Acumentrics Rugged-UPS ACG1250U-52B Uninterruptible Power Supply User Manual

Add to My manuals
21 Pages

advertisement

Acumentrics Rugged-UPS ACG1250U-52B User Manual | Manualzz

ACUMENTRICS CORPORATION

1000 Watt Rugged-UPS

TM

with optional 24 VDC 250 Watt Output

97-0057 Rev I

ACG1250U-52B

1. INTRODUCTION

Welcome

Thank you for purchasing this Rugged-UPS

TM

uninterruptible power supply. This UPS was designed for world wide deployment in harsh and rugged environments.

Please save packing materials

.

The UPS’s shipping materials are designed to provide the necessary protection during shipping.

These materials must be used if you ever have to return the UPS for service. Damage sustained during transit is not covered under warranty.

Operation Topology

AC Input

Input EMI

Filter

Universal

Power Factor

Corrected Boost

Converter

DC/AC

Inverter

Isolation

Transformer

Output EMI

Filter

115 VAC, 60 Hz* 1250VA

*230, 50HZ for international model

DC Input

Input EMI

Filter

DC/DC Boost

Converter

With Galvanic

Isolation

400

VDC

BUS

DC/DC

Converter

24 VDC, 250 W*

*for “-24” models only

Removable

Battery Pack

DC/DC Boost

Converter

With Galvanic

Isolation

Constant Current & Constant Voltage

Battery Charger with Galvanic Isolation

This unit is an ON-LINE Power Factor Corrected (PFC), Uninterruptible Power Supply (UPS).

This UPS accepts wide range voltage and frequency inputs to allow it to provide clean, reliable AC power to the computer equipment connected to it.

The UPS is continually creating the AC output from a high voltage DC bus, thus protecting your equipment from surges, spikes, brownouts, blackouts and noise.

Charge Battery

The UPS charges its battery when connected to utility power. For best results, charge the battery 4 hours before use. It is acceptable to use the UPS without first charging the battery, but on battery run time maybe shorter until the battery fully charges.

Contents are copyrighted

©

by Acumentrics Corporation. All rights reserved; reproduction in whole or in part with out permission is prohibited. Rugged-UPS is a registered trademark of Acumentrics Corporation. All other trademarks are the property of their respective owners.

2 Acumentrics Corporation

2. SAFETY

UPS SAFETY GUIDELINES

To reduce the risk of electric shock, disconnect the Uninterruptible Power Source from the mains before installing a computer interface signal cable (when used). Reconnect the power cord only after all signaling interconnections have been made.

Connect the Uninterruptible Power Source to a two-pole, three-wire grounding mains receptacle. The receptacle must be connected to appropriate branch protection (fuse or circuit breaker). Connection to any other type of receptacle may result in a shock hazard and may violate local electrical codes.

This Uninterruptible Power Source has an internal energy source (the battery) that cannot be de-energized by the user. The output may be energized when the unit is not

connected to a mains supply.

To properly de-energize the Uninterruptible Power Source in an emergency, move the I/O switch to the O (off) position and disconnect the power cord from the mains.

Avoid installing the Uninterruptible Power Source in locations where there is water or excessive humidity.

Do not allow water or any foreign object to get inside the Uninterruptible Power Source.

Do not put objects containing liquid on or near the unit.

To reduce the risk of overheating the Uninterruptible Power Source, avoid exposing the unit to the direct rays of the sun. Avoid installing the unit near heat emitting appliances such as a room heater or stove.

Warnings

This Uninterruptible Power Source contains potentially hazardous voltages. Do not attempt to disassemble the unit. The unit contains no user serviceable parts. Repairs are performed only by factory trained service personnel.

The Uninterruptible Power Source uses batteries. The batteries will eventually become too weak to provide rated autonomous operation. To obtain battery replacement or repair service, please call the Customer Service telephone number written on the front or back cover of this manual for information on the Service Center nearest you.

3 Acumentrics Corporation

3. Package Purchase Options

Domestic Model Options (120VAC/60Hz Output)

Model Ships with

ACG26BP

Ships with

ACG52BP

24 Volt DC

Output 250

Watts

ACG1250U

ACG1250U-24 X

ACG1250U-SH

ACG1250U-24-SH

ACG1250U-26B

ACG1250U-52B

ACG1250U-24-26B

ACG1250U-24-52B

ACG1250-24-26SH

ACG1250-24-52SH

ACG1250U-26B-SH

ACG1250U-52B-SH

X

X

X

X

X

X

X

X

X

X

X

X

X

U.S. Navy

Shipboard

Approved

X

X

X

X

X

X

4 Acumentrics Corporation

4. DISPLAYS AND FUNCTIONS

Front Display ACG1250U, ACG1250U-SH

AC Circuit

Breaker

LED Display

Panel

ON/OFF

DC Input

AC Input

AC Output

TVSS

Fan Filter Communications

Interface

Hot Swappable , User

Replaceable Battery Pack

Front Display ACG1250U-24, ACG1250-24-SH

AC Circuit

Breaker

LED Display

Panel

ON/OFF

DC Input

AC Input

AC Output

TVSS

Fan Filter 24 Volt DC

Output

Communications

Interface

5

Hot Swappable , User

Replaceable Battery Pack

Acumentrics Corporation

NOTE: ALL POWER CONNECTIONS USE MILITARY STYLE TWIST LOCK

CONNECTORS

CONNECTIONS

Input/Output

AC Input

AC Output

DC Input

DC Output

AC Output IEC

Communications Port

Cable Type

Accepts an ACG9200 cable

Accepts an ACG9201 cable

Accepts an ACG9202 cable

Accepts an ACG9203 cable

Accepts an ACG9207 cable

Used for UPS monitoring

Connector Type

MS3470L14-4P

MS3470L14-4S

MS27472T16F6P

MS3470L14-4S

MS3470L14-4S

DB9

SWITCHES/ BREAKERS

ON/OFF -

AC Input Breaker -

Powers the unit as well as turns on\off audible alarm.

Trips when the loads exceed the UPS’s capacity.

LED DISPLAY PANEL

Battery Status Meter - Displays the present battery charge in volts DC (Range 20 -28 VAC).

Load Meter - Displays the power being drawn by the load (Range 0 - 1000 watts).

Overload - This LED lights when the loads connected to the UPS exceed the UPS’s capacity.

On Internal DC - The unit is supplying power to the loads for the internal batteries.

Over Temperature - This LED lights when the UPS internal operating temperature has exceeded specifications.

On AC - The unit is supplying power to the loads for the AC connection source.

ON External DC - The unit is supplying power to the loads from the external DC connection source.

Replace Battery - This LED lights when the battery has reached the end of its usable life.

6 Acumentrics Corporation

MIL-STD-810E Specifications

Environmental

Temperature:

Operating: 0 o

F to 120 o

F (-18 o

C to 49 o

C)

Storage: -25 o

F to 150 o

F (-32

Shock: 0 o

F to 70 o

F (-18 o o

C to 66

C to 21 o

C) o

C) and 120 o

F to 70 o

F (49 o

C to 21 o

C) in 10 minutes

Turn-on: From 0 o

F to 40 o

F (-18

(4 o

C) instantaneous o

C to 4 o

C) in 10 minutes; above 40 o

F

Humidity: 10 to 95% (non-condensing)

Altitude: 0 to 15,000 ft. (operating)

0 to 40,000 ft. (non-operating)

Vibration:

Shock/Drop:

Rain:

Sand and Dust:

Operation and transport in HHMMWV and tracked vehicles

30 o

rotational (without transit cases). 3 drops form 3 ft. (in transit case)

Operation in conditions of blown precipitation and spillage

3.5 mph, 20 minutes

Tilt:

Fungus:

EMI:

HAEMP:

Operations stationary, 30 o

incline on any axis

No nutrients/contaminants

MIL-STD-461C, Notice 2, CE03, CS02, CS06, RE02, and RS03

Quadripartite Standardization Agreement-244 (Classified)

This unit complies with FCC A testing

7 Acumentrics Corporation

5. SPECIFICATIONS

Input Specifications

Input AC Voltage

Frequency

Input Power Factor

Input Circuit Breaker Rating

Input DC Voltage

Maximum DC Current

Simultaneous AC and DC inputs

DC input Connector

AC input Connector

Output Specifications

Continuous Output Power

Values

80-280 VAC

47-63Hz

0.8 Minimum

20 A

22 to 31 VDC

70 A

AC takes precedence over DC which takes precedence over battery

Matrix Series MS27472T16F6P

Connector

Matrix Series MS3470L14-4P Connector

Values

1000 W or 1250 VA (includes both AC and DC)

Load Crest Factor

AC Output Voltage (ACG1250U/U-24/-SH)

DC Output

AC Output Connector

2.5 Continuous

115 VAC +/- 5%

AC Output Frequency (ACG1250U/U-24/-SH) 60 Hz. +/- 5%

AC Output Waveform Sinusoidal

250 Watt/24 VDC +/- 5%

Matrix Series MS3470L14-4S Connector

Matrix Series MS3470L14-4S Connector DC Output Connector

Mechanical

Size

Values

Chassis: 16"wide x 16" deep x 6"tall

Weight

Shipping Size

Shipping Weight

Envelope: 17"wide x 17"deep x 6.25" tall

36 lbs. (no batteries); 84 lbs. (max. battery pack)

21"wide x 21"deep x 12"tall

45 lbs. (no batteries); 95lbs. (max. battery pack)

Finish Lusterless Light Gray (36492)

8 Acumentrics Corporation

Pin Out Specifications:

Note: Acumentrics does not warranty the ACG1250U, ACG1250U-SH, ACG1250U-24, and the

ACG1250U-24-SH against damages caused by cables manufactured by any parties other than the

Acumentrics Corporation.

Legend: Signifies Pin

Signifies Pin Receptacle

AC Input Pin Out Functionality:

(ACG1250U, ACG1250U-SH, ACG1250U-24, and ACG1250U-24-SH)

Plug Part Number MS3476W14-4S

B

A

D

To line

To Neutral To Ground

Not Used

C

9 Acumentrics Corporation

AC Output Pin Out Functionality:

(ACG1250U, ACG1250U-SH, ACG1250U-24 and ACG1250U-24-SH only)

Warning DO NOT USE THIS CABLE IN A 230VAC APPLICATION

Plug Part Number MS3476W14-4P

To Ground

Not Used

D

A

C

B

To line

To Neutral

10 Acumentrics Corporation

DC Input Pin Out Functionality:

(ACG1250U, ACG1250U-SH, ACG1250U-24, and ACG1250U-24-SH)

Plug Part Number MS27473T16B6S

+28VDC Return

B

A

F

C

E

D

+28 VDC Input

DC Output Pin Out Functionality:

(ACG1250U-24, and ACG1250U-24-SH only)

Plug Part Number MS3476L14-04P

A

D

Black-Negative

White-Positive

C

B

Not Used

Not Used

11 Acumentrics Corporation

Communications Interface Pin Out Functionality (DB9):

The DB9 connector is a 9 pin D type female with the following RS232 level:

TRUE = SPACE = +7.5V or greater

FALSE = MARK = -7.5V or less

5

9

4

8

3

7

2

6

1

Pin 1- Low battery warning. Goes TRUE if the battery voltage indicates less than 10% hold up time.

Pin 2- Not utilized

Pin 3- AC power good. TRUE if AC input is viable.

Pin 4- External shutdown input. When TRUE shuts down inverter.

Pin 5- Signal ground common.

Pin 6- Not utilized

Pin 7- Not utilized

Pin 8- Source fail. Goes TRUE if input power (AC or DC) fails or exceeds acceptable limits and UPS is

operating on internal DC (battery backup).

Pin 9- Over temperature warning. Goes TRUE if internal temperature of UPS exceeds safe

upper limit.

Rugged-UPS DB9 Interface Description

Comm Port

Comm Port

(Front View of the ACG1250U) (Front View of the ACG1250U-24)

12 Acumentrics Corporation

Interface for the ACG1250U, ACG1250U-SH, ACG1250U-24, and ACG1250U-24-SH:

The Comm Port is an RS232 compatible interface through a nine pin D type connector. This port provides UPS and input power status information to the operator. UPS shutdown capability is provided as well.

Mechanical

Size:

Weight:

Finish: chassis: 16” wide x 16” deep x 6” tall envelope: 17” wide x 17” deep x 6.25” tall

35 pounds (no batteries); 85 pounds with maximum battery pack

Lusterless Light Gray (36492)

16”

6”

16”

16”

Removable battery pack

8.25”

5.5”

13 Acumentrics Corporation

6. ACCESSORIES

Batteries:

The ACG1250U, ACG1250U-24, ACG1250U-SH and ACG1250U-24-SH do not ship with batteries.

There are two optional battery packs that can be used with these units, the ACG26BP and the ACG52BP.

Not all installations will require internal batteries if you have the capability to utilize the external DC connections to the unit or if you plan to use the unit as an inverter.

Load (watts)

100

200

300

400

500

600

700

800

900

1000

Typical Minutes of Runtime

ACG26BP

106

65

36

22

16

13

11

9

8

7

ACG52BP

212

131

72

44

33

28

23

19

16

14

The ACG26BP has a recharge time of 2 hours to 90% capacity from full discharge. The ACG52BP has a

4 hour recharge time to 90% capacity from full discharge.

14 Acumentrics Corporation

Cables:

ACG9200 AC input cable

ACG9201 AC output cable

ACG9202 DC input cable

ACG9203 DC output cable

ACG9207 AC output cable for IEC style connectors (230VAC output)

*Cable set combinations are available – call or email for model numbers

*Note: warranty is void if damage is caused by third party cables are used

Front Fan Filter Cover

*See Appendix A for servicing instructions

Rack mount Kits

15

Front fan sand and dust filter

Acumentrics Corporation

ACG9011 Rack mount kit for standard 19” cabinets with depths from 22” - 34”

ACG9012 Slide rail rack mount kit for standard 19” cabinets with depths from 20”-26”

ACG9013 Slide rail rack mount kit for standard 19” cabinets with depths from 26”-32”

16 Acumentrics Corporation

7. BATTERY STORAGE AND MAINTENANCE

The proper storage of batteries can not be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. This is called self-discharge. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. The rate of reaction, and therefore self-discharge, increases as a function of temperature. If the batteries are stored long enough without a periodic replenishment of charge, an irreversible loss of battery capacity can occur, causing premature battery failure.

All Acumentrics battery packs are shipped fully charged. They should be stored separately from the

UPS and used on a FIFO (First In, First Out) basis. All battery packs should be recharged before use if 100% capacity is required. The stored battery packs should be kept on a maintenance program and should be recharged periodically according to the recommendations shown in table 1.

Battery packs can be recharged using the UPS.

Table 1 Storage temperature and Supplementary Recharge Intervals

Storage Temperature

Below 20°C (68°F)

Recharge Interval

Every six months

Between 20°C and 30°C (68°F and 86°F)

Over 30°C (86°F)

Every three months

Storage to be avoided

The battery OCV (Open Circuit Voltage) can be used as an indicator of battery pack residual capacity. When measuring the OCV, the battery pack should not have been charged or discharged within the past 24 hours. A supplemental recharge should be performed if the battery pack OCV is

24.6 volts or less when measured at 25°C (77°F).

17 Acumentrics Corporation

8. BATTERIES AND RECYCLING

The batteries used by this Uninterruptible Power Source are recyclable. Proper disposal of the batteries is required. The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly. Please refer to local codes for proper disposal requirements or return the unit to a factory-authorized Service Center for battery replacement or disposal.

Battery replacement should be performed or supervised by personnel familiar with the danger of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing batteries, use the same number and type of sealed lead acid batteries as were originally contained in your UPS.

Caution - Do not dispose of battery in fire. The batteries may explode.

Caution - Do not open or mutilate the battery or batteries. They contain an electrolyte that is toxic and harmful to the skin.

Caution - A battery can present a risk of electrical shock and high short circuit current.

When replacing batteries, wristwatches and jewelry such as rings should be removed. Use only tools with insulated handles.

18 Acumentrics Corporation

9. WARRANTY INFORMATION

Limited Warranty

Acumentrics Corporation warrants its products to be free from defects in materials and workmanship for a period of one year from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from

Acumentrics. Products must be returned to Acumentrics with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. The product must be shipped back in the original packaging. This warranty does not apply to equipment, which has been damaged by accident, negligence, or miss-application or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

EXCEPT AS PROVIDED HEREIN, ACUMENTRICS CORPORATION MAKES NO

WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL ACUMENTRICS BE LIABLE FOR

DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING

OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF

SUCH DAMAGE. Specifically, Acumentrics is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise. This warranty gives you specific legal rights and you may also have other rights, which vary from state to state.

19 Acumentrics Corporation

10. LIFE SUPPORT USE INFORMATION

Life Support Policy

As a general policy, Acumentrics Corporation does not recommend the use of any of its products in life support applications where failure or malfunction of the Acumentrics product can be reasonably expected to cause failure of the life support device or to significantly effect its safety or effectiveness. Acumentrics does not recommend the use of any of its products in direct patient care. Acumentrics will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Acumentrics that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of Acumentrics is adequately protected under the circumstances.

Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pace makers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the U.S. FDA.

Acumentrics Corporation

20 Southwest Park, Westwood, MA 02090 Phone (781) 461-8251 Fax (781)-461-1261

20 Acumentrics Corporation

Appendix A

Optional Front Fan Filter Servicing Instructions

The front fan filter purchased with the ACG1250U or ACG1250U-24 has been designed to reduce the amounts of sand, dirt and dust, which can enter the unit via the fan. For this filter to operate effectively it must be serviced monthly. If the unit is being utilized in a harsh or dusty environment servicing should be more frequent.

To service the filter the following steps should be followed:

1. Remove the fan filter from the unit by gently pulling the top left and right hand corners of the filter out.

Once these corners are removed pull the filter cover gently off the fan cover

2. Once the filter cover is removed from the unit, the soft mesh can be removed from the filter housing and taped to remove loose dirt then rinse with warm water. If the filter mesh is extremely caked with dirt, a mild soap can be used to assist in the cleaning.

3. Once the mesh has been washed dry it thoroughly.

4. Place the clean dry mesh into the fan housing.

5. Place the fan filter back onto the unit by pressing firmly in the center on all four sides. Be sure the fan filter snaps into all four groves, which are on each side of the fan cover.

21 Acumentrics Corporation

advertisement

Key Features

  • 1000 Watts of continuous power
  • 24 VDC 250 Watt Output
  • Optional battery packs
  • Wide range voltage and frequency inputs
  • Protects against surges, spikes, brownouts, blackouts and noise
  • Continuous AC output from a high voltage DC bus

Related manuals

Frequently Answers and Questions

What is the battery pack weight?
The battery pack weighs 50 pounds, so handle it carefully when installing or removing it.
How does the UPS protect equipment from power problems?
The UPS continuously creates the AC output from a high voltage DC bus, providing clean, reliable power and protecting against surges, spikes, brownouts, blackouts and noise.
What is the purpose of the ON/OFF switch?
The ON/OFF switch powers the unit as well as turns on/off the audible alarm.
How do I de-energize the UPS in an emergency?
Move the I/O switch to the O (off) position and disconnect the power cord from the mains.
What are the recharge times for the battery packs?
The ACG26BP has a 2-hour recharge time to 90% capacity from full discharge. The ACG52BP has a 4-hour recharge time to 90% capacity from full discharge.
Where can I find information on the Service Center nearest me?
The Customer Service telephone number written on the front or back cover of this manual will provide information on the Service Center nearest you.
Download PDF