Bosch | Appliances Smoke Alarm SM 210 LSN RW | User's Manual | Bosch Appliances Smoke Alarm SM 210 LSN RW User's Manual

PRODUCT INFORMATION
PI - 34.52c
Manual call point SM 210 LSN RW
Seite
Seite
11
601 -4.998.125.088
A2.en / 29.12.2004
ST -FIR/ PRM1 / deh
Product Information SM 210 LSN RW
PI - 32.52c
Table of contents
1.
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2.
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3.
Planning notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3.1
Maximum connectable detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3.2
Standards, guidelines, projecting recommendations . . . . . . . . . . . . .
3
4.
Order list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5.
Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
6.
Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
6.1
Detector test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
7.
Installation notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
7.1. Fixing details for the indoor versions (IP54) . . . . . . . . . . . . . . . . . . . . .
6
7.2. Fixing details for the outdoor version (IP67) . . . . . . . . . . . . . . . . . . . . .
7
7.3. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
8.
9
Notes for maintenance and service . . . . . . . . . . . . . . . . .
8.1. Further documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
8.2. Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
9.
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
10. Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
11. Memos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Seite 2 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
1.
PI - 32.52c
Product description
Call points SM 210 LSN RW are used for manual alarming.
Manual call points SM 210 LSN RW are used within the Local Security Network
LSN in association with fire detection central units.
Manual call points SM 210 LSN RW are available in 3 versions:
- SM 210 LSN RW, with back box for indoor surface mounting
- SM 210 LSN RW, with bezel for indoor flush mounting
- SM 210 LSN RW, with back box for outdoor surface mounting
2.
Features
D Alarm initiating by pushing (breaking) the glass plate
⇒ injury protection by foilcoated glass plate
D Detector request routines with evaluation and multi data transmission
D Detector identification and address reported at the fire panel in the event of an
alarm for a faster fire localization.
D Alarm indication at the detector via a flashing red LED
3.
Planning notes
D Manual call points should be installed in easy visible and accessible places.
D Manual call points should be illuminated adequately by daylight or another light
source (inclusively safety light if present).
D Manual call points should be installed in rescue- and escaping corridors (i.e. exits,
passages, stairways).
3.1. Maximum connectable detectors
Because of the different current consumption of LSN elements out of the LSN dataline the maximum current consumption value per LSN loop is absolute to aboden.
For limit values please refer to the product information of the used fire detection
central unit.
3.2. Standards, guidelines, projecting recommendations
See standards, guidelines and projecting recommendations for installation place
and so on.
Heed the regulations of the local fire brigades.
Seite 3 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
4.
PI - 32.52c
Order list
Order number DU*
Designation
4.998.098.964 ST Manual call point SM 210 LSN RW, colour red, with test key
and back box for indoor surface mounting
Manual call point as per UL / LPC - standard.
4.998.098.965
ST
4.998.104.058
ST
4.998.103.969
ST
Manual call point SM 210 LSN RW, colour red, with test key
and bezel for indoor flush mounting.
Manual call point as per UL / LPC - standard.
Manual call point SM 210 LSN RW, colour red, with test key
and back box for outdoor surface mounting
Manual call point as per UL / LPC - standard.
Spare glass for SM 210 LSN RW / SM 120 RW
*DU = delivery unit / ST = Piece
5.
Construction
5
3
1
8
2
Pos.
1
2
3
4
5
6
7
8
9
4
6
7
9
Designation
detector front plate
alarm indication (LED)
glass plate with labeled protection foil
mechanism for alarm reset and detector test
micro switch
detector housing
hole for under plaster cable feed
template for cable glands
back box
Seite 4 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
6.
PI - 32.52c
Functional description
After pushing in the glass plate (1) the alarm will be released by the knob of the
microswitch (2) and the LED (3) starts flashing.
The reset of the microswitch (2) follows by replacing the glass plate (1).
2
1
5
3
4
Call point without front plate
6.1. Detector test
Shifting the test key into the recess (4) will unlock the retaining collar (5). Therefore
the glass plate (1) shifts downwards and the knob of the microswitch (2) releases an
alarm. The indicating LED (3) starts flashing.
Seite 5 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
7.
PI - 32.52c
Installation notes
Flush call point
The flush call point comes complete with a bezel and will mount onto any standard
U.K. single gang back box with a depth of min. 25mm or directly to a wall. Consideration should be given to the amount of cabling space at the rear of the call point,
i.e. a deeper box or spacer eases installation.
Surface call point
The surface mounting call point comes complete with a back box onto which the
calll point is mounted. There is provision for rear cable entry. By using the template
at the leaflet, cable holes can be drilled into the top or bottom of the back box to
accept one or two cable glands - Max. dia. 20mm.
7.1. Fixing details for the indoor versions (IP 54)
View: back box inside
View: bezel
87
∅4
107
∅4
20
36
60
100
Cable feed over plaster,
via cable glands
See template at the call
point leaflet for the hole
positions of cable glands.
TOP
Cable feed under plaster for
detector mounting with back
box and rear cable entry
TOP
Seite 6 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
PI - 32.52c
7.2. Fixing details for the outdoor version (IP 67)
View: back box with
mounted call point
75
View: back box inside
20
97
45
Cable feed over plaster, via cable glands
∅4
TOP
87
111
Seite 7 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
PI - 32.52c
7.3. Connection
LSN
LSN
a2
LSN2 b2
a1
LSN1
b1
+U
0V
Detector backside
Back box for surface mounting
Connecting terminals
+U
rt
0V
sw
a2
ws
b2
ge
a1
ws
b1
ge
power supply
l ffor other
th LSN-Elements
LSN El
t i.e.
i LSN-Couplers
LSN C
l
LSN2
LSN1
coming from the fire panel or an upstream LSN-Element
going to the next LSN-Element
Seite 8 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
8.
PI - 32.52c
Notes for Maintenance and Service
Maintenance and service works should be undertaken regularly by skilled and trained personnel in accordance with the national legislative requirements.
Faulty detectors under the warranty terms will be replaced free of charge.
8.1. Further Documentation
Order number
DU*
3.002.218.156
ST
Connection manual AHB BMZ / EMZ
3.002.218.155
ST
Connection manual AHB UGM
*DU = delivery unit,
Designation
ST = piece
For those with access authorization, on the Bosch ST ExtraNet at
www.boschsecurity.com/emea/fire
the current information for each product, as well as the installation instructions
supplied with the device, are available for download as a PDF file.
8.2. Disposal
Defective manual call points will be completely replaced and should be
disposed according to the legal requirements.
9.
Technical data
Voltage rating (LSN):
10V DC . . . 31V DC
Current consumption (LSN):
0.4mA
IP Rating (as per EN 60529):
IP 54 (indoor versions)
IP 67 (outdoor version)
Environmental temperature:
- 25°C . . . +65°C
Environmental class (VdS):
III
Dimensions (H x B x T):
Indoor Versions
87 x 87 x 53mm (surface mounting)
87 x 87 x 20mm (flush mounting)
107 x 107 x 36mm (flush mounting with bezel)
Outdoor Version
111 x 111 x 65mm (surface mounting)
Housing material:
Plastic, ABS
Colour:
Red (RAL 3001)
Weight:
approx. 150g
LPC- Approval number:
378c
Seite 9 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
PI - 32.52c
10. Abbreviatons
AHB
= Anschaltehandbuch / Connection manual
BMZ = Brandmeldezentrale / Fire panel
BM
= Brandmelder / Fire detector
DIN
= Deutsches Institut f. Normung / German institute for standardization
EMZ = Einbruchmeldezentrale / Intrusion panel
EN
= Europa Norm / European standard
GMZ = Gefahrenmeldeanlage / Security system
KI
= Kundendienst Information / Maintenance information
LED
= Light emittend diode
LPC
= Loss prevention council
LSN
= Local Security Network
SM
= Springknopfmelder / Manual call point
UGM = Universelle Gefahrenmeldezentrale (Universal security system panel
VDE
= Verband Deutscher Elektrotechniker e.V. /
Association of German Electrotechnicians
Seite 10 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Product Information SM 210 LSN RW
PI - 32.52c
11. Memos
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
--------------------------------------------------------------------------------
Seite 11 von 12
601-4.998.125.088
A2.en / 29.12.2004
ST-FIR/ PRM1 / deh
Bosch Security Systems
Robert -Koch -Str. 100
D-85521 Ottobrunn
Info -Service
Telephone: +49 89 6290 - 1039
Fax:
+49 89 6290 - 1039
www.boschsecurity.com
info.service@de.bosch.com
Page 12 of 12