Bulletin No. T&P16-E Drawing No. LP0486 Released 12/02 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion-controls.com MODELS T16 & P16 - TEMPERATURE/PROCESS CONTROLLERS ! PID CONTROL WITH REDUCED OVERSHOOT ! T16 ACCEPTS TC AND RTD ! P16 ACCEPTS 0-10 V AND 0/4-20 mA SIGNALS ! ON DEMAND AUTO-TUNING OF PID SETTINGS ! DC ANALOG OUTPUT (OPTIONAL) ! USER PROGRAMMABLE FUNCTION BUTTON ! PC OR FRONT PANEL PROGRAMMING ! PC CONFIGURABLE WITH TP16KIT UL Recognized Component, File #E156876 y x EMC COMPLIANT NEMA 4X IP65 PARAMETER LOCKOUT FRONT PANEL PROGRAMMABLE PROGRAMMING SOFTWARE ALARMS ANALOG OUTPUT PC CONFIGURABLE Product Features FAX/WEB DOC # 05019 output response. The alarms can be programmed for Automatic or Latching operation. A selectable standby feature suppresses the alarm during power-up until the temperature stabilizes outside the alarm region. GENERAL DESCRIPTION The Model T16 Controller accepts signals from a variety of temperature sensors (thermocouple or RTD), while the Model P16 Controller accepts either a 0 to 10 VDC or 0/4 to 20 mA DC input signal. Both controllers can provide an accurate output control signal (time proportional or DC Analog Output) to maintain a process at a setpoint value. Dual 4-digit displays allow viewing of the process/temperature and setpoint simultaneously. Front panel indicators inform the operator of the controller and output status. The comprehensive programming allows these controllers to meet a wide variety of application requirements. ANALOG OUTPUT OPTION The optional DC Analog Output (10 V or 20 mA) can be configured and scaled for control or re-transmission purposes. The programmable output update time reduces valve or actuator activity. PC PROGRAMMING KIT MAIN CONTROL The optional TP16KIT contains a programming module with a 9 pin RS232 connector, cable and Windows® based configuration software. The software allows downloading, uploading and storage of T16 and P16 program files. All controllers have a communications port that allows configuration by PC even without controller power connected. Controller calibration is also possible using the software when the proper calibration equipment and controller power is connected. The controller operates in the PID Control Mode for both heating and cooling, with on-demand auto-tune, that establishes the tuning constants. The PID tuning constants may be finetuned through the front panel and then locked out from further modification. The controller employs a unique overshoot suppression feature, that allows the quickest response without excessive overshoot. Switching to Manual Mode provides the operator direct control of the output. The controller may also be programmed to operate in On/Off mode with adjustable hysteresis. CONSTRUCTION The controller is constructed of a lightweight, high impact, black plastic textured case and bezel with a clear display window. The front panel meets NEMA 4X/IP65 specifications when properly installed. In applications that do not require protection to NEMA 4X, multiple controllers can be stacked horizontally or vertically. Modern surface-mount technology, extensive testing, plus high immunity to noise interference makes the controller extremely reliable in industrial environments. ALARMS Optional alarm(s) can be configured independently for absolute high or low acting with balanced or unbalanced hysteresis. They can also be configured for deviation and band alarm. In these modes, the alarm trigger values track the setpoint value. Adjustable alarm trip delays can be used for delaying DIMENSIONS In inches (mm) PANEL CUT-OUT 1 Product Features Continued SAFETY SUMMARY All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. An independent and redundant temperature limit indicator with alarm outputs is strongly recommended. CAUTION: Read complete instructions prior to installation and operation of the unit. CAUTION: Risk of electric shock. General Specifications 1. DISPLAY: 2 Line by 4-digit, LCD negative image transmissive with backlighting. Top (Process) Display: 0.3" (7.6 mm) high digits with red backlighting. Bottom (Parameter) Display: 0.2" (5.1 mm) high digits with green backlighting. 2. ANNUNCIATORS: Status Annunciators: O1 - Main control output is active. O2 - Cooling output is active (when Alarm 2 is used for cooling). A1 - Alarm 1 output is active. A2 - Alarm 2 output is active. °F, °C - Temperature units. %PW - Output power percentage is shown in Bottom display. MAN - Controller is in Manual Mode. R - Ramping Setpoint indicator. % - Percent indicator (P16 models only). Display Messages: !"#"#$ - Measurement exceeds + sensor range !%#%#$ - Measurement exceeds - sensor range !"&'($ - Open sensor is detected (T16 only) !)*+,$ - Shorted sensor is detected (RTD only) !)'()$ - Measurement exceeds controller limits (P16 only) !----$ - Display value exceeds + display range !.---$ - Display value exceeds - display range 3. POWER: Line Voltage Models: 85 to 250 VAC, 50/60 Hz, 8 VA Low Voltage Models: DC Power: 18 to 36 VDC, 4 W AC Power: 24 VAC, ±10%, 50/60 Hz, 7 VA 4. CONTROLS: Three rubber push buttons for modification and setup of controller parameters. One additional button (F1) for user programmable function. One external user input (models with alarms) for parameter lockout or other user programmable functions. 5. MEMORY: Nonvolatile E2PROM retains all programmable parameters. 6. ISOLATION LEVEL: AC power with respect to all other I/O: 250 V working (2300 V for 1 minute) Sensor input to analog output: 50 V working (500 V for 1 minute) Relay contacts to all other I/O: 300 V working (2300 V for 1 minute) DC power with respect to sensor input and analog output: 50 V working (500 V for 1 minute) 7. CERTIFICATIONS AND COMPLIANCES: SAFETY UL Recognized Component, File #E156876, UL873, CSA 22.2 No. 24 Recognized to US and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc. Type 4X Enclosure rating (Face only), UL50 IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part I IP65 Enclosure rating (Face only), IEC 529 ELECTROMAGNETIC COMPATIBILITY Immunity to EN 50082-2 Electrostatic discharge EN 61000-4-2 Level 2; 4 kV contact Level 3; 8 kV air Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1 80 MHz - 1 GHz Fast transients (burst) EN 61000-4-4 Level 4; 2 kV I/O Level 3; 2 kV power RF conducted interference EN 61000-4-6 Level 3; 10 V/rms 2 150 KHz - 80 MHz Emissions to EN 50081-2 RF interference EN 55011 Enclosure class A Power mains class A Notes: 1 Self-recoverable loss of performance during EMI disturbance at 10 V/m: Measurement input signal may deviate during EMI disturbance. For operation without loss of performance: Install one ferrite core one turn, RLC #FCOR0000 or equivalent, to I/O cables at unit. 2 Self-recoverable loss of performance during EMI disturbance at 10 Vrms: Process and analog output signal may deviate during EMI disturbance. For operation without loss of performance: Install one ferrite core one turn, RLC #FCOR0000 or equivalent, to I/O cables and power cable at unit. Refer to the EMC Installation Guidelines section of this bulletin for additional information. 8. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: 0 to 50°C Storage Temperature Range: -40 to 80°C Operating and Storage Humidity: 85% max relative humidity (non-condensing) from 0°C to 50°C Altitude: Up to 2000 meters 9. CONNECTION: Wire-clamping screw terminals 10. CONSTRUCTION: Black plastic alloy case and collar style panel latch. Panel latch can be installed for vertical or horizontal instrument stacking. Black plastic textured bezel with transparent display window. Controller meets NEMA 4X/IP65 requirements for indoor use when properly installed. Installation Category II, Pollution Degree 2. 11. WEIGHT: 6.3 oz (179 g) 2 Input Specifications 1. SENSOR INPUT: Sample Period: 100 msec (10Hz rate) Step Response Time: 300 msec typical, 400 msec max to within 99% of final value with step input. Failed Sensor Response: Main Control Output(s): Programmable preset output Display: “OPEN” Alarms: Upscale drive Analog Output: Upscale drive when assigned to retransmitted input. Normal Mode Rejection: >40 dB @ 50/60 Hz Common Mode Rejection: >120 dB, DC to 60 Hz Overvoltage Protection: 120 VAC @ 15 sec max 2. THERMOCOUPLE INPUTS: (T16 only) Types: T, E, J, K, R, S, B, N, C, and Linear mV Input Impedance: 20 MΩ for all types Lead Resistance Effect: 0.25 µV/Ω Cold Junction Compensation: Less than ±1°C typical (1.5°C max) error over ambient temperature range. Resolution: 1° for types R, S, B and 1° or 0.1° for all other types TYPE DISPLAY RANGE T WIRE COLOR BS 1843 -200 to +400°C -328 to +752°F (+) Blue (-) Red (+) White (-) Blue ITS-90 E -200 to +750°C -328 to +1382°F (+) Violet (-) Red (+) Brown (-) Blue ITS-90 J -200 to +760°C -328 to +1400°F (+) White (-) Red (+) Yellow (-) Blue ITS-90 K -200 to +1250°C (+) Yellow (+) Brown -328 to +2282°F (-) Red (-) Blue ITS-90 R 0 to +1768°C +32 to +3214°F No standard (+) White (-) Blue ITS-90 S 0 to +1768°C +32 to +3214°F No standard (+) White (-) Blue ITS-90 B +149 to +1820°C No +300 to +3308°F standard No standard ITS-90 N -200 to +1300°C (+) Orange (+) Orange -328 to +2372°F (-) Red (-) Blue mV -5.00 mV to 56.00 mV TYPE INPUT TYPE RANGE STANDARD 385 100 Ω platinum, Alpha = .00385 -200 to +600°C -328 to +1112°F IEC 751 392 100 Ω platinum, Alpha = .003919 -200 to +600°C -328 to +1112°F No official standard 672 120 Ω nickel, Alpha = .00672 -80 to +215°C -112 to +419°F No official standard 0.0 to 320.0 Ω N/A Ohms Linear Resistance 4. TEMPERATURE INDICATION ACCURACY: (T16 only) ± (0.3% of span, +1°C) at 23 °C ambient after 20 minute warm up. Includes NIST conformity, cold junction effect, A/D conversion errors and linearization conformity. Span Drift (maximum): 130 PPM/°C 5. SIGNAL INPUT: (P16 only) STANDARD ANSI C 0 to +2315°C W5/W6 +32 to +4199°F 3. RTD INPUTS: (T16 only) Type: 2 or 3 wire Excitation: 150 µA typical Lead Resistance: 15 Ω max per input lead Resolution: 1° or 0.1° for all types INPUT RANGE MAX ACCURACY * IMPEDANCE CONTINUOUS RESOLUTION OVERLOAD 10 VDC (-1 to 11) 0.30 % of reading +0.03V 1 MΩ 50 V 10 mV 20 mA DC (-2 to 22) 0.30 % of reading +0.04mA 10 Ω 100 mA 10 µA * Accuracies are expressed as ± percentages over 0 to 50 °C ambient range after 20 minute warm-up. 6. USER INPUT: (Only controllers with alarms have a user input terminal.) Internally pulled up to +7 VDC (100 KΩ), VIN MAX = 35 V, VIL = 0.6 V max, VIH = 1.5 V min, IOFF = 40 µA max Response Time: 120 msec max Functions: Programmable ITS-90 No standard No standard ASTM E988-96 N/A N/A N/A Output Specifications 1. CONTROL AND ALARM OUTPUTS: Relay Output: Type: Form A Contact Rating: 3 A @ 250 VAC or 30 VDC; 1/10 HP @ 120 VAC (inductive load) Life Expectancy: 100,000 cycles at max. load rating (Decreasing load and/or increasing cycle time, increases life expectancy) Logic/SSR Output (main control output only): Rating: 45 mA max @ 4 V min., 7 V nominal 2. MAIN CONTROL: Control: PID or On/Off Output: Time proportioning or DC Analog Cycle Time: Programmable Auto-Tune: When selected, sets proportional band, integral time, derivative time, and output dampening time. Also sets input filter and (if applicable) cooling gain. Probe Break Action: Programmable 3. ALARMS: (optional) 2 relay alarm outputs. Modes: None Absolute High Acting (Balanced or Unbalanced Hysteresis) Absolute Low Acting (Balanced or Unbalanced Hysteresis) Deviation High Acting Deviation Low Acting Inside Band Acting Outside Band Acting Heat (Alarm 1 on Analog Output models only) Cool (Alarm 2) Reset Action: Programmable; automatic or latched Standby Mode: Programmable; enable or disable Hysteresis: Programmable Sensor Fail Response: Upscale Annunciator: “A1” and “A2” programmable for normal or reverse acting 4. COOLING: Software selectable (overrides Alarm 2). Control: PID or On/Off Output: Time proportioning Cycle Time: Programmable Proportional Gain Adjust: Programmable Heat/Cool Deadband Overlap: Programmable 5. ANALOG DC OUTPUT: (optional) Action: Control or retransmission Update Rate: 0.1 to 250 sec OUTPUT RANGE ** ACCURACY * COMPLIANCE RESOLUTION 0 to 10 V 0.3% of FS + ½ LSD 10 kΩ min 1/8000 500 Ω max 1/8000 500 Ω max 1/6400 0 to 20 mA 4 to 20 mA 0.3% of FS + ½ LSD 0.3% of FS + ½ LSD * Accuracies are expressed as ± percentages over 0 to 50 °C ambient range after 20 minute warm-up. ** Outputs are independently jumper selectable for either 10 V or 20 mA. The output range may be field calibrated to yield approximately 5% overrange and a small underrange (negative) signal. 3 Ordering Information MODEL NO. MAIN CONTROL 2 ALARMS & USER INPUT Relay T16 PART NUMBERS 18-36 VDC/24 VAC 85 to 250 VAC — T1610010 T1610000 Relay Yes T1611110 T1611100 Logic/SSR — T1620010 T1620000 T1621100 Logic/SSR Yes T1621110 Analog Out * Yes T1641110 T1641100 Relay — P1610010 P1610000 Relay Yes P1611110 P1611100 Logic/SSR — P1620010 P1620000 Logic/SSR Yes P1621110 P1621100 Analog Out * Yes P1641110 P1641100 P16 * Analog out may be used for retransmitted signals. When using analog output for retransmitted signals, AL1 becomes main control O1, if selected for heating in the analog out models. ACCESSORIES MODEL NO. TP16 RLY DESCRIPTION PART NUMBERS Programming Kit 1 : Includes Software, Comms Module w/ 9-pin connector and cable, and 115 VAC Power Adapter TP16KIT1 Programming Kit 2 : Includes Software, Comms Module w/ 9-pin connector and cable TP16KIT2 External SSR Power Unit (for Logic/SSR models) RLY50000 Single Phase Din Rail Mount Soild State Relay RLY60000 Three Phase Din Rail Mount Soild State Relay RLY70000 BLOCK DIAGRAM *AL1 becomes main control O1, if selected for heating in the analog out models. 4 EMC INSTALLATION GUIDELINES Although this controller is designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure electromagnetic compatibility (EMC) in each application. The type of the electrical noise, source or coupling method into the controller may be different for various installations. The controller becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMC guidelines for successful installation in an industrial environment. 1. The controller should be mounted in a metal enclosure that is properly connected to protective earth. 2. Use shielded (screened) cables for all Signal and Control inputs. The shield (screen) pigtail connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness. a. Connect the shield only at the panel where the controller is mounted to earth ground (protective earth). b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is more than 1 MHz. c. Connect the shield to common of the controller and leave the other end of the shield unconnected and insulated from earth ground. 3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. 4. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components. 5. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the controller as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the controller to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for Signal and Control cables: Fair-Rite # 0443167251 (Red Lion Controls # FCOR0000) TDK # ZCAT3035-1330A Steward # 28B2029-0A0 Line Filters for input power cables: Schaffner # FN610-1/07 (Red Lion Controls # LFIL0000) Schaffner # FN670-1.8/07 Corcom # 1 VR3 Note: Reference manufacturer’s instructions when installing a line filter. 6. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible. 7. Switching of inductive loads produces high EMI. Use of snubbers across inductive loads suppresses EMI. Snubber: Red Lion Controls # SNUB0000. STEP 1 Setting The Jumpers To insure proper operation, the Analog Output jumpers must be set to the same range selected in programming Module 2-OP. The default jumper setting is for 20 mA. The default setting in Module 2-OP is 4-20 mA. To access the jumpers, insert a flat-blade screwdriver between the front panel and the side case slot. This should disengage the top and bottom front panel latches from the case grooves. Pull the front panel assembly with the controller boards out of the case. The jumpers are located inside the controller on the left board along the back top section. VIEW FROM TOP OF UNIT 5 (Analog output models only) STEP 2 INSTALLING THE CONTROLLER The T16 and P16 controllers meet NEMA 4X/IP65 requirements for indoor use to provide a watertight seal in steel panels with a minimum thickness of 0.09", or aluminum panels with a minimum thickness of 0.12". The controllers are designed to be mounted into an enclosed panel. The bezel assembly must be in place during installation of the controller. Instructions: 1. Prepare the panel cutout to the proper dimensions. 2. Remove the panel latch from the controller. Discard the cardboard sleeve. 3. Carefully remove the center section of the panel gasket and discard. Slide the panel gasket over the rear of the controller, seating it against the lip at the front of the case. 4. Insert the controller into the panel cutout. While holding the controller in place, push the panel latch over the rear of the controller, engaging the tabs of the panel latch in the farthest forward slot possible. 5. To achieve a proper seal, tighten the panel latch screws evenly until the controller is snug in the panel, torquing the screws to approximately 7 in-lb (79 N-cm). Overtightening can result in distortion of the controller, and reduce the effectiveness of the seal. Note: The installation location of the controller is important. Be sure to keep it away from heat sources (ovens, furnaces, etc.) and away from direct contact with caustic vapors, oils, steam, or any other process by-products in which exposure may affect proper operation. Multiple Controller Stacking The controller is designed to allow for close spacing of multiple controllers in applications that do not require protection to NEMA 4X. Controllers can be stacked either horizontally or vertically. For vertical stacking, install the panel latch with the screws to the sides of the controller. For horizontal stacking, the panel latch screws should be at the top and bottom of the controller. The minimum spacing from centerline to centerline of controllers is 1.96” (49.8 mm). This spacing is the same for vertical or horizontal stacking. Note: When stacking controllers, provide adequate panel ventilation to ensure that the maximum operating temperature range is not exceeded. 6 STEP 3 WIRING THE CONTROLLER WIRING CONNECTIONS All wiring connections are made to the rear screw terminals. When wiring the controller, use the numbers on the label and those embossed on the back of the case, to identify the position number with the proper function. All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power (AC or DC) supplied to the controller be protected by a fuse or circuit breaker. Strip the wire, leaving approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned with solder). Insert the wire under the clamping washer and tighten the screw until the wire is clamped tightly. CONTROLLER POWER CONNECTIONS VDC For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the controller be protected by a fuse or circuit breaker. VAC INPUT CONNECTIONS For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input common terminal. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then use a jumper. A temperature offset error will exist. The error may be compensated by programming a temperature offset. RTD and Resistance Thermocouple and Millivolt Voltage and Current CONTROL AND ALARM OUTPUT CONNECTIONS Main Control Relay Models Alarm Models Main Control Logic/SSR Models *AL1 becomes main control O1, if selected for heating in the analog out models. USER INPUT CONNECTIONS ANALOG DC OUTPUT CONNECTIONS 7 STEP 4 REVIEWING THE FRONT KEYS AND DISPLAY FRONT PANEL KEYS The Arrow keys are used to scroll through The F1 key is pressed to exit (or escape) directly to the selections/values and in the Configuration # $ parameter Loop they are used to scroll to the appropriate of the Display Loop. While in the Display Loop, the F1 ! start key can be pressed to activate its programmed function. Parameter Module. " The Loop key is pressed to advance to the next parameter, to activate a changed selection/value, and when held for three seconds, enter the Hidden Loop. STEP 5 PROGRAMMING WITHIN THE DISPLAY LOOP DISPLAY LOOP Note: Setpoint and Output Power are the only parameters visible in the Display Loop with Factory Settings. The remaining parameters can be selected for the Display Loop within Module 3 Parameter availability is model and programming dependent. DISPLAY LOOP When the " is pressed the controller advances to the next parameter in the Display Loop. Except for Setpoint and % Output Power, the bottom display alternates between the parameter name and its selection/value. The arrow keys are pressed to change the selection/value for the shown parameter. The new selection/value is activated when the " is pressed. Display Loop parameters may be locked out or hidden in Lockout Module 3. #4. Some parameters are model and programming dependent. At power up, all display segments light, and then the programmed input type and the controller’s software version will flash. Then the Temperature/Process Value is shown in the top display, and the Setpoint Value is shown in the bottom display. This is the Display Loop. If the Setpoint is hidden or locked, the Display Loop will default to Output Power. If Output Power is also hidden or locked out, the bottom display is blank. During programming, the F1 key can be pressed to return the controller to this point. (Only in the Display Loop will the F1 key perform the user /012 function programmed in Input Module 0.1(.) 8 The values shown for the displays are the factory settings. SETPOINT VALUE (SP1) * )& 6 676 INTEGRAL TIME 12,, " ! 086 .555 to 5555 T16 .555 to 5555 T16 DERIVATIVE TIME P16 -'+, " ! 36 Typically, the controller is operating with the Setpoint value in the bottom display. There is no annunciator nor parameter indication for Setpoint in the Display Loop. The parameter name alternates with the setpoint value in the Hidden Loop. The Setpoint value can be changed, activated and stored by pressing the arrow keys. This is the only parameter that can be configured as read only in the Display Loop, but read/write in the Hidden Loop. It is possible to store a second Setpoint value that can be selected in the Hidden Loop, by the F1 key or the user input. Both Setpoint values are limited by the Setpoint Low and High Limits in Input Module 0.1(. 6 to 5555 seconds per repeat Derivative time helps to stabilize the response, but too high of a derivative time, coupled with noisy signal processes, may cause the output to fluctuate too greatly, yielding poor control. Setting the time to zero disables derivative action. ALARM 1 VALUE :#.0 " ! 6 676 % OUTPUT POWER * "& 676 seconds Integral action shifts the center point position of the proportional band to eliminate error in the steady state. The higher the integral time, the slower the response. The optimal integral time is best determined during PID Tuning. If time is set to zero, the previous Integral output power value is maintained. Offset Power can be used to provide Manual Reset. P16 SETPOINT VALUE (SP2) * )& 86 876 6 to 5555 .066 to 06676 .555 to 5555 T16 P16 On models with alarms, the value for Alarm 1 can be entered here. The value is either absolute (absolute alarm types) or relative to the Setpoint value (deviation and band alarm types.) When Alarm 1 is programmed for *':, or (;2', this parameter is not available. For more details on alarms, see Alarm Module <.:#. The % Output Power is shown with the %PW annunciator. The parameter name alternates with the % Output Power value in the Hidden Loop. While the controller is in Automatic Mode, this value is read only. When the controller is placed in Manual Mode, the value can be changed, activated and stored by pressing the arrow keys. For more details on % Output Power, see Control Mode Explanations. ALARM 2 VALUE :#.8 " ! 6 676 OUTPUT POWER OFFSET "&"/ " ! 676 .066 to 06676 When the Integral Time is set to zero and the controller is in the Automatic Mode, this parameter will appear after % Output Power. It is also shown with the %PW annunciator illuminated. The power offset is used to shift the proportional band to compensate for errors in the steady state. If Integral Action is later invoked, the controller will re-calculate the internal integral value to provide “bumpless” transfer and Output Power Offset will not be necessary. .555 to 5555 T16 P16 On models with alarms, the value for Alarm 2 can be entered here. The value is either absolute (absolute alarm types) or relative to the Setpoint value (deviation and band alarm types.) When Alarm 2 is programmed for 4;;# or (;2', this parameter is not available. For more details on alarms, see the Alarm Module <.:#. PROPORTIONAL BAND &+;& " ! <76 * Alternating indication only used in the Hidden Loop. 676 to 55575 (% of full input range) The proportional band should be set to obtain the best response to a process disturbance while minimizing overshoot. A proportional band of 0.0% forces the controller into On/Off Control with its characteristic cycling at Setpoint. For more information, see Control Mode and PID Tuning Explanations. 9 STEP 6 PROGRAMMING WITHIN THE HIDDEN LOOP To enter Hidden Loop, press " for 3 seconds. HIDDEN LOOP Note: Parameters shown bold are the only parameters visible in the Hidden Loop with Factory Settings. Setpoint and Output Power are factory set for the Display Loop. The remaining parameters can be selected for the Hidden Loop within Module 3 Parameter availability is model and programming dependent. HIDDEN LOOP When " is pressed and held for three seconds, the controller advances to the Hidden Loop. The Temperature/Process Value is shown in the top display. The bottom display alternates between the parameter and its selection/value. # or $ is pressed to change the selection/value for the shown parameter. The new selection/value is activated after " is pressed. When ! is pressed, the controller returns to the Display Loop and stores changed selection/values to permanent memory. Hidden Loop parameters may be locked out in Lockout Module 3.#4. Some parameters are model and programming dependent. ACCESS CODE 4;-' " ! 6 is always in tenths of degrees per minute, regardless of the resolution chosen for the process display. With the P16, the ramp rate is in least-significant (display units) digits per minute. A value of 0.0 or 0 disables setpoint ramping. Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to starting Auto-Tune, the ramping is suspended during Auto-Tune and then resumed afterward. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint. A slow process may not track the programmed setpoint rate. At power up, the ramping setpoint is initialized at the ambient temperature/process value. 0 to 08= If the Access Code is set from 1 to 125, in Lockout Module 3. #4, Access Code will appear here. By entering the proper Code, access to the Hidden Loop is permitted. With the factory setting of 0, Access Code will not appear in the Hidden Loop. A universal code of 111 can be entered to gain access, independent of the programmed code number. SETPOINT SELECT )&)# " ! )&0 )&0 or )&8 CONTROL MODE TRANSFER The SPSL function allows the operator to switch from or to, setpoint 1 and setpoint 2. In the Display Loop, there is no annunciator indicating the selected Setpoint, however, the selected Setpoint value is displayed and activated. ,+2/ " ! :>,; 676 to %)'+ In Automatic Mode, the percentage of Output Power is automatically determined by the controller. In Manual/User %)'+ Mode, the percentage of Output Power is adjusted manually while in the Display Loop. The Control Mode can also be transferred through the F1 Key or User Input. For more information, see Control Mode Explanations. SETPOINT RAMP RATE )&+& " ! 676 :>,; 55575 The setpoint ramp rate can reduce sudden shock to the process and reduce overshoot on startup or after setpoint changes, by ramping the setpoint at a controlled rate. R annunciator flashes while ramping. With the T16, the ramp rate 10 AUTO-TUNE START ,%(' " ! (" (" ACCESS CODE 4;-' " ! 6 ?') The Auto-Tune procedure of the controller sets the Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Output Dampening Time, and Relative Gain (Heat/Cool) values appropriate to the characteristics of the process. This parameter allows front panel starting ?') or stopping (" of AutoTune. For more information, see PID Tuning Explanations. to .08= If the Access Code is set from -1 to -125, in Lockout Module 3.#4, Access Code will appear here. By entering the proper Code, access to the Configuration Loop is permitted (with a negative Code value, the Hidden Loop can be accessed without the use of a code). With the factory setting of 0 or with an active User Input configured for Program Lock (&#"4), Access Code will not appear here. An active user input configured for Program Lock (&#"4) always locks out the Configuration Loop, regardless of Access Code. ALARMS RESET :#+) " ! 0.8 .0 0.8 With alarm models, the alarms can be manually reset. The up key resets Alarm 1 and the down key resets Alarm 2. STEP 7.0 PROGRAMMING WITHIN THE CONFIGURATION LOOP CONFIGURATION LOOP To access the Configuration Loop, press the up key when 4(/&/(" is displayed in the Hidden Loop. The arrow keys are used to select the parameter module (1-9). To enter a specific module press " while the module number is displayed. In the Configuration Loop, 4(/& will alternate with the parameter number in the bottom display. The Temperature/Process Value is shown in the top display. After entering a parameter module, press " to advance through the parameter names in the module. To change a parameter’s selection/value, press the arrow keys while the parameter is displayed. In the modules, the top display shows the parameter name, and the bottom display shows the selection/value. Use " to enter any selection/values that have been changed. The change is not committed to permanent memory until the controller is returned to the Display Loop. If a power loss occurs before returning to the Display Loop, the new values must be entered again. At the end of each module, the controller returns to 4(/&/(". At this location, pressing " again returns the display to the the Display Loop. Pressing the Up key allows re-entrance to the Configuration Loop. Whenever ! is pressed, '2- momentarily appears as the parameters are stored to permanent memory and the controller returns to the Display Loop. 11 STEP 7.1 MODULE 1 - Input Parameters (0.1() T16 Only PARAMETER MENU INPUT TYPE ,?&' ,@.A SELECTION TYPE tc-t tc-E tc-A tc-K tc-r tc-S tc-b SETPOINT LOW LIMIT SELECTION T TC E TC J TC K TC R TC S TC B TC tc-N tc-C LIN r385 r392 r672 rLIN )&#" 6 TYPE N TC C TC The controller has a programmable low setpoint limit value to restrict the setting range of the setpoint. Set the limit so that the setpoint value cannot be set below the safe operating area of the process. Linear mV RTD 385 RTD 392 RTD 672 Linear Ohms SETPOINT HIGH LIMIT Select the input type that corresponds to the input sensor. )&*1 5555 TEMPERATURE SCALE )4:# B/ USER INPUT FUNCTION (OPTIONAL) 12&, &#"4 DECIMAL RESOLUTION SELECTION 6 to 676 for temperature and resistance inputs 6766 for mV inputs NONE PLOC ILOC trnF Select whole degrees, or tenths of degrees for Temperature display, Setpoint values, and related parameters. For Linear Resistance inputs +#1(, the same parameter selections apply in ohms or tenths of an ohm. For mV inputs #1(, only hundredths of a mV resolution is available. 6 = least to < = most The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. If the signal is varying too greatly due to measurement noise, increase the filter value. If the fastest controller response is needed, decrease the filter value. SHIFT/OFFSET )*C, 6 FUNCTION No Function Program Lock Integral Action Lock SELECTION SPt SPrP ALrS FUNCTION Setpoint 1 or 2 Select Setpoint Ramp Disable Reset Both Alarms Auto/Manual Select The controller performs the selected User Input function (User Input available only on models with alarms), when the User terminal 1 is connected (pulled low) to Common terminal 8. No Function: No function is performed. Program Lock: The Configuration Loop is locked, as long as activated (maintained action). Integral Action Lock: The integral action of the PID computation is disabled (frozen), as long as activated (maintained action). Auto/Manual Select: This function selects (maintained action) Automatic (open) or Manual Control (activated). Setpoint 1 or 2 Select: This function selects (maintained action) Setpoint 1(open) or Setpoint 2 (activated) as the active setpoint. Setpoint Ramp Disable: The setpoint ramping feature is disabled, as long as activated (maintained action). Any time the user input is activated with a ramp in process, ramping is aborted. Reset Alarms: Active alarms are reset, as long as activated (maintained action). Active alarms are reset until the alarm condition is cleared and triggered again (momentary action). DIGITAL FILTERING /#,+ 0 .555 to 5555 The controller has a programmable high setpoint limit value to restrict the setting range of the setpoint. Set the limit so that the setpoint value cannot be set above the safe operating area of the process. B/ Fahrenheit B4 Celsius Select either degrees Fahrenheit or Celsius. For linear mV and ohms input types, this has no effect. If changed, adjust related parameter values, as the controller does not automatically convert them. -4&, 6 .555 to 5555 .555 to 5555 degrees This value offsets the controller’s temperature display value by the entered amount. This is useful in applications in which the sensor cannot provide the actual temperature signal due to mounting constraints, inaccuracy, etc. 12 The controller performs the selected F1 Key Function, when ! is pressed while in the Display Loop. In any other loop or module location, pressing ! will perform an escape to the Display Loop. No Function: No function is performed. Auto/Manual Select: This function toggles (momentary action) the controller between Automatic and Manual Control. Setpoint 1 or 2 Select: This function toggles (momentary action) the controller between Setpoint 1 and Setpoint 2. Reset Alarms: This function can be used to reset one or both of the alarms when activated (momentary action) The alarm will remain reset until the alarm condition is cleared and triggered again. F1 KEY FUNCTION /012 ("(' SELECTION NONE trnF SPt FUNCTION SELECTION No Function Auto/Manual Select Setpoint 1 or 2 Select A1rS A2rS ALrS FUNCTION Reset Alarm 1 Reset Alarm 2 Reset Both Alarms STEP 7.1 MODULE 1 - Input Parameters (0.1() P16 Only PARAMETER MENU DIGITAL FILTERING INPUT TYPE ,?&' 4>++ SELECTION TYPE Curr VOLt Current /#,+ 0 Voltage The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes. If the signal is varying too greatly due to measurement noise, increase the filter value. If the fastest controller response is needed, decrease the filter value. Select the input type that corresponds to the input signal. PERCENT ANNUNCIATOR &4, (" ?') On (" Off SCALING To scale the controller, two scaling points are necessary. Each scaling point has a coordinate pair of Display Values and Input Values. It is recommended that the two scaling points be at the low and high ends of the input signal being measured. Process value scaling will be linear between and continue past the entered points to the limits of the input range. (Factory settings example will display 0.0 at 4.00 mA input and display 100.0 at 20.00 mA input.) Reverse acting indication can be accomplished by reversing the two signal points or the Display value points, but not both. If both are reversed, forward (normal) acting indication will occur. In either case, do not reverse the input wires to change the action. This only illuminates the % annunciator. It does not perform any type of percent function, but is useful in applications that have been scaled in percent. DECIMAL RESOLUTION -4&, 676 6 676 6766 67666 This selection affects the decimal point placement for the Process value, and related parameters. DISPLAY VALUE SCALING POINT 1 -)&0 676 ROUNDING INCREMENT +2670 6 = least to < = most .555 to 5555 Enter the first coordinate Display Value by using the arrow keys. 0 to 066 In steps of 1 least significant digit, regardless of decimal point. INPUT VALUE SCALING POINT 1 Rounding selections other than 1 cause the process value display to round to the nearest rounding increment selected. (For example, rounding of 5 causes 122 to round to 120 and 123 to round to 125.) Rounding starts at the least significant digit of the process value. Setpoint values, Setpoint limits, Alarm values, Input Scaling values, and Analog Scaling values are not affected by rounding. 1(&0 <766 6766 to 86766 6766 to 06766 mA V For Key-in Method, enter the first coordinate Input Value by using the arrow keys. To allow the P16 to “learn” the signal, use the Applied Method. For Applied Method, press !. The ° annunciator is turned on to indicate the applied method. Adjust the applied signal level externally until the appropriate value appears under 1(&0. Using either method, press " to store the value for 1(&0. (The controller can be toggled back to the Key-in Method by pressing ! before ".) 13 DISPLAY VALUE SCALING POINT 2 -)&8 06676 USER INPUT FUNCTION (OPTIONAL) 12&, &#"4 .555 to 5555 Enter the second coordinate Display Value by using the arrow keys. SELECTION NONE PLOC ILOC trnF INPUT VALUE SCALING POINT 2 1(&8 86766 6766 to 86766 6766 to 06766 mA V Program Lock Integral Action Lock SELECTION SPt SPrP ALrS FUNCTION Setpoint 1 or 2 Select Setpoint Ramp Disable Reset Both Alarms Auto/Manual Select The controller performs the selected User Input function (User Input available only on models with alarms), when the User terminal 1 is connected (pulled low) to Common terminal 8. No Function: No function is performed. Program Lock: The Configuration Loop is locked, as long as activated (maintained action). Integral Action Lock: The integral action of the PID computation is disabled (frozen), as long as activated (maintained action). Auto/Manual Select: This function selects (maintained action) Automatic (open) or Manual Control (activated). Setpoint 1 or 2 Select: This function selects (maintained action) Setpoint 1(open) or Setpoint 2 (activated) as the active setpoint. Setpoint Ramp Disable: The setpoint ramping feature is disabled, as long as activated (maintained action). Any time the user input is activated with a ramp in process, ramping is aborted. Reset Alarms: Active alarms are reset, as long as activated (maintained action). Active alarms are reset until the alarm condition is cleared and triggered again (momentary action). For Key-in Method, enter the second coordinate Input Value by using the arrow keys. To allow the P16 to “learn” the signal, use the Applied Method. For Applied Method, press !. The ° annunciator is turned on to indicate the applied method. Adjust the applied signal level externally until the appropriate value appears under 1(&8. Using either method, press " to store the value for 1(&8. (The controller can be toggled back to the Key-in Method by pressing ! before ".) SETPOINT LOW LIMIT )&#" 676 FUNCTION No Function .555 to 5555 The controller has a programmable low setpoint limit value to restrict the setting range of the setpoint. Set the limit so that the setpoint value cannot be set below the safe operating area of the process. F1 KEY FUNCTION /012 ("(' SETPOINT HIGH LIMIT )&*1 55575 .555 to 5555 SELECTION NONE trnF SPt The controller has a programmable high setpoint limit value to restrict the setting range of the setpoint. Set the limit so that the setpoint value cannot be set above the safe operating area of the process. FUNCTION No Function Auto/Manual Select Setpoint 1 or 2 Select SELECTION A1rS A2rS ALrS FUNCTION Reset Alarm 1 Reset Alarm 2 Reset Both Alarms The controller performs the selected F1 key function, when ! is pressed while in the Display Loop. In any other loop or module location, pressing ! will perform an escape to the Display Loop. No Function: No function is performed. Auto/Manual Select: This function toggles (momentary action) the controller between Automatic and Manual Control. Setpoint 1 or 2 Selection: This function toggles (momentary action) the controller between Setpoint 1 and Setpoint 2. Reset Alarms: This function can be used to reset one or both of the alarms when activated (momentary action). The alarm will remain reset until the alarm condition is cleared and triggered again. 14 STEP 7.2 MODULE 2 - Output Parameters (8."&) PARAMETER MENU SENSOR FAIL POWER LEVEL CYCLE TIME 4?4, 876 "&/# 6 676 to 8=676 seconds This parameter sets the power level for the control outputs in the event of a sensor failure. If Alarm 2 is not selected for cooling, the range is from 0% (O1 output full off) to 100% (O1 output full on). If A2 is selected for cooling, the range is from -100 to +100%. At 0%, both O1 and O2 are off; at 100%, O1 is on; and at -100%, O2 is on. The alarm outputs are upscale drive with an open sensor, and downscale drive with a shorted sensor (RTD only), independent of this setting. Manual Control overrides the sensor fail preset. The Cycle Time is entered in seconds with one tenth of a second resolution. It is the total time for one on and one off period of the time proportioning control output O1. With time proportional control, the percentage of power is converted into an output on-time relative to the cycle time value set. (If the controller calculates that 65% power is required and a cycle time of 10.0 seconds is set, the output will be on for 6.5 seconds and off for 3.5 seconds.) For best control, a cycle time equal to onetenth or less, of the natural period of oscillation of the process is recommended. When using the Analog Output signal for control, the Cycle Time setting has no effect. If the O1 output is not being used, a cycle time of 0 can be entered to prevent the output and indicator from cycling. OUTPUT POWER DAMPENING "&-& 3 0 CONTROL ACTION "&:4 +'D 6 to 066 percent O1 .066 to 066 percent O1/O2 [email protected], Direct (cooling) +'D Reverse (heating) 6 to 8=6 seconds T16 P16 The Dampening Time, entered as a time constant in seconds, dampens (filters) the calculated output power. Increasing the value increases the dampening effect. Generally, dampening times in the range of one-twentieth to one-fiftieth of the controller’s integral time (or process time constant) are effective. Dampening times longer than these may cause controller instability due to the added lag effect. This determines the control action for the PID loop. Programmed for direct action (cooling), the output power will increase if the Process value is above the Setpoint value. Programmed for reverse action (heating), the output power decreases when the Process Value is above the Setpoint Value. For heat and cool applications, this is typically set to reverse. This allows O1 or A1 (models with Analog Output) to be used for heating, and A2/O2 to be used for cooling. ON/OFF CONTROL HYSTERESIS 4*?) 8 678 OUTPUT POWER LOWER LIMIT "&#" 6 6 to 066 percent O1 .066 to 066 percent O1/O2 P16 The controller can be placed in the On/Off Control Mode by setting the Proportional Band to 0.0%. The On/Off Control Hysteresis (balanced around the setpoint) eliminates output chatter. In heat/cool applications, the control hysteresis value affects both Output O1 and Output O2 control. It is suggested to set the hysteresis band to Factory Setting prior to starting AutoTune. After Auto-Tune, the hysteresis band has no effect on PID Control. On/Off Control Hysteresis is illustrated in the On/Off Control Mode section. This parameter may be used to limit controller power at the lower end due to process disturbances or setpoint changes. Enter the safe output power limits for the process. If Alarm 2 is selected for cooling, the range is from -100 to +100%. At 0%, both O1 and O2 are off; at 100%, O1 is on; and at -100%, O2 is on. When the controller is in Manual Control Mode, this limit does not apply. AUTO-TUNE CODE OUTPUT POWER UPPER LIMIT "&*1 066 0 to 8=6 T16 ,@;6 6 to 066 percent O1 .066 to 066 percent O1/O2 6 fastest to 8 slowest Prior to starting Auto-Tune, this code should be set to achieve the necessary dampening level under PID Control. This value allows customization of the PID values that Auto-Tune will calculate. For the process to be controlled aggressively (fastest process response with possible overshoot), set the Auto-Tune Code to 0. For the process to be controlled conservatively (slowest response with the least amount of overshoot), set this value to 2. If the Auto-Tune Code is changed, Auto-Tune needs to be reinitiated for the changes to affect the PID settings. For more information, see PID Tuning Explanations Section. This parameter may be used to limit controller power at the upper end due to process disturbances or setpoint changes. Enter the safe output power limits for the process. If Alarm 2 is selected for cooling, the range is from -100 to +100%. At 0%, both O1 and O2 are off; at 100%, O1 is on; and at -100%, O2 is on. When the controller is in Manual Control Mode, this limit does not apply. 15 ANALOG OUTPUT RANGE (OPTIONAL) :(,& <.86 6.06 V 6.86 <.86 mA ANALOG LOW SCALING (OPTIONAL) :(#" 676 mA Select the type of output and range. The Analog output jumpers are factory set to current. They must be changed if voltage output is desired. The Analog output can be calibrated to provide up to approximately 5% over range operation (0 mA current can only go slightly negative). The Analog Output assignment value that corresponds to 0 V, 0 mA or 4 mA output as selected. ANALOG OUTPUT ASSIGNMENT (OPTIONAL) :(:) "& "& 12& SP .555 to 5555 ANALOG HIGH SCALING (OPTIONAL) Main Control % Output Power :(*1 06676 Input Signal Retransmission Active Setpoint This setting selects the parameter that the Analog Output will retransmit or track. .555 to 5555 The Analog Output assignment value that corresponds to 10 V or 20 mA output as selected. An inverse acting output can be achieved by reversing the low and high scaling points. ANALOG UPDATE TIME (OPTIONAL) :(%, 6 6 to 8=6 seconds 6 = update rate of 0.1 second The update time of the Analog Output can be used to reduce excess valve actuator or pen recorder activity. STEP 7.3 MODULE 3 - Lockout Parameters (3.#4) PARAMETER MENU SELECTION dISP HIdE LOC dSPr ACCESS CODE DESCRIPTION 4;-' 6 Display: accessible in Display Loop. Hide: accessible in Hidden Loop. .08= to 08= Locked: not accessible in either loop. (SP only) 0 Display/read: read only in Display Loop, but read/write in Hidden Loop. -1 to -125 1 to 125 Full access to Display, Hidden, and Configuration Loops Code necessary to access Configuration Loop only. Code necessary to access Hidden and Configuration Loops. The following parameters can be configured for #"4, *1-', and -1)&. SETPOINT ACCESS )& -1)& OUTPUT POWER ACCESS "& -1)& PID VALUES ACCESS &1*1-' The following parameters can be configured for #"4 or *1-' only. ALARM VALUES ACCESS SETPOINT SELECT ACCESS :# *1-' SETPOINT RAMP ACCESS CONTROL TRANSFER ACCESS )&+& *1-' ,+2/ #"4 )&)# #"4 AUTO-TUNE START ACCESS ,%(' *1-' 16 RESET ALARMS ACCESS :#+) #"4 STEP 7.4 MODULE 4 - Alarm Parameters (<.:#) (OPTIONAL) PARAMETER MENU AVAILABLE ALARM ACTIONS NONE None No action, the remaining Alarm parameters are not available. d-HI Deviation High Alarm 1 and 2 value tracks the Setpoint value AbHI Absolute High (balanced hysteresis) The alarm energizes when the Process Value exceeds the alarm value + 1/2 the hysteresis value. d-LO Deviation Low Alarm 1 and 2 value tracks the Setpoint value Band Acting (inside) Alarm 1 and 2 value tracks the Setpoint value AbLO The alarm energizes when the Process Value falls below the alarm value -1/2 the hysteresis value. b-IN Absolute Low (balanced hysteresis) b-ot Band Acting (outside) Alarm 1 and 2 value tracks the Setpoint value AuHI Absolute High (unbalanced hysteresis) The alarm energizes when the Process Value exceeds the alarm value. HEAt Heat (A1 Analog models only) If heating is selected, the remaining Alarm 1 parameters are not available. AuLO Absolute Low (unbalanced hysteresis) The alarm energizes when the Process Value falls below the alarm value. CooL Cool (A2 only) If cooling is selected, the remaining Alarm 2 parameters are not available. ALARM ACTION FIGURES Note: Hys in the above figures refers to the Alarm Hysteresis. 17 ALARM ACTION ALARM 2 ALARM ACTION ALARM 1 :4,0 :>*1 :4,8 :>*1 NONE AbHI AbLO AuHI AuLO d-HI d-LO b-IN b-ot HEAt Select the action for the alarms. See Alarm Action Figures for a visual explanation. Select the action for the alarms. See Alarm Action Figures for a visual explanation. ALARM ANNUNCIATOR ALARM 1 #E,0 2;+ ALARM ANNUNCIATOR ALARM 2 #E,8 2;+ 2;+ Normal +'D Reverse With normal selection, the alarm annunciator indicates “on” alarm output 1. With reverse selection, the alarm annunciator indicates “off” alarm output. ALARM RESET MODE ALARM 2 +),8 :>,; :>,; Automatic #:,@ Latched In Automatic mode, an energized alarm turns off automatically after the Temperature/Process value leaves the alarm region. In Latched mode, an energized alarm requires an F1 key or user input alarm reset to turn off. After an alarm reset, the alarm remains reset off until the trigger point is crossed again. ALARM STANDBY ALARM 2 ),F8 (" ?') Standby on (" Standby off Standby prevents nuisance (typically low level) alarms after a power up or setpoint change. After powering up the controller or changing the setpoint, the process must leave the alarm region (enter normal non-alarm area of operation). After this has occurred, the standby is disabled and the alarm responds normally until the next controller power up or setpoint change. 6 676 ?') Standby on (" Standby off Standby prevents nuisance (typically low level) alarms after a power up or setpoint change. After powering up the controller or changing the setpoint, the process must leave the alarm region (enter normal non-alarm area of operation). After this has occurred, the standby is disabled and the alarm responds normally until the next controller power up or setpoint change. ALARM VALUE ALARM 1 :#.0 :>,; Automatic #:,@ Latched In Automatic mode, an energized alarm turns off automatically after the Temperature/Process value leaves the alarm region. In Latched mode, an energized alarm requires an F1 key or user input alarm reset to turn off. After an alarm reset, the alarm remains reset off until the trigger point is crossed again. ALARM STANDBY ALARM 1 ),F0 (" 2;+ Normal +'D Reverse With normal selection, the alarm annunciator indicates “on” alarm output 2. With reverse selection, the alarm annunciator indicates “off” alarm output. ALARM RESET MODE ALARM 1 +),0 :>,; NONE AbHI AbLO AuHI AuLO d-HI d-LO b-IN b-ot CooL ALARM VALUE ALARM 2 :#.8 86 876 .555 to 5555 T16 P16 The alarm values are entered as process units or degrees. They can also be entered in the Display or Hidden Loops. When the alarm is configured as deviation or band acting, the associated output tracks the Setpoint as it is changed. The value entered is the offset or difference from the Setpoint. .555 to 5555 T16 P16 The alarm values are entered as process units or degrees. They can also be entered in the Display or Hidden Loops. When the alarm is configured as deviation or band acting, the associated output tracks the Setpoint as it is changed. The value entered is the offset or difference from the Setpoint. ALARM HYSTERESIS :*?) 0 670 6 to 8=6 T16 P16 The Hysteresis Value is either added to or subtracted from the alarm value, depending on the alarm action selected. The same value applies to both alarms. See the Alarm Action Figures for a visual explanation of how alarm actions are affected by the hysteresis. 18 STEP 7.5 MODULE 5 - Cooling (Secondary) Parameters (=."8) PARAMETER MENU To enable Cooling in Heat/Cool applications, the Alarm 2 Action must first be set for Cooling. (For P16 Controllers, the cooling output is sometimes referred to as secondary output.) When set to cooling, the output no longer operates as an alarm but operates as a cooling output. The O2 terminals are the same as A2, however a separate O2 annunciator indicates Cooling Operation. Cooling output power ranges from -100% (full cooling) to 0% (no cooling, unless a heat/cool overlap is used). The Power Limits in Output Module 8."& also limit the cooling power. In applications requiring only a Cooling output, the main 01 output should be used. DEADBAND/OVERLAP CYCLE TIME 4?48 876 -F.8 6 676 to 8=676 seconds This cycle time functions like the O1 Output Cycle Time but allows independent cycle time for cooling. A setting of zero will keep output O2 off. This defines the overlap area in which both heating and cooling are active (negative value) or the deadband area between the bands (positive value). If a heat/cool overlap is specified, the percent output power is the sum of the heat power (O1) and the cool power (O2). If Relative Gain is zero, the cooling output operates in the On/Off Control Mode, with the On/Off Control Hysteresis 4*?) in Output Module 8."& becoming the cooling output hysteresis. The function of Deadband is illustrated in the Control Mode Explanations. For most applications, set this parameter to 0.0 prior to starting Auto-Tune. After the completion of Auto-Tune, this parameter may be changed. RELATIVE GAIN G:(8 076 .555 to 5555 676 to 0676 This defines the gain of the cooling relative to the heating. It is generally set to balance the effects of cooling to that of heating. This is illustrated in the Heat/Cool Relative Gain Figures. A value of 0.0 places the cooling output into On/Off Control. HEAT/COOL RELATIVE GAIN FIGURES Heat/Cool Deadband = 0 Heat/Cool Deadband < 0 Heat/Cool Deadband > 0 19 STEP 7.5 MODULE 9 FACTORY SERVICE OPERATIONS (5./)) RTD Resistance (T16) RTD calibration requires a precision 277.0 ohm resistor with an accuracy of 0.1 Ω (or better). Connect a jumper between terminals 9 and 10 with a 0 ohm jumper between 9 and 8 at ),&0 and the 277.0 ohm resistor between 9 and 8 at ),&8. If using thermocouple only, the RTD calibration need not be performed. PROMPT [CodE] [CAL] [CJC] [rtd] [StP1] [StP2] CALIBRATION 4;-' <H The controller is fully calibrated from the factory. Recalibration is recommended every two years by qualified technicians using appropriate equipment. Calibration may be performed by using the front panel or with the TP16KIT. The front panel method is explained below. (Refer to the TP16KIT bulletin for calibration instructions using TP16KIT cable and software.) Calibration may be aborted by disconnecting power to the controller before exiting Factory Service Module 5./). In this case, the existing calibration settings remain in effect. Note: Allow the controller to warm up for 30 minutes minimum and follow the manufacturer’s warm-up recommendations for the calibration source or measuring device. [CodE] [CAL] [StP1] [StP2] [StP3] [StP4] [StP5] PROMPT [CodE] [CAL] [StP1] [StP2] [StP3] [StP4] [StP5] [StPA] [StPb] FRONT PANEL ACTION Press $ until Press # for <H, press ". ?'), press ". 0.0 mV After 5 seconds (minimum), press ". 14.0 mV After 5 seconds (minimum), press ". 28.0 mV After 5 seconds (minimum), press ". 42.0 mV After 5 seconds (minimum), press ". 56.0 mV After 5 seconds (minimum), press ". [CodE] [CAL] [CJC] PROMPT FRONT PANEL ACTION Press $ until <H, press ". Press ". Press # for Top display to external reference Press ". Press # for 0.0 ohm ?'), press ". After 5 seconds (minimum), press ". 277.0 ohm After 5 seconds (minimum), press ". APPLY FRONT PANEL ACTION Press $ until Press # for <H, press ". ?'), press ". 0.0 V After 5 seconds (minimum), press ". 2.5 V After 5 seconds (minimum), press ". 5.0 V After 5 seconds (minimum), press ". 7.5 V After 5 seconds (minimum), press ". 10.0 V After 5 seconds (minimum), press ". 0.0 mA After 5 seconds (minimum), press ". 20.0 mA After 5 seconds (minimum), press ". Set the controller Analog jumpers to the output type being calibrated. Connect an external meter with an accuracy of 0.05% (or better) that is capable of measuring 10.00 V or 20.00 mA to terminals 6 (+V/I) and 7 (-V/I). The voltage or current calibration that is not being used must be skipped by pressing " until End appears. Cold Junction calibration requires a thermocouple of known accuracy of types T, E, J, K, C or N (connected to terminals 8 and 9) and a calibrated external reference thermocouple probe measuring in °C with resolution to tenths. The two probes should be brought in contact with each other or in some way held at the same temperature. They should be shielded from air movement and allowed sufficient time to equalize in temperature. (As an alternative, the T16 thermocouple may be placed in a calibration bath of known temperature.) If performing the millivolt calibration prior, verify that the correct input type is configured in Input Module 0.1( before performing the following procedure. (After the millivolt calibration the controller will default to type J.) If using RTD only, the cold junction calibration need not be performed. COMPARE <H, press ". Press ". Analog Output Calibration (T16 and P16) Cold Junction (T16) PROMPT Press $ until Process calibration requires a precision signal source with an accuracy of 0.03% (or better) that is capable of generating 10.0 V connected to terminals 8 (COMM) and 9 (+10V) and 20.00 mA connected to terminals 8 (COMM) and 10 (20mA). The current calibration can be skipped by pressing " at the not applicable prompts if using the controller for process voltage only. Millivolt calibration requires a precision voltage source with an accuracy of 0.03% (or better) connected to terminals 8 (comm.) and 9 (+). When calibrating the input, the millivolt calibration must be performed first, then the Cold Junction or RTD Resistance. APPLY FRONT PANEL ACTION Input Calibration (P16) Millivolt Calibration (T16) PROMPT APPLY EXTERNAL METER [CodE] [CAL] [CJC] [rtd] [ANCL] [C 0v] 0.00 V Press # or $ until external meter matches listing, press ". C 10v 10.00 V Press # or $ until external meter matches listing, press ". C 0c] 0.00 mA Press # or $ until external meter matches listing, press ". C 20c 20.00 mA Press # or $ until external meter matches listing, press ". Press $ until 20 <H, press ". Press ". Press ". (T16 only) Press ". (T16 only) Press # for ?'), press ". Press # or $ to adjust the bottom display until the top process display matches the external reference then press ". FRONT PANEL ACTION ?'), press ". RESTORE FACTORY SETTINGS NOMINAL CALIBRATION SETTINGS 4;-' II 4;-' JJ Press and hold # to display 4;-' II. Press ". The controller will display +)', and then return to 4(/&. Press ! to return to the Display Loop. This will overwrite all user settings with Factory Settings. Press and hold # to display 4;-' JJ. Press ". Press and hold # to display 4;-' JJ again. Press ". The controller will then return to 4(/&. Press ! to return to the Display Loop. This will not overwrite any user settings but will erase the controller calibration values. This procedure does not require any calibration signals nor external meters. This can be used to clear calibration error flag '.4#. CAUTION: This procedure will result in up to ±10% reading error and the controller will no longer be within factory specifications. For this reason, this procedure should only be performed if meter error is outside of this range to temporarily restore operation until the unit can be accurately calibrated. TROUBLESHOOTING For further technical assistance, contact technical support. PROBLEM CAUSE REMEDIES NO DISPLAY 1. 2. 3. 4. Power off. 1. Brown-out condition. 2. Loose connection or improperly wired. 3. Bezel assembly not fully seated into rear of 4. controller. 1. CONTROLLER NOT WORKING 1. Incorrect setup parameters. '.'8 IN DISPLAY 1. Loss of setup parameters due to noise spike or 1. Press F1 to escape, then check all setup parameters. other EMI event. a. Check sensor input and AC line for excessive noise. b. If fault persists, replace controller. '.4# IN DISPLAY 1. Loss of calibration parameters due to noise 1. Press F1 to escape, then check controller accuracy. spike or other EMI event. a. Recalibrate controller. (See Factory Service Module code 77.) b. Reset parameters to factory default settings. ---- or .--- IN DISPLAY 1. Display value exceeds 4 digit display range. "&'( IN DISPLAY (T16) 1. 2. 3. 4. Probe disconnected. Broken or burned-out probe. Corroded or broken terminations. Excessive process temperature. 1. 2. 3. 4. Connect probe. Replace probe. Check connections. Check process parameters. )'() IN DISPLAY (P16) 1. 2. 3. 4. Input exceeds range of controller. Incorrect input wiring. Defective transmitter. Internal malfunction. 1. 2. 3. 4. Check input parameters. Check input wiring. Replace transmitter. Perform input calibration. "#"# IN TOP DISPLAY 1. 2. 3. 4. 5. Input exceeds range of controller. Temperature exceeds range of input probe. Defective or incorrect transmitter or probe. Excessive high temperature for probe. Loss of setup parameters. 1. Check input parameters. 2. Change to input sensor with a higher temperature range. 3. Replace transmitter or probe. 4. Reduce temperature. 5. Perform input calibration. %#%# 1. 2. 3. 4. 5. Input is below range of controller. Temperature below range of input probe. Defective or incorrect transmitter or probe. Excessive low temperature for probe. Loss of setup parameters. 1. 2. 3. 4. 5. IN TOP DISPLAY )*+, IN DISPLAY (T16) Check power. Verify power reading. Check connections. Check installation. Check setup parameters. 1. Change resolution to display whole number and verify reading. 2. Defective or miscalibrated cold junction circuit. 2. Perform cold junction calibration. 3. Loss of setup parameters. 3. Check setup parameters. 4. Internal malfunction. 4. Perform Input calibration. 1. RTD probe shorted. Check input parameters. Change to input sensor with a lower temperature range. Replace transmitter or probe. Raise temperature. Perform input calibration. 1. Check wiring and/or replace RTD probe. CONTROLLER SLUGGISH OR 1. Incorrect PID values. 2. Incorrect probe location. NOT STABLE 1. See PID control. 2. Evaluate probe location. 21 CONTROL MODE EXPLANATIONS ON/OFF CONTROL ON/OFF CONTROL - HEAT/COOL OUTPUT FIGURES The controller operates in On/Off Control when the Proportional Band is set to 0.0%. In this control mode, the process will constantly oscillate around the setpoint value. The On/Off Control Hysteresis (balanced around the setpoint) can be used to eliminate output chatter. Output O1 Control Action can be set to reverse for heating (output on when below the setpoint) or direct for cooling (output on when above the setpoint) applications. ON/OFF CONTROL REVERSE OR DIRECT ACTING FIGURES Note: CHYS in the On/Off Control Figures refers to the On/Off Control Hysteresis (4*?)) in parameter Module 2. For heat and cool systems, O1 Control Action is set to reverse (heat) and the Alarm 2 Action is set to cooling (O2). The Proportional Band is set to 0.0 and the Relative Gain in Cooling to 0.0. The Deadband in Cooling sets the amount of operational deadband or overlap between the outputs. The setpoint and the On/Off Control Hysteresis applies to both O1 and O2 outputs. The hysteresis is balanced in relationship to the setpoint and deadband value. PID CONTROL TYPICAL PID RESPONSE CURVE In PID Control, the controller processes the input and then calculates a control output power value by use of a modified Proportional Band, Integral Time, and Derivative Time control algorithm. The system is controlled with the new output power value to keep the process at the setpoint. The Control Action for PID Control can be set to reverse for heating (output on when below the setpoint) or direct for cooling (output on when above the setpoint) applications. For heat and cool systems, the heat (O1) and cool (O2) outputs are both used. The PID parameters can be established by using Auto-Tune, or they can be Manually tuned to the process. 22 TIME PROPORTIONAL PID CONTROL MANUAL CONTROL MODE In Time Proportional applications, the output power is converted into output On time using the Cycle Time. For example, with a four second cycle time and 75% power, the output will be on for three seconds (4 × 0.75) and off for one second. The cycle time should be no greater than 1/10 of the natural period of oscillation for the process. The natural period is the time it takes for one complete oscillation when the process is in a continuously oscillating state. In Manual Control Mode, the controller operates as an open loop system (does not use the setpoint and process feedback). The user adjusts the percentage of power through the % Power display to control the power for Output O1. When Alarm 2 is configured for Cooling (O2), Manual operation provides 0 to 100% power to O1 (heating) and -100 to 0% power to O2 (Cooling). The Low and High Output Power limits are ignored when the controller is in Manual. MODE TRANSFER LINEAR PID CONTROL In Linear PID Control applications, the Analog Output Assignment :(:) is set to % Output Power, "&. The Analog Low Scaling, :(#" , is set to 0.0 and the Analog High Scaling, :(*1 , is set to 100.0. The Analog Output will then be proportional to the PID calculated % output power for Heat or Cooling per the Control Action "&:4. For example, with 0 VDC to 10 VDC (scaled 0 to 100%) and 75% power, the analog output will be 7.5 VDC. When transferring the controller mode between Automatic and Manual, the controlling outputs remain constant, exercising true “bumpless” transfer. When transferring from Manual to Automatic, the power initially remains steady, but Integral Action corrects (if necessary) the closed loop power demand at a rate proportional to the Integral Time. AUTOMATIC CONTROL MODE In Automatic Control Mode, the percentage of output power is automatically determined by PID or On/Off calculations based on the setpoint and process feedback. For this reason, PID Control and On/Off Control always imply Automatic Control Mode. PID TUNING EXPLANATIONS AUTO-TUNE AUTO-TUNE CODE FIGURE Auto-Tune is a user-initiated function that allows the controller to automatically determine the Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Output Dampening Time, and Relative Gain (Heat/Cool) values based upon the process characteristics. The Auto-Tune operation cycles the controlling output(s) at a control point three-quarters of the distance between the present process value and the setpoint. The nature of these oscillations determines the settings for the controller’s parameters. Prior to initiating Auto-Tune, it is important that the controller and system be first tested. (This can be accomplished in On/Off Control or Manual Control Mode.) If there is a wiring, system or controller problem, Auto-Tune may give incorrect tuning or may never finish. Auto-Tune may be initiated at start-up, from setpoint or at any other process point. However, ensure normal process conditions (example: minimize unusual external load disturbances) as they will have an effect on the PID calculations. Start Auto-Tune Below are the parameters and factory settings that affect AutoTune. If these setting are acceptable then Auto-Tune can be started just by performing two steps. If changes are needed, then they must be made before starting Auto-Tune. DISPLAY PARAMETER tYpE Input Type FLtr Digital Filtering CHYS On/Off Control Hysteresis tcod Auto-Tune Code db-2 Deadband tUnE Auto-Tune Access FACTORY SETTING AUTO-TUNE OPERATION (REVERSE ACTING) MODULE tc-A T16 Curr P16 1 2 T16 0.2 P16 [0] 1-IN [0] 5-O2 [HidE] 3-LC 1-IN 2-OP 2-OP 1. Enter the Setpoint value in the Display Loop. 2. Initiate Auto-Tune by changing Auto-Tune Start ,%(' to ?') in the Hidden Loop. Auto-Tune Progress The controller will oscillate the controlling output(s) for four cycles. The bottom display will flash the cycle phase number. Parameter viewing is permitted during Auto-Tune. The time to complete the Auto-Tune cycles is process dependent. The controller should automatically stop Auto-Tune and store the calculated values when the four cycles are complete. If the controller remains in Auto-Tune unusually long, there may be a process problem. AutoTune may be stopped by entering (" in Auto-Tune Start ,%('. 23 PID Adjustments In some unusual cases, the Auto-Tune function may not yield acceptable control results or induced oscillations may cause system problems. In these applications, Manual Tuning is an alternative. In some applications, it may be necessary to fine tune the Auto-Tune calculated PID parameters. To do this, a chart recorder or data logging device is needed to provide a visual means of analyzing the process. Compare the actual process response to the PID response figures with a step change to the process. Make changes to the PID parameters in no more than 20% increments from the starting value and allow the process sufficient time to stabilize before evaluating the effects of the new parameter settings. PROCESS RESPONSE EXTREMES MANUAL TUNING A chart recorder or data logging device is necessary to measure the time between process cycles. This procedure is an alternative to the controller’s Auto-Tune function. It will not provide acceptable results if system problems exist. 1. Set the Proportional Band (&+;&) to 10.0% for temperature models (T16) and 100.0% for process models (P16). 2. Set both the Integral Time (12,,) and Derivative Time (-'+,) to 0 seconds. 3. Set the Output Dampening Time ("&-&) in Output Module 8."& to 0 seconds. 4. Set the Output Cycle Time [CYCt] in Output Module 8."& to no higher than one-tenth of the process time constant (when applicable). 5. Place the controller in Manual %)'+ Control Mode ,+2/ in the Hidden Loop and adjust the % Power to drive the process value to the Setpoint value. Allow the process to stabilize after setting the % Power. Note: ,+2/ must be set to *E-' in Parameter Lockouts Module 3.#4. 6. Place the controller in Automatic (:>,;) Control Mode ,+2/ in the Hidden Loop. If the process will not stabilize and starts to oscillate, set the Proportional Band two times higher and go back to Step 5. 7. If the process is stable, decrease Proportional Band setting by two times and change the Setpoint value a small amount to excite the process. Continue with this step until the process oscillates in a continuous nature. 8. Fix the Proportional Band to three times the setting that caused the oscillation in Step 7. 9. Set the Integral Time to two times the period of the oscillation. 10. Set the Derivative Time to 1/8 (0.125) of the Integral Time. 11. Set the Output Dampening Time to 1/40 (0.025) the period of the oscillation. 24 Programmer:______________________Date:_________ Controller Number:_______ Security Code:_______ PARAMETER VALUE CHART OUTPUT MODULE (8."&) DISPLAY LOOP DISPLAY PARAMETER SP SETPOINT VALUE SP1 SP OP ProP * SETPOINT VALUE SP2 Intt * INTEGRAL TIME dErt * AL-1 * AL-2 * DERIVATIVE TIME OUTPUT POWER PERCENT PROPORTIONAL BAND ALARM 1 VALUE ALARM 2 VALUE FACTORY SETTING USER SETTING 0 676 86 876 676 <76 T16 06676 P16 086 T16 <6 P16 36 T16 < P16 0 0 T16 P16 T16 P16 * Factory Setting places these parameters in the Hidden Loop (set to Lockout Module 3.#4. *E-' in DISPLAY PARAMETER CYCt OPAC OPLO OPHI OPFL OPdP CYCLE TIME CHYS tcod AntP ANAS ANUt ANLO ANHI ON/OFF CONTROL HYSTERESIS CONTROL ACTION OUTPUT POWER LOWER LIMIT OUTPUT POWER UPPER LIMIT SENSOR FAIL POWER PRESET OUTPUT POWER DAMPENING AUTO-TUNE CODE ANALOG OUTPUT RANGE ANALOG OUTPUT ASSIGNMENT ANALOG UPDATE TIME ANALOG LOW SCALING ANALOG HIGH SCALING FACTORY SETTING USER SETTING 2.0 rEv 6 066 6 3 T16 0 P16 2 T16 678 P16 6 <.86 "& 6 676 06676 HIDDEN LOOP DISPLAY SPSL SPrP trnF tUNE PARAMETER FACTORY SETTING USER SETTING SP1 676 :>,; (" SETPOINT SELECT SETPOINT RAMP RATE CONTROL MODE TRANSFER AUTO-TUNE START DISPLAY INPUT MODULE (0.1( ) T16 ONLY DISPLAY tYPE SCAL dCPt FLtr SHFt SPLO SPHI InPt F1In PARAMETER FACTORY SETTING USER SETTING tc-A B/ 6 0 6 6 5555 &#"4 ("(' INPUT TYPE TEMPERATURE SCALE DECIMAL RESOLUTION DIGITAL FILTERING SHIFT/OFFSET SETPOINT LOW LIMIT SETPOINT HIGH LIMIT USER INPUT FUNCTION F1 KEY FUNCTION tYPE PCt dCPt rnd FLtr dSP1 InP1 dSP2 InP2 SPLO SPHI InPt F1In PARAMETER INPUT TYPE PERCENT ANNUNCIATOR DECIMAL RESOLUTION ROUNDING INCREMENT DIGITAL FILTERING DISPLAY VALUE SCALING 1 INPUT VALUE SCALING 1 DISPLAY VALUE SCALING 2 INPUT VALUE SCALING 2 SETPOINT LOW LIMIT SETPOINT HIGH LIMIT USER INPUT FUNCTION F1 KEY FUNCTION FACTORY SETTING Curr NO 676 670 0 676 <766 06676 86766 676 55575 &#"4 ("(' SP OP PId AL CodE SPSL SPrP trnF tUNE ALrS PARAMETER SETPOINT ACCESS OUTPUT POWER ACCESS PID VALUE ACCESS ALARM VALUE ACCESS ACCESS CODE SETPOINT SELECT ACCESS SETPOINT RAMP ACCESS TRANSFER CONTROL ACCESS AUTO-TUNE ACCESS RESET ALARMS ACCESS FACTORY SETTING USER SETTING -1)& -1)& HIdE HIdE 6 #"4 *1-' #"4 *1-' #"4 ALARM MODULE (<.:#) DISPLAY INPUT MODULE (0.1( ) P16 ONLY DISPLAY LOCKOUT MODULE (3.#4) USER SETTING ACt1 Lit1 rSt1 Stb1 AL-1 ACt2 Lit2 rSt2 Stb2 AL-2 AHYS PARAMETER ALARM 1 ACTION ALARM 1 ANNUNCIATOR ALARM 1 RESET MODE ALARM 1 STANDBY ALARM 1 VALUE ALARM 2 ACTION ALARM 2 ANNUNCIATOR ALARM 2 RESET MODE ALARM 2 STANDBY ALARM 2 VALUE ALARM 1 & 2 HYSTERESIS FACTORY SETTING USER SETTING :>*1 2;+ Auto NO 6 :>*1 2;+ :>,; (" 6 1 T16 670 P16 COOLING MODULE (=."8) DISPLAY CYC2 GAN2 db-2 PARAMETER CYCLE TIME RELATIVE GAIN DEADBAND 25 FACTORY SETTING 2.0 076 6 USER SETTING 26 5./) =."8 <.:# 3.#4 8."& 0.1( 4(/& " ! 2; HIDDEN LOOP Factory Service Code 4;-' Cooling Cycle Time 4?48 Alarm 1 Action :4,0 Setpoint Access Ends and returns to start of Display Loop. )4:# :(,& "& Cooling Relative Gain G:(8 Alarm 1 Annunciator #E,0 Output Power Access "&#" :(:) ✽ "&*1 :(%, Heat/Cool Deadband/Overlap -F.8 Alarm 1 Reset Mode +),0 Alarm 1 Standby ),F0 Alarm Values Access :# )&#" :(#" Alarm 1 Value :#.0 Access Code :(*1 Alarm 2 Reset Mode +),8 Alarm 2 Action :4,8 Setpoint Select Access )&)# Analog High Scaling 4;-' Analog Low Scaling Output Power Dampening /012 ,@;- ✽✽ ,%(' :#.8 Alarm 2 Value Alarm 2 Standby Alarm 1 & 2 Hysteresis :*?) :#+) Reset Alarms Access ✽ - T16 only ✽✽ - P16 only Auto-Tune Auto/Manual Off/On Access Transfer Access ,+2/ Auto-Tune Code ),F8 Alarm 2 Annunciator #E,8 Setpoint Ramp Rate Access )&+& 1(&0 Input Value 1 F1 Key Function On/Off Control Hysteresis 4*?) 12&, User Input Function Display Value 1 ✽✽ Advances to the next module, then changes parameter selection/value. -)&0 )&*1 "&-& Digital Filtering /#,+ #$ Setpoint High Limit Sensor Fail Power Preset "&/# Rounding Increment +2- ✽✽ Enters displayed module, then advances to the next parameter. Setpoint Low Limit Output Power High Limit Analog Output Update Time &1PID Values Access )*/, Decimal Resolution -4&, Shift/Offset ✽ Output Power Low Limit Input Value 2 Analog Output Assignment "&:4 Control Action Display Value 2 1(&8 ✽✽ ✽✽ ✽✽ &4, Temp Scale -)&8 " Parameter availability is model and program dependent. ! Percent Symbol Analog Output Range )& Cycle Time 4?4, Input Type ,?&' DISPLAY LOOP T16 & P16 PROGRAMMING QUICK OVERVIEW This page intentionally left blank. 27 LIMITED WARRANTY The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to one year from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter. No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations. Red Lion Controls 20 Willow Springs Circle Red Lion Controls BV Basicweg 11b Red Lion Controls Asia 31, Kaki Bukit Road 3 #06-04/05 TechLink York PA 17402 NL - 3821 BR Amersfoort Singapore 417818 Tel +1 (717) 767-6511 Tel +31 (0) 334 723 225 Tel +65 6744-6613 Fax +1 (717) 764-0839 Fax +31 (0) 334 893 793 Fax +65 6743-3360
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement