D-9107RExd Digital Flame Proof Dual IR Flame Detector

D-9107RExd Digital Flame Proof Dual IR Flame Detector
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
CONTENTS
1 Overview ..................................................................................................................... 1
2 Specification ............................................................................................................... 1
3 Construction and Operation Principle..................................................................... 2
3.1 Construction .......................................................................................................... 2
3.2 Adjustment Frame ................................................................................................. 3
3.3 Operation Principle................................................................................................ 3
4 Installation and Connection...................................................................................... 3
4.1 Installation ............................................................................................................. 3
4.2 Connection ............................................................................................................ 4
5 Testing ......................................................................................................................... 6
6 Operation .................................................................................................................... 6
7 Application .................................................................................................................. 7
8 Troubleshooting ......................................................................................................... 7
9 Maintenance ............................................................................................................... 8
10 Caution ...................................................................................................................... 8
11 Accessories .............................................................................................................. 8
Page I
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
1 Overview
 Dual-band infrared light detection for fire alarm.
 Sensitive to flame from material containing carbon. Suitable for fire starting from
flame in large indoor or outdoor areas.
 Addressable (connecting fire alarm control panel) and non-addressable (through
relay contact) working modes optional.
 Flame-proof. Applicable to either commercial or hazardous industrial areas, such
as explosive Zone 1 and 2, and Zone 21 and 22 with flammable dust.
2 Specification
 Operating Voltage:
 Loop: Range 16V~28V
 24VDC: Range 20VDC~28VDC
 Operating Current:
 Loop: Standby current≤ 1mA, alarm current≤1mA, Maximum Consumption
28mW
 24VDC: Standby current ≤ 20mA, alarm current ≤ 30mA, Maximum
Consumption:840mW
 Sensitivity Level:
The detector has three sensitivity levels. The factory default sensitivity is Level I,
which can be reduced in field using GST handheld programmer.
 Detection Distance:
 Sensitivity Level I: 25m (furthest)
 Sensitivity Level II: 17m
 Sensitivity Level III: 12m
Test Fire: 33cm×33cm n-heptane fire.
The correlation between detection distance and angle is shown in Fig. 1. The
shaded area is detectable.
The semicircle in the figure represents the detection distance in percentage.
furthest
15 o
0o
15o
30 o
30o
45o
100%
45o
50%
Detector
Fig. 1
Page 1
50%
100%
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
Note: The detection angle to all directions are the same. Fig. 1 only gives a section
illustration.
 Response Spectral Range: 4.4μ m±0.5μ m
 Response Time ≤30s
 Indicators:
 Red LED: Flashes periodically in standby state, and steadily illuminates in fire
alarm.
 Yellow LED: Off in standby state, and steadily illuminates in fault.
 Contact Output:
 Fire alarm contact: 1A/25VDC, normally closed in fire alarm, and normally
open in other states.
 Fault contact: 1A/25VDC, normally open in fault state, and normally closed in
other states.
 Operating Environment:
Temperature: -20℃~+55℃
Relative Humidity: ≤95%, non-condensing
 Ingress Protection: IP66
 Dimensions: 166mm×235mm×199mm (with adjustment frame)
 Installation Hole Space: 125.5mm×80mm
 Material and Color of Enclosure: Stainless steel, metallic grey
 Weight:
 Detector: 4.8kg
 Adjustment frame: 1.3kg
 Explosion-proof Mark: Exd IIC T6 Gb/DIP A21 TA,T6
 Explosion-proof Certificate Number: CE11.1229
 Standard: GB 3836.1-2010,GB 3836.2-2010,GB 12476.1-2000,EN54-10
3 Construction and Operation Principle
3.1 Construction
The construction of the detector is shown in Fig. 2.
Adjustment
Frame
Securing Bolt
Fire LED
Detection
Window
Fault LED
Axes
Cap
Earth
Page 2
Cable Junction
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
Fig. 2
3.2 Adjustment Frame
The adjustment frame can rotate by 60°around the axe, as shown in Fig. 3.
Fig. 3
3.3 Operation Principle
The detector uses two pyroelectric infrared sensors to detect the change of light signal
of flame and background light signal at two bands of infrared spectrum through two
signal processing channels. Its microprocessor analyzes the signal through the flame
channel and background channel to judge if there is flame.
4 Installation and Connection
4.1 Installation
Before installation, check first if the enclosure is in good condition with all necessary
markings. Then set the detector address and sensitivity level (please refer to Section 6
Operation), and then install it according to Fig. 4.
M
Base
Wall
Frame
lt
Bo
p4
S te
p1
Ste
Page 3
Step 3
p2
Ste
p
ca
et
ck
so 25
n ×
go 8
xa s M
h e r ew
sc
cover
rew
c
5s
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
Fig. 4
Step 1: Install the adjustment frame.
Fix the adjustment frame securely on the wall using 4 M6 expansion bolts.
Step 2: Install the base.
Remove the protective cover (Fig. 5) from the base leaving the screws and washer with
the base, and install the base onto the adjustment frame using a M5 screw.
Aligning Element
Protective Cover
Fig. 5
Step 3: Cable connection. Pleaser refer to “Connection” section.
Step 4: Install the cover. Remove the protective washer, insert the ribbon cable to XT3 of
the base circuit, and then install the enclosure onto the base with reference to the
aligning element with the U-shaped slot and secure the four screws using an Allen key.
Note: The base and enclosure shall be securely installed. There shall not be any
scratches or cracks on the detection window. The enclosure shall be earthed.
Protective washer
U-shaped slot
Fig. 6
Finally, adjust the frame to make sure the detection window is facing the protected area,
and fix the screws after adjustment.
Note: The detector shall be installed in compliance with relative installation
codes and make sure the enclosure is in good condition. Please always contact
your installer in case of any off-normal condition. Never conduct maintenance or
repair with the power on.
4.2 Connection
(1) It is recommended to use multi-core copper cable with core cross section≥
Page 4
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
1.0mm 2, and external diameter 8mm~10mm.
(2) The cable shall meet field requirements on resistance to explosion, heat,
corrosion and fire.
(3) The cable layout for hazardous explosive area must comply with
corresponding codes. The connecting cable can be copper-core screened
cable or explosion-proof hose with suitable junction thread matching with the
detector taper thread of the cable nut (Fig. 7).
(4) The cable must enter the detector through the junction nut, and there must be
an O-ring, a seal and a washer, as shown in Fig. 7.
Fig. 7
(5) Connect the screen cover of the cable with the protective earth inside the
detector.
(6) Terminals on the base are shown in Fig. 8.
FT1 FT2 AL1 AL2
Fig. 8
 Z1, Z2: Communication loop input from fire alarm control panel. Polarity
insensitive.
 D1, D2: 24VDC power input. Polarity insensitive.
 AL1, AL2: Fire alarm contact output. Normally open contact. Closed in fire
alarm.
 FT1, FT2: Fault contact output. Normally closed contact. Open in fault.
The loop cable and the power shall enter the detector through a cable nut, and the
signal cable through another cable nut (Fig. 9). If no signal cable is needed, the cable
inlet shall be inserted with an end cap with O-ring.
If Z1 and Z2 does not connect with the loop, they must be connected with D1 and D2
polarity-insensitively.
Page 5
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
Loop and 24VDC cable inlet
Contact Signal cable outlet
Fig. 9
(7) After connection, screw down the cable nut.
5 Testing
Warning: Power up only after all detectors are installed.
1 The detector must be tested after installation and regular maintenance.
2 Tests:
(1) Connect the detector to loop and 24VDC, it should be able to be registered by
the control panel, and the red LED should flash periodically. After the detector
is powered up for 20 minutes, igniting an infrared light source at 1.5m distance
in front of it, it shall report a fire alarm to the control panel within 30s and light
the fire LED, and it should be reset from the control panel to standby state.
(2) Connect the detector to 24VDC only, the red LED should flash periodically in
standby state. After the detector is powered up for 20 minutes, igniting an
infrared light source at 1.5m distance in front of it, it shall give fire signal within
30s and light the fire LED.
3 After testing, reset the detector from control panel if it connects to the loop. If it’s not
connected to loop, disconnect 24VDC power and re-power it up. Notify the proper
authorities the system is back in operation.
4 If a detector fails in testing, clean and test it again. If it still fails, return it for repair.
6 Operation
1
2
The address and sensitivity level can be programmed using a handheld
programmer. Please refer to the manual for the programmer.
The range of address is 1~242.
For setting sensitivity level, number 1 represents sensitivity level I, number 2 for
level II and number 3 for level III.
If the detector connects with the loop, it needs to be programmed with an address
Page 6
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
to be identified by the control panel. If it doesn’t connect with the loop, no address
setup is required. But terminal Z1 and Z2 must be connected with D1 and D2 in an
polarity-insensitive way.
7 Application
1
Fig. 10 shows the connection of the detector with GST fire alarm control panel.
Fire Alarm Control Panel
2
Infrared Flame Detector
Power
FT1 FT2 AL1 AL2 D1 D2 Z1 Z2
Loop
Fig. 10
Connection of the detector with control panels of other suppliers are shown in Fig.
11.
Infrared Flame Detector
Fault Signal
Input
Fire Alarm
Signal Input
FT1 FT2 AL1 AL2 D1 D2 Z1 Z2
Power
Control Unit
Fig. 11
8 Troubleshooting
Possible Problem
The indicator doesn’t flash
Incorrect contact signal
Resolution
Check the cable connection. If there is no problem,
replace the detector.
Page 7
D-9107RExd
Digital Flame Proof Dual IR Flame Detector
Installation and Operation Manual
Registration failure
Other problems
9 Maintenance
1
2
3
The detection window should be cleaned at least every three months.
Before cleaning, notify relative departments that the system is undergoing
maintenance and will be out of service. Disable the zone or system in maintenance
to avoid unwanted alarms.
After cleaning, install the detector back and test again.
10 Caution
(1) The detector should be handled with care during maintenance to avoid damage.
(2) Installation and maintenance should strictly comply with relative codes for
explosive and hazardous areas.
(3) Never open the cover for maintenance in field.
(4) The enclosure must be earthed.
(5) False alarms may occur if there is arc welding operation within 5 meters to the
detector.
(6) The following places are not suitable for the detector:
 Where flameless fires are to be expected.
 Where intensive smoke spreads before flames.
 Where the "view" of the detector is easy to be obscured.
 Where the sun can directly shine the detection window.
 Where the detector may encounter frequent vibration.
11 Accessories





1 installation and operation manual
4 M6×60 expansion bolts
1 M5×10 screws
1 adjustment frame
1 Allen Key
Page 8
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502434
Fax: +86 (0) 335 8502532
[email protected]
www.gst.com.cn