operational manual air handling units

operational manual air handling units
OM-1-2015
Published December 2014
OPERATIONAL MANUAL
for the
CERTIFICATION
of
AIR CONDITIONERS
OM-1-2015
Published December 2014
To supersede OM-1-2014 (Dec. 2013)
Editing (date):
Checking (date):
Approval (date):
Arnaud LACOURT
Jean FOURCROY
Compliance Committee for Air conditioners
CPPC
Comes into effect from:
23 July 2014
13 November 2014
9 October 2014
5 December 2014
1 January 2015
Modifications as against last version
No.
Modifications as against last version
1 Updating of Office’s address
2
Updating EN 14511:2013
3
2nd test Rules modification
4 Deleting an unrelevant example for the rerating of the capacities (SCOP)
Section
IV.2.b
IV.3.f
V.4 Table2
This document is strictly reserved for use in the Eurovent Certified Performance
Programmes. Reproduction or translation of any part of the document is forbidden without
written permission from Eurovent Certita Certification.
Published by Eurovent Certita Certification SAS
48-50 rue de la Victoire, 75009
Paris, France
Tel: +33 1 7544 7155
E-mail: [email protected]
AC, OM-1-2015
Published December 2014
Page 2 of 30
p.
2
8-9
11
14
TABLE OF CONTENTS
I.
II.
III.
PURPOSE ________________________________________________________________4
SCOPE __________________________________________________________________4
BASIC OUTLINE OF THE PROGRAMME _______________________________________4
III.1
III.2
III.3
III.4
III.5
IV.
V.
OPERATION OF THE PROGRAMME __________________________________________5
IV.1
Declaration of data .............................................................................................................................. 5
a.
b.
c.
d.
Rated performance data .................................................................................................................................. 5
Certification forms ............................................................................................................................................ 5
Reporting of models ......................................................................................................................................... 6
Basic model group and acoustical family ......................................................................................................... 6
IV.2
Selection of units to be tested ............................................................................................................. 6
a.
b.
c.
d.
e.
f.
g.
h.
Number of units to be tested ............................................................................................................................ 6
Thermal measurements for AC1 ...................................................................................................................... 7
Thermal measurements for AC1 Water Cooled Units, AC2, AC3 and CC ....................................................... 7
Acoustics measurements for AC1, AC2, AC3 and CC ..................................................................................... 8
Acquisition of unit ............................................................................................................................................. 8
Tests at the laboratory ..................................................................................................................................... 8
Report of test results ........................................................................................................................................ 8
Selection, shipment and return......................................................................................................................... 9
IV.3
Failure treatment ................................................................................................................................. 9
a.
b.
c.
d.
e.
f.
Component failure ............................................................................................................................................ 9
Testing at Tol ................................................................................................................................................... 9
Failure to meet the required capacity ratio (variable capacity) ......................................................................... 9
Testing of general performances...................................................................................................................... 9
Penalty tests................................................................................................................................................... 10
Second test .................................................................................................................................................... 10
IV.4
Repeated failures along the test campaigns .....................................................................................10
RE-RATING RULES _______________________________________________________10
V.1
V.2
V.3
V.4
V.5
V.6
V.7
VI.
Application ........................................................................................................................................... 4
Qualifying procedure ........................................................................................................................... 5
Repetition procedure ........................................................................................................................... 5
Failure treatment ................................................................................................................................. 5
Complaint procedure ........................................................................................................................... 5
Rerating of Tol ...................................................................................................................................10
Seasonal efficiency points: rerating of design load ...........................................................................10
Rerating of auxiliary power consumption ..........................................................................................11
Rerating when capacity and/or efficiency fails ..................................................................................11
Rerating of SEER and SCOP ............................................................................................................14
Rerating on acoustic performances ..................................................................................................15
Possible uprating ...............................................................................................................................15
PROMOTION OF THE PROGRAMME _________________________________________15
VI.1
VI.2
By Eurovent Certita Certification .......................................................................................................15
By Participants ..................................................................................................................................16
a.
b.
Display of certification symbol on literature, software and advertising ........................................................... 16
Display of certification mark on production units ............................................................................................ 17
APPENDIX A.
APPENDIX B.
B.I.
B.II.
B.III.
B.IV.
B.V.
B.VI.
CERTIFICATION SCHEDULE ______________________________________18
FORMS ________________________________________________________19
Form AC-1: Submittal for certification ...............................................................................................19
Form AC-2: Technical Data Sheet ....................................................................................................22
Seasonal Efficiency Calculation Sheet..............................................................................................23
Form AC-3: Additional Information Form ..........................................................................................23
Form AC-4: Test result form ..............................................................................................................26
Form AC-5: Re-rate form...................................................................................................................27
APPENDIX C.
CALCULATION METHOD AND IMPLEMENTATION OF MVF _____________28
C.I. General ..............................................................................................................................................28
C.II. Implementation & newcomers ...........................................................................................................28
C.III. Notification of being expelled ............................................................................................................28
APPENDIX D.
ECO-DESIGN AND ENERGY LABELLING ____________________________30
OM-1-2015
Published December 2014
Page 3 of 30
I.
PURPOSE
The purpose of this manual is to prescribe procedures for the operation of the Eurovent
Certified Performance Programme for Air Conditioners in accordance with the Certification
Manual.
II.
SCOPE
The programme for Air Conditioners is divided in four sub-programmes, as it applies to air
conditioners in the following groups:
 Comfort air cooled air conditioners and air/air heat pumps rated up to 12 kW cooling
capacity, except double duct and single duct units (AC1);
 Comfort air conditioners rated from 12 kW up to but not including 45 kW cooling
capacity (AC2);
 Comfort air conditioners rated from 45 kW up to 100 kW cooling capacity (AC3);
 Close control air conditioners up to 100 kW, direct expansion and chilled water (CC).
Companies may apply to participate in any of the above certification sub-programmes:
Are included in the scope:
 Multi-split with data declared and published as combination of outdoor and indoor
units with 2 indoor units only: each unit individually connected to the outdoor unit and
with an expansion device inside the outdoor unit. The 2 indoor units have to be of the
same mounting type. For AC1 capacity ratio must be 1 ± 0.05.
Are excluded from the scope:
 Variable Refrigerant flow Systems
 Multi-split with 3 or more indoor units;
 AC1 multi with 2 indoors and a connection ratio different of 1 ± 0.05;
 Single duct mono-bloc mobile air conditioners;
 Packaged combined air conditioning and control mechanical ventilation;
 Air conditioners up to 12 kW not fulfilling the requirements of Regulation 206/2102
(see APPENDIX D).
“Certify-all”requirement: If a company participates in one of the sub-programmes for Air
Conditioners (AC1, AC2, AC3 and/or CC), all production models, within the scope of that
sub-programme, shall be certified in accordance with the relevant Rating Standard.
III. BASIC OUTLINE OF THE PROGRAMME
Participation in the programme consists of the following:
III.1 Application
After signing the Licence Agreement, the Applicant has to fill in the declaration list for
each sub-programme separately with all models that comply with respectively Rating
Standard:
- 6/C/001A for Air-cooled AC1 products,
- 6/C/001 for Water-cooled AC1 products, AC2 and AC3 products
- 6/C/004 for CC products.
OM-1-2015
Published December 2014
Page 4 of 30
III.2 Qualifying procedure
When the declaration file is completed, units selected by Eurovent Certita
Certification shall be tested in an Independent Laboratory chosen by Eurovent Certita
Certification. If the tests show conformity with the relevant Rating Standards,
certification is granted until 3 months after delivery deadline of next testing campaign.
III.3 Repetition procedure
Every year, Eurovent Certita Certification checks whether the certified performances
of the certified products still fulfil the requirements. If the participants fulfilled all
previous test campaigns and provided all the necessary elements and delivered all
the units for the current campaign, the certification is renewed for another campaign
within the timeframe allocated by the certification schedule, see Appendix A.
III.4 Failure treatment
When the test results fail to comply with the requirements of the relevant Rating
Standard(s) the failure treatment shall be applied.
III.5 Complaint procedure
Under special conditions a complaint procedure may be carried out as described in
the Certification Manual.
IV. OPERATION OF THE PROGRAMME
IV.1 Declaration of data
a.
Rated performance data
All characteristics and performance items shall be expressed in SI Units.
Maximum of 3 significant figures shall be used forcapacity, EER, COP, SEER,
SCOP, power consumption and water pressure drop and 2 significant figures for
sound power.
b. Certification forms
Submittal for certification of models shall be made in writing and sent to
Eurovent Certita Certification as an .xls or .xlsx file (Copy of these forms is part
of this manual (see APPENDIX B).
Declaration list (Form AC-1) shall be used for declaration of ranges, ranges,
models and data. For models submitted by a private brand manufacturer (BN)
the form will be used to identify the corresponding model number of the original
equipment manufacturer.
Technical Data Sheet (Form AC-2) for models selected for testing shall be
completed with technical description of all components along with
complementary declared data.
Additional Information Form (Form AC-3) shall be filled-in explaining how to
start the unit and to reach the proper frequency of the motor and including a
contact person the laboratory can reach in case of problem.
Reporting of test result (Form AC-4) is sent by Eurovent Certita Certification for
models tested, showing the deviations between claimed and measured data.
Response form after failure: (Form AC-5), is sent by Eurovent Certita
Certification for models which failed the test, showing the list of products
affected by the failed test.
AC, OM-1-2015
Published December 2014
Page 5 of 30
c.
Reporting of models
In reporting models for certification and for publication on the Eurovent Certified
Performance website, certified ratings shall be given for Packaged Air
Conditioners Units and all combinations of Split Air Conditioners which are
intended by the participant to be used together and which meet the
requirements of the relevant Rating Standard(s).
Optional devices or accessories which are used to obtain the ratings of the
basic unit assembly and which affect the ratings shall be included in the
certification data. Systems having coils with both horizontal and vertical
orientation, when ratings are different, shall be certified to reflect the capacity
and efficiency ratings for both positions.
Besides current models, the Participants shall provide Eurovent Certita
Certification with the list of:
 models under development,
 new models,
 deleted models,
 obsolete models.
d. Basic model group and acoustical family
Each Participant declaration list will be grouped in Basic Model Groups (BMG).
A basic model shall be defined by units which are essentially the same in terms
of thermal performance (±10% on capacity) and function (cooling or heating)
and the same or comparable in terms of basic components, specifically fans,
coils, compressors and motors. In the case of split packaged units, the unit
containing the compressor shall be the reference unit.
The Acoustical Family is defined as same reference for all sizes for outdoor
units and as same reference and same mounting type for indoor units.
IV.2 Selection of units to be tested
Within the programme, tests may be conducted under the following procedures:
 Scheduled tests in qualifying procedure
 Scheduled tests in repetition procedure
 Penalty test
 Complaint test
a.
Number of units to be tested
Eurovent Certita Certification shall select models on the basis of its evaluation
of a Manufacturer's declaration to establish suitable criteria of types and sizes to
be tested. The number of units tested each year per participant shall be as
follows:
 8% (rounded, at least 1) of the number of the listed basic model groups for
AC1
 10% (rounded, at least 1) of the number of the listed basic model groups
for AC2, AC3 and CC.
Examples of rounding (with 10%):
 7 declared units ⇒ 1 selected unit;
 14 declared units ⇒ 1 selected unit;
 15 declared units ⇒ 2 selected units
AC, OM-1-2015
Published December 2014
Page 6 of 30
b. Thermal measurements for AC1
For certification of seasonal efficiency, 30% of the selected units (minimum one
unit) the following measurements at the following conditions shall be performed:
 One running test at Tol. If for the average climate Tol ≥ -10°C and a
measurement has to be made at Tol (chosen conditon), the running test is
unnecessary.
 One point at the standard condition full load, i.e. condition A (35°C) in
cooling mode at TdesignC
 One point at +7°C standard rating condition in heating mode, as specified
in EN14511-2:2013. (if declared)
 One point to be chosen by Eurovent Certita Certification at part load
condition in cooling mode between B, C or D
 One point at the condition F at Tbivalent in heating mode for the average
climate (mandatory to declare)
 One point at the condition F at Tbivalent in heating mode for each additional
optional declared climate
 One point to be chosen by Eurovent Certita Certification at part load
condition in heating mode between A (if different from F), B (if different
from F), C, D or E (if ≠F)
 Tests of Poff, Psb and Pto (cooling mode)
 Pck whenever relevant (in alternance with Poff, Psb and Pto)
 Test of Cd if declared at a different value than the default value (0.25).
For the remaining selected units from the conditions listed above:
 One point selected by Eurovent Certita Certification in cooling
 One point selected by Eurovent Certita Certification in heating
This can be summarized in the following table:
Table 1: Thermal measurements of AC1 units
Running test at Tol
cooling A (standard +35°C full load) at TdesignC
heating nominal (+7°C standard rating condition)
cooling B, C or D
heating F at Tbiv for the average climate
heating F at Tbiv for each additional climate
heating A (at part load, if ≠F), B (if ≠F), C, D or E (if ≠F)
Poff
Psb
Pto (cooling)
Pck
Cd
cooling A (full load), B, C or D
nominal +7°C (standard rating condition), Favg, Fcolder , Fwarmer, A (part
heating load), B, C, D or E (if ≠F)
30% 70%
X
X
(X)
X
X
(X)
X
X
X
X
X
(X)
X
X
c.
Thermal measurements for AC1 Water Cooled Units, AC2, AC3 and
CC
At standard rating conditions, in cooling and heating as specified in EN145112:2013 (no test at part load conditions):
AC, OM-1-2015
Published December 2014
Page 7 of 30
d. Acoustics measurements for AC1, AC2, AC3 and CC
A weighted sound power level test for indoor(s) and outdoor shall be carried out
for all units selected.
e.
Acquisition of unit
Deadline for delivery of units to the laboratory together with the technical forms
duly completed, the starting procedure and the payment/order1 is given in the
Certification Schedule (see APPENDIX A).
If units, technical forms, starting procedures and payment/orders are not
delivered within the time limits specified in the notification received from
Eurovent Certita Certification, it is considered as non-application of procedures
(see Certification Manual).
f.
Tests at the laboratory
Units shall be installed in the test facility in accordance with the Participant
published installation instructions. The Participant will provide the laboratory
with full information about the installation, including at least the following items:
 any adjustment of the fan speeds (change of connector, switches, etc.);
 any change of the settings for any part of the unit (for instance, switch for
floor/ceiling mounting, switch for cooling only/heat pump unit, etc.);
 maximum external static pressure for ducted units;
 exact location of the refrigerant piping for multisplit systems, above all for
units intended for more than 2 indoor units;
 any other information necessary to the correct installation of the unit.
The laboratory shall install and check out the units. The procedures used shall
be in accordance with the Participant installation, start-up and service
instructions.
Participant personnel can be allowed to attend the setting-up and the starting of
the unit on request (for inverter units for example) but not the test itself and are
not permitted in the laboratory test room facility.
Prior to the test, the Laboratory personnel are only allowed to:
 Repair leaks
 Repair or replace items damaged by shipping or handling
 Assure correct refrigerant charge
 Assure correct fan speed(s) where adjustable speed fans are used
If the unit is not repairable, it shall be replaced by the Participant.
g. Report of test results
Upon completion of the tests on each unit, the Laboratory will render its
complete report as pdf file to Eurovent Certita Certification. Eurovent Certita
Certification will transmit a copy of the report together with reporting, Form AC4, and re-rating, Form AC-5, test result to the Participant.
1
Depending of the licence agreement signed between Eurovent Certita Certification and the manufacturer.
AC, OM-1-2015
Published December 2014
Page 8 of 30
h. Selection, shipment and return
Selected units shall be obtained either from the Applicant/Participant production
line or a stocking point, and then delivered to the Laboratory. Following
completion of the tests, the Participant shall arrange for the shipment of the unit.
The Laboratory shall have the responsibility of un-crating, handling, testing and
re-crating the unit for shipment.
A contact person shall be designated by the Applicant/Participant to organise
the shipment to the laboratory, the laboratory shall inform him when the testis
completed.
All transport fees shall be covered by the participant. The laboratory shall not
engage any transport fees.
The Participant has to notify Eurovent Certita Certification within four weeks
after receiving the test report if he intends to recover the tested unit. If the
participant fails to do so, Eurovent Certita Certification will order the laboratory
to dispose of the units and invoice the participant the disposal fee.
For AC1 units the participant can choose to recover all units at the end of the
testing campaign. The Participant has to recover its units within four weeks after
receiving the last test report. For AC2, AC3 and CC units the Participant has to
recover its units within eight weeks after receiving the test report.
IV.3 Failure treatment
a.
Component failure
If any functional component is inoperative, or the unit is damaged and cannot
be repaired at the Laboratory, the unit is considered as a “component failure”. A
new unit shall then be delivered within 2 weeks.
b. Testing at Tol
If the unit fails to start and operate continually for 30 min at Tol the
Applicant/Participant has 2 weeks to choose from the following alternatives:
 Change Tol and ask for a second test on the same unit (SCOP to be
recalculated)
 Change Tol to the lowest fully tested outdoor temperature (-7°C for
average climate, SCOP to be recalculated)
 Maintain Tol and ask for a second test on the same unit
c.
Failure to meet the required capacity ratio (variable capacity)
For variable capacity units in case the tested capacity ratio fails to reach the
required load ratio within  10% the laboratory should contact immediately the
Applicant/Participant to acquire the information to test the closest for the steps
on either side of the required heating load. If the manufacturer fails to provide
the information the unit will be considered as a component failure.
d. Testing of general performances
For each test, a performance item fails when the difference between the
declared value and the measurement differs by more than the acceptable
tolerance (see relevant Rating Standard(s)). A test fails when one or more
performance items fail.
For each failed test, the Applicant/Participant has 4 weeks after notification of
failure to choose between one of the following alternatives:
AC, OM-1-2015
Published December 2014
Page 9 of 30
 Re-rate the products in accordance with the re-rating rules (see dedicated
chapter below);
 Ask for a second test on the same unit;
 Ask for a second test on another unit of the same model selected by
Eurovent Certita Certification.
e.
Penalty tests
An additional unit will be selected for the next test campaign each time there is
a deviation by more than the high tolerance (see relevant Rating Standard) on:
 efficiency and/or capacity;
 sound power level.
Penalty tests following a qualifying procedure need to be validated before the
certification is granted.
f.
Second test
If the Applicant/Participant had shipped back the unit, the complete test shall be
carried out.
If the second test is performed on the same unit (without any modification on
the unit, and not leaving the laboratory), the Applicant/Participant can choose to
repeat only:
 All thermal and pressure measurements
or
 All sound measurements
Note: For a complete test, if the Part Load tests failed but not the Standard
points, the second tests can be carried out only for the Part Load tests
(Tbiv, conditions A to D, TOL) with/without auxiliary test.
IV.4 Repeated failures along the test campaigns
This paragraph refers to paragraph V.6 of the Certification Manual.
The rules regarding Mean Value of Failure (MVF) are described in APPENDIX C.
V.
RE-RATING RULES
For each failed test, the model shall be re-rated according to the following rules:
V.1 Rerating of Tol
If Tol has been changed for second tests and second measurement passed, Tol is
rerated at changed value.
If during second test, second measurement has also failed, Tol will be rerated at the
tested point with the lowest outdoor temperature (-7°C for average climate).
V.2 Seasonal efficiency points: rerating of design load
Whenever the test at extreme/bivalent condition shows a deviation on capacity larger
than the allowed tolerance, the design load is rerated according to the measured
deviation for all models in the same basic model group.
AC, OM-1-2015
Published December 2014
Page 10 of 30
V.3 Rerating of auxiliary power consumption
Whenever the test on auxiliary power consumption shows a deviation larger than the
allowed tolerance, the auxiliary power consumption is rerated according to the
measured deviation for all models in the same basic model group.
V.4 Rerating when capacity and/or efficiency fails
In case of failure on capacity and efficiency, then capacity, efficiency and power input
of the tested model shall be rerated to the measured values.
Deviation on capacity shall be applied to all models in the same basic model group
(BMG).
Deviation on efficiency shall be applied to all models in the same BMG.
Power input shall be recalculated for all models in the same BMG.
In case of failure on capacity only or efficiency only, the power input shall also be
recalculated for all models in the same basic model group.
AC, OM-1-2015
Published December 2014
Page 11 of 30
Table 2: Example of rerating when efficiency or capacity only fails
Complete tests :
Partial tests :
(30% of the selected units - minimum one unit)
(1 point in cooling, 1 point in heating)
Cooling :
EER
Conditions
A
EER
Passed /
T° Deviation Failed Rerate SEER with
35
-2%
P
EER A,declared
B
30
C
25
D
20
-12%
F
Conditions T° Deviation
A
35
EER B,declared -12%
B
30
EER C,measured
C
25
EER D,delared -12%
D
20
EER
Conditions
A
B
C
D
-2%
Rerate SEER with
EER A,declared
EER B,declared -12%
-12%
F
EER C,measured
EER D,delared -12%
EER
Passed /
T° Deviation Failed Rerate SEER with
35
-12%
F
EER A, measured
30
25
20
Passed /
Failed
P
EER B, declared
EER C, declared
EER D, declared
Conditions T° Deviation
A
35
-12%
B
C
D
30
25
20
Passed /
Failed
F
Rerate SEER with
EER A, measured
EER B, declared
EER C, declared
EER D, declared
EER
Conditions
A
B
T° Deviation
35
-11%
30
C
25
D
Other
points :
20
-12%
Passed /
Failed Rerate SEER with
F
EER A, measured
EER B,declared -12%
F
EER C, measured
EER D,delared -12%
Power consumption at off mode, standby
mode, thermostat off mode and crankcase
heater mode
Power
Passed /
consumption
Deviation Failed Rerate SEER with
P off
P
P off,declared
P
P sb
P sb,declared
P to
P ck
12%
F
P to, measured
P ck,declared
AC, OM-1-2015
Published December 2014
Page 12 of 30
Heating
COP
COP
Passed
/
Deviation Failed Rerate SCOP with
Conditions
T°
E
Tol
(unit
running
at TOL)
P
F
Tbiv
-11%
F
A
-7
B
2
-12%
F
C
D
Rerate SCOP
with
T°
TOL declared
E
Tol
TOL declared
COP tbiv,measured
F
Tbiv
COP A,declared -12%
A
-7
COP tbiv,declared
COP A,declared 12%
COP B,measured
B
2
7
COP C,declared -12%
C
7
COP C,declared -12%
12
COP D,declared -12%
D
12
COP D,declared -12%
COP
Deviation
Passed /
Failed
Conditions
-12%
F
COP B,measured
COP
Passed
/
Deviation Failed Rerate SCOP with
Conditions
T°
E
Tol
(unit
running
at TOL)
P
F (-7°)
Tbiv
-11%
A
-7
B
2
C
D
Deviation
Passed /
Failed
Rerate SCOP
with
Conditions
T°
TOL declared
E
Tol
F
COP tbiv,measured
F
Tbiv
-11%
F
COP A,declared -11%
A
-7
COP A,declared
-12%
F
COP B,measured
B
2
COP B,declared
7
COP C,declared -12%
C
7
COP C,declared
12
COP C,declared -12%
D
12
COP D,declared
TOL declared
-11%
F
COP tbiv,measured
COP
COP
Conditions
T°
E
Tol
F
Tbiv
Passed
/
Deviation Failed Rerate SCOP with
(not
running
at TOL)
F
Tol
P
COP tbiv,declared
-7
rerated
COP A,declared
P
B
2
COP B,declared
C
7
COP C,declared
D
12
COP D,declared
AC, OM-1-2015
Published December 2014
Page 13 of 30
Pdesignh
Passed
/
Deviation Failed Rerate Pdesignh
Ph Tbiv
-12%
F
Pdesignh
Ph Tbiv, measured
Pdesignh,declared -12%
The rerated P designh is used to calculate the rerated SCOP.
Other
points :
Power consumption at off mode, standby
mode, thermostat off mode and crankcase
heater mode
Power
consumption
P off
P sb
P to
P ck
Passed
/
Deviation Failed Rerate SCOP with
P
P off,declared
P
P sb,declared
12%
F
P to, measured
P ck,declared
V.5 Rerating of SEER and SCOP
When second measurement of Tol fails, SCOP of the tested model shall be
recalculated with the assumption that all demands beyond Tol are provided by an
electric backup heater with a COP of 1.
Whenever a measurement at a part-load condition selected by Eurovent Certita
Certification shows a deviation on EER or COP larger than the allowed tolerance, the
§ V.4 shall be applied on all the other part load EER (respectively COP) and then,
SEER and SCOP will be recalculated by Eurovent Certita Certification, to be rerated.
Whenever the test on auxiliary power consumption or/and the test on capacity at
extreme condition/bivalentcondition shows a deviation larger than the allowed
tolerance the value of SCOP/SEER should be recalculated.
In case of recalculation of the SEER or SCOP, the annual energy consumption
should be recalculated for the tested unit.
In case of recalculation of SEER or SCOP and annual energy consumption for the
tested model:
- the deviation on SEER or SCOP shall be applied to all models in the same basic
model group (BMG),
- the deviation on annual energy consumption shall be applied to all models in the
same basic model group (BMG).
- the deviation of the tested auxiliary power consumptions shall be applied to all
models in the same basic model group (BMG).
AC, OM-1-2015
Published December 2014
Page 14 of 30
Table 3: Example of rerating
BMG
Model
A
1
B
C
Items
Declared
Calculed Deviation
Rerated Value
SCOP
3,8
3,18
-16%
3,18
Qhe
1750
1805
3%
1805
SCOP
3,9
-
-
SCOPdeclared x (1 - 0,16)
3,26
Qhe
1780
-
-
Qhedeclared x (1 + 0,05)
1836
SCOP
3,7
-
-
SCOPdeclared x (1 - 0,16)
3,10
Qhe
1700
-
-
Qhedeclared x (1 + 0,05)
1753
V.6 Rerating on acoustic performances
 If the result on sound power level exceeds the claimed by the tolerance, but
less than than the high tolerance (see relevant Rating Standard), only the tested
model shall be re-rated in accordance with the test result.
 If the result exceeds the claimed value by the tolerance or more, the tested
model shall be re-rated in accordance with the test result. In addition, the whole
product family of the failed model shall be re-rated to the tested deviation value
minus 2 dB(A).
Table 4: Example of rerating when sound power level fails
Family Declared Measured Deviation Rerated?
50
51
1
Y
1
49
N
60
65
5
Y
2
58
Y
Rerated value
Lwmeasured
Lwdeclared
Lwmeasured
Lwdeclared + Lwdeviation - 2
51
49
65
61
V.7 Possible uprating
At the moment of the annual declaration, an uprating of performances from a same
BMG is allowed:
- If the deviation of tested unit (in the BMG) is above inversed tolerance
Or if:
- Units are not already tested and rerated and
- Units of the BMG, if we received the proof (=report) that the tested unit was very
underrated
VI. PROMOTION OF THE PROGRAMME
This section refers to section VI of the Certification Manual.
VI.1 By Eurovent Certita Certification
The certified data of the certified products are published on the Eurovent Certified
Performance website: www.eurovent-certification.com.
AC, OM-1-2015
Published December 2014
Page 15 of 30
Eurovent Certita Certification will supply, on request, to any interested party, the
current status of any Participant or of any model (under development, new, deleted or
obsolete).
The following information pertaining to each model certified shall be published on the
Website for Air Conditioners:
 Name of Company
 Trade or brand name of model
 Model number(s) or designation(s)
 A-weighted indoor side sound power
 A-weighted outdoor side sound power
 A-weighted sound power radiated from the duct (ducted units)
 Refrigerant line for split system
 Main Power Supply
 Mounting base
 Refrigerant fluid
 Design load in cooling
 EER at condition A in Coolinga
 Bivalent Temperature (for each climate declared)
 Performances at bivalent temperature (Ph and COP)
 Tol operation limit temperature
 Performances at Tol (Ph and COP)
 Design load in heating (for each climate declared)
 Total heating capacity and COP for reverse cycle unit at standard rating
condition (+7°C)
 Seasonal Energy Effeciency Ratio SEER
 Seasonal Coefficient Of Performance SCOP (for each climate declared)
 Annual electric power consumption in cooling mode
 Annual electric power consumption in heating mode (for each climate declared)
 Auxiliary Power consumption
In addition, for AC2, AC3 and CC
 Total cooling capacity
 Total heating capacity for reverse cycle unit at +7°C
 Sensible cooling capacity for close control units
 Effective power input (cooling and heating)
 EER and COP
 Water pressure drop (chilled water close control units)
VI.2 By Participants
The participating company may indicate participation in the programme. When he
does, it shall be by displaying the appropriate Eurovent Certified Performance mark
on all specification sheets and in other literature carrying ratings, or claiming
certification, of certified models (see Certification Manual).
a.
Display of certification mark in literature, software and advertising
Use of the Eurovent Certified Performance mark is described in Certification
Manual. The following completes the description in the AC programme.
AC, OM-1-2015
Published December 2014
Page 16 of 30
When publishing ratings a Participant shall include at least the certified
performance in the standard rating conditions, as specified in the relevant
Rating Standard(s).
b. Display of certification mark on production units
Each Participant is entitled to display the Eurovent Certified Performance mark
on units of models which have been certified. The Participant may also display
the Eurovent Certified Performance mark on each certified unit by application of
Eurovent Certified Performance mark. No data or other marking shall be added
to the mark. The Participant may affix the certification mark at any location
thereon satisfactory to him for single-package units, and on the component
containing the compressor for split units. The Eurovent Certified Performance
mark may be applied as part of the nameplate of a certified model.
AC, OM-1-2015
Published December 2014
Page 17 of 30
APPENDIX A.
Certification schedule
For each repetition test campaign (year n), the following schedule shall be applied:
Eurovent Certita Certification asks for up-date of product list
Participant confirms up-date of products list
Eurovent Certita Certification sends selection list for test
The Participant confirms selection list
Delivery + submittal form + order/payment from Participant (+
starting procedure for inverter units) are completed for units with
cooling capacity not higher than 5 kW
Delivery + submittal form + order from Participant (+ starting
procedure for inverter units) are completed for units with cooling
capacity higher than 5 kW
Diploma for test campaign are valid until
The Laboratory carries out all first tests
Eurovent Certita Certification sends the test reports
The Participant can ask for a second test up to
Eurovent Certita Certification sends selection list for 2nd test(s)
Delivery + submittal form + order/payment from Participant are
completed for secondtest(s)
The Laboratory carries out all second tests
31/10/n-1
30/11/n-1
15/01/n
31/01/n
15/03/n
30/04/n
31/07/n+1
30/11/n or 60 days after
test is ordered
3 days after reception
of the laboratory
report
15/12/n
05/01/n+1
28/02/n+1
OM-1-2015
Published December 2014
Page 18 of 30
APPENDIX B.
Forms
B.I. Form AC-1: Submittal for certification
Label
Unit
Description
GENERIC
Product Number
Master product
number
Tested On
Rerated on
Created on
Last update on
Status
Participant Name
Product Name
Trade Name
(see Certification Manual)
Thermal
Type of product
Range Name
BMG
Ps (CC only)
Sensible cooling capacity (Close Control units only)
kW
Pc
Cooling Capacity
kW
EER
Energy Efficiency Ratio
-
Ph
Heating Capacity
kW
COP
-
Dpc
LwO env
LwI1 env
LwI1 duct
LwI2 env
LwO duct
LwI2 duct
Coefficient of Performance
Sensible Cooling Capacity (Chilled Water cooled Close Control units
only)
Total Cooling Capacity (Chilled Water cooled Close Control units
only)
Effective Power Input for Cooling (Chilled Water cooled CC units
only)
Pressure Drop in Cooling Mode (Chilled Water cooled CC units only)
A-weighted sound power level outdoor unit (non ducted)
A-weighted sound power level indoor unit 1 (non ducted)
A-weighted sound power level indoor unit 2 (non ducted)
A-weighted sound power level outdoor unit (ducted)
A-weighted sound power level indoor unit 1 (ducted)
A-weighted sound power level indoor unit 2 (ducted)
EER @ 35°C
Energy Efficiency at full load at 35°C
-
Pc @ 35°C
Cooling Cpapcity at full load at 35°C
kW
Ps (CW CC only)
Pc (CW CC only)
Cooling
Acoustic
Pec (CW CC only)
kW
kW
kW
kPa
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
EER Stage1 @ 30°C Energy Efficiency step 1 at 30°C
-
Pc Stage 1 @ 30°C
EER Stage 2 @ 30°C
Pc Stage 2 @ 30°C
EER Stage1 @ 25°C
Pc Stage 1 @ 25°C
kW
kW
kW
Cooling Cpapcity at step 1 at 30°C
Energy Efficiency step 2 at 30°C
Cooling Cpapcity at step 2 at 30°C
Energy Efficiency step 1 at 25°C
Cooling Capacity at step 1 at 25°C
AC, OM-1-2015
Published December 2014
Page 19 of 30
PLH Heating Average Climate
EER Stage2 @ 25°C
Pc Stage 2 @ 25°C
EER Stage1 @ 20°C
Pc Stage 1 @ 20°C
EER Stage2 @ 20°C
Pc Stage 2 @ 20°C
Pdesignc
SEER
SEER_on
Energy Efficiency step 2 at 25°C
Cooling Capacity at step 2 at 25°C
Energy Efficiency step 1 at 20°C
Cooling Capacity at step 1 at 20°C
Energy Efficiency step 2 at 20°C
Cooling Capacity at step 2 at 20°C
Design Load Cooling
Seasonal Energy Efficiency Ratio
Seasonal Energy Efficiency Ratio in active cooling mode
Qce
Annual electricity consumption for cooling
SEER Class
COP @-7°C
Ph Stage1 @ -7°C
COP Stage 2 @-7°C
Ph Stage2 @ -7°C
COP Stage 1 @ 2°C
Ph Stage 1 @ +2°C
COP Stage 2 @2°C
Ph Stage 2 @ +2°C
COP Stage1 @ +7°C
Ph Stage 1 @ +7°C
COP Stage 2 @
+7°C
Ph Stage 2 @ +7°C
COP Stage 1 @
+12°C
Ph Stage1 @ +12°C
COP Stage 2 @
+12°C
Ph Stage2 @ +12°C
Pdesignh
Seasonal Energy Efficiency Ratio Class
Coefficient of performances at -7°C step 1
Heating capacity at -7°C step 1
Coefficient of performances at -7°C step 2
Heating capacity at -7°C step 2
Coefficient of performances at +2°C step 1
Heating capacity at +2°C step 1
Coefficient of performances at +2°C step 2
Heating capacity at +2°C step 2
Coefficient of performances at +7°C step 1
Heating capacity at +7°C step 1
kW
kW
kW
kW
kWh/
annum
kW
kW
kW
kW
kW
Coefficient of performances at +7°C step 2
-
Heating capacity at +7°C step 2
kW
Coefficient of performances at +12°C step 1
-
Heating capacity at +12°C step 1
kW
Coefficient of performances at +12°C step 2
-
Heating capacity at +12°C step 2
Heating load at design conditions
The seasonal efficiency of a unit calculated for the reference annual
heating demand
Seasonal Energy Efficiency Ratio in active heating mode
Seasonal Energy Efficiency in active Heating mode without
supplementary electric heaters
kW
kW
SCOP
SCOPnet
SCOP on
Qhe
TOL
Bivalent
Runing Test Point
Tbiv
COP @ Tbiv
Ph TBiv
Heating Colder
Climate
SCOP Class
Pdesignh
TOL
COP @ TOL
Ph @ TOL
SCOP
SCOP net
kWh/
annum
Annual electricity consumption for heating
Class of seasonal efficiency of a unit calculated for the reference
annual heating demand
Bivalent Temperature
Coefficienct of Performances at bivalent temperatures conditions
Heating Capacity at bivalent temperatures conditions
The lowest outdoor temperature at which the heat pump can still
deliver heating capacity, as declared by the manufacturer
Coefficienct of Performances at TOL temperatures conditions
Heating Capacity at TOL temperatures conditions
Heating load at design conditions
(kW)
The seasonal efficiency of a unit calculated for the reference annual
heating demand
Seasonal Energy Efficiency in active heating mode without
supplementary electric heaters
°C
kW
°C
kW
kW
-
AC, OM-1-2015
Published December 2014
Page 20 of 30
SCOP on
Seasonal Energy Efficiency Ratio in active heating mode
Annual electricity consumption for heating
[kWh/annum]
Coefficienct of Performances at bivalent temperatures conditions
Heating Capacity at bivalent temperatures conditions
Bivalent Temperature
[°C]
Coefficienct of Performances at TOL temperatures conditions
Heating Capacity at TOL temperatures conditions
The lowest outdoor temperature at which the heat pump can still
deliver heating capacity, as declared by the manufacturer
Heating load at design conditions
(kW)
The seasonal efficiency of a unit calculated for the reference annual
heating demand
Seasonal Energy Efficiency in active heating mode without
supplementary electric heaters
Seasonal Energy Efficiency Ratio in active heating mode
Annual electricity consumption for heating
Coefficienct of Performances at bivalent temperatures conditions
Heating Capacity at bivalent temperatures conditions
Bivalent Temperature
Coefficienct of Performances at TOL temperatures conditions
Heating Capacity at TOL temperatures conditions
The lowest outdoor temperature at which the heat pump can still
deliver heating capacity, as declared by the manufacturer
kWh/
annum
kW
Pck
Power consumption in the crank case heater mode
W
Poff
Power consumption in the off mode
W
Psb
Pto
Off Mode
Capacity Control
Inverter
MPS
Refrigerant
Refr. Line
Mounting
Mount. Opt.
Ducted Outdoor
Ducted Indoor
Ducted Vertical
Duct Option
Power consumption in the standby mode
Power consumption in the thermostat off mode
True/False
Fixed, Staged, Variable
Inverter
Main Power Supply: Voltage (V)-Phase-Frequency(Hz)
Refrigerant(Refr)
Refrigerant Line.
Mounting Type
Mounting Option
Ducted Outdoor
Ducted Indoor
Ducted Vertical
Duct Option
W
W
True/False
Qhe
COP @ Tbiv
Ph @ Tbiv°C
Tbiv
COP @TOL
Ph @TOL°C
TOL
Pdesignh
Heating Warmer Climate
SCOP
SCOP net
SCOPon
Qhe
COP @ Tbiv
Ph @ Tbiv°C
TBiv
COP @ TOL
Ph @TOL°C
General
RT
20
12
Psb, Pto
and Poff
Crankcase
heater
TOL
°C
kW
kW
kWh/annum
kW
°C
kW
°C
True/False
m
True/False
True/False
True/False
AC, OM-1-2015
Published December 2014
Page 21 of 30
B.II. Form AC-2: Technical Data Sheet
Technical Data Sheet shows all information of Declaration file, to which will be added:
General
Label
Description
Unit
mm.mm.
mm
kg
kg
°C
m3/s
Dimension
Unit dimension length by height by width
Total Charge
Weight
Attendance
Compressor Manufacturer
Compressor Model
Contact Name
Contact Title
Expansion Device Location
Heating Mode Minimum Temperature
Indoor Coil 1 Air Flow
Indoor Coil 1 Available Static
Pressure
Total charge
Unit weight (indoor unit / outdoor unit)
Attendance [true/false]
Compressor manufacturer
Compressor model
Contact name
Contact title
Expansion device location (outdoor/indoor)
Heating mode minimum temperature
Air flow rate indoor coil
Indoor Coil 1 Dimension
Coil length × height ×width
Indoor Coil 1 Fan Motor Type
Indoor Coil 1 Fan Type
Indoor Coil 1 Fin Spacing
Indoor Coil 1 Fin Type
Indoor Coil 1 Number of Fan
Indoor Coil 1 Number of Circuit
Indoor Coil 1 Number of Row
Indoor Coil 1 Pitch
Indoor Coil 1 Tube Outside Ø
Indoor Coil 1 Tube Type
Outdoor Coil Air Flow Rate
Outdoor Coil Available Static
Pressure
Fan motor type (dc inv, ac inv, ac large slip)
Fan type
Fin spacing
Fin type
Number of fans
Number of circuits
Number of row
Tube pitch × row pitch
Tube outside diameter
Tube type
Air flow rate outdoor coil
Outdoor Coil Dimension (L X H X W)
Coil length × height × width
Outdoor Coil Fan Type
Outdoor Coil Fin Spacing
Outdoor Coil Fin Type
Outdoor Coil Number of Circuit
Outdoor Coil Number of Fan
Outdoor Coil Number of Row
Outdoor Coil Pitch
Outdoor Coil Tube Outside
Dimension
Outdoor Coil Water Flow Rate
Heating
Outdoor Coil Fan Motor Type
Outdoor Coil Tube Type
Refrigerant Line Outside Ø (Liquid)
Refrigerant Line Outside Ø (Vapour)
Remote Control Box
Water Cooled Condenser
Manufacturer
Water Cooled Condenser Pump
Included
Water Cooled Condenser Reference
Water Cooled Condenser Type
Water Flow Rate Outdoor Coil at
30°C
Water Flow Rate Outdoor Coil at
30/35 °C
Fan type
Fin spacing
Fin type
Number of circuits
Number of fan
Number of row
Tube pitch × row pitch
mm.mm.
mm
mm
mm.mm
Tube outside diameter
mm
Outdoor coil water flow rate heating mode
m3/s
Outdoor coil fan motor type)
Outdoor coil tube type
Refrigerant line outside diameter liquid (split syst)
Refrigerant line outside diameter vapour (split syst)
Remote control box [true/false]
mm
mm
-
Available pressure indoor coil
Pa
mm.mm.
mm
mm.mm
mm
m3/s
Avialable pressure outdoor coil
Pa
Manufacturer
-
Pump included [true/false]
-
Water cooled condenser reference
Water cooled condenser type
-
Water flow rate outdoor coil at 30 °C
m3/s
Water flow rate outdoor coil at 30/35 °C
m3/s
AC, OM-1-2015
Published December 2014
Page 22 of 30
B.III. Seasonal Efficiency Calculation Sheet
B.IV. Form AC-3: Additional Information Form
This form is to be completed for inverter AND non-inverter models.
Test Number
Model
1.
Participant technical contact person
In order to be able to quickly solve starting-up problems, the laboratory needs to have data
of a technical contact. Please fill the table below.
Name
Telephone number
E-mail address / fax number
2.
Fan speeds and compressor frequencies
The following data will help the laboratory to check that the unit is running in TEST MODE.
It’s highly recommended to fill the table below for inverter models.
Fan speed [rpm]
Cooling
Heating
Model
Compressor frequency [Hz]
Cooling
Heating
Outdoor Unit
Indoor Unit 1
Indoor Unit 2
For cooling mode in part load conditions (part load condition A is covered above):
Part load ratio [%]
Outdoor air dry bulb
T [°C]
B
74
30
C
47
25
D
21
20
Fan outdoor
unit [rpm]
Fan indoor
unit 1 [rpm]
Fan indoor
unit 2 [rpm]
Compressor
frequency [Hz]
For heating mode in part load conditions:
AC, OM-1-2015
Published December 2014
Page 23 of 30
A
88
-7(-8)
B
54
2(1)
C
35
7(6)
D
15
12(11)
F
(Tbivalent-16)/(Tdesignh -16)
Tbivalent(Tbivalent-1)
Following EN 14825:2012, indoor fan speeds in part load can be different for m the ones in
standard rating conditions
3.
Has the laboratory to apply a specific start-up procedure to achieve the rated
capacities? (No test will be performed without answer to this question.)
YES |
4.
NO
Start-up procedure
Note: Once frequencies and expansion valves opening are fixed, no further changes will
be allowed until test completion.
If answer to clause 3 is YES, a detailed start-up procedure shall be attached.
VERY IMPORTANT: Attached start-up proceduret shall be drafted with enough details to
ensure the laboratory personal will be able to set the unit at the first try. In particular,
special care shall be given to the following items:
 Initial state of the following items (before starting the configuration):
 wired/remote controller model status (ON or OFF)
 appliance status (ON or OFF)
 mode (cooling, heating, ventilation, auto, etc.)
 room temperature range requirements (if yes, specify clearly), Temperature
requirements cannot be closer than ± 2 K from the rating conditions.
In addition:
 Indicate if the remote controller shall be configured with the indoor unit(s) receiving or
not the signals from the remote controller.
 When entering TEST MODE, indicate if the appliance will give a feedback (acoustic
or visible) to acknowledge the setting.
 Indicate the louver position, and the method to reach it. A drawing may be useful.
 For multisplit systems, please clearly specify if the starting procedure has to be
performed for all indoor units at the same time, or in which order.
5.
Time before beginning of the measurement period
Please note that the measurement period will begin 60 minutes (heating mode) or 70 min
(heating mode) after starting the unit. This means that the unit shall be running in
TEST MODE by that time.
6.
Default start up procedure
When there are no details on start-up supplied with the units, the normal start-up
procedure used by the laboratory will be as follows:
COOLING CAPACITY TESTING AND SOUND POWER DETERMINATION
Configuration of the remote controller:
 Mode: Cooling mode*
AC, OM-1-2015
Published December 2014
Page 24 of 30
 Temperature set: Minimum allowed by remote controller without including special
modes like LOW temperature function.
 Fan speed: Maximum allowed by remote controller without including special modes
like TURBO mode.
 Louver: Maximum airflow position**
HEATING CAPACITY TESTING
Configuration of the remote controller:
 Mode: Heating mode*
 Temperature set: Maximum allowed by remote controller without including special
modes like HIGH temperature function.
 Fan speed: Maximum allowed by remote controller without including special modes
like TURBO mode.
 Louver: Maximum airflow position**
* Any other functions, like eco mode, display backlighting, ionizer, etc will be kept as default after inserting the batteries
in the remote controller or switching the power on for wired remote controllers. **The louver position for maximum airflow
is only checked visually so there is a risk not to exactly be in the maximum airflow position.
Contacts in Ceis laboratory:
Contacts in Tüv-Nord laboratory:
Ms Pilar GARCIA – [email protected]
Mr Julio CONDE – [email protected]
Ms Monika STEIMLE – [email protected]
Dr. Ing. Helge UHLIG – [email protected]
AC, OM-1-2015
Published December 2014
Page 25 of 30
B.V. Form AC-4: Test result form
2
2
Displayed Performances may vary according to subprogramme (AC1,AC2,AC3 or CC) and product type
OM-1-2015
Published December 2014
Page 26 of 30
B.VI. Form AC-5: Re-rate form
OM-1-2015
Published December 2014
Page 27 of 30
APPENDIX C.
Calculation method and implementation of MVF
C.I. General
Mean Value of Failure (MVF) is equal, for each manufacturer and for each
considered characteristic, to the ratio between the total number of measurements
above the “High deviation limit” (see table below) and the total performed
measurements in the considered years.
MHFV
Mean High FailureValue

 Numb er of measurements failed with high deviation
 Numb er of measurements performed
Number of considered years
Number of considered years
When there is a second test on a unit, then the first measurements are not taken into
account.
A manufacturer is expelled from the Eurovent Certified Performance Programme for
one year if, for at least one considered characteristic, the mean value of MVF is
higher than the limit z.
Current Failure treatment (re-rating and additional tests) still applies above the
“Eurovent AC tolerance” (see IV.3).
Participants
Test campaigns
to be considered
Time of application
Eurovent
CharacAC
teristic
tolerance
Pc
< -5%
Ph
< -5%
EER
< -8%
COP
< -8%
Lw
> + 0dB(A)
Participants already certified
High
deviation
limit
< -12%
< -12%
< -15%
< -15%
> + 3dB(A)
New participants
Qualifying test campaign + first
3 last test campaigns
repetition test campaign
starting from 2011
after first repetition test campaign
Limits for being expelled
MVF > …
> 25 %
> 40 %
> 25 %
> 40 %
> 40 %
C.II. Implementation & newcomers
At the end of 2009 test campaign, Eurovent Certita Certification takes into
consideration the last two test campaign data of each manufacturer. At the end of
2010 test campaign and at the end of each following year, Eurovent Certita
Certification takes into consideration the last three test campaign data of each
manufacturer.
Data of new participants will be first taken into consideration after two test campaigns
(including qualifying tests).
C.III. Notification of being expelled
A participant who is going to be expelled will receive a notification from Eurovent
Certita Certification, with a possible additional selected unit to be tested. The purpose
of this additional test is to give the participant the opportunity to comply with the
limits. The response to Eurovent Certita Certification with confirmation of request for
additional testing has to be done within 30 days after this notification, and the unit
has to be delivered within 45 days after this notification.
OM-1-2015
Published December 2014
Page 28 of 30
A manufacturer that leaves the programme because he has been expelled should
complete the qualifying procedure within the year for which he has been expelled in
order to rejoin for the next year. He becomes a newcomer.
AC, OM-1-2015
Published December 2014
Page 29 of 30
APPENDIX D.
ECO-DESIGN AND ENERGY LABELLING
Commission Regulation (EU) No 206/2012 implementing Directive 2009/125/EC of the
European Parliament and of the Council with regard to ecodesign requirements for air
conditioners and comfort fans gives requirements for all air conditioners with the cooling
capacity under 12 kW (AC1) introduced on the European market after 1 January 2013.
The Directive defines maximum sound power levels and energy efficiency as given in the
following tables.
Commission Regulation(EU) No 626/2011 supplementing Directive 2010/30/EU of the
European Parliament and of the Council with regard to energy labelling of air conditioners
makes mandatory energy labelling of all air conditioners with the cooling capacity under
12 kW (AC1) introduced on the European market after the 1st January 2013. The Directive
defines for each function the energy class going from A++ (more efficient) to G (less
efficient). The classification is given in the following table.
Table 5: Energy Classification for Conditioners except double ducts and single
ducts
Energy Efficiency Class
A+++
A++
A+
A
B
C
D
E
F
G
SEER
SEER ≥ 8.50
6.10 ≤ SEER < 8.50
5.60 ≤ SEER < 6.10
5.10 ≤ SEER < 5.60
4.60 ≤ SEER < 5.10
4.10 ≤ SEER < 4.60
3.60 ≤ SEER < 4.10
3.10 ≤ SEER < 3.60
2.60 ≤ SEER < 3.10
SEER < 2.60
SCOP
SCOP ≥ 5.10
4.60 ≤ SCOP < 5.10
4.00 ≤SCOP < 4.60
3.40 ≤ SCOP < 4.00
3.10 ≤ SCOP < 3.40
2.80 ≤ SCOP < 3.10
2.50 ≤ SCOP < 2.80
2.20 ≤ SCOP < 2.50
1.90 ≤ SCOP < 2.20
SCOP < 1.90
OM-1-2015
Published December 2014
Page 30 of 30