Programmable LED indicator
Programmable LED indicator
5714
– 4-digit 14-segment LED display
– Input for mA, V, Ohm, RTD, TC and potentiometer
– 2 relays and analog output
– Universal supply
– Front key programmable
Application
• Display for digital readout of current / voltage / resistance /
temperature or potentiometer signals.
• Process control with 2 potential-free relays and / or analog
output.
• For local readout in extremely wet atmospheres with a
specially designed splash-proof cover.
Connections
Technical characteristics
• 4-digit LED indicator with 13.8 mm 14-segment characters.
Max. display readout -1999...9999 with programmable
decimal point and relay ON / OFF indication.
• All standard operational parameters can be adjusted to any
application by way of the front function keys.
• Help texts in eight languages can be selected via a menu
item.
• PR5714 is available fully-configured according to
specifications ready for process control and visualization.
• In versions with relay outputs the user can minimize the
installation test time by activating / deactivating each relay
independently of the input signal.
Mounting / installation
• To be mounted in panel front. The included rubber packing
must be mounted between the panel cutout hole and the
display front to obtain a protection degree of IP65 (type 4X).
For extra protection in extreme environments, PR5714 can be
delivered with a specially designed splash-proof cover as
accessory.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree (mounted
in panel).........................................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP65 / Type 4X, UL50E
Mechanical specifications
Dimensions (HxWxD).....................................
Cut out dimensions........................................
Weight approx................................................
Wire size, pin 41-46 (max.)............................
Wire size, others, max...................................
48 x 96 x 120 mm
44.5 x 91.5 mm
230 g
1 x 1.5 mm2 stranded wire
1 x 2.5 mm2 stranded wire
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Max. power consumption............................... 2.5 W (5714A)
Max. power consumption............................... 3.0 W (5714B/C)
Max. power consumption............................... 3.5 W (5714D)
Internal consumption...................................... 2.2 W (5714A)
Internal consumption...................................... 2.7 W (5714B/C)
Internal consumption...................................... 3.2 W (5714D)
Isolation voltage, test /
working........................................................... 2.3 kVAC / 250 VAC
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 1...60 s
mA / V input (programmable)......................... 0.4...60 s
Auxiliary supply: 2-wire supply
(pin 46...45).................................................... 25...15 VDC / 0...20 mA
EMC immunity influence................................ < ±0.5% of readout
Input specifications
Output specifications
Display readout..............................................
Decimal point.................................................
Digit height.....................................................
Display updating............................................
Input outside input range
is indicated by................................................
Current output: Signal range.........................
Programmable current ranges.......................
-1999...9999 (4 digits)
Programmable
13.8 mm
2.2 times / s
Explanatory text
0...20 mA
0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/800 Ω/16 VDC
Load stability, current output.......................... ≤0.01% of span/100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
Relay output: Relay functions........................ Setpoint
Hysteresis...................................................... 0...100%
ON and OFF delay......................................... 0...3600 s
Sensor error reaction..................................... Break / Make / Hold
Max. voltage................................................... 250 VRMS
Max. current................................................... 2 AAC
Max. AC power.............................................. 500 VA
Max. load at 24 VDC...................................... 1 A
Approvals
EMC............................................................... EN 61326-1
LVD................................................................ EN 61010-1
GOST R......................................................... Yes
DNV Marine.................................................... Stand. f. Certific. No. 2.4
UL................................................................... UL 508
5714-061714
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000 Ni50, Ni100,
Ni120, Ni1000, Cu10, Cu20,
Cu50, Cu100
RTD input....................................................... Linear resistance
RTD input....................................................... Potentiometer
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Yes
Short circuit detection, RTD........................... < 15 Ω
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Yes
Sensor error current: When
detecting / else............................................... Nom. 2 μA / 0 μA
Current input: Measurement
range.............................................................. 0...20 mA
Current input: Programmable
measurement ranges..................................... 0...20 and 4...20 mA
Input resistance, current
input............................................................... Nom. 20 Ω + PTC 25 Ω
Sensor error detection, current
input............................................................... Loop break 4...20 mA
Voltage input: Measurement
range.............................................................. 0...12 VDC
Programmable measurement ranges,
VDC................................................................ 0/0.2...1; 0/2...10 VDC
Input resistance, voltage
input............................................................... Nom. 10 MΩ