System pro E control Gemini. Low voltage insulating

System pro E control Gemini. Low voltage insulating
ABB SACE
A division of ABB S.p.A.
Enclosures and Cable Systems
Viale Vicenza, 61
36063 Marostica (VI) - Italy
Tel.: (+39) 0424 478200
Fax: (+39) 0424 478305
www.abb.it/lowvoltage
www.abb.com
The data and illustrations are not binding. Depending on the
technical development of products, we reserve the right to
change the contents of this document without notice.
Copyright 2015 ABB. All right reserved.
1SLC805001D0205 - 01/2015 - 3.000 CAL
Contacts
Catalogue | 2015
System pro E control
Gemini. Low voltage insulating
switchboards
Table of contents
1
Introduction
2
Order codes
3
Technical information
4
Overall dimensions
5
Code list
6
7
8
9
10
11
12
13
14
15
17
18
Gemini | 1SLC805001D0205
/I
Introduction
Characteristics of Gemini switchboards
1/2
System pro M compact®1/6
SACE Tmax low voltage moulded-case circuit breakers
Devices for industrial automation 1/8
1/10
Gemini | 1SLC805001D0205
1/1
1
Introduction
Characteristics of Gemini switchboards
1
Gemini, something completely different in switchboards
Gemini range is revolutionizing the market of low voltage
electric insulating switchboards. The reason for this is that
it is the first switchboard made in thermoplastic material, to
which the co-injection molding technique gives the same
mechanical characteristics as polyester. This means that it is
extremely sturdy, with its rigid covering and expanded internal
core. Moreover, it contains no fiberglass, a material that with
time rises to the surface, jeopardizing the functioning and
safety of switchboards made in polyester with which it is
usually mixed. Gemini switchboards have an IP66 protection
degree (IP30 with the door open and with the appropriate
components installed) and a very high resistance to chemical
and atmospheric agents. This is the reason why Gemini
guarantees excellent performances even in particularly severe
operating conditions.
Strong outside and versatile inside, Gemini fits to any
application
There are as many configurations as ABB devices for low voltage
automation and distribution: moulded-case circuit breakers,
modular circuit breakers, monitoring, control and signaling
devices, wiring ducts and electrical connection systems. All of
these components give to “Gemini system” an enormous range
of specific solutions that are easy to assemble with the snapon system. Nothing can be compared to Gemini, even when
they reach the end of their life cycle because they are totally
ecologically compatible. The material used to manufacture
Gemini is 100% recyclable. Polyester, on the other hand, cannot
be recovered. Moreover, to make sure that correct disposal
procedures are followed, instructions are provided about how
to identify materials and what to do with the product once it has
served its useful purpose.
Gemini switchboards are made through co-injection,
technology and ABB is the first manufacturer to use it as
a molding technique. This process obtains a “sandwich”
of two materials with a compact external covering and
an expanded core, guaranteeing the highest level of
mechanical protection against impacts (IK10) without
the need to add hardening substances. Competitors
products are usually made in polyester that is usually
mixed with fiberglass; passing the time, it rises to the
surface and become a risk factor for skin burns that
may occur during installation and maintenance through
1/2
1SLC805001D0205 | Gemini
accidental contact. Moreover, it causes deterioration of
the technical strength and lasting characteristics of the
material to which it is added. Gemini, on the other hand,
keeps its mechanical characteristics in the long term.
The co-injection technique makes the manufacturing
operations themselves safe because the products are
completely finished when they come out of the mold
without any flash or other surface irregularities.
Quality and safety
Gemini is designed and built in compliance with reference
Standards that define its constructional and functional
characteristics. In particular, the IP66 degree certifies that
Gemini is totally protected against the infiltration of solid
bodies and is resistant to the penetration of jets of water
similar to sea waves. Absolute protection is provided by
double insulation even in the event of indirect contact. Even in
very difficult application circumstances, Gemini gives highlevel performances, with resistance to fire and abnormal heat
up to a temperature of 750 °C and a functioning temperature
from -25 °C to 100 °C. Moreover, the material with which it is
manufactured retains its characteristics for a long time since
it is not subject to corrosion by chemical or atmospheric
agents. Also it does not turn yellow when exposed to UV rays.
Photovoltaic
In a typical photovoltaic plant the direct current section
comprises a generator consisting of strings composed
of photovoltaic modules connected in series. The Gemini
series of IP65 sealed switchboards are ideal for use as
field combiners or as parallel switchboards, i.e. for outdoor
installation near the modules. ABB has a range which is
currently unique on the market, and has developed a family
of plug & operate solutions, i.e. a series of finished, wired and
certified switchboards to meet the needs of a huge range of
plant types: from single string for residential applications to
large-scale solar fields.
Gemini is made in thermoplastic material that is 100%
recyclable. The environmental compatibility of Gemini is
an important objective right from the design phase where
the Life Cycle Assessment (LCA) procedure, defined in
1990 during the Society of Environmental Toxicology and
Chemistry Conference (Vermont, USA), is followed.
Life Cycle Assessment is an objective method for
analyzing the energy and environmental loads relating to
a product, process or activity, carried out by identifying
and quantifying energy, the materials used and
emissions released into the environment. Divided into
four phases, the assessment covers the entire life cycle
of the product, process or activity, from the extraction
and transformation of raw materials, to manufacturing
and distribution, and from usage to recycling and
decommissioning.
Gemini | 1SLC805001D0205
1/3
1
Introduction
Characteristics of Gemini switchboards
1
A switchboard that is not just one system, but three
Gemini is the result of design work conducted by ABB
with the direct collaboration of switchboard manufacturers,
installers and designers who considered versatility to be
the discriminating element when purchasing a switchboard,
equally important as sturdiness and reliability. Gemini fulfils
this requirement by providing a product that can be used for
three different purposes: in addition to the basic configuration,
it also provides the components necessary to be equipped
as an automation switchboard or as a distribution and mixed
switchboard. In any application, compatibility with ABB
protection, control and monitoring portfolio of products means
that a real system of integrated and complementary functions
can be configured.
Typical examples of some Gemini applications can be seen in
industrial production departments and on board machines, in
galvanization plants and varnishing cabins, in petrol stations
and carwashing plants, boiler-rooms, car parks, shopping
malls and in any other environments where distribution and
automation demand specific safety requirements and service
continuity.
Gemini is also flexible with six different box sizes and internal
space to accommodate from 24 to 216 DIN modules.
To respect safety standards, all the switchboard components
can be fixed to the base plate or to the box frame without
using any tool; wiring is carried out from the front followed by
snapping the base plate or the frame onto the box.
The patented frame is fitted with the cable duct incorporated
in the uprights.
In its design, Gemini repeats the shapes and RAL 7035 grey
color of ABB switchboards with which it can be configured as
a main protection switchboard.
Experience and innovation
Gemini has two central aspects. It is both the result of years
of work in the production of installation material and the
expression of the most advanced technology, from design
to distribution. In ABB laboratories, computer aided design
programs simulate all types of application conditions,
translating virtual checks into a process to improve the
Gemini performances so that it will be able to respond more
accurately to market requirements.
Through Internet at URL www.abb.com/edesign-software you
could download free of charge ABB “e-design” software; it
includes softwares for the configuration and budgeting of
Gemini in distribution and automation mixed applications.
Distribution switchboards
System pro E power
1/4
1SLC805001D0205 | Gemini
1
Gemini | 1SLC805001D0205
1/5
System pro M compact®
A complete, integrated range for electrical system safety
1
Thanks to its long-term experience and know-how ABB is able to offer the
best solutions and the most suitable products for electrical systems, whether
in residential, commercial or industrial applications. System pro M compact®
is a complete, structured and fully integrated range of modular products that
guarantees quality, reliability and easy installation. System pro M compact® is the
most complete line of modular devices currently available on the market.
System pro M compact® is a complete range of modular
products for installation on DIN rails. Its multi-purpose nature
offers every possible solution for creating safe, reliable
installations to protect not only people but also the system
and everything connected to it.
The products of System pro M compact® range are developed
by ABB in its production centres, each one specialised in
specific product lines; this ensures a specialist approach for
every application and function required. Constant research
and the development of ground-breaking products and
production solutions, means continuous improvement of the
characteristics and performance of all the equipment, guided
also by specific market requests. ABB’s modular range not
only develops elements for protection, control and command;
it also includes a wide selection of modular KNX devices to
create systems that are extremely user-friendly in terms of
both installation and use, and specifically referring to energy
efficiency in buildings.
1/6
1SLC805001D0205 | Gemini
ABB System pro M compact® - a choice of value
Choosing System pro M compact® means choosing numerous
advantages, including over 120 years of experience, products
developed for the global market (without forgetting the
specific needs and habits of each single country), the widest
range of international certifications, marks and approvals,
optimum product availability thanks to unique worldwide
codes, and the widespread international presence of ABB
sales branches.
System pro M compact ® offers a wide, specialised range of
devices for domestic, commercial and industrial applications,
guaranteeing optimum safety, service continuity, maximum
flexibility and limited maintenance costs.
Circuit breakers and differential protection devices
From the most simple applications to the most complex and
unusual ones, System pro M compact® switches protect
systems from short-circuiting and overloads, guaranteeing the
utmost reliability and safety during various operations.
To protect installations in residential, commercial and
industrial applications, in alternating or direct current, for
photovoltaic systems or for use on machines or production
systems, ABB circuit breakers always provide the ideal
solution with the widest range and best reliability.
With its residual current circuit breakers and residual current
circuit breakers with overcurrent protection, residual current
devices, residual current relays with separate toroid (both
modular and front panel versions), ABB offers various
differential protection solutions for any low voltage installation
levels, from low voltage infeed to power distribution and
terminal distribution.
Protection against overvoltages
The ABB range of devices for protection against lightning
and atmospheric overvoltage includes OVR surge protective
devices and equipment for protecting low voltage distribution
lines, photovoltaic systems and any telecommunication
systems. Designed and built to guarantee optimum operating
reliability, service continuity and reduced maintenance costs,
OVR range is the best of its kind.
Control functions are offered by devices for load
disconnection on the basis of predefined priorities, preventing
the intervention of a meter when the contract limits agreed
with the energy supplying Company are exceeded. They also
guarantee the signalling and management of faults such as an
absent or incorrect phase sequence and increased or reduced
voltage/current values, thereby ensuring optimum protection
for the conected loads. Measurement devices of the System
pro M compact® range verify the electrical system parameters,
providing essential functions for diagnostics, fault prevention,
consumption optimisation and preventive maintenance. They
cover a whole series of activities stretching from singlefunction solutions for direct insertion to multi-function devices
for the complete remote monitoring and management of the
systems connected.
The range includes analogue and digital measurement tools,
multimeters, high level mains analysers, modular electronic
energy meters (MID certified) and a wide selection of
accessories for complete installation monitoring, guaranteeing
a detailed control of absorption and of any electric parameters.
Command, control and measurement devices
When it comes to low voltage systems, System pro M
compact® range offers a wide variety of functions to ensure
service continuity, efficiency and consumption optimisation
at all times and in every situation. These parameters are
fundamental for the design and creation of an electric system,
whether it is of the residential, commercial or industrial type.
Considering command functions, the extensive System pro
M compact® range is made up of disconnecting switches,
modular indicator lights (or for panel installations), contactors,
monostable relays, latching relays, electronic relays, timer
relays, electro-mechanical or digital timer switches, lightsensitive switches, GSM telephone actuators and modular
thermostats.
Gemini | 1SLC805001D0205
1/7
1
SACE Tmax low voltage moulded-case circuit breakers
The best technology for a choice of total safety
1
The moulded-case circuit breakers range SACE Tmax T and Tmax XT offer
an extremely high performance level alongside ever smaller dimensions, easy
installation and a constantly increasing guarantee of safety. Particularly suitable
for secondary distribution in alternating and direct current, they provide specific
solutions for every type of application requirement. They are used mainly in low
voltage civil and industrial systems with an operating current up to 3200A
(for the Tmax T range) or 250A (for the Tmax XT range). Their primary field of
use is in distribution boards in alternating and direct current to protect motors,
generators, capacitors and final utilities.
The ABB range of moulded-case circuit breakers for low
voltage applications is wide and comprehensive and can be
broken down into two lines: Tmax T and Tmax XT.
The main construction features of the range are: dual
insulation between the active power parts (excluding the
terminals) and the front parts of the device, where the
operator stands during normal system operation; an accurate
indication of the position of the mobile contacts to guarantee
reliable signalling; circuit disconnection in compliance with
IEC 60947-2 Standards; an operating temperature between
-25°C and +70°C; a storage temperature between -40°C
1/8
1SLC805001D0205 | Gemini
and +70°C; nominal characteristics that undergo no form
of derating up to a height of 2000 metres; an operating
guarantee even in presence of disturbances caused by
electronic devices; tropicalisation tests in environmental
conditions of moist heat; resistance to impact and vibrations;
installation versatility (horizontal, vertical or flat assembly
on back-mounting plates or DIN profiles). A wide range
of accessories and compliance with the IEC 60947-2
international standards, EC directives and shipping registers.
SACE Tmax T
The SACE Tmax T range consists of 9 circuit breaker sizes, all
available in 3-pole and 4-pole versions, in fixed execution from
T1 to T9, plug-in from T2 to T5 and extractable from T4 to T7.
The following ranges are designed to meet all the various
application requirements: circuit breakers for power
distribution in alternating and direct current, circuit breakers
for advanced zone selectivity, circuit breakers for motor
protection, circuit breakers for applications up to 1150V in
alternating current and 1000V in direct current, PV switchdisconnectors for photovoltaic systems.
SACE Tmax XT
The SACE Tmax XT range fully meets all system needs, from
the most basic to the most advanced, thanks also to its
completeness (offering four sizes from 160A to 250A).
These items are distinguished by their excellent capacity to
limit peak currents and specific let-through energy, thereby
ensuring optimum sizing of the circuits and the devices
downstream. The SACE Tmax XT circuit breakers are fitted
with thermomagnetic and electronic releases to guarantee
protection against both overloads and short-circuiting, and
against earth faults and indirect contact in the low voltage
distribution network.
The SACE Tmax XT moulded-case circuit breakers can be
equipped with thermomagnetic releases to offer protection
for networks in direct and alternating current (by exploiting
the physical properties of a bimetal and an electromagnet,
they can detect overloads and short- circuits), or electronic
releases to protect alternating current networks. These
releases use microprocessor technology to obtain highly
reliable protection functions with accurate intervention.
The power supply for correct operation is provided directly
by the ammeter sensors of the release, guaranteeing its
intervention even with a single-phase load or at the minimum
setting.
Gemini | 1SLC805001D0205
1/9
1
Devices for industrial automation
1
In industrial automation, ABB offers a wide range of devices that are easy to
install. Thanks to specific accessories they can be used in both distribution
applications and in automation command and control applications.
Command and signalling devices
ABB has a range of modular and compact devices for optic
command and signalling. They are easily combined, thanks to
the single model front. The modular range offers a wide selection
of components with excellent combination flexibility. The special
clip-on structure means quick, easy assembly, producing a whole
variety of functions with just a few standard elements.
The compact range is based on an “all-in-one” formula and
a robust design, to make installation even easier. The entire
compact range and part of the modular range, guarantee a
protection degree of IP67 and IP69K, allowing them to be used
in even critical conditions. During operation, the contact blocks of
both types trigger a contact self-cleaning operation to ensure the
device works perfectly even with limited or sporadic use.
Modular terminals
The complete range of ABB connections encompasses different
types, from the most traditional screw or spring terminals to the
most recent solutions - ADO insulation displacement terminals
for quick connection execution, safety and reliability. The SNK
range of modular screw terminals (the result of more than 50 years
of Entrelec experience), offering numerous advantages such as
improved mark visibility, optimised cable entry, easier manual use,
optimisation of the space in the control panels, and a notable
reduction in the number of codes for simpler warehouse stock
management. The ABB modular terminals meet IEC, UL, CSA and
DIN VDE Standards at international level.
Circuit breakers for motor protection
Our circuit breakers for motor protection are magnetic
or miniature type with a high breaking capacity. They fully meet
motor protection Standards and can also be used as main or
emergency switches. Thanks to the technology used and the
accessories available, these devices offer short-circuit protection,
thermal protection, minimum voltage protection, phase loss
protection, on-off commands, signalling, remote release and
testing. Used as single starters and in combination with ABB
contactors, the characteristics of the motor protection circuit
breakers allow them to be used to protect three-phase motors up
to 50 kW at 400V and also to protect other utilities up to 100A.
Switch-disconnectors
To create control panels in the industrial and commercial sectors,
ABB has a complete range of switch-disconnectors with or
without fuse-holders. All the device ranges guarantee excellent
technical performance to ensure optimum operating safety.
A wide choice of accessories are available, such as mechanical
interlocks, motorised commands, switchover kits, adjustable
shafts and metal or plastic handles. Protection degree is IP65. The
indication on the handle shows the status of the contacts even if
they are welded together.
1/10
1SLC805001D0205 | Gemini
1
Contactors
To overcome the limits regarding the field of control voltages that
can be applied to the coil and the operating temperature range,
ABB has created the A and AF contactors range which, thanks to
the latest design criteria, offers numerous application advantages
such as top electrical and mechanical performances and certified
test procedures carried out in the strictest conditions envisaged
by current regulations. These devices can be used in any industrial
applications, for maximum power levels from 4 to 560kW in AC3400V.
Power supply unit command and control electronics
For three-phase networks, ABB has produced a complete set of
control relays (the CM range) for controlling phase voltage, phase
sequence, phase imbalance and phase absence. The set includes
multi-function relays and various other types to control individual
parameters. The CT range of timers respects various operating
needs: accuracy, operating safety, disturbance immunity,
resistance to impact and vibration. Circuits are based on CMOS
technology to guarantee optimum precision.
CR plug-in relays are used in a variety of industrial applications,
acting as an interface between the electronic control devices in
the system and the utilities connected to it.
The versions that make up the range are supplied with 11 different
coil voltages in lead-free cadmium. ABB has a selection of
compact power supply units with a nominal current from 0.3A and
5A to 20A. The innovation of these new units is the availability of
various additional modules to create one-off solutions.
Soft starters
For applications requiring the movement control of pumps, fans,
compressors, conveyor belts, etc. ABB has a complete range of
soft starters that can work with currents from 3A to 1810A.
These devices provide a gradual, controlled motor start-up to
avoid operating problems and high maintenance costs, and
ensure a longer system lifespan.
Miniaturised contactors
Used mainly in building automation and for small command/drive
applications in industry, the ABB miniaturised contactors can be
assembled on DIN profiles and offer different cable connection
options: screwed, welded, or by means of Faston clamps.
They are available in a number of ranges, with command in
alternating or direct current, a compact contactor/reversing switch
version, and a low absorption version.
Programmable controllers
Trigonometric functions, a detailed text, TUV-certified safety
function libraries and two separate CPUs for safety and standard
applications. A single programming concept based on CoDesys,
and standard/safety I/O remote control via Profinet.
These are just a few of the main features that distinguish the
ABB series of programmable controllers. Thanks to over 30
years’ experience, ABB is able to provide practical solutions for
applications ranging from small function control systems to more
complex systems like those of distribution and web press.
ABB’s PLCs are amongst the fastest and most reliable on the
market.
Gemini | 1SLC805001D0205
1/11
1
1/12
1SLC805001D0205 | Gemini
Order codes
Basic configuration
2/2
Components for automation applications
2/5
Components for distribution and mixed applications
2/10
Accessories2/19
Fast selection table
2/24
Gemini | 1SLC805001D0205
2/1
2
Order codes
Basic configuration
2
In the basic configuration, Gemini switchboards are
composed of boxes in six different sizes ranging from
335x400x210 mm to 840x1005x360 mm (WxHxD, external
measurements) and with opaque or transparent doors. In both
versions, the doors are reversible and clip onto the hinges
without the need to use tools; the fact that they open at an
angle of more than 180° means that it is easy to work on the
components installed inside the switchboard.
The seal applied by extrusion along the sides of the doors
guarantees IP66 degree of protection. Access to the inside
of the switchboard is protected by a standard double bit lock
that can be replaced by locks of another type available in
Specifications
Protection
the accessories. Boxes and doors can be requested either
separately or as combined “box + door” codes, to make
filling out the order form more flexible. Inside the packages,
the door is always wrapped separately and inserted inside a
pocket that protects it from accidental damage until wiring
is completed and the switchboard is installed. Hole-cover
plugs to guarantee IP protection and double insulation for wall
mounting are also supplied with the pack together with the
instruction sheet.
IP66 (IEC EN 60529)
Class II insulation
Strenght
Thermoplastic material moulded in co-injection
Resistance to abnormal heat and fire up to a temperature of 750 °C (IEC EN 60695-2-11)
IK10 (IEC EN 50102) degree of resistance to impacts
Protection against chemical and atmospheric agents (water, saline solutions, acids, basic agents, mineral oils, UV rays)
Performances
Operating temperature -25 °C ÷ +100 °C
Rated operational voltage up to 690 V (1)
Flexibility of use
6 sizes from 335x400x210 mm to 840x1005x360 mm (WxHxD, external dimensions)
Installation
DIN 24 to 216 modules
Snap-on mounting of all components in compliance with safety Standards
Quality and envirnoment
Compliance with CEI EN 62208 international reference Standard,
qualification for the requirements of CEI EN 60439 Standard, IMQ mark according to EN 62208 Standard.
100% recyclable
(1)
Rated operational voltage according to IEC 61439-1 1000 V AC and 1500 V DC
Gemini doors open at an angle of more than
180° giving easy access to the devices installed
inside the switchboard.
2/2
1SLC805001D0205 | Gemini
No tools are needed for installation. The doors
hook onto the hinges with special hinge pins
and are reversible.
The special structure of the inner perimeter of
the box ensures further protection against the
penetration of water. The box is supplied with a
spirit level.
Boxes and doors
- Available in 6 sizes
- Single order code combined with box and transparent and opaque door
- Pack with door dismounted and wrapped separately
- Door designed so that it can be hooked onto hinges at both vertical sides and mounted
without the use of tools
- To be mounted to the wall using internal holes or fixing brackets supplied as accessories
- Door opening at an angle of more than 180°
- RAL 7035 grey color
- Doors supplied with 2 standard double bit locks (3 for sizes 5 and 6) that can be replaced
with locks for ciphered key or with square/triangular impression (the standard triplex key is
suitable for use with three types of impressions).
2
Transparent door
1SLC805001F0901
Size
Transparent door switchboard
Unit/Pack
Internal
WxHxD (mm)
250x300x180
Modules
Max No.
DIN mod.
24 (12x2)
Code
1
External
Dimensions
WxHxD (mm)
335x400x210
No. vertical mod.
(H=150 mm)
2
1SL0211A00
1/1
2
460x550x260
375x450x230
54 (18x3)
3
1SL0212A00
1/1
3
460x700x260
375x600x230
72 (18x4)
4
1SL0213A00
1/1
4
590x700x260
500x600x230
96 (24x4)
4
1SL0214A00
1/1
5
590x855x360
500x750x330
120 (24x5)
5
1SL0215A00
1/1
6
840x1005x360
750x900x330
216 (36x6)
6
1SL0216A00
1/1
Unit/Pack
Internal
WxHxD (mm)
250x300x180
Modules
Max No.
DIN mod.
24 (12x2)
Code
1
External
Dimensions
WxHxD (mm)
335x400x210
No. vertical mod.
(H=150 mm)
2
1SL0201A00
1/1
2
460x550x260
375x450x230
54 (18x3)
3
1SL0202A00
1/1
3
460x700x260
375x600x230
72 (18x4)
4
1SL0203A00
1/1
4
590x700x260
500x600x230
96 (24x4)
4
1SL0204A00
1/1
5
590x855x360
500x750x330
120 (24x5)
5
1SL0205A00
1/1
6
840x1005x360
750x900x330
216 (36x6)
6
1SL0206A00
1/1
Opaque door
1SLC805002F0901
Size
Opaque door switchboard
Gemini | 1SLC805001D0205
2/3
Order codes
Basic configuration
Single boxes
Size
Code
Unit/Pack
1
External
dimensions
WxHxD (mm)
335x400x210
Internal
WxHxD (mm)
250x300x180
1SL0221A00
1/1
2
460x550x260
375x450x230
1SL0222A00
1/1
3
460x700x260
375x600x230
1SL0223A00
1/1
4
590x700x260
500x600x230
1SL0224A00
1/1
5
590x855x360
500x750x330
1SL0225A00
1/1
6
840x1005x360
750x900x330
1SL0226A00
1/1
1SLC805003F0901
2
Single box
Single doors
1SLC805004F0901
Transparent door
1SLC805005F0901
Transparent door
Opaque door
2/4
1SLC805001D0205 | Gemini
Size
1
Box dimensions WxHxD (mm)
335x400x210
Code
1SL0241A00
Unit/Pack
1/1
2
460x550x260
1SL0242A00
1/1
3
460x700x260
1SL0243A00
1/1
4
590x700x260
1SL0244A00
1/1
5
590x855x360
1SL0245A00
1/1
6
840x1005x360
1SL0246A00
1/1
Size
1
Box dimensions WxHxD (mm)
335x400x210
Code
1SL0231A00
Unit/Pack
1/1
2
460x550x260
1SL0232A00
1/1
3
460x700x260
1SL0233A00
1/1
4
590x700x260
1SL0234A00
1/1
5
590x855x360
1SL0235A00
1/1
6
840x1005x360
1SL0236A00
1/1
Opaque door
Order codes
Components for automation applications
Gemini switchboards are designed to be perfectly compatible
with ABB components for low voltage control and monitoring.
For these applications they can be equipped with modular
devices belonging to the System pro M range, with Tmax
moulded-case circuit-breakers and control and signaling
devices, creating a truly integrated automation system.
When deciding the Gemini layout for control and monitoring
applications, not only is it possible to select the box and door
in the required size, but you can also select the base plate in
one of the three versions in the range.
After wiring with the ducts and the Fix-O-Rapid device, the
special standard adjustable feet and hooks must be fitted
onto the base plate, allowing it to be inserted inside the
box at up to seven different depths and three further levels
of adjustment: no tools need to be used to carry out these
operations. To finish the job, the inner door can be mounted
(reversible and in insulating material), guaranteeing IP30
degree of protection when the switchboard door is open.
No tools are needed unless the inner door is equipped with
buttons, warning lights, etc.
The fixing hooks and feet supplied in the standard versions are applied without having to use tools,
making it possible to install the base plate at seven different depths inside the switchboard.
They can also be adjusted at three further positions.
Application of the inner door guarantees IP40
degree of protection when the switchboard door
is open.
Example of the configuration of a switchboard for an automation application: some ABB control and protection devices are installed on the plate.
The inner door is fitted with light-signaling devices.
Gemini | 1SLC805001D0205
2/5
2
Order codes
Components for automation applications
Base plates
-Available in three versions in blank or drilled metal and insulating material
-Positioning at 3 different depths for size 1, 4 different depths for sizes 2-3-4 and 7 different
depths for sizes 5-6 (adjustments with 30 mm pitch)
-Supplied with feet and hooks adjustable at three further positions (with 7.5 mm pitch)
-Snap-on mounting
-Plates can also be mounted directly on the base with the special kit.
2
Blank metal
1SLC805006F0901
Size of the switchboard
1
Blank metal base plate
2
1SL0260A00
1/6
1SL0261A00
1/4
1/4
4
1SL0262A00
5
1SL0263A00
1/4
6
1SL0264A00
1/2
Code
1SL0275A00
Unit/Pack
1/6
Drilled metal
1SLC805007F0901
2
1SL0276A00
1/6
3
1SL0277A00
1/4
4
1SL0278A00
1/4
5
1SL0279A00
1/4
6
1SL0280A00
1/2
Code
1SL0267A00
Unit/Pack
1/6
Insulating material
1SLC805008F0901
Size of the switchboard
1
I nsulating material b ase plate
2/6
1SLC805001D0205 | Gemini
Unit/Pack
1/6
3
Size of the switchboard
1
Drilled metal base plate
Code
1SL0259A00
2
1SL0268A00
1/6
3
1SL0269A00
1/4
4
1SL0270A00
1/4
5
1SL0271A00
1/4
6
1SL0272A00
1/2
Description
Base mounting kit for metal plate
Code
1SL0383A00
Unit/Pack
1/10
1SLC805009F0901
Inner doors
Made in insulating material
IP30 degree of protection with door open
Designed so that door can be hinged onto both vertical sides
Snap-on mounting and fixing
Size of the switchboard
1
2
Code
1SL0251A00
Unit/Pack
1/4
2
1SL0252A00
1/4
3
1SL0253A00
1/2
1/2
4
1SL0254A00
5
1SL0255A00
1/2
6
1SL0256A00
1/1
1SLC805010F0901
Inner door, sizes 1-2
-
Inner door, sizes 3-4-5-6
Gemini | 1SLC805001D0205
2/7
Order codes
Components for automation applications
Wiring ducts
- Made in self-extinguishing thermoplastic material (UL 94 V0), resistant to abnormal heat and
fire up to 960 °C (IEC 695-2-1)
- RAL 7030 grey color
- Available in version with 8/12 mm and 4/6 mm slots
- Base strip designed to snap onto Fix-O-Rapid
- Available in standard lengths of 2 m
2
With 8/12 mm slots
1SLC805010F0901
Wiring duct
with 8/12 mm slot
2/8
1SLC805001D0205 | Gemini
Dimensions
WxH (mm)
15x17
Code
05 019
Weight
(kg/m)
0,06
Unit/Packmeters
46
25x30
25x40
05 033
0,21
58
05 043
0,25
48
25x60
05 063
0,24
34
25x80
05 083
0,29
28
25x100
05 094
0,46
20
40x30
05 035
0,27
40
40x40
05 045
0,31
30
40x60
05 065
0,34
22
40x80
05 085
0,38
36
40x100
05 095
0,53
28
60x30
05 037
0,38
52
60x40
05 047
0,46
40
60x60
05 067
0,47
32
60x80
05 087
0,50
24
60x100
05 096
0,73
20
80x40
05 049
0,47
32
80x60
05 069
0,52
24
80x80
05 089
0,59
16
80x100
05 097
0,91
14
100x40
05 051
0,55
24
100x60
05 071
0,59
20
100x80
05 091
0,68
16
100x100
05 098
1,06
8
120x40
05 053
0,65
20
120x60
05 073
0,73
14
120x80
05 093
0,89
12
150x100
05 099
1,37
8
With 4/6 mm slots
1SLC805011F0901
Wiring duct
with 4/6 mm slot
Dimensions
WxH (mm)
15x17
Code
05 119
Weight
(kg/m)
0,06
Unit/Packmeters
46
25x30
05 133
0,21
58
25x40
05 143
0,25
48
25x60
05 163
0,24
34
25x80
05 183
0,29
28
25x100
05 194
0,46
20
40x30
05 135
0,27
40
40x40
05 145
0,31
30
40x60
05 165
0,34
22
40x80
05 185
0,38
36
40x100
05 195
0,53
28
60x30
05 137
0,38
52
60x40
05 147
0,46
40
60x60
05 167
0,47
32
60x80
05 187
0,50
24
60x100
05 196
0,73
20
80x40
05 149
0,47
32
80x60
05 169
0,52
24
80x80
05 189
0,59
16
80x100
05 197
0,91
14
100x40
05 151
0,55
24
100x60
05 171
0,59
20
100x80
05 191
0,68
16
100x100
05 198
1,06
8
120x40
05 153
0,65
20
120x60
05 173
0,73
14
120x80
05 193
0,89
12
150x100
05 199
1,37
8
Fix-O-Rapid
Rapid mounting device for attaching wiring ducts to the base plate: it snaps onto the plate
after drilling a ø 7 mm hole. Two Fix-O-Rapid devices are enough for each wiring duct section.
Fix-O-Rapid guarantees maximum insulation since it does not involve the use of any metal
component inside the wiring duct. If the wrong wiring duct is selected, it can be dismounted
and a version with the same base and a different height can be attached to the Fix-O-Rapid.
1SLC805013F0901
Description
Rapid mounting device for wiring duct, W 25 mm
Fix-O-Rapid
Code
05 270
Unit/Packno. pieces
20/600
Rapid mounting device for wiring duct, W 40 mm
05 272
20/600
Rapid mounting device for wiring duct, W 60 mm
05 274
20/600
20/240
Rapid mounting device for wiring duct, W 80 mm
05 276
Rapid mounting device for wiring duct, W 100 mm
05 278
20/240
Rapid mounting device for wiring duct, W 120 mm
05 280
20/240
Rapid mounting device for wiring duct, W 150 mm
05 282
20/240
Gemini | 1SLC805001D0205
2/9
2
Order codes
Components for distribution and mixed applications
2
In distribution and mixed applications, the Gemini switchboard
is designed to be fitted with System pro M modular devices
and Tmax moulded-case circuit breakers. The frame is the
load-bearing element of the configuration: DIN rails, partial
modular plates and the special Tmax mounting and cabling
kits are snapped onto the uprights.
All the components can be adjusted to six different depths
with a pitch of 12.5 mm and arranged at heights with
standard installation pitch of 150, 225 and 300 mm and a
distance of 75 mm between the rows.
Blank or drilled front panels are applied to protect the
equipment and these can be hinged onto both sides;
the cables are housed inside the vertical wiring duct
integrated in the uprights according to an exclusive ABB
patent. Wiring is carried out by pulling out the frame and
working from the front; the ergonomic grip and the standard
feet and snap-on hooks supplied make it easy to insert it
inside the switchboard after the job is finished.
The DIN rail is supplied with special hooks
already in position for attaching to the uprights.
The upright with the incorporated wiring duct
is an exclusive ABB patent that rationalizes the
path of cables inside the switchboard.
The depth at which the DIN rail, the modular
plates, the kit for fixing the Tmax circuit
breakers and the wiring duct are positioned can
be adjusted with a simple sliding movement.
The frame can be extracted to make wiring
operations easier at the workbench.
The blank and drilled panels are hinged onto
both sides; the description of the installed
components can be kept in the special
compartment protected by a transparent, hinged
flange.
Fixing hooks and feet allow the frame to be
snap-mounted inside the box.
2/10
1SLC805001D0205 | Gemini
Uprights
1SLC805014F0901
- Incorporated vertical wiring duct (ABB patent)
- Snap-on mounting of all components (installation pitch of 75 mm)
- Snap-on insertion into box
- Depth of installed components adjusted at a pitch of 12.5 mm
(4 positions for uprights of size 1 and 6 positions for the remaining ones)
- Ergonomic grip to make it easy to insert and extract
2
Size of the switchboard
Code
1
1SL0283A00
Unit/Pack
1/4
2
1SL0284A00
1/4
3
1SL0285A00
1/4
4
1SL0285A00
1/4
5
1SL0286A00
1/2
6
1SL0287A00
1/1
Uprights
DIN rails
1SLC805015F0901
-
DIN rail
Two-sided version
Supplied with mounting supports that snap onto uprights
Depth adjustment on uprights
Designed so that rapid Unifix L mounting bars can be snapped on
Size of the switchboard
Modules per row
Code
Unit/Pack
1
12
1SL0290A00
1/10
2
18
1SL0291A00
1/10
3
18
1SL0291A00
1/10
4
24
1SL0292A00
1/10
5
24
1SL0292A00
1/10
6
36
1SL0293A00
1/10
Gemini | 1SLC805001D0205
2/11
Order codes
Components for distribution and mixed applications
Drilled panels
- Supplied with DIN rail complete with supports to snap onto uprights and adjustable in depth
- Available in 1 module (H 150 mm) and 1+1/2 module (H 225 mm, sizes 2-6) dimensions
- Designed to be hinged onto both vertical sides
- Snap-on mounting onto uprights (in compliance with reference Standards a tool must be
used for removing the panel)
- Document pocket for storing descriptions of installed devices
2
1SLC805016F0901
1 module
Code
1SL0307A00
Unit/Pack
1/8
2
1SL0308A00
1/8
3
1SL0308A00
1/8
4
1SL0309A00
1/4
5
1SL0309A00
1/4
6
1SL0310A00
1/2
Unit/Pack
1 + 1/2 module
1SLC805017F0901
Drilled panel, 1 module
Drilled panel, 1 + 1/2 module
2/12
Size of the switchboard
1
1SLC805001D0205 | Gemini
Size of the switchboard
Code
2
1SL0313A00
1/8
3
1SL0313A00
1/8
4
1SL0314A00
1/4
5
1SL0314A00
1/4
6
1SL0315A00
1/2
Blank panels
-Available in 1/2 module (H 75 mm), 1 module (H 150 mm) and 2 modules (H 300 mm)
dimensions
-H 150 mm and H 300 panels designed to be hinged onto both vertical sides
-Snap-on mounting onto uprights (in compliance with reference Standards a tool must be
used for removing the panel)
2
1SLC805018F0901
1/2 module
Blank panel, 1/2 module
Size of the switchboard
Code
1
1SL0318A00
Unit/Pack
1/10
2
1SL0319A00
1/10
3
1SL0319A00
1/10
4
1SL0320A00
1/6
5
1SL0320A00
1/6
6
1SL0321A00
1/4
Unit/Pack
1SLC805019F0901
1 module
Blank panel, 1 module
Size of the switchboard
Code
1
1SL0324A00
1/8
2
1SL0325A00
1/8
3
1SL0325A00
1/8
4
1SL0326A00
1/4
5
1SL0326A00
1/4
6
1SL0327A00
1/4
Unit/Pack
1SLC805020F0901
2 modules
Blank panel, 2 modules
Size of the switchboard
Code
1
1SL0330A00
1/6
2
1SL0331A00
1/6
3
1SL0331A00
1/6
4
1SL0332A00
1/4
5
1SL0332A00
1/4
6
1SL0333A00
1/4
Gemini | 1SLC805001D0205
2/13
Order codes
Components for distribution and mixed applications
Partial modular plates
- Available in 1 module (H 150 mm) and 2 module (H 300 mm, sizes 2-6) dimensions
- Snap-on mounting onto uprights with depth adjustment.
2
1SLC805021F0901
1 module
Partial modular plate,
1 module
Size of the switchboard
Code
1
1SL0296A00
Unit/Pack
1/6
2
1SL0297A00
1/4
3
1SL0297A00
1/4
4
1SL0298A00
1/4
5
1SL0298A00
1/4
6
1SL0299A00
1/2
Unit/Pack
1SLC805022F0901
2 modules
Partial modular plate,
2 modules
Size of the switchboard
Code
2
1SL0302A00
1/4
3
1SL0302A00
1/4
4
1SL0303A00
1/4
5
1SL0303A00
1/4
6
1SL0304A00
1/2
Kit for installing Tmax moulded-case circuit breakers
- For installing Tmax moulded-case circuit breakers in fixed version with front terminals
- Composed of a plate with special drilled holes and a protection panel with vertical slots that
can be hinged on bothsides and snap-on mounted (in compliance with reference Standards
a tool must be used for removing the panel)
- Available for sizes 2-6
- Snap-on mounting onto uprights with the possibility of adjusting the plate depth
1SLC805023F0901
H 150 mm
H 150 mm
Size of the switchboard
Code
2
1SL0336A00
Unit/Pack
1/4
3
1SL0336A00
1/4
4
1SL0337A00
1/4
5
1SL0337A00
1/4
6
1SL0338A00
1/2
Unit/Pack
1SLC805024F0901
H 300 mm
H 300 mm
2/14
1SLC805001D0205 | Gemini
Size of the switchboard
Code
2
1SL0370A00
1/4
3
1SL0370A00
1/4
4
1SL0371A00
1/4
5
1SL0371A00
1/4
6
1SL0372A00
1/2
Kit selection
Size
1
2
Instal.
Tmax T1
Tmax T2
Tmax T3
3p D
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
D
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
K2
4
K2
5
K2
6
K2
3p
4p
■
■
Tmax T5
4p
K2
3
Tmax T4
3p
3p D
4p D
3p
4p
3p D
4p D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Caption
- D, installation on DIN rail
- K1, installation with Tmax kit H = 150 (holes made)
- K2, installation with Tmax kit H = 300 (holes made)
- O1, installation on modular plate (1 module, H = 150 mm)
- O2, installation on modular plate (2 modules, H = 300 mm)
- T, installation on total base plate
Gemini | 1SLC805001D0205
2/15
2
Order codes
Components for distribution and mixed applications
Kit for installing Tmax XT moulded-case circuit breakers
- For installing Tmax XT moulded-case circuit breakers in fixed version with front terminals
- Composed of a plate with special drilled holes and a protection panel with vertical slots that
can be hinged on both sides and snap-on mounted (in compliance with reference Standards
a tool must be used for removing the panel)
- Available for sizes 2-6
- Snap-on mounting onto uprights with the possibility of adjusting the plate depth
2
1SLC805023F0901
H 150 mm
H 150 mm
Size of the switchboard
Code
2
1SL0373A00
Unit/Pack
1/4
3
1SL0373A00
1/4
4
1SL0374A00
1/4
5
1SL0374A00
1/4
6
1SL0375A00
1/2
Unit/Pack
1SLC805059F0901
H 300 mm
H 300 mm
2/16
1SLC805001D0205 | Gemini
Size of the switchboard
Code
2
1SL0376A00
1/4
3
1SL0376A00
1/4
4
1SL0377A00
1/4
5
1SL0377A00
1/4
6
1SL0378A00
1/2
Kit selection
Size
1
2
Installation
XT1
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
K2
5
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
K2
6
XT4
3p D
K2
4
XT3
4p
K2
3
XT2
3p
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
K2
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Caption
- D, installation on DIN rail
- K1, installation with Tmax kit H = 150 (holes made)
- K2, installation with Tmax kit H = 300 (holes made)
- O1, installation on modular plate (1 module, H = 150 mm)
- O2, installation on modular plate (2 modules, H = 300 mm)
- T, installation on total base plate
Gemini | 1SLC805001D0205
2/17
2
Order codes
Components for distribution and mixed applications
Wiring kits
- Composed of wiring duct in versions 25x60 mm and 40x60 mm (WxH, 8-12 mm slots) and Fix-O-Rapid
- Snap-on mounting on uprights with depth adjustment
2
1SLC805025F0901
Wiring duct 25x60 mm
Wiring kit
2/18
1SLC805001D0205 | Gemini
Size of the switchboard
Code
1
1SL0353A00
Unit/Pack
1/4
2
1SL0354A00
1/4
3
1SL0354A00
1/4
1/4
4
1SL0355A00
5
1SL0355A00
1/4
6
1SL0356A00
1/4
Size of the switchboard
Code
Unit/Pack
1
1SL0360A00
1/4
Wiring duct 40x60 mm
2
1SL0361A00
1/4
3
1SL0361A00
1/4
1/4
4
1SL0362A00
5
1SL0362A00
1/4
6
1SL0363A00
1/4
Order codes
Accessories
Gemini switchboards have the same accessories for both
automation and distribution applications, ensuring maximum
versatility and integration of functions. In particular, the
ventilation and anti-condensation kits make it even safer for
the devices to run, protecting them from the effects of heat
and humidity while the wall brackets, pole mounting kit and
pedestal make it easier to install the switchboards in any
context.
Three different kinds of locks are supplied for the doors with
which it is possible to replace the standard double bit model.
The universal drill bit can be used to open the side branch
connections. Module covers hide the unused modules of the
DIN rail guaranteeing IP40 protection when the door is open
in distribution and mixed configurations.
The standard locks supplied can be replaced by the version with ciphered key and handle or with square or triangular impression.
Gemini wall-mounted installation using the special mounting brackets.
The fact that Gemini switchboards can also be pole-mounted (see photo
above) or mounted on a special pedestal (see photo at the side) makes
them suitable for any application situation.
Gemini | 1SLC805001D0205
2/19
2
Order codes
Accessories
Locks
Available in three versions with ciphered key and handle, with triangular and square
impressions.
1SLC805026F0901
2
Locks
Description
Code
Lock with Yale type ciphered key and handle
1SL0340A00
Unit/Pack
1/10
Lock with triangular impression
1SL0341A00
1/10
Lock with square impression
1SL0339A00
1/10
Tamper-proof locking kit (code 1SLO340A00 included)
1SL0458A00
1/10
Gemini standard lock
1SL0459A00
1/10
Unit/Pack
1SLC805027F0901
Mounting elements
Guarantee optimum wall, pole and floor mounting conditions.
1SLC805030F0901
Plastic wall brackets
Iron wall brackets
Description
Code
Horizontal and vertical plastic wall brackets (4 pieces)*
1SL0342A00
1/10
Iron wall brackets (4 pieces
1SL0401A00
1/10
Pole mounting kit for sizes 1 switchboards**
1SL0343A00
1/4
1/4
Pole mounting kit for sizes 2-3 switchboards**
1SL0344A00
Pole mounting kit for sizes 4-5 switchboards**
1SL0345A00
1/2
Pole mounting kit for size 6 switchboards**
1SL0346A00
1/2
IP43 Floor mounting pedestal for sizes 1-4
1SL0352A00
1/1
Pole mounting kit
1SLC805029F0901
1SLC805028F0901
* There are two types of inserts for adapting brackets to ø 6 e 8 mm fixing devices.
** The kit includes two elements for fixing the upper and the lower part of the switchboard.
Floor
mounting
pedestal
Pedestals
1SLC805031F0901
Allows the application of the Gemini switchboard to the ground without the need to prepare
the construction of concrete footings or foundations when the pedestal is buried.
Pedestal
2/20
1SLC805001D0205 | Gemini
Description
Code
Unit/Pack
Pedestal Gemini size 4
1SL0464A00
1/1
Pedestal Gemini size 5
1SL0465A00
1/1
Pedestal Gemini size 6
1SL0466A00
1/1
IP21/54 ventilation kits
-
Composed of plastic grills and filter to ensure switchboard ventilation.
D egree of protection without filter: IP21.
Degree of protection with filter: IP54.
P reassembled seal.
1SLC805032F0901
Description
Ventilation kit
2
Code
Unit/Pack
Grid + air flow kit
Dimensions
(mm)
105x105
EN0105K
1/1
Grid + air flow kit (not suitable for size. 1)
150x150
EN0150K
1/1
Grid + air flow kit (not suitable for size. 1)
204x204
EN0204K
1/1
Note: screws not included; use 4 self lock screws 2,9x13 or ask for order code 1SL0384A00.
Base covers
1SLC805033F0901
For aesthetic as well as functional purposes, in particular for pedestal installations.
Size of the switchboard
Code
1
1SL0385A00
Unit/Pack
1/4
2
1SL0386A00
1/4
3
1SL0387A00
1/2
1/2
4
1SL0388A00
5
1SL0389A00
1/2
6
1SL0390A00
1/2
Unit/Pack
Base cover
Coupling kits
1SLC805034F0901
It follows the aesthetic outline of the boxes.
Description
Code
Vertical coupling kit for sizes 2-3 switchboards
1SL0413A00
1/2
Vertical coupling kit for sizes 4 switchboards
1SL0414A00
1/2
Vertical coupling kit for sizes 5 switchboards
1SL0415A00
1/2
Vertical coupling kit for sizes 6 switchboards
1SL0416A00
1/2
Coupling kit
Gemini | 1SLC805001D0205
2/21
Order codes
Accessories
Bottom bases H 30
1SLC805035F0901
For fixing the Gemini switchboard directly to the floor.
2
Description
Code
Bottom base for size 2-3 switchboards
1SL0423A00
Unit/Pack
1/2
Bottom base for size 4 switchboards
1SL0424A00
1/2
Bottom base for size 5 switchboards
1SL0425A00
1/2
Bottom base for size 6 switchboards
1SL0426A00
1/2
Unit/Pack
Bottom base
Fixed frames
1SLC805036F0901
- In combination with bottom base H 30
- For fixing onto poured concrete floors and bases.
Description
Code
Fixed frame for size 2-3 switchboards
1SL0433A00
1/2
Fixed frame for size 4 switchboards
1SL0434A00
1/2
Fixed frame for size 5 switchboards
1SL0435A00
1/2
Fixed frame for size 6 switchboards
1SL0436A00
1/2
Unit/Pack
Fixed frame
1SLC805037F0901
Integral covers
Integral cover
Description
Code
Integral cover for size 1 switchboard
1SL0451A00
1/1
INtegral cover for size 2-3 switchboard
1SL0452A00
1/1
Integral cover for size 4 switchboard
1SL0454A00
1/1
Integral cover for size 5switchboard
1SL0455A00
1/1
Integral cover for size 6 switchboard
1SL0456A00
1/1
Unit/Pack
Horizontal Kits
1SLC805038F0901
Kit for a proper opening of switchboard upward.
Horizontal Kit Gemini
2/22
1SLC805001D0205 | Gemini
Description
Code
Horizontal Kit Gemini size 3
1SL0470A00
1/1
Horizontal Kit Gemini size 4
1SL0471A00
1/1
Horizontal Kit Gemini size 5
1SL0472A00
1/1
Horizontal Kit Gemini size 6
1SL0473A00
1/1
Anti-condensation kits
1SLC805039F0901
- Kit in special material to prevent condensation from forming inside the switchboard:
it include
- Impermeable to water (pressure): 0.6 bar / 60 sec.
- Air flow: 400 ml/min. (dp = 70 mbar)
- 1 kit for sizes 1-2, 2 kits for sizes 3-4 and 3 kits for sizes 5-6 are recommended to guarantee
adequate dissipation; in any case the number of kits to be installed depend on the number
and type of devices installed inside the switchboard.
- IP66
Base socket
Description
Code
Unit/Pack
Anti-condensation kit
1SL0351A00
1/6
Unit/Pack
1SLC805041F0901
1SLC805040F0901
Other accessories
Module covers
Code
12894
1/30
Module covers in RAL 7035 grey, 4 modules
12863
25/300
Plastic spacer for installing modular devices and moulded-case circuit breakers at the same depth
12851
10/60
Small bag plate mounting kit
1SL0383A00
1/10
Small bag for ventilation kit
1SL0384A00
10/50
1SLC805042F0901
Universal
drill bit
Description
Universal drill bit
Spacer
Gemini | 1SLC805001D0205
2/23
2
F
Order codes
Fast selection table
F
E
C
C
D A
D A
E
B
B
Basic configuration
2
FFF
FF
DD AA
DDDAAA
F F F F F
CCC
CC
Size
No. of
installable
DIN modules
No. of
vertical mod.
External
dimensions
A A
D DA DA D
D A
EEE
BBB
EE
BB
E EE E E
Complete switchboard
B BB B B
Internal
Box
Door
CC C
C C dimensions
(mod. x row)
(H=150 mm)
A
B
C
D
E
F
Trasparent door
Opaque door
Transparent
Opaque
1
24 (12x2)
2
400
335
210
300
250
180
1SL0211A00
1SL0201A00
1SL0221A00
1SL0241A00
1SL0231A00
2
54 (18x3)
3
550
460
260
450
375
230
1SL0212A00
1SL0202A00
1SL0222A00
1SL0242A00
1SL0232A00
3
72 (18x4)
4
700
460
260
600
375
230
1SL0213A00
1SL0203A00
1SL0223A00
1SL0243A00
1SL0233A00
4
96 (24x4)
4
700
590
260
600
500
230
1SL0214A00
1SL0204A00
1SL0224A00
1SL0244A00
1SL0234A00
5
120 (24x5)
5
855
590
360
750
500
330
1SL0215A00
1SL0205A00
1SL0225A00
1SL0245A00
1SL0235A00
6
216 (36x6)
6
1005
840
360
900
750
330
1SL0216A00
1SL0206A00
1SL0226A00
1SL0246A00
1SL0236A00
Components for automation
Accessories for distribution
SIze
Base plate
Inner door
Blank
Drilled
Insulating
Former version
New version
1
1SL0259A00
1SL0275A00
1SL0267A00
1SL0251A00
-
2
1SL0260A00
1SL0276A00
1SL0268A00
1SL0252A00
-
3
1SL0261A00
1SL0277A00
1SL0269A00
-
1SL0253A00
4
1SL0262A00
1SL0278A00
1SL0270A00
-
1SL0254A00
5
1SL0263A00
1SL0279A00
1SL0271A00
-
1SL0255A00
6
1SL0264A00
1SL0280A00
1SL0272A00
-
1SL0256A00
2/24
1SLC805001D0205 | Gemini
Wiring ducts
Fix-O-Rapid
See pag. 2/8-2/9
See pag. 2/9
C
B
C
F
D A
F
D A
F
E
C
D A
E
B
CE
C
B
B
Components for automation
2
Size
1
Uprights
1SL0283A00
DIN rail
1SL0290A00
Drilled panel
Blank panel
Modular plate
H=150 mm
H=225 mm
H=75 mm
H=150mm
H=300 mm
H=150 mm
H=300 mm
1SL0307A00
-
1SL0318A00
1SL0324A00
1SL0330A00
1SL0296A00
-
2
1SL0284A00
1SL0291A00
1SL0308A00
1SL0313A00
1SL0319A00
1SL0325A00
1SL0331A00
1SL0297A00
1SL0302A00
3
1SL0285A00
1SL0291A00
1SL0308A00
1SL0313A00
1SL0319A00
1SL0325A00
1SL0331A00
1SL0297A00
1SL0302A00
4
1SL0285A00
1SL0292A00
1SL0309A00
1SL0314A00
1SL0320A00
1SL0326A00
1SL0332A00
1SL0298A00
1SL0303A00
5
1SL0286A00
1SL0292A00
1SL0309A00
1SL0314A00
1SL0320A00
1SL0326A00
1SL0332A00
1SL0298A00
1SL0303A00
6
1SL0287A00
1SL0293A00
1SL0310A00
1SL0315A00
1SL0321A00
1SL0327A00
1SL0333A00
1SL0299A00
1SL0304A00
H. 300 mm
25x60 mm
Accessories for distribution
Size
Kit for Tmax
H. 150 mm
Kit for Tmax XT
H. 300 mm
H. 150 mm
x-O-Rapid kit with wiring duct
40x60 mm
1
-
-
-
-
1SL0353A00
1SL0360A00
2
1SL0336A00
1SL0370A00
1SL0373A00
1SL0376A00
1SL0354A00
1SL0361A00
3
1SL0336A00
1SL0370A00
1SL0373A00
1SL0376A00
1SL0354A00
1SL0361A00
4
1SL0337A00
1SL0371A00
1SL0374A00
1SL0377A00
1SL0355A00
1SL0362A00
5
1SL0337A00
1SL0371A00
1SL0374A00
1SL0377A00
1SL0355A00
1SL0362A00
6
1SL0338A00
1SL0372A00
1SL0375A00
1SL0378A00
1SL0356A00
1SL0363A00
Module covers
RAL 7035
12863
Gemini | 1SLC805001D0205
2/25
Order codes
Fast selection table
Accessories common to the whole range
2
Size
Lock with handle
Lock with
triangular
impression
Lock with square
impression
Anti tampering
locking kit
Bounting brackets Pole installation
kit
Pedestal
1
1SL0343A00
-
2
1SL0344A00
-
1SL0344A00
-
1SL0345A00
1SL0464A00
3
4
1SL0340A00
1SL0341A00
1SL0339A00
1SL0458A00
See pag. 2/20
5
1SL0345A00
1SL0465A00
6
1SL0346A00
1SL0466A00
Size
Ventilation kit
Base cover
Anti
condensation
kit
Floor pedestal
Coupling kit
Bottom base
H 30
Fixed frame
Integral cover
Universal drill bit
Base mounting kit
for metal plate
12894
1SL0383A00
Depth adapter
Horizontal kit
1
1SL0385A00
-
-
-
1SL0451A00
-
2
1SL0386A00
1SL0413A00
1SL0423A00
1SL0433A00
1SL0452A00
1SL0470A00
3
1SL0387A00
1SL0413A00
1SL0423A00
1SL0433A00
1SL0452A00
1SL0414A00
1SL0424A00
1SL0434A00
1SL0454A00
4
See pag. 2/21
1SL0388A00
1SL0352A00
1SL0351A00
12851
1SL0471A00
5
1SL0389A00
-
1SL0415A00
1SL0425A00
1SL0435A00
1SL0455A00
1SL0472A00
6
1SL0390A00
-
1SL0416A00
1SL0426A00
1SL0436A00
1SL0456A00
1SL0473A00
2/26
1SLC805001D0205 | Gemini
Technical information
Compliance with standards and technical characteristics
- Reference standards
3/2
- Gemini switchboards features table
3/3
IP degree of protection
3/4
IK degree of resistance to impacts
3/5
Double insulation
3/6
Self-extinguishing tests
3/6
Resistance to chemical agents
3/7
Integration with ABB products
- Installation of Tmax moulded-case circuit breakers
3/8
- Installation of Tmax XT moulded-case circuit breakers
3/9
- Unifix L fast wiring system
3/10
- Screw technology connection
3/12
Configurations examples
3/14
Component mounting distances
3/17
Disposal instructions
3/19
Gemini | 1SLC805001D0205
3/1
3
Technical information
Compliance with standards and technical characteristics
Reference Standards
3
Standard IEC 62208 (“Empty enclosures for low voltage
switch-gear and control gear assemblies. General
requirements”), that has implemented at an international
level the Standard EN 50298, presently EN 62208, is the
prescriptive reference for Gemini switchboards.
The object of Standard CEI EN 50298 is to formulate
definitions, classifications, characteristics and test
prescriptions for cases designed to be used as part of
protection and operating equipment (switchboards) in
compliance with the Standards of the EN 60439 series, that
have a maximum rated voltage of 1000 V in alternating current
for maximum frequencies of 1000 Hz or 1500 V in direct
current and are suitable for general use in both internal and
external applications.
3/2
1SLC805001D0205 | Gemini
The Standard applies to empty enclosures, before the user
has installed protection and operating devices inside them.
The Standard does not apply to enclosures with structural
and functional characteristics that make them subject to
other prescriptions (e.g. cases for domestic installations
and the like). In this case Standards IEC 60670 – CEI 23-48
(“General requirements for enclosures for accessories for
household and similar fixed electrical installations”) and CEI
23-49 (“Enclosures for accessories for household and similar
fixed electrical installations. Part 2: particular requirements for
enclosures for protection devices and accessories dissipating
a considerable power in normal use”) apply. On the basis of
the indications of the ABB SACE technical characteristics’
table, the installer may have to certify compliance with
Standards CEI 23-51 – EN 60439-1 – CEI 17-13-1
(“Part 1: standard equipment subject)
Gemini switchboards features table
Size
1
2
3
4
5
6
Gemini with transparent door
1SL0211A00
1SL0212A00
1SL0213A00
1SL0214A00
1SL0215A00
1SL0216A00
Gemini with opaque door
1SL0201A00
1SL0202A00
1SL0203A00
1SL0204A00
1SL0205A00
1SL0206A00
External dimensions WxHxD (mm)
335x400x210
460x550x260
460x700x260
590x700x260
590x855x360
840x1005x360
Internal dimensions WxHxD (mm)
250x300x180
375x450x230
375x600x230
500x600x230
500x750x330
750x900x330
IP degree
IP66
IP66
IP66
IP66
IP66
IP66
3
Double isolation
Sì
Sì
Sì
Sì
Sì
Sì
IK degree
10
10
10
10
10
10
GWT (°C)
750
750
750
750
750
750
Operating temperature
-25 °C … +100 °C -25 °C … +100 °C -25 °C … +100 °C -25 °C … +100 °C -25 °C … +100 °C -25 °C … +100 °C
No. of DIN modules
24 (12x2)
54 (18x3)
72 (18x4)
96 (24x4)
120 (24x5)
216 (36x6)
No. of vertical modules (H=150 mm)
2
3
4
4
5
6
Material
Thermoplastic
Thermoplastic
Thermoplastic
Thermoplastic
Thermoplastic
Thermoplastic
Color
Gray RAL7035
Gray RAL7035
Gray RAL7035
Gray RAL7035
Gray RAL7035
Gray RAL7035
Fast wiring system
Unifix L
Unifix L
Unifix L
Unifix L
Unifix L
Unifix L
No. of locks
2
2
2
2
3
3
Rated frequency
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
50-60 Hz
45 W
72 W
85 W
102 W
156 W
248 W
STANDARD CEI 23-51(1)
- Max. dispersible power(2)
STANDARD CEI EN 60439-1
Over-temperature (par. 8.2.1)(3)
- Max. dispersible power with over-temperature of 25 °C 40 W
65 W
77 W
91 W
133 W
205 W
- Max. dispersible power with over-temperature of 30 °C
72 W
85 W
102 W
156 W
248 W
45 W
- Max. dispersible power with over-temperature of 35 °C
52 W
85 W
100 W
121 W
187 W
299 W
- Max. dispersible power with over-temperature of 40 °C
62 W
100 W
118 W
143 W
221 W
355 W
Impulse withstand (par. 8.2.2)
- Rated service voltage(4)
≤ 800 V
≤ 800 V
≤ 800 V
≤ 800 V
≤ 800 V
≤ 800 V
- Rated impulse withstand voltage
8 kV
8 kV
8 kV
8 kV
8 kV
8 kV
(1)
(2)
(3)
(4)
imits of applicability of the standard CEI 23-51
L
The standard may be applied only when the wired switchboard meets all the following conditions:
- fixed installation with average ambient temperature up to 25 °C, occasionally up to 35 °C;
- alternate current with rated voltage up to 440 V;
- input rated current up to 125 A;
- assumed short circuit rated current up to 10 kA or liming current devices protection with limited current up to 15 kA at their rated breaking capacity.
Maximum dissipation power data was obtained following the indications of Standard CEI 23-49, with a temperature difference of Dt=30 °C.
Note to paragraph 8.2.1 of Standard CEI EN 60439-1
The table gives the thermal dissipation values of Gemini switchboards when they are wall-mounted. The dispersible power figures (in Watts) vary according to the overtemperature
allowed in the accessible parts of the switchboard and must be compared with the total amount of power dissipated by all the components installed inside the switchboard taking
into due account the factor of contemporaneity.
Rated service voltage according to CEI EN 61439-1 1000V AC and 1500V DC
Gemini | 1SLC805001D0205
3/3
Technical information
IP degree of protection
As indicated in the following table, the IP degree of protection
is expressed by two characteristic numbers depending on
the behavior of the product to which it refers according to the
prescriptions of CEI 70-1 and IEC 529 Standards.
First number: protection against the
3 penetration of solid bodies
IP
Second number: protection against the
penetration of water
IP
0
1
With IP66 degree of protection, Gemini switchboards are
totally protected against the penetration of dusts and sprays
of seawater.
ø 50 mm
No protection
0
No protection
Protection against the penetration of solid bodies
1
Protection against the penetration of drops of
with a diameter of over 50 mm
2
Protection against the penetration of solid bodies
ø 12 mm
water falling vertically
2
Protection against the penetration of drops of
15
with a diameter of over 12 mm or a length of over
water falling at an angle of up to 15° from vertical
80 mm
5
ø 1 mm
4
ø 2,5 mm
3
Protection against the penetrationof solid bodies
3
with a diameter or thickness of over 2,5 mm
Protection against the penetration of solid bodies
Protection against the penetration of drops of
60
water falling at an angle of up to 60° from vertical
Protection against the penetration of splashes of
4
with a diameter or thickness of over 1,0 mm
Protection against the penetration of dusts
water from all directions
Protection against the penetration of water
5
sprayed by a hose from all directions
6
Total protection against the penetration of dusts
Protection against the penetration of sea water
7
Protection against the penetration of water
15 cm
1st number defined by Standards CEI 70-1 – IEC 60529
6
8
during temporary immersion
Protection against the penetration of water
during continual immersion
2nd number defined by Standards CEI 70-1 - IEC 60529.
3/4
1SLC805001D0205 | Gemini
Technical information
IK degree of resistance to impacts
The IK degree is expressed in Joules in compliance with Standard CEI EN 50102.
IK 05
0,25 kg
400 mm
IK 07
Resistance to impacts with impact
energy up to 0,200 J
IK 08
300 mm
0,25 kg
energy up to 0,150 J
Resistance to impacts with impact
energy up to 0,350 J
IK 09
200 mm
0,25 kg
Resistance to impacts with impact
Resistance to impacts with impact
energy up to 0,500 J
IK 10
impact energy up to 1,00 J
3
0,50 kg
1,7 kg
5 kg
5 kg
400 mm
56 mm
IK 04
80 mm
IK 03
0,25 kg
140 mm
IK 02
0,25 kg
280 mm
IK 01
IK 06
200 mm
IK 0
0,25 kg Resistance to impacts with
400 mm
No protection against impacts
Resistance to impacts with
impact energy up to 2,00 J
Resistance to impacts with
impact energy up to 5,00 J
Resistance to impacts with
impact energy up to 10,00 J
Resistance to impacts with
impact energy up to 20,00 J
Resistance to impacts with impact
energy up to 0,700 J
Gemini | 1SLC805001D0205
3/5
Technical information
Double insulation and self-extinguishing tests
Double insulation
3
Double insulation guarantees that Gemini is protected
against indirect contacts on condition that the manufacturer’s
instructions are observed when carrying out mounting and
wiring operations on the switchboard and that the appropriate
accessories are used (e.g. screw-cover caps).
Double insulation is indicated by the graphic symbol
Self-extinguishing tests
Test text
Equipment required
Glow-wire test
Compliance Purpose
with
Standards
Test results
of the test
IEC 695-2-1
To assess the danger of
If a flame is generated,
CEI 50-11
fire by simulating thermal it must go out within 30
Test
Characteristic
Glow wire
period
30 sec.
elements
Assessment of
ø 4 mm
the time it takes
seconds of removing
for the flame to
by heat sources or by
the glow wire. The
go out
ignition (e.g. glowing
test is conducted at
elements, resistances
temperatures of:
overloaded for short
- 650 °C
intervals)
- 750 °C
- 960 °C
1SLC805001D0205 | Gemini
Heat source
stresses produced
- 850 °C
3/6
Test conditions
Technical information
Resistance to chemical agents
Resistance to chemical agents
The behavior of Gemini switchboards in the presence of chemical agents is indicated in the table with the symbols:
Cold water
■
Hot water
■
Sulfuric acid 50%
■
Hydrochloric acid 36%
■
Acetic acid 60%
■
Benzol
▲
Gasoline
▲
Acetone
■
Ethyl alcohol
■
Ammonia
■
Dichloromethane
▲
Diesel oil - naphtha
▲
Mineral oils and greases
■
Food oils and greases
■
Perchloroethylene
▲
Trichlorethene
▲
Ethylether
■
Toluene
▲
Methanol
■
Wine
■
Fruit juices
■
Laundry lye
■
Detergents
■
3
Caption:
■ high resistance
▲ limited resistance
Gemini | 1SLC805001D0205
3/7
Technical information
Integration with ABB products
Installation of Tmax moulded-case circuit breakers
The table indicates the type of installation required for the
different versions of Tmax moulded-case circuit breakers in
Gemini switchboards.
3
Size
Installation
3p
4p
3p D
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
1
D
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
2
Tmax T1
Tmax T2
Before carrying out wiring operations check compliance with
Standards on the basis of the technical characteristics of the
switchboard and circuit breaker (CEI EN 60439-1).
Tmax T3
K2
3
K2
4
K2
5
K2
6
K2
Caption
- D, installation on DIN rail
- K1, installation with Tmax kit H = 150 (holes made)
- K2, installation with Tmax kit H = 300 (holes made)
- O1, installation on modular plate (1 module, H = 150 mm)
- O2, installation on modular plate (2 modules, H = 300 mm)
- T, installation on total base plate
3/8
1SLC805001D0205 | Gemini
Tmax T4
3p
4p
■
■
Tmax T5
3p D
4p D
3p
4p
3p D
4p D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Installation of Tmax XT moulded-case circuit breakers
The table indicates the type of installation required for the
different versions of Tmax XT moulded-case circuit breakers in
Gemini switchboards.
Installation
3p
4p
3p D
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
3p
4p
3p D
4p D
1
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
K2
3
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
■
■
K2
6
XT4
■
K2
5
XT3
O1
K2
4
XT2
3
Size
2
XT1
Before carrying out wiring operations check compliance with
Standards on the basis of the technical characteristics of the
switchboard and circuit breaker (CEI EN 60439-1).
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
D
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
K1
■
■
■
■
■
K2
■
■
■
■
■
■
O1
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
O2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
T
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
Caption
- D, installation on DIN rail
- K1, installation with Tmax kit H = 150 (holes made)
- K2, installation with Tmax kit H = 300 (holes made)
- O1, installation on modular plate (1 module, H = 150 mm)
- O2, installation on modular plate (2 modules, H = 300 mm)
- T, installation on total base plate
Gemini | 1SLC805001D0205
3/9
Technical information
Integration with ABB products
Unifix L fast wiring system
Unifix is the system patented by ABB for the fast and safe wiring of equipment in the System
pro M range and Tmax and Isomax moulded-case circuit breakers. It is available in three
versions, of which Unifix L is the one most suitable for installing in Gemini switchboards with
rated currents of up to 100 A and short-circuit currents of up to 25 kA.
Unifix L is composed by assembling its components listed in the following tables that should
be referred to when ordering.
3
1SLC805044F0901
The busbars are housed in a system of ducts with a capacity of 100 A and short-circuit current
of 25 kA. They are supplied in two and four-pole versions with from 12 to 36 modules.
They snap onto the back of the DIN rail.
Description
Busbars 2 poles
Dimensions L (mm)
Code
Pack/Pieces
Busbar 100 A, 2 poles, 12 modules
400
ED2993
1/6
Busbar 100 A, 2 poles, 18 modules
450
ED3009
1/6
Busbar 100 A, 2 poles, 24 modules
600
ED3017
1/6
Busbar 100 A, 2 poles, 36 modules
800
ED3025
1/6
Busbar 100 A, 4 poles, 12 modules
400
ED2944
1/6
Busbar 100 A, 4 poles, 18 modules
450
ED2951
1/6
Busbar 100 A, 4 poles, 24 modules
600
ED2969
1/6
Busbar 100 A, 4 poles, 36 modules
800
ED2977
1/6
Busbars 4 poles
Busbars
1SLC805045F0901
Connections are made in copper, cut to size and bent to allow power supply between the
terminals of the modular System pro M devices and the Unifix system busbars. They are
supplied in the versions L1, L2, L3, N and 1p+N depending on the polarity of the device to be
wired.
Connections
3/10
1SLC805001D0205 | Gemini
Description
Connections for different equipment
Code
Pack/Pieces
1/6
Connections with 2 conductors L1/N 16A
ED3108
Connections with 3 conductors L1/L2/L3 16A
ED3116
1/6
Connections with 4 conductors L1/L2/L3/N 16A single phase
ED3124
1/6
Connections with 2 conductors L1/N 40A
ED3355
1/6
Connections with 3 conductors L1/L2/L3 40A
ED3363
1/6
Connections with 4 conductors L1/L2/L3/N 40A
ED3371
1/6
Connections for devices
N° 10 connections L1-N 40A
ED3272
1/10
N° 10 connections L2-N 40A
ED3280
1/10
N° 10 connections L3-N 40A
ED3298
1/10
N° 10 connections L1 100A
ED3033
1/10
N° 10 connections L2 100A
ED3041
1/10
N° 10 connections L3 100A
ED3058
1/10
N° 10 connections N 100A
ED3066
1/10
Feeder with cable 4P 100A (L=350mm)
ED3132
1/10
Feeder with cable 4P 100A (L=1500mm)
ED0026
1/10
Feeder with cable 4P 100A (L=2500mm)
ED0025
1/10
1SLC805046F0901
Feeder modular devices are available with and without cable. Modular devices with cable have
a capacity of 36 A and 2-module dimensions; they are supplied in two and four pole versions.
Modular devices with cable have a capacity of 100 A and 1-module dimensions;
they are supplied in the L1, L2, L3 and N version. Both modular devices connect to the
conductors feeding the busbars directly when installation of the main line switch is not
envisaged.
Description
Feeder modular device with cable
Code
Pack/Pieces
Feeder modular device 2P 100A with cable
ED3082
1/6
Feeder modular device 4P 100A with cable (W=600mm)
ED3090
1/6
Feeder modular device 4P 100A with cable (W=800mm)
ED3413
1/6
Feeder modular device 4P 100A with cable (W=1500mm)
ED3439
1/6
Feeder modular device without cable L1
ED3101
1/10
Feeder modular devices without cable L2
ED3102
1/10
Feeder modular devices without cable L3
ED3103
1/10
Feeder modular devices without cable N
ED3104
1/10
Feeder modular device without cable In 100A
1SLC805046F0901
Feeder modular device with cable
Feeder modular device without
cable
Gemini | 1SLC805001D0205
3/11
3
Electrical connection systems
Screw technology connection
3
Feed-through
Ground circuit
N
Section
UL/CSA
4 mm²
12 AWG
ZS4
5,2 mm
ZS4-PE
5,2 mm
6 mm²
10 AWG
ZS6
6 mm
ZS6-PE
6 mm
10 mm²
6 AWG
ZS10
8 mm
ZS10-PE
8 mm
16 mm²
4 AWG
ZS16
10 mm
ZS16-PE
10 mm
35 mm²
0 AWG
ZS35
16 mm
35 mm²
2 AWG
ZS35-PE
16 mm
70 mm²
00 AWG
ZS70
22 mm
ZS70-PE
22 mm
95 mm²
0000 AWG
ZS95
26 mm
ZS95-PE
26 mm
ZS35-PEN 35 mm
53 2.09"
56.3 2.22"
48.8 1.92"
56.3 2.22"
53 2.09"
48.8 1.92"
IEC
26.7 1.05"
26.7 1.05"
Disconnect with blade
Section
UL/CSA
4 mm²
10 AWG
4 mm²
10 AWG
6 mm²
10 AWG
10 mm²
6 AWG
10 mm²
10 AWG
ZS4-S
5,2 mm
ZS6-S
6 mm
ZS10-S
8 mm
ZS4-S-T2
5,2 mm
ZS4-S-T2.3
5,2 mm
ZS4-S-R1
6 mm
ZS4-S-T2-R1
6 mm
ZS4-S-T2.3-R1
6 mm
56.3 2.22"
48.8 1.92"
53 2.09"
56.3 2.22"
53 2.09"
26.7 1.05"
26.7 1.05"
For 5 x 20 mm fuses (0,197” x 0,787”)
Section
IEC
UL/CSA
4 mm²
10 AWG
4 mm²
10 AWG
ZS4-SF
6 mm
ZS4-SF-T2
6 mm
Note: for additional information refer to SNK Series catalogue, code 1SDC160004D0902.
3/12
1SLC805001D0205 | Gemini
ZS4-SF-R1
6 mm
ZS4-SF-R2
6 mm
ZS4-SF-R3
6 mm
ZS4-SF-R4
6 mm
48.8 1.92"
IEC
3
Double Deck - Feed-through
Double Deck with ground circuit
ZS4-D2
5,2 mm
ZS4-D1
5,2 mm
ZS6-D2
6 mm
ZS6-D1
6 mm
ZS6-D2-PE
53
53 2.09"
2.09"
53 2.09"
26.7 1.05"
1.05"
26.7
26.7 1.05"
26.7 1.05"
26.7 1.05"
ZS4-SP-R1
5,2 mm
6 mm
ZS4-SP-T2-R1
6 mm
ZS4-S-R2
53 2.09"
2.09"
53
53 2.09"
53 2.09"
53 2.09"
53 2.09"
26.7 1.05"
1.05"
26.7
26.7 1.05"
1.05"
26.7
26.7 1.05"
26.7 1.05"
26.7 1.05"
26.7 1.05"
For 5 x 20 mm and 5 x 25 mm fuses (0,197” x 0,787” e 0,197” x 0,984”)
ZS4-SF1
8 mm
ZS4-SF1-T2
8 mm
ZS4-S-R3
6 mm
56.3 56.3
2.22"
56.3
56.3
2.22"
2.22"
2.22"
53 2.09"
2.09"
53
48.8 48.8
1.92"
48.8
48.8
1.92"
1.92"
1.92"
ZS4-SP-T2
56.3 56.3
2.22"
56.3
56.3
2.22"
2.22"
2.22"
8 mm
Disconnect with lever
8 mm
48.8 48.8
1.92"
48.8
48.8
1.92"
1.92"
1.92"
Disconnect with plug
ZS10-SP
48.848.8
1.92"
48.8
48.8
1.92"
1.92"
1.92"
56.356.3
2.22"
56.3
56.3
2.22"
2.22"
2.22"
48.848.8
1.92"
48.8
48.8
1.92"
1.92"
1.92"
56.356.3
2.22"
56.3
56.3
2.22"
2.22"
2.22"
53 2.09"
26.7 1.05"
1.05"
26.7
26.7 1.05"
5,2 mm
6 mm
53 2.09"
2.09"
53
53 2.09"
53 2.09"
ZS4-SP
ZS6-D1-PE
6 mm
Feed-through
ZS4-SF1-R1
8 mm
ZS4-SF1-R2
8 mm
ZS4-SF1-R3
8 mm
ZS4-SF1-R4
8 mm
ZS4-R1
8 mm
Note: for additional information refer to SNK Series catalogue, code 1SDC160004D0902.
Gemini | 1SLC805001D0205
3/13
Technical information
Configurations examples
The selection of components for the configuration of Gemini switchboards depends on the space available and the type of
application. Two examples for each size are given below.
1SLC805048F0901
1SLC805047F0901
3
Size 1
Distribution
Automation
1SL0211A00
Box + opaque door
1SL0201A00
Uprights
1SL0283A00
Metal base plate
1SL0259A00
1-mod. drilled panel + DIN rail
1SL0307A00 (x2)
Inner door
1SL0251A00
Wall-mounting brackets
1SL0342A00
1SLC805050F0901
1SLC805049F0901
Box + transparent door
Size 2
Distribution/Mixed
Automation
Box + transparent door
1SL0212A00
Box + opaque door
1SL0202A00
Uprights
1SL0284A00
Metal base plate
1SL0260A00
Modular plate 1 mod.
1SL0297A00
Inner door
1SL0252A00
Blank panel 1 mod.
1SL0325A00
Wiring duct
See pag. 2/8
Drilled panel 1+1/2 mod. + DIN rail
1SL0313A00
Fix-O-Rapid
See pag. 2/9
Blank panel 1/2 mod.
1SL0319A00
Module covers
12863
3/14
1SLC805001D0205 | Gemini
1SLC805052F0901
1SLC805051F0901
3
Size 3
Distribution/Mixed
Automation
Box + opaque door
1SL0203A00
Uprights
1SL0285A00
Base insulating plate
1SL0269A00
Kit for Tmax
1SL0336A00
Inner door
1SL0253A00
Drilled panel 1 mod. + DIN rail
1SL0308A00(x2)
Wiring duct
See pag. 2/8
DIN rail
1SL0291A00
Fix-O-Rapid
See pag. 2/9
Blank panel 1 mod.
1SL0325A00
Wall-mounting brackets
1SL0342A00
Entrelec terminals
See pag. 3/12-3/13
1SLC805054F0901
1SL0213A00
1SLC805053F0901
Box + transparent door
Taglia 4
Distribution/Mixed
Automation
Box + transparent door
1SL0214A00
Box + opaque door
1SL0204A00
Uprights
1SL0285A00
Metal base plate
1SL0262A00
Drilled panel 1 mod. + DIN rail
1SL0309A00 (x3)
Inner door
1SL0254A00
Blank panel 1 mod.
1SL0326A00
Wiring duct
See pag. 2/8
Wiring kit 25x60 mm
1SL0355A00 (x2)
Fix-O-Rapid
See pag. 2/9
DIN rail
1SL0292A00
Fixing on pole kit
1SL0345A00
Module covers
12863
Entrelec terminals
See pag. 3/12-3/13
Gemini | 1SLC805001D0205
3/15
1SLC805055F0901
3
1SLC805056F0901
Technical information
Configurations examples
Size 5
Distribution/Mixed
Automation
1SL0215A00
Box + opaque door
1SL0205A00
Uprights
1SL0286A00
Drilled base plate
1SL0279A00
Kit for Tmax
1SL0337A00
Inner door
1SL0255A00
Modular plate 2 mod.
1SL0303A00
Wiring duct
See pag. 2/8
Blank panel 2 mod.
1SL0332A00
Fix-O-Rapid
See pag. 2/9
Drilled panel 1+1/2 mod.
1SL0314A00
Wall-mounting brackets
1SL0342A00
Blank panel 1/2 mod.
1SL0320A00
Ventilation kit
1SL0350A00
Module covers
12863
1SLC805057F0901
1SLC805058F0901
Box + transparent door
Size 6
Distribution/Mixed
Automation
Box + transparent door
1SL0216A00
Box + opaque door
1SL0206A00
Uprights
1SL0287A00
Metal base plate
1SL0264A00
Modular plate 2 mod.
1SL0304A00
Inner door
1SL0256A00
Blank panel 2 mod.
1SL0333A00
Wiring duct
See pag. 2/8
Drilled panel 1+1/2 mod.
1SL0315A00
Fix-O-Rapid
See pag. 2/9
Blank panel 1/2 mod.
1SL0321A00
Triangular lock
1SL0341A00 (x3)
Panel with holes 1 mod.
1SL0310A00 (x2)
Anti-condensation kit
1SL0351A00 (x3)
Wiring kit 25x60 mm
1SL0356A00
Wiring kit 40x60 mm
1SL0363A00
3/16
1SLC805001D0205 | Gemini
Technical information
Component mounting distances
The reference mounting distances between components for the functional configuration of Gemini switchboards are shown in
the diagrams.
Automation components
3
c
f
p
Size
1
f = distance
mounting plate/floor
c = distance
mounting plate/inner door
Size
MIN.
MAX.
MIN.
MAX.
16,3
91
33,5
110
f
1
p = distance
inner door/door
63
f = distance
door/floor
128
2
63
177
63
177
2
36,4
140
33,5
139
3
3
36,4
140
33,5
139
4
63
177
4
36,4
140
33,5
139
5
63
277
5
47
244
33,5
228
6
63
277
6
47
244
33,5
228
d
d
D
Gemini | 1SLC805001D0205
3/17
Technical information
Component mounting distances
Distribution components
d
d
3
D
d = distance drilled panel/DIN rail
d = distance drilled panel/plate
pos. 1
pos. 2
pos. 3
pos. 4
pos. 5
pos. 6
Size
pos. 1
pos. 2
pos. 3
pos. 4
pos. 5
54,7
67,2
79,7
92,2
-
-
1
51
63,5
76
88,5
-
-
54,7
67,2
79,7
92,2
104,7
117,2
2
51
63,5
76
88,5
101
113,5
54,7
67,2
79,7
92,2
104,7
117,2
3
51
63,5
76
88,5
101
113,5
54,7
67,2
79,7
92,2
104,7
117,2
4
51
63,5
76
88,5
101
113,5
54,7
67,2
79,7
92,2
104,7
117,2
5
51
63,5
76
88,5
101
113,5
54,7
67,2
79,7
92,2
104,7
117,2
6
51
63,5
76
88,5
101
113,5
D = distance blank panel/plate
pos. 1
pos. 2
pos. 3
pos. 4
pos. 5
pos. 6
71,5
84
96,5
109
-
-
71,5
84
96,5
109
121,5
134
71,5
84
96,5
109
121,5
134
71,5
84
96,5
109
121,5
134
71,5
84
96,5
109
121,5
134
71,5
84
96,5
109
121,5
134
p
p
f
f
Size
p= distance
drilled panel/door
f = distance
drilled panel/floor
Size
1
p= distance
blank panel/door
26,5
f = distance
blank panel/floor
162
1
44
145
2
44
3
44
197
2
26,5
214
197
3
26,5
4
214
44
197
4
26,5
214
5
44
297
5
26,5
314
6
44
297
6
26,5
314
Measurements are in millimeters
3/18
1SLC805001D0205 | Gemini
pos. 6
Technical information
Disposal instructions
Information about how to dispose of Gemini switchboards when they reach the end
of their life
Instructions are given below about the procedures to adopt
when disposing of Gemini switchboards at the end of their life
cycle.
The text is drafted in the form of a table referring to Standard
CEI 308-1 “Information table concerning the end of life of
electric and electronic products and a compilation guide”,
2002 -04, ed. 1, pamphlet number 308-1 6454.
Section I – Global product specification
Name
Type of product
Size
With transparent door
With opaque door
Rated weight (kg)
External dimensions WxHxD (mm)
1
1SL0211A00
1SL0201A00
4,3
335x400x210
2
1SL0212A00
1SL0202A00
7,9
460x550x260
3
1SL0213A00
1SL0203A00
9,5
460x700x260
4
1SL0214A00
1SL0204A00
12,0
590x700x260
5
1SL0215A00
1SL0205A00
17,8
590x855x360
6
1SL0216A00
1SL0206A00
21,1
840x1005x360
Section II – Global product table
General code: CER 17 02 03 plastic (more than 95% of the product’s weight)
Part
(P1, P2 ecc.)/Component
number
P1/BOX
Diagram
P5/ACCESSORIES
P2/ROOF
Quantity % over
total weight
Material
description
~ 80%
Polypropylene
Symbol
Dangerousness
(Yes/No)
CER code
No
17 02 03
No
17 02 03
No
17 04 05
>PP<
P2/ROOF
Polycarbonate
>PP<
P3/DOOR
~ 20%
Steel
>PC<
P4/ACCESSORIES
< 5%
Brass
-
No
17 04 01
< 5%
Polypropylene
-
No
17 02 03
P3/DOOR
P1/BOX
P5/ACCESSORIES
P4/ACCESSORIES
Gemini | 1SLC805001D0205
3/19
3
Technical information
Disposal instructions
Section III – Components to be removed from the product and sent for separate treatment
Refer to section II of the table for a description of the materials.
3
Notes for recovery and disposal
At the end of its life, after separating it from components, the
product can be sent to be recovered.
The product is not biodegradable: do not dispose of it in the
environment.
The product/waste product is assimilable as solid urban
waste. It must be incinerated or disposed of in compliance
with current EEC, national and local regulations. You are
recommended to check all reutilization possibilities.
Other recommendations
The information in this sheet are related to the state of supply
of the product. Assembled parts of different suppliers should
be treated separately according to the reference requirements
of their respective manufacturers.
Section IV – Safety instructions
Handling
No special instructions. Refer to the general regulations
concerning hygiene on the workplace when using.
The product’s main components contain mineral additives and
coloring agents in concentrations that comply with current
European Directives at the time this catalogue went to press:
they do not contain substances classified as dangerous.
Transport
No special instructions.
Storage
No gas or harmful vapors are released during storage.
Thermal decomposition in the event of fire or combustion
may release dangerous products: if this should occur, specific
means of protection must be used. In the event of fire,
conventional fire extinguishing instruments are recommended
(atomized water, foam, carbon dioxide, powder).
Empty packages are not contaminated by the product and
can therefore be recycled or reused.
3/20
1SLC805001D0205 | Gemini
Utilization
No special instructions.
Other instructions
The information given in this section is based on current LVP
Division know-how and is aimed at describing the product
only for environmental, health and safety purposes. It must
not, therefore, be considered as a guarantee of specific
properties. LVP Division assumes no responsibility for the
behavior of buyers that do not comply with the information
given in this table and for incorrect or improper usages of the
product or usages that cannot reasonably be envisaged.
Overall dimensions
Basic configuration 4/2
Components for automation applications 4/5
Components for distribution and mixed applications 4/6
4
Gemini | 1SLC805001D0205
4/1
Overall dimensions
Basic configuration
Front view
=
460
460
700
400
=
=
=
150
=
250
=
270
550
300
=
180
=
400
200
4
475
=
335
=
=
=
270
Size 1
Size 2
Size 3
1SL0201A00 - 1SL0211A00 - 1SL0221A00
1SL0202A00 - 1SL0212A00 - 1SL0222A00
1SL0203A00 - 1SL0213A00 - 1SL0223A00
=
840
286
=
=
250
706
558
855
250
385
=
700
400
=
1005
250
250
=
590
250
=
590
=
=
390
=
=
640
=
Size 4
Size 5
Size 6
1SL0204A00 - 1SL0214A00 - 1SL0224A00
1SL0205A00 - 1SL0215A00 - 1SL0225A00
1SL0206A00 - 1SL0216A00 - 1SL0226A00
Top view
30
30
30
30
30
30
30
250
335
375
460
Size 1
Size 2
Size 3
30
30
30
30
500
590
Size 4
Measurements are expressed in millimeters.
4/2
375
460
1SLC805001D0205 | Gemini
500
590
Size 5
30
30
30
30
30
30
30
750
840
Size 6
Side view
360
330
360
330
260
230
260
230
Size 1
Size 2
Size 3
900
750
855
600
700
700
600
550
300
400
450
210
180
1005
260
230
4
Size 4
Size 5
Size 6
Installation with plastic brackets
445
320
320
560
760
412
612
263
463
395
520
Size 1
562
762
195
520
Size 2
645
Size 3
Size 4
695
713
913
863
1063
445
645
Size 5
8
132
100
40
895
Size 6
Bracket
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/3
Overall dimensions
Basic configuration
Installation with stainless steel brackets
445
320
320
560
760
412
612
263
463
562
762
195
4
395
520
Size 1
520
Size 2
645
Size 4
Size 3
695
713
913
863
1063
445
39,5
131,5
95,5
645
4
895
Size 5
Bracket
Size 6
28
28
External opaque and transparent doors
w
Size 1, 2, 3, 4
Measurements are expressed in millimeters.
4/4
1SLC805001D0205 | Gemini
Size 5, 6
h
d
d
h
d/2
w
Size
1
w
325
h
349
Locks
2
d = lock distance
200
2
450
499
2
300
3
450
649
2
400
4
575
649
2
400
5
575
799
3
500
6
825
949
3
750
Overall dimensions
Components for automation applications
Base plate
Metal, drilled
Metal, blank and insulating
s
w
w
=
=
c
=
x
f
=
inner door
base plate
y
h
h
4
Size
w
h
1
235
285
Metal, blank
and drilled
Insulating
f = base distance
c = distance
inner door
s
2
s
5
MIN.
16,3
MIN.
33,5
MAX.
91
MAX.
110
Distance of the
plate from the
inner door
-
Drilling for base mounting
with code 1SL0383A00
Size
1
x
–
y
–
2
360
435
2
5
36,4
140
33,5
139
152,4
2
337
248
3
360
585
2
5
36,4
140
33,5
139
152,4
3
337
398
4
485
585
2
5
36,4
140
33,5
139
152,4
4
462
398
5
485
735
2
5
47
244
33,5
228
252,0
5
462
548
6
735
885
2
5
47
244
33,5
228
252,0
6
711
698
The distance of the plate from the base and inner door depends on the installation point selected for mounting the
plate on the box.
Inner doors
w
w
3
x
b
s
d
39
h
y
h
38
Size
1
2
3
4
5
6
w
250
375
375
500
500
750
h
300
450
600
600
750
900
s
Inner door distance
3
4
4
4
4
4
d = door
63
63
63
63
63
63
x
y
245
365
215
340
340
585
295
435
435
440
590
735
b = base
128
177
177
177
277
277
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/5
Overall dimensions
Components for distribution and mixed applications
300
Size 1
Size 2
Size 3, 4
Size 5
h
900
4
450
600
750
Uprights
Upright
w
Size 6
Measurements are expressed in millimeters.
4/6
1SLC805001D0205 | Gemini
W
Duct
Size
W
132
w
18
h
1
2
152
27
46
3
152
27
46
4
152
27
46
5
152
36
46
6
152
55
46
46
DIN rails
35
22,5
A
d
4
Size
A
d = distance between panel with holes/DIN rail
1
210
pos. 1
51
pos. 2
63,5
pos. 3
76
pos. 4
88,5
pos. 5
-
pos. 6
-
2
318
51
63,5
76
88,5
101
113,5
3
318
51
63,5
76
88,5
101
113,5
4
443
51
63,5
76
88,5
101
113,5
5
443
51
63,5
76
88,5
101
113,5
6
663
51
63,5
76
88,5
101
113,5
The distances of the DIN rail from the Panel depend on depth adjustment made through rail mountings.
Drilled panels
H
h
H
1 module
h
1 + 1/2 module
19
w
d
19
w
Drilled panel
1 mod.
Size
w
H
w
1+1/2 mod.
H
h
Window
module
d = door
b = base
1
250
150
-
-
46
12
44
145
b
Panel distance
2
375
150
375
225
46
18
44
197
3
375
150
375
225
46
18
44
197
4
500
150
500
225
46
24
44
197
5
500
150
500
225
46
24
44
297
6
750
150
750
225
46
36
44
297
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/7
Overall dimensions
Components for distribution and mixed applications
Blank panels
Blank panel 1 module
h
h
Blank panel 2 modules
w
19
4
19
w
h
Blank panel 1/2 module
19
w
Size
1/2 mod.
1 mod.
2 mod.
Panel distance
w
h
w
h
w
h
d = door
b = base
1
250
75
250
150
250
300
26,5
162
2
375
75
375
150
375
300
26,5
214
3
375
75
375
150
375
300
26,5
214
4
500
75
500
150
500
300
26,5
214
5
500
75
500
150
500
300
26,5
314
6
750
75
750
150
750
300
26,5
314
Measurements are expressed in millimeters.
4/8
1SLC805001D0205 | Gemini
d
b
130
b
Kit for Tmax
Kit H 150
Kit H 300
Plate
Plate
f
H
280
130
130
H
f
b
s
B
b
b
f
Panel
Panel
f
H
H
280
280
H
f
4
d
W
d
W
b
b
f
s
B
d
W
kit for Tmax H 300 (available for sizes 2-6)
kit for Tmax H 150 (available for sizes 2-6)
W
H
d
f
b
Size
W
H
d
f
b
2
375
150
19
46
318
2
375
300
19
46
318
3
375
150
19
46
318
3
375
300
19
46
318
4
500
150
19
46
443
4
500
300
19
46
443
5
500
150
19
46
443
5
500
300
19
46
443
6
750
150
19
46
663
6
750
300
19
46
663
W
H
Size
d
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/9
130
Overall dimensions
Components for distribution and mixed applications
b
Kit for Tmax XT
Kit H 150
Kit H 300
Plate
Plate
f
b
4
H
280
130
130
H
f
s
B
b
b
f
Panel
d
W
Panel
f
H
H
280
280
H
f
d
W
b
b
f
s
B
d
W
kit for Tmax XT H 300 (available for sizes 2-6)
kit for Tmax XT H 150 (available for sizes 2-6)
W
H
d
f
b
Size
W
H
d
f
b
2
375
150
10
46
318
2
375
300
10
46
318
3
375
150
10
46
318
3
375
300
10
46
318
4
500
150
10
46
443
4
500
300
10
46
443
5
500
150
10
46
443
5
500
300
10
46
443
6
750
150
10
46
663
6
750
300
10
46
663
W
Measurements are expressed in millimeters.
4/10
1SLC805001D0205 | Gemini
H
Size
d
Modular plates
h
d
h
D
2
w
1 module
w
2 modules
12,5
2,2
73,7
19
12,5
73,7
54,7
71,5
67,2
79,7
84
96,5
92,2
109
104,7
121,5
117,2
134
Drilled panel
Size
4
2
Blank panel
1 module
2 modules
D = distance blank panel/plate
d = distance drilled panel/plate
w
h
w
h
pos. 1
pos. 2
pos. 3
pos. 4
pos. 5
pos. 6
pos. 1
pos. 2
pos. 3
pos. 4
pos. 5
pos. 6
1
210
130
-
-
71,5
84
96,5
109
-
-
54,7
67,2
79,7
92,2
-
-
2
318
130
318
280
71,5
84
96,5
109
121,5
134
54,7
67,2
79,7
92,2
104,7
117,2
3
318
130
318
280
71,5
84
96,5
109
121,5
134
54,7
67,2
79,7
92,2
104,7
117,2
4
443
130
443
280
71,5
84
96,5
109
121,5
134
54,7
67,2
79,7
92,2
104,7
117,2
5
443
130
443
280
71,5
84
96,5
109
121,5
134
54,7
67,2
79,7
92,2
104,7
117,2
6
663
130
663
280
71,5
84
96,5
109
121,5
134
54,7
67,2
79,7
92,2
104,7
117,2
The distance of the panels from the modular plates depends on the depth at which the DIN rail is regulated by using fixing devices.
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/11
Overall dimensions
Components for distribution and mixed applications
Coupling kit
20
B
Y
20
B
Bottom base H 30
X
H
H
4
X
Y
20
H
H
X
X
10
B
X
H
X
H
10
B
Y1
Y
70
Y
70
10
10
Y1
1SLC805001D0205 | Gemini
H
X
Y
-
-
-
2
455
258
90
286
3
455
258
90
286
4
583
260
90
412
5
583
360
190
412
6
834
360
190
662
Y
Y
4/12
B
-
20
B
B
Measurements are expressed in millimeters.
Size
1
Size
B
H
X
Y
1
-
-
-
-
2
458
260
91
316
3
458
260
91
316
4
583
260
91
440
5
590
366
164
400
6
840
366
164
640
H
X
Fixed frame
Size
B
H
X
Y
Y1
1
-
-
-
-
-
2
415
240
130
305
205
3
415
240
130
305
205
4
540
240
130
430
330
5
584
330
210
480
280
6
834
330
210
730
530
X
H
10
B
4
10
Y1
70
Y
Integral cover
51,5
Size
B
H
1
347
238
2
472
289
3
472
289
4
600
289
5
604
390
6
854
390
H
B
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/13
Overall dimensions
Components for distribution and mixed applications
Pedestal
H
s
Front view
4
B
77
H
77
48
Size 4, 5
264
264
B
77
H
77
900
48
Size 6
60
97
97
60
782
B
Size
B
H
s
4
592
254
28
5
592
254
28
6
846
254
28
Measurements are expressed in millimeters.
4/14
1SLC805001D0205 | Gemini
B
Side view
Y
Y1
Y
Y1
Y1
Y1
600
900
4
B
18,5
22
42
62
Size
B
Y
Y1
4
213
130
65
5
313
120
60
6
313
120
60
Size 4
Size 5, 6
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/15
Overall dimensions
Components for distribution and mixed applications
Y
128
H
Horizonal Gemini kit
4
C
B
20
A
50,5
50,5
20
A
D
E
Size
A
B
C
H
Y
D
E
3
56
715,6
523
288
51
692
696
4
56
715,6
523
288
51
692
696
5
60
870
660
388
151
844
848
6
60
1021
810
388
153
994
998
Wiring kit
14
31
60
Duct 25x60 mm
25
A
46
14
60
Duct 40x60 mm
40
Measurements are expressed in millimeters.
4/16
1SLC805001D0205 | Gemini
A
Size
A
1
210
2
318
3
318
4
443
5
443
6
663
Ventilation kit
Anti-condensation
kit
E
B
C
F
A
Code
A
EN0105K
105
EN0150K
150
EN0204K
204
A
D
Ø25
E
F
4
Ø4.5 (da utilizzarsi solo per fissaggio con viti)
Floor pedesta
295
40
55
800
50
180
120
Pole installation kit
60
B
A
L
30
Size
A
B
L
1
232
206
196
2
358
332
320
3
358
332
320
4
483
457
447
5
483
457
447
6
733
707
697
Note: minimum pole section = 150 mm
25
Measurements are expressed in millimeters.
Gemini | 1SLC805001D0205
4/17
Code list
5
5/1
1SLC805001D0205 | Gemini
Code list
Code
Chapter/Page
Code
Chapter/Page
Code
Chapter/Page
05 019
2/8
05 196
2/9
1SL0264A00
2/6
05 033
2/8
05 197
2/9
1SL0267A00
2/6
05 035
2/8
05 198
2/9
1SL0268A00
2/6
05 037
2/8
05 199
2/9
1SL0269A00
2/6
05 043
2/8
05 270
2/9
1SL0270A00
2/6
05 045
2/8
05 272
2/9
1SL0271A00
2/6
05 047
2/8
05 274
2/9
1SL0272A00
2/6
05 049
2/8
05 276
2/9
1SL0275A00
2/6
05 051
2/8
05 278
2/9
1SL0276A00
2/6
05 053
2/8
05 280
2/9
1SL0277A00
2/6
05 063
2/8
05 282
2/9
1SL0278A00
2/6
05 065
2/8
1SL0201A00
2/3
1SL0279A00
2/6
05 067
2/8
1SL0202A00
2/3
1SL0280A00
2/6
05 069
2/8
1SL0203A00
2/3
1SL0283A00
2/11
05 071
2/8
1SL0204A00
2/3
1SL0284A00
2/11
05 073
2/8
1SL0205A00
2/3
1SL0285A00
2/11
05 083
2/8
1SL0206A00
2/3
1SL0286A00
2/11
05 085
2/8
1SL0211A00
2/3
1SL0287A00
2/11
05 087
2/8
1SL0212A00
2/3
1SL0290A00
2/11
05 089
2/8
1SL0213A00
2/3
1SL0291A00
2/11
05 091
2/8
1SL0214A00
2/3
1SL0292A00
2/11
05 093
2/8
1SL0215A00
2/3
1SL0293A00
2/11
05 094
2/8
1SL0216A00
2/3
1SL0296A00
2/14
05 095
2/8
1SL0221A00
2/4
1SL0297A00
2/14
05 096
2/8
1SL0222A00
2/4
1SL0298A00
2/14
05 097
2/8
1SL0223A00
2/4
1SL0299A00
2/14
05 098
2/8
1SL0224A00
2/4
1SL0302A00
2/14
05 099
2/8
1SL0225A00
2/4
1SL0303A00
2/14
05 119
2/9
1SL0226A00
2/4
1SL0304A00
2/14
05 133
2/9
1SL0231A00
2/4
1SL0307A00
2/12
05 135
2/9
1SL0232A00
2/4
1SL0308A00
2/12
05 137
2/9
1SL0233A00
2/4
1SL0309A00
2/12
05 143
2/9
1SL0234A00
2/4
1SL0310A00
2/12
05 145
2/9
1SL0235A00
2/4
1SL0313A00
2/12
05 147
2/9
1SL0236A00
2/4
1SL0314A00
2/12
05 149
2/9
1SL0241A00
2/4
1SL0315A00
2/12
05 151
2/9
1SL0242A00
2/4
1SL0318A00
2/13
05 153
2/9
1SL0243A00
2/4
1SL0319A00
2/13
05 163
2/9
1SL0244A00
2/4
1SL0320A00
2/13
05 165
2/9
1SL0245A00
2/4
1SL0321A00
2/13
05 167
2/9
1SL0246A00
2/4
1SL0324A00
2/13
05 169
2/9
1SL0251A00
2/7
1SL0325A00
2/13
05 171
2/9
1SL0252A00
2/7
1SL0326A00
2/13
05 173
2/9
1SL0253A00
2/7
1SL0327A00
2/13
05 183
2/9
1SL0254A00
2/7
1SL0330A00
2/13
05 185
2/9
1SL0255A00
2/7
1SL0331A00
2/13
05 187
2/9
1SL0256A00
2/7
1SL0332A00
2/13
05 189
2/9
1SL0259A00
2/6
1SL0333A00
2/13
05 191
2/9
1SL0260A00
2/6
1SL0336A00
2/14
05 193
2/9
1SL0261A00
2/6
1SL0337A00
2/14
05 194
2/9
1SL0262A00
2/6
1SL0338A00
2/14
05 195
2/9
1SL0263A00
2/6
1SL0339A00
2/20
Gemini | 1SLC805001D0205
5
5/2
5
Code
Chapter/Page
Code
Chapter/Page
1SL0340A00
2/20
1SL0458A00
2/20
1SL0341A00
2/20
1SL0459A00
2/20
1SL0342A00
2/20
1SL0464A00
2/20
1SL0343A00
2/20
1SL0465A00
2/20
1SL0344A00
2/20
1SL0466A00
2/20
1SL0345A00
2/20
1SL0470A00
2/22
1SL0346A00
2/20
1SL0471A00
2/22
1SL0351A00
2/23
1SL0472A00
2/22
1SL0352A00
2/20
1SL0473A00
2/22
1SL0353A00
2/18
12851
2/23
1SL0354A00
2/18
12863
2/23
1SL0355A00
2/18
12894
2/23
1SL0356A00
2/18
ED2944
3/10
1SL0360A00
2/18
ED2951
3/10
1SL0361A00
2/18
ED2969
3/10
1SL0362A00
2/18
ED2977
3/10
1SL0363A00
2/18
ED2993
3/10
1SL0370A00
2/14
ED3009
3/10
1SL0371A00
2/14
ED3017
3/10
1SL0372A00
2/14
ED3025
3/10
1SL0373A00
2/16
ED3033
3/10
1SL0374A00
2/16
ED3041
3/10
1SL0375A00
2/16
ED3082
3/11
1SL0376A00
2/16
ED3090
3/11
1SL0377A00
2/16
ED3101
3/11
1SL0378A00
2/16
ED3102
3/11
1SL0383A00
2/6-2/23
ED3103
3/11
1SL0384A00
2/23
ED3104
3/11
1SL0385A00
2/21
ED3108
3/10
1SL0386A00
2/21
ED3116
3/10
1SL0387A00
2/21
ED3124
3/10
1SL0388A00
2/21
ED3272
3/10
1SL0389A00
2/21
ED3280
3/10
1SL0390A00
2/21
ED3298
3/10
1SL0401A00
2/20
ED3355
3/10
1SL0413A00
2/21
ED3363
3/10
1SL0414A00
2/21
ED3405
3/11
1SL0415A00
2/21
ED3413
3/11
1SL0416A00
2/21
ED3439
3/11
1SL0423A00
2/22
EN0105K
2/21
1SL0424A00
2/22
EN0150K
2/21
1SL0425A00
2/22
EN0204K
2/21
1SL0426A00
2/22
1SL0433A00
2/22
1SL0434A00
2/22
1SL0435A00
2/22
1SL0436A00
2/22
1SL0451A00
2/22
1SL0452A00
2/22
1SL0454A00
2/22
1SL0455A00
2/22
1SL0456A00
2/22
5/3
1SLC805001D0205 | Gemini
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF