°F, or О©) Raw / Proportional (-32768…+32767) Scaled for PID (0…16383) System Operation and Configuration Chapter 4 Analog Module 4 – Input Channel 02 Temperature Unit Analog Module 4 – Input Channel 02 Temperature Unit (Parameter 550) defines the temperate unit for RTD sensor readings. Table 151 - Analog Module 4 – Input Channel 02 Temperature Unit (Parameter 550) Value 0 1 Assignment DegreesC DegreesF Description Report RTD Temperature Data in В°C Report RTD Temperature Data in В°F Analog Module 4 – Input Channel 02 Filter Frequency Analog Module 4 – Input Channel 02 Filter Frequency (Parameter 551) defines update rate for the analog module’s input channels. Table 152 - Analog Module 4 – Input Channel 02 Filter Frequency (Parameter 551) Value 0 1 2 3 Assignment 17 Hz 4 Hz 62 Hz 470 Hz Description Analog to Digital Conversion Update Frequency of 17 Hz Analog to Digital Conversion Update Frequency of 4 Hz Analog to Digital Conversion Update Frequency of 62 Hz Analog to Digital Conversion Update Frequency of 470Hz Analog Module 4 – Input Channel 02 Open Circuit State Analog Module 4 – Input Channel 02 Open Circuit State (Parameter 552) defines what the input channel reports when the input channel has an open circuit. Open circuit detection is always enabled for this input channel. Table 153 - Analog Module 4 – Input Channel 02 Open Circuit State (Parameter 552) Value 0 1 2 Assignment Upscale Downscale Zero Description Reports the high limit of the input channel type Reports the low limit of the input channel type Reports zero Analog Module 4 – Input Channel 02 RTD Type Enable Analog Module 4 – Input Channel 02 RTD Type Enable (Parameter 556) defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor. Table 154 - Analog Module 4 – Input Channel 02 RTD Type Enable (Parameter 556) Value 0 1 Assignment 3-Wire 2-Wire Description Scan a 3-wire RTD sensor Scan a 2-wire RTD sensor Analog Module 4 – Output Channel 00 Type Analog Module 4 – Output Channel 00 Type (Parameter 557) defines the type of analog signal that Output Channel 00 of Analog Module 4 will be providing. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 121 Chapter 4 System Operation and Configuration Table 155 - Analog Module 4 – Output Channel 00 Type (Parameter 557) Value 0 1 2 3 4 5 Assignment Disabled 4To20mA 0To20mA 0To10Volts 1To5Volts 0To5Volts Description Disable the analog input Provide an analog current signal from 4…20 mA Provide an analog current signal from 0…20 mA Provide an analog voltage signal from 0…10 V DC Provide an analog voltage signal from 1…5 V DC Provide an analog voltage signal from 0…5 V DC Analog Module 4 – Output Channel 00 Selection Analog Module 4 – Output Channel 00 Selection (Parameter 558) defines the E300 Electronic Overload Relay parameter that Output Channel 00 will be representing. Table 156 - Analog Module 4 – Output Channel 00 Selection (Parameter 558) Value 0 1 2 3 4 5 6 7 8 9 10 11 Assignment AveragePCTFLA ScaledAvgPctFLA PercentTCU GFCurrent CurrentImbalance AvgLLVoltage VoltLLImbalance TotalkW TotalkVA Total kVAR TotalPF UserDLXData Description Average %FLA (0…100%) Scaled Average %FLA (0…200%) %TCU (0…100%) Ground Fault Current (Ground Fault Type Range) Current Imbalance (0…100%) Average L-L Voltage (0…PT Primary) Voltage Imbalance (0…100%) Total kW (0…FLA x PT Primary x 1.732) Total kVA (0…FLA x PT Primary x 1.732) Total kVAR (0…FLA x PT Primary x 1.732) Total Power Factor (-50% Lagging…+50% Leading) User-defined Value (-32768…32767) Analog Module 4 – Output Channel 00 Expansion Bus Fault Action Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter 559) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when there is an E300 Expansion Bus fault. Table 157 - Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter 559) Value 0 1 2 3 Assignment Zero Maximum Minimum HoldLastState Description Provide an analog signal of zero Provide an analog signal equal to the high limit Provide an analog signal equal to the low limit Provide the last known analog signal Analog Module 4 – Output Channel 00 Protection Fault Action Analog Module 4 – Output Channel 00 Expansion Bus Fault Action (Parameter 560) defines the value that the E300 Analog I/O Expansion Module Output Channel 00 provides when the E300 is in a tripped state. 122 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 System Operation and Configuration Chapter 4 Figure 42 - Analog Module 4 – Output Channel 00 Protection Fault Action (Parameter 560) Introduction to Operating Modes Value Assignment Description 0 Ignore Continue providing the appropriate analog signal 1 Maximum Provide an analog signal equal to the high limit 2 Minimum Provide an analog signal equal to the low limit 3 HoldLastState Provide the analog signal at the time of the fault The E300 Electronic Overload Relay supports a number of Operating Modes, which consist of configuration rules and logic to control typical full-voltage motor starters, including: • Overload • Non-Reversing Starter • Reversing Starter • Wye/Delta (Star/Delta) Starter • Two-Speed Starter • Monitor The default Operating Mode (Parameter 195) for the E300 Electronic Overload Relay is Overload (Network) in which the E300 Electronic Overload Relay operates like a traditional overload relay in which one of the output relays is assigned as a Trip Relay or Control Relay. You can use network commands to control any output relays that are assigned as Normal output relays or Control Relays. For Control Module firmware v1.000 and v2.000, one output relay must be assigned as a Trip Relay. For Control Module firmware v3.000 and higher, one output relay must be configured as a Trip Relay or Control Relay. Invalid configuration of the output relays causes the E300 Electronic Overload Relay to go into Invalid Configuration Mode and trip on a configuration trip. Operating Modes on page 125 describes the functionality of the available Operating Modes for the E300 Electronic Overload Relay and their associated configuration rules. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 123 Chapter 4 System Operation and Configuration Notes: 124 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 5 Operating Modes Introduction The E300в„ў Electronic Overload Relay supports up to 54 Operating Modes, which consist of configuration rules and logic to control typical full-voltage motor starters, including: • Overload • Non-Reversing Starter • Reversing Starter • Wye/Delta (Star/Delta) Starter • Two Speed Starter • Monitoring Device This chapter explains the configuration rules, logic, and control wiring that is required for the available Operating Modes (Parameter 195). Failure to follow the configuration rules causes the E300 Electronic Overload Relay to go into Invalid Configuration Mode and trip the E300 Electronic Overload Relay on a configuration trip. Overload (Network) The E300 Electronic Overload Relay’s default Operating Mode (Parameter 195) is Overload (Network) in which the E300 Electronic Overload Relay operates as a traditional overload relay with one output relay that is assigned as a normally closed Trip Relay. You can use network commands to control the remaining output relays that are assigned as Normal output relays. Rules 1. For Control Module firmware v1.000 and v2.000, one output relay must be assigned as a Trip Relay. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay. 2. For Control Module firmware v3.000 and higher, one output relay must be assigned as a Trip Relay or Control Relay. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay or Control Relay. 3. Overload Trip must be enabled in TripEnableI (Parameter 183). Wiring Diagram The E300 Electronic Overload Relay is wired as a traditional overload relay with one of the output relays configured as a normally closed Trip Relay. Figure 43 is a wiring diagram of a Non-Reversing Starter. Relay 0 is configured as a Trip Relay, Rockwell Automation Publication 193-UM015C-EN-P - December 2014 125 Chapter 5 Operating Modes and Relay 1 is configured as a normally open Normal Relay, which receives commands from an automation controller to energize the contactor coil. Figure 43 - Trip Relay Wiring Diagram Relay 0 Configured as a Trip Relay 1 Relay 1 R13 R14 A1 A2 M R03 R04 1 Contact shown with supply voltage applied. For Control Module firmware v3.000 and higher, the E300 Electronic Overload Relay can also be wired as a Control Relay in which the relay that is controlled by the communications network opens when a trip event is present. Figure 44 is a wiring diagram of a Non-Reversing Starter with Relay 0 configured as a Control Relay. Relay 0 receives control commands from an automation controller to energize or de-energize the contactor coil. Relay 0 also goes to an open state when there is a trip event. Figure 44 - Control Relay Wiring Diagram Relay 0 Configured as a Control Relay 1 R03 R04 A1 M A2 1 Contact shown with supply voltage applied. 126 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Operating Modes Chapter 5 Timing Diagram Figure 45 - Timing Diagram Trip Relay or Control Relay Device Status0.Trip Present Trip Reset Monitor (Custom) The E300 Electronic Overload Relay’s Monitor (Custom) Operating Mode allows you to use the E300 Electronic Overload Relay as a monitoring device. No configuration rules apply in this operating mode if the motor protection features are disabled. Rules 1. If any protection trips are enabled (excluding Configuration, NVS, and Hardware Fault trip), then set any of the Output Ptxx Assignments (Parameters 202…204) to the appropriate value of Trip Relay, Control Relay, Monitor Lx Trip Relay, or Monitor Lx Control Relay. Wiring Diagram Not Applicable Timing Diagram Not Applicable Rockwell Automation Publication 193-UM015C-EN-P - December 2014 127 Chapter 5 128 Operating Modes Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 6 Protective Trip and Warning Functions Introduction This chapter provides detailed information about the protective trip and warning functions of the E300пЂ Electronic Overload Relay. The protective trip and warning functions are organized into five sections: • Current-based • Voltage-based • Power-based • Control-based • Analog-based This chapter explains the trip and warning protection features of the E300 Electronic Overload Relay and the associated configuration parameters. Current-based Protection The E300 Electronic Overload Relay digitally monitors the electrical current that is consumed by an electric motor. This electric current information is used for the following protective trip and warning functions: • Overload Trip/Warning • Phase Loss Trip • Ground Fault Trip/Warning • Stall Trip • Jam Trip/Warning • Underload Trip/Warning • Current Imbalance Trip/Warning • Line Under Current Trip/Warning • Line Over Current Trip/Warning • Line Loss Trip/Warning Rockwell Automation Publication 193-UM015C-EN-P - December 2014 129 Chapter 6 Protective Trip and Warning Functions Current Trip Enable (Parameter 183) and Current Warning Enable (Parameter 189) are used to enable the respective current-based protective trip and warning functions. Table 158 - Current Trip Enable (Parameter 183) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Overload Trip X Phase Loss Trip X Ground Fault Trip X Stall Trip X Jam Trip X Underload Trip X Current Imbalance Trip X L1 Under Current Trip X L2 Under Current Trip X L3 Under Current Trip X L1 Over Current Trip X L2 Over Current Trip X L3 Over Current Trip X L1 Line Loss Trip X L2 Line Loss Trip X L3 Line Loss Trip Table 159 - Current Warning Enable (Parameter 189) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Overload Warning Reserved X Ground Fault Warning Reserved X X X X X X X X X X X X 130 Jam Warning Underload Warning Current Imbalance Warning L1 Under Current Warning L2 Under Current Warning L3 Under Current Warning L1 Over Current Warning L2 Over Current Warning L3 Over Current Warning L1 Line Loss Warning L2 Line Loss Warning L3 Line Loss Warning Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Current Trip Status (Parameter 4) and Current Warning Status (Parameter 10) are used to monitor the respective current-based protective trip and warning functions. Table 160 - Current Trip Status (Parameter 4) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Overload Trip X Phase Loss Trip X Ground Fault Current Trip X Stall Trip X Jam Trip X Underload Trip X Current Imbalance Trip X L1 Under Current Trip X L2 Under Current Trip X L3 Under Current Trip X L1 Over Current Trip X L2 Over Current Trip X L3 Over Current Trip X L1 Line Loss Trip X L2 Line Loss Trip X L3 Line Loss Trip Table 161 - Current Warning Status (Parameter 10) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Overload Warning Reserved X Ground Fault Warning Reserved X X X X X X X X X X X X Jam Warning Underload Warning Current Imbalance Warning L1 Under Current Warning L2 Under Current Warning L3 Under Current Warning L1 Over Current Warning L2 Over Current Warning L3 Over Current Warning L1 Line Loss Warning L2 Line Loss Warning L3 Line Loss Warning Rockwell Automation Publication 193-UM015C-EN-P - December 2014 131 Chapter 6 Protective Trip and Warning Functions Overload Protection The E300 Electronic Overload Relay provides overload protection through true RMS current measurements of the individual phase currents of the connected motor. Based on the highest current measured, the programmed FLA Setting, and Trip Class, a thermal model that simulates the actual heating of the motor is calculated. Percent Thermal Capacity Utilized (Parameter 1) reports this calculated value and can be read via the communications network. Overload Trip The E300 Electronic Overload Relay trips with an overload indication if: • No trip currently exists • Overload trip protection is enabled • Current is present • % Thermal Capacity Utilized reaches 100% If the E300 Electronic Overload Relay trips on an overload, the following occurs: • The TRIP/WARN LED flashes a red short-1 blink pattern, • Bit 0 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT 132 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Full Load Amps Setting FLA (Parameter 171) is one of two parameters that affect the E300 Electronic Overload Relay’s thermal capacity utilization algorithm. you enters the motor’s full-load current rating into this parameter. Table 162 - FLA (Parameter 171) FLA (Parameter 171) 0.50 (0.5…30 A Sensing Modules) Default Value 6.00 (6…60 A Sensing Modules) 10.00 (10…100 A Sensing Modules) 20.00 (20…200 A Sensing Modules) Minimum Value 0.50 Maximum Value 65535.00 Parameter Type UDINT Size (Bytes) 4 Scaling Factor 100 Units Amps FLA2 (Parameter 177) is provided for programming the high-speed FLA value in two-speed motor applications. Activating FLA2 is described in Chapter 4. Table 163 - FLA2 (Parameter 177) FLA2 (Parameter 177) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.50 (0.5…30 A Sensing Modules) 6.00 (6…60 A Sensing Modules) 10.00 (10…100 A Sensing Modules) 20.00 (20…200 A Sensing Modules) 0.50 65535.00 UDINT 4 100 Amps USA and Canada Guidelines • Motor Service Factor ≥ 1.15: For motors with a service factor rating of 1.15 or greater, program the FLA setting to the full-load current rating on the printed nameplate. • Motor Service Factor < 1.15: For motors with a service factor rating less than 1.15, program the FLA setting to 90% of the full-load current rating on the printed nameplate. • Wye-Delta (Y-О”) Applications: Follow the application’s service factor instructions, except divide the full-load current rating on the printed nameplate by 1.73. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 133 Chapter 6 Protective Trip and Warning Functions Outside USA and Canada Guidelines • Maximum Continuous Rated (MCR) Motors: Program the FLA setting to the full-load current rating on the printed nameplate. • Star-Delta (Y-О”) Applications: Follow the MCR instructions, except divide the full-load current rating on the printed nameplate by 1.73. Trip Class Trip Class is the second of two parameters that affect the E300 Electronic Overload Relay’s thermal capacity utilization algorithm. Trip class is defined as the maximum time (in seconds) for an overload trip to occur when the motor’s operating current is six times its rated current. The E300 Electronic Overload Relay offers an adjustable trip class range of 5…30. Enter the application trip class into Trip Class (Parameter 172). Table 164 - Trip Class (Parameter 172) Trip Class (Parameter 172) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 10 5 30 USINT 1 1 В Trip Curves The following figures illustrate the E300 Electronic Overload Relay’s timecurrent characteristics for trip classes 5, 10, 20, and 30. 134 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Figure 46 - Time-Current Characteristics for Trip Classes 5, 10, 20, and 30 Trip Class 5 1000 100 Time (seconds) Time (seconds) 1000 10 1 100% 10 Trip Class 20 1000 1000 Time (seconds) 10000 Time (seconds) 10000 100 10 1 100% Cold Trip Hot Trip 100 1 100% 1000% Current (% FLA) Trip Class 10 Current (% FLA) 1000% Trip Class 30 100 10 Current (% FLA) 1000% 1 100% Current (% FLA) 1000% For trip class time-current characteristics other than 5, 10, 20, or 30, scale the Class 10 trip time according to the following table: Table 165 - Time-Current Characteristic Scaling Factors Trip Class 5 6 7 8 9 10 11 12 13 Trip Class 10 Multiplier 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 Trip Class 14 15 16 17 18 19 20 21 22 Trip Class 10 Multiplier 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 Trip Class 23 24 25 26 27 28 29 30 Trip Class 10 Multiplier 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 Automatic/Manual Reset Overload Reset Mode (Parameter 173) allows you to select the reset mode for the E300 Electronic Overload Relay after an overload or thermistor (PTC) trip. If an overload trip occurs and automatic reset mode is selected, the E300 Electronic Overload Relay automatically resets when the value stored in % Thermal Capacity Utilized (Parameter 1) falls below the value stored in Overload Reset Level (Parameter 174). If manual reset mode is selected, the E300 Overload Rockwell Automation Publication 193-UM015C-EN-P - December 2014 135 Chapter 6 Protective Trip and Warning Functions Relay can be manually reset after the % Thermal Capacity Utilized is less than the OL Reset Level. Table 166 - Overload Reset Mode (Parameter 173) Overload Reset Mode (Parameter 173) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 = Manual 0 = Manual 1 = Automatic BOOL 1 1 В Table 167 - Overload Reset Level (Parameter 174) Overload Reset Level (Parameter 174) 136 Default Value 75 Minimum Value 0 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %TCU Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Overload Reset Level (Parameter 174) is adjustable from 1 to 100% TCU. The following figures illustrate the typical overload reset time delay when Overload Reset Level is set to 75% TCU. OL Reset Level (% TCU) Figure 47 - Overload Reset Times 100 90 80 70 60 50 40 30 20 10 0 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 OL Reset Level (% TCU) Time to Reset in Seconds 100 90 80 70 60 50 0 100 200 300 400 500 Time to Reset in Seconds Trip Class 5 Trip Class 10 Trip Class 20 Trip Class 30 ATTENTION: In explosive environment applications, Overload Reset Mode (Parameter 173) must be set to Manual. ATTENTION: In an explosive environment application Overload Reset Level (Parameter 174) must be set as low as possible or in accordance with the motor thermal time constant. Overload Warning The E300 Electronic Overload Relay indicates an overload warning if: • No warning currently exists • Overload warning is enabled • Current is present • % Thermal Capacity Utilized is equal to or greater than Overload Warning Level When the overload warning conditions are satisfied, the: • TRIP/WARN LED status indicator flashes a yellow short-1 blink pattern • Bit 0 in Current Warning Status (Parameter 10) sets to 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 137 Chapter 6 Protective Trip and Warning Functions • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as Warning Alarm close Overload Warning Level (Parameter 175) can be used as an alert for an impending overload trip and is adjustable from 0…100% TCU. Table 168 - Overload Warning Level (Parameter 175) Overload Warning Level (Parameter 175) Default Value 85 Minimum Value 0 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %TCU Time to Trip When the measured motor current exceeds the trip rating of the E300 Electronic Overload Relay, Overload Time to Trip (Parameter 2) indicates the estimated time remaining before an overload trip occurs. When the measured current is below the trip rating, the Overload Time to Trip value is reported as 9,999 seconds. Table 169 - Overload Time to Trip (Parameter 2) Overload Time to Trip (Parameter 2) Default Value 9999 Minimum Value 0 Maximum Value 9999 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Seconds Time To Reset After an overload trip, the E300 Electronic Overload Relay reports the time remaining until the device can be reset through Overload Time to Reset (Parameter 3). When the % Thermal Capacity Utilized value falls to or below the Overload Reset Level (Parameter 174), the Overload Time to Reset value indicates zero until the overload trip is reset. After an overload trip is reset, the Overload Time to Reset value is reported as 0 seconds. 138 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 170 - Overload Time to Reset (Parameter 3) Overload Time to Reset (Parameter 3) Default Value 0 Minimum Value 0 Maximum Value 9999 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Seconds Nonvolatile Thermal Memory The E300 Electronic Overload Relay includes a nonvolatile circuit to provide thermal memory. The time constant of the circuit corresponds to a Trip Class 20 setting. During normal operation, the thermal memory circuit is continuously monitored and updated to accurately reflect the thermal capacity utilization of the connected motor. If power is removed, the thermal memory of the circuit decays at a rate equivalent to the cooling of a Trip Class 20 application. When the power is re-applied, the E300 Electronic Overload Relay checks the thermal memory circuit voltage to determine the initial value of % Thermal Capacity Utilized (Parameter 1). Phase Loss Protection A high current imbalance, or phase failure, can be caused by defective contacts in a contactor or circuit breaker, loose terminals, blown fuses, sliced wires, or faults in the motor. When a phase failure exists, the motor can experience an additional temperature rise or excessive mechanical vibration. This may result in a degradation of the motor insulation or increased stress on the motor bearings. Rapid phase loss detection helps to minimize the potential damage and loss of production. Phase Loss Inhibit Time Phase Loss Inhibit Time (Parameter 239) allows you to inhibit a phase loss trip from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 171 - Phase Loss Inhibit Time (Parameter 239) Phase Loss Inhibit Time (Parameter 239) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 250 USINT 1 1 Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 139 Chapter 6 Protective Trip and Warning Functions IMPORTANT The phase loss inhibit timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for a phase loss condition until the Phase Loss Inhibit Time expires. Phase Loss Trip The E300 Electronic Overload Relay trips with a phase loss indication if: • No trip currently exists • Phase Loss Protection is enabled • Current is Present • Phase Loss Inhibit Time has expired • Current Imbalance is equal to or greater than 100% for a time period greater than the programmed Phase Loss Trip Delay If the E300 Electronic Overload Relay trips on a phase loss, the: • TRIP/WARN LED status indicator flashed a red short-2 blink pattern • Bit 1 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 of Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT 140 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Phase Loss Trip Delay Phase Loss Trip Delay (Parameter 240) allows you to define the time period for which a phase loss condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 172 - Phase Loss Trip Delay (Parameter 240) Phase Loss Trip Delay (Parameter 240) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Ground Fault Current Protection In isolated or high impedance-grounded systems, core-balanced current sensors are typically used to detect low-level ground faults caused by insulation breakdowns or entry of foreign objects. Detection of such ground faults can be used to interrupt the system to prevent further damage or to alert the appropriate personnel to perform timely maintenance. The E300 Electronic Overload Relay provides core-balanced ground fault current detection capability, with the option of enabling Ground Fault Trip, Ground Fault Warning, or both. The ground fault detection method and range depends upon the catalog number of the E300 Sensing Module and Control Module ordered. Table 173 - Ground Fault Capabilities Catalog Number Ground Fault Method Ground Fault Trip/Warning Range Internal 0.5…5.0 A External вћЉ 0.02…5.0 A 193-ESM-IG-__-__ 592-ESM-IG-__-__ 193-ESM-VIG-__-__ 592-ESM-VIG-__-__ 193-EIOGP-22-___ 193-EIOGP-42-___ вћЉ One of the following Catalog Number 193-CBCT_ Core Balance Ground Fault Sensors must be used: 1 — Г� 20 mm window 2 — Г� 40 mm window 3 — Г� 65 mm window 4 — Г� 85 mm window Rockwell Automation Publication 193-UM015C-EN-P - December 2014 141 Chapter 6 Protective Trip and Warning Functions ATTENTION: The E300 Electronic Overload Relay is not a ground fault circuit interrupt or for personal protection as defined in Article 100 of the NEC. ATTENTION: The E300 Electronic Overload Relay is not intended to signal a disconnecting means to open the faulted current. A disconnecting device must be capable of interrupting the maximum available fault current of the system on which it is used. Ground Fault Type The E300 Electronic Overload Relay has two options available to measure ground fault current. Ground Fault Type (Parameter 241) allows you to select the internal option or the external option with the appropriate measurement range. Table 174 - Ground Fault Type (Parameter 241) Ground Fault Type (Parameter 241) Default Value 1 = Internal 0.500…5.000 A Range 1 = Internal 0.500…5.000 A 2 = External 0.020…0.100 A 3 = External 0.100…0.500 A 4 = External 0.200…1.000 A 5 = External 1.000…5.000 A Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Ground Fault Maximum Inhibit Ground faults can quickly rise from low-level arcing levels to short circuit magnitudes. A motor starting contactor may not have the necessary rating to interrupt a high magnitude ground fault. In these circumstances it is desirable for an upstream circuit breaker with the proper rating to interrupt the ground fault. When enabled, Ground Fault Maximum Inhibit (Parameter 248), inhibits a ground fault trip from occurring when the ground fault current exceeds the maximum range of the core-balance sensor (approximately 6.5 A). 142 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 175 - Overload Reset Level (Parameter 248) Overload Reset Level (Parameter 248) Default Value 0 = Disable Minimum Value 0 = Disable Maximum Value 1 = Enable Parameter Type BOOL Size (Bytes) 1 Scaling Factor 1 Units Ground Fault Filter An E300 Electronic Overload Relay can filter ground fault currents for High Resistance Grounded (HRG) systems from its current-based protection trip and warning functions, which include: • Thermal overload • Current imbalance • Jam • Stall The Ground Fault Filter is useful for smaller-sized motors that trip unexpectedly due to a controlled ground fault current that is significant relative to the current draw of the electric motor. Ground Fault Filter (Parameter 131) allows you to enable this filter. Table 176 - Ground Fault Filter (Parameter 247 Ground Fault Filter (Parameter 247) Default Value 0 = Disable Minimum Value 0 = Disable Maximum Value 1 = Enable Parameter Type BOOL Size (Bytes) 1 Scaling Factor 1 Units This filter only disables the effects of the ground fault current from the currentbased motor protection trip and warning functions. Current-based diagnostic data is reported unfiltered when this feature is enabled. Ground Fault Inhibit Time Ground Fault Inhibit Time (Parameter 242) allows you to inhibit a ground fault trip and warning from occurring during the motor starting sequence and is adjustable from 0…250 seconds. The ground fault inhibit time begins when the Current Present (bit 3) or Ground Fault Current Present (bit 4) is set in Device Status 0 (Parameter 20). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 143 Chapter 6 Protective Trip and Warning Functions Table 177 - Ground Fault Inhibit Time (Parameter 242 Ground Fault Inhibit Time (Parameter 242) Default Value 0 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Table 178 - Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 В В В В В В В В В В В В В В В X Trip Present Function В В В В В В В В В В В В В В XВ В Warning Present В В В В В В В В В В В В В X В В Invalid Configuration В В В В В В В В В В В В XВ В В В Current Present В В В В В В В В В В В X В В В В Ground Fault Current Present В В В В В В В В В В X В В В В В Voltage Present В В В В В В В В В X В В В В В В Emergency Start Enabled В В В В В В В В В X В В В В В В В DeviceLogix Enabled В В В В В В В В X В В В В В В В В Feedback Timeout Enabled В В В В В В В X В В В В В В В В В Operator Station Present В В В В В В X В В В В В В В В В В Voltage Sensing Present В В В В В X В В В В В В В В В В В В В В В X В В В В В В В В В В В В Internal Ground Fault Sensing Present External Ground Fault Sensing Present В В В X В В В В В В В В В В В В В PTC Sensing В В X В В В В В В В В В В В В В В Ready В В В В В В В В В В В В В В В В Reserved Ground Fault Trip The E300 Electronic Overload Relay trips with a ground fault indication if: • No trip currently exists • Ground fault protection is enabled • Ground fault current is present • Ground Fault Inhibit Time has expired • Ground Fault Current is equal to or greater than the Ground Fault Trip Level for a time period greater than the Ground Fault Trip Delay If the E300 Electronic Overload Relay trips on a ground fault, the: • TRIP/WARN LED flashes a red 3-short blink pattern • Bit 2 in Current Trip Status (Parameter 4) sets to 1 144 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions • • • • • Chapter 6 Bit 0 of Device Status 0 (Parameter 20) sets to 1 Any relay outputs configured as a Trip Relay open Any relay outputs configured as a Control Relay open Any relay outputs configured as a Trip Alarm close Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Ground Fault Trip Delay Ground Fault Trip Delay (Parameter 243) allows you to define the time period a ground fault condition must be present before a trip occurs and is adjustable from 0.0…25.0 s. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 145 Chapter 6 Protective Trip and Warning Functions Table 179 - Ground Fault Trip Delay (Parameter 243) Ground Fault Trip Delay (Parameter 243) Default Value 0.5 Minimum Value 0.0 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Ground Fault Trip Level Ground Fault Trip Level (Parameter 244) allows you to define the ground fault current in which the E300 Electronic Overload Relay trips and is adjustable from: • 0.500…5.00 A (Internal) • 0.020…5.00 A (External) Table 180 - Ground Fault Trip Level (Parameter 244) Ground Fault Trip Level (Parameter 244) Default Value 2.5 Minimum Value 0.5 (internal); 0.02 (external) Maximum Value 5.00 Parameter Type UINT Size (Bytes) 2 Scaling Factor 100 Units Amps IMPORTANT The ground fault inhibit timer starts after the maximum phase load current transitions from 0 A to 30% of the minimum FLA rating of the device or the ground fault current is greater than or equal to 50% of the minimum ground fault current rating of the device. The E300 Electronic Overload Relay does not begin monitoring for a ground fault condition until the Ground Fault Current Inhibit Time expires. Ground Fault Warning The E300 Electronic Overload Relay indicates a ground fault warning if: • No warning currently exists • Ground Fault Warning is enabled • Current is present • Ground Fault Inhibit Time has expired 146 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • Ground Fault Current is equal to or greater than the Ground Fault Warning Level for a time period greater than the Ground Fault Warning Delay. When the ground fault warning conditions are satisfied, the: • TRIP/WARN LED status indicator flashes a yellow 3-short blink pattern • Bit 2 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 of Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Ground Fault Warning Level Ground Fault Warning Level (Parameter 246) allows you to define the ground fault current at which the E300 Electronic Overload Relay indicates a warning and is adjustable from 0.20…5.00 A. Table 181 - Ground Fault Warning Level (Parameter 246) Ground Fault Warning Level (Parameter 246) Default Value 2.00 Minimum Value 0.20 Maximum Value 5.00 Parameter Type UINT Size (Bytes) 2 Scaling Factor 100 Units Amps Ground Fault Warning Delay Ground Fault Warning Delay (Parameter 245) allows you to define the time period (adjustable from 0.0…25.0 s) for which a ground fault condition must be present before a warning occurs. Table 182 - Ground Fault Warning Delay (Parameter 245) Ground Fault Warning Delay (Parameter 245) Default Value 0.0 Minimum Value 0.0 Maximum Value 25.00 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 147 Chapter 6 Protective Trip and Warning Functions Stall Protection A motor stalls when its inrush current lasts for a longer than normal period of time during its starting sequence. As a result, the motor heats up rapidly and reaches the temperature limit of its insulation. Rapid stall detection during the starting sequence can extend the motor’s life, and minimize potential damage and loss of production. The E300 Electronic Overload Relay can monitor for this condition with its Stall Trip function and stop the motor before damage and loss of production can occur. Stall Trip The E300 Electronic Overload Relay trips with a Stall Trip indication when: • No trip currently exists • Stall protection is enabled • Current is present • The maximum phase current is greater than the Stall Trip Level for a time period greater than the Stall Enabled Time If the E300 Electronic Overload Relay trips on a stall, the: • TRIP/WARN LED status indicator flashes a red 4-short blink pattern • Bit 3 in Current Trip Status Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 148 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Stall Enabled Time Stall Enabled Time (Parameter 249) allows you to adjust the time the E300 Electronic Overload Relay monitors for a stall condition during the motor starting sequence and is adjustable from 0…250 s. Table 183 - Stall Enabled Time (Parameter 249) Stall Enabled Time (Parameter 249) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Stall Trip Level Stall Trip Level (Parameter 250) allows you to define the locked rotor current and is adjustable from 100…600% of the FLA Setting (Parameter 171). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 149 Chapter 6 Protective Trip and Warning Functions Table 184 - Stall Trip Level (Parameter 250) Stall Trip Level (Parameter 250) Default Value 600 Minimum Value 100 Maximum Value 600 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units %FLA IMPORTANT Stall Protection is only enabled during the motor starting sequence. If the maximum phase of load current falls below the programmed Stall Trip Level before the Stall Enabled Time elapses, the E300 Electronic Overload Relay disables Stall Protection until the next motor starting sequence. IMPORTANT The E300 Electronic Overload Relay considers a motor to have begun its starting sequence if the maximum phase of motor current transitions from 0A to approximately 30% of the minimum FLA setting of the device. Jam Protection A motor goes into a jam condition when a running motor begins to consume current greater than50% of the motor’s nameplate rating. An example of this condition could be an overloaded conveyor or jammed gear. These conditions can result in the overheating of the motor and equipment damage. The E300 Electronic Overload Relay can monitor for this condition with its Jam Trip and Warning function to detect for a rapid jam fault to minimize damage and loss of production. Jam Inhibit Time Jam Inhibit Time (Parameter 251) allows you to inhibit a jam trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 s. TableВ 185 ‐ JamВ TripВ InhibitВ TimeВ (ParameterВ 251) 150 Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Jam Trip The E300 Electronic Overload Relay trips with a jam indication if: • No trip currently exists • Jam Trip is enabled • Jam Inhibit Time has expired • The maximum phase current is greater than the Jam Trip Level for a time period greater than the Jam Trip Delay. If the E300 Electronic Overload Relay trips on a jam, the: • TRIP/WARN LED status indicator flashes a red 5-short blink pattern • Bit 4 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Jam Trip Delay Jam Trip Delay (Parameter 252) allows you to define the time period a jam condition must be present before a trip occurs. It is adjustable from пЂ 0.1…25.0 s. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 151 Chapter 6 Protective Trip and Warning Functions Table 186 - Jam Trip Delay (Parameter 252) Default Value 5.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Jam Trip Level Jam Trip Level (Parameter 253) allows you to define the current at which the E300 Electronic Overload Relay trips on a jam. It is user-adjustable from 50…600% of the FLA Setting (Parameter 171). Table 187 - Jam Trip Level (Parameter 253) Default Value 250 Minimum Value 50 Maximum Value 600 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units %FLA IMPORTANT The Jam Inhibitor timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum fla SETTING of the device. The E300 Electronic Overload Relay does not begin monitoring for a jam condition until the Jam Inhibit Time expires. Jam Warning The E300 Electronic Overload Relay indicates a Jam warning if: • No warning currently exists • Jam Warning is enabled • Current is present • Jam Inhibit Time has expired • The maximum phase current is equal to or greater than the Jam Warning Level When the Jam Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 5-short blink pattern • Bit 4 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close 152 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Jam Warn Level Jam Warn Level (Parameter 254) allows you to define the current at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 50…600% for the FLA Setting (Parameter 171). Table 188 - Jam Warning Level (Parameter 254) Default Value 150 Minimum Value 50 Maximum Value 600 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units %FLA IMPORTANT The Jam Warning function does not include a time delay feature. Once the Jam Inhibit Time has expired, the Jam Warning indication is instantaneous. Underload Protection Motor current less than a specific level may indicate a mechanical malfunction in the installation, such as a torn conveyor belt, damaged fan blade, broken shaft, or worn tool. Such conditions may not harm the motor, but they can lead to loss of production. Rapid underload fault detection helps to minimize damage and loss of production. The E300 Electronic Overload Relay can monitor for this condition with its Underload Trip and Warning function to detect for a rapid underload fault to minimize damage and loss of production. Underload Inhibit Time Underload Inhibit Time (Parameter 255) allows you to inhibit an underload trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 s. Table 189 - Underload Inhibit Time (Parameter 255) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 153 Chapter 6 Protective Trip and Warning Functions Underload Trip The E300 Electronic Overload Relay trips with an underload indication if: • No trip currently exists • Underload Trip is enabled • Current is present • Underload Inhibit Time has expired • Minimum phase current is less than the Underload Trip Level for a time period greater than the Underload Trip Delay. If the E300 Electronic Overload Relay trips on an underload, the: • TRIP/WARN LED status indicator flashes a red 6-short blink pattern • Bit 5 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Underload Trip Delay Underload Trip Delay (Parameter 256) allows you to define the time period an underload condition must be present before a trip occurs. It is adjustable from 0.1…25.0 s. 154 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 190 - Underload Trip Delay (Parameter 256) Default Value 5.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Underload Trip Level Underload Trip Level (Parameter 257) allows you to define the current at which the E300 Electronic Overload Relay trips on an underload. It is user-adjustable from 10…100% of the FLA Setting (Parameter 171). Table 191 - Underload Trip Level (Parameter 257) Default Value 50 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The Underload Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum fla SETTING of the device. The E300 Electronic Overload Relay does not begin monitoring for an underload condition until the Underload Inhibit Time expires. IMPORTANT For any given application, the practical limit of the Underload Trip Level (Parameter 246) is dependent on the FLA Setting and the lower limit of the E300 Electronic Overload Relay’s current measurement capability. Underload Warning The E300 Electronic Overload Relay indicates an underload warning if: • No warning currently exists • Underload Warning is enabled • Current is present • Underload Inhibit Time has expired • The minimum phase current is less than the Underload Warning Level Rockwell Automation Publication 193-UM015C-EN-P - December 2014 155 Chapter 6 Protective Trip and Warning Functions When the Underload Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 6-short blink pattern • Bit 5 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Underload Warning Level Underload Warning Level (Parameter 258) allows you to define the current at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 10…100% for the FLA Setting (Parameter 171). Table 192 - Underload Warning Level (Parameter 258) Default Value 70 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The Underload Warning function does not include a time delay feature. Once the Underload Inhibit Time has expired, the Underload Warning indication is instantaneous. Current Imbalance Protection A current imbalance can be caused by an imbalance in the voltage supply, unequal motor winding impedance, or long and varying wire lengths. When a current imbalance exists, the motor can experience an additional temperature rise, resulting in degradation of the motor insulation and reduction of life expectancy. The E300 Electronic Overload Relay can monitor for this condition with its Current Imbalance Trip and Warning function to detect for a rapid current imbalance fault to minimize damage and loss of production. Current Imbalance can be defined by the following equation: %CI = 100% * (Id/Ia)пЂ where %CI = Percent Current ImbalanceпЂ Id = Maximum Deviation from the Average CurrentпЂ Ia = Average Current 156 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Current Imbalance Inhibit Time Current Imbalance Inhibit Time (Parameter 259) allows you to inhibit a current imbalance trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 s. Table 193 - Current Imbalance Inhibit Time (Parameter 259) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Current Imbalance Trip The E300 Electronic Overload Relay trips with a current imbalance indication if: • No trip currently exists • Current Imbalance Trip is enabled • Current is present • Current Imbalance Inhibit Time has expired • The Current Imbalance (parameter 52) is greater than the Current Imbalance Trip Level for a time period greater than the Current Imbalance Trip Delay. If the E300 Electronic Overload Relay trips on a current imbalance, the: • TRIP/WARN LED status indicator flashes a red 7-short blink pattern • Bit 6 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 157 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Current Imbalance Trip Delay Current Imbalance Trip Delay (Parameter 260) allows you to define the time period a current imbalance condition must be present before a trip occurs. It is adjustable from 0.1…25.0 s. Table 194 - Current Imbalance Trip Delay (Parameter 260) Default Value 5.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Current Imbalance Trip Level Current Imbalance Trip Level (Parameter 261) allows you to define the percentage at which the E300 Electronic Overload Relay trips on a current imbalance. It is user-adjustable from 10…100%. 158 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 195 - Current Imbalance Trip Level (Parameter 261) Default Value 35 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Current Imbalance Inhibit Timer starts after a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for a current imbalance condition until the Current Imbalance Inhibit Time expires. Current Imbalance Warning The E300 Electronic Overload Relay indicates a current imbalance warning if: • No warning currently exists • Current Imbalance Warning is enabled • Current is present • Current Imbalance Inhibit Time has expired • The current imbalance (parameter 52) is greater than the Current Imbalance Warning Level When the Current Imbalance Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 7-short blink pattern • Bit 6 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Current Imbalance Warning Level Current Imbalance Warning Level (Parameter 262) allows you to define the percentage at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 10…100%. Table 196 - Current Imbalance Warning Level (Parameter 262) Default Value 20 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units % Rockwell Automation Publication 193-UM015C-EN-P - December 2014 159 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Current Imbalance Warning function does not include a time delay feature. Once the Current Imbalance Inhibit Time has expired, the Current Imbalance Warning indication is instantaneous. Line Under Current Protection For non-motor applications when the measured current is less than a specific level for a specific phase may indicate an electrical malfunction, such as bad resistive heater element or non-operating incandescent light bulb. Such conditions may not harm the power system, but it can lead to loss of production or certification noncompliance. The E300 Electronic Overload Relay can monitor for an undercurrent condition per phase with its Line Under Current Trip and Warning function to detect for a rapid under current in a specific phase to minimize damage and loss of production. Under Current Inhibit Time Under Current Inhibit Time (Parameter 265) allows you to inhibit an L1, L2, and L3 Under Current trip and warning from occurring during a load starting sequence. It is adjustable from 0…250 seconds. Table 197 - Under Current Inhibit Time (Parameter 265) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds L1 Under Current Trip The E300 Electronic Overload Relay trips with a L1 Under Current indication if: • No trip currently exists • L1 Under Current Trip is enabled • Current is present • Under Current Inhibit Timer has expired • L1 Percent FLA (Parameter 47) is less than the L1 Under Current Trip Level for a time period greater than the L1 Under Current Trip Delay. • If the E300 Electronic Overload Relay trips on a L1 Under Current, the: • TRIP/WARN LED status indicator flashes a red 8-short blink pattern 160 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions • • • • • • Chapter 6 Bit 7 in Current Trip Status (Parameter 4) sets to 1 Bit 0 in Device Status 0 (Parameter 20) sets to 1 Any relay outputs configured as a Trip Relay open Any relay outputs configured as a Control Relay open Any relay outputs configured as a Trip Alarm close Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L1 Under Current Trip Delay L1 Under Current Trip Delay (Parameter 266) allows you to define the time period an L1 Under Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 198 - L1 Under Current Trip Delay (Parameter 266) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1.0 0.1 25.0 USINT 1 10 Seconds 161 Chapter 6 Protective Trip and Warning Functions L1 Under Current Trip Level L1 Under Current Trip Level (Parameter 267) allows you to define the current at which the E300 Electronic Overload Relay trips on a L1 Under Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter 171). Table 199 - L1 Under Current Trip Level (Parameter 267) Default Value 35 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The Under Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an undercurrent condition until the Under Current Inhibit Time expires. IMPORTANT For any given application, the practical limit of the L1 Under Current Trip Level (Parameter 267) is dependent on the FLA Setting and the lower limit of the E300 Electronic Overload Relay’s current measurement capability L1 Under Current Warning The E300 Electronic Overload Relay indicates an L1 Under Current warning if: • No warning currently exists • L1 Under Current Warning is enabled • Current is present • The Under Current Inhibit Timer has expired • L1 Percent FLA (Parameter 47) is less than the L1 Under Current Warning Level When the L1 Under Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 8-short blink pattern • Bit 7 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close L1 Under Current Warning Level L1 Under Current Warning Level (Parameter 268) allows you to define the current at which the E300 Electronic Overload Relay indicates a L1 Under 162 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). Table 200 - L1 Under Current Warning Level (Parameter 268) Default Value 40 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The L1 Under Current Warning function does not include a time delay feature. Once the Under Current Inhibit Timer has expired, the L1 Under Current Warning indication is instantaneous. L2 Under Current Trip The E300 Electronic Overload Relay trips with a L2 Under Current indication if: • No trip currently exists • L2 Under Current Trip is enabled • Current is present • Under Current Inhibit Timer has expired • L2 Percent FLA (Parameter 48) is less than the L2 Under Current Trip Level for a time period greater than the L2 Under Current Trip Delay. If the E300 Electronic Overload Relay trips on a L2 Under Current, the: • TRIP/WARN LED status indicator flashes a red 9-short blink pattern • Bit 8 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 163 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L2 Under Current Trip Delay L2 Under Current Trip Delay (Parameter 269) allows you to define the time period an L2 Under Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 201 - L2 Under Current Trip Delay (Parameter 269) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds L2 Under Current Trip Level L2 Under Current Trip Level (Parameter 270) allows you to define the current at which the E300 Electronic Overload Relay trips on a L2 Under Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter 171). 164 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 202 - L2 Under Current Trip Level Parameter 270) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 35 10 100 USINT 1 1 %FLA IMPORTANT The Under Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an undercurrent condition until the Under Current Inhibit Time expires. IMPORTANT For any given application, the practical limit of the L2 Under Current Trip Level (Parameter 270) is dependent on the FLA Setting and the lower limit of the E300 Electronic Overload Relay’s current measurement capability L2 Under Current Warning The E300 Electronic Overload Relay indicates an L2 Under Current warning if: • No warning currently exists • 2 Under Current Warning is enabled • Current is present • The Under Current Inhibit Timer has expired • 2 Percent FLA (Parameter 48) is less than the L2 Under Current Warning Level When the L2 Under Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 9-short blink pattern • Bit 8 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close L2 Under Current Warning Level L2 Under Current Warning Level (Parameter 271) allows you to define the current at which the E300 Electronic Overload Relay indicates a L2 Under Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 165 Chapter 6 Protective Trip and Warning Functions Table 203 - L2 Under Current Warning Level (Parameter 271) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 40 10 100 USINT 1 1 %FLA The L2 Under Current Warning function does not include a time delay feature. Once the Under Current Inhibit Timer has expired, the L2 Under Current Warning indication is instantaneous. L3 Under Current Trip The E300 Electronic Overload Relay trips with a L3 Under Current indication if: • No trip currently exists • L3 Under Current Trip is enabled • Current is present • Under Current Inhibit Timer has expired • Percent FLA (Parameter 49) is less than the L3 Under Current Trip Level for a time period greater than the L3 Under Current Trip Delay. If the E300 Electronic Overload Relay trips on a L3 Under Current, the: • TRIP/WARN LED status indicator flashes a red 10-short blink pattern • Bit 9 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 166 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) IMPORTANT L3 Under Current Trip Delay (Parameter 272) allows you to define the time period that an L3 Under Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds Table 204 - L3 Under Current Trip Delay (Parameter 272) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds L3 Under Current Trip Level L3 Under Current Trip Level (Parameter 273) allows you to define the current at which the E300 Electronic Overload Relay trips on a L3 Under Current. It is user-adjustable from 10…100% of the FLA Setting (Parameter 171). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 167 Chapter 6 Protective Trip and Warning Functions Table 205 - L3 Under Current Trip Level (Parameter 273) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 35 10 100 USINT 1 1 %FLA IMPORTANT The Under Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an undercurrent condition until the Under Current Inhibit Time expires. IMPORTANT For any given application, the practical limit of the L3 Under Current Trip Level (Parameter 273) is dependent on the FLA Setting and the lower limit of the E300 Electronic Overload Relay’s current measurement capability L3 Under Current Warning The E300 Electronic Overload Relay indicates an L3 Under Current warning if: • No warning currently exists • L3 Under Current Warning is enabled • Current is present • The Under Current Inhibit Timer has expired • L3 Percent FLA (Parameter 49) is less than the L3 Under Current Warning Level When the L3 Under Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 10-short blink pattern • Bit 9 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close L3 Under Current Warning Level L3 Under Current Warning Level (Parameter 274) allows you to define the current at which the E300 Electronic Overload Relay indicates a L3 Under Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). 168 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 206 - L3 Under Current Warning Level (Parameter 274) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 40 10 100 USINT 1 1 %FLA The L3 Under Current Warning function does not include a time delay feature. Once the Under Current Inhibit Timer has expired, the L3 Under Current Warning indication is instantaneous. Line Over Current Protection For non-motor applications when the measured current is greater than a specific level for a specific phase may indicate an electrical malfunction, such as bad resistive heater element. Such conditions could harm the power system over a period of time, which could lead to loss of production. The E300 Electronic Overload Relay can monitor for an overcurrent condition per phase with its Line Over Current Trip and Warning function to detect for a rapid over current in a specific phase to minimize damage and loss of production. Over Current Inhibit Time Over Current Inhibit Time (Parameter 275) allows you to inhibit an L1, L2, and L3 Over Current trip and warning from occurring during a load starting sequence. It is adjustable from 0…250 seconds. Table 207 - Over Current Inhibit Time (Parameter 275) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds L1 Over Current Trip The E300 Electronic Overload Relay trips with a L1 Over Current indication if: • No trip currently exists • L1 Over Current Trip is enabled • Current is present Rockwell Automation Publication 193-UM015C-EN-P - December 2014 169 Chapter 6 Protective Trip and Warning Functions • Over Current Inhibit Timer has expired • L1 Percent FLA (Parameter 47) is greater than the L1 Over Current Trip Level for a time period greater than the L1 Over Current Trip Delay. If the E300 Electronic Overload Relay trips on a L1 Over Current, the: • TRIP/WARN LED status indicator flashes a red 11-short blink pattern • Bit 10 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L1 Over Current Trip Delay L1 Over Current Trip Delay (Parameter 276) allows you to define the time period an L1 Over Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. 170 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 208 - L1 Over Current Trip Delay (Parameter 276) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds L1 Over Current Trip Level L1 Over Current Trip Level (Parameter 277) allows you to define the current at which the E300 Electronic Overload Relay trips on a L1 Over Current. It is useradjustable from 10…100% of the FLA Setting (Parameter 171). Table 209 - L1 Over Current Trip Level (Parameter 277) Default Value 100 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The Over Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an overcurrent condition until the Over Current Inhibit Time expires. L1 Over Current Warning The E300 Electronic Overload Relay indicates an L1 Over Current warning if: • No warning currently exists • 1 Over Current Warning is enabled • Current is present • The Over Current Inhibit Timer has expired • 1 Percent FLA (Parameter 47) is greater than the L1 Over Current Warning Level When the L1 Over Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 11-short blink pattern • Bit 10 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Rockwell Automation Publication 193-UM015C-EN-P - December 2014 171 Chapter 6 Protective Trip and Warning Functions L1 Over Current Warning Level L1 Over Current Warning Level (Parameter 278) allows you to define the current at which the E300 Electronic Overload Relay indicates a L1 Over Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). Table 210 - L1 Over Current Warning Level (Parameter 278) Default Value 90 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The L1 Over Current Warning function does not include a time delay feature. Once the Over Current Inhibit Timer has expired, the L1 Over Current Warning indication is instantaneous. L2 Over Current Trip The E300 Electronic Overload Relay trips with a L2 Over Current indication if: • No trip currently exists • 2 Over Current Trip is enabled • Current is present • Over Current Inhibit Timer has expired • 2 Percent FLA (Parameter 48) is greater than the L2 Over Current Trip Level for a time period greater than the L2 Over Current Trip Delay. If the E300 Electronic Overload Relay trips on a L2 Over Current, the: • TRIP/WARN LED status indicator flashes a red 12-short blink pattern • Bit 11 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 172 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L2 Over Current Trip Delay L2 Over Current Trip Delay (Parameter 279) allows you to define the time period an L2 Over Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 211 - L2 Over Current Trip Delay (Parameter 279) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds L2 Over Current Trip Level L2 Over Current Trip Level (Parameter 280) allows you to define the current at which the E300 Electronic Overload Relay trips on a L2 Over Current. It is useradjustable from 10…100% of the FLA Setting (Parameter 171) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 173 Chapter 6 Protective Trip and Warning Functions Table 212 - L2 Over Current Trip Level (Parameter 280). Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 100 10 100 USINT 1 1 %FLA The Over Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an overcurrent condition until the Over Current Inhibit Time expires. L2 Over Current Warning The E300 Electronic Overload Relay indicates an L2 Over Current warning if: • No warning currently exists • 2 Over Current Warning is enabled • Current is present • The Over Current Inhibit Timer has expired • 2 Percent FLA (Parameter 48) is greater than the L2 Over Current Warning Level When the L2 Over Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 12-short blink pattern • Bit 11 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes L2 Over Current Warning Level L2 Over Current Warning Level (Parameter 281) allows you to define the current at which the E300 Electronic Overload Relay indicates a L2 Over Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). Table 213 - L2 Over Current Warning Level (Parameter 281) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 174 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 90 10 100 USINT 1 1 %FLA Protective Trip and Warning Functions Chapter 6 . IMPORTANT The L2 Over Current Warning function does not include a time delay feature. Once the Over Current Inhibit Timer has expired, the L2 Over Current Warning indication is instantaneous. L3 Over Current Trip The E300 Electronic Overload Relay trips with a L3 Over Current indication if: • No trip currently exists • L3 Over Current Trip is enabled • Current is present • Over Current Inhibit Timer has expired • L3 Percent FLA (Parameter 49) is greater than the L3 Over Current Trip Level for a time period greater than the L3 Over Current Trip Delay. If the E300 Electronic Overload Relay trips on a L3 Over Current, the: • TRIP/WARN LED status indicator flashes a red 13-short blink pattern • Bit 12 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 175 Chapter 6 Protective Trip and Warning Functions L3 Over Current Trip Delay L3 Over Current Trip Delay (Parameter 282) allows you to define the time period an L3 Over Current condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 214 - L3 Over Current Trip Delay (Parameter 282) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds L3 Over Current Trip Level L3 Over Current Trip Level (Parameter 283) allows you to define the current at which the E300 Electronic Overload Relay trips on a L3 Over Current. It is useradjustable from 10…100% of the FLA Setting (Parameter 171). Table 215 - L3 Over Current Trip Level (Parameter 283) Default Value 100 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The Over Current Inhibit Timer starts after the maximum phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an overcurrent condition until the Over Current Inhibit Time expires. L3 Over Current Warning The E300 Electronic Overload Relay indicates an L3 Over Current warning if: • No warning currently exists • L3 Over Current Warning is enabled • Current is present • The Over Current Inhibit Timer has expired • L3 Percent FLA (Parameter 49) is greater than the L3 Over Current Warning Level 176 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 When the L2 Over Current Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 13-short blink pattern • Bit 12 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes L3 Over Current Warning Level L3 Over Current Warning Level (Parameter 284) allows you to define the current at which the E300 Electronic Overload Relay indicates a L3 Over Current warning. It is user-adjustable from 10…100% for the FLA Setting (Parameter 171). Table 216 - L3 Over Current Warning Level (Parameter 284) Default Value 90 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units %FLA IMPORTANT The L3 Over Current Warning function does not include a time delay feature. Once the Over Current Inhibit Timer has expired, the L3 Over Current Warning indication is instantaneous. Line Loss Protection For non-motor applications when the measured current is 0 amps a specific phase, this may indicate an electrical malfunction such as bad resistive heater element or non-operating incandescent light bulb. Such conditions may not harm the power system, but it can lead to loss of production or certification noncompliance. The E300 Electronic Overload Relay can monitor for a current-based line loss per phase with its Line Loss Trip and Warning function to detect for a rapid line loss in a specific phase to minimize damage and loss of production. Line Loss Inhibit Time Line Loss Inhibit Time (Parameter 285) allows you to inhibit an L1, L2, and L3 Line Loss trip and warning from occurring during a load starting sequence. It is adjustable from 0…250 seconds. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 177 Chapter 6 Protective Trip and Warning Functions Table 217 - Line Loss Inhibit Time (Parameter 285) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds L1 Line Loss Trip The E300 Electronic Overload Relay trips with a L1 Line Loss indication if: • No trip currently exists • L1 Over Current Trip is enabled • L1 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L1 Percent FLA (Parameter 47) is • equal to 0% for a time period greater than the L1 Line Loss Trip Delay. If the E300 Electronic Overload Relay trips on a L1 Line Loss, the: • TRIP/WARN LED status indicator flashes a red 14-short blink pattern • Bit 13 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 178 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L1 Line Loss Trip Delay L1 Line Loss Trip Delay (Parameter 276) allows you to define the time period an L1 Line Loss condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 218 - L1 Line Loss Trip Delay (Parameter 286) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds IMPORTANT The Line Loss Inhibit Timer starts when L1, L2, or L3 Line Loss protection is activated by a programmed digital input (see Input Assignment Parameters 196-201). The E300 Electronic Overload Relay does not begin monitoring for Line Loss condition until the Line Loss Inhibit Timer expires. L1 Line Loss Warning The E300 Electronic Overload Relay indicates an L1 Line Loss warning if: • No warning currently exists Rockwell Automation Publication 193-UM015C-EN-P - December 2014 179 Chapter 6 Protective Trip and Warning Functions • L1 Line Loss Warning is enabled • L1 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L1 Percent FLA (Parameter 47) is equal to 0% When the L1 Line Loss Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 14-short blink pattern • Bit 13 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes IMPORTANT The L1 Line Loss Warning function does not include a time delay feature. Once the Line Loss Inhibit Timer has expired, the L1 Line Loss Warning indication is instantaneous. L2 Line Loss Trip The E300 Electronic Overload Relay trips with a L2 Line Loss indication if: • No trip currently exists • L2 Over Current Trip is enabled • L2 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L2 Percent FLA (Parameter 48) is equal to 0% for a time period greater than the L2 Line Loss Trip Delay. If the E300 Electronic Overload Relay trips on a L2 Line Loss, the: • TRIP/WARN LED status indicator flashes a red 15-short blink pattern • Bit 14 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 180 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L2 Line Loss Trip Delay L2 Line Loss Trip Delay (Parameter 287) allows you to define the time period an L2 Line Loss condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 219 - L2 Line Loss Trip Delay (Parameter 287) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds IMPORTANT The Line Loss Inhibit Timer starts when L1, L2, or L3 Line Loss protection is activated by a programmed digital input (see Input Assignment Parameters 196-201). The E300 Electronic Overload Relay does not begin monitoring for Line Loss condition until the Line Loss Inhibit Timer expires. L2 Line Loss Warning The E300 Electronic Overload Relay indicates an L2 Line Loss warning if: • No warning currently exists Rockwell Automation Publication 193-UM015C-EN-P - December 2014 181 Chapter 6 Protective Trip and Warning Functions • L2 Line Loss Warning is enabled • L2 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L2 Percent FLA (Parameter 48) is equal to 0% When the L2 Line Loss Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 15-short blink pattern • Bit 14 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes IMPORTANT The L2 Line Loss Warning function does not include a time delay feature. Once the Line Loss Inhibit Timer has expired, the L2 Line Loss Warning indication is instantaneous. L3 Line Loss Trip The E300 Electronic Overload Relay trips with a L3 Line Loss indication if: • No trip currently exists • L3 Over Current Trip is enabled • L3 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L3 Percent FLA (Parameter 49) is equal to 0% for a time period greater than the L3 Line Loss Trip Delay. If the E300 Electronic Overload Relay trips on a L3 Line Loss, the: • TRIP/WARN LED status indicator flashes a red 16-short blink pattern • Bit 15 in Current Trip Status (Parameter 4) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 182 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) L3 Line Loss Trip Delay L3 Line Loss Trip Delay (Parameter 288) allows you to define the time period an L3 Line Loss condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 220 - L3 Line Loss Trip Delay (Parameter 288) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds IMPORTANT The Line Loss Inhibit Timer starts when L1, L2, or L3 Line Loss protection is activated by a programmed digital input (see Input Assignment Parameters 196-201). The E300 Electronic Overload Relay does not begin monitoring for Line Loss condition until the Line Loss Inhibit Timer expires. L3 Line Loss Warning The E300 Electronic Overload Relay indicates an L3 Line Loss warning if: • No warning currently exists Rockwell Automation Publication 193-UM015C-EN-P - December 2014 183 Chapter 6 Protective Trip and Warning Functions • L3 Line Loss Warning is enabled • L3 Line Loss is activated via the appropriately programmed digital input (see Input Assignments, Parameters 196…201, in Chapter 4) • Line Loss Inhibit Timer has expired • L3 Percent FLA (Parameter 49) is equal to 0% When the L3 Line Loss Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 16-short blink pattern • Bit 15 in Current Warning Status (Parameter 10) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close IMPORTANT Voltage-based Protection The L3 Line Loss Warning function does not include a time delay feature. Once the Line Loss Inhibit Timer has expired, the L3 Line Loss Warning indication is instantaneous. The E300 Electronic Overload Relay can digitally monitor the voltage supplied to an electric motor to help protect against poor voltage quality. You can prevent a contactor from energizing if the voltage is either too high, too low, or wrong rotation. The following E300 Sensing Modules provide voltage monitoring capabilities. Table 221 - Voltage Capabilities Catalog Number Measurement Method L-L Voltage Trip/Warning Range 193-ESM-VIG-__-__ Internal 20…800V 592-ESM-VIG-__-__ Internal 20…800V 193-ESM-VIG-30A-CT External 20…6500V This voltage information is used for the following protective trip and warning functions: • Undervoltage trip/warning • Overvoltage trip/warning • Voltage imbalance trip/warning • Phase rotation mismatch trip • Under frequency trip/warning • Over frequency trip/warning Voltage Trip Enable (Parameter 184) and Voltage Warning Enable (Parameter 190) are used to enable the respective voltage-based protective trip and warning functions. 184 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 222 - Voltage Trip Enabled (Parameter 184) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Under Voltage Trip X Over Voltage Trip X Voltage Imbalance Trip X Phase Rotation Mismatch Trip X Under Frequency Trip X Over Frequency Trip Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Table 223 - Voltage Warning Enable (Parameter 190) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Under Voltage Warning X X X X X Over Voltage Warning Voltage Imbalance Warning Phase Rotation Mismatch Warning Under Frequency Warning Over Frequency Warning Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Voltage Trip Status (Parameter 5) and Voltage Warning Status (Parameter 11) are used to view the status of the respective voltage-based protective trip and warning functions. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 185 Chapter 6 Protective Trip and Warning Functions Table 224 - Voltage Trip Status (Parameter 5) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Under Voltage Trip X Over Voltage Trip X Voltage Imbalance Trip X Phase Rotation Mismatch Trip X Under Frequency Trip X Over Frequency Trip Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Table 225 - Voltage Warning Status (Parameter 11) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Under Voltage Warning X X X X X Over Voltage Warning Voltage Imbalance Warning Phase Rotation Mismatch Warning Under Frequency Warning Over Frequency Warning Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 186 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Under Voltage Protection Electric motors consume more electric current when the voltage supplied to the motor is lower than the motor nameplate rating. This can damage to an electric motor over an extended period of time. The E300 Electronic Overload Relay can monitor for this condition with its Under Voltage Trip and Warning function to detect for low voltage levels to minimize motor damage and loss of production. Under Voltage Inhibit Time Under Voltage Inhibit Time (Parameter 355) allows you to inhibit an under voltage trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 226 - Under Voltage Inhibit Time (Parameter 355) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under Voltage Trip The E300 Electronic Overload Relay trips with an undervoltage indication if: • No trip currently exists • Under Voltage Trip is enabled • Voltage is present • Under Voltage Inhibit Time has expired • The minimum phase voltage is less than the Under Voltage Trip Level for a time period greater than the Under Voltage Trip Delay. If the E300 Electronic Overload Relay trips on an under voltage, the: • TRIP/WARN LED status indicator flashes a red 1-long / 1-short blink pattern • Bit 0 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 187 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under Voltage Trip Delay Under Voltage Trip Delay (Parameter 356) allows you to define the time period an under voltage condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 227 - Under Voltage Trip Delay (Parameter 356) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under Voltage Trip Level Under Voltage Trip Level (Parameter 357) allows you to define the voltage at which the E300 Electronic Overload Relay trips on an under voltage. It is useradjustable from 0…6553.5 volts. 188 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 228 - Under Voltage Trip Level (Parameter 357) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 100.0 0.0 6553.5 UINT 2 10 Volts The Under Voltage Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for an under voltage condition until the Under Voltage Inhibit Time expires. Under Voltage Warning The E300 Electronic Overload Relay indicates an Under Voltage warning if: • No warning currently exists • Under Voltage Warning is enabled • Voltage is present • Under Voltage • Inhibit Time has expired • The minimum phase voltage is equal to or less than the Under Voltage Warning Level When the Under Voltage Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 1-long / 1-short blink pattern • Bit 0 in Voltage Warning Status (Parameter 11) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Under Voltage Warn Level Under Voltage Warn Level (Parameter 358) allows you to define the voltage at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 0…6553.5 volts. Table 229 - Under Voltage Warn Level Default Value 400.0 Minimum Value 0.0 Maximum Value 6553.5 Parameter Type UINT Size (Bytes) 2 Scaling Factor 10 Units Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 189 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Under Voltage Warning function does not include a time delay feature. Once the Under Voltage Inhibit Time has expired, the Under Voltage Warning indication is instantaneous. Over Voltage Protection The winding insulation for electric motors degrades faster when more voltage is supplied to the motor than the motor nameplate rating. This can damage to an electric motor over an extended period of time. The E300 Electronic Overload Relay can monitor for this condition with its Over Voltage Trip and Warning function to detect for high voltage levels to minimize motor damage and loss of production. Over Voltage Inhibit Time Over Voltage Inhibit Time (Parameter 359) allows you to inhibit an over voltage trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Default Value 10.0 Minimum Value 0.0 Maximum Value 250.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 11 Units Seconds Over Voltage Trip The E300 Electronic Overload Relay trips with an Over Voltage indication if: • No trip currently exists • Over Voltage Trip is enabled • Voltage is present • Over Voltage Inhibit Time has expired • The minimum phase voltage is greater than the Over Voltage Trip Level for a time period greater than the Over Voltage Trip Delay. If the E300 Electronic Overload Relay trips on an over voltage, the: • TRIP/WARN LED status indicator flashes a red 1-long / 2-short blink pattern • Bit 1 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open 190 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over Voltage Trip Delay Over Voltage Trip Delay (Parameter 360) allows you to define the time period an over voltage condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 230 - Over Voltage Trip Delay (Parameter 360) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over Voltage Trip Level Over Voltage Trip Level (Parameter 357) allows you to define the voltage at which the E300 Electronic Overload Relay trips on an over voltage. It is useradjustable from 0…6553.5 volts. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 191 Chapter 6 Protective Trip and Warning Functions Table 231 - Over Voltage Trip Level (Parameter 361) Default Value 500.0 Minimum Value 0.0 Maximum Value 6553.5 Parameter Type UINT Size (Bytes) 2 Scaling Factor 10 Units Volts IMPORTANT The Over Voltage Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for an over voltage condition until the Over Voltage Inhibit Time expires. Over Voltage Warning The E300 Electronic Overload Relay indicates an Over Voltage warning if: • No warning currently exists • Over Voltage Warning is enabled • Voltage is present • Over Voltage Inhibit Time has expired • The maximum phase voltage is equal to or greater than the Over Voltage Warning Level When the Over Voltage Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 1-long / 2-short blink pattern • Bit 1 in Voltage Warning Status (Parameter 11) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Over Voltage Warn Level Over Voltage Warn Level (Parameter 362) allows you to define the voltage at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 0…6553.5 volts. Table 232 - Over Voltage Warn Level (Parameter 362) 192 Default Value 490.0 Minimum Value 0.0 Maximum Value 6553.5 Parameter Type UINT Size (Bytes) 2 Scaling Factor 10 Units Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Over Voltage Warning function does not include a time delay feature. Once the Over Voltage Inhibit Time has expired, the Over Voltage Warning indication is instantaneous. Voltage Imbalance Protection A voltage imbalance can be caused by poor power quality and unequal distribution of power. When a voltage imbalance exists, the motor can experience an additional temperature rise, resulting in degradation of the motor insulation and reduction of life expectancy. The E300 Electronic Overload Relay can monitor for this condition with its Voltage Imbalance Trip and Warning function to detect for a rapid voltage imbalance fault to minimize damage and loss of production. Voltage Imbalance can be defined by the following equation: %VImb = 100% * (Vd/Va) where %VImb = Percent Voltage Imbalance Vd = Maximum Deviation from the Average Voltage Va = Average Voltage Voltage Imbalance Inhibit Time Voltage Imbalance Inhibit Time (Parameter 365) allows you to inhibit a voltage imbalance trip from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 233 - Voltage Imbalance Inhibit Time (Parameter 365) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Voltage Imbalance Trip The E300 Electronic Overload Relay trips with a voltage imbalance indication if: • No trip currently exists Rockwell Automation Publication 193-UM015C-EN-P - December 2014 193 Chapter 6 Protective Trip and Warning Functions • • • • Voltage Imbalance Trip is enabled Voltage is present Voltage Imbalance Inhibit Time has expired The Voltage Imbalance (Parameter 61) is greater than the Voltage Imbalance Trip Level for a time period greater than the Voltage Imbalance Trip Delay. If the E300 Electronic Overload Relay trips on a voltage imbalance, the: • TRIP/WARN LED status indicator flashes a red 1-long / 3-short blink pattern • Bit 2 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Voltage Imbalance Trip Delay Voltage Imbalance Trip Delay (Parameter 366) allows you to define the time period a voltage imbalance condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. 194 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 234 - Voltage Imbalance Trip Delay (Parameter 366) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Voltage Imbalance Trip Level Voltage Imbalance Trip Level (Parameter 367) allows you to define the percentage at which the E300 Electronic Overload Relay trips on a voltage imbalance. It is user-adjustable from 10…100%. Table 235 - Voltage Imbalance Trip Level (Parameter 367) Default Value 15 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Voltage Imbalance Inhibit Timer starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for a voltage imbalance condition until the Voltage Imbalance Inhibit Time expires. Voltage Imbalance Warning The E300 Electronic Overload Relay indicates a voltage imbalance warning if: • No warning currently exists • Voltage Imbalance Warning is enabled • Voltage is present • Voltage Imbalance Inhibit Time has expired • The Voltage Imbalance (Parameter 61) is greater than the Voltage Imbalance Warning Level When the Voltage Imbalance Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow red 1-long / 3-short blink pattern • Bit 2 in Voltage Warning Status (Parameter 11) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Rockwell Automation Publication 193-UM015C-EN-P - December 2014 195 Chapter 6 Protective Trip and Warning Functions Voltage Imbalance Warning Level Voltage Imbalance Warning Level (Parameter 368) allows you to define the percentage at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 10…100%. Table 236 - Voltage Imbalance Warning Level (Parameter 368) Default Value 10 Minimum Value 10 Maximum Value 100 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Voltage Imbalance Warning function does not include a time delay feature. Once the Voltage Imbalance Inhibit Time has expired, the Voltage Imbalance Warning indication is instantaneous. Phase Rotation Protection Wiring of a three-phase voltage system can affect the rotational direction of an electric motor. The E300 Electronic Overload Relay can help protect against the improper phase rotation so that an electric motor rotates in the proper direction, ABC or ACB, to prevent equipment from being damaged. Phase Rotation Inhibit Time Phase Rotation Inhibit Time (Parameter 359) allows you to inhibit a phase rotation mismatch trip and warning from occurring. It is adjustable from 0…250 seconds. Table 237 - Phase Rotation Inhibit Time (Parameter 363) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Phase Rotation Trip The E300 Electronic Overload Relay trips with a Phase Rotation indication if: • No trip currently exists 196 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions • • • • • Chapter 6 Phase Rotation Trip is enabled Voltage is present Phase Rotation Inhibit Time has expired The measured Voltage Phase Rotation (Parameter 63) does not match the required Phase Rotation Type (Parameter 364). If the E300 Electronic Overload Relay trips on a phase rotation mismatch, the: • TRIP/WARN LED status indicator flashes a red 1-long / 4-short blink pattern • Bit 3 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Phase Rotation Trip Type Phase Rotation Trip Type (Parameter 364) allows you to define the required voltage phase rotation for the motor application. E300 Electronic Overload Relay trips on a phase rotation mismatch when this parameter does not match the measured voltage phase rotation. It is user-adjustable, ABC or ACB. Table 238 - Phase Rotation Trip Type (Parameter 364) Default Value Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 = ABC 197 Chapter 6 Protective Trip and Warning Functions 1 = ABC Range 2 = ACB Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units IMPORTANT The Phase Rotation Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for a phase rotation mismatch condition until the Phase Rotation Inhibit Time expires. Frequency Protection The E300 Electronic Overload Relay has the capability to help protect against poor voltage quality by offering frequency-based protection. This protection is used when electric power is provided by stand-alone electric generators. You can prevent a contactor from energizing if the voltage frequency is either too high or too low. The E300 Electronic Overload Relay can monitor for this condition with its Over and Under Frequency Trip and Warning function, and it can detect for an improper voltage frequency to minimize motor damage and loss of production. Under Frequency Inhibit Time Under Frequency Inhibit Time (Parameter 369) allows you to inhibit an under frequency trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 239 - Under Frequency Inhibit Time (Parameter 369) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over Frequency Inhibit Time Over Frequency Inhibit Time (Parameter 373) allows you to inhibit an over frequency trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. 198 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 240 - Over Frequency Inhibit Time (Parameter 373) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under Frequency Trip The E300 Electronic Overload Relay trips with an Under Frequency indication if: • No trip currently exists • Under Frequency Trip is enabled • Voltage is present • Under Frequency Inhibit Time has expired • The voltage frequency is less than the Under Frequency Trip Level for a time period greater than the Under Frequency Trip Delay. If the E300 Electronic Overload Relay trips on an under frequency, the: • TRIP/WARN LED status indicator flashes a red 1-long / 5-short blink pattern • Bit 4 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 199 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under Frequency Trip Delay Under Frequency Trip Delay (Parameter 370) allows you to define the time period an under frequency condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 241 - Under Frequency Trip Delay (Parameter 370) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under Frequency Trip Level Under Voltage Trip Level (Parameter 371) allows you to define the frequency at which the E300 Electronic Overload Relay trips on an under frequency. It is useradjustable from 46…65 Hz. 200 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 242 - Under Frequency Trip Level (Parameter 371) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 57 46 65 USINT 1 1 Hz The Under Frequency Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for an under frequency condition until the Under Frequency Inhibit Time expires. Under Frequency Warning The E300 Electronic Overload Relay indicates an Under Frequency warning if: • No warning currently exists • Under Frequency Warning is enabled • Voltage is present • Under Frequency Inhibit Time has expired • The voltage frequency is equal to or less than the Under Frequency Warning Level When the Under Frequency Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 1-long / 5-short blink pattern • Bit 4 in Voltage Warning Status (Parameter 11) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Under Frequency Warn Level • Under Frequency Warn Level (Parameter 372) allows you to define the frequency at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 46…65 Hz. Table 243 - Under Frequency Warn Level (Parameter 372) Default Value 58 Minimum Value 46 Maximum Value 65 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Hz Rockwell Automation Publication 193-UM015C-EN-P - December 2014 201 Chapter 6 Protective Trip and Warning Functions Over Frequency Trip The E300 Electronic Overload Relay trips with an Over Frequency indication if: • No trip currently exists • Over Frequency Trip is enabled • Voltage is present • Over Frequency Inhibit Time has expired • The voltage frequency is greater than the Over Frequency Trip Level for a time period greater than the Over Frequency Trip Delay. If the E300 Electronic Overload Relay trips on an over frequency, the: • TRIP/WARN LED status indicator flashes a red 1-long / 6-short blink pattern • Bit 5 in Voltage Trip Status (Parameter 5) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over Frequency Trip Delay Over Frequency Trip Delay (Parameter 374) allows you to define the time period an over frequency condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. 202 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 244 - Over Frequency Trip Delay (Parameter 374) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over Frequency Trip Level Over Voltage Trip Level (Parameter 375) allows you to define the frequency at which the E300 Electronic Overload Relay trips on an over frequency. It is useradjustable from 46…65 Hz. Table 245 - Over Frequency Trip Level (Parameter 375) Default Value 63 Minimum Value 46 Maximum Value 65 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Hz IMPORTANT The Over Frequency Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L. The E300 Electronic Overload Relay does not begin monitoring for an over frequency condition until the Over Frequency Inhibit Time expires. Over Frequency Warning The E300 Electronic Overload Relay indicates an Over Frequency warning if: • No warning currently exists • Over Frequency Warning is enabled • Voltage is present • Over Frequency Inhibit Time has expired • The voltage frequency is equal to or greater than the Over Frequency Warning Level When the Over Frequency Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 1-long / 6-short blink pattern • Bit 5 in Voltage Warning Status (Parameter 11) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Rockwell Automation Publication 193-UM015C-EN-P - December 2014 203 Chapter 6 Protective Trip and Warning Functions Over Frequency Warn Level Over Frequency Warn Level (Parameter 376) allows you to define the frequency at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 46…65 Hz. Table 246 - Over Frequency Warn Level (Parameter 376) Default Value 62 Minimum Value 46 Maximum Value 65 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Hz IMPORTANT Power-based Protection The Over Frequency Warning function does not include a time delay feature. Once the Over Frequency Inhibit Time has expired, the Over Frequency Warning indication is instantaneous. The E300 Electronic Overload Relay can digitally monitor the power that is supplied to an electric motor to help protect against poor power quality or alert you when power consumed by the motor differs from what is expected. This protection is useful for pump cavitation and pump material change detection. The following E300 Sensing Modules provide power monitoring capabilities. Table 247 - Power Capabilities Catalog Number Measurement Method L-L Voltage Trip/Warning Range 193-ESM-VIG-__-__ Internal 20-800V 592-ESM-VIG-__-__ Internal 20-800V 193-ESM-VIG-30A-CT External 20-6500V This power information is used for the following protective trip and warning functions: • Under Real Power (kW) Trip/Warning • Over Real Power (kW) Trip/Warning • Under Reactive Power (kVAR) Trip/Warning • Over Real Power (kVAR) Trip/Warning • Under Reactive Power (kVA) Trip/Warning • Over Real Power (kVA) Trip/Warning • Under Power Factor Trip/Warning • Over Power Factor Trip/Warning 204 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Power Trip Enable (Parameter 185) and Power Warning Enable (Parameter 191) are used to enable the respective power-based protective trip and warning functions. Table 248 - Power Trip Enable (Parameter 185) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Under kW Trip X X Over kW Trip Under kVAR Consumed Trip X Over kVAR Consumed Trip X Under kVAR Generated Trip X Over kVAR Generated Trip X Under kVA Trip X Over kVA Trip X Under PF Lagging Trip X Over PF Lagging Trip X Under PF Leading Trip X Over PF Leading Trip Reserved Reserved Reserved Reserved Table 249 - Power Warning Enable (Parameter 191) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Warning Over kW Warning Under kVAR Consumed Warning Over kVAR Consumed Warning Under kVAR Generated Warning Over kVAR Generated Warning Under kVA Warning Over kVA Warning Under PF Lagging Warning Over PF Lagging Warning Under PF Leading Warning Over PF Leading Warning Reserved Reserved Reserved Reserved Power Trip Status (Parameter 6) and Power Warning Status (Parameter 12) are used to view the status of the respective power-based protective trip and warning functions. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 205 Chapter 6 Protective Trip and Warning Functions Table 250 - Power Trip Status (Parameter 6) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Trip Over kW Trip Under kVAR Consumed Trip Over kVAR Consumed Trip Under kVAR Generated Trip Over kVAR Generated Trip Under kVA Trip Over kVA Trip Under PF Lagging Trip Over PF Lagging Trip Under PF Leading Trip Over PF Leading Trip Reserved Reserved Reserved Reserved Table 251 - Power Warning Status (Parameter 12) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Warning Over kW Warning Under kVAR Consumed Warning Over kVAR Consumed Warning Under kVAR Generated Warning Over kVAR Generated Warning Under kVA Warning Over kVA Warning Under PF Lagging Warning Over PF Lagging Warning Under PF Leading Warning Over PF Leading Warning Reserved Reserved Reserved Reserved Real Power (kW) Protection The E300 Electronic Overload Relay has the capability to help protect against real power (kW) for specific applications that require the monitoring of both voltage and current. You can help protect or issue a warning ifthe real power (kW) consumption of an electric motor is either too high or too low. 206 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Under kW Inhibit Time Under kW Inhibit Time (Parameter 378) allows you to inhibit an under real power (kW) trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 252 - Under kW Inhibit Time (Parameter 378) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over kW Inhibit Time Over kW Inhibit Time (Parameter 382) allows you to inhibit an over real power (kW) trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 253 - Over kW Inhibit Time (Parameter 382) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under kW Trip The E300 Electronic Overload Relay trips with an Under kW indication if: • No trip currently exists • Under kW Trip is enabled • Current is present • Voltage is present • Under kW Inhibit Time has expired • The total real power (kW) is less than the Under kW Trip Level for a time period greater than the Under kW Trip Delay. If the E300 Electronic Overload Relay trips on an under real power (kW), the: • TRIP/WARN LED status indicator flashes a red 2-long / 1-short blink pattern • Bit 0 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 207 Chapter 6 Protective Trip and Warning Functions • • • • Any relay outputs configured as a Trip Relay open Any relay outputs configured as a Control Relay open Any relay outputs configured as a Trip Alarm close Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under kW Trip Delay Under kW Trip Delay (Parameter 379) allows you to define the time period an under real power (kW) condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 254 - Under kW Trip Delay (Parameter 379) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under kW Trip Level Under kW Trip Level (Parameter 380) allows you to define the real power (kW) at which the E300 Electronic Overload Relay trips on an under real power (kW). It is user-adjustable from 0…2,000,000 kW. 208 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 255 - UnderkW Trip Level (Parameter 380) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 0.000 0.000 2,000,000.000 DINT 4 1000 kW The Under kW Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under real power (kW) condition until the Under kW Inhibit Time expires. Under kW Warning The E300 Electronic Overload Relay indicates an Under kW warning if: • No warning currently exists • Under kW Warning is enabled • Current is present • Voltage is present • Under kW Inhibit Time has expired • The total real power (kW) is equal to or less than the Under kW Warning Level When the Under kW Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 1-short blink pattern • Bit 0 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Under kW Warn Level Under kW Warn Level (Parameter 381) allows you to define the real power (kW) at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 209 Chapter 6 Protective Trip and Warning Functions Table 256 - Under kW Warn Level (Parameter 381) Default Value 0.000 Minimum Value 0.000 Maximum Value 2000000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kW IMPORTANT The Under kW Warning function does not include a time delay feature. Once the Under kW Inhibit Time has expired, the Under kW Warning indication is instantaneous. Over kW Trip The E300 Electronic Overload Relay trips with an Over kW indication if: • No trip currently exists • Over kW Trip is enabled • Current is present • Voltage is present • Over kW Inhibit Time has expired • The total real power (kW) is greater than the Over kW Trip Level for a time period greater than the Over kW Trip Delay. If the E300 Electronic Overload Relay trips on an over real power (kW), the: • TRIP/WARN LED status indicator flashes a red 2-long / 2-short blink pattern • Bit 1 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 210 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over kW Trip Delay Over kW Trip Delay (Parameter 383) allows you to define the time period an over real power (kW) condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 257 - Over kW Trip Delay Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over kW Trip Level Over kW Trip Level (Parameter 384) allows you to define the total real power (kW) at which the E300 Electronic Overload Relay trips on over real power (kW). It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 211 Chapter 6 Protective Trip and Warning Functions Table 258 - Over kW Trip Level (Parameter 384) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 0.000 0.000 2000000.000 DINT 4 1000 kW The Over kW Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over real power (kW) condition until the Over kW Inhibit Time expires. Over kW Warning The E300 Electronic Overload Relay indicates an Over kW warning if: • No warning currently exists • Over kW Warning is enabled • Current is present • Voltage is present • Over kW Inhibit Time has expired • The total real power (kW) is equal to or greater than the Over kW Warning Level When the Over kW Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 2-short blink pattern • Bit 1 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Over kW Warn Level Over kW Warn Level (Parameter 385) allows you to define the real power (kW) at which the E300 Electronic Overload Relay indicates a warning. It is useradjustable from 0…2,000,000 kW. Table 259 - Over kW Warn Level Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 212 0.000 0.000 2000000.000 DINT 4 1000 kW Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Over kW Warning function does not include a time delay feature. Once the Over kW Inhibit Time has expired, the Over kW Warning indication is instantaneous. Reactive Power (kVAR) Protection The E300 Electronic Overload Relay has the capability to help protect against reactive power (kVAR) for specific applications that require the monitoring of both voltage and current. You can help protect or issue a warning if the reactive power (kVAR) of an electric motor is either too high or too low. Under kVAR Consumed Inhibit Time Under kVAR Consumed Inhibit Time (Parameter 386) allows you to inhibit an under reactive power (kVAR) consumed trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 260 - Under kVAR Consumed Inhibit Time (Parameter 386) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over kVAR Consumed Inhibit Time Over kVAR Consumed Inhibit Time (Parameter 390) allows you to inhibit an over reactive power (kVAR) consumed trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 261 - Over kVAR Consumed Inhibit Time (Parameter 390) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 213 Chapter 6 Protective Trip and Warning Functions Under kVAR Generated Inhibit Time Under kVAR Generated Inhibit Time (Parameter 394) allows you to inhibit an under power factor leading trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 262 - Under kVAR Generated Inhibit Time (Parameter 394) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over kVAR Generated Inhibit Time Over kVAR Generated Inhibit Time (Parameter 398) allows you to inhibit an over reactive power (kVAR) generated trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 263 - Over kVAR Generated Inhibit Time (Parameter 398) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under kVAR Consumed Trip The E300 Electronic Overload Relay trips with an Under kVAR Consumed indication if: • No trip currently exists • Under kVAR Consumed Trip is enabled • Current is present • Voltage is present • Under kVAR Consumed Inhibit Time has expired • The total reactive power (kVAR) consumed is less than the Under kVAR Consumed Trip Level for a time period greater than the Under kVAR Consumed Trip Delay. If the E300 Electronic Overload Relay trips on an under reactive power (kVAR) consumed, the: 214 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • TRIP/WARN LED status indicator flashes a red 2-long / 3-short blink pattern • Bit 2 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under kVAR Consumed Trip Delay Under kVAR Consumed Trip Delay (Parameter 387) allows you to define the time period an under reactive power (kVAR) consumed condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 264 - Under kVAR Consumed Trip Delay (Parameter 387) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 215 Chapter 6 Protective Trip and Warning Functions Under kVAR Consumed Trip Level Under kVAR Consumed Trip Level (Parameter 388) allows you to define the reactive power (kVAR) consumed at which the E300 Electronic Overload Relay trips on an under reactive power (kVAR) consumed. It is user-adjustable from 0…2,000,000 kW. Table 265 - Under kVAR Consumed Trip Level (Parameter 388) Default Value 0.000 Minimum Value 0.000 Maximum Value 2000000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVAR IMPORTANT The Under kVAR Consumed Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under reactive power (kVAR) consumed condition until the Under kVAR Consumed Inhibit Time expires. Under kVAR Consumed Warning The E300 Electronic Overload Relay indicates an Under kVAR Consumed warning if: • No warning currently exists • Under kVAR Consumed Warning is enabled • Current is present • Voltage is present • Under kVAR Consumed Inhibit Time has expired • The total reactive power (kVAR) consumed is equal to or less than the Under kVAR Consumed Warning Level When the Under kVAR Consumed Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 3-short blink pattern • Bit 2 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Under kVAR Consumed Warn Level Under kVAR Consumed Warn Level (Parameter 389) allows you to define the reactive power (kVAR) consumed at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. 216 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 266 - Under kVAR Consumed Warn Level (Parameter 389) Default Value 0.000 Minimum Value 0.000 Maximum Value 2000000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVAR IMPORTANT The Under kVAR Consumed Warning function does not include a time delay feature. Once the Under kVAR consumed Inhibit Time has expired, the Under kVAR Consumed Warning indication is instantaneous. Over kVAR ConsumedTrip The E300 Electronic Overload Relay trips with an Over kVAR Consumed indication if: • No trip currently exists • Over kVAR Consumed Trip is enabled • Current is present • Voltage is present • Over kVAR Consumed Inhibit Time has expired • The total reactive power (kVAR) consumed is greater than the Over kVAR Consumed Trip Level for a time period greater than the Over kVAR Consumed Trip Delay. If the E300 Electronic Overload Relay trips on an over reactive power (kVAR) consumed, the: • TRIP/WARN LED status indicator flashes a red 2-long / 4-short blink pattern • Bit 3 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 217 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over kVAR Consumed Trip Delay Over kVAR Consumed Trip Delay (Parameter 399) allows you to define the time period an over reactive power (kVAR) consumed condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 267 - Over kVAR Consumed Trip Delay (Parameter 391) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over kVAR Consumed Trip Level Over kVAR Consumed Trip Level (Parameter 392) allows you to define the total reactive power (kVAR) consumed at which the E300 Electronic Overload Relay trips on over reactive power (kVAR) consumed. It is user-adjustable from 0…2,000,000 kW. 218 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 268 - Over kVAR Consumed Trip Level (Parameter 392) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 0.000 0.000 2000000.000 DINT 4 1000 kVAR The Over kVAR Consumed Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over reactive power (kVAR) consumed condition until the Over kVAR Consumed Inhibit Time expires. Over kVAR Consumed Warning The E300 Electronic Overload Relay indicates an Over kVAR warning if: • No warning currently exists • Over kVAR Consumed Warning is enabled • Current is present • Voltage is present • Over kVAR Consumed Inhibit Time has expired • The total reactive power (kVAR) consumed is equal to or greater than the Over kVAR Consumed Warning Level When the Over kVAR Consumed Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 4-short blink pattern • Bit 3 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Over kVAR Consumed Warn Level Over kVAR Consumed Warn Level (Parameter 393) allows you to define the reactive power (kVAR) consumed at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Table 269 - Over kVAR Consumed Warn Level (Parameter 393) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVAR Rockwell Automation Publication 193-UM015C-EN-P - December 2014 219 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Over kVAR Consumed Warning function does not include a time delay feature. Once the Over kVAR Consumed Inhibit Time has expired, the Over kVAR Consumed Warning indication is instantaneous. Under kVAR Generated Trip The E300 Electronic Overload Relay trips with an Under kVAR Generated indication if: • No trip currently exists • Under kVAR Generated Trip is enabled • Current is present • Voltage is present • Under kVAR Generated Inhibit Time has expired • The total reactive power (kVAR) generated is less than the Under • kVAR Generated Trip Level for a time period greater than the Under kVAR Generated Trip Delay. If the E300 Electronic Overload Relay trips on an under reactive power (kVAR) generated, the: • TRIP/WARN LED status indicator flashes a red 2-long / 5-short blink pattern • Bit 4 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 220 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under kVAR Generated Trip Delay Under kVAR Generated Trip Delay (Parameter 395) allows you to define the time period an under reactive power (kVAR) generated condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 270 - Under kVAR Generated Trip Delay (Parameter 395) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under kVAR Generated Trip Level Under kVAR Generated Trip Level (Parameter 396) allows you to define the reactive power (kVAR) generated at which the E300 Electronic Overload Relay trips on an under reactive power (kVAR) generated. It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 221 Chapter 6 Protective Trip and Warning Functions Table 271 - Under kVAR Generated Trip Level (Parameter 396) Default Value 0.000 Minimum Value 0.000 Maximum Value 2000000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVAR IMPORTANT The Under kVAR Generated Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under reactive power (kVAR) generated condition until the Under kVAR Generated Inhibit Time expires. Under kVAR Generated Warning The E300 Electronic Overload Relay indicates an Under kVAR Generated warning if: • No warning currently exists • Under kVAR Generated Warning is enabled • Current is present • Voltage is present • Under kVAR Generated Inhibit Time has expired • The total reactive power (kVAR) generated is equal to or less than the Under kVAR Generated Warning Level When the Under kVAR Generated Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 5-short blink pattern • Bit 4 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Under kVAR Generated Warn Level Under kVAR Generated Warn Level (Parameter 397) allows you to define the reactive power (kVAR) generated at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. 222 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 272 - Under kVAR Generated Warn Level (Parameter 397) Default Value 0.000 Minimum Value 0.000 Maximum Value 2000000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVAR IMPORTANT The Under kVAR Generated Warning function does not include a time delay feature. Once the Under kVAR generated Inhibit Time has expired, the Under kVAR Generated Warning indication is instantaneous. Over kVAR Generated Trip The E300 Electronic Overload Relay trips with an Over kVAR Generated indication if: • No trip currently exists • Over kVAR Generated Trip is enabled • Current is present • Voltage is present • Over kVAR Generated Inhibit Time has expired • The total reactive power (kVAR) generated is greater than the Over • kVAR Generated Trip Level for a time period greater than the Over kVAR Generated Trip Delay. If the E300 Electronic Overload Relay trips on an over reactive power (kVAR) generated, the: • TRIP/WARN LED status indicator flashes a red 2-long / 6-short blink pattern • Bit 5 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 223 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over kVAR Generated Trip Delay Over kVAR Generated Trip Delay (Parameter 399) allows you to define the time period an over reactive power (kVAR) generated condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 273 - Over kVAR Generated Trip Display (Parameter 399) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over kVAR Generated Trip Level Over kVAR Generated Trip Level (Parameter 400) allows you to define the total reactive power (kVAR) generated at which the E300 Electronic Overload Relay trips on over reactive power (kVAR) generated. It is user-adjustable from 0…2,000,000 kW. 224 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 274 - Over kVAR Generated Trip Level (Parameter 400) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 0.000 0.000 2000000.000 DINT 4 1000 kVAR The Over kVAR Generated Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over reactive power (kVAR) generated condition until the Over kVAR Generated Inhibit Time expires. Over kVAR Generated Warning The E300 Electronic Overload Relay indicates an Over kVAR warning if: • No warning currently exists • Over kVAR Generated Warning is enabled • Current is present • Voltage is present • Over kVAR Generated Inhibit Time has expired • The total reactive power (kVAR) generated is equal to or greater than the Over kVAR Generated Warning Level When the Over kVAR Generated Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 6-short blink pattern • Bit 5 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Over kVAR Generated Warn Level Over kVAR Generated Warn Level (Parameter 401) allows you to define the reactive power (kVAR) generated at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Table 275 - Over kVAR Generated Warn Level (Parameter 401) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVAR Rockwell Automation Publication 193-UM015C-EN-P - December 2014 225 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Over kVAR Generated Warning function does not include a time delay feature. Once the Over kVAR Generated Inhibit Time has expired, the Over kVAR Generated Warning indication is instantaneous. Apparent Power (kVA) Protection The E300 Electronic Overload Relay has the capability to help protect against apparent power (kVA) for specific applications that require the monitoring of both voltage and current. You can help protect or issue a warning if the apparent power (kVA) consumption of an electric motor is either too high or too low. Under kVA Inhibit Time Under kVA Inhibit Time (Parameter 402) allows you to inhibit an under apparent power (kVA) trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 276 - Under kVA Inhibit Time (Parameter 402) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over kVA Inhibit Time Over kVA Inhibit Time (Parameter 406) allows you to inhibit an over apparent power (kVA) trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 277 - Over kVA Inhibit Time (Parameter 406) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under kVA Trip The E300 Electronic Overload Relay trips with an Under kVA indication if: 226 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions • • • • • • Chapter 6 No trip currently exists Under kVA Trip is enabled Current is present Voltage is present Under kVA Inhibit Time has expired The total apparent power (kVA) is less than the Under kVA Trip Level for a time period greater than the Under kVA Trip Delay. If the E300 Electronic Overload Relay trips on an under apparent power (kVA), the: • TRIP/WARN LED status indicator flashes a red 2-long / 7-short blink pattern • Bit 6 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under kVA Trip Delay Under kVA Trip Delay (Parameter 403) allows you to define the time period an under apparent power (kVA) condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 227 Chapter 6 Protective Trip and Warning Functions Table 278 - Under kVA Trip Delay (Parameter 403) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under kVA Trip Level Under kVA Trip Level (Parameter 404) allows you to define the apparent power (kVA) at which the E300 Electronic Overload Relay trips on an under apparent power (kVA). It is user-adjustable from 0…2,000,000 kVA. Table 279 - Under kVA Trip Level (Parameter 404) Default Value 0.000 Minimum Value 0.000 Maximum Value 2,000,000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVA IMPORTANT The Under kVA Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under apparent power (kVA) condition until the Under kVA Inhibit Time expires. Under kVA Warning The E300 Electronic Overload Relay indicates an Under kVA warning if: • No warning currently exists • Under kVA Warning is enabled • Current is present • Voltage is present • Under kVA Inhibit Time has expired • The total apparent power (kVA) is equal to or less than the Under kVA Warning Level When the Under kVA Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 7-short blink pattern • Bit 6 in Power Warning Status (Parameter 12) sets to 1 228 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Under kVA Warn Level Under kVA Warn Level (Parameter 405) allows you to define the apparent power (kVA) at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kVA. Table 280 - Under kVA Warn Level (Parameter 405) Default Value 0.000 Minimum Value 0.000 Maximum Value 2,000,000.000 Parameter Type DINT Size (Bytes) 4 Scaling Factor 1000 Units kVA IMPORTANT The Under kVA Warning function does not include a time delay feature. Once the Under kVA Inhibit Time has expired, the Under kVA Warning indication is instantaneous. Over kVA Trip The E300 Electronic Overload Relay trips with an Over kVA indication if: • No trip currently exists • Over kVA Trip is enabled • Current is present • Voltage is present • Over kVA Inhibit Time has expired • The total apparent power (kVA) is greater than the Over kVA Trip Level for a time period greater than the Over kVA Trip Delay. If the E300 Electronic Overload Relay trips on an over apparent power (kVA), the: • TRIP/WARN LED status indicator flashes a red 2-long / 8-short blink pattern • Bit 7 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 229 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over kVA Trip Delay Over kVA Trip Delay (Parameter 407) allows you to define the time period an over apparent power (kVA) condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 281 - Over kVA Trip Delay (Parameter 407) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over kVA Trip Level Over kVA Trip Level (Parameter 408) allows you to define the total apparent power (kVA) at which the E300 Electronic Overload Relay trips on over apparent power (kVA). It is user-adjustable from 0…2,000,000 kVA. 230 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 282 - Over kVA Trip Level (Parameter 408) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 0.000 0.000 2,000,000.000 DINT 4 1000 kVA The Over kVA Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over apparent power (kVA) condition until the Over kVA Inhibit Time expires. Over kVA Warning The E300 Electronic Overload Relay indicates an Over kVA warning if: • No warning currently exists • Over kVA Warning is enabled • Current is present • Voltage is present • Over kVA Inhibit Time has expired • The total apparent power (kVA) is equal to or greater than the Over kVA Warning Level When the Over kVA Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 8-short blink pattern • Bit 7 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Over kVA Warn Level Over kVA Warn Level (Parameter 409) allows you to define the apparent power (kVA) at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kVA. Table 283 - Over kVA Warn Level (Parameter 409) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2,000,000.000 DINT 4 1000 kVA Rockwell Automation Publication 193-UM015C-EN-P - December 2014 231 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Over kVA Warning function does not include a time delay feature. Once the Over kVA Inhibit Time has expired, the Over kVA Warning indication is instantaneous. Power Factor Protection The E300 Electronic Overload Relay has the capability to help protect against power factor for specific applications that require the monitoring of both voltage and current. You can help protect or issue a warning if the power factor of an electric motor is either too high or too low. Under Power Factor Lagging Inhibit Time Under Power Factor Lagging Inhibit Time (Parameter 410) allows you to inhibit an under power factor lagging trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 284 - Under Power Factor Lagging Inhibit Time (Parameter 410) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over Power Factor Lagging Inhibit Time Over Power Factor Lagging Inhibit Time (Parameter 414) allows you to inhibit an over power factor lagging trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 285 - Over Power Factor Lagging Inhibit Time (Parameter 414) Default Value 232 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Under Power Factor Leading Inhibit Time Under Power Factor Leading Inhibit Time (Parameter 418) allows you to inhibit an under power factor leading trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 286 - Under Power Factor Leading Inhibit Time (Parameter 418) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Over Power Factor Leading Inhibit Time Over Power Factor Leading Inhibit Time (Parameter 422) allows you to inhibit an over power factor leading trip and warning from occurring during the motor starting sequence. It is adjustable from 0…250 seconds. Table 287 - Over Power Factor Leading Inhibit Time (Parameter 422) Default Value 10 Minimum Value 0 Maximum Value 250 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Seconds Under Power Factor Lagging Trip The E300 Electronic Overload Relay trips with an Under Power Factor Lagging indication if: • No trip currently exists • Under Power Factor Lagging Trip is enabled • Current is present • Voltage is present • Under Power Factor Lagging Inhibit Time has expired • The total power factor lagging is less than the Under Power Factor Lagging Trip Level for a time period greater than the Under Power Factor Lagging Trip Delay. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 233 Chapter 6 Protective Trip and Warning Functions If the E300 Electronic Overload Relay trips on an under power factor lagging, the: • TRIP/WARN LED status indicator flashes a red 2-long / 9-short blink pattern • Bit 8 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under Power Factor Lagging Trip Delay Under Power Factor Lagging Trip Delay (Parameter 411) allows you to define the time period an under power factor lagging condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 288 - Under Power Factor Lagging Trip Delay (Parameter 411) 234 Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Under Power Factor Lagging Trip Level Under Power Factor Lagging Trip Level (Parameter 412) allows you to define the power factor lagging at which the E300 Electronic Overload Relay trips on an under power factor lagging. It is user-adjustable from 0…2,000,000 kW. Table 289 - Under Power Factor Lagging Trip Level (Parameter 412) Default Value -90 Minimum Value -100 Maximum Value 0 Parameter Type SINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Under Power Factor Lagging Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under power factor lagging condition until the Under Power Factor Lagging Inhibit Time expires. Under Power Factor Lagging Warning The E300 Electronic Overload Relay indicates an Under Power Factor Lagging warning if: • No warning currently exists • Under Power Factor Lagging Warning is enabled • Current is present • Voltage is present • Under Power Factor Lagging Inhibit Time has expired • The total power factor lagging is equal to or less than the Under Power Factor Lagging Warning Level When the Under Power Factor Lagging Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 9-short blink pattern • Bit 8 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Under Power Factor Lagging Warn Level Under Power Factor Lagging Warn Level (Parameter 413) allows you to define the power factor lagging at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 235 Chapter 6 Protective Trip and Warning Functions Table 290 - Under Power Factor Lagging Warn Level (Parameter 413) Default Value -95 Minimum Value -100 Maximum Value 0 Parameter Type SINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Under Power Factor Lagging Warning function does not include a time delay feature. Once the Under Power Factor Lagging Inhibit Time has expired, the Under Power Factor Lagging Warning indication is instantaneous. Over Power Factor Lagging Trip The E300 Electronic Overload Relay trips with an Over Power Factor Lagging indication if: • No trip currently exists • Over Power Factor Lagging Trip is enabled • Current is present • Voltage is present • Over Power Factor Lagging Inhibit Time has expired • The total power factor lagging is greater than the Over Power Factor Lagging Trip Level for a time period greater than the Over Power Factor Lagging Trip Delay. If the E300 Electronic Overload Relay trips on an over power factor lagging, the: • TRIP/WARN LED status indicator flashes a red 2-long / 10-short blink pattern • Bit 9 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 236 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over Power Factor Lagging Trip Delay Over Power Factor Lagging Trip Delay (Parameter 415) allows you to define the time period an over power factor lagging condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 291 - Over Power Factor Lagging Trip Delay (Parameter 415) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over Power Factor Lagging Trip Level Over Power Factor Lagging Trip Level (Parameter 416) allows you to define the total power factor lagging at which the E300 Electronic Overload Relay trips on over power factor lagging. It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 237 Chapter 6 Protective Trip and Warning Functions Table 292 - Over Power Factor Lagging Trip Level (Parameter 416) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT -95 -100 0 SINT 1 1 % The Over Power Factor Lagging Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over power factor lagging condition until the Over Power Factor Lagging Inhibit Time expires. Over Power Factor Lagging Warning The E300 Electronic Overload Relay indicates an Over kVAR warning if: • No warning currently exists • Over Power Factor Lagging Warning is enabled • Current is present • Voltage is present • Over Power Factor Lagging Inhibit Time has expired • The total power factor lagging is equal to or greater than the Over Power Factor Lagging Warning Level When the Over Power Factor Lagging Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 10-short blink pattern • Bit 9 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Over Power Factor Lagging Warn Level Over Power Factor Lagging Warn Level (Parameter 417) allows you to define the power factor lagging at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Table 293 - Over Power Factor Lagging Warn Level (Parameter 417) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 238 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 -90 -100 0 SINT 1 1 % Protective Trip and Warning Functions IMPORTANT Chapter 6 The Over Power Factor Lagging Warning function does not include a time delay feature. Once the Over Power Factor Lagging Inhibit Time has expired, the Over Power Factor Lagging Warning indication is instantaneous. Under Power Factor Leading Trip The E300 Electronic Overload Relay trips with an Under Power Factor Leading indication if: • No trip currently exists • Under Power Factor Leading Trip is enabled • Current is present • Voltage is present • Under Power Factor Leading Inhibit Time has expired • The total power factor leading is less than the Under Power Factor Leading Trip Level for a time period greater than the Under Power Factor Leading Trip Delay. If the E300 Electronic Overload Relay trips on an under power factor leading, the: • TRIP/WARN LED status indicator flashes a red 2-long / 11-short blink pattern • Bit 10 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 239 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Under Power Factor Leading Trip Delay Under Power Factor Leading Trip Delay (Parameter 419) allows you to define the time period an under power factor leading condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 294 - Under Power Factor Leading Trip Delay (Parameter 419) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Under Power Factor Leading Trip Level Under Power Factor Leading Trip Level (Parameter 420) allows you to define the power factor leading at which the E300 Electronic Overload Relay trips on an under power factor leading. It is user-adjustable from 0…2,000,000 kW. 240 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 295 - Under Power Factor Leading Trip Level (Parameter 420) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 90 100 0 USINT 1 1 % The Under Power Factor Leading Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an under power factor leading condition until the Under Power Factor Leading Inhibit Time expires. Under Power Factor Leading Warning The E300 Electronic Overload Relay indicates an Under Power Factor Leading warning if: • No warning currently exists • Under Power Factor Leading Warning is enabled • Current is present • Voltage is present • Under Power Factor Leading Inhibit Time has expired • The total power factor leading is equal to or less than the Under Power Factor Leading Warning Level When the Under Power Factor Leading Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 11-short blink pattern • Bit 10 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Under Power Factor Leading Warn Level Under Power Factor Leading Warn Level (Parameter 421) allows you to define the power factor leading at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 241 Chapter 6 Protective Trip and Warning Functions Table 296 - Under Power Factor Leading Warn Level (Parameter 421) Default Value 95 Minimum Value 100 Maximum Value 0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units % IMPORTANT The Under Power Factor Leading Warning function does not include a time delay feature. Once the Under Power Factor Leading Inhibit Time has expired, the Under Power Factor Leading Warning indication is instantaneous. Over Power Factor Leading Trip The E300 Electronic Overload Relay trips with an Over Power Factor Leading indication if: • No trip currently exists • Over Power Factor Leading Trip is enabled • Current is present • Voltage is present • Over Power Factor Leading Inhibit Time has expired • The total power factor leading is greater than the Over Power Factor Leading Trip Level for a time period greater than the Over Power Factor Leading Trip Delay. If the E300 Electronic Overload Relay trips on an over power factor leading, the: • TRIP/WARN LED status indicator flashes a red 2-long / 12-short blink pattern • Bit 11 in Power Trip Status (Parameter 6) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 242 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Over Power Factor Leading Trip Delay Over Power Factor Leading Trip Delay (Parameter 423) allows you to define the time period an over power factor leading condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 297 - Over Power Factor Leading Trip Delay (Parameter 423) Default Value 1.0 Minimum Value 0.1 Maximum Value 25.0 Parameter Type USINT Size (Bytes) 1 Scaling Factor 10 Units Seconds Over Power Factor Leading Trip Level Over Power Factor Leading Trip Level (Parameter 424) allows you to define the total power factor leading at which the E300 Electronic Overload Relay trips on over power factor leading. It is user-adjustable from 0…2,000,000 kW. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 243 Chapter 6 Protective Trip and Warning Functions Table 298 - Over Power Factor Leading Trip Level (Parameter 424) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units IMPORTANT 95 100 0 USINT 1 1 % The Over Power Factor Leading Inhibit Time starts after a phase voltage transitions from 0V to 20V L-L and a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device. The E300 Electronic Overload Relay does not begin monitoring for an over power factor leading condition until the Over Power Factor Leading Inhibit Time expires. Over Power Factor Leading Warning The E300 Electronic Overload Relay indicates an Over kVAR warning if: • No warning currently exists • Over Power Factor Leading Warning is enabled • Current is present • Voltage is present • Over Power Factor Leading Inhibit Time has expired • The total power factor leading is equal to or greater than the Over Power Factor Leading Warning Level When the Over Power Factor Leading Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 2-long / 12-short blink pattern • Bit 11 in Power Warning Status (Parameter 12) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Over Power Factor Leading Warn Level Over Power Factor Leading Warn Level (Parameter 425) allows you to define the power factor leading at which the E300 Electronic Overload Relay indicates a warning. It is user-adjustable from 0…2,000,000 kW. Table 299 - Over Power Factor Leading Warn Level (Parameter 425) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 244 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 90 100 0 USINT 1 1 % Protective Trip and Warning Functions Chapter 6 I IMPORTANT The Over Power Factor Leading Warning function does not include a time delay feature. Once the Over Power Factor Leading Inhibit Time has expired, the Over Power Factor Leading Warning indication is instantaneous. The E300 Electronic Overload Relay provides a number of control-based protection functions including: • Test Trip • Operator Station Trip • Remote Trip • Start Inhibit • Preventive Maintenance • Configuration Trip • Option Match Trip/Warning • Expansion Bus Trip/Warning • Non Volatile Storage Trip • Test Mode Trip Control-Based Protection Control Trip Enable (Parameter 186) and Control Warning Enable (Parameter 192) are used to enable the respective control-based protective trip and warning functions. Table 300 - Control Trip Enable (Parameter 186) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Test Trip Enable X X X X X X X X X X PTC Trip Enable DeviceLogix Trip Enable Operator Station Trip Enable Remote Trip Enable Blocked Start Trip Enable Hardware Fault Trip Enable Configuration Trip Enable Option Match Trip Enable Feedback Timeout Trip Enable Expansion Bus Trip Enable Reserved Reserved X X Nonvolatile Memory Trip Enable Test Mode Trip Enable Reserved Rockwell Automation Publication 193-UM015C-EN-P - December 2014 245 Chapter 6 Protective Trip and Warning Functions Control Trip Status (Parameter 7) and Control Warning Status (Parameter 13) are used to monitor the respective current-based protective trip and warning functions. Table 301 - Control Warning Enable (Parameter 192) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function Reserved Reserved X DeviceLogix Warning Enable X Operator Station Warning Enable Reserved Reserved Reserved Reserved X Option Match Warning Enable X Feedback Timeout Warning Enable X Expansion Bus Warning Enable X Number Of Starts Warning Enable X Operating Hours Warning Enable Reserved Reserved Reserved Table 302 - Control Trip Status (Parameter 7) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function X Test Trip X X X X X X X X X X PTC Trip DeviceLogix Trip Operator Station Trip Remote Trip Blocked Start Trip Hardware Fault Trip Configuration Trip Option Match Trip Feedback Timeout Trip Expansion Bus Trip Reserved Reserved X X Nonvolatile Memory Trip Test Mode Trip Reserved 246 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 303 - Control Warning Status (Parameter 13) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function Reserved X X X PTC Warning DeviceLogix Warning Operator Station Warning Reserved Reserved Reserved Reserved X X X X X Option Match Warning Feedback Timeout Warning Expansion Bus Warning Number Of Starts Warning Operating Hours Warning Reserved Reserved Reserved Test Trip The E300 Electronic Overload Relay provides the capability to put the overload relay into a Test Trip state. You can implement this feature when commissioning a motor control circuit to verify the response of the E300 Electronic Overload Relay, its associated Expansion I/O modules, and the networked automation system. The E300 Electronic Overload Relay trips with a test trip indication if: • No trip currently exists • Test Trip protection is enabled • You press the blue reset button on the Communication Module for more than 3 seconds. If the E300 Electronic Overload Relay trips on a test trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 1-short blink pattern • Bit 0 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 247 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Operator Station Trip The E300 Electronic Overload Relay provides the capability to plug and play its optional operator stations. The operator station protection feature trips the E300 Electronic Overload Relay when you press the red O (stop) button. This feature is a failsafe mechanism to allow you to de-energize a contactor coil anytime the red O (stop) button is pressed. Operator Station Trip should be disabled when an operator station is being used to send start and stop signals to an automation control system. The E300 Electronic Overload Relay trips with an operator station trip indication if: • No trip currently exists • Operator Station Trip is enabled • You press the red O button on an operator station If the E300 Electronic Overload Relay trips on an operator station trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 4-short blink pattern • Bit 3 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open 248 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Remote Trip The E300 Electronic Overload Relay provides the capability to remotely cause the E300 Electronic Overload Relay to trip via a network command or assigned digital input on the Control Module (see Chapter 4 for digital input assignments). This feature allows the capability of tripping the E300 Electronic Overload Relay from a remote source such as a vibration switch or external monitoring relay. The E300 Electronic Overload Relay trips with a remote trip indication if: • No trip currently exists • Remote Trip is enabled • A Control Module’s digital input with a remote trip assignment is activated or the Communication Module receives a remote trip command from the communications network If the E300 Electronic Overload Relay trips on a remote trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 5-short blink pattern • Bit 4 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open Rockwell Automation Publication 193-UM015C-EN-P - December 2014 249 Chapter 6 Protective Trip and Warning Functions • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Start Inhibit Protection This protective function allows you to limit the number of starts in a given time period and limit the operating hours for an electric motor. A start is defined as the E300 Electronic Overload Relay sensing a transition in current from 0 A to 30% of the minimum FLA rating of the device. The Blocked Start protective function is set by Starts Per Hour (Parameter 205) and/or Starts Interval (Parameter 206). Blocked Start Trip The E300 Electronic Overload Relay trips with a blocked start trip indication if: • No trip currently exists • Blocked Start Trip is enabled • The number of starts within the past hour equals the value set in Starts Per Hour (Parameter 205) • The time between starts is less than the value set in Starts Interval (Parameter 206) 250 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 If the E300 Electronic Overload Relay trips on a blocked start trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 6-short blink pattern • Bit 5 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Starts Per Hour Starts Per Hour (Parameter 205) is the number of starts within the last hour (60 minutes). This value is adjustable from 0…120 starts. Table 304 - Starts Per Hour (Parameter 205) Default Value 2 Minimum Value 0 Maximum Value 120 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 251 Chapter 6 Protective Trip and Warning Functions Starts Interval Starts Interval (Parameter 206) is the time that you must wait between starts. This value is adjustable from 0…3600 seconds. Table 305 - Starts Interval (Parameter 206) Default Value 600 Minimum Value 0 Maximum Value 3600 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Seconds Starts Available Starts Available (Parameter 30) reports the number of starts currently available based on the blocked start settings and the actual motor starting events. Table 306 - Starts Available (Parameter 30) Default Value 0 Minimum Value 0 Maximum Value 120 Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Time to Start Time to Start (Parameter 31) reports the amount of the time remaining until a new start can be issued. If the Time to Start time has elapsed, this parameter reports zero until the next Blocked Start trip occurs. Table 307 - Time to Start (Parameter 31) Default Value 252 0 Minimum Value 0 Maximum Value 3600 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Seconds Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Preventive Maintenance The E300 Electronic Overload Relay offers preventive maintenance warnings based on the number of start cycles and the number of operating hours. These warnings can be used to alert you that the number of starts or number of operating hours has been reached, and it is time to perform preventive maintenance. Number of Starts Warning The E300 Electronic Overload Relay warns with a number of starts warning indication if: • No warning currently exists • Number of Starts Warning is enabled • The value in Starts Counter (Parameter 29) is greater than the value set in Total Starts (Parameter 207) If the E300 Electronic Overload Relay warns on a number of starts warning, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 12-short blink pattern • Bit 11 in Control Warning Status (Parameter 13) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Total Starts Total Starts (Parameter 207) allows you to set the number starts until the starts counter warning occurs. Table 308 - Total Starts (Parameter 207) Default Value 0 Minimum Value 0 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Starts Counter Starts Counter (Parameter 29) represents the number of times a motor has been started. This value can be reset to zero using the Clear Command (Parameter 165) function Clear Operating Statistics. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 253 Chapter 6 Protective Trip and Warning Functions Table 309 - Starts Counter (Parameter 29) Default Value 0 Minimum Value 0 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Operating Hours Warning The E300 Electronic Overload Relay warns with an operating hours warning indication if: • No warning currently exists • Operating Hours Warning is enabled • The value in Operating Time (Parameter 28) is greater than the value set in Total Operating Hours (Parameter 208) If the E300 Electronic Overload Relay warns on an operating hours warning, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 13-short blink pattern • Bit 12 in Control Warning Status (Parameter 13) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Total Operating Hours Total Operating Hours (Parameter 208) allows you to set the number operating hours that a motor can operate until the operating hours warning occurs. Table 310 - Total Operating Hours (Parameter 208) Default Value 0 Minimum Value 0 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Hours Operating Time Operating Time (Parameter 28) represents the number hours that a motor has been running. This value can be reset to zero using the Clear Command (Parameter 165) function Clear Operating Statistics. 254 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 311 - Operating Time (Parameter 28) Default Value 0 Minimum Value 0 Maximum Value 65535 Parameter Type UINT Size (Bytes) 2 Scaling Factor 1 Units Hours Hardware Fault The E300 Electronic Overload Relay continuously monitors the status of the Control, Sensing, and Communication Modules. The E300 Electronic Overload Relay issues a hardware fault trip if there is an issue with the Control, Sensing, and Communications Modules or if one of the modules is missing or incompatible. The Hardware Fault Trip is always enabled. The E300 Electronic Overload Relay trips with a hardware fault trip indication if: • No trip currently exists • Hardware Fault Trip is enabled • An issue exists between the Control Module, Sensing Module, and/or Communication Module If the E300 Electronic Overload Relay trips on a hardware fault trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 7-short blink pattern • Bit 6 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 255 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Configuration Trip See Invalid Configuration Mode in Chapter 4 for more information on Configuration Trip. Option Match See Option Match in Chapter 4 for more information on Option Match Trip and Warning. Expansion Bus Fault See Expansion Bus Fault in Chapter 4 for more information on Expansion Bus Trip and Warning. Nonvolatile Storage Fault The E300 Electronic Overload Relay continuously monitors the status of its nonvolatile storage. The E300 Electronic Overload Relay issues a nonvolatile storage fault trip if there is an issue with its nonvolatile storage or if it becomes corrupt. The Nonvolatile Storage Fault Trip is always enabled. 256 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 The E300 Electronic Overload Relay trips with a hardware fault trip indication if: • No trip currently exists • Nonvolatile Storage Fault Trip is enabled • An issue exists in the E300 Electronic Overload Relay’s nonvolatile storage If the E300 Electronic Overload Relay trips on a nonvolatile storage fault trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 14-short blink pattern • Bit 13 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Test Mode Trip Some motor control center enclosures include a Test Position in which the motor power is disconnected from the enclosure, but the control power is still active. This allows motor control center commissioning staff to verify that the motor starter is mechanically working and communications are established with the automation control system. The E300 Electronic Overload Relay provides the capability to put the overload relay into a Test Mode Trip state if motor control Rockwell Automation Publication 193-UM015C-EN-P - December 2014 257 Chapter 6 Protective Trip and Warning Functions center enclosure is in a test position, and the E300 Electronic Overload Relay detects motor current and/or voltage is present. The E300 Electronic Overload Relay trips with a test mode trip indication if: • No trip currently exists. • Test Mode Trip protection is enabled. • The digital input that is assigned to read the Test Position feedback is active. See Input Assignments (Parameters 196…201) in Chapter 4. • Motor current and/or voltage is present. If the E300 Electronic Overload Relay trips on a test mode trip, the following occurs: • The TRIP/WARN LED flashes a red 3-long / 15-short blink pattern • Bit 14 in Control Trip Status (Parameter 7) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 258 IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) IMPORTANT Motor current is detected when a phase of load current transitions from 0 A to 30% of the minimum FLA setting of the device Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 The E300 Electronic Overload Relay’s Analog I/O Expansion Modules scan up to three analog signals per module. This information can be used to trigger an over analog level Trip or Warning. The analog-based protection features can be used with the following analog applications: • Monitoring motor winding and bearing temperatures that are measured by RTD sensors • Monitoring liquid, air, or steam flow • Monitoring temperature • Monitoring weight • Monitoring levels • Monitoring a potentiometer • Monitoring PTC or NTC thermistor sensors Analog-based Protection Analog Trip Enable (Parameter 187) and Analog Warning Enable (Parameter 193) are used to enable the respective analog-based protective trip and warning functions. Table 312 - Analog Trip Enable (Parameter 187) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 В В В В В В В В В В В В В В В X Analog Module 1 - Input Channel 00 Trip В В В В В В В В В В В В В В X В Analog Module 1 - Input Channel 01 Trip В В В В В В В В В В В В В X В В Analog Module 1 - Input Channel 02 Trip В В В В В В В В В В В В X В В В Analog Module 2 - Input Channel 00 Trip В В В В В В В В В В В X В В В В Analog Module 2 - Input Channel 01 Trip В В В В В В В В В В X В В В В В Analog Module 2 - Input Channel 02 Trip В В В В В В В В В X В В В В В В Analog Module 3 - Input Channel 00 Trip В В В В В В В В X В В В В В В В Analog Module 3 - Input Channel 01 Trip В В В В В В В X В В В В В В В В Analog Module 3 - Input Channel 02 Trip В В В В В В X В В В В В В В В В Analog Module 4 - Input Channel 00 Trip В В В В В X В В В В В В В В В В Analog Module 4 - Input Channel 01 Trip В В В В X В В В В В В В В В В В Analog Module 4 - Input Channel 02 Trip Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Function 259 Chapter 6 Protective Trip and Warning Functions Table 313 - Analog Warning Enable (Parameter 193) Bit 15 В В В В В В В В В В В В 14 В В В В В В В В В В В В 13 В В В В В В В В В В В В 12 В В В В В В В В В В В В 11 В В В В В В В В В В В X 10 В В В В В В В В В В X В 9 В В В В В В В В В X В В 8 В В В В В В В В X В В В 7 В В В В В В В X В В В В 6 В В В В В В X В В В В В 5 В В В В В X В В В В В В 4 В В В В X В В В В В В В 3 В В В X В В В В В В В В 2 В В X В В В В В В В В В 1 В X В В В В В В В В В В 0 X В В В В В В В В В В В Function Analog Module 1 - Input Channel 00 Warning Analog Module 1 - Input Channel 01 Warning Analog Module 1 - Input Channel 02 Warning Analog Module 2 - Input Channel 00 Warning Analog Module 2 - Input Channel 01 Warning Analog Module 2 - Input Channel 02 Warning Analog Module 3 - Input Channel 00 Warning Analog Module 3 - Input Channel 01 Warning Analog Module 3 - Input Channel 02 Warning Analog Module 4 - Input Channel 00 Warning Analog Module 4 - Input Channel 01 Warning Analog Module 4 - Input Channel 02 Warning Analog Trip Status (Parameter 8) and Analog Warning Status (Parameter 14) are used to monitor the respective analog-based protective trip and warning functions. Table 314 - Analog Trip Status (Parameter 8) Bit 260 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 В В В В В В В В В В В В В В В X Analog Module 1 - Input Channel 00 Trip В В В В В В В В В В В В В В X В Analog Module 1 - Input Channel 01 Trip В В В В В В В В В В В В В X В В Analog Module 1 - Input Channel 02 Trip В В В В В В В В В В В В X В В В Analog Module 2 - Input Channel 00 Trip В В В В В В В В В В В X В В В В Analog Module 2 - Input Channel 01 Trip В В В В В В В В В В X В В В В В Analog Module 2 - Input Channel 02 Trip В В В В В В В В В X В В В В В В Analog Module 3 - Input Channel 00 Trip В В В В В В В В X В В В В В В В Analog Module 3 - Input Channel 01 Trip В В В В В В В X В В В В В В В В Analog Module 3 - Input Channel 02 Trip В В В В В В X В В В В В В В В В Analog Module 4 - Input Channel 00 Trip В В В В В X В В В В В В В В В В Analog Module 4 - Input Channel 01 Trip В В В В X В В В В В В В В В В В Analog Module 4 - Input Channel 02 Trip Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Function Protective Trip and Warning Functions Chapter 6 Table 315 - Analog Warning Status (Parameter 14) Bit 15 В В В В В В В В В В В В 14 В В В В В В В В В В В В 13 В В В В В В В В В В В В 12 В В В В В В В В В В В В 11 В В В В В В В В В В В X 10 В В В В В В В В В В X В 9 В В В В В В В В В X В В 8 В В В В В В В В X В В В 7 В В В В В В В X В В В В 6 В В В В В В X В В В В В 5 В В В В В X В В В В В В 4 В В В В X В В В В В В В 3 В В В X В В В В В В В В 2 В В X В В В В В В В В В 1 В X В В В В В В В В В В 0 X В В В В В В В В В В В Function Analog Module 1 - Input Channel 00 Warning Analog Module 1 - Input Channel 01 Warning Analog Module 1 - Input Channel 02 Warning Analog Module 2 - Input Channel 00 Warning Analog Module 2 - Input Channel 01 Warning Analog Module 2 - Input Channel 02 Warning Analog Module 3 - Input Channel 00 Warning Analog Module 3 - Input Channel 01 Warning Analog Module 3 - Input Channel 02 Warning Analog Module 4 - Input Channel 00 Warning Analog Module 4 - Input Channel 01 Warning Analog Module 4 - Input Channel 02 Warning Analog Module 1 The E300 Analog I/O Expansion Module scans up to three analog signals. An over level trip or warning can be configured for each input channel. Analog Module 1 – Channel 00 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 1 – Channel 00 Over Level Trip indication if: • No trip currently exists • Analog Module 1 – Channel 00 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 1 – Channel 00 Trip Level for a time period greater than the Analog Module 1 – Channel 00 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 00 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 1-short blink pattern • Bit 0 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 261 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 1 – Channel 00 Over Level Trip Delay Analog Module 1 – Channel 00 Over Level Trip Delay (Parameter 443) allows you to define the time period an Analog Module 1 – Channel 00 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 316 - Analog Module 1 – Channel 00 Over Level Trip Delay (Parameter 443) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 1 – Channel 00 Trip Level Analog Module 1 – Channel 00 Trip Level (Parameter 444) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 00 Over Level trip. It is user-adjustable from -32768…+32767. 262 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 317 - Analog Module 1 – Channel 00 Trip Level (Parameter 444) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Channel 00 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 1 – Channel 00 Over Level warning if: • No warning currently exists • Analog Module 1 – Channel 00 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 1 – Channel 00 Warning Level When the Analog Module 1 – Channel 00 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 1-short blink pattern • Bit 0 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 1 – Channel 00 Warning Level Analog Module 1 – Channel 00 Warning Level (Parameter 445) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 00 Over Level warning. It is useradjustable from -32768…+32767. Table 318 - Analog Module 1 – Channel 00 Warning Level (Parameter 445) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Channel 01 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 1 – Channel 01 Over Level Trip indication if: • No trip currently exists • Analog Module 1 – Channel 01 Over Level Trip is enabled Rockwell Automation Publication 193-UM015C-EN-P - December 2014 263 Chapter 6 Protective Trip and Warning Functions • The measured analog input signal is greater than the Analog Module 1 – Channel 01 Trip Level for a time period greater than the Analog Module 1 – Channel 01 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 01 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 2-short blink pattern • Bit 1 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 1 – Channel 01 Over Level Trip Delay Analog Module 1 – Channel 01 Over Level Trip Delay (Parameter 452) allows you to define the time period an Analog Module 1 – Channel 01 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. 264 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 319 - Analog Module 1 – Channel 01 Over Level Trip Delay (Parameter 452) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 1 – Channel 01 Trip Level Analog Module 1 – Channel 01 Trip Level (Parameter 453) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 01 Over Level trip. It is user-adjustable from -32768…+32767. Table 320 - Analog Module 1 – Channel 01 Trip Level (Parameter 453) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Channel 01 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 1 – Channel 01 Over Level warning if: • No warning currently exists • Analog Module 1 – Channel 01 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 1 – Channel 01 Warning Level When the Analog Module 1 – Channel 01 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 2-short blink pattern • Bit 1 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Analog Module 1 – Channel 01 Warning Level Analog Module 1 – Channel 01 Warning Level (Parameter 454) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 01 Over Level warning. It is useradjustable from -32768…+32767. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 265 Chapter 6 Protective Trip and Warning Functions Table 321 - Analog Module 1 – Channel 01 Warning Level (Parameter 454) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Channel 02 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 1 – Channel 02 Over Level Trip indication if: • No trip currently exists • Analog Module 1 – Channel 02 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 1 – Channel 02 Trip Level for a time period greater than the Analog Module 1 – Channel 02 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 02 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 3-short blink pattern • Bit 2 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 266 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 1 – Channel 02 Over Level Trip Delay Analog Module 1 – Channel 02 Over Level Trip Delay (Parameter 461) allows you to define the time period an Analog Module 1 – Channel 02 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 322 - Analog Module 1 – Channel 02 Over Level Trip Delay (Parameter 461) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 1 – Channel 02 Trip Level Analog Module 1 – Channel 02 Trip Level (Parameter 462) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 02 Over Level trip. It is user-adjustable from -32768…+32767. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 267 Chapter 6 Protective Trip and Warning Functions Table 323 - Analog Module 1 – Channel 02 Trip Level (Parameter 462) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Channel 02 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 1 – Channel 02 Over Level warning if: • No warning currently exists • Analog Module 1 – Channel 02 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 1 – Channel 02 Warning Level When the Analog Module 1 – Channel 02 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 3-short blink pattern • Bit 2 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Analog Module 1 – Channel 02 Warning Level Analog Module 1 – Channel 02 Warning Level (Parameter 463) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 1 – Channel 02 Over Level warning. It is useradjustable from -32768…+32767. Table 324 - Analog Module 1 – Channel 02 Warning Level (Parameter 463) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 The E300 Analog I/O Expansion Module scans up to three analog signals. An over level trip or warning can be configured for each input channel. 268 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Analog Module 2 – Channel 00 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 2 – Channel 00 Over Level Trip indication if: • No trip currently exists • Analog Module 2 – Channel 00 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 2 – Channel 00 Trip Level for a time period greater than the Analog Module 2 – Channel 00 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 00 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 4-short blink pattern • Bit 3 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 2 – Channel 00 Over Level Trip Delay Analog Module 2 – Channel 00 Over Level Trip Delay (Parameter 474) allows you to define the time period an Analog Module 2 – Channel 00 Over Level Rockwell Automation Publication 193-UM015C-EN-P - December 2014 269 Chapter 6 Protective Trip and Warning Functions condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 325 - Analog Module 2 – Channel 00 Over Level Trip Delay (Parameter 474) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 2 – Channel 00 Trip Level Analog Module 2 – Channel 00 Trip Level (Parameter 475) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 00 Over Level trip. It is user-adjustable from -32768…+32767. Table 326 - Analog Module 2 – Channel 00 Trip Level (Parameter 475) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Channel 00 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 2 – Channel 00 Over Level warning if: • No warning currently exists • Analog Module 2 – Channel 00 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 2 – Channel 00 Warning Level When the Analog Module 2 – Channel 00 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 4-short blink pattern • Bit 3 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Analog Module 2 – Channel 00 Warning Level Analog Module 2 – Channel 00 Warning Level (Parameter 476) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload 270 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Relay trips on an Analog Module 2 – Channel 00 Over Level warning. It is useradjustable from -32768…+32767. Table 327 - Analog Module 2 – Channel 00 Warning Level (Parameter 476) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Channel 01 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 2 – Channel 01 Over Level Trip indication if: • No trip currently exists • Analog Module 2 – Channel 01 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 2 – Channel 01 Trip Level for a time period greater than the Analog Module 2 – Channel 01 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 01 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 5-short blink pattern • Bit 1 in Analog Trip Status (Parameter 8) sets to 1 • Bit 4 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 271 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 2 – Channel 01 Over Level Trip Delay Analog Module 2 – Channel 01 Over Level Trip Delay (Parameter 483) allows you to define the time period an Analog Module 2 – Channel 01 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 328 - Analog Module 2 – Channel 01 Over Level Trip Delay (Parameter 483) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 2 – Channel 01 Trip Level Analog Module 2 – Channel 01 Trip Level (Parameter 484) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 01 Over Level trip. It is user-adjustable from -32768…+32767. 272 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 329 - Analog Module 2 – Channel 01 Trip Level (Parameter 484) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Channel 01 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 2 – Channel 01 Over Level warning if: • No warning currently exists • Analog Module 2 – Channel 01 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 2 – Channel 01 Warning Level When the Analog Module 2 – Channel 01 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 5-short blink pattern • Bit 4 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Analog Module 2 – Channel 01 Warning Level Analog Module 2 – Channel 01 Warning Level (Parameter 485) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 01 Over Level warning. It is useradjustable from -32768…+32767. Table 330 - Analog Module 2 – Channel 01 Warning Level (Parameter 485) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Channel 02 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 2 – Channel 02 Over Level Trip indication if: • No trip currently exists • Analog Module 2 – Channel 02 Over Level Trip is enabled Rockwell Automation Publication 193-UM015C-EN-P - December 2014 273 Chapter 6 Protective Trip and Warning Functions • The measured analog input signal is greater than the Analog Module 2 – Channel 02 Trip Level for a time period greater than the Analog Module 2 – Channel 02 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 02 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 6-short blink pattern • Bit 5 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 2 – Channel 02 Over Level Trip Delay Analog Module 2 – Channel 02 Over Level Trip Delay (Parameter 492) allows you to define the time period an Analog Module 2 – Channel 02 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. 274 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 331 - Analog Module 2 – Channel 02 Over Level Trip Delay (Parameter 492) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 2 – Channel 02 Trip Level Analog Module 2 – Channel 02 Trip Level (Parameter 493) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 02 Over Level trip. It is user-adjustable from -32768…+32767. Table 332 - Analog Module 2 – Channel 02 Trip Level (Parameter 493) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Channel 02 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 2 – Channel 02 Over Level warning if: • No warning currently exists • Analog Module 2 – Channel 02 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 2 – Channel 02 Warning Level When the Analog Module 2 – Channel 02 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 6-short blink pattern • Bit 5 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 2 – Channel 02 Warning Level Analog Module 2 – Channel 02 Warning Level (Parameter 494) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 2 – Channel 02 Over Level warning. It is useradjustable from -32768…+32767. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 275 Chapter 6 Protective Trip and Warning Functions Table 333 - Analog Module 2 – Channel 02 Warning Level (Parameter 494) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 The E300 Analog I/O Expansion Module scans up to three analog signals. An over level trip or warning can be configured for each input channel. Analog Module 3 – Channel 00 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 3 – Channel 00 Over Level Trip indication if: • No trip currently exists • Analog Module 3 – Channel 00 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 3 – Channel 00 Trip Level for a time period greater than the Analog Module 3 – Channel 00 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 00 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 7-short blink pattern • Bit 6 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 276 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 3 – Channel 00 Over Level Trip Delay Analog Module 3 – Channel 00 Over Level Trip Delay (Parameter 505) allows you to define the time period an Analog Module 3 – Channel 00 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 334 - Analog Module 3 – Channel 00 Over Level Trip Delay (Parameter 505) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 3 – Channel 00 Trip Level Analog Module 3 – Channel 00 Trip Level (Parameter 506) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 00 Over Level trip. It is user-adjustable from -32768…+32767. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 277 Chapter 6 Protective Trip and Warning Functions Table 335 - Analog Module 3 – Channel 00 Trip Level (Parameter 506) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Channel 00 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 3 – Channel 00 Over Level warning if: • No warning currently exists • Analog Module 3 – Channel 00 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 3 – Channel 00 Warning Level When the Analog Module 3 – Channel 00 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 7-short blink pattern • Bit 6 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 3 – Channel 00 Warning Level Analog Module 3 – Channel 00 Warning Level (Parameter 507) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 00 Over Level warning. It is useradjustable from -32768…+32767. Table 336 - Analog Module 3 – Channel 00 Warning Level (Parameter 507) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Channel 01 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 3 – Channel 01 Over Level Trip indication if: • No trip currently exists • Analog Module 3 – Channel 01 Over Level Trip is enabled 278 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • The measured analog input signal is greater than the Analog Module 3 – Channel 01 Trip Level for a time period greater than the Analog Module 3 – Channel 01 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 01 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 8-short blink pattern • Bit 7 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 3 – Channel 01 Over Level Trip Delay Analog Module 3 – Channel 01 Over Level Trip Delay (Parameter 514) allows you to define the time period an Analog Module 3 – Channel 01 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 279 Chapter 6 Protective Trip and Warning Functions Table 337 - Analog Module 3 – Channel 01 Over Level Trip Delay (Parameter 514) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 3 – Channel 01 Trip Level Analog Module 3 – Channel 01 Trip Level (Parameter 515) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 01 Over Level trip. It is user-adjustable from -32768…+32767. Table 338 - Analog Module 3 – Channel 01 Trip Level (Parameter 515) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Channel 01 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 3 – Channel 01 Over Level warning if: • No warning currently exists • Analog Module 3 – Channel 01 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 3 – Channel 01 Warning Level When the Analog Module 3 – Channel 01 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 8-short blink pattern • Bit 7 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 3 – Channel 01 Warning Level Analog Module 3 – Channel 01 Warning Level (Parameter 516) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 01 Over Level warning. It is useradjustable from -32768…+32767. 280 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 339 - Analog Module 3 – Channel 01 Warning Level (Parameter 516) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Channel 02 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 3 – Channel 02 Over Level Trip indication if: • No trip currently exists • Analog Module 3 – Channel 02 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 3 – Channel 02 Trip Level for a time period greater than the Analog Module 3 – Channel 02 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 02 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 9-short blink pattern • Bit 8 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 281 Chapter 6 Protective Trip and Warning Functions IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 3 – Channel 02 Over Level Trip Delay Analog Module 3 – Channel 02 Over Level Trip Delay (Parameter 523) allows you to define the time period an Analog Module 3 – Channel 02 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 340 - Analog Module 3 – Channel 02 Over Level Trip Delay (Parameter 523) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 3 – Channel 02 Trip Level Analog Module 3 – Channel 02 Trip Level (Parameter 524) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 02 Over Level trip. It is user-adjustable from -32768…+32767. 282 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Table 341 - Analog Module 3 – Channel 02 Trip Level (Parameter 524) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Channel 02 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 3 – Channel 02 Over Level warning if: • No warning currently exists • Analog Module 3 – Channel 02 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 3 – Channel 02 Warning Level When the Analog Module 3 – Channel 02 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 9-short blink pattern • Bit 8 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 3 – Channel 02 Warning Level Analog Module 3 – Channel 02 Warning Level (Parameter 525) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 3 – Channel 02 Over Level warning. It is useradjustable from -32768…+32767. Table 342 - Analog Module 3 – Channel 02 Warning Level (Parameter 525) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 The E300 Analog I/O Expansion Module scans up to three analog signals. An over level trip or warning can be configured for each input channel. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 283 Chapter 6 Protective Trip and Warning Functions Analog Module 4 – Channel 00 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 4 – Channel 00 Over Level Trip indication if: • No trip currently exists • Analog Module 4 – Channel 00 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 4 – Channel 00 Trip Level for a time period greater than the Analog Module 4 – Channel 00 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 00 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 10-short blink pattern • Bit 9 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 4 – Channel 00 Over Level Trip Delay Analog Module 4 – Channel 00 Over Level Trip Delay (Parameter 536) allows you to define the time period an Analog Module 4 – Channel 00 Over Level 284 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 343 - Analog Module 4 – Channel 00 Over Level Trip Delay (Parameter 536) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 4 – Channel 00 Trip Level Analog Module 4 – Channel 00 Trip Level (Parameter 537) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 00 Over Level trip. It is user-adjustable from -32768…+32767. Table 344 - Analog Module 4 – Channel 00 Trip Level (Parameter 537) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Channel 00 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 4 – Channel 00 Over Level warning if: • No warning currently exists • Analog Module 4 – Channel 00 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 3 – Channel 00 Warning Level When the Analog Module 3 – Channel 00 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 10-short blink pattern • Bit 9 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm closes Analog Module 4 – Channel 00 Warning Level Analog Module 4 – Channel 00 Warning Level (Parameter 538) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Rockwell Automation Publication 193-UM015C-EN-P - December 2014 285 Chapter 6 Protective Trip and Warning Functions Relay trips on an Analog Module 4 – Channel 00 Over Level warning. It is useradjustable from -32768…+32767. Table 345 - Analog Module 4 – Channel 00 Warning Level (Parameter 538) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Channel 01 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 4 – Channel 01 Over Level Trip indication if: • No trip currently exists • Analog Module 4 – Channel 01 Over Level Trip is enabled • The measured analog input signal is greater than the Analog Module 4 – Channel 01 Trip Level for a time period greater than the Analog Module 4 – Channel 01 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 01 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 11-short blink pattern • Bit 10 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) 286 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions IMPORTANT Chapter 6 The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 4 – Channel 01 Over Level Trip Delay Analog Module 4 – Channel 01 Over Level Trip Delay (Parameter 545) allows you to define the time period an Analog Module 4 – Channel 01 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Table 346 - Analog Module 4 – Channel 01 Over Level Trip Delay (Parameter 545) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 4 – Channel 01 Trip Level Analog Module 4 – Channel 01 Trip Level (Parameter 546) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 01 Over Level trip. It is user-adjustable from -32768…+32767. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 287 Chapter 6 Protective Trip and Warning Functions Table 347 - Analog Module 4 – Channel 01 Trip Level (Parameter 546) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Channel 01 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 4 – Channel 01 Over Level warning if: • No warning currently exists • Analog Module 4 – Channel 01 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 4 – Channel 01 Warning Level When the Analog Module 4 – Channel 01 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 11-short blink pattern • Bit 10 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close Analog Module 4 – Channel 01 Warning Level Analog Module 4 – Channel 01 Warning Level (Parameter 547) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 01 Over Level warning. It is useradjustable from -32768…+32767. Table 348 - Analog Module 4 – Channel 01 Warning Level (Parameter 547) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Channel 02 Over Level Trip The E300 Electronic Overload Relay trips with an Analog Module 4 – Channel 02 Over Level Trip indication if: • No trip currently exists • Analog Module 4 – Channel 02 Over Level Trip is enabled 288 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 • The measured analog input signal is greater than the Analog Module 4 – Channel 02 Trip Level for a time period greater than the Analog Module 4 – Channel 02 Over Level Trip Delay. If the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 02 Over Level, the: • TRIP/WARN LED status indicator flashes a red 4-long / 12-short blink pattern • Bit 11 in Analog Trip Status (Parameter 8) sets to 1 • Bit 0 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Trip Relay open • Any relay outputs configured as a Control Relay open • Any relay outputs configured as a Trip Alarm close • Any relay outputs configured as a Normal Relay are placed in their Protection Fault state (if so programmed) IMPORTANT The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and Digital Module 4 Output Relays are defined by the respective parameters: • Output PT00 Protection Fault Action (Parameter 304) • Output PT00 Protection Fault Value (Parameter 305) • Output PT01 Protection Fault Action (Parameter 310) • Output PT01 Protection Fault Value (Parameter 311) • Output PT02 Protection Fault Action (Parameter 316) • Output PT02 Protection Fault Value (Parameter 317) • Output Digital Module 1 Protection Fault Action (Parameter 322) • Output Digital Module 1 Protection Fault Value (Parameter 323) • Output Digital Module 2 Protection Fault Action (Parameter 328) • Output Digital Module 2 Protection Fault Value (Parameter 329) • Output Digital Module 3 Protection Fault Action (Parameter 334) • Output Digital Module 3 Protection Fault Value (Parameter 335) • Output Digital Module 4 Protection Fault Action (Parameter 340) • Output Digital Module 4 Protection Fault Value (Parameter 342) Analog Module 4 – Channel 02 Over Level Trip Delay Analog Module 4 – Channel 02 Over Level Trip Delay (Parameter 554) allows you to define the time period an Analog Module 4 – Channel 02 Over Level condition must be present before a trip occurs. It is adjustable from 0.1…25.0 seconds. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 289 Chapter 6 Protective Trip and Warning Functions Table 349 - Analog Module 4 – Channel 02 Over Level Trip Delay (Parameter 554) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 1.0 0.1 25.0 USINT 1 10 Seconds Analog Module 4 – Channel 02 Trip Level Analog Module 4 – Channel 02 Trip Level (Parameter 555) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 02 Over Level trip. It is user-adjustable from -32768…+32767. Table 350 - Analog Module 4 – Channel 02 Trip Level (Parameter 555) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Channel 02 Over Level Warning The E300 Electronic Overload Relay indicates an Analog Module 4 – Channel 02 Over Level warning if: • No warning currently exists • Analog Module 4 – Channel 02 Over Level Warning is enabled • The maximum phase current is equal to or greater than the Analog Module 4 – Channel 02 Warning Level When the Analog Module 4 – Channel 02 Over Level Warning conditions are satisfied, the: • TRIP/WARN LED flashes a yellow 4-long / 12-short blink pattern • Bit 11 in Analog Warning Status (Parameter 14) sets to 1 • Bit 1 in Device Status 0 (Parameter 20) sets to 1 • Any relay outputs configured as a Warning Alarm close 290 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Protective Trip and Warning Functions Chapter 6 Analog Module 4 – Channel 02 Warning Level Analog Module 4 – Channel 02 Warning Level (Parameter 556) allows you to define the magnitude of the analog signal in which the E300 Electronic Overload Relay trips on an Analog Module 4 – Channel 02 Over Level warning. It is useradjustable from -32768…+32767. Table 351 - Analog Module 4 – Channel 02 Warning Level (Parameter 556) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Rockwell Automation Publication 193-UM015C-EN-P - December 2014 291 Chapter 6 292 Protective Trip and Warning Functions Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 7 Commands Introduction This chapter provides detailed information aboutthe resetting, clearing, and preconfiguration functions of the E300 Electronic Overload Relay. The E300 Electronic Overload Relay provides three types of commands: • Trip reset • Configuration preset • Clear command Trip Reset Trip Reset (Parameter 163) allows you to reset an E300 Electronic Overload Relay when it is in a tripped state. Trip Reset has the same functionality as pressing the blue reset button on E300 communication module and using the Trip Reset bit in the consumed output assemblies of a communications network. A trip reset can only be performed when all conditions for the trip event have been cleared. For an overload trip event, the % Thermal Capacity Utilized (Parameter 1) must be below the value that is specified in Overload Reset Level (Parameter 174). Table 352 - Trip Reset (Parameter 163) Default Value 0 = Ready Range 0 = Ready 1 = Trip Reset Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Configuration Preset The E300 Electronic Overload Relay has a number of preset configurations that allow you to quickly configure all of the configuration parameters that are needed for a specific operating mode in one command. This also allows you to restore the factory default values for all configuration parameters in the E300 Electronic Overload Relay. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 293 Chapter 7 Commands Table 353 - Config Preset (Parameter 164) Default Value 0 = Ready Range 0 = Ready 1 = Factory Defaults Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units The following pages list the available configuration presets and the values for the associated pre-configured configuration values. Factory Defaults When the Factory Defaults configuration preset command is selected, the E300 Electronic Overload Relay restores all configuration parameters back to their original factory default values. Figure 48 - Factory Default Values Number Parameter Name 139 TripHistoryMaskI Default Units Value 0xFFFF Number Parameter Name 304 OutPt00PrFltAct 140 TripHistoryMaskV 0x003F 305 OutPt00PrFltVal 141 TripHistoryMaskP 0x0FFF 306 OutPt00ComFltAct 142 TripHistoryMaskC 0x27FF 307 OutPt00ComFltVal 143 TripHistoryMaskA 0x0FFF 308 OutPt00ComIdlAct 145 WarnHistoryMaskI 0xFFFF 309 OutPt00ComIdlVal 146 WarnHistoryMaskV 0x003F 310 OutPt01PrFltAct 147 WarnHistoryMaskP 0x0FFF 311 OutPt01PrFltVal 148 WarnHistoryMaskC 0x1FFF 312 OutPt01ComFltAct 149 WarnHistoryMaskA 0x0FFF 171 FLASetting 0.50 172 173 174 Default Units Value Goto Value Open Number Parameter Name 428 Screen1Param1 Default Value 1 429 Screen1Param2 50 Goto Value Open 430 Screen2Param1 2 431 Screen2Param2 3 Goto Value Open 432 Screen3Param1 51 433 Screen3Param2 52 Goto Value Open 434 Screen4Param1 38 435 Screen4Param2 39 Goto Value 436 DisplayTimeout 300 Second s 313 OutPt01ComFltVal Open 437 InAnMod1Ch00Type Disable Amps 314 OutPt01ComIdlAct 438 InAMod1Ch0Format Eng Units TripClass 10 315 OutPt01ComIdlVal Goto Value Open 439 InAMod1C0TmpUnit Degrees C OLPTCResetMode 316 OutPt02PrFltAct InAMod1C0FiltFrq 17 Hz 317 OutPt02PrFltVal Goto Value Open 440 OLResetLevel Automati c 75 %TCU 441 InAMod1C0OpCktSt Upscale 175 OLWarningLevel 85 318 OutPt02ComFltAct 442 InAnMod1Ch0RTDEn 3-Wire 176 SingleOrThreePh Three Phase 319 OutPt02ComFltVal Goto Value Open 443 InAMod1C0TripDly 1.0 177 FLA2Setting 0.50 183 TripEnableI 0x0003 294 %TCU Units Second s Amps 320 OutPt02ComIdlAct 321 OutPt02ComIdlVal Goto Value Open 444 InAMod1C0TripLvl 0 445 InAMod1C0WarnLvl 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Commands Number Parameter Name 184 TripEnableV Default Units Value 0 Number Parameter Name 322 OutDig1PrFltAct 185 TripEnableP 0 323 OutDig1PrFltVal 186 TripEnableC 0x20C9 324 OutDig1ComFltAct 187 TripEnableA 0 325 OutDig1ComFltVal 189 WarningEnableI 0 326 OutDig1ComIdlAct 190 WarningEnableV 0 327 OutDig1ComIdlVal 191 WarningEnableP 0 328 OutDigp2PrFltAct Default Units Value Goto Value Open Number Parameter Name InAnMod1Ch01Type Default Value Disable Goto Value Open 447 InAMod1Ch1Format Eng Units 448 InAMod1C1TmpUnit Degrees C 449 InAMod1C1FiltFrq 17 Hz Goto Value Open 450 InAMod1C1OpCktSt Upscale 451 InAnMod1Ch1RTDEn 3-Wire Goto Value 452 InAMod1C1TripDly 1.0 446 Chapter 7 Units Second s 192 WarningEnableC 0 329 OutDig2PrFltVal Open 453 InAMod1C1TripLvl 0 193 WarningEnableA 0 330 OutDig2ComFltAct 454 InAMod1C1WarnLvl 0 195 SetOperatingMode 331 OutDig2ComFltVal 455 InAnMod1Ch02Type Disable 196 InPt00Assignment Net Overload Normal Goto Value Open 332 OutDig2ComIdlAct 456 InAMod1Ch2Format Eng Units 197 InPt01Assignment Normal 333 OutDig2ComIdlVal Goto Value Open 457 InAMod1C2TmpUnit Degrees C 198 InPt02Assignment Normal 334 OutDig3PrFltAct 458 InAMod1C2FiltFrq 17 Hz 199 InPt03Assignment Normal 335 OutDig3PrFltVal Goto Value Open 459 InAMod1C2OpCktSt Upscale 200 InPt04Assignment Normal 336 OutDig3ComFltAct 460 InAnMod1Ch2RTDEn 3-Wire 201 InPt05Assignment Normal 337 OutDig3ComFltVal 461 InAMod1C2TripDly 1.0 Goto Value Open Second s 202 OutPt0Assignment * Trip Relay 338 OuDig3ComIdlAct Goto Value Open 462 InAMod1C2TripLvl 0 203 OutPt1Assignment Normal 339 OutDig3ComIdlVal 463 InAMod1C2WarnLvl 0 204 OutPt2Assignment Normal 340 OutDig4PrFltAct Goto Value Open 464 OutAnMod1Type Disable 205 StartsPerHour 2 341 OutDig4PrFltVal 465 OutAnMod1Select Ave %FLA 206 StartsInterval 600 342 OutDig4ComFltAct Goto Value 466 OutAnMod1FltActn Zero 343 OutDig4ComFltVal Open 467 OutAnMod1IdlActn Zero 344 OutDig4ComIdlAct 468 InAnMod2Ch00Type Disable 469 InAMod2Ch0Format Eng Units Second s 207 PMTotalStarts 0 208 PMOperatingHours 0 209 ActFLA2wOutput Disable 345 OutDig4ComIdlVal Goto Value Open 211 SecurityPolicy 0x801F 346 CommOverride Disable 470 InAMod2C0TmpUnit Degrees C 212 Language English 347 NetworkOverride Disable 471 InAMod2C0FiltFrq 17 Hz 213 FeedbackTimeout 500 350 PtDevOutCOSMask 0x0000 472 InAMod2C0OpCktSt Upscale 214 TransitionDelay 10000 352 VoltageMode Delta 473 InAnMod2Ch0RTDEn 3-Wire 215 InterlockDelay 100 353 PTPrimary 480 474 InAMod2C0TripDly 1.0 Hrs Second s 216 EmergencyStartEn Disable 354 PTSecondary 480 221 ControlModuleTyp Ignore 355 UVInhibitTime 10 475 InAMod2C0TripLvl 0 476 InAMod2C0WarnLvl 0 Second s Rockwell Automation Publication 193-UM015C-EN-P - December 2014 295 Chapter 7 Commands Number Parameter Name 222 SensingModuleTyp Default Units Value Ignore 223 CommsModuleType Ignore Number Parameter Name Number Parameter Name UVTripLevel Default Units Value 1.0 Second s 100.0 Volt 356 UVTripDelay 357 224 OperStationType Ignore 358 UVWarningLevel 400.0 225 DigitalMod1Type Ignore 359 OVInhibitTime 10 Volt 477 InAnMod2Ch01Type Default Value Disable 478 InAMod2Ch1Format Eng Units 479 InAMod2C1TmpUnit Degrees C 480 InAMod2C1FiltFrq 17 Hz Units Second s 226 DigitalMod2Type Ignore 360 OVTripDelay 1.0 227 DigitalMod3Type Ignore 361 OVTripLevel 500.0 Second s Volt 228 DigitalMod4Type Ignore 362 OVWarningLevel 490.0 Volt 481 InAMod2C1OpCktSt Upscale 482 InAnMod2Ch1RTDEn 3-Wire 483 InAMod2C1TripDly 1.0 Second s 229 AnalogMod1Type Ignore 363 PhRotInhibitTime 10 484 InAMod2C1TripLvl 0 485 InAMod2C1WarnLvl 0 486 InAnMod2Ch02Type Disable Second s 230 AnalogMod2Type Ignore 364 PhaseRotTripType ABC 231 AnalogMod3Type Ignore 365 VIBInhibitTime 10 Second s 232 AnalogMod4Type Ignore 233 MismatchAction 0x0000 239 PLInhibitTime 0 366 VIBTripDelay 1.0 367 VIBTripLevel 15 Second s % 368 VIBWarningLevel 10 % 369 UFInhibitTime 10 487 InAMod2Ch2Format Eng Units 488 InAMod2C2TmpUnit Degrees C 489 InAMod2C2FiltFrq 17 Hz 490 InAMod2C2OpCktSt Upscale 491 InAnMod2Ch2RTDEn 3-Wire 492 InAMod2C2TripDly 1.0 Second s 240 PLTripDelay 1 Second s 241 242 GroundFaultType GFInhibitTime Internal Second s 370 10 371 UFTripDelay UFTripLevel 1.0 57 Second s Hz Second s 243 244 GFTripDelay GFTripLevel 0.5 2.50 Second s Amps Second s 372 UFWarningLevel 58 373 OFInhibitTime 10 Hz 493 InAMod2C2TripLvl 0 494 InAMod2C2WarnLvl 0 495 OutAnMod2Type Disable Second s 245 GFWarningDelay 0 374 OFTripDelay 1.0 246 GFWarningLevel 2.00 375 OFTripLevel 63 Second s Hz 247 GFFilter Disable 376 OFWarningLevel 62 Hz 248 GFMaxInhibit Disable 377 PowerScale kW 249 StallEnabledTime 10 378 UWInhibitTime 10 250 StallTripLevel 600 Second s Amps Second s %FLA 496 OutAnMod2Select Ave %FLA 497 OutAnMod2FltActn Zero 498 OutAnMod2dlActn Zero 499 InAnMod3Ch00Type Disable 500 InAMod3Ch0Format Eng Units Second s 379 UWTripDelay 1.0 Second s 296 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Commands Number Parameter Name 251 JamInhibitTime 252 JamTripDelay 253 JamTripLevel Default Units Value 10 Second s 5.0 Second s 250 %FLA Number Parameter Name 380 UWTripLevel Default Units Value 0.000 kW 381 UWWarningLevel 0.000 382 OWInhibitTime 10 kW Chapter 7 Number Parameter Name 501 InAMod3C0TmpUnit Default Units Value Degrees C 502 InAMod3C0FiltFrq 17 Hz 503 InAMod3C0OpCktSt Upscale 504 InAnMod3Ch0RTDEn 3-Wire 505 InAMod3C0TripDly 1.0 Second s 254 255 JamWarningLevel ULInhibitTime 150 %FLA 10 383 384 OWTripDelay OWTripLevel 1.0 0.000 Second s kW Second s 256 257 ULTripDelay ULTripLevel 5.0 50 Second s %FLA Second s 385 OWWarningLevel 0.000 386 UVARCInhibitTime 10 kW 506 InAMod3C0TripLvl 0 507 InAMod3C0WarnLvl 0 Second s 258 259 ULWarningLevel CIInhibitTime 70 %FLA 10 387 UVARCTripDelay 1.0 388 UVARCTripLevel 0.000 Second s kVAR 389 UVARCWarnLevel 0.000 kVAR 390 OVARCInhibitTime 10 508 InAnMod3Ch01Type Disable 509 InAMod3Ch1Format Eng Units 510 InAMod3C1TmpUnit Degrees C 511 InAMod3C1FiltFrq 17 Hz Second s 260 261 CITripDelay CITripLevel 5.0 35 Second s % Second s 262 CIWarningLevel 20 % 391 OVARCTripDelay 1.0 263 CTPrimary 5 392 OVARCTripLevel 0.000 Second s kVAR 264 CTSecondary 5 393 OVARCWarnLevel 0.000 kVAR 512 InAMod3C1OpCktSt Upscale 513 InAnMod3Ch1RTDEn 3-Wire 514 InAMod3C1TripDly 1.0 Second s 265 UCInhibitTime 10 394 UVARGInhibitTime 10 Second s 266 L1UCTripDelay 1.0 395 267 L1UCTripLevel 35 Second s % 268 L1UCWarningLevel 40 % 269 L2UCTripDelay 1.0 270 L2UCTripLevel 35 271 L2UCWarningLevel 40 272 L3UCTripDelay 1.0 Second s % % 515 InAMod3C1TripLvl 0 Second s UVARGTripDelay 516 InAMod3C1WarnLvl 0 0.000 Second s kVAR 517 InAnMod3Ch02Type Disable UVARGWarnLevel 0.000 kVAR 518 InAMod3Ch2Format Eng Units OVARGInhibitTime 10 519 InAMod3C2TmpUnit Degrees C 396 UVARGTripLevel 397 398 1.0 Second s 399 OVARGTripDelay 1.0 400 OVARGTripLevel 0.000 Second s kVAR 401 OVARGWarnLevel 0.000 kVAR 520 InAMod3C2FiltFrq 17 Hz 521 InAMod3C2OpCktSt Upscale 522 InAnMod3Ch2RTDEn 3-Wire Second s Rockwell Automation Publication 193-UM015C-EN-P - December 2014 297 Chapter 7 Commands Number Parameter Name 273 L3UCTripLevel Default Units Value 35 % 274 L3UCWarningLevel 40 275 OCInhibitTime 10 % Number Parameter Name 403 UVATripDelay 404 UVATripLevel Default Units Value 10 Second s 1.0 Second s 0.000 kVA 405 UVAWarningLevel 0.000 406 OVAInhibitTime 10 402 UVAInhibitTime Number Parameter Name 523 InAMod3C2TripDly Default Value 1.0 Units Second s 524 InAMod3C2TripLvl 0 525 InAMod3C2WarnLvl 0 526 OutAnMod3Type Disable 527 OutAnMod3Select Ave %FLA Second s 276 277 L1OCTripDelay L1OCTripLevel 1.0 100 Second s % kVA Second s 278 279 L1OCWarningLevel L2OCTripDelay 90 % 1.0 280 L2OCTripLevel 100 Second s % 281 L2OCWarningLevel 90 % 407 OVATripDelay 1.0 408 OVATripLevel 0.000 Second s kVA 409 OVAWarningLevel 0.000 kVA 410 UPFLagInhibTime 10 528 OutAnMod3FltActn Zero 529 OutAnMod3dlActn Zero 530 InAnMod4Ch00Type Disable 531 InAMod4Ch0Format Eng Units Second s 282 283 L3OCTripDelay L3OCTripLevel 1.0 411 UPFLagTripDelay 532 InAMod3C0TmpUnit Degrees C -90 Second s % 533 InAMod4C0FiltFrq 17 Hz UPFLagWarnLevel -95 % 534 InAMod4C0OpCktSt Upscale OPFLagInhibTime 10 535 InAnMod4Ch0RTDEn 3-Wire 536 InAMod4C0TripDly 1.0 100 Second s % 412 UPFLagTripLevel % 413 414 284 L3OCWarningLevel 90 285 LineLossInhTime 10 1.0 Second s 286 L1LossTripDelay 1.0 Second s 415 OPFLagTripDelay 1.0 Second s 287 L2LossTripDelay 1.0 416 OPFLagTripLevel -95 Second s % 417 OPFLagWarnLevel -90 % 418 UPFLeadInhibTime 10 Second s 537 InAMod4C0TripLvl 0 538 InAMod4C0WarnLvl 0 539 InAnMod4Ch01Type Disable Second s 288 L3LossTripDelay 1.0 Second s 291 Datalink0 0 Second s 292 Datalink1 0 419 UPFLeadTripDelay 1.0 293 Datalink2 0 420 UPFLeadTripLevel 90 Second s % 294 Datalink3 0 421 UPFLeadWarnLevel 95 % 295 Datalink4 0 422 OPFLeadInhibTime 10 540 InAMod4Ch1Format Eng Units 541 InAMod4C1TmpUnit Degrees C 542 InAMod4C1FiltFrq 17 Hz 543 InAMod4C1OpCktSt Upscale 544 InAnMod4Ch1RTDEn 3-Wire 545 InAMod4C1TripDly 1.0 Second s 296 297 Datalink5 Datalink6 0 0 423 424 OPFLeadTripDelay OPFLeadTripLevel 1.0 95 Second s % Second s 298 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Commands Number Parameter Name 298 Datalink7 Default Units Value 0 Number Parameter Name 425 OPFLeadWarnLevel Default Units Value 90 % 426 DemandPeriod 15 427 NumberOfPeriods 1 Min Number Parameter Name 546 InAMod4C1TripLvl Default Value 0 547 InAMod4C1WarnLvl 0 548 InAnMod4Ch02Type Disable 549 InAMod4Ch2Format Eng Units 550 InAMod4C2TmpUnit Degrees C 551 InAMod4C2FiltFrq 17 Hz 552 InAMod4C2OpCktSt Upscale 553 InAnMod4Ch2RTDEn 3-Wire 554 InAMod4C2TripDly 1.0 Chapter 7 Units Second s Clear Command 555 InAMod4C2TripLvl 0 556 InAMod4C2WarnLvl 0 557 OutAnMod4Type Disable 558 OutAnMod4Select Ave %FLA 559 OutAnMod4FltActn Zero 560 OutAnMod4dlActn Zero Clear Command (Parameter 165) allows you to clear historical logs, operating statistics, and energy data within the nonvolatile memory of the E300 Electronic Overload Relay. Table 354 - Clear Command (Parameter 165) Default Value 0 = Ready Range 0 = Ready 1 = Clear Operating Statistics 2 = Clear History Logs 3 = Clear %TCU 4 = Clear kWh 5 = Clear kVARh 6 = Clear kVAh 7 = Clear Max kW Demand 8 = Clear Max kVAR Demand 9 = Clear Max kVA Demand 10 = Clear All Parameter Type USINT Size (Bytes) 1 Scaling Factor 1 Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 299 Chapter 7 Commands Clear Operating Statistics When the Clear Operating Statistics command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • Operating Time (Parameter 28) • Starts Counter (Parameter 29) Clear History Logs When the Clear History Logs command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • Trip History 0 (Parameter 127) • Trip History 1 (Parameter 128) • Trip History 2 (Parameter 129) • Trip History 3 (Parameter 130) • Trip History 4 (Parameter 131) • Warning History 0 (Parameter 132) • Warning History 1 (Parameter 133) • Warning History 2 (Parameter 134) • Warning History 3 (Parameter 135) • Warning History 4 (Parameter 136) Clear %TCU When the Clear %TCU command is issued, the E300 Electronic Overload Relay sets % Thermal Capacity Utilized (Parameter 1) to a value of zero (0). Clear kWh When the Clear kWh command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • kWh x 109 (Parameter 80) • kWh x 106 (Parameter 81) • kWh x 103 (Parameter 82) • kWh x 100 (Parameter 83) • kWh x 10-3 (Parameter 84) 300 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Commands Chapter 7 Clear kVARh When the Clear kVARh command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • kVARh Consumed x 109 (Parameter 85) • kVARh Consumed x 106 (Parameter 86) • kVARh Consumed x 103 (Parameter 87) • kVARh Consumed x 100 (Parameter 88) • kVARh Consumed x 10-3 (Parameter 89) • kVARh Generated x 109 (Parameter 90) • kVARh Generated x 106 (Parameter 91) • kVARh Generated x 103 (Parameter 92) • kVARh Generated x 100 (Parameter 93) • kVARh Generated x 10-3 (Parameter 94) • kVARh Net x 109 (Parameter 95) • kVARh Net x 106 (Parameter 96) • kVARh Net x 103 (Parameter 97) • kVARh Net x 100 (Parameter 98) • kVARh Net x 10-3 (Parameter 99) Clear kVAh When the Clear kVAh command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • kVAh x 109 (Parameter 100) • kVAh x 106 (Parameter 101) • kVAh x 103 (Parameter 102) • kVAh x 100 (Parameter 103) • kVAh x 10-3 (Parameter 104) Clear Max kW Demand When the Clear %TCU command is issued, the E300 Electronic Overload Relay sets Max kW Demand (Parameter 106) to a value of zero (0). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 301 Chapter 7 Commands Clear Max kVAR Demand When the Clear %TCU command is issued, the E300 Electronic Overload Relay sets Max kVAR Demand (Parameter 108) to a value of zero (0). Clear Max kVA Demand When the Clear %TCU command is issued, the E300 Electronic Overload Relay sets Max kVA Demand (Parameter 110) to a value of zero (0). Clear All When the Clear All command is issued, the E300 Electronic Overload Relay sets the following parameters to a value of zero (0): • % Thermal Capacity Utilized (Parameter 1) • Operating Time (Parameter 28) • Starts Counter (Parameter 29) • kWh x 109 (Parameter 80) • kWh x 106 (Parameter 81) • kWh x 103 (Parameter 82) • kWh x 100 (Parameter 83) • kWh x 10-3 (Parameter 84) • kVARh Consumed x 109 (Parameter 85) • kVARh Consumed x 106 (Parameter 86) • kVARh Consumed x 103 (Parameter 87) • kVARh Consumed x 100 (Parameter 88) • kVARh Consumed x 10-3 (Parameter 89) • kVARh Generated x 109 (Parameter 90) • kVARh Generated x 106 (Parameter 91) • kVARh Generated x 103 (Parameter 92) • kVARh Generated x 100 (Parameter 93) • kVARh Generated x 10-3 (Parameter 94) • kVARh Net x 109 (Parameter 95) • kVARh Net x 106 (Parameter 96) • kVARh Net x 103 (Parameter 97) • kVARh Net x 100 (Parameter 98) • kVARh Net x 10-3 (Parameter 99) 302 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Commands Chapter 7 • kVAh x 109 (Parameter 100) • kVAh x 106 (Parameter 101) • kVAh x 103 (Parameter 102) • kVAh x 100 (Parameter 103) • • • • • • • • • • • • • • kVAh x 10-3 (Parameter 104) Max kW Demand (Parameter 106) Max kVAR Demand (Parameter 108) Max kVA Demand (Parameter 110) Trip History 0 (Parameter 127) Trip History 1 (Parameter 128) Trip History 2 (Parameter 129) Trip History 3 (Parameter 130) Trip History 4 (Parameter 131) Warning History 0 (Parameter 132) Warning History 1 (Parameter 133) Warning History 2 (Parameter 134) Warning History 3 (Parameter 135) Warning History 4 (Parameter 136) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 303 Chapter 7 Commands Notes: 304 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 8 Metering and Diagnostics Introduction This chapter provides detailed information aboutthe metering and diagnostic information that the E300 Electronic Overload Relay generates. The metering and diagnostic functions are organized into seven sections: • Device Monitor • Current Monitor • Voltage Monitor • Power Monitor • Energy Monitor • Trip/Warning History • Trip Snapshot Device Monitor The E300 Electronic Overload Relay's device monitor diagnostics provides information on the status of the device, which includes: • Thermal overload protection • Trip and warning protection functions • Digital inputs and relay outputs • Operator station • Hardware options • Time and date Percent Thermal Capacity Utilized Percent Thermal Capacity Utilized (Parameter 1) reports the calculated percent thermal capacity utilization of the motor being monitored. When the percent thermal capacity utilization equals 100%, the E300 Electronic Overload Relay issues an overload trip. Table 355 - Percent Thermal Capacity Utilization (Parameter 1) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 100 USINT 1 1 % Rockwell Automation Publication 193-UM015C-EN-P - December 2014 305 Chapter 8 Metering and Diagnostics Time to Trip When the measured motor current exceeds the trip rating of the E300 Electronic Overload Relay, Overload Time to Trip (Parameter 2) indicates the estimated time remaining before an overload trip occurs. When the measured current is below the trip rating, the Overload Time to Trip value is reported as 9,999 seconds. Table 356 - Overload Time to Trip (Parameter 2) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 9999 0 9999 UINT 2 1 Seconds Time To Reset After an overload trip, the E300 Electronic Overload Relay reports the time remaining until the device can be reset through Overload Time to Reset (Parameter 3). When the % Thermal Capacity Utilized value falls to or below the Overload Reset Level (Parameter 174), the Overload Time to Reset value indicates zero until the overload trip is reset. After an overload trip is reset, the Overload Time to Reset value is reported as 0 seconds. Table 357 - Overload Time to Reset (Parameter 3) Default Value Minimum Value Maximum Value Parameter Type 306 0 0 9999 UINT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Current Trip Status Current Trip Status (Parameter 4) reports the status of the current-based protective trip functions. Table 358 - Current Trip Status (Parameter 4) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function X Overload Trip Phase Loss Trip Ground Fault Current Trip Stall Trip Jam Trip Underload Trip Current Imbalance Trip L1 Under Current Trip L2 Under Current Trip L3 Under Current Trip L1 Over Current Trip L2 Over Current Trip L3 Over Current Trip L1 Line Loss Trip L2 Line Loss Trip L3 Line Loss Trip 307 Chapter 8 Metering and Diagnostics Voltage Trip Status Voltage Trip Status (Parameter 5) reports the status of the voltage-based protective trip functions. Table 359 - Voltage Trip Status (Parameter 5) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X 308 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function X Under Voltage Trip Over Voltage Trip Voltage Imbalance Trip Phase Rotation Mismatch Trip Under Frequency Trip Over Frequency Trip Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Metering and Diagnostics Chapter 8 Power Trip Status Power Trip Status (Parameter 6) reports the status of the voltage-based protective trip functions. Table 360 - Power Trip Status (Parameter 6) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Trip Over kW Trip Under kVAR Consumed Trip Over kVAR Consumed Trip Under kVAR Generated Trip Over kVAR Generated Trip Under kVA Trip Over kVA Trip Under PF Lagging Trip Over PF Lagging Trip Under PF Leading Trip Over PF Leading Trip Reserved Reserved Reserved Reserved Control Trip Status Control Trip Status (Parameter 7) reports the status of the control-based protective trip functions. Table 361 - Control Trip Status (Parameter 7) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function X Test Trip PTC Trip DeviceLogix Trip Operator Station Trip Remote Trip Blocked Start Trip Hardware Fault Trip Configuration Trip Option Match Trip Feedback Timeout Trip Expansion Bus Trip Reserved Reserved Nonvolatile Memory Trip Test Mode Trip Enable Reserved 309 Chapter 8 Metering and Diagnostics Current Warning Status Current Warning Status (Parameter 10) reports the status of the current-based protective warning functions. Table 362 - Current Warning Status (Parameter 10) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X 0 Function X Overload Warning Reserved Ground Fault Warning Reserved Jam Warning Underload Warning Current Imbalance Warning L1 Under Current Warning L2 Under Current Warning L3 Under Current Warning L1 Over Current Warning L2 Over Current Warning L3 Over Current Warning L1 Line Loss Warning L2 Line Loss Warning L3 Line Loss Warning Voltage Warning Status Voltage Warning Status (Parameter 11) reports the status of the control-based protective warning functions. Table 363 - Voltage Warning Status (Parameter 11) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X 310 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function X Under Voltage Warning Over Voltage Warning Voltage Imbalance Warning Phase Rotation Mismatch Warning Under Frequency Warning Over Frequency Warning Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Metering and Diagnostics Chapter 8 Power Warning Status Power Warning Status (Parameter 12) reports the status of the control-based protective warning functions. Table 364 - Power Warning Status (Parameter 12) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Warning Over kW Warning Under kVAR Consumed Warning Over kVAR Consumed Warning Under kVAR Generated Warning Over kVAR Generated Warning Under kVA Warning Over kVA Warning Under PF Lagging Warning Over PF Lagging Warning Under PF Leading Warning Over PF Leading Warning Reserved Reserved Reserved Reserved Control Warning Status Control Warning Status (Parameter 13) reports the status of the control-based protective warning functions. Table 365 - Control Warning Status (Parameter 13) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function Reserved PTC Warning DeviceLogix Warning Operator Station Warning Reserved Reserved Reserved Reserved Option Match Warning Feedback Timeout Warning Expansion Bus Warning Number Of Starts Warning Operating Hours Warning Reserved Reserved Reserved 311 Chapter 8 Metering and Diagnostics Input Status 0 Input Status 0 (Parameter 16) reports the state of the digital inputs on the E300 Electronic Overload Relay Control Module. Table 366 - Input Status 0 (Parameter 16) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X 0 X Input Pt00 Input Pt01 Input Pt02 Input Pt03 Input Pt04 Input Pt05 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Function Input Status 1 Input Status 1 (Parameter 17) reports the state of the digital inputs on the E300 Electronic Overload Relay Digital Expansion Modules. Table 367 - Input Status 1 (Parameter 17) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X X X 312 0 Function X Digital Module 1 Input Pt00 Digital Module 1 Input Pt01 Digital Module 1 Input Pt02 Digital Module 1 Input Pt03 Digital Module 2 Input Pt00 Digital Module 2 Input Pt01 Digital Module 2 Input Pt02 Digital Module 2 Input Pt03 Digital Module 3 Input Pt00 Digital Module 3 Input Pt01 Digital Module 3 Input Pt02 Digital Module 3 Input Pt03 Digital Module 4 Input Pt00 Digital Module 4 Input Pt01 Digital Module 4 Input Pt02 Digital Module 4 Input Pt03 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Output Status Output Status (Parameter 18) reports the state of the relay outputs on the E300 Electronic Overload Relay Control Module and Digital Expansion Modules. Table 368 - Output Status (Parameter 18) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X 0 Function X Output Pt00 Output Pt01 Output Pt02 Digital Module 1 Output Pt00 Digital Module 1 Output Pt01 Digital Module 2 Output Pt00 Digital Module 2 Output Pt01 Digital Module 3 Output Pt00 Digital Module 3 Output Pt01 Digital Module 4 Output Pt00 Digital Module 4 Output Pt01 Reserved Reserved Reserved Reserved Reserved Rockwell Automation Publication 193-UM015C-EN-P - December 2014 313 Chapter 8 Metering and Diagnostics Operator Station Status Operator Station Status (Parameter 19) reports the state of the E300 Electronic Overload Relay Operator Station input buttons and output LEDs. Table 369 - Operator Station Status (Parameter 19) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X 314 0 Function X Operation Station I Operation Station II Operation Station Local Remote Operation Station O Operation Station Reset Reserved Reserved Reserved Operation Station I LED Operation Station II LED Operation Station Local LED Operation Station Remote LED Operation Station O LED Reserved Reserved Reserved Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Device Status 0 Device Status 0 (Parameter 20) reports the general status of the E300 Electronic Overload Relay and the sensing capabilities that are present. Table 370 - Device Status 0 (Parameter 20) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X X 0 Function X Trip Present Warning Present Invalid Configuration Current Present Ground Fault Current Present Voltage Present Emergency Start Enabled DeviceLogix Enabled Feedback Timeout Enabled Operator Station Present Voltage Sensing Present Internal Ground Fault Sensing Present External Ground Fault Sensing Present PTC Sensing Present Ready Reserved Device Status 0 bit 14, "Ready", is cleared under the following circumstances: • Device Status 0 bit 0, "Trip Present", is set • The E300 Electronic Overload Relay has not completed its power-up initialization • The processing of data in a configuration assembly is in progress • A CopyCat function is in progress • A Factory Defaults command has been invoked and is in progress. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 315 Chapter 8 Metering and Diagnostics Device Status 1 Device Status 1 (Parameter 21) reports the specific features of the E300 Electronic Overload Relay Control and Sensing Modules, it reports which Expansion Digital Modules Analog Modules are present on the E300 Electronic Overload Relay Expansion Bus. Table 371 - Device Status 1 (Parameter 21) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X X 0 Function X 24V DC Control Module Present 120V AC Control Module Present 240V AC Control Module Present 0.5…30 A Sensing Module Present 6…60 A Sensing Module Present 10…100 A Sensing Module Present 20…2000 A Sensing Module Present Digital Module 1 Present Digital Module 2 Present Digital Module 3 Present Digital Module 4 Present Analog Module 1 Present Analog Module 2 Present Analog Module 3 Present Analog Module 4 Present Reserved Firmware Revision Number Firmware Revision Number (Parameter 22) reports the firmware revision number of the E300 Electronic Overload Relay system. Table 372 - Firmware Revision Number (Parameter 22) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 65.535 UINT 2 1000 Control Module ID Control Module ID (Parameter 23) identifies which specific Control Module is present in the E300 Electronic Overload Relay system. 316 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 373 - Control Module ID (Parameter 23) Default Value Range Parameter Type Size (Bytes) Scaling Factor Units 0 0 = Unknown 1 = 193-EIO-63-24D 2 = 193-EIO-43-120 3 = 193-EIO-43-240 4 = 193-EIOGP-42-24D 5 = 193-EIOGP-22-120 6 = 193-EIOGP-22-240 USINT 1 1 Sensing Module ID Sensing Module ID (Parameter 24) identifies which specific Sensing Module is present in the E300 Electronic Overload Relay system. Table 374 - Sensing Module ID (Parameter 24) Default Value Range Parameter Type Size (Bytes) Scaling Factor Units 0 0 = Unknown 1 = 193/592-EIO-VIG-30A-__ 2 = 193/592-EIO-VIG-60A-__ 3 = 193/592-EIO-VIG-100A-__ 4 = 193/592-EIO-VIG-200A-__ 5 = 193/592-EIO-IG-30A-__ 6 = 193/592-EIO-IG-60A-__ 7 = 193/592-EIO-IG-100A-__ 8 = 193/592-EIO-IG-200A-__ 9 = 193/592-EIO-I-30A-__ 10 = 193/592-EIO-I-60A-__ 11 = 193/592-EIO-I-100A-__ 12 = 193/592-EIO-I-200A-__ USINT 1 1 Operator Station ID Operator Station ID (Parameter 25) identifies which specific Operator Station is present on the Expansion Bus of the E300 Electronic Overload Relay system. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 317 Chapter 8 Metering and Diagnostics Table 375 - Operator Station ID (Parameter 25) Default Value 0 0 = Unknown 1 = None 2 = 193-EOS-SCS 3 = 193-EOS-SDS USINT 1 1 Range Parameter Type Size (Bytes) Scaling Factor Units Expansion Digital Module ID Expansion Digital Module ID (Parameter 26) identifies which specific Expansion Digital Modules are present on the Expansion Bus of the E300 Electronic Overload Relay system. Table 376 - Expansion Digital Module ID (Parameter 26) Bit 15 14 13 12 11 10 9 8 0 0 0 1 0 0 0 1 0 1 1 0 7 0 1 1 0 6 5 4 3 0 0 0 1 0 1 1 0 0 0 1 0 2 0 0 0 1 0 0 1 0 0 0 1 0 1 0 1 1 0 0 0 0 1 0 Function None 193-EXP-DIO-42-24D Digital Module 1 193-EXP-DIO-42-120 193-EXP-DIO-42-240 None 193-EXP-DIO-42-24D Digital Module 2 193-EXP-DIO-42-120 193-EXP-DIO-42-240 None 193-EXP-DIO-42-24D Digital Module 3 193-EXP-DIO-42-120 193-EXP-DIO-42-240 None 193-EXP-DIO-42-24D Digital Module 4 193-EXP-DIO-42-120 193-EXP-DIO-42-240 Operating Time Operating Time (Parameter 28) represents the number hours that a motor has been running. This value can be reset to zero using the Clear Command (Parameter 165) function Clear Operating Statistics. 318 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 377 - Operating Time (Parameter 28) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 65535 UINT 2 1 Hours Starts Counter Starts Counter (Parameter 29) represents the number of times a motor has been started. This value can be reset to zero using the Clear Command (Parameter 165) function Clear Operating Statistics. Table 378 - Starts Counter (Parameter 29) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 65535 UINT 2 1 Starts Available Starts Available (Parameter 30) reports the number of starts currently available based on the blocked start settings and the actual motor starting events. Table 379 - Starts Available (Parameter 30) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 120 USINT 1 1 Time to Start Time to Start (Parameter 31) reports the amount of time remaining until a new start can be issued. If the Time to Start time has elapsed, this parameter reports zero until the next Blocked Start trip occurs. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 319 Chapter 8 Metering and Diagnostics Table 380 - Time to Start (Parameter 31) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 3600 UINT 2 1 Seconds Year Year (Parameter 32) reports the year in the virtual real-time clock of the E300 Electronic Overload Relay. Table 381 - Year (Parameter 32) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 12 UINT 2 1 Month Month (Parameter 33) reports the month in the virtual real-time clock of the E300 Electronic Overload Relay. Table 382 - Month (Parameter 33) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 12 UINT 2 1 Day Day (Parameter 34) reports the day in the virtual real-time clock of the E300 Electronic Overload Relay. 320 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 383 - Day (Parameter 34) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 31 UINT 2 1 Hour Hour (Parameter 35) reports the hour in the virtual real-time clock of the E300 Electronic Overload Relay. Table 384 - Hour (Parameter 35) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 24 UINT 2 1 Minute Minute (Parameter 36) reports the minute in the virtual real-time clock of the E300 Electronic Overload Relay. Table 385 - Minute (Parameter 36) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 60 UINT 2 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 321 Chapter 8 Metering and Diagnostics Second Second (Parameter 37) reports the second in the virtual real-time clock of the E300 Electronic Overload Relay. Table 386 - Second (Parameter 37) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 60 UINT 2 1 Invalid Configuration Parameter Invalid Configuration Parameter (Parameter 38) reports the parameter number that is causing a configuration trip in the E300 Electronic Overload Relay. See Chapter 4 for more information about a configuration fault. Table 387 - Invalid Configuration Parameter (Parameter 38) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 0 9999 UINT 2 1 Invalid Configuration Cause Invalid Configuration Cause (Parameter 39) reports the reason for the configuration trip in the E300 Electronic Overload Relay. See Chapter 4 for more information about a configuration fault. Table 388 - Invalid Configuration Cause (Parameter 39) Default Value Range Parameter Type Size (Bytes) Scaling Factor Units 322 0 0 = No Error 1 = Value Over Maximum 2 = Value Under Minimum 3 = Illegal Value 4 = L3 Current Detected 5 = CopyCat Error USINT 1 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Mismatch Status Mismatch Status (Parameter 40) reports the module that is causing a mismatch trip or warning in the E300 Electronic Overload Relay. See Chapter 4 for more information on a mismatch fault. Table 389 - Mismatch Status (Parameter 40) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 Current Monitor 0 0 Match 1 Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Match Mismatch Function Control Module Sensing Module Communication Module Operator Station Digital Module 1 Digital Module 2 Digital Module 3 Digital Module 4 Analog Module 1 Analog Module 2 Analog Module 3 Analog Module 4 The E300 Electronic Overload Relay current monitor diagnostics provides information on the current consumed by the load that the E300 Electronic Overload Relay is monitoring, and it provides diagnostics for a three-phase current system including imbalance and ground fault current. L1 Current L1 Current (Parameter 43) reports the current in Amperes flowing through the L1 and T1 power terminals of the E300 Electronic Overload Relay Sensing Module. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 323 Chapter 8 Metering and Diagnostics Table 390 - L1 Current (Parameter 43) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.00 0.00 20000000.00 DINT 4 100 Amps L2 Current L2 Current (Parameter 44) reports the current in Amperes flowing through the L2 and T2 power terminals of the E300 Electronic Overload Relay Sensing Module. Table 391 - L2 Current (Parameter 44) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.00 0.00 20000000.00 DINT 4 100 Amps L3 Current L3 Current (Parameter 45) reports the current in Amperes flowing through the L3 and T3 power terminals of the E300 Electronic Overload Relay Sensing Module. Table 392 - L3 Current (Parameter 45) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.00 0.00 20000000.00 DINT 4 100 Amps Average Current Average Current (Parameter 46) reports the average current of the monitored current. When single or three phase (Parameter 176) is set to three phase, average current is calculated as follows:пЂ Average Current = (L1 Current + L2 Current + L3 Current) / 3 324 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 When single or three phase (Parameter 176) is set to single phase, average current is calculated as follows:пЂ Average Current = (L1 Current + L2 Current) / 2 Table 393 - Average Current (Parameter 46) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.00 0.00 20000000.00 DINT 4 100 Amps L1 Percent FLA L1 Percent FLA (Parameter 47) reports the L1 current in comparison to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2 (Parameter 177).пЂ L1 Percent FLA = L1 Current / Full Load Amps Table 394 - L1 Percent FLA (Parameter 47) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 1000.00 UINT 2 10 % L2 Percent FLA L2 Percent FLA (Parameter 48) reports the L2 current in comparison to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2 (Parameter 177).пЂ L2 Percent FLA = L2 Current / Full Load Amps Table 395 - L2 Percent FLA (Parameter 48) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 1000.00 UINT 2 10 % Rockwell Automation Publication 193-UM015C-EN-P - December 2014 325 Chapter 8 Metering and Diagnostics L3 Percent FLA L3 Percent FLA (Parameter 49) reports the L3 current in comparison to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2 (Parameter 177).пЂ L3 Percent FLA = L3 Current / Full Load Amps Table 396 - L3 Percent FLA (Parameter 49) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 1000.00 UINT 2 10 % Average Percent FLA Average Percent FLA (Parameter 50) reports the average current in comparison to the active Full Load Amps programmed in FLA (Parameter 171) and FLA2 (Parameter 177).пЂ Average Percent FLA = Average Current / Full Load Amps Table 397 - Average Percent FLA (Parameter 50) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 1000.00 UINT 2 10 % Ground Fault Current Ground Fault Current (Parameter 51) reports the ground fault current measured by the internal core balanced current transformer of the E300 Electronic Overload Relay Sensing Module or external core balanced current transformer. Table 398 - Ground Fault Current (Parameter 51) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 326 0.0 0.0 99.99 UINT 2 100 Amps Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Current Imbalance Current Imbalance (Parameter 52) reports the percentage of uneven current consumption in the monitored power system. Current Imbalance is defined by the following equation:пЂ Current Imbalance = 100% * (Id/Ia)пЂ whereпЂ Id = Maximum Line Current Deviation from the Average CurrentпЂ Ia = Average Current Table 399 - Current Imbalance (Parameter 52) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Voltage Monitor 0 0 200 UINT 2 1 % The E300 Electronic Overload Relay’s voltage monitor diagnostics provides information on the voltage being supplied to the load. The voltage diagnostics include three-phase voltage, phase imbalance, phase rotation, and frequency. L1-L2 Voltage L1-L2 Voltage (Parameter 53) reports the voltage in volts in reference to the T1 and T2 power terminals of the E300 Electronic Overload Relay Sensing Module. Table 400 - L1-L2 Voltage (Parameter 53) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 327 Chapter 8 Metering and Diagnostics L2-L3 Voltage L2-L3 Voltage (Parameter 54) reports the voltage in volts in reference to the T2 and T3 power terminals of the E300 Electronic Overload Relay Sensing Module. Table 401 - L2-L3 Voltage (Parameter 54) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Table 402 - L3-L1 Voltage L3-L1 Voltage (Parameter 55) reports the voltage in volts in reference to the T3 and T1 power terminals of the E300 Electronic Overload Relay Sensing Module. Table 403 - L3-L1 Voltage (Parameter 55) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Average L-L Voltage Average L-L Voltage (Parameter 56) reports the average voltage of the monitored L-L voltages. When Single or Three Phase (Parameter 176) is set to Three Phase, Average L-L Voltage is calculated as follows: Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage + L3-L1 Voltage) / 3 When Single or Three Phase (Parameter 176) is set to Single Phase, Average L-L Voltage is calculated as follows: Average L-L Voltage = (L1-L2 Voltage + L2-L3 Voltage) / 2 Table 404 - Average L-L Voltage (Parameter 56) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 328 0.0 0.0 6553.5 UINT 2 10 Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 L1-N Voltage L1-N Voltage (Parameter 57) reports the voltage in volts in reference to the T1 power terminal of the E300 Electronic Overload Relay Sensing Module. Table 405 - L1-N Voltage (Parameter 57) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts L2-N Voltage L2-N Voltage (Parameter 58) reports the voltage in volts in reference to the T2 power terminal of the E300 Electronic Overload Relay Sensing Module. Table 406 - L2-N Voltage (Parameter 58) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts L3-N Voltage L3-N Voltage (Parameter 59) reports the voltage in volts in reference to the T3 power terminal of the E300 Electronic Overload Relay Sensing Module. Table 407 - L3-N Voltage (Parameter 59) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Rockwell Automation Publication 193-UM015C-EN-P - December 2014 329 Chapter 8 Metering and Diagnostics Average L-N Voltage Average L-N Voltage (Parameter 60) reports the average voltage of the monitored L-N voltages. When Single or Three Phase (Parameter 176) is set to Three Phase, Average L-N Voltage is calculated as follows: Average L-N Voltage = (L1-N Voltage + L2-N Voltage + L3-N Voltage) / 3 When Single or Three Phase (Parameter 176) is set to Single Phase, Average L-N Voltage is calculated as follows: Average L-N Voltage = (L1-N Voltage + L2-N Voltage) / 2 Table 408 - Average L-N Voltage (Parameter 60) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Voltage Imbalance Voltage Imbalance (Parameter 61) reports the percentage of uneven voltage being supplied by the monitored power system. Voltage Imbalance is defined by the following equation: Voltage Imbalance = 100% * (Vd/Va) where Vd = Maximum L-L Voltage Deviation from the Average L-L Voltage Va = Average L-L Voltage Table 409 - Voltage Imbalance (Parameter 61) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 330 0 0 200 UINT 2 1 % Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Frequency Frequency (Parameter 62) reports the voltage frequency in Hertz of the monitored power system from the E300 Electronic Overload Relay Sensing Module. Table 410 - Frequency (Parameter 62) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 74.0 UINT 2 10 Hz Phase Rotation Phase Rotation (Parameter 63) reports the voltage phase rotation as ABC or ACB of the monitored power system from the E300 Electronic Overload Relay Sensing Module. Table 411 - Phase Rotation Trip Type (Parameter 63) Default Value Range Parameter Type Size (Bytes) Scaling Factor Units Power Monitor 0 = No Rotation 0 = No Rotation 1 = ABC 2 = ACB USINT 1 1 The E300 Electronic Overload Relay’s power monitor diagnostics provides information on the power being supplied to the load. The power diagnostics include real power (kW), reactive power (kVAR), apparent power (kVA), and power factor. Power Scale For large medium voltage-based power systems, it may be more convenient for you to view the real-time power information (Parameters 64-75) in terms of Megawatts instead of Kilowatts. Power Scale (Parameter 377) allows the E300 Electronic Overload Relay to display the values of Parameters 64…75as Kilowatts or Megawatts. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 331 Chapter 8 Metering and Diagnostics Table 412 - Power Scale (Parameter 377) Default Value Range Parameter Type Size (Bytes) Scaling Factor Units 0 = Kilowatts 0 = Kilowatts 1 = Megawatts USINT 1 1 L1 Real Power L1 Real Power (Parameter 64) reports the real power for line 1 in kW or MW depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L1 Real Power is set to 0. Table 413 - L1 Real Power (Parameter 64) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW or MW L2 Real Power L2 Real Power (Parameter 65) reports the real power for line 2 in kW or MW depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L2 Real Power is set to 0. Table 414 - L2 Real Power (Parameter 65) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW or MW L3 Real Power L3 Real Power (Parameter 66) reports the real power for line 3 in kW or MW depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L3 Real Power is 332 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 set to 0. When Single or Three Phase (Parameter 176) is set to Single Phase, L3 Real Power is set to 0. Table 415 - L3 Real Power (Parameter 66) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW or MW Total Real Power Total Real Power (Parameter 67) reports the total real power of the monitored power conductors in kW or MW depending on the configuration value for Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is set to Three Phase, Total Real Power is calculated as follows: Total Real Power = (L1 Real Power + L2 Real Power + L3 Real Power) When Single or Three Phase (Parameter 176) is set to Single Phase, Total Real Power is calculated as follows: Total Real Power = (L1 Real Power + L2 Real Power) Table 416 - Total Real Power (Parameter 67) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW or MW L1 Reactive Power L1 Reactive Power (Parameter 68) reports the reactive power for line 1 in kVAR or MVAR depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L1 Reactive Power is set to 0. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 333 Chapter 8 Metering and Diagnostics Table 417 - L1 Reactive Power (Parameter 68) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR or MVAR L2 Reactive Power L2 Reactive Power (Parameter 69) reports the reactive power for line 2 in kVAR or MVAR depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L2 Reactive Power is set to 0. Table 418 - L2 Reactive Power (Parameter 69) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR or MVAR L3 Reactive Power L3 Reactive Power (Parameter 70) reports the reactive power for line 3 in kVAR or MVAR depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L3 Reactive Power is set to 0. When Single or Three Phase (Parameter 176) is set to Single Phase, L3 Reactive Power is set to 0. Table 419 - L3 Reactive Power (Parameter 70) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR or MVAR Total Reactive Power Total Reactive Power (Parameter 71) reports the total Reactive power of the monitored power conductors in kVAR or MVAR depending on the 334 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 configuration value for Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is set to Three Phase, Total Reactive Power is calculated as follows: Total Reactive Power = (L1 Reactive Power + L2 Reactive Power + L3 Reactive Power) When Single or Three Phase (Parameter 176) is set to Single Phase, Total Reactive Power is calculated as follows: Total Reactive Power = (L1 Reactive Power + L2 Reactive Power) Table 420 - Total Reactive Power (Parameter 71) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000c -2000000.000 2000000.000 DINT 4 1000 kVAR or MVAR L1 Apparent Power L1 Apparent Power (Parameter 72) reports the apparent power for line 1 in kVA or MVA depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L1 Apparent Power is set to 0. Table 421 - L1 Apparent Power (Parameter 72) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA or MVA L2 Apparent Power L2 Apparent Power (Parameter 73) reports the apparent power for line 2 in kVA or MVA depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L2 Apparent Power is set to 0. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 335 Chapter 8 Metering and Diagnostics Table 422 - L2 Apparent Power (Parameter 73) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA or MVA L3 Apparent Power L3 Apparent Power (Parameter 74) reports the apparent power for line 3 in kVA or MVA depending on the configuration value for Power Scale (Parameter 377). When Voltage Mode (Parameter 352) is set to any Delta base setting, L3 Apparent Power is set to 0. When Single or Three Phase (Parameter 176) is set to Single Phase, L3 Apparent Power is set to 0. Table 423 - L3 Apparent Power (Parameter 74) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA or MVA Total Apparent Power Total Apparent Power (Parameter 75) reports the total apparent power of the monitored power conductors in kVA or MVA depending on the configuration value for Power Scale (Parameter 377). When Single or Three Phase (Parameter 176) is set to Three Phase, Total Apparent Power is calculated as follows: Total Apparent Power = (L1 Apparent Power + L2 Apparent Power + L3 Apparent Power) When Single or Three Phase (Parameter 176) is set to Single Phase, Total Apparent Power is calculated as follows: Total Apparent Power = (L1 Apparent Power + L2 Apparent Power) 336 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 424 - Total Apparent Power (Parameter 75) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA or MVA L1 Power Factor L1 Power Factor (Parameter 76) reports the power factor for line 1 in percentage. When Voltage Mode (Parameter 352) is set to any Delta base setting, L1 Power Factor is set to 0. Table 425 - L1 Power Factor (Parameter 76) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 -100.0 100.0 INT 2 10 % L2 Power Factor Power L2 Power Factor (Parameter 77) reports the power factor for line 2 in percentage. When Voltage Mode (Parameter 352) is set to any Delta base setting, L2 Power Factor is set to 0. Table 426 - L2 Power Factor (Parameter 77) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 -100.0 100.0 INT 2 10 % L3 Power Factor L3 Power Factor (Parameter 78) reports the power factor for line 3 in percentage. When Voltage Mode (Parameter 352) is set to any Delta base setting, L3 Power Factor is set to 0. When Single or Three Phase (Parameter 176) is set to Single Phase, L3 power factor is set to 0. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 337 Chapter 8 Metering and Diagnostics Table 427 - L3 Power Factor (Parameter 78) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 -100.0 100.0 INT 2 10 % Total Power Factor Total Power Factor (Parameter 79) reports the total power factor of the monitored power conductors in percentage. When Single or Three Phase (Parameter 176) is set to Three Phase, Total Power Factor is calculated as follows: Total Power Factor = (L1 Power Factor + L2 Power Factor + L3 Power Factor) / 3 When Single or Three Phase (Parameter 176) is set to Single Phase, Total Power Factor is calculated as follows: Total Power Factor = (L1 Power Factor + L2 Power Factor) / 2 Table 428 - Total Power Factor (Parameter 79) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Energy Monitor 0.0 -100.0 100.0 INT 2 10 % The E300 Electronic Overload Relay’s energy monitor diagnostics provides information on the electrical energy the load is consuming. The energy diagnostics include kWh, kVARh, kVAh, kW Demand, kVAR Demand, and kVA Demand. kWh 109 kWh 109 (Parameter 80) reports a component of total real energy (kWh). Multiply this value by 109 and add to the other kWh parameters. Represents XXX,000,000,000.000 kWh 338 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 429 - kWh x 10E9 (Parameter 80) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kWh 106 kWh 106 (Parameter 81) reports a component of total real energy (kWh). Multiply this value by 106 and add to the other kWh parameters. RepresentsВ 000,XXX,000,000.000В kWh Table 430 - kWh x 10E6 (Parameter 81) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kWh 103 kWh 103 (Parameter 82) reports a component of total real energy (kWh). Multiply this value by 103 and add to the other kWh parameters. Represents 000,000,XXX,000.000 kWh Table 431 - kWh x 10E3 (Parameter 82) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 -999 999 INT 2 1 339 Chapter 8 Metering and Diagnostics kWh 100 kWh 100 (Parameter 83) reports a component of total real energy (kWh). Multiply this value by 100 and add to the other kWh parameters. Represents 000,000,000,XXX.000 kWh Table 432 - kWh x 10E0 (Parameter 83) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kWh 10-3 kWh 10-3 (Parameter 84) reports a component of total real energy (kWh). Multiply this value by 10-3 and add to the other kWh parameters. Represents 000,000,000,000. XXX kWh Table 433 - kWh x 10E-3 (Parameter 84) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Consumed 109 kVARh Consumed 109 (Parameter 85) reports a component of total reactive energy consumed (kVARh). Multiply this value by 109 and add to the other kVARh Consumed parameters. Represents XXX,000,000,000.000 kVARh 340 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 434 - kVARh Consumed x 10E9 (Parameter 85) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Consumed 106 kVARh Consumed 106 (Parameter 86) reports a component of total reactive energy consumed (kVARh). Multiply this value by 106 and add to the other kVARh Consumed parameters. Represents 000,XXX,000,000.000 kVARh Table 435 - kVARh Consumed x 10E6 (Parameter 86) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Consumed 103 kVARh Consumed 103 (Parameter 87) reports a component of total reactive energy consumed (kVARh). Multiply this value by 103 and add to the other kVARh Consumed parameters. Represents 000,000,XXX,000.000 kVARh Table 436 - kVARh Consumed x 10E3 (Parameter 87) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 -999 999 INT 2 1 341 Chapter 8 Metering and Diagnostics kVARh Consumed 100 kVARh Consumed 100 (Parameter 88) reports a component of total reactive energy consumed (kVARh). Multiply this value by 100 and add to the other kVARh Consumed parameters. Represents 000,000,000,XXX.000 kVARh Table 437 - kVARh Consumed x 10E0 (Parameter 88) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Consumed 10-3 kVARh Consumed 10-3 (Parameter 89) reports a component of total reactive energy consumed (kVARh). Multiply this value by 10-3 and add to the other kVARh Consumed parameters. Represents 000,000,000,000. XXX kVARh Table 438 - kVARh Consumed x 10E-3 (Parameter 89) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Generated 109 kVARh Generated 109 (Parameter 90) reports a component of total reactive energy generated (kVARh). Multiply this value by 109 and add to the other kVARh Generated parameters. Represents XXX,000,000,000.000 kVARh 342 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 439 - kVARh Generated x 10E9 (Parameter 90) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Generated 106 kVARh Consumed 106 (Parameter 91) reports a component of total reactive energy generated (kVARh). Multiply this value by 106 and add to the other kVARh Generated parameters. Represents 000,XXX,000,000.000 kVARh Table 440 - kVARh Generated x 10E6 (Parameter 91) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Generated 103 kVARh Generated 103 (Parameter 92) reports a component of total reactive energy generated (kVARh). Multiply this value by 103 and add to the other kVARh Generated parameters. Represents 000,000,XXX,000.000 kVARh Table 441 - kVARh Generated x 10E3 (Parameter 92) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 -999 999 INT 2 1 343 Chapter 8 Metering and Diagnostics kVARh Generated 100 kVARh Generated 100 (Parameter 93) reports a component of total reactive energy generated (kVARh). Multiply this value by 100 and add to the other kVARh Generated parameters. Represents 000,000,000,XXX.000 kVARh Table 442 - kVARh Generated x 10E0 (Parameter 93) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Generated 10-3 kVARh Generated 10-3 (Parameter 94) reports a component of total reactive energy generated (kVARh). Multiply this value by 10-3 and add to the other kVARh Generated parameters. Represents 000,000,000,000. XXX kVARh Table 443 - kVARh Generated x 10E-3 (Parameter 94) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Net 109 kVARh Net 109 (Parameter 95) reports a component of total reactive energy net (kVARh). Multiply this value by 109 and add to the other kVARh Net parameters. Represents XXX,000,000,000.000 kVARh 344 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 444 - kVARh Net x 10E9 (Parameter 95) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Net 106 kVARh Net 106 (Parameter 96) reports a component of total reactive energy net (kVARh). Multiply this value by 106 and add to the other kVARh Net parameters. Represents 000,XXX,000,000.000 kVARh Table 445 - kVARh Net x 10E6 (Parameter 96) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Net 103 kVARh Net 103 (Parameter 97) reports a component of total reactive energy net (kVARh). Multiply this value by 103 and add to the other kVARh Net parameters. Represents 000,000,XXX,000.000 kVARh Table 446 - kVARh Net x 10E3 (Parameter 97) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 -999 999 INT 2 1 345 Chapter 8 Metering and Diagnostics kVARh Net 100 kVARh Net 100 (Parameter 98) reports a component of total reactive energy net (kVARh). Multiply this value by 100 and add to the other kVARh Net parameters. Represents 000,000,000,XXX.000 kVARh Table 447 - kVARh Net x 10E0 (Parameter 98) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVARh Net 10-3 kVARh Net 10-3 (Parameter 99) reports a component of total reactive energy net (kVARh). Multiply this value by 10-3 and add to the other kVARh Net parameters. Represents 000,000,000,000. XXX kVARh Table 448 - kVARh Net x 10E-3 (Parameter 99) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVAh 109 kVAh 109 (Parameter 100) reports a component of total apparent energy (kVAh). Multiply this value by 109 and add to the other kVAh parameters. Represents XXX,000,000,000.000 kVAh 346 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 449 - kVAh x 10E9 (Parameter 100) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVAh 106 kVAh 106 (Parameter 101) reports a component of total apparent energy (kVAh). Multiply this value by 106 and add to the other kVAh parameters. Represents 000,XXX,000,000.000 kVAh Table 450 - kVAh x 10E6 (Parameter 101) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVAh 103 kVAh 103 (Parameter 102) reports a component of total apparent energy (kVAh). Multiply this value by 103 and add to the other kVAh parameters. Represents 000,000,XXX,000.000 kVAh Table 451 - kVAh x 10E3 (Parameter 102) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 -999 999 INT 2 1 347 Chapter 8 Metering and Diagnostics kVAh 100 kVAh 100 (Parameter 103) reports a component of total apparent energy (kVAh). Multiply this value by 100 and add to the other kVAh parameters. Represents 000,000,000,XXX.000 kVAh Table 452 - kVAh x 10E0 (Parameter 103) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kVAh 10-3 kVAh 10-3 (Parameter 104) reports a component of total apparent energy (kVAh). Multiply this value by 10-3 and add to the other kVAh parameters. Represents 000,000,000,000. XXX kVAh Table 453 - kVAh x 10E-3 (Parameter 104) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -999 999 INT 2 1 kW Demand kW Demand (Parameter 105) reports the average real energy usage in kW over a defined period. Table 454 - kW Demand (Parameter 105) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 348 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0.000 -2000000.000 2000000.000 DINT 4 1000 kW Metering and Diagnostics Chapter 8 Max kW Demand Max kW Demand (Parameter 106) reports the maximum kW Demand since the last Max kW Demand Reset command. Table 455 - Max kW Demand (Parameter 106) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW kVAR Demand kVAR Demand (Parameter 107) reports the average reactive energy usage in kVAR over a defined period. Table 456 - kVAR Demand (Parameter 107) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR Max kVAR Demand Max kVAR Demand (Parameter 108) reports the maximum kVAR Demand since the last Max kVAR Demand Reset command. Table 457 - Max kVAR Demand (Parameter 108) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR kVA Demand kVA Demand (Parameter 109) reports the average reactive energy usage in kVA over a defined period. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 349 Chapter 8 Metering and Diagnostics Table 458 - kVA Demand (Parameter 109) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA Max kVA Demand Max kVA Demand (Parameter 110) reports the maximum kVA Demand since the last Max kVA Demand Reset command. Table 459 - Max kVA Demand (Parameter 110) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units Analog Monitor 0.000 0.000 2000000.000 DINT 4 1000 kVA The E300 Electronic Overload Relay’s Analog I/O Expansion Modules scan up to three analog signals per module. This information can be used to monitor the following analog applications: • Motor winding and bearing temperatures that are measured by RTD sensors • Liquid, air, or steam flow • Temperature • Weight • Vessel level • Potentiometer • PTC or NTC thermistor sensors Analog Module 1 Analog Module 1 – Input Channel 00 Analog Module 1 – Input Channel 00 (Parameter 111) reports the monitored value of Analog Module 1 – Input Channel 00. 350 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 460 - Analog Module 1 – Input Channel 00 (Parameter 111) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Input Channel 01 Analog Module 1 – Input Channel 01 (Parameter 112) reports the monitored value of Analog Module 1 – Input Channel 01. Table 461 - Analog Module 1 – Input Channel 01 (Parameter 112) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 – Input Channel 02 Analog Module 1 – Input Channel 02 (Parameter 113) reports the monitored value of Analog Module 1 – Input Channel 02. Table 462 - Analog Module 1 – Input Channel 02 (Parameter 113) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 1 Status Analog Module 1 Status (Parameter 123) reports the status of Analog Module 1. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 351 Chapter 8 Metering and Diagnostics Table 463 - Analog Module 1 Status (Parameter 123) Bit 15 В В В В В В В В В В 14 В В В В В В В В В В 13 В В В В В В В В В В 12 В В В В В В В В В В 11 В В В В В В В В В В 10 В В В В В В В В В В 9 В В В В В В В В В X 8 В В В В В В В В X В 7 В В В В В В В X В В 6 В В В В В В X В В В 5 В В В В В X В В В В 4 В В В В X В В В В В 3 В В В X В В В В В В 2 В В X В В В В В В В 1 В X В В В В В В В В 0 X В В В В В В В В В В В В В В X В В В В В В В В В В В В В В В В В В X В X В X В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В В X В В В В В В В В В В В В В В X В В В В В В В В В В В В В В В Function Input Channel 00 Open Circuit Input Channel 00 Over Range Input Channel 00 Under Range Input Channel 01 Open Circuit Input Channel 01 Over Range Input Channel 01 Under Range Input Channel 02 Open Circuit Input Channel 02 Over Range Input Channel 02 Under Range Output Channel 00 Open Circuit Output Channel 00 Hold Last State Mode Active Output Channel 00 Over Range Output Channel 00 Under Range Analog Module Configured Analog Module Warning (Module Number Dial Changed) Analog Module Faulted Analog Module 2 Analog Module 2 – Input Channel 00 Analog Module 2 – Input Channel 00 (Parameter 114) reports the monitored value of Analog Module 2 – Input Channel 00. Table 464 - Analog Module 2 – Input Channel 00 (Parameter 114) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Input Channel 01 Analog Module 2 – Input Channel 01 (Parameter 115) reports the monitored value of Analog Module 2 – Input Channel 01. 352 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 465 - Analog Module 2 – Input Channel 01 (Parameter 115) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 – Input Channel 02) Analog Module 2 – Input Channel 02 (Parameter 113) reports the monitored value of Analog Module 2 – Input Channel 02. Table 466 - Analog Module 2 – Input Channel 02 (Parameter 116) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 2 Status Analog Module 2 Status (Parameter 124) reports the status of Analog Module 2. Table 467 - Analog Module 2 Status (Parameter 124) Bit 15 В В В В В В В В В В В В В В В X 14 В В В В В В В В В В В В В В X В 13 В В В В В В В В В В В В В X В В 12 В В В В В В В В В В В В X В В В 11 В В В В В В В В В В В X В В В В 10 В В В В В В В В В В X В В В В В 9 В В В В В В В В В X В В В В В В 8 В В В В В В В В X В В В В В В В 7 В В В В В В В X В В В В В В В В 6 В В В В В В X В В В В В В В В В 5 В В В В В X В В В В В В В В В В 4 В В В В X В В В В В В В В В В В 3 В В В X В В В В В В В В В В В В 2 В В X В В В В В В В В В В В В В 1 В X В В В В В В В В В В В В В В 0 X В В В В В В В В В В В В В В В Function Input Channel 00 Open Circuit Input Channel 00 Over Range Input Channel 00 Under Range Input Channel 01 Open Circuit Input Channel 01 Over Range Input Channel 01 Under Range Input Channel 02 Open Circuit Input Channel 02 Over Range Input Channel 02 Under Range Output Channel 00 Open Circuit Output Channel 00 Hold Last State Mode Active Output Channel 00 Over Range Output Channel 00 Under Range Analog Module Configured Analog Module Warning (Module Number Dial Changed) Analog Module Faulted Rockwell Automation Publication 193-UM015C-EN-P - December 2014 353 Chapter 8 Metering and Diagnostics Analog Module 3 Analog Module 3 – Input Channel 00 Analog Module 3 – Input Channel 00 (Parameter 117) reports the monitored value of Analog Module 3 – Input Channel 00. Table 468 - Analog Module 3 – Input Channel 00 (Parameter 117) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Input Channel 01 Analog Module 3 – Input Channel 01 (Parameter 118) reports the monitored value of Analog Module 3 – Input Channel 01. Table 469 - Analog Module 3 – Input Channel 01 (Parameter 118) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 – Input Channel 02 Analog Module 3 – Input Channel 02 (Parameter 119) reports the monitored value of Analog Module 3 – Input Channel 02. Table 470 - Analog Module 3 – Input Channel 02 (Parameter 119) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 3 Status Analog Module 3 Status (Parameter 125) reports the status of Analog Module 3. 354 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 471 - Analog Module 3 Status (Parameter 125) Bit 15 В В В В В В В В В В В В В В В X 14 В В В В В В В В В В В В В В X В 13 В В В В В В В В В В В В В X В В 12 В В В В В В В В В В В В X В В В 11 В В В В В В В В В В В X В В В В 10 В В В В В В В В В В X В В В В В 9 В В В В В В В В В X В В В В В В 8 В В В В В В В В X В В В В В В В 7 В В В В В В В X В В В В В В В В 6 В В В В В В X В В В В В В В В В 5 В В В В В X В В В В В В В В В В 4 В В В В X В В В В В В В В В В В 3 В В В X В В В В В В В В В В В В 2 В В X В В В В В В В В В В В В В 1 В X В В В В В В В В В В В В В В 0 X В В В В В В В В В В В В В В В Function Input Channel 00 Open Circuit Input Channel 00 Over Range Input Channel 00 Under Range Input Channel 01 Open Circuit Input Channel 01 Over Range Input Channel 01 Under Range Input Channel 02 Open Circuit Input Channel 02 Over Range Input Channel 02 Under Range Output Channel 00 Open Circuit Output Channel 00 Hold Last State Mode Active Output Channel 00 Over Range Output Channel 00 Under Range Analog Module Configured Analog Module Warning (Module Number Dial Changed) Analog Module Faulted Analog Module 4 Analog Module 4 – Input Channel 00 Analog Module 4 – Input Channel 00 (Parameter 120) reports the monitored value of Analog Module 4 – Input Channel 00. Table 472 - Analog Module 4 – Input Channel 00 (Parameter 120) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Input Channel 01 Analog Module 4 – Input Channel 01 (Parameter 121) reports the monitored value of Analog Module 4 – Input Channel 01. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 355 Chapter 8 Metering and Diagnostics Table 473 - Analog Module 4 – Input Channel 01 (Parameter 121) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 – Input Channel 02 Analog Module 4 – Input Channel 02 (Parameter 122) reports the monitored value of Analog Module 4 – Input Channel 02. Table 474 - Analog Module 4 – Input Channel 02 (Parameter 122) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0 -32768 32767 INT 2 1 В Analog Module 4 Status Analog Module 4 Status (Parameter 126) reports the status of Analog Module 4. Table 475 - Analog Module 4 Status (Parameter 126) 356 Bit 15 В В В В В В В В В В В В В В 14 В В В В В В В В В В В В В В 13 В В В В В В В В В В В В В X 12 В В В В В В В В В В В В X В 11 В В В В В В В В В В В X В В 10 В В В В В В В В В В X В В В 9 В В В В В В В В В X В В В В 8 В В В В В В В В X В В В В В 7 В В В В В В В X В В В В В В 6 В В В В В В X В В В В В В В 5 В В В В В X В В В В В В В В 4 В В В В X В В В В В В В В В 3 В В В X В В В В В В В В В В 2 В В X В В В В В В В В В В В 1 В X В В В В В В В В В В В В 0 X В В В В В В В В В В В В В В X В В В В В В В В В В В В В В X В В В В В В В В В В В В В В В Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Function Input Channel 00 Open Circuit Input Channel 00 Over Range Input Channel 00 Under Range Input Channel 01 Open Circuit Input Channel 01 Over Range Input Channel 01 Under Range Input Channel 02 Open Circuit Input Channel 02 Over Range Input Channel 02 Under Range Output Channel 00 Open Circuit Output Channel 00 Hold Last State Mode Active Output Channel 00 Over Range Output Channel 00 Under Range Analog Module Configured Analog Module Warning (Module Number Dial Changed) Analog Module Faulted Metering and Diagnostics Trip / Warning History Chapter 8 The E300 Electronic Overload Relay provides a trip and warning history in which the last five trips and last five warnings are recorded into nonvolatile storage. A mask is available to limit which trip and warning events are logged to the history's memory. Trip History When the E300 Electronic Overload Relay issue a trip, the reason for the trip is recorded into the Trip History. Table 476 lists the codes that are available for the trip history records. Table 476 - Trip History Codes Trip History Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 25 26 27 28 29 30 31 32 33 34 35 36 37 Description No Fault Conditions Detected Motor current overload condition Phase current Loss is detected in one of the motor phases Power conductor or motor winding is shorting to ground Motor has not reached full speed by the end of Stall Enable Time Motor current has exceeded the programmed jam trip level Motor current has fallen below normal operating levels Phase to phase current imbalance detected L1Current was below L1 Undercurrent Level longer than Trip Delay L2Current was below L2 Undercurrent Level longer than Trip Delay L3Current was below L3 Undercurrent Level longer than Trip Delay L1 Current was over L1 Overcurrent Level longer than Trip Delay L2 Current was over L2 Overcurrent Level longer than Trip Delay L3 Current was over L3 Overcurrent Level longer than Trip Delay L1 Current Lost for longer than the L1 Loss Trip Delay L2 Current Lost for longer than the L2 Loss Trip Delay L3 Current Lost for longer than the L3 Loss Trip Delay Line to Line Under-Voltage condition detected Line to Line Over-Voltage condition detected Phase to phase voltage imbalance detected The unit detects the supply voltage phases are rotated Line voltage frequency is below trip level Line voltage frequency has exceeded trip level Sensing Module boot loader failed to load firmware Sensing Module output enable open Sensing Module missing interrupts Sensing Module not calibrated Sensing Module frame type failure Sensing Module flash configuration failure Sensing Module detected an overrun error Sensing Module is not responding Total Real Power (kW) is below trip level Total Real Power (kW) has exceeded trip level Under Total Reactive Power Consumed (+kVAR) condition detected Over Total Reactive Power Consumed (+kVAR) condition detected Under Total Reactive Power Generated (-kVAR) condition detected Rockwell Automation Publication 193-UM015C-EN-P - December 2014 357 Chapter 8 Metering and Diagnostics Trip History Code 38 39 40 41 42 43 44 49 50 51 52 53 54 55 56 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 81 82 83 84 85 86 87 88 90 91 92 93 94 358 Description Over Total Reactive Power Generated (-kVAR) condition detected Total Apparent Power (VA or kVA or MVA) is below trip level Total Apparent Power (VA or kVA or MVA) exceeded trip level Under Total Power Factor Lagging (-PF) condition detected Over Total Power Factor Lagging (-PF) condition detected Under Total Power Factor Leading (+PF) condition detected Over Total Power Factor Leading (+PF) condition detected Test trip caused by holding the Test/Reset button for 2 seconds PTC input indicates that the motor stator windings overheated DeviceLogix defined trip was generated The Stop button the Operator Station was pressed Remote trip command detected Maximum starts per hour exceeded Hardware configuration fault. Check for shorts on input terminal Invalid parameter config. See parameters 38-39 for details DeviceLogix Feedback Timeout Trip was detected Control Module CAN0 initialization failure Control Module CAN0 bus failure Control Module CAN1 initialization failure Control Module CAN1 bus failure Control Module ADC0 failure Control Module detected too many CRC errors Input Channel 00 on Analog Module 1 exceeded its Trip Level Input Channel 01 on Analog Module 1 exceeded its Trip Level Input Channel 02 on Analog Module 1 exceeded its Trip Level Input Channel 00 on Analog Module 2 exceeded its Trip Level Input Channel 01 on Analog Module 2 exceeded its Trip Level Input Channel 02 on Analog Module 2 exceeded its Trip Level Input Channel 00 on Analog Module 3 exceeded its Trip Level Input Channel 01 on Analog Module 3 exceeded its Trip Level Input Channel 02 on Analog Module 3 exceeded its Trip Level Input Channel 00 on Analog Module 4 exceeded its Trip Level Input Channel 01 on Analog Module 4 exceeded its Trip Level Input Channel 02 on Analog Module 4 exceeded its Trip Level External NVS Chip has detected communication timeout error External NVS Chip has detected a CRC error External NVS Chip has detected data out of range Digital Expansion Module 1 is not operating properly Digital Expansion Module 2 is not operating properly Digital Expansion Module 3 is not operating properly Digital Expansion Module 4 is not operating properly Analog Expansion Module 1 is not operating properly Analog Expansion Module 2 is not operating properly Analog Expansion Module 3 is not operating properly Analog Expansion Module 4 is not operating properly Control Module installed does not match the expected type Sensing Module installed does not match the expected type Comms Module installed does not match the expected type Operator Station installed does not match expected type Digital Module installed does not match the expected type Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Trip History Code 95 96 97 98 Chapter 8 Description Analog Module installed does not match the expected type Test Mode is engaged and current/voltage was detected Heap memory could not be allocated Vendor ID hardware fault Trip History Mask You can decide which trip events are recorded into the E300 Electronic Overload Relay’s trip history by using the Trip History Masks. Current Trip History Mask Current Trip History Mask (Parameter 139) allows you to select which currentbased trip events are recorded in the trip history. Table 477 - Current Trip History Mask (Parameter 139) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X X X X 0 Function X Overload Trip Phase Loss Trip Ground Fault Trip Stall Trip Jam Trip Underload Trip Current Imbalance Trip L1 Under Current Trip L2 Under Current Trip L3 Under Current Trip L1 Over Current Trip L2 Over Current Trip L3 Over Current Trip L1 Line Loss Trip L2 Line Loss Trip L3 Line Loss Trip Voltage Trip History Mask Voltage Trip History Mask (Parameter 140) allows you to select which voltagebased trip events are recorded in the trip history. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 359 Chapter 8 Metering and Diagnostics Table 478 - Voltage Trip History Mask (Parameter 140) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X 0 Function X Under Voltage Trip Over Voltage Trip Voltage Imbalance Trip Phase Rotation Trip Under Frequency Trip Over Frequency Trip Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Power Trip History Mask Power Trip History Mask (Parameter 141) allows you to select which powerbased trip events are recorded in the trip history. Table 479 - Power Trip History Mask (Parameter 141) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 0 Function X Under kW Trip Over kW Trip Under kVAR Consumed Trip Over kVAR Consumed Trip Under kVAR Generated Trip Over kVAR Generated Trip Under kVA Trip Over kVA Trip Under Power Factor Lagging Trip Over Power Factor Lagging Trip Under Power Factor Leading Trip Over Power Factor Leading Trip Reserved Reserved Reserved Reserved Control Trip History Mask Control Trip History Mask (Parameter 142) allows you to select which controlbased trip events are recorded in the trip history. 360 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Chapter 8 Table 480 - Control Trip History Mask (Parameter 142) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X X 0 Function X Test Trip PTC Trip DeviceLogix Trip Operator Station Trip Remote Trip Blocked Start Trip Hardware Fault Trip Configuration Trip Option Match Trip Feedback Timeout Trip Expansion Bus Trip Reserved Reserved Nonvolatile Memory Trip Test Mode Trip Reserved Analog Trip History Mask Analog Trip History Mask (Parameter 143) allows you to select which analogbased trip events are recorded in the trip history. Table 481 - Analog Trip History Mask (Parameter 143) Bit 15 В В В В В В В В В В В В 14 В В В В В В В В В В В В 13 В В В В В В В В В В В В 12 В В В В В В В В В В В В 11 В В В В В В В В В В В X 10 В В В В В В В В В В X В 9 В В В В В В В В В X В В 8 В В В В В В В В X В В В 7 В В В В В В В X В В В В 6 В В В В В В X В В В В В 5 В В В В В X В В В В В В 4 В В В В X В В В В В В В 3 В В В X В В В В В В В В 2 В В X В В В В В В В В В 1 В X В В В В В В В В В В 0 X В В В В В В В В В В В Function Analog Module 1 - Input Channel 00 Trip Analog Module 1 - Input Channel 01 Trip Analog Module 1 - Input Channel 02 Trip Analog Module 2 - Input Channel 00 Trip Analog Module 2 - Input Channel 01 Trip Analog Module 2 - Input Channel 02 Trip Analog Module 3 - Input Channel 00 Trip Analog Module 3 - Input Channel 01 Trip Analog Module 3 - Input Channel 02 Trip Analog Module 4 - Input Channel 00 Trip Analog Module 4 - Input Channel 01 Trip Analog Module 4 - Input Channel 02 Trip Warning History When the E300 Electronic Overload Relay issue a warning, the reason for the warning is recorded into the Warning History. Table 482 lists the codes that are available for the warning history records. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 361 Chapter 8 Metering and Diagnostics Table 482 - Warning History Codes Warning History Code 0 1 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 33 34 35 36 37 38 39 40 41 42 43 44 50 51 56 58 60 61 65 66 67 68 69 70 71 72 73 362 Description No Warning Conditions Detected Approaching a motor current overload condition Power conductor or motor winding is shorting to ground Motor current has exceed the programmed jam warning level Motor current has fallen below normal operating levels Phase to phase current imbalance detected L1 Current was below L1 Undercurrent Warning Level L2 Current was below L2 Undercurrent Warning Level L3 Current was below L3 Undercurrent Warning Level L1 Current was over L1 Overcurrent Warning Level L2 Current was over L2 Overcurrent Warning Level L3 Current was over L3 Overcurrent Warning Level L1 Current Lost for longer than the L1 Loss Trip Delay L2 Current Lost for longer than the L2 Loss Trip Delay L3 Current Lost for longer than the L3 Loss Trip Delay Line to Line Under-Voltage condition detected Line to Line Over-Voltage condition detected Phase to phase voltage imbalance detected The unit detects the supply voltage phases are rotated Line voltage frequency is below the warning level Line voltage frequency has exceeded warning level Total Real Power (kW) is below warning level Total Real Power (kW) has exceeded warning level Under Reactive Power Consumed (+kVAR) condition detected Over Reactive Power Consumed (+kVAR) condition detected Under Reactive Power Generated (-kVAR) condition detected Over Reactive Power Generated (-kVAR) condition detected Total Apparent Power (kVA) is below warning level Total Apparent Power (kVA) exceeded warning level Under Total Power Factor Lagging (-PF) condition detected Over Total Power Factor Lagging (-PF) condition detected Under Total Power Factor Leading (+PF) condition detected Over Total Power Factor Leading (+PF) condition detected PTC input indicates that the motor stator windings overheated DeviceLogix defined warning was generated Invalid parameter config. See parameters 38-39 for details DeviceLogix Feedback Timeout Trip was detected Number of Starts Warning Level Exceeded Operating Hours Warning Level Exceeded Input Channel 00 on Analog Module 1 exceeded its Warning Level Input Channel 01 on Analog Module 1 exceeded its Warning Level Input Channel 02 on Analog Module 1 exceeded its Warning Level Input Channel 00 on Analog Module 2 exceeded its Warning Level Input Channel 01 on Analog Module 2 exceeded its Warning Level Input Channel 02 on Analog Module 2 exceeded its Warning Level Input Channel 00 on Analog Module 3 exceeded its Warning Level Input Channel 01 on Analog Module 3 exceeded its Warning Level Input Channel 02 on Analog Module 3 exceeded its Warning Level Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Metering and Diagnostics Warning History Code 74 75 76 81 82 83 84 85 86 87 88 90 91 92 93 94 95 98 Chapter 8 Description Input Channel 00 on Analog Module 4 exceeded its Warning Level Input Channel 01 on Analog Module 4 exceeded its Warning Level Input Channel 02 on Analog Module 4 exceeded its Warning Level Digital Expansion Module 1 is not operating properly Digital Expansion Module 2 is not operating properly Digital Expansion Module 3 is not operating properly Digital Expansion Module 4 is not operating properly Analog Expansion Module 1 is not operating properly Analog Expansion Module 2 is not operating properly Analog Expansion Module 3 is not operating properly Analog Expansion Module 4 is not operating properly Control Module installed does not match the expected type Sensing Module installed does not match the expected type Comms Module installed does not match the expected type Operator Station installed does not match expected type Digital Module installed does not match the expected type Analog Module installed does not match the expected type A hardware fault condition was detected Warning History Mask You can decide which warning events are recorded into the E300 Electronic Overload Relay’s warning history by using the Warning History Masks. Current Warning History Mask Current Warning History Mask (Parameter 145) allows you to select which current-based warning events are recorded in the warning history. Table 483 - Current Warning History Mask (Parameter 145) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 X X X X X X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 0 Function X Overload Warning Reserved Ground Fault Warning Reserved Jam Warning Underload Warning Current Imbalance Warning L1 Under Current Trip L2 Under Current Trip L3 Under Current Trip L1 Over Current Trip L2 Over Current Trip L3 Over Current Trip L1 Line Loss Trip L2 Line Loss Trip L3 Line Loss Trip 363 Chapter 8 Metering and Diagnostics Voltage Warning History Mask Voltage Warning History Mask (Parameter 146) allows you to select which voltage-based warning events are recorded in the warning history. Table 484 - Voltage Warning History Mask (Parameter 146) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X 0 X Function Under Voltage Warning Over Voltage Warning Voltage Imbalance Warning Phase Rotation Warning Under Frequency Warning Over Frequency Warning Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Power Warning History Mask Power Warning History Mask (Parameter 147) allows you to select which powerbased warning events are recorded in the warning history. Table 485 - Power Warning History Mask (Parameter 147) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X X X X X 364 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Function X Under kW Warning Over kW Warning Under kVAR Consumed Warning Over kVAR Consumed Warning Under kVAR Generated Warning Over kVAR Generated Warning Under kVA Warning Over kVA Warning Under Power Factor Lagging Warning Over Power Factor Lagging Warning Under Power Factor Leading Warning Over Power Factor Leading Warning Reserved Reserved Reserved Reserved Metering and Diagnostics Chapter 8 Control Warning History Mask Control Warning History Mask (Parameter 148) allows you to select which control-based warning events are recorded in the warning history. Table 486 - Control Warning History Mask (Parameter 148) Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 X X X X X X X 0 Function Reserved PTC Warning DeviceLogix Warning Reserved Reserved Reserved Reserved Reserved Option Match Warning Feedback Timeout Warning Expansion Bus Warning Number Of Starts Warning Operating Hours Warning Reserved Reserved Reserved Analog Warning History Mask Analog Warning History Mask (Parameter 149) allows you to select which control-based warning events are recorded in the warning history. Table 487 - Analog Warning History Mask (Parameter 149) Bit 15 В В В В В В В В В В В В 14 В В В В В В В В В В В В 13 В В В В В В В В В В В В 12 В В В В В В В В В В В В 11 В В В В В В В В В В В X 10 В В В В В В В В В В X В 9 В В В В В В В В В X В В 8 В В В В В В В В X В В В 7 В В В В В В В X В В В В 6 В В В В В В X В В В В В 5 В В В В В X В В В В В В 4 В В В В X В В В В В В В 3 В В В X В В В В В В В В 2 В В X В В В В В В В В В 1 В X В В В В В В В В В В Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 X В В В В В В В В В В В Function Analog Module 1 - Input Channel 00 Warning Analog Module 1 - Input Channel 01 Warning Analog Module 1 - Input Channel 02 Warning Analog Module 2 - Input Channel 00 Warning Analog Module 2 - Input Channel 01 Warning Analog Module 2 - Input Channel 02 Warning Analog Module 3 - Input Channel 00 Warning Analog Module 3 - Input Channel 01 Warning Analog Module 3 - Input Channel 02 Warning Analog Module 4 - Input Channel 00 Warning Analog Module 4 - Input Channel 01 Warning Analog Module 4 - Input Channel 02 Warning 365 Chapter 8 Metering and Diagnostics Trip Snapshot Trip Snapshot L1-L2 Voltage Trip Snapshot L1-L2 Voltage (Parameter 156) reports the voltage in volts in reference to the T1 and T2 power terminals of the E300 Electronic Overload Relay Sensing Module at the time of the most recent trip event. Table 488 - Trip Snapshot L1-L2 Voltage (Parameter 156) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Trip Snapshot L2-L3 Voltage Trip Snapshot L2-L3 Voltage (Parameter 157) reports the voltage in volts in reference to the T2 and T3 power terminals of the E300 Electronic Overload Relay Sensing Module at the time of the most recent trip event. Table 489 - Trip Snapshot L2-L3 Voltage (Parameter 157) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.0 0.0 6553.5 UINT 2 10 Volts Trip Snapshot L3-L1 Voltage Trip Snapshot L3-L1 Voltage (Parameter 158) reports the voltage in volts in reference to the T3 and T1 power terminals of the E300 Electronic Overload Relay Sensing Module at the time of the most recent trip event. Table 490 - Trip Snapshot L3-L1 Voltage (Parameter 158) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 366 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0.0 0.0 6553.5 UINT 2 10 Volts Metering and Diagnostics Chapter 8 Trip Snapshot Total Real Power Trip Snapshot Total Real Power (Parameter 159) reports the total real power of the monitored power conductors in kW at the time of the most recent trip event. Table 491 - Trip Snapshot Total Real Power (Parameter 159) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kW Trip Snapshot Total Reactive Power Trip Snapshot Total Reactive Power (Parameter 160) reports the total Reactive power of the monitored power conductors in kVAR at the time of the most recent trip event. Table 492 - Trip Snapshot Total Reactive Power (Parameter 160) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 -2000000.000 2000000.000 DINT 4 1000 kVAR or MVAR Trip Snapshot Total Apparent Power Trip Snapshot Total Apparent Power (Parameter 161) reports the total apparent power of the monitored power conductors in kVA at the time of the most recent trip event. Table 493 - Trip Snapshot Total Apparent Power (Parameter 161) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 0.000 0.000 2000000.000 DINT 4 1000 kVA Rockwell Automation Publication 193-UM015C-EN-P - December 2014 367 Chapter 8 Metering and Diagnostics Trip Snapshot Total Power Factor Trip Snapshot Total Power Factor (Parameter 162) reports the total power factor of the monitored power conductors in percentage at the time of the most recent trip event. Table 494 - Trip Snapshot Total Power Factor (Parameter 162) Default Value Minimum Value Maximum Value Parameter Type Size (Bytes) Scaling Factor Units 368 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0.0 -100.0 100.0 INT 2 10 % Chapter 9 EtherNet/IP Communications Introduction This chapter provides the necessary instructions to successfully connect the E300 Electronic Overload Relay EtherNet/IP Communication Module (Catalog Number 193-ECM-ETR) to an Ethernet network and configure it to communicate to an EtherNet/IP scanner such as an Allen-Bradley Logix controller. Network Design The E300 Electronic Overload Relay EtherNet/IP Communication Module has dual Ethernet ports that function as an Ethernet switch with RJ45 ports to connect Ethernet cable CAT5 type or better to. Rockwell Automation offers a wide variety of Allen-Bradley Ethernet patch cables with its Bulletin 1585 line of Ethernet cables (http://ab.rockwellautomation.com/Connection-Devices/ RJ45-Network-Media). The E300 Electronic Overload Relay EtherNet/IP Communication Module supports a Star, Linear, and Ring Ethernet topology. Figure 49 shows an example of a Star Ethernet Topology, in which all Ethernet nodes wire back to a central Ethernet switch, hub, or router. Figure 49 - Star Ethernet Topology Rockwell Automation Publication 193-UM015C-EN-P - December 2014 369 Chapter 9 EtherNet/IP Communications Rockwell Automation also offers a line of managed and unmanagedпЂ Allen-Bradley Ethernet Switches with its Stratix family of Ethernet switches. See http://ab.rockwellautomation.com/Networks-and-Communications/EthernetIP-Infrastructure for more information. The E300 Electronic Overload Relay EtherNet/IP Communication Module also supports an ethernet Ring topology in which all ethernet nodes are wired in series with one another until a complete network ring is made as shown in Figure 50. The E300 Electronic Overload Relay EtherNet/IP Communication Module supports Rockwell Automation's Device Level Ring (DLR) topology as a slave device in which the EtherNet/IP network continues to communicate if one of the network chains is disrupted Figure 50 - Ring Ethernet Topology 370 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Determining Network Parameters Chapter 9 To operate an EtherNet/IP network, you must define these parameters. Table 495 - EtherNet/IP Network Parameters Network Parameter Description IP Address The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where each xxx is a number from 0...255. Do not use the following IP addresses, as these are reserved values: • 0.0.0.1...0.255.255.255 • 127.0.0.0...127.255.255.255 • 224.255.255.255...255.255.255.255 Subnet Mask Subnet addressing is an extension of the IP address scheme that allows a site to use a single network ID for multiple physical networks. Routing outside of the site continues by dividing the IP address into a net ID and a host ID via the class. Inside a site, the subnet mask is used to redivide the IP address into a custom network ID portion and host ID portion. NOTE: If you change the subnet mask of an alreadyconfigured module, you must cycle power to the module for the change to take effect. Gateway A gateway connects individual physical networks into a system of networks. When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. If DNS addressing is used or if the module is referenced via a host name in an MSG instruction, the following parameters must be defined. IMPORTANT Consult with your Ethernet network administrator to determine if these parameters need to be specified. Table 496 - EtherNet/IP Network Parameters for DNS Addressing Network Parameter Description Host Name A host name is part of a text address that identifies the module. The full text address of a module is: host_name.domain_name. Domain Name A domain name is part of a text address that identifies the domain in which the module resides. The full text address of a module is: host_name.domain_name. The domain name has a 48-character limit. Primary DNS Server Address This identifies any DNS servers that are used in the network. You must have a DNS server configured if you specify an SMTP server with a name. The DNS server converts the domain name or host name to an IP address that can be used by the network. For more information on DNS addressing, see page 380. Secondary DNS Server Address Rockwell Automation Publication 193-UM015C-EN-P - December 2014 371 Chapter 9 EtherNet/IP Communications Setting the IP Network Address The E300 Electronic Overload Relay EtherNet/IP Communication Module ships with DHCP enabled. You can set the network Internet Protocol (IP) address by using: • The EtherNet/IP node address selection switches • A Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol (DHCP) server (for example, the Rockwell Automation BOOTP-DHCP Server Utility, which is included with Rockwell Software's RSLinx Classic software) • A web browser and MAC scanner software EtherNet/IP Node Address Selection Switches The E300 Electronic Overload Relay EtherNet/IP Communication Module comes with three node address selection switches that allow you to select the last octet for the IP address 192.168.1.xxx. Network Information - MAC Id - Serial Number - Firmware Revision Node Address x100 Node Address 001 - 254 255 - 887 889 - 999 888 000 EXAMPLE x10 x1 Function Set IP Address to 192.168.1.xxx Set IP Address via DHCP or use static IP Address Reset to factory defaults Administration mode When the left dial is set to 1, the middle dial is set to 2, and the right dial is set to 3, the resulting IP address is: 192.168.1.123. When the node address selection switches are set to a value greater than 255 (excluding 888), the IP address is set to DHCP Enabled or programmed for a static IP address.A power cycle is required for any selection changes to take effect. 372 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 Assign Network Parameters via the BOOTP/ DHCP Utility By default, the E300 Electronic Overload Relay EtherNet/IP Communication Module is DHCP Enabled. The BOOTP/DHCP utility is a standalone program that is located in the BOOTPDHCP Server folder accessed from the Start menu. IMPORTANT Before starting the BOOTP/DHCP utility, make sure you have the hardware MAC ID of the module, which is printed on the front of the E300 Electronic Overload Relay EtherNet/IP Communication Module. The MAC ID has a format similar to: 00-0b-db-14-55-35. This utility recognizes DHCP-enabled devices and provides an interface to configure a static IP address for each device. To assign network parameters via the BOOTP/DHCP utility, perform this procedure: 1. Execute the BOOTP/DHCP software. 2. Choose Tool >Network Settings. 3. If appropriate for the network, type the subnet mask, gateway address, primary/secondary server addresses, and domain name in their respective fields. 4. Click OK.пЂ The Request History panel displays the hardware addresses of modules issuing BOOTP or DHCP requests. 5. Double-click the MAC address of the module to be configured. NOTE: The MAC address is printed underneath the sliding front cover of the E300 Electronic Overload Relay EtherNet/IP Communication Module. The format of the hardware address resembles: 00-0b-db-14-55-35 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 373 Chapter 9 EtherNet/IP Communications The New Entry window appears with the module's Ethernet Address (MAC). 6. Type the IP address, host name, and a module description. 7. Click OK. 8. Cycle power to the E300 Electronic Overload Relay EtherNet/IP Communication Module. 9. To permanently assign this configuration to the module: Select the module in the Relation List panel and click Disable BOOTP/DHCP. When module power is cycled, it uses the assigned configuration and does not issue a DHCP request. If you do not click Disable BOOTP/DHCP, on a power cycle, the module clears the current IP configuration and again begins sending DHCP requests. 374 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 Assign Network Parameters Via a Web Browser and MAC Scanner Software If you do not have access to a DHCP software utility, you can assign network parameters via a web browser (for example, MicrosoftВ® Internet Explorer) and Media Access Control (MAC) scanner software (for example, MAC Scanner from ColasoftВ® - http://www.colasoft.com/). Follow these steps to configure the module using this method. 1. Locate and identify the MAC ID printed on the label of the E300 Electronic Overload Relay EtherNet/IP Communication Module. This address has a format that is similar to: 00-0b-db-14-55-35 2. Connect the E300 Electronic Overload Relay EtherNet/IP Communication Module to the same wide area network (WAN) as your personal computer. 3. Initiate the MAC scanner software. 4. Select the appropriate subnet to scan for available MAC addresses. 5. Scan the Subnet for all available MAC addresses . 6. Identify the IP address assigned to the MAC ID of the E300 Electronic Overload Relay EtherNet/IP Communication Module. The IP address will have a format that is similar to 192.168.0.100. Other Factors to Consider When Assigning Network Parameters There are other factors to consider when assigning network parameters, which include: • Network isolation from or integration into the plant/enterprise network. • Network size. For large networks, even isolated networks, it might be more convenient and safer to use a BOOTP/DHCP server rather than RSLinx software. The BOOTP/DHCP server also limits the possibility of assigning duplicate IP addresses. • Company policies and procedures that are associated with plant floor network installation and maintenance. • Level of involvement by information technology personnel in plant floor network installation and maintenance. • Type of training that is offered to control engineers and maintenance personnel. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 375 Chapter 9 EtherNet/IP Communications If the Rockwell Automation DHCP server is used in an uplinked subnet where an enterprise DHCP server exists, a module may get an address from the enterprise server before the Rockwell Automation utility even sees the module. In this case, disconnect the uplink to set the address and configure the module to retain its static address before reconnecting to the uplink. This is not a problem if you have node names configured in the module and leave DHCP enabled. Web Server As a security precaution the embedded web server of the E300 Electronic Overload Relay EtherNet/IP Communication Module is disabled by default. To temporarily enable the web server to make it permanently available, you must enter into Administration Mode. To do this, set the rotary dials that are located underneath the front cover of the E300 Electronic Overload Relay EtherNet/IP Communication Module to 000 and cycle power. The device will then go online with the IP Address used at the time of the previous start-up. Web Server Security and System Password The E300 EtherNet/IP Communication Module’s web server allows you to view any diagnostic and parameter information. Security measures are built into the web server to deter a malicious user from making any unwanted EtherNet/IP system changes and E300 configuration parameter edits. When you attempt to make an EtherNet/IP system change or E300 configuration parameter edit, you will be prompted to enter a user name and password. System User Name The user name Administrator (case sensitive) is the only user name that allows you to make EtherNet/IP system changes or E300 configuration parameter edits. System Password For EtherNet/IP Communication Modules with firmware v1.003, the default password is <blank>. 376 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 For EtherNet/IP Communication Modules with firmware v1.004 and higher, the default password is the serial number of the E300 EtherNet/IP Communication Module which can be found on the home page of the E300 web server. It is recommended that you change the password for user name Administrator to deter any malicious activity through the E300 EtherNet/IP Communication Module’s web server. The password can be change on the password configuration web page. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 377 Chapter 9 EtherNet/IP Communications Resetting the System Password If the password for user name Administrator is misplaced or forgotten, you can restore the password to the factory default value by turning the rotary dials on the E300 EtherNet/IP Communication Module to 8-8-8 and cycling power. This resets all EtherNet/IP communication settings and E300 configuration parameters back to the factory default values. Permanently Enabling the Web Server In Administrative Mode, you can change any configuration parameter of the E300 Electronic Overload Relay including permanently enabling the embedded web server by following these steps: 1. Enter Administrative Mode by turning the rotary dials to 000 and cycle power on the E300 Electronic Overload Relay 2. Access the web page 3. Navigate to Administrative Settings->Network Configuration 4. You will be prompted for user name and password. Enter "Administrator" for the user name, and enter the appropriate password. 378 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 5. Enable the Web Server Control and press Apply Changes Duplicate IP Address Detection When you change the IP address or connect the module to an EtherNet/IP network, the module checks to make sure that the IP address assigned to this module does not match the address of any other network device. If the module determines that another device on the network with a matching IP address, the EtherNet/IP port of the module goes into conflict mode where the Network Status LED indicator is solid red. To resolve this conflict, use the following instructions to change the IP address of the module. Then, cycle power to the module or reset the modules by disconnecting and then reconnecting the Ethernet cable. Two modules could possibly detect a conflict simultaneously. If this occurs, perform this procedure. 1. Remove the module with the incorrect IP address and correct its conflict. 2. Cycle power or disconnect the Ethernet cable from the second module and reconnect it. Behavior of Modules With Duplicate IP Addresses Devices in conflict over an IP address behave differently depending on whether connections have been established to either of the modules and whether both modules support duplicate IP address detection. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 379 Chapter 9 EtherNet/IP Communications Table 497 - Device Conflict over Duplicate IP Addresses DNS Addressing If then both modules support duplicate IP address detection, the first started module uses and retains its IP address. The other module will detect a conflict, give up the IP address and enter conflict mode. both modules support duplicate IP address detection and are started at roughly the same time, one of the modules surrenders the IP address and enters conflict mode. one module supports duplicate IP address detection and a second module does not, the second module generally keeps its IP address, regardless of which module first obtains the IP address. The module that supports duplicate IP address detection will detect the conflict and give up the IP address. To further qualify a module’s address, use DNS addressing to specify a host name for a module, which also includes specifying a domain name and DNS servers. DNS addressing makes it possible to configure similar network structures and IP address sequences under different domains. DNS addressing is only necessary if you see the module by host name, such as in path descriptions in MSG instructions. To use DNS addressing, perform this procedure. 1. Assign a host name to the module. NOTE: Contact the network administrator to have a host name assigned. Valid host names should be compliant with IEC-1131-3. 2. Configure the module's parameters. In addition to the IP address, subnet mask, and gateway address, configure a host name for the module, domain name, and primary/secondary DNS server addresses. Electronic Data Sheet (EDS) File Installation 380 Before the E300 Electronic Overload Relay EtherNet/IP Communication Module is configured to communicate on an EtherNet/IP network, it must be registered to the software that configures the network (for example, RockwellВ Automation RSLinx Classic and RSNetWorx for EtherNet/IP software). Register the module by installing an EDS file. The EDS file for the E300 Electronic Overload Relay EtherNet/IP Communication Module can be obtained from one of two locations: • Embedded in the module • The Allen-Bradley EDS file download website. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 Download the EDS File Embedded in the Module The EDS file for the E300 Electronic Overload Relay EtherNet/IP Communication Module is embedded within the module. Using RSLinx Classic, you can install the E300 Electronic Overload Relay EtherNet/IP Communication Module's EDS file from the RSLinx Classic RSWho screen using these steps: 1. Open RSLinx Classic and browse the EtherNet/IP network that has the E300 Electronic Overload Relay. It will be identified with a yellow question mark. Right click on the unrecognized device and select "Upload EDS File from Device". 2. Using the EDS Wizard, install the embedded E300 Electronic Overload Relay EtherNet/IP Communication Module EDS file. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 381 Chapter 9 EtherNet/IP Communications 3. When finished, RSLinx Classic will recognize the newly registered E300 Electronic Overload Relay EtherNet/IP Communication Module. From the EDS File Download Site The EDS file for the E300 Electronic Overload Relay EtherNet/IP Communication Module can also be downloaded from the Allen-Bradley EDS File download site. Using a web browser on the personal computer that is connected to the internet, you can download the EDS file by following these steps: 1. Type http://www.rockwellautomation.com/rockwellautomation/ support/networks/eds.page? on the address line of the web browser. 2. Select EtherNet/IP as the network type, enter 193 for the Bulletin Number, and click Search. 382 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 3. Locate the EDS file for the E300 Electronic Overload Relay EtherNet/IP Communication Module and download it to the personal computer. 4. Start the EDS Hardware Installation Tool located at Start>Programs>Rockwell Software>RSLinx Tools and Add a new device 5. Using the EDS Wizard, install the downloaded E300 Electronic Overload Relay EtherNet/IP Communication Module EDS file. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 383 Chapter 9 EtherNet/IP Communications 6. When finished, RSLinx Classic will recognize the newly registered E300 Electronic Overload Relay EtherNet/IP Communication Module. View and Configure Parameters The web server in the E300 Electronic Overload Relay EtherNet/IP Communication Module when enabled is able to view and configure parameters for the E300 Electronic Overload Relay. You can use the web interface to edit parameters for E300 Electronic Overload Relay if it is not being scanned by an EtherNet/IP scanner. Viewing Parameters Follow the steps below to view parameters using the web interface of the E300 Electronic Overload Relay EtherNet/IP Communication Module. 1. Using a web browser, open the web page of the E300 Electronic Overload Relay EtherNet/IP Communication Module by typing its IP address for the URL. 384 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 2. Navigate to the Parameters folder and select a parameter group. The example below shows the information from the Current Monitoring parameters. 3. To increase the update rate of the data being viewed, enter a faster update time in the refresh rate box shown below: 4. E300 Electronic Overload Relay EtherNet/IP Communication Module web page displays up to 17 parameters per web page. If more than 17 parameters exist for a parameter group, use the navigation arrows to display the other parameters. Editing Parameters Follow the steps below to edit configuration parameters using the web interface of the E300 Electronic Overload Relay EtherNet/IP Communication Module. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 385 Chapter 9 EtherNet/IP Communications 1. Select a parameter group that contains programmable parameters, then click the Edit button. The value options appears. 2. Click the down arrow on the pull-down boxes to adjust fixed values and/or enter numerical values in the fields without an arrow to adjust the values. 3. Click Apply once all parameter edits have been completed. The E300 Electronic Overload Relay EtherNet/IP Communication Module will download the new parameter values to the device. 386 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 4. A confirmation window appears. Press OK. NOTE: If you attempt to edit a configuration parameter when a Class 1 EtherNet/IP connection exists between an EtherNet/IP scanner and the E300 Electronic Overload Relay EtherNet/IP Communication Module, a message similar to the one shown below appears when the Apply button is pressed. Automation Controller Communications The E300 Electronic Overload Relay EtherNet/IP Communication Module supports two types of EtherNet/IP messaging. • I/O Messaging - Used for deterministic EtherNet/IP communications with ControlLogix, CompactLogix, SoftLogix, and EtherNet/IP scanners. Its primary use is to read and write I/O data for control purposes. • Explicit Messaging - Used for non-deterministic communications in which the data is not critical for control. Logic explicit messages have a lower priority compared to I/O messages and are used to read and write noncritical data. I/O Messaging RSLogix 5000в„ў and Studio 5000в„ў software is used to configure I/O messaging between an automation controller and the E300 Electronic Overload Relay EtherNet/IP Communication Module on an EtherNet/IP network. Shown below are two examples and the steps necessary to configure a Logix controller for I/O messaging. • Logix Configuration with Add-on Profile • Logix Configuration with a Generic Profile Rockwell Automation Publication 193-UM015C-EN-P - December 2014 387 Chapter 9 EtherNet/IP Communications Logix Configuration with Add-on Profile An Add-on Profile is available for the E300 Electronic Overload Relay EtherNet/ IP Communication Module and can be used with RSLogix 5000 version 17 and higher and Studio 5000 version 21 and higher. The profile can be downloaded from:пЂ http://compatibility.rockwellautomation.com/Pages/ MultiProductFindDownloads.aspx?crumb=112&refSoft=0&toggleState=&ver sions=50428 An existing project can be used or a new project can be created to configure EtherNet/IP I/O Messaging. After the controller configuration, the E300 Electronic Overload Relay EtherNet/IP Communication Module has to be added to the I/O configuration by following these steps: 1. Right-click on the EtherNet/IP scanner within the I/O Configuration folder, then select New Module to open the Select Module Type window. 2. Select the E300 Electronic Overload Relay EtherNet/IP Communication Module (193-ECM-ETR), then click Create. 388 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 3. Enter a name and the IP address for the E300 Electronic Overload Relay EtherNet/IP Communication Module. The name creates tags in RSLogix 5000 or Studio 5000 that can be used to read and write data from the E300 Electronic Overload Relay EtherNet/IP Communication Module. 4. Select Change to select the modules and accessories of the E300 Electronic Overload Relay system. 5. Select the specific E300 Electronic Overload Relay Sensing and Control Modules and their respective Option Match actions. 6. Right click on the Expansion Bus to add the specific Expansion Bus accessories for the E300 Electronic Overload Relay system and select their specific Option Match action. When finished, press OK. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 389 Chapter 9 EtherNet/IP Communications 7. Configure the E300 Electronic Overload Relay system's Operating Mode and associated relay output assignments. See Chapter 5 for more information about Operating Modes. 8. The E300 Electronic Overload Relay allows you to configure up to eightВ Datalinks. Select the parameters for the additional data to be included with the input tags. Press OK to complete the module definition. 9. Next, set the overload protection configuration parameters for your specific motor application by selecting Protection. 390 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 10. To configure the other parameters for a Control Module with firmware v3.000 or higher, navigate to the proper display and make the appropriate adjustments. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 391 Chapter 9 EtherNet/IP Communications 11. To configure the other configuration parameters for Control Modules with firmware v1.000 and v2.000, navigate to the configuration tags of the newly added E300 Electronic Overload Relay. Modify the configuration tags directly to enable and adjust the other current-, voltage-, power-, and control-based protection functions of the E300 Electronic Overload Relay. 12. When finished, press OK to complete the addition of the E300 Electronic Overload Relay to the Logix system. 13. Download the project to the Logix controller, and place the controller into Run Mode. The E300 Electronic Overload Relay is actively communicating with the Logix controller. 392 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 14. To access the data provided by the E300 Electronic Overload Relay EtherNet/IP Communication Module, navigate to input tags created by the Add-on Profile. 15. To control the output relays or remote reset the E300 Electronic Overload Relay navigate to the output tags created by the Add-on Profile. Logix Configuration with a Generic Profile An existing project can be used or a new project can be created to configure EtherNet/IP I/O Messaging. After the Logix controller has been configured, the E300 Electronic Overload Relay EtherNet/IP Communication Module must be added to the I/O configuration. Follow these steps when using a Generic Profile. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 393 Chapter 9 EtherNet/IP Communications 1. Right-click on the EtherNet/IP scanner within the I/O Configuration folder, then select New Module to open the Select Module Type window. 2. Select the Generic Ethernet Module, then click Create. 3. Enter a name and the IP address for the E300 Electronic Overload Relay EtherNet/IP Communication Module. The name creates tags in RSLogix 5000 or Studio 5000 that can be used to read and write data from the E300 Electronic Overload Relay EtherNet/IP Communication Module. 4. Select Data-DINT for the Comm Format. The Data-DINT format represents the data from the EtherNet/IP Communications Auxiliary E300 Electronic Overload Relay EtherNet/IP Communication Module as a collection of 32-bit values. Set the I/O Assemblies to the following values: • Input Assembly Instance 199 (Size 39) 394 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 • Output Assembly Instance 144 (Size 2) • Configuration Assembly Instance 120 (Size 0) 5. To access the data provided by the E300 Electronic Overload Relay EtherNet/IP Communication Module, navigate to input tags created by the Generic Profile. Table 498 represents the Input Assembly data. Table 498 - Instance 199 - Input (Produced) Assembly Bit INT DINT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 1 0 Reserved for Logix 2 3 DeviceStaus0 1 DeviceStaus1 4 5 InputStatus0 2 InputStatus1 6 7 OutputStatus 3 OpStationStatus 8 9 TripStsCurrent 4 WarnStsCurrent 10 11 TripStsVoltage 5 WarnStsVoltage 12 13 TripStsPower 6 WarnStsPower 14 15 TripStsControl 7 WarnStsControl 16 17 TripStsAnalog 8 WarnStsAnalog 18 19 20 9 Reserved ThermUtilizedPct 10 21 CurrentImbalance AvgPercentFLA 22 23 11 AverageCurrent Rockwell Automation Publication 193-UM015C-EN-P - December 2014 395 Chapter 9 EtherNet/IP Communications Bit INT DINT 15 14 13 12 11 10 9 8 7 6 24 25 12 L1Current 13 L2Current 14 L3Current 26 27 28 29 30 31 32 33 16 34 35 GFCurrent 15 17 Reserved AvgVoltageLtoL L1toL2Voltage L2toL3Voltage L3toL1Voltage 36 37 18 TotalRealPower 19 TotalReactivePwr 20 TotalApparentPwr 21 TotalPowerFactor 22 Datalink0 23 Datalink1 24 Datalink2 25 Datalink3 26 Datalink4 27 Datalink5 28 Datalink6 29 Datalink7 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 30 62 63 31 64 65 396 32 PtDeviceOuts AnDeviceOuts InAnMod1Ch00 InAnMod1Ch01 InAnMod1Ch02 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Reserved 5 4 3 2 1 0 EtherNet/IP Communications Chapter 9 Bit INT DINT 66 67 33 68 69 34 70 71 35 72 73 36 74 75 37 76 77 38 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 InAnMod2Ch00 InAnMod2Ch01 InAnMod2Ch02 Reserved InAnMod3Ch00 InAnMod3Ch01 InAnMod3Ch02 Reserved InAnMod4Ch00 InAnMod4Ch01 InAnMod4Ch02 Reserved For example, E300_Overload:I.Data[12] represents L1 Current as shown below. 6. To control the output relays or remotely reset the E300 Electronic Overload Relay, navigate to the output tags created by the Generic Profile. Table 499 represents the Input Assembly data. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 397 Chapter 9 EtherNet/IP Communications Table 499 - Instance 144 - Output (Consumed) Assembly Bit INT DINT 15 14 13 12 11 10 9 0 8 7 6 5 4 3 2 1 OutputStatus0 NetworkStart1 X NetworkStart2 X TripReset X EmergencyStart X RemoteTrip 1 0 X Reserved X X X X X 1 X X HMILED1Green HMILED3Green HMILED3Red X 2 X HMILED2Green X 3 HMILED4Red X Reserved DLXPtDeviceIn DLXAnDeviceIn For example, E300_Overload:O.Data[0].0 represents Relay Output Pt00 as shown below. E-mail/Text The E300 Electronic Overload Relay EtherNet/IP Communication Module is capable of sending e-mail messages and text notifications for different trip and warning events using a Simple Mail Transfer Protocol (SMTP) server. The subject and body contents in the e-mail message is created from the: • Type of trip or warning that is detected • Device name • Device description 398 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 • Device location • Contact information EXAMPLE E-mail Subject: E300 Overload Relay has detected a fault E-mail Body: Fault Status: Device Name: E300 Overload Relay Device Description: Motor Starters Device Location: Bay 6-U29 Contact Info: Contact Person [email protected] The first word in the e-mail subject is the device name. If a device name is not configured, then the product name attribute from the identity object is used. E-mail Configuration To be able to send an e-mail, the IP address of the host name of a Simple Mail Transfer Protocol (SMTP) server must be configured and notifications must be selected. Follow these steps to configure an e-mail notification. 1. In the web browser, enter the IP address of the E300 Electronic Overload Relay EtherNet/IP Communication Module URL of the web browser. 2. Select Administrative Settings>Device Identity 3. Type the Device Identity information into the fields as described below and press Apply. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 399 Chapter 9 EtherNet/IP Communications Device Name Device Description Device Location Contact Information The name of the E300 Electronic Overload Relay. The description of the E300 Electronic Overload Relay. The location of the E300 Electronic Overload Relay. The contact information for the E300 Electronic Overload Relay. 4. Select Administrative Settings>E-Mail Configuration 5. Type the information into the e-mail notification fields as stated below. Multiple e-mail addresses can be entered into the E-mail Recipient field by separating each e-mail address with a semicolon (;). The E-mail Recipient field is limited to 255 characters. E-mail Recipient E-Mail Sender SMTP Server SMTP Username SMTP Password SMTP Port The e-mail address of the person who will receive the notifications. The e-mail address from which the notification will be sent. Consult with the network administrator for the SMTP server address. Consult with the network administrator for the SMTP username. Consult with the network administrator for the SMTP password. Consult with the network administrator which SMTP port number to use. Port 25 is the most common SMTP port. 6. Check the desired notification time, fault conditions, and local conditions to be included in notification e-mails to the recipient. You can change these after the initial configurations. 400 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Communications Chapter 9 7. Click Apply to accept the configuration 8. When an E300 Electronic Overload Relay event occurs, the e-mail message will look like the following: Text Notifications The E300 Electronic Overload Relay EtherNet/IP Communication Module can send a text message to a wireless phone by e-mailing the wireless phone's service provider. The format for the text message is provided by the service provider and looks similar to the example formats below. • AT&Tв„ў: 10-digit wireless phone [email protected] • SprintВ®: 10-digit wireless phone [email protected] Limitations Based on the functionality of the E300 Electronic Overload Relay EtherNet/IP Communication Module, there are some limitations on when the e-mails can be triggered. • If two events occur at the same time, an e-mail is only sent for the most significant error. • If the device has been configured to send an e-mail for a lower prioritized event and this event occurs at the same time as a higher prioritized event for which the device has not been programmed to send an e-mail, an e-mail is not sent for either event. • The Clear e-mail is only sent when all events have been cleared and an event e-mail has previously been sent. Troubleshooting The following table identifies possible causes and corrective actions when troubleshooting the E300 Electronic Overload Relay EtherNet/IP Communication Module. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 401 Chapter 9 EtherNet/IP Communications Status LED Network Status (NS) Module Status Link1 or Link2 402 Color State None — Green, Red, Not Illuminated Flashing (once) Green Flashing Green Solid Red Flashing Red Solid None — Green, Red, Not Illuminated Flashing (once) Green Flashing Green Solid Red Flashing Red Solid None — Green Green Flashing Solid Possible Cause The E300 EtherNet/IP Communication Module is not receiving power. Normal Corrective Action Verify that the proper control voltage exists between terminals A1 and A2 on the E300 Control Module. This is a normal power-up sequence. The E300 EtherNet/IP Communication Module is online, but with no connections established. Normal operating state and the E300 EtherNet/IP Communication Module is allocated to a master. One or more EtherNet/IP connections timed out. Diagnostics test failed on power-up/reset. An internal fault exists. Duplicate EtherNet/IP module address exists. Two modules cannot have the same address. A fatal communication error occurred. The E300 EtherNet/IP Communication Module is not receiving power. Check the EtherNet/IP master and its scan list for correct scanner configuration. No action is required. Reset the EtherNet/IP master device. Cycle power to the unit. If the fault still exists, replace the unit. Change the IP address to a valid setting and reset the device. Check Ethernet media for proper installation. Check the control power connection on the A1 and A2 terminals of the E300 EtherNet/IP Control Module. Normal This is a normal power-up sequence. The E300 EtherNet/IP Communication Module is not being scanned by the EtherNet/IP master. Normal operating state, the E300 EtherNet/IP Communication Module is allocated to its master. One or more EtherNet/IP connections timed out. Check the Ethernet scan list for the correct scanner configuration. No action is required. Reset the E300 EtherNet/IP Communication Module. Reset the E300 EtherNet/IP Communication Module or The E300 Overload Relay is in a fault state. verify the validity of the data in the configuration assembly. Cycle power to the device. If the fault still exists, replace Diagnostics test failed on power-up/reset. the device. The E300 EtherNet/IP Communication Module is not Check the Ethernet cabling to make sure it is properly properly connected to an Ethernet network. installed. The Ethernet network is properly connected. No action is required. Communications are occurring on the Ethernet network. No action is required. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 10 Firmware Updates Introduction This chapter provides detailed information about firmware compatibility among the various E300 Electronic Overload Relay modules and provides instructions on how to update firmware for an E300 Electronic Overload Relay module. Firmware Compatibility The sensing, control, and communication modules of an E300 Electronic Overload Relay have their own firmware for the functionality of the module and its subsystems. Each module and its associated subsystems can be updated using the ControlFLASH utility, which is the same utility that is used to download firmware into a Logix-based controller. Table 500 shows the specific firmware revisions for all E300 Electronic Overload Relay modules and subsystems for the three system releases. Table 500 - E300 System Revision Table E300 Control Module E300 Communication Module E300 Sensing Module E300 System Revision 1.034 1.035 2.034 2.035 3.033 3.049 193-EIO Application 1.002 1.003 2.002 2.003 3.001 3.001 193-EIO Boot Code 1.005 1.005 1.006 1.006 1.007 1.007 193-EIO EDS Files — — — — 3.001 3.001 193-ECM-ETR Application 1.003 1.003 1.003 1.003 1.003 1.004 193-ECM-ETR Boot Code 2.001 2.001 2.001 2.001 2.001 2.001 193-ECM-ETR FPGA 1.008 1.008 1.008 1.008 1.008 1.008 193-ECM-ETR File System 1.001 1.001 1.001 1.001 1.001 1.002 193-ESM Sensing Module 1.001 1.001 2.002 2.002 2.002 2.002 Table 501 shows which firmware revisions are compatible with the other E300 Electronic Overload Relay modules and their associated subsystems. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 403 Chapter 10 Firmware Updates Table 501 - E300 Firmware Compatibility Table E300 Control Module E300 Communication Module 193-ECM-ETR Application 193-ECM-ETR File System 193-ECM-ETR File System 193-ECM-ETR File System 193-ECM-ETR Boot Code 193-ECM-ETR FPGA E300 Sensing Module 193-ESM Sensing Module 193-EXP-DIO-42-24D E300 Digital I/O Expansion Modules 193-EXP-DIO-42-120 193-EXP-DIO-42-240 E300 Analog I/O Expansion Module 193-EXP-AIO-31 193-EOS-SCS E300 Operator Stations 193-EOS-SDS Updating Firmware 404 193-EIO Application 193-EIO Boot Code 193-EIO EDS Files 1.003 1.001 1.004 1.002 2.001 1.008 1.001 2.002 — — — — — — 1.002 1.005 — вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ — вњ“ вњ“ вњ“ — вњ“ — 1.003 1.005 — вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ — вњ“ вњ“ вњ“ — вњ“ — 2.002 1.006 — вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ — вњ“ — 2.003 1.006 — вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ — вњ“ — 3.001 1.007 3.001 вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ вњ“ Firmware for the E300 Electronic Overload Relay modules and their associated subsystems can be downloaded from the Product Compatibility and Download Center located at http://www.rockwellautomation.com/rockwellautomation/ support/pcdc.page?. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 After the firmware has been downloaded and installed, run the ControlFLASH application by selecting ControlFLASH from the Start menu located at Start -> FLASH Programming Tools -> ControlFlash as shown below. Select the Local directory to locate the ControlFLASH update file and press Next to continue. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 405 Chapter 10 Firmware Updates Select the module update file and press Next. 406 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 Select the specific device to update and press OK. Select the specific module subsystem to update and press OK. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 407 Chapter 10 Firmware Updates Select the specific firmware revision for the firmware update and press Next. Verify that you want to update the firmware for that specific module subsystem by pressing Yes. 408 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 The ControlFLASH utility will begin to download the new firmware files. At the end of the download, the device will automatically reset. When the device finishes its power cycle sequence, a successful firmware update message is displayed. Press OK to finish the firmware update process. IMPORTANT Do not interrupt power or communications to the device during the firmware update process. Failure of control power or communications could permanently damage the device. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 409 Chapter 10 Firmware Updates E300 Firmware Update Example Updating the firmware for an E300 Electronic Overload Relay involves updating multiple internal firmware subsystems. The Communication Module, Control Module, and Sensing Module have their own firmware. This example explains the process to update an E300 Electronic Overload Relay from v2.034 to v3.033 firmware. Download the firmware update files fromпЂ http://compatibility.rockwellautomation.com/Pages/ MultiProductDownload.aspx?crumb=112. Table 502 contains the firmware files that are associated with v3.033. Table 502 - E300 Firmware v3.033 Files В E300 Communication Module E300 Sensing Module E300 Control Module E300 System Revision 3.033 193-ECM-ETR Application 1.003 193-ECM-ETR Boot Code 2.001 193-ECM-ETR FPGA 1.008 193-ECM-ETR File System 1.001 193-ESM Sensing Module 2.002 193-EIO Application 3.001 193-EIO Boot Code 1.007 193-EIO EDS Files 3.001 The firmware for the EtherNet/IP communication and sensing module did not change in the update for an E300 Electronic Overload Relay with firmware v2.034 to v3.033. No firmware update is needed for the E300 EtherNet/IP Communication Module and Sensing Module. However, five control module firmware subsystems changeed. Update the following control module firmware subsystems: • 193-EIO Boot Code • 193-EIO Application • 193-EIO Uncompressed EtherNet/IP EDS File • 193-EIO Compressed EtherNet/IP EDS File 410 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 • 193-EIO Compressed DeviceNet EDS File Control Module Boot Code Firmware Update 1. To update the firmware for the E300 Control Module Boot Code, start the ControlFlash Utility, select 193-EIO BootCode, and press Next. 2. Select the device to update and press OK. 3. Select the firmware subsystem type 193-EIO Boot Code to update and press OK. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 411 Chapter 10 Firmware Updates 4. Select firmware revision 1.007.1 to update to. 412 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 5. Verify the firmware revision change and press Finish. 6. Begin the firmware updating process by pressing Yes. When the firmware update is successful, the following display appears. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 413 Chapter 10 Firmware Updates Control Module Application Code Firmware Update 1. To update the firmware for the E300 Control Module Application Code, start the ControlFlash Utility, select 193-EIO Application, and press Next. 2. Select the device to update and press OK. 3. Select the firmware subsystem type 193-EIO Application to update and press OK. 414 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 4. Select firmware revision 3.001.12 to update to. 5. Verify the firmware revision change and press Finish. 6. Begin the firmware updating process by pressing Yes. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 415 Chapter 10 Firmware Updates When the firmware update is successful, the following display appears. Control Module Uncompressed EtherNet/IP EDS File Firmware Update 1. To update the embedded uncompressed EtherNet/IP EDS file, start the ControlFlash Utility, select 193-EIO Uncompressed EDS, and press Next. 416 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 2. Select the device to update and press OK. 3. Select the firmware subsystem type 193-EIO EDS Files to update and press OK. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 417 Chapter 10 Firmware Updates 4. Select the first firmware revision 3.001.1 to update to. 5. Verify the firmware revision change and press Finish. 6. Begin the firmware updating process by pressing Yes. 418 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 When the firmware update is successful, the following display appears. Control Module Compressed EtherNet/IP EDS File Firmware Update 1. To update the embedded compressed EtherNet/IP EDS file, start the ControlFlash Utility, select 193-EIO Compressed EDS, and press Next. 2. Select the device to update and press OK. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 419 Chapter 10 Firmware Updates 3. Select the firmware subsystem type 193-EIO EDS Files to update and press OK. 4. Select the second firmware revision 3.001.1 to update to. 5. Verify the firmware revision change and press Finish. 420 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 6. Begin the firmware updating process by pressing Yes. When the firmware update is successful, the following display appears. Control Module Compressed DeviceNet EDS File Firmware Update 1. To update the embedded compressed DeviceNet EDS file, start the ControlFlash Utility, select 193-EIO Compressed DNET EDS, and press Next. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 421 Chapter 10 Firmware Updates 2. Select the device to update and press OK. 3. Select the firmware subsystem type 193-EIO EDS Files to update and press OK. 422 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Firmware Updates Chapter 10 4. Select the third firmware revision 3.001.1 to update to. 5. Verify the firmware revision change and press Finish. 6. Begin the firmware updating process by pressing Yes. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 423 Chapter 10 Firmware Updates When the firmware update is successful, the following display appears. Completed Firmware Update When the E300 Electronic Overload Relay firmware is successfully updated from v2.034 to v3.033, the system information displays the information below. 424 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 11 Troubleshooting Introduction This chapter helps troubleshoot the E300 Electronic Overload Relay using its advisory LEDs and diagnostic parameters. ATTENTION: Servicing energized industrial control equipment can be hazardous. Electrical shock, burns, or unintentional actuation of controlled industrial equipment may cause death or serious injury. For safety of maintenance personnel and others who may be exposed to electrical hazards associated with the maintenance activities, follow the local safety-related work practices (for example, the NFPA 70E, Part II, Electrical Safety for Employee Workplaces, in the United States) when working on or near energized equipment. Maintenance personnel must be trained in the safety practices, procedures, and requirements that pertain to their respective job assignments. Do not work alone on energized equipment. ATTENTION: Do not attempt to defeat or override fault circuits. The cause of a fault indication must be determined and corrected before attempting operation. Failure to correct a control system or mechanical malfunction may result in personal injury and/or equipment damage due to uncontrolled machine system operation. Advisory LEDs All E300 Electronic Overload Relay Communication Modules and Operator Station have two diagnostic status indicators: Power LED and Trip/Warn LED. You can use these diagnostic status indicators to help identify the state of the E300 Electronic Overload Relay and the reason for the trip or warning event. Power LED The E300 Electronic Overload Relay Power LED identifies the state of the E300 Electronic Overload Relay system. Table 503 - Power LED Blinking Green Solid Green Device Ready / Operation Mode Device Active (Current Detected) / Run Mode Solid Red Device Error Blinking Red вћЉ Communications Error Blinking Green/Red вћЉ Copy Cat in Progress вћЉ Available on Operator Station Rockwell Automation Publication 193-UM015C-EN-P - December 2014 425 Chapter 11 Troubleshooting Trip/Warn LED The E300 Electronic Overload Relay Power LED identifies the reason for the trip or warning event. The E300 Electronic Overload Relay will display a long and short blinking pattern to identify the reason for the trip or warning event. Table 504 - Trip / Warn LED Blinking Red Blinking Yellow Trip Event Warning Event Listed below are the blink patterns for the E300 Electronic Overload Relay trip and warning events. Voltage Current Table 505 - Blink Patterns for Trip/Warn Events 426 Code Long Blink Pattern Short Blink Pattern Overload 0 1 Phase Loss 0 2 Ground Fault Current 0 3 Stall 0 4 Jam 0 5 Underload 0 6 Current Imbalance 0 7 L1 Under Current 0 8 L2 Under Current 0 9 L3 Under Current 0 10 L1 Over Current 0 11 L2 Over Current 0 12 L3 Over Current 0 13 L1 Line Loss 0 14 L2 Line Loss 0 15 L3 Line Loss 0 16 Under Voltage 1 1 Over Voltage 1 2 Voltage Imbalance 1 3 Phase Rotation Mismatch 1 4 Under Frequency 1 5 Over Frequency 1 6 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Troubleshooting Analog Control Power Code Long Blink Pattern Chapter 11 Short Blink Pattern Under kW 2 1 Over kW 2 2 Under kVAR Consumed 2 3 Over kVAR Consumed 2 4 Under kVAR Generated 2 5 Over kVAR Generated 2 6 Under kVA 2 7 Over kVA 2 8 Under PF Lagging 2 9 Over PF Lagging 2 10 Under PF Leading 2 11 Over PF Leading 2 12 Test 3 1 PTC 3 2 DeviceLogix 3 3 Operator Station 3 4 Remote Trip 3 5 Blocked Start 3 6 Hardware Fault 3 7 Configuration 3 8 Option Match 3 9 Feedback Timeout 3 10 Expansion Bus 3 11 Number Of Starts 3 12 Operating Hours 3 13 Nonvolatile Memory 3 14 Test Mode 3 15 Analog Module 1 - Input Channel 00 4 1 Analog Module 1 - Input Channel 01 4 2 Analog Module 1 - Input Channel 02 4 3 Analog Module 2 - Input Channel 00 4 4 Analog Module 2 - Input Channel 01 4 5 Analog Module 2 - Input Channel 02 4 6 Analog Module 3 - Input Channel 00 4 7 Analog Module 3 - Input Channel 01 4 8 Analog Module 3 - Input Channel 02 4 9 Analog Module 4 - Input Channel 00 4 10 Analog Module 4 - Input Channel 01 4 11 Analog Module 4 - Input Channel 02 4 12 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 427 Chapter 11 Troubleshooting Resetting a Trip ATTENTION: Resetting a trip does not correct the cause for the trip. Take corrective action before resetting the trip. The E300 Electronic Overload Relay trip condition can be reset by taking one of the following actions: • Actuating the Blue Trip/Reset button on the E300 Electronic Overload Relay Communication Module • Actuating the Reset button on the E300 Electronic Overload Relay Operator Station • Setting the Trip Reset bit in the E300 Electronic Overload Relay’s Output Assembly via the communications network • Actuating a reset signal to one of the assigned digital inputs • Setting Overload Reset Mode (Parameter 173) to “Automatic” to allow the unit to automatically reset after an overload trip • Setting Trip Reset (Parameter 163) to a value of 1, “Trip Reset” IMPORTANT Trip/Warn LED Troubleshooting Procedures An overload trip cannot be reset until the value of Percent Thermal Capacity Utilized (Parameter 1) is below the value set in Overload Reset Level (Parameter 174). Trip Description Possible Cause Test Trip 1. Operation of the Test/Reset 1. Motor overloaded Overload 2. Improper parameter settings 1. Missing supply phase 2. Poor electrical connection Phase Loss 3. Contactor operation 4. Improper parameter setting 1. Power conductor or motor winding is shorting to ground 2. Motor winding insulation is decayed Ground Fault 428 Corrective Action 1. Operate the Test/Reset button to clear 1. Check and correct source of overload (load, mechanical transmission components, motor bearings). 2. Set parameter values to match the motor and application requirements. 1. Check for open line (for example, blown fuse). 2. Check all power terminations from the branch circuit-protecting device down to the motor for proper tightness. Make sure that the overload connection to the contactor is secure. 3. Inspect contactor for proper operation. 4. Single-phase applications require that Single/ Three Phase (Parameter 176) is set to “single phase”. 1. Check power conductors and motor windings for low resistance to ground. 2. Check motor winding insulation for low resistance to ground. 3. Check for foreign objects. 3. Foreign Object short 4. External ground fault sensor (core balance current transformer) has improper 4. Check cable connections. connection Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Troubleshooting Trip Description Stall Possible Cause 1. Motor has not reached full speed by the end of the Stall Enabld Time (Parameter 249) 2. Improper parameter settings 1. Motor current has exceeded the programmed jam level Jam 2. Improper parameter settings PTC 1. Motor stator windings overheated 2. Thermistor leads short-circuited or broken 1. Imbalance in incoming power 2. Motor winding imbalance Current Imbalance 3. Motor idling 4. Contactor or circuit breaker operation 1. Firmware Downgrade corrupted: Nonvolatile Storage Nonvolatile memory Fault 2. Internal product failure 1. Firmware of sensing module is not compatible with control module firmware Hardware Fault 2. Hardware configuration failure 1. Single/Three Phase (Parameter 176) is set to "Single Phase" and current is being sensed in phase L3 during motor operation. Operating Mode "Overload (Network)" Configuration Fault 2. does not have an assigned Trip Relay 3. Illegal configuration value Remote Trip 1. Contact closure of remote sensor (for example, vibration switch). 1. Starts Counter (Parameter 29) is equal to Total Starts Warning or greater than the value set in Total Starts (Parameter 207) Operating Time (Parameter 28) is equal to Total Operating 1. greater than the value set in Total Hours Warning or Operating Hours (Parameter 208) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Chapter 11 Corrective Action 1. Check for source of stall (for example, excessive load, or mechanical transmission component failure). 2. Stall Enabled Time (Parameter 249) is set too low for the application. Check to make sure that FLA Setting (Parameter 171) is set correctly. 1. Check for the source of the jam (i.e., excessive load or mechanical transmission component failure). 2. Jam Trip Level (Parameter 253) is set too low for the application. Check to make sure that FLA Setting (Parameter 171) is set correctly. 1. Check for source of motor overtemperature (for example, overload, obstructed cooling, high ambient temperature, excessive starts/hour). 2. Inspect thermistor leads for short-circuit or open 1. Check power system (for example, blown fuse). 2. Repair motor, or if acceptable, raise value of Current Imbalance Trip Level (Parameter 261), CI Trip Level 3. Raise value of Current Imbalance Trip Level (Parameter 261) to an acceptable level. 4. Inspect contactor and circuit breaker for proper operation. 1.Execute the Clear Command to the operating Statistics, History Logs, and % TCU 2. Consult the factory. 1. Verify firmware revisions of control module and sensing module 2. Update firmware of control module to v2.0 or higher 3. Consult the factory. 4. Verify that the Sensing, Control, and Communication Module are connected properly. 5. Verify that connection pins between sensing module and control module are not bent. 1. For three-phase applications, Single/Three Phase (Parameter 176) should be set to “Three-Phase”; for single-phase applications, verify that current is flowing through L1 and L2 only. 2. Verify that one of the Output Assignments (Parameters 202…204) is configured as a "Trip Relay" 3. Review Invalid Configuration Parameter (Parameter 38) and Invalid Configuration Cause (Parameter 39) to identify which configuration parameter is illegal and the reason why. 1. Take corrective action to address the issue that caused the sensor to actuate. 2. Check sensor for proper operation. 3. Check wiring. 1. Set Clear Command (Parameter 165) to "Clear Operating Statistics" to reset Starts Counter (Parameter 29) 1. Clear Command (Parameter 165) to "Clear Operating Statistics" to reset Operating Time (Parameter 28) 429 Chapter 11 Troubleshooting Trip Description Blocked Start 430 Possible Cause 1. The number of starts count within the past hour period equals the value set in the Starts Per Hour (Parameter 205) 2. The time expired since the most recent start is less than the value set in the Starts Interval (Parameter 206) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Corrective Action 1. Check Time to Start (Parameter 31) and wait that amount of time, or change the configuration to allow more starts/hour. 2. Check Time to Start (Parameter 31) and wait that amount of time, or change the configuration to shorten the interval between starts. Appendix A Specifications Electrical Specifications Table 506 - Motor/Load Ratings Terminals Rated Insulation Voltage (Ui) Rated Operating Voltage (Ue) IEC: UL: Rated Impulse Voltage (Uimp) Rated Operating Current (Ie) Rated Frequency Short Circuit Ratings Number of Poles Application 1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3 690V AC 690V AC 600V AC 6 kV See Catalog Number Explanation 45...65 Hz See Short-Circuit Ratings on page 44 3 Single-phase or Three-phase Table 507 - Power Supply Ratings Rated Supply Voltage (Us) Operating Range Maximum Inrush Current Maximum Power Consumption E300: E300 with expansion: Maximum Power Interruption Time Vmin: Vmax: 24V DC 11…30V DC 3 A for 30 ms 120V AC 85…132V AC 10 A for 1 ms 240V AC 159…265V AC 8 A for 3 ms 6W 8W 5 ms 5 ms 10 ms 10 ms 10 ms 10 ms Table 508 - Output Relay Ratings (Control Module and Expansion Digital Module) Terminals Relay 0: Relay 1: Relay 2: Type of Contacts Rated Thermal Current (Ithe) Rated Insulation Voltage (Ui) Rated Operating Voltage (Ue) Rated Operating Current (Ie) Minimum Operating Current Rating Designation Utilization Category Resistive Load Rating (p.f. = 1.0) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 R03/R04 R13/R14 R23/R24 Form A SPST - NO 5A 300V AC 250V AC 3 A (@120V AC), 1.5 A (@240V AC) 0.25 A (@110V DC), 0.1 A (@220V DC) 10 mA @ 5V DC B300 AC-15 5 A, 250V AC 5 A, 30V DC 431 Appendix A Specifications Table 508 - Output Relay Ratings (Control Module and Expansion Digital Module) Inductive Load Rating (L/R = 7 ms) Short Circuit Current Rating (p.f. = 0.4) 2 A, 250V AC 2 A, 30V DC 1,000 A KTK-R-6 (6 A, 600 V) Recommended Control Circuit Fuse Rated Number of Operations Relay 0, Relay 1, and Relay 2: W/100-C09…100-C43 W/100-C60…100-C85 W/NEMA Size 0…2 W/NEMA Size 3 5,000,000 2,500,000 1,000,000 300,000 Table 509 - Input Ratings (Control Module and Expansion Digital Module) Terminals Input 0: Input 1: Input 2: Input 3: Input 4: Input 5: Supply Voltage Type of Inputs On-State Voltage On-State Current (turn-on) Off-State Voltage Off-State Current Transition Voltage Transition Current 24V DC 11V DC 2 mA 5V DC 1.5 mA 5...11V DC 1.5...2.0 mA IN0 IN1 IN2 IN3 IN4 IN5 120V AC Current Sinking 74V AC 5 mA 20V AC 2.5 mA 20…74V AC 2.5…5 mA 240V AC 159V AC 5 mA 40V AC 2.5 mA 40…159V AC 2.5…5 mA Table 510 - Analog I/O Ratings (Expansion Analog Module) Bus to In/Out isolation Group Isolation (In/Out) Channel to channel isolation Max. current draw Max. Surge Current at Power-Up Input ranges Input Impedance Tolerances Input resolution 432 Module 1000V AC = 1415V DC (1 min.) 1000V AC = 1415V DC (1 min.) None 85 mA at 24V 0.5 A @ 24V DC for 1 ms Input Channels Current: 0…20 mA, 4…20 mA Voltage: 0…10V, 1…5V, 0…5V RTD: 100 пЃ—, 200 пЃ—, 500 пЃ—пЂ and 1000 пЃ—пЂ PT385 and Pt3916, 100 пЃ—пЂ Ni618 and Ni672, 10 пЃ—пЂ Cu 426, 604 пЃ—пЂ NiFe 518 Resistance: 0-150 пЃ—, 0-750 пЃ—, 0-3000 пЃ—, 0-6000 пЃ— Current Impedance: 249 пЃ— В± 1.0% Voltage Impedance: 10M at 10Vin 4M at 5Vin 680k at 1Vin 12 bits Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Specifications Appendix A Table 510 - Analog I/O Ratings (Expansion Analog Module) Output ranges Output Resolution Voltage Output Load Current Output Load Output Impedance Output Open Circuit detect Output Channels Current: 0…20 mA, 4…20 mA Voltage: 0…10V, 0…5V, 1…5V 12 bits 2k пЃ— min. at 10V output (5 mA max.), including wire resistance 50 пЃ—minimum to 750 пЃ— max Current: >1MпЃ—, Voltage: <1 пЃ— Current outputs: O.C. detect supported Voltage outputs: O.C. detect not supported Max Inductive Load (current outputs) Max Capacitive Load (voltage outputs) 0.1 mH 1пЃ­F Table 511 - Thermistor/PTC Input Ratings (PTC only) Terminals Type of Control Unit Maximum Number of Sensors Maximum Cold Resistance of PTC Sensor Chain Trip Resistance Reset Resistance Short-circuit Trip Resistance Maximum Voltage @ PTC Terminals (RPTC = 4 kпЃ—) Maximum Voltage @ PTC Terminals (RPTC =open) Response Time Low Voltage Directive IT1, IT2 Mark A 6 1500 пЃ— 3400 пЃ—пЂ В± 150 пЃ— 1600 пЃ—пЂ В± 100 пЃ— 25 пЃ—пЂ В± 10 пЃ— 7.5V DC 30V DC 800 ms The E300 Electronic Overload Relay expansion digital modules are tested to comply with EN60947-5-1 Low-voltage switchgear and controlgear Part 5-1: Control circuit devices and switching elements. Table 512 - Expansion Digital I/O Modules Expansion Digital I/O Modules 193-EXP-DIO-42-24D 193-EXP-DIO-42-120 193-EXP-DIO-42-240 250V AC 250V AC 250V AC Digital Output Rated Operational Voltage (Ue): 2000Vrms for 1s 2000Vrms for 1s 2000Vrms for 1s Digital Output Rated Insulation Voltage (Ui): Rated Impulse Withstand Voltage (Uimp): N/A N/A N/A Conditional Short Circuit Current: 1000 A 1000 A 1000 A Recommended Control Circuit Fuse: KTK-R (6 A, 600V) KTK-R (6 A, 600V) KTK-R (6 A, 600V) Utilization Category: AC15, DC13 AC15, DC13 AC15, DC13 Pollution Degree: 3 3 3 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 433 Appendix A Specifications Table 513 - Expansion Power Supply Modules Expansion Power Supply Modules Rated Operational Voltage (Ue): Rated Insulation Voltage (Ui): Rated Impulse Withstand Voltage (Uimp): Conditional Short Circuit Current: Protection Against Short Circuits: Utilization Category: Pollution Degree: 193-EXP-PS-AC 100…250V AC 2640Vrms for 1s 4 kV N/A N/A N/A 3 Environmental Specifications Table 514 - Environmental Specifications Ambient Temperature Storage Operating (Open) (Enclosed) –40…+85 п‚°C (–40…+185 п‚°F) –20…+55 п‚°C (–4…+131 п‚°F)вћ‹вћЊ –20…+40 п‚°C (–4…+104 п‚°F)вћЊвћЌ Humidity Operating Damp Heat – Steady State (per IEC 68-2-3) Damp Heat – Cyclic (per IEC 68-2-30) 5…95% Non-condensing 92% r.h., 40 п‚°C (104 п‚°F), 56 days 93% r.h., 25 п‚°C/40 п‚°C (77 п‚°F/104 п‚°F), 21 Cycles Natural Convection 2.5G operating, 5 G non-operating 30 G 2000 m вћЉ Pollution Degree 3 EN 50012 IP20 Cooling Method Vibration (per IEC 68-2-6) Shock (per IEC 68-2-27) Maximum Altitude Pollution Environment Terminal Marking Degree of Protection вћЉ Current ratings must be derated at altitudes greater than 2000 m вћ‹ Temperature rating based on 120V AC control module with 1 A going through relays 0, 1, and 2. вћЊ Temperature rating based on 240V DC control module with four digital inputs active and 0.2 A going through relays 0, 1, and 2. вћЌ Temperature rating based on 120V AC or 240V AC control module with 5A going through relays 0, 1, and 2. NOTE: The E300 Electronic Overload Relay expansion power supplies (Cat. Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding air temperature must not exceed 55 В°C (131 В°F). Table 515 - Temperature Derating Control Module Voltage 120/240V AC Open Application 24V DC 120/240V AC Enclosed Application 434 24V DC Relay 0 Current Relay 1 Current Relay 2 Current 1.0 A 5.0 A 0.2 A 0.2 A 5.0 A 5.0 A 0.2 A 5.0 A 1.0 A 1.0 A 0.2 A 0.2 A 1.0 A 5.0 A 0.2 A 1.0 A 1.0 A 1.0 A 0.2 A 0.2 A 1.0 A 5.0 A 0.2 A 1.0 A Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Number of Digital Inputs Active 4 4 4 6 6 4 4 6 Operating Temperature Range -20…+55 В°C (-4…+131 В°F) -20…+50 В°C (-4…+122 В°F) -20…+55 В°C (-4…+131 В°F) -20…+50 В°C (-4…+122 В°F) -20…+30 В°C (-4…+86 В°F) -20…+40 В°C (-4…+104 В°F) -20…+40 В°C (-4…+104 В°F) -20…+30 В°C (-4…+86 В°F) Specifications Appendix A Electromagnetic Compatibility Specifications Table 516 - Electromagnetic Compatibility Specifications Electrostatic Discharge Immunity Test Level: Performance Criteria: RF Immunity Test Level: Performance Criteria: Electrical Fast Transient/Burst Immunity Test Level: Performance Criteria: Surge Immunity Test Level: Performance Criteria: Radiated Emissions Conducted Emissions 8kV Air Discharge 6kV Contact Discharge 1 вћЉвћ‹ 10V/m 1 вћЉвћ‹ 4kV (Power) 2kV (Control and Comm) 1 вћЉвћ‹ 2kV (L-E) 1kV (L-L) 1 вћЉвћ‹ Class A Class A вћЉPerformance Criteria 1 requires the DUT to experience no degradation or loss of performance. вћ‹Environment 2. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 435 Appendix A Specifications Protection Table 517 - Protection Trip Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Overload Phase Loss Ground Fault Stall Jam Underload Thermistor (PTC) Current Imbalance Communication Fault Communication Idle Remote Trip Blocked Start/Start Inhibit Under Voltage L-L Over Voltage L-L Voltage Unbalance Phase Rotation Under Frequency Over Frequency Under Real Power (kW) Over Real Power (kW) Under Reactive Power Consumed (+kVAR) Over Reactive Power Consumed (+kVAR) Under Reactive Power Generated (-kVAR) Over Reactive Power Generated (-kVAR) Under Apparent Power (kVA) Over Apparent Power (kVA) Under Power Factor Lagging (-PF) Over Power Factor Lagging (-PF) Under Power Factor Leading (+PF) Over Power Factor Leading (+PF) Power Value Overflow (kW, kVAR or KVA) Analog Over Level Warning Yes No Yes No Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Table 518 - Overload Protection 436 Type of Relay Ambient Compensated Time-Delay Phase Loss Sensitive Nature of Relay Solid-State FLA Setting See Full Load Amps Setting on page 133 Trip Rating 120% FLA Trip Class 5…30 Reset Mode Automatic or Manual Overload Reset Level 1…100% TCU Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Specifications Appendix A Table 519 - Ground Fault Protection (External Ground Fault Module) Type Core Balanced Intended Use Equipment Protection Classification (Per UL 1053) Class I 20…100 mA 100…500 mA Protection Range 200 mA…1.0 A 1.0…5.0 A Accuracy Trip and Warning Time Delay 0.1…25.0 s Protection Inhibit Time 0…250 s Metering The E300 Electronic Overload Relay metering accuracy is listed below: Table 520 - Metering Accuracy Current В±2% of Sensing Module Current Range Voltage В±2% of Sensing Module Voltage Range Power В±5% Protection Timers All E300 Electronic Overload Relay trip timers shall have a resolution of В±0.1 s or 0.1 s/25 s (whichever is greater). Rockwell Automation Publication 193-UM015C-EN-P - December 2014 437 Appendix A Specifications Notes: 438 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Appendix B Parameter List This appendix lists all accessible parameters of the E300в„ў overload relay in numerical order. Overview The setting range for each parameter is provided to assist especially for applications where it is desirable to set values from a logic controller via a network connection. Information values provided include the following: Value Group Device Monitor Param No. Parameter Name 1 ThermUtilizedPct 2 OLTimeToTrip 3 Function Setting Range Indicated as raw numerical values. Scale Factor Indicate the decimal precision associated with each parameter. This must be given close attention when writing or reading values. Default Indicate the factory pre-programmed values. Device Profile Tag Name I.PercentTCU OLTimeToReset Description Type Data Size (bytes) Scale Factor Min Max Default Units % Thermal Capacity Used USINT 1 1 0 100 0 Time until an overload trip UINT 2 1 0 9999 0 Time until OL trip can be reset UINT % Second s 2 1 0 9999 0 Second s 4 TripStsCurrent I.Protection.OverloadTrip I.Protection.PhaseLossTrip I.Protection.GroundFaultCurrentTrip I.Protection.StallTrip I.Protection.JamTrip I.Protection.UnderloadTrip I.Protection.CurrentImbalanceTrip I.Protection.L1UnderCurrentTrip I.Protection.L2UnderCurrentTrip I.Protection.L3UnderCurrentTrip I.Protection.L1OverCurrentTrip I.Protection.L2OverCurrentTrip I.Protection.L3OverCurrentTrip I.Protection.L1LineLossTrip I.Protection.L2LineLossTrip I.Protection.L3LineLossTrip Trip Status bits for UINT Current 2 1 Bit0= OverloadTrip Bit1= PhaseLossTrip Bit2= GroundFaultTrip Bit3= StallTrip Bit4= JamTrip Bit5= UnderloadTrip Bit6= CurrentImbalTrip Bit7= L1UnderCurrTrip Bit8= L2UnderCurrTrip Bit9= L3UnderCurrTrip Bit10= L1OverCurrenTrip Bit11= L2OverCurrenTrip Bit12= L3OverCurrenTrip Bit13= L1LineLossTrip Bit14= L2LineLossTrip Bit15= L3LineLossTrip 0 5 TripStsVoltage I.Protection.UnderVoltageTrip I.Protection.OverVoltageTrip I.Protection.VoltageImbalanceTrip I.Protection.PhaseRotationMismatchTrip I.Protection.UnderFrequencyTrip I.Protection.OverFrequencyTrip Trip Status bits for UINT Voltage 2 1 Bit0= UnderVoltageTrip Bit1= OvervoltageTrip Bit2= VoltageUnbalTrip Bit3= PhaseRotationTrp Bit4= UnderFreqTrip Bit5= OverFreqTrip 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 439 Appendix B Group Device Monitor (continued) Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Max Default Units 6 TripStsPower I.Protection.UnderRealPowerTrip I.Protection.OverRealPowerTrip I.Protection.UnderReactivePowerConsumedTrip I.Protection.OverReactivePowerConsumedTrip I.Protection.UnderReactivePowerGeneratedTrip I.Protection.OverReactivePowerGeneratedTrip I.Protection.UnderApparentPowerTrip I.Protection.OverApparentPowerTrip I.Protection.UnderPowerFactorLaggingTrip I.Protection.OverPowerFactorLaggingTrip I.Protection.UnderPowerFactorLeadingTrip I.Protection.OverPowerFactorLeadingTrip Trip Status bits for UINT Power 2 1 Bit0= UnderKWTrip Bit1= OverKWTrip Bit2= UnderKVARConTrip Bit3= OverKVARConTrip Bit4= UnderKVARGenTrip Bit5= OverKVARGenTrip Bit6= UnderKVATrip Bit7= OverKVATrip Bit8= UnderPFLagTrip Bit9= OverPFLagTrip Bit10= UnderPFLeadTrip Bit11= OverPFLeadTrip 0 7 TripStsControl I.Protection.TestTrip I.Protection.PTCTrip Trip Status bits for UINT Control 2 1 Bit0= TestTrip Bit1= PTCTrip Bit2= DLXTrip Bit3= OperStationTrip Bit4= RemoteTrip Bit5= BlockedStartTrip Bit6= HardwareFltTrip Bit7= ConfigTrip Bit8= OptionMatchTrip Bit9= DLXFBTimeoutTrip Bit10= ExpansionBusTrip Bit11= Reserved Bit12 =Reserved Bit13= NVSTrip Bit 14=TestMode Trip 0 I.Protection.Analog1Ch00Trip I.Protection.Analog1Ch01Trip I.Protection.Analog1Ch02Trip I.Protection.Analog2Ch00Trip I.Protection.Analog2Ch01Trip I.Protection.Analog2Ch02Trip I.Protection.Analog3Ch00Trip I.Protection.Analog3Ch01Trip I.Protection.Analog3Ch02Trip I.Protection.Analog4Ch00Trip I.Protection.Analog4Ch01Trip I.Protection.Analog4Ch02Trip Trip Status bits for UINT Analog 2 1 Bit0= InAnMod1Ch00Trip Bit1= InAnMod1Ch01Trip Bit2= InAnMod1Ch02Trip Bit3= InAnMod2Ch00Trip Bit4= InAnMod2Ch01Trip Bit5= InAnMod2Ch01Trip Bit6= InAnMod3Ch00Trip Bit7= InAnMod3Ch01Trip Bit8= InAnMod3Ch02Trip Bit9= InAnMod4Ch00Trip Bit10= InAnMod4Ch01Trip Bit11= InAnMod4Ch02Trip 0 I.Protection.OverloadWarning Warning Status bits for Current UINT 2 1 Bit0= OverloadWarning Bit1= Reserved Bit2= GroundFltWarning Bit3= Reserved Bit4= JamWarning Bit5= UnderloadWarning Bit6= CurrentImbalWarn Bit7= L1UnderCurrWarn Bit8= L2UnderCurrWarn Bit9= L3UnderCurrWarn Bit10= L1OverCurrenWarn Bit11= L2OverCurrenWarn Bit12= L3OverCurrenWarn Bit13= L1LineLossWarn Bit14= L2LineLossWarn Bit15= L3LineLossWarn 0 I.Protection.OperatorStationTrip I.Protection.RemoteTrip I.Protection.BlockedStartTrip I.Protection.HardwareFaultTrip I.Protection.ConfigurationTrip I.Protection.ModuleMismatchTrip I.Protection.ExpansionBusTrip I.Protection.NVMErrorTrip I.Protection.MCCTestPositionTrip 8 TripStsAnalog 9 Reserved 10 WarnStsCurrent I.Protection.GroundFaultCurrentWarning I.Protection.JamWarning I.Protection.UnderloadWarning I.Protection.CurrentImbalanceWarning I.Protection.L1UnderCurrentWarning I.Protection.L2UnderCurrentWarning I.Protection.L3UnderCurrentWarning I.Protection.L1OverCurrentWarning I.Protection.L2OverCurrentWarning I.Protection.L3OverCurrentWarning I.Protection.L1LineLossWarning I.Protection.L2LineLossWarning I.Protection.L3LineLossWarning 440 Min 11 WarnStsVoltage I.Protection.UnderVoltageWarning I.Protection.OverVoltageWarning I.Protection.VoltageImbalanceWarning I.Protection.PhaseRotationMismatchWarning I.Protection.UnderFrequencyWarning I.Protection.OverFrequencyWarning Warning Status bits for Voltage UINT 2 1 Bit0= UnderVoltageWarn Bit1= OvervoltageWarn Bit2= VoltageUnbalWarn Bit3= PhaseRotationWrn Bit4= UnderFreqWarning Bit5= OverFreqWarning 0 12 WarnStsPower I.Protection.UnderRealPowerWarning I.Protection.OverRealPowerWarning I.Protection.UnderReactivePowerConsumedWarning I.Protection.OverReactivePowerConsumedWarning I.Protection.UnderReactivePowerGeneratedWarning I.Protection.OverReactivePowerGeneratedWarning I.Protection.UnderApparentPowerWarning I.Protection.OverApparentPowerWarning I.Protection.UnderPowerFactorLaggingWarning I.Protection.OverPowerFactorLaggingWarning I.Protection.UnderPowerFactorLeadingWarning I.Protection.OverPowerFactorLeadingWarning Warning Status bits for Power UINT 2 1 Bit0= UnderKWWarning Bit1= OverKWWarning Bit2= UnderKVARConWarn Bit3= OverKVARConWarn Bit4= UnderKVARGenWarn Bit5= OverKVARGenWarn Bit6= UnderKVAWarning Bit7= OverKVAWarning Bit8= UnderPFLagWarn Bit9= OverPFLagWarn Bit10= UnderPFLeadWarn Bit11= OverPFLeadWarn 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Device Monitor (continued) Param No. 13 Parameter Name Device Profile Tag Name WarnStsControl Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units Warning Status bits for Control UINT 2 1 BBit0= Reserved Bit1= PTCWarning Bit2= DLXWarning Bit3= Reserved Bit4= Reserved Bit5= Reserved Bit6= Reserved Bit7= Reserved Bit8= OptionMatchWarn Bit9= DLXFBTimeoutWarn Bit10= ExpansionBusWarn Bit11= PMNumberOfStarts Bit12= PMOperatingHours I.Protection.Analog1Ch00Warning I.Protection.Analog1Ch01Warning I.Protection.Analog1Ch02Warning I.Protection.Analog2Ch00Warning I.Protection.Analog2Ch01Warning I.Protection.Analog2Ch02Warning I.Protection.Analog3Ch00Warning I.Protection.Analog3Ch01Warning I.Protection.Analog3Ch02Warning I.Protection.Analog4Ch00Warning I.Protection.Analog4Ch01Warning I.Protection.Analog4Ch02Warning Warning Status bits for Analog UINT 2 1 Bit0= InAnMod1Ch00Warn 0 Bit1= InAnMod1Ch01Warn Bit2= InAnMod1Ch02Warn Bit3= InAnMod2Ch00Warn Bit4= InAnMod2Ch01Warn Bit5= InAnMod2Ch02Warn Bit6= InAnMod3Ch00Warn Bit7= InAnMod3Ch01Warn Bit8= InAnMod3Ch02Warn Bit9= InAnMod4Ch00Warn Bit10= InAnMod4Ch01Warn Bit11= InAnMod4Ch02Warn I.Protection.PTCWarning I.Protection.ModuleMismatchWarning I.Protection.ExpansionBusWarning I.Protection.NumberOfStartsWarning I.Protection.OperatingHoursWarning 0 14 WarnStsAnalog 15 Reserved 16 InputStatus0 I.Pt00Data I.Pt01Data I.Pt02Data I.Pt03Data I.Pt04Data I.Pt05Data Status of Digital Inputs UINT 2 1 Bit0= InputPt00 Bit1= InputPt01 Bit2= InputPt02 Bit3= InputPt03 Bit4= InputPt04 Bit5= InputPt05 0 17 InputStatus1 I.Digital1Pt00Data I.Digital1Pt01Data I.Digital1Pt02Data I.Digital1Pt03Data I.Digital2Pt00Data I.Digital2Pt01Data I.Digital2Pt02Data I.Digital2Pt03Data I.Digital3Pt00Data I.Digital3Pt01Data I.Digital3Pt02Data I.Digital3Pt03Data I.Digital4Pt00Data I.Digital4Pt01Data I.Digital4Pt02Data I.Digital4Pt03Data Status of Digital UINT Expansion Module Inputs 2 1 Bit0= InputDigMod1Pt00 Bit1= InputDigMod1Pt01 Bit2= InputDigMod1Pt02 Bit3= InputDigMod1Pt03 Bit4= InputDigMod2Pt00 Bit5= InputDigMod2Pt01 Bit6= InputDigMod2Pt02 Bit7=1nputDigMod2Pt03 Bit8= InputDigMod3Pt00 Bit9= InputDigMod3Pt01 Bit10= InputDigMod3Pt02 Bit11= InputDigMod3Pt03 Bit12= InputDigMod4Pt00 Bit13= InputDigMod4Pt01 Bit14= InputDigMod4Pt02 Bit15= InputDigMod4Pt03 0 18 OutputStatus I.Pt00Readback I.Pt01Readback I.Pt02Readback I.Digital1Pt00Readback I.Digital1Pt01Readback I.Digital2Pt00Readback I.Digital2Pt01Readback I.Digital3Pt00Readback I.Digital3Pt01Readback I.Digital4Pt00Readback I.Digital4Pt01Readback Status of Digital Outputs UINT 2 1 Bit0= OutputPt00 Bit1= OutputPt01 Bit2= OutputPt02 Bit3= OutDigMod1Pt00 Bit4= OutDigMod1Pt01 Bit5= OutDigMod2Pt00 Bit6= OutDigMod2Pt01 Bit7= OutDigMod3Pt00 Bit8= OutDigMod3Pt01 Bit9= OutDigMod4Pt00 Bit10= OutDigMod4Pt01 0 19 OpStationStatus I.OperatorStationI I.OperatorStationII I.OperatorStationLocalRemote I.OperatorStationO I.OperatorStationReset Status of Operator UINT Station Buttons and LEDs 2 1 Bit0= OpStationStart1 Bit1= OpStationStart2 Bit2= OSLocalRemote Bit3= OpStationStop Bit4= OpStationReset Bit5= Reserved Bit6= Reserved Bit7= Reserved Bit8= OSLED1Green Bit9= OSLED2Green Bit10= OSLED3Amber Bit11= OSLED3Red Bit12= OSLED4Red 0 I.OperatorStationILEDReadback I.OperatorStationIILEDReadback I.OperatorStationLocalLEDReadback I.OperatorStationRemoteLEDReadback I.OperatorStationOLEDReadback Rockwell Automation Publication 193-UM015C-EN-P - December 2014 441 Appendix B Group Device Monitor (continued) 442 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 20 DeviceStatus0 I.TripPresent I.WarningPresent I.InvalidConfiguration I.MotorCurrentPresent I.GroundFaultCurrentPresent I.MotorVoltagePresent I.EmergencyStartEnabled I.DeviceLogixEnabled I.FeedbackTimeoutEnabled I.OperatorStationPresent I.VoltageSensingPresent I.InternalGroundFaultSensingPresent I.ExternalGroundFaultSensingPresent I.PTCSensingPresent I.Ready Device Status bits UINT 2 1 Bit0= TripPresent Bit1= WarningPresent Bit2= InvalidConfig Bit3= CurrentPresent Bit4= GFCurrentPresent Bit5= VoltagePresent Bit6= EmergencyStartEn Bit7= DeviceLogixEn Bit8= FeebckTimeoutEn Bit9= OperatorStation Bit10= VoltageSensing Bit11= InternGFSensing Bit12= ExternGFSensing Bit13= PTCSensing Bit14= Ready Bit 15=Admin Mode Active 0 21 DeviceStatus1 I.ContolModule24VDCPresent I.ControlModule120VACPresent I.ControlModule240VACPresent I.SensingModule30APresent I.SensingModule60APresent I.SensingModule100APresent I.SensingModule200APresent I.DigitalModule1Present I.DigitalModule2Present I.DigitalModule3Present I.DigitalModule4Present I.AnalogModule1Present I.AnalogModule2Present I.AnalogModule3Present I.AnalogModule4Present Device Status bits UINT 2 1 Bit0= 24VoltControl Bit1= 120VoltControl Bit2= 240VoltControl Bit3= CurrentSense30A Bit4= CurrentSense60A Bit5= CurrentSense100A Bit6= CurrentSense200A Bit7= DigitalModule1 Bit8= DigitalModule2 Bit9= DigitalModule3 Bit10= DigitalModule4 Bit11= AnalogModule1 Bit12= AnalogModule2 Bit13= AnalogModule3 Bit14= AnalogModule4 0 22 Firmware Firmware Revision UINT Number 2 1000 0 1001 23 ControlModuleID Control Module Type Detected USINT 1 1 0= Unknown 1= 6In3Out24VDC 2= 4In3Out120VAC 3= 4In3Out240VAC 4= 4In2OutGFPTC24V 5= 2In2OutGFPTC120V 6= 2In2OutGFPTC240V 0 24 SensingModuleID Sensing Module Types Detected USINT 1 1 0= Unknown 1= VIGPt5to30Amp 2= VIG6to60Amp 3= VIG10to100Amp 4= VIG20to200Amp 5= IGPt5to30Amp 6= IG6to60Amp 7= IG10to100Amp 8= IG20to200Amp 9= IPt5to30Amp 10= I6to60Amp 11= I10to100Amp 12= I20to200Amp 0 25 OperStationID Operator Station Types Detected USINT 1 1 0= Unknown 1= NoStation 2= ControlStation 3= DiagStation 0 26 DigitalModuleID Expansion Digital Module Types Detected UINT 2 1 Bit0= DigitalMod1[0] Bit1= DigitalMod1[1] Bit2= DigitalMod1[2] Bit3= DigitalMod2[0] Bit4= DigitalMod2[1] Bit5= DigitalMod2[2] Bit6= DigitalMod3[0] Bit7= DigitalMod3[1] Bit8= DigitalMod3[2] Bit9= DigitalMod4[0] Bit10= DigitalMod4[1] Bit11= DigitalMod4[2] 0 27 AnalogModuleID Expansion Bus Analog Module Types UINT 2 1 Bit0= AnalogMod1[0] Bit1= AnalogMod1[1] Bit2= AnalogMod2[0] Bit3= AnalogMod2[1] Bit4= AnalogMod3[0] Bit5= AnalogMod3[1] Bit6= AnalogMod4[0] Bit7= AnalogMod4[1] 0 28 OperatingTime Time unit has been UINT powered on 2 1 0 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 65535 65535 Hrs Parameter List Group Device Monitor (continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 29 StartsCounter Number of starts UINT 2 1 0 65535 0 30 Starts Available Number of Starts Available USINT 1 1 0 120 0 31 TimeToStart The Time to Start UINT 2 1 0 3600 0 Second s Current Monitor Voltage Monitor 32 Year Virtual RTC Year UINT 2 1 0 9999 0 33 Month Virtual RTC Month UINT 2 1 0 12 0 34 Day Virtual RTC Day UINT 2 1 0 31 0 35 Hour Virtual RTC Hour UINT 2 1 0 23 0 36 Minute Virtual RTC Minute UINT 2 1 0 59 0 37 Second Virtual RTC Second UINT 2 1 0 59 0 38 InvaldCfgParam Number of incorrectly configured parameter 2 1 0 9999 0 39 InvaldCfgCause Description of error USINT 1 1 0=NoError 1=ValueOverMax 2=Value UnderMin 3=IllegalValue 4=L3CurrentDetected 5=CopyCat Error 6-50 = Reserved 40 Reserved 41 Reserved UINT 0 42 Reserved 43 L1Current I.L1Current The actual L1 Phase Current. DINT 4 100 0 2000000000 0 Amps 44 L2Current I.L2Current The actual L2 Phase Current. DINT 4 100 0 2000000000 0 Amps 45 L3Current I.L3Current The actual L3 Phase Current. DINT 4 100 0 2000000000 0 Amps 46 AverageCurrent I.AvgCurrent Average of Phase Currents. DINT 4 100 0 2000000000 0 Amps % 47 L1PercentFLA L1 Current in %FLA UINT 2 10 0 10000 0 48 L2PercentFLA L2 Current in %FLA UINT 2 10 0 10000 0 % 49 L3PercentFLA L3 Current in %FLA UINT 2 10 0 10000 0 % 50 AvgPercentFLA I.AvgPercentFLA Average Current in UINT %FLA 2 10 0 10000 0 % 51 GFCurrent I.GroundFaultCurrent The Ground Fault Current. UINT 2 100 0 9999 0 Amps 52 CurrentImbal I.CurrentImbalance Percent Current Imbalance USINT 1 1 0 200 0 % 53 L1toL2Voltage I.L1L2Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt 54 L2toL3Voltage I.L2L3Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt 55 L3toL1Voltage I.L3L1Voltage 3 Phase RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt 56 AvgVoltageLtoL I.AvgLLVoltage Average RMS Voltage Line-Line UINT 2 10 0 65535 0 Volt 57 L1toNVoltage 3 Phase RMS Voltage LineNeutral UINT 2 10 0 65535 0 Volt 58 L2toNVoltage 3 Phase RMS Voltage LineNeutral UINT 2 10 0 65535 0 Volt 59 L3toNVoltage 3 Phase RMS Voltage LineNeutral UINT 2 10 0 65535 0 Volt Rockwell Automation Publication 193-UM015C-EN-P - December 2014 443 Appendix B Group Voltage Monitor (Continued) Power Monitor Energy Monitoring 444 Parameter List Param No. 60 Parameter Name Device Profile Tag Name Description AvgVoltageLtoN Average RMS Voltage LineNeutral 61 VoltageUnbalance 62 VoltageFrequency 63 Type Scale Factor Min Max Default Units 2 10 0 65535 0 Volt Voltage Unbalance USINT 1 1 0 255 0 % Voltage Frequency UINT 2 10 0 2500 0 Hz VPhaseRotation Voltage Phase RotationпЂ (ABC or ACB) UINT 2 1 0= NoRotation 1= ABC 2= ACB 64 L1RealPower Phase L1 Real Power. DINT 4 1000 -2000000000 2000000000 0 kW 65 L2RealPower Phase L2 Real Power. DINT 4 1000 -2000000000 2000000000 0 kW 66 L3RealPower Phase L3 Real Power. DINT 4 1000 -2000000000 2000000000 0 kW Total Real Power I.TotalRealPower UINT Data Size (bytes) 0 67 TotalRealPower DINT 4 1000 -2000000000 2000000000 0 kW 68 L1ReactivePower Phase L1 Reactive DINT Power 4 1000 -2000000000 2000000000 0 kVAR 69 L2ReactivePower Phase L2 Reactive DINT Power 4 1000 -2000000000 2000000000 0 kVAR 70 L3ReactivePower Phase L3 Reactive DINT Power 4 1000 -2000000000 2000000000 0 kVAR 71 TotalReactivePwr Total Reactive Power DINT 4 1000 -2000000000 2000000000 0 kVAR 72 L1ApparentPower Phase L1 Apparent DINT Power 4 1000 0 2000000000 0 kVA 73 L2ApparentPower Phase L2 Apparent DINT Power 4 1000 0 2000000000 0 kVA 74 L3ApparentPower Phase L3 Apparent DINT Power 4 1000 0 2000000000 0 kVA 75 TotalApparentPwr Total Apparent Power DINT 4 1000 0 2000000000 0 kVA 76 L1PowerFactor Phase L1 True Power Factor (PF) INT 2 10 -1000 1000 0 % 77 L2PowerFactor Phase L2 True Power Factor (PF) INT 2 10 -1000 1000 0 % 78 L3PowerFactor Phase L3 True Power Factor (PF) INT 2 10 -1000 1000 0 % 79 TotalPowerFactor Total True Power Factor (PF) INT 2 10 -1000 1000 0 % 80 kWhTimes10E9 Total Real Energy INT (kWh) Word 10^9 2 1 -999 999 0 81 kWhTimes10E6 Total Real Energy INT (kWh) Word 10^6 2 1 -999 999 0 82 kWhTimes10E3 Total Real Energy INT (kWh) Word 10^3 2 1 -999 999 0 83 kWhTimes10E0 Total Real Energy INT (kWh) Word 10^0 2 1 -999 999 0 84 kWhTimes10E-3 Total Real Energy INT (kWh) Word 10^-3 2 1 -999 999 0 85 kVARhCon10E9 Total Reactive INT Energy Consumed (kVARh) Word 10^9 2 1 -999 999 0 86 kVARhCon10E6 Total Reactive INT Energy Consumed (kVARh) Word 10^6 2 1 -999 999 0 87 kVARhCon10E3 Total Reactive INT Energy Consumed (kVARh) Word 10^3 2 1 -999 999 0 88 kVARhCon10E0 Total Reactive INT Energy Consumed (kVARh) Word 10^0 2 1 -999 999 0 I.TotalReactivePower I.TotalApparentPower I.PowerFactor Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units Energy Monitoring 89 (Continued) kVARhCon10E-3 Total Reactive INT Energy Consumed (kVARh) Word 10^-3 2 1 -999 999 0 90 kVARhGen10E9 Total Reactive INT Energy Generated (kVARh) Word 10^9 2 1 -999 999 0 91 kVARhGen10E6 Total Reactive INT Energy Generated (kVARh) Word 10^6 2 1 -999 999 0 92 kVARhGen10E3 Total Reactive INT Energy Generated (kVARh) Word 10^3 2 1 -999 999 0 93 kVARhGen10E0 Total Reactive INT Energy Generated (kVARh) Word 10^0 2 1 -999 999 0 94 kVARhGen10E-3 Total Reactive INT Energy Generated (kVARh) Word 10^-3 2 1 -999 999 0 95 kVARhNet10E9 Total Reactive Energy Net (kVARh) Word 10^9 INT 2 1 -999 999 0 96 kVARhNet10E6 Total Reactive Energy Net (kVARh) Word 10^6 INT 2 1 -999 999 0 97 kVARhNet10E3 Total Reactive Energy Net (kVARh) Word 10^3 INT 2 1 -999 999 0 98 kVARh Net 10E0 Total Reactive Energy Net (kVARh) Word 10^0 INT 2 1 -999 999 0 99 kVARhNet10E-3 Total Reactive Energy Net (kVARh) Word 10^-3 INT 2 1 -999 999 0 100 kVAhTimes10E9 Total Apparent Energy (kVAh) Word 10^9 INT 2 1 -999 999 0 101 kVAhTimes10E6 Total Apparent Energy (kVAh) Word 10^6 INT 2 1 -999 999 0 102 kVAhTimes10E3 Total Apparent Energy (kVAh) Word 10^3 INT 2 1 -999 999 0 103 kVAhTimes10E0 Total Apparent Energy (kVAh) Word 10^0 INT 2 1 -999 999 0 104 kVAhTimes10E-3 Total Apparent Energy (kVAh) Word 10^-3 INT 2 1 -999 999 0 105 kWDemand Real Power Demand DINT 4 1000 -2000000000 2000000000 0 kW 106 MaxkWDemand Maximum Real Power Demand DINT 4 1000 -2000000000 2000000000 0 kW 107 VARDemand Reactive Power Demand DINT 4 1000 -2000000000 2000000000 0 kVAR 108 MaxVARDemand Maximum Reactive DINT Demand 4 1000 -2000000000 2000000000 0 kVAR 109 VADemand Apparent Power Demand DINT 4 1000 0 2000000000 0 kVA 110 MaxVADemand Maximum Apparent Power Demand DINT 4 1000 0 2000000000 0 kVA Rockwell Automation Publication 193-UM015C-EN-P - December 2014 445 Appendix B Group Analog Monitoring Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Max Default Units 111 InAnMod1Ch00 I.Analog1.Ch00Data Value measured at UINT Analog Expansion Module 1 Input 00 2 1 -32768 32767 0 112 InAnMod1Ch01 I.Analog1.Ch01Data Value measured at UINT Analog Expansion Module 1 Input 01 2 1 -32768 32767 0 113 InAnMod1Ch02 I.Analog1.Ch02Data Value measured at UINT Analog Expansion Module 1 Input 02 2 1 -32768 32767 0 114 InAnMod2Ch00 I.Analog2.Ch00Data Value measured at UINT Analog Expansion Module 2 Input 00 2 1 -32768 32767 0 115 InAnMod2Ch01 I.Analog2.Ch01Data Value measured at UINT Analog Expansion Module 2 Input 01 2 1 -32768 32767 0 116 InAnMod2Ch02 I.Analog2.Ch02Data Value measured at UINT Analog Expansion Module 2 Input 02 2 1 -32768 32767 0 117 InAnMod3Ch00 I.Analog3.Ch00Data Value measured at UINT Analog Expansion Module 3 Input 00 2 1 -32768 32767 0 118 InAnMod3Ch01 I.Analog3.Ch01Data Value measured at UINT Analog Expansion Module 3 Input 01 2 1 -32768 32767 0 119 InAnMod3Ch02 I.Analog3.Ch02Data Value measured at UINT Analog Expansion Module 3 Input 02 2 1 -32768 32767 0 120 InAnMod4Ch00 I.Analog4.Ch00Data Value measured at UINT Analog Expansion Module 4 Input 00 2 1 -32768 32767 0 121 InAnMod4Ch01 I.Analog4.Ch01Data Value measured at UINT Analog Expansion Module 4 Input 01 2 1 -32768 32767 0 122 InAnMod4Ch02 I.Analog4.Ch02Data Value measured at UINT Analog Expansion Module 4 Input 02 2 1 -32768 32767 0 123 AnalogMod1Status I.Analog1.Ch00InputOpenWire I.Analog1.Ch00InputOverrange I.Analog1.Ch00InputUnderrange I.Analog1.Ch01InputOpenWire I.Analog1.Ch01InputOverrange I.Analog1.Ch01InputUnderrange I.Analog1.Ch02InputOpenWire I.Analog1.Ch02InputOverrange I.Analog1.Ch02InputUnderrange I.Analog1.Ch00OutputOpenWire I.Analog1.Ch00OutputInHold I.Analog1.Ch00OutputOverrange I.Analog1.Ch00OutputUnderrange I.Analog1.AddressChanged Analog Expansion UINT Module 1 Status 2 1 Bit0= InCh00OpenCrcuit Bit1= InCh00OverRange Bit2= InCh00UnderRange Bit3= InCh01OpenCrcuit Bit4= InCh01OverRange Bit5= InCh01UnderRange Bit6= InCh02OpenCrcuit Bit7= InCh02OverRange Bit8= InCh02UnderRange Bit9= OutOpenCircuit Bit10= OutHoldLastSt Bit11= OutOverRange Bit12= OutUnderRange Bit 13=Module Configured Bit 14=Module Warning Bit 15=Module Faulted 0 124 AnalogMod2Status I.Analog3.Ch00InputOpenWire I.Analog3.Ch00InputOverrange I.Analog3.Ch00InputUnderrange I.Analog3.Ch01InputOpenWire I.Analog3.Ch01InputOverrange I.Analog3.Ch01InputUnderrange I.Analog3.Ch02InputOpenWire I.Analog3.Ch02InputOverrange I.Analog3.Ch02InputUnderrange I.Analog3.Ch00OutputOpenWire I.Analog3.Ch00OutputInHold I.Analog3.Ch00OutputOverrange I.Analog3.Ch00OutputUnderrange I.Analog3.AddressChanged Analog Expansion UINT Module 2 Status 2 1 Bit0= InCh00OpenCrcuit Bit1= InCh00OverRange Bit2= InCh00UnderRange Bit3= InCh01OpenCrcuit Bit4= InCh01OverRange Bit5= InCh01UnderRange Bit6= InCh02OpenCrcuit Bit7= InCh02OverRange Bit8= InCh02UnderRange Bit9= OutOpenCircuit Bit10= OutHoldLastSt Bit11= OutOverRange Bit12= OutUnderRange Bit 13=Module Configured Bit 14=Module Warning Bit 15=Module Faulted 0 I.Analog1.SelftestFailed I.Analog3.SelftestFailed 446 Min Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Param No. Parameter Name Device Profile Tag Name I.Analog3.Ch00InputOpenWire I.Analog3.Ch00InputOverrange I.Analog3.Ch00InputUnderrange I.Analog3.Ch01InputOpenWire I.Analog3.Ch01InputOverrange I.Analog3.Ch01InputUnderrange I.Analog3.Ch02InputOpenWire I.Analog3.Ch02InputOverrange I.Analog3.Ch02InputUnderrange I.Analog3.Ch00OutputOpenWire I.Analog3.Ch00OutputInHold I.Analog3.Ch00OutputOverrange I.Analog3.Ch00OutputUnderrange I.Analog3.AddressChanged Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units Analog Monitoring 125 (Continued) AnalogMod3Status Analog Expansion UINT Module 3 Status 2 1 Bit0= InCh00OpenCrcuit Bit1= InCh00OverRange Bit2= InCh00UnderRange Bit3= InCh01OpenCrcuit Bit4= InCh01OverRange Bit5= InCh01UnderRange Bit6= InCh02OpenCrcuit Bit7= InCh02OverRange Bit8= InCh02UnderRange Bit9= OutOpenCircuit Bit10= OutHoldLastSt Bit11= OutOverRange Bit12= OutUnderRange Bit 13=Module Configured Bit 14=Module Warning Bit 15=Module Faulted 0 126 AnalogMod4Status Analog Expansion UINT Module 4 Status 2 1 Bit0= InCh00OpenCrcuit Bit1= InCh00OverRange Bit2= InCh00UnderRange Bit3= InCh01OpenCrcuit Bit4= InCh01OverRange Bit5= InCh01UnderRange Bit6= InCh02OpenCrcuit Bit7= InCh02OverRange Bit8= InCh02UnderRange Bit9= OutOpenCircuit Bit10= OutHoldLastSt Bit11= OutOverRange Bit12= OutUnderRange Bit 13=Module Configured Bit 14=Module Warning Bit 15=Module Faulted 0 127 TripHistory0 Last trip to occur UINT 2 1 See Trip History Codes 0 128 TripHistory1 Second last trip to UINT occur 2 1 See Trip History Codes 0 129 TripHistory2 Third last trip to occur UINT 2 1 See Trip History Codes 0 130 TripHistory3 Fourth last trip to occur UINT 2 1 See Trip History Codes 0 131 TripHistory4 Fifth last trip to occur UINT 2 1 See Trip History Codes 0 132 Reserved 133 WarningHistory0 Last warning to occur. UINT 2 1 See Warning History Codes 0 134 WarningHistory1 Second last warning to occur. UINT 2 1 See Warning History Codes 0 135 WarningHistory2 Third last warning UINT to occur. 2 1 See Warning History Codes 0 136 WarningHistory3 Fourth last warning to occur. UINT 2 1 See Warning History Codes 0 137 WarningHistory4 Fifth last warning to occur. UINT 2 1 See Warning History Codes 0 138 Reserved 139 TripHistoryMaskI C.History.OverloadTripEnEn C.History.PhaseLossTripEn C.History.GroundFaultCurrentTripEn C.History.StallTripEn C.History.JamTripEn C.History.UnderloadTripEn C.History.CurrentImbalanceTripEn C.History.L1UnderCurrentTripEn C.History.L2UnderCurrentTripEn C.History.L3UnderCurrentTripEn C.History.L1OverCurrentTripEn C.History.L2OverCurrentTripEn C.History.L3OverCurrentTripEn C.History.L1LineLossTripEn C.History.L2LineLossTripEn C.History.L3LineLossTripEn Trip History Mask for Current-based Trips UINT 2 1 Bit0= OverloadTrip Bit1= PhaseLossTrip Bit2= GroundFaultTrip Bit3= StallTrip Bit4= JamTrip Bit5= UnderloadTrip Bit6= CurrentImbalTrip Bit7= L1UnderCurrTrip Bit8= L2UnderCurrTrip Bit9= L3UnderCurrTrip Bit10= L1OverCurrenTrip Bit11= L2OverCurrenTrip Bit12= L3OverCurrenTrip Bit13= L1LineLossTrip Bit14= L2LineLossTrip Bit15= L3LineLossTrip 0xFFFF 140 TripHistoryMaskV C.History.UnderVoltageTripEn C.History.OverVoltageTripEn C.History.VoltageImbalanceTripEn C.History.PhaseRotationMismatchTripEn C.History.UnderFrequencyTripEn C.History.OverFrequencyTripEn Trip History Mask UINT for Voltage-based Trips 2 1 Bit0= UnderVoltageTrip Bit1= OvervoltageTrip Bit2= VoltageUnbalTrip Bit3= PhaseRotationTrp Bit4= UnderFreqTrip Bit5= OverFreqTrip 0x3F I.Analog3.SelftestFailed I.Analog4.Ch00InputOpenWire I.Analog4.Ch00InputOverrange I.Analog4.Ch00InputUnderrange I.Analog4.Ch01InputOpenWire I.Analog4.Ch01InputOverrange I.Analog4.Ch01InputUnderrange I.Analog4.Ch02InputOpenWire I.Analog4.Ch02InputOverrange I.Analog4.Ch02InputUnderrange I.Analog4.Ch00OutputOpenWire I.Analog4.Ch00OutputInHold I.Analog4.Ch00OutputOverrange I.Analog4.Ch00OutputUnderrange I.Analog4.AddressChanged I.Analog4.SelftestFailed Trip/Warn History Rockwell Automation Publication 193-UM015C-EN-P - December 2014 447 Appendix B Group Trip/Warn History (continued) Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Max Default Units 141 TripHistoryMaskP C.History.UnderRealPowerTripEn C.History.OverRealPowerTripEn C.History.UnderReactivePowerConsumedTripEn C.History.OverReactivePowerConsumedTripEn C.History.UnderReactivePowerGeneratedTripEn C.History.OverReactivePowerGeneratedTripEn C.History.UnderApparentPowerTripEn C.History.OverApparentPowerTripEn C.History.UnderPowerFactorLaggingTripEn C.History.OverPowerFactorLaggingTripEn C.History.UnderPowerFactorLeadingTripEn C.History.OverPowerFactorLeadingTripEn Trip History Mask for Power-based Trips UINT 2 1 Bit0= UnderKWTrip Bit1= OverKWTrip Bit2= UnderKVARConTrip Bit3= OverKVARConTrip Bit4= UnderKVARGenTrip Bit5= OverKVARGenTrip Bit6= UnderKVATrip Bit7= OverKVATrip Bit8= UnderPFLagTrip Bit9= OverPFLagTrip Bit10= UnderPFLeadTrip Bit11= OverPFLeadTrip 0xFFF 142 TripHistoryMaskC C.History.TestTripEn C.History.PTCTripEn Trip History Mask for Control-based Trips UINT 2 1 Bit0= TestTrip Bit1= PTCTrip Bit2= DLXTrip Bit3= OperStationTrip Bit4= RemoteTrip Bit5= BlockedStartTrip Bit6= HardwareFltTrip Bit7= ConfigTrip Bit8= OptionMatchTrip Bit9= DLXFBTimeoutTrip Bit10= ExpansionBusTrip Bit11= Reserved Bit12= Reserved Bit13= NVSTrip Bit14=TestModeTrip 0x27FF C.History.Analog1Ch00TripEn C.History.Analog1Ch01TripEn C.History.Analog1Ch02TripEn C.History.Analog2Ch00TripEn C.History.Analog2Ch01TripEn C.History.Analog2Ch02TripEn C.History.Analog3Ch00TripEn C.History.Analog3Ch01TripEn C.History.Analog3Ch02TripEn C.History.Analog4Ch00TripEn C.History.Analog4Ch01TripEn C.History.Analog4Ch02TripEn Trip History Mask for Analog Input Based Trips UINT 2 1 Bit0= InAnMod1Ch00Trip Bit1= InAnMod1Ch01Trip Bit2= InAnMod1Ch02Trip Bit3= InAnMod2Ch00Trip Bit4= InAnMod2Ch01Trip Bit5= InAnMod2Ch02Trip Bit6= InAnMod3Ch00Trip Bit7= InAnMod3Ch01Trip Bit8= InAnMod3Ch02Trip Bit9= InAnMod4Ch00Trip Bit10= InAnMod4Ch01Trip Bit11= InAnMod4Ch02Trip 0xFFF C.History.OverloadWarningEn Warning History Mask for Currentbased Warnings UINT 2 1 Bit0= OverloadWarning Bit1= Reserved Bit2= GroundFltWarning Bit3= Reserved Bit4= JamWarning Bit5= UnderloadWarning Bit6= CurrentImbalWarn Bit7= L1UnderCurrWarn Bit8= L2UnderCurrWarn Bit9= L3UnderCurrWarn Bit10= L1OverCurrenWarn Bit11= L2OverCurrenWarn Bit12= L3OverCurrenWarn Bit13= L1LineLossWarn Bit14= L2LineLossWarn Bit15= L3LineLossWarn 0xFFFF C.History.OperatorStationTripEn C.History.RemoteTripEn C.History.BlockedStartTripEn C.History.HardwareFaultTripEn C.History.ConfigurationTripEn C.History.ModuleMismatchTripEn C.History.ExpansionBusTripEn C.History.NVMErrorTripEn C.History.MCCTestPositionTripEn 143 TripHistoryMaskA 144 Reserved 145 WarnHistoryMaskI C.History.GroundFaultCurrentWarningEn C.History.JamWarningEn C.History.UnderloadWarningEn C.History.CurrentImbalanceWarningEn C.History.L1UnderCurrentWarningEn C.History.L2UnderCurrentWarningEn C.History.L3UnderCurrentWarningEn C.History.L1OverCurrentWarningEn C.History.L2OverCurrentWarningEn C.History.L3OverCurrentWarningEn C.History.L1LineLossWarningEn C.History.L2LineLossWarningEn C.History.L3LineLossWarningEn 448 Min 146 WarnHistoryMaskV C.History.UnderVoltageWarningEn C.History.OverVoltageWarningEn C.History.VoltageImbalanceWarningEn C.History.PhaseRotationMismatchWarningEn C.History.UnderFrequencyWarningEn C.History.OverFrequencyWarningEn Warning History UINT Mask for Voltagebased Warnings 2 1 Bit0= UnderVoltageWarn Bit1= OvervoltageWarn Bit2= VoltageUnbalWarn Bit3= PhaseRotationWrn Bit4= UnderFreqWarning Bit5= OverFreqWarning 0x3F 147 WarnHistoryMaskP C.History.UnderRealPowerWarningEn C.History.OverRealPowerWarningEn C.History.UnderReactivePowerConsumedWarningEn C.History.OverReactivePowerConsumedWarningEn C.History.UnderReactivePowerGeneratedWarningEn C.History.OverReactivePowerGeneratedWarningEn C.History.UnderApparentPowerWarningEn C.History.OverApparentPowerWarningEn C.History.UnderPowerFactorLaggingWarningEn C.History.OverPowerFactorLaggingWarningEn C.History.UnderPowerFactorLeadingWarningEn C.History.OverPowerFactorLeadingWarningEn Warning History Mask for Powerbased Warnings 2 1 Bit0= UnderKWWarning Bit1= OverKWWarning Bit2= UnderKVARConWarn Bit3= OverKVARConWarn Bit4= UnderKVARGenWarn Bit5= OverKVARGenWarn Bit6= UnderKVAWarning Bit7= OverKVAWarning Bit8= UnderPFLagWarn Bit9= OverPFLagWarn Bit10= UnderPFLeadWarn Bit11= OverPFLeadWarn 0xFFF UINT Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Trip/Warn History (continued) Param No. 148 Parameter Name Device Profile Tag Name WarnHistoryMaskC C.History.PTCWarningEn Description Type Data Size (bytes) Scale Factor Default Units UINT 2 1 Bit0= Reserved Bit1= PTCWarning Bit2= DLXWarning Bit3= Reserved Bit4= Reserved Bit5= Reserved Bit6= Reserved Bit7= ConfigWarning Bit8= OptionMatchWarn Bit9= DLXFBTimeoutWarn Bit10= ExpansionBusWarn Bit11= PMNumberOfStarts Bit12= PMOperatingHours Warning History Mask for Analog Input Based Warnings UINT 2 1 Bit0= InAnMod1Ch00Warn 0xFFF Bit1= InAnMod1Ch01Warn Bit2= InAnMod1Ch02Warn Bit3= InAnMod2Ch00Warn Bit4= InAnMod2Ch01Warn Bit5= InAnMod2Ch02Warn Bit6= InAnMod3Ch00Warn Bit7= InAnMod3Ch01Warn Bit8= InAnMod3Ch02Warn Bit9= InAnMod4Ch00Warn Bit10= InAnMod4Ch01Warn Bit11= InAnMod4Ch02Warn C.History.ExpansionBusWarningEn C.History.NumberOfStartsWarningEn C.History.OperatingHoursWarningEn Trip Snapshot Max Warning History Mask for Controlbased Warnings C.History.ModuleMismatchWarningEn C.History.Analog1Ch00WarningEn C.History.Analog1Ch01WarningEn C.History.Analog1Ch02WarningEn C.History.Analog2Ch00WarningEn C.History.Analog2Ch01WarningEn C.History.Analog2Ch02WarningEn C.History.Analog3Ch00WarningEn C.History.Analog3Ch01WarningEn C.History.Analog3Ch02WarningEn C.History.Analog4Ch00WarningEn C.History.Analog4Ch01WarningEn C.History.Analog4Ch02WarningEn Min Appendix B 0x1FFF 149 WarnHistoryMaskA 150 Reserved 151 TSL1Current Snapshot of the actual L1 Phase Current at trip DINT 4 100 0 2000000000 0 Amps 152 TSL2Current Snapshot of the actual L2 Phase Current at trip DINT 4 100 0 2000000000 0 Amps 153 TSL3Current Snapshot of the actual L3 Phase Current at trip DINT 4 100 0 2000000000 0 Amps 154 TSThermUtilized Snapshot of % Thermal Capacity Used at trip UINT 2 1 0 100 0 % 155 TSGFCurrent Snapshot of the Ground Fault Current at trip INT 2 100 0 2540 0 Amps 156 TSL1toL2Voltage Snapshot of 3 UINT Phase RMS Voltage Line-Line at trip 2 10 0 65535 0 Volt 157 TSL2toL3Voltage Snapshot of 3 UINT Phase RMS Voltage Line-Line at trip 2 10 0 65535 0 Volt 158 TSL3toL1Voltage Snapshot of 3 UINT Phase RMS Voltage Line-Line at trip 2 10 0 65535 0 Volt 159 TSTotalRealPwr Snapshot of Total Real Power at trip DINT 4 1000 -2000000000 2000000000 0 kW 160 TSTotalkVAR Snapshot of Total DINT Reactive Power at trip 4 1000 -2000000000 2000000000 0 kVAR 161 TSTotalkVA Snapshot of Total DINT Apparent Power at trip 4 1000 0 2000000000 0 kVA 162 TSTotalPF Snapshot of Total True Power Factor (PF) at trip 2 10 -1000 1000 % INT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 449 Appendix B Group Command Overload Setup Device Setup 450 Parameter List Param No. Parameter Name 163 TripReset 164 165 Device Profile Tag Name Type Data Size (bytes) Scale Factor Min Max Default Units Attempt to reset a BOOL trip 0=Ready 1=TripReset 0 1 0 ConfigPreset IO Configuration based on Logic Personality USINT 0=Ready 1=Factory Defaults 0 54 0 ClearCommand Reset Accumulator(s) USINT 1 1 0= Ready 1= ClrOperStats 2= ClrHistoryLogs 3= ClrPercentTCU 4= ClrKWh 5= ClrKVARh 6= ClrKVAh 7= ClrMaxKWDemad 8= ClrMaxKVARDemand 9= ClrMaxKVADemand 10= ClearAll 0 166 Reserved 167 Reserved O.TripReset Description 168 Reserved 169 Reserved 170 Reserved 171 FLASetting C.FLA1 Overload Full Load UDINT Current Setting 4 100 50 6553500 50 172 TripClass C.TripClass Trip Class Setting USINT 1 1 5 30 10 173 OLPTCResetMode C.OverloadResetMode Overload and PTC Trip Reset Mode BOOL 1 1 0=Manual 1=Automatic 174 OLResetLevel C.OverloadResetLevel Overload Trip Reset USINT Level 1 1 0 100 75 %TCU 175 OLWarningLevel C.OverloadWarningLimit Overload Warning USINT Reset Level 1 1 0 100 85 %TCU 176 SingleOrThree Ph C.ThreePhase Single Phase = L1 BOOL and L2 1 1 0=SinglePhase 1=ThreePhase 177 FLA2Setting C.FLA2 Overload Full Load UDINT Current Setting 2 4 100 50 178 Reserved 179 Reserved 180 Reserved 181 Reserved 0 1 6553500 50 182 Reserved 183 TripEnableI C.Protection.OverloadTripEnEn C.Protection.PhaseLossTripEn C.Protection.GroundFaultCurrentTripEn C.Protection.StallTripEn C.Protection.JamTripEn C.Protection.UnderloadTripEn C.Protection.CurrentImbalanceTripEn C.Protection.L1UnderCurrentTripEn C.Protection.L2UnderCurrentTripEn C.Protection.L3UnderCurrentTripEn C.Protection.L1OverCurrentTripEn C.Protection.L2OverCurrentTripEn C.Protection.L3OverCurrentTripEn C.Protection.L1LineLossTripEn C.Protection.L2LineLossTripEn C.Protection.L3LineLossTripEn Bitmask used to UINT enable/disable current-based trips 2 1 Bit0= OverloadTrip Bit1= PhaseLossTrip Bit2= GroundFaultTrip Bit3= StallTrip Bit4= JamTrip Bit5= UnderloadTrip Bit6= CurrentImbalTrip Bit7= L1UnderCurrTrip Bit8= L2UnderCurrTrip Bit9= L3UnderCurrTrip Bit10= L1OverCurrenTrip Bit11= L2OverCurrenTrip Bit12= L3OverCurrenTrip Bit13= L1LineLossTrip Bit14= L2LineLossTrip Bit15= L3LineLossTrip 3 184 TripEnableV C.Protection.UnderVoltageTripEn C.Protection.OverVoltageTripEn C.Protection.VoltageImbalanceTripEn C.Protection.PhaseRotationMismatchTripEn C.Protection.UnderFrequencyTripEn C.Protection.OverFrequencyTripEn Bitmask used to enable/disable voltage-based trips 2 1 Bit0= UnderVoltageTrip Bit1= OvervoltageTrip Bit2= VoltageUnbalTrip Bit3= PhaseRotationTrp Bit4= UnderFreqTrip Bit5= OverFreqTrip 0 UINT Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Amps Amps Parameter List Group Device Setup (continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 185 TripEnableP C.Protection.UnderRealPowerTripEn C.Protection.OverRealPowerTripEn C.Protection.UnderReactivePowerConsumedTripEn C.Protection.OverReactivePowerConsumedTripEn C.Protection.UnderReactivePowerGeneratedTripEn C.Protection.OverReactivePowerGeneratedTripEn C.Protection.UnderApparentPowerTripEn C.Protection.OverApparentPowerTripEn C.Protection.UnderPowerFactorLaggingTripEn C.Protection.OverPowerFactorLaggingTripEn C.Protection.UnderPowerFactorLeadingTripEn C.Protection.OverPowerFactorLeadingTripEn Bitmask used to UINT enable/disable power-based trips 2 1 Bit0= UnderKWTrip Bit1= OverKWTrip Bit2= UnderKVARConTrip Bit3= OverKVARConTrip Bit4= UnderKVARGenTrip Bit5= OverKVARGenTrip Bit6= UnderKVATrip Bit7= OverKVATrip Bit8= UnderPFLagTrip Bit9= OverPFLagTrip Bit10= UnderPFLeadTrip Bit11= OverPFLeadTrip 0 186 TripEnableC C.Protection.TestTripEn C.Protection.PTCTripEn Bitmask used to UINT enable/disable control-based trips 2 1 Bit0= TestTrip Bit1= PTCTrip Bit2= DLXTrip Bit3= OperStationTrip Bit4= RemoteTrip Bit5= BlockedStartTrip Bit6= HardwareFltTrip Bit7= ConfigTrip Bit8= OptionMatchTrip Bit9= DLXFBTimeoutTrip Bit10= ExpansionBusTrip Bit11= Reserved Bit12= Reserved Bit13= NVSTrip Bit14=TestModeTrip 1 C.Protection.Analog1Ch00TripEn C.Protection.Analog1Ch01TripEn C.Protection.Analog1Ch02TripEn C.Protection.Analog2Ch00TripEn C.Protection.Analog2Ch01TripEn C.Protection.Analog2Ch02TripEn C.Protection.Analog3Ch00TripEn C.Protection.Analog3Ch01TripEn C.Protection.Analog3Ch02TripEn C.Protection.Analog4Ch00TripEn C.Protection.Analog4Ch01TripEn C.Protection.Analog4Ch02TripEn Bitmask used to UINT enable/disable analog-based trips 2 1 Bit0= InAnMod1Ch00Trip Bit1= InAnMod1Ch01Trip Bit2= InAnMod1Ch02Trip Bit3= InAnMod2Ch00Trip Bit4= InAnMod2Ch01Trip Bit5= InAnMod2Ch02Trip Bit6= InAnMod3Ch00Trip Bit7= InAnMod3Ch01Trip Bit8= InAnMod3Ch02Trip Bit9= InAnMod4Ch00Trip Bit10= InAnMod4Ch01Trip Bit11= InAnMod4Ch02Trip 0 C.Protection.OverloadWarningEn Bitmask used to enable/disable current-based warnings UINT 2 1 Bit0= OverloadWarning Bit1= Reserved Bit2= GroundFltWarning Bit3= Reserved Bit4= JamWarning Bit5= UnderloadWarning Bit6= CurrentImbalWarn Bit7= L1UnderCurrWarn Bit8= L2UnderCurrWarn Bit9= L3UnderCurrWarn Bit10= L1OverCurrenWarn Bit11= L2OverCurrenWarn Bit12= L3OverCurrenWarn Bit13= L1LineLossWarn Bit14= L2LineLossWarn Bit15= L3LineLossWarn 0 C.Protection.OperatorStationTripEn C.Protection.RemoteTripEn C.Protection.BlockedStartTripEn C.Protection.HardwareFaultTripEn C.Protection.ConfigurationTripEn C.Protection.ModuleMismatchTripEn C.Protection.ExpansionBusTripEn C.Protection.NVMErrorTripEn C.Protection.MCCTestPositionTripEn 187 TripEnableA 188 Reserved 189 WarningEnableI C.Protection.GroundFaultCurrentWarningEn C.Protection.JamWarningEn C.Protection.UnderloadWarningEn C.Protection.CurrentImbalanceWarningEn C.Protection.L1UnderCurrentWarningEn C.Protection.L2UnderCurrentWarningEn C.Protection.L3UnderCurrentWarningEn C.Protection.L1OverCurrentWarningEn C.Protection.L2OverCurrentWarningEn C.Protection.L3OverCurrentWarningEn C.Protection.L1LineLossWarningEn C.Protection.L2LineLossWarningEn C.Protection.L3LineLossWarningEn 190 WarningEnableV C.Protection.UnderVoltageWarningEn C.Protection.OverVoltageWarningEn C.Protection.VoltageImbalanceWarningEn C.Protection.PhaseRotationMismatchWarningEn C.Protection.UnderFrequencyWarningEn C.Protection.OverFrequencyWarningEn Bitmask used to enable/disable voltage-based warnings UINT 2 1 Bit0= UnderVoltageWarn Bit1= OvervoltageWarn Bit2= VoltageUnbalWarn Bit3= PhaseRotationWrn Bit4= UnderFreqWarning Bit5= OverFreqWarning 0 191 WarningEnableP C.Protection.UnderRealPowerWarningEn C.Protection.OverRealPowerWarningEn C.Protection.UnderReactivePowerConsumedWarningEn C.Protection.OverReactivePowerConsumedWarningEn C.Protection.UnderReactivePowerGeneratedWarningEn C.Protection.OverReactivePowerGeneratedWarningEn C.Protection.UnderApparentPowerWarningEn C.Protection.OverApparentPowerWarningEn C.Protection.UnderPowerFactorLaggingWarningEn C.Protection.OverPowerFactorLaggingWarningEn C.Protection.UnderPowerFactorLeadingWarningEn C.Protection.OverPowerFactorLeadingWarningEn Bitmask used to enable/disable power-based warnings UINT 2 1 Bit0= UnderKWWarning Bit1= OverKWWarning Bit2= UnderKVARConWarn Bit3= OverKVARConWarn Bit4= UnderKVARGenWarn Bit5= OverKVARGenWarn Bit6= UnderKVAWarning Bit7= OverKVAWarning Bit8= UnderPFLagWarn Bit9= OverPFLagWarn Bit10= UnderPFLeadWarn Bit11= OverPFLeadWarn 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 451 Appendix B Group Device Setup (continued) Parameter List Param No. 192 Parameter Name Device Profile Tag Name WarningEnableC C.Protection.PTCWarningEn Description Type Data Size (bytes) Scale Factor Default Units UINT 2 1 Bit0= Reserved Bit1= PTCWarning Bit2= DLXWarning Bit3= Reserved Bit4= Reserved Bit5= Reserved Bit6= Reserved Bit7= ConfigWarning Bit8= OptionMatchWarn Bit9= DLXFBTimeoutWarn Bit10= ExpansionBusWarn Bit11= PMNumberOfStarts Bit12= PMOperatingHour Bitmask used to enable/disable analog-based warnings UINT 2 1 Bit0= InAnMod1Ch00Warn 0 Bit1= InAnMod1Ch01Warn Bit2= InAnMod1Ch02Warn Bit3= InAnMod2Ch00Warn Bit4= InAnMod2Ch01Warn Bit5= InAnMod2Ch02Warn Bit6= InAnMod3Ch00Warn Bit7= InAnMod3Ch01Warn Bit8= InAnMod3Ch02Warn Bit9= InAnMod4Ch00Warn Bit10= InAnMod4Ch01Warn Bit11= InAnMod4Ch02Warn Logic personality Selection USINT 1 1 2 C.Protection.ExpansionBusWarningEn C.Protection.NumberOfStartsWarningEn C.Protection.OperatingHoursWarningEn 452 Max Bitmask used to enable/disable control-based warnings C.Protection.ModuleMismatchWarningEn C.Protection.Analog1Ch00WarningEn C.Protection.Analog1Ch01WarningEn C.Protection.Analog1Ch02WarningEn C.Protection.Analog2Ch00WarningEn C.Protection.Analog2Ch01WarningEn C.Protection.Analog2Ch02WarningEn C.Protection.Analog3Ch00WarningEn C.Protection.Analog3Ch01WarningEn C.Protection.Analog3Ch02WarningEn C.Protection.Analog4Ch00WarningEn C.Protection.Analog4Ch01WarningEn C.Protection.Analog4Ch02WarningEn Min 0 193 WarningEnableA 194 Reserved 195 SetOperatingMode 196 InPt00Assignment C.Pt00InputFunction_0 C.Pt00InputFunction_1 C.Pt00InputFunction_2 C.Pt00InputFunction_3 Assignment for Input Point 00 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 197 InPt01Assignment C.Pt01InputFunction_0 C.Pt01InputFunction_1 C.Pt01InputFunction_2 C.Pt01InputFunction_3 Assignment for Input Point 01 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 198 InPt02Assignment C.Pt02InputFunction_0 C.Pt02InputFunction_1 C.Pt02InputFunction_2 C.Pt02InputFunction_3 Assignment for Input Point 02 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 54 2 Parameter List Group Device Setup (continued Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 199 InPt03Assignment C.Pt03InputFunction_0 C.Pt03InputFunction_1 C.Pt03InputFunction_2 C.Pt03InputFunction_3 Assignment for Input Point 03 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 200 InPt04Assignment C.Pt03InputFunction_0 C.Pt03InputFunction_1 C.Pt03InputFunction_2 C.Pt03InputFunction_3 Assignment for Input Point 04 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 201 InPt05Assignment C.Pt05InputFunction_0 C.Pt05InputFunction_1 C.Pt05InputFunction_2 C.Pt05InputFunction_3 Assignment for Input Point 05 function USINT 1 1 0=Normal 1=TripReset 2=RemoteTrip 3=ActivateFLA2 4=ForceSnapshot 5=EmergencyStart 6=TestMode 7=L1LossArm 8=L2LossArm 9=L3LossArm 10=L1L2LossArm 11=L2L3LossArm 12=L1L3LossArm 13=L1L2L3LossArm 0 202 OutPt0Assignment Assignment for OutputPt00 function USINT 1 1 0=Normal 1=TripRelay 2=ControlRelay 3=TripAlarm 4=WarningAlarm 5=MonL1TripRelay 6= MonL2TripRelay 7= MonL3TripRelay 1 203 OutPt1Assignment Assignment for OutputPt01 function USINT 1 1 0=Normal 1=TripRelay 2=ControlRelay 3=TripAlarm 4=WarningAlarm 5=MonL1TripRelay 6= MonL2TripRelay 7= MonL3TripRelay 0 204 OutPt2Assignment Assignment for OutputPt02 function USINT 1 1 0=Normal 1=TripRelay 2=ControlRelay 3=TripAlarm 4=WarningAlarm 5=MonL1TripRelay 6= MonL2TripRelay 7= MonL3TripRelay 0 205 StartsPerHour C.StartsPerHourLimit Allowable Starts per Hour USINT 1 1 0 120 2 206 StartsInterval C.StartsIntervalLimit The minimum UINT allowable interval between starts 2 1 0 3600 600 Total number of starts for preventative maintenance 2 207 PMTotalStarts C.TotalStartsLimit UINT Second s Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 0 65535 0 453 Appendix B Group Device Setup (continued Options Setup 454 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max 208 PMOperatingHours C.OperatingHoursLimit Total operating hours for preventative maintenance UINT 2 1 0 209 ActFLA2wOutput C.FLA2Select_0 C.FLA2Select_1 C.FLA2Select_2 C.FLA2Select_3 Select FLA2 activate source USINT 1 1 0=Disable 1=OutputPt00 2=OutputPt01 3=OutputPt02 0 210 Reserved 211 SecurityPolicy Select network security feature locks UINT 2 1 Bit0= DeviceConfigEna Bit1= DeviceResetEna Bit2= FWUpdateEnable Bit3= NetworkCfgEna Bit4= PortCfgEna Bit5= Reserved Bit6= Reserved Bit7= Reserved Bit8= Reserved Bit9= Reserved Bit10= Reserved Bit11= Reserved Bit12= Reserved Bit13= Reserved Bit14= Reserved Bit15= PolicyConfigEna 0x8007 212 Language Select the language USINT 1 1 0 2 0 213 FeedbackTimeout DeviceLogix Feedback Timer Timeout UINT 2 1 0 65535 500 214 TransitionDelay Motor Contactor Transition Delay UINT 2 1 0 65535 10000 215 InterlockDelay Motor Contactor Interlock Delay UINT 2 1 1 65535 100 216 EmergencyStartEn Enables the ability UINT to command an Emergency Start of the motor 1 1 0=Disable 1=Enable 0 217 Reserved 218 Reserved 219 Reserved C.EmergencyStartEn 65535 Default Units 0 220 Reserved 221 ControlModuleTyp Select Control Module Type USINT 1 1 0= IgnoreType 1= 6In3Out24VDC 2= 4In3Out120VAC 3= 4In3Out240VAC 4= 4In2OutGFPTC24V 5= 2In2OutGFPTC120V 6= 2In2OutGFPTC240V 0 222 SensingModuleTyp Select Sensing Module Type USINT 1 1 0= IgnoreType 1= VIGPt5to30Amp 2= VIG6to60Amp 3= VIG10to100Amp 4= VIG20to200Amp 5= IGPt5to30Amp 6= IG6to60Amp 7= IG10to100Amp 8= IG20to200Amp 9= IPt5to30Amp 10= I6to60Amp 11= I10to100Amp 12= I20to200Amp 0 223 CommsModuleType Select Communications Module Type USINT 1 1 0=IgnoreType 1=EtherNetIP 2=DeviceNet 3=Profibus 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Hrs Parameter List Group Options Setup (Continued) Current Setup Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 224 OperStationType Select Operator Station Type USINT 1 1 0= IgnoreType 1= NoStation 2= ControlStation 3= DiagStation 0 225 DigitalMod1Type Select Digital I/O USINT Expansion Module 1 Type 1 1 0= IgnoreType 1=NoModule 2=4In2Out24VDC 3=4In2Out120VAC 4=4In2Out240VAC 0 226 DigitalMod2Type Select Digital I/O USINT Expansion Module 2 Type 1 1 0= IgnoreType 1=NoModule 2=4In2Out24VDC 3=4In2Out120VAC 4=4In2Out240VAC 0 227 DigitalMod3Type Select Digital I/O USINT Expansion Module 3 Type 1 1 0= IgnoreType 1=NoModule 2=4In2Out24VDC 3=4In2Out120VAC 4=4In2Out240VAC 0 228 DigitalMod4Type Select Digital I/O USINT Expansion Module 4 Type 1 1 0= IgnoreType 1=NoModule 2=4In2Out24VDC 3=4In2Out120VAC 4=4In2Out240VAC 0 229 AnalogMod1Type Select Analog I/O USINT Expansion Module 1 Type 1 1 0=IgnoreType 1=NoModule 2=3In1OutAnalog 0 230 AnalogMod2Type Select Analog I/O USINT Expansion Module 2 Type 1 1 0=IgnoreType 1=NoModule 2=3In1OutAnalog 0 231 AnalogMod3Type Select Analog I/O USINT Expansion Module 3 Type 1 1 0=IgnoreType 1=NoModule 2=3In1OutAnalog 0 232 AnalogMod4Type Select Analog I/O USINT Expansion Module 4 Type 1 1 0=IgnoreType 1=NoModule 2=3In1OutAnalog 0 233 MismatchAction Select Mismatched UINT Module Actions 0=warning 1= fault 1 1 Bit0= ControlModule Bit1= SensingModule Bit2= CommsModule Bit3= OperatorStation Bit4= DigitalModule1 Bit5= DigitalModule2 Bit6= DigitalModule3 Bit7= DigitalModule4 Bit8= AnalogModule1 Bit9= AnalogModule1 Bit10= AnalogModule1 Bit11= AnalogModule1 0 Phase Loss Inhibit USINT Time 1 1 0 0 Phase Loss Trip Delay USINT 1 234 Reserved 235 Reserved 236 Reserved 237 Reserved 238 Reserved 239 PLInhibitTime 240 PLTripDelay C.PhaseLossInhibitTime C.PhaseLossTripDelay 250 Second s 10 1 250 10 Second s 241 GroundFaultType C.GroundFaultType Select Ground Fault Type USINT 1 1 0= Disabled 1= Internal1to5Amps 2= ExtPt02toPt1Amps 3= ExtPt1toPt5Amps 4= ExtPt5to1Amps 5= External1to5Amps 0 242 GFInhibitTime C.GroundFaultInhibitTime Ground Fault Inhibit Time USINT 1 1 0 10 Ground Fault Trip Delay USINT 243 GFTripDelay C.GroundFaultTripDelay 250 Second s 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 10 0 250 5 Second s 455 Appendix B Group 456 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 244 GFTripLevel C.GroundFaultTripLimit Ground Fault Trip Level UINT 2 100 2 500 200 245 GFWarningDelay C.GroundFaultWarnDelay Ground Fault Warning Delay USINT 1 10 0 250 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Amps Second s Parameter List Group Current Setup continued Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max 500 Appendix B Default Units 246 GFWarningLevel C.GroundFaultWarnLimit Ground Fault Warning Level UINT 2 100 2 247 GFFilter C.GroundFaultFilterEn Filter GF current from %TCU calculation BOOL 1 1 0=Disable 1=Enable 0 248 GFMaxInhibit C.GroundFaultMaxInhibitEn Trip is inhibited when GF exceeds max value BOOL 1 1 0=Disable 1=Enable 0 249 StallEnabledTime C.StallEnabledTime Stall Monitor and Trip Delay USINT 1 1 0 UINT 250 200 10 Second s 250 StallTripLevel C.StallTripLimit Stall Trip Level 2 10 100 600 600 251 JamInhibitTime C.JamInhibitTime Jam Detect Inhibit USINT Time 1 1 0 250 10 Jam Detect Trip Delay USINT 1 252 JamTripDelay C.JamTripDelay Amps %FLA Second s 10 1 250 50 Second s 253 JamTripLevel C.JamTripLimit Jam Detect Trip Level UINT 2 1 50 600 250 %FLA 254 JamWarningLevel C.JamWarnLimit Jam Detect Warning Level UINT 2 1 50 600 150 %FLA 255 ULInhibitTime C.UnderloadInhibitTime Underload Inhibit Time USINT 1 1 0 250 10 Underload Trip Delay USINT 256 ULTripDelay C.UnderloadTripDelay Second s 1 10 1 250 50 Second s 257 ULTripLevel C.UnderloadTripLimit Underload Trip Level USINT 1 1 10 100 50 %FLA 258 ULWarningLevel C.UnderloadWarnLimit Underload Warning Level USINT 1 1 10 100 70 %FLA 259 CIInhibitTime C.CurrentImbalanceInhibitTime Current Imbalance USINT Inhibit Time 1 1 0 250 10 Current Imbalance USINT Trip Delay 1 260 CITripDelay C.CurrentImbalanceTripDelay Second s 10 1 250 50 Second s 261 CITripLevel C.CurrentImbalanceTripLimit Current Imbalance USINT Trip Level 1 1 10 100 35 % 262 CIWarningLevel C.CurrentImbalanceWarnLimit Current Imbalance USINT Warning Level 1 1 10 100 20 % 263 CTPrimary C.CTPrimary Current Transformer Primary Ratio UINT 2 1 1 65535 5 264 CTSecondary C.CTSecondary Current Transformer Secondary Ratio UINT 2 1 1 65535 5 265 UCInhibit Time C.UnderCurrentInhibitTime Under Current Inhibit Time USINT 1 1 0 250 10 L1 Under Current Trip Delay USINT 266 L1UCTripDelay C.L1UnderCurrentTripDelay Second s 1 10 0 250 10 Second s 267 L1UCTripLevel C.L1UnderCurrentTripLimit L1 Under Current Trip Level USINT 1 1 10 100 35 % 268 L1UCWarningLevel C.L1UnderCurrentWarnLimit L1 Under Current Warning Level USINT 1 1 10 100 40 % 269 L2UCTripDelay C.L2UnderCurrentTripDelay L2 Under Current Trip Delay USINT 1 10 0 250 10 Second s 270 L2UCTripLevel C.L2UnderCurrentTripLimit L2 Under Current Trip Level USINT 1 1 10 100 35 % 271 L2UCWarningLevel C.L2UnderCurrentWarnLimit L2 Under Current Warning Level USINT 1 1 10 100 40 % 272 L3UCTripDelay C.L3UnderCurrentTripDelay L3 Under Current Trip Delay USINT 1 10 0 250 10 L3 Under Current Trip Level USINT 273 L3UCTripLevel C.L3UnderCurrentTripLimit Second s 1 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 10 100 35 % 457 Appendix B Group Current Setup continued Parameter List Param No. Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 277 L1OCTripLevel C.L1OverCurrentTripLimit L1 Over Current Trip Level USINT 1 1 10 200 100 % 278 L1OCWarningLevel C.L1OverCurrentWarnLimit L1 Over Current Warning Level USINT 1 1 10 200 90 % 279 L2OCTripDelay L2 Over Current Trip Delay USINT 1 10 0 250 10 Second s 280 L2OCTripLevel C.L2OverCurrentTripDelay L2 Over Current Trip Level USINT 1 1 10 200 100 % 281 L2OCWarningLevel C.L2OverCurrentTripLimit L2 Over Current Warning Level USINT 1 1 10 200 90 % 282 L3OCTripDelay C.L2OverCurrentWarnLimit L3 Over Current Trip Delay USINT 1 10 0 250 10 Second s 283 L3OCTripLevel C.L3OverCurrentTripDelay L3 Over Current Trip Level USINT 1 1 10 200 100 % 284 L3OCWarningLevel C.L3OverCurrentTripLimit L3 Over Current Warning Level USINT 1 1 10 200 90 % 285 LineLossInhTime C.L3OverCurrentWarnLimit Line Loss Inhibit Time USINT 1 1 0 250 10 L1 Line Loss Trip Delay USINT L2 Line Loss Trip Delay USINT L3 Line Loss Trip Delay USINT 286 287 288 458 Parameter Name L1LossTripDelay L2LossTripDelay L3LossTripDelay C.LineLossInhibitTime C.L1LineLossTripDelay C.L2LineLossTripDelay Second s 1 10 0 250 10 Second s 1 10 0 250 10 Second s 1 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 10 0 250 10 Second s Parameter List Group Communications Setup Param No. Parameter Name 289 OutputAssembly 290 Device Profile Tag Name Type Data Size (bytes) Scale Factor Min Max Default Units Output Assembly UINT Instance used by IO Connections 2 1 0 180 144 InputAssembly Input Assembly UINT Instance used by IO Connections 2 1 0 300 300 291 Datalink0 Produced I/O UINT Assembly Datalink0 Parameter Number 2 1 0 560 0 292 Datalink1 Produced I/O UINT Assembly Datalink1 Parameter Number 2 1 0 560 0 293 Datalink2 Produced I/O UINT Assembly Datalink2 Parameter Number 2 1 0 560 0 294 Datalink3 Produced I/O UINT Assembly Datalink3 Parameter Number 2 1 0 560 0 295 Datalink4 Produced I/O UINT Assembly Datalink4 Parameter Number 2 1 0 560 0 296 Datalink5 Produced I/O UINT Assembly Datalink5 Parameter Number 2 1 0 560 0 297 Datalink6 Produced I/O UINT Assembly Datalink6 Parameter Number 2 1 0 560 0 298 Datalink7 Produced I/O UINT Assembly Datalink7 Parameter Number 2 1 0 560 0 299 Reserved 300 Reserved 301 Reserved 302 Reserved 303 Reserved C.L3LineLossTripDelay Description Appendix B Rockwell Automation Publication 193-UM015C-EN-P - December 2014 459 Appendix B Group Output Setup 460 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 304 OutPt00PrFltAct C.Pt00OutputProtectionFaultMode Output Pt00 action BOOL on protection fault 1 1 0= GoToPrFltValue 1= IgnoreIfPossible 0 305 OutPt00PrFltVal C.Pt00OutputProtectionFaultValue Output Pt00 value BOOL on protection fault 1 1 0=Open 1=Closed 0 306 OutPt00ComFltAct C.Pt00OutputFaultMode Output Pt00 action BOOL on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 307 OutPt00ComFltVal C.Pt00OutputFaultValue Out Pt00 value on BOOL comms fault 1 1 0=Open 1=Closed 0 308 OutPt00ComIdlAct C.Pt00OutputProgMode Output Pt00 action BOOL on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 309 OutPt00ComIdlVal C.Pt00OutputProgValue Output Pt00 value BOOL on comms idle 1 1 0=Open 1=Closed 0 310 OutPt01PrFltAct C.Pt01OutputProtectionFaultMode Output Pt01 action BOOL on protection fault 1 1 0= GoToPrFltValue 1= IgnoreIfPossible 0 311 OutPt01PrFltVal C.Pt01OutputProtectionFaultValue Output Pt01 value BOOL on protection fault 1 1 0=Open 1=Closed 0 312 OutPt01ComFltAct C.Pt01OutputFaultMode Output Pt01 action BOOL on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 313 OutPt01ComFltVal C.Pt01OutputFaultValue Output Pt01 value BOOL on comms fault 1 1 0=Open 1=Closed 0 314 OutPt01ComIdlAct C.Pt01OutputProgMode Output Pt01 action BOOL on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 315 OutPt01ComIdlVal C.Pt01OutputProgValue Output Pt01 value BOOL on comms idle 1 1 0=Open 1=Closed 0 316 OutPt02PrFltAct C.Pt02OutputProtectionFaultMode Output Pt02 action BOOL on protection fault 1 1 0= GoToPrFltValue 1= IgnoreIfPossible 0 317 OutPt02PrFltVal C.Pt02OutputProtectionFaultValue Output Pt02 value BOOL on protection fault 1 1 0=Open 1=Closed 0 318 OutPt02ComFltAct C.Pt02OutputFaultMode Output Pt02 action BOOL on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 319 OutPt02ComFltVal C.Pt02OutputFaultValue Output Pt02 value BOOL on comms fault 1 1 0=Open 1=Closed 0 320 OutPt02ComIdlAct C.Pt02OutputProgMode Output Pt02 action BOOL on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 321 OutPt02ComIdlVal C.Pt02OutputProgValue Output Pt02 value BOOL on comms idle 1 1 0=Open 1=Closed 0 322 OutDig1PrFltAct C.Digital1ProtectionFaultMode Digital Expansion BOOL Module 1 Outputs action on protection fault 1 1 0= GoToPrFltValue 1= Ignore 0 323 OutDig1PrFltVal C.Digital1ProtectionFaultValue Digital Expansion BOOL Module 1 Outputs value on protection fault 1 1 0=Open 1=Closed 0 324 OutDig1ComFltAct C.Digital1FaultMode Digital Expansion BOOL Module 1 Outputs action on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 325 OutDig1ComFltVal C.Digital1FaultValue Digital Expansion BOOL Module 1 Outputs value on comms fault 1 1 0=Open 1=Closed 0 326 OutDig1ComIdlAct C.Digital1ProgMode Digital Expansion BOOL Module 1 Outputs action on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 327 OutDig1ComIdlVal C.Digital1ProgValue Digital Expansion BOOL Module 1 Outputs value on comms idle 1 1 0=Open 1=Closed 0 328 OutDig2PrFltAct C.Digital2ProtectionFaultMode Digital Expansion BOOL Module 2 Outputs action on protection fault 1 1 0= GoToPrFltValue 1= Ignore 0 329 OutDig2PrFltVal C.Digital2ProtectionFaultValue Digital Expansion BOOL Module 2 Outputs value on protection fault 1 1 0=Open 1=Closed 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Output Setup Continued DeviceLogix Setup Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 330 OutDig2ComFltAct C.Digital2FaultMode Digital Expansion BOOL Module 2 Outputs action on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 331 OutDig2ComFltVal C.Digital2FaultValue Digital Expansion BOOL Module 2 Outputs value on comms fault 1 1 0=Open 1=Closed 0 332 OutDig2ComIdlAct C.Digital2ProgMode Digital Expansion BOOL Module 2 Outputs action on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 333 OutDig2ComIdlVal C.Digital2ProgValue Digital Expansion BOOL Module 2 Outputs value on comms idle 1 1 0=Open 1=Closed 0 334 OutDig3PrFltAct C.Digital3ProtectionFaultMode Digital Expansion BOOL Module 3 Outputs action on protection fault 1 1 0= GoToPrFltValue 1= Ignore 0 335 OutDig3PrFltVal C.Digital3ProtectionFaultValue Digital Expansion BOOL Module 3 Outputs value on protection fault 1 1 0=Open 1=Closed 0 336 OutDig3ComFltAct C.Digital3FaultMode Digital Expansion BOOL Module 3 Outputs action on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 337 OutDig3ComFltVal C.Digital3FaultValue Digital Expansion BOOL Module 3 Outputs value on comms fault 1 1 0=Open 1=Closed 0 338 OuDig3ComIdlAct C.Digital3ProgMode Digital Expansion BOOL Module 3 Outputs action on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 339 OutDig3ComIdlVal C.Digital3ProgValue Digital Expansion BOOL Module 3 Outputs value on comms idle 1 1 0=Open 1=Closed 0 340 OutDig4PrFltAct C.Digital4ProtectionFaultMode Digital Expansion BOOL Module 4 Outputs action on protection fault 1 1 0= GoToPrFltValue 1= Ignore 0 341 OutDig4PrFltVal C.Digital4ProtectionFaultValue Digital Expansion BOOL Module 4 Outputs value on protection fault 1 1 0=Open 1=Closed 0 342 OutDig4ComFltAct C.Digital4FaultMode Digital Expansion BOOL Module 4 Outputs action on comms fault 1 1 0= GoToCommFltValue 1= HoldLastState 0 343 OutDig4ComFltVal C.Digital4FaultValue Digital Expansion BOOL Module 4 Outputs value on comms fault 1 1 0=Open 1=Closed 0 344 OutDig4ComIdlAct C.Digital4ProgMode Digital Expansion BOOL Module 4 Outputs action on comms idle 1 1 0= GoToCommIdlValue 1= HoldLastState 0 345 OutDig4ComIdlVal C.Digital4ProgValue Digital Expansion BOOL Module 4 Outputs value on comms idle 1 1 0=Open 1=Closed 0 346 CommOverride Enabling allows BOOL local logic to override a loss of an I/O Connection. 1 1 0=Disable 1=Enable 0 347 NetworkOverride Enabling allows BOOL local logic to override a Network Fault. 1 1 0=Disable 1=Enable 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 461 Appendix B Parameter List Group DeviceLogix Setup (Continued) 462 Param No. Parameter Name 348 PtDeviceOuts 349 Reserved 350 351 Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units Status of UINT DeviceLogix Network Outputs. 2 1 Bit0= Pt00DeviceOut Bit1= Pt01DeviceOut Bit2= Pt02DeviceOut Bit3= Pt03DeviceOut Bit4= Pt04DeviceOut Bit5= Pt05DeviceOut Bit6= Pt06DeviceOut Bit7= Pt07DeviceOut Bit8= Pt08DeviceOut Bit9= Pt09DeviceOut Bit10= Pt10DeviceOut Bit11= Pt11DeviceOut Bit12= Pt12DeviceOut Bit13= Pt13DeviceOut Bit14= Pt14DeviceOut Bit15= Pt15DeviceOut 0 PtDevOutCOSMask When bit is set the UINT network output will trigger a COS message. 2 1 Bit0= Pt00DeviceOut Bit1= Pt01DeviceOut Bit2= Pt02DeviceOut Bit3= Pt03DeviceOut Bit4= Pt04DeviceOut Bit5= Pt05DeviceOut Bit6= Pt06DeviceOut Bit7= Pt07DeviceOut Bit8= Pt08DeviceOut Bit9= Pt09DeviceOut Bit10= Pt10DeviceOut Bit11= Pt11DeviceOut Bit12= Pt12DeviceOut Bit13= Pt13DeviceOut Bit14= Pt14DeviceOut Bit15= Pt15DeviceOut 0 DLXUserDefData General Purpose UDINT Data Value for Use in DeviceLogix Programs 4 1 0 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 0xFFFFFFFF Parameter List Group Voltage Setup Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Default Units 352 VoltageMode C.VoltageMode Voltage Wiring Mode USINT 1 1 0= DeltaпЂ 1= WyeпЂ 2= DeltaPTDelta2WyeпЂ 3= WyePTDelta2WyeпЂ 4= DeltaPTWye2DeltaпЂ 5= WyePTWye2Delta 0 353 PTPrimary C.PTPrimary Potential Transformer Primary Rating UINT 2 1 1 65535 480 354 PTSecondary C.PTSecondary Potential Transformer Secondary Rating UINT 2 1 1 540 480 355 UVInhibitTime C.UnderVoltageInhibitTime Under Voltage Inhibit Time USINT 1 1 0 250 10 356 UVTripDelay C.UnderVoltageTripDelay Second s Under Voltage Trip USINT Delay 1 10 1 250 10 Second s 357 UVTripLevel C.UnderVoltageTripLimit Under Voltage Trip UINT Level 2 10 0 65535 1000 Volt 358 UVWarningLevel C.UnderVoltageWarnLimit Under Voltage Warning Level UINT 2 10 0 65535 4000 Volt 359 OVInhibitTime C.OverVoltageInhibitTime Over Voltage Inhibit Time USINT 1 1 0 250 10 Over Voltage Trip Delay USINT 360 OVTripDelay C.OverVoltageTripDelay Second s 1 10 1 250 10 Second s 361 OVTripLevel C.OverVoltageTripLimit Over Voltage Trip Level UINT 2 10 0 65535 5000 Volt 362 OVWarningLevel C.OverVoltageWarnLimit Over Voltage Warning Level UINT 2 10 0 65535 4900 Volt 363 PhRotInhibitTime C.PhaseRotationInhibitTime Phase Rotation Inhibit Time USINT 1 1 0 250 10 364 PhaseRotTripType C.PhaseRotationTripType_0 Second s Voltage Phase USINT Rotation Trip Type 1 1 1 0= NoRotation 1= ABC 2= ACB 1 Voltage Imbalance USINT Inhibit Time 1 1 0 250 10 Voltage Imbalance USINT Trip Delay 1 C.PhaseRotationTripType_1 365 Voltage Setup (continued) Max Appendix B 366 VIBInhibitTime VIBTripDelay C.VoltageImbalanceInhibitTime C.VoltageImbalanceTripDelay Second s 10 1 250 10 Second s 367 VIBTripLevel C.VoltageImbalanceTripLimit Voltage Imbalance USINT Trip Level 1 1 0 100 85 % 368 VIBWarningLevel C.VoltageImbalanceWarnLimit Voltage Imbalance USINT Warning Level 1 1 0 100 75 % 369 UFInhibitTime C.UnderFrequencyInhibitTime Under Frequency Inhibit Time USINT 1 1 0 250 10 Under Frequency Trip Delay USINT 370 UFTripDelay C.UnderFrequencyTripDelay Second s 1 10 1 250 10 Second s 371 UFTripLevel C.UnderFrequencyTripLimit Under Frequency Trip Level USINT 1 1 46 65 57 Hz 372 UFWarningLevel C.UnderFrequencyWarnLimit Under Frequency Warning Level USINT 1 1 46 65 58 Hz 373 OFInhibitTime C.OverFrequencyInhibitTime Over Frequency Inhibit Time USINT 1 1 0 250 10 Over Frequency Trip Delay USINT 374 OFTripDelay C.OverFrequencyTripDelay Second s 1 10 1 250 10 Second s 375 OFTripLevel C.OverFrequencyTripLimit Over Frequency Trip Level USINT 1 1 46 65 63 Hz 376 OFWarningLevel C.OverFrequencyWarnLimit Over Frequency Warning Level USINT 1 1 46 65 62 Hz Rockwell Automation Publication 193-UM015C-EN-P - December 2014 463 Appendix B Group Power Setup Parameter List Param No. Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min 377 PowerScale C.PowerScale Power value scale factor (kW MW) USINT 1 1 0=kW 1=MW 378 UWInhibitTime C.UnderRealPowerInhibitTime Under Total Real USINT Power Inhibit Time 1 1 0 Under Total Real Power Trip Delay USINT 1 379 UWTripDelay C.UnderRealPowerTripDelay Max Default Units 0 250 10 Second s 10 1 250 10 Second s 380 UWTripLevel C.UnderRealPowerTripLimit Under Total Real Power Trip Level DINT 4 1000 0 2000000000 0 kW 381 UWWarningLevel C.UnderRealPowerWarnLimit Under Total Real Power Warning Level DINT 4 1000 0 2000000000 0 kW 382 OWInhibitTime C.OverRealPowerInhibitTime Over Total Real USINT Power Inhibit Time 1 1 0 250 Over Total Real Power Trip Delay USINT 1 383 OWTripDelay C.OverRealPowerTripDelay 10 Second s 10 1 250 10 Second s 384 OWTripLevel C.OverRealPowerTripLimit Over Total Real Power Trip Level DINT 4 1000 0 2000000000 0 kW 385 OWWarningLevel C.OverRealPowerWarnLimit Over Total Real Power Warning Level DINT 4 1000 0 2000000000 0 kW 386 UVARCInhibitTime C.UnderReactivePowerConsumedInhibitTime Under Total Reactive Power Consumed (+kVAR) Inhibit Time USINT 1 1 0 250 387 UVARCTripDelay C.UnderReactivePowerConsumedTripDelay 10 Second s Under Total USINT Reactive Power Consumed (+kVAR) Trip Delay 1 10 1 250 10 Second s 388 UVARCTripLevel C.UnderReactivePowerConsumedTripLimit Under Total DINT Reactive Power Consumed (+kVAR) Trip Level 4 1000 0 2000000000 0 kVAR 389 UVARCWarnLevel C.UnderReactivePowerConsumedWarnLimit Under Total DINT Reactive Power Consumed (+kVAR) Warning Level 4 1000 0 2000000000 0 kVAR 390 OVARCInhibitTime C.OverReactivePowerConsumedInhibitTime Over Total Reactive USINT Power Consumed (+kVAR) Inhibit Time 1 1 0 250 Over Total Reactive USINT Power Consumed (+kVAR) Trip Delay 1 391 464 Parameter Name OVARCTripDelay C.OverReactivePowerConsumedTripDelay 10 Second s Rockwell Automation Publication 193-UM015C-EN-P - November 2013 10 1 250 10 Second s Parameter List Group Power Setup (Continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 392 OVARCTripLevel C.OverReactivePowerConsumedTripLimit Over Total Reactive DINT Power Consumed (+kVAR) Trip Level 4 1000 0 2000000000 0 kVAR 393 OVARCWarnLevel C.OverReactivePowerConsumedWarnLimit Over Total Reactive DINT Power Consumed (+kVAR) Warning Level 4 1000 0 2000000000 0 kVAR 394 UVARGInhibitTime C.UnderReactivePowerGeneratedInhibitTime Under Total USINT Reactive Power Generated (-kVAR) Inhibit Time 1 1 0 250 Under Total USINT Reactive Power Generated (-kVAR) Trip Delay 1 395 UVARGTripDelay C.UnderReactivePowerGeneratedTripDelay 10 Second s 10 1 250 10 Second s 396 UVARGTripLevel C.UnderReactivePowerGeneratedTripLimit Under Total DINT Reactive Power Generated (-kVAR) Trip Level 4 1000 -2000000000 0 0 kVAR 397 UVARGWarnLevel C.UnderReactivePowerGeneratedWarnLimit Under Total DINT Reactive Power Generated (-kVAR) Warning Level 4 1000 -2000000000 0 0 kVAR 398 OVARGInhibitTime C.OverReactivePowerGeneratedInhibitTime Over Total Reactive USINT Power Generated (-kVAR) Inhibit Time 1 1 0 10 Over Total Reactive USINT Power Generated (-kVAR) Trip Delay 1 399 OVARGTripDelay C.OverReactivePowerGeneratedTripDelay 250 Second s 10 1 250 10 Second s 400 OVARGTripLevel C.OverReactivePowerGeneratedTripLimit Over Total Reactive DINT Power Generated (-kVAR) Trip Level 4 1000 -2000000000 0 0 kVAR 401 OVARGWarnLevel C.OverReactivePowerGeneratedWarnLimit Over Total Reactive DINT Power Generated (-kVAR) Warning Level 4 1000 -2000000000 0 0 kVAR 402 UVAInhibitTime C.UnderApparentPowerInhibitTime Under Total Apparent Power Inhibit Time USINT 1 1 0 10 Under Total Apparent Power Trip Delay USINT 403 UVATripDelay C.UnderApparentPowerTripDelay 250 Second s 1 10 1 250 10 Second s 404 UVATripLevel C.UnderApparentPowerTripLimit Under Total Apparent Power Trip Level DINT 4 1000 0 2000000000 0 kVA 405 UVAWarningLevel C.UnderApparentPowerWarnLimit Under Total Apparent Power Warning Level DINT 4 1000 0 2000000000 0 kVA 406 OVAInhibitTime C.OverApparentPowerInhibitTime Over Total Apparent Power Inhibit Time USINT 1 1 0 250 Over Total Apparent Power Trip Delay USINT 407 OVATripDelay 10 Second s 1 10 1 250 10 Second s 408 OVATripLevel C.OverApparentPowerTripDelay Over Total Apparent Power Trip Level DINT 4 1000 0 2000000000 0 kVA 409 OVAWarningLevel C.OverApparentPowerWarnLimit Over Total Apparent Power Warning Level DINT 4 1000 0 2000000000 0 kVA 410 UPFLagInhibTime C.UnderPowerFactorLaggingInhibitTime Under Total Power USINT Factor Lagging (PF) Inhibit Time 1 1 0 250 Under Total Power USINT Factor Lagging (PF) Trip Delay 1 Under Total Power SINT Factor Lagging (PF) Trip Level 1 411 412 UPFLagTripDelay UPFLagTripLevel C.UnderPowerFactorLaggingTripDelay C.UnderPowerFactorLaggingTripLimit 10 Second s 10 1 250 10 Second s Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 -100 0 -90 % 465 Appendix B Group Power Setup (Continued) Parameter List Param No. Description Type Data Size (bytes) Scale Factor Min Max Default Units UPFLagWarnLevel C.UnderPowerFactorLaggingWarnLimit Under Total Power SINT Factor Lagging (PF) Warning Level 1 1 -100 0 -95 414 OPFLagInhibTime C.OverPowerFactorLaggingInhibitTime Over Total Power Factor Lagging (PF) Inhibit Time USINT 1 1 0 250 10 Over Total Power Factor Lagging (PF) Trip Delay USINT OPFLagTripDelay C.OverPowerFactorLaggingTripDelay % Second s 1 10 1 250 10 Second s 416 OPFLagTripLevel C.OverPowerFactorLaggingTripLimit Over Total Power Factor Lagging (PF) Trip Level SINT 1 1 -100 0 -95 % 417 OPFLagWarnLevel C.OverPowerFactorLaggingWarnLimit Over Total Power SINT Factor Lagging (PF) Warning Level 1 1 -100 0 -90 % 418 UPFLeadInhibTime C.UnderPowerFactorLeadingInhibitTime Under Total Power USINT Factor Leading (+PF) Inhibit Time 1 1 0 250 10 Under Total Power USINT Factor Leading (+PF) Trip Delay 1 419 UPFLeadTripDelay C.UnderPowerFactorLeadingTripDelay Second s 10 1 250 10 Second s 420 UPFLeadTripLevel C.UnderPowerFactorLeadingTripLimit Under Total Power USINT Factor Leading (+PF) Trip Level 1 1 0 100 90 % 421 UPFLeadWarnLevel C.UnderPowerFactorLeadingWarnLimit Under Total Power USINT Factor Leading (+PF) Warning Level 1 1 0 100 95 % 422 OPFLeadInhibTime C.OverPowerFactorLeadingInhibitTime Over Total Power USINT Factor Leading (+PF) Inhibit Time 1 1 0 250 10 Over Total Power Factor Leading (+PF) Trip Delay USINT 1 423 466 Device Profile Tag Name 413 415 Diagnostic Display Setup Parameter Name OPFLeadTripDelay C.OverPowerFactorLeadingTripDelay Second s 10 1 250 10 Second s 424 OPFLeadTripLevel C.OverPowerFactorLeadingTripLimit Over Total Power Factor Leading (+PF) Trip Level USINT 1 1 0 100 95 % 425 OPFLeadWarnLevel C.OverPowerFactorLeadingWarnLimit Over Total Power Factor Leading (+PF) Warning Level USINT 1 1 0 100 90 % 426 DemandPeriod C.DemandPeriod The number of minutes in a specific demand period USINT 1 1 1 255 15 Min 427 NumberOfPeriods C.NumberOfDemandPeriods The number of USINT periods to average for the demand calculation 1 1 1 15 1 428 Screen1Param1 C.Screen1ParameterSelect1 Parameter to display on Operator Station Startup screen 1 line 1 UINT 2 1 0 560 1 429 Screen1Param2 C.Screen1ParameterSelect2 Parameter to display on Operator Station Startup screen 1 line 2 UINT 2 1 0 560 50 430 Screen2Param1 C.Screen2ParameterSelect1 Parameter to display on Operator Station Startup screen 2 line 1 UINT 2 1 0 560 2 431 Screen2Param2 C.Screen2ParameterSelect2 Parameter to display on Operator Station Startup screen 2 line 2 UINT 2 1 0 560 3 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Diagnostic Display Setup (Continued) Analog1 Setup Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 432 Screen3Param1 C.Screen3ParameterSelect1 Parameter to display on Operator Station Startup screen 3 line 1 UINT 2 1 0 560 51 433 Screen3Param2 C.Screen3ParameterSelect2 Parameter to display on Operator Station Startup screen 3 line 2 UINT 2 1 0 560 52 434 Screen4Param1 C.Screen4ParameterSelect1 Parameter to display on Operator Station Startup screen 4 line 1 UINT 2 1 0 560 38 435 Screen4Param2 C.Screen4ParameterSelect2 Parameter to display on Operator Station Startup screen 4 line 2 UINT 2 1 0 560 39 436 DisplayTimeout C.OperatorStationDisplayTimeout Inactivity time for UINT a Diagnostic Station 2 1 0 65535 300 437 InAnMod1Ch00Type C.Analog1.Ch00InputRangeType_0 C.Analog1.Ch00InputRangeType_1 C.Analog1.Ch00InputRangeType_2 C.Analog1.Ch00InputRangeType_3 C.Analog1.Ch00InputRangeType_4 Assignment for Analog Module 1 Input Channel 00 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 438 InAMod1Ch0Format C.Analog1.Ch00InputFormat_0 C.Analog1.Ch00InputFormat_1 C.Analog1.Ch00InputFormat_2 Assignment for Analog Module 1 Input Channel 00 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 439 InAMod1C0TmpUnit C.Analog1.Ch00InputTempMode Assignment for USINT Analog Module 1 Input Channel 00 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 440 InAMod1C0FiltFrq C.Analog1.Ch00InputFilter_0 C.Analog1.Ch00InputFilter_1 C.Analog1.Ch00InputFilter_2 Assignment for Analog Module 1 Input Channel 00 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 441 InAMod1C0OpCktSt C.Analog1.Ch00InputOpenWire_0 C.Analog1.Ch00InputOpenWire_1 Indicates Analog Module 1 Input Channel 00 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 442 InAnMod1Ch0RTDEn C.Analog1.Ch00InputTwoWireRTD Enable Analog BOOL Module 1 Input Channel 00 to function with RTD 1 1 0=3-wire 1=2-wire 0 443 InAMod1C0TripDly C.Analog1.Ch00InputTripDelay Analog Module 1 Input Channel 00 Trip Delay USINT 1 10 0 Level (in selected Units) where Analog Input generates a trip UINT 444 InAMod1C0TripLvl C.Analog1.Ch00InputTripLimit 250 10 Second s 2 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 1 0 65535 0 467 Appendix B Group Analog1 Setup (Continued) 468 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max 65535 Default Units 445 InAMod1C0WarnLvl C.Analog1.Ch00InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 0 446 InAnMod1Ch01Type C.Analog1.Ch01InputRangeType_0 C.Analog1.Ch01InputRangeType_1 C.Analog1.Ch01InputRangeType_2 C.Analog1.Ch01InputRangeType_3 C.Analog1.Ch01InputRangeType_4 Assignment for Analog Module 1 Input Channel 01 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 447 InAMod1Ch1Format C.Analog1.Ch01InputFormat_0 C.Analog1.Ch01InputFormat_1 C.Analog1.Ch01InputFormat_2 Assignment for Analog Module 1 Input Channel 01 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 4= PercentRange 0 448 InAMod1C1TmpUnit C.Analog1.Ch01InputTempMode Assignment for USINT Analog Module 1 Input Channel 01 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 449 InAMod1C1FiltFrq C.Analog1.Ch01InputFilter_0 C.Analog1.Ch01InputFilter_1 C.Analog1.Ch01InputFilter_2 Assignment Analog Module 1 Input Channel 01 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 450 InAMod1C1OpCktSt C.Analog1.Ch01InputOpenWire_0 C.Analog1.Ch01InputOpenWire_1 Indicates Analog Module 1 Input Channel 01 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 451 InAnMod1Ch1RTDEn C.Analog1.Ch01InputTwoWireRTD Enable Analog BOOL Module 1 Input Channel 01 to function with RTD 1 1 0=3-wire 1=2-wire 0 452 InAMod1C1TripDly C.Analog1.Ch01InputTripDelay Analog Module 1 Input Channel 01 Trip Delay USINT 1 10 0 250 0 10 Second s 453 InAMod1C1TripLvl C.Analog1.Ch01InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 0 65535 0 454 InAMod1C1WarnLvl C.Analog1.Ch01InputWarnLimit Level (in selected Units) where Analog Input generate UINT 2 1 0 65535 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Analog1 Setup (Continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 455 InAnMod1Ch02Type C.Analog1.Ch02InputRangeType_0 C.Analog1.Ch02InputRangeType_1 C.Analog1.Ch02InputRangeType_2 C.Analog1.Ch02InputRangeType_3 C.Analog1.Ch02InputRangeType_4 Assignment for Analog Module 1 Input Channel 02 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 456 InAMod1Ch2Format C.Analog1.Ch02InputFormat_0 C.Analog1.Ch02InputFormat_1 C.Analog1.Ch02InputFormat_2 Assignment for Analog Module 1 Input Channel 02 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 457 InAMod1C2TmpUnit C.Analog1.Ch02InputTempMode Assignment for USINT Analog Module 1 Input Channel 02 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 458 InAMod1C2FiltFrq C.Analog1.Ch02InputFilter_0 C.Analog1.Ch02InputFilter_1 C.Analog1.Ch02InputFilter_2 Assignment Analog Module 1 Input Channel 02 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 459 InAMod1C2OpCktSt C.Analog1.Ch02InputOpenWire_0 C.Analog1.Ch02InputOpenWire_1 Indicates Analog Module 1 Input Channel 02 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 460 InAnMod1Ch2RTDEn C.Analog1.Ch02InputTwoWireRTD Enable Analog BOOL Module 1 Input Channel 02 to function with RTD 1 1 0=3-wire 1=2-wire 0 461 InAMod1C2TripDly C.Analog1.Ch02InputTripDelay Analog Module 1 Input Channel 02 Trip Delay USINT 1 10 0 250 10 Second s 462 InAMod1C2TripLvl C.Analog1.Ch02InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 0 65535 0 463 InAMod1C2WarnLvl C.Analog1.Ch02InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 0 65535 0 464 OutAnMod1Type C.Analog1.Ch00OutputRangeType_0 C.Analog1.Ch00OutputRangeType_1 C.Analog1.Ch00OutputRangeType_2 C.Analog1.Ch00OutputRangeType_3 Assignment for Analog Module 1 Output function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4=1to5 Volts 5= 0to5 Volts 0 465 OutAnMod1Select C.Analog1.Ch00OutputMode Assignment of parameter data value to drive Analog Module 1 Output USINT 1 1 0= AveragePctFLA 1= ScaledAvgPctFLA 2= PercentTCU 3= GFCurrent 4= CurrentUnbalance 5= AvgLLVoltage 6=VoltLLUnbalance 7= TotalkW 8= TotalkVA 9= TotalkVAR 10= TotalPF 11= UserDLXData 0 466 OutAnMod1FltActn C.Analog1.Ch00OutputFaultMode_0 C.Analog1.Ch00OutputFaultMode_1 Analog Module 1 Output action on comms fault USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= Hold Last State 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 469 Appendix B Group Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units Analog1 Setup (continued) 467 OutAnMod1IdlActn C.Analog1.Ch00OutputProtectionFaultMode_0 C.Analog1.Ch00OutputProtectionFaultMode_1 Analog Module 1 Output action on comms idle USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= Hold Last State 0 Analog2 Setup 468 InAnMod2Ch00Type C.Analog2.Ch00InputRangeType_0 C.Analog2.Ch00InputRangeType_1 C.Analog2.Ch00InputRangeType_2 C.Analog2.Ch00InputRangeType_3 C.Analog2.Ch00InputRangeType_4 Assignment for Analog Module 2 Input Channel 00 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 469 InAMod2Ch0Format C.Analog2.Ch00InputFormat_0 C.Analog2.Ch00InputFormat_1 C.Analog2.Ch00InputFormat_2 Assignment for Analog Module 2 Input Channel 00 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 470 InAMod2C0TmpUnit C.Analog2.Ch00InputTempMode Assignment for USINT Analog Module 2 Input Channel 00 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 471 InAMod2C0FiltFrq C.Analog2.Ch00InputFilter_0 C.Analog2.Ch00InputFilter_1 C.Analog2.Ch00InputFilter_2 Assignment for Analog Module 2 Input Channel 00 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 472 InAMod2C0OpCktSt C.Analog2.Ch00InputOpenWire_0 C.Analog2.Ch00InputOpenWire_1 Indicates Analog Module 2 InputпЂ Channel 00 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 473 InAnMod2Ch0RTDEn C.Analog2.Ch00InputTwoWireRTD Enable Analog BOOL Module 2 InputпЂ Channel 00 to function with RTD 1 1 0=3-wire 1=2-wire 0 474 InAMod2C0TripDly C.Analog2.Ch00InputTripDelay Analog Module 2 Input Channel 00 Trip Delay USINT 1 10 0 470 250 10 Second s 475 InAMod2C0TripLvl C.Analog2.Ch00InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 476 InAMod2C0WarnLvl C.Analog2.Ch00InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Analog2 Setup (Continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 477 InAnMod2Ch01Type C.Analog2.Ch01InputRangeType_0 C.Analog2.Ch01InputRangeType_1 C.Analog2.Ch01InputRangeType_2 C.Analog2.Ch01InputRangeType_3 C.Analog2.Ch01InputRangeType_4 Assignment for Analog Module 2 Input Channel 01 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 478 InAMod2Ch1Format C.Analog2.Ch01InputFormat_0 C.Analog2.Ch01InputFormat_1 C.Analog2.Ch01InputFormat_2 Assignment for Analog Module 2 Input Channel 01 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 479 InAMod2C1TmpUnit C.Analog2.Ch01InputTempMode Assignment for USINT Analog Module 2 Input Channel 01 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 480 InAMod2C1FiltFrq C.Analog2.Ch01InputFilter_0 C.Analog2.Ch01InputFilter_1 C.Analog2.Ch01InputFilter_2 Assignment Analog Module 2 Input Channel 01 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 481 InAMod2C1OpCktSt C.Analog2.Ch01InputOpenWire_0 C.Analog2.Ch01InputOpenWire_1 Indicates Analog Module 2 Input Channel 01 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 482 InAnMod2Ch1RTDEn C.Analog2.Ch01InputTwoWireRTD Enable Analog BOOL Module 2 Input Channel 01 to function with RTD 1 1 0=3-wire 1=2-wire 0 483 InAMod2C1TripDly C.Analog2.Ch01InputTripDelay Analog Module 2 Input Channel 01 Trip Delay USINT 1 10 0 250 10 Second s 484 InAMod2C1TripLvl C.Analog2.Ch01InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 0 65535 0 485 InAMod2C1WarnLvl C.Analog2.Ch01InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 486 InAnMod2Ch02Type C.Analog2.Ch02InputRangeType_0 C.Analog2.Ch02InputRangeType_1 C.Analog2.Ch02InputRangeType_2 C.Analog2.Ch02InputRangeType_3 C.Analog2.Ch02InputRangeType_4 Assignment for Analog Module 2 Input Channel 02 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 471 Appendix B Group Analog2 Setup (continued) 472 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 487 InAMod2Ch2Format C.Analog2.Ch02InputFormat_0 C.Analog2.Ch02InputFormat_1 C.Analog2.Ch02InputFormat_2 Assignment for Analog Module 2 Input Channel 02 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 488 InAMod2C2TmpUnit C.Analog2.Ch02InputTempMode Assignment for USINT Analog Module 2 Input Channel 02 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 489 InAMod2C2FiltFrq C.Analog2.Ch02InputFilter_0 C.Analog2.Ch02InputFilter_1 C.Analog2.Ch02InputFilter_2 Assignment Analog Module 2 Input Channel 02 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 490 InAMod2C2OpCktSt C.Analog2.Ch02InputOpenWire_0 C.Analog2.Ch02InputOpenWire_1 Indicates Analog Module 2 Input Channel 02 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 491 InAnMod2Ch2RTDEn C.Analog2.Ch02InputTwoWireRTD Enable Analog BOOL Module 2 Input Channel 02 to function with RTD 1 1 0=3-wire 1=2-wire 0 492 InAMod2C2TripDly C.Analog2.Ch02InputTripDelay Analog Module 2 Input Channel 02 Trip Delay USINT 1 10 0 250 10 Second s 493 InAMod2C2TripLvl C.Analog2.Ch02InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 494 InAMod2C2WarnLvl C.Analog2.Ch02InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 495 OutAnMod2Type C.Analog2.Ch00OutputRangeType_0 C.Analog2.Ch00OutputRangeType_1 C.Analog2.Ch00OutputRangeType_2 C.Analog2.Ch00OutputRangeType_3 Assignment for Analog Module 2 Output function. USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4=1To5 Volts 5=OTo5 Volts 0 496 OutAnMod2Select C.Analog2.Ch00OutputMode Assignment of parameter data value to drive Analog Module 2 Output USINT 1 1 0= AveragePctFLA 1= ScaledAvgPctFLA 2= PercentTCU 3= GFCurrent 4= CurrentUnbalance 5= AvgLLVoltage 6=VoltLLUnbalance 7= TotalkW 8= TotalkVA 9= TotalkVAR 10= TotalPF 11= UserDLXData 0 497 OutAnMod2EFltAct C.Analog2.Ch00OutputFaultMode_0 C.Analog2.Ch00OutputFaultMode_1 Analog Module 2 Output action on an Expansion Bus fault USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= HoldLastState 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Group Analog3 Setup Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 498 OutAnMod2PFltAct C.Analog2.Ch00OutputProtectionFaultMode_0 C.Analog2.Ch00OutputProtectionFaultMode_1 Analog Module 2 USINT Output action on a protection fault 1 1 0= Ignore 1= Maximum 2= Minimum 3= HoldLastState 0 499 InAnMod3Ch00Type C.Analog3.Ch00InputRangeType_0 C.Analog3.Ch00InputRangeType_1 C.Analog3.Ch00InputRangeType_2 C.Analog3.Ch00InputRangeType_3 C.Analog3.Ch00InputRangeType_4 Assignment for Analog Module 3 Input Channel 00 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 500 InAMod3Ch0Format C.Analog3.Ch00InputFormat_0 C.Analog3.Ch00InputFormat_1 C.Analog3.Ch00InputFormat_2 Assignment for Analog Module 3 Input Channel 00 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 501 InAMod3C0TmpUnit C.Analog3.Ch00InputTempMode Assignment for USINT Analog Module 3 Input Channel 00 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 502 InAMod3C0FiltFrq C.Analog3.Ch00InputFilter_0 C.Analog3.Ch00InputFilter_1 C.Analog3.Ch00InputFilter_2 Assignment for Analog Module 3 Input Channel 00 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 503 InAMod3C0OpCktSt C.Analog3.Ch00InputOpenWire_0 C.Analog3.Ch00InputOpenWire_1 Indicates Analog Module 3 Input Channel 00 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 504 InAnMod3Ch0RTDEn C.Analog3.Ch00InputTwoWireRTD Enable Analog BOOL Module 3 Input Channel 00 to function with RTD 1 1 0=3-wire 1=2-wire 0 505 InAMod3C0TripDly C.Analog3.Ch00InputTripDelay Analog Module 3 Input Channel 00 Trip Delay USINT 1 10 0 250 10 Second s 506 InAMod3C0TripLvl C.Analog3.Ch00InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 507 InAMod3C0WarnLvl C.Analog3.Ch00InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 473 Appendix B Group Analog3 Setup (Continued) 474 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 508 InAnMod3Ch01Type C.Analog3.Ch01InputRangeType_0 C.Analog3.Ch01InputRangeType_1 C.Analog3.Ch01InputRangeType_2 C.Analog3.Ch01InputRangeType_3 C.Analog3.Ch01InputRangeType_4 Assignment for Analog Module 3 Input Channel 01 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 509 InAMod3Ch1Format C.Analog3.Ch01InputFormat_0 C.Analog3.Ch01InputFormat_1 C.Analog3.Ch01InputFormat_2 Assignment for Analog Module 3 Input Channel 01 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 510 InAMod3C1TmpUnit C.Analog3.Ch01InputTempMode Assignment for USINT Analog Module 3 Input Channel 01 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 511 InAMod3C1FiltFrq C.Analog3.Ch01InputFilter_0 C.Analog3.Ch01InputFilter_1 C.Analog3.Ch01InputFilter_2 Assignment Analog Module 3 Input Channel 01 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 512 InAMod3C1OpCktSt C.Analog3.Ch01InputOpenWire_0 C.Analog3.Ch01InputOpenWire_1 Indicates Analog Module 3 Input Channel 01 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 513 InAnMod3Ch1RTDEn C.Analog3.Ch01InputTwoWireRTD Enable Analog BOOL Module 3 Input Channel 01 to function with RTD 1 1 0=3-wire 1=2-wire 0 514 InAMod3C1TripDly C.Analog3.Ch01InputTripDelay Analog Module 3 Input Channel 01 Trip Delay USINT 1 10 0 250 10 Second s 515 InAMod3C1TripLvl C.Analog3.Ch01InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 516 InAMod3C1WarnLvl C.Analog3.Ch01InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 517 InAnMod3Ch02Type C.Analog3.Ch02InputRangeType_0 C.Analog3.Ch02InputRangeType_1 C.Analog3.Ch02InputRangeType_2 C.Analog3.Ch02InputRangeType_3 C.Analog3.Ch02InputRangeType_4 Assignment for Analog Module 3 Input Channel 02 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm Rockwell Automation Publication 193-UM015C-EN-P - November 2013 0 Parameter List Group Analog3 Setup (continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 518 InAMod3Ch2Format C.Analog3.Ch02InputFormat_0 C.Analog3.Ch02InputFormat_1 C.Analog3.Ch02InputFormat_2 Assignment for Analog Module 3 Input Channel 02 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 519 InAMod3C2TmpUnit C.Analog3.Ch02InputTempMode Assignment for USINT Analog Module 3 Input Channel 02 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 520 InAMod3C2FiltFrq C.Analog3.Ch02InputFilter_0 C.Analog3.Ch02InputFilter_1 C.Analog3.Ch02InputFilter_2 Indicates Analog Module 3 Input Channel 02 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 521 InAMod3C2OpCktSt C.Analog3.Ch02InputOpenWire_0 C.Analog3.Ch02InputOpenWire_1 Indicates Analog Module 3 Input Channel 02 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 522 InAnMod3Ch2RTDEn C.Analog3.Ch02InputTwoWireRTD Enable Analog BOOL Module 3 Input Channel 02 to function with RTD 1 1 0=3-wire 1=2-wire 0 523 InAMod3C2TripDly C.Analog3.Ch02InputTripDelay Analog Module 3 Input Channel 02 Trip Delay USINT 1 10 0 250 10 Second s 524 InAMod3C2TripLvl C.Analog3.Ch02InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 525 InAMod3C2WarnLvl C.Analog3.Ch02InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 526 OutAnMod3Type C.Analog3.Ch00OutputRangeType_0 C.Analog3.Ch00OutputRangeType_1 C.Analog3.Ch00OutputRangeType_2 C.Analog3.Ch00OutputRangeType_3 Assignment for Analog Module 3 Output function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4=1to5 Volts 5=0to5 Volts 0 527 OutAnMod3Select C.Analog3.Ch00OutputMode Assignment of parameter data value to drive Analog Module 3 Output USINT 1 1 0= AveragePctFLA 1= ScaledAvgPctFLA 2= PercentTCU 3= GFCurrent 4= CurrentUnbalance 5= AvgLLVoltage 6=VoltLLUnbalance 7= TotalkW 8= TotalkVA 9= TotalkVAR 10= TotalPF 11= UserDLXData 0 528 OutAnMod3EFltAct C.Analog3.Ch00OutputFaultMode_0 C.Analog3.Ch00OutputFaultMode_1 Analog Module 3 Output action on an Expansion Bus fault USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= HoldLastState 0 529 OutAnMod3PFltAct C.Analog3.Ch00OutputProtectionFaultMode_0 C.Analog3.Ch00OutputProtectionFaultMode_1 Analog Module 3 USINT Output action on a protection fault 1 1 0= Ignore 1= Maximum 2= Minimum 3= HoldLastState 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 475 Appendix B Group Analog4 Setup 476 Parameter List Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Default Units 530 InAnMod4Ch00Type C.Analog4.Ch00InputRangeType_0 C.Analog4.Ch00InputRangeType_1 C.Analog4.Ch00InputRangeType_2 C.Analog4.Ch00InputRangeType_3 C.Analog4.Ch00InputRangeType_4 Assignment for Analog Module 4 Input Channel 00 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 531 InAMod4Ch0Format C.Analog4.Ch00InputFormat_0 C.Analog4.Ch00InputFormat_1 C.Analog4.Ch00InputFormat_2 Assignment for Analog Module 4 Input Channel 00 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 532 InAMod4C0TmpUnit C.Analog4.Ch00InputTempMode Assignment for USINT Analog Module 4 Input Channel 00 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 533 InAMod4C0FiltFrq C.Analog4.Ch00InputFilter_0 C.Analog4.Ch00InputFilter_1 C.Analog4.Ch00InputFilter_2 Assignment for Analog Module 4 Input Channel 00 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 534 InAMod4C0OpCktSt C.Analog4.Ch00InputOpenWire_0 C.Analog4.Ch00InputOpenWire_1 Indicates Analog Module 4 Input Channel 00 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 535 InAnMod4Ch0RTDEn C.Analog4.Ch00InputTwoWireRTD Enable Analog BOOL Module 4 Input Channel 00 to function with RTD 1 1 0=3-wire 1=2-wire 0 536 InAMod4C0TripDly C.Analog4.Ch00InputTripDelay Analog Module 4 Input Channel 00 Trip Delay USINT 1 10 0 250 10 Second s 537 InAMod4C0TripLvl C.Analog4.Ch00InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 538 InAMod4C0WarnLvl C.Analog4.Ch00InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 539 InAnMod4Ch01Type C.Analog4.Ch01InputRangeType_0 C.Analog4.Ch01InputRangeType_1 C.Analog4.Ch01InputRangeType_2 C.Analog4.Ch01InputRangeType_3 C.Analog4.Ch01InputRangeType_4 Assignment for Analog Module 4 Input Channel 01 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm Rockwell Automation Publication 193-UM015C-EN-P - November 2013 0 Parameter List Group Analog4 Setup (continued) Param No. Parameter Name Device Profile Tag Name Description Type Data Size (bytes) Scale Factor Min Max Appendix B Default Units 540 InAMod4Ch1Format C.Analog4.Ch01InputFormat_0 C.Analog4.Ch01InputFormat_1 C.Analog4.Ch01InputFormat_2 Assignment for Analog Module 4 Input Channel 01 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 541 InAMod4C1TmpUnit C.Analog4.Ch01InputTempMode Module 4 Input USINT Channel 01 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 542 InAMod4C1FiltFrq C.Analog4.Ch01InputFilter_0 C.Analog4.Ch01InputFilter_1 C.Analog4.Ch01InputFilter_2 Assignment Analog Module 4 Input Channel 01 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 543 InAMod4C1OpCktSt C.Analog4.Ch01InputOpenWire_0 C.Analog4.Ch01InputOpenWire_1 Indicates Analog Module 4 Input Channel 01 Open Circuit State USINT 1 1 0=Upscale 1=Downscale 2=Zero 0 544 InAnMod4Ch1RTDEn C.Analog4.Ch01InputTwoWireRTD Enable Analog BOOL Module 4Input Channel 01 to function with RTD 1 1 0=3-wire 1=2-wire 0 545 InAMod4C1TripDly C.Analog4.Ch01InputTripDelay Analog Module 4 Input Channel 01 Trip Delay USINT 1 10 0 250 10 Second s 546 InAMod4C1TripLvl C.Analog4.Ch01InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 547 InAMod4C1WarnLvl C.Analog4.Ch01InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 548 InAnMod4Ch02Type C.Analog4.Ch02InputRangeType_0 C.Analog4.Ch02InputRangeType_1 C.Analog4.Ch02InputRangeType_2 C.Analog4.Ch02InputRangeType_3 C.Analog4.Ch02InputRangeType_4 Assignment for Analog Module 4 Input Channel 02 function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 6= 100Pt385 7= 200Pt385 8= 500Pt385 9= 1000Pt385 10=100Pt3916 11= 200Pt3916 12= 500Pt3916 13= 1000Pt3916 14= 10Cu426 15= 120Ni618 16= 120Ni672 17= 604NiFe518 18= 150ohm 19= 1000ohm 20 = 3000ohm 21= 6000ohm 0 549 InAMod4Ch2Format C.Analog4.Ch02InputFormat_0 C.Analog4.Ch02InputFormat_1 C.Analog4.Ch02InputFormat_2 Assignment for Analog Module 4 Input Channel 02 Data Format USINT 1 1 0= EngUnits 1= EngUnitsTimes10 2= RawProportional 3= ScaledForPID 0 550 InAMod4C2TmpUnit C.Analog4.Ch02InputTempMode Assignment for USINT Analog Module 4 Input Channel 02 Temperature Units 1 1 0=DegreesC 1=DegreesF 0 551 InAMod4C2FiltFrq C.Analog4.Ch02InputFilter_0 C.Analog4.Ch02InputFilter_1 C.Analog4.Ch02InputFilter_2 Indicates Analog Module 4 Input Channel 02 Filter Freq USINT 1 1 0=17Hz 1=4Hz 2=62Hz 3=470Hz 0 552 InAMod4C2OpCktSt C.Analog4.Ch02InputOpenWire_0 C.Analog4.Ch02InputOpenWire_1 Indicates Analog Module 4 Input Channel 02 Open Circuit State USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= HoldLastState 0 553 InAnMod4Ch2RTDEn C.Analog4.Ch02InputTwoWireRTD Enable Analog BOOL Module 4 Input Channel 02 to function with RTD 1 1 0=Disable 1=Enable 0 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 477 Appendix B Group Analog4 Setup (continued) 478 Parameter List Param No. 554 Parameter Name InAMod4C2TripDly Device Profile Tag Name C.Analog4.Ch02InputTripDelay Description Type Analog Module 4 Input Channel 02 Trip Delay USINT Data Size (bytes) 1 Scale Factor 10 Min 0 Max 250 Default Units 10 Second s 555 InAMod4C2TripLvl C.Analog4.Ch02InputTripLimit Level (in selected Units) where Analog Input generates a trip UINT 2 1 -32768 32767 0 556 InAMod4C2WarnLvl C.Analog4.Ch02InputWarnLimit Level (in selected Units) where Analog Input generates a warning UINT 2 1 -32768 32767 0 557 OutAnMod4Type C.Analog4.Ch00OutputRangeType_0 C.Analog4.Ch00OutputRangeType_1 C.Analog4.Ch00OutputRangeType_2 C.Analog4.Ch00OutputRangeType_3 Assignment for Analog Module 4 Output function USINT 1 1 0= Disabled 1= 4To20mA 2= 0To20mA 3= 0To10Volts 4= 1To5Volts 5= 0To5Volts 0 558 OutAnMod4Select C.Analog4.Ch00OutputMode Assignment of parameter data value to drive Analog Module 4 Output USINT 1 1 0= AveragePctFLA 1= ScaledAvgPctFLA 2= PercentTCU 3= GFCurrent 4= CurrentUnbalance 5= AvgLLVoltage 6=VoltLLUnbalance 7= TotalkW 8= TotalkVA 9= TotalkVAR 10= TotalPF 11= UserDLXData 0 559 OutAnMod4EFltAct C.Analog4.Ch00OutputFaultMode_0 C.Analog4.Ch00OutputFaultMode_1 Analog Module 4 Output action on an Expansion Bus fault USINT 1 1 0= Zero 1= Maximum 2= Minimum 3= HoldLastState 0 560 OutAnMod4PFltAct C.Analog4.Ch00OutputProtectionFaultMode_0 C.Analog4.Ch00OutputProtectionFaultMode_1 Analog Module 4 USINT Output action on a protection fault 1 1 0= Zero 1= Maximum 2= Minimum 3= HoldLastState 0 Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Parameter List Appendix B Notes: Rockwell Automation Publication 193-UM015C-EN-P - December 2014 479 Appendix B 480 Parameter List Rockwell Automation Publication 193-UM015C-EN-P - November 2013 Appendix C EtherNet/IP Information Common Industrial Protocol (CIP) Objects The E300 Electronic Overload Relay’s EtherNet/IP Communication Module supports the following Common Industrial Protocol (CIP). Table 521 - CIP Object Classes Class Object 0x0001 Identity 0x0002 Message Router 0x0003 DeviceNet 0x0004 Assembly 0x0005 Connection 0x0008 Discrete Input Point 0x0009 Discrete Output Point 0x000A Analog Input Point 0x000F Parameter Object 0x0010 Parameter Group Object 0x001E Discrete Output Group 0x0029 Control Supervisor 0x002B Acknowledge Handler 0x002C Overload Object 0x004E Base Energy Object 0x004F Electrical Energy Object 0x008B Wall Clock Time Object 0x0097 DPI Fault Object 0x0098 DPI Warning Object 0x00C2 MCC Object Rockwell Automation Publication 193-UM015C-EN-P - December 2014 481 Appendix C EtherNet/IP Information Identity Object — CLASS CODE 0x0001 The following three instances of the Identity Object are supported: Table 522 - Identity Object Instances Instance 1 2 3 Name Operating System Flash Boot code Flash Sensing Module Revision Attribute The firmware rev of the Control firmware stored in flash memory The firmware rev of the Boot Code stored in flash memory The firmware rev of the Sensing Module firmware The following class attributes are supported for the Identity Object: Table 523 - Identity Object Class Attributes Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 1 Instance 1 of the Identity Object contains the following attributes: Table 524 - Identity Object Instance 1 Attributes 482 Attribute ID 1 2 3 Access Rule Get Get Get 4 Get Name Vendor Device Type Product Code Revision Major Revision Minor Revision Data Type UINT UINT UINT Structure of: USINT USINT 5 Get Status WORD 6 Get 7 Get 8 Get Serial Number Product Name String Length ASCII String State UDINT Structure of: USINT STRING USINT 9 Get Configuration Consistency Value UINT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value 1 = Allen-Bradley 3 651 Firmware revision of the Control firmware Bit 0 – 0=not owned; 1=owned by master Bit 2 – 0=Factory Defaulted; 1=Configured Bits 4-7 – Extended Status (see Table 525) Bit 8 – Minor Recoverable fault Bit 9 – Minor Unrecoverable fault Bit 10 – Major Recoverable fault Bit 11 – Major Unrecoverable fault unique number for each device “193-EIO Application” See CIP Common Spec 16 bit CRC or checksum of all data included in the following data sets: Parameter included in the configuration assembly MCC Object configuration data DeviceLogix program data Base Energy Object attribute 16 EtherNet/IP Information Appendix C Table 525 - Extended Device Status Field (bits 4-7) in “Status” Instance Attribute 5 Value 0 1 2 3 4 5 6 7 Description Self-Testing or Unknown Firmware Update in Progress At least one faulted I/O connection No I/O connections established Nonvolatile Configuration bad Major Fault – either bit 10 or bit 11 is true (1) At least one I/O connection in run mode At least one I/O connection established, all in idle mode Instance 2 of the Identity Object contains the following attributes: Table 526 - Identity Object Instance 2 Attributes Attribute ID 1 2 3 Access Rule Get Get Get 4 Get Name Vendor Device Type Product Code Revision Major Revision Minor Revision Data Type UINT UINT UINT Structure of: USINT USINT 5 Get Status WORD 6 Get 7 Get 8 Get Serial Number Product Name String Length ASCII String State UDINT Structure of: USINT STRING USINT 9 Get Configuration Consistency Value UINT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value 1 = Allen-Bradley 3 651 Firmware revision of the Boot Code Bit 0 – 0=not owned; 1=owned by master Bit 2 – 0=Factory Defaulted; 1=Configured Bits 4-7 – Extended Status (see Table 525) Bit 8 – Minor Recoverable fault Bit 9 – Minor Unrecoverable fault Bit 10 – Major Recoverable fault Bit 11 – Major Unrecoverable fault unique number for each device “193-EIO Boot Code” See CIP Common Spec 16 bit CRC or checksum of all data included in the following data sets: Parameter included in the configuration assembly MCC Object configuration data DeviceLogix program data Base Energy Object attribute 16 483 Appendix C EtherNet/IP Information Instance 3 of the Identity Object contains the following attributes: Table 527 - Identity Object Instance 3 Attributes Attribute ID 1 2 3 Access Rule Get Get Get 4 Get Name Vendor Device Type Product Code Revision Major Revision Minor Revision Data Type UINT UINT UINT Structure of: USINT USINT 5 Get Status WORD 6 Get 7 Get 8 Get Serial Number Product Name String Length ASCII String State UDINT Structure of: USINT STRING USINT 9 Get Configuration Consistency Value UINT Value 1 = Allen-Bradley 3 651 Firmware revision of the Sensing Module firmware Bit 0 – 0=not owned; 1=owned by master Bit 2 – 0=Factory Defaulted; 1=Configured Bits 4-7 – Extended Status (see Table 525) Bit 8 – Minor Recoverable fault Bit 9 – Minor Unrecoverable fault Bit 10 – Major Recoverable fault Bit 11 – Major Unrecoverable fault unique number for each device “193-EIO Sensing Module” See CIP Common Spec 16 bit CRC or checksum of all data included in the following data sets: Parameter included in the configuration assembly MCC Object configuration data DeviceLogix program data Base Energy Object attribute 16 The following common services are implemented for the Identity Object. Table 528 - Identity Object Common Services Service Code Implemented for: Service Name Class Instance 0x0E No Yes Get_Attribute_Single 0x05 No Yes Reset Message Router — CLASS CODE 0x0002 No class or instance attributes are supported. The message router object exists only to rout explicit messages to other objects. Assembly Object — CLASS CODE 0x0004 The following class attributes are supported for the Assembly Object: 484 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Appendix C Table 529 - Assembly Object Class Attributes Attribute ID Access Rule Name Data Type Value 2 Get Max. Instance UINT 199 The following static assembly instance attributes are supported for each assembly instance. Table 530 - Assembly Instance Attributes Attribute ID Access Rule 1 Get 2 Get 3 4 100 Conditional Get Get Name Number of Members in Member List Member List Member Data Description Member Path Size Member Path Data Size Name String Data Type Value UINT Array of STRUCT Array of CIP paths UINT Size of Member Data in bits UINT Packed EPATH Array of BYTE UINT STRING Size of Member Path in bytes Member EPATHs for each assembly instance Number of bytes in attribute 3 The following services are implemented for the Assembly Object. Table 531 - Assembly Object Services Service Code Implemented for: Service Name Class Instance 0x0E Yes Yes Get_Attribute_Single 0x10 No Yes Set_Attribute_Single The following table summarizes the various instances of the Assembly Object that are implemented: Table 532 - Assembly Object Instance Summary Inst 2 50 120 144 198 199 Type Consumed Produced Config Consumed Produced Produced Name Trip Reset Cmd Trip Status Configuration E300 Consumed Current Diags All Diags Description Required ODVA Consumed Instance Required ODVA Produced Instance Configuration Assembly Default Consumed Assembly Produced Assembly with Current Diagnostics Only Default Produced Assembly Instance 2 The following table summarizes Attribute 3 Format: Rockwell Automation Publication 193-UM015C-EN-P - December 2014 485 Appendix C EtherNet/IP Information Table 533 - Instance 2 — Basic Overload Output Assembly from ODVA Profile Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Fault Reset Bit 0 Table 534 - Instance 2 Attributes Attribute ID Access Rule Member Index Name 1 Get Number of Members in Member List Member List Member Data Description 0 Member Path Size 2 Get Member Path Member Data Description 1 Member Path Size Member Path 3 Set Data 4 Get Size 100 Get Name Data Type UINT Array of STRUCT UINT UINT Packed EPATH UINT UINT Packed EPATH UINT UINT SHORT_STRING Value 2 2 0 1 12 6BH and “Fault Reset” See data format above 1 “Trip Reset Cmd” Instance 50 The following table summarizes Attribute 3 Format: Table 535 - Instance 50 — Basic Overload Input Assembly from ODVA Overload Profile Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Tripped Table 536 - Instance 50 Attributes Attribute ID Access Rule Member Index Name 1 Get Number of Members in Member List Member List Member Data Description 2 Get 0 Member Path Size Member Path 3 Get Data 4 Get Size 100 Get Name Data Type UINT Array of STRUCT UINT UINT Packed EPATH UINT UINT SHORT_STRING Value 1 1 8 67H and “Tripped” See data format above 1 “Trip Status” Instance 120 - Configuration Assembly Revision 2 The following table shows Attribute 3 Format and Attribute 2 Member List for revision 2 of the assembly. Table 537 - Instance 120 — Configuration Assembly INT 0 1 486 DINT 15 14 13 ConfigAssyRev = 2 0 Reserved 12 11 10 9 8 7 6 5 4 SetOperatingMode Rockwell Automation Publication 193-UM015C-EN-P - December 2014 3 2 1 0 Size (bits) 16 8 8 Param 1100 195 1102 EtherNet/IP Information INT 2 3 4 5 DINT 15 14 13 12 11 10 9 8 4 3 2 1 0 Size (bits) Param 32 171 2 FLA2Setting 32 177 8 1 1 1 1 1 1 2 8 8 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 8 8 4 3 3 3 3 2 2 2 2 8 172 173 176 247 248 364 377 1101 174 175 183 189 184 190 185 191 186 192 187 193 139 145 140 146 141 147 142 148 143 149 233 221 222 224 225 226 227 228 229 230 231 232 N/A X 6 X 3 X X X X 7 4 5 6 7 8 9 10 11 12 13 TripClass OLPTCResetMode SingleOrThreePh GFFilter GFMaxInghibit PhaseRotTrip PowerScale Reserved OLResetLevel OLWarningLevel TripEnableI WarningEnableI TripEnableV WarningEnableV TripEnableP WarningEnableP TripEnableC WarningEnableC TripEnableA WarningEnableA TripHistoryMaskI WarnHistoryMaskI TripHistoryMaskV WarnHistoryMaskV TripHistoryMaskP WarnHistoryMaskP TripHistoryMaskC WarnHistoryMaskC TripHistoryMaskA WarnHistoryMaskA MismatchAction 14 ControlModuleTyp SensingModuleTyp X 30 X X 15 31 5 FLASetting X 29 6 1 X 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 7 Appendix C X X X AnalogMod1Type AnalogMod2Type AnalogMod3Type AnalogMod4Type Reserved X X X X X X X X X X Rockwell Automation Publication 193-UM015C-EN-P - December 2014 OperStationType DigitalMod1Type DigitalMod2Type DigitalMod3Type DigitalMod4Type X X X X 487 Appendix C EtherNet/IP Information INT DINT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 Language 1 OutAAssignment 32 OuBAssignment 16 OutCAssignment InPt00Assignment InPt01Assignment 33 InPt02Assignment InPt03Assignment InPt04Assignment InPt05Assignment 34 17 X 18 19 20 21 43 22 23 47 25 26 JamInhibitTime JamTripDelay JamTripLevel JamWarningLevel ULTripDelay ULTripLevel ULWarningLevel CIInhibitTime 54 27 55 28 CITripDelay CITripLevel CIWarningLevel CTPrimary CTSecondary UCInhibitTime 58 29 488 StallEnabledTime ULInhibitTime 53 59 PLTripDelay 24 52 56 57 GFTripDelay GFWarningDelay GFTripLevel GFWarningLevel Reserved StallTripLevel 48 50 51 GFInhibitTime PLInhibitTime 46 49 Reserved StartsInterval PMTotalStarts PMOperatingHours FeedbackTimeout TransitionDelay InterlockDelay GroundFaultType 42 44 45 X StartsPerHour 35 36 37 38 39 40 41 X ActFLA2wOutput X EmergencyStartEn Reserved L1UCTripDelay L1UCTripLevel L1UCWarningLevel Rockwell Automation Publication 193-UM015C-EN-P - December 2014 0 Size (bits) 4 4 4 4 4 4 4 4 4 4 4 4 4 8 8 16 16 16 16 16 16 8 8 8 8 16 16 8 8 8 8 16 8 8 16 16 8 8 8 8 8 8 8 8 16 16 8 8 8 8 Param 212 202 203 204 196 197 198 199 200 201 209 216 N/A 205 N/A 206 207 208 213 214 215 241 242 243 245 244 246 239 240 249 N/A 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 EtherNet/IP Information INT DINT 15 60 30 61 13 12 11 10 9 8 7 6 5 L2UCTripDelay 4 L2UCTripLevel L2UCWarningLevel L3UCTripDelay L3UCTripLevel 62 31 63 L3UCWarningLevel OCInhibitTime L1OCTripDelay L1OCTripLevel 64 32 65 L1OCWarningLevel L2OCTripDelay L2OCTripLevel L2OCWarningLevel 66 33 67 L3OCTripDelay L3OCTripLevel L3OCWarningLevel LineLossInhTime 68 34 69 70 71 72 73 74 75 76 77 14 35 36 37 38 L1LossTripDelay L2LossTripDelay L3LossTripDelay Datalink0 Datalink1 Datalink2 Datalink3 Datalink4 Datalink5 Datalink6 Datalink7 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 3 2 1 0 Size (bits) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 16 16 16 16 16 16 16 16 Appendix C Param 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 291 292 293 294 295 296 297 298 489 Appendix C EtherNet/IP Information INT 78 DINT 15 14 13 OutPt00PrFltAct OutPt00PrFltVal OutPt00ComFltAct OutPt00ComFltVal OutPt00ComIdlAct OutPt00ComIdlVal OutPt01PrFltAct OutPt01PrFltVal 12 11 10 9 8 X X X OutPt02ComIdlAct OutPt02ComIdlVal OutDig1PrFltAct OutDig1PrFltVal OutDig1ComFltAct OutDig1ComFltVal OutDig1ComIdlAct OutDig1ComIdlVal 0 X X X OutPt01ComFltAct OutPt01ComFltVal OutPt01ComIdlAct OutPt01ComIdlVal OutPt02PrFltAct OutPt02PrFltVal OutPt02ComFltAct OutPt02ComFltVal X X X X X X X X X X X X X OutDig3ComFltAct OutDig3ComFltVal OutDig3ComIdlAct OutDig3ComIdlVal OutDig4PrFltAct OutDig4PrFltVal OutDig4ComFltAct OutDig4ComFltVal X OutDig2PrFltAct OutDig2PrFltVal OutDig2ComFltAct OutDig2ComFltVal OutDig2ComIdlAct OutDig2ComIdlVal OutDig3PrFltAct OutDig3PrFltVal X X X X X X X X X X 490 1 X X 41 2 X X 81 82 83 3 X X 40 4 X X 80 5 X X 79 6 X X 39 7 X X OutDig4ComIdlAct OutDig4ComIdlVal CommOverride NetworkOverride Reserved PtDevOutCOSMask PTPrimary PTSecondary Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Size (bits) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 16 16 16 Param 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 N/A 350 353 354 EtherNet/IP Information INT DINT 15 OWTripDelay Size (bits) 8 8 8 8 16 16 8 8 16 16 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 Param 352 363 355 356 357 358 359 360 361 362 365 366 367 368 369 370 371 372 373 374 375 376 426 427 378 379 382 383 50 UWTripLevel 32 380 51 UWWarningLevel 32 381 52 OWTripLevel 32 384 53 OWWarningLevel 32 385 OVARCTripDelay 8 8 8 8 386 387 390 391 55 UVARCTripLevel 32 388 56 UVARCWarnLevel 32 389 57 OVARCTripLevel 32 392 58 OVARCWarnLevel 32 393 84 42 85 86 87 88 43 11 10 9 8 7 6 5 VoltageMode 4 UVInhibitTime UVTripDelay UVTripLevel UVWarningLevel OVTripDelay OVTripLevel OVWarningLevel VUBInhibitTime VUBTripDelay VUBTripLevel 46 93 VUBWarningLevel UFInhibitTime UFTripDelay UFTripLevel 94 47 95 UFWarningLevel OFInhibitTime OFTripDelay OFTripLevel 96 48 97 OFWarningLevel DemandPeriod NumberOfPeriods UWInhibitTime 98 49 99 UWTripDelay OWInhibitTime UVARCInhibitTime 108 54 109 110 111 112 113 114 115 116 117 12 PhRotInhibitTime 45 92 100 101 102 103 104 105 106 107 13 OVInhibitTime 44 89 90 91 14 UVARCTripDelay OVARCInhibitTime Rockwell Automation Publication 193-UM015C-EN-P - December 2014 3 2 1 0 Appendix C 491 Appendix C EtherNet/IP Information INT DINT 15 OVARGTripDelay Size (bits) 8 8 8 8 Param 394 395 398 399 60 UVARGTripLevel 32 396 61 UVARGWarnLevel 32 397 62 OVARGTripLevel 32 400 63 OVARGWarnLevel 32 401 OVATripDelay 8 8 8 8 402 403 406 407 65 UVATripLevel 32 404 66 UVAWarningLevel 32 405 67 OVATripLevel 32 408 68 OVAWarningLevel 32 409 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 16 16 16 16 16 16 16 16 16 16 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 428 429 430 1103 1103 1103 1103 1103 1103 1103 118 59 119 120 121 122 123 124 125 126 127 64 129 69 139 11 10 9 8 7 6 5 UVARGInhibitTime 4 UVARGTripDelay OVARGInhibitTime UVATripDelay OVAInhibitTime UPFLagTripDelay UPFLagTripLevel UPFLagWarnLevel OPFLagInhibTime 140 70 141 OPFLagTripDelay OPFLagTripLevel OPFLagWarnLevel UPFLeadInhibTime 142 71 143 UPFLeadTripDelay UPFLeadTripLevel UPFLeadWarnLevel OPFLeadInhibTime 144 72 145 492 12 UPFLagInhibTime 138 146 147 148 149 150 151 152 153 154 155 13 UVAInhibitTime 128 130 131 132 133 134 135 136 137 14 73 74 75 76 77 OPFLeadTripDelay OPFLeadTripDelay OPFLeadWarnLevel Screen1Param1 Screen1Param2 Screen1Param3 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Rockwell Automation Publication 193-UM015C-EN-P - December 2014 3 2 1 0 EtherNet/IP Information INT DINT 15 156 78 157 158 159 160 161 162 163 79 80 81 14 13 12 11 10 9 8 7 6 5 InAMod1C0TripDly 4 3 2 1 0 X X InAMod1C1TripDly InAMod1C2TripDly Reserved InAMod1C0TripLvl InAMod1C0WarnLvl InAMod1C1TripLvl InAMod1C1WarnLvl InAMod1C2TripLvl InAMod1C2WarnLvl InAnMod1Ch00Type InAnMod1Ch01Type 164 82 X InAnMod1Ch02Type Reserved X 165 X X X X InAMod1Ch1Format InAMod1C1FiltFrq InAMod1C1OpCktSt 166 83 167 X X X X 84 169 170 171 172 173 174 175 85 86 87 X X X X InAMod1C0TmpUnit InAnMod1Ch0RTDEn InAMod1C1TmpUnit InAnMod1Ch1RTDEn InAMod1C2TmpUnit InAnMod1Ch2RTDEn OutAnMod1FltActn X X X X X InAMod1Ch2Format InAMod1C2FiltFrq InAMod1C2OpCktSt X X X X X X X X OutAnMod1Select InAMod1Ch0Format InAMod1C0FiltFrq InAMod1C0OpCktSt X X 168 X X X X X X X X X X OutAnMod1IdlActn OutAnMod1Type Reserved InAMod2C0TripDly InAMod2C1TripDly InAMod2C2TripDly Reserved InAMod2C0TripLvl InAMod2C0WarnLvl InAMod2C1TripLvl InAMod2C1WarnLvl InAMod2C2TripLvl InAMod2C2WarnLvl Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Size (bits) 8 8 8 8 16 16 16 16 16 16 5 5 5 1 8 3 3 2 3 3 2 3 3 2 1 1 1 1 1 1 2 2 4 2 8 8 8 8 16 16 16 16 16 16 Appendix C Param 443 452 461 1102 444 445 453 454 462 463 437 446 455 1101 465 438 440 441 447 449 450 456 458 459 439 442 448 451 457 460 466 467 464 1101 474 483 492 1102 475 476 484 485 493 494 493 Appendix C EtherNet/IP Information INT DINT 15 14 13 12 11 10 9 7 6 5 4 3 2 1 InAnMod2Ch00Type 88 X InAnMod2Ch02Type Reserved X 177 X X X X InAMod2Ch1Format InAMod2C1FiltFrq InAMod2C1OpCktSt 178 89 179 X X X X X 90 181 91 92 93 X X X X InAMod2C0TmpUnit InAnMod2Ch0RTDEn InAMod2C1TmpUnit InAnMod2Ch1RTDEn InAMod2C2TmpUnit InAnMod2Ch2RTDEn OutAnMod2FltActn X OutAnMod2Select InAMod2Ch0Format InAMod2C0FiltFrq InAMod2C0OpCktSt X X X X X X X X X X X X X X OutAnMod2dlActn OutAnMod2Type Reserved InAMod3C0TripDly InAMod3C2TripDly Reserved InAMod3C0TripLvl InAMod3C0WarnLvl InAMod3C1TripLvl InAMod3C1WarnLvl InAMod3C2TripLvl InAMod3C2WarnLvl InAnMod3Ch00Type InAnMod3Ch01Type 94 X InAnMod3Ch02Type Reserved X 189 X X X X X X InAMod2Ch2Format InAMod2C2FiltFrq InAMod2C2OpCktSt InAMod3C1TripDly 188 X X X X 180 X X X X 494 0 InAnMod2Ch01Type 176 182 183 184 185 186 187 8 X X X X OutAnMod3Select InAMod3Ch0Format InAMod3C0FiltFrq InAMod3C0OpCktSt Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Size (bits) 5 5 5 1 8 3 3 2 3 3 2 3 3 2 1 1 1 1 1 1 2 2 4 2 8 8 8 8 16 16 16 16 16 16 5 5 5 1 8 3 3 2 Param 468 477 486 1101 496 469 471 472 478 480 481 487 489 490 470 473 479 482 488 491 497 498 495 1101 505 514 523 1102 506 507 515 516 524 525 499 508 517 N/A 527 500 502 503 EtherNet/IP Information INT 190 DINT 15 14 13 12 InAMod3Ch1Format InAMod3C1FiltFrq InAMod3C1OpCktSt 11 10 X 95 191 X X X X InAMod3C0TmpUnit InAnMod3Ch0RTDEn InAMod3C1TmpUnit InAnMod3Ch1RTDEn InAMod3C2TmpUnit InAnMod3Ch2RTDEn OutAnMod3FltActn 9 X X 192 96 193 194 195 196 197 198 199 97 98 99 X X X 7 6 5 4 3 X X X 2 X 1 X 0 X X X InAMod3Ch2Format InAMod3C2FiltFrq InAMod3C2OpCktSt X X X X X X X 8 X X X X X X X OutAnMod3dlActn OutAnMod3Type Reserved InAMod4C0TripDly InAMod4C1TripDly InAMod4C2TripDly Reserved InAMod4C0TripLvl InAMod4C0WarnLvl InAMod4C1TripLvl InAMod4C1WarnLvl InAMod4C2TripLvl InAMod4C2WarnLvl InAnMod4Ch00Type InAnMod4Ch01Type 200 100 InAnMod4Ch02Type Reserved X 201 X X X X InAMod4Ch1Format InAMod4C1FiltFrq InAMod4C1OpCktSt 202 X X X X InAMod3C0TmpUnit InAnMod4Ch0RTDEn InAMod4C1TmpUnit InAnMod4Ch1RTDEn InAMod4C2TmpUnit InAnMod4Ch2RTDEn OutAnMod4FltActn X X X X OutAnMod4Select InAMod4Ch0Format InAMod4C0FiltFrq InAMod4C0OpCktSt X X X X X X X X InAMod4Ch2Format InAMod4C2FiltFrq InAMod4C2OpCktSt X X X X X X X X X X X X X X 101 203 X X X X X X OutAnMod4dlActn OutAnMod4Type Reserved Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Size (bits) 3 3 2 3 3 2 1 1 1 1 1 1 2 2 4 2 8 8 8 8 16 16 16 16 16 16 5 5 5 1 8 3 3 2 3 3 2 3 3 2 1 1 1 1 1 1 2 2 4 2 Appendix C Param 509 511 512 518 520 521 501 504 510 513 519 522 528 529 526 1101 536 545 554 1102 537 538 546 547 555 556 530 539 548 1101 558 531 533 534 540 542 543 549 551 552 532 535 541 544 550 553 559 560 557 1001 495 Appendix C EtherNet/IP Information Instance 120 - Configuration Assembly Revision 1 The following table shows Attribute 3 Format and Attribute 2 Member List for revision 1 of the assembly. This is a stripped down simple version of a config assembly. Table 538 - Instance 120 — Configuration Assembly INT 0 1 2 3 DINT 15 14 13 ConfigAssyRev = 1 0 Reserved 1 12 11 10 9 8 7 6 Reserved 3 2 1 0 TripClass OLPTCResetMode SingleOrThreePh Reserved OLResetLevel X 5 4 FLASetting 4 3 5 X X X X X X X OLWarningLevel Size (bits) Param 16 1002 16 N/A 32 171 8 1 1 6 8 8 172 173 176 N/A 174 175 Instance 144 – Default Consumed Assembly Table 539 - Instance 144 – Default Consumed Assembly INT 0 1 DINT 15 14 13 OutputStatus0 NetworkStart1 NetworkStart2 TripReset EmergencyStart RemoteTrip 0 Reserved 12 11 10 9 8 5 4 3 2 1 0 X X X X X X X X 1 6 X X 2 3 7 X X X DLXPtDeviceIn DLXAnDeviceIn X X X HMILED1Green HMILED2Green HMILED3Green HMILED3Red HMILED4Red Reserved Size (bits) Path 16 Param18 Symbolic Symbolic Symbolic Symbolic Symbolic N/A Symbolic Symbolic Symbolic Symbolic Symbolic N/A 16 Symbolic 16 Symbolic Instance 198 - Current Diagnostics Produced Assembly Table 540 - Instance 198 – Current Diagnostics Produced Assembly INT 0 1 2 3 496 DINT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Size (bits) Param 0 Reserved for Logix 32 1104 1 DeviceStaus0 DeviceStaus1 16 16 20 21 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information INT 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 DINT 15 14 13 InputStatus0 2 InputStatus1 OutputStatus 3 OpStationStatus TripStsCurrent 4 WarnStsCurrent TripStsVoltage 5 WarnStsVoltage TripStsPower 6 WarnStsPower TripStsControl 7 WarnStsControl TripStsAnalog 8 WarnStsAnalog Reserved 9 MismatchStatus 12 11 10 9 8 7 6 5 4 3 10 CurrentImbal AvgPercentFLA Size (bits) 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 8 8 16 11 AverageCurrent 32 46 12 L1Current 32 43 13 L2Current 32 44 14 L3Current 32 45 15 GFCurrent Reserved 16 16 51 1103 16 Datalink1 32 1291 17 Datalink2 32 1292 18 Datalink3 32 1293 19 Datalink4 32 1294 20 Datalink5 32 1295 21 Datalink6 32 1296 22 Datalink7 32 1297 23 Datalink8 32 1298 PtDeviceOuts AnDeviceOuts InAnMod1Ch00 InAnMod1Ch01 16 16 16 16 348 1105 111 112 ThermUtilizedPct 24 25 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 2 1 0 Appendix C Param 16 17 18 19 4 10 5 11 6 12 7 13 8 14 1103 40 1 52 50 497 Appendix C EtherNet/IP Information INT 52 53 54 55 56 57 58 59 60 61 62 63 64 65 DINT 15 14 13 InAnMod1Ch02 26 Reserved InAnMod2Ch00 27 InAnMod2Ch01 InAnMod2Ch02 28 Reserved InAnMod3Ch00 29 InAnMod3Ch01 InAnMod3Ch02 30 Reserved InAnMod4Ch00 31 InAnMod4Ch01 InAnMod4Ch02 32 Reserved 12 11 10 9 8 7 6 5 4 3 2 1 0 Size (bits) 16 16 16 16 16 16 16 16 16 16 16 16 16 16 Param 113 1103 114 115 116 1103 117 118 119 1103 120 121 122 1103 Instance 199 - All Diagnostics Produced Assembly Table 541 - Instance 199 - All Diagnostics Produced Assembly INT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 498 DINT 15 0 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Size (bits) Param Reserved for Logix 32 1104 DeviceStaus0 DeviceStaus1 InputStatus0 InputStatus1 OutputStatus OpStationStatus TripStsCurrent WarnStsCurrent TripStsVoltage WarnStsVoltage TripStsPower WarnStsPower TripStsControl WarnStsControl TripStsAnalog WarnStsAnalog Reserved 20 21 16 17 18 19 4 10 5 11 6 12 7 13 8 14 1104 40 1 52 50 10 CurrentImbalance AvgPercentFLA 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 8 8 16 11 AverageCurrent 32 46 12 L1Current 32 43 13 L2Current 32 44 1 2 3 4 5 6 7 8 9 ThermUtilizedPct Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information INT 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 DINT 15 14 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Appendix C Size (bits) Param L3Current 32 45 GFCurrent Reserved AvgVoltageLtoL L1toL2Voltage L2toL3Voltage L3toL1Voltage 16 16 16 16 16 16 51 1103 56 53 54 55 18 TotalRealPower 32 67 19 TotalReactivePwr 32 71 20 TotalApparentPwr 32 75 21 TotalPowerFactor 32 79 22 Datalink0 32 1291 23 Datalink1 32 1292 24 Datalink2 32 1293 25 Datalink3 32 1294 26 Datalink4 32 1295 27 Datalink5 32 1296 28 Datalink6 32 1297 29 Datalink7 32 1298 PtDeviceOuts AnDeviceOuts InAnMod1Ch00 InAnMod1Ch01 InAnMod1Ch02 Reserved InAnMod2Ch00 InAnMod2Ch01 InAnMod2Ch02 Reserved InAnMod3Ch00 InAnMod3Ch01 InAnMod3Ch02 Reserved InAnMod4Ch00 InAnMod4Ch01 InAnMod4Ch02 Reserved 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 348 1105 111 112 113 1103 114 115 116 1103 117 118 119 1103 120 121 122 1103 15 16 17 30 31 32 33 34 35 36 37 38 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 499 Appendix C EtherNet/IP Information Connection Object — CLASS CODE 0x0005 No class attributes are supported for the Connection Object Multiple instances of the Connection Object are supported, instances 1, 2 and 4 from the group 2 predefined master/slave connection set, and instances 5-7 are available explicit UCMM connections. Instance 1 is the Predefined Group 2 Connection Set Explicit Message Connection. The following instance 1 attributes are supported: Table 542 - Connection Object — CLASS CODE 0x0005 Instance 1 Attributes 500 Attribute ID Access Rule Name Data Type 1 Get State USINT 2 Get Instance Type USINT 3 Get Transport Class Trigger USINT 4 Get Produced Connection ID UINT 5 Get Consumed Connection ID UINT 6 7 8 9 Get Get Get Get/Set Initial Comm Characteristics Produced Connection Size Consumed Connection Size Expected Packet Rate USINT UINT UINT UINT 12 Get Watchdog Action USINT 13 14 15 16 Get Get Get Get Produced Connection Path Length Produced Connection Path Consumed Connection Path Length Consumed Connection Path UINT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 UINT Value 0=nonexistant 1=configuring 3=established 4=timed out 0=Explicit Message 0x83 - Server, Transport Class 3 10xxxxxx011 xxxxxx = node address 10xxxxxx100 xxxxxx = node address 0x22 0x61 0x61 in milliseconds 01 = auto delete 03 = deferred delete 0 Empty 0 Empty EtherNet/IP Information Appendix C Instance 2 is the Predefined Group 2 Connection Set Polled IO Message Connection. The following instance 2 attributes are supported: Table 543 - Connection Object — CLASS CODE 0x0005 Instance 2 Attributes Attribute ID Access Rule 1 Get 2 Get 3 Get 4 Get 5 Get 6 7 8 9 Get Get Get Get/Set 12 Get/Set 13 14 15 16 Get Get/Set Get Get/Set Name Data Type Value 0=nonexistant 1=configuring State USINT 3=established 4=timed out Instance Type USINT 1= I/O Connection 0x82 - Server, Transport Class 2 (If alloc_choice != polled and ack Transport Class Trigger USINT suppression is enabled then value = 0x80) 01111xxxxxx Produced Connection ID UINT xxxxxx= node address 10xxxxxx101 Consumed Connection ID UINT xxxxxx= node address Initial Comm Characteristics USINT 0x21 Produced Connection Size UINT 0 to 8 Consumed Connection Size UINT 0 to 8 Expected Packet Rate UINT in milliseconds 0=transition to timed out Watchdog Action USINT 1=auto delete 2=auto reset Produced Connection Path Length UINT 8 Produced Connection Path 21 04 00 25 (assy inst) 00 30 03 Consumed Connection Path Length UINT 8 Consumed Connection Path 21 04 00 25 (assy inst) 00 30 03 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 501 Appendix C EtherNet/IP Information Instance 4 is the Predefined Group 2 Connection Set Change of State / Cyclic I/ O Message Connection. The following instance 4 attributes are supported: Table 544 - Connection Object — CLASS CODE 0x0005 Instance 4 Attributes 502 Attribute ID Access Rule Name Data Type 1 Get State USINT 2 Get Instance Type USINT 3 Get Transport Class Trigger USINT 4 Get Produced Connection ID UINT 5 Get Consumed Connection ID UINT 6 Get Initial Comm Characteristics USINT 7 8 9 Get Get Get/Set Produced Connection Size Consumed Connection Size Expected Packet Rate UINT UINT UINT 12 Get Watchdog Action USINT 13 14 15 16 Get Get Get Get/Set Produced Connection Path Length UINT Produced Connection Path Consumed Connection Path Length UINT Consumed Connection Path Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value 0=nonexistant 1=configuring 3=established 4=timed out 1=I/O Connection 0x00 (Cyclic, unacknowledged) 0x03 (Cyclic, acknowledged) 0x10 (COS, unacknowledged) 0x13 (COS, acknowledged) 01101xxxxxx xxxxxx= node address 10xxxxxx101 xxxxxx= node address 0x02 (acknowledged) 0x0F (unacknowledged) 0 to 8 0 to 8 in milliseconds 0=transition to timed out 1=auto delete 2=auto reset 8 21 04 00 25 (assy inst) 00 30 03 8 21 04 00 25 (assy inst) 00 30 03 EtherNet/IP Information Appendix C Instances 5 - 7 are available group 3 explicit message connections that are allocated through the UCMM. The following attributes are supported: Table 545 - Connection Object — CLASS CODE 0x0005 Instance 5…7 Attributes Attribute ID Access Rule Name Data Type 1 Get State USINT 2 Get Instance Type USINT 3 Get Transport Class Trigger USINT 4 Get Produced Connection ID UINT 5 Get Consumed Connection ID UINT 6 7 8 9 Get Get Get Get/Set Initial Comm Characteristics Produced Connection Size Consumed Connection Size Expected Packet Rate USINT UINT UINT UINT 12 Get Watchdog Action USINT 13 14 15 16 Get Get Get Get Produced Connection Path Length UINT Produced Connection Path Consumed Connection Path Length UINT Consumed Connection Path Value 0=nonexistant 1=configuring 3=established 4=timed out 0=Explicit Message 0x83 - Server, Transport Class 3 Depends on message group and Message ID Depends on message group and Message ID 0x33 (Group 3) 0 in milliseconds 01 = auto delete 03 = deferred delete 0 Empty 0 Empty The following services are implemented for the Connection Object. Table 546 - Connection Object Services Implemented for: Class No No No Service Code 0x05 0x0E 0x10 Instance Yes Yes Yes Service Name Reset Get_Attribute_Single Set_Attribute_Single Discrete Input Point Object — CLASS CODE 0x0008 The following class attributes are supported for the Discrete Input Point Object: Table 547 - Discrete Input Point Object Class Attributes Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 2 Get Max. Instance UINT 22 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 503 Appendix C EtherNet/IP Information 22 instances of the Discrete Input Point Object are supported. Table 548 - Discrete Input Point Object Instances Instance 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Name InputPt00 InputPt01 InputPt02 InputPt03 InputPt04 InputPt05 InputDigMod1Pt00 InputDigMod1Pt01 InputDigMod1Pt02 InputDigMod1Pt03 InputDigMod2Pt00 InputDigMod2Pt01 InputDigMod2Pt02 InputDigMod2Pt03 InputDigMod3Pt00 InputDigMod3Pt01 InputDigMod3Pt02 InputDigMod3Pt03 InputDigMod4Pt00 InputDigMod4Pt01 InputDigMod4Pt02 InputDigMod4Pt03 Description Control Module Input 0 Control Module Input 1 Control Module Input 2 Control Module Input 3 Control Module Input 4 Control Module Input 5 Digital Expansion Module 1 Input 0 Digital Expansion Module 1 Input 1 Digital Expansion Module 1 Input 2 Digital Expansion Module 1 Input 3 Digital Expansion Module 2 Input 0 Digital Expansion Module 2 Input 1 Digital Expansion Module 2 Input 2 Digital Expansion Module 2 Input 3 Digital Expansion Module 3 Input 0 Digital Expansion Module 3 Input 1 Digital Expansion Module 3 Input 2 Digital Expansion Module 3 Input 3 Digital Expansion Module 4 Input 0 Digital Expansion Module 4 Input 1 Digital Expansion Module 4 Input 2 Digital Expansion Module 4 Input 3 All instances contain the following attributes. Table 549 - Discrete Input Point Object Instance Attributes Attribute ID 3 115 116 Access Rule Get Get/Set Get/Set Name Value Force Enable Force Value Data Type BOOL BOOL BOOL Value 0=OFF, 1=ON 0=Disable, 1=Enable 0=OFF, 1=ON The following common services are implemented for the Discrete Input Point Object. Table 550 - Discrete Input Point Object Common Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes No Yes Service Name Get_Attribute_Single Set_Attribute_Single Discrete Output Point Object — CLASS CODE 0x0009 The following class attributes are supported for the Discrete Output Point Object: 504 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Appendix C Table 551 - Discrete Output Point Object Class Attributes Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 1 2 Get Max. Instance UINT 11 11 instances of the Discrete Output Point Object are supported. Table 552 - Discrete Output Point Object Instances Instance 1 2 3 4 5 6 7 8 9 10 11 Name OutputPt00 OutputPt01 OutputPt02 OutDigMod1Pt00 OutDigMod1Pt01 OutDigMod2Pt00 OutDigMod2Pt01 OutDigMod3Pt00 OutDigMod3Pt01 OutDigMod4Pt00 OutDigMod4Pt01 Description Control Module Output 0 Control Module Output 1 Control Module Output 2 Digital Expansion Module 1 Output 0 Digital Expansion Module 1 Output 1 Digital Expansion Module 2 Output 0 Digital Expansion Module 2 Output 1 Digital Expansion Module 3 Output 0 Digital Expansion Module 3 Output 1 Digital Expansion Module 4 Output 0 Digital Expansion Module 4 Output 1 All instances contains the following attributes. Table 553 - Discrete Output Point Object Instance Attributes Attribute ID Access Rule 3 Get Name Value Data Type BOOL 5 Get/Set Fault Action BOOL 6 Get/Set Fault Value BOOL 7 Get/Set Idle Action BOOL 8 113 114 115 116 Get/Set Get/Set Get/Set Get/Set Get/Set Idle Value Pr Fault Action Pr Fault Value Force Enable Force Value BOOL BOOL BOOL BOOL BOOL Input Binding STRUCT: USINT Array of USINT 117 Get/Set Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value 0=OFF, 1=ON 0=Fault Value attribute, 1=Hold Last State 0=OFF, 1=ON 0=Fault Value attribute, 1=Hold Last State 0=OFF, 1=ON 0=Pr Fault Value attribute, 1=Ignore 0=OFF, 1=ON 0=Disable, 1=Enable 0=OFF, 1=ON Size of appendix I encoded path Appendix I encoded path: NULL path means attribute 3 drives the output. Otherwise, this is a path to a bit in an instance of the DeviceLogix Data Table. 505 Appendix C EtherNet/IP Information The following common services are implemented for the Discrete Output Point Object. Table 554 - Discrete Output Point Object Common Services Implemented for: Class Instance No Yes No Yes Service Code 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Analog Input Point Object — CLASS CODE 0x000A The following class attributes are supported for the Analog Input Point Object: Table 555 - Analog Input Point Object Class Attributes Attribute ID Access Rule Name Data Type Value 1 Get Revision UINT 2 2 Get Max. Instance UINT 1 12 Instances of the Analog Input Point Object are supported. The raw analog value is scaled appropriately to the analog input configuration parameters and the scaled value are placed in the Value attribute. Table 556 - Analog Input Point Object Instances Instance 1 2 3 4 5 6 7 8 9 10 11 12 Name InAnMod1Ch00 InAnMod1Ch01 InAnMod1Ch02 InAnMod2Ch00 InAnMod2Ch01 InAnMod2Ch02 InAnMod3Ch00 InAnMod3Ch01 InAnMod3Ch02 InAnMod4Ch00 InAnMod4Ch01 InAnMod4Ch02 Description Analog Expansion Module 1 Input Channel 0 Analog Expansion Module 1 Input Channel 1 Analog Expansion Module 1 Input Channel 2 Analog Expansion Module 2 Input Channel 0 Analog Expansion Module 2 Input Channel 1 Analog Expansion Module 2 Input Channel 2 Analog Expansion Module 3 Input Channel 0 Analog Expansion Module 3 Input Channel 1 Analog Expansion Module 3 Input Channel 2 Analog Expansion Module 4 Input Channel 0 Analog Expansion Module 4 Input Channel 1 Analog Expansion Module 4 Input Channel 2 All instances contains the following attributes. Table 557 - Analog Input Point Object Instance Attributes Attribute ID 3 8 148 149 506 Access Rule Get Get Get/Set Get/Set Name Value Value Data Type Force Enable Force Value Data Type INT USINT BOOL INT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value Default = 0 0=INT 0=Disable, 1=Enable Default = 0 EtherNet/IP Information Appendix C The following common services are implemented for the Analog Input Point Object. Table 558 - Analog Input Point Object Common Services Implemented for: Class Instance Yes Yes No Yes Service Code 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Parameter Object — CLASS CODE 0x000F The following class attributes are supported for the Parameter Object: Table 559 - Parameter Object Class Attributes Attribute ID 1 2 8 9 10 Access Rule Get Get Get Get Get Name Revision Max Instance Parameter Class Descriptor Configuration Assembly Instance Native Language Data Type UINT UINT WORD UINT UINT Value 1 560 0x03 0 1 = English The following instance attributes are implemented for all parameter attributes. Table 560 - Parameter Object Instance Attributes Attribute ID Access Rule 1 Get/Set 2 Get 3 Get 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get Name Value Link Path Size Data Type Specified in Descriptor USINT Array of: Link Path BYTE EPATH Descriptor WORD Data Type EPATH Data Size USINT Parameter Name String SHORT_STRING Units String SHORT_STRING Help String SHORT_STRING Minimum Value Specified in Descriptor Maximum Value Specified in Descriptor Default Value Specified in Descriptor Scaling Multiplier UINT Scaling Divisor UINT Scaling Base UINT Scaling Offset INT Multiplier Link UINT Divisor Link UINT Base Link UINT Offset Link UINT Decimal Precision USINT Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value 08 Path to specified object attribute. Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent Parameter Dependent 01 01 01 00 0 0 0 0 Parameter Dependent 507 Appendix C EtherNet/IP Information The following common services are implemented for the Parameter Object. Table 561 - Parameter Object Common Services Implemented for: Class Instance Yes Yes No Yes Service Code 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Parameter Group Object — CLASS CODE 0x0010 The following class attributes are supported for the Parameter Object: Table 562 - Parameter Object Class Attributes Attribute ID 1 2 8 Access Rule Get Get Get Name Revision Max Instance Native Language Data Type UINT UINT USINT Value 1 23 1 = English The following instance attributes are supported for all parameter group instances: The following instance attributes are implemented for all parameter attributes. Table 563 - Parameter Group Object Instance Attributes Attribute ID 1 2 3 4 n Access Rule Get Get Get Get Get Name Group Name String Number of Members 1st Parameter 2nd Parameter Nth Parameter Data Type SHORT_STRING UINT UINT UINT UINT Value The following common services are implemented for the Parameter Group Object. Table 564 - Parameter Group Object Common Services Service Code 0x0E Implemented for: Class Instance Yes Yes Service Name Get_Attribute_Single Discrete Output Group Object — CLASS CODE 0x001E No class attributes are supported for the Discrete Output Group Object. Five instances of the Discrete Output Group Object are supported. Instance 1 has the following instances: 508 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Appendix C Table 565 - Discrete Output Group Object Instance 1 Attributes Attribute ID 3 4 6 Access Rule Get Get Get/Set Name Number of Instances Binding Command Data Type USINT Array of UINT BOOL 104 Get/Set Network Status Override BOOL 105 Get/Set Comm Status Override BOOL Value 11 1,2,3,4,5,6,7,8,9,10,11 0=idle; 1=run 0=No Override (go to safe state) 1=Override (run local logic) 0=No override (go to safe state) 1=Override (run local logic) Instances 2-5 each represent a single expansion module. They have the following attributes. Table 566 - Discrete Output Group Object Instance 2…5 Attributes Attribute ID Access Rule 3 Get Name Number of Instances Data Type USINT 4 Get Binding Array of UINT 6 Get/Set Command BOOL 7 Get/Set Fault Action BOOL 8 Get/Set Fault Value BOOL 9 Get/Set Idle Action BOOL 10 Get/Set Idle Value BOOL 113 Get/Set Pr Fault Action BOOL 114 Get/Set Pr Fault Value BOOL Value 2 Instance 2: 4, 5 Instance 3: 6, 7 Instance 4: 8, 9 Instance 5: 10, 11 0=idle; 1=run 0=Fault Value Attribute, 1=Hold Last State 0=OFF, 1=ON 0=Idle Value Attribute, 1=Hold Last State 0=OFF, 1=ON 0=Pr Fault Value Attribute, 1=Ignore 0=OFF, 1=ON The following common services are implemented for the Discrete Output Group Object. Table 567 - Discrete Output Group Object Common Services Service Code 0x0E 0x10 Implemented for: Class Instance No Yes No Yes Service Name Get_Attribute_Single Set_Attribute_Single Control Supervisor Object — CLASS CODE 0x0029 No class attributes are supported. A single instance (instance 1) of the Control Supervisor Object is supported. Rockwell Automation Publication 193-UM015C-EN-P - December 2014 509 Appendix C EtherNet/IP Information Table 568 - Control Supervisor Object Instance 1 Attributes Attribute ID Access Rule Name Data Type 10 Get Tripped BOOL 11 Get Warning BOOL 12 Get/Set Fault Reset BOOL Value 0 = No Fault present 1 = Fault Latched 0 = No Warning present 1 = Warning present (not latched) 0->1 = Trip Reset otherwise no action The following common services are implemented for the Control Supervisor Object. Table 569 - Control Supervisor Object Common Services Implemented for: Class Instance No Yes No Yes Service Code 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Overload Object — CLASS CODE 0x002c No class attributes are supported for the Overload Object. A single instance (instance 1) of the Overload Object is supported. Table 570 - Overload Object Instance 1 Attributes Attribute ID 4 5 6 7 8 9 10 11 Access Rule Get/Set Get Get Get Get Get Get Get Name Trip Class Average Current %Phase Imbal % Thermal Utilized Current L1 Current L2 Current L3 GF Current Data Type USINT INT USINT USINT INT INT INT INT Value 5…30 xxx.x Amps (tenths of amps) xxx% FLA xxx% FLA xxx.x Amps (tenths of amps) xxx.x Amps (tenths of amps) xxx.x Amps (tenths of amps) 0.00 – 12.75 Amps The following common services are implemented for the Overload Object. Table 571 - Overload Object Common Services Service Code 0x0E 0x10 Implemented for: Class Instance No Yes No Yes Service Name Get_Attribute_Single Set_Attribute_Single Base Energy Object — CLASS CODE 0x004E The following class attributes are supported for the Base Energy Object. 510 Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Appendix C Table 572 - Base Energy Object Class Attributes Attribute ID 1 Access Rule Get Name Object Revision Data Type USINT Value 2 A single instance of the Base Energy Object is supported Table 573 - Base Energy Instance Attributes Attribute ID Access Rule 1 Get 2 Get Name Data Type Energy/Resource Type UINT Energy Object WORD Capabilities 3 Get Energy Accuracy UINT 4 Get UINT 5 Get Real x.xxx kW (TBD) 7 Get ODOMETER Returns params 80-84 values. 9 10 Get Get Energy Accuracy Basis Full Scale Power Reading Consumed Energy Odometer Total Energy Odometer Total Real Power 500 = 5.00 percent of full scale reading 1 = Percent of full scale reading Returns params 80-84 values. Param 67 value converted to a REAL 12 Get Energy Type Specific Object Path SIGNED ODOMETER REAL STRUCT of UINT Padded EPATH 16 Set Odometer Reset Enable BOOL Value 1 = Electrical 0x0001 = Energy Measured 03 00 21 00 4F 00 24 01 0 = Disabled (Default) 1 = Enabled Enables resetting of Energy Odometers by Reset service The following services are implemented for the Base Energy Object. Table 574 - Base Energy Object Common Services Service Code 0x01 0x05 0x0E 0x10 Implemented for: Class No No No No Instance Yes Yes Yes Yes Service Name GetAttributes_All Reset Get_Attribute_Single Set_Attribute_Single The following table describes the Get_Attributes_All response. Table 575 - Base Energy Object Class Attributes Get_Attributes_All Response Attribute ID 1 2 3 4 5 6 7 8 9 10 Data Type UINT WORD UINT UINT REAL UINT ODOMETER ODOMETER SIGNED ODOMETER REAL Name Energy/Resource Type Energy Object Capabilities Energy Accuracy Energy Accuracy Basis Full Scale Reading Data Status Consumed Energy Odometer Generated Energy Odometer Value Attribute 1 value Attribute 2 value Attribute 3 value Attribute 4 value Attribute 5 value 0 0Attribute 7 value 0,0,0,0,0 Total Energy Odometer Attribute 9 value Energy Transfer Rate Attribute 10 value Rockwell Automation Publication 193-UM015C-EN-P - December 2014 511 Appendix C EtherNet/IP Information Attribute ID 11 Name Value Energy Transfer Rate User Setting 0.0 12 Data Type REAL STRUCT of UINT, Padded EPATH 1 13 UINT Energy Aggregation Path Array Size 0 14 Array of STRUCT of UINT, Padded EPATH 1 Energy Aggregation Paths Null Energy Type Specific Object Path Attribute 12 value 15 STRINGI Energy Identifier 16 17 BOOL BOOL Odometer Reset Enable Metering State LanguageChar1 USINT =вЂ�e’ LanguageChar2 USINT)=вЂ�n’ LanguageChar3 USINT) =вЂ�g’ CharStringStruct USINT=0xD0 CharSet UINT = 0 = undefined InternationalString = null Attribute 16 value 1 Electrical Energy Object — CLASS CODE 0x004F No class attributes are supported for the Electrical Energy Object. A single instance of the Electrical Energy Object is supported Table 576 - Electrical Energy Object Instance Attributes Attribute ID Access Rule 512 1 Get 3 Get 4 Get 5 Get 6 Get 7 Get 9 10 11 12 13 Get Get Get Get Get 14 Get 15 16 17 18 19 20 21 22 Get Get Get Get Get Get Get Get Name Real Energy Consumed Odometer Real Energy Net Odometer Reactive Energy Consumed Odometer Reactive Energy Generated Odometer Reactive Energy Net Odometer Apparent Energy Odometer Line Frequency L1 Current L2 Current L3 Current Average Current Percent Current Unbalance L1 to N Voltage L2 to N Voltage L3 to N Voltage Avg Voltage L to N L1 to L2 Voltage L2 to L3 Voltage L3 to L1 Voltage Avg Voltage Lto N Data Type Value ODOMETER Returns params 80-84 values. SIGNED ODOMEETER Returns params 80-84 values. ODOMETER Returns params 85-89 values. ODOMETER Returns params 90-94 values. SIGNED ODOMETER Returns params 95-99 values. ODOMETER Returns params 100-104 values. REAL REAL REAL REAL REAL Param 62 value converted to a REAL Param 43 value converted to a REAL Param 44 value converted to a REAL Param 45 value converted to a REAL Param 46 value converted to a REAL REAL Param 52 value converted to a REAL REAL REAL REAL REAL REAL REAL REAL REAL Param 57 value converted to a REAL Param 58 value converted to a REAL Param 59 value converted to a REAL Param 60 value converted to a REAL Param 53 value converted to a REAL Param 54 value converted to a REAL Param 55 value converted to a REAL Param 56 value converted to a REAL Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Attribute ID Access Rule 23 Get 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 Get Get Get Get Get Get Get Get Get Get Get Get Get Get Get 39 Get 40 Get Name Percent Voltage Unbalance L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power L1 True Power Factor L2 True Power Factor L3 True Power Factor Three Phase True Power Factor Phase Rotation Get Associated Energy Object Path 41 Appendix C Data Type Value REAL Param 61 value converted to a REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL Param 64 value converted to a REAL Param 65 value converted to a REAL Param 66 value converted to a REAL Param 67 value converted to a REAL Param 68 value converted to a REAL Param 68 value converted to a REAL Param 70 value converted to a REAL Param 71 value converted to a REAL Param 72 value converted to a REAL Param 73 value converted to a REAL Param 74 value converted to a REAL Param 75 value converted to a REAL Param 76 value converted to a REAL Param 77 value converted to a REAL Param 78 value converted to a REAL REAL Param 79 value converted to a REAL UINT STRUCT of UINT Padded EPATH Param 63 value 03 00 21 00 4E 00 24 01 The following services are implemented for the Electrical Energy Object. Table 577 - Electrical Energy Object Common Services Service Code 0x01 0x0E Implemented for: Class Instance No Yes No Yes Service Name GetAttributes_All Get_Attribute_Single The following table describes the Get_Attributes_All response. Table 578 - Electrical Energy Object Class Attributes Get_Attributes_All Response Attribute ID 1 2 3 Data Type Array[5] of INT Array[5] of INT Array[5] of INT 4 Array[5] of INT 5 Array[5] of INT 6 7 8 9 10 11 12 13 14 Array[5] of INT Array[5] of INT Array[5] of INT REAL REAL REAL REAL REAL REAL Name Real Energy Consumed Odometer Real Energy Generated Odometer Real Energy Net Odometer Reactive Energy Consumed Odometer Reactive Energy Generated Odometer Reactive Energy Net Odometer Apparent Energy Odometer Line Frequency L1 Current L2 Current L3 Current Average Current Percent Current Unbalance Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Value Attribute 1 Value 0.0.0.0.0 Attribute 3 Value Attribute 4 Value Attribute 5 Value Attribute 6 Value Attribute 7 Value 0.0.0.0.0 Attribute 9 Value Attribute 10 Value Attribute 11 Value Attribute 12 Value Attribute 13 Value Attribute 14 Value 513 Appendix C EtherNet/IP Information Attribute ID 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Data Type REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL REAL UINT STRUCT of UINT Padded EPATH Name L1 to N Voltage L2 to N Voltage L3 to N Voltage Avg Voltage L to N L1 to L2 Voltage L2 to L3 Voltage L3 to L1 Voltage Avg Voltage Lto N Percent Voltage Unbalance L1 Real Power L2 Real Power L3 Real Power Total Real Power L1 Reactive Power L2 Reactive Power L3 Reactive Power Total Reactive Power L1 Apparent Power L2 Apparent Power L3 Apparent Power Total Apparent Power L1 True Power Factor L2 True Power Factor L3 True Power Factor Three Phase True Power Factor Phase Rotation Value Attribute 15 Value Attribute 16 Value Attribute 17 Value Attribute 18 Value Attribute 19 Value Attribute 20 Value Attribute 21 Value Attribute 22 Value Attribute 23 Value Attribute 24 Value Attribute 25 Value Attribute 26 Value Attribute 27 Value Attribute 28 Value Attribute 29 Value Attribute 30 Value Attribute 31 Value Attribute 32 Value Attribute 33 Value Attribute 34 Value Attribute 35 Value Attribute 36 Value Attribute 37 Value Attribute 38 Value Attribute 39 Value Attribute 40 Value Associated Energy Object Path Attribute 41 Value Wall Clock Time Object — CLASS CODE 0x008B The following class attributes are supported: Table 579 - Wall Clock Time Object Class Attributes Attribute ID 1 2 Access Rule Get Get Name Object Revision Number of Instances Data Type UINT UINT Value 3 1 One instance is supported: Table 580 - Wall Clock Time Object Instance Attributes 514 Attribute ID Access Rule Name Data Type 2 Set Time Zone UINT 3 Set / SSV Offset from CSV LINT 4 Set Local Time Adjustment WORD Value Time zone in which Current value is being used (Never been used) 64-bit offset value in ОјS that when added to the CST value yields the Current_UTC_Value Set of flags for specific local time adjustments (Never been used) Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Attribute ID Access Rule Name Data Type 5 Set / SSV Date and Time пЂ (Local Time) DINT[7] – Array of seven DINTs 6 Set / SSV Current UT value (UTC Time) LINT 7 Set / SSV UTC Date and Time (UTC Time) DINT[7] – Array of seven DINTs 8 Set / SSV Time Zone String Struct of UDINT SINT[Length] 9 Set / SSV DST Adjustment INT 10 Set / SSV Enable DST USINT 11 Set Current value (local time) LINT Appendix C Value Current adjusted time in human readable format. DINT[0] – year DINT[1] – month DINT[2] – day DINT[3] – hour DINT[4] – minute DINT[5] – second DINT[6] – пЃ­sec. Current value of Wall Clock Time. 64-bit ОјS value referenced from 0000 hrs January 1, 1970 Current time in human readable format. DINT[0] – year DINT[1] – month DINT[2] – day DINT[3] – hour DINT[4] – minute DINT[5] – second DINT[6] – пЃ­sec. This string specifies the time zone where the controller is located, and ultimately the adjustment in hours and minutes applied to the UTC value to generate the local time value. TimeZoneString can be specified in the following formats: o UTC+hh:mm <location> o UTC-hh:mm <location> hh:mm portion is used internally to calculate the local time, and the <location> portion is used to describe the time zone and is optional. GMT is also accepted Length of the Data array can be from 10 to 82. Examples: UTC-05:00 Eastern Time UTC+01:00 Coordinated Universal Time The number of minutes to be adjusted for daylight saving time It specifies if we are in daylight saving time or not. Not internally set. Needs user action. Adjusted Local value of Wall Clock Time. 64-bit ОјS value referenced from 0000 hrs January 1, 1970 The following services are implemented for the Wall Clock Time Object. Table 581 - Wall Clock Time Object Common Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes Yes No Service Name GetAttributes_All Set_Attribute_Single DPI Fault Object — CLASS CODE 0x0097 This object provides access to fault information within the device. The following class attributes are supported: Rockwell Automation Publication 193-UM015C-EN-P - December 2014 515 Appendix C EtherNet/IP Information Table 582 - DPI Fault Object Class Attributes Attribute ID 1 2 Access Rule Get Get 3 Get/Set 4 Get 5 Get 6 Get Name Class Revision Number of Instances Data Type Value UINT 1 UINT 8 0=NOP; 1=Clear Fault; 2=Clear Flt Fault Cmd Write USINT Queue The instance of the Fault Queue Entry Fault Instance Read UINT containing information about the Fault that tripped the Device Fault Data list Struct of: The total number of parameters Number of Parameter Instances UINT instances stored when a fault occurs An array of parameters instance Parameter Instances UINT [x ] numbers The number of Faults recorded in the Number of Recorded Faults UINT Fault Queue Five instances of the DPI Fault Object are supported. Table 583 - DPI Fault Object Instance Attributes Attribute ID Access Rule 0 Get 1 Get 3 Get Name Full / All Info Fault Code Fault Source DPI Port Number Device Object Instance Fault Text Fault Time Stamp Data Type Struct of: UINT Struct of: USINT USINT BYTE[16] Value See Fault Table below 0 0x2c See Fault Table below Struct of: Timer Value ULINT Timer Descriptor WORD Help Object UINT Instance Fault Data Basic Info Struct of: Fault Code UINT Fault Source Struct of: DPI Port Number USINT Device Object USINT Instance Fault Time Stamp Struct of: Timer Value ULINT Timer Descriptor WORD Help Text STRING See Table 585 0 0x2C See Table 585 The following common services are implemented for the DPI Fault Object. Table 584 - DPI Fault Object Common Services Service Code 0x0E 0x10 516 Implemented for: Class Instance Yes Yes Yes No Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Service Name Get_Attribute_Single Set_Attribute_Single EtherNet/IP Information Appendix C The table below lists Fault Codes, Fault Text, and Fault Help Strings. Table 585 - Fault Codes, Fault Text, and Fault Help Strings Fault Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Fault Text No Fault OverloadTrip PhaseLossTrip GroundFaultTrip StallTrip JamTrip UnderloadTrip Current Imbal L1UnderCurrTrip L2UnderCurrTrip L3UnderCurrTrip L1OverCurrenTrip L2OverCurrenTrip L3OverCurrenTrip L1LineLossTrip L2LineLossTrip L3LineLossTrip UnderVoltageTrip OverVoltageTrip VoltageUnbalTrip PhaseRotationTrp UnderFreqTrip OverFreqTrip Fault23 Fault24 Fault25 Fault26 Fault27 Fault28 Fault29 Fault30 Fault31 Fault32 UnderKWTrip OverKWTrip UnderKVARConTrip OverKVARConTrip UnderKVARGenTrip OverKVARGenTrip UnderKVATrip OverKVATrip UnderPFLagTrip OverPFLagTrip UnderPFLeadTrip OverPFLeadTrip Fault45 Fault46 Help Text No Fault Conditions Detected Motor current overload condition Phase current Loss detected in one of the motor phases Power conductor or motor winding is shorting to ground Motor has not reached full speed by the end of Stall Enable Time Motor current has exceed the programmed jam trip level Motor current has fallen below normal operating levels Phase to phase current imbalance detected L1Current was below L1 Undercurrent Level longer than Trip Delay L2Current was below L2 Undercurrent Level longer than Trip Delay L3Current was below L3 Undercurrent Level longer than Trip Delay L1 Current was over L1 Overcurrent Level longer than Trip Delay L2 Current was over L2 Overcurrent Level longer than Trip Delay L3 Current was over L3 Overcurrent Level longer than Trip Delay L1 Current Lost for longer than the L1 Loss Trip Delay L2 Current Lost for longer than the L2 Loss Trip Delay L3 Current Lost for longer than the L3 Loss Trip Delay Line to Line Under-Voltage condition detected Line to Line Over-Voltage condition detected Phase to phase voltage imbalance detected The unit detects the supply voltage phases are rotated Line voltage frequency is below trip level Line voltage frequency has exceeded trip level Total Real Power(kW)is below trip level Total Real Power(kW)has exceeded trip level Under Total Reactive Power Consumed (+kVAR) condition detected Over Total Reactive Power Consumed (+kVAR) condition detected Under Total Reactive Power Generated (-kVAR) condition detected Over Total Reactive Power Generated (-kVAR) condition detected Total Apparent Power (VA or kVA or MVA) is below trip level Total Apparent Power (VA or kVA or MVA) exceeded trip level Under Total Power Factor Lagging (-PF) condition detected Over Total Power Factor Lagging (-PF) condition detected Under Total Power Factor Leading (+PF) condition detected Over Total Power Factor Leading (+PF) condition detected Rockwell Automation Publication 193-UM015C-EN-P - December 2014 517 Appendix C EtherNet/IP Information Fault Code 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 518 Fault Text Fault47 Fault48 TestTrip PTCTrip DLXTrip OperStationTrip RemoteTrip BlockedStartTrip Trip55 ConfigTrip Trip57 DLXFBTimeoutTrip Trip59 Trip60 Trip61 NVSTrip Trip63 Trip64 InAnMod1Ch00Trip InAnMod1Ch01Trip InAnMod1Ch02Trip InAnMod2Ch00Trip InAnMod2Ch01Trip InAnMod2Ch02Trip InAnMod3Ch00Trip InAnMod3Ch01Trip InAnMod3Ch02Trip InAnMod4Ch00Trip InAnMod4Ch01Trip InAnMod4Ch02Trip Trip77 Trip78 Trip79 Trip80 DigitalMod1Trip DigitalMod2Trip DigitalMod3Trip DigitalMod4Trip AnalogMod1Trip AnalogMod2Trip AnalogMod3Trip AnalogMod4Trip Trip89 CtlModMismatch SenseModMismatch CommModMismatch OperStatMismatch DigModMismatch AnModMismatch Trip96 Help Text Test trip caused by holding the Test/Rest button for 2 seconds PTC input indicates that the motor stator windings overheated DeviceLogix defined trip was generated The Stop button the Operator Station was pressed Remote trip command detected Maximum starts per hour exceeded Hardware configuration fault. Check for shorts on input terminal Invalid parameter config. See parameters 38-39 for details DeviceLogix Feedback Timeout Trip was detected NonVolatile Storage memory problem detected Input Channel 00 on Analog Module 1 exceeded its Trip Level Input Channel 01 on Analog Module 1 exceeded its Trip Level Input Channel 02 on Analog Module 1 exceeded its Trip Level Input Channel 00 on Analog Module 2 exceeded its Trip Level Input Channel 01 on Analog Module 2 exceeded its Trip Level Input Channel 02 on Analog Module 2 exceeded its Trip Level Input Channel 00 on Analog Module 3 exceeded its Trip Level Input Channel 01 on Analog Module 3 exceeded its Trip Level Input Channel 02 on Analog Module 3 exceeded its Trip Level Input Channel 00 on Analog Module 4 exceeded its Trip Level Input Channel 01 on Analog Module 4 exceeded its Trip Level Input Channel 02 on Analog Module 4 exceeded its Trip Level Digital Expansion Module 1 is not operating properly Digital Expansion Module 2 is not operating properly Digital Expansion Module 3 is not operating properly Digital Expansion Module 4 is not operating properly Analog Expansion Module 1 is not operating properly Analog Expansion Module 2 is not operating properly Analog Expansion Module 3 is not operating properly Analog Expansion Module 4 is not operating properly Control Module installed does not match the expected type Sensing Module installed does not match the expected type Comms Module installed does not match the expected type Operator Station installed does not match expected type Digital Module installed does not match the expected type Analog Module installed does not match the expected type Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Fault Code 97 98 99 Fault Text Trip97 HardwareFltTrip Trip99 Appendix C Help Text A hardware fault condition was detected DPI Warning Object — CLASS CODE 0x0098 This object provides access to warning information within the device. The following class attributes are supported: Table 586 - DPI Warning Object Class Attributes Attribute ID 1 2 3 Access Rule Get Get Get/Set Name Class Revision Number of Instances Warning Cmd Write 4 Get Warning Instance Read 6 Get Number of Recorded Faults Data Type Value UINT 1 UINT 8 USINT 0=NOP 2=Clear Queue The instance of the Warning Queue UINT Entry containing information about the most recent warning The number of Warning recorded in UINT the Warning Queue Four instances of the DPI Warning Object are supported. Table 587 - DPI Warning Object Instance Attributes Attribute ID Access Rule 0 1 3 Get Get Get Name Full / All Info Warning Code Warning Source DPI Port Number Device Object Instance Warning Text Warning Time Stamp Timer Value Timer Descriptor Help Object Instance Fault Data Basic Info Warning Code Warning Source DPI Port Number Device Object Instance Warning Time Stamp Timer Value Timer Descriptor Help Text Data Type Struct of: UINT Struct of: USINT USINT BYTE[16] Value See Warning Table below 0 0x2c See Table 589 Struct of: ULINT WORD UINT Struct of: UINT Struct of: USINT USINT See Table 589 0 0x2C Struct of: ULINT WORD STRING Rockwell Automation Publication 193-UM015C-EN-P - December 2014 See Table 589 519 Appendix C EtherNet/IP Information The following common services are implemented for the DPI Warning Object. Table 588 - DPI Warning Object Common Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes Yes No Service Name Get_Attribute_Single Set_Attribute_Single The table below lists Warning Codes, Warning Text, and Warning Help Strings. Table 589 - Warning Codes, Warning Text, and Warning Help Strings Warning Code 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 520 Warning Text Warning Help Text No Warning OverloadWarning Warning2 Ground Fault Warning4 JamWarning UnderloadWarning Current ImbalWarn L1UnderCurrWarn L2UnderCurrWarn L3UnderCurrWarn L1OverCurrenWarn L2OverCurrenWarn L3OverCurrenWarn L1LineLossWarn L2LineLossWarn L3LineLossWarn UnderVoltageWarn OvervoltageWarn VoltageUnbalWarn PhaseRotationWrn UnderFreqWarning OverFreqWarning Warning23 Warning24 Warning25 Warning26 Warning27 Warning28 Warning29 Warning30 Warning31 Warning32 UnderKWWarning OverKWWarning UnderKVARConWarn OverKVARConWarn UnderKVARGenWarn No Warning Conditions Detected Approaching a motor current overload condition Power conductor or motor winding is shorting to ground Motor current has exceed the programmed jam warning level Motor current has fallen below normal operating levels Phase to phase current imbalance detected L1Current was below L1 Undercurrent Warning Level L2Current was below L2 Undercurrent Warning Level L3Current was below L3 Undercurrent Warning Level L1 Current was over L1 Overcurrent Warning Level L2 Current was over L2 Overcurrent Warning Level L3 Current was over L3 Overcurrent Warning Level L1 Current Lost for longer than the L1 Loss Trip Delay L2 Current Lost for longer than the L2 Loss Trip Delay L3 Current Lost for longer than the L3 Loss Trip Delay Line to Line Under-Voltage condition detected Line to Line Over-Voltage condition detected Phase to phase voltage imbalance detected The unit detects the supply voltage phases are rotated Line voltage frequency is below the warning level Line voltage frequency has exceeded warning level Total Real Power (kW) is below warning level Total Real Power (kW) has exceeded warning level Under Reactive Power Consumed (+kVAR) condition detected Over Reactive Power Consumed (+kVAR) condition detected Under Reactive Power Generated (-kVAR) condition detected Rockwell Automation Publication 193-UM015C-EN-P - December 2014 EtherNet/IP Information Warning Code 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 Appendix C Warning Text Warning Help Text OverKVARGenWarn Under Power kVA Over Power kVA Under PF Lagging Over PF Lagging Under PF Leading Over PF Leading Warning 45 Warning 46 Warning 47 Warning 48 Warning49 PTC DLXWarning Warning52 Warning53 Warning54 Warning55 ConfigWarning Warning57 DLXFBTimeoutWarn Warning59 PM Starts PM Oper Hours Warning62 Warning63 Warning64 InAnMod1Ch00Warn InAnMod1Ch01Warn InAnMod1Ch02Warn InAnMod2Ch00Warn InAnMod2Ch01Warn InAnMod2Ch02Warn InAnMod3Ch00Warn InAnMod3Ch01Warn InAnMod3Ch02Warn InAnMod4Ch00Warn InAnMod4Ch01Warn InAnMod4Ch02Warn Warning77 Warning 78 Warning 79 Warning 80 DigitalMod1Warn DigitalMod2Warn DigitalMod3Warn DigitalMod4Warn AnalogMod1Warn AnalogMod2Warn Over Reactive Power Generated (-kVAR) condition detected Total Apparent Power (kVA) is below warning level Total Apparent Power (kVA) exceeded warning level Under Total Power Factor Lagging (-PF) condition detected Over Total Power Factor Lagging (-PF) condition detected Under Total Power Factor Leading (+PF) condition detected Over Total Power Factor Leading (+PF) condition detected PTC input indicates that the motor stator windings overheated DeviceLogix defined warning was generated Invalid parameter config. See parameters 38-39 for details DeviceLogix Feedback Timeout Trip was detected Number of Starts Warning Level Exceeded Operating Hours Warning Level Exceeded Input Channel 00 on Analog Module 1 exceeded its Warning Level Input Channel 01 on Analog Module 1 exceeded its Warning Level Input Channel 02 on Analog Module 1 exceeded its Warning Level Input Channel 00 on Analog Module 2 exceeded its Warning Level Input Channel 01 on Analog Module 2 exceeded its Warning Level Input Channel 02 on Analog Module 2 exceeded its Warning Level Input Channel 00 on Analog Module 3 exceeded its Warning Level Input Channel 01 on Analog Module 3 exceeded its Warning Level Input Channel 02 on Analog Module 3 exceeded its Warning Level Input Channel 00 on Analog Module 4 exceeded its Warning Level Input Channel 01 on Analog Module 4 exceeded its Warning Level Input Channel 02 on Analog Module 4 exceeded its Warning Level Digital Expansion Module 1 is not operating properly Digital Expansion Module 2 is not operating properly Digital Expansion Module 3 is not operating properly Digital Expansion Module 4 is not operating properly Analog Expansion Module 1 is not operating properly Analog Expansion Module 2 is not operating properly Rockwell Automation Publication 193-UM015C-EN-P - December 2014 521 Appendix C EtherNet/IP Information Warning Code 87 88 89 90 91 92 93 94 95 96 97 98 99 Warning Text Warning Help Text AnalogMod3Warn AnalogMod4Warn Warning89 CtlModMismatch SenseModMismatch CommModMismatch OperStatMismatch DigModMismatch AnModMismatch Warning96 Warning97 HardwareFltWarn Warning99 Analog Expansion Module 3 is not operating properly Analog Expansion Module 4 is not operating properly Control Module installed does not match the expected type Sensing Module installed does not match the expected type Comms Module installed does not match the expected type Operator Station installed does not match expected type Digital Module installed does not match the expected type Analog Module installed does not match the expected type A hardware fault condition was detected MCC Object — CLASS CODE 0x00C2 A single instance (instance 1) of the MCC Object is supported: Table 590 - MCC Object Instance Attributes Attribute ID Access Rule 1 Get/Set 2 Get/Set 3 4 5 6 Get/Set Get/Set Get/Set Get/Set Name Mcc Number Vertical Section Number Starting Section Letter Space Factors Cabinet Width Mcc Number Data Type USINT Range 0-255 Value 0 USINT 0-255 0 USINT USINT USINT USINT 0-255 0-255 0-255 0-255 65 0x3F 0 0 EC1=2 EC2=EC3=EC4=4 EC5=6 7 Get Number of Device Inputs USINT 8 Get/Set Array of USINT 00000000000000 9 Get USINT 2 10 Get/Set Devices Connected at Inputs Number of Device Outputs Devices Connected at Outputs Array of USINT 0000 The following common services are implemented for the MCC Object. Table 591 - MCC Object Common Services Service Code 0x0E 0x10 0x18 0x19 522 Implemented for: Class No No No No Instance Yes Yes Yes Yes Rockwell Automation Publication 193-UM015C-EN-P - December 2014 Service Name Get_Attribute_Single Set_Attribute_Single Get_Member Set_Member Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products.пЂ At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates. In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visitпЂ http://www.rockwellautomation.com/services/online-phone. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Outside United States Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Rockwell Otomasyon Ticaret A.Ећ., Kar Plaza Д°Еџ Merkezi E Blok Kat:6 34752 Д°Г§erenkГ¶y, Д°stanbul, Tel: +90 (216) 5698400 Publication 193-UM015C-EN-P - December 2014 Supersedes publication 193-UM015B-EN-P - June 2014 Copyright В© 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. ">
Advertisement
Key features
- Modular Design
- Communication Options
- Simplified Wiring
- Diagnostic Information
- Standard Current-Based Protection
- Ground Fault Current-based Protection
- Voltage- and Power-based Protection
- EtherNet/IP Communications
- Analog Input and Output Channels
- Metering and Diagnostics
Frequently asked questions
The E300 provides standard current-based protection such as overload and phase loss, as well as ground fault current-based protection. In addition, it offers voltage- and power-based protection including under voltage, over voltage, frequency, and power factor.
The E300 can communicate with other devices via EtherNet/IP, which is a common industrial communication protocol.
The E300 supports optional expansion modules that can add capabilities such as digital and analog I/O, operator stations, and additional bus power supplies.