Below you will find brief information for fireplaces MEZZO 1000-AU, MEZZO 1300-AU, MEZZO 1300ST-AU. This manual is intended for use by qualified personnel who are certified to install gas fireplaces. It contains important safety instructions, framing and finishing details, vent system configuration and electrical/gas information as well as steps on how to setup the appliance.
Advertisement
Advertisement
Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
NOTICE: DO NOT discard this manual!
Models:
MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1300ST-AU
MEZZO-1600-AU
Ref No: GMK10222
AS4553:
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
• DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
DANGER
NOTE: NOT INTENDED FOR
FIREPLACE INSERT.
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
DO NOT PLACE ARTICLES ON OR AGAINST THIS APPLIANCE.
DO NOT USE OR STORE FLAMMABLE MATERIALS NEAR THIS APPLIANCE.
DO NOT SPRAY AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHILE IT IS IN OPERATION.
DO NOT MODIFY THIS APPLIANCE.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
1
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
Installation Standard Work Checklist . . . . . . . . . . . . . . . . . . . . 3
1 Product Specific and Important Safety Information
A. Appliance Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. Glass Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. Gas Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . 4
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 5
E. Non-Combustible Materials Specification. . . . . . . . . . . . . . 5
F. Combustible Materials Specification . . . . . . . . . . . . . . . . . 5
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 6
B. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . 6
C. Inspect Appliance and Components . . . . . . . . . . . . . . . . . . 6
3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams . . . . . . . 7
B. Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . 11
C. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 12
D. Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 16
B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
C. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
D. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
E. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
F. Exhaust Restrictor Instructions. . . . . . . . . . . . . . . . . . . . . 18
G. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 26
B. Wall Penetration Framing/Firestops . . . . . . . . . . . . . . . . . 26
C. Install the Ceiling Firestop . . . . . . . . . . . . . . . . . . . . . . . . 27
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 27
E. Installing the Heat-Zone
®
Kit . . . . . . . . . . . . . . . . . . . . . . 28
6 Appliance Preparation
A. Vent Collar Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . 29
B. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 30
C. Installing Non-Combustible Facing Material . . . . . . . . . . 31
7 Venting and Chimneys
A. Assemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . . 32
B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 33
C. Secure The Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . 33
D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 34
E. Vertical Termination Requirements . . . . . . . . . . . . . . . . . . 35
F. Horizontal Termination Requirements . . . . . . . . . . . . . . . 36
8 Electrical Information
A. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
B. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
C. Gas Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
D. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
E. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 43
F. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10 Finishing
A. Facing and Finishing Instructions. . . . . . . . . . . . . . . . . . . 45
B. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 50
C. Decorative Front Dimensions for Finishing . . . . . . . . . . . 51
11 Appliance Setup
A. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
B. Remove the Shipping Materials/Install Vanity Panel . . . . 52
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
D. Install Glass Refractory Panels . . . . . . . . . . . . . . . . . . . . 53
E. Install Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
F. Install Log Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
G. Appliance Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
12 Reference Materials
A. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 57
B. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
2
= Contains updated information.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this installation manual.
Customer:
Lot/Address:
Model (circle one): MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1600-AU, MEZZO-1300ST-AU
Date Installed:
Location of Fireplace:
Installer:
Dealer/Distributor Phone #
Serial #:
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can lead to a fire or explosion.
Appliance Install Sections 3 and 6
Verified that the chase is insulated and sealed. (Pg. 12)
YES
Required factory included non-combustible board is in place. (Pg. 31)
Verified clearances to combustibles. (Pg. 11,13,14)
IF NO, WHY?
___________________________
___________________________
___________________________
___________________________ Fireplace is leveled and secured. (Pg. 30)
Pipe heat shield is attached to header. Header no wider than 3.5 in.(2x4)
(Pg. 29) ___________________________
Required factory included non-combustible board is in place.
Venting/Chimney Sections 4,5 and 7
Venting configuration complies to vent diagrams. (Pg. 16-25)
Venting installed, locked, and secured in place with proper clearance.
Firestops installed. (Section 5)
Attic insulation shield installed. (Pg. 27)
Exterior wall/Roof flashing installed and sealed. (Section 7)
Terminations installed and sealed. (Section 7)
___________________________
___________________________
___________________________
___________________________
___________________________
___________________________
Electrical Section 8 (Pg 38-40)
Unswitched power (220/240 VAC) provided to the appliance.
Switch wires properly installed.
___________________________
___________________________
Gas Section 9 (Pg 41-44)
Proper appliance for fuel type.
Was a conversion performed?
Leak check performed and inlet pressure verified.
Verified proper air shutter setting for installation type.
___________________________
___________________________
___________________________
___________________________
Finishing Section 10 (Pg 45-51)
Combustible materials not installed in non-combustible areas.
Verified all clearances meet installation manual requirements.
___________________________
___________________________
Finishing done correctly using inside fit or overlap fit method. ___________________________
Finishing template removed. ___________________________
Mantels and wall projections comply with installation manual requirements. ___________________________
Appliance Setup Section 11 (Pg 52-56)
All packaging and protective materials removed (inside & outside of appliance).
Refractories and media installed correctly.
Glass assembly installed and secured.
Accessories installed properly.
___________________________
___________________________
___________________________
___________________________
Decorative front properly installed. ___________________________
Manual bag and all of its contents are removed from inside/under
the appliance and given to party responsible for use and operation.
Started appliance and verified no gas leaks exist.
Lights work in all switched positions (if so equipped).
___________________________
___________________________
___________________________
Component heat shield is installed. (Pg. 36) ___________________________
Hearth & Home Technologies recommends the following:
• Photographing the installation and copying this checklist for your file.
• That this checklist remain visible at all times on the appliance until the installation is complete.
Comments: Further description of the issues, who is responsible (Installer/ Builder/ Other Trades, etc) and corrective action needed _____________________________________________________________________________________
_________________________________________________________________________________________________
Comments Communicated to party responsible ____________________ by ______________________on ___________
= Contains updated information.
2304-972 Rev. C 5/15
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
3
1
Product Specific and Important Safety Information
A. Appliance Certification
C. Gas Pressure Requirements
Pressure requirements for MEZZO-AU fireplaces are shown in table below.
MODEL: MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1300ST-AU, MEZZO-1600-AU
LABORATORY: IAMPO OCEANA
TYPE: Direct Vent Heater
STANDARD: AS:4553
Two taps are provided on the right hand side of the gas control for a test gauge connection to measure the inlet and outlet pressures.
This product is listed to ANSI standards for “Vented Gas
Fireplace Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for
Use at High Altitudes”.
The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 3.4 kPa.
If the fireplace must be isolated from the gas supply piping system by closing an individual shut-off valve, it must be of the handle-less type.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
B. Glass Specifications
This appliance is equipped with 5 mm ceramic glass. Replace glass only with 5 mm ceramic glass. Please contact your dealer for replacement glass.
MEZZO-1000-AU
NATURAL GAS ULPG
MEZZO-1300-AU,
MEZZO1300ST-AU
NATURAL GAS ULPG
MEZZO-1600-AU
NATURAL GAS ULPG
Inlet Gas Pressure 1.13 - 3.40 kPA 2.75 - 3.40 kPA 1.13 - 3.40 kPA 2.75 - 3.40 kPA 1.13 - 3.40 kPA 2.75 - 3.40 kPA
Outlet (Manifold)
Gas Pressure
Max. Gas Consumption
Min. Gas
Consumption
Burner Injector
DMS (mm)
Pilot Injector
.87 kPA
32.55
22.07
#36
(2.71 mm)
.023 in.
(.584 mm)
2.40 kPA
32.05
23.22
.#52
(1.61 mm)
.010 in.
(.254 mm)
.87 kPA
43.62
(43.62 ST)
29.36
(31.91 ST)
.124 in.
(3.15 mm)
.023 in.
(.584 mm)
2.40 kPA
39.69
(39.69 ST)
28.68
(28.82 ST)
#49
(1.85 mm)
.010 in.
(.254 mm)
.87 kPA
52.19
35.76
#28
(3.57 mm)
.023 in.
(.584 mm)
2.40 kPA
44.65
32.54
#48
(1.93 mm)
.010 in.
(.254 mm)
NOTE: The gas control valve supplied with this product is approved for a maximum inlet pressure of
3.40 kPa. For pressures over 3.40 kPa, an in line pressure regulator must be installed upstream
from the gas control valve.
4
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation:
Reduce input rate 4% for each 1000 ft. (305 m) above
2000 ft. (610 m).
E. Non-Combustible Materials Specification
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing
ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC (1382 °F) and UL763 shall be considered non-combustible materials.
F. Combustible Materials Specification
Materials made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that can ignite and burn, whether flame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
All electrical safety testing has been done following the EN
60335-2-102 standard. Local codes apply.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
5
6
2
Getting Started
A. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.
No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fire officials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system configuration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and finishing details.
• Whether optional accessories—devices such as a wall switch or remote control—are desired.
Installation and service of this appliance should be performed by qualified personnel. Hearth & Home
Technologies suggests NFI certified or factory trained professionals, or technicians supervised by an NFI certified professional (www.nficertified.org).
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified service technician, service agency or your dealer.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material
Pliers
Hammer
Non-corrosive leak check solution
Phillips screwdriver
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in. (6 mm)
magnetic)
Plumb line
Level
Safety glasses
Reciprocating saw
Manometer Flat blade screwdriver
1/2 - 3/4 in.(13-19 mm) length, #6 or #8 Self-drilling screws
Caulking material (300 ºF (149 ºC) minimum continuous exposure rating)
C. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• If packaged separately, the media, refractory, and/or optional log kits must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
•
Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent system component.
• Modification of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved by Hearth & Home Technologies.
Any such action may cause a fire hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under water. Call a qualified service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
3
Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.
M
K
J
H
I
B
G
V
U
T
P
O
N
Q
S
R
GAS ACCESS
A
C
D
E
F
ELECTRICAL ACCESS
Location
F
G
H
I
D
E
J
K
A
B
C
MEZZO-1000-AU MEZZO-1300-AU
Inches Millimeters Inches Millimeters
50 1270 62 1575
39-1/4
15-5/8
997
397
51-1/8
15-5/8
1299
397
42-1/2
4
8-9/16
62
8-9/16
1
48-3/16
17-1/8
1080
102
217
1575
217
25
1224
435
42-1/2
4
8-9/16
62
8-9/16
1
60
17-1/8
1080
102
217
1575
217
25
1524
435
N
O
P
L
M
S
T
U
V
Q
R
Location
MEZZO-1000-AU MEZZO-1300-AU
Inches Millimeters Inches Millimeters
8 203 8 203
18-5/8
41-3/4
2-3/8
8-9/16
471
1060
60
217
18-5/8
41-3/4
2-3/8
8-9/16
471
1060
60
217
24-1/2
7-1/4
8-7/8
2-3/4
23-3/4
30-3/4
622
184
225
70
603
781
24-1/2
7-1/4
8-7/8
2-3/4
23-3/4
30-3/4
622
184
225
70
603
781
Figure 3.1 Appliance Dimensions - MEZZO-1000-AU, MEZZO-1300-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
7
M
K
V
U
T
P
O
N
Q
S
R
GAS ACCESS
J
I
B
H o L
CENTERED ON APPLIANCE
A
C
D
E
F
ELECTRICAL ACCESS
G
Location
C
D
E
A
B
H
I
J
K
F
G
MEZZO-1600-AU
Inches Millimeters
74 1880
63-1/8
15-5/8
48-1/2
4
1603
397
1232
102
8-9/16
62
8-9/16
1
72
17-1/8
217
1575
217
25
1829
435
Location
P
Q
R
S
L
M
N
O
T
U
V
MEZZO-1600-AU
Inches Millimeters
8
18-5/8
203
471
47-3/4
2-3/8
1213
60
8-9/16
24-1/2
7-1/4
8-7/8
2-3/4
23-3/4
30-3/4
217
622
184
225
70
603
781
8
Figure 3.2 Appliance Dimensions - MEZZO-1600-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
M
K
V
U
T
P
O
N
Q
S
R
GAS ACCESS
J
B
I
H o
L
A
C
D
E
ELECTRICAL ACCESS
F
G
Location
C
D
E
A
B
H
I
J
K
F
G
MEZZO-1300ST-AU
Inches Millimeters
62 1575
51-1/8
15-5/8
42-1/2
4
1299
397
1080
102
8-9/16
62
8-9/16
1/2
60
17-1/8
217
1575
217
13
1524
432
Location
T
U
V
R
S
N
O
L
M
P
Q
MEZZO-1300ST-AU
Inches Millimeters
8 203
18-1/8
41-3/4
460
1060
2-3/8
8-9/16
24-1/2
7-1/4
8-7/8
2-3/4
23-3/4
30-3/4
60
217
622
184
225
70
603
781
Figure 3.3 Appliance Dimensions - MEZZO-1300ST-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
9
CLEAN FACE TRIM DECORATIVE FRONT
A
Note: See Section 10 for hearth, mantel and finishing requirements.
G
H
F
E
D
A
F
G
H
B
C
D
E
Location
MEZZO-1000-AU MEZZO-1300-AU
MEZZO-1300ST-AU
Inches Millimeters Inches Millimeters
39 991 51 1295
16-3/4
13-1/8
37-3/16
40-5/16
24
5/8
25
425
333
945
1024
610
16
635
16-3/4
13-1/8
49-3/16
52-5/16
24
5/8
25
425
333
1249
1329
610
16
635
MEZZO-1600-AU
Inches
63
16-3/4
13-1/8
61-3/16
64-5/16
24
5/8
25
Millimeters
1600
425
333
1554
1634
610
16
635
C
B
10
Figure 3.4 Clean Face Trim Front (Inside Fit) Decorative Front Dimensions
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
B. Clearances to Combustibles
When selecting a location for the appliance it is important to consider the required clearances to walls. See Figure
3.5 and Figure 3.6.
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
NOTICE: Illustrations reflect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation could vary due to individual design preference.
It is important to follow the framing and finishing instructions step by step to ensure proper placement of fireplace in the surrounding framing/finishing materials.
E
G
B
A
G
B
C
D
Refer to Section 10 for hearth, mantel and wall projection information.
If a HEAT-ZONE® will be installed, refer to
Section 5.E for information.
B
Add 712 mm for one or two HEAT-ZONES.
B
F
Model
MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1600-AU
Inches
Millimeters
Inches
Millimeters
Inches
Millimeters
A
62-1/2
1588
70-3/4
1797
79-1/2
1835
B
48-1/4
1226
60-1/4
1530
72-1/4
2013
C
88-1/8
2239
100-3/8
2550
112-3/8
2854
D
See
Section
10, Figure
10.14 and
10.15.
E
24-1/2
622
28-1/2
724
31-3/4
807
F
18-3/4
477
18-3/4
477
18-3/4
477
G
1
25
1
25
1
25
Figure 3.5 Appliance Locations: MEZZO-AU Single-Sided Models
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
11
NOTICE: This See-Through appliance is NOT designed or approved for an indoor/outdoor application.
D
C
B
D
C
A
MODEL
MEZZO-
1300ST-AU
A
Inches
Millimeters 1530
B
60-1/4 17-1/8
435
Figure 3.6 Appliance Locations: MEZZO-AU See-Through Models
C
48
1219
D
.4
10
C. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling firestops and wall shield firestops and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infiltration may be an issue, the inside surfaces may be sheetrocked and taped (or an equivalent method may be used) to achieve maximum air tightness.
12
To further prevent drafts, the wall shield and ceiling firestops should be caulked with caulk with a minimum of
300 ºF (149 ºC) continuous exposure rating to seal gaps.
Gas line holes and other openings should be caulked with caulk with a minimum of 300 ºF (149 ºC) continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
Note: Figure 3.7 and Figure 3.8, and Figure 3.9 show the fireplace installed on the floor. However, this fireplace can be elevated off the floor provided that the fireplace is properly supported by framing materials and the ceiling clearances are maintained.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
A
E=MEASUREMENT FROM TOP OF
FIREPLACE OPENING
TO CEILING
K=MEASUREMENT FROM
BOTTOM OF FIREPLACE
TO CEILING
E
F
HEADER
DEPTH**
B
C
D
APPLIANCE MAY BE INSTALLED OFF OF FLOOR***
J
G
I
H
K
MEZZO-
1000-AU
Inches
Millimeters
A
Rough
Opening
(Vent Pipe)
10
254
MEZZO-
1300-AU
Inches
Millimeters
A
Rough
Opening
(Vent Pipe)
10
254
B
Rough
Opening
(Height)
42
1067
B
Rough
Opening
(Height)
42
1067
C
Rough
Opening
(Depth)
MINIMUM FRAMING DIMENSIONS*
D
Rough
Opening
(Width)
18-1/4 48-1/4
E
Clearance to Ceiling
31
F
Combustible
Floor
0
G
Combustible
Flooring
0
464 1226 787 0 0
H
Behind
Appliance
1
25
C
Rough
Opening
(Depth)
MINIMUM FRAMING DIMENSIONS*
D
Rough
Opening
(Width)
18-1/4 60-1/4
E
Clearance to Ceiling
31
F
Combustible
Floor
0
G
Combustible
Flooring
0
464 1530 787 0 0
H
Behind
Appliance
1
25
I
Sides of
Appliance
1
25
I
Sides of
Appliance
1
25
J
Front of
Appliance
K
Clearance to Ceiling
48
1219
55-1/2
1410
J
Front of
Appliance
K
Clearance to Ceiling
48
1219
55-1/2
1410
MEZZO-
1600-AU
Inches
Millimeters
A
Rough
Opening
(Vent Pipe)
10
254
B
Rough
Opening
(Height)
48
1219
C
Rough
Opening
(Depth)
MINIMUM FRAMING DIMENSIONS*
D
Rough
Opening
(Width)
18-1/4 72-1/4
E
Clearance to Ceiling
31
F
Combustible
Floor
0
G
Combustible
Flooring
0
464 1835 787 0 0
H
Behind
Appliance
1
25
I
Sides of
Appliance
1
25
J
Front of
Appliance
K
Clearance to Ceiling
48
1219
55-1/2
1410
* = Adjust framing dimensions for interior sheathing (such as sheetrock)
**= Header depth not to exceed 3-1/2 in. (89 mm).
***= If appliance is installed off of floor, maintain required clearances to combustibles.
Construct platform in accordance with local building codes.
Figure 3.7 Clearances to Combustibles MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1600-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
13
A
HEADER
DEPTH**
HEADER
DEPTH**
F
C
D
B
APPLIANCE MAY BE
INSTALLED OFF OF FLOOR***
I
G
H
E=MEASUREMENT FROM TOP
OF FIREPLACE OPENING
TO CEILING
J=MEASUREMENT FROM
BOTTOM OF FIREPLACE
TO CEILING
E
J
MEZZO-
1300ST-AU in.
mm
A
Rough
Opening
(Vent Pipe)
10
254
MINIMUM FRAMING DIMENSIONS*
B C D E F
Rough
Opening
(Height)
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance to Ceiling
Combustible
Floor
42 17 60-1/4 31 0
1067 432 1530 787 0
G
Combustible
Flooring
H
Sides of
Appliance
0
0
1
25
I
Front or
Rear of
Appliance
48
1219
J
Clearance to Ceiling
55-1/2
1410
* = Adjust framing dimensions for interior sheathing (such as sheetrock)
**= Header depth not to exceed 3-1/2 in. (89 mm).
***= If appliance is installed off of floor, maintain required clearances to combustibles.
Construct platform in accordance with local building codes.
14
Figure 3.8 Clearances to Combustibles - MEZZO-1300ST-AU
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
D. Floor Protection
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specified air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fireplace or chimney.
• Failure to maintain airspace could cause overheating and fire.
Figure 3.9 Floor Protection
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
15
4
Termination Location and Vent Information
A. Vent Termination Minimum Clearances
WARNING
A
6 in. (minimum) up to 20 in.
152 mm/508 mm
20 in. and over
Fire Risk.
Maintain vent clearance to combustibles as specified.
• DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe could cause overheating and fire.
B
Gas, Wood or Fuel Oil
Termination Cap
B
18 in. minimum
457 mm
0 in. minimum
A *
HORIZONTAL
OVERHANG
Gas
Termination
Cap **
610 mm MIN.
510 mm MIN.
LOWEST
DISCHARGE
OPENING
TERMINATION
CAP
VERTICAL
WALL
305 mm
X
ROOF PITCH
IS X/ 305 mm
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
**
*
If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood or fuel oil terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.
Figure 4.2 Staggered Termination Caps
Angle H (Min.) mm
0°-26.6° .......................................................... 500*
26.6°-30.3° .......................................................... 500*
30.3°-33.7° .......................................................... 500*
33.7°-36.9° .......................................................... 610*
36.9°-39.8° .......................................................... 760*
39.8°-42.5° .......................................................... 990
42.5°-45.0° ........................................................1 220
45.0°-49.4° ........................................................1 520
49.4°-53.1° ........................................................1 830
53.1°-56.3° ........................................................2 130
56.3°-59.0° ........................................................2 290
59.0°-60.3° ........................................................2 440
*910 mm minimum in snow regions
Figure 4.1 Minimum Height From Roof To Lowest Discharge
Opening
16
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
B. Chimney Diagram
a
T j h c j j e e d openable window h
P
See note 3 door h n g f c
I
k
T d
M
b g k
See note 2
T = Flue terminal
I = Mechanical air inlet
M = Gas meter
P = Electricity meter or fuse box
Shading indicates prohibited areas for flue terminals a - Below eaves, balconies or other projections: MIN. CLEARANCE - in. (mm)
Appliances up to 50 MJ/h input .................................................................................... 12 (300)
Appliances over 50 MJ/h input ...............................................................................20-1/2 (500) b - From the ground or above a balcony ............................................................................... 12 (300) c - From a return wall or external corner .........................................................................20-1/2 (500) d - From a gas meter (M) ...................................................................................................... 39 (1000) e - From an electricity meter or fuse box (P) ...................................................................20-1/2 (500) f - From a drain or soil pipe .................................................................................................... 6 (150) g - Horizontally from any building structure (unless appliance approved
for closer installation) or obstruction facing a terminal ............................................... 20-1/2 (500) h - From any other flue terminal, cowl, or combustion air intake .................................... 20-1/2 (500) j - Horizontally from an openable window, door, non-mechanical air
inlet, or any other opening into a building, with the exception of
sub-floor ventilation:
Appliances up to 150 MJ/h input ............................................................................20-1/2 (500)
Appliances over 150 MJ/h input ................................................................................... 60 (1500) k - From a mechanical air inlet, including a spa blower ....................................................... 60 (1500) n - Vertically below an openable window, non-mechanical air
inlet or any other opening into a building, with the exception of ...................................... See table
sub-floor ventilation ................................................................................................................ below
T
Space Heaters
Up to 50 MJ/h input
6 in. (150 mm)
CLEARANCE
All other appliances
Up to 50 MJ/h input
20 in. (500 mm)
Over 50 MJ/h input and
Up to 150 MJ/h input
39 in. (1000 mm)
Over 50 MJ/h input
59 in. (1500 mm)
NOTES:
1. All distances are measured vertically or horizontally along the wall to a point in line with the nearest part of the terminal.
2. Prohibited area below electricity meter or fuse box extends to ground level.
3. See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.
4. See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS
OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES
Figure 4.3 Minimum Clearances for Termination
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
17
C. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies DVP venting systems. Refer to Section
12.A for vent component information and dimensions.
DO NOT mix pipe, fittings or joining methods from different manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see
Figure 4.4).
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows.
See Figure 4.4.
Figure 4.4
Vertical
12 in.
(305 mm)
8-1/2 in.
(216 mm)
Horizontal
E. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards:
• Pipe measurements are shown using the effective length of pipe. See Section 12.A for information on effective length of pipe components.
• Measurements are made from the appliance outer wrap, not from the standoffs.
• Horizontal terminations are measured to the outside mounting surface (flange of termination cap). See
Figure 4.3.
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
F. Exhaust Restrictor Instructions
Exhuast Restrictor is only used with vent runs 8 ft.
(2.4 m) of vertical pipe.
Note: The exhaust restrictor can be located in the appliance manual bag.
Exhaust restrictor: MEZZO-1000-AU
1. Locate the two pilot holes in the inside firebox chamber as shown in Figure 4.5.
2. Break the flue restrictor into two pieces. Do this by bending the part back and forth until it breaks. See
Figure 4.6.
3. The setting for MEZZO-1000-AU is 2-2. Align the holes marked “2” on the numbered exhaust restrictor piece with the holes on the other exhaust restrictor piece. See Figure 4.7. Align the exhaust restrictor pieces with the pilot holes in the inner firebox chamber. Use two 1/2 in. (13 mm) self-piercing screws to secure vent restrictor to firebox heat shield.
4. In some applications, such as those where the fireplace is elevated off the floor, the exhaust restrictor may be painted, but painting is not required.
NOTICE: Before painting, contact your dealer for
information on the appropriate high temperature paint.
18
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Exhaust restrictor: MEZZO-1300-AU, MEZZO-1600-AU,
MEZZO-1300ST-AU
Exhuast Restrictor is only used with vent runs 8 ft.
(2.4 m) of vertical pipe.
1. Break the flue restrictor into two pieces. Do this by
bending the part back and forth until it breaks. See
Figure 4.6.
Note: The MEZZO-1600-AU do not have pilot holes for
the exhaust restrictor in the firebox chamber.
2. The setting for MEZZO-1300-AU, MEZZO-1300ST-AU and MEZZO-1600-AU is 1-1. Align the holes marked
“1” on the numbered exhaust restrictor piece with the hole on the other exhaust restrictor piece. See Figure 4.8. Center the exhaust restrictor on the vent and secure in place with two 1/2 in. (13 mm) self-piercing screws.
3. In some applications, such as those where the fireplace is elevated off the floor, the exhaust restrictor may be painted, but painting is not required.
NOTICE: Before painting, contact your dealer for
information on the appropriate high temperature paint.
PILOT
HOLES
1 2 3 4 5
1 2 3 4 5
SETTING
1 2 3 4 5
Figure 4.7 Setting the Exhaust Restrictor for MEZZO-1000-AU
SETTING
EXHAUST
RESTRICTOR
1 2 3 4 5
Figure 4.8 Setting the Exhaust Restrictor for MEZZO-1300-AU,
MEZZO-1300ST-AU, MEZZO-1600-AU
Figure 4.5 Exhaust Restrictor
BREAK
HERE
G. Vent Diagrams
General Rules:
• When penetrating a combustible wall, a wall shield firestop must be installed.
• When penetrating a combustible ceiling, a ceiling firestop must be installed.
• Horizontal runs of vent do not require vertical rise; horizontal runs may be level.
• Horizontal termination cap should have a 1/4 in. (6mm) downward slant to allow any moisture in cap to be released.
Figure 4.6 Break the Exhaust Restrictor
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
19
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
• ALWAYS maintain specified clearances around venting and firestop systems.
• Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe could cause fire.
Top Vent - Horizontal Termination Venting with 1 elbow
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1600-AU
V
1
Minimum
2 ft.
610 mm
H
1
1.5 ft.
Maximum
457 mm
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ H
1
H
1
= 63 ft. (19.2 m) Maximum
= 40 ft. (12.2 m) Maximum
Note: Use DVP Series components only.
MEZZO-1300ST-AU
V
1
Minimum
2 ft.
610 mm
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
H
1
Maximum
3 ft.
914 mm
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
H
1
= 40 ft. (12.2 m) Maximum
H
1
V
1
Figure 4.9
20
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Top Vent - Horizontal Termination
Venting with 2 elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1600-AU
V
1
Minimum
2 ft.
610 mm
H
1
1.5 ft.
+ H
2
Maximum
457 mm
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ H
1
H
1
+ H
+ H
2
= 63 ft. (19.2 m) Maximum
2
= 40 ft. (12.2 m) Maximum
Note: Use DVP Series components only.
MEZZO-1300ST-AU
V
1
Minimum
2 ft.
610 mm
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
H
1
+ H
2
Maximum
3 ft.
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
914 mm
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ H
1
H
1
+ H
+H
2
= 63 ft. (19.2 m) Maximum
2
= 40 ft. (12.2 m) Maximum
H
2
INSTALLED
HORIZONTALLY
H
1
V
1
Figure 4.10
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
21
Top Vent - Horizontal Termination
Venting with 3 Elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1600-AU
V
1
+ V
2
Minimum
2 ft.
610 mm
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
H
1 +
H
2
Maximum
1.5 ft.
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
457 mm
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ V
2
+ H
H
1
+ H
2
1
+ H
2
= 63 ft. (19.2 m) Maximum
= 40 ft. (12.2 m) Maximum
Note: Use DVP Series components only.
MEZZO-1300ST-AU
V
1
+ V
2
Minimum
2 ft.
610 mm
3 ft.
4 ft.
5 ft.
6 ft.
7 ft.
8 ft.
914 mm
1.2 m
1.5 m
1.8 m
2.1 m
2.4 m
H
1 +
H
2
Maximum
3 ft.
6 ft.
9 ft.
12 ft.
15 ft.
18 ft.
21 ft.
914 mm
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m
V
1
+ V
2
H
1
+ H
1
+ H
2
+ H
2
= 63 ft. (19.2 m) Maximum
= 40 ft. (12.2 m) Maximum
H
2
V
2
H
1
V
1
Figure 4.11
22
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Top Vent - Vertical Termination
No Elbows
V = 3 ft Min. (1m), 50 ft. Max. (15.2 m)
Note: If installing a vertical vent/termination off the top of the appliance, the optional exhaust restrictor may be needed.
Note: Use DVP Series components only.
V
Figure 4.12 Vertical Vent Maximum
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
23
Top Vent - Vertical Termination
Venting with 2 elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
M E Z Z O - 1 0 0 0 - A U , M E Z Z O - 1 3 0 0 - A U ,
MEZZO-1300ST-AU, MEZZO-1600-AU
V
1
+ V
2
2 ft.
Minimum
610 mm
H Maximum
1.2 m
3 ft.
4 ft.
5 ft.
914 mm
1.2 m
1.5 m
4 ft.
9 ft.
12 ft.
15 ft.
2.7 m
3.6 m
4.5 m
V
1
+ H
1
H
Total
+ V
2
= 63 ft. (19.2 m) Maximum
= 23 ft. (7.1 m) Maximum
Note: Use DVP Series components only.
V
2
H
1
V
1
Figure 4.13
24
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Top Vent - Vertical Termination
Venting with 3 elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
MEZZO-1000-AU, MEZZO-1300-AU,
MEZZO-1300ST-AU, MEZZO-1600-AU
V
1
+ V
2
Minimum
2 ft.
3 ft.
610 mm
914 mm
H
1
+ H
2
Maximum
4 ft.
1.2 m
9 ft.
2.7 m
4 ft.
5 ft.
1.2 m
1.5 m
12 ft.
15 ft.
3.6 m
4.5 m
V
1
+ V
2
+ H
1
H
1
+ H
2
+ H
2
= 63 ft. (19.2 m) Maximum
= 23 ft. (7.1 m) Maximum
Note: Use DVP Series components only.
V
2
H
2
INSTALLED
HORIZONTALLY
H
1
V
1
Figure 4.14
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
25
5
Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:
• Between ceiling firestops
• Between wall shield firestops
• Around vent system
Failure to keep insulation or other material away from vent pipe could cause overheating and fire.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
• DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in.
(102 mm to 184 mm) thick.
• If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
(DVP Pipe Shown)
3 in. (76 mm) top clearance
Heat
Shield
3 in. (76 mm) top clearance *
Heat
Shield
1 in. (25 mm) clearance around vertical sections
Wall
Shield
Firestop
1 in. (25 mm) clearance bottom & sides
WALL
Figure 5.1 Horizontal Venting Clearances To Combustible
Materials
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall shield firestop(s). The wall shield firestop maintains minimum clearances and prevents cold air infiltration.
• The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.
• DVP pipe - A wall shield firestop must be placed on each side of an interior wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be maintained.
• See Section 7.F. for information for regarding the installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combustible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
Note: Do not pack the gap with insulation.
Whenever a non-combustible wall is penetrated, the wall shield firestop is only required on one side and no heat shield is necessary.
DO NOT PACK WITH
INSULATION OR
OTHER MATERIAL
12 in.
10 in.
B
A
MODEL
MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1300ST-AU
MEZZO-1600-AU
A*
63 in.
1.60 m
B
62 in.
1.57 m
* Shows center of vent framing hole for top venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.
26
Figure 5.2 Wall Penetration
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
C. Install the Ceiling Firestop
A ceiling firestop MUST be used between floors and attics.
• DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/floor. See
Figure 5.3.
• Frame the area with the same sized lumber as used in ceiling/floor joist.
• The ceiling firestop may be installed above or below the ceiling joists when installed with an attic insulation shield. It must be under joists between floors that are not insulated. Refer to Figure 5.4.
• Secure with two fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept back from the pipe to prevent overheating.
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth
& Home Technologies requires the use of an attic shield.
The International Fuel Gas Code requires an attic shield constructed of 26 gauge minimum steel that extends at least 2 in. (51 mm) above insulation.
• Attic insulation shields must meet specified clearances to combustible materials and be secured in place.
• An attic insulation shield kit is available from
Hearth & Home Technologies. Contact your dealer to order. Install attic insulation shield according to instructions included with kit.
Figure 5.3 Installing Ceiling Firestop
ATTIC ABOVE
A
A
PIPE
DVP
A
10 in. (254 mm)
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
Figure 5.4 Installing the Attic Shield
CEILING FIRESTOP
INSTALLED ABOVE CEILING
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
27
E. Installing the Heat-Zone
®
Kit
• Locate the Heat-Zone
®
ports on the left and right sides of the appliance. See Figure 5.5. Remove the knockouts from the appliance with a tin snips.
• Place the Heat-Zone
®
adapter box into position prior to the final positioning of the fireplace as shown in Figure
5.5. Secure using eight self-tapping screws. Ensure the
Heat-Zone
®
knockouts are completely covered by the adapter box.
• Center the duct collar around the exposed hole and attach it to the appliance with 3 screws.
Note: The adapter box will protrude out further than the one inch (25 mm) standoffs on the appliance.
• Determine the location for the air register/fan housing assembly.
Reference the Heat-Zone
®
Kit instructions for the remaining installation steps and pages 39-40.
• Jumper wire provided with Heat-Zone
®
Kit, accessory still requires wire from appliance to Heat-Zone
®
Kit.
• One or two Heat-Zone
®
Kit(s) may be ran off the AUX1 port. If independent fan control is desired, one Heat-
Zone
®
Kit may be ran through AUX1 and the other through FAN port in AUX300CE as shown in Figure 8.4.
HEAT ZONE ® LOCATION
LEFT AND RIGHT SIDES
HEAT ZONE
®
ADAPTER BOX
Figure 5.5 Heat Zone Adapter
NOTE: If the fan housing is installed in a 2 x 4 wall, the front of the housing will protrude approximately 13 mm out of the wall.
FAN HOUSING
REGISTER
1/2 in.
(13 mm)
28
Figure 5.6
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
6
Appliance Preparation
A. Vent Collar Preparation
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
1. Position the pipe heat shield up against the header and attach to header with two screws.
WARNING! Risk of Fire! Pipe heat shield must be fastened to header.
2. Place a 24 in. (610 mm) vent section on the starting collar.
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• The MEZZO-1000-AU, MEZZO-1300-AU MEZZO-
1300ST-AU and MEZZO-1600-AU require a minimum of 24 in. (610 mm) of vertical venting before attaching any elbow to the appliance.
3. Place the 1/8 in. (3 mm) thick, square fiberglass gasket over the initial 24 in. (610 mm) vent section.
4. Place the fiberglass rope ring over the gasket. Ensure both the gasket and the rope ring are seated on the top of the appliance.
PIPE HEAT SHIELD
FIBERGLASS ROPE RING
BOTTOM PANEL SCREW LOCATIONS
Figure 6.1 Location of Fiberglass Rope Ring
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
29
B. Securing and Leveling the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials
Block openings into the chase to prevent entry of blownin insulation. Make sure insulation and other materials are secured.
DO NOT notch the framing around the appliance standoffs. Failure to maintain air space clearance could cause overheating and fire.
To properly position, level, and secure the appliance, see below. Nailing tabs are provided to secure the appliance to the framing members.
• Bend out the two nailing tabs on each side.
• Place the appliance into position.
• Keep nailing tabs flush with the framing. See Figure 6.2.
• Level the appliance from side to side and front to back.
• Shim the appliance as necessary. It is acceptable to use wood shims underneath the appliance.
• Secure the appliance to the framing by using nails or screws through the nailing tabs.
Some figures in manual show the fireplace installed on the floor. However, this fireplace can be elevated off the floor provided that the fireplace is properly supported by framing materials and the ceiling clearances are maintained.
Setting the Fireplace into the Framing
The left and right nailing tabs were designed as a means to ensure the fireplace is mounted flush with the framing materials. See Figures 6.2-6.4
1. The shipping flanges protrude further out from the appliance than the side standoffs. The shipping flange may be bent upward or broken off in order to place the appliance into position in the framing.
2. Bend out all nailing tabs. The see-through model will have eight nailing tabs. The single-sided model will have four nailing tabs.
3. Screw each nailing tab to the adjoining framing material. Ensure that the one inch air space clearance is maintained on the sides and back of the fireplace.
See Figures 3.5-3.8 for framing and clearance details.
1 IN. STANDOFF
NAILING
TAB
NAILING
TAB
SHIPPING
FLANGE
Figure 6.3 Nailing Tabs
Shipping Position
SHIPPING
FLANGE
Figure 6.4 Nailing Tabs
Installation Position
NAILING TABS
BOTH SIDES
Figure 6.2 Nailing Tab Locations
30
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
C. Installing Non-Combustible Facing Material
WARNING! Risk of Fire!
• Follow these instructions exactly.
• Facing materials must be installed properly to prevent fire.
• No materials may be substituted without authorization by Hearth & Home Technologies.
• Remove protective cardboard sleeve from noncombustible facing pieces, which are included with the appliance.
• Install non-combustible facing material to the appliance using the 2 in. (51 mm) screws supplied in the manual bag assembly. There may be extra screws included.
• Attach top board to the framing members with regular sheetrock screws or nails. See Figure 6.5.
• Attach left and right side pieces to framing members with regular sheetrock screws or nails.
• Use a wet or dry towel or soft brush to remove dust or dirt from facing material.
• See Section 10 for finishing materials guidelines.
Figure 6.5 Install Factory-Included Non-Combustible Facing
Material
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
31
7
Venting and Chimneys
A. Assemble Vent Sections
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face toward the appliance.
Attach the first pipe section to the starting collar:
• Lanced pipe end of the starting collar.
• Inner pipe over inner collar.
• Push the pipe section until all lanced tabs snap in place.
• Lightly tug on pipe to confirm it has locked.
Required Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
All outer pipe joints must be sealed with 100% silicone
(300 ºF (149 ºC) minimum continuous exposure rating), including the slip section that connects directly to the horizontal termination cap.
• Apply a bead of silicone sealant (300º F (149 ºC) minimum continuous exposure rating) inside the female outer pipe joint prior to joining sections. See Figure 7.1.
• Only outer pipes need to be sealed. All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in this manner, unless otherwise stated.
Figure 7.1 High Temperature Silicone Sealant
A
Lances
B
WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent could leak.
Figure 7.2
Figure 7.3
Note:
Make sure that the seams are not aligned to prevent unintentional disconnection.
Assemble Pipe Sections
Per Figure 7.2:
• Start the inner pipe on the lanced end of section A into the flared end of section B.
• Start the outer pipe of section A over the outer pipe of section B.
• Once both vents sections are started, push firmly until all lanced tabs lock into place.
• Lightly tug on the pipe to confirm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer pipe sections together. If predrilling holes,
DO NOT penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction from horizontal to vertical, one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2 in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.
32
Figure 7.4 Seams
CORRECT
INCORRECT
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
B. Assemble Slip Sections
• Slide the inner flue of the slip section into the inner flue of the pipe section and the outer flue of the slip section over the outer flue of the pipe section. See Figure 7.5.
• Slide together to the desired length.
Pilot hole
Figure 7.5 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe section.
• Secure the pipe and slip section with two screws no longer than 1/2 in. (13 mm), using the pilot holes in the slip section. See Figure 7.6.
C. Secure The Vent Sections
• Vertical runs originating off the top of the appliance, with no offsets, must be supported every 8 ft. (2.44 m) after the maximum allowed 25 ft. (7.62 m) of unsupported rise.
• Vertical runs, after any elbow, must be supported every
5 ft. (1.52 m).
• Horizontal runs must be supported every 5 ft. (1.52 m).
• Vent supports or plumbers strap (spaced 120º apart) may be used to support. See figures 7.7 and 7.8.
• Wall shield firestops may be used to provide horizontal support.
• Ceiling firestops have tabs that may be used to provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support could allow vent to sag and separate.
Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below connection point to appliance.
120º
Figure 7.7 Securing Vertical Pipe Sections
Figure 7.6 Screws into Slip Section
• Continue adding pipe as necessary following instructions in “Assembling Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer flues of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC termination cap, all pipe system joints shall be sealed using a silicone sealant with a minimum of 300 ºF (149
ºC) continuous exposure rating.
• Apply a bead of silicone sealant inside the female outer pipe joint prior to joining sections.
• Only outer pipes are sealed, sealing the inner flue is not required.
• All unit collar, pipe, slip section, elbow and cap outer flues shall be sealed.
120º
Figure 7.8 Securing Horizontal Pipe Sections
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
33
D. Disassemble Vent Sections
• Rotate either section (see Figure 7.9) so the seams on both pipe sections are aligned as shown in Figure 7.10
• Pull carefully to separate the pieces of pipe.
Figure 7.9 Rotate Seams for Disassembly
Figure 7.10 Align and Disassemble Vent Sections
34
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
E. Vertical Termination Requirements
Install Metal Roof Flashing
• See minimum vent heights for various pitched roofs
(Figure 7.11) to determine the length of pipe to extend through the roof.
• Slide the roof flashing over the pipe sections extending through the roof as shown in Figure 7.12.
HORIZONTAL
OVERHANG
610 mm MIN.
510 mm MIN.
LOWEST
DISCHARGE
OPENING
TERMINATION
CAP
VERTICAL
WALL
305 mm
X
ROOF PITCH
IS X/ 305 mm
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
CAULK
Figure 7.12
Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
• Slide the storm collar onto the exposed pipe section and align brackets.
• Insert a bolt (provided) through the brackets and install nut. Do not completely tighten. See Figure 7.13.
Angle H (Min.) mm
0°-26.6° .......................................................... 500*
26.6°-30.3° .......................................................... 500*
30.3°-33.7° .......................................................... 500*
33.7°-36.9° .......................................................... 610*
36.9°-39.8° .......................................................... 760*
39.8°-42.5° .......................................................... 990
42.5°-45.0° ........................................................1 220
45.0°-49.4° ........................................................1 520
49.4°-53.1° ........................................................1 830
53.1°-56.3° ........................................................2 130
56.3°-59.0° ........................................................2 290
59.0°-60.3° ........................................................2 440
*910 mm minimum in snow regions
Figure 7.11 Minimum Height From Roof To Lowest Discharge
Opening
NOTICE: Failure to properly caulk the roof flashing and pipe seams could permit entry of water.
• Caulk the gap between the roof flashing and the outside diameter of the pipe.
• Caulk the perimeter of the flashing where it contacts the roof surface. See Figure 7.12.
• Caulk the overlap seam of any exposed pipe sections that are located above the roof line.
Figure 7.13 Install Bolt into Brackets
• Slide the assembled storm collar down the pipe section until it rests on the roof flashing (see Figure 7.14).
• Tighten nut and make sure the collar is tight against the pipe section.
• Caulk around the top of the storm collar. See Figure 7.14.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
35
Install Vertical Termination Cap
• Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.
• Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe. See Figure 7.14.
Termination Cap
Caulk
Figure 7.14
Storm
Collar
F. Horizontal Termination Requirements
Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thickness.
• DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap
(shown in Figure 7.15).
• Heat shields must overlap 1-1/2 in. (38 mm) minimum.
There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 7.15.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended heat shield must be used.
• If the wall thickness is less than 4 in. (102 mm), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.
• Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.
• Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.
• Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.
Important Notice: Heat shields may not be field constructed.
36
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of flue telescoping section is required.
Failure to maintain overlap could cause overheating and fire.
• Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at outside edges of cap.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a flashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall.
WALL SHIELD
FIRESTOP
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
OUTER VENT
INNER VENT
SLIP SECTION
CAN BE EXTENDED
INTERIOR
Figure 7.15 Venting Through the Wall
SHEATHING
EXTERIOR
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
37
8
Electrical Information
A. General Information
WARNING! Risk of Shock or Explosion! DO NOT wire
220/240 VAC to the valve or to the appliance wall switch.
Incorrect wiring will damage controls.
• Wire the appliance junction cord to unswitched 220/240
VAC. This is required for proper operation of the appliance.
• A 220/240 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
• Low voltage and 220/240 VAC voltage cannot be shared within the same wall box.
Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
VANITY
LOWER
PANEL
ACCESS P
ANEL
BOTTOM PANEL SCREW LOCATIONS
Figure 8.1 Lower Access Panel Location
WARNING! Risk of Shock! Replace damaged wire with type 105 ºC rated wire. Wire must have high temperature insulation.
Accessories Requirements
• This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home Technologies approved accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
Junction Cord Installation
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105 °C rated wire. Wire must have high temperature insulation.
3. Make the connection inside the junction cord to the
220/240V wire. Connect green to the ground nut, black to black, and white to white.
4. To reattach the junction cord, insert one end of the junction cord in the slot provided and securely screw the other end of the junction cord to the control tray panel.
5. Reinstall component heat shield.
CAUTION! Risk of Overheating! Component heat shield
MUST be installed before operating appliance. Electrical components will be damaged.
JUNCTION CORD
Figure 8.2 Junction Cord Detail
In the event that the junction cord may need to be accessed or installed after finish methods have been applied, access is possible by removing the vanity panel.
1. Remove bottom metal panel by removing two screws.
Screw locations are shown in Figure 8.1. After removing two screws, gently lift the panel off the appliance avoiding contact with the non-combustible board if possible.
2. Remove screws on left and right sides of component heat shield and lift it out of the control cavity.
38
CONTROL MODULE
AUX
JUNCTION CORD
LED POWER SUPPLY
Figure 8.3. Valve Cavity (Lower Access Panel Removed)
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
B. Wiring Requirements
IntelliFire™ Plus Ignition System Wiring
• Wire the appliance junction cord to 220/240 VAC for proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction cord to a switched circuit. Incorrect wiring will override IPI safety lockout.
• Refer to Figure 8.4, IPI Wiring Diagram.
• This appliance is equipped with an IntelliFire™ Plus control valve which operates on a 6 volt/1.5 AMP system.
• Plug the 6 volt transformer plug into the appliance junction cord to supply power to the unit OR install 4 AA cell batteries (not included) into the battery pack before use.
NOTICE: Batteries should only be used as a power source in the event of an emergency power outage. Batteries should not be used as a primary long-term power source.
Battery polarity must be correct when installing batteries.
When using batteries as a power source, the 6-volt transformer must be unplugged from the receptacle.
Do not store batteries in the battery pack when the appliance is powered by the 6 volt transformer connected to permanent electrical service.
Accessories Requirements
• This appliance ships standard with a remote control.
Wiring for optional Hearth & Home Technologies approved accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
The junction cord, control module, LED power supply and wall switch receiver can be accessed by removing the vanity panel and component heat shield. The decorative front must be removed to access these components. See
Figure 8.2.
CAUTION! Risk of Overheating! Component heat shield
MUST be installed before operating appliance. Electrical components will be damaged.
RC300 4.5V DC
(AAA X 3)
TO JUNCTION
CORD (220/240V)
FLAME
MODULATION
MODULE
I
S
FLAME
SENSE
IGNITER
Heat-Zone
®
AUX300 MODULE
FAN
AUX 1 AUX 2
Heat-Zone ®
CORD ADAPTER
ORANGE
(PILOT)
GREEN
(MAIN)
RED
BLACK
BROWN
GROUND
LED CONTROL
TO JUNCTION CORD
(220/240V)
BATTERY PACK
6V DC
LED LIGHT TRAY
Figure 8.4 IntelliFire™ Plus Wiring Diagram with Remote
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
39
FAN
Figure 8.5
BROWN
JUNCTION BOX AND
CONNECTION WIRE SUPPLIED
BY INSTALLATION
PROFESSIONAL
FAN
JUNCTION BOX
BLACK
WHITE
GREEN
BLUE
GROUND
2166-191 JUMPER
AUX1 AUX2
APPLIANCE
JUNCTION CORD
40
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
9
Gas Information
A. Fuel Conversion
• Make sure the appliance is compatible with available gas types.
• Conversions must be made by a qualified service technician using Hearth & Home Technologies specified and approved parts.
B. Gas Pressure
• Optimum appliance performance requires proper input pressures.
• Pressure requirements are:
Gas Pressure
Minimum inlet pressure
Maximum inlet pressure
Manifold pressure
Natural Gas
1.13 kPa
3.40 kPa
.87 kPa
ULPG
2.75 kPa
3.40 kPa
2.40 kPa
C. Gas Service Access
Note: This appliance does include a manual gas shutoff valve that is located in the valve compartment. This manual gas shutoff valve is accessible for service by removing the decorative front and the vanity panel. The valve is most accessible if it is located forward in the control cavity of the appliance.
Depending upon local code, an additional manual gas shutoff, in a readily accessible area may be required and located upstream from the appliance.
The lower access cover panel is removable if finishing material is not installed. See Figure 9.2.
WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low pressure could cause explosion.
• Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is greater than 1/2 psig.
• Valve pressure taps are accessible by removing the decorative front and the vanity panel.
VANITY
LOWER
PANEL
ACCESS P
ANEL
VALVE PRESSURE TAPS
BOTTOM PANEL SCREW LOCATIONS
Figure 9.2. Vanity Panel and Lower Access Panel Location
If the finishing materials have been installed around the appliance opening, proceed as follows:
1. Remove vanity panel.
2. Remove screws on left and right sides of component heat shield and lift it out of the control cavity.
CAUTION! Risk of Overheating! Component heat shield
MUST be installed before operating appliance. Electrical components will be damaged.
3. Unplug the 6V transformer from the junction cord.
This will turn the power off to the appliance.
Figure 9.1. Valve Pressure Taps.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.
• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
41
4. Turn the gas shutoff handle to the “OFF” position to shut off the gas supply.
If additional access is needed, proceed as follows:
5. Remove glass assembly from appliance by unlatching the top spring latches from the glass frame and lifting glass frame assembly out of the bottom bracket.
6. Remove interior media and refractory from the unit if already installed.
7. Remove the media tray. It is attached to the interior firebox bottom with ten screws. See Figure 9.3.
8. Remove the two screws that attach the pilot to the burner.
9. Remove the four screws securing the burner to the firebox sides and disengage burner from orifice. Remove burner. See Figure 9.3.
10. Remove the eight screws that secure the glass window.
Remove the glass window. Handle with care. See
Figure 9.4.
11.
Remove light tray from appliance by lifting up and out through the bottom glass opening.
ROCK MEDIA PLACEMENT JIG
PILOT SHIELD
BURNER RAILS (2)
Figure 9.4. Gas and Electrical Access - Remove Glass Window
GAS VALVE
GAS ACCESS
Figure 9.5. Gas Fitting Access with Vanity Panel Removed
BURNER
(MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1300ST-AU
MODELS)
MEDIA TRAY
BURNER
(MEZZO-1600-AU MODELS)
Figure 9.3. Media Tray with Burner and Pilot Shield
42
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
D. Gas Connection
• Refer to Reference Section 3.A for location of gas line access in appliance.
• Gas line may be run through the left side of appliance.
• The gap between supply piping and gas access hole may be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with noncombustible, unfaced insulation to prevent cold air infiltration.
• Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up during line purge could ignite.
• Purge should be performed by qualified service technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or open flames.
Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loosened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.
E. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 ft. (610 m) elevation:
Reduce input rate 4% for each 1000 ft. (305 m) above
2000 ft. (610 m).
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
43
F. Air Shutter Setting
Air shutter settings may be adjusted by a qualified installer at the time of installation. The air shutter is set at the factory for minimum vertical vent run. Adjust air shutter for longer vertical runs. See Figure 9.6.
• Refer to Gas Service Access instructions in Section 9.C to access the air shutter.
• Loosen the 1/4 in. (6 mm) screw.
• Twist shutter to adjust.
• Shutter may be open for longer horizontal vent runs.
• Do not close the air shutter more than 1/16 in. (2 mm) for NG or 1/4 in. (6 mm) for ULPG
• Tighten the screw.
NOTICE: If sooting occurs, provide more air by opening the air shutter.
Air Shutter Settings
MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1300ST-AU
GLASS REFRACTORY
KIT
LOG KIT
NG
Standard
Opening=
3/16 in. (5 mm)
1/4 in. (6 mm)
ULPG
Standard
Opening=
Full Open
Full Open
MEZZO-1600-AU
GLASS REFRACTORY
KIT
LOG KIT
NG
Standard
Opening=
3/8 in. (10 mm)
3/8 in. (10 mm)
ULPG
Standard
Opening=
Full Open
Full Open
DETAIL
Figure 9.6 Air Shutter Location
44
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
10
Finishing
A. Facing and Finishing Instructions
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified. Framing closer than the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.).
Splatter Guard
The splatter guard is a piece of corrugated material used to protect the appliance during the installation process before finishing work on the whole hearth is complete. A splatter guard is factory-installed on
MEZZO-AU models. Splatter guards must be removed before appliance is fired.
WARNING! Risk of Fire! Remove the splatter guard before lighting the appliance. Shut off gas to the appliance when the splatter guard is in place to prevent accidental operation.
Finishing Instructions
It is important to follow the framing and finishing instructions to ensure proper placement of fireplace into the surrounding framing / finishing materials.
Wall sheathing materials 10 mm thick are specified in this installation manual to properly align with the factory-installed non-combustible material.
WARNING! Risk of Fire! DO NOT remove the installed non-combustible board or cover it with combustible material, such as:
• Drywall (gypsum board)
• Plywood
• Materials that do not meet the ASTM E 136 Non-combustibility standard (below).
Removal of installed, non-combustible board and/or use of materials not meeting the ASTM E 136 standard could cause fire.
Non-Combustible Materials Specification
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing
ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC.
WARNING! Risk of Fire! Maintain specified air space clearances to combustibles. Inadequate air space could cause overheating and fire.
Finishing Materials
NOTICE: The maximum finishing material not only includes the decorative finish materials (marble, tile, slate, etc) but also the thin set, lath and adhesive used to attach the decorative finish material.
WARNING! Risk of Fire! DO NOT use screws longer than two inches when attaching finishing materials to installed non-combustible material. Screws longer than two inches will compromise clearance and could cause overheating and fire.
WARNING! Risk of Fire, Explosion or Asphyxiation!
DO NOT use screws more than one inch long on lower cover panel. Longer screws may penetrate gas line or damage valve or electrical components.
This section discusses installation details associated with the Inside and Overlap Fit methods and specifies additional non-combustible materials required.
When finishing the wall around the fireplace, it is critical that wall sheathing be fastened properly. Wall sheathing fasteners, such as screws or nails, are not permitted in some locations. See Figure 10.1.
It is acceptable to pre-drill holes and use self-tapped screws in the installed non-combustible board which may be used to lathe (a backer for tile, marble, etc.). Screws being installed through the installed non-combustible board should be self-tapping type with a maximum length of 2 in. (51 mm) See Figure 10.1.
When installing finish material on the lower cover panel,
DO NOT drill or install screws longer than one inch.
Screws longer than one inch could penetrate the lower cover panel causing damage to components or penetrate the gas line. One inch screws are included in the manual bag assembly that are intended for use when attaching finishing material to lower cover panel. See Figure 10.1.
To Reduce the Risk of Sheetrock Cracking:
DO
Use all purpose joint compound.
Use eggshell paint
(gloss or semi-gloss).
Tape over trim strips.
To Avoid Sheetrock Cracking:
DO NOT
Use a quick set or light weight joint compound.
Use flat paint.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
45
WARNING! Risk of Fire, Explosion or Asphyxiation!
DO NOT use screws more than one inch long on lower cover panel. Longer screws may penetrate gas line or damage valve or electrical components.
MAXIMUM SCREW LENGTH = 2 in. (51 mm)
(INSTALLED NON-COMBUSTIBLE BOARD)
NON-COMBUSTIBLE MATERIAL
ONLY IN THIS AREA
2 in.
51 mm
MAXIMUM SCREW LENGTH = 1 in. (25 mm)
(LOWER COVER PANEL)
= NO FASTENERS IN THIS AREA
Figure 10.1 Screw Length Requirements
The appliance is designed to mate with 10 mm wall sheathing materials such as drywall, plywood, wood composites, or non-combustible materials.
Note: It is acceptable to use a high temperature silicone sealant to adhere drywall to lower cover panel.
Finish and Sealing Joints
All joints between the finished wall sheathing and the appliance must be sealed with non-combustible materials.
Sealants, such as caulk or mastic used to seal the gap between the wall and the fireplace, should be rated at a minimum continuous exposure to 300 ºF (149 ºC).
Finishing Around Opening with Gypsum Wallboard
Gypsum wallboard (drywall) joints adjacent to the fireplace opening, including the non-combustible board on the appliance, require special attention to minimize cracking. When installing gypsum wallboard around the fireplace, install the hole for the fireplace opening in a single wallboard sheet, if possible. This will minimize the joints adjacent to the fireplace opening.
Tape wall board joints around the fireplace opening with fiberglass-mesh tape. It will provide a more crack-resistant joint than paper tape. Fill, smooth and finish wall joints with chemically setting-type joint compound. It will provide a more crack-resistant joint than air-drying lightweight compound.
Painting
If desired finishing includes a painted wall, 100% acrylic latex with compatible primer is recommended around this appliance. Oil-based or standard acrylic paints may discolor due to heat exposure.
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite and will interfere with proper operation of doors and louvers.
WARNING! Risk of Fire! DO NOT install drywall or other combustible materials directly onto the installed non-combustible board. Overlapping materials could ignite.
Facing Material
• Facing and/or finishing materials must not interfere with air flow through louvers or decorative fronts.
• Facing and/or finishing materials must never overhang into the glass opening.
• Observe all clearances when applying combustible materials.
Finishing - Hearth
See Inside Fit or Overlap Method sections to determine the necessary requirements for installation of a noncombustible hearth for this model. Only hearths made of non-combustible materials are allowed.
10 mm THICK
WALL SHEATHING
BOTTOM
FINISHING
TEMPLATE
Figure 10.2 Finishing and Facing Materials - Single-sided Models
46
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
NON-COMBUSTIBLE
FINISHING MATERIAL
INSIDE FIT = 0-1 in. ( 0-25 mm) THICK
10 mm THICK
WALL SHEATHING
1/2 in. (13 mm)
FACTORY-INSTALLED
NON-COMBUSTIBLE
BOARD
NON-COMBUSTIBLE
FINISHING MATERIAL
INSIDE FIT = 0-1 in. ( 0-25 mm)THICK
TEMPLATE BRACKET
TEMPLATE BRACKET
Figure 10.3 Finishing Materials - See-Through Models
Decorative facing material thickness is measured from the face of the factory-installed non-combustible board.
See Figure 10.2 and Figure 10.3.
The front for this appliance are compatible with non-combustible materials. See Figure 10.2 and Figure 10.3.
Refer to Section 1.E and 1.F of this manual for definitions and qualifications of non-combustible and combustible materials.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
47
Inside Fit Finishing
Non-Combustible Finish Materials
Clean Face Trim (CFT) Front Only
0 in. (0 mm) to 1 in. (25 mm) Thick Inside Fit Method
Note: When a Clean Face Trim (CFT) decorative front is installed, the rectangular holes in bottom access panel will be covered.
NOTICE: This 1 in. (25 mm) maximum not only includes the decorative finish materials (marble, tile, slate, etc) but also the thin set, lath and adhesive used to attach the
decorative finish material.
The Clean Face Trim decorative front is approved for inside fit applications. When using non-combustible finishing materials 0 - 1 in. (0 - 25 mm) thick, follow the instructions below. Refer to Section 1.E and 1.F of this manual for definition and qualifications and definition of non-combustible and combustible materials.
1. Remove finishing template from bottom access panel.
2. Install finishing material to the top ledge of the bottom access panel, covering the eight rectangle holes in the access panel. See Figure 10.1 for screw length requirements.
3. Install trim ring onto the wall. The trim ring acts as a finishing template in this application. Finishing materials may not extend past the outside edge of the trim ring.
4. Follow instructions provided with decorative front for installation.
WARNING! Risk of Fire!
• If a Clean Face Trim (CFT) front has been installed and
is to be replaced by a front with an overlap fit, the finish-
ing material must be removed to reveal the eight rectan-
gular holes on the bottom access panel.
• Over heating and fire could occur.
Non-Combustible Finish Materials
Clean Face Trim (CFT) Front Only
0 in. (0 mm) to 1 in. (25 mm) Thick Inside Fit Method
Finishing material greater than 1 in. (25 mm) thick is only approved for non-combustible materials with a Clean
Face Trim (CFT) front only. Refer to Section 1.E and 1.F of this manual for definition and qualifications and definition of non-combustible and combustible materials.
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite.
1. Remove finishing template from bottom access panel.
2. Install trim ring onto the wall. The trim ring acts as a finishing template in this application. Finishing materials may not extend past the outside edge of the trim ring.
NOTICE: If finishing extends past the inside opening of the outer trim ring, the decorative front will not fit.
3. Install non-combustible finishing material up to the outer edges of the trim ring. See Figure 10.1 for screw length requirements.
4. Follow instructions provided with decorative front for installation.
WARNING! Risk of Fire!
• If a Clean Face Trim (CFT) front has been installed and
is to be replaced by a front with an overlap fit, the finish-
ing material must be removed to reveal the eight rectan-
gular holes on the bottom access panel.
• Over heating and fire could occur.
TRIM RING INSTALLED
Figure 10.4 Non-Combustible Finish Material Diagram for
1 - 4 in. (25 - 102 mm) Thick Inside Fit Method
48
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
Finishing - Non-Combustible Hearth CFT Fronts-Inside Fit
A non-combustible hearth may be installed in front of the appliance only if the inside fit finishing method with CFT doors is used.
1. Install trim ring.
2. Non-combustible hearth material may be placed up to the bottom edge of the trim ring. The hearth may be a maximum of 12 in. (305 mm) in depth.
TRIM RING
CFT FRONTS ONLY
NON-COMBUSTIBLE HEARTH
12 in.
(305 mm)
MAX
Figure 10.5 Finishing and Facing Materials - Inside Fit
15-3/4 in.
(400 mm)
51-1/8 in. (1299 mm) MEZZO-1300-AU, MEZZO-1300ST-AU
63-1/8 in. (1603 mm) MEZZO-1600-AU
FIREPLACE VIEWING AREA
Figure 10.6 Finished Opening Dimensions - Inside Fit Method
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
49
B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specified. Framing closer than the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.)
Note: For non-combustible fireplace finish material (marble, stone, etc) specifications refer to Section 10.A.
Combustible Mantels
TO CEILING
MAX.
6 in. (152 mm)
3 in. (76 mm)
1 in. (25 mm)
12 in. (305 mm)
9 in. (229 mm)
TO CEILING
MAX.
9 in. (229 mm)
6 in. (152 mm)
3 in. (76 mm)
MEASUREMENT FROM
TOP EDGE OPENING
MEASUREMENT FROM
TOP EDGE OPENING
Measurement from top edge opening to bottom of appliance = 24-1/2 in. (622 mm)
Figure 10.7 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles - MEZZO-1000-AU
MEZZO-1300-AU, MEZZO-1300ST-AU
Measurement from top edge opening to bottom of appliance = 24-1/2 in. (622 mm)
Figure 10.8 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles - MEZZO-1600-AU
50
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
MAX.
14 in. -
(356 mm)
16 in.
(406 mm)
INSIDE FIT
TO CEILING
7 in.
(178 mm)
6 in.
(152 mm)
5 in.
(127 mm)
MIN.
4 in.
(102 mm)
MEASUREMENTS FROM TOP EDGE
OF THE APPLIANCE OPENING
Measurement from top edge of opening to bottom of appliance = 24-1/2 in. (622 mm)
Figure 10.9 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles - Inside Fit
Finishing
Mantel Legs Or Wall Projections Extending Past The Face
Of The Fireplace (Combustible or Non-Combustible)
Note: Clearance from opening to perpendicular wall.
Note: Clearance from opening
to perpendicular wall.
7 in.
(178 mm)
MINIMUM
UNLIMITED
FIREPLACE OPENING
See Appliance Dimension Diagram-Dimension B
Figure 3.1 (MEZZO-1000-AU, MEZZO-1300-AU)
Figure 3.2 (MEZZO-1600-AU)
Figure 3.3 (MEZZO-1300ST-AU)
Figure 10.11 Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
C. Decorative Front Dimensions for
Finishing
WARNING! Risk of Burns! A decorative front is required for this model. DO NOT operate this appliance without a decorative front in place.
Only the decorative front certified for use with this appliance model may be used. Contact your dealer for a list of decorative fronts that may be used.
Inside Fit Doors (Clean Face Trim front): These doors are installed flush with the non-combustible finishing material up to four inches thick. Finishing materials may be a maximum of 1 in. (25 mm) thick. Stop finishing material flush with opening.
4-1/2 in.
(114 mm)
MINIMUM
3 ft. (914 mm)
MAXIMUM
FIREPLACE OPENING
See Appliance Dimension Diagram-Dimension B
Figure 3.1 (MEZZO-1000-AU, MEZZO-1300-AU)
Figure 3.2 (MEZZO-1600-AU)
Figure 3.3 (MEZZO-1300ST-AU)
Figure 10.10 Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Note: See appliance Owner’s Manual for TV mounting
guidelines.
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
51
11
Appliance Setup
A. Fixed Glass Assembly
WARNING! Risk of Asphyxiation! Handle fixed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches.
• DO NOT strike, slam or scratch glass.
•
DO NOT operate fireplace with glass removed, cracked,
broken or scratched.
• Replace as a complete assembly.
Removing Fixed Glass Assembly
1. Remove the decorative front from fireplace and set aside on work surface.
2. Locate the glass latches that are on the upper edge of the glass frame of the appliance. See Figure 11.1.
3. Use both index fingers to release the glass clips.
4. Allow glass to tilt forward. Grasp glass on the upper return lip of glass frame and lift up and out. The glass should lift easily out of the bottom retaining lip.
Replacing Fixed Glass Assembly
1. Locate retaining lip on lower front face of firebox.
2. Place glass assembly into retaining lip end. Tilt top of glass assembly toward fireplace.
3. Assure proper left to right placement of glass and engage all four spring latches.
B. Remove the Shipping Materials/Install
Vanity Panel
Remove shipping materials from inside or underneath the firebox. Verify all components are with the fireplace.
Unwrap the vanity panel and replace in the same location as shown in Figure 11.2.
VANITY
PANEL
Figure 11.2 Vanity Panel Location
C. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated inside the firebox or underneath in the control cavity.
GLASS CLIPS
BOTTOM RETAINING LIP
Figure 11.1 Fixed Glass Assembly
52
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
D. Install Glass Refractory Panels
See-Through Models: Start at Step 3.
1.
Single-Sided Models:
Set back glass panel, labeled A in Figure 11.3, into firebox. Back panel will be held in place by the side panels and will sit on the heads of the screws holding the media tray in place. Set back glass panel against the back wall of the firebox with the smooth side of the glass facing outward. Insert retaining bracket through the slot in the inner firebox heat shield. Line up the existing hole in the heat shield with the hole closest to the bend in the bracket and secure in place with a screw.
Set left side glass panel, labeled B in Figure 11.3, into firebox with the smooth side facing outward. Insert a retaining bracket through the slot in the inner firebox heat shield. Line up the existing hole in the heat shield with the hole closest to the bend in the bracket and secure in place with a screw. Ensure the side glass refractory panel is stationary. See Figure 11.4. Repeat for right side panel.
2.
See-Through Models:
Set left side glass panel, labeled B in Figure 11.3, into firebox with the smooth side facing outward. Place retaining bracket over glass panel so holes in the bracket are against the firebox side. Use two self-drilling screws to secure the bracket to the firebox side. See
Figure 11.5. Repeat for right side panel.
RETAINING BRACKET
DETAIL
RETAINING BRACKET LOCATION
Figure 11.4 Retaining Bracket Installation - Single-sided Models
B
A*
*Back panel used in single-sided models
Figure 11.3 Placement of Glass Panels
C
RETAINING BRACKET
DETAIL
RETAINING BRACKET LOCATION
Figure 11.5 Retaining Bracket Installation - See-Through Models
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
53
E. Install Media
A media kit is included with the MEZZO-AU models. Install rock media according to these instructions.
WARNING! Choking Hazard! Keep media out of reach of children.
CAUTION! Risk of Burns! The fireplace should be turned off and cooled before media is installed.
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
Cleaning the Media
During shipment of the media, dust and debris can accumulate. It is recommended that the media be rinsed thoroughly with water to remove dust and small particles.
An easy method to clean the media is to place the media into a pail and rinse thoroughly. Spread the media out over paper towels and allow the media to dry before installing them into the fireplace.
INSTALLATION
1. Choose 7 - 10 round pieces of media approximately
1/2 in. (13 mm) in size and set them aside. These will be used later to conceal the pilot end of the burner.
Reference Figure 11.6 for choosing round pieces of glass.
WARNING! Risk of Explosion! DO NOT put any flat media pieces larger than 1/2 in. (13 mm) in diameter near pilot. Delayed ignition could occur. Use only round 1/2 in.
(13 mm) pieces near pilot.
WARNING
Delayed Ignition Risk
• Place media according to instructions.
• Do NOT place media in area in front of pilot
• Do NOT place media in a position that they may fall into area in front of pilot.
• Do NOT use any media other than the media supplied with this fireplace.
• Do NOT exceed one layer of media on base pan.
Fireplace will not function properly.
Delayed ignition may occur.
ROCK MEDIA PLACEMENT JIG
PILOT SHIELD
BURNER
(MEZZO-1000-AU
MEZZO-1300-AU
MEZZO-1300ST-AU
MODELS)
BURNER RAILS (2)
MEDIA TRAY
BURNER
(MEZZO-1600-AU MODELS)
NO YES
Figure 11.7 Media Tray Components
3. The media placement jig must remain in place while media is placed on the media tray and around the pilot bracket.
MEDIA PLACEMENT JIG
Figure 11.6 Selecting Flat Media for Pilot Cover.
2.
The included media placement jig, shown in Figure
11.7, MUST be used any time media are placed on the burner to ensure that none end up in the burner lighting area. Verify that the media placement jig is correctly installed in place in the appliance. See Figure
11.8.
54
Figure 11.8 Media Placement Jig in Place
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
4.
Place an even layer of media around the media tray as shown in Figure 11.9. Figure 11.9 shows an outline of the burner rails and the area in front of the pilot assembly.
5. Continue to place an even amount of media over the entire media tray.
WARNING
Risk of Asphyxiation or Fumes.
• Place media according to instructions.
• Do NOT place media in area between glass and firebox.
• Do NOT place media in a position that they may fall into area between glass and firebox.
• Do NOT use any media other than the media supplied with this fireplace.
Fireplace will not function properly.
Gas leak may occur.
SCREW
Figure 11.11 Media Installed.
Fogging Option
8. If desired, the media can be fogged using a high temperature black paint. See below for fogging tips. Prior to painting, take precautions to prevent any overspray from reaching the pilot assembly.
• Apply paint with the LED lights turned on. This will help you avoid over fogging or under fogging.
• Reduce the lighting in the room while applying the paint.
• Fog the media to the desired look.
MEDIA BETWEEN
BURNER RAILS
Figure 11.9 Media Placement Jig in Place
6. Remove the screw, noted in Figure 11.9 (shown in Figure
11.10), from the media placement jig and carefully lift it out of the appliance. Do not allow any pieces of media to fall into the area in front of the pilot.
7. Place the round media set aside in Step 1 over the pilot shield and areas uncovered by removing the media placement jig. See Figure 11.11.
WARNING! Risk of Fire. DO NOT place media directly in front of the pilot assembly.
Figure 11.12 Fogging the Media
9. Place the glass frame assembly back on the appliance according to the instructions provided in the appliance installation manual. Assure that there is no media between the glass and the firebox. Media in this area will prevent the glass gasket from sealing.
10. Install bottom vanity panel between glass and glass frame. See Figure 11.13.
Figure 11.10 Remove Media Placement Jig
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
55
Figure 11.13 Install Bottom Vanity Panel
TROUBLESHOOTING
After the initial start up burn, it may be necessary to adjust the media placement to achieve the best flame appearance. While flame height variation is normal, there may appear to be higher peaks in some areas and low flame peaks in other areas.
If the flame height appears to be excessively high in some spots, applying more media to these areas on top of the burner will help even out the flames. Spreading the media as evenly as possible is the most effective way to achieve optimal flame appearance and the most even flame heights. One or more test burns may be required to watch the flames mature and see how even they look before making adjustments.
Avoid using media pieces larger than two inches in diameter, these can be disruptive to the flame patterns. If you find exra large media pieces, discard.
F. Install Log Set
An optional log set is available for use with the MEZZO-
AU models. Install the log set per instructions included with kit.
G. Appliance Operation
Start the appliance to verify proper function and installation. See the appliance Owner’s Manual for IPI lighting instructions.
Appliance ON/OFF
Use the IntelliFire™ Plus Remote Control to control the
ON/OFF function of the appliance. Follow instructions included with the installed control. If a wall switch is installed, refer to the instructions included with the control.
LED Lighting
The ON/OFF function for the LED lighting option is controlled by the IntelliFire™ Plus remote control. Follow instructions included with the installed control to test the
LED lighting.
56
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
12
Reference Materials
A. Vent Components Diagrams
Effective
Height/Length
DVP Pipe (see chart)
Pipe
DVP4
DVP6
DVP12
DVP24
DVP36
DVP48
DVP6A
Effective Length
Inches Millimeters
4 102
6
12
24
36
48
3 to 6
152
305
610
914
1219
76 to 152
DVP12A 3 to 12 76 to 305
10-1/2 in.
(267 mm)
4-7/8 in.
( 276 mm)
10-7/8 in.
(276 mm)
DVP45 (45º Elbow)
45°
10 in.
(254 mm)
20-3/4 in.
(527 mm)
10 in.
(254 mm)
Tab=1 in.
(25.4 mm)
Finished Height: 19-3/4 in./502 mm
UNIV-AS2 (Attic Insulation Shield)
DVP-FS (Ceiling Firestop)
1 in.
(25 mm)
11-3/8 in.
(289 mm)
7-3/8 in.
(187 mm)
1-1/4 in. (32 mm)
9-1/4 in.
(235 mm)
13-1/4 in.
(337 mm)
1/2 in. TYP
(13 mm)
DVP90ST (90° Elbow)
12 in.
(305 mm)
1 in.
(25 mm)
10 in.
(254 mm)
UP
1- 1/2 in.
(38 mm)
5 in.
(127 mm)
12 in.
(305 mm)
14 in.
(356 mm)
8 in.
(203 mm)
DVP-HVS (Vent Support)
6 in.
(152 mm)
DVP-WS (Wall Shield Firestop)
Figure 12.1 DVP Vent Components
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
57
A. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
8 in.
(203 mm)
Heat
Shield
15-1/8 in.
(384 mm)
12 in.
(305 mm)
DVP-TRAP2
Horizontal Termination Cap
Max
Effective
Length
Term Cap
Trap1
Trap2
Minimum
Effective Length
3-1/8 in.
79 mm
5-3/8 in.
137 mm
Maximum
Effective Length
4-5/8 in.
117 mm
9-3/8 in.
238 mm
DVP-TRAP2
1 in.
(25 mm)
7-1/4 in.
(184 mm)
14 in.
(356 mm)
3/8 in. (10 mm)
1 in. (25 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
FireBrickTermination Cap
Figure 12.2 DVP Vent Components
58
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
A. Vent Components Diagrams (continued)
8-1/8 in.
(206 mm)
15 in.
(381 mm)
13 in.
(330 mm)
DVP-HRC-SS
Horizontal Termination Cap
WARNING
Fire Risk.
• When using DVP-HRC-SS termination cap
on top vented fireplaces, a 6 inch (152 mm)
minimum vertical vent section is required before
installing first elbow.
DVP-TRAPFL
Flashing
31 in.
(787 mm)
24-5/8 in.
(625 mm)
RF12M
Roof Flashing Multi-pak
13-1/4 in.
(367 mm)
12 in.
305 mm
7-1/4 in.
(184 mm)
12-1/2 in.
(318 mm)
5-1/4 in.
(133 mm)
DVP-TVHW
VerticalTermination Cap (Highwind)
13-7/8 in.
(352 mm)
9-1/2 in.
(241 mm)
13-1/4 in.
(367 mm)
24-5/8 in.
(625 mm)
27-1/2 in.
(127 mm)
14 in.
(356 mm)
RF6M
Roof Flashing Multi-pak
DRC-RADIUS
Cap Shield
Figure 12.3 DVP Vent Components
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15
59
B. Accessories
Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to operate your fireplace:
For safety:
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
Contact your dealer if you have questions.
Heat-Zone
®
Kit
Follow the instruction supplied with the kit for operation.
• Preparation for installation of Heat-Zone
®
Kit is discussed in Section 5.E.
Contact your dealer if you have questions.
60
Heat & Glo, a brand of Hearth & Home Technologies
7571 215 th
Street West, Lakeville, MN 55044 www.heatnglo.com
Please contact your Heat & Glo dealer with any questions or concerns.
For the location of your nearest Heat & Glo dealer, please visit www.heatnglo.com.
Printed in U.S.A. - Copyright 2015
Heat & Glo • MEZZO-1000-AU, MEZZO-1300-AU, MEZZO-1300ST-AU, MEZZO-1600-AU Installation Manual • 2304-970 Rev. L • 9/15

Download
Advertisement
Key features
- Natural gas or ULPG
- Direct Vent Heater
- 5 mm ceramic glass
- Approved for use with Hearth & Home Technologies DVP venting systems
- NOT intended for fireplace insert
- NOT to be used as primary heat source
- Install on hard metal or wood surfaces
- Maintain specified air space clearances