Commercial Products

Commercial Products
Commercial Products
PRODUCTS
GUIDE
2002
Index
Commercial Products
Packaged Products
Outdoor Packaged Rooftop Units
Single Zone Electric Cooling/Gas Heating
48TF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
48TJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-25 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
48TM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
48TM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-25 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14
48HJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
48HJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 & 15 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18
48HG (CENTURION™) . . . . . . . . . . . . . . . . . . . . . 12 1/2-25 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-20
48A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-60 Ton Constant Volume/Variable Air Volume . . . . . . . . . . . . . . . . . .21-22
48Z . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-105 Ton Constant Volume/Variable Air Volume . . . . . . . . . . . . . . . . .23-24
48GX, GXN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25-26
48GS, GSN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27-28
48GP, GPN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency with Puron . . . . . . . . . . . . . . . . . . . . . . . . . . . .29-30
Single Zone Electric Cooling/Electric Heating
50TFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
50TJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-25 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
50TM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
50TM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-25 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-14
50HJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 1/2 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-16
50HJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 & 15 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-18
50HG (CENTURION) . . . . . . . . . . . . . . . . . . . . . . . 12 1/2-25 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-20
50A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-60 Ton Constant Volume/Variable Air Volume . . . . . . . . . . . . . . . . . .31-32
50Z . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-105 Ton Constant Volume/Variable Air Volume . . . . . . . . . . . . . . . . .33-34
50SX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35-36
50ZP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37-38
50GS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39-40
50GL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency with Puron . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-42
50GX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43-44
Single Zone Heat Pump
50TFQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45-46
50HJQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47-48
50HJQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 & 15 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49-50
50HX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-52
50JS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53-54
50JX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55-56
50JZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton High Efficiency with Puron . . . . . . . . . . . . . . . . . . . . . . . . . . . .57-58
50ZH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton Standard Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59-60
Factory-Installed Options/Field-Installed Accessories
Enviro-Shield™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Corrosion Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-62
Durablade Economizer . . . . . . . . . . . . . . . . . . . . . . for 3-12 1/2 Ton Rooftop Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63-64
Hinged Panels Factory-Installed Option . . . . . . . . . for 48/50HJ 3-12 1/2 Ton Rooftop Units . . . . . . . . . . . . . . . . . . . . . . . . 65-66
MoistureMi$er™ Dehumidification Pkg . . . . . . . . . for 48/50HJ 3-12 1/2 Ton Rooftop Units . . . . . . . . . . . . . . . . . . . . . . . . 67-68
MoistureMi$er High Latent Dehumidification Pkg . . for 48/50TJ,HJ 12-25 Ton Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69-70
EconoMi$er2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . for 3-12 1/2 Ton Rooftop Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71-72
Indoor Packaged Self-Contained Units
Air-Cooled Units
50AH (ROOMTOP®) . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Ton Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73-74
50BY (ECOZONE™) . . . . . . . . . . . . . . . . . . . . . . . . 5-20 Ton Vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75-76
• Commercial Product Guide • 2002 •
3
Vertical Water-Cooled or Remote Air-Cooled
50BR, BZ (ECOZONE™) . . . . . . . . . . . . . . . . . . . . 5-20 Ton Vertical Single Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77-78
50BVC, BVQ, BVJ, BVY (ECOZONE) . . . . . . . . . . 18-60 Ton Standard Water-Cooled Indoor Packaged System . . . . . . . . . 79-80
50BVE, BVK (ECOZONE) . . . . . . . . . . . . . . . . . . . 18-60 Ton Standard Remote Air-Cooled Indoor Packaged System . . . . . .81-82
50BVT, BVV, BVW, BVZ (ECOZONE) . . . . . . . . . . 20-60 Ton Modular Water-Cooled Indoor Packaged System . . . . . . . . . .83-84
50BVU, BVX (ECOZONE) . . . . . . . . . . . . . . . . . . . 20-60 Ton Modular Remote Air-Cooled Indoor Packaged System . . . . . .85-86
50XJ (ECOZONE) . . . . . . . . . . . . . . . . . . . . . . . . . . 50-110 Ton Vertical VAV Indoor Packaged System . . . . . . . . . . . . . . . . .87-88
90MF, MA, MU . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Ton Industrial Single Package, Water Cooled . . . . . . . . . . . . . . . . . 89-90
Water Source Heat Pump
50RHR, RVR (AQUAZONE™) . . . . . . . . . . . . . . . . 1/2-5 Ton Vertical and Horizontal High Efficiency WSHP . . . . . . . . . . . 91-92
50RDS,RHS, RVS (AQUAZONE) . . . . . . . . . . . . . . 1 1/4-6 Ton Vertical, Horizontal and
Downflow Premium-Efficiency WSHP . . . . . . . . . . . . . . . . . . . . . . . . . .93-94
50RHC,RVC (AQUAZONE) . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Vertical and Horizontal Standard-Efficiency WSHP . . . . . . .95-96
50RWS (AQUAZONE) . . . . . . . . . . . . . . . . . . . . . . 3-10 Ton Water-to-Water WHSP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97-98
50HQL, VQA, VQD (AQUAZONE) . . . . . . . . . . . . 6-25 Ton Vertical and Horizontal Large-Capacity WSHP . . . . . . . . . . . 99-100
50KQA, KQD (AQUAZONE) . . . . . . . . . . . . . . . . . 1/2-1 1/2 Ton Console WSHP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101-102
50RTG (AQUAZONE) . . . . . . . . . . . . . . . . . . . . . . . 3-20 Ton Rooftop WSHP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103-104
Split System Products
Air-Cooled Condensing Units
38AKS (GEMINI) . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1/2-40 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105-106
38AH (GEMINI) . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-130 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107-108
38ARZ, ARS (GEMINI) . . . . . . . . . . . . . . . . . . . . . . 6-10 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109-110
38ARD (GEMINI) . . . . . . . . . . . . . . . . . . . . . . . . . . 10-20 Ton Dual Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111-112
Heat Pumps
38AQ, ARQ, AQS (GEMINI) . . . . . . . . . . . . . . . . . . 6-15 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113-114
Direct Expansion Fan Coils
Packaged Air-Handling Units
40RM, RMQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,800-15,000 CFM DX and Heat Pump . . . . . . . . . . . . . . . . . . . . . . . .115-116
40RMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,250-15,000 CFM Chilled-Water Air-Handling Unit . . . . . . . . . . . . .117-118
Ductfree Split Systems
40QNB, QNE, QNH . . . . . . . . . . . . . . . . . . . . . . . . . 3/4-2 Ton High Wall Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119-124
40QKB, QKE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-3 Ton Cassette Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119-124
40QAB, QAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Under Ceiling Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . .119-124
38HDC, QR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Commercial Grade Condensing Unit . . . . . . . . . . . . . . . .119-124
38AN, BK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4-2 Ton Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119-124
38HDL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-5 Ton Light Commercial Condensing Unit . . . . . . . . . . . . . . . . 119-124
38HDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ton Multizone Condensing Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 119-124
40CG, CS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-2 1/2 Ton Console/Under Ceiling Indoor Unit . . . . . . . . . . . . . .119-124
40HD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 Ton Satellite Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119-124
38CG, CS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1/2-2 1/2 Ton Console/Under Ceiling Condensing Unit . . . . . . . . . .119-124
38SC, SB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ton Console Multizone Condensing Unit . . . . . . . . . . . . . . . . . . . . .119-124
42WKN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hydronic Cassette Fan Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125-126
Packaged Terminal Air Conditioner
52C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comfort Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127-128
52F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Through-The-Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129-130
52P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Premier Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131-132
4
• Commercial Product Guide • 2002 •
Index
Commercial Products
Water Chillers and Refrigeration
Absorption Chillers, Single Effect
16JB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108-680 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133-134
Centrifugal Chillers, Hermetic
19XR, XRV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-1,500 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135-136
Screw Chillers, Water-Cooled
23XL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229-360 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137-138
30HX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70-265 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139-140
Packaged Air-Cooled Chillers
30GTN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-400 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141-142
30GX (ECOLOGIC™) . . . . . . . . . . . . . . . . . . . . . . . 80-525 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .143-144
30GX (ECOLOGIC η™) . . . . . . . . . . . . . . . . . . . . . 83-528 Ton High Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145-146
30RA (AQUASNAP™) . . . . . . . . . . . . . . . . . . . . . . 10-55 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147-148
Packaged Water-Cooled/Condenserless Chillers
30HK, HL, HWC . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-60 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149-150
30HWA, HWB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-215 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151-152
Condensing Units
Air-Cooled Condensers
09DE, DK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-116 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153-154
09BY (ECOZONE™) . . . . . . . . . . . . . . . . . . . . . . . . 5-20 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155-156
09AW, AZ (ECOZONE) . . . . . . . . . . . . . . . . . . . . . . 1-20 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157-158
09AZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100-220 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159-160
Airside Products
Central Station Air-Handling Units
39L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,800-15,000 CFM Modular Single Wall . . . . . . . . . . . . . . . . . . . . . .161-162
39T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15,000-50,000 CFM Modular Single Wall . . . . . . . . . . . . . . . . . . . . . 163-164
39M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,500-15,000 CFM Modular Double Wall . . . . . . . . . . . . . . . . . . . . . .165-166
39T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15,000-50,000 CFM Modular Double Wall . . . . . . . . . . . . . . . . . . . . .163-164
39NC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,600-50,000 CFM Weather-Tight Rooftop . . . . . . . . . . . . . . . . . . . . 167-168
Air Treatment/Indoor Air Quality Products
Heat Recovery Ventilator/Energy Recovery Ventilator
62AQ Energy$Recycler . . . . . . . . . . . . . . . . . . . . . . 600-3,000 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169-170
62AA, AB, AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-3,800 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171-172
• Commercial Product Guide • 2002 •
5
Air Terminal Products
35E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-7,100 CFM Single Duct VAV Terminals . . . . . . . . . . . . . . . . . . . .173-176
35J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-3,700 CFM Single Duct VAV Terminals . . . . . . . . . . . . . . . . . . . .173-176
35L, M, N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-7,100 CFM Dual Duct VAV Terminals . . . . . . . . . . . . . . . . . . . . 173-176
45J, K, L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500-3,300 CFM Series Fan Powered Terminals . . . . . . . . . . . . . . . . . 173-176
45M, N, P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500-3,700 CFM Parallel Fan Powered Box . . . . . . . . . . . . . . . . . . . . 173-176
35K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-4,400 CFM Bypass Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173-176
35BD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100-500 CFM Boot Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173-176
37H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100-400 CFM Integral Diffuser VAV Unit . . . . . . . . . . . . . . . . . . . . . 173-176
36R, S, T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-130 CFM Induction Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173-176
Unit Ventilators
40UV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500-1,500 CFM Vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .177-178
40UH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750-2,000 CFM Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .177-178
Fan Coils
Vertical & Horizontal
42V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-1,200 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179-180
42C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200-1,200 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179-180
Ducted
42D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600-2,000 CFM Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179-180
42DD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600-2,000 CFM Vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179-180
Belt-Driven Fan Coil
42BH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800-4,000 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179-180
Vertical Stack
42S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300-1,200 CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179-180
Systems Products
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181-239
6
• Commercial Product Guide • 2002 •
48TF/50TFF
Commercial Products
Standard-Efficiency Single-Package Rooftop Units
Gas Heating/Electric Cooling or Electric Heating/Electric Cooling
3 to 12 1/2 Nominal Tons
3-6 Tons
Features
• Listed by UL and UL, Canada, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor, 5 Year Heat Exchanger
• Easily convertible airflow capability (down supply/return standard)
• Internally-sloped, composite condensate pan (dual connections)
• Exclusive tool-less filter access door
• Roll-formed base-rail design with forklift slots and rigging holes
• Two curbs for entire line
• 004-006 operating weights under 500 lbs
• Through-the-bottom utility capability (requires accessory)
• 2" disposable filters
• Low pressure, high pressure and freeze protection
• All condenser coils are set on rubber isolators to prevent contact
with unit base pan eliminating galvanic corrosion
• Refrigerant filter drier
• Permanently lubricated fan motors
• Compressor vibration isolation mounting
• All units are run tested at the factory
• Low voltage terminal blocks for easy thermostat wiring connections
• Dual compressors and dual refrigeration circuits on 008-014
48TF Only
• Integrated Gas Control (IGC) board with diagnostics
• Tubular, dimpled gas heat exchanger design
• Low NOx models
• Flame rollout safety protector
• Induced draft combustion with fan proving switch
• Direct spark electronic ignition sytem
• Two stage gas heat on most sizes
Factory-Installed Options
• Alternate Motor(s) and Adjustable Belt Drive Fans
• Manual Outside Air Damper
• Integrated EconoMi$er2 with CO2 control capability
• Apollo Communicating Control
• High Static Indoor Fan Motor (Belt Drive)
• Corrosion-Resistant Coils (including E-Coat)
• 115 Volt Convenience Outlet
• Non-Fused Disconnect Switch
• PremierLink™ DDC Controls
• Novar 2024/3051 Controls
• Stainless steel (type 409) heat exchangers (48TF only)
7.5-12.5 Tons
Dimensions
TONNAGE
L
W
H
3-6
73 11/16
45
33 5/16
7.5-8.5
87 3/8
57 3/4
41 5/16
10-12.5
87 3/8
57 3/4
49 5/16
NOTE: All dimensions are in inches
Field-Installed Accessories
• EconoMi$er2 with CO2 control capability
• Durablade Economizer
• EconoMi$er Enthalpy Controls
• EconoMi$er2 w/4-20mA actuator (PremierLink/3rd party control)
• 25% or 100% Two-Position Outdoor Air Dampers
• 25% or 50% Open Manual Outdoor Air Dampers
• Fan/Filter Status Sensor – EconoMi$er2
• Power Exhaust System
• Horizontal power exhaust module
• Low Ambient Controls
• Time Guard® II Compressor Delay
• Roof Curbs
• Through-The-Bottom Electrical and/or Gas Connections
• Liquid Propane Kit
• 62AQ Energy$Recycler Energy Recovery Unit
• Flue Hood Protector Assembly
• Flue Discharge Deflector
• Condenser Coil Grille
• Condenser Hail Guard
• Thermostats
• Thermidistat™
• CO2 Sensors (EconoMi$er2 or PremierLink required)
• Space temp sensors T55,T56 (PremierLink)
• Electric Heaters and Single Point Kits
• Commercial Product Guide • 2002 •
7
Performance & Sizing Information
48TF GAS/ELECTRIC
UNIT
48TF
004
005
006
UNIT
48TF
007
008
009
012
014
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
3
4
5
35,000
47,000
57,000
4.0
5.3
6.7
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
6
72,000
8.0
7 1/2
85,000
9.6
8 1/2
98,000
10.9
10
117,000
13.0
12 1/2
144,000
16.0
SEER
Belt Drive
Direct Drive
10.0
10.0
10.0
9.7
9.7
9.7
EER
SOUND
RATING (Bels)
8.7
8.8
8.5
8.1
8.1
8.1
SOUND
RATING (Bels)
8.1
8.7
8.7
8.8
8.7
EER
9.0
8.9
9.0
9.0
9.0
IPLV
9.4
9.0
9.4
9.2
50TFF ELECTRIC/ELECTRIC
UNIT NOMINAL NET COOLING TOTAL
50TFF
CAPACITY (Btuh)
kW
TONS
kW
004
005
006
3
4
5
35,000
47,000
57,000
4.0
5.3
6.7
UNIT NOMINAL NET COOLING TOTAL
50TFF
TONS
CAPACITY (Btuh)
kW
kW
007
6
72,000
8.0
008
7 1/2
85,000
9.6
009
8 1/2
98,000
10.9
012
10
117,000
13.0
014
12 1/2
144,000
15.7
SEER
Belt Drive
Direct Drive
10.0
10.0
10.0
9.7
9.7
9.7
EER
9.0
8.9
9.0
9.0
9.2
3-6 Ton
EER
SOUND
RATING (Bels)
8.7
8.8
8.5
8.1
8.1
8.1
SOUND
RATING (Bels)
8.1
8.7
8.7
8.8
8.7
IPLV
9.4
9.0
9.4
9.2
7.5-12.5 Ton
48TFD
48TFE
48TFF
48TFG
48TFH
48TFK
48TFL
48TFM
48TFN
–
–
–
–
–
–
–
–
–
Low Heat
Medium Heat
High Heat
Non-NOx Low Capacity Heat
Non-NOx Medium Capacity Heat
Non-NOx High Capacity Heat
Low NOx Low Capacity Heat
Low NOx Medium Capacity Heat
Low NOx High Capacity Heat
3-5 Ton
Only
3 Phase
Refer to product data information for further details.
Rated in
accordance with
ARI Standard
(60 Hz Only)
8
• Commercial Product Guide • 2002 •
48/50TJ
Commercial Products
Standard-Efficiency Rooftop Units
Gas Heating/Electric Cooling or Electric Heating/Electric Cooling
15 to 25 Nominal Tons
45”
H
86 1/8”
SIZE
H
15, 18 TON
20, 25 TON
45.0
47 1/4
83 1/2”
Features
Factory-Installed Options
• Listed by ETL and ETL Canada, Certified by ARI
• Dual Independent Refrigerant Circuits on All Units
• TXV Refrigerant Control on All Units
• Low Pressure/Loss of Charge Protection, Dual Freeze
Protection and High Pressure Switches
• Two Stage Heating and Cooling Operation
• Variable Pitch, LO-MED or HIGH ESP Fan Drives
• Insulated Cabinet With 500 Hour Salt Spray Protection,
Pre-Painted, Galvanized Steel
• Thru-the-Bottom Power and Gas Capability
• Manually Adjustable Outside Air Intake for up to 25%
Outside Air
• 2" Disposable Filters
• Warranty: 1 Year Parts, 5 Year Heat Exchangers
with Extended Compressor and Heat Exchanger
Warranties Available
48TJ Only
• Induced draft combustion with fan proving switch
• Integrated gas control board with diagnostics
• Direct spark electronic ignition system
• E-Coat (coil post-coating)
• Integrated EconoMi$er with CO2 Control Capability
• Electric Heaters (50TJ Only)
• PremierLink™ DDC Controls
• Apollo Direct Digital Controls
• Coil Material/Coating for Corrosive Environments
• Service Option Package:
- Hinged Access Panels
- Non-Fused Disconnect
- Non-Powered Convenience Outlet (115 V)
• UV-C Lamps
• MoistureMi$er™ Dehumidification Package
• Stainless Steel Heat Exchangers (48TJ only)
Field-Installed Accessories
• Power Exhaust
• Electric Heaters (50TJ Only)
• Integrated EconoMi$er with CO2 Control Capability
• LP Conversion Kits (48TJ Only)
• Barometric Relief
• Low Ambient Kits
• Full Perimeter Heavy Gauge Roof Curb
• Programmable Thermostats and Subbases
• Horizontal Adapter Roof Curb
• Glycol Coils (50TJ Only)
• Hail Guard
• CO2 Sensors (Wall or Duct Mounted)
• Commercial Product Guide • 2002 •
9
Performance & Sizing Information
TJ - SINGLE PACKAGE ROOFTOP UNITS 15-25 TONS
GAS/ELECTRIC, HEATING & COOLING 48 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
MODEL
NOM
NUMBER* TONS
ET
NO.
NOM CON
OLING COOLING
CFM
(Btuh)
STAGES
EER IPLV
48TJD016
15
5,250
174,000
2
8.60
9.3
48TJF016
15
5,250
174,000
2
8.60
9.3
48TJD020
18
6,200
188,000
2
8.70
9.5
HT.
INPUT
(Btuh)
HT.
STEADY
NO.
OUTPUT STATE HEATING
(Btuh)
%
STAGES
WT
(lbs)
Length
Width
Height
230,000
186,000
81
2
1,700
86.125
83.5
45
300,000
243,000
81
2
1,700
86.125
83.5
45
275,000
223,000
81
2
1,800
86.125
83.5
45
DIMENSIONS (in.)
48TJF020
18
6,200
186,000
2
8.50
9.3
360,000
292,000
81
2
1,800
86.125
83.5
45
48TJD024
20
6,600
220,000
2
8.60
8.7
275,000
223,000
81
2
1,850
86.125
83.5
47.25
48TJF024
20
6,600
218,000
2
8.50
8.5
360,000
292,000
81
2
1,850
86.125
83.5
47.25
48TJD028
25
7,200
268,000
2
8.60
9.2
275,000
223,000
81
2
2,000
86.125
83.5
47.25
48TJF028
25
7,200
268,000
2
8.50
8.9
360,000
292,000
81
2
2,000
86.125
83.5
47.25
ELECTRIC/ELECTRIC, HEATING & COOLING 50 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
ET
NO.
NOM CON
OLING COOLING
CFM
(Btuh)
STAGES
EER IPLV
15
5,250
176,000
2
8.90
18
6,200
188,000
2
MODEL
NUMBER
NOM
TONS
50TJ016
50TJ020
DIMENSIONS (in.)
TOTAL
kW
HEATING CAPACITY (kW)
([email protected] 460/3/60)
WT
(lbs)
Length
Width
Height
9.6
19.8
32 / 55 / 80
1,550
86.125
83.5
45
8.80
9.8
21.3
32 / 55 / 80
1,650
86.125
83.5
45
50TJ024
20
6,600
220,000
2
8.70
8.9
25.2
32 / 55 / 80
1,700
86.125
83.5
47.25
50TJ028
25
7,200
268,000
2
8.70
9.3
30.9
32 / 55 / 80
1,850
86.125
83.5
47.25
TJ - Single Packaged Rooftop Units 15-25 Tons
For more information, ask your Carrier salesperson for a complete 48/50TJ catalog.
* 48TJD Low Gas Heat - Standard Aluminized Steel Heat Exchangers
48TJM Low Gas Heat - Optional Stainless Steel Heat Exchangers
48TJF High Gas Heat - Standard Aluminized Steel Heat Exchangers
48TJN High Gas Heat - Optional Stainless Steel Heat Exchangers
Heating Capacities and Operating CFM Ranges same for Standard Aluminized Steel Heat Exchangers
or Optional Stainless Steel Heat Exchangers.
Rated in
accordance with
ARI Standard
590-92
10
• Commercial Product Guide • 2002 •
R
(60 Hz Only)
48/50TM
Commercial Products
Standard-Efficiency Single-Package Rooftop Units
Gas Heating/Electric Cooling or Electric Heating/Electric Cooling
3 to 12 1/2 Nominal Tons
3-6 Tons
Features
7.5-12.5 Tons
• Listed by UL and UL, Canada, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor, 5 Year Heat Exchanger
• Easily convertible airflow capability (down supply/return standard)
• Internally-sloped, composite condensate pan (dual connections)
• Exclusive tool-less filter access door
• Roll-formed base-rail design with forklift slots and rigging holes
• Two curbs for entire line
• 004-006 operating weights under 500 lbs
• Through-the-bottom utility capability (requires accessory)
• 2" disposable filters
• Low pressure, high pressure and freeze protection
• All condenser coils are set on rubber isolators to prevent contact
with unit base pan eliminating galvanic corrosion
• Refrigerant filter drier
• Permanently lubricated fan motors
• Compressor vibration isolation mounting
• All units are run tested at the factory
• Low voltage terminal blocks for easy thermostat wiring connections
• Dual compressors and dual refrigeration circuits on 008-014
48TM Only
• Integrated Gas Control (IGC) board with diagnostics
• Tubular, dimpled gas heat exchanger design
• Low NOx models
• Flame rollout safety protector
• Induced draft combustion with fan proving switch
• Direct spark electronic ignition sytem
• Two stage gas heat on most sizes
Factory-Installed Options
• Alternate Motor(s) and Adjustable Belt Drive Fans
• 25% Manual Outside Air Damper
• Integrated EconoMi$er2 with CO2 control capability
• Apollo Communicating Control
• High Static Indoor Fan Motor (Belt Drive)
• Corrosion-Resistant Coils (including E-Coat)
• 115 Volt Convenience Outlet
• Non-Fused Disconnect Switch
• PremierLink™ DDC Controls
• Novar 2024/3051 Controls
• Stainless steel (type 409) heat exchangers (48TM only)
Dimensions
TONNAGE
L
W
H
3-6
73 11/16
45
33 5/16
7.5-8.5
87 3/8
57 3/4
41 5/16
10-12.5
87 3/8
57 3/4
49 5/16
NOTE: All dimensions are in inches
Field-Installed Accessories
• EconoMi$er2 with CO2 control capability
• Durablade Economizer
• EconoMi$er2 Enthalpy Controls
• EconoMi$er2 w/4-20mA actuator (PremierLink/3rd party control)
• 25% or 100% Two-Position Outdoor Air Dampers
• 25% or 50% Manual Outdoor Air Dampers
• Fan/Filter Status Sensor – EconoMi$er2
• Power Exhaust System
• Horizontal power exhaust module
• Low Ambient Controls
• Time Guard® II Compressor Delay
• Roof Curbs
• Through-The-Bottom Electrical and/or Gas Connections
• Liquid Propane Kit
• 62AQ Energy$Recycler Energy Recovery Unit
• Flue Hood Protector Assembly
• Flue Discharge Deflector
• Condenser Coil Grille
• Condenser Hail Guard
• Thermostats
• Thermidistat™
• CO2 Sensors (EconoMi$er2 or PremierLink required)
• Space temp sensors T55,T56 (PremierLink)
• Electric Heaters and Single Point Kits
• Commercial Product Guide • 2002 •
11
Performance & Sizing Information
48TM GAS/ELECTRIC
UNIT
48TM
004
005
006
UNIT
48TM
007
008
009
012
014
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
3
4
5
35,000
47,000
57,000
4.0
5.3
6.7
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
6
71,000
7.0
7 1/2
88,000
8.7
8 1/2
100,000
9.9
10
114,000
11.3
12 1/2
136,000
14.3
SEER**
EER
SOUND
RATING (Bels)
10.0
10.0
10.0
8.7
8.8
8.5
8.1
8.1
8.1
EER
10.1
10.1
10.1
10.1
9.5
SOUND
RATING (Bels)
8.0
8.2
8.2
8.4
8.6
IPLV
10.3
10.4
11.0
9.7
** The SEER values shown for sizes 004, 005
and 006 are for units with the optional belt drive
motors; SEER rating for these units with the
standard direct drive motor is 9.7.
50TM ELECTRIC/ELECTRIC
UNIT
50TM
004
005
006
UNIT
50TM
007
008
009
012
014
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
3
4
5
35,000
47,000
57,000
4.0
5.3
6.7
NOMINAL NET COOLING TOTAL
TONS
CAPACITY (Btuh)
kW
kW
6
71,000
6.9
7 1/2
89,000
8.6
8 1/2
100,000
9.7
10
115,000
11.2
12 1/2
136,000
14.0
SEER**
EER
SOUND
RATING (Bels)
10.0
10.0
10.0
8.7
8.8
8.5
8.1
8.1
8.1
EER
10.3
10.3
10.2
10.3
9.7
3-6 Ton
SOUND
RATING (Bels)
8.0
8.2
8.2
8.4
8.6
IPLV
10.6
10.6
11.1
10.1
7.5-12.5 Ton
** The SEER values shown for sizes 004, 005
and 006 are for units with the optional belt drive
motors; SEER rating for these units with the
standard direct drive motor is 9.7.
48TMD –
48TME –
48TMF –
48TMG –
48TMH –
48TMK –
48TML –
48TMM –
48TMN –
Low Heat
Medium Heat
High Heat
Non-NOx Low Capacity Heat
Non-NOx Medium Capacity Heat
Non-NOx High Capacity Heat
Low NOx Low Capacity Heat
Low NOx Medium Capacity Heat
Low NOx High Capacity Heat
3-5 Ton
Only
3 Phase
Refer to product data information for further details.
Rated in
accordance with
ARI Standard
(60 Hz Only)
12
• Commercial Product Guide • 2002 •
48/50TM
Commercial Products
Standard-Efficiency Rooftop Units
Gas Heating/Electric Cooling or
Electric Heating/Electric Cooling
15 to 25 Nominal Tons
Features
Factory-Installed Options
• Listed by ETL and ETL Canada, Certified by ARI
• Dual Independent Refrigerant Circuits on All Units
• TXV Refrigerant Control on All Units
• Low Pressure/Loss of Charge Protection, Dual Freeze
Protection and High Pressure Switches
• Two Stage Heating and Cooling Operation
• Variable Pitch, LO-MED or HIGH ESP Fan Drives
• Insulated Cabinet With 500 Hour Salt Spray Protection,
Pre-Painted, Galvanized Steel
• Thru-the-Bottom Power and Gas Capability
• Manually Adjustable Outside Air Intake for up to 25%
Outside Air
• 2" Disposable Filters
• Warranty: 1 Year Parts, 5 Year Heat Exchangers
with Extended Compressor and Heat Exchanger
Warranties Available
48TM Only
• Induced draft combustion with fan proving switch
• Direct spark electronic ignition system
• E-Coat (coil post-coating)
• Integrated EconoMi$er with CO2 Control Capability
• Electric Heaters (50TM Only)
• PremierLink™ DDC Controls
• Apollo Direct Digital Controls
• Coil Material/Coating for Corrosive Environments
• Service Option Package:
- Hinged Access Panels
- Non-Fused Disconnect
- Non-Powered Convenience Outlet (115 V)
• UV-C Lamps
• MoistureMi$er™ Dehumidification Package
• Stainless Steel Heat Exchangers (48TM only)
Field-Installed Accessories
• Power Exhaust
• Electric Heaters (50TM Only)
• Integrated EconoMi$er with CO2 Control Capability
• LP Conversion Kits (48TM Only)
• Barometric Relief
• Low Ambient Kits
• Full Perimeter Heavy Gauge Roof Curb
• Programmable Thermostats and Subbases
• Horizontal Adapter Roof Curb
• Glycol Coils (50TM Only)
• Hail Guard
• CO2 Sensors (Wall or Duct Mounted)
• Commercial Product Guide • 2002 •
13
Commercial Products
Performance & Sizing Information
TM - SINGLE PACKAGE ROOFTOP UNITS 15-25 TONS
GAS/ELECTRIC, HEATING & COOLING 48 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
NET
NO.
MODEL
NOM
OLING COOLING
NUMBER* TONS CO
(Btuh)
STAGES
EER IPLV
HT.
INPUT
(Btuh)
HT.
STEADY
NO.
OUTPUT STATE HEATING
(Btuh)
%
STAGES
DIMENSIONS (in.)
WT
(lbs)
Width
Length
Height
48TMD016
15
176,000
2
9.5
9.5
230,000
186,000
81
2
1,800
86.125
83.5
45
48TMF016
15
176,000
2
9.7
9.5
300,000
243,000
81
2
1,800
86.125
83.5
45
48TMD020
18
202,000
2
9. 7
10.2
275,000
223,000
81
2
1,850
86.125
83.5
45
48TMF020
18
202,000
2
9. 7
10.1
360,000
292,000
81
2
1,850
86.125
83.5
45
48TMD025
20
236,000
2
9.5
10.1
275,000
223,000
81
2
1,900
86.125
83.5
47.25
48TMF025
20
236,000
2
9.5
10.0
360,000
292,000
81
2
1,900
86.125
83.5
47.25
48TMD028
25
278,000
2
9.7
10.4
275,000
223,000
81
2
2,270
86.125
105.5
47.25
48TMF028
25
277,000
2
9.5
10.0
360,000
292,000
81
2
2,270
86.125
105.5
47.25
ELECTRIC/ELECTRIC, HEATING & COOLING 50 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
MODEL
NUMBER
NET
NO.
NOM
OLING COOLING
TONS CO
(Btuh)
STAGES
EER IPLV
HEATING CAPACITY (kW)
([email protected] 460/3/60)
WT
(lbs)
DIMENSIONS (in.)
Width
Length
Height
50TM016
15
178,000
2
9.7
9.9
30 / 50 / 73
1,650
86.125
83.5
45
50TM020
18
204,000
2
10.0
10.5
30 / 50 / 73
1,710
86.125
83.5
45
50TM024
20
236,000
2
9.7
10.4
30 / 50 / 73
1,770
86.125
83.5
47.25
50TM028
25
278,000
2
9.8
10.5
30 / 50 / 73
2,120
86.125
105.5
47.25
TM - Single Packaged Rooftop Units 15-25 Tons
For more information, ask your Carrier salesperson for a complete 48/50TM catalog.
* 48TMD Low Gas Heat - Standard Aluminized Steel Heat Exchangers
48TMM Low Gas Heat - Optional Stainless Steel Heat Exchangers
48TMF High Gas Heat - Standard Aluminized Steel Heat Exchangers
48TMN High Gas Heat - Optional Stainless Steel Heat Exchangers
Heating Capacities and Operating CFM Ranges same for Standard Aluminized Steel Heat Exchangers
or Optional Stainless Steel Heat Exchangers.
Rated in
accordance with
ARI Standard
590-92
R
(60 Hz Only)
14
• Commercial Product Guide • 2002 •
48/50HJ
Commercial Products
High-Efficiency Single-Package Rooftop Units
Gas Heating/Electric Cooling or
Electric Heating/Electric Cooling
3 to 12 1/2 Nominal Tons
3-6 Ton
7.5-12.5 Ton
Features
• Listed by UL and UL, Canada, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor, 10 Year Heat Exchanger
• Easily convertible airflow capability (down supply/return standard)
• Exclusive Cycle-LOC™ anti-compressor cycle protection
• Scroll compressors in all models
• Tool-less filter access door
• Low pressure/loss of charge, freeze protection and
high pressure switches
• Insulated cabinet with 500 hour salt spray prepainted material
• Through-the-bottom utility capability (requires accessory)
• 2" disposable filters
• Internally sloped composite condensate pan (dual connections)
• Roll-formed base-rail design with forklift slots and rigging holes
• Two curbs for the entire line
• All condenser coils are set in rubber isolators to prevent contact
with unit base pan eliminating galvanic corrosion
• Refrigerant filter drier
• Permanently lubricated fan motors
• Compressor vibration isolation mounting
• All units are run tested at the factory
• Low voltage terminal blocks for easy thermostat wiring connections
• Dual compressors and dual refrigeration circuits on 008-014
48HJ Only
• State-of-the-art Integrated Gas Control (IGC) board
• Tubular, dimpled gas heat exchanger design
• Flame rollout safety protector
• Induced draft combustion with fan proving switch
• Two stage gas heat on most sizes
• Low NOx models
Factory-Installed Options
• Non-Fused Disconnect Switch
• Integrated EconoMi$er2 with CO2 control capability
• 115-Volt convenience outlet (hot)
• Corrosion-resistant coils (including E-Coat)
• MoistureMi$er™ Dehumidification Package
• Apollo Direct Digital Controls
• Stainless steel (type 409) heat exchangers (48HJ only)
• 62AQ Energy$Recycler factory installed
• Hinged Access Panels
Dimensions
TONNAGE
L
W
H
3-5
73 11/16
45
33 5/16
6
73 11/16
45
41 5/16
7.5
87 3/8
57 3/4
41 5/16
10
87 3/8
57 3/4
49 5/16
12.5
87 3/8
57 3/4
49 5/16
NOTE: All dimensions are in inches
• Extended 2-5 Year, Limited Parts Warranty
• PremierLink™ controls
• Novar 2024/3051 controls
• High static indoor fan motor and adjustable fan drive
Field-Installed Accessories
• Electric Heaters and Single Point Kits
• EconoMi$er2 with CO2 control capability
• EconoMi$er2 with 4-20mA actuator (for PremierLink or
3rd party controls)
• Durablade Economizer
• 25% or 100% Open Two Position Damper
• 25% or 50% Open Manual Damper
• LP Gas Conversion Kits
• Hail Guard Protectors
• Condenser Coil Guard Protector
• Roof Curbs
• Programmable Thermostat and Subbases
• Time Guard® Anti-Cycle Protector
• Flue Discharge Deflector
• 62AQ Energy$Recycler Energy Recovery Unit
• Indoor Fan/Filter Status Indicator
• Through-The-Bottom Electrical and/or Gas Connections
• Low Ambient Fan Speed Controllers
• Humidistat
• Thermidistat™
• CO2 Sensors (EconoMi$er2 or PremierLink required)
• Power Exhaust System
• Low NOx kit
• Commercial Product Guide • 2002 •
15
Commercial Products
Performance & Sizing Information
48HJ GAS/ELECTRIC
MODEL
NUMBER
NOMINAL
TONS
48HJE004
48HJF004
48HJD005
48HJE005
48HJF005
48HJD006
48HJE006
48HJF006
48HJD007
48HJE007
48HJF007
48HJD008
48HJE008
48HJF008
48HJD009
48HJE009
48HJF009
48HJD012
48HJE012
48HJF012
48HJD014
48HJE014
3
3
4
4
4
5
5
5
6
6
6
7.5
7.5
7.5
8.5
8.5
8.5
10
10
10
12.5
12.5
NET
COOLING
BTUH
36,000
36,000
46,000
46,000
46,000
61,000
61,000
61,000
73,000
73,000
73,000
90,000
90,000
90,000
102,000
102,000
102,000
120,000
120,000
120,000
138,000
138,000
*SEER/
EER
13/11.2
13/11.2
13/11.1
13/11.1
13/11.1
13/11.0
13/11.0
13/11.0
11
11
11
11
11
11
10.8
10.8
10.8
11
11
11
9.6
9.6
INDOOR
MOTOR FAN
DRIVE TYPE
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
BELT
SOUND
RATING
(Bels)
7.6
7.6
7.6
7.6
7.6
8.0
8.0
8.0
8.0
8.0
8.0
8.2
8.2
8.2
8.2
8.2
8.2
8.4
8.4
8.4
8.6
8.6
OPERATING
WEIGHT
(lbs)
530
530
540
540
540
560
560
560
635
635
635
870
870
870
880
880
880
1035
1035
1035
1050
1050
INDOOR
MOTOR FAN
DRIVE TYPE
BELT
BELT
BELT
BELT
BELT
BELT
SOUND
RATING
(Bels)
7.6
7.6
8.0
8.0
8.2
8.2
OPERATING
WEIGHT
(lbs)
435
445
465
540
755
760
HEATING
INPUT
BTUH
72,000
115,000
72,000
115,000
150,000
72,000
115,000
150,000
72,000
115,000
150,000
125,000
180,000
220,000
125,000
180,000
220,000
180,000
220,000
250,000
220,000
250,000
NO.
HEATING
STAGES
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
AFUE
%
82
80
82
81
80
82
81
80
82
81
80
82
82
82
82
82
82
82
82
80
82
80
*SEER/EER shown for 3-5 tons, all others rated at EER
NOTE: Heating input shown with all stages activated
50HJ ELECTRIC/ELECTRIC
ET
MODEL NOMINAL CON
OLING *SEEEERR/
NUMBER
TONS
BTUH
50HJ004
3
36,000
13/11.2
50HJ005
4
46,000
13/11.1
50HJ006
5
61,000
13/11.0
50HJ007
6
73,000
11.1
50HJ008
7.5
90,000
11.0
50HJ009
8.5
102,000
10.8
50HJ012
10
120,000
11.0
BELT
8.4
915
50HJ014
12.5
140,000
9.8
BELT
8.6
930
Refer to product data information for futher details.
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
16
• Commercial Product Guide • 2002 •
48/50HJ
Commercial Products
High-Efficiency Rooftop Units
Gas Heating/Electric Cooling or
Electric Heating/Electric Cooling
12 and 15 Nominal Tons
45”
Features
• Listed by ETL and ETL Canada, Certified by ARI
• Dual independent Refrigerant Circuits on all units
• EERs up to 10.8
• Scroll Compressors with Circuit Breaker Overcurrent
Protection
• TXV Refrigerant Control on all Units
• Low Pressure/Loss of Charge Protection, Dual Freeze
Protection and High Pressure Switches
• Variable Pitch LO-MED or HIGH ESP Fan Drives
• Two-Stage Heating and Cooling Operation
• Insulated Cabinet with 500-Hour Salt Spray Protection,
Pre-Painted Galvanized Steel
• Thru-the-Bottom Power and Gas Capability
• Manually Adjustable Outside Air Intake for up to 25%
Outside Air
• 2" Disposable Filters
• Warranty: 1 Year Parts, 5 Year Heat Exchangers with
Extended Compressor, Heat Exchanger, and Full Unit Part
Warranties Available
48HJ Only
• Induced draft combustion with fan proving switch
• IGC board with diagnostics
• Direct spark electronic ignition switch
Factory-Installed Options
• MoistureMi$er™ Dehumidification Package
• Integrated EconoMi$er with CO2 Control Capability
• PremierLink™ DDC Controls
• Apollo Direct Digital Controls
• Coil Material/Coating for Corrosive Environments
86 1/8”
83 1/2”
• Service Option Package:
- Hinged Access Panels
- Non-Fused Disconnect
- Non-powered Convenience Outlet (115v)
• UV-C Lamps
• E-Coat (Coil post-coating)
• Stainless Steel Heat Exchanger (48HJ only)
• Electric Heaters (50HJ only)
Field-Installed Accessories
• Power Exhaust
• Electric Heaters
• Integrated EconoMi$er with CO2 Control Capability
• L.P. Conversion Kits (48HJ only)
• Barometric Relief
• Low Ambient Kits
• Full Perimeter Heavy Gauge Roof Curb
• Programmable Thermostats and Subbases
• Horizontal Adapter Roof Curb
• Glycol Coils (50HJ Only)
• Hail Guard
• CO2 Sensors (Wall or Duct Mounted)
• Commercial Product Guide • 2002 •
17
Performance & Sizing Information
HJ-SINGLE PACKAGED ROOFTOP UNITS 12-15 TONS
GAS/ELECTRIC, HEATING & COOLING 48 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
MODEL
NUMBER*
NOM
TONS
NOM
CFM
NET
COOLING
(Btuh)
NO.
COOLING
STAGES
EER
HEAT
INPUT
(Btuh)
HEAT
OUTPUT
(Btuh)
STEADY
STATE
%
NO.
HEATING
STAGES
WEIGHT
(lbs)
48HJD015
12
3,600
130,000
2
10.6
11.4
230,000
186,300
81
2
48HJF015
12
3,600
130,000
2
10.6
11.4
300,000
243,000
81
2
IPLV
DIMENSIONS (in.)
Length
Width
1,725
86.125
83.5
Height
45
1,725
86.125
83.5
45
48HJD017
15
5,300
180,000
2
10.5
11.4
275,000
222,750
81
2
1,800
86.125
83.5
45
48HJF017
15
5,300
180,000
2
10.5
11.1
360,000
291,600
81
2
1,800
86.125
83.5
45
ELECTRIC/ELECTRIC, HEATING & COOLING 50 SERIES - CONSTANT VOLUME, VERTICAL SUPPLY AND RETURN
MODEL
NUMBER
NOM
TONS
NOM
CFM
NET
COOLING
(Btuh)
NO.
COOLING
STAGES
EER
50HJ015
12
3,600
130,000
2
10.7
11.6
50HJ017
15
5,300
180,000
2
10.8
11.7
IPLV
HEATING CAPACITY (kW)
([email protected] 460/3/60)
WEIGHT
(lbs)
12.13
15/32/55
16.83
32/55/80
TOTAL kW
DIMENSIONS (in.)
Length
Width
1575
86.125
83.5
45
1650
86.125
83.5
45
* 48HJD Low Gas Heat - Standard Aluminized Steel Heat Exchangers
48HJM Low Gas Heat - Optional Stainless Steel Heat Exchangers
48HJF High Gas Heat - Standard Aluminized Steel Heat Exchangers
48HJN High Gas Heat - Optional Stainless Steel Heat Exchangers
Heating Capacities and Operating CFM Ranges are same for Standard Aluminized Steel Heat Exchangers or Optional Stainless Steel Heat Exchangers
48HJD – Low Capacity Heat
48HJF – High Capacity Heat
Rated in
accordance with
ARI Standard
340/360
18
• Commercial Product Guide • 2002 •
Height
Commercial Products
48/50HG
High-Efficiency Rooftop Units
Gas Heating/Electric Cooling or
Electric Heating/Electric Cooling
12 1/2 to 25 Nominal Tons
Features
• EERs up to 11.6
• 15, 17.5 & 20 ton models utilize three electronically and
mechanically independent refrigerant circuits. 12 1/2 & 25 ton
units utilize two electronically and mechanically independent
refrigerant circuits
• Refrigerant metering devices for each circuit are TXV
• Freeze protection on all circuits
• Liquid line filter driers
• Fit up to installed Carrier DP,DR,TJ,HJ roof curbs
• Dedicated vertical or side by side horizontal airflow units
• Vertical airflow units are field convertible to side by side
horizontal airflow
• ComfortLink™ Controller
- Communications
- Scrolling Marquee Display
- Time Schedule
- Space Temperature Sensor capability
- Service Diagnostics
- Installation Run Test capability
- CO2 sensor capability for Demand Control Ventilation
- Reverse Rotation Protection for Compressors
• Hinged Service Access Panels with double wall
construction and tiebacks
• Indoor fan deck slides out for added service convenience
• 0-125° F ambient cooling operation
• Low sound: 8.2 bel (014-024), 8.4 bel (028)
• Single Point electrical service entry. Through the basepan
electrical connection available
• Condenser fan motors are internally protected
• Weather Armor pre-painted galvanized steel cabinet with
baked enamel finish insulated with neoprene-coated fiberglass
48HG Only
• Induced draft combustion system
• Reliable IGC (Integrated gas unit controller) provides system
evaluation and troubleshooting via onboard LED
• Direct Spark Ignition
• Alumagard Coated Turbo-tubular™ Heat Exchanger
Factory-Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Non-Fused Disconnect
Convenience Outlet
30% Filters
Corrosion Protection Options
Alternate motor and high static drives
Fan Status
Barometric Relief
Smoke Detector
Filter Status
CO2 Sensor
Electric Heaters (50HG)
Gear Driven Economizer
Power Exhaust
4" filter track
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
65% Filters
Condensor Coil Hail Guard
Enthalpy Sensor
Differential Enthalpy Sensor
Two-Position Damper
Thermostats and Subbases
Electronic Programmable Thermastat
Fan Status
Barometric Relief
Smoke Detector
Horizontal Kit
Filter Status
CO2 Sensor
Electric Heaters (50HG)
Gear Driven Economizer
Power Exhaust
• Commercial Product Guide • 2002 •
19
Performance & Sizing Information
MODEL
48HG 014
48HG 016
48HG 020
48HG 024
48HG 028
50HG 014
50HG 016
50HG 020
50HG 024
50HG 028
ET
NOMINAL CON
OLING
TONS
CAPACITY
12.5
155,400
15
182,500
17.5
201,300
20
238,200
25
283,600
12.5
155,400
15
182,500
17.5
201,300
20
238,200
25
283,600
EER
IPLV*
11.6
11.5
11.2
11.2
10.4
11.6
11.5
11.2
11.2
10.4
13.2
13.7
12.8
12.4
11
13.2
13.7
12.8
12.4
11
HEATING
CAPACITY
(low/hi)
205,000/242,700
205,000/328,000
205,000/328,000
205,000/328,000
205,000/328,000
0,15,25,50 kW
0,25,50,75 kW
0,25,50,75 kW
0,25,50,75 kW
0,25,50,75 kW
*IPLV values are calculated based on control configuration T.CTL = 2 (2 stage Y1)
MODEL
48HG 014
48HG 016
48HG 020
48HG 024
48HG 028
50HG 014
50HG 016
50HG 020
50HG 024
50HG 028
LENGTH*
(in.)
146/116
146/116
146/116
146/116
146/116
146/116
146/116
146/116
146/116
146/116
WIDTH†
(in.)
86.625
86.625
86.625
86.625
86.625
86.625
86.625
86.625
86.625
86.625
HEIGHT
(in.)
58.125
58.125
58.125
58.125
70.125
58.125
58.125
58.125
58.125
70.125
*Top/Bottom; does not include economizer hood
†Flue extended at 4.25"
20
• Commercial Product Guide • 2002 •
48A
Commercial Products
Single-Package Rooftop Units
Gas Heating/Electric Cooling
Constant Volume or Variable Air Volume
20 to 60 Nominal Tons
48AJ - Constant Volume, Vertical Supply and Return
48AK - Variable Air Volume, Vertical Supply and Return
48AW - Constant Volume, Horizontal Supply and Return
48AY - Variable Air Volume, Horizontal Supply and Return
Features
• Accurately match building loads with up to 6 steps of
compressor unloading
• Dual semi-hermetic compressors with suction & discharge
service valves
• Independent refrigeration circuits for full backup
• EER meets requirements of ASHRAE Standard 90.1-1999
• Dedicated vertical and horizontal discharge configurations
• Constant and variable air volume controls
• Full cable ready DDC controls are standard
• Variable frequency drives standard on variable air volume
models
• External access to VFD display
• Electric unloading standard (VAV)
• Superior airside performance up to 3.8" net ESP
• Gear-driven, low-leak economizer is standard
• Full IAQ capability
• Easily replaces old Carrier rooftops
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
•
Roofcurbs
Barometric relief
Power exhaust
LP conversion kits
Expansion control board for demand limit &
smoke/purge control
Hail guard
Full range of thermostats and sensors
Low ambient kit (-20° F)
IAQ CO2 sensor
LID2B enhanced interface display
Factory-Installed Options
•
•
•
•
•
•
•
•
•
•
•
Staged gas heat (CV only)
Stainless steel heat exchangers
Barometric relief
Powerful centrifugal fan modulating power exhaust
Standard and high efficiency evaporator fan motors
Optional corrosion resistant fin coatings and materials
Electric and pressure unloading packages
Double wall airstream
Smoke detectors
UV-C lamps
VFD bypass
NOTE: Some options may impact agency approvals
• Commercial Product Guide • 2002 •
21
Performance & Sizing Information
22
SIZE
NOMINAL
TONS
NOMINAL
CFM
48A-020
48A-025
48A-027
48A-030
48A-035
48A-040
48A-050
48A-060
20
25
27
30
35
40
50
60
8,000
10,000
11,000
12,000
14,000
16,000
20,000
24,000
GROSS
COOLING
(MBH)
254
302
337
373
402
462
575
710
DIMENSIONS (in.)
LENGTH
WIDTH
HEIGHT
165.08
165.08
165.08
165.08
215.40
215.40
215.40
311.28
88.90
88.90
88.90
88.90
88.90
88.90
88.90
88.00
73.12
73.12
73.12
73.12
73.12
73.12
73.12
73.12
• Commercial Product Guide • 2002 •
48Z
Commercial Products
Features
• Constant volume or VAV models
• Up to 9 steps of cooling capacity control
• Multiple Semi-hermetic compressors with suction and
discharge service valves, automatically reversible oil pump,
insert-type crankcase heater, spring isolation
• Available for vertical & horizontal duct configurations
• Compressor protection includes calibrated circuit breaker
overloads, and high and low pressure protection
• Dual independent refrigeration circuits with TXVs
• Intertwined evaporator coils for full-face active operation at
part-load conditions
• Single low speed supply fan
• 2-in. deflection isolation springs on supply fan sled
• Pre-painted galvanized steel casing with 500-hour salt
spray finish
• Hinged panels for service access
• Standard 2-in. filter tracks are field convertible to accept
4-in. filter
• Stainless steel dual sloped condensate pan
• Tuf-Skin Rx™ anti-microbial insulation
• Factory-installed pivoting outdoor air hoods
• Highly reliable induced draft gas heating system with direct
spark ignition (DSI) control system, using the integrated gas
control module for 81% AFUE efficiency
• -20° F low ambient operation (PIC model)
• Will start and run at 120° F
• Listed by ETL and rated in accordance with ARI 340/360
• Standard one-year warranty with extended warranties
available
Single-Package Rooftop Units
Electric Cooling/Gas Heating
Constant Volume or Variable Air Volume
30 to 105 Nominal Tons
•
•
•
•
•
•
•
•
•
•
•
•
•
Non-modulating power exhaust
Modulating power exhaust
Modulating power exhaust with VFD modulation
4 sizes of indoor fan motors
Premium efficiency fan motors
Alternate speed drive sets
30% 2 in. pleated filters
90% bag filters with pre-filters (30-70 ton models)
65% pleated filters (75-105 ton models)
Smoke detectors
115 volt convenience outlets
Double wall construction in airstream of unit
UV-C lamps
NOTE: Some options may impact agency approvals
Field-Installed Accessories
Factory-Installed Options
• PIC: DDC communicating control system, for VAV or CV
unit operation, with all sensors factory-installed; cooling
capacity control via supply air temperature
• Alternate high capacity coils
• Airfoil fans (75-105 ton models)
• Extended chassis with tracks for auxiliary coil
• Re-heat/heat reclaim coils
• Modulating gas heat
• Stainless steel heat exchangers
• Non-fused disconnect
• Variable frequency drive (VAV model)
• Bypass added to VFD (VAV)
• Hot gas bypass
• Cu/Cu condenser coil
• Pre-coated condenser coil
• E-coated (post coat) condenser coil
• Economizer with outdoor air hoods, ultra low leak dampers &
integrated compressor operation
• Barometric relief
•
•
•
•
•
•
•
•
•
Roof curb
Barometric relief
Modulating power exhaust (30-70 ton models)
Hail guard
LP conversion kit
Pressure unloaders (CV)
Communicating programmable thermostats (CV)
Compressor short-cycle protection (CV)
Motormaster® control for 20° F low ambient operation
(CV & VAV, std on PIC)
• Space temperature reset (VAV)
• Two-step demand limit module (VAV)
• Remote VAV control panel (VAV)
• VFD remote display module (VAV, PIC)
• Keypad/display module (HSIO) (PIC)
• CO2 sensors for demand control ventilation (PIC)
• Outdoor air CFM control package (PIC)
• Pressure transducers and thermistors (PIC)
• Space temp sensor with set point adjustment (PIC)
• Commercial Product Guide • 2002 •
23
Performance & Sizing Information
SIZE
NOMINAL
TONS
NOMINAL
CFM
48Z030
48Z035
48Z040
48Z050
48Z055
48Z060
48Z070
48Z075
48Z090
48Z105
30
35
40
50
55
60
70
75
90
105
12,000
14,000
16,000
20,000
22,000
24,000
28,000
30,000
36,000
42,000
HEATING CAPACITY
(INPUT)
LOW
HIGH
325
650
325
650
325
650
325
650
650
975
650
975
650
975
650
975
650
975
650
975
DIMENSIONS (ft-in.)
LENGTH*
22-4
22-4
26-4
26-4
36-7
36-7
39-6
40-10
40-10
40-10
*Vertical Airflow model.
24
• Commercial Product Guide • 2002 •
WIDTH
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
HEIGHT
5-11
5-11
5-11
5-11
5-11
5-11
5-11
6-11
6-11
6-11
48GX,GXN
Commercial Products
High-Efficiency Packaged Units
Gas Heating/Electric Cooling
2 to 5 Nominal Tons
Unit Dimensions
Features
• 12.0 SEER
• R-22 refrigerant
• AFUE up to 81%
• TurboTubular heat exchanger
• Automatic electric pilot ignition with diagnostics
• Monoport inshot burners
• Sound ratings as low as 72 dB
• Weather Armor cabinet design
• Envirotuff™ rustproof base
• Direct drive multi-speed PSC motor
• Vertical discharge condenser air
• Field convertible to downshot airflow
• Scroll compressors
• UL and c-UL
• Copper Tube and aluminum fin condenser and
evaporator coils
• 1 Year warranty on all parts
• 10 Year warranty on compressor
• 15 Year warranty on heat exchangers
• Duct covers standard
• 48GXN Low NOx approved for use in California
Factory-Installed Options
• Louvered outdoor coil protectors
• E-coat (available on special quote only)
• Vinyl coated outdoor coil
• AL indoor coil and CU/CU outdoor coil
• CU/CU indoor and outdoor coil
DIMENSIONS
WEIGHT
LBS.
MODEL
SIZE
48GX
024
48.28
32.72
35.02
290
48GX
48GX
48GX
48GX
48GX
030
036
042
048
060
48.28
48.28
48.28
48.28
48.28
32.72
32.72
44.22
44.22
44.22
39.02
35.02
38.98
38.98
42.98
313
321
382
421
468
LENGTH
IN.
WIDTH
IN.
HEIGHT
IN.
NOTE: All dimensions in inches
Field-Installed Accessories
• Roof Curbs
• Economizers (internal)
• Filter rack (internal)
• Manual air damper
• Pressure switch kit
• LP conversion kit
• High altitude kit
• Hard start kits (single phase)
• Factory thermostats
• Rigging kit for rooftop application
• Louvered grilles
• Commercial Product Guide • 2002 •
25
Performance & Sizing Information
GAS/ELECTRIC 48 SERIES
MODEL
SIZE
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
024040
024060
030040
030060
036060
036090
042060
042090
048090
048115
048130
060090
060115
060130
NOM CAP
TONS
2
2
2 1/2
2 1/2
3
3
3 1/2
3 1/2
4
4
4
5
5
5
CFM @
.5 E.S.P
HIGH
994
994
1111
1111
1325
1325
*1672
*1672
1879
1879
1879
2208
2208
2208
NET CLG
CAP
BTUH
24,000
24,000
30,000
30,000
35,000
35,000
42,000
42,000
48,000
48,000
48,000
58,000
58,000
58,000
SEER
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
GAS INP
RATE
BTUH
40,000
60,000
40,000
60,000
60,000
88,000
60,000
90,000
90,000
115,000
130,000
90,000
115,000
130,000
HEAT CAP
BTUH
31,000
46,000
31,000
46,000
46,000
70,000
47,000
71,000
70,000
92,000
104,000
70,000
92,000
103,000
TEMP RISE
RANGE
F
20-50
35-65
20-50
35-65
25-55
45-75
15-45
35-65
25-55
35-65
40-70
25-55
35-65
40-70
AFUE
(%)
80.1
78.4
80.0
80.1
78.7
79.9
78.7
79.9
78.6
81.1
80.3
78.6
81.1
80.3
SOUND
RATING
BELS
7.2
7.2
7.2
7.2
7.4
7.4
7.4
7.4
8.0
8.0
8.0
7.8
7.8
7.8
*On medium speed tap
ELECTRICAL DATA
VOLT RANGE
MODEL
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
48GX
SIZE
024
030
030
036
036
036
042
042
042
048
048
048
060
060
060
COMPRESSOR
V-PH-Hz
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
CONDENSER
FAN MOTOR
EVAPORATOR POWER SUPPLY FUSE
FAN MOTOR
OR HACR BREAKER
MIN
MAX
RLA
LRA
FLA
FLA
MCA
MOCP
187
187
187
187
187
414
187
187
414
187
187
414
187
187
414
253
253
253
253
253
506
253
253
506
253
253
506
253
253
506
10.3
13.5
9.0
16.7
11.2
5.4
17.9
12.4
6.1
19.5
12.4
5.8
28.8
17.3
9.0
56.0
73.0
63.0
97.0
75.0
37.5
104.0
88.0
44.0
104.0
88.0
44.0
169.0
123.0
62.0
0.8
0.8
0.8
0.8
0.8
0.9
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
2.0
2.1
2.1
3.6
3.6
1.9
4.1
4.1
2.0
4.1
4.1
2.0
6.2
6.2
3.2
15.7
19.8
14.2
25.3
18.4
9.6
28.1
21.2
10.5
30.1
21.2
10.2
43.8
29.4
15.4
25
30
20
40
25
15
45
30
15
45
30
15
60
45
20
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
26
• Commercial Product Guide • 2002 •
48GS,GSN
Commercial Products
Standard-Efficiency Packaged Units
Gas Heating/Electric Cooling
2 to 5 Nominal Tons
Features
Dimensions (in.)
• 10.0 SEER
• R-22 refrigerant
• AFUE of up to 81%
• Envirotuff™ rustproof base with integrated drain
• Easily converted for down or side discharge applications
• Induced-draft combustion and venting
• Multi-speed indoor fan motor
• Vertical condenser fan discharge
• Automatic electric pilot ignition
• Sound Ratings as low as 75 dB
• Copper tube and aluminum fin condenser and evaporator
coils
• UL and c-UL
• Copper tubing
• Wire grille standard
• Duct covers standard
• 1 Year limited product warranty
• 5 Year limited compressor warranty
• 10 Year limited warranty on heat exchanger
• 48GSN Low NOx approved for use in California
MODEL
W
H
D
48GS018-042
48.3
35-39
32.7
48GS048-060
48.3
39-43
44.2
Field-Installed Accessories
• LP gas conversion kits
• Economizers
• Manual outdoor air damper
• Roof curbs
• Filter racks
• High altitude kits
• Compressor anti-cycle timer
• Electronic programmable thermostats
• High and low pressure switches
• Rigging kits for rooftop applications
• Crankcase heaters
• Factory thermostats
• Louvered grilles
Factory-Installed Options
• Louvered grilles
• AL indoor coil and CU/CU outdoor coil
• CU/CU indoor coils, CU/CU outdoor coils
• E-coat (available on special quote only)
• Commercial Product Guide • 2002 •
27
Performance & Sizing Information
GAS/ELECTRIC 48 SERIES
MODEL
NOMINAL
TONS
ARI COOLING
Btuh
PERFORMANCE
SEER
48GS-0180403
48GS-0240403
48GS-0240603
48GS-0300403
48GS-0300405
48GS-0300603
48GS-0300605
48GS-0360603
48GS-0360605
48GS-0360606
48GS-0360903
48GS-0360905
48GS-0360906
48GS-0420603
48GS-0420605
48GS-0420606
48GS-0420903
48GS-0420905
48GS-0420906
48GS-0480903
48GS-0480905
48GS-0480906
48GS-0481153
48GS-0481155
48GS-0481156
48GS-0481303
48GS-0481305
48GS-0481306
48GS-0600903
48GS-0600905
48GS-0600906
48GS-0601153
48GS-0601155
48GS-0601156
48GS-0601303
48GS-0601305
48GS-0601306
1.5
2.0
2.0
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.5
3.5
3.5
3.5
3.5
3.5
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
18,000
24,600
24,600
28,800
28,800
28,800
28,800
34,400
34,400
34,400
34,400
34,400
34,400
42,000
42,000
42,000
42,000
42,000
42,000
46,500
46,500
46,500
46,500
46,500
46,500
46,500
46,500
46,500
60,000
60,000
60,000
60,000
60,000
60,000
60,000
60,000
60,000
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
CFM @
HEATING
.S.P. HIGH
INPUT (MBH) .5OE
PERATING
40
633
40
1125
60
1125
40
1125
40
1125
60
1125
60
1125
60
1465
60
1465
60
1465
90
1465
90
1465
90
1465
60
1424
60
1424
60
1424
90
1424
90
1424
90
1424
90
1922
90
1922
90
1922
115
1922
115
1922
115
1922
130
1922
130
1922
130
1922
90
2124
90
2124
90
2124
115
2124
115
2124
115
2124
130
2124
130
2124
130
2124
WEIGHT
SOUND
249
280
280
280
280
280
280
314
314
314
314
314
314
355
355
355
355
355
355
415
415
415
415
415
415
415
415
415
450
450
450
450
450
450
450
450
450
75
75
75
80
80
80
80
ELECTRICAL DATA
UNIT
SIZE
48GS
018
024
030
036
042
048
060
V-Ph-Hz
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
VOLTAGE RANGE
MIN
187
187
187
187
187
187
414
187
187
414
197
187
414
187
187
414
MAX
253
253
253
253
253
253
506
253
253
506
253
253
506
253
253
506
COMPRESSOR
RLA
9.0
12.8
14.4
8.3
15.1
10.9
5.8
18.6
10.7
5.3
25.3
14.6
7.3
28.9
18.6
8.5
LRA
45.0
61.0
73.0
68.0
81.0
78.0
40.0
105.0
85.0
42.0
131.0
108.0
47.5
147.0
125.0
66.5
COND
FAN
MOTOR
INDOOR
FAN
MOTOR
FLA
0.8
0.8
0.8
0.8
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
FLA
1.8
2.0
2.0
2.0
3.6
3.6
1.9
3.8
3.8
2.0
3.8
3.8
2.0
6.2
6.2
3.2
POWR SUPPLY
FUSE OR HACR
BRKR
MCA
13.9
18.8
20.8
13.2
24.1
18.8
10.1
28.9
18.8
9.5
37.0
23.7
12.0
43.9
31.1
14.7
MOCP
20
30
30
20
35
25
15
45
25
15
60
35
15
60
45
20
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
28
• Commercial Product Guide • 2002 •
48GP,GPN
Commercial Products
High-Efficiency Single-Package Units
Gas Heating/Electric Cooling
2 to 5 Nominal Tons
ComfortHeat™ Technology Featuring
Factory-Installed Options
•
•
•
•
•
•
• Copper fin and coil coatings available
• Vinyl coated condenser fins
Better dehumidification; up to 30 times better
Economical constant fan; about $30 a year
Improved indoor air quality
SEER Boost; up to 12.7 SEER
Selectable CFM: High, Medium, Low
Constant CFM at higher static pressures; at least 350 CFM
at up to .9 ESP
• Single-phase only
Warranty
• 5-Year warranty on parts
• 10-Year warranty on compressor
• 15-Year non-prorated warranty on heat exchanger
Field-Installed Accessories
Features
• 12 SEER
• Puron™ (R-410A) refrigerant
• AFUE of up to 81%
• Envirotuff™ rust proof base with integrated drain
• Easily converted for down or side discharge applications
• Induced-draft combustion and venting
• Multi-speed indoor fan motor
• Vertical condenser fan discharge
• Automatic electric pilot ignition
• Sound ratings as low as 72 dB
• Copper tube and aluminum fin condenser and
evaporator coils
• UL and c-UL
• Louvered grille, pressure switches, duct covers
and filter drier standard
• 48GPN Low NOx approved for use in California
• 3-phase products available (not with variable speed motors)
• Economizer
• Relief dampers
• Manual air damper (25% open)
• Filter rack
• Roof curbs (8" and 14")
• Square-to-round duct transition kit
• Programmable and non-programmable thermostats; to include
Thermidistat™ control
• Crankcase heater
• Compressor hard start kit (for use on single-phase units only)
• LP conversion kit
• High altitude kit
• Low ambient kit (Motormaster® II Control)
• Solid-state Time Guard® II device; not needed with
corporate thermostats
• Commercial Product Guide • 2002 •
29
Performance & Sizing Information
GAS/ELECTRIC 48 SERIES
2
2
2 1/2
CFM AT
.5 ESP
(HIGH)
956
956
1061
NET CLG
CAP
(BTUH)
24,000
24,000
29,000
2 1/2
3
3
3 1/2
3 1/2
4
4
4
5
5
5
1061
1243
1243
*1630
*1630
1793
1793
1793
1905
1905
1905
29,000
35,000
35,000
41,000
41,000
48,000
48,000
48,000
59,000
59,000
59,000
MODEL
SIZE
NOM CAP
(TONS)
48GP
48GP
48GP
024040
024060
030040
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
030060
036060
036090
042060
042090
048090
048115
048130
060090
060115
060130
12.0
12.0
12.0
GAS INP
RATE
(BTUH)
40,000
60,000
40,000
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
12.0
60,000
60,000
88,000
60,000
90,000
90,000
115,000
130,000
90,000
115,000
130,000
SEER
RISE
HEAT CAP TERMAPNG
E
(BTUH)
(° F)
31,000
20-50
46,000
35-65
31,000
20-50
46,000
46,000
70,000
47,000
71,000
70,000
92,000
104,000
70,000
92,000
103,000
35-65
25-55
45-75
15-45
35-65
25-55
35-65
40-70
25-55
35-65
40-70
80.1
78.4
80.0
SOUND
RATING
(dB)
72
72
72
80.1
78.7
79.9
78.7
79.9
78.6
81.1
80.3
78.6
81.1
80.3
72
73
73
73
73
78
78
78
78
78
78
AFUE
(%)
*Medium setting.
ELECTRICAL DATA (CHECK PRODUCT DATA FOR VARIABLE SPEED DATA)
MODEL
SIZE
V-PH-Hz
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
48GP
024
030
030
036
036
036
042
042
042
048
048
048
060
060
060
208/230-1-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
VOLT RANGE
Min
187
187
187
187
187
414
187
187
414
187
187
414
187
187
414
Max
253
253
253
253
253
506
253
253
506
253
253
506
253
253
506
COMPRESSOR
RLA
13.5
14.7
9.6
15.4
12.2
5.1
18.6
13.8
6.3
20.5
14.7
6.5
27.6
18.1
9.0
LRA
61.0
73.0
63.0
83.0
77.0
35.0
105.0
86.0
39.0
109.0
91.0
46.0
158.0
137.0
62.0
CONDENSER
FAN MOTOR
FLA
0.8
0.8
0.8
0.8
0.8
0.8
1.6
1.6
0.9
1.6
1.6
0.9
1.6
1.6
0.9
EVAPORATOR
FAN MOTOR
FLA
2.0
2.1
2.1
3.6
3.6
1.9
4.1
4.1
2.0
4.1
4.1
2.0
6.2
6.2
3.2
POWER SUPPLY FUSE
OR HACR BREAKER
MCA
MOCP
19.7
30
21.3
35
14.9
20
23.7
35
19.7
30
9.1
15
28.3
45
22.3
35
10.8
15
31.3
50
24.1
35
11.0
15
42.3
60
30.4
45
15.4
20
Rated in
accordance with
ARI Standard 210
30
• Commercial Product Guide • 2002 •
50A
Commercial Products
Single-Package Rooftop Units
Electric Heating/Electric Cooling
Constant Volume or Variable Air Volume
20 to 60 Nominal Tons
50AJ - Constant Volume, Vertical Supply and Return
50AK - Variable Air Volume, Vertical Supply and Return
50AW - Constant Volume, Horizontal Supply and Return
50AY - Variable Air Volume, Horizontal Supply and Return
Features
• Accurately match building loads with up to 6 steps of
compressor unloading
• Dual semi-hermetic compressors with suction & discharge
service valves
• Dual independent refrigeration circuits for full backup
• EER meets requirements of ASHRAE Standard 90.1-1999
• Dedicated vertical and horizontal discharge configurations
• Constant and variable air volume controls
• Full cable ready DDC controls are standard
• Variable frequency drives standard on variable air volume
models
• External access to VFD display
• Electric unloading standard (VAV)
• Superior airside performance up to 3.8" net ESP
• Low-leak gear-driven economizer is standard
• Easily replaces old Carrier DF, DD, DL series rooftops
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
•
•
Roof curbs
Barometric relief
Power exhaust
Electric heaters
LP conversion kits
Electronic expansion board for demand limit &
smoke/purge control
Hail guard
Full range of thermostats and sensors
Low ambient kit (-20° F)
IAQ CO2 sensor
LID2B remote software access device
Factory-Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
Stainless steel heat exchangers
Electric heaters
Barometric relief
Powerful centrifugal fan modulating power exhaust
Standard and high efficiency evaporator fan motors
Optional corrosion resistant fin coatings and materials
E-Coat (coil post coating)
Electric unloading (CV)
Double wall airstream
Smoke detectors
UV-C lamps
VFD bypass
NOTE: Some options may impact agency approvals
• Commercial Product Guide • 2002 •
31
Performance & Sizing Information
32
SIZE
NOMINAL
TONS
NOMINAL
CFM
50A-020
50A-025
50A-027
50A-030
50A-035
50A-040
50A-050
50A-060
20
25
27
30
35
40
50
60
8,000
10,000
11,000
12,000
14,000
16,000
20,000
24,000
GROSS
COOLING
(MBH)
254
302
337
373
402
462
575
710
HEATING
CAPACITY ELECTRIC
(kW)
0, 36, 72
0, 36, 72
0, 36, 72
0, 36, 72
0, 36, 72
0, 36, 72
0, 36, 72
0, 54, 108
DIMENSIONS (in.)
LENGTH
WIDTH
HEIGHT
165.08
165.08
165.08
165.08
215.40
215.40
215.40
311.28
88.90
88.90
88.90
88.90
88.90
88.90
88.90
88.00
73.12
73.12
73.12
73.12
73.12
73.12
73.12
73.12
• Commercial Product Guide • 2002 •
50Z
Commercial Products
Features
• Constant volume or VAV models
• Up to 9 steps of cooling capacity control
• Multiple Semi-hermetic compressors with suction and
discharge service valves, automatically reversible oil pump,
insert-type crankcase heater, spring isolation
• Available for vertical & horizontal duct configurations
• Compressor protection includes calibrated circuit breaker
overloads, and high and low pressure protection
• Dual independent refrigeration circuits with TXVs
• Intertwined evaporator coils for full-face active operation at
part-load conditions
• Single low speed supply fan
• 2-in. deflection isolation springs on supply fan sled
• Pre-painted galvanized steel casing with 500-hour salt
spray finish
• Hinged panels for service access
• Standard 2-in. filter tracks are field convertible to accept
4-in. filters
• Stainless steel dual sloped condensate pan
• Tuf-Skin Rx™ anti-microbial insulation
• Factory-installed pivoting outdoor air hoods
• -20° F low ambient operation (PIC model)
• Will start and run at 120° F
• Listed by ETL and rated in accordance with ARI 340/360
• Standard one-year warranty with extended warranties
available
Single-Package Rooftop Units
Electric Heating/Electric Cooling
Constant Volume or Variable Air Volume
30 to 105 Nominal Tons
•
•
•
•
•
•
•
•
•
Premium efficiency fan motors
Alternate speed drive sets
30% 2 in. pleated filters
90% bag filters with pre-filters (30-70 ton models)
65% pleated filters (75-105 ton models)
Smoke detectors
115 volt convenience outlets
Double wall construction in airstream of unit
UV-C lamps
NOTE: Some options may impact agency approvals
Factory-Installed Options
• PIC: DDC communicating control system, for VAV or CV
unit operation, with all sensors factory-installed; cooling
capacity control via supply air temperature
• Alternate high capacity coils
• Airfoil fans (75-105 ton models)
• Extended chassis with tracks for auxiliary coil
• Re-heat/heat reclaim coils
• Non-fused disconnect
• Hot water heat
• Variable frequency drive (VAV model)
• Bypass added to VFD (VAV)
• Hot gas bypass
• Cu/Cu condenser coil
• Pre-coated condenser coil
• E-coated (post coat) condenser coil
• Economizer with outdoor air hoods, ultra low leak dampers &
integrated compressor operation
• Barometric relief
• Non-modulating power exhaust
• Modulating power exhaust
• Modulating power exhaust with VFD modulation
• 4 sizes of indoor fan motor
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
Roof curb
Barometric relief
Modulating power exhaust (30-70 ton models)
Hail guard
Electric heaters
Pressure unloaders (CV)
Communicating programmable thermostats (CV)
Compressor short-cycle protection (CV)
Motormaster® control for 20° F low ambient operation
(CV & VAV, std on PIC)
• Space temperature reset (VAV)
• Two-step demand limit module (VAV)
• Remote VAV control panel (VAV)
• VFD remote display module (VAV, PIC)
• Keypad/display module (HSIO) (PIC)
• CO2 sensors for demand control ventilation (PIC)
• Outdoor air CFM control package (PIC)
• Pressure transducers and thermistors (PIC)
• Space temp sensor with set point adjustment (PIC)
• Commercial Product Guide • 2002 •
33
Performance & Sizing Information
SIZE
NOMINAL
TONS
NOMINAL
CFM
50Z030
50Z035
50Z040
50Z050
50Z055
50Z060
50Z070
50Z075
50Z090
50Z105
30
35
40
50
55
60
70
75
90
105
12,000
14,000
16,000
20,000
22,000
24,000
28,000
30,000
36,000
42,000
HEATING CAPACITY
(kW)
36
36
36
36
36
36
36
108
108
108
72
72
72
72
72
72
72
216
216
216
108
108
108
108
108
108
108
-
DIMENSIONS (ft-in.)
LENGTH*
20-9
20-9
24-9
24-9
33-1
33-1
36-1
39-6
39-6
39-6
*Vertical airflow model.
34
• Commercial Product Guide • 2002 •
WIDTH
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
7-8
HEIGHT
5-11
5-11
5-11
5-11
5-11
5-11
5-11
6-11
6-11
6-11
50SX
Commercial Products
High-Efficiency Small Packaged Units
Electric Heating/Electric Cooling
2 to 5 Nominal Tons
Features
• Up to 12.0 SEER
• R-22 refrigerant
• Scroll compressors on all sizes
• Warranty - 1 year parts, 10 year compressor
• Three-speed direct drive indoor fan motors
• Foil faced, cleanable insulation
• Non-corrosive sloped condensate pan
• Condenser coil grille
• Easy to convert packaged units
• UL and c-UL
• Sound levels as low as 8 bels
Factory-Installed Options
• Commercial grade base rails
• Copper fin/copper tube coils
• E-coat coils
Base Unit Dimensions
(Without Base Rail)
MODEL
NUMBERS
DEPTH
LENGTH
HEIGHT
50SX024-036
36.8
43.7
28.1
50SX042-060
36.8
43.7
34.1
NOTE: All dimensions in inches
Field-Installed Accessories
• Electric heaters
• Roof curbs
• Low ambient kit — 0 degree F operation
• One inch filter with rack
• 30% Open manual outdoor air damper
• Compressor anti-cycle timer
• Electronic programmable thermostat
• High and low pressure switch
• Duct covers
• Commercial Product Guide • 2002 •
35
Performance & Sizing Information
ELECTRIC/ELECTRIC 50 SERIES
MODEL
NUMBER
NET
COOLING
(Btuh)
NOMINAL
TONS
SEER
DRY COIL @
.5 E.S.P. CFM
HIGH
OPERATING
WEIGHT
(lbs)
SOUND
(dB)
50SX024
2.0
23,400
12.0
1150
270
80
50SX030
2.5
29,800
12.0
1150
273
80
50SX036
3.0
36,800
12.0
1500
291
80
50SX042
3.5
41,500
12.0
1780
309
80
50SX048
4.0
47,500
12.0
1850
340
82
50SX060
5.0
60,000
11.0
2000
359
82
NOTE: Operating weight does not include base rails
ELECTRICAL DATA
MAXIMUM
WIRE
LENGTH
(ft)
30
12
75
22.8
30
10
100
2.8
25.1
30
10
95
2.8
17.8
25
12
70
0.8
1.4
9.0
10
14
100
104.0
1.4
3.1
29.5
45
10
80
88.0
1.4
3.1
21.9
30
10
60
6.8
44.0
0.8
1.6
10.9
15
14
100
253
26.4
129.0
1.4
7.2
41.6
60
6
100
253
15.0
99.0
1.4
7.2
27.4
40
10
80
V-PH-HZ
MIN
MAX
RLA
024
208/203-1-60
187
253
12.9
030
208/230-1-60
187
253
208/230-1-60
187
208/230-3-60
187
460-3-60
036
042
048
060
POWER SUPPLY
FUSE OR
HACR BRKR
AWG 60 C
MINIMUM
WIRE
VOLTAGE
RANGE
UNIT
SIZE
50SX
COMPRESSOR
OFM
IFM
LRA
FLA
FLA
MCA
MOCP
62.5
1.4
2.0
19.5
15.0
76.0
1.4
2.6
253
16.7
95.0
1.4
253
10.9
75.0
1.4
414
506
5.4
40.0
208/230-1-60
187
253
20.0
208/230-3-60
187
253
13.9
460-3-60
414
506
208/230-1-60
187
208/230-3-60
187
460-3-60
414
506
8.2
49.5
0.8
2.3
13.4
20
14
100
208/230-1-60
187
253
32.1
169.0
2.1
7.2
49.4
60
6
100
208/230-3-60
187
253
19.3
123.0
2.1
7.2
33.4
50
8
90
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
36
• Commercial Product Guide • 2002 •
50ZP
Commercial Products
Standard-Efficiency Single-Package Units
Electric Heating/Electric Cooling
2 to 5 Nominal Tons
Performance Data
Features
• 10 SEER
• R-22 refrigerant
• Improved fan blade with lower sound levels
• Warranty — 1 year parts, 5 year compressor
• Louvered metal panel for condenser coil protection
• Easy installation design
- Starter collars
- Cartridge style drop-in heaters
- Single point electrical hook-up
- Single footprint all sizes
- Built-in hand holds
• Dedicated side discharge
• Light-weight compact construction
• Weather Armor cabinet
• Corrosion-proof single piece base
• Sloped non-corrosive drain
• Through-the-top service access
• UL, c-UL and N.O.M. certified
NET COOLING
CAPACITY
22,800
30,000
34,200
40,000
46,000
57,000
50ZP
024
030
036
042
048
060
SEER
10
10
10
10
10
10
CABINET DIMENSIONS
MODEL SIZE HEIGHT LENGTH WIDTH
IN.
IN.
IN.
50ZP
50ZP
50ZP
50ZP
50ZP
50ZP
024
030
036
042
048
060
22
22
22
30
30
34
51
51
51
51
51
51
32
32
32
32
32
32
CFM @ .5 ESP
ON HIGH
1115
1115
1297
1510
1799
2052
OPERATING
WEIGHT
LBS.
SOUND
(dB)
222
236
250
297
310
350
77
81
81
81
81
83
Field-Installed Accessories
• Electric heaters
• Programmable thermostats
• Non-programmable thermostats
• Compressor anti-cycle timer
• High and low pressure switches
• Duct covers
• Commercial Product Guide • 2002 •
37
Performance & Sizing Information
ELECTRICAL DATA
UNIT
50ZP
NOMINAL
VOLTAGE
(V-PH-HZ)
VOLTAGE
RANGE
MIN
MAX
COMPRESSOR
RLA
LRA
ELECTRIC HEAT
POWER SUPPLY
DISCONNECT
SIZE
OFM
IFM
FLA
FLA
NOMINAL
kW
kW
FLA
MCA
MOCP
FLA
LRA
--/-18.1/20.8
36.1/41.7
16.9/16.9
25.6/29.0
48.1/55.1
20/20
30/30
50/60
16/16
24/27
44/51
68
024
208/230-1-60
187
254
10.9
61.0
0.9
2.4
--/-3.8/5.0
7.5/10.0
030
208/230-1-60
187
254
15.2
69.4
1.5
2.4
--/-3.8/5.0
7.5/10.0
11.3/15.0
--/-18.1/20.8
36.1/41.7
54.2/62.5
22.9/22.9
25.6/29.0
48.1/55.1
70.7/81.1
30/30
30/30
50/60
80/90
22/22
24/27
44/51
65/75
79
208/230-1-60
187
254
15.9
86.0
1.5
2.8
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
24.3/24.3
26.1/29.5
48.6/55.6
71.2/81.6
93.6/107.7
30/30
30/30
50/60
80/90
100/110
23/23
24/27
45/51
66/75
86/99
92
208/230-3-60
187
254
8.9
64.5
1.5
2.8
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
17.6/17.6
17.6/18.5
29.6/33.6
42.6/48.6
55.6/63.6
20/20
20/20
30/35
45/50
60/70
17/17
17/17
27/31
39/45
51/59
88
208/230-1-60
187
254
18.5
97.6
1.5
2.8
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
27.4/27.4
27.4/29.5
48.6/55.6
71.2/81.6
93.8/107.7
35/35
35/35
50/60
80/90
100/110
26/26
26/27
45/51
66/75
86/99
107
208/230-3-60
187
254
10.9
73.0
1.5
2.8
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
17.9/17.9
17.9/18.5
29.6/33.6
42.6/48.6
55.6/63.6
25/25
25/25
30/35
45/50
60/70
17/17
17/17
27/31
39/45
51/59
83
208/230-1-60
187
254
21.3
107.0
1.5
4.2
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
32.3/32.3
32.3/32.3
50.4/57.3
72.9/83.4
95.5/109.4
40/40
40/40
60/60
80/90
100/110
31/31
31/31
46/53
67/77
88/101
121
208/230-3-60
187
254
12.3
73.0
1.5
4.2
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
21.1/21.1
21.1/21.1
31.3/35.3
44.3/50.4
57.4/65.4
25/25
25/25
35/40
45/60
60/70
21/21
21/21
29/32
41/46
53/60
87
208/230-1-60
207
254
26.9
128.0
1.4
6.2
-5.0
10.0
15.0
20.0
-20.8
41.7
62.5
83.3
41.2
41.2
59.8
85.9
111.9
50
50
60
90
125
40
40
55
79
103
141
208/230-3-60
187
254
17.7
128.0
1.4
6.2
--/-3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
--/-10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
29.7/29.7
29.7/29.7
33.8/37.8
46.8/52.9
59.9/67.9
35/35
35/35
35/40
50/60
60/70
29/29
29/29
31/35
43/49
55/62
146
460-3-60
414
508
9.0
63.0
0.7
3.2
-5.0
10.0
15.0
20.0
-6.0
12.0
18.0
24.1
15.2
15.2
19.0
26.6
34.1
20
20
20
30
35
15
15
18
24
31
71
036
042
048
060
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
38
• Commercial Product Guide • 2002 •
50GS
Commercial Products
Standard-Efficiency Single-Package Units
Electric Heating/Electric Cooling
1 1/2 to 5 Nominal Tons
Features
Field-Installed Accessories
• 10 SEER
• R-22 refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Multi-speed indoor fan motor
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound ratings as low as 75 dB
• Copper tube/aluminum fin condenser and
evaporator coils
• UL and c-UL
• Copper tubing
• Wire grille standard
• 3-phase units available
• Economizer
• Manual air damper (25% open)
• Filter rack
• Louvered grille
• Electric heaters
• Roof curbs (8-in. and 14-in.)
• Square-to-round duct transition kit
• Programmable and non-programmable thermostats
• Crankcase heater
• Compressor hard start kit (for use on
single-phase units only)
• Low ambient kit (Motormaster® II control)
• Solid-state Time Guard® II device; not
required on corporate thermostats
• High and low pressure switches
Factory-Installed Options
• Copper fin and coil coatings available
• Vinyl coated condenser fins
• Louver grille
Warranty
• 1-year warranty on parts
• 5-year warranty on compressor
• Extended warranties available
• Commercial Product Guide • 2002 •
39
Performance & Sizing Information
MODEL
NUMBER
NOMINAL
TONS
50GS018
50GS024
50GS030
50GS036
50GS042
50GS048
50GS060
1 1/2
2
2 1/2
3
3 1/2
4
5
NET COOLING
CAPACITY
(Btuh)
18,000
24,600
28,800
34,400
42,000
46,500
60,000
PERFORMANCE
SEER
[email protected]
.5 ESP HIGH
10
10
10
10
10
10
10
503
1000
1000
1322
1360
1845
2041
OPERATING
WEIGHT
(lbs)
254
260
258
262
294
324
389
SOUND
(dB)
75
75
75
80
80
80
80
50GS ELECTRICAL DATA
UNIT 50GS
SIZE
VOLTAGE RANGE
COMPRESSOR
OFM
IFM
FLA
FLA
Min
Max
RLA
LRA
018
208/230-1-60
187
253
9
45
0.80
2
024
208/230-1-60
187
253
13
61
1
2
208/230-1-60
187
253
14
73
1
2
208/230-3-60
187
253
8
68
1
2
208/230-1-60
187
253
15
81
1
4
208/230-3-60
187
253
11
78
1
4
460-3-60
414
506
6
40
1
2
208/230-1-60
187
253
19
105
2
4
208/230-3-60
187
253
11
85
2
4
460-3-60
414
506
5
42
1
2
208/230-1-60
197
253
25
131
2
4
208/230-3-60
18 7
253
15
108
2
4
460-3-60
414
506
7
48
1
2
208/230-1-60
187
253
29
147
2
6
208/230-3-60
187
253
19
125
2
6
460-3-60
414
506
9
67
1
3
030
036
042
048
060
ELECTRIC HEAT
POWER SUPPLY
V-PH-HZ
Nominal kW
FLA
MCA
MOCP
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
5.0
10.0
15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
6.0
12.0
18.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
6.0
12.0
18.0
24.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
6.0
12.0
18.0
24.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
6.0
12.0
18.0
24.0
13.9/13.9
24.8/28.3
47.4/54.3
18.8/18.8
25.1/28.5
47.6/54.6
20.8/20.8
25.1/28.5
47.6/54.6
70.2/80.6
20/20
25/30
50/60
25/25
25/30
50/60
25/25
25/30
50/60
80/90
20/20
20/20
30/35
45/50
30/30
30/30
50/60
80/90
25/25
25/25
30/35
45/50
15
15
20
25
35/35
35/35
60/60
90
100/110
25/25
25/25
35/40
45/60
60/70
15
15
20
30
35
50/50
50/50
60/60
90
100/125
30/30
30/30
35/40
50/60
60/70
15
15
20
30
35
60/60
60/60
60/70
90
100/125
40/40
40/40
40/40
50/60
70/70
20
20
20
30
35
15.5/17.5
28.6/32.6
41.6/47.6
23.1/23.1
26.1/29.5
48.6/55.6
71.2/81.6
17.8/17.8
17.8/18.5
29.6/33.6
42.6/48.6
9.5
9.5
16.8
24.3
28.7/28.7
28.7/31.0
50.1/57.1
72.7/83.1
95.3/109.2
18.8/18.8
18.8/18.8
18.8/35.1
44.1/50.1
57.0/65.0
9.4
10.0
17.5
25.1
32.6
38.7/38.7
38.7/38.7
51.4/58.3
73.9/84.4
96.5/110.4
25.4/25.4
25.4/25.4
32.3/36.3
45.3/51.4
58.2/66.2
12.5
12.5
17.9
25.4
32.9
45.0/45.0
45.0/45.0
53.6/60.6
76.2/86.6
98.8/112.7
32.2/32.2
32.2/32.2
34.6/38.6
47.6/53.6
60.5/68.5
14.9
14.9
19.0
26.6
34.1
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
40
• Commercial Product Guide • 2002 •
50GL
Commercial Products
High-Efficiency Single-Package Units
Electric Heating/Electric Cooling
2 to 5 Nominal Tons
ComfortHeat™ Technology Featuring
Factory-Installed Options
•
•
•
•
•
•
• Copper fin and coil coatings available
• Vinyl coated condenser fins
Better dehumidification; up to 30 times
Economical constant fan; about $30 a year
Improved indoor air quality
SEER Boost; up to 12.7 SEER
Selectable CFM: High, Medium, Low
Constant CFM at higher static pressures; at least 350 CFM at
up to .9 ESP
• Single-phase only
Warranty
• 5-year warranty on parts
• 10-year warranty on compressor
• Extended warranties available
Field-Installed Accessories
Features
• 12.0 SEER
• Puron™ (R-410A) refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Multi-speed indoor fan motor
• Louvered grille, pressure switches, duct covers and
filter drier standard
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound ratings as low as 72 dB
• Copper tube/aluminum fin condenser and
evaporator coils
• Scroll compressor
• UL and c-UL
• Copper tubing
• 3-phase product available
• Economizer
• Manual air damper (25% open)
• Filter rack
• Electric heaters
• Roof curbs (8" and 14")
• Square-to-round duct transition kit
• Programmable and non-programmable thermostats to include
Thermidistat™ control
• Crankcase heater
• Compressor hard start kit (for use on single-phase units only)
• Low ambient kit (Motormaster® II control)
• Solid-state Time Guard® II device; not required on
corporate thermostats
• Commercial Product Guide • 2002 •
41
Performance & Sizing Information
MODEL
NUMBER
NOMINAL
TONS
50GL024
50GL030
50GL036
50GL042
50GL048
50GL060
2
2 1/2
3
3 1/2
4
5
NET COOLING PERFORMANCE
CAPACITY
SEER
24,000
29,000
35,000
41,000
48,000
59,000
12
12
12
12
12
12
[email protected]
.5 ESP HIGH
884
988
1196
1593*
1804
2122
OPERATING
WEIGHT
(lbs)
270
291
299
321
326
399
SOUND
(dB)
72
72
72
73
78
76
*Medium setting.
50GL ELECTRICAL DATA (check Product Data for variable speed data)
VOLTAGE RANGE
UNIT 50GL
SIZE
V-PH-HZ
024
COMPRESSOR
OFM
IFM
042
048
060
POWER SUPPLY
Min
Max
RLA
LRA
FLA
FLA
Nominal kW*
FLA
MCA
Max Fuse
or CRCT
Breaker
MOCP
208/230-1-60
187
253
13.5
61.0
0.8
2.0
-/3.8/5.0
7.5/10.0
-/18.1/20.8
36.1/41.7
19.7/19.7
25.1/28.5
47.6/54.6
25/25
25/30
50/60
-
208/230-1-60
187
253
14.7
73.0
0.8
2.1
-/3.8/5.0
7.5/10.0
-/18.1/20.8
36.1/41.7
21.3/21.3
25.2/28.7
47.8/54.7
25/25
25/30
50/60
-
208/230-3-60
187
253
9.6
63.0
0.8
2.1
-/3.8/5.0
7.5/10.0
-/10.4/12.0
20.8/24.1
14.9/14.9
15.7/17.7
28.7/32.7
20/20
20/20
30/35
-
208/230-1-60
187
253
15.4
83.0
0.8
3.6
-/3.8/5.0
7.5/10.0
11.3/15.0
-/18.1/20.8
36.1/41.7
54.2/62.5
23.7/23.7
27.1/30.5
49.8/58.6
72.2/82.5
30/30
30/30
50/60
-
80/90
208/230-3-60
187
253
12.2
77.0
0.8
3.6
-/3.8/5.0
7.5/10.0
11.3/15.0
-/10.4/12.0
20.8/24.1
31.3/36.1
19.7/19.7
19.7/19.7
30.6/34.5
43.6/49.6
25/25
25/25
35/35
45/50
-
460-3-60
414
506
5.1
35.0
0.8
1.9
5.0
10.0
15.0
6.0
12.0
18.0
9.1
9.9
17.4
24.9
15
15
20
25
-
208/230-1-60
187
253
18.6
105.0
1.6
4.1
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
28.2/28.2
28.2/31.2
50.3/57.2
72.6/83.3
95.4/109.3
35/35
35/35
60/60
-
100/110
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
22.2/22.2
22.2/22.2
31.2/35.2
44.2/50.2
57.1/65.1
30/30
30/30
35/40
45/60
-
60/70
030
036
ELECTRIC HEAT
-
208/230-3-60
187
253
13.8
88.0
1.6
4.1
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
460-3-60
414
506
6.3
39.0
0.8
2.0
5.0
10.0
15.0
20.0
6.0
12.0
18.0
24.1
10.7
10.7
17.5
25.1
32.5
15
15
20
30
35
-
208/230-1-60
187
253
20.5
109.0
1.6
4.1
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
31.3/31.3
31.3/31.3
50.3/57.2
72.8/83.3
95.4/109.3
40/40
40/40
60/60
-
80/90
100/110
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
24.1/24.1
24.1/24.1
31.2/35.2
44.2/50.2
57.1/85.1
30/30
30/30
35/40
45/60
-
60/70
208/230-3-60
187
253
14.7
91.0
1.6
4.1
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
460-3-60
414
506
6.5
46.0
0.9
2.0
5.0
10.0
15.0
20.0
6.0
12.0
18.0
24.1
11.0
11.0
17.5
25.1
32.6
15
15
20
30
35
-
208/230-1-60
187
253
27.6
158.0
1.6
6.2
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
42.3/42.3
42.3/42.3
52.9/59.6
75.4/85.9
96.0/111.9
50/50
50/50
60/60
-
80/90
100/125
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
30.4/30.4
30.4/30.4
33.8/37.8
46.9/52.9
59.7/57.7
35/35
35/35
35/40
50/60
-
60/70
6.0
12.0
18.0
24.1
15.4
15.4
19.0
26.6
34.1
20
20
20
30
35
-
208/230-3-60
187
253
18.1
137.0
1.6
6.2
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
460-3-60
414
506
9.0
62.0
0.9
3.2
5.0
10.0
15.0
20.0
*Heater capacity (kW) based on heater voltage of 208v, 240v, & 480v. If power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
42
• Commercial Product Guide • 2002 •
Commercial Products
50GX
High-Efficiency Single-Package Units
Electric Heating/Electric Cooling
2 to 5 Nominal Tons
Features
Field-Installed Accessories
• 12.0 SEER
• R-22 refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Multi-speed indoor fan motor
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound ratings as low as 72 dB
• Copper tube/aluminum fin condenser and evaporator coils
• Scroll compressor
• UL and c-UL
• Copper tubing
• Wire grill standard
• Economizer
• Manual air damper (25% open)
• Filter rack
• Louvered grille
• Electric heaters
• Roof curbs (8" and 14")
• Square-to-round duct transition kit
• Programmable and non-programmable thermostats
• Crankcase heater
• Compressor hard start kit (for use on single-phase units only)
• Low ambient kit (Motormaster® II control)
• Solid-state Time Guard® II device; not required on
corporate thermostats
• High and low pressure switches
• Lifting kit for roof installation
• Thermostats
Factory-Installed Options
• Copper fin and coil coatings available
• Vinyl coated Condenser Fins
• Louvered grille available
Warranty
• 1-year warranty on parts
• 10-year warranty on compressor
• Extended warranties available
• Commercial Product Guide • 2002 •
43
Performance & Sizing Information
50GX024
2
24,000
12
884
OPERATING
WEIGHT
(lbs)
270
50GX030
2 1/2
30,000
12
988
291
72
50GX036
3
35,000
12
1196
299
74
50GX042
3 1/2
42,000
12
*1593
321
74
50GX048
4
48,000
12
1804
326
80
50GX060
5
58,000
12
2122
399
78
MODEL
NUMBER
NOMINAL
TONS
NET COOLING
CAPACITY
PERFORMANCE
SEER
[email protected]
.5 ESP HIGH
SOUND
(dB)
72
*Medium setting.
50GX ELECTRICAL DATA
VOLTAGE RANGE
OFM
IFM
Min
Max
RLA
LRA
FLA
FLA
208/230-1-60
187
253
10.3
56.0
0.8
2.0
208/230-1-60
187
253
13.5
73.0
0.8
2.1
208/230-3-60
187
253
9.0
63.0
0.8
2.1
208/230-1-60
187
253
16.7
97.0
0.8
3.6
208/230-3-60
187
253
11.2
75.0
0.8
3.6
460-3-60
414
506
5.4
37.5
0.9
1.9
208/230-1-60
187
253
17.9
104.0
1.6
4.1
208/230-3-60
187
253
12.4
88.0
1.6
4.1
460-3-60
414
506
6.1
44.0
0.9
2.0
208/230-1-60
187
253
19.5
104.0
1.6
4.1
208/230-3-60
187
253
12.4
88.0
1.6
4.1
460-3-60
414
506
5.8
44.0
0.9
2.0
208/230-1-60
187
253
28.8
169.0
1.6
6.2
208/230-3-60
187
253
17.3
123.0
1.6
6.2
460-3-60
414
506
9.0
62.0
0.9
3.2
UNIT 50GX
SIZE
V-PH-HZ
024
COMPRESSOR
030
036
042
048
060
ELECTRIC HEAT
POWER SUPPLY
Nominal kW
FLA
MCA
MOCP
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
5.0
10.0
15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
6.0
12.0
18.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
21.7/48.1
6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.7/48.1
-/6.0
12.0
18.0
24.1
15.7/15.7
25.1/28.5
47.6/54.6
19.8/19.8
25.2/28.7
47.8/54.7
70.3/80.8
20/20
47.6/54.6
50/60
25/25
25/30
50/60
80/90
20/20
20/20
30/35
80/90
30/30
30/30
50/80
80/90
25/25
25/25
35/35
45/50
15.00
15.00
20.00
25.00
35/35
35/35
60/60
90.00
100/110
25/25
25/25
35/40
45/60
60/70
15.00
15.00
20.00
30.00
35.00
35/35
35/35
60/60
90.00
100/110
25/25
25/25
35/40
45/60
60/70
15.00
15.00
20.00
30.00
35.00
60/60
60/60
60/60
90.00
100/125
35/35
35/35
35/40
50/60
60/70
20.00
20.00
20.00
30.00
35.00
15.7/17.7
28.7/32.7
70.3/80.8
25.3/25.3
27.1/30.5
49.6/56.6
72.2/82.6
18.4/18.4
18.4/19.5
30.6/34.6
43.6/49.6
9.6
9.9
17.4
24.9
28.1/28.1
28.1/31.2
50.3/57.2
72.2/83.3
85.4/109.3
21.2/21.2
21.2/21.2
31.2/35.2
44.2/50.2
57.1/65.1
10.5
10.5
17.5
25.1
32.6
30.1/30.1
30.1/31.2
50.3/57.2
72.8/83.3
95.4/109.3
21.2/21.2
21.2/21.2
31.2/35.2
44.2/50.2
57.1/65.1
10.2
10.2
17.5
25.1
32.6
43.8/43.8
43.8/43.8
52.9/59.8
75.4/85.9
98.0/111.9
29.4/29.4
29.4/29.4
33.8/37.8
46.8/52.9
59.7/67.7
15.4
15.4
19.0
26.6
34.1
Rated in
accordance with
ARI Standard 210
44
• Commercial Product Guide • 2002 •
(60 Hz Only)
50TFQ
Commercial Products
Standard-Efficiency Rooftop
Heat Pump Units
3 to 10 Nominal Tons
3-6 Ton
Features
7.5-10 Ton
• Units are listed by UL and UL, Canada, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor
• Cooling Efficiencies up to 10.2 SEER/9.05 EER
• Heating Efficiencies up to 7.5 HSPF/3.20 COP (High Heat)
• Available in 3, 4, 5, 6, 7.5, 8.5, and 10 Ton Sizes
• Exclusive Cycle-LOC™ anti-compressor cycle protection
• Refrigerant filter drier and accumulator
• Easily convertible airflow (down supply/return standard)
• Internally-sloped composite condensate pan (dual connections)
• Exclusive tool-less, filter access door
• Through-the-Bottom Utility Capability (requires accessory)
• Roll-formed base-rail design with forklift slots and rigging holes
• Two Curbs for entire line
• 2" Disposable Filters
• Low Pressure, High Pressure, Freeze Protection
• Insulated cabinet with 500 hour salt spray prepainted material
• All condenser coils are set on rubber isolators to prevent
contact with unit base pan eliminating galvanic corrosion
• Permanently lubricated fan motors
• Compressor vibration isolation mounting
• All units are tested at the factory
• Low voltage terminal blocks for easy thermostat
wiring connections
• Dual compressors and dual refrigeration circuits on 008-012
Factory-Installed Options
• Alternate Motor(s) and Adjustable Belt Drive Fans
• EconoMi$er2 with CO2 control capability
• Non-Fused Disconnect Switch
• 115-Volt Convenience Outlet
• High Static Indoor Fan Motor (belt drive)
• Apollo Communicating Control
• Corrosion-Resistant Coils (including E-Coat)
• PremierLink™ DDC Controls
• Novar 2024/3051 Controls
Dimensions
TONNAGE
L
W
H
33 5/16
3-6
73 11/16
45
7.5-8.5
87 3/8
57 3/4
41 5/16
10
87 3/8
57 3/4
49 5/16
NOTE: All dimensions are in inches
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Electric Heaters and Single Point Kits
EconoMi$er2 with CO2 control capability
Durablade Economizer
EconoMi$er Enthalpy Controls
EconoMi$er2 w/4-20mA actuator (PremierLink/3rd party control)
25% or 100% Open Two-Position Outdoor Air Dampers
25% or 50% Open Manual Outdoor Air Dampers
Indoor Fan/Filter Status Indicator – EconoMi$er
Power Exhaust System
Horizontal power exhaust module
Low Ambient Controls
Time Guard® II Compressor Delay
Roof Curbs
Through-The-Bottom Electrical Connections
62AQ Energy$Recycler Energy Recovery Unit
Condenser Coil Grille
Condenser Hail Guard
Programmable Thermostats and Subbases
Thermidistat™
CO2 Sensors (EconoMi$er or PremierLink required)
Space temp sensors T55,T56 (PremierLink)
• Commercial Product Guide • 2002 •
45
Performance & Sizing Information
HEATING (HIGH)
CAPACITY
COOLING CAPACITY
UNIT
50TFQ
NOMINAL
TONS
(Btuh)
SEER
BELT
DIRECT
EER
(Btuh)
HSPF
SOUND
RATING
(Bels)
004
3
35,600
10.20
10.0
9.2
34,400
6.7
8.4
005
4
46,500
10.00
9.70
8.9
46,500
7.0
8.0
006
5
57,000
10.00
9.9
8.9
57,000
7.5
8.2
UNIT
50TFQ
NOMINAL
TONS
COOLING
CAPACITY
(Btuh)
EER
HEATING (HIGH)
CAPACITY
(Btuh)
IPLV
COP
SOUND
RATING
(Bels)
007
6
70,000
9.05
72,400
3.20
--
8.2
008
7.5
86,000
9.00
78,000
3.00
9.3
8.6
009
8.5
96,000
8.90
93,000
3.10
8.9
8.6
012
10
112,000
9.00
105,000
3.10
9.0
8.4
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
46
• Commercial Product Guide • 2002 •
50HJQ
Commercial Products
High-Efficiency Single-Package
Heat Pump Units
3 to 10 Nominal Tons
3-6 Ton
Features
• Listed by UL and UL, Canada, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor
• Cooling Efficiencies up to 12 SEER/10.6 EER
• Heating Efficiencies up to 7.6 HSPF/3.4 C.O.P.
• Available in 3, 4, 5, 6, 7.5 and 10 Ton Sizes
• Exclusive Cycle-LOC™ anti-compressor cycle protection
• Scroll compressors in all models
• Tool-less filter access door
• Low pressure/loss of charge, freeze protection and high
pressure switches
• Refrigerant filter drier and accumulator
• Insulated cabinet with 500 hour salt spray prepainted material
• Through-the-bottom utility capability (requires accessory)
• 2" disposable filters
• Internally-sloped composite condensate pan (dual connections)
• Roll-formed base-rail design with forklift slots and rigging
holes
• Easily convertible airflow (down supply/return standard)
• All condenser coils are set on rubber isolators to prevent
contact with unit base pan eliminating galvanic corrosion
• Permanently lubricated fan motors
• Compressors vibration isolation mounting
• All units are run tested at the factory
• Low voltage terminal blocks for easy thermostat wiring
connections
• Dual compressors and dual refrigeration circuits on 008-012
Factory-Installed Options
• Alternate Motor(s) and Adjustable Belt Drive Fans
• EconoMi$er2 with CO2 control capability
• Non-Fused Disconnect Switch
• 115 Volt Convenience Outlet
• High Static Indoor Fan Motor (belt drive)
• Apollo Communicating Control
• Corrosion-Resistant Coils (including E-Coat)
• PremierLink™ DDC Controls
• Novar 2024/3051 Controls
7.5-10 Ton
Dimensions
TONNAGE
L
W
H
3-5
6
7.5
10
73 11/16
73 11/16
87 3/8
87 3/8
45
45
57 3/4
57 3/4
33 5/16
41 5/16
41 5/16
49 5/16
NOTE: All dimensions are in inches
Field-Installed Accessories
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Electric Heaters and Single Point Kits
EconoMi$er2 with 4-20mA actuator (PremierLink/3rd party control)
EconoMi$er2 Enthalpy Controls
Durablade Economizer
25% or 100% Open Two Position Damper
25% or 50% Open Manual Damper
Hail Guard Coil Protectors
Condenser Coil Guard Protector
62AQ Energy$Recycler Energy Recovery Unit
Roof Curbs
Programmable Thermostat and Sub-bases
Time Guard® Anti-Cycle Protector
Power Exhaust System
Indoor Fan/Filter Status Indicator - EconoMi$er2
Through-the-Bottom Electrical Connections
Low Ambient Fan Speed Controllers
Emergency Heat Control Package
Thermidistat™
CO2 Sensors (EconoMi$er2 or PremierLink required)
Space temp sensors T55, T56 (PremierLink)
• Commercial Product Guide • 2002 •
47
Performance & Sizing Information
50HJQ Heat Pumps
NET COOLING
HEATING (HIGH-TEMP)
MODEL
NUMBER
NOMINAL
TONS
BTUH
SEER/EER
BTUH
COP
HSPF
50HJQ004
50HJQ005
50HJQ006
50HJQ007
50HJQ008
50HJQ012
3
4
5
6
7.5
10
36,000
45,000
60,000
71,000
88,000
116,000
12/10.7
12/10.6
11.9/10.3
10.5 EER
10.3 EER
10.3 EER
34,000
46,000
60,000
69,000
88,000
114,000
3.3
3.4
3.3
3.3
7.6
7.6
7.6
-
SOUND OPERATING
RATING
WEIGHT
(Bels)
(lbs)
7.6
7.6
8.0
8.0
8.2
8.4
500
550
590
610
870
1000
Refer to product data information for further details.
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
48
• Commercial Product Guide • 2002 •
50HJQ
Commercial Products
High-Efficiency Rooftop
Heat Pump Units
13 and 15 Nominal Tons
45”
86 1/8”
83 1/2”
Features
Factory-Installed Options
• Listed by ETL, Certified by ARI
• Cooling EERs up to 9.8
• Heating COPs up to 3.3
• Carlyle Semi-Hermetic Compressors with Circuit Breaker
Overcurrent Protection
• Low Pressure/Loss of Charge Protection, Dual Freeze
Protection and High Pressure Switches
• Two-Stage Heating and Cooling Operation
• Insulated Cabinet With 500-Hour Salt Spray Protection,
Pre-Painted, Galvanized Steel
• Manually Adjustable Outside Air Intake for up to
25% Outside Air
• 2" Disposable Filters
• Warranty: 1 Year Parts, Extended Compressor
Warranties Available
• Integrated EconoMi$er with CO2 Control Capability
• Apollo Direct Digital Controls
• Coil Material/Coating for Corrosive Environments
• Alternate High Static Fan Drives
• Service Option Package:
- Hinged Access Panels
- Non-Fused Disconnect
- Non-Powered Convenience Outlet (115v)
• UV-C Lamp
• E-coat (coil post-coating)
• Electric Heaters
Field-Installed Accessories
• Power Exhaust
• Barometric Relief
• Electric Heaters
• Integrated Economizer with Spring Return Motors
• Low Ambient Kits
• Full Perimeter Heavy Gauge Roof Curb
• Programmable Thermostats and Subbases
• Horizontal Adapter Roof Curb
• Glycol Coils
• Hail Guards
• Commercial Product Guide • 2002 •
49
Performance & Sizing Information
MODEL
NUMBER
50HJQ014
50HJQ016
AVAILABLE
VOLTAGE
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
COOLING
ARI NET
(Btuh)
COOLING
EER
140,000
9.8
172,000
9.3
HEATING
OUTPUT
(Btuh)
HEATING
COP
@ 47° F
12.4
136,000
9.7
172,000
IPLV
HEATING - LOW TEMP
SHIP
WEIGHT
(lbs)
Total
Capacity
(Btuh)
Total
kW
COP
3.2
72,000
10.0
2.1
1615
3.3
90,000
12.5
2.2
1925
Rated in
accordance with
ARI Standard
340/360
50
• Commercial Product Guide • 2002 •
50HX
Commercial Products
High-Efficiency
Small Packaged Heat Pump Units
2 to 5 Nominal Tons
Features
• Up to 12.0 SEER
• R-22 refrigerant
• Scroll compressors on all sizes
• Chronotemp™ Defrost System features time and temperature
based defrost control
• Warranty — 1-year parts and 10-year compressor
• Three-speed direct drive indoor fan motors
• Foil-faced, cleanable insulation
• Non-corrosive sloped condensate pan
• Condenser coil grille
• Easy-to-convert packaged units
• Loss-of-charge switch
• Compressor Time Guard® standard
• UL and c-UL
• Sound levels as low as 78 dB
Factory-Installed Options
• Commercial grade base rails
• Factory converted vertical discharge includes base rail
• Copper fin/copper tube coils
• E-coat coils
Base Unit Dimensions
(Without Base Rail)
MODEL
NUMBERS
50HX024-036
50HX042-060
WIDTH LENGTH HEIGHT
36.8
36.8
43.7
43.7
28.1
34.1
NOTE: All dimensions in inches.
Field-Installed Accessories
• Electric heaters — 5-20 kW
• Roof curbs
• Low ambient kit 0 degree F operation
• One inch filter with rack
• 30% Open manual outdoor air damper
• Electronic programmable thermostat
• High pressure switch
• Downshot conversion kits
• Duct covers
• Commercial Product Guide • 2002 •
51
Performance & Sizing Information
DRY COIL
MODEL NOMINAL
CFM @
NUMBER
TONS
.5 E.S.P. HIGH
50HX024
2.0
1150
50HX030
2.5
1220
50HX036
3.0
1625
50HX042
3.5
1780
50HX048
4.0
1575
50HX060
5.0
1800
OPERATING
WEIGHT
(lbs)
309
340
368
368
411
425
HEATING (HIGH-TEMP) AT 47 F
NET COOLING
BTUH
23,400
28,600
35,000
41,500
47,500
57,000
SOUND
(dB)
SEER
12.0
12.0
12.0
12.0
12.0
11.0
78
78
80
80
82
82
HEATING (LOW-TEMP) AT 17 F
MODEL
NUMBER
BTUH
COP
HSPF
BTUH
COP
50HX024
50HX030
50HX036
50HX042
50HX048
50HX060
23,800
28,200
33,000
40,000
44,000
57,000
3.2
3.2
3.2
3.3
3.5
3.5
6.9
7.1
7.0
7.0
7.0
7.2
12,400
15,400
18,000
21,000
23,600
31,800
1.8
1.9
1.9
1.9
2.0
2.0
NOTE: Operating weight does not include base rails
ELECTRICAL DATA
208/230 V, SINGLE PHASE
MODEL
SIZE
NOMINAL
VOLTS
50HX
50HX
50HX
50HX
50HX
50HX
024
030
036
042
048
060
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
COMPRESSOR
OFM
IFM
RLA
11.2
15.0
16.0
20.0
26.4
32.1
FLA
1.4
1.4
1.2
1.4
1.4
2.1
FLA
2.0
2.6
2.6
3.1
7.2
7.2
COMPRESSOR
OFM
IFM
RLA
LRA
FLA
FLA
LRA
56.0
73.0
88.0
104.0
129.0
169.0
POWER SUPPLY
MOCP
MCA
17.4
22.8
23.8
29.5
41.6
48.7
MAX
25
30
35
45
60
80
208/230 V, 3-PHASE
MODEL
SIZE
NOMINAL
VOLTS
POWER SUPPLY
MOCP
MCA
MAX
50HX
030
208/230-3-60
10.1
63.0
1.4
2.8
18.6
25
50HX
036
208/230-3-60
10.3
77.0
1.2
2.6
16.7
25
50HX
042
208/230-3-60
13.9
88.0
1.4
3.1
21.9
30
50HX
048
208/230-3-60
15.0
99.0
1.4
7.2
27.4
40
50HX
060
208/230-3-60
19.3
123.0
2.1
7.2
32.7
50
COMPRESSOR
OFM
IFM
RLA
LRA
FLA
FLA
MCA
MAX
5.1
6.8
39.0
44.0
0.7
0.8
1.3
1.6
8.4
10.9
10
15
460 V, 3-PHASE
MODEL
SIZE
NOMINAL
VOLTS
50HX
50HX
036
042
460
460
POWER SUPPLY
MOCP
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
52
• Commercial Product Guide • 2002 •
50JS
Commercial Products
Standard-Efficiency Single-Package
Heat Pump Units
1 1/2 to 5 Nominal Tons
Features
Warranty
• 10.0 SEER
• R-22 refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Multi-speed indoor fan motor
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound ratings as low as 73 dB
• Copper tube/aluminum fin condenser and evaporator coils
• UL and c-UL
• Copper tubing
• Wire grille
• Compressor cycling protection with Time Guard® II logic
built into the defrost board
• 3-phase units available
• 1-year warranty on parts
• 5-year warranty on compressor
• Extended warranties available
Factory-Installed Options
Field-Installed Accessories
• Economizer
• Manual air damper
• Filter rack
• Louvered grille
• Electric heaters
• Roof curb (8-in. and 14-in.)
• Square-to-round duct transition
• Programmable and non-programmable thermostats
• Crankcase heaters
• Compressor hard start kit (for use on single-phase only)
• Low ambient kit (Motormaster® II control)
• High and low pressure switches
• Copper fin and coil coatings available
• Vinyl coated condenser fins
• Louver grille
• Commercial Product Guide • 2002 •
53
Performance & Sizing Information
MODEL
NUMBER
NOMINAL
TONS
NET COOLING
CAPACITY
PERFORMANCE
SEER
HSPF
[email protected]
.5 ESP HIGH
OPERATING
WEIGHT
(lbs)
SOUND
(dB)
73
50JS018
1 1/2
19,000
10
6.6
707
283
50JS024
2
24,000
10
6.8
*872
289
73
50JS030
2 1/2
29,000
10
6.9
1027
287
75
50JS036
3
35,000
10
7.0
1452
291
79
50JS042
3 1/2
42,000
10
7.0
1331
323
73
50JS048
4
47,000
10
7.0
1914
353
80
50JS060
5
57,500
10
7.0
2061
418
78
*Medium setting.
50JS ELECTRICAL DATA
UNIT 50JS
SIZE
VOLTAGE RANGE
COMPRESSOR
OFM
IFM
FLA
FLA
Min
Max
RLA
LRA
018
208/230-1-60
187
253
9.0
48.0
0.9
1.8
024
208/230-1-60
187
253
12.8
61.0
0.9
2.0
208/230-1-60
187
253
14.7
82.0
0.9
2.0
208/230-3-60
187
253
9.9
78.0
0.9
2.0
208/230-1-60
187
253
16.8
82.0
1.5
4.1
208/230-3-60
187
253
9.9
85.0
1.5
4.1
460-3-60
414
506
5.5
40.0
0.8
1.9
208/230-1-60
187
253
20.6
115.0
0.9
3.8
208/230-3-60
187
253
12.4
90.0
0.9
3.8
460-3-60
41 4
506
6.7
45.0
0.8
1.8
208/230-1-60
187
253
24.4
140.0
1.5
3.5
208/230-3-60
187
253
14.1
105.0
1.5
3.5
460-3-60
414
506
7.1
53.0
0.8
1.8
208/230-1-60
187
253
28.8
165.0
1.5
6.2
208/230-3-60
187
253
19.4
125.0
1.5
6.2
460-3-60
41 4
506
8.0
63.0
0.8
3.2
030
036
042
048
060
ELECTRIC HEAT
SINGLE POINT POWER SUPPLY
V-PH-HZ
Nominal kW
FLA
MCA
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/5.0
10.0
15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
36.1/41.7
31.3/36.1
-/6.0
12.0
18.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
14.0/14.0
36.5/40.0
59.1/66.0
18.9/18.9
41.5/44.9
64.0/71.0
21.3/21.3
43.8/47.3
66.4/73.4
89.0/99.4
15.3/15.3
28.3/30.3
41.3/45.3
54.4/60.4
26.6/26.6
49.2/52.6
71.7/78.7
94.3/104.7
18.0/18.0
31.0/33.0
44.0/48.0
57.1/63.1
9.6
17.1
24.6
32.1
30.5/30.5
53.0/56.5
75.6/82.5
98.1/108.6
120.7/134.6
20.2/20.2
33.2/35.2
46.3/50.3
59.3/65.3
72.2/80.2
11.0
18.5
26.0
33.5
41.0
35.5/35.5
58.1/61.5
80.6/87.6
103.2/113.6
125.8/139.7
22.6/22.6
35.7/37.7
48.7/52.7
61.7/67.7
74.6/82.6
11.5
19.0
26.5
34.0
41.5
43.7/43.7
66.3/69.7
88.8/95.8
111.4/121.8
134.0/147.9
32.0/32.0
45.0/47.0
58.0/62.1
71.1/77.1
83.9/91.9
14.0
21.5
29.0
36.6
44.1
Fuse or
HACR Bkr
20/20
45/45
25/25
45/45
25/25
45/50
20/20
30/35
45/50
35/35
50/60
25/25
35/35
45/50
15
20
25
35
40/40
60/60
25/25
40/40
50/60
15
20
30
35
45
45/45
30/30
40/40
50/60
15
20
30
35
45
60/60
40/40
50/50
20
25
35
40
45
MOCP
60/70
70/80
70/80
90/100
60/70
80/80
100/110
60/70
80/90
100/110
125/150
60/70
80/90
70/70
90/100
110/125
150/150
70/70
80/90
70/80
90/100
125/125
150/150
60/70
80/80
90/100
-
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
54
• Commercial Product Guide • 2002 •
50JX
Commercial Products
High-Efficiency Single-Package
Heat Pump Units
2 to 5 Nominal Tons
Features
Warranty
• 12.0 SEER and up to 7.2 HSPF
• R-22 refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Multi-speed indoor fan motor
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound rating as low as 72 dB
• Copper tube/aluminum fin condenser and evaporator coils
• Scroll compressors
• UL and c-UL
• Copper tubing
• Wire grille
• Compressor cycling protection with Time Guard® II logic
built into defrost board
• 1-year warranty on parts
• 10-year warranty on compressor
Factory-Installed Options
Field-Installed Accessories
• Economizer
• Manual air damper (25% open)
• Filter rack
• Louvered grille
• Electric heaters
• Roof curb (8" and 14")
• Square-to-round duct transition
• Programmable and non-programmable thermostat
• Crankcase heaters
• Compressor hard start kit (for use on single-phase only)
• Low ambient kit (Motormaster® II control)
• High and low pressure switches
• Copper fin and coil coatings available
• Vinyl coated condenser fins
• Louvered grille
• Commercial Product Guide • 2002 •
55
Performance & Sizing Information
MODEL
NUMBER
NOMINAL
TONS
NET COOLING
CAPACITY
PERFORMANCE
SEER
HSPF
[email protected]
.5 ESP HIGH
OPERATING
WEIGHT
SOUND
(dB)
50JX024
2
23,200
12
7.1
50JX030
2 1/2
29,000
12
7.1
*814
299
72
988
320
50JX036
3
35,000
12
72
7.1
1069
328
77
50JX042
3 1/2
41,500
50JX048
4
48,000
12
7.2
*1662
350
73
12
7.2
1839
355
79
50JX060
5
60,000
12
7.2
2122
428
79
*Medium setting.
50JX ELECTRICAL DATA
UNIT 50JX
SIZE
024
VOLTAGE RANGE
COMPRESSOR
OFM
IFM
FLA
FLA
Min
Max
RLA
LRA
208/230-1-60
187
253
10.8
56.0
0.9
2.0
208/230-1-60
187
253
14.0
73.0
0.9
2.1
208/230-3-60
187
253
10.4
63.0
0.9
2.1
208/230-1-60
187
253
16.7
97.0
1.6
3.6
208/230-3-60
187
253
11.2
75.0
1.6
3.6
460-3-60
414
506
5.4
37.5
0.9
1.9
208/230-1-60
187
253
18.4
104.0
0.9
4.1
208/230-3-60
187
253
12.4
88.0
0.9
4.1
460-3-60
414
506
5.8
44.0
0.9
2.0
208/230-1-60
187
253
23.4
104.0
1.6
4.1
208/230-3-60
187
253
13.5
88.0
1.6
4.1
460-3-60
414
506
6.8
44.0
0.9
2.0
208/230-1-60
187
253
28.8
169.0
1.4
6.2
208/230-3-60
187
253
17.3
123.0
1.4
6.2
460-3-60
414
506
9.0
62.0
0.9
3.2
030
036
042
048
060
ELECTRIC HEAT
SINGLE POINT POWER SUPPLY
V-PH-HZ
Nominal kW
FLA
MCA
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/5.0
10.0
15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/5.0
10.0
15.0
20.0
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/18.1-20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/6.0
12.0
18.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
41.6/48.0
31.3/36.1
41.6/48.0
-/6.0
12.0
18.0
24.1
16.4/16.4
39.0/42.4
61.5/68.5
20.5/20.5
43.1/46.5
65.6/72.6
88.2/98.6
16.0/16.0
29.0/31.0
42.1/46.1
55.1/61.1
26.1/26.1
48.6/52.1
71.2/78.2
93.8/104.2
19.2/19.2
32.2/34.2
47.8/54.7
58.3/64.3
9.6
17.1
24.6
32.1
28.0/28.0
50.6/54.0
73.1/80.1
95.7/106.1
118.3/132.2
20.5/20.5
33.5/35.5
46.6/50.6
59.6/65.6
72.5/80.5
10.2
17.7
25.2
32.7
40.2
35.0/35.0
57.5/61.0
80.1/87.0
102.6/113.1
125.2/139.1
22.6/22.6
35.6/37.6
48.6/52.6
61.7/67.7
74.5/82.5
11.4
18.9
26.4
34.0
41.5
43.6/43.6
66.2/69.6
88.7/95.7
111.3/121.7
133.9/147.8
29.2/29.2
42.3/44.3
55.2/54.4
68.3/74.3
81.2/89.2
15.4
22.9
30.4
37.9
45.4
Fuse or
HACR Bkr
20/20
40/45
25/25
45/50
20/20
35/35
45/50
35/35
50/60
25/25
35/35
50/50
15
20
25
35
35/35
60/60
25/25
40/40
50/60
15
20
30
35
45
45/45
30/30
40/40
50/60
15
20
30
35
45
60/60
35/35
50/50
60/60
20
25
35
40
50
MOCP
70/70
60/70
60/70
80/80
100/110
60/70
80/90
100/110
125/150
60/70
80/90
70/70
90/90
110/125
150/150
70/70
80/90
70/80
100/100
125/125
150/150
70/80
90/90
-
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
56
• Commercial Product Guide • 2002 •
Commercial Products
50JZ
High-Efficiency Single-Package
Heat Pump Units
2 to 5 Nominal Tons
ComfortHeat™ Technology Featuring
Factory-Installed Options
•
•
•
•
•
•
• Copper fin and coil coatings available
• Vinyl coated condenser fins
Better dehumidification; up to 30 times
Economical constant fan; about $30 a year
Improved indoor air quality
SEER Boost; up to 12.7 SEER
Selectable CFM: High, Medium, Low
Constant CFM at higher static pressures; at least 350 CFM
at up to .9 ESP
• Single-phase only
Warranty
• 5-year warranty on parts
• 10-year warranty on compressor
• Extended warranties available
Field-Installed Accessories
Features
• 12.0 SEER and up to 7.2 HSPF
• Puron™ refrigerant
• Envirotuff™ rust-proof base with integrated drain
• Direct-drive indoor blower
• Louvered grille, pressure switches, duct covers, and filter
drier standard
• Multi-speed indoor fan motor
• Easily converted from side discharge to down discharge
• Vertical condenser fan discharge
• Sound rating as low as 72 dB
• Copper tube/aluminum fin condenser and evaporator coils
• Scroll compressors
• UL and c-UL
• Copper tubing
• Compressor cycling protection with Time Guard® II logic
built into defrost board
• 3-phase product available
• Economizer
• Manual air damper (25% open)
• Filter rack
• Electric heaters
• Roof curb (8-in. and 14-in.)
• Square-to-round duct transition
• Programmable and non-programmable thermostat; to
include the Thermidistat™ control
• Crankcase heaters
• Compressor hard start kit (for use on single-phase only)
• Low ambient kit (Motormaster® II control)
• Commercial Product Guide • 2002 •
57
Performance & Sizing Information
MODEL
NUMBER
NOMINAL
TONS
NET COOLING
CAPACITY
PERFORMANCE
SEER
HSPF
[email protected]
.5 ESP HIGH
OPERATING
WEIGHT
SOUND
(dB)
50JZ024
2
24,000
12
7.0
50JZ030
2 1/2
29,000
12
7.1
*814
299
72
988
320
50JZ036
3
36,000
12
72
7.2
1069
328
77
50JZ042
3 1/2
41,000
50JZ048
4
42,500
12
7.2
*1701
350
73
12
7.2
1839
355
79
50JZ060
5
59,000
12
7.2
2122
428
79
*Medium setting.
50JZ ELECTRICAL DATA
UNIT 50JZ
SIZE
024
VOLTAGE RANGE
COMPRESSOR
OFM
IFM
FLA
FLA
Min
208/230-1-60
187
Max
253
RLA
LRA
13.5
61.0
0.9
2.0
208/230-1-60
187
253
15.9
73.0
0.9
2.1
208/230-3-60
187
253
10.9
63.0
0.9
2.1
208/230-1-60
18 7
253
16.9
83.0
1.6
4.1
208/230-3-60
187
253
12.2
77.0
1.6
4.1
460-3-60
414
506
5.8
35.0
0.9
2.0
208/230-1-60
18 7
253
22.4
105.0
0.9
4.1
208/230-3-60
187
253
15.4
88.0
0.9
4.1
460-3-60
414
506
7.3
39.0
0.9
2.0
208/230-1-60
187
253
21.3
109.0
1.6
4.1
208/230-3-60
187
253
14.7
91.0
1.6
4.1
460-3-60
414
506
7.2
46.0
0.9
2.0
208/230-1-60
18 7
253
27.6
158.0
1.5
6.2
208/230-3-60
187
253
19.2
137.0
1.5
6.2
460-3-60
414
506
9.0
62.0
0.9
3.2
030
036
042
048
060
ELECTRIC HEAT
SINGLE POINT POWER SUPPLY
V-PH-HZ
Nominal kW
FLA
MCA
-/3.8/5.0
7.5/10.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
-/5.0
10.0
15.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-/3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.0
10.0
15.0
20.0
-/18.1/20.8
36.1/41.7
-/18.1/20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/18.1-20.8
36.1/41.7
54.2/62.5
-/10.4/12.0
20.8/24.1
31.3/36.1
-/6.0
12.0
18.0
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
6.0
12.0
18.0
24.1
-/18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
6.0
12.0
18.0
24.1
19.8/19.8
42.3/45.8
64.9/71.9
22.9/22.9
45.4/48.9
68.0/75.0
90.6/101.0
29.7/31.7
42.7/46.7
55.7/61.7
26.8/26.8
49.4/52.9
72.0/78.9
94.5/105.0
21.0/21.0
34.0/36.0
47.0/51.0
60.0/66.1
10.2
17.7
25.2
32.7
33.0/33.0
55.6/59.0
78.1/85.1
100.7/111.1
123.3/137.2
24.3/24.3
37.3/39.3
50.3/54.3
63.3/69.4
76.2/84.2
12.0
19.5
27.1
34.6
42.1
32.3/32.3
54.9/58.4
77.5/84.4
100.0/110.5
122.6/136.5
24.1/24.1
37.1/39.1
50.1/54.1
63.2/69.2
76.0/84.0
11.9
19.4
26.9
34.5
42.0
42.2/42.2
64.8/68.2
87.3/94.3
109.9/120.3
132.5/146.4
31.7/31.7
44.7/46.7
57.8/61.8
70.8/76.8
83.7/91.7
15.4
22.9
30.4
37.9
45.4
Fuse or
HACR Bkr
30/30
50/50
20/20
35/35
45/50
35/35
60/60
25/25
40/40
50/60
15
20
30
35
40/40
60/60
30/30
50/50
60/60
15
25
30
35
45
40/40
45/50
60/60
15
25
30
35
45
50/50
40/40
50/60
20
30
35
40
50
MOCP
70/80
70/80
100/110
60/70
80/80
100/110
70/70
90/90
110/125
125/150
70/70
80/90
70/70
80/90
110/125
125/150
70/70
80/90
80/80
100/110
110/125
150/150
70/70
80/80
90/100
-
Rated in
accordance with
ARI Standard 240
(60 Hz Only)
58
• Commercial Product Guide • 2002 •
50ZH
Commercial Products
Standard-Efficiency Single-Package
Heat Pump Units
2 to 5 Nominal Tons
Features
• 10 SEER
• R-22 refrigerant
• Improved fan blade with lower sound levels
• Easy Installation Design
- Starter collars
- Cartridge style drop-in heaters
- Single point electrical hook-up
- Single footprint all sizes
- Built-in hand holds
• Dedicated side discharge
• Lightweight compact construction
• Weather Armor cabinet
• Corrosion-proof base
• Sloped drain
• Through-the-top service access
• Loss of charge switch
• Warranty — 1 year parts, 5 year compressor
• Louvered metal panel for condenser coil protection
• Compressor Time Guard® standard
• UL and c-UL
MODEL SIZE
50ZH
024
NET
CLG
CAP
BTUH
22,800
CFM
@ .5 ESP SEER
HIGH
1115
10.0
NET HTG
CAP @ COP @
47° F
47° F
BTUH
21,800
2.8
NET HTG
CAP
@ 17° F
BTUH
13,300
COP @
SOUND
HSPF
(dB)
17° F
2.0
6.8
76
50ZH
030
28,200
1115
10.0
27,200
2.9
16,000
1.9
6.8
81
50ZH
036
34,200
1297
10.0
33,800
3.0
20,000
2.0
6.8
78
50ZH
042
40,000
1519
10.0
40,000
3.0
23,400
2.0
6.8
78
50ZH
048
46,000
1799
10.0
45,000
3.0
26,000
2.0
6.8
80
50ZH
060
55,000
2052
10.5
52,500
3.0
28,000
1.9
6.8
84
Field-Installed Accessories
• Electric heaters
• Programmable thermostats
• Non-programmable thermostats
• High pressure switches
• Duct covers
• Commercial Product Guide • 2002 •
59
Performance & Sizing Information
ELECTRICAL DATA
UNIT
50ZH
NOMINAL
V-PH-HZ
IFM
TYPE
024
208/230-1-60
030
036
060
OFM IFM
FLA
LRA
None
CPHEATER026A00
CPHEATER024A00
-18.3/20.8
36.1/41.7
19.3/19.3
42.2/45.3
64.4/71.4
25/25
45/50
70/80
19/19
40/42
60/66
70/70
89/91
107/112
2.4
None
CPHEATER026A00
CPHEATER024A00
CPHEATER040A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
-18.3/20.8
36.1/41.7
54.3/62.5
21.9/21.9
44.8/47.9
67.0/74.0
89.8/100.0
30/30
45/50
70/80
90/110
21/21
42/45
63/69
83/93
83/83
101/103
119/124
137/14
1.5
2.8
None
CPHEATER026A00
CPHEATER024A00
CPHEATER040A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
-18.3/20.8
36.1/41.7
54.3/62.5
26.4/26.4
49.3/52.4
71.6/78.6
94.3/104.6
35/35
50/60
80/80
100/110
25/25
46/49
67/73
88/97
103/103
121/123
139/144
157/165
77.0
1.5
2.8
None
CPHEATER029A00
CPHEATER030A00
CPHEATER031A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
-10.5/12.0
20.8/24.1
31.4/36.1
17.2/17.2
30.3/32.2
43.2/47.3
56.4/62.3
20/20
35/35
45/50
60/70
17/17
29/31
41/45
53/58
87/87
97/99
107/111
118/123
39.0
0.8
2.0
None
CPHEATER034A00
CPHEATER035A00
CPHEATER036A00
-5.0
10.0
15.0
-6.0
12.0
18.0
9.9
17.4
24.9
32.4
15
20
25
35
10
17
24
30
46
52
58
64
2.8
None
CPHEATER026A00
CPHEATER024A00
CPHEATER040A00
CPHEATER028A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
15.0/20.0
-18.3/20.8
36.1/41.7
54.3/62.5
72.1/83.3
31.2/31.2
54.1/57.2
76.3/83.3
99.1/109.3
121.3/135.3
40/40
60/60
80/90
100/110
125/150
30/30
51/54
71/78
92/102
113/125
113/113
131/133
149/154
167/175
185/196
-3.8/ 5.0
7.5/10.0
11.3/15.0
15.0/20.0
-10.5/12.0
20.8/24.1
31.4/36.1
41.6/48.1
19.8/19.8
32.9/34.8
45.8/49.9
59.1/64.9
71.8/79.9
25/25
35/35
50/50
60/70
80/80
19/19
31/33
43/47
55/61
67/75
98/98
108/110
118/122
129/134
139/146
187
254
12.8
63.0
0.9
2.4
208/230-1-60
Std
187
254
14.4
73.0
1.5
208/230-1-60
Std
187
254
17.7
93.0
208/230-3-60
Std
187
254
10.3
460-3-60
Std
414
508
5.7
21.5
DISCONNECT
SIZE
MOCP
Std
254
POWER
SUPPLY
MCA
LRA
187
ELECTRIC
HEAT
FLA
RLA
Std
HEATER
PACKAGE NO.
NOMINAL
kW
-3.8/ 5.0
7.5/10.0
MAX
103.0
FLA FLA
1.5
208/230-3-60
Std
187
254
12.4
88.0
1.5
2.8
None
CPHEATER029A00
CPHEATER030A00
CPHEATER031A00
CPHEATER041A00
460-3-60
Std
414
508
6.8
44.0
0.8
2.0
None
CPHEATER034A00
CPHEATER035A00
CPHEATER036A00
CPHEATER037A00
-5.0
10.0
15.0
20.0
-6.0
12.0
18.0
24.1
11.3
18.8
26.3
33.8
41.4
15
20
30
35
45
11
18
25
32
39
51
57
63
89
75
4.2
None
CPHEATER038A00
CPHEATER024A00
CPHEATER040A00
CPHEATER028A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
15.0/20.0
-18.3/20.8
36.1/41.7
54.3/62.5
72.1/83.3
41.0/41.0
63.8/67.0
88.1/93.1
108.8/119.1
131.1/145.1
50/50
70/70
90/100
110/125
150/150
39/39
60/63
81/87
101/111
122/135
143/143
161/163
179/184
197/205
215/226
-3.8/ 5.0
7.5/10.0
11.3/15.0
15.0/20.0
-10.5/12.0
20.8/24.1
31.4/36.1
41.6/48.1
22.6/22.6
35.7/37.6
48.6/52.7
61.8/67.7
74.6/82.7
30/30
40/40
50/60
70/70
80/90
22/22
34/36
46/50
58/64
70/77
113/113
123/125
133/137
144/149
154/161
208/230-1-60
048
COMP
MIN
208/230-1-60
042
VOLTAGE
RANGE
Std
187
254
28.2
129.0
1.5
208/230-3-60
Std
187
254
13.5
99.0
1.5
4.2
None
CPHEATER029A00
CPHEATER030A00
CPHEATER031A00
CPHEATER041A00
460-3-60
Std
414
508
8.2
129.0
0.8
4.2
None
CPHEATER034A00
CPHEATER035A00
CPHEATER036A00
CPHEATER037A00
-5.0
10.0
15.0
20.0
-6.0
12.0
18.0
24.1
15.2
22.7
30.2
37.7
45.3
20
25
35
40
50
15
22
29
36
43
141
147
153
159
165
-3.8/ 5.0
7.5/10.0
11.3/15.0
15.0/20.0
-18.3/20.8
36.1/41.7
54.3/62.5
72.1/83.3
43.9/43.9
65.8/59.9
89.1/96.1
111.8/122.1
134.1/148.1
60/60
70/70
90/100
125/125
150/150
43/43
64/66
84/91
105/114
125/138
192/192
210/213
228/233
246/254
254/275
208/230-1-60
Std
187
254
27.7
170.0
3.1
6.2
None
CPHEATER038A00
CPHEATER024A00
CPHEATER040A00
CPHEATER028A00
208/230-3-60
Std
187
254
15.9 124.0
3.1
6.2
None
CPHEATER029A00
CPHEATER030A00
CPHEATER031A00
CPHEATER041A00
-3.8/ 5.0
7.5/10.0
11.3/15.0
14.9/19.9
-10.5/12.0
20.8/24.1
31.4/36.1
41.4/47.9
29.2/29.2
42.3/44.2
55.2/59.3
68.4/74.3
80.9/89.1
35/35
45/45
60/60
70/80
90/90
29/29
41/43
53/57
65/70
77/84
146/146
158/158
167/170
177/182
187/194
460-3-60
Std
414
508
8.0
1.5
3.2
None
CPHEATER034A00
CPHEATER035A00
CPHEATER036A00
CPHEATER037A00
-5.0
10.0
15.0
20.0
-6.0
12.0
18.0
24.1
14.7
22.2
29.7
37.2
44.8
20
25
30
40
45
15
22
28
35
42
68
74
80
86
93
60.0
Rated in
accordance with
ARI Standard
210 and 240
(60 Hz Only)
60
• Commercial Product Guide • 2002 •
ENVIRO-SHIELD™
Commercial Products
Environmental Corrosion Protection
A. Pre-coated Aluminum-Fin Coils
D. E-Coated Copper-Fin Coils
Pre-coated coils have a baked-on organic coating applied
to aluminum fin stock prior to the fin-stamping process.
This creates an inert barrier between the aluminum fin
and the copper tube, thus inhibiting galvanic action.
Pre-coated aluminum fins are an economical option for
protection in mildly corrosive environments.
Providing maximum protection in virtually all
environments, this option combines the continuous,
impenetrable barrier of the E-coating process with the
natural resistance of an all-copper construction. E-coated
copper-fin coil assemblies ensure long life, even in
environments that combines harsh coastal conditions with
industrial contamination.
B. E-Coated Aluminum-Fin Coils
Coil assemblies undergo a precisely controlled scientific
process that bonds an impermeable epoxy coating to the
specially prepared fin coil surface. E-coating produces a
smooth, consistent coating that is less brittle, more
resilient and more durable than previous postcoating
processes. E-coated aluminum-fin coils offer economical
protection and improved coil life in many contaminated
environments.
The Best Protection Method for Each Environment
GOOD
BETTER
BEST
COASTAL
A
C
B
INDUSTRIAL
A
D
B
MARINE &
INDUSTRIAL
COMBINED
A
B
D
URBAN
—
A
B
C. Copper-Fin Coils
All-copper construction eliminates the corrosion-inducing
bimetallic junction that occurs when aluminum fins are
bonded to copper tubes. This provides substantially
improved corrosion protection in coastal environments.
Uncoated copper forms a natural protective film in coastal
environments and a monometallic bond exists between
the tube and fin. However, it is not suitable for industrial
applications, since many industrial contaminants attack
copper.
• Commercial Product Guide • 2002 •
61
Performance & Sizing Information
E-COATING - THE ULTIMATE PROTECTION
Water Rinse
Our E-Coated aluminum and copper-fin coils have a
continuous, impenetrable barrier that effectively seals out
environmental contaminants. This impervious coating,
when combined with the natural resistance of all-copper
construction, gives our E-Coated copper-fin coils
improved corrosion resistance compared to dipped and
baked coil coatings.
• Rinse residual dust/contaminants away
• Prepares coil for E-coating process
E-Coat Process
• Flexible coating material application
• Penetrates deep into all coil surfaces
• Covers edges and fills cracks
• Ensures consistent film thickness
Degreasing
• Complete immersion process - cleans all surfaces
• Removes all contaminants
• Ensures ultra-clean coil surfaces
Final Rinse
• Removes and recovers residual coating material
Oven Cure
• Precise temperature controlled process
• Uniformly cures film
• Ensures consistent adhesion
UV Topcoat
• Protective layer applied by spray
• Ensures durability and long life against ultraviolet exposure
62
• Commercial Product Guide • 2002 •
DURABLADE ECONOMIZER
Commercial Products
Field-Installed Accessory
For All 3 to 12 1/2 Nominal
Ton Rooftops
Features
• Bind Free Operation
• Field Installed on all 3 to 12.5 Ton Rooftops
• Industry Exclusive Design
• Saves Energy While Providing Economical and Reliable
Cooling
• Automatic Closure During a Loss of Power Occurrence
• Single Sliding Blade for Improved Air Control and Low Leak
Rates
• Lowest Ambient Air Leakage with a Virtually Leakproof Seal
• Easy Mixed Air Adjustment from 0% to 100%
• Equipped with Standard Barometric Relief
Capability of 30%
ECONOMIZER
INSTALLED VIEW
• Commercial Product Guide • 2002 •
63
Performance & Sizing Information
ECONOMIZER STATIC PRESSURE DROP (in. wg)
3-6 TON ROOFTOPS
UNIT
DURABLADE
CFM
900
0.05
1200
0.05
1400
0.05
1600
0.05
1800
0.05
2000
0.05
2400
0.05
2200
0.05
2600
0.05
4500
0.06
5000
0.07
5500
0.08
6000
0.09
ECONOMIZER STATIC PRESSURE DROP (in. wg)
7.5-12.5 TON ROOFTOPS
UNIT
DURABLADE
CFM
2200
0.02
2500
0.02
3000
0.03
3500
0.04
4000
0.05
DURABLADE ECONOMIZER BAROMETRIC RELIEF DAMPER CHARACTERISTICS
3-6 TON ROOFTOPS
64
7.5-12.5 TON ROOFTOPS
• Commercial Product Guide • 2002 •
HINGED PANELS
Commercial Products
Factory-Installed Option
For 48/50HJ 3 to 12 1/2 Ton Rooftop Units
Filter Access
Features
• Hinged Access Panels to:
1. Control Box
2. Compressor
3. Evaporator Fan Motor
4. Filters
• Serviceability has Never Been Easier Than with the New
“Hinged Panel Option”
• Control Box, Compressor Section and Evaporator Fan Motor
all have “Hot” Wires and are therefore required by UL to
have tooled access. These Hinged Panels are provided with
simple, sturdy, quarter-turn fastener with large slots for
various tool opening
Compressor Access 3-6 Ton Sizes
• Filter Area does not have “Hot” Wires and Therefore has been
Provided with Quarter-Turn Handles which are also
Collapsible for Less Shipping Damage
• All Panels are Permanently Attached to the Unit with Sturdy
Hinges
• No More Concern of Panels Dropping to Puncture Holes in
Rubber Membrane Roof
• No More Concern of Screws being Removed, Left Out and
Puncturing Holes in Roof
Compressor Access 7.5-12.5 Ton Sizes
• Commercial Product Guide • 2002 •
Evaporator Fan Motor Access
65
Performance & Sizing Information
Control Box Access 7.5-12.5 Ton Sizes
Control Box Access 3-6 Ton Sizes
Example: 48HJE008G—5
9TH DIGIT ORDERING CODE
G
H
P
Y
PremierLink Control
-
YES
YES
-
-
Apollo
-
-
-
YES
YES
YES
YES
-
YES
-
Hinged Filter Panel
Z
Hinged Control Box Panel
YES
YES
-
YES
-
Hinged Evap. Fan Motor Panel
YES
YES
-
YES
-
Hinged Compressor Panel
YES
YES
-
YES
-
-
YES
-
-
-
Microprecessor/Hinged Panel
Hinged Panel w/1/4 turn
fastener for PremierLINK
Access
PremierLINK Control
Access
Access panel
panel open,
open, PremierLink
PremierLINK
control
control cover
cover removed
removed
PremierLink™ Hinged Panels
66
• Commercial Product Guide • 2002 •
MOISTUREMI$ER™
Commercial Products
Factory-Installed Option
Dehumidification Package
For All 48/50HJ 3 to 12 1/2 Ton Rooftop Units
INSIDE UNIT VIEW
TOP COVER AND BLOWER ACCESS REMOVED
The patented Carrier MoistureMi$er™ option features dual circuit
reheat coil controlled by independent three way valves to provide
superior control of both temperature and humidity on demanding
high latent applications!
Applications
Features
RESTAURANTS:
The kitchen areas have many humidity producing activities,
such as dish washing and cooking.
• Increases Latent Capacity of Unit
• Lower Humidity Levels Provide:
- Improved Indoor Air Quality (IAQ)
- Improved Comfort Level
- Allows for Higher Space Temperatures
which will Lower Utility Bills
- Reduced Property Deterioration
• Operation can be Controlled with Field Installed Humidistat
or ThermidistatTM Accessory with Adjustable Settings for
Relative Humidity
• Operates Only When Needed to Maximize Either Sensible or
Latent Capacity
• Low Pressure Switch(es) and Crankcase Heater(s)
are Provided to Protect Unit
SUPERMARKETS:
High humidity levels cause inefficient operation of
refrigeration and freezer systems.
MUSEUMS & LIBRARIES:
Humidity damages books and artwork.
HEALTH CLUBS, GYMNASIUMS, LOCKER ROOMS:
Showers and perspiration generate high latent loads and
uncomfortable space conditions.
HOT HUMID CLIMATES:
Particularly useful when increased amounts of hot and humid
outside air are brought in for proper ventilation.
How Does It Work
The MoistureMi$er dehumidification package is a factoryinstalled option that provides increased dehumidification
by cooling the hot liquid refrigerant leaving the condenser coil.
This drops the evaporator coil operating temperature and
boosts the dehumidification process. The subcooler coil reheats
the colder than normal air passing over the evaporator coil to
normal supply air temperature preventing over-cooling of the
space.
• Commercial Product Guide • 2002 •
67
Performance & Sizing Information
How It Works
During normal operation of the 48/50HJ rooftop
when space humidity levels are below the
Humidistat/Thermidistat setpoint, liquid refrigerant is
routed through the setpoint, liquid refrigerant is routed
through the MoistureMi$er™ 3-way valve direct to the
unit’s TXV and the evaporator coil.
When space humidity levels rise above the setpoint, the
Humidistat/Thermidistat’s contacts close - energizing the
MoistureMi$er 3-way valve, redirecting the liquid
refrigerant through the MoistureMi$er coil.
When the MoistureMi$er coil is operating, the liquid
refrigerant flowing through it is subcooled to a very low
temperature approaching the units supply air temperature.
This subcooled liquid travels through the unit’s wide
range TXV and drops the evaporator coil operating
temperature well below normal operation. This lower
evaporator coil temperature is what boosts latent capacity
by up to 40%. Supply air passing through the evaporator
coil is chilled well below normal supply air temperature,
boosting the dehumidification process.
The chilled, super-dehumidified supply air is then passed
through the MoistureMi$er coil where it is reheated to
normal supply air temperature.
MOISTUREMI$ER™ PACKAGE WEIGHTS
UNIT SIZE
48/50HJ
004-007
008, 009
012, 014
NOMINAL
TONS
3-6
7.5, 8.5
10, 12.5
MOISTUREMI$ER
WEIGHT (lbs)
18
29
33
MOISTUREMISER
% RELATIVE HUMIDITY
MOISTUREMI$ER STATIC PRESSURE DROP (in. wg)
68
CFM PER TON
UNIT SIZE
48/50HJ
NOMINAL
TONS
300
400
500
004
005
006
007
008
009
012
014
3
4
5
6
7.5
8.5
10
12.5
0.04
0.07
0.09
0.12
0.08
0.1
0.08
0.11
0.07
0.12
0.15
0.2
0.13
0.15
0.13
0.18
0.09
0.15
0.21
0.28
0.18
0.22
0.18
0.26
• Commercial Product Guide • 2002 •
48/50TJ,HJ MOISTUREMI$ER™
Commercial Products
High Latent Dehumidification Option
For All 48/50TJ,HJ 12 to 25 Ton Rooftop Units
The patented Carrier MoistureMi$er™ option features dual circuit
reheat coil controlled by independent three way valves to provide
superior control of both temperature and humidity on demanding
high latent applications!
Applications
RESTAURANTS:
The kitchen areas have many humidity producing activities,
such as dish washing and cooking.
SUPERMARKETS:
High humidity levels cause inefficient operation of refrigeration
and freezer systems.
MUSEUMS & LIBRARIES:
Humidity damages books and artwork.
HEALTH CLUBS, GYMNASIUMS, LOCKER ROOMS:
Showers and perspiration generate high latent loads and
uncomfortable space conditions.
HOT HUMID CLIMATES:
Particularly useful when increased amounts of hot and humid
outside air are brought in for proper ventilation.
Features
• Increases Latent Capacity of Unit
• Lower Humidity Levels Provide:
- Improved Indoor Air Quality (IAQ)
- Improved Comfort Level
- Allows for Higher Space Temperatures
which will Lower Utility Bills
- Reduced Property Deterioration
• Operation can be Controlled with Field Installed Humidistat
or ThermidistatTM Accessory with Adjustable Settings for
Relative Humidity
• Operates Only When Needed to Maximize Either Sensible or
Latent Capacity
• Low Pressure Switch(es) and Crankcase Heater(s)
are Provided to Protect Unit
How Does It Work
The MoistureMi$er dehumidification package is a factoryinstalled option that provides increased dehumidification
by cooling the hot liquid refrigerant leaving the condenser
coil. This drops the evaporator coil operating temperature
and boosts the dehumidification process. The subcooler coil
reheats the colder than normal air passing over the evaporator
coil to normal supply air temperature preventing over-cooling
of the space.
• Commercial Product Guide • 2002 •
69
Performance & Sizing Information
How It Works
During normal operation of the 48/50TJ,HJ rooftop
when space humidity levels are below the
Humidistat/Thermidistat setpoint, liquid refrigerant is
routed through the MoistureMi$er™ 3-way valve direct
to the unit’s TXV and the evaporator coil.
When space humidity levels rise above the setpoint, the
Humidistat/Thermidistat’s contacts close - energizing the
MoistureMi$er 3-way valve, redirecting the liquid
refrigerant through the MoistureMi$er coil.
48/50TJ
016
020
024
NOMINAL CAPACITY
15
18
20
25
TC
186.0
200.6
237.0
291.0
SHC
133.0
151.0
175.0
222.0
LHC
53.0
49.6
62.0
69.0
TC
172.6
187.5
225.9
270.5
SHC
103.3
119.3
144.7
178.9
LHC
69.3
68.2
81.2
91.6
NOM.
3.7
5
7.5
10
MAX CONT.
4.25
5.9
9.5
11.8
MAX EPS @ 400 CFM/TON
1.57
2.87
2.66
1.83
OPERATING WEIGHT ADDER
40
40
40
40
SHIPPING WEIGHT ADDER
40
40
40
40
STD RATING
COOLING CAP.
@400 CFM/TON
MOISTUREMI$ER
COOLING CAP.
@400 CFM/TON
FAN MOTOR
HORSEPOWER
When the MoistureMi$er coil is operating, the liquid
refrigerant flowing through it is subcooled to a very low
temperature approaching the units supply air temperature.
This subcooled liquid travels through the unit’s wide
range TXV and drops the evaporator coil operating
temperature well below normal operation. This lower
evaporator coil temperature is what boosts latent capacity
by up to 40%. Supply air passing through the evaporator
coil is chilled well below normal supply air temperature,
boosting the dehumidification process.
The chilled, super-dehumidified supply air is then passed
through the MoistureMi$er coil where it is reheated to
normal supply air temperature.
028
MOISTUREMISER
% RELATIVE HUMIDITY
48/50HJ
015
NOMINAL CAPACITY
12
15
TC
137.7
190.0
SHC
104.4
136.0
LHC
33.3
54.0
TC
130.9
176.0
SHC
91.5
108.7
LHC
39.4
67.3
NOM.
2.9
5
MAX CONT.
3.13
6.13
STD RATING
COOLING CAP.
@400 CFM/TON
MOISTUREMI$ER
COOLING CAP.
@400 CFM/TON
FAN MOTOR
HORSEPOWER
017
MAX EPS @ 400 CFM/TON
1.39
2.39
OPERATING WEIGHT ADDER
40
40
SHIPPING WEIGHT ADDER
40
40
70
• Commercial Product Guide • 2002 •
ECONOMI$ER2
Commercial Products
Factory-Installed Option or Field-Installed Accessory
For all 3 to 12 1/2 Ton Rooftop Units
CONTROLLER
GEAR-DRIVEN
DAMPER
ECONOMI$ER
PLUG
ACTUATOR
Features
• Warranty-Limited 3 Years on entire unit
• Heavy gauge galvanized steel design
• Integral Barometric Relief Damper (100%)
• Outdoor Temperature Sensor
• Direct-mount spring-return electric actuator that
automatically closes upon loss of power
• Gear-driven damper blades
• Microprocessor-based controller
- Optimum control of compressors and “free” cooling
- Set-point adjustment of key parameters
- Minimum position
- Economizer changeover
- Mechanical cooling lockout
- CO2 set-point
- Discharge Air Control
- CO2 Ventilation Control
- Maximum energy efficiency with minimum
temperature swing
- Maximum damper position
OUTDOOR AIR
TEMPERATURE
SENSOR
BAROMETRIC
RELIEF DAMPERS
EconoMi$er2
Field-Installed Accessories
• Power exhaust system
- Field installed accessory
- Single stage fan
- 24" curb not required
• Horizontal power exhaust
- Single fan
- Relay controlled
- 200" power harness for remote mounting
Power Exhaust
• Commercial Product Guide • 2002 •
71
Performance & Sizing Information
ACCESSORIES AND DESCRIPTIONS
PART NUMBER AND DESCRIPTIONS
HH57AC078 (HH57AC077-PremierLink™ models only)
• Outdoor air enthalpy sensor
CROASENR001A00
• Outdoor Air/Return air temperature sensor (adjustable)
HH57AC078
• Return air enthalpy sensor
33ZCSENCO2
• CO2 room sensor (wall mount/duct mount)
33ZCASPCO2
• Aspirator box (required for duct mount CO2 room sensor)
--HT--01AH-859
• 575VAC Stepdown transformer for 575VAC
power exhaust applications
Vertical
Horizontal
CRECOMZR020A00
CRPWREXH021A00
CRPWREXH025A00
CRECOMZR024A00
CRPWREXH029A00
7.5-12.5 ton EconoMi$er2
CRECOMZR021A00
7.5-12.5 ton power exhaust (460-3-60)
CRPWREXH023A00
7.5-12.5 ton PE with EconoMi$er2 (460-3-60) CRPWREXH027A00
CRECOMZR025A00
CRPWREXH029A00
3-6 ton EconoMi$er2 system
3-6 ton power exhaust (460-3-60)
3-6 ton PE with EconoMi$er2 (460-3-60)
VERTICAL ECONOMI$ER2 PERFORMANCE DATA
HORIZONTAL ECONOMI$ER2 PERFORMANCE DATA
5000
2500
2000
3000
3-6 Ton
2000
7.5-12.5 Ton
1000
FLOW (cfm)
FLOW (cfm)
4000
1500
1000
500
0
0
0.1
0.2
0.3
0.4
0.5
0
0
0.2
0.3
0.4
0.5
2500
2500
2000
3-6 Ton
1500
7 1/2 - 12 1/2 Ton
1000
500
0
0.15
0.05
0.25
2000
1500
3-6 Ton
7-12 1/2 Ton
1000
500
0
STATIC PRESSURE (in. wg)
0.05"
BAROMETRIC RELIEF FLOW CAPACITY
30
25
20
3-6 Ton
7 1/2-12 1/2 Ton
15
10
5
0
0.13
0.20 0.22
0.25
0.30 0.35 0.40
0.45
0.15"
0.25"
BAROMETRIC RELIEF FLOW CAPACITY
Flow in cubic feet per minute (cfm)
FLOW IN CUBIC FEET PER MINUTE (cfm)
0.1
HORIZONTAL POWER EXHAUST
Flow in cubic feet per minute (cfm)
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
VERTICAL POWER EXHAUST
30
25
20
3-6 Ton
15
7-12 1/2 Ton
10
5
0
0.50
0.1"
0.2"
0.3"
0.4"
0.5"
Static Pressure (in. wg)
STATIC PRESSURE (in. wg)
OUTDOOR AIR DAMPER LEAKAGE
OUTDOOR AIR DAMPER LEAKAGE
ECONOMI$ER2 POWER EXHAUST DATA
3 – 6 Ton
7.5 – 12.5 Ton
5000
2000
2 FANS
OPERATING
1500
1 FAN
OPERATING
1000
500
FLOW (cfm)
FLOW (cfm)
2500
4000
3000
2 FANS
OPERATING
2000
1 FAN
OPERATING
1000
0
0
0
0
72
0.1
0.2 0.3 0.4 0.5
STATIC PRESSURE (in. wg)
0.1
0.2
0.3
0.4
0.5
STATIC PRESSURE (in. wg)
• Commercial Product Guide • 2002 •
50AH
Commercial Products
Roomtop® Horizontal Indoor
Single-Package Cooling Units
2 to 5 Nominal Tons
Dimensions
Features
• ASHRAE 90.1 minimum efficiency compliant
• Installs in Ceiling - Truly Out-of-Sight Cooling!
• Compact Design and Low Silhouette a space-saving design
• Ease of accessibility for time-saving maintenance
• Application Flexibility - Unit can be installed as
a Split System
• Quiet and Efficient - Scroll Compressors in all sizes
• Listed by UL, CSA approved, certified by ARI
• Warranty: 1 Year Parts, 5 Year Compressor
• 1" disposable filter
• Refrigerant filter drier
• Permanently lubricated fan motors
• High and low pressure protection
Factory-Installed Options
SIZE 50AH
A
B
C
024, 036
5' - 6''
4' - 0''
1' - 5 3/4''
048, 060
5' - 6''
4' - 0''
1' - 11 5/8''
Field-Installed Accessories
• Electric Heat Module
• Thermostat Assembly
• Compressor Cycle Delay
• Condensate Pump
• Heat Pressure Control Package
• Vibration Isolation Package
• 1.5 Horsepower High-Static Motor (048, 060 Sizes)
• Commercial Product Guide • 2002 •
73
Performance & Sizing Information
NOMINAL
CFM
SEER
SEER
w/TDR
SOUND
(Bels)
2.6
NET
COOLING
(Btuh)
25,000
800
10.8
11.0
7.8
4.3
36,000
1200
10.0
10.0
8.2
5.5
49,500
1600
10.2
10.4
8.2
6.9
58,500
2000
9.7
10.0
8.2
UNIT
50AH
V-PH-HZ
TOTAL
kW
kW
024
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
036
048
060
ELECTRICAL DATA
UNIT
50AH
V-PH
(60 HZ)
024
230-1
036
230-1
208/230-3
048
060
048
060
230-1
208/230-3
460-3
575-3
230-1
208/230-3
460-3
575-3
208/230-3
460-3
208/230-3
460-3
VOLTAGE RANGE
Min
Max
207
207
187
414
207
187
414
518
207
187
414
518
187
414
187
414
254
254
254
508
254
254
508
632
254
254
508
632
254
508
254
508
POWER SUPPLY
Min CKT
Amps
20.8
29.5
19.9
8.8
42.0
24.8
13.4
10.1
49.5
30.4
15.8
13.7
26.4
14.0
32.0
16.5
MOCP Amps
25
40
25
15
60
35
15
15
70
45
25
20
35
20
40
25
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
74
• Commercial Product Guide • 2002 •
50BY
Commercial Products
Vertical Air-Cooled
Self-Contained Single-Package Units
5 to 20 Nominal Tons
Features
• Free Blow or Ducted Applications Evaporator and
Condenser Air
• Max 33" width Fits Through Most Elevators and Doors,
and 20 Ton unit may be Split
• All Service Done Through Front Panels
• High Static Belt Drive Condenser Fan to 1" ESP
• Scroll Compressors on All Sizes
• 2 Independent Stages Above 7 1/2 Ton
• Standard IAQ Feature
- Dual Sloped Condensate Pan
- Double Wall Construction
- Ventilation Air Capability
- 1" or 2" Filter Tracks
- Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor
• TEFC 3 ph Fan Motors on Adjustable Belt Drive Fans
Evaporator and Condenser
• All Units Except 12 Ton may be Rotated for Vertical or
Horizontal Front Evaporator Discharge
• HP and LP Switches, Time Guard® and Cycle-LOC™
Standard
• Available in 208/230, 460 and 575 volt 3 ph All Models
• Choice of Controls
- 24 V Commercial Thermostat
- TEMP Comfort System with Communicating Controls
-VVT® compatible
• Motors are VFD compatible
• UL Listed and Manufactured in an ISO 9001 Facility
Field-Installed Accessories
•
•
•
•
Hot Water Heating Coils With Unit Filter Track
Steam Heating Coils With Unit Filter Track
Low Ambient Head Pressure Control Damper
Thermostats
- Commercial Remote
- Communicating Remote
• Mixing Boxes, Economizers and Plenums
• UV-C Germicidal Lamps
• High Efficiency Filter
• Commercial Product Guide • 2002 •
75
Performance & Sizing Information
SELF-CONTAINED VERTICAL PACKAGED UNITS
MODEL
NUMBER
TONS
CFM
50BYN006
5
2000
COOL
(Btuh)
EER
59,000
10.0†
WEIGHT
(lbs.)
FAN HP
STG.
594
1
DIMENSIONS (in.)
Evap
Cond
Length
Width
Height
1 1/ 2
2
41
27 1/8
70 5/8
50BYN008
7.5
3000
81,000
8.9
765
1
2
3
48 1/ 2
27 1/8
70 5/8
50BYN012
10
4000
121,000
8.5
948
2
3
5
63 1/ 2
29 3/8
70
50BYN014
12
4800
137,000
8.5
1036
2
5
5
71
29 3/8
70
50BYN016
15
6000
162,000
8.5
1190
2
5
5
75
29 3/8
78
50BYN024
20
8000
224,000
8.5
1654
2
7 1/2
7 1/2
83
31 1/4
92 1/4*
* 20 Ton unit has removable fan section, it may be rotated for vertical or horizontal front discharge. Height without fan section is 58.5 inches.
† Seasonal Energy Efficency Rating
ELECTRICAL DATA
MOTOR HP
208/230 VOLT - 3 ph - 60 Hz
460 VOLT - 3 ph - 60 Hz
575 VOLT- 3 - 60
MODEL
Evap
Cond
MCA
Fuse
MCA
50BYN006
1 1/2
2
37.0
50
17.8
50BYN008
2
3
43.6
60
21.0
50BYN012
3
5
67.1
80
32.3
50BYN014
5
5
76.4
90
50BYN016
5
5
80.4
50BYN024
7 1/2
7 1/2
116.8
MCA
Fuse
25
14.3
20
30
16.8
20
40
25.9
30
36.7
45
29.4
35
100
38.7
45
31.0
35
125
56.0
60
45.2
50
FUSE - Maximum fuse size allowed (Amps)
MCA - Minimum Circuit Amps
76
• Commercial Product Guide • 2002 •
Fuse
50BR,BZ
Commercial Products
Vertical Air-Cooled and Water-Cooled
Single-Package Units
5 to 20 Nominal Tons
Features
•
•
•
•
Free Blow or Ducted Applications
Max 32" width Fits Through Most Elevators and Doors
Rear Return Air Capability on All Units
Field Convertible Vertical to Horizontal Supply Fan
Discharge - Except 014 Size
• All Service Done Through Front Panels
• Attractive Cabinet with High Impact Polystyrene Grilles
5 to 12 Ton
• Scroll Compressors on All Sizes
• 2 Independent Stages Above 7 1/2 Ton
• Standard IAQ Features
- Dual Sloped Condensate Pan
- Double Wall Construction
- Ventilation Air Capability
- 1" or 2" Internal Filters
- Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor
• TEFC 3 ph Fan Motors on Adjustable Belt Drive Fans
• 50BR has 400 psi Rated Low Pressure Drop Brazed
Plate Condenser
• HP and LP Switches, Time Guard® and
Cycle-LOC™ Standard
• Available in 208/230, 460 or 575 Volt 3 ph All Models
• Choice of Controls
- Internal Thermostat with Unit Fan Switch
(except 016 and 024)
- 24 V Commercial Thermostat
- TEMP Comfort System with Communicating Controls
• 24 V Condenser Controls on 50BZ Units
• UL Listed and Manufactured in an
ISO 9002 Facility
50BR WATER-COOLED
50BZ REMOTE AIR-COOLED
Field-Installed Accessories
•
•
•
•
•
Supply Air Discharge Plenum
Internal Hot Water Heating Coils
Internal Steam Heating Coils
Water Side Economizer
Thermostats
- Internal Mounted
- Commercial Remote
- Communicating Remote
• IAQ Option Packages
• Mixing Boxes and Air Side Economizer
• Commercial Product Guide • 2002 •
77
Performance & Sizing Information
MODEL
NUMBER TONS
50BRN
NOM.
CFM
NET
COOL
(BTUH)
WATER-COOLED VERTICAL PACKAGE UNITS
WATER
NOM. WEIGHT STG
FAN
EER
CONN.
GPM
(LBS)
HP
(in.)
006
5
2000
62,000
13.1†
15.4
595
1
1.5
[email protected] 1/4
008
012
014
016
024
7.5
10
12
15
20
3000
4000
4500
6000
8000
82,000
119,000
136,000
168,000
230,000
11.5
11.4
11.5
11.5
12.0
20.0
29.0
34.0
40.0
60.0
639
926
970
1071
1422
1
2
2
2
2
2
3
5
5
7.5
[email protected] 1/4
[email protected] 1/4
[email protected] 1/4
[email protected] 1/4
[email protected] 1/4
DIMENSIONS (in.)
Length
Depth Height
40 15/16 22 13/16 77 1/2
48 1/2
56.0
63 1/2
75.0
80.0
22 13/16 77 1/2
27 9/16 78 1/8
27 9/16 78 1/8
25 5/8 78 1/2*
30.30
88.9*
*15 and 20 ton units have a removable fan section, which may be rotated for vertical, horizontal front or rear discharge. Height
without fan section is 58.5 inches, connection sizes are size for each inlet and outlet connection.
†Seasonal Energy Efficiency Ratio.
REMOTE AIR-COOLED VERTICAL PACKAGE UNITS
MODEL
NUMBER
50BZN
TONS
NOM.
CFM
NET
COOL
(BTUH)
EER
WEIGHT
(LBS)
STG
FAN
HP
006
008
012
5
7.5
10
2000
3000
4000
59,000
81,000
121,000
10.0†
8.9
8.9
570
613
873
1
1
2
1.5
2
3
014
12
4500
135,000
8.5
917
2
5
016
15
6000
162,000
8.5
1014
2
5
REFRIGERANT
CONNECTIONS
Liq
Gas
[email protected]/2
[email protected]/8
[email protected]/2
[email protected]/8
[email protected]/2
[email protected]/8
[email protected]/8
[email protected]/2
[email protected]/8
[email protected]/2
[email protected]/8
DIMENSIONS (in.)
Length
40 15/16
48 1/2
56
Depth
22 13/16
22 13/16
27 9/16
Height
77 1/2
77 1/2
78 1/8
63 1/2
27 9/16
78 1/8
75
25 5/8
78 1/2
† Seasonal Energy Efficiency Ratio.
REMOTE CONDENSER OPTIONS FOR 50BZN (S-STANDARD, O-OPTIONAL)
09AZ
SIZE
09BY
006
008
012
014
016
50BZ006
S
O
NR
NR
50BZ008
NR
S
O
NR
50BZ012
NR
NR
S
09DE
09DK
006
008
012
014
016
024
016
020
024
NR
S
O
NR
NR
NR
NR
NR
NR
NR
NR
NR
S
O
NR
NR
NR
NR
NR
NR
O
NR
NR
NR
S
O
NR
NR
NR
NR
NR
50BZ014
NR
NR
NR
S
O
NR
NR
NR
S
O
NR
S
S
NR
50BZ016
NR
NR
NR
NR
S
NR
NR
NR
NR
S
O
O
O
S
NR — Not Recommended
208/230-3-60
460-3-60
575-3-60
50BRN
50BRZ
MOTOR
HP
MCA
MOCP
MCA
MOCP
MCA
MOCP
006
1.5
28.9
45
14.4
20
11.6
15
008
2
32.3
50
16.2
25
12.9
20
012
3
51.1
60
25.6
30
20.4
25
014
5
58.6
70
29.2
35
23.4
25
016
5
61.2
80
30.6
40
24.5
30
024*
7 1/2
88.8
100
44.5
50
35.5
40
* 50BRN Only.
50BZ Rated ARI Standard
360, when matched with
appropriate 09 Series
Condenser.
(60 Hz Only)
78
• Commercial Product Guide • 2002 •
50BVC,BVQ,BVJ,BVY
Commercial Products
Standard Water-Cooled Indoor Packaged Constant Volume Systems
Variable Air Volume Systems
18 to 60 Nominal Tons
Features
• Constant volume with 2 stage thermostat control and
compressor safety lock out (50BVC, 50BVQ)
• Variable volume with factory mounted Carrier DDC 6400
Microprocessor control with full CCN compatibility. Factory
mounted VFD and static pressure sensor (BVJ, BVY)
• Cabinet made of heavy-gauge steel compact design
• Easily removable panels provide service to all sections
• Refrigerant R-22
• Unit frame is free standing post construction
• Evaporator fan compartment, interior cabinet surfaces are
insulated with 1/2" minimum thick fiberglass
• Crankcase heaters
• Stainless steel condensate drain pan with positive slope
• Multiple scroll compressors with independent circuits
• 2 independent circuits up to 30 ton
• 4 independent circuits above 30 ton
• Anti-short cycle timer, HP and LP switch protection
• Face split coils specially designed for independent,
two-circuit operation
• Forward curved fans to 2" ESP
• High-efficiency tube and tube condensers
• Pre-wired electrical control center
• Standard IAQ Feature
- Sloped Condensate Pan
- Ventilation Air Capability
- 2" Filters Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor (option)
• 50BVC - Constant volume cooling
• 50BVQ - Constant volume heat pump
• 50BVJ - VAV cooling
• 50BVY - VAV with heat pump warm up
• Water/air heat pump (BVQ,BVY)
Factory-Installed Options
• Variable frequency drives (standard on 50BVJ, 50BVY)
• Alternate fan positions
• Hot gas bypass
• Hot gas reheat for humidity control
• Alternate fan motor drive
• Water side economizer package with valve package
• 1 Row steam coils
• Hot water coils
• Condensate overflow switch
• Extend water temperature range option
• Double wall evaporator
• E-Coated coils
• CU/NI condensers
Field-Installed Accessories
• Air side economizer and mixing box
• High efficiency filters with 4" deep filter racks
• Heating coils: 1 row steam or 2 row hot water
• Thermostats
- Commercial remote
- Communicating remote
• Sound lined discharge plenum
• Commercial Product Guide • 2002 •
79
Performance & Sizing Information
MODEL
50BVC,BVQ,
BVJ,BVY
020
024
028
034
038*
044*
048*
054*
064*
TONS
GROSS
COOLING
NOMINAL
AIR FLOW
EER
GPM
HEAT PUMP
HEATING
FAN
WEIGHT
(lbs.)
WIDTH
(in.)
DEPTH
(in.)
HEIGHT
(in.)
18
20
25
30
35
40
45
50
60
213,000
240,000
286,000
360,000
436,000
480,000
526,000
572,000
720,000
7,000
8,000
10,000
12,000
14,000
16,000
18,000
20,000
24,000
14.0
13.8
12.4
14.4
14.0
13.8
12.4
12.4
14.4
54
61
75
90
108
122
136
150
180
274,000
323,000
366,000
440,000
548,000
646,000
689,000
732,000
880,000
2 @ 1.5 hp
2 @ 2 hp
2 @ 3 hp
2 @ 5 hp
4 @ 1 1/2 hp
4 @ 2 hp
4 @ 2 hp
4 @ 3 hp
4 @ 5 hp
1260
1340
1400
1700
1700
2680
2740
2800
3400
32
32
32
32
64
64
64
64
64
80
80
80
80
80
80
80
80
80
66 1/2
66 1/2
66 1/2
86 1/2
66 1/2
66 1/2
66 1/2
66 1/2
86 1/2
* Unit consists of two modules in master/slave arrangement.
ELECTRICAL DATA
MODEL
50BVC,BVQ,
BVJ,BVY
MCA
MOCP
MCA
MOCP
MCA
MOCP
020
77.6
100
39.5
50
22.9
30
024
82.4
110
36.0
45
29.2
35
028
82.0
110
39.8
60
-
-
034
133.7
175
60.9
80
-
-
038
148.0
175
75.3
80
-
-
044
159.4
175
70.5
80
-
-
048
165.3
200
76.8
90
-
-
054
183.6
225
89.7
110
-
-
064
272
300
125.1
125
-
-
80
208/230-3-60
460-3-60
575-3-60
• Commercial Product Guide • 2002 •
50BVE,BVK
Commercial Products
Standard Remote Air-Cooled Indoor Packaged Constant Volume Systems
Variable Air Volume Systems
18 to 60 Nominal Tons
Features
• Constant volume with 2 stage thermostat control and
compressor safety lock out (50BVE)
• Variable volume with factory mounted Carrier DDC 6400
Microprocessor control with full CCN compatibility. Factory
mounted VFD and static pressure sensor (50BVK)
• Cabinet made of heavy-gauge steel, compact design
• Easily removable panels provide service to all sections
• Refrigerant R-22 (unit shipped with nitrogen charge)
• Unit frame is free standing post construction
• Evaporator fan compartment, interior cabinet surfaces are
insulated with 1/2" minimum thick fiberglass
• Stainless steel condensate drain pan with positive slope
• Multiple scroll compressors with independent circuits
• 2 independent circuits up to 30 ton
• 4 independent circuits above 30 ton
• Anti-short cycle timer, HP and LP switch protection
• Face split coils specially designed for independent,
two-circuit operation
• Crankcase heaters
• Unit starts and runs at 125° F ambient outdoor temp
• Forward curved fans to 2" ESP
• Liquid and discharge service valves
• Pre-wired electrical control center
• Standard IAQ Feature
- Sloped Condensate Pan
- Ventilation Air Capability
- 2" Filters Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor (option)
• Units may be matched to 09DK condensers
• 50BVE - Constant volume
• 50BVK - VAV
Factory-Installed Options
• Variable frequency drives (standard on 50BVK)
• Alternate fan positions
• Hot gas bypass
• Hot gas reheat for humidity control
• Alternate fan motor drive
• 1 row steam coils
• Hot water coils
• Condensate overflow switch
• Double wall evaporator
• E-Coated coils
Field-Installed Accessories
• Air side economizer and mixing box
• High efficiency filters with 4" deep filter racks
• Heating coils: 1 row steam or 2 row hot water
• Thermostats
- Commercial remote
- Communicating remote
• Sound lined discharge plenum
• Commercial Product Guide • 2002 •
81
Performance & Sizing Information
MODEL
50BVE,BVK
TONS
GROSS
COOLING
NOMINAL
AIR FLOW
EER
FAN
WEIGHT
(lbs.)
WIDTH
(in.)
DEPTH
(in.)
HEIGHT
(in.)
020
024
028
034
038*
044*
048*
054*
064*
18
20
25
30
35
40
45
50
60
171,500
205,300
242,500
313,100
343,000
376,800
410,600
485,000
626,200
7,000
8,000
10,000
12,000
14,000
16,000
18,000
20,000
24,000
9.4
10.1
9.3
9.6
9.4
10.1
9.4
9.3
9.6
2 @ 1.5 hp
[email protected] 2 hp
2 @ 3 hp
2 @ 5 hp
4 @ 1 1/2 hp
4 @ 2 hp
4 @ 2 hp
4 @ 3 hp
4 @ 5 hp
1060
1140
1200
1500
1500
2280
2340
2400
3000
32
32
32
32
64
64
64
64
64
80
80
80
80
80
80
80
80
80
66 1/2
66 1/2
66 1/2
86 1/2
66 1/2
66 1/2
66 1/2
66 1/2
86 1/2
* Unit consists of two modules in master/slave arrangement. 4 Condenser circuits required.
ELECTRICAL DATA
208/230-3-60
460-3-60
575-3-60
MODEL
50BVE,BVK
RECOMMENDED
CONDENSER
MCA
MOCP
MCA
MOCP
MCA
MOCP
020
09DK020
77.6
100
39.5
50
22.9
30
024
09DK024
82.4
110
36.0
45
29.2
35
028
09DK028
82.0
110
39.8
60
-
-
034
09DK034
133.7
175
60.9
80
-
-
038
(2) 09DK020
148.0
175
75.3
80
-
-
044
(2) 09DK024
159.4
175
70.5
80
-
-
048
(2) 09DK028
165.3
200
76.8
90
-
-
054
(2) 09DK028
183.6
225
89.7
110
-
-
064
(2) 09DK034
272
300
125.1
125
-
-
82
• Commercial Product Guide • 2002 •
50BVT,BVV,BVW,BVZ
Commercial Products
Modular Water-Cooled Indoor Packaged Constant Volume Systems
Variable Air Volume Systems
20 to 60 Nominal Tons
Features
• Constant volume with 2 stage thermostat control and
compressor safety lock out (50BVT, 50BVV)
• Variable volume with factory mounted Carrier DDC 6400
Microprocessor control with full CCN compatibility. Factory
mounted VFD and static pressure sensor (50BVW, 50BVZ)
• Cabinet made of heavy-gauge steel modular construction
allows modules to pass through 36" door without breaking
refrigerant lines
• Easily removable panels provide service to all sections
• Refrigerant R-22
• Crankcase heaters
• Unit frame is free standing post construction
• Evaporator fan compartment, interior cabinet surfaces are
insulated with 1/2" minimum thick fiberglass
• Stainless steel condensate drain pan with positive slope
• Multiple scroll compressors with independent circuits.
2 circuits up to 30 ton, 4 circuits above 30 ton
• Anti-short cycle timer, HP and LP switch protection
• Face split coils specially designed for independent,
two-circuit operation
• Forward curved fans to 4" ESP
• High-efficiency tube and tube condensers
• Pre-wired electrical control center
• Standard IAQ Feature
- Sloped Condensate Pan
- Ventilation Air Capability
- 4" Standard Filters, Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor (option)
• 50BVT - Constant volume cooling
• 50BVV - Constant volume heat pump
• 50BVW - VAV cooling
• 50BVZ - VAV with heat pump warm up
• Water/air heat pump (BVV, BVZ)
Factory-Installed Options
• Variable frequency drives (standard on 50BVW, BVZ)
• Alternate horizontal fan position
• Hot gas bypass
• Hot gas reheat for humidity control
• Alternate fan motor drive
• Water side economizer package with valve package
• 1 Row steam coils
• Hot water coils one or two row
• Condensate overflow switch
• Extend water temperature range option
• Double wall evaporator
• E-Coated coils
• CU/NI condensers
Field-Installed Accessories
• Air side economizer and mixing box
• High efficiency filter racks
• Heating coils: 1 row steam or 2 row hot water
• Thermostats
- Commercial remote
- Communicating remote
• Commercial Product Guide • 2002 •
83
Performance & Sizing Information
MODEL
50BVT,BVV,
BVW,BVZ
TONS
GROSS
COOLING
NOMINAL
AIR FLOW
EER
GPM
HEAT PUMP
HEATING
FAN
HP
WEIGHT
(lbs.)
WIDTH*
(in.)
DEPTH*
(in.)
HEIGHT*
(in.)
024
028
034
044
048
054
064
20
25
30
40
45
50
60
260,000
325,000
400,000
500,000
585,000
650,000
800,000
8,000
10,000
12,000
16,000
18,000
20,000
24,000
16.2
16.2
16.2
16.2
16.2
16.2
16.2
60
75
90
120
135
150
180
340,000
400,000
425,000
680,000
740,000
800,000
850,000
10
15
15
2 @ 10
2 @ 10
2 @ 15
2 @ 15
2423
2850
2866
4846
5273
5700
5732
69 3/4
69 3/4
69 3/4
139 1/2
139 1/2
139 1/2
139 1/2
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
* Unit breaks down into modules to bring into building, see product data.
ELECTRICAL DATA
MODEL
50BVT,BVV,
BVW,BVZ
84
208/230-3-60
460-3-60
MCA
MOCP
MCA
MOCP
024
120.3
150
56.1
70
028
144.6
175
70.2
90
034
178.6
225
81.4
100
044
219.1
250
109.1
125
048
209.8
250
100.4
125
054
284.9
350
138.7
175
064
345.3
450
158.7
175
• Commercial Product Guide • 2002 •
50BVU,BVX
Commercial Products
Modular Remote Air-Cooled Indoor Packaged Constant Volume Systems
Variable Air Volume Systems
20 to 60 Nominal Tons
Features
• Constant volume with 2 stage thermostat control and
compressor safety lock out (50BVU)
• Variable volume with factory mounted Carrier DDC 6400
Microprocessor control with full CCN compatibility. Factory
mounted VFD and static pressure sensor (50BVX)
• Cabinet made of heavy-gauge steel modular design
construction allows modules to pass through 36" door
• Easily removable panels provide service to all sections
• Refrigerant R-22 (units shipped with nitrogen charge)
• Unit frame is free standing post construction
• Crankcase heaters
• Evaporator fan compartment, interior cabinet surfaces are
insulated with 1/2" minimum thick fiberglass
• Stainless steel condensate drain pan with positive slope
• Multiple scroll compressors with independent circuits.
2 circuits up to 30 ton, 4 circuits above 30 ton
• Anti-short cycle timer, HP and LP switch protection
• Face split coils specially designed for independent,
two-circuit operation
• Unit starts and runs at 125° F ambient outdoor temp
(air cooled)
• Forward curved fans to 4" ESP
• Liquid and discharge service valves
• Pre-wired electrical control center
• Standard IAQ Feature
- Sloped Condensate Pan
- Ventilation Air Capability
- 4" Standard Filters, Easy to Clean Coils and Condensate Pan
- Demand Control Ventilation with IAQ Sensor
• Units may be matched to 09DK condensers
• 50BVU - Constant volume
• 50BVX - VAV
Factory-Installed Options
• Variable frequency drives (standard on 50BVX)
• Alternate horizontal fan position
• Hot gas bypass
• Hot gas reheat for humidity control
• Alternate fan motor drive
• 1 Row steam coils
• Hot water coils 1 or 2 row
• Condensate overflow switch
• Double wall evaporator
• E-Coated coils
Field-Installed Accessories
• Air side economizer and mixing box
• High efficiency filters with 4" deep filter racks
• Heating coils, steam and hot water coils
• Thermostats
- Commercial remote
- Communicating remote
• Commercial Product Guide • 2002 •
85
Performance & Sizing Information
MODEL
50BVU,BVX
TONS
GROSS
COOLING
NOMINAL
AIR FLOW
EER
FAN
HP
WEIGHT
(lbs.)
WIDTH*
(in.)
DEPTH*
(in.)
HEIGHT*
(in.)
024
028
034
044**
048**
054**
064**
20
25
30
40
45
50
60
218,100
278,000
342,100
436,200
496,100
556,000
684,200
8,000
10,000
12,000
16,000
18,000
20,000
24,000
13.0
13.0
13.0
13.0
13.0
13.0
13.0
10
15
15
2 @ 10
2 @ 10
2 @ 15
2 @ 15
2223
2650
2666
4446
4873
5300
5332
69 3/4
69 3/4
69 3/4
139 1/2
139 1/2
139 1/2
139 1/2
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
51 5/8
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
117 1/4
* Unit breaks down into modules to bring into building, see Product Data.
** 4 condenser circuits required.
ELECTRICAL DATA
208/230-3-60
460-3-60
MODEL
50BVU,BVX
RECOMMENDED
CONDENSER
MCA
MOCP
MCA
MOCP
024
09DK024
120.3
150
56.1
70
028
09DK028
144.6
175
70.2
90
034
09DK034
178.6
225
81.4
100
044
(2) 09DK024
219.1
250
109.1
125
048
(2) 09DK028
209.8
250
100.4
125
054
(2) 09DK028
284.9
350
138.7
175
064
(2) 09DK034
345.3
450
158.7
175
86
• Commercial Product Guide • 2002 •
50XJ
Commercial Products
Indoor Packaged Cooling Variable Air Volume Systems
50 to 110 Nominal Tons
Features
Factory-Installed Options
• Quiet scroll compressors on all units
• Multiple compressor sizes per model allow matching load
while retaining optimum partload performance
• Internally spring isolated supply fan selected for peak VAV
operation
• Factory mounted VFD with duct static pressure control
• CCN compatible control system allows integration to VAV
boxes and other system components
• Microprocessor based control of all unit functions and alarms
• 365-day time clock function standard with setpoint
adjustments at unit control panel or remote
• High pressure, low pressure, frost protection and high duct
static protection
• Filter maintenance switch standard
• Stainless steel positively sloped condensate drain pan
• Double wall evaporator construction
• Unit hand-off auto switch standard
• Sound insulated compressor section 3# density
• Water side economizer with control valve package for
constant or variable flow water systems
• Head pressure water regulating valve
• Hot water heating coils
• Steam heating coils
• Optional motor and drive combinations
• High efficiency filters 65% to 85%
• VFD bypass switch
• System integrated controls, control pumps and towers
• High pressure water side condensers (400 PSI)
• Water flow switch
• Oversized VFD drive
• Unit mounted disconnect switch
• Phase loss protection module
• Service valves
• Refrigerant relief connection
• Extended grease service connections
Field-Installed Accessories
• Air side economizer/mixing box (control function provided by
unit control)
• Acoustic discharge plenum in 2" and 4" wall thickness and
variable heights
• Extended depth filter sections (2" pre-filter, 6" or 12" for
cartridge filters)
• Commercial Product Guide • 2002 •
87
Performance & Sizing Information
WATER-COOLED VAV UNITS
UNIT SIZE
NOMINAL
CFM
50XJ-064
20,000
50XJ-074
24,000
50XJ-084
28,000
50XJ-094
30,000
50XJ-104
32,000
COMP.
OPTION
COMPRESSORS
NOMINAL
TONS
C
E
F
B
C
D
E
A
B
C
D
E
F
A
B
C
D
F
A
B
D
E
4 @ 10 hp
2 @ 10 / 2 @ 13 hp
4 @ 13 hp
2 @ 10 / 2 @ 13 hp
4 @ 13 hp
2 @ 13 / 2 @ 15 hp
4 @ 15 hp
4 @ 13 hp
2 @ 13 / 2 @ 15 hp
4 @ 15 hp
2 @ 13 / 2 @ 20 hp
2 @ 15 / 2 @ 20 hp
2 @ 13 / 2 @ 25 hp
4 @ 15 hp
2 @ 13 / 2 @ 20 hp
2 @ 15 / 2 @ 20 hp
2 @ 13 / 2 @ 25 hp
2 @ 15 / 2 @ 25 hp
2 @ 15 / 2 @ 20 hp
2 @ 13 / 2 @ 25 hp
2 @ 15 / 2 @ 25 hp
2 @ 20 / 2 @ 25 hp
50
60
65
60
65
70
75
65
70
75
80
85
90
75
80
85
90
100
85
90
100
110
†
WIDTH
124
84
88
3 1/8
124
84
88
3 1/8
124
84
88
3 1/8
124
84
96
3 1/8
124
84
96
3 1/8
6830
6930
7030
6980
7080
7160
7240
7180
7260
7340
7378
7436
7378
7590
7628
7628
7628
7628
7741
7683
7683
7783
† Weights are base unit and standard motor with no options.
ELECTRICAL DATA
460-3-60
UNIT SIZE
50XJ-064
50XJ-074
50XJ-084
50XJ-094
50XJ-104
COMP OPTION
C
E
F
B
C
D
E
A
B
C
D
E
F
A
B
C
D
F
A
B
D
E
FAN HP
10
10
10
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
MIN. FAN
MCA
85.5
97.5
108.1
103.4
114.0
118.2
122.0
114.0
118.2
122.0
132.6
136.4
151.3
122.0
132.6
136.4
151.3
155.1
141.9
156.8
160.6
173.4
MOCP
100
110
125
125
125
125
125
125
125
125
150
150
175
125
150
150
175
175
150
175
175
200
FAN HP
30
30
30
30
30
30
30
40
40
40
40
40
40
40
40
40
40
40
50
50
50
50
MAX. FAN
MCA
114.9
125.5
136.1
125.5
136.1
139.9
143.7
149.2
153.0
156.8
165.8
169.6
182.4
132.6
165.8
169.6
182.4
186.2
184.6
197.4
201.2
214.0
* Other fan motor size options are availabe. Consult full product data.
88
WATER
HEIGHT CON
NECTION
LENGTH
• Commercial Product Guide • 2002 •
MOCP
150
150
150
150
150
175
175
175
200
200
200
200
225
150
200
200
225
225
225
250
250
250
90MF,MA,MU
Commercial Products
Industrial Water-Cooled Single-Package Cooling Units
R-22, R-407C & R-134a
3 to 10 Nominal Tons
Features
• Ducted or Free Blow Applications
• 4 sizes using R-22 or R-407C and 2 sizes using chlorine-free
R-134a
• Easily removal of interior access panels for easy service
• Quick sensing elements prevent compressor trouble before it
starts
• Quiet fan performance with lower rpm than most comparable
fans
• Specially designed discharge air section for superior airhandling capability especially 3/4" on 3 and 5 ton and 1.2" on
7 1/2 ton and 10 ton
• Cleanable aluminum mesh return air filters
• R-22 units of 10 ton cooling capacity or R-134a 8 ton
capacity are provided with 2 steps of cooling capacity (100%
and 66%)
• Serviceable hermetic or welded hermetic scroll with
suitable vibration isolators
• Crankcase heaters
• Located in sound-attenuated compartment within the cabinet
• Seamless copper tubes
• Thermostatic expansion valve refrigerant control and filter
drier
• Water regulating valve (MA/MF) (field installed)
• Selector switch with internal thermostat
Factory-Installed Options
• Alternate HP motors
• Choice of condenser:
- High-efficiency tube-in-tube Cu-Cu
- High-efficiency tube-in-tube 90-10 Cu-Ni
- Condenserless
Field-Installed Accessories
• Supply-air discharge plenum
• Thermostats
- Commercial remote
- Communicating remote
• Electric heaters
• Evaporator defrost thermostat heating coils
• Remote monitor relays
• Non-standard drive package
• Heating coils
- Steam
- Hot water
90MF208, 308, 212, and 312 sizes use Carrier’s
semi-hermetic 06D compressors
Difference between this unit and others are the compressor
and the condenser
Model MF uses a Copper Condenser
Model MA uses 90-10 Cu-Ni Condenser sea water duty
Model MU condenserless
• Commercial Product Guide • 2002 •
89
Performance & Sizing Information
R-22 and R-407C
MODEL TONS NOM
NO.
CFM
NET COOL
(BTUH)
EER
NOM
GPM
WEIGHT STG
LBS
DENSER
STD. CON
CONN.
FAN
(in.)
DIMENSIONS
(in.)
COMPRESSOR
TYPE
Height
Depth
Length
204
3
1200
36268
11.1
9
390
1
1/3
1/2
Scroll
59 1/8
21 7/8
36 3/16
206
208
212
5
7.5
10
2000
3000
4000
58999
89675
116650
10.8
12.1
11
15
22.5
30
427
895
950
1
1
2
3/4
1
2
3/4
1
1
Scroll
Semi-Hermetic
Semi-Hermetic
59 1/8
69 1/2
69 1/2
21 7/8
29 5/8
29 5/8
36 3/16
48
48
R-134a
MODEL
NO.
TONS
NOM
CFM
NET
COOL
(BTUH)
EER
NOM
GPM
WEIGHT
LBS
STG
FAN
CONDENSER
CONN.
(in.)
COMPRESSOR
TYPE
308
312
5.5
8
2200
3200
62733
83648
12.4
11.9
16.5
24
895
950
1
2
1
2
1
1
Semi-Hermetic
Semi-Hermetic
ELECTRICAL DATA
MODEL NO.
90
208/230-3-60
460-3-60
MCA
MOCP
MCA
MOCP
004
006
008
14.2
29.4
42.5
20
45
70
7.6
17.8
20.4
10
25
35
012
45.5
70
22.7
35
• Commercial Product Guide • 2002 •
DIMENSIONS
(in.)
Height
69 1/2
69 1/2
Depth
29 5/8
29 5/8
Length
48
48
50RHR,RVR
Commercial Products
High-Efficiency
Water Source Heat Pumps
Horizontal - 1/2 to 5 Nominal Tons
Vertical - 1/2 to 5 Nominal Tons
Applications
• Appropriate for all waterloop (boiler/tower) installations
• Flexible solution for all geothermal ground loop and ground
water systems
Features
•
•
•
•
•
•
•
•
•
•
•
•
EER to 13.3 and COP to 4.6 (boiler/tower)
Operating water loop temp. of 20 to 110° F
Horizontal units have field convertible discharge air
Interior surfaces lined with 1/2 in. thick, 1 1/2 lb insulation
3-speed PSC type blower
Vertical units are painted
Compressors are spring mounted and isolated
Horizontal units have factory mounted hanging brackets
Removable blower inlet rings for easy motor and fan removal
Thermostatic expansion valve (TXV)
Enhanced aluminum fin/rifled copper tube air coil
Coaxial refrigerant to water heat exchanger rated
450 psig water side working pressure
• Solid-state Complete “C” control system:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes,
locks out after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
•
•
•
•
•
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
Insulated water circuit for low temperature
PremierLink™ CCN controller
High static blower on size 048
Internally mounted solenoid two-way valve
Internally mounted auto-flow regulator on water side of
coaxial coil
Field-Installed Accessories
•
•
•
•
•
•
•
Stainless steel braided hose kits
Ball valves
Y strainers
Solenoid valves
Hose kit assemblies with GPM Autoflow valves
Aquazone thermostats
Aquazone System Control Panel
Factory-Installed Options
Extended Warranty Protection
• Cupernickel heat exchangers
• Sound attenuation package
• Enhanced Deluxe “D” control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
• Option I – 1st year labor allowance
• Option II – 2nd to 5th year parts and labor allowance
• Option III – Combination of Options I and II
• Commercial Product Guide • 2002 •
91
Performance & Sizing Information
50RHR
WEIGHT
(lbs)
COMP
WATER CONN.
SIZE
FAN
HP
VOLTAGE
006
110
ROTARY
1/2
1/25
112
ROTARY
1/2
1/10
012
121
ROTARY
1/2
1/10
015
147
ROTARY
3/4
1/6
019
169
RECIP.
3/4
1/5
024
193
RECIP.
3/4
1/3
030
219
RECIP.
3/4
1/2
036
229
RECIP.
3/4
3/4
042
257
RECIP.
1
3/4
048
267
RECIP.
1
3/4
060
323
SCROLL
1
1
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
009
SIZE
MCA
4.0
3.5
5.7
5.0
7.5
6.2
8.4
7.7
11.0
9.7
12.1
12.0
8.8
4.9
15.9
14.5
9.9
5.0
20.6
19.5
13.3
6.8
23.2
15.8
7.1
6.1
26.2
19.2
8.9
7.5
36.4
22.7
11.8
9.8
DIMENSIONS (in.)
MOCP
15
15
15
15
15
15
15
15
15
15
20
20
15
15
25
20
15
15
30
30
20
15
35
25
15
15
40
30
15
15
60
35
15
15
Width
Depth
Height
22.4
43.1
11.3
22.4
43.1
11.3
22.4
43.1
11.3
22.4
43.1
17.3
22.4
43.1
17.3
22.4
43.1
17.3
22.4
53.2
19.3
22.4
53.2
19.3
22.4
62.2
19.3
22.4
62.2
19.3
25.4
71.2
21.3
50RVR
WEIGHT
(lbs)
COMP
WATER CONN.
SIZE
FAN
HP
VOLTAGE
009
112
ROTARY
1/2
1/10
121
ROTARY
1/2
1/10
015
147
ROTARY
1/2
1/6
019
169
RECIP.
3/4
1/5
024
193
RECIP.
3/4
1/3
030
219
RECIP.
3/4
1/2
036
229
RECIP.
3/4
3/4
042
257
RECIP.
1
3/4
048
267
RECIP.
1
3/4
060
323
SCROLL
1
1
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
265-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
012
SIZE
MCA
5.7
5.0
7.5
6.2
8.4
7.7
11.0
9.7
12.1
12.0
8.8
4.9
15.9
14.5
9.9
5.0
20.6
19.5
13.3
6.8
23.2
15.8
7.1
6.1
26.2
19.2
8.9
7.5
36.4
22.7
11.8
9.8
15
15
15
15
15
15
15
15
20
20
15
15
25
20
15
15
30
30
15
15
35
25
15
15
40
30
15
15
60
35
15
15
NRTL/C
92
• Commercial Product Guide • 2002 •
DIMENSIONS (in.)
MOCP
Width
Depth
Height
22.4
21.6
22.6
22.4
21.6
22.6
22.4
21.6
34.6
22.4
21.6
34.6
22.4
21.6
34.6
22.4
25.6
40.6
22.4
25.6
40.6
22.4
25.6
48.6
22.4
25.6
48.6
25.4
30.6
50.6
50RDS,RHS,RVS
Commercial Products
Premium-Efficiency
Water Source Heat Pumps
Horizontal - 1 1/4 to 6 Nominal Tons
Vertical - 1 1/4 to 6 Nominal Tons
Downflow - 1 1/4 to 6 Nominal Tons
S
50RD
2!
R 200
O
F
NEW
Applications
• High end unit for installations that require optimum energy
efficiency
• Appropriate in all waterloop (boiler/tower) and geothermal
applications
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
EER to 16 and COP to 5.3 (boiler/tower)
Operating water loop temp. of 20 to 110° F
Horizontal units have field convertible discharge air
Interior surfaces lined with 1/2 in. thick, 1 1/2 lb insulation
Standard scroll compressor (except 015)
3-speed PSC type blower
Horizontal and Vertical units are painted
Compressors are spring mounted and isolated
Horizontal units have factory mounted hanging brackets
Removable blower inlet rings for easy motor and fan removal
Thermostatic expansion valve (TXV)
Enhanced aluminum fin/rifled copper tube air coil
Coaxial refrigerant to water heat exchanger rated
450 psig water side working pressure
• Solid-state Complete “C” control system with:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes,
locks out after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
Factory-Installed Options
• Cupronickel heat exchangers
• Sound attenuation package
• Enhanced Deluxe “D” control system:
- 75VA transformer
- Random start on return from night set back
•
•
•
•
•
•
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
Insulated water circuit for low temperature
application below 60° EWT
PremierLink™ CCN controller
High static blower on sizes 030 and 036
Internally mounted solenoid two-way valve
Internally mounted auto-flow regulator on water side of
coaxial coil
Hot water generator (HWG) coil and temperature switch
Field-Installed Accessories
• Stainless steel braided hose kits
• Ball valves
• Y strainers
• Solenoid valves
• Hose kit assemblies with GPM Autoflow valves
• Aquazone thermostats
• Aquazone System Control Panel
Extended Warranty Protection
• Option I – 1st year labor allowance
• Option II – 2nd to 5th year parts and labor allowance
• Option III – Combination of Options I and II
• Commercial Product Guide • 2002 •
93
Performance & Sizing Information
50RHS
MODEL
NO.
OPERATING
WEIGHT
(lbs)
COMP
015
179
019
189
DIMENSIONS (in.)
WATER
CONN. SIZE
FAN
HP
HP
ROTARY
3/4
1/6
7.2
-
-
15
-
SCROLL
3/4
1/6
9.8
-
-
15
-
MCA*
MOCP*
EER
COP
Width
Depth
Height
-
22.4
53.2
19.3
16.0
5.3
-
22.4
53.2
19.3
14.8
5.0
4.8
024
250
SCROLL
3/4
1/5
13.9
9.9
5
20
15
15
22.4
62.2
19.3
14.9
030
252
SCROLL
3/4
1/3
16.5
10.9
5.7
25
15
15
22.4
62.2
19.3
15.1
4.8
036
266
SCROLL
3/4
1/2
18.6
13.8
6.8
30
20
15
22.4
62.2
19.3
14.9
4.6
042
323
SCROLL
1
1/2
22.6
14.7
7.4
35
25
15
25.4
71.2
21.3
14.6
4.8
048
327
SCROLL
1
3/4
25.9
18.5
9.7
40
30
15
25.4
71.2
21.3
14.6
4.9
060
416
SCROLL
1
3/4
43.6
25
10.2
50
40
15
25.4
76.2
21.3
13.4
4.7
070
443
SCROLL
1
1
40.4
25.9
13.7
60
20
40
25.4
81.2
21.3
12.4
4.5
OPERATING
WEIGHT
(lbs)
COMP
WATER
CONN. SIZE
FAN
HP
HP
EER
COP
015
179
ROTARY
3/4
1/6
7.2
-
-
15
-
-
22.4
25.6
40.6
16.0
5.3
019
189
SCROLL
3/4
1/6
9.8
-
-
15
-
-
22.4
25.6
40.6
14.8
5.0
50RDS,RVS
MODEL
NO.
DIMENSIONS (in.)
MCA*
MOCP*
Width
Depth
Height
024
250
SCROLL
3/4
1/5
13.9
9.9
5
20
15
15
22.4
25.6
44.6
14.9
4.8
030
252
SCROLL
3/4
1/3
16.5
10.9
5.7
25
15
15
22.4
25.6
44.6
15.1
4.8
4.6
036
266
SCROLL
3/4
1/2
18.6
13.8
6.8
30
20
15
22.4
25.6
48.6
14.9
042
323
SCROLL
1
1/2
22.6
14.7
7.4
35
25
15
25.4
30.6
50.6
14.5
4.8
048
327
SCROLL
1
3/4
25.9
18.5
9.7
40
30
15
25.4
30.6
50.6
14.6
4.9
060
416
SCROLL
1
3/4
43.6
25
10.2
50
40
15
25.4
30.6
54.6
13.4
4.7
070
443
SCROLL
1
1
40.4
25.9
13.7
60
20
40
25.4
30.6
54.6
12.4
4.5
*Data rated for voltages 208-230/60/1, 208-230/60/3, 460/60/3 only.
All ratings based on ARI/ASHRAE/ISO 13256-1 water loop conditions.
NRTL/C
94
• Commercial Product Guide • 2002 •
50RHC,RVC
Commercial Products
Standard-Efficiency
Water Source Heat Pumps
Horizontal - 1-1/2 to 5 Nominal Tons
Vertical - 1-1/2 to 5 Nominal Tons
NEW
002!
2
R
O
F
Applications
• Appropriate for all waterloop (boiler/tower) installations
• Flexible compact cabinet for all replacement and retrofit
projects
Features
•
•
•
•
•
•
•
•
•
•
•
•
EER to 12.3 and COP to 4.3 (boiler/tower)
Operating water loop temp. of 60 to 95° F
Horizontal units have field convertible discharge air
Interior surfaces lined with 1/2 in. thick, 1 1/2 lb insulation
3-speed PSC type blower
Vertical units are painted
Compressors are grommet mounted and isolated
Horizontal units have factory mounted hanging brackets
Removable blower inlet rings for easy motor and fan removal
Capillary tube expansion device
Enhanced aluminum fin/rifled copper tube air coil
Coaxial refrigerant to water heat exchanger rated
450 psig water side working pressure
• Solid-state Complete “C” control system:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes,
locks out after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
Factory-Installed Options
• Sound attenuation package
• Enhanced Deluxe “D” control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
• PremierLink™ CCN controller
• High static blower on all sizes
Field-Installed Accessories
•
•
•
•
•
•
•
Stainless steel braided hose kits
Ball valves
Y strainers
Solenoid valves
Hose kit assemblies with GPM Autoflow valves
Aquazone thermostats
Aquazone System Control Panel
Extended Warranty Protection
• Option I – 1st year labor allowance
• Option II – 2nd to 5th year parts and labor allowance
• Option III – Combination of Options I and II
• Commercial Product Guide • 2002 •
95
Performance & Sizing Information
Rated Performance Under ARI/ISO-13256-2 Conditions
MODEL
50RHC,RVC
LIQUID FLOW
(gpm)
WATER LOOP HEAT PUMP
AIR
FLOW
(cfm)
COOLING 86° F
HEATING 68° F
CAPACITY
Btuh
EER
Btuh/W
CAPACITY
Btuh
COP
018
4.5
600
18,200
12.1
22,600
4.2
024
6.0
800
23,800
12.2
27,800
4.3
030
7.5
1000
28,300
12.0
32,900
4.3
036
9.5
1250
35,000
12.0
46,800
4.2
042
11.0
1350
41,000
12.0
52,600
4.2
048
12.0
1600
47,100
12.2
58,000
4.3
060
15.0
2000
58,000
12.3
69,500
4.3
ARI/ASHRAE/ISO 13256-1 English (IP) Units.
Not Rated in Ground Water or Ground Loop Heat Pump applications of
ARI/ASHRAE/ISO 13256-1.
Intended for use only in applications with EWT ranges of 60° F to 95° F.
Cooling capacities based upon 80.6° F DB, 66.2° F WB entering air temperature.
Heating capacities based upon 68° F DB, 59° F WB entering air temperature.
All air flow rated on high speed.
All ratings based upon operation at lower voltage of dual voltage rated models.
ELECTRICAL DATA
MODEL
50RHC,RVC
018
024
030
036
042
048
060
COMPRESSOR
FAN
MOTOR
FLA
1.00
MIN
CIRC
AMP
10.9
MAX
FUSE/
HACR
15
8.0
9.7
15
10.2
9.6
12.4
11.7
20
15
TOTAL
UNIT
FLA
8.9
VOLT
CODE
RATED
VOLTAGE
VOLTAGE
MIN/MAX
QTY
RLA
LRA
G
208-230/60/1
197/254
1
7.9
48.3
E
265/60/1
239/292
1
7.1
41.0
0.86
G
E
208-230/60/1
265/60/1
197/254
239/292
1
1
8.7
8.3
48.3
47.0
1.50
1.30
H
208-230/60/3
197/254
1
6.0
50.0
1.50
7.5
9.0
15
F
460/60/3
414/506
1
3.2
25.0
0.70
3.9
4.7
15
G
E
208-230/60/1
265/60/1
197/254
239/292
1
1
11.2
10.3
60.0
58.0
3.00
2.70
14.2
13.0
17.0
15.6
25
15
H
208-23-/60/3
197/254
1
6.4
50.0
3.00
9.4
11.0
15
F
460/60/3
414/506
1
3.2
25.0
1.70
4.9
5.7
15
G
E
208-230/6-/1
265/60/1
197/254
239/292
1
1
14.7
13.5
84.0
83.0
1.80
2.00
16.5
15.5
20.2
18.8
30
30
H
208-230/60/3
197/254
1
8.7
63.4
1.80
10.5
12.6
20
F
460/60/3
414/506
1
4.5
36.0
1.24
5.7
6.8
15
G
H
208-230/60/1
208-230/60/3
197/254
197/254
1
1
17.1
10.7
105.0
85.0
3.00
3.00
20.1
13.7
24.3
16.4
40
25
15
F
460/60/3
414/506
1
5.3
42.0
1.70
7.0
8.3
G
208-230/60/1
197/254
1
18.3
102.0
3.40
21.7
26.3
40
H
F
208-230/60/3
460/60/3
197/254
414/506
1
1
12.6
5.7
91.0
42.0
3.40
1.80
16.0
7.5
19.2
8.9
30
15
G
208-230/60/1
197/254
1
25.6
170.0
4.30
29.9
36.3
60
H
208-230/60/1
197/254
1
14.7
124.0
4.30
19.0
22.7
35
F
460/60/3
414/506
1
7.4
59.6
2.50
9.9
11.8
15
NRTL/C
96
• Commercial Product Guide • 2002 •
50RWS
Commercial Products
Water-to-Water
Water Source Heat Pump
3 to 10 Nominal Tons
NEW 2!
00
FOR 2
Applications
• Used to provide both chilled and hot water to other hydronic
equipment (air handlers, fan coils, etc)
• Adaptable in stand alone boiler/chiller applications or serving
process related equipment
Features
• EER to 14.3 and COP to 5
• Rated in accordance with ARI/ASHRAE/ISO 13256-1
• Scroll compressors standard
• 3, 5, and 10 nominal ton sizes available
• Extended range (20° F to 110° F) standard
• Thermostatic expansion valve (TXV)
• Copper load coaxial coil
• Copper source coaxial coil
• 3-sided compressor access
• External cabinet fault indicator and compressor run LED's
• Can be installed in parallel or series operation to increase
capacity or leaving water temperature
• Stackable cabinet
• Solid-state complete "C" control system:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes, locks out
after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
Factory-Installed Options
• Choice of cupronickel or copper double vented lead coil
• Cupronickel for source coaxial coil
• Sound attenuation package
• Enhanced Deluxe "D" control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input
- Pump restart
• PremierLink™ CCN controller
• Water connections on front, left, right, or back (120 only)
Field-Installed Accessories
• Stainless steel braided hose kits
• Ball valves
• Y strainers
• Solenoid valves
• Hose kit assemblies with GPM Autoflow valves
• Aquazone thermostats
• Aquazone System Control Panel
Extended Warranty Protection
• Option I – 1st year labor allowance
• Option II – 2nd to 5th year parts and labor allowance
• Option III – Combination of Options I and II
• Commercial Product Guide • 2002 •
97
Performance & Sizing Information
MODEL
TONS
50RWS036
50RWS060
50RWS120
3
5
10
OPERATING
WEIGHT
(lbs)
236
343
725
WATER
CONNECTIO
SIZE (in.)
3/4
1
1-1/2
TOTAL
COOLING
(Btuh)
29,000
44,000
88,600
EER
TOTAL
HEATING
COP
14.3
12.0
11.6
43,000
63,300
126,900
5.0
4.2
4.1
DIMENSIONS (in.)
Height
Depth
Width
29.5
33
40.1
25.6
30.6
41.1
22.4
25.4
26
All ratings based on ARI/ASHRAE/ISO 13256-1 water loop conditions and 208V operation.
ELECTRICAL DATA
MODEL
50RWS036
50RWS060
50RWS120
RATED
VOLTAGE
208/230-60-1
265/277-60-1
208/230-60-3
460-60-3
208/230-60-1
208/230-60-3
460-60-3
575-60-3
208/230-60-1
208/230-60-3
460-60-3
575-60-3
VOLTAGE
MIN/MAX
197/254
239/292
187/254
414/506
197/254
187/254
414/506
518/633
197/254
187/254
414/506
518/633
MCA
MOCP
18.8
17.9
13.4
6.3
35.0
24.1
9.4
8.0
63.0
43.4
16.9
14.4
30
30
20
15
60
40
15
15
90
60
20
20
NRLT/C
98
• Commercial Product Guide • 2002 •
WATER
FLOW
GPM
9
15
30
50HQL,VQA,VQD
Commercial Products
Large-Capacity
Water Source Heat Pumps
Horizontal - 6 to 10 Nominal Tons
Vertical - 6 1/2 to 25 Nominal Tons
L
50HQ
002!
2
R
O
F
NEW
Applications
• Used for conditioning larger areas
• Appropriate for all waterloop (boiler/tower) and geothermal
applications
Features
• EERs to 14 and COPs to 4.2 (boiler/tower)
• Standard heat exchanger material is Cu/Cu tube and tube
on closed or open loop applications with 400 psi working
pressure
• Compressors are spring mounted and isolated
• 3 horizontal and 7 vertical units
• Standard 50VQA temperature 60° to 90° F
• 50VQD units with range of 40° to 110° F
• 50HQL units with range of 20° to 110° F
• Dual refrigerant circuits 8 tons and above
• Scroll compressors on 50HQL 096 and 120
• Water-to-refrigerant heat exchanger has Cu inner and steel
outer tubing
• 3-sided compressor section access on horizontal units
• Large service access panels for easy maintenance
• Filter tracks permit easy filter replacement
• Solid state Complete “C” control system with:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes, locks out
after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
• Five blower drive options for high static flexibility
• Sound attenuation package
• Enhanced Deluxe “D” control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
• PremierLink™ CCN controller
Field-Installed Accessories
•
•
•
•
•
•
Stainless steel braided hose kits
Ball valves
Y strainers
Solenoid valves
Aquazone thermostats
Aquazone System Control Panel
Factory-Installed Options
Extended Warranty Protection
• Return-air configurations (vertical only)
- sizes 080-240, return rear or front, discharge rear,
front, or top
- size 300, return rear or front, discharge top
• Cupronickel heat exchangers
•
•
•
•
Option I –
Option II –
Option III –
Option IV–
• Commercial Product Guide • 2002 •
1st year labor allowance
2nd to 5th year parts and labor allowance
Combination of Options I and II
2nd to 5th year parts and labor allowance
on compressor only (VQ160-300 sizes)
99
Performance & Sizing Information
VERTICAL UNITS - PHYSICAL DATA
MODEL
NO.
50VQ
080
100
120
160
200
240
300
IGHT FAN
TONS W(Elb
s)
HP
HP
6 1/2
8 1/2
10
13
17
20
25
595
685
735
1120
1265
1350
1465
1.5
1.5
2.0
3.0
1.5
2.0
3.0
COOLING
TC
TC
(Btuh)
74,400
100,000
120,000
148,000
202,000
240,000
300,000
EER
14.0
11.4
11.2
14.0
11.5
11.4
10.0
HEATING
TC
TC
(Btuh)
82,500
125,000
143,000
166,000
218,000
270,000
360,000
COP
CFM
4.2
3.8
3.8
4.2
3.8
3.8
3.2
2600
3500
4200
5200
7000
8400
9000
DIMENSIONS (in.)
HEIGHT
DEPTH
WIDTH
69 3/4
69 3/4
69 3/4
70 3/4
70 3/4
70 3/4
70 3/4
29
29
29
29
29
29
29
41
41
41
82
82
82
82
WATER
CONNECTIONS
(in.)
1 1/4
1 1/4
1 1/4
1 1/2
1 1/2
1 1/2
1 1/2
VERTICAL UNITS - ELECTRICAL DATA
208/230-3-60
MODEL NO.
50VQ
MCA
32
41.5
50.3
56.1
75.9
92
113.5
030
100
120
160
200
240
300
460-3-60
MOCP
50
60
80
70
100
125
150
MCA
15.5
21.1
25.2
27.3
38.6
46.1
71.5
575-3-60
MOCP
25
30
40
35
50
60
90
MCA
12.7
16.7
19.4
22.4
30.5
35.5
57.3
MOCP
20
25
30
30
40
45
70
HORIZONTAL UNITS - PHYSICAL DATA
MODEL
LING
IGHT FAN COO
NO.
TONS W(Elb
TC
TC
s
)
HP
H
P
50HQ
(Btuh)
072
096
120
6
8
10
615
580
630
1.5
2
2
69,000
94,600
120,000
EER
HEATING
TC
TC
(Btuh)
COP
CFM
11.0
12.8
12.7
88,000
106,700
137,800
3.8
4.4
4.2
2400
3200
4000
DIMENSIONS (in.)
HEIGHT
21
21
21
DEPTH
36
36.3
36.3
WIDTH
72.3
72.3
72.3
HORIZONTAL UNITS - ELECTRICAL DATA
MODEL NO.
50HQ
208/230-3-60
460-3-60
575-3-60
MCA
MOCP
MCA
MOCP
MCA
MOCP
072
29.6
40
13
15
NA
NA
096
38.7
50
19.3
25
15.6
20
120
49.9
60
20
25
17.2
50
NRLT/C
100
• Commercial Product Guide • 2002 •
WATER
CONNECTIONS
(in.)
1-1/4
1-1/4
1-1/4
50KQA, KQD
Commercial Products
Console
Water Source Heat Pumps
1/2 to 1 1/2 Nominal Tons
Applications
• For use in under windows or other installations in finished
interior space
• Appropriate for waterloop (boiler/tower) and all geothermal
applications
Features
• EER to 12.8 and COP to 4.6
• 50KQA standard temp 60-90° F
• 50KQD low temp 40-110° F
• Compact cabinet design of 10" deep, 48" wide, and 23" tall
with a 3" subbase
• Fan Motor sleeve bearings permanently lubricated
• Large service access panels
• Lock-out relay
• Loss of charge protection
• Service access ports on both the suction and discharge
refrigerant lines
• Water-to-refrigerant heat exchanger has copper inner
and steel outer tubing
• Standard line voltage internally mounted thermostat
• Fan speed selection
• Solid state Complete "C" control system with:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Option to reset unit at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes, locks out
after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
- Electric heat controls/output
• Automatic Changeover (ACO)
• Available fused or unfused disconnect switch
• Water connections can be mounted left or right side
• Cupronickel heat exchangers
• Remote thermostat capability
• Internally mounted auto flow regulator on water side of
coaxial coil
• Enhanced Deluxe “D” control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
• PremierLink™ CCN controller
Field-Installed Accessories
• Remote Thermostat
• Adjoining room kit
• Aquazone System Control Panel
• Hose kits
• Ball valves
• Solenoid valves
Factory-Installed Options
Extended Warranty Protection
• Locking control panel
• Motorized fresh air dampers
• Internally mounted solenoid two-way valve
• Option I – 1st year labor allowance
• Option II – 2nd to 5th year parts and labor allowance
• Option III – Combination of Options I and II
• Commercial Product Guide • 2002 •
101
Performance & Sizing Information
STANDARD AND LOW TEMPERATURE
MODEL
50KQA,
KQD
COOLING
TC
TC
(Btuh)
EER
HEATING
TC
TC
(Btuh)
COP
CFM
GPM
NOM.
CAP.
WEIGHT
(lbs)
FAN
HP
HP
WATER
CONN.
(in.)
07
09
12
15
19
7,200
9,200
11,600
14,200
16,900
12.2
12.5
11.5
12.0
11.3
9,200
11,400
13,500
17,200
21,300
4.3
4.2
4.0
4.0
3.8
275
275
350
395
395
1.7
2.3
3.0
3.8
4.5
3/4
3/4
1
1 1/4
1 1/2
151
154
164
168
174
1/20
1/20
1/15
1/15
1/15
5/8
5/8
5/8
5/8
5/8
ELECTRICAL DATA
MODEL
50KQA,
KQD
07
09
12
15
19
208/230-1-60
MCA
4.3
6
6.6
9.3
11.5
MOCP
15
15
15
15
15
265-1-60
MCA
4.0
4.5
5.9
7.3
8.8
MOCP
15
15
15
15
15
115-1-60
MCA
8.5
10.9
14.0
NA
NA
MOCP
15
15
15
NA
NA
NRLT/C
102
• Commercial Product Guide • 2002 •
DIMENSIONS (in.)
WIDTH HEIGHT
48
24
48
24
48
24
48
24
48
24
DEPTH
10
10
10
10
10
50RTG
Commercial Products
Outdoor Rooftop
Water Source Heat Pump
3 to 20 Nominal Tons
Applications
• Use for larger zone requirements and to provide
ventilation air
• Appropriate for waterloop (boiler/tower) and all
geothermal applications
Features
• EER to 15.7, and COP to 5.1
• Entering fluid temp of 20° to 110° F
• Dedicated Down Discharge Air Flow
• Dual refrigeration circuits 8 tons and above
• All piping and electrical connections are made through
bottom of unit
• Scroll compressor spring mounted on isolation rails
• Slide-out blower assembly allows for quick
adjustment of drive components
• Insulated basepan
• Belt drive evaporator motor with variable pitch sheaves
• Water-to-refrigerant heat exchanger has copper inner and steel
outer tubing
• Large side doors for easy access to fan motor and controls
• Heavy duty steel cabinet with corrosion resistant powder
coat finish
• Solid state Complete "C" control system with:
- 50VA transformer
- Anti-short cycle timer
- Random start relay
- High and low voltage protection
- High and low pressure protection
- Water coil freeze protection
- Air coil freeze protection
- Condensate overflow sensor
- Unit to reset at thermostat or disconnect
- Automatic intelligent reset. Resets 5 minutes, locks
out after 3 faults
- Service Test mode
- LED fault and status lights
- Selectable 24 V or pilot duty dry contact alarm output
Factory-Installed Options
• 2" or 4" Pleated Filter Options
• Manual outside air damper up to 20% with rain
hood and bird screen
• Two position motorized fresh air damper
• Low maintenance and corrosion resistant ABS
gear driven dampers
• Fully modulating enthalpy controlled economizer supplied
with direct gear driven outdoor air, return air and gravity
relief dampers
• Enhanced Deluxe "D" control system:
- 75VA transformer
- Random start on return from night set back
- Night set back with thermostat override
- Boilerless system control
- 24 V output to cycle a motorized water valve/damper
with compressor contactor
- Emergency shutdown
- Dehumidistat input and fan speed control
- Pump restart
• Internally mounted solenoid two-way valve
• Optional motor and drives
• Disconnects
• Cupro-Nickel Condenser Coil
• PremierLink™ CCN controller
Field-Installed Accessories
• Roof Curb
• Aquazone Thermostats
• Aquazone System Control Panel
• Stainless steel braided hose kits
• Hose kit assemblies with GPM autoflow valves
Extended Warranty Protection
•
•
•
•
Option I –
Option II –
Option III –
Option IV–
• Commercial Product Guide • 2002 •
1st year labor allowance
2nd to 5th year parts and labor allowance
Combination of Options I and II
2nd to 5th year parts and labor allowance
on compressor only (RTG12, 15, 20 sizes)
103
Performance & Sizing Information
50RTG
SIZE
03
04
05
07
08
10
12
15
20
208/230-3-60
460-3-60
575-3-60
DIMENSIONS (in.)
NOM.
TONS
MCA
MOCP
MCA
MOCP
MCA
MOCP
Height
Width
Depth
WEIGHT
(lbs)
03
04
05
07
08
10
12
15
20
17
21
28.6
32.1
37.5
51.2
52.6
55.8
88.1
25
30
45
50
50
70
70
70
125
8.1
9.8
11.2
15.6
17.5
20
26.8
26.8
44.9
15
15
15
25
20
25
35
35
60
NA
8.2
9.6
12.6
14.2
16.7
21
21.9
34.4
NA
15
15
20
15
20
25
30
45
39.52
39.52
39.52
39.52
45.4
45.4
45.4
50.62
50.62
43.9
43.9
43.9
43.9
49.9
49.9
49.9
88
88
81
81
81
81
81
91.07
91.07
91.07
91.07
735
785
835
880
1080
1125
1175
1770
1960
SIZE
COOLING
(Btuh)
EER
03
04
05
07
08
10
12
15
20
33,400
45,600
58,100
78,800
91,900
119,100
133,100
175,700
249,700
13.5
14.7
13.4
13.4
14.7
13.6
13.4
15.7
14.2
HEATING
TOTAL
(Btuh)
38,300
52,200
68,000
90,900
96,700
129,900
148,200
175,700
267,100
COP
CFM
GPM
FAN
HP
HP
WATER CONN.
(in.)
4.8
5.1
4.5
4.4
4.6
4.2
4.3
5.0
4.5
1200
1600
2000
2600
3200
4000
4800
6000
8000
8.4
11.2
14.7
19.9
22.7
29.7
33.2
43.0
62.0
1
1
1
2
2
2
3
3
5
3/4
3/4
1
1 1/4
1 1/4
1 1/2
1 1/2
2
2
All ratings based on ARI/ASHRAE/ISO 13256-1 water loop conditions.
NRLT/C
104
• Commercial Product Guide • 2002 •
38AKS
Commercial Products
Outdoor Air-Cooled Condensing Units
12 1/2 to 40 Nominal Tons
Features
Factory-Installed Options
• Serviceable Semi-Hermetic Compressor
• Functional Run Test
• “Weather Armor” Baked Enamel Finish
• Single Refrigerant Circuit
• ARI Capacity Certified
• Assured Quality (ISO 9002)
• Matched Ratings With 40RM Fan Coil Unit
• Compact Design
• Easy Access to Compressor and Controls
• Service Valves
• Numerous Control Options:
- Programmable
- Communicating
- Electro Mechanical
• Enviro-Shield™ Condenser Coil Corrosion Protection
• Aluminum or Copper Fin Coils
Field-Installed Accessories
• VAV Application (028-044)
• Part-Wind Start (028-044)
• Gauge Panel
• Hot Gas Bypass
• Low Ambient Control
• Additional Unloaders
• Condenser Coil Grille (013-024)
• Commercial Product Guide • 2002 •
105
Performance & Sizing Information
PERFORMANCE
MODEL
38AKS014
38AKS016
38AKS024
38AKS028
38AKS034
38AKS044
CAPACITY
TONS
12.5
15
20
25
30
40
TYPICAL REFRIG
OPS CHARGE (lbs) CONNECT
23
1 3/8
23
1 3/8
28
1 5/8
30.5
1 5/8
43.5
2 1/8
65
2 1/8
(SWEAT) in. OD
5/8
5/8
5/8
7/8
7/8
7/8
3/8
3/8
3/8
5/8
5/8
5/8
TOTAL OP. WEIGHT (lbs)
779
789
900
1650
1803
2437
919
929
1040
1804
2009
2745
OVERALL DIMENSIONS
MODEL
LENGTH
HEIGHT
WIDTH
38AKS014
38AKS016
38AKS024
38AKS028
38AKS034
38AKS044
6' - 4 1/4"
6' - 4 1/4"
6' - 4 1/4"
10' - 7 13/16"
10' - 7 13/16"
14' - 6 1/8"
3' - 3 7/8"
3' - 3 7/8"
3' - 3 7/8"
3' - 8 13/16"
3' - 8 13/16"
3' - 8 13/16"
3' - 7"
3' - 7"
3' - 7"
5' - 8 9/16"
5' - 8 9/16"
5' - 8 9/16"
ELECTRICAL DATA
MODEL
38AKS014
38AKS016
38AKS024
38AKS028
38AKS034
38AKS044
MCA
208/230
69.3
87.5
93.4
124.6
145.5
203
MOCP
MCA 460
MOCP
MCA 575
MOCP
100
125
150
200
250
350
31.7
40.7
48.1
60.7
68.7
91
50
60
80
100
110
150
25.6
33
40.1
52.5
54.9
81.5
40
50
60
80
90
125
Nominal voltages: 3ph, 60hz
MCA = Minimum Circuit Amps
MOCP = Maximum Overcurrent Protection
Rated in accordance
with ARI Standard
365, up to 240,000
Btuh/hr
(60 Hz Only)
106
• Commercial Product Guide • 2002 •
38AH
Commercial Products
Outdoor Air-Cooled Condensing Units
20 to 130 Nominal Tons
Features
Factory-Installed Options
• Serviceable Semi-Hermetic Compressors
• Functional Run Test
• “Weather Armor” Baked Enamel Finish
• Dual Refrigerant Circuit
• ARI Capacity Certified to 240 MBH
• Assured Quality (ISO 9002)
• Compact Design
• Easy Access to Compressor and Controls
• Service Valves
• Numerous Control Options:
- Programmable
- Communicating
- Electro Mechanical
•
•
•
•
VAV Application
Single Refrigerant Circuit (sizes 044-084)
Enviro-Shield™ Condenser Coil Protection
Aluminum or Copper Fin Coils
Field-Installed Accessories
•
•
•
•
•
•
Sound Reduction Package (sizes 044-134)
Condenser Coil Protective Grille (sizes 044-134)
Condenser Coil Hail Guard (sizes 044-134)
Gauge Panel
Low Ambient Control
Additional Unloaders
• Commercial Product Guide • 2002 •
107
Performance & Sizing Information
PERFORMANCE
MODEL
ICAL
CAPACITY RETFYRPIG
. OPS
(Tons)
CHARGE (lbs)
38AH024
38AH028
38AH034
38AH044
38AH054
38AH064
38AH074
38AH084
38AH094
38AH104
38AH124
38AH134
20
25
30
40
50
60
70
80
90
100
120
130
CONNECT (SWEAT)
in. OD
TOTAL OP. WEIGHT
(lbs)
Suction
Liquid
HGBP
AL Coil
CU Coil
1 3/8
1 3/8
1 3/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
5/8
5/8
5/8
3/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1760
1820
1880
3259
3309
3565
3812
4059
5088
5435
7260
7507
1923
1982
2097
3547
3597
3998
4229
4735
5813
6160
8126
8357
40
40
50
62
72
88
104
130
148
135
176
192
Ratings based on 45° F SST and 95° F Ent. Air Temperature & 60 Hz power supply
OVERALL DIMENSIONS
MODEL
38AH024
38AH028
38AH034
38AH044
38AH054
38AH064
38AH074
38AH084
38AH094
38AH104
38AH124
38AH134
LENGTH
10' - 7 13/16"
10' - 7 13/16"
10' - 7 13/16"
8' - 3 9/16"
8' - 3 9/16"
8' - 3 9/16"
10' - 3 1/4"
10' - 3 1/4"
11' - 2 1/2"
11' - 2 1/2"
18' - 6 3/8"
20' - 6 1/8"
HEIGHT
4' - 7 5/8"
4' - 7 5/8"
4' - 7 5/8"
6' - 7 1/4"
6' - 7 1/4"
6' - 7 1/4"
7' - 3 3/8"
7' - 3 3/8"
7' - 11 9/16"
7' - 11 9/16"
6' - 7 1/4"
7' - 3 3/8"
WIDTH
5' - 8 9/16"
5' - 8 9/16"
5' - 8 9/16"
7' - 4 11/16"
7' - 4 11/16"
7' - 4 11/16"
7' - 4 11/16"
7' - 4 11/16"
7' - 8"
7' - 8"
7' - 4 11/16"
7' - 4 11/16"
ELECTRICAL DATA (DUAL CIRCUIT)
208/230
460
575
MODEL
38AH024
38AH028
38AH034
38AH044
38AH054
38AH064
38AH074
38AH084
38AH094
38AH104
38AH124A
38AH124B
38AH134A
38AH134B
MCA
MOCP
MCA
MOCP
MCA
MOCP
100.8
110.5
135.5
174.6
201.8
244
322.3
363.3
391.3
392.2
244
244
244
322.3
125
150
175
225
250
350
450
500
500
500
350
350
350
450
50.3
55.9
65.8
88.9
100.1
113.1
145
163.6
179.5
192.7
113.1
113.1
113.1
145
60
70
90
110
125
150
200
225
225
225
150
150
150
200
42.1
47.1
53.3
78.4
88
100.6
132.2
148.9
160.9
168
100.6
100.6
100.6
132.2
50
60
70
90
125
125
175
200
200
200
125
125
125
175
38AH 124 and 134 consist of two
components
MCA = Minimum Circuit Amps
MOCP = Maximum Overcurrent
Protection
Rated in
accordance with
ARI Standard
360/365
(60 Hz Only)
108
• Commercial Product Guide • 2002 •
38ARZ, ARS
Commercial Products
Split-System Condensing Units
6, 7 1/2 and 10 Nominal Tons (38ARZ)
7 1/2, 8 1/2 and 10 Nominal Tons (38ARS)
38ARZ007-012
38ARS008-012
Features
Factory-Installed Options
• EERs exceed ASHRAE 90.1 requirements
• Compact, low profile design allows installation in a
variety of locations
• Scroll (38ARZ) or semi-hermetic (38ARS) compressor,
whatever your customer's preference
• Single refrigerant circuits for simplicity
• Multiple condenser fans for superior head pressure control
• Factory-Installed Options (FIOPS) reduce installed costs
• Equipped with suction, discharge and liquid service
valves for easy servicing
• Simple control interface ensures compatibility with a
variety of control methods
• All units receive a functional run test prior to leaving
the factory
• Low ambient controls
• Non-fused disconnect
• 115 V GFI convenience outlet
• Enviro-Shield™ coil protection
Field-Installed Accessories
• Coil guard to protect the coil from large
objects and vandalism
• Hail guard to protect the coil from hail damage
• Thermostats
• Commercial Product Guide • 2002 •
109
Performance & Sizing Information
CONDENSING
UNIT
AIR HANDLER/
INDOOR COIL
38ARZ007
SYSTEM
Net Cap.
(Btuh)
EER
28LA008
40RM007
40RM007H
40RM008
40RM008H
66,000
69,000
72,000
70,000
73,000
38ARZ008
40RM007
40RM007H
40RM008
40RM008H
40RM012
40RM012H
CONDENSING UNIT ONLY
IPLV
Net Cap.
(Btuh)
EER
IPLV
10.3
11.0
11.2
11.1
11.3
N/A
N/A
N/A
N/A
N/A
72,000
12.4
N/A
89,000
93,000
90,000
94,000
93,000
98,000
10.5
11.1
10.6
11.2
10.6
11.1
N/A
N/A
N/A
N/A
N/A
N/A
100,000
12.7
N/A
38ARS008
28CB012
28LA012
40RM008
40RM008H
40RM012
40RM012H
89,000
89,000
89,000
94,000
93,000
98,000
10.4
10.4
10.9
11.2
10.9
11.0
N/A
N/A
N/A
N/A
N/A
N/A
97,000
12.8
N/A
38ARS009
40RM012
40RM012H
111,000
116,000
10.3
10.5
N/A
N/A
122,000
12.0
N/A
38ARZ012
40RM012
40RM012H
40RM014
40RM014H
118,000
125,000
123,000
129,000
10.3
10.4
10.4
10.7
N/A
N/A
N/A
N/A
133,000
12.4
N/A
38ARS012
40RM012
40RM012H
40RM014
40RM014H
114,000
119,000
118,000
125,000
10.3
10.3
10.4
10.3
13.1
13.6
14.1
14.5
124,000
12.0
16.5
ELECTRICAL DATA
UNIT
SIZE
38ARZ007
38ARZ008
38ARZ012
38ARS008
38ARS009
38ARS012
OVERALL DIMENSIONS
FACTORYINSTALLED
OPTION
NOMINAL
VOLTAG
V-Ph-Hz
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230-3-60
460-3-60
575-3-60
400-3-50
208/230-3-60
460-3-60
575-3-60
400-3-50
208/230-3-60
460-3-60
575-3-60
400-3-50
208/230-3-60
460-3-60
575-3-60
400-3-50
208/230-3-60
460-3-60
575-3-60
400-3-50
208/230-3-60
460-3-60
575-3-60
400-3-50
VOLTAGE
POWER
FAN MOTORS
COMPRESSOR
(Qty 2)
SUPPLY
RANGE
MIN MAX RLA
LRA
FLA (ea) LRA (ea) MCA MOCP
25.8
35
146
0.9
1.6
187
254 19.2
30.6
35
12.8
20
418
506
9.6
73
0.4
0.9
15.0
20
10.2
15
523
632
7.7
58.4
0.4
0.9
12.0
15
12.8
20
360
440
9.6
73
0.4
0.9
15.0
20
35.0
60
190
1.5
3.1
187
254 25.6
39.8
60
17.4
30
418
506 12.8
95
0.7
1.9
19.6
30
13.8
20
523
632 10.2
76
0.7
1.9
15.5
20
17.4
30
360
440 12.8
95
0.7
1.9
19.6
30
50.3
60
239
1.5
3.1
187
254 37.8
55.1
70
22.9
30
418
506 17.2
125
0.7
1.9
25.1
30
17.8
25
523
632 13.4
80
0.7
1.9
19.5
25
22.9
30
360
440 17.2
125
0.7
1.9
25.1
30
38.3
60
160
1.5
3.1
187
254 28.2
43.1
60
19.0
25
418
506 14.1
80
0.7
1.9
21.2
25
15.2
20
523
632 11.3
64
0.7
1.9
16.9
20
19.0
25
360
440 14.1
80
0.7
1.9
21.2
25
48.0
60
198
1.5
3.1
187
254
36
52.8
70
23.9
35
418
506
18
99
0.7
1.9
26.1
35
18.6
30
523
632
14
79
0.7
1.9
20.3
30
23.9
35
360
440
18
99
0.7
1.9
26.1
35
48.0
60
198
1.5
3.1
187
254
36
52.8
70
23.9
35
418
506
18
99
0.7
1.9
26.1
35
18.6
30
523
632
14
79
0.7
1.9
20.3
30
23.9
35
360
440
18
99
0.7
1.9
26.1
35
MODEL
LENGTH WIDTH HEIGHT
(in.)
(in.)
(in.)
38ARZ007
59.42
45.78
38ARZ,ARS008
59.42
45.78
34.38
34.38
38ARS009
59.42
45.78
34.38
38ARZ,ARS012
59.42
45.78
34.38
Rated in
accordance with
ARI Standard 210
(60 Hz Only)
110
• Commercial Product Guide • 2002 •
38ARD
Commercial Products
Split-System Condensing Units
Dual Refrigeration Circuits
10 to 20 Nominal Tons
38ARD012
38ARD014-024
Features
Factory-Installed Options
• EERs exceed ASHRAE 90.1 requirements
• Compact, low profile design allows installation in a
variety of locations
• Scroll compressors
• Dual refrigerant circuits allow redundancy and better control
• Multiple condenser fans for superior head pressure control
• Factory-Installed Options (FIOPS) reduce installed costs
• Equipped with suction, discharge and liquid service valves for
easy servicing
• Simple control interface ensures compatibility with a variety
of control methods
• All units receive a functional run test prior to leaving
the factory
• Low ambient controls
• Non-fused disconnect
• 115 V GFI convenience outlet
• Enviro-Shield™ coil protection
Field-Installed Accessories
• Coil guard to protect the coil from large objects
and vandalism
• Hail guard to protect the coil from hail damage
• Thermostats
• Commercial Product Guide • 2002 •
111
Performance & Sizing Information
CONDENSING
UNIT
AIR HANDLER/
INDOOR COIL
SYSTEM
Net Cap.
(Btuh)
EER
38ARD012
40RM012
40RM012H
40RM014
40RM014H
113,000
118,000
118,000
124,000
10.3
10.5
10.5
10.9
38ARD014
40RM012
40RM012H
40RM014
40RM014H
40RM016
40RM016H
135,000
143,000
145,000
153,000
152,000
161,000
38ARD016
40RM014
40RM014H
40RM016
40RM016H
40RM024
40RM024H
38ARD024
40RM024H
40RM028
40RM028H
CONDENSING UNIT ONLY
IPLV
Net Cap.
(Btuh)
EER
IPLV
11.7
12.4
12.8
13.2
123,000
12.3
16.0
9.7
10.2
10.5
11.1
10.8
11.3
9.9
10.3
10.9
11.5
11.0
11.5
158,000
12.5
15.1
176,000
185,000
187,000
198,000
194,000
204,000
10.0
10.3
10.2
10.6
10.1
10.4
10.4
10.8
10.5
10.9
10.2
10.4
204,000
11.9
13.9
243,000
242,000
252,000
9.6
9.6
9.7
9.8
9.9
9.9
259,000
11.2
13.1
OVERALL DIMENSIONS
MODEL
LENGTH
(in.)
WIDTH
(in.)
HEIGHT
(in.)
38ARD012
59.42
45.78
34.38
38ARD014
76.25
43.0
39.88
38ARD016
76.25
43.0
39.88
38ARD024
76.25
43.0
39.88
ELECTRICAL DATA
UNIT
38ARD
012
014
016
MIN
MAX
RLA
LRA
RLA
LRA
FAN MOTORS
(QTY 2)
FLA (ea)
kW
Fan No.
1
2
208/230-3-60
187
254
16
125
16
125
1.5
1.5
3.1
460-3-60
418
506
8
66.5
8
66.5
0.7
0.7
1.9
NONE OR DISCONNECT
CONVENIENCE OUTLET
575-3-60
523
632
6.4
50
6.4
50
0.7
0.7
1.9
NONE OR DISCONNECT
CONVENIENCE OUTLET
400-3-50
360
440
8
66.5
8
66.5
0.7
0.7
1.9
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230-3-60
187
253
20.7
156
20.7
156
4.3
3.7
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
460-3-60
342
418
10.0
75
10.0
75
2.3
1.9
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
575-3-60
518
660
8.2
54
8.2
54
1.8
1.8
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
380-3-60
414
528
10.7
70
10.7
70
4.3
3.7
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230-3-60
187
253
32.1
195
32.1
195
4.3
3.7
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
460-3-60
342
418
16.4
95
16.4
95
2.3
1.9
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
575-3-60
518
660
12.0
80
12.0
80
1.8
1.8
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
380-3-60
414
528
16.7
123
16.7
123
4.3
3.7
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230-3-60
187
253
37.8
239
37.8
239
4.3
3.7
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
460-3-60
342
418
19.2
125
19.2
125
2.3
1.9
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
575-3-60
518
660
13.8
80
13.8
80
1.8
1.8
1.41
NONE OR DISCONNECT
CONVENIENCE OUTLET
380-3-60
414
528
23.5
145
23.5
145
4.3
3.7
1.41
FACTORY
INSTALLED
OPTION
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NOMINAL
VOLTAGE
VOLTAGE
RANGE
COMPRESSOR COMPRESSOR
1
2
024
Rated in accordance
with ARI 210/240
or 360
112
• Commercial Product Guide • 2002 •
POWER SUPPLY
MCA
39.0
43.8
19.4
21.6
15.8
17.5
19.4
21.6
55.6
63.5
27.7
31.3
23.1
25.9
33.1
37.4
81.2
89.2
42.1
45.7
31.6
34.5
46.6
50.9
94.1
102.0
48.4
52.0
35.7
38.5
61.9
66.2
MOCP
55
55
25
25
20
20
25
25
70
80
35
40
30
30
40
45
100
100
50
60
40
40
60
60
125
150
60
70
45
50
70
80
ICF
186
194
90
94
67
70
90
94
236
244
117
120
97
99
149
153
286
294
149
153
98
101
178
182
38AQ,ARQ,AQS
Commercial Products
Outdoor Split-System Heat Pumps
6 to 15 Nominal Tons
Heat Pump
38AQS016
38AQ007
Factory-Installed Options
• Enviro-Shield™ Condenser Coil Protection
• Aluminum Fin or Copper Fin Coils
• Low ambient control (38ARQ,AQS)
• Disconnect switch (38ARQ,AQS)
• Convenience outlet (38ARQ,AQS)
Field-Installed Accessories
38ARQ008,012
Features
•
•
•
•
Leg Kit (016)
Outdoor Thermostat
Low Ambient Control
Coil Grille (ARQ & AQS)
• Scroll Compressor (AQ & ARQ)
• Semi-Hermetic Compressor (38AQS)
• Functional Run Test
• Single Refrigerant Circuit
• ARI Capacity Certified with Carrier’s 40RMQ
Packaged Air Handler
• Assured Quality (ISO 9002)
• Compact Design
• Easy Access to Compressor and Controls
• Service Valves
• Numerous Control Options:
- Programmable
- Communicating
- Electro Mechanical
• Commercial Product Guide • 2002 •
113
Performance & Sizing Information
MODEL
38AQ007
38ARQ008
38ARQ012
38AQS016
CAPACITY
TONS
TYPICAL REFRIG.
OPS CHARGE
(lbs)
6
7 1/2
10
15
CONNECT (SWEAT) in. OD
TOTAL OP WEIGHT
(lbs)
Suction
Liquid
AL Coil
CU Coil
1 1/8
1 1/8
1 3/8
1 3/8
5/8
1/2
5/8
5/8
345
540
750
803
600
890
943
20
20
30
37
ELECTRICAL DATA - OUTDOOR UNIT
VOLTAGE RANGE
UNIT
V-PH-Hz
38AQ007
208/230-3-60
460-3-60
208/230-3-60
460-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
38ARQ008
38ARQ012
38AQS016
POWER SUPPLY
Min
Max
Min CKT (Amps)
MOCP (Amps)
187
414
187
414
187
414
518
187
414
518
354
508
354
508
253
528
660
253
528
660
28.7
14.5
39.0
19.8
50.3
22.9
17.8
87.5
40.7
33.0
45
20
60
30
60
30
25
125
60
50
OVERALL DIMENSIONS
MODEL
LENGTH
HEIGHT
WIDTH
38AQ007
2'-9"
3'-2 1/2"
2'-11"
38ARQ008
4'-11 1/2"
2'-10 3/8"
3'-9 7/8"
38ARQ012
4'-11 1/2"
2'-10 3/8"
3'-9 7/8"
38AQS016
6'-4 1/2"
3'-3 7/8"
3'-7"
Rated in accordance
with ARI Standard
210/240, 270, 340/360
(60 Hz Only)
114
• Commercial Product Guide • 2002 •
40RM,RMQ
Commercial Products
Packaged DX and Heat Pump
Air Handlers
1,800 to 15,000 CFM
Features
Factory-Installed Option
• All models capable of at least 2" of ESP
• Sloped Condensate Drain Pans
• Cleanable Insulation With Anti-Microbial Coating
• ARI Rated With Carrier’s 38 Series Condensing Units
• High Efficiency, Precision Balanced Fan Systems Provide
Reliable, Quiet Operation
• Units Install Horizontally or Vertically with no Modifications
• Factory Installed TXV Assemblies
• Pre-Wired Fan Motor and Contactor
• Filters, Motor, Drives, electrical and TXV’s are Accessible by
Removing a Single Panel
• Piping/Drain Connections may be made on
either side of unit
• High Capacity Coil (40RM only)
Field-Installed Accessories
• Electric Heaters With Single Point Connection
• Mixing Box With Enthalpy Controls (Economizer) and
CO2 Sensor
• Plenum Assembly For “Free Standing” Applications
• Hot Water or Steam Coils
• UV-C Germicidal Lamps
• PremierLink™ communicating controls
• Commercial Product Guide • 2002 •
115
Performance & Sizing Information
B
A
C
MODEL
Heat Pump
40RMQ008
40RMQ012
40RMQ016
40RMQ024
40RMQ028
Cooling Only
40RM007
40RM008
40RM012
40RM014
40RM016
40RM024
40RM028
40RM034
NOMINAL
CAPACITY
NOMINAL
AIRFLOW
MACHINE
WEIGHT
tons
cfm
lbs
7.5
10
15
20
25
3000
4000
6000
8000
10000
6
7.5
10
12.5
15
20
25
30
2400
3000
4000
5000
5000
8000
10000
12000
DIMENSIONS
A
B
in.
C
385
427
713
720
1050
49
49
89
89
99
57
57
57
57
67
28
28
28
28
33
381
385
405
670
685
690
1020
1030
49
49
49
89
89
89
99
99
57
57
57
57
57
57
67
67
28
28
28
28
28
28
33
33
Rated in accordance with
ARI Standard 360, when
matched with appropriate
38 Series Condensing Units
(60 Hz Only)
116
• Commercial Product Guide • 2002 •
Commercial Products
40RMS
Packaged Chilled-Water Air Handlers
2,250 to 15,000 CFM
Features
Field-Installed Accessories
• All models capable of at least 2" of ESP
• Sloped condensate drain pan
• Face split coils on size 014 and larger
• Cleanable insulation with anti-microbial coating
• High efficiency coils, with internally enhanced tubes
• 2" filters and filter tracks
• High efficiency, precision balanced fan systems provide
reliable, quiet operation
• Units install horizontally or vertically with no modifications
• Pre-wired fan motor and contactor
• Filters, motors, drives and electrical connections accessible
by removing a single panel
• Piping/drain connections may be made on
either side of unit
• Electric heaters with single point connections
• Mixing box with enthalpy controls (Economizer)
and CO2 sensor
• Plenum Assembly for “Free Standing” Applications
• Hot water or steam coils
• UV-C Germicidal Lamps
• PremierLink™ communicating controls
• Commercial Product Guide • 2002 •
117
Performance & Sizing Information
B
A
C
MODEL
NOMINAL
CAPACITY*
(tons)
NOMINAL
AIRFLOW
(cfm)
COIL FACE
AREA
(sq ft)
MACHINE
WEIGHT
(lbs)
A
B
C
40RMS008
7.5
3000
8.3
390
49
57
28
40RMS010
8.5
3400
9.0
391
49
57
28
28
DIMENSIONS (in.)
40RMS012
10
4000
9.8
391
49
57
40RMS014
12.5
5000
13.8
661
89
57
28
40RMS016
15
6000
16.6
677
89
57
28
40RMS024
20
8000
19.3
683
89
57
28
40RMS028
25
10000
24.8
1035
99
67
33
40RMS034
30
12000
27.9
1042
99
67
33
*45° F EWT, 10° F Fluid Temp Rise
118
• Commercial Product Guide • 2002 •
DUCT-FREE SYSTEM
Commercial Products
Heat Pump and Cooling Only
COOLING
38HDC,QR
40QNB,QNE,QNH
• 1 1/2-5 Tons
• 200 ft Line Lengths
• Robust commercial grade CDU designed to
be reliable, quiet and extremely efficient
• Horizontal discharge
(High Wall) 3/4-2 ton
• Sleek new design uses IR wireless controller
• Whisper Quiet
• Features include 24-hour timer, dry mode
and auto-swing louvers
• Electric heat available
38AN,BK
40QKB,QKE
* Grille sold
separately
(Cassette) 1 1/2-3 Ton
• 24 V Electro-Mechanical Control
• Ideal for retrofit and modernization projects
with hung ceilings
• Fresh Air Intake
• Easily installed or moved and includes fresh air intake
• Electric heat available with or without Heat Pump
• AN 009 & 012 (3/4 & 1 Ton)
• BK 009-024 (3/4-2 Tons)
• All new Robust Design to perform
in the most severe conditions imaginable
• Combines reduced weight and size and enhanced
performance with state-of-the-art styling
• Horizontal discharge
38HDL
• Light Commercial application
(1 1/2-5 Tons)
• 100 ft Line Lengths
• Rugged, Quiet and Efficient
• Competitively priced
• Cooling only
• Horizontal discharge
40QAB,QAE
38HDS
(Under Ceiling) 1 1/2-5 Ton
• 24 V Electro-Mechanical Control
• Ideal where wall space and above ceiling space is limited
• Features 30% fresh air intake and auto pulse louvers
• Electric heat available with or without Heat Pump
• 2 Tons
• Serves 2 zones allowing for
numerous fan coil combinations
• Cooling only
• Horizontal discharge
• Commercial Product Guide • 2002 •
COOLING
119
40CG,CS
• Console/Under Ceiling 1 1/2 to 2 1/2 ton
• Sleek new design uses IR remote control
• Optional 2-way operation
• Auto swing louvers
• Intelligent microprocessor
• Electric heat available
38CG,CS
• Console/Under Ceiling Condensed 1 1/2 to 2 1/2 tons
• Compact cabinet design
• Galvanized steel casing
• Simple installation
• Horizontal discharge
40HD
• Satellite 2 to 4 tons
• Specifically designed for retrofit & make over projects
• 24-V controls
• High and low voltage terminal blocks
• Built in condensate pump
• Numerous accessories available
120
38SC,SB
• Console Multizone 5 tons
• Specifically designed for console/under ceiling
• Cooling only and Heat pump
• Simple installation
• Horizontal discharge
• Commercial Product Guide • 2002 •
Commercial Products
Cooling Only System Specifications
40QNB High Wall with 38AN/HDC/HDL Condenser, Duct Free Split Systems, 0.75 to 2 Tons
NOMINAL
CAPACITY
TONS
0.75
1.0
SOUND RATING (dBa)
INDOOR
UNIT
OUTDOOR
UNIT
ARI
CAPACITY
Btuh
ARI
CFM
SEER
EER
INDOOR
POWER
40QNB009-1
40QNB012-1
40QNB012-3
38AN-009-1
38AN-012-1
38AN-012-3
38HDC018-3
38HDL018-3
38HDL018-3
38HDC024-3
38HDL024-3
8,500
11,000
11,600
17,300
16,200
17,600
22,600
22,600
215
300
302
480
480
550
550
550
10.5
10.5
11.0
11.3
11.0
11.7
12.0
11.3
9.7
9.3
10.1
10.4
9.7
10.4
10.8
11.3
50.4
54.0
54.0
57.6
57.6
42.1
45.7
45.7
49.3
49.3
62.5
54.2
1.5
40QNB018-3
2.0
40QNB024-3
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
62.3
63.1
63.1
66.1
59.5
59.5
65.5
63.2
54.0
54.8
54.8
57.8
51.2
51.2
57.2
54.9
TOTAL
kW
0.9
1.2
1.2
1.7
1.7
1.7
2.1
2.0
40QAB Under Ceiling with 38HDC/HDL Condenser, Duct Free Split Systems, 1.5 to 5 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
1.5
40QAB024-331
2.0
40QAB024-331
2.5
40QAB036-321
3.0
40QAB036-321
4.0
40QAB048-321
5.0
40QAB060-311
SOUND RATING (dBa)
OUTDOOR
UNIT
ARI
CAPACITY
Btuh
ARI
CFM
SEER
EER
38HDC018-3
38HDL018-3
38HDC024-3
38HDL024-3
38HDC030-3
38HDL030-3
38HDC036-3,5,6
38HDL036-3
38HDC048-3,5,6
38HDL048-3
38HDC060-3,5,6
38HDL060-3
18,000
18,000
22,800
23,000
30,000
29,000
34,000
34,000
47,000
45,500
58,000
58,500
500
500
600
600
840
840
840
840
1,200
1,200
1,600
1,600
12.0
11.6
12.0
11.0
12.0
10.3
12.0
10.1
12.0
10.8
12.0
10.8
11.0
10.5
11.0
11.2
11.0
9.7
10.5
9.6
10.8
9.9
11.2
9.5
INDOOR
POWER
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
57.2
48.9
58.4
50.1
68.4
60.1
68.4
60.1
67.3
59
70.1
61.8
66.1
59.5
65.5
63.2
63.0
59.5
64.5
64.7
70.1
65.4
69.4
65.8
57.8
51.2
57.2
54.9
54.7
51.2
56.2
56.4
61.8
57.1
61.1
57.5
TOTAL
kW
1.6
1.7
2.1
2.1
2.7
3.0
3.3
3.5
4.4
4.6
5.2
6.2
40QKB Cassette with 38HDC/HDL Condenser, Duct Free Split Systems, 1.5 to 3 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
1.5
40QKB024-3
2.0
2.5
3.0
40QKB036-3
SOUND RATING (dBa)
OUTDOOR
UNIT
ARI
CAPACITY
Btuh
ARI
CFM
SEER
38HDC018-3
38HDL018-3
38HDC024-3
38HDL024-3
38HDC030-3
38HDL030-3
38HDC036-3,5,6
38HDL036-3
18,300
17,800
24,000
24,000
30,000
29,000
33,000
34,400
525
525
915
915
915
915
915
915
11.0
11.4
11.0
11.8
10.8
11.1
10.8
10.5
EER
INDOOR
POWER
10.4
56.3
48.0
54.8
46.5
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
10.9
9.6
10.5
66.1
59.5
65.5
63.2
63.0
59.5
64.5
64.7
57.8
51.2
57.2
54.9
54.7
51.2
56.2
56.4
TOTAL
kW
1.8
1.7
2.2
2.1
3.1
2.9
3.1
3.5
40CG Console with 38CG Condenser, Duct Free Split Systems, 1.5 to 2.5 Tons
SOUND RATING (dBa)
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
OUTDOOR
UNIT
ARI
CAPACITY
Btuh
ARI
CFM
SEER
EER
INDOOR
POWER
1.5
2.0
2.5
40CG-018---3
40CG-024---3
40CG-030---3
38CG-018---3
38CG-024---3
38CG-030---3
18,000
23,400
30,000
650
800
800
10
10
10
9.0
9.1
9.0
55.0
56.0
55.0
SEER
EER
INDOOR
POWER
11.0
11.0
11.0
10.0
11.0
10.5
10.2
9.8
10.5
10.0
10.4
10.0
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
38.0
40.0
40.0
79.0
74.0
78.0
49.0
49.0
49.0
TOTAL
kW
1.9
2.4
3.4
40HD Satellite with 38HDC/HDL Condenser, Duct Free Split Systems, 2 to 4 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
2
40HD024-3
3
40HD036-3
4
40HD048-3
OUTDOOR
UNIT
ARI
CAPACITY
Btuh
38HDC024-3
38HDL024-3
38HDC036-3,5,6
38HDL036-3
38HDC048-3,5,6
38HDL048-3
24,000
24,000
34,400
35,000
47,000
46,400
ARI
CFM
800
1,226
1,610
SOUND RATING (dBa)
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
n/a
n/a
68.6
n/a
n/a
n/a
65.5
63.2
64.5
64.7
70.1
65.4
57.2
54.9
56.2
56.4
61.8
57.1
TOTAL
kW
n/a
LEGEND
CFM - Cubic Feet Per Minute
SEER - Seasonal Energy Efficiency Rating
n/a - Not available at this time
• Commercial Product Guide • 2002 •
121
Heat Pump System Specifications
40QNE/H High Wall with 38BK Condenser, Duct Free Split Systems, 0.75 to 2 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
OUTDOOR
UNIT
0.8
1.0
1.5
2.0
40QNE009-1
40QNH012-3
40QNH018-3
40QNH024-3
38BK-009-1
38BK-012-3
38BK-018-3
38BK-024-3
ARI CAPACITIES
C/O
Btuh
H/P
Btuh
8,700
11,100
17,300
23,000
9,000
11,700
16,400
21,000
ARI
CFM
SOUND RATING (dBa)
SEER EER HSPF INDOOR INDOOR
OUTDOOR OUTDOOR
POWER PRESSURE
POWER PRESSURE
252
300
485
520
10.0
10.0
11.0
11.0
9.2
9.5
10.1
10.4
6.8
6.8
6.8
6.8
50.6
54.0
58.6
61.7
42.3
45.7
50.3
53.4
63.4
62.8
67.2
63.3
55.1
54.5
58.9
55.0
TOTAL
kW
1.0
1.2
1.7
2.2
40QAE Under Ceiling with 38QR Condenser, Duct Free Split Systems, 1.5 to 5 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
2.0
40QAE024-331
3.0
40QAE036-321
4.0
5.0
40QAE048-321
40QAE060-311
OUTDOOR
UNIT
38QR-018C-3
38QR-024C-3
38QR-030C-3
38QR-036C-3
38QR-036C-5,6
38QR-048C-3,5,6
38QR-060C-3,5,6
ARI CAPACITIES
C/O
Btuh
H/P
Btuh
19,000
24,000
30,000
34,600
36,000
48,000
58,000
17,000
22,600
28,000
33,000
34,400
45,500
57,500
ARI
CFM
SOUND RATING (dBa)
SEER EER HSPF INDOOR INDOOR
OUTDOOR OUTDOOR
POWER PRESSURE
POWER PRESSURE
500
525
870
870
870
1,100
1,600
11.0
11.0
11.0
11.5
11.0
10.2
11.0
10.0
10.0
10.2
10.2
9.8
9.6
9.9
7.2
7.3
7.4
7.2
6.8
7.3
7.4
57.2
48.9
68.4
60.1
67.3
70.1
59.0
61.8
67.2
66.3
65.9
66.2
71.5
73.0
73.6
58.9
58.0
57.6
57.9
63.2
64.7
65.3
TOTAL
kW
1.9
2.4
2.9
3.4
3.7
5.0
5.9
40QKE Cassette with 38QR Condenser, Duct Free Split Systems, 1.5 to 3 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
OUTDOOR
UNIT
1.5
40QKE024-3
2.0
40QKE036-3
3.0
40QKE048-3
38QR-018C-3
38QR-024C-3
38QR-030C-3
38QR-036C-3
38QR-036C-5,6
ARI CAPACITIES
C/O
Btuh
H/P
Btuh
18,000
25,000
29,000
33,000
34,400
17,600
23,800
27,000
33,000
34,000
ARI
CFM
SOUND RATING (dBa)
SEER EER HSPF INDOOR INDOOR
OUTDOOR OUTDOOR
POWER PRESSURE
POWER PRESSURE
525
980
980
1,100
1,100
10.0
10.7
11.5
10.5
10.0
9.0
10.2
11.1
9.5
9.2
6.8
7.6
7.6
6.8
6.8
56.3
48.0
54.8
46.5
59.1
50.8
67.2
66.3
65.9
66.2
71.5
58.9
58.0
57.6
57.9
63.2
TOTAL
kW
2.0
2.4
2.6
3.5
3.7
40CS Console with 38CS Condenser, Duct Free Split Systems, 1.5 to 2.5 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
OUTDOOR
UNIT
1.5
2
2.5
40CS-018---3
40CS-024---3
40CS-030---3
38CS-018---3
38CS-024---3
38CS-030---3
ARI CAPACITIES
C/O
Btuh
H/P
Btuh
18,000
23,400
30,000
18,000
24,000
31,000
ARI
CFM
650
800
800
SOUND RATING (dBa)
SEER EER HSPF INDOOR INDOOR
OUTDOOR OUTDOOR
POWER PRESSURE
POWER PRESSURE
10
10
10
9.0
9.1
9.0
6.8
6.9
6.8
55.0
56.0
55.0
LEGEND
CFM - Cubic Feet Per Minute
HSPF - Heating Seasonal Performance Factor
SEER - Seasonal Energy Efficiency Rating
C/O - Cooling Only
H/P - Heat Pump
122
• Commercial Product Guide • 2002 •
38.0
40.0
40.0
79.0
74.0
78.0
49.0
49.0
49.0
TOTAL
kW
1.9
2.4
3.4
Commercial Products
Multi-Zone System Specifications
40QNB/QAB/QKB High Wall, Under Ceiling & Cassette Cooling Only, with 38HDS Condenser, Duct Free Split Systems, 2 Tons
NOMINAL
CAPACITY
TONS
2.0
INDOOR
UNIT
(Any two)
OUTDOOR
UNIT
40QNB018-3
40QAB023-3 38HDS024-3
40QKB024-3
ARI CAPACITIES
C/O
Btuh
H/P
Btuh
23,000
24,000
23,000
n/a
SOUND RATING (dBa)
ARI
CFM
SEER
EER
HSPF
960
1,000
1,060
12.0
11.3
10.8
10.5
n/a
INDOOR
POWER
INDOOR
OUTDOOR OUTDOOR
PRESSURE
POWER PRESSURE
57.6
57.2
56.3
49.3
48.9
48.0
68.0
57.9
TOTAL
kW
2.0
2.2
2.2
40CG Console with 38SC Condenser, Duct Free Split Multi Zone System, 2.5 Tons
SOUND RATING (dBa)
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
Two Sections
OUTDOOR
ARI
UNIT
CAPACITY
One Section
Btuh
ARI
CFM
SEER
EER
5.0
40CG-030---3
38SC-030---3
800
10
9.0
30,000
INDOOR
POWER
55
INDOOR
PRESSURE
OUTDOOR
POWER
OUTDOOR
PRESSURE
40
80
51
TOTAL
kW
3.4 x 2
40CS Console with 38SB Condenser, Duct Free Split Multi Zone System, 2.5 Tons
NOMINAL
CAPACITY
TONS
INDOOR
UNIT
Two Sections
OUTDOOR
UNIT
One Section
5.0
40CS-030---3
38SB-030---3
ARI CAPACITIES
C/O
Btuh
30,000
H/P
Btuh
31,000
ARI
CFM
800
SOUND RATING (dBa)
SEER EER
10
9.0
HSPF
6.8
INDOOR
POWER
55.0
• Commercial Product Guide • 2002 •
INDOOR
PRESSURE
40.0
OUTDOOR
POWER
80.0
OUTDOOR
PRESSURE
49.0
TOTAL
kW
3.4 x 2
123
124
• Commercial Product Guide • 2002 •
42WKN
Commercial Products
Hydronic Cassette Fan Coils
42WKN004-010
7,000 to 32,000 Btuh Cooling
12,000 to 52,000 Btuh Heating
42WKN016,020
NOTE: Grille sold separately
Features
Field-Installed Accessories
• Modular to Match Standard Suspended
Ceiling Tiles 2x2/2x4
• High Efficiency One, Two or Three Row Heat Exchanger
• New Improved High Efficiency Fan (Lower Sound Levels)
• Three Speed Motor
• Low Sound Level (High Noise Insulation)
• Independent Louvers (2-3-4 Flow Directions Distributions)
• Fresh/Outside Air Intake
• Integrated Condensate Pump
• Built-in Overflow Safety Devices
• Branch Ducting Capability
• Ceiling Located
• Promotes Ideal Air Circulation
• All Floor Space Remains “Free”
• Two Position Motorized Valve Accessory package
- 3-Way Diverting Type
- Pre-Assembled piping with Fittings for Fast and
Easy Installation
• Choice of 3 Solid-State 24 V Electronic Wall Mounted
Thermostat
- Slim Line
- Flat Stat
- 5-1-1 Programmable
• Power Ventilation and Outside Air Adapter Kit for
Introducing Fresh Air
Factory-Installed Options
• Optional Heating Coil on 4-Pipe Systems - 010
and 020 Size Units
• Commercial Product Guide • 2002 •
125
Performance & Sizing Information
Hydronic Units
UNIT SIZE
Cooling Capacity:
Total
Sensible
Air Flow: Cooling
Heating Capacity
Air Flow: Heating
Water Flow
Pressure Drop
Motor Power
42WKN004T
004
TWO TUBE
SINGLE
42WKN008T
008
TWO TUBE
SINGLE
42WKN010T
010
TWO TUBE
SINGLE
42WKN010F
010
FOUR TUBE
SINGLE
42WKN016T
016
TWO TUBE
DOUBLE
42WKN020T
020
TWO TUBE
DOUBLE
42WKN020F
020
FOUR TUBE
DOUBLE
6,900
6,100
420
13,700
420
1.4
1.3
55
13,300
10,200
420
23,000
420
2.7
3.1
60
13,700
9,600
400
20,700
355
2.9
5.9
80
13,300
9,800
445
11,600
425
2.9
4.3
80
27,000
20,700
845
46,900
845
2.7
3.2
140
31,600
22,600
930
51,500
910
3.4
5.4
180
28,800
21,600
990
25,300
940
3.2
4.1
180
Btuh
Btuh
CFM
Btuh
CFM
GPM
Ft-Wg
Watts
ARI 440 Rated Conditions
Conditions: cooling 80/67 EWT 45°F
Conditions: heating 70/- EWT 140°F
* Grille sold separately
126
• Commercial Product Guide • 2002 •
52C
Commercial Products
Comfort Series
Packaged Terminal Air Conditioner (PTAC)
Your smart selection for reliable performance.
An economical choice for new construction, or as
replacement units in hospitality and healthcare
facilities, the 52C Comfort Series features durable
design and reliable operation.
Features
• Reliable performance
• Easy-access lifetime filters
• User-friendly controls
• Improved condensate removal system
• Low sound levels
• Enhanced temperature control
• Enhanced humidity control
• Exceeds ARI minimum efficiency standards
• Energy Saver Switch
• Durable polymer front cabinet, resists scratches, dents and
fading
• Simple maintenance and service, with easily accessible
electrical components and slide-out chassis
• Can easily retrofit in to most industry standard 42" x 16"
wall sleeves
Factory-Installed Options
• Wall thermostat control
• Corrosion protection
Field-Installed Accessories
• Wall sleeves
• Wall sleeve extension
• Outdoor grilles
• Non-electrical and pre-wired electrical subbase
• Subbase accessories
• Wall thermostats
• Wall thermostat interface retrofit kit
• Locking thermostat cover
• Universal condensate drain kit
• Lateral duct system
• Curtain deflector
• Lateral air deflector
• Locking security door
• Front desk control
• Hard-wire electrical kit
• Commercial Product Guide • 2002 •
127
Performance & Sizing Information
HEAT/COOL UNITS
COOLING
(Btuh)
MODEL
NUMBER
52CE-207---3
52CE-307---3
52CE-209---3
52CE-309---3
52CE-212---3
52CE-312---3
52CE-512---3
52CE-215---3
52CE-315---3
52CE-515---3
52CE-207---4
52CE-307---4
52CE-209---4
52CE-309---4
52CE-212---4
52CE-312---4
52CE-512---4
52CE-215---4
52CE-315---4
52CE-515---4
ELECTRIC
HEAT
(Btuh)
COP
7800/6400
11600/9700
7800/6400
11600/9700
7800/6400
11600/9700
17000/13600
7800/6400
11600/9700
17000/13600
7800
11600
7800
11600
7800
11600
17000
7800
11600
17000
-
EER
7000/6900 11.1/11.1
7000/6900 11.1/11.1
9000/8900 10.7/10.7
9000/8900 10.7/10.7
12000/11900 10.1/10.1
12000/11900 10.1/10.1
12000/11900 10.1/10.1
14500/14000 9.4/9.5
14500/14000 9.4/9.5
14500/14000 9.4/9.5
7000
11.1
7000
11.1
8900
10.7
8900
10.7
12000
10.1
12000
10.1
12000
10.1
14500
9.4
14500
9.4
14500
9.4
REVERSE
EVAP FAN
CYCLE HEAT
CFM
(HI-SPEED)
(Btuh)
-
260/250
260/250
260/250
260/250
350/320
350/320
350/320
290/270
290/270
290/270
260
260
260
260
340
340
340
290
290
290
APPROX.
WEIGHT
(SHIP)
125
125
125
125
140
140
140
150
150
150
125
125
125
125
140
140
140
150
150
150
CURRENT (AMPS) INPUT POWER (WATTS BRANCH
1-PH 60Hz
CIRCUIT
ELECTRIC
ELECTRIC
FUSE
VOLTS
COOLING
COOLING
HEAT
HEAT
(AMPS)
230/208
2.7/2.9
10.4/9.5
631/622
2393/1985
15
230/208
2.7/2.9
15.2/14.1
631/622
3493/2935
20
230/208
3.7/3.8
10.4/9.5
841/832
2393/1985
15
230/208
3.7/3.8
15.2/14.1
841/832
3493/2935
20
230/208
5.2/5.6
10.8/9.9 1188/1178 2470/2047
15
230/208
5.2/5.6
15.6/14.5 1188/1178 3570/2997
20
230/208
5.2/5.6
22.5/20.0 1188/1178 5170/4147
30
230/208
6.8/7.6
10.9/10.0 1543/1473 2517/2117
15
230/208
6.8/7.6
15.7/14.6 1543/1473 3617/3067
20
230/208
6.8/7.6 22.6/20.01 1543/1473 5217/4217
30
265
2.4
9.2
631
2396
15
265
2.4
13.3
631
3496
20
265
3.1
9.2
832
2396
15
265
3.1
13.3
832
3496
20
265
4.6
9.4
1188
2470
15
265
4.6
13.5
1188
3570
20
265
4.6
19.6
1188
5170
25
265
6.0
9.7
1543
2517
15
265
6.0
13.8
1543
3617
20
265
6.0
19.9
1543
5217
25
HEAT PUMP
MODEL
NUMBER
52CQ-207---3
52CQ-307---3
52CQ-209---3
52CQ-309---3
52CQ-212---3
52CQ-312---3
52CQ-512---3
52CQ-215---3
52CQ-315---3
52CQ-515---3
52CQ-207---4
52CQ-307---4
52CQ-209---4
52CQ-309---4
52CQ-212---4
52CQ-312---4
52CQ-512---4
52CQ-215---4
52CQ-315---4
52CQ-515---4
128
COOLING
(Btuh)
EER
7000/6900 11.1/11.1
7000/6900 11.1/11.1
9000/8900 10.7/10.7
9000/8900 10.7/10.7
12000/11900 10.1/10.1
12000/11900 10.1/10.1
12000/11900 10.1/10.1
14500/14000 9.4/9.5
14500/14000 9.4/9.5
14500/14000 9.4/9.5
7000
11.1
7000
11.1
8900
10.7
8900
10.7
12000
10.1
12000
10.1
12000
10.1
14500
9.4
14500
9.4
14500
9.4
ELECTRIC
HEAT
(Btuh)
COP
7800/6400
11600/9700
7800/6400
11600/9700
7800/6400
11600/9700
17000/13600
7800/6400
11600/9700
17000/13600
7800
11600
7800
11600
7800
11600
17000
7800
11600
17000
3.1/3.1
3.1/3.1
3.1/3.1
3.1/3.1
3.0/3.0
3.0/3.0
3.0/3.0
2.9/2.9
2.9/2.9
2.9/2.9
3.1
3.1
3.1
3.1
3.0
3.0
3.0
2.9
2.9
2.9
REVERSE
EVAP FAN
CYCLE HEAT
CFM
(HI-SPEED)
(Btuh)
6100/6000
6100/6000
7900/7800
7900/7800
10800/10700
10800/10700
10800/10700
13400/13200
13400/13200
13400/13200
6100
6100
7700
7700
10800
10800
10800
13400
13400
13400
260/250
260/250
260/250
260/250
350/320
350/320
350/320
290/270
290/270
290/270
260
260
260
260
340
340
340
290
290
290
APPROX.
WEIGHT
(SHIP)
125
125
125
125
140
140
140
150
150
150
125
125
125
125
140
140
140
150
150
150
CURRENT (AMPS) INPUT POWER (WATTS BRANCH
1-PH 60Hz
CIRCUIT
ELECTRIC
ELECTRIC
FUSE
VOLTS
COOLING
COOLING
HEAT
HEAT
(AMPS)
230/208
2.7/2.9
10.4/9.5
631/622
2393/1985
15
230/208
2.7/2.9
15.2/14.1
631/622
3493/2935
20
230/208
3.7/3.8
10.4/9.5
841/832
2393/1985
15
230/208
3.7/3.8
15.2/14.1
841/832
3493/2935
20
230/208
4.7/5.2
10.8/9.9 1188/1178 2470/2047
15
230/208
4.7/5.2
15.6/14.5 1188/1178 3570/2997
20
230/208
4.7/5.2
22.5/20.0 1188/1178 5170/4147
30
230/208
6.8/7.6
10.9/10.0 1543/1473 2517/2117
15
230/208
6.8/7.6
15.7/14.6 1543/1473 3617/3067
20
230/208
6.8/7.6
22.6/20.1 1543/1473 5217/4217
30
265
2.4
9.2
631
2396
15
265
2.4
13.3
631
3496
20
265
3.1
9.2
832
2396
15
265
3.1
13.3
832
3496
20
265
4.5
9.4
1188
2470
15
265
4.5
13.5
1188
3570
20
265
4.5
19.6
1188
5170
25
265
6.0
9.7
1543
2517
15
265
6.0
13.8
1543
3617
20
265
6.0
19.9
1543
5217
25
• Commercial Product Guide • 2002 •
52F
Commercial Products
Solid Side
Through-The-Wall Configuration
Carrier's new 52F Series Solid-Side Air Conditioners
deliver efficient heating and cooling in an attractive
through-the-wall configuration.
Features
Field-Installed Accessories
• Retrofit kit to allow easy use with all competitive wall sleeves
• Adjustable fan speed
• Four-way air flow
• Easy-out filter
• Attractive appearance
• Molding kit included standard with all units, to trim unit to
wall
• Window kit
• Wall sleeve (stamped grille included)
• Trim kit
• Architectural outdoor grille
• Commercial Product Guide • 2002 •
129
Performance & Sizing Information
HEAT/COOL
COOL ONLY
CATALOG NUMBER
52FE108-1
52FE310-3
52FE312-3
52FC009-3
52FC010-1
52FC012-3
COOLING CAPACITY, Btu/Hr
8,000
10,000/9,800
12,000/11,700
8,500/8,300
10,000
12,000/11,700
HEATING CAPACITY, Btu/Hr
4,200
10,600/8,600
10,600/8,600
N/A
N/A
N/A
VOLTAGE
115
230/208
230/208
230/208
115
230/208
EER
9.0
9.0
8.5
9.0
8.7
8.5
WATTS (COOL)
890
1100/1090
1415/1380
945/925
1150
1415/1380
WATTS (HEAT)
1250
3450/2800
3450/2800
N/A
N/A
N/A
AMPERES (COOL)
8.5
5.5/6.0
6.4/7.7
4.5/4.7
10.5
6.4/6.7
AMPERES (HEAT)
12
15.5/14.0
15.5/14.0
N/A
N/A
N/A
RECEPTACLE TYPE
1
4
4
3
1
3
FUSE SIZE (AMPS)
12
20
20
15
15
15
2/2/1
2/2/1
2/2/1
3/3
3/3
3/3
FAN SPEEDS
(COOL/FAN ONLY/HEAT)
MAXIMUM WALL THICKNESS
18”
18”
18”
18”
18”
18”
CFM, (HI)
250
255
255
245
250
265
A
14-1/2”
14-1/2”
14-1/2”
14-1/2”
14-1/2”
14-1/2”
B
24”
24”
24”
24”
24”
24”
C
20”
20”
20”
20”
20”
20”
UNIT
DIMENSIONS
A
D
C
B
WALL
SLEEVE
A
C
B
WEIGHT (NET/SHIP)
D
18-1/2”
18-1/2”
18-1/2”
18-1/2”
18-1/2”
18-1/2”
A
15-9/16”
15-9/16”
15-9/16”
15-9/16”
15-9/16”
15-9/16”
B
25-7/8”
25-7/8”
25-7/8”
25-7/8”
25-7/8”
25-7/8”
C*
18”
18”
18”
18”
18”
18”
90/110 LBS.
100/120 LBS.
102/122 LBS
93/113 LBS.
98/118 LBS.
102/122 LBS.
*Nominal
130
• Commercial Product Guide • 2002 •
52P
Commercial Products
Premier Series
Packaged Terminal Air Conditioner (PTAC)
HIGHNCY
CIE
EFFI
For your next upgrade, remodel or new construction, step
up to Carrier's Premier Series. Carrier's quietest, most
energy-efficient Packaged Terminal Air Conditioner ever.
Features
Field-Installed Accessories
•
•
•
•
•
•
•
• Wall sleeves
• Wall sleeve extension
• Outdoor grilles
• Non-electrical and pre-wired electrical subbase
• Subbase accessories
• Wall thermostats
• Wall thermostat interface retrofit kit
• Locking thermostat cover
• Universal condensate drain kit
• Lateral duct system
• Curtain Deflector
• Lateral air deflector
• Locking security door
• Front desk control
• Hard-wire electrical kit
Ultimate in temperature/humidity-controlled comfort
Modern, high-tech sculpted appearance
New two-stage condensate removal system
Lifetime filter for effective air filtration and easy cleaning
User-friendly controls
Energy Saver Switch
Durable polymer front cabinet, resists scratches, dents and
fading
• Simple maintenance and service, with easily accessible
electrical components and slide-out chassis
Factory-Installed Options
• Wall thermostat control
• Corrosion protection
• Commercial Product Guide • 2002 •
131
Performance & Sizing Information
HEAT/COOL UNITS
MODEL
NUMBER
52PE-207---3
52PE-307---3
52PE-209---3
52PE-309---3
52PE-212---3
52PE-312---3
52PE-512---3
52PE-215---3
52PE-315---3
52PE-515---3
52PE-207---4
52PE-307---4
52PE-209---4
52PE-309---4
52PE-212---4
52PE-312---4
52PE-512---4
52PE-215---4
52PE-315---4
52PE-515---4
COOLING
(Btuh)
EER
7200/7100 12.7/12.7
7200/7100 12.7/12.7
9100/9000 11.5/11.5
9100/9000 11.5/11.5
12100/12000 11.1/10.7
12100/12000 11.1/10.7
12100/12000 11.1/10.7
14500/14000 9.4/9.5
14500/14000 9.4/9.5
14500/14000 9.4/9.5
7200
12.7
7200
12.7
9100
11.5
9100
11.5
12100
11.1
12100
11.1
12100
11.1
14500
9.4
14500
9.4
14500
9.4
ELECTRIC
HEAT
(Btuh)
COP
7800/6400
11600/9700
7800/6400
11600/9700
7800/6400
11600/9700
17000/13600
7800/6400
11600/9700
17000/13600
7800
11600
7800
11600
7800
11600
17000
7800
11600
17000
-
ELECTRIC
HEAT
(Btuh)
COP
7800/6400
11600/9700
7800/6400
11600/9700
7800/6400
11600/9700
17000/13600
7800/6400
11600/9700
17000/13600
7800
11600
7800
11600
7800
11600
17000
7800
11600
17000
3.4/3.4
3.4/3.4
3.2/3.2
3.2/3.2
3.2/3.2
3.2/3.2
3.2/3.2
2.9/2.9
2.9/2.9
2.9/2.9
3.4
3.4
3.2
3.2
3.2
3.2
3.2
2.9
2.9
2.9
REVERSE
EVAP FAN
CYCLE HEAT
CFM
(HI-SPEED)
(Btuh)
-
260/250
260/250
260/250
260/250
350/320
350/320
350/320
290/270
290/270
290/270
260
260
260
260
340
340
340
290
290
290
APPROX.
WEIGHT
(SHIP)
125
125
125
125
140
140
140
150
150
150
125
125
125
125
140
140
140
150
150
150
CURRENT (AMPS) INPUT POWER (WATTS BRANCH
1-PH 60Hz
CIRCUIT
ELECTRIC
ELECTRIC
FUSE
VOLTS
COOLING
COOLING
HEAT
HEAT
(AMPS)
230/208
2.7/2.9
10.4/9.5
567/559
2393/1985
15
230/208
2.7/2.9
15.2/14.1
567/559
3493/2935
20
230/208
3.7/3.8
10.4/9.5
791/783
2393/1985
15
230/208
3.7/3.8
15.2/14.1
791/783
3493/2935
20
230/208
4.8/5.3
10.8/9.9 1090/1122 2470/2047
15
230/208
4.8/5.3
15.6/14.5 1090/1122 3570/2997
20
230/208
4.8/5.3
22.5/20.0 1090/1122 5170/4147
30
230/208
6.8/7.6
10.9/10.0 1543/1473 2517/2117
15
230/208
6.8/7.6
15.7/14.6 1543/1473 3617/3067
20
230/208
6.8/7.6
22.6/20.1 1543/1473 5217/4217
30
265
2.4
9.2
567
2396
15
265
2.4
13.3
567
3496
20
265
3.1
9.2
791
2396
15
265
3.1
13.3
791
3496
20
265
4.2
9.4
1090
2470
15
265
4.2
13.5
1090
3570
20
265
4.2
19.6
1090
5170
25
265
6.0
9.7
1543
2517
15
265
6.0
13.8
1543
3617
20
265
6.0
19.9
1543
5217
25
HEAT PUMP
MODEL
NUMBER
52PQ-207---3
52PQ-307---3
52PQ-209---3
52PQ-309---3
52PQ-212---3
52PQ-312---3
52PQ-512---3
52PQ-215---3
52PQ-315---3
52PQ-515---3
52PQ-207---4
52PQ-307---4
52PQ-209---4
52PQ-309---4
52PQ-212---4
52PQ-312---4
52PQ-512---4
52PQ-215---4
52PQ-315---4
52PQ-515---4
132
COOLING
(Btuh)
EER
7200/7100 12.7/12.7
7200/7100 12.7/12.7
9100/9000 11.5/11.5
9100/9000 11.5/11.5
12100/12000 11.1/10.7
12100/12000 11.1/10.7
12100/12000 11.1/10.7
14500/14000 9.4/9.5
14500/14000 9.4/9.5
14500/14000 9.4/9.5
7200
12.7
7200
12.7
9100
11.5
9100
11.5
12100
11.1
12100
11.1
12100
11.1
14500
9.4
14500
9.4
14500
9.4
REVERSE
EVAP FAN
CYCLE HEAT
CFM
(HI-SPEED)
(Btuh)
6300/6300
6300/6300
7900/7900
7900/7900
11000/11000
11000/11000
11000/11000
13400/13200
13400/13200
13400/13200
6300
6300
7700
7700
10800
10800
10800
13400
13400
13400
260/250
260/250
260/250
260/250
350/320
350/320
350/320
290/270
290/270
290/270
260
260
260
260
340
340
340
290
290
290
APPROX.
WEIGHT
(SHIP)
125
125
125
125
140
140
140
150
150
150
125
125
125
125
140
140
140
150
150
150
CURRENT (AMPS) INPUT POWER (WATTS BRANCH
1-PH 60Hz
CIRCUIT
ELECTRIC
ELECTRIC
FUSE
VOLTS
COOLING
COOLING
HEAT
HEAT
(AMPS)
230/208
2.7/2.9
10.4/9.5
567/559
2393/1985
15
230/208
2.7/2.9
15.2/14.1
567/559
3493/2935
20
230/208
3.7/3.8
10.4/9.5
791/783
2393/1985
15
230/208
3.7/3.8
15.2/14.1
791/783
3493/2935
20
230/208
4.8/5.3
10.8/9.9 1090/1122 2470/2047
15
230/208
4.8/5.3
15.6/14.5 1090/1122 3570/2997
20
230/208
4.8/5.3
22.5/20.0 1090/1122 5170/4147
30
230/208
6.8/7.6
10.9/10.0 1543/1473 2517/2117
15
230/208
6.8/7.6
15.7/14.6 1543/1473 3617/3067
20
230/208
6.8/7.6
22.6/20.1 1543/1473 5217/4217
30
265
2.4
9.2
567
2396
15
265
2.4
13.3
567
3496
20
265
3.1
9.2
791
2396
15
265
3.1
13.3
791
3496
20
265
4.2
9.4
1090
2470
15
265
4.2
13.5
1090
3570
20
265
4.2
19.6
1090
5170
25
265
6.0
9.7
1543
2517
15
265
6.0
13.8
1543
3617
20
265
6.0
19.9
1543
5217
25
• Commercial Product Guide • 2002 •
16JB
Commercial Products
Steam/Hot Water Single-Effect, Hermetic
Absorption Liquid Chiller
108 to 680 Nominal Tons
(380 to 2392 kW)
Carrier’s 16JB single-effect hermetic absorption liquid chiller
offers a viable alternative to traditional electric driven chillers.
By utilizing low pressure steam or hot water, the 16JB avoids
high cost electricity and qualifies for utility rebates and
incentives as a gas cooling product. The utilization of low
pressure steam or hot water in the generator provides the 16JB
with application flexibility.
• No CFCs; environmentally friendly
• One-stage design for simple, reliable operation
• Operates using low pressure steam or hot water
• Quiet, vibration-free operation
• Few moving parts equates to high reliability
• Nominal 18 lb/hr-ton steam rate
• Direct digital controls (DDC) available as an option
• Commercial Product Guide • 2002 •
133
Performance & Sizing Information
16JB SINGLE-EFFECT STEAM/HOT WATER*
NOMINAL
CAPACITY
LENGTH
WIDTH
HEIGHT
SHIPPING
WEIGHT
Tons
kW
ft-in.
mm
ft-in.
mm
ft-in.
mm
Lbs
Kg
100
200
350
500
680
350
700
1,230
1,760
2,390
16-9
16-10
16-10
21-8
21-8
5,110
5,130
5,130
6,600
6,600
3-8
4-5
6-4
6-4
7-5
1,120
1,350
1,930
1,930
2,260
7-4
7-10
10-2
11-10
13-2
2,240
2,390
3,100
3,610
4,010
9,000
12,300
18,900
28,500
35,400
4,100
5,600
8,600
12,900
16,100
*Partial listing of available sizes.
134
• Commercial Product Guide • 2002 •
19XR,XRV
Commercial Products
High-Efficiency Hermetic Centrifugal Liquid Chiller
19XR - 200 to 1500 Nominal Tons (703 to 5275 kW)
19XRV - 200 to 800 Nominal Tons (703 to 2813 kW)
Carrier’s Evergreen™ chillers offer the best value in
high-efficiency chlorine-free centrifugal chillers.
Today’s customers demand high-efficiency products with
exceptional value. Carrier’s Evergreen centrifugal chillers
provide this value by achieving energy efficiency levels using
proven technology designed specifically for chlorine-free
refrigerant. This combination ensures the most cost-effective,
reliable solution for today’s comfort cooling and process
cooling applications.
Carrier has significantly reduced the power consumption of
HFC-134a positive-pressure chillers. The result is ultrahigh
energy efficiencies, giving the Evergreen chillers the highest
efficiency of any chlorine-free chiller in the world.
With the use of unit mounted refrigerant cooled (19XRV)
variable frequency drives, IPLV values in the range
of 0.35 kW/ton can be achieved.
• Commercial Product Guide • 2002 •
135
Performance & Sizing Information
C
A
B
NOMINAL
HEAT
CAPACITY EXCHANGER
(Tons)
SIZE
A (LENGTH, WITH NOZZLE-IN-HEAD
WATERBOX)
2-Pass
B (WIDTH)
C (HEIGHT)
1 or 3 Pass
ft-in.
mm
ft-in.
mm
ft-in.
mm
ft-in.
mm
200
10 TO 12
11-4
3454
11-11
3632
4-11 3/4
1518
6-1 1/4
1861
225
15 TO 17
13-7 3/8
4150
14-2 1/4
4324
4-11 3/4
1518
6-1 1/4
1861
250
20 TO 22
11-5 1/8
3483
12-0
3658
5-5 3/4
1670
6-3 1/4
1911
300
30 TO 32
13-8 1/4
4172
14-3 1/4
4350
5-5 3/4
1670
6-9 5/8
2073
350
35 TO 37
15-4 3/4
4693
15-11 3/4
4870
5-5 3/4
1670
6-9 5/8
2073
450
40 TO 42
13-11
4242
14-7
4445
6-2
1880
7-0 3/4
2153
500
45 TO 47
15-8
4775
16-3 1/4
4959
6-2
1880
7-0 3/4
2153
550
50 TO 52
13-11 1/4
4248
14-6 3/4
4439
6-6 1/2
1994
7-2 7/8
2207
600
55 TO 57
15-7 3/4
4769
16-3 1/4
4959
6-6 1/2
1994
7-2 7/8
2207
700
60 TO 62
13-11 3/4
4261
14-7 1/4
4451
6-10 1/2
2096
7-4 7/8
2257
800
65 TO 67
15-8 1/4
4782
16-3 3/4
4972
6-10 1/2
2096
7-4 7/8
2257
1000
70 TO 72
16-2
4937
16-10
5131
7-11 1/2
2426
9-9 1/2
2985
1200
75 TO 77
18-2
5537
18-10
5740
7-11 1/2
2426
9-9 1/2
2985
1300
80 TO 82
16-3
4953
16-11
5156
8-10 3/4
2711
9-11 1/4
3029
1500
85 TO 87
18-3
5603
18-11
5766
8-10 3/4
2711
9-11 1/4
3029
136
• Commercial Product Guide • 2002 •
23XL
Commercial Products
Hermetic Screw Liquid Chiller
60 Hz - 275 to 360 Nominal Tons (967 to 1,270 kW)
50 Hz - 229 to 300 Nominal Tons (805 to 1,060 kW)
The 23XL screw chiller provides the performance and
reliability of a centrifugal class machine by using advanced
engineering technology. Optimized for low life cycle costs,
the 23XL offers superior value in a compact design.
Features
• Innovative direct digital controls combine an easy to use
Chiller Visual Controller (CVC) with sophisticated
capabilities.
• Carrier’s factory testing program ensures quality
while providing peace of mind and protecting your
chiller investment.
• Exceptional full and part load efficiencies, coupled with
a design that is easy to install and maintain, provide low
overall cost of ownership
• The rugged, reliable, and fully field serviceable compressor
is designed for a lifetime of trouble-free operation
• A low leak, ASME certified, positive pressure design
uses environmentally acceptable HCFC-22 or
HFC-134a refrigerant
• Commercial Product Guide • 2002 •
137
Performance & Sizing Information
NOMINAL
CAPACITY
Tons
275
300
325
360
138
kW
967
1055
1142
1266
HEAT
EXCHANGER
SIZE
40-43
40-43
40-43
40-43
DIMENSIONS
LENGTH
ft-in.
13-8
13-8
13-8
13-8
mm
4166
4166
4166
4166
WIDTH
ft-in.
5-11
5-11
5-11
5-11
mm
1803
1803
1803
1803
HEIGHT
ft-in.
7-7
7-7
7-7
7-7
mm
2311
2311
2311
2311
• Commercial Product Guide • 2002 •
OPERATING
WEIGHT
lbs
24250
25010
24250
25010
kg
11000
11345
11000
11345
30HX
Commercial Products
Indoor Water-Cooled & Condenserless Chillers
50/60 Hz – 70 to 265 Nominal Tons
Com
NA
L e a vi
MO
Run
R™
k
re
DE
Status
ce Te
Pres
Lin
ATO
ng W
a te r
4 4 . 0 Te m p e
ra tu
°F
Ala rm
Servi
Temp
fort
VIG
St atu
s
st
eratur
es
sures
Setpo
ints
Inputs
Outpu
ts
Confi
gurat
ion
Time
Clock
Opera
ting
Mode
Alarm
s
s
ENT
ESC
ER
Reliable, Efficient Design
Specifications
• Serviceable Semi-Hermetic Twin Screw Compressors
• Efficiencies to < .53 kW/Ton
• Dual Independent Refrigerant Circuits
• HFC 134a Refrigerant
• Factory Load Tested
General:
Compressor:
Cooler:
Easy Installation
• Compact Design for Easy Indoor Installation
• Completely Packaged for Quick Installation
• ETL/C Approved
Condenser:
Control:
Options:
ETL Canada Listed, manufactured in ISO 9002
facility, ARI certified for performance
(Water-cooled only)
Serviceable semi-hermetic screw
compressors, dual independent
refrigerant circuits
Shell and tube type; 300 psig waterside
design*; ASME stamped
Shell and tube type; 300 psig waterside
design*; ASME stamped
Microprocessor leaving temperature
control, 4 Line 20 Character display in
English, Spanish, French, Portuguese
Water-cooled and condenserless, wye delta
starter, flow switch, control transformer,
sound enclosure, clamp-on cooler and
condenser connections for easy assembly
non-fused disconnect, Low Temperature
brine (To 15° F [-9° C]) Dual Chiller
Control
* 250 psig waterside in Canada
• Commercial Product Guide • 2002 •
139
Performance & Sizing Information
PERFORMANCE & PHYSICAL DATA - 60 HZ WATER COOLED
MODEL
CAPACITY
(Tons)
IPLV
(kW/Ton)
LENGTH
ft
WIDTH
ft
HEIGHT
ft
OPER WEIGHT
(lbs)
30HXC076
30HXC086
30HXC096
30HXC106
30HXC116
30HXC126
30HXC136
30HXC146
30HXC161
30HXC171
30HXC186
30HXC206
30HXC246
30HXC261
30HXC271
74
82
92
103
112
121
134
143
155
164
176
211
246
255
265
.53
.54
.53
.55
.53
.53
.55
.55
.58
.56
.59
.53
.54
.54
.54
8.5
8.5
8.5
8.5
8.5
11.1
11.1
11.1
11.1
11.1
11.1
11.1
12.4
12.4
12.4
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.9
2.9
2.9
3
3
3
3
5.4
5.4
5.4
5.6
5.4
5.4
5.4
5.4
5.8
5.8
5.8
6.2
6.2
6.2
6.2
5700
5723
5855
6177
6415
6465
6688
6718
7452
7660
7854
10581
10696
10992
11029
Contact your local Carrier representative for condenserless ratings.
Rated in
accordance with
ARI Standard
550/590-98
140
• Commercial Product Guide • 2002 •
R
30GTN
Commercial Products
Air-Cooled Chillers
with ComfortLink™
40 to 400 Nominal Tons
30GTN040-110
Features
• Simple, Easy to use, “Clear Language” Controls
• 30% Faster start-ups with less training
• Multiple Language Display standard
• Optional Hand-held Navigator Display for
Faster Troubleshooting
• Sound comparable with many screw chillers
• Capable of variable flow operation
• Wide operating range (-20° to 125° F)
• Carrier Comfort Network (CCN) Ready
• Simple Energy Management Interface to EMS/BMS Systems
• 300 psig (2068 kPa) Cooler Waterside Pressure Rating
• ARI Certified Efficiencies/ASHRAE 90.1 compliant
• Over 35,000 Worldwide Installations
• Available with Enviro-Shield™ Coil Corrosion protection and
E-Coat for superior protection from the most severe
environments
• Commercial Product Guide • 2002 •
30GTN130-210
141
Performance & Sizing Information
CARRIER AIR-COOLED CHILLERS
COOLING CAPACITY
MODEL
30GTN040
30GTN045
30GTN050
30GTN060
30GTN070
30GTN080
30GTN090
30GTN100
30GTN110
30GTN130
30GTN150
30GTN170
30GTN190
30GTN210
30GTN230
30GTN245
30GTN255
30GTN270
30GTN290
30GTN315
30GTN330
30GTN360
30GTN360
30GTN390
30GTN420
60 Hz
kW
126
146
177
223
255
288
307
350
378
426
493
553
606
707
781
802
844
900
988
1087
1106
1213
1313
1414
Tons
36
42
50
63
73
82
87
100
108
121
140
157
172
201
222
228
240
256
281
309
314
345
373
402
DIMENSIONS
50 Hz
kW
123
147
180
212
247
285
319
352
390
434
509
557
632
703
805
787
866
909
1022
1097
1113
1188
1335
1407
Tons
35
42
51
60
70
81
91
100
111
124
145
158
180
200
229
224
246
259
291
312
317
338
380
400
Length
mm
2515
2515
2515
3124
3124
3429
3429
4267
4267
5944
5944
5944
6858
6858
9354
9354
11887
10221
12527
11906
11906
13716
12815
13716
13716
ft
8.3
8.3
8.3
10.3
10.3
11.3
11.3
14.0
14.0
19.5
19.5
19.5
22.5
22.5
30.7
30.7
39.0
33.5
41.1
39.1
39.1
45.0
42.0
45.0
45.0
Width
mm
2261
2261
2261
2261
2261
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
2337
Height
ft
7.4
7.4
7.4
7.4
7.4
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
mm
2261
2261
2261
2261
2261
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
2438
ft
7.4
7.4
7.4
7.4
7.4
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
Rated in
accordance with
ARI Standard
590-92
R
(60 Hz Only)
142
• Commercial Product Guide • 2002 •
30GX
Commercial Products
Ecologic™ Air-Cooled Chillers
80 to 525 Nominal Tons
Com
NA
L e a vi
MO
Run
Lin
ATO
R™
ng W
a te r
4 4 . 0 Te m p e
ra tu
°F
k
re
DE
Status
Ala rm
Servi
ce Te
Temp
Pres
fort
VIG
St atu
s
st
eratur
es
sures
Setpo
ints
Inputs
Outpu
ts
Confi
gurat
Time
Opera
Alarm
ion
Clock
ting
Mode
s
ENT
ESC
s
ER
The 30GX family of chillers features Carrier’s 06N
Twin-Screw Compressors, Chlorine-Free R-134a Refrigerant,
New “Aeroacoustic” Fans, Low Pressure Drop, Mechanically
Cleanable Coolers and Advanced Microprocessor Controls.
Features
• The 30GX compact design is up to 35% smaller
• Carrier 06N Twin Screw Compressors (up to 8 dBA
quieter than competitive models) assure quiet, low
vibration operation
• R-134a refrigerant is completely Chlorine-Free and
environmentally friendly
• Aeroacoustic fans greatly reduce sound levels and
improve sound quality
• Low pressure drop, mechanically cleanable coolers with
moveable water heads minimizes installation costs and
enables performance to be maintained at optimum levels
• Advanced Microprocessor controls and Electronic
Expansion Valves provide fully automatic temperature
and time chilled fluid control, optimum part load efficiency
and easy maintenance and diagnostics. Enhanced Display
and CCN ready
• Standard series flow option provides greater efficiency with
higher temperature rise for large tonnage plants up to 700 tons
• More factory-installed options such as: Non-Fused
Disconnects, Brine Modification, Control Transformer, Low
Ambient (Motormaster®) Control, Dual-Chiller Control, and
Series-flow Heads
• Available with Enviro-Shield™ Coil Corrosion protection
and E-Coat for superior protection in the most severe
environments
• Commercial Product Guide • 2002 •
143
Performance & Sizing Information
30GX MODEL NO.
080
090
1 06
115
125
136
151
161
176
NOMINAL CAPACITY (Tons)
75
82
97
107
117
128
142
153
167
COMPRESSOR (TYPE) 06N
Geared Twin Screw
Number of Circuits/Compr.
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
2/2
REFRIGERANT ECONOMIZER
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
MIN STEP CAPACITY (%)
Standard
Optional
20%
10%
20%
10%
20%
10%
20%
10%
20%
10%
20%
10%
20%
10%
20%
10%
20%
10%
DIMENSIONS (Inches)
Length
Width
Height
114
86.5
86
114
86.5
86
132
86.5
86
132
86.5
86
132
86.5
86
APPROX WEIGHT (lbs)
6,313
6,333
7,379
7,389
7,554
168
86.5
86
8,717
168
86.5
86
9,118
231
86.5
86
9,446
231
86.5
86
10,056
REFRIGERANT TYPE
CAPACITY CONTROL STEPS
Standard
Optional
30GX MODEL NO.
206
226
251
265
281
301
325
350
NOMINAL CAPACITY (Tons)
191
210
233
244
267
287
309
334
COMPRESSOR (TYPE) 06N
Geared Twin Screw
Number of Circuits/Compr.
2/3
2 /3
2/3
2/3
2/4
2/4
2/4
2/4
REFRIGERANT ECONOMIZER
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
8
10
8
10
8
10
8
10
10
12
10
12
10
12
10
12
MIN STEP CAPACITY (%)
Standard
Optional
15%
10%
15%
10%
15%
10%
15%
10%
10%
6%
10%
6%
10%
6%
10%
6%
DIMENSIONS (Inches)
Length
Width
Height
267.2
86.5
86
267.2
86.5
86
303.3
86.5
86
303.3
86.5
86
APPROX WEIGHT (lbs)
12,794
12,974
13,774
13,829
339
86.5
86
18,250
339
86.5
86
18,270
339
86.5
86
18,310
339
86.5
86
18,360
30GX MODEL NO.
370
390
415
450
475
500
525
NOMINAL CAPACITY (Tons)
366
379
406
429
454
479
503
REFRIGERANT TYPE
CAPACITY CONTROL STEPS
Standard
Optional
COMPRESSOR (TYPE) 06N
Geared Twin Screw
Number of Circuits/Compr.
4/5
4/5
4/5
4/5
6/4
6/4
6/4
REFRIGERANT ECONOMIZER
Yes
Yes
Ye s
Yes
Yes
Yes
Yes
REFRIGERANT TYPE
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
R-134a
CAPACITY CONTROL STEPS
Standard
Optional
14
18
14
18
14
18
16
20
16
20
16
20
16
20
MIN STEP CAPACITY (%)
Standard
Optional
8%
4%
7%
3.15%
8%
4%
7.5%
5%
8%
4%
7.5%
5%
7.5%
5%
DIMENSIONS (Inches)
Length
Width
Height
435.6
86.5
86
435.6
86.5
86
470.4
86.5
86
APPROX WEIGHT (lbs)
21,769
21,617
22,974
498
86.5
86
25,970
534
86.5
86
26,852
576
86.5
86
27,734
715
86.5
86
27,804
Rated in
accordance with
ARI Standard
550/590-98
R
(60 Hz Only)
144
• Commercial Product Guide • 2002 •
30GX
Commercial Products
Ecologic η™ High-Efficiency
Air-Cooled Chillers
83 to 528 Nominal Tons
Com
NA
L e a vi
MO
Run
Servi
Temp
Pres
fort
VIG
Lin
ATO
R™
k
ng W
a te r
4 4 . 0 Te m p e
ra tu
°F
re
DE
Status
ce Te
Ala rm
St atu
s
st
eratur
es
sures
Setpo
ints
Inputs
Outpu
ts
Confi
gurat
ion
Time
Clock
Opera
ting
Mode
Alarm
s
s
ENT
ESC
ER
The 30GX family of chillers features Carrier’s 06N
Twin-Screw Compressors, Chlorine-Free R-134a Refrigerant,
New “Aeroacoustic” Fans, Low Pressure Drop, Mechanically
Cleanable Coolers and Advanced Microprocessor Controls.
Features
• Carrier 06N Twin Screw Compressors (up to 8 dBA
quieter than competitive models) assure quiet, low
vibration operation
• R-134a refrigerant is completely Chlorine-Free and
environmentally friendly
• Aeroacoustic fans greatly reduce sound levels and
improve sound quality
• Low pressure drop, mechanically cleanable coolers with
moveable water heads minimizes installation costs and
enables performance to be maintained at optimum levels
• Advanced Microprocessor controls and Electronic
Expansion Valves provide fully automatic temperature
and time chilled fluid control, optimum part load efficiency
and easy maintenance and diagnostics. Enhanced Display
and CCN ready
• Standard series flow option provides greater efficiency with
higher temperature rise for large tonnage plants up to 700 tons
• More factory-installed options such as: Non-Fused
Disconnects, Brine Modification, Control Transformer, Low
Ambient (Motormaster®) Control, Dual-Chiller Control, and
Series-flow Heads
• Available with Enviro-Shield™ Coil Corrosion protection
and E-Coat for superior protection in the most severe
environments
• Full load EER's from 10.0 to 10.4
• Commercial Product Guide • 2002 •
145
Performance & Sizing Information
30GX MODEL NO.
NOMINAL CAPACITY (Tons)
COMPRESSOR (TYPE) 06N
Number of Circuits/Compr.
REFRIGERANT ECONOMIZER
REFRIGERANT TYPE
CAPACITY CONTROL STEPS
Standard
Optional
MINI STEP CAPACITY (%)
Standard
Optional
DIMENSIONS
Length
Width
Height
APPROX WEIGHT (lbs)
30GX MODEL NO.
NOMINAL CAPACITY (Tons)
COMPRESSOR (TYPE) 06N
Number of Circuits/Compr.
REFRIGERANT ECONOMIZER
REFRIGERANT TYPE
CAPACITY CONTROL STEPS
Standard
Optional
MINI STEP CAPACITY (%)
Standard
Optional
DIMENSIONS
Length
Width
Height
APPROX WEIGHT (lbs)
30GX MODEL NO.
NOMINAL CAPACITY (Tons)
COMPRESSOR (TYPE) 06N
Number of Circuits/Compr.
REFRIGERANT ECONOMIZER
REFRIGERANT TYPE
CAPACITY CONTROL STEPS
Standard
Optional
MINI STEP CAPACITY (%)
Standard
Optional
DIMENSIONS
Length
Width
Height
APPROX WEIGHT (lbs)
146
83
77
93
85
108
98
2/2
No
2/2
No
2/2
Yes
6
8
6
8
6
8
6
8
6
8
6
8
20
10
20
10
20
10
20
10
20
10
132
86.5
86
8,649
132
86.5
86
8,664
132
86.5
86
6,907
118
106
128
138
153
116
128
141
Semi-Hermetic, Twin Screw
2/2
2/2
2/2
2/2
Yes
Yes
Yes
Yes
HFC 134a
132
132
86.5 86.5
86
86
7,201 7,662
163
153
178
169
208
200
2/2
Yes
2/2
Yes
3/2
Yes
6
8
6
8
6
8
8
10
20
10
20
10
20
10
20
10
15
10
231
86.5
86
8,789
231
86.5
86
9,684
231
86.5
86
10,279
228
210
253
240
268
253
3/2
Yes
3/2
Yes
3/2
Yes
8
10
8
10
8
10
12
16
12
16
15
10
15
10
15
10
10
5
498
86.5
86
18,473
303
86.5
86
14,114
418
401
5/4
Yes
339
339
86.5
86.5
86
86
16,736 16,751
283
303
328
275
287
317
Semi-Hermetic, Twin Screw
4/4
4/4
4/4
Yes
Yes
Yes
HFC 134a
453
478
503
429
461
492
Semi-Hermetic, Twin Screw
6/4
6/4
6/4
Yes
Yes
Yes
HFC 134a
303
303
86.5
86.5
86
86
10,294 14,099
353
346
373
376
393
385
4/4
Yes
5/4
Yes
5/4
Yes
12
16
12
16
14
18
14
18
10
5
10
5
10
5
8
4
8
4
498
86.5
86
19,068
570.25
86.5
86
19,978
642.5
86.5
86
20,588
606
86.5
86
25,525
606
86.5
86
26,420
528
517
6/4
Yes
14
18
16
20
16
20
16
20
16
20
8
4
7.5
5
8
4
7.5
5
7.5
5
606
86.5
86
26,435
642.5
86.5
86
28,228
642.25
86.5
86
30,850
714
86.5
86
33,472
714
86.5
86
33,502
• Commercial Product Guide • 2002 •
30RA
Commercial Products
AQUASNAP™ Chiller
with Integrated Hydronic System
10 to 55 Nominal Tons
Carrier's 30RA – “AQUASNAP” features a compact, efficient
and quiet all-in-one package design.
AQUASNAP features Carrier's latest “Aeroacoustic” fan
mounted on a rigid tower structure, and ultraquiet, highefficiency scroll compressors to eliminate noise concerns and
keep utility costs down. The AQUASNAP also offers optional
pump, piping, piping specialties, and fluid storage tank built
into the compact unit, to create an all-encompassing chilled
water plant.
One wrench and one screwdriver, and you're ready to go —
Features
• The 30RA is a highly efficient air-cooled chiller,
with full-load EERs up to 10.1 and part-load ratings
as high as 14.2
• AQUASNAP chillers use ultraquiet, high-efficiency scroll
compressors, operated in tandem for greater efficiency at
partial loads
• Field-proven design is backed by a 12-month warranty that
includes the hydronic system
• Flow switch, strainer, and blow-down valve are all
standard components
• The compressor is maintenance-free and protected by an
auto-adaptive control that minimizes compressor wear
• Units 34 tons and up have two independent
refrigerant circuits
• AQUASNAP is low profile — all models are just 4'-4" high
• The ComfortLink™ control system monitors and controls
each AQUASNAP chiller in plain English, Portuguese,
Spanish, or French
• The large Scrolling Marquee display provides up to 60
characters for the 15 diagnostic read/write functions
• All-in-one design greatly reduces the overall applied
cost of the chilled water plant
• Low-speed fan operation during part load offers even
quieter operation at night
• Optional water tank prevents problems associated with
“short” water loops
• Optional freeze protection and low ambient operation
to -20° F (-29° C)
• Commercial Product Guide • 2002 •
147
Performance & Sizing Information
60 Hz Data
MODEL 30RA
010
015
018
022
025
030
035
040
045
050
055
Nominal Cooling
Capacity (Tons)
Nominal Cooling
Capacity (kW)
Length
(in. [mm])
Width
(in. [mm])
Height
(in. [mm])
Approx. Weight
(Chiller Only)
(lbs. [kg])
9
13
16
20
24
27
34
37
42
47
53
31
45
56
70
84
94
119
130
147
165
186
82
82
82
108
108
108
108
108
108
108
108
(2083) (2083) (2083) (2743) (2743) (2743) (2743) (2743) (2743) (2743) (2743)
43
43
43
43
43
43
90
90
90
90
90
(1092) (1092) (1092) (1092) (1092) (1092) (2286) (2286) (2286) (2286) (2286)
52
52
52
52
52
52
52
52
52
52
52
(1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321)
930
(422)
1046
(474)
1182
(536)
1491
(676)
1551
(704)
1660 2815 2874 3220 3319 3520
(753) (1277) (1304) (1461) (1505) (1597)
MODEL 30RA
010
015
018
022
025
032
035
042
045
Nominal Cooling
Capacity (Tons)
Nominal Cooling
Capacity (kW)
Length
(in. [mm])
Width
(in. [mm])
Height
(in. [mm])
Approx. Weight
(Chiller Only)
(lbs. [kg])
9
12
14
18
22
27
32
38
44
31
42
49
63
77
94
112
133
154
50 Hz Data
148
82
82
82
108
108
108
108
108
108
(2083) (2083) (2083) (2743) (2743) (2743) (2743) (2743) (2743)
43
43
43
43
43
90
90
90
90
(1092) (1092) (1092) (1092) (1092) (2286) (2286) (2286) (2286)
52
52
52
52
52
52
52
52
52
(1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321) (1321)
961
(436)
1171
(531)
1182
(536)
1523
(691)
1592 2786 2895 3269 3386
(722) (1264) (1313) (1483) (1536)
• Commercial Product Guide • 2002 •
30HK,HL,HWC
Commercial Products
Indoor Water-Cooled & Condenserless Chillers
50/60 Hz 15 to 60 Nominal Tons
Easy Installation
Specifications
• Compact design for easy indoor installation
• Clamp on Cooler Connections for easy assembly
• Standard Control Transformer
General:
Compressor:
Reliable, Efficient Design
• Serviceable Semi-Hermetic Recip Compressors
• High Efficiency Suction Cutoff Unloading
Cooler:
Condenser:
Control:
Options:
• Commercial Product Guide • 2002 •
UL, CSA Listed, manufactured in ISO 9002
facility, ARI certified for performance
Serviceable semi-hermetic reciprocal
compressors, high efficiency suction cut-off
unloading, dual independent refrigerant
circuits (HK040-060)
Clamp on Victaulic type connections;
ASME stamped
Shell and tube type; ASME stamped
Microprocessor-based leaving
temperature control
Water-cooled and condenserless, flow switch,
Scrolling Marquee Display, control transformer
(standard 30HW), sound enclosure, gauge
panel, automatic lead/lag package
(HK,HL040-060)
149
Performance & Sizing Information
PERFORMANCE DATA - 60 HZ WATER COOLED
MODEL
CAPACITY
(TONS)
30HWC018
30HWC025
30HWC028
30HWC035
30HWC040
30HK040
30HK050
30HK060
15.7
19.7
25.2
27.9
37.5
40.7
50.0
58.1
EFFICIENCY
(BTU/WATTHR)
IPLV
17.1
17.5
16
14.9
14.5
17.4
16
15.8
Contact your local Carrier representative for condenserless
and 50 Hz ratings
PHYSICAL/ELECTRICAL DATA
MODEL
LENGTH
(ft)
WIDTH
(ft)
HEIGHT
(ft)
OPER.
WEIGHT
(lbs)
208
230
460
380/415-50
30HWC018
30HWC025
30HWC028
30HWC035
30HWC040
30HK040
30HK050
30HK060
7.2
7.2
7.2
7.2
7.2
8.2
8.6
8.6
2.1
2.1
2.1
2.1
2.1
2.8
2.8
2.8
3.5
3.5
3.5
3.5
3.5
4.9
4.9
4.9
1231
1359
1484
1508
1702
2830
3210
3340
62
72
89
102
145
129
161
187
62
72
89
102
145
129
161
187
28
34
44
48
69
59
75
88
34
38
54
54
78
71
81
131
MCA
Rated in
accordance with
ARI Standard
550/590-98
R
(60 Hz Only)
150
• Commercial Product Guide • 2002 •
30HWA,HWB
Commercial Products
Indoor Water-Cooled & Condenserless Chillers
15 to 215 Nominal Tons
Easy Installation
Controls:
• Each 30" Wide Component Unit Fits Through a Door
(Wheels Optional)
• Each Component Unit Easily Fits In Elevator
• No Time-Consuming Unit Disassembly Required
• Quick Clamp-On Cooler and Condenser
(Water Cooled Only) Fittings
Microprocessor-based Leaving
Temperature Control
• Scrolling Marquee Display
• Brine For Cooler Temperatures
Below 40° F
• Hot Gas Bypass for Low Loads
• Vibration Isolation
• Condenserless for Special
Condenser Applications
• Flow Switch
• Wheels
• Chillervisor™ System Manager
Options:
Reliable
• True Redundancy - Multiple Independent Refrigerant
Circuits and Controls (075-215)
• Serviceable Semi Hermetic 06E Compressors
• Stainless Steel Cooler and Condensers (Water Cooled Only)
Rated for 300 PSIG Waterside Pressure
CONTROL (TYP)
ELECTRIC POWER (TYP)
Specifications
General:
Compressor:
Cooler:
Condenser:
UL Approved Component Base Units,
Manufactured in ISO 9002 Facility, Each
Water Cooled Component Unit is ARI
Certified for Performance
Single Serviceable Semi Hermetic
Recip With 3 Steps Unloading Per
Component Unit
300 PSIG, Stainless Steel Brazed Plate
Construction, Victaulic Type Connections
300 PSIG, Stainless Steel Brazed Plate
Construction, Victaulic Type Connections
(Water Cooled Only)
PLAN VIEW
A
37”/940mm
5.75”
11.7” (TYP)
12.3” (TYP) 6” (TYP)
B (TYP)
CLR 1 CND 0
CLR 1 CND 0
CLR 1 CND 0
CLR 1 CND 0
CLR 0 CND 0
CLR 0 CND 1
CLR 0 CND 1
CLR 0 CND 1
18”/458mm
55.6”/1412mm
BACK VIEW
34”/864mm
30”/864mm (TYP)
LENGTH
CLR 1 = COOLER INLET
CLR 0 = COOLER OUTLET
• Commercial Product Guide • 2002 •
CND 1 = CONDENSER INLET
CND 0 = CONDENSER OUTLET
151
Performance & Sizing Information
WATER COOLED
COOLING CAPACITY
MODEL
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
30HWB
60 Hz
QTY
COMPONENT
UNITS
50 Hz
kW Out
Tons
kW Out
Tons
52
69
89
100
126
253
301
379
401
501
505
601
631
758
15
20
25
29
36
72
86
108
114
143
144
171
180
215
46
60
78
88
111
222
264
332
352
440
443
528
554
665
13
17
22
25
32
63
75
95
100
125
126
150
158
189
018
025
028
035
040
075
090
110
115
140
150
170
180
215
1
1
1
1
1
2
3
3
4
5
4
6
5
6
DIMENSIONS
Length
Width
Height
WATER
TOTAL
NOZZLE OPERATING
DIA(in.) WEIGHT (lbs)
A
mm
ft
mm
ft
mm
ft
mm
in.
762
762
762
762
762
1524
2286
2286
3048
3810
3048
4572
3810
4572
2.5
2.5
2.5
2.5
2.5
5.0
7.5
7.5
10.0
12.5
10.0
15.0
12.5
15.0
940
940
940
940
940
940
940
940
940
940
940
940
940
940
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
2835
2835
2835
2835
2499
2499
2835
2499
2835
2835
2499
2835
2499
2499
9.3
9.3
9.3
9.3
8.2
8.2
9.3
8.2
9.3
9.3
8.2
9.3
8.2
8.2
1-1/2"
1-1/2"
1-1/2"
1-1/2"
2-1/2"
2-1/2"
1-1/2"
2-1/2"
1-1/2"
1-1/2"
2-1/2"
1-1/2"
2-1/2"
2-1/2"
795
950
1065
1085
1310
2620
3255
3930
4340
5425
5240
6510
6550
7860
CONDENSERLESS
COOLING CAPACITY
QTY
COMPONENT
UNITS
MODEL
60 Hz
50 Hz
kW Out Tons kW Out
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
30HWA
018
025
028
035
040
075
090
110
115
140
150
170
180
215
47
62
79
88
112
224
264
337
352
440
449
528
561
673
14
18
23
25
32
64
75
96
100
125
128
150
160
191
43
55
75
81
113
226
244
339
325
406
452
487
564
677
Tons
12
16
21
23
32
64
69
96
92
116
128
139
161
193
1
1
1
1
1
2
3
3
4
5
4
6
5
6
DIMENSIONS
Length
Width
TOTAL
WATER
TING
NOZZLE OPWEERIA
GHT
Dia(in.)
(lbs)
Height
mm
ft
mm
ft
mm
ft
724
724
724
724
724
1448
2172
2172
2896
3620
2896
4343
3620
4343
2.4
2.4
2.4
2.4
2.4
4.8
7.1
7.1
9.5
11.9
9.5
14.3
11.9
14.3
902
902
902
902
902
902
902
902
902
902
902
902
902
902
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
1415
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
1-1/2"
1-1/2"
1-1/2"
1-1/2"
2-1/2"
2-1/2"
1-1/2"
2-1/2"
1-1/2"
1-1/2"
2-1/2"
1-1/2"
2-1/2"
2-1/2"
Rated in
accordance with
ARI Standard
590-92
740
880
960
975
1080
2160
2925
3240
3900
4875
4320
5850
5400
6480
R
(60 Hz Only)
152
• Commercial Product Guide • 2002 •
09DE,DK
Commercial Products
Outdoor Air-Cooled Condenser
18 to 116 Nominal Tons
Features
• Multiple Circuit Splits
• Multiple Refrigerant Capability
• Functional Run Test
• “Weather Armor” Baked Enamel Finish
• Assured Quality (ISO 9002)
• Compact Design
• Easy Access to Controls
• Two or More Condensing Circuits
09DE016
Factory-Installed Options
• Enviro-Shield™ Condenser Coil Protection
• Aluminum Fin or Copper Fin Coils
Field-Installed Accessories
•
•
•
•
Low Ambient Control
Condenser Coil Protective Grille (054-094)
Condenser Coil Hail Guard (054-094)
Sound Reduction Package (054-094)
09DK020-044
09DK054-094
• Commercial Product Guide • 2002 •
153
Performance & Sizing Information
PERFORMANCE
MODEL
CAPACITY
TONS
NUMBER OF
REFRIGERANT CIRCUITS
09DE016
09DK020
09DK024
09DK028
09DK034
09DK044
09DK054
09DK064
09DK074
09DK084
09DK094
18.4
21.9
25.9
33.3
48
56.2
65.8
78.6
95.4
103.5
116.3
2
2
2
3
3
4
4
4
4
4
2
TOTAL OP. WEIGHT (lbs)
AL Coil
CU Coil
465
762
762
944
1438
1589
1645
1771
2106
2310
2714
605
815
815
986
1493
1638
1933
2204
2523
2988
3424
Ratings based on 45 F SST and 95 F Ent. Air Temperature & 60 Hz power supply
OVERALL DIMENSIONS
MODEL
LENGTH
(ft-in.)
HEIGHT
(ft-in.)
WEIGHT
(ft-in.)
09DE016
09DK020
09DK028
09DK034
09DK044
09DK054
09DK064
09DK074
09DK084
09DK094
6 - 4 1/4
8 - 10 7/8
8 - 10 7/8
12 - 9 1/4
12 - 9 1/4
8 - 3 9/16
8 - 3 9/16
10 - 3 1/4
10 - 3 1/4
11 -2 1/2
3 - 3 7/8
4 - 3 3/4
4 - 3 3/4
4 - 3 3/4
4 - 3 3/4
6 - 3 11/16
6 - 3 11/16
6 - 11 3/4
6 - 11 3/4
7 - 7 15/16
3-8
3 - 8 1/2
5 - 8 5/8
5 - 8 5/8
5 - 8 5/8
7 - 4 11/16
7 - 4 11/16
7 - 4 11/16
7 - 4 11/16
7-8
ELECTRICAL DATA (DUAL CIRCUIT)
MODEL
MCA
208/230
MOCP
MCA
460
MOCP
MCA
575
MOCP
09DE016
09DK020
09DK024
09DK028
09DK034
09DK044
09DK054
09DK064
09DK074
09DK084
09DK094
10.4
8.1
13.9
13.9
17.5
20.1
23.2
23.2
34
34
34
15
15
20
20
30
30
25
25
35
35
35
5.2
4
7
7
8.8
10.1
11.7
11.7
17.1
17.1
17.1
15
15
15
15
15
15
15
15
20
20
20
7.6
7.6
7.6
11
11
14.5
14.5
21.3
21.3
21.3
15
15
15
15
15
15
15
25
25
25
MCA = Minimum Circuit Amps
MOCP = Maximum Overcurrent Protection
154
• Commercial Product Guide • 2002 •
09BY
Commercial Products
Remote Air-Cooled Condenser
5 to 20 Nominal Tons
Features
Field-Installed Accessories
• Free Blow or Ducted Applications
• Mounts Indoors or Outdoors
• Use with 50BZ or other units
• All service done through rear or side panels
• TEFC 3 ph fan motors on adjustable belt drive fans
• External static capability over 1" wg
• Cabinet meets 500 hour salt spray requirement
• Available in 208/230-460V 3 ph one model for all voltage
requirements or 575V-3-60
• 24 V condenser controls designed to work with 50BZ Units
• Two circuits 10 to 20 ton
• Circuits may be manifolded
• UL Listed and manufactured in an ISO 9001 facility
• Low Ambient Control Dampers
• Inlet Filter Frame
• Commercial Product Guide • 2002 •
155
Performance & Sizing Information
REMOTE AIR COOLED CONDENSER
Model
Number
09BYN
Tons
Nom.
CFM
Weight
(lbs)
CKT
Fan
HP
006
008
012
014
016
024
5
7.5
10
12
15
20
3000
4500
6000
6800
7500
10000
267
357
441
471
837
970
1
1
2
2
2
2
2
3
5
5
5
7 1/2
Refrigerant
Connections
Liq
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
Dimensions (in.)
Gas
Length
Depth
Height
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
[email protected]/2
48 7/8
56
63 1/2
71
90 1/2
90 1/2
19 5/8
23 5/8
23 5/8
23 5/8
33 1/2
33 1/2
35 1/2
42 3/4
42 3/4
42 3/4
60
60
ELECTRICAL DATA
MODEL
MOTOR
HP
09BYN006
09BYN008
09BYN012
09BYN014
09BYN016
09BYN024
2
3
3
5
5
7 1/2
208/230 VOLT - 3 PH - 60 HZ
460 VOLT - 3 PH - 60 HZ
575 VOLT - 3PH - 60Hz
MCA
FUSE
MCA
FUSE
MCA
FUSE
8.5
12.4
19.1
19.1
19.1
28.1
15
20
30
30
30
50
4.3
6.3
9.5
9.5
9.5
14.1
15
15
15
15
15
25
3.4
4.9
7.6
7.6
7.6
11.3
15
15
15
15
15
20
Units factory wired for 460 volt, may be field wired for 208/230 volt.
FUSE - Maximum Fuse Size Allowed (Amps)
MCA - Minimum Circuit Amps
Only as listed
component
156
• Commercial Product Guide • 2002 •
09AW,AZ
Commercial Products
Remote Air-Cooled Condenser
1 to 20 Nominal Tons
Features
Factory-Installed Options
• Direct Drive Condenser Fan
• Heavy Duty Corrosion Resistant Fan Guards
• Vertical or Horizontal Air Flow
• Single or Dual Circuit Design
• Available in Single or 3 Phase Voltages
• Mounting Legs provided on all sizes
• Weatherproof Control Box
• UL and UL, Canada Listed
• 09AZ Models are configured to be the appropriate
match with 50BZ Units
– Correct number of circuits with subcooler in last pass
– Fan Contactor
– Coil Face area and Fins for ARI Rated capacity
and efficiency
• Embossed Aluminum Cabinet
• Low Sound Motor
• Fan Control Contactors (24 V)
• Fan Cycling Control for 2 Fan Units
• Speed Controlled Low Ambient Control
• Totally Enclosed Air Over Motors
• Subcooler Circuit (standard on 09AZ models)
• Copper, Polyester or Phenolic Coated Fins
• Fused Disconnect on 3 Phase Units
• 24 V Control Transformer
• Commercial Product Guide • 2002 •
157
Performance & Sizing Information
Model
09AW001 (H,V)
09AW002 (H,V)
09AW003 (H,V)
09AW004 (H,V)
09AW006 (H,V)
09AW008 (H,V)
09AW012 (H,V)
09AW014 (H,V)
09AW016 (H,V)
09AW018 (H,V)
09AW020 (H,V)
09AW001 (L,W)
09AW002 (L,W)
09AW003 (L,W)
09AW004 (L,W)
09AW006 (L,W)
09AW008 (L,W)
09AW012 (L,W)
09AW014 (L,W)
09AW016 (L,W)
09AW018 (L,W)
09AW020 (L,W)
09AZ006 (H,V)
09AZ008 (H,V)
09AZ012 (H,V)
09AZ014 (H,V)
09AZ016 (H,V)
09AZ006 (L,W)
09AZ008 (L,W)
09AZ012 (L,W)
09AZ014 (l,W)
09AZ016 (L,W)
Tons
1
2
3
4
5
7 1/2
10
12
15
17
20
1
2
3
4
5
7 1/2
10
12
15
17
20
5
7 1/2
10
12
15
5
7 1/2
10
12
15
CFM
3100
2750
3850
3700
7700
7400
7000
15700
15600
15400
15300
2540
2040
2850
2740
5700
5480
5110
11600
11400
11500
11300
3600
7500
15260
15132
14872
6400
5300
11070
10872
10566
Wt. (lbs)
109
121
144
160
234
259
283
510
518
536
555
109
121
144
160
234
259
283
510
518
530
555
234
259
510
518
518
234
259
518
536
555
REMOTE AIR COOLED CONDENSER
Circuits
HP
HP
Liq
Gas
1
1/2
5/8
5/8
1 or 2
1/2
5/8
7/8
1 or 2
1/2
5/8
7/8
1 or 2
1/2
7/8
1 1/8
1 or 2
1/2
7/8
1 1/8
1 or 2
1/2
1 1/8
1 3/8
1 or 2
1/2
1 1/8
1 3/8
1 or 2
1
1 1/8
1 3/8
1 or 2
1
1 3/8
1 5/8
1 or 2
1
1 3/8
1 5/8
1 or 2
1
1 3/8
1 5/8
1
1/4
5/8
5/8
1 or 2
1/4
5/8
7/8
1 or 2
1/4
5/8
7/8
1 or 2
1/4
7/8
1 1/8
1 or 2
1/4
7/8
1 1/8
1 or 2
1/4
1 1/8
1 3/8
1 or 2
1/4
1 1/8
1 3/8
1 or 2
1/2
1 1/8
1 3/8
1 or 2
1/2
1 3/8
1 5/8
1 or 2
1/2
1 3/8
1 5/8
1 or 2
1/2
1 3/8
1 5/8
1
1/2
7/8
1 1/8
1
1/2
1 1/8
1 3/8
2
1
1 1/8
1 3/8
2
1
1 3/8
1 5/8
2
1
1 3/8
1 5/8
1
1/4
7/8
1 1/8
1
1/4
1 1/8
1 3/8
2
1/2
1 3/8
1 5/8
2
1/2
1 3/8
1 5/8
2
1/2
1 3/8
1 5/8
Length (in.)
32 3/4
32 3/4
37 3/4
32 3/4
69 3/4
69 3/4
69 3/4
104 1/4
104 1/4
104 1/4
104 1/4
32 3/4
32 3/4
37 3/4
37 3/4
69 3/4
69 3/4
69 3/4
104 1/4
104 1/4
104 1/4
104 1/4
37 3/4
69 3/4
104 1/4
104 1/4
104 1/4
69 3/4
69 3/4
104 1/4
104 1/4
104 1/4
Depth (in.)
15 13/16
15 13/16
17 3/4
17 3/4
17 3/4
17 3/4
19
48
48
48
48
15 13/16
15 13/16
17 3/4
17 3/4
17 3/4
17 3/4
19
48
48
48
48
17 3/4
17 3/4
48
48
48
17 3/4
17 3/4
48
48
48
Height (in.)
40 5/8
40 5/8
45 5/8
45 5/8
45 5/8
45 5/8
45 5/8
42 3/4
42 3/4
42 3/4
42 3/4
40 5/8
40 5/8
45 5/8
45 5/8
45 5/8
45 5/8
45 5/8
42 3/4
42 3/4
42 3/4
42 3/4
45 5/8
45 5/8
42 3/4
42 3/4
42 3/4
45 5/8
45 5/8
42 3/4
42 3/4
42 3/4
REMOTE AIR COOLED CONDENSER
Model
09AW001 (H,V)
09AW002 (H,V)
09AW003 (H,V)
09AW004 (H,V)
09AW006 (H,V)
09AW008 (H,V)
09AW012 (H,V)
09AW014 (H,V)
09AW016 (H,V)
09AW018 (H,V)
09AW020 (H,V)
09AW001 (L,W)
09AW002 (L,W)
09AW003 (L,W)
09AW004 (L,W)
09AW006 (L,W)
09AW008 (L,W)
09AW012 (L,W)
09AW014 (L,W)
09AW016 (L,W)
09AW018 (L,W)
09AW020 (L,W)
09AZ006 (H,V)
09AZ008 (H,V)
09AZ012 (H,V)
09AZ014 (H,V)
09AZ016 (H,V)
09AZ006 (L,W)
09AZ008 (L,W)
09AZ012 (L,W)
09AZ014 (L,W)
09AZ016 (L,W)
Motor
HP
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1 1/2*
1 1/2*
1 1/2*
1 1/2*
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1 1/2
1 1/2
1 1/2
1 1/2
1/2
1/2
1 1/2*
1 1/2*
1 1/2*
1/4
1/4
1 1/2
1 1/2
1 1/2
208/230-1-60
MCA
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
NA
NA
NA
NA
15
15
15
15
15
15
15
NA
NA
NA
MOCP
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
NA
NA
NA
NA
15
15
15
15
15
15
15
NA
NA
NA
208/230-3-60
MCA
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
MOCP
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
460-3-60
MCA
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
MOCP
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
575-3-60
MCA
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
NA
NA
NA
NA
15
15
15
15
15
15
15
NA
NA
NA
MOCP
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
NA
NA
NA
NA
15
15
15
15
15
15
15
NA
NA
NA
*1 hp motor on 208/230-1-60 (1140 rpm)
Only as listed
component
(60 Hz Only)
158
• Commercial Product Guide • 2002 •
09AZ
Commercial Products
Remote Air-Cooled Condenser
100 to 220 Nominal Tons
Features
Factory-Installed Options
• Direct Drive Condenser Fan
• Heavy Duty Corrosion Resistant Fan Guards
• Vertical Air Flow
• Designed for matchup to 30HXA Condenserless Chillers
• Weatherproof Control Box
• UL and UL, Canada Listed
• Fan Control Contactors and Control Standard
• Selected for use with refrigerant R-134a
• Aluminum Cabinet
• Speed Controlled Low Ambient Control
• Totally Enclosed Air Over Motors
• Copper, Polyester or Phenolic Coated Fins
• Fused Disconnect
• Commercial Product Guide • 2002 •
159
Performance & Sizing Information
Physical Data
09AZV
102
112
122
132
142
162
172
182
For application with 30HXA:
106
116
126
136
146
161
171
186
091
101
151
171
206,246,
206
246
261
271
261,271
Circuit B Circuit A Circuit A Circuit A Circuit A
2300
2590
3081
3730
3770
2510
2800
3450
4040
4090
Operating Weight (lbs)
2495
3164
2590
4032
3110
3081
3730
3820
Shipping Weight (lbs)
2705
3374
2800
4242
3370
3450
4040
4130
Refrigerant
134a
FAN
Direct Drive, Vertical Discharge
Qty Fans
8
10
8
10
10
12
12
12
8
Prop Dia (in.)
26
26
26
26
26
26
26
26
26
Blade Qty
4
4
4
4
4
4
4
4
4
RPM
1140
1140
1140
1140
1140
1140
1140
1140
1140
Total Airflow (CFM)
124000 155000 124000 155000 155000 186000 186000 186000 124000
Motor HP
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/2
1 1/12
COIL
Arrangement
Horizontal, Aluminum Fin, Copper Tube
Rows (Circuit A/B)
4/3
3/3
4/4
4/3
4/4
4/3
4/4
4/4
3
Fins per Inch
14
14
14
14
10
12
10
14
14
Total Coil Face Area (ft2)
120.6 150.6 120.6 150.6 150.6 180.6 180.6 180.6
120.6
Number Refrigerant Circuits
2
2
2
2
2
2
2
2
1
Subcooler Circuit
Standard
CONNECTIONS
Discharge, A Circuit
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
NA
Liquid Out, A Circuit
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
NA
Discharge, B Circuit
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
Liquid Out, B Circuit
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
ELECTRICAL DATA
208-230-3-60
Min=187; Max=253
FLA-Fan Motor
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
MCA
53.6
66.0
53.6
66.0
66.0
79.6
79.6
79.6
53.6
MOCP
60.0
70.0
60.0
70.0
70.0
80.0
80.0
80.0
60.0
460-3-60
Min=414; Max=506
FLA-Fan Motor
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
MCA
27.2
33.8
27.2
33.8
33.8
40.5
40.5
40.5
27.2
MOCP
30.0
35.0
30.0
35.0
35.0
45.0
45.0
45.0
30.0
575-3-60
Min=518; Max=632
FLA-Fan Motor
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
MCA
19.8
24.6
19.8
24.6
24.6
29.4
29.4
29.4
19.8
MOCP
20.0
25.0
20.0
25.0
25.0
30.0
30.0
30.0
20.0
CONTROL CIRCUIT
115 V-1-60
8
26
4
1140
124000
1 1/2
10
26
4
1140
155000
1 1/2
12
26
4
1140
186000
1 1/2
12
26
4
1140
186000
1 1/2
4
14
120.6
1
4
14
150.6
1
4
10
180.6
1
4
12
180.6
1
3 1/8
2 5/8
NA
NA
3 1/8
2 5/8
NA
NA
3 1/8
2 5/8
NA
NA
3 1/8
2 5/8
NA
NA
6.5
53.6
60.0
6.5
66.0
70.0
6.5
79.6
80.0
6.5
79.6
80.0
3.3
27.2
30.0
3.3
33.8
35.0
3.3
40.5
45.0
3.3
40.5
45.0
2.4
19.8
20.0
2.4
24.6
25.0
2.4
29.4
30.0
2.4
29.4
30.0
Only as listed
component
160
• Commercial Product Guide • 2002 •
181
39L
Commercial Products
Air Handler Units
1,800 to 15,000 Nominal CFM
Features
• Horizontal and vertical draw-through arrangements for
heating, cooling, ventilation, and VAV applications
• Sloped stainless steel condensate drain pan complies with
ASHRAE Standard 62
• Small footprint assures rigging ease and reduced
space requirements
• High-efficiency fan minimizes fan surging and turbulence
and reduces operating costs
• Factory-installed, internally-mounted fan motors and drives
operate in a clean environment to extend motor and belt life
• Exclusive Nu-Fin coil surface provides peak heat transfer
• 39L units offer a wide variety of coils for your cooling,
heating, preheat with cooling, or cooling with reheat
applications
• Manufactured at ISO 9002 listed facility to guarantee quality
Installation, Maintenance and
AirManager™ Controller Features
• Factory assembled, compact size allows for installation
in tight places
• Factory assembled, pre-aligned drives and fans eliminate
field installation expense
• Hinged access doors on most sections ease service and
promote regular maintenance, saving time and money
• Filtration flexibility includes flat or angle filter sections
• AirManager controller can respond to input from a variety
of sensors to maintain ventilation requirements
• AirManager will shut down all fan operation in response to
smoke or fire detection systems. It can also activate a local
alarm and report an alarm condition through communication
to a Carrier user interface
• AirManager defends your system and building with a variety
of safety functions. They protect against freezing coils,
excessive humidity, and other problems
• AirManager takes indoor and outdoor temperatures, humidity
levels, and scheduling information into account to determine
and initiate the best, most economical occupied and
unoccupied-free-cooling solutions
Flexible, Compact Units Designed
with Unlimited Versatility
Available in sizes for vertical and horizontal draw-through
applications. Flexibility to meet a wide range of cooling,
heating and ventilation requirements and a small footprint
to ensure economical use of building space.
• Double-Wall Access Doors
• Units Shipped Fully Assembled
• Unit panels are constructed of pre-painted galvanized steel
to withstand 500-hour salt spray test per ASTM B-117
• Rugged pillow-block bearings rated at 200,000 hours
average life
• Mixing and Filter-Mixing boxes have parallel blades to
provide thorough, efficient air mixing
• Precision-balanced fan wheels limit vibration and eliminate
abnormal stress on bearings and other components
• Internally mounted motors and drives are installed and
aligned at the factory
• Commercial Product Guide • 2002 •
161
Performance & Sizing Information
MODEL
NOMINAL
CAPACITY*
(cfm)
39L03
39L06
39L08
39L10
39L12
39L15
39L18
39L21
39L25
DIMENSIONS (in.)
1500
3000
4100
5000
6400
7500
9000
12000
14000
A
B
C
30
34
37
37
37
45
49
49
57
38
46
50
58
66
66
66
78
78
25
29
33
33
33
40
44
44
52
* Capacities based on small face area coil @ 500 ft/m.
Dimensions are for typical 39LB cooling only.
C
B
A
Rated in
accordance with
ARI Standard
410 & 430
162
• Commercial Product Guide • 2002 •
39T
Commercial Products
Central Station Air Handlers
15,000 to 50,000 Nominal CFM
Features
• Flanged and gasketed modular components-units are available
as a single assembly up to 40-ft long, or shipped in sections
• Sloped stainless steel condensate drain pan complies with
ASHRAE Standard 62
• Efficient design requires less space than competitive units
• Design versatility - flexible, compact units; forward-curved,
airfoil and plenum fan wheels
• Factory-installed, internally-mounted fan motors and drives
operate in a clean environment to extend motor and belt life
• Manufactured at an ISO 9002 listed facility to guarantee
quality.
Installation, Maintenance and
AirManager™ Controller Features
• Modular construction ensures job site flexibility
• Flanges and gaskets on every section allows for
easy installation
• Compact size allows for installation in tight spaces
• Lifting brackets on all sections
• Double wall doors on both sides of fan, filter and
access sections
• All exterior panels are pre-painted G-90 galvanized steel
to minimize corrosion and provide durable life
• Filtration flexibility includes flat, angle or bag filter sections
• Slide out coils make servicing easy
• AirManager controller can respond to input from a variety of
sensors to maintain ventilation requirements
• AirManager will shut down all fan operation in response to
smoke or fire detection systems. It can also activate a local
alarm and report an alarm condition through communication
to a Carrier user interface
• AirManager defends your system and building with a variety
of safety functions. They protect against freezing coils,
excessive humidity, and other problems
• AirManager takes indoor and outdoor temperatures, humidity
levels, and scheduling information into account to determine
and initiate the best, most economical occupied and
unoccupied-free-cooling solutions
Flexible, Compact Units Designed
with Unlimited Versatility
• Horizontal or vertical draw-through/horizontal
blow-through
• ARI certified coils and fans
• Pillow-block bearings are rated at 200,000 hours average
life in 32-39 size forward-curved fans. Bearings in plenum
fans, sizes 32-92 size Airfoil Fans, and 49-61 size forwardcurved fans have 400,000 hour average life
• Standard low-leak dampers in mixing box sections
seal tightly
• All 39T coils have Carrier’s high performance
coil surface
• Standard internal 2" deflection
• Isolation of fan assembly reduces vibration and eliminates
that need for isolation of unit at time of installation
• Commercial Product Guide • 2002 •
163
Performance & Sizing Information
UNIT
39T32
39T39
39T49
39T61
39T74
39T92
NOMINAL
CAPACITY*
(cfm)
16,000
19,500
24,500
30,500
37,000
46,000
DIMENSIONS (in.)
A
B
Width
94
101
113
125
141
141
Height
58
62
70
78
82
98
Airway length is variable upon different component arrangements. Check the product
catalog for individual airway length of components.
* Capacity is based upon 500ft/m face velocity.
B
2 3/8”
A
Rated in
accordance with
ARI Standard
410 & 430
164
• Commercial Product Guide • 2002 •
39M
Commercial Products
Central Station Air Handlers
1,500 to 15,000 Nominal CFM
Features
• Standard unit panels are made using a sealed, double-wall
insulation system that is unique in the industry. Panels can be
washed down without affecting insulation integrity
• All panels are easily removable with quarter turn latches
actuated by a simple tool. No screws to lose, strip or break off!
• The 39M is the only standard air handler on the market today
to have a continuous thermal break as standard to prevent heat
transfer between the inner and outer panels
• Double bulb automotive style rubber gasketing assures a leak
rate of less than 1% at 3.5" wg. Seals are positively retained
and will not fall off or deteriorate over time like foam or slip
on rubber gasketing
• Quad-sloped, fully insulated condensate drain pan directs
condensate flow from all directions towards the drain
eliminating the possibility of standing water in the pan
• Vibration absorbent fan discharge seal is more durable and
efficient than traditional canvas duct transitions
• Manufactured at an ISO 9002 listed facility to guarantee
quality
Installation, Maintenance and
AirManager™ Controller Features
• User specifiable construction breaks ensure job site flexibility
• Lifting brackets at all section breaks
• Easily removable panels have no exposed metal edges to injure
service personnel or corrode
• Optional AeroConnect latch speeds up unit assembly at the
jobsite
• All exterior and interior panels are pre-painted galvanized steel
to minimize corrosion and provide durable life
• Filtration flexibility includes flat, angled, cartridge, bag and
HEPA filter sections as standard options!
• Slide out coils for easy serviceability
• AirManager controller can respond to input from a variety of
sensors to maintain ventilation requirements
• AirManager will shut down all fan operation in response to
smoke or fire detection systems. It can also activate a local
alarm and report an alarm condition through communication
to a Carrier user interface
• AirManager defends your system and building with a variety
of safety functions. They protect against freezing coils,
excessive humidity, and other problems
• AirManager takes indoor and outdoor temperatures, humidity
levels, and scheduling information into account to determine
and initiate the best, most economical occupied and
unoccupied free-cooling solutions
Flexible, Compact Units Designed
with Unlimited Versatility
• Horizontal or vertical draw-thru and horizontal blow-thru
configurations available
• ARI certified coils and fans
• Pillow-block bearings are rated at 200,000 hours average life
(L50) in all 03-30 size airfoil, forward-curve, backwardinclined and plenum fans. Optionally, bearings rated at
500,000 hours average life (L50) are available
• Standard low-leak dampers in dampered sections seal tightly.
Premium low pressure drop dampers are an available option
for exhaust and mixing box sections
• All 39M coils have Carrier's high performance coil surface
• Factory installed and wired Starters, Disconnects, and
Variable Frequency Drives are easily available at the click of
a button in AHUBuilder
• Commercial Product Guide • 2002 •
165
Performance & Sizing Information
UNIT
NOMINAL
CAPACITY*
(cfm)
39M03
39M06
39M08
39M10
39M12
39M14
39M17
39M21
39M25
39M30
1,500
3,000
4,000
5,000
6,000
7,000
8,500
10,500
12,500
15,000
DIMENSIONS (in.)
A
Width
39
39
42
42
49
49
52
62
62
62
B
Height
33
46
54
67
67
72
79
79
86
104
Airway length is variable upon different component arrangements. Check the product
catalog for individual airway length of components.
* Capacity is based upon 500ft/m face velocity.
B
2 3/8”
A
Rated in
accordance with
ARI Standard
410 & 430
166
• Commercial Product Guide • 2002 •
39NC
Commercial Products
Rooftop, Curb-Mounted Central Station Air Handlers
2,600 to 50,000 Nominal CFM
Features
• Weather-tight cabinets have sloped roofs to prevent
standing water
• Factory installed gaskets between overlapping panels
ensure leak-free performance
• Patent-pending double sealed doors with rain hoods
ensure moisture stays outside
• Unique intake damper hoods divert water away from
intake and integral moisture eliminators prevent atomized
water entry
• Bottom frame includes a channel for mounting unit to
roof curb
• Insulated double-wall construction is standard
• Sloped stainless steel condensate drain pan complies with
ASHRAE Standard 62
• Design Versatility - Flexible, compact units; forward-curved,
airfoil, and plenum fan wheels
• Factory-installed, internally-mounted fan motors and drives
operate in a clean environment to extend motor and belt life
Versatile Components
• Small footprint contributes to application and
installation flexibility
• Rugged welded 3/16-in. thick steel lifting lugs assure
safe rigging and placement of unit
• Fan and motor bearings are mounted on a corrosion-resistant
steel frame, which is isolated from the outer casing with
factory-installed 2" spring isolators and vibration absorbent
fan discharge seal
• Doors on both sides of fan section allow for service
and maintenance access from both sides of the unit
• Factory balancing of fan wheel ensures smooth,
trouble-free operation
• Filtration flexibility includes flat, angle or bag filter sections
• Slide-out coils make servicing easy
Flexible Compact Units Designed with
Unlimited Versatility
• Casing withstands 5" wg negative and 9" wg positive total
static pressure to meet design conditions while maintaining
structural integrity
• Weather-tight design is tested with 13" of water per hour
at 5" wg negative pressure without leakage
• ARI Certified Coils and Fans
• Pillow-block bearings are rated at 200,000 hours Average Life
in 07-32 size Airfoil Fans and 07-39 Size Forward-Curved
Fans. Bearings in 32-92 size Airfoil Fans, and 49-61 size
Forward-Curved Fans have 400,000 hour Average life
• Standard low-leak dampers in mixing box sections
seal tightly
• All 39NC’s coils have Carrier’s high performance
coil surface
• Commercial Product Guide • 2002 •
167
Performance & Sizing Information
UNIT
NOMINAL
CAPACITY*
39NC07
39NC09
39NC11
39NC13
39NC17
39NC21
39NC26
39NC32
39NC39
39NC49
39NC61
39NC74
39NC92
DIMENSIONS (in.)
A
B
CFM
3,500
4,500
5,500
6,500
8,500
10,500
13,000
WIDTH
54
58
66
73
77
81
89
HEIGHT
44
48
48
52
56
64
68
15,000
19,500
24,500
30,500
37,000
46,000
94
101
113
125
141
141
68
72
80
88
92
108
NOTE: Airway length is variable upon different component arrangements.
Check the product catalog for individual airway length of components.
* Capacity is based upon 500ft/m face velocity.
B
A
Rated in
accordance with
ARI Standard
410 & 430
168
• Commercial Product Guide • 2002 •
48/50HJ + 62AQ
Commercial Products
High End RTU+ Energy$Recycler
Factory Installed
For 3 to 12 1/2 Ton Rooftops
600 to 3000 Nominal CFM
Thermidistat Controller
Features
• Warranty-Limited 5 Year Compressor, 1 Year entire unit
• Multi-speed centrifugal fans
• Proven heat pump technology
• Smooth, quiet rotary compressors
• Sloped non-corrosive condensate pans
• Also retrofits to older 48/50 series rooftops
• Energy$Recycler Control
- 7-day programmable
- Occupied/Unoccupied modes
- Built-in Humidistat
- Hold function
- Holiday mode
- Keypad lock
• UL and UL, Canada Listed
• Units need no addtional field wiring for Energy$Recycler
accessory; all units built with Energy$Recycler molex
connector as standard
• Smart technology – does exactly what you want it to
• Requires less chemical cleaning than energy recovery wheel
• Economizer-like functionality
• Additional step of heating and cooling – great part
load capability
• Energy$Recycler can operate by itself prior to unit
turning on – controlled through rooftop
• Available in sizes:
- 600 CFM
- 1000 CFM
- 2000 CFM
- 3000 CFM
FIOP Benefits
Benefits
• The Energy$Recycler provided to support ASHRAE 62-99
and ASHRAE 90.1-2002 required ventilation levels while
preconditioning outdoor air saving energy costs by reducing
heating, cooling and dehumidification demands by up to
80%. This lightens the load for the rooftop unit allowing you
to downsize the tonnage needed for a total system cost
advantage
• Energy$Recycler is designed to physically match the base
unit so no additional roof curb or modified stands are
necessary
• Set up for single point electrical connection
• RTU available with integral non-fused disconnect standard
(limited to 80A D/C maximum)
• All internal power wiring, control wiring and condensate
piping complete
• Factory run tested
• Eliminate field labor
• Eliminates field coordination of separate components
• Commercial Product Guide • 2002 •
169
Performance & Sizing Information
The Energy$Recycler can be used with or without a MoistureMi$er™ rooftop unit depending on the amount of required latent
RTU
MODEL NO.
UNIT SIZE
62AQ
48/50HJ004-007
ACCESSORY FAN KIT
PART NUMBER
V-PH (60 HZ)
060
208/230-1
CRFANKIT001A00
100
208/230-1
CRFANKIT002A00
208/230-1
CRFANKIT003A00
200
208/230-3
CRFANKIT003A00
48/50HJ008-014
300
460-3
CRFANKIT004A00
208/230-3
CRFANKIT005A00
460-3
CRFANKIT006A00
NOTE:
1. For 48/50HJ + 62AQ. FIOP use ECAT for combined electrical requirements.
2. Use ECAT for combined performance rating of 48/50HJ004-014 RTU and respective 62AQ060-300 FIOP.
Energy$Recycler Airflow Diagram
ROOFTOP UNIT W/OPTIONAL MOISTUREMI$ER DEHUMIFICATION COIL
AND
OPTIONAL PREMIERLINK DDC CONTROL
SUPPLY
PLINK
13 TC 9.8 LATENT
450 CFM
FRESH AIR
95DB/75WB
EV
AP
O
R
AT
O
R
7WB
SUPPLY AIR
B
7W
B/6
80D
EXHAUST
HUMIDISTAT
170
73DB/67WB
80DB/6
COMPRESSOR
450 CFM
EXHAUST AIR
CONDENSER
ACCESSORY
ENTHALPY
CONTROL
SUB-COOLER COIL
600CFM
ENERGY RECYCLER
COMBOROOM SENSOR
CO2 SENSOR
• Commercial Product Guide • 2002 •
ROOF LINE
62AA, 62AB, 62AC
Commercial Products
Heat Recovery Ventilators & Energy
Recovery Ventilators
300 to 3800 Nominal CFM
Heat Recovery Ventilators (HRV)- Recover sensible
energy from the building exhaust air and preheat the
incoming outdoor supply air in winter; reject unwanted
sensible energy from the building outdoor supply air and
transfer it to exhaust air in summer.
Energy Recovery Ventilators (ERV)- Recover sensible
and latent energy from the building exhaust air and
preheat and humidify the incoming outdoor supply air in
winter; pre-cool and dehumidify outdoor supply air and
reject it to exhaust air in summer.
Features
• Allows a reduction in total installed heating and cooling
equipment
• Meets requirements of ASHRAE STD. 62 ventilation
codes with reduced impact on energy consumption
• Models for sensible only and sensible and latent heat
recovery, with models for indoor, outdoor free-standing
and outdoor coupled to packaged units
• May be controlled to operate with CO2 sensors for
energy efficient demand control ventilation
ERV
• Painted cabinets meet 500-hour salt spray requirements
• Molecular sieve desiccant heat recovery wheel
• Wheel complies with NFPA 90A requirements
• Free cooling operation without wheel rotation
• Energy saving recirculation defrost for defrost control
• Cleanable interior surfaces for IAQ
HRV
• Painted cabinet
• Corrosion resistant aluminum core
• Less than 1% cross-leakage
• Meets requirements of NFPA 90A
• Defrost and non-defrost models available
• Commercial Product Guide • 2002 •
171
Performance & Sizing Information
CFM
RANGE
VOLTAGE
HP
EFF
WEIGHT
(lbs.)
640
330-750
115-1-60
1/4 DIRECT
79.5
228
1270
600-1270
115-1-60
1/3 DIRECT
79.5
266
2200
1000-2400
280/230-1-60
1 1/2 BELT
79.5
750
2200
1000-2400
208/230&460-3-60
1 1/2 BELT
79.5
400-700
115-1-60
1/3 DIRECT
700-1450
208/230-1-60
1/2 DIRECT
700-1450
208/230&460-3-60
800-2000
208/230-1-60
1500
800-2000
2000
1200-2800
ERV-INDOOR
2000
62AB300
ERV-INDOOR
62AB300
ERV-INDOOR
WIDTH
(in.)
HEIGHT
(in.)
36
28
25.5
53.45
42.9
22
91
48
30
750
91
48
30
72.7
215
56
23
23
74.7
525
71
42.5
22
1/2 DIRECT
74.7
525
71
42.5
22
3/4 BELT
70.7
600
53.45
42.9
45.15
208/230&460-3-60
3/4 BELT
70.7
600
53.45
42.9
45.15
208/230-1-60
1 1/2 BELT
71.4
725
91
48.5
30
1200-2800
208/230&460-3-60
1 1/2 BELT
71.4
725
91
48.5
30
3000
1800-3800
208/230-1-60
2 BELT
72.3
1185
88.6
49.8
55.4
3000
1800-3800
208/230&460-3-60
2 BELT
72.3
1185
88.6
49.8
55.4
62AC035 ERV-OUTDOOR
350
300-400
115-1-60
1/4 DIRECT
72.4
215
68
23
27
62AC075 ERV-OUTDOOR
750
700-900
115-1-60
1/3 DIRECT
72.7
525
71
42.5
22
62AC150 ERV-OUTDOOR
1500
800-2000
208/230-1-60
3/4 BELT
70.7
600
53.45
42.9
45.15
62AC150 ERV-OUTDOOR
1500
800-2000
208/230&460-3-60
3/4 BELT
70.7
600
53.45
42.9
45.15
62AC200 ERV-OUTDOOR
2000
1200-2800
208/230-1-60
1 1/2 BELT
71.4
875
91
48.5
30
62AC200 ERV-OUTDOOR
2000
1200-2800
208/230&460-3-60
1 1/2 BELT
71.4
875
91
48.5
30
62AC300 ERV-OUTDOOR
3000
1800-3800
208/230-1-60
2 BELT
72.3
1185
88.6
49.8
55.4
62AC300 ERV-OUTDOOR
3000
1800-3800
208/230& 460-3-60
2 BELT
72.3
1185
88.6
49.8
55.4
MODEL
TYPE
62AA064
HRV-INDOOR
62AA127
HRV-INDOOR
62AA220
HRV-INDOOR
62AA220
HRV-INDOOR
62AB050
ERV-INDOOR
500
62AB100
ERV-INDOOR
1000
62AB100
ERV-INDOOR
1000
62AB150
ERV-INDOOR
1500
62AB150
ERV-INDOOR
62AB200
ERV-INDOOR
62AB200
172
CFM
• Commercial Product Guide • 2002 •
LENGTH
(in.)
Commercial Products
AIR TERMINAL PRODUCTS
35E Single Duct VAV Terminals
45J,K,L Series
Fan Powered Terminals
• 200-7100 CFM
• Control Variations Pneumatic, Analog, Carrier VVT®/CCN
or Field Supplied/Factory Installed
• Hot Water or Electric Heat Option
• Large Zone Cooling and Heating Applications
35J Single Duct VAV Terminals
• 500-3300 CFM
• Control Variations: Pneumatic, Analog, Carrier VVT/CCN,
or Field Supplied/Factory Installed
• Hot Water or Electric Heat
• Constant Volume Cooling or Heating for Applications
Requiring Continuous Air Circulation
45M,N,P Parallel
Fan Powered Box
• 200-3700 CFM
• Control Variations Pneumatic, Analog, Carrier VVT/CCN
or Field Supplied/Factory Installed
• Round single duct VAV provides cooling only to meet
retrofit and special application needs
• 500-3700 CFM Primary Cooling; 400-2200 CFM Fan Heating
• Control Variations: Pneumatic, Analog, Carrier VVT/CCN
or Field Supplied/Factory Installed
• Hot Water or Electric Heat
• VAV Cooling Combined with Constant Volume Heating
for Exterior Zone Heating or Cooling Applications
35L,M,N Dual Duct VAV Terminals
35K Bypass Terminal
• 200-7100 CFM
• Control Variations Pneumatic, Analog, Carrier CCN
or Field Supplied/Factory Installed
• Zone control by varying the air volume supplied by a
hot or cold supply duct
• 45 to 4400 CFM
• Control Variations: Pneumatic, VVT (pressure dependent
only), Electric Actuator only
• Designed to operate with low-pressure Constant Volume
Systems
• Commercial Product Guide • 2002 •
173
Performance & Sizing Information
SINGLE DUCT VAV
MODEL
All with Option for Hot
Water or Electric Heat
CONTROL
35EA
Analog
35EC
35EV
35EP
35EN
CCN – Carrier Comfort Network
Carrier VVT – Variable Vol/Variable Temp
Pneumatic
No Controls or For Field Supplied Controls
FAN POWERED TERMINALS
All with Option for Hot Water
or Electric Heat
NOMINAL SIZE
200-7100 CFM
MODEL
NOMINAL CFM
45J * - SERIES - CONSTANT AIRFLOW COOLING OR HEATING
500 - 3300
45K* - SERIES - QUIET BOX
45L* - SERIES - LOW PROFILE
45M* - PARALLEL - INTERMITTENT AIRFLOW COOLING OR HEATING
45N* - PARALLEL QUIET PROFILE
45P* - PARALLEL LOW PROFILE
500 - 2850
850 - 1750
500 - 3700
500 - 3700
500 - 1800
* Control Designation
A = Analog
C = CCN - Carrier Comfort Network
V = VVT - Variable Volume/Variable Temp
P = Pneumatic
N = No Control or Field Supplied Control
DUAL DUCT CFM RANGE DISCHARGE AIRFLOW BLENDING
Application where blending of
35L*
200-7100
hot and cold air is not required
Integral attenuator and mixing baffle
35M*
200-3700
to maintain discharge temperature
Integral attenuator and blending
35N*
200-3700
chamber for precise control of
discharge temperature
*Control designations A, C, P, N – see above
MODEL
35JA
35JC
35JV
35JP
35JN
MODEL
35KP
35KV
35KN
CONTROL
CFM RANGE
Analog
CCN – Carrier Comfort Control
Carrier VVT – Variable Volume,
200-3700
Variable Temperature
Pneumatic
No Controls or Field Supplied
CONTROL
Pneumatic
Carrier VVT,
Pressure Dependent Only
No Controls or Field Supplied
CFM RANGE
45-4400
(60 Hz Only)
174
• Commercial Product Guide • 2002 •
Commercial Products
AIR TERMINAL PRODUCTS cont'd
35BD Boot Diffusers
• 100-500 CFM
• Linear Slot Diffusers Std 2, 4, or 5 ft Lengths
• Flat T-Bar, Tegular or Special Ceilings
• One or Two Way Blow Configuration
• Zone Air Distribution for Cooling, Heating or
Cooling/Heating Applications
36R,S,T Induction Unit
• 20-130 CFM Primary Air
• 2 or 4 Pipe Systems
• Horizontal, Vertical or Lo-boy Configurations
• Temp Control by Water Valve or Bypass Damper
• Heating/Cooling Perimeter Zone Applications
37H Integral Diffuser
VAV Unit
• 100, 200, 400 CFM
• Linear 2, 4, or 5 ft Lengths
• T-Bar, Tegular or Special Ceilings
• One or Two Way Blow Configuration
• System Powered Controls
• Small Zone Cooling Applications
• Commercial Product Guide • 2002 •
175
Performance & Sizing Information
BOOT DIFFUSERS
MODEL - 35BD
Nominal 2,4, or 5 ft
Diffuser Length
AG/CM 1 and 2 Way
CN 1 and 2 Way
DG/DM 2 and 3 Slot
DN 2 and 3 Slot
HS 1 Slot
INTEGRAL DIFFUSERS
VAV UNIT
Nominal 2, 4, or 5 ft
Diffuser Lengths
TYPE
NOMINAL CFM
200-400
500
200-400
500
100
Cooling
Cooling/Heating
Heating
MODEL
TYPE
NOMINAL CFM
37HS1
2 Slot 2 Way
or
2 Slot 1 Way
or
3 Slot Heating/Cooling
100
37HS2
37HS4
INDUCTION AIR
TERMINALS
MODEL
Vertical/Horizontal
Configurations
36RV, RH
36SL, SC, ST, SV, SH
36SD, SP SM, SJ
36TE
CONTROL
Bypass Damper
Water Control
Water Control
Bypass Damper
200
400
SYSTEM
2 Pipe
2 Pipe
4 Pipe
2 Pipe Electric Heat
(60 Hz Only)
176
• Commercial Product Guide • 2002 •
40UV, UH
Commercial Products
Unit Ventilator
Vertical 500 to 1500 Nominal CFM
Horizontal 750 to 2000 Nominal CFM
Features
• Design flexibility for vertical/horizontal cabinet or
horizontal furred-in applications
• Control capability for 2/3 way valve water control or face
and bypass damper
• 2 Pipe, 4 Pipe Systems with Chilled Water or DX Cooling,
Hot Water, Steam or Electric Resistance Heating
• Control Options to meet ASHRAE Cycles I, II, or III that
provide Heating, Heating and Ventilating, Economizer
Cooling with up to 100% Outside Air
• IAQ Demand-Control Ventilation with CO2 sensors
• Building integration with Carrier Comfort Controllers and
linkage to Carrier’s Comfort Network (CCN) or with
compatibility for a range of other customer supplied controls
• Rugged 12 gauge frame provides strength and support for
16 gauge cabinet painted with a durable textured powder
coat finish
• Commercial Product Guide • 2002 •
177
Performance & Sizing Information
VERTICAL 40UV MODEL SIZES
HORIZONTAL 40UH MODEL SIZES
NOMINAL CFM
SHIPPING WEIGHT
(Aprox lbs)
16 5/8" Deep Unit
21 7/8" Deep Unit
Horizontal Unit
*DIMENSIONS (inches)
Length
Width
Horizontal
Height
Length
Height
Width
1/050
500
2/075
2/075
750
3/100
3/100
1000
4/125
4/125
1250
5/150
5/150
1500
6/200
2000
325
345
-
350
370
385
425
445
465
495
525
540
570
600
620
680
52
16 5/8
21 7/8
30
-
64
16 5/8
21 7/8
30
64
16 5/8
30
76
16 5/8
21 7/8
30
76
16 5/8
30
88
16 5/8
21 7/8
30
88
16 5/8
30
100
16 5/8
21 7/8
30
100
16 5/8
30
100
16 5/8
30
* Dimensions shown are nominal, dimensions can vary with unit configuration.
(60 Hz Only)
178
• Commercial Product Guide • 2002 •
42V,C,D,BH,S
Commercial Products
Fan Coil Systems
Features and Benefits: Complete Model Offering to
Meet Any Fan Coil System Needs.
42V Vertical 200-1200 CFM
42DD Ducted 600-2000 CFM
• Furred-in, Painted Cabinet, Slope Top,
and Lo-boy Models
• Vertical Design for Against a Wall or
Under Window Application
• Vertical Galvanized Casing with
Top Discharge
• Commonly for Installation in Closets
42C Horizontal 200-1200 CFM
42BH Belt Drive 800-4000 CFM
• Furred-in, Painted Cabinet, or Telescoping Bottom
Panel Models
• Horizontal Design for Above a Ceiling or
Doorway Application
• Up to 2" Static Capability
• Galvanized Casing For Furred-in Applications
Requiring Higher CFM’s and Static
42D Ducted 600-2000 CFM
42S Stack 300-1200 CFM
• Higher Static Capability to 0.5"
• Horizontal Furred-in or Cabinet Models for
Higher Capacity Applications
• Furred-in, Painted Cabinet, and
Back-to-Back Models
• Vertical Design Includes Risers for
Simple System Installation in
Hi-Rise Applications
• Commercial Product Guide • 2002 •
179
Performance & Sizing Information
Options
• 2-Pipe or 4-Pipe System Combinations
2, 3, 4 Row Chilled Water/DX Cooling
1 or 2 Row Hot Water/Steam Heating
Total or Auxiliary Electric Heat
• Motors 120, 208, 230, 277/1/60, or 220/1/50
• Throwaway or Permanent Filters
• Factory supplied valve and thermostat packages for
- Non-programmable 24 V (non-communicating) control
(see below)
- Programmable 24 V (non-communicating) control
(see below)
- Integrated CCN communicating control
(see page 203 for data sheet)
• Numerous accessory options and grilles, camlocks, outside
air dampers, drain pans, cabinet modifications
SELECTION
VERTICAL ROOM FAN COILS
CFM RANGE
42VB Cabinet - Painted
42VA Furred-In - Galvanized Casing
42VF Slant-Top Cabinet - Painted
42VE Lo-boy Cabinet - Painted
42VC Furred-In Lo-boy - Galvanized Casing
42VG Furred-In Wall - Painted Panel
STACK FAN COILS
200-1200
200-1200
200-1200
200-600
200-600
150-300
42SG Furred-In w/ Galvanized Casing
42SH Cabinet - Painted
42SJ Back-to-Back (42SG)*
HORIZONTAL ROOM FAN COILS
300-1200
300-1200
300-1200 ea.
42CA Furred-In - Galvanized Casing
42CE Furred-In Galvanized Casing w/Plenum
42CG Cabinet - Painted
42CK Telescoping Cabinet - Bottom Panel
Painted
42CF Furred-In High Static - Galvanized Casing
SYSTEM FAN COIL
200-1200
200-1200
200-1200
200-1200
400-1000
42BH Ceiling Mounted, Belt-Drive - Galvanized
Casing
DUCTED FAN COILS
800-4000
42DA Furred-In Ceiling - Galvanized Casing
42DC Furred-In Ceiling - Galvanized Casing w/Plenum
42DE Furred-In w/Full Galvanized Casing
42DF Cabinet Ceiling - Painted
42DD Vertical w/Galvanized Cabinet
600-2000
600-2000
600-2000
600-2000
600-2000
*Use common risers for each section
COOL
BACK LIT
LIQUID
CRYSTAL
DISPLAY
MODE
BUTTON
AUTO
HEAT
FAN
BUTTON
HEAT/COOL INDICATOR
RED = HEAT
GREEN = COOL
UP AND DOWN
ARROW BUTTONS
24 V Fan Coil Thermostats
Non-Programmable – 33CSSN2-FC
Programmable – 7 Day – 33CSSP2-FC
• Digital thermostat configurable for 2 or 4 pipe systems
• Dynamic or manual fan speed control
• Dual set point or single set point, Farenheit or Celsius
• Locking cover furnished with thermostat
• On board dry contact closure available to force thermostat
into occupied/unoccupied operation
• Large Thermoglow™ display
• NeverLost™ non-volatile memory (no batteries required)
• Maintains temperature within 1° of set point
• Accessory backplate to mount over 2x4 or 4x4 box
• Heating or cooling operation indicator light
(60 Hz Only)
180
• Commercial Product Guide • 2002 •
Commercial Products
33CN Carrier Comfort Network
Wireless Transceiver
Comfort System Components
The Carrier wireless transceivers enable connection to the Carrier Comfort
Network (CCN) in areas where standard wiring cannot be used. The
wireless transceiver can be plugged into any standard serial port (RS232
or RS485) on a wide variety of devices to provide CCN communications.
(Not recommended for use on sites with secondary buses.)
Features
The wireless transceiver offers the following advantages:
• Cost reduction of CCN installations
• Wireless extension of the CCN bus inside or outside
of buildings
• Use of ComfortVIEW™ and Service Pack on a mobile computer
which can be taken anywhere in the building
• Data is transmitted reliably and securely with wireless
communications which enable user-interface mobility
• Ideal for transmissions over long distances: up to 1500 ft indoors
and line-of-sight to the horizon outdoors
• Communicates with CCN at speeds up to 9600 bps
• Operates in the license-free portion of the FCC designated ISM
(industrial, scientific, and medical) frequency band at 2.4 GHz.
Two wireless transceiver kits are available from Carrier. The
33CNWIRMOD kit contains the following: 2 wireless transceivers,
2 power supplies, 2 RS232 to RS485 converters, 2 RS232 cables,
Carrier Wireless Transceiver Configuration Manager, 2 antennas,
and a loopback connector.
The 33CNSNGMOD kit contains the following: wireless
transceiver, power supply, RS232 to RS485 converter, RS232
cable, and an antenna.
In order to communicate outdoors between structures, additional
outdoor antennas (part number 33CNOAANT1) for each device
are required.
The wireless transceiver can be used for: a wireless extension of
the CCN primary bus within a building or to a remote building,
communication between multiple remote buildings, wireless Service
Tool usage for technicians, or moving the CCN computer within a
building. The Carrier wireless transceivers are not recommended for
use on sites with secondary buses.
Specifications
Frequency
2.400 to 2.4835 GHz license-free ISM band in U.S.A. (may vary
in other countries)
Radio type
Frequency hopping spread spectrum
Channels
417 independent, non-interfering frequencies
Data transfer rate
600 bps to 9.6 kbps full duplex
Indoor range
Up to 1500 ft in normal construction
Outdoor range
Up to 2 miles with omni-directional antenna
Up to 12 miles with directional antenna (line-of-sight)
(supplied separately)
Protocol
CSMA (Carrier Sense Multiple Access)
Flow control
Supports hardware, software, or none
Error detection and correction
CRC 16 error detection. Forward error correction can correct errors
in 1 out of every 4 bits transmitted
Warranty
1 year parts and labor
Certifications
FCC Part 15 Certified, Industry Canada, Japan, Europe (ETSI),
and Brazil
Electrical interface
RS-232C voltage levels
Input power
Shipped with a 115 VAC power adapter providing between 6.5 and
9.0 V and a ripple of less than 250 mV (RMS) from DC to 1 MHz
Input current draw
Idle: 200 mA
Transmit: 550 mA instantaneous current
Transmit/Receive: 360 mA (time averaged over 100 msec)
Transmit power output
• Commercial Product Guide • 2002 •
181
Commercial Products
CCN-to-Ethernet Converter
• Bridge – Acts as a CCN/Ethernet interface device in
applications where the Ethernet is being used to connect
separate CCN Buses. This application requires an additional
Converter functioning as a Gateway.
In this application each converter occupies a unique bus and
element address on the CCN. When configured as a bridge, it
is addressed similarly to other CCN Bridges where the system
element number on the primary bus identifies the secondary
bus number.
Each Converter also has an Internet Protocol (IP) address,
which can easily be set using a CCN Network Service Tool, or
a tool such as Microsoft® Windows® HyperTerminal using an
RS-232 null modem connection. In the bridge configuration the
Converter supports either static or dynamic (DHCP) IP
addressing (dynamic addressing requires a DHCP-ready
Ethernet server.) In the gateway configuration the Ethernet
address must be static.
Comfort System Components
The CCN-to-Ethernet Converter is a device designed to enable
connection of a CCN to an Ethernet-based Local Area Network
(LAN). In addition, it can be used in a bridge function to
interface CCN Communication Buses in order to extend a CCN
within a campus or building. Because it enables use of existing
LAN wiring, it is an ideal solution for integrating CCN into
almost any building or facility.
Physically, the CCN-to-Ethernet Converter consists of a
compact desktop unit equipped with specialized hardware and
software. It also can be wall-mounted using the detachable
mounting plate that is included as standard equipment along
with the unit.
The Converter connects to the CCN Bus through a removable
3-position connector and to a building’s Ethernet LAN through
a 10Base-T connector. It functions by encapsulating CCN
protocol messages into Ethernet packets for transmission to the
LAN, and by extracting CCN protocol messages out of Ethernet
packets received from the LAN. User Datagram Protocol/
Internet Protocol (UDP/IP) is used for Ethernet communication.
Functions
The Converter functions in one of the following two capacities,
depending on configuration:
• Gateway – Provides access to the CCN Bus from a
ComfortWORKS® or ComfortVIEW™ server that is residing
on the Ethernet. The converter is serving as the access node
from the Ethernet to the CCN and is responsible for
maintaining a routing table of CCN system elements.
In this application the Converter is connected directly to the
CCN's primary bus (Bus 0) and, like other CCN system
elements, occupies a unique address on the CCN (Bus 0,
Element 1-239.)
Specifications
Power Requirements
15 VA @ 24 Vac + 15%
Storage Temp
-40° F to 185° F (-40° C to 85° C)
Operating Temp
32° F to 140° F (0° C to 60° C)
Operating Humidity
0% to 95% RH, noncondensing
Storage Humidity
0% to 95% RH, noncondensing
Dimensions (LxWxD)
7.19" x 5.56" x 1.56" (18.26 x 14.12 x 3.96 cm)
Communication Ports
CCN Service Tool: RJ-11, RS-485
COM 1 (CCN): 3-position removable, RS-485
COM 2 (IP Configuration): 3-position removable, RS-485,
9 pin D, RS-574 (RS-232)
LAN: RJ45 10Base-T
Conforms to guidelines for radiated and conducted emissions
for a Class A device as stated in FCC Rules and Regulations
Part 15, Subpart J and Part 68.
UL 1949/1950 ULC, and CE mark (Light Industrial) listed.
UL 1949/1950, ULC, and CE MARK (Light Industrial) listed.
Typical Application
ComfortWorks
Ethernet
0,12
Gateway
0,7
0,1
Bridge
Bridge
0,18
Bridge
CCN Bridge
Bus 0
Bus 1
0,6
Bus 6
182
• Commercial Product Guide • 2002 •
Bus 7
Bus 18
Commercial Products
33CS
Debonair® Commercial Programmable Thermostats
Flatstat
2 3/4”
2 3/4”
1 1/4”
1 1/4”
4 1/4”
4 1/4”
3/8”
5/16”
The Debonair line of commercial, 7-day programmable
thermostats provides the following features and benefits:
• Compatible with electric heat, gas heat, and
heat pump operation
• Seven-day programmable clock with 4 time
periods per day
• Holiday scheduling (up to 99 consecutive days)
• Copy command for programming schedules
• Large Thermoglow™ display
• Heating and cooling operation LED
• Zone temperature control to 1° accuracy
• Auto-changeover
• 4-hour setback override
• Neverlost™ non-volatile memory (no batteries required)
• Service filter indicator
• Energy saving Smart Fan
• Three security levels with keypad lockout and
ExactFit locking cover
• Five-minute compressor time guard
• Adjustable heat/cool set point limiting
• External input (dry contact switch)*
• Soft start/staggered start*
• Pre-occupancy purge (0 to 3 hours)*
• Remote room temperature sensor capability*
• Title 24 compliance
• Carrier warranty
• Calibration of internal temperature sensor
Specifications
Recommended Wiring
22 AWG (36 ft max)
18 AWG (100 ft max)
Operating Temperature
32° F to 122° F (0° C to 50° C)
Storage Temperature
14° F to 40° F (-10° C to 60° C)
Temperature Display Range
32° F to 99° F (0° C to 38° C)
Operating Relative Humidity
0 to 95%, non-condensing
Dimensions (LxWxD):
4.25" x 2.75" x 1.25"
Power
5VA at 24VAC 60 Hz
Product Standards
FCC Part 15, UL, UL Canada, Title 24, CE Mark
NOTE: This control is considered a low voltage device by
UL (Underwriters Laboratories) and therefore does not require
UL or CSA (Canadian Standards Associate) approval.
* 33CS 250-FS only
• Commercial Product Guide • 2002 •
183
184
• Commercial Product Guide • 2002 •
33CS Debonair®
Commercial Products
Commercial Non-Programmable Thermostat
and 5-1-1 Programmable
R
COOL
COOL
AUTO
AUTO
HEAT
The Debonair commercial non-programmable
thermostat (33CSSN2-WC) provides the following
features and benefits:
• Compatible with electric heat, gas heat, and heat
pump operation
• Common wire not required for operation with
gas or electric heating systems
• Large Thermoglow™ display
• Heating and cooling operation indicator light
• Zone temperature control to 1˚ accuracy
• Auto-changeover
• Neverlost™ non-volatile memory (no batteries required)
• Five-minute compressor time guard
• Adjustable dead band
• Dual heating and cooling set points
• Celsius or Fahrenheit display
• ExactFit locking cover (tamper-proof screws
with keyed access)
• Accessory backplates
• Carrier warranty
NOTE: 33CSSP2-WC offers:
• 5+1+1 Programming
• M-F Schedule
• Sat. Schedule
• Sun. Schedule
HEAT
an HVAC (Heating, Ventilation, and Air Conditioning)
system. Separate heating and cooling set points and autochangeover are standard features.
The thermostat can be set to accept several different
equipment configurations, including single-stage heating and
cooling, 2 stages of heating and cooling, heat pumps, gas or
electric heating, and hydronic systems.
Batteries are not required. During power interruption, the
internal memory stores settings for an unlimited time.
Flexibility for every application
Thermostat can be configured for use with many different
applications including single-stage heating and cooling,
2 stages of heating and cooling, heat pumps, gas or electric
heating, and hydronic systems.
Thermoglow™ display is large and easy to read
A single adjustment shows temperature in Celsius
or Fahrenheit.
Reliability for year-round comfort
One degree control accuracy precisely controls the desired
space temperature to within 1 degree of user set point. The
thermostat uses a solid-state, laser-trimmed sensor.
Neverlost™ memory protection on the thermostat eliminates
the need to reconfigure the thermostat after power outages.
Comfort configuration will remain intact indefinitely.
Features
Carrier’s Debonair commercial non-programmable
thermostat is a wall-mounted, low-voltage thermostat that
maintains room temperature by controlling operation of
Five-minute compressor time guard protects HVAC
equipment by preventing compressor short cycling and
limiting the number of cycles per hour with and adjustable
cycle limit.
• Commercial Product Guide • 2002 •
185
Performance & Sizing Information
The Debonair commercial non-programmable
thermostat (33CSSN2-WC) provides the following
features and benefits:
• Compatible with electric heat, gas heat, and heat
pump operation
• Common wire not required for operation with
gas or electric heating systems
• Large Thermoglow™ display
• Heating and cooling operation indicator light
• Zone temperature control to 1˚ accuracy
• Auto-changeover
• Neverlost™ non-volatile memory (no batteries required)
• Five-minute compressor time guard
186
• Adjustable dead band
• Dual heating and cooling set points
• Celsius or Fahrenheit display
• ExactFit locking cover (tamper-proof screws
with keyed access)
• Accessory backplates
• Carrier warranty
NOTE: 33CSSP2-WC offers:
• 5+1+1 Programming
• M-F Schedule
• Sat. Schedule
• Sun. Schedule
• Commercial Product Guide • 2002 •
Commercial Products
Debonair® Commercial
Non-Programmable Thermostat
Comfort System Components
Carrier’s Debonair line of commercial, non-programmable
thermostats are wall-mounted, low-voltage thermostats,
which maintain room temperature by controlling the
operation of an HVAC system.
This thermostat is not Carrier Comfort Network
(CCN) Compatible.
Features
• One-for-all control Physical Characteristics
Electrical Characteristics
• Large Thermoglow™ display
• Red/green LED
• 1° control accuracy
• Neverlost™ memory, no batteries required
• Service filter indicator
• Energy saving Smart Fan
• 3 security levels with keypad lockout
• 5 minute compressor timeguard
• Adjustable heat/cool setpoint limiting
• External input
• Soft start
• Remote room sensing
• Carrier warranty
Specifications
Physical Characteristics
Dimensions (LxWxD):
4.8" x 4.3" x 1.1"
Appearance:
White Plastic, Textured Cover
Weight:
1 lb.
Power Requirements
5VA @ 24VAC 60 Hz
No Batteries Required
Environmental Requirements
Temperature:
Operating: 41° F to 104° F (5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity: 0 to 95% Relative Humidity, non-condensing
Agency Approvals
FCC Part 15; UL; UL, Canada; CE
Electrical Characteristics
Input: 24VAC
Outputs:
Minimum Load = 1,000 ohms
Maximum Load = 1.5 Amps, 50% pf Inductive
Nominal Load Capacity = 1.5 Amps
Wiring Requirements
Wire Size vs. Run Length
22 AWG 36 ft; 18 AWG 100 ft
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference that may
cause undesirable operation.
• Commercial Product Guide • 2002 •
187
Commercial Products
Debonair® Commercial
Programmable Thermostat
Comfort System Components
Carrier’s Debonair line of commercial, programmable
thermostats are wall-mounted, low-voltage thermostats,
which maintain room temperature by controlling the operation
of an HVAC system. Separate heating and cooling setpoints and
auto-changeover capability allow occupied and unoccupied
programming for energy savings.
All thermostats can be configured for single stage
heating/cooling, 2 stage heat/cool, gas/electric, heat pump
or hydronic systems – all from one thermostat – and allow up
to 4 time/temperature settings to be programmed per 24-hour
period. Each thermostat stores schedules for 7 independent
days. Batteries are not required. During power interruption, the
internal memory stores schedules for an unlimited time while
the clock continues to run for at least 48 hours.
This thermostat is not Carrier Comfort Network
(CCN) compatible.
Features
• One-for-all control
• 7-day programmable clock with 4 time periods/day
• Holiday programming (up to 99 consecutive days)
• Copy command
• Large Thermoglow™ display
• Auto-changeover
• 4 hour setback override
• Neverlost™ memory, no batteries required
• Energy saving Smart Fan
• 3 security levels with keypad lockout
• Adjustable heat/cool setpoint limiting
The 250-01 offers these additional features:
• External input
• Soft start/staggered start
• Pre-occupancy purge (0-3 hrs.)
• Remote room sensing
188
Specifications
Physical Characteristics:
Dimensions (LxWxD): 4.8" x 4.3" x 1.1"
Appearance: White Plastic, Textured Cover
Weight: 1 lb.
Power Requirements
5VA @ 24VAC 60 Hz
No Batteries Required
Environmental Requirements
Temperature:
Operating: 41° F to 104° F (5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity: 0% to 95% Relative Humidity, non-condensing
Agency Approvals
FCC Part 15; UL; UL, Canada; CE
Electrical Characteristics
Input: 24VAC
Outputs:
Minimum Load 1,000 ohms
Maximum Load 1.5 Amps, 50% pf Inductive
Nominal Load Capacity: 1.5 Amps
Wiring Requirements
Wire Size vs. Run Length
22 AWG 36 ft; 18 AWG 100 ft
This device complies with Part 15 of the FCC rules. Operation
is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference that may cause
undesirable operation.
• Commercial Product Guide • 2002 •
Commercial Products
Debonair® Commercial
Programmable Light-Activated Thermostat
Comfort System Components
Carrier’s Debonair line of commercial, programmable
thermostats are wall-mounted, low-voltage thermostats, which
maintain room temperature by controlling the operation of an
HVAC (Heating, Ventilation, and Air Conditioning) system.
Separate heating and cooling setpoints and auto-changeover
capability allow occupied and unoccupied programming for
energy savings.
All thermostats can be configured for single stage
heating/cooling, 2 stage heat/cool, gas/electric, heat pump or
hydronic systems – all from one thermostat – and allow up to 4
time/temperature settings to be programmed per 24-hour
period. Each thermostat stores schedules for 7 independent
days. Batteries are not required. During power interruption, the
internal memory stores schedules for an unlimited time while
the clock continues to run for at least 48 hours.
This thermostat is not Carrier Comfort Network
(CCN) Compatible.
Features
• One-for-all control
• 7-day programmable clock with 4 time periods/day
• Holiday programming (up to 99 consecutive days)
• Copy command
• Built-in light sensor
• Large Thermoglow™ display
• Auto-changeover
• 4-hour setback override
• Neverlost™ memory, no batteries required
• Energy saving Smart Fan
• 3 security levels with keypad lockout
• Adjustable heat/cool setpoint limiting
The 250-LA offers these additional features:
• External input
• Soft start/staggered start
• Pre-occupancy purge (0-3 hrs.)
• Remote room sensing
Specifications
Physical Characteristics:
Dimensions (LxWxD):
4.8" x 4.3" x 1.1"
Appearance:
White Plastic, Textured Cover
Weight:
1 lb.
Power Requirements
5VA @ 24VAC 60 Hz; No Batteries Required
Environmental Requirements
Temperature:
Operating: 41° F to 104° F (5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity: 0 to 95% Relative Humidity, non-condensing
Agency Approvals
FCC Part 15; UL; UL, Canada; CE
Electrical Characteristics
Input: 24VAC Outputs:
Minimum Load 1000 ohm
Maximum Load 1.5 Amps,
50% pf. Inductive
Nominal Load Capacity: 1.5 Amps
Wiring Requirements
Wire Size vs. Run length
22 AWG 36 ft; 18 AWG 100 ft
This device complies with Part 15 of the FCC rules. Operation
is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference that may cause
undesirable operation.
• Commercial Product Guide • 2002 •
189
Commercial Products
Carrier’s Debonair® Wireless
Remote Room Sensors
JP2
JP1
Temperature Transmission Interval Flexibility –
The Transmitting Remote Sensor transmits the temperature
to the Receiver in one of four selectable time intervals:
• Every 5 seconds for set-up/diagnosis
• Every 2 minutes for remote room sensing
when fast response is needed
• Every 5 minutes for remote room sensing
when fast response is not needed
• Every 10 minutes for outdoor temperature sensing
3
2
1
0
Carrier’s Debonair Wireless Remote Room Sensors
offer the following advantages:
• Up to 16 sensors can be used with one receiver
• Monitors indoor or outdoor temperature
• Sensor averaging
• Up to 64 sensors can be installed in close
proximity with no interference
• User controlled monitoring intervals promote
longer battery life.
• Override button for flexibility during after-hour usage
• Sensor location not restricted by wiring constraints
• Reliability for year-round comfort
• Attractive design
NOTE: The longer the interval, the longer the battery life.
Battery Life - Sensors can be set to different monitoring
intervals; a 5-minute interval results in two-year battery life; a
ten-minute interval results in longer battery life. Uses 2 AA
Lithium batteries.
No interference - Sensors and receivers can be configured for
up to 64 different identification codes allowing as many as 4
receivers and 64 sensors to operate in the same area without
causing interference.
Product Standards
• Conforms to Underwriters’ Laboratory, Class II
• Conforms to CE Mark Requirements for residential, light
commercial, commercial, and light industrial applications
• Conforms to FCC Part 15, Subject J, Class A
Specifications
Features
Mounting Flexibility – The wireless sensors are battery
operated and can be wall-mounted almost anywhere without
additional wiring installation.
Multiple Sensors Flexibility – Up to 16 sensors may be used
with one receiver. Multiple sensor temperatures are
automatically averaged by the receiver.
Flexibility After Hours – The override button allows override
programming for up to 4-hours in 2-hour increments when
systems is in use beyond normal programmed hours.
Recommended Wiring
Operating Temperature °F (°C)
41° F to 104° F (5° C to 40° C)
Operating Relative Humidity
0 - 95% Relative Humidity, non-condensing
Power
24VAC
Product Standards - This device complies with Part 15 of the
FCC rules and may be operated subject to the following
compliance conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received, including
interference that may cause undesirable operation.
FCC ID: MUHRSTX
190
• Commercial Product Guide • 2002 •
Commercial Products
Remote Temperature Sensor
with Override Button (Debonair®)
Comfort System Components
The Remote Temperature Sensor with Override Button,
designed for the Debonair thermostat (33CS071-01 and
33CS250-01), measures indoor air temperature at a location
separate from the thermostat. It is a three-wire, digital sensor.
The override button changes the thermostat from unoccupied
to occupied mode, for example, to provide after-hours heating
or cooling.
Features
• Three-wire
• Digital
• Override allows change to occupied mode with
the touch of a button
• Measures temperatures from 0° F to 150° F
Specifications
Dimensions (HxWxD):
1.75" x 1.37" x .62"
Wire
Three-wire
18-20 ga., thin wire or unshielded cable
Maximum distance between sensor and thermostat
18 ga. wire - 300 ft
20 ga. wire - 500 ft
Operating temperature/Relative humidity
41° F to 104° F/0 to 95%, non-condensing
Operating Characteristics
Remote Room Sensor:
Debonair 71 (33CS071-01)
Debonair 250 (33CS250-01)
• Commercial Product Guide • 2002 •
191
Commercial Products
Outdoor Air Sensor (Debonair®)
Comfort System Components
The Outdoor Air Sensor is an accessory for the Debonair 71
only. It allows the outdoor temperature to be displayed at
the thermostat.
Features
• Sends outdoor temperature readings to the thermostat
• Can also be used as remote room sensor without override
on Debonair 71 and Debonair 250
192
Specifications
Wire
18-20 ga., unshielded
Maximum distance between sensor and thermostat
18 ga. wire - 300 ft
20 ga. wire - 500 ft
Operating temperature/Relative humidity
41° F to 104° F/0 to 95%, non-condensing
For outdoor installation
Measures temperatures from 0° F to 160° F
Operating Characteristics
Outdoor Air Sensor:
Debonair 71 (33CS071-01)
Remote Room Sensor:
Debonair 71 (33CS071-01)
Debonair 250 (33CS250-01)
• Commercial Product Guide • 2002 •
Commercial Products
Remote Duct Temperature
Sensor (Debonair®)
1/8″
3/8″
24″ LEAD
The Remote Duct Sensor or supply air sensor is used in
applications where it is desirable to monitor supply air
temperature for optimized system operation. It can be used
on the VVT Monitor Thermostat, bypass controller or TEMP
Monitor Thermostat. It interfaces to the relay board of the
TEMP/VVT Monitor Thermostat.
Features
• 30° F to 180° F operating range, easy to install
Specifications
Physical Characteristics
Dimensions (LxW):
3/8" x 1/8" with 24" lead
Shipping Weight:
2 lbs.
Operating Range
30° F to 180° F
Maximum length from monitor
1,000 ft.
Wiring
2 Wire - 18 ga.
• Commercial Product Guide • 2002 •
193
Commercial Products
Debonair® Wireless
Commercial Thermostat
Comfort System Components
The Debonair wireless thermostat is a commercial,
programmable thermostat that is compatible with gas,
electric, heat pump and hydronic equipment including up to
2-stage heat/cool. It allows up to 4 time/temperature settings
per 24-hour period and stores schedules for 7 independent
days. Separate heating and cooling setpoints and
auto-changeover capability allow occupied and unoccupied
programming for energy savings.
This thermostat is not Carrier Comfort Network
(CCN) compatible.
Features
• Wireless operation
• Receiver controls up to 4 thermostat transmitters - last
thermostat touched is the master control
• Flexible installation location
• Transmits up to 500 feet through floors, walls, ceilings
• Soft start/staggered start
• Pre-occupancy purge (0-3 hrs.)
• One-for-all control
• 7 day programmable clock with 4 time periods/day
• Holiday programming
• Copy command
• Large, Thermoglow™ display
• Auto-changeover
• 4 hour setback override
• Neverlost™ memory, no batteries required
• Adjustable setpoint limiting
• Energy saving Smart Fan
• 3 security levels with keypad lockout
194
Specifications
Transmitter
Temperature:
Operating: 41° F to 104° F (-5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity:
0 to 95% Relative Humidity, non-condensing
Power Requirements:
2AA Lithium batteries
Transmits:
200', 418 MHz
Receiver
Temperature:
Operating: 41° F to 104° F (-5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity:
0 to 95% Relative humidity, non-condensing
Electrical Characteristics
Input: 24VAC
Outputs:
Minimum Load 1,000 ohms
Maximum Load 1.5 Amps, 50% pf Inductive
Nominal Load Capacity:
1.5 Amps
• Commercial Product Guide • 2002 •
Commercial Products
Commercial Programmable
Thermostat
Comfort System Components
Carrier’s 7-day Commercial Programmable Thermostats are
wall-mounted, low-voltage thermostats which maintain room
temperature by controlling operation of an HVAC (Heating,
Ventilation, and Air Conditioning) system. Separate heating
and cooling setpoints and auto-changeover capability allow
occupied and unoccupied programming for energy savings.
All thermostats allow up to 4 time/temperature settings to be
programmed per 24-hour period. Each thermostat stores
schedules for 7 independent days. Batteries are not required.
During power interruption, the internal memory stores comfort
schedules for an unlimited time while the clock continues to
run for at least 72-hours.
This thermostat is not Carrier Comfort Network (CCN)
compatible.
Features
• Remote sensing and averaging
• Keypad lockout security
• Four-period, 7-day programmable clock
• Auto-changeover
• Smart recovery (heating only)
• Non-volatile memory (no batteries necessary)
• Heat/cool lockout
Specifications
Physical Characteristics
Dimensions (LxWxD):
7 1/2" x 4 1/4" x 1 1/2"
Appearance:
Plastic Material; Taupe Color; Textured Cover
Weight:
Approx. 1 lb.
Power Requirement
5VA @ 24VAC 50/60 Hz
No Batteries Required
Environmental Requirements
Temperature:
Operating: 41° F to 104° F (-5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity: 0 to 95% Relative Humidity, non-condensing
Agency Approvals
FCC Part 15, Subpart J
Electrical Characteristics
Inputs: 24VAC
Outputs:
Minimum Load 1,000 ohms
Maximum Load 1.5A, 50% pf, Inductive
Nominal Load Capacity:
1.5 Amps
• Commercial Product Guide • 2002 •
195
Commercial Products
Remote Room Sensor
Comfort System Components
The Remote Room Sensor is used in applications where it is
desirable to monitor space temperature with the Carrier
Corporate Thermostat (33CSPTN-01) remotely located in a
panel or closet. The Remote Room Sensor interfaces to the
connector board of the thermostat. Room temperature can be
averaged using multiple Remote Room Sensors.
Features
• Easy to install
• 32° F to 130° F operating temperature range
• High security in public areas
• Sensor averaging (1, 4, 9, 16, etc. perfect squares)
196
Specifications
Physical Characteristics
Dimensions (LxWxD):
3 1/4" x 2 7/16" x 7/8"
Appearance:
Plastic Material: Taupe Color
Weight:
6 oz.
Electrical Characteristics
Input Volts: 5 VDC
YSI Curve 10 K Thermistor @ 77° + 2°
Environmental Requirements
Temperature:
Operating: 41° F to 104° F (-5° C to 40° C)
Storage: -40° F to 135° F (-40° C to 57° C)
Humidity: 0 to 95% Relative humidity, non-condensing
Communications Characteristics
None
Wiring Requirements
2 Conductor 18 Ga, Stranded with a shield. Shield
grounded at one end. Use extra wire from thermostat
to equipment ground.
Operating Characteristics
Remote Room Sensor for Commercial Programmable
Thermostat - 33CSPTN-01
• Commercial Product Guide • 2002 •
Commercial Products
Outdoor Temperature Sensor
Comfort System Components
The Outdoor Temperature Sensor, or OAS, is an accessory for
the Carrier Corporation Thermostat (33CSPTN-01). It allows
the outdoor temperature to be displayed at the thermostat and to
be used to lockout heating or cooling.
Features
• Easy to install
• Operating range 30° F to 120° F
Specifications
Physical Characteristics
Dimensions (LxWxD):
4" x 2 1/2" x 1/2"
Shipping Weight:
1 lb.
Operating Range
30° F to 120° F
Maximum Length from Thermostat
1,000 ft.
Wiring Requirements
2 Conductor 18 Ga, Stranded with a shield. Shield
grounded at one end. Use extra wire from thermostat
to equipment ground.
Operating Characteristics
Use with (33CSPTN-01)
• Commercial Product Guide • 2002 •
197
Commercial Products
Add-A-Subzone™
Comfort System Components
The Add-A-Subzone system is used to create a “floating”
or subzone within a larger conditioned area. Add-A-Subzone
creates the subzone by comparing duct temperature and zone
demand, and opening or closing the dampers accordingly. AddA-Subzone can also be used to control ventilation to the zone.
Features
• Designed to work with residential Comfort Zone/Zone
Perfect dampers.
• Includes digital duct temperature sensor
• Uses only 300 mA of 23VAC power
• Can be configured for ventilation or energy savings mode
• Easy to install
• Controls up to four dampers for simultaneous operation.
Corrects over conditioning in conference rooms, offices, etc.
• Add a fifth “floating” zone to 4 zone systems, or a third zone
to a 2 zone system
• Use to add or replace Moduline® units
• Use in areas that only need conditioning occasionally, save
energy by allowing conditioning only when required
Specifications
Dimensions (HxW):
1.87" x 2.87"
18.00" duct sensor wiring (can be extended to 100' maximum)
6.00" zone damper wiring
Wire
20 ga., unshielded
Power Requirement
24VAC
* Add-A-Subzone controls a damper only and does not directly
control HVAC equipment
198
• Commercial Product Guide • 2002 •
Commercial Products
Add-A-Wire™
Comfort System Components
Add-A-Wire is a thermostat accessory that allows the addition
of a wire to the thermostat where new wiring cannot be run.
Add-A-Wire can be used to make one thermostat wire work
like two, add cooling to a heat only system or add a common
wire to a four-wire system. The Add-A-Wire accessory can also
be used to fix a broken wire.
Features
• Allows an existing thermostat installation to
accommodate new features without rewiring
• Allows repair of a broken wire
• Can be mounted inside the HVAC unit or inside
the control box (must be protected from the elements)
Specifications
Dimensions (HxW):
1.75" x 2.125"
Wire
18-22 ga., unshielded
Maximum distance from Add-A-Wire to Thermostat
18 ga. wire - 100 ft
22 ga. wire - 36 ft
• Commercial Product Guide • 2002 •
199
Commercial Products
ComfortWORKS®
Comfort System Components
• Super VGA high resolution graphics
• Customized Access Levels - provides you with the ability to
assign one of 5 pre-defined operator access levels or create
your own custom level on an area by area basis
• Export data into other application software - you can
transport ComfortWORKS data to popular spreadsheet, word
processor, and database programs
• Dynamic Data Exchange (DDE) - support to display
and override third party software points from within a
WorkSPACE. Also supports DDE Poke, which allows
third party software to override CCN points
• Time and Setpoint Schedule DLL - includes this Dynamic
Link Library, which allows third party access to CCN time
and setpoint schedules and remote CCN connection
Specifications
ComfortWORKS is a PC-based software interface which
fully utilizes the power of Microsoft® Windows NT® or
Windows 2000. Its multi-tasking ability means there’s no
need for a dedicated PC, and other Windows-based software
can run simultaneously. In addition to a built-in graphics
library, ComfortWORKS allows users to create customized
screen graphics, illustrating the entire HVAC system for ease
of monitoring and configuration. The system is compatible
with common LANs such as Ethernet and Token Ring.
Features
• Display dynamic data in both text and graphic modes
• Create dynamic trend plots of data from one or
multiple controllers
• View, print, and acknowledge alarms from the network.
Configure operating parameters such as time schedules,
setpoints, and point configuration. View and configure
time and setpoint schedules in graphic and tabular mode
• Downline load data to and upline load data from controllers
• Override the state or value of selected input and output points
• Verify active controllers
• Customize graphics and create custom links from
graphic to graphic
• Generate reports from system data and activity
• Create custom WorkSPACEs for each user
• Easily backup and store all database information to disk
• Obtain on-line operator help
• Create custom controller programs (BEST++)
• Connect to remote CCNs and perform all functions as if
locally connected
• True System Multi-tasking - no need for a dedicated PC other Windows application software can run simultaneously
• Graphical User Interface (GUI) - provides a consistent look
and intuitive operation, utilizes standard Windows features
and operations
200
The following hardware is required to support
ComfortWORKS software:
Personal Computer:
Server
• Pentium Intel®-based processor with 256K cache RAM*
• 256MB of memory
• 500MB hard disk
• 3.5" 1.44 MB high density disk drive
• 17" 1024 x 768 video graphics adapter card*
• CD-ROM Drive
• SQL Server 2000 (database management software)*
• 10 BaseT Ethernet Network Interface
• Parallel printer port
Client
• Pentium Intel-based processor with
256K cache RAM* 64MB of memory
• 300MB hard disk
• 3.5" 1.44 MB high density disk drive
• 17" 1024 x 768 video graphics adapter card*
• Laser, ink jet, or 24-pin dot matrix printer*
- 1 Printer for Alarms and Reports, or
- 2 Printers -1 dedicated to each function
• 10 BaseT Ethernet Network Interface
• Parallel printer port
*These components must be verified as Windows NT®
compatible by your computer dealer.
The following software is required to support
ComfortWORKS software:
Windows NT or Windows 2000 Professional operating system
An Upgrade Kit is available (CEAS 130447-03)
• Commercial Product Guide • 2002 •
Commercial Products
ComfortVIEW™
Comfort System Components
Standard Product Offering
• Single Local/Single Remote CCN - Control and
monitoring of one locally-connected CCN and one
remote CCN, accessed by CCN Autodial Gateway,
TeLINK, NAM, or modem.
• Carrier Network Manager - This application, through the use
of branching tree structure displays (similar to those in the
Windows Explorer) shows you the CCNs, areas, controllers,
and tables that make up your ComfortVIEW™ database.
• Alarm Manager - This application gives you the ability to
view and acknowledge incoming alarms, regardless of the
application that you have running on your computer.
• Setup - You use this application to add, modify, and delete
ComfortVIEW operators, and to specify global system-type
parameters such as engineering units, and time of day for
automatic report data retrieval.
• Help - A full complement of Windows-style help is included
in the standard ComfortVIEW product.
Options
• Multiple Remote CCNs - Control and monitoring of multiple
remote CCNs, accessed by CCN Autodial Gateway, TeLINK,
NAM, or modem.
• WorkSPACE Manager -This application allows you to
create customized graphic displays of data and save them
as WorkSPACEs. You can also create dynamic trend plots
of data.
• Report Panel - This application gives you the ability to create
consumable, runtime, history, tenant billing, and system
activity reports.
• BEST++™ - This application gives you access to Carrier’s
Building Environmental System Translator (BEST++) custom
controller programming language.
Features
• Display dynamic data in both text and graphic modes
• Create dynamic trend plots of data from one or
multiple controllers
• View, print, and acknowledge alarms from the network.
Configure operating parameters such as time schedules,
setpoints, and point configuration. View and configure
time and setpoint schedules in graphic and tabular mode
• Downline load data to and upline load data
from controllers
• Override the state or value of selected input and
output points
• Verify active controllers
• Customize graphics and create custom links from
graphic to graphic
• Generate reports from system data and activity
• Create custom WorkSPACEs for each user
• Easily backup and store all database information to disk
• Obtain on-line operator help
• Create custom controller programs (BEST++)
• Connect to remote CCNs and perform all functions as if
locally connected
• True System Multi-tasking - no need for a dedicated PC other Windows application software can run simultaneously
• Graphical User Interface (GUI) - provides a consistent look
and intuitive operation, utilizes standard Windows features
and operations
• Super VGA high resolution graphics
• Customized Access Levels - provides you with the ability to
assign one of 5 pre-defined operator access levels on an area
by area basis
• Export data into other application software - you can transport
ComfortVIEW data to popular spreadsheet, word processor,
and database programs
• Dynamic Data Exchange (DDE) - support to display
and override third party software points from within a
WorkSPACE. Also supports DDE Poke, which allows
third party software to override CCN points
• Time and Setpoint Schedule DLL - includes this Dynamic
Link Library, which allows third party access to CCN time
and setpoint schedules and remote CCN connection
• The following software is required to support ComfortVIEW:
Windows 95/98/ME
• Commercial Product Guide • 2002 •
201
Commercial Products
Humidity Sensor
Comfort System Components
The Humidity Sensor is used on the VVT® and TEMP Comfort
Systems Monitor Thermostats for information purposes only.
When a Carrier Comfort Network exists, one Humidity
Sensor may be used to broadcast the humidity information
to other devices.
Features
• 0 to 100% Relative humidity sensing
• Easy to install
202
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 1/4" x 3" x 4 3/4"
Shipping Weight:
2 lbs.
Operating Range
0 to 100%
Maximum Length from Thermostat
1,000 ft.
Wiring
4 Wire - 18 ga.
• Commercial Product Guide • 2002 •
Commercial Products
Network Service Tool IV
Comfort System Components
The Network Service Tool IV is a software package that can be
used by Carrier Comfort Network technicians to start up and
troubleshoot CCN systems.
Because the Network Service Tool runs on a portable PC, it
can be carried anywhere in a building to provide the technician
with local access to any CCN system element.
An additional feature of the NST is the ability to connect over
telephone lines to a remote network.
Network Service Tool is required to start-up and configure
Comfort Controllers 1600/6400.
The Network Service Tool User-Manual (808-562) can be
ordered separately from Literature Distribution.
The Network Service Tool can run on a dual-floppy PC or it
can be installed on a hard drive.
An NST IV Upgrade Kit is also available (CEAS130306 01)
Minimum PC requirements:
• 640K memory
• DOS, Windows 3.1 or Windows 95
• One 1.44 MB 3.5" high density disk drive and a hard drive
Features
The Network Service Tool requires a Carrier-approved
RS232/485 Converter. The following RS232 to RS485
converters have been tested and approved for use with the
Network Service Tool:
OPTO 22 converter card
B&B Electronics Model 485COR
B&B Electronics Model 485CARLP9
CCN Repeater
Network Access Module (33CSNA—01)
• Connect to a remote building by means of a modem
• Configure operating parameters such as time schedules,
temperature set points, and system gains
• Points that are currently in alarm are highlighted and can be
viewed. The Diagnostic Trace function enables a service
technician to collect data from up to 20 points. Search a
network for active devices and addresses
• Display current data dynamically in customary US
and metric units
• Create and edit BEST/BEST++™ (custom) programming
Specifications
The Network Service Tool Kit (CEAS121367) includes:
• Network Service Tool Software
• Access key
• Network Service Tool User’s Manual
• Commercial Product Guide • 2002 •
203
Commercial Products
TeLINK
Comfort System Components
TeLINK serves as an interface between a CCN and a
telecommunications network. The TeLINK module and a
modem enable the CCN to communicate over telephone
lines with other similarly equipped CCNs. The telephone
connection between the CCNs enables system elements in
the two networks to communicate as though they were
connected directly.
The TeLINK module is a device similar in appearance to an
external modem. It can be placed on a desktop or inside a
standard NEMA enclosure.
Features
• Report alarms generated at a remote job site to a central
monitoring center or beeper service
• Allow alarm reporting to one site during occupied hours
and another during unoccupied hours.
• Allow remote system elements to be queried from a
monitoring center. Link to a remote site from a monitoring
center using ComfortWORKS® software
• Provide an automatic daily or manual “self-health” check of
communication from the remote site to the monitoring center
• Provide some Network Directory Services (NDS) directory
and diagnostic functions for the primary CCN bus to which it
is connected
204
Specifications
Power Requirements
Control module
9 VAC, ±15%,
500 mA minimum
Storage Temperature
-40° F to 140° F (-40° C to 60° C)
Operating Temperature
32° F to 122° F (0° C to 50° C)
Operating Humidity
10% to 90% Relative humidity, non-condensing
Storage Humidity
10% to 90% Relative humidity, non-condensing
Dimensions
Width: 5.25 in (13.335 cm)
Length: 5.00 in (12.7 cm)
Height: 1.62 in (4.15cm)
Conforms to guidelines for radiated and conducted emissions
for Class A device as stated in FCC Rules and Regulations Part
15, Subpart J.
UL 916 PAZX, UL 864 UDTZ, UL,Canada, and CE MARK
(Light Industrial) listed.
NOTE: Modem selection should comply with the rules
and regulations specified by the local telecommunications
company. Modems should be purchased in the country where
they will be used.
• Commercial Product Guide • 2002 •
Commercial Products
Comfort Controller 1600
Comfort System Components
The Comfort Controller 1600 is a microcontroller-based
module that provides general purpose HVAC control and
monitoring capability in a stand alone or network environment
using closed-loop, direct digital control. The 1600 gives the
Carrier Comfort Network (CCN) the capability to control
and communicate with non-Carrier equipment and Carrier
HVAC equipment not equipped with Product Integrated
Controls (PICs).
Features
• Stand-alone control and monitoring of up to
16 field points, using proven algorithms
• Total facilities management when linked to a CCN
• Alarm processing, messages and annunciation
• Demand limiting/load shedding
• Algorithm library for a variety of control operations
• Simplified field wiring using “plug type” terminals
(two-pin connection)
Specifications
Power Requirements
[email protected] ± 15% [email protected] VDC ± 15%
Dimensions
13" H x 2.75" W x 5.5" D (33 cm x 7 cm x 14 cm)
Operating Temperature
32° F to 140° F (0° C to 60° C)
Storage Temperature
-40° F to 185° F (-40° C to 85° C)
Operating Humidity
0 to 90%, non-condensing
Discrete Out Specifications
Output Signal
24 VDC @80 mA current limited
Analog Out Specifications
4-20 mA Milliamp Type
Load Resistance 0-600 ohms
Resolution 0.085 mA Accuracy ± 2%
0-10 Vdc Voltage Type
Load Resistance >50,000 ohms
Resolution 50mV
Accuracy ±2%
Discrete In Specifications
Dry Contacts Switch Closure
Pulsing Dry Contacts
Repetition Rate: 5 Hz max.
Minimum Pulse: Width 100 msec
Analog In Specifications
4-20 mA Milliamp Type
Wire type 2-wire
Resolution 0.025 mA
Accuracy ±1%
0-10 Vdc Voltage Type
Resolution 0.0125V
Accuracy ±11%
5K Thermistor Type
Nominal reading @ 5,000 ohms
77° F (25° C)
Resolution 0.1°F
Accuracy ±1°F
10K Thermistor Type
Nominal reading @ 10,000 ohms
77° F (25° C)
Resolution 0.1° F Accuracy ±1° F
Nickel RTD Type
Nominal reading @ 1,000 ohms
70° F (21° C)
Resolution 0.1° F
Accuracy ±2° F
The 1600 is UL 916 PAZX, and UL, Canada listed.
• Commercial Product Guide • 2002 •
205
Commercial Products
Comfort Controller 6400
Comfort System Components
The Comfort Controller 6400 is a microcontroller-based module
that provides general purpose HVAC control and monitoring
capability in a stand-alone or network environment using
closed-loop, direct digital control. The 6400 gives the Carrier
Comfort Network (CCN) the capability to control and
communicate with non-Carrier equipment and Carrier HVAC
equipment not equipped with Product Integrated Controls
(PICs). With multiple I/O modules, the 6400 can control and/or
monitor up to 64 field points.
Features
• Stand-alone control and monitoring of up to 16 field points,
using proven algorithms
• Total facilities management when Dimensions linked
to a CCN
• Simplified field wiring using “plug type” terminals
(two-pin connection)
• Alarm processing, messages and annunciation
• Demand limiting/load shedding
• Library of algorithms for a variety of control operations
• Inputs can be configured universally
• Outputs can be configured universally
Power Requirements
[email protected] VAC ±15%
[email protected] VDC ±15%
Dimensions
13" H x 2.75" W x 5.5" D (33 cm x 7 cm x 14 cm)
Operating Temperature
32° F to 140° F (0° C to 60° C)
206
Storage Temperature
-40° F to 185° F (-40° C to 85° C)
Operating Humidity
0 to 90%, non-condensing
Discrete Out Specifications
Output Signal
24 VDC @ 80 mA current limited
Analog Out Specifications
4-20 mA Milliamp Type
Load Resistance 0-600 ohms
Resolution 0.085 mA
Accuracy ±2%
0-10 Vdc Voltage Type
Load Resistance >50,000 ohms
Resolution 50mV
Accuracy ±2%
Discrete In Specifications
Dry Contacts Switch Closure
Pulsing Dry Contacts
Repetition Rate: 5 Hz max.
Minimum Pulse.- Width 100 msec
Analog In Specifications
4-20 mA Milliamp Type
Wire type 2-wire
Resolution 0.025 mA
Accuracy ±1%
0-10 Vdc Voltage Type
Resolution 0.0125V
Accuracy ±1%
5K Thermistor Type
Nominal reading @ 5,000 ohms
77° F (25° C)
Resolution 0.1° F
Accuracy ±1° F
10K Thermistor Type
Nominal reading @ 10,000 ohms
77°F (25°C) Resolution 0.1° F
Accuracy ±1° F
Nickel RTD Type
Nominal reading @ 1,000 ohms
70° F (21° C)
Resolution 0.1° F
Accuracy ±2° F
The 6400 is UL 916 PAZX and UL, Canada listed.
• Commercial Product Guide • 2002 •
Commercial Products
Comfort Controller 6400-I/O
Comfort System Components
The Comfort Controller 6400-I/O is used with the Comfort
Controller 6400 to expand the field point capacity from 16
points (8 inputs and 8 outputs) up to a total of 64 points. Each
I/O expands the Comfort Controller 6400 an additional 16
points (8 inputs and 8 outputs). A total of three I/O modules
can be connected to the Comfort Controller 6400 for a total of
64 points of control.
Features
• Can be configured to use all 16 points (8 inputs and 8 outputs)
up to a total of 64 points
• LEDs indicate processor status (red) Dimensions and module
communication status (green)
• Local connection for LID (Local Interface Device)
• Ability to disable all inputs or all outputs by simply
flipping a switch
• Simplified field wiring using “plug type” terminals
Specifications
Power Requirements
[email protected] 15%
[email protected] 15%
Dimensions
13" H x 2.75" W x 5.5" D (33 cm x 7 cm x 14 cm)
Operating Temperature
32° F to 140° F (0° C to 60° C)
Storage Temperature
-40° F to 185° F (-40° C to 85° C)
Operating Humidity
0 to 90%, non-condensing
Discrete Out Specifications
Output Signal
24 [email protected] mA current limited
Analog Out Specifications
4-20 mA Milliamp Type
Load Resistance: 0-600 ohms
Resolution: 0.085 mA
Accuracy: ±2%
0-10 VDC Voltage Type
Load Resistance: >50,000 ohms
Resolution: 50mV
Accuracy: ±2%
Discrete In Specifications
Dry Contacts Switch Closure
Pulsing Dry Contacts
Repetition Rate: 5 Hz max.
Minimum Pulse: Width 100 msec
Analog In Specifications
4-20 mA Milliamp Type
Wire type 2-wire
Resolution 0.025 mA
Accuracy ±1%
0-10 VDC Voltage Type
Resolution 0.0125V
Accuracy ±1%
5K Thermistor Type
Nominal reading @ 5,000 ohms
77° F (25° C)
Resolution 0.1° F
Accuracy ±1° F
10K Thermistor Type
Nominal reading @ 10,000 ohms
77° F (25° C)
Resolution: 0.1° F Accuracy ±1° F
Nickel RTD Type
Nominal reading @ 1,000 ohms
70° F (21° C)
Resolution: 0.1° F
Accuracy: ±2° F
The 6400 and 6400 1/0 are UL 916 PAZX, VDE
and UL, Canada listed.
• Commercial Product Guide • 2002 •
207
Commercial Products
6400 Hand-Off Auto
Comfort System Components
The 6400 Hand-Off Auto is an optional device used on the
Comfort Controller 6400. It consists of eight switches that
provide you with the capability to manually override each
discrete output point.
Features
• Manual override discrete output points
• Used on Comfort Controller 6400 only
• Eight toggle switches
208
Specifications
Shipping Weight
3 lbs.
Operating Temperature
32° F to 140° F (0° C to 60° C)
Storage Temperature
-40° F to 185° F (-40° C to 85° C)
Operating Humidity
0 to 90%, non-condensing
Power Requirements
None, plugs into 6400 module
• Commercial Product Guide • 2002 •
Commercial Products
33AM Comfort System
AirManager™ Control
Comfort System Components
The AirManager is a compact, self-contained, pre-engineered
air handler manager, designed to control ventilation, heating,
cooling, filtration and distribution functions for constant
volume as well as variable volume systems. It controls,
monitors and adjusts for varying indoor and outdoor
temperatures, humidity levels and scheduling information, to
ensure optimal performance, efficiency and indoor air quality
during occupied and unoccupied periods. AirManager’s safety
features provide alarms and shut-down functions to protect
against damage caused by hazardous conditions such as smoke,
fire, freezing coils and excessive humidity.
AirManager is a near-universal control, compatible with
Carrier’s three complete lines of air handlers, as well as other
brands and built-up units in both network and stand-alone
configurations. It can be fully integrated with all of Carrier’s
Comfort Network products.
Features
• Local set point and occupancy scheduling (with optional
linkage thermostat)
• Supply air temperature reset (variable volume applications)
Specifications
Dimensions (HxWxD):
20" x 24" x 10"
Shipping Temperature
40° F to 165° F (40° C to 74° C)
Shipping Humidity
10% to 95% Relative Humidity
Operating Temperature
32° F to 140° F (0° C to 60° C)
Operating Humidity
10% to 90% Relative Humidity, non-condensing
Power Requirements
120VAC, 50 or 60 Hz, 5A
• Key control components together in a single enclosure
• Works with networks and stand-alone systems
• Compact, rugged housing
• Remote mounting capability, easy to install
• Compatible with most air handlers
• Integrates with Carrier Comfort Network products
• Supports Digital Air Volume (DAV) control
• Monitors indoor and outdoor temperatures, humidity levels
and scheduling information
• Self-tunes control routines to ensure optimal performance
• Temperature compensated start function
• Local occupancy override
• Local temperature set point offset (constant volume
applications)
• Commercial Product Guide • 2002 •
209
Commercial Products
Comfort System Linkage
Thermostat
Comfort System Components
Specifications
The Comfort System Linkage Thermostat is a communications
device that performs standard CCN linkage with up to eight air
source elements. It maintains temperature conditions by
measuring zone temperature, maintaining schedules and
coordinating the distribution of information with connected
elements. It has an electronic timeclock that can broadcast time
to all devices on the communication bus. The linkage
thermostat can be programmed to provide user-defined
occupied and unoccupied time schedules, and the display
allows the user to monitor operation mode, current set points,
local space temperature and time. When used with the
Comfort System AirManager™, the temperature compensated
start feature can perform the necessary calculations and
pre-start the unit to reach the desired occupied temperature
by the start of the occupied period. The thermostat kit includes
a linkage thermostat, 24VAC transformer and a 10 VDC power
supply. The Comfort System Linkage Thermostat is compatible
with the full line of Carrier air source products, including air
handlers, unit ventilators, Comfort Controllers and rooftop
units.
Features
Zone Control Capabilities - Physical Characteristics
Clock Power Loss Backup Time:
• Four levels of security
• Remote space temperature sensing and averaging
• Occupied and unoccupied heat and cool set points
• Occupied schedule with 8 time periods
210
Dimensions (HxWxD):
3.875" x 7.062" x 2.875"
Appearance:
Taupe Plastic, Textured Plastic
Weight:
16 oz.
Electrical Characteristics
Input Volts/Amps:
10-11 VDC/100 mA from unit controller
Environmental Requirements
Operating Temperature:
32° F to 130° F
Relative Humidity:
10% to 95%, non-condensing
Storage Temperature
-40° F to 158° F
Relative Humidity:
10% to 95% Relative humidity, non-condensing
Operating Characteristics
Set Point Range:
50° F to 99° F
Scheduling:
365-day
Override:
Unoccupied to occupied at thermostat
Clock Power Loss Backup Time:
10 hours without Battery
Permanent Memory for Configuration
Auto/Manual Changeover
Optimal Start
Wiring Requirements
Communication Bus:
3 conductor, 20 ga.,
stranded, plus shield (1,000 ft. maximum)
Power Supply:
2 conductor, 18 ga.,
twisted pair cable (100 ft. maximum)
• Commercial Product Guide • 2002 •
Commercial Products
1
J6
1
2
1
J2B LEN
Unit#:
yel
• Provides Pressure Independent (VAV) control
• Uses Proportional Integral Derivative (PID) control
• Mounts directly onto VAV box damper shaft
• For terminals up to 9000 cfm or 3.4 sq. ft
inlet (primary air)
• Auxiliary heating control of modulating (floating) hot water,
single-position hot water, single or two-stage electric, or zone
perimeter heat
• Quick and easy commissioning and balancing process
• Automatic self calibration of airflow transducer
• Capable of stand-alone operation, with supply-air
temperature sensor
• Actuator preassembled to housing
• Capable of demand controlled ventilation support with
field-installed IAQ sensor
• Easy access to airflow sensor pneumatic connections
• Uses Carrier Comfort Network (CCN) protocol
• Capable of high-speed 38.4 kilobaud communications
network operation
• 128 controller maximum system (must be located on
same CCN bus segment)
• Capable of zone humidity control (dehumidification)
with field-installed humidity sensor
• Carrier Linkage System capability
• Global set point and occupancy scheduling
• Capable of local set point adjustment with field-installed
temperature sensor (with temperature offset)
• Both controller housing and actuator are UL94-5V plenum
rated.
Features
Flexibility for every application
The zone controller is a single duct, fan powered, variable
air volume (VAV) terminal control with a factory-integrated
controller and actuator. The zone controller maintains
precise temperature control in the space by operating the
blu
ora
blk
red
+
G -
1
6
J1
1
24VAC
1 2 3
3
COM
WIP
CCW
COM
CW
HEAT1
24VAC
HEAT2
J6
HIGH
5K
- G
3
J2A CCN
Element#:
Class 2 Supply
24VAC/DC
50/60 Hz
3VA 2W
+
SRVC
LISTED
94D5
TENP IND &
REG. EQUIP.
+
3
S/N:
Bus#:
J3
33ZCVAVTRM VAV
Features
Part Number: 33ZCVAVTRM
NEMA 2
GND
1
®
ZONE Controller
35 in-lb (4 Nm)
80...110s
LR 92800
T56
- G
HF23BJ042
SAT
PAT
TEST
N/A
GND
®
Made in Switzerland
by Belimo Automation
+24V
SPT
GND
RH/IAQ
GND
FAN AC
FAN SECFLOW
+10V
24VAC
N/A DMPPOS
HEAT3
GND
J4
1 2
J7
1
0
16
15
US
C
3
The Single Duct Air Terminal Zone Controller provides
dedicated control functions for single duct terminals with
modulating heat or up to 2 stages of heat. The zone controller
is part of the Carrier ComfortID™ system.
LOW
Single Duct Air Terminal
Zone Controller
wht
terminal damper and regulating the flow of conditioned air
into the space.
Buildings with diverse loading conditions can be supported
by controlling reheat (single duct only) or supplemental heat.
The zone controller can support single position hot water,
modulating hot water, 2-stage electric, or perimeter heat.
Specifications
Wiring connections
Field wiring is 18 to 22 AWG (American Wire Gauge).
The zone controller is a NEC (National Electronic Code)
Class 2 rated device.
Inputs
• Space temperature sensor
• Primary air damper position
• Airflow sensor (factory installed)
• Field-installed remote wall sensor set point adjustment
• Optional primary air temperature sensor (required for
systems which do not utilize a linkage compatible air source)
• Optional IAQ sensor
• Optional relative humidity sensor
Outputs
• Internally factory-wired VAV actuator
• Heating
-modulating (floating) heat
-up to 2 stages of heat
-single position heat
• Commercial Product Guide • 2002 •
211
Power Supply
The power supply is 24VAC ±10% at 40VA (50/60 Hz)
Power consumption
The power requirement sizing allows for the damper actuator
and accessory water valves or electric heat contactor. Water
valves are limited to 15VA on both single-position and
modulating hot water.
Accuracy
Terminal airflow (nominal cfm) is rated at 1-in. wg (249 kPa)
measured velocity pressure. The zone controller is capable
of controlling to as low as 10% or as high as 125% of nominal
airflow with an accuracy of ±3% (nominal) at any point within
the range.
Hardware (memory)
FLASH EPROM
Differential pressure range
0 to 2.0 in. wg (0 to 498 kPa) maximum for the
on-board flow sensor.
Specified sensing temperature range
The zone controller space temperature range is -40° F to 245° F
(-40° C to 118° C). The zone controller has an allowable
control set point range from 40° F to 90° F (4° C to 32° C) for
heating and 45° F to 99° F (7° C to 37° C) for cooling.
Communications
The number of controllers is limited to 128 zones
maximum, with a limit of 8 systems (Linkage Coordinator
configured for at least 2 zones). Bus length may not exceed
4000 ft (1219 m), with no more than 60 devices on any
1000 ft (305 m) section. Optically isolated RS-485 repeaters
are required every 1000 ft (305 m). At 19,200 and 38,400 baud,
the number of controllers is limited to 128 maximum, with no
limit on the number of Linkage Coordinators. Bus length may
not exceed 1000 ft (305 m).
Environmental ratings
Operating Temperature:
32° F to 140° F (0° C to 60° C) at 0 to 90% Relative
Humidity, non-condensing
Shipping Temperature:
-40° F to 185° F (-40° C to 85° C) at 0 to 90% Relative
Humidity, non-condensing
Vibration
Performance vibration:
0.014-in. (0.356 mm) Peak-to-Peak displacement
measured at 5 to 31 Hz
0.75 G measured at 31 to 300 Hz
Corrosion
Office environment. Indoor use only.
Approvals
• Listed under UL 916-PAZX and UL 873
• Conforms to requirements per European Consortium
standards EN50081-1 (CISPR 22, Class B) and EN50082-1
(IEC 801-2, IEC 801-3, and IEC 801-4) for CE mark labeling
• Ul94-5V plenum rated (housing and actuator)
212
Field-Installed Accessories
Conduit box
The 33ZCCONBOX conduit box provides two conduit
connections to the zone controller for installations requiring
the use of conduit due to local electrical codes.
Supply air temperature sensor
The 33ZCSENSAT supply air temperature sensor is required for
heating applications or stand-alone operation. The sensor
is optional on cooling only applications and is used for
supply air monitoring. The sensor has an operating range of
-40° F to 245° F (-40° C to 118° C).
Primary air temperature sensor
The 33ZCSENPAT primary air temperature sensor is required
on a linkage coordinator zone controller if the zone controller
is not using a CCN linkage compatible air source. The sensor
is used to monitor the equipment’s supply-air temperature. The
temperature is broadcast to the zone controllers which receive
information from the linkage coordinator. The sensor has an
operating range of -40° F to 245° F (-40° C to 118° C).
Space temperature sensor with override button
The 33ZCT55SPT space temperature sensor with override
button is required for all applications. The space temperature
sensor monitors room temperature which is used by the zone
controller to determine the amount of conditioned air that is
allowed into the space.
Space temperature sensor with override button
and set point adjustment
The 33ZCT56SPT space temperature sensor with override
button and setpoint adjustment can be used in place of the
33ZCT55SPT space temperature sensor if local set point
adjustment is required. A space temperature sensor is required
for all applications. The space temperature sensor monitors
room temperature which is used by the zone controller to
determine the amount of conditioned air that is allowed into the
space. The set point adjustment bar allows up to a ±15° F
(8° C) temperature adjustment by the room occupant.
Communicating Space Temperature Sensor
The 33ZCT58SPT is communicating space sensor with an LCD
screen and four push buttons for user interaction with the VAV
operation and set point adjustment.
Combo CO2/Space Temperature Sensor
The 33ZCT55CO2 and 33ZCT56CO2 (with set point
adjustment) provides both CO2 sensing for demand controlled
ventilation and space temperature sensing in one easy to install
device. All of the features of the 33ZCT56SPT are combined
with a single beam absorption infrared diffusion CO2 sensor.
• Commercial Product Guide • 2002 •
Commercial Products
US
Flexibility for every application
• The zone controller is a single duct, fan powered, variable air
volume (VAV) terminal control with a factory-integrated
controller and actuator. The zone controller maintains precise
temperature control in the space by operating the terminal fan
and regulating the flow of conditioned air into the space.
• Buildings with diverse loading conditions can be supported
by controlling reheat (single duct only) or supplemental heat.
3
1
J2B LEN
1
SRVC
J3
Element#:
Unit#:
Class 2 Supply
24VAC/DC
50/60 Hz
3VA 2W
yel
blu
ora
blk
red
1
6
J1
1
+
G -
1 2 3
WIP
24VAC
J6
COM
3
5K
+
- G
- G
+
3
CW
COM
CCW
3
3
S/N:
Bus#:
LISTED
94D5
TENP IND &
REG. EQUIP.
J2A CCN
1
Part Number: 33ZCFANTRM
NEMA 2
J8
SEC DMP
LR 92800
1
ZONE Controller
35 in-lb (4 Nm)
80...110s
2
J7
Features
®
®
Made in Switzerland
by Belimo Automation
CCW
COM
CW
HEAT1
24VAC
HEAT2
• Provides Pressure independent (VAV) control
• Uses Proportional Integral Derivative (PID) control
• Mounts directly onto VAV box damper shaft
• Terminal fan control
• For terminals up to 9000 cfm or 3.4 sq. ft inlet (primary air)
• Auxiliary heating control of modulating (floating) hot water,
two position hot water; single, two or three stage electric; or
zone perimeter heat
• Quick and easy commissioning and balancing process
• Automatic self calibration of airflow transducer
• Capable of stand-alone operation, with supply air
temperature sensor
• Actuator preassembled to housing
• Capable of demand controlled ventilation support with
field-installed IAQ sensor
• Capable of individual zone pressure control for individual
supply and exhaust control in conjunction with field-installed
secondary terminal
• Easy access to airflow sensor pneumatic connections
• Uses Carrier Comfort Network (CCN) protocol
• Capable of high-speed 38.4 kilobaud communications
network operation
• 128 controller maximum system (must be located on same
CCN bus segment)
• Capable of zone humidity control (dehumidification)
with field-installed humidity sensor
• Carrier Linkage System capability
• Global set point and occupancy scheduling
• Capable of local set point adjustment with field-installed
temperature sensor (with temperature offset)
• Both controller housing and actuator are UL94-5V
plenum rated
1
0
HF23BJ042
HIGH
The 33ZCFANTRM VAV Fan Terminal
Zone Controller Features
+24V
RH/IAQ
SPT
GND
GND
FAN AC
FAN SECFLOW SAT
+10V
24VAC
T56
N/A DMPPOS
GND
HEAT3
GND
PAT
TEST
N/A
GND
J4
1 2
J6
1
C
16
15
VAV Fan Terminal Zone
Controller
LOW
The VAV Fan Terminal Zone Controller provides dedicated
control functions for series fan or parallel fan powered
terminals, single duct terminals with 3 stages of heat, or as
a primary controller for dual duct or zone pressurization
applications. The zone controller is part of the Carrier
ComfortID™ System.
wht
The zone controller can support two-position hot water,
modulating hot water, or 3-stage electric heat.
• With the addition of a secondary terminal and the
33ZCSECTRM controller, either dual duct or zone
pressurization applications can be supported.
Specifications
Wire connections
Field wiring is 18 to 22 AWG (American Wire Gauge).
The zone controller is a NEC (National Electrical Code)
Class 2 rated device.
Inputs
• Space temperature sensor
• Primary air damper position
• Airflow sensor (factory installed)
• Field-installed remote wall sensor set point adjustment
• Optional supply temperature sensor (required for heat and
supply air monitoring)
• Optional primary air temperature sensor (required for systems
which do not utilize a linkage compatible air source)
• Optional IAQ sensor
• Optional relative humidity sensor
• Optional secondary airflow (zone pressure or dual duct)
Outputs
• Internally factory-wired VAV actuator
• Heating
-modulating (floating) heat
-up to 3 stage heat
-two-position heat
• Fan start/stop
• Secondary damper actuator
Power supply
The power supply is 24VAC ± 10% at 40VA (50/60 Hz).
• Commercial Product Guide • 2002 •
213
Power consumption
The power requirement sizing allows for accessory water
valves and for the fan contactor. Water valves are limited to
8VA on both two-position and modulating hot water. The fan
contactor is limited to 11VA (holding).
NOTE: If a water valve or fan contactor exceeds these limits,
or external contactors are required for electric heat, then it is
recommended a 60VA transformer be used. The maximum
rating for any output is 20VA.
Accuracy
Terminal airflow (nominal cfm) is rated at 1 in. wg (249 kPa)
measured velocity pressure. The zone controller is capable of
controlling to as low as 10% or as high as 125% of nominal
airflow with an accuracy of ±3% (nominal) at any point within
the range.
Hardware (memory)
FLASH EPROM
Differential pressure range
0 to 2.0 in. wg (0 to 498 kPa) maximum for the
on-board flow sensor.
Specified sensing temperature range
The zone controller space temperature range is -40° F to 245° F
(-40° C to 118° C). The zone controller has an allowable
control set point range from 40° F to 90° F (4° C to 32° C) for
heating and 45° F to 99° F (7° C to 37° C) for cooling.
Communications
The number of controllers is limited to 128 zones maximum,
with a limit of 8 systems (Linkage Coordinator configured
for at least 2 zones). Bus length may not exceed 4000 ft
(1219 m), with no more than 60 devices on any 1000 ft (205 m)
selection. Optically isolated RS-485 repeaters are required
over 100 ft (305 m). At 19,200 and 38,400 baud, the number
of controllers is limited to 128 maximum, with no limit on the
number of Linkage Coordinators. Bus length may not exceed
1000 ft (305 m).
Environmental Ratings
Operating Temperature:
32° F to 140° F (0° C to 60° C) at 0 to 90% Relative
humidity, non-condensing
Shipping Temperature:
-40° F to 185° F (-40° C to 85° C) at 0 to 90% Relative
humidity, non-condensing
Vibration
Performance vibration: 0.014-in. (0.356 mm) peak to peak
displacement, 5 to 31 Hz; 0.75 G, 31 to 300 Hz
Corrosion
Office environment. Indoor use only.
Approvals
Listed under UL 916-PAZX, UL 873, and UL94-5V.
214
Accessories
Secondary terminal controller
The 33ZCSECTRM secondary terminal controller is required
for dual duct or zone pressurization applications. The secondary
terminal is used on a field-supplied, single zone damper.
Conduit box
The 33ZCCONBOX conduit box provides two conduit
connections to the zone controller for installations requiring
the use of conduit due to local electrical codes.
Supply air temperature sensor
The 33ZCSENSAT supply air temperature sensor is required for
heating applications or stand-alone operation. The sensor
is optional on cooling only applications and is used for
supply air monitoring. The sensor has an operating range of
-40° F to 245° F (-40° C to 118° C).
Primary air temperature sensor
The 33ZCSENPAT primary air temperature sensor is required
on a linkage coordinator zone controller if the zone controller is
not using a CCN linkage compatible air source. The sensor is
used to monitor the equipment’s supply air temperature. The
temperature is broadcast to the zone controllers which receive
information from the linkage coordinator. The sensor has an
operating range of -40° to 245° F (-40° to 118° C).
Space temperature sensor with override button
The 33ZCT55SPT space temperature sensor with override
button is required for all applications. The space temperature
sensor monitors room temperature which is used by the zone
controller to determine the amount of conditioned air that is
allowed into the space.
Space temperature sensor with override button
and set point adjustment
The 33ZCT56SPT space temperature sensor with override
button and set point adjustment can be used in place of the
33ZCT55SPT space temperature sensor if local set point
adjustment is required. A space temperature sensor is required
for all applications. The space temperature sensor monitors
room temperature which is used by the zone controller to
determine the amount of conditioned air that is allowed up to a
±15° F (8° C) temperature adjustment by the room occupant.
Communicating Space Temperature Sensor
The 33ZCT58SPT is communicating space sensor with an LCD
screen and four push buttons for user interaction with the fan
terminal operation and set point adjustment.
Combo CO2/Space Temperature Sensor
The 33ZCT55CO2 and 33ZCT56CO2 (with set point
adjustment) provides both CO2 sensing for demand controlled
ventilation and space temperature sensing in one easy to install
device. All of the features of the 33ZCT56SPT are combined
with a single beam absorption infrared diffusion CO2 sensor.
• Commercial Product Guide • 2002 •
Commercial Products
Fan Coil Zone Controller
16
15
1
GND
2
1
1
LED1
LED2
+
3
- G
J2B LEN
1
- G
+
1
J1
3
6
24VAC
J3
SRVC
3
J2A CCN
1
J7
2
24VAC
OAD ENA
VLV/DX1
COM
VLV/DX2
HEAT1
24VAC
HEAT2
1
T56
GND
J5
• Provides 3-speed PID (proportional integral derivative)
automatic fan control to minimize fan noise by matching
fan speed to load (also providing improved dehumidification
during cooling and maximizing energy efficiency)
• Uses PID heating and cooling control to maintain
space temperature
• Provides dehumidification control (requires RH sensor to
RH value via network input)
• Provides software clock and local occupancy schedule for
local occupancy control (requires time broadcaster and
hardware clock from another device in the system)
• Uses remote timeclock input to provide occupancy control
through external contacts
• Provides optional Linkage Thermostat interface capability
• Features supply air temperature limiting and integrated
safeties for DX (direct expansion) and electric heat units
• Provides changeover control via a 10K ohm surface
mounted thermistor temperature sensor or via a forcible
CCN software variable
• Provides control of two-position outside air damper to
maintain minimum quantity of outside air during occupied
periods (after completion of warm-up)
• Provides CCN Tables and Alarms
• Provides diagnostic tests that enable the user to check I/O
points and verify their functionality
• Features spring return or non-spring modulating water
valve capability
• Provides optional remote mounted space sensor with set point
adjustment, timed override, and CCN service port jack
• Controls modulating or two-position chilled water valves
or up to two stages of DX cooling to maintain space
temperature set point
• Controls modulating or two-position hot water/steam valves
or up to two stages of electric heat to maintain space
temperature set point
• Operates the supply fan based on a local or global occupancy
schedule or remote timeclock input status
SAT
SPEED
CNGOVR
CONDSW
REMOTE
GND
ZONE Controller
Part Number: 33ZCFANCOL
S/N:
Bus#:
Element#:
Unit#:
IAQ
+10V
J4
J6
5
FAN AC
FAN ON
LOW
MED
HIGH
®
33ZCFANCOL Fan Coil Zone
Controller Features
+24V
SPT
GND
RH
GND
US
C
+
G -
The Fan Coil Zone Controller is a field retrofit or factoryinstalled CCN (Carrier Comfort Network) compatible
communicating control for fan coils (specifically designed
for applications under 2,000 cfm). The fan coil zone controller
can function as either a stand-alone control or as part of the
CCN. User interfaces include the CCN Service Tool,
ComfortVIEW™, and ComfortWORKS® software. When
used as part of the CCN, other devices such as the CCN data
transfer, Linkage Thermostat, or Comfort Controller can read
data from or write data to the fan coil zone controller.
• Provides Morning Warm-up or Smart Start cooling to achieve
set point by the start of the scheduled occupied time (requires
linkage thermostat or the use of the local occupancy schedule)
• Provides alarms for analog temperature input(s) out of range
• Provides alarm for space temperature deviation from desired
set point
• Provides Condensate Overflow alarm when condensate pan
is full (optional)
• Provides alarm for Dirty Filter based on resettable timer
• Allows manual and system overrides of selected
input/output channels
• Supports CCN remote timed override, set point adjustment,
and manual fan speed override
• Provides Broadcast Acknowledger capability for
CCN (configuration)
• Conforms to the general requirements for CCN devices
Specifications
Wiring Connections
Field wiring is 18 to 22 AWG (American Wire Gauge). The
fan coil zone controller is a NEC (National Electrical Code)
Class 2 rated device.
Inputs
• Space temperature sensor
• Field-installed remote wall sensor set point adjustment
• Supply air temperature sensor
• Manual 3-speed fan control
• Optional IAQ sensor
• Optional relative humidity sensor
• Changeover sensor
• Condensate pan full sensor
• Remote timed override input
• Commercial Product Guide • 2002 •
215
Outputs
• Heating
-modulating (floating) valve
-two-position valve
-two-stage electric
• Fan start/stop (normally open contact)
• Fan speed (low, medium, high)
• Outdoor air damper
• Cooling
-modulating (floating) valve
-two-position valve
-two-stage DX
Power Supply
The power supply is 24VAC ± 10% at 40VA (50/60Hz)
Power Consumption
The power requirement sizing allows for accessory water
valves and for 3 fan speed relays. Water valves are limited to
10VA on both two-position and modulating hot water. The fan
relays are limited to 3VA (holding) each.
NOTE: If a water valve or fan contactor exceeds these limits
or, contactors are required, then it is recommended a 60VA
transformer be used. The maximum rating for any output
is 20VA.
Accessories
Conduit Box
The 33ZCCONBOX conduit box provides two conduit
connections to the fan coil zone controller for installations
requiring the use of conduit due to local electrical codes.
The conduit box is UL94-5V rated for plenum use.
Supply air temperature sensor
The 33ZCSENSAT supply air temperature sensor is required for
all applications. The sensor has an operating range of
-40° F to 245° F (-40° C to 118° C).
Space temperature sensors
The 33ZCT55SPT space temperature sensor with override
button is required for all applications. The space temperature
sensor monitors room temperature which is used by the fan
coil zone controller to determine the temperature of conditioned
air that is allowed into the space.
Other optional space sensors include:
• 33ZCT58SPT is a communicating space sensor with an LCD
screen and four push buttons for user interaction with the fan
operation and set point adjustment
• 33ZCT56SPT space temperature sensor with override button
and set point adjustment
• 33ZCT57SPT space temperature sensor with override button,
set point adjustment, and fan speed control can be used in
place of the 33ZCT55SPT. The set point adjustment bar
allows up to a ±15° F (8° C) temperature adjustment by the
room occupant
216
Hardware (memory)
FLASH EPROM
Specified sensing temperature range
The fan coil zone controller space temperature range is
-40° F to 245° F (-40° C to 118° C). The fan coil zone
controller has an allowable control set point range from
40° F to 90° F (4° C to 32° C) for heating and 45° F to 99° F
(7° C to 37° C) for cooling.
Dimensions
Height: 5-in. (127 mm)
Width: 6 1/2-in. (165 mm)
Depth: 3-in. (76 mm)
Minimum service dimensions
Height: 7-in. (178 mm)
Width: 9-in. (229 mm)
Depth: 4-in. (102 mm)
Environmental ratings
Operating Temperature:
32° F to 140° F (0° C to 60° C) at 10% to 90% Relative
Humidity, non condensing
Shipping Temperature:
40° F to 185° F (-40° C to 85° C) at 10% to 90% Relative
Humidity, non-condensing
Vibration
Performance vibration: 0.014-in. (0.356 mm) peak to peak
displacement, 5 to 31 Hz; 0.75 G, 31 to 300 Hz
Corrosion
Office environment
Indoor use only
Approvals
Listed under UL 873, and UL94-5V (plastic).
• Commercial Product Guide • 2002 •
Commercial Products
Indoor Air Quality CO2 Sensor and
Duct-Mounted Aspirator Box
clear mode
enter
The Indoor Air Quality CO2 sensor is designed to monitor
carbon dioxide (CO2) levels in the air and interface with the
ventilation damper in an HVAC (Heating, Ventilation, and Air
Conditioning) system. In addition, the sensor can be used solely
for the purpose of monitoring and alarming.
The CO2 sensor uses infrared technology to measure the levels
of CO2 in the air. These levels can be used as input to a CCN
(Carrier Comfort Network) controller to control the ventilation
damper position and ensure an adequate level of outside air in
the building.
The aspirator box (part no. 33ZCASPCO2), houses the Indoor
Air Quality CO2 sensor for duct mount applications. The
custom internal mounting bracket secures the base of the sensor
inside the aspirator box. Power is applied by running the
conduit through a knockout and wiring to the terminal blocks
located on the sensor mounting bracket.
Features
The Indoor Air Quality CO2 sensor offers the
following advantages:
• Sleek, low profile
• On board push button interface with 2 line x 8
character display
• Mounting plate with terminal block for easy installation
and wiring
• Compatible with US and European junction boxes
• CO2 measurement range of 0 to10,000 ppm (default range
of 0 to 2000 ppm)
• Versatile sensor options including optional temperature
sensor, TEMA self-calibration, 4 to 20 mA or 0 to
10 V output
• Dual beam infrared technology guarantees no calibration
for 5 years
• Solid, locking cover for tamper resistance hides display
In addition, the aspirator box offers the following advantages:
• Duct mounted for monitoring CO2 levels in return airflow
• Quick, easy installation
• Lightweight and durable
• External mounting provides ease of sensor operation and
maintenance
• Clear cover allows for sensor verification at a glance
Specifications
Method:
Dual Beam Absorption Infrared™ Patented TEMA (time
extended measurement algorithm) self-calibration software
Optional thermistor temperature measurement
Sample Method
Diffusion or flow-thru (50 to 100 ml/min)
Performance:
Measurement Range
Analog Output:
0 to 2000 ppm factory default
adjustable to 10,000 ppm
Digital Display
0 to1000 ppm
Sensitivity: ±10 ppm
Resolution: ±1 ppm
Accuracy:
Typical Conditions
60° F to 90° F (15° C to 32° C)
0 to 2000 ppm: ±50 ppm or ±3% of reading,
whichever is greater
2000 to 10,000 ppm: ± 5% of reading
• Commercial Product Guide • 2002 •
217
Extended Conditions
32° F to 122° F (0° C to 50° C)
0 to 2000 ppm: ±100 ppm or ±5%, whichever is greater
2000 to 10,000 ppm: ±7% of reading, whichever is greater
Pressure Dependence
Add 0.13% of reading per mm Hg decrease from 760
(On board correction, user set)
Annual Drift:
±10 ppm (negligible) with TEMA on
±20 ppm typical with TEMA off
Response Time 0..90% FS
< 2 minutes
Warm-Up Time at 25 C < 2 minutes
Operating Conditions
32° F to 122° F (0° C to 50° C)
0...95% Relative humidity, non-condensing
Storage Conditions
–40° F to 158° F (–40° C to 70° C)
Agency Certification:
FCC Part 15 Class B
Calibration Interval
Five years/zero ppm gas offset adjust
Temperature Sensor:
Thermistor
Standard
No sensor
Optional
User-specified, direct pass-through
connection (consult factory)
Input/Output:
Power (dedicated power supply required)
18 to 36 VAC RMS (root mean square), 50/60 Hz
18 to 42 VDC polarity protected/dependent.
70 mA average,
100 mA peak at 24 VDC
Analog CO2 Output
0 to 10 VDC (100 Ohms output impedance)
4 to 20 mA (RLmax [maximum load
resistance] = 500 Ohms).
Both outputs are available simultaneously
Relay:
Normally Open or Normally Closed (wire either way), gold
fabricated, 2A rating. Adjustable set point, factory set at
1000 ppm, 50 ppm hysteresis
Wiring:
18 to 20 AWG (American Wire Gage) stranded copper wire
only. Two wires each for power, analog output, relay and
optional thermistor
218
• Commercial Product Guide • 2002 •
Commercial Products
T58 Communicating Room Sensor
MODE FAN
Carrier’s T58, communicating room sensors are wall-mounted,
low-voltage sensors which communicate room temperature set
point changes and time schedule overrides to the controller that
operates the HVAC (heating, cooling and ventilation)
equipment.
The T58 sensor provides a custom Liquid Crystal Display
(LCD) with universally recognized icons and 4 push-buttons
allowing user interface and feedback capabilities. During power
interruption, the T58 sensor stores configuration parameters in
non-volatile memory, allowing coordinated control to resume
after power is restored.
Features
The T58 Communicating room sensor provides the following
features and benefits:
• Single unit user interface operation
• Space temperature display from onboard thermistor
• Set point adjustment using data from attached device
• Occupancy mode override of attached device
• Outside air temperature display
• Non-volatile memory allowing retention of user
settings/configurations during power outages
• Configurable display
• User-friendly operations
• Universal LCD icons
• CCN Communications
• Fahrenheit or Centigrade
• Display of attached device type
• Display/change fan speed
• Display attached devices mode
Specifications
• Compatible with ComfortID™ air terminals, fan coil
controller and retrofit rooftop controller
• User control mode disable feature with up to 4 hours of
occupancy override configured in attached device.
• Heating and cooling set points adjustment
• Display features mode, status, and occupancy override status
The T58 sensor has four raised buttons – two below the LCD
display window labeled MODE and FAN respectively, and two
unlabeled buttons to the right of the LCD display, which are
used to invoke the increment and decrement functions.
Following are the functions of T58 sensor:
• Select/change installer options
• Read/change current fan speed
• Read current controller operating mode
• Read/change heating or cooling set point value
• Initiate time schedule override
• Display network outside air temperature
The following list identifies the data values and graphics that
are shown in the T58 LCD display window depending on which
function is requested of the sensor:
• Space temperature value (default display)
• Heating or cooling set point value (attached device)
• Current operating mode (attached device)
• Current fan speed (attached device)
• Network outside air temperature
• Time schedule override in effect
• Error indications
The T58 sensor complies with FCC Part 15, Subpart J.
• Commercial Product Guide • 2002 •
219
Physical characteristics
Dimensions (L x W x D):
4.3" x 2.7" x 0.875"
Appearance:
Plastic Material, White Color, Textured Cover
Weight:
0.15 lb maximum
Power requirement
24 va RMS nominal (18 min. to 30 max. vac)
Power consumption is less than 100 ma @ 24 vac RMS
RS-485 system connection
Environmental requirements
Temperature:
Operating: 32° F to 104° F (0° C to 40° C)
Non-Operating: –40° F to 136° F (–40° C to 57° C)
Humidity: 10 to 95% Relative Humidity, non-condensing
Safety requirements
EN 60335-1 Generic Appliance Safety Standard
EN 60335-2-40 HP/AC Safety Standard
Electrical characteristics
Inputs: 24 VAC supply voltage drawing .1 amp maximum
and .05 amps minimum
Temperature control
Determined by attached controller
220
• Commercial Product Guide • 2002 •
Commercial Products
CO2 and Space Temperature
Sensors
The CO2 and Space Temperature Sensors are comprised of two
sensors housed in one unit. They are designed to monitor
carbon dioxide (CO2) levels in the air and measure the interior
building temperature.
The sensors use Single Beam Absorption Infrared™ Diffusion
technology to measure CO2 levels and a 10K thermistor for
measuring space temperature. The CO2 levels can then be used
as input into a CCN (Carrier Comfort Network) controller to
control the ventilation damper position and ensure an adequate
level of outside air in the building as well as space temperature
control function.
Features
The CO2 and space temperature sensors offer the
following advantages:
• Combined CO2 measurement range of 0 to 2000 ppm
and a 10K thermistor temperature sensor
• Patented ABC Logic™ (Automatic Baseline Calibration)
self-calibration provides a 5-year calibration interval
• Sleek, low profile
• Mounting plate with terminal blocks for easy installation
and wiring
• Versatile sensor options including 4 to 20 mA or
0 to 10 v output
• Set point adjustment potentiometer with a nominal resistance
of 100K Ohm ±10% (available on P/N 33ZCT56CO2)
• Push button override
• Commercial Product Guide • 2002 •
221
CO2 AND SPACE TEMPERATURE SENSOR SPECIFICATIONS
P/N 33ZCT55CO2 AND 33ZCT56CO2
Sensing Method
Sample Method
Measurement Range
Sensitivity
Accuracy
Pressure Dependency
Response time 0 to 90% Step Change
Warm-up Time @77° F (25° C)
Operating Conditions
Storage Temperatures
Agency Certification
Calibration/Interval
Power
Analog CO2 Output
Temperature Sensor
Single Beam Absorption Infrared™
Patented TEMA self-calibration software and 10K
temperature sensor
Diffusion
0-2000 ppm
±20 ppm
±100 ppm
60° F to 90° F (15° C to 32° C),760 mmHG
0.13% of reading per mmHg
<2 minutes
<2minutes
60° F to 90° F (15° C to 32° C)
0 to 95% Relative humidity, non-condensing
-40° F to 158° F (-40° C to 70° C)
FCC Part 15 Class B/CE/CA Energy Commission
Five years with TEMA
Single point calibration via push button and LED
18-30 VAC RMS, 50/60 Hz – half wave rectified (dedicated)
18-42 VDC polarity protected (dedicated)
1.75 VA maximum average power
3.25 VA peak power
4 to 20 mA (RImax = 500 Ohms) and
0 to 10 v (source 100 mA, Sink 10 mA)
10 K Ohm Thermistor, 10 K Ohm ±2% @77° F (25° C)
Temperature Sensor (P/N 33ZCT56CO2 Only) Equipped with a slide potentiometer
Positions
Resistance
Left (Stop)
0 K (+5 K)
Right (Stop)
100 K (±10 K)
Override Control
Equipped with a push button that when depressed shorts
out its internal thermistor
Reliability
Meets applicable Carrier reliability requirements
LEGEND
RI
— Maximum Load Resistance
RMS — Root Mean Square
TEMA — Time Extended Measurement Algorithm
CO2 AND SPACE TEMPERATURE SENSOR ELECTRICAL CONNECTIONS
CONNECTOR
J7
J8
RJ-14
222
TERMINAL DESIGNATION
5-pin wire screw terminal for CO2 Sensor
(Screw terminal accept 18-22 AWG)
1—24 VAC (+) (dedicated)
2—24 VAC (-) (dedicated)
3—0 to 10 VDC CO2 Output
4—Common CO2 Output
5—4 to 20 mA CO2 Output
6-pin wire screw terminal for temperature
sensing and communication
1—Thermistor
2—Common
3—Offset potentiometer (P/N
33ZCT56CO2 only)
4—CCN(-)
5—CCN(+)
6—CCN Ground
RJ-14 Connector (accessible from
outside of case)
1—Not used
2—CCN(+)
3—CCN Ground
4—Not used
5—CCN(-)
6—Not used
• Commercial Product Guide • 2002 •
Commercial Products
VVT® Monitor Thermostat
w/Timeclock
Comfort System Components
VVT Monitor Thermostats feature push-button programmability
and a straightforward, categorized configuration method.
Monitor Thermostats control the HVAC unit based on demand
from all zones, combining precise temperature control with
networked communications. Locking cover clips eliminate the
need for unsightly lock boxes. In addition, access security
prevents nuisance tampering.
Features
• Fan/filter status
• Set point range: 50° F to 99° F
• Scheduling:
365-day/8 time periods per day/one minute increments
• Up to 32 zones of control
• Auto/Manual changeover
• No batteries
• IAQ operation
• Available without timeclock also
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 3/8" x 3 7/8" x 7/8"
Appearance:
Plastic Material; Taupe Color; Textured Cover
Weight:
14 oz.
Electrical Characteristics
Input Volts/Amps: 10-11
VDC/100 mA from
Damper Board or
Unit Controller
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
223
Commercial Products
VVT® Bypass Controller
Comfort System Components
Part of the VVT Bypass System, the Bypass Controller controls
the bypass damper that allows airflow into either the return
air duct or plenum. Changeover mode protects heating/cooling
unit by preventing air at extreme temperatures from entering
the unit between modes. Also compensates for changes in the
supply air duct static pressure, helping to ensure proper
airflow and promote smoother, quieter system operation. The
bypass controller must be used with either the 33CSPS-01 or
33CSPS-02 pressure sensor.
Features
• Adjustable pressure set point for system operation
• Auto temperature changeover cycle between modes
• Centralized system damper control for test and balance setup
• Sensor input: IAQ sensor
• Pressure range: 0 to 2.0 in. wg. (0.001 setpoint increment)
• Central indoor air quality (IAQ) monitoring and alarming
224
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 3/8" x 3 7/8" x 7/8"
Appearance:
Plastic Material, Taupe Color, Textured Cover
Weight:
14 oz.
Electrical Characteristics
Input Volts/Amps: 10-11
VDC/100 mA from Bypass
Damper Board
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
Commercial Products
VVT® Zone Controller
Comfort System Components
The VVT Zone Controller continuously monitors zone
temperature conditions, electronically communicating data
- zone demand, overrides, diagnostic information and more to the VVT Monitor Thermostat.
The Zone Controller allows each occupant to control the
temperature comfort within their space.
Features
• Individual time schedule and occupied setpoints per zone
• Four levels of security for thermostat programming
• Remote space temperature sensing and averaging
• Auxiliary heat control w/outside air temp lockout
• No batteries required
• IAQ zone operation capability
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 3/8" x 3 7/8" x 7/8"
Appearance:
Plastic Material, Taupe Color, Textured Cover
Weight:
14 oz.
Electrical Characteristics
Input Volts/Amps: 10-11
VDC/100 mA from
Zone Damper Board
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
225
Commercial Products
VVT® Zone Controller
Pressure Independent
Comfort System Components
The Pressure Independent Zone Controller is used in
applications where zone independent operation is required.
The 33CSZC-PI must be used with either the 33CSPS-01
or 33CSPS-02 pressure sensor (depends on the pressure
range, see specs for the pressure sensor) to control either
CFMs or static pressure. The zone controller can be used
to control supplemental heat as well as series/parallel fan
powered mixing boxes.
Features
• Pressure independent operation
• Control supplemental heat
• Series/parallel fan powered mixing box operation
• Zone IAQ capability
226
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 3/8" x 3 7/8" x 7/8"
Appearance:
Plastic Material, Taupe Color; Textured Cover
Weight:
14 oz.
Electrical Characteristics
Input Volts/Amps: 10-11
VDC/100 mA from
Zone Damper Board
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% - 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
Commercial Products
VVT® Universal Relay Pack
Comfort System Components
The Universal Relay Pack is used in VVT (variable
volume/variable temperature) systems as an interface
between the HVAC unit and the damper actuator. It can be
used on cooling only, heating/cooling and heat pump units (it
is not used in monitor-only applications). In addition, the
Universal Relay Pack can be used for supplemental heat and
fan relays on zone controllers.
Features
• Allows communication between HVAC Wire unit
and damper actuator Can be used for cooling only,
heating/cooling or heat pump units
• Can also be used for supplemental heat and fan relays
on zone controllers
• Can be mounted in the damper actuator or in a
remote enclosure
Specifications
Wire
Relay Pack comes with factory-installed 2-conductor power
cable and 7-conductor relay connector cable
Relay Pack to HVAC unit
4-, 7- or 9-conductor, 18 ga. wire, depending on application
and type of unit
Relay Pack to fan mixing box or supplemental heat
4- or 6-conductor, 18 ga. wire, depending on application
and type of unit
Relay Pack to damper actuator, installed in
damper actuator
No field wiring required
Relay Pack to damper actuator, installed in remote location
Add length with 18 ga. standard or plenum-rated wire
Maximum distance between Relay Pack and
damper actuator
18 ga. wire - 100 ft.
Operating Temperature/Relative Humidity
32° F to 158° F/10% to 95%, non-condensing
• Commercial Product Guide • 2002 •
227
Commercial Products
Pressure Sensor 0-0.5” WC
Comfort System Components
The 33CSPS-01 is used on the VVT® Comfort System for
bypass control or with a Zone Controller for pressure
independent control. The pressure sensor must be used to
control the static pressure within a VVT system to maintain a
constant airflow over the coil, and to prevent excessive static
pressure within the duct system.
Features
•
•
•
•
•
Easy installation
No calibration required
Performs auto changeover with Bypass Controller
Highly accurate pressure sensor
Maintains maximum and minimum CFMs on pressure
independent systems
228
Specifications
Physical Characteristics
Dimensions (LxWxD):
4 9/16" x 2 3/8" x 1 1/4"
Appearance:
Case (LxWxD):
8 5/8" x 6 1/8" x 2"
Electrical Rating
24VAC, 0.5VA
Environmental Requirements
Maximum Operating Temp/Humidity:
32° F to 131° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Pressure Range
0 - 0.5" WC
• Commercial Product Guide • 2002 •
Commercial Products
Pressure Sensor 0.5-2.0” WC
Comfort System Components
The 33CSPS-02 is used on the VVT system for bypass
control or with a Zone Controller for pressure independent
control. The pressure sensor must be used to control the static
pressure within a VVT system to maintain a constant airflow
over the coil, and to prevent excessive static pressure within
the duct system.
Features
•
•
•
•
Easy installation
No calibration required
Performs auto changeover with Bypass Controller
Highly accurate pressure sensor
Specifications
Physical Characteristics
Dimensions (LxWxD):
4 9/16" x 2 3/8" x 1 1/4"
Appearance:
Case (LxWxD):
8 5/8" x 6 1/8" x 2"
Electrical Rating
24VAC, 0.5VA
Environmental Requirements
Maximum Operating Temp/Humidity:
32° F to 131° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Pressure Range
0.5 - 2.0" WC
• Commercial Product Guide • 2002 •
229
Commercial Products
Filter Status Switch
Comfort System Components
The Filter Status Sensor Switch is used in VVT® and TEMP
Comfort System applications where a dirty filter alarm is
received. This switch measures pressure differential, thus
providing timely detection of a dirty filter situation. Clean
filters ensure proper system operation to maximize efficiency
and help eliminate IAQ problems. This switch interfaces to the
relay pack of the VVT Monitor or TEMP Monitor Thermostat.
Features
•
•
•
•
•
Easy to install
Setpoint adjustment
2" maximum pressure
Used on VVT and TEMP system
Used on Comfort Controllers
Specifications
Physical Characteristics
Dimensions (LxWxD):
4 11/16" x 3 9/16" x 1 9/16"
Appearance:
Black Case with Hi and Lo Connections
Weight:
4 oz.
Electrical Rating
10 VDC/100 mA
Environmental Requirements
Maximum Operating Temp:
190° F
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%
230
Compatibility
For use with air only
Pressure Connection
Dual Size for 1/8" or 3/16" ID
Rubber/Vinyl Tubing
Pressure Range and Maximum
0. 17 to 0.55" WC
2.0 psig maximum
Wiring Connections
(3) 1/4" Quick Connects;
Common, NC, NO
2 Conductor, 18 Gauge
Stranded (field supplied)
Common and NO used for System Interface
Setpoint Adjustment
Field Adjust with External Slotted Head Screw
Operating Characteristics
Housing:
Glass Filled PBT (polybutylene terephthalate)
Diaphragm:
Molded Silicon Rubber
Calibration Spring:
Blue Spring Steel
Operating Position:
Diaphragm Vertical
• Commercial Product Guide • 2002 •
Commercial Products
Fan Status Sensor Switch
Comfort System Components
The Fan Status Sensor Switch is used in VVT® and TEMP
Comfort System applications where fan status needs to be
verified. This helps in diagnosing system problems from
remote sites. Alarms will be generated when the fan has failed
to operate. The switch interfaces to the relay pack of the
VVT/TEMP system.
Features
•
•
•
•
•
Easy to install
Setpoint adjustment
2" Maximum pressure
Used on VVT or TEMP system
Used on Comfort Controllers
Specifications
Physical Characteristics
Dimensions (LxWxD):
4 11/16" x 3 9/16" x 1 9/16"
Appearance:
Black Case with Hi and Lo Connections
Weight:
4 oz.
Electrical Rating
10 VDC/100 mA
Environmental Requirements
Maximum Operating Temp:
190° F
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%
Compatibility
For use with air only
Pressure Connection
Dual Size for 1/8" or 3/16" ID
Rubber/Vinyl Tubing
Pressure Range and Maximum
0.5" to 7.5" WC
2.0 psig maximum
Wiring Connections
(3) 1/4" Quick Connects;
Common, NC, NO
2 Conductor, 18 Gauge
Stranded (field supplied)
Common and NO used for System Interface
System Interface
Setpoint Adjustment
Field Adjust with External Slotted Head Screw
Operating Characteristics
Housing:
Glass Filled PBT (polybutylene terephthalate)
Diaphragm:
Molded Silicon Rubber
Calibration Spring:
Blue Spring Steel
Operating Position:
Diaphragm Vertical
• Commercial Product Guide • 2002 •
231
Commercial Products
VVT® Rectangular Zone Dampers
Comfort System Components
Carrier’s VVT Comfort System Zone Dampers are used with
VVT Monitor Thermostats, Bypass Controllers and Zone
Controllers. These dampers are an integral part of the VVT
Bypass Controller system. They deliver air to the space in a
quiet, efficient manner. Each damper is equipped with a
temperature sensor and damper circuit board. The high quality
construction ensures a long operating life.
Features
• Counterclockwise and clockwise damper rotation
• Configurable minimum and maximum open damper positions
• Pressure independent control
• Integral supply air temperature sensor
• Indoor air quality sensor (IAQ) input point
• Link up to four dampers in master/slave configuration
232
Specifications
Physical Characteristics
Duct Housing: 24 Ga.
Damper Blade: 20 Ga.
Duct Connection: Standard “S”
Lock & Drive Cleats
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%
Storage Temp/Relative Humidity:
-40° F to 130° F/10% to 95%
Electrical Characteristics
Input Power Requirement: 24VAC, 20VA, (25VAV
with Optional Sensors) 60 Hz (Field Supplied)
Output Power: 10 VDC to Monitor, Bypass, Zone
Controller, Unit Controller
Operating Performance
Torque Rating: 18 in. lbs.
Degree of Rotation: 60°
Pressure Rating: 1" WC static
• Commercial Product Guide • 2002 •
Commercial Products
VVT® Round Zone Dampers
Comfort System Components
Carrier’s VVT Comfort System Zone Dampers are used with
VVT Monitor Thermostats, Bypass Controllers and Zone
Controllers. These dampers are an integral part of the VVT
system. They deliver air to the space in a quiet, efficient
manner with the help of an elliptical damper blade. Each
damper is equipped with a temperature sensor and damper
circuit board. The high quality construction ensures a long
operating life.
Features
• Counterclockwise and clockwise damper rotation
• Configurable minimum and maximum open damper positions
• Pressure independent control
• Integral supply air temperature sensor
• Indoor air quality sensor (IAQ) input point
• Link up to four dampers in master/slave configuration
Specifications
Physical Characteristics
Spiral Metal Duct Housing: 24 Ga.
Elliptical Damper Blade: 20 Ga.
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%
Storage Temp/Relative Humidity:
-40° F to 130° F/10% to 95%
Electrical Characteristics
Input Power Requirement:
24VAC, 20VA, (25VA with Optional Sensors)
60 Hz (Field Supplied)
Output Power:
10 VDC to Monitor, Bypass, Zone Controller,
Unit Controller
Operating Performance
Torque Rating:
18 in. lbs.
Degree of Rotation:
60°
Pressure Rating:
1" WC static
• Commercial Product Guide • 2002 •
233
Commercial Products
TEMP Monitor Thermostat
with Timeclock (Single Zone Control)
Comfort System Components
TEMP Monitor Thermostats can be linked together for
centralized system control from a single entry point. The
built-in timeclock makes custom programming fast and easy.
Thermostats feature a simple, categorized programming method
and push-button design. Their sleek profile and neutral tone
blend with any decor. The 365-day real-time clock offers auto
adjustment for daylight savings time and leap year. The clock
allows 18 holiday schedules and flexible daily schedules.
Features
• Setpoint range: 50° F to 99° F
• Scheduling: 365-day auto daylight savings/leap year
• Clock power/loss backup time: 10 hours. without battery
• Auto/manual changeover
• No batteries
• IAQ operation
• Fan/filter status
234
Specifications
Physical Characteristics
Dimensions (LxWxD):
7 1/16" x 3 7/8" x 7/8"
Appearance:
Plastic Material,Taupe Color, Textured Cover
Weight:
16 oz.
Electrical Characteristics
Input Volts/Amps: 10-11 VDC/100 mA from Unit Controller
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130°F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
Commercial Products
TEMP Monitor Thermostat
without Timeclock (Single Zone Control)
Comfort System Components
TEMP Monitor Thermostats can be linked together for
centralized system control from a single entry point.
Thermostats feature a simple, categorized programming
method and push-button design that make it easy to meet
individual comfort requirements while managing energy usage.
The thermostats’ sleek profile and neutral tone blend with any
decor. This component must receive time from another
component with a timeclock on the CCN bus.
Features
• Fan/filter status
• Setpoint range: 50° F to 99° F
• Scheduling: 365-day/8 periods per day/one minute increments
• Auto/manual changeover
• No batteries required
• IAQ operation
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 3/8" x 3 7/8" x 7/8"
Appearance:
Plastic Material, Taupe Color, Textured Cover
Weight:
14 oz.
Electrical Characteristics
Input Volts/Amps: 10-11 VDC/100 mA from Unit Controller
Environmental Requirements
Operating Temp/Relative Humidity:
32° F to 130° F/10% to 95%, non-condensing
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%, non-condensing
Agency Approvals
FCC Part 15, Subpart J, Class A
• Commercial Product Guide • 2002 •
235
Commercial Products
33CSUCE-06 Unit Controller
with Economizer
Comfort System Components
The 33CSUCE-06 is the relay pack required for the interface
between the TEMP monitor thermostat and the cooling/heating
equipment. Controls two stages of heating and cooling: fan
operation and reversing valve. Allows various sensor inputs,
such as fan status, filter status, humidity, duct temperature, DX
coil temperature, and outside air temperature.
Features
• Two-stage heating and cooling, unit fan and economizer relay
• Outdoor temperature duty rated
• Sensor input: IAQ, fan status, filter status or humidity,
supply air temp, DX coil temp and outside air temp
236
Specifications
Physical Characteristics
Dimensions (LxWxD):
8 112" x 6" x 2"
Appearance:
Metal Enclosure with Internal
Circuit Board
Weight:
22 oz.
Electrical Characteristics
Power Input Requirements:
24VAC, 60 Hz, 10 VA
Power Output Requirements:
10 VDC to Monitor
Output Relay Rating:
6 Pilot Duty at 24VAC, 1.0 Amp
Agency Approvals
FCC Part 15, Subpart J, Class A
Environmental Requirements
Operating Temp/Relative Humidity:
-29° F - 158° F/10% to 95%
Storage Temp/Relative Humidity:
-40° F to 158° F/10% to 95%
• Commercial Product Guide • 2002 •
Commercial Products
Remote Duct Sensor
Comfort System Components
The Remote Duct Sensor or supply air sensor is used in
applications where it is desirable to monitor supply air
temperature for optimized system operation. It can be used on
the VVT® Monitor Thermostat, bypass controller or TEMP
Monitor Thermostat. It interfaces to the relay board of the
TEMP/VVT Monitor Thermostat.
Features
• 30° F to 180° F operating range
• Easy to install
Specifications
Physical Characteristics
Dimensions (LxWxD):
5 1/4" x 3" x 4 3/4"
Shipping Weight:
2 lbs.
Operating Range
30° F to 180° F
Maximum length from monitor
1,000 ft.
Wiring
2 Wire - 18 ga.
• Commercial Product Guide • 2002 •
237
Commercial Products
Remote Room Sensor
Comfort System Components
The Remote Room Sensor is used in applications where it is
desirable to monitor space temperature with the Monitor
Thermostat, Bypass Controller or Zone Controller remotely
located in a panel or closet. The Remote Room Sensor
interfaces to the connector board of the thermostat. Room
temperature can be averaged using multiple (up to 4) remote
room sensors.
Features
• 30° F to 180° F operating range
• Easy to install
238
Specifications
Physical Characteristics
Dimensions (LxWxD):
1 3/4" x 1 3/8" x 3/4"
Shipping Weight:
2 lbs.
Operating Range
30° F to 80° F
Maximum Length from Thermostat
1,000 ft.
Wiring
2 Wire - 18 ga.
• Commercial Product Guide • 2002 •
Commercial Products
Outside Air Sensor
Comfort System Components
The Outside Air Sensor is used in applications where the
outside air needs to be monitored either for information
purposes or to control the cooling/heating equipment. The
equipment can be locked out based on outside air temperature.
When a Carrier Comfort Network exists, one outside air sensor
may be used to broadcast the outside air temperature
information to other devices.
Features
• 0° F to 150° F operating range
• Easy to install
Specifications
Physical Characteristics
Dimensions (LxWxD):
4 1/2" x 2 3/4" x 1 1/2"
Shipping Weight:
2 lbs.
Operating Range
0° F to 150° F
Maximum Length from Thermostat
1,000 ft.
Wiring
2 Wire - 18 ga.
• Commercial Product Guide • 2002 •
239
As the world leader in Heating,
Ventilation and Air Conditioning,
Carrier is committed to continually
improving the quality of comfort we
provide our customers.
But our level of responsibility
extends well beyond...
Carrier Corporation has identified
six specific areas which directly
impact how we, as a world
manufacturer, balance our
customers’ needs for comfort with
the environment’s needs for
responsible consumption.
These symbols graphically represent
our six areas of concentration and
will serve as visual reminders of
the importance of managing our
finite resources.
Each one of us at Carrier
Corporation believes that, for
generations to come, success will
not only be measured by the quality
of our products and systems, but
also by how we have improved the
quality of life.
For more information contact your nearest
Carrier Representative, call 1-800-CARRIER,
or visit our website at www.carrier.com and click
on Commercial/Industrial Heating and Cooling Systems.
© 2002 Carrier Corporation 08/02
Catalog No. 811-10120
Manufacturer reserves the right to discontinue
or change at any time, specifications or designs
without notice or without incurring obligations.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement