400518-04 EP-P Reference Manual

400518-04 EP-P Reference Manual
Reference Manual
Epsilon EP-P
Servo Drive
"MOTION MADE EASY" ®
Part Number: 400518-04
Revision: A3
Date: April 30, 2010
© Control Techniques Americas LLC, 2006-2010
Epsilon EP-P Drive Reference Manual
Information furnished by Control Techniques Americas LLC (Control Techniques) is believed to be accurate and reliable. However,
no responsibility is assumed by Control Techniques for its use. Control Techniques reserves the right to change the design or
operation of the equipment described herein and any associated motion products without notice. Control Techniques also assumes
no responsibility for any errors that may appear in this document. Information in this document is subject to change without notice.
P/N 400518-04
Revision: A3
Date: April 30, 2010
© Control Techniques Americas LLC, 2006 - 2010
© Control Techniques Americas LLC, 2006-2010 All rights reserved.
Part Number: 400518-04
Revision: A3
Date: April 2010
Printed in United States of America
Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any
form or by any means, electronic or mechanical, for any purpose, without the express written permission of Control Techniques.
The following are trademarks of Control Techniques and may not be reproduced in any fashion without written approval of Control
Techniques: AXIMA, “Motion Made Easy”, and Position Tracker
Control Techniques is a division of EMERSON Co.
Control Techniques, Inc. is not affiliated with Microsoft Corporation, owner of the Microsoft, Windows, and Windows NT
trademarks.
This document has been prepared to conform to the current released version of the product. Because of our extensive development
efforts and our desire to further improve and enhance the product, inconsistencies may exist between the product and documentation
in some instances. Call your customer support representative if you encounter an inconsistency.
ii
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Customer Support
Control Techniques Americas LLC
12005 Technology Drive
Eden Prairie, Minnesota 55344-3620
U.S.A.
Telephone: (952) 995-8000 or (800) 893-2321
It is Control Techniques’ goal to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to
providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it’s by
phone, fax or modem, you can access Control Techniques support information 24 hours a day, seven days a week. Our wide range of
services include:
FAX
(952) 995-8099
You can FAX questions and comments to Control Techniques. Just send a FAX to the number listed above.
Website and Email
www.emersonct.com
Website: www.emersonct.com
Email: [email protected]
If you have Internet capabilities, you also have access to technical support using our website. The website includes technical notes,
frequently asked questions, release notes and other technical documentation. This direct technical support connection lets you request
assistance and exchange software files electronically.
Technical Support
(952) 995-8033 or (800) 893-2321
Email: [email protected]
Control Techniques’ “Motion Made Easy” products are backed by a team of professionals who will service your installation. Our technical
support center in Eden Prairie, Minnesota is ready to help you solve those occasional problems over the telephone. Our technical support
center is available 24 hours a day for emergency service to help speed any problem solving. Also, all hardware replacement parts, if
needed, are available through our customer service organization.
When you call, please be at your computer, with your documentation easily available, and be prepared to provide the following
information:
•
Product version number, found by choosing About from the Help menu
•
The type of controller or product you are using
•
Exact wording of any messages that appear on your screen
•
What you were doing when the problem occurred
• How you tried to solve the problem
Need on-site help? Control Techniques provides service, in most cases, the next day. Just call Control Techniques’ technical support
center when on-site service or maintenance is required.
Training Services
(952) 995-8000 or (800) 893-2321
Email: [email protected]
Control Techniques maintains a highly trained staff of instructors to familiarize customers with Control Techniques’ “Motion Made Easy”
products and their applications. A number of courses are offered, many of which can be taught in your plant upon request.
Application Engineering
(952) 995-8000 or (800) 893-2321
Email: [email protected]
An experienced staff of factory application engineers provides complete customer support for tough or complex applications. Our
engineers offer you a broad base of experience and knowledge of electronic motion control applications.
Customer Service (Sales)
(952) 995-8000 or (800) 893-2321
Email: [email protected]
Authorized Control Techniques distributors may place orders directly with our Customer Service department. Contact the Customer
Service department at this number for the distributor nearest you.
Epsilon EP-P Drive Reference Manual
Revision A3
iii
www.emersonct.com
Document Conventions
Manual conventions have been established to help you learn to use this manual quickly and easily. As much as possible, these conventions correspond to
those found in other Microsoft® Windows® compatible software documentation.
Menu names and options are printed in bold type: the File menu.
Dialog box names begin with uppercase letters: the Axis Limits dialog box.
Dialog box field names are in quotes: “Field Name.”
Button names are in italic: OK button.
Source code is printed in Courier font: Case
ERMS.
In addition, you will find the following typographic conventions throughout this manual.
This
Represents
bold
Characters that you must type exactly as they appear. For example, if you are directed to type
a:setup, you should type all the bold characters exactly as they are printed.
italic
Placeholders for information you must provide. For example, if you are directed to type
filename, you should type the actual name for a file instead of the word shown in italic type.
ALL CAPITALS
Directory names, file names, key names, and acronyms.
SMALL CAPS
Non-printable ASCII control characters.
KEY1+KEY2
example: (Alt+F)
A plus sign (+) between key names means to press and hold down the first key while you press
the second key.
KEY1,KEY2
example: (Alt,F)
A comma (,) between key names means to press and release the keys one after the other.
Reference Materials
The following related reference and installation manuals may be useful with your particular system.
•
Epsilon EP Installation Manual (P/N 400518-01)
•
Epsilon EP Connectivity Manual (P/N 400518-05)
iv
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Safety Information
Safety Precautions
This product is intended for professional incorporation into a complete system by qualified persons. If you install the product
incorrectly, it may present a safety hazard. The product and system may use high voltages and currents, carry a high level of
stored electrical energy, or are used to control mechanical equipment that can cause injury.
You must give close attention to the electrical installation and system design to avoid hazards either in normal operation or in
the event of equipment malfunction. System design, installation, commissioning and maintenance must be carried out by
personnel who have the necessary training and experience. Read and follow this safety information and this instruction manual
carefully.
Qualified Person
For the purpose of this manual and product, a “qualified person” is one who is familiar with the installation, construction and
operation of the equipment and the hazards involved. In addition, this individual has the following qualifications:
Is trained and authorized to energize, de-energize, clear and ground and tag circuits and equipment in accordance with
established safety practices.
Is trained in the proper care and use of protective equipment in accordance with established safety practices.
Is trained in rendering first aid.
Enclosure
This product is intended to be mounted in an enclosure that prevents access except by qualified persons and that prevents the
ingress of contamination. This product is designed for use in an environment classified as pollution degree 2 in accordance with
IEC664-1. This means that only dry, non-conducting contamination is acceptable.
Setup, Commissioning and Maintenance
It is essential that you give careful consideration to changes to drive settings. Depending on the application, a change could
have an impact on safety. You must take appropriate precautions against inadvertent changes or tampering. Restoring default
parameters in certain applications may cause unpredictable or hazardous operation.
Safety of Machinery
Within the European Union all machinery in which this product is used must comply with Directive 89/392/EEC, Safety of
Machinery.
The product has been designed and tested to a high standard, and failures are very unlikely. However the level of integrity
offered by the product’s control function – for example stop/start, forward/reverse and maximum speed – is not sufficient for
use in safety-critical applications without additional independent channels of protection. All applications where malfunction
could cause injury or loss of life must be subject to a risk assessment, and further protection provided where needed.
Identification of Safety Information
Safety related information through out this manual is identified with the following markings.
“Warning” indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
WARNING
“Caution” indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury.
CAUTION
NOTE
For the purpose of this manual and product, “Note” indicates essential information about the product or the respective part
of the manual
Throughout this manual, the word "drive" refers to an Epsilon EP-P drive.
Epsilon EP-P Drive Reference Manual
Revision A3
v
www.emersonct.com
General warning
Failure to follow safe installation guidelines can cause death or serious injury. The voltages used in this unit can cause
severe electric shock and/or burns, and could be lethal. Extreme care is necessary at all times when working with or
adjacent to this equipment. The installation must comply with all relevant safety legislation in the country of use.
Supply isolation device
The AC supply or high voltage DC supply must be removed from the drive using an approved isolation device or disconnect
before any servicing work is performed, other than adjustments to the settings or parameters specified in the manual. The
drive contains capacitors which remain charged to a potentially lethal voltage after the supply has been removed. Allow at
least 6 minutes for Epsilon EP206/209/216 and 3 minutes for Epsilon EP202/204 after removing the supply before carrying
out any work which may involve contact with electrical connections to the drive.
Products connected by plug and socket
A special hazard may exist where the drive is incorporated into a product which is connected to the AC supply by a plug
and socket. When unplugged, the pins of the plug may be connected to the drive input, which is only separated from the
charge stored in the bus capacitor by semiconductor devices. To avoid any possibility of electric shock from the pins, if they
are accessible, a means must be provided for automatically disconnecting the plug from the drive (e.g., a latching
contactor).
Grounding (Earthing, equipotential bonding) - High Leakage Current
The drive must be grounded by a conductor sufficient to carry all possible fault current in the event of a fault. This
equipment has high earth leakage current. You must comply with local safety regulations with respect to minimum size and
special installation requirements on the protective earth conductor for high leakage current equipment. The ground
connections shown in the manual must be followed.
Fuses
Fuses or over-current protection must be provided at the input in accordance with the instructions in the manual.
The drive alone does not provide branch circuit protection. Branch circuit protection must be provided in accordance with
the National Electrical Code and any additional local codes.
Isolation of control circuits
The installer must ensure that the external control circuits are isolated from human contact by at least one layer of
insulation rated for use at the applied AC supply voltage. External control circuits identified as PELV circuits do not need
this isolation when they are completely within a zone of equipotential bonding, generally within a single enclosure or group
of enclosures bonded together.
vi
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Table of Contents
Customer Support
iii
Safety Information
v
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualified Person . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup, Commissioning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety of Machinery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification of Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
v
v
v
v
v
v
1
Epsilon EP Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Operational Overview
3
Software Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PowerTools Pro Setup Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
How Motion Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
How Jogging Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
How Home Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Home Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Establishing a Home Reference Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Accuracy and Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Home Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
End of Home Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Home Limit Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Home Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
How Indexes Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Absolute vs. Incremental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
How Communications Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Configuring Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Upload Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Downloading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Change Path Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
NVM Options for Uploading and Downloading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Updating to RAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Options/Preferences/Ptools Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Secure Downloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Brake Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
How Data Capture Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Navigating the Graph Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Setting Up Parameters
23
Status View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Status Online Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Motor Position Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Motor Velocity Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control Loop Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Master Feedback Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Torque Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Information Tab (Online Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Drive Information Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Graph View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Epsilon EP-P Drive Reference Manual
Revision A3
vii
www.emersonct.com
Data Capture Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Timing Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identification Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drive Encoder Output Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positive Direction Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Update Rate Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching Frequency Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Type List Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use Motor Data From .ddf File Check box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Parameters Column . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run Auto-Tune Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Values from Drive Column. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Apply to Config. Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Save .ddf Values Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User Units View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Distance Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Velocity Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acceleration Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual Loop View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Dual Loop Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position Encoder Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sync Output Connector Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual Loop Encoder Ration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Units View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Encoder Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sync Output Connector Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Position Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Distance Units Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Velocity Units Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Acceleration Units Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Master Position Filter Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Virtual Master View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enable Virtual Master Check Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Virtual Master Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Virtual Master Conversion Ratio Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Feedrate Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limits Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotary Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Tab (not shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Velocity View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Tab (not shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ramps View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ramps Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limits Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Peak Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viii
www.emersonct.com
25
25
26
27
27
28
28
28
28
29
29
29
29
30
31
33
33
33
35
35
36
36
36
37
37
37
38
38
38
38
39
39
39
39
39
39
40
40
41
41
41
41
42
42
43
43
43
44
45
45
45
47
48
48
48
48
48
Epsilon EP-P Drive Reference Manual
Revision: A3
Distance Recovery View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Gear and Camming Distance Recovery Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Tuning View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Load Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Low Pass Filter Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Tuning Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Position Error Integral Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Shunt View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
External Shunt Resistor Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Shunt Control Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Faults View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Active Faults Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Power Up Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Fault Log Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Fault Counts Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Drive Fault Log Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Setup NVM View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Devices / Vars Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
PLS View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Capture View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Queues View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Queue Sources and Destinations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Timers View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Timer Signals/Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Using Timers within Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Variables View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Adding and Deleting Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Using Variables in a Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Bits View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Adding and Deleting User Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
User 32-bit Bit Register and User Bit Masking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Configuring the User Bit Mask Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Packed Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Packed Bits Control Words View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pack Bits Status Words View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
I/O Setup Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Assignments View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Creating An Assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Deleting An Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Assignment Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
User Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Only Show Assigned Check Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Assignments that Automatically Use Position Capture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Selector View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Input Lines View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Output Lines View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Analog Inputs View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Enable Channel Check Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Set Maximums Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Set Minimums Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
A/D Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
ValueIn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Read Max/Min Voltage Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Analog Outputs View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Enable Channel Check Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Epsilon EP-P Drive Reference Manual
Revision A3
ix
www.emersonct.com
Maximum Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Maximum Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Minimum Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Minimum Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Motion Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Jog View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Jog Sources and Destinations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Home View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Home Sources and Destinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Index View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Timed Indexes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Index Sources and Destinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Adding and Deleting Indexes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Gearing View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Use Scale Check Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Gear Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Acc/Dec Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Camming View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Cam Table Plot Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Torque Mode View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Torque Mode Settings Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Velocity Limiting Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Multiple Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Stopping Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
MotionStop from a Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
MotionStop from an Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Profile.#.MotionStop from a Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Profile.#.MotionStop from an Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Network Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Modbus RTU/TCP View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Modbus Master View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
DeviceNet View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Profibus View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Ethernet View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Programming
111
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Toolbar Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Multi-Tasking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Instruction Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Flow Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Math Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Array Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motion Modifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Slave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adding and Deleting Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PowerTools Toolbar Button Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Tools Menu Bar Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Right Click Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run Anytime Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Blocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
x
www.emersonct.com
111
111
115
121
121
125
126
126
132
133
136
136
136
136
136
137
139
Epsilon EP-P Drive Reference Manual
Revision: A3
Parameter Descriptions
145
Tuning Procedures
187
PID vs. State-Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Motor Tuning and Motor Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Tuning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Initial Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Tuning Steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
No Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Basic Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Intermediate Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Fully Optimized Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Tuning Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Determining Tuning Parameter Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Diagnostics and Troubleshooting
193
Diagnostic Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Drive Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Non-Programming Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Programming Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Online Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Watch Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Global Where Am I Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Motion Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Diagnostic Analog Output Test Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Specifications
205
Dimensions and Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Cable Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
EIO26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
XV Motor Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
XTMDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
XCMDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
XCMDBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
XTBMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
XEFTS/XUFTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
XEFCS/XUFSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
NT and MG Motors Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
CMDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
CMMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
CBMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
EFCS / UFCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
SYNC Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
ENCO Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
SNCDD-915 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
SNCFLOA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
SNCMD-815 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
SNCFLI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
SNCMD-89 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
SNCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Communications Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
ESA-SP-485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
ETH-PATCH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Epsilon EP-P Drive Reference Manual
Revision A3
xi
www.emersonct.com
Glossary
225
Index
231
xii
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
1
Introduction
1.1
Epsilon EP Drive
The Epsilon EP drive is a stand-alone, fully digital brushless servo drive designed and built to reliably provide high
performance and flexibility without sacrificing ease of use.
The use of State-Space algorithms make tuning very simple and forgiving. The drives are designed to operate with up to a
10:1 inertia mismatch right out of the box. Higher (50:1 and more) inertial mismatches are possible with two simple parameter
settings.
The Epsilon EP drive can be quickly configured to many applications in less than 5 minutes with Emerson Control Techniques
- PowerTools Pro software on a PC running Windows® 98, 2000, XP (32-bit) or Vista (32-bit).
Complete diagnostics are provided for quick troubleshooting. A diagnostic display on the front of the drive informs the user of
the operational or fault status. The last 10 faults are stored in non-volatile memory along with a time stamp for easy recall.
Shunt Connector (J8)
Diagnostic Display
Reset Button
AC Power Connections
Motor Connections
24 Vdc Logic Power Supply Connections
Serial
Connectors (J2)
DeviceNet Connector (J9)
(EP-IDN or EP-PDN only)
Ethernet
Connector (J4)
(EP-Pxx only)
Digital I/O Connctor (J3)
Sync Input Connector (J10)
Analog/Sync Output
Connector (J5)
Figure 1:
Encoder Feedback Connector (J6)
Epsilon EP-PDN (EP202-206) Drive Feature Location
Epsilon EP-P Drive Reference Manual
Revision A3
1
www.emersonct.com
Shunt Connector (J8)
Status/Diagnostic Display
Reset Button
AC Power Connector
Serial
Connectors (J2)
Motor Power Connections
24 Vdc Logic Power
Supply Connections
Ethernet Connector (J4)
(EP-Pxx only)
Model Number, Part Number,
Revision and Serial Number Label
DeviceNet Connector (J9)
(EP-PDN only)
Sync Input Connector (J10)
Digital I/O Connector (J3)
Profibus Connector (J13)
(EP-PPB only)
Analog/Sync Output
Connector (J5)
Figure 2:
Encoder Feedback Connector (J6)
Epsilon EP-209 Drive Feature Location
Shunt Connector (J8)
Status/Diagnostic Display
24 Vdc Logic Power
Supply Connector
Reset Button
Serial
Connectors (J2)
AC Power Connections
Motor Power Connections
Ethernet Connector (J4)
(EP-Pxx only)
Ethernet Connector (J9)
(EP-PDN only)
Model Number, Part Number,
Revision and Serial Number Label
Sync Input Connector (J10)
Digital I/O Connector (J3)
Profibus Connector (J13)
(EP-PPB only)
Analog/Sync Output
Connector (J5)
Figure 3:
Encoder Feedback Connector (J6)
Epsilon EP-216 Drive Feature Location
2
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
2
Operational Overview
This section provides a complete functional description of the Epsilon EP-P drive. It is intended to provide you, the user, with a
thorough understanding of all operations. The description includes references to many Epsilon EP-P drive parameters which
can be displayed and/or edited using PowerTools Pro software, or through any Modbus interface.
The Epsilon EP-P drive allows the user to set up 100 different Indexes, Jog functions and a Home. The Epsilon EP-P drive
provides fifteen digital inputs and eight digital outputs.
2.1
Software Interface
The Epsilon EP-P drive is set up using PowerTools Pro software. PowerTools Pro is an easy-to-use Windows® based setup
and diagnostics tool. It provides the user with the ability to create, edit and maintain the drive’s setup. You can download or
upload the setup data to or from a drive. The setup data can also be saved to a file on the PC or printed for review or
permanent storage.
2.2
PowerTools Pro Setup Software
PowerTools Pro is designed to be the easiest-to-use software available for single axis motion controllers.
Features
•
“Hierarchy Tree” for quick navigation to any setup view
•
Simple I/O function assignments
•
Powerful online diagnostic capabilities
•
Programming
Figure 4:
Hierarchy Tree
The “Hierarchy Tree” (shown above in the left side) contains expandable groups of parameters. The groups can be expanded
and contracted just like folders in Windows® Explorer. Left click on a view name in the Hierarchy Tree will display that view on
the right side of the computer screen.
To setup a drive the user simply steps through the Hierarchy Tree from top to bottom starting with the Setup view. Simple
applications can be setup in a matter of minutes.
2.3
How Motion Works
The Epsilon EP-P drive provides six types of motion: jogging, homing, indexing, gearing, camming, and torque mode. The
drive will be either in velocity mode or torque mode. What this means is that while the drive is in torque mode, the other types
of motion cannot run. If the other types of motion are active on either profile, the torque mode may not run. It is possible to run
two different velocity mode types of motion at the same time. For instance, gearing could be running on profile zero while an
index is running on profile one. Note that the same instance of a motion type may not run on both profiles at the same time.
This means that while index 0 is running on profile zero, it may not run on profile one. But while index 0 is running on profile
Epsilon EP-P Drive Reference Manual
Revision A3
3
www.emersonct.com
zero, index 1 may run on profile one.
Please note that Indexes and Jogs can be run simultaneously by using the two Profiles, however, Gearing or Camming can only run on one
profile at a time. This means that two indexes or two jogs can run at the same time, but gearing or camming can not be run on multiple profiles
simultaneously.
The Positive direction parameter affects all motion types by specifying which direction of motor revolution (CW or CCW) is considered motion
in the “+” direction.
2.4
How Jogging Works
Jogging produces rotation of the motor at controlled velocities in a positive or negative direction.
Assignments to jogs are level sensitive such that when the jog input is turned on, jogging begins and continues jogging until the jog input is
removed.
Each jog has its own acceleration and deceleration ramp along with a specified velocity. Jogging has no distance parameter associated with it.
If trying to move a specific distance or to a known position, then an index is used.
Jog velocity can be changed on the fly with a negative value reversing the direction. The velocity transition will use the deceleration or
acceleration parameters.
Figure 5:
2.5
Jog View
How Home Works
The Home is used in applications in which the axis must be precisely aligned with some part of the machine. The Home is initiated in one of
three ways: with the Initiate Destination function found in the Assignments view, through a program, or with the Online tab. A Home or Define
Home is required to set the Absolute Position Valid so that any index to absolute position can work.
The Epsilon EP-P drive can home the motor to an external sensor, the motor’s encoder marker pulse, or to a sensor and then to the encoder
marker pulse.
Gear Reducer
External
Home Sensor
NT Motor
with Encoder
Carriage
io
ect
Dir
n
+
Figure 6:
Sensor Point
Home Offset
Distance
Basic Home Function, Example
The figure above show a basic home function using a ball screw. This example uses most of the setup features in the PowerTools Pro Home
4
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
view.
2.5.1
Home Sequence
1.
Back off the sensor, if on the sensor. (This step is optional).
2.
Move to the external home sensor to establish a home reference point.
3.
Next it will move to the Offset position.
4.
Then the command and feedback positions are set to the value entered into the End of Home Position.
Homing to the motor’s encoder marker will establish the most accurate and repeatable home position. This method will
position the motor relative to the location of the rising edge of the encoder marker pulse. Most applications will use a sensor
and marker to find an accurate home position in the vicinity of the home sensor.
Several parameters affect how the Home function operates. Each of these parameters are explained in detail on the following
pages.
NOTE
The Home function will NOT be initiated when any other motion command is in progress.
2.5.2
Establishing a Home Reference Position
The first step in setting up a home is to select the desired home reference type. The Home Reference type selected
determines how the Home Reference Position is established. PowerTools Pro allows selection of one of three different Home
Reference types: Sensor, Marker, or Sensor then Marker.
Sensor
Selecting Sensor means the rising edge of the Home Sensor input function is used to establish the home reference position.
Figure 7:
Sensor Home Reference Position
Marker
Selecting Marker means the rising edge of the motor’s encoder marker channel is used to establish the reference position.
Figure 8:
Marker Home Reference Position
Sensor then Marker
Selecting Sensor then Marker means the reference position is established using the first marker rising edge after the drive
sees the rising edge of the Home Sensor input function.
Epsilon EP-P Drive Reference Manual
Revision A3
5
www.emersonct.com
Figure 9:
2.5.3
Sensor then Marker Home Reference Position Example 1
Accuracy and Repeatability
The accuracy is one trajectory update rate. For example - if the trajectory update rate is set to 800 s then the accuracy will be 800 s, if the
trajectory update rate is set to 1.6 ms then the accuracy will be 1.6 ms.
The amount of accuracy the application requires will determine the Home Reference type selected. Homing to an external sensor will only
establish a repeatable home position within 0.04 revolutions at 3000 RPMs (800 sec sensor capture interval).
NOTE
The data above assumes the use of a perfectly repeatable home sensor.
In Sensor then Marker applications, the marker must be at least 800 sec after the rising edge of the sensor input to be considered a valid
marker pulse, see Figure 10.
NOTE
At 1000 RPM, the motor will travel 0.0133 revolutions (or 4.8°) in 800 sec.
>800 µsec
Sensor
Marker
Direction of Travel
Figure 10:
Sensor then Marker Home Reference Position Example 2
The Home Sensor must be “On” for at least 800 sec to guarantee that it will be recognized.
Sensor Min.
On Time
Sensor
800 μsec
Figure 11:
2.5.4
Sensor then Marker Home Reference Position Example 3
Home Offset
The Home Offset is the distance from the home reference position to the final stopping point at the end of the homing sequence. Regardless of
6
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
the value you enter for the Offset or which Home Reference type you choose, there is always an offset inherent in the homing
process.
The user may either specify a desired offset or allow the drive to calculate an offset automatically. The drive calculates an
offset that guarantees that the motor will not have to backup to get to the offset position. This is very convenient for
unidirectional applications.
The Calculated offset is the distance travelled during deceleration ramp from the home velocity to a stop plus the distance
travelled at the home velocity for 800 usec. This extra distance is used to guarantee that the motor will not need to backup
after the deceleration ramp.
The Specified offset allows the user to choose an exact offset from the home reference. Once the home reference is detected,
the drive will do whatever is necessary to reach the offset position. This may be as simple as a deceleration to a stop, a
continuation at speed followed by a deceleration to a stop, or a deceleration followed by a move in the opposite direction.
To enter a Specified offset, select the Specified offset radio button. PowerTools Pro always displays the calculated offset value
as a reference.
Offset Examples
With a Calculated offset if the home reference is detected before the axis has reached its peak velocity, the axis will still
continue to the precise offset position, see Figure 12.
Figure 12:
Calculated Home Offset, Peak Velocity Not Reached
If the home reference is detected after the axis has reached its peak velocity, the axis will decelerate to the precise offset
position.
Calculated
Home Offset
Figure 13:
Calculated Home Offset, Peak Velocity Reached
Two examples below show operation when the specified offset is greater or lesser than the calculated offset. This causes the
axis to continue on at speed before decelerating and stopping at the offset position, or backing up after the home sensor.
Epsilon EP-P Drive Reference Manual
Revision A3
7
www.emersonct.com
Specified
Offset
Figure 14:
Specified Home Offset, Greater than Calculated Offset
Specified
Offset
Figure 15:
2.5.5
Specified Home Offset, Backup Required
End of Home Position
The End of Home Position (End Posn) defines the home position in relation to the machine’s coordinate system. At the completion of the
home, the value of the End of Home Position is put into the command position.
2.5.6
Home Limit Distance
This parameter places an upper limit on the incremental distance the motor will travel during the home.
If no reference is found, the system will decelerate and stop at the limit distance. The Home Limit Distance Hit function will be activated if the
home stops at the limit distance without finding the reference. Additionally, the Home.CommandComplete function will not turn “On” if the limit
distance is hit.
2.5.7
Home Examples
Linear Application
In this example, the system uses an external sensor and the motor’s encoder marker channel to establish a Home Reference Position. This is
the most accurate and most common way to home.
8
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Gear Reducer
External
Home Sensor
NT
Motor
Di
rec
tio
n
+
Figure 16:
Home to Sensor and Marker, Example
When the drive sees the Home Initiate, it accelerates the motor to the Home Velocity.
The motor continues at that velocity until it first senses the Home Sensor input. It continues at the same velocity until the
motor’s encoder marker channel is sensed. The rising edge of the motor’s encoder marker channel is used to establish the
reference position. Once the home reference is detected, the motor decelerates to a stop and moves to the offset position.
Home Sequence
1.
If on sensor then back off (if enabled)
2.
Search for sensor
3.
Search for marker
4.
Go to offset (2.0 Revs)
5.
Set feedback position equal to End of Home Position
Velocity
+ 100
+ 100
Back off
Sensor
Time
- 100
Sensor
Figure 17:
Marker
Home Velocity Profile
Epsilon EP-P Drive Reference Manual
Revision A3
9
www.emersonct.com
1
Start of Home
Back Off Sensor
2
Sensor
Marker
Home Move
4
Offset Move
5
Final Position = End of Home Position
2.0 Revs
Offset
Figure 18:
Home Move Sequence
Rotary Application
This example uses an external sensor and the motor’s encoder marker pulse to establish a home reference position.
External
Home Sensor
Re Gear
du
ce
r
NT Motor
Figure 19:
Home Sensor and Marker then Offset, Example
When the drive sees the rising edge of the Home Initiate function, it accelerates the motor to the Home Velocity. The motor continues at that
velocity until it first senses the Home Sensor input. The motor continues on at the home velocity until the marker is activated.
The rising edge of the motor’s encoder marker channel is used to establish the reference position.
After sensing the rising edge of the motor’s marker channel, the drive will continue moving and will decelerate to a stop at the specified offset
position.
Figure 20:
Home Velocity Profile
10
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
2.6
How Indexes Work
An index is a complete motion sequence that moves the motor a specific incremental distance or to an absolute position. This
motion sequence includes an acceleration ramp to a programmed velocity, a run at velocity, and a deceleration ramp to a stop.
Velocity
Run at Velocity
Acceleration
Deceleration
Time
Figure 21:
Index Motion Sequence
Figure 22:
Indexes View
Indexes use acceleration and deceleration ramps which may or may not reach the specified velocity depending on the total
distance and the ramp values. For example, a short move with long acceleration and deceleration ramps may not reach the
target velocity entered.
Indexes cannot be initiated when any other motion (jogging, homing, or program) is in progress. Indexes can be aborted with
the Stop destination found in the Ramps group on the Assignments View.
The Epsilon EP-P supports eight types of indexes: absolute, correction, incremental, posn track cont., posn track once,
registration, rotary plus and rotary minus.
2.6.1
Absolute vs. Incremental
The difference between absolute and incremental indexes is that absolute indexes move to a specific absolute position and
incremental indexes move the motor a specific distance. The following figures and explanations demonstrate this concept.
Epsilon EP-P Drive Reference Manual
Revision A3
11
www.emersonct.com
Absolute Indexes
Absolute indexes are used in applications where the motor must travel to a specific position, regardless of where the motor is when the index
is initiated.
The drive calculates the distance required to move to the specified position from the current position.
Absolute Index
Start Position = 1 Rev
Index Position = 5 Revs
Figure 23:
Absolute Index Example 1
In the example above, the current position is 1 rev. If this index is initiated, the motor will travel to a position of 5 revs no matter where it is
sitting before the move. From 3 revs, it will travel 2 revs to finish at 5 revs. If the absolute index to 5 revs is initiated a second time immediately
after the index, no motion will occur because the motor will already be at a position of 5 revs.
The direction of an Absolute Index is determined by the starting position and the absolute index position. If the starting position for the above
index is 9 revs, then the motor will rotate in the negative direction to end up at 5 revs. The figure below shows this.
Absolute Index
Start Position = 9 Revs
Index Position = 5 Revs
Figure 24:
Absolute Index Example 2
Absolute indexes with Rotary Rollover enabled will take the shortest path to the position entered in the index position parameter.
NOTE
Absolute indexes move to positions relative to where the machine was homed using the Home, or the DefineHome destination.
Incremental Indexes
An incremental index will move the motor a specified distance in the + or - direction regardless of the starting position. The direction of the
incremental index motion is determined by the sign (+ or -) of the Index Distance parameter.
Incremental Index
Start Position = 1 Rev
Index Distance = 2 Revs
Figure 25:
Incremental Index Example
In the example above, the motor starts at 1 rev, travels a distance of 2 revs and stops at 3 revs. If the same index is initiated a second time, the
drive would move the motor another 2 revs to a position of 5 revs. If initiated a third time, the motor would travel another 2 revs to a final
position of 7 revs. Figure 26 shows this operation.
12
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Incremental Index
Start Position = 1 Rev
Index Distance = 2 Revs
Figure 26:
Incremental Index Example 2
Correction Indexes
A Correction index is intended to continuously run on the second profile correcting any position drift. It will adjust the motor
position based on changes to it's index.#.dist parameter. The Correction indexes use incremental distance values. Updates to
the index distance while the correction index is executing will take effect immediately by recalculating the index on the fly.
Another words, if this index is in progress and the distance value is changed, the move profile instantaneously recalculates
based on the index's current position, speed and acceleration. Once the Correction index is initiated it will remain active until
stopped by the user with the Profile.#.MotionStop function.
Example: Correction index distance sources are user program calculations, fieldbus inputs or analog input values. The index
distance value can be updated via Fieldbus, by simply writing to the index distance parameter. If the analog input's Destination
Variable is set to the Index.#.Dist parameter, the index's distance value will be updated by the Analog Input. This can be set to
a automatic refresh using the Analog Input view
Posn Tracker Cont and Posn Tracker Once Indexes
Posn Tracker Cont and Posn Tracker Once are indexes which expect their position values to be dynamically changed while
executing. Position Tracker indexes use absolute position values. Posn Tracker Cont index once initiated, will remain active
until stopped by the user with the Profile.#.MotionStop function. The Posn Tracker Once index will accept position changes
until the target position is reached, at which point the index is complete.
The index 's position value can be updated via fieldbus, by simply writing to the index position parameter. Posn Tracker
Indexes are used to follow dynamic changes to the end point of the index prior to and during the index motion. If the analog
input's Destination is set to an Index.#.distance, the index's position value will be updated by the Analog to Position scaling
found in the Analog Input view.
Posn Tracker also accepts on the fly changes to index velocity, acceleration and deceleration. The index is recalculated on the
next trajectory update.
Registration Indexes
A Registration Index is used in applications where the motor must move until an object is detected and then move a specific
distance from the point of detection, such as finding a registration mark and moving a distance beyond.
The Registration Index consists of two parts. The first part accelerates the motor to the target velocity and continues at this
velocity until it receives a registration trigger (sensor or analog). Upon receipt of a registration trigger, the registration offset will
be executed at the target velocity. The Sensor Limit Distance Hit source can be used to turn on an output, if a sensor input or
analog limit is not received within the Limit Distance. A registration window can also be used to determine the validity of a
registration trigger. If a registration trigger is received outside of the registration window, it will be ignored.
Rotary Plus and Rotary Minus Indexes
Rotary Plus and Rotary Minus Indexes provide forced directional control of moves to absolute positions. The position entered
for a Rotary Plus or Minus type index must be within the rotary range (i.e. 0  Position < Rotary Rollover Point). All other
parameters function the same as they do with absolute indexes. An Absolute Index is a direct move to a specific position,
regardless of the starting point. A Rotary Plus Index moves to the specified position, but is forced in a positive direction.
Similarly, a Rotary Minus index moves to the specific position, but is forced in a negative direction.
Rotary Plus and Minus Indexes are usually used in rotary applications, therefore the rotary rollover feature on the Setup Position view in the PowerTools Pro software must be enabled to use them.
1.
In the following examples the term “D” = (absolute position specified) - (current position). If “D” is negative,
motion in the negative direction is implied.
2.
In the following examples the Rotary Rollover parameter on the Setup - Position view is set to 360.00°. This
means that with each revolution of the motor (or rotary table), feedback will count up to 359.99°, then roll over
to Ø°.
Indexes with Rotary Rollover Enabled
Incremental move distances can be outside of the rotary rollover range. See the "Setting Up Parameters" chapter for an
explanation of Rotary Rollover.
Example 1: If the starting position is at Ø° and 720° is the specified distance, an Incremental index would move 2 revolutions
in the positive direction. At the completion of this index the motor position would be Ø°.
Absolute indexes will take the shortest path to the specified position. Absolute index positions must be within the rotary
Epsilon EP-P Drive Reference Manual
Revision A3
13
www.emersonct.com
rollover range.
Example 2: If the starting position is at 90° and 80° is the specified position, an Absolute index would travel 10° in the negative direction. At
the completion of this index the motor position would be 80°.
Example 3: If the starting position is 45° and 315° is the specified position, an Absolute index would travel 90° in the negative direction
because that is the shortest path between 45° and 315°.
Rotary Plus indexes will move to the specified position and are forced in a positive (or plus) direction. Rotary Plus index distances must be
within the rotary rollover range.
Example 4: As in example 2 above, the starting position is at 90° and 80° is the specified position. A Rotary Plus index would travel 350° in
the positive direction. At the completion of this index the motor position would be 80°.
Example 5: If the starting position is 10° and the specified position is 350°, a Rotary Plus index will travel 340° in the positive direction.
Rotary Minus indexes move to the specified position, but are forced to travel in the negative (or minus) direction. Rotary Minus index positions
must be within the rotary rollover range.
Example 6: As in examples 2 and 4 above, the starting position is at 90° and 80° is the specified position. A Rotary Minus index would travel
10° in the negative direction. At the completion of this index the motor position would be 80°.
Example 7: If the starting position is 15° and the specified position is 270°, a Rotary Minus index would travel 105° in the negative direction.
2.7
2.7.1
How Communications Work
Configuring Communication
Before attempting to upload or download a configuration file using PowerTool Pro, the software must be configured to the correct
communication settings for the intended communication connection. The Epsilon EP-P drive supports both RS-485 serial communication
connections (J2) and Ethernet communication (J4) connection, on the front of the drive.
When downloading or uploading a selected configuration file that is open in PowerTools the communication scanner will only scan the
configuration file’s Modbus ID and Ethernet address (unless Ethernet change address is clear). Once a connection is established, that
connection (Comm port used, port number, modbus ID and Ethernet address) is saved, a second download, upload or reconnect will bypass
the scanner and use this previously defined communication path. To change the communication path use the Change Path toolbar button.
The communication connection may be selected in the Upload Drive Configuration, Download to Device IDx or the Change Path dialog boxes.
From the Device menu, choose Upload Drive, Download or Path Change to open the dialog box or the toolbar buttons can also be used,
see below.
2.7.2
Upload Drive
Uploading is the process of reading information back from the drive to the PowerTools Pro configuration file views.
To upload information from a drive, click on the Upload All button, on the PowerTools Pro toolbar or from the Device menu,
choose Upload All or Upload Drive. The Upload Drive Configuration dialog box will open, all communication connections are
scanned and the results appear. In Figure 27, it shows that one drive on COM 1 was found, an Epsilon EP204-P drive. The Upload
Drive Configuration dialog box contains the following information for every drive found:
•
Ip Address/COM
•
Modbus Address ID
•
Drive Type
•
Module Type
•
Communication Options
•
Base/Drive FW Revision
•
Module FW Revision
•
Module Serial Number
•
Drive Serial Number
14
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
.
Figure 27:
Upload Drive Configuration Dialog Box
Select the drive to upload and click Upload.
2.7.3
Downloading
Downloading is the process of sending the configuration created with PowerTools Pro from the PC to the drive. Changes
made in PowerTools Pro will not take effect until the information has been downloaded or the Update to RAM button has been
clicked.
To download information to a drive, click the Download button on the PowerTools Pro toolbar or from the Device
menu, choose Download. The Download to Device IDx (x equals the modbus address) dialog box will open, all
communication connections are scanned and the results appear. In Figure 28, one drive on COM port 1 was
found, it’s a Epsilon EP204-P drive. The Download Drive Configuration dialog box contains the following
information for every drive found:
•
Ip Address/COM
•
Modbus Address ID
•
Drive Type
•
Module Type
•
Communication Options
•
Base/Drive FW Revision
•
Module FW Revision
•
Module Serial Number
•
Drive Serial Number
Epsilon EP-P Drive Reference Manual
Revision A3
15
www.emersonct.com
Figure 28:
Download to Device ID 1 Dialog box
Select the drive to download to and click OK.
2.7.4
Change Path Connection
This function allows the user to change the drive and Ip address/Com port used for download and upload. It is used when the user has already
selected one Ip Address/Com port and wishes to change to another.
The dialog box provides the user with communication information available on the Modbus and Ethernet network. This information contains:
•
Ip Address/COM
•
Modbus Address ID
•
Drive Type
•
Module Type
•
Communication Options
•
Base/Drive FW Revision
•
Module FW Revision
•
Module Serial Number
•
Drive Serial Number
Figure 29:
Change Path Dialog Box
Select the drive in the list and then click OK. The communication connection path will then be displayed in the status bar at the bottom of
PowerTools Pro window.
16
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
2.7.5
NVM Options for Uploading and Downloading
Uploading
When uploading from a drive, the values that were last downloaded are uploaded and put into a PowerTools Pro configuration
file. At the completion of the upload, the user will be asked if they wish to upload the NVM values. This dialog box is shown
below.
By selecting Yes, the values of all parameters stored in NVM will be uploaded and entered into the PowerTools Pro file values.
If No is selected, the values entered into the PowerTools Pro file will remain the same as those that were last downloaded to
the drive.
Downloading
When downloading to the drive the user will be required to select how to handle the NVM parameters upon downloading. The
dialog box asking the user to select one of three options for the download is shown below.
A description of each of the options is as follows:
Overwrite – This option will overwrite all the parameters stored in NVM with the current values in the user configuration
(PowerTools Pro file). The values that are in NVM prior to the download will be lost.
Update – This option will upload the current NVM parameter values from the drive and enter them into the user configuration
(PowerTools Pro file). Once the NVM values have been stored in the file, the file is fully downloaded.
Keep – This option will download the entire user configuration, but then NVM parameters will be restored to the value prior to
download. This is similar to the Update option, but the Keep option does not upload the NVM values into the user
configuration (PowerTools Pro file).
The following table shows an example of how these options work:
Before Download
After Download
Overwrite
Option
2.7.6
Update
Option
Keep
Option
PT Pro file value for Index.0.Vel
150
150
500
150
NVM value for Index.0.Vel
500
150
500
500
Updating to RAM
The Update to RAM button can be used to send changes to the drive without performing a complete download.
The Update to RAM button is found in the PowerTools Pro toolbar. This operation will send only those changes
that have been made since the last Update to RAM or a Device>Download to the drive was done. The changes
will take effect immediately upon clicking on the button.
The parameters will be sent to the drive without stopping motion or disabling the drives. Because of this, it is
important to use caution when changing motion parameters while the motor is in motion.
CAUTION
The Update to RAM button saves the parameters only to RAM and not to Non-Volatile Memory (NVM). Therefore, if the
system power is removed, any changes made using the Update to RAM button will be lost. In order to save changes to NVM,
a full-download must be performed.
The flowchart below describes a typical process using the Update to RAM to make changes, and then downloading when
complete to save changes to NVM.
Epsilon EP-P Drive Reference Manual
Revision A3
17
www.emersonct.com
Figure 30:
Update to RAM Flow Chart
The Update to RAM button operates according to the following rules:
•
If no parameters have been modified by the user, the Update to RAM button will be disabled
•
If the user modifies a parameter that does not require a full download, the Update to RAM button will be enabled
• If while the button is enabled, the user modifies a parameter that requires a full download, the Update to RAM button will become
disabled
• When the user clicks on the Update to RAM button, all the modified parameters are transmitted to the drive. Once transmitted,
the button will become disabled again until another parameter is changed
• If the user performs a full download while the button is enabled, when the download is complete, the Update to RAM button will
be disabled
•
2.7.7
If the user modifies parameters, and disconnects, the Update to RAM button will be disabled, and the changes will not be sent.
Options/Preferences/Ptools Operation
Communications Tab
This tab allows the user to set-up the serial communication baud rate. The drive baud rate and PowerTools Pro baud rate must match, default
drive baud rate = 19200. The Enable Scan group allows the user to select which communications connections are scanned when doing any
communication operations. Windows allows up to 256 COM ports. PowerTools Pro scans the Windows registry to find all the defined COM
ports. The scanner sends commands down each of the COM ports to find the drives. Default = All ports are scanned. The user also has the
control of which Modbus node address are scanned when doing any communication operations The range is 1 to 247 but since it’s not
practical from a time stand point to scan all nodes in the range the default is 1 to 4 node addresses. This scan range can be changed by the
user.
Figure 31:
Preferences-Communications Tab
PopUps Tab
The options in this dialog box controls the dialog boxes that the user encounters when uploading and downloading the configuration file.
18
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 32:
Preferences-PopUps Tab
Download Section:
Ignore saving file on Ptools/Drive revision conversion.
On a download PowerTools Pro checks the firmware revision of the drive that it is about to be downloaded to and is required to
make changes to files that are to be downloaded to older firmware revisions. This check box allows the user to avoid saving
the newer file before converting it to a previous revision.
Overwrite – Reset the NVM configuration.
When this option is selected the “Overwrite” function will default on every download to the drive. This function will overwrite the
entire configuration including user defined NVM parameters as set in the NVM setup area of PowerTools Pro.
NOTE
It is required to Overwrite the Non-Volatile Memory on the first download to the drive since no Non-Volatile Memory
parameters have been loaded into the drive on initial startup.
Update – Upload the values into the current Update PowerTools configuration.
When this option is selected the “Update” function will Update the NVM on every download to the drive. Upon download the
Update function uploads the configured NVM from the drive and places the data into the PowerTools Pro configuration file.
The software then downloads this newly updated file to the drive.
Keep – Remember the values, and restore them after the download.
This option was created to allow users to save the values that have been changed via HMI, PLC or internally in a program so
long as they have been added to the NVM list. When this option is selected PowerTools Pro will poll the drive on download for
all of the values that have been added to the NVM list. PowerTools Pro then stores these values into a temporary memory
location and after the program download is complete PowerTools Pro reinstates these values to the parameters before the
drive can be enabled.
Ask on each download.
This option was created for users who want control of whether they will overwrite or keep the NVM on download. When this
option is selected, PowerTools Pro will display a pop-up window that gives the user the option to Overwrite, Update, or Keep
as described above.
Upload Non-Volatile Memory (NVM) Section:
Always upload NVM
When this option is selected, PowerTools Pro will default on an upload to uploading all of the parameters that have been
mapped to the NVM and updating the display of these parameters in PowerTools Pro.
Always bypass NVM upload
When this option is selected, PowerTools Pro will not upload the NVM and the values that were originally downloaded to the
drive will be displayed in the PowerTools Pro configuration.
Ask on each upload
When this option is selected, PowerTools Pro will default to asking the user via a dialog box whether to upload the NVM or to
bypass the NVM upload.
Motor DDF Tab
The Motor DDF tab controls which .ddf files PowerTools Pro will use when working in the configuration file. The standard ddf
files contain a list of motors that can be purchased from Control Techniques and their parameters. This tab gives the advanced
user the capability to create their own standard motor ddf file. Never save a newly created user standard ddf file as
StdMotor.ddf because it will be overwritten with the next release of PowerTools Pro. The user’s ddf file name would be enter
Epsilon EP-P Drive Reference Manual
Revision A3
19
www.emersonct.com
into the Standard Motor DDF Name text box for the correct drive type, see below.
Figure 33:
Preferences-Motor DDF Tab
En, MDS, Epsilon Motor DDF Section:
Use the standard Motor DDF file
Select this check box to use the standard motor ddf file.
Standard Motor DDF Name
The name of the standard motor ddf file is entered in the text box, the information in this file will be used to setup the configuration file, the
default is stdmotor.ddf.
User Motor DDF Name
When a custom motor is created this is the name of the motor ddf file where the information is stored, default is motor.ddf.
Ep Motor DDF Section
Standard Motor DDF Name
The name of the standard motor ddf file for Epsilon EP drives.
Unidrive SP Motor DDF Section
Use the SP Standard Motor DDF file
Select this check box to use the standard motor ddf file with the Unidrive SP.
SP Standard Motor DDF Name
The name of the standard motor ddf file is entered in the text box, default is spstdmotor.ddf.
SP User Motor DDF Name
When a custom motor is created this is the name of the motor ddf file where the information is stored, default is spmotor.ddf.
2.7.8
Secure Downloading
The Secure Download feature allows the user to download a configuration that prevents anyone from uploading the file, or going online with
the system. This is used to protect a file from being accessed by unauthorized personnel. If a secure file is downloaded to the system, all
diagnostics capabilities in the software are lost. The only way to go online with the system again is to download the original (non-secure) file
over the secure version, or to download a completely new file.
Before performing a secure download, the file must first be saved in the secure file format. To do this, open the file you wish to save in the
secure format using PowerTools Pro. Then on the File menu, click SaveAs. The following SaveAs dialog box should appear when saving an
EP-P configuration file.
20
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
In this dialog box, select the “Save also as secure download format” check box located at the bottom of the dialog box, then
click Save. Doing this will save the file in BOTH the standard file format (.EPP), as well as in the secure file format (EPPs). The
“s” at the end of the file extension stands for “secure”. The secure file will be saved to the same directory as the standard file.
To perform the Secure Download, close all open files in PowerTools Pro. Then on the Device menu, click Secure Download,
as shown below.
A dialog box will then open asking the user to select the secure file that they wish to download. Select the secure file that was
just saved, then click Open. This will download the secure file to the target drive.
A secure file (EPPs) cannot be opened or modified. The file extension cannot be changed to allow the user to open it. The
secure file is only valid for use by the secure download function. If a user attempts to upload a secure file, a message will
appear indicating that the file residing in the drive has been protected by the user. An example of this is shown below.
2.8
Brake Operation
The brake is operational when the Brake.Disengaged parameter is wired to an output. It is expected that this output is then
physically wired to the Motor's brake. The standard operation for brake is to engage the brake when the drive is disabled. The
LED shows the little "b" when the brake is engaged. The Brake can further be controlled by the Brake controls Brake.Activate
and Brake.Release. The Brake.Release overrides all conditions (drive disable and Brake.Activate) to insure the brake is
disengaged. The Brake Activate parameter allows the user to engage the brake while the drive is enabled. However, you need
to be careful because Brake.Activate does not stop motion commands
The table below shows the relationship between the Brake sources and destinations.
Epsilon EP-P Drive Reference Manual
Revision A3
21
www.emersonct.com
NOTE
No motion should be commanded while the brake is engaged.
Brake.Activate Brake.Release Drive Enable
Brake.Disengaged
Brake Status
Drive Diagnostic Display
b
Off
Off
Off
Off
Enabled
Off
Off
On
On
Disabled
On
Off
Off
Off
Enabled
On
Off
On
Off
Enabled
x
On
x
On
Disabled
b
Brake Release
The Brake.Release destination function will release the brake under all conditions. When this function is active, the Brake output will be on
(that is, release brake). This function overrides all other brake control, thus allowing the brake to be released while a fault is active or the power
stage is disabled.
Brake Activate
The Brake.Activate destination function, when active, will engage the brake unless overridden by the Brake Release function. This function lets
you externally engage the brake while allowing the drive to also control the brake during fault and disabled conditions.
Brake Disengaged
The Brake.Disengaged source function is used to control the motor holding brake. If the Brake function is off, the brake is mechanically
engaged. When the brake is engaged, the diagnostic display on the front of the drive will display a “b”.
The drive outputs are limited to 150 mA capacity, therefore, a suppressed relay is required to control motor coil. Control Techniques offers a
relay, model # BRM-1.
2.9
How Data Capture Works
Data Capture is a mechanism to capture data and display that data graphically. The capture mechanism is part of the drive and captures drive
data as fast as 100 usec. Data is captured in a circular 8 K byte buffer. The format is fixed at 4 channels of 32 bit words for a total of 512 time
samples. The circular buffer is continuously loaded until the trigger condition (or command abort) stops loading data. The capture mechanism
follows three buffer states - Filling Buffer, Waiting for trigger, and Triggered.
At the start of the Run command, the buffer starts to fill (filling the whole buffer). The buffer must be completely filled before the trigger is
armed. Once the buffer is filled, the buffer state will display - Waiting for Trigger. When the trigger is detected, the data capture is stopped
(triggered). The sampling rate is based on the trajectory update rate. The sample rate can be adjusted in multiples of the trajectory update rate.
PowerTools displays this in the form of seconds. At the update sampling, a new set of data is overwritten into the circular buffer and the trigger
is checked.
The Data Capture update rate for the Epsilon EP-P drive is 100 usec. The drive captures data at the user selectable trajectory update rate of
800, 1200 or 1600 usec for Drive Inputs, Drive Outputs and Custom Variables. This means if the Data Capture rate is faster then the Epsilon
EP-P drive trajectory update rate the user will be sampling data faster than it is changing. All other parameters in the Select list box are
captured at 100 usec except Bus Voltage and Following Error which are 400 usec.
The trigger detection checks the data level. It does not specially look for an edge. Once the buffer is filled the trigger is armed and the check for
trigger level is started. Since the drive is looking back in the buffer at data captured during the fill, the trigger condition may already exist. If that
is so, the drive immediately transitions to the trigger state. If not, the drive continues the data capture cycle of sample and trigger check until
the trigger is detected at the edge of the data transition. When the Trigger Falling Edge check box is selected the trigger is detected when the
data transitions below the trigger level.
When sampling digital inputs and outputs, the data captured is binary bit mapped. The state of all the digital signals in the group selected are
encoded into one 32 bit word. When this is graphed it is displayed as an analog signal. To trigger on this bit map data, the trigger mechanism
is changed to a mask. The user can select one of the bits to trigger on.
The captured data is uploaded when the UploadPlot button is pressed. Once uploaded, PowerTools plots the data in graph window. Data is
also saved in a data file named, PtProGraphData.csv. This data file can be exported to a spread sheet for data manipulation and graphing.
2.9.1
Navigating the Graph Window
The Graph window display can be altered, double-click anywhere in the Graph Window except on the graph area itself. The Customization
dialog box opens and contains tabbed graph options. Many of the graphs attributes, such as colors, line format, etc. can be changed in this
box. The graph can also be exported to a file.
Holding the shift key down while moving the mouse allows the user to zoom in on the graph area. Double-click on the graph area and the
Graph Coordinate window opens and gives the x/y coordinate of where the mouse point was when double-clicked.
The Graph window overlaps the data into a Y axis if the next channel has the same units. If the units change for the next channel, a new graph
on the Y axis is added to the plot. If None is selected for a channel the drive data capture samples zero for that channel an PowerTools ignores
plotting that channel. The Reserved channel selection is for internal use only and also captures zero. The title of the graph matches the
application’s name defined on the Setup view.
Graph settings are downloaded to the drive when the Run button is pressed. Only changed values are sent. The graph settings are the same
as any application variable. When a variable is changed in a PowerTools view the Update to RAM button is available, indicating the
application and drive are out of sync, (Update to RAM remains unavailable if the user changes a variable that requires a reboot. The user then
requires a full download). When the Run button is pressed, it does a limited Update to RAM by downloading the changed graph settings to
RAM.
22
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3
Setting Up Parameters
3.1
3.1.1
Status View
Status Online Tab
The Status Online tab (see Figure 34) is visible when online and consists of the Motor Position group, Motor Velocity group,
Control Loop group, Master Feedback group, and the Torque group.
Figure 34:
3.1.2
Status View - Status Online Tab
Motor Position Group
Position Command
Position command (PosnCommand) is the commanded position generated by the drive based on the application. This
parameter does not take following error into account. See also Position Feedback and Following Error. Units are in user units.
Position Feedback
Feedback position (PosnFeedback) is the actual motor position in user units. PosnCommand minus the PosnFeedback is the
FollowingError.
Following Error
Following Error (FollowingError) is the difference between the PosnCommand and the PosnFeedback. It is positive when the
PosnCommand is greater than the PosnFeedback.
Encoder Position
Motor encoder position in encoder counts (PosnFeedbackInCounts). This position reflects the feedback position of the motor
and is not scaled into user units. This is a signed 32 bit value.
3.1.3
Motor Velocity Group
Velocity Command
The Velocity Command (VelCommand) is the velocity that the drive is commanding the motor to run at. This command is
generated by the drive velocity control loop and position loop. It is displayed in user units.
Velocity Feedback
The Velocity Feedback (VelFeedback) is the feedback (or actual) velocity. It is calculated using the change in position of the
motor encoder. It will always return the actual motor velocity - even in synchronized applications in which the master axis is
halted during a move.
3.1.4
Control Loop Group
Changing the Trajectory Update Rate can have a major effect on the performance of the servo system. A longer trajectory
update rate means that more time is available to process user programs. A shorter update rate means that the control loop is
updated more often and provides the most accurate performance. Without proper diagnostics, it can be impossible to tell how
much time is being consumed by the control loop update, and how much time is available to run user programs.
The Control Loop group of parameters on the Status Online tab shows the user how much time is available to run programs.
There are two parameters available to help with this. They are as follows:
Epsilon EP-P Drive Reference Manual
Revision A3
23
www.emersonct.com
Control Loop Limit
This parameter shows the lowest measured time difference (in microseconds) between the Trajectory Update Rate and the time taken to
process the control loop since the last reset. Certain features in the Epsilon EP-P require more time to process (i.e. Real Time program
execution, PLS, Capture, Compound Indexes), and therefore will cause lower limits. The software records the lowest measured value and
displays it as the limit. To reset the limit to the average and continue tracking the lowest value, the user can click on the Limit button. If the Limit
reaches 0, a fault will be generated. If a Limit of less then 75 - 100 usec is seen, it is recommended to switch the trajectory update rate to the
next higher value.
The cyclic program is run as a high priority user program and is not part of the Control loop time.
Average Margin
This parameter shows a running average of the difference (in microseconds) between the Trajectory Update Rate and the time taken to
process the control loop since the Status Online tab was brought up. The higher the value, the more time available to run user programs. For
Averages less than 150 usec, it is recommended to switch the trajectory update rate to the next higher value.
3.1.5
Master Feedback Group
Master Position
Used for synchronized motion, this displays the position of the master encoder in the user units name, defined on the Master Units View.
Encoder Position
This displays the position of the master encoder in counts.
Master Velocity
This displays the velocity of the master encoder in master user units/second.
3.1.6
Torque Group
Torque Command
This displays the torque command value before it is limited. The torque command may be limited by the motors rating, the drives rating, the
Torque Limit (if the Torque Limit Enable destination is active) or Current Foldback. Units for this parameter are defined in the Torque Group on
the User Units View.
Limited Torque
This is the actual torque commanded to the motor. This value is the result after the TorqueCommand is limited by the current foldback or the
TorqueLimit value (if enabled).
Foldback RMS
This parameter accurately models the thermal heating and cooling of the drive and motor. When it reaches 100 percent, current foldback will
be activated. See the Diagnostics section for an explanation of foldback.
Shunt Power RMS
This parameter models the thermal heating and cooling of the drive internal shunt. This parameter indicates the percent of shunt capacity
utilization. When this value reaches 100 percent, the drive will generate an RMS Shunt Power Fault.
3.1.7
Information Tab (Online Only)
PowerTools Pro is designed to work with all releases of drive firmware. PowerTools Pro internally uses interface revisions to negotiate and
define the application to match the connected drive. The first line shows the file name and user application for reference.
3.1.8
Drive Information Group
Firmware Revision
Displays the revision of the drive firmware.
Serial Number
Displays the serial number of the drive.
The following interface revisions are PowerTools and the drive firmware internal revision numbers to identify parameter sets, data structures,
data ranges and access attributes to match the drives’s data structures to PowerTools. When parameters are added to support new features or
parameters are altered, a new interface revision is assigned.
Base Interface Revision
This parameter displays the interface revision of the data parameter structure in the Epp's base drive. This revision has a correlation with the
features supported by the Epp drive.
Registry Interface Revision
This parameter displays the interface revision of the "Registry" data parameter structure in the Epp drive. This revision has a correlation with
the features supported by the Epp. On download, both the Registry and Base Interface revisions are used to convert the Power Tools data set
to match the drive's data structure. In this way Power Tools can support different releases of the EPP Flashes. For the most part the user does
not need to be concerned over interface revisions.
FPGA Revision
The Field Programmable Date Array (FPGA) is an electronic component in the drives. The FPGA revision is only displayed because when the
Epsilon EP drive was first released the FPGA was not field upgradable. When the revision is <100 the drive is not field upgradable. When the
revision is >100 the FPGA can be upgraded by flash upgrading and then Virtual Master Sync Output will work.
24
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.2
Graph View
Figure 35:
3.2.1
Graph View
Data Capture Group
Graph State
There are three graph state conditions in the following order: Filling Buffer, Filled. Waiting for Trigger, and Filled and Triggered.
Run
The Run button commands the drive to begin a high speed data capture of the parameters as selected in each of the four data
channels. After the Run button is activated the buffer will fill up to the trigger offset while the words “Filling Buffer” appear
indicating this Graph State. Once the trigger offset level is reached the words “Waiting Trigger” will appear next to the Graph
State indicating that graphical monitor is now ready to be triggered based on the trigger level selected.
Upload and Plot
The Upload and Plot button will upload captured data from the drive and display this data in the Graph window. The user
should wait for the Graph State to read “Filled and Triggered” before the data is uploaded.
Stop
The Stop button stops the data capture with the data captured at that point. You can upload and plot that data. If the buffer is
only partially filled you will get a combination of good and bad data. Stop works well as a manual trigger, in place of the
configured trigger.
Automatically Re-trigger and Plot Check Box
Select the check box and the Automatically Re-trigger and Plot tells PowerTools Pro to monitor the graph state for the
triggered condition. When this condition occurs, it automatically initiates the UploadPlot command, waits for a brief time then
initiates the Run button to repeat the cycle. Initially the user must press the Run button to start the auto cycle.
This mechanism is only active when the graph view is displayed, If the user enters a different PowerTools view the auto update
will stop and it will restart when returning to the Graph view.
Print
The Print button is used to print the graph in the Graph window.
3.2.2
Timing Group
The sliders can be moved in several different ways.
1. With the mouse pointer over the slider, left click and hold while dragging the slider back or forth to the desire setting.
2. With the mouse pointer over the slider, left click on the slider and then the arrow keys on the PC keyboard can be used to
move the slider in fine increments. The Page Up and Page Down keys move the slider in course increments. The Home key
will move the slider all the way to the left and the End key will all the way to the right.
Sample Rate
The Sample Rate slider gives the user control of time spacing for the captured date. To give the user a better idea of what this
number means, the total number of samples and total capture time is displayed on the bottom of the “Timing” group box.
Trigger Offset
The Trigger Offset slider corresponds to the number of samples that will be included on the graph display and data capture
prior to the actual trigger. If the Trigger offset slider is completely to the left (min samples), the data capture and graphing will
Epsilon EP-P Drive Reference Manual
Revision A3
25
www.emersonct.com
start at the trigger location. If the slider is completely to the right (max samples) the graph will capture data until the trigger point.
Buffer Upload Size
The buffer upload size slider truncates the drive captured data. If the slider is completely to the right (max) the complete buffer will be
uploaded. If the slider is completely to the left, only 1% of the buffer will be uploaded. This parameter does not effect the data capture size, it
only defines how much of the buffer will be uploaded.
3.2.3
Data Group
Data Channel 1 - 4 Select List Boxes
The Channel 1 through Channel 4 list boxes give the user options for parameter display. If parameters with the same units are mapped on
adjacent channels then the graphical display will show these two parameters overlapped on the same x/y axis. If it is desirable to have two
adjacent Channels with the same units mapped to separate axis on the graph then the selection (none) should be used on the channel in
between these two parameters.
Trigger Radio Buttons
Selecting the radio button will cause the graphical capture to trigger the capture off the selected Channel. The “Trigger Level” text box on the
bottom of the display will change units to the selected channel's parameter units. This trigger level may be changed at any time but the change
must be sent to the drive via the Update to RAM or Download button. If a manual trigger is desired, set the channel to None and select the
corresponding trigger radio button. If no trigger is selected the capture will begin when the Run button is clicked and end at the end of the
Sample Rate.
Custom Variable
A Custom Variable text box is only available once the user has selected Custom Variable from the Select list box. This field is used to define
what parameter will be plotted on that channel. The custom variable parameter can be entered two ways: by just typing any custom variable
using the program format for the variable, or click the Popup Variables button and the variable window will open. Then select the variable and
drag it over to the channel custom variable text box.
Trigger Mask List Box
This list box is only available when Drive Inputs or Drive Outputs are selected in the channel select list box and the Trigger radio button is
selected for that channel. The Trigger Mask list box will only list the inputs or outputs for the selected channel parameter.
Trigger Falling Edge Check Box
When the Trigger Falling Edge check box is selected, the trigger is detected when the data transitions below the trigger level. When the Trigger
Falling Edge check box is clear, the trigger is detected when the data transitions above the trigger level.
Trigger Level
This is the level at which the graph is triggered. The “Trigger Level” text box will change units to the selected channel's parameter unit. This
trigger level may be changed at any time but the change must be sent to the drive via the Update to RAM or Download button.
26
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.3
Setup View
The Setup View contains all of the primary system setup parameters. These parameters must be setup prior to using your
system.
By selecting Setup in the Hierarchy Tree, the Setup view will appear on the right side of the view (see Figure 36). The Setup
view is divided into six groups, with an explanation of each function. The groups are Identification, Configuration, Drive
Encoder Output, Positive Direction, Update Rate and Switching Frequency.
Figure 36:
3.3.1
Setup View-Epsilon EP-P drive
Identification Group
The identification group consists of the Name, Target Drive Address, Change IP Address Check box, IP Address, Subnet and
Gateway.
Name
This is a 12-character alpha/numeric user-configured name for this axis. Enter this name for the drive currently being set up.
Assigning a unique name for each drive in the system allows the user to quickly identify a drive when downloading, editing,
and troubleshooting. All keyboard characters are valid. This will default to Axis 1.
Target Drive Address
This parameter (Modbus.ModbusId) is the Modbus address of the target drive to which the user will download the
configuration. The default target drive address is 1.
Change IP Address Check box
Change IP Address check box is used to determine if the user wants to use the scanner to determine the application's
Ethernet address. If Change IP Address check box is selected then the scanner selected address becomes the new
application address (saved with application). This applies for Download, Upload into an existing application and Change Path.
When Change IP Address check box is clear the Ethernet Address scanner range is the last scan range entered using the
scanner's "Stop Scan". If Change IP Address is selected, then the scanner's "Ip Address Scan Range" range will be loaded to
select only the applications IP address.
The Change IP Address check box must be selected to change the IP Address, Subnet and Gateway.
IP Address
This parameter (Ethernet.EthernetConfiguration.IPAddress) is a 32-bit identification number for each node on an Internet
Protocol network. These addresses are represented as four 8-bit numbers (0 to 255), with periods between them. Each node
on the Ethernet network must have a unique IP address.
Subnet
This 32-bit parameter (Ethernet.EthernetConfiguration.Subnet) indicates the subnet mask used for this node. The subnet
mask is used to group drives that are connected on the same physical connection. For a detailed description of Subnet mask
refer to the Industrial Ethernet Overview section in the Epsilon EP Connectivity Reference Manual (P/N 400518-04).
Gateway
This 32-bit parameter (Ethernet.EthernetConfiguration.Gateway) indicates the default Gateway address for the drive. When
attempting to communicate with a drive on a different Subnet, the message must go through this gateway to reach it’s
destination. For a detailed description of the Gateway address refer to the Industrial Ethernet Overview section in the Epsilon
Epsilon EP-P Drive Reference Manual
Revision A3
27
www.emersonct.com
EP Connectivity Reference Manual (P/N 400518-04).
3.3.2
Configuration Group
The configuration group consists of list boxes for Drive Type and Motor Type.
Drive Type List Box
Select the drive model for the system you are currently setting up.
Motor Type List Box
Select the motor model for the application from the list of motors.
Motor types are arranged as follows:
•
FM motors
•
NT motors
•
XV motors
•
MG motors
•
Unimotor Classic motors
Motor voltage is determined by the first letter (E=230, U=460), brake motors have a 1 as the last digit (095E2A401).
Standard 230 V motors, brake motors have BR after the model #.
Standard 230 V motors, brake motors have BR after the model #.
Standard 230 V motors, brake motors have BR after the model #.
Model numbers end with a UL in the part number, for example: 115EZB200-UL.
Motor voltage is determined by the first letter (E=230, U=460).
For brake motors, use the standard motor model.
NOTE
Selecting the wrong motor type can cause poor performance and may even damage the motor and/or drive.
3.3.3
Drive Encoder Output Group
The drive encoder output group consists of the encoder scaling check box and encoder scaling.
Encoder Scaling Check Box
Select this check box to enable the Encoder Scaling parameter of the Drive Encoder Output.
Encoder Scaling
This parameter defines the encoder resolution (lines per revolution) of the drive's encoder output. This feature allows you to change the drive
encoder output resolution in increments of 1 line per revolution up to the density of the encoder in the motor. If the Encoder Output Scaling
parameter is set to a value higher than the motor encoder density, the drive encoder output density will equal that of the motor encoder.
3.3.4
Positive Direction Group
The Positive Direction group consists of a CW (clockwise) Motor Rotation radio button or a CCW (counter-clockwise) Motor Rotation radio
button.
The motion will move in either CW direction or CCW direction. Perspective of rotation is defined as you face the motor shaft from the front of
the motor.
CW Motor Rotation Radio Button
Select this radio button for applications in which CW motor rotation is considered to be motion in the positive direction (increasing absolute
position).
CCW Motor Rotation Radio Button
Select this radio button for applications in which CCW motor rotation is considered to be motion in the positive direction (increasing absolute
position).
3.3.5
Update Rate Group
Trajectory
This parameter configures the interrupt interval for the drive processor. This defines how often the motion program is interrupted and the
Control Loop is processed. In the Control Loop, the feedback information is processed and a new position command is generated. Also, in the
Control Loop, the I/O is scanned. After Control Loop is complete, all messages are handled. Messages are Modbus data, DeviceNet data,
28
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Display information, and are only processed if a message is waiting. If no device is querying data from the Epsilon EP-P drive
or sending data to the Epsilon EP-P drive, then messages do not take up any time. Once messages have been processed, the
remainder of the interrupt is dedicated to running the motion programs of user programs.
Available selections for Trajectory Update are 800, 1200, and 1600 microseconds. The longer the update, the more time is
dedicated to the user programs, and the less time dedicated to servo performance. The shorter the update, the more precise
the servo performance, but less time is available to process user programs. Diagnostics are available on the Status Online tab
when online with the drive to help select the ideal setting. (See description of Control Loop Group of online parameters on
page 23 for further information)
3.3.6
Switching Frequency Group
This parameter defines the switching frequency of the drive. For the Epsilon EP drives, the switching frequency is 10 kHz and
cannot be changed.
3.4
Motor View
The Motor view under Setup view is used for many different functions:
1.
To see/verify the motor data for a standard motor that had been selected
2.
To create a new motor entry in the .ddf file
3.
To Run the Auto-Tune feature
4. To store Auto-Tune results into an existing configuration
The primary function of this view is to define the parameters for the given motor that is to be connected to the drive.
Following is a description of all the different functions on the Motor view.
Figure 37:
3.4.1
Motor View
Motor Type List Box
Use this list box to select the motor type. PowerTools Pro software will display all the standard motor models and any user
defined motors.
Selecting the wrong motor type can cause instability and may cause property damage to the motor
and/or drive.
CAUTION
3.4.2
Use Motor Data From .ddf File Check box
When selecting a motor for use with the Epsilon EP-P drive the user has two basic options:
1.
Use a motor that already exists in the standard motor definition file (StdMotor.ddf) or custom motor definition file
(Motor.ddf).
Epsilon EP-P Drive Reference Manual
Revision A3
29
www.emersonct.com
2.
Create a custom motor that has not been used before.
When selecting option 1 from above (use an existing motor), the user simply selects one of the motors from the Motor Type list at the top of the
Motor view. Once the user selects a motor from the Motor Type list, the data for that motor is read from the pertinent .ddf file and then is
displayed in the Motor Parameters column on the Motor view (see Figure 37). The parameters in this column will be dimmed and unavailable
because the motor information comes directly from the .ddf file.
If the user wishes to edit one or more of the parameters read from the .ddf file, it is necessary to clear the “User Motor Data From .ddf File”
check box. Clearing the check box will break the “link” between the motor data displayed on this view, and the motor data in the .ddf file. This
is necessary because as soon as the user changes any of the values, it no longer matches the .ddf file, and is now in effect a “custom motor”.
When the “User Motor Data From .ddf File” check box is cleared, all of the values in the Motor Parameters column will become available, and
the Motor Name will be changed to “New Motor” so that there is no association with the existing motor that was previously selected. The user
can now change any of the values as desired and give the motor a new name. Once the values have been changed, the motor data only exists
within the active configuration. To save the new values into the .ddf file, the user must click on the Save .ddf Values button on the right side of
the view.
3.4.3
Motor Parameters Column
Motor Parameters column is a column of data displayed on the Motor view under the Setup view (See Figure 37). This column of data contains
the values for each of the motor data parameters. The values in this column are unavailable for edit if the “Use Motor Data From .ddf File”
check box is selected. This means that since the data is associated with the .ddf file, it cannot be changed. The values in this column become
available when the “Use Motor Data From .ddf File” check box is cleared. The user can then change one or more of the parameter values
because there no longer is a link to the data in the .ddf file.
If the user does edit motor parameter values on this view, those values are only stored within that particular configuration file. In order to save
the values to the .ddf file, the user must click the “Save .ddf Values” button on the right side of the view. Below are the motor parameter with a
brief description.
Motor Name
The motor name is limited to 12 characters and must begin with an alpha character (non-numeric character). This is the motor name that will
appear in the “Motor Type” list box above.
Peak Current
Specifies the peak current allowed by the motor. The motor manufacturer typically provides the peak current data.
If a system is “drive limited” (meaning that the motor can handle more current than the drive can deliver), the peak current actually used by the
system may be lower than the value specified here.
Continuous Current Rating
Specifies the continuous current allowed by the motor. It is used to determine the drive continuous current and peak current limits. The drive
can also limit the continuous current to the motor based on the drive capacity. The motor manufacturer typically provides the continuous
current data.
If a system is “drive limited” (meaning that the motor can handle more current than the drive can deliver), the continuous current actually used
by the system may be lower than the value specified here.
Motor Poles
Specifies the number of magnetic pole pairs (N-S) on the motor. The supported values are 2, 4, 6, 8, 10, 12, 14 and 16 poles. The motor
manufacturer typically provides the motor pole information.
Rotor Inertia
This parameter specifies the inertia of the motor rotor. The drive uses this parameter to interpret the “Inertia Ratio” parameter. “Inertia Ratio” is
specified as a ratio of reflected load inertia to motor inertia.
Motor KE
Specifies the Ke of the motor. The units are Vrms/ kRPM. The line-to-line voltage will have this RMS value when the motor is rotated at 1000
RPM. The range is 5.0 to 500.0 Vrms/ kRPM. The motor manufacturer will typically provide the Ke data.
Phase Resistance
Specifies the phase-to-phase resistance of the motor. This value is determined by measuring the resistance between any two motor stator
terminals with an ohm meter. The range is.1 to 50 ohms.
Phase Inductance
Specifies the phase-to-phase inductance of the motor.
Max Operating Speed
This parameter specifies the maximum speed of the motor when used with a variable speed drive to achieve velocities over the rated base
speed of the motor.
Encoder Lines/Rev
Specifies a coefficient for determining the number of encoder lines per mechanical revolution. The supported values are 1 to 16383. The
equation for determining the total number of encoder lines per revolutions is:
nLines = n*10x
where:
nLines = Total number of Encoder Lines
n = Motor Encoder Lines per Rev Coefficient
x = Motor Encoder Exponent
The total number of encoder lines is used both for commutation and for position/velocity control. To properly commutate the motor, the drive
30
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
must know the electrical angle (the angle between the motor magnetic field and stator coils).
Encoder Lines/Rev Exponent
Specifies a coefficient for determining the number of encoder lines per mechanical revolution. The supported values are 1 to
16383. The equation for determining the total number of encoder lines per revolutions is:
nLines = n*10x
where:
nLines = Total number of Encoder Lines
n = Motor Encoder Lines per Rev Coefficient
x = Motor Encoder Exponent
The total number of encoder lines is used both for commutation and for position/velocity control. To properly commutate the
motor, the drive must know the electrical angle (the angle between the motor magnetic field and stator coils).
Encoder Marker Angle
Specifies the electrical angle at which the marker (Z) pulse occurs with reference to VTS when the motor is spun in the encoder
reference direction. At power-up the drive obtains an initial estimate of the electrical angle from the status of the U, V and W
commutation tracks. This estimate can be off by as much as 30 °.
When the drive receives the marker pulse, the drive will, within one second, gradually shift the commutation to the more
accurate electrical angle specified by this parameter. The system will then operate more efficiently.
Encoder U-track Angle
Specifies the electrical angle at which the rising edge of the U commutation track will occur with reference to VTS when the
motor is spun in the encoder reference direction.
At power-up the drive looks at the status of the U, V and W commutation tracks and, using this parameter, obtains a crude (±
30 °) estimate of the electrical angle.
Encoder Reference Motion
Specifies the direction of motion assumed in phase plots of the encoder’s quadrature and summation signals. The supported
values are CW(1) and CCW(0). Your encoder may have the same phase plot but is generated from a different direction of
rotation. This parameter affects the way the drive interprets the quadrature and commutation signals.
Encoder Type
The supported values for this parameter are 1 and 0. If set to a 1 the drive uses the Encoder Marker angle as well as the
Encoder U Angle for commutation. If this parameter is set to a 0, the drive uses only the Encoder U Angle.
3.4.4
Run Auto-Tune Button
The drive has the ability to run an Auto-Tune operation thereby measuring several different motor parameters. Doing so allows
the drive to obtain certain parameters that are not typically provided by the motor manufacturer, and also optimizes other drive
parameters to work properly with the connected motor/load.
PowerTools Pro allows the user to initiate the Auto-Tune feature from the Motor view.
The following table shows which parameters must be entered in order to run the Auto-Tune feature, and which parameters are
measured by the Auto-Tune.
Motor Parameters
Needed to Run Auto-Tune
Measured by Auto-Tune Mode #
Motor Name
Peak Current
Yes
Continuous Current Rating
Yes
Motor Poles
Yes
Rotor Inertia
3
Motor Ke
3
Phase Resistance
2,3
Phase Inductance
2,3
Max Operation Speed
Yes
Encoder Lines/Rev
Yes
1,2,3
Encoder Lines/Rev Exponent
Yes
1,2,3
Encoder Marker Angle
1,2,3
Encoder U-Marker
1,2,3
Encoder Reference Motion
1,2,3
Encoder Type
All Auto-Tune modes cause motion. It is important to read and understand the warnings and instructions on the Auto-Tune
windows. It is strongly recommended to unload the motor before performing an Auto-Tune.
Epsilon EP-P Drive Reference Manual
Revision A3
31
www.emersonct.com
When online with the drive, to initiate an Auto-Tune, click RunAuto-Tune button. The Auto-Tune dialog box opens and contains warnings and
instructions related to the Auto-Tune procedure, as well as selection of the Auto-Tune mode. An example of one of the Auto-Tune windows is
shown in Figure 38.
Figure 38:
Auto-Tune Dialog Box - Auto-Tune Mode 3
After the Auto-Tune Mode has been selected, click Proceed, to start the Auto-Tune. As the Auto-Tune is executing the gray check boxes will
show the progress of the Auto-Tune. When the Auto-Tune is completed the Auto-Tune dialog box closes and the auto-tune results will be in the
Values from Drive column on the Motor view.
Auto-Tune Mode 1
Auto-Tune Mode 1 provides the encoder information of the motor. Auto-Tune Mode 1 is the most beneficial tuning by providing parameter
values that are difficult to measure or vary the most from common motor specifications. Auto-Tune Mode 1 will rotate the motor for 1 or more
revolutions at a slow speed.
With Auto-Mode 1 the test sequence is Moves 1 through 3 consisting of:
Move #1, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #2, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #3, Vel = 0.15 Electrical Cycles/sec (approx 1 rev/min), Distance < 1.0 Revolutions of motor, Direction = CW
The parameters measured in Auto-Tune Mode 1 are Encoder Marker Angle, U-track Angle, Encoder Reference Motion and Encoder
Resolution.
As Auto-Tune Mode 1 is executed the test is checked off, Phase 1 Encoder Marker Angle, U Angle, Motion.Resolution
Auto-Tune Mode 2
Auto Tune Mode 2 provides and method to determine the motor resistance and inductance. These are used in the current control loop. It is
more accurate to make these measurements with external meters. If you do not have measured motor resistance and inductance, you can use
auto tune 2.
Auto Mode 2 is a subset of auto mode 3 running Moves 1 through 3:
Move #1, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #2, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #3, Vel = 0.15 Electrical Cycles/sec (approx 1 rev/min), Distance < 1.0 Revolutions of motor, Direction = CW
The parameters measured by Auto-Tune Mode 2 are those tested in Auto-Tune Mode 1 plus Phase Resistance and Phase Inductance.
As Auto-Tune Mode 2 is executed, the completed portion of the test is checked off,
Phase 1 Encoder Marker Angle, U Angle, Motion.Resolution
32
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Phase 2 Voltage for Phase 3
Phase 3 Resistance and Inductance
Auto-Tune Mode 3
Auto Tune Mode 3 provides a method to determine the motor Ke and Rotor Inertia. These are used in the velocity control loop.
It is more accurate to use the Motor Ke and Rotor Inertia from the manufacturer. If you do not have manufacturer provided
motor Ke and Rotor Inertia specifications, you can run an Auto-Tune Mode 3.
Auto-Tune Mode 3 runs the motor at 75% max motor velocity. If the load is connected this may cause harm to the
system or personnel. It is strongly recommended to unload the motor before performing any Auto-Tune Mode.
WARNING
Auto-Tune Mode 3 is the full auto-tune running Moves 1 through 5:
Move #1, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #2, Vel = Max Motor Vel, Distance < (1 / # of motor poles) motor revs, Either Direction
Move #3, Vel = 0.15 Electrical Cycles/sec (approx 1 rev/min), Distance < 1.0 Revolutions of motor, Direction = CW
Move #4, vel < 0.75 max motor velocity, Time = 4 sec, Direction = CW
Move #5 - #12, vel < 0.75 max motor velocity, Distance = 3 Revolutions of the motor, Direction = CW
As Auto-Tune Mode 3 is executing the completed portion of the test is checked off,
Phase 1 Encoder Marker Angle, U Angle, Motion.Resolution
Phase 2 Voltage for Phase 3
Phase 3 Resistance and Inductance
Phase 4 Motor Ke
Phase 5 Rotor Inertia
3.4.5
Values from Drive Column
The Values from Drive column shows the new motor parameters as a result of an Auto-Tune. These parameters are
continually being read from the drive. The theory of operation is that the user will perform an Auto-Tune function that reads/
measures/calculates the motor parameters within the drive. The results are read from the drive and displayed in the Values
from Drive column. Once they are displayed in PowerTools Pro (in the Values From Drive column) the user can apply those
values to the Motor Parameters column by clicking on the Apply to Config. button, in the middle of the Motor view (this button
looks like a series of arrows pointing from the Values from Drive column towards the Motor Parameters column).
The values in the Values from Drive column are not saved as part of the configuration file. To save these values, the user must
use the “Apply to Config” button to save them.
This column is only functional when online with the drive. When offline, the values in the Values from Drive column will all read
zero.
3.4.6
Apply to Config. Button
After any Auto-Tune has been performed, the results are displayed in the Values from Drive column on the Motor view and the
measured parameter values are saved in the drives NVM. When the user clicks Apply to Config., the values in the Values
From Drive column are transferred into the Motor Parameters column. The configuration file then can be saved to disk.
Therefore, in order to store the motor parameter values in the drives flash memory the configuration file must be downloaded
to the drive using Device > Download.
3.4.7
Save .ddf Values Button
Once the user has entered the data for the motor they are using, they may or may not wish to save the motor data to the
Motor.ddf file so it can be easily recalled at a later time. If the user does not save the motor data to the Motor.ddf file, then the
motor data will only reside in the specific application configuration file that it has been entered into.
In order to save the motor data to the Motor.ddf file, click the Save .ddf Values button. This takes all the parameter values and
writes them to the Motor.ddf file.
When saving to the .ddf file, if PowerTools Pro finds that a motor already exists with the same name, the User Defined Motor
Name Conflict dialog box will appear. The user must then decide how to proceed with saving the motor data .ddf file.
User Defined Motor Name Conflict Dialog Box
The purpose of this dialog box is to resolve conflicts between the application’s motor settings and those defined in the .ddf file.
The User Defined Motor Name Conflict dialog box opens during the following conditions:
1.
From the Motor view, click the Save .ddf values button and the motor already exists with the same name but
has different motor parameters
2.
Opening an application (or uploading a application), where the Use Motor data from the .ddf file check box is
select but the data in the application no longer matches the .ddf file.
This occasionally occurs when a newer version of PowerTools Pro is installed and the parameters for the
standard motors has been updated in the .ddf file.
If the motor name does not exist in the .ddf file, it will be written into the file.
Epsilon EP-P Drive Reference Manual
Revision A3
33
www.emersonct.com
Figure 39:
The User Defined Motor Name Conflict Dialog Box
The User Defined Motor Name Conflict dialog box presents the user with four options on how to proceed with saving the motor data. Those
four options are:
Create new motor entry In .ddf File
The user can select to keep the existing data and create a new entry into the motor.ddf file with a different name. After selecting this option, the
user simply enters a new name in the Please enter a new motor name text box. Then click OK, the data will be written to the .ddf file using the
new motor name.
Overwrite existing .ddf file motor entry
The user can select to overwrite the existing data in the .ddf file with the current data in the Motor Parameters column. If this option is selected,
the data in the .ddf file will be overwritten and the overwritten data will be lost forever. The overwritten data cannot be recovered.
If the user attempts to overwrite data for a Standard Motor (in the stdmotor.ddf file), the operation will be canceled and the user will be notified
that they cannot proceed. The figure below shows the error message that will be produced when the user attempts to overwrite a standard
motor. In this case, the user would need to change the motor name before saving to the .ddf file.
Load and use motor parameters from matching motor in .ddf file
If this option is selected, the motor data in the Motor.ddf or stdmotor.ddf file for the matching Motor Name will overwrite the data in the Motor
Parameters column. After this option is selected, the “Use Motor Data From .ddf File” check box will be selected, and all the parameter values
will be unavailable.
Retain existing Motor Parameters without saving to .ddf
If the user selects this option, the values in the Motor Parameters column will not be written to the motor.ddf file, and the values will only reside
within the configuration file. The specific motor data values will not be available for selection in the Motor Type list box because they are not
saved to the .ddf file. The “Save .ddf Values” operation is in effect canceled.
Existing Motor Names List Box
This list box is part of the User Defined Motor Name Conflict dialog box and contains all the names of the motors that exist in the motor.ddf and
stdmotor.ddf files. When selecting a new name, it is important to select a name that is not already displayed in this list box.
Parameters Not Matching List
This list is part of the User Defined Motor Name Conflict dialog box and displays the parameter value(s) from the Motor Parameters column
that do not match the equivalent parameter value in either the motor.ddf or stdmotor.ddf files, for the motor with the matching name.
This helps the user to determine whether they wish to overwrite, cancel, or create a new motor with this Save .ddf Values operation.
34
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.5
User Units View
The User Units View is used to scale the desired application units into known values. All information for distance, velocity, and
accel/decel units are set up here and used throughout the system setup.
By selecting User Units in the Hierarchy Tree, the User Units view will appear on the right (see Figure 40).
Figure 40:
3.5.1
User Units View
Distance Group
Units Name
This is a 10-character name for the distance user units the user wants to use in the application.
Decimal Places
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all distance
and position parameters throughout the configuration. Using a high number of decimal places will improve position resolution,
but will also limit the range of absolute position. You can select from zero to six decimal places of accuracy.
NOTE
When the number of decimal places are changed in an existing configuration file the Index accel and decel parameters need
to be checked.
Scaling
A Characteristic Distance and Length must be established to allow the drive to scale user units back to actual motor
revolutions. This scaling factor is as follows:
Characteristic Distance
Scaling = -----------------------------------------------------------------Characteristic Length
Characteristic Distance
This is the distance the load travels (in user units) when the motor travels the characteristic length (in motor revolutions).
Characteristic Length
This is the distance the motor travels (in whole number of revolutions) to achieve one characteristic distance of load travel.
Distance Scaling Examples:
A 1.5" diameter pulley is used to drive a conveyor belt, and the user wishes to use units of inches instead of revolutions.
Units Name — Set to Inches
Decimal Places — Set to desired accuracy 0.000
In one revolution of the motor (or pulley), the belt will travel a distance of one pulley circumference.
= 1.5" x 
= 1.5 x 3.14...
= 4.712 inches / revolution
Characteristic Distance = 4.712
Scaling = ---------------------------------------------------------------------------------------Characteristic Length = 1
Epsilon EP-P Drive Reference Manual
Revision A3
35
www.emersonct.com
If the user decides to put a 5:1 reducer on the system, the user simply needs to change the Characteristic Length.
Now the belt travels 4.71" in 5 motor revolutions.
Characteristic Distance = 4.712
Scaling = ------------------------------------------------------------------------------------------Characteristic Length = 5
Keep in mind that the characteristic length is always a whole number and the valid range is from 1 to 2000.
NOTE
User Units may affect end motor speed and could cause trajectory faults.
Because of internal math in the Epsilon EP-P drive, some user unit combinations may cause a drive trajectory faults. The maximum motor
velocity allowed by the drive is detailed under the distance section of the User Units View and is labeled “User Unit Limited Speed”. When the
user unit setup is altered in such a way that the maximum motor speed allowed by the drive is less than the maximum speed allowed by the
chosen motor, the readout of maximum motor speed allowed by the drive changes to have a red background. If a configuration is downloaded
to the drive with a red background on the “User Unit Limited Speed”, the drive will obtain a trajectory fault at speeds near this velocity. To
alleviate this issue, simply remove decimal places from your user units, and/or change the characteristic distance (numerator) of your scaling
parameters to be a smaller number that it was. The red background indicating trajectory faults will go away when the user unit setup is scaled
for a realistic accuracy based on the encoder counts per revolution.
3.5.2
Velocity Group
Enable Separate Distance Units Check Box
If selected (enabled), separate distance and velocity units, name and scaling will be enabled. If not enabled, the velocity units, name and
scaling will be defined by the Distance Group.
Scaled Distance Name
If the user wants the velocity units to have a different distance scaling than the distance units a name can be entered here up to 10 characters.
For example, the user distance units name could be inches while the velocity units name is feet per minute.
Velocity Distance Units Scale Factor
This parameter scales the Velocity Distance Units back to actual distance units. To do this, enter the number of distance user units that are
equal to one velocity scaled distance unit.
Separate Distance Units Example:
A user has an application using a leadscrew with a 0.5"/turn lead. The user wants to have Distance Units of Inches, but wants Velocity Units of
Feet so motion can be programmed in feet/minute.
Distance Units Name — Inches
Enable Separate Distance Units — Select check box (enabled)
Scaled Distance Name — Feet
Velocity Distance Units Scale Factor — # of Distance Units / 1 Scaled Distance Unit
1 Foot = 12 Inches
Velocity Distance Units Scale Factor = 12
Time Scale List Box
The time can be one of two values: seconds or minutes. This selection sets the real-time velocity time scale.
Decimal Places
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all real-time velocity
parameters throughout the software. Using a high number of decimal places will improve velocity resolution, but will also limit the maximum
velocity. You can select from zero to six decimal places of programming resolution.
3.5.3
Acceleration Group
Time Scale List Box
From this list box, select the acceleration time scale to be used for all real-time profiles. The time scale selected will be used for both
acceleration and deceleration parameters. You can select from milliseconds or seconds.
Decimal Places
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all real-time accel/decel
parameters throughout the software. Using a high number of decimal places will improve accel/decel resolution, but will also limit the
maximum accel/decel rate. You can select from zero to six decimal places of programming resolution.
3.5.4
Torque Group
Units Name
10-character name for the torque user units.
Decimal Places
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all torque parameters
throughout the software. Using a high number of decimal places will improve torque resolution, but will also limit the maximum torque. You can
select from zero to six decimal places of programming resolution.
Scaling
The amount of torque in user torque units will be set equal to the Percent Continuous Current. This parameter is used to scale the actual
36
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
torque back into the user defined units. The units of this parameter are % ContinuousCurrent. This scaling factor is used
along with the user torque to establish a relationship between torque user units and actual torque.
3.6
Dual Loop View
Dual Loop View provides the setup parameters to have an axis position controlled by a remote or secondary encoder, while
maintaining a velocity encoder feedback to help with loop stability and to prevent the axis “runa way” if the remote encoder
becomes disconnected.
An example application would be where a web is pulled through rollers, but there is not a precise gripon the material so it can
slip a little and so loose position. This is solved by an external encoder touching the web and providing the accurated feedback
of the web position.
Figure 41:
3.6.1
Dual Loop View
Display Dual Loop Setup
Select this check box to enable the Dual Loop Mode feature which accepts a secondaryfeedback device to close the position
loop while still using the motor encoder to close the velocity loop.
3.6.2
Position Encoder Setup Group
Position Feedback Polarity
Position Feedback Polarity defines the direction of the position encoder that corresponds to a positive position change. This
value is somewhat arbitrary, since the position encoder can be mounted to spin CW or CCW as the material moves "forward".
If this value is not set correctly in Dual Loop mode the motor will rotate in the opposite direction as desired.
Master Interpertation
This parameter determines how the incoming pulses are seen to generate the synchronized motion command. This setting
allows the user to choose the appropriate signal type to match the device generating the master input pulses.
Pulse Quadrature
The most common type for use with incremental encoders using AB Quadrature signals
Pulse Direction
Used with Step and Direction control signals
Pulse Pulse
Used with Pulse Forward and Pulse Reverse control signals
Available when Sync Encoder Input is selected as the Master Source on the MasterUnits View or on the Dual Loop View when
the Dual Loop setup checkbox is selected enabling the feature.
Drive Input Signal
This is selected accordingly based on whether the incoming pulses are Differential (default) or Single Ended. Available when
Sync Encoder Input is selected as the Master Source on the Master Units view or when the Dual Loop feature is enabled.
Epsilon EP-P Drive Reference Manual
Revision A3
37
www.emersonct.com
3.6.3
Sync Output Connector Group
Output Source
This determines which signal is sent out the Sync Output connector on the drive. If Motor Encoder (default) is selected, the encoder signals
from the motor that the drive is controlling will be sent out the 15-pin Analog/Sync Output connector (J5). If Drive Encoder Input is selected,
then the signals coming in the drives 9-pin Sync Input connector on the drive will be sent out the Analog/Sync. Output connector. When Virtual
Master is selected the virtual master signal generated by the drive will be sent out the Analog/Sync. Output connector.
3.6.4
Dual Loop Encoder Ration
Motor Encoder
Dual Loop Encoder Ratio = ------------------------------------------------Position Encoder
Motor Encoder
This parameter is the numerator in the ratio used to define the mechanical ratio between the Motor Encoder and the Position Feedback
Encoder. This parameter is only used when Dual Loop Control Mode is enabled, and must be set correctly to achieve the correct target
velocity.
Position Encoder
This parameter is the denominator in the ratio used to define the mechanical ratio between the Motor Encoder and the Position Feedback
Encoder. This parameter is only used when Dual Loop Control Mode is enabled, and must be set correctly to achieve the correct target
velocity.
3.7
Master Units View
Master Units View provides the setup parameters for use with synchronized motion. This setup window determines how the encoder signals
are interpreted and establishes the scaling for all master units (master distance, master velocity, etc.).
Figure 42:
3.7.1
Master Units View
Encoder Setup Group
Master Source
Master Source (MasterAxis.Source) indicates the source of the master encoder input.
Select Custom Variable, the Custom Variable text box will became available to enter a parameter. The custom variable can be entered two
ways: by just typing any parameter into the text box using the program format for the variable, or click the Popup Variables button and the
Select Variables from Tree window will open. Select the variable and drag it over to the Custom Variable text box.
Select Sync Encoder Input to use the Sync Input connector (J10) on the Epsilon EP drive.
Select Virtual Master.Counts to use the Virtual Master as the Master Source.
Custom Variable
The Custom Variable (MasterAxis.CustomSourceVariable) text box is only available once the user has selected Custom Variable from the
Master Source list box. This field is used to define what parameter will be used as the Master Source. The Custom Variable can be entered two
ways: by just typing any parameter using the program format for the variable, or click the Popup Variables button and the Select Variables from
Tree window will open. Select the variable and drag it over to the Custom Variable text box.
38
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Master Polarity
Master Polarity (MasterAxis.Polarity) defines the direction of the master encoder that corresponds to a positive master position
change.
Master Interpretation
Master Interpretation (MasterAxis.Interpetation) determines how the incoming pulses are seen to generate the synchronized
motion command. This setting allows the user to choose the appropriate signal type to match the device generating the
master input pulses.
Drive Input Signal
Drive Input Signal is selected based on whether the incoming pulses are Differential (default) or Single Ended. Available only
when Sync Encoder Input is selected as the Master Source.
3.7.2
Sync Output Connector Group
Output Source
Output Source determines which signal will be sent to the 15-pin Analog/Sync Output connector on the drive. If Motor Encoder
(default) is selected, then the encoder signals from the motor that the drive is controlling will be sent out the Analog/Sync
Output connector. If Drive Encoder Input is selected, then the synchronization signals sent to the drives 9-pin Sync Input
connector will be sent to the drives Analog/Sync Output connector. When Virtual Master is selected the Virtual Master that was
setup on the Virtual Master view is sent to the Analog/Sync Output connector.
3.7.3
Master Position Setup Group
Define Home Position
Define Home Position (MasterAxis.DefineHomePosn) is the value that the Master Position Feedback will be set to when the
MasterAxis.DefineHome destination is activated. After the MasterAxis.DefineHome has been activated, the
MasterAxis.AbsolutePosnValid source will activate.
Rotary Rollover Check Box
When selected, (MasterAxis.RotaryRolloverEnable=on)the rotary rollover feature for the Master Axis will be enabled.
Rotary Rollover
If enabled, the Master Position will rollover to zero at the value specified here. As the master encoder counts up, the master
position feedback will increase until it reaches the Rotary Rollover value (MasterAxis.RotaryRolloverPosn) and then reset to
zero and continue to count up. If rotating in the negative direction, the master position feedback will decrease until it reaches
zero, and then start over at the Rotary Rollover value.
3.7.4
Master Distance Units Group
The parameters in this group are used to establish the scaling of the master axis into user units.
Units Name
This is a text string up to 12 characters that will be used to define the units of distance traveled by the master axis for incoming
synchronization signals.
Decimal Places
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all distance
and position parameters used in synchronized motion throughout the software. Using a high number of decimal places will
improve position resolution, but will also limit the maximum position. You can select from zero to six decimal places of
programming resolution.
Scaling
When Sync Encoder Input is selected as the Master Source then the scaling factor is defined as
MasterAxis.CharacteristicDistance/MasterAxis.Counts. The numerator (top value of the scaling fraction) is the Characteristic
Distance. The denominator (bottom value of the scaling fraction) is the # of Counts. The Characteristic Distance is the number
of Master Distance Units that will be traveled per number of counts in the bottom of the fraction. The Counts parameter is the
number of incoming pulses it takes to travel the characteristic distance.
3.7.5
Master Velocity Units Group
Decimal Places
3.7.6
Master Acceleration Units Group
Decimal Places
Decimal Places determines the number of decimal places to be used in the velocity parameter for all synchronized motion.
The number of decimal places set in this parameter determines the number of digits after the decimal point used in all realtime accel/decel parameters used for synchronized motion throughout the software. Using a high number of decimal places
will improve accel/decel resolution, but will also limit the maximum accel/decel rate. You can select from zero to six decimal
places of programming resolution.
3.7.7
Master Position Filter Group
The master position filter is designed for applications where the master encoder input requires smoothing due to low resolution
or high gain. These applications include low speed masters, low resolution master encoders, and large follower to master gear
ratios.
Filters inherently introduce phase shift (or delay) in the followers response to the master position, velocity and acceleration.
Epsilon EP-P Drive Reference Manual
Revision A3
39
www.emersonct.com
The drive provides Feedforward compensation to correct for these delays introduced by the filter.
The user may set the number of filter samples to be used to “smooth” the master encoder velocity. The more samples used by the filter, the
smoother the master velocity signal, however, the more positional delay introduced by the filter. This means that more filtering will cause more
position error between master and follower. Feedforward is used in conjunction with the filter to provide accurate positioning performance while
still maintaining smooth motion.
The following table can be used to best determine the proper filter settings for your application.
Feedforward OFF
Feedforward ON
Disabled
One update of phase shift
(not velocity dependent)
No Filtering
No delay,
No Filtering
4
Small Lag (function of
speed),
Low Filtering
Poor at low speed,
Low Filtering
8
Medium Lag (function of
speed),
Medium Filtering
Good at low speed,
Medium Filtering
16
Large Lag (function of
speed),
High Filtering
Best at low speeds,
High Filtering
# of
Sample
s
Smoother
Increasing
Lag with FF
Off
Reduced Lag
Filter parameters cannot be changed using the “Update to RAM” feature. Changes must be fully downloaded before taking effect.
The gray box in the table above denotes the default setting for the master filter parameters.
Enable Check Box
The Enable check box is used to turn on or turn off the Master Position Filter. If selected, the filter is turned on (active) and the user must select
the number of samples used by the filter. If clear, the filter is not used.
Samples
Defines the number of samples used by the filter to smooth the master signal. Increasing the number of samples increases smoothness, but
also increases lag. See Filter table above to select proper setting.
Enable Feedforward Check Box
The Enable Feedforward check box is used to turn on or turn off feedforward. If selected, feedforward is active. If the check box is clear,
feedforward is not used.
3.8
Virtual Master View
The Virtual Master View is used to create a simulated encoder output. It generates an encoder stream of counts without the actual operation of
a motor. This count can be used by the drive itself as an input to the Master Source (MasterAxis.Source). It can also be transmitted to other
drives through the Sync Encoder Output connector and into their Master Sync Input connector.
Figure 43:
3.8.1
Virtual Master View Enabled
Enable Virtual Master Check Box
Enable Virtual Master check box (VirtualMaster.VirtualMasterEnable) by default is clear. Select the check box to enable the virtual master
40
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
feature.
3.8.2
Virtual Master Setup Group
Distance
Distance (VirtualMaster.Dist) is the incremental distance virtual master will move, in user units, if the virtual master is initiated
as an index.
Velocity
Velocity (VirtualMaster.Vel) is the maximum virtual velocity that will be attained by the virtual master. This parameter is in user
units.
Acceleration
Acceleration (VirtualMaster.Accel) is the acceleration rate, in user units, that the virtual master will use to accelerate. This
parameter is used when in either jog or indexing mode.
Deceleration
Deceleration (VirtualMaster.Decel) is the deceleration rate, in user units, that the virtual master will use to decelerate in either
jog or index mode.
Marker Count
The encoder marker pulses are simulated and this parameter (VirtualMaster.MarkerCount) specifies the number of
VirtualMaster.Counts per encoder marker pulse generated.
3.8.3
Virtual Master Conversion Ratio Group
Scaling
Converts the user units distance into virtual counts.
VirtCnts
The numerator (top value of the scaling fraction) is the VirtualMaster.CharacteristicLength. The characteristic length is the
number of virtual counts that will be generated per the distance, in user units, defined by the denominator (bottom number of
the scaling fraction).
Distance (UserUnits)
The denominator (bottom value of the scaling fraction) is VirtualMaster.CharateristicDistance, in user units, and is used with
VirtualMaster.CharacteristicLength to create the virtual master conversion ratio.
Example:
If the user sets the numerator to 10,000 and the denominator to 1 revs, then 10,000 virtual counts will be sent out when the
virtual master produces 1 rev of virtual motion.
3.8.4
Feedrate Group
FeedRate Override
This parameter (VirtualMaster.FeedRateOverride) is used to scale the Virtual Master counts. It can be described as “scaling in
real time”. The default setting of 100% will allow all counts to occur in real time. A seeing of 50% will scale time so that all
counts are half as fast as they are at 100%. A setting of 200% will scale time so that all count run twice as fast as they would
at 100%. Feed Rate Override is always active, and this parameter may be modified via Modbus, Ethernet, or in a program.
FeedRate Decel/Accel
FeedRate Decel/Accel (VirtualMaster.FeedRateDecelerationTime) specifies the ramp used when velocity changes due to a
change in the FeedRate Override value. The units of FeedRate Decel/Accel are seconds/100%. Therefore, the user must
specify the amount of time (in seconds) to accelerate or decelerate 100% of programmed feedrate.
3.9
Position View
The Position View allows you to set up and view the parameters related to drive positioning. In Figure 44, Position has been
selected in the Hierarchy Tree. The right side of the view is divided into groups. An explanation of the groups and their
functions is provided below.
Epsilon EP-P Drive Reference Manual
Revision A3
41
www.emersonct.com
Figure 44:
3.9.1
Position View
Settings Group
Define Home Position
Define Home Position (DefineHomePosn) is the value to which the Position Command will be set when the DefineHome destination is
activated. This is used in applications which do not use a home routine but, require a known reference point. The units are defined on the User
Units View.
In Position
The In Position (InPosn) source will activate at the end of a move if the absolute value of following error is less than or equal to the In Position
Window (InPosnWindow) for the In Position Time (InPosnTime).
In Position Window (InPosnWindow)
The absolute value of the Following Error must be less than or equal to this value at the end of an index in order for the InPosn source to
activate. This window is set in units specified in the User Units View.
Example:
The In Position window is set to 0.0025 revs. At the end of an index, the following error is calculated to be 0.0012 revolutions. Therefore,
the InPosn source will activate.
Or the In Position window is set to 0.001 inches. If at the end of an index, the following error is calculated to be.0015 inches, then the InPosn
source will not activate.
In Position Time (InPosnTime)
This is the amount of time in seconds that commanded motion must be complete and the absolute value of the following error must be less
than the In Position Window for the InPosn source to activate. If set to zero (default), then InPosn will activate as soon as motion stops and the
following error is less than the In Position Window parameter value.
3.9.2
Limits Group
Enable Following Error Check Box
Select this check box (FollowingErrorEnable) to enable (or disable if the check box is clear) the Following Error Limit. If enabled, a fault will be
generated if the absolute value of the following error ever exceeds the value in the following error parameter. If disabled, a fault will never be
generated.
Following Error
Following Error (FollowingError) is the difference between the Position Command and the Position Feedback. It is positive when the Position
Command is greater than the Position Feedback. If the absolute value of the following error exceeds the value you enter here, the drive will
generate a Following Error Fault (F). All accumulated Following Error will be cleared when the drive is disabled.
The Following Error Limit is defined in user units.
Enable Software Travel Limits Check Box
Select this check box (SoftwareTravelLimitEnable) to enable (or disable if clear) the software travel limits. If disabled, the software travel limits
are not monitored.
Software Travel Limits
Software Travel limits can be used to limit machine travel. They are often setup inside the hardware travel limits to add another level of security
or protection from exceeding the machines travel limits. The Epsilon EP-P drive constantly monitor the feedback position, and if this position
exceeds the values entered for Software Travel Limit + or -, then the drive will decel to a stop. Software Travel Limits are not functional unless
the Absolute PosnValid source is active. AbsolutePosnValid is active upon successful completion of a home or the DefineHome destination is
activated.
To recover from a software travel limit, a jog may be commanded in the opposite direction of travel. For example, if a software travel limit - is
42
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
hit, then the axis can be jogged in the + direction.
Software Travel Limit + (SoftwareTravelLimitPlusPosn)
If the absolute position is greater than or equal to this value the SoftwareTravelLimitPlusActive source shall activate.
A rising edge occurs when the absolute position is greater than or equal to the parameter SoftwareTravelLimitPlusPosn. A
falling edge will be generated as soon as the above is not true.
Software Travel Limit - (SoftwareTravelLimitMinusPosn)
If the absolute position is less than or equal to this value the SoftwareTravelLimitMinusActivate shall activate.
A rising edge occurs when the absolute position is less than or equal to the parameter SoftwareTravelLimitMinusPosn. A
falling edge will be generated as soon as the above is not true.
3.9.3
Rotary Group
Rotary Rollover Check Box
Select this check box (RotaryRolloverEnable) to enable (or disable if clear) the rotary rollover feature.
Rotary Rollover
This parameter (RotaryRolloverPosn) is used in rotary applications and determines the position at which the internal position
counter will be reset to zero.
Example:
The user has a rotary table application with distance user units of degrees, 360.00 degrees/1 rev. The Rotary Rollover
would be set to a value of 360°.
The motor is travelling in the positive direction. As the feedback position reaches 359.999 and continues on, the feedback
position will reset (or roll-over) to zero. If the motor changes direction and travels in the negative direction, the position will
rollover at 0 to 359.999 degrees and count down. The resolution of the rotary rollover point is determined by the Distance
Units Decimal Places parameter on the User Units view in the PowerTools Pro software.
If an absolute index is used with a non-zero rotary rollover point, the Epsilon EP-P drive will calculate the shortest path to its
destination and move in the required direction.
To force the motor to run a certain direction, use the Rotary Plus or Rotary Minus type of indexes.
3.9.4
Online Tab (not shown)
While online, the following real-time data will be displayed.
Motor Position Group
Position Command
This is the commanded position in user units.
Position Feedback
This is the feedback position of the motor in user units.
Following Error
The Following Error is the difference (in user units) between the Position Command and the Position Feedback. It is positive
when the Position Command is greater than the Position Feedback.
Encoder Position
The motor position in encoder counts since power up when the value was set to zero. This is a signed 32-bit value.
3.10
Velocity View
The Velocity View allows the setup of feedrate override details.
By selecting Velocity in the Hierarchy Tree, the Velocity View will appear on the right (see Figure 45).
Epsilon EP-P Drive Reference Manual
Revision A3
43
www.emersonct.com
Figure 45:
Velocity View
3.10.1 Settings Group
FeedRate Override
This parameter is used to scale all motion. It can be described as scaling in real time. The default setting of 100% will allow all motion to occur
in real time. A setting of 50% will scale time so that all moves run half as fast as they do at 100%. A setting of 200% will scale time so that all
moves run twice as fast as they would at 100%. FeedRate Override is always active and affects all motion, including accels, decels, dwells,
and synchronized motion. This parameter may be modified via Modbus or in a program.
FeedRate Decel/Accel
The FeedRate Decel/Accel parameter specifies the ramp used when velocity changes due to a change in the FeedRate Override value. The
units of FeedRate Decel/Accel are Seconds/100% of FeedRate. Therefore, the user must specify the amount of time (in seconds) to accelerate
or decelerate 100% of FeedRate.
Example:
Feedrate Override is set to 100% (default). The user wishes to slow down motion to 50% of programmed velocity. If FeedRate Decel/Accel
is set to 1 Sec/100%, when the FeedRate Override parameter is changed to 50%, it will take 0.5 seconds to decelerate to 50% velocity.
Decel/Accel Time
= FeedRate Decel/Accel * % Change in FeedRate
= (1 Sec/100%) * (100% - 50%)
= 0.5 Seconds
44
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Example:
A user wishes to accelerate from 100% programmed velocity to 175% in 0.5 Seconds. Therefore, the value they need to
enter for Feedrate Decel/Accel is calculated as follows:
FeedRate Decel/Accel
=
=
=
=
=
Decel Time/ % Change in FeedRate
(0.5 Sec) / (175% - 100%)
0.5 Sec / 75%
(0.5 Sec) / (100% * 75%)
0.66 Sec / 100%
3.10.2 Online Tab (not shown)
If online, the following real-time data will be displayed.
Motor Velocity Group
Velocity Command
The Velocity Command is the actual command generated by the drive to the motor in user units.
Velocity Feedback
This parameter is the actual feedback motor velocity in user units.
3.11
Ramps View
The Ramps View allows the user to define various accel/decel ramps used under typical application conditions. By selecting
Ramps in the Hierarchy Tree, the Ramps View will appear on the right (see Figure 46).
Figure 46:
Ramps View
3.11.1 Settings Group
Acceleration Type
The Acceleration Type list box display the various acceleration types: 5/8 S-Curve, 1/4 S-Curve, Linear, and S-Curve.
This is used to select the acceleration/deceleration type for all motion (homes, jogs and indexes). The “S-Curve” ramps offer
the smoothest motion, but lead to higher peak acceleration/deceleration rates. “Linear” ramps have the lowest peak
acceleration/deceleration rates but they are the least smooth ramp type. “5/8 S-Curve” ramps and “1/4 S-Curve” ramps use
smoothing at the beginning and end of the ramp but have constant (linear) acceleration rates in the middle of their profiles.
The “5/8 S-Curve” is less smooth than the “S-Curve” but smoother than the “1/4 S-Curve”.
S-Curve accelerations are very useful on machines where product slip is a problem. They are also useful when smooth
machine operation is critical. Linear ramps are useful in applications where low peak torque is critical. Below is a comparison
of the 4 ramp types:
S-Curve: Peak Acceleration = 2 x Average Acceleration
5/8 S-Curve: Peak Acceleration = 1.4545 x Average
1/4 S-Curve: Peak Acceleration = 1.142857 x Average Acceleration
Linear: Peak Acceleration = Average Acceleration
Honor Distance Enable Group
User Ramps/Auto Calculate Ramps
The user has the ability to select one of two ramp control types for the entire motion control system. By default, User Ramps is
selected, The user can change the ramp controls in PowerTools Pro and perform a download to make the change, or the
parameter AutoCalcRampsEnable can be turned On or Off within a program. To enable User Ramps, AutoCalcRampsEnable
should be turned Off, and to enable Auto Ramps, AutoCalcRampsEnable should be turned On. Once a motion profile is in
Epsilon EP-P Drive Reference Manual
Revision A3
45
www.emersonct.com
progress, changes to this parameter will be ignored until the next motion is initiated. See the description of each of the ramp types below.
User Ramps Radio Button
Prior to the introduction of this feature, User Ramps was the only ramp control type available. When User Ramps are enabled, the Acceleration
or Deceleration ramp entered by the user will ALWAYS be used during a motion profile, even if that means the motor must overshoot the
entered stopping position. Under this circumstance, the acceleration or deceleration ramp would be honored, and therefore the motor may
need to reverse directions after coming to a stop in-order to reach the user entered target position. This scenario most often occurs when using
Compound or Blended Index instructions within a program. During Compound or Blended indexes, the user occasionally does not enter an
aggressive enough acceleration or deceleration ramp to reach the target velocity within the specified distance. See Figure 47 and Figure 48
below for examples of how User Ramps work. For more information on Index.#.CompoundInitiate and/or Index.#.BlendInitiats, see the
programming section of this manual.
Auto Calculate Ramps Radio Button
When Auto Calculate Ramps is selected the drive will automatically calculate the necessary ramp to reach the target velocity within the user
specified distance without any overshoot. In this scenario, the user entered acceleration of deceleration rate is ignored, See the figures below
for examples of how Auto Calculate Ramps work.
Distance
(Revs)
Velocity
(RPM)
Accel
(RPM/sec)
Decel
(RPM/sec)
Index 0
20
1250
2000
3000
Index 1
3
500
500
500
= Index 0
= Index 1
V
1
1250
3
4
2
500
t
Compound Index
User Ramps
Blended Index
User Ramps
Compound Index
Auto Ramps
Blended Index
Auto Ramps
1.
Index.1.Accel specified by user is used to decelerate from Index.0.Vel, to Index.1.Vel, but overshoots since ramp is not
aggressive enough to reach Index.1.Vel within Index.1.Dist of 3 Revs.
2.
Index.1 begins at Index.1.Vel but since Index.1.Decel specified by user is not aggressive enough to decelerate to zero velocity
within Index.1.Dist of 3 Revs slight overshoot occurs.
3.
Index.1 begins at Index.0.Vel and ramp is automatically calculated to reach zero speed within Index.1.Dist of 3 Revs without any
overshoot. If Index.1.Accel and or Decel were aggressive enough to reach zero speed within 3 Revs, they would have been used
instead of automatically calculating the ramp.
4.
Index.1 begins at Index.1.Vel and ramps is automatically calculated to reach zero speed within Index.1.Dist of 3 Revs without
any overshoot. If Index.1.Decel was aggressive enough to reach zero speed within 3 Revs, it would have been used instead of
automatically calculating the ramp.
Figure 47:
Ramps Examples of a Fast Index to a Slower Index
46
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Distance
(Revs)
Velocity
(RPM)
Accel
(RPM/sec)
Decel
(RPM/sec)
Index 0
5
500
1000
1000
Index 1
20
1250
2000
2000
= Index 0
= Index 1
V
1250
1
4
3
2
500
t
Compound Index
User Ramps
Blended Index
User Ramps
Compound Index
Auto Ramps
Blended Index
Auto Ramps
1.
Index.0.Accel specified by user is used to accelerate up to Index.0.Vel. Index.0.Accel is aggressive enough to
reach Index.0.Vel within Index.0.Dist of 5 Revs. Since indexes are compounded together, Index 1 begins at
Index.0.Vel.
2.
When indexes are Blended, Index 0 should end at velocity of Index 1, but Index.0.Accel is not aggressive
enough to reach Index.1.Vel within Index.0.Dist of 5 Revs. Therefore, entire distance of Index 0 is used to
accelerate towards Index.1.Vel.
3.
Acts the same as the Compound with User Ramps because Index.0.Accel entered by user is aggressive enough
to reach Index.0.Vel of 500 RPM. If Index.0.Accel entered by the user was not aggressive enough to reach 500
RPM within 5 Revs, necessary ramp would be calculated.
4.
Acceleration ramp is automatically calculated to reach Index.1.Vel within Index.1.Dist of 5 Revs. If user had
entered a ramp aggressive enough to reach Index.1.Vel within 5 Revs, no automatic ramp calculation would be
required, and the user entered acceleration rate would be followed.
Figure 48:
Ramps Examples of a Slow Index to a Faster Index
3.11.2 Ramps Group
Stop Deceleration
The value you enter here defines the deceleration rate which is used when the Stop destination is activated. The default is 100
RPM/second.
The Stop destination is found in the Ramps Group in the Assignments view.
Feedhold Decel/Accel
When the Feedhold destination is activated, the motor will decelerate to a stop in the time specified by the
FeedholdDecelTime parameter. When feedhold is cleared, the motor will accelerate back to speed in the same specified
period of time.
Feedhold is a means to halt the motor within a velocity profile and then return to the profile later at the exact same place in the
profile. Feedhold does not ramp and does not decelerate in terms of velocity. Instead, it stops by decelerating time. For
example, if the motor is running at 50 revs/second and feedhold is activated with 2 seconds specified in the
FeedholdDecelTime parameter, then the motor will actually slow and stop in 2 seconds as measured time (on a time/velocity
profile) goes from 100% to 0%.
Travel Limit Decel
The value entered here is the deceleration ramp that is used when a software or hardware travel limit is hit.
Epsilon EP-P Drive Reference Manual
Revision A3
47
www.emersonct.com
3.12
Torque View
The Torque View allows you to edit torque level and limit parameters as well as view real-time torque values when online.
By selecting Torque in the Hierarchy Tree, the Torque View will appear on the right (see Figure 49). The right part of the window is divided into
groups. An explanation of the groups and their functions is provided below.
Figure 49:
Torque View
3.12.1 Settings Group
Torque Level
This parameter sets the activation point for the Torque Level Active source. If set to 100%, the Torque Level Active source will activate any time
the Torque Command reaches or exceeds 100% continuous. This parameter is specified in Torque User Units.
3.12.2 Limits Group
Torque Limit
This parameter sets the value to which the Torque Command will be limited when the Torque Limit Enable destination is active. To make the
Torque Limit always active, assign the Torque Limit Enable destination to the Initially Active source on the Assignments view.
3.12.3 Peak Torque
Displays the Peak Torque for the motor drive combination setup in the Setup View.
3.12.4 Online Tab
If online, this view will show the Torque Command, Limited Torque, Foldback RMS, and Shunt Power RMS.
3.13
Distance Recovery View
When initiating gear or cam using the Master Axis to provide synchronization, distance is lost as we must follow the acceleration limitations.
This distance can be recovered when at velocity by adding a distance recovery index on top of the gear operation or cam. This view defines
the limits of that recovery index.
Gearing uses distance recovery after accelerating from zero to a locked state. Camming uses distance recovery after using the Resume
48
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
process.
Figure 50:
Distance Recovery View
3.13.1 Gear and Camming Distance Recovery Group
Enable Distance Recovery Check Box
The Enable Distance Recovery Check box (DistanceRecovery.DistanceRecoveryEnable) is clear (disabled) by default. Select
the check box to enable the additive distance recovery index feature.
Velocity
This parameter (DistanceRecovery. Vel) is the velocity limit of the distance recovery index in user units.
Acceleration
Acceleration (DistanceRecovery. Accel) is acceleration rate for the distance recovery index in user units.
Deceleration
This (DistanceRecovery. Decel) is the deceleration rate for the distance recovery index in user units.
3.14
Tuning View
The Tuning View allows you to modify tuning parameters based on specific application information.
By selecting Tuning in the Hierarchy Tree, the Tuning View will appear on the right (see Figure 51). The right part of the
window is divided into groups. An explanation of the groups and their functions is provided below.
For help on calculating tuning parameters and more in-depth tuning information, turn to Tuning Procedures on page 187.
Figure 51:
Tuning View
3.14.1 Load Group
Inertia Ratio
Inertia Ratio specifies the load to motor inertia ratio and has a range of 0.0 to 50.0. If the exact inertia is unknown, a
Epsilon EP-P Drive Reference Manual
Revision A3
49
www.emersonct.com
conservative approximate value should be used. If you enter an inertia value higher than the actual inertia, the resultant motor response will
tend to be more oscillatory.
Friction
This parameter is characterized in terms of the rate of friction increase per 100 motor RPM. If estimated, always use a conservative (less than
or equal to actual) estimate. If the friction is completely unknown, a value of zero should be used. A typical value used here is less than one
percent.
3.14.2 Low Pass Filter Group
The Low Pass Filter will reduce machine resonance due to mechanical coupling and other flexible drive/load components by filtering the
command generated by the velocity loop.
Low Pass Filter Enable Check Box
When this check box is selected it enables a Low Pass Filter to be applied to the output of the velocity command before the torque
compensator.
Low Pass Filter Frequency
This parameter defines the Low Pass Filter cut-off frequency. Signals exceeding this frequency will be filtered at a rate of 40 dB per decade.
The default value is 600 Hz.
3.14.3 Tuning Group
Response
The Response adjusts the velocity loop bandwidth with a range of 1 to 500 Hz. In general, it affects how quickly the drive will respond to
commands, load disturbances and velocity corrections. A good value to start with (the default) is 50 Hz. The maximum value recommended is
80 Hz.
Enable Feedforwards Check Box
When feedforwards are enabled, the accuracy of the Inertia and Friction parameters is very important. If the Inertia parameter is larger than the
actual inertia, the result could be a significant overshoot during ramping. If the Inertia parameter is smaller than the actual inertia, following
error during ramping will be reduced but not eliminated. If the Friction parameter is greater than the actual friction, it may result in velocity error
or instability. If the Friction parameter is less than the actual friction, velocity error will be reduced but not eliminated.
3.14.4 Position Error Integral Group
Time Constant Check Box
When this check box is selected it enables the Time Constant parameter.
Time Constant
Position Error Integral is a control term, which can be used to compensate for the continuous torque required to hold a vertical load against
gravity. It is also useful in low speed applications, which have high friction.
The user configures this control term using the “Position Error Integral Time Constant” parameter. This parameter determines how quickly the
drive will correct for in-position following error. The time constant is in milliseconds and defines how long it will take to decrease the following
error to 37 percent of the original value. In certain circumstances the value actually used by the drive will be greater than the value specified
here.
Min Time Constant = 1000/Response
For example, with “Response” set to 50, the minimum time constant value is 1000/50 = 20 msec.
3.15
Shunt View
The Shunt view is used to configure the external shunt for the EP204, EP206, EP209 and EP216 drives.
Figure 52:
Shunt View
50
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.15.1 External Shunt Resistor Group
Max Energy
The total energy that can be absorbed by the resistor when its initial temperature is ambient temperature.
Average Power
The average power rating of the shunt resistor.
Resistance
The resistance value of the shunt resistor.
3.15.2 Shunt Control Group
The parameters in this group are read-only and only available when online with the drive.
Shunt Power RMS
This parameter models the thermal heating and cooling of the drive internal shunt. This parameter indicates the percent of
shunt capacity utilization and is based on the Heat Sink RMS value. When this value reaches 100 percent the drive will
generate a RMS Shunt Power Fault.
Bus Voltage
Displays the actual measured voltage of the DC power bus.
Epsilon EP-P Drive Reference Manual
Revision A3
51
www.emersonct.com
3.16
Faults View
The Faults View displays any active faults when online. Figure 53 below shows the Faults view offline.
Figure 53:
Faults View - Offline
When online and a fault is detected, the Faults window opens, showing the fault condition and allows the fault to be reset or ignored. Pressing
Reset attempts to reset the fault if the cause of the fault has been removed. Pressing Ignore just closes the faults window.
Figure 54:
Faults Window
When online, the Active Faults window, Reset button and Power Up group window become active. There will also be three tabs that appear,
Fault Log, Fault Counts, and Drive Fault Log.
52
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 55:
Faults View Online - Faults Log Tab
3.16.1 Active Faults Group
The Active Faults group contains the Active Faults window.
Active Faults Window
This window displays any active faults in the system. Those faults which do not require a reboot can be cleared by clicking on
the Reset button. For more detailed fault information, refer to Diagnostics and Troubleshooting on page 193.
3.16.2 Power Up Group
These parameters will be active when online with the drive.
Drive Power Up Count
This parameter shows the number of times the drive has been powered up since the last reset by the factory.
Drive Power Up Time
This parameter shows the time, in hours, since the drive was last powered up.
Drive Total Power Up
This parameter shows the total time that the drive has been powered up since reset by the factory.
3.16.3 Fault Log Tab
The Fault Log tab is visible when online and consists of a list of the ten most recent faults detected by the drive. These are
saved in non-volatile memory to be preserved during power down.
Faults are listed in reverse order of occurrence-the most recent fault is listed first, and older faults are pushed off the list.
Fault Code
The fault code has the same description of the fault that is or was reported in the Active Faults window.
Fault Sub Code
The fault subcode applies to only a few faults and provides some additional information about the fault when available. When
there is no additional information for the fault, OK is displayed.
Power Up (counts)
This is the drive’s power up counter at the time of the fault.
Time (hours.minutes)
This is the drive’s total power up time in tenths of an hour at the time of the fault.
Epsilon EP-P Drive Reference Manual
Revision A3
53
www.emersonct.com
3.16.4 Fault Counts Tab
Figure 56:
Fault View - Fault Counts Tab
The Fault Counts tab is visible when online and consists of a list of all supported faults and the number of times each fault has been detected.
Most of the counts start at zero following a power up or a configuration download.
A few faults are saved in non-volatile memory so that the total number of times they have occurred can be easily viewed. These faults tend to
have hardware significance.
Fault Code
This is the faults parameter name.
Fault Counts
This is the number of times that the fault has occurred.
Clear Non-Critical Fault Counts Button
Pressing this control button will zero the Fault Counts of all non-critical faults(i.e.software travel limit). Critical faults are faults that are used by
the factory to verify warranty claim and aid in troubleshooting the drive.
54
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.16.5 Drive Fault Log Tab
Figure 57:
Faults View - Drive Fault Log Tab
The Drive Fault Log tab is visible when online and consists of a list of the ten most recent faults detected by the drive. These
are saved in the drive’s non-volatile memory to be preserved during power cycles. Faults are listed in reverse order of
occurrence so that the most recent is listed first.
Fault Code
The fault code has the same description of the fault that is or was reported in the Active Faults window.
Power Up (Counts)
This is the Drive Power Up Counts when the fault was detected.
Time (Hours.Minutes)
This is the Drive Power Up Time when the fault was detected.
3.17
Setup NVM View
At power-down, parameters can be saved to Non-Volatile Memory (NVM). See the “How Communications Work” section of the
“Operational Overview” chapter for more details. In PowerTools Pro, you can customize which parameters will be saved in
non-volatile memory.
Figure 58:
Setup NVM View
Epsilon EP-P Drive Reference Manual
Revision A3
55
www.emersonct.com
3.18
Devices / Vars Group
3.19
PLS View
The PLS View allows users to define Programmable Limit Switches (PLS) for advanced machine operation. By selecting PLS in the Hierarchy
Tree, the PLS View will appear on the right (see Figure 59).
Figure 59:
PLS View
A PLS can be used to turn on or off a bit based on feedback position, commanded position, or master feedback position. Eight global PLS’s are
available for a single application. To operate a PLS, first it must be enabled (see the PLS enable destinations in the assignments view) and
then the Absolute Position Valid source must be active. Each PLS has its own OnPoint and Off Point, as well as a Rollover Point.
The terms OnPoint and Off Point assume movement in the positive direction. Those labels should be reversed if traveling in the negative
direction.
Number of PLS Points
This parameter determines the number of PLS Points that will be used. Count always begins with 0, so 5 points will be 0 to 4. Up to eight PLS
points may be used simultaneously.
Source
The source list box is used to select the source for the individual PLS and reference its OnPosn and OffPosn to determine the PLS.#.Status
parameter. The source of a PLS (PLS.#.Source) can be assigned to the motor axis (MotorPosnFeedback, MotorPosnCommand), a master
synchronization signal (MasterPosnFeedback) or the real time clock from the drive’s built-in microprocessor (FreeRunTime). The term motor
axis refers to the motor being controlled by the drive.
ON Point
PLS.#.Status will be active when the selected source position is between the PLS.#.OnPosn and the PLS.#.OffPosn.
Examples:
Example 1: Assume that the PLS.#.Source is MotorPosnFeedback and PLS.#.Direction is set to "Both". When traveling in the positive direction
and the feedback position executes the OnPosn, the PLS.#.Status will activate. As the motor continues in the same direction, the PLS.#.Status
will deactivate when feedback position reaches or exceeds the OffPosn. If motor travel changes to the negative direction, the PLS.#.Status will
activate when the feedback position reaches the OffPosn, and will deactivate when it continues past the OnPosn. All on/off positions are
defined in user units.
Example 2: Assume that the PLS.#.Source is MotorPosnFeedback and PLS.#.Direction is set to "Plus". When traveling in the positive direction
and the feedback position executes the OnPosn, the PLS.#.Status will activate. As the motor continues in the positive direction, the
PLS.#.Status will deactivate when feedback position reaches or exceeds the OffPosn. If motor travel changes to the negative direction after
passing the OffPosn, the PLS.#.Status will remain deactivate. If the motor travel changes to the negative direction before passing the OffPosn
the PLS.#.Status will deactivate. All on/off positions are defined by the selected PLS.#.Source, either user units or seconds.
PLS.#.Status will be active if:PLS.#.OnPosn < Feedback Position  PLS.#.OffPosn
OFF Point
PLS.#.Status will be active when the selected source position is between the PLS.#.OnPosn and the PLS.#.OffPosn. Assume that the
PLS.#.Direction is set to "Both". When traveling in the positive direction and the feedback position reaches the OnPosn, the PLS.#.Status will
56
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
activate. As the motor continues in the same direction, the PLS.#.Status will deactivate when feedback position reaches or
exceeds the OffPosn. If motor travel changes to the negative direction, the PLS.#.Status will activate when feedback position
reaches the OffPosn, and will deactivate when it continues past the OnPosn.
PLS.#.Status will be active if:PLS.#.OnPosn < Feedback Position  PLS.#.OffPosn
If using negative values for your OnPosn and OffPosn, the most negative value should go in the OnPosn parameter, and the
least negative value should go in the OffPosn.
If the PLS has a rollover point, and the OnPosn is greater than the OffPosn, the PLS will be active whenever the position
feedback is not between the On and Off positions, and in-active whenever the position feedback is between the two positions.
However, the PLS.#.Status will not turn on until it reaches the OnPosn the first time.All on/off positions are defined in user
units.
Direction
This parameter (PLS.#.Direction) specifies the direction of motion that a particular PLS output will function. If set to Both, the
PLS will activate regardless of whether the motor (or master motor) is moving in the positive or negative direction. If set to
Plus, the PLS will activate only when the motor is moving in the positive direction. If set to Minus, the PLS will activate only
when the motor is moving in the negative direction.
Example:
A flying cutoff or flying shear application may use this feature to activate the PLS to fire the knife only when the axis is
moving in the positive direction.
If accessing this parameter from a network, the following table displays the value for this 16-bit integer.
0
N/A
1
Both
2
Plus
3
Minus
Rotary Enable
This parameter (PLS.#.RotaryRolloverEnable) is used to enable the RotaryRolloverPosn for this PLS.
Rollover Point
This parameter (PLS.#.RotaryRolloverPosn) is the absolute position of the first repeat position for this PLS. When enabled it
causes the PLS to repeat every time this distance is passed. The repeating range begins at an absolute position of zero and
ends at the RotaryRolloverPosn.
For example, in a rotary application a PLS could be setup with an OnPosn of 90 degrees and an OffPosn of 100 degrees. If
the RotaryRolloverPosn is set to 360 degrees the PLS would come on at 90, go off at 100, go on at 450 (360+90), go off at 460
(360+100), go on at 810 (2*360+90), go off at 820 (2*360+100), and continue repeating every 360 degrees forever.
Example: if the source of the PLS is FreeRunTime, this parameter is the time of the first repeat for this PLS. When enabled it
causes the PLS to repeat every time this time is passed. The repeating range begins at the beginning of the trajectory update
rate and ends at the RotaryRolloverPosn.
3.20
Capture View
Many applications require the ability to accurately capture a position at an exact moment in time so that the motion profile can
be repeatably time accurate. The Epsilon EP-P drive allows for this by using the Capture component. The Capture component
is fully controlled by the user through the Assignments View or through the Programs View. When the capture is activated, the
following parameters are captured and stored: Time, Command Position, Feedback Position, and Master Feedback Position.
Epsilon EP-P Drive Reference Manual
Revision A3
57
www.emersonct.com
Figure 60:
Capture View
The user must determine which signals are used to enable, activate, and then reset the Capture component. A CaptureTriggered destination
is then available to indicate to the user that data has been captured and is available for use.
CaptureEnable
CaptureActivate
Time
CaptureTriggered
Command Position
CaptureReset
Feedback Position
Master Position
Captured Data
Figure 61:
Capture Component
A detailed description of all the Capture parameters is below.
CaptureEnable
The CaptureEnable is used to enable or “arm” the capture component. If the CaptureEnable is not active, then the CaptureActivate has no
effect, and the CaptureTriggered remains inactive. Once the CaptureEnable is activated, the Capture component is ready and waiting for a
CaptureActivate signal to capture data. CaptureEnable is a read-only destination on the Assignments view, and is accessible through a user
program.
CaptureActivate
If the Capture component is enabled and has been reset (CaptureTriggered is inactive), then the rising edge of CaptureActivate will capture
the four data parameters and cause CaptureTriggered to be activated. If the Capture component is not enabled, or has not been reset, the
CaptureActivate will be ignored.
CaptureReset
The CaptureReset is used to reset or re-arm the capture component after it has been activated. If the capture has been activated, the
CaptureTriggered destination will be active. The capture component cannot capture data again until it has been reset. The capture
component will automatically reset itself if the CaptureEnable signal is removed.
CaptureTriggered
The CaptureTriggered signal is read-only and indicates that the Capture component was activated and that data has been captured.
CaptureTriggered will activate on the leading edge of CaptureActivate if the Capture component is enabled and reset. Capture Triggered will
remain active until CaptureReset is activated.
Name
You can assign a descriptive name to each capture, making the setup easier to follow. The length of the text string is limited by the column
58
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
width with a maximum of 12 characters. Simply double click on the Name field of any capture’s line to assign a name to it.
Capture Number
This parameter defines the number of Capture objects available. Maximum is eight.
Captured Data
The data that is acquired by the position capture is available to be used as variables in a program. The four parameters can
be accessed as follows:
Capture.#.CapturedTime
The time, in microseconds, from a free-running 32-bit binary counter at which CaptureTriggered activated.
Capture.#.CapturedPositionCommand
The command position, in user units, at the time when CaptureTriggered activated.
Capture.#.CapturedPositionFeedback
The feedback position, in user units, at the time when CaptureTriggered activated.
Capture.#.CapturedMasterPostion
The master axis feedback position, in master axis distance units, at the time when CaptureTriggered activated.
The captured data remains in these parameters until the capture component is reset and CaptureActivate is activated. When
the capture component is reset and CaptureActivate is activated, the data related to the previous capture will be over-written
by the most recent capture data.
Figure 62:
Capture Timing Diagram
Figure 62 is a timing diagram that shows how the different capture related sources and destinations function. The three
numbers located on the diagram are associated to the following three notes respectively:
1.
The CaptureActivate has no effect when the CaptureTriggered is active. CaptureActivate is ignored until the
capture component has been reset.
2.
When CaptureEnable is deactivated, CaptureTriggered is deactivated, and the capture component is
automatically reset. The captured data is retained until the capture component is re-enabled and
CaptureActivate is activated.
3.
CaptureActivate has no effect while the capture component is not enabled.
Assignments that Automatically Use Position Capture
Certain assignments (Sources or Destinations) automatically generate position capture data internally without using the
capture component. This data is used by the drive, but is not directly available to the user like the capture component data.
Following is a list of assignments that automatically generate or use captured data.
Sources that generate capture data:
Drive Inputs 1-8 – The Epsilon EP-P drive Inputs 1-8 are constantly monitored by the processor, and when activated will
automatically capture related data. The processor controls all resetting requirements. The capture only occurs on the rising
edge of an input. When the input is activated, the captured data will automatically be passed to the destination that it is
assigned to. The destination may then use the captured data to accurately initiate motion (if it is a motion-related destination).
Motor Encoder Marker – The rising edge of the motor encoder marker pulse will automatically capture data. This will allow
the user to accurately initiate motion on the rising edge of the motor encoder marker pulse. The falling edge of the marker
pulse does not capture data.
Master Encoder Marker – The rising edge of the master encoder marker pulse will automatically capture data. This allows
the user to accurately initiate motion on the rising edge of the master encoder marker pulse. The falling edge of the marker
pulse does not capture data.
Index/Jog Command Complete – Activation of the command complete signal at the end of indexes and jogs will
automatically capture data. A subsequent index, jog, or dwell can then use the captured data to start itself extremely accurate
at the end of the previous motion.
Index/Jog At Velocity – Activation of the command complete signal at the end of indexes and jogs will automatically capture
Epsilon EP-P Drive Reference Manual
Revision A3
59
www.emersonct.com
data. A subsequent index, jog, or dwell can then use the captured data to start itself extremely accurately at the end of the previous motion.
PLS Status – A rising or a falling edge of a Global PLS will automatically capture data for use in initiating motion. In order to accurately initiate
motion from a Global PLS, an assignment can be made from PLS.#.Status to the initiate destination.
Destinations that use captured data:
Index/Jog Initiates – When one of the sources listed above is assigned to an Index or Jog Initiate, the captured information is automatically
applied to the index starting point. This offers extremely high accuracy for initiation of motion, which is beneficial especially in synchronized
applications.
Index.#.SensorTrigger – The sensor trigger destination used in registration indexes can use captured data to accurately calculate the ending
position of the index based on the Registration Offset parameter. The Offset distance is added to the captured position to get the accurate
stopping position for the registration index.
3.21
Queues View
Many applications require the ability to store data in a temporary memory location as the data comes in. The user then has access to the data
for use in a program or other operation. The Epsilon EP-P drive use an object called a queue to store data in this way. The queue is a first-infirst-out (FIFO) type memory device. In other words, the first piece of data put into the queue is the first piece of data to come out of the queue.
The user has complete control over what data is stored in the queue, and when to put data into the queue, as well as when to remove it from
the queue.
Figure 63:
Queues View
Queue Object
Exit
Clear
Compare
Enable
Data[ ]
Size
Offset
Full Level
Comparitor Select
Name
Empty
Full
Overflow
Data In
Queue Data = X
Figure 64:
Data Out
Y = Queue Data
Queue Object and Components Diagram
A detailed explanation of each of the queue components is as follows:
Queue Data
The queue data is loaded into the queue by statements in the user program. Two types of data are most often used with the queue: Position
Feedback, and Master Position Feedback.
60
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Queue Size
This is the maximum number of elements that can be stored in the queue. If more pieces of data than this number are in the
queue at a time, then a Queue Overflow source will activate.
Queue Offset
The Queue Offset is the value that is added to the Queue Data and then compared to the selected source to determine when
the Queue Exit event activates. For instance, if the source in selected source is set to Feedback Position, and the Queue
Offset is set to 10, and the user puts the value 5 into the queue, the Queue Exit source will activate when the Feedback
Position is greater than or equal to 5 + 10 or 15.
Full Level
The amount of data in the queue is constantly monitored and the Queue Full source will activate when the number of pieces of
data in the queue exceeds the Full Level parameter. This is only a flag and does not indicate a fault of any kind.
Source
The Source determines which parameter the sum of the Queue Data and Queue Offset are compared to in order to activate
the Queue Exit function. If set to FeedBackPosn (Position Feedback), the sum of the data and offset are compared to the
Position Feedback parameter. If set to MasterPosn (Master Position), then the sum is compared to the Master Feedback
Position parameter, and if set to CommandPosn (Command Position), then the sum is compared to the Motor Commanded
Position.
Name
You can assign a descriptive name to each queue, making the setup easier to follow. The length of the text string is limited by
the column width with a maximum of 12 characters. Simply double click on the Name field of any queue’s line to assign a
name to it.
Number of Queue Units
This selects the number of Queues available. Maximum of eight.
3.21.1 Queue Sources and Destinations
Sources
Queue Exit
This source activates when the Comparitor Select parameter is greater to or equal to the sum of the data entered into the
queue, and the queue offset.
Queue Empty
This source is active if no data is stored in the queue. It will become inactive when the first piece of data is loaded into the
queue and remain inactive until all data has been removed from the queue.
Queue Full
The Queue Full source will activate if the number of pieces of data in the queue equals or exceeds the Full Level parameter.
The source will deactivate when the number of pieces of data in the queue is less than the Full Level.
Queue Overflow
This source activates when there is no more room in the queue to store data. The maximum number of pieces of data is
determined by the Queue Size parameter.
Destinations
Queue Clear
This destination automatically clears all of the data out of the queue. The cleared data is not saved and there is no way to
recover the cleared data. This is typically activated on power-up of the system to make sure no old data remains in the queue.
Queue Compare Enable
The Compare Enable causes the comparitor internal to the queue to function. If the Compare Enable is inactive, then the
Queue Exit source will never activate. If activated, then the Queue Exit source will activate when the Queue Data plus the
Queue Offset is greater than or equal to the Comparitor Select parameter.
To fully understand the operation of the queue, the following diagram has a more detailed view of the Queue object.
Epsilon EP-P Drive Reference Manual
Revision A3
61
www.emersonct.com
QueueEmpty
IF (# of Queue
Objects = 0)
QueueClear
Set # of Queue Objects = 0
and clear data in queue
IF (# of Queue
Objects = or > Full Level)
Data In
QueueFull
Source Select:
Full
Level
MasterPosn
FeedbackPosn
CommandPosn
Queue
Size
Data Out
QueueExit
Comparitor
Comparitor
Exit Position
Queue Offset
CompareEnable
Sum
IF (# of Queue
Objects = Queue Size)
Figure 65:
3.22
QueueOverflow
Detailed Queue Diagram
Timers View
The Timer View is used to configure necessary parameters to use Timer objects within an application. Timers are used in many different types
of applications to accurately control the timing of a given machine event with respect to one or more previous events. For example: When a
digital input turns on, we want to start a program exactly 500 msec later. Or, when an index is complete, we want to hold an output on for
exactly 2.000 seconds.
There are several different types of Timers available to the user based on the task they are trying to achieve.
Figure 66:
Timers View
Number of Timers
This parameter determines the number of Timer objects that are available in the configuration. Use the spin control to change the number of
Timers from 1 to 8. The Timers are numbered with a base number of 0. This means that if there are 5 Timers available, they will be numbered
0 through 4.
62
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The number of Timers in the configuration can only be modified while offline.
Timer Name
The user can assign a descriptive name to each Timer, making the configuration easier to follow. The length of the text string
is limited by the column width, with a maximum of 12 characters. Spaces are not allowed in the name, but underscores are.
Simply click on the name field to modify the individual Timer Name.
Timer Type
There are several types of Timers available that help you to achieve different tasks. Use the combobox in the Type column to
change the individual Timer Type. The Enable is not shown in the diagrams below. Assume in all cases the TimerEnable is
ON. Select from these Types:
Edge ON Timer
With this type of timer, when the input of the timer activates, the internal clock begins to count. When the Preset time is
reached, the Output of the timer turns ON.
In the case of the Edge type timer, once the rising-edge occurs on the Input, it doesn't matter what happens to the state of the
Input after that. The Output will always turn ON when the Preset Time is reached (unless the Reset activates before the Preset
Time is reached). The Timer Output will remain ON until the Reset is activated or the TimerEnable is deactivated.
Figure 67:
Edge On Timer - Timing Diagram
Level ON Timer
With this type of timer, when the Input of the timer activates, the internal clock begins to count. When the Preset time is
reached, the output of the timer turns ON. If the Input of the timer turns OFF before the output turns ON, then the internal clock
stops counting and the output will not turn ON. The whole sequence begins again the next time the Input turns ON. This
means that the Input must remain ON for the duration of the Preset Time in order for the Output to turn ON.
The Level On Timer does not use the Reset, but rather, the Output will remain ON as long as the Input remains ON. When the
Input turns OFF, the Output will automatically turn OFF.
Figure 68:
Level On Timer - Timing Diagram
Edge OFF Timer
With this type of timer, when the Input of the timer activates, the Output turns ON automatically. When the Input turns OFF, the
internal clock begins to count. Once the Preset time is reached, the Output of the timer turns OFF. As soon as the Input turns
OFF, it does not matter what happens to the state of the Input, the Output will turn OFF when the Preset time is reached. The
Epsilon EP-P Drive Reference Manual
Revision A3
63
www.emersonct.com
Output will remain OFF until the Reset is activated.
Note that if the Input is already ON when the Reset activates, the Output will not automatically activate at that point. The timer controller must
see a rising edge on the Input to activate the Output.
Figure 69:
Edge Off Timer - Timing Diagram
Level OFF Timer
With this type of timer, when the Input of the timer activates, the Output turns ON automatically. When the Input turns OFF, the internal clock
begins to count. Once the Preset time is reached, the Output of the timer turns OFF. If the Input turns ON again before the Preset time is
reached, the clock resets to zero and waits again for the Input to turn OFF before starting the count.
The Level Off Timer does not use the Reset, but rather, the Output will remain OFF as long as the Input remains OFF.
Figure 70:
Level Off Timer - Timing Diagram
Cumulative ON Timer
This type of timer works exactly like the Level ON Timer, except that if the Input turns OFF before the Preset time is reached, the elapsed time
is not reset. The total time that the Input is ON is added together such that when the total time of the Input being ON reaches the Preset time,
64
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
the Output turns ON. Figure 6 below shows an example timing diagram of the Cumulative On Timer.
Figure 71:
Cumulative ON Timer, No Reset - Timing Diagram
Additionally, a Reset signal can be used to clear the cumulative timer and restart it at zero. The figure below shows an
example of this.
Figure 72:
Cumulative ON Timer with Reset - Timing Diagram
Cumulative OFF Timer
This type of timer works exactly like the Level OFF Timer, except that with this type of timer, when the Input of the timer
activates, the output turns ON. When the Input turns off, the internal clock begins to count. Once the Preset time is reached,
the Output of the timer turns OFF. If the Input turns ON again before the Preset time is reached, the clock resets to zero and
Epsilon EP-P Drive Reference Manual
Revision A3
65
www.emersonct.com
waits again for the Input to turn OFF before resuming the count again.
Figure 73:
Cumulative OFF Timer - Timing Diagram
Additionally, a Reset signal can be used to clear the cumulative timer and restart it at zero. The figure below shows an example of this.
Figure 74:
Cumulative OFF Timer with Reset - Timing Diagram
Watchdog Timer
With this type of timer, when the Enable of the timer activates, the internal clock begins to count. If a rising edge is seen on the Input before the
Preset Time is reached, the Elapsed Time is set to zero and the internal clock again starts counting immediately. The duration that the Input
remains on does not have any effect on the Output. If at any point, the Elapsed Timer reaches Preset time, the Output turns ON. The Output
will remain ON until the Timer Reset is activated. If a rising edge is seen on the Input while the Output is ON, it will be ignored and the Elapsed
Time will NOT be reset.
66
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 75:
Watchdog Timer - Timing Diagram
One Shot
With this type of timer, when the Input activates, the internal clock begins to count. Once the Preset time is reached, the
Output of the timer turns ON. If the Input of the timer turns OFF before the Output turns ON, then the internal clock keeps
counting and the Output will turn on when Preset time is reached. If the Output is active and a rising edge of the Input timer is
received the Output will be reset. The Output will activate once the Preset time has past.
In the case of the One Shot type timer, once the rising-edge occurs on the Input, it does not matter what happens to the state
of the Input after that during the Preset time. When past the Preset time and the Output is still active and a rising-edge occurs
on the Input the timer will reset. The Output deactivates and will not become active until the Preset time has past.
Input
Preset
Preset
Preset
Output
Active
Figure 76:
One Shot Timer - Timing Diagram
Timer Timebase
This parameter is used to select the desired Timebase for each timer object. If you want to control the Timer using actual time
(seconds, or milliseconds, or microseconds) then the Timebase should be set to Realtime. Realtime is the default setting for
the Timebase of each Timer object. When using Realtime, the Preset value of the Timer is entered in units of seconds. For
example, after a program has run, you wish to hold an output active for ten seconds. This is an example that uses Realtime.
However, if you wanted to hold that same output active for ten revolutions of the Master Encoder instead of ten seconds, you
set the Timebase to Synchronized. This means that you are using the master encoder position to control the duration of the
Timer rather than actual Time. When the Timebase of the Timer is set to Synchronized, the Preset is entered in units of Master
Epsilon EP-P Drive Reference Manual
Revision A3
67
www.emersonct.com
Distance rather than units of Time.
Use the combo box in the Timebase column to change the individual Timer Timebase settings.
Timer Preset
This parameter is used to control the actual duration of the timer delay.
If the Timebase is set to Realtime, the user specifies the Preset value in units of seconds with resolution of 1 microsecond (0.000001 seconds).
If the Timebase is set to Synchronized, the Preset value is set in units of Master Distance and the resolution is dependant upon the Master
Distance Units Decimal Places configured on the master Units view.
Once a timer has begun timing, if the Preset is modified, it is ignored until the next time the timer starts.
The Preset value must always be positive and can range from 0 to 2147483647 with the decimal place removed (example: 0.000000 to
2147.483647 with six decimal places).
Timer "Elapsed Time"
This is a read only parameter available on the Online tab that acts as feedback to the user to indicate how much of the Preset time has expired.
This value starts at zero and counts up to the Preset value.
This parameter has the same resolution as the Preset parameter.
If a Timer is Reset or Enable deactivates, this value is zeroed out automatically. Once the Preset time is reached, the Elapsed Time will remain
at its full preset value until the Timer is Reset, the Enable deactivates, or the Output deactivates.
3.22.1 Timer Signals/Events
The Timer objects has several inputs and outputs that are available on the Assignments view, or within a user program. A block diagram of the
Timer object is seen in Figure 77 below.
Input Events
TimerEnable
TimerInput
Output Events
Timer.#
TimerActive
Preset
Type
TimerReset
Figure 77:
Timebase
TimerOutput
Elapsed Time
Timer Object Block Diagram
Input Events / Destinations
The following signals are available in user programs and as Destinations on the Assignments view.
Timer.#.TimerEnable
The Timer Enable event is level sensitive (not edge only) and is used to enable the Timer object. If a timer is not Enabled, the Output will never
activate regardless of the state of the Input.
When the TimerEnable is deactivated, all output events associated with that Timer object will also deactivate and Elapsed Time will be set to
zero.
All timer types use the Enable even though it is not shown in the individual timing diagrams. See examples of how TimerEnable affects timer
functionality in Figure 78 and Figure 79.
68
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 78:
Timer Enable with Edge ON Timer
Figure 79:
Time Enable with Level ON Timer
Timer.#.TimerInput
The Timer Input event is level sensitive (not edge only) and is used to define when the Timer starts counting against the Preset
(along with the Timer Type). See the various timing diagrams in Figure 67 through Figure 76 to see how the Timer Input affects
the Timer Output.
Timer.#.TimerReset
The Timer Reset event is used to reset the ElapsedTime to zero and deactivate the TimerOutput and TimerActive. Level On
and Level Off timer types do not utilize the reset, as they reset automatically based on the state of the Input.
The Reset is a self-clearing function meaning that the reset occurs on the rising edge of the Reset input, and internally the
reset is set off. Therefore a timer can immediately begin counting again even if the user holds the Reset input ON. Additionally,
when resetting a timer in user program, the user must only set the Reset ON, and the controller will automatically set it off.
There is no reason for the user to force the Reset OFF within the program.
Output Events / Destinations
The following signals are available in user programs and as Sources on the Assignments view.
Timer.#.TimerOutput
The Timer Output state is controlled by the Timer Input, the Timer Type, and the other configuration settings of the Timer
object. See the various timing diagrams in Figures 2 through 10 to see how Timer Output functions.
The Timer Output can be assigned to multiple Destinations on the Assignments view just as any other Output Event.
Timer.#.TimerActive
The TimerActive event is used as an indicator that the Timer is actively counting (i.e. In the case of an OFF Timer, the Active
event would not activate until the Input turns OFF.).
In the case of Cumulative timers, the Active does not remain on even though the Elapsed Time may be non-zero, if the timer is
Epsilon EP-P Drive Reference Manual
Revision A3
69
www.emersonct.com
not currently counting.
When a timer reaches the user defined Preset time, the Output activates, and the Active event turns OFF.
See the timing diagrams for each of the Timer Types for examples of how TimerActive behaves.
3.22.2 Using Timers within Programs
Timers can be used within user programs without the need for assignments. Following are some examples of using Timer functions within a
program.
To start a Timer in a program, you must do the following:
Timer.#.Input = ON
The user must also turn the Input off as necessary to control the timer:
Timer.#.Input = OFF
To use the output of a Timer within a program:
Wait For Timer.#.Output = ON (or = OFF)
To change the value of a Timer Preset in a program:
Timer.#.Preset = 12.345 'Seconds
To check if a timer is running:
If (Timer.#.Active = ON) Then
Some code
.
.
Endif
To wait for a Timer to start running:
Wait For Timer.#.Active = ON
Other examples:
If((Timer.#.Active=ON) AND (Timer.#.ElapsedTimer<0.500)) Then
Some code
.
.
Endif
If ((Timer.#.Output = ON) AND (Index.#.CommandComplete)) Then
Timer.#.Reset = ON 'Self-resetting - No need to turn OFF
Endif
3.23
Variables View
Variables allow the user to store data related to their system into a parameter, which the user can name. The user must define each user
variable by giving it a name, resolution (number of decimal places), and initial value. All variables are signed 32-bit parameters. Setup for the
Variables is done on the Variables view located under the Drive /Var group in the Hierarchy Tree. The Variables view is shown in Figure 80.
Figure 80:
Variables View
70
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The following parameters are part of the User Variable definition:
Name
This is a twelve-character string that allows the user to assign a descriptive name to the parameter. Spaces are not allowed in
the name of a user variable.
Decimal
This parameter (Var.Var#.Decimal) defines the number of digits (up to 6) to be used after the decimal point for the specific
variable. This is the maximum resolution that the parameter will have.
Initial Value
This is the initial value of the user variable that will be used on power up. If the user variable has been configured as a Save
to NVM parameter, then the value in NVM will overwrite the initial value on power up.
3.23.1 Adding and Deleting Variables
The default number of variables is ten. To add more user variables, click on the up arrow next to the “Number of User
Variables” box on the User Variables view. The maximum number of user variables is 500.
Only the last variable in the list can be deleted. To delete the last variable, simple click on the down arrow next to the “Number
of User Variables” box.
User variables are all of a Global type, meaning that they can be accessed from any program.
Online Tab (not shown)
While online with the Epsilon EP-P drive, an online tab will be shown next to the Setup tab. This online tab will show the
current online value of each of the user variables.
3.23.2 Using Variables in a Program
Once setup, user variables can be used inside a program in calculations, motion profile setup, or any other user-desired
function. To access user variables, click on the Drag in Variables button in the user program toolbar. User Variables is a
branch in the Select Variables From Tree dialog box.
3.24
Bits View
Bits act just like Variables except that they allow the user to store bit level parameters rather than 32-bit parameters. The user
may customize each Bit by giving it a Name and an Initial Value.
The Name for each bit may be up to 12 characters in length, and must start in an alpha character (non-numeric character).
Spaces are not available in the Name for a Bit, however the underscore character ("_") may be used.
The Initial Value for each user bit is configured using the check box for the specific bit. To make the Initial Value “On” or
“Active”, simply select the check box for that bit. The default value for each User Bit will be “Off” or “Inactive”.
User Bits are configured on the Bits view as shown in Figure 81.
Bits may be accessed on the User Program. Several examples of this are shown below.
Bit.Raise_Table = ON
Wait For Bit.Vacuum_ON = OFF
Wait For Bit.RunPart_A OR Bit.RunPart_B OR Bit.RunPart_C
If (Bit.RunPart_A = ON AND Bit.Vacuum_ON = OFF) Then
Call Program.1
Endif
Bits are turned on by setting them equal to ON, TRUE, YES, SET, or ENABLE (not case sensitive), and can be deactivated by
setting them equal to OFF, FALSE, NO, CLEAR, or DISABLE. Setting an individual bit equal to 1 or 0 in a user program will
cause a red dot error. The Boolean values listed above must be used.
Epsilon EP-P Drive Reference Manual
Revision A3
71
www.emersonct.com
Figure 81:
User Bits View
3.24.1 Adding and Deleting User Bits
Bits can be added or deleted in groups of 32-bits. Individual bits cannot be added or deleted. The default number of User Bits available is 32.
To add an additional 32 bits, simply click on the up arrow next to the “Number of Bit Registers” box at the top of the User Bits view (see Figure
81).
To decrease the number of User Bits by 32, click on the down arrow next to the “Number of Bit Registers” box. When decreasing the number of
User Bits, it is always the last 32 bits in the list that will be eliminated.
3.24.2 User 32-bit Bit Register and User Bit Masking
When using different communications protocols (i.e. DeviceNet, Profibus, Modbus), it is often desirable to access groups of User Bits in a
single parameter, rather than having to access them individually. In the Epsilon EP-P drive it is possible to access 32 User Bits in a single
parameter. This parameter is named BitRegister.#.Value. Because some of the 32 User Bits may be used by the program, and should not be
modified from the network communications, it is possible to “Mask Off” certain bits. Masking bits prevents them from being modified in the
program when the 32-bit parameter is written to.
When a User Bit Register (group of 32 User Bits) is written to, the value is then logic-AND’ed with the mask to determine the resulting state of
each of the 32 individual bits. If the individual bit value of the 32-bit mask is “1”, then the corresponding bit from the written 32-bit parameter is
passed through, and the resulting value stored in the specific bit will be the written bit value. If the bit value of the 32-bit mask is “0”, then that
particular bit is blocked (or masked), and the resulting bit value does not change, (Original Value AND NOT 32-Bit Mask) or (Value Written over
Network AND 32-Bit Mask). An example of this is shown in Figure 82.
72
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Original
Value
Bit #31
15
0
1 0 0 0 0 0 0 1 0 1 0 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0
Value written
over network
0 1 1 0 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 1 1 1 0 1 0 1 0 1 1 0
32-bit Mask
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Result stored
in each bit
1 1 0 0 0 0 0 0 0 1 0 1 0 0 0 0 1 1 0 1 0 1 1 1 0 1 0 1 0 1 0 0
Figure 82:
Writing to the User Bit Register
The Mask is only used when WRITING to the 32-bit parameter, BitRegister.#.Value. When reading the 32-bit value, all bits are
read regardless of the mask.
Epsilon EP Drive
Write
Network
Master
Read
AND
Mask
Value
Written data is AND’ed with the Mask
and then written into 32-bit Value.
Read data is read directly from the
32-bit Value and bypasses the Mask.
Figure 83:
User Bits Read/Write Process
3.24.3 Configuring the User Bit Mask Register
The User Bit Mask is a 32-bit parameter that can be configured through Power Tools Pro, in the User Program, or over the
communications network. The default value for the Mask register is 0xFFFFFFFF (HEX), or all bits ON. To change the Mask
value using PowerTools Pro, navigate to the Mask tab on the User Bits view, see Figure 84.
In the User Bits Mask view, each bit of the Mask can be set to 0 or 1 individually. ON (or 1) is indicated by a shaded square,
and OFF (or 0) is indicated by an empty square. Bit 31 is the most significant bit in the word, and bit 0 is the least significant
bit. If the bit is shaded, it means that particular bit will be passed through when written.
Each additional group of 32 User Bits that are added, a new Mask parameter will appear for that group. Mask 0 will control the
mask for User Bits 0 through 31. Mask 1 will control the mask for Bits 32 through 63. This sequence repeats for each
additional 32 bits that is added.
Epsilon EP-P Drive Reference Manual
Revision A3
73
www.emersonct.com
Figure 84:
User Bits Mask View
To configure the mask in a user program, the parameter named BitRegisiter.#.ValueMask is written to. The mask can be written to using
Hexadecimal based values or decimal based values. To write a hexadecimal value to the parameter, the hex value must be preceded with the
characters "0x". To write a decimal value to the parameter, normal notation is used. For examples of writing the Mask to a value in a program,
see below.
Example: BitRegister.1.ValueMask = 0xFFFF0000
This example writes a 1 into all bits of the upper sixteen bits, and 0 into each of the lower sixteen bits using hexadecimal value. To write the
same value using decimal notation, the following instruction would be used.
Example: BitRegister.1.ValueMask = 4294901760
This instruction would also write a 1 into each of the upper sixteen bits, and a 0 into each of the lower sixteen bits.
3.24.4 Packed Bits
Packed Bits are 16-bit words configured by the user to read and write groupings of bit-level parameters (booleans and input/output events).
Packed Bits are broken into Control Word(s) and Status Word(s). These words, once configured, can then be accessed via communication
networks and/or within user programs to handle the bits as desired.
Control Words
A master device such as a PLC or HMI writes to the Control Word(s) as a 16-bit word. The data within that word is then broken into individual
bits and written to the bit-level parameters that the user has mapped (see Figure 85). Note that if one of the bit-level parameters within the
control word is modified from some other means (i.e. a user program or an Assignment), that the value of that parameter is not written into the
Control Word value. For example, if a user initiates a Jog Plus within a user program, Bit0 of the Control Word in the Figure 85 below would not
automatically change to 1. Bit0 will only be 1 if the master device sets that bit when writing to the Control Word.
ControlWord.0
PLC
Modbus, EtherNet I/P,
Profibus, DeviceNet
HMI
Figure 85:
Value
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
Jog.0.PlusActivate
Jog.0.MinusActivate
Home.0.Initiate
Index.0.Initiate
Index.1.Initiate
Program.0.Initiate
Program.0.Stop
Stop
Feedhold
Control Words Communications Example
Status Words
Status Words are read by the master device as a 16-bit word. The drive assembles the bit-level parameters mapped by the user into 16-bit
74
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
words for efficient transfer of status information to the master (see Figure 86 below).
StatusWord.0
PLC
Modbus, EtherNet I/P,
Profibus, DeviceNet
HMI
Figure 86:
Value
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
DriveOK
PowerStageEnabled
Jog.0.CommandInProgress
Jog.0.CommandComplete
Home.0.CommandComplete
Index.0.CommandComplete
Index.0.Accelerating
Index.0.AtVel
Index.0.Decelerating
Program.0.ProgramRunning
Program.0.ProgramComplete
Status Word Communication Example
3.24.5 Packed Bits Control Words View
Control Words handle data being written to the user defined drive bit-level parameters. The user configures the Control
Word(s) by dragging-and-dropping the desired bit-level parameters they wish to write into the Control Word mapping. Figure
87 below shows the Packed Bits Control Words view onto which the user has dragged several motion initiate parameters.
Figure 87:
Packed Bits Control Words View
Enable Packed Bits Control and Status Words
In order to use the Pack Bits Control Word and Status Word mapping, the function must be enabled by activating the Enable
Packed Bits Control and Status Words checkbox. If the checkbox is clear, the view remains blank (default). If the checkbox is
selected, then the mapping tree appears which allows the user to configure the Control Word(s) as desired. This checkbox
enables both Control Words and Status Words, and the two cannot be enabled/disabled independently.
Number of Control Words
The user can specify the number of desired 16-bit Control Words for the application. This parameter is adjustable from 1 to 4
words (1 default) using the arrows next to the box. The Number of Control Words cannot be adjusted while online with the
device. If online, the user must disconnect communications and then adjust the number of control words.
Epsilon EP-P Drive Reference Manual
Revision A3
75
www.emersonct.com
Control Word Setup Tab
The Control Word Setup Tab is used to map the desired bit-level parameters onto the existing control word(s). The parameters can be mapped
using one of two methods:
•
•
Drag and Drop: Using the Drag and Drop method, the user navigates the parameter tree, which as been pre-filtered to only show bit-level
parameters, to find the desired parameter they wish to control (write to). Once the desired parameter is found, the user left-clicks and hold
on the desired parameter. While still holding the left-button down, the user drags the parameter onto the desired bit of the desired Control
Word. Then the left-button is released. Doing so will map the selected bit parameter to the selected Control Word bit.
Add Button: Using the Add Button method, the user navigates the parameter tree to find the desired parameter they wish to control. Once
the desired parameter is found, the user left clicks on the parameter to highlight it. Then the user clicks on the desired bit of the Control
Word to highlight it. Once both are highlighted, the Add button on the right side of the view (see Figure 87 above) should become enabled.
Simply click the Add button and the highlighted parameter will be assigned to the highlighted bit on the Control Word.
To delete parameters from the Control Word, simply drag and drop the parameter off the control word (see explanation above), or highlight the
desired parameter to delete, and click the Delete button on the right side of the view.
NOTE
Parameters can be mapped while online, but cannot be sent to the drive using the Update to RAM function. Therefore, any changes to Control
Word mapping requires a full download.
Online Status Tab (Available Online Only)
While online with the drive, the user can monitor the Control Words value (see Figure 88 below). The data is displayed in binary form for each
individual bit of the Control Word(s), as well as hexidecimal and decimal format for each Control Word.
Figure 88:
Control Word Online Status View
Using Pack Bits Control Words
Once the Control Word(s) have been configured by the user, they can be utilized by fieldbus communications (i.e. Modbus, EtherNet I/P,
Profibus, DeviceNet, etc.) or within a user program. Figure 89 shows an example in which the user will write to the Control Word 0 and 1 via
Ethernet I/P.
76
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 89:
Using Ethernet to Communicate to the Control Words 0 and 1
3.24.6 Pack Bits Status Words View
Status Words work to pass bit-level status information from the drive back to the master device as a 16-bit word(s). The user
configures the Status Word(s) by dragging-and-dropping the desired bit-level parameters they wish to read onto the Status
Word mapping. Figure 90 below shows the Packed Bits Status Words view onto which the user has dragged several status
parameters.
Figure 90:
Pack Bits Status Words View
Epsilon EP-P Drive Reference Manual
Revision A3
77
www.emersonct.com
Enable Packed Bits Control and Status Words
In order to use the Pack Bits Control Word and Status Word mapping, the function must be enabled by activating the Enable Packed Bits
Control and Status Words checkbox. If the checkbox is unchecked, the view remains blank (default). If the checkbox is checked, then the
mapping tree appears which allows the user to configure the Status Word(s) as desired. This checkbox enables both Control Words AND
Status Words, and the two cannot be enabled/disabled independently.
Number of Status Words
The user can specify the number of desired 16-bit Status Words for the application. This parameter is adjustable using the spinner control from
1 to 4 words (1 default). The Number of Status Words cannot be adjusted while online with the device. If online, the user must disconnect
communications and then adjust the number of status words.
Status Word Setup Tab
The Status Word Setup Tab is used to map the desired bit-level parameters onto the existing status word(s). The method for mapping
parameters to the Status Word(s) is the same as for the Control Words. See the Drag and Drop and Add Button methods described in the
Control Words section above.
To delete parameters from the Status Word, simply drag and drop the parameter off the status word (see explanation above), or highlight the
desired parameter to delete, and click the Delete button on the right side of the view.
NOTE
Parameters can be mapped while online, but cannot be sent to the drive using the Update to RAM function. Therefore, any changes to Status
Word mapping requires a full download.
Online Status Tab (Available Online Only)
While online with the device, the user can monitor the Status Word value (see Figure 91). The data is displayed in binary form for each
individual bit of the Status Word(s), as well as hexidecimal and decimal format for each Status Word.
Figure 91:
Pack Bits Online Status Tab
Using Pack Bits Status Words
Once the Status Word(s) have been configured by the user, they can be utilized by fieldbus communications (i.e. Modbus, EtherNet I/P,
Profibus, DeviceNet, etc.) or within a user program. Figure 92 below shows an example in which the user will read Status Word 0 from the
drive via Ethernet I/P.
78
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 92:
3.25
Configuring Ethernet to Communicate Status Word 0 from the Drive
I/O Setup Group
The I/O Setup group contains views that control input and output functions as well as other drive functions. These views are as
follows: Selector, Assignments, Input Lines, Output Lines, Analog Inputs, and Analog Outputs. These can be viewed by
expanding I/O Setup then simply clicking on any one of the setup views underneath the I/O Setup.
3.26
Assignments
External control capability is provided through the use of assignments to the Sources (Drive Inputs) or the Destinations (Drive
Outputs). Assignments provide a mechanism for the user to define the internal and external dynamic control structure to
separate complex motion profiles. These functions directly correspond to any input or output line on the drive. External
controllers, such as a PLC or other motion controllers, may be connected to affect or monitor the drive’s operation.
All inputs and outputs are configured as sourcing and are designed to operate from a +10 Vdc to +30 Vdc power source. The
user is responsible for limiting the output current to less than 200 mA for each digital output.
The drive is equipped with sixteen optically isolated input lines (one dedicated to a Drive Enable function) and can be
accessed through the 26-pin dsub connector (J3) located on the front of the drive.
3.27
Assignments View
The Assignments View not only displays information but also makes assignments regarding the source and the destination.
Epsilon EP-P Drive Reference Manual
Revision A3
79
www.emersonct.com
Figure 93:
Assignments View
The Assignments View is used to tie a source to a destination. Destinations are functions that need to be triggered, such as Index Initiates,
Program Initiates, Jog Initiates and so on.
Sources are located on the left side of the Assignment View and reflect events that occur in the drive. These events are based on drive activity.
By expanding individual groups, you will see more detailed parameters. For example, in an Epsilon EP-P drive configuration if you expand the
Inputs source group, you will see DriveInput.1 through DriveInput.15, as shown in Figure 93. You can use these events to trigger certain
actions (or destinations) on the right side of the view.
To make an assignment, a source must be tied to a destination. Any source can be tied to any destination to create the desired system
operation.
3.27.1 Creating An Assignment
Various methods can be used to tie a source (such as DriveInput.1) to a destination, (such as Index.0.Initiate).
Drag and Drop Method
First, position the mouse pointer over the source on the left to assign to the destination on the right. Press the left mouse button while over the
source, and hold the button down. While holding the left button down, drag the source until the pointer is positioned over the desired
destination and release the left mouse button.
Destinations can also be dragged over to sources, see Figure 94.
Assign Button Method
Click on both the source and destination you wish to assign to each other. Once both are selected, the Assign button in the lower left corner of
the view will become enabled. Click the Assign button to complete the assignment. Figure 93 shows the source and destination highlighted,
and the Assign button available to click on.
Once an assignment has been made, you will see the “Assigned to..” and the “Set From” columns filled in for the specific sources and
destinations. This indicates what destination(s) an individual source has been assigned to, and what source(s) an individual destination is
assigned to.
Any source can be assigned to up to ten different destinations maximum. Any destination can have as many sources as desired assigned to it.
3.27.2 Deleting An Assignment
Delete Button Method
Click on the source or destination you wish to delete. Once selected, the Delete button will become available. Click the Delete button to
remove the assignment.
Right Click Method
Position the pointer over the specific assignment to delete then right click. A selection box will appear. From this selection box, choose Delete.
After either of these procedures, the assignment will disappear.
80
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Drag and
Drop Method
Figure 94:
Tying a Source to a Destination
3.27.3 Assignment Polarity
The active state of an assignment can be programmed to be Active Off, Active On, or Custom using PowerTools Pro. Making
an assignment “Active On” means that the destination will be active when the source it is assigned to becomes active, and is
inactive when the source is inactive. Making an assignment “Active Off” means that the destination will be active when the
source it is assigned to is inactive, and will be inactive when the source is active.
The polarity of the assignment can also be changed to Custom when required. Custom polarity allows you to make a
destination activate and deactivate based on two different sources.
NOTE
Destination functions which initiate motion (Jog.PlusInitiate, Jog.MinusInitiate, Index.#.Initiate, and Home.#.Initiate) cannot
be set “Active Off”.
Default polarity for a new assignment is Active On. Two methods will change the polarity of an assignment.
Polarity Button Method
Click on either the Source or the Destination you wish to change the polarity of. Once highlighted, the Polarity button will
become available in the lower right corner of the view. Click on the Polarity button and change the settings as desired in the
Polarity dialog box. Click OK to apply the changes.
Right Click Method
Position the pointer over the specific assignment you with to change polarity of and click the right mouse button. A selection
box will appear. From this selection box, choose Polarity. the Polarity dialog box will appear. Change the Polarity settings as
desired and click OK to apply the changes.
3.27.4 User Level
The User Level filters the available assignments. The User Level is changed on the Options menu at the top of the PowerTools
Pro toolbar. Choose Options/Preferences/User Levels. Easy mode filters out all but the most commonly used sources and
destinations. Detailed mode filters out less, expanding the list of sources and destinations for more complex configurations.
Too Much mode does not filter at all and provides all sources and destinations.
3.27.5 Only Show Assigned Check Box
When this check box is selected it removes the unassigned sources and destinations from the view. It allows the user to
quickly see how many sources and destinations have been assigned.
3.27.6 Assignments that Automatically Use Position Capture
Certain assignments (Sources or Destinations) automatically generate position capture data internally for greater performance
and accuracy. This captured data is used by the Epsilon EP-P drive, but is not directly available to the user. Following is a list
of assignments that automatically generate or use captured data.
Epsilon EP-P Drive Reference Manual
Revision A3
81
www.emersonct.com
Sources that generate capture data
Drive Inputs 1-15
The Epsilon EP-P Inputs are constantly monitored by the processor, and when activated will automatically capture related data. The processor
controls all resetting requirements. The capture only occurs on the rising edge of an input. When the input is activated, the captured data will
automatically be passed to the destination that it is assigned to. The destination may then use the captured data to accurately initiate motion (if
it is a motion-related destination).
Motor Encoder Marker
The rising edge of the motor encoder marker pulse will automatically capture data. This will allow the user to accurately initiate motion on the
rising edge of the motor encoder marker pulse. The falling edge of the marker pulse does not capture data.
Master Encoder Marker
The rising edge of the master encoder marker pulse will automatically capture data. This allows the user to accurately initiate motion on the
rising edge of the master encoder marker pulse. The falling edge of the marker pulse does not capture data.
Index/Jog Command Complete
Activation of the command complete signal at the end of indexes and jogs will automatically capture data. A subsequent index, jog, or dwell
can then use the captured data to start itself extremely accurately at the end of the previous motion.
Index/Jog At Velocity
Activation of the command complete signal at the end of indexes and jogs will automatically capture data. A subsequent index, jog, or dwell
can then use the captured data to start itself extremely accurately at the end of the previous motion.
PLS Status
A rising or a falling edge of a Global PLS will automatically capture data for use in initiating motion. In order to accurately initiate motion from a
Global PLS, an assignment can be made from PLS.#.Status to the initiate destination.
Destinations that use captured data:
Index/Jog Initiates
When one of the sources listed above is assigned to an Index or Jog Initiate, the captured information is automatically applied to the index
starting point. This offers extremely high accuracy for initiation of motion, which is beneficial especially in synchronized applications.
Index.#.SensorTrigger
The sensor trigger destination used in registration indexes can use captured data to accurately calculate the ending position of the index based
on the Registration Offset parameter. The Offset distance is added to the captured position to get the accurate stopping position for the
registration index.
3.28
Selector View
The Selector view is located under I/O Setup in the Hierarchy Tree on the left of the view.
Figure 95:
Selector View
The selector allows conservation of the number of input lines by using a binary input conversion to decimal. The binary select lines are set up
by assigning sources to the Selector.Select destinations on the Assignments view. In most cases, hardware inputs are assigned to the
Selector.Select functions (see Figure 96).
Based on the status of the binary select lines, a Selector.Selection source will be active when the Selector.SelectorInitiate destination is
activated.
At the top of the Selector view, the Selector Input Destinations scroll box defines how many binary select lines will be used. The number of
Selector.Selections is a direct result of the number of select lines. The formula is as follows:
# of selections = 2n where n is the number of select lines.
82
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The maximum number of select lines is eight.
Once you have determined how many select lines you want, the assignments to these Selector.Select lines must then be
made in the Assignments view.
Figure 96:
Assignment View
For example, if we entered 3 for the number of Selector Input Destinations, we would have 8 selection lines
(Selector.Selection0 through Selector.Selection7). The Selector.Selection number that is activated is determined by the status
of the Selector.Select lines when the Selector.Selector Initiate bit is activated. Each select line has a specific binary value.
The binary value is determined as follows:
S n x 2n
where Sn = Status of Selector.Select line n
Sn = 0 if Selector.Select line n is inactive, and
Sn = 1 if Selector.Select line n is active
The sum of all the binary values determines which Selector.Selection line will be active.
The following examples demonstrate how to determine which Selector.Selection will activate based on the Selector.Select
lines.
Example: 1
If Selector.Select2 is active, Selector.Select1 is inactive, and Selector.Select0 is active, then the total binary value is as
follows:
S2 = 1, S1 = 0, and S0 = 1. Therefore,
Total Binary Value = (1 x 22) + (0 x 21) + (1 x 20)
Total Binary Value = 4 + 0 + 1
Total Binary Value = 5
Therefore, when Selector.SelectorInitiate activates, then Selector.Selection5 will activate.
Example: 2
If Selector.Select2 is inactive, Selector.Select1 is active, and Selector.Select0 is active, then the total binary value would be as
follows:
S2 = 0, S1 = 1, and S0 = 1. Therefore,
Total Binary Value = (0 x 22) + (1 x 21) + (1 x 20)
Total Binary Value = 0 + 2 + 1
Total Binary Value = 3
Epsilon EP-P Drive Reference Manual
Revision A3
83
www.emersonct.com
Therefore, Selector.Selection3 would activate.
The Selector.Select lines can change without any action until the Selector.SelectorInitiate destination is activated.
Selector.Selection sources can be tied to any destination in the Assignments view. Figure 96 shows the four selection lines being tied to Index
0 through Index 3 initiates. By doing this, we could initiate up to four indexes with only two select lines and a selector initiate. This can help
minimize the number of inputs required to initiate a large number of indexes or programs.
3.29
Input Lines View
The Input Lines View displays any functions that have been assigned to the drive hardware inputs. See Figure 97.
NOTE
No assignments can be made using the Input Lines View, assignments are only displayed in the Input Lines View.
Figure 97:
Input Lines View
The following two functions can be performed on the Input Lines view.
Name
You can assign a descriptive name to each input and make the setup easier to follow. The length of the text string is limited to a maximum of
12 characters. Simply double click on the Name field of any input line to assign a name to it.
Debounce
You can program a “Debounce Time” to any input line, which means the motion profile will need to be steady for at least the debounce time
before it is recognized. This feature helps prevent false triggering in applications in noisy electrical environments. At the end of the debounce
time, the next action can occur.
Figure 98:
Input Line Diagram
If the Input Line attached to the home sensor is debounced, the actual rising edge of the Home Sensor is used to determine the Home
Reference Position (the debounce time ensures a minimum pulse width).
3.30
Output Lines View
The Output Lines View displays any functions that have been assigned to the drive hardware outputs. See Figure 99.
84
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 99:
Output Lines View
Names
Descriptive text names can be assigned to individual output lines to make the setup easier to follow.
3.31
Analog Inputs View
The analog input is scaled from +10 V to -10 V range to either the units of the selected variable or to the defined units. A linear
scale with offset is defined by entering two points on the scale, a min and max to correlate the user unit to analog voltage. The
actual minimum and maximum range of either user unit or analog voltage does not need to be entered as the algorithm will
extrapolate the range.
The drive has one Analog input channel that accepts a +10 V to -10 V signal. The drive has a 12-bit over sampled to 14-bit
analog to digital converter (A/D), which is used to transform the analog voltage to a usable parameter in the drive. The analog
input is scanned by the drive every 100 microseconds.
Figure 100:
Analog Inputs View - Enabled
3.31.1 Enable Channel Check Box
By default, the analog input channel is not enabled meaning that the drive is not reading the A/D value read by the analog
circuit. If the check box is clear, the channel is not enabled and the configuration parameters for the analog input are
unavailable and therefore have no effect.
To enable the analog input, simply select the Enable Channel check box, and the configuration parameters will become
available to edit. With the channel enabled, the trajectory loop update will transfer data from the drive into
DriveAnalogInput.RawValue as volts and into DriveAnalogInput.ValueIn scaled.
Destination Variable
The Destination Variable (DriveAnalogInput.CustomDestinationVariable) can be entered one of two ways: by just typing any
parameter using the program format (dot notation) for the variable, or click the Popup Variables button and the Select
Variables from Tree window will open. Select the variable and drag it over to the Destination Variable text box.
Epsilon EP-P Drive Reference Manual
Revision A3
85
www.emersonct.com
Bandwidth
This parameter (DriveAnalogInput.LowPassFilterFrequency) sets the low-pass filter cutoff frequency applied to the analog input. Signals
exceeding this frequency will be filtered at a rate of 20 db per decade.
3.31.2 Set Maximums Group
Maximum Value
This parameter (DriveAnalogInput.MaxUserValue) is used for user unit scaling. Enter the maximum value in analog user units to which the
maximum analog voltage should correspond.
Maximum Voltage
Enter the maximum voltage that will be seen on the analog input terminals. The user can enter the value in this text box
(DriveAnalogInput.MaxVoltageValue) by hand, or set the analog source to it’s maximum value with just a click of the “Set Max Voltage to
Measured” button next to the text box.
Set Max Voltage To Measured Button
Click this button to read the current value on the analog channel and enter it into the Maximum Voltage text box.
3.31.3 Set Minimums Group
Minimum Value
Enter the minimum value in analog user units that the minimum analog voltage should correspond to.
Minimum Voltage
Enter the minimum voltage that will be seen on the analog input terminals. The user can enter the value in this text box
(DriveAnalogInput.MinVoltageValue) by hand, or set the analog source to it’s minimum value with just a click of the “Set MinVoltage to
Measured” button next to the text box.
Set Min Voltage To Measured Button
Click this button to read the current value on the analog channel and enter it into the Minimum Voltage text box.
3.31.4 A/D Voltage
This parameter (DriveAnalogInput.RawValue) is visible while online. It is the raw analog input in Volts.
3.31.5 ValueIn
This parameter (DriveAnalogInput.ValueIn) is visible while online. This is the results of the analog value scaled to the user unit value.
3.31.6 Read Max/Min Voltage Settings
This button when pressed will read the Min and Max voltages from the drive and the voltages are entered into the Min and Max Voltage text
boxes in the configuration file.
3.32
Analog Outputs View
The drive has two 10-bit Analog Outputs that may be used for diagnostics, monitoring or control purposes. These outputs are referred to as
Channel 1 and Channel 2. They can be accessed from the analog/sync output connector (J5) on the Epsilon EP-P drive.
The analog output is scaled from the units of the selected variable to the +10/-10 volt range of the Analog Output. It is a linear scale with offset
defined by entering two points on the scale, a minimum and maximum to correlate the user units to analog voltage. The actual minimum and
maximum range of either user unit or analog voltage does not need to be entered as the algorithm will extrapolate the ranges.
Figure 101:
Analog Outputs View
86
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.32.1 Enable Channel Check Box
By default, the analog output channels are not enabled meaning that a value is not being sent to the analog circuit. When the
channel is disabled (check box is clear), the configuration parameters for that analog output are unavailable and therefore
have no effect. To enable the output, simply select the Enable Channel check box, and the configuration parameters will
become available to edit.
If the user wishes to control the Analog Output through other means, it is necessary to clear the Enable Channel check box.
3.32.2 Source
This list box allows the user to create a direct connection from a Source parameter to the Analog Output. The current value of
the parameter selected as the Source will directly determine the value of the Analog Output signal. The Source list box
contains a list of predefined parameters to select from.
Custom Variable
The Custom Variable parameter is only available once the user has selected Custom Variable from the Source list box above.
This text box is used to define what parameter will control the Analog Output. The selected parameter will directly determine
the value of the analog output based on the Max and Min scaling values entered on this view. The parameter is entered here
in program format or see Popup Variables Button, below.
Popup Variables Button
Click this button to open the Select Variables from Tree window. Select the variable and drag the variable over to the Custom
Variable text box to assign the variable to the Analog output channel.
3.32.3 Maximum Value
The analog output is a linear interpolation of the selected drive variable between the minimum and maximum specified end
points. Each end point is specified as the user value and the corresponding output value at that point. The number of decimal
places for both values is taken from the selected drive variable. MaxUserValue is the maximum user unit value which
corresponds to the maximum analog output value.
3.32.4 Maximum Output
The analog output is a linear interpolation of the selected drive variable between the minimum and maximum specified end
points. Each end point is specified as the user value and the corresponding output value at that point. The number of decimal
places for both values is taken from the selected drive variable. MaxOutputValue is the maximum analog output value which
corresponds to the maximum user value.
3.32.5 Minimum Value
The analog output is a linear interpolation of the selected variable between the minimum and maximum specified end points.
Each end point is specified as the user value and the corresponding output value at that point. The number of decimal places
for both values is taken from the selected variable. MinUserValue is the minimum user unit value which corresponds to the
minimum analog output value.
3.32.6 Minimum Output
The analog output is a linear interpolation of the selected variable between the minimum and maximum specified end points.
Each end point is specified as the user value and the corresponding output value at that point. The number of decimal places
for both values is taken from the selected variable. MinOutputValue is the minimum analog output value which corresponds to
the minimum user value.
3.32.7 Feedback
Analog Output Feedback is the Analog output voltage to be sent out after scaling the selected source parameter.
3.33
Motion Group
All motion parameters related to Jogs, Homes, Indexes, Gearing and Camming are located in the Motion hierarchy group.
Motion views will use units that correspond to Realtime or Synchronized motion. This choice is made on each motion view.
The units are customized in the Setup Group: Realtime units are defined on the User Units View, and Synchronized units are
defined on both the User Units View and the Master Units View.
Each of the motion views, when online, have an Online tab that displays feedback information and provides buttons to initiate
motion.
3.34
Jog View
Jogging produces rotation of the motor at controlled velocities in a positive or negative direction. The jog is initiated with the
Jog.#.Initiate destination or from a program.
Epsilon EP-P Drive Reference Manual
Revision A3
87
www.emersonct.com
Figure 102:
Jog View
Jog Number
This box allows you to select between Jog0 and Jog1 setup views.
Jog Name
This is a descriptive character string which can be assigned to the specific jog. Giving a name to a jog can make the motion setup easier to
follow.
Time Base
This list box allows the user to select between a jog that is based on time (Realtime) as defined by user units, normally in seconds, or a time
based on Master position via an external encoder (Synchronized) set in the Master Units View.
Jog Velocity
This parameter specifies the target jog velocity for the individual Jog. The motor will run at this velocity when jogging with an assignment or
through a program. This value is a signed number. The direction of the jog is determined by the sign of the jog velocity as well as using the
Jog.PlusInitiate or the Jog.MinusInitiate.
Jog Acceleration
This is the acceleration ramp used when initiating this individual Jog. If S-Curve ramps are used, then this is the average acceleration rate for
the entire ramp. The units for the acceleration are setup in the Setup - User Units view in PowerTools Pro.
Jog Deceleration
This is the deceleration ramp used when stopping this individual Jog. If S-Curve ramps are used, then this is the average deceleration rate for
the entire ramp. The units for the deceleration are setup in the Setup - User Units view in PowerTools Pro.
3.34.1 Jog Sources and Destinations
Sources
The following source functions can be found in the Assignments view under the Jog setup group:
Jog.AnyCommandComplete
The Jog.AnyCommandComplete source will activate when either Jog0 or Jog1 completes its deceleration ramp, and reaches zero
commanded velocity. It will deactivate when any Jog is initiated again. If the Stop destination is used during a Jog, then the
Jog.AnyCommandComplete will not activate.
Jog.#.Accelerating
This source is active while a jog is accelerating to its target velocity. Once the Jog reaches the target velocity, the Jog.#.Accelerating source
will deactivate.
Jog.#.AtVel
This source activates when the individual jog reaches its target velocity. It deactivates when a jog deceleration ramp begins.
Jog.#.CommandInProgress
The Jog.#.CommandInProgress source is active throughout an entire jog profile. The source activates at the beginning of a jog acceleration
ramp, and deactivates at the end of a jog deceleration ramp.
Jog.#.CommandComplete
The Jog.#.CommandComplete source will activate when the specific jog completes its deceleration ramp. It will remain active until the specific
jog is initiated again. If the Stop destination is used during a Jog, then the Jog.#.CommandComplete will not activate.
88
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Jog.#.Decelerating
This source is active while a jog is decelerating from its target velocity. Once the Jog reaches zero velocity (or its new target
velocity), the Jog.#.Decelerating source will deactivate.
Destinations
The following destination functions can be found in the Assignments view under the Jog setup group:
Jog.PlusActivate
When this destination is activated, jogging motion will begin in the positive direction. The jog velocity is determined by which
jog (Jog0 or Jog1) is active or not. A jog stops when this destination is deactivated. If the jog velocity is negative,
Jog.PlusActivate will cause the motor to jog in the negative direction.
Jog.MinusActivate
When this destination is activated, jogging motion will begin in the negative direction. The jog velocity is determined by which
jog (Jog0 or Jog1) is active or not. A jog stops when this destination is deactivated. If the jog velocity is negative,
Jog.MinusActivate will cause the motor to jog in the positive direction.
Jog.Select0
This destination is used to select between Jog0 and Jog1. When the Jog.Select0 destination is not active, the target velocity
for the jog is the Jog.0.Velocity. If the Jog.Select0 destination is active, the target velocity of the jog is the Jog.1.Velocity.
Jog.Select0 can be toggled “On” or “Off” while jogging. Jog acceleration and deceleration ramps are used to ramp between jog
velocities.
Below is a description of jog operation using these destinations.
NOTE
In the table below Jog.0.Velocity = 100 RPM and Jog.1.Velocity = -500 RPM.
Jog.PlusActivate
Jog.MinusActivate
Jog.Select0
Motion
Off
Off
Off
0 RPM
On
Off
Off
+100 RPM
Off
On
Off
-100 RPM
On
Off
On
-500 RPM
Off
On
On
+500 RPM
On
On
Off
0 RPM
On
On
0 RPM
On
All Jog destinations are level sensitive.
Figure 103:
Jog Activation
Epsilon EP-P Drive Reference Manual
Revision A3
89
www.emersonct.com
0
Figure 104:
Jog Select Details
If the Jog direction is reversed, the Jog.#.Decel value will be used to decelerate the motor to zero speed and then the Jog.#.Accel will be used
to accelerate to the new (opposite sign) velocity.
NOTE
The Jog destinations cannot be initiated when any other motion type (homing, indexing, or programs) is in progress.
If both jog input functions are “On” there is no motion after a jog deceleration (they effectively cancel each other). The drive’s display will show
“R”, for ready.
If the drive is jogging with the Jog.PlusActivate destination active and the Jog.MinusActivate destination activates, the motor will behave the
same as if it would if Jog.PlusActivate just deactivated.
The Stop destination (found under the Ramps group in the Assignments view) will override the Jog operation and decelerate the motor to zero
speed at the stop deceleration rate.
If the motor reaches a Travel Limit, you can Jog off the Travel Limit in the opposite direction. (Use Jog.PlusActivate to move off a Travel Limit ).
3.35
Home View
The Home is used in applications in which the axis must be precisely aligned with some part of the machine. The Home is initiated with the
Home.#.Initiate Destination or from a program.
Figure 105:
Home View
Home Number
The Home Number parameter displays which home sequence you are editing and allows you to scroll through multiple home sequences using
the up and down arrows. The first release only allows for one home sequence.
90
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Name
Allows the user to assign a descriptive name to the home sequence up to 10 characters in length.
Home Reference
This parameter determines the signal used as the reference. The parameter can have one of three different values: 'Sensor',
'Marker', or 'Marker then Sensor'. When the home reference is 'Sensor' the rising edge of the 'Home.#.SensorTrigger'
destination is used to establish the home position. When the home reference is 'Marker' the rising edge of the motor encoder's
marker channel is used to establish the home position. When the home reference is 'Sensor then Marker' the home position is
established using the first marker rising edge after the Home.#.SensorTrigger destination activates.
Time Base
Selects the Time Base for the home move velocity and acceleration/deceleration. Real-time and sync are the allowed
selections.
Velocity
Sets the target velocity for the home. The polarity determines the home direction. Positive numbers cause motion in the
positive direction and negative numbers cause motion in the negative direction in search of the home reference.
Acceleration
Average Acceleration rate used during the home. Units are specified on the User Units View.
Deceleration
This is the average Deceleration rate used at the end of the Home move in user units.
If on sensor... Group
These radio buttons determine how the system reacts if the Home.#.SensorTrigger is already active when the home is
initiated.
’Back off before homing’ Radio Button
If this radio button is selected, the drive will back off the sensor before beginning the home. It does this by moving the direction
opposite to that specified by the sign of the home velocity. It continues moving in this direction at the target home velocity until
the sensor deactivates. The motor then decelerates to a stop and performs a standard home.
’Go forward to next sensor’ Radio Button
If this radio button is selected, then the system will ignore the sensor that is active when the home is initiated, and move in the
proper direction until the first low to high transition of the Home Reference signal.
Home Offset Group
The Home Offset group has two buttons, the calculated Offset Radio Button and the Specified Offset Radio Button.
Calculated Offset Radio Button
The calculated offset is defined as the distance traveled during deceleration ramp from the home velocity to a stop plus the
distance traveled at the home velocity for 1600µs. This extra distance is used to guarantee that the motor will not need to
backup after the deceleration ramp.
Specified Offset Radio Button
The specified offset allows the user to choose an exact offset from the Home Reference point. The commanded motion will
stop at exactly the offset distance away from the reference point as specified. If the specified offset is smaller than the
calculated offset, the motor will decelerate to a stop and then back up to its final offset position.
Limit Distance
LimitDistEnable
This check box enables the specified Home Limit Distance.
The Limit Distance parameter places an upper limit on the incremental distance traveled during a home. If no home reference
is found in this distance, the motor will decelerate to a stop at the limit distance and activate the Home.#.LimitDistHit source.
End of Home Position
This parameter defines the position at the completion of the home. This defaults to 0.0 such that at the end of a home, the
Feedback Position and the Commanded Position are set to 0.0. If you wish your Feedback Position to be something other
than 0.0 at the end of a home, then enter the exact desired position here.
Figure 106 is a diagram of a home using the "Back off before homing" radio box, a Home Reference of "Sensor", and using a
Epsilon EP-P Drive Reference Manual
Revision A3
91
www.emersonct.com
"Calculated Offset".
Home
Sensor
Input
Off
On
On
Off
Velocity
Back off
Sensor Move
Time
Start of Normal
Home Routine
Home Reference
Position
Figure 106:
Home Reference Position
3.35.1 Home Sources and Destinations
Sources
Home.AbsolutePosnValid
This source is activated when a Home is successfully completed. It indicates that the drive has been homed properly. It is will be deactivated
by the Home.#.Initiate destination, an encoder fault, a reboot, or when the drive’s 24 V logic is powered down.
Home.AnyCommandComplete
This source is activated when any home motion command is completed. If a drive stop destination is activated before the home has
completed, this source will not activate. It will be deactivated when another home is initiated.
Home.#.Accelerating
This source is active while a home is accelerating to its target velocity. Once the home reaches the target velocity, the Home.#.Accelerating
source will deactivate. This source will also activate during the "back off sensor" motion before the actual home.
Home.#.AtVel
This source activates when the home reaches its target velocity. It deactivates when a home deceleration ramp begins. Home.#.AtVel will not
be activated during the "back off sensor" portion of the home.
Home.#.CommandComplete
The Home.#.CommandComplete source will activate when the specific home completes its deceleration ramp. It will remain active until the
specific home is initiated again. If the drive stop destination is used during a home, then the Home.#.CommandComplete will not activate.
Home.#.CommandInProgress
Activated when the Home is initiated and remains active until all motion related to the Home has completed.
Home.#.Decelerating
This source is active while a home is decelerating from its target velocity. Once the home reaches zero velocity (or its’ new target velocity), the
Home.#.Decelerating source will deactivate. This source will also activate during the "back off sensor" motion before the actual home.
Home.#.LimitDistHit
This source is activated when the home reference is not found before the Home Limit Distance is traveled. It will remain active until the home
is initiated again.
Destinations
Home.#.Initiate
The Home.#.Initiate destination is used to initiate the home function. The Home is initiated on the rising edge of this function. The drive will not
initiate a Home if there is an Index, Jog, or Program in progress, or if the Stop destination is active or if a travel limit is active.
Home.#.SensorTrigger
This destination is required to be used if you are homing to a sensor. This destination is edge sensitive. The home position is determined when
the Home Sensor destination is activated.
If the drive receives a Home.#.Initiate input while the Home.#.SensorTrigger is active, you can choose to have the motor “back-off” of the home
sensor before it initiates the home function, or move forward to the next sensor.
If debounce is used on the hardware input that the Home.#.SensorTrigger is assigned to, the debounce determines the length of time the input
must be active to be considered a valid input. The rising edge of the sensor is still used for the reference position. This maintains accuracy
while providing the ability to ignore false inputs.
92
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.36
Index View
An index is a complete motion sequence that moves the motor a specific incremental distance or to an absolute position. The
index is initiated with the Index.#.Initiate destination or from a program.
Figure 107:
Index View
Index Number
The Index Number parameter selects the index number with a scroll box.
Index Name
The User can specify an Index name of up to 12 alphanumeric characters. This allows assigning a descriptive name to each
index indicating different machine operations.
IndexType
Select the index type from Incremental, Absolute, Correction, Posn Track Cont., Posn Track Once, Registration, Rotary Plus,
or Rotary Minus. Click the down arrow on the parameter list box to select the desired type of Index profiles, as follows:
Incremental Indexes run a specified distance from the current position.
Absolute Indexes move to an exact position with respect to the home reference point. The absolute index could run in either a
clockwise (CW) or counterclockwise (CCW) direction dependent on the current position when it is initiated.
Correction Indexes are used to follow a dynamic fieldbus or analog value that changes the index distance of the index prior to
and during the index motion. Correction indexes use incremental distance values. The index distance value can be updated
via Fieldbus, by simply writing to the index distance parameter. If the analog input's Destination Variable is set to an Index
Distance parameter, the index's distance value will be updated by the Analog to Position scaling found in the Analog Input
view. See Analog Input view.
Posn Tracker indexes are used to follow a dynamic fieldbus or analog value that changes the end point of the index prior to
and during the index motion. Position Tracker indexes use absolute position values. The position value can be updated via
fieldbus, by simply writing to the index position parameter. If the analog input's Destination is set to an Index number, the
index's position value will be updated by the Analog to Position scaling found in the Analog Input view.
A Registration Index runs at the specified velocity until a registration sensor is seen or until it reaches the Registration Limit
Distance. If a Registration Sensor is seen, then the index runs an additional Registration Offset distance.
Rotary Plus and Rotary Minus type indexes are typically used in applications which use rotary rollover. These absolute
indexes are forced to run in a specific direction regardless of the starting point.
TimeBase
This list box selects the Time Base for the index velocity and acceleration/deceleration. Real-time and Sync are the allowed
selections.
Epsilon EP-P Drive Reference Manual
Revision A3
93
www.emersonct.com
Distance/Position
The Distance/Position parameter is a signed value which specifies the distance the index will travel (incremental index) or the absolute position
the index will move to (absolute index). In the case of an incremental index, this parameter also determines the direction the index will travel. If
an index type of Registration is selected, then this is a limit distance, or the maximum distance the index will travel if a registration sensor is not
seen.
Velocity
This sets the target velocity for the index profile. The velocity parameter is unsigned and must be greater than zero. Direction of the index is not
determined by the velocity, but by the Distance/Position parameter.
Acceleration
Average Acceleration rate used during the index. Units are specified on the User Units view.
Deceleration
The Deceleration parameter specifies the deceleration value to be used during the index in user units.
3.36.1 Timed Indexes
A Timed Index allows the user to specify the amount of time in which to perform an index rather than specifying the Velocity, Acceleration, and
Deceleration. The processor in the Epsilon EP-P drive will automatically calculate the necessary velocity, accel, and decel in order to achieve
the programmed distance in the specified time. A Timed Index can not be compounded into or out of.
All index types can be specified as a Timed Index, except for Registration and Posn Track type indexes. This is because these types of
indexes do not have a specified distance or absolute position. If a Registration or Posn Track type index is selected, then the Timed check box
will become disabled.
Based on the Distance entered (or Position for Absolute indexes) and the Time value specified, the calculations could result in extremely high
Velocities, Accels, and Decels. To avoid damage to mechanical parts, or potentially dangerous situations, the user is allowed to enter the
Maximum Velocity, Acceleration, and Deceleration used for the calculations. The results of the firmware calculations will never exceed the
maximum values specified.
Figure below shows a screen capture in which the Time check box has been enabled. Notice how the parameters which normally say Velocity,
Acceleration, and Deceleration have changed to say Max. Velocity, Max. Acceleration, and Max. Deceleration. When the Time check box is
enabled, these parameters automatically become maximums for use in the calculations.
Figure 108:
Time Check Box Enabled
If the values for Max.Velocity, Max.Acceleration, and Max.Deceleration are such that the distance cannot be covered in the specified time, the
Index.ProfileLimited flag will activate when the index is initiated, indicating the index cannot be performed as desired. The internal calculation
are performed only when the index is initiated, and therefore is the only time the flag will activate. The Index.ProfileLimited flag will remain
active until cleared using the Index.ResetProfileLimited assignment or program instruction. In this situation, the index will still operate, but the
time will be extended. In other words, the profile will be performed using the maximums values and still cover the specified distance, but not in
the specified time.
94
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The units for the Time parameter depend on the current setting of the Time Base parameter. If Time Base is set to “Realtime”
(default), then the units for the Time parameter are Seconds.The user can program the index time with resolution of 0.001
Seconds (or milliseconds). If Time Base is set to “Synchronized”, the units for the Time parameter are defined by the Master
Distance Units found on the Master Units view.
Doing a synchronized Timed Index means that the user can specify the master distance in which the index should be
performed. This can be very useful in many synchronized motion applications.
The internal calculations are designed to calculate a triangular profile (all accel and decel) The ratio of acceleration to
deceleration will be the same ratio as Max. Acceleration to Max. Deceleration parameters. For example, if the deceleration is
desired to be twice the acceleration, a number twice the value of max acceleration would be entered for maximum
deceleration. If the Maximum Velocity is low enough such that the profile will become trapezoidal (some duration at max
velocity). Even in trapezoidal moves, the same ratio of acceleration and deceleration is maintained.
The calculations are based on the assumption that Feedrate Override is set to 100%. If set to greater that 100%, the motor
could run in excess of the specified Max. Velocity.
Max Velocity
Max Accel
Trapezoidal
Move
Max Decel
Index.ProfileLimited activates
for this profile
Triangle
Move
Time
Figure 109:
Timed Index Profiles
Enable Index PLS
This check box enables (when selected) or disables the Index PLS function.
An Index PLS is similar to a global PLS (explained in the PLS View section), but is incremental in nature. The Index PLS has
On and Off points just like a global PLS, but the On and Off points are specified as an incremental distance from the start of
the index, instead of absolute positions. Each index has its own On and Off points, and the Index.#.PLSStatus is only updated
when Index# is run. The direction of the PLS does not matter, the Index.#.PLSStatus will activate and deactivate the same
incremental distance from the start of the index.
PLS On Point
This parameter is an incremental distance from the start position of the index, at which the PLS.#.Status will become active. It
is an unsigned value in user units. The On Point must always be less than the Off Point.
PLS Off Point
This parameter is an incremental distance from the start position of the index, at which the PLS.#.Status will deactivate. It is
an unsigned value in user units. The Off Point must always be greater than the On Point. If the Off Point is larger than the
Distance parameter in an Incremental type of index, the PLS Status will never deactivate until the index is run again.
Example 1:
Index 0 is an Incremental index with a distance of 5 Revs. The PLS On Point is set to 1 Rev, and the PLS Off Point is set to 4
Revs. A home is completed, and Position Feedback is equal to 0.0 Revs.
If Index 0 is run, the Index.0.PLSStatus will activate when the feedback position reaches 1 Rev and remain active until
feedback position reaches 4 Revs, and deactivate. At the end of Index 0, position feedback is equal to 5 Revs. If we initiate
Index 0 again, Index.0.PLSStatus will activate 1 Rev into the index, or at 6 Revs. It will remain active until position feedback
reaches 9 Revs, and deactivate. This index could be run over and over again, and Index.0.PLSStatus will activate 1 Rev from
the starting position and deactivate 4 Revs from the starting position every time.
Example 2:
Index 1 is an Incremental index with a distance of -10 revs. The PLS On Point is set to 4 Revs, and the PLS Off Point is set to
6 Revs. A home is completed, and Position Feedback is equal to 0.0 Revs.
If Index 1 is run, the Index.1.PLSStatus will activate when the position feedback reaches -4 Revs (or 4 Revs from the start of
the index). Index.1.PLSStatus will then deactivate when position feedback reaches -6 Revs (or 6 Revs from the start of the
index). If Index 1 is run again, Index.1.PLSStatus will activate and deactivate at -14 Revs and -16 Revs respectively.
Index PLS’s can be used on any type of an index.
If an index is so short (possible in the case of an absolute index) that it reaches the On Point, or incremental distance, into the
index, but never reaches the Off Point, the Index.#.PLSStatus will remain active until the index is run again.
Epsilon EP-P Drive Reference Manual
Revision A3
95
www.emersonct.com
Similarly, if the index is so short that it never reaches the On Point, the Index.#.PLSStatus will never activate.
Registration Tab Parameters
The following parameters are entered on the Registration tab and are only available if Registration is selected as the Index Type.
’Analog’ or ’Sensor’ Radio Buttons
Select one of these radio buttons to determine what signal will be used as your registration trigger.
If ’Sensor’ is selected, a source must be assigned to the Index.#.SensorTrigger. Typically a proximity sensor is wired to a hardware input, and
therefore a drive input source is assigned to the Index.#.SensorTrigger, but any source can be used.
If ’Analog’ is selected, one of the analog signals must be selected in the analog list box. Available selections are Analog In, Torque Command,
or Torque Feedback. Then a comparison operator must be selected from the operator list box. Available selections are > (greater than) and <
(less than). Last, an analog value must be entered for comparison.
Registration to Analog Input Value
If Analog In is selected from the list box, the value of the drive Analog Input is used as the registration signal. When the value of the analog
input reaches a value that satisfies the comparison operator, the sensor trigger will activate. Units for the registration value will match the units
configured on the Analog Inputs view when Analog In selected.
Registration Offset
The incremental distance the motor will travel after a valid registration sensor or analog limit value has been detected. This is a signed
parameter; so if an index is travelling in the negative direction, the offset needs to be negative to continue travelling in the same direction. If the
registration offset is zero or less than the decel distance shown on the calculations tab, the motor will decelerate at the programmed rate and
then back up to the specified offset distance from the trigger position.
Enable Registration Window
This check box enables (if selected) the Registration Sensor Valid Window. When active, only registration marks that occur inside the
registration window are seen as valid.
Window Start
This parameter defines the start of the Registration Sensor Valid Window relative to start position of this index. This is an unsigned value and
is relative only to starting position of this index. Index direction does not affect this parameter. The Registration Window Start position (or
distance) should be less than the Registration Window End position. If a registration sensor is seen outside of this window (not between the
WindowStart and WindowEnd positions) then it will be ignored.
Window End
This parameter defines the end of the Registration Sensor Valid Window relative to start position of this index. This is an unsigned value and is
relative only to starting position of this index. Index direction does not affect this parameter. The Registration Window End position (or distance)
should be greater than the Registration Window Start position. If a registration sensor is seen outside of this window (not between the
WindowStart and WindowEnd positions) then it will be ignored.
Example: 1
Index 0 is defined as a Registration type of index. The user wants the index to run at velocity for 10 Revs, or until the Torque Feedback reaches
50% continuous torque and then continue for another 0.5 Revs.
In the Limit Distance text box, enter 10.0
On the Registration tab, select the Analog radio button.
In the analog list box, select Torque Command
In the comparison operator list box, select ">"
In the analog value parameter, enter 50 (Units are established on the User Units view)
In the Registration Offset parameter, enter 1.5
This index would accelerate up to it’s target velocity, and run at speed until one of the following:
The Limit Distance is approaching, and the index decels down to zero velocity, completing the move at the Limit Distance. At this point, the
Index.#.LimitDistHit source would activate. Or,
The Torque Command reaches or exceeds 50% continuous, and the index continues at speed before decelerating to zero velocity at the
registration point plus the Registration Offset distance.
If the Registration Offset distance is in the opposite direction from the move, or is so short that the motor cannot stop in the specified distance
at the programmed deceleration rate, the motor will decelerate with the programmed ramp, and then back-up to the specified position
(registration point + the Registration Offset).
3.36.2 Index Sources and Destinations
Sources
Index.AnyCommandComplete
Active when any index motion command is completed. If a stop is activated before the index has completed, this source will not activate.
Deactivated when any new index command is initiated.
Index.#.Accelerating
This source is active while an index is accelerating to its’ target velocity. Once the index reaches the target velocity, or begins to decelerate,
the Index.#.Accelerating source will deactivate.
Index.#.AtVel
This source activates when the target index velocity is reached. If Feedrate override is changed or FeedHold is activated AtVelocity shall
remain active. Index.#.AtVel will deactivate at the start of any deceleration or acceleration. During a synchronized index, this source could be
96
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
active even without any motor motion if the master axis stops.
Index.#.Command Complete
The Index.#.CommandComplete source will activate when the specific index completes its deceleration ramp. It will remain
active until the specific index is initiated again. If the drive stop destination is used during an Index, then the
Index.#.CommandComplete will not activate.
Index.#.Command In Progress
The Index.#.CommandInProgress source is active throughout an entire index profile. The source activates at the beginning of
the index acceleration ramp, and deactivates at the end of the index deceleration ramp. During a synchronized index, this
source could be active even without any motor motion if the master axis stops.
Index.#.Decelerating
This source is active while an index is decelerating from its’ target velocity. Once the index reaches zero velocity, or its’ next
target velocity, the Index.#.Decelerating source will deactivate.
Index.#.LimitDistHit
Activated when the registration sensor is not found before the Limit Distance is traveled. If the Registration Window is enabled
the sensor must be activated inside the window to be recognized.
Index.#.PLSStatus
Controlled by the PLSOn and PLSOff Points which are relative to the distance commanded since the start of the index.
Activated when index distance command is in between the PLSOn point and PLSOff points.
Index.ProfileLimited
For timed indexes, if the values for Max. Velocity, Max. Acceleration, and Max. Deceleration are such that the distance cannot
be covered in the specified time, the Index.ProfileLimited flag will activate when the index is initiated, indicating that the index
cannot be performed as desired. The Index.ProfileLimited flag will remain active until cleared using the
Index.ResetProfileLimited assignment or program instruction. In this situation, the index will still operate, but the time will be
extended. In other words, the profile will be performed using the maximums values and still cover the specified distance, but
not in the specified time.
Destinations
Index.ResetProfileLimited
If a timed index was not able to complete in the specified time, the Index.ProfileLimited source will activate.
Index.ResetProfileLimited is used to clear the ProfileLimited flag and acknowledge that the index did not complete in the
specified time. This can be activated through an assignment, or through a user program. This function is edge-sensitive, so
holding it active will not prevent ProfileLimited from activating.
Index.#.Initiate
The Index.#.Initiate destination is used to initiate the specific index. The Index is initiated on the rising edge of this function. An
Index cannot be initiated if there is an Home, Jog, or Program in progress, or if the Stop destination or if a travel limit is active.
It can be activated from an assignment or from a program.
Index.#.Sensor Trigger
If registration to Sensor is selected, when this destination activates, motor position is captured and is used as the registration
point for registration type indexes.
3.36.3 Adding and Deleting Indexes
Adding or removing indexes from the user configuration can be done in three ways. Indexes may only be added or deleted
while offline.
Toolbar button Method
The Add Index button (shown below) will add a new index to the user configuration. Indexes are added in sequential order.
Clicking on the button will add an index and bring you to the Index setup view allowing you to enter the index parameters.
The Delete Index button (shown below) will delete an index from the user configuration. The highest numbered index will
automatically be deleted unless a different index is selected on the Indexes heading screen. To delete a specific index, click on
the Motion\Indexes branch in the Hierarchy Tree. From this view, select the specific Index you wish to delete, and then click on
the Delete Index button.
PowerTools Pro Menu Bar Method
Adding an Index
From the PowerTools Pro menu bar, select Edit/New/Index. An index will be added in sequential order and you will be brought
to the Index setup view allowing you to enter the index parameters.
Deleting an Index
Navigate to the Indexes View, and select the Index you wish to delete. From the PowerTools Pro menu bar, select Edit/Delete/
Index. The selected Index will be deleted from the configuration.
Epsilon EP-P Drive Reference Manual
Revision A3
97
www.emersonct.com
Right Click Method
Adding an Index
Navigate to the Indexes View. Position the mouse pointer in the right side of the view and right-click the mouse. A selection box will appear
allowing the user to add a New Index or Delete an Index. Click on New Index and an index will be added in sequential order and that Index’s
setup view will open allowing the user to enter the index parameters.
Deleting an Index
Navigate to the Indexes View. Select the Index you wish to delete, and then right-click the mouse. A selection box will appear allowing the user
to add a New Index or Delete an Index. Click on Delete Index and the selected index will be deleted from the configuration.
3.37
Gearing View
Figure 110:
Gearing View
3.37.1 Use Scale Check Box
Select this check box (Gear.UseScaleEnable) to enable the Scaling feature and disable Gear Ratio. Scaling allows the user to use irrational
ratios such as 1.0/7.0 that were not possible with the single parameter ratio (Gear.Ratio). Scaling is defined as follows:
Scaling =
Gear.ScaleNumerator (User Units)
Gear.ScaleDenominator (Master Units)
3.37.2 Gear Ratio
Gearing is used to fix the motion of the motor to the motion of the master axis signal at a specified ratio. This is commonly called “electronic
line shafting” or “electronic gearing”. To gear the motor to the master axis, a ratio must be specified as a relationship between follower distance
units and master distance units. The ratio is as follows:
Gear Ratio =
# of Follower Distance Units
1 Master Distance Unit
The ratio (Gear.Ratio) is defined as the number of follower distance units to move the motor per master distance unit of travel. The master
distance units are configured on the Master Units view. The gear ratio can be positive or negative and is a signed 32-bit parameter. The
resolution of the parameter is determined by the number of decimal places configured for the Master Velocity Units on the Master Units view
By default, gearing does not use acceleration or deceleration ramps with respect to the master encoder. This means that once gearing is
activated, peak torque is available to try to achieve the specified gear ratio. Therefore, if the master axis is already in motion when gearing is
activated, the control loop will attempt to accelerate the motor to the programmed ratio within one update (800µsec < update rate <1600 µsec).
Analogously, when gearing is deactivated, the motor will use peak torque to bring the motor to a stop without a deceleration ramp.
3.37.3 Direction
Direction allows the user to select which master axis command the follower is going to follow and the choices are Bidirectional, ComMinus and
ComPlus.
Bidirectional
The follower will follow both the plus and minus master axis command.
ComMinus
The follower will follow only the minus master axis command.
ComPlus
98
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The follower will follow only the plus master axis command.
3.37.4 Acc/Dec Group
Acceleration and Deceleration ramps may be enabled on the Gearing view as seen in Figure 110 above. If enabled, the accel
and decel ramps are specified in units of Follower Units / Velocity Time Base / Acceleration Time Base. Note that this is a
Realtime ramp. Therefore, the time that it takes to reach the programmed ratio depends on how fast the master is traveling
when gearing is activated. Figure 111 below demonstrates that the faster the Master Velocity, the longer it will take to reach the
programmed ratio. If the Master Axis is not moving when gearing is initiated, then the follower locks into its programmed gear
ratio instantly (no acceleration time required).
Figure 111:
Gearing Acceleration Ramp Description
The Gear.Ratio/Scaling can be changed on the fly (while in motion), but acceleration or deceleration must be enabled to use
ramps to achieve the new ratio. If gearing accel and/or decel ramps are not enabled, the motor will attempt to achieve the new
ratio in one trajectory update (800<t<16000 microseconds).
Initiating Gearing Motion
Gearing can be activated through an Assignment, or from a program instruction (Gear.Initiate). If initiated from an assignment,
the Gear.Activate destination is a level-sensitive event. This means that gearing will be active as long as the source to which it
is assigned is active. If gearing from a program, the Gear.Stop instruction is used to stop the gearing motion.
Stopping Gearing Motion
The method used to stop gearing motion depends on how the gearing was initiated. If gearing was initiated using an
Assignment, then simply deactivating the Gear.Active destination will cause gearing motion to stop. If gearing was initiated
from within a program, then the Gear.Stop command must be used to stop gearing. If gearing motion is operating on Profile.1,
then the On Profile.1 motion modifier must be used after the Gear.Stop instruction. See Multiple Profiles on page 103 for more
information.
Distance Recovery when Gearing
If accel ramps are used, the gear will lag the master when Gear.AtVel is activated. The total lag distance will be stored in
parameter Gear.RecoveryDist. This parameter value can be loaded in to Index.#.Dist and that Index is ran on the other profile.
An alternative method is to enable the Distance Recovery feature on the Distance Recovery view. With Distance Recovery
enabled.
3.38
Camming View
Electronic cams provide a non-linear motion function for a single axis. The basic motion can best be illustrated in Figure 112 of
a mechanical cam and cam follower (or slave).
Epsilon EP-P Drive Reference Manual
Revision A3
99
www.emersonct.com
180
225
270
MASTER
AXIS
FOLLOWER AXIS
(SLAVE)
315
0
45
90
135
180
Figure 112:
Mechanical Master and Slave Follower
As the master axis (the cam lobe) rotates, the follower axis produces a non-linear motion profile. This same profile can then be produced with
a single motor driving a linear axis programmed with an electronic cam.
The cam motion object uses a master/follower principal in a synchronized mode and also has a follower with Realtime mode that allows the
follower to travel through its cam table without a physical master axis moving.
Control Techniques provides a Cam as a collection of cam table(s) that can be used individually of chained together to form a full sequence of
motion. Each cam table is a user specific sequence of movements whereby the user can specify the master and follower movement along with
the interpolation type. Coupled with a user program to monitor the flow, the motion can dynamically be altered by changing the cam table
chains selecting a different sequence of tables. You can further adjust the flow by dynamically changing the cam tables themselves or using a
cam table time base index to adjust time or distance.
As an alternative, the cam is initiated in the same manor as jogs, home and indexes.
Figure 113:
Camming View
Cam Number
Use the arrows of the spin box to increment or decrement the Cam Number and view the setup information for that Cam number. A maximum
of 32 different cam tables can be created.
100
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Name
The user can specify a cam name (Cam.#.Name) of up to 12 alphanumeric characters. This allows assigning a descriptive
name to each cam table indicating different machine operations.
Cam Type
Cam type (Cam.#.CamType) allow the user to choose from; Master Follower, Absolute MFI, Incremental MFI, Cubic Spline, or
Time Based Index cams. Most data entries are “Absolute” which means each point is an absolute distance from the start of the
cam table which is an implied zero, although the starting value does not have to be zero. The Incremental MFI (Master/
Follower/Interpolation) has the entries as distance deltas from point to point which means the point is relative to the previous
point.
Master Follower
Master Follower is an Absolute Master Follower with a fixed interpolation type of Linear for each point. This is convenient
when there are many points entered or are importing data from a CAD system. A large number of data points are required for
smooth motion.
Absolute MFI
Absolute MFI allows a different master, follower, and interpolation for each point in the cam. The values are in reference to the
beginning of the cam table (position zero). The master positions must increase from point to point since change in master
position must always be increasing.
The position interpolation types that are valid in this mode are:
Linear – Constant velocity across the complete point.
Square – Velocity increases or decreases linearly across the point. This means that the position changes quadratic across
the point.
S-curve - The velocity and position change along a sinusoidal shape across the point
Cosine – The velocity starts and ends at the same velocity, but increases or decreases along a sinusoidal shape in order
that the proper final position is achieved
Jerk Free – The jerk starts and ends at zero. Jerk increases or decreases in smooth transition.
Incremental MFI
Incremental MFI is different from Absolute MFI in that each point is a delta position. This allows values in the middle to be
modified.
3.38.1 Cam Table Plot Error
Figure 114:
Cam Table View With a Smilely Face
When the Master and Follower parameter values are entered into the cam table the graph is updated to reflect these values. If
Epsilon EP-P Drive Reference Manual
Revision A3
101
www.emersonct.com
PowerTools is unable to plot the graph due to these values a smilely face will appear in the graph area of the view. To correct this error just
change parameter values until the smilely face is cleared and the plot appears.
3.39
Torque Mode View
Torque Mode is a mode where the drive is controlled by torque command rather than a position command. The drive can switch between
position and torque mode. Note that when in torque mode, there is no following error.
Torque Mode can be velocity limited. If there is not enough back force to keep the motor velocity below the velocity limit, the torque mode will
switch into and out of a velocity limiting mode as needed.
The Velocity Limiting has values and enables for acceleration and deceleration. This allows for position control integration with compound and
blended Indexes. We recommend using the graphical monitor to debug your motion integration.
Figure 115:
Torque Mode - Online
3.39.1 Torque Mode Settings Group
Torque Command
This parameter (TorqueMode.TorqueCommand) value is the torque level that will be applied when Torque mode is activated.
Peak Torque
This is a read only parameter displays the peak torque available from the selected drive and motor combination.
3.39.2 Velocity Limiting Settings
Velocity Limit Enable Check Box
This check box (TorqueMode.VelocityLimitEnable) when selected will enable the velocity limiting feature in Torque mode.
Max Velocity
This parameter (TorqueMode.VelocityLimit) value is the maximum limit of the velocity when velocity limit enable is enabled.
Hysteresis
When velocity is limited, this parameter (TorqueMode.TorqueModeHysteresis) is the value that the velocity must drop to before the drive
returns to toque mode.
Acceleration Check Box
Select this check box (TorrqueMode.AccelEnable) when an acceleration ramp is desired.
Acceleration
This parameter (TorqueMode.Accel) is the acceleration ramp for the velocity limit feature, when enabled.
Deceleration Check Box
Select this check box (TorrqueMode.DecelEnable) when an deceleration ramp is desired.
102
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Deceleration
This parameter (TorqueMode.Decel) is the deceleration ramp for the velocity limit feature, when enabled.
3.40
Multiple Profiles
Motor motion or "Axis" motion may be generated from either of two Profiles: Profile.0 and Profile.1. Each of these Profiles can
run any type of motion (i.e. Index, Jog, Gear, etc.) at any time. Both of the Profiles can generate motion simultaneously. For
example while Gearing, an incremental index can be initiated "on top" of the Gear velocity. The sum of both Profiles provides
the motors commanded position and this parameter is called PosnCommand.
In order to run motion on both Profiles, a program must be used. To specify which profile a motion object runs on, the On
Profile instruction is used. The default Profile is Profile.0 and therefore it is unnecessary to specify On Profile.0 in user
programs. If no Profile is specified, the default profile is used. For example, a user program that initiates an index on
Profile.0. The following two program lines will generate the same result.
Index.0.Initiate
and
Index.0.Initiate On Profile.0
Both of these lines of code will initiate Index 0 on Profile 0. The first one uses Profile 0 because it is the default profile, and the
second one uses Profile 0 because it is specified. The On Profile.0 command is completely optional, but may be used for
clarity.
To run a motion object on the other profile (Profile 1), we must specify the use of Profile 1. The following program line will
perform Index 0 on Profile 1.
Index.0.Initiate On Profile.1
Any motion may be run on either Profile, but running the same motion object on both profiles simultaneously is prohibited. For
example, it is illegal to run Index 0 on Profile 0 and on Profile 1 at the same time.
Illegal:
Index.0.Initate
Index.0.Initiate On Profile.1
Legal:
Index.0.Initiate
Wait For Index.0.CommandComplete
Index.0.Initiate On Profile.1
Any two motion objects can be run on both profiles at the same time. For example, it is legal to run Index 0 on Profile 0 and
Index 1 on Profile 1 at the same time.
Legal:
Index.0.Initiate
Index.1.Initiate On Profile.1
The distance and velocity of the two indexes is summed to generate the overall position command and velocity command for
the motor.
All motion run from the Assignments view is automatically run on Profile 0. It is not possible to change the Profile on which
motion run from the Assignments view operates. Therefore in order to run motion from both the Assignments view and from a
program simultaneously, motion initiated by the program must be run on Profile 1.
The Profile view allows the user to view the Position Command and Velocity Command for each profile individually. An
example of this view is shown below.
Epsilon EP-P Drive Reference Manual
Revision A3
103
www.emersonct.com
Figure 116:
Profile View - Online
The following example program code runs Index 0 on Profile 0, Wait for 1 second, and then initiate Index 1 on Profile 1. The diagram shows
how the two profiles look individually, and then shows how the motion looks after being summed by the two profiles.
Index.0.Initiate
Wait For Time 1.00 ‘Seconds
Index.1.Initiate On Profile.1
Wait For Index.1.CommandComplete
DriveOutput.1 = ON
If using the “On Profile” command on the same line of code as the “Using Capture” command, “Using Capture” should precede the “On Profile”
command. Below are example lines of program code that initiate indexes on different profiles using captured data for the starting point.
Initiate Index 1 on Profile 0 using data stored in Capture object 2 as the starting point.
Index.1.Initiate Using Capture.2
Initiate Index 3 on Profile 1 using data stored in Capture object 1 as the starting point.
Index.3.Initiate Using Capture.1 On Profile.1
3.41
Stopping Motion
3.41.1 MotionStop from a Program
The MotionStop command will cause all motion to stop regardless of what type of motion it is, or where it was initiated from. Upon activation of
the MotionStop, all motion will begin to decelerate to a stop using the standard Stop deceleration ramp. That ramp is defined using the
StopDecel parameter. MotionStop is a level sensitive command meaning that as long as it is active, all motion will be stopped and prevented
from running. When MotionStop is deactivated, all motion is permitted again. Any motion that is interrupted with the MotionStop command is
cancelled, and will not complete when MotionStop deactivates.
The MotionStop command DOES NOT stop any programs. All programs that are active when the MotionStop is activated will continue to run
as normal.
All motion stopped using the MotionStop command will stop using a realtime deceleration ramp (even if the timebase of the motion being
stopped is synchronized). This can help in applications that use synchronized motion if the master stops and then the user wishes to break out
104
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
of the synch motion without performing an synchronized deceleration ramp.
Neither the CommandComplete signals from motion objects nor the ProgramComplete signals will activate if they have been
stopped using the MotionStop command.
In the example below, Program 0 runs an infinite loop in which Index 5 runs and then waits for half a second and then repeats
itself. When Input 2 activates, Index 5 will stop if in progress and the program will loop back to the Index.5.Initiate.
Example: 1
Program 0 – Running on Task 0
Do While TRUE
Index.5.Initiate
Wait For (Index.AnyCommandComplete OR MotionStop = ON)
Wait For Time 0.50 ‘Seconds
Loop
Program 1 – Running on Task 1
Wait For DriveInput.2 = ON
MotionStop = ON
Wait For DriveInput.2 = OFF
MotionStop = OFF
3.41.2 MotionStop from an Assignment
The MotionStop as explained above can also be initiated from an Assignment. MotionStop can be found in the Ramps group of
Destinations.
3.41.3 Profile.#.MotionStop from a Program
The Profile.MotionStop instruction is used to stop motion on an individual profile without stopping all motion. Upon activation of
the Profile.MotionStop, any motion running on the specified profile will begin to decelerate using the StopDecel ramp down to
zero velocity. The deceleration is performed in realtime regardless of the timebase of the active motion. This can be used in
applications where motion is being run on both profiles simultaneously, and the user only wishes to stop one of the motion
types. For example, an application that uses gearing to follow a master encoder and then uses indexes on the other profile to
do correction profiles. The application may call for stopping all correction moves, but continuing the gearing motion. In this
application, the user would perform a Profile.MotionStop on the profile doing the correction moves. The below example uses a
separate program to control the Profile.Stop.
The Profile.MotionStop instruction does not stop the program that the motion is initiated from.
The Profile.MotionStop is level sensitive so that when it is activated, all motion on that profile will stop, and remain stopped,
until the Profile.MotionStop is deactivated. If the Profile.MotionStop is activated, it will stop any motion in progress, and will
also prevent any new motion from starting on that profile. No motion will be permitted on that profile until the profile being
stopped has come to a complete stop. The motion that was stopped while in progress will not resume when the
Profile.MotionStop is deactivated. Level sensitive motion that is initiated from the Assignments view (i.e. jogging, gearing) will
not operate until the activate signal is reset and activated again.
The CommandComplete signal for the motion will NOT activate if the motion was interrupted using the Profile.MotionStop
command regardless of motion type. In the example below, Program 0 would be stuck on the Wait For
Index.AnyCommandComplete instruction if the Profile.MotionStop is used. To avoid this condition, “OR Profile.1.Stop” has
been inserted after the Wait For Index.AnyCommandComplete.
Example: 1
Program 0 – Running on Task 0
Gear.Initiate On Profile.0
Do While TRUE
Wait For DriveInput.1 = ON
Index.1.Initiate On Profile.1
Wait For (Index.AnyCommandComplete OR Profile.1.MotionStop)
Loop
Program 1 – Running on Task 1
Do While TRUE
Wait For DriveInput.2 = ON
Profile.1.MotionStop = ON
Wait For DriveInput.2 = OFF
Profile.1.MotionStop = OFF
Loop
3.41.4 Profile.#.MotionStop from an Assignment
The Profile.#.MotionStop as explained above can also be initiated from an Assignment. Profile.#.MotionStop can be found in
each Profiler group of destinations.
3.42
Network Group
For information on the DeviceNet, Ethernet and Profibus Views, please refer to the Epsilon EP Drive Connectivity Reference
Manual (P/N 400518-04).
Epsilon EP-P Drive Reference Manual
Revision A3
105
www.emersonct.com
3.43
Modbus RTU/TCP View
The Modbus RTU/TCP View is used to assign Modbus addresses to individual parameters.
By selecting Modbus RTU/TCP in the Hierarchy Tree, the Modbus RTU/TCP View will appear on the right (see Figure 117). The right part of
the window displays all of the drive parameters. The number of parameters that appear depends on the User Level.
Figure 117:
Modbus View
An external device such as a Human Machine Interface (HMI) or PLC can be used to monitor or edit individual drive parameters. The Epsilon
EP-P drive uses a 32-bit Modbus RTU communications protocol.
In order to view or modify a parameter, a Modbus address must be assigned to the specific parameter. To do this, locate the parameter you
wish to read/write to or from in the variables list in the middle of the view. Once you have found the proper parameter, click and hold the left
mouse button over the parameter. While still holding the button on your mouse, drag the parameter into the Modbus window area on the right
of the view. Now let go of the mouse button.
The New Assignment dialog box will appear. This will automatically assign the next available modbus address, or allow you to enter a different
Modbus address. Click OK, then you will be able to read or write the parameter at that address.
Figure 118:
Modbus New Address Dialog Box
Address ranges are as follows:
Address Range
Accessibility
Type
Data Size
4xxxx
Read/Write
Register
32 bit word
3xxxx
Read Only
Register
32 bit word
1xxxx
Read Only
Input Bits
bit
0xxxx
Read/Write
Coil
bit
106
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Any individual Modbus address can be deleted by selecting the parameter you wish to delete, and click on the Remove
button. The address selected will be removed from the list. If you wish to delete all of the Modbus addresses that have been
created, then simply click on the Remove All button. All of the addresses will disappear and the Modbus window will be
empty.
Some Modbus addresses have been reserved and can not be assigned: 39980-39999 and 49501-49999.
NOTE
Some configuration software uses a 6 digit addressing base. The first digit is an indication of register or bit type. Thus 400001
in this software is equal to 40001 in Control Techniques Modbus RTU.
3.44
Modbus Master View
Modbus Master provides a method for the Epsilon EP drive to read or write directly to standard compliant Modbus slaves
(such as extended I/O blocks). The process of using this function is to first define the communication path to the slave(s), then
use the user program instructions to directly read or write either bits or words to the identified slave(s).
Configuring Modbus Master
The Modbus Master view, RTU Setup tab allows the user to configure the drive's serial (RS-485) port to operate as a Modbus
Gateway and/or as a Modbus Master. Modbus Gateway check box or Modbus Master check box must be selected otherwise
the port is configured as a Modbus slave. The RTU configuration comprises of two sets of parameters:
•
The serial port configuration (baud, parity and stop bits)
•
The timeouts and gaps for data transmission, see Figure 121 Modbus RTU Timing Diagram on page 108.
Figure 119:
Modbus Master View
Identifying Slaves
Slaves need to be identified before they can be used. The Slaves tab on the Modbus Master view specifies the attributes of
the slave(s). The quantity of slaves can be increased or decreased by changing the "number of slaves" field using the up and
down arrows. This will add or remove slave entries.
Each slave entry identifies how the drive can reach the slave, its unit ID, data representation and Modbus specific timing
attributes, see Figure 121 Modbus RTU Timing Diagram on page 108 for more details.
Epsilon EP-P Drive Reference Manual
Revision A3
107
www.emersonct.com
Figure 120:
Modbus Master View - Slave Tab
Master
Slave
∆a
Figure 121:
∆b
∆c
∆d
Modbus RTU Timing Diagram
a - Response Gap - Specifies the maximum timeout for the response packet. If a response packet is not detected within this
period then the slave device status is set to no_response.
b - Inter Character - Specifies the maximum period for receiving each character of the Modbus packet. If a character is not
received during this period, then the master considers the partial packet incomplete, and sets the slave device status to
no_response.
c - Inter Frame - Specifies the period of no data transmission indicating the end of the Modbus packet. Modbus specifications
generally specify this gap to be 3½ characters wide. If data is received during this period, then it is considered a part of the current
data packet.
d - Message Gap - Specifies idle period between the last packet received and the next packet transmitted. This gap allows for
extended quite time for multiple slaves on the same communications path; where slaves may be actively monitoring Modbus
packets and may miss the standard Inter Frame gap.
108
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.45
DeviceNet View
For those drives that have the DeviceNet option, please refer to the Epsilon EP Drive Connectivity Reference Manual, P/N
400518-04, which can be found on the Control Techniques MME Power CD.
3.46
Profibus View
For those drives that have the Profibus option, please refer to the Epsilon EP Drive Connectivity Reference Manual, P/N
400518-04, which can be found on the Control Techniques MME Power CD.
3.47
Ethernet View
This view is used to navigate through the Ethernet related setup for the Epsilon EP-P drives. The Epsilon drive needs a
minimum of an IP address and Subnet Mask configured before attacking it to an Ethernet hardware setup. For more
information please refer to the Epsilon EP Drive Connectivity Reference Manual, P/N 400518-04, which can be found on the
Control Techniques MME Power CD.
Epsilon EP-P Drive Reference Manual
Revision A3
109
www.emersonct.com
110
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
4
4.1
Programming
Programs
Programs are a series of indexes, homes and jogs that have been previously setup. You combine these with other
programming steps to create a complex motion profile. Each motion program provides a series of movements in conjunction
with other machine functions. The movements are used to perform a particular machine operation.
Multiple programs can be created using PowerTools Pro software and stored in the Epsilon EP-P drive. The drive is capable of
storing up to 100 indexes, 99 motion programs, and a maximum of 1024 program steps in Flash Memory. The amount of
available Flash Memory determines how many programs, program steps, indexes, etc. that the configuration can hold.
The number of available programs and average number of steps per program are directly related to each other. The memory
is setup such that if you require 99 programs (maximum), each program can have an average of 10 program steps each. If the
number of programs is reduced to a minimum, you could have as many as 1024 steps in a single program.
Expanding Programs in the Hierarchy Tree the user will notice there is three types of programs. Cyclic Programs, User
Programs (Programs), and Real Time Programs.
A Cyclic Program is designed to execute over several update rate cycles, utilizing a specified amount of the update rate time
and a specified number of update rate cycles. CyclicProgram.#.EnableProgram must be activated to initiate the Cyclic
Program.
A Real Time Program is designed to execute to completion in a single update rate cycle. RealTimeProgram.#.EnableProgram
must be active to initiate the Real Time Program.
User Programs can be initiated either using the Program.#.Initiate destination or the program instruction. User Programs use
as many update rate cycles as needed to complete the program.
4.2
Program Toolbar Buttons
Following is a detailed description of each of the buttons found on the Program Toolbar. These buttons will help the user edit
programs as well as debug errors and troubleshoot program functionality. Some of these buttons are only available when
online with the drive and others are not available in a Real Time or Cyclic programs.
Undo Last Change
This button will undo the last change made to the program. PowerTools Pro will save up to ten of the last
changes performed in the program.
Redo Last Change
This button will redo the last change that was undone. PowerTools Pro will save up to ten of the last changes
that have been undone in the program.
Find
This button allows the user to search for a given string inside the program. Modifying several parameters in the
Find dialog box (i.e. Search Up, Search Down, Match Case, etc.) can customize the search.
Find Next
This button will find the next instance of the string last searched for. This allows you to quickly find all the
matches to your search with out re-entering the selected word.
Book Mark
This button will insert a bookmark on the line of code on which the cursor is placed. Bookmarks allow the user
to mark certain sections of the program for easy access to at a later time. The next BookMark and Previous
BookMark buttons can be used to jump from one bookmark to the next very quickly. If this button is clicked
when a bookmark already exists on the line of code, the bookmark will be removed.
Next Book Mark
This button will position the cursor on the next available bookmark ahead of the cursor in the program.
Previous Book Mark
This button will position the cursor on the previous bookmark behind the cursor in the program.
Delete All Book Marks
This button will delete all of the bookmarks in the program. To delete only a single bookmark, place the cursor
on the line for which you wish to delete the bookmark, and click on the Book Mark button.
Red Dot Help
If a user program contains an error, the realtime program parser will detect it, and place a red-dot next to the
line of code with the error. For help on what the particular error is, click on the Red Dot Help button, and then
click on the line of code with the red-dot next to it. PowerTools Pro will attempt to give a detailed description of
the error.
Red Dot Help can also be used to read the status of a program variable. Click the Red Dot Help button to activate Red Dot
help, then click on the variable in the line of code in the program text. The line of code selected must not have a red dot
because the error will take precedence.
Epsilon EP-P Drive Reference Manual
Revision A3
111
www.emersonct.com
After clicking on the variable a yellow popup window displays information about the variable.
•
When online it will display the current values for the variable
•
A short description of the variable is displayed
•
It will display the initialization value set in the application by the view settings
•
It will display the range for numerical data, selection options for selections, Boolean options for Booleans
•
If the variable is read only
Drag In I/O
Clicking on this button will open the Select EPP Inputs/Outputs window. From this window, the user can drag Drive Input/Output
lines of text into the program. This feature can be used to minimize the need to type in program statements. The Input or Output
state (i.e. =On or =Off) can also be dragged into the program from this window.
Drag In Operands
This button will open the Select Math Operator window. From this window, the user can drag formula Operands (i.e. +, -, /, *)
into the program formula.
Drag In Variables
This button will open the Select Variables From Tree window. From this window, the user can find any variable they wish to use
in a program, and simply drag it into the program code. This list will easily allow you to find any of the available pre-defined
variables in the Epsilon EP-P drive. The available parameters shown in the window depends on the selected Program User
Level.
Lock Program
Toggling this button will lock and unlock the program for editing. When locked, the user is not able to modify the program code.
After downloading, the program automatically locks to prevent the user from inadvertently changing program statements. To
unlock the program, simply click the button.
Run This Program
Clicking on this button will automatically initiate the program that is currently being viewed. The drive must first be enabled in
order to run a program. Only available while online.
Program Where Am I?
Clicking on this button will show the line of the program that is currently being executed. A blue arrow will point to the line in the
program that was executing when the button was clicked. The arrow will not continue to follow program flow. If the program is
not currently running, then the arrow will point to the top of the program, or to the last line of the program that was processed
before it was stopped. Only available while online.
Stop All
This button is the same as the Stop destination found in the Assignments view. Clicking on this button will stop all programs
and motion. If in motion, the motor will decelerate to a stop using the StopDeceleration ramp value. Only available while online.
Disable Error Check
This button can be used to temporarily disable the program parser. The parser is what detects errors in a user program. When
user programs are very large, the parser can take an appreciable amount of time to check the entire program for errors. To
avoid this, the user can disable the program parser, enter all of the changes, and then re-enable the parser to check for errors.
112
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Cyclic Program View
The Cyclic Program initiation is synchronized to a multiple of the update rate cycles. Therefore it provides a deterministic cycle
time that is repeated automatically. The Cyclic Program executes over multiple update rates and therefore has a reduced
program instruction set compared to Real Time programs.
Figure 122:
Cyclic Programs View
Program Name
This is a 12 character string that the user can assign to an individual program. It allows the user to give a descriptive name to
the program for ease of use.
Update Rate
This parameter defines the number of Update rates the cyclic program has to finish. This parameter can only be setup on the
Cyclic Program view.
Utilize
Utilize is the percent of the Control Loop time utilized for control loop, Real Time Program and a portion of the Cyclic Program.
When this limit is hit, the cyclic program is suspended until the next control loop. The percentage left over will processes user
programs, communications and other processes. To prevent complete starvation of user programs and communications, the
execution of the Cyclic Program is spread out over several control loops based on the Utilize percentage.
The drive’s CPU time is allocated between the background processes and the foreground control loop interrupt. The control
loop interrupt executes event updates, motion calculations, the complete real time program and a portion of the cyclic program
up to the Utilize percentage of the trajectory rate. Then the control loop interrupt is exited and the background processes
continue to run.
No matter how low the Utilize percentage is set, the required control loop motion calculations will be completed, the Real Time
Program will run to completion, and at least one cyclic instruction will be executed. If these do not complete, a real time
program timeout fault is generated. A Cyclic Program Timeout Fault occurs if the cyclic program has not completed at the next
Cyclic Program Initiate.
In actuality the Cyclic Programs are initiated from the control loop but are run outside the control loop interrupt. They run as
processes along with user programs, but at a higher priority so cyclic programs are run before any user program. Other
processes may run at lower or higher priorities. These include processing the communications. The cyclic programs are
suspended and resumed based the utilize percentage and trajectory rate.
Epsilon EP-P Drive Reference Manual
Revision A3
113
www.emersonct.com
User Program View
Click on Programs\Program#, the program view will appear on the right (see Figure 123). The left side (pane) of this view contains the program
instructions. The right side of the Programs view contains the Program Toolbar above the program code area.
Figure 123:
Programs View
Program Name
This parameter (Program.#.Name) is a 12 character string that the user can assign to an individual program. It allows the user to give a
descriptive name to programs for ease of use.
Program Number
This spin box allows the user to create additional programs. Unlike the motion views, to get to Program1 you must use the arrows of the spin
box.
Task Number
This parameter (Program.#.TaskNumber) allows programs to run simultaneously. To run one program (for example, Program1) while another
program (Program0) is executing, Program0 will be set for Task Number 0 and select Program1, click on the up scroll arrow of the Program
Number to Program 1 then click on the up arrow of the Task Number to number 1.
Use the up and down arrows next to the Task Number to change the Task Number. To create a new Task, simply click on the up arrow until
PowerTools Pro asks if you wish to create a new Task. The maximum number is up to four different tasks in a single application.
If the user wishes to operate two programs simultaneously, the two programs must be assigned to two different tasks. Multiple programs can
be assigned to the same task if desired, but that means that the two programs cannot be run at the same time. If a given program calls another
program, then the calling and the called programs must be on the same task. All programs default to task zero and therefore will not run
simultaneously unless specified to do so.
Run Anytime Enable Check Box (Programs only)
Some applications require the ability to run a program as soon as a fault occurs or continue running a program even through a fault condition.
In order to do this, a program must be classified as "Run Anytime". To define a program to be able to run during a fault or while the drive is
disabled, the "Run Anytime" check box must be enabled (selected) in the Program view or Program.#.RunAnytimeEnable can be activated in
a program.
NOTE
Note: If a Program Fault occurs the program will stop executing regardless of the "Run Anytime" setting.
Global Where Am I Check Box (Programs only)
This parameter (Program.#.GlobalWhereAmIEnable) is used to control the functionality of the Global Where Am I arrow in a user program. If
the user activates the Global Where Am I feature by clicking the Global Where Am I button on the PowerTools Pro toolbar, a blue arrow will
follow the program flow on a given task by pointing to the line of the user program that is currently being processed. If the Global Where Am I
is active, and one user program calls another user program (using the Call Program instruction), the PowerTools Pro view will automatically
114
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
switch to the “called program”. In some cases it may be desirable to stop the screen from automatically changing to the “called
program”, this can be done by disabling (clearing) the Global Where Am I Enable check box. When clear, the Global Where
Am I feature will not function within the specific program. Each program has its own Global Where Am I Enable check box. By
default, all Global Where Am I Enable check boxes are selected (active).
Real Time Program View
The Real Time program is designed to be executed to completion in every update rate cycle. The real time program instruction
set is reduced to insure all the operations are completed within the update rate.
Figure 124:
Real Time Programs View
Program Name
This is a 12 character string that the user can assign to an individual program. It allows the user to give a descriptive name to
the program for ease of use.
4.3
Program Multi-Tasking
Many applications require the operation of a background task that operates outside of the main program loop, but must be
consistently processed. For instance, a background task that performs calculations for values sent to an operator interface or
a background task that monitors parameters for fault detection.
The Epsilon EP-P processor has the ability to execute multiple tasks. Because only one task can be processed at a time, a
process called time slicing must be used. Time Slicing is simply splitting the total processing time between multiple tasks. The
processor stops all tasks and updates the control loop every 1600 microseconds (default, update time may be set by user).
Inside the control loop update, the drive updates the motion trajectory, captured data, digital inputs and outputs, and other
control parameters. Between each control loop update, the drive processes messages (i.e. Modbus, Ethernet, Faults, etc.)
and then runs as much of the user programs as possible until the next control loop update begins. Each update, a different
task is processed, and therefore how long it takes a given user program to complete depends how many tasks have been
created.
Control Loop Update
Messages
User Program Execution
T0
T1
T2
TN
Update Rate
Figure 125:
Time Slicing and Multiple Tasking Handling
The task assignment is done on the program view. Figure 123 shows the program view with the Task Number parameter. Use
the up and down arrows next to the Task Number to change the value. To create a new Task, simply click on the up arrow until
PowerTools Pro asks if you wish to create a new Task.
The Epsilon EP-P drive allows up to four different tasks in a single application.
Epsilon EP-P Drive Reference Manual
Revision A3
115
www.emersonct.com
If the user wishes to operate two programs simultaneously, the two programs must be assigned to two different tasks. Multiple programs can
be assigned to the same task if desired, but that means that the two programs can not be run at the same time. If a given program calls another
program, then calling and the called programs must be on the same task. All programs default to task zero and therefore will not run
simultaneously unless specified to do so.
Timing Diagrams
In Figure 125 the update rate is set to 1600 microseconds (Found on the Setup View). The first routine to be processed in the update rate is
the control loop update. Next, all messages will be handled. If no message has been sent from a Modbus master and no faults are active, then
this step is skipped. After all messages are processed, then execution switches to the user programs. The user programs are assigned to
tasks, and the tasks are handled in ascending order starting with task 0. If a task has been assigned, but not initiated, then that task can be
skipped. After 1600 microseconds has passed, the task is stopped, and the process is repeated using the next available task. Once each task
has been processed (depends on how many have been assigned by the user), the whole process starts over at the first task. This process is
accurate as long as no program is blocked. The following figure shows examples of user programs and task numbers and how the drive
processes them.
Control Loop + User Program on one Task
Control Loop
User Program
T0
T0
T0
T0
T0
T0
Update Rate
Control Loop + User Programs on two Tasks
Control Loop
User Program
T0
T1
T0
T1
T0
T1
Update Rate
Control Loop + User Programs on three Tasks
Control Loop
User Program
T0
T1
T2
T0
T1
T2
Update Rate
Control Loop + User Programs on two large Tasks
Control Loop
User Program
T0
T0
T0
T1
T1
T0
Update Rate
Figure 126:
Diagram of User Programs with Multiple Tasks
116
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
The following three figures are timing diagrams of a cyclic program with different utilization values (showing the effect) and a
user program initiated to run on a single task.
Cyclic Program Utilization
set to 80%
Control Loop + Cyclic Prog + User Prog on one Task. Cyclic
Program Utilization set to 80% means cyclic program is suspended
after 80% of update is reached, then resumed next update
Control Loop
Cyclic Program
T0
User Program
T0
T0
T0
T0
T0
Update Rate
Cyclic Update = 3x Update Rate
Figure 127:
Diagram of User Program and a Cyclic Program
Cyclic Program Utilization
set to 50%
Same as above except Cyclic Program Utilization is set to 50%
instead of 80%. Note that Cyclic Program takes an extra update rate
cycle to complete
Control Loop
Cyclic Program
User Program
T0
T0
T0
T0
T0
T0
Update Rate
Cyclic Update = 3x Update Rate
Figure 128:
Diagram of User Program and a Cyclic Program
Cyclic Program Utilization
set to 40%
Same as above except Cyclic Program Utilization is set to 40%. In
this scenario, Cyclic Program cannot complete within 3 updates and
so Overrun Error occurs in next update. Need less code in Cyclic
Prog, higher Utilization setting, or Larger Cyclic Update Rate setting
Overrun Error
Control Loop
Cyclic Program
User Program
T0
T0
Update Rate
Cyclic Update = 3x Update Rate
Figure 129:
Diagram of User Program and a Cyclic Program
Epsilon EP-P Drive Reference Manual
Revision A3
117
www.emersonct.com
The following two figures are timing diagrams of a cyclic program with different utilization values (showing the effect) and a user program
initiated to run on several tasks.
Cyclic Program Utilization
set to 70%
Control Loop + Cyclic Prog + User Progs on two Tasks. Cyclic
Program Utilization set to 70% means cyclic program is suspended
after 70% of update is reached, then resumed next update
Control Loop
Cyclic Program
T0
User Program
T0
T1
T1
T1
T0
Update Rate
Cyclic Update = 3x Update Rate
Figure 130:
Diagram of User Programs on Two Tasks and a Cyclic Program
Cyclic Program Utilization
set to 70%
Control Loop + Cyclic Prog + User Progs on three Tasks. Note how
when the number of Tasks is the same as the Cyclic Program
Update Rate setting, some programs get shortchanged. This
should be avoided by changing the Cyclic Program Update Rate
Control Loop
Cyclic Program
User Program
T0
T2
T1
T0
T2
T1
Update Rate
Cyclic Update = 3x Update Rate
Figure 131:
Diagram of User Programs on Three Tasks and a Cyclic Program
The two figures show how the Real Time program is executed prior to the user program and how the size of the Real Time program effects the
time left in the update rate for the user program to complete.
Control Loop + Real Time Prog + User Prog on one Task
Control Loop
Real Time Program
User Program
T0
T0
T0
T0
T0
T0
Update Rate
Figure 132:
Diagram of User Program and a Real Time Program
118
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
User program can be "choked" if too much code is put into
real time program
Control Loop
Real Time Program
User Program
Update Rate
Figure 133:
Diagram of User Program and a Real Time Program
When the Real Time program is to large and can not be completed in the update rate time the drive will fault.
Real Time program must complete every update rate. If too
much code is put in realitime program, overrun error can
occur
Control Loop
Overrun Error
Real Time Program
User Program
Update Rate
Figure 134:
Diagram of User Program and a Real Time Program
Figure 135 shows how the Real Time program finishes and the two task user programs are processed.
Control Loop + Real Time Prog + User Progs on two Tasks
Control Loop
Real Time Program
User Program
T0
T1
T0
T1
T0
T1
Update Rate
Figure 135:
Diagram of User Programs on Two Tasks and a Real Time Program
Epsilon EP-P Drive Reference Manual
Revision A3
119
www.emersonct.com
The following three figures show how the drive processes Real Time, Cyclic, and User Programs with different number of tasks.
Cyclic Program Utilization
set to 80%
Control Loop + Real Time + Cyclic + User Program on one Task.
Cyclic Program Update Rate set to 4x Trajectory Update Rate and
Utilization set to 80%.
Control Loop
Real Time Program
Cyclic Program
User Program
T0
T0
T0
T0
T0
T0
T0
Update Rate
Cyclic Update = 4x Update Rate
Figure 136:
Diagram of User Program, a Real Time Program and a Cyclic Program
Cyclic Program Utilization
set to 80%
Control Loop + Real Time + Cyclic + User Programs on two Tasks.
Cyclic Program Update Rate set to 4x Trajectory Update Rate and
Utilization set to 80%.
Control Loop
Real Time Program
Cyclic Program
User Program
T0
T1
T0
T1
T0
T1
T0
Update Rate
Cyclic Update = 4x Update Rate
Figure 137:
Diagram of User Program on Two Tasks, a Real Time Program and a Cyclic Program
Control Loop + Real Time + User Programs on three Tasks.
Cyclic Program fUpdate Rate set to 4x Trajectory Update Rate and
Utilization set to 80%.
Control Loop
Real Time Program
Cyclic Program
User Program
Update Rate
Cyclic Update = 4x Update Rate
Figure 138:
Diagram of User Programs on Three Tasks, a Real Time Program and a Cyclic Program
120
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
4.4
4.4.1
Program Instruction Types
Program Flow Instructions
Break
For Switch instruction, break stops the instruction execution flow and continues execution after the EndSwitch instruction. A
break is required to prevent the Case instruction flow continuing the executing through to the next case or default instructions.
For "Do While” instruction, break stops the instruction execution flow and continues execution after the Loop instruction.
For the “For Count" instruction, break stops the instruction execution flow and continues execution after the Next instruction.
Call Program
This program flow instruction is used to call another program. When the called program finishes the controller picks up where
it left off in the program that called it. This is often used when a section of code is used in multiple places in a program. By
moving the code to another program and calling that program the total number of program lines can be reduced. This can also
make the program easier to understand. Care should be taken not to “nest” more than four program calls due to processor
stack overflow. Therefore, no more than four different programs should be called without returning to the original program.
In the diagram below, => Represents a Call Program instruction
Program0=>Program1=>Program2=>Program3=>Program4 => NO MORE THAN 4!
Example:
Call Program.10
‘Program 10 contains a complex home
‘routine.
Example:
Call Program.100
‘Program 100 contains a “teach position”
‘routine.
Case:
When the Switch expression value and the case number instruction match, all the instructions that follow the case instruction
up to a Break or EndSwitch are executed. This includes instructions following the next case instructions and the default
instruction found. Duplicate "Case number" are not allowed.
Default:
The default is an optional statement within the switch instruction. It must follow all the case instruction within a Switch
instruction. When none of the case instruction numbers match the switch expression value the program instructions following
the Default instruction are executed. They are also executed if there is no break instruction in the previous case statements
Do While/Loop
This program instruction is used for repeating a sequence of code as long as an expression is true. To loop forever use
“TRUE” as the test expression as shown in the third example below. The test expression is tested before the loop is entered. If
the test expression is evaluated as False (0) the code in the loop will be skipped over.
Logical tests (AND, OR, NOT) can be used in the Do While/Loop instruction. Parenthesis “()” can be used to group the logical
tests.
Example:
Do While DriveInput.1=ON
Index.1.Initiate
Dwell For Time 1.000
Loop
‘Repeat the three lines of code below
‘as long as DriveInput.1 is ON.
‘Incremental,Dist=5.250in,Vel=10.0in/s
‘seconds
Example:
Do While (DriveInput.1=ON AND DriveInput.2=OFF)
‘Repeat the three lines of code below
‘as long as DriveInput.1 is ON and
‘DriveInput.2=OFF.
Index.1.Initiate
‘Incremental,Dist=5.250in,Vel=10.0in/s
Dwell For Time 1.000
‘seconds
Loop
Example:
Do While (TRUE)
Index.1.Initiate
Dwell For Time 1.000
Loop
Epsilon EP-P Drive Reference Manual
Revision A3
‘Repeat until the program is halted
‘Incremental,Dist=5.250in,Vel=10.0in/s
‘seconds
121
www.emersonct.com
Else
This program flow instruction is used in conjunction with the If/Then/Endif instruction. If the If/Then test condition evaluates to true the code
after the If/Then and before the Else is executed. If the test evaluates to false the code between the Else and the Endif is executed.
Example:
If DriveInput.1=ON Then
DriveOutput.1=ON
DriveOutput.2=OFF
Else
‘The following two lines are executed if
‘DriveInput.1=ON
‘The following two lines are executed if
‘DriveInput.1=OFF
DriveOutput.1=OFF
DriveOutput.2=ON
Endif
Example:
If (DriveInput.5=ON) Then
Jog.0.Vel = 1.0 ‘in/s
Else
Jog.0.Vel = 0.1 ‘in/s
Endif
‘Set fast velocity if DriveInput.5 = ON
‘Set slow velocity if DriveInput.5 = OFF
End
This program flow instruction is used to halt the execution of the program. It can be used in multiple places within the program. It is not required
on the last line of every program. It is implied that after the controller executes the last line of code in a program the program will halt. It is
commonly used inside of If/Then/Endif constructs to end the program if a certain condition has been met.
Example:
If DriveInput.1=OFF Then
End
Endif
Example:
If DriveInput.1=ON Then
DriveOutput.1=ON
End
Endif
For Count/Next
This instruction is used to execute section of code a specific number of times.
Example:
For Count = 1 to 5
Index.1.Initiate
Dwell For Time 1.000
Next
‘Incremetal,Dist=5.250in,Vel=10.0in/s
‘seconds
Example:
For Count = 1 To 10
Wait For DriveInput.1 = ON
Index.0.Initiate
‘Incremetal,Dist=5.000in,Vel=50in/s
Wait For Index.AnyCommandComplete
DriveOutput.1=ON
‘Turn DriveOutput.1 On
Wait For Time 1.000
‘seconds
DriveOutput.1=OFF
‘Turn DriveOutput.1 Off
Next
Formula
This program instruction can be used to enter a formula or assignment into a program. All parameters are available for use in a formula. They
may be dragged and dropped into a formula, but the program User Level will determine how many appear for dragging and dropping (see the
section on User Level in the Setting Up Parameters chapter). Formulas can also be created by simply typing them into the program. This
instruction was created to inform the user that formulas can be used in a program.
Examples:
Index.1.Vel = 20.0
Index.0.Dist = Index.2.Dist + 0.1
DriveOutput.1 = ON
Index.0.Accel = (Index.0.Accel*1000)+5.00
122
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
For<var>
This program instruction is used to execute a section of code as long as the end number is not reached.
For <variable> = <start> to <end> step <increment>... Next
<variable> = A single user variable that will be set and incremented by this instruction.
<start> = An expression that the <variable> will be initialized to at the start of the instruction.
<end> = A number that is used to exit the For<var> loop. For a positive increment, when <variable> Greater than or equal
to <end> the loop is exited. For negative increment, when <variable> is Less than or equal to <end> the loop is exited.
<increment> = An expression that the <variable> will be incremented by at the end of the loop. Expression is a
mathematical formula including variables, numbers, and math operators that represent a single value when executed.
Example:
For var.var0 = 1 To 20 Step .5
Next
The Break instruction is allowed within the For<var> instruction loop.
GoTo
The GoTo instruction is used in conjunction with the Label: instruction to cause program flow to transfer to a specified location
within a program. The destination label is allowed to be above or below the GoTo instruction within the same program. It is not
possible to GoTo a label outside of the program containing the GoTo instruction, nor is it possible to use a GoTo/Label: to exit
out of a For Count/Next loop. In either of these conditions, a RedDot error will be generated.
The Label to which program flow transfers is a character string up to 50 characters in length and can be made up of any
alphanumeric character. The label name must not start with a number, and must end with a colon character “:”.
Labels are not case sensitive.
Example:
Do While (TRUE)
If (DriveInput.1 = ON) Then
GoTo RunIndex1:
Else
GoTo RunIndex2:
EndIf
RunIndex1:
Index.1.Initiate
GoTo EndLoop:
RunIndex2:
Index.2.Initiate
EndLoop:
Wait For Index.AnyCommandComplete
Loop
‘Go to RunIndex1 label
‘Go to RunIndex2 label
‘If Input.1 is on, resume here
‘GoTo EndLoop label
‘If Input.1 is off, resume here
See the Label: instruction for additional examples.
If/Then/Endif
This is a program flow control instruction used to selectively run a section of code only if a logical test condition is true. If the
test evaluates to true the code between the If/Then and Endif lines is executed. If the test evaluates to false the code is not
executed and the program skips to the next line of code after the Endif.
Logical tests (AND, OR, NOT) can be used in the If/Then/Endif instruction. Parenthesis “()” can be used to group the logical
tests.
Examples:
If DriveInput.1=ON Then
’Turn Outputs 1 On and 2 Off if Drive
’Input.1 is ON.
DriveOutput.1=ON
DriveOutput.2=OFF
Endif
If (DriveInput.1=ON AND DriveInput.2=OFF) Then
‘Turn Outputs 1 On and 2 Off if Drive
‘Input.1 is ON and DriveInput.2 is OFF
DriveOutput.1=ON
DriveOutput.2=OFF
Endif
If (DriveInput.2=ON) Then
Jog.0.PlusInitiate
Wait For DriveInput.2=OFF
Jog.Stop
Epsilon EP-P Drive Reference Manual
Revision A3
‘Jog+ when DriveInput.2=ON
‘Vel=20in/s
‘Stop when the input goes OFF
‘Decelerate to a stop
123
www.emersonct.com
Endif
If (DriveInput.3=ON) Then
Jog.0.MinusInitiate
Wait For DriveInput.3=OFF
Jog.Stop
Endif
‘Jog- when DriveInput.3=ON
‘Vel=20in/s
‘Stop when the input goes OFF
‘Decelerate to a stop
Label:
The Label: instruction is used in conjunction with the GoTo instruction to cause program flow to transfer to a specified location within a
program. The destination label is allowed to be above or below the GoTo instruction within the same program. It is not possible to GoTo a label
outside of the program containing the GoTo instruction, nor is it possible to use a GoTo/Label: to exit out of a For Count/Next loop. In either of
these conditions, a RedDot error will be generated.
The Label to which program flow transfers is a string of up to 50 characters in length and can be made up of any alphanumeric character. The
label name must not start with a number, and must end with a colon character “:”. When using the Label: instruction, a “:” will be automatically
inserted for the user.
Labels are not case sensitive.
Example:
Start:
Index.1.Initiate
Wait For Index.AnyCommandComplete
If (DriveInput.2 = ON) Then
GoTo Start:
‘ Go to Start label if Input2 on
EndIf
DriveOutput.1 = ON
End
See GoTo instruction for additional examples.
Switch
The Switch instruction is used in conjunction with the Case: instruction to cause program flow to transfer based on the switch expression value
and execute the instructions associated with that case instruction. In the following example if the value of var.var0 is one then case <1> will be
executed. When the break instruction is encountered the program will continue with the instruction after the EndSwitch command.
Example:
Switch<var.var0>
case <1>
Home.0.Initiate
‘Home0,Sensor,SpecifiedOffset=0.0000 revs,Vel=200 revs/m
break
case <2>
Dwell For Time 60 ‘seconds
break
Default:
Index.0.Initiate
‘Index0,Incremental,Distance-300 revs,Vel=2000 rev/m
Wait For Index.AnyCommandComplete
EndSwitch
In the above example if var.var0 = 2 then the program will execute from “case 2” and process the instructions of case 2 and proceed through
the program.
Wait For
This program flow instruction is used to halt program execution until an expression becomes true. Once the expression becomes true the
program continues on with the next line of code.
Logical tests (AND, OR, NOT) can be used in the Wait For instruction. Output events (DriveInput=ON, AtVel, etc.) as well as comparisons
(PosnFeedback > 1234, VelFeedback < 100, etc.) can be used in a Wait For instruction.
Example:
Wait For (DriveInput.1=ON AND DriveInput.2=OFF)
Index.0.Initiate
Wait For Index.AnyCommandComplete
If (DriveInput.2=ON) Then
Jog.0.PlusInitiate
Wait For DriveInput.2=OFF
Jog.Stop
Endif
If (DriveInput.3=ON) Then
Jog.0.MinusInitiate
Wait For DriveInput.3=OFF
‘Jog+ when DriveInput.2=ON
‘Vel=20in/s
‘Stop when the input goes OFF
‘Decelerate to a stop
‘Jog- when DriveInput.3=ON
‘Vel=20in/s
‘Stop when the input goes OFF
124
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Jog.Stop
Endif
‘Decelerate to a stop
Example:
Wait For (MasterAxis.PosnFeedback > 1000.00)
DriveOutput.1 = ON
Wait For (VelFeedback > 50.00)
DriveOutput.2 = ON
Wait For Control Loop
This program instruction is used to halt the program execution until the next control loop. The control loop processes the input
and output events. So the “Wait For Control Loop” is very useful to allow an event to be processed before using the results or
clearing it’s activation request.
Examples:
DefineHome=true
Wait For Control Loop
DefineHome=false
Wait For Time
This program instruction is used to halt program execution for a specified period of time. This instruction is not a motion
instruction and can be used while a motion instruction is executing. Units: Seconds, Resolution: 0.001 seconds
A comment is automatically inserted after the “Wait For Time” instruction which notes that the time is in units of seconds. The
comment starts with the apostrophe ‘ character.
Examples:
Wait For Time 5.000
‘seconds
Do While (TRUE)
Index.1.Initiate
‘Repeat until the program is halted
‘Incremental,Dist=25.250in,Vel=10.0in/s
Wait For AtVel
‘Turn Output 1 ON for 1 second, after the ‘index
reaches its’ target velocity
DriveOutput.1=ON
Wait For Time 1.000
‘seconds
DriveOutput.1=OFF
Wait For Index.AnyCommandComplete
Loop
4.4.2
Program Math Functions
Cos
This trig function can be used in formulas from within a program. Example: var.var0 =
the trigonometric cosine in degrees. Cos(x) x is in degrees and accurate to 6 decimal places.
Cos(var.var1). Returns
Sin
This trig function can be used in formulas from within a program. Example: var.var0 =
the trigonometric sine in degrees. Sin(x) x is in degrees and accurate to 6 decimal places.
Sin(var.var1). Returns
Tan
This trig function can be used in formulas from within a program. Example: var.var0 =Tan(var.var1). Returns
the trigonometric tangent in degrees. Tan(x) x is in degrees and accurate to 6 decimal places.
ArcCos
This trig function can be used in formulas from within a program. Example: var.var0 = ArcCos(var.var1).
Returns the trigonometric ArcCos in degrees. The ArcCosine is the angle whose cosine is the given number.
ArcSin
This trig function can be used in formulas from within a program. Example: var.var0 = ArcSin(var.var1).
Returns the trigonometric ArcSin in degrees. The ArcSin is the angle whose Sine is the given number.
ArcTan
This trig function can be used in formulas from within a program. Example: var.var0 = ArcTan(var.var1).
Returns the trigonometric ArcTan in degrees. The ArcTan is the angle whose Tan is the given number.
Modulus
Returns the remainder (Modulus) resulting when a numerator is divided by a denominator. The result has the same sign as the
denominator. The floating-point operators are NOT rounded to integers as would be in the Mod operator.
The exact mathematical function for the Modulus function is as follows:
Modulus(x,y) = x - [(FLOOR (x/y)) * y]
Epsilon EP-P Drive Reference Manual
Revision A3
125
www.emersonct.com
Where FLOOR is defined as rounding the argument down to the next whole integer value towards negative infinity.
Example: FLOOR(-3.5715) = -4 or FLOOR(3.5715) = 3
The FLOOR function itself is not available to the user within a user program.
Example 1: Modulus(5,1.4) Returns 0.8
Example 2: Modulus(5,-1.4) Returns -0.6
Example 3: Modulus(-5,1.4) Returns 0.6
Example 4: Modulus(-5,-1.4) Returns -0.8
BitAnd
This operator may be used when it is desirable to AND each individual bit of a 32-bit parameter. This operator can be found by clicking on
the Drag in Operands button to open the Select Math Operator window.
var.var2 = var.var0 bitand var.var1
Example: if var.var0 = 1000 and var.var1 = -1
var.var0 = 0000000000000000000001111101000b
var.var1 = 1111111111111111111111111111111b
var.var2 = 0000000000000000000001111101000b
BitOr
This operator may be used when it is desirable to OR each individual bit of a 32-bit parameter. This operator can be found by clicking on
the Drag in Operands button to open the Select Math Operator window.
var.var2 = var.var0 bitor var.var1
Example: if var.var0 = 1000 and var.var1 = -10000
var.var0 = 0000000000000000000001111101000b
var.var1 = 1111111111111111101100011110000b
var.var2 = 1111111111111111101101111111000b
4.4.3
Program Array Access
Cam[ ].Master
This instruction allows the user to write to a cam tables master value at a given table number and element number.
Example:
Cam[0,3].Master =7
Cam[ ].Follower
This instruction allows the user to write to a cam tables master value at a given table number and element number.
Example:
Cam[1,2].Follower =3
Cam[ ].Interpolation
This instruction allows the user to write to a cam tables master value at a given table number and element number.
Example:
Cam[0,3].Interpolation =5
4.4.4
Motion Instructions
Dwell For Time
This motion instruction is used to pause program execution for a very precise amount of time. It operates as a motion instruction – similar to
an index, home or jog. Like all other motion instructions it will not start until the preceding motion instruction has completed. A “Wait for
Index.AnyCommandComplete” is not required. Likewise, any subsequent motion commands will wait and start after the dwell has completed.
The total time required to complete a sequence of indexes and “Dwell For Time” instructions is extremely repeatable.
The “Dwell For Time” instruction is in units of seconds with a resolution of milliseconds (0.000 seconds).
If you want to pause the program while an index is executing you should use a “Wait for Time” instruction described below.
A comment is automatically inserted after the “Dwell For Time” instruction which notes that the dwell time is in units of seconds. The comment
starts with the ‘ character.
Examples:
Do While (TRUE)
Index.0.Initiate
Dwell For Time 1.000
Loop
‘Incremetal,Dist=25.000in,Vel=25in/s
‘Seconds
Do While (TRUE)
Index.0.Initiate
Dwell For Time 1.000
Index.1.Initiate
Dwell For Time 0.500
Loop
‘Incremetal,Dist=25.000in,Vel=25in/s
‘Seconds
‘Incremental,Dist=15.000in,Vel=25in/s
‘Seconds
126
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Dwell for Master Dist
This motion instruction is used to pause program execution for a precise change in distance on the master encoder signal.
This is typically used in synchronized motion applications. This dwell does not begin until all other motion has completed.
When the dwell begins, program flow will wait until the specified master distance has passed. The units for the dwell value are
specified in the Master Units View.
Example:
Do While (TRUE)
Index.0.Initiate
MstrInch
Dwell For MasterDist 12.00
Loop
‘Synch,Incr,Dist=5.0 Inches,Vel=1 Inches/
‘MstrInch
IndexInitiate by Expression
This motion instruction is used to initiate a single index. The index is preset to include an acceleration up to speed, a run at
speed and a deceleration to a stop. IndexInitiate by Expression is used to initiate different indexes with the same line of code
in a program.
One notable change from a standard Index.#.Initiate is that Wait for Index.AnyCommandComplete” line of code normally
inserted after the initiate will not be inserted after IndexInitiate by Expression. No comments will be added to this instruction as
the index selected can change anytime before the initiate command is encountered.
The following example will initiate index.0, wait for complete, initiate index.1, wait for complete, index.2... etc.
Example:
var.var0 = 0
a:
indexinitiate var.var0
Var.var0 = 1 + var.var0
wait for index.anycommandcomplete
goto a:
CompoundIndexInitiate by Expression
This motion instruction is used to vary the index numbers making up a compound index. No comments will be added to this
instruction as the index selected can change anytime before the initiate command is encountered.
The following code will continuously compound initiate Index.0 and Index.1 in a loop.
Example:
a:
if var.var0 = 0 then
var.var0 = 1
else
var.var0 = 0
endif
CompoundIndexInitiate var.var0
goto a:
CamInitate By Expression
This motion instruction is used to initiate a cam. The cam is preset to include cam type, time base, direction, any chaining
requirements, and a deceleration to a stop, optional. CamInitiate by Expression is used to initiate different Cams with the same
line of code in a program.
The following example will initiate Cam Table 0, wait for complete, initiate Cam Table.1, wait for complete, index.2... etc.
Example:
var.var0 = 0
a:
CamInitiate var.var0
Var.var0 = 1 + var.var0
wait for index.anycommandcomplete
goto a:
Epsilon EP-P Drive Reference Manual
Revision A3
127
www.emersonct.com
Set Cam Master Offset(...)
Slave’s
corresponding
position is
returned
Feed the Master’s
position into this
function
The function
interpolates between
cam table points!
Set Cam Follower Offset(...)
Master’s
corresponding
position is returned
Feed the Slave’s position
into this function
The function interpolates
between cam table points
and returns the Master
Position.
Calling the function
again will return the
next master position
Index.Initiate
This program instruction is used to initiate a single index. The index is preset to include an acceleration up to speed, a run at speed and a
deceleration to a stop.
A comment is automatically inserted after the index instruction which shows key data about the particular index. The comment starts with the
apostrophe ‘character.
A “Wait For Index.AnyCommandComplete” instruction is also automatically inserted after each index. This insures that the index has
completed before the program continues on to the next line of code. It is also possible make the program wait until the index is complete and
the following error is less than a specified amount. This is accomplished by changing the “Wait For Index.AnyCommandComplete” to “Wait For
InPosn”. The In Position Window is configured in the Position view.
Example:
Index.0.Initiate
‘Incremental,Dist=5.000in,Vel=2.0in/s
Wait For Index.AnyCommandComplete
Index.37.Initiate
Wait For InPosn
‘Absolute,Posn=120.60mm,Vel=50.2mm/s
128
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Index.CompoundInitiate
This program instruction is used to initiate an index which has no deceleration ramp. The index accelerates or decelerates
towards the next index velocity using the next index acceleration ramp. The index will finish at velocity. The program then
moves on to the next index. It smoothly transitions into the second index without stopping. The second index then ramps to its
pre-configured velocity. Multiple indexes can be “compounded” to create a complex velocity profile. The last index in a
complex profile must have a deceleration ramp. This is accomplished using a standard Index.Initiate rather than a
Index.CompoundInitiate. The final index will honor the deceleration ramp. If the last index is not long enough to perform a
decel ramp at the programmed rate, the motor will backup at the end of the last index.
Each index can be used in multiple places as both a standard index with a deceleration ramp, and a compound index without
a deceleration ramp. The program instruction (Index.0.Initiate or Index.0.CompoundInitiate), not the index itself, determines
whether or not the index will execute a deceleration ramp. For example, Index.0 can be used multiple times in multiple
programs. It can be initiated at different times using the Index.0.Initiate instruction and the Index.0.CompoundInitiate
instruction.
A comment is automatically inserted after the index instruction which shows key data about the particular index. The comment
starts with the apostrophe ‘ character.
Examples:
Velocity
Complex Velocity Profile
Index 0
Index 1
Index 2
Time
Index.0.CompoundInitiate
‘Incremental,Dist=5.000in,Vel=50in/s
Index.1.CompoundInitiate
‘Incremental,Dist=20.000in,Vel=75in/s
Index.2.Initiate
‘Incremental,Dist=10.000in,Vel=30in/s
Wait For Index.AnyCommandComplete
Figure 139:
Index Velocity Profile
Complex Velocity Profile
Velocity
Drive Output 3 ON
OFF
Drive Output 2 ON
OFF
Drive Output 1 ON
OFF
Index 0
Index 1
Index 2
Time
Index.0.CompoundInitiate
DriveOutput.1=ON
Index.1.CompoundInitiate
DriveOutput.2=ON
Index.2.Initiate
Epsilon EP-P Drive Reference Manual
Revision A3
‘Incremetal,Dist=5.000in,Vel=50in/s
‘Turns ON immediately after Index.0 is started
‘Incremental,Dist=20.000in,Vel=75in/s
‘Turns ON immediately after Index.1 is started
‘Incremental,Dist=10.000in,Vel=30in/s
129
www.emersonct.com
DriveOutput.3=ON
‘Turns ON immediately after Index.2 is started
Wait For Index.AnyCommandComplete
DriveOutput.1=OFF
‘Turns OFF after Index.2’s command is completed
DriveOutput.2=OFF
‘Turns OFF after Index.2’s command is completed
DriveOutput.3=OFF
‘Turns OFF after Index.2’s command is completed
Figure 140:
Index Velocity Profile with Drive Outputs
Index.BlendInitiate
This program instruction is used to allow an index to complete its move at the velocity of another index. A blended index accelerates towards
its index velocity using its accel ramp. The index will run at velocity before using its deceleration ramp to accelerate or decelerate towards the
velocity of the next index specified. This differs from the compound index where the index finishes using the accel ramp of the next index.
The index that is to be "blended into" is on the command line in parenthesis immediately after the Index.BlendInitiate command.
Index.BlendInitiate into (1)
This command will cause index zero to finish at the velocity of Index 1. The value within the parenthesis can also be a variable. The following
example will operate the same as the previous.
Index.0.BlendInitiate into (var.var0)
The next index that is to be blended must:
•
Exist
• Have the same time base as the present index (synch verus real time)
If the index does not exist or the time base is different, the blended index will convert into a regular compound index.
The direction of the next index (blended into index) is not looked at. Hence, blending an index into another index will not cause the index to
cross through zero velocity.
Example:
Index.0.BlendInitiate into (1)
DriveOutput.1=ON
Index.1.BlendInitiate into (2)
DriveOutput.2=ON
Index.2.Initiate
DriveOutput.3=ON
Wait For Index.AnyCommandComplete
DriveOutput.1=OFF
DriveOutput.2=OFF
DriveOutput.3=OFF
Index.StopTracking
This command is used to cancel the position tracker continuous index once it has been initiated within the program using the Index.#.Initiate
program command. If the Index.#.Initiate input function starts the position tracker index, then Index.#.StopTracking will not stop the tracking
index.
Home.Initiate
This program instruction is used to initiate the home.
A comment is automatically inserted after the Home.Initiate instruction which shows key data about the particular home. The comment starts
with the apostrophe ‘ character.
A “Wait For Home.AnyCommandComplete” instruction is not required because the home is actually a program which already has a “Wait For”
instruction.
Example:
Home.0.Initiate
‘Sensor,Offset=2.000in,Vel=-10.0in/s
Jog.Stop
This program instruction is used to halt jogging using the deceleration ramp setup for the currently operating jog.
Examples:
Wait For DriveInput.2=ON
Jog.0.MinusInitiate
Wait For DriveInput.2=OFF
Jog.Stop
‘Wait for “Jog –“ input to turn on
‘Vel=27.2in/s
‘Wait for “Jog –“ input to turn off
‘Decelerate to a stop
Do While(TRUE)
If (DriveInput.2=ON) Then
Jog.0.PlusInitiate
Wait For DriveInput.2=OFF
Jog.Stop
Endif
‘Repeat until the program is halted
‘Jog+ when DriveInput.2=ON
‘Vel=20in/s
‘Stop when the input goes OFF
‘Decelerate to a stop
If (DriveInput.3=ON) Then
‘Jog- when DriveInput.3=ON
130
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Jog.0.MinusInitiate
Wait For DriveInput.3=OFF
Jog.Stop
Endif
Loop
‘Vel=20in/s
‘Stop when the input goes OFF
‘Decelerate to a stop
Jog.PlusInitiate
This program instruction is used to initiate jogging in the positive direction. The Jog.Stop instruction is used to stop jogging
motion.
A comment is automatically inserted after the Jog.PlusInitiate instruction which shows key data about the particular jog. The
comment starts with the apostrophe ’ character.
Examples:
Jog.0.PlusInitiate
Jog.1.PlusInitiate
‘Vel=27.2in/s
‘Sync,Vel=1.000in/in
Jog.MinusInitiate
This program instruction is used to initiate jogging in the negative direction. The Jog.Stop instruction is used to stop jogging
motion.
A comment is automatically inserted after the Jog.MinusInitiate instruction which shows key data about the particular jog. The
comment starts with the apostrophe ‘ character.
Examples:
Jog.0.MinusInitiate
Jog.1.MinusInitiate
‘Vel=27.2in/s
‘Sync,Vel=1.000in/in
Program.ProgramStop
The Program.#.ProgramStop instruction is used to stop processing a specific program. The ProgramStop instruction can be
used in a program to stop itself or any other program. The ProgramStop instruction DOES NOT stop the motion that has been
initiated by the program being stopped. Either the MotionStop or the Profile.Stop instruction must be used to stop motion from
a program.
If the ProgramStop instruction is used to stop a program that is not running, the Stop will be issued, but will be ignored.
If the program that is stopped was called by another program, the call is killed. This means that program flow will not return to
the program that originally called the program that was stopped. For example, Program 1 calls Program 2. While Program 2 is
running, Program 3 (which is running on a different task) issues a Program.2.ProgramStop command. If Program 2 ended
because of normal conditions (i.e. the “End” instruction), then program flow would return back to Program 1. Because Program
2 was terminated using the Program.Stop instruction, program flow does not return to Program 1.
The ProgramComplete signal will not activate if a program has been stopped using the Program.Stop command.
Example:
Program 0 – Running on Task 0
Do While TRUE
Index.1.Initiate
Wait For Index.AnyCommandComplete
Var.Counter = Var.Counter + 1
Loop
Program 1 – Running on Task 1
Wait For DriveInput.1 = ON
Program.0.Stop
NOTE
In the example above, when input 1 turns on, Program 0 will be stopped. If Index 1 was in progress when the program was
stopped, the index will continue until it is complete.
Program.Initiate
This instruction allows the user to start another program from within a program. This is different from a Call Program
instruction because the program this instruction is in does not stop when the other program starts. Therefore the program that
is initiated must be on a different task. (See Program Multi-Tasking on page 115)
Gear Stop
Gear Stop will stop gearing motion that has been initiated from a program.
Example:
Gear.Initiate
Wait for DriveInput.2=ON
Gear.Stop
Gear.Initate
Gear Initiate will initiate gearing from a program. Gearing will remain active until the Gear.Stop command is used.
Example:
Epsilon EP-P Drive Reference Manual
Revision A3
131
www.emersonct.com
Gear.Initiate
Wait for DriveInput.2=ON
Gear.Stop
Cam.Initiate
Cam.#.Initiate has two forms - Program Instruction and Assignment (as a Destination). Both are used to initiate a specific Cam. For the
Destination, the Cam is initiated on the rising edge of this event. Using the Destination, a Cam cannot be initiated if there is an Index, Home,
Jog, or Program in progress, or if the Cam.#.Initiate is an instruction. If any motion is active, the program will hold on this instruction until that
motion is complete (unless it is run on a different profile).
Cam.Resume
Resumes the cam execution from a Cam.Suspend command (or SetCamMasterOffset(MasterPosn), or SetCamFollowerOffset
(FollowerPosn). The cam points are all relative to the start of the Cam table. On Cam.Resume the current physical position becomes the cam
start point and the cam aligns it’s resume position to the current physical position without any physical movement. This means if you suspend
a cam and move the physical position; for example with a Jog, you will need to position the motor back to the desired position before resuming.
Cam.Suspend
When Cam.Suspend is activated the current cam will stop using the Cam.Decel ramp rate (if Cam.DecelEnable is enabled). The cam will
accept a Cam.Resume after a suspend. The suspend records the master and follower positions at the point of the suspend for future
Cam.Resume execution.
Cam.Stop
When Cam.Stop is activated the cam will stop using the Cam.Decel ramp rate (if Cam.DecelEnable is enabled).
4.4.5
Motion Modifiers
Timeline Control Instructions
Keeping the timeline intact is most important in applications using synchronized motion. This is because in synchronized motion, time is
replaced by master encoder motion. If time is lost in a synchronized motion application, then master distance is lost, and the follower position
is off with respect to the master.
The Epsilon EP-P drive has program instructions to allow better control of the timeline. These instructions are the “Using Capture” and the
“Using Last” instructions. Following is a description of each of the instructions:
On Profile
The On Profile instruction can be inserted after any motion type Initiate, Dwell For Time, or Dwell For MasterDist instructions. By inserting the
On Profile modifier, it specifies which Profile the instruction will run on (See Multiple Profiles section for more information). Select from Profile
0 or Profile 1. Both Profiles sum to give a single commanded position and commanded velocity. If no On Profile modifier is used, the motion/
dwell will operate on Profile 0. All motion that is initiated from the Assignments view operates on Profile 0.
The On Profile modifier is also used with the Jog.Stop and Gear.Stop. When stopping jog or gear motion that is operating on Profile 1, the On
Profile 1 modifier must also be used on the stop instruction.
Examples:
Index.0.Initiate
Index.1.Initiate On Profile.1
'Index 0 runs on Profile 0
'Index 1 runs on Profile 1
Gear.Initiate On Profile.1
Wait For DriveInput.3 = ON
Gear.Stop On Profile.1
'Gear operates on Profile 1
'Stop Gear running on Profile 1
Jog.0.PlusInitiate On Profile.1
'Jog 0 runs in positive direction on Profile 1
Index.0.Initiate
'Index 0 runs on Profile 0
Wait For Index.AnyCommandComplete
Wait For DriveInput.2 = ON
Jog.Stop On Profile.1
'Stop Jog running on Profile 1
Using Capture
The Using Capture instruction can be inserted after any Jog Initiate, Index Initiate, Dwell For Time, and Dwell For MasterDist instructions. By
inserting the Using Capture instruction, it specifies that data captured by the position capture object is to be used as the starting point for the
motion initiate. If the motion time base is realtime, then the captured time is used as the starting point for the motion profile. If the motion time
base is synchronized, then the captured master position is used as the starting point for the profile.
Example:
Wait For (Capture.0.CaptureTriggered)
Index.0.Initiate Using Capture.0 ‘Index0,Incrmntl,Dist=5.0revs
Using Last
When the Using Last instruction is inserted after a motion initiate instruction, the time (or master position in synch motion) of the last command
complete is used as the starting point of the motion profile. Whenever a motion profile is complete, the time/position is automatically captured
behind the scenes. The Using Last instruction simply references this “automatically” captured time or position.
The Epsilon EP-P drive performs motion based on a concept called the timeline. The timeline allows for accurate and repeatable motion with
respect to a single point in time. The timeline guarantees that all motion profiles occur at the right time with respect to each other.
132
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
If Index0 takes 3 seconds to complete, and Index1 takes 5 seconds to complete, by initiating Index0 and then Index1 in a
program, the user would expect these profiles to take a total of 8 seconds to complete. It is possible though, that because of
processor timing, Index.1 does not start at exactly the same time Index0 is complete. Therefore, the two profiles could take
slightly more than 8 seconds to complete. Although the amount of time lost is extremely small (less than 5 milliseconds), over
a long period of time, this lost time can accumulate.
Keeping the timeline intact is most important in applications using synchronized motion. This is because in synchronized
motion, time is replaced by master encoder motion. If time is lost in a synchronized motion application, then master distance is
lost, and the follower position is off with respect to the master.
Example:
Index.0.Initiate
Dwell For Time 1.000 Using Last
Index.1.Initiate Using Last
4.4.6
‘Index0,Incrmntl,Dist=1.5revs
‘Index1,Incrmntl,Dist=3.5revs
Modbus Slave
ReadBit
Reads bit values (coils or inputs) from the slave into user bits.
ReadBit (<SlaveId>, <ModbusAddr>, <Qty>, <BitInstance>)
<slaveId> =The instance number of a defined slave. See Network Modbus Master Slave tab,
<ModbusAddr> = The starting modbus address of the slave coil or input.
Range
Description
00001 - 09999
one coil for each user bit
10001 - 19999
one input for each user bit
<Qty> = The number of coils or inputs to be read which equals the number of user bits
<BitInstance> = The starting bit instance number that the coil or input results will be written to
This is a block transfer command that can load several coil status bits or inputs into User Bits.
The program will not proceed to the next instruction until either the data transfer is complete or an error has occurred.
Example:
' Read from slave 2 - 3 coils (10, 11 and 12) and stores the result
' in user bits bit.1, bit.2 and bit.3
ReadBit (2, 10, 3, 1)
Example:
' Read from slave 1 - n(var.qty) coils starting at coil var.from
' and store the results in n(var.qty) user bits starting at
' bit instance var.to.
var.from = 39980
var.qty = 3
var.to = 1
ReadBit (1, var.from, var.qty, var.to)
ReadVar
This instruction reads values from the modbus slave to the user variables.
ReadVar (<SlaveId>, <ModbusAddr>, <Qty>, <VarInstance>)
<SlaveID> = The instance number of a defined slave. See Network Modbus Master Slave tab.
<ModbusAddr> = The starting modbus address of the slave holding or input register.
Range
Description
00001 - 09999
Each multiple of 16 coils are packed into one user variable. <Qty> defines the number of coils to
read
10001 - 19999
Each multiple of 16 coils are packed into one user variable. <Qty> defines the number of coils to
read
30001 - 39999
16 bit read only slave register is loaded into the lower 16bits of a user variable
40001 - 49999
16 bit writable slave data is loaded into the lower 16bits of a user variable
Two 16 bit read only slave registers are loaded into the lower 16bits of a user variable and the upper
130001 - 139999
16 bits of the user variable
140001 - 149999
Two 16 bit writable slave registers are loaded into the lower 16bits of a user variable and the upper
16 bits of the user variable
400001 - 409999
Unidrive 32bit values:
Two 16bit slave holding registers are written from the 32bit user variable with word swap as
specified by the slave configuration.
Epsilon EP-P Drive Reference Manual
Revision A3
133
www.emersonct.com
<Qty> = The number of slave values to be read.
<VarInstance> = The starting user variable instance number that the slave values will be written to. Decimal point of the user variable will
not be altered.
This a block transfer command that can load several holding or input registers into user variables.
The program will not proceed to the next instruction until either the data transfer is complete or an error has occurred.
All operands can be numbers or expressions.
Example:
' Read from slave 2 - 3 input registers (39980, 39981 and 39982)
' and stores the result in user variables var.var1, var.var2 and
' var.var3
Recover (2, 39980, 3, 1)
Example:
' Read from slave 1 - n(var.qty) registers starting at register
' var.from and store the results in n(var.qty) user variables
' starting at var instance var.to
var.from = 39980
var.qty = 3
var.to = 1
ReadVar (1, var.from, var.qty, var.to)
WriteBit
This instruction writes bit values (coil) to the slave from user bits.
WriteBit (<SlaveId>, <ModbusAddr>, <Qty>, <BitInstance>)
<SlaveID> = The instance number of a defined slave. See Network Modbus Master Slave tab.
<ModbusAddr> = The starting modbus address of the slave coil.
Range
Description
00001 - 09999
one coil for each user bit
<Qty>= The number of coils to be written which equals the number of user bits
<BitInstance> = The starting user bit instance number that the coil values will be set to.
This is a block transfer command that can set several coil status bits from the User Bits.
The program will not proceed to the next instruction until either the data transfer is complete or an error has occurred.
All operands can be numbers or expressions.
Example:
' Write to slave 2 - 2 coils (23, and 24) the values set in
' in user bits bit.3, and bit.4
WriteBit (2, 23, 2, 3)
Example:
' Write to slave 1 - n(var.qty) coils starting at coil var.to
' the values stored in n(var.qty) user bits starting at
' bit instance var.from
var.to
= 39980
var.qty = 3
var.from = 1
WriteBit (1, var.to, var.qty, var.from)
WriteVar
This instruction writes values (coils or holding registers) to the slave from user variables.
WriteVar (<SlaveId>, <ModbusAddr>, <Qty>, <VarInstance>)
<SlaveId> = The instance number of a defined slave. See Network Modbus Master Slave tab.
<ModbusAddr> = The starting modbus address of the slave holding register
Range
Description
00001 - 09999
Each multiple of 16 coils are written from the lower 16 bits of user variable. <Qty> defines the
number of coils to write
40001 - 49999
16 bit writable slave data is loaded into the lower 16bits of a user variable
140001 - 149999
Two 16 bit writable slave registers are loaded into the lower 16bits of a user variable and the upper
16 bits of the user variable
400001 - 409999
Unidrive 32bit values: Two 16bit slave holding registers are written from the 32bit user variable with
word swap as specified by the slave configuration.
134
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
"Range 00001 to 09999 - Each multiple of 16 coils are extracted from one user variable. <Qty> defines the number of coils
to write
"Range 40001 to 49999 the lower 16bits of a user variable is written to the 16 bit writable slave register
"Range 140001 to 149999 the lower 16bits of a user variable is written to the slave and the next modbus register is written
with the upper 16 bits of the user variable
<Qty> = The number of slave values to be written
<VarInstance> = The starting user variable instance number that the slave values will be set from. Decimal points will be
ignored.
This a block transfer command that can set several holding or input registers from user variables.
The program will not proceed to the next instruction until either the data transfer is complete or an error has occurred.
All operands can be numbers or expressions.
Example:
' Writes to slave 2 - 3 registers (41121, 41122 and 41123)
' the values in user variables var.var3, var.var4 and var.var5
WriteVar (2, 41121, 3, 3)
Example:
' Writes
' var.to
' at var
var.to
var.qty
var.from
WriteVar
to slave 1 - n(var.qty) registers starting at register
the values in n(var.qty) user variables starting
instance var.from
= 41121
= 3
= 3
(1, var.from, var.qty, var.to)
WriteValue
This instruction will writes a single value to the slave
WriteValue (<SlaveId>, <ModbusAddr>, <Qty>, <Value>)
<SlaveId> = The instance number of a defined slave. See Network Modbus Master Slave tab
<ModbusAddr> = The starting modbus address of the slave coil or holding register
Range
Description
00001 - 09999
Each multiple of 16 coils are packed into one user variable. <Qty> defines the number of coils to
read
10001 - 19999
Each multiple of 16 coils are packed into one user variable. <Qty> defines the number of coils to
read
40001 - 49999
16 bit writable slave data is loaded into the lower 16bits of a user variable
140001 - 149999
Two 16 bit writable slave registers are loaded into the lower 16bits of a user variable and the upper
16 bits of the user variable
400001 - 409999
Unidrive 32bit values: Two 16bit slave holding registers are written from the 32bit user variable with
word swap as specified by the slave configuration.
<Qty> = The number of Modbus addresses of the specific type to write with the given value
<Value> = An expression representing a 32 bit value. Decimal point for the Value will be ignored
This is a block transfer command that can load up to 32 modbus coils or two Holding registers.
When multiple coils are written, the low 16 bits of <value> is written least significant to most significant bit. If more than 16 coils
are written, <Value> is re-used.
The program will not proceed to the next instruction until either the data transfer is complete or an error has occurred.
All operands can be numbers or expressions.
Example:
' Write 1x 45 to register 39980 on MbMaster.1
WriteValue (1, 39980, 1, 45)
Example:
' Write 1x the content of var.var1 to register var.var0 on MbMaster.1
WriteValue (1, var.var0, 1, var.var1)
Epsilon EP-P Drive Reference Manual
Revision A3
135
www.emersonct.com
4.5
Adding and Deleting Programs
Programs can be added or removed from the user configuration in three ways. Programs may only be added or deleted while offline.
4.5.1
PowerTools Toolbar Button Method
Add Program Button
The Add Program button (shown below) will add a new program to the user configuration. Programs are added in sequential order. Clicking on
the button will add a program and bring you to the program-editing view allowing you to enter program instructions.
Delete Program Button
The Delete Program button (shown below) will delete a program from the user configuration. The highest numbered program will automatically
be deleted unless a different program is selected on the Programs heading screen. To delete a specific program, click on the Programs branch
in the Hierarchy Tree. From this view, select the specific program you wish to delete, and then click on the Delete Program button.
4.5.2
Power Tools Menu Bar Method
Adding a Program
From the PowerTools Pro menu bar, select Edit/New/Program. A program will be added in sequential order and you will be brought to the
program-editing view allowing you to enter program instructions.
Deleting a Program
Navigate to the Programs view on the Hierarchy Tree, and select the program you wish to delete. From the PowerTools Pro menu bar, select
Edit/Delete/Program. The selected Program will be deleted from the configuration.
4.5.3
Right Click Method
Adding a Program
Navigate to the Programs view in the Hierarchy Tree. Position your mouse pointer on the right side of the view and right-click. A selection
menu will appear allowing you to add a New Program or Delete a Program. Click on New Program and a program will be added in sequential
order and you will be brought to the program-editing view allowing you to enter program instructions.
Deleting a Program
Navigate to the Programs view in the Hierarchy Tree. Select the program you wish to delete and then right-click on your mouse. A selection
menu will appear allowing you to add a New Program or Delete a Program. Click on Delete Program and the selected program will be deleted
from the configuration.
4.5.4
Run Anytime Programs
The programming environment has been designed to automatically stop all programs when a fault occurs (regardless of what type of fault).
Some applications require the ability to run a program as soon as a fault occurs of continue running a program even through a fault condition.
In order to do this, a program must be classified as “Run Anytime”. To define a program to be able to run during a fault or while the drive is
disabled, the “Run Anytime” check box must be selected in the Program view. Figure 141 shows an example of the “Run Anytime” check box
after it has been selected.
136
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 141:
Program View with “Run Anytime” Check box Enabled
When a fault occurs, the drive will still be disabled, and no motion will be possible. For this reason, it may be necessary to
reset the fault in the “Run Anytime” program prior to running motion again. If a motion instruction is processed while the drive
is disabled, the program will stall on that particular line of the program, but the program will not stop.
Certain conditions will still cause a program designated as “Run Anytime” to stop. These conditions are listed below:
•
Stop Function is activated
• “Run Anytime” program has a program fault
Multiple programs may be configured as “Run Anytime” programs and can be called from a program the same as any other
program. If a “Run Anytime” program calls another program which is not configured to run anytime while the drive is faulted or
disabled, the task will be stopped.
Resetting Faults in “Run Anytime” Programs
To reset a fault from a “Run Anytime” program, use Fault.Reset = ON command in the user program. The Fault.Reset
command does not clear all types of faults. Some faults require power to be cycled in order to clear the fault. For more
information on the method used to clear individual faults, see the Diagnostics and Troubleshooting section.
After using the Fault.Reset command in a user program, use a Wait For Time 0.100’seconds command to give the drive time
to clear the fault and re-enable the drive before initiating motion. If this is not done, the motion will be initiated before the drive
is disabled. and the instruction will be ignored.
4.5.5
Program Blocking
A user program (or task) can be blocked from operation for a period of time. When a program or task is blocked, execution is
simply passed on to the next task. The following program instructions will cause a program to be blocked:
Index.#.Initiate
Home.Initiate
Jog.PlusInitiate
Jog.MinusInitiate
Dwell For Time
Epsilon EP-P Drive Reference Manual
Revision A3
137
www.emersonct.com
Dwell For Master Dist
Wait For (XXXX)
The motion related instructions will only block the task for the remainder of the current update and the task will operate normally the next time
it is processed. However, because the drive can currently only process one motion command at a time, a buffered motion command could
cause the program to be blocked for a longer period of time.
For instance, if a program initiates Index0 and the next program instruction initiates Index1, the program will be blocked until Index0 is
complete. This is because Index1 cannot start until Index0 is finished.
Index.0.Initiate
Index.1.Initiate
DriveOutput.1=ON
Blocked here until
Index0 is complete
A Dwell instruction is also a motion instruction and can block the program in the same way. The Dwell cannot start until Index0 is complete,
and therefore the program (or task) is blocked until Index0 is finished.
Index.0.Initiate
Dwell For Time 1.000 'Seconds
ModuleOutput.1=ON
Blocked here until
Index0 is complete
The Wait For instruction will block the program until the Wait For condition is satisfied. The Wait For condition does not have to be TRUE at
the exact time the task is processed. If the Wait For condition is satisfied at any time (even when that task is not being processed) the task will
be scheduled to run the next time through the loop.
Figure 142 shows the same time-slicing diagram as the previous figure, but Task 0 is blocked in this example. Notice how Task 0 is skipped
when the processor recognizes the task is blocked and processor execution switches to Task 1.
Control Loop Update
User Program Execution
Task 0
Messages
T1
T2
T3
T4
Update Rate
= Control Loop
= Messages (Modbus, Ethernet, Faults, etc.
= Program Execution
= Blocked Task (Blocked Program)
Figure 142:
Block Time Slice
The time taken to process the blocked task and pass on to the next available task is between 50 and 100 microseconds.
Figure 143 is a flowchart that reflects the time-slicing process. It shows the complete loop based on whether Modbus messages need
processing and if programs (tasks) are blocked.
138
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
t = 0 usec
Control Loop Update
Yes
Message(s)
Waiting?
Process
Message(s)
No
Switch to next task
Process Task
Yes
End of
Update?
t = 1600 usec
No
Task
Blocked?
No
Yes
Switch to next task
Figure 143:
4.6
Time Slicing Flow Chart
Example Programs
Out and Return - Simple
Description: Move out to an absolute position and return
Index.2.Initiate
‘Absolute,Posn=10.000in,Vel=5.0in/s
Index.1.Initiate
‘Absolute,Posn=0.000in,Vel=10.0in/s
Wait For Index.AnyCommandComplete
Out and Return – More Complex
Description: Home, Wait For an input, Move out to an absolute position, set an output, dwell for 1 second, clear the output,
return to home position, repeat the out and return sequence until the stop input halts the program.
Home.0.Initiate
DriveOutput.1=ON
‘Sensor,Offset=0.000in,Vel=-10.0in/s
‘Set the “At Position 1” output
Do While (TRUE)
Wait For DriveInput.2=ON
‘Repeat until the program is halted
‘Wait for the “Go” Input
Epsilon EP-P Drive Reference Manual
Revision A3
139
www.emersonct.com
DriveOutput.1=OFF
Index.2.Initiate
Wait For InPosn
DriveOutput.2=ON
Wait For Time 1.000
DriveOutput.2=OFF
Index.1.Initiate
Wait For InPosn
DriveOutput.1=ON
Loop
‘Clear the “At Position 1” output
‘Absolute,Dist=10.000in,Vel=5.0in/s
‘Set the “At Position 2” output
‘Seconds
‘Clear the “At Position 2” output
‘Absolute,Dist=0.000in,Vel=10.0in/s
‘Set the “At Position 1” output
Punch a Hole in a Web a Specified Distance Beyond a Registration Mark
Description: Index a web to a position 2 inches beyond a registration mark. Then fire a solenoid to punch a hole in the web. Wait for a sensor
to indicate that the punch is in the down position. Retract the solenoid. Wait until it is sensed in the up position.
Do While (TRUE)
Index.0.Initiate
Wait For InPosn
DriveOutput.1=ON
Wait For DriveInput.2=ON
DriveOutput.1=OFF
Wait For DriveInput.3=ON
Loop
‘Repeat until the program is halted
‘Registration,Offet=2.0in,Dist=20in,Vel=20in/s
‘Fire the punch solenoid
‘Wait for the “down” indicator
‘Retract the punch solenoid
‘Wait for the “up” indicator
Registration Index to Place a Product on a Conveyor After Each Lug
Registration Index (synchronized) to find the front edge of product, wait for input from a lug sensor and repeat.
Do While (TRUE)
Index.0.Initiate
‘Repeat until the program is halted
‘Sync,Registration,Offset=0.500,
‘Dist=50.000,Vel=1.000in/in
‘Registration move to product sensor.
‘Go to head of next product.
Wait For Index.AnyCommandComplete
Wait For DriveInput.2=ON
‘Wait for lug sensor on master conveyor.
Loop
Elevator (Accumulator) with 100 Stop Positions
Home, when an input goes on move down to the next position. When the bottom position is reached, move back to home when the input goes
on.
Home.0.Initiate
‘Sensor,Offset=0.00mm,Vel=100mm/s
Do While (TRUE)
For Count = 2 To 100
‘Repeat until the program is halted
‘Step to positions 2 - 100
Wait For DriveInput.2=ON‘Wait for “Go” input
Index.2.Initiate‘Incremetal,Dist=2.00mm,Vel=100mm/s
Wait For InPosn
Next
Wait For DriveInput.2=ON
Index.1.Initiate
Wait For InPosn
Loop
‘Wait for “Go” input
‘Absolute,Dist=0.00mm,Vel=1000mm/s
Simple Jogging within a Program
Jog+ when DriveInput.2 goes ON and stop when it goes off. Jog- when DriveInput.3 goes ON and stop when it goes off. This could also be
accomplished using the Jog input functions when there is no program running.
Do While (TRUE)
If(DriveInput.2=ON) Then
Wait For DriveInput.2=OFF
Jog.Stop
Endif
If (DriveInput.3=ON) Then
Jog.0.MinusInitiate
Wait For DriveInput.3=OFF
‘Repeat until the program is halted
‘Jog+ when DriveInput.2=ON
Jog.0.PlusInitiate‘Vel=20in/s
‘Stop jogging when DriveIput.2 goes OFF
‘Decelerate to a stop
‘Jog- when DriveInput.3=ON
‘Vel=20in/s
‘Stop jogging when DriveInput.3 goes OFF
140
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Jog.Stop
Endif
Loop
‘Decelerate to a stop
Rotary Table with “Calibrated” Stop Positions
Home the axis, wait for an input and then index to 3 different stop positions (absolute positions), wait for an input between
indexes. The InPosn output function could be assigned to an output to indicate when the axis has completed the index and the
following error is less than a specified amount. Since the indexes are to absolute positions they can be adjusted to “calibrate”
the stop positions to account for mechanical non-linearity in the particular rotary table. A rollover position of 360.00 degrees
would be entered into the setup view so that the system would take the shortest path (across the rollover) during the last
move.
Home.0.Initiate
‘Sensor,Offset=0.0deg/s,Vel=-1000deg/s
Do While (TRUE)
Wait For DriveInput.1=ON
Index.2.Initiate
Wait For InPosn
Wait For DriveInput.1=ON
Index.3.Initiate
Wait For InPosn
Wait For DriveInput.1=ON
Index.1.Initiate
Wait For InPosn
Loop
‘Repeat until the program is halted
‘DriveInput.1 is the “Go” input
‘Absolute,Dist=120.07deg,Vel=1000deg/s
‘Absolute,Dist=239.95deg,Vel=1000deg/s
‘Absolute,Dist=0.03deg,Vel=1000deg/s
Flying Cutoff/Shear
Flying cutoff or flying shear application to perform synchronized out and return indexes which repeat every 100 inches of
master travel.
Part Length = 100 inches
Knife Travel Distance = 20 inches
PLS.0 is used to initiate Index.0 every 100 inches. PLS.0 has an “ON” point at 0.000 inches and an “OFF” point at 90.000
inches. PLS.0 has a rollover position of 100.000 inches. The rollover position is used to set the part length. The source for
PLS.0 is the master axis. The PLS is configured in the PLS view. The PLS output does not necessarily need to be connected
to an output line on the drive because it is used within the program to initiate an index.
An Index PLS is used to fire the cutoff knife. The Index PLS is connected to Output #1 on the drive. The Index PLS is
configured in the index setup view. The Index PLS for Index.1 has an “ON” point 2.000 inches into the index and an “OFF”
point 18 inches into the index.
Home.0.Initiate
MasterAxis.DefineHome=ON
PLS.0.Enable=ON
Do While (TRUE)
Wait For DriveInput.1=ON
If PLS.0.Status = ON Then
DriveOutput.4=ON
End
Endif
Wait For PLS.0.Status=ON
‘Sensor,Offset=1.000in,Vel=-5.0 in/s
‘Set the master position to 0.0
‘Turn on PLS.0
‘Repeat until the program is halted
‘Input 1 is used as a “hold” input.
‘If the PLS is already on you are too late.
‘Set a “Too Late” output
‘Drop out of the program
‘Start the Index when PLS.0 goes on
‘(every 100 inches).
Index.1.Initiate
‘Incremental,Sync,Dist=20.0in,Vel=1.0in/in
Index.0.Initiate
‘Absolute,Sync,Dist=0.0in,Vel=2.0in/in
Wait For Index.AnyCommandComplete
Loop
Synchronized Jog with Manual Phase Adjustment
The motor controls a lugged conveyor belt which is synchronized to another lugged conveyor belt. Jog.0 is configured as a
“Synchronized” jog using the setup software. The program first homes the follower and then waits for an input from a sensor
on the master axis lugs. When the input comes on the follower starts the synchronized jog. If the home is setup correctly the
follower will be in perfect phase when it gets up to speed. If the follower gets out of phase with the master the operator can
manually bring the it back into phase using “Advance” and “Retard” inputs. The program adjusts the phase of the follower axis
by adjusting the jog velocity (Jog.0.Vel) when the operator hits one of the phasing inputs.
Home.0.Initiate
Epsilon EP-P Drive Reference Manual
Revision A3
‘Sensor,Offset=2.25in,Vel=10in/s
141
www.emersonct.com
Jog.0.Vel=1.000
‘follower inches/master inch
Wait For DriveInput.1=ON
Jog.0.PlusInitiate
‘Start when a master lug is detected
‘Sync,Vel=1.000in/in
Do While (TRUE)
If (DriveInput.2=ON) Then
Jog.0.Vel=1.100
Wait For DriveInput.2=OFF
Jog.0.Vel=1.000
Endif
‘Repeat until the program is halted
‘Phase Advance when DriveInput.2=ON
‘follower inches/master inch
If (DriveInput.3=ON) Then
Jog.0.Vel=0.900
Wait For DriveInput.3=OFF
Jog.0.Vel=1.000
Endif
‘follower inches/master inch
‘Phase Retard when DriveIput.3=ON
‘follower inches/master inch
‘follower inches/master inch
Loop
Auger Filler with Inputs to Adjust the Fill Amount
Incremental indexes are used to squirt a specified amount of food product into a box. Inputs are used to adjust the index distance. It would be
much simpler to adjust the index distance with an OIT-3165 operator interface panel, but inputs could be used as described below.
DriveOutput.3=OFF
DriveOutput.4=OFF
Do While (TRUE)
‘Repeat until the program is halted
If (DriveInput.2=ON) Then
‘Fill a box if the “Go” input is on.
Index.1.Initiate
‘Incremental,Dist=16.00oz,Vel=16.0oz/s
Wait For Index.AnyCommandComplete
Endif
‘Increase the fill amount once every time DriveInput.3 is pressed
If((DriveInput.3=ON) AND (DriveOutput.3=OFF)) Then
Index.1.Dist = Index.1.Dist + 0.10‘ounces
DriveOutput.3=ON
‘DriveOutput.3 is used to make sure that the distance is
‘incremented only once each time DriveInput.3 is pressed.
If (Index.1.Dist > 20) Then
DriveOutput.1=ON
‘Long index output
Else
DriveOutput.1=OFF
Endif
Endif
If((DriveInput.3=OFF) AND (DriveOutput.3=ON)) Then
DriveOutput.3=OFF
Endif
‘Decrease the fill amount once every time DriveInput.4 is pressed.
If ((DriveInput.4=ON) AND (DriveOutput.4=OFF)) Then
Index.1.Dist = Index.1.Dist - 0.10 ‘ounces
DriveOutput.4=ON
‘DriveOutput.4 is used to make sure that the distance is
‘incremented only once each time DriveInput.4 is pressed.
If (Index.1.Dist < 12) Then
DriveOutput.2=ON
‘Short index output
Else
DriveOutput.2=OFF
Endif
Endif
142
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
If((DriveInput.4=OFF) AND (DriveOutput.4=ON)) Then
DriveOutput.4=OFF
Endif
Loop
Sequence Learn and Playback
This example consists of three programs. The first program is used to learn 3 positions using “Jog+”, “Jog-“, “Jog Fast” and
“Learn” inputs. The second program is called several times by the first program. The third program steps through the learned
positions
Learn Program (Program 0)
Home.0.Initiate
‘Sensor,Offset=0.000in,Vel=-10in/s
Index.1.Initiate
‘Move to position 1
Wait For Index.AnyCommandComplete
Call Program.1
If (DriveInput.1=ON) Then
Index.1.Dist = PosnCommand
Endif
Wait For DriveInput.1=OFF
Wait For DriveInput.2=OFF
‘Program 1 allows the axis to be jogged
‘into position
‘Learn the new position if the “Learn”
‘input is on
‘Read the Position Command into Index.1’s
‘absolute position.
‘Wait until the “Learn” input goes off
‘Wait until the “Skip” input goes off
Index.2.Initiate
‘Move to position 2
Wait For Index.AnyCommandComplete
Call Program.1
If (DriveInput.1=ON) Then
Index.2.Dist = PosnCommand
Endif
Wait For DriveInput.1=OFF
Wait For DriveInput.2=OFF
‘Program 1 allows the axis to be jogged
‘into position
‘Learn the new position if the “Learn”
‘input is on
‘Read the Position Command into Index.2’s
‘absolute position.
‘Wait until the “Learn” input goes off
‘Wait until the “Skip” input goes off
Index.3.Initiate
‘Move to position 3
Wait For Index.AnyCommandComplete
Call Program.1
If (DriveInput.1=ON) Then
Index.3.Dist = PosnCommand
Endif
Wait For DriveInput.1=OFF
Wait For DriveInput.2=OFF
‘Program 1 allows the axis to be jogged
‘into position
‘Learn the new position if the “Learn”
‘input is on
‘Read the Position Command into Index.3’s
‘absolute position.
‘Wait until the “Learn” input goes off
‘Wait until the “Skip” input goes off
Subroutine for Jogging the Axis into the Desired Position (Program 1)
‘Allow jogging until either the “Learn” input (DriveInput.1)
‘or the “Skip” input (DriveInput.2) goes ON.
Do While ((DriveInput.1=OFF) AND (DriveInput.2=OFF))
If (DriveInput.3=ON) Then
‘Jog+ if the Jog+ input is on
Jog.0.PlusInitiate
‘Vel=0.1in/s
Do While (DriveInput.3=ON)
If (DriveInput.5=ON) Then
Jog.0.Vel = 1.0
Else
Jog.0.Vel = 0.1
Epsilon EP-P Drive Reference Manual
Revision A3
‘DriveInput.5 = “Jog Fast”
‘in/s
‘in/s
143
www.emersonct.com
Endif
Loop
Jog.Stop
Endif
‘Stop jogging when the Jog+ input goes off.
If (DriveInput.4=ON) Then
Jog.0.MinusInitiate
‘Jog- if the Jog- input is on
‘Vel=0.1in/s
Do While (DriveInput.4=ON)
If (DriveInput.5=ON) Then
Jog.0.Vel = 1.0
Else
Jog.0.Vel = 0.1
Endif
Loop
Jog.Stop
Endif
Loop
‘DriveInput.5 = “Jog Fast”
‘in/s
‘in/s
‘Stop jogging when the Jog+ input goes off.
Playback Program (Program 2)
Home.0.Initiate
‘Sensor,Offset=0.000in,Vel=-10in/s
Do While (TRUE)
Index.1.Initiate
Wait For InPosn
DriveOutput.1=ON
Wait For Time 1.000
DriveOutput.1=OFF
‘Repeat until the program is halted
‘Absolute,Posn=1.000in,Vel=5in/s
Index.2.Initiate
Wait For InPosn
DriveOutput.1=ON
Wait For Time 1.000
DriveOutput.1=OFF
Index.3.Initiate
Wait For InPosn
DriveOutput.1=ON
Wait For Time 1.000
DriveOutput.1=OFF
Loop
‘Turn on DriveOutput.1 for 1 second
‘seconds
‘Absolute,Posn=20.000in,Vel=7in/s
‘Turn on DriveOutput.1 for 1 second
‘seconds
‘Absolute,Posn=5.250in,Vel=10in/s
‘Turn on DriveOutput.1 for 1 second
‘seconds
144
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
5
Parameter Descriptions
This section lists all programmable and feedback parameters available. The parameters are listed alphabetically by variable
name (shown in italics below the on screen name) and give a description. Range is dynamic and depends on User Unit
scaling. The units of the parameters are dynamic and depend on selected User Units.
Absolute Position Valid
AbsolutePosnValid
This source is activated when either the DefineHome destination is activated, or any home routine is successfully completed
(sensor or marker found). This source is deactivated if the drive is rebooted, an encoder fault occurs, the drive is powered
down, a home is re-initiate, or the UndefinedHome destination activates.
Accelerating
Accelerating
This source is active when the drive is executing an acceleration ramp. A normal index consists of 3 segments: Accelerating,
At Velocity, and Decelerating. The Accelerating source will be set (active) during this acceleration segment regardless of
whether the motor is speeding up or slowing down. Therefore, this source can sometimes be active when the motor is
decelerating. This could be true when compounding indexes together.
Acceleration Type
AccelType
This parameter is used to select the accel/decel type for all motion (homes, jogs and indexes). The “S-Curve” ramps offer the
smoothest motion, but lead to higher peak accel/decel rates. “Linear” ramps have the lowest peak accel/decel rates but they
are the least smooth ramp type. “5/8 S-Curve” ramps and “1/4 S-Curve” ramps use smoothing at the beginning and end of the
ramp but have constant (linear) accel rates in the middle of their profiles. The “5/8 S-Curve” is less smooth than the “S-Curve”
but smoother than the “1/4 S-Curve”. S-Curve accelerations are very useful on machines where product slip is a problem.
They are also useful when smooth machine operation is critical. Linear ramps are useful in applications where low peak
torque is critical. Below is a comparison of the 4 ramp types:
•
S-Curve: Peak Accel = 2 x Average Accel
•
5/8 S-Curve: Peak Accel = 1.4545 x Average Accel
•
1/4 S-Curve: Peak Accel = 1.142857 x Average Accel
•
Linear: Peak Accel = Average Accel
Acceleration Decimal Places
AccelUnits.Decimal
This parameter is the decimal point location for all real-time accel./decel. ramps.
Acceleration Time Scale
AccelUnits.TimeScale
This parameter is the time units for accel./decel. ramps. Possible selections are milliseconds or seconds.
At Velocity
AtVel
This source is active when the drive is executing a constant velocity motion segment. One example would be during an index.
The source would activate after the motor has finished accelerating up to speed and before the motor begins to decelerate to
a stop. A normal index consists of 3 segments: Accelerating, At Velocity, and Decelerating. This source is active during the At
Velocity segment, and is activated based on the commanded velocity, not the feedback velocity. During synchronized motion,
AtVel can be active without actual motor movement.
Bit Number Value
Bit.B#
This read/write bit may be used in a program as an intermediary variable bit controlled by the user. Bit.B# is one of 32 bits that
make up the BitRegister parameter. Assigned to communication networks such as DeviceNet, Profibus and Modbus, Bit.B#
may be used to transfer events that have occurred in a PLC to the program.
NOTE
When the value of Bit.B# is changed, the value of BitRegister.#.Value is changed as well.
Epsilon EP-P Drive Reference Manual
Revision A3
145
www.emersonct.com
Bit Register Number Value
BitRegister.#.Value
This parameter is made up of the combination of the 32 Bit.B#. The BitRegister.#.Value. The BitRegister.#.Value register may be accessed
bitwise by using Bit.B#, or double word-wise by using BitRegister.#.Value.
Bit Register Number Value Mask
BitRegister.#.ValueMask
This parameter is the Mask for the BitRegister.#.Value. Each bit location is set to either transfer the current data in the corresponding bit
location of BitRegister.#.Value (by setting the bit location to 1) or to clear the current data in BitRegister.#.Value (by setting the bit location to 0).
Brake Activate
Brake.Activate
This destination, when activated, engages the brake. This is simply used to manually engage the brake outside of the normal brake operation.
This is level sensitive.
Brake Disengaged
Brake.Disengaged
This source is used to control the motor holding brake. When it is "off" the brake is mechanically engaged. When the brake is engaged, the
diagnostic display on the front of the drive will display a "b". The drive outputs are limited to 150 mA capacity, therefore, a suppressed relay is
required to control the brake coil. Model BRM-1 may be used.
Brake Release
Brake.Release
This destination will release the brake under all conditions, even when Brake.Activate is engaged. When this input function is active, the
Brake.Disengaged output function (source) will be activated. This is used as a manual brake override.This is level sensitive.
Active Point
Cam.ActivePoint
This parameter is the point within a cam table that is being executed. This is useful to determine the cam location when a fault occurs. This is
only available when online.
Active Table
Cam.ActiveTable
This parameter is active when the cam table instance number is being executed. This is useful to determine the cam location when a fault
occurs. Only available when online.
Direction
Cam.CamDirection
When CamPlus is selected the cam only moves in the forward direction and only chains in the forward direction. If in CamPlus mode and the
master axis moves backwards, the cam stops motion and will not continue its forward motion until the master has moved back into position
where it started to move backwards.
When Bidirectional is selected the cam will follow the path backwards and will backwards chain to another cam table. This parameter is
accessible on the Cam view. The user can change the Cam.CamDirection in a program, it will take effect in the next Cam.#.Initiate.
Realtime cams move only in the CamPlus direction. If you backup from a bidirectional sync cam into a realtime cam the cam will fault. If you
have this configuration, we recommend you add a backup cam table for a sync table to handle transition jitter.
Captured Master Position Homed
Cam.CaptureMasterPosHomed
This parameter is the master commanded position captured when the current running cam table was initiated, value is referenced to home. If
the cam is not running it is the “Master Position Homed ” when the cam was exited (by stop, suspend, or normal completion).
Captured Master Position
Cam.CapturedMasterPosition
The master commanded position captured when the current running cam table was initiated. If the cam is not running it is the “Master Position”
when the cam was exited (by stop, suspend, or normal completion).
146
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Captured Position Command
Cam.CapturedPositionCommand
The follower commanded position captured when the current running cam table was initiated. If the cam is not running it is the
"Position Command" when the cam was exited (by stop, suspend, or normal completion).
Captured Position Feedback
Cam.CapturedPositionFeedback
The follower feedback position captured when the current running cam table was initiated. If the cam is not running it is the
"Position Feedback" when the cam was exited (by stop, suspend, or normal completion).
Captured Time
Cam.CapturedTime
Time the current running cam table was initiated. If the cam is not running it is the time when the cam was exited (by stop,
suspend, or normal completion).
Command Complete
Cam.CommandComplete
This pararmeter is active when any cam motion command is completed. If a stop is activated before the cam has completed,
this parameter will not activate. This parameter is deactivated when any cam command is initiated.
Commanding Motion
Cam.CommandingMotion
This source is active (on) when any Cam table is executing. Note this source may be on even when no physical motor motion
is occurring. For example the master may not be moving, but the follower is still considered to be in a Commanding Motion
state.
Stop Decel Enable Check Box
Cam.DecelEnable
When the check box is selected (activated) the Cam.StopDecel parameter is used when Cam.Stop and Cam.Suspend
commands are activated.
Resume
Cam.Resume
Resumes the cam execution from a Cam.Suspend command (or SetCamMasterOffset(MasterPosn), or
SetCamFollowerOffset(FollowerPosn). The cam points are all relative to the start of the Cam table. On Cam.Resume the
current physical position becomes the cam start point and the cam aligns it’s resume position to the current physical position
without any physical movement. This means if you suspend a cam and move the physical position; for example with a Jog,
you will need to position the motor back to the desired position before resuming.
Cam.Resume will be ignored if executed without Cam.ResumeAvailable set.
Resume Available
Cam.ResumeAvailable
Indicates that the cam is in a state where it will accept the Cam.Resume command. The cam can be resumed after executing
a Cam.Suspend, SetCamMasterOffset(masterPosn), or SetCamFollowerOffset(FollowerPosn). Cam.Resume will be ignored
if executed without Cam.ResumeAvailable set.
This source is active when a cam Resume is available.
To alter the pattern a program is run concurrently with the cam motion and the Cam.#.ForwardChain and
Cam.#.BackwardsChain are changed on the fly to alter the motion pattern. To get even more flexibility you can dynamically
alter the cam data table itself with the cam[t,e]xxx commands. You can even alter the size of the table.
Accepts Motion Modifiers
Action
Cam[table,element].Master=
Writes to a cam table’s master value
Cam[table,element].Follower=
Writes to a cam table’s follower value
Cam[table,element].Interpolation=
Writes to a cam table’s master value. There is no range checking of interpolation until
cam execution. If the cam type does not support Interpolation, a parm not found fault
is generated
= Cam[table,element].Master
Reads the cam table’s master value
Epsilon EP-P Drive Reference Manual
Revision A3
147
www.emersonct.com
Accepts Motion Modifiers
Action
= Cam[table,element].Follower
Reads a cam table’s follower value
= Cam[table,element].Interpolation
Reads a cam table’s interpolation value
In the table above “table” and “element” are expressions.
The time based index is defined as a cam component. Time based index allows easy entry to dynamically define either the distance at a fixed
time or dynamically define time at a fixed distance or dynamically alter both distance and time.
Resume Follower Position
Cam.ResumeFollowerPosn
This will be the initial Follower Position the cam will be set to on execution of the Cam.Resume command. This value is valid only after
Cam.Suspend, SetCamMasterOffset(MasterPosn), or SetCamFollowerOffset(FollowerPosn) commands.
Resume Master Position
Cam.ResumeMasterPosn
For cam tables running in synchronized mode, this will be the initial Master Position the cam will be set to on execution of the Cam.Resume
command. This value is valid only after Cam.Suspend, SetCamMasterOffset(MasterPosn), or SetCamFollowerOffset(FollowerPosn)
commands.
Resume Master Time
Cam.ResumeMasterTime
For cam tables running in real time mode, This will be the initial Master Time the cam will be set to on execution of the Cam.Resume
command. This value is valid only after Cam.Suspend, SetCamMasterOffset(MasterPosn), or SetCamFollowerOffset(FollowerPosn)
commands.
Stop
Cam.Stop
When Cam.Stop is activated the cam will stop using the Cam.Decel ramp rate (if Cam.DecelEnable is enabled).
Stop Decel
Cam.StopDecel
This parameter is the deceleration rate of the cam after a Cam.Suspend or Cam.Stop command is initiated. A value of zero disables the stop
decel ramp as well as clearing the Stop Decel Enable check box.
Suspend
Cam.Suspend
When Cam.Suspend is activated the current cam will stop using the Cam.Decel ramp rate (if Cam.DecelEnable is enabled). The cam will
accept a Cam.Resume after a suspend. The suspend records the master and follower positions at the point of the suspend for future
Cam.Resume execution.
Max Accel
Cam.#.Accel
This parameter is the maximum acceleration for the Time Base Index cam type. The time base index will not accelerate faster than this value.
Backward Chain
Cam.#.BackwardChain
This parameter holds the next cam table to initiate if this cam table completes in reverse (master axis is moving from larger to smaller position
values). This is only available in bidirectional mode. The next cam table will be initiated at the end (which is really the starting point) of the
current table. If no cam is to be initiated, this value should be set to –1 (minus one) to stop at the end of the cam table execution.
Cam Table Complete
Cam.#.CamTableComplete
This parameter is active when the specified cam table motion command is completed, if a stop is activated before the cam has completed this
parameter will not be activated. Inactivated when the specified cam command is executed.
148
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Cam Table In Motion
Cam.#.CamTableInMotion
This parameter is active (on) when the specified cam table is executing. Note this source may be on even when no physical
motor motion is occurring. For example the master may not be moving, but the follower is still considered to be in a
Commanding Motion state.
Cam Table Size
Cam.#.CamTableSize
This parameter is the number of elements entered in the specified cam table.
Writable Check Box
Cam.#.CamTableWritable
Moves the cam table into ram memory so the user can change the cam table values using a program.
Cam Type
Cam.#.CamType
Cam types to choose from are; Master Follower, Absolute MFI, Incremental MFI, Cubic Spline, or Time Based Index. Most
data entries are “Absolute” which means each point is an absolute distance from the start of the cam table which is an implied
zero, although the starting value does not have to be zero. The Incremental MFI (Master/Follower/Interpolation) has the
entries as distance deltas from point to point which means the point is relative to the previous point.
Decel
Cam.#.Decel
This parameter is the maximum deceleration for the Timed Index. The timed index will not decelerate faster than this value.
Distance
Cam.#.Dist
This parameter is the incremental distance the timed index will move.
Final Velocity
Cam.#.FinalVelocity
The cam table profile will exit at this velocity. See Initial Velocity for more information. When using a single cam table, with no
chaining, simply set the Initial Velocity to zero.
Forward Chain
Cam.#.ForwardChain
This parameter holds the next cam table to initiate when this cam table is completed. If no cam table is to be initiated, this
parameter should be set to -1 (negative one) to stop the cam at the end of the current table. The cam will then conclude
execution.
Forward chain and Backward chain can be dynamically changed by a user program. For example, a program monitors the
cam motion flow and alters the forward and backward chain variables to switch the flow. You can have a start up sequence of
tables, a running sequence of tables, a shut down sequence of tables and a alternate operation sequence of tables. The
monitoring program adjusts the chains to dynamically change the cam sequence.
The cam tables themselves can be altered on the fly as long as you are altering the non-executing cam table. Each cam point
is accessible by the user program provided the Writable check box has been selected.
Index Time
Cam.#.IndexTime
The Timed Base Index will slow down the index velocity so the index will run for this parameter value. The acceleration and
deceleration will be reduced to meet the distance and index time of this timed base index.
Initial Velocity
Cam.#.InitialVelocity
This is the entry point velocity for the cam table. For Master Follower this is a calculated value. The user should take care in
matching the velocity transitions when chaining one cam profile into another.
For MFI and Spline cam tables: If the first segment interpolation type is Linear, the initial velocity is the calculated velocity of
the first segment. When using a single cam table, with no chaining, simply set the Initial Velocity to zero.
Epsilon EP-P Drive Reference Manual
Revision A3
149
www.emersonct.com
Initiate
Cam.#.Initiate
Cam.#.Initiate has two forms - Program Instruction and Assignment (as a Destination). Both are used to initiate a specific Cam. For the
Destination, the Cam is initiated on the rising edge of this event. Using the Destination, a Cam cannot be initiated if there is an Index, Home,
Jog, or Program in progress, or if the Cam.#.Initiate is an instruction. If any motion is active, the program will hold on this instruction until that
motion is complete (unless it is run on a different profile).
Interpolation
Cam.#.Interpolation
This a Timed Index parameter. The Interpolation method to be used for the acceleration and deceleration portion of the timed Index.
Interpolation types are Square, S-Curve and Jerk.
Name
Cam.#.Name
The user can specify a cam name of up to 12 alphanumeric characters. This allows assigning a descriptive name to each cam table indicating
different machine operations.
Repeat
Cam.#.Repeat
This parameter specifies how many times in a row the cam table is to run before proceeding on to the next cam table as defined by Forward
Chain or Backward Chain text boxes. To repeat a single cam table forever use the Forward Chain and Backward Chain and set the chain value
to it own cam table number.
Table Limit
Cam.#.TableLimit
The cam table execution is limited to this value, so you can programmatically change the size of the cam table execution. On download and
restart, this is initialized to match the Cam.#.CamTableSize. If you attempt to set Cam.#.TableLimit > Cam.#.CamTableSize it will be set to the
maximum, Cam.#.CamTableSize.
Time Base
Cam.#.TimeBase
This list box selects the Time Base for the cam master position entries. Realtime and Synchronized (to the Master Encoder) are allowed
selections.
Max Velocity
Cam.#.Vel
This parameter is the maximum velocity of the Timed Base Index.
Number
Capture.Number
This parameter defines the size of the Capture list.
Capture Activate
Capture.#.CaptureActivate
If the Capture component is enabled and has been reset (CaptureTriggered is inactive), then the rising edge of CaptureActivate will capture
the four data parameters and cause CaptureTriggered to be activated. If the Capture component is not enabled, or has not been reset, the
CaptureActivate will be ignored.
Capture Clear
Capture.#.CaptureClear
This command may be used within a program to rearm the capture for the next cycle. This command can be used instead of Capture.#.Reset
destination which needs to be cleared after a control loop cycle to allow another reset.
Capture Enable
Capture.#.CaptureEnable
The CaptureEnable is used to enable or “arm” the capture component. If the CaptureEnable is not active, then the CaptureActivate has no
150
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
effect, and the CaptureTriggered remains inactive. Once the CaptureEnable is activated, the Capture component is ready and
waiting for a CaptureActivate signal to capture data. CaptureEnable is a read-only destination on the Assignments view, and is
accessible through a user program.
Capture Reset
Capture.#.CaptureReset
The CaptureReset is used to reset or re-arm the capture component after it has been activated. If the capture has been
activated, the CaptureTriggered destination will be active. The capture component cannot capture data again until it has been
reset. The capture component will automatically reset itself if the CaptureEnable signal is removed.
Capture Triggered
Capture.#.CaptureTriggered
The CaptureTriggered signal is read-only and indicates that the Capture component was activated and that data has been
captured. CaptureTriggered will activate on the leading edge of CaptureActivate if the Capture component is enabled and
reset. Capture Triggered will remain active until CaptureReset is activated.
Captured Master Position Homed
Capture.#.CapturedMasterPosHomed
On the rising edge of the Capture Activate event, the master axis position is captured (in counts). The captured counts value is
then converted into Master Distance User Units and stored in the Captured Master Position parameter. If the user redefines
the zero position of the master axis, the master position in User Units is zeroed out, however the counts parameter is not.
Therefore, if another capture occurs after the position has been zeroed, the value stored in the Captured Master Position
parameter will be off by the value of the master axis before the position was zeroed out. This parameter is to be used if the
master axis position is redefined after power-up.
Captured Master Position
Captured.#.CapturedMasterPosition
The master axis feedback position, in master axis distance units, at the time when CaptureTriggered activated.
Captured Position Command
Capture.#.CapturedPositionCommand
The command position, in user units, at the time when CaptureTriggered activated.
Captured Position Feedback
Capture.#.CapturedPositionFeedback
The feedback position, in user units, at the time when CaptureTriggered activated.
Captured Time
Capture.#.CapturedTime
The time, in microseconds, from a free-running 32-bit binary counter at which CaptureTriggered activated.
Name
Capture.#.Name
You can assign a descriptive name to each capture, making the setup easier to follow. The length of the text string is limited by
the column width with a maximum of 12 characters. Simply double click on the Name field of any capture’s line to assign a
name to it.
Clear Following Error
ClearFollowingError
Clear Following Error is a destination found in the Position group on the Assignments view. When this destination is activated,
any following error that has accumulated will be erased. Following Error is cleared by setting the commanded position to the
feedback position, automatically resulting in a zero following error. The drive will deactivate the Clear Following Error
destination as soon as Following Error is zero.
Commanding Motion
CommandingMotion
This source activates when VelCommand is non-zero.
Epsilon EP-P Drive Reference Manual
Revision A3
151
www.emersonct.com
Commutation Angle Correction
CommutationAngleCorrection
The difference between the electrical angle as determined at power up from the U, V, and W commutation tracks and the electrical angle as
determined from the marker pulse or UVW transitions. This value will be zero until the marker pulse is detected or UVW transition is detected.
Commutation Track Angle
CommutationTrackAngle
This parameter is derived directly from the state of commutation tracks and the Encoder U Electrical Angle parameter.
Commutation Voltage
CommutationVoltage
This parameter is used to determine commutation angle accuracy. When queried it returns the value of the direct axis voltage. The value is
given as a percentage of 1/2 the bus voltage.
Decelerating
Decelerating
This source is active when the drive is decelerating. A normal index consists of 3 segments: Accelerating, At Velocity, and Decelerating.
Decelerating follows the accelerating segment and the At Velocity segment. When indexes are compounded to create a complex motion
profile, only the last index may contain a decelerating segment.
Define Home
DefineHome
This destination is used to set the Commanded Position to the value specified in the DefineHomePosn variable. On the rising edge of this input
function the absolute position is set equal to the DefineHomePosn and the AbsolutePosnValid output function (source) is activated.
Define Home Position
DefineHomePosn
This is the value to which the position command will be set when the Define Home Destination is activated, This is used in applications that do
not use a home routine, but is required to define a known reference point.
Acceleration
DistanceRecovery.Accel
This parameter in user units is the acceleration rate for the distance recovery index.
Deceleration
DistanceRecovery.Decel
This parameter in user units is the deceleration rate for the distance recovery index.
Enable Distance Recovery
DistanceRecovery.DistanceRecoveryEnable
Select the check box to enable the additive distance recovery index feature.
Velocity
DistanceRecovery.Vel
This parameter in user units is the velocity limit of the distance recovery index.
Characteristic Distance
DistUnits.CharacteristicDistance
This parameter is the distance the load travels (in user units) when the motor travels the characteristic length (in motor revolutions). This
parameter is used along with the DistUnits.CharacteristicLength to establish the relationship between user distance and actual motor travel
distance. See the section on the User Units View in the Setting Up Parameters chapter.
Characteristic Length
DistUnits.CharacteristicLength
This parameter is the distance the motor travels (in whole number of revolutions) to achieve one characteristic distance of load travel. This
152
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
parameter is used along with the DistUnits.CharacteristicDist to establish the relationship between user distance and motor
travel distance. See the section on the User Units View in the Setting Up Parameters chapter.
Distance Decimal Places
DistUnits.Decimal
This parameter is used to select the number of decimal places used in the DistUnits.CharacteristicDist. Using a high number
of decimal places will improve positioning resolution, but will also limit the maximum travel distance. The number of decimal
places set in this parameter determines the number of decimal places used in all distance parameters throughout the
software. You can select from zero to six decimal places of accuracy.
Distance Units Name
DistUnits.Name
This is a text variable which is used as the label for the distance/position user units. It can be up to 12 characters in length.
Enable Channel Check Box
DriveAnalogInput.ChannelEnable
By default, the analog input channel is enabled meaning that the drive is reading the A/D value read by the analog circuit. If
the check box is clear, the channel is not enabled and the configuration parameters for the analog input is unavailable and
therefore has no effect.
To enable the analog input, simply select the Enable Channel check box, and the configuration parameters will become
available to edit. With the channel enabled, the trajectory loop update will transfer data from the drive into
DriveAnalogInput.RawValue as volts and into DriveAnalogInput.ValueIn scaled.
Destination Variable
DriveAnalogInput.CustomDestinationVariable
PowerTools Pro displays a text box that the user can enter any available parameter using the dot notation format for the
variable on the Analog Inputs View.
When the Popup Variables... button is pressed a window will open containing the list of variables that can be dragged into the
Destination Variable text box.
Destination Variable is used to allow Position Tracker or Correction index types to perform an index to the scaled analog value.
Set the Destination Variable to an index distance parameter. When the index type is set to Position Tracker, the Analog to
Position scaling is used to scale the index’s absolute position. When the index type is set to Correction, the Analog to Distance
scaling is used to scale the index’s incremental distance.
Bandwidth
DriveAnalogInput.LowPassFilterFrequency
This parameter sets the low-pass filter cutoff frequency applied to the analog input. Signals exceeding this frequency will be
filtered at a rate of 20 db per decade.
Maximum Value
DriveAnalogInput.MaxUserValue
Enter the maximum value in analog user units that the maximum analog voltage should correspond to. Set Maximums Group.
Maximum Voltage
DriveAnalogInput.MaxVoltageValue
Enter the maximum voltage that will be seen on the analog input terminals. The user can enter the value in this field by hand,
or set the analog source to it’s maximum value, and click on the “Set Max Voltage to Measured” button next to the text box on
the Analog Inputs view. This will read the current value on the analog channel and enter it into the Maximum Voltage text box.
Minimum Value
DriveAnalogInput.MinUserValue
Enter the minimum value in analog user units that the minimum analog voltage should correspond to.
Minimum Voltage
DriveAnalogInput.MinVoltageValue
Enter the minimum voltage that will be seen on the analog input terminals. The user can enter the value in this field by hand,
or set the analog source to it’s minimum value by clicking on the "Set Min Voltage to Measured" button next to the text box.
This will read the current value on the analog channel and enter it into the Minimum Voltage text box. This parameter is used
Epsilon EP-P Drive Reference Manual
Revision A3
153
www.emersonct.com
for user units scaling.
A/D Voltage
DriveAnalogInput.RawValue
This is the raw analog input value in Volts.
Set Max Voltage To Measured
DriveAnalogInput.SetMax
Activate to set the maximum voltage to the current reading of the Analog Input channel.
Set Min Voltage To Measured
DriveAnalogInput.SetMin
Activate to set the minimum voltage to the current reading of the Analog Input channel.
Enable Channel
DriveAnalogOutput.#.ChannelEnable
By default, the analog output channel is not enabled meaning that a value is not being sent to the analog circuit. When the channel is not
enabled (cleared), the configuration parameters for that analog output is unavailable and therefore has no effect. To enable the output, simply
select the Enable Channel check box, and the configuration parameters will become available to edit.
If the user wishes to control the Analog Output through other means, it is necessary to clear the Enable Channel check box.
Custom Variable
DriveAnalogOutput.#.CustomSourceVariable
The Custom Variable parameter is only available once the user has selected Custom Variable from the Source list box. The field is used to
define what parameter will control the Analog Output. This means that the selected variable parameter will directly determine the value of the
analog output based on the Max and Min scaling values entered on this view. When the Popup Variables... button is pressed a window will
open containing the list of variables that can be dragged into the Custom Variable text box.
Drive Analog Output Feedback
DriveAnalogOutput.#.Feedback
Displays the Output voltage from one of the two analog outputs found on the drive analog/sync connector.
Analog Output - Maximum Output
DriveAnalogOutput.#.MaxOutputValue
The analog output is a linear interpolation of the selected module variable between the minimum and maximum specified end points. Each end
point is specified as the user value and the corresponding output value at that point. The number of decimal places for both values is taken
from the selected source variable. MaxOutputValue is the maximum analog output value which corresponds to the maximum user value.
Analog Output - Maximum Value
DriveAnalogOutput.#.MaxUserValue
The analog output is a linear interpolation of the selected module variable between the minimum and maximum specified end points. Each end
point is specified as the user value and the corresponding output value at that point. The number of decimal places for both values is taken
from the selected module variable. MaxUserValue is the maximum user unit value which corresponds to the maximum analog output value.
Analog Output - Minimum Output
DriveAnalogOutput.#.MinOutputValue
The analog output is a linear interpolation of the selected module variable between the minimum and maximum specified end points. Each end
point is specified as the user value and the corresponding output value at that point. The number of decimal places for both values is taken
from the selected module variable. MinOutputValue is the minimum analog output value which corresponds to the minimum user value.
Analog Output - Minimum Value
DriveAnalogOutput.#.MinUserValue
The analog output is a linear interpolation of the selected module variable between the minimum and maximum specified end points. Each end
point is specified as the user value and the corresponding output value at that point. The number of decimal places for both values is taken
from the selected module variable. MinUserValue is the minimum user unit value which corresponds to the minimum analog output value.
154
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Drive Enable Status
DriveEnableStatus
This source is active when the drive is enabled.
Power Up (counts)
DriveFaultLog.#.PowerUpCounts
This indicates during which power up the fault occurred in.
Time (minutes)
DriveFaultLog.#.Time
This indicates the time into the power up that the fault occurred.
Drive Input Debounced
DriveInput.#.Debounced
This displays the state of the input after the debounce is taken into account.
Drive Input Debounce Time
DriveInput.#.DebounceTime
The Drive Input Debounce Time parameter is the minimum time a digital input must be steady in order to be recognized by the
drive. This feature helps prevent false triggering in applications in electrically noisy environments.
Drive Input Force
DriveInput.#.Force
Input can be forced either On or Off. This parameter is the state to which the input will be forced when the ForceEnable bit is
activated.
Drive Input Force Enable
DriveInput.#.ForceEnable
If DriveInput.#.ForceEnable parameter is activated, then the state of the DriveInput.#.Force bit will override the current input
state.
Drive Input Name
DriveInput.#.Name
This is a text string up to 12 characters that can be assigned to a given input. It allows the user to use application specific
terminology in naming digital inputs.
Drive Input Raw
DriveInput.#.Raw
This displays the raw state of the digital input without debounce or forcing to override the raw status.
Drive Input Status
DriveInput.#.Status
This source is the state of the input after debounce and forcing are taken into account.
Drive Output Force
DriveOutput.#.Force
A drive output can be forced either On or Off with this parameter. If the ForceEnable bit is activated, the DriveOutput.#.State
will be set to this value.
Drive Output Force Enable
DriveOutput.#.ForceEnable
If DriveOutput.#.ForceEnable parameter is activated, then the state of the DriveOutput.#.Force bit will override the current
output state.
Epsilon EP-P Drive Reference Manual
Revision A3
155
www.emersonct.com
Drive Output Name
DriveOutput.#.Name
This is a text string up to 12 characters that can be assigned to a given output. It allows the user to use application specific terminology in
naming digital outputs.
Drive Output State
DriveOutput.#State
This destination sets the current state of an output line.
Drive Output Encoder Scaling
DriveOutputEncoder.Scaling
This parameter allows scaling of the drive encoder output resolution in increments of one line per revolution. Allowable range is from one line
per revolution up to the actual density of the encoder in the motor. If the Encoder output scaling is set greater than the motor encoder density
the output scaling will be equal to the motor encoder density.
Drive Output Encoder Scaling Enable
DriveOutputEncoder.ScalingEnable
When on, this parameter enables the use of the drive encoder output scaling feature.
Drive Serial Number
DriveSerialNumber
This displays the serial number of the Drive.
Dual Loop Enable
DualLoopEnable
This Destination is used to initiate, turns on, the Dual Loop feature. The system will remain in this mode as long as this Destination is active.
DualLoopEnable can be assigned or initiate by a user program.
Dual Loop Encoder Ratio - Motor Encoder
DualLoopMotorEncoder
This parameter is the numerator in the ratio used to define the mechanical ratio between the Motor Encoder and the Position Feedback
Encoder. This parameter is only used when Dual Loop Control Mode is enabled, and must be set correctly to achieve the correct target
velocity.
Motor - Position Feedback
DualLoopMotorPosnFdbk
This is the actual motor position in user units. The difference between the PosnCommand and the PosnFeedback is the FollowingError.
Motor - Velocity Feedback
DualLoopMotorVelFdbk
This is the feedback (or actual) velocity. It is calculated using the change in position of the motor encoder. It will always return the actual motor
velocity - even in synchronized applications in which the master axis is halted during a move.
Dual Loop Encoder Ratio - Position Encoder
DualLoopPositionEncoder
This value along with the Motor Encoder value define the mechanical ratio of motor turns to position encoder turns. Typically these values will
have units of encoder counts since this will give the highest degree of accuracy. The user must calculate the mechanical ratio as accurately as
possible for best results.
Dual Loop Position Feedback Polarity
DualLoopPosnFdbkPolarity
Position Feedback Polarity defines the direction of the position encoder that corresponds to a positive position change. This value is somewhat
arbitrary, since the position encoder can be mounted to spin CW or CCW as the material moves "forward". If this value is not set correctly in
Dual Loop mode the motor will rotate in the opposite direction as desired.
156
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Output Source
EncoderOutput.Source
This determines which signal is sent out the Sync Output connector on the drive. If Motor Encoder (default) is selected, the
encoder signals from the motor that the drive is controlling will be sent out the 15-pin Analog/Sync Output connector (J5). If
Drive Encoder Input is selected, then the signals coming in the drives 9-pin Sync Input connector on the drive will be sent out
the Analog/Sync. Output connector. When Virtual Master is selected the virtual master signal generated by the drive will be
sent out the Analog/Sync. Output connector.
Current Data Rate
Ethernet.EthernetConfiguration.DataRate
The data rate is a read-only parameter that indicates the bit rate of communications over the Ethernet Hardware. Supported
Data rated include 10 Mbps Full Duplex and 100 Mbps Full Duplex. The EP-P defaults to auto detect of the network data rate.
Modbus Port Number
Ethernet.EthernetConfiguration.ModbusPortNumber
This parameter is the Modbus TCP port number. Default is 502.
Explicit Parameter - Attribute
Ethernet.EthernetExplicit.#.Attribute
The Ethernet/IP Attribute is a sub-classification for a parameter or bit. The attribute is grouped directly under the broader
category of class.
Ethernet Explicit Command Complete
Ethernet.EthernetExplicit.#.CommandComplete
This Source becomes active when the explicit message process is complete. An Explicit message is complete when it is sent
to another Ethernet/IP device, and the device responds.
NOTE
This parameter does not indicate a successful explicit message. The Ethernet.EthernetExplicit.#.CommandComplete bit
turns "off" when the corresponding Ethernet.EthernetExplicit.#.Initiate is activated and then turns "on" when the command is
complete.
Ethernet Explicit Command In Progress
Ethernet.EthernetExplicit.#.CommandInProgress
This Source activates when the corresponding Ethernet.EthernetExplicit.#.Initiate becomes active and deactivates when the
corresponding Ethernet.EthernetExplicit.#.CommandComplete becomes active.
Ethernet Explicit Initiate
Ethernet.EthernetExplicit.#.Initiate
This Destination starts the explicit messaging process using the data in the corresponding explicit message.
Explicit Parameter – Instance
Ethernet.EthernetExplicit.#.Instance
The Ethernet/IP Instance is a sub-classification for a parameter or bit. The instance is grouped directly under the broader
category of attribute and allows for multiple occurrences of a parameter.
For example: Class = Index, Attribute = Index Dwell. Instance1 = Index 0, Instance2 = Index 1.
Each Instance is assigned a unique number under its respective attribute.
Ethernet Explicit Message Failed
Ethernet.EthernetExplicit.#.MessageFailed
This Source becomes active when the explicit message fails to either send a valid command to another IP address, or when
the explicit message is not accepted from another address. The Ethernet.EthernetExplicit.#.MessageFailed source is cleared
when the corresponding Ethernet.EthernetExplicit.#.Initiate is activated.
Explicit Message - Operation
Ethernet.EthernetExplicit.#.Operation
The operation can be one of two values, "GET" or "SET". The "GET" command defines an explicit message that will be
Epsilon EP-P Drive Reference Manual
Revision A3
157
www.emersonct.com
querying another device for data. The "SET" command defines an explicit message that will be sending data to another device.
As with all Destinations in the Epsilon EP-P, Explicit.Instance.Initiate may be initiated via a program, assignment, or a network connection.
When this parameter is changed from within a program or over a network connection, the following values correspond to the terms GET and
SET.
GET = 0
SET = 1
Explicit Signed Data Check Box
Ethernet.EthernetExplicit.#.SignedData
The Signed Data check box is used for explicit message read commands. When data for the read command comes in, it is stored in the
parameter Ethernet.EthernetExplciit.#.Value. The signed data check box determines whether this data is consumed as a 32 bit signed, or 32
bit unsigned value.
Explicit Message - Value
Ethernet.EthernetExplicit.#.Value
This parameter gives an initial value to "SET" data that will be sent from the FM-3E or FM-4E out onto the network. This parameter is also used
to store the data coming in from an explicit message from a "GET" command.
Module Status
Ethernet.EthernetStatus.EthernetModuleStatus
Module Status is an Ethernet/IP protocol specific parameter that gives feedback data of the Epsilon EP-P drive. Module Status indicates one of
the following conditions: Standby, Operational. Minor Flt, or Major Flt.
Standby - Module is not configured
Operational - Module operating correctly
Minor Flt - A recoverable fault occurred. This fault does not require a power reset.
Major Flt - A non-recoverable fault occurred. The module needs to have it's 24 V power cycled to reset.
Network Status
Ethernet.EthernetStatus.EthernetNetworkStatus
Network Status is an Ethernet/IP protocol specific parameter that gives feedback data on the Ethernet/IP network as it relates to the
corresponding Epsilon EP-P drive. Network Status indicates one of the following conditions: No IP, No Conn, Conn est, Conn Timeout, or Dup
IP.
No IP - The Epsilon EP-P does not have an IP address configured
No Conn - The Epsilon EP-P has no established connections
Conn est - The Epsilon EP-P has at least one established connection
Conn Timeout - At least one of the established connections has timed out.
Dup IP - The Epsilon EP-P has detected that it's IP address is already in use on the network.
Ethernet Status Link Status
Ethernet.EthernetStatus.LinkState
The Link State is a parameter that indicates whether or not the Ethernet 802.3 communications interface is connected to an active network.
Link State as displayed on the LCD keypad indicates one of the following conditions: Active link or Inactive link.
Active Link - The Epsilon EP-P is physically connected to a network.
Inactive Link - The Epsilon EP-P is not physically attached to an operating Ethernet network.
Ethernet Status Rcv Counter
Ethernet.EthernetStatus.RcvCounter
The Receive Counter keeps track of all IP data packets received by the Epsilon EP-P drive. This counter is useful when commissioning the EPP drive to verify incoming communications.
Ethernet Status Xmit Counter
Ethernet.EthernetStatus.XmitCounter
The Transmit Counter keeps track of all IP data packets sent from the Epsilon EP-P drive. This counter is useful when commissioning the EPP drive to verify outgoing communications.
158
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Commutation Hardware Fault Enable
Fault.CommutationHardwareFaultEnable
When this check box is selected or this parameter is enabled, faults occurring from the commutation tracks U, V, and W will be
recognized as "E" faults in the drive. When this check box is clear, no fault will occur due to the commutation tracks. This
functionality can be useful to diagnose the nature of the "E" fault. If the check box is clear and "E" faults are still occurring, then
the encoder lines (A, A/, B, B/, C, C/) are the most likely source of the "E" fault.
Active Fault
Fault.#.Active
The specified fault is active. See the help index for more information on faults and recovery from them.
Clear Non-Critical Fault Counts
Fault.ClearNonCriticalFaultCounts
Set the value to TRUE to reset all of the module fault counts to zero. The read back value is whatever was last set (TRUE or
FALSE). It is not necessary to set it FALSE before setting it TRUE – the act of writing TRUE initiates the operation. Another
way to clear Non-Critical Fault Counts is to click on the Clear Non-Critical Fault Counts button on the Faults view/ Faults
Counts Tab when online with the drive.
Fault Counts
Fault.#.Counts
The drive stores the total number of times the specific fault has occurred since it was manufactured.
Drive OK
Fault.DriveOK
Active when there are no faults. Inactivated when any fault except travel limits occur. Drive enable has no effect on this event.
Faults Bitmap 1
Fault.FaultBitmap1
This parameter is a 32-bit register which holds drive fault status bits. Following is a list of drive faults and their associated bit
numbers:
0 = Encoder state fault
1 = Encoder hardware fault
3 = Drive power module fault
4 = Low DC bus fault
5 = High DC bus fault
8 = ISR overrun fault
9 = Drive trajectory fault
10 = Sync fault
19 = Drive over speed fault
20 = Drive invalid configuration fault
21 = Drive power up self test fault
22 = NVM Invalid fault
24 = Drive RMS shunt power fault
25 = Motor Overtemperature fault
26 = Drive Over Temp fault
30 = Auto Tune fault
All other bits are not used. A "1" in these bit locations indicates the specific fault is active, and a "0" is inactive.
Faults Bitmap 2
Fault.FaultBitmap2
This parameter is a 32-bit register holds the drive fault status bits. Following is a list of drive faults and their associated bit
numbers:
0 = Watchdog Timer fault #2
1 = Invalid Configuration fault #2
2 = NVM Invalid fault #2
3 = Power Up Test fault #2
Epsilon EP-P Drive Reference Manual
Revision A3
159
www.emersonct.com
4 = Following Error fault
5 = Travel Limit Plus fault
6 = Travel Limit Minus fault
7 = Program fault
8 = No Program Loaded fault
9 = DeviceNet Connection Timeout fault
10 = DeviceNet BusOff Interrupt fault
11 = DeviceNet Duplicate Mac ID fault
12 = Trajectory fault #2
13 = Profibus Parameterization fault
14 = Profibus Watchdog fault
15 = Profibus Configuration fault
18 = Cam fault
All other bits are not used. A "1" in these bit locations indicates the specific fault is active, and a "0" is inactive.
Faulted
Fault.Faulted
Any fault will activate this event.
Reset Faults
Fault.Reset
Resets faults that do not require a power down. This event is "or"ed with the reset button on the drive.
Fault Log - Fault Type
FaultLog.#.FaultType
This is the fault identifier for the current fault log entry. It is a read only parameter for the logged fault.
It may hold a value for any fault supported by the drive. They are the same as the faults listed on the Assignments View for Faults.
Code
Fault Description
00
EncoderStates
01
EncoderHardware
03
PowerModule
04
LowDCBus
05
HighDCBus
08
IsrOverrun
09
TrajectoryFault
0A
Synchronization
10
WatchdogTimer
13
OverSpeed
14
InvalidConfiguration
15
PowerUpSelfTest
18
RMSShuntPower
19
MotorOverTemperature
1A
OverTemperature
1E
Auto-Tune
20
WatchdogTimer
21
InvalidConfiguration
22
NVMInvalid
23
PowerUpTest
24
FollowingError
25
TraveLimitPlus
26
TraveLimitMinus
27
ProgramFault
160
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Code
Fault Description
28
NoProgram
29
DevicenetConnTimeout
2A
DevicenetBusOffInt
2B
DevicenetDupMacId
2C
TrajectoryFault
2D
ProfibusParameterizationFlt
2E
ProfibusWatchdogFault
2F
ProfibusConfigurationFault
Fault Log - Power Up Count
FaultLog.#.PowerUpCount
This is the drive power up count at the time that the fault occurred.
Fault Log - Power Up Time
FaultLog.#.PowerUpTime
This is the drive power up time when the fault occurred.
Fault Log - Sub Fault
FaultLog.#.SubFault
The sub-fault value at the time the fault occurred.
Fault Log - Valid Entry
FaultLog.#.ValidEntry
Flag to indicate that the log entry is valid. The flag is cleared for all fault entries when the fault log is cleared.
Enable Feedforwards
FeedforwardsEnable
This parameter may be setup on the Tuning view or through a program, and enables feedforward compensation. When
feedforwards are enabled, the accuracy of the Inertia and Friction settings are very important. If the Inertia setting is larger
than the actual inertia, the result could be a significant overshoot during ramping. If the Inertia setting is smaller than the actual
inertia, following error during ramping will be reduced but not eliminated. If the Friction is greater than the actual friction, it may
result in velocity error or instability. If the Friction setting is less than the actual friction, velocity error will be reduced, but not
eliminated.
Feedhold
Feedhold
When this destination is activated the motor will decelerate to a stop in the time specified by the FeedholdDecelTime
parameter. When it is deactivated the motor will accelerate back up to the programmed speed in the same amount of time. It
is used to hold motion without cancelling the move in progress. If a feedhold is activated during an index the motor will come
to a halt, but the index's velocity command remains at the velocity it was at before the feedhold was activated. When the
feedhold is deactivated time will ramp back up and the index will continue on to its programmed distance or position.
Feedhold affects indexes, homes, and programs. A jog is not affected by the feedhold unless it is initiated from a program.
This is level sensitive.
Feedhold Deceleration Time
FeedholdDecelTime
When Feedhold destination is activated the motor will decelerate to a stop in the time specified by the FeedholdDecelTime
parameter. While the feedhold destination is active, the motion profile is stopped. When the feedhold destination is
deactivated the motor will accelerate to full velocity using the value of the FeedholdDecelTime.
FeedRate Deactivate
FeedRateDeactivate
This destination allows the user to deactivate the FeedRate Override feature. When FeedRate Deactivate is enabled,
FeedRate Override will be disabled and all index or home motion will operate at its programmed velocity. When FeedRate
Deactivate is disabled, FeedRate Override will be enabled, and index and home motion is subject to scaling by the FeedRate
Epsilon EP-P Drive Reference Manual
Revision A3
161
www.emersonct.com
Override parameter. The default value for FeedRate Override is 100%, so even when FeedRate Override is enabled, default motion will run at
programmed velocity.
FeedRate Override
FeedRateOverride
This parameter is used to scale all motion. It can be described as “scaling in real time.” The default setting of 100% will allow all motion to
occur in real time. A setting of 50% will scale time so that all motion runs half as fast as it runs in real time. A setting of 200% will scale time so
that all motion runs twice as fast as it would in real time. FeedRate Override is always active, and this parameter may be modified via Modbus
or in a program. When changed, the new value takes effect immediately.
Foldback Active
FoldbackActive
This source (output function) is active when the drive is limiting motor current. If the Foldback RMS exceeds 100 percent of the continuous
rating, the current foldback circuit will limit the current delivered to the motor to 80 percent of the continuous rating.
Foldback RMS
FoldbackRMS
This read-only parameter accurately models the thermal heating and cooling of the drive. When this parameter reaches 100 percent, current
foldback will be activated.
Following Error
FollowingError
Following Error displays the difference between the Position Command and the Position Feedback.
Enable Following Error
FollowingErrorEnable
This parameter can be setup from the Position view or from a program. When enabled, a following error fault will be generated if the absolute
value of the Following Error exceeds the Following Error Limit.
Following Error Limit
FollowingErrorLimit
This parameter is used when the FollowingErrorEnable bit is set. This limit is compared to the absolute value of the FollowingError. If the
FollowingError is greater than the FollowingErrorLimit, a following error fault will be generated.
Friction
Friction
This parameter is characterized in terms of the rate of friction increase per 100 motor RPM. If estimated, always use a conservative (less than
or equal to actual) estimate. If the friction is completely unknown, a value of zero should be used. A typical value used here is less than one
percent.
Gear Accel
Gear.Accel
This parameter sets the acceleration of the realtime gearing ramp. Gear.Accel units are in Follower Units/Velocity Time Base/Acceleration
Time Base. The Gear.Accel functions only when the follower is ramping its speed up to meet the Masters at the specified Gear.Ratio.
Gear Accel Enable
Gear.AccelEnable
Gear.AccelEnable is a Destination that when it is "on" allows a gear to run a specified accel ramp after the gearing command is turned on.
Gear Accelerating
Gear.Accelerating
If Gear.AccelEnable is activated, this source is activated during the time between Gear.Initate = On and Gear.AtVel = On.
Gear Activate
Gear.Activate
The Gear.Activate destination is used to start gearing from an assignment. It is a level-sensitive function, which means that as long as
Gear.Activate is active, gearing will be in progress. When deactivated, gearing motion will come to a stop without deceleration. This function is
162
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
only available through the Assignments view. When gearing from a program, the Gear.Initiate and Gear.Stop instruction are
used to start and stop gearing.
The gearing function must be stopped by the same method that started it. If it is started from an assignment, then it must be
stopped from an assignment or if started in a user program, it must be stopped in a user program.
Gear at Velocity
Gear.AtVel
The Gear.AtVel source indicates that the motor is running at the programmed gear ratio. In early releases of Gearing,
acceleration and deceleration will not be used with gearing, so this source will always be active when gearing is active.
Gear Command Complete
Gear.CommandComplete
This source will activate when gearing has been stopped, and will remain active until the gear is initiated again. This source
will activate immediately after a Gear.Activate destination is deactivated.
Gear Command In Progress
Gear.CommandInProgrees
This source will activate when Gearing is initiated either from a program or through an assignment. The source will remain
active as long as gearing is in operation. This source can be active even if the motor is not in motion as long as gearing is
active.
Gear Decel
Gear.Decel
This parameter sets the deceleration of the realtime gearing ramp. Gear.Decel units are in Follower Units/Velocity Time Base/
Acceleration Time Base. The Gear.Decel functions only when the follower is ramping its speed down after the gearing function
has turned off.
Gear Decel Enable
Gear.DecelEnable
Gear.DecelEnable is a Destination that when it is "on" allows a gear to run a specified decel ramp after the gearing command
is turned off.
Gear Decelerating
Gear.Decelerating
If Gear.DecelEnable is activated, this source is activated during the time between Gear.Initate = Off and
Gear.CommandComplete = On.
Gear Initiate
Gear.Initiate
Gearing can be activated through an assignment, or from a program instruction, Gear.Initiate. If initiated from an assignment,
the Gear.Activate destination is a level-sensitive event. This means that gearing will be active as long as the source to which it
is assigned is active. If gearing from a user program, the Gear.Stop instruction is used to stop the gearing motion. The gearing
function must be stopped by the same method that started it. If it is started from an assignment, then it must be stopped from
an assignment or if started in a user program, it must be stopped in a user program.
Gear Recovery Distance
Gear.RecoveryDist
This variable measures the distance the follower loses from the master. This distance lost is measured between a Gear Initiate
and the Gear At Velocity.
Gear Stop
Gear.Stop
Gear.Stop will stop gearing motion that has been initiated from a program using Gear.Initate.
Graph Run
GraphRun
This instruction allows the user to enable the graph from a user program. It is similar to pressing the Run button on the Graph
Epsilon EP-P Drive Reference Manual
Revision A3
163
www.emersonct.com
view. This instruction will wait until the graph buffer is full, then it exits into the looking for trigger state.
Any Command Complete
Home.AnyCommandComplete
This source is active when any home motion command is completed, if a stop is activated before the home has completed the function will not
be activated. Inactivated when a home command is executed.
Acceleration
Home.#.Accel
This parameter sets the average Acceleration rate used during the home, units are specified on the User Units page.
Accelerating
Home.#.Accelerating
Active during any acceleration while the specified home is in progress. Accelerating may turn off and on again based on the type of Home
selected. Accelerating will activate during the Home back off sensor motion.
At Velocity
Home.#.AtVel
This source is activated when the home velocity is reached when a the specified home is in progress. It will activate and deactivate base on the
home. Home At Velocity will not be activated during back off sensor portion of the home.
Calculated Offset
Home.#.CalculatedOffset
The Calculated offset is the distance travelled during the deceleration ramp from the home velocity to a stop. Calculated by PowerTools.
Command Complete
Home.#.CommandComplete
This source is active when the specified home command is completed, if a stop is activated before the home has completed the function or if
the Home Limit Distance has been exceeded it will not be activated. Inactive when a home command is executed.
Command In Progress
Home.#.CommandInProgress
This source is activated when the Home is initiated and remains active until all motion related to the Home has completed.
Deceleration
Home.#.Decel
The Deceleration ramp parameter is used during all the home moves specified in user units.
Decelerating
Home.#.Decelerating
This source is active during any deceleration while the specified home is in progress. Decelerating will turn off and on based on the type of
Home selected. Decelerating will activate during the Home back off sensor motion.
End of Home Position
Home.#.EndPosn
This parameter defines the drive position at the completion of a home. Typically used to define the machine coordinate home position.
Initiate
Home.#.Initiate
When activated, this destination will initiate the specified home. Home will not initiate if an index, jog, program, or stop is currently active.
Limit Distance
Home.#.LimitDist
This parameter places an upper limit on the incremental distance traveled during a home. If no home reference is found the motor will
decelerate to a stop at the limit distance and activate the Home.#.LimitDistHit event.
164
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Enable Limit Distance
Home.#.LimitDistEnable
This parameter enables the specified Home.#.LimitDist. If not enabled, the home will run indefinitely until the home reference
is found.
Limit Distance Hit
Home.#.LimitDistHit
This source is activated when the home sensor is not found before the Home Limit Distance is traveled.
Name
Home.#.Name
The user can specify a name up to 12 alphanumeric characters that allows a descriptive name for the home.
Home Offset Type
Home.#.OffsetType
Selects calculated or specified home offset. Calculated offset is the distance traveled during the deceleration ramp from the
home velocity. The specified offset allows the user to choose an exact offset from the Home Reference.
If On Sensor
Home.#.OnSensorAction
If the home sensor input is active when the home is initiated, this parameter determines the direction of motion. Two selections
are possible. If "Back off before homing" is selected, the motor will turn in the opposite direction of the home until the home
sensor is clear and then begin the home. If "Go forward to next sensor" is selected, the motor will turn in the commanded
direction until the next rising edge of the sensor is seen. If using Modbus to view or modify this parameter, 1= Back off before
homing, 0 = Go forward to next sensor.
Home Reference
Home.#.Reference
This parameter determines how the reference position is determined. The parameter can have one of three different values:
'Sensor', 'Marker', 'Sensor then Marker'. When the home reference is 'Sensor' the rising edge of the 'Home Sensor' input
function is used to establish the reference position. When the home reference is 'Marker' the rising edge of the motor
encoder's marker channel is used to establish the reference position. When the home reference is 'Sensor then Marker' the
reference position is established using the first marker rising edge after the Home Sensor input function goes active.
Sensor Trigger
Home.#.SensorTrigger
This destination is usually a sensor input used as a reference for the home. This event is only used if the home is defined by
sensor or by sensor then marker.
Specified Offset
Home.#.SpecifiedOffset
The specified offset parameter allows the user to specify an exact offset relative to the Home Reference. The commanded
motion will stop at exactly the offset distance away from the sensor or the marker as specified.
Time Base
Home.#.TimeBase
The time base selects either realtime, which allows velocities, acceleration and deceleration to be based on real time, or
synchronized, which allows for an external synchronization signal.
Velocity
Home.#.Vel
This parameter sets the target velocity for all of moves in the home. The sign determines the home direction. Positive numbers
cause motion in the positive direction and negative numbers cause motion in the negative direction in search of the home
sensor.
Epsilon EP-P Drive Reference Manual
Revision A3
165
www.emersonct.com
Any Command Complete
Index.AnyCommandComplete
This source is active when any index motion command is completed. If a stop is activated before the index has completed, this destination will
not activate. Deactivated when any index command is initiated.
Index Profile Limited
Index.ProfileLimited
For timed indexes, if the values for Max. Velocity, Max. Acceleration and Max. Deceleration are such that the distance cannot be covered in the
specified time, the Index.ProfileLimited flag will activate when the index is initiated. The Index.ProfileLimited flag will remain active until cleared
using the Index.ResetProfileLimited assignment or program instruction. In this situation, the index will still operate, but the time will be
extended. In other words, the profile will be performed using the maximum values and still cover the specified distance, but not in the specified
time.
If entering a timed based index at a non zero velocity, the Max. Velocity must be greater than the entry velocity to prevent Index.ProfileLimited.
Once Index.ProfileLimited is set, the index will be treated as a non-timed based index.
Index Reset Profile Limited
Index.ResetProfileLimited
If a timed index was not completed in the specified time, the Index.ProfileLimited source will activate. Index.ResetProfileLimited is used to
clear the ProfileLimited flag and acknowledge that the index was not completed in the specified time. This can be activated through an
assignment, or through a user program. This function is edge-sensitive, so holding Reset Profile Limited active will not prevent ProfileLimited
from activating.
Acceleration
Index.#.Accel
This parameter is the average Acceleration rate used during the index. Units are specified on the User Units view in the PowerTools Pro
software.
Accelerating
Index.#.Accelerating
This source is active while an index is accelerating to its target velocity. Once the index reaches the target velocity, or begins to decelerate, the
Index.#.Accelerating source will deactivate.
Analog
Index.#.AnalogLimitType
Select the analog parameter (i.e. Torque Command) to compare to the AnalogLimitValue. Satisfying the comparison triggers the index
registration event.
Limit Value
Index.#.AnalogLimitValue
This preset value is compared to the selected AnalogLimitType to determine the registration point.
At Velocity
Index.#.AtVel
This source activates when the target index velocity is reached. If Feedrate override is changed or FeedHold is activated AtVelocity shall
remain active. Index.#.AtVel will deactivate at the start of any deceleration or acceleration. During a synchronized index, this source could be
active even without any motor motion if the master axis stops.
Command Complete
Index.#.CommandComplete
The Index.#.CommandComplete source will activate when the specific index completes its deceleration ramp. It will remain active until the
specific index is initiated again. If the Stop destination is used during an Index, then the Index.#.CommandComplete will not activate.
Command In Progress
Index.#.CommandInProgress
The Index.#.CommandInProgress source is active throughout an entire index profile. The source activates at the beginning of the index
acceleration ramp, and deactivates at the end of the index deceleration ramp.
166
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Compound Initiate
Index.#.CompoundInitiate
When activated will initiate the specified Index to compound into the next index in the program. Only allowed in a program.
Deceleration
Index.#.Decel
This parameter is the Average Deceleration rate used during the index. Units are specified on the User Units page.
Decelerating
Index.#.Decelerating
This source is active while an index is decelerating from its target velocity. Once the index reaches zero velocity, or its next
target velocity, the Index.#.Decelerating source will deactivate.
Distance
Index.#.Dist
This parameter is the Incremental distance that the index will travel or the absolute position for the specified index in user
units. If an index type of Registration is selected, then this is a limit distance, or the maximum distance the index will travel if a
registration sensor is not seen.
Index Time
Index#.IndexTime
This parameter is used in conjunction with the Index.TimeIndexEnable parameter. If TimeIndexEnable is activated, then this is
the time in which an index should complete its programmed distance. The units for this parameter depend on the current
setting of the TimeBase parameter for the specific index. If TimeBase is set to “Realtime” (default), then the units are Seconds.
The user can program the index time with resolution on 0.001 Seconds (or milliseconds). If TimeBase is set to “Synchronized”,
the units defined by the Master Distance Units found on the Master Units view.
Initiate
Index.#.Initiate
The Index.#.Initiate destination is used to initiate the specific index. The Index is initiated on the rising edge of this function. An
Index cannot be initiated if there is an Home, Jog, or Program in progress, or if the Stop destination or if a travel limit is active.
It can be activated from an assignment or from a program.
Limit Distance Hit
Index.#.LimitDistHit
This source is activated when the registration sensor is not found before the Limit Distance is traveled. If the Registration
Window is enabled the sensor must be activated inside the window to be recognized.
Name
Index.#.Name
The user can specify an Index name of up to 12 characters.
Enable PLS
Index.#.PLSEnable
When Activated, this parameter enables the PLS (programmable limit switch) function for the specified index. It can be
controlled from index view check box or from a program.
PLS Off Point
Index.#.PlsOffDist
This an incremental distance from the start of the index to the Index PLS off point. This is an unsigned value and is relative
only to starting position of this index. Index direction does not affect this parameter. Index.#.PLSStatus will be active if the
distance traveled from the start of the index is greater than the Index.#.PlsOnDist and less than the Index.#.PlsOffDist.
PLS On Point
Index.#.PlsOnDist
This an incremental distance from the start of the index to the Index PLS On Point. This is an unsigned value and is relative
Epsilon EP-P Drive Reference Manual
Revision A3
167
www.emersonct.com
only to starting position of this index. Index direction does not affect this parameter. Index.#.PLSStatus will be active if the distance traveled
from the start of the index is greater than the Index.#.PlsOnDist and less than the Index.#.PlsOffDist.
PLS Status
Index.#.PLSStatus
Controlled by the PlsOnDist and PlsOffDist Points, this is relative to the distance commanded since the start of the index. Index.#.PLSStatus
will be active if the distance traveled from the start of the index is greater than the Index.#.PlsOnDist and less than the Index.#.PlsOffDist.
Registration Offset
Index.#.RegistrationOffset
This parameter is the Distance the motor will travel after a valid registration sensor or analog limit value has been detected.
Registration Type
Index.#.RegistrationType
This selects either sensor or analog as the registration mark for a registration index.
Enable Registration Window
Index.#.RegistrationWindowEnable
This check box enables (if checked) the Registration Sensor valid Window. When active, only registration marks that occur inside the
registration window are seen as valid.
Window End
Index.#.RegistrationWindowEnd
This parameter defines the end of the Registration Sensor Valid Window relative to start position of this index. This is an unsigned value and is
relative only to starting position of this index. Index direction does not affect this parameter. The Registration Window start position is greater
than or equal to the Registration point and less than the Registration Window End position. If a registration sensor is seen outside of this
window (not between the WindowStart and WindowEnd positions) then it will be ignored.
Window Start
Index.#.RegistrationWindowStart
This parameter defines the start of the Registration Sensor Valid Window relative to start position of this index. This is an unsigned value and
is relative only to starting position of this index. Index direction does not affect this parameter. The Registration Window start position is greater
than or equal to the Registration point and less than the Registration Window End position. If a registration sensor is seen outside of this
window (not between the WindowStart and WindowEnd positions) then it will be ignored.
Registration Sensor
Index.#.SensorTrigger
If registration to Sensor is selected, when this destination activates, motor position is captured and is used as the registration point for
registration type indexes.
Time Base
Index.#.TimeBase
The time base selects either realtime, which allows velocities, acceleration and deceleration to be based on real time, or synchronized, which
allows for an external synchronization signal.
Index Timed Index Enable
Index.#.TimedIndexEnable
This parameter is used in conjunction with the Index.#.IndexTime parameter. If Index.#.TimedIndexEnable is active, then the programmed
Velocity, Acceleration, and Deceleration will be used as maximum values, and the Index Time parameter will determine how long it takes to
perform an index.
Velocity
Index.#.Vel
This parameter sets the target velocity of the specific index. The units for this parameter are specified in the User Units Setup view. When an
index is initiated, it will ramp up to this velocity at the specified acceleration rate and run at speed until it decelerates to a stop (assuming the
index is not compounded).
168
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Inertia Ratio
Inertia
This specifies the load to motor inertia ratio. For example, a value of 25.0 specifies that the load inertia is 25 times the inertia
of the motor.
Initially Active
InitiallyActive
This source, when assigned to a destination, will activate the destination on power-up or a reset. InitiallyActive can be
assigned to any destination that does not create motion (i.e. indexes, jogs, homes, programs).
In Position
InPosn
This source activates when commanded velocity is zero and the absolute value of the following error is less than the
InPosnWindow for at least the amount of time specified in the InPosnTime parameter.
In Position Time
InPosnTime
This parameter is the minimum amount of time, in seconds, that commanded motion must complete and the absolute value of
the following error is less than the InPosnWindow parameter for the InPosn source to activate. If set to zero (default), then
InPosn will activate as soon as motion stops and the following error is less than the In Position Window parameter.
In Position Window
InPosnWindow
The absolute value of the following error must be less that this value at the completion of a move for the InPosnTime before
InPosn will activate.
Any Command Complete
Jog.AnyCommandComplete
The Jog.AnyCommandComplete bit will activate when either Jog 0 or Jog 1 completes its deceleration ramp and reaches zero
commanded speed. It deactivates when another jog is initiated.
Minus Activate
Jog.MinusActivate
This destination is used to initiate jogging motion in the negative direction using the jog parameters of the jog selected by the
Jog select input function. Jogging will continue as long as the destination is active. The motor will decelerate to a stop when
the destination is deactivated. This is level sensitive.
Plus Activate
Jog.PlusActivate
This destination is used to initiate jogging motion in the positive direction using the jog parameters of the jog selected by the
Jog select input function. Jogging will continue as long as the destination is active. The motor will decelerate to a stop when
the destination is deactivated. This is level sensitive.
Select
Jog.Select0
This destination is used to select between the jogs. It is used along with the Jog.PlusActivate and Jog.MinusActivate
destinations. If the Jog.Select0 destination is not active then the Jog.0 setup parameters will be used for jogging. If the
Jog.Select0 input function is active, the Jog.1 setup parameters will be used for jogging. If the Jog.Select destination is
changed during jogging motion the axis will ramp smoothly from the previously selected jog velocity to the new jog velocity
using the specified jog acceleration. This is level sensitive.
Stop
Jog.Stop
This is used only in programs to halt jogging motion. Jogging motion is initiated in programs using the Jog.#.MinusActivate or
Jog.#.PlusActivate instructions, and using the Jog.Stop will cause the motor to decelerate to a stop at the Jog.#.Decel rate for
the jog that is active.
Epsilon EP-P Drive Reference Manual
Revision A3
169
www.emersonct.com
Acceleration
Jog.#.Accel
This parameter is the average acceleration ramp for the specific jog.
Accelerating
Jog.#.Accelerating
This source is active while a jog is accelerating to its target velocity. Once the jog reaches the target velocity, the Jog.#.Accererating bit will turn
off.
At Velocity
Jog.#.AtVel
This source activates when the particular jog has reached its target velocity. It deactivates when accelerating or decelerating to another target
jog velocity.
Command Complete
Jog.#.CommandComplete
The Jog.#.CommandComplete source activates when the specific Jog completes its deceleration ramp and reaches zero commanded speed.
It deactivates when the specific Jog is initiated again.
Command In Progress
Jog.#.CommandInProgress
The Jog.#.CommandInProgress source is high throughout an entire jog profile. The bit goes high at the start of a jog acceleration ramp, and
turns off at the end of a jog deceleration ramp.
Deceleration
Jog.#.Decel
This parameter is the average deceleration ramp for the specific jog.
Decelerating
Jog.#.Decelerating
This source turns on at the beginning of a jog deceleration ramp and turns off at the completion of the ramp.
Initiate Minus
Jog.#.MinusInitiate
This is used inside a program to initiate a specific jog. When this bit is active, jogging motion will be initiated in the negative direction at the
specified jog velocity.
Initiate Plus
Jog.#.PlusInitiate
This is used inside a program to initiate a specific jog. When this bit is active, jogging motion will be initiated in the positive direction at the
specified jog velocity.
Time Base
Jog.#.TimeBase
The time base selects either realtime, which allows velocities, acceleration and deceleration to be based on real time, or synchronized, which
allows for an external synchronization signal.
Velocity
Jog.#.Vel
This parameter specifies the velocity used for jogging with the Jog.PlusActivate and Jog.MinusActivate destinations or the Jog.#.PlusInitiate
and Jog.#.MinusInitiate inside a program. The units for this parameter are specified in the User Units view.
Low Pass Filter Frequency Enable
LowPassFilterEnable
This parameter enables a low pass filter applied to the output of the velocity command before the torque compensator. The low pass filter is
170
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
only active in Pulse and Velocity modes, not in Torque mode.
Low Pass Filter Frequency
LowPassFilterFrequency
When enabled this parameter defines the low pass filter cut-off frequency. Signals exceeding this frequency will be filtered at a
rate of 40 dB per decade. The default value is 600 Hz. The low pass filter is only active in Pulse and Velocity modes, not in
Torque mode.
Modbus Master Baud Rate
MbMaster.CommPort.Baudrate
When the drive's serial port is operating as the Modbus master (either MbMaster.CommPort.EnableMbGateway or
MbMaster.CommPort.EnableMbMaster is enabled) this parameter sets the data rate for the port.
When operating as a Modbus slave (for an HMI or PowerTools connectivity), the data rate is controlled by Modbus.Baudrate.
Enable Modbus Gateway
MbMaster.CommPort.EnableMbGateway
This parameter when enabled allows the drive to pass through Modbus messages received in the Ethernet port through to the
serial port that do not match the Target Drive Address (Modbus.ModbusID) of the drive.
Enable Modbus Master
MbMaster.CommPort.EnableMaster
When this parameter is enabled the drive operates the serial port as a Modbus master. Slave devices can be read from or
written to using user program - Modbus commands.
Force Slave Mode
MbMaster.CommPort.ForceSlaveMode
When this parameter is active it forces the drive to operate the serial port in Modbus slave mode. This will override both
Modbus bridging mode (MbMaster.CommPort.EnableMbGateway) and Modbus master operations
(MbMaster.CommPort.EnableMbMaster.
Inter-character Timeout
MbMaster.CommPort.IntercharacterTimeout
Defines a broken frame if data stream is interrupted with this duration of silence, but less than Inter-frame Timeout time. See
b in Figure 121 Modbus RTU Timing Diagram on page 108.
Inter-frame Timeout
MbMaster.CommPort.InterframeTimeout
This parameter specifies the period of no-data transmission indicating the end of a Modbus packet. See c in Figure
121 Modbus RTU Timing Diagram on page 108.
Msg Gap
MbMaster.CommPort.MsgGap
This parameter defines the minimum amount of time to wait following a slave response before sending a new query to a
different slave. See d in Figure 121 Modbus RTU Timing Diagram on page 108.
Parity
MbMaster.CommPort.ParitySetting
When the device's serial port is operating as a Modbus master (either MbMaster.CommPort.EnableMbGateway or
MbMaster.CommPort.EnableMbMaster is enabled) this value sets the data parity for the port.
When operating as a Modbus slave (for HMI or PowerTools connectivity), the data parity defaults to none.
Response Gap
MbMaster.CommPort.ResponseGap
This parameter is the maximum time to wait before the slave has timed out. See a in Figure 121 Modbus RTU Timing
Diagram on page 108.
Epsilon EP-P Drive Reference Manual
Revision A3
171
www.emersonct.com
Stop Bits
MbMaster.CommPort.StopBits
When the device's serial port is operating as a modbus master (either MbMaster.CommPort.EnableMbGateway or
MbMaster.CommPort.EnableMbMaster is enabled) this parameter value sets the data stop bits for the port.
Operating as a modbus slave (for HMI or PowerTools connectivity), the data stop bits defaults to 2.
Transmission Counts
MbMaster.CommPort.TransCount
Number of transmissions requested. (writable so it can be zeroed).
Transmission Time
MbMaster.CommPort.TransTime
The duration of the last transmission from request to receive.
ErrorAllSlavesCount
MbMaster.ErrorAllSlavesCount
Indicates the number of communication errors for ALL slaves.
Error Slave Count
MbMaster.#.ErrorSlaveCount
Indicates the number of failed attempts to communicate with the slave device. This parameter can be cleared by setting it to zero in a user
program.
Error Slave Detected
MbMaster.#.ErrorSlaveDetected
Indicates weather the last transmission to the slave failed.
Error Status
MbMaster.#.ErrorStatus
The status of the last command processed by the specified slave. The slave status is updated as follows:
•
•
•
Cleared at start of the command
At end of command it is set non-zero if there was any errors
Errors less than 100 are Modbus exception responses .
Error Status Number
Error Description
01
Illegal Function
The slave does not support the request
02
Illegal Data Address
The data address is not supported by the slave
03
Illegal Data Value
The value (range) is not supported by the slave
04
Slave Device
Failure
An unrecoverable error occurred while the slave was a
attempting to perform the request
05
Acknowledge
The slave accepted the request but expects a
06
Busy
The slave is busy processing a previous request
Errors greater than 100 are internal errors whose meaning may vary with each firmware revision.
Modbus ID
MbMaster.#.ID
The Modbus slaves Modbus ID number.
Message Gap
MbMaster.#.MsgGap
This parameter defines the minimum amount of time to wait following a slave response before sending a new query to a different slave. See d
in Figure 121 Modbus RTU Timing Diagram on page 108.
If the value of MbMaster.CommPort.MsgGap is larger, then its value will take precedence.
172
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Modbus Master Path Type
MbMaster.#.PathType
This parameter defines the connection method to reach the slave. The user can choose between Ethernet (Modbus TCP/IP)
or Serial (Modbus RTU).
When Ethernet is selected the master attempts to communicate to the slave device using Ethernet.
When selecting Serial, the master attempts to communicate to the slave using the serial port.
NOTE
The drive’s serial port must be configured as a modbus master before attempting to communicate to the slave via serial
communications.
Receive Count
MbMaster.#.RecvCount
Indicates the number of responses from the slave device. This parameter can be cleared by setting it to zero in a user
program.
Response Gap
MbMaster.#.ResponseGap
This parameter defines the maximum amount of time to wait for a response before declaring a timeout. See a in Figure
121 Modbus RTU Timing Diagram on page 108.
If the value of MbMaster.CommPort.ResponseGap is larger, then that value will take precedence.
Transmission Count
MbMaster.#.TransCount
This parameter indicates the number of transmissions to the slave device. This parameter can be cleared by setting it to zero
in a user program.
Transmission Time
MbMaster.#.TransTime
This parameter indicates (in milliseconds) the time to complete the last Modbus command.
Word Swap
MbMaster.#.WordSwap
Word Swap is used to change the order that the user will send or receive the 32-bit parameters over the network. The default
Word Swap for Modbus Master is LSW-MSW.
BaudRate
Modbus.BaudRate
Modbus baudrate for the Epsilon EP-P drive serial communication.
Modbus Id
Modbus.ModbusId
Modbus ID # for the Epsilon EP-P drive.
Motion Stop
MotionStop
This destination is used to stop all motion operating without stopping programs. MotionStop can be activated through an
assignment, or in a user program. This function is level sensitive, meaning that as long as MotionStop is active, all motion will
be prevented. If a program has a motion statement, the program will wait on that line of code until the MotionStop function has
been deactivated. If motion is in progress when MotionStop is activated, the profile will decelerate to zero velocity at the
deceleration rate specified in the Stop.Decel parameter. All motion will stop using a realtime deceleration, regardless of the
motions original timebase.
Motor Type
MotorType
This parameter is used to select the motor type.
Epsilon EP-P Drive Reference Manual
Revision A3
173
www.emersonct.com
Name
Name
User name for this axis can have a length up to 12 characters. This can be used to help differentiate setup files.
Packed Bits Control Word Value
PackedBits.ControlWord.#.Value
When accessing the Packed Bits Control Words for network mapping or use in a program, the Value parameter is what holds the data. When
used in a program, the "PackedBits." and the ".Value" portions of the parameter name are optional. Therefore, to write to the Control Word
Value in a program, the following lines of code are all interchangeable:
PackedBits.ControlWord.0.Value = 5
PackedBits.ControlWord.0 = 5
ControlWord.0.Value = 5
ControlWord.0 = 5
Packed Bits Status Word Value
PackedBits.StatusWord.#.Value
When accessing the Packed Bits Status Words for network mapping or use in a program, the Value parameter is what holds the data. When
used in a program, the "PackedBits." and the ".Value" portions of the parameter name are optional. Therefore, to read the Status Word Value in
a program, the following lines of code are all interchangeable:
Var.MyVar
Var.MyVar
Var.MyVar
Var.MyVar
=
=
=
=
PackedBits.StatusWord.0.Value
PackedBits.StatusWord.0
StatusWord.0.Value
StatusWord.0
PLS Direction
PLS.#.Direction
This parameter specifies the direction of motion that a particular PLS output will function. If set to Both, the PLS will activate regardless of
whether the axis is moving in the positive or negative direction. If set to Plus, the PLS will activate only when the axis is moving in the positive
direction. If set to Minus, the PLS will activate only when the axis is moving in the negative direction. When set to Plus or Minus the PLS Status
will activate when the position of the PLS source is > or = to the on position, + or < the off position. See PLS View on page 56 for more
information on how the PLS feature works.
A flying cutoff or flying shear application may use this feature to activate the PLS to fire the knife only when the axis is moving in the positive
direction.
PLS Off Point
PLS.#.OffPosn
PLS.#.Status will be active when the selected source position is between the PLS.#.OnPosn and the PLS.#.OffPosn. The terms On and Off
assume you are traveling in a positive direction.
With the PLS.#.Direction set to "Both". The PLS.#.Status will activate when traveling in the positive direction and the position feedback reaches
the OnPosn. As the motor continues in the same direction, the PLS.#.Status will deactivate when the source reaches or exceeds the OffPosn.
If motor travel changes to the negative direction after passing the OffPosn, the PLS.#.Status will activate when position feedback reaches the
OffPosn, and will deactivate when it continues past the OnPosn. The important thing to remember is that the PLS.#.Status will be active
between the PLS On and Off points.
If using negative values for the OnPosn and OffPosn, the most negative value should go in the OnPosn parameter, and the least negative
value should go in the OffPosn.
If the PLS has a rollover point, and the OnPosn is greater than the OffPosn, the PLS will be active whenever the axis is not between the On
and Off positions, and inactive whenever the axis is between the two positions. However, the PLS.#.Status will not turn on until it reaches the
OnPosn the first time.
PLS On Point
PLS.#.OnPosn
PLS.#.Status will be active when the selected source position is between the PLS.#.OnPosn and the PLS.#.OffPosn. The terms On and Off
assume the motor is traveling in a positive direction.
Assume the PLS.#.Direction is set to "Both". When traveling in the positive direction and the source reaches the OnPosn, the PLS.#.Status will
activate. As the motor continues in the same direction, the PLS.#.Status will deactivate when feedback position reaches or exceeds the
OffPosn. If motor travel changes to the negative direction, the PLS.#.Status will activate when position feedback reaches the OffPosn, and will
deactivate when it continues past the OnPosn. The important thing to remember is that the PLS.#.Status will be active if between the PLS On
and Off points.
If using negative values for your OnPosn and OffPosn, the most negative value should go in the OnPosn parameter, and the least negative
174
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
value should go in the OffPosn.
If the PLS has a rollover point, and the OnPosn is greater than the OffPosn, the PLS will be active whenever the axis is not
between the On and Off positions, and inactive whenever the axis is between the two positions. However, the PLS.#.Status
will not turn on until it reaches the OnPosn the first time.
PLS Enable
PLS.#.PLSEnable
This destination is used to enable an individual PLS. A PLS can be enabled though the Assignments view in PowerTools Pro
or from a program. If enabled, the PLS will begin to function as soon as the drive has been homed or a DefineHome
destination has been activated. Master Posn Valid must be active (Master Define Home is activated) if using a master position
feedback signal for PLS source.
PLS Rollover Enable
PLS.#.RotaryRolloverEnable
This parameter is used to enable the RotaryRolloverPosn for the individual PLS.
PLS Rollover Position
PLS.#.RotaryRolloverPosn
This parameter is the absolute position of the first repeat position for this PLS. When enabled it causes the PLS to repeat
every time this distance is passed. The repeating range begins at an absolute position of zero and ends at the
RotaryRolloverPosn. For example in a rotary application a PLS could be setup with an OnPosn of 90 degrees and an OffPosn
of 100 degrees. If the RotaryRolloverPosition is set to 360 degrees the PLS would come on at 90, go off at 100, go on at 450
(360+90), go off at 460 (360+100), go on at 810 (2*360+90), go off at 820 (2*360+100), and continue repeating every 360
degrees forever.
PLS Source
PLS.#.Source
PLSs can be assigned to four different sources: MotorPosnFeedback, MotorPosnCommand, MasterPosnFeedback, or
FreeRunTime. This parameter determines which signal the PLS uses to reference its On Position and Off Position in order to
determine the PLS.#.Status parameter.
PLS Status
PLS.#.Status
This source is active when the position of the PLS source is greater than or equal to the On Position and less than the Off
Position.
Positive Direction
PositiveDirection
This bit is used to select which direction of motor rotation is considered motion in the positive direction. Select from CW or
CCW.
Position Command
PosnCommand
Position command is the commanded position based on information entered into the application. This parameter does not take
following error into account. See also PosnFeedback and FollowingError. Units are in user units.
Position Error Integral Time Constant
PosnErrorIntegralTimeConst
Position Error Integral parameter is a control term, which can be used in Pulse mode to compensate for the continuous torque
required to hold a vertical load against gravity or to minimize following error.
The user configures this control term using the “Position Error Integral Time Constant” parameter. This parameter determines
how quickly the drive will correct for in-position following error. The time constant is in milliseconds and defines how long it will
take to decrease the following error to 37 percent of the original value. In certain circumstances the value actually used by the
drive will be greater than the value specified here.
Min Time Constant = 1000/Response
For example, with “Response” set to 50, the minimum time constant value is 1000/50 = 20 msec.
Epsilon EP-P Drive Reference Manual
Revision A3
175
www.emersonct.com
Position Feedback
PosnFeedback
Feedback position is the actual motor position in user units. PosnCommand minus the PosnFeedback is the FollowingError
Position Feedback In Counts
PosnFeedbackInCounts
Motor encoder position in encoder counts since power up. This position reflects the feedback position of the motor and is not scaled into user
units. It can be used to confirm the exact position of the motor in applications where precise positioning is required.
Position Error Integral Enable
PosnIntegralEnable
This parameter is used to enable the position error integral compensation. See also Position Error Integral Time Constant.
Power Stage Enabled
PowerStageEnabled
This source (output function) is active when the drive's power stage is enabled.
Power Up Count
PowerUpCount
Number of times the drive has been powered up since it was manufactured.
Power Up Time
PowerUpTime
Time elapsed since the drive was last powered-up. The units is hours.
Accelerating
Profile.#.Accelerating
This source will be active when the motion being run on the specified profile is accelerating to its programmed velocity. When the motion has
reached its programmed velocity, this function will deactivate. This allows the user to see when any motion being run on this profile is
accelerating rather than having to monitor each motion object individually.
At Velocity
Profile.#.AtVel
This source is active when the motion being run on the specified profile is running at the programmed velocity. This function will activate after
the acceleration ramp is completed, and before the deceleration ramp begins. This allows the user to see when any motion being run on this
profile is at its programmed velocity rather than having to monitor each motion object individually.
Command Complete
Profile.#.CommandComplete
This source activates when the commanded motion for a motion object running on the specified profile is completed. The function will remain
active until the next motion is initiated on the same profile. If the MotionStop of the Stop function is used to stop the motion running on the
specified profile, the CommandComplete will not activate. The CommandComplete does not activate after a stop because the motor may not
be in the desired end position of the motion. This allows the user to see when any motion being run on this profile is complete rather than
having to monitor each motion object individually.
NOTE
Activation of the CommandComplete signal does not mean that the motor is no longer moving. If there is any following error at the end of the
motion, the CommandComplete will turn on before the actual motor motion is stopped.
Command In Progress
Profile.#.CommandInProgress
This source is active while any motion is being commanded on the specified profile. This function is active during all segments of a motion
(Accel, AtVel, and Decel). This function will deactivate when the CommandComplete signal activates. The CommandInProgress signal can be
active without actual motor movement if the master encoder stops during gearing or synchronized motion. This allows the user to see when
any motion being run on this profile is in progress rather than having to monitor each motion object individually.
176
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Decelerating
Profile.#.Decelerating
This source will be active when the motion being run on the specified profile is decelerating to zero velocity (or to the next
programmed velocity). When the motion has reached zero velocity, or its next programmed velocity, this function will
deactivate. This allows the user to see when any motion being run on this profile is decelerating rather than having to monitor
each motion object individually.
Feedhold
Profile.#.Feedhold
This function is used to suspend or pause a profile in motion without stopping it altogether. The Feedhold effects all types of
motion except for Gearing. When activated, any motion being run on the specified profile will decelerate to a stop in the time
programmed in the FeedholdDecelTime parameter, found on the Ramps view. The motion will remain stopped as long as the
function is active. When deactivated, the motion will accelerate back up to the programmed speed in the same amount of time
as the decel, to finish its profile.
Motion Stop
Profile.#.MotionStop
This function is used to stop any motion operating on the specified profile. This allows the user to stop motion running on one
profile without stopping motion on both profiles. When activated, motion running on the specified profile will decelerate to a
stop using the deceleration rate programmed in the StopDecel parameter. The profile will decelerate using a real-time
deceleration ramp regardless of the original timebase of the move.
Any Complete
Program.AnyComplete
This source is activated when any program ends normally. If a program ends due to a fault or the stop destination, this source
does not activate. Deactivates when any program is initiated.
Initiate
Program.#.Initiate
When activated, this destination initiates the specified program unless an index, home, or jog is already executing, a stop is
active, or a program is already executing with the same task number.
Name
Program.#.Name
This can be a 12 character string which the user can assign to an individual program. It allows the user to give a descriptive
name to programs for ease of use.
Program Complete
Program.#.ProgramComplete
This source is activated when a specific program ends normally. If the program ends due to a fault or the stop destination, this
source does not activate. Deactivates when the specific program is initiated again.
Stop
Program.#.Stop
This destination is used to stop a specific program from processing. It can be used to halt a program that is currently in
operation, or to prevent a program from initiating. If a program has initiated some motion, and the program is stopped while
that motion is still in progress, the motion will NOT be stopped. The motion initiated by the stopped program will continue until
it is complete (i.e. indexes), or until it is stopped by another program (i.e. jog,gear). This function is edge sensitive meaning
that when the Program.#.Stop activates, the specified program will be stopped, but not prevented from starting again.
Name
Queue Name
You can assign a descriptive name to each queue, making the setup easier to follow. The length of the text string is limited by
the column width with a maximum of 12 characters. Simply double click on the Name field of any queue’s line to assign a
name to it.
Epsilon EP-P Drive Reference Manual
Revision A3
177
www.emersonct.com
Data In
Queue.#.DataIn
Data is loaded into the queue using the Queue.#.DataIn instruction in a program. When Data In is set equal to a value, that value is entered
into the queue and the queue offset is added to it. If Queue Overflow is active, then no more data can be put into the Queue.
Full Level
Queue.#.FullLevel
The amount of data in the queue is constantly monitored and the Queue Full source will activate when the number of pieces of data in the
queue exceeds the Full Level parameter. This is only a flag and does not indicate a fault of any kind.
Queue Clear
Queue.#.QueueClear
This destination automatically clears all of the data out of the queue. The cleared data is not saved and there is no way to recover the cleared
data. This is typically activated on power-up of the system to make sure no old data remains in the queue.
Queue Compare Enable
Queue.#.QueueCompareEnable
The Compare Enable is what causes the comparator internal to the queue to function. If the Compare Enable is inactive, then the Queue Exit
source will never activate. If activated, then the Queue Exit source will activate when the Queue Data plus the Queue Offset is equal to the
Comparator Select parameter.
Queue Empty
Queue.#.QueueEmpty
This source is active if no data is stored in the queue. It will become inactive when the first piece of data is loaded into the queue and remain
inactive until all data has been removed from the queue.
Queue Exit
Queue.#.QueueExit
This source activates when the Comparator Select parameter is equal to the sum of the data entered into the queue, plus the queue offset.
Queue Exit deactivates when the Queue Remove instruction is processed.
Queue Full
Queue.#.QueueFull
The Queue Full source will activate if the number of pieces of data in the queue equals or exceeds the Full Level parameter. The source will
deactivate when the number of pieces of data in the queue is less than the Full Level.
Offset
Queue.#.QueueOffset
The Queue Offset is the value that is added to the Queue Data and then compared to the Comparator to determine when the Queue Exit event
activates. For instance, if Comparator Select is set to Feedback Position, and the Queue Offset is set to 10, and the user puts the value 5 into
the queue, the queue exit function will activate when the Feedback Position is equal to 5 + 10 or 15.
Queue Overflow
Queue.#.QueueOverflow
This source activates when there is no more room in the queue to store data. The maximum number of pieces of data is determined by the
Queue Size parameter.
Size
Queue.#.QueueSize
This is the maximum number of elements that can be stored in the queue. If more than this number of pieces of data is in the queue at a time,
then a Queue Overflow event will activate.
Queue Remove
Queue.#.Remove
The Queue Remove instruction is used in the program to remove data from the queue. When processed, the oldest piece of data will be
deleted out of the queue. The Queue Remove instruction also deactivates the Queue Exit function.
178
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Source
Queue.#.Source
The Queue Source determines which parameter the sum of the Queue Data and Queue Offset are compared to in order to
activate the Queue Exit function. If set to Position Feedback, the sum of the data and offset are compared to the Position
Feedback parameter. If set to Master Position, then the sum is compared to the Master Feedback Position parameter, and if
set to Command Position, then the sum is compared to the Motor Commanded Position.
Read Bit
ReadBit
This instruction reads bit values (coils or inputs) from the slave into user bits.
Response
Response
The Response parameter adjusts the velocity loop bandwidth with a range of 1 to 500 Hz. In general, it affects how quickly the
drive will respond to commands, load disturbances and velocity corrections. A good value to start with (the default) is 50 Hz.
Rotary Rollover Enable
RotaryRolloverEnable
This parameter is used in applications with a predefined repeat length. One example would be a rotary table with a rotary
rollover position of 360 degrees. The position will rollover to zero when the axis position gets to 360 degrees. (358, 359,
359.999, 0.0000, 1, 2, and so on.) The rollover point is defined to be exactly the same position as 0.
Selector Input Destinations
Selector.SelectLinesUsed
The selector is a binary to decimal decoder. This parameter selects the number of destinations (input lines) to be used by the
selector. The number of lines used determines the number of sources (selections) that can be made by the selector; that is 2
input lines can select 4 destinations (selections), 5 input lines can select 32 destinations. Range is 1 to 8.
Select
Selector.#.Select
This source selects Binary inputs to the selector, usually assigned to input lines. This is level sensitive.
Selection
Selector.#.Selection
This source selects Decimal outputs from the selector, assigned to indexes, homes or programs.
Initiate
Selector.SelectorInitiate
When this destination is activated, the selector checks the status of all Selector.Select destinations to determine which
Selector.Selection to activate.
Shunt Active
ShuntActive
This source is active when the drive's internal shunt is active (conducting current).
Shunt Power RMS
ShuntPowerRMS
This parameter models the thermal heating and cooling of the drive internal shunt. This parameter indicates the percent of
shunt capacity utilization and is based on the Heat Sink RMS value. When this value reaches 100 percent the drive will
generate an RMS Shunt Power Fault.
Enable Software Travel Limits
SoftwareTravelLimitEnable
Software travel limits can be used to limit machine travel. They are often setup inside the hardware travel limits to add a level
of protection from exceeding the machines travel limits. The SoftwareTravelLimitMinusActive source (output function) is active
when the SoftwareTravelLimitMinusPosn is reached or exceeded. Motion is halted using the TravelLimitDecel whenever a
Epsilon EP-P Drive Reference Manual
Revision A3
179
www.emersonct.com
hardware or software travel limit is hit or exceeded. Software travel limits are not active unless Absolute Position Valid is active.
Software Travel Limit Minus Activate
SoftwareTravelLimitMinusActive
The SoftwareTravelLimitMinusActive source is active when the SoftwareTravelLimitMinusPosn is reached or exceeded. Motion will come to a
stop using the TravelLimitDecel ramp. Software travel limits are not active unless enabled and Absolute Position Valid is active.
Software Travel Limit Plus Activate
SoftwareTravelLimitMinusPosn
The SoftwareTravelLimitMinusActive source will activate when the SoftwareTravelLimitMinusPosn is reached or exceeded. Motion will come to
a stop using the TravelLimitDecel. Software travel limits are not active unless enabled and Absolute Position Valid is active.
Software Travel Limit Plus Active
SoftwareTravelLimitPlusActive
The SoftwareTravelLimitPlusActive source is active when the SoftwareTravelLimitPlusPosn is reached or exceeded. Motion will come to a stop
using the TravelLimitDecel ramp. Software travel limits are not active unless enabled and Absolute Position Valid is active.
Software Travel Limit Plus Position
SoftwareTravelLimitPlusPosn
The SoftwareTravelLimitPlusActive source is active when the SoftwareTravelLimitPlusPosn is reached or exceeded. Motion is halted using the
TravelLimitDecel whenever a hardware or software travel limit is hit or exceeded. Software travel limits are not active unless enabled and
Absolute Position Valid is active.
Start Up
StartUp
This source can be used to trigger an event to occur on startup (when the Epsilon EP-P drive powers up or is rebooted). This source is typically
used to initiate a program or to initiate a home so that a machine will automatically home on power up or reboot. StartUp will activate when the
Epsilon EP-P drive has powered up and no faults are active. Startup may take as long as five seconds to activate. Depending on what the
Startup source is assigned to, the drive may need to be enabled to perform the function. If the drive is not enabled, the startup source cannot
initiate programs or motion. The source will remain active until the Epsilon EP-P drive is powered down.
Stop
Stop
Activate this destination to stop all motion and programs. If Stop is activated when a Jog, Index, Home or Program is in progress, they will
decelerate to zero speed at the Stop Decel ramp. When Stop is active, all Jog, Home, Index and Program initiate destinations will be ignored.
When it is deactivated, all level sensitive and active input functions (Jog.0.PlusActivate, Jog.0.MinusActivate, etc.) will become operational. For
example, if the Jog.PlusActivate input function is active when the Stop input function is deactivated, the Jog.Plus motion will initiate using the
acceleration found in the Jog.0.Accel parameter. This is level sensitive.
Stop Deceleration
StopDecel
Deceleration rate used when the Stop destination is activated.
Torque Command
TorqueCommand
This parameter is the torque command value before it is limited. The torque command may be limited by the motor’s rating, the amplifier’s
rating, the Torque Limit (if the Torque Limit Enable destination is active) or Current Foldback. Units for this parameter are defined in the Torque
Group on the User Units view.
Limited Torque Command
TorqueCommandLimited
This is the actual torque commanded to the motor. This value is the result after the TorqueCommand is limited by the current foldback or the
TorqueLimit value (if enabled).
Torque Level
TorqueLevel
This parameter is compared to the TorqueCommand. If the absolute value of the TorqueCommand is greater than or equal to the TorqueLevel
the TorqueLevelActive source is activated. This parameter is specified in Torque User Units.
180
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Torque Level Active
TorqueLevelActive
This source is used to indicate that the absolute value of the TorqueCommand is greater than or equal to the TorqueLevel
setting.
Torque Limit
TorqueLimit
This is the level to which the TorqueCommand will be limited when the TorqueLimitEnable input function is active.
Torque Limit Active
TorqueLimitActive
Active when the TorqueCommand is greater than the TorqueLimit and the TorqueLimitEnable input function is active.
Torque Limit
TorqueLimitEnable
This destination is used to enable the TorqueLimit. This is level sensitive.
Travel Limit Deceleration
TravelLimitDecel
This parameter defines the ramp used to decelerate the motor to a stop when any travel limit is activated.
Travel Limit Disable
TravelLimitDisable
TravelLimitDisable can be used from the Assignments view, or through a user program. It can be used to temporarily disable
the travel limit fault capability of the Epsilon EP-P drive. When TravelLimitDisable is activated, the travel limits (hardware or
software) are no longer valid. If disabled using a program, the travel limits will automatically be re-enabled when the program
ends, if they haven’t already been enabled. This feature is typically used when a machine must use one of its limit switches as
a home switch. The user disables the travel limits, then homes to the limit switch, and then re-enables the travel limit.
Travel Limit Minus Activate
TravelLimitMinusActivate
This destination is used to activate the travel limit minus fault. It should be assigned to the travel limit minus sensor. When it is
activated the drive will decelerate to a stop using the deceleration rate defined in the TravelLimitDecel parameter. This is level
sensitive.
Travel Limit Minus Active
TravelLimitMinusActive
This source is active when the TravelLimitMinusActivate is active.
Travel Limit Plus Activate
TravelLimitPlusActivate
This destination is used to activate the travel limit plus fault. It should be assigned to the travel limit plus sensor. When it is
activated the drive will decelerate to a stop using the deceleration rate defined in the TravelLimitDecel parameter. This is level
sensitive.
Travel Limit Plus Active
TravelLimitPlusActive
This source is active when the TravelLimitPlusActivate is active.
Decimal Places
TorqueUnits.Decimal
This parameter is the decimal point location for user torque units.
Epsilon EP-P Drive Reference Manual
Revision A3
181
www.emersonct.com
Units Name
TorqueUnits.Name
The User can specify a torque unit name of up to 12 characters. Default is % Cont.
Percent Continuous
TorqueUnits.PercentContinuousCurrent
This parameter is the denominator of torque scaling factor. This is an amount of continuous current in percent that is equal to the
TorqueUnits.Torque parameter.
Torque
TorqueUnits.Torque
This parameter is the numerator of the torque scaling factor. This is an amount of torque in Torque User Units that is equivalent to one unit of
PercentContinuousCurrent (denominator of scaling factor). This scaling factor is used to relate actual current or torque to user units.
Variable Decimal
Var.Var#.Decimal
This parameter specifies the number of decimal placed of resolution that this particular user variable will use. Minimum value is 0 (default), and
the maximum number of decimal places in 6 (0.000000). When assigning the value of a User Variable to different parameters, make sure that
the parameter and the User Variable have the same number of decimal places.
Variable Value
Var.Var#.Value
This parameter specifies the current value of a user variable. In a program, the ".Value" portion of the parameter name can be left off. For
example:
Var.Var0.Value = 12345 is the same as Var.Var0 = 12345
When assigning the value of a User Variable to different parameters, make sure that the parameter and the User Variable have the same
number of decimal places.
Velocity Command
VelCommand
The Velocity Command is the velocity that the Epsilon EP-P drive is commanding the motor to run at. This command is generated by the drive
velocity control loop. It is displayed in user units.
Velocity Feedback
VelFeedback
This is the feedback (or actual) velocity. It will always return the actual motor velocity, even in synchronized applications in which the master
axis is halted during a move.
Decimal Places
VelocityUnits.Decimal
This parameter is used to select the number of decimal places used in velocity units scaling. Using a high number of decimal places will
improve velocity resolution, but will also limit the maximum velocity. This parameter is selectable between 0 and 6 decimal places. The
number of decimal places set in this parameter determines the number of decimal places used in all velocity parameters throughout the
PowerTools Pro software.
Scaling
VelocityUnits.DistVelScale
Velocity units can be scaled to different from distance units, i.e. user distance units are inches and velocity units are feet per minute, instead of
inches per minute. To do this, simply enter 12 to set 1 foot equal to 12 inches (1 velocity unit = 12 distance units). Range is 1 to 1000, integers
only.
Units Name
VelocityUnits.Name
If the user wants the velocity units to have a different distance scaling than the distance units a name can be entered here up to 12 characters,
e.g. user distance units are inches and velocity units are feet per minute.
182
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Scaling
VelocityUnits.ScalingEnable
This parameter enables separate velocity and distance user units, name and scaling. If disabled, the velocity units, name and
scaling will be defined by the Distance Group.
Time Scale
VelocityUnits.TimeScale
Velocity time scale can be set to user units per second or user units per minute, used for all real-time velocities throughout the
PowerTools Pro software.
Acceleration
VirtualMaster.Accel
This parameter is the acceleration rate, in user units, that the virtual master will use to accelerate. This parameter is used
when in either jog or indexing mode.
Scaling
VirtualMaster.CharacteristicDistance
The denominator (bottom value of the scaling fraction) is the VirtualMaster.CharacteristicDistance and is used with
VirtualMaster.CharacteristicLength to create the virtual master conversion ratio. Converting the user units distance into virtual
counts.
ScalingVirtualMaster.CharacteristicLength
The numerator (top value of the scaling fraction) is the VirtualMaster.CharacteristicLength and is used with
VirtualMaster.CharacteristicDistance to create the virtual master conversion ratio scaling. Converting the user units distance
into virtual counts.
Scaling =
Virtual MasterCharacteristicLength
VirtualMaster.CharacteristicDistance
Command Complete
VirtualMaster.CommandComplete
This parameter indicating when a Virtual Master index or jog is complete.
Command In Progress
VirtualMaster.CommandInProgress
This parameter is an output event indicating a Virtual Master index or jog is currently being executed.
Counts
VirtualMaster.Counts
This read only parameter is the number of virtual counts transmitted. It is zeroed on power up only.
Deceleration
VirtualMaster.Decel
This parameter is the deceleration rate, in user units, that the virtual master will use to decelerate. This parameter is used
when in either jog or indexing mode.
Distance
VirtualMaster.Dist
This parameter is the incremental distance virtual master will move, in user units, if the virtual master is initiated as an index.
FeedRate Deactivate
VirtualMaster.FeedRateDeactivate
When this parameter is activated, from an assignment or a program, virtual master feedrate override is deactivated meaning
that the virtual master counts will be 100%.
Epsilon EP-P Drive Reference Manual
Revision A3
183
www.emersonct.com
FeedRate Decel/Accel
VituralMaster.FeedRateDecelerationTime
This parameter specifies the ramp used when velocity changes due to a change in the FeedRate Override value. The units of FeedRate Decel/
Accel are seconds/100%. Therefore, the user must specify the amount of time (in seconds) to accelerate or decelerate 100% of programmed
feedrate.
FeedRate Override
VirtualMaster.FeedRateOverride
This parameter is used to scale the Virtual Master counts. It can be described as “scaling in real time”. The default setting of 100% will allow all
counts to occur in real time. A seeing of 50% will scale time so that all counts are half as fast as they are at 100%. A setting of 200% will scale
time so that all count run twice as fast as they would at 100%. Feed Rate Override is always active, and this parameter may be modified via
Modbus, Ethernet, or in a program.
Initiate
VirtualMaster.Initiate
This initiates a Virtual Master index that generates virtual master pulses equivalent to VirtualMaster.Dist. The pulse rate will be defined by the
accel rate, velocity and decel rate. VirtualMaster.Initiate can be assigned or activated by a user program.
Marker Count
VirtualMaster.MarkerCount
The encoder marker pulses are simulated and this parameter (VirtualMaster.MarkerCount) specifies the number of
VirtualMaster.Counts per encoder marker pulse generated.
Minus Activate
VirtualMaster.MinusActivate
When active, this executes a Virtual Master jog in the minus direction that generates virtual master pulses as long as
the VirtualMaster.MinusActive is set. The pulse rate will be defined by the accel rate, velocity and decel rate.
VirtualMaster.MinusActivate can be assigned or activated by a user program
Plus activate
VirtualMaster.PlusActivate
When this parameter is active, this executes a Virtual Master jog in the plus direction that generates virtual master
pulses as long as the VirtualMaster.PlusActive is set. The pulse rate will be defined by the accel rate, velocity and
decel rate. VirtualMaster.PlusActivate can be assigned or activated by a user program.
Position Count
VirtualMaster.PosnCmdInCounts
This parameter is the number of virtual counts transmitted. Write to this parameter to zero it's value. It is only used
as a user display for virtual master debugging
Position Command
VirtualMaster.PosnCommand
This is the virtual position which uses VirtualMaster.PosnCmdInCounts and the conversion ratio to display the
position in user units. This is zeroed by clearing VirtualMaster.PosnCmdInCounts.
Posn Command
VirtualMaster.Stop
This parameter when activated stops the Virtual Master using the VirtualMaster.Decel rate.
Velocity
VirtualMaster.Vel
This parameter is the maximum virtual velocity that will be attained by the virtual master. This parameter is in user
units.
184
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Enable Virtual Master
VirtualMaster.VirtualMasterEnable
Enable Virtual Master check box by default is clear. Select the check box to enable virtual master
(VirtualMaster.VirtualMasterEnable = ON).
Epsilon EP-P Drive Reference Manual
Revision A3
185
www.emersonct.com
186
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
6
Tuning Procedures
The drive uses closed loop controllers to control the position and velocity of the attached motor. These position and velocity
controllers and the associated tuning parameters are in effect when the drive is in velocity or pulse mode and have no effect
when the drive is in Torque mode.
Many closed loop controllers require tuning using individual user-specified proportional, integral and derivative (PID) gains
which require skilled “tweaking” to optimize. The combination of these gains along with the drive gain, motor gain, and motor
inertia, define the system bandwidth. The overall system bandwidth is usually unknown at the end of the tweaking process.
The drive closes the control loops for the user using a state-space pole placement technique. Using this method, the drive’s
position control can be simply and accurately tuned. The overall system’s bandwidth can be defined by a single user-specified
value (Response).
The drive’s default settings are designed to work in applications with up to a 10:1 load to motor inertia mismatch. Most
applications can operate with this default setting.
Some applications may have performance requirements which are not attainable with the factory settings. For these
applications a set of measurable parameters can be specified which will set up the internal control functions to optimize the
drive performance. The parameters include Inertia Ratio, Friction, Response and Line Voltage. All the values needed for
optimization are “real world” values that can be determined by calculation or some method of dynamic measurement.
6.1
PID vs. State-Space
The power of the state-space control algorithm is that there is no guessing and no “fine tuning” as needed with user-specified
PID methods. PID methods work well in controlled situations but tend to be difficult to setup in applications where all the
effects of the system are not compensated for in the PID loop. The results are that the system response is compromised to
avoid instability.
The drive state-space control algorithm uses a number of internally calculated gains that represent the wide variety of effects
present in a servo system. This method gives a more accurate representation of the system and maximizes the performance
by minimizing the compromises.
You need only to setup the system and enter three parameters to describe the load and the application needs. Once the
entries are made the tuning is complete - no guessing and no “tweaking”. The drive uses these entries plus motor and
amplifier information to setup the internal digital gain values. These values are used in the control loops to accurately set up a
stable, repeatable and highly responsive system.
6.2
Motor Tuning and Motor Auto-Tuning
The unloaded motor parameters are set by the motor .ddf file or by using the motor Auto-tuning. This is a separate process
that is separate from this system tuning. The motor tuning should be set prior to tuning the system.
6.3
Tuning Procedure
Once the initial setup has been completed, you can run the system to determine if the level of tuning is adequate for the
application. A drive can be tuned basically to four levels.
•
No Tuning
•
Basic Level
•
Intermediate Level
• Fully Optimized Level
Each level is slightly more involved than the previous one requiring you to enter more information. If your system needs
optimization, we recommend that you start with the Basic Level, then determine if further tuning is needed based on axis
performance.
The setup procedures explained here assume that you are using PowerTools Pro software.
6.4
Initial Settings
Set the drive tuning parameters as follows:
6.5
•
Inertia Ratio = 0
•
Friction = 0
•
Response = 50
•
Feedforwards = Disabled
Tuning Steps
If your Inertia Ratio is greater than 10 times the motor inertia go directly to the Intermediate Level tuning.
6.5.1
No Tuning
6.5.2
Basic Level
No tuning will be required in most applications where the load inertia is 10 times the motor inertia or less.
Adjust Response to obtain the best performance.
Epsilon EP-P Drive Reference Manual
Revision A3
187
www.emersonct.com
6.5.3
6.5.4
Intermediate Level
1.
Calculate or estimate the load inertia. It is always better to estimate low.
2.
Disable the drive.
3.
Enter the inertia value calculated into the Inertia Ratio parameter.
4.
Leave all other tuning parameters at the initial values.
5.
Enable the drive and run the system.
6.
Adjust Response to obtain the best performance.
Fully Optimized Level
1.
Determine the actual system parameters.
2.
Disable the drive.
3.
Enter the parameters.
4.
Enable the drive and run the system.
5.
Adjust Response to obtain the best performance.
General Tuning Hints
General Tuning Procedure:
1.
Calculate inertia of the system
The inertia of the system up to the motor shaft should be calculated using CT-Size software or some other inertia calculating software. Under
perfect mechanical conditions, entering this number into the “Inertia” parameter will produce a well-matched system tuning. Because most
systems include mechanics that are less than ideal, a number less than the inertia parameter will need to be used to avoid bandwidth issues or
“buzzing” of the motor. See Figures 144 and 145.
Figure 144:
Default Inertia Setting (0)
188
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Figure 145:
2.
Inertia Setting (5)
Increase the response parameter
The Response is normally the final adjustment when tuning. For best performance the Response should be lower with a
higher inertia mismatch (>10:1) and higher with a lower inertia mismatch.
If your system has some torsional compliance, such as with a jaw type coupling with a rubber spider, or if there is a long drive
shaft, the Response should be decreased. The highest recommended Response with High Performance Gains enabled is 100
Hz.
Also, enabling the Low Pass Filter helps diminish the resonant frequency of torsionally compliant loads. In such cases, using
the Low Pass Filter usually allows for higher Response values. The optimum Low Pass Filter frequency is at the frequency of
the resonance.
Feedforwards can be enabled if the performance requirements are very demanding. However when using them, make sure
the Inertia Ratio and Friction values are an accurate representation of the load. Otherwise, the system performance will
actually be degraded or stability will suffer. Enabling the Feedforward makes the system less tolerant of inertia or friction
variations during operation.
6.6
Tuning Parameters
Inertia Ratio
Inertia Ratio specifies the load to motor inertia ratio and has a range of 0.0 to 50.0. A value of 1.0 specifies that load inertia
equals the motor inertia (1:1 load to motor inertia). The drives can control up to a 10:1 inertia mismatch with the default Inertia
Ratio value of 0.0. Inertial mismatches of over 50:1 are possible if response is reduced.
The Inertia Ratio value is used to set the internal gains in the velocity and position loops, including feedforward compensation
if enabled.
To calculate the Inertia Ratio value, divide the load inertia reflected to the motor by the motor inertia of the motor. Include the
motor brake as a load where applicable. The resulting value should be entered as the Inertia Ratio parameter.
IR 
RLI
MRI
Where:
IR = Inertia Ratio
RLI = Reflected Load Inertia (lb-in-sec2)
MI = Motor Inertia (lb-in- sec2)
If the exact inertia is unknown, a conservative approximate value should be used. If you enter an inertia value higher than the
actual inertia, the resultant motor response will tend to be more oscillatory.
If you enter an inertia value lower than the actual inertia, but is between 10 and 90 percent of the actual, the drive will tend to
be more sluggish than optimum but will usually operate satisfactorily. If the value you enter is less than 10 percent of the actual
inertia, the drive will have a low frequency oscillation at speed.
Friction
In the drive, this is a viscous friction parameter, characterized in terms of the rate of friction increase per 100 motor RPM. The
range is 0.00 to 100.00 in units of percent continuous torque of the specified motor/drive combination. The Friction value can
either be estimated or measured.
Epsilon EP-P Drive Reference Manual
Revision A3
189
www.emersonct.com
If estimated, always use a conservative (less than or equal to actual) estimate. If the friction is completely unknown, a value of zero should be
used. A typical value used here would be less than one percent.
If the value entered is higher than the actual, system oscillation is likely. If the value entered is lower than the actual a more sluggish response
is likely but generally results in good operation.
Response
The Response adjusts the velocity and position loop bandwidths with a range of 1 to 500 Hz. In general, it affects how quickly the drive will
respond to commands, load disturbances and velocity corrections. The Response bandwidth is set to the Response value. It reflects both the
velocity command and the load disturbance correction bandwidth. Increasing the Response value will increase loop stiffness. The maximum
Response level recommended is approximately 100 Hz.
If the Inertia Ratio and Friction values are exactly correct, changing the Response will not affect the damping (percent of overshoot and
number of ringout cycles) to velocity command changes or load disturbance corrections but will affect their cycle frequency. The response level
generally should be decreased as the load to motor inertia ratio increases.
Feedforwards
Feedforward gains are essentially open loop gains that generate torque commands based on the commanded velocity, accel/decel and the
known load parameters (Inertia Ratio and Friction). Using the feedforwards reduces velocity error during steady state and reduces overshoot
during ramping. This is because the Feedforwards do not wait for error to build up to generate current commands.
Feedforwards should be disabled unless the absolute maximum performance is required from the system. Using them reduces the forgiveness
of the servo loop and can create instability if the actual inertia and/or friction of the machine varies greatly during operation or if the Inertia Ratio
or Friction parameters are not correct.
The internal feedforward velocity and acceleration gains are calculated by using the Inertia Ratio and Friction parameters. The feedforward
acceleration gain is calculated from the Inertia Ratio parameter and the feedforward velocity gain is calculated from the Friction parameter.
When Feedforwards are enabled, the accuracy of the Inertia Ratio and Friction parameters is very important. If the Inertia Ratio parameter is
larger than the actual inertia, the result would be a significant velocity overshoot during ramping. If the Inertia parameter is smaller than the
actual inertia, velocity error during ramping will be reduced but not eliminated. If the Friction parameter is greater than the actual friction, it may
result in velocity error or instability. If the Friction parameter is less than the actual friction, velocity error will be reduced, but not eliminated.
Low Pass Filter Group
The Low Pass Filter will reduce machine resonance due to mechanical coupling and other flexible drive/load components by filtering the
command generated by the velocity loop. A check box on the Tuning view enables a low pass filter applied to the output of the velocity
command before the torque compensator. The low pass filter frequency parameter defines the low pass filter cut-off frequency. Signals
exceeding this frequency will be filtered at a rate of 40 dB per decade. The default value is 600Hz.
6.7
Determining Tuning Parameter Values
For optimum performance you will need to enter the actual system parameters into the drive. This section discusses the methods which will
most accurately determine those parameters.
NOTE
If you have an application which exerts a constant unidirectional loading throughout the travel such as in a vertical axis, the inertia tests must
be performed in both directions to cancel out the unidirectional loading effect.
Initial Test Settings
When running the tests outlined in this section, the motor and drive must be operational so you will need to enter starting values.
If your application has less than a 10:1 inertia mismatch, the default parameter settings will be acceptable. If the inertial mismatch is greater
than 10:1, use the following table for initial parameter settings.
Parameter
Setting
Friction
0.00
Inertia Ratio
1/3 to 1/2 Actual
Response
500/Inertia Ratio
Feedforwards
Enabled
Determining Friction
This parameter represents friction that increases proportionally as motor velocity increases. The viscous friction of your system can be
determined by reading the percent of continuous torque required to operate the loaded motor at two different speeds.
190
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Consider the following before determining the Friction:
•
•
•
•
•
•
The most consistent readings can usually be obtained at motor speeds higher than 500 RPM but lower test speeds can be
used if necessary.
If your application has travel limits, it may be helpful to use an external position controller to prevent the axis from
exceeding the machine limits. Set up a trapezoidal profile as shown.
In the procedure below, the Torque Command and Velocity Feedback parameters can be measured using the drive’s
analog outputs, PowerTools software.
With vertical loads the test readings must be taken while traveling in the same direction.
The use of the PowerTools graph feature or an oscilloscope may be needed for systems with limited travel moves to
measure the rapidly changing torque and velocity signals.
If your system’s friction changes with operating temperature, perform this procedure at normal operating temperature.
Procedure for Determining Friction:
1.
Run the motor at the low test speed (at least 500 RPM).
2.
While at speed, note the Torque Command Actual value (TCL).
NOTE
If the friction loading of your system varies when operating at constant speed, due to a load or spring load that changes as
the motor rotates, use the lowest value measured.
3.
Repeat Step 1 using a velocity at least two times the low speed.
4.
While at speed, note the Torque Command Actual value (TCH).
5.
Use the following formula to calculate the friction:
FV  (100)
(TCH - TCL)
RPMH - RPML
Where:
TCH = Torque Command Limited value at higher speed
TCL = Torque Command Limited at lower speed
RPMH = Higher RPM (velocity)
RPML = Lower RPM (velocity)
FV = Friction value
The figure below shows the relationship of Torque Command to the Velocity Feedback. There is increased torque during the
Accel ramp (Ta), constant torque (Tc) during the constant velocity portion of the ramp and decreased torque (Td) during the
decel ramp.
Figure 146:
Trapezoidal Velocity Waveform with Torque Waveform
Determining Inertia Ratio
Actual system Inertia Ratio is determined by accelerating and decelerating the load with a known ramp while measuring the
torque required.
Epsilon EP-P Drive Reference Manual
Revision A3
191
www.emersonct.com
Consider the following before determining the inertia:
•
•
•
•
•
•
The accel and decel ramp should be aggressive enough to require at least 20 percent of continuous motor torque. The higher the torque
used during the ramp, the more accurate the final result will be.
With ramps that take less than 1/2 second to accelerate, use PowerTools graph to measure the Torque Feedback.
With ramps that take 1/2 second or longer to accelerate, read the Torque Command parameter on the Torque view, while online, or with
the Watch Window.
To best determine the inertia, use both acceleration and deceleration torque values. The difference allows you to drop the constant friction
out of the final calculation.
If your application exerts a constant “unidirectional loading” throughout the travel such as in a vertical axis, the inertia test profiles must be
performed in both directions to cancel out the unidirectional loading effect.
The Torque Command Limited and Velocity Feedback parameters can be measured using the drive’s Analog Outputs or PowerTools Pro
graph.
These will be needed for systems with limited travel moves and rapidly changing signals of torque and velocity.
Inertia Measurement Procedure:
NOTE
The test profile will need to be run a number of times in order to get a good sample of data.
1.
Enable the drives and run the test profiles.
2.
Note the Torque Command Limited value during acceleration and deceleration.
3.
Use the appropriate formula below to calculate the inertia.
For horizontal loads or counterbalanced vertical loads use the following formula:
IR 
(R  Vm (Ta  Td))
1
2000
Where:
IR = Inertia Ratio
R = ramp in ms/kRPM
Ta = (unsigned) percent continuous torque required during acceleration ramping (0 - 300)
Td = (unsigned) percent continuous torque required during deceleration ramping
(0 - 300)
Vm = MotorKt * System Continuous Current / Motor Inertia in Kg-cm2
For un-counter balanced vertical loads use the following formula:
IR 
(R  Vm (Tau  Tud  Tad  Tdd))
1
4000
Where:
IR = Inertia Ratio
R = ramp in ms/kRPM
Vm = MotorKt * System Continuous Current / Motor Inertia in Kg-cm2
Tau = (unsigned) percent continuous torque required during acceleration ramping while moving up (against the constant force)
Tdu = (unsigned) percent continuous torque required during deceleration ramping while moving up (against the constant force)
Tad = (unsigned) percent continuous torque required during acceleration ramping while moving down (aided by the constant force)
Tdd = (unsigned) percent continuous torque required during deceleration ramping while moving down (aided by the constant force)
192
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
7
Diagnostics and Troubleshooting
7.1
Diagnostic Display
The diagnostic segment display on the front of the Epsilon EP-P drive shows drive status and fault codes. When a fault
condition occurs, the drive will display the fault code, overriding the status code.
The decimal point is “On” when the drives are enabled, and the stop input is not active. This indicates that the drives are ready
to run and any motion command will cause motion. Motion commands will not cause motion unless you are Ready (R) and the
decimal point is “On”.
7.1.1
Status Codes
Display
Indication
Status
Description
Ready
The system is functioning normally and is ready to execute a motion command.
Brake Engaged (Output "Off")
Motor brake is mechanically engaged. This character will only appear if the Brake
output function is assigned to an output line.
See Brake Operation section for detailed description of Brake Output function.
Disabled
Power Stage is disabled.
RMS Foldback
Motor torque is limited to 80 percent.
Stall Foldback
Drive output current is limited to 80 percent of drive stall current.
Ready to Run
Drive enabled. No Stop input.
Homing
Home cycle is executing. Other motion commands do not funtion.
Indexing
Index is executing. Other motion commands do not function.
Decelerating from Stop or
Travel Limit Decel
Deceleration ramp after the Stop or Travel Limit function is activated. The ramp is
displayed while decelerating, and then display will go back to normal after completing
the decel ramp.
Jogging
Jog function in progress. Other motion commands do not function.
Camming
Camming function in progress. Other motion commands do not function.
Epsilon EP-P Drive Reference Manual
Revision A3
193
www.emersonct.com
Display
Indication
7.1.2
Status
Description
Program
Program is executing.
Pulse Mode
Pulse Mode Operation is executing.
Torque Mode
Analog Torque Mode Operation
Velocity Mode
Analog Velocity Mode Operation
Fault Codes
A number of diagnostic and fault detection circuits are incorporated to protect the drive. Some faults, such as High DC Bus and Motor Over
Temperature can be reset with the Reset button on the front of the drive or the Reset input function. Other faults, such as Encoder Faults, can
only be reset by cycling power “Off” (wait until the diagnostics display turns “Off”), then power “On”.
The drive accurately tracks motor position during fault conditions. For example, if there is a Low DC Bus fault where the power stage is
disabled, the drive will continue to track the motor’s position provided the logic power is not interrupted.
The +/- Travel Limit faults are automatically cleared when the fault condition is removed.
Segment
Display
Fault
Action to Reset
Bridge
Disabled
Flash Invalid
Reprogram the Flash
Yes
Drive Power Up Test
Cycle Logic Power
Yes
Drive NVM Invalid
Reset Button or Input Line
Yes
Invalid Configuration
Reset Button or Input Line
Yes
Power Module
Reset Button or Input Line
Yes
High DC Bus
Reset Button or Input Line
Yes
Low DC Bus
Reset Button or Input Line
Yes
194
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Segment
Display
Fault
Action to Reset
Bridge
Disabled
Encoder State
Cycle Power
Yes
Encoder Hardware
Cycle Power
Yes
Motor Overtemp
Reset Button or Input Line
Yes
RMS Shunt Power
Reset Button or Input Line
Yes
Overspeed
Reset Button or Input Line
Yes
Max Following Error
Reset Button or Input Line
Yes
Travel Limit +/-
Auto
No
All "On"
Normally on for one second during
power up
Yes
Run Time Faults
Reset Button or Input Line
Yes
Drive Overtemp
Allow the drive to cool down,
Cycle Logic Power
Yes
Fault Descriptions
Flash Invalid
This fault indicates that the firmware checksum has failed. Use the Tools Program Flash menu item from PowerTools to
reprogram/upgrade the firmware stored in flash memory. If this problem persists, call Control Techniques. A common cause
would be an interrupted F/W Flash upgrade (cable disconnected during an upgrade process).
Power Up Test
This fault indicates that the power-up self-test has failed. This fault cannot be reset with the reset command or reset button.
NVM Invalid
At power-up the drive tests the integrity of the non-volatile memory. This fault is generated if the contents of the non-volatile
memory are invalid.
Epsilon EP-P Drive Reference Manual
Revision A3
195
www.emersonct.com
Power Module
This fault is generated when a power stage over-temperature, over-current or loss of power stage logic supply occurs. This can be the result of
a motor short to ground, a short in the motor windings, a motor cable short or the failure of a switching transistor.
High DC Bus
This fault will occur whenever the voltage on the DC bus exceeds the High DC Bus threshold. The most likely cause of this fault would be an
open external shunt, a high AC line condition, or an application that requires an external shunt (e.g., a large load with rapid deceleration) but
none is installed.
High DC Bus Threshold
Epsilon EP
415 Vdc
Low DC Bus
This fault will occur whenever the voltage on the DC bus drops below the Low DC Bus threshold. The most likely cause of this fault is a
reduction (or loss) of AC power. A 50 ms debounce time is used with this fault to avoid faults caused by intermittent power disruption. With an
Epsilon EP drive, the low DC bus monitoring can be disabled. In an EP-B and EP-I this fault is disabled by clearing the check box on the Faults
view, and for an EP-P the check box is located on the Advanced view
Low DC Bus Threshold
Epsilon EP
60 Vdc
Special note for EP209 and EP216 drives, the Low DC Bus fault may not be disabled. The bus voltage must reach 140 Vdc (100 Vac input)
before this fault will reset and it will reset automatically. It will occur again when the bus voltage drops by 50 V from the voltage on the bus
when soft-start mode ends and the drive is ready to run.
Encoder State
Certain encoder state transitions are invalid and will cause the drive to report an encoder state fault. This is usually the result of noisy encoder
feedback caused by poor shielding. For some types of custom motors it may be necessary to disable this fault. With an Epsilon EP-P drive, the
Encoder State monitoring can be disabled by clearing the check box on the Advanced view.
Encoder Hardware
If any pair of complementary encoder lines (A, B, Z) are in the same state, an encoder line fault is generated. Also, can be generated if all three
commutation channels (U, V, W) are 0 or 1, an illegal state. The most likely cause is a missing or bad encoder connection.
Motor Overtemp
This fault is generated when the motor thermal switch is open due to motor over-temperature or incorrect wiring.
RMS Shunt Power
This fault is generated when RMS shunt power dissipation is greater than the design rating of the internal shunt.
Overspeed
This fault occurs in one of two circumstances:
1.
When the actual motor speed exceeds the Overspeed Velocity Limit parameter or 150% of motor maximum operating speed.
This parameter can be accessed with PowerTools Pro software.
2.
If the combination of command pulse frequency and Pulse Ratio can generate a motor command speed in excess of the fixed
limit of 13000 RPM, an Overspeed Fault will be activated. In Pulse mode operation and any Summation mode which uses Pulse
mode, the input pulse command frequency is monitored and this calculation is made. For example, with a Pulse Ratio of 10
pulses per motor revolution, the first pulse received will cause an Overspeed fault even before there is any motor motion.
Drive Over Temp
3.
Indicates the drive internal temperature has reached an over temperature condition - not currently implemented in the EP202,
EP204 or EP206 models. For Epsilon EP209 and EP216 drive models, this fault will occur if the soft-start circuit has failed or
mis-wiring of the bus or shunt prevents proper start-up, resulting in overheating the soft-start resistor internal to the drive. With
the EP216 model this over temperature condition could be the result of fan failure.
Following Error
This fault is generated when the following error exceeds the following error limit. With PowerTools Pro you can change the Following Error
Limit value, enable or disable it in the Position view.
196
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Travel Limit +/This fault is caused when either the + or - Travel Limit input function is active.
Sync Fault
This fault occurs when the user selected trajectory update rate is set too short based on the processor requirements. The
three possible trajectory update rates are 800µs, 1200 µs, or 1600 µs. Try changing the trajectory update rate to the largest
value (1600 µs) and run the application again. If the problem persists after setting to 1600 µs, contact Control Techniques
technical support.
Run Time Faults
A 4 will be displayed on the diagnostic display when the Epsilon EP-P drive experiences one of the following faults.
Trajectory Fault #1
This fault occurs when the drive commands motion that cannot be achieved due to excessive following error, accel, decel,
velocity settings, or unusable user units. Check the user units, velocities, accels and decels for correct values.
Trajectory Fault #2
This fault occurs when using the "Using Capture.#" option in a user program. If the capture has never been triggered, or the
capture data has gone "stale", the drive will not be able to process motion properly.
Program Fault
This fault indicates a problem was encountered in a user program. For example: an illegal math operation resulting in a divide
by zero or overflow of 32-bit data. This error can also occur if trying to access a drive parameter that is non-existent or not
available to the user.
Invalid Configuration Fault #2
The user program in flash memory will not run. Download the user program again using PowerTools Pro. A common cause of
this fault could be an interrupted configuration download, such as a cable being disconnected during the download.
No Program
This fault will be displayed on initial power-up indicating that no configuration has been downloaded to the drive. To clear the
fault, download a valid configuration to the drive.
All "On"
This is a normal condition during power up of the drive. It will last for less than 1 second. If this display persists, call Control
Techniques for service advice.
7.2
Drive Faults
The Active Drive Faults dialog box is automatically displayed whenever a fault occurs. There are two options in this dialog box:
Reset Faults and Ignore Faults.
Resetting Faults
Some drive faults are automatically reset when the fault condition is cleared. Others require drive power to be cycled or the
drive to be “rebooted” to be cleared. If you wish to continue working in the PowerTools Pro software without resetting the fault,
click the Ignore Fault button.
To reset faults that can be reset with the Reset Faults button, simply click the Reset Faults button in the Drive Faults Detected
dialog box or push the Reset button on the front of the drive where the fault occurred.
Viewing Active Drive Faults
To view all active drive faults, select the View Faults command from the Device menu. The dialog box displayed is the same as
Active Drive Faults dialog box described above.
Rebooting the Drive
To reboot the drive, cycle power or select Reboot Drive from the Device menu. This command reboots the drive attached to
the active Configuration Window.
7.3
Error Messages
PowerTools Pro will pop-up an error message box to alert the user to any errors it encounters. These message boxes will
describe the error and offer a possible solution.
The terms below appear in a list of common problems you might encounter when working with PowerTools Pro software along
with the error message displayed, the most likely cause and solution.
Assign means to set a value using an equation. For example, x = 2, you are assigning the value of 2 to x.
A Boolean value is a value that represents two states such as On or Off. In the Epsilon EP-P drive there are three variable
types that have Boolean values. They are Boolean Variables, Input Event Variables and Output Event Variables. They all have
a Boolean Value and can be used in equations to assign their Boolean value to another variable or in a conditional test.
In an equation, conditional tests such as (vel > 3.1) become Boolean values.
In Epsilon EP-P drive, unquoted text names are used to represent Boolean constants. Several different names are available.
Epsilon EP-P Drive Reference Manual
Revision A3
197
www.emersonct.com
They all represent the two Boolean states and therefore are interchangeable.
An Expression is a collection of mathematical operands (variables, constants and numbers) and operators( +, -, *, <, >, etc.) that form a
value. The right hand side of an equation (to the right of the =) is an expression.
The Parser is an internal component of PowerTools Pro software that reads your program text file and generates executable code used by the
Epsilon EP-P drive firmware. The parser detects errors that are reported to you as Red Dot Error Messages.
Program errors are displayed in the program view in Red Dot Error Messages. They are indicated with red dots. To get further information on
the cause of the error, use the program toolbar RedDot Help button. This is an on/off setting that enables error message displays and
application help messages.
7.3.1
Non-Programming Error Messages
These messages occur while you are working in a view other than the Program view. The Program view has error messages specific to it, and
they are described in a Programming Error Messages section. The popup messages are listed below.
Can Not Add Index, until current is valid.,
Can Not Add Jog, until current is valid.,
Can Not Add Program, until current is valid.
The current view must be valid before you can create a new instance of Index, Jog or Home.
Error: The maximum limit of Instances is reached.
The number of Index instances, Jog Instances and Home Instances is limited. If you attempt to add an instance and the number of existing
instances is at the maximum, you will get this message.
7.3.2
Programming Error Messages
These Red Dot Error messages occur while you are working in the Program view.
When creating a program, the parser is executed when you left mouse click, when you arrow off the current Line, when you enter the carriage
return, when you paste or when you drop a drag source. The parser detects errors and marks the line with a “Red Dot”. To get further
information on the cause of the error, use the program toolbar Red Dot Help button. This is an on/off setting that enables error message
displays and application help messages.
Problem/Message
Cause
Solution
Your Application is not valid
to download ...
There are errors such as “Red Dot”
errors in one or more programs that
prevent the program from being
downloaded to the drive.
The message will provide more information
such as which program is invalid to help the
user correct the problem.
Your Application has ...
There are errors such as “Red Dot”
errors in one or more programs. The
operation (i.e. file save) was completed,
however other operations such as
download would fail for this application.
The message will provide more information
such as which program is invalid to help the
user correct the problem.
A Epsilon EP-P drive
number’s decimal Point
resolution can not be
greater than ten
The Epsilon EP-P drive does not use
standard floating point. It uses Integer
arithmetic to prevent round off errors.
Decimals are used, but decimal point
position is handled separately from the
integer value. Zero puts the decimal
point to the far right. Ten puts the
decimal point at the far left.
The decimal point position must be between
zero and ten.
A Epsilon EP-P drive
number’s mantissa must be
between -2147483647 and
2147483647
The mantissa must be between 2147483648 and 214748364.
The decimal point position must be between
zero and ten.
A numeric variable can only
be assigned a numeric
value
The Variable is a numeric. It only
accepts types consisting of numeric
values.
A string variable can only be
assigned a quoted text
string
The Variable is string. It only accepts
types consisting of text strings.
Can only compare(>,<,etc)
numeric results
This message occurs in conditional
Expressions (i.e. If then). Variables are
type identified, so equation and
assignments (x = 9) can be verified. In
an expression only numerical values can
be compared for greater than and less
than conditions.
Could not find the variable
See message.
198
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Problem/Message
Cause
Could not find the variable
defined by program text
See message.
Destination Event variables
can only be assigned an
Event or Boolean
The Variable is an Input event. It only
accepts types consisting of Boolean, and
events.
Program Instance does not
Exist
You attempted the “Call Program.#”, but
the program does not exist.
Single value expressions
can only be Boolean
constants, Events or
Boolean variables
This message occurs in conditional
Expressions (i.e. If then). Variables are
type identified, so equation and
assignments .(x = 9) can be verified.
String does not represent a
predefined name...
The string needs to match one of the
defined strings on record in the Epsilon
EP-P drive Registry data base.
String is not a selection
The string matches one of the defined
strings, but that string is not a selection.
Syntax error encountered
Parser Error Message. The Parser can
not understand your text sequence.
Text Strings are limited to 12
characters...
To change a Name you assign a quoted
text string to that name. In Epsilon EP-P
drive, text strings are fixed at 12
characters. If you use fewer than 12
characters, blanks are automatically
inserted. An error occurs if you attempt
to use more than 12 characters.
The Boolean variables can
only be assigned an Event
or Boolean value
The Variable only accepts types
consisting of Boolean, and events.
The destination variable
does not accept Data
The Variable’s internal data type
attribute was not found.
The destination variable
does not accept negative
numbers
You attempted to assign a negative
number to an unassigned variable .
The destination variable is
Read Only
This message occurs when trying to
assign a value to a read only variable.
The destination variable
only accepts a numeric
value
See message.
The destination variable
only accepts a Boolean or
Event value
See message.
The destination variable
only accepts quoted "text"
See message.
The destination variable
only accepts selection text
See message.
The destination variable's
resolution is less than the
resolution of the number
You attempted to assign a number with a
greater resolution of decimal points than
the variable will accept (i.e. index.0.vel =
2.34567).
The User Units setup will allow you to define
the desired decimal point resolution.
The number is outside the
range of the destination
variable
You attempted to assign a number that is
outside the variable’s range.
To determine the range comment out this
instruction and use the red dot help on the
variable.
The mix of variable or
expressions types can not
be added or subtracted
This message occurs in equations.
Variables are type identified, so equation
and assignments (x = 9) can be verified.
In an equation only numerical values can
be multiplied or divided. Booleans,
Selections, text and events can not be
added.
Epsilon EP-P Drive Reference Manual
Revision A3
Solution
In an expression you can use single variables
without a comparison, but , then they must be
a Boolean constants, Events or Boolean
variable.
199
www.emersonct.com
7.4
7.4.1
Problem/Message
Cause
The mix of variable or
expressions types can not
be compared(=)
This message occurs in conditional
Expressions (i.e. If then). Variables are
type identified, so equation and
assignments (x = 9) can be verified. In
an expression numerical, Boolean and
event values can be compared for
equality conditions. Selections and text
can not be used.
The mix of variable or
expression types can not be
multiplied or divided
This message occurs in equations.
Variables are type identified, so equation
and assignments (x = 9) can be verified.
In an equation only numerical values can
be multiplied or divided. Booleans,
Selections, text and events can not be
compared.
The Source Event<variable name> can only
be assigned <max number>
times
The limits to Source Event assignments
are the number of destinations assigned
to a single Output event is limited.
Generally this is three. For Selections it
is one. The Waitfor Instruction
temporarily assigns its Output Event
Operands. This is subject to the
assignment limitations.
The Selection variable can
only be assigned a
Selection value
The destination variable only accepts
selection values. Selection values are
fixed unquoted text. The selection text
must exactly match the available
selections of the Destination variable.
This instance does not exist
This variable is referencing an instance
that has not been created in your
application. For example “Index.9.vel”
the instance 9 of index has not been
defined.
This is not a fully qualified
variable
To use a variable it must be fully defined.
Some variables are global variables and
only the name is defined. Other
Variables require a name.name
convention. Other variables require an
instance number (index.1.vel). All the
components identifying the variable
must be available to qualify the variable.
This variable cannot be
assigned a selection value
The variable that you are attempting to
define with a selection does not accept
selection values.
This variable type cannot be
assigned a value
The Variable is of a type that does not
accept any assignments. A Source
Event variable is an example. You can
not assign a value to an output event.
The selection is not valid for
this variable
The variable that you are attempting to
define with a selection does accept
selection values. However the selection
you are attempting to use is not
accepted by this variable.
Trying to assign a selection
variable with bad selection
data
When checking to see if the selection
goes with the destination variable, the
source is not a defined selection for the
destination variable.
Solution
To use an Output Event in a Waitfor
instruction, there must be at least one free
assignment.
Online Status Indicators
Watch Window
PowerTools Pro contains a diagnostic utility called the Watch Window. The Watch Window can be used while PowerTools Pro is running and
the PC is online with the device. The Watch Window allows the user to monitor the status of all the desired system parameters in one location.
200
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
An example of the Watch Window is found in Figure 148 below.
To setup the Watch Window, select Tools\Watch Window from the PowerTools Pro menu. If not online with the device, the
Watch Window will be unavailable on the menu. Upon selecting Watch Window, the following window will appear.
Figure 147:
Watch Window, Select Parameters Window
The Select Parameters window as seen in Figure 147 allows the user to specify which parameters are to be seen in the Watch
Window. To select a parameter for the Watch Window, simple double-click on the parameter in the Drag Source window or
drag and drop the parameter from the Drag Source window on the left over to the Parameters Displayed in Watch Window on
the right and it will be added to the Watch Window.
Figure 148:
The Watch Window
Once a parameter is added to the Watch Window, it’s current value or state is constantly monitored. If a parameter in the
window changes value or state, it will change to a red color. It will remain red until it hasn’t changed for a period of 4 seconds.
After 4 seconds, the parameter will turn back to black in color. This allows the user to see what has changed recently without
looking directly at every parameter.
The following are descriptions of the buttons and controls on the Select Parameters window:
Clear All
By clicking on the Clear All button, all of the parameters in the Parameter Displayed in Watch Window pane will be erased and
Epsilon EP-P Drive Reference Manual
Revision A3
201
www.emersonct.com
the Watch Window closes.
Save Selections
By clicking on Save Selections, the user can save the specific parameters that have been added to the Watch Window. Once the selections
have been saved, the Restore Selections button can be used to monitor all the same parameters the next time the user opens the Watch
Window. Therefore, if there is a list of helpful diagnostic parameters the user wishes to see when online, those specific parameters can be
saved and recalled in the Watch Window at any time. The settings can be saved in the default file named “fm3watch.wch” or the user can
create their own file. Setup the parameter that will be displayed in the Watch Window, enter the file name in the Selection File text box, then
click the Save Selections button.
Restore Selections
By clicking on the Restore Selections button, the Watch Window will be filled with the list of parameters that were last saved using the Save
Selections button.
Select Defaults
The Select Defaults button adds the most commonly used parameters to the Watch Window.
Select I/O
The Select I/O button will add the drive digital inputs and outputs to the Watch Window.
Not Moving?
The Not Moving? button will load the watch window with a list of predefined parameters (shown in the following table) that will give an
indication why the motor is not moving.
Parameters
Expected Value to get Motion
Comments
DriveEnableStatus
True
Drive must be enabled.
Fault.Faulted
False
Motion stops on a fault.
DriveOK
True
The drive status must be ok to enable motion.
PowerStageEnabled
True
Must have power to move the motor.
Stop
False
Motion is stopped if stop is active.
PowerSupplyReady
True
PowerSupplyReady will become inactive if the 24 volt
logic power is taken away or if the bus voltage drops
below the "low bus fault" threshold.
MotionStop
False
Motion is stopped on motion stop.
SoftDriveDisable
False
Motion is prevented by SoftDriveDisable.
True
Absolute indexes can not executed until the Absolute
position is defined.
InPosn
True
If using "In Position" the last index is not considered
complete until this status is met. So motion will stop if
you can not achieve in position. While running this is
expected to be false as it is only true at the end of a
move and prior to starting a new move.
Feedhold
False
Feed Hold stops motion.
FeedRateOverride
100%
Feed rate scales the speed of the Motion. 100%
scaling indicates one to one scaling.
FeedRateDeactivate
False / True
Activate to disable FeedRate. If feedrate is 100% it
does not matter.
FoldbackActive
False
When Foldback is active it indicates a current
overload and the Foldback circuit is limiting the
current. Foldback in it’s self indicates motor selection
of wiring problems that effect motor motion.
SoftwareTravelLimitMinusActive
False
Motion stops when a travel limit is active.
SoftwareTravelLimitPlusActive
False
Motion stops when a travel limit is active.
TorqueLimitActive
False
Torque limits may effect motor motion as it reduces
motor generated torque.
Profile.0.MotionStop
False
Each profile has it’s own Stop. To get motion out of
this profile this parameter must be false.
Profile.0.FeedHold
False
Each profile has it’s own FeedHold. To get motion out
of this profile this parameter must be false.
Profile.1.MotionStop
False
Each profile has it’s own Stop. To get motion out of
this profile this parameter must be false.
Profile.1.FeedHold
False
Each profile has it’s own FeedHold. To get motion out
of this profile this parameter must be false.
AbsolutePosnValid
202
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Close
The Close button will close the Select Parameters window, while the Watch Window will remain open.
Help
The Help button will give associated help on the Watch Window setup.
User Level
The User Level setting is a filter for the parameters that are seen in the Select Drive Parameters list. If set to Easy, the
parameters used in most basic applications will be seen while the more advanced parameters are hidden. If set to Detailed,
the parameters used in more advanced applications will be added to the list. If set to Too Much, then all parameters available
in the system will be seen in the list. This allows the user to select the User Level they are most comfortable with to avoid
confusion. If a parameter has been selected and the User Level is changed, then the selected parameter will remain selected.
Write Parameter
Within the Select Parameters window the user can change the value of parameters in the drive’s RAM memory. Click on a
parameter in the Parameters Displayed in Watch Window pane. Just below the pane the parameter that was selected will be
shown along with either a check box, text box or list box. The type of box is depended on the parameter selected. Enter the
new parameter value and press the Write button.The data should change in the watch window to the new value.
7.4.2
Global Where Am I Button
In the Program View, when online and executing a program or sequence of programs, the user can display current program
status. Pressing the Where Am I button on the PowerTools Pro toolbar creates a blue triangle that appears on the line of the
program currently being executed.
The Global Where Am I can be used for diagnostics. When the user needs to know where in a complicated program the drive
is or when the user wishes to follow the logical flow of the program.
7.4.3
Motion Status
While the drive is online, the name of the program currently running or the motion type currently running will appear in the
status bar at the bottom left corner of the PowerTools Pro window.
7.5
Diagnostic Analog Output Test Points
The drive has two 10 bit Analog Outputs which may be used for diagnostics, monitoring or control purposes. These outputs
are referred to as Channel 1 and Channel 2. With the Epsilon EP-P drive the Analog Outputs are accessed from the Analog/
Sync Output connector (J5).
The Analog Output source is assigned to the outputs on the Analog Outputs view.
Epsilon EP-P Drive Reference Manual
Revision A3
203
www.emersonct.com
204
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8
Specifications
8.1
Dimensions and Clearances
The following table applies to A and B as shown in Figure 149 below.
Drive Model
Dimension “A”
(shown in inches/mm)
Dimension “B”
(shown in inches/mm)
EP202-B,-I,-IDN
2.11 [53.59]
0.45 [11.4]
EP204-B,-I,-IDN
2.11 [53.59]
0.45 [11.4]
EP206-B,-I,-IDN
2.82 [71.63]
0.45 [11.4]
EP202-P
2.69 [68.3]
1.03 [26.16]
EP204-P
2.69 [68.3]
1.03 [26.16]
EP206-P
3.40 [86.9]
1.03 [26.16]
5.94
[150.88]
5.22
[132.59]
“A”
2.5
[63.50]
“B”
.200
[5.08]
DDC-RJ45
1.20
[30.48]
(4X)Ø.219
[5.56]
8.099
[205.72]
7.70
[195.58]
0.75
[19.05]
3.50
[88.0]
Cable
Clearence
Figure 149:
EIO26 Cable
Epsilon EP202 through 206 Drive Dimensions and Clearances
Epsilon EP-P Drive Reference Manual
Revision A3
205
www.emersonct.com
3.40
[86.36]
5.94
[150.88]
5.86
[148.85]
2.69
[68.33]
1.03
[26.16]
5.23
[132.84]
2.5
[63.50]
1.20
[30.48]
0.20 [5.08]
4X Ø.219
DDC-RJ45
9.60
[243.84]
9.20
[233.68]
EP209-XXX-XX00
9606XX-XX A1
SN 0610E014
3.50
[88.0]
Cable
Clearence
0.75
[19.05]
EIO26 Cable
Figure 150:
Dimensional Drawing for all Epsilon EP209 Drive
206
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
3.40
[876.9]
5.96
[151.38]
1.03
[26.16]
5.23
[132.84]
1.20
[30.48]
2.5
[63.50]
DDC-RJ45
9.60
[243.84]
9.20
[233.68]
0.75
[19.05]
3.50
[88.0]
Cable
Clearence
Figure 151:
EIO26 Cable
Dimensional Drawings for all Epsilon EP216 Drives
Epsilon EP-P Drive Reference Manual
Revision A3
207
www.emersonct.com
8.2
8.2.1
Cable Diagrams
EIO26
1.530
0.770
E IO
PIN 1
10
LT. BLU
INPUT LINE 1
1
RED/WHT
INPUT LINE 2
11
INPUT LINE 3
2
INPUT LINE 4
12
ENABLE
INPUT LINE 5
3
INPUT LINE 6
13
INPUT LINE 7
4
OUTPUT LINE 1
7
OUTPUT LINE 2
17
OUTPUT LINE 3
8
OUTPUT LINE 4
18
I/O +V
19
I/O COM
20
INPUT LINE 8
14
INPUT LINE 9
5
INPUT LINE 10
LT. BLU/WHT
ORG/WHT
LT. GRN/WHT
GRN/WHT
YEL/GRY
PNK/WHT
ORG
YEL
PNK
BLU
RED
BLK
BLU/WHT
GRY/WHT
PUR/WHT
15
INPUT LINE 11
6
INPUT LINE12
16
OUTPUT LINE 8
21
INPUT LINE 13
22
INPUT LINE 14
23
INPUT LINE15
24
OUTPUT LINE 5
9
OUTPUT LINE 6
25
OUTPUT LINE 7
26
BRN/WHT
BRN
BLK/WHT
WHT/BLK
GRN
LIGHT GRN
GRY
PUR
WHT
DRAIN WIRE
1
2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26
SOLDER SIDE
Socket
208
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.3
8.3.1
XV Motor Cables
XTMDS
PIN 1
PE/GND
4
R
1
S
3
T
2
1
BRAID SHIELD
GRN/YEL
FORM WIRE
BRN
BLK
BLU
2
3
4
REAR VIEW OF
CONNECTOR
Epsilon EP-P Drive Reference Manual
Revision A3
209
www.emersonct.com
8.3.2
XCMDS
PE/GND
D
U
A
V
C
W
B
BRAID SHIELD
GRN/YEL
FORM WIRE
BRN
BLK
BLU
BLU
(20 AWG)
BLU/WHT (20 AWG)
Drain Wire
D
A
C
B
SOLDER SIDE
Socket
210
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.3.3
XCMDBS
PE/GND
D
U
A
V
C
W
B
BRK+
E
BRK -
BRAID SHIELD
GRN/YEL
FORM WIRE
BRN
BLK
BLU
BLU
(20 AWG)
BLU/WHT (20 AWG)
F
Drain Wire
F
A
G
E
D
B
C
SOLDER SIDE
Socket
Epsilon EP-P Drive Reference Manual
Revision A3
211
www.emersonct.com
8.3.4
XTBMS
PIN 1
+24V
1
0V
2
RED
BLK
DRAIN WIRE
1
2
REAR VIEW OF
CONNECTOR
212
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.3.5
XEFTS/XUFTS
Pin 1
PIN 1
A
3
A/
4
B
1
GRN
P
BRN
Inner Drain Wire
BLU
P
ORN
B/
2
Z
5
Z/
6
U
9
U/
10
V
7
V/
W
8
11
W/
12
+5 VDC
13
0V
14
Inner Drain Wire
BLK
P
YEL
WHT/GRY Inner Drain Wire
GRY/WHT
P
WHT/BRN
BRN/WHT
P
RED/ORG
ORG/RED
P
RED/BLU (18 ga.)
BLU/RED (18 ga.)
P
RED/GRN Inner Drain Wire
GRN/RED
1
A
2
A/
3
B
4
B/
5
Z
6
Z/
7
U
8
U/
9
V
10
11
V/
W
12
W/
13
+5 VDC
14
COMMON
15
MOTOR TEMP
P
15
SHIELD
Overall Shield Drain Wire
1
2
3
4
5
6
10
7
9
11 12 13 14 15
5
4
3
2
1
10 9 8 7 6
15 14 13 12 11
8
SOLDER SIDE
Pin
REAR VIEW OF
CONNECTOR
Epsilon EP-P Drive Reference Manual
Revision A3
213
www.emersonct.com
8.3.6
XEFCS/XUFSC
Pin 1
A
GRN
C
A/
D
B
A
B/
B
Z
E
Z/
F
U
M
U/
N
V
K
V/
W
L
BLU
BLK
H
0V
G
P
Inner Drain Wire
P
YEL
WHT/GRY
Inner Drain Wire
P
GRY/WHT
WHT/BRN
P
BRN/WHT
RED/ORG
P
ORG/RED
R
+5 VDC
Inner Drain Wire
ORN
P
W/
P
BRN
RED/BLU (18 ga.)
BLU/RED (18 ga.)
RED/GRN
P
Inner Drain Wire
GRN/RED
P
1
A
2
A/
3
B
4
B/
5
Z
6
Z/
7
U
8
U/
9
V
10
11
V/
W
12
W/
13
+5 VDC
14
COMMON
15
MOTOR TEMP
J
SHIELD
Overall Shield Drain Wire
A
M
L
K
P
H
G
5 4 3 2 1
10 9 8 7 6
15 14 13 12 11
C
D
E
R
S
J
B
N
T
F
SOLDER SIDE
Pin
SOLDER SIDE
Socket
214
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.4
8.4.1
NT and MG Motors Cables
CMDS
1 1/2" MAX.
3 3/4" MAX.
GRN/YEL
BRN
D
A
B
C
BLK
BLU
R
S
T
SHELL
A
G
F
B
H
C
D
E
SOLDER SIDE
8.4.2
CMMS
1 1/2" MAX.
3 3/4" MAX.
GRN/YEL
BRN
D
A
B
C
BLK
BLU
R
S
T
SHELL
F
A
B
G
E
D
C
SOLDERSIDE
Epsilon EP-P Drive Reference Manual
Revision A3
215
www.emersonct.com
8.4.3
CBMS
RED
B
BLK
C
DRAIN WIRE
A
GND
C
A
B
SOLDER SIDE
Socket
216
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.4.4
EFCS / UFCS
Pin 1
3 3/4" MAX.
1 1/2" MAX.
GRN
A
N
A/
P
B
B
B/
C
Z
M
Z/
U
U
F
U/
S
V
E
V/
W
R
G
W/
H
+5 VDC
K
GND
T
MOTOR OVERTEMP
A
NOT USED
V
BLU
BLK
GRY/WHT
BRN/WHT
P
P
RED/ORG
ORG/RED
P
RED/BLU
BLU/RED
P
RED/GRN Inner Drain Wire
GRN/RED
P
1
A
2
A/
3
B
4
B/
5
Z
6
Z/
7
U
8
U/
9
V
10
11
V/
W
12
W/
13
+5 VDC
14
COMMON
15
MOTOR TEMP
Outer Drain Wire
A
Z
5 4 3 2 1
10 9 8 7 6
15 14 13 12 11
B
S
T
V
U
G
F
C
D
E
SOLDER SIDE
Pin
SOLDER SIDE
Socket
To Motor MG/NT/MH
Epsilon EP-P Drive Reference Manual
Revision A3
P
WHT/BRN
R
X
W
K
J
H
Inner Drain Wire
WHT/GRY Inner Drain Wire
P
L
P
YEL
N
Y
Inner Drain Wire
ORN
Z
M
P
BRN
To DRIVE
217
www.emersonct.com
8.5
8.5.1
SYNC Cables
ENCO Cable
YEL/WHT
H
RED/WHT
A
BLK/WHT
I
BLU/WHT
B
J
YEL
F
RED
DRAIN WIRE
Z
GND
P
+5 V
Shield
A
H
B
C
I
J
E
B
Z/
P
BLK
D
A
B/
P
BLU
C
G
F
A/
P
D
SOLDER SIDE
Socket
218
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.5.2
SNCDD-915
Pin 1
Pin 1
BLK
1
A
A
2
B
3
RED
YEL
6
Z
Z
BLU
8
1
A
9
A
2
B
10
B
3
Z
11
Z
8
GND
4
3
P
PUR
4
5V
P
GRN
7
GND
P
ORG
5
B
P
BRN
Drain Wire
4
5
9
3
8
2
7
1
6
8
7
5
2
1
15 14 13 12 11 10 9
SOLDER SIDE
SOLDER SIDE
Pin
Pin
Epsilon EP-P Drive Reference Manual
Revision A3
6
219
www.emersonct.com
8.5.3
SNCFLOA
Pin 1
Blunt end
ENCODER OUT A
1
ENCODER OUT A
9
ENCODER OUT B
2
ENCODER OUT B
10
ENCODER OUT Z
3
ENCODER OUT Z
11
PULSE IN A (SINGLE ENDED)
4
PULSE IN B (SINGLE ENDED)
12
ANALOG OUT CHANNEL 1 +
7
ANALOG OUT CHANNEL 2 +
15
ANALOG OUT 0V
6
ANALOG OUT 0V
14
ANALOG COMMAND IN +
5
ANALOG COMMAND IN -
13
GND
8
BLU
ORN
GRN
BRN
7
6
5
P
BLK
YEL
P
WHT/BRN
BRN/WHT
P
WHT/GRY
GRY/WHT
P
RED/ORG
ORG/RED
P
RED/BLU
BLU/RED
P
GRN/RED
RED/GRN
8
P
4
3
2
P
1
15 14 13 12 11 10 9
SOLDER SIDE
Pin
220
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.5.4
SNCMD-815
Pin 1
+A
-A
+B
-B
+Z
-Z
GND
+5 VDC
RED
ORG
GRN
YEL
BLK
BRN
PUR
BLU
DRAIN WIRE
1
2
3
5
6
7
8
4
P
5
8
7
6
5
4
3
2
1
15 14 13 12 11 10 9
8
SOLDER SIDE
CONNECTOR END VIEW
Pin
8.5.5
3
11
8
P
7
4
2
9
2
10
P
6
3
1
1
P
Pin
SNCFLI
Pin 1
Blunt end
A
1
A
2
B
3
B
5
Z
6
Z
7
GND
8
5V
4
N/C
9
BLK
BRN
RED
ORG
9
P
YEL
GRN
P
BLU
PUR
P
Drain Wire
4
5
P
3
8
2
7
1
6
SOLDER SIDE
Pin
Epsilon EP-P Drive Reference Manual
Revision A3
221
www.emersonct.com
8.5.6
SNCMD-89
Pin 1
A
1
A
2
B
3
B
5
Z
6
Z
7
GND
8
5V
RED
2
GRN
3
P
YEL
5
BLK
6
P
BRN
7
PUR
8
P
BLU
4
4 Pin removed
Drain Wire
9
N/C
1
P
ORG
Completely remove pin 4
4
5
3
2
1
6
3
9
8
7
6
1
4
2
5
7
8
SOLDER SIDE
CONNECTOR END VIEW
Pin
Pin
8.5.7
SNCE
Pin 1
A+
1
A-
2
B+
3
B-
5
Z+
6
Z-
7
+5 Vdc
4
GND
8
RED/WHT
YEL/WHT
P
BLU/WHT
BLK/WHT
P
YEL
BLU
P
RED
BLK
P
A
A+
H
A-
B
B+
I
B-
C
Z+
J
Z-
D
+5 Vdc
F
GND
DRAIN WIRE
222
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
8.6
8.6.1
Communications Cables
ESA-SP-485
Drain Wire
4
7
WHT/BLU
P
ORG
6
220 Ω
10 TXRX-
WHT/ORG
5
15
16
WHT/BRN
1
18
P
BRN
8
SIGNAL GND
22 TXRX+
P
BLU
7
470 Ω
TXRX+ 2
TXRX-
5
P
GRN
3
470 Ω
SIGNAL GND
4
WHT/GRN
25
470 Ω
13 12 11 10 9
8
7
6
5
4
3
2
25 24 23 22 21 20 19 18 17 16 15
1
14
470 Ω
220 Ω
SOLDER SIDE
Pin
PIN 1
Pin 1
8.6.2
ETH-PATCH
8
1
1
8
1
2
3
6
4
5
7
8
Epsilon EP-P Drive Reference Manual
Revision A3
WHITE
ORANGE
P
LIGHT GREEN
GREEN
6
4
P
LIGHT BROWN
BROWN
2
3
P
BLUE
LIGHT BLUE
1
5
7
P
8
223
www.emersonct.com
224
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
9
Glossary
µs
Microsecond, which is 0.000001 seconds.
A
Amps.
Amplifier
Servo Drive.
ARMS
Amps Root Mean Squared (RMS).
Axis
The full system to control in a single motor shaft. A single Epsilon EP-P drive can denote an
axis.
AWG
American Wire Gauge.
Baud Rate
The number of binary bits transmitted per second on a serial communications link such as RS232. (1 character is usually 10 bits.)
Check Box
In a dialog box, a check box is a small box that the user can turn “On” or “Off” with the mouse.
When “On” it displays an X in a square; when “Off” the square is blank. Unlike option (radio)
buttons, check boxes do not affect each other; any check box can be “On” or “Off”
independently of all the others.
Complex Motion
A string of multiple motion commands and logical instructions that form a repeatable operation.
For the Epsilon EP-P drive, the configuration file defines complex motion by setups, functional
assignments and programs.
Compound Motion
The combination of indexes in a row in which the deceleration ramp of the first index goes to
the velocity of the secondary index. The first index must be initiated within a program
(Index.#.CompoundInitiate).
Configuration
The user-created application. It can be saved as a disk file or downloaded to configure the
Epsilon EP-P drive. It includes all the user-defined setup, assignments and programs.
CRC
Cyclical Redundancy Check, the data transfer error checking mechanism.
Destination
A function (i.e., Stop, Preset) that may be assigned to an input line. In Epsilon EP-P drive, the
input function is connected to the action through click and drag operations in PowerTools
Software on the Assignment View.
Epsilon EP-P Drive Reference Manual
Revision A3
225
www.emersonct.com
Dialog Box
A dialog box is a window that appears in order to collect information from the user. When the user has filled
in the necessary information, the dialog box disappears.
DIN Rail
Deutsche Industrie Norm Rail
DLL
In Microsoft® Windows®, a Dynamic Link Library contains a library of machine-language procedures that
can be linked to programs as needed at run time.
Downloading
The transfer of a complete set of parameters from the computer to a Epsilon EP-P drive.
Drive
Servo drive or amplifier.
EEPROM
An EEPROM chip is an Electrically Erasable Programmable Read-Only Memory; that is, its contents can
be both recorded and erased by electrical signals, but they do not go blank when power is removed.
EMC
Electromagnetic Compatibility. The relative immunity of a drive to the effects of electromagnetic fields.
EMI - Electro-Magnetic Interference
EMI is noise which, when coupled into sensitive electronic circuits, may cause problems.
Firmware
The term firmware refers to software (i.e., computer programs) that are stored in some fixed form, such as
read-only memory (ROM).
Flash
Another type of EEPROM.
Flash File
In the Epsilon EP-P drive, this file loads the firmware into the drive. Flash files can field upgrade the
firmware.
Global Where Am I
PowerTools feature that indicates which line of which user program is executing.
Home Routine
The home provides motion in applications in which the axis must precisely align with some part of a
machine.
Hysteresis
For a system with an analog input, the output tends to maintain its current value until the input level changes
past the point that set the current output value. The difference in response of a system to an increasing input
signal versus a decreasing input signal.
I/O
Input/Output. The reception and transmission of information between control devices. In modern control
systems, I/O has two distinct forms: switches, relays, etc., which are in either an on or off state, or analog
signals that are continuous in nature generally depicting values for speed, temperature, flow, etc.
226
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Index
An index is a complete motion sequence (defined motion profile) that moves the motor a
specific incremental distance or to an absolute position.
Inertia
The property of an object to resist changes in rotary velocity unless acted upon by an outside
force. Higher inertia objects require larger torque to accelerate and decelerate. Inertia is
dependent upon the mass and shape of the object.
Input Function
See destination. A function (i.e., Stop, Preset) that may be assigned to an input line. In
PowerTools Pro, the input function is connected to the action through click and drag operations
in PowerTools Software on the Assignment View.
Input Line
The terminals of a device or circuit to which energy is applied.
Jog
A jog produces rotation of the motor at controlled velocities in a positive or negative direction.
Least Significant Bit
The bit in a binary number that is the least important or having the least weight.
LED
Light Emitting Diode used on the front display of the drive.
List Box
In a dialog box, a list box is an area in which the user can choose among a list of items, such
as files, directories, printers or the like.
mA
Milliamp, which is 1/1000th of an Ampere.
MB
Mega-byte.
MODBUS
Communication Protocol by Modicon. The drives follows the Modbus specification outlined in
the Modicon Modbus Protocol Reference Manual, PI-MBNS-300 Revision G, November 1994.
Most Significant Bit
The bit in a binary number that is the most important or that has the most weight.
ms
Millisecond, which is 1/1000th of a second.
NVM
Non-Volatile Memory. NVM stores specifically defined variables as the variables dynamically
change. It is used to store changes through a power loss.
NTC
Negative Temperature Resistor
Epsilon EP-P Drive Reference Manual
Revision A3
227
www.emersonct.com
Option Button
See Radio Button.
Opto-isolated
A method of sending a signal from one piece of equipment to another without the usual requirement of
common ground potentials. The signal is transmitted optically with a light source (usually a Light Emitting
Diode) and a light sensor (usually a photosensitive transistor). These optical components provide electrical
isolation.
Output Function
See source. The terminals at which energy is taken from a circuit or device.
Output Line
The actual transistor or relay controlled output signal.
Parameters
User read only or read/write parameters that indicate and control the drive operation. These variables
generally hold numerical data defined in the Setup Views.
PC
Personal Computer.
PE
Protective Earth.
PID
Proportional-Integral-Derivative. An acronym that describes the compensation structure that can be used in
many closed-loop systems.
PLC
Programmable Logic Controller. Also known as a programmable controller, these devices are used for
machine control and sequencing.
PowerTools Pro V#
PowerTools Pro V# is a Windows® based software to interface with the Epsilon EP-P drive.
Radio Button
Also known as the Option Button. In a dialog box, radio buttons are small circles only one of which can be
chosen at a time. The chosen button is black and the others are white. Choosing any button with the mouse
causes all the other buttons in the set to be cleared.
RAM
RAM is an acronym for Random-Access Memory, which is a memory device whereby any location in
memory can be found, on average, as quickly as any other location. Commonly refers to Read-Write
memory, as opposed to Read-Only Memory (ROM, EPROM, EEPROM, Flash). RAM is considered volatile,
because its contents are lost during a power loss.
RMS
Root Mean Squared. For an intermittent duty cycle application, the RMS is equal to the value of steady state
current which would produce the equivalent heating over a long period of time.
ROM
ROM is an acronym for Read-Only Memory. A ROM contains computer instructions that do not need to be
changed, such as permanent parts of the operating system.
228
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
RPM
Revolutions Per Minute.
Serial Port
A digital data communications port configured with a minimum number of signal lines. This is
achieved by passing binary information signals as a time series of 1’s and Ø’s on a single line.
Source
The terminals at which energy is taken from a circuit or device.
Travel Limit
The distance that is limited by either a travel limit switch or the software.
Torque
The moment of force, a measure of its tendency to produce torsion and rotation about an axis.
Uploading
The transfer of a complete set of parameters from a drive to the configuration file.
User Units
Ability of program to allow user to specify which type of units will measure and specify motion
and time.
Vac
Volts, Alternating Current.
Variable
A labeled value that encompasses numeric boolean, input function, and output functions.
Vdc
Volts, Direct Current.
Velocity
The rate of change in position in a given direction during a certain time interval.
View
Portion of screen within frame.
Windows®, Microsoft®
Microsoft Windows is an operating system that provides a graphical user interface, extended
memory and multi-tasking. The screen is divided into windows and the user uses a mouse to
start programs and make menu choices.
Epsilon EP-P Drive Reference Manual
Revision A3
229
www.emersonct.com
230
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
10
Index
Symbols
+/- Travel Limit, 197
Encoder Line Fault, 196
Encoder State, 196
End, 122
Error Messages, 197
Example Programs, 139
A
F
Add Program Icon, 136
Adding a Program, 136
All "On", 197
Analog Output, 197
B
Book Mark, 111
Brake Operation and Wiring, 197
Fault Codes, 194
Fault Descriptions, 195
Find, 111
Find Next, 111
Firmware Checksum, 195
Following Error Fault, 196
For Count/Next, 122
Formula, 124
G
C
Cable Diagrams, 208
Call Program, 121
Cam Table Smilely Face, 101
D
Delete All Book Marks, 111
Delete Program Icon, 136
Deleting a Program, 136
Diagnostic Display, 193
Digital Inputs and Outputs, 84
Disable Error Check, 112
Display Dual Loop Setup, 37
Do While/Loop, 121
Drag In I/O, 112
Drag In Operands, 112
Drag In Variables, 112
Drive Faults, 197
Drive Input Signal, 37
Dual Loop Encoder Ration, 38
Dual Loop View, 37
Dwell for Master Dist, 127
Dwell For Time, 126
Gear Stop, 131
Gear.Initate, 131
H
High DC Bus Fault, 196
Home.Initiate, 130
I
If/Then/Endif, 123
Index.CompoundInitiate, 129
Index.Initiate, 128
Introduction, 1
J
Jog.MinusInitiate, 131
Jog.PlusInitiate, 131
Jog.Stop, 130
L
E
Else, 122
Epsilon EP-P Drive Reference Manual
Revision A3
Label, 124
Lock Program, 112
Low DC Bus Fault, 196
231
www.emersonct.com
M
Ready to Run, 193
Stop All, 112
Sync Fault, 197
Motion Instructions, 126
Motion Modifiers, 132
Motor Over Temperature Fault, 196
T
N
Timeline Control Instructions, 132
Next Book Mark, 111
Non-volatile Memory Invalid, 195
U
O
Undo Last Change, 111
Using Capture, 132
Using Last, 132
On Profile, 132
Over Speed Fault, 196
W
P
Wait For, 124
Wait For Time, 125
Power Stage Fault, 196
Power-Up Self-Test Failure, 195
Previous Book Mark, 111
Program Instruction Types, 121
Program Toolbar Icons, 111
Program Where Am I?, 112
Program.#.ProgramStop, 131
Program.Initiate, 131
Programming Error Messages, 198
R
Red Dot Help, 111
Redo Last Change, 111
Registration Index, 13
RMS Shunt Power Fault, 196
Rotary + and Rotary - Indexes, 13
Rotary Indexes, 13
Run Anytime Programs, 136
Run This Program, 112
S
Safety Information, v
Safety of Machinery, v
Safety Precautions, v
Setup, 27
Setup, Commissioning and Maintenance, v
status codes
decimal point, 193
Ready, 193
232
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Since 1979, the “Motion Made Easy” products, designed and manufactured
in Minnesota U.S.A., are renowned in the motion control industry for their
ease of use, reliability and high performance.
For more information about Control Techniques “Motion Made Easy”
products and services, call (800) 893-2321 or contact our website at
www.emersonct.com.
Control Techniques Americas LLC
Division of EMERSON Co.
12005 Technology Drive
Eden Prairie, Minnesota 55344
U.S.A.
Customer Service
Phone: (952) 995-8000 or (800) 893-2321
Fax: (952) 995-8129
Technical Support
Phone: (952) 995-8033 or (800) 893-2321
Fax (952) 995-8020
graphics/CT3.5.tif @ 300 dpi i
graphics/eia_BlackWhiteOnWhite.tif @ 2400 dpi i
graphics/cover_globe4.eps i
graphics/CT3.5.tif @ 300 dpi i
graphics/Warning_AQ.wmf v
graphics/Caution_AQ.wmf v
graphics/EpsilonEP-202_4EthrOptionISO.eps 1
graphics/EP209FeaturesView2D.eps 2
graphics/EP216PPB_ISO.eps 2
Screens/EPP_Hierarchy.jpg @ 300 dpi 3
Screens/JogView.JPG @ 150 dpi 4
graphics/Home_01.eps 4
graphics/Sensor_01.wmf 5
graphics/Sensor_03.wmf 5
graphics/Sensor_02.wmf 6
graphics/FM_08.wmf 6
graphics/fm_12b.eps 6
graphics/Offset_05.wmf 7
graphics/offset_01a.eps 7
graphics/offset_02a.eps 8
graphics/offset_03a.eps 8
graphics/Home7.eps 9
graphics/FM_09.wmf 9
graphics/Fm_10.eps 10
graphics/Home_09.eps 10
graphics/Index_06.wmf 10
graphics/FM_03.wmf 11
graphics/Index_absolute.gif @ 150 dpi 11
graphics/Index_03.eps 12
graphics/Index_08.eps 12
graphics/Index_04.eps 12
graphics/Index_09.eps 13
graphics/Upload_button.gif @ 75 dpi 14
Screens/UploadDrive.JPG @ 150 dpi 15
graphics/Download_button.gif @ 75 dpi 15
Screens/DownloadDevice_New.JPG @ 150 dpi 16
Screens/ChangePath_New.JPG @ 150 dpi 16
graphics/Upload NVM.bmp @ 300 dpi 17
graphics/NVM Parameters on Download.bmp @ 300 dpi 17
graphics/Update to RAM.bmp @ 75 dpi 17
graphics/Caution_AQ.wmf 17
graphics/updateRAM.wmf 18
Screens/Preference_Comms.GIF @ 150 dpi 18
Screens/Preference_PopUps.GIF @ 150 dpi 19
Screens/Preference_MotorDDF.GIF @ 150 dpi 20
Screens/SecureDownload.GIF @ 150 dpi 21
fm4 screens/Secure Download Screen - 2.bmp @ 150 dpi 21
fm4 screens/Secure File Upload Screen.bmp @ 150 dpi 21
Screens/StatusOnlineTab.GIF @ 150 dpi 23
Epsilon EP-P Drive Reference Manual
Revision A3
235
www.emersonct.com
Screens/GraphView.JPG @ 150 dpi 25
Screens/SetUpView.GIF @ 150 dpi 27
graphics/Motor Rotate.bmp @ 150 dpi 28
Screens/MotorView_Offline.GIF @ 150 dpi 29
graphics/Caution_AQ.wmf 29
graphics/AutoTune_Mode3.JPG @ 150 dpi 32
graphics/Warning_AQ.wmf 33
graphics/UserDefinedMotor.gif @ 150 dpi 34
graphics/Overwritstdmotor.bmp @ 150 dpi 34
Screens/UserUnitsView.GIF @ 150 dpi 35
graphics/DualLoopView.jpg 37
Screens/MasterUnitsView.GIF @ 150 dpi 38
graphics/VirtualMasterView.JPG @ 150 dpi 40
Screens/PositionView.GIF @ 150 dpi 42
graphics/VelocityView.gif @ 150 dpi 44
Screens/RampsView.GIF @ 150 dpi 45
graphics/Fast to Slow - User Ramps vs. Auto Ramps.eps 46
graphics/Slow to Fast - User Ramps vs. Auto Ramps.eps 47
Screens/TorqueView.GIF @ 150 dpi 48
Screens/DistanceRecovery.GIF @ 150 dpi 49
Screens/TuningView.GIF @ 150 dpi 49
Screens/ShuntView.GIF @ 150 dpi 50
Screens/FaultsView.GIF @ 150 dpi 52
graphics/FaultWindow.gif @ 150 dpi 52
Screens/FaultLogTab.GIF @ 150 dpi 53
Screens/FaultCountsTab.GIF @ 150 dpi 54
Screens/FaultLogTab.GIF @ 150 dpi 55
Screens/NVMView.GIF @ 175 dpi 55
Screens/PLSView.GIF @ 150 dpi 56
Screens/CaptureView.GIF @ 150 dpi 58
graphics/capture1.eps 58
graphics/capture2.wmf 59
Screens/QueueView.GIF @ 150 dpi 60
graphics/queue1.wmf 60
graphics/Queue Object - Detailed.eps 62
Screens/TimersView.GIF @ 150 dpi 62
graphics/EdgeOnTimer.jpg @ 300 dpi 63
graphics/LevelOnTimer.jpg @ 300 dpi 63
graphics/EdgeOffTimer.jpg @ 300 dpi 64
graphics/LevelOffTimer.jpg @ 300 dpi 64
graphics/CumulativeOnTimer-NoReset.jpg @ 300 dpi 65
graphics/CumulativeOnTimer-WithReset.jpg @ 300 dpi 65
graphics/CumulativeOffTimer-NoReset.jpg @ 300 dpi 66
graphics/CumulativeOffTimer-WithReset.jpg @ 300 dpi 66
graphics/WatchdogTimer.jpg @ 300 dpi 67
graphics/OneShotTimer.eps 67
graphics/TimerObjectBlockDia.eps 68
graphics/TimerEnableExample1.jpg @ 300 dpi 69
graphics/TimerEnableExample2.jpg @ 300 dpi 69
236
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Screens/VariablesView.GIF @ 150 dpi 70
Screens/UserBitView.GIF @ 150 dpi 72
graphics/Bit register.eps 73
graphics/UserBit_RW.eps 73
Screens/UserBitViewMask.GIF @ 150 dpi 74
graphics/Control Words.eps 74
graphics/Status Words.eps 75
graphics/ControlWordView.JPG @ 150 dpi 75
graphics/PackBitsCtrlWordOnline.JPG @ 150 dpi 76
graphics/PackBitsEthernet.JPG @ 150 dpi 77
graphics/StatusWordView.JPG @ 150 dpi 77
graphics/PackBitsStatusTabOnline.JPG @ 150 dpi 78
graphics/PackBitsStatusEthernet.JPG @ 150 dpi 79
Screens/AssignmentsView.GIF @ 175 dpi 80
graphics/AssignedAssignments.eps 81
Screens/SelectorView.GIF @ 150 dpi 82
Screens/AssignSelectors.GIF @ 150 dpi 83
Screens/InputsView.GIF @ 150 dpi 84
graphics/Debounce Time.wmf 84
Screens/OutputLinesView.GIF @ 150 dpi 85
Screens/ANAlogInputsView.GIF @ 150 dpi 85
Screens/AnalogOutputsView.GIF @ 150 dpi 86
Screens/JogView.GIF @ 150 dpi 88
graphics/FM_04_2.wmf 89
graphics/jogplusac1.wmf 90
Screens/HomeView.GIF @ 150 dpi 90
graphics/FM_07.wmf 92
Screens/IndexView.GIF @ 150 dpi 93
Screens/IndexViewTimed.GIF @ 150 dpi 94
graphics/Tindexes.eps 95
graphics/Add Index Icon.bmp @ 75 dpi 97
graphics/Delete Index Icon.bmp @ 75 dpi 97
Screens/GearingView.GIF @ 150 dpi 98
graphics/gearratio.gif @ 200 dpi 99
graphics/CammingMaster.eps 100
Screens/CammimgTableView copy.gif @ 150 dpi 100
graphics/SmileFace_Camming.JPG @ 200 dpi 101
Screens/TorqueModeOnline.JPG @ 150 dpi 102
Screens/ProfileViewOnline.GIF @ 150 dpi 104
graphics/Profile 1.tif @ 300 dpi 104
Screens/ModbusRTUView.GIF @ 150 dpi 106
graphics/variableassign.bmp @ 96 dpi 106
Screens/ModbusMasterView.JPG @ 150 dpi 107
Screens/ModbusMasterViewSlv.JPG @ 150 dpi 108
graphics/ModbusMasterDiagram.eps 108
Progbuttons/undo button.gif @ 100 dpi 111
Progbuttons/RedoLastChange.gif @ 100 dpi 111
Progbuttons/FindButton.gif @ 100 dpi 111
Progbuttons/FindNextButton.gif @ 100 dpi 111
Epsilon EP-P Drive Reference Manual
Revision A3
237
www.emersonct.com
Progbuttons/Bookmark.gif @ 100 dpi 111
Progbuttons/NextBookmark.gif @ 100 dpi 111
Progbuttons/PrevBookmark.gif @ 100 dpi 111
Progbuttons/DeleteBookmark.gif @ 100 dpi 111
Progbuttons/RedotHelp.gif @ 100 dpi 111
Progbuttons/DragInIO.gif @ 100 dpi 112
Progbuttons/DragInOper.gif @ 100 dpi 112
Progbuttons/DragInVari.gif @ 100 dpi 112
Progbuttons/LockProgram.gif @ 100 dpi 112
Progbuttons/RunProg.gif @ 100 dpi 112
Progbuttons/ProgWhereAmI.gif @ 100 dpi 112
Progbuttons/StopAll.gif @ 100 dpi 112
Progbuttons/DisablErrChck.gif @ 100 dpi 112
graphics/CyclicProgramView.JPG @ 150 dpi 113
graphics/ProgramView.JPG @ 150 dpi 114
graphics/RealTimeProgramView.JPG @ 150 dpi 115
graphics/TimeSlice_2.eps 115
graphics/Control Loop + User.eps 116
graphics/Control Loop + Cyc + User(1).eps 117
graphics/Control Loop + Cyc + User(2).eps 117
graphics/Control Loop + Cyc + User(3A).eps 117
graphics/Control Loop + Cyc + User(4).eps 118
graphics/Control Loop + Cyc + User(5).eps 118
graphics/Control Loop + RT + User(1).eps 118
graphics/Control Loop + RT + User(2).eps 119
graphics/Control Loop + RT + User(3).eps 119
graphics/Control Loop + RT + User(4).eps 119
graphics/Control Loop + RT + Cyc + User(1).eps 120
graphics/Control Loop + RT + Cyc + User(2).eps 120
graphics/Control Loop + RT + Cyc + User(3).eps 120
graphics/programflow.wmf 121
graphics/SetCamMasterOffset.eps 128
graphics/SetCamSlaveOffset.eps 128
graphics/velprofile1.eps 129
graphics/velprofile2.eps 129
graphics/Add Program Icon.bmp @ 300 dpi 136
graphics/Delete Program Icon.bmp @ 300 dpi 136
graphics/ProgramView_RunAnytime.JPG @ 150 dpi 137
fm4 screens/Progblock1.wmf 138
fm4 screens/progblock2.wmf 138
graphics/TimeSlice_2Blocked.eps 138
graphics/progblock3.eps 139
Screens/tuning 01.gif @ 150 dpi 188
Screens/tuning02.gif @ 175 dpi 189
graphics/Tuning_01.wmf 191
Display LEDs/R.eps 193
Display LEDs/b.eps 193
Display LEDs/d.eps 193
Display LEDs/Big C.eps 193
238
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Display LEDs/c.eps 193
Display LEDs/dot.eps 193
Display LEDs/homing.eps 193
Display LEDs/X.eps 193
Display LEDs/slash.eps 193
Display LEDs/J.eps 193
Display LEDs/K.eps 193
Display LEDs/P.eps 194
Display LEDs/P.eps 194
Display LEDs/Big T.eps 194
Display LEDs/V.eps 194
Display LEDs/Flash.eps 194
Display LEDs/I.eps 194
Display LEDs/N.eps 194
Display LEDs/U.eps 194
Display LEDs/Z.eps 194
Display LEDs/H.eps 194
Display LEDs/lowDCbus.eps 194
Display LEDs/encoderS.eps 195
Display LEDs/E.eps 195
Display LEDs/M.eps 195
Display LEDs/RMS_Shunt.eps 195
Display LEDs/overspeed.eps 195
Display LEDs/F.eps 195
Display LEDs/L.eps 195
Display LEDs/all on.eps 195
Display LEDs/4.eps 195
Display LEDs/A.eps 195
Display LEDs/Flash.eps 195
Display LEDs/I.eps 195
Display LEDs/N.eps 195
Display LEDs/Z.eps 196
Display LEDs/H.eps 196
Display LEDs/lowDCbus.eps 196
Display LEDs/encoderS.eps 196
Display LEDs/E.eps 196
Display LEDs/M.eps 196
Display LEDs/RMS_Shunt.eps 196
Display LEDs/overspeed.eps 196
Display LEDs/A.eps 196
Display LEDs/F.eps 196
Display LEDs/L.eps 197
Display LEDs/Sync_dash.eps 197
Display LEDs/4.eps 197
Display LEDs/all on.eps 197
Screens/WatchWindow.GIF @ 150 dpi 201
Screens/WatchWindowSelected.GIF @ 150 dpi 201
graphics/Epsilon206_WOEtherClearance.eps 205
graphics/Epsilon209_WEthernetClearance.eps 206
Epsilon EP-P Drive Reference Manual
Revision A3
239
www.emersonct.com
graphics/Epsilon216_wEthernetClearance.eps 207
graphics/Cables/EIO_a2.wmf 208
graphics/Cables/810757-01_EIO26.eps 208
graphics/Cables/810862-01_XTMDS.eps 209
graphics/Cables/810866-A1_XCMDS.eps 210
graphics/Cables/810867-A1_XCMDBS.eps 211
graphics/Cables/810863-01_XTBMS.eps 212
graphics/Cables/810871-01_XEFTS.eps 213
graphics/Cables/810875-01_XEFCS.eps 214
graphics/Cables/810719-D3_CMDSassy.eps 215
graphics/Cables/CMDSwir_a4.wmf 215
graphics/Cables/810719-D3_CMDSassy.eps 215
graphics/Cables/CMMSwir_a5.wmf 215
graphics/Cables/810728-A7_CBMS.eps 216
graphics/Cables/810815-000-D2-2d.eps 217
graphics/810578-000-A4-ENCOassy.eps 218
graphics/810578-000-A4-ENCOwire.eps 218
graphics/Cables/810753-01_SNCDD-915.eps 219
graphics/Cables/810755-01_SNCFLOA.eps 220
graphics/Cables/810873-01_SNCMD-815.eps 221
graphics/Cables/810752-01_SNCFLI.eps 221
graphics/Cables/810874-01-SNCMD89.eps 222
graphics/Cables/810789-000-A4-SNCEassy.eps 222
graphics/Cables/810789-000-A4-SNCEwire.eps 222
graphics/Cables/810308-01_ESA-SP485.eps 223
graphics/Cables/810241-01_ETH-PATCH.eps 223
240
www.emersonct.com
Epsilon EP-P Drive Reference Manual
Revision: A3
Was this manual useful for you? yes no