SYSCOIL - Reftec AS

SYSCOIL - Reftec AS
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
SYSCOIL
CENTRIFUGAL FAN COIL UNIT
2012-0
centrifugal fan coil unit
Vers. 2012-0
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
FOR THE USER
FOR THE INSTALLER
INDEX
INTRODUCTION
4
RECOMMENDATIONS
4
TRANSPORTATION, RECEIVING, HANDLING
4
SAFETY RULES
4
GENERAL DIMENSIONS
5
GENERAL TECHNICAL DATA
5
MAIN PARTS
5
RECOMMENDATIONS FOR INSTALLATION
6
FAN COIL INSTALLATION
6
WATER CONNECTIONS
7
Connection to the water mains
7
Condensate water drainage
7
ELECTRICAL CONNECTIONS
7
CONNECTION TO THE TERMINAL BLOCK
7
Without control panel
7
With control panel
7
CHANGING THE MOTOR SPEEDS OF ROTATION
8
TESTING THE FAN COIL
8
TURNING THE COIL
8
USING THE APPLIANCE
9
Using the control panel
CLEANING AND MAINTENANCE
Cleaning the air filter
Cleaning the housing and the control panel
9
9
9
10
WHAT TO DO IF...
10
DISMANTLING THE APPLIANCE
10
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
centrifugal fan coil unit
INTRODUCTION
TRASPORTATION, RECEIVING, HANDLING
This installation, operation and maintenance booklet should always accompany
the fancoil ready consultation by the installer or user if necessary. The appliance
should be installed in compliance with regulations in force in each country and
according to the manufacturer’s or qualified installer’ instruction. The manufacturer cannot be held liable for any damage to property or injury to persons and
animals caused by incorrect installation of the appliance. Only qualified persons
should install the appliance and connect it to the mains electricity supply. Before
carrying out any work on the appliance, ensure that it disconnected from the
electricity supply. Read this instruction booklet before installing the appliance.
The appliance is dispatched enclosed in special protective packaging, which
should be kept intact until the appliance is positioned in the final place of installation.
The appliance should be handled with extreme care, always keeping it in its
original packaging.
One pallet may hold 11 fan coils model 1-6 (9 in vertical + 2 in horizontal) or 9
fan coils model 7-9 (9 in vertical).
To take the appliance out of the packaging, proceed as Pic. 1:
1. Turn the fan coil box upside down and open the bottom.
2. Remove the polystyrene filling and keep it.
3. Keeping the bottom of the box open, turn the pack 180°, taking care that
the contents are firmly hald before resting it gently on the ground. Lift off the
packaging from the appliance.
RECOMMENDATIONS
The appliance is easy to use, ut it is important to read this guide completely
before using for the first time.
This will help you:
- use the appliance in all safety;
- obtain best performance;
- avoid errors;
- respect the environment.
- Do not allow children or unassisted handicapped persons to use the
appliance.
- Do not touch the appliance with wet parts of the body or if barefoot.
- Do not tug, pull or twist electrical cables attached to the appliance, even when
disconnected from the electricity supply.
- Do not open the flaps giving access to the internal parts of the appliance without having first put the system on-off switch to “off”.
- Do not introduce sharp pointed objects through the air intake and outlet grilles.
- Do not leave packing material (cardboard, staples, plastic bags, etc.) within
reach of children since they could be a source of danger.
- Dispose of correctly.
- Do not sit or climb on the appliance or rest any type of object on it.
- Do not spray or throw water directly on the appliance.
- Do not use the appliance in places with suspended dust/powder or in potentially explosive atmospheres, in very damp environments or in
the presence of oil in suspension or in particularly aggressive atmospheres.
- Do not cover the appliance with objects or drapes that even partially obstruct
the air flow.
- The appliance works by electricity at mains voltage (230 Vac, 50 Hz). Always
bear in mind that mains voltage is potentially dangerous and any appliance
connected to it should be used with caution. Before carrying out any work on the
appliance, disconnect it from the electricity supply (by pulling out the plug from
the mains socket or isolating the supply line by putting the on-off switch to off).
- If the appliance is not to be used for long periods, make sure that the controls
are in the position 0 (off). If the appliance is not going to be used in winter when
temperatures are near to freezing, drain the system and ensure that the appliance heat exchanger has no water in it in order to prevent the formation of ice and
consequent breakage.
- To make the appliance inoperable, disconnect it totally from the electricity supply.
- It is unsafe to alter or try to alter the characteristics of this product. Any tampering or alteration renders the warranty null and void.
- In the event of malfunction or failure, do not try to repair the appliance yourself;
contact a qualified technician. Repairs carried out by unqualified persons could
cause damage or accidents.
- Always keep the appliance clean. In particular clean the air filter periodically
(at least once a month).
2
3
1
Pic. 01
SAFETY RULES
Secure packs during transportation.
Do not expose to the elements.
Do not tread on packs.
Protect hands with work gloves when dismantling the appliance.
FAILURE TO COMPLY WITH THE ASSEMBLY INSTRUCTIONS GIVEN IN
THIS GUIDE RELIEVES THE MANUFACTURER OF ALL AND ANY LIABILITY. INCORRECT INSTALLATION COULD CAUSE MALFUNCTIONING OR
FAILURE OF THE APPLIANCE. COULD ALSO REPRESENT A HAZARD
FOR THE USER.
Work in PAIRS if the applinance weighs more than 25 kg.
4
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
centrifugal fan coil unit
GENERAL DIMENSIONS
10-12
7-9
L
M
D
C
180
110
3/4”G
3/4”G
1-6
1/2”G
1/2”G
3/4”G
1/2”G
Ø20
Ø20
Ø20
200
200
without cabinet
with cabinet
220
225
420
167
350
Ø20
147
130
Ø20
400
Ø20
30
147
H
25
234
220
225
with cabinet
257
Pic. 02
* NOTE: dimensions referred to the units with left side water connections
GENERAL TECHNICAL DATA
MODELS
Fans
n°
1
2
3
4
5
6
7
8
9
10
11
12
1
1
2
2
2
2
2
2
2
3
3
3
Row
n°
3
3
3
3
3
3
3
3
3
3
3
3
Fitting
Ø
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
Row
n°
1
1
1
1
1
1
1
1
1
1
1
1
1/2”
Standard coil
Auxiliary coil
Fitting
Condensate drain fitting
Ø
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Ø mm
20
20
20
20
20
20
20
20
20
20
20
20
Height
(H)
mm
480
480
480
480
480
480
585
585
585
602
602
602
Lenght
(L)
mm
660
860
1.060
1.060
1.260
1.260
1.260
1.460
1.460
1.660
1.960
1.960
Depth
(S)
mm
225
225
225
225
225
225
225
225
225
257
257
257
(M)
mm
420
620
820
820
1.020
1.020
1.020
1.220
1.220
1.380
1.680
1.680
(C)
mm
370
570
770
770
970
970
970
1.170
1.170
1.330
1.630
1.630
(D)
mm
395
595
795
795
995
995
995
1.195
1.195
1.356
1.656
1.656
kg
15,2
19,9
25,0
25,2
29,4
29,6
34,9
40,7
41,2
53,0
62,0
62,5
Net weight (max)
Power supply 230V / 1 / 50Hz
5
Tab. 1
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
centrifugal fan coil unit
MAIN PARTS
Pic. 03
1
Air valve
5
Electric motor
9
Load-bearing structure
2
Exchange coil
6
Centrifugal fan
10
Knockouts
3
Condensate drain pan
7
Condensate drain
11
Cover motor panel
4
Air filter
8
Wall-mounting slots
6
Vers. 2012-0
centrifugal fan coil unit
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
RECOMMENDATIONS FOR INSTALLATION
2
Before installing the appliance, ensure that:
1) the place of installation has sufficient space for carrying out installation as
well as routine and extraordinary maintenance work (see Pic. 4).
2) There are no obstructions for air intake and delivery.
3) The water connections are of the sizes, in the position and spaced apart as
required by the appliance (see Dimension).
4) The system pressure does not exceed 8 bar for the water versions.
5) The electricity supply corresponds to the data on the appliance rating plate
and that there is a afety switch readily accessible to the user to cut off the power
supply whenever necessary.
6) The safety switch is in the OFF position so that there is no voltage on the
appliance supply line.
Pic. 08
Pic. 09
To replace the housing.
Take the cabinet from the packing box. Standing in front of the fancoil, lift cabinet, holding it by the sides, and tilt it (Pic. 10).
140
150
90
B
130
A
Pic. 04
Pic. 10
FAN COIL INSTALLATION
Insert the lugs A into the relative slots B (Pic.11). Pivot the cabinet on its base
until it is aligned with the wall. Raise the flaps covering the control panel and
water connections and tighten the two fixing screws (Pic.5).
Before installing the appliance, remove the housing (if present). Raise the flaps
covering the control panel and the water connections. Remove the two screws
fixing the housing to the fan coil load-bearing structure. Gipping the rear of the
housing, remove it as shown in the Pic. 5 (NOTE: be careful of the lugs on the
front part of the load-bearing structure, as shown in Pic.10).
Put the cabinet in the packing box to prevent it from being soiled or damaged
(Pic.6)
Pic. 11
Pic. 05
Pic. 06
Offer the appliance up to the required point of installation and mark, through the
fixing holes, the points on the wall where the holes should be driller for the 4
screw anchors, as shown in Pic. 7.
Vertical version
Horizontal version
Pic. 07
Remove the appliance from the point of installation, drill the holes where merked on the wall (see Pic. 8) and insert the screw anchors. Place the appliance
against the wall and fix it by tightening the screws into the anchors see (Pic.
9). Carry out the water and electrical connections as described in the relevant
paragraphs.
7
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
centrifugal fan coil unit
WATER CONNECTIONS
ELECTRICAL CONNECTIONS
CONNECTION TO THE WATER MAINS
RECOMMENDATIONS!
Before carrying out electrical connections, ensure that the electricity supply to
the supply line has been cut off, checking that the on-off switch is in the OFF
position. Only qualified electricians should carry out the electrical connections.
Check that the mains supply is single-phase 230 Vac/1/50 Hz (± 10%).
Operating the appliance with voltages outside the above limits could cause malfunction and renders the warranty null and void.
The fan coil power supply line should be fitted with at least a switch isolator in
conformity with European standard EN60947-3. Make sure that the electrical
system is suitable for providing not only the working current required by the
appliance, but also the necessary current for powering household and other
electrical appliances already in use.
Any electrical and mechanical alterations or tampering render the warranty null
and void. The motor and accessories power cables in channels or ducts should
remain inside the same until they are inside the appliances.
The cables should be sufficiently long so that they are not permanently taut or
create throttling or pressure on metal parts (see Pic. 16). The power cables
should be sufficiently long so that in the event of accidental tugging the active
wires are subjected to stress before the earth wire. Connect the earth wire to the
relative terminal marked with the symbol .
Check the earth connection. Comply with the safety regulations in force in the
country of installation.
CAUTION! Always use a wrench and nose key for connection of the coil
to the pipes (Pic. 12). If the solenoid valve is installed, suitably insulate the
valve body with insulating material (Pic. 13).
Connect the water inlet and outlet pipes, observing the indications given on the
side of the appliance. Correctly insulate the water supply pipes to prevent dripping during the cooling mode of operation. An shutoff valve should be inserted
on the water supply pipe and balancing valve on the outlet pipe. The valve body
and balancing valve should also be properly insulated to prevent dripping. It is
the installer’s responsibility to insulate properly and the manufacturer cannot be
held liable for any insulation work.
NOTE: it is always advisable to install the solenoid valve. In the heating
mode of operation the solenoid valve reduces consumption because upon
reaching the set temperature the circulation of water is stopped to avoid
wasting energy (the fan coil would otherwise continue to heat like a radiator, even with the motor at a standstill). In the cooling mode of operation
the solenoid valve stops the circulation of water when the set temperature
is reached, this stopiing the internal exchanger
from continuing to condense water with possible undersirable dripping
into the floor. It also reduces chiller operation with consequent energy
saving.
Pic. 16
CONNECTIONS TO THE TERMINAL BLOCKS
Pic. 12
Pic. 13
WITHOUT CONTROL PANEL
The electrical connections should be made to the terminal block on the side of
the appliance (Pic. 17).
Each terminal is identified by the label to be found on the terminal block.
WITH CONTROL PANEL
The electrical connections should be made directly to the control panel, as shown
by the relative wiring diagram. If the control panel has an electronic temperature
sensor (NTC) this sensor will be powered by mains voltage (230Vac/1/50 Hz)
and is therefore provided with double insulation.
CONDENSATE WATER DRAINAGE
The condensate drain pipe should slope downwards by at least 3 cm/m and
should not have ascending or throttled section in order to ensure a regular flow
of water. It is advisable for a trap to be fitted. The condensate drain pipe should
be connected to a rainwater drainage system. Do not use sewage system to
avoid possible odours in the event of evaporation of the water in the trap. Upon
completion of work, check that the condensate flows out properly by pouring
water into the tray (see Pic. 14 and 15). The condensate water drainage system
should be fabricated
in a workmanlike manner and should be periodically checked. The manufacturer
cannot be held liable for any damage caused by dripping in the absence of a
solenoid valve or of periodic maintenance of the drainage system.
CAUTION: FAILURE TO COMPLY WITH THE INDICATED CONNECTIONS
MAY CAUSE MOTOR BURNOUT!
M
Fan motor
T1
Autotransformer
(not installed in all models)
XA1
Fan motor terminal board
5 mm
3 cm/m
3 cm/m
8
Common
(Com)
Min (I)
Med (II)
Pic. 15
Max (III)
Pic. 14
XA1
230 Vac - 50 Hz
Pic. 17
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
centrifugal fan coil unit
CHANGING THE MOTOR SPEEDS OF ROTATION
TURNING THE COIL
The fan coil motor has 6 speed settings, 3 of which are connected in the factory (red, blue and black wires connected to the motor auto-transformer). To
use other speeds than those wired up in the factory, the red (minimum), blue
(medium) and black (maximum) wires may be connected onto 3 of the 6 numbered terminals (1…6), taking into account that the speeds follow a sequence
as shown in Pic. 18.
CAUTION!
The fan may reach the speed of 1,000 rpm. Do not insert objects or hands into
the electric fan. The motor becomes hot during operation; wait for it to cool
before touching it. During the heating mode of operation the exchanger and the
connecting pipes may become very hot (80°C).
Wait for the exchanger to cool before touching it or protect hands with
suitable gloves. The heat exchange water coils are suitable for working up
to ma maximum pressure of 8 bar.
To turn the coil, proceed as follows:
* CAUTION!
UNDER NO CIRCUNSTANCES SHOULD THE CONNECTIONS TO THE TERMINALS L, M, M BE CHANGED!
1
2
6
0
°
Red
Blue
Black
Motor (*)
Common
Motor (*)
0
°
5
3
4
Pic. 18
TESTING THE FANCOIL
Upon completion of installation, scrupulously check both the water and the electrical connections before switching on the appliance.
Before mounting the housing (if present), fill the system, bring it up to pressure and bleed. Make the water circulate and check for leaks.
Check correct operation of the fan coil at the 3 speeds, of the solenoid
valves and of the minimum temperature thermostat (if installed). The cabinet is covered by a protective film: remove it before fixing the housing
to the appliance.
Remount the housing (if present), otherwise the customer has the responsibility of concealing the appliance.
6
0
°
2
0
°
5
6
CAUTION! Protect the appliance with a cardboard box if building works
are still being carried out (Pic. 19).
Pic. 20
1. Remove the housing (if present).
2. Disconnect the terminal block or the control panel (2), if present, from the
side of the appliance.
3. Remove the condensate collecting tray in horizontal models or the galvanised panels in vertical models (4).
4. Remove the coil fixing screws (5).
5. Take out the coil (1), being careful not to be cut by the fins and not to damage them.
6. Remove the knockouts (6) on the opposite side of the fan coil (using a
screwdriver), to allow the coil connections to pass through.
7. Position the coil, turning it without tipping it upside down, so that the fittings
are in line with the holes left by the knockouts.
8. Fix the coil using the previously removed screws (5).
9. Shift the control panel (2), if present, or the terminal block (fixing it to the
side opposite the water fittings), the motor and sensor cables (3), if present,
fixing them with their grips. Ensure that the cables pass through the hole in the
side of the appliance, protecting them with the relative grommet. If it proves easier to carry out this operation by separating the wires from the terminal blocks,
mark the positions of the wires to avoid making mistakes when reconnecting.
10. Reconnect the wires to the relative terminal blocks or control panel (2),
taking care that they are correctly positioned.
11. Replace the condensate collecting tray (4) in horizontal models or the galvanised panels in vertical models.
12. Remount the housing (if present).
Pic. 19
9
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
The room temperature may be set approx. between 10°C and 30°C. If the
appliance does not have a built-in control panel, but is controlled by a
wall-mounted thermostat, refer to the thermostat instructions for use.
USING THE APPLIANCE
CAUTION!
This appliance should only be used by adults. Make sure that children do not
touch the controls or play with the appliance. This appliance has been designed
for use as a heating and cooling appliance in rooms that are clean and frequented by persons (with normal pollution). Avoid using for any other purpose. This
appliance should not be used in places with suspended dust/powder or in potentially explosive atmospheres, in very damp environments or in the presence
of oil in suspension or in particularly aggressive atmospheres.
CLEANING AND MAINTENANCE
The appliance requires no periodic maintenance. Simple checks by the user to
keep it in perfect working order are, however, necessary.
CAUTION! Before carrying out any cleaning or maintenance work, disconnect the appliance from the mains electricity supply!
CLEANING THE AIR FILTER
The appliance is fitted with an air filter on the fan inlet. During normal operation
the filter withholds impurities in the air. The filter should be cleaned periodically
to keep its filtering properties and the airflow to the fan unchanged. It is advisable to clean the filter at least once a month, proceeding as follows.
1. Take out the filter.
2. Place the filter on a flat, dry surface and remove the accumulated dust with
a vacuum cleaner.
3. Wash the filter with water and detergent (no solvents).
4. Leave the filter to dry in a ventilated place in the sun.
5. Replace the filter when it is perfectly dry.
Clean the filter at the beginning and end of every season.
USING THE CONTROL PANEL
If the appliance has a built-in control panel, raise the flap and proceed as
follows.
CONTROL PANEL
WITH THERMOSTAT
BASE CONTROL PANEL
Pic. 21
Heating mode
Put the season selector switch from the off position ( ) to the winter position
( ).
The fan starts.
In models with minimum temperature thermostat (optional), the fan starts when
the internal heat exchanger is sufficiently hot. If the water is not hot enough, the
fan does not start.
Cooling mode
Put the season selector switch from the off position ( ) to the summer position
( ).
The fan starts immediately.
Selecting the fan speed
Put the selector switch to the required speed.
The higher the speed the quicker the room will be heated/cooled, although appliance operation will be noisier (Pic. 22).
Min. speed
centrifugal fan coil unit
Med. speed
WATER
+
DETERGENT
Pic. 24
Description Pic. 24 - Cleaning the filter for the lower intake version
Max. speed
Pic. 22
Automatic temperature adjustment
(for control panel with built-in thermostat)
This control panel has a built-in temperature sensor, which measures the room
air temperature. This information is used for the automatic control of the fan
or introduction of water into the internal exchanger through the solenoid valve
(optional).
The appliance this keeps the room at the temperature set by the user.
WATER
+
DETERGENT
Pic. 25
Description Pic. 25: Cleaning the filter for the front intake version
NOTE
The procedure for ceiling-mounted horizontal version is the same.
Turn the knob towards the symbol +
to raise the temperature
Turn the knob towards the symbol to lower the temperature
Pic. 23
10
Vers. 2012-0
centrifugal fan coil unit
CLEANING THE HOUSING AND THE CONTROL PANEL
To clean the housing, use a dry soft cloth to avoid scratching the enamel.
To clean the control panel and the air outlet louvres, use a vacuum cleaner fitted
with a soft dusting tool or use a separate brush.
Delicately clean the louvres and the controls by removing dust from the cracks
and corners.
Under no circumstances use water.
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
DISMANTLING THE APPLIANCE
This appliance is made to last for many years. Qualified personnel are needed
to dismantle it in all safety. The first operation to be carried out before dismantling the appliance is to disconnect it totally from the electricity supply.
This appliance has been made using recyclable materials (copper, aluminium,
brass, plastic) assembled by screws and push-fits to make separation of the
parts easy.
Contact a firm specialised in differentiated waste disposal; it is the only way
to be certain of correct recycling and thereby contribute to protection of the
environment.
RIFIUTI
Pic. 26
WHAT TO DO IF...
The fan does not work
Possible cause:
power failure
Possible remedy:
check the on/off switch
Possible cause:
switch in position “0”
Possible remedy:
change position on the control panel
Possible cause:
water in the system not hot enought
Possible remedy:
check that the outlet temperature is above 40°C
Little outflowing air
Possible cause:
clogged filter
Possible remedy:
clean the filter
The appliance does not heat
Possible cause:
no hot water in the system
Possible remedy:
check that the boiler and circulating pump are
working
Possible cause:
Incorrectly positioned hot/cold switch
Possible remedy:
check that the switch is on
cooling.
for heating and
for
The appliance does not cool
Possible cause:
no cold water in the system
Possible remedy:
check that the chiller and the circulating pump are
working
The appliance heat/cool very little
Possible cause:
incorrectly regulated thermostat
Possible remedy:
turn the thermostat knob (if installed) left/right
Possible cause:
air in the pipes
Possible remedy:
bleed by loosening the valve at the heat exchanger
inlet
Water on the floor during cooling
Possible cause:
blocked condensate drain
Possible remedy:
switch off the appliance and contact the installer to
check condensate drainage
11
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
Vers. 2012-0
NOTES
12
centrifugal fan coil unit
systemair.com
With the perspective of improvement, and against the continuous action of research and development,
the Manufacturer might modify, even without any prior notice, the given technical data.