Kohler 48RCL RDC2 generator set Installation Instructions
Below you will find brief information for generator set 48RCL RDC2. This generator set is designed for residential and light commercial applications and provides reliable backup power in the event of a power outage. The RDC2 controller offers versatile features and settings for managing the generator set operation.
Advertisement
Advertisement
Installation
Residential/Light Commercial Generator Sets
Model:
48RCL
Controller:
RDC2
TP-6809 1/12
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference.
Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
2 TP-6809 1/12
Table of Contents
Product Identification Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Safety Precautions and Instructions
Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
9
Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
Section 1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
Enclosed Generator Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3
Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2
Lifting the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Unit-Mounted Radiator Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.1
Cooling System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2
Recommended Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5
Fuel Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.1
Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.2
Gas Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6
Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.1
Line Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.2
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.3
Ground and Neutral Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.4
Terminal Connector Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.5
Battery Chargers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6.6
Automatic Transfer Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11
12
12
12
12
13
13
13
13
13
13
13
14
15
15
11
11
11
Section 2 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1
Location Factors
2.1.2
Mounting Surface
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.3
Vibration Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.4
Lifting Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Prepare Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3
Mount and Ground Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4
Connect AC and DC Wiring
2.2.5
Transfer Switch Connection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.6
System Connections with Accessory Modules . . . . . . . . . . . . . . . . . . . . .
2.2.7
Other Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.8
Install Engine Starting Battery
2.2.9
Set Exerciser
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.10
Install and Connect Fuel Supply
2.2.11
Fuel Conversion Procedures
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.12
Add Coolant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.13
Prestart Installation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.14
Operation Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
27
28
28
29
31
32
33
33
19
19
21
22
23
17
17
18
18
18
18
19
Section 3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2
Block Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3
Programmable Interface Module (PIM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1
PIM to Generator Set Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2
PIM Inputs and Outputs
3.4
Load Control Module (LCM)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5
OnCue Home Generator Management System . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
35
35
36
36
36
37
38
TP-6809 1/12 Table of Contents 3
Table of Contents, continued
Section 4 Generator Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1
Voltage Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2
Four-Lead (Single-Phase) Generator Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3
12-Lead (Three-Phase) Generator Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4
Changing System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5
Voltage Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 5 Diagrams and Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
39
40
40
42
45
47
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
55
4 Table of Contents TP-6809 1/12
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely.
Read and follow all safety precautions and instructions.
SAVE
THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, substantial property damage.
or
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, substantial property damage.
or
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely.
The decals are shown throughout this publication to improve operator recognition.
Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set.
Remove the negative (--) lead first when disconnecting the battery.
Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set.
Accidental starting can cause severe injury or death.
Before working on the generator set or equipment connected to the set, disable the generator set as follows:
(1) Press the generator set off/reset button to shut down the generator set.
(2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wear protective goggles and clothing.
Battery acid may cause blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging.
Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects.
Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections.
Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin.
Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water.
Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
TP-6809 1/12 Safety Precautions and Instructions 5
Battery short circuits.
Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage.
Disconnect the battery before generator set installation or maintenance.
Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Engine Backfire/Flash
Fire
Fire.
WARNING
Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors.
Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive.
Handle these materials carefully to minimize the risk of fire or explosion.
Equip the compartment or nearby area with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BC for electrical fires or as recommended by the local fire code or an authorized agency.
Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide.
Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation.
Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors.
Carbon monoxide can cause severe nausea, fainting, or death.
Install carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide.
Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according manufacturer’s instructions.
to the
Carbon monoxide symptoms.
Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in joints and muscles
D Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep.
Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Fuel System
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system.
Explosive fuel vapors can cause severe injury or death.
Vaporized fuels are highly explosive.
Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks.
Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel
6 Safety Precautions and Instructions TP-6809 1/12
lines with rigid lines.
Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming generator set operation.
Explosive fuel vapors can cause severe injury or death.
Take additional precautions when using the following fuels:
Propane (LP)—Adequate ventilation is mandatory.
Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturer’s instructions.
Natural Gas—Adequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturer’s instructions.
Gas fuel leaks.
Explosive fuel vapors can cause severe injury or death.
Fuel leakage can cause an explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to
6--8 ounces per square inch
(10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Hazardous Noise
CAUTION
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before opening the enclosure.
WARNING
Hazardous voltage.
Moving parts.
Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
WARNING
Hazardous voltage.
Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets not equipped with sound enclosures can produce noise levels greater than
105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
TP-6809 1/12
Welding the generator set.
Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment.
Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards.
Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load.
Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by turning off the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads.
High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Welding on the generator set. Can cause severe electrical equipment damage.
Before welding on the generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module
(ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors.
(4) Disconnect the engine batterycharging alternator connections.
(5) Attach the weld ground connection close to the weld location.
Installing the battery charger.
Hazardous voltage can cause severe injury or death.
An ungrounded battery charger may cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead on the battery charger. Install the battery charger as prescribed in the equipment manual. Install the battery charger in compliance with local codes and ordinances.
Safety Precautions and Instructions 7
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies).
Have a qualified electrician install the battery(ies).
Short circuits.
Hazardous voltage/current can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage.
Do not contact electrical connections with tools or jewelry while making adjustments or repairs.
Remove all jewelry before servicing the equipment.
Engine block heater.
Hazardous voltage can cause severe injury or death. The engine block heater can cause electrical shock. Remove the engine block heater plug from the electrical outlet before working on the block heater electrical connections.
Electrical backfeed to the utility.
Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power.
Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Heavy Equipment
WARNING
Hot Parts
WARNING
Hot coolant and steam.
Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until it cools.
WARNING
Hot engine oil.
Can cause severe injury or death.
Avoid skin contact with hot oil. Do not start or operate the generator set with the engine oil filler cap removed, as hot oil can spray out. Ensure that the lubrication system is not under pressure when servicing. Do not work on the generator set until it cools.
Unbalanced weight.
Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes.
Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Notice
NOTICE
Canadian installations only.
For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with
Canadian Electrical Code, Part 1.
8 Safety Precautions and Instructions TP-6809 1/12
Introduction
This manual provides installation instructions for the model 48RCL generator set. Operation manuals are available separately.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
Figure 1 Model 48RCL Generator Set
List of Related Materials
Figure 2 identifies related literature available for the generator sets covered in this manual. Only trained and qualified personnel should install or service the generator set.
Literature Type
Specification Sheet, Generator Set
Operation Manual, Generator Set
Operation Manual Supplement, Engine
Service Manual, Generator Set
Service Manual, Engine
Service Manual, Engine
Service Manual, Alternator
Parts Catalog, Engine
Parts Catalog, Generator Set
Installation Instructions, Load Control
Module (LCM)
Installation Instructions, Programmable
Interface Module (PIM)
Operation Manual, OnCue t Software
Operation/Installation Manual, RXT ATS
Operation/Installation Manual, RDT ATS
Installation Manual, RSB Transfer Switch
Operation Manual, RSB Transfer Switch
Figure 2 Related Literature
Part Number
G4-211
TP-6810
TP-6101
TP-6811
TP-6104
TP-6724
TP-6783
TP-6731
TP-6812
TT-1574
TT-1584
TP-6796
TP-6807
TP-6345
TP-6486
TP-6487
Warranty Registration
Complete the startup and installation checklists supplied with the startup notification form. Complete and sign the startup notification form and register the unit using the Kohler online Warranty processing
System.
TP-6809 1/12 Introduction 9
Service Assistance
For professional advice on generator power requirements and conscientious service, please contact your nearest authorized Kohler distributor/dealer.
D
Consult the Yellow Pages under the heading
Generators—Electric.
D
Visit the Kohler Power Systems website at
KohlerPower.com.
D
Look at the labels and stickers on your Kohler product or review the appropriate literature or documents included with the product.
D
Call toll free in the US and Canada 1-800-544-2444.
D
Outside the US and Canada, call the nearest regional office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax: (813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax: (863) 701-7131
10 Service Assistance TP-6809 1/12
Section 1 General
1.1 Introduction
Review this section and the Safety Precautions before starting the installation procedure. The generator set specification sheet also contains data that may be required during the installation process.
The generator set and accessories must be installed by an authorized Kohler distributor/dealer or authorized representative. The installation must comply with all applicable national and local codes.
1.2 Enclosed Generator Sets
Install the generator set outdoors. Enclosed generator sets include a factory-supplied sound enclosure. The exhaust systems of enclosed units are complete for outdoor installations. Review Section 1 and then refer to
Section 2 for the outdoor installation of enclosed units.
Note: DO NOT install enclosed units inside a building.
1.3 Lifting
WARNING
1.3.1
General Precautions
Follow these general precautions when lifting all generator sets and related equipment.
D
Install proper size rigging at the skid lifting eyes providing a direct pull on the skid lifting eye. Make sure the rigging does not work as a pry bar lever against the lifting eye.
D
Do not lift the generator set using the lifting eyes attached to the engine and/or alternator as these lifting eyes can not support the total weight of the generator set.
D
Always protect cables, chains, and straps from sharp edges.
D
Lifting should only be conducted by those trained and experienced in lifting and rigging to achieve a safe and effective lift. Consideration needs to be given to, but not necessarily limited to the following items: d
Weight and center of gravity of the equipment being lifted d d d d d d
Weight and center of gravity of the lifting device
Boom angles
Selection of rated rigging
Stability of lifting foundation
Wind and weather conditions
Local or regional codes may require or restrict types of rigging.
D
Use a spreader bar to prevent lifting cables from contacting the enclosure.
Unbalanced and elevated weight.
Improper lifting can cause severe injury or death and equipment damage.
Do not lift the generator set from the engine or alternator eyes.
Never stand under a unit being lifted.
Always maintain a safe distance from the unit being lifted.
See the lifting instructions in the installation manual that was provided with the unit.
TP-6809 1/12 Section 1 General 11
1.3.2
Lifting the Generator Set
The distributor/lifting contractor should choose one of the following methods to lift the generator set depending upon the location circumstances and the generator set’s weight and size. Remove cover plates as needed to access the generator set skid lifting eyes.
Single Spreader Bar and Skid Lifting Bar Method
Refer to Figure 1-1.
Double Spreader Bar and Skid Lifting Bar Method
Refer to Figure 1-2.
1.4 Unit-Mounted Radiator Cooling
The generator set is equipped with a unit-mounted radiator common cooling system.
1.4.1
Cooling System Features
The system’s major components include two electric fans, a circulating water pump, a radiator, and a thermostat.
The pump circulates water through the engine until it reaches operating temperature. Then the engine thermostat opens, allowing water circulation through the radiator. The thermostat restricts water flow as necessary to prevent overcooling. The fans blow air through the radiator across the cooling surface.
1.4.2
Recommended Coolant
Add antifreeze before starting the generator set or energizing the block heater.
The generator set manufacturer recommends a solution of 50% ethylene glycol and 50% clean, softened water to provide freezing protection to --37
_C (--34_F) and boiling protection to 129
_C (256_F). A 50/50 solution also inhibits corrosion. Consult the engine manufacturer’s instructions for engine coolant specifications. See the
List of Related Materials in the Introduction.
TP-5700-2/L10
Figure 1-1 Single Spreader Bar and Skid Lifting Bar
Method
12 Section 1 General
TP-5700-2/L11
Figure 1-2 Double Spreader Bar and Skid Lifting
Bar Method
TP-6809 1/12
1.5 Fuel Supply
Gas fuel systems operate on either LP vapor or natural gas. Refer to the generator set specification sheet and
Section 2.2.10 for more detailed information on fuel requirements.
Note: The fuel system installation must comply with the
National Electrical Code r (NEC) and applicable local codes.
1.5.1
Fuel Lines
Gas lines. Never use fuel piping to ground electrical equipment. The gas supplier is responsible for installation, repair, and alteration to gas piping.
Use Schedule 40 black-iron pipe for gas piping. Copper tubing may be used if the fuel does not contain hydrogen sulfide or other ingredients that react chemically with copper.
Line size. Size piping according to the requirements of the equipment.
Refer to the the instructions in
Section 2.2.10. In addition to actual fuel consumption, consider the following pressure loss factors:
D
D
D
Pipe length
Other appliances on the same fuel supply
Number of fittings
Flexible connections. Rigid mount the piping but protect it from vibration. Use flexible connections spanning a minimum of 152 mm (6 in.) between the stationary piping and the engine fuel inlet connection.
1.5.2
Gas Regulators
Gas regulators reduce high incoming fuel pressures to lower levels acceptable for engines. See the generator set specification sheet for fuel supply pressure requirements.
Primary gas regulator. The primary regulator reduces the high pressure from a tank or transmission line to the lower pressure required by the secondary regulator on the engine.
The fuel supplier provides the primary regulator.
The fuel supplier is also responsible for providing sufficient gas pressure to operate the primary regulator.
Secondary gas regulator. The secondary regulator is factory-installed on the generator set engine and controls the inlet pressure to the engine. The models covered by this manual use an electronic pressure regulator. See Section 2.2.11.
Note: The Integrated Electronic Pressure Regulator
(IEPR) and air/fuel mixer are specially calibrated emission-control devices. Do not adjust the IEPR or the air/fuel mixer.
1.6 Electrical System
Before installing the generator set, provide for electrical connections through conduit to the transfer switch and other accessories for the generator set. Route DC leads in separate conduit from AC conductors.
Carefully install the selected generator set accessories. Route wiring to the generator set through flexible connections.
Comply with all applicable codes when installing a wiring system.
1.6.1
Line Circuit Breakers
AC circuit protection. All AC circuits must include circuit breaker or fuse protection. The circuit breaker must be rated for a maximum of 125% of the rated generator set output current. The circuit breaker must open all ungrounded connectors.
The generator set is equipped with a factory-installed circuit breaker.
1.6.2
Electrical Connections
Several electrical connections must be made between the generator set and other components of the system for proper operation. Most field-installed accessory kits include installation instructions. Comply with applicable national and local codes when installing a wiring system.
See the dimension drawings in Section 5 for the recommended stub-up location.
Size the wire according to the length of run and 115% of the circuit current (amperage) based on 75
_C wire rating or less as directed by the National Electrical
Code r (NEC) in ANSI/NFPA 70.
For Canadian installations, refer to the Canadian
Electrical Code (CEC).
1.6.3
Ground and Neutral Connections
Ground the generator set. The grounding method must comply with NEC and local codes.
Connect the grounding strap to the generator set ground lug. See
Section 2.2.3 for the ground lug location.
The National Electrical Code r is a registered trademark of the National Fire Protection Association, Inc.
TP-6809 1/12 Section 1 General 13
Various regulations and site configurations including the
National Electrical Code (NEC), local codes, and the type of transfer switch used in the application determine the grounding of the neutral at the alternator. NEC 2002
Section 250.20 is one example that has a very good explanation of the neutral grounding requirements for generator sets.
Generator sets are shipped with the generator set neutral attached to the alternator in the junction box. At installation, the neutral can be grounded at the generator set or lifted from the ground stud and isolated if the installation requires an ungrounded neutral connection at the alternator.
The generator set will operate properly with the neutral either bonded to ground or isolated from ground at the alternator.
Socket Size Across
Flats, mm (in.)
3.2
(1/8)
4.0
(5/32)
4.8
(3/16)
5.6
(7/32)
6.4
(1/4)
7.9
(5/16)
9.5
(3/8)
12.7
(1/2)
14.3
(9/16)
Tightening Torque,
Nm (in. lb.)
5.1
(45)
11.4
(100)
13.8
(120)
17.0
(150)
22.6
(200)
31.1
(275)
42.4
(375)
56.5
(500)
67.8
(600)
Note: For values of slot width or length not corresponding to those specified, select the largest torque value associated with the conductor size. Slot width is the nominal design value. Slot length is to be measured at the bottom of the slot.
Figure 1-3 Tightening Torque for Pressure Wire
Connectors with Internal-Drive
Socket-Head Screws
1.6.4
Terminal Connector Torque
Use the torque values shown in Figure 1-3 or Figure 1-4 for terminal connectors. Refer to UL-486A, UL-486B, and UL-486E for information on terminal connectors for aluminum and/or copper conductors.
Comply with applicable national and local codes when installing a wiring system.
Note: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test the connector using both applicable torque values provided in
Figure 1-4.
Tightening Torque, Nm (in. lb.)
Wire Size for Unit
Connection
AWG, kcmil (mm
2
)
18--10
8
6--4
3
2
1
1/0--2/0
3/0--4/0
250--350
400
500
600--750
800--1000
1250--2000
(0.82--5.3)
(8.4)
(13.3--21.2)
(26.7)
(33.6)
(42.4)
(53.5--67.4)
(85.0--107.2)
(127--177)
(203)
(253)
(304--380)
(406--508)
(635--1016)
Slot Head 4.7 mm (No. 10) or Larger*
Slot Width <1.2 mm (0.047 in.)
Slot Length <6.4 mm (0.25 in.)
2.3 (20)
2.8 (25)
4.0 (35)
4.0 (35)
4.5 (40)
—
—
—
—
—
—
—
—
—
Slot Width >1.2 mm (0.047 in.)
Slot Length >6.4 mm (0.25 in.)
4.0 (35)
4.5 (40)
5.1 (45)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
5.6 (50)
—
Hexagonal Head—External
Drive Socket Wrench
Split-Bolt
Connectors
9.0
9.0
(80)
(80)
18.6
(165)
31.1
(275)
31.1
(275)
31.1
(275)
43.5
(385)
56.5
(500)
73.4
(650)
93.2
(825)
93.2
(825)
113.0
(1000)
124.3
(1100)
124.3
(1100)
Other
Connections
8.5
(75)
8.5
(75)
12.4
(110)
16.9
(150)
16.9
(150)
16.9
(150)
20.3
(180)
28.2
(250)
36.7
(325)
36.7
(325)
42.4
(375)
42.4
(375)
56.5
(500)
67.8
(600)
* For values of slot width or length not corresponding to those specified, select the largest torque value associated with the conductor size.
Slot width is the nominal design value. Slot length is to be measured at the bottom of the slot.
Note: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test the connector using both applicable torque values.
Figure 1-4 Tightening Torque for Screw-Type Pressure Wire Connectors
14 Section 1 General TP-6809 1/12
1.6.5
Battery Chargers
An engine-driven, battery-charging alternator charges the battery whenever the generator set operates.
Engine-driven systems can quickly restore the charge used in a normal cranking cycle.
When the engine is not operating, a very low charge rate from an AC-powered battery charger is usually sufficient to maintain a full charge on the batteries. The RDC2 controller contains a built-in battery charger to maintain the generator set’s engine starting battery. Be sure to provide 120 VAC power for the integral battery charger as instructed in Section 2.2.
1.6.6
Automatic Transfer Switches
A typical standby system has at least one automatic transfer switch connected to the generator set output to automatically transfer the electrical load to the generator set if the normal source fails. The normal power source is typically utility power. When normal power returns, the switch transfers the load back to the normal power source and then signals the generator set to stop.
Kohler Model RXT Automatic Transfer Switch
The RDC2 controller is designed to control the Kohler
Model RXT transfer switch as well as the 48RCL generator set.
Follow the installation instructions to connect the transfer switch interface board to the appropriate terminals on the generator set. The RDC2 controller uses a Kohler-propietary communication protocol to communicate with the transfer switch.
When connected to a Kohler Model RXT transfer switch, the RDC2 controller provides the following features:
D
Monitors and displays utility voltage and frequency.
D
Schedule loaded exercises from the RDC2 generator set controller.
D
Set the ATS system voltage and frequency.
D
Allows calibration of the utility voltage and frequency at the generator set controller.
D
Allows adjustment of transfer switch transfer time delays from the generator set controller.
Other Transfer Switches
The Kohler Model RDT and RSB transfer switches can be used with the 48RCL generator set. These transfer switches contain separate ATS controls that do not communicate with the RDC2 controller.
Other transfer switches use a set of contacts to signal the engine/generator to start. When the normal source fails and the generator set is in AUTO mode, the transfer switch contacts close to start the generator set.
The engine start terminals are usually located near the transfer switch contactor with an engine start decal identifying the terminals. Use the transfer switch wiring diagrams to identify the engine start terminals prior to making connections.
Connect the transfer switch engine-start contacts or a remote manual engine-start switch to the engine start terminals (3 and 4) on the generator set. Size the wire according to the transfer switch connection and the length of run.
Use separate conduit for the DC engine-start leads and the AC generator set load cables and battery charger leads.
TP-6809 1/12 Section 1 General 15
Notes
16 Section 1 General TP-6809 1/12
Section 2 Installation Instructions
2.1 Introduction
Have the generator set installed by an authorized Kohler distributor/dealer or authorized representative. Install the equipment in compliance with the National Electrical
Code (NEC) and local codes.
For Canadian installations, refer to the Canadian Electrical Code
(CEC).
Note: These instructions outline one procedure for installing the generator set. Local codes may require different procedures.
The generator set must be installed outdoors.
The exhaust systems on enclosed units are designed for outdoor installation only.
Review the information in
Section 1, General, before beginning the installation procedure.
Note: DO NOT install these generator sets inside a building.
Note: Install carbon monoxide (CO) detector(s) on each level of any building adjacent to a generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide.
Read and follow the safety precautions in this manual and observe the decals on the equipment. Refer to the diagrams and drawings in Section 5 for dimensions and electrical connections during the installation procedure.
Read the entire installation procedure and obtain the accessories and tools needed before beginning installation. Perform the steps in the order shown.
To install optional accessories, follow the instructions provided with each kit.
WARNING
Hazardous voltage.
Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
TP-6809 1/12
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards.
Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
WARNING
Carbon monoxide.
Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors.
Carbon monoxide can cause severe nausea, fainting, or death. Install carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide.
Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
2.1.1
Location Factors
The manufacturer recommends mounting the generator set on concrete at ground level.
For above-ground installations, including roof installations, weight considerations are especially important. The building engineer must determine whether the structure can support the weight of the generator set.
The location of the generator set must:
D
Support the weight of the generator set and related equipment such as batteries, radiators, and mounting pad(s). Keep in mind that the mounting pad weight may exceed the weight of the generator set.
Section 2 Installation Instructions 17
D
Meet applicable fire rating codes and standards.
D
Minimize the risk that people will come into contact with hot generator set surfaces.
D
Position the generator set over a noncombustible surface. DO NOT allow accumulation of combustible materials under or around the generator set.
D
Permit vibration isolation to reduce noise and prevent damage.
D
Not be subject to flooding.
D
Provide clearance for cooling air flow and access for service. See Section 2.2 and the dimension drawing in Section 5 for required clearances from obstructions and combustible materials.
D
Allow safe expulsion of exhaust.
D
Minimize the risk of public or unauthorized access.
Notice
DO NOT locate the generator set near patios, decks, play areas, or animal shelters. Keep items such as lawn furniture, toys, sports equipment, and all combustible materials away from the generator set exhaust outlet.
Remind family members, children, and visitors to use caution near the generator set. Generator sets connected to automatic transfer switches start automatically during exercise periods and power outages. Some generator set components become hot when the generator set is running and remain hot for a time after the generator set shuts down.
2.1.2
Mounting Surface
Install the generator set on a single, level concrete mounting pad. This method provides maximum stability and ensures correct cooling air flow through the generator set.
The recommended mounting pad dimensions are shown in the dimension drawings in
Section 5.
Refer to the generator set dimension drawings for conduit and fuel-line placement.
The drawings give dimensions for electrical and fuel connection rough-ins and stub-ups.
2.1.3
Vibration Isolation
The generator set is equipped with neoprene vibration isolators. Connections between the generator set or its mounting base and any conduits or fuel lines must include flexible sections to prevent breakage and to isolate vibration.
2.1.4
Lifting Generator Set
WARNING
Unbalanced weight.
Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes.
Lift the generator set using lifting bars inserted through the lifting holes on the skid.
The generator set with enclosure weighs approximately
893 kg (1970 lb.). Use equipment that is rated for the generator set’s weight to lift the unit into place. Lift the enclosure and generator set together as one unit.
DO NOT lift the generator set using the lifting eyes attached to the engine and/or alternator. These eyes cannot support the generator set’s weight.
Instead, insert lifting bars through the four holes in the mounting skid. The placement of the holes maintains balance during lifting. See Section 1.3 for more information.
2.2 Installation Procedure
Tools Required:
D
D
D
D
D
D
D
D
D
D
Multimeter (for measuring voltage and current)
Frequency meter (may be part of multimeter)
Manometer (for measuring fuel pressure)
Torque wrench
Wrenches
Screwdrivers
Socket wrenches or nut drivers
Pliers
Safety glasses or goggles
Drill with bits and hole saw
18 Section 2 Installation Instructions TP-6809 1/12
D
D
D
D
Installer/Customer-Supplied Items:
D
D
One BCI group 24 size 12-volt battery with a minimum rating of 650 cold cranking amps (CCA) at 0
_F.
Remote harness with pigtail connector
(to connect ATS engine start, if used)
Gravel or crushed stone
Concrete mounting pad
Cables and conduit
Fuel supply line with shutoff valve and pipe sealant
(provided by fuel supplier)
D
Carbon monoxide (CO) detector(s)
Available Accessories:
D
D
D
D
D
Battery
Battery heater
Block heater
Flexible fuel lines
Programmable Interface Module (PIM)
See TT-1584 for installation instructions.
D
Load Control Module (LCM)
See TT-1574 for installation instructions.
D
OnCue Home Generator Management System
(requires Ethernet cable connection to your router)
2.2.1
Prepare Site
Choose a location that is at least 0.9 m (3 ft.) from any building or structure and near the incoming gas service.
Allow a minimum of 2.4 m (8 ft.) clearance beyond the exhaust end of the generator set. Plan the installation so that the exhaust end of the generator set is not directed toward the building or any openings where exhaust gas could be drawn into the building.
Install carbon monoxide detectors on each level of any building adjacent to the generator set.
Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide.
1. Obtain a building permit and contact your local utility companies to mark the locations of underground pipes and cables.
2. Prepare an area for mounting the generator set.
a. Clear all combustible materials, including plants and shrubs, building materials, and lawn furniture, from an area at least 2.4 m (8 ft.) beyond the exhaust end of the generator set.
b. Spread a 76 mm (3 in.) thick layer of gravel to support the concrete mounting pad. For the mounting pad dimensions, see the generator set dimension drawing in Section 5.
c. Lay a 100 mm (4 in.) thick concrete pad on the gravel layer. Include mounting bolts and stubups for the fuel supply and electrical conduit.
See the dimension drawing in Section 5 for the mounting bolt and stub-up locations.
2.2.2
Power Supply
Power must be supplied to the generator set location for the battery charger and optional accessories.
The power source must be GFCI protected. The power to the accessories must be available at all times, i.e. the circuit must be powered by the utility source and backed up by the generator set.
Connect power to the utility power connection points on the terminal block. See the wiring diagrams in Section 5 for connection details. See Figure 2-1 for the power requirements for the battery charger and accessories.
Equipment
Battery charger (standard, integral to RDC2 controller)
Block heater (optional)
Battery heater (optional)
Power Requirement
Watts Amps Volts
120
1500
80
Figure 2-1 Power Requirements
1
12.5
6.3
0.7
120
120
240
120
2.2.3
Mount and Ground Generator Set
1. Place the generator set on the concrete mounting pad. Secure the generator set with mounting bolts anchored in the concrete pad.
2. Remove the enclosure doors and alternator-end panel to gain access to the junction box and other generator set components during installation.
Rremove the covers to access the AC and DC connection terminal blocks.
3. Ground the generator set. The grounding method must comply with NEC and local codes. Connect the grounding strap to the generator set ground lug, terminal GRD inside the junction box or on
TB2. See Figure 2-2. Connect the ground to the
GND terminals on terminal block TB2.
Generator sets are shipped with the generator set neutral attached to the generator set in the junction box. At installation, the neutral can be grounded at the generator set or lifted from the ground stud and isolated if the installation requires an ungrounded neutral connection at the generator set.
The generator set will operate properly with the neutral
TP-6809 1/12 Section 2 Installation Instructions 19
either bonded to ground or isolated from ground at the generator set.
Various regulations and site configurations including the National Electrical Code (NEC), local codes, and the type of transfer switch used in the application determine the grounding of the neutral at the generator set. NEC 2002 Section 250.20 is one example that has a very good explanation of the neutral grounding requirements for generator sets.
1
GM78527
1. Access panel (remove to access connections)
2. 120VAC connection leads and ground screw
3. Installer to punch access openings
4. Low voltage connection terminal block TB1
5. Ethernet cable connection for OnCue
6. Ground (GRD) lug
7. Load lead access opening
8. Load lead connections to line circuit breaker
9. Neutral lug
Figure 2-2 Generator Set Connections
9 8 7 6 5
Connection details
Access panel removed.
4
2
3
20 Section 2 Installation Instructions TP-6809 1/12
2.2.4
Connect AC and DC Wiring
Note: Have a licensed electrician make the following electrical connections.
All connections must comply with state and local codes.
Size the wire according to the length of run and 115% of the circuit current (amperage) based on 75
_C wire rating or less as directed by the National Electrical
Code r (NEC) in ANSI/NFPA 70. See Section 1.6 for additional information about connecting the electrical system.
The generator set is equipped with a field-connection terminal block located in the access area below the junction box. Leads have been factory-installed from the junction box to the terminal block for easy field wiring.
See Figure 2-2.
Make all AC and DC customer connections inside the customer connection box. Do not remove the end panel or make connections inside the junction box. Refer to the diagrams in the wiring diagram manual provided with the generator set.
Generator Set Connections
Use separate conduit for the power cables and the low voltage communication or engine start leads.
Local codes and the length of run as well as the transfer switch wire size requirements will determine the wire size needed for the AC leads.
Note: Some codes require the use of a disconnect switch. Check the code requirements for your location and install a disconnect switch, if required.
1. Route the load leads into the junction box through the access opening in the bottom of the box.
Connect the load leads from the line circuit breaker in the generator set junction box to the transfer switch emergency power connection points. See
Figure 2-2 and refer to transfer switch installation manual for ATS connection instructions.
2. Connect the neutral (L0) and ground (GRD) leads from the ATS and the main panel to the corresponding lugs in the connection box. See
Section 2.2.3 for grounding information.
3. Cut or punch openings in the side of the connection box for the 120 VAC power supply leads and the low voltage connections. See Figure 2-2. Use separate conduit for the power leads and the low voltage leads.
4. Connect utility power for the controller’s battery charger. Connect to a circuit that is supplied by the utility source and backed up by the generator. The power source must be GFCI protected.
See
Section 2.2.2 for more information about the utility power requirement.
5. For connection of optional transfer switches, the programmable interface module (PIM), and/or a load control module (LCM), see Section 2.2.5.
6. Install a 120 VAC receptacle for the optional block heater, if equipped. Power to this receptacle must be available when the generator set is not running.
7. If the OnCue Home Generator Management
System will be used with the generator set, run category 5E network cable from the generator set to the customer’s router or modem.
Note: Installation of the network cable at the time of generator set installation is highly recommended. Installing the Ethernet cable now will make connection much easier if you choose to add OnCue later.
a. Route the network cable with other low-voltage signal wiring (for example, the RBUS communication leads or engine start leads to the transfer switch), in separate conduit from the AC load leads. If the network cable is longer than 100 meters (328 ft.), use a repeater or switch.
b. Use an RJ45 inline coupler to connect the
Ethernet cable to the cable in the customer connection box. The inline coupler is included with the OnCue kit.
TP-6809 1/12 Section 2 Installation Instructions 21
2.2.5
Transfer Switch Connection
Connect the ATS or remote start/stop switch. Connect the load leads from the generator set to the Emergency source lugs on the ATS.
Route low-voltage communication leads through separate conduit.
All connections must comply with applicable state and local codes.
Communication connections for a Model RXT transfer switch:
See Figure 2-3.
Use Belden #9402 or equivalent
20 AWG shielded, twisted-pair cable to connect P10-1 through P10-4 on the transfer switch interface module to the generator set terminal block TB1 connections A, B,
PWR, and COM.
Note: Connections 3 and 4 on the generator set are not used with the Model RXT transfer switch.
Engine start connection for other transfer switches or a remote start/stop switch:
See Figure 2-4. Connect the engine start leads from the transfer switch or remote start switch to terminals 3 and
4 on the terminal block. Route the engine start leads through separate conduit from the AC power and load leads.
Connect one end of each cable shield to
GROUND at the generator set.
GND
Generator Set
12VDC
RBUS
COM
PWR
B
A
Generator Set Terminal Block TB1.
See Figure 2-2 for location. Check the decal on the generator set for terminal block connections.
1
A
B
PWR
COM
Interface Board on the
Model RXT Transfer Switch
RXT
Leave the end of each cable shield disconnected at the last device. If accessory modules (PIM or
LCM) are connected, see Section 2.2.6.
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Note: Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS.
Figure 2-3 Model RXT Transfer Switch Communication Connection to Generator Set Terminal Block
22 Section 2 Installation Instructions TP-6809 1/12
Generator Set
12VDC
RBUS
1
1
ATS
Models RDT or RSB
Generator Set Terminal Block TB1.
See Figure 2-2 for location. Check the decal on the generator set for terminal block connections.
tp6809
1. Engine start leads 3 and 4. See the ATS manual for cable size specifications.
Figure 2-4 Engine Start Connections with Transfer Switch Models RDT or RSB
2.2.6
System Connections with
Accessory Modules
See Figure 2-6 through Figure 2-10 for connection options with up to three accessory modules. Accessory modules can include one Model RXT transfer switch, one programmable interface module (PIM), and/or one load control module (LCM)..
D
Use Belden #9402 (4-conductor) or equivalent
20 AWG shielded, twisted-pair cable. Note the shield connections shown in Figure 2-6.
D
If longer cable runs are required, 12--14 AWG wire can be used for the COM and PWR connections. The maximum total cable length is the value shown for 12 or 14 AWG wire in Figure 2-5.
See Figure 2-5 for the maximum total cable length with
1, 2, or 3 accessory modules per cable run.
Cable
Belden #9402 or equivalent 20AWG
14 AWG
12 AWG
Maximum length per run, meters (ft.)
Number of Modules per Run
1
61 (200)
152 (500)
2
31 (100)
152 (500)
3
21 (67)
122 (400)
152 (500) 152 (500) 152 (500)
Figure 2-5 Total Cable Lengths with Accessory Modules Connected in Series (daisy-chain)
TP-6809 1/12 Section 2 Installation Instructions 23
Connect one end of each cable shield to GROUND at the generator set.
GND
Generator Set
12VDC
RBUS
COM
PWR
B
A
1
A
B
PWR
COM
Connect shields together as shown.
RXT
A
B
PWR
COM
Generator Set Terminal Block TB1.
See Figure 2-2 for location. Check the decal on the generator set for terminal block connections.
PIM
A
B
PWR
COM
A
B
PWR
COM
A
B
PWR
COM
Note: See Figure 2-5 for maximum total cable length per run (1 run shown).
Leave one end of each cable shield disconnected at the last device.
1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable
Figure 2-6 Accessory Module Communication Connection Details
LCM
24 Section 2 Installation Instructions TP-6809 1/12
RXT ATS
Generator Set
1
TB1
1
LCM
Note: See Figure 2-2 for terminal block location on generator set.
Check the decal on the generator set for terminal block connections.
See Figure 2-5 for maximum total cable length per run
(3 runs with 1 module each shown).
See Figure 2-6 for communication connection detail.
Use splices or wire nuts to collect multiple leads for connection to the generator set terminal block. See Figure 2-8.
1. Belden #9402 or equivalent, 20 AWG shielded cable with 2 twisted pairs
1
Figure 2-7 Accessory Module Connections (three cable runs with one module each)
PIM
Generator Set
12VDC
RBUS
1
Connect all of the shield leads on this end to GROUND at the generator set.
COM
PWR
B
A
TO GROUND
COM
PWR
B
A
9402 CABLE
9402 CABLE tp6809
Generator Set Terminal Block TB1.
See Figure 2-2 for location. Check the decal on the generator set for terminal block connections.
1. Splice
Figure 2-8 Multiple Connections to the Generator Set tp6809
TP-6809 1/12 Section 2 Installation Instructions 25
Generator Set
TB1
1
RXT ATS
1
PIM
1
Note: See Figure 2-2 for terminal block location on generator set.
Check the decal on the generator set for terminal block connections.
See Figure 2-5 for maximum total cable length with 12 or 14
AWG wire.
See Figure 2-6 for communication connection (A and B, PWR and COM) details. Connect the cable shield to ground at the generator set.
LCM
1. Belden #9402 or equivalent, 20 AWG shielded cable with 2 twisted pairs
Figure 2-9 Accessory Module Connections (two cable runs with one and two modules shown) tp6809
26 Section 2 Installation Instructions TP-6809 1/12
Generator Set
A and B
PWR
COM
1
2
2
RXT ATS
A and B
PWR
COM
1
2
2
Note: See Figure 2-2 for terminal block location on generator set.
Check the decal on the generator set for terminal block connections.
See Figure 2-5 for maximum total cable length with
12 or 14 AWG wire. (1 run with 3 modules shown)
See Figure 2-6 for communication connection (A and B) detail. Connect the cable shield to ground at the generator set.
1
2
2
A and B
PWR
COM
PIM
A and B
PWR
COM
LCM
1. Belden #9402 or equivalent, 20 AWG shielded cable (use one pair)
2. 12--14 AWG wire tp6809
Figure 2-10 Accessory Module Connections with 12--14 AWG Power Leads (one cable run with three modules shown)
2.2.7
Other Accessories
Install and connect optional accessories. Follow the installation instructions provided with the accessory kits.
See Section 3 for information about available accessories.
TP-6809 1/12 Section 2 Installation Instructions 27
2.2.8
Install Engine Starting Battery
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes.
Battery gases.
Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire.
To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Use a 12 VDC battery with a minimum rating of
650 CCA.
1. Ensure that the starting battery is fully charged before placing the battery in service.
2. Clean the battery posts and/or adapters if necessary.
3. Install battery post adapters, if needed.
4. See the dimension drawing in Section 5 for the battery rack location.
Place the battery on the battery rack on the skid.
5. Connect the red battery cable to the positive (+) battery terminal.
6. Connect the black battery cable to the negative (--) battery terminal.
7. Place the boots over the battery terminals.
When power is applied to the RDC2 controller (that is, when the battery is connected), you will be prompted to set the date and time, and then to set the exerciser. See
Section 2.2.9 and the generator set operation manual for instructions.
If the battery is disconnected for service or replacement, the exercise settings on the RDC2/DC2 controller are lost. Set the exerciser after installing and connecting the battery. See Section 2.2.9, Set Exerciser.
2.2.9
Set Exerciser
When power is applied to the RDC2 controller (that is, when the battery is connected), you will be prompted to set the date and time, and then to set the exerciser. Set the exerciser to automatically run the generator set on the desired day and time every week or every two weeks.
Figure 2-11 shows the controller screens.
The first setting will flash. Press the Up and Down arrow buttons to change the setting. Press Select to save the setting and move on to the next. Repeat until the date, time, and exercise are set and the controller display shows the main menu. See TP-6810, Generator Set Operation
Manual, for more detailed instructions to set the date and time and set the exerciser.
Date:
05Dec2011
Time:
08:31a
Setting will flash.
Press the up and down arrow buttons to change the setting.
Press Select to save the setting.
Next Exercise:
08:31a 12Dec2011
Figure 2-11 Set Time, Date, and Exercise, RDC2
Controller tp6803
In order to set a loaded exercise using the RDC2 controller, a Kohler r Model RXT transfer switch must be connected. To set a loaded exercise on a generator set connected to a transfer switch other than a Model RXT, use the transfer switch controller to set the exercise.
Refer to the transfer switch operation manual for instructions.
The controller must be in automatic mode for the exerciser to operate as scheduled.
Press AUTO to place the generator set controller into automatic mode.
28 Section 2 Installation Instructions TP-6809 1/12
2.2.10 Install and Connect Fuel Supply
WARNING
4. Have your fuel supplier install a manual fuel shutoff valve and rigid gas piping. Bring the pipe to within
254 mm (10 in.) of the generator set fuel inlet location. See Figure 2-13.
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Note: Have the fuel piping and regulator installed by the fuel supplier. The fuel supply installation must comply with NEC and local codes.
1. See the generator set spec sheet for the fuel supply requirements. Add up the fuel requirements for the generator set plus all other gas-fired equipment fueled by the same supply.
2. Check that the primary regulator and gas meter have sufficient capacity for the fuel requirements for the generator set plus all other gas-fired equipment. Have the fuel supplier install a larger gas meter, if necessary.
3. Measure the pipe length from the primary gas pressure regulator to the pipe connection on the generator set fuel inlet. Add 2.4 m (8 ft.) to the measured length for each 90 degree elbow. Use the pipe size indicated in Figure 2-12 for the total length of pipe.
Maximum Pipe Length, m (ft.)
6.1 m (20 ft.)
9.1 m (30 ft.)
18.3 m (60 ft.)
30.5 m (100 ft.)
45.7 m (150 ft.)
61.0 m (200 ft.)
Figure 2-12 Fuel Pipe Sizes
TP-6809 1/12
Pipe Size
1 1/4 in. NPT
1 1/4 in. NPT
1 1/2 in. NPT
1 1/2 in. NPT
2 in. NPT
2 in. NPT
Figure 2-13 Manual Fuel Shutoff Valve (outdoor installation shown)
Section 2 Installation Instructions 29
5. Remove the enclosure door on the service side of the unit.
6. Connect the fuel supply: a. Apply pipe sealant that is approved for fuel connections to the threaded fuel connections.
b. Use a section of flexible fuel line to connect the fuel supply to the 1 in. NPT fuel inlet connection on the generator set. See Figure 2-14 for the fuel inlet connection location.
Also see
ADV-7962 in Section 5.
c. Open the manual fuel valves and leak test all fuel connections using soapy water. If a leak is detected, close the fuel valves, disconnect the lines at the location of the leak, clean the fittings, and apply fresh pipe sealant.
Reconnect the lines and recheck for leaks.
Note: After the system installation is complete, you will be instructed to check for fuel leaks with the generator set running.
See Section 2.2.14, Operation Tests.
7. Verify that the fuel system is set up for the fuel being used (natural gas or LP). See Section 2.2.11.
1
2
1. Fuel solenoid valves (2)
2. Fuel inlet connection
Figure 2-14 Fuel Supply Connection Location (generator set enclosure not shown)
GM78523
30 Section 2 Installation Instructions TP-6809 1/12
2.2.11 Fuel Conversion Procedures
Note: The Integrated Electronic Pressure Regulator
(IEPR) and air/fuel mixer are specially calibrated emission-control devices. Do not adjust the IEPR or the air/fuel mixer.
Check the connections to the fuel solenoid valve to verify that the fuel system is set up for the type of fuel that will be used. See Figure 2-14 for the location of the fuel solenoid valve.
To change the fuel type, change the connection to the fuel solenoid valve as described below and shown in
Figure 2-15.
LP Connections:
D
Disconnect lead 73A from the fuel valve.
D
Connect lead 73B to the fuel valve.
D
Connect lead 65 to lead N3 (ground).
Natural Gas Connections:
D
Disconnect lead 65 from N3.
D
Disconnect lead 73B from the fuel valve.
D
Connect lead 73A to the fuel valve.
FOR LP REMOVE 73A LEAD FROM FV1
AND PLUG IN 73B LEAD
FOR LP FUEL
CONNECT 65 AND N3
TO ECM
NATURAL GAS CONFIGURATION SHOWN
GM79871
Figure 2-15 Fuel Type Connections
Converting the fuel will change the generator set rating.
See the generator set specification sheet for ratings with natural gas and LP. Order a new nameplate with the updated rating and fuel information from an authorized distributor/dealer, if necessary. Provide the following information from the original nameplate:
D Model Number
D Spec Number
D Serial Number
D Fuel (original and new)
D kW
D kVA
D Amps
D Volts
D Hz
TP-6809 1/12 Section 2 Installation Instructions 31
2.2.12 Add Coolant
Follow the instructions below to fill the cooling system.
1. Close the radiator’s coolant drain valve and tighten the hose clamps.
Note: Do not add coolant to a hot engine. Adding coolant to a hot engine can cause the cylinder block or cylinder head to crack.
Wait until the engine has cooled.
2. Fill the radiator with the recommended coolant mixture of 50% ethylene glycol and 50% clean, softened water to inhibit rust/corrosion and prevent freezing. See Figure 2-16 for coolant capacity. Do not replace the pressure cap at this time.
Note: A coolant solution of 50% ethylene glycol provides freezing protection to --37
°C
(--34
°F) and overheating protection to
129
°C (265°F). A coolant solution with less than 50% ethylene glycol may not provide adequate freezing and overheating protection.
A coolant solution with more than 50% ethylene glycol can cause engine or component damage. Do not use alcohol or methanol antifreeze or mix them with the specified coolant.
Model
48RCL
Coolant Capacity, L (Gal.)
17 (4.5)
Figure 2-16 Coolant Capacity
3. Check the oil level before operating the engine.
4. Operate the engine with the radiator’s pressure cap removed until the thermostat opens and the radiator upper hose becomes hot.
5. Stop the engine and allow it to cool.
6. Add coolant to the radiator to just below the overflow tube on the filler neck. See Figure 2-17.
7. Replace the radiator’s pressure cap.
8. Maintain the coolant level in the coolant overflow bottle between the High and Low markings. See
Figure 2-17 for the coolant overflow bottle location.
Note: Block Heater Damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater.
1
2
1. Pressure cap (engine coolant fill)
2. Overflow tube
3. Coolant overflow bottle
Figure 2-17 Coolant Fill
32 Section 2 Installation Instructions
3
GM83070
TP-6809 1/12
2.2.13 Prestart Installation Check
Review the entire installation section. Inspect all wiring and connections to verify that the generator set is ready for operation. Check all items in the following Prestart
Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is installed to prevent unfiltered air from entering the engine. See the generator set operation manual for instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.
Coolant Level. Check the coolant level as described in
Section 2.2.12.
Note: Block Heater Damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater.
Enclosure.
Check that all enclosure panels and internal baffling are in place.
Exhaust System.
Check for exhaust leaks and blockages. Check the muffler condition.
D
Inspect the exhaust system components for cracks, leaks, and corrosion. Check for tight exhaust system connections.
D
Check for corroded or broken metal parts and replace them as needed.
D
Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area.
Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
2.2.14 Operation Tests
WARNING
Hazardous voltage.
Moving parts.
Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
1. Verify that all guards are in place.
Install the enclosure’s end panels and nonservice side door.
2. Check the items in the Prestart Checklist in the generator set operation manual.
3. Set the time and date, and then set the exerciser to run the generator set once a week or every other week to keep the generator set in good operating condition. See TP-6710, Operation Manual, for instructions to set the date and time and set the exerciser.
4. Press the RUN button on the generator set controller to start the generator set.
5. Use a digital voltmeter (DVM) to check the output voltage from the generator set.
If voltage adjustments are required, refer to Section 4.5 for instructions to use the RDC2 controller’s voltage adjustment menu.
6. Perform voltage checks as described in the ATS operation and installation manual. Close the main circuit breaker on the main distribution panel when instructed to connect power in the test procedure.
7. Press OFF and then AUTO on the RDC2 controller.
8. Install the enclosure’s service-side door. Verify that all enclosure doors and panels are installed. Lock the enclosure doors to prevent unauthorized access.
TP-6809 1/12 Section 2 Installation Instructions 33
Notes
34 Section 2 Installation Instructions TP-6809 1/12
Section 3 Accessories
3.1 Introduction
Accessories are available factory-installed and/or shipped loose.
Obtain the most current list of accessories from the generator set specification sheet or by contacting an authorized Kohler distributor/ dealer.
Have accessories installed by your local authorized
Kohler distributor/dealer or authorized representative.
Follow the installation instructions provided with each kit.
Use separate conduit for AC and DC leads to reduce the possibility of electrical interference. Use shielded cable for all analog inputs. Verify that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas.
Verify that the accessory installation complies with the
National Electrical Code (NEC) and all applicable local and state codes.
Accessory Wiring. To determine the appropriate size for the customer-supplied wiring of engine batterypowered accessories, use the guidelines in Figure 3-1.
Use 18--20 gauge wire for signal wires up to 305 m
(1000 ft.). See Section 3.5 or Figure 3-7 for OnCue connections.
Length, m (ft.)
30.5
(100)
152.4
(500)
304.8
(1000)
Wire Gauge
18--20
14
10
Figure 3-1 Wire Length and Size, Lead N and 42B
Refer to the wiring diagram manual for more information regarding generator set electrical connections.
The following sections detail a few common accessories and their functions. The instructions provided with the accessory kit supersede these instructions, if different.
3.2 Block Heaters
Block heaters are available as loose accessories. Use block heaters on standby applications where the generator set is frequently subjected to temperatures below 0
_C (32_F).
The generator set engine is equipped with valves that eliminate the need to drain the cooling system before installing the block heater.
Refer to the installation instructions provided with the block heater kit.
Connect the block heater to a power source that is energized when the generator set is not running.
Note: Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm and refill the radiator to purge the air from the system before energizing the block heater.
GM78529
1
1. Block heater
Figure 3-2 Block Heater
TP-6809 1/12 Section 3 Accessories 35
3.3 Programmable Interface
Module (PIM)
The optional Programmable Interface Module (PIM) provides two programmable inputs and six dry contact outputsfour of which are programmable. The PIM with enclosure is shown in Figure 3-3. See TT-1584 for PIM installation and connection instructions.
The PIM is mounted in a NEMA 3R aluminum enclosure, which can be mounted indoors or outdoors. See Section
2.2.6 and the installation instructions provided with the
PIM for the maximum recommended cable lengths and detailed installation instructions.
3.3.1
PIM to Generator Set Connections
The PIM communicates with the RDC2 generator set controller. Connect the PIM module to the generator set as shown in Section 2.2.6.
3.3.2
PIM Inputs and Outputs
Connect customer-supplied equipment to the PIM as instructed in TT-1584.
Factory-default settings for the outputs are shown in
Figure 3-4. The outputs are controlled by the RDC2 controller.
The run output is activated when the generator set is running. The common fault output is activated on a fault.
Use a personal computer running Kohler r OnCuer or
SiteTech t software to assign functions to the other inputs and outputs, and/or change the settings for factory-set inputs and outputs. Verify that the input and output assignments match the connections to the PIM terminal strip.
Outputs 3 through 6 can also be controlled remotely using the OnCue r program. If an output is activated or deactivated through OnCue, it is no longer controlled by the RDC2 controller.
See the OnCue Software
Operation Manual for instructions.
PIM Connection Factory Default Setting
Input 1 None
Input 2 None
Output 1 (Relay 1) Run
Output 2 (Relay 2) Common Fault
Output 3 (Relay 3) Low Battery Voltage (programmable)
Output 4 (Relay 4) Not in Auto (programmable)
Output 5 (Relay 5) Cooldown (programmable)
Output 6 (Relay 6) Normal Source Failure
(programmable)
Figure 3-4 PIM Factory Settings
ADV--8199
Figure 3-3 Programmable Interface Module (PIM)
(covered removed for illustration)
36 Section 3 Accessories TP-6809 1/12
3.4 Load Control Module (LCM)
The optional Load Control Module (LCM) provides an automatic load management system to comply with
Section 702.5 of NEC 2008. The installer is responsible for ensuring that the power system installation complies with all applicable state and local codes.
The LCM automatically manages up to six residential loads. Four power relays are provided for management of non-essential secondary loads, and two relays are available to control two independent air conditioner loads.
Note: Connect only non-essential loads to the load control module.
The load on the generator set is monitored, and loads are added or shed in the order of their priority.
The LCM is available with or without a pre-wired harness for load relay connection. The prewire harness requires installation of the LCM within 2 feet of the distribution panel. The load control module with the optional wire harness is shown in Figure 3-5. If the harness is not used, connect to the terminal blocks inside the LCM enclosure. Figure 3-6 shows the load control module without the optional harness.
Current transformers (CTs) on the emergency source lines are required for LCM operation.
The CTs are included with the LCM kits. Installation of the CTs inside the transfer switch enclosure is recommended.
See TT-1574 for detailed installation and connection instructions.
Figure 3-5 Load Control Module (shown with optional wire harness)
TP-6809 1/12
Figure 3-6 Load Control Module (cover removed to show field-connection terminal blocks)
Section 3 Accessories 37
3.5 OnCue Home Generator
Management System
The OnCue t Home Generator Management System allows monitoring and control of your generator set from a personal computer located in your home or at other remote locations. OnCue can also be configured to send email or text message notifications in the event of a generator set fault.
See TP-6796, OnCue Software
Operation Manual, for software instructions.
The OnCue system is available separately as a loose kit.
Use category 5E network cable to connect the RDC2 controller to the customer-supplied Ethernet router and cable or DSL modem.
Route the cable with other low-voltage signal wiring (for example, the RBUS communication leads or engine start leads to the transfer switch), in separate conduit from the AC load leads. If the network cable is longer than 100 meters
(328 ft.), use a repeater or switch.
Recommended: Use a laptop computer to verify the network connection before connecting to the generator set.
Checking the network connection
1. Check for and turn OFF any wireless connections to the laptop.
2. Connect the network cable to the laptop. Connect the other end of the network cable to the customer’s router or modem.
3. Verify the Internet connection by opening your web browser and going to www.kohlerpower.com or another website.
4. After verifying the connection through the network cable, disconnect the network cable from the laptop and turn the laptop wireless connections back on.
Connect to the Ethernet cable in the customer connection area of the generator set. See Figure 3-7.
Use an RJ45 inline coupler, provided with the OnCue kit, to connect the customer’s Ethernet cable to the cable in the customer connection box.
1
1. Connect to Ethernet cable in customer connection box.
Figure 3-7 Network Connection for OnCue
38 Section 3 Accessories TP-6809 1/12
Section 4 Generator Reconnection
4.1 Voltage Reconnection
The reconnection procedure explains voltage reconnections only.
Do not attempt to change the frequency (e.g. from 60 Hz to 50 Hz) in the field.
The following instructions explain the reconnection of
12-lead generator sets. In all cases, follow the National
Electrical Code (NEC) guidelines.
Reconnect the stator leads of the generator set if a different output phase or voltage is desired. Refer to the following procedure and the connection schematics.
Follow all safety precautions at the front of this manual and in the text while performing this procedure.
Note: Order voltage reconnection decal 246242 from an authorized service distributor/dealer and affix decal to generator set after reconnecting to a voltage different than the nameplate.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set.
Remove the negative (--) lead first when disconnecting the battery.
Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set.
Accidental starting can cause severe injury or death.
Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
WARNING
Hazardous voltage.
Moving parts.
Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Ensure you comply with all applicable codes and standards.
Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Short circuits.
Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage.
Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
TP-6809 1/12 Section 4 Generator Reconnection 39
4.2 Four-Lead (Single-Phase)
Generator Sets
Figure 4-1 shows the factory connection for the singlephase 120/240 V 60 Hz generator set.
Four-lead, single-phase models are not reconnectable.
ADV-5857-A
Figure 4-1 Single-Phase Factory Connection,
120/240 V 60 Hz
4.3 12-Lead (Three-Phase)
Generator Sets
Note: The current transformers (CTs) shown on the following diagrams are not used on generator sets equipped with the RDC2 controller.
Three-phase, 12-lead generator sets are reconnectable to the voltages and phases shown on the generator set specification sheet.
See Figure 4-2 and use the following procedure to reconnect the generator to the desired voltage configuration, change the system voltage setting, and adjust the output voltage.
Note: Equipment damage.
Verify that the voltage ratings of the transfer switch, line circuit breakers, and other accessories match the selected line voltage.
Reconnection Procedure
1. Press the OFF button on the RDC2 controller.
2. Disconnect engine starting battery, negative (--) lead first.
3. Disconnect utility power to the generator set.
4. Select desired voltage connection from Figure 4-2.
Connect the leads according to the diagram for desired phase and voltage.
5. Reconnect generator set engine starting battery, negative (--) lead last.
6. Follow the instructions in Section 4.4 to enter the
RDC2 Genset System menu. Check the system voltage, frequency, and phase settings, and change them if necessary.
7. Connect a digital multimeter (DVM) to the generator set output.
8. Follow the instructions in Section 4.5 to start the generator set and enter the VR Adjust menu.
9. Use a voltmeter to check for the correct voltage.
Adjust output voltage, if necessary, using the
RDC2 Voltage Regulator menu.
10. Stop the generator set after the adjustment procedure.
40 Section 4 Generator Reconnection TP-6809 1/12
Note: The current transformers (CTs) shown are not used on generator sets equipped with the RDC2 controller.
Figure 4-2 12-Lead Generator Reconnection
TP-6809 1/12
ADV-5875B-J
Section 4 Generator Reconnection 41
4.4 Changing System Settings
The RDC2 controller’s keypad and display allow the installer to check and change the generator system settings, if necessary. The system settings for each generator model are set at the factory and should not normally require changes. Check the genset system settings and change them, if necessary, after generator reconnection or controller replacement.
The following procedure explains how to change the system settings. The procedure is also illustrated in
Figure 4-5.
Procedure to Change System Settings
1. Press the Select button to enter the main menu.
See Figure 4-3 and Figure 4-4.
The Overview screen will be displayed.
2. Press the down arrow button to navigate to the
Genset System menu. See Figure 4-4.
3. Press the Select button to enter the Genset System menu. See Figure 4-5.
4. Press the down arrow button to step through the generator set system settings.
5. To change any of the genset system settings, press and hold the Select button until Editing Enabled is displayed. Release the select button.
6. Use the down arrows to step to the setting that you wish to change.
7. When the setting is displayed (for example,
System Voltage), press the select button.
The value will flash.
8. Press the up or down arrow buttons to increase or decrease the setting.
9. When the desired setting is shown, press Select.
The value stops flashing.
10. Press the down arrow to step to the next setting.
11. To exit, press the down arrow button until Return is displayed.
Press the Select button to exit the menu.
12. Press the AUTO or OFF button to exit the main menu.
Note: If no buttons are pushed, the controller exits the menus and returns to the generator set status display after 5 minutes.
1
3
1. Display
2. Select button
3. AUTO button
Figure 4-3 RDC2 Controller
2
GM77569
42 Section 4 Generator Reconnection TP-6809 1/12
Status
Displays
Overview ---->
1.2 h
Engine ---->
Metering
Generator---->
Metering
Genset ---->
Information
Genset ---->
Run Time
System voltage, frequency, and phase adjustments are in the Genset System menu.
Genset ---->
System
ATS
Status
---->
* ATS configuration appears only if a Model RXT transfer switch is connected.
Figure 4-4 RDC2 Main Menu
ATS ---->
Configuration *
Date and Time
---->
Network ---->
Information
PIM
Status
---->
Load
Control
---->
Event Log----> tp6810
TP-6809 1/12 Section 4 Generator Reconnection 43
Changing System Settings on the RDC2 Controller
1. Press the Select button to enter the main menu.
Press: Display:
Overview ---->
1.2 h
7. When the desired setting is shown, press Select.
The value stops flashing.
Press: Display:
System Voltage
220 V
2. Press the down arrow button to navigate to the
Genset System menu. See Figure 4-4.
8. Press the down arrow to step to the next setting.
Press:
Display:
Genset
System
---->
Press: Display:
System Freq:
60 Hz
3. Press the Select button to enter the genset system menu.
Press: Display:
System Voltage:
240 V
9. To exit, press the down arrow button until Return is displayed.
---->
Press: Display:
Return
4. Press the down arrow button, if necessary, to step to the setting that you want to change.
5. When the setting is displayed (for example,
System Voltage), press the select button. The value will flash.
Press: Display:
System Voltage
240 V
10. Press the Select button to exit the menu.
Press: Display:
Overview ---->
1.2 h
6. Press the up or down arrow buttons to increase or decrease the setting.
11. Press Auto to signal the controller to exit the menus and return to the generator set status display.
Press:
Display:
Genset State
Standby
AUTO
Press:
Display:
System Voltage
220 V
Note: If no buttons are pushed, the controller returns to the status display after 5 minutes.
Figure 4-5 Changing Genset System Settings
44 Section 4 Generator Reconnection TP-6809 1/12
4.5 Voltage Adjustments
WARNING
Hazardous voltage.
Moving parts.
Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
Short circuits.
Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage.
Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
After reconnection, check the voltage and adjust it, if necessary. The controller’s adjustment mode allows adjustment of the output voltage. Have adjustments performed by an authorized Kohler distributor/ dealer or service technician.
Note: A digital voltmeter is required for these adjustments.
Use a voltmeter to check the output voltage. If the output voltage is not within specifications, use the ADC controller to adjust the output voltage while the generator set is running.
Refer to Figure 4-5 for general instructions and
Figure 4-6 for the voltage adjustment menus.
Voltage Adjustment Procedure
1. With the generator set off, connect a digital multimeter to the output leads or an electrical outlet on the load side of the generator set. Set the meter to measure AC voltage.
2. Start the generator set by pressing the RUN button on the RDC2 controller.
3. Navigate to the Genset System menu and then to the VR Voltage Adjust menu. See Figure 4-4.
4. Press the Select button. The voltage flashes to show that it can be changed. Press the up or down arrow button to adjust the voltage until the desired voltage is shown on the voltmeter. See Figure 4-6 for adjustment instructions.
5. Press Select to save the voltage setting.
6. Exit the Voltage Regulator menu as described in
Figure 4-5.
7. Stop the generator set by pressing OFF or AUTO on the RDC2 controller.
TP-6809 1/12 Section 4 Generator Reconnection 45
Genset ---->
System
System Voltage:
240 V
System Freq:
60 Hz
VR Voltage Adj:
240.0V
System Phase:
Single
System Battery:
12 V
<---Return
Figure 4-6 Output Voltage Adjustments
System Voltage:
240 V
Press the Up or Down arrow button to change the setting.
Press the Select button to save the setting and move to the next screen.
System Freq:
60 Hz
VR Voltage Adj:
240.0V
System Phase:
Single tp6809
46 Section 4 Generator Reconnection TP-6809 1/12
Section 5 Diagrams and Drawings
This section contains dimension drawings, wiring diagrams, and schematics for the enclosed generator set. Figure 5-1 lists the drawing numbers and page numbers.
Drawing Description
Dimension Drawing:
Dimensions
Installation clearances
Wiring Diagrams:
Schematic:
Sheet 1
Sheet 2
Alternator
Wiring Diagram:
Sheet 1
Sheet 2
Drawing Number
ADV-7962, 1 of 2
ADV-7962, 2 of2
ADV-8061, 1 of 2
ADV-8061, 2 of 2
ADV-6957
GM79871, 1 of 2
GM79871, 2 of 2
Figure 5-1 Drawing Numbers and Locations
See the generator set Operation Manual for service views, if necessary.
Page
48
49
50
51
52
53
54
TP-6809 1/12 Section 5 Diagrams and Drawings 47
Figure 5-2 Dimension Drawing, ADV-7962 sheet 1
48 Section 5 Diagrams and Drawings TP-6809 1/12
Figure 5-3 Dimension Drawing, Installation Clearances, ADV-7962, Sheet 2
TP-6809 1/12 Section 5 Diagrams and Drawings 49
Figure 5-4 Schematic Diagram, ADV-8061 Sheet 1
50 Section 5 Diagrams and Drawings TP-6809 1/12
Figure 5-5 Schematic Diagram, ADV-8061 Sheet 2
TP-6809 1/12 Section 5 Diagrams and Drawings 51
Figure 5-6 Schematic, Alternator, ADV-6957
52 Section 5 Diagrams and Drawings TP-6809 1/12
Figure 5-7 Wiring Diagram GM79871 Sheet 1
TP-6809 1/12 Section 5 Diagrams and Drawings 53
Figure 5-8 Wiring Diagram GM79871 Sheet 2
54 Section 5 Diagrams and Drawings TP-6809 1/12
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
CARB
CAT5
CB
CC cc
CCA ccw.
CEC cert.
cfh
A, amp ampere
ABDC after bottom dead center
AC
A/D
ADC adj.
ADV alternating current analog to digital advanced digital control; analog to digital converter adjust, adjustment
Ah
AHWT
AISI advertising dimensional drawing amp-hour anticipatory high water temperature
American Iron and Steel
Institute
ALOP alt.
anticipatory low oil pressure alternator aluminum Al
ANSI American National Standards
Institute (formerly American
Standards Association, ASA) anticipatory only AO
APDC
API
Air Pollution Control District
American Petroleum Institute approx.
approximate, approximately
APU Auxiliary Power Unit
AQMD Air Quality Management District
AR
AS
ASE
ASME as required, as requested as supplied, as stated, as suggested
American Society of Engineers
American Society of
Mechanical Engineers assy.
ASTM
ATDC
ATS auto.
aux.
avg.
AVR
AWG
AWM assembly
American Society for Testing
Materials after top dead center automatic transfer switch automatic auxiliary average automatic voltage regulator
American Wire Gauge appliance wiring material bat.
BBDC
BC
BCA
BCI
BDC battery before bottom dead center battery charger, battery charging battery charging alternator
Battery Council International before dead center
BHP blk.
brake horsepower black (paint color), block
(engine) blk. htr.
block heater
BMEP bps br.
BTDC
Btu brake mean effective pressure bits per second brass before top dead center
British thermal unit
Btu/min.
British thermal units per minute
C Celsius, centigrade cal.
CAN calorie controller area network
California Air Resources Board
Category 5 (network cable) circuit breaker crank cycle cubic centimeter cold cranking amps counterclockwise
Canadian Electrical Code certificate, certification, certified cubic feet per hour cfm
CG
CID
CL cm
CMOS
EPS
ER
ES
ESD est.
E-Stop etc.
cubic feet per minute center of gravity cubic inch displacement centerline centimeter complementary metal oxide substrate (semiconductor) com coml communications (port) commercial
Coml/Rec Commercial/Recreational conn.
connection cont.
continued
CPVC crit.
CSA chlorinated polyvinyl chloride critical
Canadian Standards
Association current transformer CT
Cu cUL
CUL cu. in.
cw.
copper
Canadian Underwriter’s
Laboratories
Canadian Underwriter’s
Laboratories cubic inch
CWC cyl.
D/A
DAC dB clockwise city water-cooled cylinder digital to analog digital to analog converter decibel dB(A)
DC
DCR deg.,
° dept.
dia.
DI/EO
DIN decibel (A weighted) direct current direct current resistance degree
DIP
DPDT
DPST
DS disconnect switch
DVR
E
2 digital voltage regulator
PROM, EEPROM electrically-erasable programmable read-only memory
E, emer.
emergency (power source)
ECM
EDI
EFR double-pole, double-throw double-pole, single-throw electronic control module, engine control module electronic data interchange e.g.
EG
EGSA
EIA department diameter dual inlet/end outlet
Deutsches Institut fur Normung e. V. (also Deutsche Industrie
Normenausschuss) dual inline package emergency frequency relay for example (exempli gratia) electronic governor
Electrical Generating Systems
Association
Electronic Industries
Association
EI/EO
EMI emiss.
eng.
EPA end inlet/end outlet electromagnetic interference emission engine
Environmental Protection
Agency emergency power system emergency relay engineering special, engineered special electrostatic discharge estimated emergency stop et cetera (and so forth)
TP-6809 1/12 Appendix 55 exh.
ext.
F
FHM fl. oz.
flex.
freq.
FS ft.
ft. lb.
ft./min.
ftp g ga.
gal.
gen.
genset
GFI exhaust external
Fahrenheit, female flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute file transfer protocol gram gauge (meters, wire size) gallon generator generator set ground fault interrupter hex
Hg
HH
HHC
HP hr.
HS hsg.
HVAC
GND, gov.
gph gpm gr.
ground governor gallons per hour gallons per minute grade, gross
GRD gr. wt.
equipment ground gross weight
H x W x D height by width by depth
HC hex cap
HCHT
HD
HET high cylinder head temperature heavy duty high exhaust temp., high engine temp.
hexagon mercury (element) hex head hex head cap horsepower hour heat shrink housing heating, ventilation, and air conditioning
HWT
Hz
IBC
IC
ID
IEC
IEEE high water temperature hertz (cycles per second)
International Building Code integrated circuit inside diameter, identification
International Electrotechnical
Commission
Institute of Electrical and
Electronics Engineers
IMS in.
improved motor starting inch in. H
2 in. Hg
O inches of water inches of mercury in. lb.
Inc.
ind.
inch pounds incorporated industrial int.
internal int./ext.
internal/external
I/O
IP
ISO
J
JIS input/output internet protocol
International Organization for
Standardization joule
Japanese Industry Standard k
K kA
KB
KBus kg kilo (1000) kelvin kiloampere kilobyte (2
10 bytes)
Kohler communication protocol kilogram
kph kV kVA kVAR kW kWh kWm kWth kg/cm kgm kg/m
3 kHz
2 kilograms per square centimeter kilogram-meter kilograms per cubic meter kilohertz kJ kilojoule km kilometer kOhm, k
Ω kilo-ohm kPa kilopascal kilometers per hour kilovolt kilovolt ampere kilovolt ampere reactive kilowatt kilowatt-hour kilowatt mechanical kilowatt-thermal
L
LAN liter local area network
L x W x H length by width by height lb.
lbm/ft
3 pound, pounds pounds mass per cubic feet
LCB line circuit breaker
LCD
LED
Lph liquid crystal display light emitting diode liters per hour
Lpm
LOP
LP
LPG liters per minute low oil pressure liquefied petroleum liquefied petroleum gas left side LS
L wa
LWL sound power level, A weighted low water level
LWT low water temperature m
M meter, milli (1/1000) mega (10
6 when used with SI units), male m m m
3
3
3
/hr.
cubic meter cubic meters per hour
/min.
cubic meters per minute mA milliampere man.
max.
MB
MCCB
MCM manual maximum megabyte (2
20 bytes) molded-case circuit breaker one thousand circular mils meggar megohmmeter
MHz megahertz mi.
mil min.
misc.
MJ mile one one-thousandth of an inch minimum, minute miscellaneous megajoule mJ millijoule mm millimeter mOhm, m
Ωmilliohm
MOhm, M
Ωmegohm
MOV metal oxide varistor
MPa megapascal mpg mph
MS ms m/sec.
mtg.
MTU
MW miles per gallon miles per hour military standard millisecond meters per second mounting
Motoren-und Turbinen-Union megawatt mW
μF milliwatt microfarad
N, norm.
normal (power source)
NA not available, not applicable nat. gas natural gas
NBS National Bureau of Standards psi psig pt.
PTC
PTO
PVC qt.
qty.
R
OV oz.
p., pp.
PC
PCB pF
PF ph.,
∅
PHC
NC
NEC
NEMA normally closed
National Electrical Code
National Electrical
Manufacturers Association
NFPA
Nm
NO
National Fire Protection
Association newton meter normally open no., nos.
number, numbers
NPS National Pipe, Straight
NPSC
NPT
National Pipe, Straight-coupling
National Standard taper pipe thread per general use
National Pipe, Taper-Fine NPTF
NR ns
OC
OD
OEM not required, normal relay nanosecond overcrank outside diameter original equipment manufacturer overfrequency OF opt.
OS
OSHA option, optional oversize, overspeed
Occupational Safety and Health
Administration
PHH
PHM
PLC
PMG pot ppm
PROM overvoltage ounce page, pages personal computer printed circuit board picofarad power factor phase
Phillips r head Crimptiter
(screw)
Phillips r hex head (screw) pan head machine (screw) programmable logic control permanent magnet generator potentiometer, potential rad.
RAM
RBUS parts per million programmable read-only memory pounds per square inch pounds per square inch gauge pint positive temperature coefficient power takeoff polyvinyl chloride quart, quarts quantity replacement (emergency) power source radiator, radius random access memory
RS-485 proprietary communications
RDO ref.
rem.
relay driver output reference remote
Res/Coml Residential/Commercial
RFI radio frequency interference
RH
RHM round head round head machine (screw) rly.
rms rnd.
RO
ROM rot.
rpm
RS
RTDs relay root mean square round read only read only memory rotate, rotating revolutions per minute right side
Resistance Temperature
Detectors
RTU
RTV
RW
SAE scfm
SCR s, sec.
SI
SI/EO sil.
SMTP
SN
SNMP
UF
UHF
UIF
UL
UNC
UNF univ.
URL
TDOE
TDON temp.
term.
THD
TIF tol.
turbo.
typ.
std.
stl.
tach.
TB
TCP
TD
TDC
TDEC
TDEN
SPDT
SPST spec specs sq.
sq. cm sq. in.
SMS
SS
TDES
TDNE
US
UV
V
VAC
VAR
VDC
VFD
VGA
VHF
W
WCR w/
WO w/o wt.
xfmr remote terminal unit room temperature vulcanization read/write
Society of Automotive
Engineers standard cubic feet per minute silicon controlled rectifier second
Systeme international d’unites,
International System of Units side in/end out silencer simple mail transfer protocol serial number simple network management protocol single-pole, double-throw single-pole, single-throw specification specification(s) square square centimeter square inch short message service stainless steel standard steel tachometer terminal block transmission control protocol time delay top dead center time delay engine cooldown time delay emergency to normal time delay engine start time delay normal to emergency time delay off to emergency time delay off to normal temperature terminal total harmonic distortion telephone influence factor tolerance turbocharger typical (same in multiple locations) underfrequency ultrahigh frequency user interface
Underwriter’s Laboratories, Inc.
unified coarse thread (was NC) unified fine thread (was NF) universal uniform resource locator
(web address) undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt withstand and closing rating with write only without weight transformer
56 Appendix TP-6809 1/12
Notes
TP-6809 1/12 57
Notes
58 TP-6809 1/12
TP-6809 1/12
E 2012 by Kohler Co. All rights reserved.
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455