FSP UPS Shortform catalogue 2016

P OWER
NEVER ENDS
STANDBY UPS
LINE INTERACTIVE UPS
ONLINE UPS
OFF-GRID INVERTER
ON-GRID INVERTER WITH ENERGY STORAGE
ACCESSORY
UPS SOLAR INVERTER
FSP Group is the leading switching power supplier in the world.
Since established in 1993, the company has drawn together its R&D expertise, sizeable production capacity and outstanding product quality to consistently excel in this competitive marketplace.
FSP Group produces large selections of products to serve its OEM / ODM customers in LCD TV, LED Lighting,
Medical, Industrial / Desktop computers and Servers. FSP Group has more than 28 branch offices worldwide,
4 manufacturing facilities and about 8,500 people throughout the world.
With its broad range of products, FSP Group is uniquely positioned for strong growth on several long term trends and environment protection including green power products, higher energy-efficient conversion products, and highly electrical safety and reliable products.
FSP Group’s global presence
in Taiwan, Brazil, China, Germany, Sweden, France, India, Japan, Korea, Russia,
Turkey, UK, USA also provide our OEM / ODM customers with integrated global logistic. This translates to
“Door-to-Door” service and faster time-to-market for product deliveries. Please check with your highly trained professional account manager on how to take advantage of our global logistic service for your business.
Our current focus
in FSP Group is to further enhance our green power products, expand market presence of FSP branded retail products, and extend our research and development effort on all our products. At FSP
Group, we are not only focusing on building a bigger company, also a better one.
Energetic Friendly Simple Reliable
P O W E R
NEVER ENDS
Applications:
TV HI-FI Game
Console
Computer
TECHNICAL SPECIFICATIONS
MODEL
CAPACITY
INPUT
Voltage
Voltage Range
Frequency Range
OUTPUT
AC Voltage Regulation(Batt. Mode)
Frequency Range(Batt. Mode)
Transfer Time
Waveform(Batt. Mode)
BATTERY
Battery Type
Numbers
Typical Recharge Time
INDICATORS
AC Mode
Battery Mode
Low Battery (Batt. Mode)
Fault
ALARM
Battery Mode
Low Battery (Batt. Mode)
Fault
PHYSICAL
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Humidity
Operating Temperature
Nano400
400 VA / 240 W
12V / 4.5 Ah
1
2.2
Product specifications are subject to change without further notice
Nano Series
Standby UPS
Nano UPS provides comprehensive protection in a small and economic package, the compact size offer basic protection to against utility abnormal situations
- surges and spikes. FSP Nano will continue generating stable power to serve the connected equipments and able to shutdown PC safely when input power failure.
Embedded Microprocessor controller guarantees its reliability and suitable for home, small office, and power backup application.
GENERAL FEATURES
Compact size with stand and mounting flexibility
Excellent microprocessor controller guarantees high reliability
Auto restart while AC is recovering
Simulated sine wave output
Cold start function
Discharge, overcharge, short circuit, and thermal protection
2
Nano600
600 VA / 360 W
110/120 V or 220/230/240 V
90-145 V / 180-270 V
50 Hz or 60Hz (Auto sensing)
±10%
50 Hz or 60 Hz ± 1 Hz
2-6 ms
Simulated Sine Wave
12V / 7 Ah
1
8 Hours recover to 90% capacity
Green lighting
Green flashing every 10 seconds
Green flashing every second and red lighting
Red lighting
Sounding every 10 seconds
Sounding every second
Continuously sounding
228 (D) x 207 (W) x 82.5(H)
2.7
0-90 %
0- 40°C (non-condensing)
Nano800
800 VA / 480 W
12V / 9 Ah
3.1
1
www.fsp-ps.de
3
FP SERIES
Line Interactive UPS
400VA-2KVA
Applications:
Built-in AVR
Computer
Simple Solution for Home and
Office Users
FP Series is a “Lite” UPS to protect your power issue on personal computers. It provides comprehensive protection in a small and economic package. Not only offering greater comprehensive power protection against surges and spikes, it also provides pure voltage with built-in AVR stabilizer. The UPS will continue providing clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability, perfect for any home or small office application.
GENERAL FEATURES
Compact size
Excellent microprocessor control guarantees high reliability
Boost and buck AVR for voltage stabilization
Auto restart while AC is recovering
Simulated sine wave
Off-mode charging
Cold start function
Generator compatible(option)
FP Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
FP 400
400 VA / 240 W
FP 600
600 VA / 360 W
FP 800 FP 1000
1-phase in / 1-phase out
800 VA / 480 W 1000 VA / 600 W
FP 1500
1500 VA / 900 W
FP 2000
2000 VA / 1200 W
INPUT
Voltage
Voltage Range
Frequency Range
OUTPUT
AC Voltage Regulation(Batt. Mode)
Frequency Range(Batt. Mode)
Transfer Time
Waveform(Batt. Mode)
BATTERY
Battery Type
Numbers
Typical Recharge Time
PROTECTION
Full Protection
INDICATORS
AC Mode
Battery Mode
Fault
ALARM
Battery Mode
Low Battery
Overload
Fault
12V / 4.5 Ah
1
PHYSICAL
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
3.55
Product specifications are subject to change without further notice
12V / 7 Ah
1
4 hours recover to 90% capacity
Green lighting
Green flashing
N/A
279 (D) x 101 (W) x 142 (H)
42
110/120 V or 220/230/240 V
60/50 Hz (auto sensing)
4.9
81-145 V / 140-290 V
±10%
60 Hz or 50 Hz ±1 Hz
Typical 2 ~ 6 ms
Simulated Sine Wave
12V / 9 Ah
1
12V / 7 Ah
2
Overload, discharge, and overcharge protection
Sounding every 10 seconds
Sounding every second
Sounding every 0.5 second
Continuously sounding
8.2
12V / 9 Ah
2
4-6 hours recover to 90% capacity
0-90% RH @ 0-40°C (non-condensing)
Less than 40 dBA @ 1 Meter
Green lighting
Yellow flashing
Red lighting
320 (D) x 130 (W) x 182 (H)
10.4
12V / 9 Ah
2
10.6
4
Backup time table for FP series
MODEL
FP 400
FP 600
FP 800
FP 1000
FP 1500
FP 2000
Type of Battery
12V 4.5Ah
12V 7.0Ah
Battery
Total Q'ty
1
1
12V 9.0Ah
1
12V 7.0Ah
12V 9.0Ah
12V 9.0Ah
2
2
2
NOTE : Data given are the average values, not the minimum values.
25% Load
15min
19min
20min
18min
18min
15min
Back Time (minutes)
50% Load
8min
6min
75% Load
3min
30sec
3min 8min
5min
6min30sec
3min44sec
1min50sec
3min30sec
1min36sec
100% Load
40sec
5sec
5sec
28sec
1min20sec
36min
www.fsp-ps.de
5
CP SERIES
Line Interactive UPS
750VA-2KVA
Applications:
Built-in AVR POS Mini Servers
Computer
Pure Sine Wave UPS
With pure sine wave output waveform,
FSP CP 750/1K/1.5K/2K Series offers perfect power protection for sensitive equipment. It provides comprehensive LCD display for users to monitor the power and UPS status. CP implemented powerful protection and built-in automatic voltage regulator, it secures your data loss from power outage, surge, brownout and swell.
GENERAL FEATURES
Line interactive pure sine wave UPS
Digitalized PWM-based controller
Excellent microprocessor control guarantees high reliability
Boost and buck AVR for voltage stabilization
Optional USB and RJ45 protection
Perfect protection for mini servers, POS,& workstation
CP Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
INPUT
Voltage
Voltage Range
Frequency Range
OUTPUT
AC Voltage Regulation(Batt. Mode)
Frequency Range(Batt. Mode)
Transfer Time
Waveform(Batt. Mode)
BATTERY
Battery Type
Numbers
Typical Recharge Time
PROTECTION
Full Protection
INDICATORS
AC Mode
ALARM
Battery Mode
Low Battery
Battery Mode
Overload
Fault
PHYSICAL
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level Less than 45dB
CP 1000
1-phase in / 1-phase out
CP 1500
1000 VA / 700 W 1500 VA / 1050 W
110/120 V or 220/230/240 V
81-145 V / 162-290 V
60/50 Hz (auto sensing)
12V / 7 Ah
2
6 hours recover to 90% capacity
Overload, discharge, and overcharge protection
AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery
MANAGEMENT
USB & RS-232 Port
Product specifications are subject to change without further notice
CP 750
750 VA / 480 W
12V / 9 Ah
1
6.8
350 (D) x 146 (W) x 160 (H)
9.0
±10%
50 Hz or 60 Hz ± 1 Hz
Typical 2-6 ms, 10ms max.
Pure SineWave
Sounding every 10 seconds
Sounding every second
Sounding every 0.5 seconds
Sounding every 2 second
Continuously sounding
12V / 9 Ah
2
0-90 % RH @ 0- 40°C (Non-condensing)
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC
CP 2000
2000 VA / 1400 W
12V / 10 Ah
397 (D) x 146 (W) x 205 (H)
12.2
Less than 55dB
2
13.7
Backup time table for CP series
MODEL
CP 750
CP 1000
CP 1500
CP 2000
Type of Battery
12V 9.0Ah
Battery
Total Q'ty
1
12V 7.0Ah
12V 9.0Ah
12V 10Ah
2
2
2
NOTE : Data given are the average values, not the minimum values.
25% Load
18min
28min
18min
16min
Back Time (minutes)
50% Load
6min30sec
75% Load
2min30
7min30sec
5min30sec
4min
4min20
3min
2min10sec
100% Load
10sec
1min30
40sec
10sec
6
www.fsp-ps.de
7
EUFO SERIES
High-Level Line-Interactive UPS
1.1KVA-3KVA
Applications:
Work-Stations Rack server Network device
Multiple communication
Professional Line-Interactive UPS
Solutions
Eufo series rating is from 1.1kVA to 3.0kVA and implemented protect functions for power failure,surge overvoltage and brownout. Rack/Tower with easy-shift
LCD design is flexible for installation. moreover, this series built-in Efficiency corrective Optimizer(ECO) that the efficiency is up to 98% for more energy saving. The application is suitable for networking, telecom, server and mission-critical applications.
GENERAL FEATURES
Pure sine wave
Output power factor 0.8
Microprocessor control optimizes reliability
User-friendly and easy-shift LCD design
Rack/Tower 2 in 1 design
Built-in boost and buck AVR
Programmable power management outlets
ECO operation for energy saving
(Efficiency Corrective Optimizer)
Emergency power off function (EPO)
RJ45 Surge protector
Hot-swappable battery design
Built-in internal battery & extend battery function
Multiple communication available
Microprocessor-based line interactive design
Eufo series UPS is designed with microprocessor controller for fast response to power disturbances.
Pure sine wave output
With pure sine wave output, Eufo series guarantees compatibility for all kinds of loads. It's perfect power protection for versatile applications such as networking, telecom and other mission-critical applications.
User-friendly and easy-shift LCD display
The front panel digital display can be easily shifted through LCD setting to suit the installation format, vertically stand or flat wall mount.
Eufo Series
ECO operation for energy saving
(Efficiency Corrective Optimizer)
The ECO function allows cost-effective operation of
UPS Systems as high as 98%. In this operation mode, load is supplied by the mains. When battery is fully charged, the fan will stop running for energy saving.
In the event of a mains failure, the inverter takes over the load and provides supply continuity to the connected systems.
98%
ECO
Emergency Power Off Function (EPO)
This feature can secure the personnel and equipment in case of fires or other emergencies.
Hot-swappable battery design
This design ensures clean and uninterruptible power to protected equipment during battery replacement.
8
90°
Rack / Tower design
Eufo series is designed in true universal-mount case. It can be easily installed as floor-standing tower or in
19-inch rackmount bracket.
Extend battery capacity Function
Eufo series offer extend battery capacity function for long back up time purpose.
19" rack-mounting
Floor-standing Tower
Built-in boost and buck AVR
With built-in voltage regulator, the UPS will maintain regulated nominal output without using battery power during brownouts and overvoltages.
Output power factor 0.8
Eufo series is a high-density UPS with output power factor 0.8 to provide higher performance and efficiency to critical applications.
Programmable power management outlets
With programmable power management outlets, users can easily and independently control load segments.
During power failure, this feature enables users to extend battery time to missioncritical devices by shutting down the non-critical devices.
RJ-45 Surge protector
Eufo Series implements RJ-45 Surge Protection ports to prevent Ethernet network damage caused by lightning or ground surges.
Multiple communication
- USB port
- RS-232 port
- Intelligent slot for SNMP or Relay Card (option)
Also offer free monitoring software, ViewPower, downloaded from the internet. This advanced and networking software supports various operating systems and multiple languages.
SNMP Card AS400 Card
Programmable Outlets (P1)
- connect to non-critical devices
www.fsp-ps.de
9
Eufo Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
EU-1101RS/TS
1.1 kVA / 0.88kW
EU-1102RS/TS
Single phase with ground
2.0 kVA / 1.6kW
EU-1103RS/TS
3.0 kVA / 2.4kW
INPUT
Voltage Range
Acceptable Voltage Range
Frequency Range
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer Time
Waveform (Batt. Mode)
EFFICIENCY
AC Line Mode
Boost/Buck Mode
Battery Mode
BATTERY
Battery Type
Numbers
Typical Recharge Time
Charging Current (max.)
Float Charging Voltage
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
Standard
Model
Long-Run
Model
Dimension, D x W x H(mm)
Net Weight (kgs)
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
Optional SNMP
Product specifications are subject to change without further notice
24 V
2
1.0 A
27.4 VDC ± 1%
1 x IEC 320 C14
8 x IEC 320 C13
380 (D) x 438 (W) x 88 (H)
14,23
380 (D) x 438 (W) x 88 (H)
10,8
110/120 VAC or 208/220/230/240 VAC
81 - 145VAC or 162-290 VAC
50Hz/60Hz (Auto sensing)
110/120 VAC or 208/220/230/240VAC
± 3% (Before battery Alarm)
50 Hz ± 0.2 Hz or 60 Hz ± 0.2 Hz
3:1 (max.)
8% max @ 100% linear Last ; 15% max @ non linear mode
2-6ms (typical), 10ms max.
Pure Sinewave
88%
90%
85%
48 V
4
4 Hours recover to 90% capacity
1.0 A
54.6 VDC ± 1%
Sounding every 10 seconds
Sounding every second
Sounding twice every second
Continuously sounding
1 x IEC 320 C14
8 x IEC 320 C13
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
480 (D) x 438 (W) x 88 (H)
23,1
480 (D) x 438 (W) x 88 (H)
14.0
20-90% RH @ 0-40°C (Non-condensing)
Less than 45 dBA @ 1 Meter
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Power management from SNMP manager and web browser
72
6
1.0 A
82.1 VDC ± 1%
1 x IEC 320 C20
6 x IEC 320 C13 / 1 x IEC C19
600 (D) x 438 (W) x 88 (H)
32,24
600 (D) x 438 (W) x 88 (H)
18,0
Backup Time Table for Eufo Series
EU-1101
EU-1102
EU-1103
Battery Bank
+ 1xBB-24/18RT (4 x 9Ah Batteries)
+ 2xBB-24/18RT (8 x 9Ah Batteries)
+ 3xBB-24/18RT (12 x 9Ah Batteries)
+ 4xBB-24/18RT (16 x 9Ah Batteries)
+ 1x48/18RT (8 x 9Ah Batteries)
+ 2x48/18RT (16 x 9Ah Batteries)
+ 3x48/18RT (24 x 9Ah Batteries)
+ 4x48/18RT (32 x 9Ah Batteries)
+ 1xBB-72/18RT (12 x 9Ah Batteries)
+ 2xBB-72/18RT (24 x 9Ah Batteries)
+ 3xBB-72/18RT (36 x 9Ah Batteries)
+ 4xBB-72/18RT (48 x 9Ah Batteries)
58
131
225
270
60
130
230
288
25%
Backup Time with Load (Min)
50% 75%
112
256
358
512
57
139
221
280
36
86
152
218
28
62
100
163
17
40
60
94
28
66
107
167
17
41
62
92
100 %
25
60
98
153
10
26
44
69
10
26
43
68
www.fsp-ps.de
KNIGHT SERIES
10
PF0.8 Online UPS
1KVA-10KVA
Applications:
Server POS ATM Computer
Reliable UPS Solution
Knight Series is specifically designed for operation in poor power areas. Built-in internal battery and extend battery connector in tower model, user can extend autonomy time via plug and play battery design. The
Reliable design is ideal for Banking, ATM, and other business critical application.
GENERAL FEATURES
True double-conversion
Microprocessor control optimizes reliability
Input power factor correction ≧ 0.99
Output power factor 0.8
Wide input voltage (110 V – 300 V)
Converter mode available
ECO mode for energy saving
Generator compatible
S NMP Function operate with USB or RS-232 synchronizingly
Comprehensive LCD Display for access & setting
11
Knight Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
INPUT
Low Line Transfer
KN-1101-TS
1000 VA / 800W
KN-1102-TS
Single phase with ground
2000 VA / 1600W
KN-1103-TS
30000 VA / 2400 W
Voltage
Range
Low Line Comeback
High Line Transfer
High Line Comeback
Frequency Range
Power Factor
OUTPUT
Nominal Voltage
AC Voltage Regulation
Frequency Range(Synchronized Range)
Frequency Range(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer
Time
AC mode to Battery mode
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
Line Mode
Battery Mode
ECO Mode
BATTERY
Battery Type
Numbers
Typical Recharge Time
Charging Current (max.)
Charging Voltage
INDICATORS
LCD Display
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
87%
83%
94%
12V / 7 Ah
3
1.0 A
41.0 VDC ± 1%
1 x IEC 320 C14
4 x IEC 320 C13
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(Based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
168 VAC / 148 VAC / 128VAC / 118 VAC ± 5 %
(Based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
≧
0.99 @ Nominal Voltage (100% Last)
200/208/220/230/240VAC
± 1%
47~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
3:1
≦
2 % THD (Linear Load),
≦
4 % THD (Non-linear Load)
Zero
4 ms (Typical)
Pure Sinewave
90%
87%
95%
12V / 7 Ah
6
4 hours recover to 90% capacity
1.0 A
82.1 VDC ± 1%
Last level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continously sounding
1 x IEC 320 C14
8 x IEC 320 C13
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
90%
89%
96%
12 V / 9 AH
6
1.0 A
82.1 VDC ± 1%
1 x IEC 320 C20
6 x IEC 320 C13 / 1 x IEC C19
Dimension, D x W x H(mm)
Net Weight (kgs)
UPS Unit: 397 (D) x 145 (W) x 220 (H)
Battery Pack:
397 (D) x 145 (W) x 220 (H)
UPS Unit: 13
Battery Pack: 18
UPS Unit: 419 (D) x 119 (W) x 318 (H)
Battery Pack:
535 (D) x 190 (W) x 318 (H)
UPS Unit:26
Battery Pack:49.4
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
20-90% RH @ 0-40°C (non-condensing)
Less than 50 dBA @ 1 Meter
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC
Product specifications are subject to change without further notice
UPS Unit: 419 (D) x 119 (W) x 318 (H)
Battery Pack:
535 (D) x 190 (W) x 318 (H)
UPS Unit:28
Battery Pack:67.5
Backup Time Table for Knight Series
Battery Bank
KN-1101TS
+ 1 BB-36/14T - 36V / 14 Ah
+ 2 BB-36/14T - 36V / 28 Ah
+ 3 BB-36/14T - 36V / 42 Ah
KN-1102TS
KN-1103TS
+ 1 BB-72/14T - 72V / 14 Ah
+ 2 BB-72/14T - 72V / 28 Ah
+ 3 BB-72/14T - 72V / 42 Ah
+ 1 BB-72/18T - 72V / 18 Ah
+ 2 BB-72/18T - 72V / 36 Ah
+ 3 BB-72/18T - 72V / 54 Ah
25%
29:25
97:40
155:25
249:05
Backup Time with Load (Min)
50% 75%
15:33
49:48
8:28
27:50
78:34
125:10
46:12
63:24
35:05
113:25
190:25
261:05
25:05
97:45
140:25
201:15
18:11
57:30
95:32
131:08
13:11
49:48
71:28
101:18
12:05
28:21
66:21
56:09
8:30
28:16
45:24
59:10
100 %
5:51
18:12
31:42
45:22
6:46
20:00
34:13
45:41
5:27
17:20
30:10
44:46 www.fsp-ps.de
Knight Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
INPUT
Nominal Voltage
KN-1101RL
1000 VA / 800W
KN-1102RL
2000 VA / 1600W
KN-1103RL
Single phase with ground
30000 VA / 2400 W
200/208/220/230/240VAC
KN-1106RL
6000 VA / 4800 W
KN-1110RL
10000 VA / 8000 W
Voltage Range
Frequency Range
Power Factor
OUTPUT
Nominal Voltage
AC Voltage Regulation
Frequency Range(Synchronized Range)
Frequency Range(Batt. Mode)
Overload
Current Crest Ratio
Harmonic Distortion
Transfer
Time
AC mode to Battery mode
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
Line Mode
Battery Mode
ECO Mode
BATTERY
Battery Type
Numbers
Typical Recharge Time
Charging Current (max.)
Charging Voltage
INDICATORS
LCD Display
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
110-300 VAC ± 1%
88%
87%
93%
12V / 9 Ah
3
41 VDC ± 1%
110-300 VAC ± 1%
40Hz ~ 70 Hz
≧
± 3%
47~ 53Hz or 57 ~ 63Hz
≦
3 % THD (Linear Load),
≦
6 % THD (Non-linear Load)
Zero
4 ms (Typical)
90%
88%
95%
12V / 9 Ah
6
Pure Sinewave
Depending on the capacity of external battery bank
1.0/2.0/4.0/6.0A ± 10%
82.1 VDC ± 1%
110-300 VAC ± 1%
0.99 @ Nominal Voltage (100% Last)
200/208/220/230/240VAC
50Hz ± 0.25Hz or 60Hz ± 0. Hz
100%~110%:audible warning , 110%~130%: UPS shut down in 30 seconds at battery mode or transfer to bypass when the utility is normal >130%:UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal 3:1 ( Max)
3:1 (Max)
91%
89%
96%
12V / 9 Ah
6
82.1 VDC ± 1%
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
1 x IEC 320 C14
4 x IEC 320 C13
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
Optional SNMP
Battery Pack:
410 (D) x 438 (W) x 88 (H)
UPS unit: 13
Battery Pack: 21.3
UPS Unit:
410 (D) x 438 (W) x 88 (H)
Battery Pack:
510 (D) x 438 (W) x 88 (H)
UPS unit: 8.3
Battery Pack: 28.7
20-90% RH @ 0-40°C (non-condensing)
Less than 50 dBA @ 1 Meter
Battery Pack:
630 (D) x 438 (W) x 88 (H)
UPS unit: 10
Battery Pack: 40.8
*Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC
Product specifications are subject to change without further notice
110-300 VAC ± 1% @50% Load
176-300VAC ± 1% @100% Load
46Hz ~ 54 Hz or 56Hz ~ 64 Hz
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
88%
12 V / 9 AH
16
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Power management from SNMP manager and web browser
± 1%
46~ 54Hz or 56 ~ 64Hz
90.3%
95.7%
273 VDC ± 1%
-
Zero
Last level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
Terminal
Terminal
90.7%
89%
96%
12 V / 9 AH
4.0/6.0A ± 10%
20
273 VDC ± 1%
UPS Unit:
580 (D) x 438 (W) x 88 (H)
UPS Unit:
668 (D) x 438 (W) x 88 (H)
Battery Pack:
580 (D) x 438 (W) x 131 (H)
UPS unit: 15
Battery Pack: 57
UPS unit: 18
Battery Pack: 65
Less than 55 dBA @ 1 Meter
12
Backup Time Table for Knight Series
KN-1101RL
KN-1102RL
KN-1103RL
KN - 1106RL
KN - 1110RL
Battery Bank
+1 BB-36/09RT
+1 BB-72/09RT
+2 BB-72/09RT
+1 BB-72/09RT
+2 BB-72/09RT
+1 BB-240/09RT
+2 BB-240/09RT
+1 BB-240/09RT
+2 BB-240/09RT
Backup Time with Load (Min)
25 % 50 % 75%
60 31.0
17.0
30.9
70.0
27.0
58.0
57
120
29.0
64.0
23.3
47.0
13.2
27.0
40.0
57.0
12.0
46.0
13.2
27.0
8.5
18.0
23.0
48.0
7.0
31.0
100%
12
8.5
18.0
5.3
11.0
9.0
40.0
4.0
17.0
www.fsp-ps.de
13
CHAMP SERIES
PF0.9 Online UPS
1KVA-3KVA
Applications:
Work-Stations
Generator compatible
Computer
Compact & Small-Scale Online
UPS Solutions
Champ Series is the high power density double-conversion online UPS with a output power factor 0.9. It’s designed in small cabinet with microprocessor controller.
Champ Series also have USB and RS-232 communication
ports as standard, with a built-in intelligent slot for
additional adapters, protocol converters and relate
contact cards.
GENERAL FEATURES
True double-conversion
Microprocessor control optimizes reliability
Input power factor correction >=0.99
Output power factor 0.9
Wide input voltage (130 V – 280 V)
Converter mode available
ECO mode for energy saving
Generator compatible
Smart SNMP works well with either USB or RS-232 together display allows easy monitoring and access of
UPS status
Champ Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
CH-1101-TS
1000 VA / 900W
CH-1102-TS
Single phase with ground
2000 VA / 1800W
CH-1103-TS
30000 VA / 2700 W
INPUT
Low Line Transfer
Voltage
Range
Low Line Comeback
High Line Transfer
High Line Comeback
Frequency Range
Power Factor
OUTPUT
Nominal Voltage
AC Voltage Regulation
Frequency Range(Synchronized Range)
Frequency Range(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer
Time
AC mode to Battery mode
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
Line Mode
Battery Mode
ECO Mode
BATTERY
Battery Type
Numbers
Typical Recharge Time
Charging Current (max.)
Charging Voltage
INDICATORS
LCD Display
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
Dimension, D x W x H(mm)
87%
83%
94%
12V / 9 Ah
2
1.0 A
27.4 VDC ± 1%
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(Based on Last percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
168 VAC / 148 VAC / 128VAC / 118 VAC ± 5 %
(Based on Last percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
≧
0.99 @ Nominal Voltage (100% Last)
200/208/220/230/240VAC
± 1%
47~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
3:1
≦
2 % THD (Linear Load),
≦
4 % THD (Non-linear Load)
Zero
4 ms (Typical)
Pure Sinewave
90%
87%
95%
12V / 9 Ah
4
4 hours recover to 90% capacity
1.0 A
54.7 VDC ± 1%
Last level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
1 x IEC 320 C14
3 x CEE 7/4 (Schuko)
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
1 x IEC 320 C14
3 x CEE 7/4 (Schuko)
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
282 (D) x 145 (W) x 220 (H)
9.8
397 (D) x 145 (W) x 237 (H)
17.0
20-90% RH @ 0-40°C (non-condensing)
Less than 50 dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 200/208VAC
Product specifications are subject to change without further notice
90%
89%
96%
12 V / 9 AH
6
1.0 A
82.1 VDC ± 1%
1 x IEC 320 C20
4 x CEE 7/4 (Schuko)
421 (D) x 190 (W) x 336 (H)
17.6
Backup Time Table for Champ Series
CH 1101TS
CH 1102TS
CH 1103TS
Battery Bank
Internal battery only (24V:12V-9Ah x 2)
Internal battery only (48V:12V-9Ah x 4)
Internal battery only (72V:12V-9Ah x 6)
25%
Backup Time with Load (Min)
50% 75%
24
26
31
11
12
13
6.0
6.5
7.0
100 %
4.0
4.0
4.5
14 www.fsp-ps.de
15
CUSTOS 9X+
SERIES
High-Level Online UPS
1KVA-10KVA
Applications:
Data Center
Telecom
Networking
Computer
Professional On-Line UPS Solutions
Ideal for medium-density power protection demand,
Power guardian, FSP Custos 9X+ series provides Rack/
Tower to fit diverse environment. Despite its compact footprint, Custos 9X+ incorporates internal battery packs which can be accessed via the front panel for maintenance checks and replacement without removing the UPS from its rack mounting. The LCD display panel can be easily shifted by pressing buttons to suit the installation format, vertical stand or horizontal rack mount. Besides, IT personnel can manage equipment well from learning Intuitive information via LCD display.
GENERAL FEATURES
True double-conversion online UPS
Output power factor 0.9
User-friendly and easy-shift LCD display
Rack/Tower design
Programmable power management outlets
50/60 Hz frequency converter mode
ECO and advanced ECO mode for energy saving
Emergency Power Off Function (EPO)
Hot-swappable battery design
Parallel option for 6K-10K models
True double-conversion online UPS
A true double conversion UPS will rectify input power to offer clean,pure, high level quality power with ± 1% voltage output regulation to fully protect mission-critical devices such as sensitive networks, small computer centers servers, telecom applications, as well as for industrial applications.
Output power factor 0.9
Custos 9X+ series is a high-density UPS with output power factor 0.9 to provide higher performance and efficiency to critical applications.
User-friendly and easy-shift LCD display
The front panel digital display can be easily shifted through LCD setting to suit the installation format, vertically stand or flat wall mount.
90°
50/60 Hz frequency converter mode
Lock output frequency at 50Hz or 60Hz to suit power sensitive equipments.
ECO and advanced ECO mode for energy saving
Thanks FSP Custos9X+ smart design, operation efficiency up to 97% ECO mode implemented.
Furthermore, Custos 9X+ 1-3K even offers advanced
ECO mode to allow UPS to operate at higher efficiency up to 98% for more energy saving.
In these operation modes, load is supplied by the utility. When utility failure, UPS inverter will assume control the load and provide clean power continuity to the connected devices.
98%
Emergency Power Off function (EPO)
The safety function can guarantee & secure the emergency responders, fire fighters not exposed to dangerous voltage, electrical hazard from the device.
This is important if equipment is emitting smoke, fire, or flood, or if person is being electrocuted.
Hot-swappable battery design
This design ensures clean and uninterruptible power to protected equipment during battery replacement.
Rack / Tower design
Custos 9X+ series is designed in true universal-mount case. It can be easily installed as floor-standing tower or in 19-inch rackmount bracket.
19" rack-mounting
Floor-standing Tower
Programmable power management
With programmable power management outlets, users can easily and independently control load segments.
During power failure, this feature will extend battery time to mission critical devices by shutting down the non-critical devices.
RJ-45 Surge protector
Custos 1-3kVA implements RJ-45 Surge Protection ports to prevent Ethernet network damage caused by lightning or ground surges.
Intelligent slot for SNMP or Relay Card
SNMP Card AS400 Card
Parallel Option N+X for 6K-10K models
Custos 9X+ 6K/10K can be parallel operated with up to 3 units to accommodate increses in power demand as well as to attain power redundancy with high system integrity.
16
Programmable Outlets (P1)
- connect to non-critical devices www.fsp-ps.de
17
Custos 9X+ Series
TECHNICAL SPECIFICATIONS
MODEL
CU-1101
PHASE
CAP
ACITY
INPUT
1000 VA / 900 W
L o w Line Transfer
V oltage Range
L o w Line Comeback
F requency Range
Power F actor
High Line Transfer
High Line Comeback
OUTPUT
Output V oltage
CU-1102
Single phase with ground
2000 VA / 1800 W
≧
0.99 @ Nominal V oltag e (100% load)
3000 VA / 2700 W
80 VAC / 70 VAC / 60 VAC / 55 VAC ± 5 % or 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 %
(Based on load percentag e 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
85 VAC / 75 VAC / 65 VAC / 60 VAC ± 5 % or 170 VAC / 150 VAC / 130 VAC / 120 VAC ± 5 %
(Based on load percentag e 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
150 VAC ± 5 % or 300 VAC ± 5 %
140 VAC ± 5 % or 290 VAC ± 5 %
CU-1103
F requency Rang e ( Synchronized Rang e)
Transfer Time
Line mode to Battery mode
Inverter to B ypass
110/115/120/127 VAC or 208/220/230/240 VAC
± 1%
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
5:1 (m a x.)
≦
2 % THD (Linear Load) ;
≦
8 % THD (Non-linear Load)
Zero
4 ms ( Typic al)
Pure Sinewave
EFFICIENCY
AC Mode
ECO Mode
BATTERY
90%
88%
97%
86%
83%
97%
91%
90%
97%
Numbers
Typical Recharge Time
Cha rging Cur ren t (m a x.)
Cha rging V oltage
INDICATORS
LCD Displ ay
ALARM
12 V / 9 AH
2
4 hou rs recover t o 90% capacity
1.0 A
27.4 VDC ± 1%
12 V / 9 AH
4
12 V / 9 AH
6
STD 4hr recover to 90% cap/ LongRun Model depend on external battery capacity
Standard:1.0A / LongRun Model: 1A/2A/4A/8A
54.8 VDC ±1% 82.1 VDC ±1%
Sounding ever y 4 se conds
Sounding every second
Sounding twice every second
Continuously sounding
Overload
F ault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
PHYSICAL
Dimension, D x W x H (mm)
1 x IEC 320 C20
8 x IEC 320 C13
410 x 438 x 88 [2U]
12.9
1 x IEC 320 C20
8 x IEC 320 C13
Standard:630 x 438 x 88 [2U] /
LongRun Model: 410 x 438 x 88 [2U]
Standard:19.5 / LongRun Model: 6.5
1 x IEC 320 C20
1 x IEC 320 C19 / 6 x IEC 320 C13
Standard:630 x 438 x 88 [2U] /
LongRun Model: 510 x 438 x 88 [2U]
Standard:27.4 / LongRun Model: 10.5
Net Weigh t (kgs)
ENVIRONMENT
Humidity
Noise L evel
MANAGEMENT
Smart RS -232 / USB
0-95 % RH @ 0- 40°C (nonc ondensing)
Less than 50d BA @ 1 M eter
Supports Windows 2000/2003/X P /Vi sta/ 2008, Windows MAC
Power management fr om SNMP mana ger and web browser
*LongRun Model without internal battery.
Backup Time Table for Custos Series
CU-1101
CU-1102
CU-1103
Battery Bank
internal battery (2 x 9Ah Batteries)
+1 x BB1-24/18RT (6 x 9AH Batteries)
+2 x BB1-24/18RT (10 x 9AH Batteries)
+1 x BB1-48/9RT ( 4 x 9AH Batteries)
+1 x BB1-48/18RT ( 8 x 9AH Batteries)
+2 x BB1-48/18RT (16 x 9AH Batteries)
+3 x BB1-48/18RT (24 x 9AH Batteries)
+1 x BB1-72/9RT (6 x 9AH Batteries)
+1 x BB1-72/18RT (12 x 9AH Batteries)
+2 x BB1-72/18RT (24 x 9AH Batteries)
+3 x BB1-72/18RT (36 x 9AH Batteries)
25%
Backup Time with Load (Min)
50% 75%
27.0
87.3
156.0
11.0
37.7
70.4
6.0
22.6
43.0
21.0
52.1
117.5
184.0
8.9
22.0
52.0
84.0
4.8
13.1
31.6
52.0
21.9
52.1
117.6
184.0
8.9
21.9
52.0
84.5
4.9
13.1
31.6
52.2
100 %
3.5
16.0
33.2
4.2
8.9
22.0
36.0
4.0
8.9
21.9
36.6
www.fsp-ps.de
Custos 9X+ Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CU-1106
Single phase with ground
CU-1110
CAPACITY
INPUT
6000 VA / 5400 W 10000 VA / 9000 W
Low Line Transfer
Voltage
Range
Low Line Comeback
High Line Transfer
High Line Comeback
Frequency Range
Power Factor
OUTPUT
Nominal Voltage
AC Voltage Regulation
Frequency Range(Synchronized Range)
Frequency Range(Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer
Time
AC mode to Battery mode
Battery mode to AC mode
Inverter to Bypass
Bypass to Inverter
Waveform (Batt. Mode)
EFFICIENCY
Line Mode
Battery Mode
ECO Mode
BATTERY
Nominal Voltage
Battery Type
Numbers
Charging Current (max.)
Float Charging Voltage
176 VAC @ 100% load
110VAC @ 50% load
186 VAC @ 100% load
120VAC @ 50% load
46~54 Hz or 56~64 Hz
≧
300 VAC
290 VAC
0.99 @ 100% Load
200/208/220/230/240 VAC
± 1%
46~54 Hz or 56~64 Hz
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
3:1 (max.)
≦
2 % THD (Linear Load),
≦
4 % THD (Non-linear Load)
Zero
Zero
Zero
Zero
Pure Sinewave
91%
88%
96%
240 VDC
12 V / 7 AH
20 (18-20 pcs adjustable)*
1.0 A
273 VDC (based on battery numbers at 20 pcs)
12 V / 9 AH
20 (18-20 pcs adjustable)*
1.0 A
INDICATORS
LCD Display
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
PHYSICAL
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
Terminal
Terminal
Dimension, D x W x H(mm)
Net Weight (kgs)
UPS unit: 606 x 438 x 133 [3U]
Battery pack:
606 x 438 x133 [3U]
UPS unit: 20
Battery pack: 58
UPS unit: 668 x 438 x 133 [3U]
Battery pack:
606 x 438 x133 [3U]
UPS unit: 23.5
Battery pack: 65
ENVIRONMENT
Operation Humidity
Noise Level
0-95 % RH @ 0- 40°C (non-condensing)
Less than 58 dBA @ 1 Meter Less than 60 dBA @ 1 Meter
MANAGEMENT
Smart RS-232 / USB
Supports Windows 7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=PRating x N/20
** If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
* L means long-run model
Product specifications are subject to change without further notice
Backup Time Table for Custos Series
CU-1106
CU-1110
Battery Bank
+1 x BB1-240/9RT (20 x 9AH Batteries)
+2 x BB1-240/9RT (40 x 9AH Batteries)
+3 x BB1-240/9RT (60 x 9AH Batteries)
+1 x BB1-240/9RT (20 x 9AH Batteries)
+2 x BB1-240/9RT (40 x 9AH Batteries)
+3 x BB1-240/9RT (60 x 9AH Batteries)
25%
Backup Time with Load (Min)
50% 75%
43.0
99.0
150.0
22.0
54.0
88.0
20.0
46.0
71.0
9.0
23.0
38.0
12.9
31.7
43.5
6.0
16.9
23.0
100 %
8.0
22.7
30.4
3.0
12.0
16.0
www.fsp-ps.de
18
19
PROLINE SERIES
3Phase in -3/Single Phase Out
Online UPS
10KVA-30KVA
Applications:
Data Center Networking
Computer Banking
On-Line UPS Solutions
3 Phase Tower UPS Solutions FSP Proline 3P/3P, 3P/1P
Online UPS series integrates true double conversion design, DSP technology, and active input power factor correction design to ensure output power quality and performance at all times. N+X redundancy function available reduce power failure or lost rick. Besides, easy-configurable program via LCD panel enhances the flexibility to meet ever-increasing power demand of IT and networked environment.
GENERAL FEATURES
True double-conversion
DSP technology guarantees high performance
Output power factor 0.8
Wide input voltage range (110-300 VAC)
Active power factor correction in all phases
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving
Emergency power off function (EPO)
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Accepts dual-mains inputs
Generator compatible
Battery number adjustable
Maintenance bypass available
Optional N+X parallel redundancy
Optional isolation transformer offers full isolation and complete common mode noise rejection
Proline Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
PR-3110TL PR-3120TL
3-phase in / 1-phase out
20.0 kVA / 16kW
PR-3130TL
CAPACITY
10.0 kVA / 8kW
30.0 kVA / 24kW
INPUT
Voltage Range
Frequency Range
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range ( Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer Time
Bypass to Inverter
Inverter to Bypass
Waveform (Batt. Mode)
305-478 VAC (3-phase) @ 100% Last
190-520 VAC (3-phase) @ 50% Last
46Hz ~ 54Hz or 56Hz ~ 64Hz
≧ 0.99 @ 100% Last
208/220/230/240 VAC (3Ph + N)
± 1%
46Hz ~ 54Hz or 56Hz ~ 64Hz
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
3:1 (max.)
≦ 2% THD (Linear Last) ; ≦ 5% THD (Non-linear Last)
Zero
Zero
Pure Sinewave
EFFICIENCY
AC Line Mode
Battery Mode
BATTERY
Battery Type
Numbers
Charging Current (max.)
Charging Voltage
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
89%
86%
4.0 A
89%
88%
Depending on the capacity of external batteries
4.0 A
273 VDC ± 1% (based on 20 pcs batteries)
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
91.3%
88%
4.0 A
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
Dimension,
D x W x H(mm)
Terminal
Terminal
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
592 (D) x 250 (W) x 826 (H)
38
Less than 58dBa @ 1 Meter
592 (D) x 250 (W) x 826 (H)
40
0-90% RH @ 0-40°C (non-condensing)
Less than 60dBa @ 1 Meter
815 (D) x 250 (W) x 826 (H)
64
Less than 65dBa @ 1 Meter
Optional SNMP
Windows® 2000/2003/XP/Vista/2008 and Windows® 7/8 /Windows SBS 2011 and Windows server 2012
Power management from SNMP manager and web browser
*When using internal batteries from 18-19, the unit will de-rate according to the below formula: P = PRating x N/20.
Product specifications are subject to change without further notice
Rackmount/Rack Tower Battery Pack
Form Factor
Model Name
Battery Type
Battery Number
Dimension (DxWxH) mm
Net Weight (kgs)
Tower Battery Pack
Form Factor
Model Name
Battery Type
Battery Number
Charger
Dimension (DxWxH) mm
Net Weight (kgs)
3U
BB-240/RT
12 V / 9 Ah
20 pcs
580 x 438 x 131 [3U]
65
BB-240/18T
12 V / 9 Ah
40 pcs x
592 x 250 x 576
125
Tower
BB-240/27T
12 V / 9 Ah
60 pcs
4A
830 x 250 x 576
190
20 www.fsp-ps.de
21
Proline Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
PR-3310TL
10.0 kVA / 8kW
PR-3320TL
3 phase in / 3 phase out
20.0 kVA / 16kW
PR-3330TL
30.0 kVA / 24kW
INPUT
Voltage Range
Frequency Range
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency Range ( Synchronized Range)
Frequency Range (Batt. Mode)
Current Crest Ratio
Harmonic Distortion
Transfer Time
Bypass to Inverter
Inverter to Bypass
Waveform (Batt. Mode)
EFFICIENCY
AC Line Mode
Battery Mode
BATTERY
Battery Type
Numbers
Charging Current (max.)
Charging Voltage
ALARM
Battery Mode
Low Battery
Overload
Fault
AC INPUT & OUTPUT CONNECTORS
AC Input Connector
AC Output Connector
STANDARDS
Safety / EMC
PHYSICAL
Dimension, D x W x H(mm)
Net Weight (kgs)
ENVIRONMENT
Operation Humidity
Noise Level
MANAGEMENT
Smart RS-232 / USB
Optional SNMP
89%
86%
4.0 A
592 (D) x 250 (W) x 826 (H)
38
Less than 58dBa @ 1 Meter
305-478 VAC (3-phase) @ 100% Load
190-520 VAC (3-phase) @ 50% Load
46Hz ~ 54Hz or 56Hz ~ 64Hz
≧ 0.99 @ 100% Load
3x400 VAC (3Ph + N)
± 1%
46Hz ~ 54Hz or 56Hz ~ 64Hz
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
3:1 (Max.)
≦ 2% THD (Linear Load) ; ≦ 5% THD (Non-linear Load)
Zero
Zero
Pure Sinewave
89%
88%
Depending on the capacity of external batteries
4.0 A
273 VDC ± 1% (based on 20 pcs batteries)
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
Terminal
Terminal
IEC 62040-1 (safety) / IEC-62040-2 (EMC) / CE
592 (D) x 250 (W) x 826 (H)
40
0-90% RH @ 0-40°C (non-condensing)
Windows® 2000/2003/XP/Vista/2008 and Windows® 7/8 /Windows SBS 2011 and Windows server 2012
Power management from SNMP manager and web browser
*When using internal batteries from 18-19, the unit will de-rate according to the below formula: P = PRating x N/20.
Product specifications are subject to change without further notice
89%
87%
4.0 A
815 (D) x 250 (W) x 826 (H)
Less than 60dBa @ 1 Meter
62
Backup Time Table for Proline Series
PR-3310TL
PR-3110TL
PR-3320TL
PR-3120TL
PR-3330TL
PR-3130TL
Battery Bank
+ 1 BB-240/9RT - 240V / 9 Ah
+ 1 BB-240/18T - 240V / 18 Ah
+ 2 BB-240/18T - 240V / 36 Ah
+ 1 BB-240/27T - 240V / 27 Ah
+ 2 BB-240/27T - 240V / 54 Ah
+ 1 BB-240/18T- 240V / 18 Ah
+ 2 BB-240/18T - 240V / 36 Ah
+ 1 BB-240/27T - 240V / 27 Ah
+ 2 BB-240/27T - 240V / 54 Ah
+ 1 BB-240/27T - 240V / 27 Ah
+ 2 BB-240/27T - 240V / 54 Ah
+ 3 BB-240/27T - 240V / 81 Ah
25
25
%
61
136
98
200
Backup Time with Load (Min)
50% 75%
12.5
26
5.5
15.5
61
43
98.2
37
26
61
25.9
61
43
98
10.6
26
18
43
6.0
15.5
10.6
26
26
61
98.2
11
26
43
6.0
16
26
100 %
2.5
12.5
51
18
43
7.1
12.7
7.1
18
4
10.6
18.0
www.fsp-ps.de
AGIES SERIES
22
3 Phase High Efficiency UPS
10-120kVA
Telecom Networking Medical Industrial
machinery
3-Level Design UPS
Agies is applied to the high technology to reach high
efficiency with output power factor 0.9. It can easily adapt to all kinds of diverse and complicated loads, such as the non-linear systems (IT systems), strongly inductive or capacitive loads, discharge lamps, and induction motors. To meet diverse applications, it is allowed to have alternative battery configuration based on different backup time requirement. To facilitate expansion easily, this unit can be set up in parallel-redundant systems with up to 4 units.
GENERAL FEATURES
Online double conversion technology with DSP control
Advanced control with Adaptive Feed Forward
Cancellation (AFC) technology for
Low harmonic distortion
Input current distortion THDi < 1%
Input power factor 0.99 at 10% load
Output efficiency up to 95%
Space-saving compact design
Front access makes maintenance and replacement easily
Control designed to withstand all kinds of loads
Parallel redundant operation with up to 4 units
Variety of communication options available
Remaining backup time calculation
5.7" Graphic LCD panel design with multiple languages for easy-configuration
23
Agies Series
The Most Versatile Solution for Power Protection
Agies, applied with state-of-the-art PWM-transformerless technology, can easily adapt to all kinds of diverse and complicated loads, such as the non-linear systems (IT systems), strongly inductive or capacitive loads, discharge lamps, and induction motors. Ranging from 10K-120KVA, Agies is designed in terms of criteria of maximum efficiency and energy savings with highly compact format. It makes installation and operation easily and eco-environmentally.
Each unit also has a wide range of communication possibilities and a large variety of options to fill out customers’ diverse inquiries. To facilitate expansion easily, this unit can be set up in parallel-redundant systems without any need for additional hardware in the near future
Online double conversion technology with
DSP control
Agies is applied online double conversion technology to effectively insulate against network disturbances and enable higher load uptime. A
Digital Signal Processor (DSP) control provides an improved solution with high performance.
Advanced control with Adaptive Feed
Forward Cancellation (AFC) technology for very low harmonic distortion
By cancelling input current and output voltage harmonics, the harmful effects of harmonic injection into the power network is eliminated and it will enhance load integrity.
Very low input current distortion (THDi < 1%)
AFC cells are used to achieve extremely low distortion values. Low input current distortion rat
THDi < 1% at full load and also THDi < 5% with very small load (10% of load). This will avoid the distortion of the electrical network upstream of the UPS, resulting in savings from the optimal use of the cables and protection devices in the electrical network.
Output efficiency up to 95%
Applied with DSP controller and the forth generation
IGBT transistors, the UPS can achieve high efficiency of up to 95%. It will save consumed energy due to lower heat losses and make a longer lifespan for the critical components of the unit.
EFFICIENCY
100%
80%
60%
40%
20%
0%
20K EFF I CIENCY
20% 40%
LOAD
60% 80% 100%
Space-saving compact design
The use of transformerless technology allows a considerable reduction of the weight and volume of the units.
Input power factor 0.99 at 10% load
Lower power losses would result in reduced consumption, lower operation and maintenance costs.
INPUT POWER FACTOR
1,20
1,00
0,80
0,60
0,40
0,20
0,00
0% 25% 50%
LOAD
75% 100%
Front access makes maintenance and replacement easily
An important consideration has been given to allow generous access to the unit’s electronic cards and power components. All the boards are accessible by front panel for easily maintenance and replacement.
www.fsp-ps.de
Agies Series
Control designed to withstand all kinds of loads
In Agies series, the control is designed to be able to withstand all kinds of loads: resistive, capacitive, non-linear, discharge lamps, induction motors, speed drivers, etc. It makes the UPS tremendously versatile and flexible in supplying power to different types of electronics. To make it simple to adapt the
UPS for different environment, there are a large number of parameters that can be programmed locally or remotely.
Parallel redundant operation with up to 4 units
Up to 4 units in parallel can be operated without additional hardware, to accommodate increases in power demand as well as to attain power redundancy with high system integrity.
Variety of communications and options available
The UPS has provided the following standard communication selections:
Relay interface
RS-232/485 port
1 x SNMP slot
Modbus RTU / SEC protocol
2 x connectors for parallel connection
Over 60% materials recyclable
The UPS uses more than 60% recyclable materials for being more respectful of the environment.
Remaining backup time calculation
By using powerful algorithms, an estimated remaining backup time can be calculated and help users for further arrangement in the event of a prolonged power outage.
Optional fast-access touch screen for 5.7" LCD panel
We also offer touch panel for 5.7" LCD panel. Touch screen provides higher operability on configuration and information display.
5.7" graphic LCD panel design with multiple languages for easy-configuration
With graphic design, it becomes more intuitive to configure programs. Besides, we also offer multiple languages for 5.7" LCD version. Users can easily configure programs and read displayed messages.
EN FR ES DE CN
Applications:
Agies vides great flexibility and adaptability to suit versatile applications.
Data centers (computing centers, centralized sales/distribution systems, hosting, housing, ...)
IT-networks (server farms, local computer networks, network switches and hubs,...)
Financial services (bank offices, automatic cash dispensers, card payment authorisation systems,...)
Industrial processes (productive and control systems, industrial machinery, emergency and lighting systems,...)
Telecommunications
Infrastructures (hospitals, airports, tunnels,...)
24 www.fsp-ps.de
25
Agies Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CAPACITY
INPUT
Nominal Voltage
Acceptable Voltage Range
F requency
Agies 10K
10K V A/9KW
Agies 15K Agies 20K Agies 30K Agies 40K Agies 60K
3-phase in / 3-phase out
15K V A/13.5KW 20K VA/ 18KW 30K V A/27KW 40K VA/ 36KW 60K V A/54KW
< 1.5% @ 100% load
< 6.0% @ 10% Load
3 x 400V (3Ph + N)
+15% or –20%
50 / 60 Hz ±5 %
< 1.0% @ 100% load
< 5.0% @ 10% Load
Agies 80K Agies 100K Agies 120K
80K V A/72KW 100K V A/90KW 120K V A/108KW
< 1.5% @ 100% Load
< 6.0% @ 10% Load
Power F actor
INVERTER
Nominal Voltage
Precision
F requency
M
W ave f orm
1.0
3 x 400V (3Ph + N)
50/60 Hz synchr onised ±4 % With mains a bsen t ±0.05%
10 Hz /s
Pure Sinewave
< 0.5% (Linear Load) ; < 1.5% (Non-linear Load)
120º ±1% (Balanced load) ; 120º ±2% (imbalances 50% of the load) Phase Displacement
Dynamic Recover y Time
Admissible Overload
Admissible Crest F actor
Admissible Power F actor
Imbalance Output Voltag [email protected] 100%
Unbalanced Load
Current Limit
STATIC BYPASS
T ype
Voltage
F requency
Phase Ov
3.4 : 1
High erload: 125% for 10 min., 150% for 60s ; T overload, short-cir cuit: RMS Voltag
<1% otal Ov
3.2 :1 e Limit ; High C erload: 112.5% for 10 min., 135% for 60s restF actor curren
2.8 : 1 t: P eak Voltage Limit
3.2 :1
T rans fer Time
Admissible Overload
T rans f er to Bypass
Retrans f er
MAINTENANCE BYPASS
T ype
Voltage
F requency
90.0% 90.5% 91.0%
Solid state
3x400V (3Ph + N)
50/60 Hz
Mic roprocessor control
Zero
400% for 10 sec.
Immediate, f or overloads abov e 150%
Automatic after alarm clear
92.0%
Without interruption
3 x 400V (3Ph + N)
50/60 Hz
92.5% 93.0% 94.0% 93.0%
BATTERY
Bac k-up Time (minu t es)
M a x. Cha rging Current
PHYSICAL
Dimension, D x W x H(mm)
N e
12V 4.5Ah
5
78
178
12V 4.5Ah
3
86
186
23.5 A
12V 7Ah
5
94
249
12V 9Ah
3
770 x 450 x 1100
110
290
12V 12Ah
3
122
357
47 A
162 231
-
-
70.5 A
805 x 590 x 1320
-
*N O TE: When temperature is abov e 30° C, the output power will be derat ed. The output p ower is derated t o 90% a t 31°C -35°C and 80% a t 36°C -40°C.
255
93.3%
188 A
External Battery Cabinet for HV
Dimensions, D x W x H (mm)
Built-in Battery Type
Battery Numbers
Net Weight (Kg)
700 x 450 x 1100
12V 12Ah
Dimensions, D x W x H (mm)
Built-in Battery Type
Battery Numbers
Net Weight (Kg)
250
Type 2
805 x 590 x 1320
12V 26Ah
710
*Product specifications are subject to change without further notice.
Type 1
62 pcs (2 x 31)
62 pcs (2 x 31)
700 x 450 x 1100
12V 18Ah
410
Type 3
980 x 650 x 1320
12V 40Ah
1020 www.fsp-ps.de
MPLUS SERIES
26
Hot Swappable Modular UPS
30-210kVA / 20-200kVA
Data Center Networking Industrial Banking
PowerFactor 1 Modular UPS
Mplus series is a truly double converion online modular UPS with high scales from 20kW/30kW to
200kW/210kW. Modular design implemented in STS,
Power module, and battery, it achieves low MTTR,
technican will streamline and simplify their maintenance and replacement, furthermore end
customer will be more flexable, more convenient to
escalate their power demand in the future.
GENERAL FEATURES
Power Factor 1.0** (kVA = kW)
Efficiency up to 96%
20/30 kVA per module
Adjustable charging current
Adjustable Battery Voltage
Dual input function
Power modules are hot swapable
Redundancy ready
Easy maintenance in service
Emergency power off function (EPO)
Maintenance Bypass included
5,7" LCD Panel
27
Mplus Series
High efficiency online double conversion technology
Mplus is applied online double conversion technology with high performance over 94.5% at 50% load. It significantly reduces overall Total Cost of Ownership
(TCO).
High scalability
DSP control provides an improved solution with high performance. Integrated with modular design and parallel technology, Mplus simplifies future power expansion.
Unity output power factor
Mplus delivers unity output power (kVA=kW) providing the maximum power capacity to mission critical loads. It satisfies the requirements of the latest servers and optimizes IT investment with every penny.
Modular design lowers MTTR
Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR (Mean Time To Repair).
N+1 or N+X parallel redundancy for power guarantee
Scalable architecture allows you to optimize cost expense to meet power demands by vertically expanding in a single rack enclosure from 30KVA to
210KVA and achieve N+1 or N+X redundancy in the same rack.
Optional 10" touch LCD panel
Ease of installation and maintenance
Built-in maintenance bypass assures continuous power to critical loads during UPS maintenance. Besides, to facilitate installation and maintenance, all panel control and connectors are front accessibility.
Flexible battery configuration adapts different applications
Battery numbers can be adjusted flexibly. It will adapt different power demands and shorten system downtime.
Battery voltage can be set from 32 to 40 pieces per string.
Graphic 5.7” LCD design for easy management
Designed for easy management, Mplus is equipped with
5.7” graphic LCD screen. Intuitive design enhances display information identified and advanced configuration.
High reliable operation with redundant power supply in STS
Mplus provides 2 power supplies in STS. It will ensure no shutdown risk for STS.
User-adjustable charging current
Mplus provides maximum 8A or 6A charging current for every power module and it's user-adjustable based on requirement.
High overload capability
Mplus supports, 110% overload for 60 minutes, 125% for 10 minutes, and 150% for 1 minute.
Standard Series Extended Series
Mplus 30U-90 Mplus 42U-120 Mplus 30U-120 Mplus 30U-180 Mplus 42U-200 Mplus 42U-210 www.fsp-ps.de
LCD Panel Display
YEAR 1:
INITIAL INSTALL
Mplus Series
•
• Input / Output
• Maintenance Bypass
Breakers
STS Module Includes
Communication Ports
Power Module
Battery Module
YEAR 3:
EXPANSION
Expandability. Flexibility. Uninterruptibility.
Via Modular architecture
Thanks MPLUS Modular design architecture, scalable and compact size 3U rackmount power module that supplies
30kW of backup power protection. Whole system can be easily expanded as your data center growth. Plug and play
N+X,N+1 redundancy design optimizes customer's power demand and enhance the capital investment plan and deployment.
MPLUS smart intelligent load sharing system proportionates workload into each power module without linking any extra communication, paralleled, current share cables. Besides, system is no need to shutdown or interrupt, MPLUS can provide backup support during power module maintenance.
YEAR 5:
FURTHER EXPANSION
28
42U enclosure
30 kW Mplus occupies 3U of space
Total rack space: 15U
Redundant N+1 configuration:
30KW UPS Power modules = 210KW of backup power 7+1, 8 modules share the load equally.
No wiring to extend power module
MPLUS Offers 20KVA and 30KVA power module, no matter which model, e.g, in 30U extend model, power module can be installed up to 6PC, 120KVA with 20KVA or 180KVA with 30kVA 6PC power modules. In addition, same cabinet reduces wiring, or human error operation issue and ensures backup power increased to cover new power demand in a right way.
MPLUS also offers 15U cabinet as economy purpose, full range power rating is not only suitablit for large IT room, Datacenter, but also adquate to infrastructures and different purposes.
MPLUS 30U/42U extremely flexible characteristic, One power module with 30KW unity power factor can be single or multi module operation. In
42U cabinet model can up to 7+1 modules 210kW, elastic design offers proper backup power protection with appropriate capital investment whenever needed.
15 U 90kW
www.fsp-ps.de
29
Mplus Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
CABINET CAPACITY*
B A TTE R Y TYPE
Mplus 15U
90K W or
9
60K
0
W
Mplus 30U
90K W
9 0 Mplus 42U
120 K
-120
W
Mplus 30U -120
3-phase in / 3-phase out
120 K W or 80K W
Mplus 30U 18 0
180K W or 120 K W
Mplus 42U
200 K
-200
W
Mplus 42U -210
210 K W
ON
V
Fr ol
E P ta
O WER M ge Rang
Nominal F r
Power Factor
ODULE e equency equency Rang e
CAPA
M AX . P O WER M ODULE NO .
M AX . B A TT ERY SE T NO .**
INPUT
Nominal V ol ta g e
CIT Y
PM-20HV : 20K VA/20 K W or PM-30HV :
30 K VA/30 K W
3
3
PM-30HV
30 K VA/30
3
3
K
:
W
PM-30HV
30 K VA/30
4
5
K
:
W
PM-20HV
4
-
: 20
PM-30HV :
K
30
VA/20
K
K
VA/30
W or
K W
6
-
3 x 380 VA C/400 VA C/415 VAC
(3Ph+N)
305 ~ 478 VAC a t 100% load; 208 ~ 304 VAC a t <70% load
50/60Hz (Au t o Sensing)
40Hz ~70Hz
> 0.99 @ 100% Load , >0.98 @ 50% Load
< 3% @ 100% load
OUTPUT
Nominal V
Nominal F
Fr r ol ta g e equency equency Rang e (S
Overload Capability ynch r onized)
3 x 380 VA C/400 VA C/415 VA C (3Ph+N)
≦
± 1% Typi c al (balanced load) ;
≦
± 2% Typi c al (unbalanced load)
≦
± 5% Typi c al
50/60Hz
46Hz ~ 54Hz or 56Hz ~ 64Hz
1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150%
≦
1.5% THD (Linear Load) ;
≦
4% THD (Non-linear Load)
Up t o 94.5%
BATTERY / CHARGER
Nominal
Ma
Minimum
Flo a ximum t Cha
V
Boost Cha r r ol
V
V ta ol ol g ta ta ging e
V ging g g
V e e ol ol ta ta g g e e
+/- 216V (12V x 36 pcs)
+/- 240V (12V x 40 pcs)
+/- 192V (12V x 32 pcs)
2.25V / Cell
2.35V / Cell
Y es
8A f or 30 KW p ow er module
6A f or 20 KW p ow er module
Ma ximum Cha r ging Cur re n t
(Per Pow er Module)
PHYSICAL
Ca bin et Dimensi o n (D x W x H) mm
N et W eigh t ( Kg)
ENVI R ONMENT
1100 x 514 x 763
182
8A
1100 x 600 x 1475 1100 x 600 x 2010 1100 x 600 x 1475 1100 x 600 x 1475
183.5
932 335 or 333 437.5 or 434.5
0 ~ 40°C
0 ~ 95% nonc ondensing
<1000m for Nominal p ower
IP 20 IP Class
MANAGEMENT
RS -232/USB Supports Wind ow s 2000/2003/X P /Vis ta/ 2008, Wind ow s 7/8 , Linux and M AC
Pow er management f r om SNMP manager and w eb b row ser
STANDARDS
Sa f e
EMC ty I E C/EN 60950-1; I E C/EN 62040-1
I E C/EN 62040-2 C ate g or y C3
*When t empe ra tu r e is ab o v e 30
℃
, the output p ower f act or will be derat ed, 0.9 at 31
℃
~35
℃
and 0.8 a t 36
℃
~40
℃
.
PM-20HV :
20 K VA/20 K W
10
6A
625
PM-30HV :
30 K VA/30 K W
1100 x 600 x 2010
7 + 1
-
8A
549
Model
PM-20HV
PM-30HV
Battery Module
Description
3P /3P 20K VA / 20 KW p ow er module
3P /3P 30K VA / 30 KW p ow er module
10 pcs of 12V 9Ah batteries
Dimension DxWxH(mm)
650 x 440 x 132(3U)
650 x 440 x 132(3U)
735 x 107 x 155
Weight (kg)
34
34.5
26 www.fsp-ps.de
iDL SERIES
30
Industrial UPS
10KVA-800KVA
Applications:
Reliable & Dependable Power Solution
FSP iDL industrial UPS designed true double conversion
and galvanic isolation with static bypass switch which solves ultimately all types of input power disturbances, such as noise, lightning, and leakage current etc.
Through advanced technology of PWM, DSP and IGBT designed, iDL UPS continually process control and become a high frequency and efficiency product, also choosed the high reliable components which can tolerent & endure extreme power problems to ensure, to offer the best power quality for the protection of industrial mission critical equipments. Product rating range is from 10kVA - 800kVA that can fullfill different industrial segments, heavy-duty, heavy reliability.
GENERAL FEATURES
True Galvanic isolation
Microprocessor DSP design
Multi-CPU design and software/hardware cooperate control Make the system extremely high reliable
Plug & Play modular
Protection against detaching and floating of the neutral
Protection from user error Advanced circuitry prohibits damage to the system
Intelligent charger with temperature compensation
Intelligent, safe battery test circuitry Test
Cold start function
Multiple output sockets
Hot swappable battery function
RS232 communication port
Tel/modem internet surge suppression
Mini- remote control panel (option)
31
iDL Series
True Galvanic isolation
An isolation transformer is placed at the output. This can solve the problem of poor input grounding, can allow a different ground between input and output, can avoid the annoying problem of ground leakage current, and can be tied to any potential provided on site. The AC output is isolated under every mode of operation.
Additionally, the user gets the bonus of attenuation of common mode noise from the output isolation transformer.
High frequency design
The inverter uses high frequency, high efficiency IGBT,
PWM methodology to convert the DC power to AC power. Therefore, the number of components is fewer, reliability is improved, and the size and weight of UPS is reduced, performance is improved, and acoustic noise is minimized.
Cold start function
The UPS can be started without an AC source, that is, can be started with battery power only. This is possible because current limit circuitry is added, preventing the problem of large inrush current blowing the battery fuse and damaging the DC capacitors when batteries are connected to an empty DC bus (before the DC bus is energized).
Plug & Play Modular design
The power circuit is separated into several modules plugged into slots in the UPS, which are easy to pull out, permitting quick maintenance and easier trouble shooting.
Multi-CPU design
Several CPUs are employed in the control circuit, and critical functions are designed with parallel redundancy to improve reliability. Therefore, in case of one CPU failure, the other CPUs keep the UPS operational, and the output AC is not affected.
Intelligent battery test
The batteries are tested after every boost (initiated by battery discharge or by the monthly boost charge cycle).
This is done without interrupting the operation of the rectifier, preventing the risk of output AC failure in case of a bad battery. The user is informed of the battery condition, so that action can be taken before the full capacity of the batteries is needed.
Intelligent charger
The UPS will automatically recharge (boost charge) the batteries every time the batteries are depleted to a voltage level equal to 2V/Cell. Thus, the batteries can be restored to full capacity as soon as possible, and made ready for the next back-up requirement. In order to keep the batteries in the best condition, the UPS will boost charge the batteries for several hours (selectable) automatically every month. To avoid over charging the batteries, boost charge will stop when the ambient temperature is over 35 o
C (95 o
F).
Protection against misuse
The UPS is designed with breaker on/off sensor, power supply sensor, etc. Therefore, any operational mistake made by the user causes no harm to the UPS.
Variety of accessory (options)
With built-in intelligent communication interface as well as output ports of RS-232, RS-485, and dry contacts, there are several options are hence available such as remote control panel, 3 phases software for PC monitoring, auto dialing module, battery monitoring module, 3 phases SNMP card, and emergent power off (EPO) switch. Please refer to the chapter 7 of options for details.
www.fsp-ps.de
iDL Series
TECHNICAL SPECIFICATIONS
MODEL
INVERTER
DC Input Range
Wave Form
Output Voltage
Output Power Factor
Voltage Regulation 100% Unbalance Load
Frequency Lock Range
Output Frequency (Free Running)
Phase Shift Under 100% Unbalance Load
Thd (Linear Load)
<110%
Overload
110 – 124%
125 – 149%
>= 150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Frequency Range
Efficiency
Transfer
Time
- Mains -> Inverter
- Inverter -> Mains
Overload
150%
300%
Isolation With Output
OVERALL CHARACTERISTICS
Overall Efficiency
OPERATING ENVIRONMENT
- Temperature
- Humidity
- Altitude
PHYSICAL
Dimension, D X W X H (mm)
Maximum Heat Dissipation(Kw)
Weight(Kg) (No Battery)
STANDARDS
Safety
PROTECTIONS
- Short Circuit
- Lightning
- Emc Filter
- Galvanic Isolation
INDICATIONS & ALARMS
- Led,Lcd,Buzzer
Dry Contact
Battery Start
10
92%
90%
0.65
300
Product specifications are subject to change without further notice
20 30 40 50
92%
285 – 420VDC
Sinusoid
380 / 400 / 415 VAC 3 Phase 4 Wire (Special spec can be customized)
0.8
± 1 %
45 – 55 Hz / 55 – 65 Hz
50 / 60 Hz ± 0.1 Hz
120 % + / - 0.5°
< 3 %
Continuous
15 min
5 min
30 sec
93% 93.5% 93.5%
90%
173 – 277 VAC (Line To Neutral)
45 – 55 Hz / 55 – 65 Hz
99.5%
0 ms
0 ms
30 sec
1 sec
YES
91% 91.5%
0 – 40°C ( 32 – 104°F )
0% - 90% ( Non–condensing )
<1500m Above Sea Level
92%
1.3
400
1.9
470
800 x 550 x 1600
2.6
520
- EN50091-1,-2 & FCC CLASS A
Rectifier, Reserve, Bypass Nfb
Mov
Input & Output
Between Input & Output
Yes
Yes
Yes
3
560
60
94%
92%
3.5
630
32 www.fsp-ps.de
33
iDL Series
TECHNICAL SPECIFICATIONS
MODEL
RECTIFIER
Input Voltage
Input Range
Input Frequency
Input Power Factor
Power Walk In
Efficiency
Voltage Regulation
Ripple Voltage
BATTERY
Battery Type
No. Of Cells
Voltage Range
Battery Low Voltage
Battery Low Stop Voltage
Boost Charge
Float Charge
INVERTER
Dc Input Range
Wave Form
Output Voltage
Output Power Factor
80
Voltage Regulation 100% Unbalance Load
Frequency Lock Range
Output Frequency (Free Running)
Phase Shift Under 100% Unbalance Load
Thd (Linear Load)
Overload
<110%
110 – 124%
125 – 149%
>= 150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Frequency Range
Efficiency
Transfer
Time
Overload
- Mains -> Inverter
- Inverter -> Mains
150%
300%
Isolation With Output
OVERALL CHARACTERISTICS
Overall Efficiency
Temperature
Operating
Environment
Humidity
Altitude
PHYSICAL
Dimension, D X W X H (mm)
Maximum Heat Dissipation(Kw)
Weight(Kg) (No Battery)
STANDARDS
Safety
PROTECTIONS
- Short Circuit
- Lightning
- Emc Filter
- Galvanic Isolation
94.5%
94.5%
4.6
950
Product specifications are subject to change without further notice
100 120 160 200 240
380 / 400 / 415VAC 3 Phase 4 Wire (Special spec can be customized)
± 20%
50 / 60 Hz ± 7%
0.8
0% - 100% : 20 sec
99%
1%
0.5%
SEAL LEAD ACID / NiCd
174 / 271
295 – 410VDC / 285-415VDC
320VDC / 305VDC
295VDC / 285VDC
402VDC / 415VDC
390VDC / 410VDC
285 – 420VDC
Sinusoid
380 / 400 / 415 VAC 3 Phase 4 Wire (Special spec can be customized)
0.8
+ / - 1 %
45 – 55 Hz / 55 – 65 Hz
50 / 60 Hz + / - 0.1 Hz
120 % + / - 0.5
°
< 3 %
CONTINUOUS
15 min
5 min
30 sec
94.5% 95% 95% 95%
94.5%
5.4
1250
173 – 277 VAC (LINE TO NEUTRAL)
45 – 55 Hz / 55 – 65 Hz
99.5%
0 ms
0 ms
30 sec
1 sec
YES
95%
0 - 40
℃
( 32 - 104
℉
)
95%
0% - 90% ( Non–condensing )
<1500 m above sea level
6.5
1400
800 x 1100 x 1600
8.7
1600
- EN50091-1,-2 & FCC CLASS A
Rectifier, Reserve, Bypass Nfb
Mov
Input & Output
Between Input & Output
94%
11.5
2500
95%
94%
800 x 2240 x 1600
13
2700 www.fsp-ps.de
iDL Series
TECHNICAL SPECIFICATIONS
MODEL
RECTIFIER
Input Voltage
Input Range
Input Frequency
Input Power Factor
Power Walk In
Efficiency
Voltage Regulation
Ripple Voltage
BATTERY
Battery Type
No. Of Cells
Voltage Range
Battery Low Voltage
Battery Low Stop Voltage
Boost Charge
Float Charge
INVERTER
Dc Input Range
Wave Form
Output Voltage
Output Power Factor
320
Voltage Regulation 100% Unbalance Load
Frequency Lock Range
Output Frequency (Free Running)
Phase Shift Under 100% Unbalance Load
Thd (Linear Load)
Overload
<110%
110 – 124%
125 – 149%
>= 150%
Efficiency (100% Load)
STATIC SWITCH
Voltage Range
Frequency Range
Efficiency
Transfer
Time
Overload
- Mains -> Inverter
- Inverter -> Mains
150%
300%
Isolation With Output
OVERALL CHARACTERISTICS
Overall Efficiency
Temperature
Operating
Environment
Humidity
Altitude
PHYSICAL
Dimension, D X W X H (mm)
Weight(Kg) (No Battery)
STANDARDS
Safety
PROTECTIONS
- Short Circuit
- Lightning
- Emc Filter
- Galvanic Isolation
95%
92%
800 x 2240 x 1600
3000
Product specifications are subject to change without further notice
400 500 600 700
95%
93%
380 / 400 / 415VAC 3 Phase 4 Wire
± 20%
50 / 60 Hz ± 7%
0.8
15% - 100% : 15 sec
99%
1%
0.5%
Seal Lead Acid / Nicd
174 / 271
295 – 410VDC / 285-415VDC
320VDC / 305VDC
295VDC / 285VDC
402VDC / 415VDC
390VDC / 410VDC
285 – 420VDC
Sinusoid
380 / 400 / 415 VAC 3 Phase 4 Wire
0.8
+ / - 1 %
45 – 55 Hz / 55 – 65 Hz
50 / 60 Hz + / - 0.1 Hz
120 % + / - 0.5
°
< 5 %
Continuous
15 min
5 min
30 sec
95% 95%
173 – 277 VAC (Line To Neutral)
45 – 55 Hz / 55 – 65 Hz
99.5%
0 ms
0 ms
30 sec
1 sec
YES
93%
0 - 40
℃
( 32 - 104
℉
)
93%
0% - 90% ( Non–condensing )
<1500 m above sea level
95%
93%
1000 x 2220 x 1900
3600
1000 x 3340 x 1900
4500 6000
1000 x 4460 x 1900
7200
- EN50091-1,-2 & FCC CLASS A
Rectifier, Reserve, Bypass Nfb
Mov
Input & Output
Between Input & Output
800
95%
93%
7500
34 www.fsp-ps.de
35
FSP SOLAR POWERMANAGER
OFF-GRID SERIES
Remote
Control Panel
Power Solution for Unstable or without Utility Grid
1kVA-5kVA
FSP Solar PowerManager Off-Gird
An ideal Off-Grid inverter for households, FSP Solar
PowerManager Off-Grid with specific AC and high efficiency MPPT Solar charger built-in, Dual charging sources (utility+solar) up to 140A current satisfying battery charging under different weather conditions and ensuring your power continuously.
Wide input range from 90-280Vac will overcome most of grid power instabilities.
Design as true sine wave off-grid inverter with 1kVA to
5kVA rating, 4/5kVA parallel function up to 30kVA
(single phase) suitable for different applications and supporting 3-Phase power system in anymode. FSP
Solar PowerManager Off-Grid with smart user-friendly control panel is an adjustable power source for optimal settings according to end users needs. The unit also offers USB Port for PC monitoring purpose.
As non-household application, FSP Solar PowerManager
Off-Grid is able to provide power e.g. for a water pump.
GENERAL FEATURES
High frequency pure sine wave
Wide AC input range 90-280 Vac
Solar and AC Dual charger built in
Charging Ability up to 140A (AC+Solar)
Built-in dry-contact for Generator
Double surge capacity of rating
4k/5kVA parallel function support single Phase up to 30kVA
3Phase AnyMode support
Intuitive LCD Display
User friendly LCD Panel control & setting
Source Priority programmable
Remote Control Panel support
User defined Bulk/Float Charging voltage
Free monitoring software
FSP Solar PowerManager Off-Grid Series
Ideal Off-Grid inverter
Programmable Power Source Priority function.
More Flexible, More Independent for energy usage and storage.
The Principle of FSP Solar PowerManager Off-Grid
36
As Hybrid Power System As Power backup System
Solar Power Solar Power
Generator Utility
SLS Battery Home Appliance
Generator Utility
SLS Battery Home Appliance
FSP Solar PowerManager Off-Grid Smart Power Priority
Power and charging source priority of FSP Solar PowerManager Off-Grid smart design can be set up by the front LCD panel according to the power consumption environment, storing and withdrawal of energy are also user-defined.
Output source Priority is Solar->Bat->Utility
Charger source priority is Solar Power Only
Solar energy is sufficient to charge the battery and feed the loads. Once solar power is low, system will switch to battery mode automatically until the battery reaches low warning and system transfers to utility.
Power source priority succession is Solar -> Battery -> Utility
Charging source priority is only Solar power
Output source priority is Utility &
Charging source priority is solar power
Utility will feed output loads, Solar power will charge the battery until solar power ceases. Solar and battery energy will be used when utility fails.
Power source priority is Utility -> Solar & Battery
Charging source priority is Solar -> Utility www.fsp-ps.de
37
FSP Solar PowerManager Off-Grid Series
Single Phase Parallel and 3-Phase AnyMode
High expansion ability: FSP Solar PowerManager Off-Grid 4kVA and 5kVA design can be expanded to 30kVA in parallel mode, single phase, and also specifically supports 3 Phase AnyMode. The Power capacity can satisfy most of household energy demand.
Parallel 3 units in Single Phase
Up to 30kVA parallel ability: FSP Solar
PowerManager Off-Grid will achieve expansion function by parallel kits in order to get more power capacity. (The drawing presents 3 units in parallel mode, power capacity is 15kVA.)
Parallel 6 units in 3 Phase AnyMode
FSP Solar PowerManager Off-Grid supports
3 Phase AnyMode. By consulting and measurement user can define which phase needs more power support, e.g. P1 = Phase
1 is consuming most of the power in the house, system can install Max 4 PC in L1 to get 20kVA power.
Battery
Utility
Load
N
L
N
L
Phase 1=P1 P2 P3
Battery
N
Utility
Load
L3
N
L1
L2
L3
O/P Source Priority 1 2 3
Output source & Charging source priority is solar power
When Solar energy is sufficient to charge the battery and feed the loads, utility will stand by until Solar power ceases or battery voltage drops to user’s setting.
Power source priority is Solar -> Battery or Utility
Charging source priority is Solar -> Utility
Output source is Solar-Bat-Utility
Charger source priority is Solar & Utility (4/5k only)
System will adapt Solar and utility both source to charge battery at the same time. Once solar power is low, system will switch to battery mode automatically until reach low bat warning then transfer to utility.
Power source priority is Solar -> Battery -> Utility
Charge source priority is Solar & Utility
www.fsp-ps.de
FSP Solar PowerManager Off-Grid Series
TECHNICAL SPECIFICATIONS
MODEL
RATED POWER
INPUT
Voltage
Selectable Voltage Range
Frequency Range
OUTPUT
AC Voltage Regulation (Batt. Mode)
Surge Power
Efficiency (Peak)
Transfer Time
Waveform
BATTERY & AC CHARGER
Battery Voltage
Floating Charge Voltage
Overcharge Protection
SOLAR CHARGER & AC CHARGER
Maximum PV Array Power
MPPT Range @ Operating Voltage
Maximum PV Array Open Circuit Voltage
Maximum Solar Charge Current
Maximum AC Charge Current
Maximum Charge Current
Maximum Efficiency
Standby Power Consumption
PHYSICAL
Dimension, D x W x H (mm)
Net Weight (kgs)
Ingress Protection Rating
Cooling system
OPERATING ENVIRONMENT
Humidity
Operating Temperature
Storage Temperature
PM-OffGrid 1K-24 PM-OffGrid 1K-48 PM-OffGrid 2K-24 PM-OffGrid 3K-24 PM-OffGrid 3K-24
1000VA/800W 1000VA/1000W 2000VA/1600W 3000VA/2400W 3000VA/2400W
24 VDC
27 VDC
31 VDC
2000VA
90%-93%
600 W
30VDC~ 66VDC
75VDC
25A
20A
25A
6.8
48 VDC
54 VDC
62 VDC
230 VAC
170-280 VAC (For Personal Computers)
90-280 VAC (For Home Appliances)
50 Hz/60 Hz (Auto sensing)
230VAC ± 5%
4000VA
6000VA
93%
10 ms (For Personal Computers); 20 ms (For Home Appliances)
Pure sine wave
24 VDC
27 VDC
31 VDC
24 VDC
27 VDC
31 VDC
900 W 600 W 600 W
60VDC~ 88VDC
75VDC
30VDC~ 66VDC
75VDC
30VDC~ 66VDC
75VDC
18A 25A 25A
15A
18A
30A
30A
30A
30A
AC charger and solar charger can’t work at the same time
98%
2 W
100 x 272 x 355
7
IP20
AirForce cooling
7.4
48 VDC
54 VDC
62 VDC
900 W
60VDC~ 88VDC
102VDC
18A
15A
18A
5% to 95% Relative Humidity (Non-condensing)
0°C - 55°C
-15°C - 60°C
PM-OffGrid 4K
4000VA/3200W
8000VA
48 VDC
54 VDC
60 VDC
PM-OffGrid 5K
5000VA/4000W
10000VA
48 VDC
54 VDC
60 VDC
4000 W
60VDC~ 115VDC
145VDC
80A
60A
140A
4000 W
60VDC~ 115VDC
145VDC
80A
60A
120 x 295 x 468
11
MODEL
RATED POWER
INPUT
Voltage
Selectable Voltage Range
PM-OffGrid 2K-24+
2000VA/2600W
Frequency Range
OUTPUT
AC Voltage Regulation (Batt. Mode)
Surge Power
Efficiency (Peak)
Transfer Time
Waveform
BATTERY & AC CHARGER
Battery Voltage
Floating Charge Voltage
Overcharge Protection
SOLAR CHARGER & AC CHARGER
Maximum PV Array Power
MPPT Range @ Operating Voltage
Maximum PV Array Open Circuit Voltage
Maximum Solar Charge Current
Maximum Efficiency
Standby Power Consumption
24 VDC
27 VDC
31 VDC
1500 W
30VDC~ 115VDC
PHYSICAL
Dimension, D x W x H (mm)
Net Weight (kgs)
Ingress Protection Rating
Cooling system
OPERATING ENVIRONMENT
Humidity
Operating Temperature
Storage Temperature
Product specifications are subject to change without further notice
PM-OffGrid 2K-48+
2000VA/1600W
170-280 VAC (For Personal Computers)
90-280 VAC (For Home Appliances)
50 Hz/60 Hz (Auto sensing)
230VAC ± 5%
4000VA
6000VA
90%-93%
10 ms (For Personal Computers); 20 ms (For Home Appliances)
Pure sine wave
48 VDC
54 VDC
62 VDC
3000 W
60VDC~ 115VDC
230 VAC
145VDC
60A
98%
2W
140 x 295 x 479
11.5
IP20
AirForce cooling
PM-OffGrid 3K-24+
3000VA/2400W
24 VDC
27 VDC
31 VDC
1500 W
30VDC~ 115VDC
5% to 95% Relative Humidity (Non-condensing)
0°C - 55°C
-15°C - 60°C
PM-OffGrid 3K-48+
3000VA/2400W
48 VDC
54 VDC
62 VDC
3000 W
60VDC~ 115VDC
38 www.fsp-ps.de
39
FSP SOLAR POWERMANAGER
HYBRID SERIES
Smart Energy for Smart Home
FSP Solar PowerManager-Hybrid
Offers a more intelligent power solution for our customers to reduce the energy bill and make a contribution to our homeland, to our earth. Your energy can be used as efficiently, as smart as possible under current power consumption environment.
YOUR ENERGY, YOU DECIDE!
By the unique optimum technology of FSP Solar
PowerManager-Hybrid Series you can control whether or how to use your energy, to store the generated power into battery or feed into the grid. Moreover, if grid power failed, by the brilliant ability of FSP Solar
PowerManager-Hybrid Series, the load will be handled smartly by direct support from solar, by combining solar
& storage energy or withdrawing storage power only.
Multiple communication methods for different applications: FSP Solar PowerManager-Hybrid Series implements USB, RS232 ports and also fits with intelligent slot for SNMP card monitoring or Modbus Card for smart meter compensation applicable to keep your electricity meter at zero. to stay your electricity meter at zero.
3KW-10KW
GENERAL FEATURES
Just ONE integrated design of Grid-tied & Off-Grid function
Solar PowerManager-Hybrid implements AC I/P breaker and DC switch
Solar Energy Storage
Optimized Self-Consumption
Load Dual-compensated: Solar & Storage Power or Grid
& Storage Power
Power securing during Grid Failure
Back-up function
Intuitive LCD Display
SNMP, Modbus AS400 Support
Certified VDE0126 & VDE4105
5kW&10kW Model Parallel function available, up to 6PC
1
3
2
4
FSP Solar PowerManager-Hybrid Series
40
1. Solar Panel
2. FSP Solar PowerManager-Hybrid
3. SLS Battery
4. MBS:Maintenance Bypass Switch
Multi-Operation Mode
Solar Energy Multi-Use
Intelligent design adding more options to use
Solar Energy: It is not just conventional PV inverter Feed-in function, the system with sufficient solar power will not only feed in grid, but also store energy and support loads.
Self-Consumption
When Solar Energy is low e.g. at night, the FSP
Solar PowerManager will automatically withdraw the power from Energy storage
(Battery) without using power from utility; saving & reducing your energy bill.
Back-up Power when Grid Outage
FSP Solar PowerManager implements off-grid inverter function. If a utility failure or outage occurs, the system will switch to back-up mode and offer continuous power.
www.fsp-ps.de
41
FSP Solar PowerManager-Hybrid Series
Manage Your Own Power
FSP Soalr PowerManger - Hybrid is an ingenious design unit. Product achieves tri-power source, Solar, Utility, and Battery Management.
Home Appliance
Solar Power
Monitoring System
SLS Battery
Socket & Emergency Lighting
Energy Meter
FSP Solar PowerManager-Hybrid Compensation Mode:
Modbus Card for smart meter compensation applicable to keep your electricity meter at zero.
All the loads are connected with Grid FSP Solar PowerManager-Hybrid which is an auxiliary power. At daytime, Solar Power is sufficient to feed in grid and store energy at the same time.
At nighttime, FSP Solar PowerManager-Hybrid will withdraw the power constantly from the battery providing energy to your home appliances in order to decrease your energy bill.
If a utility outage occurs, FSP Solar PowerManager-Hybrid will generate the back-up power for emergency demand, e.g. lighting which is connected to the unit.
www.fsp-ps.de
FSP Solar PowerManager-Hybrid Series
TECHNICAL SPECIFICATIONS
MODEL
PHASE
MAXIMUM PV INPUT POWER
RATED OUTPUT POWER
MAXIMUM CHARGING POWER
GRID-TIE OPERATION
PV INPUT
Nominal DC Voltage / Maximum DC Voltage
Start-up Voltage / Initial Feeding Voltage
MPP Voltage Range
Number of MPP Trackers / Maximum Input Current
GRID OUTPUT
Nominal Output Voltage
Output Voltage Range
Nominal Output Current
Power Factor
EFFICIENCY
Maximum Conversion Efficiency (DC/AC)
European Effi[email protected] Vnominal
HYBRID / OFF-GRID OPERATION
PV INPUT
Nominal DC Voltage /Maximum DC Voltage
Start-up Voltage / Initial Feeding Voltage
MPP Voltage Range
Number of MPP Trackers / Maximum Input Current
GRID OUTPUT
Nominal Output Voltage
Output Voltage Range
Nominal Output Current
AC IUTPUT
PowerManager-Hybrid 3kW PowerManager-Hybrid 5kW
Single phase
4500 W
3000 W
1200 W
10000 W
5000 W
4800 W
360VDC / 500VDC
116VDC / 150VDC
250VDC / 450VDC
1/1 x 18A
13 A
360VDC / 500VDC
116VDC / 150VDC
250VDC / 450VDC
1/1 x 18A
13 A
720VDC / 900VDC
225VDC / 250VDC
250VDC / 850VDC
2/2 x 10A
208/220/230/240VAC
184 - 265 VAC*
720VDC / 900VDC
225VDC / 250VDC
250VDC / 850VDC
2/2 x 10A
202/208/220/230/240VAC
184 - 264.5 VAC*
21 A
> 0.99
96 %
95 %
21 A
120 - 140 VAC / 180 VAC
170 - 280 VAC
AC Start-up Voltage/Auto Restart Voltage
Acceptable Input Voltage Range
Maximum AC Input Current
BATTERY MODE OUTPUT
Nominal Output Voltage
Efficiency (DC to AC)
BATTERY & CHARGER
Nominal DC Voltage
Maximum Charging Current
30 A
30 A
202/208/220/230/240VAC
93%
40 A
48 VDC
Default 60A, 5A-100A
(Adjustable)
GENERAL
PHYSICAL
Dimension, D x W x H (mm)
Net Weight (kgs)
INTERFACE
Communication Port
Intelligent Slot
ENVIRONMENT
Humidity
Ingress Protection Rating
Cooling system
Operating Temperature
Altitude
*These figures may vary depending on different AC voltage and country requirements.
* * Power derating 1% every 100 m when altitude is over 1000m.
* Product specifications are subject to change without further notice
107 x 438 x 480
15.5
RS-232 / USB
0 to 40°C
204.2 x 460 x 600
29
0 ~ 90% RH (No condensing)
IP20
AirForce cooling
-10 to 55°C
0 ~ 1000 m** Max2000m
PowerManager-Hybrid 10kW
3-phase in / 3-phase out
14850 W
10000 W
9600 W
720VDC / 900VDC
320VDC / 350VDC
400VDC / 800VDC
2/2 x 18.6A
230VAC(P-N) /400VAC(P-P)
184-265 VAC* per phase
14.5A per phase
720VDC / 900VDC
320VDC / 350VDC
400VDC / 800VDC
2/2 x 18.6A
230VAC(P-N) /400VAC(P-P)
184-264.5 VAC* per phase
14.5A per phase
120-140VAC per phase /
180VAC per phase
170-280 VAC per phase
40 A
230VAC(P-N) /400VAC(P-P)
91%
Default 60A, 10A-200A
(Adjustable)
167.5 x 500 x 622
45
RS-232/USB and CAN Interface
Optional SNMP, Modbus, and AS-400 cards available
42 www.fsp-ps.de
43
SCC-MPPT
Applications:
ECO
Solar Input CO
2
Free
98% Efficiency Solar Charger
SCC-MPPT Solar Charge Controller With advanced maximum-power-tracking technology, SCC-MPPT series ensures maximum performance from your
solar array at all times and in all weather conditions.
Solar Charger Controller
3KW
GENERAL FEATURES
Intelligent Maximum Power Point Tracking technology
Built-in DSP controller with high performance
1 2/24/48V Automatic battery voltage detection when initial
Battery temperature compensation support
Three-stage charging optimizes battery performance
Multifunction LCD displays detailed information
Reverse polarity protection for solar panel and battery
Overcharge protection
Suitable for battery types of sealed lead acid, vented
Gel, and NiCd
SCC-MPPT
TECHNICAL SPECIFICATIONS
MODEL
INPUT
MPPT Range @ Operating Voltage
Maximum PV Array Open Circuit Voltage
Maximum PV Array Power
Maximum Current
OUTPUT
Nominal Battery Voltage
Connected Battery Type
800W
SCC-MPPT 3KW
60 VDC ~ 115 VDC
145VDC
1600W
50 A
3200W
12 VDC 24 VDC
Sealed lead acid, AGM or Gel
48 VDC
Maximum Charging Current
Maximum Efficiency
60 A
98%
Charging Method
PROTECTION
Overload Protection
Overcharge Protection
Net Weight (Kgs)
Three stages: bulk, absorption, and floating
> 110% : audible alarm
Polarity Reversal [email protected] Cell & Battery
INDICATORS
LCD Panel
Yes
LCD panel indicating solar power, load level, battery voltage/capacity, charging current, and fault conditions
LED Display
PHYSICAL
Dimension, D x W x H (mm)
Yes
Three indicators for solar, charging, and load status
315 x 165 x 128
4.5
IP 31
Type of Mechanical Protection
ENVIRONMENT
Humidity
Operating Temperature
Storage Temperature
Altitude
Product specifications are subject to change without further notice
5 ~ 95% RH (Non-condensing)
0°C to 55°C
-15°C to 60°C
0 ~ 3000 m
44
Standalone Solar Power System:
Combined MPPT technology and DSP controller,
FSP Solar charger controller will convert best voltage and power to charge battery based on varied temperature.
Compared to traditional solar charge controllers, it allows your solar panels to operate at their optimum power output voltage, providing higher efficiency up to 98% with lower power loss.
Integrated FSP Solar charger controller with inverter, solar panel, and external battery packs, it can become a standalone solar power system to generate green power for your home appliances.
External battery packs
SCC-MPPT
Inverter
Solar panel
Home appliances www.fsp-ps.de
45
Accessory
Synergy Super Charger
• Isolation design for 24/36/48/72/240VDC System
• Input power factor correction
• Microprocessor guarantee smart & stable three-stage charging
• User-adjustable charging current based on applications
• Output short circuit protection
• Maximum current restriction
• Over-voltage protection
• Thermal control protection and reversal polarity protection
• Parallel operation
PDU & Maintenance Bypass Switch
• 1-3 kVA Tower/Rack PDU & MBS
• 16A for 208/220/230/240 VAC
• Provides continuous power to connected equipment during UPS maintenance
• Easy operation with simple rotary switch and indicators
• Simple installation with plug-and-play socket type
AC input 1x IEC C20 (16A) connector
UPS I/P 1x IEC C19 (16A) connector
UPS O/P 1x IEC C20 (16A) connector
O/P Socket 5 x IEC C13 + 1x IEC C19, 2 breakers
External Maintenance Bypass Switch
• 6-10kVA Rack MBS
• 63A. max input current
• 100% make before break to provide continuous power to connected equipment
during UPS maintenance
• Automatic UPS-protection design
• Easy operation with simple rotary switch
• Terminal block type
30kVA Wall-Mounted External Maintenance Bypass
• 3-Phase design
• Nominal current 63A
• Isolation Voltage 660VAC
• EN90647-3:2009+A1 TUV certificated
IEC Cable 16A C19/C20 (180cm) IEC Cable 16A C20/C13 (180cm) IEC Cable 16A C14/C19 (150cm)
Rackmount Slider
Simple installation for mounting Rack in your server rack enclosure.
RMS-001 for 1-3kVA Rack UPS
RMS-002 for 6-10kVA Rack UPS
Software
ViewPower - UPS Management Software
ViewPower Pro is UPS management software which is perfect for home users and enterprises. It can monitor and manage from one to multiple UPSs in a networked environment including LAN, INTERNET and Modbus networks. Integrated with
Shutdown Wizard, it can not only prevent data loss from power outage and safely shutdown systems, but also store programming data and scheduled shut down UPSs.
All UPS working data and event records can be kept in local database system.
www.fsp-ps.de
Accessory
UPS Remote Monitoring and Connectivity
FSP provides complete connectivity solutions with comprehensive products and software package. These connectivity products ensure communication compatibility with a variety external devices through relay, SNMP and Modbus.
Connects to
Environmental
Monitoring Device
LAN
Router
SNMP
Router
LAN
WAN
5Vdc DC input
WWW
WAN
WWW
Connectivity Product
SNMP Card
SNMP Web Card
(DP801B)
Modbus Card
SNMP Web Card
SNMP Web Box
Modbus Web Card
SNMP Web Card/Box
• Allows control and monitoring of multiple inverters through RJ-45 network
connection
• Real-time dynamic graphs of UPS / PowerManager data
• Warning notifications via audible alarm, broadcast, mobile messenger, e-mail and
SNMP traps
• Historic data log stored in centralized PC database
• Simple firmware upgrade with one click
• Password security protection and remote access management
• Supports optional environmental monitoring detector for temperature, humidity
and smoke
Modbus Card
• Real-time control and monitoring of multiple inverters via RS-485 communication port
• Supports Modbus RTU protocol
• Provides MODBUS functions including read Holding Registers and write Registers
• Provides surge protection
Modbus Web Box
• Supports to monitor off-grid inverter through modbus interface
• Implements MODBUS RTU protocol
• Integrated with WatchPower software
• Supports PowerManager Hybrid series
Relay Card
The AS400 communication card provides contact closures for remote monitoring UPS.
To meet different application requirement, the AS400 card is capable of selection the status of the dry-contact signal (active close or active open) by setting jumper.
DB9 Port
EMD
9-pin Port
Energy meter
Environmental Monitoring Device (EMD)
• Plug & use for simple installation with SNMP manager
• Monitor temperature and humidity to protect your precious equipment
• Allow 4 contact closure signals for user-defined usage
• Management software to remote monitor temperature and humidity status via web browser
• Measure temperatures between 0 to 100°C with an accuracy of ±1.5°C
• Measure relative humidity between 10 to 90% RH with an accuracy of ±3%
• Optional smoke alarm available
Touch screen 3-phase multi-function meter
Measures and displays the parameter of voltage,frequency,current, active and reactive energy,imported or exported. Max Demand,THD of voltage and current can be meaured over present periods of up to 60 minute. Built-in interfaces provide pulse and
RS485 Modbus RTU output
46
Software
Solarower -Solar inverter Management Software
SolarPower is a solar inverter monitoring software. It can monitor multiple devices via
USB and Serial port at the same time. The major functions of SolarPower monitoring software include data log for devices, power generation statistics, alarm messages, fault messages and parameter setting for devices.
www.fsp-ps.de
Jakobshöhe 16 | 41066 Mönchengladbach | Germany
Tel: +49-2161-4952490 | Fax: +49-2161-495249-21 [email protected] | www.fsp-ps.de
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project