Basic contacts interface

Basic contacts interface
Basic contacts interface
3477
Description
This devices let you integrate traditional control devices (switches, pushbuttons, etc.) in
advanced systems with BUS operating logic.
Therefore, it is possible to extend the use of the automation system and Lighting
Management in rooms where traditional systems are already present or in historic and
prestigious environments whereby the complete or partial remaking of the electric
system involves heavy masonry work. The old but valuable switch with its no longer
compliant wiring can therefore continue to be used with it as the connection to the
load to be controlled is carried out safely by connecting it with its SCS interface with
no-voltage contact.
The PL1 contact drives the PL1 light point, the PL2 contact drives the PL2 light point.
The interface is fitted with two LEDs for the notification of correct operation and three
cables for connection to traditional devices. The device is made with Basic enclosure,
with reduced dimensions and can be used in flush mounted and junction boxes and
trunkings. The installation in boxes is particularly advantageous, with the positioning
of the item inside the flush mounted box, behind lowered automation devices or behind
traditional devices (pushbuttons, circuit breakers etc.).
The device may be installed in a MY HOME system and can be configured both physically
and virtually, or as a component of the Lighting Management system, using specific
configuration procedures (Plug&go, Project&Download).
Technical data
Power supply from SCS BUS: Operating power supply with SCS BUS: Absorption: A
PL1
PL2
M
SPE
1
3477
2
PL1
4
PL2
C
3
Legend
27 Vdc
18 – 27 Vdc
3.5 mA
Dimensional data
1. Configurator socket
(attention, it must only be used in MY HOME systems with physical configuration)
2. LED
3. Cords for connection to traditional devices
4. BUS
Size: basic module
MY HOME configuration
When installed in a MY HOME system, the device may be configured in two ways:
- PHYSICAL CONFIGURATION, by connecting the physical configurators to their sockets.
- VIRTUAL CONFIGURATION, by connecting the system to the PC using the 3503N Kit or
the web server. The Virtual configurator software must be installed on the PC.
BT00272-a-UK
Technical sheets - Automation
MY HOME
1
3477
Physical configuration
The interface includes two independent central units, identified with positions PL1 and
PL2. The two units can send:
- controls to two actuators for two independent loads (ON, OFF or adjustment) identified
with the address PL1 and PL2 and mode specified in M or;
- a control to the scenario module item F420;
- a double control intended for a single load (motor for rolling shutter UP/DOWN, OPENCLOSE curtains) identified with the address PL1 and PL2 and mode specified M.
The interface is fitted with a LED to signal correct operation, and three clamps for
connection to traditional devices such as:
- two traditional NO (normally open) and NC (normally closed) switches or pushbuttons;
- a two-way switch.
1) SPE=0 mode - Standard functions - Automation
Value configurator in M
Possible function
single function
double function
Cyclical ON-OFF for short press and adjustment with long pressure
no configurator
-
ON
ON
-
1–8
-
OFF
OFF
-
OFF pressing the key connected to PL1 - ON pressing the key connected to PL2 and
adjustment with long pressure (dimmer) 2)
-
0/1
UP/DOWN rolling shutter to end of stroke
-

UP/DOWN rolling shutter monostable
-
 M
Pushbutton
PUL
-
ON timed
1)
1) The device sends an OFF control after a time set by the configurators used as indicated in
the table below.
Configurator
Time (min.)
1
1
2
2
3
3
4
4
5
5
6
15
7
30 sec.
8
0.5 sec.
BT00272-a-UK
2
MY HOME
Technical sheets - Automation
2) As a function of the receiver actuator operating mode.
NotE: If circuits are connected to the interface clamps, the operating mode to select is PUL.
If normally open (NO) pushbuttons are connected all the other operating modes indicated in
the table are performed.
3477
2) Operating mode with the configurator in M and in SPE
Possible function
Value configurator in SPE
Locks the status of the devices to which the control is addressed
Value configurator in M
single function
double function
1
1
-
Unlocks the status of the devices to which the control is addressed
1
2
-
Unlocks with key connected to PL2
and locks with key connected to PL1
1
-
3
On with flash 1)
2
none – 9
-
ON (key in PL2) - OFF (key in PL1) without adjustment
1
-
0/1
Cyclical ON/OFF without adjustment (only NO contact)
1
7
-
3
1–9
-
Call the scenarios of module F420
4
-
see table (3)
Management of scenario module item F4203)
6
see table (3)
ON timed (2 seconds)
8
1
ON timed (10 minutes)
8
2
1) Device to be combined with an OFF control for switching OFF.
The flash time is indicated in the table:
3) With SPE=4 it is only possible to recall the scenario saved in the F420 module; with SPE=6
it is possible to recall and program the scenarios saved in the F420 module. M=1-8: group of
scenarios to be controlled:
Selection adjustment level fixed at 10 to 90 % of the dimmer
2)
Configurator
Time configurator (sec.)
none
0.5
M
First contact (PL1)
Second contact (PL2)
1
1
1
1
2
2
1.5
2
3
4
3
2
3
5
6
4
2.5
4
7
8
5
3
5
9
10
6
3.5
6
11
12
7
4
7
13
14
8
4.5
8
15
16
9
5
A=0 to 9 and PL1=1 to 9 are the room and the light point of the scenario module to be
controlled. PL2 must be the same as PL1, or not configured (in this case the second contact is
disabled).
2) Device to be combined with the dimmer actuator and an OFF control for switching OFF.
The configurator defines the adjustment in % of the load power.
% P of load
1
10
2
20
3
30
4
40
5
50
6
60
7
70
8
80
9
90
BT00272-a-UK
Configurator in N
Technical sheets - Automation
MY HOME
3
3477
Scenario programmer: in order to program, change or cancel a scenario, it is necessary to
enable the programming mode of the Module item F422 so that the status LED is green
(press the lock/unlock key on the Scenario Module for at least 0.5 seconds); continue with
the following operations:
To call a set scenario just press its pushbutton on the control quickly.
To cancel a scenario completely, keep the corresponding pushbutton pressed for about ten
seconds.
1) press one of the four control keys the scenario is to be associated to for 3 seconds. The
corresponding LED will begin to flash.
2) Set the scenario using the corresponding controls belonging to the various Automation,
Temperature control, Sound system functions, etc.
3) confirm the scenario by quickly pressing the corresponding key on the control to exit
programming mode;
4) To change or create new scenarios to be linked to the other keys, repeat the procedure
starting from point 1.
3) Mode with SPE=7 - Automation standard functions - normally closed contact
This mode can perform the controls envisaged by the Basic operating mode with SPE = 0 when NC pushbuttons or switches are connected to the interface clamps.
4) Mode with SPE=5 - sound system When the interface is correctly configured, the following functions are performed:
M=1 Source cycling/track cycling mode
M=0 ON/OFF mode:
N1 contact: cycle source
N1 contact:
N2 contact: cycle track
With a short pressure, the following sequence is sent:
In this operating mode:
- ON of the sources. PL2 indicates the source to activate before switching the amplifier on. If PL2=0, source 1 is turned on (follow-me mode)
- room controls
- ON of the A/PL1 amplifier.
With extended pressure the following happens:
- For point-point controls, if the amplifier is already on, only the volume is adjusted (VOL+);
if the amplifier is off, the switch on sequence is sent first;
- For AMB or GEN controls, only the volume is adjusted.
N2 contact:
With a short pressure, the OFF command of the A/PL1 amplifier is sent
With an extended pressure the volume is adjusted (VOL -)
In this operating mode:
Point-point control
- A = 1-9 amplifier room
- PL1= 0-9 amplifier speaker
BT00272-a-UK
Room control
A = AMB
PL1 = 1-9 amplifier room the control is intended for
General control
A = GEN
PL1 = 0
PL2 = 1-4 indicates the source to activate before switching the amplifier on.
If PL2=0, follow-me mode is activated
4
MY HOME
Technical sheets - Automation
A = 1-9 is the amplifier room
- General controls
A = GEN for general controls
PL1=PL2=0
3477
Lighting Management configuration
Virtual configuration
Using the Virtual Configurator software it is possible to perform all the functions listed
below:
- contact;
- single light control;
- single disable control;
- single scenario control;
- single CEN control;
- single scenario PLUS control;
- single CEN PLUS control;
- single AUX control.
When installed in a Lighting Management system, the device can be configured in the
following ways:
- Plug&Go
- Project&Download,
Using the Virtual Configurator software it is possible to perform all the functions listed below:
- contact
- single light control
- single disable control
- single scenario control
- single CEN control
- single scenario PLUS control
- single CEN PLUS control
- single AUX control
For more information on the functions see the glossary before the Technical sheets
chapter.
Wiring diagram
Basic interface
A
PL1
PL2
M
SPE
Historical actuator
3477
PL1
PL2
C
1
1
Historical switch
C1
2
2
3
3
4
4
C2
SCS BUS
L
N
BT00272-a-UK