036-21537-001-A-0403
®
DESCRIPTION
York Sunline 2000™ Heat Pumps are convertible single package
units. All models have dual refrigerant circuits for efficient part load
operation. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground level
or set on steel beams above a finished roof.
These heat pumps utilize a unique ambient compensated timetemperature defrost system. The defrost module automatically
increases the time interval between defrost cycles as the outdoor
ambient temperature decreases. This helps to eliminate unnecessary and costly defrosts.
TECHNICAL GUIDE
SUNLINE 2000TM
SINGLE PACKAGE
HEAT PUMPS
MODEL BP180
15 NOMINAL TONS
(WORLD 50 HZ)
All units include:
•
•
•
•
•
•
Simplicity Control Board
Powder Paint finish that meets ASTM-B-117 750 hour salt
spray standards
Two-stage cooling provided by dual independent refrigeration
circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats
Hermetically sealed compressors with crankcase heaters
•
Permanently lubricated motors
Bottom or side air discharge configuration capability (field convertible)
Belt Drive Blower Motor
•
•
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
•
Zero-25% fixed air damper with hood
•
•
Copper tube/aluminum fin coils
Easy access to all components
•
•
Rigging holes in base rails for lifting
Single point power connection
•
•
Complete factory package - tested, charged and wired
Agency approvals on all units
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21537-001-A-0403
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . . 9
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 9
LIST OF FIGURES
Fig. #
LIST OF TABLES
Tbl. #
Pg. #
1
CAPACITY RATINGS - COOLING . . . . . . . . . . 11
2
CAPACITY RATINGS - HEATING . . . . . . . . . . . . . . 11
3
COOLING CAPACITIES (M3/S AIRFLOW) 180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4
COOLING CAPACITIES (CFM AIRFLOW) 180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5
HEATING CAPACITIES (M3/S AIRFLOW) 180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6
HEATING CAPACITIES (CFM AIRFLOW) 180 UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Pg. #
1
SUNLINE 2000™ HEAT PUMP . . . . . . . . . . . . . . . . . 11
2
ELECTRONIC THERMOSTAT FIELD WIRING . . . . . 17
3
FIELD WIRING 24 VOLT THERMOSTAT . . . . . . . . . 17
4
FIELD WIRING DISCONNECT . . . . . . . . . . . . . . . . . . 18
5
UNIT DIMENSIONS - 15 TON . . . . . . . . . . . . . . . . . . 21
6
DETAIL “X” ACCY. SIDE SUPPLY & RETURN AIR
OPENINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7
BP180 SUPPLY AIR WITH DOWNFLOW DUCT
APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7
DETAIL “Y” UNIT WITH RAIN HOODS . . . . . . . . . . . 22
8
STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . 16
8
CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 22
9
POWER EXHAUST PERFORMANCE . . . . . . . . . . . 16
9
FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 23
10
BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . 16
10 ROOF CURB DIMENSIONS - 15 TON . . . . . . . . . . . . 23
11
VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . 18
11 ROOF CURB BENEFITS . . . . . . . . . . . . . . . . . . . . . . 24
12
ELECTRICAL DATA -WITHOUT POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . 19
13
ELECTRICAL DATA -WITH POWERED
CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . . 19
14 TYPICAL ROOF-TOP INSTALLATION . . . . . . . . . . . 25
14
ELECTRIC HEAT CORRECTION FACTORS . . . . . 19
15 SIMPLICITY™ CONTROL WIRING DIAGRAM . . . . . 25
15
PHYSICAL DATA - BASIC UNIT . . . . . . . . . . . . . . . 20
16
OPERATING WEIGHTS (KG. / LBS.) . . . . . . . . . . . 20
17
MINIMUM CLEARANCES (MM/IN.) . . . . . . . . . . . . . 21
18
UTILITIES ENTRY DATA (MM/IN.) . . . . . . . . . . . . . . 21
19
FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . 23
12 UNIT AND CURB APPLICATIONS . . . . . . . . . . . . . . . 24
13 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 24
2
Unitary Products Group
036-21537-001-A-0403
PRODUCT NOMENCLATURE
15T Sunline 2000™ Model Number Nomenclature
York Brand
B P 180 C 00 A 7 A AA 1
Product Category
B = Heat Pump, Single Package
Product Generation
1 = First Generation
Product Identifier
P = R-22 High Efficiency Heat Pump
Voltage
7 = 380/415-3-50
Nominal Cooling
Capacity - MBH
180 = 15 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. No field installed electric heat
Electric Heat Options
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Options 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Additional Options
(See Next Page)
Airflow
A = Std Motor/Drive
B = Std Mtr/Drive/Single Input Econo
C = Std Mtr/Drive/Single Input Econo/Power Exhaust*
D = Std Mtr/Drive/Motorized Damper
F = Std Mtr/Drive/4" Filters
G = Std Mtr/Drive/4" Filters/Single Input Econ
H = Std Mtr/Drive/4" Filters/Single Input Econ/Power Exhaust*
L = Std Mtr/Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
M = Std Mtr/Drive/BAS Ready Econ (No BAS Controller)/Power Exhaust w/2" Pleated Filters*
N = Hi Static Drive
P = Hi Static Drive/Single Input Econo
Q = Hi Static Drive/Single Input Econo/Power Exhaust*
R = Hi Static Drive/Motorized Damper
T = Hi Static Drive/4" Filters
U = Hi Static Drive/4" Filters/Single Input Econ
V = Hi Static Drive/4" Filters/Single Input Econ/Power Exhaust*
Y = Hi Static Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Z = Hi Static Drive/BAS Ready Econ (No BAS Controller)/Power Exhaust w/2" Pleated Filters*
Unitary Products Group
3
036-21537-001-A-0403
PRODUCT NOMENCLATURE - CONTINUED
15T Sunline 2000™ Model Number Nomenclature
Additional Options
AA
None
AB
Phase Monitor
AC
Coil Guard
AD
Dirty Filter Switch
AE
Phase Monitor & Coil Guard
AF
Phase Monitor & Dirty Filter Switch
AG
Coil Guard & Dirty Filter Switch
AH
Phase Monitor, Coil Guard, & Dirty Filter Switch
BA
Hinged Filter Door & Tooless Access Panels
BB
Phase Monitor, Hinged Filter Door & Tooless Access Panels
BC
Coil Guard, Hinged Filter Door & Tooless Access Panels
BD
Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BE
Phase Monitor & Coil Guard, Hinged Filter Door & Tooless Access Panels
BF
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BG
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
BH
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
CA
CPC Controller with Dirty Filter Switch & Air Proving Switch
CB
CPC Controller, DFS, APS & Phase Monitor
CC
CPC Controller, DFS, APS & Coil Guard
CD
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE
CPC Controller, DFS, APS & Technicoat Cond. Coil
CF
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ
CPC Controller, DFS, APS & Technicoat Evap. Coil
CK
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
DB
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DC
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
DD
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DE
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
DF
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DG
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DH
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DJ
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
DK
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DL
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DM
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DN
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
DP
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
DQ
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
DR
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
4
Unitary Products Group
036-21537-001-A-0403
Additional Options
EA
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
EB
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EC
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
ED
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EE
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
EF
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EG
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EH
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EJ
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
EK
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EL
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EM
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
EN
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
EP
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
EQ
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
ER
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GA
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
GB
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GC
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
GD
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GE
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
GF
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GG
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GH
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GJ
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
GK
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
GL
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
GN
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
GP
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access
Panels
GQ
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
GR
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless
Access Panels
HA
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JA
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Unitary Products Group
5
036-21537-001-A-0403
Additional Options
JB
Johnson UNT Controller, DFS, APS & Phase Monitor
JC
Johnson UNT Controller, DFS, APS & Coil Guard
JD
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB
Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC
Novar ETC-3 Controller, DFS, APS & Coil Guard
ND
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels
PB
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PC
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels
PD
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PE
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels
PF
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PG
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PH
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PJ
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels
PK
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PL
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PM
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PN
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels
PP
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels
PQ
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels
PR
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access
Panels
TA
Technicoat Condenser Coil
TB
Technicoat Condenser Coil & Phase Monitor
TC
Technicoat Condenser Coil & Coil Guard
TD
Technicoat Condenser Coil & Dirty Filter Switch
TE
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
6
Unitary Products Group
036-21537-001-A-0403
Additional Options
TF
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ
Technicoat Evaporator Coil
TK
Technicoat Evaporator Coil & Phase Monitor
TL
Technicoat Evaporator Coil & Coil Guard
TM
Technicoat Evaporator Coil & Dirty Filter Switch
TN
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS
Technicoat Evaporator & Condenser Coils
TT
Technicoat Evaporator & Condenser Coils & Phase Monitor
TU
Technicoat Evaporator & Condenser Coils & Coil Guard
TV
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA
Technicoat Condenser Coil, Hinged Filter Door & Tooless Access Panels
UB
Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UC
Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UD
Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UE
Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UF
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UG
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UH
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UJ
Technicoat Evaporator Coil, Hinged Filter Door & Tooless Access Panels
UK
Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UL
Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels
UM
Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UN
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UP
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UQ
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UR
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
US
Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Tooless Access Panels
UT
Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Tooless Access Panels
UU
Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Tooless Access Panels
UV
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels
UX
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UY
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
UZ
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels
Unitary Products Group
7
036-21537-001-A-0403
FEATURES
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
•
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models are available with a wide variety of factorymounted options such as phase monitor, dirty filter switch,
and coil guard to make them suitable for almost every application.
All models are available with these “factory mounted” outdoor
air damper options:
•
Single enthalpy economizer
•
Single enthalpy economizer with power exhaust
•
Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
•
All compressors have internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filterdrier, a discharge line high pressure switch and a suction line
with a freezestat and low pressure/loss of charge switch to
protect all system components.
•
Simplicity™ Controls - Simplicity™ control boards
have standardized a number of features previously available only as options or by utilizing additional controls.
•
8
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Electric Heat Operation - All electric heat models (factory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
Unitary Products Group
036-21537-001-A-0403
FACTORY-INSTALLED OPTIONS
•
BAS - See “Additional Options” section in the product
nomenclature.
•
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
HIGH SPEED DRIVE - Includes a belt and blower pulley
upgrade to enhance blower performance.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HINGED FILTER DOOR/”TOOLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed
option.
•
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood and the back-draft
damper need to be assembled and installed in the field.
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool-less operation.
The power exhaust option can only be used on bottom duct configurations.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
FIELD-INSTALLED ACCESSORIES
•
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
•
FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated filters are offered as a factory installed option.
•
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or
you may order the unit with a “non-powered” convenience outlet that can be wired in the field.
•
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
DISCONNECT SWITCH - For heat pump units, a HACR
breaker sized to the name plate max fuse size for the
particular unit is provided. Factory installed option only.
Unitary Products Group
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed option.
•
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
9
036-21537-001-A-0403
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
•
•
10
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
HIGH SPEED DRIVE - A smaller blower pulley and a
shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
WOOD SKID - Allows unit to be handled with 90” forks.
•
CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
Unitary Products Group
036-21537-001-A-0403
_
!#$
`j
%+9%!%:+;<<>
[email protected][email protected]#!$
[
_
[
$
\
]^
FIGURE 1 -
SUNLINE 2000TM HEAT PUMP
TABLE 1: CAPACITY RATINGS - COOLING
DESIGN TEMPERATURES (°C)
MODEL
BP180
COP1
EER2
SENSIBLE
OUTPUT
kW / MBH
LATENT OUTPUT
kW / MBH
17.7
2.50
8.45
38.8 / 132
5.0 / 17
20.4
1.90
6.55
39.0 / 133
0.0 / 0
16.1
2.65
9.05
34.8 / 119
7.9 / 27
TOTAL OUTPUT TOTAL INPUT
kW / MBH
kW
RATING3
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
T1
27 / 19
35 / 24
43.8 / 149
T2
29 / 19
46 / 24
39.0 / 133
T3
21 / 15
27 / 19
42.7 / 146
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
TABLE 2: CAPACITY RATINGS - HEATING
DESIGN TEMPERATURES (°C)
MODEL
BP180
TOTAL OUTPUT
kW / MBH
TOTAL INPUT
kW
COP1
EER2
7/6
47.3 / 161
16.0
2.95
10.1
RATING
POINT
INDOOR
DB / WB
OUTDOOR
DB / WB
High
20 / 12
Low
20 / 12
2/1
27.4 / 93
14.5
1.90
6.45
X-Low
20 / 12
-7 / -8
19.8 / 68
13.3
1.50
5.10
ELECTRIC HEAT3
NOMINAL CAPACITY
kW
15, 27, 40, 54
1. COP = Coefficient of Performance - total output kW divided by the total input kW.
2. EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
3. Heaters available as factory-installed options - all with single point power supply.
Unitary Products Group
11
036-21537-001-A-0403
TABLE 3: COOLING CAPACITIES (M3/S AIRFLOW) - 180 UNIT
AIR ON
INDOOR COIL
m3/s
WB °C
TOTAL1
CAP.
kW
POWER2
INPUT
KW
SENSIBLE CAPACITY1, kW
ENTERING DRY BULB TEMPERATURE, °C
32
30
28
26
24
22
@ 27°C AIR TEMPERATURE ON OUTDOOR COIL
3.40
2.83
2.12
23
60.8
16.3
51
44
38
32
25
-
21
57.4
16.1
57
51
44
38
32
25
19
54.0
15.8
54
54
51
45
38
32
17
52.2
15.7
52
52
52
49
43
36
15
50.5
15.5
50
50
50
47
41
35
23
59.0
16.2
44
39
33
27
22
-
21
55.7
16.0
50
44
39
33
28
22
19
52.4
15.7
52
50
44
39
33
28
17
50.7
15.6
51
51
48
42
37
31
15
48.9
15.4
49
49
49
46
41
35
23
54.2
15.8
37
33
28
24
20
-
21
51.1
15.6
42
38
33
29
25
20
19
48.1
15.4
47
43
38
34
30
25
17
46.5
15.2
47
46
42
37
33
29
15
45.0
15.0
45
45
45
40
36
32
@ 35°C AIR TEMPERATURE ON OUTDOOR COIL
3.40
2.83
2.12
23
58.7
21.0
45
38
32
26
19
-
21
54.4
19.1
53
46
40
34
27
21
19
50.2
17.3
50
50
48
41
35
29
17
49.5
18.5
50
50
50
43
37
31
15
48.8
19.7
49
49
49
45
39
32
23
54.7
17.9
41
35
30
24
19
-
21
50.7
16.3
48
43
37
32
26
20
19
46.8
14.7
47
47
45
39
33
28
17
46.1
15.8
46
46
46
41
35
30
15
45.5
16.8
45
45
45
42
37
31
23
51.6
20.6
32
28
24
19
15
-
21
47.9
18.7
38
34
30
25
21
17
19
44.1
16.9
44
40
35
31
27
22
17
43.5
18.1
44
41
37
32
28
24
15
42.9
19.3
43
42
38
34
29
25
@ 46°C AIR TEMPERATURE ON OUTDOOR COIL
3.40
2.83
2.12
23
50.2
20.3
44
38
31
25
19
-
21
47.3
19.8
47
44
38
31
25
19
19
44.4
19.3
44
44
44
38
32
25
17
43.4
19.3
43
43
43
40
34
27
15
42.3
19.2
42
42
42
39
33
26
23
48.1
20.1
39
34
28
22
17
-
21
45.3
19.6
45
39
34
28
23
17
19
42.5
19.1
43
43
39
34
28
23
17
41.5
19.0
42
42
41
36
30
24
15
40.5
18.9
41
41
41
37
32
26
23
44.8
19.5
32
28
23
19
15
-
21
42.3
19.0
37
32
28
24
19
15
19
39.7
18.6
40
37
33
29
24
20
17
38.7
18.5
39
39
34
30
26
21
15
37.8
18.4
38
38
36
32
27
23
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
12
Unitary Products Group
036-21537-001-A-0403
TABLE 4: COOLING CAPACITIES (CFM AIRFLOW) - 180 UNIT
AIR ON
INDOOR COIL
CFM
WB °F
TOTAL1
CAP.
MBH
POWER2
INPUT
KW
SENSIBLE CAPACITY1, MBH
ENTERING DRY BULB TEMPERATURE, °F
90
86
82
79
75
72
@ 80°F AIR TEMPERATURE ON OUTDOOR COIL
7200
6000
4500
73
207
16.3
173
151
129
108
86
-
70
196
16.1
195
173
152
130
108
87
66
184
15.8
184
184
174
152
130
109
63
178
15.7
178
178
178
167
145
123
59
172
15.5
172
172
172
161
140
118
73
201
16.2
151
132
113
94
75
-
70
190
16.0
170
151
132
113
94
75
66
179
15.7
179
170
151
132
113
94
63
173
15.6
173
173
164
145
126
107
59
167
15.4
167
167
167
158
139
120
73
185
15.8
127
112
97
82
68
-
70
175
15.6
143
129
114
99
84
70
66
164
15.4
160
145
131
116
101
86
63
159
15.2
159
157
142
127
112
98
59
153
15.0
153
153
153
138
123
109
@ 95°F AIR TEMPERATURE ON OUTDOOR COIL
7200
6000
4500
73
200
21.0
153
131
109
88
66
-
70
186
19.1
179
158
136
114
93
71
66
171
17.3
171
171
163
141
120
98
63
169
18.5
169
169
169
147
126
104
59
167
19.7
167
167
167
154
132
110
73
187
17.9
140
121
102
83
64
-
70
173
16.3
165
146
127
108
89
70
66
160
14.7
160
160
152
133
114
95
63
157
15.8
157
157
157
139
120
101
59
155
16.8
155
155
155
145
126
107
73
176
20.6
110
96
81
66
51
-
70
163
18.7
130
115
101
86
71
56
66
151
16.9
150
135
121
106
91
76
63
148
18.1
148
140
125
110
96
81
59
146
19.3
146
145
130
115
100
86
73
171
20.3
150
129
107
85
64
-
70
161
19.8
161
151
129
107
86
64
66
152
19.3
152
152
151
129
108
86
63
148
19.3
148
148
148
136
114
93
59
144
19.2
144
144
144
134
112
90
73
164
20.1
133
114
95
76
57
-
70
155
19.6
153
134
115
96
77
58
66
145
19.1
145
145
134
115
96
77
63
142
19.0
142
142
140
121
102
83
59
138
18.9
138
138
138
127
108
89
73
153
19.5
109
94
80
65
50
-
70
144
19.0
125
111
96
81
66
52
66
135
18.6
135
127
112
98
83
68
63
132
18.5
132
132
117
103
88
73
59
129
18.4
129
129
123
108
93
78
@ 115°F AIR TEMPERATURE ON OUTDOOR COIL
7200
6000
4500
1. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance
Table for the kW of the supply air blower motor.
2. These ratings include the outdoor fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
13
036-21537-001-A-0403
TABLE 5: HEATING CAPACITIES1 (M3/S AIRFLOW) - 180 UNIT
3
m /s
2.12
2.83
3.40
CAP.
RETUR (C)
N AIR PWR.
(P)
ºC
(KW)
OUTDOOR AIR TEMPERATURE, ºC (72% RH)
-20
-15
-10
-5
0
5
10
15
20
13
(C)
(P)
13.3
8.8
17.1
9.4
21.8
10.1
27.4
10.8
33.8
11.5
41.0
12.3
49.2
13.2
58.2
14.1
68.1
15.1
20
(C)
(P)
12.7
9.0
16.2
9.7
20.5
10.6
25.5
11.4
31.4
12.2
38.6
13.0
46.0
13.9
54.2
14.9
63.0
15.9
27
(C)
(P)
12.1
9.2
15.3
9.9
19.1
10.7
23.8
11.5
29.1
12.3
35.1
13.2
41.8
14.1
49.2
15.1
57.1
16.1
13
(C)
(P)
13.7
8.3
17.6
8.8
22.4
9.4
28.1
10.1
34.6
10.8
42.1
11.6
50.4
12.4
59.7
13.2
69.8
14.2
20
(C)
(P)
13.2
8.9
16.9
9.6
21.5
10.3
26.9
11.0
33.3
11.8
41.1
12.7
49.3
13.6
58.3
14.6
68.2
15.6
27
(C)
(P)
12.8
9.1
16.3
9.9
20.6
10.6
25.8
11.5
31.9
12.4
38.9
13.4
46.8
14.4
55.6
15.4
65.3
16.5
13
(C)
(P)
14.0
7.8
18.0
8.3
22.9
8.9
28.8
9.5
35.5
10.1
43.2
10.9
51.8
11.6
61.2
12.4
71.6
13.3
20
(C)
(P)
13.8
8.6
17.7
9.2
22.6
9.9
28.4
10.7
35.3
11.5
43.8
12.4
52.7
13.3
62.7
14.3
73.7
15.3
27
(C)
(P)
13.5
9.0
17.3
9.8
22.1
10.6
28.0
11.5
35.0
12.5
43.1
13.5
52.4
14.6
62.9
15.8
74.6
17.0
1. The MBH and kW values do not include the supply air blower.
TABLE 6: HEATING CAPACITIES1 (CFM AIRFLOW) - 180 UNIT
CFM
4500
6000
7200
OUTDOOR AIR TEMPERATURE, ºF (72% RH)
RETURN AIR
ºF
CAP. (MBH)
PWR. (kW)
-4
5
14
23
32
41
50
59
68
55
MBH
kW
45
8.8
58
9.4
74
10.1
93
10.8
115
11.5
140
12.3
168
13.2
199
14.1
232
15.1
68
MBH
kW
43
9.0
55
9.7
70
10.6
87
11.4
107
12.2
132
13.0
157
13.9
185
14.9
215
15.9
80
MBH
kW
41
9.2
52
9.9
65
10.7
81
11.5
99
12.3
120
13.2
143
14.1
168
15.1
195
16.1
55
MBH
kW
47
8.3
60
8.8
76
9.4
96
10.1
118
10.8
144
11.6
172
12.4
204
13.2
238
14.2
68
MBH
kW
45
8.9
58
9.6
73
10.3
92
11.0
114
11.8
140
12.7
168
13.6
199
14.6
233
15.6
80
MBH
kW
44
9.1
55
9.9
70
10.6
88
11.5
109
12.4
133
13.4
160
14.4
190
15.4
223
16.5
55
MBH
kW
48
7.8
62
8.3
78
8.9
98
9.5
121
10.1
147
10.9
177
11.6
209
12.4
244
13.3
68
MBH
kW
47
8.6
60
9.2
77
9.9
97
10.7
120
11.5
150
12.4
180
13.3
214
14.3
251
15.3
80
MBH
kW
46
9.0
59
9.8
76
10.6
96
11.5
120
12.5
147
13.5
179
14.6
215
15.8
254
17.0
1. The MBH and kW values do not include the supply air blower.
14
Unitary Products Group
036-21537-001-A-0403
TABLE 7: BP180 SUPPLY AIR WITH DOWNFLOW DUCT APPLICATIONS
AIRFLOW
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
2.10 m3/s
2.45 m3/s
2.80 m3/s
3.10 m3/s
3.40 m3/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
STANDARD DRIVE (m3/s)
845
6.0
173
1.8
2.2
138
2.2
2.6
83
2.6
3.1
18
3.0
3.5
-
-
-
885
5.0
208
1.9
2.3
172
2.3
2.8
115
2.7
3.3
49
3.1
3.7
-
-
-
925
4.0
245
2.0
2.4
208
2.4
2.9
149
2.9
3.4
82
3.3
3.9
-
-
-
960
3.0
281
2.1
2.6
242
2.6
3.1
182
3.0
3.6
114
3.4
4.1
30
3.8
4.6
1000
2.0
323
2.3
2.7
283
2.7
3.2
222
3.2
3.8
152
3.6
4.3
67
4.0
4.8
1040
1.0
369
2.4
2.9
327
2.9
3.4
264
3.3
4.0
193
3.8
4.5
107
4.2
5.1
357
2.4
2.8
316
2.8
3.4
253
3.3
3.9
183
3.7
4.5
97
4.2
5.0
HIGH SPEED DRIVE (m
1030
3/s)
6.0
1070
5.0
405
2.5
3.0
362
3.0
3.6
298
3.5
4.2
226
3.9
4.7
-
-
-
1115
4.0
461
2.7
3.2
416
3.2
3.8
351
3.7
4.4
278
4.2
5.0
-
-
-
1155
3.0
514
2.9
3.4
468
3.4
4.0
401
3.9
4.7
-
-
-
-
-
-
1200
2.0
577
3.1
3.7
529
3.6
4.3
461
4.1
5.0
-
-
-
-
-
-
1240
1.0
636
3.3
3.9
587
3.8
4.5
-
-
-
-
-
-
-
-
-
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
4450 CFM
5190 CFM
5930 CFM
6565 CFM
7200 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
STANDARD DRIVE (CFM)
845
6.0
0.7
2.4
2.2
0.6
2.9
2.6
0.3
3.5
3.1
0.1
4.0
3.5
-
-
-
885
5.0
0.8
2.6
2.3
0.7
3.1
2.8
0.5
3.7
3.3
0.2
4.2
3.7
-
-
-
925
4.0
1.0
2.7
2.4
0.8
3.3
2.9
0.6
3.8
3.4
0.3
4.4
3.9
-
-
-
960
3.0
1.1
2.9
2.6
1.0
3.4
3.1
0.7
4.0
3.6
0.5
4.6
4.1
0.1
5.2
4.6
1000
2.0
1.3
3.0
2.7
1.1
3.6
3.2
0.9
4.2
3.8
0.6
4.8
4.3
0.3
5.4
4.8
1040
1.0
1.5
3.2
2.9
1.3
3.8
3.4
1.1
4.5
4.0
0.8
5.1
4.5
0.4
5.7
5.1
HIGH SPEED DRIVE (CFM)
1030
6.0
1.4
3.2
2.8
1.3
3.8
3.4
1.0
4.4
3.9
0.7
5.0
4.5
0.4
5.6
5.0
1070
5.0
1.6
3.4
3.0
1.5
4..0
3.6
1.2
4.7
4.2
0.9
5.3
4.7
-
-
-
1115
4.0
1.9
3.6
3.2
1.7
4.3
3.8
1.4
5.0
4.4
1.1
5.6
5.0
-
-
-
1155
3.0
2.1
3.9
3.4
1.9
4.5
4.0
1.6
5.2
4.7
-
-
-
-
-
-
1200
2.0
2.3
4.1
3.7
2.1
4.8
4.3
1.8
5.5
5.0
-
-
-
-
-
-
1240
1.0
2.6
4.4
3.9
2.4
5.1
4.5
-
-
-
-
-
-
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 8 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
15
036-21537-001-A-0403
TABLE 8: STATIC RESISTANCES1
RESISTANCE, IWG/Pa
m3/s (CFM)
DESCRIPTION
15 TON
2.12 (4500)
2.83 (6000)
3.39 (7200)
WET INDOOR COIL
ELECTRIC HEAT OPTIONS
0.1/25
0.1/25
0.1/25
18 KW
0.1/25
0.1/25
0.1/25
36 KW
0.1/25
0.2/50
0.3/75
54 KW
0.2/50
0.3/75
0.4/100
72 KW
0.2/50
0.4/100
0.6/150
0.1/25
0.1/25
0.1/25
0.1/25
0.2/50
0.3/75
ECONOMIZER OPTION
HORIZONTAL DUCT CONNECTIONS
2
1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for
exception.)
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values
on the respective unit’s blower performance table.
TABLE 9: POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETURN DUCTWORK, IWG/Pa
MOTOR
SPEED
0.2/50
0.3/75
0.4/100
0.5/125
0.6/150
m3/s (CFM)
KW
m3/s (CFM)
KW
m3/s (CFM)
KW
m3/s (CFM)
KW
m3/s (CFM)
KW
HIGH*
2.47 (5250)
0.83
2.12 (4500)
0.85
1.98 (4200)
0.88
1.77 (3750)
0.93
1.41 (3000)
0.99
MEDIUM
2.31 (4900)
0.77
1.84 (3900)
0.79
1.65 (3500)
0.82
1.37 (2900)
0.85
-
-
LOW
2.07 (4400)
0.72
1.74 (3700)
0.74
1.41 (3000)
0.78
-
-
-
-
* Factory Setting
Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
TABLE 10: BLOWER MOTOR AND DRIVE DATA
UNIT
SIZE
(MBH)
ADJUSTABLE MOTOR PULLEY2
FIXED BLOWER PULLEY
kW/HP
FRAME
SIZE
845 - 1040
3.0/4.0
184T
83
109 - 135 /
4.3 - 5.3
29 / 1-1/8
1VP56
188 / 7.4
HIGH
SPEED 1030 - 1240 3.7/5.0
DRIVE
184T
84
124-150
4.9-5.9
29 / 1-1/8
1VP62
175 / 6.9
STD
DRIVE
180
MOTOR1
BLOWER
RANGE
(RPM)
EFF. PITCH DIA.
BORE
(%)
(mm / in.) (mm / in.)
BELT
(NOTCHED)
DESIGNATION
PITCH
LENGTH
(mm/in.)
DESIGNATION
QTY.
25 / 1
BK80
1773 / 69.8
BX68
1
25 / 1
BK75
1773 / 69.8
BX68
1
DESIG- PITCH DIA.
BORE
NATION (mm / in.) (mm / in.)
1. All motors are 1450 RPM, have sold bases and a 1.10 service factor.
2. Do NOT close this pulley below 1 turn open.
16
Unitary Products Group
036-21537-001-A-0403
U N IT T E R M IN A L S
S T R IP T B 1
T H E R M O S T A T *
T E R M IN A L S
R C
W
R H
W
Y 1
2
Y 1
Y 2
1
O C C
R E M O T E
M IN P O S
2
G
C
Y 2
X 1
X
X 3
R
X 4
A 1
A 2
The thermostat must provide a “G” signal
when there is a call for “W1.”The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for “W2” during the antishort-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for “W2.”
G
W
W
1
S D
†
†
C
T
2 4
V o lt
T r a n s fo r m e r
T
T O R E M O T E S E N S O R
2 E T 0 4 7 0 1 3 2 4 IF U S E D
†
* E le c tr o n ic p r o g r a m m a b le T h e r m o s ta t 2 E T 0 7 7 0 0 1 0 0 2 4 ( in c lu d e s s u b b a s e ) .
T e r m in a ls A 1 a n d A 2 p r o v id e a r e la y o u tp u t to c lo s e th e o u td o o r
e c o n o m iz e r d a m p e r s w h e n th e th e r m o s ta t s w itc h e s to th e s e t- b a c k p o s itio n .
FIGURE 2 -
ELECTRONIC THERMOSTAT FIELD WIRING
NOTE: This unit does NOT REQUIRE a heat pump thermostat. It is designed to work with a standard two-stage
cool, two-stage heat thermostat; however, the thermostat must provide a “G” signal when there is a call
for “W1”.
T -S T A T
W 1
W 1
W 2
W 2
Y 1
Y 1
G
G
Y 2
O C C
R E M O T E
M IN P O S
C
R H
U N IT C O N T R O L
B O A R D
Y 2
R C
X
The thermostat must provide a “G” signal
when there is a call for “W1.”The unit control
board will energize the indoor blower when
the compressors are energized; however, if
the thermostat calls for “W2” during the antishort-cycle delay, the electric heat (when
installed) will be energized immediately
upon the call for “W2.”
R
S D
C
FIGURE 3 -
FIELD WIRING 24 VOLT THERMOSTAT
Unitary Products Group
17
036-21537-001-A-0403
T E R M IN A L B L O C K T B 1
F A C T O R Y O R F IE L D
S U P P L IE D D IS C O N N E C T
G R O U N D
L U G
T H R
P H A
P O W
S U P
FIGURE 4 -
E E
S E
E R
P L Y
FIELD WIRING DISCONNECT
TABLE 11: VOLTAGE LIMITATIONS
POWER SUPPLY
380/415-3-50
Note 1:
Note 2:
18
VOLTAGE
MIN.
MAX.
342
456
Maximum HACR breaker of the same amp size is
acceptable.
Only 18kW of the 36 or 54kW, or only 36kW of the 72kW
electric heat can be simultaneously energized with the
mechanical heating. The full heater kW operates only if
both compressors are locked out.
Unitary Products Group
036-21537-001-A-0403
TABLE 12: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
VOLTAGE
TONNAGE
RLA
EACH
LRA
EACH
HEATER OPTION
ID
OD FAN
CONV
BLOWER
MOTORS
OUTLET
2
MOTOR
FLA EACH
AMPS MODEL KW STAGES AMPS
FLA
-
380
12.8
128
2.1
8.3
0.0
BP180
415
12.8
128
2.1
8.3
0.0
0.0
-
-
MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
41.3
50
E18
11.3
1
17.1
62.8
70
E36
22.6
2
34.3
62.8
60
E54
33.8
2
51.4
74.6
80
E72
45.1
2
68.6
96.0
100
-
0.0
-
-
41.3
50
E18
13.5
1
18.7
64.8
70
E36
26.9
2
37.4
64.8
70
E54
40.4
2
56.2
80.6
90
E72
53.8
2
74.9
88.1
100
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 13: ELECTRICAL DATA -WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
VOLTAGE
TONNAGE
380
RLA
EACH
12.8
LRA
EACH
128
HEATER OPTION
ID
CONV
OD FAN
BLOWER
MOTORS
OUTLET
2
MOTOR
FLA EACH
AMPS MODEL KW STAGES AMPS
FLA
2.1
8.3
6.3
BP180
415
12.8
128
2.1
8.3
6.3
MAX.
MIN.
FUSE/
CIRCUIT
1
AMPACITY BRKR
SIZE
(AMPS)
(AMPS)
-
0.0
-
-
47.6
60
E18
11.3
1
17.1
69.1
70
E36
22.6
2
34.3
69.1
70
E54
33.8
2
51.4
82.4
90
E72
45.1
2
68.6
103.9
110
-
0.0
-
-
47.6
60
E18
13.5
1
18.7
71.1
80
E36
26.9
2
37.4
71.1
80
E54
40.4
2
56.2
88.5
90
E72
53.8
2
74.9
94.4
100
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
TABLE 14: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
KW CAP. MULTIPLIER
380
380
0.627
415
415
0.75
Unitary Products Group
19
036-21537-001-A-0403
TABLE 15: PHYSICAL DATA - BASIC UNIT
MODEL
SUPPLY AIR
BLOWER
BP180
CENTRIFUGAL BLOWER
(Dia. x Wd. mm.)
(Dia. x Wd. in.)
FAN MOTOR (KW/HP)
3.0/4
ROWS DEEP
4
FINS PER INCH
13
INDOOR COIL
FACE AREA (Sq. M./Sq. Ft.)
OUTDOOR
FAN
(Two Per Unit)
(Each)
762/30
FAN MOTOR (KW/HP)
(Each)
0.8/1.25
NOM. M3/S/CFM TOTAL
(Each)
3.06/6500
ROWS DEEP
3
FINS PER INCH
15
FACE AREA (Sq. M./Sq. Ft.)
3.35/36.0
7-1/2 TON SCROL
2
COMPRESSOR
(Qty. Per Unit)
CHARGE
1.45/15/5
PROPELLER DIA. (mm/in.)
OUTDOOR COIL
AIR
FILTERS
381 x 381
15 x 15
QUANTITY PER UNIT (457 X 610 X 51 mm) / (18" X 24" X 2")
5
TOTAL FACE AREA (Sq. M./Sq. Ft.)
1.4/15.0
REFRIGERANT 22
SYSTEM NO. 1 (Kg./Lbs.)
10.2/22.5
SYSTEM NO. 2 (Kg./Lbs.)
10.2/22.5
TABLE 16: OPERATING WEIGHTS (KG. / LBS.)
MODEL
Basic Unit
BP180
BP (Heat Pump)
862/1900
Economizer
73/160
Economizer with Power Exhaust
111/245
Motorized Damper
68/150
Options
Electric Heater
Accessories
20
18 KW
11/25
36 KW
14/30
54 KW
16/35
72 KW
18/40
Roof Curb
79175
Barometric Damper
20/45
Wood Skid
91/200
Unitary Products Group
036-21537-001-A-0403
All dimensions are in inches. They are
subject to change without notice. Certified dimensions will be provided upon
request.
FIGURE 5 - UNIT DIMENSIONS - 15 TON
TABLE 17: MINIMUM CLEARANCES (MM/IN.)
LOCATION
Front
CLEARANCE
914 mm/36”
Back
610 mm/24” (Less Economizer)
1245 mm/49” (With Economizer
Left Side (Filter Access)
610 mm/24” (Less Economizer)
914 mm/36” (With Economizer)
Right Side (Cond. Coil)
914 mm/36”
1
0 mm/0”
Below Unit
Above Unit2
1829 mm/72” With 914 mm/36”
Maximum Horizontal Overhang
(For Condenser Air Discharge)
TABLE 18: UTILITIES ENTRY DATA (MM/IN.)
HOLE
A
B
OPENING SIZE (DIA.)
28.6 mm/1-1/8” KO
19.1 mm/3/4” NPS (Fem.)
92.1 mm/3-5/8” KO
76.2 mm/3” NPS (Fem.)
USED FOR
Control Wiring
Power Wiring
Front
Bottom
Front
Bottom
NOTE: All entry holes should be field sealed to prevent rain
water entry into building.
1. Units (applicable in U.S.A. only) may be installed on
combustible floors made from wood or class A, B or C
roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
NOTE: Units and ductwork are approved for zero clearance
to combustible materials when equipped with electric heaters.
Unitary Products Group
21
036-21537-001-A-0403
DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for connecting side ducts.
For bottom duct applications:
1. Remove the side panels from the supply and return
air compartments to gain access to the bottom
supply and return air duct covers.
2. Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
3. Replace the side supply and return air compartment
panels.
For side duct applications;
1. Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2. Connect ductwork to the duct flanges on the rear of
the unit.
OUTDOOR AIR PANEL SIZE
15 TON UNITS 21-1/2" X 43"
FIGURE 6 - DETAIL “X” ACCY. SIDE SUPPLY & RETURN AIR OPENINGS
FIGURE 7 - DETAIL “Y” UNIT WITH RAIN HOODS
FIGURE 8 - CENTER OF GRAVITY
22
Unitary Products Group
036-21537-001-A-0403
B
D
C
A
A
FRONT
C
FRONT
B
D
6 Point Loads
4 Point Loads
FIGURE 9 -
E
F
FOUR AND SIX POINT LOADS
TABLE 19: FOUR AND SIX POINT LOADS
4 - POINT LOADS (Kg. / Lbs.)
UNIT
180
TOTAL
A
B
C
D
952 / 2100
233 / 513
231 / 510
253 / 558
253 / 559
NOTE: These weights are with economizer and 72 kW electric heat.
6 - POINT LOADS (Kg. / Lbs.)
UNIT
180
TOTAL
A
B
C
D
E
F
952 / 2100
155 / 342
162 / 358
161 / 357
164 / 372
161 / 356
155 / 341
NOTE: These weights are with economizer and 72 kW electric heat.
FIGURE 10 - ROOF CURB DIMENSIONS - (180 & 240 UNITS)
Unitary Products Group
23
036-21537-001-A-0403
FIGURE 11 - ROOF CURB BENEFITS
FIGURE 12 - UNIT AND CURB APPLICATION
FIGURE 13 - TYPICAL APPLICATIONS
24
Unitary Products Group
036-21537-001-A-0403
FIGURE 14 - TYPICAL ROOF-TOP INSTALLATION
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
W1
W1
W2
1
W2
Y1
Y1
Y2
G
2
OCC
P
G
P1
R
Y2
Smoke
Detector
X
C
R
4
SD
RC
OCC
X
5
C
R
3
SD
SD
6
Jumper
C
24 VAC
Class 2
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
1
Second stage heating not required on single stage heating units.
2
Second stage cooling not required on single stage cooling units.
3
Jumper is required if there is no Smoke Detector circuit.
4
Jumper is required for any combination of R, RC, or RH.
5
OCC is an output from the thermostat to indicate the Occupied condition.
6
X is an input to the thermostat to display Error Status conditions.
FIGURE 15 - SIMPLICITY™ CONTROL WIRING DIAGRAM
Unitary Products Group
25
036-21537-001-A-0403
26
Unitary Products Group
036-21537-001-A-0403
Unitary Products Group
27
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products Group 2003. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21537-001-A-0403
Supersedes: Nothing
Norman
OK
73069