Smaller Lighter More Powerful
Sealed Weather-Proof Construction
Smaller
Lighter
More Powerful
Made in USA
Uninterruptible Power Supply
Military-Grade UPS
Uninterruptible Power Supply
SynQor’s UPS is designed for the extreme environmental and demanding electrical conditions of Military/Avionics
applications. SynQor’s UPS incorporates field proven high efficiency designs and rugged packaging technologies.
This UPS will accept a wide range of input voltage and frequency values while delivering a well-conditioned AC
output to the load. Its use of lithium polymer batteries permits the lowest profile and lowest weight solution in its
power class. It is designed and manufactured to comply with a wide range of military standards. Options include a
DC output and the ability to also draw power from a military standard 28VDC input.
UPS Product Features
Options
Sealed, weather-proof, shock-proof construction
Military Tough, Die-Cast Aluminum Chassis
1250W-1500VA; 2500W-3000VA output power
>10 minute run-time at full power
Full power operation -20°C to +55°C (Storage: -20°C to +65°C)
True on-line double conversion
Hot swappable internal battery pack (lithium polymer)
Universal AC input: 80-265VAC; 47-65Hz
Dual input: AC and optional DC
Cold-start with no AC or DC input connections
Power factor correction at AC input
Pure sinusoidal AC output voltage (115VAC, 60Hz)
Handles 0.0—1.0 power factor loads and non-linear loads
User I/O and Configuration signal ports
Up to 3 units can be combined for higher power, voltage or a
3-phase AC output
1U high rack mount unit (17” x 21.6”) UPS-1500
2U high rack mount unit (17” x 21.6”) UPS-1500
2U high rack mount unit (17” x 22.2”) UPS-3000
Low weight: 32 lbs. (UPS-1500 1U including battery)
Low weight: 50 lbs. (UPS-1500 2U including battery)
Low weight: 65 lbs. (UPS-3000 including batteries)
DC input (28Vnom) for dual source
2U Extended battery pack gives >24 minutes of
run‑time (UPS 1500)
Wide-range AC input frequency: 47Hz to 800Hz
115Vrms or 230Vrms AC output
50Hz, 60Hz, or 400Hz output
DC1: Auxiliary isolated DC output (up to 500W)
DC2: High power DC output (up to 1250W)
parallelable for higher power
Total AC & DC1 & DC2 output power = 1250W
(UPS-1500)
Shipboard version with floating neutral wire
Rack mounting style
Specification Compliance
UPS units are designed to meet:
MIL-STD-704F - Aircraft Electrical Power
Mil-STD-1399-300B - Interface Shipboard
MIL-STD-1275D - Vehicle Electrical Power
MIL-STD-461F - Electromagnetic Interference
MIL-STD-810G - Environmental Engineering
block diagram
AC
INPUT
DC
INPUT or
DC2 OUTPUT
AC to DC
w/ PFC
and
ISOLATION
ISOLATED
INVERTER
AC
OUTPUT
ELECTRONIC
SWITCH /
Non-Isolated
DC-DC Converter
ISOLATED
DC/DC
CONVERTER
DC
OUTPUT
(OPTIONAL)
(OPTIONAL)
BATTERY
with
CHARGER
and
ELECTRONIC SWITCH
BULK ENERGY
STORAGE
CAPACITOR
1.25kW 1U Model
SynQor Headquarters 155 Swanson Road, Boxborough, MA 01719-1316 USA | 1.888.567.9596 (USA only) | www.synqor.com
TECHNICAL eLECTRICAL CHARACTERISTICS
INPUT CHARACTERISTICS
UPS-1500 / UPS-3000
ENVIRONMENTAL CHARACTERISTICS MIL-STD-810G
Voltage
80-265Vrms*
Temperature Methods 501.5, 502.5
Frequency
47-65Hz
Operating Temperature
-20°C — +55°C
(47-800Hz Optional)
Storage Temperature
-20°C — +65°C
>0.98 at 47-65Hz
Altitude Method 500.5
>0.97 at 400Hz
Operating
>0.93 at 800Hz
Non-operating
Operating AC Input
Input Power Factor
MTBF
100kHrs
Maximum Input Current Continuous 20A / 40A (full load, 85Vrms)
Electromagnetic Capability
AC Input Circuit Breaker Rating
MIL-217F Ground Benign, Ta=25°C
0 - 15,000 ft
0 - 40,000 ft
MIL-STD-461F
CE101
30 Hz - 10 kHz
(* Power Derating to 80% below 90Vrms)
CE102
10 kHz - 10 MHz
Operating DC Input (Optional)
CS101
30 Hz - 150 kHz
CS106
10 kHz - 40 GHz
Continuous Maximum Input Current 62A / 124A (full load, 22V)
CS114
10 kHz - 200 MHz
Transient Maximum Input Current
75A / 150A
CS116
10 kHz - 100 MHz
OUTPUT CHARACTERISTICS
UPS-1500 / UPS-3000
RE101
30 Hz - 100 kHz
Total Output Power Continuous
1250W / 2500W
RE102
10 kHz - 18 GHz
Voltage
25A / 50A
22-33V
(1500VA) / (3000VA)
RS101
30 Hz - 100 kHz
Maximum DC1 Output Power
510W / 2 x 510W
RS103
2 MHz - 40 GHz
Maximum DC2 Output Power
1250W / 2500W
Environmental Tests
(Note: Available AC power is reduced by power delivered to the DC output)
Shock/Drop
Method 516.6, Procedures 1,4,6
AC Output
Vibration
Method 514.6, CAT 5, 7, 8, 9, 24
AC Output Waveform
Pure Sinusoidal
Fungus
Voltage
115Vrms ± 3%
Salt Fog
230Vrms ± 3%
Sand and Dust
60Hz ± 0.5%
Rain
Method 506.5
50Hz ± 0.5%
EMI
MIL-STD-461F
400Hz ± 0.5%
Humidity
26A / 52A (115Vrms)
Mechanical Vibrations of
13A / 26A (230Vrms)
Shipboard Equipment
Load Power Factor
0-1.0 (leading or lagging)
MECHANICAL CHARACTERISTICS
Total Harmonic Distortion
2%
UPS-1500-S-1U
(1000W / 3000W resistive load)
Chassis Size (H x W x D)
Frequency
Peak Load Current
DC1 Output (optional)
Voltage Regulation
Case Material
± 3% (Over Load & Temperature)
Common Voltage / Power combinations 12V at 42A
=504W
15V at 34A
=510W
(UPS-3000 has two separate DC1 outputs) 24V at 21A
=504W
28V at 18A
=504W
40V at 12.5A
=500W
50V at 10A
=500W
(Other Options Available)
DC2 Output (optional)
Voltage Setpoint
± 3%
No Sharing (UPS-1500 Only)
Voltage Regulation
-2% (Over Load & Temperature)
Common Voltage / Power combinations 24V at 50A
=1200W
28V at 44.6A
=1250W
Droop Share
(Output droops vs. load to allow passive sharing among modules.)
24V Option
Voltage Regulation
28V Option
Voltage Regulation
-15% (Over Load & Temperature)
26V at 0A
22V at 50A / 100A =1100W / 2500W
-13% (Over Load & Temperature)
30V at 0A
26V at 48A / 96A =1250W / 2500W
Designed and manufactured in the United States of America
Total Weight
Method 508.6
Method 509.5
Method 510.5, Procedures 1,2
Method 507.5
Method 528
1.73"(1U) x 17" x 21.6"
Aluminum
32 lbs. (with chassis & battery)
UPS-1500-E-2U
3.33"(2U) x 17" x 21.6"
Chassis Size (H x W x D)
Aluminum
Case Material
50 lbs. (with chassis & battery)
Total Weight
UPS-3000-S-2U
3.40”(2U) x 17” x 22.2”
Chassis Size (H x W x D)
Aluminum
Case Material
65 lbs. (with chassis & battery)
Total Weight
Connectors
UPS-1500 / UPS-3000
AC Input Connector
MS3470L14-4P / CA02COME22-2PB
DC Input Connector
MS3470L18-8P / CA02COME24-10PB
AC Output Connector
MS3470L14-4S / CA02COME22-2SB
DC1 Output Connector
MS3470L14-4SW / CA02COME22-22SB
DC2 Output Connector
MS3470L18-8S / NA
User I/O Ports
HD DB15 Female
Configuration I/O Port
HD DB15 Male
Cooling Exhaust Fans
Sound Pressure Level (SPL)
54 dB(A)
Air Flow
0.67(m3/min) 23.7 CFM
Two / four fans in system, above specs are for each fan separately.
Military-Grade Uninterruptible Power Supply
atus LED
Model Number
Power
UPS-1500-S-1U
(1 Standard Battery)
1250W
1500VA
>10 min.
(>13 min.)
1U
32 lbs.
•
500W DC1
1250W DC2
•
•
•
•
UPS-1500-E-2U
(1 Extended Battery)
1250W
1500VA
>24 min.
(>31 min.)
2U
50 lbs.
•
500W DC1
1250W DC2
•
•
•
•
UPS-3000-S-2U
(2 Standard Batteries)
2500W
3000VA
>10 min.
(>13 min.)
•
2 X 500W DC1
2250W DC2
•
•
•
•
Pack Height
UPS Output Power Battery
Size
On/Off
Switch
Height
Weight
DC Input
(28V nom)
DC Output
Front
Panel
2U
65
lbs.
AC Input
Frequency
Status Indicator Panel
AC Input AC Output AC Output
Floating
Frequency
Frequency
Voltage
Neutral (47-65Hz or (115Vrms or (50Hz, 60Hz
AC Output
or 400Hz))
47-800Hz) 230Vrms)
AC
AC Output AC Output Output
Voltage Neutral Wire Set Point
Freq
DC Input
DC
Output
Voltage
S:Not Installed
D:DC Input
M:DC2 Out 24VDC 00:None
12:12V
w/Droop Share
S:Standard 1U:1.73" L:47-65Hz 1:115Vrms G:Grounded 5:50Hz P:DC2 Out 24VDC 15:15V
24:24V
E:Extended 2U:3.48" W:47-800Hz 2:230Vrms F:Floating
6:60Hz
no sharing
28:28V
N:No Battery
4:400Hz
R:DC2 Out 28VDC 40:40V
w/Droop Share
50:50V
Out 28VDC
Fan
COMM/AUX Ground DC
Fan V:DC2AC
AC Circuit
no sharing
Rear Panel
1500:1500VA
1250W
UPS
3000:3000VA
2500W
DC
Output
Options
Battery RunTime @ Full
Power
(80% Power)
AC
Output
Exhaust
Port
Stud
Input
Exhaust
Input
Additional
Options
000: Standard
0CE: CE Marking
E00: Ethernet /
SNMP
ECE: Ethernet /
SNMP &
CE Marking
Breaker
The DC Input is not available if a DC2 Option is selected. DC2 Options
P & V are only available on the UPS-1500.
(1/4 -20)
For valid part numbers, refer to the website or contact your local sales representative or distributor.
Part Numbering Example: UPS-1500-E-2U-L1G6D28-000, UPS-1500-S-1U-L2G5S00-000, UPS-1500-S-1U-L2G5S00-0CE
Side View
Top View
Hot swappable
battery pack
21.60"
UNIT MOUNTING HOLES
8-32 .250
x26
1.50"
Front View
17.00"
1.73"
Rev A 006-0006128
Status LED
Status Indicator Panel
UPS-1500-1U UNIT
1.73”
1U
Air intakes
17.00"
On/Off
UPS-1500-1U UNIT with DC Input/DC1 Output Options
DC1
Output
Option
AC
Output
Exhaust
Fan
Ethernet I/O USER Ground
DC
Port Port CONFIG Stud
Input
Option
Port (1/4-20) Option
Exhaust
Fan
AC
Input
AC Circuit
Breaker
UPS-1500-1U UNIT with DC1 Output/DC2 Output Options
DC1
Output
Option
AC
Output
Status LED
On/Off
Exhaust
Fan
Status Indicator Panel
Ethernet I/O USER Ground DC2
Port Port CONFIG Stud Output
Option
Port (1/4-20) Option
Exhaust
Fan
AC
Input
AC Circuit
Breaker
UPS-3000-2U UNIT
3.40”
2U
Air intakes
17.00"
UPS-3000-2U UNIT UPS Units with DC Input / DC1 Output Options
DC1 Output Option
AC Output
Exhaust Fans
DC Input Option Ethernet Port Option AC Input
User I/O
Exhaust Fans
AC Circuit Breaker
CONFIG Port Ground Stud (1/4-20)
UPS products are available in a variety of rack mounting and extended battery configurations.
See the website for data sheets with more details.
Military-Grade Expansion Battery Module (EBM)
SynQor’s Military-Grade UPS Expansion Battery (EBM) units are designed for the extreme environmental and
demanding electrical conditions of Military Land, Shipboard, & Aerospace applications. SynQor’s EBM incorporates
field proven high efficiency designs and rugged packaging technologies. This EBM will accept a wide range of input
voltage and frequency values while delivering a DC power source to the UPS. The use of lithium polymer batteries
permits the lowest profile and lowest weight solution in its power class. It is designed and manufactured in
SynQor’s USA facilities to comply with a wide range of military standards.
EBM Product Features
Sealed, weather-proof, shock-proof construction
>45 minute run-time at full power 1250W UPS
>20 minute run-time at full power 2500W UPS
Integral 500W battery charger
Full power operation: -20°C to +55°C
Universal AC input: 80-265VAC; 47-65Hz
Power factor correction at AC input
Dual input (AC and DC)
Cold start with no AC or DC input connections
3 units can be combined for extended run time
User I/O, Ethernet and Configuration signal ports
2U high rack mount unit (17” x 22.28”)
Low weight: 68 lbs.
Specification Compliance
EBM units are designed to meet: (pending)
MIL-STD-704F - Aircraft Electrical Power
Mil-STD-1399-300B - Interface Shipboard
MIL-STD-1275D - Vehicle Electrical Power
MIL-STD-461F - Electromagnetic Interference
MIL-STD-810G - Environmental Engineering
EBM-1000-2U UNIT
3.48”
2U
On/Off
Status Indicator Panel
Air intakes
17.00"
Ethernet Port
DC Output
Exhaust Fan
DC Input
User I/O
CONFIG Port
Ground Stud (1/4-20)
AC Circuit Breaker
Exhaust Fan
UPS
Model Number
EBM-1000-2U
(Expansion Battery Module)
Family
EBM
Options
Power
Battery
Run-Time
@ Full Power
1250W
2500W
>45 min.
>20 min.
Energy
1000: 1000 Watt Hours
AC Input
Height
2U: 3.48”
DC Output
28: 28V DC
Height
Weight
DC Input
(28V nom)
DC Output
AC Input Frequency
(47-65Hz or
47-800Hz)
2U
68 lbs.
•
28V
•
Power
3000: 3000W
AC Input Freq.
L:47-65Hz Single Phase
W:47-800Hz Single Phase
Additional Options
000:Standard
0CE:CE Marking
E00:Ethernet/SNMP
ECE:Ethernet/SNMP & CE Marking
Part Numbering Example: EBM-1000-2U-28-3000-L-000 For valid part numbers, refer to the website or contact your local sales representative or distributor.