Diris A40-A41_gb.qxd

Diris A40-A41_gb.qxd
DIRIS® system
DIRIS A40
DIRIS A41
Measurement control & energy management
DIRIS A40 / DIRIS A41
Functions
The DIRIS A40 and A41 are multi-function
meter for measuring electrical values in all
low and high voltage networks. All the
parameters can be configured and
displayed on its front panel and measuring
and timing functions used.
The user can also connect plug-in
modules to the rear of the device at any
time, adding such functions as :
• energy metering
• harmonics measurement
• alarms
• communication
diris_561_a_1_x_cat
Conformity to standards
1 2
3
4
5
6
7
DIRIS A40
1. Backlit LDC display
2. Direct access key for currents and setup
wiring correction
3. Direct access key for voltages and frequency
4. Direct access key for active, reactive,
apparente power and power factor
5. Direct access key for max. and average
current and power values
6. Direct access key for harmonics values
7. Direct access key for energies and hour run
meter.
• IEC 62053-22 class 0,5 S
• IEC 62053-23 class 2
• IEC 61010-1
• IEC 61000-4-2
• IEC 61000-4-3
• IEC 61000-4-4
• IEC 61000-4-5
• IEC 61000-4-6
• IEC 61000-4-8
• IEC 61000-4-11
• IEC 60068-2-6
• IEC 60068-2-11
• IEC 60068-2-30
Applications
RS485
Diris A40
Diris A41
485
Main
meter panel
232
PLC
de
CON
TRO
L VISI
ON
on
rvisi
supe
DIR
®
IS
et
CO
®
1
®
TIS
UN
B. 1
per phase
curve
ciel
Logi
diris_581_a_1_gb_cat
PC Currents
CONTROL VISION software
Using electrical parameters mean using
several analogue or digital single-function
products such as ammeters, voltmeters or
wattmeters.
DIRIS A40 and A41, with its six direct
access keys and LCD display, helps you
use all the parameters in an LV or HV
installation. These parameters can be
centralized on a PC or PLC through an
RS485 link using JBUS/MODBUS® or
PROFIBUSr DP protocol. The unit is
designed so that the installer can easily fit
the DIRIS A40 or A41 to the door of a
cabinet. To facilitate and optimize the
operator's work, the DIRIS A40 and A41
uses one of the most functional principles
for integrating communications, metering,
harmonics, analog outputs or alarm relays.
Simply fit a module to the rear of the
casing to add a function.
Measurement in real effective values
(TRMS) of :
• current per phase and instantaneous
neutral, average and maximum values
over a programmable period
• phase-to-neutral and phase-to-phase
voltages
• frequency
• active power on 4 quadrants (±) per
phase and total in instantaneous,
average and maximum values over a
programmable period
• reactive power in 4 quadrants (±) per
phase and total in instant, average and
maximum values over a programmable
period
• apparent power per phase and total in
instantaneous, average and maximum
values over a programmable period
• Power Factor (PF) per phase and total
with inductive or capacitive indication.
• harmonic distortion rate (thd) up to 49 on
the phase to neutral and phase to phase
voltages and the currents (thd 3U, thd
3V, thd 3I, thd In).
Meter
• active power meter on 4 quadrants
• reactive power meter on 4 quadrants
• apparent power meter
• Hour run meter to 1/100th of an hour for
the duration of operation.
SOCOMEC general catalogue
Measurement control & energy management
References
diris_561_a_2_cat
diris_561_a_2_cat
DIRIS A40 / DIRIS A41
DIRIS A40
DIRIS A41
Fourth CTs
Reference
4825 0A40
4825 1A40
Reference
4825 0A41
4825 1A41
Reference
4825 0090
4825 0091
4825 0092
4825 0093
4825 0094
4825 0096
Reference
4825 0090
4825 0091
4825 0092
4825 0093
4825 0094
4825 0096
Basic unit
Auxiliary power supply Us
110 … 400 VAC / 120 … 350 VDC
12 … 48 VDC
Optional Plug & display modules
Plug-in modules
Metering (module 1)
Metering + harmonics (module 2)
Communication RS485 JBUS / MODBUS® (module 3)
Analogue outputs (module 4)
Monitoring or control / command (module 5)
Communication RS485 PROFIBUS® DP
Easy integration of extra functions (maximum 4) by means of modules that the user can snap in at the back of the device at any time.
DIRIS 445 A
Metering
2 configurable outputs impulses (type, weight and duration) for ± kWh, ± kvarh et ± kVAh.
DIRIS ® A40
DIRIS 563 A
DIRIS 446 A
Metering + harmonics
2 configurable outputs impulses (type, weight and duration) for ± kWh, ± kvarh et ± kVAh.
Harmonics analysis by row up to 15 and by phase for 3I, In, 3V and 3U.
DIRIS 447 A
Communication RS485 JBUS / MODBUS®
Communication PROFIBUS® DP
DIRIS 466 A
DIRIS ® A41
1 module RS485 and 1 module protocol PROFIBUS® DP (speed up to 1.5 Mbauds)
Analogue outputs
DIRIS 448 A
DIRIS 564 A
RS485 link with JBUS/MODBUS® protocol (speed up to 38400 bauds)
2 configurable outputs on 3I, In, 3V, 3U, F, ±ΣP, ±ΣQ, ±ΣS et ΣPFL/C.
2 modules may be installed, that 4 analogues ouputs max.
DIRIS 449 A
2 inputs - 2 ouputs
SOCOMEC general catalogue
2 inputs for pulse metering or for input status, or 2 outputs for alarm monitoring or output command. The
monitoring function allows upper and lower alarm threshold to be programmed with time delay, hysteresis
and working method options for the 3I, In, 3U, 3V, ±ΣP, ±ΣQ, ±ΣS, thd I, thd In, thd U.
Maximum connecting possibility of 3 modules (6 inputs or 6 outputs, but only 2 outputs on alarm.)
B. 2
DIRIS® system
DIRIS A40
DIRIS A41
Measurement control & energy management
DIRIS A40 / DIRIS A41
Electrical characteristics
Current measurement on insulated inputs (TRMS)
CT primary
CT secondary
Measurement range
Input consumption
Measurement updating period
Accuracy
Sustained overload
Intermittent overload
Auxiliary power supply
10 000 A
1 and 5
0 … 11 kA
≤ 0,1 VA
1s
0,5 %
6A
10 In for 1 s
Voltage measurement (TRMS)
Direct measurement between phases
Direct measurement between phase and neutral
VT primary
VT secondary
Frequency
Input consumption
Mesaurement updating period
Accuracy
Sustained overload
50 … 700 V~
28 … 404 V~
500 000 V~
60, 100, 110, 173, 190 V~
50 / 60 Hz
≤ 0,1 VA
1s
0,5 %
760 V~
Maximum ratio KI x KV
Limitation for 1A CT
Limitation for 5A CT
10 000 000
10 000 000
Power measurement
Mesaurement updating period
Accuracy
1s
1%
Power factor measurement
Measurement updating period
Accuracy
1s
1%
Frequency measurement
Measurement range
Measurement updating period
Accuracy
45 … 65 Hz
1s
0,1 %
Energy accuracy
Active (according to IEC 61036)
Active (according to IEC 62053-22)
Reactive (according to IEC 62053-23)
B. 3
class 1
class 0,5 S
class 2
AC voltage
AC tolerance
DC voltage
DC tolerance
Frequency
Consumption
120 … 350 V
110 …400 V~
± 10 %
/ 24 … 48 V
- 6 … + 20 %
50 / 60 Hz
≤ 10 VA
Inputs
Number
Power supply
Minimum signal width
Minimum length between 2 impulses
Type
2…6
10 … 30 V
10 ms
18 ms
phototransistor
Outputs (alarms / control)
Number of relays
Type
2
250 V~ - 6 A - 1600 VA
Outputs (pulse)
Number of relays
Type
Max. number of operations
100 V
2
- 0,5 A - 10 VA
≤ 108
Outputs (analogue)
Number of outputs
Type
Range
Charging resistance
Maximum current
2…4
isolated
0 / 4 … 20 mA
600 Ω
30 mA
Communication
Link
Type
Protocol
JBUS/MODBUS® speed
Protocol
PROFIBUS® speed
RS485
2 … 3 wires half duplex
JBUS/MODBUS® in RTU mode
1400 … 38400 bauds
PROFIBUS® DP
9,8 kbauds … 1,5 Mbauds
Operating conditions
Operating temperature
Storage temperature
Relative humidity
- 10 … + 55 °C
- 20 … + 85 °C
95 %
SOCOMEC general catalogue
Measurement control & energy management
DIRIS A40 / DIRIS A41
Overall dimensions
Type
Dimensions H x W x D
Case protection rating
Front protection rating
Display type
Terminal block type
Voltage and other connection section
Current connection section
Weight
92 + 0.8
-0
.0
96
92 + 0.
diris_582_a_1_x_cat
-0 8
.0
panel mounting
96 x 96 x 60 mm
IP 30
IP 52
LCD
fixed or removable
0,2 … 2,5 mm2
0,5 … 6 mm2
400 g
20
60
96
Terminals
diris_569_a_1_x_cat
• DIRIS A40
V1
V2
V3
VN
A U X
S1 S2 S1 S2 S1 S2
I1
I2
S1 - S2 : current inputs
I3
AUX : auxiliary power supply Us
V1, V2, V3 & VN : voltage inputs
DIRIS A40
V2
V3
VN
S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
I3
S1 - S2 : current inputs
IN
AUX : auxiliary power supply Us
V1, V2, V3 & VN : voltage inputs
DIRIS A41
• Communication module
diris_571_a_1_x_cat
A U X
0V -
+
1
0n
R = 120 Ω
RS485
DIRIS A40 / A41
RS485 link
R = terminaison resistance
• Metering module
1
2
OUT 1
DIRIS A40 / A41
3
4
OUT 2
1 - 2 : pulse output no. 1
3 - 4 : pulse output no. 2
• Analogue outputs module
diris_573_a_1_x_cat
V1
diris_572_a_1_x_cat
diris_570_a_1_x_cat
• DIRIS A41
5
6
7
8
0/4-20 mA 0/4-20 mA
OUT 1
OUT 2
DIRIS A40 / A41
5 - 6 : analogue output n° 1
7 - 8 : analogue output n° 2
• 2 inputs and 2 outputs
diris_574_a_1_x_cat
9 10 11 12
OUT 1
OUT 2
A-Cd
A-Cd
1 3 14 15 16
IN 1
IN 2
DIRIS A40 / A41
9 - 10 : output relay n°1
11 - 12 : output relay n°2
13 - 14 : opto input n°1
15 - 16 : opto input n°2
SOCOMEC general catalogue
B. 4
DIRIS® system
DIRIS A40
DIRIS A41
Measurement control & energy management
DIRIS A40 / DIRIS A41
Connections
Recommendation : when disconnecting the DIRIS, it is essential
that the secondaries of each current transformer be shortcircuited.
This can be done automatically using a product from the
SOCOMEC catalogue, the PTI.
Low voltage balanced network for DIRIS A40
• 3/4 wires with 1 CT
• Single phase
• Two phases
1 = Fus. 0.5 A gG / BS88 2A gG
S1
S2
P1
S1
P1
L1
N
S2
S1
S1 S2 S1 S2 S1 S2
I1
I2
I3
V1 V2 V3 VN
diris_394_a_1_gb_cat
diris_393_a_1_gb_cat
V1 V2 V3 VN
L1
L2
S2
1
1
1
diris_392_a_1_gb_cat
1 = Fus. 0.5 A gG / BS88 2A gG
1 = Fus. 0.5 A gG / BS88 2A gG
N
L1
L2
L3
P1
S1 S2 S1 S2 S1 S2
I1
I2
I3
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 1 CT reduces by 0.5 % the accuracy of the
phases whose current is determined by vector calculation.
Low voltage unbalanced network for DIRIS A40
• 3/4 wires with 3 CTs
• 3 wires with 2 CTs
1 = Fus. 0.5 A gG / BS88 2A gG
N
L1
L2
L3
P1
S2
S1
P1
• 3 wires with 2 CTs
1 = Fus. 0.5 A gG / BS88 2A gG
1 = Fus. 0.5 A gG / BS88 2A gG
P1
P1
L1
L2
L3
S2
S1
P1
S1
S1
1
1
S1 S2 S1 S2 S1 S2
I2
I3
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 2 CTs reduces by 0.5 % the accuracy of the
phase whose current is worked out by vector calculation.
diris_397_a_1_gb_cat
diris_396_a_1_gb_cat
diris_395_a_1_gb_cat
1
I1
S2
S2
S1
S2
S1
V1 V2 V3 VN
L1
L2
L3
P1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
The use of 2 CTs reduces by 0.5 % the accuracy of the
phase whose current is worked out by vector calculation.
Low voltage unbalanced network for DIRIS A41
• 4 wires with 4 CTs
1 = Fus. 0,5 A gG
P1
N
L1
L2
L3
S1
P1
S2
S1
P1
S2
S1
diris_575_a_1_x_cat
1
1
1
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 S1 S2
I1
I2
I3
IN
Other information
• Communication via RS485 link
• Connection of voltage transformer for
HV networks
• AC or DC voltage auxiliary power
supply
L1
L2
L3
110 / 400 VAC
120 / 350 VDC
or
12-48 VDC
RS485
+
ON
R
V1 V2 V3 N
diris_400_c_1_gb_cat
0V -
diris_399_b_1_x_cat
diris_398_b_1_x_cat
LIYCY-CY
A U X
It is recommended that the auxiliary power supply be
protected by the use of 500 mA / BS88 2A gG fuses.
B. 5
SOCOMEC general catalogue