Design Tools for Submersible Converter
Ritchie, Andrew Ewen; Trintis, Ionut; Nica, Florin Valentin Traian; Boian, Daniela; Biris,
Ciprian; Burlacu, Paul Dan; Shivachev, Stoyan
Publication date:
2014
Link to publication from Aalborg University
Citation for published version (APA):
Ritchie, E., Trintis, I., Nica, F. V. T., Boian, D., Biris, C., Burlacu, P. D., & Shivachev, S. (2014). Design Tools for
Submersible Converter. Department of Energy Technology, Aalborg University.
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners
and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.
? Users may download and print one copy of any publication from the public portal for the purpose of private study or research.
? You may not further distribute the material or use it for any profit-making activity or commercial gain
? You may freely distribute the URL identifying the publication in the public portal ?
Take down policy
If you believe that this document breaches copyright please contact us at [email protected] providing details, and we will remove access to
the work immediately and investigate your claim.
Downloaded from vbn.aau.dk on: december 22, 2014
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Contents
........................................................................................................................................................................... 1
DeepWind WP3 D3.32 – Technical Report – Submersible Converter ............................................................... 2
Introduction ....................................................................................................................................................... 3
Deliverable Description from DOW ............................................................................................................... 3
Converter functional modes .............................................................................................................................. 3
Four quadrant two level converter for the DeepWind demonstrator .............................................................. 6
Design proposal: Multi level four quadrant converter for the 5MW and 20MW versions ............................... 7
Subsea requirements for the converter ........................................................................................................ 7
Prototype small scale three level four quadrant converter .............................................................................. 8
Conclusion ......................................................................................................................................................... 9
Further Work ..................................................................................................................................................... 9
References ......................................................................................................................................................... 9
Appendix 1 Report – Power Electronics for WP3 DeepWind Project – September 2012 ............................... 10
Author: Ionut Trintis .................................................................................................................................... 10
1. Introduction ............................................................................................................................................... 3
2. Test Bench Converter for the 1 kW Floating VAWT Demonstrator........................................................... 3
2.1.
Test on Electrical Generator .......................................................................................................... 4
2.1.1.
No-Load Test .............................................................................................................................. 4
2.1.2.
Blocked Rotor Test..................................................................................................................... 5
2.1.3.
Calculated Machine Parameters................................................................................................ 5
2.1.4.
Mechanical Brake Test............................................................................................................... 5
2.2.
Test of the Power Converter with the SCIG................................................................................... 6
3. Design of the Full Scale Wind Turbine Converter ...................................................................................... 7
3.1.
Design Requirements .................................................................................................................... 8
3.1.1.
General Requirements............................................................................................................... 8
3.1.2.
Offshore Requirements ............................................................................................................. 8
3.1.3.
Subsea Requirements ................................................................................................................ 8
3.1.4.
Special Requirements ................................................................................................................ 9
3.2.
Converter Topologies .................................................................................................................... 9
3.3.
Internal and External Grid Connections of the Wind Farm ........................................................... 9
Conclusions and Future work ...................................................................................................................... 10
Appendix 2 Report - Control of a 5MW multilevel converter for direct drive wind turbine application .......... 0
Authors: Florin Valentin Traian Nica, Paul Dan Burlacu, Stoyan Shivachev .................................................. 0
Appendix 3 Report - Development of Modulation Strategies for NPC Inverter Addressing DC Link Balancing
and CMV Reduction ........................................................................................................................................... 0
Authors: Daniela Boian, Ciprian Biris ............................................................................................................. 0
Appendix 4 Report - Sensor less Control of PMSM Using Three Level NPC Converter ..................................... 0
Author: Florin Valentin Traian Nica ............................................................................................................... 0
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 2 of 29
Introduction
The DeepWind project is a study of a Darreius type VAWT system. The
blades cannot be pitch controlled to suit the wind and other
operational requirements such as braking. This means that the wind
turbine is stall regulated and the generator and its control system
together provide the means of controlling the power supplied to the
grid. They must also provide the braking force for normal and some of
the emergency braking. An additional requirement is that the Darreius
Wind Turbine is not self-starting meaning that the converter must be
able to start the generator as a motor and drive the Turbine up to
normal operating speed, when the function may revert to generating
mode.
Deliverable Description from DOW
D3.32) Design tools for submersible converter: Report on a four
quadrant, submersible electrical power converter developed and
designed for the 5MW and the 20 MW wind turbines. The converter is
to provide controllability and facilitate starting the turbine. A
submersible power converter is necessary for the 5 MW and 20 MW
machines. Electrical power regulation and electrical grid connection
will be determined and a control strategy proposed to enable direct
wind turbine rotor control. The power controller will be provided with
appropriate protection systems, e.g. for overvoltage and overcurrent.
Fig. 1 Artist's impression of
The wind energy controller will be provided by the control system
DeepWind
Turbine
neglecting
work package (WP4). Because of the complex arrangement of
Generator.
proprietary components in a power electronic converter, and the
continuing development of these components, necessitating new component models, it is not practical to
produce a software design tool. Therefore a report will be provided detailing the design strategy and design
rules. [month 43]
Converter functional modes
The converter for the 5 MW and 20 MW DeepWind wind turbines is required to operate in several different
modes.
1. Start the wind turbine from standstill and run up to speed. In this mode of operation the converter
will take power from the grid and use it to operate the generator as a motor that will drive the
wind turbine shaft up to speed as shown in Fig. 2. As the shaft speed approaches normal operating
speed, the wind power will take over the shaft drive and the motor load on the generator will be
reduced.
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 3 of 29
Turbine Controller
Electrical power
Mechanical power
Wind
power
Rotor
Power conversion
& transmission
Generator
Power electronics
Supply grid
Power conversion
Power conversion
& power control
Power
transmission
Fig. 2 Diagram of power flow in DeepWind system for starting the turbine. The generator is acting as a
motor.
2. Operate as a generator. In this mode, power is supplied to the grid at the frequency and voltage of
the grid. Power comes from the generator at a frequency and voltage that are determined by the
shaft speed. The shaft speed is controlled by the Turbine Controller to give the best power yield
corresponding to the actual wind speed. The required torque will vary correspondingly. Fig. 3 show
a diagram of the power flow when operating in this mode.
Turbine Controller
Electrical power
Mechanical power
Wind
power
Rotor
Power conversion
& transmission
Generator
Power electronics
Supply grid
Power conversion
Power conversion
& power control
Power
transmission
Fig. 3 Diagram of power flow in DeepWind system for normal operation. The generator is acting as a
generator.
3. Normal Braking Mode. If braking is required, to change speed or to stop the turbine rotor, the
generating torque will be increased beyond the torque available from the turbine. This will be
possible only if the grid is connected and is able to absorb the power. Energy will continue to be
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 4 of 29
supplied to the grid, by reducing the kinetic energy of rotation. Fig. 3 shows the power flow in this
mode of operation. The power flow is the same as for the normal generating mode.
4. Emergency braking mode #1. If braking is required, and the grid connection has been lost, the
generator will continue to generate voltage so long as the generator rotor is rotating. In this case
the generator side of the power electronics may be used to divert the output power into a dump
resistor in a controlled manner to ensure current and torque limits are not exceeded. Fig. 4
illustrates the power flow diagrammatically
Turbine Controller
Electrical power
Mechanical power
Wind
power
Rotor
Power conversion
& transmission
Generator
Power electronics
Dump Resistor
Power conversion
Power conversion
& power control
Energy Dump
Fig. 4 Diagram of power flow in DeepWind system for emergency braking #1 operation. The generator is
acting as a generator. The kinetic energy and converted wind energy is dissipated as heat in a controlled
manner, in the dump resistor.
5. Emergency braking mode #2. If braking is required, and the grid connection has been lost, the
generator will continue to generate voltage so long as the generator rotor is rotating. If the normal
duty power electronics is damaged, an emergency contactor may be provided to divert the output
power into a dump resistor in an uncontrolled manner to ensure that the turbine rotor speed is
reduced to an acceptable level. As the available control is negligible, this method may be expected
to damage essential components, such as the turbine blades, the permanent magnets, or the
generator windings. This method is to be used in extreme emergency only. Fig. 5 illustrates the
power flow diagrammatically.
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 5 of 29
Turbine Controller
Mechanical power
Wind
power
Rotor
Power conversion
& transmission
Electrical power
Generator
Dump Resistor
Power conversion
Energy Dump
Fig. 5 Diagram of power flow in DeepWind system for emergency braking #1 operation. The generator is
acting as a generator. The kinetic energy and converted wind energy is dissipated as heat in a controlled
manner, in the dump resistor.
6. Standstill mode. From time to time it will be necessary to ensure that the wind turbine rotor is
stationary and does not turn. This can be achieved by controlling the generator so that the
generator rotor does not rotate relative to the generator stator. Fig. 2 illustrates the power flow in
this this mode. The difference here in relation to mode 1 is that the control objective here, is to
hold the speed at zero.
7. Compliance with grid connection code. A major requirement is to provide voltage ride-through so
that the DeepWind electro-mechanical system will need to use energy stored in the system to
provide voltage ride-through power for the specified time. As a permanent magnet generator is
employed in DeepWind, the rotation of the turbine will always generate voltage enabling the
kinetic energy of rotating to be utilised for this purpose. Any shortfall in energy required for voltage
ride through will have to be compensated by using energy stored in the DC link capacitors. This
means that voltage ride-through must be considered as a part of simultaneous engineering of the
DeepWind drive chain.
Four quadrant two level converter for the DeepWind demonstrator
For the demonstrator, a commercial pulse width modulated two level converter was selected as a solution
that fulfilled most of the modes of operation cheaply and quickly. Modes 4 and 5 for emergency braking
were not fulfilled, but this was compensated by the fitting of a fail-safe brake on the generator shaft. Fig. 6
shows a diagram illustrating the 4 quadrant, 2 level converter applied here.
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 6 of 29
Generator side
converter
Grid side
converter
VAWT
Generator Filter
Grid Filter
Grid
Generator
Fig. 6 Diagram showing 2 level, 4 quadrant converter for 1 kW VAWT DeepWind demonstrator generator system.
The converter was bench tested with the induction generator and found to exhibit suitable performance for
the DeepWind VAWT demonstrator system. Designs and results are reported in detail in Appendix 1
Design proposal: Multi level four quadrant converter for the 5MW and 20MW versions
For the 5 MW and 20MW a multi-level, four quadrant converter was proposed. The selection process and
design criteria are described in Appendix 2. The four quadrant converter comprises two multi-level
inverters arranged back to back with a DC link. Inverter number 1, described in Appendix 3 converts the DC
to grid frequency and voltage and controls the power flow in all situations. Inverter number 2 converts the
frequency and voltage of the generator to DC. For both inverters, the power flow may be in either
direction, so that the generator can operate either as a generator or as a motor. This operation and the
change-over from one to the other are described in Appendix 4. In both inverters, as the DC link circuit is
common to them, the neutral point is clamped (NPC). This ensures an even voltage stress distribution
throughout. For design consideration, it was assumed that the grid voltage and frequency at the point of
connection was 13.5 kV and 50 Hz.
The selection of semiconductor ratings for the output devices will depend on the voltage and current
required and the cooling arrangement selected. As Power semiconductors are currently in a rapid state of
development, it is not possible to make an actual choice at this time, but silicon carbide field effect
transistors are a strong candidate (SiC).
It is unlikely that the energy storage capacitors of the DC link circuit will be dimensioned according to the
normal operational needs of DeepWind. It is more likely that the dimension of these will be decided by the
needs of the grid code for connection, and the kinetic energy in the DeepWind system available to satisfy
these needs.
Subsea requirements for the converter
In the subsea environment, the housing of the converter is the deciding factor that drives the chosen
basic components and materials. This can be classified in two categories: housing with pressure
compensation, or housing without pressure compensation. Due to the given timeline, the first
solution is considered where the housing will ensure the pressure compensation in order to be able
to make use of standard components.
Considering the installation of the power converter subsea, the following requirements must be met:
• Ensure housing to handle the pressure under the seawater at the site
• Ensure proper air conditioning in the converter location
• Reduced humidity in the ambient air to avoid condensation
• Cooling system with liquid preheating - to avoid condensation
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 7 of 29
•
•
•
Protect against corrosion - suitable surface treatment, cathodic protection
Ensure proper cooling - water to water heat exchangers with pressure compensators
Reinforced insulation
Prototype small scale three level four quadrant converter
To validate the proposal that a three level four quadrant converter is suitable for the DeepWind system,
two small scale inverters were designed, built and tested. One was to test the operation of the grid side
inverter, and the other was to test the operation of the generator side converter, given the DC link voltage.
These are described in detail in Appendix 3 and Appendix 4 respectively. The generator side converter was
tested in conjunction with the prototype small scale permanent magnet generator designed and built in the
DeepWind project.
Fig. 7 Photo of one of the small scale laboratory model inverters made for the DeepWind project tests (Appendix 3)
The three level inverters also clamp the neutral point voltage to ensure balance of the voltage stress on the
high power components.
For the grid side inverter of Appendix 3 an important feature is the control of common mode voltage and
total harmonic distortion. To this end a study of the effects of the different possible modulation strategies
was carried out. The results were published in [1], and Fig. 8 shows a table summarising the results. The
best all-round strategy tested was the Zero Small Medium Large vector (ZSML) strategy. The grid side
inverter was successfully tested thermally to 6 [kW] load.
For the machine side inverter of Appendix 4, it was considered important to obtain the highest possible
efficiency of energy conversion. This was obtained experimentally using a vector control strategy with an
added maximum torque per ampere (MTPA) strategy. The inverter was able to start the permanent magnet
generator reliably and the control was able to hold the speed steady within about 1.3% despite changes in
shaft torque in the ratio 20:1. The control is able to regulate the speed during a transition of load torque
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 8 of 29
from motoring to generating. Tests were also
carried out to check that emergency braking was
possible using the methods proposed. A
dedicated position estimator was required to
enable holding the shaft at zero speed.
Conclusion
A standard two level four quadrant converter was
used for the 1 kW DeepWind demonstrator
system. This worked very well.
For the 5 MW and 20 MW versions a three level,
NPC four quadrant converter was proposed,
comprising two back to back inverters. This was
Fig. 8 Table showing the effects of the different
partly because of the medium voltage of the grid,
modulation strategies on CMV and THD for the NPC three
higher than the industrial voltage usually
level inverter.[1], Appendix 3.
encountered on smaller wind energy generators.
Two identical demonstrator inverters were made and tested. Detailed design calculations were performed
prior to fabricating the inverters. One was tested as the grid side inverter and the other was tested as the
generator side inverter, using the DeepWind prototype generator as generator.
Simulations of the inverter performance in steady state and dynamic events were performed and the
results were compared favourably with the test results. In this way the design process has been mapped
out. In case 5 MW and 20 MW versions are required to be made, the design process is unchanged,
however, the characteristics of the devices used and the mounting and cooling techniques used will be
suited to the rating of the inverter to be designed.
The terms of the description of the deliverable are satisfied.
Further Work
A number of facilities remain to be tested.
• Test the two inverters back to back.
• Add a dump resistor to the DC link, with activation circuit.
• Add dump resistors to the generator terminals with an activation circuit.
• Investigate encapsulation of the power electronics. Will it make the circuits withstand condensation?
Will it make the circuits withstand immersion?
• Test encapsulated inverters in a suitable ambient.
References
[1] Boian, Daniela, Ciprian Biris, Remus Teodorescu, and Michal Sztykiel. "Development of modulation
strategies for NPC converter addressing DC link voltage balancing and CMV reduction." In Power
Electronics for Distributed Generation Systems (PEDG), 2012 3rd IEEE International Symposium on, pp.
828-835. IEEE, 2012.
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 9 of 29
Appendix 1 Report – Power Electronics for WP3 DeepWind Project – September 2012
This report addresses work on the four quadrant converter supplied for the DeepWind 1 kW demonstrator
and tests with the corresponding generator. Supplementary work reported covers the initial consideration
of the converter required for the 5 MW and 20 MW versions.
Author: Ionut Trintis
Ewen Ritchie
DeepWind WP3 D3.32 – Technical Report – Submersible Converter
Page 10 of 29
Report – Power
Electronics
For WP3 DeepWind Project
– September 2012 –
Ionut Trintis
Synopsis
This report addresses work on the four quadrant converter supplied for the DeepWind 1 kW
demonstrator and tests with the corresponding generator.
Supplementary work reported covers the initial consideration of the converter required for the 5 MW
and 20 MW versions.
Table of Contents
........................................................................................................................................................................... 1
DeepWind WP3 D3.32 – Technical Report – Submersible Converter ............................................................... 2
Introduction ....................................................................................................................................................... 3
Deliverable Description from DOW ............................................................................................................... 3
Converter functional modes .............................................................................................................................. 3
Four quadrant two level converter for the DeepWind demonstrator .............................................................. 6
Design proposal: Multi level four quadrant converter for the 5MW and 20MW versions ............................... 7
Subsea requirements for the converter ........................................................................................................ 7
Prototype small scale three level four quadrant converter .............................................................................. 8
Conclusion ......................................................................................................................................................... 9
Further Work ..................................................................................................................................................... 9
References ......................................................................................................................................................... 9
Appendix 1 Report – Power Electronics for WP3 DeepWind Project – September 2012 ............................... 10
Author: Ionut Trintis .................................................................................................................................... 10
1. Introduction ............................................................................................................................................... 3
2. Test Bench Converter for the 1 kW Floating VAWT Demonstrator........................................................... 3
2.1.
Test on Electrical Generator .......................................................................................................... 4
2.1.1.
No-Load Test .............................................................................................................................. 4
3.
2.1.2.
Blocked Rotor Test..................................................................................................................... 5
2.1.3.
Calculated Machine Parameters................................................................................................ 5
2.1.4.
Mechanical Brake Test............................................................................................................... 5
2.2.
Test of the Power Converter with the SCIG................................................................................... 6
Design of the Full Scale Wind Turbine Converter ...................................................................................... 7
3.1.
Design Requirements .................................................................................................................... 8
3.1.1.
General Requirements............................................................................................................... 8
3.1.2.
Offshore Requirements ............................................................................................................. 8
3.1.3.
Subsea Requirements ................................................................................................................ 8
3.1.4.
Special Requirements ................................................................................................................ 9
3.2.
Converter Topologies .................................................................................................................... 9
3.3.
Internal and External Grid Connections of the Wind Farm ........................................................... 9
Conclusions and Future work ...................................................................................................................... 10
Appendix 2 Report - Control of a 5MW multilevel converter for direct drive wind turbine application .......... 0
Authors: Florin Valentin Traian Nica, Paul Dan Burlacu, Stoyan Shivachev .................................................. 0
Appendix 3 Report - Development of Modulation Strategies for NPC Inverter Addressing DC Link Balancing
and CMV Reduction ........................................................................................................................................... 0
Authors: Daniela Boian, Ciprian Biris ............................................................................................................. 0
Appendix 4 Report - Sensor less Control of PMSM Using Three Level NPC Converter ..................................... 0
Author: Florin Valentin Traian Nica ............................................................................................................... 0
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 1 of 29
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 2 of 29
1. Introduction
This progress report presents a brief status and summary on the work related to the power electronic
converters used in the DeepWind project.
The report is divided in two parts. The first part is related to the test bench used for the small scale project
demonstrator, where a wind power converter system was realized to drive the generator. The second part
presents the design of the wind power converter system, to be used in the full scale offshore floating
vertical axes wind turbine (VAWT).
2. Test Bench Converter for the 1 kW Floating VAWT Demonstrator
The wind power converter system used in the test bench is shown in Figure 2.1. It is based on the full scale
conversion, meaning that the whole electrical power generated by the squirrel-cage induction generator
(SCIG) is converted to be delivered to the power grid. The electrical generator speed is controlled by the
AC-DC generator converter and the resulting electrical energy is rectified to a common DC level with the
DC-AC grid converter. The DC-AC grid converter is synchronized with the power grid, and delivers the
generated power at unity power factor.
AC
DC
Gear-box
(optional)
SCIG
Grid
DC
Pref
AC
Qref
Figure 2.1. Wind turbine system with full scale power converter
The detailed schematic of the wind power conversion system is shown in Figure 2.2. The wind turbine is
located offshore and floating, and the SCIG is installed subsea at the bottom of the wind turbine in a sealed
case. The power converter is located onshore, and therefore there will be a long cable between the
generator and converter. For this reason, a generator filter (du/dt filter) is required to reduce the
overvoltage on the generator windings created by the long cable.
Generator
Filter
Generator
Grid
Filter
Grid
Figure 2.2. Two-level back-to-back full scale voltage source converter system
The power converter consists of two back-to-back two-level DC-AC converters with a common DC-bus. The
AC voltage levels for both converters is 400V line-to-line RMS, and therefore the transistors used are 1200V
insulated gate bipolar transistors (IGBTs) and 1200V diodes. The grid converter controls the grid current in
phase with the grid voltage and the common DC-bus voltage level. A grid filter is installed on the grid side
to reduce the harmonics of the current injected into the grid.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 3 of 29
2.1.
Test on Electrical Generator
Tests on the SCIG have been done to verify the functionality and to determine the electrical parameters. A
test setup was realized with the generator coupled mechanically with a DC motor, see Figure 2.3. A torque
transducer was installed in the mechanical assembly to measure the mechanical torque, speed and power.
Figure 2.3. Electrical generator test setup
To determine the electrical parameters, the no-load and blocked rotor tests have been done. The machine
parameters are given in Table 2.1.
Number of phases
HS rated power (kW)
Rated current (A)
No-load current (A)
Rated torque (N.m)
Starting torque (N.m)
Maximum torque (N.m)
Rated speed (min-1)
FCR J02 Brake torque (N.m)
Main voltage (V)
Connection
Starting type
Motor winding (V)
Rated Frequency (Hz)
Operation position
Index of protection
Index of cooling
Insulation class
3
1.100
2.5
1.4
7.35
12.00
15.00
1429
20.00
400
DY
DOL
230VD/400VY
50
IM3601(IMB14)
IP55
IC411
F
Table 2.1. SCIG parameters (integrated mechanical brake)
2.1.1. No-Load Test
Balanced voltages at the rated frequency (50Hz) are applied to the machine stator varying the line-to-line
voltage from 0 to 400V. The characteristics of current and power as a function of the applied voltage are
shown in Figure 2.4.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 4 of 29
I=f(V)
[A]
2,5
250
2
200
1,5
150
1
100
0,5
50
0
0
100
P=f(V)
[W]
200 [V] 300
400
0
0
200 [V]
100
300
400
Figure 2.4. No-load test results
2.1.2. Blocked Rotor Test
Balanced voltages are applied to the machine stator, while the rotor is mechanically blocked to prevent
rotation. The current and power characteristics as a function of the applied voltage are shown in Figure 2.5.
I=f(V)
P=f(V)
[A]
[W]
5
1000
4
800
3
600
2
400
1
200
0
0
50
[V]
100
0
150
0
50
[V]
100
150
Figure 2.5. Blocked rotor test results
2.1.3. Calculated Machine Parameters
Based on the above test results, the machine equivalent circuit parameters can be calculated. In Figure 2.6,
and equivalent circuit with the calculated values is shown. The parameters are calculated in Ohms at the
rated frequency (50 Hz).
=
Rs 12.8 Ω
X=
7.5 Ω
ls
2.7 Ω
X=
7.5 Ω R=
r
lr
+

im

vs

j (ω − ωr )ϕr
-
+
-
+

is

jωϕ s

ir
=
X m 148.9 Ω
Figure 2.6. SCIG equivalent circuit for an arbitrary phase, in the arbitrary reference frame
2.1.4. Mechanical Brake Test
In order to break the generator and therefore the wind turbine in case of too high wind speed, or in case of
loss of the power supply, a mechanical brake is installed at the generator axe. The mechanical brake it is
normally coupled if the built-in DC coil is not supplied. Having the generator brake supplied from the same
electrical grid, in Figure 2.7 the mechanical torque given by the brake in case of the power supply for the
DC coil, while the machine operates at nominal speed with no load.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 5 of 29
Brake Torque Test
12
Torque [Nm]
10
8
6
Supply
Loss
4
2
0
18.9
19
19.1
19.2
19.3
19.4
19.5
Figure
Time [s]
2.7. Mechanical Brake Test
2.2.
Test of the Power Converter with the SCIG
The back-to-back power converter test setup is shown in Figure 2.8. The grid converter is controlling the
grid current at unity power factor, and maintains the total harmonic distortion below 5% as imposed by the
standards and controls the DC-link voltage level to around 570 V (with 2% more than the peak line-to-line
voltage)
Grid
Filter
Generator
Filter
Grid
Converter
Generator
Converter
Figure 2.8. Back-to-back power converter test setup
The measured grid voltage and grid current during the operation of the electrical generator is shown in
Figure 2.9. It can be noticed the unity power factor operation, and low distortion level.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 6 of 29
Figure 2.9. Grid Converter Operation
The operation of the generator, while controlled by the power converter, can be seen in Figure 2.10.
Figure 2.10. Generator Converter Operation
3. Design of the Full Scale Wind Turbine Converter
A design of 5 MW wind power converter will be considered for the full scale turbine. Considering the
choices on the generator side, such as squirrel-cage induction generator or permanent magnet
synchronous generator the full scale power converter will be considered (total electrical power is
processed). During the design process, the possibility to upscale in power up to 20 MW is taken as a
background requirement.
The considered general structure of the wind turbine with full scale converter is shown in Figure 3.1. As
main components, the followings can be enumerated: rotor, optional gear-box depending on the generator
design, electrical generator, AC-DC generator converter, DC-AC grid converter, common DC-bus, and boost
transformer.
AC
DC
Gear-box
(optional)
SCIG
PMSG
Pref
Grid
DC
AC
Qref
Pitch
Figure
3.1. Wind turbine system with full scale converter
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 7 of 29
3.1.
Design Requirements
The requirements of the converter design are directly linked to the desired location of the installation, and
the configuration. It is clear that the converter must be designed for the offshore application, the same as
for the generator. The electrical generator must be located subsea, considering the floating structure of the
VAWT. However, regarding the electrical configuration, the following aspects can be distinguished with
regard to the power converters location in the wind turbine:
1. Converter located above sea level  Generator connected with long cables to the AC-DC generator
converter. This case will require a dV/dt filter between the generator and the generator converter
to reduce the overvoltage on the generator’s windings.
2. Generator converter located close to the generator, subsea, and grid converter located above sea
level having the DC-links of the two converters connected with a DC cable
3. Converter located subsea with boost transformer located above sea level
4. Converter located subsea with boost transformer located subsea
3.1.1. General Requirements
As a state of the art wind turbine converter, the following requirements have to be met:
• Operation with wind speeds on a broad range
• Ability to operate under weak grid conditions
• Ensure low harmonic content on the generator and grid
• Grid compatibility  Comply with the grid codes at the turbine/farm point of common coupling
• Low voltage ride through capability
• Grid support with reactive power on demand
3.1.2. Offshore Requirements
Considering the location of the wind turbine in the harsh conditions created by the sea, the following
requirements have to be met:
• High reliability  Maintenance and Service are difficult and costly  must be reduced
o Remote Operated Vehicles or Robots for maintenance and monitoring?
• High availability  Low downtime  increase energy production
o Redundancy of some components is justified
• Safety  Overspeed, overvoltage and overcurrent protections
• Remote monitoring and sensing
3.1.3. Subsea Requirements
In the subsea environment, the housing of the converter is the deciding factor that drives the chosen basic
components and materials. This can be classified in two categories: housing with pressure compensation,
or housing without pressure compensation. Due to the given timeline, the first solution is considered where
the housing will ensure the pressure compensation in order to be able to make use of standard
components.
Considering the installation of the power converter subsea, the following requirements must be met:
• Ensure housing to handle the pressure under the seawater at the site
• Ensure proper air conditioning in the converter location
o Reduced humidity in the ambient to avoid condensation
• Cooling system with liquid preheating  to avoid condensation
• Protect against corrosion  proper paint, cathodic protection
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 8 of 29
•
•
Ensure proper cooling  water to water heat exchangers with pressure compensators
Reinforced insulation
3.1.4. Special Requirements
In the new turbine concept based on Darrieus VAWT, due to the mechanical construction and functionality,
the following aspects need to be considered:
• Suitable for the required wind turbine speed control to increase the harvesting energy
• Braking using the electrical generator capabilities  Reduce the braking torque on the additional
installed mechanical brake
• Overspeed protection and handling
• Handling of fault situations
o Grid loss  auxiliary power supply with enough installed power and energy capacity
o Safe/Soft Shutdown Sequence
3.2.
Converter Topologies
Considering the defined design requirements, a survey on the suitable converter topologies is in progress.
The topology must allow a reliable construction of the 5 MW converter system and scalability up to 20 MW.
The state of the art power converters for wind turbines up to 5 MW make use of the low voltage
technologies. However, the 5MW power range is the border between low voltage and medium voltage
power electronics.
The shift to medium voltage technologies becomes relevant in order to reduce the current levels and
therefore reduce the amount of copper and copper losses in the connections. Moreover, having the
perspective of the 20 MW power range the medium voltage becomes very relevant. However, the reliability
and availability of such a converter must be very high and this is a well-known design challenge.
3.3.
Internal and External Grid Connections of the Wind Farm
In the design of the full scale wind turbine, the connections in a future wind farm and the wind farm
connection to the shore must be considered. When considering the internal connections in the farm, the
state of the art is the medium voltage AC bus. Proposals to replace the AC with DC distribution inside the
wind farm have been done. However, a DC-DC converter to convert the power bidirectional from HVDC to
MVDC with high power and high reliability does not exist yet in industry. Therefore, the most easy and
industry available solution to boost the voltage up to the highest levels is done in AC. The typical
configurations for the offshore wind farms depending on the distance to shore are shown in Figure 3.2. For
short distances to shore, the investment and the conversion to HVDC is not justified and therefore the
HVAC connection like in Figure 3.2.(a) is chosen. For long distances to shore, the investment in a HVDC
transmission line starts to be justified. The typical wind farm connection via HVDC can be seen in Figure
3.2.(b).
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 9 of 29
(a) With HVAC connection for short distances to shore
(b) With HVDC connection for long distances to shore
Figure 3.2. Offshore wind farm connections
Conclusions and Future work
The power converter and generator systems, for the 1 kW demonstrator, were tested at Aalborg University,
Department of Energy Technology. The operation is according to expectations, and expected to be similar
on the field test with the wind turbine system.
The generator system was delivered in July to our project partners in Risø, and the expected commissioning
is scheduled to be in October 2012.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 10 of 29
The design of the full scale wind turbine converter was started by setting up the requirements for the
present application. The reliability and availability of the system are key points for the converter system in
the offshore application. Therefore, the next step is to identify the suitable converter topologies that
comply with the given requirements. The converter system design will take into account also the grid
connection inside the future wind farms, and the external connection to shore.
Ionut Trintis
WP3 – DeepWind – Progress Report – September 2012
Page 11 of 29
Appendix 2 Report - Control of a 5MW multilevel converter for direct drive wind
turbine application
This report proposes a multi-level, four quadrant converter as a possible solution for the control of a 5 MW
wind turbine generator. A method to design multilevel neutral point clamped (NPC) converters according to
different power ratings is also proposed.
The system comprises a wind turbine, a permanent magnet synchronous generator, a back to back three
level NPC converter and the grid. A mathematical model of each element of the system was built and
control strategies were implemented.
The generator side converter is controlled in such a way that a field oriented control (FOC) technique is
applied to the generator. A current control is applied to the grid side converter and a PLL control technique
is used for grid synchronization and active and reactive power control.
The different simulations and results presented in the project were carried out considering different wind
speeds. Results are presented under different working conditions, such as normal working conditions and
grid fault working conditions.
Authors: Florin Valentin Traian Nica, Paul Dan Burlacu, Stoyan Shivachev
Control of a 5MW multilevel converter for direct
drive wind turbine application
Authors:
2013
Supervisors:
Stoyan Shivachev
Ewen Ritchie
Paul Dan Burlacu
Weihao Hu
Florin Valentin Nica
Krisztina Monika Leban
Aalborg University
Department of Energy Technology
Title:
Control of 5MW multilevel converter for direct drive wind turbine
application
Project period:
1 February 2013 – 30 May 2013
Authors:
Florin Valentin Traian Nica
Paul Dan Burlacu
Stoyan Ivelinov Shivachev
Supervisors:
Ewen Ritchie
Weihao Hu
Leban
Krisztina Monika
Synopsis
A possible solution for the control of a 5 MW wind
turbine generator system is studied in this report. A
method about how to design multilevel neutral point
clamped (NPC) converters according to different power
ratings is also proposed.
The system is composed of a wind turbine, a permanent
magnet synchronous generator, a back to back three
level NPC converter and the grid. A mathematical model
of each element of the system was built and control
strategies were implemented.
The generator side converter is controlled in such a way
that a field oriented control (FOC) technique is applied to
the generator. A current control is applied to the grid
side converter and a PLL control technique is used for
grid synchronization and active and reactive power
control.
The different simulations and results presented in the
project were carried out considering different wind
speeds. Results are presented under different working
conditions, such as normal working conditions and grid
fault working conditions.
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND TURBINE APPLICATION
Preface
This 8th semester report was conducted by power electronics and drives and wind power
systems students at the Department of Energy Technology, Aalborg University. The project
started on 1st of February and finished on 30th May 2012. The project theme is “Control of
Converter-fed AC Drives”.
The project, named “Control of a 5MW multilevel converter for direct drive wind turbine
application”, was chosen from the different project proposal presented at the beginning of the
semesters. It has as a main purpose to enhance the student’s knowledge in designing,
modelling, analysis and simulation of the power electronics control systems.
The authors have different cultural backgrounds, each of them coming from different
countries.
The text is divided into seven chapters plus 2 appendixes.
We will like to show our gratitude to our supervisors for their support during the entire project
work.
We will like also to thank the Aalborg Department of Energy Engineering for the possibility that
they offered us to develop in the field that we have chosen.
Authors,
Florin Valentin Traian Nica
Paul Dan Burlacu
Stoyan Ivelinov Shivachev
Group PED2-841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Table of contents
Table of contents....................................................................................................................... 6
Chapter 1 ....................................................................................................................................... 1
Introduction .................................................................................................................................. 1
1.1 Background and evolution of wind power systems. ........................................................... 1
1.2. DeepWind project. ............................................................................................................. 3
1.1. Project statement and objectives. ..................................................................................... 5
1.1.
Project limitations. ........................................................................................................ 6
Chapter 2 ....................................................................................................................................... 7
Converter and electrical machine parameters determination ..................................................... 7
2.1.
Converter topology selection. ....................................................................................... 7
2.2 Multilevel NPC converters................................................................................................. 11
2.2.1 Three level neutral point clamped converter. ........................................................... 11
2.2.2 n level topologies for NPC. ......................................................................................... 13
2.3. PMSG parameters estimation. ......................................................................................... 17
Chapter 3 ..................................................................................................................................... 25
System description and modelling .............................................................................................. 25
3.1 Grid Model ........................................................................................................................ 25
3.2 Level NPC Convertor Model .............................................................................................. 27
3.3 Dynamic Model of a Synchronous Permanent Magnet Machine ..................................... 30
3.3.1. dq model of the PMSM ............................................................................................. 30
3.4 Wind Turbine. .................................................................................................................... 32
Chapter 4 ..................................................................................................................................... 35
System Control ............................................................................................................................ 35
4.1.
Rectifier control........................................................................................................... 35
4.1.1. Current controllers .................................................................................................... 36
4.1.2. DC voltage controller................................................................................................. 41
4.1.3. Reactive power controller ......................................................................................... 45
4.2.
Machine Control .......................................................................................................... 48
4.2.1. Current Controllers.................................................................................................... 49
4.2.2. Speed Controller........................................................................................................ 53
Chapter 5 ..................................................................................................................................... 59
Simulation Results ....................................................................................................................... 59
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
5.1. Normal operation ......................................................................................................... 59
5.2. Stopping the turbine .................................................................................................... 61
5.3. Starting the turbine ...................................................................................................... 65
5.4. Voltage dip situation .................................................................................................... 69
5.5. Normal working condition with the converter model ................................................. 74
Chapter 6 ..................................................................................................................................... 77
Converter design ......................................................................................................................... 77
6.1. Define the system specifications.................................................................................. 77
6.2. DC Bus Voltage calculation ........................................................................................... 78
6.3. Calculation of the switching devices and free-wheeling diodes .................................. 79
6.4. Calculation of the clamping diodes for the converter ................................................. 80
6.5. Calculation of the dc-bus capacitors ............................................................................ 80
Chapter 7 ..................................................................................................................................... 83
Conclusions and future work ...................................................................................................... 83
7.1. Conclusions ...................................................................................................................... 83
7.2. Future Work ..................................................................................................................... 84
References................................................................................................................................... 87
Converter design program .......................................................................................................... 90
Semiconductors used in the design program.............................................................................. 94
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 1
Introduction
In the present chapter introductory concepts and background of wind energy are
presented. This sets the scenario where the DeepWind project is born. Project formulations,
project limitations and project objectives are presented at the end.
1.1 Background and evolution of wind power systems.
The conventional energy sources as coal, oil or natural gases are finite and generate a
high amount of pollution. Because of these reasons research in alternative energy sources has
been rapidly increasing in the last few years. Alternative renewable energy sources like wind,
solar, biomass or geothermal are clean and widely available in the nature [1], [2].
Wind energy is one of the major sources of renewable energy in the world. The
energy obtained from the wind is clean and emission free. It has none of the polluting effects
associated with the conventional energy sources. The energy of the wind is converted into
electrical energy by the wind turbines, which cause virtually no emissions during their
operation and a small amount during their manufacturing, installation, maintenance and
removal [1], [2].
For the last 10 years wind energy has been one of the fastest growing energy
technologies worldwide [1], [2]. Some of the factors that contributed to this rapid growth
include falling cost of wind energy, state legislative requirements for greater use of renewable
energy and the benefits of the wind energy in competitive renewable energy markets [1], [2].
From Figure 1 and Figure 2 it can be seen how wind power installed worldwide has
been steadily increasing over the last years. Nowadays there are over 300.000 MW of wind
power energy installed over the world and the trend is to keep increasing the amount of wind
farms and the electrical power generated form wind energy even more [1].
As a consequence of this general growth in the wind power market new ideas in the
field are studied and subjected to research. The DeepWind project is one of these ideas and it
studies a new concept of off-shore large power wind turbines.
PED2 - 841
Page 1
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
MW
1996
1997
1998
1999
2000
2001
2002
2003
2005
2006
2007
2008
2009
2010
2011
2012
2004
45000
40000
35000
30000
25000
20000
15000
10000
5000
0
Year
Figure 1. Global annual installed wind capacity 1996-2012 [3].
MW
1996
1997
1998
1999
2000
2001
2002
2003
2005
2006
2007
2008
2009
2010
2011
2012
2004
300000
250000
200000
150000
100000
50000
0
Years
Figure 2. Global cumulative installed wind capacity 1996-2012 [3].
PED2 - 841
Page 2
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
1.2. DeepWind project.
The DeepWind project consists of designing an offshore wind turbine with a power
ranging from 5 to 20 MW which can operate in water depths of more than 150 meters.
The type of wind turbine selected to be
used in this project is a floating vertical axis wind
turbine, also known as Darrieus wind turbine. The
wind turbine will be anchored to the bottom of the
sea while the entire structure will be floating like a
buoy. The concept can be seen in Figure 3. The
generator will be directly connected to the axis of
the turbine. Because of this topology, the generator
will have to be placed under the water, at the
bottom of the structure.
The placement of the wind turbine in the
water raises a number of problems for the
generator, which have to be taken into account in
the design process. Some of the problems
encountered are:

the enclosure of the generator (totally
enclosed and tight or totally open and filled
with sea water);

the maintenance, because of the depth at
which the generator is operating any
maintenance operation will demand a large
economical and technical effort;

the control, no pitch control can be applied for this type of turbine because of its
geometry and also different problems with the mechanical brake appear because the
structure is placed under the water, etc;
Figure 3. Darrieus wind turbine
(concept selected for the Deep Wind
Project)
In order to capture sufficient amount of wind to produce the electrical power
requested by the project, the scale of the entire wind turbine has to be very large. To get a
sense of the entire size a schematic with the dimensions of the wind turbine is presented in
Figure 4. The dimensions according to the drawing are placed in Table 1.
It should be noted that this is only an initial design of the wind turbine and the
dimensions could differ for the final design. As it can be seen the total length of the wind
turbine is 253 meters. Constructing and putting together the entire structure will represent a
magnificent task.
PED2 - 841
Page 3
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
D1
after the proper rotating speed is
reached, which depends on the wind
speed, the turbine will produce a
torque in opposite direction and the
machine will act as a generator;


Mean water level
pitch control cannot be applied for this
geometry, the entire structure will have
to be controlled using the generator;
the size and weight of the entire
structure creates a very large moment
of inertia which will affect the way the
generator has to be controlled;
the stopping of the turbine cannot be
made using traditional mechanical
brakes, the generator has to be able to
stop the entire structure from rotating;
H3

H0

H1
the Darrieus turbine type is not selfstarting, even when the wind is
powerful enough to maintain the
rotational speed. The generator has to
accelerate the turbine until certain
speed is reached. During the starting
procedure, the machine will be working
as a motor and power will be consumed
from the grid [4];
H2

HR
This topology of the wind turbine carries the
following technical problems which need to be
solved by controlling the generator:
D2
Figure 4. Darrieus wind turbine (placement
in the water and dimensions).
Geometry of the tower above sea level [m]
Total length above sea level (
)
Clearance from mean water level ( )
Diameter of the tower ( )
Thickness of the tower
Geometry of the tower below sea level [m]
Total length below sea level
Length of the slender part ( )
Thickness of the slender part
Length of the tapered part ( )
Length of the bottom part ( )
Diameter of the bottom part ( )
Thickness of the bottom part
145
15
3.15
0.02
108
5
0.02
10
93
4.15
0.05
Table 1. Dimensions of Darrieus Wind Turbine
PED2 - 841
Page 4
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
1.1. Project statement and objectives.
This master project is developed based on the DeepWind Project. The study of a
design method of a back to back power electronic converter needs to be carried out and the
control strategies for it implemented. One side of the converter will be connected to a
synchronous permanent magnet generator and the other side will be connected to the grid.
The main objectives for this project are:

propose a power converter topology capable to ensure a full four quadrant control
of the generator;

for the selected topology a design process has to be created (general recipe) which
can be used to build the converter for different power levels and will enables the
user to get a feeling about how to approach a converter design;

propose control strategies in order to operate the converter in normal and abnormal
working conditions for the wind turbine;

The control strategies will be implemented for only four situations:


Normal conditions (the turbine works in nominal condition and it is
connected to the grid);

Abnormal conditions:
- starting the turbine;
- stopping the turbine while a connection to the grid exists;
- fault in grid voltage (voltage dip);
build the models of the different elements of the system in MATLAB Simulink and
implement the control strategies for them;
PED2 - 841
Page 5
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
1.1. Project limitations.

This project will focus only on the theoretical converter design and the control
applied for the converter;

Only one converter topology will be discussed and analysed for different power
levels;

No MPPT strategy will be implemented in the control;

The input and output filters of the converter will not represent a part of this project;

This project is focused on the mathematical modelling of the control system, hence,
switching strategy and switching frequency selection have not been taken into
account.

The thermal study of the converter will not be covered by this project;
PED2 - 841
Page 6
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 2
Converter and electrical machine parameters
determination
The two main parts of the system are the power electronic converter and the
electrical machine. The first step carried out in the project was to study the different
topologies of the multilevel converters and select the most suitable one for our purpose. In
order to gain a deep understanding of them research and study of the fundamental working
principles have been carried out.
2.1. Converter topology selection.
To achieve the objectives of this project a converter topology has to be selected in
order to enable the application of different control strategies for the generator.
Because the purpose of this project is not focused on presenting convertor
topologies, only a very brief presentation of the main topologies will be made along with their
advantages and disadvantages.
After a thorough research on the literature the direction for the high power
converters implemented in wind applications seems to be very clear towards the multilevel
converters[5]-[8].
From the different multilevel converters presented in the literature mainly three
topologies have managed to impose themselves as a viable solution to be implemented in the
industry. The three topologies are the neutral point clamped (NPC), flying capacitor and
cascaded H bridge which are presented below. The main advantages and disadvantages for
each topology will be presented in order to decide on the most attractive option for this
project.
PED2 - 841
Page 7
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION

Neutral Point Clamped (NPC)
Vdc/2
S1
C1
D1
S2
n
Vdc
a
D2
C2
S1'
S2'
-Vdc/2
Figure 5. Neutral Point Clamped (NPC).
The layout of this topology is shown in Figure 5. The advantages that make this topology
appropriate are [5], [6], [8]-[20]:
-
The harmonic content is reduced because the topology adds the zero level to the
output of the voltage [9];
-
This topology can be extended to any number of levels by inserting additional
capacitors and diodes;
-
Relatively small DC link capacitor;
-
Simple power circuit topology;
-
Low number of components compare to the other two;
-
Easy to implement protection and modulation schemes leading to a smaller footprint
[10];
-
Highest convertor efficiency among the available solutions implemented in the
industry [15];
-
The back-to-back topology for regenerative applications can be implemented because
all the phases share a common DC bus;
-
This topology is one of the most widely used in MV applications where it has shown its
capabilities [12], [14], [15], [20], [21].
The disadvantages are:
-
A problem appears in balancing the capacitor voltage for high levels, which made the
implementation of the converter to be mostly used for three levels [9].
-
This topology features medium/high voltage devices [integrated gate-commutated
thyristor (IGCT) and medium/high voltage insulated gate bipolar transistors (IGBTs)].
PED2 - 841
Page 8
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION

Flying Capacitor (FLC)
Vdc/2
S1
C2
S2
n
Vdc
C1
a
S1'
C2
S2'
-Vdc/2
Figure 6. Flying Capacitor (FLC)
The advantages that make this topology appropriate for this project are:
-
Symmetric switching loss distribution;
-
Reduced cost of flying capacitors.
The disadvantages are:
-
The capacitors must be pre-charge at the start time and the capacitors voltage must be
balanced.
-
This topology is impractical at very low switching frequencies because the required
capacitance increases with inverse proportion to the switching frequency [22].

Cascaded H Bridge (CHB)
S1
S3
Vdc
Van
S2
S4
Figure 7. Cascaded H-Bridge (CHB)
The advantages that make this topology appropriate for this project are:
-
The output voltage
has three states:
. Compared to the other two it
can deliver at the output the entire input voltage;
-
It uses exclusively low voltage IGBTs;
PED2 - 841
Page 9
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
-
It reaches higher voltage and higher power levels;
-
The switch power rating and the stored energy in the LC filter are reduced compared
to the other typologies [15];
-
Due to its modular construction it can be used in high-power and high-quality
applications.
The disadvantages are:
-
In order to achieve a regenerative option it needs a higher number of devices [14].
-
It requires a large number of isolated power supplies, the only alternative being a
phase shifting transformer, which increases significantly the price of the entire
structure [9], [14].
-
For the grid part a complicated grid transformer is needed, which increases the DC-link
capacitance [9];
-
Complex control strategies.
Based on the analysis made for every topology the conclusion was to use the neutral
point clamped converter. After deciding on this matter the entire structure of the converter is
displayed in Figure 8 for a better understanding of the system.
+
+
-
WIND TURBINE
UTILITY GRID
Figure 8. Multilevel back-to-back converter for a direct connection of a wind turbine to the
utility grid.
PED2 - 841
Page 10
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
2.2 Multilevel NPC converters.
Multilevel converters are finding increased usage in the industry as one of the
preferred choices of power electronic conversion for high power applications. For a medium
voltage grid, it is troublesome to connect only one power semiconductor switch directly. As a
result, a multilevel power converter structure has been introduced as an alternative in high
power and medium voltage systems. The basic concept of a multilevel converter to achieve
higher power is to use a series of power semiconductor switches with several lower voltage DC
sources to obtain the required power conversion by combining a staircase voltage waveform.
The commutation of the switching devices combine the output of this multiple DC sources in
order to achieve higher voltage levels at the output terminal, however the rated voltage of the
power semiconductors that they should be able to withstand depends only on the rating of the
DC voltage source which they are connected to and not the output voltage level of the
converter [23]-[25].
2.2.1 Three level neutral point clamped converter.
M2 idc2
T2a
DT2a
T2b
.
.
idc1
T’2b
T’2a
.
D1b
Uc1
D1c
T’1b
T’1c
.
T’1a
.
.
-
T’2c
.
D1a
C1
DT1c
T1c
.
M1
DT1b
T1b
.
Udc
D2c
D2b
DT1a
DT2c
.
D2a
T1a
T2c
.
Uc2
C2
DT2b
.
+
M0 idc0
a
b
c
Figure 9. Three-Phase Three-Level Neutral Point Clamped Converter.
PED2 - 841
Page 11
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
A three level NPC converter consists of 2 capacitors on the DC bus, 12 unidirectional
active switches each with its own free-wheeling diode and 6 neutral point clamped diodes
[26].
The main benefit of this configuration is that while there are twice as many switching
devices as in the two level converter topology each of the switches must block only half of the
DC link voltage
[26].
In the NPC converter in order to produce three voltage levels, the switching devices
are controlled in such a way that only 2 of the 4 switches in each phase leg are conducting at
any given time. Basically each of the phase nodes a, b and c can be connected to any node in
the capacitor bank M0, M1 and M2 thus the number of the different switching states is:
Eq. 1
,where “N” is the number of voltage levels in the DC link and “
” the number of phases.
Connection of phase “a” to point M0 and M2 can be accomplished by switching both
switches T1a and T2a on or off. This will yield a phase voltage of U=
Uc1=Uc2=
or U= -
considering
. The connection to the junction point M1 is done by switching on T1a and
switching off T2a .Since the switching devices are always turned in pairs the complement
switches are named accordingly T’1a and T’2a [26].
From Figure 9 it can be seen that with this particular switching in the circuit the
phase a current ipha will flow into the junction point through the diode D1a if it is negative and
out of it through D2a if it is positive. The switching positions for the three possible voltages are
given in Table 2.
state
T1x
T2x
T'1x
T'2x
"+"
on
on
off
off
"0"
on
off
off
on
"-"
off
off
on
on
Table 2. Switching positions for one phase of the three level NPC.
The current paths for the positive, negative and zero states are shown in Figure 10. In
zero state the direction of the phase current dictates whether the upper or lower path of the
neutral tap is utilized. Thus both switches T1x and T’2x have to be turned on in zero state “0”to
provide an open path in case the phase current reverses. In any state 2 active switches or 2
diodes lie in series within the current path depending if it is a positive “+”or negative “-“state
[26].
PED2 - 841
Page 12
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
DT2x
.
Udc/2
Udc/2
D2x
.
Udc/2
DT2x
T2x
.
T2x
DT2x
T2x
D2x
D2x
DT1x
T1x
DT1x
T1x
DT1x
T1x
.
.
.
T’2x
T’2x
T’2x
.
.
D1x
.
D1x
Udc/2
Udc/2
Udc/2
D1x
T’1x
T’1x
T’1x
.
.
.
Positive state.
Zero state.
Negative state.
Figure 10. Different conduction paths of the Three level NPC.
It should be considerate that each of the switching devices must block only one-half
of the DC link voltage assuming sinusoidal currents. The maximum semiconductors current is
the maximum phase current. These parameters ratings are considerate when choosing the
components for the converter [26].
state
T1x
DT1X
T2X
DT2X
T'1x
D'T1X
T'2X
D'T2X
D1X
D2X
Positive phase current
"+"
X
"0"
X
X
X
"-"
X
X
Negative Phase current
"+"
X
X
"0"
X
"-"
X
X
X
Table 3. Conduction losses in a three level NPC.
2.2.2 n level topologies for NPC.
As the number of levels for the converter increases the compiled output waveform
adds more and more steps producing a staircase waveform which approaches the sinusoidal
PED2 - 841
Page 13
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
wave with less harmonic distortion. Theoretically a zero harmonic distortion at the output
wave signal can be obtained by using an infinite number of levels for the converter [27].
The basic principle for the multilevel Neutral Point Clamped converter topology can
be summarized as follows. An m-level NPC converter consists of m-1 DC link capacitors and is
able to produce m number of levels for the phase voltage [27], [28].
Three different multilevel NPC converters are presented in Figure 9, Figure 11 and
Figure 12 to show the basic difference between the circuits.
.
.
.
.
.
.
C1
.
.
.
C2
.
.
.
.
.
.
C3
.
.
.
a
b
c
Figure 11. Four level NPC converter.
Figure 12 shows the basic circuit of a five level diode clamped multilevel converter.
The total DC link voltage is divided into four voltage levels by connecting the four DC bus
capacitors in series. The voltage rating over each capacitor is
. The midpoint node of the
DC link is considerate as the neutral point and the possible converter AC output voltage levels
are
,
, 0,
and
[27], [28].
The three middle nodes of the DC link are connected to the phase legs by means of
clamping diodes to limit the collector-emitter voltages of the switching devices to the voltage
level across only one of the DC link capacitors. The converter consists of 24 switching devices
and each of the phase legs includes 8 switches. The switches in one phase leg are commutated
in such way that at any given time four consecutive switches are conducting. It should be
noted that the clamping diodes must block different voltage levels than the switching devices
in the converter. The voltage levels for the clamping diodes can go as high as
of the
total voltage. This requires diodes with different voltage ratings to be used or to implement
series connected clamping diodes in the circuit which will increase the complexity of the
system [27], [28].
PED2 - 841
Page 14
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Assuming that each blocking diode voltage rating is the same as the switching device
voltage rating the number of diodes needed for each phase will be (m-1)x(m-2). When the
level of the converter is subsequently high the number of diodes required for the topology will
make the converter impractical to be implemented [27], [28].
a
c
b
Sa1
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Sa2
.
Sa3
.
Sa4
.
0
S’a1
.
S’a2
.
S’a3
.
S’a4
.
Figure 12. Five level NPC converter.
The staircase voltage in the five level NPC converter is obtained using 5 different
switch combinations to synthesize the five voltage levels [27]
-
For
-
For voltage level
-
For
-
For voltage level
Sa4 is turned on and S’a1, S’a2 are turned on
-
For voltage level
all lower switches S’a1 through S’a4 are turned on
PED2 - 841
all upper switches Sa1 through Sa4 are turned on
switches Sa2 through Sa4 and S’a1 are turned on
Sa3 and Sa4 are turned on, also S’a1 and S’a2 are also turned on
Page 15
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
V5
V4
V3
V2
Vdc/2
V1
-V2
-Vdc/2
-V3
-V4
-V5
Figure 13. Phase and line voltage waveforms of a 5-level NPC converter.
Table 4 shows the voltage levels and the corresponding switch states. It should be
noted that each switch is switched only once per cycle. There are four complimentary switch
pairs in each phase leg. The complimentary switches are defined such as that when turning
one of the switches on automatically excludes the other one from being turned on. In phase
“a” the complimentary switches are Sa1-S’a1, Sa2-S’a2, Sa3-S’a3 and Sa4-S’a4 [27].
Output Vao
Switch state
Sa1
Sa2
Sa3
Sa4
S'a1
S'a2
S'a3
S'a4
V5=VDC/2
on
on
on
on
off
off
off
off
V4=3VDC/8
off
on
on
on
on
off
off
off
V3=VDC/4
off
off
on
on
on
on
off
off
V2=VDC/8
off
off
off
on
on
on
on
off
V1=0
off
off
off
off
on
on
on
on
Table 4. Voltage levels and their corresponding switch states in five level NPC.
PED2 - 841
Page 16
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
2.3. PMSG parameters estimation.
In order to carry out the modelling and simulation of the system the parameters of
the machine are needed. Given that the real machine that will be used in the application is not
designed yet, the parameters are determined here. In order to determine the model
parameters of the permanent magnet generator the power flow diagram of an ac generator
shown in Figure 14 is used [29].
Figure 14. Power flow of an ac generator[29].
Along with the diagram shown above, the following per phase equivalent circuit of
the inverter – PMSG system is also necessary for the determination of the machine
parameters. The parameters are determined considering that the machine is in steady state
working as a generator and a FOC is performed during its operation.
Figure 15. Per phase equivalent circuit of an ac machine.
PED2 - 841
Page 17
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The parameters of the PMSM used for our simulations are determined below. For it,
the following assumptions are taken into account:
-Line to line rms voltage is:
Eq. 2
The phase rms voltage of the machine is:
√
Eq. 3
√
The peak phase voltage of the machine will be then:
√
Eq. 4
The PMSG will be controlled using a FOC technique, which means that the back e.m.f. and the
phase current are in phase all the time.
( )
Eq. 5
The efficiency of the machine is considered to be 95%.
Eq. 6
The nominal rotational speed of the shaft is 5.68 r.p.m.
Eq. 7
Which expressed in rad/s is equal to:
Eq. 8
The number of pair poles of the machine is considered to be:
PED2 - 841
Page 18
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 9
The nominal electrical frequency will be then:
Eq. 10
Eq. 11
Eq. 12
The active power at the terminals of the generator must be 5MW.
Eq. 13
Eq. 14
Taking into account the efficiency of the machine, the power at the input will be:
Eq. 15
The torque in nominal conditions will be then:
( )
(
)
Eq. 16
As the performance of the machine is 95%, 5% of the input power of the generator are losses.
The stray losses, mechanical losses and core losses are considered to introduce 4.9% of the
total losses. The remaining 0.1% will be considered as copper losses. Hence, it will be
considered that only 95.1% of the input power is converted into electrical power.
Eq. 17
PED2 - 841
Page 19
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
This is the same as considering that only 0.951 of the applied torque, Tapp will be
converted into electrical power:
Eq. 18
Eq. 19
Eq. 20
As the current will be in phase with the back e.m.f:
Eq. 21
Eq. 22
The cosine of theta is estimated as:
Eq. 23
The angle theta is then:
Eq. 24
The peak value of the current is calculated then:
Eq. 25
Eq. 26
PED2 - 841
Page 20
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 27
√
√
Eq. 28
Given that the phase current and the back e.m.f. are in phase all the time:
Eq. 29
The peak value of the back e.m.f. is calculated then:
Eq. 30
As FOC technique will be used, in the synchronous dq reference frame the torque is given by
the following expression:
Eq. 31
Taking into account that when using the FOC technique id = 0 and iq = iphpk, the peak values of
the permanent magnet flux linkage is:
( )
( )
Eq. 32
Eq. 33
At the terminals of the generator it is known that the active power is 5e6 W and this is equal
to:
Eq. 34
The reactive power at the output will be:
PED2 - 841
Page 21
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 35
Eq. 36
Eq. 37
The output apparent power will be:
√
√
Eq. 38
Eq. 39
The copper losses are the power dissipated into the phase resistors:
Eq. 40
The phase copper loss is also equal to:
Eq. 41
Eq. 42
The phase winding resistance is then:
Eq. 43
As can be observed the apparent power at the terminals of the generator, Sout, is greater than
the converted apparent power, Sconv. This is due to the phase inductance, which consume
reactive power. As the back emf is in phase with the phase current, the reactive power needed
is provided by the inverter. The phase reactive power is then:
PED2 - 841
Page 22
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 44
Eq. 45
Because of the signs convention adopted this reactive power will have a negative
sign at the inverter generator, indicating that it is actually provided by the inverter
and not consumed.
The value of the phase synchronous reactance is then:
Eq. 46
Given that the electrical frequency is 12.5 Hz, the values of the phase synchronous
inductance can be calculated as following:
Eq. 47
The calculated value of the inductance is equal to the leakage inductance plus the
magnetization inductance, and as the machine is considered to be a surface
mounted PM machine:
Eq. 48
The calculations carried above are resumed in the following table where the main
parameters are presented:
Nominal Output Power
Nominal Line-to-line voltage
Nominal Current
Nominal Torque
Nominal Speed
Stator Winding Resistance
Synchronous inductance
Permanent magnet peak flux linkage
Moment of inertia
Number of pole pairs
Table 5. Machine parameters.
PED2 - 841
Page 23
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
Page 24
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 3
System description and modelling
The system discussed in the project is composed by a wind turbine, a permanent
magnet synchronous generator, a back to back three level NPC converter and the grid. A
mathematical model of each element of the system was built and control strategies were
implemented. A graph showing the different parts of the system and how they are
interconnected is shown in Figure 16.
Figure 16. Block diagram of the system.
The grid, the converter, the permanent magnet synchronous generator and the
turbine are described in this chapter.
3.1 Grid Model
The grid presented in Figure 17 can be modelled in abc reference frame using the
following equation:
Eq. 49
where:
k - represents phase a, b and c,
ek - represents the grid voltage,
Rgrid - represents the grid resistance,
Lgrid - represents the grid inductance,
PED2 - 841
Page 25
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
ik - represents the phase current and
vkn - represents the phase voltage which will be applied at the rectifier terminals.
ea
~
~
~
eb
n
ec
Rgrid
Lgrid
Rgrid
Rgrid
ia
van
Lgrid
ib
vbn
Lgrid
ic
vcn
Figure 17. Grid model (abc reference frame).
For an ease of implementation in the Simulink model the equations will be transferred
in dq reference frame. After the transformation the equations will be:
Eq. 50
Eq. 51
where:
are cross-coupling terms introduced by the dq transformation.
From Eq. 50 and Eq. 51 the equations for the rectifier input current can be obtained.
∫
Eq. 52
∫
Eq. 53
Equations Eq. 52 and Eq. 53 are implemented in Simulink to model the behavior of
the grid.
PED2 - 841
Page 26
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
3.2 Level NPC Convertor Model
To construct the mathematical model for the 3 level back to back neutral point
clamped convertor a transfer from the physical to an ideal system has to be made. Starting
from the model presented in Figure 8 the ideal model is produced as in [18] and displayed in
Figure 18. The ideal switches have three positions as explained earlier.
idcr1
idci1
ic1
N
PMSG
A
ii1 vi1
B
ii2
C
ii3
vi2
idci2
ic2
vi3
idci3
+vc1
-
vr1
vr2
idcr2
ir1
A
ir2
B
ir3
C
o
+vc2
-idcr3
vr3
GRID
R
Figure 18. Back to back equivalent circuit based on ideal switches.
From the current directions it can be seen that the machine part of the convertor
acts as an inverter, all these values have the letter i as an index and the grid side of the
convertor acts as a rectifier, the letter r is presented as the index for these values. The inverter
side of the converter can be modelled using the following equations:
Eq. 54
where:
– phase to neutral voltage (k= A, B, C)
– switch voltage (j= 1, 2, 3)
– the voltage from the DC link point to neutral
Taking into consideration that the sum of the phase currents (
to be zero, by adding all three equations the voltage
becomes:
(
Direct substitution of
PED2 - 841
)
) is supposed
Eq. 55
in Eq. 54 yields the equation written in matrix form:
Page 27
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
[
]
[
][
]
Eq. 56
The similar result is obtained for the rectifier part of the converter as it can be seen in
the following equation:
[
]
[
][
]
Eq. 57
Because in a 3level NPC convertor the most important task is to ensure a constant DC
voltage and the balance of the two capacitors voltages two new variables are defined [18] :
Eq. 58
where:
– represents the DC voltage divided by two (the maximum or minimum value of voltage at
the output of the converter);
– represents the difference of capacitors voltages divided by two (this value characterises
the balance between the capacitors voltages);
The next step is to define the voltages in the switches as a function of the duty
cycle,
and . This is done using a quadratic function with a characteristic as the one
presented in the following figure:
Vc2 = Vc1
Vi
Vc2
-1
δi
1
Vc2 > Vc1
- Vc1
Vc2 < Vc1
Figure 19. Description of voltage quadratic function
Analytically, the function presented in Figure 19 can be expressed using the following
equations:
(
PED2 - 841
)
Eq. 59
Page 28
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
(
)
In order to obtain the capacitors voltage equations Kirchhoff’s current law is applied to
the circuit, as in [ref1], and the result is:
Eq. 60
Eq. 61
where:
– the capacitance of each DC link capacitor;
– the current in the inverter/rectifier part of the DC link (j=1, 2, 3);
The
and
currents are obtained from the phase currents and duty cycle, using a
quadratic function, as in [ref].
idc1k
idc2k
ik
ik
-1
-1
0
0
δk
1
1
Figure 20. Description of current function
δk
Figure 21. Description of current function
idc3k
ik
-1
0
1
δk
Figure 22. Description of current function
PED2 - 841
Page 29
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The currents have the same expressions for the inverter and rectifier part of the
convertor and are obtained from the quadratic function presented earlier, as in []:
(
)
(
(
(
)
)
)
(
(
)
(
)
(
)
)
(
Eq. 62
)
By substituting the currents from Eq. 62 in Eq. 61 we obtain the expressions for the
capacitors voltages:
(
)
(
)
Eq. 63
(
)
(
)
3.3 Dynamic Model of a Synchronous Permanent Magnet Machine
The voltage and flux linkage equations that describe the electrical behavior of the
surface permanent magnet synchronous machine in the abc system are presented below[30].
The complexity and difficulty of these equations is obvious because of the large number of
variables which are time and position dependent[30]. A simpler model of the machine is
obtained when using a synchronous reference frame.
()
()
()
()
()
()
()
()
()
()
()
()
()
Eq. 64
()
Eq. 65
()
Eq. 66
()
()
()
Eq. 67
()
()
()
Eq. 68
()
()
Eq. 69
()
3.3.1. dq model of the PMSM
A permanent magnet synchronous machine which has npp pair of poles and rotates at
a mechanical speed ωmec can be regarded as a one pair pole machine rotating at electrical
speed ωel due to magnetic symmetry. In order to obtain the model of the machine in the
PED2 - 841
Page 30
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
synchronous reference frame dq, the Park Transformation must be applied. Two of the main
advantages of applying the transformation is that the number of equations is reduced and the
values of the different inductances of the machine are not position dependent any more
simplifying the control of the machine[30], [31].
The dq reference axes are placed on the rotor of the machine and will rotate the with
the same angular speed ωel. The consequence of this is that the three phase stationary
windings are transformed in two rotating windings and hence in steady state all machine
parameters will be constants.
The d axis has to be placed along the magnetic axis of the rotor and the q axis
perpendicular to it. Both axes form π/2 electrical radians, which correspond to (π/2)/npp
mechanical degrees [31]. This is shown in Figure 23. As the type of motor considered for the
project is a surface mounted permanent magnet, the Ld and Lq are equal [32].
a. mechanically defined dq axes.
b. electrically defined dq axes.
Figure 23. dq axes definition.
The voltage equations in the dq synchronous reference frame are:
()
()
()
()
Eq. 70
()
()
()
()
Eq. 71
Where:
p: is the derivative operator d/dt
The flux linkage equations in the dq synchronous reference frame are:
()
()
(
(
)
)
()
()
()
()
()
Eq. 72
Eq. 73
Torque equation:
PED2 - 841
Page 31
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
()
()
Eq. 74
Mechanical equations:
()
()
()
()
()
Eq. 75
Eq. 76
3.4 Wind Turbine.
The model of the wind turbine implemented in the simulation will be a simplified
one, constructed base on the Wind Turbine Block presented in Matlab Simulink [33].
The input variables for the model are the ones provided by the DeepWind Project so
the maximum wind speed is considered to be 15 m/sec.
The behaviour of the wind turbine model is presented in the following figure:
Figure 24. Wind turbine characteristic [33].
In order to simplify the model the values from this characteristic are used to create
two functions. The first function is created in order to obtain the maximum power from the
wind turbine as a function of the wind speed and the second function gives the optimal
rotational speed of the turbine as a function of the wind speed. Through this approach the
PED2 - 841
Page 32
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
wind turbine will provide for each wind speed the optimum rotational speed for the turbine in
order to obtain the maximum power.
The values taken from the wind turbine characteristic were analysed using the Matlab
functions polyval and polifit in order to obtain the coefficient for the function. The result of
this analysis provides the two functions for the wind turbine model:
( )
( )
Eq. 77
Eq. 78
The characteristic of the two functions are displayed in the following figure along with
the torque characteristics.
Figure 25. Functions results.
It can be observed that the rotational speed of the generator has a linear dependency
of the wind speed, while the power and the load increase more slowly in the first part.
The torque function is determined from the other two functions, dividing power by the
speed. The output values are given in per-unit so a multiplication with the nominal values is
required.
PED2 - 841
Page 33
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
Page 34
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 4
System Control
In the present chapter two control strategies are presented. One strategy is applied
to the PMSG and it consists of a FOC technique. The second strategy is commonly named as
current mode control and it is used in order to control the active and reactive power sent to
the grid.
4.1. Rectifier control
The rectifier control method used in this report is based on voltage oriented control,
as presented in [34]. The block diagram of the rectifier control is presented in Figure 26.
eq
vdc
vdc*
-
Vdc
controller
+
iq*
+
-
vq*
iq
controller
ed
+
+
+
vqn*
dq
ωL
vαβ*
αβ
VNorm
VNorm -> IQ/IN
IQ/IN
id*
x
+
-
vd*
id
controller
+
+
-
Space
vector
modulator
SW
Three level
rectifier
vdn*
In
rms
3
ωL
id
dq
iq
iabc
abc
θ
ed
eq
dq
Lgrid
PLL
eabc
Rgrid
abc
~
eabc
Figure 26. Block diagram of rectifier control system with dq current control.
The principle behind this control method is to control the dq current ( ) using the
phase voltage (
), the grid voltage (
), and the DC voltage ( ). The control can be
separated in two levels. The interior level is represented by the current controllers and the
external level is represented by the DC voltage controller and the reactive power controller
PED2 - 841
Page 35
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
[35]. A PI controller structure will be used in each case, with the structure as presented in
Figure 27:
In
++
kp
ki
Out
1/s
Figure 27. Structure of PI controller.
In the following of this subchapter the control strategy along with method to
determine the parameters for the PI controllers will be presented step by step for each
controller.
4.1.1. Current controllers
In order to design the current controllers for the rectifier the equations of the grid
model are necessary.
Eq. 79
Eq. 80
Starting from the grid equations the reference values for the rectifier can be
determined. These values are represented by the phase voltages (
). To obtain these
voltages the equations will become:
Eq. 81
Eq. 82
A problem appears at this stage because the two axes are coupled by the
terms. This problem will be solved by introducing the feed-forward terms in the PI controllers,
procedure which is similar as for the machine control. Besides the coupling terms the feedforward terms will also contain the voltage from the grid, as it can be seen in the following
equations:
PED2 - 841
Page 36
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 83
Eq. 84
Once the feed-forward components are determined the structure of the PI controllers
can be presented:
(
)(
)
Eq. 85
(
)(
)
Eq. 86
With the structure of the PI established the transfer function of the current can be
determined by joining Eq. 81 with Eq. 85 and Eq. 82 with Eq. 86, as it can be seen in the
following.
(
)(
)
Eq. 87
(
)(
)
Eq. 88
The feed-forward components are going to be eliminated from both sides of the equal
and the equations in Laplace domain will become:
(
)(
)
Eq. 89
(
)(
)
Eq. 90
Once having these equations the axis can be combined in vectorial form again
considering:
Eq. 91
Eq. 92
In this case the main equation will become:
(
)
(
)
(
)
Eq. 93
Both sides of the equal will be multiply with s to eliminate the s in the denominator
and the
component will be transferred to the other side of the equal. By doing this the
equation will be:
PED2 - 841
Page 37
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
(
)
[
(
)
]
Eq. 94
The transfer function of the current is:
( )
(
Eq. 95
)
Once the transfer function of the current was determined the next step is to tune the
current controllers. This procedure is done by allocating the poles of the transfer function. The
poles are the roots of the characteristic equation.
(
)
Eq. 96
In the following the poles will be represented by
conditions:
(
)
and
and they have to fulfil the
Eq. 97
Eq. 98
In order to have a stable behaviour of the system the poles must be selected from the
left half plane, which means that the real part has to be negative. In this case the PI
coefficients will become:
(
)
(
Eq. 99
)
Eq. 100
Like in the control of the machine case the current loop has to be faster than the speed
loop, by an approximation, the current loop has to be at least ten times faster than the speed
loop.
The time constants of the regulator are:
Eq. 101
Eq. 102
Based on the parameters of the system the user has to select the time constants of the
PI controller.
The first time constant of the PI controller is selected to be equal to the time constant
of the electrical circuit.
PED2 - 841
Page 38
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Because the first time constant of the PI controller is equal to the time constant of the
electrical circuit the two poles are going to get simplified and the second order equation will
become a first order equation. Because of the simplification the second time constant will
control the behaviour of the system. This has to be selected faster than the previous one for
the system to have an adequate response.
In order to obtain the best tuning parameters three time variables are tested with the
step function to determine the behaviour of the system. As it can be seen in Figure 28 the first
time variable represented by the blue line has a response which is too slow for the control that
we want to implement. The red line, which represents the system with the fastest response,
presents an aggressive behaviour which can affect the stability of the system. The variable
presented in the middle of the range is selected to be used for the model because it provides a
fast enough response which doesn’t affect the stability of the system.
Figure 28. The step response for different time variables.
In the model used in this report the time constant is selected to be one hundred times
smaller than the time constant of the electrical circuit.
With these two values for the time constant the coefficients of the PI controller can be
determined.
Once the coefficients are determined the transfer function of the current is obtained:
PED2 - 841
Page 39
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
( )
To test the behaviour of the transfer function a step is applied at the input. The result
is displayed in Figure 28. As it can be seen the system response is according to the second time
constant selected and no steady state error appears.
In order to test the stability of the system a root locus will be constructed. The result is
displayed in Figure 29. From the result it can be seen that the system is stable for every value
of the gain because the characteristic remains in the left half plane.
The transfer function has to be tested also for frequency response. For this purpose
the Bode diagram is constructed and displayed in Figure 30. From the results it can be seen
that the gain margin is infinite and the phase margin is equal to -180°. These results provide
the information that the current transfer function is stable and it does not have steady state
errors.
Figure 29. Root locus of the current transfer function.
PED2 - 841
Page 40
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 30. Bode diagram of the current transfer function.
4.1.2. DC voltage controller
In order to create the controller for the DC voltage
the equation which models the system is required [34], [36].
In this case the DC voltage is modelled as a pure
capacitor which stores energy according to the formula:
Pin
Pout
Figure 31. Energy transfer.
Eq. 103
The time derivative of this stored energy has to be equal to the sum of input power
and output power, with the power direction according to Figure 31 [34], [36].
Eq. 104
A problem appears when using this equation to simulate the model because, as it can
be seen in Eq. 104 the equation is not linear with respect to
.
In order to solve this problem the system has to be linearized. This is done by
replacing
with a new variable, , and Eq. 104 becomes linear with respect to :
PED2 - 841
Page 41
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 105
To create the controller for this system the input and output power has to be defined
for our system.
The input power is considered to be the power that comes from the grid to the DC
link and the output power is considered to be the power that goes from the DC link to the
motor.
The equation for the input active and reactive power to the converter is:
(
)
Eq. 106
(
)
Eq. 107
The control strategy applied for the rectifier maintains the current equal to zero
and because
grid voltage is equal to zero from the Park transformation the unity power
factor is achieved in the grid side. This means that the input power is equal with:
Eq. 108
Because the output of the DC voltage PI controller is the current
replaced in Eq. 105 and the current will be obtained:
Eq. 108 will be
Eq. 109
Once this form is obtained for the current the equation for the PI controller which
provides the reference current is introduced:
)(
(
)
Eq. 110
In order to obtain the transfer function Eq. 110 is transformed into Laplace domain
and the
is considered to be equal to zero.
(
)
(
)
Eq. 111
From Eq. 111 we can determine the transfer function:
( )
Eq. 112
The tuning of the DC voltage controller is made in the same way as for the current
controller, by determining the positions of the poles in the left half plane of the system.
and
The poles of the system, which represent the roots of the characteristic equation
must fulfil the following equations:
PED2 - 841
Page 42
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 113
Eq. 114
As in the case of the machine control the current control loop has to be faster than the
DC voltage control loop because the dynamic of the current is faster than the dynamic of the
DC voltage. The same difference between the poles is applied here as for the machine
controller.
The tuning condition that ensures that the current loop is faster than the DC voltage
loops is:
With the poles determined the PI controller coefficients and the transfer function can
be calculated:
( )
To determine the behaviour of the system a step input is applied. The result is
displayed in Figure 32 and it can be seen that no steady state errors are introduced.
Figure 32. The response of the DC voltage transfer function when a step is applied.
PED2 - 841
Page 43
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The stability of the system is tested by constructing the root locus. The result displayed
in Figure 33 provides the information that the system stability is independent of the gain. The
system is stable for every value of the gain applied because the characteristic is present only in
the left half plane.
The last test applied to the transfer function is the frequency response test. For this
the Bode diagram is constructed and displayed in Figure 34. From the results it can be seen
that the gain margin is infinite and the phase margin is equal to 171.99° for ω=30.3 rad/sec.
Figure 33. Root locus of the DC voltage transfer function.
PED2 - 841
Page 44
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 34. Bode diagram of the DC voltage transfer function.
After the tests the results show that the system is stable, does not introduce steady
state errors and the time response is in accordance with the one selected initially.
4.1.3. Reactive power controller
Using Eq. 106 and Eq. 107 the active and reactive power from or to the grid can be
determined. As it was explained earlier the control strategy in normal working conditions
maintains the current equal to zero to ensure that the rectifier provides unity power factor.
Because in the project presented in this report there are situations when reactive power is
needed, for example in a voltage drop situation, the controller has to be able to control the
amount of reactive power produced.
In order to implement the control on the real turbine it must respect a series of
requirements presented in the grid codes [37]. The reactive power control becomes a priority
when an abnormal event appears in the system. One of the biggest problems encountered in
such a system is represented by the voltage drop [37]. The grid codes have very specific
requirements for the tolerance in this kind of situation as presented in Figure 35 [37]. These
requirements must be complied for symmetrical as well as for asymmetrical faults, for one,
two or three phases.
It can be seen in Figure 35 that the grid codes require that the turbine must withstand
voltage drops down to 20% of the voltage in the point of connection over a period of minimum
0.5 seconds without disconnecting.
PED2 - 841
Page 45
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The voltage drop can be separated in three areas where the behaviour has to be
different:
-
Area A: the wind power plant has to stay connected to the grid and uphold normal
protection;
-
Area B: the wind power plant has to stay connected to the grid. The wind power
plant must provide voltage support by supplying reactive power. The amount of
reactive power that the wind power plant has to supply is depicted in Figure 36;
-
Area C: the wind power plant can be disconnected;
Figure 35. Requirements for tolerance of voltage drops for wind power plants with an output
power greater than 1.5MW [37].
PED2 - 841
Page 46
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 36. Requirements for reactive power supply, , during voltage drops for wind power
plants with a power output greater than 1.5MW [37].
The control must behave as the characteristic in Figure 36 because the reactive
power has to follow the control characteristic with a tolerance of ±20% after 100 ms. In Area B
the supply of reactive power has first priority, while the supply of active power has second
priority.
Another requirement is for the active power to be maintained constant during the
voltage drop, but a reduction in active power is acceptable [37].
The control method, as presented in the bloc diagram in Figure 26 is an open loop
control, where the normalized rms voltage of the grid is the input variable. From the input
variable, using the diagram in Figure 36 the report ⁄ is determined which is multiply by the
nominal current in order to obtain the reference for the reactive current.
In the simulation the diagram is implemented using the Matlab Function block which
separates the entire voltage spectre in three regions:
-
If
-
If
-
If
PED2 - 841
,
then
,
,
;
then
then
;
;
Page 47
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
From these three regions it can be seen that if the grid voltage is maintained above
90% of its nominal value the control will be affiliated with Area A and no reactive power will be
transmitted into the grid. If the grid voltage drops within a [50, 90] per cent region a reference
for the reactive power will be introduced into the system according to the equation presented
earlier. In the third region, when the grid voltage drops below 50% the reference for the
reactive current will become equal with one.
4.2. Machine Control
The machine control method used in this report is based on flux oriented control, as
presented in [34]. Based on the advantages that the dq transformation offers for the induction
machine and synchronous machine, like the possibility to control the torque by simply
controlling the current, similar to the DC machine, field oriented control has the purpose to
control the current in such a way that maximum torque is obtained at any moment for
minimum current [31]. The block diagram of the machine control is presented in Figure 26
[30].
Udff
id*
+
id
controller
-
+
+
dq
Uqff
vabc*
abc
ωr*
+
-
Te*
speed
controller
kt
iq*
+
iq
controller
-
+
Three level
inverter
+
θ
3
id
dq
iq
iabc
abc
θ
1/s
ωe
PMSG
Figure 37. Block diagram of a flux oriented control system
The principle behind this method is to control the speed using the torque and the dq
currents ( ). The control can be separated in two levels. The interior level is represented by
the current controllers and the external level is represented by the speed controller. For each
controller the PI structure will be used, with the structure as presented in Figure 27:
In
++
kp
ki
Out
1/s
Figure 38. Structure of PI controller.
PED2 - 841
Page 48
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
In the following of this subchapter the control strategy along with method to
determine the parameters for the PI controllers will be presented step by step for each
controller.
4.2.1. Current Controllers
In order to design the current controllers the equations of the machine model are
necessary. Eq. 50 and Eq. 51 represent the machine model in dq reference frame.
Eq. 115
(
)
Eq. 116
Starting from the machine equations the reference values for the converter can be
determined. These values are represented by the voltages (
).
A problem appears at this stage because of the dq transform, the two axes are coupled
by the
terms. This problem will be solved by introducing the feed-forward terms in
the PI controllers, as it can be seen in the following equations:
Eq. 117
(
)
Eq. 118
Once the feed-forward components are determined the structure of the PI controllers
can be presented:
(
)(
)
Eq. 119
(
)(
)
Eq. 120
With the structure of the PI established the transfer function of the current can be
determined by joining Eq. 50 with Eq. 85 and Eq. 51 Eq. 82 with Eq. 86, as it can be seen in
the following.
(
)(
)
Eq. 121
(
)(
)
Eq. 122
The feed-forward components are going to be eliminated from both sides of the equal
and the equations in Laplace domain will become:
PED2 - 841
Page 49
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
(
)(
)
(
)
Eq. 123
(
)(
)
(
)
Eq. 124
Once having these equations the axis can be combined in vectorial form considering:
Eq. 125
Eq. 126
Eq. 127
)
Eq. 128
In this case the main equation will become:
(
)
(
)
(
Both sides of the equal will be multiply with s in order to eliminate the s in the
denominator and the
component will be transferred to the other side of the equal. By
doing this the equation will be:
(
)
[
(
)
]
Eq. 129
The transfer function of the current is:
( )
(
Eq. 130
)
Once the transfer function of the current was determined the next step is to tune the
current controllers. This procedure is done by allocating the poles of the transfer function. The
poles are the roots of the characteristic equation.
(
)
Eq. 131
In the following the poles will be represented by
conditions:
(
)
and
and they have to fulfil the
Eq. 132
Eq. 133
In order to have a stable behaviour of the system the poles must be selected from the
left half plane, which means that the real part has to be negative. In this case the PI
coefficients will become:
PED2 - 841
Page 50
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
(
)
(
Eq. 134
)
Eq. 135
Like in the control of the machine case the current loop has to be faster than the speed
loop, by an approximation, the current loop has to be at least ten times faster than the speed
loop.
The time constants of the regulator are:
Eq. 136
Eq. 137
Based on the parameters of the system the user has to select the time constants of the
PI controller. Starting from this point the poles and the coefficients of the PI controller are
determined.
The first time constant is selected to be equal with the time constant of the electrical
circuit in order to simplify the transfer function from a second order equation to a first order
equation. Then will become:
The second time constant of the PI controller has to be selected smaller than the
electrical time constant in order to obtain a good control of the system. The second time
constant is selected to be two hundred times smaller than the time constant.
With the two time constants selected the coefficients of the PI controller can be
calculated.
The transfer function of the system becomes:
( )
In order to observe the behaviour of the system a step input is applied. The result can
be observed in Figure 39. It can be observed that the system reaches steady state in
approximately 0.1 seconds, which means that the time constant of the system is the second
time constant selected earlier.
PED2 - 841
Page 51
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 39. The response of the current transfer function when a step is applied.
The stability of the transfer function is tested by constructing the root locus. The result
is presented in Figure 40. As it can be seen the system remains in the left half plane for every
value of the gain, which means that the system is stable.
Figure 40. Root locus of the current transfer function.
The third and the last test of the transfer function is made using the Bode diagram
which determines the frequency response of the system. As it can be seen from Figure 41 the
PED2 - 841
Page 52
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
gain margin is infinite and the phase margin is -180°. The system frequency response proves
that the system is stable.
Figure 41. Bode diagram of the current transfer function.
4.2.2. Speed Controller
Like in the current controller case the equation of the machine are required to
develop the control. In this case the mechanical equation is used, in which the speed varies
based on the torque. The mechanical equation is presented in Eq. 138.
Eq. 138
,where: – moment of inertia [kg*m]
– number of pole pairs
– rotor electrical speed [rad/sec]
– electric torque [Nm]
– load torque [Nm]
The speed controller applied in field oriented control has to provide the reference
current to the current controller. Because the output of the speed controller is the torque, it
has to be transformed to current by a gain
. The gain is determined from the torque
equation of the machine obtained after dq transformation.
PED2 - 841
Page 53
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
[
(
) ]
Eq. 139
Because in our case the machine is a PM synchronous machine with equal inductances
on the d and q axes, Eq. 139 can be simplify to the following form:
Eq. 140
Eq. 140 is used to obtain the
coefficient, which makes the translation from torque,
which will be the output of the speed controller to the current which will be the reference
for the current controller. The coefficient is:
Eq. 141
Once the transfer function from torque to current is determined the PI speed
controller can be designed. The design of the controller starts from Eq. 138 which is
rearranged to obtain the electrical torque from the speed. Besides this, the equation is
transferred in Laplace domain and the load torque is considered to be equal to zero (
).
After these changes the equation will become:
Eq. 142
The equation of the PI speed controller is:
)(
(
)
Eq. 143
If the equation is multiplied on both sides with s to eliminate the s in the denominator
and if the speed component is transferred to the other side of the equal the equation will
become:
(
)
[
]
Eq. 144
From Eq. 144 the transfer function will become:
( )
Eq. 145
Once the transfer function of the speed controller was determined the next step is to
select the poles of the transfer function. The characteristic equation is:
Eq. 146
The roots of the transfer function, which in this case represent the poles of the
characteristic equation, must respect the following conditions:
PED2 - 841
Page 54
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 147
Eq. 148
In order for the system to be stable the poles must be selected from the left half side,
which means that the real part of the poles has to be negative. From Eq. 147 and Eq. 148 the
coefficients of the PI controller can be determined:
(
(
)
)
Eq. 149
Eq. 150
Because the time constant of the mechanical system is slower from the time constant
of the electrical system the poles for the speed transfer function must be selected considering
this problem. This is why both poles are selected starting from the current transfer function
and applying the difference coefficient. In the case presented in this report the difference
coefficient will be selected to be equal to fourteen, then the poles become equal to:
From these poles values the coefficients of the PI controller can be calculated.
With the PI coefficients determined the speed transfer function is obtained.
( )
As for the current transfer function a step is applied to the system in order to observe
the behaviour. The result is placed in Figure 32. It can be seen that the system enters steady
state in approximately 1.6 seconds, which is determined by the second pole.
A rood locus of the transfer function is created to observe the stability of the system.
The result can be observed in Figure 33. As it can be seen the system is stable for every value
of the gain, because the characteristic remains in the left half plane.
The frequency response of the transfer function is determined constructing the Bode
diagram. From the result displayed in Figure 34 it can be observed that the gain margin is
infinite and the phase margin is equal to 174.3° at ω = 0.2438 rad/sec.
PED2 - 841
Page 55
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 42. The response of the speed transfer function when a step is applied.
Figure 43. Root locus of the speed transfer function.
PED2 - 841
Page 56
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 44. Bode diagram of the speed transfer function.
These results provide the information that the system created with the selected time
constants is stable.
PED2 - 841
Page 57
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
Page 58
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 5
Simulation Results
In this chapter the results of the simulation will be presented for different working
conditions like: normal operation, starting the turbine, stopping the turbine and voltage dip
situation.
5.1. Normal operation
In the normal operation mode the generator is working at nominal values and it is
providing power to the grid. The speed of the wind is considered to be constant, which means
that the speed of the turbine is also constant and working at nominal value.
The shape of the current in both sides is presented in the following figure:
Figure 45. The current in both sides of the system.
The shape of the voltage in both sides is presented in the following figure:
PED2 - 841
Page 59
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 46. The voltage in both sides of the system.
Because the voltage and the current are constant the active power is constant and is
equal with the nominal value. As it can be seen in the following figure the reactive power in
the machine side of the converter is constant and positive because the inductors presented in
the machine consume reactive power which comes from the converter, opposite to the power
flow.
Figure 47. The active and reactive power at the machine terminals.
PED2 - 841
Page 60
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
It should be mentioned that the entire model was created to have the positive power
flow from the grid to the generator. This means that the model of the machine was built using
the motor equations, and if the active power is negative, as in Figure 45 it means that machine
works as a generator and power is transferred to the grid.
The direction of the power can also be observed in the grid side of the converter,
where the active power is negative. In this case the reactive power consumed by the inductors
which model the grid is also negative because this power comes from the converter and has
the same direction as the power flow.
Figure 48. The voltage in both sides of the system.
5.2. Stopping the turbine
The stopping procedure is applied when the wind speed decreases under a certain
value for which the wind turbine cannot function.
In this simulation the wind speed is reduced from nominal value to zero in a time
interval of 50 seconds. The normal time needed to stop the turbine has to be greater but
because of the long simulation time and the amount of virtual memory required the simulation
was made to last for only 52 seconds. The wind speed targets the rotation speed of the turbine
to reduce linearly to zero. This strategy is implemented in the wind turbine block in order to
obtain the maximum power at any given wind speed. The behaviour of the rotation speed can
be seen in Figure 49 along with the reference for the electrical speed. It can be observed that
the measured speed follows very close the reference speed, meaning that the control provides
a good result.
PED2 - 841
Page 61
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 49. Electrical speed of the turbine (
)
The waveform of the currents on both sides of the convertor has the shape as
presented in the following figure:
Figure 50. The current in both sides of the system.
PED2 - 841
Page 62
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The behaviour of the voltages on both sides of the converter can be observed in the
following figures:
Figure 51. The voltage in both sides of the system.
To better observe the behaviour of the system the active and reactive power is
displayed for both sides of the converter.
It can be observed that the power reduces from the nominal value to zero, but with an
increase in the initial step. This happens because the ramp which controls the speed of the
wind turbine has a slope which decreases too fast for this system. For a practical
implementation the slope has to be reduced in order to maintain the current inside specific
limits. This strategy could not be applied in this simulation because of the problems mentioned
at the beginning of this working condition.
The rest of the behaviour, positive reactive power, is the same as for the normal
working situation.
PED2 - 841
Page 63
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 52. The active and reactive power on the machine side.
Figure 53. The active and reactive power on the grid side.
The last important parameter for this simulation is the DC voltage. The behaviour of
this parameter can be observed in Figure 54. A large increase can be observed at the beginning
of the simulation, when the stopping procedure is enabled. This increase is quickly
PED2 - 841
Page 64
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
compensated by the control and the DC voltage reaches a value close to the nominal one. The
reference DC voltage is achieved when the system stops.
Figure 54. The DC voltage.
5.3. Starting the turbine
The procedure of starting the turbine from zero to nominal speed was simulated for
60 seconds. The reference value and actual value of the speed can be observed in Figure 55. A
ramp is applied at the input as a reference for the speed in order to limit the rise of the
current.
Figure 55. The machine speed.
PED2 - 841
Page 65
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
During the starting procedure the load torque provided by the wind turbine varies
from a positive initial value to the nominal negative value as a function of the speed. This
behaviour is caused by the Darreius wind turbine, which cannot be started only by the wind.
This type of turbine needs to be started by the machine until a certain value of the speed is
achieved. The load torque characteristic as a function of time is presented in in the following
figure:
Figure 56. The wind turbine torque.
The behaviour of the current in the machine and grid side is displayed:
Figure 57. The current on both sides of the convertor.
Only one phase of the current is displayed for a better visualization of the process. It
can be seen in the machine part that the current increases from zero to a certain value
PED2 - 841
Page 66
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
necessary to produce the electromagnetic torque which starts the turbine. The current
increases in frequency as the rotational speed increases. In the first region the current is
positive because the machine works as a motor, but changes sign once the load torque
becomes negative, the machine becomes a generator. The current reaches its nominal value
once the nominal speed is achieved, and the system enters steady state.
In the grid side of the converter it can be observed a different behaviour of the
current. It starts from zero and goes to a maximum value smaller than the nominal value which
is achieved at the middle of the starting period. The current also changes sign when the
turbine starts rotating only by the influence of the wind, and power is transmitted into the
grid.
The behaviour of the voltage in both sides of the converter is:
Figure 58. The voltage on both sides of the convertor.
It can be seen that the voltage on the machine side increases in magnitude and
frequency as the speed of the machine increases until the nominal value is reached. This is
done by the machine control.
On the grid side the voltage is almost constant on the entire period, but with a smaller
magnitude in the first part of the simulation when the machine works as a motor and power is
taken from the grid. When the machine enters generator mode the voltage at the convertor
terminals on the grid side increases to enable the power flow to the grid.
For a better visualization of the power flow direction the active and reactive power at
the machine terminals is displayed in Figure 65. It can be seen that the machine starts as a
motor in order to rotate the wind turbine to a specific value and the switch to generator mode
is made once the load torque changes sign. The machine provides nominal power to the grid
when the speed of the turbine reaches the nominal value.
PED2 - 841
Page 67
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 59. The active and reactive power at the machine terminals.
Figure 60. The active and reactive power at the grid terminals.
From the grid side active and reactive power it can be seen that the active power
taken from the grid in order to start the turbine is equal to the active power on the machine
side. The reactive power is negative on the entire time domain because the flow of reactive
power is negative compared to the flow of energy.
The DC voltage is affected by this transient process, as it can be seen in Figure 61 but
the control strategy is able to provide compensation in order to maintain the voltage at the
reference value.
PED2 - 841
Page 68
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 61. The DC voltage.
5.4. Voltage dip situation
In this situation the voltage of the grid is falling from the nominal value to 20% and
increases back to 90% of the nominal value, as in the requirement presented in the grid codes
[37]. In this situation the main priority is to supply reactive power to the grid in order to help
the grid recover from this abnormal situation.
Figure 62. The voltage dip characteristic.
PED2 - 841
Page 69
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Because the voltage drop has a time span of only 4 seconds and the time constant of
the mechanical circuit has a very big value the voltage dip is not observed on the machine side
of the converter. As it can be seen in the following figure the speed of the machine is not
affected by this fault.
Figure 63. The speed of the generator.
Also the current and the voltage are not affected by this fault on the machine type,
the influence can be observed only on the grid side.
Figure 64. The current on both sides of the convertor.
PED2 - 841
Page 70
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 65. The voltage on both sides of the convertor.
The stability of the machine side convertor can be observed also from the active and
reactive power characteristic.
Figure 66. The active and reactive power in the machine sides of the system.
Here it can be observed that the active and reactive power do not change during the
voltage drop in the grid. This is a requirement of the grid codes [37].
PED2 - 841
Page 71
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The main part of the control in this situation happens in the grid side of the convertor.
Here the influence of the fault can be observed better.
Figure 67. The active and reactive power at the grid side converter terminals.
It can be observed that the active power is maintained almost constant during the
entire period, the increase and decrease of the power taking place for very short periods. The
reactive power increases from zero to a certain value which is determined by the control using
the requirements presented in the grid codes.
Figure 68. The active and reactive power at the grid side converter terminals.
PED2 - 841
Page 72
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The complete behavior of the system can be better observed in the power which is
transferred directly to the grid. This power is presented in the following figure:
Figure 69. The active and reactive power transferred to the grid.
From these characteristics we can observe that if a voltage drop such severs appears in
the grid the convertor supplies only reactive power to the grid in order to help the grid.
Although this drastic phenomenon happens in the grid side converter the value of the
DC voltage is maintained between acceptable limits and after a period of time it is brought
back to the reference value, as it can be seen in Figure 70.
From these characteristics it can be seen that the system is able to handle a fault
presented in the grid according to the grid requirements.
PED2 - 841
Page 73
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Figure 70. The DC voltage.
5.5. Normal working condition with the converter model
The simulation was made as in the previous situation, when the system is in steady
state and the power flow is from the generator to the grid.
The shape of the current in dis situation is presented in the following figure:
Figure 71. The current wave form on both sides of the convertor.
PED2 - 841
Page 74
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
It can be seen that the wave forms are affected by perturbation once the model of
the convertor has been introduced. The same result can be seen in the voltage waveform.
Figure 72. The voltage wave form on both sides of the convertor.
The problem that appears once the convertor is connected is related with the
balancing of the voltages in the DC link. Because no balancing control strategy was applied to
this part of the convertor the wave forms and the behaviour of the system is drastically
affected. The difference of capacitor voltages in the DC link is displayed in the following figure:
Figure 73. The difference between the capacitors voltages.
PED2 - 841
Page 75
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
As it can be seen from the figure the voltage increases to dangerous values. In order
to test the entire model with the convertor attached the strategy to control the voltage
balance has to be implemented.
Once the convertor model is implemented the entire set of values which describes
the model can be visualized, as for example the DC currents in the grid side and the machine
side.
Figure 74. The DC currents in the machine side of the convertor.
Figure 75. The DC currents in the grid side of the convertor.
PED2 - 841
Page 76
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 6
Converter design
The objective of this chapter is to present the general idea how to design and
calculate multilevel Neutral Point Clamped Converter.
In the design process the determination of the number of levels for the topology is
one of the most crucial factors affecting the number of the devices in the circuit, their ratings
and even the control techniques to be used for the converter. The minimum number of levels
for the converter and the voltage ratings for the active devices are inversely related to each
other. Higher converter level topology will require more active devices for the circuit but the
voltage levels applied on the switches will be lower compared to a topology with fewer levels.
However it should be considerate that unlike the active devices additional levels do not enable
a decrease in the voltage rating for the clamping diodes [24], [38].
6.1. Define the system specifications
The first step is to define the system specifications for the converter, the utility grid
to which it is going to be connected and the generator in our case the wind turbine and some
additional information about the converter. The required parameters for the input and the
output of the design program are summarized and shown in Figure 76 [38]:
PED2 - 841
Page 77
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Input parameters
Level of suitable NPC
Input Power of
the converter
Ratings and number of IGBT’s
Input Voltage of
the converter
Commutation
period
Ratings and number of Diodes
Grid ferquency
Design Program
Design program
Capacitors number and ratings
Diode on time
Diode off time
Losses in IGBT’s and Diodes
Type of IGBT’s
Type of Diodes
Converter efficency
Output values
Figure 76. Input and output parameters of the design program.
-
Desired input and output voltage levels of the converter
-
The NPC converter nominal power
-
Converters efficiency
-
The desired commutation period for the switches in the converter
-
Grid frequency to which the converter will be connected
6.2. DC Bus Voltage calculation
The first parameter for the converter to be demined is the DC Bus voltage for the DC
link. The value of this voltage is closely related to the selection process of the semiconductor
devices, active switches and capacitors in the circuit and is one of the main basic parameters
for the converter [39].
The DC bus voltage is composed of two values that have to be defined the minimum
DC voltage in the DC link
and the max value for the DC voltage in the DC bus link
. Both of them are dependent on the AC output voltage level that we want to
generate. It should be mentioned that in our project the input voltage level will be the same as
the output AC voltage level of the converter and the NPC have the main function of control in
our system [39].
The minimum dc-bus voltage to achieve a line to line voltage of given magnitude
using the PWM strategy is
PED2 - 841
Page 78
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
√
Eq. 151
The maximum dc-bus voltage is fixed around a value of
Eq. 152
Where k is a coefficient between 1,5-2 it is chosen based on what kind of voltage
level are presented in our system.
There are 2 main reasons for limiting the maximum DC-bus voltage in the converter
[39]
-
In order to limit to limit the minimum value of the amplitude modulation index
-
In order to have an safety margin, with consideration to the nominal voltages of the
components that are used under possible oscillations in the system
6.3. Calculation of the switching devices and free-wheeling diodes
In this step the voltage rating and the current for the switches used in the circuit
(IGBT’s MOSFET etc.) and the free-wheeling diodes will be determined.
The voltage that these devices have to withstand as mentioned before is based on
the level of the Neutral Point Clamped converters topology used. The voltage rating that each
switch has to be able to withstand can be summarized in the following equation [39].
Eq. 153
Where “m” is the level of the NPC converter used.
For the free-wheeling diodes the same equations is valid and is going to be used.
Eq. 154
Hence it can be seen that in the multilevel NPC converter topology the voltage that
the switching devices have to be able to withstand is reduces starting by factor of 2 for the
three level NPC converter topology and keeps increasing so forth as the number of levels for
the converter increases [24], [39].
The current rating for the switches and the freewheeling diodes is given in the
following equation. It should be noted that the level for the Neutral Point Clamped converter
topology does not affect the current that this devices have to be able to withstand [39].
PED2 - 841
Page 79
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Eq. 155
√
Eq. 156
√
Where
is the line to line current of the converter so basically the devices should
be able to withstand the phase to phase current for the converter.
6.4. Calculation of the clamping diodes for the converter
Although each active switching device and the freewheeling diodes in an NPC
converter are required to block voltage level of
Eq. 157
The clamping diodes need to have different voltage rating for the reverse voltage
blocking capabilities than the other semiconducting devices [28].
For example using Figure 12 of a 5 level NPC, when all off the lower switching devices
S’a1 to S’a4 are switched on the clamping diode D’a1 is required to block three capacitor
voltage levels. The highest voltage level that each clamping diode in an “m” level NPC
converter will have to block can be summarized in the following equation [28].
(
)
Eq. 158
m- Level of the NPC topology used
If we assume that each clamping diode has a voltage rating of the same value as the
switches and the freewheeling diodes in the circuit the number of diodes required for each leg
is :
(
) (
)
Eq. 159
6.5. Calculation of the dc-bus capacitors
A critical part of the NPC converter is the design and calculation of the DC link
capacitors. The calculation of the DC bus capacitor is closely related to the different types of
PED2 - 841
Page 80
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
ripples that the converter should be able to withstand under all type of conditions. The
capacitance required for the DC link and the voltage ripple in the converter are inversely
related to each other. An increase in the capacitance will decrease the amount of ripple in the
DC voltage [39], [40].
It is assumed that the capacitance value of each of the capacitors in the DC link of
the Neutral Point Clamped Converter is equal.
=
Eq. 160
The ripple types and the corresponding analytical expressions can be summarized as
follows [39], [40] :
-
Ripple of High Frequency Due to Commutation
Eq. 161
– Maximum allowed ripple. The maximum allowed voltage ripple is normally
chosen to be in the range between 5% - 10% of the minimum DC bus voltage
– Commutation Frequency
– Nominal Power of the converter
-
Ripple of Twice the Utility Grid Frequency (Active Filter)
The worst situation takes place when it is necessary to balance a load of negative
sequence to nominal. In these circumstances the ripple is twice the utility grid
frequency and the capacitance should fulfill the requirement [39], [40]:
Eq. 162
– Base frequency of the converter
-
Ripple of frequency equal to three times the modulation frequency
This ripple produces an unbalance voltage between the capacitor banks in the DC link
bus and should be limited.
√
Eq. 163
√
- Phase current of the converter
PED2 - 841
Page 81
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
– The unbalance voltage between the capacitor banks is considerate to 5% of
The capacitance of each capacitor in the DC link should fulfill this requirements and
its value should be higher than the biggest one for the given conditions. If these requirements
are not fulfilled some of the following negative effect that affects the normal work of the
converter will be observed [39], [40]:
-
Possible overvoltage’s in the power electronic devices and in the DC bus capacitors
-
Worsening of the quality of the current that circulate for the load
-
In extreme cases an inappropriate behavior of the converter
PED2 - 841
Page 82
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Chapter 7
Conclusions and future work
In this chapter the main conclusions for each part of the report are going to be
presented along with the main directions that can be studied and implemented in the future,
starting from the work that has been done so far.
7.1. Conclusions
System Modelling
All the components of the system were implemented in Matlab Simulink to test their
behaviour. Each mathematical model was developed to simulate as best as possible the real
system. During the development process simplifications were made to the mathematical
model in order to reduce the complexity and to make the process faster.
From the results presented in the previous chapter it can be observed that each
model provides relevant information, comparable with the practical component that it models.
From this information we can conclude that the models are correctly implemented and the
control strategies can be applied to them.
System Control
In order to implement the control, the converter was separated in two parts, the
machine side converter and the grid side converter. For each part of the converter a different
control strategy was implemented.
For the part of the converter placed on the machine side a field oriented control was
applied, where the current and the speed of the machine are controlled.
For the part of the converter placed on the grid side a current control was applied in
order to maintain unity power factor for the power transmitted to the grid. A DC voltage
control was also implemented to maintain the DC voltage level in the DC link to a constant
value. The last control was made for the reactive power, which has to be controlled in fault
situations as voltage dip.
PED2 - 841
Page 83
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
The control implemented on the converter has provided acceptable results for the
model as it can be observed from the results presented in the previous chapter.
The system is efficiently controlled in different working situations as starting the
turbine, stopping the turbine and grid faults, as well as in normal working situation, when the
entire process is in steady state operation.
Converter design program
The presented converter design program offers the basic concept for calculation of a
multilevel NPC converter. The output results from the program include the level of the
topology needed to implement the NPC converter, the quantity and the ratings for the
semiconductor devices and DC link values for the capacitors based on the user input
specifications. Values regarding the losses in the components and the efficiency of the
converter are also calculated and presented in the output.
The results obtained are only theoretical, they have not been verified with real data
in order to proof if they are correct or not.
7.2. Future Work
System Modelling
In order to obtain results closer to the practical system the mathematical models
have to be made with a more increase degree of complexity that can cover a larger number of
phenomenon’s present appear in the real system.
The grid model can be implemented with the connection switch in order to be able to
simulate the grid connection procedure and to implement the control for this procedure.
The Darreius wind turbine presents a different behaviour from the normal wind
turbines which are already modelled in the literature, which make this topology interesting for
further study and modelling.
System Control
Because the control presented in this project has proven to work in the simulation a
next step will be to implement it in a practical system in order to validate its behaviour. All the
control system presented is in continuous time all the components are considered ideal. The
next step regarding this is to discretize the control system and to implement PWM modulators.
More control strategies have to be implemented for the real system as: voltage
balancing control and control for different fault situations.
Converter design program
Future work regarding the converter design should include more detailed component
selection including bigger library for the semiconductors and additional components such as
gate drives.
PED2 - 841
Page 84
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
An important step to be carried out is to verify the data provided by the software
with real applications in order to prof if they are correct or not.
Thermal design including transient and steady state models thermal models should
be implemented and also the program should be able to propose different cooling techniques
and heat sink selection based on the obtained results.
PED2 - 841
Page 85
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
Page 86
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
References
1. S.M.Muyeen, Wind Power Chapter 1, June 01, 2010.
2. Anonymous [Online]. available:
http://www.window.state.tx.us/specialrpt/energy/renewable/.
3. Anonymous Global wind statistics [Online]. available: http://www.ewea.org/.
4. I. Paraschivoiu, Wind turbine design: with emphasis on Darrieus concept, Montreal:
Polytechnic International Press, 2002.
5. K. Ma and F. Blaabjerg, "Multilevel converters for 10 MW wind turbines," in Power
Electronics and Applications (EPE 2011), Proceedings of the 2011-14th European Conference
on, 2011, pp. 1-10.
6. K. Ma, F. Blaabjerg and D. Xu, "Power devices loading in multilevel converters for 10 MW
wind turbines," in Industrial Electronics (ISIE), 2011 IEEE International Symposium on, 2011, pp.
340-346.
7. K. Ma, F. Blaabjerg and M. Liserre, "Thermal analysis of multilevel grid side converters for 10
MW wind turbines under Low Voltage Ride Through," in Energy Conversion Congress and
Exposition (ECCE), 2011 IEEE, 2011, pp. 2117-2124.
8. C.H. Ng, M.A. Parker, L. Ran, P.J. Tavner, J.R. Bumby and E. Spooner, "A multilevel modular
converter for a large, light weight wind turbine generator," Power Electronics, IEEE
Transactions on, vol. 23, no. 3, pp. 1062-1074 2008.
9. H. Abu-Rub, J. Holtz, J. Rodriguez and G. Baoming, "Medium-voltage multilevel converters—
State of the art, challenges, and requirements in industrial applications," Industrial Electronics,
IEEE Transactions on, vol. 57, no. 8, pp. 2581-2596 2010.
10. S. Bernet, "State of the art and developments of medium voltage converters–an overview,"
Przeglad Elektrotechniczny (Electrical Review), vol. 82, no. 5, pp. 1-10 2006.
11. J.M. Carrasco, L.G. Franquelo, J.T. Bialasiewicz, E. Galván, R.P. Guisado, M.A. Prats, J.I. León
and N. Moreno-Alfonso, "Power-electronic systems for the grid integration of renewable
energy sources: A survey," Industrial Electronics, IEEE Transactions on, vol. 53, no. 4, pp. 10021016 2006.
12. Z. Chen, J.M. Guerrero and F. Blaabjerg, "A review of the state of the art of power
electronics for wind turbines," Power Electronics, IEEE Transactions on, vol. 24, no. 8, pp. 18591875 2009.
13. L.G. Franquelo, J. Rodriguez, J.I. Leon, S. Kouro, R. Portillo and M.A. Prats, "The age of
multilevel converters arrives," Industrial Electronics Magazine, IEEE, vol. 2, no. 2, pp. 28-39
2008.
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
14. S. Kouro, M. Malinowski, K. Gopakumar, J. Pou, L.G. Franquelo, B. Wu, J. Rodriguez, M.A.
Perez and J.I. Leon, "Recent advances and industrial applications of multilevel converters,"
Industrial Electronics, IEEE Transactions on, vol. 57, no. 8, pp. 2553-2580 2010.
15. D. Krug, S. Bernet, S.S. Fazel, K. Jalili and M. Malinowski, "Comparison of 2.3-kV mediumvoltage multilevel converters for industrial medium-voltage drives," Industrial Electronics, IEEE
Transactions on, vol. 54, no. 6, pp. 2979-2992 2007.
16. M. Malinowski, K. Gopakumar, J. Rodriguez and M.A. Perez, "A survey on cascaded
multilevel inverters," Industrial Electronics, IEEE Transactions on, vol. 57, no. 7, pp. 2197-2206
2010.
17. T. Porselvi and R. Muthu, "Comparison of Cascaded H-Bridge, Neutral Point Clamped and
Flying Capacitor multilevel inverters using multicarrier PWM," in India Conference (INDICON),
2011 Annual IEEE, 2011, pp. 1-4.
18. R.C. Portillo, M.M. Prats, J.I. León, J.A. Sanchez, J.M. Carrasco, E. Galván and L.G.
Franquelo, "Modeling strategy for back-to-back three-level converters applied to high-power
wind turbines," Industrial Electronics, IEEE Transactions on, vol. 53, no. 5, pp. 1483-1491 2006.
19. J.G.P. Reddy and K.R. Reddy, "Design and simulation of cascaded H-bridge multilevel
inverter based DSTATCOM,".
20. J. Rodriguez, J. Lai and F.Z. Peng, "Multilevel inverters: A survey of topologies, controls, and
applications," Industrial Electronics, IEEE Transactions on, vol. 49, no. 4, pp. 724-738 2002.
21. J. Rodríguez, S. Bernet, B. Wu, J.O. Pontt and S. Kouro, "Multilevel voltage-sourceconverter topologies for industrial medium-voltage drives," Industrial Electronics, IEEE
Transactions on, vol. 54, no. 6, pp. 2930-2945 2007.
22. M.D. Manjrekar and T.A. Lipo, "A hybrid multilevel inverter topology for drive
applications," in Applied Power Electronics Conference and Exposition, 1998. APEC'98.
Conference Proceedings 1998., Thirteenth Annual, 1998, pp. 523-529.
23. Carlos Castillo Bonilla, Shweta Merilyn Tigga, "Design and performance comparison of twolevel and multilevel converters for HVDC applications," 2011.
24. Surin Khomfoi, Leon M. Tolbert, "Chapter 31 Multilevel Power Converters," in Anonymous .
25. Samir Kouro, Mariusz Malinowski, K. Gopakumar, Josep Pou, Leopoldo G. Franquelo,
BinWu, Jose Rodriguez, Marcelo A. Pérez, Jose I. Leon, "Recent advances and industrial
applications of multilevel converters," AUGUST 2010.
26. Seyed Saeed Fazel, "Investigation and comparison of multi-level converters for medium
voltage applications," 23.08.2007.
27. Jih-Sheng Lai, Fang Zheng Peng, "Multilevel converters-A new breed of power converters,"
1996.
28. José Rodríguez, Jih-Sheng Lai, Fang Zheng Peng, "Multilevel inverters: A survey of
topologies,controls, and applications," AUGUST 2002.
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
29. S.J. Chapman, Electric machinery fundamentals, McGraw-Hill, 1985.
30. T.A. Lipo, Vector control and dynamics of AC drives, Oxford University Press, USA, 1996.
31. P.C. Krause, O. Wasynczuk and S.D. Sudhoff, "Analysis of electric machinery and drive
systems," 2002.
32. A. Hughes, Electric motors and drives: fundamentals, types and applications, Newnes, 2005.
33. MathWorks. (2013). Wind Turbine<br />Implement model of variable pitch wind turbine
[Online]. available: http://www.mathworks.se/help/physmod/powersys/ref/windturbine.html.
34. S.S. Lechat, "Voltage oriented control of three‐phase boost PWM converters," 2010.
35. A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Systems, Wiley, 2010.
36. R. Ottersten, On control of back-to-back converters and sensorless induction machine
drives, Chalmers University of Technology, 2003.
37. Energinet.dk. (1-30 September 2010). Technical regulation 3.2.5 for wind power plants
with a power output greater than 11 kW [Online]. available:
http://www.energinet.dk/SiteCollectionDocuments/Engelske%20dokumenter/El/5598610_v1_Grid%20Code%203%202%205_v%204%201-30%20%20September%202010.pdf.
38. Hang-Seok Choi. Application Note AN4137<br />Design Guidelines for Off-line Flyback
Converters Using Fairchild Power Switch [Online]. available: www.fairchildsemi.com.
39. Emilio J. Bueno, Santiago C´obreces, Francisco J. Rodrıguez, A lvaro Hernandez, Felipe
Espinosa, "Design of a back-to-back NPC converter interface for wind turbines with squirrelcage<br />Induction generator," SEPTEMBER 2008.
40. Emilio J. Bueno, Santiago Cobreces, Francisco J. Rodriguez, Felipe Espinosa, Marta Alonso,
Rau'l Alcaraz, "Calculation of the DC-bus capacitors of the backto to back NPC converters,".
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Appendix A
Converter design program
%% A help file is presented with all of the used variables as an
addition
%% Input values for the Converter
% In this part the user has to introduce the design variables for the
% converter;
Sinput=5e3;
% input Power of the converter
Vllinput=12000;
% input Voltage level of the converter
Iphase=Sinput/(sqrt(3)*Vllinput);
%phase current of the converter
fsw=1000;
% commutation period
Tsw=1/fsw;
% commutation frequency
fgrid=50;
% grid ferquency
Wbase=2*pi*fgrid;
% base frequency of the converter
ton=0.17e-4;
% diode on time
toff=0.13e-4;
%diode off time
Tbase=1/fgrid;
%% IGBT Selection
%IGBT 1 - Vigbt=1700 V;
PED2 - 841
Iigbt=1600 A;
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
%IGBT 2 - Vigbt=3300 V;
%IGBT 3 - Vigbt=4500 V;
%IGBT 4 - Vigbt=6500 V;
selectIGBT=4;
Iigbt=1500 A;
Iigbt=1200 A;
Iigbt=750 A;
[Vigbt, Iigbt, Eon, Eoff, Rcc, Vce]=IGBT(selectIGBT);
if Iigbt<Iphase
disp('The IGBT selected cannot withstand the current;')
end
%% Diode Selection
%Diode 1 - Idiode=275
%Diode 2 - Idiode=1100
%Diode 3 - Idiode=1650
%Diode 4 - Idiode=2750
selectDiode=4;
A;
A;
A;
A;
Vdiode=4500V;
Vdiode=4500V;
Vdiode=4500V;
Vdiode=4500V;
[Vdiode, Idiode, Vfd, Ir]=Diode(selectDiode);
if Idiode<Iphase
disp('The selected diode cannot withstand the current;')
end
%% DC-bus Voltage level calculation
% The minimum and the maximum DC voltage of the converter is computed;
k=1.5;
%coefficient for the DC bus max voltage 1,5 - 2
Vdcmin=Vllinput*sqrt(2);
%minimum dc-bus voltage level
Vdcmax=Vllinput*k;
%maximum dc-bus voltage level
%% Converter Level Determination
convLevelIGBT=ceil(Vdcmax/Vigbt)+1;
convLevelDiode=ceil(Vdcmax/Vdiode)+1;
convLevel=max(convLevelIGBT,convLevelDiode);
disp(['The convertor need to have at least ',num2str(convLevel),'
levels.'])
%%Number of componenets for the convertor determination
ClmapingDiodes=6*(convLevel-1)*(convLevel-2);
disp(['The convertor will have ',num2str(ClmapingDiodes),' clamping
diodes.'])
igbts=12*(convLevel-1);
freewhdiodes=igbts;
disp(['The convertor will have ',num2str(igbts),' IGBTs.'])
disp(['The convertor will have ',num2str(freewhdiodes),' Free-wheeling
diodes.'])
%% Capacitor Selection
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
% In this part of the program the value for the capacitor si selected;
deltaVdc=0.1*Vdcmin;
% deltaVdc= maximum allowed ripple
deltaVp=deltaVdc/2;
Cdc1=(Tsw*Sinput)/(2*deltaVdc*Vdcmin);
%Ripple of High frequency due to the commutation
Cdc2=Sinput/(2*Wbase*deltaVdc*Vdcmin);
%Ripple of Twice the utility grid frequency
Cdc3=(4*sqrt(2)*Iphase*Tbase)/(3*pi^3*deltaVp);
%Ripple of frequency equal to three times modulation frequency
Cdc=max(Cdc1,max(Cdc2,Cdc3));
Capnumber=convLevel-1;
disp(['The capacitor should have at least ',num2str(Cdc),' F
capacitanse.'])
disp(['The convertor will have ',num2str(Capnumber),' Capacitors.'])
%% Power Losses Determination
% Power losses for the IGBT's
Vf=Vce+Rcc*Iphase;
Pcond=Iphase*Vf*0.5;
% Conduction losses
Pswitch=(Eon+Eoff)*Tsw;
% Switching losses
igbtlosses=(Pswitch+Pcond)*igbts;
disp(['The losses for IGBTs are ',num2str(igbtlosses),' watts.'])
%Power losses for the Diodes
Pconddiode=Vfd*Iphase*ton/Tsw;
% Diode Conduction losses
Poff=Ir*Vdcmax*toff/Tsw;
% Diode off-state losses
Diodelosses=(Pconddiode+Poff)*(ClmapingDiodes+freewhdiodes);
disp(['The losses for the Diodes are ',num2str(Diodelosses),'
watts.'])
%%Converter efficiency
eff=(Sinput-(igbtlosses+Diodelosses))*100/Sinput;
disp(['The Efficiency of the converter is ',num2str(eff),' %.'])
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
Appendix B
Semiconductors used in the design program
The switching devices selected for the design program are IGBT’s from the ABB
manufacture. The codes of the devices with the voltage and current rating are
presented in the following table.
IGBT's used for the converter design program
Code of the device
Voltage rating
Current rating
5SNA 1600N170100
1700
1600
5SNA 1500E330305
3300
1500
5SNA 1200G450350
4500
1200
5SNA 0750G650300
6500
750
The diodes selected for the design program are also from the ABB manufacture. The
main parameters for the diodes the reverse voltage rating and the current rating of the
devices are presented in the following table.
Diodes used for the converter design program
Code of the device
Voltage rating
Current rating
5SDF 03D4502
4500
275
5SDF 10H4503
4500
1100
5SDF 16L4503
4500
1650
5SDF 28L4520
4500
2620
PED2 - 841
CONTROL OF 5MW MULTILEVEL CONVERTER FOR DIRECT DRIVE WIND
TURBINE APPLICATION
PED2 - 841
Appendix 3 Report - Development of Modulation Strategies for NPC Inverter
Addressing DC Link Balancing and CMV Reduction
This report addresses the development of a multi-level inverter suitable for the grid side DeepWind
converter. Two level inverters are known to generate Common Mode Voltage (CMV) in the machine
windings, causing machine failures due to bearing currents. Furthermore, a leakage current will flow
through the stator windings and motor frame creating common mode electromagnetic interference. Taking
these problems into consideration and the fact that the multilevel inverters offer better Total Harmonic
Distortion (THD) as well as the possibility to reduce the CMV by selecting a suitable modulation strategy,
they became a point of interest. In addition, multi-level inverters offer the possibility of developing high
voltage units without placing extra voltage stress on the semiconductor switches. Compared to higher level
topologies, a good ratio between complexity and performance is offered by the three-level topology. As
this type of inverter synthesises the output voltage from series connected DC link capacitors, problems
such as neutral point balancing might appear, causing voltage stress on the semiconductors.
The aim of this project is to develop modulation strategies that address both DC link voltage balancing and
CMV reduction.
Four modulation strategies that address these problems were developed and validated through simulation.
In order to experimentally validate them, a small scale Neutral Point Clamped (NPC) inverter was designed,
built and tested. Analysis was performed on each developed modulation, of the CMV and Electromagnetic
Interference (EMI) and neutral point balance assessment. The authors conclude that all proposed strategies
offer better CMV and EMI spectrum compared with classical NTV and ZCM.
Authors: Daniela Boian, Ciprian Biris
Master Thesis
Department of Energy Technology-Pontoppidanstraede 101
Aalborg University, Denmark
Development of Modulation Strategies for NPC Inverter Addressing DC
Link Balancing and CMV Reduction
PED 9 -10
2011-2012
Title:
Semester:
Semester theme:
Project period:
ECTS:
Supervisors:
Project group:
Development of Modulation Strategies for NPC Inverter Addressing DC Link
Balancing and CMV Reduction
9th – 10th
Master Thesis
01.09.2011 to 31.05.2012
60
Remus Teodorescu
Michal Sztykiel
PED1041
SYNOPSIS:
Two level inverters generate Common Mode Voltage (CMV) in the motor
windings, causing motor failures due to bearing currents. Furthermore, a
leakage current will flow throughout the stator windings and motor frame
creating common mode electromagnetic interference. Taking these
problems into consideration and the fact that the multilevel inverters
offer better Total Harmonic Distortion (THD) as well as the possibility to
reduce the CMV by modulation strategy, they it became a point of
interest. Compared to higher level topologies, a good ratio between
complexity and performance is offered by the three-level topology. As
this type of inverter synthesises the output voltage from series connected
DC link capacitors, problems such as neutral point balancing might
appear, causing voltage stress on the semiconductors.
Daniela Boian
Ciprian Biris
The aim of this project is to develop modulation strategies that address
both DC link voltage balancing and CMV reduction.
Four modulation strategies that address these problems were developed
and validated through simulation. Furthermore, in order to
experimentally validate them, a Neutral Point Clamped (NPC) inverter
was designed and built. Analysis, regarding CMV and Electromagnetic
Interference (EMI) together with neutral point balance assessment, was
performed on each developed modulation which concluded that all
proposed strategies offer better CMV and EMI spectrum compared with
classical NTV and ZCM.
Copies:
Pages:
Appendix:
Supplements:
[3]
[ 110 ]
[ 11 ]
[ 1 CD ]
By signing this document, each member of the group confirms that all group members have participated in
the project work, and thereby all members are collectively liable for the contents of the report.
Furthermore, all group members confirm that the report does not include plagiarism.
[I]
[II]
Preface
The Master in Science thesis was carried out during 9th and 10th semester at Aalborg University in the
Department of Energy Technology starting from 1st of September 2011 until 31st of May 2012. The project
“Modulation of three-level inverter with common-mode voltage elimination and DC-link balancing” was
chosen by the authors from the Vestas catalogue containing proposals for students from Energy Technology
department.
Acknowledgments
The authors would like to thank their supervisors: Remus Teodorescu, Michal Sztykiel and Osman Selcuk
Senturk for their guidance during the master thesis.
They would like to give special thanks to Stig Munk-Nielsen, Carsten Karup Nielsen and Laszlo Mathe for
their help during inverter design, as well as to Adrian Hasmasan and Ram Krishan Maheshwari.
More thanks goes to Anamaria Man for her moral support as well as to Krisztina Leban.
The authors would like to give thanks to Vestas for the financial support during the two years of Master in
Science.
The Master in Science Thesis was conducted by:
Daniela Boian
Ciprian Biris
_________________________
___________________________
[III]
[IV]
Summary
As well known the two-level topology generates CMV in the motor windings furthermore causing motor
failures due to bearing currents. As there are parasitic capacitive couplings between the stator windings and
the motor frame a common mode leakage current will flow, hence there will be common mode
electromagnetic interference. Taking these problems into consideration, multilevel inverters have gained
interest. These types of inverters offer lower THD in the phase-to-phase voltage as well as the possibility to
reduce the CMV through modulation strategy. As the phase-to-phase waveform is produced form series
connected capacitors an unbalance may appear causing voltage stress on the IGBTs.
Solutions to reduce the common mode voltage and to balance the DC link through modulation strategies
have been studied in this project due to their cost effectiveness.
This thesis is structured in six chapters and has ten appendixes. The background of the three-level NPC
inverter together with the problem formulation regarding CMV and DC link balance is presented in the first
chapter. Furthermore, the study and development of new and improved modulation strategies as well as the
hardware design represent the objectives. Also, project limitations are stated.
Chapter two is focused on the NPC inverter topology and its background. Further in this chapter space vector
modulation and switching states make an introduction for the classical modulation strategies studied:
Nearest Three Vectors with Even Harmonic Elimination (NTV-EHE) and Zero Common Mode (ZCM). Also the
DC link balancing problem and mitigation for NPC converters is studied as well as CMV and its mechanism
together with its effects. The end of second chapter presents the methods for measuring the CMV and EMI.
The new proposed modulation strategies are presented in the third chapter. The theoretical basics together
with the validation through simulations are part of the acknowledgement of these strategies. The chapter
ends with a comparative evaluation of the developed strategies compared with the classical ones.
The fourth chapter is dedicated entirely to hardware design. A NPC inverter was built featuring reduced size,
snubberless design due to newly introduced NPC leg Insulated Gate Bipolar Transistor (IGBT) modules,
protections, RS-232 and CAN communications and mixed analogue and digital design. The overview of the
developed platform is made after which, the sizing and implementation of the DC link is described, IGBT
modules, gate drivers, microcontroller and protections. The thermal cooling solution is presented together
with its validation through thermal imaging. This chapter ends with an overview of the implemented control
on the Digital Signal Processor (DSP) and Complex Programmable Logic Device (CPLD) is followed by
hardware validation tests.
The experimental validation and analysis of the developed modulation strategies is the main focus of
chapter 5. The results and waveforms of the new strategies as well as the classical ones are presented and
analysed together with the DC link balancing capability assessment and CMV evaluation. The chapter is
ended with results regarding the conductive EMI produced by these strategies.
The last chapter presents conclusions regarding the results of CMV, DC link balancing and conductive EMI of
the developed modulation strategies, in comparison with classical ones.
[V]
Furthermore, the appendixes are included as follows:











Appendix 1: Project Proposal
Appendix 2:
Appendix 3: Experimental Setup Data
Appendix 4: CPLD/DSP Pin Assignment
Appendix 5: CPLD Functional Schematic
Appendix 6: PCB Photos
Appendix 7: PCB Layers
Appendix 8: Electrical Schematic
Appendix 9: Bill of Materials
Appendix 10: Paper
Appendix 11: Contents of the CD
Contributions
This project brings the following contributions:


NPC inverter design with NPC leg IGBT modules
 Reduced size
 RS-232, RS485 and CAN communication
 Software and hardware protections
 Snubberless design
 Embedded DSP
Modulation Strategies that address both DC link balancing problem and CMV reduction
During this project a paper has been written. This paper has been accepted in the IEEE PEDG conference held
in Aalborg, Denmark in June 2012. This paper can be seen in Appendix 10.

Daniela Boian, Ciprian Biris, Remus Teodorescu, Michal Sztykiel, “Development of Modulation
Strategies for NPC Converter Addressing DC Link Voltage Balancing and CMV Reduction“
[VI]
Abbreviation Full form
AC
ADC
ASD
CAL
CAN
CM
CMC
CMR
CMV
CPLD
CSI
DC
DCB
DMOS
DSP
EDM
EHE
EMC
EMI
ePWM
FFT
FLC
FLIR
GPIO
HF
HV
HVDC
I/O
IC
IGBT
ISR
LCI
LED
LISN
NP
NPC
NPT
NTC
NTV
NTV-EHE
OLOM
OSOM
PCB
PSRR
PWD
Alternative Current
Analogue to Digital Converter
Adjustable Speed Drive
Controlled Axial Lifetime
Controller Area Network
Common Mode
Common Mode Current
Common Mode Rejection
Common Mode Voltage
Complex Programmable Logic Device
Current Source Inverter
Direct Current
Direct Copper Bonded
Double Diffused Metal Oxide Semiconductor
Digital Signal Processor
Electric Discharge Machine
Even Harmonic Elimination
Electromagnetic Compatibility
Electromagnetic Interference
enhanced Pulse Width Modulator
Fast Fourier Transformation
Flying Capacitor
Forward Looking Infra-Red
General Purpose Input Output
High Frequency
High Voltage
High Voltage DC
Input/ Output
Integrated Circuit
Insulated Gate Bipolar Transistor
Interrupt Service Routine
Load Commutated Inverter
Light Emitting Diode
Line Impedance Stabilisation Network
Neutral Point
Neutral Point Clamped
Non Punch Through
Negative Temperature Coefficient
Nearest Three Vectors
NTV with Even Harmonic Elimination
One Large One Medium
One Small One Medium
Printed Circuit Board
Power Supply Rejection Ratio
Pulse Width Distortion
[VII]
PWM
RAM
RC
RCD
RL
RLL
RMS
RS3N
RZD
SARAM
SHE
SOIC
SVM
TBCTR
THD
TNPC
UVLO
V/f
VSI
ZCM
ZSML
Pulse Width Modulation
Random Access Memory
Resistive - Capacitive
Random Centre Distribution
Resistive - Inductive
Random Lead-Lag
Root Mean Square
Random Sequence of 3 with Neutral Balancing
Random Zero Distribution
Single Access RAM
Selective Harmonic Elimination
Small Outline Integrated Circuit
Space Vector Modulation
Time Based Counter
Total Harmonic Distortion
Type Neutral Point Clamped
Under Voltage Lock-Out
Volt/hertz
Voltage Source Inverter
Zero Common Mode
Zero Small Medium Large
[VIII]
Table of Contents
Summary ............................................................................................................................................................. V
1.
2.
Introduction ..................................................................................................................................................1
1.1.
Background...........................................................................................................................................1
1.2.
Problem Formulation and Motivation..................................................................................................4
1.3.
Objectives .............................................................................................................................................5
1.4.
Project Limitations................................................................................................................................6
Neutral Point Clamped Converter ................................................................................................................7
2.1.
Background of NPC ...............................................................................................................................7
2.2.
Classical Modulation Strategies......................................................................................................... 13
2.2.1.
Background ................................................................................................................................ 13
2.2.2.
Nearest Three Vectors with Even Harmonic Elimination .......................................................... 19
2.2.3.
Zero Common Mode Method ................................................................................................... 29
2.3.
DC Link Balancing .............................................................................................................................. 32
2.4.
Common Mode Voltage .................................................................................................................... 34
2.4.1.
A.
Shaft Voltage ..................................................................................................................................... 36
B.
Shaft Current ..................................................................................................................................... 37
2.4.2.
2.5.
3.
Common Mode Voltage in Adjustable Speed Drives ................................................................ 34
Switching Sequence Influence on CMV ..................................................................................... 37
Method of Measuring EMI and CMV................................................................................................. 39
2.5.1.
Method of Measuring EMI ........................................................................................................ 39
2.5.2.
Method of Measuring CMV ....................................................................................................... 41
Improved Modulation Strategies .............................................................................................................. 43
3.1.
One Small One Medium Vector ......................................................................................................... 43
[IX]
4.
5.
3.2.
One Large One Medium Vector ......................................................................................................... 47
3.3.
Zero Small Medium Large Method .................................................................................................... 50
3.4.
Random Sequence of 3 Vectors with Neutral Point Balancing Method............................................ 53
3.5.
Performance Evaluation of Improved Modulation Strategies .......................................................... 56
Hardware Design of three-level NPC Inverter ........................................................................................... 59
4.1.
System Overview ............................................................................................................................... 59
4.2.
DC Link Capacitors and Load ............................................................................................................. 61
4.3.
Switching ........................................................................................................................................... 63
4.4.
Gate Drivers and Protections ............................................................................................................ 65
4.4.1.
Gate Drivers ............................................................................................................................... 65
4.4.2.
Signal Acquisition....................................................................................................................... 70
4.4.3.
Protection Adjustment .............................................................................................................. 76
4.4.4.
Voltage Supply and Regulators .................................................................................................. 77
4.4.5.
Communication ......................................................................................................................... 79
4.5.
Power Tracks Sizing ........................................................................................................................... 80
4.6.
Cooling ............................................................................................................................................... 80
4.7.
CPLD and DSP Control........................................................................................................................ 86
4.8.
Hardware Validation .......................................................................................................................... 89
Experimental Validation and Analysis of the Developed Modulation Strategies...................................... 95
5.1.
Experimental Setup ........................................................................................................................... 95
5.2.
Nearest Three Vectors with Even Harmonic Elimination Method .................................................... 96
5.3.
Zero Common Mode Method............................................................................................................ 96
5.4.
One Large One Medium Method ...................................................................................................... 97
5.5.
Zero Small Medium Large Method .................................................................................................... 98
5.6.
One Small One Medium Method..................................................................................................... 100
5.7.
Random Sequence of 3 with Neutral Point Balancing Method ....................................................... 100
[X]
5.8.
DC Link Balancing Capability............................................................................................................ 101
5.9.
CMV Analysis ................................................................................................................................... 103
5.10.
6.
Comparison of Conductive EMI produced by Modulation Strategies ......................................... 104
Conclusions and Future Work ................................................................................................................. 107
6.1. Conclusions Regarding the Development of Modulation Strategies that Address DC Link Balancing
and CMV Reduction ..................................................................................................................................... 107
6.2.
Conclusions Regarding Hardware Design of the Three-Level NPC Inverter .................................... 108
6.3.
Future Work .................................................................................................................................... 109
Bibliography...........................................................................................................................................................I
Appendix 1: Project Proposal ............................................................................................................................ VII
Appendix 2: Switching Tables for All Methods................................................................................................... IX
Appendix 3: Experimental Setup Data ............................................................................................................. XIII
Appendix 4: CPLD/DSP Pin Assignment ............................................................................................................ XIV
Appendix 5: CPLD Functional Schematic ......................................................................................................... XVII
Appendix 6: PCB Photos ................................................................................................................................... XIX
Appendix 7: PCB Layers .................................................................................................................................... XXI
Appendix 8: Electrical Schematic ................................................................................................................... XXIX
Appendix 9: Bill of Materials .......................................................................................................................... XXXI
Appendix 10: Paper ...................................................................................................................................... XXXIII
Appendix 11: Contents of the CD ...................................................................................................................... XLI
[XI]
[XII]
List of Figures
Figure 1-1 - Typical ASD ........................................................................................................................ 1
Figure 1-2 – Family of High – Power Converters [5].............................................................................. 2
Figure 1-3 – Three-Level NPC Converter Schematic .............................................................................. 3
Figure 2-1 – General Inverter Leg .......................................................................................................... 8
Figure 2-2 – General Three Level Inverter ............................................................................................. 9
Figure 2-3 – Neutral Point Clamped Inverter Topology....................................................................... 10
Figure 2-4 – Switching Paths for NPC Inverter .................................................................................... 11
Figure 2-5 – Space Vector Diagram - Sectors and Regions [19] ......................................................... 14
Figure 2-6 – NPC Vectors and Switching States [28] ........................................................................... 16
Figure 2-7 – NTV – Stationary and Reference Vectors with Corresponding Dwell Times for Sector I,
Region 4 ............................................................................................................................................... 19
Figure 2-8 – Feasible Regions for Case 1 ............................................................................................. 22
Figure 2-9 – Seven Segment Switching Sequence for
in Sector I, Region 4 [19] ........................ 22
Figure 2-10 – Division of Region 2 in Sector I for Minimization of NP Voltage Deviation .................. 23
Figure 2-11 – Seven Segment Switching Sequences for
in Sector 1, Region 2a and 2b ............ 23
Figure 2-12 – Alternation of A and B Switching Sequences for Even Harmonic Elimination [29] ....... 24
Figure 2-13 – Switching Sequence when
is situated in Sector IV, Region 4. .............................. 24
Figure 2-14 – General Structure of NPC Converter Developed in Matlab/Simulink and Plecs ............ 25
Figure 2-15 - Modulation Strategy Structure for Simulation Model .................................................. 26
Figure 2-16 – Output Current for NTV-EHE at
Figure 2-17 – Leg Voltage for NTV-EHE at
– Simulation .................................................. 27
– Simulation ....................................................... 27
Figure 2-18 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for NTV-EHE at
- Simulation ........................................................................................................................... 28
[XIII]
Figure 2-19 Switching Vectors for Zero Common Mode Method ........................................................29
Figure 2-20 – Switching Sequence for the First Sector in ZCM Method ...............................................30
Figure 2-21 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZCM at
- Simulation .....................................................................................................................31
Figure 2-22 – Space Vectors Influence on the NP Current ...................................................................33
Figure 2-23 – Common Mode Voltage Path.........................................................................................35
Figure 2-24 – Parasitic Capacitances [1] ..............................................................................................35
Figure 2-25 – Inverter – Induced Bearing Currents Classification ........................................................37
Figure 2-26 – NTV-EHE Sector I, Region 4 - Leg Voltages and their Resultant CMV ............................38
Figure 2-27 Test Setup for EMI Measurement .....................................................................................40
Figure 2-28 – Test Setup for Measuring the CMV and CMC ................................................................41
Figure 3-1 – One Small One Medium Vector Method ..........................................................................43
Figure 3-2 – Five Segment Switching Sequences for
in Sector I and VII .....................................45
Figure 3-3 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OSOM at
-Simulation ..........................................................................................................................46
Figure 3-4 – One Large One Medium Vector Method ..........................................................................47
Figure 3-5 – Five Segment Switching Sequences for
in Sector I .................................................48
Figure 3-6 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OLOM at
- Simulation ............................................................................................................................49
Figure 3-7 – Space Vector Diagram for Zero Small Medium Method in Sector I .................................50
Figure 3-8 – Switching Sequence for ZSML in Sector I, Region 1 .........................................................51
Figure 3-9 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZSML Method at
ma=1 - Simulation ...............................................................................................................................52
Figure 3-10 – Randomization Effect on CMV on RS3N Modulation Strategy in Sector I, Region 1 .....54
Figure 3-11 – Space Vector Diagram of RS3N Modulation Strategy ...................................................54
Figure 3-12 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for RS3N at
- Simulation ............................................................................................................................55
[XIV]
Figure 3-13 – Modulation Index vs. Line Voltage THD of Classic and Developed Modulation
Strategies based on Developed Simulation ......................................................................................... 57
Figure 4-1 – Simplified Schematic of Hardware Platform ................................................................... 60
Figure 4-2 – DC Link Capacitors from the Developed Experimental Board ......................................... 61
Figure 4-3 – DC Link Configuration Used ............................................................................................. 63
Figure 4-4 – One NPC Leg IGBT Module [49]....................................................................................... 64
Figure 4-5 – Internal NPC Module Schematic...................................................................................... 64
Figure 4-6 –
as a Function of Switching Times [49]....................................................................... 65
Figure 4-7 – Avago ACPL-332j Gate Driver [54] .................................................................................. 66
Figure 4-8 – ACPL-332j Circuit Application .......................................................................................... 66
Figure 4-9 – Miller Capacitor ............................................................................................................... 69
Figure 4-10 – Allegro ACS756 Hall Current Sensor .............................................................................. 71
Figure 4-11 – ACS756 Current Acquisition........................................................................................... 71
Figure 4-12 – Phase Signal Divider ...................................................................................................... 71
Figure 4-13 – LT1366 Voltage Acquisition ........................................................................................... 73
Figure 4-14 – NJ28 Temperature Acquisition ...................................................................................... 74
Figure 4-15 – Window Comparator Configuration ............................................................................. 75
Figure 4-16 – Window Comparator Operation ................................................................................... 76
Figure 4-17 – OPA2343 Buffer Solution............................................................................................... 77
Figure 4-18 – TPS79533, 3.3 Vdc Voltage Regulator........................................................................... 78
Figure 4-19 – CAN and RS-232 / 485 Communication ........................................................................ 79
Figure 4-20 – NPC Leg Module – Copper Baseplate ............................................................................ 81
Figure 4-21 Typical IGBT Structure – Layers and Heat Flow Path [80] ............................................... 81
Figure 4-22 – Losses on Each Component in the NPC Leg ................................................................... 84
Figure 4-23 Thermal Model of Semikron SEMITOP Module (NPC Leg) ............................................... 85
[XV]
Figure 4-24 – Control card Integration into the Designed Inverter......................................................86
Figure 4-25 – DSP Counter Modes .......................................................................................................87
Figure 4-26 – CPLD used for Deadtime and Protection Management .................................................87
Figure 4-27 – Deadtime between Two Complementary IGBTs – Experimental Result ........................89
Figure 4-28 – Turn On and Off Procedures of the Semikron IGBT Module – Experimental Results .....90
Figure 4-29 – Reset Procedure for Restarting the Modulation – Experimental Result ........................91
Figure 4-30 – DC Link Voltage Range Protection – Experimental Results............................................91
Figure 4-31 – Overcurrent Protection – Experimental Result ..............................................................92
Figure 4-32 – Overtemperature Protection – Experimental Result......................................................92
Figure 4-33 – Experimental Setup for Thermal Validation ...................................................................93
Figure 4-34 – Thermal Picture of the Inverter at
After One Hour ...........................................93
Figure 5-1 – Experimental Setup for Testing the Developed Modulation Strategies ...........................95
Figure 5-2 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for NTV-EHE Experimental Results ............................................................................................................................96
Figure 5-3 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZCM Experimental Results ............................................................................................................................97
Figure 5-4 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OLOM Experimental Results ............................................................................................................................98
Figure 5-5 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltage for ZSML Experimental Results ............................................................................................................................99
Figure 5-6 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OSOM Experimental Results ..........................................................................................................................100
Figure 5-7 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for RS3N Experimental Results ..........................................................................................................................101
Figure 5-8 – Experimental Setup Used for DC Link Balancing Capability Assessment .......................102
Figure 5-9 – Capability Curve Function of Phase Current vs. Modulation Index Determined
Experimentally....................................................................................................................................102
[XVI]
Figure 5-10 – FFT on CMV for Classic and Developed Modulation Strategies – Experimental Results
........................................................................................................................................................... 103
Figure 5-11 – Common Mode Current Measurement [87]................................................................ 104
Figure 5-12 – Conductive EMI Currents Produced by Modulation Strategies ................................... 105
[XVII]
[XVIII]
Development of Modulation Strategies for NPC Inverter Addressing DC Link Balancing and CMV Reduction
1. Introduction
This chapter introduces the problems that appear in Adjustable Speed Drives (ASD) - which affect both the
inverter and motor, as well as presenting advantages and disadvantages for the three-level NPC inverter.
Furthermore, problem formulation, motivation, objectives and limitations are stated.
1.1.
Background
A widely discussed subject is the one of saving energy. Electrical motors are widely used to generate motion
from electrical energy [1]. Industrial and domestic applications use electric motors with a large variety of
power ratings. In most countries, electric motors use approximately 70% of the produced electric energy [2].
In the past, DC machines were used due to their simplicity in speed control. Nevertheless, these types of
machines compared with AC ones, have some disadvantages such as higher cost, higher rotor inertia and
maintenance issues with the brushes. Due to these problems, DC machines have been progressively replaced
by AC machines. These types of machines cannot be efficiently controlled with direct connection to the grid,
thus ASD for control of the magnitude and frequency of the output voltage are needed. These types of drives
have a large scale of utilization in industrial applications. Due to the development of adjustable drives, the
reliance in three phase AC motors has increased [1]. As a consequence of the rotor simplicity, induction
motors have allowed solutions with lower cost [3].
As most applications require variable speed. Its principle is to convert the constant AC voltage into a variable
one with the purpose of controlling the speed of the AC motor. A typical structure can be seen in Figure 1-1.
Figure 1-1 - Typical ASD
The Pulse Width Modulation (PWM) inverter needs to synthesise the input voltage in order to obtain the
desired variable output voltage with a corresponding pulse shape sinusoidal.
[1]
Chapter 1 - Introduction
When long cables are required in order to connect the inverter to the motor, a LC filter is used [3]. The
variation in time has to be taken into account as it is dependent on the rise and fall time of the switching
device that might lead to stress at the motor terminals.
Adjustable speed drives can be classified based on the inverter topologies according to [4]:






Voltage Source Inverter (VSI) drives: have a constant DC link voltage. The DC link capacitors are used
in order to supply reactive power to the motor and to smooth the DC link voltage.
Multi-level Voltage Source Inverter drives: uses series connected low voltage IGBTs.
Current Source Inverter (CSI) drives: makes use of DC link current.
Load Commutated Inverter (LCI) drives: takes part of the CSI. This type of drive store energy in the
DC link inductor in order to supply quasi-sinusoidal current.
Cycloconverter: does not have the ability to store energy in the DC link. Each phase of the
Cycloconverter modifies the fixed line AC voltage into an alternating voltage at a variable load
frequency.
Cascade drives: makes use of a three phase diode rectifier that operates at slip frequency and feds
back the power to the supply network through a reactor and line commutated inverter. The motor
speed is controlled by the DC current.
Nowadays, the need to increase efficiency and reduce production cost is the most discussed subject. This
can be achieved by increasing the size and power of all electrical drives and equipment. The power increase
can be done in two ways [5]:


Developing High Voltage (HV) semiconductors with increased voltage blocking capabilities
Development of multilevel inverters
The dominant topology for low voltage is two-level VSI. At medium and high voltage there are a variety of
topologies. In high voltage, it is possible to use direct converters (cyclo-converters) and indirect converters
(with current or voltage in DC link). Figure 1-2 presents the structure for high power converters [5].
Figure 1-2 – Family of High – Power Converters [5]
[2]
Chapter 1 - Introduction
The type of inverter used in this project is NPC Converter with the schematic from Figure 1-3. As it can be
seen, this inverter has the neutral point clamped to the midpoint of the DC link. This configuration uses
series IGBTs, thus the stress on the devices is reduced. Furthermore, the NP is used in order to generate at
the inverter output three levels of voltage:
, based on commutation of the twelve switching
devices. The combination of these semiconductors allows 27 switching vectors.
Figure 1-3 – Three-Level NPC Converter Schematic
A three phase inverter provides leg voltages (
), phase voltages (
) and phase-to-phase
voltages (
). Aside from these voltages, another one appears between the neutral point of the
motor and the neutral point of the inverter, acknowledged as common mode voltage (CMV). This voltage
can be calculated based on the influence of each switching vector; however the general formula for
calculating CMV is presented in [6] and can be seen in equation (1-1).
(1-1)
Based on equation (1-1) it can be noticed that the CMV is created by the switching pattern on each device,
thus this voltage can be reduced by using appropriate switching patterns.
The effect of high frequency PWM voltage is generally neglected in the electromagnetic performance of the
induction motor. From the motor point of view it needs to be said that there exist small capacitive
couplings, however they can be neglected in low frequency analysis. At high frequencies, a low impedance
path is created and current flows through the capacitive couplings. As a consequence of high dv/dt applied
to the motor, high frequency leakage currents flow through the capacitive couplings created between the
stator winding and motor frame. Furthermore, as the motor frame is connected to the ground the high
frequency currents may cause electromagnetic interference (EMI) [7].
As the semiconductors are improved the switching speed increases making the effect of capacitive couplings
to be dominant. Considering this, two important parasitic capacitances can be observed: the one between
stator winding – stator iron and stator winding – rotor iron [8]. These capacitances in interaction with CMV
[3]
Chapter 1 - Introduction
and high dv/dt can cause shaft voltage, leading to bearing currents, and leakage currents, which further lead
to noise and EMI, in the induction motor [3].
The main problems in ASD are CMV and high dv/dt. The two problems cause issues such as [3]:




Grounding currents – circulating between the parasitic capacitance inside the motor and ground
Shaft voltages – that result in bearing currents
Conductive and radiated noise
Overvoltage at motor terminals
There have been developed multiple techniques with the purpose of reducing or eliminating the shaft
voltage and CMV. The PWM techniques based can be summarised according to [3] as:


Bearing current reduction methods
Leakage current mitigation techniques
Three level inverters present advantages such as reduced voltage ratings for the semiconductors, good
harmonic spectrum and good dynamic response, that makes them very popular. As disadvantage they have
is increased control complexity over conventional VSI [9].
1.2.
Problem Formulation and Motivation
When referring to three-level Voltage Source Inverters (VSI) it needs to be mentioned that since their
invention they have been considered to be used in high capacity, high performance AC drives applications
[10]. Taking this into account this thesis focuses mainly on the ASD application.
ASD are often used in industrial and household applications, like ventilation system, pumps and electric
drives for machine tools. The output speed can be modified through magnitude and frequency of the output
voltage by means of PWM [3].
Common Mode Voltage (CMV) is defined as the voltage between the neutral point of the inverter and
neutral of the wye connected load, and it is generated by the PWM strategies. This type of voltage creates
important problems in high switching frequencies. The techniques regarding attenuation of high frequency
problems in AC motor drives systems have at base the reduction of CMV. This voltage has a very important
influence over the shaft voltage. One important solution for reducing the shaft voltage and leakage current is
the reduction of CMV. This can be achieved using two methods [3]:


Attenuation of the shaft voltage through motor design
CMV attenuation through PWM strategy
[4]
Chapter 1 - Introduction
Further on, in low frequency analysis these capacitances can be neglected due to their small values, but their
effects become important when the switching frequency of the converter is increased as the switching
devices are improved. These capacitances offer a flow path for high frequency currents.
One important problem discovered in three – level NPC converter is the balancing of the DC link Neutral
Point (NP). This type of inverter is exposed to problems like fluctuations in the NP due to irregular and
unpredictable charging and discharging of the upper and lower DC link capacitors [10]. As it is defined in
literature [10] , there is an unbalance regarding the charging and discharging in each capacitor, thus the
voltage across the capacitor may rise or fall and the NP voltage will not be able to maintain half of the DC
link voltage. Due to this problem a high voltage may be applied to the semiconductors or DC link capacitors
causing damage. This can be solved through three methods:



Separate DC sources [11]
Voltage regulators for each level using an additional small leg [12]
Modified PWM pattern and voltage vector selection [11] [13]
The main focus of the thesis is to reduce the CMV and to balance the DC link voltage through appropriate
PWM strategies due to their cost effectiveness.
1.3.
Objectives
The following objectives have to be addressed according to Appendix 1: Project Proposal.


Development of modulation strategies that address DC link balancing and CMV reduction
 Study of classical modulation strategies
 Study of DC link unbalance and CMV
 Development of simulation model to test different modulation strategies before
experimental implementation
 CMV Analysis
 Analysis of DC link unbalance
Hardware design of the three-level NPC inverter
 Study of NPC converter
 DSP implementation of the modulation strategy for the three level converter
 Comparison of the emitted common mode EMI from conventional modulations and the
developed ones
 CMV Analysis
 Analysis of DC link unbalance
[5]
Chapter 1 - Introduction
1.4.
Project Limitations
During the development of this project some limitations had to be imposed, due to limited time and/or
resources. The main limitations are:




Only conducted EMI up to 20 MHz– radiated EMI requires special chamber and equipment
Current <16 A – for analysing the developed modulation strategies this current is enough
Application – The developed methods are tested only for induction motor adjustable speed drives
DC link voltage,
– for analysis purposes and due to the fact that most wye connected
induction motors available in the Aalborg University laboratories have the rated voltage of 380 – 420
V. Hence, the DC link has to be large enough in order to produce the rated voltage:
√
.
[6]
√
Chapter 2 – NPC Converter
2. Neutral Point Clamped Converter
This chapter begins with the general theory regarding the three-level NPC inverter, followed by an
introduction into SVM and theory concerning classical modulation strategies. A general simulation structure
was developed. Simulation results are presented for further comparison with the proposed modulation
strategies. The problems that need to be addressed in this project, DC link balancing and CMV reduction are
presented.
2.1.
Background of NPC
In the last few years interest in multilevel converters has increased. Different topologies for utility grid and
drives have been studied among years. The ability to synthesise waveforms with the improvement in
harmonic spectrum and acquirement of higher voltages with a limited maximum device rating made three
level inverters suitable for high voltage and high power applications [14].
The oldest topology of three level inverters was introduced by Nabae in 1981 [11], the neutral point clamped
topology. The layout of three level diode – clamped inverter is also called three – level NPC inverter.
Compared with two level voltage source inverters this topology has better spectral performance. Multilevel
inverters reduce voltage stress on the devices. Bhagwat and Stefanovic improved the spectral structure of
output waveforms in multilevel inverters. The original topology with the neutral point clamped has been
expanded to higher number of levels. The required voltage blocking capability of the clamping diodes varies
with the levels, thus multiple diodes at higher levels may be required [14].
According to [15] a general comparison between two level and three level inverter can be done. This is
presented in Table 2-1.
Table 2-1 – Comparison between two level inverter and three level inverter [15]
Driver
PWM Algorithms
DC Link
Output Filters
THD
Current Ripple Losses
Two Level
Better
Better
No difference
Worst
Worst
Worst
Three Level
Worst
Worst
No difference
Much better
Much better
Much better
Much worst
Much better
IGBT Voltage
Losses (switching/conduction)
[7]
Chapter 2 – NPC Converter
Multilevel converters supply ingenious methods of series connection of the switches, therefore enabling the
processing of voltages that are higher than the device ratings. These converters are effective by means of
reduction of harmonic distortion and dv/dt output voltage, thus making the devices useful for utility
interface and drives [16]. One of the major disadvantages in multilevel inverters is the voltage unbalance
between different levels. The output voltage of a three level inverter is a quasi-sinusoidal waveform [17].
Problems created by common mode voltages are encountered in conventional two level drives. These
voltages are responsible for the shaft voltages and bearing failures, thus both need to be eliminated or
reduced within certain bounds. Four leg inverters, passive filters, passive elements with active circuitry and
dual bridge inverters have been investigated for reduction of common mode voltages [3].
Multi-level inverters can be divided into three main categories based on their topology [9]:



Neutral Point Clamped (NPC)
Flying Capacitor (FLC)
H – Bridge
By means of PWM, quasi-sinusoidal waveform can be obtained at the output of the inverter. In order to have
a high quality waveform, filtering and high switching frequency is required. Flexibility can be obtained by
splitting the DC link voltage in two equal sources [18]. Now the output can have the voltage levels: 0 and
. This configuration can be seen in Figure 2-1:
Figure 2-1 – General Inverter Leg
The idea can be expanded in order to obtain a generalized three level inverter that can be seen in Figure 2-2.
In order to raise the blocking capacity of conventional two level inverters the switching devices are
connected in series. Fast switching devices connected in series that switch simultaneous will generate a high
dv/dt at the output terminal of the inverter. The short rise time of the output of the inverter correlated with
a long cable is potentially hazardous for the insulation of a motor and for the cable due to the fact that high
dv/dt generates partial discharges and as a result the aging of the insulation is accelerated. This
phenomenon appears in the motor as leakage current. In motor drives this current leads to electromagnetic
[8]
Chapter 2 – NPC Converter
interference noise, thus causing trip of the inverter, problems with the protections of the supply transformer
and interference with electronic equipment from the vicinity [2].
Figure 2-2 – General Three Level Inverter
The switching states can be described using three variables in order to show where each phase leg is
connected. The variables are:
for connection to neutral point,
for connection to the negative bus and
for connection to the positive bus. These variables are Boolean. Only one of the variables can be on high
state for each leg. This property can be written as in equation (2-1):
(2-1)
If the voltages on the DC link capacitors are equal,
and x is one of the three phases of the load then
the leg voltage of the inverter can be written as in equation (2-2):
(2-2)
This results in three possible phase voltages:
,
and 0. If x and y are two different phases, the phase
to phase voltage can be written as in equation (2-3):
(2-3)
Furthermore, five levels of line voltage can be obtained: 0,
,
,
and
. The phase voltage is
defined as in equation (2-4). If switching variables are introduced in this equation, another equation (2-5)
will result.
(2-4)
(
(2-5)
)
If the stationary vectors are introduced into equation (2-5) it can be observed that nine voltage levels are
created. Furthermore, as the DC link voltage for this project was chosen to be 600 V, those nine levels are
.
[9]
Chapter 2 – NPC Converter
To produce AC voltage waveforms with multiple levels, the diode – clamped multilevel inverter employs
clamping diodes and cascade DC capacitors. In high power, the configuration used most often is three level
neutral point clamped inverter. The most important characteristic of the NPC inverter, in comparison with
two level inverters is that in AC output voltage dv/dt and THD is reduced [19].
Figure 2-3 presents the layout of a three level NPC inverter. Each inverter leg is composed of four switches
with anti-parallel diodes. In real life these diodes are comprised inside the switching device module, if they
are IGBTs. A zero DC voltage point is present dividing the DC link in two, which ensures the switching of each
phase output to one of three level voltages. The most important benefit of this configuration is that every
switching device needs to block only one half of the DC link voltage, but the main problem emphasis that DC
link created by the two series capacitors needs to be balanced. A steady-state unbalance at the neutral point
can appear due to non-idealities, nonlinearities and transients. For this problem there are two solutions
presented [20]:
 Connect each capacitor to its own isolated DC source
 Balance of the midpoint by feedback control
Figure 2-3 – Neutral Point Clamped Inverter Topology
The clamping diodes
,
,
,
,
,
are connected to neutral point. When the switches
and
are switched on, the inverter output terminal A is connected to the neutral point through one of the
clamping diodes
and
. For a better analysis, one inverter leg is presented in Figure 2-4, representing
the inverter states: P, N, 0.
In the switching state P (Figure 2-4a) the upper two switching devices are on and the resulting inverter leg
voltage is
leg voltage is
, while in N switching state (Figure 2-4c) the lower two switching devices are on and inverter
. When the inner two switches
switching state 0 (Figure 2-4b). The switches
–
and
and
[10]
are on the inverter leg voltage is 0, hence the
–
operate in a complementary mode [21].
Chapter 2 – NPC Converter
a) P state
b) 0 State
c) N State
Figure 2-4 – Switching Paths for NPC Inverter
Considering that the load current
is constant during commutation due to inductive load, the DC link
capacitors are large enough and that all the switching devices are ideal, the commutation can be analysed
[19]:
 Commutation when
In switching state 0, switches
and
are off and voltage across each one is
. The devices
and
are
on and the voltage across them is 0. Furthermore, the clamping diode
is turned on by phase A current, .
During dead time , is turned off and load current path remains the same. When is completely off, the
voltage across
and
becomes
.
In switching state P, the first transistor
is commutated from
to
. Since
is on and the clamping diode
and
is turned off. The load current
were off, the voltage across each one is
[11]
.
Chapter 2 – NPC Converter

Commutation when
In switching state 0, the transistors
current,
. The voltage across
and
and
are on and the clamping diode
is
is turned on by the phase A
. Furthermore, during dead time interval ,
is turned off.
Diodes
and
are turned on and the voltage across
and
is 0 because cannot change direction
instantly. The phase A current, , is then commutated from
to the diodes. While
is turned off, the
voltage across
from 0 to
will have a maximum of
while voltage across
is
due to the diode
. Hence, the voltage across
increases
.
In switching state P, the first two transistors,
and , are turned on and not affect the operation of the
circuit. Even if and are on, they do not carry load current due to
and
conduction. The conclusion
is that all switching devices sustain half of the DC link voltage during switching P-0, 0-P, N-0, 0-N. Switching
P-N is denied because it involves all four switches commutated and the switching losses will be doubled.
Table 2-2 describes the switching states of the NPC inverter leg presented in Figure 2-4. The positive state
denotes that the two upper switches are on and the voltage across the output terminal is
. This voltage
is determined with respect to the neutral point 0. The negative state denotes that the two lower switches
are turned on with respect to neutral point 0 and the output voltage is
.
Table 2-2 – NPC Switching States
T1
T2
T3
T4
State P
1
1
0
0
State N
0
0
1
1
State 0
0
1
1
0
Output phase
Voltage
0
Some of the most important advantages of diode-clamped multilevel VSI can be summarised as [17]:



If the inverter level increases, the size and weight of harmonic filter decreases and thus, the need for
harmonic filter decreases
High efficiency
Simple control for a back-to-back system
Electrostatic couplings between the rotor and stator windings produce shaft voltages and voltages between
the rotor and the motor frame. These voltages will generate flashovers when the voltage exceeds the
dielectric strength of the grease in the bearing [22].
One of the most important problems in the control of multilevel converters is the determination of switching
angle so that the converter produces the required fundamental voltage and does not generate lower order
dominant harmonics.
The main problems in the NPC can be summarised as [23]:
[12]
Chapter 2 – NPC Converter



Increased switching frequency in the converters can generate EMI.
The common mode voltage is generated between the neutral point of the load and the NP of the
inverter by means of PWM in the three phase inverter.
Due to parasitic capacitances in the machine structure, the CMV creates problems such as shaft
voltage and bearing currents.
In multilevel inverters CMV can be reduced or eliminated. These types of inverters have a high number of
switching states; therefore the output voltage is stepped in small increments. The switching losses are
reduced by the mitigation of the harmonics at low frequencies, thus the leakage current is reduced by a
lower dv/dt [2]. A feasible solution is to eliminate the CMV by PWM techniques
2.2.
Classical Modulation Strategies
2.2.1. Background
In the early stages of Voltage Source Inverters (VSI), the operation mode was square wave. Using this type of
operation mode the inverter phase and phase – to – phase output voltage has a square wave shape. An
important drawback of this operation mode is that the output voltage of the inverter has low order
harmonics, such as 5th and 7th, with large magnitude. Regardless of this drawback this operation mode was
preferred due to low number of switchings, as the switching devices used in the first inverters had long turn
– on and turn – off time, thus the switching losses were high. Utilization of these switches made the
switching at high frequency impossible, therefore the square wave operation was preferred [1].
Due to increasing development in the semiconductor technology faster switching devices have been
developed. In VSI the most used power semiconductors are the IGBTs. These devices have low turn – on and
turn – off times, thus reducing switching losses and making switching at high frequency possible. Nowadays,
the PWM methods are preferred in three – phase motors due to superior characteristics. In this operation
mode low current harmonics are not present, only at inverter switching frequency, and further on current
damped by the motor windings [1].
In the carrier based PWM method, the power switches are turned on and off according to a carrier period in
an appropriate manner in order to generate switch pulse patterns. There are three categories of modulation
and control strategies for three level inverters [5]:



Carrier based PWM – is a method based on the comparison of a fundamental sinusoidal waveform
with two carrier signals
Space Vector Modulation (SVM) – is defined by the switching states of the commutation devices
Selective Harmonic Elimination (SHE) – in this method the commutation devices operate at a very
low frequency in order to reduce the losses. The strategy is to control the fundamental frequency
and to eliminate the harmonics five and seven.
[13]
Chapter 2 – NPC Converter
Recently, more and more modulation strategies are implemented into Digital Signal Processors (DSP). PWM
signals have to be calculated in real time, thus significant time is required for computation. When using SVM,
the process for calculation is simplified. Therefore the computation time is reduced and better performance
can be achieved.
It is known [24] that for each carrier-based there is an equivalent SVM and vice-versa. In [24] [25] [26] is
concluded that by common-mode injections, an equivalent SVM of carrier-based modulation can be
obtained. By selection of proper dwell times for the redundant states, the SVM can provide an equivalent for
the carrier-based modulation. The authors choose for this project the Space Vector Modulation.
The SVM determines each switching state of the inverter in the complex
space. The phasor rotating at
the fundamental frequency is sampled and the three inverter switching states (nearest) are selected with
the duty cycles calculated so that the same volt-second average is obtained as in the sampled reference
frame. There is a vast research based on modulation strategies as SVM, which became a standard in the
industry for the power converters. Park and Kron were the first ones to represent three phase systems in
vectorial form [27]. Active and zero space vectors represent active and zero switching states. A typical space
vector diagram is formed in the SVM hexagon with six equal sectors. Each sector can be divided into four
equilateral triangles. This can be seen in Figure 2-5. The centre of the hexagon is represented by the zero
vector ⃗⃗⃗ [19].
Figure 2-5 – Space Vector Diagram - Sectors and Regions [19]
A three phase system defined by
equation (2-6):
⃗⃗⃗⃗
[
can be represented by a rotating vector ⃗⃗⃗⃗⃗ from
and
(2-6)
]
(2-7)
The vectorial form can be obtained after Clarke transformation represented in equations (2-8) and (2-9):
[14]
Chapter 2 – NPC Converter
[
]
[
]
(2-8)
√
(2-9)
√
[
]
The coefficient
is used so that the magnitude of the two phase voltages after transformation will have the
same magnitude as the three phase voltages [19]. Inverse transformation can be obtained as in equation
(2-10):
[
]
and
[
]
(2-10)
form a orthogonal two phase system. Furthermore, ⃗⃗⃗⃗ can be written as in equation (2-11):
⃗⃗⃗⃗
(2-11)
Now there is a correspondence between the three phase system and the space vector in the three phase
plane, hence some advantages appear:


The three phase system can be analysed as a whole.
Properties of a vectorial system can be used. When rotating with
The voltage space vector in the complex
phasor is expressed like in equation (2-13).
the analysis can be made in DC
can be written as in equation (2-12). Furthermore, the voltage
⃗⃗⃗⃗⃗⃗⃗⃗
(2-12)
⃗⃗⃗⃗⃗⃗⃗⃗
√
(
√
)
(2-13)
The exponential form can be written as in equation (2-14).
⃗⃗⃗⃗⃗⃗⃗⃗
(2-14)
From equation (2-14) the size for each type of vector can be calculated, equations (2-15) – (2-18).

⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
Zero vector:
⃗⃗⃗⃗⃗⃗⃗⃗
[
]
(2-15)
[15]
Chapter 2 – NPC Converter

⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗

Small vector:
⃗⃗⃗⃗⃗⃗⃗⃗⃗
[
]
Medium vector:
⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗⃗⃗⃗

Large vector:
⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
(2-16)
⃗⃗⃗⃗⃗⃗⃗⃗⃗
[
[
√
]
]
(2-17)
(2-18)
Space vector modulation is performed in real time and is used to determine the correct duty cycles for the
corresponding switching sequences [18].
There is a total number of 24 active vectors which can be split in three categories: large, medium and small
vectors. There are 6 large vectors, 6 medium vectors, 12 small vectors and 3 additional zero vectors. The
midpoint charge is related to the switching vectors [28]. Figure 2-6 presents the vectors and their switching
states.
Figure 2-6 – NPC Vectors and Switching States [28]
Active and zero vectors are called stationary vectors due to the fact that they do not move in space. The
reference vector ⃗⃗⃗⃗⃗⃗⃗⃗ rotates with the angular speed
which is proportional with the fundamental
frequency of the inverter, equation (2-19):
[16]
Chapter 2 – NPC Converter
(2-19)
In
plane the angle between
and
axis is, equation (2-20):
∫
(2-20)
The twelve small vectors can be split in six sets of two types: N and P. The six sets have same direction and
magnitude according to switching combination and will connected to one of the output lines through the
upper or lower capacitor. Each set of vectors draw current in the opposite directions from the neutral point.
By correct selection of small vectors for the reference vector, the balance can be set.
The medium vectors have one definition per current direction. One of the three output lines is permanently
connected to the midpoint. When the reference vector is synthetized with the medium vector the line
current flows through the midpoint. If the charge cannot be compensated with small vectors, the
compensation is given to the next medium vector because it could have opposite current direction [28].
Further, the large vectors does not have direct connection to the neutral point, hence they do not influence
it.
Table 2-3 – Space Vectors and Switching States
Vector Magnitude
Vector Type
Space Vector
Small Vector
√
Medium Vector
Large Vector
0
Zero Vector
Switching State
P Type
N Type
P00
0NN
PP0
00N
0P0
N0N
0PP
N00
00P
NN0
P0P
0N0
P0N
0PN
NP0
N0P
0NP
PN0
PNN
PPN
NPN
NPP
NNP
PNP
000
PPP
NNN
A switching state, for example 0NP means that the inverter leg A is connected to the neutral point (0), leg B
is connected to negative side (- or N) and the third leg C is connected to the positive side (+ or P).
[17]
Chapter 2 – NPC Converter
These methods are based on load currents and the midpoint balance is kept to zero with a small variance,
depending on the size of the capacitors. The efficiency of these methods is limited. This problem appears
because the midpoint is used as power source. The midpoint problem increases with the level of the
converter. The voltage vectors and the switching states are summarized in the Table 2-3:
The reference vector is built based on three stationary vectors. Each of the stationary vectors is applied for a
specific time, the dwell time. The dwell time is defined as the duty cycle time of the switches during the
modulation sampling period. The volt per second balancing principle is used in order to calculate the dwell
times [19]. The principle is shown in equation (2-21):
∫ ⃗⃗⃗⃗⃗⃗⃗⃗
∫ ⃗⃗⃗
∫ ⃗⃗⃗
∫ ⃗⃗⃗
(2-21)
(2-22)
Where:

is the sampling period
⃗⃗⃗ , ⃗⃗⃗ and ⃗⃗⃗ are the nearest three vectors from arbitrary sector and region


,
and
are the dwell times for the three chosen vectors.
The volt – second balancing principle states that the product of the reference vector with the sampling
period equals the sum of the products between the stationary vectors and their corresponding dwell times.
This is shown in equation (2-23):
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
(2-23)
Voltage space vectors can also be expressed as:
⃗
(2-24)
Where:


is the angle displacement
k a constant dependent on the vector type
The fundamental output voltage of the inverter is controlled by amplitude modulation index
defined as in equation (2-25):
√
which is
(2-25)
The maximum magnitude of
is the radius of the largest circle that can be inscribed in the SVM hexagon.
Medium vectors have the same length as the maximum
.
√
√
(2-26)
[18]
Chapter 2 – NPC Converter
Based on equations (2-25) and (2-26), the maximum modulation index can be calculated:
√
(2-27)
The range of modulation index in SVM is in interval [0, 1] if over-modulation is not considered. The
maximum phase-to-phase voltage obtained by means of SVM is calculated in equation (2-28):
√ (
Where:
√
√
)
(2-28)
is the maximum RMS value of the fundamental phase voltage.
2.2.2. Nearest Three Vectors with Even Harmonic Elimination
The Nearest Three Vectors with Even Harmonic Elimination (NTV-EHE) method was introduced by D. W. Feng
and B. Wu in 2004 [29] for compliance with harmonic standards, like IEEE 519-1992, when the converter is
used in rectifier mode. The generation of even order harmonics is due to fact that the waveform generated
by SVM is not half – wave symmetrical [29]. Alternative switching sequences: one starting with N – type
vector and the other with P – type vector needs to be used in order to obtain half – wave symmetrical
voltage at the output.
The reference vector is synthetized by three stationary space vectors. The stationary vectors are chosen as
the nearest three vectors from the region in which the reference vector is found. An example is considered
where the reference vector falls in sector I, region 4, as seen in Figure 2-7. The reference vector will be
synthetized by ⃗⃗⃗ , ⃗⃗⃗ and ⃗⃗⃗⃗⃗⃗ .
Figure 2-7 – NTV – Stationary and Reference Vectors with Corresponding Dwell Times for Sector I, Region 4
Using volt – second principle and assuming that during
(2-29) can be written.
[19]
the reference vector
is constant equation
Chapter 2 – NPC Converter
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
(2-29)
The stationary vectors can be summarized as in equation (2-30).
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
√
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
(2-30)
The dwell times can be calculated by introducing equation (2-30) in (2-29). The result can be seen in
equation (2-31).
√
(2-31)
Equation (2-32) is obtained by transformation of equation (2-31) in polar coordinates.
(
√
)
(
)
(2-32)
(
)
In order to calculate the dwell times, equation (2-32) is divided into real and imaginary part. Together with
the switching period, the equation system (2-33) is obtained:
√
√
√
(2-33)
{
By solving equation system (2-33) the dwell times will result as in equation (2-34):
( √
( √
{
(
)
(
√
))
(
(2-34)
))
Observing equation (2-34) it can be noticed that √
is the modulation index,
calculations the dwell times for the first sector are obtained in Table 2-4 [19]:
[20]
. Using the above
Chapter 2 – NPC Converter
Table 2-4 – Dwell Times for Reference Voltage in Sector I [19]
Region
1
⃗⃗⃗
2
⃗⃗⃗
3
⃗⃗⃗
4
⃗⃗⃗⃗⃗
(
(
(
))
(
))
⃗⃗⃗
(
⃗⃗⃗
(
(
(
))
⃗⃗⃗
)
⃗⃗⃗
(
⃗⃗⃗⃗⃗
(
⃗⃗⃗
(
)
⃗⃗⃗
⃗⃗⃗
(
(
))
(
(
))
)
(
)
))
The dwell times for each sector can be determined based on Table 2-4 by modifying the angular
displacement . When calculating the dwell times for other sectors, the angle has to be adjusted so that it
falls in the interval [
]. This can be done by extracting a multiple of
⁄ from the actual angle and it is
presented in equation (2-35):
(2-35)
Where:

is the angle reduced to sector I

is the actual angle
 n is the sector number
The overall requirements for switching sequence design of a three level inverter are [19]:
 In one inverter leg, when moving from one switching state to another, only two switches can be
used in complementary mode
 When moving from one sector to another there should be a minimum number of switchings
 Neutral point voltage deviation should be minimum
The dwell time between two opposite small vectors can be equally distributed in order to minimise the
neutral point voltage deviation. There are two cases that need to be investigated regarding the position of
the reference vector inside a sector:
 One small vector in the nearest three vectors – case 1
 Two small vectors in the nearest three vectors – case 2
Case 1 - the reference vector in sector I can be in region 3 or 4, as shown in Figure 2-8:
[21]
Chapter 2 – NPC Converter
Figure 2-8 – Feasible Regions for Case 1
In order to minimize the NP voltage deviation, the dwell time for the small vector should be equally
distributed between P and N type states [19]. A typical seven segment switching sequence is shown in Figure
2-9. From the switching sequence the following conclusions can be drawn:
 The sampling period equals the sum of all dwell times
 Only two switches are used in complementary mode
 Dwell time
for ⃗⃗⃗ is equally distributed between P and N type states, thus minimizing the NP

voltage influence
The device switching frequency is half of the sampling frequency due to the fact that in each inverter
leg there are only two switchings on each sampling period.
Figure 2-9 – Seven Segment Switching Sequence for ⃗⃗⃗⃗⃗⃗⃗⃗ in Sector I, Region 4 [19]
Case 2 – the reference vector in sector I can be in region 1 or 2. The region in which the reference vector is
found is split in two sub-regions. Depending on which sub-region the reference vector is found, it will be
[22]
Chapter 2 – NPC Converter
closer to one of the two small vectors. This will be the dominant small vector as it has the highest effect in
the NP voltage. The dominant vectors dwell time is distributed equally between its N and P type states. An
example can be seen in Figure 2-10:
Figure 2-10 – Division of Region 2 in Sector I for Minimization of NP Voltage Deviation
Based on Figure 2-10 observations can be made:


Transition between the two sub-regions implies an extra switching
The average switching frequency is increased because of six extra switches in each fundamental
switching period. The extra switching requires only two devices
The seven switching sequence for region 2a and 2b are shown in Figure 2-11:
⃗⃗⃗⃗⃗⃗⃗⃗ in Region 2a
⃗⃗⃗⃗⃗⃗⃗⃗ in Region 2b
Figure 2-11 – Seven Segment Switching Sequences for ⃗⃗⃗⃗⃗⃗⃗⃗ in Sector 1, Region 2a and 2b
[23]
Chapter 2 – NPC Converter
Most standards, such as IEEE 519-1992, are very restrictive regarding THD in even harmonics. The NTV
switching sequences can be altered in order to cancel phase-to-phase even harmonics from the voltage
waveform.
Switching sequences can be split in two categories:
 Type A – the sequence starts with N type small vector
 Type B – the sequence starts with P type small vector
In classical SVM, only A type sequences are used. In order to force the phase-to-phase even harmonics to
cancel, A and B types of switching sequences have to be alternated as shown in Figure 2-12.
Figure 2-12 – Alternation of A and B Switching Sequences for Even Harmonic Elimination [29]
The requirement for even harmonic elimination is that the phase-to-phase voltage waveform is half wave
symmetrical. Consider that the reference voltage vector is situated in sector I, region 4, as in Figure 2-9. The
opposite half wave is reached when the reference vectors is situated in sector IV, region 4, as seen in Figure
2-13a.
a) Default A Type Switching Sequence
b) Modified B Type Switching Sequence
Figure 2-13 – Switching Sequence when ⃗⃗⃗⃗⃗⃗⃗⃗ is situated in Sector IV, Region 4.
[24]
Chapter 2 – NPC Converter
In order to gain symmetry, the switching sequence in sector IV, region 4 has to start with a P type small
vector. The modified sequence can be seen in Figure 2-13b. The phase voltages appear to be different in
Figure 2-13, the only difference is an offset of
between the a) and b) variants of the switching sequence.
It can be observed that
from Figure 2-13a equals
from Figure 2-13b, as the
sequences are 180 degree apart. A minor increase in the switching frequency can be observed compared
with conventional NTV method [19]. The increase is due to extra switching required to alternate between A
and B type sequences.
In order to validate the theory presented here and to develop new modulation strategies a base model was
built using Matlab/Simulink R2011b and Plecs. The inverter model was divided into two main parts: the
electronic part, consisting in switching devices, and the control one. In order to facilitate the DSP
implementation, the modulation strategy was developed in Matlab code. The switching devices were
modelled using Plecs toolbox. The general structure is presented in Figure 2-14. For a better control of the
modulation strategy few input parameters have been chosen:

Reference voltage,




Simulation time
Output frequency, f
Switching time,
Deadtime, dt
The outputs of the Control block are the gate signals. These signals are fed to the Inverter block through the
dead time generator, together with the DC link voltage.
Figure 2-14 – General Structure of NPC Converter Developed in Matlab/Simulink and Plecs
In order to analyse the modulation strategy the following parameters were saved:





DC link voltage
DC link current
CMV
Inverter leg voltages (
Inverter phase voltages (
)
)
[25]
Chapter 2 – NPC Converter


Inverter phase – to – phase voltages (
Inverter currents (
)
)
The main conditions in which the simulations were performed are:






DC link voltage of 600 V
Switching frequency of 4 kHz
Fundamental frequency of 50 Hz
Dead time of 2 µs
Six DC link capacitors with the configuration presented in chapter 4.2
Load of 7.5 kW modelled as in chapter 4.2
The general structure for the developed modulation strategies is presented in Figure 2-15. First the input
parameters have to be set, followed by the definition of the stationary vectors and switching table. Next a
decision has to be done regarding neutral point balancing. If the method has the ability to balance the
neutral point, and it is needed, the switching sequence for balancing is chosen otherwise the default one. If
the method does not have NP balancing and it is needed a fault will be triggered, otherwise the default is
selected. After choosing the output switching sequence the dwell times are calculated and the PWM signals
are generated.
Figure 2-15 - Modulation Strategy Structure for Simulation Model
In order to validate the proposed simulation model, the results of NTV-EHE implementation are analysed.
Simulations at maximum modulation index were performed. Figure 2-16 presents the output currents in
steady state. The RMS value of current on a phase is 12.11 A.
[26]
Chapter 2 – NPC Converter
Figure 2-16 – Output Current for NTV-EHE at
– Simulation
The leg voltage is defined as the voltage drop between one leg and the neutral point of the inverter, Figure
2-17. This voltage can have only three levels:
, due to the direct connection to the positive,
negative or midpoint of the DC link. Hence, the limits for the leg voltage are +300 V, -300 V and 0 V.
Figure 2-17 – Leg Voltage for NTV-EHE at
– Simulation
Figure 2-18 presents two fundamental periods of phase voltage, phase-to phase voltage, CMV and DC link
voltages. The first waveform from Figure 2-18 presents the phase voltage, defined as the voltage drop
between one inverter leg and neutral point of the load with wye connection,
. As can be seen this voltage
is quasi-sinusoidal and has nine voltage levels
. The second waveform from
Figure 2-18 represents the phase-to-phase voltage, which has five voltage levels
. The total
harmonic distortion in this voltage is
. Furthermore, the CMV for this method is presented in the
third waveform from Figure 2-18 and it is defined as the voltage drop between the neutral point of the wye
connected load and the neutral point of the DC link. As can be seen there are three voltage
levels
with a fundamental period of 150 Hz. An analysis of this voltage will be performed in
subchapter 5.9.
When referring to DC link voltage there has to be mentioned that this method has the ability of natural
balancing. The voltage on the upper capacitor fluctuates between approximately 294 V and 308 V as for the
lower capacitor the voltage is between 291 V and 306V at maximum modulation index.
[27]
Chapter 2 – NPC Converter
Figure 2-18 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for NTV-EHE at
Simulation
-
The active switching frequency per device is different than the sampling frequency. If
is the number of
devices which perform a commutation,
is the total number of switches, is the sampling frequency,
is the fundamental frequency and
is the number of on/off and off/on switchings. The average
active device switching frequency for NTV can be calculated as:
(2-36)
Only six of the twelve transistors switch on and off per sampling frequency. Ignoring extra switching, for a 4
kHz sampling frequency there would result a 2 kHz active device frequency, due to the fact that when
passing from region 1a to 1b or 2a to 2b, there is an extra switching, the 2 kHz is slightly increased. Per each
fundamental period, there are six extra switchings which involve four devices out of twelve. The switching
involves only on/off or off/on transition, hence the number of switches is divided by 2. The resulting
frequency of 2.025 kHz is the average active switching frequency per IGBT.
[28]
Chapter 2 – NPC Converter
2.2.3. Zero Common Mode Method
The Zero Common Mode Method (ZCM) was first introduced by Haoran Zhang and Annette von Jouanne in
2000 [30]. This method uses the six active middle vectors and one zero vector due to their ability to create
zero common mode voltage as long as the DC link is balanced. These vectors can be seen in Figure 2-19.
Figure 2-19 Switching Vectors for Zero Common Mode Method
As can be seen in Figure 2-19 the sectors need to be redefined compared with NTV-EHE, therefore the first
sector is between ⃗⃗⃗ and ⃗⃗⃗⃗⃗⃗ . Based on this rearrangement and together with volt-second principle the dwell
times for the first sector can be calculated, (2-37):
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
(2-37)
Where:

– dwell time for vector ⃗⃗⃗⃗⃗⃗
– dwell time for vector ⃗⃗⃗

– dwell time for vector ⃗⃗⃗

The stationary vectors for this method can be summarised as in equation (2-38)
⃗⃗⃗⃗⃗⃗
√
⃗⃗⃗
√
(2-38)
⃗⃗⃗
Introducing equation (2-38) in (2-37) it will result into equation (2-39).
√
√
(2-39)
Dividing equation (2-39) into real and imaginary part and transforming it into polar coordinates the system
of equations (2-40) will be obtained:
[29]
Chapter 2 – NPC Converter
√
√
(2-40)
{
By solving (2-40) the dwell times are obtained as in (2-41):
(
)
(2-41)
{
If the angular displacement is modified in such a manner that falls into the first sector the dwell times are
valid for the other sectors. By the use of zero and medium vectors the modulation index will be decreased
[29]. The maximum amplitude for the reference voltage is described in equation (2-42):
√
√
(2-42)
The maximum modulation index for this method is presented in (2-43):
√
√
√
(2-43)
Due to the fact that in this method there are no redundant states and the transition between two adjacent
states involves two inverter legs, the harmonic content is increases [31]. This method does not follow the
rule regarding the transition between two switching states. Figure 2-20 presents the switching sequences for
the first sector in the ZCM method.
Figure 2-20 – Switching Sequence for the First Sector in ZCM Method
[30]
Chapter 2 – NPC Converter
In order to test this modulation strategy, simulations were performed. The simulation structure presented in
Chapter 2.2.2 was used. Simulations at its maximum modulation index,
, were done.
Figure 2-21 presents two fundamental periods from phase voltage, phase-to phase voltage, CMV and DC link
voltages in steady state. The first waveform describes the phase voltage,
. As can be seen this voltage is
very similar with the output of a two level voltage source inverter, due to the fact that this strategy does not
use all the vectors. Hence, the phase voltage levels are
. The second waveform from Figure 2-21 is
the phase-to-phase voltage, which has five voltage levels
as NTV-EHE. The total harmonic
distortion in this voltage is
. Furthermore, the CMV for this method is presented in the third
waveform. As it can be seen CMV has three voltage levels
(when deadtime is introduced) with a
fundamental period of 150 Hz. As at NTV-EHE, a more specific analysis will be performed in subchapter 5.9.
By the use only of medium and zero vectors this method has the ability to self-balance. In steady state the
voltage on the upper capacitor varies between approximately 296 V and 309 V as for the lower capacitor the
voltage is between 292 V and 304V, at maximum modulation,
.
Figure 2-21 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZCM at
Simulation
-
As described at NTV-EHE the active switching frequency per device can be calculated. For this method this
frequency is 2 kHz, due to the fact that there are no extra switchings.
[31]
Chapter 2 – NPC Converter
2.3.
DC Link Balancing
The voltage deviation problem is inherent to all three level NPC converters [32]. Neutral point voltage
deviation implies that any current flowing through the NP of a three level inverter would cause the charging
of one of the capacitors and the discharging of the other. The effect is that the output voltage becomes
asymmetric. The unbalance problem does not appear in two level inverters or in three level inverters with
separate DC sources [18].
From the total of 27 vector combination, 18 produce neutral point voltage deviation [32]. The zero and the
large vectors have no influence on the neutral point. Aside from this, the voltage deviation can have more
causes [18]:




The capacitors have different parameters
DC link capacitor failure
Switching devices have different parameters
Non-linear and unbalanced loads
By not taking care of the DC link voltage deviation the following problems can occur [18]:

Premature failure of the switching devices because the voltage increases above



THD increase due to asymmetric supply
The terminal with lower voltage will limit the modulation ratio
The inverter will become unable of synthetizing the output voltage in case of a major DC link voltage
deviation
The effect of some switching states determines the AC currents to flow in and out the NP. These currents will
generate a ripple in the NP voltage and low order harmonics. Without caring about the NP balancing, the DC
link capacitors and the switching devices are prone to destruction [32].
The DC current ripple is important for the size determination of the DC link capacitors as they suppress the
PWM current ripple. For the analysis of the DC link current ripple performance,
factor is defined which
is the squared ratio of DC link ripple RMS over the output phase current RMS [1]. This can be seen on
equations (2-44) and (2-45):
(
(2-44)
)
(2-45)
For a longer capacitor life and smaller size requirements, the
variable has to be small. When the ASD
runs at full load at rated current, the
will be small. At no load and small currents the DC link current
ripple,
, will have higher values. The influence of each type of vector can be seen in Figure 2-22.
[32]
Chapter 2 – NPC Converter
a) Zero Vector
b) Medium Vector
c) P Type Small Vector
d) N Type Small Vector
e) Large Vector
Figure 2-22 – Space Vectors Influence on the NP Current
[33]
Chapter 2 – NPC Converter
When the inverter uses the zero vector with 000 configuration, all three inverter legs are connected to the
midpoint of the DC link, Figure 2-22a, thus the switching states do not affect . Figure 2-22b describes how
the medium vector influences the neutral point. For a better understanding one medium vector was chosen,
. As can be seen in Figure 2-22b each of the inverter legs are connected to one of the load terminals: the
positive side of the DC link is connected to the A terminal, the neutral point is connected to B terminal and
negative side of the DC link is connected to C terminal. The voltage across the lower capacitor may increase
or decrease depending on the operating conditions of the inverter [19].
The small vectors have an important influence on the neutral point. The P type vector causes an increase in
the voltage across one capacitor and the N type vector a decrease. This is due to the fact that for P type
vectors, one of the load terminals is connected to the positive DC link, respectively negative DC link for N
type vectors. As an example the small vector was chosen. Its influence can be seen in Figure 2-22c for P
type small vector, and Figure 2-22d for N type small vector [19].
When talking about large vectors it can be noticed that each of the load terminals are connected to the
positive or negative DC link, never at the neutral point. Hence, these types of vectors do not influence the
neutral point. Figure 2-22e presents the
large vector. As it can be seen the A terminal of the load is
connected to the positive DC link and B and C terminals to the negative DC link [19].
2.4.
Common Mode Voltage
2.4.1. Common Mode Voltage in Adjustable Speed Drives
Electric machines are an important part of the industry. Most motors are controlled by variable frequency
drives. These drives generate high frequency noise in current and voltage. This noise can follow the paths
[33]:



To the load
To the supply
Shaft through the motor bearings
When applying PWM to a three phase inverter a voltage is generated between neutral point of the wye
connected load and NP of the inverter. This voltage is known as common mode voltage and acts like a source
for many unwanted problems in motor drives such as shaft voltage and bearing currents due to parasitic
capacitances that exists in the motor structure [23] [34].
The switching operation of the inverter generates common mode voltages. From this point of view the
common mode voltages are defined as being the zero – sequence voltages overlapped with noise generated
by switching. If the magnitude is not reduced the motor phase – to – ground voltage can be substantially
increased, thus leading to premature failure of motor winding insulation. As a result, the life of the motor is
shortened. In medium voltage, motors need to be protected against common mode voltages, if they are not,
[34]
Chapter 2 – NPC Converter
the cost of the damaged motor will increase the cost of production [19]. The CMV path can be seen in Figure
2-23.
Figure 2-23 – Common Mode Voltage Path
The parasitic capacitance between the stator winding and the rotor can be changed by changing the design
parameters while other capacitances cannot be changed that easily. Also, shaft voltage will be higher on an
increased stator slot tooth [6].
The parasitic capacitances between the stator winding, rotor and motor frame is presented in Figure 2-24.
The capacitances are:

– equivalent capacitance between motor windings and motor frame


– capacitance between the stator windings and rotor
– capacitance between rotor and motor frame

– bearing capacitance
Figure 2-24 – Parasitic Capacitances [1]
In Figure 2-24
describes the overall leakage current flowing from the motor frame to ground and
bearing current. In practice the bearing currents are a small part of the overall leakage currents [1].
is the
Three phase inverters have leg voltages
, phase voltages
and phase-to-phase
voltages
. As can be seen from Figure 2-23 the leg voltages can be calculated as in equations
(2-46), (2-47) and (2-48):
[35]
Chapter 2 – NPC Converter
(2-46)
(2-47)
(2-48)
If equations (2-46), (2-47) and (2-48) are summed equation (2-49) is obtained:
(2-49)
As well known, the sum of a three phase voltages into a balanced system is equal to zero, thus the CMV at
the motor terminals can be described as in equation (2-50) and defined as the load star point to the centre
of the DC bus of the VSI [35].
(2-50)
The CMV magnitude depends on the switching sequence. Leakage currents (common mode currents) flow
from motor to ground and from cables to ground due to high dv/dt and magnitude of CMV. The most
important consequences of the Common Mode Current (CMC) are the bearing currents, electromagnetic
interference and inverter unwanted trips [1].
A. Shaft Voltage
On rotating shafts stray voltages occur with magnitudes from micro – volts to hundreds of volts. This voltage
may be produced in two ways: by rotation of the shaft (and produced into the magnetic field of the earth)
and electromagnetic communication signal induction. The stray voltage induced by electromagnetic signal
can be produced by shaft rotation that links to the asymmetrical magnetism of electrical machine, through
the residual magnetism present in the shaft or in adjacent stationary members and by induction from power
electronics devices, exciters or current – carrying brushes [36].
Shaft voltages are produced by CMV through capacitive couplings between rotor and stator windings ( )
and between rotor and frame ( ). The structure of a simplified high frequency model of motor is described
in Figure 2-24. Based on this figure the shaft voltage can be calculated as:
(2-51)
Shaft voltages can help and harm the system. They can warn about problems regarding development at an
early stage, but at the same time they can generate circulating currents, reduce the efficiency of the unit,
and generate flashovers that can damage the bearings, seals, gears and couplings. The potential for damage
can be reduced by controlling the shaft voltages. There are two methods for controlling the shaft voltage:
passive and active. The active method refers to injecting counteracting current signals in the rotor and the
passive method is by simply placing grounding brushes [36].
[36]
Chapter 2 – NPC Converter
B. Shaft Current
According to the generating mechanism there can be multiple types of bearing currents. The inverter –
induced bearing currents classification can be found in Figure 2-25 .
Figure 2-25 – Inverter – Induced Bearing Currents Classification
The common mode voltage can result in capacitive bearings currents, Electric Discharge Machine (EDM) and
leakage currents. High frequency shaft voltage is induced by leakage ground currents originated from high
dv/dt, therefore resulting in a source of high frequency circulating bearing currents. From all types of
currents, the capacitive currents have the smallest magnitude and do not harm the motor. The most
important common mode currents are EDM and High Frequency (HF) circulating bearing currents [1]. This
can be seen in Figure 2-25.
The bearing currents appear when the shaft voltage exceeds the breakdown limit of the insulating grease
thin film [3].
2.4.2. Switching Sequence Influence on CMV
Stationary vectors produce CMV, thus every vector influence in different manners [31]. Based on equations
(2-46), (2-47), (2-48) and (2-50) the influence of every switching state on CMV can be calculated. As an
example the sector I, region 4 from NTV-EHE was chosen. Each of the leg voltages has been drawn, as well as
the resultant CMV for the case in which the DC link is balanced, presented in Figure 2-26.
[37]
Chapter 2 – NPC Converter
Figure 2-26 – NTV-EHE Sector I, Region 4 - Leg Voltages and their Resultant CMV
Furthermore the influence of each space vector on the CMV can be calculated. This can be seen in Table 2-5:
first column represents the switching state, column two the vector type, column three describes the CMV
when the neutral potential is zero and column four when it is different from zero.
Table 2-5 – Influence of Space Vectors on CMV [31]
State
000
Vector Type
Zero
NNN
Zero
PPP
Zero
NOO
Small
ONO
Small
OON
Small
POO
Small
OPO
Small
OOP
Small
NNO
Small
NON
Small
ONN
Small
Common Mode Voltage (
[38]
)
Common Mode Voltage (
)
Chapter 2 – NPC Converter
PPO
Small
POP
Small
OPP
Small
PON
Medium
OPN
Medium
NPO
Medium
NOP
Medium
ONP
Medium
PN0
Medium
NNP
Large
NPN
Large
PNN
Large
PPN
Large
PNP
Large
NPP
Large
2.5.
Method of Measuring EMI and CMV
2.5.1. Method of Measuring EMI
One of the most important problems in electric motor drives is the electromagnetic interference. This
phenomenon produces undesirable effects on electronic devices. The top requirements in markets are
increasing power density and decreasing cost and size of a system. When designing or optimising an electric
machine drive: switching losses, harmonics and electromagnetic interference should be taken into account
[37].
The operation of switching in power electronics, that feed one motor, creates electromagnetic noise in the
drive system. EMI is generated by electromagnetic disturbances and can be classified as noise, impulses and
transients. This noise goes into close circuits by inductive and capacitive couplings. This type of disturbance
can be divided into [38]:
 Conducted EMI
[39]
Chapter 2 – NPC Converter

Radiated EMI
The most problematic frequency range that Electromagnetic Compatibility (EMC) standards address for
conducted disturbances is 0.15 – 30 MHz [39]. There are four methods developed for mitigation of Common
Mode (CM) EMI:
 Passive CM current cancellation [40]
 Active noise cancellation [41]
 CMV source reduction through modified PWM strategies [42]
 Filters [43] [44]
Conducted EMI is defined as undesired electromagnetic energy coming from an emitter or entering into a
receptor through cables or wires. This type of electromagnetic energy causes interference in electronic
system due to the fact that power distribution is represented as a large antenna. In order to measure it the
CISPR 16 standard needs to be taken into account. This international standard specifies the tests for
compliance with conducted emissions limits and utilises the Line Impedance Stabilization Network (LISN), a
passive filter, for measurements. This can be seen in Figure 2-27:
Figure 2-27 Test Setup for EMI Measurement
The current created by noise has two components:


Common mode noise current,
earth wire
Differential mode noise current,
, that flows out from line and neutral and returns through the
, which flows from line and returns through neutral.
The test set-up presented in Figure 2-27 measures the total common and differential mode current in the
line or neutral. These are measured across the 50 Ohm LISN resistor (R2).
This thesis proposes the reduction of the CM EMI by reducing the CMV through improved PWM strategies.
[40]
Chapter 2 – NPC Converter
2.5.2. Method of Measuring CMV
For measuring CMV and CMC the setup from Figure 2-28 can be used. The setup is isolated from the network
through the isolation transformer. The motor is mounted on an insulated plate (wood) for a good galvanic
separation from the ground. The CMV is measured between the neutral point of the motor and the zero
point of the DC link. The CMC must be measured via a high bandwidth current transducer and the CMV via a
high bandwidth voltage probe [1].
Figure 2-28 – Test Setup for Measuring the CMV and CMC
[41]
Chapter 2 – NPC Converter
[42]
Chapter 3 – Improved Modulation Strategies
3. Improved Modulation Strategies
This chapter introduces four improved modulation strategies developed based on the space vector table and
theory presented in chapter 2. Each of this modulation strategies are validated through simulation results.
This chapter ends with a comparative performance evaluation consisting of comparison at maximum
modulation index as well as an analysis of THD in the phase-to-phase voltage throughout entire modulation
index range.
3.1.
One Small One Medium Vector
Analysing Table 2-5 from Chapter 2.4.2 it can be noticed that small vectors have the ability to natural
balance the neutral point by proper switching from N – type to P – type vectors. In order to create this
modulation strategy the space vector diagram is divided in twelve sectors with a 30° angle between small
vectors and medium vectors. The appropriate vectors for this method, regarding sector one and two, are
presented in Figure 3-1.
a) Space Vectors for Creation of Reference
Voltage in the First Sector
b) Space Vectors for Creation of Reference
Voltage in the Second Sector
Figure 3-1 – One Small One Medium Vector Method
Considering the first sector, the reference vector is created from the stationary vectors ⃗⃗⃗ , ⃗⃗⃗⃗⃗ , ⃗⃗⃗⃗⃗ . In order
to calculate the dwell times for this sector the volt – second principle together with the assumption that
during the reference voltage
is constant are used. This can be seen in equation (3-1).
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
(3-1)
The stationary vectors that form the reference voltage as well as the reference vector are summarized in
equation (3-2).
[43]
Chapter 3 – Improved Modulation Strategies
⃗⃗⃗
⃗⃗⃗
√
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
(3-2)
Introducing (3-2) in (3-1) the dwell times can be calculated. The result can be seen in equation (3-3).
√
(3-3)
Equation (3-4) is obtained by transforming equation (3-3) into polar coordinates.
√
(
)
(3-4)
In order to calculate the dwell times, equation (3-4) is divided into real and imaginary part. Equation system
(3-5) is obtained for a switching period:
√
(3-5)
{
Solving equation (3-5), dwell times will result as in equation (3-6):
(
)
(3-6)
√
{
The dwell times for odd sectors are determined based on equation (3-6) by adjusting the angular
displacement so that it can fall in the interval [
]. For even sectors the dwell times are determined in the
same manner.
In order to cancel the phase-to-phase even harmonics from the voltage waveform the switching sequences
are divided in:
 Odd sector – the sequence is predominant by P type small vector
 Even sector – the sequence is predominant by N type small vector
The requirement for even harmonic elimination is that the phase-to-phase voltage waveform is half wave
symmetrical. By alternating the N and P type small vectors these harmonics are forced to cancel. This can be
seen in Figure 3-2.
[44]
Chapter 3 – Improved Modulation Strategies
⃗⃗⃗⃗⃗⃗⃗⃗ in Region 1
⃗⃗⃗⃗⃗⃗⃗⃗ in Region 7
Figure 3-2 – Five Segment Switching Sequences for ⃗⃗⃗⃗⃗⃗⃗⃗ in Sector I and VII
When referring to modulation index it is needed to be mentioned that, for this method, the magnitude for
the reference vector is limited to the inscribed circle in the hexagon created by the small vectors. The
maximum reference vector is presented in equation (3-7):
√
√
(3-7)
The maximum modulation index is presented in equation (3-8):
√
√
(3-8)
√
It can be mentioned that in comparison with ZCM, this method has the advantages:


Redundant states
Transition between two adjacent states does not involve two inverter legs
In order to test this modulation strategy simulations at its maximum modulation index,
, were
performed. The simulation structure presented in Chapter 2.2.2 was used. Figure 3-3 presents two
fundamental periods of phase voltage, phase-to phase voltage, CMV and DC link voltages in steady state.
The first waveform describes the phase voltage,
. This voltage has five levels
, due to the
fact that only small, medium and zero vectors are used. The second waveform from the same figure
represents the phase-to-phase voltage, which has five voltage levels
as the classical
methods. The total harmonic distortion in this voltage is
. Furthermore, the CMV is presented in
[45]
Chapter 3 – Improved Modulation Strategies
the third waveform. As it can be seen CMV has three voltage levels
, with a fundamental period of
150 Hz. As the classical modulation strategies a more specific analysis will be performed in Chapter 5.8.
By the use of small, medium and zero vectors this method has the ability to self-balance, through a proper
switching between P and N type small vectors. The DC link voltage is presented in last waveform from Figure
3-3. In steady state the voltage on the upper capacitor varies between approximately 299 V and 304 V as for
the lower capacitor the voltage is between 296 V and 301 V at maximum modulation,
.
Figure 3-3 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OSOM at
Simulation
-
As described at NTV-EHE the active switching frequency can be calculated and results as 1.33 kHz, due to the
fact that only four transistors from a total of twelve perform a full commutation on each sampling period.
[46]
Chapter 3 – Improved Modulation Strategies
3.2.
One Large One Medium Vector
In order to increase the modulation index and to better use the bus bar, one large and one medium vectors
are used to define the reference vector. The space vector diagram is divided into twelve sectors with 30°
angle between medium and large vectors as shown in Figure 3-4.
a) Space Vectors for Creation of Reference
Voltage in the First Sector
b) Space Vectors for Creation of Reference
Voltage in the Second Sector
Figure 3-4 – One Large One Medium Vector Method
In order to calculate the dwell times, for this method, the first sector is taken into account. The reference
vector is created by ⃗⃗⃗ , ⃗⃗⃗⃗⃗⃗⃗ , ⃗⃗⃗⃗⃗ . Using volt – second principle together with the assumption that during
the reference voltage is constant, equation (3-9) is obtained.
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
(3-9)
The stationary vectors that form the reference voltage are summarized in equation (3-10).
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
√
⃗⃗⃗
(3-10)
The dwell times can be calculated by introducing (3-10) in (3-9). The result can be seen in equation (3-11).
√
(3-11)
By transforming equation (3-11) into polar coordinates equation (3-12) is obtained.
√
(
)
(3-12)
Equation (3-12) is divided into real and imaginary part, thus obtaining the system of equations (3-13) for a
switching period:
[47]
Chapter 3 – Improved Modulation Strategies
√
(3-13)
{
Solving equation (3-13) the dwell times will result as in equation (3-14):
(
)
(3-14)
√
{
The dwell times for all odd sectors are determined based on equation (3-14) by adjusting the angular
displacement in such a manner that it can fall in the interval [
]. Furthermore, for even sectors the dwell
times are determined in the same manner.
For a better understanding of the proposed modulation strategy the switching sequence for sector I is
presented in Figure 3-5.
Figure 3-5 – Five Segment Switching Sequences for ⃗⃗⃗⃗⃗⃗⃗⃗ in Sector I
The modulation index for this method is determined by the inscribed circle in the hexagon created by large
vectors. The maximum reference vector is presented in equation (3-15):
√
√
(3-15)
The maximum modulation index is calculated in (3-16):
[48]
Chapter 3 – Improved Modulation Strategies
√
√
(3-16)
√
In order to test this modulation strategy simulations at maximum modulation index,
, were
performed. The simulation structure presented in subchapter 2.2.2 was used. Figure 3-6 presents two
fundamental periods of phase voltage, phase-to phase voltage, CMV and DC link voltages in steady state.
The first waveform describes the phase voltage,
. This voltage has seven levels
,
due to the fact that only large, medium and zero vectors are used. The second waveform from the same
figure represents the phase-to-phase voltage, which has five voltage levels
as expected. The
total harmonic distortion in this voltage is
. Furthermore, the CMV is presented in the third
waveform. As it can be seen CMV has three voltage levels
, with a fundamental period of 150 Hz. As
the classical modulation strategies a more specific analysis will be performed in subchapter 5.9.
By the use of only of large, medium and zero vectors this method has the ability to self-balance. The DC link
voltage is presented in last waveform from Figure 3-6. In steady state the voltage on the upper capacitor
varies between approximately 294 V and 308 V as for the lower capacitor the voltage is between 292 V and
306 V at maximum modulation index,
.
Figure 3-6 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OLOM at
Simulation
-
As described for the classical modulation strategy NTV-EHE the active switching frequency on each device
can be calculated. For this method the active switching frequency is 2 kHz.
[49]
Chapter 3 – Improved Modulation Strategies
3.3.
Zero Small Medium Large Method
Taken into consideration Table 2-5 and theory presented at NTV, another method can be proposed. The idea
behind this method is to use all four vectors in order to maintain the THD low, while choosing the small
vectors in such a manner that the CMV levels are half compared to NTV. The space vector diagram is divided
into six sectors each of them having two regions. This configuration can be seen in Figure 3-7. First region
lasts between [
] and the second one between [
].
b) Space Vectors for Sector I, Region 2
a) Space Vectors for Sector I, Region 1
Figure 3-7 – Space Vector Diagram for Zero Small Medium Method in Sector I
In order to calculate the dwell times the volt-second principle is used, together with the assumption that
during switching time the reference vector is constant. As an example the reference vector from sector I,
region 1 is presented in equation (3-20) and its stationary vectors in equation (3-18).
⃗⃗⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
√
⃗⃗⃗
(3-17)
⃗⃗⃗
⃗⃗⃗
(3-18)
The dwell times are calculated differently for each half-sector. A factor k1 is inserted in the equations in
order to make possible the division of the dwell times between the four vectors. This factor has been
defined as the ratio between the reference voltage and maximum reference voltage, equation (3-19).
Furthermore, when the amplitude of the reference voltage is maximum only small, medium and large
vectors will form it.
(3-19)
When calculating the dwell times, the displacement angle needs to be taken into account. Hence when the
displacement angle is in region 1 the dwell times have the form presented in equation (3-20) and when is in
region 2 they have the form presented in equation (3-21).
[50]
Chapter 3 – Improved Modulation Strategies
√
√
(3-20)
√
√
{
√
√
(3-21)
√
{
Based on equations (3-20) and (3-21), the dwell times are presented in equation (3-22) :
{
(3-22)
This method is able to balance the DC link, in a case of an external event, by proper use of the small vectors.
When is in balancing mode, the CMV levels are same as NTV. As all the vectors are used, the largest vector
that can be inscribed in the hexagon is the large vector, thus the modulation index is 1, as at the classical
method, NTV-EHE. For a better understanding of this method a typical switching sequence is presented in
Figure 3-8:
Figure 3-8 – Switching Sequence for ZSML in Sector I, Region 1
[51]
Chapter 3 – Improved Modulation Strategies
In order to test this modulation strategy, simulations at maximum modulation index,
, were
performed based on the simulation structure presented in subchapter 2.2.2. Figure 3-9 presents two
fundamental periods of phase voltage, phase-to phase voltage, CMV and DC link voltages in steady state.
The first waveform describes the phase voltage,
. This voltage has a quasi – sinusoidal shape and nine
levels
, because all the stationary vectors are used in order to form the
reference voltage vector. The second waveform from this figure represents the phase-to-phase voltage,
which has five voltage levels
as expected. The total harmonic distortion in the line voltage
is
. Furthermore, the CMV is presented in the third waveform. As it can be seen CMV has three
voltage levels
, with a fundamental period of 150 Hz. As the classical modulation strategies a more
specific analysis will be performed in subchapter 5.9.
By the use of stationary vectors this method has the ability to self-balance and balance the DC link in case of
an external disturbance. The voltage on the DC link capacitors under natural balancing conditions is
presented in last waveform from Figure 3-9. In steady state the voltage on the upper capacitor varies
between approximately 295 V and 309 V as for the lower capacitor the voltage is between 291 V and 305 V
at maximum modulation index,
.
Figure 3-9 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZSML Method at ma=1 Simulation
As presented at NTV-EHE the active switching frequency on each device can be calculated. For this method
this frequency is 2 kHz as only six of the twelve transistors are commutated in each sampling period.
[52]
Chapter 3 – Improved Modulation Strategies
3.4.
Random Sequence of 3 Vectors with Neutral Point Balancing Method
The idea of randomization is not new to inverters modulation, but its purpose and utilization is quite
different from the idea implemented in Random Sequence of 3 Vectors with Neutral Point Balancing (RS3N).
Some methods used are SVM with variable switching frequency others are deterministic [45] because of the
fixed switching frequency. The methods try to maintain the average switching frequency low while reducing
acoustic noise [46]. Lead-lag modulation (RLL) aligns the pulse position with the beginning or the end of the
switching interval. Random displacement of pulse centre (RCD) aligns the centre of pulses from each phase.
Random distribution of zero vector (RZD) is based on the idea that zero vector time is randomly divided
between PPP and 000 state [46]. The RLL, RCD and RZD are fixed frequency random modulation strategies
for two level inverters.
Random pulse width modulation is known to be proposed for reduction of current harmonics, torque ripple
and acoustic noise [45]. Because using a variable switching frequency is microcontroller intensive, the
methods based on fixed switching frequency are preferred.
The proposed method is based on the idea that each switching sequence can have the vector order changed,
having an impact in the CMV due to the reduction of voltage levels at high frequencies. Eliminating the
repetition of the CMV distribution between each switching sequence should have a big impact on the
frequencies which are a multiple of the switching frequency. These assumptions are confirmed in both the
simulation and the experimental results.
The idea behind the RS3N modulation strategy is to improve spectral performance on CMV while reducing it
in the time domain to half of NTV. To obtain this, the switching sequence for each combination of nearest
three vectors is done in a sequence of three vectors. Using a pseudo-random number generator, this
switching sequence is randomized up to 80 times on each period of the output frequency. The maximum
randomization value is obtained as in equation (3-23).
(3-23)
Where:



– is the randomization factor
– is the switching frequency
– is the output frequency
By having the switching sequence randomized, the resultant CMV levels on each sequence will not be
repeated anymore, thus reducing the CMV levels which are multiple of switching frequency, in the frequency
domain. An example of the effect of randomization can be seen in Figure 3-10, the CMV output does not
repeat from one sequence to another.
[53]
Chapter 3 – Improved Modulation Strategies
Figure 3-10 – Randomization Effect on CMV on RS3N Modulation Strategy in Sector I, Region 1
For this method, the space vector diagram is divided in 6 sectors, as the NTV-EHE. The difference between
these two is that there are only four regions in each sector, and the behaviour of the modulation in these
regions is different. As it is well known that some of the small vectors produce less CMV [31], these vectors
are preferred in each region. By choosing these vectors, the CMV levels in the time domain are half of NTV
for any modulation index. The division between sectors and regions can be seen in Figure 3-11. The THD
should follow the behaviour of the NTV-EHE method due to the fact that it relies on the choice of the
nearest three vectors.
Figure 3-11 – Space Vector Diagram of RS3N Modulation Strategy
As this method uses the same principle as NTV, the dwell times will have the same form as well as the
modulation index.
[54]
Chapter 3 – Improved Modulation Strategies
The method is able to balance the DC link voltage, in a case of an external event, by proper use of the P and
N type small vectors. During balancing mode, in case on an external event, the CMV level in time domains
are same to NTV, however there is an improvement in the frequency domain due to switching sequence
randomization.
In order for this method to function adequately, two filters were implemented. The first filter ensures that
there is no N-P or P-N switching between two consecutive sequences and the second one that the
combination P-O-P is avoided, in order to make the DSP implementation possible. These two filters follow
the principle: if one of the two events is detected, another random number is chosen and the switching
sequence is randomized again. If the new combination passes the two filters, is sent to the output. For the
DSP implementation, this method uses asymmetrical up-count mode for the enhanced Pulse Width
Modulator (ePWM) modules.
As the other methods, this one has been tested on the structure presented in subchapter 2.2.2. Figure 3-12
presents two fundamental periods of phase voltage, phase-to phase voltage, CMV and DC link voltages in
steady state. The first waveform describes the phase voltage,
. This voltage has a quasi – sinusoidal shape
and nine levels
, as NTV. The second waveform from this figure represents the
phase-to-phase voltage, which has five voltage levels
as expected. The total harmonic
distortion in the line voltage is
. Furthermore, the CMV is presented in the third waveform. As it
can be seen it has three voltage levels
, with a fundamental period of 150 Hz. As the classical
modulation strategies a more specific analysis will be performed in subchapter 5.9.
Figure 3-12 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for RS3N at
Simulation
[55]
-
Chapter 3 – Improved Modulation Strategies
This method has the ability to self-balance and balance the DC link in case of an external disturbance. The
fourth waveform from Figure 3-12 presents the DC link voltage in natural balancing mode. The voltage on
the DC link capacitors is presented in last waveform from Figure 3-9. In steady state the voltage on the upper
capacitor varies between approximately 295 V and 310 V as for the lower capacitor the voltage is between
290 V and 305 V at maximum modulation index,
.
The active switching frequency on each device is 2 kHz as only six transistors from a total of twelve perform
a full commutation on each sampling period.
3.5.
Performance Evaluation of Improved Modulation Strategies
Based on the theory and simulations results presented in this chapter, a comparative analysis has been
performed between the developed modulation strategies and the classical ones.
Two of the developed modulations, ZSML and RS3N, have nine levels on the phase voltage as NTV-EHE, while
OLOM has seven and OSOM five. Hence, for ZSML and RS3N the output filter requirements are as for NTV,
while at OLOM and OSOM the filter needs to be increased. For a better understanding of the output filter
requirements, in order to reduce the cost of the drive, the current and phase-to-phase voltage THD have
been calculated. OLOM and ZSML have the current THD very similar with NTV, while ZSML present
similarities with ZCM. OSOM has the largest distortion in the phase current and phase-to-phase voltage, but
the modulation index is half of the other ones. ZSML and RS3N have similar harmonic distortion with NTV, at
maximum modulation index, while at OLOM is slightly increased.
For a good utilization of the bus bar the modulation index needs to be taken into account as this is
proportional with the DC link voltage. From this point of view OLOM, ZSML and RS3N have the best
perspective, while OSOM can use only half of it.
In case of an external event that will unbalance the DC link, the modulation strategy needs to be able to
counteract it as to maintain the balance. The RS3N and ZSML have this ability, while the other methods have
only the ability to self-balance. Furthermore, the CMV needs to be analysed. From this point of view all the
developed methods present a better performance in time domain, half of the NTV amplitude.
[56]
Chapter 3 – Improved Modulation Strategies
Table 3-1 – Comparative Analysis between Modulation Strategies
Modulation
Strategy
Output phase to neutral
voltage levels [V]
Modulation
Index
NTV
1
ZCM
0.866
OLOM
1
ZSML
1
OSOM
0.5
RS3N
1
DC link
balancing
CMV Levels
[V]
Phase to
phase
Natural
balancing
Natural
balancing
Natural
balancing
Natural
balancing and
balancing
Natural
balancing
Natural
balancing and
balancing
For a better understanding of how each modulation strategy acts at different reference voltages a chart has
been developed, Figure 3-13. This figure presents the THD on phase-to-phase voltage as a function of
modulation index. From the developed strategies only OLOM, ZSML and RS3N have a proper utilization of
the DC link.
Figure 3-13 – Modulation Index vs. Line Voltage THD of Classic and Developed Modulation Strategies based
on Developed Simulation
As it can be seen from Figure 3-13 RS3N has the THD exactly the same as NTV-EHE. OSOM presents a good
performance in the entire range, less than half of the distance between NTV and ZCM. At maximum
modulation index ZSML and OLOM present similar performance with NTV, but when the modulation index
decreases the similarity is closer to ZCM.
[57]
Chapter 3 – Improved Modulation Strategies
[58]
Chapter 4 – Hardware Design
4. Hardware Design of three-level NPC Inverter
This chapter presents the design of the 7.5 kW NPC inverter that was built featuring newly introduced NPC
leg modules from Semikron, four layer PCB for noise reduction and full protections against over temperature,
overcurrent or out of range voltages on the DC link capacitors. The embedded DSP design together with a
CPLD for deadtime and protection management make the inverter very customisable through software.
Advanced gate drivers with extra protection add to the design performance.
4.1.
System Overview
The three level NPC inverter was modelled based on the simplified hardware schematic from Figure 4-1 and
has the following main features:
 Embedded TMS320F28335 DSP design.
 4 layer Printed Circuit Board (PCB) with stacked DC link layout, ground and power planes.
 Design based on NPC leg IGBT modules.
 Adjustable over temperature, overcurrent and overvoltage protection.
 Xilinx XC9572XL CPLD based dead time and protection management.
 Real time PWM Signal analysis and protection.
 DC Link up to 1kV.
 Shielded Analog to Digital Converter (ADC) and PWM signals.
 RS-232, RS-485 and Controller Area Network (CAN) communication.
 Optocoupler galvanic isolated gate driver with active Miller clamping.
 Desaturation detection.
 JTAG interface for DSP and CPLD.
 Hall effect current sensors.
 Mixed analog and digital design.
 Reduced size.
[59]
Chapter 4 – Hardware Design
Figure 4-1 – Simplified Schematic of Hardware Platform
The developed schematic is based on two stages – control and power – which are electrically isolated from
each other. In the low power, low voltage stage, the DSP supplies the six PWM signals which are a result of
the implemented modulation algorithms. The PWM signals from the DSP are transmitted to the CPLD, which
manages the insertion of deadtime and PWM signal multiplication. The twelve PWM signals outputs of the
CPLD are used by the gate drivers in order to control the three IGBT modules that supply the three phase AC
voltage to the desired load. The power input for the modules is the DC Link, a high voltage DC which is
supplied with an external DC source and the bulk capacitors form the DC link.
As feedback, the three phase currents are acquired via Hall Effect sensors. Each sensor transmits the
analogue signal to the DSP through the ADC. The same signals are used in order to detect an overcurrent
event. The upper “OC” block, manages the phase overcurrent / short-circuit situations. The OC block consists
of three window comparators that generate an active high fault signal which is transmitted to the CPLD
through an AND gate (not shown).
From the DC link, using the same Hall effect sensors, two signals are acquired and used in order to detect a
DC Link overcurrent or shortcircuit. The signals are processed through the lower “OC” block. The CPLD is
interfaced via an AND logic gate.
The DC link voltages, corresponding to the superior and the inferior halves of the DC link, are acquired using
a differential operational amplifier from Linear Technology, LT1366. The signals are fed back to the DSP via
its ADC. The same signals are used in “OV” block in order to detect a DC link overvoltage or voltage out of
range. The detected overvoltage is processed through an AND gate and fed to the CPLD.
Overtemperature detection is also implemented. Three thermistors are used in order to monitor the
temperature on each IGBT module. For each module, the comparators detect two temperature levels. The
[60]
Chapter 4 – Hardware Design
six resulted signals are passed thorough and AND logic gate which outputs two signals, one for each level.
The two signals are passed to the CPLD. The overtemperature management is included in “OT” block.
Each gate driver outputs an active high fault signal. The twelve signals are tied on a logical AND configuration
indicated by the “F” block. The resulting signal is passed to the CPLD. Another two inputs for the CPLD come
from the user via two buttons, one for reset / trip and one for initialisation of modulation (not shown). The
XC9572 outputs a communication signal for the DSP, marked by the letter “A”. Also, seven Light-Emitting
Diodes (LED) are controlled by the CPLD in order to show current circuit state.
The DSP receives five analogue signals which are converted in numerical form by the internal ADCs.
Furthermore, the six PWM signals are sent to the CPLD. The begging and ending of the modulation is
controlled through the “A” pin. The RS-232 / 485 and CAN protocols for communication with other devices
are also implemented.
The dotted line which passes through the gate driver block represents the electrical isolation which
separates high power circuitry from the low power control stage.
4.2.
DC Link Capacitors and Load
The DC link capacitors are used mainly to decouple the effects of the inductance from the DC voltage source.
They provide a low impedance path for the ripple currents that are associated with the switching devices of
the inverter. There are three main factors that influence the ripple currents: the output inductance of the
load, the bus voltage and the PWM frequency of the inverter. These ripple currents are the most important
in sizing the electrolytic DC link capacitors [47]. Figure 4-2 presents the structure of the DC link capacitors as
developed on the experimental board.
Figure 4-2 – DC Link Capacitors from the Developed Experimental Board
These capacitors have to reduce the leakage inductance of the power bridge. The leakage inductances
produces inefficiencies throughout voltage spikes when the semiconductors are switched on and off with a
high
. If this inductance has a large value the switching time of the semiconductors needs to be increased
in order to protect the switching devices from voltage spikes. If this solution is implemented the losses
[61]
Chapter 4 – Hardware Design
during turn on and off increase, thus more heat is dissipated through the switching devices, hence the
impedance of the DC link has to be low.
When calculating the value of the DC link capacitors the amount DC link capacitance needs to be taken into
account as required for the inverter design. There are two important limitations when talking about
electrolytic capacitors in the DC link: the ripple current and the voltage that these capacitors can sustain
[47].
It has been highlighted that the impedance of the load influences the ripple currents in the DC link, thus for
the inverter designed a
induction motor was chosen as a load. The motor has the following
parameters according to [48]:




Power:
Voltage: 220 V
Poles:
Type: squirrel – cage induction motor

Stator resistance:

Stator inductance:
[
]

Rotor inductance:
[
]

Rotor resistance:

Mutual inductance:

Inertia:
[
]
[
]
[
]
Taking this information into account the equivalent resistance and inductance per phase can be obtained as:
and
. These calculations were made based on the equivalent schematic of the
induction motor.
Based on equivalent impedance per phase, the peak phase current can be written as in equation (4-1).
|
|
(4-1)
The three phase currents can be further modelled as in (4-2).
(4-2)
{
The only influence in the neutral point is due to small and medium vectors. For maximum modulation index,
the reference vector lies in region 3 or 4. If the reference vector lies in region 3, the dwell times for chosen
vectors are the one in Table 2-4. Given that only the small and medium vector influences the neutral point,
and that in the region 3, the dwell times of small vectors is equally split between N and P state, the RMS
value of the NP current for half sector is:
[62]
Chapter 4 – Hardware Design
(4-3)
√ ∫ | √ |
√ ∫ |
√
|
Given the neutral point current, the capacitor current can be written as:
(4-4)
The total DC link capacitance results as:
(4-5)
For a maximum voltage change of 2 V at 4 kHz switching frequency, the needed capacitance results as 1.5
mF. Given the neutral point current ripple and the needed capacitance, the DC link was modelled using 6
capacitors of 330 µF, each supporting up to 3 A rms current ripple at 450 V. The Panasonic capacitor chosen
feature reduced size and 85 °C endurance. Each half of the DC link consists of 3 parallel connected capacitors
as seen in Figure 4-3. The total supported current ripple is
and the equivalent capacitance is 1.98
mF.
Figure 4-3 – DC Link Configuration Used
4.3.
Switching
As mentioned earlier, for switching, three NPC IGBT leg modules from Semikron were chosen. The Semitop 3
series module, Figure 4-4, SK50MLI065 features the following [49]:
[63]
Chapter 4 – Hardware Design







600 V / 54 A per IGBT
Compact design
One screw mounting
Snubberless design
Heat transfer and isolation through
Direct Copper Bonded aluminium oxide
ceramic (DCB)
Ultra-fast Non Punch Through (NPT) IGBT
technology
Controlled Axial Lifetime (CAL)
technology for freewheeling diodes [50]
Figure 4-4 – One NPC Leg IGBT Module [49]
The advantage of using modules is that they are designed with special consideration for the commutation
paths [51]. Large commutation paths would make the circuit prone to high stray inductance. The chosen
Semikron modules are designed to minimise the stray inductance problem [51].
The CAL technology used for the freewheeling diodes is able to provide 30% more current compared with
previous generations. The technology features high power density and high thermal stability and reliability
[50]. The IGBT leg configuration is shown in Figure 4-5:



4 N-channel IGBTs:
4 freewheeling diodes:
2 clamping diodes:
Figure 4-5 – Internal NPC Module Schematic
The gate switching times as a function of gate resistor , extracted from IGBTs datasheet, is shown in
Figure 4-26. Based on this characteristic, in order to have a fall time of 20 ns and a rise time of 25 ns, the
value for
was chosen to be 20.1 . The switch on delay results as 60 ns and the switch off delay as 300 ns.
The switch off delay is the main reason for the chosen value.
[64]
Chapter 4 – Hardware Design
Figure 4-6 –
as a Function of Switching Times [49]
Given a dead time of 1.5 , the switching frequency has to be chose so that the dead time represents only a
small fraction of the switching period (calculated in subchapter 4.7). Considering maximum 1% deadtime
[52], the maximum switching frequency preferred is:
(4-6)
Given that the DSP main code run time for the NTV modulation is approximately 0.1
and considering that
the whole code should run at least twice after each interrupt, the preferred frequency considering the
update of the main code inside the 150 MHz DSP of 2.5 times is:
(4-7)
Based on this, the 4 kHz frequency was used both in the simulations and experiments.
4.4.
Gate Drivers and Protections
4.4.1. Gate Drivers
When choosing a gate driver, high interest was focused on a solution which would integrate both
optocoupler isolation and protection on a single Integrated Circuit (IC). Avago ACPL-332j, Figure 4-7, was
chosen due to its features such as [53]:
[65]
Chapter 4 – Hardware Design
-
Desaturation detection
Active Miller Clamping
Isolated Fault feedback
“Soft” IGBT turn-off
Under Voltage Lock-Out
Small package – Small Outline Integrated
Circuit SOIC-16
50
Common Mode Rejection (CMR) at
VCM = 1500 V
2.5 A output current
Figure 4-7 – Avago ACPL-332j Gate Driver [54]
The gate driver has an optically isolated power stage capable of driving IGBTs with up to 150 A and 1200 V
[53] . Under normal operation, the output voltage at pin 11 is controlled by the input LED PWM signals. At
the same time, the
voltage is monitored. The fault output is active high.
When the voltage on the desaturation pin 14 exceeds 6.5 V while the switching devices are on, the output
voltage is “softly” turned off in order to avoid large di/dt voltages [53]. At the same time, the fault output is
brought low. During “soft” turn-off, all input signal are ignored and the output is shut down for at least 5 .
The output of the gate driver is a combination of LED PWM input, Under Voltage Lock-Out (UVLO) and
desaturation detection.
Figure 4-8 – ACPL-332j Circuit Application
The gate driver is used based on the recommended application circuit from Avago datasheet. The
implementation for driving the third transistor from leg A is shown in Figure 4-8.
The circuit is powered through the floating isolated dual DC-DC converter DCDC8 from Murata
(NMK1212SC). The converter is floating with respect to IGBT emitter voltage. The input voltage is +12
[66]
Chapter 4 – Hardware Design
between pin 1 and 2. The output voltage between pin 5 an 7 is 24
. This 2 Watt converter was chosen for
the physical form, being rectangular instead of a square, as the other single output 24
DC-DC converters
were. The physical form helps in designing a reduced size inverter. Also, if features 3 kV isolation. Two
Schottky diodes, B0530W from Taiwan Semiconductor are tied between pins 5-6 and 6-7. The two diodes are
used in order to prevent converter damage from reverse current [55].
For obtaining the required 18 V for supplying the power part of the gate driver, the L78S18CV voltage
regulator from ST Microelectronics is used. The regulator features 2 A current capability, thermal overload
protection and shortcircuit protection [56]. The 0.33
electrolytic capacitor is used for input filtering and
the 10
electrolytic capacitor is used for improving regulator transient response [56] and for supplying
high currents needed during transient switching for the IGBT. The TESTR8 resistor is used for debugging
purposes.
The Avago ACPL-332j gate driver is formed by two circuits optically separated. The primary input voltage is
3.3
and the secondary input voltage is 18
. The 3.3
is supplied to the pins 2, 6 and 7. Because the
signal coming from the CPLD is passed through an inverting buffer, the PWM signal is connected to pin 5 and
8 (cathode) while the anode (pins 6-7) is kept a 3.3
potential. The 330 resistor used limits the input
LED current to recommended 10 mA. The low power ground is connected to pins 1 and 4.
The fault signal is transmitted through a LED (pins 5-8). A 0.471
pull-up resistor (not shown) is used after
the logical AND connection of the twelve fault signals. The 1000 pF capacitor on each fault output is used for
filtering. C1_08, a 0.1
capacitor is used for bypassing and circuit decouplings. The values chosen are the
ones recommended by the datasheet.
In the secondary part of the gate driver circuit, 18
is supplied to pin 13. The power ground (which is the
IGBT emitter) is connected to pins 9, 12 and 16. Another 0.1
capacitor is used for decoupling. CBLNK_08,
D_08, 35 ns diode from Taiwan Semiconductor and the 100 resistor, are required for fault detection. The 0
resistor is used as a simple jumper. The parallel connection of the 10
Zener diode and the 0.5 A
Schottky (On Semiconductor) diodes to pins 14 and 16, is used for improving desaturation detection by
avoiding false triggering which could happen when the gate driver substrate diode is forward biased. This
can happen when the negative voltage spikes due to freewheeling IGBT diode bring the desaturation pin
below ground. The Schottky prevents the substrate diode from being forward biased and the Zenner diode
prevents positive transient voltage to affect the desaturation pin.
The fast recovery, 35 ns diode is used in order to deny reverse recovery spikes on forwarding the gate driver
substrate diode which would lead to false fault detection. The 100 Ω resistor is used to limit the current
which could appear due to a negative voltage spike on the desaturation, pin 14. The negative voltage spike
can happen when the IGBT anti-parallel diode has a large instantaneous voltage transient [57].
The parallel 40.2 resistors from Te Connectivity are 0.1% precision, 0.5 W power devices used as IGBT gate
resistors with an equivalent resistance of 20.1 . The resistor limits the gate charge and collector rise and fall
times. The value is chosen based on IGBTs characteristics [49] from Figure 4-6. The 47
resistor is used for
pull-down in order to benefit a predictable high level output voltage.
Power dissipation in the gate resistors needs to be checked. Based on [58] the peak power dissipation in the
gate resistor can be calculated using (4-8) resulting as 16.119 W.
[67]
Chapter 4 – Hardware Design
(4-8)
The RMS current is the value that needs to be considered. Based on (4-8), the power dissipation in the gate
resistor for a 4 kHz switching frequency is 1.07 [mW]:
(4-9)
The RMS gate current is obtained considering a triangle pulse derivation during turn-on time:
(4-10)
√
Under Voltage Lockout [53]
The under voltage lockout prevents the application of insufficient voltage in the gate of the IGBT by forcing
the output of the gate driver to be low by clamping it. When the
(pin 13) goes above
(positive
threshold) the UVLO clamp is released and the gate driver will respond to input PWM signals. During the
increase of
from 0 V, the first function which becomes active is the desaturation function. UVLO has an
integrated hysteresis for improved noise immunity [57].
Active Miller Clamping [59]
A serious problem when driving IGBTs is the parasitic turn-on. This arises due to the Miller capacitor
between gate and collector. During turn-off, a high dv/dt transient could induce a parasitic turn-on which
could destroy the power converter. A current flowing through the parasitic Miller capacitor, gate resistor
and gate driver internal resistor can create a voltage drop on the gate resistor. If the voltage drop is higher
than the IGBT threshold, the parasitic turn-on will occur. Also, gate threshold is reduced by chip temperature
increase.
The Miller current can be derived as:
(4-11)
In equation (4-11), the
is the Miller capacitor,
is the Miller current and
is the IGBT collectoremitter voltage. This effect can be seen of both switching devices of a half – bridge configuration. The Miller
capacitance can be seen in Figure 4-9.
[68]
Chapter 4 – Hardware Design
Figure 4-9 – Miller Capacitor
The classical solution for dealing with Miller capacitor is the use of an additional gate-emitter capacitor to
shunt the Miller current or the use of a negative power supply in order to increase the threshold voltage for
the IGBT. First method suffers from efficiency loss and the second from the increased cost by the use of a
negative power supply.
Another solution would be the shorting of gate-emitter path through the help of an additional transistor
between gate and emitter. The currents across Miller capacitance are shunted by this transistor and will not
flow through the output gate driver pin 11. The gate clamp is activated when, during turn-off, the gate
voltage goes below 2 V.
“Soft” Turn-off Feature [60]
When short-circuit or overcurrent events occur, the soft turn-off feature helps by improving the designed
application reliability. Soft turn-off means that the gate driver output voltage is brought low softly in order
to reduce overvoltage spikes caused by lead wire inductances.
This feature is a process which occurs in two stages. The ACPL-332j features two pull-down devices, a weak
one (Doubled Diffused Metal Oxide Semiconductor – DMOS) and a larger (fifty times) DMOS transistor. In
the first stage, the weak pull-down device will slowly discharge the IGBT. During turn-off the large DMOS
remains off until the gate voltage output goes below
V. This is the time the large DMOS will clamp
the gate voltage to
.
Desaturation Detection [57]
Desaturation detection and protection are used to ensure the safety operation of IGBTs in short-circuit
condition. Desaturation can also occur due to other reasons such as driver supply voltage problems or
insufficient driver gate signal. Human error and supply rail short-circuits can cause high power dissipation in
the switching devices which lead to device destruction by overheat. The desaturation protection works by
monitoring the collector-emitter voltage,
. When a high current of a shorcircuit occurs, the voltage will
rise. The gate driver detects and triggers a fault when the collector-emitter voltage rises above the internal
gate driver desaturation voltage threshold, 6.5 V. When the fault is triggered, the IGBT is “softly” turned off
and the fault output is brought low.
[69]
Chapter 4 – Hardware Design
While the IGBT is in off state, the fault detection is disabled in order to prevent false triggering. Also, the
desaturation fault detection has to be disabled for a small amount of time after the IGBT is turned on in
order to allow the
voltage to fall below the internal desaturation threshold. The blanking time is
controlled by the internal desaturation charge current of 250
, the desaturation threshold and the
external blanking capacitor. The blanking time is calculated using equation (4-12):
(4-12)
With the recommended 100 pF capacitor, the resulting blanking time is 2.6
Gate driver fault management, as a combination of LED current
in Table 4-1:
UVLO (
On
Active
On
Inactive
On
Off
Off
Inactive
Active
Inactive
.
, UVLO and desaturation function is shown
Table 4-1 – Fault Management [53]
)
DESAT Function
FAULT Output
Inactive
Active
(desaturation fault)
Active (no fault)
Inactive
Inactive
High
Low
Low (fault)
Low
High (no fault)
High
High
High
Low
Low
4.4.2. Signal Acquisition
To assure that the inverter is working in its safe operating area and that in case of a fault, no hardware
destruction occur, different types of hardware protection must be considered. The protections implemented
for the proposed design are:





Phase overcurrent / short-circuit protection
DC Link overcurrent / short-circuit protection
DC Link overvoltage / out of range protection and detection
Over temperature protection
Integrated gate driver protection
In order to implement these protections, essential measurements have to be made. The phase currents and
the DC link currents are measured with Allegro ACS756 Hall Effect based current sensor. The DC link voltages
are measured by means of Linear Technology LT1366 differential amplifier. Temperatures are measured
using AVX NJ28 Negative Temperature Coefficient (NTC) thermistor.
Currents and voltages have been passed through the TLC372 voltage comparators used in a window
configuration. The temperature signals are compared with two levels. All signals are passed through AND
gates and then supplied to the CPLD. The CPLD will further stop the modulation in case of a fault and output
the fault condition through LEDs. All fault management is performed through the CPLD.
[70]
Chapter 4 – Hardware Design
Current Signal Acquisition
Allegro ACS756 Hall Effect IC sensor is a precise and economical solution for current sensing in AC and DC.
The low-offset linear Hall circuit converts the current flowing though the conductive path and generates
proportional magnetic field which is then converted into a voltage signal. The obtained voltage is precise due
to low-offset chopper stabilised IC. The Allegro ACS756, shown in Figure 4-10, benefits from the following
features [61]:









Industry-leading noise performance
Total output error 0.8%
Monolithic Hall IC
Ultra-low power loss: 130
conductor
resistance
3 kV RMS minimum isolation
Nearly zero magnetic hysteresis
Small package size
Measurement of ±50 A
Chopper stabilisation technique
Figure 4-10 – Allegro ACS756 Hall Current Sensor
The current sensors are used in the configuration shown in Figure 4-11 for both phase current acquisition
and DC link current acquisition. The shown example from Figure 4-11 is for phase A. The 0.1
capacitor is
used for bypassing and the 100
capacitor is recommended for filtering [61]. The current path is through
pins 4 and 5. The 5
analogue supply voltage is connected to pins 1-2. The output voltage signal is yielded
at pin 3. Tbe SNS_CRTx (where x=1:3) signal outputs have a value of 2.5
for 0 A and
characteristic.
Figure 4-11 – ACS756 Current Acquisition
Figure 4-12 – Phase Signal Divider
For a correct ADC interface, the 2.5
for 0 A has to be brought to about 1.5
. This is performed
through a divider on each SNS_CRTx signal (where x=1:3), like in Figure 4-12. The resulting signal, SNS_CRTxA
(where x=1:3) has a value of:
(4-13)
The SNS_CRTxA signal could be written as a function of measured current, equation (4-15).
[71]
Chapter 4 – Hardware Design
(4-14)
Where
is defined as in equation (4-15).
(4-15)
For a current of 0 A through the sensor, SNS_CRTxA will have a value of 1.666
. The
characteristic is also changed by the divider based on equation (4-13) to
. The SNS_CRTx
signals are passed to the window comparators and the SNS_CRTxA signals are supplied to the ADC through
voltage followers (buffers).
Voltage Signal Acquisition
An effective and economical solution for acquirement of voltage signals is the use of a differential
operational amplifier connected to the DC Link through high value resistors. The resistor network used is
composed of four High Voltage Direct Current (HVDC) connections through three series resistors
(470k+470k+560k). The series connection of the resistors ensures that the connection to the DC link will not
fail, as the current is small compared to resistors current capability.
The operational amplifier chosen is Linear Technology LT1366. The application of LT1366 is shown in Figure
4-13. The choice was made for to the features that this amplifier benefits of:








Input common mode range includes both rails
Output swing rail-to-rail
Low offset voltage
High Common Mode Rejection Ratio – 90dB
Power Supply Rejection Ration – 105 dB
Low input bias current – 10nA
Low supply current
400 kHz gain bandwidth
[72]
Chapter 4 – Hardware Design
Figure 4-13 – LT1366 Voltage Acquisition
The LT1366 is a dual operational amplifier supplied by a dual
isolated DC-DC converter
(NMK1212SC from Murata). A voltage of +12
is supplied at pin 8 and -12
at pin 4. Both pins are
bypassed by a 0.1
capacitor. The DC-DC converter is bypassed by two 10
electrolytic capacitors, one
between pins 5-6 and the other between pins 6-7. Resistors TESTRVa and TESTRVb are for debugging
purposes.
The inputs of each comparator are protected from DC link voltage transients through a pair of antiparallel
small signal diodes (TS148 from Taiwan Semiconductor). As said earlier, the high voltage signal is passed
through four series of three resistors with an equivalent resistance of 1.5
. The 100
capacitor on both
non-inverting inputs forms with the resistors a low-pass filter. The cut-off filter frequency results as in (4-16)
where R=1.5
and C=100 .
(4-16)
The transfer function of each operational amplifier, configured as a differential amplifier, is derived as an
example for first amplifier as in equation (4-17). In the normal operating condition, +HVDC=300 V, 0HDVC=0
V and –HVDC=-300 V. The second output can be calculated in the same manner, equation (4-18).
(4-17)
(4-18)
Both 6
outputs are passed through a voltage divider in order to obtain
VSISO2 voltages will have for 300
an output of:
[73]
. The VSISO1 and
Chapter 4 – Hardware Design
(4-19)
Combining (4-17), (4-18) and (4-19), the VSISOx (where x=1,2) could be written as:
(4-20)
Where:
(4-21)
The VSISOx signals are passed through the window comparators and then to the ADC through operational
amplifier voltage followers (buffers).
Temperature Signal Acquisition
The temperature is acquired using NJ28 high accuracy thermistors from AVX. The thermistors have a
resistance of 100
at 25 °C, which decreases with the temperature increase – thus having a NTC
characteristic. Temperature acquirement setup is shown in Figure 4-14:
Figure 4-14 – NJ28 Temperature Acquisition
Each thermistor, RTx (x=1:3) is connected in parallel with a 22
resistor and the resulted value signal is
passed through a voltage divider in order to modify the NJ28 characteristic. They are supplied with 5
.
The output voltage of the thermistors becomes (example shown for RT1), equation (4-22):
(4-22)
THERM1 values for important temperatures are shown in Table 4-2, calculated using (4-22).
Degree Celsius
25
70
75
80
85
Table 4-2 – Output Signal from Thermistor Acquisition
RT1 Value
[62]
THERM1 Output
100
1.0337
14.83
1.4994
12.28
1.6106
10.22
1.7332
8.537
1.8679
[74]
Chapter 4 – Hardware Design
The THERMx signals are compared with two pre-settable values and the result is passed to the CPLD through
logical AND gates.
Signal Processing Through Windows Comparators
The TLC372 from Texas Instruments was chose due to following features [63]:



Fast response time: 200 ns typical
Low supply current drain: 150
at 5
High input impedance:
The voltage signals corresponding to phase currents, DC link currents and DC link voltages are passed
through windows comparators with an active high output [64] when the signal is in the window limits. The
TLC372 [63] voltage comparator from Texas Instruments features two comparator per each IC, which are
connected in a window configuration as shown in Figure 4-15 (example for phase A current):
Figure 4-15 – Window Comparator Configuration
The comparator IC is supplied with 5
at pin 8 and bypassed with a 0.1
capacitor. The signal to be
compared is fed to pin 2 (inverting input for first comparator) and pin 5 (non-inverting input for the second
comparator). The “window” is formed by the reference voltages supplied at pins 3 and 6. The high reference
is supplied at the non-inverting input pin 3 and the low reference to the inverting pin 6. The high reference is
always greater than the low reference voltage. Each voltage reference is obtained by means of a voltage
divider between a potentiometer, configured as a variable resistor and a fixed 20
resistor. The output
signal is the union of first comparator output from pin 1 and the second comparator output from pin 7. The
signal is pulled up through a 10
resistor. Signals should not go above the maximum common mode input
voltage of 3.5
.
When the input signal voltage is between the two references, the output will be high and low when the
input signal is out of the voltage window from Figure 4-16 . The output signal is the thick dashed line and the
input is the thin arrow-ended line.
[75]
Chapter 4 – Hardware Design
Figure 4-16 – Window Comparator Operation
4.4.3. Protection Adjustment
The phase overcurrent and DC link overcurrent protection should be adjustable in
range. The input
signal for the window comparators is 1.666
for 0 A and the sensitivity is
. The output
voltage, using (4-14), will be 2.9993
at +50 A and 0.3327
at -50 A. Based on these values, the
potentiometers for high reference voltage and the one for low reference voltage can be chosen. For the low
reference value a potentiometer of 20
was chosen, and for the high reference value a potentiometer of
200 . The choice is viable for both phase overcurrent protection as for DC link overcurrent protection.
The over temperature protection should have two pre-settable levels. First level should be settable up to
70°C and the second level should be settable up to 80°C. For both levels one potentiometer with the value of
100
was chosen.
The DC link voltages should be settable to deviate up to
of the DC link voltage. At 300
, the output
of the voltage sensing is 1.522
. For 330
, the output signal will be 1.674
and for 270
will be
1.37
. For the low voltage reference a 10
potentiometer is chosen and a 20
potentiometer for the
high voltage reference.
For management and further fault notification, two SN75F21D AND logical gates from Texas Instruments are
used. Each IC contains three AND logical gates with three input each. The choice was made due to 3.2
fast
switching times [65]. Each gate is decoupled by a 0.1
capacitor. Through these gates, the outputs of the
three window comparator for phase overcurrent detection are merged into a single signal informing about a
fault condition regarding the current on one of the phases. The operation is logical AND because the fault
signals are active high. Furthermore, the signal is supplied to the CPLD.
The output of the six comparators used for over temperature detection are merged through the AND gates
in order to have two fault signals – one representing the first temperature level threshold and another
representing the second temperature threshold. These two signals are also supplied to the CPLD.
The two outputs regarding DC link overvoltage are also merged through the AND gates into a single signal.
The DC link overcurrent conditions are performed in the same manner. The gate drivers fault signals are tied
in a wired AND connection. The final fault signals supplied to the CPLD are:
[76]
Chapter 4 – Hardware Design






OT_A - which will switch low when one of the temperature of the IGBT modules will go above first
threshold level
OT_B - which will switch low when IGBTs temperature goes above second threshold level
DC_OV - will switch low when there is an overvoltage on one of the DC link halves
DC_OC - will switch low if there is an overcurrent condition on the two DC link halves
OCR - which switches low if a overcurrent condition occurs on any of the three phases
FAULT_GDX - which will be low if any of the twelve gate drivers encounters a fault
The three phase currents and the two DC link voltages are transmitted to the ADC block of the DSP. The
interfacing is made through five operational amplifiers configured as voltage followers. The chosen amplifier
is also recommended by Texas Instruments – OPA234, the manufacturer of the DSP. These are chosen due to
features such as rail-to-rail input/output, low noise and low quiescent current [66]. The voltage follower
configuration is shown in Figure 4-17 for the signals corresponding to the currents on two phases. The
configuration used is the same for the other signals.
Each OPA2343 IC contains two operational amplifiers. The IC is supplied with 3.3
from the analog supply.
The 0.1
capacitor on pin 8 is used for bypassing. The 100 resistor and the 0.1
capacitor on the
outputs of each operational amplifier are used as a low-pass filter for ADC input. Other scope of the two
components is to be used as a flywheel for the currents pulses created by the ADC’s input circuitry [67] . The
resulted filter cut-off frequency is 15.91
, calculated using (4-16).
The buffer input signals and the ADC input signals are protected from going over 3.3
or below ground
potential using a pair of dual series small signal Schottky diodes (BAT54S) from ST Microelectronics, Figure
4-17. The chosen solution is made due to low conduction and reverse losses, low forward and reverse
recovery times, low capacitance and extreme fast switching (8 ns) [68].
Figure 4-17 – OPA2343 Buffer Solution
4.4.4. Voltage Supply and Regulators
The developed PCB is divided in two main areas: HVDC area and low voltage – control area. The HVDC is
supplied through an external power supply. For the control area, a 12
also must be supplied externally.
The low voltage area has three parts: analog, digital and isolated communications area. For this purpose,
three isolated DC-DC converters from Traco Power (TEL3-1211) are used. These converters feature high
[77]
Chapter 4 – Hardware Design
efficiency, 1.5
isolation, and short-circuit protection and regulated 5
output. Power supplied is up to
3 W [69]. The output of each DC-DC converter is decoupled by a 33
capacitor.
In order to obtain 3.3






, the Texas Instruments TPS79533 regulator was chosen due to its features:
500
low dropout regulator
Ultralow noise
50 start-up
Very low dropout voltage, 110
at full load
High Power Supply Rejection Ration (PSRR)
Internal current limiting and thermal protection
The application of TPS79533 is show in Figure 4-18 . The datasheet [70] recommends a 2.2
filtering
capacitor near the input of the regulator – pins 1 and 2. The output capacitor, used to stabilize the internal
control loop is chosen to be 2.2
and connected between pin 4 and 6. The 0.01
capacitor is user for
bypassing the NR pin. Together with the internal 250
resistor, a low pass filter is created for the internal
voltage reference.
Figure 4-18 – TPS79533, 3.3 Vdc Voltage Regulator
Three 3.3
regulators are used on the board design. The given example, Figure 4-18, is for obtaining
desired voltage level for powering digital circuitry. The other two regulators supply 3.3
to analog
circuitry and isolated communication circuitry. Their usage is the same as give in Figure 4-18 .
In Table 4-3 the low voltage sequencing is shown. Each voltage type has its own ground and power planes.
The analogue and digital grounds meet near the DSP.
Table 4-3 – Voltage Type and Levels used on the Experimental Board
Type
Voltage Levels [
Input
Isolated
Analog
Digital
Floating
]
12
3.3
-12
5
3.3
5
3.3
-12
[78]
12
5
12
18
24
Chapter 4 – Hardware Design
4.4.5. Communication
The DSP can communicate with external CPUs through the CAN or RS-232 / 485 protocols. Hardware
implementation for CAN and RS-232 / 485 is shown in Figure 4-26. Through the D_Isolator1, signals needed
for RS-485 communication are isolated. Furthermore, the CAN signal isolation is obtained through the
D_Isolator2. The digital isolator chosen is the ISO7221 from Texas Instruments, featuring up to 150 Mbps
signalling rate, low Pulse Width Distortion (PWD), low jitter (1 ns), 4 kV isolation and high electromagnetic
immunity [71].
Figure 4-19 – CAN and RS-232 / 485 Communication
The digital isolators are powered with 3.3
from the digital supply on the PCB side and with 5
from
isolated supply for the output side. Both are decoupled by a 0.1
capacitor. The 0 resistor on pin 6 of the
D_Isolator1 is to be soldered only if RS-485 is going to be used. The input of the D_Isolator1 is formed by RXB
and TXB signals coming from the DSP. The D_isolator2 input is composed of CAN_RXA and CAN_TXA also
coming from the DSP. All digital isolator input signals are pulled-up with a 10
resistor.
The signals for RS-485 communication are passed through SN75LBC176 differential bus transceiver from
Texas Instruments, featuring bidirectional transmission, high speed, low skew, current limiting and thermal
shutdown protection [72]. The IC is supplied with 5
from the isolated supply and bypassed with 0.1
capacitor. The driver and the receiver enable pins 2 and 3, RE and DE, connected to the 5
supply (DE pin)
and ground (RE pin). A and B are the driver outputs and R is the receiver output. The jumper J1 is used to
enable or disable the 120 termination resistor.
The output of the transceiver together with the RXA_ISO and TXA_ISO are received from the DSP and are
interfaced through a serial DE-9 connector. RXA_ISO and TXA_ISO are connector to pins 2 and 3 of the RS232 communication. Pins 4-8 and 5-9 are used for RS-485 communication [73].
The CAN signals are passed through SN65HVD1050 CAN transceiver from Texas Instruments. It features high
electromagnetic immunity, low electromagnetic emissions and bus fault protection [74]. The IC is supplied
with isolated 5
and bypassed with 0.1
capacitor. The J2 jumper is used to enable or disable the 120
[79]
Chapter 4 – Hardware Design
resistor termination. The output signals are transmitted to the outside world through another DE-9
connector, that has pins 2 and 7 used for data [75].
4.5.
Power Tracks Sizing
The current carrying capability of the PCB has to be calculated prior to the board manufacture. The
maximum current is proportional to the cross-sectional area of the tracks. The copper thickness is 70 µm.
Given the minimum width of the DC link track as 6.73 mm and of the phase track as 10.5 mm, the maximum
current [76] can be calculated as in equation (4-23).
(4-23)
Where I is the current in amperes, A is the cross section in square mills and
is the temperature rise in
Celsius degree between ambient temperature and the safe operating temperature of the PCB [76]. The
constant k is defined as k=0.048 for outer layers and k=0.024 for inner layers. Knowing that 1 mil = 0.0254
mm, the equation (4-23) can be modified to be used with the metric units, thus resulting equation (4-24).
(4-24)
Using equation (4-24), the current carrying capability of the DC link, for a temperature rise of 55 °C, results
as 33 A for outer layers and 17 A for inner layers. For the same temperature rise, the phase current for inner
layers results as 23 A for inner layers and 46 A for outer layers. The above calculation is validated through
thermal imaging in subchapter 4.8.
4.6.
Cooling
An important role is hold by maximum electrical ratings and thermal limitations of semiconductor devices.
There needs to be taken into account that the operating junction temperature of all devices does not exceed
the limits under all specified conditions [77]. The Semikron modules have high thermal performance and
integrate latest silicon technology, thus the result has high efficiency and cost effectiveness. These modules
are used for PCB soldering, Figure 4-20. A single mounting screw and the copper baseplate are used in order
to ensure thermal performance [78].
[80]
Chapter 4 – Hardware Design
Figure 4-20 – NPC Leg Module – Copper Baseplate
The inverter designed in this thesis has a power rating of 8
at a frequency of 4
. Semikron offers
an application note for loss calculation [51]. The analytical method presented in this application note is
based on [79]. The cross – sectional view of a typical Semikron IGBT package can be seen in Figure 4-21.
Figure 4-21 Typical IGBT Structure – Layers and Heat Flow Path [80]
On the three level NPC configuration presented in Chapter 2 the conduction losses for transistors T1 and T4
can be calculated in the same manner. This is presented in (4-25).
̂
{
̂
Where:





– Modulation index
̂ – Peak value of current
– IGBT forward threshold voltage
– conduction angle
– IGBT on – state slope resistance
[81]
}
(4-25)
Chapter 4 – Hardware Design
For a proper calculation regarding the thermal resistance of the heatsink NTV-EHE modulation strategy was
taken into account. As a load, for thermal calculations, an induction motor with the power rating of 8
,
peak current of 19.2
, power factor of 0.85 and a voltage of 400
was considered. Considering these
informations the conduction angle was calculated and it has a value of
.
The switching losses for transistors T1 and T4 are calculated as in equation (4-26).
(
̂
) (
)
(
(4-26)
)
Where:




– Switching frequency
– Sum of energy dissipation during turn – on and turn – off time
– Exponent for the current dependency of the switching losses
– Reference current value of the switching loss measurement



– Exponent for the voltage dependency of the switching losses
– Collector – emitter supply voltage
– Reference voltage value of the switching loss measurement

– Adaptation factor for the non – linear semiconductor characteristics
Conduction losses for transistors T2 and T3 are calculated based on (4-27).
̂
̂
{
(4-27)
}
In order to calculate the switching losses for transistors T2 and T3 formula (4-28) is used.
(
̂
) (
)
(
(4-28)
)
The formula for conduction losses on the clamping diodes D5 and D6 is presented in (4-29).
̂
{
[
]
̂
}
(4-29)
Where:


– Diode collector – emitter threshold voltage
– Diode on – state slope resistance
In order to calculate the switching losses for the clamping diodes D5 and D6 formula (4-30) is used.
(
̂
) (
)
(
(4-30)
)
Conduction losses for reverse recovery diodes D1 and D4 are calculated as (4-31):
[82]
Chapter 4 – Hardware Design
̂
̂
{
}
(4-31)
Based on equation (4-32) the switching losses for reverse recovery diodes D1 and D4 are calculated.
(
̂
) (
)
(
(4-32)
)
The formula for conduction losses on reverse recovery diodes D2 and D3 are presented in (4-33).
̂
̂
{
}
(4-33)
Switching losses for reverse recovery diodes D2 and D3 are presented in (4-34).
(4-34)
The typical values for , , and are found on the Semikron modules datasheet for three level NPC and
three level Type Neutral Point Clamped (TNPC). They are presented in Table 4-4.
Table 4-4 – Typical
,
, and
IGBT
1.4
1
1
for Semikron Modules [51]
Diode
0.6
0.6
1.15
In order to calculate the thermal resistance of the heat sink the total losses in the NPC leg need to be
calculated. The absolute maximum ratings described in (NPC leg datasheet) are used. The other parameters
are selected based on the NTV modulation strategy. The most important ratings are:








– for each IGBT
– for each diode

– freewheeling diode

– antiparallel diode

The ambient temperature was considered to be
. By solving the equations presented above
conduction losses on each device are obtained and presented in Figure 4-22.
[83]
Chapter 4 – Hardware Design
Figure 4-22 – Losses on Each Component in the NPC Leg
Taking all the calculated losses into account the equivalent thermal model for the NPC converter can be
drawn. The equivalent model of the thermal behaviour can be seen in Figure 4-23. This represents the
Semikron Semitop3 Module with the structure presented in the beginning of this chapter (Figure 4-4). From
the thermal point of view the NPC leg has been considered to be built of ten parallel heat sources,
correspondent into electrical terms as current sources. The model presented in Figure 4-23 describes each
device from the NPC converter leg. The temperature difference between each nod is considered to be a
voltage drop on the equivalent thermal resistance. There are three types of thermal resistances that are
generally considered: junction – to – case resistance
, case – to – heat sink resistance
, sink – to –
ambient resistance
. The junction – to – case resistance and case – to – heat sink resistance are offered
by the producer in the datasheet. Semikron gives in [49].the thermal resistance between junction and heat
sink for each device:

per IGBT.

per antiparallel diode

per freewheeling diode.
[84]
Chapter 4 – Hardware Design
Figure 4-23 Thermal Model of Semikron SEMITOP Module (NPC Leg)
When talking about the heat sink all devices that produce heat has to be taken into account. One of the
important components that need cooling is the voltage regulator that supplies the gate driver. There are 12
gate drivers, thus 12 voltage regulators need to be used. These voltage regulators are supplied with
and have
at the output. The power dissipation on these devices has been calculated based on [81]
[82]. This is presented in equation (4-35).
(
)
(4-35)
Where:





– Power dissipation
– Input voltage supplied to the regulator
– regulator output voltage
– regulator output current
– Regulator biasing currents
In general, when talking about thermal considerations the worst case scenario needs to be used. The output
current of the voltage regulator is decided by the gate driver, thus
at
output
voltage. The regulator biasing current is zero. In conclusion, the power dissipated on a voltage regulator is
, therefore all the voltage regulators dissipates
. The base plates of the
voltage regulators have different potential, thus in order to avoid short circuit the thermo – conducting
insulating layers have to be used. The thermal resistance of the pads is
.
Taking into account the voltage regulators and NPC legs the total power dissipated on the inverter
is
. The thermal resistance was calculated based on [83] and is presented in (4-36).
[85]
Chapter 4 – Hardware Design
(4-36)
[ ]
Considering the value of the thermal resistance a heat sink with the thermal resistance of
[ ] from H S
Marston has been chosen.
4.7.
CPLD and DSP Control
The space vector modulation strategies were implemented on a TMS320F28335 DSP based Control Card
from Texas Instruments. Deadtime and protection management is performed through Complex
Programmable Logic Device (CPLD) XC9572XL. The use of the Control Card represents a fully embedded
design solution, Figure 4-24, providing features as:
ControlCard Features
 Small Form Factor
 Standard 100 pin DIMM
 Analog and Digital Input/ Output (I/O)
 JTAG Interface
 Isolated RS-232 Interface
 5v Supply
CPU Features
 150 mhz, 32 bit Floating Point
 256k x 16 Flash, 34k x 16 Single Access
Random Access Memory (SARAM)
 Up to 18 PWM Outputs
 12 Bit ADC With 16 Channels
 80 ns ADC Conversion Rate
 88 General Purpose Input/ Output (GPIO)
 CAN, RS-232
Figure 4-24 – Control card Integration into the Designed Inverter
Different modulation strategies are implemented on the DSP based on the code developed in the simulation
model. The PWM is executed by six ePWM modules. Analogue signals, as three phase currents and DC link
voltages are acquired on 5 ADC channels. Pin number 95 is reserved for communication with the CPLD. The
ePWM modules are set to work based on modified Up-Down-Count mode with Dual Edge Asymmetric
Waveform [84]. The schematic of how the ePWM module configuration works can be seen in Figure 4-25:
[86]
Chapter 4 – Hardware Design
b) Asymetrical Up Count Mode
a) Symetrical Up – Down Count Mode
Figure 4-25 – DSP Counter Modes
There are two counters active for each ePWM module, CA and CB. When the Time Based Counter (TBCTR)
reaches CA on Up Count, or CB on Down Count, the output is set high. When TBCTR reaches CB on Up Count,
CA on Down Count, equals zero or period, the output is switched low. This mode of operation permits better
use of the ePWM module, retaining 0-100% duty cycle. All modulation strategies use the symmetrical updown count mode, except for RS3N and ZCM which use the asymmetrical up count mode.
An interrupt takes place on the beginning of each period that is acknowledged in an Interrupt Service
Routine (ISR). During the ISR, the dwell times calculated on the main function are assigned to the ePWM
module counters. Also, ePWM1A sends the Start-Of-Conversion signal to all ADCs. The ePWM module uses
the shadow registers which act as time buffers. On the beginning of each period, the values of the counters
are updated on the shadow register after the register has assigned the values to the active counters.
From the ADC module [85], 5 channels are used. The sampling frequency is set to 12.5 MHz. The three phase
currents and the two DC link voltages are acquired on each Start-Of-Conversion signal received from the
ePWM module. In order to save time, the values are read into 5 global variables on the ISR used for PWM.
Pin 95 on the control card makes possible communication with the CPLD. The signal received from the CPLD
stops the modulation or starts the V/f control when needed. One of the LEDs on the Control Card is used to
show operation of the DSP and it flashes with the system frequency of 50 Hz or the frequency used to start
in V/f control. The LED is off while the modulation is not running. In order to benefit from the full speed
while embedded, the DSP has been programmed to load the entire code from flash memory to the Random
Access Memory (RAM) memory at power-up. Then, the programs run fully from the RAM memory.
The Xilinx XC9572XL, Figure 4-26, CPLD used benefits from the following features:





72 Macrocells
100 MHz frequency
1600 usable logic gates
34 User I/O
3.3/5v Tolerant
Figure 4-26 – CPLD used for Deadtime and Protection Management
[87]
Chapter 4 – Hardware Design
The tasks performed by the CPLD are:




Deadtime management for each pair of complementary switches.
Stop the modulation and disable the buffers in case of a fault.
Signal fault status.
Manages PWM procedures specific to NPC topology.
When IGBTs are used the deadtime or interlock delay time needs to be taken into account. This time is used
to first turn off one IGBT and turn on another. Furthermore, bridge shoot through caused by unsymmetrical
turn on and off times are avoided [86]. The dead time was calculated based on equation (4-37).
[(
)
(
)]
(4-37)
Where:

– is the maximum turn off delay time


– the minimum turn on delay time
– the maximum propagation delay of driver

- the minimum propagation delay of driver
By the use of gate driver [53] and Semikron module datasheets [49] the dead time can be calculated. The
maximum turn off delay time is
, the minimum turn on delay time is
, the maximum
propagation delay of the driver is
and the minimum propagation delay of the driver is
.
Hence, the dead time according to equation (4-37) is
. As the developed board is a test one and
the dead time is generated through the CPLD, dead time can be modified through software, for safety
reasons a dead time of
was chosen. Aside from deadtime insertion, the algorithm has to assure that
certain gate signal combinations are avoided. On a three level inverter using IGBT leg modules, the following
switching states are possible [51], Table 4-5.
T1
T2
T3
T4
state
0
0
0
0
0
1
0
0
0
1
0
1
1
0
0
0
Allowed States
0
1
1
0
Table 4-5 – NPC Switching States
0
1
0
1
1
0
0
0
0
0
1
0
0
0
1
1
0
1
1
0
Dangerous States
0
1
0
1
1
1
1
0
1
1
0
1
0
1
0
1
1
1
1
1
Destructive States
1
1
1
1
All the destructive states are avoided by insertion of deadtime by means of shift registers because switch
pairs T1-T3 and T2-T4 cannot be high at the same time. By means of a simple filter on the PWM inputs, the
rest of the dangerous states are avoided.
Also, in the case of an emergency shutdown, the switches have to be turned off in a certain manner. In order
to avoid voltage breakdown, outer switches (T1 and T4) have to be switched off first [51]. Also, in a
desaturation event, there is a window of 10 us for complete switch-off [51]. The shutdown procedure
ensures that any switching sequence is overridden with state “O” after proper deadtime. After reach of state
“O” the inverter is completely shut down by disabling the external PWM buffers. The shutdown procedure is
applied whenever there is a fault or the inverter is manually tripped.
[88]
Chapter 4 – Hardware Design
In case of a desaturation event, the gate drivers will latch in fault state. In order to be able to further use the
inverter, a gate driver reset procedure is performed. The reset procedure disables the PWM from the DSP
and sends the command sequence O-N-O-P-O to the inverter. This way each gate driver receives a short
reset pulse used to release the latch (in case the fault is cleared).
The LED enable procedure sends the multiplexed LED signals to a demultiplexer through PWM. Seven LEDs,
two green and five red provide information about the inverter state.
LED1
Green
LED2
Green
Power On
SVM On
Table 4-6 – Fault Warning
LED3
LED4
LED5
Red
Red
Red
DC
DC Voltage
Gate driver
Overcurrent
Range
LED6
Red
Phase
Overcurrent
LED7
Red
Overtemperature
The start/end of PWM is transmitted to the DSP in order to stop the ePWM modules or to start the V/f
control.
4.8.
Hardware Validation
The three level NPC inverter design presented in this chapter has been built and tested in the laboratory.
Furthermore, the protections together with dead time and turn on and off procedures are validated through
experimental results.
Deadtime Insertion
Before powering up the inverter at full power a few tests have to be performed. The dead time between two
complementary IGBTs has to be tested. The experimental result can be seen in Figure 4-27. The purple signal
is the command for transistor T1 and the blue signal is the command for transistor T3. A proper 1.5 us dead
time is inserted between any two complementary IGBTs.
Figure 4-27 – Deadtime between Two Complementary IGBTs – Experimental Result
[89]
Chapter 4 – Hardware Design
Turn On and Off Procedures
As stated before, in chapter 4.7, each IGBT leg of the inverter has to be turned on and off in a certain way.
When the inverter is shut down, the outer transistors have to be turned off first followed by the inner
transistors after proper deadtime.
Figure 4-28 – Turn On and Off Procedures of the Semikron IGBT Module – Experimental Results
The turn on and turn off procedures can be seen in Figure 4-28. The procedures are applied in parallel for all
three inverter legs. Each of the inverter legs can be in a different state (0, N or P). Figure 4-28 presents one
inverter leg. For all waveforms, the blue represents signal for transistor T1, light blue signal for transistor T2,
purple represent signal for transistor T3 and the green signal represents transistor T4. As seen in the first
waveform, the inverter is in N state. After deadtime, the inverter is switched to state 0 and after 1.5 us, the
octal buffers are disabled, switching the inverter off completely. Second waveform represents the shut down
from an N state and the third waveform shows turn off from a 0 state. The fourth waveform represents the
turn on procedure. Every time, every leg starts in the 0 state, after which the modulation is started.
Reset Procedure
In the case that one of the gate drivers encounters a fault, a reset procedure has to be followed in order to
release all gate drivers latch and restart modulation. Signal colours are the same as in Figure 4-28. The reset
procedure can be seen in Figure 4-29.
[90]
Chapter 4 – Hardware Design
Figure 4-29 – Reset Procedure for Restarting the Modulation – Experimental Result
The reset procedure works together with the turn on and the turn off procedures. Hence, the start and end
of the reset procedure is the state “0” (0110), meaning that the inner transistors are switch first at the
beginning and end of procedure. As each gate driver has to receive a short pulse in order to release the
latch, the gate driver reset procedure ensures that the entire inverter is reset using zero states. As it can be
seen in Figure 4-29, each inverter leg goes through states O-N-O-P-0. Because the procedure is applied at the
same time for all legs, the inverter will switch through all zero vectors: 000, NNN and PPP thus ensuring that
each gate driver receives a short signal in order to release the fault latch, while the voltage applied to the
load is 0 V.
DC Link Voltage Range Protection
The DC link voltage has to be maintained between certain limits. The protection is set to shut down the
inverter if each capacitor voltages voltage drops or increases with 10%. This means a
band for each
of the capacitors. For this test, the DC link was connected to a three phase power switch in order to be able
to connect a 5 kΩ resistor to upper or lower side. In Figure 4-30, the green signals serves as overvoltage
reference, set at 330V. The light blue signal serves as undervoltage reference equal to 270 V. The blue signal
is the capacitor bank voltage for upper half of the DC link (left) and lower half (right). The purple signal
represents the protection response. As it can be seen in Figure 4-30, when the capacitor voltage is outside
the two references, the protection triggers a fault, shutting down the inverter. The capacitor voltage in each
case was raised from below the lower reference to above the upper reference and back.
Figure 4-30 – DC Link Voltage Range Protection – Experimental Results
[91]
Chapter 4 – Hardware Design
DC Link and Phase Overcurrent Protection
An overcurrent event on the DC link or one of the phases also triggers the inverter. The phase overcurrent
response can be seen in Figure 4-31. For this test the DC link was set at 15V and two of the output phases
have been connected together. The pink signals serves as the reference and it is set to 25 A. The green signal
is the short circuit current for phase overcurrent protection (left) and for DC link overcurrent protection
(right). The blue signal is the protection response in each case. At the encounter of a high current the
inverter trips in both cases.
Figure 4-31 – Overcurrent Protection – Experimental Result
Overtemperature Protection
The overtemperature protection has to trip the inverter if any of the three modules surface reaches 80°C.
The protection response can be seen in Figure 4-32. For this test, the thermistors were removed from their
sockets and external resistors were used to trigger the protection. Each of the signals represents one of the
IGBT thermal protection responses.
Figure 4-32 – Overtemperature Protection – Experimental Result
Three 9.09 kΩ resistors corresponding to a temperature of 82 degree Celsius has been inserted at different
times in the socket of each thermistor in order to trigger the protection. The protection triggers a fault
immediately as the resistors are inserted.
[92]
Chapter 4 – Hardware Design
Thermal Design Validation
Furthermore, the thermal design needs to be validated through experimental results. The setup from Figure
4-33 was used. The inverter had an R-L load with equivalent of 6 kVA. Temperature was verified each ten
minutes using a thermal camera. The inverter reached thermal steady state after 40 minutes. In order to
have a confidence in the measurement the test was carried another 20 minutes. The temperature did not
increase in this interval.
Figure 4-33 – Experimental Setup for Thermal Validation
The infrared picture from Figure 4-34 was taken after one hour. As it can be seen the temperature in the DC
link capacitors was approximately 30°C, which is below the 85°C limit of the Panasonic capacitor chosen. The
temperature from the modules area was 50°C, which is below the maximum surface temperature of 80°C
allowed for the IGBT modules. The hottest part of the inverter was at 56°C on the gate drivers and their DCDC converters. The board shows thermal symmetry with the hot area in the middle being surrounded by
colder areas, presenting good heat dissipation. Hence, the thermal design was validated.
Figure 4-34 – Thermal Picture of the Inverter at
[93]
After One Hour
Chapter 4 – Hardware Design
[94]
Chapter 5 – Experimental Validation
5. Experimental Validation and Analysis of the Developed Modulation
Strategies
Four modulation strategies were developed and rigorously tested through simulation before implemented on
the designed inverter. The comparison between the four new strategies was made against classical NTV and
ZCM. All offer reduced spectra for CMV compared to NTV. Although all offer natural NP balancing, only two
provide extra balancing capability of up to 35%. One of the strategies developed, RS3N exhibits very strong
advantages: the CMV is similar to ZCM method while maintaining the maximum modulation index of the NTV
modulation. It also offers better EMI performance in high frequency range and the ability to balance the DC
link in the event of external factors.
5.1.
Experimental Setup
For validation of the theory and simulations, regarding the developed modulation strategies, experiments
have been performed on the developed board described in Chapter 4. All experiments were performed in
the same manner and with the same settings at its maximum modulation index. The control of the inverter
was supplied from an external source, GwInstek GPS-4303. The DC link voltage was provided by 2 power
supplies of 300 V each, SM 300-5. A 1.5 kW three phase induction motor was used as a load connected to a
DC motor and power resistor. In order to see how the modulation strategy influences the CMV and EMI, no
output filters were used. All voltage measurements were acquired using differential probes and visualised on
the Tektronix oscilloscope. The experimental setup used to validate the developed modulation strategies is
presented in Figure 5-1.
Figure 5-1 – Experimental Setup for Testing the Developed Modulation Strategies
[95]
Chapter 5 – Experimental Validation
5.2.
Nearest Three Vectors with Even Harmonic Elimination Method
Figure 5-2 presents the experimental results regarding the phase, phase-to-phase, common mode and DC
link voltages for NTV-EHE. The experiment was performed at maximum modulation index,
. As
expected, this voltage has a quasi-sinusoidal shape and nine voltage levels. The line voltage features five
levels and the CMV has the maximum amplitude of +. The DC link maintains balance proving the
natural balancing mode. The voltage variation on the DC link capacitors is under 5V. The results are in
concordance with the theoretical basics and with the simulations. The results regarding the performance of
the following methods will be compared to this method.
Figure 5-2 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for NTV-EHE - Experimental
Results
5.3.
Zero Common Mode Method
The waveforms for ZCM are also in concordance with theory and the results from simulation. The level on
the phase and on the line voltages are the same with the simulation. The effect of dead time is seen in the
presence of CMV, Figure 5-3. The amount is to be analysed on chapter 5.9. Considering that the reference
vector lies in sector 1 the switching sequence is
. The IGBT modules will receive the command
from Table 5-1. In the ideal case, the switching between vectors does not have any dead time inserted, thus
resulting in no CMV. This can be seen in the first line of Table 5-1. In the presence of dead time, the
intermediate states appear when switching between certain vectors, as seen in the second line of Table 5-1.
For example, the crossing between PON and PNO vectors has an intermediate state for which both second
[96]
Chapter 5 – Experimental Validation
leg and third leg are in zero state, hence P00. The length of this state is the dead time interval. Known from
Table 2-5 in chapter 2.4.2, the POO intermediate state generates a CMV of
rest of the sectors, resulting in a CMV of
. Similarly happens in the
, but on a very short period of time, compared to the applied
vectors.
The performance of the proposed modulation strategies is going to be analysed in comparison with the ZCM
and NTV.
Table 5-1 – Influence of dead time on the switching sequence
000
000
000
P0N
000
PON
PN0
P00
PNO
000
000
000
Figure 5-3 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for ZCM - Experimental
Results
5.4.
One Large One Medium Method
Experimental results for OLOM validate the simulation model proposed before. The experiment, Figure 5-4,
shows the same number levels in the phase voltage, phase-to-phase voltage and CMV. The DC link benefits
the natural balancing mode, with the capacitor voltage having a ripple under 5V. The CMV has a
fundamental of 150 Hz, easily visible. The performance regarding CMV is going to be analysed in chapter 5.9.
[97]
Chapter 5 – Experimental Validation
Figure 5-4 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OLOM - Experimental
Results
5.5.
Zero Small Medium Large Method
The results of the ZSML, Figure 5-5, seem to be similar with NTV modulation. This occurs only at maximum
modulation index, due to the fact that the zero vector is not applied. This can be seen from equation (5-1).
(
(5-1)
)
As the reference voltage is increased, the time for zero vector is decreased. Hence, the dwell time for the
zero vector becomes zero when
. This particularity makes the phase and phase-to-phase
voltages to look identical with NTV-EHE. The difference can be clearly seen in the CMV levels, which are
maxim
compared with
for NTV. The method is tested in natural balancing mode, but
there is the possibility of balancing in the case of an external neutral point unbalance. The balancing
capability curve is presented in chapter 5.8.
[98]
Chapter 5 – Experimental Validation
Figure 5-5 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltage for ZSML - Experimental
Results
[99]
Chapter 5 – Experimental Validation
5.6.
One Small One Medium Method
The good concordance between theory, simulation and experiment is also maintained for OSOM, Figure 5-6.
The ripple on the capacitor voltages is smaller when compared with the rest of the modulations, being under
2.5 V. As in the OLOM modulation, the CMV fundamental frequency of 150 Hz can also be clearly seen.
Figure 5-6 – Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for OSOM - Experimental
Results
5.7.
Random Sequence of 3 with Neutral Point Balancing Method
RS3N modulation follows the same pattern of good concordance between simulation, theory and
experimental results as seen in Figure 5-7. Although the similarity with the NTV modulation is very high, this
method has some clear differences compared to NTV. The line voltage and phase voltage are similar to NTV
but the randomization of the vectors inside each switching sequence can be clearly seen. Another difference
is the level of
in the CMV voltage, which is half of NTV. Again, the random component can also be
seen clearly in the CMV which is expected to reduce the amplitudes at high frequencies.
The voltage on the capacitors features a variation under 5 V. The waveforms were acquired for natural
balancing mode. Another method of differentiating it from NTV is by the fact that this modulation will
recover natural point balance if the neutral point potential slides towards negative or positive voltages. The
balancing capability curve is presented in chapter 5.8.
[100]
Chapter 5 – Experimental Validation
Figure 5-7 –Phase Voltage, Phase-to-Phase Voltage, CMV and DC Link Voltages for RS3N - Experimental
Results
5.8.
DC Link Balancing Capability
All developed modulation strategies have the ability to self-balance, but only ZSML and RS3N can balance
the DC link in case of an external event. The balancing capability can be determined based on theory
presented at DC link capacitors, chapter 4.2 – equation (4-3). According to [32] it can be determined which
phase is connected to the neutral point. Furthermore, the balancing capability is calculated as a function of
phase current, equation (4-15).
(5-2)
When the modulation index is maxim and the displacement angle is between 0 and
the balancing current
can be calculated as in equation (5-3) for both ZSML and RS3N.
(5-3)
√ ∫ |
√ |
Starting from minimum modulation index until at half of it, both modulation use two small vectors for
balancing. Hence, their balancing capability can be calculated. As an example, the equation for balancing
capability at
is presented in (5-4).
[101]
Chapter 5 – Experimental Validation
(5-4)
√ ∫ |
√
√ |
In order to validate this theory experiments at different modulation indexes have been performed on the
two methods, ZSML and RS3N. The setup shown in Figure 5-8 was used. A variable power resistor was
connected through a three position switch to the neutral point of the inverter, enabling the connection to
the upper or lower halves of the DC link. When the switch is in neutral position the resistor has no effect
(natural balancing mode).
Figure 5-8 – Experimental Setup Used for DC Link Balancing Capability Assessment
Based on the performed experiments Figure 5-9 was obtained. As it can be observed RS3N has better
capabilities of balancing than ZSML. The RS3N has the maximum balancing capability at
, while
ZSML at
. The ability to balance the DC link at maximum modulation index is similar.
Figure 5-9 – Capability Curve Function of Phase Current vs. Modulation Index Determined Experimentally
[102]
Chapter 5 – Experimental Validation
5.9.
CMV Analysis
The general theory regarding CMV has been presented in subchapter 2.4 and the theory of developed
modulation strategies chapter in 3. For a better understanding, experiments have been performed with the
measurement setup described in chapter 2.5.2. The CMV has been measured at the maximum modulation
index of each modulation strategy and performed the Fast Fourier Transformation (FFT) on it, Figure 5-10. As
it can be seen, all modulation strategies decrease in amplitude while increasing in frequency. As the parasitic
coupling inside the motor are mainly capacitive, this characteristic is preferred. The amplitude at very low
frequency, as 150 Hz has little effect as the current generated is small. This can be observed from the
formula (5-5). As the frequency of the capacitance decreases, the current decreases.
(5-5)
|
|
The fundamental frequency for all modulation strategies is 150 Hz. The NTV-EHE modulation has 53.7 V on
the fundamental frequency. Around the switching frequency, 4 kHz, the CMV amplitude is 44.3 V. At the rest
of the frequency range, the NTV-EHE modulation has amplitudes under 14.8 V. The CMV is present up to
100 kHz. The ZCM modulation should have zero CMV, if it was ideal, but in real life applications deadtime
has an influence resulting in the low CMV, Figure 5-10. The fundamental for ZCM is at 8.24 V; while at
switching frequency is 16.5 V. The CMV vanishes before reaching 50 kHz.
Figure 5-10 – FFT on CMV for Classic and Developed Modulation Strategies – Experimental Results
[103]
Chapter 5 – Experimental Validation
Further on, the proposed modulation strategies are to be compared with the classical ones. OLOM shares
the same 100 kHz frequency range as NTV while having only 27 V CMV around the switching frequency. The
rest of the spectrum remains below 11.8V. OSOM has higher amplitude on fundamental frequency 74.7 V,
and low amplitude, 12.3 V, around the switching frequency. The disadvantage would be the 32.7 V at the
double of the switching frequency. The spectrum remains below 100 kHz with amplitudes below 14.7V.
ZSML has 43 V on CMV around the switching frequency, but the spectrum is only until 50 kHz with
amplitudes under 17.7V. An interesting result is provided by the RS3N modulation strategy. By randomizing
its vectors inside the switching sequence, the CMV frequencies are moved towards lower frequency range.
The CMV around the switching frequency for RS3N is 19.1 V. The rest of the spectrum, which is until 50 kHz,
features amplitudes below 7.5 V.
In an overall comparison, ZSML maintains the level of CMV around the switching frequency, compared with
NTV, while having half its spectrum. OLOM has almost twice as low CMV at switching, retaining amplitudes
under NTV throughout the entire spectrum. OSOM seems to move the amplitudes, seen at other strategies,
to double of switching frequency, while the rest of the spectrum is comparable with NTV-EHE. The RS3N
modulation has superior results to NTV-EHE for entire spectrum. Around switching frequency, it features half
of the CMV, compared to NTV-EHE, and almost the same level compared to ZCM. The performance of RS3N
is comparable with ZCM modulation in terms of spectrum length and CMV levels throughout the entire
frequency range.
5.10.
Comparison of Conductive EMI produced by Modulation Strategies
The theoretical part regarding EMI is described in chapter 2.5.1. An experimental setup has been built in
order to observe the influence of modulation strategy over the EMI. Due to limited resources an alternative
solution has been adopted. This solution is based on [87] and uses a clamp-on current probe for measuring
the common mode current. The current probe used can measure currents with frequencies up to 20 MHz.
Figure 5-11 presents the adopted solution. The probe will add the currents in the same direction and
subtract the one with opposite directions, hence only the common mode current will be measured.
Figure 5-11 – Common Mode Current Measurement [87]
[104]
Chapter 5 – Experimental Validation
Based on this solution experiments were performed on each modulation strategy at its maximum
modulation index. Figure 5-12 presents the conducted EMI, between the inverter and load, in decibels on a
logarithmic scale. All six modulation strategies seem to develop the same EMI, but at a closer look, there are
some differences. The four developed modulation strategies are compared against the classical ones, ZCM
and NTV. The ZCM method has 7 dB less at lower frequencies, compared to NTV, which is constant at 60 dB
up to 1 MHz. After this frequency the difference between these two decreases to 2 dB. The peak for all
strategies is at 2 Mhz. NTV has a peak of 79 dB, while ZCM has 70 dB. Both strategies remain at 50 dB on the
high frequency range, between 3 MHz and 20 MHz.
The proposed strategies have similar results in the low frequency range, amplitude of 57 dB. The peak for al
strategies is around 75-77 dB at 2 MHz, being situated between ZCM and NTV. In the high frequency range,
OLOM, OSOM and ZSML remain at 50 dB. RS3N has lower amplitude between 3 MHz and 20 MHz, 43 dB,
being 7 dB lower than the rest of the modulation strategies.
Comparing all the EMI results it can be seen that OSOM, OLOM and ZSML seem to be situated between ZCM
and NTV. RS3N is situated between ZCM and NTV at low frequency range, while at high frequency range
seem to offer improvements over both.
Figure 5-12 – Conductive EMI Currents Produced by Modulation Strategies
[105]
Chapter 5 – Experimental Validation
[106]
Chapter 6 – Conclusions
6. Conclusions and Future Work
This chapter presents the conclusions regarding the two main objectives: development of modulation
strategies that address DC link balancing and CMV reduction and the hardware design of the three-level NPC
inverter. Further on, future work is stated.
6.1.
Conclusions Regarding the Development of Modulation Strategies
that Address DC Link Balancing and CMV Reduction
Solutions to reduce the common mode voltage and to balance the DC link through modulation strategies
regarding three-level NPC inverter were studied. Throughout the master thesis four modulation strategies
have been developed that address these problems:




OLOM – uses one large, one medium and one zero vector in order to create the reference voltage
vector over each 30° displacement angle.
ZSML – the reference vector comprises all types of stationary vectors. At maximum modulation
index only small, medium and large vectors are used. The zero vector is applied at smaller
modulation indexes and its time is dependent on the amplitude of the reference voltage.
OSOM – on each 30° displacement angle one small, one medium and one zero vector are used to
build the reference vector.
RS3N – uses the nearest three vectors to create the reference vector. The difference from NTV is
that has the switching sequence of three and it is randomized.
All of the developed modulations have the ability to self-balance, but only two can balance the DC link
voltage in case of external event. The balancing capability has been determined as a function of phase
current. At maximum modulation index both ZSML and RS3N have similar capabilities for balancing the
neutral point, but RS3N offers more at smaller modulation indexes than ZSML.
The methods were developed targeting an improved CMV response over the classical modulation strategies.
All methods offer reduced CMV spectrum. Their performance is between ZCM and NTV. Good results are
obtained by RS3N, which offers performance similar to ZCM while preserving the modulation index of NTV
and offering up to 35% balancing capability.
Furthermore, each of these methods was analysed regarding electromagnetic interference. Conductive EMI
has been measured and the results show that OSOM, OLOM and ZSML are situated between NTV and ZCM.
RS3N is as well situated between NTV and ZCM at low frequencies, until 3 MHz, while at high frequency,
over 3 MHz, offers better performance.
[107]
Chapter 6 – Conclusions
By the use of small and medium vectors OSOM can only go at half of the maximum modulation index. The
other three methods have a better utilisation of the bus bar, modulation index equal to one.
All of the developed modulations were validated through simulations and experimental results. All
experimental analysis has been performed on the designed three-level NPC prototype. Based on the analysis
performed on each of them it can be affirmed that all of them offers reduction of the CMV. From the
spectral and CMV analysis it can be affirmed that the best performance is offered by RS3N.
6.2.
Conclusions Regarding Hardware Design of the Three-Level NPC
Inverter
The three-level NPC inverter PCB was design in Altium. The PCB manufacturing had to be done by an
external company based on the source files provided due to the fact that it has four layers and only PCBs
with two layers can be done in AAU laboratories. The assembly, test and all experiments were performed in
AAU laboratories. The PCB features integrated DC link and galvanic isolation between power and control
stage together with mixed analog and digital design. All ADC and PWM signals are shielded against noise by
being buried into the PCB and having ground layers on top and bottom.
The new specialized NPC leg IGBT modules reduce the commutation paths; therefore the high voltage spikes
and noise are reduced. By using these modules the inverter has no overvoltage snubbers and permits an
overall enhanced design.
Furthermore, special attention was paid when sizing the DC link capacitors. They have reduced size, 30%,
and are configured in a bank having a thermally optimal position.
The use of optocoupler based gate drivers with advanced features such as undervoltage lock-out,
desaturation detection and active Miller clamping contribute even more to the reduced size, featuring the
need only for single power supply because the turn-off is performed by the gate driver through the active
Miller clamping. The possibility of current up to 2.5 A together with soft turn-off and isolated fault feedback
make these drivers well suited for this application.
The inverter reduced size is also a consequence of the embedded DSP design in combination with the CPLD
used for management of dead-time and protections. This combination offers flexibility and safety. The
chosen DSP benefits of small form factor, DIMM100 connector, as well as integrated FLASH and RAM
memory with CPU speed up to 150 MHz. The ADC modules have fast sampling, 80ns, and run independently
of the CPU as the ePWM units. Having this property the ePWM gain extra degrees of freedom. Furthermore,
the CPLD features a 100 MHz running frequency and full flexibility in configuring the I/O and extra clocks.
The 3.3V/5V tolerance makes the CPLD a very good choice as it permits a mixed voltage design.
Protections regarding DC link overcurrent, phase overcurrent, DC link voltage out of range, overtemperature
and protection against desaturation events make the design bullet proof. The protections are all fully
[108]
Chapter 6 – Conclusions
adjustable thus providing a flexible hardware platform. The protections were tested and resulted in full
validation of the design. As a feature this protections have an optical fault feedback system through LEDs.
Furthermore, special attention was given to the specifics of the three-level topology such as semiconductor
turn-on and turn-off order. For this concern, turn-off, turn-on and reset procedures are implemented on the
CPLD and validated though experiments as well as the PWM filters. These filters prevent the shoot-through
of the entire inverter and N-P or P-N switching sequence combinations. The start-up behavior of the inverter
was also carefully managing ensuring no destructive device states occur.
Other features such as use of Hall-effect current sensors and RS-232 and CAN communications provide an
enhanced design. The JTAG interfaces for both CPLD and DSP were implemented, thus making the debugging
and onboard programming processes easy.
The code inside the DSP is designed to automatically transfer itself from flash memory into RAM at each
power-up, and run from there in order to optimize the computing speed and algorithm performance.
Conduction losses as well as the switching ones were calculated using a methodology offered by Semikron.
Furthermore, the thermal influence of the voltage regulators, need for gate drivers, were taken into account.
Based on these calculations the thermal resistance was calculated. This design was experimentally validated
through thermal imaging.
6.3.
Future Work
Future work might include:


Standard measurement of Conducted EMI
Measurements and Analysis of Radiated EMI
[109]
Chapter 6 – Conclusions
[110]
Bibliography
[1] Emre Un, "Common Mode Voltage and Current Reduction in Voltage Source Inverter Driven Three
Phase AC Motors," Master Thesis 2007.
[2] Hiralal M. Suryawanshi Mohan M. Renge, "Multilevel Inverter to Reduce Common Mode Voltage in AC
Motor Drives Using SPWM Technique," IEEE Power Electronics, vol. 11, 2011.
[3] Jafar Adabi Firouzjaee, "Remediation Strategies of Shaft and Common Mode Voltages in Adjustable
Speed Drive Systems," School of Engineering Systems, Queensland University of Techology, Queensland,
Australia, Doctor in Philosophy Thesis August 2010.
[4] David Armitage Ewan Morris, "A Guide to Standard Medium Voltage Variable Speed Drives Part 2," ABB,
March 2012.
[5] Steffen Bernet, Peter K. Steimer, Ignacio E. Lizama Jose Rodriguez, "A Survey on NPC Inverters," IEEE
Power Electronics, vol. 57, no. 7, pp. 2219-2230, July 2010.
[6] Firuz Zare Jafar Adabi, "Analysis, Calculation and Reduction of Shaft Voltage in Induction Generators," in
International Conference on Renewable Energy and Power Quality, Valencia, April 2009.
[7] E. Carpaneto A. Boglietti, "Induction Motor High Frequency Model," IEEE, vol. 3, pp. 1551 - 1558,
October 1999.
[8] N. Zargari, Bin Wu, S.Rizzo Sanmin Wei, "Comparison and Mitigation of Common Mode Voltage in
Power Converter Topologies," IEEE Transactions, vol. 3, pp. 1852-1857, November 2004.
[9] Sergio Busquets-Monge, Josep Bordonau, Javier Gago, Davi Gonzalez, Josep Balcells Salvador Alepuz,
"Interfacing Renewable Energy Sources to the Utility Grid Using a Three-Level Inverter," vol. 53, no. 5,
2006.
[10] Dushan Boroyevich Nikola Celanovic, "A Comprehensive Study of Neutral-Point Voltage Balancing
Problem in Three-Level Neutral-Point-Clamped Voltage Source PWM Inverters," IEEE Transactions, vol.
15, no. 2, pp. 242-249, March 2000.
[11] I. Takahashi, H. Akagi A. Nabae, "A New Neutral Point Clamped PWM Inverter," IEEE Transactions on
Industrial Applications, vol. IA-17, no. 5, pp. 518-523, 1981.
[12] T. Ohnishi, T. Suzuki R. Rojas, "An Improved Voltage Vector Control Method for Neutral Point Clamped
Inverters," IEEE Transactions on Power Electronics, vol. 10, no. 6, pp. 666-672, 1995.
[I]
[13] G. H. Cho H. L. Liu, "Three-Level Space Vector PWM in Low Index Modulation Region avoiding Narrow
Pulse Problem," IEEE Transactions on Power Electronics, vol. 9, no. 5, pp. 481-486, 1994.
[14] Thomas A. Lipo Madhav D. Manjrekar, "A hybrid multilevel inverter topology for drive applications,"
IEEE, 1998.
[15] Riccardo Ramin Marco Di Lella, "The Low and Medium Power Module for Hogh Integrated Applications,"
Semikron , Application Note 2008.
[16] Peter Steimer Peter Barbosa, "ANPC Multi Level Converters," IEEE, 2005.
[17] Fang Zheng Pend Jing-Sheng Lai, "Multilevel Converters – A New Breed of Power Converters," vol. 32,
no. 3, 1996.
[18] Andrzej Adamczyk Maciej Swierczynski, "Modulation Of Three-Level Inverter With Common-Mode
Voltage Elimination And DC-Link Balancing," Master Thesis 2008-2009.
[19] Bin Wu, High - Power Converters and Drives.: John Wiley & Sons, 2006.
[20] Thomas A. Lipo D. Grahame Holmes, "Pulse Width Modulation for Power Converters - Principles and
Practice".
[21] Pramod Agrawal Kalpesh H. Bhalodi, "Space Vector Modulation With DC-Link Voltage Balancing Control
For Three-Level Inverters," 2006.
[22] Firuz Zare Hod Ghoreishy, "A New Common-mode Voltage Reduction Technique for Multilevel
Inverters," 2007.
[23] Abolfazi Vahedi M. Ebrahim Adabi, "A Common-mode Voltage Reduction Strategy for a DFIG with a
Three-Level Back-to-Back Converter," 2011.
[24] Fei Wang, "Sine-triangle versus space-vector modulation for three-level PWM voltage source inverters,"
IEEE Transactions on Power Electronics, vol. 38, no. 2, pp. 500-506, March/April 2002.
[25] Danwei Wang Kelinang Zhou, "Relationship between space-vector modulation and three-phase carrierbased PWM: a comprehensive analysis," IEEE Transactions on Power Electronics, vol. 49, no. 1, pp. 1861986, February 2002.
[26] Haibing Hu, Zhengyu Lu Wenxi Yao, "Comparison of Space Vector Modulation and Carrier-Based
Modulation of Multilevel Inverter," IEEE Transactions on Power Electronics, vol. 23, no. 1, pp. 45-51,
January 2008.
[27] Dorin O. Necsu, "Space Vector Modulation – An Introduction," IEEE Transactions, pp. 1583-1892, 2001.
[28] Seong R. Lee, Fred C. Lee Dong Ho Lee, "An Analysis Of Midpoint Balance For The NPC Three Level VSI,"
[II]
vol. vol. 1, May 1998.
[29] B. Wu D. W. Feng, "Space Vector Modulation for Neutral Point Clamped Multilevel Inverter with Even
Order Harmonic Elimination," in Canadian Conference on Electrical and Computer Engineering, 2004, pp.
1471-1475.
[30] Annette von Jouanne, Shaoan Dai, Alan K. Wallace, Fei Wang Haoran Zhang, "Multilevel Inverter
Modulation Schemes to Eliminate Common-Mode Voltages," vol. 36, no. 6, 2000.
[31] Slododan Krstic, James Meer, Giri Venkataramanan Ashish Bendre, "Comparative Evaluation of
Modulation Algorithms for Neutral-Point-Clamped Converters," IEEE Transactions on Industry
Applications, vol. 41, no. 2, pp. 634-643, March/April 2005.
[32] Yunping Zou, Zhan Wang, Hongyuan Jin Lei Lin, "Modelling And Control of Neutral-Point Voltage
Balancing Problem In Three-Level NPC PWM Inverter," IEEE, 2005.
[33] Environmental Potentials Research and Development Department, "Reducing Motor Shaft Voltages,"
800.500.7436,.
[34] R. J. Kerkman, D. W. Schlegel, and G. L. Skibiniski J. M. Erdman, "Effect of PWM inverters on ac motor
bearing currents and shaft voltages," vol. 32, no. 2, Mar./Apr. 1996.
[35] Ahmet M. Hava Emre Un, "A Near-State PWM Method With Reduced Switching Losses and Reduced
Common Mode Voltage fot Three-Phase Voltage Source Inverters," vol. 45, no. 2, March/April 2009.
[36] Elizabeth S. Galano Paul I. Nippes, "Understanding Shaft Voltage and Grounding Currents of Turbine
Generators".
[37] Firuz Zare, "EMI in Modern AC Motor Drive Systems," IEEE, 2009.
[38] Andrzej Trzynadlowski, "Active Attenuation of Electromagnetic Noise in an Inverter Fed Automotive
Electric Drive System ," vol. 21, no. 3, May 2006.
[39] L. Tihanyi, "Electromagnetic Compatibility in Power Electronics," IEEE Press, 1995.
[40] T. Kume M. Mysore, "Common mode current attenuation techniques for use with PWM drives," IEEE
Transactions on Power Electronics, vol. 16, no. 2, 2001.
[41] H. Akagi S. Ogasawara, "An active circuit for cancellation of common mode voltage generated by a PWM
inverter," IEEE Transactions on power electronics, vol. 13, no. 5, 1998.
[42] T. Lipo A. Julian, "Elimination of common-mode voltage in three-phase sinusoidal power Converters,"
vol. 14, no. 5, 1999.
[43] S. Guttowski, and K. Heumann H. Jorgensen, "Reduction of conducted line emissions in voltage fed
[III]
pulsed inverters by using suppressor capacitors in the intermediate circuit," , 1997.
[44] Hirofumi Akagi and Shunsuke Tamura, "A Passive EMI Filter for Eliminating both Bearing and Ground
Leakage Current from an Inverter Driven Motor," IEEE TRANSACTIONS ON POWER ELECTRONICS, vol. 21,
no. 5, SEPTEMBER 2006.
[45] Marcin Zelechowski, "Space Vector Modulated - Direct Torque Controlled (DTC-SVM) Inverter - Fed
Induction Motor," Warsaw University of Technology, Warsaw - Poland, PhD Thesis 2005.
[46] Frede Blaabjerg, John K. Pederson Michael M. Bech, "Random Modulation Techniques with Fixed
Switching for Three-Phase Power Converters," IEEE Transactions on Power Electronics, vol. 15, no. 4,
July 2000.
[47] Joe Bond Michael Salcome, "Selecting Film Bus Capacitors For High Performance Inverter Applications,"
IEEE, no. May 2009, pp. 1692-1699, May 2009.
[48] T.F. Chan, Y. K. Wong, S.L. Ho K. L. Shi, "Modeling and Simulation of the Three-Phase Induction Motor
using Simulink," IEEE, vol. 36, pp. 163-172, 1997.
[49] Semikron, "SK50MLI065," Datasheet 2008.
[50] Bernhard Koenig, Martin Hansmann, Wolfgang Nichtl-Pecher Fryderyk Kozlowski, "Enhanced 4th
Generation CAL Diode for Highly Efficient Applications," 2011.
[51] Ingo Staudt, "3L NPC & TNPC Topology," Texas Instruments, Application Note 2012.
[52] Jan Sundvall Mads Christian Pilgaar Vaerens, "Three-level Inverter for Medium Level Voltage Using
Series Connected IGBTs," Aalborg University, Aalborg, Master Thesis 2008.
[53] Avago, "ACPL - 332j, AV02 - 0120EN," Datasheet 2011.
[54] (2012) www.uk.farnell.com.
[55] Aimtec, "Connecting Converters in Series," Application Note.
[56] STMicroelectronics, "L78Sxx, L78SxxC," Datasheet 2148 Rev 5, February 2012.
[57] Avago, "Desaturation Fault Detection," Application Note 5324 AV02-0258EN, January 9, 2012.
[58] Markus Hermiwille, "Gate Resistor - Principles and Applications," Application Note 11283450, 2007.
[59] Avago, "Active Miller Clamp," Application Note 5314.
[60] Avago, "“Soft” Turn-Off Feature," Application Note 5315 AV02-0073EN, July 21, 2010.
[61] Allegro, "Fully integrated, Hall Effect-Based Linear Current Sensor IC with 3 kV RMS Voltage Isolation
[IV]
and a Low-Resistance Current Conductor," ACS756 Datasheet.
[62] AVX, "NTC Thermistors, S-TNTC3M406-N," Datasheet.
[63] Texas Instruments, "TLC372, LinCMOS Dual Differential Comparators," Dallas, Texas, USA,.
[64] Texas Instruments, "Analog Comparator, EFM32," Application Note AN0020_rev1.04 21 October 2011.
[65] Texas Instruments, "SN54F21, SN74F21 Dual 4-Input Positive AND Gates," Datasheet.
[66] Texas Instruments, "OPA343, OPA2343, OPA4343, Single Supply, Rail-to-Rail Operational Amplifiers,"
Datasheet SBOS090A,.
[67] Texas Instruments, "Pradeep Shinde, Hardware Design Guidelines for TMS320f28xx and TMS320f28xxx
DSCs," Application Report SPRAAS1B, August 2011.
[68] STMicroelectronics, "Small Signal Schotty Diodes, BAT54," Doc ID 5505 Rev 10, October 2009.
[69] Traco Power, "DC/DC Converters, TEL 3 Series, 3 Watt,".
[70] Texas Instruments, "Ultralow-noise, High PSRR, Fast, RF, 500 mA, Low Dropout Linear Regulators,"
Datasheet.
[71] Texas Instruments, "Dual digital isolators, ISO7221," Datasheet.
[72] Texas Instruments, "Differential bus transceivers, SN75LBC176," Datasheet.
[73] National Instruments , "How to do a serial loopback test," Datasheet - Tutorial 3 August 2011.
[74] Texas Instruments, "EMC Optimized CAN Transciever, SN65HVD1050, SLL532-B," Datasheet December
2005.
[75] National Instruments, "Controller Area Network (CAN) Interfaces," 2005_5388_151_101_D,.
[76] Association Connecting Electronics Industries, IPC-2221A. Northbrook, Illinois, USA: Association
Connecting Electronics Industries, 2003.
[77] Steffen Bernet Thomas Brucker, "Estimation and Measurement of Junction Temperatures in a Three
Level Voltage Source Converter," IEEE Transactions on Power Electronics, vol. 22, no. 1, January 2007.
[78] Riccardo Ramin Marco Di Lella, "IGBTs for 3-level inverters," Application Note ISSN: 1863-5598, 2008.
[79] Rodrigo Alvarez, Ingo Staudt, Steffen Bernet Michael Sprenger, "Characterisation of a New 1.2kV IGBT
3L-NPC Phase-leg Module for Low Voltage Applications," IEEE , pp. 1-10, September 2011.
[80] Thomas P. Abraham, Characterization and Development of Advanced Heat Transfer Technologies.
[V]
Washington: U.S. Department of Energy, Energy Efficiency and Renewable Energy, 2009.
[81] Bob Wolbert, "Design Considerations for 5V to 3.3V Pass Regulators," Application Note 1997.
[82] Texas Instruments, "Low Dropout Linear Regulators," Application Note 2006.
[83] Semikron, "SKiM Modules Technical Explanations," Application Note 2011.
[84] Texas Instruments, "TMS320x2833x, 2823x Enhanced Pulse Width Modulator (ePWM) Module," Texas
Instruments, Reference Guide 2009.
[85] Texas Instruments, "TMS320x2833x Analog-to-Digital Converter (ADC) Module," Texas Instruments,
Reference Guide 2007.
[86] Zhang Xi, "How to calculate and minimize the dead time requirement for IGBTs properly," Infineon
Technologies AG, Munchen, Germany, Application note 2007.
[87] Jacobus Johannes Engelbrecht, "Methods to Measure and Limit Electromagnetic Interference, with
Reference to Power Systems and Satellite Earth Stations," Rand Afrikaans University, Master Thesis
2004.
[VI]
Appendix 1 – Project Proposal
Appendix 1: Project Proposal
#16 Student Project
Project Title
Modulation of three-level inverter with common-mode voltage elimination and DC-link
balancing
Target Group
M.Sc.E.E. or B.Sc.E.E. graduate students
Background
Conventional two-level voltage source inverters (VSI) generate common-mode voltage within
the motor windings, which may cause motor failures due to bearing currents. Further, due to
the capacitive coupling between the stator winding and the grounded motor frame, a
common mode leakage current will flow, resulting in significant common-mode EMI. By use
of a three-level inverter, c.f. Fig 1. and by use of only six of the active switch vectors, the
common-mode voltage can be eliminated. (The common-mode voltage elimination is
achieved at the expense of a reduction in the voltage transfer ratio, which becomes 0.866.)
This modulation scheme was proposed by [1] where the voltage levels within the three-level
inverter were achieved from independent DC-sources. However, in three-level converter
structures, where the voltage levels are obtained by series connected capacitors, a DC-link
voltage problem might occur by which an excessive high voltage might be applied to the
switching devices (only for the topology in Fig. 1a). Further, the three-level converter might
be unable to synthesize the reference voltage if too large voltage unbalance occurs. Hence,
besides avoiding the common mode voltage, the modulation of the three-level converter also
has to address the voltage unbalance between the upper and the lower switches.
s1A
D1A
s1B
D1B
s1C
D1C
s2A
s2B
s2C
s1A
s2A
C1
N
s3B
D2B
s3C
D2C
s4A
s4B
s4C
s2B
s2C
N
VD C
s3A
D2A
s1C
C1
VDC
C2
s1B
D1A
D1B
D1C
D2A
D2B
D2C
s3B
s3C
C2 s
s4B
s4C
3A
s4A
A
B
A
C
a)
B
C
b)
Fig. 1. Three-level neutral point clamped inverters. a) Conventional topology. b) Modified
topology.
[1] Haoran Zhang and Annette von Jouanne and Alan Vallace, Multilevel inverter
modulation schemes to eliminate common-mode voltages, Transaction on industry
[VII]
Appendix 1 – Project Proposal
applications, Vol. 36, No. 6, pp. 1645-1653, 2000
Problem Statement:
Based on the problems listed above, the problem statement for this project becomes:
Development of a modulation scheme that addresses both common-mode
voltage elimination and DC-link balancing.
Project Content
Besides paying attention to the stated problem, the project could/should include the
following issues:
• Hardware design of the three-level inverter
• Development of a simulation model to test different modulation strategies before
implementation.
• d-SPACE or DSP implementation of the modulation/control of the three-level converter.
• Comparison of the emitted common-mode EMI from conventional modulation schemes
and the developed modulation scheme.
Analysis of the DC-link unbalance problem.
[VIII]
Appendix 2 – Switching Tables
Appendix 2: Switching Tables for All Methods
In this appendix the switching table from each modulation strategy is presented. The first implemented
method was the classical NTV –EHE for comparison with the developed ones. The switching table for NTVEHE is presented below.
Sector I
Region 1a
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OON
⃗⃗⃗⃗⃗⃗
ONN
⃗⃗⃗⃗⃗⃗
OON
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
POO
Region 1b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OON
OOO
POO
PPO
POO
OOO
OON
Region 2a
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗
PON
⃗⃗⃗⃗⃗⃗ OON
⃗⃗⃗⃗⃗⃗
ONN
⃗⃗⃗⃗⃗⃗ OON
⃗⃗⃗
PON
⃗⃗⃗⃗⃗⃗
POO
Region 2b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OON
PON
POO
PPO
POO
PON
OON
Region 3
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
POO
PON
PNN
ONN
PNN
PON
POO
Region 4
⃗⃗⃗⃗⃗⃗ OON
⃗⃗⃗
PON
⃗⃗⃗⃗⃗⃗ PPN
⃗⃗⃗⃗⃗⃗ PPO
⃗⃗⃗⃗⃗⃗ PNN
⃗⃗⃗
PON
⃗⃗⃗⃗⃗⃗ OON
Sector II
Region 1a
⃗⃗⃗⃗⃗⃗
OON
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗⃗⃗⃗
PPO
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OON
Region 1b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OPO
OOO
OON
NON
OON
OOO
OPO
Region 2a
⃗⃗⃗⃗⃗⃗ OON
⃗⃗⃗
OPN
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗⃗⃗⃗
PPO
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗
OPN
⃗⃗⃗⃗⃗⃗ OON
Region 2b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OPO
OPN
OON
NON
OON
OPN
OPO
Region 3
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OON
OPN
PPN
PPO
PPN
OPN
OON
Region 4
⃗⃗⃗⃗⃗⃗ OPO
⃗⃗⃗
OPN
⃗⃗⃗⃗⃗⃗ NPN
⃗⃗⃗⃗⃗⃗ NON
⃗⃗⃗⃗⃗⃗ NPN
⃗⃗⃗
OPN
⃗⃗⃗⃗⃗⃗ OPO
Sector III
Region 1a
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗⃗⃗⃗
NON
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OPO
Region 1b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
NOO
OOO
OPO
OPP
OPO
OOO
NOO
Region 2a
⃗⃗⃗⃗⃗⃗
OPO
⃗⃗⃗
NPO
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗⃗⃗⃗ NON
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗
NPO
⃗⃗⃗⃗⃗⃗
OPO
Region 2b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
Sector IV
[IX]
NOO
NPO
OPO
OPP
OPO
NPO
NOO
Region 3
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OPO
NPO
NPN
NON
NPN
NPO
OPO
Region 4
⃗⃗⃗⃗⃗⃗ NOO
⃗⃗⃗
NPO
⃗⃗⃗⃗⃗⃗ NPP
⃗⃗⃗⃗⃗⃗ OPP
⃗⃗⃗⃗⃗⃗ NPP
⃗⃗⃗
NPO
⃗⃗⃗⃗⃗⃗ NOO
Appendix 2 – Switching Tables
Region 1a
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗⃗⃗⃗
OPP
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
NOO
Region 1b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OOP
OOO
NOO
NNO
NOO
OOO
OOP
Region 2a
⃗⃗⃗⃗⃗⃗
NOO
⃗⃗⃗⃗⃗⃗
NOP
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗⃗⃗⃗
OPP
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗⃗⃗⃗
NOP
⃗⃗⃗⃗⃗⃗
NOO
Region 2b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OOP
NOP
NOO
NNO
NOO
NOP
00P
Region 3
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
NOO
NOP
NPP
OPP
NPP
NOP
NOO
Region 4
⃗⃗⃗⃗⃗⃗ OOP
⃗⃗⃗⃗⃗⃗ NOP
⃗⃗⃗⃗⃗⃗ NNP
⃗⃗⃗⃗⃗⃗ NNO
⃗⃗⃗⃗⃗⃗ NNP
⃗⃗⃗⃗⃗⃗ NOP
⃗⃗⃗⃗⃗⃗ OOP
Sector V
Region 1a
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
ONO
⃗⃗⃗⃗⃗⃗
NNO
⃗⃗⃗⃗⃗⃗
ONO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
OOP
Region 1b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗
⃗⃗⃗⃗⃗⃗
ONO
OOO
OOP
POP
OOP
OOO
ONO
Region 2a
⃗⃗⃗⃗⃗⃗
OOP
⃗⃗⃗⃗⃗⃗
ONP
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ NNO
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗
ONP
⃗⃗⃗⃗⃗⃗
OOP
Region 2b
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
ONO
ONP
OOP
POP
OOP
ONP
ONO
Region 3
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
⃗⃗⃗⃗⃗⃗
OOP
ONP
NNP
NNO
NNP
ONP
OOP
Region 4
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ ONP
⃗⃗⃗⃗⃗⃗ PNP
⃗⃗⃗⃗⃗⃗ POP
⃗⃗⃗⃗⃗⃗ PNP
⃗⃗⃗⃗⃗⃗ ONP
⃗⃗⃗⃗⃗⃗ ONO
Sector VI
Region 1a
⃗⃗⃗⃗⃗⃗
ONO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗⃗⃗⃗
POP
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗
ONO
Region 1b
⃗⃗⃗⃗⃗⃗ POO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ ONN
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗
OOO
⃗⃗⃗⃗⃗⃗ POO
Region 2a
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗
PNO
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗⃗⃗⃗
POP
⃗⃗⃗⃗⃗⃗
POO
⃗⃗⃗⃗⃗⃗
PNO
⃗⃗⃗⃗⃗⃗ ONO
Region 2b
⃗⃗⃗⃗⃗⃗ POO
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ ONN
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ POO
Region 3
⃗⃗⃗⃗⃗⃗ ONO
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ PNP
⃗⃗⃗⃗⃗⃗ POP
⃗⃗⃗⃗⃗⃗ PNP
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ ONO
Region 4
⃗⃗⃗⃗⃗⃗ POO
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ PNN
⃗⃗⃗⃗⃗⃗ ONN
⃗⃗⃗⃗⃗⃗ PNN
⃗⃗⃗⃗⃗⃗ PNO
⃗⃗⃗⃗⃗⃗ POO
Furthermore, another classical method was implemented for its ability to reduce the CMV. The switching
table is presented below.
ZCM switching sequence
Sector 1
Sector 2
Sector 3
Sector 4
[X]
Sector 5
Sector 6
Appendix 2 – Switching Tables
The first method developed modulation strategy is OLOM. This method is divided into 12 sectors with a
displacement angle of 30°. The switching table is presented below.
OLOM Switching table
Sector 1
Sector 2
Sector 3
Sector 4
Sector 5
Sector 6
Sector 7
Sector 8
Sector 9
Sector 10
Sector 11
Sector 12
Next, another method arises, OSOM. This method is divided into 12 sectors as well as OLOM, but uses small,
medium and zero vectors in order to crate the reference vector. Its table can be seen below.
OSOM switching sequence
Sector 1
Sector 2
Sector 3
Sector 4
Sector 5
Sector 6
Sector 7
Sector 8
Sector 9
Sector 10
Sector 11
Sector 12
Theory states that if all stationary vectors are used the number of levels, in the phase voltage, is maximum.
The switching table for ZSML, when in natural balancing, is presented below.
ZSML switching sequence for natural balancing
Region 1
Region 2
Sector 1
Sector 2
Sector 3
[XI]
Appendix 2 – Switching Tables
Sector 4
Sector 5
Sector 6
Furthermore, if the DC link is unbalanced due to an external event the next switching tables are going to be
used until the perturbation is eliminated.
ZSML switching sequence in balancing mode – P and N type tables
Region 1 – P type
Region 2 – P type
Region 1 – N type
Region 2 – N type
Sector 1
Sector 2
Sector 3
Sector 4
Sector 5
Sector 6
Based on nearest three vectors idea, another method was developed. This method randomises the switching
table in order to reduce the CMV. The switching sequence can be seen below. As ZSML, this method has the
ability to balance the DC link in case of an external event.
RS3N switching sequence when in natural balancing mode
Sector 1
Sector 2
Sector 3
Sector 4
Sector 5
Sector 6
Region 1
Region 2
Region 3
Region 4
RS3N switching sequence when in balancing mode
Sector 1
Sector 2
Sector3
Sector 4
Sector 5
Region 1 – P Type
Region 2 – P Type
Region 3 – P Type
Region 4 – P Type
Region 1 – N Type
Region 2 – N Type
Region 3 – N Type
Region 4 – N Type
[XII]
Sector 6
Appendix 3 – Experimental Setup Data
Appendix 3: Experimental Setup Data
When the experiments were performed the following devices were used as a part of the setup:























2x SM 300-5, 300V, 5A Power Supplies
1x SM 600-10, 600V, 10A Power Supply
1x GwInstek GPS-4303, 12v Power Supply
1x Tektronix DPO 2014 Digital Phosphor Oscilloscope
3x Tektronix P5200 High Voltage Differential Probe 130v / 1300v
1x Tektronix TCP0150 Current Probe, 150A, 20 MHz
1x Fluke 179 True RMS Multimeter
4x Tektronix P2221 Voltage Probe
1x Digilent HS1 JTAG Emulator for CPLD
1x Signum JTAGJET-C2000 JTAG Emulator for DSP
1x National Instruments NI cDAQ-9172 Acquisition System Chasis
1x NI 9227 Quad Current Sensor Module
2x ASEA Load Inductor, 3 kVAr
2x ASEA 5514 152-8, 220/95 V, 4000 ohm, Load Resistor, 4.5 / 2 kW,
1x Zentro Elektric Electronic Load, EL1000/800/20, Vi=230v, 50hz, 0.2A, V0=800v, 20A, 1000W.
2x Danotherm 23 E, 12.5 ohm, 13.6 A Variable Resistors
1x Danotherm 23 E, 2.5 ohm, 13.6 A Variable Resistor
1x Danotherm 23 E, 5000 ohm, 0.33 A Variable Resistor
1x Danotherm 23 D, 500 ohm, 0.96 A Variable Resistor
1x ABB Induction Motor, M2VA80C-2 3GVA081003-ASB, Wye Connection, 380-420V, 50hz, 2840
rpm, 1.5 kW, 3.4/5.7 A, cos(fi)=0.83
1x Transtecno DC Motor, EC350.240, 24V, 29.4A, 3000 rpm, 1.57 Nm, 0.5 kW
1x Forward Looking Infra-Red (FLIR) Camera – Thermal Camera
Three Phase Switch, 72502E, AAU
[XIII]
Appendix 4 – CPLD/DSP Pin Assignment
Appendix 4: CPLD/DSP Pin Assignment
When the modulation strategies have been developed on the DSP, the pin assignment had to be performed.
This was done accordingly to the DSP hardware design guidelines [67].
DSP Pin Assignment
Pin
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Function
3V3 ISO
RXA_ISO
NC
NC
NC
GND ISO
ADC PHASE A
GND A
ADC PHASE B
GND A
ADC PHASE C
GND A
ADC DC+
GND A
ADC DCGND A
GND A
NC
GND A
NC
Pin
No.
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Function
GND A
NC
EPWM 1A
EPWM 2A
EPWM 3A
EPWM 4A
GND D
EPWM 5A
EPWM 6A
NC
GPIO 84
GPIO 86
NC
NC
NC
NC
GND D
NC
NC
NC
Pin
No.
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Pin
No.
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Function
NC
GPIO 87
NC
CAN RXA
NC
NC
GND D
TCK
TMS
EMU1
3V3 ISO
TXA ISO
NC
NC
NC
GND ISO
GND A
GND A
GND A
GND A
Pin
No.
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
Function
GND A
GND A
GND A
GND A
GND A
GND A
GND A
NC
GND A
NC
GND A
NC
NC
NC
NC
NC
5V D
TXB
RXB
NC
Function
GPIO 85
5V D
NC
NC
NC
NC
5V D
NC
NC
NC
NC
5V D
NC
CAN TXA
TO DSP
5V D
TDI
TDO
TRSTn
EMU0
The CPLD pin configuration can be seen in the following table.
CPLD Pin Assignment
Pin
No.
1
2
3
4
5
6
7
8
9
10
11
Function
PWM_out 4
PWM_out 3
PWM_out 12
PWM_out 11
PWM_out 6
PWM_out 5
GCK3
PWM_in 6
PWM_in 5
GND
PWM_in 4
Pin
No.
12
13
14
15
16
17
18
19
20
21
22
Function
PWM_in 3
PWM_in 2
PWM_in 1
TDI
TMS
TCK
Buffer Enable
To DSP
Fault Gate Driver
Vcc +3V3
NC
Pin
No.
23
24
25
26
27
28
29
30
31
32
33
The following figure shows how the control signal path.
[XIV]
Function
GND
DC OV
DC OC
Demux C
Demux B
Demux A
NC
TDO
GND
Vcc +3V3
Over current
Pin
No.
34
35
36
37
38
39
40
41
42
43
44
Function
Over temp B
Over temp A
PWM_out 8
PWM_out 7
PWM_out 2
GSR
GTS2
Vcc +3V3
PWM_out 1
PWM_out 10
PWM_out 9
Appendix 4 – CPLD/DSP Pin Assignment
Signal Path from DSP to gate drives
[XV]
Appendix 4 – CPLD/DSP Pin Assignment
[XVI]
Appendix 5 – CPLD Functional Schematic
Appendix 5: CPLD Functional Schematic
[XVII]
Appendix 4 – CPLD/DSP Pin Assignment
Appendix 5: CPLD
Functional Schematic
[XVIII]
Appendix 6 – PCB Photos
Appendix 6: PCB Photos
[XIX]
Appendix 6 – PCB Photos
[XX]
Appendix 7 – PCB Layers
Appendix 7: PCB Layers
Layer 1
[XXI]
Appendix 7 – PCB Layers
Appendix 7: PCB Layers
Layer 1
[XXII]
Appendix 7 – PCB Layers
Layer 2
[XXIII]
Appendix 7 – PCB Layers
Appendix 7: PCB Layers
Layer 2
[XXIV]
Appendix 7 – PCB Layers
Layer 3
[XXV]
Appendix 7 – PCB Layers
Appendix 7: PCB Layers
Layer 3
[XXVI]
Appendix 7 – PCB Layers
Layer 4
[XXVII]
Appendix 7 – PCB Layers
Appendix 7: PCB Layers
Layer 4
[XXVIII]
Appendix 8 – Electrical Schematic
Appendix 8: Electrical Schematic
[XXIX]
Appendix 8 – Electrical Schematic
Appendix 8: Electrical
Schematic
[XXX]
Appendix 9 – Bill Of Materials
Appendix 9: Bill of Materials
NO.
Value
Order Code
Provider
Manufactured
Manufactured Code
Pieces
1
Capacitor 10pF
499110
farnell
AVX
06035A100JAT2A
1
2
Capacitor 100pF
1414603
farnell
Kemet
C0603C101J5GACTU
19
3
Capacitor 1000pF
1414605RL
farnell
Kemet
C0603C102J5GACTU
12
4
Capacitor 0.01uF
722236
farnell
Yageo
CC0603KRX7R9BB103
3
5
Capacitor 0.1uF
1759122RL
farnell
Multicorp
MCCA000255
65
6
Capacitor 0.33u
1870967
farnell
Multicorp
MCMR50V334M4X7
12
7
Capacitor 2.2uF
1845734
farnell
Murata
1845734
6
8
Capacitor 10uF
1458902
farnell
Yageo
CC0603MRX5R5BB106
15
9
Capacitor 10uF
1539492
farnell
Panasonic
EEEFPV100UAR
2
10
Capacitor 33uF
1870963
farnell
Multicomp
MCMR35V336M6.3X7
2
11
Capacitor 330uF
1198688
farnell
Panasonic
EETUQ2W331DA
6
12
1559131
farnell
Taiwan Semi
ES1JL
12
9556923
farnell
On Semi
MBR0540T1G
12
9801510
farnell
BAT54SFILM
10
1863142
farnell
STMicroelectronics
TAIWAN
SEMICONDUCTOR
B0530W
24
16
Diode 35 ns
Diode Schottjy
40V 0.5A
Diode Schottjy
BAT54S
Diode Schottky
30V, 0.5A
Diode Small
Signal
8150192RL
farnell
Taiwan Semi
TS4148 RZG
4
17
Diode Zener 10V
1431280RL
farnell
On Semi
MMSZ5240BT1G
12
18
x
x
x
x
2
DIMM100
mouser
Molex
x
x
x
x
1
425-8720
rs-online
Weidmuller
PM 5.08/2/90 3.5 SW
1
692-0553
rs-online
Amphenol
ESPM03200
2
23
Connector DE9
Connector
DIMM100
Connector 39 pin
header
Connector
Header 2H
Connector
Headere 3H
IC CAN
Transciever
1220984
farnell
Texas Instruments
SN65HVD1050D
1
24
IC Comparator
660-6783
rs-online
Texas Instruments
TLC372QDRG4
10
25
IC CPLD
1193232
farnell
xilinx
XC9572XL-10PCG44C
1
26
IC Current Sensor
1791390
farnell
Allegro
ACS756SCA-050B-PFF-T
5
27
IC Demultiplexer
662-8617
rs-online
Texas Instruments
SN74LVC138ADRG4
1
28
IC Digital Isolator
660-7679
rs-online
Texas Instruments
ISO7221BDG4
2
29
IC Gate Driver
1640541
farnell
Avago
ACPL-332J-000E
12
30
IC Octal Buffer
663-2899
rs-online
Texas Instruments
SN74LVC540ADWG4
2
31
IC OpAmp
461-8526
rs-online
Texas Instruments
OPA2343UA
3
32
IC OpAmp
9560483
farnell
Linear Technology
LT1366CS8#PBF
1
33
478-8653
rs-online
IQD
LFSPXO018038
1
34
IC Quartz
IC RS 485
Transciever
527-877
rs-online
Texas Instruments
SN75LBC176DRG4
1
35
IC Triple Input
1739952
farnell
Texas Instruments
CD74HCT11M
2
13
14
15
19
20
21
22
[XXXI]
87630-1001
1
Appendix 9 – Bill Of Materials
AND Gate
36
37
IC Voltage
Regulator 18V
IC Voltage
Regulator 3.3V
L78S18CV
9756183
farnell
ST
12
620-1899
rs-online
Texas Instruments
TPS79533DCQ
3
38
Resistor 0
1692540
farnell
Vishay
CRCW12060000ZSTA
44
39
Resistor 40.2
1501453RL
farnell
Te Conect.
24
40
Resistor 100
9238360RL
farnell
Yageo
RP73D2B40R2BTG
RC0603FR-07100RL
41
Resistor 120
223-2136
rs-online
TE Connectivity
CRG1206F120R
2
42
Resistor 270
1577598RL
farnell
Panasonic
ERA3AEB271V
5
43
Resistor 330
740-8931
rs-online
Bourns
19
44
Resistor 470
9331239RL
farnell
Multicorp
45
Resistor 2.7K
9337288RL
farnell
Multicomp
CR0603-JW-331GLF
MC 0.063W 0603 1%
470R
MC 0.125W 1206 5%
2K7
46
Resistor 4.7k
x
x
x
x
3
47
Resistor 6.8k
1717690RL
farnell
Panasonic
ERA3APB682P
2
48
Resistor 10k
1469748RL
farnell
Vishay
CRCW060310K0FKEA
44
49
Resistor 20k
1160374
farnell
Welwyn
PCF0603R 20KB.T1
27
50
Resistor 22k
x
x
x
x
3
51
Resistor 30k
1841783RL
farnell
Panasonic
ERA8AEB303V
4
52
Resistor 47k
1697398
farnell
Te
CPF0603B47KE1
12
53
Resistor 470k
1841811
farnell
Panasonic
ERA8AEB474V
8
54
1841813
farnell
Panasonic
ERA8AEB564V
4
691-2612
rs-online
Bourns
3302W-3-203E
9
729-9673
rs-online
Panasonic
EVM2WSX80B15
6
57
Resistor 560k
Potentiometer
20k
Potentiometer
100k
Potentiometer
200k
729-9676
rs-online
Panasonic
EVM2WSX80B25
5
58
Thermistor
697-4588
rs-online
AVX
NJ28RA0104F
3
59
LED Green
1466000
farnell
Dialight
5988270107F
2
60
1465997
farnell
Dialight
5988210107F
5
61
LED Red
Push Button Green
1550259
farnell
Multicorp
TS0B26
1
62
Push Button - Red
1550258
farnell
Multicorp
TS0B23
1
63
DCDC 12 -> +-12
689-5236P
rs-online
Murata
NMK1212SC
13
64
DCDC 12 -> 5V
396-5146
rs-online
Traco
TEL 3-1211
3
65
IGBT Module
X
semikron
Semikron
SK50MLI065
3
66
ControlCard DSP
X
ti
Texas Instruments
x
1
67
Heatsink
148121
farnell
H S MARSTON
96CN-02500-A-200
1
68
PCB
X
printline
printline.dk
x
1
55
56
[XXXII]
17
1
4
Appendix 10 – Paper
Appendix 10: Paper
[XXXIII]
Appendix 10 – Paper
[XXXIV]
Appendix 10 – Paper
[XXXV]
Appendix 10 – Paper
[XXXVI]
Appendix 10 – Paper
[XXXVII]
Appendix 10 – Paper
[XXXVIII]
Appendix 10 – Paper
[XXXIX]
Appendix 10 – Paper
[XL]
Appendix 10 – Paper
Appendix 11: Contents of the CD
The CD will contain the following folders and documents:





Report.
CPLD Program ISE Design Suite: this folder contains the CPLD program that has integrated
deadtime programming and protections.
Developed Modulation Strategies – Matlab Simulation: this folder contains the simulations
regarding classical and developed modulation strategies.
Modulation Strategies – DSP Code Composer C++: this folder contains the C++ code
implemented into DSP regarding the classical and developed modulation strategies,
NPC Inverter Design – Altium: the PCB layout of the three level NPC converter designed in
Altium.
[XLI]
Appendix 4 Report - Sensor less Control of PMSM Using Three Level NPC Converter
This report continues the work of Appendix 3, but addressing the operation of the DeepWind generator
(referred to as Permanent Magnet Synchronous Machine in the report). A second small scale inverter was
built for testing with the small scale generator prototype previously built in the DeepWind project to
validate the equations used in the generator design tool.
As the converter has to control the generator in various modes of operation, many of these are simulated
and tested in the laboratory.
It was assumed that the wind turbine control system issues a speed reference to the converter control, as
this is the only way to control the Darreius wind turbine that has no equipment to change the pitch of the
blades. The converter controller then determines the corresponding response of the converter and controls
the converter accordingly.
Author: Florin Valentin Traian Nica
5/27/2014
AALBORG
UNIVERSITY
SENSORLESS CONTROL OF PMSM
USING THREE LEVEL NPC CONVERTER
Student | Florin Valentin Traian Nica
Title:
Semester:
Semester theme:
Converters
Project period:
ECTS:
Supervisor:
Project group:
Sensorless control of PMSM using three level NPC converter
10th
Optimisation, Diagnostics and Control of Power Electronic Drives of
01.09.2013 – 27.05.2014
50
Ramkrishan Maheshwari; Ewen Ritchie; Krisztina Leban;
PED4-1045
SYNOPSIS:
_____________________________________
Florin Valentin Traian Nica
Copies:
Pages, total:
Appendix:
Supplements:
This project is focused on the
construction of a three level neutral
point clamped prototype converter, for a
wind turbine application. The converter
has to ensure the control for a vertical
axis Darreius wind turbine, which has
special requirements for the system.
Two sensorless control strategies are
implemented and tested in laboratory
experiments, to determine the best
method. The conclusion of the
experiments is that sensorless field
oriented control is the most adequate
control to be implemented for this type
of application.
3
83
3
CD
By signing this document, each member of the group confirms that all group members
have participated in the project work, and thereby all members are collectively liable for
the contents of the report. Furthermore, all group members confirm that the report does
not include plagiarism.
Preface
The current report, entitled “Sensorless control of PMSM using three level NPC converter” was
written by Florin Valentin Traian Nica, master student of Power Electronics and Drives, at the
Department of Energy Technology, Aalborg University, Denmark.
The project was proposed by Ewen Ritchie, associate professor, and Krisztina Leban, Ph.D.
student, as part of a European Programme contracted by Aalborg University, called DeepWind.
The span of the project was one school year, started on 1st of September 2013 and finished on
27th May 2014, thus being the master thesis project of the author.
Reading Instructions
The text is divided into seven chapters plus two appendixes. The chapters are consecutive
numbers, whereas the appendixes are labelled with capital letters.
The references are shown in form of number placed into square brackets. Additional information
about each reference is presented in Bibliography.
The format of equations is (X.Y), where X is the chapter number and Y is the equation number.
The format of figures is Fig. X.Y, where X is the chapter number and Y is the figure number.
The format of tables is TABLE X.Y, where X is the chapter number and Y is the table number.
The enclosed CD-ROM contains the report in Word and PDF format, two Matlab Simulink
models, which present different approaches of constructing the model, an extra Matlab Simulink
Library, constructed by the author and images with laboratory results.
Acknowledgments
The author will like show its gratitude to the supervisors, for their extensive support during the
entire project period. Special thanks are made to Krisztina Leban and Ewen Ritchie, for their
financial and moral support during the two year master programme.
Summary
In order to help the reader understand the structure of the report, a summary of all the chapters is
made in the following.
1. Introduction
This chapter presents at the beginning a short retrospective of wind energy evolution during the
last years. This retrospective is necessary to understand way the European Union has proposed
the DeepWind Programme.
A short description of the DeepWind Programme is presented afterwards, along with the tasks
that Aalborg University has to fulfil.
Because one of these tasks represents the starting point for the current master thesis, a more
detailed description is made about this task.
The last part of the chapter presents the objectives along with the limitations.
2. Theoretical Background
The most important theoretical concepts used during the project are presented in this chapter.
The chapter starts by presenting the three level neutral point clamped (NPC) converter, because
this topology is used for the prototype. Only the most important information about the converter
is presented here, along with a selection of references.
The problem and solution for the neutral point voltage balance is presented, because this topic is
very important for the NPC, and it is part of the practical implementation.
The chapter continues by presenting the permanent magnet synchronous machine (PMSM)
model, in a short section.
The state of the art for scalar and vector control is presented in the last part of the chapter, along
with the control theory specific for PMSM.
3. Control Description and Implementation
This chapter presents which control methods are selected for the project. Because a decision was
made to use both scalar and vector control, these two are presented separately.
Scalar control is presented first, followed by vector control. As it can be seen from the report,
these two control methods have a similar structure with similar components. All these similar
components will be presented, in the vector control subchapter, to avoid repeating the same
theory twice.
After each control method is described, the implementation process is presented. This
implementation process provides the PI controller parameters.
The last part of the chapter presents the speed and position estimator. Although the estimator is
used for vector control, it is presented in a separate subchapter, because it represents the most
important component of the control.
4. Simulations
Using the information from chapter two and three, a Simulink model of the entire system is
created. These simulations were selected based on the second objective.
The results are presented for each simulation, along with necessary explanation.
5. Hardware Design of Converter
The main circuits of the three level NPC prototype are presented in this chapter. Only general
block diagrams are used to highlight the main circuits, because the design was not made during
this project. For a more detailed description of the prototype and the components, references are
provided.
6. Laboratory Experiments
During this chapter, all the laboratory experiments are presented with measurements and
explanations. In order to have a comparison between the Simulink model and the real system, the
tests are made under similar conditions as the simulations.
7. Conclusions
This chapter presents the main conclusions of the project.
Appendix A. Reference Frame Transformation
The reference frame transformations used in the report are presented.
Appendix B. Neutral Point Voltage Balance Results
The voltage measurements obtained, using space vector modulation, are presented at the
beginning. The rest of the appendix presents the DC link voltages for all the experiments,
obtained using sinusoidal pulse width modulation.
Appendix C. Numeric Parameters
All the numeric values used during the project are presented in this appendix. These numeric
values represent the machine parameters, the control parameters and the convertor parameters.
Contents
1
2
3
Introduction ............................................................................................................................. 1
1.1
Wind Energy Evolution .................................................................................................. 1
1.2
DeepWind Programme.................................................................................................... 2
1.3
Converter and Control for DeepWind Programme ......................................................... 3
1.4
Project Objectives ........................................................................................................... 4
1.5
Project Limitations .......................................................................................................... 5
Theoretical Background .......................................................................................................... 7
2.1
Three Level NPC Converter ........................................................................................... 7
2.2
Neutral Point Voltage Balance........................................................................................ 8
2.3
Modulation Strategies ................................................................................................... 10
2.3.1
Sinusoidal PWM ..................................................................................................... 10
2.3.2
Space Vector Modulation ....................................................................................... 12
2.4
Permanent Magnet Synchronous Machine Model ........................................................ 15
2.5
Control of PMSM ......................................................................................................... 17
2.5.1
Scalar Control ......................................................................................................... 17
2.5.2
Vector Control ........................................................................................................ 19
Control Description and Implementation.............................................................................. 21
3.1
Scalar Control (I-f Control) .......................................................................................... 21
3.2
Vector Control (Field Oriented Control) ...................................................................... 23
3.2.1
Controller Design Requirements............................................................................. 25
3.2.2
Current Controller ................................................................................................... 25
3.2.3
Flux control loop ..................................................................................................... 30
3.2.4
Speed Controller ..................................................................................................... 30
3.2.5
Anti-Windup ........................................................................................................... 33
3.3
4
Rotor Position Estimation ............................................................................................. 34
Simulations ........................................................................................................................... 37
4.1
Model Overview ........................................................................................................... 37
4.2
Scalar Control Simulations ........................................................................................... 38
4.2.1
Speed reference variation ........................................................................................ 38
4.2.2
4.3
5
6
Vector Control Simulations .......................................................................................... 41
4.3.1
Speed reference variation ........................................................................................ 41
4.3.2
Load torque variation .............................................................................................. 43
4.3.3
Transition from motor to generator......................................................................... 43
4.3.4
Emergency breaking ............................................................................................... 44
4.3.5
Holding the machine at zero speed ......................................................................... 46
Hardware Design of Converter ............................................................................................. 49
5.1
General Structure .......................................................................................................... 49
5.2
Power Side .................................................................................................................... 50
5.3
Control Side .................................................................................................................. 51
Laboratory Experiments........................................................................................................ 57
6.1
Laboratory Setup ........................................................................................................... 57
6.2
Scalar Control Experiments .......................................................................................... 58
6.2.1
Speed reference variation ........................................................................................ 58
6.2.2
Load torque variation .............................................................................................. 59
6.3
7
Load torque variation .............................................................................................. 40
Vector Control Experiments ......................................................................................... 60
6.3.1
Speed reference variation ........................................................................................ 60
6.3.2
Load torque variation .............................................................................................. 61
6.3.3
Transition from motor to generator......................................................................... 62
6.3.4
Emergency breaking ............................................................................................... 64
6.3.5
Holding the machine at zero speed ......................................................................... 65
Conclusions ........................................................................................................................... 67
Appendix A.
Reference Frame Transformation........................................................................ 69
Appendix B.
Neutral Point Voltage Balance Results ............................................................... 73
Appendix C.
Numeric Parameters ............................................................................................ 77
Chapter 1. Introduction
1
Introduction
This chapter presents the wind energy evolution in the last years at a global level. The focus will
be then changed to the European Union and its programmes, which support the development of
renewable energies. A short presentation of one of these programmes, contracted by Aalborg
University, called DeepWind, will be made, to relate the requirements of the programme with the
project at hand. The objectives of this project will be presented in the second part, along with
necessary information for each objective. The final part of the chapter will present the
limitations imposed for the project.
1.1 Wind Energy Evolution
Political and economical conditions have lead to a significant increase in research and
development of renewable energies in the last decade [1, 2]. Because of this, wind energy has
become one of the mainstream renewable technologies with more than 300,000MW installed
globally until 2013 [2], as it can be seen from Fig. 1.1.
Fig. 1.1. Global cumulative installed wind capacity 1996-2013 [2].
From the total amount of wind power installed globally until 2013, Europe is the leading region,
with 38% of the total installed renewable power [2], which covers approximately 7% of the
electricity demand.
Europe is the leader in installed wind power due to the policies implemented, and due to the long
term objectives imposed by the European Union [3]. These targets, presented in [3], require that
by 2050, 50% of the energy consumed in Europe to be produced by wind turbines.
In order to achieve this goal, massive investments are made in research and development, to
increase the energy capacity of each generator, and to provide better solutions for the structure
[3]. As a result, the average generator capacity installed each year has increased from 200kW for
onshore and 450kW for offshore in 1991, to 1,700kW for onshore and 2,800kW for offshore in
1
Chapter 1. Introduction
2010 [3]. This trend is expected to be maintained in the future, allowing for an increase above
3,000kW.
TABLE 1.1.
L ONG TERM OBJECT IV E S SET BY THE EU RE GARD ING WIND POWER [3] .
Onsh
ore
wind
(GW
)
Offsho Total
re wind wind
(GW)
energy
capacit
y
(GW)
Averag
e
capacit
y
factor
onshor
e
Averag (TWh)
e
onshor
capacit e
y
factor
offshor
e
(TWh) (TWh)
offshor total
e
EU-27
gross
electricity
consumpt
ion
Wind
power’s
share of
electrici
ty
demand
2020
190
40
230
26%
42.3%
433
148
581
3,690
16%
2030
250
150
400
27%
42.8%
591
562
1,154
4,051
29%
2050
275
460
735
29%
45%
699
1,813
2,512
5,000
50%
The European Union is supporting this development thought Framework Programmes since 1984
and plans to continue at least until 2020 [4]. Aalborg University is one of the participants
engaged in one of these programmes called DeepWind [5]. A short description of the programme
is presented in the following section.
1.2 DeepWind Programme
The DeepWind programme was proposed on the hypothesis that a new wind turbine concept,
developed specifically for offshore, has potential for better cost efficiency than existing offshore
technology [5].
Considering this hypothesis a series of objectives have been set [5]:
 To explore the technologies needed for development of a new, simple, floating offshore
concept, with a vertical axis rotor, and a floating and rotating foundation;
 To develop calculation and design tools for development and evaluation of very large
wind turbines, based on this concept;
 Evaluation of the overall concept with floating offshore horizontal axis wind turbines;
As part of the DeepWind programme Aalborg University is responsible for a series of tasks:
 Design the bearings of the wind turbine;
 Construct a design tool which is able to design a wind turbine generator in the range of 5
to 20MW, specific for an offshore application;
 Propose a converter topology adequate for this application;
As an integrated part in the DeepWind Programme, the current master thesis focuses on the
converter topology for the wind turbine.
2
Chapter 1. Introduction
1.3 Converter and Control for DeepWind Programme
In order to identify the best converter topology for the current application, a student project was
proposed at Aalborg University [6]. The project concluded that the best topology to be used in
this situation is the three level neutral point clamped (NPC) converter [6].
This converter topology is preferred, instead of the two level converter, which is most widely
used, because of its advantages as: reduced voltage across each switch (only half of the DC link
voltage per each switch, compared to the entire DC link voltage per each switch, for the two
level), reduced current ripple losses, reduced switching/conduction losses and reduced total
harmonic distortion.
The decision was made to use the three level NPC converter. A small scale prototype of the
converter is built. This step is considered to be the first objective of the current master thesis,
which will be presented in more detail in the following subchapter.
Although the control of the converter is not a task required for Aalborg University, by the
DeepWind Programme, it will be considered as an objective for the current master thesis.
When the control strategy is developed, the particularities specific to this application must be
taken into consideration. As a start, it should be noted that the participants engaged in this
project, responsible with the structure of the wind turbine, have proposed a vertical axis Darrieus
type turbine.
This turbine has to be anchored to the bottom of the sea, leaving the entire structure to float.
Because of the uniqueness of the construction, the generator along with the converter will be
located underwater, at the bottom of the wind turbine.
The Darrieus wind turbine imposes special requirements for the control strategy, requirements
which must be taken into consideration when the control is elaborated. These special
requirements, specific to the Darrieus wind turbine, are presented in the following:
 The unique structure restricts it from self-starting even with high levels of wind speed.
Hence, the generator will have to work as a motor in the starting phase and accelerate the
turbine until a certain rotating speed is reached. During the start procedure, since the
machine will be working as a motor, power will be consumed from the grid;
 Stopping the turbine. The size and weight of the entire structure creates a very large
moment of inertia, and because the turbine cannot be stopped using traditional
mechanical breaks, the generator has to be able to stop the entire structure;
 Pitch control cannot be implemented for this system, since the blades of the turbine are
fixed. Hence the entire structure will have to be controlled by the generator via the
converter.
Based on the information presented and the requirements imposed by the DeepWind Programme,
the objectives for the current master thesis can be elaborated.
3
Chapter 1. Introduction
1.4 Project Objectives
To have a clear understanding of why the following objectives are selected for this project, each
objective will be presented in a separated section, along with all the necessary information.
Objective 1:
A three level NPC prototype converter has to be constructed.
The prototype is constructed as a requirement of the DeepWind Programme, to test the topology
proposed for the main converter. A secondary reason is that the converter has to drive a small
scale generator prototype, which was constructed to test the analytical design program.
The main beneficiaries of this objective are the people involved in the DeepWind project and the
author of this thesis, because of the experience gained while constructing a convertor and
working in a laboratory.
The PCB schematics used in the current project are taken from a previous AAU project [7], in
order to save time with converter design. All the components are ordered according to the bill of
materials, provided in the project, and the soldering and testing part is made by the author, in the
laboratory.
Objective 2:
Propose suitable control strategies for the converter, in different working situations as:





starting the turbine as motor;
working as a motor;
working as a generator;
emergency breaking;
holding the turbine at zero speed;
The Darreius wind turbine imposes special requirements for the converter, like the ones
presented in the Converter and Control for DeepWind Programme subchapter presented earlier.
The control implemented on the converter has to be able to handle all these situations;
The main beneficiary of this objective is the author conducting this report, because it has to study
the state of the art methods in control strategies, and propose suitable ones for this project. Also
the DeepWind Programme will benefit from this objective, ensuring that tests can be made in
different situations.
To complete this objective, a review of the state of the art methods in control is made. Using the
information gained, the most suitable method that can be applied on this system is selected.
Objective 3:
Construct a mathematical model of the system and simulate the proposed control strategies.
The simulations are made to: test the functionality of the system, test the control strategies
selected during the previous objective and to improve the control by tuning the system. Also, the
4
Chapter 1. Introduction
simulation provides important information before the real system is tested, information which
can be used to improve the system and to reduce the implementation time.
After the model is constructed in Matlab Simulink, the control is implemented to drive the
system. In order to validate the control, numerous simulations are made using the conditions
imposed at objective two.
Objective 4:
Test the converter in the laboratory for all the situations simulated.
On the constructed converter, the proposed control strategies are tested to validate the behaviour
of the system and to verify its functionality.
The author of this report is the main beneficiary of this objective because it has the chance to
learn how to build a setup in the laboratory, study, develop and implement DSP programming on
the convertor and test the overall system;
With the constructed converter, and the available machine prototype, provided by the DeepWind
project, the setup is made. The control is implemented on a DSP, thus providing the control for
the converter.
1.5 Project Limitations
Because of limited time and/or resources some limitations have to be imposed to the project:
 The design of the converter is not an objective for this project. The design presented in
[7] will be used to construct the converter.
 Sinusoidal pulse width modulation, without DC balance capabilities, is used in laboratory
experiments;
 Because field weakening control is not an objective for this project, it was only presented
as a theoretical concept. Experimental tests were made in the laboratory, using this
control, but are not presented in the report.
5
Chapter 2. Theoretical Background
2
Theoretical Background
This chapter presents the main theoretical topics that will be required to handle the objectives.
The focus is placed on the most important components of the system: converter, machine and
control. In the first section, a short description of the three level NPC converter is made,
information which is required to understand its structure and functionality. The model of the
permanent magnet synchronous machine in rotating “dq” reference frame is presented
afterwards. The state of the art control methods that can be applied for this type of machine are
presented in the last section.
2.1 Three Level NPC Converter
The circuit diagram of a three level neutral point clamped (NPC) converter is presented in Fig.
2.1. [8]. It can be observed that two capacitors (
) are placed on the DC link, creating a
neutral point 0. The two diodes connected to the neutral point (
) are called clamping
diodes. E is the voltage across the DC capacitors and it is normally half of the DC voltage
,
but neutral point voltage deviation can appear because the capacitors are charged and discharged
by the neutral current [8].
+iDC
S1
D1
+ Cd1
D2
Dc1
A
E
Vdc
0
iA
B
i0
Dc2
E
S2
+
- Cd2
C
S3
D3
S4
D4
-
Fig. 2.1. Three level NPC converter [8]
7
.
iB
iC
N
LOAD
Chapter 2. Theoretical Background
The working procedure of the convertor is represented by the switching states of each phase.
Since the procedure is similar for each phase, only the switching states for phase A are presented
in TABLE 2.1.
TABLE 2.1
S WITCH ING S TATE S FOR ONE P HASE OF THE C ONVER TER
Switching
State
Switching State for Phase A
Phase Voltage
S1
S2
S3
S4
P
On
On
Off
Off
E
0
Off
On
On
Off
0
N
Off
Off
On
On
-E
As it can be seen from the table, in order to obtain at the output of the converter a positive
voltage equal with the voltage across the capacitor E, the upper two switches S1 and S2 have to be
on and the lower two switches S3 and S4 have to be off. This is also called the P switching state
because it produces a positive voltage at the output.
To obtain a negative voltage at the output, with the same magnitude, the status of the switches
has to be opposite to the P state, and this is called N switching state.
The three level NPC converter is also able to produce a zero voltage level at the output, which is
determined by the switching state 0, when the interior switches (S2 and S3) are on, and the
exterior switches are off (S1 and S4).
From these three switching states (P, N and 0) it should be noted that switch one and switch three
always work in opposition
, same as switch two and four
.
By properly controlling these switching states, on all three phases, the neutral point voltage
unbalance can be eliminated. The reasons why this phenomenon can appear are presented in the
following section.
2.2 Neutral Point Voltage Balance
The neutral point voltage balance can be influenced by numerous parameters [8], as: different
parameters for the DC link capacitors, DC capacitor failure, different parameters for the
switching devices and unbalanced loads.
If the neutral point voltage balance problem is not considered and corrected, problems can
appear in the system [8], as: premature failure of the switching devices, increased total harmonic
distortion, modulation ratio limited by the terminal with the lower voltage.
This problem can be solved by applying the adequate switching state on each of the three phases.
To have a unified notation of the switching state on all three phases, the space vector term was
introduced [8]. The space vector considers the switching state on each phase, by using the output
phase voltage, and it can be expressed using the following equation:
8
Chapter 2. Theoretical Background
(2.1)
, where:
- space vector;
- voltage on phase A (considering the neutral point 0 as reference);
;
A more detailed explanation regarding the space vector term will be made in the following
sections. At this point it is sufficient to know that the three level NPC converter has the ability to
generate four groups of space vectors based on their magnitude, each corresponding to different
switching states (TABLE 2.3).
Each of these space vectors has a different influence on the neutral point voltage [8], influence
that will be analyzed in the following, using the switching states presented in Fig. 2.2.
Zero space vectors (Fig. 2.2.a.) have no influence on the neutral point voltage balance, because
they ensures the connection of the converter terminals (A, B and C) with only one of the DC
states at a time (positive, zero or negative DC voltage) [8].
Small space vectors have a powerful influence over the voltage balance. This is because when a
P switching state is active (Fig. 2.2.b.), the load is connected between the positive DC voltage
and neutral point, causing the current to flow towards the neutral point 0, which increases .
In the opposite situation, when an N switching state is active (Fig. 2.2.c.), the current flows
from the neutral point 0 towards the negative point N, causing a decrease in [8].
Medium space vectors (Fig. 2.2.d.) also have an influence over the neutral point voltage
balance. Even thought at each moment one converter terminal is connected to a different DC
point, the voltage can increase or decrease depending on the operating condition [8].
Large space vectors (Fig. 2.2.e.) do not affect the voltage balance of the neutral point [8]. This
is because the load terminals are connected between the positive and negative DC terminals,
while the neutral point is left unconnected [8].
A
+
A
+
Cd1
Cd1
B
0
Vd
V0
0
Vd
V0
Cd2
C
i0
B
Cd2
C
-
9
Chapter 2. Theoretical Background
a)
Zero space vector [000].
b) Small space vector (P type) [PP0].
A
+
A
+
Cd1
V0
B
i0
0
Vd
Cd1
i0
0
Vd
V0
Cd2
Cd2
C
C
c)
B
d) Medium space vector [P0N].
Small space vector (N type) [00N].
A
+
Cd1
B
0
Vd
V0
Cd2
C
e)
Large space vector [PPN].
Fig. 2.2. Effect of space vectors on neutral point voltage balance [8].
By adequately controlling the space vectors during the modulation, neutral point voltage balance
can be achieved. Two of the most widely used modulation strategies will be presented in the
following.
2.3 Modulation Strategies
Numerous modulation strategies have been proposed for the three level NPC converter [9]. The
most common known and used are:
 Sinusoidal pulse width modulation (SPWM);
 Space vector modulation (SVM);
2.3.1 Sinusoidal PWM
This method is based on the comparison between a sinusoidal reference signal and two carrier
signals (
).
10
Chapter 2. Theoretical Background
Fig. 2.3. Sinusoidal PWM.
Because the first carrier signal
is always bigger than the second carrier signal
, and
because the switches work in opposition
, it is sufficient to define two
states for the PWM logic (TABLE 2.2).
TABLE 2.2
L OGIC OF THE C ARR IER B ASED PWM M E THOD
Cases
Switch State
Besides the classical method presented here, were the modulation signal is sinusoidal with only
one frequency component, there are numerous others sinusoidal PWM strategies developed to
improve the quality of the result [9].
SPWM can be used as a modulation strategy because it ensures a natural balance in the DC link,
when no external factors affect the system. The disadvantage of this method appears when an
external factor influences the DC neutral point voltage. In this situation the balance cannot be
ensured, which can cause a fault to appear in the system.
In order to provide a safe operation, even when external factors affect the DC link voltage, a
different modulation strategy has to be used. This strategy is presented in the following.
11
Chapter 2. Theoretical Background
2.3.2 Space Vector Modulation
The three level NPC converter has 33=27 switching states combinations, which can generate
different space vectors. A classification of all the space vectors obtained using (2.1) is made
based on magnitude and type, in TABLE 2.3.
TABLE 2.3
V OLTAGE V EC TORS AND S WITC HING S TATES [8]
Vector
Classification
Vector
Magnitude
Zero Vector
0
Space Vector
Switching State
P type
000
N type
PPP
NNN
P00
0NN
PP0
00N
0P0
N0N
0PP
N00
00P
NN0
P0P
0N0
Small Vector
P0N
0PN
NP0
Medium Vector
N0P
0NP
PN0
PNN
PPN
NPN
Large Vector
NPP
NNP
PNP
As it can be observed form TABLE 2.3 and from Fig. 2.2, only the small space vector has two
switching state types, positive and negative. These two types produce a space vector with the
same magnitude and angle. The difference between the two switching states is the direction of
the neutral current . For the positive type the current enters the DC link, while for the negative
type the current is taken out of the DC link.
12
Chapter 2. Theoretical Background
Using the space vectors presented in TABLE 2.3 in the correct manner, the neutral point voltage
balance can be maintained, even when external influences affect the DC voltage [8]. A
modulation technique which has this capability is presented in the following [7].
In order to understand which space vectors must be for each situation, all the space vectors are
arranged in a diagram made out of six sectors, each sector having two regions, as it can be seen
in Fig. 2.4 and Fig. 2.5.
From Fig. 2.5, it can be seen that the irst re ion is situated etween ,
and the second
re ion is situated etween
, ]. Another important information that has to be considered is
that each region contains four space vectors. For example, sector one, region one contains:
,
,
and
.
V14
Reg. 2
V2
V7
Reg. 1
V13
V0
Fig. 2.4. Space vector diagram divided in sectors and
regions [7].
V1
Fig. 2.5. Space vector from sector 1, region 1 and 2.
The neutral point voltage balance is maintained by alternating the small space vector from
positive type to negative type, when there is no fault in the system. When the voltage on the
lower capacitor
increases above a predefined value, the negative type small space vector is
used in the modulation, to draw the current out of the DC link. In the opposite situation, when
the voltage on the lower capacitor
decreases below a predefined value, the positive type
small space vector is used, to send current to the DC link.
In order to use all four space vectors the modulation index has to be considered. The modulation
index is defined as:
(2.2)
, where:
- magnitude of the reference voltage;
13
Chapter 2. Theoretical Background
The modulation index is in the [0, 1] range because the maximum magnitude of the reference
vector
corresponds to the radius of the largest circle that can be inscribed within the
hexagon in Fig. 2.4, which is equal to the medium space vectors.
The modulation index will determine the dwell time for the zero space vector
according to:
(2.3)
, where:
- dwell time for the zero space vector;
- sampling time;
As it can be seen from (2.3), if the modulation index is equal to one, the zero space vector is not
used.
In order to calculate the required dwell time for the other three space vectors, the volt-second
balance principle is applied.
This principle states that the product between the reference voltage
and the sampling time Ts
is equal to the sum of voltage multiplied by the time of the chosen space vectors [8].
To better explain this principle it will be consider that the voltage reference vector
situated in sector one, region one. This means that the nearest three vectors are
,
and
is
.
Based on the volt-second balance principle the equations can be written:
(2.4)
(2.5)
, where:
are the calculated dwell times for
,
and
, not the final dwell times.
The space vectors are expressed in the following form:
(2.6)
Substituting (2.6) in (2.4) yields:
(2.7)
From (2.7), i Euler’s ormula is applied and the real part is separated rom the ima inary part
the following two equations can be obtained [8]:
(2.8)
(2.9)
14
Chapter 2. Theoretical Background
Because there are three unknowns
and only two equations (2.8) and (2.9), equation
(2.5) is added to the system. Solving the system of equations and extracting the modulation index
from each equation will result in:
(2.10)
(2.11)
(2.12)
Because there are four space vectors used for modulation, the calculated dwell times
are must be divided by the modulation index. The division creates the required time for
the zero space vector. The four dwell times used in the modulation are:
(2.13)
The same procedure is applied for the second region and the calculated dwell times are:
(2.14)
(2.15)
(2.16)
If the reference vector is placed in another sector (II to VI) the same equations as for the first
sector can be used, keeping into consideration the difference between region one and two. Before
the dwell time calculations, the angle has to be reduced to the first sector, as in (2.17).
(2.17)
, where:
– the angle reduced to sector one;
– reference vector position (angle of
);
n – the sector number.
2.4 Permanent Magnet Synchronous Machine Model
In order to construct the mathematical model of a permanent magnet synchronous machine
(PMSM) the following assumptions are made [10]:





Saturation is neglected;
The induced electromagnetic force (EMF) is sinusoidal;
Eddy currents and hysteresis losses are negligible;
There are no field current dynamics;
The “d” axis is aligned with the permanent magnet flux linkage
15
;
Chapter 2. Theoretical Background
The voltage equations in rotating “dq” reference frame are:
(2.18)
(2.19)
, where:
- voltage on d, q axis [V];
- current on d, q axis [A];
- stator resistance [Ω];
- flux linkage on d, q axis [Wb];
- rotor electrical speed [rad/sec];
The flux equations are:
(2.20)
(2.21)
, where:
– inductance on d, q axis [H];
- flux linkage due to magnets placed on the rotor, which links the stator [Wb];
The electromagnetic torque equation is:
(2.22)
, where:
– electromagnetic torque [N m];
- number of pole pairs;
For the special case presented by the PMSM, where the inductances along the d and q axes are
equal
, equation (2.22) can be simplified to:
(2.23)
The dynamic equation for the speed of the machine is:
(2.24)
, where: - moment of inertia [kg m2];
– rotor mechanical speed [rad/sec];
- load torque [N m];
– viscous friction constant [-];
16
Chapter 2. Theoretical Background
2.5 Control of PMSM
Depending on the multitude of application where drives are being used, numerous types of
control strategies have been developed during the time, starting from the most basic ones, as
using a variable resistor to manipulate the voltage, to the most advance ones as servo-drive
control [11]. The difference between all these control strategies is in the ease of implementation,
performance and cost. In order to have an idea of the difference between different control
strategies a comparison from [11] is presented in the following.
TABLE 2.4
P ER FO R M A N C E C O M P A R IS O N B E TW E E N D I F FE R EN T C O N TR O L S TR A T E G I E S
AN D
P O SS I B L E A P P LIC A T I O N S [11]
Simple Scalar
Control
Scalar Control
(compensated)
Voltage Vector
Control
Flux Vector
Control
Servo Drive
1:10
1:25
1:50
1:10000
1:10000
(open loop)
(open loop)
(open loop)
(closed loop)
(closed loop)
Static Speed
Accuracy
5%
2%
1%
0%
0%
Torque Rise
Time
Not available
Not available
10 ms
< 1 ms
< 1 ms
Speed Rise
Time
> 100 ms
> 50 ms
> 20 ms
< 10 ms
< 10 ms
Starting
Torque
Low
Medium
High
High
High
Cost
Very Low
Low
Medium
High
High
Possible
Applications
Pumps, Fans
Conveyors
Crane, Pack
Crane, Lifts
Robots
Speed Range
As it can be seen from TABLE 2.4, only control strategies that can be implemented on
converters are presented. These control strategies can be separated in two classes, scalar control
and vector control. Both scalar and vector control strategies are implemented in the current
project to test the theoretical concept on a real system and to get a better knowledge of how the
methods behave. To do so, first, the state of the art of each control strategy is presented in the
following of this chapter. After the state of the art, the control methods selected for this project
are presented in more detail in the following chapter, along with the implementation method.
2.5.1 Scalar Control
Being initially developed for the induction machine, this motor drive control strategy is used in
systems which do not require high dynamic performances because of its simplicity and low cost
[11, 12].
17
Chapter 2. Theoretical Background
As a speed control strategy it takes into consideration two of the properties specific for the
induction machine [12]:
 The torque-speed characteristic is predominantly steep in the region of synchronous
speed, which means that the electrical rotor speed is close to the electrical frequency. By
controlling the frequency, the speed of the machine can be controlled;
 The voltage equation (2.25), expressed in steady state, highlights the fact that the flux
linkage term has a much higher influence than the resistive term in the voltage equation
for medium to high speed situation.
(2.25)
(2.26)
, where:
- magnitude of the stator flux linkage;
- magnitude of the applied voltage;
As it can be seen in equation (2.26), the magnitude of the flux linkage is in fact the ratio between
the magnitude of the applied voltage, and rotor electrical speed. This helps us understand that in
order to maintain a constant flux linkage, to avoid saturation, the ratio should be kept constant
[12]. This ratio also gives the name of this method, being widely known as V/f control.
q
q
Vs
Rs Is
j Xd Is
j Xd Is
Rs Is
R s Is
Es=ωe λs
Iq
Is
λs
a)
Iq
Is
θT
Id
Rs Is
EPM=ωe λPM
Es=ωe λs
Vs
EPM=ωe λPM
λPM
LdId
λs
θT
LqIq
d
Id
λPM
LqIq
d
LdId
b)
Fig. 2.6. Phasor diagram of PMSM with d-axis aligned with the rotor magnet flux
[13].
The phasor diagrams of the PMSM presented in Fig. 2.6 are used to better understand the main
disadvantage of this control strategy. By only controlling the voltage and the frequency, and not
the current on the direct and quadrature axis, the magnetisation of the machine cannot be control
properly [12, 13].
18
Chapter 2. Theoretical Background
As stated in [12, 13], high values of V/f cause an increase in the direct axis component of the
current , which produces an over-excitation in the machine Fig. 2.6 a). On the other hand, for
low V/f values the direct axis component of the current , becomes negative and the machine
experiences under-excitation Fig. 2.6 b).
Using this method, problems are experienced at low speeds, where the frequency has a small
value and the resistive term cannot be neglected. To handle this problem, various compensation
methods have been proposed, as it can be found in [12, 14-17].
When this control method is applied to PMSM, stability problems will appear because of
desynchronization between the rotor speed and the applied frequency [14-18]. This
desynchronization between the two frequencies will make the operation impossible.
The classical solution which can be implemented during the manufacturing process is to provide
the rotor with damper windings [18]. These damper windings will ensure the synchronization
between the two frequencies. However, this solution increases the cost significantly and it is
proven to be problematic when it comes to the design of surface mounted PMSM [18].
Different other solutions have been proposed in the literature to deal with this problem by
employing a close loop control, such as in [15-17] where the perturbation of the current in the
DC link was used to modulate the frequency. The power efficiency was the main objective
presented in all three references, with similar approach in [15] and [16], where the voltage was
controlled using a search algorithm which ensures a minimum input power to the PMSM. In [17]
the objective was to control the voltage in order to obtain unity power factor.
In [14] a voltage control method is used to improve the low speed performance, along with a
small signal model which modulates the applied frequency proportional to the input power
perturbation.
The cited methods conclude that a better stability is achieved, without the need of damper
windings in the rotor, although in [15-17] poor performance was obtained for low speed
operation.
A different scalar control method, called I-f control, is presented in [19], for start up without the
need of initial rotor position estimation and ultra low speed sensorless control. This method also
ensures over-current protection by controlling separately the and currents. The disadvantage
presented by this method is the absence of an analytical method to design the I-f controller.
2.5.2 Vector Control
By comparison with the scalar control, vector control allows separate close loop control of both
flux and torque [13], by separately controlling the direct and quadrature axis currents and .
These two currents are controlled through the voltage
and , according to the following
equations, derived from (2.18) and (2.19).
19
Chapter 2. Theoretical Background
(2.27)
(2.28)
Vector control can ensure optimum control of the machine under different working conditions,
such as: maximum torque per ampere ratio (MTPA), maximum torque per flux ratio, unity power
factor.
In the current project the MTPA strategy is implemented. Using this strategy, the control ensures
minimum current is used to achieve the required torque, which maximizes the machine
efficiency [20]. To achieve MTPA ratio the torque angle , between the PM flux linkage phasor
and the current phasor, has to e maintained at
(Fig. 2.8). By doing this the direct axis
current , which does not contribute to the production of torque (2.23) is cancelled, and the
quadrature axis current
becomes equal with the current magnitude (
).
This situation can be observed in the phasor diagram Fig. 2.7. Here it can be seen that the stator
flux linkage is produced by the permanent magnet flux and the flux on the q axis.
q
T
j Xd Is
Rs Is
Vs
Rs Is
EPM=ωe λPM
Es=ωe λs
Is
θT
0
λs
π/2
π
θT
LqIq
λPM
d
Fig. 2.8. Torque magnitude as a function of the torque
angle.
Fig. 2.7. Phasor diagram of vector controlled PMSM for
MTPA [13].
To obtain this behaviour a technique best known as field oriented control (FOC) is used. This
technique employs cascaded close loop systems to control the speed and torque, by means of
speed controller and current controller. A more in depth description of FOC will be made in the
following
chapters.
20
Chapter 3. Control Description and Implementation
3
Control Description and Implementation
This chapter presents the control strategies that are selected for this project. After the selected
scalar and vector control is presented, the implementation method is made. Because scalar and
vector control use relatively the same structure, the common components are presented in the
vector control part. The last part of the chapter presents the rotor position estimator.
3.1 Scalar Control (I-f Control)
Although V/f control is the most popular scalar control method, it was not selected for this
project because of its disadvantages related to PMSM, presented in the previous chapter. Instead,
I-f control was preferred because of its advantages, as [19]:
-
ability to protect the system by directly controlling the current;
similar structure and components as FOC;
the variation in machine parameters has a limited influence over the control;
capability to start at full load independent of the rotor position;
in wind turbine applications it is recommended for maintenance situations, when the
rotor has to be moved only slightly;
To observe the similarities with FOC, which is presented in more detail in the following
subchapter, a block diagram of the scalar control is presented in Fig. 3.3.
The main difference is that a current reference is given directly to the “q” axis, eliminating the
speed control loop. The “d” axis is kept at zero for the same reason as for FOC, to ensure better
efficiency for the machine.
If the quadrature axis current is
maintained constant during the entire
operating procedure, the active power
will decrease when the speed reaches
nominal value, providing only the
necessary power to drive the machine.
The rest of the electric power sent to
the machine will be transformed to
reactive power, which reduces the
efficiency and demagnetizes the
permanent magnets (Fig. 3.1).
Pe
Q
ωeN
ωe
Fig. 3.1. Active and reactive power variation during the starting
procedure (
).
21
Chapter 3. Control Description and Implementation
To ensure the best efficiency
possible using scalar control, the
reference quadrature axis current
has to be controlled as a function of
reference frequency .
Pe
Q
ωeN
ωe
If the reference quadrature axis
current
is decreased, after the
nominal speed is achieved, the
active power is maintained at the
same level, while the magnitude of
the reactive power is reduced (Fig.
Fig. 3.2. Active and reactive power variation during the starting
3.2). It has to be noted here that
procedure (
).
because the imposed rotor position
is not equal with the real rotor
position, unity power factor cannot be achieved. The quadrature axis current
has to be
maintained at an adequate value, to ensure stabile operation.
An important disadvantage, that makes this control unusable for a wind turbine application, must
be stated here. Because there is no outer speed loop to provide at any moment the adequate
reference quadrature axis current , this control cannot be used in all situations required by the
system. For example, when the transition from motor to generator is made, the sign of the current
reference has to be modified manually by the user, at the same time, or else the control becomes
unstable. Also, if a considerable load torque is applied, the current is not able to produce
sufficient electromagnetic torque, causing the drive to lose stability.
Vdc/2 Vdc/2
Vdc
0
f*
id*
Current
Control
iq* kpi, kii
I(f*)
vd*
va*
vb*
dq
vq*
abc
vc*
SPWM
Sa
Sb
Sc
3 level
NPC
inverter
θr*
id
iq
f*
2π
ωr*
θr*
dq
abc
ia
ib
ic
θr*
0 ≤ θr*≤ 2π
PMSM
Fig. 3.3. Block diagram of closed loop I-f scalar control [19].
22
Chapter 3. Control Description and Implementation
Because of these factors, this control cannot be applied to drive a wind turbine. However, this
control is recommended for maintenance situations, when the turbine has to be moved only for
short periods of time, at a small speed [19].
This control does not use any position or speed information from an encoder or estimator;
instead the position is derived from the frequency command given to the machine. By imposing
the position, the reference frequency controls the speed of the machine.
As for FOC two proportional integrators (PI) controllers are used to control the current. Because
these two PI controllers have the same structure as for FOC, the implementation method is
presented in the following subchapter, where FOC is explained.
The “dq” voltage obtained after the PI controllers, which is considered in this case to be the
reference voltage, is transferred to “abc” reference frame in order to create the command for the
switches.
As for vector control, the measured current of the machine is used as a feedback, making it a
closed loop control.
3.2 Vector Control (Field Oriented Control)
As stated in the previous chapter the vector control method selected for this project is sensorless
field oriented control, working in a MTPA strategy. The implemented block diagram of the
control is presented in the following:
Vdc/2 Vdc/2
Vdc
ωr*
ωr
id*
Reference
Current
Generator
Current
Control
iq* kpi, kii
idq
vd*
Decoupling
Block
idq
dq
vq*
ωr
abc
va*
vb*
vc*
SPWM
Sa
Sb
Sc
3 level
NPC
inverter
θr
id
ia
ib
ic
dq
iq
abc
θr
ωr
Position and
Speed
Estimator
iabc
vabc
PMSM
Fig. 3.4. Block diagram of the sensorless FOC.
To ensure safe operation inside the speed range and above it, three types of controllers will be
implemented: flux controller, which has as input the flux on the “d” axis and produces as output
23
Chapter 3. Control Description and Implementation
the reference current on the “d” axis, speed controller, which has as input the speed error and
produces at the output the reference current on the “q” axis, and current controller, which has as
input the current error and produces at the output the reference voltage.
The reference current generator block, where the PI controllers for speed and flux are
implemented, is presented in more detail in the following figure.
λd
|ωr|
λd*
λd*
kpi, kii
id*
-
+
|ωr|
3 p λPM
2
kpω, kiω
ω r*
sqrt(Imax^2-id*^2)
Te_max
Te*
+
iq_max
-
2
3 p λPM
iq*
ωr
Fig. 3.5. Reference current generator block.
Using field weakening the speed of the machine is increased above nominal speed by decreasing
the flux and controlling the torque limits [21].
On the “d” axis the current reference is given as a function of the speed magnitude. This
behaviour is summarising in the following:
(3.1)
(3.2)
The direct current has to be reduced
in order to reduce the back-EMF component along
the q axis (2.19). Because the direct axis current
affects the magnetisation it should be
limited to a minimum value, at which
.
(3.3)
During field weakening control the magnitude of the direct axis current increases
This increase has to be taken into consideration in order to limit the current.
When
current is modified, the maximum
torque, using the following equation.
.
current is calculated, in order to limit the
24
Chapter 3. Control Description and Implementation
(3.4)
, where:
- peak value of the maximum allowed current;
Using this approach the control ensures that the machine always runs inside the safety limits.
With the reference currents determined, the error can be calculated. This error is fed to the PI
current controllers to provide the voltage command. The decoupling terms, presented in (3.5) and
(3.6) are added to the voltage signal, to ensure the decoupling present in the machine equations
(2.18) and (2.19).
(3.5)
(3.6)
With the decoupling done, the reference “dq” voltage is transferred to “abc” reference frame,
using [4], before the switch modulation is generated.
Because the position and speed estimator represents an important part of the control, it is
presented as a separate subchapter, after all FOC components are depicted.
The implementation methods for the current, flux and speed PI controllers are made in the
following, starting with the design requirements.
It has to be noted here that in certain situations, the variables will be replaced with their
numerical values. These numerical values are presented in Appendix C.
3.2.1 Controller Design Requirements
In the process of designing the current, flux and speed controllers the following design
requirements have been taken into consideration:
-
Steady state error less than 1%;
Overshoot less than 5%;
Rise time for the current controller less than 40 sampling periods
;
Rise time for the speed controller less than 400 sampling periods
;
Bandwidth of the speed controller has to be at least 10 times slower than the bandwidth
of the current controller;
With the requirements imposed for all controllers, the implementation process is presented
separately in the following.
3.2.2 Current Controller
To design the current controllers the machine equations (2.18) and (2.19) must be used to create
the plant of the system
. The plant constitutes a first order transfer function (3.10), which
has the voltage as input, and the current as output.
25
Chapter 3. Control Description and Implementation
The hardware configuration of the current control is given in Fig. 3.6 a), where the digital
controller (PI controller) is implemented, along with the digital to analogue converter (PWM)
and the analogue to digital converter (sampler and data hold).
idq_ref(t)
-
idq(t)
Digital
Controller
A/D
+
a)
Gp(s)
D/A
Hardware configuration.
G(s)
Idq_ref(s)
E(z)
E(s)
+
-
T
Vdq(z)
Sdq(z)
D(z)
C(z)
E*(s)
Vdq*(s)
Idq(s)
H(s)
Gp(s)
Sdq*(s)
b) Block diagram.
Idq_ref
1
E
E*
C* Vdq*
D*
Sdq*
G
Idq
T
-1
c)
Flow graph.
Fig. 3.6. Digital control system of the current control loop.
The block diagram, in part b), presents all the signals and transfer functions existent in the
current loop. The transfer functions are:
PI controller;
(3.7)
, where:
- current proportional gain;
– current integral gain;
- sampling time [s];
- discrete time variable;
D/A converter, represents the PWM modulation. To represent the delay introduces by
the PWM process, a unity time delay is used.
26
Chapter 3. Control Description and Implementation
(3.8)
A/D converter, represents the zero order hold block. This is always required after the
ideal sampler [22]. The transfer function of the zero order hold is [22]:
(3.9)
Plant, represented by the electrical equations (2.18) and (2.19) of the machine, after the
decoupling terms have been eliminated. The remaining components, inductance and
resistance, form a first order transfer function.
(3.10)
A simplification in the system is made by combining the zero order hold block
plant
, with the
, to create only one transfer function.
(3.11)
To determine the system expression, a flow graph (Fig. 3.6 part c)) of the system has to be
created. The flow graph is created to represent the sampler influence, using dashed line. The
sampler imposes a problem in the system because it does not have a transfer function [22].
Once the flow graph is created, the signals are attributed to the correct position. A note has to be
made here regarding the starred variables
and transfer functions.
.
These starred variables and transfer functions appear in the system because of the ideal sampler
and have a direct link to the z domain [22].
(3.12)
To determine the system output, it has to be expressed like the sampler input, in terms of the
system input and sampler output [22].
(3.13)
(3.14)
Starring (3.13), and solving for
yields:
(3.15)
Transferring (3.14) in the z domain and replacing
using (3.15) yields:
(3.16)
27
Chapter 3. Control Description and Implementation
Equation (3.16) represents the closed loop transfer function of the current controller. To
determine the PI parameters, all transfer functions have to be replaced in (3.16). Because the
plant transfer function (3.11) is in the s domain, it has to be transferred to the z domain first.
(3.17)
The transfer function
is separated in two transfer functions, continuous transfer
function
and starred transfer function
, to simplify the procedure. These two transfer
functions are then transferred to z domain separately.
(3.18)
By defining
, and using the z transform tables,
(3.19)
The starred transfer function is transferred to the z domain using (3.12).
(3.20)
Replacing (3.19) and (3.20) in (3.17) yields:
(3.21)
A bode diagram is plotted in Fig. 3.7 to present the difference between the continuous plant
transfer function (3.10), and the discrete transfer function (3.21). From the response it can be
seen that the influence of the zero order hold block (3.9) is very limited.
Fig. 3.7. Bode diagram of continuous transfer function (3.10) and discrete transfer function (3.21)
28
Chapter 3. Control Description and Implementation
Replacing (3.7), (3.8) and (3.21) in (3.16), yields:
(3.22)
Using all transfer functions obtained, and the design requirements imposed at the beginning, the
PI parameters are determined usin Matla ’s application, Control System Tunin .
The determined PI controller is:
(3.23)
From
Fig. 3.8 it can be seen that for the selected PI parameters, the steady state error is below 1%, no
overshoot appears, the rise time is 8.2 [ms] and the settling time is 18.4 [ms]. All these
parameters correspond to the requirements imposed for the controller.
Fig. 3.8. Step response of the current closed loop transfer function (3.22).
From Fig. 3.9 it can be seen that the system is stable because all the poles are situated inside the
unity circle. Furthermore, a gain margin of 23.9[dB] and a phase margin of 85.8 [deg] can be
observed in the open loop Bode plot, which ensures the loop to be stable.
From the last plot, where the closed loop Bode diagram is presented, the bandwidth of the
controller can be obtained. For the current control loop the bandwidth is 277 [rad/sec].
29
Chapter 3. Control Description and Implementation
Fig. 3.9. Plots of the current control system: a) Root locus, b) Open loop Bode and c) Closed loop Bode
3.2.3 Flux control loop
Because the flux control loop is part of the electrical system, like the current control loop, it has
to have similar response time and bandwidth. In order to simplify the control, the same PI
parameters are adopted for the flux control loop, as for the current control loop.
This simplification is made, because field weakening was not considered to be an objective for
the project, thus a lower importance is given to this procedure.
3.2.4 Speed Controller
The speed controller applied in FOC has to provide the reference
current to the current
controller. Because the output of the speed controller is the torque, it has to be converted to
current by a coefficient , which is determined using (2.24).
(3.24)
30
Chapter 3. Control Description and Implementation
As for the current controller, the machine equation is required to develop the control. In this case
the mechanical equation is used (2.24), in which the speed is a function of the torque.
To better understand the structure of the system a block diagram is presented in Fig. 3.10. Here it
can be observed that the current control loop is situated inside the speed control loop.
l (z)
ωr_ref (z)
E(z)
+
-
Cω(z)
Te_ref (z)
kt
Iq_ref (z)
Hcl(z)
Iq (z)
(z)
1/kt
+
-
W(z)
ωr (z)
ωr (z)
Fig. 3.10. Block diagram of the speed control loop.
The transfer functions are:
PI controller;
(3.25)
, where:
- speed proportional gain;
– speed integral gain;
Current loop, represents the close loop transfer function of the current, determined
earlier after the PI was selected. The transfer function is presented in (3.22).
Plant, represented by the mechanical equation (2.24) of the machine;
(3.26)
Because the plant is in s domain, it has to be transferred to z domain before the closed loop
transfer function is determined. To diversify the procedure, Matlab is used this time to obtain the
discreet time transfer function.
(3.27)
As or the current control loop, Matla ’s Control System Tuning application was used to
determine the PI coefficients.
(3.28)
From Fig. 3.11 it can be seen that for the selected PI parameters, the steady state error below 1%,
the overshoot is 2.1 [%], the rise time is 86.7 [ms] and the settling time is 144 [ms]. All these
parameters correspond to the requirements imposed for the controller.
From Fig. 3.12 it can be seen that the system is stable because all the poles are situated inside the
unity circle. Furthermore, a gain margin of 39.2[dB] and a phase margin of 83.6 [deg] can be
observed in the open loop Bode plot, which ensures the loop to be stable.
31
Chapter 3. Control Description and Implementation
Fig. 3.11. Speed control step response (continuous).
The last plot presents the bandwidth of the controller, which is 24.27 [rad/s]. The ratio between
the bandwidths of the two controllers is 277/24.27 = 11.27. Because the ratio between the two
controllers is greater than 10, the last requirement is fulfilled.
Fig. 3.12. Plots of the speed control system: a) Root locus, b) Open loop Bode and c) Closed loop Bode.
32
Chapter 3. Control Description and Implementation
The last components of the control that have to be implemented are the limitations. These
limitations maintain the output of the PI controller in a safety region. However, when the output
of the PI exits the safety limit, a phenomenon called integrator windup appears [23]. Because this
phenomenon can affect the performance of the control, it is analysed in the following.
3.2.5 Anti-Windup
The windup phenomenon appears mainly when a large error is sent to the PI, error which
determines the output to vary outside the safety limit. Because the output is limited, the input
error cannot be reduced as fast as the controller requires. This behaviour, determines the
integrator term to increases significantly in order to correct the input error, phenomenon also
called windup [23]. The windup effect has to be eliminated from the system because it produces
a large overshoot and a high settling time [23].
In order to deal with this problem a tracking anti-windup solution is used, Fig. 3.13 [23, 24].
e(t)
y(t)
kp
ylim(t)
++
-
elim(t)
1/s
I(t)
+
+
+
ki
1/kp
Fig. 3.13. PI controller with anti-windup.
This solution is explained starting with the classical PI controller, without anti-windup, which is
created using the following equations:
(3.29)
(3.30)
(3.31)
To avoid integrator windup the input error
has to be reduced for the integrator sum
,
when the system enters saturation mode. The new input error
has to ensure that the
output is identical with limited output (
) [24].
(3.32)
From (3.30) and (3.32) the new error can be determined.
33
Chapter 3. Control Description and Implementation
(3.33)
Using the new error to determine the integrator sum, the new controller equations can be written.
(3.34)
(3.35)
(3.36)
From (3.38) it can be observed that the new error is used only to calculate the integrator sum, the
proportional part of the control uses the original error
.
Once the PI controllers are implemented with anti-windup, the only remaining problem is to
determine the rotor position. Because a sensorless method was selected to determine the rotor
position, this method will be presented in the following.
3.3 Rotor Position Estimation
The method used to determine the rotor position and speed is generally known as the back-EMF
method [11, 25, 26]. In order to estimate the position, the mathematical model of the machine, in
dq reference frame is used (2.18) and (2.19).
The two equations can be written in vectorial form as:
(3.37)
(3.38)
The method requires that the equations should be transferred to αβ reference frame:
(3.39)
(3.40)
Since the position term
appears only in the flux linkage equation (3.40), this will be the
equation from where the position will be computed. An important transformation must be made
in order to extract the position.
(3.41)
In order to better understand the meaning of each term in the equation it is written in the
following form:
(3.42)
34
Chapter 3. Control Description and Implementation
From (3.42) it can be seen that the direct current component affects only the amplitude, of the
vector that contains the rotor position information. Knowing this, the rotor position (angle), can
be expressed.
(3.43)
The estimated rotor position can be obtained using the following equation:
(3.44)
Some problems must be considered when using this method, as: integration requires an initial
value and a small drift in current value will cause increasing error after integration [21]. Because
these influences can affect the computation, rendering the method unviable, an adaptive
correction has to be implemented.
The correction method that was selected to be implemented in this project uses two elements: a
drift compensation loop and a phase lock loop (PLL) [21, 26]. In the following, both methods
will be explained along with the implementation method.
 Drift Compensation Loop
This subsystem is implemented to eliminate the error before integration, by comparing two flux
values in stationary reference frame
. The first
flux value is obtained using (3.44). The
second flux value is determined in dq reference frame, using (2.20) and (2.21), result which is
transferred to
reference frame.
The difference between the two fluxes represents the error sent to the PI controller. As output,
the PI controller produces a voltage component
, which is used to eliminate the drift.
35
Chapter 3. Control Description and Implementation
Drift Compensation Loop
θr_PLL
αβ
dq
idq
Eq. (2.20) λdq
and (2.21)
dq
αβ
λαβ
kpc, kic
+
-
vcomp
vαβ
λαβ
++
Phase Lock Loop
kpp, kpi
-
Eq. (3.44)
R
Lq
θr_estim
+
ωe_PLL
θr_PLL
-
iαβ
Back EMF Method
Fig. 3.14. Block diagram of back-EMF method along with drift compensation and PLL [21].
 Phase Lock Loop
The PLL implemented in the system is placed after the back-EMF method. It is used to eliminate
the error in the estimated position, by taking as an input the estimated position (3.44) and
comparing it to the output of the PLL, which will represent the actual estimated rotor position.
The main disadvantage of the back-EMF method comes from its name. The method is unable to
provide the correct information at very low speeds. This is because the back-EMF term contains
the speed variable. When the speed is close to zero, the back-EMF term is very small, and the
estimated position is not precisely estimated.
Because of this problem, during the start up procedure, the rotor will produce an initial vibration,
until the alignment is achieved, followed by a smooth transition, until the reference speed is
reached. This problem was observed in simulations and in laboratory experiments.
36
Chapter 4. Simulations
4
Simulations
The model created, along with the control, is tested during a series of simulations to observe the
performance. The simulation conditions are selected considering the objectives imposed in the
first chapter. This chapter will present the result of each simulation, along with necessary
explanation. All simulation are made using Matlab Simulink. To get familiarized with the Matlab
Simulink model, an overview is presented at the beginning.
4.1 Model Overview
As it could be seen in Fig. 4.1 the model consists out of three main blocks: permanent magnet
synchronous machine, field oriented control, and speed and position estimator.
Besides the main blocks, three selectors are employed to allow the user a fast change between
different load types and different working conditions.
Fig. 4.1. Matlab Simulink model of the system.
A more complex model, containing more components, like the three level NPC converter, AC
voltage source, diode bridge rectifier and SPWM, was also created. Because both models provide
similar results, the simplified model is used for the report.
Using this model, a series of simulations are made. These simulations are developed to test the
control for all the requirements imposed in the objectives.
37
Chapter 4. Simulations
4.2 Scalar Control Simulations
According to the description provided in previous chapters, scalar control is unable to operate in
all situations required by the objectives. Because of this factor, and because the dynamic
performance is reduced, compared to vector control, this is considered to be an alternative
control strategy, not the main control. Only two simulations are made using scalar control, to
verify how the control reacts during speed variation and during load torque disturbance.
4.2.1 Speed reference variation
The first simulation is made to test how the control behaves when the reference speed is
modified. From Fig. 4.2, it can be seen that during the starting procedure small oscillations in
speed appear. These oscillations appear because the position imposed from the reference
frequency is not aligned with the rotor position.
Fig. 4.2. Result of speed reference variation using scalar control.
As it could be seen from Fig. 4.2 and Fig. 4.3, the current is sinusoidal with a constant magnitude
during the entire simulation time. Small changes in current magnitude appear only during the
transient regime.
For a better view of voltage and current in steady state, Fig. 4.3 presents a closer perspective.
Here we can observe that the current and the voltage are sinusoidal, with a phase shift of
appro imately .
The large phase shift, which determines a small power factor, appears because the simulation is
done without adding a load to the system. Without a load, the active power required by the
machine is very small. Because the control maintains the current at a high value, even during no
38
Chapter 4. Simulations
load situation, a significant amount of apparent power is provided at the terminals, power which
becomes reactive power, as it was explained in Scalar Control (I-f Control).
This large phase shift, combined with the current magnitude, determines an inefficient operation.
Fig. 4.3. Voltage and current in steady state situation.
To increase the efficiency, a modified method is proposed in Scalar Control (I-f Control)
subchapter. This method requires that the reference quadrature axis current
is modified as a
function of frequency, according to Fig. 4.4.
_
Fig. 4.4. Reference quadrature axis current
as a function of frequency.
The maximum current is applied only at the beginning, to provide sufficient torque during the
starting procedure. The reference quadrature axis current
is reduced to 50% of the maximum
value
, when the frequency reaches nominal value.
The result of the simulation, presented in Fig. 4.5, shows that speed and the torque characteristics
are not affected by this modification.
39
Chapter 4. Simulations
An important difference can be observed in the current waveform. In this situation the current
has smaller amplitude, when the system enters steady state. However, from the result it can be
seen that the oscillations have increased.
Fig. 4.5. Speed reference variation using scalar control (modified version).
To analyze the phenomenon, several simulations are done at different reference currents. From
the results it was observed that the oscillations increase as the current is decreased. The reference
current has to be maintained above a minimum value, to ensure system stability.
The disadvantage is that the minimum current value cannot be determined analytically because it
is affected by numerous other parameters as, load torque, reference speed variation and PI
parameters.
4.2.2 Load torque variation
The second simulation is made to determine how the control behaves when an external
mechanical load is applied.
From Fig. 4.6, it can be seen that the control is able to maintain the speed within ±2.4% of the
nominal speed.
This fast response is due to the fact that the electromagnetic torque has a fast response time, to
counteract the load torque applied at the shaft.
From both the current and electromagnetic torque waveform, it can be seen that oscillations
appear in the system before it enters steady state. These oscillations are caused by the fast
response of the PI controllers.
As for the previous situation, the current and voltage variation is sinusoidal.
40
Chapter 4. Simulations
Fig. 4.6. Result of load torque variation using scalar control.
From the simulation, an increase in power factor is observed, when the load torque is applied.
This is due to the fact that a higher amount of apparent power, supplied at the machine terminals,
is used as active power.
4.3 Vector Control Simulations
Because this control is considered to be the primary control strategy for the drive, it will be
tested in five different situations, according to the objectives.
The first two tests are made in similar conditions as the test made for scalar control. The
difference is that for vector control, the reference speed is given using the step command, not the
ramp command.
4.3.1 Speed reference variation
As for the previous case, the main objective of this simulation is to observe how the control
behaves when the reference speed is modified.
Because the control is implemented using speed and position estimator, the performance of the
estimator is also of main interest.
From Fig. 4.7, it can be seen that the control is able to provide a fast response, when the
reference speed is modified.
41
Chapter 4. Simulations
Fig. 4.7. Result of speed reference variation using vector control.
Compared to scalar control, a higher efficiency is achieved, because the current reference is
provided by the outer speed loop.
From Fig. 4.8, it can be seen that the speed and position estimator is able to produce an accurate
estimation, in less than a second. The fast response of the estimator enables the control to start
the machine without the use of an encoder.
Fig. 4.8. Comparison between actual and estimated position, and speed.
42
Chapter 4. Simulations
4.3.2 Load torque variation
In the second simulation, the capability of the control to react in case of a load torque disturbance
is tested. From the results presented in Fig. 4.9, it can be seen that the control manages to
withstand the torque step. The speed of the machine decreases with approximately 18% of the
nominal speed, when the load torque is applied. The maximum speed achieved, when the load
torque is removed, is 12.5% the nominal speed.
Fig. 4.9. Result of load torque variation using vector control.
From the current waveform it can be seen that compared to scalar control, no oscillations appear.
The current is maintained inside the safety boundaries during the entire period.
4.3.3 Transition from motor to generator
As stated in the Converter and Control for DeepWind Programme subchapter, the Darreius wind
turbine is unable to start without the help of the machine. Because of this factor, the machine has
to be controlled in motor mode, until the required speed is achieved. Once the turbine is able to
capture the wind power, the control must ensure a safe transition from motor to generator.
In order to test the transition from motor to generator and back, a load torque is applied at the
shaft, having the same direction as the speed (Fig. 4.10).
From Fig. 4.11, it can be seen that the simulation result is very similar with the previous case.
When the load torque, having the same direction as the speed, is applied, the speed of the drive
increases too approximately 19% of the nominal speed. To maintain stability, the control
counteracts the load torque by changing the direction of the electromagnetic torque.
43
Chapter 4. Simulations
Te
ωr
Te
ωr
Motor
Generator
Tl
Tl
Fig. 4.10. Speed and torque direction for motor and generator mode.
Once the direction of the electromagnetic torque is opposite to the speed direction the machine
enters generator mode. This operation mode continues until the load torque is removed.
Fig. 4.11. Result of transition from motor to generator and back.
As it can be seen from the current waveform, the amplitude is maintained constant, inside the
safety boundaries, during the entire procedure.
4.3.4 Emergency breaking
As it was explained in the Converter and Control for DeepWind Programme subchapter,
mechanical breaks cannot be fitted to the turbine. The control must be capable to stop the turbine
in case of an emergency, as high wind or high waves.
To emulate such a situation, the load torque was maintained constant during the breaking
procedure, while the speed was brought down to zero in two seconds.
The speed was decreased using a ramp variation because of the following reasons:
44
Chapter 4. Simulations
- In case of a large structure, as the wind turbine is presumed to be, the transition
from nominal to zero speed has to be smooth;
- To observe how the control behaves when the reference is given as a ramp
command.
From the result presented in Fig. 4.12, it can be seen that between the reference and the actual
speed there is a constant steady state error. This error is removed after the reference speed
reaches zero.
Fig. 4.12. Result of emergency breaking.
When the speed reaches zero, the estimator cannot provide the correct position and speed
information, as it can be seen in Fig. 4.13. Because the simulation uses a simplified model, the
speed of the machine is maintained constant at zero, while a load torque is applied, even though
the estimated position is not similar with the actual position.
In a practical experiment, there are many other parameters that influence the control, which have
to be considered, in order to ensure stability. The discussion regarding stability at very low
speeds, in a practical system, is presented in Laboratory Experiments.
After the speed has reached zero and the load torque is removed, the control has to reduce the
electromagnetic torque, in order for the speed to remain constant at zero.
45
Chapter 4. Simulations
Fig. 4.13. Comparison between actual and estimated position, and speed, for the low speed range.
4.3.5 Holding the machine at zero speed
The last test required by the objectives is to maintain the speed of the machine at zero, while a
load torque is applied.
Because the speed and position estimator cannot provide information about the position when the
speed is zero, the control has difficulties to maintain the speed in a small interval, when a load
torque is applied.
The control can react to torque disturbance, only after the estimator provides the proper position.
Until the position is determine, the speed of the machine can increase to a high value.
From the simulation result (Fig. 4.14), it can be seen that the speed reaches a maximum value of
30% of the nominal speed.
After approximately half a second, the position estimator is able to determine the actual position
(Fig. 4.15), causing the control to ensure a smooth transition to zero speed.
When the load torque is removed, the control produces an oscillatory response, until the speed
becomes zero.
46
Chapter 4. Simulations
Fig. 4.14. Result of holding the machine at zero speed.
As for the previous case, the simplified model cannot recreate very accurate the practical
situation. To have a better understanding of how the real system behaves during this experiment,
please refer to Laboratory Experiments.
Fig. 4.15. Comparison between actual and estimated position, and speed, during holding the machine.
47
Chapter 5. Hardware Design of Converter
5
Hardware Design of Converter
In this chapter the design and the main circuits of the three level NPC converter are presented.
Because the design was not an objective for this project, only the main parts of the converter will
be presented here, with sufficient explanation in order for the reader to understand the hardware
used. For more information about the design and the components, please refer to [7].
5.1 General Structure
Based on [7] and Fig. 5.1 it can be seen that the design is made in such a way as to separate the
hardware into two isolated regions: the power side and the control side.
Power Side
A
B
Control Side
C
CS
A
A
3x IGBT
Modules
12 x PWM
12x Gate Driver
3x Thermistors
OT
6 x PWM
12 x PWM
12x
GDF
1x
CPLD
XC9572XL
CS
OC
A
-
Insulation Bridge
A
OC
E-PWM
2x
User
7x
LED
ADC
DSP
TMS320F28335
ADC
OV
VS
V
V
DC Link
+
+
+
DC
Fig. 5.1. Simplified schematic of constructed converter [7].
49
RS-232/485
CAN
3x
TS
A
Chapter 5. Hardware Design of Converter
To facilitate the communication between these two regions, gate drivers, current sensors, voltage
sensors and temperature sensors are used, which ensure that the two regions are decoupled. Also,
it should be mentioned that the converter is constructed on a four layer printed circuit board
(PCB), with stacked DC link layout, ground and power planes, in order to reduce the interference
between different circuits [7].
In the following of this chapter, the main circuits from these two regions are presented.
5.2 Power Side
Besides the power components (IGBT modules and capacitors), the power side of the converter
is made out of a series of measurements circuits. These measurement circuits represent the main
advantage of this design, because using the signal acquired, a series of protections are
implemented, as it can be mentioned: three phase AC over-current protection, DC over-current
protection, DC over-voltage protection, over-temperature protection and gate driver protection.
All these main circuits will be shortly presented in the following, in order to highlight the
components used and their functionality:
b) Capacitor bank, made out of six 330 μF Panasonic capacitors, arranged in three parallel
arms between the +HVDC and 0HVDC and three parallel arms between –HVDC and
0HVDC.
c) Three IGBT modules, each representing one leg of the three level NPC converter;
The IGBT modules are produced by Semikron (SK50MLI065), and have the following
properties, according to the datasheet [27]: compact design, 600V/50A per IGBT, direct copper
bounded aluminium oxide ceramic (heat transfer and isolation), snubber-less design, improved
commutation paths, controlled axial lifetime technology for freewheeling diodes.
d) Voltage dividers, each constructed out of four high value resistors, used in the DC
voltage measurement circuit to ensure a permanent connection to the DC link by reducing
the current below the resistor current capability and to provide DC link voltage
measurement;
e) Three NJ28 high accuracy thermistors, used in the over-temperature protection circuit
to detect the temperature of the IGBT modules. The thermistors have a negative
temperature coefficient (NTC), meaning that the resistance decreases, while the
temperature increases. At C the resistance is 100 [kΩ].
f) Five Hall current sensors, two for the DC side and three for the AC side, used to
measure the high currents in the power region and output a reference voltage value which
will be used in the control region for over-current protection and as measurement for the
DSP;
The current sensors used in this design are Allegro ACS756 Hall Effect IC Sensors, which have
the following properties [28]: total output error of 0.8%, very low power loss (130μΩ resistance),
50
Chapter 5. Hardware Design of Converter
3kV isolation, small magnetic hysteresis, measurement of ±50A, and 2.5V output for 0A with
±40mV/A characteristic.
For each measurement circuit, only the components situated in the power side have been
presented here, while the rest of the circuits, which are situated in the control side, are presented
in the following section.
5.3 Control Side
The control side of the converter is comprised of circuits which ensure the command, protection,
signal acquisition and communication. Because all these circuits are explained in [7] only the
main features of each circuit will be presented in the following, to help the reader understand the
principle of operation.
1) Gate Driver Circuit
The gate driver Avago ACPL-332j was selected for this design to ensure the interface, protection
and isolation between the power side and the control side.
The Avago ACPL-332j gate driver has the following features [29]: optically isolated power stage
capable of driving IGBTs up to 150A and 1200V, desaturation detection, isolated fault feedback,
active Miller clampin , “so t” IGBT turn o , . A output current, small packa e.
The PWM signal, sent from the command circuit to the gate driver, is applied to the anode and
cathode of the LED situated inside the gate driver. The LED is used in the gate driver to ensure
galvanic isolation between the power side and the command side.
To ensure desaturation protection, the collector-emitter voltage
is monitored during the
conduction. If this voltage rises above 6.5V the IGBT is turned off and a fault signal is
generated. To avoid false triggering the desaturation detection is disabled when the IGBT is not
conducting.
2) Command Circuit
The modulation PWM signals provided to the gate drivers are generated by the digital signal
processor (DSP). In the current configuration, the DSP only provides the signals for the upper
two switches, of each leg. These six PWM signals are transmitted to the complex programmable
logic device (CPLD), as it can be seen in Fig. 5.2.
Using the six PWM signals, the CPLD will generate the complementary PWM signals for the
lower two switches of each leg, while introducing the dead time between the complementary
signals.
All twelve PWM signals, from the CPLD, are transferred to a pair of octal buffers
(SN74LVC540A), six PWM signals for each octal buffer. The octal buffer used in this design
acts as a NOT logic circuit. This is because the anode of the LED, situated inside the gate driver,
is connected to a 3.3V DC source, and the cathode is connected at the output of the octal buffer.
51
Chapter 5. Hardware Design of Converter
E
6xPWM
6x
Gate
Drivers
DSP
6x
CPLD
6x
6x
4x
IGBT 1
4x
IGBT 2
4x
IGBT 3
Octal Buffer
pwm E
D
User
Fig. 5.2. Block diagram of the command circuit.
In this configuration, when a signal is transmitted from the CPLD, 3.3V or logic 1, the octal
buffer inverts the signal to 0V or logic 0. The 0V state is transferred to the cathode and a
potential difference appears at the LED terminals, enabling the current to pass through the LED,
which commands the IGBT to conduct.
In the opposite situation, when the CPLD gives the 0V, or logic 0 command, the octal buffer
inverts the signal to 3.3V, or logic 1. In this situation, because the cathode has the same potential
as the anode, the current will not flow through the LED, which commands the IGBT not to
conduct.
The octal buffers presented in the circuit are also used as a safety feature. When a fault is
detected in the converter the octal buffers are disabled and the command to the gate drivers is
blocked.
The user has the possibility to control the command circuit through two external buttons. The
first button (pwm E) is used to trigger the PWM modulation, while the second button (D) is used
to disable the modulation and to reset the protections.
3) Current Measurement Circuit
As stated earlier, five Hall current sensors are used in the converter. Two sensors are used for the
DC link current and three sensors are used for the AC phase current. The current measurement
circuit is implemented only for the AC phase current sensors. The circuit is comprised of the
following components:
- Hall current sensor, presented earlier, which gives a reference of 2.5[V] at 0[A],
and has a ±40 [mV/A] characteristic.
- Voltage divider, is used to reduce the voltage level at 1.6667[V] for 0[A], with a
characteristic of ±26.6667 [mV/A]. This is done because the input signal to the
DSP has to be in the 0-3[V] range.
52
Chapter 5. Hardware Design of Converter
- ADC buffer, constructed from an operational amplifier which is configured as a
voltage follower, to isolate the ADC input of the DSP from the signal source;
- Two pairs of dual series small signal Schottky diodes, one before the ADC buffer,
and the other after the ADC buffer; used to limit the voltage signal in the 0-3[V]
range;
- ADC input port of the DSP;
To have a better understanding of how these components are connected to form the current
measurement circuit, a bock diagram of the circuit is presented in Fig. 5.3.
Voltage Dividers
Vin
R1
i
LEM
2.5V
±40mV/A
R2
Schottky Diodes
ADC Buffer
Schottky Diodes
3V
Vout
Vin
1.6V
±26.6mV/A
DSP
3V
Vout
-
Vin
Vout
+
ADC
Current Sensors
Vin
Vout
Fig. 5.3. Block diagram of current measurement circuit.
4) Over-Current Protection
The over-current protection circuit is implemented for all five current sensors. By doing this,
protection is ensured for the DC side and for the AC side of the converter.
The over-current protection circuit is comprised out of (Fig. 5.4):
- Hall current sensor, same as for the current measurement circuit;
- Window comparator; for each measured signal a window comparator is used, to
compare the signal with two reference signals, maximum and minimum reference.
These two references can be set by the user through variable resistors. When the
measured signal is between the two boundaries the window comparator has a high
output state, which signals correct operation.
- Logic AND circuit. The signals from the window comparators are entered a logic
AND circuit, and the result is sent to the CPLD.
- CPLD, receives the signals from the AND circuit and takes the appropriate action.
Current Sensors
Window Comparators
Up Limit
Signal
LEM
2.5V
±40mV/A
Down Limit
AND
5V
Fig. 5.4. Block diagram of the over-current protection circuit.
53
CPLD
i
5V
Chapter 5. Hardware Design of Converter
5) Voltage Measurement Circuit
In order to protect and control the converter, a voltage measurement circuit, for the DC voltage,
is implemented on the converter. The circuit is comprised of (Fig. 5.5):
- Voltage dividers; as mention earlier, four voltage dividers are used to acquire the
voltage signal from the DC link.
- Differential amplifier; Two differential amplifiers are used to manipulate the
signal received from the voltage dividers.
- Voltage dividers; at the output of each differential amplifier a new voltage divider
is placed to reduce the voltage level which goes to the ADC buffer;
- Schottky diodes and ADC Buffer with the same structure as for the current
measurement circuit.
Differential Amplifier
+
+
Vin1
Vin2
DC
R1
Voltage Dividers
R2
R1
-
Vin
R1
Vout
+
+
R2
6V
R2
Schottky Diodes
ADC Buffer
Schottky Diodes
3V
Vout
Vin
1.52V
Vout
DSP
3V
Vin
-
Vout
+
Vin
Vout
ADC
Capacitor Bank
-
Fig. 5.5. Block diagram of the voltage measurement circuit.
Using this signal and the current signals a closed loop control can be implemented on the
convertor, in order to increase the dynamic performance of the drive.
6) Over-Voltage Protection
In order to ensure the DC over-voltage protection and to simplify the hardware structure the
circuit is comprised of components similar with the voltage measurement circuit and overcurrent protection circuit:
- Voltage dividers, differential amplifier and voltage dividers (components
presented in the voltage measurement circuit);
- Window comparator; for each measured signal a window comparator is used, to
compare the signal with two reference signals, maximum and minimum reference.
These two references can be set by the user through variable resistors. When the
measured signal is between the two boundaries the window comparator has a high
output state, which signals correct operation.
- Logic AND circuit. The signals from the window comparators are entered a logic
AND circuit, and the result is sent to the CPLD. In this way the CPLD is
announced if an over-voltage situation appears in the converter.
- CPLD, which receives the signal from the fail gate and takes the appropriate
action.
The circuit structure, in block diagram form, is presented in Fig. 5.6.
54
Chapter 5. Hardware Design of Converter
Differential Amplifier
+
R1
+
Vin1
R1
Vin2
DC
Voltage Dividers
R2
-
Vin
R1
Vout
+
+
6V
R2
Window Comparators
Up Limit
Vout
R2
Signal
1.52V
Down Limit
AND
5V
5V
CPLD
Capacitor Bank
-
Fig. 5.6. Block diagram of the over-voltage protection circuit.
7) Over-Temperature Protection
The over-temperature protection circuit is used as a safety feature for long time operation. If the
module temperature increases over a specified limit, the circuit is disabled and the fault is
signalled to the user. The circuit is made out of the following components:
- Signal conditioning circuit; the thermistors are connected in a resistive circuit in
order to modify the NJ28 characteristics.
- Window comparators; In this case the window comparator works different. The
output of the acquisition circuit is inverted for both comparators, so that the
comparators output is high (healthy situation) if the temperature is below the
preset limits.
- Two logic AND gates are used to deal with the temperature measurement circuit,
because there are two preset limits of temperature.
- CPLD receives the signal from the fail gate and takes the appropriate action.
Thermistor Circuit
Window Comparators
5V
T
R1
Vout
R2
AND
First Limit
Signal
CPLD
Second Limit
5V
5V
Fig. 5.7. Block diagram of the over-temperature protection circuit.
8) Communication Circuit
The converter has also implemented two communication circuits, CAN and RS-232/485, in order
to facilitate the communication between the converter and an external program. Because this
feature is not used in the current project it is not presented here. To get some knowledge about
these two circuits please refer to [7].
55
Chapter 6. Laboratory Experiments
6
Laboratory Experiments
This chapter presents the practical work done in the laboratory. At the beginning, the laboratory
setup used to do all the experiments is presented. The experimental results are separated in two
parts, based on the type of control implemented. The first part presents the tests done using
scalar control, while the second part presents the tests done using vector control. The tests done
on the drive are selected to be similar with the simulations.
6.1 Laboratory Setup
Vsin
Autotransfromer
The laboratory setup used to do all the tests is presented in Fig. 6.1. The components that
comprise the setup are: voltage source (grid), autotransformer, three phase diode bridge rectifier,
resistor, three level NPC convertor, PMSM, load machine, converter for the load machine and
voltage source for the converter (grid). Also, two personal computers (PC) are used to
independently control the two converters.
iDC
3 Phase
Diode
Rectifier
iR
RDC
Vsin
iconv
+
3 Level
NPC
Converter
Vdc
iA
iB
iC
PMSM
Load
Machine
Drive
Converter
-
PC 1
PC 2
Fig. 6.1. Bloc diagram of laboratory setup.
In order to drive the PMSM, power is taken from the grid through an autotransformer and a three
phase diode bridge rectifier. The autotransformer is used to adjust the DC link voltage at the
output of the three phase diode bridge rectifier.
The configuration with autotransformer, diode bridge rectifier and resistor is used, instead of a
simple DC voltage source, because the machine has to be controlled in generator mode. When
the machine is working in generator mode, the three level NPC converter will behave as a
rectifier, sending the AC power from the PMSM to the DC link. In this situation the power will
be dissipated on the resistor, because the three phase diode bridge rectifier will block the power
flowing to the grid.
A second synchronous machine is connected to the shaft of the PMSM, to act as a mechanical
load. Torque control is implemented as a control strategy on the load machine.
57
Chapter 6. Laboratory Experiments
A more in depth presentation of the laboratory setup is made in the videos written on the CD,
which is attached to this report.
Because the DC link voltages are very similar for all the experiments, these results are presented
in Appendix B, to avoid presenting very similar oscilloscope captures and repeating the same
conclusion for each situation.
As stated in the chapter description, the following section will be divided in two parts. The first
part presents the tests done using sensorless scalar control, while the second part presents the
tests done using sensorless vector control.
6.2 Scalar Control Experiments
6.2.1 Speed reference variation
The speed control capability is tested in the first experiment. Because the dynamic response of
the control is slower, the speed reference is modified using a ramp variation.
At the beginning the machine is started from zero to nominal speed in two seconds. As it could
be seen in Fig. 6.2, no initial vibration occurs in the rotor during the starting procedure.
It has to be noted here that after numerous test made in the laboratory, it was observed that for
different initial rotor positions, rotor vibrations can occur during the start up. To examine this
behaviour the starting procedure was repeated at different initial rotor positions. From the results,
it was observed that the rotor vibration depends on the initial position, and the control is able
start the machine independent of the rotor position.
Fig. 6.2. Machine speed during speed reference variation (scalar control).
The speed of the machine is maintained at the same level for another two seconds, before is
reduced to 50% of the nominal speed, in two seconds. After another two seconds, the speed is
increased to nominal speed. The last part of the control focuses on stopping the machine. The
speed of the machine is brought down to zero with a ramp variation, in two seconds.
58
Chapter 6. Laboratory Experiments
The waveform of the phase current, during the entire test procedure is presented in Fig. 6.3.
From this figure it can be seen that variations in current magnitude appear only during the
transition period. In steady state, the control is able to maintain the amplitude of the current at
the reference value during the entire testing procedure.
Fig. 6.3. Current waveform during scalar speed control (
).
Similar to the simulation, a second experiment is done, where the reference quadrature axis
current
varied as a function of frequency (Fig. 4.4). The current waveform for the second
situation is presented in Fig. 6.4.
Fig. 6.4. Current waveform during scalar speed control (
.
The decrease in current magnitude can be observed in the first region of Fig. 6.4. Compared to
the initial situation, more powerful oscillations appear in the system. Because the result obtained
here is similar with the simulation, the same conclusions are valid.
6.2.2 Load torque variation
As a second test, the load torque is modified in steps, to test the response of scalar control, when
a load disturbance appears in the system. The result presented in Fig. 6.5 shows that the control
59
Chapter 6. Laboratory Experiments
is capable to maintain the stability of the system. When the load torque is applied, the speed
decreases only 1.4% from the nominal speed. System stability is achieved again, after one
second of transitory regime.
Fig. 6.5. Machine speed (red) and load torque (blue), during load torque variation (scalar control).
When the load torque is removed, the speed increases with the same magnitude as for the
previous case. A decreasing oscillatory regime is encountered in this situation, compared to the
previous one. These oscillations can also be observed in the current waveform Fig. 6.6.
This test is done with the reference quadrature axis current
constant, to better highlight the
disadvantage of this method. Although the control is able to maintain the current at a constant
value, as it is required, this operating procedure is not efficient.
Fig. 6.6. Current waveform during load torque variation (
).
6.3 Vector Control Experiments
6.3.1 Speed reference variation
All the conditions used to do the simulation are applied for this laboratory experiment.
60
Chapter 6. Laboratory Experiments
From Fig. 6.7, it can be seen that the control is able to start the machine in 0.5 seconds, with no
initial rotor vibrations. It has to be noted here, that similar to scalar control, the vibration is
dependent on the rotor initial position.
Fig. 6.7. Machine speed during speed reference variation (vector control).
The reduced transition time between steady state situations, highlights the superior dynamic
performance of vector control, compared to scalar control.
From the current waveform, presented in Fig. 6.8, it can be seen that the current is maintained
between the safety boundaries, during the transient regime. Also, a far better efficiency is
achieved, compared to scalar control, through MTPA strategy.
Fig. 6.8. Current waveform during vector speed control.
6.3.2 Load torque variation
In the second test, the stability of the control, during load torque variation, is tested. The load
torque is applied at the shaft, using the secondary machine. The result of the test is presented in
Fig. 6.9. As it can be seen, when the load torque is applied, the control is capable to correct the
3.6% speed decrease, in approximately three seconds.
61
Chapter 6. Laboratory Experiments
When the load torque is removed, the speed reaches a maximum value of 6%, above the nominal
speed. As for the previous situation, the control is capable to ensure stability, by reducing the
speed at nominal value, in approximately four seconds.
Fig. 6.9. Machine speed (red) and load torque (blue), during load torque variation (vector control).
The current waveform, presented in Fig. 6.10, displays the current transition during the entire
experiment. As it can be seen, during the load torque transition, the current is maintained inside
predefined limits to ensure safe operation.
Fig. 6.10. Current waveform during load torque variation.
6.3.3 Transition from motor to generator
From Fig. 6.11 it can be seen that the transitory regime is very similar to the previous case. The
speed increases at the moment when the torque is applied with approximately 1.6%. The control
is able to limit the speed increase and to stabilise the system.
When the load torque is removed, the machine changes to motor mode and the speed decreases.
As for the previous case, the control is able to stabilise the system, and to ensure nominal speed.
62
Chapter 6. Laboratory Experiments
Fig. 6.11. Machine speed (red) and load torque (blue), during motor-generator transition.
The current waveform (Fig. 6.12), during the entire process, is very similar with the previous
case. The control ensures that the current is maintained between the safety margins during the
transition from motor to generator and back.
Fig. 6.12. Current waveform in motor and generator mode.
To observe the current direction during generator mode, the DC link current that enters the
converter was measured with the oscilloscope.
63
Chapter 6. Laboratory Experiments
Fig. 6.13. DC link current (magenta), phase voltage (cyan) and V0 voltage (yellow) in generator mode.
As it can be seen from Fig. 6.13, the DC link current that enters the converter (red line), has a
negative sign, meaning that the current flows from the converter to the resistor.
6.3.4 Emergency breaking
To observe the difference between simulation and experiment, the same test conditions were
used. From Fig. 6.14, it can be seen that the transition from nominal to zero speed is linear. The
control is capable to follow the ramp reference given.
When the speed is reduced close to zero, the control encounters stability problems, because the
speed and position estimator cannot provide very accurate information.
Although the speed of the machine will not be kept constant at zero, the sensorless control can
maintain the speed in a low range, characterised by rotor vibrations.
Fig. 6.14. Machine speed (red) and load torque (blue), during emergency breaking.
In the last part of the test, after the machine is brought down to zero speed, the load torque is
eliminated. In this situation the control maintains the speed at zero, without rotor vibrations.
64
Chapter 6. Laboratory Experiments
The difference between the simulation and experiment is consistent during the low speed
operation. This is because the experiment requires accurate position information to maintain
stability. Because the position cannot be estimated at zero speed, the speed cannot be maintained
zero. In order to obtain better control at very small speed, a dedicated position estimator has to
be implemented in the control.
The current waveform is presented for the entire test in Fig. 6.15. As it can be seen, the current
increases slightly in magnitude, as the speed decreases. When the speed of the machine reaches
values closed to zero, the current maintains a high magnitude to produce sufficient torque.
Fig. 6.15. Current waveform during emergency breaking.
6.3.5 Holding the machine at zero speed
The result of the test is presented in Fig. 6.16. From the result it can be seen that when a load
torque is applied at the shaft, the control encounters problems to maintain the stability.
Similar with the emergency breaking case, at low speed the control is unable to maintain the
speed at a constant zero value. The reason for this problem is the same as for the previous case.
65
Chapter 6. Laboratory Experiments
Fig. 6.16. Machine speed (red) and load torque (blue), during zero speed test.
Another observation has to be made here. If a considerable torque step is applied at the shaft, the
control is not able to counteract, causing instability.
The current waveform from Fig. 6.17, presents a similar behaviour to the previous case (Fig.
6.15). During low speed operation the current is situated inside the safety margins, and has an
irregular form, caused by the poor stability.
Fig. 6.17. Current waveform during zero speed.
66
Chapter 7. Conclusions
7
Conclusions
From the current project a series of conclusions can be drawn. These conclusions are separated
based on the topic they address.
 Conclusions regarding the converter:
The three level NPC converter is a viable solution for this wind turbine application, because it
provides numerous advantages compared to the two level converter, while the disadvantages are
not so significant.
The prototype constructed in the laboratory was able to fulfill all the requirements imposed
during the experiments.

Conclusions regarding the control:
The scalar control strategy implemented in the current project cannot be implemented as the
main control for the wind turbine, because it cannot provide stability in all situations.
Scalar control can be recommended for certain situations, as maintenance situations, when the
speed of the turbine is small [19].
The speed and position estimator provided fast and accurate information, for the medium and
high speed range, as it was observed in simulations and experiments.
Problems were encountered at speeds closed to zero, as it could be seen in the experiments,
because the estimator determines the position from the back-EMF term, which is proportional
with the speed.
The sensorless vector control was able to maintain the stability, and to provide good dynamic
response during the starting procedure.
For a more stable operation at zero and very low speeds, a dedicated estimator has to be
implemented.
67
Appendix A
Appendix A. Reference Frame Transformation
To create the mathematical model o an electrical machine the three phase “a c” system was
initially used, because it relates to the physical machine [30, 31]. Because this system comes
with disadvantages like time varying components and complex differential equations, new
reference frame transformations were developed to deal with these problems. The new variables
obtained, after reference frame transformation, do not have a physical correlation to the real
varia les, which are encountered in the three phase ‘a c’ system.
a) Reference frame transformation from “abc” to “αβ0”
If we consider the three phase system “a c” and the comple domain, in which “a” a is is alon
the real a is, the ”αβ ” system can e developed, where α is alon the real a is, β is alon the
imaginary axis and 0 is the zero component of the three phase system, perpendicular to the plan
of the paper. It should be noted that the αβ0 reference frame is fixed to the stator. The
trans ormations rom “a c” to “αβ ” re erence rame and vice versa are made usin the
transformation matrix presented in [1] and [2] [30, 31].
This new reference frame presents advantages in the study of transient regimes for unbalanced
three-phase circuits [30, 31].
Im
b
[1]
β
α
a
Re
[2]
c
Figure 1. Re erence rame trans ormation rom “a c” to “αβ ”.
b) Reference frame transformation from “abc” to “dq0”
As in the ”αβ ” re erence rame the “dq ” re erence rame is represented in the comple domain,
where the “d” a is is alon the real a is, the “q” a is is alon the ima inary a is and the zero
component is the same [30, 31]. The difference between these two reference frames is that the
“dq ” is i ed to the rotor and it is rotatin with the same speed
compared to the stator.
69
Appendix A
The trans ormation rom “a c” to “dq ” re erence rame is made usin the transformation matrix
presented in, also called Park matrix [30, 31]. To make the trans ormation rom “dq ” ack to
“a c” the inverse o the matri is required. This matri is presented in [4].
Re
b
ωr
Im
[3]
d
q
θ
a
[4]
c
Figure 2. Reference frame transformation from
“a c” to “dq ”.
For this transformation the equivalence between the number of turns in the real machine and in
the equivalent machine is:
[5]
, where:
- number of turns on d, q or a axis;
The alance o powers etween the “a c” and the “dq ” re erence rame is a ected y the
coefficient [30, 31]:
[6]
c) Reference frame transformation from “αβ0” to “dq0”
In many applications it is also required to per orm the trans ormation rom “αβ ” to “dq0”. As
stated e ore the di erence etween the two is that “αβ ” re erence rames is i ed to the stator
and “dq0” re erence rames is i ed to the rotor and is rotatin with the same speed.
The trans ormation rom “αβ ” to “dq ” re erence rame is made usin the trans ormation matri
given in [7], and inverse trans ormation rom “dq ” to “αβ ” is also presented in [8]Error!
Reference source not found..
70
Appendix A
β
d
[7]
ωr
q
θ
[8]
α
Figure 3.Reference rame trans ormation rom”αβ ” to “dq ”.
71
Appendix B
Appendix B. Neutral Point Voltage Balance Results
To ensure neutral point voltage balance, the SVM method presented in Modulation Strategies
subchapter was implemented on the DSP. An RL load was used to test the modulation.
From Figure 4, it can be seen that the modulation produces nine voltage levels (±400V, ±300V,
±200V, ±100V, 0V), as it was expected. All these voltage levels appear because the modulation
index is set to one.
Figure 4. Phase voltage.
From Figure 5, the phase to phase voltage is observed. In this situation, five voltage levels
appear (±600V, ±300V, 0V).
Figure 5. Phase to phase voltage.
For all the experiments done in the laboratory, sinusoidal pulse width modulation is used. This
control does not have the capability to maintain the neutral point voltage balance, when an
external influence appears. However, if no such influence appears, the balance is maintained
naturally by the modulation, as it can be seen from the following oscilloscope captures.
73
Appendix B
Figure 6. Speed reference variation (scalar control).
Figure 7. Load torque variation (scalar control).
Figure 8. Speed reference variation (vector control).
74
Appendix B
Figure 9. Load torque variation (vector control).
Figure 10. Transition from motor to generator (vector control).
Figure 11. Emergency breaking (vector control).
75
Appendix B
Figure 12. Holding the machine at zero speed (vector control).
As it could be seen from all the oscilloscope captures, the natural balance of the DC link is
maintained during the test procedure.
It has to be noted here though, that it is recommended to implement a balance control algorithm,
to ensure safe operation, in all situations.
76
Appendix C
Appendix C. Numeric Parameters
The parameters used to construct the Simulink model and to implement the control are presented
in the following table.
Name
Symbol
Value
Unit
Rated Speed
500
[rpm]
Stator Resistance
0.71
[Ω]
Synchronous
Inductance
17.0466e-3
[H]
Synchronous
Inductance
15.6869e-3
[H]
PM Flux Linkage
0.4932
[Wb]
No. of pole pairs
6
[-]
Viscuous Damping
1e-3
[-]
Coulomb Friction
7.7
[Nm]
Rotor Moment of
Inertia
95.107e-3
[kg*m2]
Assambly Moment of
Inertia
102.738e-3
[kg*m2]
600
[V]
330e-6
[F]
Carrier Frequency
4000
[Hz]
Dead time
1.5e-6
[s]
DC link voltage
DC link capacitance
77
Bibliography
Bibliography
[1] (2014, January 30). Understanding the 2030 Climate and Energy Framework (Analysis of
Impact Assessment). Available: http://www.erec.org/;.
[2] (2014, February 05). Global Wind Statistics 2013. Available: http://www.gwec.net/wpcontent/uploads/2014/02/GWEC-PRstats-2013_EN.pdf.
[3] (2011, July 01). Pure Power; Wind energy targets for 2020 and 2030;. Available:
http://www.ewea.org/fileadmin/ewea_documents/documents/publications/reports/Pure_Power_II
I.pdf.
[4] (2013, February 04). Programme: Framework Programe Seventh - DeepWind ( Future Deep
Sea Wind Turbine Technologies). Available: http://cordis.europa.eu/projects/rcn/96069_en.html;
http://www.risoecampus.dtu.dk/Research/sustainable_energy/wind_energy/projects/VEA_Deep
Wind.aspx.
[5] (2011, October 15). DeepWind - Future DeepSea Wind Turbine Technologies. Available:
http://cordis.europa.eu/projects/rcn/96069_en.html.
[6] F. V. T. Nica, P. D. Burlacu and S. Shivachev, "Control of a 5MW multilevel converter for
wind turbine application," Aalborg University, May. 2013.
[7] B. Daniela and B. Ciprian, "Development of modulation strategies for NPC inverter
addressing DC link balancing and CMV reduction," 2012.
[8] B. Wu, High-Power Converters and AC Drives. Wiley. com, 2006.
[9] da Silva, Edison Roberto C, E. Cipriano dos Santos and C. B. Jacobina, "Pulsewidth
modulation strategies," Industrial Electronics Magazine, IEEE, vol. 5, pp. 37-45, 2011.
[10] P. Pillay and R. Krishnan, "Modeling, simulation, and analysis of permanent-magnet motor
drives. I. The permanent-magnet synchronous motor drive," Industry Applications, IEEE
Transactions On, vol. 25, pp. 265-273, 1989.
[11] M. P. Kazmierkowski, H. Tunia and J. Tomaszczyk, Automatic Control of Converter-Fed
Drives. Elsevier, 1994.
[12] P. C. Krause, O. Wasynczuk, S. D. Sudhoff and S. Pekarek, Analysis of Electric Machinery
and Drive Systems. Wiley. com, 2013.
1 M. Štulrajter, V. Hra ovcova and M. Franko, "Permanent ma nets synchronous motor
control theory," Journal of Electrical Engineering, vol. 58, pp. 79-84, 2007.
79
Bibliography
[14] P. C. Perera, F. Blaabjerg, J. K. Pedersen and P. Thogersen, "A sensorless, stable V/f
control method for permanent-magnet synchronous motor drives," Industry Applications, IEEE
Transactions On, vol. 39, pp. 783-791, 2003.
[15] C. Perera, F. Blaabjerg, J. K. Pedersen and P. Thoegersen, "Open loop stability and
stabilization of permanent magnet synchronous motor drives using DC-link current," 2000.
[16] R. S. Colby and D. W. Novotny, "An efficiency-optimizing permanent-magnet synchronous
motor drive," Industry Applications, IEEE Transactions On, vol. 24, pp. 462-469, 1988.
[17] Y. Nakamura, T. Kudo, F. Ishibashi and S. Hibino, "High-efficiency drive due to power
factor control of a permanent magnet synchronous motor," Power Electronics, IEEE
Transactions On, vol. 10, pp. 247-253, 1995.
[18] T. M. Jahns, "Variable frequency permanent magnet AC machine drives," Power
Electronics and Variable Frequency Drives: Technology and Applications, pp. 277-331, 1997.
[19] M. Fatu, R. Teodorescu, I. Boldea, G. Andreescu and F. Blaabjerg, "IF starting method with
smooth transition to EMF based motion-sensorless vector control of PM synchronous
motor/generator," in Power Electronics Specialists Conference, 2008. PESC 2008. IEEE, 2008,
pp. 1481-1487.
[20] A. Kronberg, Design and Simulation of Field Oriented Control and Direct Torque Control
for a Permanent Magnet Synchronous Motor with Positive Saliency, 2012.
[21] I. Boldea, M. C. Paicu and G. Andreescu, "Active flux concept for motion-sensorless
unified AC drives," Power Electronics, IEEE Transactions On, vol. 23, pp. 2612-2618, 2008.
[22] C. L. Phillips and D. Royce, "Harbor, Feedback control systems," М.: Лаборатория
Базовых, 1988.
[23] C. Bohn and D. Atherton, "An analysis package comparing PID anti-windup
strategies," Control Systems, IEEE, vol. 15, pp. 34-40, 1995.
[24] R. Ottersten, On Control of Back-to-Back Converters and Sensorless Induction Machine
Drives. Chalmers University of Technology, 2003.
[25] T. A. Lipo, Vector Control and Dynamics of AC Drives. Oxford University Press, 1996.
[26] J. Chen, T. Liu and C. Chen, "Design and implementation of a novel high-performance
sensorless control system for interior permanent magnet synchronous motors," Electric Power
Applications, IET, vol. 4, pp. 226-240, 2010.
[27] (2008, January 17). SK50MLI065 [Online]. Available:
http://www.usbid.com/assets/datasheets/89/SK50MLI065.PDF.
80
Bibliography
[28] (2011, March 25). Fully Integrated, Hall Effect-Based Linear Current Sensor IC with 3
kVRMS Voltage Isolation and a Low-Resistance Current Conductor. Available:
http://www.allegromicro.com/~/Media/Files/Datasheets/ACS756-Datasheet.ashx.
[29] J. N. Khan, "Design Considerations in Using the Inverter Gate Driver Optocouplers for
Variable Speed Motor Drives," .
[30] M. P. Kazmierkowski, H. Tunia and J. Tomaszczyk, Automatic Control of Converter-Fed
Drives. Elsevier, 1994.
[31] C. Kingsley and S. D. Umans, Electric Machinery. McGraw-Hill Companies, 2003.
81