Owner Manual

Add to my manuals
44 Pages

advertisement

Owner Manual | Manualzz
Owner
Manual
UCM-CLD
Chiller Control System
RLC-SVU02F-E4
General information
Foreword
These instructions are given as a
guide to the operation of the
controller(s) mounted on Trane
RTAD/RTWB/RTRA chillers. They do
not contain full service procedures
necessary for the continued
successful operation of this
equipment. The services of a qualified
technician should be employed
through the medium of a
maintenance contract with a
reputable service company. Read
this manual thoroughly before unit
start-up.
Warnings and cautions
Warnings and Cautions appear at
appropriate sections throughout this
manual. Your personal safety and the
proper operation of this machine
require that you follow them
carefully. The constructor assumes no
liability for installations or servicing
performed by unqualified personnel.
WARNING! : Indicates a potentially
hazardous situation which, if not
avoided, could result in death or
serious injury.
CAUTION! : Indicates a potentially
hazardous situation which, if not
avoided, may result in minor or
moderate injury. It may also be
used to alert against unsafe
practices or for equipment or
property-damage-only accidents.
Safety recommendations
To avoid death, injury, equipment or
property damage, the following
recommendations should be
observed during maintenance and
service visits:
1. The maximum allowable pressures
for system leak testing on low and
high pressure side are given in the
chapter "Installation". Always provide
a pressure regulator.
2. Disconnect the main power supply
before any servicing on the unit.
3. Service work on the refrigeration
system and the electrical system
© 2009 Trane
should be carried out only by
qualified and experienced personnel.
Reception
On arrival, inspect the unit before
signing the delivery note.
Reception in France only:
In case of visible damage: The
consignee (or the site representative)
must specify any damage on the
delivery note, legibly sign and date
the delivery note, and the truck driver
must countersign it. The consignee
(or the site representative) must
notify Trane Epinal Operations Claims team and send a copy of the
delivery note. The customer (or the
site representative) should send a
registered letter to the last carrier
within 3 days of delivery.
Note: for deliveries in France, even
concealed damage must be looked
for at delivery and immediately
treated as visible damage.
Reception in all countries except
France:
In case of concealed damage: The
consignee (or the site representative)
must send a registered letter to the
last carrier within 7 days of delivery,
claiming for the described damage.
A copy of this letter must be sent to
Trane Epinal Operations - Claims
team.
Warranty
Warranty is based on the general
terms and conditions of the
manufacturer. The warranty is void if
the equipment is repaired or
modified without the written
approval of the manufacturer, if the
operating limits are exceeded or if
the control system or the electrical
wiring is modified. Damage due to
misuse, lack of maintenance or
failure to comply with the
manufacturer's instructions or
recommendations is not covered by
the warranty obligation. If the user
does not conform to the rules of this
manual, it may entail cancellation of
warranty and liabilities by the
manufacturer.
Maintenance contract
It is strongly recommended that you
sign a maintenance contract with
your local Service Agency. This
contract provides regular
maintenance of your installation by a
specialist in our equipment. Regular
maintenance ensures that any
malfunction is detected and corrected
in good time and minimizes the
possibility that serious damage will
occur. Finally, regular maintenance
ensures the maximum operating life
of your equipment. We would remind
you that failure to respect these
installation and maintenance
instructions may result in immediate
cancellation of the warranty.
Training
To assist you in obtaining the best
use of it and maintaining it in perfect
operating condition over a long
period of time, the manufacturer has
at your disposal a refrigeration and
air conditioning service school. The
principal aim of this is to give
operators and technicians a better
knowledge of the equipment they are
using, or that is under their charge.
Emphasis is particularly given to the
importance of periodic checks on the
unit operating parameters as well as
on preventive maintenance, which
reduces the cost of owning the unit
by avoiding serious and costly
breakdown.
RLC-SVU02F-E4
Contents
General Information
2
Principles of operation
of the UCM-CLD module
4
General Information
4
Operator’s Interface
5
Operational Features
9
Diagnostics
16
Diagnostics
16
Default Description
17
Controller for hydraulic module/
free cooling / heat recovery / RTWB
heat pump applications
22
Hydraulic module control
RLC-SVU02F-E4
23
Control logic
23
Module and outputs/inputs
24
Hydraulic module option
25
Data display menu
26
Configuration menu
27
Alarms messages - hydraulic module application
30
Mask and menu chart
31
Free cooling application
32
Heat recovery application
38
RTWB heat pump application
40
3
Principles of Operation of the
Module UCM-CLD
Figure 1 : Operator’s interface
General Information
Alarm
Select Report Group
Custom
Report
Chiller
Report
Refrigerant
Report
Compressor
Report
Select Setting Group
Operator
Settings
Service
Settings
Service
Tests
Diagnostics
Previous
Enter
Auto
Next
Cancel
Stop
This UCM-CLD chiller control is
composed of eight electronic
modules, which each have their
own 115V or 24V power supply and
communicate with each other via a
serial link. The names of the
modules are linked to their
functions.
ADAPTIVE CONTROL™
Module
MCSP (Motor Compressor Start and Protection)
CPM (Chiller Protection and Management)
EXV (Electronic Expansion Valves)
CSR (Communication and Setpoint Reset)
Local CLD (Local Clear Language Display)
Remote CLD (Remote Clear Language Display)
Functions
Safety, protection, and control of the helical-rotary compressor and
its components
Safety, protection, and control of the chiller
Control of both electronic expansion valves
,Control of the serial communication, unit external setpoints and
ice-making mode (optional module)
Operator interface located in the front panel of the unit
Operator interface located up to 1500m from the unit, able to
communicate with up to four units of the same type (optional module)
TCI IV, IPCB (Tracer Communication Interface 4, Inter Processor
Communication Buffer)
Protection of the internal communication bus in the unit from external
interferences (optional factory-mounted module, compulsory when
using a Remote CLD)
TCI IV, COM 3 (Tracer Communication Interface 4, COM 3)
Interface between the control of the unit and a Building Management
System using Trane COMM 3 serial link
4
RLC-SVU02F-E4
Principles of Operation of the
Module UCM-CLD
Figure 2 : Control panel mounted on a model RTWA unit
Operator's Interface
Digital Display
The display of control regulation and
operating parameters, diagnostics,
and error messages is a 2-line, 40character, liquid-crystal display. The
display has a LED backlight to read
in low-light conditions and to warm
up the display under low ambient
temperatures. When powering up
the system, the display is not lit and
the message [SELF-TEST IN
PROGRESS] is displayed. The screen
can display error codes, settings of
various setpoints, specified
temperature and pressure values,
and the status of operating
parameters and options.
Keyboard
A 16-key touchpad allows both
navigation between menus and the
modification of parameters and
setpoints. The keys are divided into
two groups:
Individual Menu Keys
Control Keys
Chiller Report Menu
+ key
- key
Custom Report Menu
Refrigerant Menu
Previous key
Compressor Menu
Next key
Operator Settings Menu
Enter key
Service Settings Menu*
Cancel key
Service Test Menu*
Auto key
Diagnostics Menu
Stop key
* Levels 2 and 3 of the Service Settings Menu and the Service Test Menu are protected by a
password and are reserved for Trane Service Engineers.
RLC-SVU02F-E4
5
Principles of Operation of the
Module UCM-CLD
Control Key Functions
[+] key If the information displayed
is read-only, pressing this key will
add it to the operator's menu. If the
information can be modified,
pressing this key will increase the
value without exceeding the
maximum possible value.
[-] key If the information displayed
is read-only, pressing this key will
remove it from the operator's menu.
If the information can be modified,
pressing this key will decrease the
value without exceeding the
minimum possible value.
[Previous] key Pressing this key
allows the operator to scroll up to
the previous information in the
current menu. Each menu is
looped, making it possible to scroll
from the first item in the menu to
the last item.
[Next] key Pressing this key allows
the operator to scroll down to the
next information in the current
menu. Each menu is looped, making
it possible to scroll from the last item
in the menu to the first item.
[Enter] key Pressing this key allows
the operator to validate a value after
modification.
[Cancel] key This key should be
pressed if a modified setting should
not be saved.
6
[Auto key] Pressing this key allows
the unit to be in Auto mode if it was
previously placed in Stop mode
with the [Stop] key. The unit cannot
be forced into Auto mode if an
external contact or the serial link
has stopped it. When the unit is
stopped by the remote interface
(Remote CLD), the local mode order
has priority.
[Stop] key Pressing this key allows
the unit to be in Stop mode. In
every case, and whatever the origin
(except a local stop), the stop order
and stop status have priority over a
run order. The stop generated is a
soft stop - the unit unloads before
stopping.
Whether a [Stop] or [Auto]
command will be accepted and
stored is based on the following
hierarchy:
1. Local Stop will always replace
Local Auto, Remote Auto, and
Remote Stop.
2. Local Auto will always replace
Local Stop, Remote Auto, and
Remote Stop.
3. Remote Stop will always replace
Local Auto and Remote Auto. It
will not replace Local Stop.
4. Remote Auto will always replace
Local Auto and Remote Stop. It
will not replace Local Stop.
Pressing the [Stop] key twice within
five seconds will result in an
Emergency Stop. The chiller will not
unload.
RLC-SVU02F-E4
Principles of Operation of
the Module UCM-CLD
Parameters and setpoints within each menu
Menu
Parameters/setpoints
Chiller Report Menu
Active Chilled Water Setpoint
Evaporator Entering/ Leaving Chilled Water Temperature
Condenser Entering / Leaving Chilled Water Temperature
Active Ice-Storing Setpoint
Active Hot Water Setpoint
Entering/Leaving Hot Water Temperature
Current Active Setpoint limits
Evaporator/Condenser Waterflow
Ambient Air Temperature
Sources of setpoints (Tracer, local CLD, external)
Custom-built by the operator (Can contain up to 20 settings)
Condenser/Evaporator Refrigerant Pressures
Refrigerant Temperature in Condenser
Refrigerant Temperature in Evaporator
Compressor Status
Time and Start Counters
Amps (% RLA)
Oil Temperature (GP compressor only)
Setpoint Source
External Chilled Water Setpoint
External Hot Water Setpoint
Chilled Water Pump Operation
Chilled Water Pump Off Delay
Ice Machine Control*
Panel Ice Termination Setpoint
Low Ambient Lockout
Low Ambient Lockout Setpoint
Front Panel Current Limit Setpoint
Front Panel Hot Water Setpoint
Front Panel Chilled Water Setpoint
Design Delta Temperature Setpoint
External Current Limit Setpoint
Differential to Start Setpoint
Chilled Water Reset Type
Type Reset Ratio
Type Start Reset Setpoint
Type Max Reset Setpoint
Custom Report Menu
Refrigerant Report Menu
Compressor Report Menu
Operator Settings Menu
RLC-SVU02F-E4
Range
Minimum/Maximum
-17.8°/18.3°C
1 min/30 min
-6.6°/-0.5°C
-28.8°/15.5°C
40%/120%
25°/60°C
-17.8°/18.3°C
2.2°/16.6°C
1.1°/16.6°C
0.0°/11.1°C
7
Principles of Operation of
the Module UCM-CLD
Service Settings Menu**
Service Tests Menu
Diagnostics Menu
LEVEL ONE-Information adjusted by customer
Unit Line Voltage
Over/Undervoltage Protection
Restart Inhibit Time
Balanced Compressor Starts and Hours
Display Language and Units
Programmable Relay Set-up
External Circuit Lockout
LEVEL TWO- Information adjusted by Service Engineer
Address of Serial Link
Display Lock Feature
Leaving Water Temperature Setpoint
Low Refrigerant Temperature Cutout Setpoint
Low Water Temperature EXV Air Compressor
Condenser Limit Setpoint
Phase Unbalance Protection
Phase Reversal Protection
Superheat Setpoint
EXV Control Response Circuit 1
EXV Control Response Circuit 2
Leaving Water Temperature Control Response Setpoint
Fan Control Deadband bias Circuit 1
Fan Control Deadband bias Circuit 2
LEVEL THREE-Configuration/Protection Information
Compressor Model Number Prefix
Number of Compressors
Oil Loss Differential Setpoint
Compressor A Ton
Compressor B Ton
Compressor C Ton
Compressor D Ton
Fan Control
Variable Speed Fan Circuit 1
Variable Speed Fan Circuit 2
Number of Fans Circuit 1
Number of Fans Circuit 2
Reduced Inrush Starting
Current Overload Compressor A
Current Overload Compressor B
Current Overload Compressor C
Current Overload Compressor D
Low Ambient Unit Half Air Flow Fan
Low Ambient Unit Two-Speed Motor
Night Noise Setback
Number of EXV Circuit 1
Number of EXV Circuit 2
Refrigerant Type
Perform Expansion Valve Test
Perform Circuit locking or Pump-out Test
Perform Compressor Test
Current Diagnostics
History of Diagnostics
Manual Reset of Diagnostics
Erase History of Diagnostics
30/120 sec
1/12
0/64
60/120%
2.2°/11.1°C
2/200
2/200
-50/50
-50/50
* Option
** This menu has three access levels. The control has a display lock feature that can be locked at request after level one.
8
RLC-SVU02F-E4
Principles of Operation of
the Module UCM-CLD
Operational features
Entering evaporator water
temperature
When one or both compressors are
running, the UCM continually
monitors and compares the
entering and leaving evaporatorwater temperatures. If the
temperature of the entering water
drops more than 1°C below the
leaving water temperature for more
than
55°C- seconds, the UCM uses this to
indicate a loss of water flow
through the evaporator. This will
shut down that circuit's compressor
and will display MMR diagnostic.
Current Limit Setpoint (CLS)
The current limit setpoints for the
system are entered through the
Clear Language Display menus. The
current limit Setpoint for each
compressor is shown in Table 1.
Table 1 – Compressor current limit
Setpoint versus Chiller current
limit Setpoint
System
CLS
120%
100%
80%
60%
40%
Numbers of compressor in
operation
One
Two
120
120
120
100
120
80
120
60
80
40
Electronic expansion valve
(EXV) test
This test can be performed only when
the “Stop“ key has been pressed. It
will confirm proper operation of the
electronic expansion valve and the
EXV module.
After the test has been initiated at
the Clear Language Display, the
UCM will:
1. Overdrive the EXV closed
(25 seconds)
2. Overdrive the EXV open
(25 seconds)
3. Overdrive the EXV closed
(25 seconds)
4. Reset the display to disable and
end the test
The EXV produces an audible
clicking sound when it is driven
against its end stops. Step 1 drives
the EXV to its closed position,
during which time service personnel
can move from the CLD to the EXV.
Current overload protection
The UCM continually monitors
compressor current to provide unit
protection in the event of an
overcurrent or locked-rotor
condition. Protection is based on
the phase with the highest current
and, if limits are exceeded, the UCM
will shut down the compressor and
will display an MMR diagnostic.
Leaving chilled-water temperature
control
If the Auto key is pressed and a
remote chilled-water Setpoint has
been communicated, the UCM will
control to that Setpoint. Otherwise,
it will control to the front-panel
Setpoint. Control is accomplished
both by staging compressors and
by modulating the slide valves on
each compressor.
Upon start-up, if the leaving chilledwater temperature is dropping 0.8°C
per minute or faster, the chiller will
not load further.
Note: A tool may be needed to aid
in hearing the clicking of the EXV,
such as a screwdriver held between
the EXV and the ear.
Based upon current levels received
at the UCM, the compressor slide
valve is modulated to prevent the
actual chiller current from
exceeding the CLS.
When a compressor is turned off,
the CLS for the remaining running
compressor shall be reset upward
immediately. When a compressor is
added, the CLS for the running
compressor shall be ramped
downward at a rate not less than
10% RLA per minute to the new
Setpoint.
RLC-SVU02F-E4
9
Principles of Operation of
the Module UCM-CLD
Chilled-Water Reset (CWR)
As an option, the UCM will reset the
chilled-water temperature setpoint,
based on either the return water
temperature or the outdoor air
temperature. The CSR module is
necessary to perform CWR.
If the leaving-water temperature
cutout is set upward, the Clear
Language Display will maintain the
2.7°C minimum and will
automatically raise the settings on
the front-panel and active-chilledwater setpoints, if necessary.
The following are selectable:
If the front-panel or active-chilledwater setpoints were adjusted, the
display will show the following
when the “enter“ key is pressed:
One of four reset types, from top to
bottom in order of reset:
If the leaving-water temperature
drops below the cutout setpoint
while the compressors are deenergized, it will produce an IFW
diagnostic. If the leaving-water
temperature drops below the cutout
setpoint while the compressors are
energized for 16°C-seconds, the unit
will shut down on an MAR
diagnostic.
no CWR
RETURN WATER TEMPERATURE
RESET
ZONE TEMPERATURE RESET
FRONT PANEL CHILLED WATER
SETPOINT HAS BEEN
INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE
OUTDOOR AIR TEMPERATURE
RESET
Leaving-water temperature cutout
This temperature cutout provides
protection against freezing caused
by low leaving-water temperature.
The setpoint is both factory-set and
adjustable from the Service Setting
Menu. Temperatures below the
setpoint will cause the UCM to
accelerate reduction of chiller
capacity, even to the point of
compressor shutdown. A nonlatching diagnostic will be
generated if the LWT is below the
cutout for more than 16°C-seconds.
There must be a minimum of 2.7°C
between the cutout temperature
and both the front-panel and activechilled-water setpoints. The Clear
Language Display will not permit
setting of either the front-panel or
active-chilled-water temperatures
less than 2.7°C above the cutout
temperature. The second line will
state:
Limited by Cutout Setpoint (+)
to change
10
RLC-SVU02F-E4
Principles of Operation of
the Module UCM-CLD
Low refrigerant temperature cutout
Both circuits are protected from a
saturated-evaporator refrigerant
temperature that goes below this
setting. The cutout Setpoint must be
at a minimum of 8°C lower than the
front panel or active chilled-water
setpoints. See Table 2 for proper
settings.
There must be a minimum of 8°C
between the cutout temperature
and active chilled-water setpoints.
The Clear Language Display will not
permit setting of the chilled-water
temperature less than 8°C above
this cutout temperature, and the
display will flash the last valid
temperature.
If the leaving-water temperature
cutout is set upward, the Clear
Language Display will maintain the
8°C minimum and will raise the
settings of the chilled-water
setpoints, if necessary.
If the saturated-evaporator
refrigerant temperature for a circuit
drops below this Setpoint for longer
than 16°C-seconds, the circuit will
be shut down and a CMR diagnostic
will be displayed.
If the chilled-water setpoints were
adjusted, the display will show the
following when the “Enter“ key is
pressed:
FRONT PANEL CHILLED WATER
SETPOINT HAS BEEN
INCREMENTED DUE TO CUTOUT
SETPOINT CHANGE
Table 2 – Leaving fluid temperature setpoints
Leaving
chilled-water
temperature
°C
5
4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
-11
-12
RLC-SVU02F-E4
Leaving-water
temperature
cutout
°C
1.5
1
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
-11
-12
-13
-14
-15
Low refrigerant
temperature
cutout
°C
-3.9
-4.4
-5.4
-6.4
-7.4
-8.4
-9.4
-10.4
-11.4
-12.4
-13.4
-14.4
-15.4
-16.4
-17.4
-18.4
-19.4
-20.4
Recommended
%EG
%
0
10
13
16
18
20
22
24
26
27
29
31
32
33
34
36
36
37
Solution
freeze
point
°C
0
-4
-5
-7
-8
-9
-10
-11
-13
-13
-15
-16
-17
-18
-19
-20
-20
-21
11
Principles of Operation of
the Module UCM-CLD
Balanced compressor starts
and hours
This feature is enabled/disabled in
balanced starts and hours (service
setting menu). When enabled, the
UCM will start the compressor with
the fewest starts and stop the
compressor with the greatest number
of operating hours, as determined by
the “compressor starts“ accumulator
and the “compressor hours“
accumulator. This will tend to balance
out hours and starts equally over both
compressors.
If phase-unbalanced protection
(service setting menu) is enabled
and the average three-phase current
is greater than 80% RLA, and the
percent of imbalance is calculated
to exceed 15%, the UCM will shut
down the compressor and display a
CMR diagnostic.
Reverse rotation protection
The Clear Language Display
monitors incoming current during
start-up and will shut down the
compressor within one second if
phase reversal is detected.
Phase imbalance protection
The Clear Language Display
monitors the current in each phase
and calculates the percentage of
imbalance as follows:
% imbalance = (Ix - I average)
I average
C AUTION
Phase relationship during
installation of unit power must be
carefully controlled to ensure
compressor protection against
reversed rotation.
Oil failure protection
The logic of the UCM uses a
comparison of the entering oil
temperature at the compressor, to
the saturated-condenser
temperature, to determine if there is
an oil line restriction.
The differential between the
entering-oil and the saturatedcondenser temperatures is referred
to as the “oil loss differential
setpoint“ in the service settings
menu.
If the entering oil temperature drops
2°C below the saturated-condenser
temperature for more than
30 minutes, the circuit will shut
down on a CMR diagnostic. The
diagnostic will be presented as:
OIL SYSTEM FAULT - CKT X
I average = (I1 + I2 + I3) / 3
Ix = phase with greatest difference
from I average (without regard
to sign).
DIP switch settings
Compressor overload DIP switches.
IPC address
The IPC address sets the address for Inter-Processor Communications of the
Clear Language Display modules. The following are the IPC DIP switch
settings for the modules.
IPC DIP
Switch
1
2
3
4
5
12
Module
A20-2
A20-1
SW1
OFF
OFF
SW2
Based
On
Motor
RLA
SW1
OFF
OFF
SW2
Based
On
Motor
RLA
A52
SW1
OFF
OFF
A9
SW1
OFF
OFF
RLC-SVU02F-E4
Principles of Operation of
the Module UCM-CLD
2-10 V (dc)/4-20 mA input for External
Chilled-Water Setpoint (CWS) or
Current limit Setpoint (CLS)
When either external CWS or
external CLS is used on the optional
module A9, DIP switch SW1
positions 1 and/or 2 must be set to
accommodate the type of of signal
source the customer has chosen,
either 2-10 V (dc) or 4-20 mA.
Position SW1-1 sets 2-10 V (dc)/420 mA for external CLS. The “OFF“
setting configures the external input
for 2-10 V (dc)/4-20 mA for external
CLS. The “OFF“ setting configures
the external input for 2-10V (dc), the
“ON“ setting configures the
external input for 4-20 mA.
Leaving Condenser-Water
Temperature control option Model RTWB
If the machine is delivered with the
LCWT control option (digit 49
position 3), the DIP switch on the
module A9 must be set at position
“ON.“ This option controls the
condenser (CDS) leaving-water
temperature (LCWT) based on a Hot
Water Temperature setpoint (HWSP).
Limitations
In the heating mode, the chiller is
not able to provide chilled water for
a process. The leaving chilled-water
temperature is not controlled. The
UCM will only take care of safeties
(water flow and freezing).
The option will provide contact to
start/stop the evaporator and the
condenser pumps. Any other devices
such as valves (2 ways/3 ways), heat
exchangers, variable-volume pumps,
or other equipment will have to be
controlled by another system.
Condenser Water Temperature
Sensors - RTAD Total and Partial
Heat Recovery
UCM-CLD will not display leaving
and entering water temperature
above 70.1°C, whereas on Total Heat
Recovery units, the temperature on
the additional controller could be
higher. These conditions would
appear in cooling mode only. This is
not harmful to the operation of the
chiller.
Mechanical control settings
The settings for the High Pressure switch are shown below:
Pressure Switch
B51
High Pressure
B23
Low Pressure
B23
Low Pressure
Approval
PED
Czech republic
Poland
PED
Czech republic
Poland
-4°C<LWTE<+15°C
PED
Czech republic
Poland
-12°C<LWTE<-4°C
Close
19-20 bar
Open
22-23 bar
1.5 bar
0.5 bar
1.2 bar
0.2 bar
Figure 3 - Water Temperature Sensor Installation - Model RTWB
Clamping Nut
Compression
Fitting
Fitting Body
1/2" NPT x 1-1/2" Large Coupling
RLC-SVU02F-E4
13
Principles of Operation of
the Module UCM-CLD
Hot-Water Mode Control
Module - Option Model
RTWB
Scope of Supply
The following parts will be installed
in the control panel of the unit:
• One Additional Board A70 with
display
• One CDS LWT sensor + immersion
well to be installed by the customer
The sensor will be connected to
terminals B3 and GND on terminal
block J2 of the A70 module.
Sequence of Operation
• Cooling Mode
The unit will operate as a standard
chiller (i.e., the chiller controls the
leaving chilled-water temperature).
The condenser pump will be driven
by the UCM relay. The chiller uses
the cooling setpoint defined in the
A70 Module.
• Heating Mode
In the heating mode, the chiller will
control the condenser leaving-water
temperature. The temperature sensor
connected to the A70 Module should
be located in the condenser leavingwater connection downstream from
the condenser. The control is done by
loading or unloading the chiller. To
load or unload the chiller, a chilledwater setpoint reset is applied (i.e.,
setpoint decrease = load; setpoint
increase = unload). The condenser
pump is always in operation. The
evaporator pump is still controlled by
the UCM and is always in operation.
The chiller uses the heating setpoint
defined in the A70 Module.
The chiller will be stopped if the
condenser leaving-water
temperature is greater than the
setpoint + the “differential to stop”.
The chiller will start if the condenser
leaving-water temperature is lower
than the setpoint - the “differential
to start”.
• Sensor Failure
In the heating mode, and if the CDS
leaving-water temperature sensor
fails, the chiller is stopped and the
alarm relay of the A70 Module is
energized. The chiller can operate in
the cooling mode if the CDS
leaving-water temperature sensor
has failed.
A70 Module and UCM interaction
Chilled-Water setpoint: The A70
Module drives the chilled-water
setpoint using a linear signal from
an Analog Output of the A70
Module to the external chilled-water
setpoint input of the UCM.
Chiller Enable/Disable: The A70
Module drives the chiller (on or off)
using a dry contact from the A70
Module to the external start/stop
input of the UCM.
CDS pump relay: The A70 Module
drives the condenser pump relay.
In heating mode, the chiller controls
the condenser leaving-water
temperature. The A70 Heat Pump
Module sends an external chilledwater setpoint to the UCM. This
analog signal (factory set at 420mA) is constantly reset to match
the heating load.
• Setpoint decreases Æ load the
chiller
• Setpoint increases Æ unload the
chiller
Note that the UCM still operates as
a chilled-water controller.
On the UCM-CLD, the parameter
“External Chilled Water setpoint”
has to be enabled.
14
RLC-SVU02F-E4
Principles of Operation of
the Module UCM-CLD
Local/ External unit control mode
From the Settings menu, the end
user can select the Control mode.
Refer to Table 4 for the setting rule.
- Control Mode: No
This input will be powered in 0-1V
or 4..20mA. The configuration will
allowed 0-1V or 4..20mA signals.
This signal will create a heating
setpoint between 25°C and 60°C.
In this case, the active cool and heat
setpoints and Heat/Cool selection
will come from the front panel (User
Settings 1).
- Control Mode: Partial
In this case, the active cool and heat
setpoints will come from the front
panel (User Settings 1). The active
Heat/Cool selection will come from
the external Cool/Heat input.
- Control Mode: Full
In this case, the active cool and heat
setpoints and Heat/Cool selection
will come from the external analog
and digital inputs.
- AI: External heating setpoint input
(configurable)
Note: The input configuration must
be done before any signal
connection.
Refer to Table 3 for the setting rule.
- DI: External ON/OFF input
This input will be normally powered
in 24Vac. This input will be the
external Auto/Off unit.
0V
"Open" : unit disabled
24Vac
"Close" : unit enabled
- AI: External cooling setpoint input
(configurable)
- DI: External Heat/Cool input
(configurable)
This input will be powered in 0-1V
or 4..20mA. The configuration
(available from menu “User
Settings 2) will allowed 0-1V or
4..20mA signals. This signal will
create a cooling setpoint between
-17.8°C and 18.3°C.
This input will be normally powered
in 24Vac. This input will be the
external Heat/Cool mode switch.
0V
"Open" : Cooling mode
24Vac
"Close" : Heating mode
Note: The A70 module will scale
automatically the value between
-12°C and 15°C.
Note: The input configuration must
be done before any signal
connection.
Table 4 - Input values vs. External chilled-water setpoint
Voltage
(V(dc))
3.6
4.6
5.6
6.7
7.7
RLC-SVU02F-E4
Current
(mA)
7.2
9.2
11.3
13.3
15.4
Resulting hot-water
set point
(°C)
-10
-5
0
5
10
15
Diagnostics
If there are no diagnostic messages,
the selected menu item will be
displayed continuously. If the
diagnostics key is pressed and there
are no active diagnostics, the
readout on the display will be:
NO ACTIVE DIAGNOSTICS
PRESENT
When a system malfunction occurs,
one of the following appropriate
diagnostic messages will be
displayed:
*** A machine shutdown has
occurred ! ***
A machine shutdown occurred
but has cleared “press (Next)”
*** A circuit shutdown has
occurred ! ***
When a circuit shutdown - manual
reset (CMR) or a machine shutdown
- manual reset (MMR) occurs, the
red LED to the right of the display
will flash. Otherwise this alarm LED
is de-energized.
If more than one diagnostic is
present, only the highest priority
active diagnostic will be explained
in detail. For example, if the
diagnostics occur in the following
order before the operator returns IFW, MMR, CMR - the display will
read:
*** A machine shutdown has
occurred ! ***
because the MMR has the highest
priority. However, as the operator
moves through the diagnostic menu
to the “Last diagnostic,” the
[Diagnostic description] will show
the CMR diagnostic as well as the
IFW. If the “Next” key is pressed,
the display will show all the other
active and historic diagnostics.
The active diagnostic priorities,
listed from highest to lowest are:
A circuit shutdown occurred
Machine shutdown - manual reset
(MMR)
but has cleared “press (Next)”
Machine shutdown - automatic reset
(MAR)
*** Informational warning ***
Circuit shutdown - manual reset
(CMR)
An informational warning occurred
Circuit shutdown - automatic reset
(CAR)
but has cleared “press (Next)”
Informational warning (IFW)
16
RLC-SVU02F-E4
Diagnostics
Default description
Displayed Code
Fault 87
Check External Chilled Water Setpt :
Fault 89
Check External Current Limit Setpt :
Fault 8A
Chilled Water Flow (Ent Wtr Temp) :
Fault 8E
Evaporator Entering Water Temp Sensor :
Fault 8F
Condenser Rfgt Temp Sensor - Ckt 1 :
Fault 90
Condenser Rfgt Temp Senspr - Ckt 2 :
Fault 93
Evaporator Rfgt Temp Sensor - Ckt 1 :
Fault 94
Evaporator Rfgt Temp Sensor - Ckt 2 :
Fault 9A
Condenser Entering Water Temp Sensor :
Fault 9b
Condenser Leaving Water Temp Sensor :
Fault A0
Zone Temp Sensor :
Fault A1
Outdoor Air Temp Sensor :
Fault Ab
Evaporator Leaving Wtr Temp Sensor :
Fault b5
Low Pressure Cutout - Ckt 1 :
Fault b6
Low Pressure Cutout - Ckt 2 :
Fault bA
Overload trip - Cprsr A :
Fault bb
Overload Trip - Cprsr B :
Fault bC
Overload trip - Cprsr C :
Fault bd
Overload trip - Cprsr D :
Fault bE
High Pressure Cutout - Cprsr C :
Fault bF
High Pressure Cutout - Cprsr D :
Fault C5
Low Chilled Water Temp (Unit Off) :
Fault C6
Low Chilled Water Temp (Unit On) :
Fault CA
Contactor - Cprsr A :
Fault Cb
Contactor - Cprsr B :
Fault CC
Contactor - Cprsr C :
Fault Cd
Contactor - Cprsr D :
Fault d7
Over Voltage :
Fault d8
Under Voltage :
Fault Ed
Chilled Water Flow Interlock :
Fault F5
High Pressure Cutout - Cprsr A :
Fault F6
High Pressure Cutout - Cprsr B :
Fault Fd
Emergency Stop Input :
RLC-SVU02F-E4
Type
Description
IFW
- Value out of range
IFW
- Value out of range
MMR
1) Entering water temperature < leaving WT
2) No water flow
3) Defective EVP sensor
MMR
- Defective sensor
MMR
-Defective sensor
MMR
- Defective sensor
MMR
- Defective sensor
MMR
- Defective sensor
IFW
- Defective sensor
IFW
- Defective sensor
IFW
- Defective sensor
IFW
- Defective sensor
MMR
- Defective sensor
CMR
- LP pressure switch open
CMR
- LP pressure switch open
CMR
- Current exceeded
CMR
- Current exceeded
CMR
- Current exceeded
CMR
- Current exceeded
CMR
- HP too high
CMR
- HP too high
IFW
- Antifreeze protection
MAR
- Antifreeze protection
MMR
- Welded compressor contactor
MMR
- Welded compressor contactor
MMR -
Welded compressor contactor
MMR
- Welded compressor contactor
MAR
- Voltage 10% > nominal
MAR
- Voltage 10% < nominal
MAR
- Flow switch open more than 6 sec.
MMR
- HP too high
MMR
- HP too high
MMR
- Emergency stop input open
17
Diagnostics
Default description
Displayed Code
Fault 180
Starter Transition - Cprsr A :
Type
Description
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 181
Starter Transition - Cprsr B :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 182
Starter Transition - Cprsr C :
CMR
1) Transition proof signal not received
2) Proof input shunted
Fault 183
Starter Transition - Cprsr D :
CMR
1) Transition proof signal not received
2) Proof input shunted
CMR
- Phase reversed
CMR
- Phase reversed
CMR
- Phase reversed
CMR
- Phase reversed
CMR
- Superheat < 1°C during more than 1333°C x sec
CMR
CMR
- Superheat < 1°C during more than 1333°C x sec
- Refrigerant temperature < Setpoint during more than
30°C x sec
- Refrigerant temperature < Setpoint during more than
30°C x sec
CMR
- Oil flow switch open during more than 20 sec
CMR
- Oil flow switch open during more than 20 sec
CMR
- Oil flow switch open during more than 20 sec
CMR
- Oil flow switch open during more than 20 sec
CMR
- Loss of 1 or more phases
CMR
- Loss of 1 or more phases
CMR
- Loss of 1 or more phases
CMR
- Loss of 1 or more phases
CAR
- Loss of all three phases in operation
Fault 184
Phase Reversal - Cprsr A :
Fault 185 :
Phase reversal - Cprsr B
Fault 186
Phase reversal - Cprsr C :
Fault 187
Phase reversal - Cprsr D :
Fault 190
Low Superheat - Ckt 1 :
Fault 191
Low Superheat - Ckt 2 :
Fault 194
Low Evap Rfgt Temp. - Ckt 1 :
Fault 195
Low Evap Rfgt Temp. - Ckt 2 :
Fault 198
Low Oil Flow - Cprsr A :
Fault 199
Low Oil Flow - Cprsr B :
Fault 19A
low Oil Flow - Cprsr C :
Fault 19b
Low Oil Flow - Cprsr D :
Fault 19C
Phase Loss - Cprsr A :
Fault 19d
Phase Loss - Cprsr B :
Fault 19E
Phase Loss - Cprsr C :
Fault 19F
Phase Loss - Cprsr D :
Fault 1A0
Power Loss - Cprsr A :
Fault 1A1
Power Loss - Cprsr B :
Fault 1A2
Power Loss - Cprsr C :
Fault 1A3
Power Loss - Cprsr D :
Fault 1A4
Tracer Communication Loss :
Fault 1A5
Oil Flow Control - Cprsr A :
Fault 1A6
Oil Flow Control - Cprsr B :
Fault 1A7
Oil Flow Control - Cprsr C :
Fault 1A8
Oil Flow Control - Cprsr D :
Fault 1A9
EXV Elec Drtive Ckt - Rfgt Ckt 1 :
18
CMR
CAR -
Loss of all three phases in operation
CAR
- Loss of all three phases in operation
CAR
- Loss of all three phases in operation
IFW
- Loss of external information
CMR
- Problem on oil circuit
CMR
- Problem on oil circuit
CMR
- Problem on oil circuit
CMR
- Problem on oil circuit
CMR
1)
2)
3)
4)
EXV wiring
Defective UCM
Defective EXV
Defective EXV relay
RLC-SVU02F-E4
Diagnostics
Default description
Displayed Code
Fault 1AA
EXV Elec Drtive Ckt - Rfgt Ckt 2 :
Fault 1Ad
Memory Error Type I :
Fault 1AE
Low Differential Pressure - Ckt 1 :
Fault 1AF
Low Differential pressure - Ckt 2 :
Fault 1b2
Severe Phase Unbalance - Cprsr A :
Fault 1b3
Severe Phase Unbalance - Cprsr B :
Fault 1b4
Severe Phase Unbalance - Cprsr C :
Fault 1b5
Severe Phase Unbalance - Cprsr D :
Fault 1b6
Compressor Overload Setting - Cprsr A :
Fault 1b7
Compressor Overload Setting - Cprsr B :
Fault 1b8
Compressor Overload Setting - Cprsr C :
Fault 1b9
Compressor Overload Setting - Cprsr D :
Fault 1bA
Phase Unbalance - Cprsr A :
Fault 1bb
Phase Unbalance - Cprsr B :
Fault 1bC
Phase Unbalance - Cprsr C :
Fault 1bd
Phase Unbalance - Cprsr D :
Fault 1bE
Winding Temp - Cprsr A :
Fault 1bF
Winding Temp - Cprsr B :
Fault 1C0
Winding Temp - Cprsr C :
Fault 1C1
Winding Temp - Cprsr D :
Fault 1C6
High Differential Pressure - Ckt 1 :
Fault 1C7
High Differential Pressure - Ckt 2 :
Fault 1d1
Memory Error Type II :
Fault 1d2
Memory Error Type III :
Fault 1d3
Cprsr Suction Temp Sensor - Ckt 1 :
Fault 1d4
Cprsr Suction Temp Sensor - Ckt 2 :
Fault 1d7
Phase Reversal Prot Lost - Cprsr A :
Fault 1d8
Phase Reversal Prot Lost - Cprsr B :
Fault 1d9
Phase Reversal Prot Lost - Cprsr C :
Fault 1dA
Phase Reversal Prot Lost - Cprsr D :
Fault 1db
Slaved EXV Elec Drive Ckt - Rfgt Ckt 1 :
Fault 1dC
Slaved EXV Elec Drive Ckt - Rfgt Ckt 2 :
Fault 1dd
High Oil Temp - Cprsr A :
RLC-SVU02F-E4
Type
Description
CMR
IFW
1) EXV wiring
2) Defective UCM
3) Defective EXV
4) Defective EXV relay
- NOVRAM problem, unit is placed on default
setting operating
CMR
- Delta P< 2,8bar during more than 2 min.
CMR
CMR
- Delta P< 2,8bar during more than 2 min.
- Phase imbalance >30%, check current transformer
and unit power supply
- Phase imbalance >30%, check current transformer
and unit power supply
- Phase imbalance >30%, check current transformer
and unit power supply
- Phase imbalance >30%, check current transformer
and unit power supply
IFW
- Check setting of compressor overload
IFW
- Check setting of compressor overload
IFW
- Check setting of compressor overload
IFW
- Check setting of compressor overload
CMR
- Phase imbalance >15%
CMR
- Phase imbalance >15%
CMR
- Phase imbalance >15%
CMR
- Phase imbalance >15%
CMR
- Winding temperature > 105°C
CMR
- Winding temperature > 105°C
CMR
- Winding temperature > 105°C
CMR
- Winding temperature > 105°C
CMR
- LB/HP pressure differential > 24,5 bar
CMR
- LB/HP pressure differential > 24,5 bar
IFW
- RAM error
IFW
- RAM error
CMR
- Defective sensor
CMR
- Defective sensor
CMR
- Phase reversal protection not operative
CMR
- Phase reversal protection not operative
CMR
- Phase reversal protection not operative
CMR
- Phase reversal protection not operative
CMR
- EXV electric drive defective
CMR
- EXV electric drive defective
CMR
- Oil temperature > 77°C
CMR
CMR
CMR
19
Diagnostics
Default description
Displayed Code
Fault 1dE
High Oil Temp - Cprsr B :
Fault 1dF
High Oil Temp - Cprsr C :
Fault 1E0
High Oil Temp - Cprsr D :
Fault 1E1
Oil System Fault - Cprsr A :
Fault 1E2
Oil System Fault - Cprsr B :
Fault 1E3
Oil System Fault - Cprsr C :
Fault 1E4
Oil System Fault - Cprsr D :
Fault 1E5
Entering Oil Temp Sensor - Cprsr A :
Fault 1E6
Entering Oil Temp Sensor - Cprsr B :
Fault 1E7
Entering Oil Temp Sensor - Cprsr C :
Fault 1E8
Entering Oil Temp Sensor - Cprsr D :
Fault 2A1
Cond Fan Vari Speed Drive Fault - Ckt 1 :
Fault 2A2
Cond Fan Vari Speed Drive Fault - Ckt 2 :
Type
Description
CMR
- Oil temperature > 77°C
CMR
- Oil temperature > 77°C
CMR
CMR
- Oil temperature > 77°C
- Oil temperature < condenser
during more than 30 min
- Oil temperature < condenser
during more than 30 min
- Oil temperature < condenser
during more than 30 min
- Oil temperature < condenser
during more than 30 min
CMR
- Defective sensor
CMR
- Defective sensor
CMR
- Defective sensor
CMR
- Defective sensor
IFW
- Defective fan variator speed after 5 attemps
IFW
- Defective fan variator speed after 5 attemps
CMR
CMR
CMR
saturated temperature
saturated temperature
saturated temperature
saturated temperature
Note :
MMR : Machine shutdown manual reset.
MAR : Machine shutdown automatic reset.
CMR : Circuit shutdown manual reset.
CAR : Circuit shutdown automatic reset.
IFW : Informational warning.
20
RLC-SVU02F-E4
Diagnostics
Communication Failures
Displayed Code
Fault 410
Fault 412
Fault 413
Fault 414
Fault 415
Fault 416
Fault 417
Fault 418
Fault 431
Fault 434
Fault 435
Fault 436
Fault 437
Fault 441
Fault 443
Fault 445
Fault 451
Fault 453
Fault 454
Fault 461
Fault 463
Fault 467
Fault 471
Fault 473
Fault 476
Fault 481
Fault 483
Fault 484
Fault 485
Fault 486
Fault 487
RLC-SVU02F-E4
Description
Loss of Local Display Panel Comm
Chiller Mod to Option Mod Comm Failure
Chiller Mod to EXV Mod Comm Failure
Chiller Mod to Cprsr A Mod Comm Failure
Chiller Mod to Cprsr B Mod Comm Failure
Chiller Mod Cprsr C Mod Comm Failure
Chiller Mod to Cprsr D Mod Comm Failure
Chiller Mod to Slv EXV Mod Comm Failure
EXV Mod to Chiller Mod Comm Failure
EXV Mod to Cprsr A Mod Comm Failure
EXV Mod to Cprsr B Mod Comm Failure
EXV Mod to Cprsr C Mod Comm Failure
EXV Mod to Cprsr D Mod Comm Failure
Cprsr A Mod to Chiller Mod Comm Failure
Cprsr A Mod to EXV Mod Comm Failure
Cprsr A Mod to Cprsr B Mod Comm Failure
Cprsr B Mod to chiller Mod Comm Failure
Cprsr B Mod to EXV Mod Comm Failure
Cprsr B Mod to Cprsr A Mod Comm Failure
Cprsr C Mod to Chiller Mod Comm Failure
Cprsr C Mod to EXV Mod Comm Failure
Cprsr C Mod to Cprsr D Mod Comm Failure
Cprsr D Mod to Chiller Mod Comm Failure
Cprsr D Mod to EXV Mod Comm Failure
Cprsr D Mod to Cprsr C Mod Comm Failure
Slv EXV Mod to Chiller Mod Comm Failure
Slv EXV Mod to EXV Mod Comm Failure
Slv EXV Mod to Cprsr A Mod Comm Failure
Slv EXV Mod to Cprsr B Mod Comm Failure
Slv EXV Mod to Cprsr C Mod Comm Failure
Slv EXV Mod to Cprsr D Mod Comm Failure
21
Controller for hydraulic module/
free cooling / heat recovery /
RTWB heat pump applications
The aim of this section is to list available screens on the additional
controller used to control Free Cooling /Heat Recovery application (version
1.0) and hydraulic modules. The built-in control terminal features:
• An LCD display (1), 4 lines x 20 characters with back lighting
• 6 buttons (2) to (7)
User interface
1
2
5
3
4
Prg
Esc
6
7
2 = Alarm button: Used for displaying or manually resetting the alarms.
The red LED lights up, when at least one alarm has been detected.
3 = Program button: Allows the various operating parameters to be set
(safety parameters, thresholds).
4 = Escape button: Allows the return to default display
5, 6 = Downward and Upward arrows: Allow management of currently
displayed screen and setting of values of control parameters
7 = Validation button Allows to move from line to line in the currently
displayed screen and to confirm the set data.
Note: In addition to the mask definition, the setting range (within
parentheses or bold for discrete data) and the default value (underlined) of
each parameter are indicated.
22
RLC-SVU02F-E4
Hydraulic module control
Control logic
Turning the control on
When switching on, all the outputs
will be disabled.
Reaction in case of failure
• Failure on entering water
temperature sensor (EWT):
A failure on this sensor (value out
of range) will disable the return
water temperature control during
the freeze protection by pump
activation.
• Failure on ambient Air temperature
sensor (OAT):
A failure on this sensor (Value out
of range) will turn on the heater
output and enable the freeze
protection by pump activation.
• No water flow while pump is
activated (demanded) or WFP:
If the water flow input is open (no
flow) for more than 20s while
pump is demanded for cooling or
for freeze protection by pump
activation, then an automatic
latching alarm is activated. During
the 10 first seconds of this flow
alarm, the module will switch to
the backup pump to try to obtain a
water flow.
• Water flow without pump
activation (demand):
If the water flow input is closed
(flow detected) for more than 30s
without pump demand and
without manual forced activation,
then an automatic latching alarm
will be activated.
RLC-SVU02F-E4
Freeze protection resistance control
This application must control the
electric heater command to protect
the unit during low ambient
temperature when UCM-CLD
doesn't demand pump activation.
Electric Heater ON/OFF
If the ambient air temperature is
lower than the heater activation
setpoint -1°C, then the heater output
is activated. When the ambient
temperature reaches +1°C over the
setpoint, the output is deactivated.
Pump control
This application must control 2
pumps mounted in parallel on the
evaporator circuit of a RTAD unit.
• Pump start and stop
When a pump demand is sent by
the UCM-CLD module and when
the system is enabled, the control
is in charge of the activation of on
the 2 pumps (1 at a time). A
hardware safety exists on the
electrical panel not to start both
pumps at the same time.
• Automatic change-over on a pump
failure:
When a failure appears on a pump
in operation, the control will
automatically switch on the other
pump and will stop the faulty
pump.
• Automatic change-over on failure
on water flow:
When a water flow loss is detected,
the control will automatically
switch on the backup pump to try
to keep water flow in the loop. If
the alarm remains or if the second
pump is out of order, an auto
latching alarm is triggered.
• Pump change-over on pump start:
When a new demand to start a
pump appears, a pump changeover will be done on the pump to
preserve pump mechanical seals.
• Freeze protection by pump
activation:
When UCM-CLD does not require
pump activation and that ambient
temperature is lower than the
electric heater freeze protection
setpoint but over 0°C, then a
water pump is cyclically activated
(5 min ON, 10 min OFF
programmable). If the ambient
temperature is lower than 0°C,
the pump is operating
continuously. This protection may
be deactivated.
However, if the ambient air
temperature is lower than the low
ambient setpoint (as a default
-18°C), the freeze protection by
pump activation is reactivated.
In all cases, a temperature control
on the return water temperature
will limit the water temperature of
the loop. If this temperature goes
over +15°C (programmable)
during 5mn, then the pump is
stopped during 10mn
(programmable) and then will
cycle according to these timers.
23
Hydraulic module control
Module and outputs/inputs
Use of the inputs-outputs
Name
Function
Power input to the module pCOXS
(50VA mini for the module only)
EWT
OAT
Pump1_In
Pump2_In
FS_In
System
Pump_Req
Pump1_Out
Pump2_Out
Heaters
FS_Out
Yes_Alarm
Yes_Alarm
24
Entering Water Temperature
Sensor EVP
Ambient Air Temperature Sensor
Power for binary inputs 24V
Failure Pump 1
Failure Pump 2
Flow Switch Input
System ON/OFF Input
Pump Activation Demand from
the UCM-CLD
Terminal
J1 : G(24Vac) / G0
(neutral, connected to
the earth)
J2 : B1(+) / GND(0)
J2
J4
J4
J4
J4
J4
J4
:
:
:
:
:
:
:
B2(+) / GND(0)
IDC1(0)
ID1(ac) / IDC1(0)
ID2(ac) / IDC1(0)
ID3(ac) / IDC1(0)
ID4(ac) / IDC1(0)
ID5(ac) / IDC1(0)
Common Relays Outputs
Pump 1 Output
Pump 2 Output
Electric Heaters Output
Common Relays Outputs
Flow Switch Output to the UCM-CLD
Customer Information Output
Common Relays Outputs
Customer information
J9 : C1
J9 : N01(ac) / C1
J9 : N02(ac) / C1
J9 : N03(ac) / C1
J10 : C4
J10 : N04(ac) / C4
J11 : N05(ac) / C5
J11: C5
Customer Information Output
J11 : NC5(ac) / C5
RLC-SVU02F-E4
Hydraulic module control
Hydraulic module option
Permanent display
Access to this mask using the Esc key from any mask. The program will
return automatically into it after 5 min.
1
2
3
4
= Application name and version number
= Current date and time
= Ambient Air temperature
= Unit status:
"Pump 1 Running"
"Pump 2 Running"
"No Pump Request"
"Pump 1 OVD"
"Pump 2 OVD"
"System OFF"
"WFP Active"
"Alarm"
Pump 1 is running
Pump 2 is running
No pump request sent by the UCM-CLD
Manual Override on pump 1
Manual Override on pump 2
System is OFF
Winter Freeze Protection by pump is active
An Alarm is present
Access to sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
1
2
3
4
RLC-SVU02F-E4
=
=
=
=
Data display menu
Settings menu
Clock menu
Unit configuration menu
25
Hydraulic module control
Data display menu
The following mask will be accessed using the Up and Down keys
Analog Inputs
Return Wat T
Outside Air T
1 = Customer return water temperature
2 = Ambient air temperature
Digital Inputs
Pump 1 Status:
Normal
Pump 2 Status:
Normal
Water flow:
Yes
Syst: Yes
5 Pump In: Yes
1
2
3
4
5
= Pump 1 (Failed, Normal)
= Pump 2 (Failed, Normal)
= Water Flow (No, Yes)
= System Validation (No, Yes)
= Pump request (No,Yes)
Digital Outputs
Pump 1 : Yes
Heaters : No
FS_Out : Yes
5 Alarm
: No
1
2
3
4
5
Pump 2 : No
= Pump 1 Output (No, Yes)
= Pump 2 Output (No, Yes)
= Heaters Output (No, Yes)
= Flow Switch Output (No,Yes)
= Alarm Output (No, Yes)
Counters
Pump 1 : 000000 hrs
Pump 2 : 000000 hrs
1 = Pump 1 Running hours
2 = Pump 2 Running hours
26
RLC-SVU02F-E4
Hydraulic module control
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
1 = Access via password, 0000 to 9999
User Settings
1 = Pumps Rotation (No, Yes)
Clock Menu
1 = Access via password, 0000 to 9999
Clock Settings
1 = Weekday (Mon, Tue, Wed, Thu, Fri, Sat or Sun)
2 = Time setting
3 = Date setting (dd/mm/yy)
RLC-SVU02F-E4
27
Hydraulic module control
Alarms Messages - Hydraulic module application
28
Alarm Screen
History Events
Record
Reset Type
Comments
Description
No Alarm
No Alarm
-
none
See Application
status on Main
display
Alarm
EWT Sensor
Faulty EWT
Sensor
Auto
No control on
EWT during WFP
Faulty sensor, out of
range -38..+70°C
during +30s
Alarm
OAT Sensor
Faulty OAT
Sensor
Auto
Heaters ON
WFP activation
Faulty sensor, out of
range -38..+70°C
during +30s
Alarm
Pump 1
Faulty Pump 1
Manual
Pump 1 OFF
Failure on pump 1
Alarm
Pump 2
Faulty Pump 2
Manual
Pump 2 OFF
Failure on pump 2
Alarm
Flow Switch On
But no pump
required
Water Flow w/o
Pump
Auto
Could be due to
a faulty water
flow switch
Water Flow is
established but there
is no pump required
Alarm
No Water Flow
No Water Flow
Auto
No water flow
Water Flow is not
established within
20s
RLC-SVU02F-E4
Free Cooling Application
Free Cooling Application
Permanent display
Access to this mask using the Esc key from any mask. The program will
return automatically into it after 5 min.
1
2
3
4
= Application name and version number
= Current date and time
= Leaving water temperature
= Unit status:
"Chiller Low Ambient"
"FC Low Ambient"
"Chiller"
"Chiller, wait => FC"
"Chiller => FC"
"Free Cooling"
"FC, wait => Chiller"
"FC => Chiller"
"Chiller, PLC Failure"
"PLC Failure"
"Stopped"
Chiller stopped by low ambient temperature
Free Cooling stopped by low ambient temperature
Chiller is running
Chiller is switching to Free Cooling
Free Cooling is switching to Chiller
Free Cooling is running
Free Cooling is waiting for the end of timer to switch to Chiller
Chiller is waiting for the end of timer to switch to Free Cooling
Chiller is enabled, PLC (Programmable Logic Controller) is in alarm mode
Chiller is not enabled, PLC is in alarm mode
System is OFF
Access to Sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
1
2
3
4
RLC-SVU02F-E4
=
=
=
=
Data display menu
Settings menu
Clock menu
Unit configuration menu
29
Free Cooling Application
Data display menu
The following mask will be accessed using the Up and Down keys
Analog Inputs
1
2
3
4
= Entering water temperature
= Leaving water temperature
= Ambient air temperature
= Active chilled water setpoint
Setpoint Source
1 = Setpoint Source (Front Panel, External, Air Reset, Return Water Reset)
2 = Active chilled water setpoint
"Front Panel"
"External"
"Air Reset"
"Return Water Reset"
30
Setpoints come from local source
Setpoints come from external source
Setpoints adjusted according to readings
from air temperature sensor
Setpoints adjusted according to readings
from return water temperature sensor
RLC-SVU02F-E4
Free Cooling Application
Digital Inputs
1
2
3
4
=
=
=
=
System (Off, On); NNSB (Off, On)
UCM Pump (Not Req., Required)
Flow Switch (OK, Not OK)
Free Cooling (Disable, Enable)
Digital Outputs
1
2
3
4
5
6
7
RLC-SVU02F-E4
=
=
=
=
=
=
=
Fans 1, 2 and 3 (Off, On)
Fan Speed (Low, High)
FC status (Off, On)
UCM enabled (Off, On)
System Pump (Off, On)
Flow Switch (Off, On)
PRG Relay (Off, On)
31
Free Cooling Application
3 Way Valve IO
Speed
Low
Relay
Off
1 = 3WV Input Position (Value and Input Analog Voltage)
2 = 3WV Output Position (Value and Output Analog Voltage)
Chilled Water Setpoint IO
1 = External Chilled Water Setpoint (Value and Input Analog Voltage)
2 = Adjusted Water Setpoint Output (Value and Output Analog Voltage)
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
1 = Access via password, 0000 to 9999
User Settings
1
2
3
4
32
=
=
=
=
Leaving Water Temp SP (-17.8°C (or LAW+2.8°C)..15°C (or HCWSP): 7°C)
Chiller Delta Temp SP (2°C..10°C: 5°C)
Pump OFF Delay Timer (0..30min: 1min)
Programmable Relay Function (PLC ON, PLC Fault, FC ON)
RLC-SVU02F-E4
Free Cooling Application
Chilled Water Reset CWR
1 = Reset Type (None, External, Based on OAT, Based on Ret Wat)
"None"
"External"
"Based on OAT"
"Based on Ret Wat"
No reset has been requested
Reset comes from external source
Reset is based on outdoor air temperature
Reset is based on return water temperature
2 = Ratio (-80%..120%: 25%)
3 = Start Temperature (-15.5°C..54.4°C: 10°C)
4 = Maximum CWR (0°C..11.1°C: 2.7°C)
Clock Menu
1 = Access via password, 0000 to 9999
Clock Settings
1 = Weekday (Mon, Tue, Wed, Thu, Fri, Sat or Sun)
2 = Time setting
3 = Date setting (dd/mm/yy)
RLC-SVU02F-E4
33
Free Cooling Application
Alarm Messages - Free Cooling Application
Alarm Screen
History Events
Record
Reset
Type
Unit status
Description
No Alarm
No Alarm
-
Free Cooling ON
Chiller ON
See unit status on
Main display
Alarm LWT Sensor
Faulty LWT
Sensor
Auto
Free Cooling OFF
Chiller ON
Faulty sensor,
out of range
-38..+ 60°C during + 30s
Alarm EWT Sensor
Faulty EWT
Sensor
Auto
Free Cooling OFF
Chiller ON
Faulty sensor,
out of range
-38..+ 60°C during + 30s
Alarm OAT Sensor
Faulty OAT
Sensor
Auto
Free Cooling OFF
Chiller ON
Faulty sensor,
out of range
-38..+ 60°C during + 30s
Alarm Flow Switch
Flow Switch
Auto
Free Cooling OFF
Chiller OFF
No water flow during 6s
Low LWT or EWT
Auto
Free Cooling OFF
Chiller OFF
LWT or EWT
below LAW for
more than 16.6°C*s
Alarm
Int (LWT-EWT)
>120°C*s
LWT > EWT
during +120s
Manual
Free Cooling OFF
Chiller OFF
LWT-EWT
above 120°C*s
Alarm
3WV Position
Diff In vs Out > 10%
3WV Delta
In vs Out
Manual
Free Cooling OFF
Chiller OFF
Diff between 3WV
In and Out > 10% for
more than 2*Valve
Stroke Time
Alarm
Low LWT or EWT
34
RLC-SVU02F-E4
Heat Recovery Application
Permanent display
Access to this mask using the Esc key from any mask. The program will
return automatically into it after 5min.
HR Application
00/00/00
Hot Wat Temp:
Cool&HR Mode
1
2
3
4
= Application name and version number
= Current date and time
= Hot water temperature
= Unit status:
"Cool Mode Running"
"Cool&HR Mode Running"
"Cool&HR Mode Stopped"
"Cool Mode Stopped"
"HR is Starting"
"HR is Stopping"
"Alarm"
RLC-SVU02F-E4
V1.0
00:00
00.0°C
Running
Chiller is running in Cool Mode
Chiller is running in Cool and Heat Recovery Mode
Chiller is stopped in Cool and Heat Recovery Mode
Chiller is stopped in Cool Mode
Heat Recovery is starting
Heat Recovery is stopping
Chiller is stopped by Alarm
35
Heat Recovery Application
Access to Sub-menus
Access to this mask using the Prg key. The sub-menu will be selected using
the Up and Down keys and selected using the Enter button.
1
2
3
4
=
=
=
=
Data display menu
Settings menu
Clock menu
Unit configuration menu
Data display menu
The following mask will be accessed using the Up and Down keys
Analog Inputs
Hot Water Temp:
C1 pressure:
C2 pressure:
Active HWSP:
1
2
3
4
36
00.0°C
00.0b
00.0b
00.0°C
= Customer return hot water temperature
= Circuit 1 pressure
= Circuit 2 pressure
= Active hot water setpoint
RLC-SVU02F-E4
Heat Recovery Application
Digital Inputs
Circuit 1:
Circuit 2:
HR Status:
NNSB:
1
2
3
4
=
=
=
=
Running
Running
Enabled
Off
Circuit 1 (Stopped, Running)
Circuit 2 (Stopped, Running)
Heat Recovery Status (Disabled, Enabled)
Night Noise Set Back (Off, On)
Digital Outputs
1
FAN1:
Off
FAN2:
Off
PRG Relay: On
2
Off
Off
3
Off
Off
CKT
On
On
1 = Circuit 1 Fans stages (Off, On)
2 = Circuit 2 Fans stages (Off, On)
3 = Programmable Relay (Off, On)
Circuit 1 Enable Output (Off, On)
Circuit 2 Enable Output (Off, On)
Analog Outputs
3WV:
DV1:
DV2:
000.0% (00.0V)
000.0% (00.0V)
000.0% (00.0V)
1 = 3-Way valve Output (Value and Output Analog Voltage)
2 = C1 Speed Inverter Output (Value and Output Analog Voltage)
3 = C2 Speed Inverter Output (Value and Output Analog Voltage)
RLC-SVU02F-E4
37
Heat Recovery Application
Settings Menu
Access to each field within a mask using the Enter key. Change the field
value using the Up and Down keys and confirmation by Enter.
1 = Access via password, 0000 to 9999
User Settings
Hot Water SP:
50°C
PRG Relay:
HR ON
1 = Hot Water Temp SP (40..60°C: 50°C)
2 = Programmable Relay Function (PLC ON, PLC Fault, HR ON)
Clock Menu
1 = Access via password, 0000 to 9999
Clock Settings
1 = Weekday (Mon, Tue, Wed, Thu, Fri, Sat or Sun)
2 = Time setting
3 = Date setting (dd/mm/yy)
38
RLC-SVU02F-E4
Heat Recovery Application
Alarms Messages - Heat Recovery Application
RLC-SVU02F-E4
Alarm Screen
History Events
Record
Reset Type
Unit status
Description
No Alarm
No Alarm
-
Heat
Recovery ON
Chiller ON
See unit status on
Main display
Alarm HWT
Sensor
Faulty HWT
Sensor
Auto
Heat
Recovery OFF
Chiller ON
Faulty sensor, out of range
-38..+ 85°C during + 30s
Alarm PRS1
Sensor
Faulty PRS1
Sensor
Auto
Heat
Recovery ON
Circuit 1 OFF
Faulty sensor, out of range
-0.5..+ 30 bars during + 15s
Alarm PRS2
Sensor
Faulty PRS2
Sensor
Auto
Heat
Recovery ON
Circuit 2 OFF
Faulty sensor, out of range
-0.5..+ 30 bars during + 15s
39
RTWB Heat Pump Application
Permanent display
Access to this mask using the "Esc" key from any mask. The program will
return automatically into it after 5 min.
1
2
3
4
= Application name and version number
= Current date and time
= Condenser Leaving Water Temperature
= Unit status:
none
no alarm
"Alarm"
An Alarm is present
Access to sub-menus
Access to this mask using the "Prg" key
1
2
3
4
=
=
=
=
Data display menu
Settings menu
Clock menu
Unit configuration menu
The sub-menu will be selected using the Up and Down keys and selected
using the Enter button.
Data display menu
The following mask will be accessed using the Up and Down keys
Binary and Analog Inputs
1
2
3
4
40
=
=
=
=
Condenser Leaving Water Temperature
ON/OFF Unit input (Stop, Auto)
External Mode input (Heat, Cool): displayed if Ext Ctrl enabled
Pump Request input (No pump, Pump Req)
RLC-SVU02F-E4
RTWB Heat Pump Application
Binary Outputs
1
2
3
4
= Active Mode (Heating, Cooling)
= Unit Status (Stopped, Running)
= CDS Pump Status (Stopped, Running)
= Sensor Alarm (Normal, Alarm)
Active Setpoints
1 = Active Mode (Heating, Cooling)
2 = Heating Setpoint (displayed if Heating Mode)
3 = Cooling Setpoint (displayed if Cooling Mode)
Note: "Ext" is displayed according to the External Control setting (No,
Partial (Mode only), Full (Mode + SP))
RLC-SVU02F-E4
41
RTWB Heat Pump Application
Settings Menu
Access to each field within a mask using the "Enter" key. Change the field
value using the Up and Down keys and confirmation by "Enter".
1 = (0000 to 9999)
User Settings 1
1
2
3
4
=
=
=
=
Front Panel Heat Setpoint (25.0°C..60.0°C: 35.0°C)
Front Panel Cool Setpoint (-12.0°C..18.0°C: 6.0°C)
Front Panel Heat/Cool switch (Heat, Cool)
External Control (No, Partial, Full)
User Settings 2
1 = External Heat Setpoint Input Type (0-1V, 4-20mA)
2 = External Cool Setpoint Input Type (0-1V, 4-20mA)
Note: This screen is displayed if the External Control setting is "Full" (Mode
+ SP)
42
RLC-SVU02F-E4
RTWB Heat Pump Application
Clock Menu
1 = Access via password, 0000 to 9999
Clock Settings
1 = Weekday (Mon, Tue, Wed, Thu, Fri, Sat or Sun)
2 = Time setting
3 = Date setting (dd/mm/yy)
Alarms Messages - RTWB Heat pump application
Alarm
Screen
RLC-SVU02F-E4
History
Reset
Events Record Type Comments
No Alarm
No Alarm
-
Alarm CDS
LWT Sensor
Faulty CDS
LWT Sensor
Auto
none
Description
See Application status on Main
display
Chiller
stopped (in Faulty sensor, out of range
Heating -38..+70°C during +60s
mode only)
43
Literature Order Number
RLC-SVU02F-E4
Date
0209
Supersedes
RLC-SVU02E-E4_0508
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.
www.trane.com
For more information, contact your local
sales office or e-mail us at [email protected]
Trane bvba
Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement