Sky Air - Daikin
Sky Air
Product catalogue 2016
for professionals
N
BLUEV EW
O
SKY A LUTION
IR R AN
LAUN
CH SP GE
RING
2016
Your business is our concern
Why choose Daikin
Our promise is to ensure that your customers can depend
on Daikin for the ultimate in comfort, so that they are free to focus
on their own working and home lives.
We promise to dedicate ourselves to technological excellence,
a design focus and the highest quality standards so that your
customers can trust and rely on the comfort we deliver.
Our promise to the planet is absolute. Our products are at the
forefront of low energy consumption and we continuously innovate
to reduce the environmental impact of HVACR solutions further.
We lead where others follow. We will continue our global leadership
in HVACR solutions as our specialist expertise in all market sectors
combined with 90 years’ experience enable us to deliver added
value in long-lasting relationships based on trust, respect and
credibility.
2
VRV Intro
Table of contents
7 reasons why Sky Air
is unique in the market
4
In the spotlight
6
Which applications?
10
Indoor units
14
Outdoor units
88
Biddle air curtains
160
Ventilation167
Control Systems
188
Options & accessories
208
Tools and platforms
216
3
ARGUE CARDS
Sky Air, the solution
for the light
commercial sector.
7 reasons why Sky Air is
unique in the market
1
High energy efficiency
›› Top seasonal efficiency
• A++ label both in cooling and heating
for combination FCQHG71F/100F + RZQG71L9V1/100L9V1
• Variable Refrigerant Temperature that automatically
adapts the refrigerant temperature to the load
›› First commercial R-32 unit boosting cooling efficiency with 5%
›› Auto cleaning cassette leading to 50% savings compared to standard cassettes
2
Top seasonal efficiency
Best comfort
›› Variable Refrigerant Temperature
preventing cold draughts
›› Low sound indoor and outdoor units
›› Presence and floor sensors direct the air flow away from persons,
while ensuring an even temperature distribution
›› Operation down to -20°C in heat pump operation
›› Fresh air intake integrated in indoor unit
presence sensor
floor sensor
Fresh air intake
3
Top reliability
›› For infrastructure cooling
›› unique boosted capacity indoor unit systems
›› duty rotation control
›› Gas-cooled PCB
›› Most extensive testing before new units
leave the factory
›› Widest support network and after sales service
›› All spare parts available in Europe
4
Market leading controls
VRV Intro
4
›› Intelligent Tablet Controller: control your Sky Air total solution
centrally from a touch screen
›› Dedicated control solutions
›› for retail applications with retail economizer
›› for infrastructure cooling with standard remote control
›› Daikin Cloud Service offers services such as online control, energy
monitoring, comparison of multiple sites
5
Intelligent Tablet Controller
Superior aesthetics
›› Fully flat cassette design unit that integrates fully flat into the ceiling
›› Auto cleaning cassette ensures dirt-free ceilings with high efficiency
filters for regular and dust prone areas
6
Unique installation benefits
›› 4-way blow ceiling suspended cassette (FXUQ) for rooms without
false ceiling.
Now connectable to Seasonal Smart and Classic
›› Plug & play Daikin air handling unit with ERQ condensing units
›› Total solution for cooling, heating, air curtains and ventilation
›› Dedicated assymetric combinations for infrastructure cooling
›› Cost-efficiently replace Daikin and non-Daikin R-22 and R-407C systems by keeping the refrigerant piping
›› Use up to 4 indoor units linked to one outdoor unit for long or
irregularly shaped rooms
7
FXUQ
AHU
Air curtain
Widest range of outdoor units
for small commercial
A product for each type of customer
Pair, twin, triple, double twin systems
Multi systems connecting to Sky Air indoors
Capacity class
25
35
50
60
71
100
125
140 200 250
40
50
52
68
80
90
4HP 5HP 6HP 8HP 10HP 12HP
Range
2.4
3.4
5.0
5.7
6.8
9.5
12.0
13.4 20.0 24.1
4.0
5.0
5.2
6.8
8.0
9.0
12.1
kW (cooling)
14.0
15.5
22.4
28.0
33.5
Industry-leading efficiency that dramatically cuts
See page 98
running costs and repays in <2 years
›› Up to Energy Label
›› Only dedicated solution for infrastructure cooling
›› Available in R-410A and R-32
See page 152
Industry-leading efficiency with individual control
of up to 9 indoor units
›› incorporates VRV IV standards and technologies
›› the most compact VRV
Versatile and effective for typical needs
See page 122
of most retail applications.
›› Up to Energy Label
See page 141
Multi model application Individual control of up to 5 indoor units
For large commercial applications
See page 131
Plug and play comfort at minimum up-front cost
See page 136
for busy shop environments
›› Up to Energy Label
(SEER A+ for 71 Cass)
5
In the spotlight
First light commercial product with R-32
Lowest environmental
footprint in it's class
More details
on page 106
Lowest environmental impact
GWP reduced with 68% as compared
with R-410A refrigerant
›› 10% lower refrigerant charge
››
Increased energy savings
thanks to
R-32 refrigerant (minimum 5% more efficient
in cooling when compared to R-410A products)
Reduced maintenance cost as no yearly
refrigerant containment leak check is required
Replacement technology
Operation range
down to -20°C in heating mode
Pair applications:
››
››
››
››
FCAHG71F / RZAG71LV1
FCAHG100F / RZAG100LV1
FCAHG125F / RZAG125LV1
FCAHG140F / RZAG140LV1
Be the leader in new markets
››
››
6
Technology you can trust.
Take the journey with us
Lead the market towards R-32
RZAG-LV1
FCAHG-F
VRV Intro
Unique cassette designs
Auto cleaning cassette
More details
on page 22
Industry-first and proven
360° air discharge design
Intelligent sensors increase
comfort and efficiency
presence
sensor
Flexible installation with
individual flap control
High efficiency filter
›› Increases efficiency with 50% and
makes maintenance easier since
the unit does not need to be
opened for filter cleaning
›› Dust can be removed easily
with a vacuum cleaner without
opening the unit
floor sensor
AUTO CLEANING FILTER
Fully flat cassette
More details
on page 34
Unique design in the market that integrates fully flat into
the ceiling Advanced technology and top efficiency combined
Unique design
›› Designed by a European design office to fully
meet the European taste.
›› Fully flat into the ceiling, leaving only 8mm.
›› Fully integrated in the one ceiling tile, enabling
lights, speakers and sprinklers to be installed in
adjoining ceiling tiles.
›› Decoration panel available in 2 colours (white and
white-silver).
Most
quiet
unit in
the market
(25dBA)
4-way blow ceiling suspended cassette
Unique Daikin unit for high rooms
with no false ceilings nor free floor space
Best in class quality
Connects to
More details
on page 77
Flexible installation
with individual flap control
Stylish unit
Stylish unit blends easily with any
interior. The flaps close entirely
when the unit is not operating and
there are no air intake grilles visible
7
In the spotlight
Unique Sky Air technologies and controls
Intelligent Tablet Controller
The Daikin Intelligent Tablet Controller gives you
central ontrol which allows different zones to be
set to different temperatures.
You can set pre- and post-trade modes
to save energy
The Daikin Intelligent Tablet Controller's local
control can be limited (amongst the staff) and
integrated with HQ control and monitoring
It is easy to use and intuitive
Daikin Cloud Service provides a flexible solution
which can grow with your business
Daikin Cloud Service's reduced communication
(polling mechanism) means your internal
payment network is secure. Via the Daikin
supplied 3G/4G router you can even run it
outside your network.
Online control from any device
Local solution
…
Replacement technology
›› Less installation time compared
to a full replacement allows you to tackle more
projects making it more profitable
›› Lower installation cost improves
your competitive edge
›› Replace non-Daikin systems
›› Extra bullit: Lower installation cost improves your
competitive edge
More details
on page 94
Reuse existing piping and wiring
Replace indoor and outdoor units only
Replace both Daikin
and other manufacturer systems
Variable refrigerant temperature
Customised, intelligent
and efficient solution
Daikin Sky Air systems are designed to adapt their
operation intelligently to meet your customers’
specific heating and cooling requirements, without
compromising efficiency. When maximum cooling or
heating is required (a big difference between
the indoor temperature and the setpoint), the system
is able to deliver the required capacity quickly. But
8
at times when the cooling or heating requirement
is lower (a small difference between the indoor
temperature and the setpoint), the system will
automatically adapt its refrigerant in order to save
energy and avoid cold draughts. Intelligent Sky Air
systems ensures peace of mind at all times without
any need for manual adjustment.
VRV Intro
In the spotlight
Infrastructure cooling
More details
on page 100
›› For rooms and enclosures that require round-the-clock cooling
›› Where continuous uptime is the absolute requirement for server data protection
equipment protection
Between
20-40%
Reliable
Guaranteed system operation:
›› Oversized indoor units boost cooling
capacity and prevent freeze-ups on the
indoor side
›› Wide operating range envelope:
operation range in cooling down
to -15°C and up to +50°C
sensible capacity
increase
Efficient
Flexible
Optimum return on investment:
›› Lowers running costs by using
highly efficient direct expansion
cooling systems
›› Lower running costs compared to other
DX systems and water based chillers.
›› Minimises environmental impact
with A++ energy labels
›› Reduces mechanical cooling and energy
consumption with the free cooling
option for single phase systems
›› Scalable in
capacity
›› Improved infrastructure control and
management
›› Lower physical footprint since no floor
space is occupied
›› Wide range of indoor units to suit
application preferences (ceiling
suspended cassettes, wall mounted
indoors, concealed ceiling ducted type
indoors)
BRC1E53
Duty rotation compatibility
Modelname
Wired remote control
BRC1E53*
Conceiled ceiling system
FBQ-D*
Wall mounted system
FAQ-C9*
Ceiling suspended system
FHQ-CB*
Multizoning
Control of multiple climate zones
with one duct indoor
Motorized dampers regulated according to ∆T
Automatic airflow adjustment according
to the demand
Centralized zone controller for central control
Plug & play plenum
Wireless room thermosthat for each zone
9
Which applications?
Ventilation
22
Air curtain
10
Control systems
Cooling and heating
Which applications?
VRV Intro
One system,
for comfort cooling / heating and
infrastructure cooling applications
22
Comfort heating and cooling
›› Extract heat from the outside air, even in cold
weather (down to -20°C).
›› Electrically powered compressor.
›› Extremely effective at heating.
›› Silent and discreet,
›› State-of-the-art technology to keep energy bills as
low as possible.
Top seasonal efficiency
›› A++ label both in cooling and heating
for combination FCQHG71F/100F +
RZQG71L9V1/100L9V1
›› Top efficiency by choosing R-32 products (minimum
5% more efficient when compared to R-410A)
Reliable infrastructure cooling
›› For rooms and enclosures that require
round-the-clock cooling
›› Oversized indoor units boost cooling capacity and
prevent freeze-ups on the indoor side
›› Wide operating range envelope:
operation range in cooling down to -15°C
and up to +50°C
Control systems
User-friendly controls allow your customers to
manage their Sky Air system for maximum efficiency:
›› From individualised unit control to centralised
management via touchscreen options and code
based controllers, they are in control at all times.
›› The DIII-net connection is standard, allowing you to
link into the wider building management systems.
›› Buildings can be monitored from a distance using
Internet monitoring.
Ventilation
Daikin’s ventilation option provides a supply
of fresh air to help create a healthy and high quality
indoor environment.
Biddle air curtains
›› Biddle air curtains can be used in combination
with the Sky Air system to provide highly efficient
heating at building entrances:
Ideal for buildings with open door policies such
as retail stores.
›› Year round climate control and comfort even on
the most demanding days.
›› Payback time of less than 12 months compared with
electric air curtains.
11
‘We were very happy to work with
Daikin in installing one of the latest
fully controllable systems with
operational flexibility, which met all
our requirements.’
Retail shop representative
Shops
Check on
Reducing retail costs
›› Creates an inviting atmosphere for your customers
›› Discreet with limited visual and operating impact
›› Reduces energy usage and costs
›› Worry-free installation
›› User-friendly control
In the current commercial environment, retailers are
under pressure to reduce both store development
and running costs. Legislation adds further financial
pressure with different energy-efficient schemes.
Therefore affordable, energy-efficient solutions
are vital to minimise lifetime costs, while ensuring
compliance with the latest regulations.
Whatever the site and requirements we can design
a system that is economical, has low environmental
impact and uses the very latest in advanced VRV
technology. Our heat pumps extract heat from the
outside air even in cold weather to warm the retail
space and can be installed either on roof tops or
against walls - the ultimate in installation flexibility.
And our air curtains solve that problem of comfort loss
resulting from exterior doors.
"Leading edge design
in harmony with the construction
and interior design.“
Architect
Office
Efficiency in the workplace
›› Fully flat cassette: Design and genius in one.
›› Cutting the cost of hot water.
›› Fresh air: A healthier office atmosphere.
›› Centralised control: Complete Daikin package for
office building management
Efficient building and facilities management is key
to minimising operational costs. Daikin’s customised
office solutions give you full control over energy
12
consumption – creating the ideal working conditions
and minimising environmental impact.
Daikin’s office air conditioning can be
integrated into a whole climate control solution.
Heat recovery between components, free cooling
ventilation and free hot water production all result in
lower running costs and minimum carbon emissions.
www.youtube.com/
DaikinEurope
Store & shop
VRV Intro
“Total renovation and expansion
of the restaurant meant new air
conditioning equipment was
required. Daikin was the first and
only supplier to contact as we had
already had good experience in
the past!” Owner of a highly-rated
restaurant.
Restaurants
Perfect ambiance for dining
›› Ensures an even temperature distribution to create
the perfect dining environment.
›› Highly energy efficient
›› Uses intelligent control systems operated from one
central location.
your customer’s restaurant into a comfortable,
welcoming environment. And with centralised
control and easy scheduling for the entire restaurant
system, energy use is minimised to reduce your
customer’s running costs.
Nothing should distract diners from enjoying
the perfect ambience, and that ambience
includes the optimum temperature. That is exactly
what Daikin’s concealed ceiling units deliver through
whisper quiet operation and improved comfort from
the 3-step air flow control. These turn
“A reliable system
and guaranteed
continuous operation are what
count for me.” General office
manager
IT serverrooms,
laboratories
and telecom shelters
Sky Air for infrastructure cooling
›› Continuous cooling operation.
›› Dedicated infrastructure cooling settings
›› Unique selection method with capacity tables
down to -15°C outdoor temperature
›› Enhanced reliability thanks to assymetric
combinations (e.g. FHQ125C + RZQG100L9V1)
with required seasonal energy labels
Servers, especially racks of servers, generate a great
deal of heat and this needs to be removed through
continuous cooling. This is achieved through
automatic switching between units after a certain
period of use to ensure that at any time, one unit is
working while the other is available for maintenance.
Given the critical importance of continuous cooling
for server rooms, the system can be managed via an
RTD-10 controller that can monitor and control up
to 8 indoor units either directly or via the building
management system (RTD-NET).
13
Sky Air, from high
specification, tailored
solutions to primary
cooling and heating
14
Indoor units
Indoor
units
Benefits for the installer
A wide range of high quality and
design indoor units for residential and light
commercial applications
›› Modular designs and factory fitted extras make
installation easier to achieve.
Products overview Benefits overview
Benefits for the consultant
›› You will have the confidence of knowing that you
can recommend the right climate control systems
to meet tomorrow’s legislation
›› You will have systems that are designed to blend
into any décor and provide optimal performance
with top seasonal efficiencies
›› You will have access to innovative technology to
maximize the climate control performance of
the entire building
›› Your credentials as an eco-conscious consultant
and designer will be enhanced.
Benefits for the end user
›› Your climate control system will meet legal
requirements well beyond the current legislation
›› You will obtain optimal seasonal performance thus
saving energy and reducing costs
›› You will have even better energy efficient
units when choosing our Sky Air R-32
product range (minimum 5% more efficient
compared to R-410A products)
›› The climate control system will add value to
the building thus protecting your investment
›› You will save on installation and running costs,
obtain rapid return on investment and contribute to
ecological protection objectives.
Ceiling mounted cassettes
16
18
22
FCAHG-F
24
FCQG-F25
FCQHG-F28
FFQ-C34
ACQ-D
38
Concealed ceiling units
40
FDBQ-B40
FDXS-F(9)42
FBQ-D46
FDQ-C54
FDQ-B59
ABQ-C
62
Wall mounted units
66
FAQ-C966
Ceiling suspended units
69
FHQ-CB69
AHQ-C
75
FUQ-C77
Floor standing units
80
FVQ-C80
Concealed floor standing units
83
FNQ-A83
15
Indoor units
Product overview
Type
Model
NEW
UNIQUE
Product name
FCAHG-F
High COP,
round flow cassette
UNIQUE
PG
24
FCQHG-F
28
FCQG-F1
25
FFQ-C
34
ACQ-D
38
Small concealed
ceiling unit
FDBQ-B
40
Slim concealed
ceiling unit
FDXS-F (9)
42
Concealed ceiling unit with medium ESP
FBQ-D1
46
Concealed ceiling unit with high ESP
FDQ-C
54
Concealed ceiling unit with high ESP
FDQ-B 1
59
Concealed ceiling unit
ABQ-C
62
Wall mounted unit
FAQ-C9
66
Ceiling suspended unit
FHQ-CB1
69
FUQ-C1
77
Ceiling suspended unit
AHQ-C
75
Floor standing unit
FVQ-C
80
Concealed floor standing unit
FNQ-A
83
High COP,
round flow cassette
Ceiling mounted cassette
1st R-32
commercial
unit in
the European
market
UNIQUE
Round flow cassette
UNIQUE
Fully flat cassette
Siesta, 4-way blow ceiling mounted unit
Concealed ceiling
Wall mounted
Ceiling suspended
UNIQUE
4-way blow ceiling suspended unit
Floor standing
1) Twin, triple, double twin application is only possible up to 125 class
16
Indoor units
Capacity class (kW)
35
50
60
71
100
125
140
First R-32 BLUEVOLUTION light commercial range available in Europe
--Lowest environmental impact: reduced GWP and higher efficiency compared to R-410A products
--5 different fan speeds available
--Reduces maintenance costs as no yearly refrigerant containment check is required
--Includes all R-410A high COP round flow cassette features
   
360° air discharge for the highest efficiency and comfort
--High COP cassette ensures top performance for commercial applications
--Auto cleaning function ensures high efficiency
--Intelligent sensors save energy and maximize comfort
--Flexibility to suit every room layout
   
360° air discharge for the highest efficiency and comfort
--Auto cleaning function ensures high efficiency
--Intelligent sensors save energy and maximize comfort
--Flexibility to suit every room layout
--Lowest installation height in the market
--27~29 dB(A) on low fan speed
Unique design in the market that integrates fully flat into the ceiling
--Perfect integration in standard architectural ceiling tiles
--Blend of iconic design and engineering excellence with a white or silver and white finish
--Intelligent sensors save energy and maximize comfort
--Flexibility to suit every room layout without changing the location of the unit!
--Quietest 600 x 600 cassette on the market

  

      
Slimmest yet most powerfull medium static pressure unit on the market!
--Slimmest unit in class, only 245mm
--Low operating sound level
--Medium external static pressure up to 150Pa facilitates using flexible ducts of varying lengths
--Automatic air flow adjustment function measures the air volume and static pressure and adjusts it towards
the nominal air flow, guaranteeing comfort
      
ESP up to 200Pa, ideal for large sized buildings
--Discretely concealed in the ceiling: only the grilles are visible
--Possibility to change ESP via wired remote control allows optimisation of the supply air volume
--Flexible installation as the air suction direction can be altered from rear to bottom suction

ESP up to 250Pa, Ideal for extra large sized spaces
--Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible
--Up to 26.4kW in heating mode
Ideal for medium sized shops with false ceilings
--Discretely concealed in the ceiling: only the grilles are visible
--Best protection against possible water leakage
   
For rooms with no false ceilings nor free floor space
--The air is comfortably spread up- and downwards thanks to 5 different discharge angles
--Easy maintenance as this can be done from the front of the unit
--Easy to install: 100 class is 35% lighter than previous model
--Flexible to install: pipe connection can be bottom, left or right
 
      
New
combination
with Seasonal
Classic
available!
Unique Daikin unit for high rooms with no false ceilings nor free floor space
--Even rooms with ceilings up to 3.5m can be heated up or cooled down very easily!
--Flexibility to suit every room layout without changing the location of the unit!
--Optimum comfort guaranteed with automatic air flow adjustment to the required load
--The air is comfortably spread up- and downwards thanks to 5 different discharge angles
  
For wide rooms with no false ceilings nor free floor space
--Guarantees a stable temperature
   
For spaces with high ceilings
--Ideal solution for commercial spaces with no or narrow false ceilings
--Even rooms with very high ceilings can be heated up or cooled down very easily!
--Guarantees a stable temperature
--Vertical and horizontal outblow
   
Designed to be concealed in walls, only grilles remain visible
--Slimmest unit on the market with a depth of only 200mm!
--Both window sill or ducted installation are possible thanks to sufficient ESP
--Whisper quiet operation allows installation in any location

   
Slim design for flexible installation
--Medium external static pressure up to 40Pa
--Small capacity unit developed for small of well insulated rooms
For wide rooms with no false ceilings nor free floor space
--Ideal for comfortable air flow in wide rooms thanks to Coanda effect
--Even rooms with ceilings up to 3.8m can be heated up or cooled down very easily!
--Can be mounted in corners or narrow spaces without any problem
250
      
Solution addressing the primary needs of small shops
--Improved energy efficiency: up to A+ energy labels
--Control several indoor units at the same time
--Exclusively offered for pair applications
Designed for hotel bedrooms and ensuring a good night rest
--Compact dimensions enable installation in narrow ceiling voids
--Easy mounting: drain pan can be located left or right of the unit
--Discretely concealed in the ceiling: only the grilles are visible
--Flexible installation as the air suction direction can be altered from rear to bottom suction
200
Indoor units
25
   
17
Indoor units
Benefits overview
We care
Seasonal efficiency - Seasonal efficiency gives a more realistic indication on how efficient air conditioners operate
Smart use of energy over an entire heating or cooling season.
Inverter technology
In combination with inverter controlled outdoor units
Home leave
operation
During absence, the indoor temperature can be maintained at a certain level.
Fan only
The air conditioner can be used as fan, blowing air without cooling or heating.
Auto cleaning filter
The filter automatically cleans itself once per day. Simplicity of upkeep means optimum energy efficiency and maximum comfort
without the need for expensive or time-consuming maintenance.
Floor and presence
sensor
The presence sensor directs the air away from any person detected in the room, when the air flow control is on.
The floor sensor detects the average floor temperature and ensures an even temperature distribution between ceiling and floor.
Comfort
Air filter
Removes airborne dust particles to ensure a steady supply of clean air.
Dry programme
Allows humidity levels to be reduced without variations in room temperature.
Ceiling soiling
prevention
A special function prevents air blowing out too long in horizontal position, to prevent ceiling stains.
Vertical auto swing
Possibility to select automatic vertical moving of the air discharge louvre, for uniform air flow and temperature distribution.
Fan speed steps
Allows to select up to the given number of fan speed.
Individual flap
control
Individual flap control via the wired remote controller makes it simple to fix the position of each flap individually,
to suit any new room configuration. Optional closure kits are available as well.
Weekly timer
Timer can be set to start operation anytime on a daily or weekly basis
Infrared remote
control
Infrared remote control with LCD to start, stop and regulate the air conditioner from a distance.
Other functions
Remote control & timer
Air flow
Whisper quiet
Air treatment
When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally
and the fan to low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired.
Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed
not to disturb the quiet of the neightbourhood.
Humidity
control
Draught prevention
18
Auto cooling-heating
Automatically selects cooling or heating mode to achieve the set temperature.
changeover
Wired remote control Wired remote control to start, stop and regulate the air conditioner from a distance.
Centralised control
Centralised control to start, stop and regulate several air conditioners from one central point.
Infrastructure
cooling
Remove in a reliable, efficient and flexible way the heat constantly generated by the IT and server equipment
to ensure maximum uptime while offering the best return on investment.
Auto-restart
The unit restarts automatically at the original settings after power failure.
Self-diagnosis
Simplifies maintenance by indicating system faults or operating anomalies.
Drain pump kit
Facilitates condensation draining from the indoor unit.
Twin/triple/double
twin application
Multi model
application
VRV for residential
application
2, 3 or 4 indoor units can be connected to only 1 outdoor unit even if they have different capacities. All indoor units operate within
the same mode (cooling or heating) from one remote control.
Up to 5 indoor units (even different capacities) can be connected to a single outdoor unit. All indoor units can individually be
operated within the same mode.
Up to 9 indoor units (even different capacities and up to 71 class) can be connected to a single outdoor unit.
All indoor units can individually be operated within the same mode.
Indoor units
NEW
Ceiling
suspended units
Concealed ceiling units
FCAHG-F
FCQHG-F
FCQG-F
FFQ-C
ACQ-D
FDBQ-B
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5
3
3
3
•
•
•
•
•
•
•
•
•
4
2
FDXS-F(9)
FBQ-D
FDQ-C
•
•
•
•
•
•
•
•
•
FDQ-B
•
•
•
4-Way blow
Wall
ceiling
mounted
suspended
unit
unit
Floor
standing
units
ABQ-C
FHQ-CB
AHQ-C
FUQ-C
FAQ-C9
FVQ-C
FNQ-A
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
3
3
3
2
•
•
•
3
3
Indoor units
Ceiling mounted
cassette units
3
2
3
3
3
•
•
•
optional optional optional optional standard
•
depending
on controller
•
•
•
•
optional optional optional
•
•
•
optional standard optional optional
optional
optional optional optional optional optional optional optional optional optional optional standard optional optional optional optional optional optional
optional optional optional optional
•
•
•
•
•
•
•
•
•
•
•
•
optional optional optional optional
•
•
•
•
•
•
standard standard standard standard standard
•
•
•
•
•
•
•
•
•
•
•
•
•
•
standard standard
•
•
•
•
•
•
•
optional
•
•
•
•
•
optional
•
•
•
•
optional optional optional optional
•
•
•
•
•
•
•
•
•
•
•
•
•
standard optional
•
•
•
•
•
19
Sky Air
FULLY FLAT CASSETTE
FFQ-C
CONCEALED FLOOR
STANDING UNIT , FNQ-A
20
CONCEALED CEILING UNIT,
FDXS-F(9) - FBQ-D - ABQ-C
4-WAY BLOW CEILING
SUSPENDED CASSETTE , FUQ-C
Sky Air
Indoor units
WALL MOUNTED UNIT,
FAQ-C
CEILING SUSPENDED CASSETTE,
FHQ-C
AUTO CLEANING CASSETTE WITH FINE MESH
FILTER, IDEAL FOR CLOTHING SHOPS
21
ARGUE CARDS
FCQG-F/FCQHG-F/FXFQ-A
Auto cleaning cassette
More energy efficient and user-friendly
than any other cassette
›› Running costs are reduced
by 50% compared with standard solutions
›› Automatic filter cleaning.
›› Less time is required to maintain the filter:
dust can be removed easily with a vacuum cleaner
without opening the unit.
Finer mesh panel
›› For dust prone areas (i.e. clothing and book shops)
a finer mesh panel (BYCQ140DGF) ensures
consistent performance and optimum air
distribution
›› Clean ceilings ensured thanks to fine mesh and
daily cleaned filter
BYCQ140DG
BYCQ140DGF
Auto-cleaning panel
auto-cleaning panel
with fine mesh filter
White with grey louvers
White with grey louvers
Self-cleaning cassette for maintaining
the optimum store atmosphere
Air distribution with a clean filter
References
Coral shop, UK
Running costs were reduced
by up to 50% compared
with standard solutions
thanks to daily filter cleaning.
Dust can be removed easily
with a vacuum cleaner
without opening the unit.
Air distribution with a dusty filter
Energy consumption
(kWh)
9000
8000
7000
6000
5000
Up to 50% savings
thanks to
automated daily
cleaning
Standard round
flow cassette
Auto cleaning cassette
4000
3000
2000
1000
Cumulative energy comparison over 12 months
22
0
July
Aug.
Sept.
Oct.
Nov.
Dec.
Jan.
Feb.
March
April
May
June
July
Why choose a round flow cassette?
Indoor units
• 360° air discharge for optimum comfort
• Intelligent sensors for maximum efficiency
360° air discharge for improved comfort
Benefits for the installer
›› Industry-first and proven design.
Intelligent sensors improve efficiency
and comfort even more
›› The presence sensor
adjusts the set point if
no one is detected in
the room leading to up
to 27% savings. It also
automatically directs air
flow away from any person
to avoid draught.
presence
sensor
floor sensor
›› The infrared floor sensor detects the average
floor temperature and ensures even temperature
distribution between ceiling and floor to prevent
cold feet.
Flexible installation
›› Flaps can be individually controlled or closed
using the wired remote control, to suit room
configuration. Optional closure kits are
also available.
›› Product with unique functions in this market.
›› Less time needed for onsite maintenance.
›› Use the controller to individually open or close any
of the four flaps to easily adapt to a changing room layout.
›› Easy set-up of the sensor option to improve comfort and
save energy.
Benefits for the consultant
›› Product with unique functions in this market.
›› Designed for use in all types and sizes of commercial offices
and retail environments.
›› Ideal product for improving BREEAM score/EPBD in
combination with Sky Air Seasonal Smart
or VRV IV heat pump units.
Benefits for the end user
›› Designed for use in all types and sizes of commercial offices
and retail environments.
›› Perfect environment conditions:
no more draughts or cold feet.
›› Save up to 50% on running costs with the auto-cleaning panel,
which also facilitates maintenance.
›› Your customers can save up to 27% on their energy bills
thanks to the sensor option.
›› Flexible use of space thanks to individual flap control.
Marketing tools
›› Visit the website: www.daikineurope.com/minisite/
round-flow-cassette/
www.youtube.com/DaikinEurope
23
FCAHG-F + RZAG-LV1
High COP, round flow cassette
360° air discharge for optimum efficiency and comfort
›› Industry leading technology extended with R-32
›› 68% lower GWP compared to R-410A products
›› 10% lower refrigerant charge compared to R-410A products
›› Minimum 5% more efficient in cooling when compared to R-410A
products
FCAHG71-100-125-140F
›› Duty rotation control (via BRC1E53A/B/C)
›› Power saving mode can be set to 70% or 40% of the demand (via
BRC1E53A/B/C)
›› 5 different fan speeds available
›› Includes all R-410A high COP round flow cassette features
RZAG100-140L7V1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
FCAHG + RZAG
kW
kW
kW
kW
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP/A
Annual energy consumption
kW
71F + 71LV1
6.8
7.5
1.66
1.56
BRC1E52A-B
100F + 100LV1
9.5
10.8
2.15
2.16
A++
9.50
6.80
125F + 125LV1
12.0
13.5
3.00
3.07
kW
324
A+
5.65
452
Colour
Dimensions
Weight
Sound power level
Cooling
Heating
Sound pressure level Cooling
Heating
Refrigerant
Type
GWP
Outdoor unit
Dimensions
Unit
Sound power level
Cooling
Sound pressure level Cooling
Heating
Night quiet mode
Operation range
Cooling
Heating
Refrigerant
Type/Charge/GWP
Piping connections
Liquid
Gas
Piping length
HeightxWidthxDepth
HeightxWidthxDepth
High/Low
High/Low
HeightxWidthxDepth
Nom.
Nom.
Level 1
Ambient
Ambient
OD
OD
OU - IU
System
Power supply
Phase/Frequency/Voltage
Contains fluorinated greenhouse gases
24
Min.~Max.
Min.~Max.
Max.
Equivalent
Chargeless
3.35
4.12
2,000
-
kWh
1,743
2,753
EER
4.09
4.42
COP
4.80
4.99
Annual energy consumption
kWh
830
1,075
Energy label
Cooling/Heating
A/A
Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load | EER/COP according to Eurovent 2012, for use outside EU only
Unit
Model
2,879
4.00
4.40
1,500
A++
9.13
Nominal efficiency
Indoor unit
Dimensions
Decoration panel
9.52
140F + 140LV1
13.4
15.5
4.00
3.77
-
12.00
6.94
605
7.35
kWh
BRC7FA532F
FCAHG
mm
mm
kg
dBA
dBA
dBA
dBA
RZAG
mm
dBA
dBA
dBA
dBA
°CDB
°CWB
kg/TCO₂eq
mm
mm
m
m
m
Hz/V
71F
100F
125F
140F
288x840x840
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
130x950x950 / 130x950x950 / 50x950x950 / 50x950x950
10.3 / 10.3 / 5.4 . 5.4
53
61
53
61
36/29
44/33
45/35
45/37
36/29
44/33
45/35
45/37
R-32
675
71LV1
990x940x320
100LV1
125LV1
1,430x940x320
66
51
64
48
50
43
49
51
140LV1
67
52
52
45
-15~50
-20~15.5
R-32/2.6/1.8/675
R-32/3.4/2.3/675
9.52
15.9
55
75
85
100
30
1~/50/60/220-240
FCQG-F + RXS-L3/L
Round flow cassette
360° air discharge for optimum efficiency and comfort
›› Lowest installation height in the market: 204mm for class 71
›› Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
›› Modern style decoration panel is available in 4 different variations
›› Daily automatic filter cleaning results in higher efficiency, comfort and
lower maintenance costs.
›› Two optional intelligent sensors improve energy efficiency and comfort.
›› No optional adapter needed for DIII-connection, link your unit into the
wider building management system
›› Branch duct discharge allows to optimize air distribution in irregular
shaped rooms or to supply air to small adjacent rooms
›› Reduced energy consumption thanks to specially developed small tube
heat exchanger, DC fan motor and drain pump
›› Standard drain pump with 675mm lift increases flexibility
and installation speed
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Min./Nom./Max.
Min./Nom./Max.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
Min./Nom./Max.
Min./Nom./Max.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Model
HeightxWidthxDepth
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
FCQG + RXS
kW
kW
kW
kW
kW
kWh
kW
kWh
kWh
FCQG
mm
kg
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
Indoor units
Combination with split outdoor units is ideal for small retail,
offices or ­residential applications
FCQG35-50-60F
RXS35L3
35F + 35L3
1.3/3.4/4.0
1.3/4.20/5.2
0.400/0.909/1.100
0.230/1.200/1.840
BRC1E52A-B, BRC7FA532F
50F + 50L
1.7/5.0/5.3
1.7/6.00/6.0
-/1.410/-/1.620/A++
5.00
6.48
270
3.50
6.35
193
A++
3.32
4.90
949
3.74
3.50
455
A/B
4.36
4.29
1,426
3.55
3.7
705
A/A
35F
50F
204x840x840
60F + 60L
1.7/5.7/5.7
1.7/7.0/7.0
-/1.640/-/1.990/5.70
6.22
321
A+
4.71
4.00
1,646
3.48
3.52
820
A/B
60F
18
19
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
130x950x950 / 130x950x950 / 50x950x950 / 50x950x950
10.3 / 10.3 / 5.4 . 5.4
Resin net with mold resistance
12.5/10.6/8.7
12.6/10.7/8.7
13.6/11.2/8.7
12.5/10.6/8.7
12.6/10.7/8.7
13.6/11.2/8.7
49
51
49
51
31/29/27
33/31/28
31/29/27
33/31/28
BRC7FA532F
BRC1D52 / BRC1E52A/B
1~ / 50 / 220-240
Outdoor unit
Dimensions
Weight
Sound power level
RXS
35L3
50L
60L
Unit
HeightxWidthxDepth
mm
550x765x285
735x825x300
Unit
kg
34
47
48
Cooling
dBA
61
62
Heating
dBA
61
62
Sound pressure level Cooling
High/Low/Silent operation
dBA
48/-/44
48/44/49/46/Heating
High/Low/Silent operation
dBA
48/-/45
48/45/49/46/Operation range
Cooling
Ambient
Min.~Max.
°CDB
-10~46
Heating
Ambient
Min.~Max.
°CWB
-15~18
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/1.2/2.5/2,087.5
R-410A/1.7/3.5/2,087.5
R-410A/1.5/3.1/2,087.5
Piping connections
Liquid
OD
mm
6.35
Gas
OD
mm
9.5
12.70
Piping length
OU - IU
Max.
m
20
30
System
Chargeless
m
10
Additional refrigerant charge
kg/m
0.02 (for piping length exceeding 10m)
Level difference
IU - OU
Max.
m
15
20.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
1~ / 50 / 220-230-240
Current - 50Hz
Maximum fuse amps (MFA)
A
10
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) ). For more detailed information
on each combination, please refer to the electrical data drawing. (3) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently
not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt. (4) BYCQ140D7W1: pure white standard panel with grey louvers; BYCQ140D7W1W: pure white
standard panel with white louvers; BYCQ140D7GW1: pure white auto cleaning panel.
25
FCQG-F + RZQSG-L3/9V1/L(8)Y1
Round flow cassette
360° air discharge for optimum efficiency and comfort
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
›› Lowest installation height in the market: 204mm for class 71
›› Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
›› Modern style decoration panel is available in 4 different variations
›› Daily automatic filter cleaning results in higher efficiency, comfort
and lower maintenance costs.
›› Two optional intelligent sensors improve energy efficiency and
comfort.
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system
›› Branch duct discharge allows to optimize air distribution in
irregular shaped rooms or to supply air to small adjacent rooms
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
FCQG + RZQSG 71F + 71L3V1
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Model
HeightxWidthxDepth
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
kW
kW
kW
kW
6.8
7.5
2.12
2.08
kW
kWh
6.80
6.10
390
kW
6.33
›› Reduced energy consumption thanks to specially developed small
tube heat exchanger, DC fan motor and drain pump
›› Standard drain pump with 675mm lift increases flexibility and
installation speed
100F +
100L9V1
9.5
10.8
2.88
3.05
A++
9.50
6.50
512
A+
7.60
4.10
kWh
kWh
2,162
3.21
3.61
1,060
2,596
3.30
3.54
1,440
A/A
FCQG
mm
kg
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
140F +
140L9V1
13.4
15.5
4.45
4.54
3.01
8.03
4.01
2,804
3.21
3.41
1,870
A/B
-
100F +
100L8Y1
9.5
10.8
2.88
3.05
A++
9.5
6.5
512
125F +
125L8Y1
12.0
13.5
3.74
3.96
A
12
5.3
793
140F + 140LY1
13.4
15.5
4.45
4.54
3.01
A+
7.6
4.1
2,596
3.30
3.54
1,440
A/A
8.03
4.01
2,804
3.21
3.41
1,870
A/B
2,225
-
71F
100F
125F
140F
100F
125F
140F
204x840x840
246x840x840
21
24
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
130x950x950 / 130x950x950 / 50x950x950 / 50x950x950
10.3 / 10.3 / 5.4 / 5.4
Resin net with mold resistance
15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
22.8/17.6/12.4
26.0/19.2/12.4
15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
22.8/17.6/12.4
26.0/19.2/12.4
51
54
58
54
58
51
54
58
54
58
33/31/28
37/33/29
41/35/29
37/33/29
41/35/29
33/31/28
37/33/29
41/35/29
37/33/29
41/35/29
BRC7FA532F
BRC1D52 / BRC1E52A/B
1~ / 50 / 220-240
71L3V1
100L9V1
125L9V1
140L9V1
100L8Y1
125L8Y1
140LY1
Unit
HeightxWidthxDepth
1,430x940x320
990x940x320
1,430x940x320
770x900x320
990x940x320
Unit
67
72
74
95
82
101
Cooling
65
70
69
70
69
Nom./Silent operation
Cooling
49/47
53/54/53/54/53/Heating
Nom.
51
57
58
54
57
58
54
Night quiet mode
Level 1
49
Min.~Max.
Operation range
Cooling
Ambient
-15~46
Min.~Max.
Heating
Ambient
-15~15.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
Equivalent
m
System
70
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
15
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
32
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing. (3) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently
not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt. (4) BYCQ140D7W1: pure white standard panel with grey louvers; BYCQ140D7W1W: pure white
standard panel with white louvers; BYCQ140D7GW1: pure white auto cleaning panel.
26
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
125F +
125L9V1
12.0
13.5
3.74
3.96
A
12.00
5.30
793
FCQG-F + RZQG-L9V1/L(8)Y1
Round flow cassette
360° air discharge for optimum efficiency and comfort
Indoor units
Combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FCQG100-125-140F
RZQG100-125-140L9V1/L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
kW
kW
kW
kW
71F +
71L9V1
6.8
7.5
2.01
1.89
kW
6.80
FCQG + RZQG
Nom.
Nom.
Cooling
Heating
Cooling
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Model
HeightxWidthxDepth
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
100F +
100L9V1
9.5
10.8
2.45
2.60
A++
9.50
6.80
kWh
kW
kWh
kWh
350
A+
6.33
4.20
2,110
3.39
3.97
1,005
489
A++
11.30
4.61
3,432
3.87
4.15
1,225
A/A
125F +
125L9V1
12.0
13.5
3.22
3.72
A+
12.00
6.00
700
A+
12.66
4.10
4,323
3.73
3.63
1,610
140F +
140L9V1
13.4
15.5
3.21
3.61
-
BRC1E52A-B, BRC7FA532F
71F +
71L8Y1
6.8
7.5
2.01
1.89
100F +
100L8Y1
9.5
10.8
2.45
2.60
A++
6.8
9.5
6.8
350
A+
6.33
4.2
2,110
3.39
3.97
1,005
489
A++
11.3
4.61
3,432
3.87
4.15
1,225
A/A
125F +
125L8Y1
12.0
13.5
3.22
3.72
A+
12
6
700
A+
12.66
4.1
4,323
3.73
3.63
1,610
140F +
140LY1
13.4
15.5
4.17
4.30
3.21
3.61
-
FCQG
71F
100F
125F
140F
71F
100F
125F
140F
mm 204x840x840
246x840x840
204x840x840
246x840x840
kg
21
24
21
24
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
mm
130x950x950 / 130x950x950 / 50x950x950
kg
10.3 / 10.3 / 5.4 / 5.4
Resin net with mold resistance
m³/min 15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
m³/min 15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
15.0/12.1/9.1 22.8/17.6/12.4
26.0/19.2/12.4
dBA
51
54
58
51
54
58
dBA
51
54
58
51
54
58
dBA
33/31/28
37/33/29
41/35/29
33/31/28
37/33/29
41/35/29
dBA
33/31/28
37/33/29
41/35/29
33/31/28
37/33/29
41/35/29
BRC7FA532F
BRC1D52 / BRC1E52A/B
Hz / V
1~ / 50 / 220-240
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
RZQG
71L9V1
100L9V1
125L9V1
140L9V1
71L8Y1
100L8Y1
125L8Y1
140LY1
Unit
HeightxWidthxDepth
mm 990x940x320
1,430x940x320
990x940x320
1,430x940x320
Unit
kg
69
95
80
101
Cooling
dBA
64
66
67
69
64
66
67
69
Cooling
Nom.
dBA
48
50
51
52
48
50
51
52
Heating
Nom.
dBA
50
52
53
50
52
53
Night quiet mode
Level 1
dBA
43
45
43
45
Min.~Max.
°CDB
Operation range
Cooling
Ambient
-15~50
Min.~Max.
°CWB
Heating
Ambient
-20~15.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
75
50
75
Equivalent
m
System
70
90
70
90
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
32
20
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing. (3) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently
not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt.
27
FCQHG-F + RZQSG-L3/9V1/L(8)Y1
High COP, round flow cassette
360° air discharge for optimum efficiency and comfort
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
›› High COP cassette ensures top performance
›› Lowest installation height in the market: 204mm for class 71
›› Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
›› Modern style decoration panel is available in 4 different variations
›› Daily automatic filter cleaning results in higher efficiency, comfort
and lower maintenance costs.
›› Two optional intelligent sensors improve energy efficiency and
comfort.
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system
›› Branch duct discharge allows to optimize air distribution in
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
FCQHG + RZQSG 71F + 71L3V1
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Model
HeightxWidthxDepth
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
kW
kW
kW
kW
6.8
7.5
1.94
1.83
kW
6.80
6.50
366
irregular shaped rooms or to supply air to small adjacent rooms
›› Reduced energy consumption thanks to specially developed small
tube heat exchanger, DC fan motor and drain pump
›› Standard drain pump with 675mm lift increases flexibility and
installation speed
100F +
100L9V1
9.5
10.8
2.57
2.51
125F +
125L9V1
12.0
13.5
3.71
3.60
A
12.00
5.40
778
A++
kWh
kW
kWh
kWh
FCQHG
mm
kg
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
71F
8.03
4.30
2,615
3.70
4.30
1,285
A/A
4.10
2,742
3.23
3.75
1,855
100F
125F
100F +
100L8Y1
9.5
10.8
2.57
2.51
A++
9.5
6.7
497
140F
288x840x840
100F
125F +
125L8Y1
12.0
13.5
3.71
3.60
A
12
5.4
778
A+
8.03
4.3
2,615
3.70
4.30
1,285
4.1
2,742
3.23
3.75
1,855
A/A
125F
140F + 140LY1
13.4
15.5
4.17
4.29
3.21
3.61
140F
25
26
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
130x950x950 / 130x950x950 / 50x950x950 / 50x950x950
10.3 / 10.3 / 5.4 / 5.4
Resin net with mold resistance
21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1
21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1
53
61
53
61
36/33/29
44/39/33
45/40/35
45/41/37
44/39/33
45/40/35
45/41/37
36/33/29
44/39/33
45/40/35
45/41/37
44/39/33
45/40/35
45/41/37
BRC7FA532F
BRC1D52 / BRC1E52A/B
1~ / 50 / 220-240
71L3V1
100L9V1
125L9V1
140L9V1
100L8Y1
125L8Y1
140LY1
Unit
HeightxWidthxDepth
1,430x940x320
990x940x320
1,430x940x320
770x900x320
990x940x320
Unit
67
72
74
95
82
101
Cooling
65
70
69
70
69
Nom./Silent operation
Cooling
49/47
53/54/53/54/53/Heating
Nom.
51
57
58
54
57
58
54
Night quiet mode
Level 1
49
Min.~Max.
Operation range
Cooling
Ambient
-15~46
Min.~Max.
Heating
Ambient
-15~15.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
Equivalent
m
System
70
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
15
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
32
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing. (3) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently
not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt. (4) BYCQ140D7W1: pure white standard panel with grey louvers; BYCQ140D7W1W: pure white
standard panel with white louvers; BYCQ140D7GW1: pure white auto cleaning panel.
28
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
7.60
4.15
2,563
3.50
4.10
970
9.50
6.70
497
A+
140F +
140L9V1
13.4
15.5
4.17
4.29
3.21
3.61
-
FCQHG-F + RZQG-L9V1/L(8)Y1
High COP, round flow cassette
360° air discharge for optimum efficiency and comfort
Indoor units
Combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FCQHG71-100-125-140F
RZQG100-125-140L9V1/L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
kW
kW
kW
kW
71F +
71L9V1
6.8
7.5
1.66
1.56
kW
6.80
FCQHG + RZQG
Nom.
Nom.
Cooling
Heating
Cooling
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Model
HeightxWidthxDepth
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
100F +
100L9V1
9.5
10.8
2.15
2.16
A++
9.50
125F +
125L9V1
12.0
13.5
3.00
3.07
12.00
6.61
636
7.00
kWh
kW
kWh
kWh
FCQHG
mm
kg
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
340
A+
7.60
4.54
2,344
4.09
4.80
830
71F
475
A++
11.30
4.80
3,296
4.42
4.99
1,075
A/A
12.66
4.63
3,829
4.00
4.40
1,500
100F
125F
140F +
140L9V1
13.4
15.5
4.00
3.77
3.35
4.12
-
BRC1E52A-B, BRC7FA532F
71F +
71L8Y1
6.8
7.5
1.66
1.56
100F +
100L8Y1
9.5
10.8
2.15
2.16
A++
9.5
6.8
125F +
125L8Y1
12.0
13.5
3.00
3.07
12
6.61
636
7
340
A+
7.6
4.54
2,344
4.09
4.80
830
475
A++
11.3
4.8
3,296
4.42
4.99
1,075
A/A
12.66
4.63
3,829
4.00
4.40
1,500
140F +
140LY1
13.4
15.5
4.00
3.77
3.35
4.12
-
140F
71F
100F
125F
140F
288x840x840
25
26
25
26
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter / BYCQ140D7GW1 - auto cleaning panel /
BYCQ140D7W1W - full white / BYCQ140D7W1 - white with grey louvers
Pure White (RAL 9010)
130x950x950 / 130x950x950 / 50x950x950 / 50x950x950
10.3 / 10.3 / 5.4 / 5.4
Resin net with mold resistance
21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1 21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1
21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1 21.2/16.7/12.2 32.3/25.7/19.0 33.5/26.7/19.9 33.5/27.3/21.1
53
61
53
61
53
61
53
61
36/33/29
44/39/33
45/40/35
45/41/37
36/33/29
44/39/33
45/40/35
45/41/37
36/33/29
44/39/33
45/40/35
45/41/37
36/33/29
44/39/33
45/40/35
45/41/37
BRC7FA532F
BRC1D52 / BRC1E52A/B
1~ / 50 / 220-240
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
RZQG
71L9V1
100L9V1
125L9V1
140L9V1
71L8Y1
100L8Y1
125L8Y1
140LY1
Unit
HeightxWidthxDepth
mm 990x940x320
1,430x940x320
990x940x320
1,430x940x320
Unit
kg
69
95
80
101
Cooling
dBA
64
66
67
69
64
66
67
69
Cooling
Nom.
dBA
48
50
51
52
48
50
51
52
Heating
Nom.
dBA
50
52
53
50
52
53
Night quiet mode
Level 1
dBA
43
45
43
45
Min.~Max.
°CDB
Operation range
Cooling
Ambient
-15~50
Min.~Max.
°CWB
Heating
Ambient
-20~15.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
75
50
75
Equivalent
m
System
70
90
70
90
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
25
40
20
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing. (3) The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently
not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt.
29
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
FCQG35-71F
WITH STANDARD PANEL
FCQG35-71F
with auto-cleaning panel
300 or less
See note 5
780 (suspension position)
860 - 910 (ceiling opening see note 3)
Drain side
Piping side
200mm
or more
(See note 3)
(See note 3)
2500 or more
(installation space)
Adjustable (0 - 675)
710 (suspension position)
860 - 910 (ceiling opening, see note 3)
5.
6.
1500mm or
more
200mm
1500mm or more
or more
REQUIRED SPACE
In case a discharge opening is closed with the “sealing member” option, the
distance of 1500mm can be reduced to 500mm on the closed side.
Hanging bolt
4 x M8 - M10
External
surfaceVentilator Other unit
light
VIEW A
1500 or more
2000 or more
4000 or more
1. Location of the nameplates
3.
4.
1500mm or
more
1500mm or
more
NOTE
2.
DETAIL C
2 PLACES
OPPOSITE SIDE
DETAIL B
2 PLACES
OPPOSITE SIDE
See note 6
- Unit body: on the control box cover
- Decoration panel: on the panel frame at the piping side under the corner cover
When installing an optional accessory, refer to the installation drawings.
- For fresh air intake kit an inspection part is necessary
Make sure the spacing between the ceiling and the cassette is no more than 35mm. Max ceiling opening: 910mm
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additional insulation
is required (polyethylene foam, thickness 10mm or more)
In case of using a sensor kit, this position will be a sensor, refer to the drawing of the sensor kit for more detail
In case of using a infrared control, this position will be a receiver, refer to the drawing of the infrared control for more detail
Item
1
2
3
4
5
6
7
8
9
10
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply entry hole
Transmission wiring entry hole
Air discharge opening
Air suction grille
Corner decoration cover
Drain hose
Knock out hole
Model
FCQG35-71FVEB, FXFQ20-63AVEB
2D090245A
FCQG100-140F
/ FCQHG-F WITH STANDARD PANEL
FCQG100-140F
with standard panel
300 or less
See note 5
780 (suspension position)
860 - 910 (ceiling opening see note 3)
Drain side
Piping side
See note 6
710 (suspension position)
860 - 910 (ceiling opening, see note 3)
200mm
or more
Hanging bolt
4 x M8 - M10
1500mm or
more
200mm
1500mm or more
or more
REQUIRED SPACE
In case a discharge opening is closed with the “sealing member” option, the
distance of 1500mm can be reduced to 500mm on the closed side.
External
surface Ventilator Other unit
light
1500 or more
2000 or more
4000 or more
VIEW A
NOTE
1. Location of the nameplates
- Unit body: on the control box cover
- Decoration panel: on the panel frame at the piping side under the corner cover
2. When installing an optional accessory, refer to the installation drawings.
- For fresh air intake kit an inspection part is necessary
3. Make sure the spacing between the ceiling and the cassette is no more than 35mm. Max ceiling opening: 910mm
4. When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additional insulation
is required (polyethylene foam, thickness 10mm or more)
5. In case of using a sensor kit, this position will be a sensor, refer to the drawing of the sensor kit for more detail
6. In case of using a infrared control, this position will be a receiver, refer to the drawing of the infrared control for more detail
30
1500mm or
more
1500mm or
more
Adjustable (0 - 675)
(See note 3)
2500 or more
(installation space)
(See note 3)
DETAIL C
2 PLACES
OPPOSITE SIDE
DETAIL B
2 PLACES
OPPOSITE SIDE
Item
1
2
3
4
5
6
7
8
9
10
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply entry hole
Transmission wiring entry hole
Air discharge opening
Air suction grille
Corner decoration cover
Drain hose
Knock out hole
Model
256
FCQG100-140FVEB, FXFQ80-100AVEB
298
FCQHG71-140FVEB, FXFQ125AVEB
3D077130E
Detailed technical drawings
Indoor units
FCQG35-71F WITH AUTO-CLEANING PANEL
FCQG100-140F / FCQHG-F WITH AUTO-CLEANING PANEL
31
Detailed technical drawings
FCQG35-71F
FCQG100-140F
32
ECPEN16-100.indd 32
20/05/16 16:07
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FCQHG-F
FCQG-F / FCQHG-F
33
ECPEN16-100.indd 33
20/05/16 16:07
ARGUE CARDS
FFQ-C / FXZQ-A
Fully Flat Cassette
Design & Genius in one
Why choose fully flat cassette
• Unique design in the market that integrates fully flat into the ceiling
• Advanced technology and top efficiency combined
• Most quiet cassette available on the market
Marketing tools
Visit the website: www.daikineurope.com/fullyflat
Unique design
Benefits for the installer
›› Unique product in the market!
›› Most quiet unit (25dBA)
›› The user-friendly remote control, available
in several languages, enables the easy set-up
of sensor option and control of the individual
flap position
›› Meeting European design taste.
Benefits for the consultant
›› Unique product in the market!
›› Blends seamlessly in any modern office
interior design
›› Ideal product to improve BREEAM score/EPBD
in combination with Sky Air Seasonal Smart
(FFQ-C) or VRV IV heat pump units (FXZQ-A).
Benefits for the end user
›› Engineering excellence and unique design
in one
›› Most quiet unit (25dBA)
›› Perfect working conditions:
no more cold draughts
›› Save up to 27% on your energy bill
thanks to the optional sensors
›› Flexible usage of space and suits any room
configuration thanks to individual
flap control
›› User-friendly remote control, available
in several languages.
›› Designed by a European design office to fully meet
the European taste.
›› Fully flat into the ceiling, leaving only 8mm.
›› Fully integrated in the one ceiling tile, enabling
lights, speakers and sprinklers to be installed in
adjoining ceiling tiles.
›› Decoration panel available in 2 colours
(white and white-silver).
Differentiating in technology
Optional presence sensor
›› When the room is empty, it can adjust the set
temperature or switch off the unit – saving energy.
›› When people are detected, the direction of
the airflow is adapted to avoid cold draughts being
directed towards occupants.
Optional floor sensor
›› Detects the temperature difference and
re-directs the airflow to ensure even
temperature distribution.
Top efficiency
*
++
›› Seasonal labels up to A
›› When the room is empty, the sensor option can
adjust the set temperature or switch off the unit –
saving up to 27% energy.
›› Individual flap control: easily control one or more
flaps via the wired remote controller (BRC1E52)
when rearranging the room. When fully closing or
blocking the flaps, the option “Sealing member of
air discharge outlet” is needed.
* for FFQ25,35C in combination with RXS25,35L3
Most quiet unit in the market
›› Most silent cassette in the market (25dBA),
important for office applications.
34
www.youtube.com/
DaikinEurope
FFQ-C + RXS-L3/L
Fully flat cassette
Combination with split outdoor units is ideal for small retail, offices or
­residential applications
›› Fully flat integration in standard architectural ceiling tiles, leaving only 8mm
›› Remarkable blend of iconic design and engineering excellence with an
elegant finish in white or a combination of silver and white
›› Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
›› Two optional intelligent sensors improve energy efficiency and comfort.
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system.
›› Branch duct discharge allows to optimize air distribution in irregular
shaped rooms or to supply air to small adjacent rooms
›› Reduced energy consumption thanks to specially developed small tube
heat exchanger, DC fan motor and drain pump
›› Standard drain pump with 675mm lift increases flexibility and installation
speed
Indoor units
Unique design in the market that integrates fully flat into
the ceiling
FFQ-C
RXS25-35L3
BRC1E52A-B, BRC7F530W_S white/grey panel, BRC7EB530 - standard panel
›› Fresh air intake integrated
in the same system thus
reducing installation
cost as no additional
ventilation is required
Fresh air intake opening in casing
Optional fresh air intake kit
* Brings in up to 10% of fresh air into the room
Branch discharge
Main unit
Main discharge
* Allows larger quantities of fresh air
to be bought in
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Min./Nom./Max.
Min./Nom./Max.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
Min./Nom./Max.
Min./Nom./Max.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
HeightxWidthxDepth
Unit
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
FFQ + RXS
kW
kW
kW
kW
kW
kWh
kW
kWh
kWh
25C + 25L3
1.4/2.50/4.0
1.3/3.20/5.1
0.360/0.551/1.470
0.300/0.820/1.650
35C + 35L3
1.4/3.4/4.0
1.3/4.20/5.1
0.360/0.899/1.470
0.300/1.200/1.650
50C + 50L
1.7/5.0/5.3
1.7/5.8/6.0
-/1.560/-/1.660/-
3.40
6.32
188
5.00
5.93
295
A
3.84
3.90
1,378
3.21
3.49
780
A/B
5.70
5.71
349
A+
3.96
4.04
1,373
3.02
3.41
945
B/B
50C
60C
A++
2.50
6.11
143
A+
A+
2.31
4.24
763
4.53
3.90
276
3.10
4.10
1,059
3.78
3.50
450
A/A
FFQ
mm
kg
mm
kg
m³/min
m³/min
dBA
dBA
dBA
Hz / V
25C
60C + 60L
1.7/5.7/6.5
1.7/7.0/8.0
-/1.890/-/2.050/-
35C
260x575x575
16
17.5
BYFQ60CW (white panel) / BYFQ60CS (grey panel) / BYFQ60B3W1 (standard panel)
White (N9.5) / White (N9.5) + Silver / White (RAL9010)
46x620x620 / 46x620x620 / 55x700x700
2.8 / 2.8 / 2.7
Resin net with mold resistance
9/8/6.5
10/8.5/6.5
12/10/7.5
14.5/12.5/9.5
9/8/6.5
10/8.5/6.5
12/10/7.5
14.5/12.5/9.5
48
51
56
60
31/28.5/25
34/30.5/25
39/34/27
43/40/32
31/28.5/25
34/30.5/25
39/34/27
43/40/32
BRC7F530W (white panel) / BRC7F530S (grey panel) / BRC7EB530 (standard panel)
BRC1D52 / BRC1E52A/B
1~ / 50 / 220-240
Outdoor unit
Dimensions
Weight
Sound power level
RXS
25L3
35L3
50L
60L
Unit
HeightxWidthxDepth
mm
550x765x285
735x825x300
Unit
kg
34
47
48
Cooling
dBA
59
61
62
Heating
dBA
59
61
62
Sound pressure level Cooling
High/Low/Silent operation
dBA
46/-/43
48/-/44
48/44/49/46/Heating
High/Low/Silent operation
dBA
47/-/44
48/-/45
48/45/49/46/Operation range
Cooling
Ambient
Min.~Max.
°CDB
-10~46
Heating
Ambient
Min.~Max.
°CWB
-15~18
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/1.0/2.1/2,087.5
R-410A/1.2/2.5/2,087.5
R-410A/1.7/3.5/2,087.5
R-410A/1.5/3.1/2,087.5
Piping connections
Liquid
OD
mm
6.35
Gas
OD
mm
9.5
12.7
Piping length
OU - IU
Max.
m
20
30
System
Chargeless
m
10
Additional refrigerant charge
kg/m
0.02 (for piping length exceeding 10m)
Level difference
IU - OU
Max.
m
15
20.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
1~ / 50 / 220-230-240
Current - 50Hz
Maximum fuse amps (MFA)
A
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
35
Detailed technical drawings
Find all technical drawings on our business portal http://my.daikin.eu
FFQ25-35C
FFQ25-35C
36
ECPEN16-100.indd 36
20/05/16 16:07
Indoor units
FULLY FLAT CASSETTE INTEGRATES
FULLY FLAT INTO THE CEILING
37
ACQ-D + AZQS-B(8)V1/BY1
4-way blow ceiling mounted
cassette
Solution addressing the primary needs of small shops
›› Ideal solution for busy retail and business environments and small
shops
›› Improved energy efficiency: up to A+ energy labels
›› Robust design and body quality
›› Easy installation and maintenance thanks to improved body structure
›› Exclusively offered for pair applications
›› Air can be discharged in any of 4 directions
›› Air filter removes airborne dust particles to ensure a steady supply of
clean air
›› Control several indoor units at the same time via the Siesta Sky Air
group control (optional)
›› Standard drain pump
›› Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation is required
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Decoration panel
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
HeightxWidthxDepth
Unit
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
High/Nom./Low/Silent operation
Fan - Air flow rate
Cooling
High/Nom./Low/Silent operation
Heating
Sound power level
Cooling
Heating
High/Nom./Low/Silent operation
Sound pressure level Cooling
High/Nom./Low/Silent operation
Heating
Control systems
Infrared remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
ACQ + AZQS
kW
kW
kW
kW
kW
kWh
kW
kWh
ACQ100-140D
AZQS100-140B(8)V1/BY1
71D + 71BV1
6.8
7.50
2.05
2.08
A+
6.80
5.70
418
6.33
4.00
2,216
3.31
100D + 100B8V1 125D + 125B8V1 140D + 140B8V1 100D + 100BY1
9.5
12.1
13.0
9.5
10.80
13.5
15.5
10.8
2.96
3.90
4.05
2.96
2.99
3.74
4.29
2.99
A
A
9.50
9.50
5.50
5.50
605
605
A
A
7.60
7.60
3.85
3.85
2,764
2,764
3.21
3.10
3.21
3.61
1,480
1,952
2,025
1,480
A/A
B/A
A/A
kWh
1,025
ACQ
mm
kg
71D
265x820x820
31
100D
mm
kg
m³/min 24.4/20.5/17.6/15.0 29.2/24.4/21.0/17.6
m³/min 24.4/20.5/17.6/15.0 29.2/24.4/21.0/17.6
dBA
54
56
dBA
54
56
dBA 41/38/35/32
44/41/38/36
dBA 41/38/35/32
44/41/38/36
Hz / V
125D
140D
100D
300x820x820
39
White
82x990x990
4
Removable / washable
34.0/29.2/26.3/22.1
29.2/24.4/21.0/17.6
34.0/29.2/26.3/22.1
29.2/24.4/21.0/17.6
60
56
60
56
47/44/43/41
44/41/38/36
47/44/43/41
44/41/38/36
ARCWLA
1~ / 50 / 220-240
125D + 125BY1
12.1
13.5
3.90
3.74
140D + 140BY1
13.0
15.5
4.05
4.29
-
3.10
3.21
1,952
B/A
2,025
-
125D
140D
34.0/29.2/26.3/22.1
34.0/29.2/26.3/22.1
60
60
47/44/43/41
47/44/43/41
71BV1
100B8V1
125B8V1
140B8V1
100BY1
125BY1
140BY1
1,430x940x320
990x940x320
1,430x940x320
Unit
HeightxWidthxDepth
770x900x320
990x940x320
Unit
67
72.8
74.3
94.9
82
101
Cooling
64
70
71
70
71
70
Cooling
Nom.
48
53
54
53
54
53
Heating
Nom.
50
57
58
54
57
58
54
Night quiet mode
Level 1
43
49
Min.~Max.
-5~46
Operation range
Cooling
Ambient
Min.~Max.
-15~15.5
Heating
Ambient
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
Equivalent
m
70
System
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
32
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
38
AZQS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
ARCWLA
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
ACQ71D
ACQ100/125/140D
39
FDBQ-B
Small concealed ceiling unit
Designed for hotel applications
›› Compact unit (230mm high & 652mm deep), can easily be
mounted in narrow ceiling voids
›› Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
›› Whisper quiet operation: down to 28dBA sound pressure level
›› Flexible installation, as the air suction direction can be altered
from rear to bottom suction
FDBQ-B
BRC1E52A/B
›› For easy mounting, the drain pan can be located to the left or
right of the unit
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Low
Heating
High/Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Low
Heating
High/Low
Control systems
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
FDBQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
25B
230x652x502
17.0
Resin net with mold resistance
6.50/5.20
6.95/5.20
55
55
35.0/28.0
35.0/29.0
BRC1D52 / BRC1E52A/B
1~ / 50 / 230
5MXS90E
Unit
HeightxWidthxDepth
mm
Unit
kg
Cooling
dBA
Cooling
Nom.
dBA
Heating
Nom.
dBA
Min.~Max.
°CDB
Operation range
Cooling
Ambient
Min.~Max.
°CWB
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
only available in multi model application
Piping connections
Liquid
OD
mm
Gas
OD
mm
Piping length
OU - IU
Max.
m
Additional refrigerant charge
kg/m
Level difference
IU - OU
Max.
m
IU - IU
Max.
m
Power supply
Phase / Frequency / Voltage
Hz / V
Current - 50Hz
Maximum fuse amps (MFA)
A
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
40
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FDBQ25B
FDBQ25B
41
FDXS-F(9) + RXS-L3/L
Concealed ceiling unit
Compact concealed ceiling unit, with a height of
only 200mm
›› Compact dimensions, can easily be mounted in a ceiling void of
only 240mm
FDXS25-35F
›› Medium external static pressure up to 40Pa facilitates unit use
with flexible ducts of varying lengths
›› Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
›› Low energy consumption thanks to DC fan motor
›› Optimised heating solution for your home
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Min./Nom./Max.
Min./Nom./Max.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Fan - External static pressure
Nom.
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
FDXS + RXS
kW
kW
kW
kW
kW
kWh
kW
kWh
kWh
FDXS
mm
kg
m³/min
m³/min
Pa
dBA
dBA
dBA
dBA
RXS25-35L3
25F + 25L3
1.3/2.4/3.0
1.3/3.2/4.5
0.641
0.800
A+
2.40
5.63
149
A+
2.60
4.24
858
3.74
4.00
321
A/A
BRC1E52A-B, BRC4C65
35F + 35L3
1.4/3.4/3.8
1.4/4.0/5.0
1.148
1.150
A
3.40
5.21
228
25F
2.90
3.88
1,047
2.96
3.48
574
B/A
50F9 + 50L
1.7/5.0/5.3
1.7/5.8/6.0
1.650
1.870
A+
5.00
5.72
306
A
4.00
3.93
1,425
3.03
3.10
825
B/D
35F
50F9
60F + 60L
1.7/6.0/6.5
1.7/7.0/8.0
2.060
2.180
A
6.00
5.51
381
4.60
3.80
1,693
2.91
3.21
1,030
C/C
60F
200x750x620
21
8.7/8.7/7.3
8.7/8.0/7.3
30
53
53
35/33/27
35/33/27
200x1,150x620
30
Removable / washable / mildew proof
12.0/11.0/10.0
16.0/16.0/13.5
16.0/14.8/13.5
40
55
55
56
56
38/36/30
38/36/30
BRC4C65
BRC1E52A/B
Hz / V
1~ / 50 / 230
1~ / 50 / 220-240
RXS
25L3
35L3
50L
60L
Unit
HeightxWidthxDepth
mm
550x765x285
735x825x300
Unit
kg
34
47
48
Cooling
dBA
59
61
62
Heating
dBA
59
61
62
High/Low/Silent operation
dBA
46/-/43
48/-/44
48/44
49/46/Sound pressure level Cooling
High/Low/Silent operation
dBA
47/-/44
48/-/45
48/45
49/46/Heating
Min.~Max.
°CDB
-10~46
Operation range
Cooling
Ambient
Min.~Max.
°CWB
-15~18
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/1.0/2.1/2,087.5
R-410A/1.2/2.5/2,087.5
R-410A/1.7/3.5/2,087.5
R-410A/1.5/3.1/2,087.5
Piping connections
Liquid
OD
mm
6.35
Gas
OD
mm
9.5
12.7
Piping length
OU - IU
Max.
m
20
30
Chargeless
m
10
System
Additional refrigerant charge
kg/m
0.02 (for piping length exceeding 10m)
Level difference
IU - OU
Max.
m
15
20.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
1~ / 50 / 220-230-240
Current - 50Hz
Maximum fuse amps (MFA)
A
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
42
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FDXS25-35F
FDXS50F9
43
ECPEN16-100.indd 43
20/05/16 16:07
Detailed technical drawings
FDXS60F
FDXS25-35F
44
ECPEN16-100.indd 44
20/05/16 16:07
Detailed technical drawings
Indoor units
FDXS50F9
FDXS60F
45
ECPEN16-100.indd 45
20/05/16 16:07
FBQ-D + RZQSG-L3/9V1/L(8)Y1
Concealed ceiling unit
with medium ESP
Slimmest yet most powerful medium static pressure unit
on the market
Combination with Seasonal Classic ensures good value for money for all
types of commercial applications
›› Top efficiency in the market! Energy label up to A++
›› Slimmest unit in class, only 245mm (300mm built-in height) and therefore
narrow ceiling voids are no longer a challenge
›› Lowest sound levels in the market: down to 25dBA!
›› Medium external static pressure up to 150Pa facilitates using flexible ducts
of varying lengths
›› Possibility to change ESP via wired remote control allows optimisation of
the supply air volume
›› Discretely concealed in the ceiling: only the suction and discharge grilles
are visible
›› Fresh air intake integrated in the same system thus reducing installation
cost as no additional ventilation is required
›› Reduced energy consumption thanks to specially developed DC fan motor
and drain pump
›› No optional adapter needed for DIII-connection, link your unit into the
wider building management system.
FBQ-D
RZQSG100-125L3/9V1/L(8)Y1
BRC1E52A-B, BRC4C65
›› Flexible installation: air suction direction can be altered from rear to
bottom suction and choice between free use or connection to optional
suction grilles
›› Standard built-in drain pump with 625mm lift increases increases flexibility
and installation speed
[~#//10.32.72.68/fs_mp1_exchange$/assets/Illustrations/AirConditioning/FXSQ-drainpump625mm.jpg#~]
For free use into a
false ceiling
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nominal efficiency
FBQ + RZQSG 71D + 71L3V1 100D + 100L9V1 125D + 125L9V1 140D + 140L9V1 100D + 100L8Y1 125D + 125L8Y1 140D + 140LY1
kW
6.8
9.5
12.0
13.4
9.5
12.0
13.4
kW
7.50
10.80
13.50
15.50
10.80
13.50
15.50
Nom.
kW
1.98
2.84
3.72
4.38
2.84
3.72
4.38
Nom.
kW
1.91
2.94
3.72
4.56
2.94
3.72
4.56
Energy label
A+
A
A+
A
Pdesign
kW
6.80
9.50
12.00
9.50
12.00
SEER
5.84
5.61
5.47
5.61
5.47
Annual energy consumption
kWh
408
593
768
593
768
Heating (Average Energy label
A+
A+
climate)
Pdesign
kW
6.00
7.60
7.60
SCOP
4.01
4.15
4.01
4.15
4.01
Annual energy consumption
kWh
2,095
2,564
2,653
2,564
2,653
EER
3.43
3.35
3.23
3.06
3.35
3.23
3.06
COP
3.92
3.67
3.63
3.40
3.67
3.63
3.40
Annual energy consumption
kWh
991
1,418
1,858
1,418
1,858
Energy label
Cooling/Heating
A/A
A/A
-
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Fan - External static pressure
High/Nom.
Sound power level
Cooling
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
For direct connection to
Daikin panel
(via EKBYBSD kit)
Nom.
Nom.
Cooling
Heating
Cooling
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
For connecting onto a
suction canvas
(not supplied by Daikin)
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom./Silent operation
Heating
Nom.
Night quiet mode
Level 1
Cooling
Ambient
Min.~Max.
Heating
Ambient
Min.~Max.
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
System
Equivalent
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
FBQ
mm
kg
m³/min
m³/min
Pa
dBA
dBA
dBA
71D
245x1,000x800
35
100D
18/15/12.5
18/15/12.5
150/30
56
30/28/25
31/28/25
29/26/23
29/26/23
150/40
58
34/32/30
36/33/30
125D
Hz / V
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
m
kg/m
m
Hz / V
A
71L3V1
770x900x320
67
65
49/47
51
-
R-410A/2.75/5.7/2,087.5
100L9V1
125L9V1
990x940x320
72
74
70
53/54/57
58
R-410A/2.9/6.1/2,087.5
15
20
140D
100D
245x1,400x800
46
Resin net with mold resistance
34/29/23.5
29/26/23
34/29/23.5
29/26/23
150/50
150/40
62
58
37/35/32
34/32/30
38/35/32
36/33/30
BRC4C65
BRC1E52A/B / BRC1D52
1~ / 50 / 220-240
1~ / 50 / 220-240
32
125D
140D
34/29/23.5
34/29/23.5
150/50
62
37/35/32
38/35/32
140L9V1
1,430x940x320
95
54
100L8Y1
125L8Y1
990x940x320
82
69
70
53/54/57
58
49
-15~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
R-410A/2.9/6.1/2,087.5
3N~ / 50 / 380-415
16
140LY1
1,430x940x320
101
69
53/54
R-410A/4.0/8.4/2,087.5
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
46
FBQ-D + RZQG-L9V1/L(8)Y1
Combination with Seasonal Smart ensures best in
class quality, highest efficiency and performance
Optimised supply air volume
External static pr essure (Pa)
Automatically selects the most appropriate fan curve to achieve the
units’ nominal air flow within ±10%
Indoor units
Fan characteristic
curves
Why?
After installation the real ducting will frequently differ from the
initially calculated air flow resistance  the real air flow may be
much lower or higher than nominal , leading to a lack of capacity or
uncomfortable air temperature
Duct resistance
curves
Automatic Airflow Adjustment function will adapt the unit’s fan
speed to any ducting automatically(10 or more fan curves are
­available on every model), making installation much faster
matic adjustment )
/min)
±
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Type
Cooling
Heating
High/Nom.
HeightxWidthxDepth
High/Nom./Low
High/Nom./Low
Fan - External static
pressure
Sound power level
Cooling
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
kWh
71D +
71L9V1
6.8
7.50
1.89
1.87
A++
6.80
6.16
386
A+
6.00
4.31
1,949
3.60
4.01
944
100D +
100L9V1
9.5
10.80
2.49
2.45
A+
9.50
5.87
566
A++
11.30
4.78
3,310
3.81
4.41
1,247
A/A
FBQ
mm
kg
71D
245x1,000x800
35
100D
m³/min
m³/min
Pa
18/15/12.5
18/15/12.5
29/26/23
29/26/23
150/30
150/40
150/50
56
30/28/25
31/28/25
58
34/32/30
36/33/30
62
37/35/32
38/35/32
71L9V1
990x940x320
69
64
48
50
43
100L9V1
FBQ + RZQG
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
kW
kW
kW
kW
kW
kWh
kW
kWh
dBA
dBA
dBA
Hz / V
RZQG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
R-410A/2.9/6.1/2,087.5
mm
mm
m
m
m
kg/m
m
Hz / V
A
50
70
20
125D +
125L9V1
12.0
13.50
3.63
3.46
A++
12.00
6.11
687
A+
12.70
4.28
4,154
3.31
3.90
1,813
140D +
140L9V1
13.4
15.50
4.00
4.31
3.35
3.60
-
71D +
71L8Y1
6.8
7.50
1.89
1.87
A++
6.80
6.16
386
A+
6.00
4.31
1,949
3.60
4.01
944
A/A
125D
140D
71D
245x1,400x800
245x1,000x800
46
35
Resin net with mold resistance
34/29/23.5
18/15/12.5
34/29/23.5
18/15/12.5
150/30
56
30/28/25
31/28/25
BRC4C65
BRC1E52A/B / BRC1D528
1~ / 50 / 220-240
125L9V1
140L9V1
71L8Y1
1,430x940x320
990x940x320
95
80
66
67
69
64
50
51
52
48
52
53
50
45
43
-15~50
-20~15.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
75
50
90
70
30
See installation manual
30.0
1~ / 50 / 220-240
32
20
100D +
100L8Y1
9.5
10.80
2.49
2.45
A+
9.50
5.87
566
A++
11.30
4.78
3,310
3.81
4.41
1,247
125D +
125L8Y1
12.0
13.50
3.63
3.46
A++
12.00
6.11
687
A+
12.70
4.28
4,154
3.31
3.90
1,813
140D +
140LY1
13.4
15.50
4.00
4.31
3.35
3.60
-
125D
245x1,400x800
46
140D
A/A
100D
29/26/23
29/26/23
34/29/23.5
34/29/23.5
150/40
150/50
58
34/32/30
36/33/30
62
37/35/32
38/35/32
100L8Y1
66
50
52
125L8Y1
140LY1
1,430x940x320
101
67
69
51
52
53
45
R-410A/4.0/8.4/2,087.5
75
90
3N~ / 50 / 380-415
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
47
FBQ-D + RXS-L3/L
Concealed ceiling unit
with medium ESP
Slimmest yet most powerful medium static pressure unit
on the market
Combination with split outdoor units is ideal for small retail, offices or
­residential applications
›› Top efficiency in the market! Energy label up to A++
›› Slimmest unit in class, only 245mm (300mm built-in height) and therefore
narrow ceiling voids are no longer a challenge
›› Lowest sound levels in the market: down to 25dBA!
›› Medium external static pressure up to 150Pa facilitates using flexible ducts
of varying lengths
›› Possibility to change ESP via wired remote control allows optimisation of
the supply air volume
›› Discretely concealed in the ceiling: only the suction and discharge grilles
are visible
›› Fresh air intake integrated in the same system thus reducing installation
cost as no additional ventilation is required
›› Reduced energy consumption thanks to specially developed DC fan motor
and drain pump
›› No optional adapter needed for DIII-connection, link your unit into the
wider building management system.
›› Flexible installation: air suction direction can be altered from rear to
bottom suction and choice between free use or connection to optional
suction grilles
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Type
Cooling
Heating
High/Nom.
HeightxWidthxDepth
High/Nom./Low
High/Nom./Low
Fan - External static
pressure
Sound power level
Cooling
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Unit
HeightxWidthxDepth
Unit
Cooling
Heating
Sound pressure level Cooling
High/Low/Silent operation
Heating
High/Low/Silent operation
Operation range
Cooling
Ambient
Min.~Max.
Heating
Ambient
Min.~Max.
Refrigerant
Type/Charge kg-TCO²Eq/GWP
Piping connections
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Power supply
Phase / Frequency / Voltage
Current - 50Hz
Maximum fuse amps (MFA)
FBQ + RXS
kW
kW
kW
kW
kW
kWh
kW
kWh
kWh
FBQ
mm
kg
FBQ-D
RXS35L3
›› Standard built-in drain pump with 625mm lift increases increases flexibility
and installation speed
For free use into a
false ceiling
For direct connection to
Daikin panel
(via EKBYBSD kit)
50D + 50L
5.0
5.50
1.42
1.44
60D + 60L
5.7
7.00
1.65
1.89
A+
5.70
5.86
340
A++
3.40
6.17
193
5.00
6.21
282
A+
4.40
4.06
1,517
3.52
3.83
710
A/A
2.90
4.07
998
3.99
4.02
426
35D
4.60
4.01
1,606
3.45
3.71
826
50D
245x700x800
28
Resin net with mold resistance
15/12.5/10.5
15/12.5/10.5
60D
245x1,000x800
35
18/15/12.5
18/15/12.5
150/30
dBA
dBA
dBA
60
35/32/29
37/34/29
56
30/28/25
31/28/25
BRC4C65
BRC1E52A/B / BRC1D52
1~ / 50 / 220-240
Hz / V
mm
mm
m
m
kg/m
m
Hz / V
A
For connecting onto a
suction canvas
(not supplied by Daikin)
35D + 35L3
3.4
4.00
0.85
1.00
m³/min
m³/min
Pa
RXS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
BRC1E52A-B, BRC4C65
35L3
550x765x285
34
61
61
48/-/44
48/-/45
R-410A/1.2/2.5/2,087.5
9.5
20
15
1~ / 50 / 220-240
16
50L
60L
735x825x300
47
48
62
62
48/44/48/45/-10~46
-15~18
R-410A/1.7/3.5/2,087.5
6.35
49/46/49/46/-
R-410A/1.5/3.1/2,087.5
12.7
30
10
0.02 (for piping length exceeding 10m)
20.0
1~ / 50 / 220-230-240
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
48
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FBQ35D
FBQ50D
49
Detailed technical drawings
FBQ60D
FBQ71D
50
Detailed technical drawings
Indoor units
FBQ100-140D
FBQ35-50D
51
Detailed technical drawings
FBQ60-71D
FBQ100D
52
Detailed technical drawings
Indoor units
FBQ125-140D
53
FDQ-C + RZQSG-L3/9V1/L(8)Y1, RZQG-L9V1/L(8)Y1
Concealed ceiling unit
with high ESP
ESP up to 200, ideal for large sized spaces
›› Seasonal Smart ensures the best in quality, highest efficiency and performance.
Seasonal Classic gives value for money.
›› Automatic air flow adjustment function measures the air volume and static pressure
and adjusts it towards the nominal air flow, whatever the length of duct, making
installation easier and guaranteeing comfort. Moreover, the ESP can be changed via
the wired remote control to optimize the supply air volume
›› High external static pressure up to 200Pa facilitates using flexible ducts of varying
lengths
›› Discretely concealed in the ceiling: only the suction and discharge grilles are visible
›› Reduced energy consumption thanks to specially developed DC fan motor
›› Possibility to change ESP via wired remote control allows optimisation of the supply air
volume
›› Flexible installation, as the air suction direction can be altered from rear to bottom
suction
›› Standard built-in drain pump increases flexibility and installation speed
›› No optional adapter needed for DIII-connection, link your unit into the wider
building management system.
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
FDQ + RZQG/RZQSG
kW
kW
kW
kW
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Unit
HeightxWidthxDepth
Required ceiling void >
Weight
Unit
Decoration panel
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Air filter
Type
Fan - Air flow rate
Cooling
High/Low
Heating
High/Low
Fan - External static pressure
High/Nom.
Sound power level
Cooling
Sound pressure level Cooling
High/Low
Heating
High/Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
kW
kWh
kW
kWh
kWh
FDQ
mm
mm
kg
mm
kg
m³/min
m³/min
Pa
dBA
dBA
dBA
Hz / V
FDQ125C
RZQSG125L3/9V1/L(8)Y1
Seasonal Smart
125C + 125L9V1
125C + 125L8Y1
12.0
13.5
3.20
3.53
A+
12.00
5.81
723
A+
12.71
4.21
4,227
3.75
3.83
1,600
A/A
BRC1E52A-B, BRC4C65
Seasonal Classic
125C + 125L9V1
125C + 125L8Y1
12.0
13.5
3.74
3.85
A
12.00
5.20
808
A
7.60
3.90
2,729
3.21
3.51
1,870
A/B
125C
300x1,400x700
350
45
BYBS125DJW1
White (10Y9/0.5)
55x1,500x500
6.5
Resin net with mold resistance
39/28
39/28
200/50
66
40/33
40/33
BRC4C65
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
RZQG/RZQSG
125L9V1
125L8Y1
125L9V1
125L8Y1
Unit
HeightxWidthxDepth
mm
1,430x940x320
990x940x320
Unit
kg
95
101
74
82
Cooling
dBA
67
70
Cooling
Nom.
dBA
51
54
Heating
Nom.
dBA
53
58
Night quiet mode
Level 1
dBA
45
49
Min.~Max.
°CDB
Operation range
Cooling
Ambient
-15~50
-15~46
Min.~Max.
°CWB
Heating
Ambient
-20~15.5
-15~15.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
75
50
Equivalent
m
System
90
70
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
32
16
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
54
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FDQ125C
FDQ125C
55
Detailed technical drawings
GNC
56
Detailed technical drawings
Indoor units
FDQ125C
FDQ125C
57
Detailed technical drawings
FDQ125C
58
FDQ-B + RZQ-C
Concealed ceiling unit with
high ESP
›› High external static pressure up to 250Pa facilitates using flexible
ducts of varying lengths
›› Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
›› Up to 26.4kW in heating mode
FDQ-B
RZQ200-250C
Efficiency data
Cooling capacity
Heating capacity
Power input
Nom.
Nom.
Cooling
Nom.
Heating
Nom.
Nominal efficiency (cooling EER
at 35°/27° nominal load,
COP
heating at 7°/20° nominal Annual energy consumption
load)
Energy label
Cooling/Heating
Indoor unit
Dimensions
Unit
HeightxWidthxDepth
Required ceiling void >
Weight
Unit
Air filter
Type
Fan - Air flow rate
Cooling
Nom.
Heating
Nom.
High/Nom./Low
Fan - External static
pressure
Sound power level
Cooling
Sound pressure level Cooling
High
Heating
Low
Control systems
Wired remote control
Power supply
Phase / Frequency / Voltage
FDQ + RZQ
kW
kW
kW
kW
kWh
Indoor units
ESP up to 250, ideal for extra large sized spaces
BRC1E52A-B
200B + 200C
20.0
23.0
6.23
6.74
3.21
3.41
3,115
250B + 250C
24.1
26.4
8.58
8.22
2.81
3.21
4,290
-
FDQ
mm
mm
kg
200B
250B
450x1,400x900
450
89.0
94.0
Resin net with mold resistance
m³/min
m³/min
Pa
69.0
69.0
dBA
dBA
dBA
81
45.0
45.0
Hz / V
89.0
89.0
250/250/250
82
47.0
47.0
BRC1D52 / BRC1E52A/B
1~ / 50 / 230
Outdoor unit
Dimensions
Weight
Sound power level
RZQ
200C
250C
Unit
HeightxWidthxDepth
mm
1,680x930x765
Unit
kg
183
184
Cooling
dBA
78
Heating
dBA
78
Sound pressure level
Nom.
dBA
57
Min.~Max.
°CDB
-5.0~46.0
Operation range
Cooling
Ambient
Min.~Max.
°CWB
-15.0~15.0
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/8.3/17.3/2,087.5
R-410A/9.3/19.4/2,087.5
Piping connections
Liquid
OD
mm
9.52
12.7
Gas
OD
mm
22.2
Piping length
OU - IU
Max.
m
100
Level difference
IU - OU
Max.
m
Power supply
Phase / Frequency / Voltage
Hz / V
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
59
Detailed technical drawings
FDQ200-250B / FDYP200-250B
FDQ-B
60
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FDQ200B7
FDQ200B7
61
ABQ-C + AZQS-B(8)V1/BY1
Concealed ceiling unit
Ideal for medium sized shops with false ceilings
›› Ideal solution for busy retail and business environments and small
shops
›› Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
›› Exclusively offered for pair applications
›› Air filter removes airborne dust particles to ensure a steady supply
of clean air
›› Easy installation and maintenance
›› Double protection drainage system ensures quality
ABQ100C
AZQS100-125B8V1/BY1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
ABQ + AZQS
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Fan - External static
pressure
Sound power level
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
Unit
Type
Cooling
Heating
High/Nom./Low
HeightxWidthxDepth
High/Nom./Low
High/Nom./Low
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
100C +
100B8V1
9.5
10.8
3.63
3.16
71C + 71BV1
kW
kW
kW
kW
6.8
7.5
2.33
2.13
kW
6.80
kWh
512
125C +
125B8V1
12.1
13.5
4.31
3.96
B
716
A
5.65
6.78
3.80
kWh
kWh
2,082
2.91
3.51
1,165
C/B
ABQ
mm
kg
71C
285x600x1,007
35
dBA
dBA
dBA
dBA
64
64
-
2,498
2.62
3.42
1,813
D/B
140C +
140B8V1
13.0
15.5
4.32
4.55
100C + 100BY1 125C + 125BY1 140C + 140BY1
9.5
10.8
3.63
3.16
B
9.50
4.65
716
A
6.78
3.80
2,498
2.62
3.42
1,813
D/B
-
9.50
4.65
kW
ARCWB
2.81
3.01
3.41
2,153
C/B
-
12.1
13.5
4.31
3.96
13.0
15.5
4.32
4.55
-
2.81
3.01
3.41
2,153
C/B
-
100C
125C
140C
100C
125C
140C
378x541x1,045 378x541x1,299 378x541x1,499 378x541x1,045 378x541x1,299 378x541x1,499
44
50
56
44
50
56
Saranet
m³/min 18.3/16.8/15.4 22.7/20.5/18.3 40.5/37.4/34.8 48.7/43.9/37.9 22.7/20.5/18.3 40.5/37.4/34.8 48.7/43.9/37.9
m³/min 18.3/16.8/15.4 22.7/20.5/18.3 40.5/37.4/34.8 48.7/43.9/37.9 22.7/20.5/18.3 40.5/37.4/34.8 48.7/43.9/37.9
Pa
90/77/64
70/57/45
150/128/111
150/122/92
70/57/45
150/128/111
150/122/92
60
60
41/38/36
41/38/36
53/52/50
53/52/50
Hz / V
AZQS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
m
kg/m
m
Hz / V
A
71BV1
770x900x320
67
64
48
50
43
100B8V1
125B8V1
990x940x320
72.8
74.3
70
71
53
54
57
58
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
20
1~ / 50 / 220-240
32
55/53/50
55/53/50
ARCWB
1~ / 50 / 220-240
140B8V1
1,430x940x320
94.9
70
53
54
49
-5~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
40
60
60
41/38/36
41/38/36
53/52/50
53/52/50
55/53/50
55/53/50
100BY1
125BY1
990x940x320
82
71
54
57
58
140BY1
1,430x940x320
101
70
53
54
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
16
3N~ / 50 / 380-415
20
25
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
62
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
ABQ71C
ABQ100-140C
63
Detailed technical drawings
ABQ71C
ABQ100C
ABQ125C
ABQ140C
ABQ125CV1 BLOWER PERFORMANCE CURVE
250
External Static Pressure (Pa)
200
SUPER HIGH
150
HIGH
MEDIUM
100
LOW
50
0
1000
2056-015
64
1200
1400
1600
Airflow (CFM)
1800
2000
Indoor units
WHERE CEILING SLOT DIFFUSER IS
USED IN SUSPENDED CEILING
65
FAQ-C + RZQSG-L3/9V1/L(8)Y1
Wall mounted unit
For rooms with no false ceilings nor free floor space
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
›› Optimum comfort guaranteed with automatic air-flow volume
control as this minimises the difference between room and
required temperature. No action required from occupants to
meet the desired temperature.
›› No optional adapter needed for DIII-connection, link your unit
into the wider building management system.
›› Flat, stylish front panel blends easily within any interior décor and
is easier to clean
›› Can easily be installed in both new and refurbishment projects
›› Reduced energy consumption thanks to specially developed DC
fan motor
›› The air is comfortably spread up- and downwards thanks to
5 different discharge angles that can be programmed via the
remote control
›› Maintenance operations can be performed easily from the front of
the unit
›› Easy to install as the largest casing only weighs 17kg and piping
connection can be done at the bottom, left or right of the unit
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
FAQ + RZQSG
kW
kW
kW
kW
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Nom./Silent operation
Cooling
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
71C + 71L3V1
6.8
7.5
2.12
2.08
100C + 100L9V1
100C + 100L8Y1
9.5
10.8
3.16
3.17
A+
kW
kWh
kW
kWh
kWh
FAQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
6.80
6.05
393
A
6.00
3.90
2,155
3.21
3.61
1,060
A/A
9.50
5.61
593
A+
6.81
4.01
2,378
3.01
3.41
1,580
B/B
71C
290x1,050x238
13
18/16/14
18/16/14
61
61
45/42/40
45/42/40
100C
340x1,200x240
17
26/23/19
26/23/19
65
65
49/45/41
49/45/41
BRC7EB518
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
Hz / V
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
71L3V1
770x900x320
67
65
49/47
51
-15.0~46
100L9V1
100L8Y1
990x940x320
72
70
82
69
53/57
49
-15~46
-15~15.5
R-410A/2.75/5.7/2,087.5
mm
mm
m
m
m
kg/m
m
Hz / V
A
15
20
R-410A/2.9/6.1/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
1~ / 50 / 220-240
3N~ / 50 / 380-415
32
16
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
66
FAQ-C + RZQG-L9V1/L(8)Y1
Wall mounted unit
For rooms with no false ceilings nor free floor space
Indoor units
›› Combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FAQ100C
RZQG100-125-140L9V1/L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
FAQ + RZQG
kW
kW
kW
kW
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
71C + 71L9V1
6.8
7.5
2.00
2.03
100C + 100L9V1
9.5
10.8
2.63
3.00
6.80
6.51
366
9.50
6.11
545
6.33
4.02
2,205
3.40
3.70
1,000
10.20
4.01
3,562
3.62
3.61
1,315
BRC1E52A-B
BRC7EB518
71C + 71L8Y1
6.8
7.5
2.00
2.03
100C + 100L8Y1
9.5
10.8
2.63
3.00
6.8
6.51
366
9.5
6.11
545
6.33
4.02
2,205
3.40
3.70
1,000
10.2
4.01
3,562
3.62
3.61
1,315
A++
kW
kWh
A+
kW
kWh
kWh
A/A
FAQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
71C
290x1,050x238
13
18/16/14
18/16/14
61
61
45/42/40
45/42/40
BRC7EB518
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
Hz / V
RZQG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
m
kg/m
m
Hz / V
A
100C
340x1,200x240
17
26/23/19
26/23/19
65
65
49/45/41
49/45/41
71L9V1
990x940x320
69
64
48
50
43
100L9V1
1,430x940x320
95
66
50
52
45
71L8Y1
990x940x320
80
64
48
50
43
100L8Y1
1,430x940x320
101
66
50
52
45
-15~50
-20~15.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
75
50
75
70
90
70
90
30
See installation manual
30.0
1~ / 50 / 220-240
3N~ / 50 / 380-415
20
32
20
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
67
Detailed technical drawings
FAQ71C
FAQ100C
68
Find all technical drawings on our business portal http://my.daikin.eu
FHQ-C + RXS-L3/L
Ceiling suspended unit
›› Ideal for comfortable air flow in wide rooms
thanks to Coanda effect: up to 100° discharge
angle
›› Even rooms with ceilings up to 3.8m can be
heated up or cooled down very easily without
capacity loss
›› Can easily be mounted in corners and narrow spaces, as it only
needs 30mm lateral service space
Indoor units
For wide rooms with no false ceilings nor free floor space
FHQ60C
Air outlet
Air inlet
30 or more
(Service space)
30 or more
(Service space)
Obstruction
›› Reduced energy consumption thanks to specially developed DC
fan motor and drain pump
›› Stylish unit blends easily with any interior. The flaps close entirely
when the unit is not operating and there are no air intake grilles
visible
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system.
›› Drain pump kit available as accessory
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Min./Nom./Max.
Min./Nom./Max.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Min./Nom./Max.
Min./Nom./Max.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
FHQ + RXS
kW
kW
kW
kW
kW
kWh
kW
kWh
kWh
FHQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
RXS35L3
BRC1E52A-B, BRC7G53
›› Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation device is required
35C + 35L3
1.4/3.40/4.0
1.3/4.00/5.1
0.410/0.950/1.490
0.270/0.980/1.980
A++
3.40
6.18
193
A+
3.10
4.43
981
3.58
4.08
475
A/A
50C + 50L
1.7/5.0/5.3
1.7/6.0/6.0
-/1.570/-/1.790/-
60C + 60L
1.7/5.7/5.7
1.7/7.20/7.2
-/1.750/-/2.170/A+
5.00
5.87
298
5.70
6.02
332
A
35C
4.35
3.86
1,578
3.18
3.35
785
B/C
4.71
3.87
1,705
3.26
3.32
875
A/C
50C
60C
235x1,270x690
31
235x960x690
24
14/11.5/10
14/11.5/10
53
53
36/34/31
36/34/31
25
Resin net with mold resistance
15/12/10
15/12/10
19.5/15/11.5
19.5/15/11.5
54
54
37/35/32
37/35/32
BRC7G53
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
37/35/33
37/35/33
Outdoor unit
Dimensions
Weight
Sound power level
RXS
35L3
50L
60L
Unit
HeightxWidthxDepth
mm
550x765x285
735x825x300
Unit
kg
34
47
48
Cooling
dBA
61
62
Heating
dBA
61
62
High/Low/Silent operation
dBA
48/-/44
48/44/49/46/Sound pressure level Cooling
High/Low/Silent operation
dBA
48/-/45
48/45/49/46/Heating
Min.~Max.
°CDB
-10~46
Operation range
Cooling
Ambient
Min.~Max.
°CWB
-15~18
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
R-410A/1.2/2.5/2,087.5
R-410A/1.7/3.5/2,087.5
R-410A/1.5/3.1/2,087.5
Piping connections
Liquid
OD
mm
6.35
Gas
OD
mm
9.5
12.7
Piping length
OU - IU
Max.
m
20
30
Chargeless
m
10
System
Additional refrigerant charge
kg/m
0.02 (for piping length exceeding 10m)
Level difference
IU - OU
Max.
m
15
20.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
1~ / 50 / 220-230-240
Current - 50Hz
Maximum fuse amps (MFA)
A
10
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
69
FHQ-C + RZQSG-L3/9V1/L(8)Y1
Ceiling suspended unit
For wide rooms with no false ceilings nor free floor space
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
›› Reduced energy consumption thanks to specially developed DC
fan motor and drain pump
›› Stylish unit blends easily with any interior. The flaps close entirely
when the unit is not operating and there are no air intake grilles
visible
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system.
›› Drain pump kit available as accessory
›› Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation device is required
›› Ideal for comfortable air flow in wide rooms thanks
to Coanda effect: up to 100° discharge angle
›› Even rooms with ceilings up to 3.8m can be
heated up or cooled down very easily without
capacity loss
›› Can easily be mounted in corners and narrow spaces, as it only
needs 30mm lateral service space
Air outlet
Air inlet
30 or more
(Service space)
30 or more
(Service space)
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Nom.
Nom.
Cooling
Heating
Cooling
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
100C +
100L9V1
9.5
10.8
2.96
2.99
A+
9.50
5.61
593
FHQ + RZQSG 71C + 71L3V1
Heating (Average
climate)
Nominal efficiency
Obstruction
kW
kW
kW
kW
6.8
7.5
1.97
1.88
kW
6.80
kWh
424
A
kW
kWh
kWh
7.60
3.91
2,722
3.21
3.61
1,480
3.90
2,727
3.46
4.00
985
A/A
FHQ
71C
mm 235x1,270x690
kg
32
m³/min
m³/min
dBA
dBA
dBA
dBA
Hz / V
20.5/17/14
20.5/17/14
55
55
38/36/34
38/36/34
100C
28/24/20
28/24/20
60
60
42/38/34
42/38/34
125C +
125L9V1
12.0
13.5
4.15
3.73
12.00
749
A+
4.01
2,654
2.89
3.62
2,075
C/A
125C
140C +
140L9V1
13.4
15.5
4.45
4.54
3.01
3.41
-
100C +
100L8Y1
9.5
10.8
2.96
2.99
125C +
125L8Y1
12.0
13.5
4.15
3.73
4.01
2,654
2.89
3.62
2,075
C/A
13.4
15.5
4.45
4.54
3.01
3.41
2,225
-
125C
140C
31/27/23
31/27/23
62
62
44/41/37
44/41/37
34/29/24
34/29/24
64
64
46/42/38
46/42/38
A+
9.5
12
5.61
593
A
749
A+
7.6
3.91
2,722
3.21
3.61
1,480
A/A
140C
100C
235x1,590x690
38
Resin net with mold resistance
31/27/23
34/29/24
28/24/20
31/27/23
34/29/24
28/24/20
62
64
60
62
64
60
44/41/37
46/42/38
42/38/34
44/41/37
46/42/38
42/38/34
BRC7G53
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
140C + 140LY1
RZQSG
71L3V1
100L9V1
125L9V1
140L9V1
100L8Y1
125L8Y1
140LY1
1,430x940x320
990x940x320
1,430x940x320
Unit
HeightxWidthxDepth
mm 770x900x320
990x940x320
Unit
kg
67
72
74
95
82
101
Cooling
dBA
65
70
69
70
69
Nom./Silent operation
dBA
49/47
53/54/53/54/53/Cooling
Heating
Nom.
dBA
51
57
58
54
57
58
54
Night quiet mode
Level 1
dBA
49
Min.~Max.
°CDB
-15~46
Operation range
Cooling
Ambient
Min.~Max.
°CWB
-15~15.5
Heating
Ambient
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
Refrigerant
Type/Charge kg-TCO²Eq/GWP
Piping connections
Liquid
OD
mm
9.52
Gas
OD
mm
15.9
Piping length
OU - IU
Max.
m
50
Equivalent
m
70
System
Chargeless
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU
Max.
m
15
30.0
Power supply
Phase / Frequency / Voltage
Hz / V
1~ / 50 / 220-240
3N~ / 50 / 380-415
Current - 50Hz
Maximum fuse amps (MFA)
A
20
32
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more detailed information
on each combination, please refer to the electrical data drawing.
70
FHQ-C + RZQG-L9V1/L(8)Y1
Ceiling suspended unit
For wide rooms with no false ceilings nor free floor space
Indoor units
For combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FHQ60-71C
RZQG100-125-140L9V1/L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
FHQ + RZQG
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
kW
kW
kW
kW
71C +
71L9V1
6.8
7.5
1.78
1.82
100C +
100L9V1
9.5
10.8
2.49
2.60
A++
kW
kWh
6.80
6.95
343
A+
7.60
4.32
2,463
3.82
4.13
890
9.50
6.11
545
A++
11.30
4.61
3,432
3.81
4.15
1,245
A/A
FHQ
mm
kg
71C
235x1,270x690
32
100C
m³/min
m³/min
dBA
dBA
dBA
dBA
20.5/17/14
20.5/17/14
55
55
38/36/34
38/36/34
28/24/20
28/24/20
60
60
42/38/34
42/38/34
71L9V1
990x940x320
69
64
48
50
43
100L9V1
kWh
kW
kWh
Hz / V
RZQG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
R-410A/2.9/6.1/2,087.5
mm
mm
m
m
m
kg/m
m
Hz / V
A
50
70
20
125C +
125L9V1
12.0
13.5
3.58
3.48
A+
12.00
6.01
699
A+
14.13
4.23
4,677
3.35
3.89
1,790
140C +
140L9V1
13.4
15.5
4.05
4.27
3.31
3.63
-
BRC1E52A-B, BRC7G53
71C +
71L8Y1
6.8
7.5
1.78
1.82
100C +
100L8Y1
9.5
10.8
2.49
2.60
125C +
125L8Y1
12.0
13.5
3.58
3.48
A+
12
6.01
699
A+
14.13
4.23
4,677
3.35
3.89
1,790
140C +
140LY1
13.4
15.5
4.05
4.27
3.31
3.63
-
100C
125C
235x1,590x690
38
140C
28/24/20
28/24/20
60
60
42/38/34
42/38/34
31/27/23
31/27/23
62
62
44/41/37
44/41/37
34/29/24
34/29/24
64
64
46/42/38
46/42/38
A++
6.8
6.95
343
A+
7.6
4.32
2,463
3.82
4.13
890
125C
140C
71C
235x1,590x690
235x1,270x690
38
32
Resin net with mold resistance
31/27/23
34/29/24
20.5/17/14
31/27/23
34/29/24
20.5/17/14
62
64
55
62
64
55
44/41/37
46/42/38
38/36/34
44/41/37
46/42/38
38/36/34
BRC7G53
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
125L9V1
140L9V1
71L8Y1
1,430x940x320
990x940x320
95
80
66
67
69
64
50
51
52
48
52
53
50
45
43
-15~50
-20~15.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
75
50
90
70
30
See installation manual
30.0
1~ / 50 / 220-240
32
20
9.5
6.11
545
A++
11.3
4.61
3,432
3.81
4.15
1,245
A/A
100L8Y1
66
50
52
125L8Y1
140LY1
1,430x940x320
101
67
69
51
52
53
45
R-410A/4.0/8.4/2,087.5
75
90
3N~ / 50 / 380-415
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
71
Detailed technical drawings
FHQ35C
FHQ50C
72
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FHQ60C
FHQ71C
73
Detailed technical drawings
FHQ100-140C
74
AHQ-C + AZQS-B(8)V1/BY1
Ceiling suspended unit
›› Ideal solution for commercial spaces with no or narrow false
ceilings
›› Exclusively offered for pair applications
›› Can easily be installed in both new and refurbishment projects
›› Air filter removes airborne dust particles to ensure a steady supply
of clean air
›› Decrease of temperature variation by automatic fan speed
selection or freely selectable 3-step fan speed.
›› Easy installation and maintenance
Indoor units
For wide rooms with no false ceilings nor free floor space
AHQ71C
AZQS71BV1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
AHQ + AZQS
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
100C +
100B8V1
9.5
10.8
3.62
3.17
71C + 71BV1
kW
kW
kW
kW
6.8
7.5
2.24
2.46
kW
kWh
6.80
4.65
511.85
kW
6.33
125C +
125B8V1
12.1
13.5
4.60
3.74
B
7.60
3.80
2,332.26
3.03
3.05
1,120
B/D
2,800
2.62
3.41
1,810
D/B
71C
260x1,320x634
38
100C
260x1,538x634
45
m³/min 23.8/21.3/18.9
m³/min 23.8/21.3/18.9
dBA
59
dBA
62
dBA
49/48/46
dBA
49/48/46
31.1/27.8/24.8
31.1/27.8/24.8
64
64
52/47/46
52/47/46
kWh
AHQ
mm
kg
Hz / V
AZQS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
m
kg/m
m
Hz / V
A
140C +
140B8V1
13.0
15.5
4.32
4.55
100C + 100BY1 125C + 125BY1 140C + 140BY1
9.5
10.8
3.62
3.17
B
9.50
4.60
723
A
7.60
3.80
2,800
2.62
-
9.50
4.60
723
A
kWh
ARCWLA
2.63
3.61
2,300
D/A
3.01
3.41
-
1,810
D/B
125C
140C
100C
260x1,786x634 285x1,902x680 260x1,538x634
54
70
45
Removable / washable
34.4/30.6/27.2 43.9/39.1/28.3 31.1/27.8/24.8
34.4/30.6/27.2 43.9/39.1/28.3 31.1/27.8/24.8
69
70
64
69
70
64
52/50/49
56/53/46
52/47/46
52/50/49
56/53/46
52/47/46
ARCWLA
ARCWB
1~ / 50 / 220-240
71BV1
770x900x320
67
64
48
50
43
100B8V1
125B8V1
990x940x320
72.8
74.3
70
71
53
54
57
58
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
20
1~ / 50 / 220-240
32
140B8V1
1,430x940x320
94.9
70
53
54
49
-5~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
12.1
13.5
4.60
3.74
13.0
15.5
4.32
4.55
-
2.63
3.61
2,300
D/A
3.01
3.41
-
125C
260x1,786x634
54
140C
285x1,902x680
70
34.4/30.6/27.2
34.4/30.6/27.2
69
69
52/50/49
52/50/49
43.9/39.1/28.3
43.9/39.1/28.3
70
70
56/53/46
56/53/46
100BY1
125BY1
990x940x320
82
71
54
57
58
140BY1
1,430x940x320
101
70
53
54
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
3N~ / 50 / 380-415
16
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
75
• Indoor Unit • AHQ-C
4 DetailedDimensional
Find all technical drawings on our business portal http://my.daikin.eu
technical drawings drawings
AHQ71-125C
• Indoor Unit • AHQ-C
4
Dimensional drawings
4
4
AHQ140C
• Split - Sky Air • AHQ-C
6
76
Indoor units
UNIQUE 4-WAY BLOW CEILING
SUSPENDED UNIT
77
FUQ-C + RZQSG-L3/9V1/RZQSG-L(8)Y1
4-way blow ceiling
suspended unit
Unique Daikin unit for high rooms with no false ceilings
nor free floor space
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
›› Even rooms with ceilings up to 3.5m can be heated up or cooled
down very easily without capacity loss
›› Ideal for solid ceilings
›› Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
›› 5 different discharge angles between
0 and 60°can be programmed via the
remote control
›› Stylish unit blends easily with any
interior. The flaps close entirely when the unit is not operating and
there are no air intake grilles visible
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
FUQ + RZQSG
kW
kW
kW
kW
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP/A
SCOPnet/A
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Low
Heating
High/Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Low
Heating
High/Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
Unit
Cooling
Cooling
Heating
Night quiet mode
Cooling
Heating
Type/Charge/GWP
Liquid
Gas
Piping length
HeightxWidthxDepth
Nom./Silent operation
Nom.
Level 1
Min.~Max.
Ambient
Min.~Max.
Ambient
OD
OD
OU - IU
System
Additional refrigerant charge
Level difference
IU - OU
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
Max.
Equivalent
Chargeless
Max.
EER/COP according to Eurovent 2012, for use outside EU only
78
›› Optimum comfort guaranteed with automatic air flow adjustment
to the required load
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system
›› Standard drain pump with 500mm lift increases flexibility and
installation speed
71C + 71L3V1
6.80
7.50
2.12
2.08
100C + 100L9V1
9.5
10.8
2.96
2.99
6.80
5.81
410
A
6.33
3.90
2,273
3.21
3.61
1,060
A/A
9.50
5.61
593
A+
125C + 125L9V1
12.0
13.5
4.53
3.95
A
12.00
5.30
793
A
4.01
4.02
2,654
3.21
3.61
A/A
1,480
3.85
3.86
2,764
2.65
3.41
D/B
2,265
4.01
4.02
2,654
3.21
3.61
1,480
A/A
3.85
3.86
2,764
2.65
3.41
2,265
D/B
71C
100C
125C
198x950x950
100C
125C
31/20
31/20
64
64
46/39
46/39
32.5/20.5
32.5/20.5
65
65
47/40
47/40
100L8Y1
125L8Y1
A+
kW
kWh
kW
kWh
kWh
FUQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
31/20
31/20
64
64
46/39
46/39
Hz / V
RZQSG
71L3V1
mm
770x900x320
kg
67
dBA
65
dBA
49/47
dBA
51
dBA
°CDB
-15.0~46
°CWB
kg/TCO₂eq R-410A/2.75/5.7/2,087.5
mm
mm
m
m
m
kg/m
m
15
Hz / V
A
20
125C + 125L8Y1
12.0
13.5
4.53
3.95
A
12.00
5.30
793
A
7.60
25
23/16
23/16
59
59
41/35
41/35
100C + 100L8Y1
9.5
10.8
2.96
2.99
A+
9.50
5.61
593
A+
26
Resin net with mold resistance
32.5/20.5
32.5/20.5
65
65
47/40
47/40
BRC7C58
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
100L9V1
125L9V1
990x940x320
72
74
82
70
53/57
69
53/57
54/58
70
54/58
49
-15~46
-15~15.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
1~ / 50 / 220-240
32
3N~ / 50 / 380-415
20
FUQ-C + RZQG-L9V1/L(8)Y1
4-way blow ceiling
suspended unit
Unique Daikin unit for high rooms with no false ceilings
nor free floor space
Indoor units
Combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FUQ-C
RZQG140L9V1//L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
FUQ + RZQG
kW
kW
kW
kW
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Cooling
Ambient
Min.~Max.
Heating
Ambient
Min.~Max.
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
System
Equivalent
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
kW
kWh
kW
kWh
kWh
71C + 71L9V1
6.8
7.5
1.68
1.84
6.80
6.50
367
100C + 100L9V1
9.5
10.8
2.46
2.73
A++
9.50
6.11
545
7.60
4.20
2,534
4.05
4.08
840
125C + 125L9V1
71C + 71L8Y1
100C + 100L8Y1
12.0
6.8
9.5
13.5
7.5
10.8
3.54
1.68
2.46
3.95
1.84
2.73
A+
A++
12.00
6.8
9.5
5.61
6.5
6.11
749
367
545
A+
14.13
7.6
11.3
4.44
4.2
4.5
4,456
2,534
3,516
3.39
4.05
3.86
3.42
4.08
3.95
1,770
840
1,230
A/B
A/A
11.30
4.50
3,516
3.86
3.95
1,230
A/A
FUQ
mm
kg
m³/min
m³/min
dBA
dBA
dBA
dBA
71C
25
23/19.5/16
23/19.5/16
59
59
41/38/35
41/38/35
71L9V1
990x940x320
69
64
48
50
43
R-410A/2.9/6.1/2,087.5
mm
mm
m
m
m
kg/m
m
Hz / V
A
100C
125C
71C
125C + 125L8Y1
12.0
13.5
3.54
3.95
A+
12
5.61
749
14.13
4.44
4,456
3.39
3.42
1,770
A/B
100C
125C
198x950x950
Hz / V
RZQG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
BRC1E52A-B, BRC7C58
50
70
20
26
31/25.5/20
31/25.5/20
64
64
46/42/39
46/42/39
25
Resin net with mold resistance
32.5/26.5/20.5
23/19.5/16
32.5/26.5/20.5
23/19.5/16
65
59
65
59
47/43/40
41/38/35
47/43/40
41/38/35
BRC7C58
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
100L9V1
125L9V1
1,430x940x320
95
66
67
50
51
52
53
45
71L8Y1
990x940x320
80
64
48
50
43
-15~50
-20~15.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
75
50
90
70
30
See installation manual
30.0
1~ / 50 / 220-240
32
20
26
31/25.5/20
31/25.5/20
64
64
46/42/39
46/42/39
32.5/26.5/20.5
32.5/26.5/20.5
65
65
47/43/40
47/43/40
100L8Y1
125L8Y1
1,430x940x320
101
66
67
50
51
52
53
45
R-410A/4.0/8.4/2,087.5
75
90
3N~ / 50 / 380-415
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
79
Detailed technical drawings
FUQ-C
80
Find all technical drawings on our business portal http://my.daikin.eu
FVQ-C + RZQSG-L3/9V1/L(8)Y1
Floor standing unit
For commercial spaces with high ceilings
›› Ideal solution for commercial and busy environments
›› Decrease of temperature variation by automatic fan speed
selection or freely selectable 3-step fan speed.
›› Improved comfort as a result of better airflow distribution from
the vertical out blow which allows manual adjustment of air outlet
blades at the top of the unit.
›› Selectable horizontal out blow to better suit the layout of the
room (via wired remote controller BRC1E52)
›› No optional adapter needed for DIII-connection, link your unit into
the wider building management system.
›› 140 class in range
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
FVQ + RZQSG 71C + 71L3V1
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Nom./Silent operation
Cooling
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
kW
kW
kW
kW
6.8
7.5
2.12
2.08
kW
6.80
kWh
kW
kWh
433
A
6.33
3.86
2,296
Side view blades air outlet
All up
100C +
100L9V1
9.5
10.8
2.96
2.99
A
9.50
5.50
605
A+
m³/min
m³/min
dBA
dBA
dBA
dBA
mm
mm
m
m
m
kg/m
m
Hz / V
A
12.00
764
A
3.85
2,764
2.81
1,480
2,135
A/B
71C
1,850x600x270
39
100C
125C
18/16/14
18/16/14
55
55
43/41/38
43/41/38
28/25/22
28/25/22
62
62
50/47/44
50/47/44
1,060
100C +
100L8Y1
9.5
10.8
2.96
2.99
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
15
1~ / 50 / 220-240
32
140C + 140LY1
13.4
15.5
4.45
4.54
3.01
A
12
5.5
605
A+
764
A
7.6
4.01
2,654
3.21
3.61
1,480
A/A
2,225
-
140C
100C
1,850x600x350
47
Resin net with mold resistance
28/26/24
30/28/26
28/25/22
28/26/24
30/28/26
28/25/22
63
65
62
63
65
62
51/48/46
53/51/48
50/47/44
51/48/46
53/51/48
50/47/44
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
100L9V1
125L9V1
990x940x320
72
74
70
53/54/57
58
125C +
125L8Y1
12.0
13.5
4.27
3.96
9.5
3.41
71L3V1
770x900x320
67
65
49/47
51
-15.0~46
20
140C +
140L9V1
13.4
15.5
4.45
4.54
3.01
7.60
Hz / V
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
Down
125C +
125L9V1
12.0
13.5
4.27
3.96
4.01
2,654
A/A
FVQ
mm
kg
Up
All down
3.21
3.61
kWh
Indoor units
Combination with Seasonal Classic ensures good value for money
for all types of commercial applications
3.85
2,764
2.81
3.41
2,135
C/B
2,225
-
125C
140C
28/26/24
28/26/24
63
63
51/48/46
51/48/46
30/28/26
30/28/26
65
65
53/51/48
53/51/48
140L9V1
1,430x940x320
95
54
100L8Y1
125L8Y1
990x940x320
82
69
70
53/54/57
58
49
-15~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
R-410A/2.9/6.1/2,087.5
3N~ / 50 / 380-415
16
140LY1
1,430x940x320
101
69
53/54
R-410A/4.0/8.4/2,087.5
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
81
FVQ-C + RZQG-L9V1/L(8)Y1
Floor standing unit
For commercial spaces with high ceilings
Combination with Seasonal Smart ensures best in class quality,
highest efficiency and performance
FVQ71C
RZQG100-125-140L9V1/L(8)Y1
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
FVQ + RZQG
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Sound power level
Cooling
Heating
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
kW
kW
kW
kW
kW
kWh
71C +
71L9V1
6.8
7.5
2.02
2.06
A++
6.80
6.31
378
100C +
100L9V1
9.5
10.8
2.49
2.61
125C +
125L9V1
12.0
13.5
3.74
3.65
A+
9.50
12.00
5.61
593
749
A
A+
kW
kWh
kWh
6.33
4.05
2,189
3.37
3.64
1,010
FVQ
71C
mm 1,850x600x270
kg
39
m³/min
m³/min
dBA
dBA
dBA
dBA
140C +
140L9V1
13.4
15.5
4.17
4.30
-
18/16/14
18/16/14
55
55
43/41/38
43/41/38
11.30
4.20
3,767
3.81
4.14
1,245
A/A
100C
28/25/22
28/25/22
62
62
50/47/44
50/47/44
Hz / V
RZQG
71L9V1
mm 990x940x320
kg
69
dBA
64
dBA
48
dBA
50
dBA
43
°CDB
°CWB
R-410A/2.9/6.1/2,087.5
mm
mm
m
50
m
70
m
kg/m
m
Hz / V
A
20
100L9V1
3.87
4,088
3.21
3.70
1,870
3.61
2,085
-
BRC1E52A-B
71C +
71L8Y1
6.8
7.5
2.02
2.06
A++
6.8
6.31
378
100C +
100L8Y1
9.5
10.8
2.49
2.61
125C +
125L8Y1
12.0
13.5
3.74
3.65
140C +
140LY1
13.4
15.5
4.17
4.30
-
A+
9.5
12
5.61
593
749
A
A+
6.33
4.05
2,189
3.37
3.64
1,010
125C
140C
71C
1,850x600x350
1,850x600x270
47
39
Resin net with mold resistance
28/26/24
30/28/26
18/16/14
28/26/24
30/28/26
18/16/14
63
65
55
63
65
55
51/48/46
53/51/48
43/41/38
51/48/46
53/51/48
43/41/38
BRC1D52 / BRC1E52A/B
1~ / 50/60 / 220-240/220
125L9V1
140L9V1
71L8Y1
1,430x940x320
990x940x320
95
80
66
67
69
64
50
51
52
48
52
53
50
45
43
-15~50
-20~15.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
75
50
90
70
30
See installation manual
30.0
1~ / 50 / 220-240
32
20
11.3
4.2
3,767
3.81
4.14
1,245
A/A
3.87
4,088
3.21
3.70
1,870
3.61
2,085
-
100C
125C
1,850x600x350
47
140C
28/25/22
28/25/22
62
62
50/47/44
50/47/44
28/26/24
28/26/24
63
63
51/48/46
51/48/46
30/28/26
30/28/26
65
65
53/51/48
53/51/48
100L8Y1
66
50
52
125L8Y1
140LY1
1,430x940x320
101
67
69
51
52
53
45
R-410A/4.0/8.4/2,087.5
75
90
3N~ / 50 / 380-415
32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information
on each combination, please refer to the electrical data drawing.
82
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FVQ71C
FVQ100-125-140C
83
FNQ-A + RXS-L3/L
Concealed floor standing unit
Designed to be concealed in walls
›› Ideal for installation in offices, hotels and residential applications
›› Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
›› Its low height (620 mm) enables the unit to fit perfectly beneath a
window
›› Requires very little installation space
as the depth is only 200 mm
FNQ-A
RXS35L3
BRC1E52A-B, BRC4C65
›› High ESP allows flexible installation
Efficiency data
Cooling capacity
Heating capacity
Power input
Seasonal efficiency
(according to
EN14825)
Nom.
Nom.
Cooling
Heating
Cooling
Heating (Average
climate)
Nominal efficiency
Nom.
Nom.
Energy label
Pdesign
SEER
Annual energy consumption
Energy label
Pdesign
SCOP
Annual energy consumption
EER
COP
Annual energy consumption
Energy label
Cooling/Heating
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
HeightxWidthxDepth
Unit
Type
Cooling
High/Nom./Low
Heating
High/Nom./Low
Fan - External static pressure
High/Nom.
Sound power level
Cooling
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Control systems
Infrared remote control
Wired remote control
Power supply
Phase / Frequency / Voltage
Outdoor unit
Dimensions
Weight
Sound power level
Unit
HeightxWidthxDepth
Unit
Cooling
Heating
High/Low/Silent operation
Sound pressure level Cooling
High/Low/Silent operation
Heating
Min.~Max.
Operation range
Cooling
Ambient
Min.~Max.
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
Piping connections
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Chargeless
System
Additional refrigerant charge
Level difference
IU - OU
Max.
Power supply
Phase / Frequency / Voltage
Current - 50Hz
Maximum fuse amps (MFA)
FNQ + RXS
kW
kW
kW
kW
kW
kWh
25A + 25L3
2.6
3.20
0.69
0.80
2.60
5.63
162
35A + 35L3
3.4
4.00
1.11
1.15
A+
3.40
5.65
211
2.80
4.24
925
3.77
4.00
345
A/A
50A + 50L
5.0
5.80
1.49
1.74
5.00
5.72
306
60A + 60L
6.0
7.00
2.24
2.25
A
6.00
5.51
381
2.90
4.05
1,002
3.06
3.48
556
B/B
4.00
4.09
1,369
3.35
3.34
746
A/C
4.60
4.16
1,548
2.68
3.11
1,119
D/D
35A
50A
A+
kW
kWh
kWh
FNQ
mm
kg
25A
60A
720 (2)x750x200
23
720 (2)x1,150x200
30
Resin net with mold resistance
m³/min
m³/min
Pa
dBA
dBA
dBA
8.7/8/7.3
8.7/8/7.3
48/30
53
33/31/28
33/31/28
BRC4C65
BRC1E52A/B / BRC1D52
1~ / 50/60 / 220-240/220
Hz / V
RXS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
25L3
35L3
550x765x285
34
59
59
46/-/43
47/-/44
50L
60L
735x825x300
47
61
61
48/-/44
48/-/45
48
62
62
48/44/48/45/-
49/46/49/46/-
-10~46
-15~18
R-410A/1.2/2.5/2,087.5
R-410A/1.7/3.5/2,087.5
6.35
R-410A/1.0/2.1/2,087.5
mm
mm
m
m
kg/m
m
Hz / V
A
16.0/14.8/13.5
16.0/14.8/13.5
49/40
56
36/33/30
36/33/30
9.5
20
R-410A/1.5/3.1/2,087.5
12.7
30
10
0.02 (for piping length exceeding 10m)
15
1~ / 50 / 220-240
16
20.0
1~ / 50 / 220-230-240
20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) Dimensions indoor unit include installation legs (3) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth
leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
84
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Indoor units
FNQ25-35A
Detailed technical drawings
FNQ50-60A
85
Detailed technical drawings
FNQ25-35A
FNQ50A
86
Detailed technical drawings
Indoor units
FNQ60A
87
SEASONAL SMART
SEASONAL CLASSIC
SUPER INVERTER
88
Outdoor
units
Products overview Benefits overview
Sky Air pair twin, triple,
double twin application
Outdoor Unit
A range of industry
leading technology
outdoor units
90
92
106
Pair solution
RZAG-LV1
106
RZQG-L9V1/L(8)Y1107
RZQSG-L3/L9V1122
RZQ-C131
AZQSB8V1/BY1136
Multi model and VRV application 141
MXS142
RXYSCQ-TV1152
RXYSQ-TV1/TY1153
SB.RKXYQ-T 159
Twin, triple, double twin solution
Benefits for the installer
›› Less piping required as all the indoor units can be
connected to one single outdoor unit.
Benefits for the consultant
›› Ideal solution for long or irregularly shaped rooms
›› Up to 4 indoor units can be connected to a single
outdoor unit
›› The air flow is evenly spread into the area, as smaller
indoor units are installed in different locations
around the room
Multi solution
Benefits for the end user
›› All the indoor units are controlled at the same time
and by using a single wired remote controller
›› Only 1 outdoor unit on a roof, terrace or against
an outside wall to control up to 4 indoor units
›› Same comfortable feeling throughout
the entire room
89
Outdoor units
Products overview outdoor units
Pair, twin, triple & double twin application
System Type
Model
Seasonal Smart
--Industry leading technology extended with R-32 range
--68% lower GWP compared to R-410A products
--10% lower refrigerant charge compared to R-410A
--Minimum 5% more efficient in cooling than R-410A
--Quiet mode: set via the remote control for example during
night time, ...
- Re-use technology
- Operation range down to -20°C in heating and -15°C in cooling
- Variable Refrigerant Temperature
Air
cooled
Seasonal Smart
--Industry leading technology for commercial applications
--Dedicated solution for infrastructure cooling
--Variable Refrigerant Temperature
--Maximum piping length up to 75m
--Re-use technology
--Extended operation range down to -20°C in heating and
-15°C in cooling
--Pair, twin, triple and double twin application
PG
RZAG-LV1
71
100
125
140
200
250
6.8 kW
9.5 kW
12.0 kW
13.4 kW
20.0 kW
24.1 kW
•
•
•
•
•
•
NEW
106
RZQG-L9V1
107
•
•
•
•
RZQG-L(8)Y1
107
•
•
•
•
RZQSG-L3/
L9V1
122
•
•
•
•
RZQSG-L(8)Y1
122
•
•
•
RZQ-C
131
AZQS-B8V1
136
AZQS-BY1
136
Heat
pump Seasonal Classic
--Technology and comfort combined for commercial
applications
--Maximum piping length up to 50m
--Re-use technology
--Operation range down to -15°C
both cooling and in heating
--Pair, twin, triple and double twin application
Capacity class
Product name
Super Inverter
--Packaged system for commercial applications
--For large commercial applications
--Re-use technology
--Pair, twin, triple and double twin applications
Standard outdoor unit
--Ideal solution for busy environments and small shops
--Easy-to-mount outdoor units: roof, terrace or wall
--Outdoor units with swing or scroll compressor
--Exclusively offered for pair applications
•
•
•
•
•
•
•
Multi model and VRV application
System Type
Model
Productname
PG 40
50
52
68
80
Capacity class
90 4HP 5HP 6HP 8HP 10HP 12HP
4.0kW 5.0kW 5.2kW 6.8kW 8.0kW 9.0kW 12.1kW 14.0kW 15.5kW 22.4kW 28.0kW 33.5kW
Multi model application
--Up to 5 indoor units can be connected to a single outdoor unit
--Individual control of the indoor units
--Different types of indoor units can be combined in one installation
--Phased installation possible
--Maximum total piping length of 25m offers solution for light commercial
or residential applications
2MXS-H
143
3MXS-K
3MXS-E
3MXS-G
144
144
145
4MXS-F
146
4MXS-E
147
5MXS-E
147
 






The most compact VRV
›› Compact and lightweight single fan design saves space and is easy to
install
›› Covers all thermal needs of a building via
Air
Heat
cooled pump
a single point of contact: accurate temperature control, ventilation, air
handling units and Biddle air curtains
›› Either connect VRV of stylish indoor units
(Daikin Emura, Nexura)
›› Incorporates VRV IV standards & technologies such as Variable Refrigerant
temperature
Space saving solution
without compromising on efficiency
›› Space saving trunk design for flexible installation
›› Covers all thermal needs of a building via
a single point of contact: accurate temperature control, ventilation,
air handling units and Biddle air curtains
›› Either connect VRV of stylish indoor units (Daikin Emura, Nexura)
›› Incorporates VRV IV standards & technologies
such as Variable Refrigerant temperature
RXYSCQ-TV1
Compact
152
 
TV1 153
  
TY1 153
   
RXYSQ-TV1/TY1
The invisible VRV
›› Unique VRV heat pump for indoor installation
›› Total flexibility for any shop location and building type as the outdoor unit
such as Variable Refrigerant temperature
›› Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation and Biddle air curtains
90
SB.RKXYQ-T*
159

 2nd half 2016
is invisible and split up in 2 parts
›› Incorporates VRV IV standards & technologies


Outdoor units
RZQG-L9V1/
L(8)Y1-
RZQSGL3/9V1/L(8)Y1
RZQ-C
AZQSB8V1/BY1
MXS-E/F/
G/H/K
RXYSCQ-TV1
RXYSQ-TV1/
TY1
SB.RKXYQ
Seasonal efficiency Smart use of energy
Seasonal efficiency gives a more realistic indication on how
efficient air conditioners operate over an entire heating or
cooling season.






Inverter technology
In combination with inverter controlled outdoor units









Replacement
technology
Service and maintenance with R-22 is prohibited after
1/01/2015, meaning repairs will be impossible to R-22 systems.
Avoid unexpected downtime for your customers and replace
these systems now!





Night quiet
Lowers the operation sound of the outdoor unit automatically.
Auto cooling-heating
changeover
Automatically selects cooling or heating mode to achieve the
set temperature.














Variable refrigeration
temperature
The intelligent systems ensures highest energy savings with
additional comfort to better suit application requirements.





Twin/triple/double
twin application
2, 3 or 4 indoor units can be connected to only 1 outdoor unit
even if they have different capacities. All indoor units operate
within the same mode (cooling or heating) from one remote
control.
Multi model application
Up to 5 indoor units (even different capacities) can be
connected to a single outdoor unit. All indoor units can
individually be operated within the same mode.
VRV for residential
application
Up to 9 indoor units (even different capacities and up to 71
class) can be connected to a single outdoor unit. All indoor
units can individually be operated within the same mode.



Swing compressor
Outdoor units are fitted with a swing compressor, renowned
for its low noise and high reliability
Scroll compressor
Outdoor units are fitted with a scroll compressor, renowned for
its low noise and high energy efficiency
Guaranteed operation
down to -20°C
Daikin is suitable for all climates, even withstanding severe
winter conditions with an operation range down to -20°C.






Infrastructure cooling
For high sensible, infrastructure cooling applications,
dedicated infrastructure cooling settings and allowing
asymmetric combinations enhance the system’s reliability.




Outdoor Unit
RZAG-LV1
Other functions
Comfort
We care icons
Benefits overview outdoor units











91
Outdoor units
Sky air outdoor units meet customers' every need for light
commercial applications, from high specification, tailored solutions
to primary needs for cooling and heating
Seasonal Smart
R-32
Seasonal Smart
Seasonal Classic
Super inverter
›› Industry-leading technology
extended with R-32 products
›› Lowest environmental impact
with R-32 refrigerant
›› 10% lower refrigerant charge
›› Minimum 5% more efficient in
cooling compared to R-410A
units
›› For all types of commercial
applications, including
infrastructure cooling
›› Best efficiency!
›› Most flexible installation
›› Widest range of connectable
indoor units
›› For all types of commercial
applications
›› Good value for money:
very efficient and comfortable
indoor units
›› Packaged system
for large commercial
applications
Cooling / Heating
Up to A++ / Up to A++
Seasonal
efficiency
Max. piping lenght
between indoor and outdoor
Operation
range
Cooling / Heating
Up to A++ / Up to A++
Cooling / Heating
Up to A++ / Up to A+
Up to 75m
Up to 50m
Cooling
-15°C ~ 50°C
-15°C ~ 46°C
Heating
-20°C ~ 15.5°C
N/A
Up to 100m
-5°C ~ 46°C
-15°C ~ 15°C
Infrastructure cooling
1.
2. Customizable
Floor standing unit
Connectable indoor units
High COP round
flow cassette
(High) Round flow
cassette
Ceiling
suspended unit
Fully flat cassette
Pair application
Twin/triple/double twin
Multi (max. number
of connectable units)
92
Concealed floor
standing unit
Wall
mounted unit
4-Way blow ceiling
suspended cassette
Concealed
ceiling unit
Siesta Sky Air
Multi model
VRV IV S-series
VRV IV i-series
›› Basic cooling/
heating ­solution
for small shops
›› Individual control
of the indoor units
›› Phased installation possible
›› Compact and lightweight
single fan design saves space and is
easy to install
›› Covers all thermal needs
of a building
›› Incorporates VRV IV standards
& technologies such as Variable
Refrigerant temperature
›› Unique VRV
for indoor installation
›› Covers all thermal needs
of a building
›› Incorporates VRV IV standards
& technologies such as Variable
Refrigerant temperature
Cooling / Heating
Up to A / Up to A
N/A
N/A
N/A
Up to 25m
Up to 50m (30m for RXYSCQ)
Up to 90m
-15°C ~ 46°C
10°C ~ 46°C
-5°C ~ 46°C (up to 52°C for 8/10/12)
-5°C ~ 46°C
-15°C ~ 15°C
-15°C ~ 18°C
-20°C ~ 15,5°C
-20°C ~ 15,5°C
Up to 50m
4-Way blow ceiling
suspended cassette
Daikin Emura
Daikin Nexura
Fully flat cassette
Round flow
cassette
Wall
mounted unit
Flexi type
Outdoor Unit
Outdoor units
Only VRV indoors
Concealed ceiling unit
Ceiling suspended unit
Concealed
ceiling unit
(5)
Ceiling
suspended unit
(9)
(only VRV indoor)
93
Outdoor units
Maximum efficiency and comfort
Inverter control
Daikin’s inverter technology is a true innovation
in the field of climate control. The principle is
simple: inverters adjust the power used to suit
the actual requirement - no more, no less! This
technology provides two clear benefits:
›› Comfort: The inverter repays its investment
many times over by improving comfort. An
air conditioning system with an inverter
continuously adjusts its cooling and heating
output to suit the temperature in the room, thus
improving comfort levels. The inverter reduces
system start-up time, so the required room
temperature is reached more quickly. As soon as
the correct temperature is reached, the inverter
ensures that it is constantly maintained.
›› Energy efficient: Because an inverter monitors
and adjusts the ambient temperature whenever
needed, energy consumption drops by 30%
compared with a traditional on/off system.
Temperature / Power input
Temperature remains stable
Air
conditioning
without
Inverter
Slow start
Air conditioning
with Inverter
Set temp.
Time
Variable refrigerant
temperature
1.
Operates with variable refrigerant temperature:
all Daikin Sky Air outdoor units are able to adapt their
operation to meet your unique cooling and heating
requirements, without comprimising efficiency.
Tin
30°C
Tin /
Tset
Big gap
Tin
28°C
Default
Te
Customised
Te max
Te
Tin
26°C
Smaller gap
Higher Te
Low Te
2. Go one step further in improving comfort and efficiency
by having the possibility to customize the settings at
time of installation. These special settings allow the
boundaries of fluctuation of refrigerant’s evaporating
and condensing temperature to be customized to fit the
application.
Te max
Te min
Tset = 22°C
Time
Te
Cooling
Ta
Winter
Heating
Default
Tc
Autumn
Spring
Te min
Customised
Tc max
Tc
Summer
Tc min
Ta
Winter
Autumn
Tc max
Spring
Tin = indoor temperature / Tset = setpoint / Te = evaporating temperature of refrigerant
Tc = condensing temperature of refrigerant / Ta = ambient temperature
Tc min
Summer
94
Ta
Ta
Outdoor units
Replacement technology
The quick and quality way of upgrading
R-22 and R-407C systems
Less installation time
Tackle more projects in less time thanks to faster
installation. It is more profitable than replacing the
full system with new piping.
The benefits will convice your customer
To prevent unexpected breakdown
Outdoor Unit
VRV-Q benefits
to increase your profit
Optimise your business
To lower running costs
To protect the environment
To improve comfort
Lower installation costs
Reducing installation costs enables you to offer
customers the most cost-effective solution and
improve your competitive edge.
Replace non-Daikin systems
It is a trouble-free replacement solution for
Daikin systems and for systems made by other
manufacturers.
Easy as one-two-three
A simple solution for replacement technology
enables you to handle more projects for more
customers in less time and offer them the best price!
Everybody gains.
Your copper pipes will last for multiple generations
- copper pipes used in air conditioning systems tested by Daikin will last over 60 years after installation.
- Japan/China have replaced with VRV Q-series
already 10 years ago!
Umeda Center Building, Japan
- original A/C system: 20 years in use
- replacement with VRV Q-series:
2006 - 2009
- capacity up from 1620HP to 2322HP
- SHASE renewal award:
2013
(1st)
How does it work?
The Daikin low-cost upgrade solution
!
Replace indoor units and BS boxes
!
Replace outdoor units
Contact your local dealer to check compatibility in
case you need to keep the indoor units.
Learn more about Daikin replacement solutions at www.daikineurope.com/minisite/r22
95
Outdoor units
Replacement technology
Procedure for Split / Sky Air
Re-use of the existing pipe work
No
Check the specification of existing pipe: pressure, diameter
and length. Please see NOTE 1.
Use new pipe for installation.
Yes
ʯʯThe existing piping has:
ʯʯNO damage, scratches, dents or fractures
ʯʯseparate insulation for the liquid and gas pipe.
No
ʯʯThe existing unit has no history of compressor breakdown.
Use new pipe for installation.
Yes
No
Confirm operation and the possibility of using
the pump down operation.
Clean the pipe work using
the appropriate equipment.
Yes
Perform cooling operation for 30 min.
Then execute pump down operation.
Remove existing air conditioner.
Check the contamination level
of the oil inside the pipe. See NOTE 2.
No
Clean the pipe work using
the appropriate equipment.
OK
Flare connection MUST be redone by using the flare nut included with the new air conditioner (for R-410A).
See NOTE 3
Install the new air conditioner
(Please refer to installation manual before doing so).
Re-use of the existing wiring
Check if the specifications of the installed wiring meet the
requirements of the new unit (type, quantity, …).
No
Use new wiring for installation.
Yes
Check that the wiring does not have any scratches.
Check that the wiring-ground and wiring-wiring insulation has
a resistance higher than 100MΩ. Measurement needs to be
performed with a 500V megger.
Yes
Possible to re-use wiring.
96
No
Use new wiring for installation.
Outdoor units
NOTE 1/ Pipe specifications
1. Pipe thickness
Outside diameter (mm)
6.4
9.5
12.7
15.9
19.1
Material
O
O
O
O
1/2H
Thickness (mm)
0.8
0.8
0.8
1.0
1.0
O: annealed
1/2H: half hard
2. Capacity class and pipe diameter
Split
Sky Air
9.5
•
x
x
x
x
6.4
9.5
12.7
12.7
15.9
19.1
15.9
o
x
x
x
x
•
o
x
x
x
∆
x
x
x
•
∆
∆
∆
•
x
∆
∆
•
o
x
Refrigerant pipe size-up required. Please consult the RZQ-C installation manual.
•
19.1
x
x
x
x
∆
Possible (Standard condition)
o Possible ( With no impact on chargeless length*
and total length)
∆ Possible (With impact on chargeless length* and total length )
x Impossible
refer to NOTE 1.3 for more information
3. Chargeless length* and total length
Split
Liquid pipe
6.4mm
9.5mm
6.4mm
9.5mm
Chargeless length
Max. total length
7.1kW
10m
4m
30m
12m
Multi model application
2MXS40
2MXS50
3MXS52
3MXS68
4MXS68
4MXS80
5MXS90
If the installation requires longer piping length than chargeless length, add refrigerant at the rate
of 20g/m (liquid pipe: 6.4mm), 50g/m(liquid pipe: 9.5mm)
Sky Air (RZQG)
Chargeless (equivalent)
Max. total length
(equivalent)
Liquid pipe
6.4mm
9.5mm
12.7mm
6.4mm
9.5mm
12.7mm
Sky Air (RZQSG)
Chargeless (equivalent)
Max. total length
(equivalent)
Liquid pipe
6.4mm
9.5mm
12.7mm
6.4mm
9.5mm
12.7mm
71
50m(70m)
25m(35m)
71
30m (50m)
15m (25m)
100
125-140
10m (15m)
30m (40m)
15m (20m)
10m (15m)
75m (95m)
35m(45m)
100
125-140
10m (15m)
25m (35m)
10m (15m)
10m (15m)
50m (70m)
25m (35m)
Liquid pipe
Chargeless length
Max. Total length
20m
30m
50m
6.4mm
30m
60m
70m
75m
If the installation requires longer piping length than chargeless length, add refrigerant at the rate of 20g/m
(Liquid pipe: 6.4mm). Should any 9.5 mm piping be in place, use the following formula to determine the
required additional refrigerant charge.
ARC=Yx50+(X-30)x20
ARC: additional refrigerant charge (g)
X: 6.4mm liquid piping length (m)
Y: 9.5mm liquid piping length (m)
In case of 4MX80:
If 0 < ARC < 800 g, apply ARC
If ARC > 800 g, apply 800 g (MAX)
If ARC < 0 g, no additional refrigerant charge required
In case of 5MX90:
If 0 < ARC < 900 g, apply ARC
If ARC > 900 g, apply 900 g (MAX)
If ARC < 0 g, no additional refrigerant charge required
Follow the installation manual for additional refrigerant charge.
* Maximum piping length achievable without additional refrigerant charge.
For more detailed information on RZQ-C consult the installation manual.
NOTE 2/ Contamination level of the oil
Check the colour of the oil in the existing piping by dipping a piece of white paper or cloth into it. If the oil is colourless, the re-use of the pipe work in place is allowed. An oil checking card can also be used for this
purpose (reference nr = 4PW18628-1).
NOTE 3/ Flare connection
Precautions for flare connection:
Piping size
Ø6.4
››
Please refer to the table for the dimensions for processing flares and for the tightening torques.
(Too much tightening will endup splitting of the flare.)
››
When connecting tha flare nut, apply refrigerating machine oil to the flare (inside and outside) and first
screw the nut 3 or 4 turns by hand.
Ø12.7
››
After completing the installation, carry out a gas leak inspection of the
piping connections with nitrogen and such.
Ø.15.9
NOTE 4/ Sky Air installation:
Ø9.5
Ø19.1
Flare nut tightening
torque
14.2~17.2 N•m
(144~176 kgf•cm)
32.7~39.9 N•m
(333~407 kgf•cm)
49.5~60.3 N•m
(504~616 kgf•cm)
61.8~75.4 N•m
(630~770 kgf•cm)
97.2~118.6 N•m
(989.8~1208 kgf•cm)
All dimensions for
processing flares (mm)
flare shape
8.7~9.1
12.8~13.2
16.2~16.6
19.3~19.7
23.6~24.0
In case of twin, triple and double twin installations, a strength pressure test must be performed on the existing piping and piping joints.This test needs to be executed according to EN 378-2 (2009), chapter
6.3.3. The acceptance criteria for the test is that no permanent deformation shall occur in the piping and piping joints at a test pressure of minimum 1.1xPS (PS = maximum allowable pressure). Only in that case
is the re-use of the piping and piping joints possible (please check the nameplate of the replacement unit to determine the maximum allowable pressure PS).
The strength pressure test should be followed by a tightness test, according to EN 378-2 (2009), chapter 6.3.4.
NOTE 5/ Precautions for refrigerant piping
ʯʯ Foreign material (air, mineral oil, moisture, ...) should be prevented from getting mixed into the system. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
ʯʯ Only use R-410A as a refrigerant.
Installation tools: use only installation tools (gauge manifold charge hose, etc.) that are appropriate for R-410A installations so as to withstand the pressure.
Vacuum pump: use a 2-stage vacuum pump with a non-return valve. Make sure the pump oil does not flow back into the system while the pump is not working. Use a vacuum pump which can evacuate to
-100.7 kPa (5 Torr. -755 mmHg).
ʯʯ If the local piping has welded connections, check them for gas leaks..
97
Outdoor Unit
Liquid
Gas
2.0-4.2kW
5.0-6.0kW
7.1kW
7.1kW
10.0-14.0kW
20.0-25.0kW
ARGUE CARDS
Seasonal Smart: The premium solution
RZQG-L9V1/L(8)Y1
Daikin is leading the way towards more efficient and cost-effective
comfort solutions with its Sky Air product range
Why choose Seasonal Smart?
Best in class
quality
Highest seasonal
efficiency values
when compared with other
systems under the same test
conditions
Advanced and
leading
technologies
98
Flexible as no other
Benefits for the installer
Top seasonal efficiency
›› Inverter control logic optimises efficiency
›› Efficiency is enhanced even further thanks to the
Variable Refrigerant Temperature settings
›› Using a highly efficient swing compressor
›› Losses are reduced in standby mode
›› A++ label both in heating and cooling A++
FCQHG71/100F + RZQG71/100L9V1
›› Available with R-32 increasing cooling effiency
with 5%
Advanced and leading technologies
›› Variable Refrigerant Temperature to suit application
requirements better: eliminating cold draughts by
varying the evaporating temperature.
Flexible as no other
›› Reliable, efficient and flexible solution offered
to meet the demanding needs of infrastructure
cooling environments
›› Long pipe runs (up to 75m)
›› Wide operation range for cooling (down to 15°C)
and for heating (down to -20°C)
›› Replacement technology: re-use of existing
pipework of R-22 and R-407C systems
›› Wide range of indoor units connectable: wall
mounted, concealed ceiling, cassette ...
Outdoor Unit
Whatever the installation requirements or
restrictions, Seasonal Smart will be able to meet
them thanks to:
›› R-22/R-407C replacement technology
›› Wide operation range for cooling (down
to -15°C) to suit even infrastructure cooling
applications
›› Wide operation range for heating (down to
-20°C) to be able to deliver heating in the most
severe winters.
›› Long pipe runs of up to 75m
›› Easy accessibility to the gas cooled PCB (L9V1)
›› Easy to install discreetly against the wall thanks
to the limited depth of the unit
›› Wide range of indoor units available
Benefits for
the consultant
›› Market leader in terms of seasonal efficiency.
The unit operates extremely efficiently
throughout the whole summer and winter.
›› R-22/R-407C replacement technology: delivering
major energy savings, rapid payback and
cost-effective upgrade solution with minimum
downtime
›› This system has been optimised to perform well
in the most severe conditions.
›› Wide range of indoor units available to suit
buildings with or without false ceilings
Benefits for the end user
›› Market leader in terms of seasonal efficiency
which reduces your customers’ electricity bills to
a minimum all year round
›› Possibility to reduce sound level via settings on
the remote controller
›› Wide range of stylish, comfortable and silent
indoor units available
›› Possibility of integrating the unit into a Building
Management system
›› Reliable system in all weather conditions
99
Infrastructure cooling solution
Infrastructure cooling
with Seasonal Smart
Daikin is the world leader when it comes to heating and cooling. With over 90
years of innovation and engineering expertise in specialised cooling, Daikin
offers a Sky Air solution that is reliable, efficient and flexible to meet the
demanding needs of infrastructure cooling environments.
Guaranteed system operation:
›› Oversized indoor units boost cooling
capacity and prevent freeze-ups on the
indoor side
›› Wide operating range envelope:
operation range in cooling down to -15°C
and up to +50°C
UNIQUE
Efficient
Optimum return on investment:
›› Lowers running costs by using highly efficient direct expansion cooling systems
›› Lower running costs compared to other
DX systems and water based chillers.
›› Minimises environmental impact with
A++ energy labels
›› Reduces mechanical cooling and energy
consumption with the free cooling option for single phase systems
2-step solution
for system selection
Benefits
Benefits
UNIQUE
UNIQUE
1. Daikin makes the system selection
procedure easy and reliable by providing detailed capacity tables based on
extensive testing.
2. Choose the best product combination
that meets end-user requirements
Flexible control
Benefits
Benefits
100
1. Optimal backup supported by duty
rotation control, automatic backup
activation and remote alarms
2. Guaranteed continuous operation from
extended compressor limits
3. Controller settings to adapt to specific
infrastructure cooling environment
conditions
4. Fewer start/stop cycles
› For
TINUOUS O
ON
RATION
PE
Efficient cooling
1. Free cooling: optimum energy efficiency
using cold ambient air
2. Widest range of indoor systems with best
in class energy efficiency
3. Wide indoor and outdoor operation
range, reliable performance even in
extreme conditions
›› Scalable in capacity
›› Improved infrastructure control and
management
›› Lower physical footprint since no floor
space is occupied
›› Wide range of indoor units to suit application preferences (ceiling suspended
cassettes, wall mounted indoors, concealed ceiling ducted type indoors)
UNIQUE
Dedicated system
combinations
1. Boost the heat transfer capacity of the
indoor system
2. Ability to work with higher evaporation
temperatures (Te) avoids downtime and
enables continuous operation
3. Official energy labels for indoor and
outdoor system combinations provide
standardized and reliable performance
data
Flexible
RELIABLE,
C
Reliable
Infrastructure
cooling solution
server rooms, telecom shelters, laboratories, IT applications
Find out more in our infrastructure
cooling brochure
Infrastructure cooling solution
Boosted capacity indoor systems
High reliability at lower running costs for infrastructure cooling
environments need enhanced capabilities for
continuous heat transfer because they work
harder to extract energy by cooling dry air.
Daikin recommends and offers asymmetric
combinations (boosted capacity indoor
combinations: e.g. 71 class outdoor + 100 class indoor).
With Daikin Sky Air, you benefit from boosted
capacity system combinations for infrastructure
cooling. You can now confidently combine
indoor systems with higher capacities than the
outdoor system. This will boost heat transfer inside
the technology or server room environments.
Outdoor Unit
Split air conditioning systems for normal comfort
cooling applications usually combine indoor systems
with matching capacities, or multiple indoor systems
with capacities lower than the outdoor system’s
capacity. This works because the indoor system’s
cooling capacity is sufficient to handle the higher
humidity conditions and varying indoor temperature
requirements that are common in a normal living
environment.
Applying this design logic to infrastructure
cooling environments can lead to risky situations
that might compromise overall system reliability
and frequent downtimes of 15 minutes.
Indoor systems for infrastructure cooling
Boosted capacity indoor system combination
Infrastructure cooling application system solutions
traditional solution
dedicated solution
Symmetric indoor-outdoor system combination
Te
kW RH%
12
12
10
Te
55
50
10
kW RH%
12
12
10
55
50
10
45
35
6
6
30
4
4
25
Time
Relative Humidity:
Capacity:
Evaporating temp:
8
40
35
6
30
4
Capacity
8
40
Capacity
4
Evaporating Temperature
6
sensible capacity
increase
45
Evaporating Temperature
8
8
Between
20-40%
25
improved solution
reduces over time
Time
reduced
Boosted capacity indoors increase the heat transfer capacity at
drops to compensate reduced capacity
low relative humidity
too low Te can lead to freeze-up
Allows the system to operate with higher Te, guaranteeing
prevention, causing system downtime
continuous operation and reducing unwanted dehumidification
Low humidity + Low ambient environment
Outside temperature Ta
Set-point
Humidity
Indoor wet-bulb temperature
traditional solution
RZQG71L9V1 + FAQ71C
Total Capacity (TC)
Sensible Heat Capacity (SHC)
Power Input (PI)
Co-efficient of Power Input (CPI)
Corrected PI
EER*
-5
22
35
13
5.63
4.28
2
0.39
0.78
5,5
°C
°C
%
°C
kW
kW
kW
kW
18%
savings on
running cost
EER
100%
82%
traditional solution
improved solution
18% SAVINGS
dedicated system combination solution
RZQG71L9V1 + FAQ100C
6,02
Total Capacity (TC)
Sensible Heat Capacity (SHC)
6,02
Power Input (PI)
2
Co-efficient of Power Input (CPI)
0,45
Corrected PI
0.90
EER*
6,7
kW
kW
kW
Sensible Heat Capacity
increases 20-40%
with dedicated system
combination.
kW
*EER = (SHC/Corrected PI)
101
Infrastructure cooling solution
2-Step solution for system selection
High reliability for infrastructure cooling
UNIQUE
Select your infrastructure cooling system in 2 steps
No humidity generation in room
(eg: Server room)
IT room requires 22°C inside. It will have 7kW of sensible
cooling demand, and no latent cooling demand (no
humidity generation) throughout the year.
Ceiling suspended indoor unit is the customer's
preference for the server room.
Indoor temperature = 22°CDB
Sensible cooling demand (SHC) = 7 kW
Latent cooling demand (LC) = 0 kW*
Total cooling demand (TC) = SHC + LC = 7 kW
Outdoor temperature operating range = -15°C ~ +40°C
Most stringent outdoor unit capacity condition = -15°C
solution
Boosted capacity indoor combination
with 10kW outdoor system.
RZQG100L8Y1/ FHQ140C
Total capacity = 7.48 kW
Sensible capacity = 7.48 kW
Power input = 0.42 x 2.49 = 1.04 kW
* If there is no latent cooling demand, look for conditions where
TC = SHC, since no more dehumidification will occur and thus the
indoor environment will stabilize. When TC > SHC and there is no
humidity generation, the indoor humidity will gradually decrease.
102
STEP 1
Determine
requested indoor
conditions
and required
cooling demand
(Sensible and
Total capacity)
STEP 2
Select the system
combination from
the given table,
where the system ‘s
sensible and total
capacity meets the
cooling demand
at the requested
indoor and outdoor
temperatures.
Some humidity source in room
(eg: Laboratory)
Lab requires 22°C inside. It will have 9 kW of sensible
cooling demand, and some humidity generation in
the room (est. indoor humidity level 42%).
Wall mounted indoor unit is the customer’s
preference for the laboratory.
Indoor temperature = 22°CDB
Indoor Relative Humidity (RH%) = 42%**
Sensible cooling demand (SHC) = 9 kW
Latent cooling demand (LC) = 0.9 kW
Total cooling demand (TC) = SHC + LC = 9.9 kW
Outdoor temperature operating range = -10°C ~ +40°C
Most stringent outdoor unit capacity condition = -10°C
solution
Boosted capacity indoor combination
with 12.5kW outdoor system.
RZQG125L9V1/ FAQ71C x 2
Total capacity = 10.45 kW
Sensible capacity = 9.34 kW
Power input = 0.48 x 3.69 = 1.78 kW
** System capacity at 42%RH (14,2°CWB) can be found by interpolation between 13°CWB (35%) and 15°CWB (48%).
Outdoor Unit
Infrastructure cooling solution
FCQG140F
FCQG125F
FCQG100F
3
2
P
2
P
4
3
2
P
2
P
4
3
2
P
3
2
2
P
4
3
2
P
4
3
P
FCQG71F
FCQG50F
FCQG60F
FCQG35F
FCQHG140F
FCQHG125F
4
4
P
FCQHG100F
FCQHG71F
P
P
FVQ71C
FBQ71D
FHQ71C
3
FFQ60C
3
4
2
2
P
Round flow cassette
3
FFQ50C
4
P
High COP,
round flow
cassette
FFQ35C
P
2
FVQ140C
2
3
FVQ125C
3
4
FVQ100C
4
P
FUQ125C
P
2
FUQ100C
2
2
Fully flat
cassette
3
FUQ71C
3
2
3
P
FDXS60F
4
FDXS50F9
2
FDXS35F
3
3
4
FBQ140D
4
4
P
FBQ125D
2
P
2
FBQ100D
2
FBQ60D
3
2
3
P
Concealed 4-way blow Floor standing
ceiling
ceiling
unit
unit
mounted
cassette
3
FBQ50D
4
FHQ140C
2
FHQ125C
2
FHQ100C
3
FHQ60C
P
Concealed ceiling unit
with medium ESP
FBQ35D
RZQG71L9V1B
RZQG71L8Y1B
RZQG100L9V1B
RZQG100L8Y1B
RZQG125L9V1B
RZQG125L8Y1B
RZQG140L9V1B
RZQG140L7Y1B
FHQ50C
Model
Ceiling suspended unit
FHQ35C
Wall
mounted
FAQ100C
Sky Air
FAQ71C
Combination table for boosted capacity indoor systems
P
Possible combinations: P = Pair 2 = Twin 3 = Triple 4 = Double Twin
Notes: The capacities in the table are combined capacities (multiple units operating simultaneously) and not individual indoor unit capacities. When combining multiple indoor
units, designate the master unit as the unit whose remote controller is equipped with the most functions. Refer to the option list when selecting the correct refnet kit required to
install a multi-combination.
103
Infrastructure cooling solution
Performance characteristics
for boosted capacity indoor combinations
Boosted capacity indoors with 7kW outdoor system
RZQG71L9V1 / RZQG71L8Y1
Indoor
RH [%] °CWB
54.5 11
41.8 11
57 13
31.4 11
44.9 13
52 14
22.9 11
34.8 13
47.6 15
54.3 16
21.2 12
32.1 14
43.8 16
50 17
21.5 14
26.3 15
31.3 16
°CDB
16
18
20
22
24
27
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
-15
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.34
0.34
0.37
0.34
0.37
0.38
0.34
0.37
0.39
0.41
0.36
0.38
0.41
0.43
0.38
0.39
0.41
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
7.82
-10
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.36
0.36
0.41
0.36
0.41
0.44
0.36
0.41
0.46
0.49
0.38
0.44
0.49
0.51
0.44
0.46
0.49
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
7.82
-5
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.37
0.37
0.45
0.37
0.45
0.50
0.37
0.45
0.54
0.58
0.41
0.50
0.58
0.60
0.50
0.54
0.58
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
7.82
0
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.39
0.39
0.50
0.39
0.50
0.55
0.39
0.50
0.61
0.66
0.44
0.55
0.66
0.68
0.55
0.61
0.66
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
7.82
5
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.41
0.41
0.52
0.41
0.52
0.58
0.41
0.52
0.63
0.69
0.46
0.58
0.69
0.70
0.58
0.63
0.69
Outdoor temperature [°C DB]
10
15
TC SHC CPI TC SHC CPI
kW kW - kW kW 4.81 3.98 0.43 4.81 3.98 0.46
4.81 4.67 0.43 4.81 4.67 0.46
6.02 5.05 0.55 6.02 5.05 0.57
4.81 4.81 0.43 4.81 4.81 0.46
6.02 6.02 0.55 6.02 6.02 0.57
6.62 5.76 0.60 6.62 5.76 0.63
4.81 4.81 0.43 4.81 4.81 0.46
6.02 6.02 0.55 6.02 6.02 0.57
7.22 6.06 0.66 7.22 6.06 0.69
7.82 5.71 0.72 7.82 5.71 0.75
5.41 5.41 0.49 5.41 5.41 0.52
6.62 6.62 0.60 6.62 6.62 0.63
7.82 6.57 0.72 7.82 6.57 0.75
8.10 6.08 0.73 8.10 6.08 0.75
6.62 6.62 0.60 6.62 6.62 0.63
7.22 7.22 0.66 7.22 7.22 0.69
7.82 7.82 0.72 7.82 7.82 0.75
TC
kW
4.81
4.81
6.02
4.81
6.02
6.62
4.81
6.02
7.22
7.82
5.41
6.62
7.82
8.10
6.62
7.22
7.82
20
SHC
kW
3.98
4.67
5.05
4.81
6.02
5.76
4.81
6.02
6.06
5.71
5.41
6.62
6.57
6.08
6.62
7.22
7.82
CPI
0.48
0.48
0.64
0.48
0.64
0.72
0.48
0.64
0.79
0.87
0.56
0.72
0.87
0.88
0.72
0.79
0.87
TC
kW
5.90
5.90
7.49
5.90
7.49
8.15
5.90
7.49
8.41
8.68
6.70
8.15
8.68
8.96
8.15
8.41
8.68
25
SHC
kW
5.25
5.90
5.89
5.90
7.00
6.56
5.90
7.49
7.00
6.54
6.70
8.15
7.45
6.99
8.15
8.41
8.68
CPI
0.98
0.98
0.99
0.98
0.99
0.99
0.98
0.99
1.00
1.00
0.99
0.99
1.00
1.00
0.99
1.00
1.00
TC
kW
5.85
5.85
7.23
5.85
7.23
7.74
5.85
7.23
7.99
8.25
6.54
7.74
8.25
8.53
7.74
7.99
8.25
30
SHC
kW
5.22
5.85
5.75
5.85
6.81
6.36
5.85
7.23
6.80
6.35
6.54
7.74
7.26
6.80
7.74
7.99
8.25
CPI
1.09
1.09
1.10
1.09
1.10
1.10
1.09
1.10
1.11
1.11
1.10
1.10
1.11
1.11
1.10
1.11
1.11
TC
kW
5.80
5.80
6.96
5.80
6.96
7.34
5.80
6.96
7.58
7.83
6.38
7.34
7.83
8.09
7.34
7.58
7.83
35
SHC
kW
5.20
5.80
5.61
5.80
6.60
6.15
5.80
6.96
6.60
6.14
6.38
7.34
7.04
6.59
7.34
7.58
7.83
CPI
1.19
1.19
1.20
1.19
1.20
1.20
1.19
1.20
1.21
1.21
1.20
1.20
1.21
1.21
1.20
1.21
1.21
TC
kW
5.76
5.76
6.70
5.76
6.70
6.93
5.76
6.70
7.16
7.40
6.23
6.93
7.40
7.66
6.93
7.16
7.40
40
SHC
kW
5.17
5.76
5.47
5.76
6.37
5.93
5.76
6.70
6.37
5.92
6.23
6.93
6.82
6.37
6.93
7.16
7.40
CPI
1.30
1.30
1.31
1.30
1.31
1.31
1.30
1.31
1.32
1.32
1.31
1.31
1.32
1.32
1.31
1.32
1.32
3D098206A
PAIR
Cooling
FAQ100C
2.00
FHQ100C
1.78
FBQ100D
1.89
FUQ100C
1.67
FVQ100C
2.02
FCQHG100F
1.66
FCQG100F
2.01
TWIN
Cooling
FHQ50C x 2
2.34
FBQ50D x 2
2.02
FDXS50F9 x 2
2.23
FFQ50C x 2
2.02
FCQG50F x 2
2.04
TRIPLE
Cooling
FHQ35CA x 3
2.39
FBQ35D x 3
2.11
FDXS35F x 3
2.26
FFQ35C x 3
2.07
FCQG35F x 3
2.06
Boosted capacity indoors with 10kW outdoor system
RZQG100L9V1 / RZQG100L8Y1
Indoor
RH [%] °CWB
54.5 11
41.8 11
57 13
31.4 11
44.9 13
52 14
22.9 11
34.8 13
47.6 15
54.3 16
21.2 12
32.1 14
43.8 16
50 17
21.5 14
26.3 15
31.3 16
°CDB
16
18
20
22
24
27
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
-15
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.33
0.33
0.42
0.33
0.42
0.47
0.33
0.42
0.52
0.56
0.38
0.47
0.56
0.58
0.47
0.52
0.56
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
-10
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.34
0.34
0.44
0.34
0.44
0.48
0.34
0.44
0.53
0.58
0.39
0.48
0.58
0.59
0.48
0.53
0.58
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
-5
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.35
0.35
0.45
0.35
0.45
0.49
0.35
0.45
0.54
0.59
0.40
0.49
0.59
0.60
0.49
0.54
0.59
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
0
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.37
0.37
0.46
0.37
0.46
0.51
0.37
0.46
0.55
0.60
0.41
0.51
0.60
0.61
0.51
0.55
0.60
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
5
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.38
0.38
0.46
0.38
0.46
0.50
0.38
0.46
0.54
0.59
0.42
0.50
0.59
0.60
0.50
0.54
0.59
Outdoor temperature [°C DB]
10
15
TC SHC CPI TC SHC CPI
kW kW - kW kW 6.00 5.63 0.38 6.00 5.63 0.39
6.00 6.00 0.38 6.00 6.00 0.39
7.48 6.37 0.46 7.48 6.37 0.45
6.00 6.00 0.38 6.00 6.00 0.39
7.48 7.25 0.46 7.48 7.25 0.45
8.22 7.18 0.49 8.22 7.18 0.49
6.00 6.00 0.38 6.00 6.00 0.39
7.48 7.48 0.46 7.48 7.48 0.45
8.96 7.82 0.53 8.96 7.82 0.52
9.70 7.54 0.57 9.70 7.54 0.55
6.74 6.74 0.42 6.74 6.74 0.42
8.22 8.22 0.49 8.22 8.22 0.49
9.70 8.68 0.57 9.70 8.68 0.55
9.98 7.86 0.60 9.98 7.86 0.60
8.22 8.22 0.49 8.22 8.22 0.49
8.96 8.96 0.53 8.96 8.96 0.52
9.70 9.70 0.57 9.70 9.70 0.55
TC
kW
6.00
6.00
7.48
6.00
7.48
8.22
6.00
7.48
8.96
9.70
6.74
8.22
9.70
9.98
8.22
8.96
9.70
20
SHC
kW
5.63
6.00
6.37
6.00
7.25
7.18
6.00
7.48
7.82
7.54
6.74
8.22
8.68
7.86
8.22
8.96
9.70
CPI
0.39
0.39
0.46
0.39
0.46
0.49
0.39
0.46
0.52
0.56
0.42
0.49
0.56
0.60
0.49
0.52
0.56
25
TC SHC
kW kW
8.36 7.11
8.36 7.98
9.71 7.67
8.36 8.36
9.71 8.53
10.50 8.45
8.36 8.36
9.71 9.71
11.28 9.19
11.84 8.40
9.04 9.04
10.50 10.50
11.84 9.74
12.39 9.45
10.50 10.50
11.28 11.28
11.84 11.84
CPI
1.00
1.00
1.00
1.00
1.00
1.01
1.00
1.00
1.01
1.01
1.00
1.01
1.01
1.02
1.01
1.01
1.01
30
TC SHC
kW kW
7.92 6.83
7.92 7.72
9.30 7.42
7.92 7.92
9.30 8.28
10.23 8.31
7.92 7.92
9.30 9.30
10.89 8.96
11.40 8.22
8.61 8.61
10.23 10.23
11.40 9.51
11.86 9.16
10.23 10.23
10.89 10.89
11.40 11.40
CPI
1.10
1.10
1.11
1.10
1.11
1.11
1.10
1.11
1.11
1.11
1.10
1.11
1.12
1.12
1.11
1.11
1.12
35
TC SHC
kW kW
7.48 6.53
7.48 7.43
8.90 7.16
7.48 7.48
8.90 8.01
9.96 8.17
7.48 7.48
8.90 8.90
10.51 8.72
11.03 8.04
8.19 8.19
9.96 9.96
11.03 9.32
11.33 8.86
9.96 9.96
10.51 10.51
11.03 11.03
CPI
1.20
1.20
1.21
1.20
1.21
1.21
1.20
1.21
1.22
1.22
1.21
1.21
1.22
1.22
1.21
1.22
1.22
40
TC SHC
kW kW
7.09 6.28
7.09 7.15
8.45 6.88
7.09 7.09
8.45 7.74
9.68 7.94
7.09 7.09
8.45 8.45
10.12 8.48
10.58 7.77
7.77 7.77
9.68 9.68
10.58 9.06
10.80 8.52
9.68 9.68
10.12 10.12
10.58 10.58
CPI
1.29
1.29
1.30
1.29
1.30
1.31
1.29
1.30
1.32
1.32
1.30
1.31
1.32
1.33
1.31
1.32
1.32
3D098207A
PAIR
Cooling
FHQ140C
2.49
FBQ140D
2.49
FVQ140C
2.49
FCQHG140F
2.15
FCQG140F
2.45
TWIN
Cooling
FAQ71C x 2
2.64
FHQ71C x 2
2.94
FBQ71D x 2
2.83
FUQ71C x 2
2.34
FCQHG71F x 2
2.14
Symbols
TC
SHC
CPI
PI
RH
104
Maximum total cooling capacity [kW]
Sensible heat capacity [kW]
Coefficient of the power input
Power input [kW]
compressor + indoor and outdoor fan motors
Relative humidity [%]
FCQG71F x 2
2.35
TRIPLE
Cooling
FHQ50C x 3
2.98
FBQ50D x 3
2.96
FDXS50F9 x 3
2.54
FFQ50C x 3
2.70
FCQG50F x 3
2.33
DOUBLE TWIN
Cooling
FHQ35C x 4
3.03
FBQ35D x 4
3.05
FDXS35F x 4
2.58
FFQ35C x 4
2.75
FCQG35F x 4
2.35
Infrastructure cooling solution
Boosted capacity indoors with 12.5kW outdoor system
Indoor
RH [%] °CWB
54.5 11
41.8 11
57 13
31.4 11
44.9 13
52 14
22.9 11
34.8 13
47.6 15
54.3 16
21.2 12
32.1 14
43.8 16
50 17
21.5 14
26.3 15
31.3 16
°CDB
16
18
20
22
24
27
-15
TC SHC
kW kW
7.49 6.72
7.49 7.49
9.34 7.60
7.49 7.49
9.34 8.65
10.27 8.56
7.49 7.49
9.34 9.34
11.20 9.34
12.12 9.00
8.42 8.42
10.27 10.27
12.12 10.35
12.47 9.38
10.27 10.27
11.20 11.20
12.12 12.12
CPI
0.33
0.33
0.42
0.33
0.42
0.46
0.33
0.42
0.51
0.55
0.37
0.46
0.55
0.57
0.46
0.51
0.55
-10
TC SHC
kW kW
7.49 6.72
7.49 7.49
9.34 7.60
7.49 7.49
9.34 8.65
10.27 8.56
7.49 7.49
9.34 9.34
11.20 9.34
12.12 9.00
8.42 8.42
10.27 10.27
12.12 10.35
12.47 9.38
10.27 10.27
11.20 11.20
12.12 12.12
CPI
0.34
0.34
0.43
0.34
0.43
0.47
0.34
0.43
0.52
0.57
0.38
0.47
0.57
0.58
0.47
0.52
0.57
-5
TC SHC
kW kW
7.49 6.72
7.49 7.49
9.34 7.60
7.49 7.49
9.34 8.65
10.27 8.56
7.49 7.49
9.34 9.34
11.20 9.34
12.12 9.00
8.42 8.42
10.27 10.27
12.12 10.35
12.47 9.38
10.27 10.27
11.20 11.20
12.12 12.12
CPI
0.35
0.35
0.44
0.35
0.44
0.49
0.35
0.44
0.53
0.58
0.39
0.49
0.58
0.59
0.49
0.53
0.58
0
TC SHC
kW kW
7.49 6.72
7.49 7.49
9.34 7.60
7.49 7.49
9.34 8.65
10.27 8.56
7.49 7.49
9.34 9.34
11.20 9.34
12.12 9.00
8.42 8.42
10.27 10.27
12.12 10.35
12.47 9.38
10.27 10.27
11.20 11.20
12.12 12.12
CPI
0.36
0.36
0.45
0.36
0.45
0.50
0.36
0.45
0.55
0.59
0.41
0.50
0.59
0.60
0.50
0.55
0.59
5
TC SHC
kW kW
7.49 6.72
7.49 7.49
9.34 7.60
7.49 7.49
9.34 8.65
10.27 8.56
7.49 7.49
9.34 9.34
11.20 9.34
12.12 9.00
8.42 8.42
10.27 10.27
12.12 10.35
12.47 9.38
10.27 10.27
11.20 11.20
12.12 12.12
CPI
0.37
0.37
0.45
0.37
0.45
0.49
0.37
0.45
0.54
0.58
0.41
0.49
0.58
0.59
0.49
0.54
0.58
Outdoor temperature [°C DB]
10
15
20
TC SHC CPI TC SHC CPI TC SHC
kW kW - kW kW - kW kW
7.49 6.72 0.38 7.49 6.72 0.38 7.49 6.72
7.49 7.49 0.38 7.49 7.49 0.38 7.49 7.49
9.34 7.60 0.45 9.34 7.60 0.45 9.34 7.60
7.49 7.49 0.38 7.49 7.49 0.38 7.49 7.49
9.34 8.65 0.45 9.34 8.65 0.45 9.34 8.65
10.27 8.56 0.49 10.27 8.56 0.48 10.27 8.56
7.49 7.49 0.38 7.49 7.49 0.38 7.49 7.49
9.34 9.34 0.45 9.34 9.34 0.45 9.34 9.34
11.20 9.34 0.52 11.20 9.34 0.51 11.20 9.34
12.12 9.00 0.56 12.12 9.00 0.54 12.12 9.00
8.42 8.42 0.41 8.42 8.42 0.41 8.42 8.42
10.27 10.27 0.49 10.27 10.27 0.48 10.27 10.27
12.12 10.35 0.56 12.12 10.35 0.54 12.12 10.35
12.47 9.38 0.59 12.47 9.38 0.59 12.47 9.38
10.27 10.27 0.49 10.27 10.27 0.48 10.27 10.27
11.20 11.20 0.52 11.20 11.20 0.51 11.20 11.20
12.12 12.12 0.56 12.12 12.12 0.54 12.12 12.12
CPI
0.38
0.38
0.45
0.38
0.45
0.48
0.38
0.45
0.51
0.55
0.41
0.48
0.55
0.59
0.48
0.51
0.55
25
TC SHC
kW kW
10.25 8.55
10.25 9.60
11.91 9.22
10.25 10.25
11.91 10.27
12.88 10.16
10.25 10.25
11.91 11.91
13.83 11.06
14.51 10.10
11.08 11.08
12.88 12.88
14.51 11.71
15.20 11.36
12.88 12.88
13.83 13.83
14.51 14.51
CPI
0.98
0.98
0.99
0.98
0.99
0.99
0.98
0.99
0.99
1.00
0.98
0.99
1.00
1.00
0.99
0.99
1.00
30
TC SHC
kW kW
9.71 8.21
9.71 9.28
11.41 8.92
9.71 9.71
11.41 9.96
12.54 10.00
9.71 9.71
11.41 11.41
13.36 10.78
13.98 9.89
10.56 10.56
12.54 12.54
13.98 11.44
14.54 11.02
12.54 12.54
13.36 13.36
13.98 13.98
CPI
1.08
1.08
1.09
1.08
1.09
1.09
1.08
1.09
1.09
1.10
1.08
1.09
1.10
1.10
1.09
1.09
1.10
35
TC SHC
kW kW
9.17 7.86
9.17 8.94
10.91 8.61
9.17 9.17
10.91 9.64
12.21 9.83
9.17 9.17
10.91 10.91
12.88 10.49
13.52 9.67
10.04 10.04
12.21 12.21
13.52 11.21
13.89 10.66
12.21 12.21
12.88 12.88
13.52 13.52
CPI
1.18
1.18
1.19
1.18
1.19
1.19
1.18
1.19
1.20
1.20
1.19
1.19
1.20
1.20
1.19
1.20
1.20
40
TC SHC
kW kW
8.69 7.55
8.69 8.60
10.37 8.28
8.69 8.69
10.37 9.31
11.87 9.55
8.69 8.69
10.37 10.37
12.41 10.20
12.98 9.35
9.53 9.53
11.87 11.87
12.98 10.90
13.24 10.25
11.87 11.87
12.41 12.41
12.98 12.98
CPI
1.27
1.27
1.28
1.27
1.28
1.29
1.27
1.28
1.29
1.30
1.27
1.29
1.30
1.31
1.29
1.29
1.30
3D098208A
PAIR
Cooling
FHQ140C
3.58
FBQ140D
3.63
FVQ140C
3.74
FCQHG140F
3.00
FCQG140F
3.22
TWIN
Cooling
FAQ71C x 2
3.69
FHQ71C x 2
3.67
FBQ71D x 2
4.10
FUQ71C x 2
3.44
FCQHG71F x 2
2.97
FCQG71F x 2
3.17
TRIPLE
Cooling
FHQ50C x 3
3.66
FBQ50D x 3
3.97
FDXS50F9 x 3
3.45
FFQ50C x 3
3.23
FCQG50F x 3
3.17
DOUBLE TWIN
Cooling
FHQ35C x 4
3.64
FBQ35D x 4
3.74
FDXS35F x 4
3.94
FFQ35C x 4
3.01
FCQG35F x 4
3.23
Combinations with 14kW outdoor system
RZQG140L9V1 / RZQG140L7Y1
Indoor
RH [%] °CWB
54.5 11
41.8 11
57 13
31.4 11
44.9 13
52 14
22.9 11
34.8 13
47.6 15
54.3 16
21.2 12
32.1 14
43.8 16
50 17
21.5 14
26.3 15
31.3 16
°CDB
16
18
20
22
24
27
-15
TC SHC
kW kW
8.24 7.27
8.24 8.24
10.28 8.22
8.24 8.24
10.28 9.35
11.30 9.26
8.24 8.24
10.28 10.28
12.32 10.10
13.33 9.73
9.26 9.26
11.30 11.30
13.33 11.20
13.72 10.15
11.30 11.30
12.32 12.32
13.33 13.33
CPI
0.32
0.32
0.41
0.32
0.41
0.45
0.32
0.41
0.50
0.54
0.37
0.45
0.54
0.56
0.45
0.50
0.54
-10
TC SHC
kW kW
8.24 7.27
8.24 8.24
10.28 8.22
8.24 8.24
10.28 9.35
11.30 9.26
8.24 8.24
10.28 10.28
12.32 10.10
13.33 9.73
9.26 9.26
11.30 11.30
13.33 11.20
13.72 10.15
11.30 11.30
12.32 12.32
13.33 13.33
CPI
0.33
0.33
0.42
0.33
0.42
0.47
0.33
0.42
0.51
0.56
0.38
0.47
0.56
0.57
0.47
0.51
0.56
-5
TC SHC
kW kW
8.24 7.27
8.24 8.24
10.28 8.22
8.24 8.24
10.28 9.35
11.30 9.26
8.24 8.24
10.28 10.28
12.32 10.10
13.33 9.73
9.26 9.26
11.30 11.30
13.33 11.20
13.72 10.15
11.30 11.30
12.32 12.32
13.33 13.33
CPI
0.34
0.34
0.43
0.34
0.43
0.48
0.34
0.43
0.52
0.57
0.39
0.48
0.57
0.58
0.48
0.52
0.57
0
TC SHC
kW kW
8.24 7.27
8.24 8.24
10.28 8.22
8.24 8.24
10.28 9.35
11.30 9.26
8.24 8.24
10.28 10.28
12.32 10.10
13.33 9.73
9.26 9.26
11.30 11.30
13.33 11.20
13.72 10.15
11.30 11.30
12.32 12.32
13.33 13.33
CPI
0.35
0.35
0.45
0.35
0.45
0.49
0.35
0.45
0.54
0.58
0.40
0.49
0.58
0.59
0.49
0.54
0.58
5
TC SHC
kW kW
8.24 7.27
8.24 8.24
10.28 8.22
8.24 8.24
10.28 9.35
11.30 9.26
8.24 8.24
10.28 10.28
12.32 10.10
13.33 9.73
9.26 9.26
11.30 11.30
13.33 11.20
13.72 10.15
11.30 11.30
12.32 12.32
13.33 13.33
CPI
0.37
0.37
0.45
0.37
0.45
0.49
0.37
0.45
0.53
0.57
0.41
0.49
0.57
0.58
0.49
0.53
0.57
Outdoor temperature [°C DB]
10
15
20
TC SHC CPI TC SHC CPI TC SHC
kW kW - kW kW - kW kW
8.24 7.27 0.37 8.24 7.27 0.37 8.24 7.27
8.24 8.24 0.37 8.24 8.24 0.37 8.24 8.24
10.28 8.22 0.44 10.28 8.22 0.44 10.28 8.22
8.24 8.24 0.37 8.24 8.24 0.37 8.24 8.24
10.28 9.35 0.44 10.28 9.35 0.44 10.28 9.35
11.30 9.26 0.48 11.30 9.26 0.47 11.30 9.26
8.24 8.24 0.37 8.24 8.24 0.37 8.24 8.24
10.28 10.28 0.44 10.28 10.28 0.44 10.28 10.28
12.32 10.10 0.51 12.32 10.10 0.50 12.32 10.10
13.33 9.73 0.55 13.33 9.73 0.53 13.33 9.73
9.26 9.26 0.41 9.26 9.26 0.41 9.26 9.26
11.30 11.30 0.48 11.30 11.30 0.47 11.30 11.30
13.33 11.20 0.55 13.33 11.20 0.53 13.33 11.20
13.72 10.15 0.58 13.72 10.15 0.58 13.72 10.15
11.30 11.30 0.48 11.30 11.30 0.47 11.30 11.30
12.32 12.32 0.51 12.32 12.32 0.50 12.32 12.32
13.33 13.33 0.55 13.33 13.33 0.53 13.33 13.33
CPI
0.38
0.38
0.44
0.38
0.44
0.47
0.38
0.44
0.50
0.54
0.41
0.47
0.54
0.58
0.47
0.50
0.54
25
TC SHC
kW kW
10.95 8.87
10.95 9.96
12.72 9.56
10.95 10.95
12.72 10.64
13.75 10.53
10.95 10.95
12.72 12.72
14.77 11.47
15.50 10.47
11.83 11.83
13.75 13.75
15.50 12.14
16.23 11.78
13.75 13.75
14.77 14.77
15.50 15.50
CPI
0.96
0.96
0.97
0.96
0.97
0.97
0.96
0.97
0.98
0.98
0.97
0.97
0.98
0.98
0.97
0.98
0.98
30
TC SHC
kW kW
10.37 8.51
10.37 9.62
12.18 9.25
10.37 10.37
12.18 10.33
13.40 10.36
10.37 10.37
12.18 12.18
14.26 11.18
14.93 10.25
11.28 11.28
13.40 13.40
14.93 11.86
15.53 11.43
13.40 13.40
14.26 14.26
14.93 14.93
CPI
1.06
1.06
1.07
1.06
1.07
1.07
1.06
1.07
1.08
1.08
1.07
1.07
1.08
1.08
1.07
1.08
1.08
35
TC SHC
kW kW
9.79 8.15
9.79 9.27
11.65 8.93
9.79 9.79
11.65 10.00
13.04 10.19
9.79 9.79
11.65 11.65
13.76 10.88
14.44 10.03
10.72 10.72
13.04 13.04
14.44 11.62
14.83 11.06
13.04 13.04
13.76 13.76
14.44 14.44
CPI
1.16
1.16
1.17
1.16
1.17
1.17
1.16
1.17
1.18
1.18
1.17
1.17
1.18
1.18
1.17
1.18
1.18
40
TC SHC
kW kW
9.28 7.83
9.28 8.92
11.07 8.58
9.28 9.28
11.07 9.65
12.68 9.90
9.28 9.28
11.07 11.07
13.25 10.57
13.86 9.69
10.17 10.17
12.68 12.68
13.86 11.30
14.14 10.63
12.68 12.68
13.25 13.25
13.86 13.86
CPI
1.25
1.25
1.26
1.25
1.26
1.27
1.25
1.26
1.27
1.28
1.25
1.27
1.28
1.29
1.27
1.27
1.28
3D098209A
PAIR
Cooling
FHQ140C
4.05
FBQ140D
4.00
FVQ140C
4.17
FCQHG140F
4.00
FCQG140F
4.17
TWIN
Cooling
FAQ71C x 2
3.81
FHQ71C x 2
3.59
FBQ71D x 2
3.75
FUQ71C x 2
3.35
FCQHG71F x 2
3.94
FCQG71F x 2
4.11
TRIPLE
Cooling
FHQ50C x 3
4.25
FBQ50D x 3
3.75
FDXS50F9 x 3
4.26
FFQ50C x 3
4.15
FCQG50F x 3
4.12
DOUBLE TWIN
Cooling
FHQ35C x 4
4.23
FBQ35D x 4
3.75
FDXS35F x 4
5.38
FFQ35C x 4
3.83
FCQG35F x 4
4.18
Notes
1. The ratings shown are net capacities
and include a deduction for indoor
fan motor heat.
2. The capacities are based on
the following conditions:
›› Outdoor air: 85% RH
›› Corresponding refrigerant
piping length: 5.0 m
›› Level difference: 0m
3. CPI is a percentage value compared
to the rated value of 1.00
4. For infrastructure cooling applications,
it is recommended to use remote
controller setting 16(26)-2-03
5. The error rate for this value is less
than 5% and depends on the indoor
unit type
6. The rated power inputs (PI) for each
model are listed in the table above
105
Outdoor Unit
RZQG125L9V1 / RZQG125L8Y1
RZAG-LV1
Pair
Industry leading technology with R-32 delivering optimal
efficiency and comfort for commercial applications
›› Daikin‘s Seasonal Smart range is the first R-32 light commercial
range available in the European market
›› 68% lower GWP compared to R-410A products
›› 10% lower refrigerant charge compared to R-410A products
›› Minimum 5% more efficient in cooling when compared to R-410A
products
›› Quiet mode: set via the remote control for example during night
time, ...
›› The perfect balance in efficiency and comfort thanks to Variable
Refrigerant Temperature: top seasonal efficiency throughout most
of the year and quick reaction speed on the hottest days.
RZQG140L9V1//(L(8)Y1
›› Re-use of existing R-22 or R-407C technology
›› Extended operation range down to -20°C in heating and down to
-15°C in cooling
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
Unit
Cooling
Cooling
Heating
Night quiet mode
Cooling
Heating
Type
Charge
GWP
Liquid
Gas
Piping length
HeightxWidthxDepth
Nom.
Nom.
Level 1
Ambient
Ambient
OD
OD
OU - IU
System
Additional refrigerant charge
Level difference
IU - OU
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
Min.~Max.
Min.~Max.
Max.
Equivalent
Chargeless
Max.
RZAG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
71LV1
990x940x320
67
kg
TCO₂eq
2.6
1.8
mm
mm
m
m
m
kg/m
m
Hz / V
A
100LV1
125LV1
1,430x940x320
93
66
51
64
48
50
43
49
51
140LV1
67
52
52
45
-15~50
-20~15.5
R-32
3.4
2.3
675
9.52
15.9
55
75
85
100
30
See installation manual
30.0
1~ / 50/60 / 220-240
-
Contains fluorinated greenhouse gases | Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
Data for standard efficiency series | Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for
standard efficiency series | See separate drawing for electrical data
106
RZQG-L9V1/L(8)Y1
Pair, Twin, Triple, double twin
Industry leading technology for commercial applications
and even for technical rooms
Outdoor Unit
›› Top efficiency:
›› energy labels up to A++ in both cooling and heating
›› compressor that offers substantial efficiency improvements
›› control logic that optimises efficiency at the most frequently
encountered operating conditions and that optimises the auxiliary
modes (when the unit is not active)
›› heat exchangers that optimise the refrigerant flow at the most
frequent operating conditions (temperature and load)
›› via improved nominal performances
›› The perfect balance in efficiency and comfort thanks to Variable
Refrigerant Temperature: top seasonal efficiency throughout most
of the year and quick reaction speed on the hottest days.
RZQG140L9V1//(L(8)Y1
›› Maximum piping length up to 75m, minimum piping length is 5m.
›› Outdoor units for pair, twin, triple, double twin application
›› Daikin outdoor units are neat, sturdy and can easily be mounted
on a roof or terrace or simply placed against an outside wall
›› Compatibility with D-BACS
›› Units optimized for seasonal efficiency give an indication on how
efficient an air conditioner operates over an entire heating or
cooling season.
›› Suits high sensible, infrastructure cooling applications
›› Re-use of existing R-22 or R-407C technology
›› Extended operation range down to -20°C in heating and down to
-15°C in cooling
›› With a gas cooled PCB reliable cooling is guaranteed as it is not
influenced by ambient temperature
Twin, triple and double twin application
FCQHG-F
capacity class
71
FCQG-F
35
50
RZQG71L9V1 RZQG71L8Y1
2
RZQG100L9V1 RZQG100L8Y1
3
2
4
3
4
3
RZQG125L9V1 RZQG125L8Y1
RZQG140L9V1 RZQG140LY1
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
2
Unit
Unit
Cooling
Cooling
60
FFQ-C
71
35
50
FDXS-F (9)
60
2
2
2
2
4
3
4
3
Nom.
Heating
Nom.
Night quiet mode
Level 1
Cooling
Ambient
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
System
Additional refrigerant charge
Level difference
IU - OU
IU - IU
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
Min.~Max.
Min.~Max.
Max.
Equivalent
Chargeless
Max.
Max.
50
FBQ-D
60
2
3
HeightxWidthxDepth
35
2
50
60
FHQ-C
71
2
3
2
4
3
4
3
RZQG
71L9V1
mm 990x940x320
kg
69
dBA
64
dBA
48
dBA
50
dBA
43
°CDB
°CWB
R-410A/2.9/6.1/2,087.5
mm
mm
m
50
m
70
m
kg/m
m
m
Hz / V
A
20
35
2
100L9V1
35
50
60
FAQ-C FUQ-C
71
71
71
2
3
2
4
3
4
3
2
2
FNQ-A
35
50
60
2
3
2
4
3
4
3
2
125L9V1
140L9V1
71L8Y1
1,430x940x320
990x940x320
95
80
66
67
69
64
50
51
52
48
52
53
50
45
43
-15~50
-20~15.5
R-410A/4.0/8.4/2,087.5
R-410A/2.9/6.1/2,087.5
9.52
15.9
75
50
90
70
30
See installation manual
30.0
0.5
1~ / 50 / 220-240
32
20
2
2
100L8Y1
66
50
52
2
3
2
4
3
4
3
2
125L8Y1
140LY1
1,430x940x320
101
67
69
51
52
53
45
R-410A/4.0/8.4/2,087.5
75
90
3N~ / 50 / 380-415
32
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
107
Detailed technical drawings
RZQG-L9V1
RZQG71-125L9V1
108
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
RZQG125-140L9V1
RZQG125-140L9V1
109
Detailed technical drawings
RZQG125-140L9V1
RZQG140L9V1
110
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
RZQG71-100L8Y1
RZQG71-100L8Y1
111
Detailed technical drawings
RZQG71-100L8Y1
RZQG71-100L8Y1
112
Detailed technical drawings
Outdoor Unit
RZQG71-100L8Y1
RZQG71-100L8Y1
113
Detailed technical drawings
RZQG100-125L8Y1
RZQG100-140L(8)Y1
114
Detailed technical drawings
Outdoor Unit
RZQG100-140L(8)Y1
RZQG125-140L(8)Y1
115
Detailed technical drawings
RZQG125-140L(8)Y1
116
RZAG-LV1
117
Outdoor Unit
Detailed technical drawings
Find all technical drawings on our business portal http://my.daikin.eu
RZQG-L9V1/L8Y1
1 Gas pipe connection </J 15.9 flare
2 Liquid pipe connection - </J 9.5 flare
3 Service port (in the unit)
4 Grounding terminal MS (in switch box)
5 Refrigerant piping intake
6 Power supply wiring intake (knock out hole </J 34)
7 Control wiring intake (Knock out hole </J 27)
8 Drain outlet
RZQG100-140L9V1/L8Y1
118
Detailed technical drawings
Outdoor Unit
RZQG-L9V1/L8Y1
119
Detailed technical drawings
RZQG-L9V1/L8Y1
120
Detailed technical drawings
RZQG-L9V1/L8Y1
Definitions: L1~L7, H1, H2
Charging
refrigerant
Pair
L1
(a)
TwinL3
H1
Pair (a)
L1
Determine R1x=Ø9.5
and R2.mm (standard)
H1
L1
2
G1≤30 m (a) If
L5
H1
L4
L1
L3
L3
H2
L2
L5
L6
(a)
(and G1+G2>30 m)
(a)
Assume that the longest line in the illustration corresponds
with the actual longest pipe, and the highest unit in the
L3
L7
illustration corresponds with the actual highest unit.
L1 Main piping
L2~L7 Branch piping
L1
H1 Height difference between the highest indoor unit and the
outdoor unit
(a) Assume
that the
longestbetween
line in the
H2 Height
difference
theillustration
highest andcorresponds
the lowest
with the
actual
longest pipe, and the highest unit in the
indoor
unit
illustration
corresponds
Refrigerant
branchwith
kit the actual highest unit.
R1:
R2:
(a)
3
3
L3=5 m
(Ø6.4 mm)
L1=35 m (Ø9.5 mm)
L2=20 m
(Ø6.4 mm)
RZQG100
L3=17 m
(Ø6.4 mm)
▪ 15 m (size-up)
L4=17 m
(Ø6.4 mm)
INFORMATION
(L1+L2+L3+L4+L5+L6+L7)>
You must add additional
Piping length is the largest one way length of liquid piping.
chargeless length
refrigerant.
L1=5 m (Ø9.5 mm)
L2=20 m
RZQG125
(Ø6.4 mm)
For future
servicing,
encircle
the
To determine the additional refrigerant
amount
(R in kg)
(in
case of pair)
selected amount in the tables
INFORMATION
L1 (standard):
30~40 m
L3=17 m
(Ø6.4 mm)
L1 (m)
40~50 m
50~60 m
(a)
60~75 m
(a)
PipingL1
length
is the largest
one way length of liquid piping.
(size-up):
15~20 m 20~25 m 25~30 m (a) 30~35 m (a)
R:
0.5 kg
1.0 kg
1.5 kg
To determine the additional refrigerant amount (R in kg) (in
(a) Only for RZQG100~140.
case of pair)
2.0 kg
30~40 m
40~50 m
1.0 kg
(a)
1.5 kg
0.6 kg
30~45 m (a)
(a)
(a)
10~15
1.5mkg
(a)
15~20
2.0mkg
0.9 kg
2.0 kg
1.2 kg
5~10 m
10~15 m (a)
15~20 m (a)
refrigerant1.5
amount
0.5 kg Additional
1.0 kg
kg (R) 2.0 kg
L4=17 m
(Ø6.4 mm)
L1=5 m (Ø9.5 mm)
RZQG125
G2 Total Ø6.4 => G2=7+5=12 m
2 Case: G1>30 m
Additional
refrigerant
(R)
R1
Length=G1−30
m=5amount
m
Case: Twin,
=> standard
R1=0.5 kgliquid pipe size
1 R2
G1 Length=G2=12
Total Ø9.5 =>mG1=35 m
G2 =>
Total
Ø6.4kg
=> G2=7+5=12 m
R2=0.6
kg
23 RCase:R=R1+R2=0.5+0.6=1.1
G1>30 m
Case:R1
Triple,
standard liquidm=5
pipemsize
Length=G1−30
1 G1 Total
Ø9.5 =>
=> R1=0.5
kgG1=5 m
G2 Total Ø6.4 => G2=20+17+17=54 m
R2 Length=G2=12 m
2 Case: G1≤30 m (and G1+G2>30 m)
=> R2=0.6 kg
R1 R1=0.0 kg
3 R
R=R1+R2=0.5+0.6=1.1 kg
R2 Length=G1+G2−30 m=5+54−30=
Case: Triple,
29 mstandard liquid pipe size
1 G1 =>
Total
Ø9.5kg
=> G1=5 m
R2=0.9
Total Ø6.4 => G2=20+17+17=54
m
3 RG2 R=R1+R2=0.0+0.9=0.9
kg
2 Case: G1≤30 m (and G1+G2>30 m)
R1 R1=0.0 kg
R2 Length=G1+G2−30 m=5+54−30=
29 m
=> R2=0.9 kg
50~60 m (a) 60~75 m (a)
RZQG71~140L_V1+Y1
+ RZQSG100~140L_V1+Y1
L1 (size-up):
15~20
m 20~25 m 25~30 m
Split system air conditioners
0.5 kg
0.3
kg
3 R
L1 (m)
L1 (standard):
1.2 kg
1 G1 Total Ø9.5 => G1=35 m
Determine
L3=5 m the additional refrigerant amount: R=R1+R2.
Layout
You do not have to add
additional
refrigerant.
You must
add additional
below.
0.9 kg
L2=7 m
Case: Twin, standard liquid pipe size
(a) Only for RZQG100~140.
(Ø6.4 mm)
L2=7 m RZQG100
(Ø6.4 mm)
Then
▪ 30 m (standard)
2.0 kg
Length
L1=35 m (Ø9.5 mm)
Chargeless length=
To determine
adding additional refrigerant is necessary
▪ 10 mif(size-down)
5~10
m
1.0 kg
0~5 m
(Ø6.4 mm)
▪ 10 m (size-down)
30~45 m
1.5 kg
Determine the additional refrigerant amount: R=R1+R2.
Examples
amount
For future servicing, encircle the
selected amount in the tables
below.
20~30 m
In case of size-up liquid pipe size:
Layout
R1, R2:
Then
refrigerant.
1.0 kg
Only for RZQG100~140.
Examples
(L1+L2+L3+L4+L5+L6+L7)≤
You do not have to add
To determine the additional
refrigerant
chargeless length
additional refrigerant.
chargeless
length
Chargeless
length=
10~20 m
0.5 kg
0~5kg
m
0.5
R1, R2:
Main piping
Branch piping
To determine
the additional
refrigerant
Height
difference between
the highest indoor
unit and the
amount
outdoor
unit
H2 Height difference between the highest and the lowest
To determine
if adding
indoor
unit additional refrigerant is necessary
Refrigerant branch kit
(L1+L2+L3+L4+L5+L6+L7)≤
▪ 15 m (size-up)
chargeless
length
(L1+L2+L3+L4+L5+L6+L7)>
0~10 m
In case of size-up: Replace 30 m by 15 m.
R1:
In case of size-up liquid pipe size: Length
0~10 m
10~20 Length
m
20~30 m
L1
L2~L7
If
▪ 30 m (standard)
Use the
table below to determine
Length
R2 (length= G1+G2−30
m ) (a) . (a)
(a)
(a)
0.3 kgliquid pipe
0.6 size:
kg
In case of R2:
standard
3.4.2H1
If
R1=0.0 kg.
In case of standard liquid pipe size:
L7
L6
H1
(a)
Usethe
thetable
tablebelow
below
determine
Use
toto
determine
(a)
R2
. R2
R1(length=
(length=G1+G2−30
G1−30 m m) (a)) and
(length=G2
). m.
In case of size-up: Replace
30 m by 15
(a)
G1≤30 m (a)
L1
L4
Then
R1=0.0 kg.
G1>30
m (a)
(and G1+G2>30
m)
Double twin (a)
L4
Then
R1 (length= G1−30 m ) (a) and R2
(length=G2 ).
Determine R1 and R2.
L4
L2
H2
Triple (a)
L2
If
G2
(m)
Total length of Ø6.4
mm liquid piping
Use the table below to determine
G1>30 m (a)
H2
H1
H1
Total
of <x>
piping
Total length of
Ø6.4liquid
mm liquid
piping
x=Ø12.7 mm (size-up)
Double twin (a)
L3
H1
2
L3
L2
3.4.2
x=Ø12.7 mm (size-up)
G1
G2(m)
(m)
L1L2
Triple (a)
L1
Determine G1 and G2.
H2
Definitions: L1~L7, H1, H2
x=Ø9.5 mm (standard)
1
L2
H1
3.4.1
3 Installation
Determine G1 and G2.
To determine
refrigerant
amount
G1 (m) the additional
Total length
of <x> liquid
piping(R in kg) (in
case of twin, triple and double twin)
Twin (a)
(a)
H2
3.4.1
1
H2
3.4
To determine the additional refrigerant amount (R in kg) (in
case of twin, triple and double twin)
Charging refrigerant
30~35 m (a)
R=R1+R2=0.0+0.9=0.9 kg
121
Installation manual
7
Outdoor Unit
3.4
3 Installation
RZQSG-L3/9V1/L(8)Y1
Pair, Twin, Triple, double twin
Technology and comfort combined for commercial
applications
›› Top efficiency:
›› Energy labels up to A++ (cooling) /A+ (heating) for
RZQG71/100L9V1 + FCQG71/100F
›› compressor that offers substantial efficiency improvements
›› control logic that optimises efficiency at the most frequently
­encountered operating conditions and that optimises the ­auxiliary
modes (when the unit is not active)
›› heat exchangers that optimise the refrigerant flow at the most
frequent operating conditions (temperature and load)
›› via improved nominal performances
›› Re-use of existing R-22 or R-407C technology
RZQSG100-125L3/9V1/L(8)Y1
›› Guarantees operation in both heating and cooling mode
down to -15°C
›› With a gas cooled PCB reliable cooling is guaranteed as it is not
influenced by ambient temperature
›› Maximum piping length up to 50m, minimum piping length is 5m.
›› Outdoor units for pair, twin, triple, double twin application
›› Daikin outdoor units are neat, sturdy and can easily be mounted
on a roof or terrace or simply placed against an outside wall
›› Compatibility with D-BACS
›› Units optimized for seasonal efficiency give an indication on how
efficient an air conditioner operates over an entire heating or
cooling season.
Twin, triple and double twin application
FCQHG-F
capacity class
71
RZQSG71L3V1
FCQG-F
35
50
RZQSG100L8Y1
3
2
RZQSG125L8Y1
4
3
RZQSG140L9V1
RZQSG140LY1
4
3
Refrigerant
Piping connections
Power supply
Current - 50Hz
2
35
50
FDXS-F(9)
60
2
RZQSG100L9V1
Operation range
FFQ-C
71
2
RZQSG125L9V1
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
60
Unit
HeightxWidthxDepth
Unit
Cooling
Nom./Silent operation
Cooling
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
IU - IU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
2
2
RZQSG
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
50
FBQ-D
60
2
3
2
4
3
4
3
71L3V1
770x900x320
67
65
49/47
51
-
R-410A/2.75/5.7/2,087.5
mm
mm
m
m
m
kg/m
m
m
Hz / V
A
35
2
35
FHQ-C
60
71
35
2
3
2
4
3
4
3
2
3
2
3
4
3
100L9V1
125L9V1
990x940x320
72
74
70
53/54/57
58
R-410A/2.9/6.1/2,087.5
1~ / 50 / 220-240
32
50
FAQ-C
60
71
71
2
4
15
20
50
2
2
FNQ-A
35
3
2
4
3
4
3
2
2
2
3
2
4
3
4
3
140L9V1
1,430x940x320
95
54
100L8Y1
125L8Y1
990x940x320
82
69
70
53/54/57
58
49
-15~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
0.5
50
60
2
R-410A/2.9/6.1/2,087.5
3N~ / 50 / 380-415
16
2
140LY1
1,430x940x320
101
69
53/54
R-410A/4.0/8.4/2,087.5
20
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
122
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
RZQSG-L3_9V1
RZQSG71-100L3_9V1
123
Detailed technical drawings
RZQSG71-100L3_9V1
RZQSG71-100L3_9V1
124
Detailed technical drawings
Outdoor Unit
RZQSG71L3V1
125
Detailed technical drawings
RZQSG71L3V1
RZQSG100-125L9V1/L8Y1
126
ECPEN16-100.indd 126
20/05/16 16:10
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
RZQSQ140LY1
127
Detailed technical drawings
RZQSG71L3V1
128
Detailed technical drawings
Outdoor Unit
RZQSG100-140L9V1
129
Detailed technical drawings
RZQSG100-140L9V1
130
RZQ-C
Pair, Twin, Triple, double twin
Packaged system for commercial applications
ʯʯAvailable as 20 and 25kW
ʯʯRe-use of existing R-22 or R-407C technology
Outdoor Unit
ʯʯGuarantees operation in heating mode down to -15°C
ʯʯStandard night quiet mode
ʯʯMaximum piping length up to 100m
ʯʯMaximum installation height difference up to 30m
ʯʯWide range of connectable indoor units
RZQ200-250C
Twin, triple and double twin application
capacity class
RZQ200C
RZQ250C
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
50
4
60
3
4
FCQG-F
71 100
3
2
125
2
FFQ-C
50
60
4
3
4
Unit
HeightxWidthxDepth
Unit
Cooling
Heating
Nom.
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Level difference
IU - OU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
FDXS-F(9)
50
60
4
3
4
RZQ
mm
kg
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
Hz / V
A
50
4
60
3
4
FBQ-D
71 100
3
2
125
50
4
4
60
3
2
FHQ-C
71 100
3
2
125
2
200C
71
3
FUQ-C
100 125
2
2
FAQ-C FDQ-C FNQ-A
71 100 125 50
60
3
2
4
3
2
4
250C
1,680x930x765
183
184
78
78
57
-5.0~46.0
-15.0~15.0
R-410A/8.3/17.3/2,087.5
9.52
R-410A/9.3/19.4/2,087.5
12.7
22.20
100
3N~ / 50 / 380-415
20
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
131
Detailed technical drawings
RZQ-C
RZQ-C
132
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
RZQ-C
RZQ200C
133
Detailed technical drawings
RZQ200-250C
134
Detailed technical drawings
Outdoor Unit
RZQ200-250C
3TW29044-1
RZQ200-250C
3TW29049-3
135
AZQS-B(8)V1/BY1
Pair application
Ideal solution for busy environments and small shops
›› Daikin outdoor units are neat, sturdy and can easily be mounted
on a roof or terrace or simply placed against an outside wall
›› With a gas cooled PCB reliable cooling is guaranteed as it is not
influenced by ambient temperature
›› Outdoor units are fitted with either a swing or scroll compressor,
renowned for low noise and high energy efficiency
›› Exclusively offered for pair applications (capacity from 71 up to 140)
›› Units optimized for seasonal efficiency give an indication on how
efficient an air conditioner operates over an entire heating or
cooling season.
AZQS100-125B8V1/BY1
Pair application
ACQ-D
ABQ-C
capacity class
71
100
125
140
71
AZQS-B(8)V1
v
v
v
v
v
v
v
v
AZQS-BY1
Outdoor unit
Dimensions
Weight
Sound power level
Sound pressure level
Operation range
Refrigerant
Piping connections
Power supply
Current - 50Hz
Unit
HeightxWidthxDepth
Unit
Cooling
Cooling
Nom.
Heating
Nom.
Night quiet mode
Level 1
Min.~Max.
Cooling
Ambient
Min.~Max.
Heating
Ambient
Type/Charge kg-TCO²Eq/GWP
Liquid
OD
Gas
OD
Piping length
OU - IU
Max.
Equivalent
System
Chargeless
Additional refrigerant charge
Level difference
IU - OU
Max.
IU - IU
Max.
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
AZQS
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
mm
mm
m
m
m
kg/m
m
m
Hz / V
A
100
AHQ-C
125
140
71
100
125
140
v
v
v
v
v
v
v
v
v
v
v
v
v
71BV1
770x900x320
67
64
48
50
43
100B8V1
125B8V1
990x940x320
72.8
74.3
70
71
53
54
57
58
R-410A/2.75/5.7/2,087.5
R-410A/2.9/6.1/2,087.5
20
1~ / 50 / 220-240
32
140B8V1
1,430x940x320
94.9
70
53
54
49
-5~46
-15~15.5
R-410A/4.0/8.4/2,087.5
9.52
15.9
50
70
30
See installation manual
30.0
0.5
40
100BY1
125BY1
990x940x320
82
71
54
57
58
140BY1
1,430x940x320
101
70
53
54
R-410A/2.9/6.1/2,087.5
R-410A/4.0/8.4/2,087.5
16
3N~ / 50 / 380-415
20
25
(1) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
136
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
AZQS-B(8)V1
AZQS- B( 8) V1
OFM
Comp
Indoor
ACQ71DV1
ABQ71CV1
AHQ71CV1
ACQ100DV1
ABQ100CV1
AHQ100CV1
ACQ125DV1
ABQ125CV1
AHQ125CV1
ABQ140CV1
AHQ140CV1
ACQ140DV1
ACQ100DV1
ABQ100CV1
AHQ100CV1
ACQ125DV1
ABQ125CV1
AHQ125CV1
ABQ140CV1
AHQ140CV1
ACQ140DV1
Symbols
MCA:
TOCA:
MFA:
MSC:
RLA:
OFM:
IFM:
FLA:
KW:
Outdoor
Hz ~ Power supply Voltage range MCA TOCA MFA MSC RLA
AZQS71B2V1B
AZQS71B2V1B
AZQS71B2V1B
AZQS100B8V1B
AZQS100B8V1B
AZQS100B8V1B
50Hz ~220-240V
AZQS125B8V1B
AZQS125B8V1B
AZQS125B8V1B
AZQS140B8V1B
AZQS140B8V1B
AZQS140B8V1B
AZQS100B7Y1B
AZQS100B7Y1B
AZQS100B7Y1B
AZQS125B7Y1B
3N~50Hz
AZQS125B7Y1B
380-415V
AZQS125B7Y1B
AZQS140B7Y1B
AZQS140B7Y1B
AZQS140B7Y1B
Min. 198V
Max. 264V
Min. 342V
Max. 456V
18.8
19.5
19.2
28.5
28.6
28.9
28.9
31.5
28.9
32.8
30.7
28.9
14.2
14.3
14.6
14.6
17.2
14.6
21.8
19.7
17.9
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
20
20
20
32
32
32
32
32
32
40
32
32
16
16
16
16
20
16
25
20
20
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
16.2
16.2
16.2
24.4
24.4
24.4
24.4
24.4
24.4
24.2
24.2
24.2
11.4
11.4
11.4
11.4
11.4
11.4
14.2
14.2
14.2
KW
0.07
0.07
0.07
0.2
0.2
0.2
0.2
0.2
0.2
0.094+0.094
0.094+0.094
0.094+0.094
0.2
0.2
0.2
0.2
0.2
0.2
0.094+0.094
0.094+0.094
0.094+0.094
IFM
FLA
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
0.6
0.4+0.4
0.4+0.4
0.4+0.4
0.6
0.6
0.6
0.6
0.6
0.6
0.4+0.4
0.4+0.4
0.4+0.4
kW
FLA
0.067 0.52
0.128 1.05
0.106 0.8
0.094 0.77
0.109 0.9
0.149 1.12
0.137 1.12
0.413 3.16
0.240 1.1
0.546 4.23
0.316 2.52
0.137 1.12
0.094 0.77
0.109 0.9
0.149 1.12
0.137 1.12
0.413 3.16
0.240 1.10
0.546 4.23
0.316 2.52
0.137 1.12
Outdoor Unit
AZQS- BY1
Minimum Circuit Ampere (A)
Total overcurrent amps [A]
Maximum Fuse Ampere (A)
Maximum current of the starting compressor [A]
Rated load amps [A]
Outdoor fan motor
Indoor fan motor
Full load amps
Fan motor rated output [kW]
Notes
1. The RLA is based on the following conditions.
Cooling
Indoor temperature 27.0°C DB / 19.0°C WB
Outdoor temperature 35.0°C DB
Heating
Indoor temperature 20.0°C DB
Outdoor temperature 7.0°C DB / 6.0°C WB
2. TOCA is the total value of each overcurrent set.
3. Voltage range
The units are suitable for use with electrical systems in which the voltage supplied to the unit ter
4. The maximum allowable voltage that is unbalanced between phases is 2%.
5. MCA is the maximum input current.
The capacity of the MFA must be greater than that of the MCA.
Select the MFA according to the table.
The next lower standard fuse rating is minimum 15 ampere.
6. Select the wire size according to the MCA.
7. MFA is used to select the circuit breaker and the ground fault circuit interruptor.
Earth leakage circuit breaker __________
minals is not below or above the listed range limits.
3D090681B
AZQS71B2V1
137
Detailed technical drawings
AZQS100-125B8V1/BY1
AZQS140B8V1/BY1
138
Detailed technical drawings
Outdoor Unit
AZQS-B8V1/BY1
139
Detailed technical drawings
AZQS-B8V1/BY1
140
Make all applications
possible
Outdoor Unit
Multi model applications
• All indoor units can be individually controlled and do not need to be
installed in the same room.
• Combine different types of indoor units: wall mounted, floor standing,
ceiling suspended, round flow cassette, concealed ceiling.
• Phased installation possible.
MXS
RXYS(C)Q
›› A very wide range is available, from 2-port
to 5-port units, making all applications possible.
›› Up to 5 indoor units can be connected to
1 multi outdoor unit.
›› Outdoor multi split units are fitted with
the Daikin swing compressor, renowned for its low
noise and high energy efficiency.
›› The outdoor units are neat and sturdy and can be
mounted easily on a roof or terrace or simply placed
against an outside wall.
›› Up to 9 indoor units can be connected
to 1 VRV outdoor unit
›› Maximum total piping length of 145m offers
much more flexibility in the choice of installation
position
Installation flexibility
Installation flexibility
BP
BP
BP Refnet
5MXS90E
RXYSQ4-6TV1
141
MXS-E/F/G/H/K
Multi model application
›› Outdoor units for multi model application.
›› Outdoor units are fitted with a swing compressor, renowned for its
low noise and high energy efficiency
›› Up to 5 indoor units can be connected to 1 multi outdoor unit;
all indoor units are individually controllable and do not need to
be installed in the same room or at the same time; they operate
simultaneously within the same cooling or heating mode
›› Different types of indoor units can be connected: e.g. wall mounted, ceiling mounted cassette corner, concealed ceiling unit
3MXS52E/4MXS68E
5MXS90E
Wall mounted
CONNECTABLE
INDOOR UNITS
FTXG-L
CTXS-K
FTXS-K
Floor standing
FTXS-G
FTX-J3
FTX-KV
FVXG-K
FVXS-F
2MXS40-50H
Flexi type
Round
flow
cassette
Fully flat
cassette
FLXS-B(9)
FCQG-F
FFQ-C
Concealed ceiling
FDBQ-B/
FBQ-D
FDXS-F(9)
Ceiling
suspended
Concealed
floor
standing
FHQ-C
FNQ-A
20 25 35 50 15 35 20 25 35 42 50 60 71 20 25 35 20 25 35 25 35 50 25 35 50 25 35 50 60 35 50 60 25 35 50 60 25 35 50 60 25 35 50 60 35 50 60 25 35 50 60
2MXS40H
2MXS50H
3MXS40K
3MXS52E
3MXS68G
4MXS68F
4MXS80E
5MXS90E
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• •
•
• •
• •
• •
• •
• •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
• •
•
•
•
•
•
•
•
•
•
•
• • • • • • •
• • • • • • •
•
•
•
•
•
•
• •
•
• •
•
•
•
•
•
•
•
•
•
• • •
• • •
• •
• • •
• • •
• • •
• • •
• • •
•
• •
•
• •
• •
• •
• •
• •
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Note : blue cells contain preliminary data
Outdoor unit
Dimensions
Weight
Sound power level
Unit
HeightxWidthxDepth
Unit
Cooling
Heating
Sound pressure level Cooling
Nom.
Heating
Nom.
Min.~Max.
Operation range
Cooling
Ambient
Min.~Max.
Heating
Ambient
Refrigerant
Type/Charge kg-TCO²Eq/GWP
Piping connections
Power supply
Current - 50Hz
142
Liquid
Gas
OD
OD
Piping length
OU - IU
Additional refrigerant charge
Level difference
IU - OU
IU - IU
Phase / Frequency / Voltage
Maximum fuse amps (MFA)
Max.
Max.
Max.
mm
kg
dBA
dBA
dBA
dBA
°CDB
°CWB
2MXS40H
2MXS50H
550x765x285
38
42
62
63
47
48
48
50
10~46
R-410A/1.20/ R-410A/1.60/
2.5/2,087.5
3.3/2,087.5
mm
6.35x2
mm
9.52x1
12.7x1
m
kg/m
m
m
Hz / V
A
20
0.02 (for piping length exceeding 20m)
1~ / 50 / 220-240
16
3MXS40K
3MXS52E
3MXS68G
735x936x300
49
59
60
46
47
4MXS68F
4MXS80E
5MXS90E
770x900x320
72
73
62
66
58
61
48
49
52
52
-10~46
-15~18
R-410A/2.59/ R-410A/2.6/
R-410A/2.0/
R-410A/2.99/6.2/2,087.5
5.4/2,087.5
5.4/2,087.5
4.2/2,087.5
6.35x3
6.35x4
6.35x5
9.52x1
9.52x2
9.52x1
9.52x2
9.52x2 12.7x2
12.7x1
12.7x1
9.52x3
12.7x1
12.7x2
15.9x2
15.9x2
25
0.02 (for piping length exceeding 30m)
15
7.5
1~ / 50 / 230
20
•
•
•
•
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
Outdoor Unit
2MXS40H
2MXS50H
143
Detailed technical drawings
3MXS40K
3MXS52E
144
Detailed technical drawings
Outdoor Unit
3MXS68G
3MXS68G2V1B
145
Detailed technical drawings
4MXS68F
4MXS68F2V1B
146
Detailed technical drawings
Outdoor Unit
4MXS68F2V1B
4MXS80E_5MXS90E
147
Detailed technical drawings
2MXS40H
2MXS50H
148
Detailed technical drawings
Outdoor Unit
3MXS40K
3MXS52E
149
ECPEN16-100.indd 149
20/05/16 16:10
Detailed technical drawings
3MXS68G
4MXS68F
150
Detailed technical drawings
Outdoor Unit
4MXS80E
5MXS90E
151
ECPEN16-100.indd 151
20/05/16 16:10
RXYSCQ-TV1
VRV IV S-series compact
heat pump
The most compact VRV
›› Compact & lightweight single fan design makes the unit almost
unnoticeable
›› Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units and
Biddle air curtains
›› Wide range of indoor units: either connect VRV or stylish indoor
units such as Daikin Emura, Nexura ...
›› Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors
›› 3 steps in night quiet mode: step 1: 47 dBA, step 2: 44 dBA, step 3:
41 dBA
›› Possibility to limit peak power consumption between 30 and 80%,
for example during periods with high power demand
›› Contains all standard VRV features
Wall mounted
CONNECTABLE
INDOOR UNITS
FTXG-L
CTXS-K
RXYSCQ-TV1
Floor standing
FTXS-K
FTXS-G
FVXG-K
Round flow
Fully flat cassette
cassette
Flexi type
FVXS-F
FLXS-B(9)
FCQG-F
Ceiling
suspended
Concealed ceiling
FFQ-C
FDXS-F(9)
FDBQ-B /FBQ-D
FHQ-C
20 25 35 50 15 35 20 25 35 42 50 60 71 25 35 50 25 35 50 25 35 50 60 35 50 60 25 35 50 60 25 35 50 60 25 35 50 60 35 50 60
RXYSCQ-TV1
●
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
●
●
●
Nom.
Nom.
Max.
Cooling
Heating
●
●
●
●
●
●
●
Nom.
Nom.
Max.
EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
●
●
●
Branch provider
152
●
●
●
●
●
●
●
●
●
●
●
●
mm
kg
●
●
●
●
●
●
4TV1
4
12.1
12.1
14.2
3.43
3.18
4.14
3.53
3.81
3.43
●
●
●
●
●
●
●
5TV1
5
14.0
14.0
16.0
4.26
3.91
5.00
3.29
3.58
3.20
64 (1)
50
62.5
-
130
mm
kg
m³/min
dBA
dBA
°CDB
°CWB
kg
TCO₂eq
162.5
823x940x460
94
91
68
51
69
52
-5~46
-20~15.5
R-410A
3.7
7.7
2,087.5
9.52
15.9
1~/50/220-240
32
indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%).
BPMKS967B2
Connectable indoor units
Max. indoor unit connectable capacity
Max. connectable combination
Dimensions
Height x Width x Depth
Weight
●
RXYSCQ
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
GWP
Liquid
OD
mm
Gas
OD
mm
Total piping length
System
Actual
m
Power supply
Phase/Frequency/Voltage
Hz/V
Current - 50Hz
Maximum fuse amps (MFA)
A
(1) Actual number of units depends on the indoor unit type (VRV DX
(2) Contains fluorinated greenhouse gases
Piping connections
●
BPMKS967B3
1~2
1~3
14.2
71+71
20.8
60+71+71
180x294x350
7
8
RXYSQ-TV1
VRV IV S-series heat pump
›› Compact & lightweight single fan design makes the unit almost
unnoticeable
›› Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units and
Biddle air curtains
›› Wide range of indoor units: either connect VRV or stylish indoor
units such as Daikin Emura, Nexura ...
›› Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors
›› 3 steps in night quiet mode: step 1: 47 dBA, step 2: 44 dBA, step 3:
41 dBA
›› Possibility to limit peak power consumption between 30 and 80%,
for example during periods with high power demand
›› Contains all standard VRV features
Wall mounted
CONNECTABLE
INDOOR UNITS
FTXG-L
CTXS-K
RXYSQ4-6TV1
Floor standing
FTXS-K
FTXS-G
FVXG-K
Outdoor Unit
Space saving solution without compromising
on efficiency
Round flow
Fully flat cassette
cassette
Flexi type
FVXS-F
FLXS-B(9)
FCQG-F
Ceiling
suspended
Concealed ceiling
FFQ-C
FDXS-F(9)
FDBQ-B /FBQ-D
FHQ-C
20 25 35 50 15 35 20 25 35 42 50 60 71 25 35 50 25 35 50 25 35 50 60 35 50 60 25 35 50 60 25 35 50 60 25 35 50 60 35 50 60
RXYSQ-TV1
●
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
●
●
●
Nom.
Nom.
Max.
Cooling
Heating
●
●
●
●
●
●
●
Nom.
Nom.
Max.
EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
●
●
●
RXYSQ-TV1
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
●
●
●
●
●
●
4TV1
4
12.1
12.1
14.2
3.03
2.68
3.43
4.00
4.52
4.14
50
130
mm
kg
m³/min
dBA
dBA
°CDB
°CWB
68
50
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
5TV1
5
14.0
14.0
16.0
3.73
3.27
4.09
3.75
4.28
3.91
64 (1)
62.5
162.5
1,345x900x320
104
106
69
●
●
●
●
●
●
6TV1
6
15.5
15.5
18.0
4.56
3.97
5.25
3.40
3.90
3.43
70
182
70
51
-5~46
-20~15.5
R-410A
3.6
7.5
2,087.5
9.52
kg
TCO₂eq
GWP
Liquid
OD
mm
Gas
OD
mm
15.9
19.1
Total piping length
System
Actual
m
Power supply
Phase/Frequency/Voltage
Hz/V
1N~/50/220-240
Current - 50Hz
Maximum fuse amps (MFA)
A
32
(1) Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%).
(2) Contains fluorinated greenhouse gases
Piping connections
Branch provider
BPMKS967B2
Connectable indoor units
Max. indoor unit connectable capacity
Max. connectable combination
Dimensions
Height x Width x Depth
Weight
mm
kg
BPMKS967B3
1~2
1~3
14.2
71+71
20.8
60+71+71
180x294x350
7
8
153
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
RXYCSQ-TV1
RXYCSQ- TV1
4 holes for anchor bolts
1
Gas pipe connection Ø15.9 flare
2
Liquid pipe connection Ø9.5 flare
3
Service port (in the unit)
4
Grounding terminal
Inside of the switch box (M5)
5
Refrigerant piping intake (knockout hole)
6
Power supply wiring intake (knockout hole Ø53)
7
Control wiring intake (knockout hole Ø27)
8
Drain pipe connection (outside diameter Ø26)
30
37
52
485
460
30
M12
60
101
170
620
40
150
940
4
2
1
823
3
5
88
19
100
151
6
7
8
69
19
80
17
62 59 118 102
104 17
52
53 95
60
53 95
289
313
5
5
20
216
130
21
32
98
89
3D098107
RXYSQ4- 6TV1
RXYSQ-TV1
RXYSQ4- 6TY1
1
4 holes for anchor bolts
140
M12
140
620
Liquid pipe connection Ø9.5 flare
3
(2X) Service port (in the unit)
4
Electronic connection and grounding terminal M5 (in the switch box)
5
320
30
350
(345~355)
Gas pipe connection A
2
Refrigerant piping intake
6
Power supply wiring intake (knockout hole Ø34)
7
Control wiring intake (knockout hole Ø27)
8
Drain outlet
Model
59
43
30
40
94
900
30
Ø19.1 brazed connection
RMXS140E8V1B
Ø19.1 brazed connection
RMXS160E8V1B
Ø19.1 brazed connection
RXYSQ4PA7V1B
4
Ø15.9 flared connection
RXYSQ6PA7V1B
Ø19.1 brazed connection
ERX100A9V1B
2
Ø15.9 flared connection
ERX140A9V1B
Ø19.1 brazed connection
Ø15.9 flared connection
GCA125BD4
Ø15.9 flared connection
GCA140BD4
Ø19.1 brazed connection
RXYSQ4PA7Y1B
7
Ø15.9 flared connection
ERX125A9V1B
GCA100BD4
1
1345
Ø15.9 flared connection
RXYSQ5PA7V1B
3
7
A
RMXS112E8V1B
Ø15.9 flared connection
RXYSQ5PA7Y1B
Ø15.9 flared connection
RXYSQ6PA7Y1B
Ø19.1 brazed connection
5
52
55
6
8
223
148
55
80
13
84
95
19
54
19
89
142
71
54
6
67
5
7
6
145
70
58
102
117
16
16
89
24
95
60
423
430
5
45
5
376
191
Model
A
RA indoor unit
VRV indoor unit
RXYSQ4(P8/T7)V1B
Ø19.1 brazed connection
Ø15.9 flared connection
RXYSQ5(P8/T7)V1B
Ø19.1 brazed connection
Ø15.9 flared connection
RXYSQ6(P8/T7)V1B
Ø19.1 brazed connection
RXYSQ4(P8/T7)Y1B
Ø19.1 brazed connection
Ø15.9 flared connection
RXYSQ5(P8/T7)Y1B
Ø19.1 brazed connection
Ø15.9 flared connection
RXYSQ6(P8/T7)Y1B
Ø19.1 brazed connection
3TW30374-1D
154
Detailed technical drawings
Outdoor Unit
RXYSCQ-TV1
155
Detailed technical drawings
RXYSCQ-TV1
156
Detailed technical drawings
Outdoor Unit
RXYSQ-TV1 / / RXYSQ4-6TY1
157
Detailed technical drawings
RXYSQ-TV1 / / RXYSQ4-6TY1
158
ARGUE CARDS
i
Find out more in the VRV catalogue
Outdoor Unit
VRV IV heat pump
for indoor installation
Unique
concept with
SB.RKXYQ-T
Keep looking
you’ll never find me
5
patents
Invisible
You can install highly efficient,
reliable Daikin air conditioning systems in
the most demanding locations while remaining
invisible from street level.
Unique split outdoor unit
Invisible
›› Completely invisible only the grilles are visible
›› Seamless integration into surrounding architecture
›› Highly suited to densely populated areas
thanks to the low operation sound
Intuitive
›› Total flexibility as the outdoor unit is
split up in 2 parts
›› Easy and quick to transport and install by just
2 persons
›› Easy servicability, all components can be easily
reached
Intelligent
›› Patented V-shape heat exchanger
for the most compact unit (400 mm high) ever
›› Connectable to all VRV indoor units
›› Provides a total solution when combined with
ventilation units, Biddle air curtains and controls
Total solution
22
159
Biddle air curtains
Biddle air curtains provide highly efficient
solutions for retailers and consultants to
combat the issue of climate separation across
their outlet or office doorway.
160
Biddle air curtains
Biddle air curtains
Biddle air curtains
162
Highly efficient solution
for doorway climate separation
CYQS/M/L-DK-F/C/R
166
161
Biddle air curtains
Outdoor units portfolio for connection
to Biddle air curtains
System
Type
Product name
Condensing units
71
ERQ-AV1 1
- High efficiency
Condensing Units
- High comfort levels
Air cooled
Heat pump
100
125
140



- Maximize installation flexibility by
ERQ-AW1
Condensing Units offering 4 types of control systems

1) Only use the condensing units in combinations with an air handling unit.
Biddle air curtain portfolio
3.0m
3
2.3m
2.75m
2.5m
2.4m
2.3m
2.15m
2.5m
2.0m
2
1
S
Installation condition
M
L
S
M
L
S
M
L
Favourable
Normal
Unfavourable
ex: covered shopping mall or
ex: little direct wind, no
ex: location at a corner or
revolving door entrance
opposite open doors, building
square, multiple floors and / or
with ground floor only
open stairwell
Type
Product name
Biddle standard air curtain
free hanging
CYQ S/M/L-DK-F
Biddle standard
air curtain cassette
CYQ S/M/L-DK-C
Biddle standard
air curtain recessed
CYQ S/M/L-DK-R
162
250


- Easy design and installation
1
Door height (m)
200
Features
- CYQ - Biddle air curtain for connection to ERQ
- Connectable to ERQ heat pump
- Cassette model (C): mounted into a false ceiling leaving only the decoration
panel visible
- Free-hanging model (F): easy wall mounted installation
- Recessed model (R): neatly conceiled in the ceiling
- A payback period of less than 1.5 years compared to installing an electric air curtain
- Easy and quick to install at reduced costs since no additional water systems,
boilers and gas connections are required
Biddle air curtains
Biddle Air Curtain Range with heat pumps
Free hanging
Designed to be fitted as close to the top of the door
as practically possible for optimum performance.
›› Easy to install either to façade or via drop rods
to ceiling
›› No maintenance issues due to easy access
›› Range of brackets to suit application
Cassette
Designed for installation above false ceiling, contains
inlet and discharge grills in one unit.
Biddle air curtains
›› Fitted in roof tiles as one complete unit
›› When specifying take into account distance from
discharge grill to floor
›› Install can be challenging due to the need to cut
and remove ceiling tiles
›› Easy maintenance due to access from underneath
Recessed
Designed for integration into false ceiling or into
a bulkhead, with the inlet opening possibly at some
distance from the unit.
›› Use of ductwork in standard bulkhead to deliver air
to fans (contractor to provide)
›› Most difficult to install due to work required for
cutting and fixing in ceiling space
›› Maintenance requires access panels the full width
of unit
163
Biddle air curtains
Benefits of Biddle air curtains
Saves energy by preventing heat loss through an open door
Provides climate separation(temperature, Humidity, fumes and dust)
Improves comfort - heated airstream will condition any draughts entering
through the protected doorway
Studies have shown that an open door increases retail trade
Quick payback of less than 2 years
Unique rectifier technology
Rectifier technology
By reducing the air turbulence at the discharge of
the Biddle air curtain, the induction of
the surrounding air is also reduced, providing
a deeply penetrating airstream. In addition the design
of the rectifier provides a laminar air flow right down
to floor level, reducing energy consumption and
increasing comfort levels all year round.
Rectifier technology
Air curtain, with turbulent air stream and
loss of airflow – low separation efficiency
164
Biddle air curtain connected to Daikin heat pump with patented rectifier grille – separation efficiency up to 80-85%
Biddle air curtains
Short pay back time
Electric air curtain
90
80
72%
more
efficient
Electric air
curtain
60
40
20
0
Total cost
(installation + running cost) in €
Cost per kW of heating (€)
100
Daikin heat
pump with
Biddle
air curtain*
12000
10000
8000
6000
Daikin heat pump
with Biddle air curtain*
4000
2000
0
years
1
2
* Payback period and gains calculated based upon the following: Air curtain is 9hrs/
day – 156 days/year (1,404 hrs/year) in use.
Annual energy consumption for an electric air curtain: 3,137EUR (COP = 0.95).
Typical installation cost: 1,000EUR; Typical equipment cost: 2,793EUR.
Annual energy consumption for CYQS200DK100FBN and ERQ100AV: 748EUR (COP
4.00). Typical installation cost: 2,000EUR; Typical equipment cost: 5,150EUR.
Calculation based upon electricity cost: 0,1705EUR /kWh.
Biddle air curtains
Selection of a Biddle air curtains
An air curtain is selected properly if it has sufficient
capacity to heat up entering cold outside air to
a comfortable temperature. Additionally, the unit must
be able to properly screen off the entire width and
height of the door opening. The air curtain type to be
selected depands on:
1. The door height (=mounting height,
measured from floor to bottom of unit)
2.The door width
3.The volume and temperature
of the outside air entering through the open door
1. Door height and 2. door width
It is importantfor the distance between the air curtain
and the door to be as short as possible. In addition, the
air curtain must be at least as wide as the door opening,
as too narrow an air curtain will lead to air leakages on
the sides.
2.
3. Entering cold air through natural
ventilation
In practice, the volume and temperature of entering
outside air are difficult to determine, as conditions near
a door vary continuously. Other aspects, such as floors
with open connections, multiple open doors in a single
room, or the orientation of the building, may also have a
large influence on the capacity need. To make selection
easy, the following guidelines may be used:
›› Favorable conditions: covered shopping mall or revolving-door entrance.
›› Normal conditions: little direct wint, no open doors,
building with ground floor only
›› Unfavorable conditions: location at a corner or square,
multiple floors and/or open stairwell.
2.
1.
Correct door height and width installation
›› To prevent air leakages on the sides, the air curtain must be at least as
wide as the door opening.
165
CYQS/M/L-DK-F/C/R
Biddle air curtain for ERQ
›› Connectable to ERQ heat pump
›› ERQ is among the first DX systems suitable for connection to air
curtains
›› Free-hanging model (F): easy wall mounted installation
›› Cassette model (C): mounted into a false ceiling leaving only the
decoration panel visible
›› Recessed model (R): neatly concealed in the ceiling
›› A payback period of less then 1.5 years compared to installing an
electric air curtain
›› Easy and quick to install at reduced costs since no additional water
systems, boilers and gas connections are required
›› Maximum energy efficiency stemming from almost zero down flow
turbulence, optimised air flow and the application of advanced
discharge rectifier technology
›› Around 85% air separation efficiency, greatly reducing both heat
loss and required indoor unit heating capacity
CYQM150DK80FSN
CYQM150DK80CSN
CYQM150DK80RSN
Small
Heating capacity
Power input
Delta T
Casing
Dimensions
Speed 3
Fan only
Heating
Speed 3
Colour
Unit
Nom.
Nom.
Height F/C/R
Width F/C/R
Depth F/C/R
Required ceiling void >
Door height
Max.
Door width
Max.
Weight
Unit
Fan-Air flow rate
Heating
Speed 3
Sound pressure level
Heating
Speed 3
Refrigerant
Type / GWP
Piping connections
Liquid/OD/Gas/OD
Required accessories (should be ordered separately)
Power supply
Voltage
kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m³/h
dBA
mm
V
Medium
CYQS150DK80
*BN/*SN
CYQS200DK100
*BN/*SN
CYQS250DK140
*BN/*SN
9.0
0.35
0.35
11.6
0.46
0.46
16.2
0.58
0.58
16
CYQM100DK80
*BN/*SN
CYQM150DK80
*BN/*SN
CYQM200DK100
*BN/*SN
9.2
11.0
13.4
0.37
0.56
0.75
0.37
0.56
0.75
15
17
14
13
BN: RAL9010 / SN: RAL9006
270/270/270
1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048
590/821/561
420
2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3)
1.5
2.0
2.5
1.0
1.5
2.0
66
83
107
57
73
94
1,746
2,328
2,910
1,605
2,408
3,210
49
50
51
50
51
53
R-410A / 2,087.5
9.52/16.0
9.52/19.0
9.52/16.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230
CYQM250DK140
*BN/*SN
19.9
0.94
0.94
15
2,500/2,500/2,548
2.5 (1) / 2.4 (2) / 2.3 (3)
2.5
108
4,013
54
9.52/19.0
Large
Heating capacity
Power input
Delta T
Casing
Dimensions
Speed 3
Fan only
Heating
Speed 3
Colour
Unit
Nom.
Nom.
Height F/C/R
Width F/C/R
Depth F/C/R
Required ceiling void >
Door height
Max.
Door width
Max.
Weight
Unit
Fan-Air flow rate
Heating
Speed 3
Sound pressure level
Heating
Speed 3
Refrigerant
Type / GWP
Piping connections
Liquid/OD/Gas/OD
Required accessories (should be ordered separately)
Power supply
Voltage
kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m³/h
dBA
mm
V
CYQL100DK125
*BN/*SN
CYQL150DK200
*BN/*SN
15.6
0.75
0.75
23.3
1.13
1.13
CYQL200DK250
*BN/*SN
CYQL250DK250
*BN/*SN
29.4
31.1
1.50
1.88
1.50
1.88
15
14
12
BN: RAL9010 / SN: RAL9006
370/370/370
1,000/1,000/1,048
1,500/1,500/1,548
2,000/2,000/2,048
2,500/2,500/2,548
774/1,105/745
520
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
1.0
1.5
2.0
2.5
76
100
126
157
3,100
4,650
6,200
7,750
53
54
56
57
R-410A / 2,087.5
9.52/16.0
9.52/19.0
9.52/22.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230
(1) Favorable conditions: covered shopping mall or revolving door entrance (2) Normal conditions: little direct wind, no opposite open doors, building with ground floor only (3) Unfavorable conditions: location
at a corner or square, multiple floors and/or open stairway
166
Ventilation
Heat Reclaim ventilation
169
Modulates the temperature
and humidity of incoming fresh air
170
172
Air Handling unit applications
182
Ventilation
VAM-FC
VH - electrical heater
Fresh air solution for buildings
with large ventilation requirements
ERQ
Overview & control possibilities
184
187
167
Ventilation
VAM - HEAT RECLAIM VENTILATION
DAIKIN AIR HANDLING UNIT AND ERQ/VRV HEAT PUMP
168
Ventilation
Outdoor units portfolio
for connection to air handling units
System
Type
Product name
Condensing units
71
ERQ-AV1 1
Condensing Units - High efficiency
100
125
140



200
250


- High comfort levels
Air cooled
Heat pump
- Easy design and installation
ERQ-AW1 1
Condensing Units
- Maximize installation flexibility by
offering 4 types of control systems

1) Only use the condensing units in combinations with an air handling unit.
Ventilation portfolio
Ventilation
Five components of indoor air quality
Heat recovery
Humidification
Air
processing
Filtration
Ventilation
›› Ventilation: ensures the provision of fresh air
›› Heat recovery: recovers heat and moisture from the outgoing
air to maximise comfort and efficiency
›› Air processing: heats or cools incoming fresh air maximising comfort and minimizing the load on the air conditioning
installation
›› Humidification: optimises the balance between indoor and
outdoor humidity
›› Filtration: removes dust, pollution and odours from the air
Air flow rate (m3/h)
Type Product name
Model
0
200
400 600
800 1,000 2,000 4,000 10,000 25,000
140,000
Components of
indoor air quality
Air Handling
Unit (application)
Heat reclaim
ventilation
VAM-FC
DX total fresh air
package
› Ventilation
› Energy recovery
Ventilation with heat recovery as standard
›› Energy saving ventilation
›› Maximise floor space for furniture,
decoration and fittings
›› Free cooling
›› Reduced energy consumption
thanks to DC inverter fan motor
›› Optional CO2 sensor saves energy
while improving indoor air quality
Fully customised solution for
ventilation and air handling
›› Inverter technology
›› Heat pump and heat recovery
›› Provides virtually free heating
›› Room temperature via Daikin control
›› Large range of expansion valve kits
(1)
1
› Ventilation
› Energy recovery
› Air processing
› Humidification
› Filtration
Daikin AHU connected to Daikin chiller solution
169
VAM-FC
Heat reclaim ventilation
Clean outdoor air
Total heat
exchanged
foul air
Ventilation with heat recovery as standard
›› Energy saving ventilation using indoor heating, cooling and
moisture recovery
›› Ideal solution for shops, restaurants or offices requiring maxi-
mum floor space for furniture, decorations and fittings
›› Free cooling possible when outdoor temperature is below
indoor temperature (eg. during nighttime)
›› Reduced energy consumption thanks to specially developed DC
Foul indoor air
fan motor
›› Prevent energy losses from over-ventilation while maintaining
indoor air quality with optional CO2 sensor
›› Can be used as stand alone unit or integrated in the VRV system
›› Wide range of units: air flow rate from 150 up to 2,000 m³/h
›› High efficiency filters available in M6 ,F7, F8 grades
›› Shorter installation time thanks to easy adjustment of nominal
air flow rate, so less need for dampers compared with traditional
installation.
›› Specially developed heat exchange element with High Efficiency Paper (HEP)
›› No drain piping needed
›› Can operate in over- and under pressure
›› Total solution for fresh air with Daikin supply of both VAM and
electrical heaters
Total heat
exchanged
clean air
High efficiencies filters available
in M6, F7, F8 grades
Prevent energy losses from over ventilation with CO2 sensor
Enough fresh air is needed to create an enjoyable environment, but ventilating constantly is leading to energy waste. Therefore an optional
CO2 sensor can be installed which throttles or even switches off the ventilation system when there is enough fresh air in the room, thus
saving energy.
Example of CO2 sensor operation in a meeting room:
9 AM
12 PM
5 PM
Decrease in air volume and more energy
saving compared to fixed ventilation rate
Increase in air
volume and
better comfort
compared to fixed
ventilation rate
7
8
9
10
When many people are in the room,
more fresh air is brought in to maintain
comfortable CO2 levels. When fewer
people are in the room, energy is saved
by bringing in less fresh air.
11
Morning meeting
12
13
Lunch time
14
15
16
Meeting
17
18
19
hour
CO2 level
Fixed ventilation rate
Ventilation amount
Using CO2 sensors has the most energy-saving potential in buildings where occupancy fluctuates during a 24-hour period, is unpredictable and peaks at a high level. For example
office buildings, government facilities, retail stores and shopping malls, movie theaters, auditoriums, schools, entertainment clubs and nightclubs. The ventilation unit's reaction to
fluctuations in CO2 can be easily adjusted through a field setting.
170
VAM-FC
Heat recovery ventilation
High Efficiency Paper
efficiency paper.
INDOOR
30.6°C
62% RH
Cross flow of air to
32°C
70% RH
exchange heat and
moisture.
SA
27.4°C
63% RH
RA
26°C
50% RH
Integrally-formed liner
Temperature
and humidity is
exhanged between
the layers
SA
RA
Ventilation
OUTDOOR
Operation of the high
RH: Relative Humidity SA: Supply Air (to room) RA: Return Air (from room)
Ventilation
Power input - 50Hz
Temperature
exchange efficiency
- 50Hz
Enthalpy exchange
efficiency - 50Hz
Heat exchange mode Nom.
Bypass mode
Nom.
Ultra high
High
Low
Cooling
Ultra high
High
Low
Heating
Ultra high
High
Low
Ultra high
Ultra high
Operation mode
Heat exchange system
Heat exchange element
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Heat exchange mode Ultra high
Fan-Air flow rate 50Hz
Bypass mode
Ultra high
Fan-External static
Ultra high/High/Low
pressure - 50Hz
Air filter
Type
Sound pressure level Heat exchange mode Ultra high
- 50Hz
Bypass mode
Ultra high
Operation range
Min./Max.
Relative humidity
Refrigerant
Type / GWP
Connection duct diameter
Power supply
Phase/Frequency/Voltage
Current
Maximum fuse amps (MFA)
VAM
kW
kW
%
%
%
mm
kg
m³/h
m³/h
Pa
dBA
dBA
°CDB
%
mm
Hz/V
A
150FC
0.132
0.132
77.0 (2) / 72.0 (3)
78.3 (2) / 72.3 (3)
82.8 (2) / 73.2 (3)
60.3 (2)
61.9 (2)
67.3 (2)
66.6 (2)
67.9 (2)
72.4 (2)
250FC
0.161
0.161
74.9 (2) / 69.5 (3)
76.0 (2) / 70.0 (3)
80.1 (2) / 72.0 (3)
60.3 (2)
61.2 (2)
64.5 (2)
66.6 (2)
67.4 (2)
70.7 (2)
350FC
500FC
650FC
800FC
1000FC
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
78.0 (2) / 71.6 (3) 77.0 (2) / 70.2 (3) 77.0 (2) / 69.8 (3) 77.0 (2) / 67.8 (3) 78.0 (2) / 70.2 (3)
79.3 (2) / 71.9 (3) 78.8 (2) / 70.7 (3) 79.1 (2) / 71.2 (3) 78.2 (2) / 68.8 (3) 78.6 (2) / 71.1 (3)
84.1 (2) / 73.0 (3) 80.9 (2) / 71.3 (3) 81.1 (2) / 72.9 (3) 79.1 (2) / 69.6 (3) 80.2 (2) / 73.4 (3)
63.4 (2)
60.3 (2)
60.3 (2)
62.4 (2)
63.4 (2)
65.0 (2)
63.4 (2)
64.0 (2)
63.6 (2)
64.2 (2)
70.7 (2)
66.9 (2)
67.3 (2)
64.6 (2)
66.3 (2)
67.6 (2)
64.5 (2)
65.5 (2)
67.6 (2)
68.6 (2)
68.9 (2)
67.6 (2)
67.7 (2)
68.8 (2)
69.4 (2)
73.7 (2)
71.1 (2)
69.7 (2)
69.8 (2)
71.5 (2)
Heat exchange mode, bypass mode, fresh-up mode
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
364x1,000x1,160
285x776x525
301x828x816
364x1,000x868
24.0
33.0
51.0
54.0
63.0
Galvanised steel plate
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
90 (4)/87 (4) 70 (4)/63 (4) 103 (1)/93 (1) 83 (1)/57 (1) 100 (1)/73 (1) 109 (1)/94 (1) 147 (1)/135 (1)
40 (4)
25 (4)
51 (1)
35 (1)
49 (1)
78 (1)
100 (1)
Multidirectional fibrous fleeces
27.0
28.0
32.0
33.0
34.5
36.0
36.0
27.0
28.0
32.0
33.5
34.5
36.0
36.0
-15/50
80% or less
100
150
15
200
1~/50/60/220-240/220
250
1500FC
0.617 (1)
0.617 (1)
78.0 (2) / 69.5 (3)
79.6 (2) / 70.3 (3)
80.8 (2) / 71.0 (3)
63.4 (2)
65.0 (2)
66.2 (2)
68.6 (2)
69.7 (2)
70.5 (2)
2000FC
0.685 (1)
0.685 (1)
78.0 (2) / 70.2 (3)
79.6 (2) / 71.3 (3)
80.6 (2) / 74.6 (3)
63.4 (2)
64.5 (2)
67.8 (2)
68.6 (2)
69.5 (2)
72.1 (2)
726x1,510x868 726x1,510x1,160
128
145
1,500 (1)
2,000 (1)
1,500 (1)
2,000 (1)
116 (1)/97 (1) 132 (1)/118 (1)
80 (1)
77 (1)
39.5
40.5
40.0
40.0
350
16
(1) Measured on fan curve 15. Refer to fan curves. (2) Measured according to JIS B 8628 (3) Measured according to EN308 : 1997 (4) Clean the filter when this icon appears on the controller screen. Regular filter
cleaning is important for delivered air quality and for the unit‘s energy efficiency. (5) In accordance with commission regulation (EU) No 1254/2014 (6) Products with an air flow rate ≤ 250m³/h must comply to
commission regulation (EU) No.1254/2014 for RVU’s, products with an air flow rate > 250m³/h must comply to commission regulation (EU) No.1253/2014 for NRVU’s.
171
VH
Preheater for VAM
›› Total solution for fresh air with Daikin supply of both VAM
and preheaters
›› Increased comfort in low outdoor temperature thanks
to the heated outdoor air
›› Integrated electrical heater concept (no additional accessories
required)
›› Standard dual flow and temperature sensor
›› Flexible setting with adjustable setpoint
›› Increased safety with 2 cut-outs: manual & automatic
›› BMS integration thanks to:
- Volt free relay for error indication
- 0-10VDC input for setpoint control
PREHEATER FOR VAM
Supply voltage
Output current (maximum)
Temperature sensor
Temperature control range
Control fuse
LED indicators
VH
(VH)
220/250V ac 50/60 Hz. +/-10%
19A at 40°C (ambient)
5k ohms at 25°C (table 502 1T)
0 to 40°C / (0-10V 0-100%)
20 x 5mm 250mA
Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red
Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input
98mm x 181mm centres 5 mm ø holes
35°C (during operation)
100°C Pre-set
125°C Pre-set
1A 120V AC or 1A 24V DC
0-10VDC
VH
Capacity
Duct diameter
Connectable VAM
kW
mm
1B
1
100
VAM150FC
-
For the selection of the appropriate capacity, please refer to the VAM selection software.
172
2B
1
150
VAM250FC
VAM350FC
3B
1
200
VAM500FC
VAM650FC
4B
1.5
250
VAM800FC
VAM1000FC
4/AB
2.5
250
VAM800FC
VAM1000FC
5B
2.5
300
VAM1500FC
VAM2000FC
Find all technical drawings on our business portal http://my.daikin.eu
Detailed technical drawings
VAM150FC
Ventilation
VAM250FC
173
Detailed technical drawings
VAM350FC
VAM500FC
174
Detailed technical drawings
VAM650FC
Ventilation
VAM800FC
175
Detailed technical drawings
VAM1000FC
VAM1500FC
176
Detailed technical drawings
VAM2000FC
Ventilation
VAM150FC
177
Detailed technical drawings
VAM250FC
VAM350FC
178
Detailed technical drawings
VAM500FC
Ventilation
VAM650FC
179
Detailed technical drawings
VAM800FC
VAM1000FC
180
Detailed technical drawings
VAM1500FC
Ventilation
VAM2000FC
181
Air handling unit applications
Air handling unit
applications
Wide range of air flows
Professional
›› Pre-configured sizes
›› Tailored to the individual
For applications that require big volumes of treated
fresh air (large atriums, banquet halls, etc)
air handling units represent the ideal solution.
Daikin’s wide range of air handling units treat
air volumes from 500 m³/h up to 144,000 m³/h.
The air handling unit can be designed to deliver
whatever air flow you require, via the specific
dimensions of flow section available
at the installation.
customer
›› Modular construction
Energy
›› High-end solution for optimised
energy consumption
›› High efficiency components
›› Strong Return on Investment
Air flow (m3/h x 1,000)
Professional
Modular
›› Plug & play, with factory
mounted controls
140
›› Pre-configured sizes
›› EC Fan Technology
›› High Efficiency Heat Wheel
›› Compact Design
120
Energy
100
90
80
70
60
50
40
20
0
182
750 m3/h
up to
144,000 m3/h
Modular
750 m /h
up to
100,000 m3/h
3
500m3/h
up to 25,000 m3/h
Ventilation
Dainkin fresh air package - plug & play
The D-AHU Modular series provide a complete solution including
unit control (EKEXV, EKEQ, DDC controller) factory mounted
and configured, plug & play with our VRV and ERQ condensing
units. The easiest solution as you save time and only
have one point of contact!
Return on investment
The air handling unit (AHU) is critical to an effective climate control
system and the savings generated by our advanced designs and
operating efficiencies guarantee a rapid return on the investment
made. Our AHU Energy series has been designed to deliver
exceptional performance thus driving down the energy consumed
and so lowering energy bills. Taken over the expected 15-year
life-span of the equipment, this will result in a substantial saving,
especially in a time of ever increasing energy prices.
Pre-defined sizes
27 fixed sizes are available, optimised to reach the optimum
combination between value for money and manufacturing
standardisation. Daikin’s section by section design means
that units can be sized by 1cm increments and assembled on site,
without welding, to suit the space constraints of the installation.
High efficiency components
All Daikin air handling units have been designed for optimum
energy efficiency. Polyurethane or Mineral wool panels guarantee
excellent thermal insulation performance. And the widest range of
filters are provided to meet even the most strict demands.
183
Air handling unit applications
Why use ERQ condensing units for connection
to air handling units?
High Efficiency
Daikin heat pumps are renowned for their high
energy efficiency. Integrating the AHU with a heat
recovery system is even more effective since
an office system can frequently be in cooling mode
while the outdoor air is too cold to be brought
inside in an unconditioned state. In this case heat
from the offices is merely transferred to heat up
the cold incoming fresh air.
Outside air = 10°C
Fresh air supplied at 21°C.
The temperature difference with
the outdoor air is heated up for free
by heat recovery via A/C system
Indoor temperature 22°C,
needs cooling because of solar
radiation.
The excessive heat can be
transferred to the AHU.
Fast response to changing loads
resulting in high comfort levels
Daikin ERQ units respond rapidly
to fluctuations in supply air temperature, resulting
in a steady indoor temperature and resultant high
comfort levels for the end user. The ultimate is
the VRV range which improves comfort even more
by offering continuous heating, also during defrost.
Easy Design and Installation
The system is easy to design and install since
no additional water systems such as boilers,
tanks and gas connections etc. are required.
This also reduces both the total system investment
and running cost.
Daikin Fresh air package
VRV IV or ERQ condensing unit
Factory fitted and welded
fresh air package
Electronic expansion
184
valve
Control box
(EKEXV)
(EKEQ)
Flexible control possibilities for air handling units
In order to maximise installation flexibility,
4 types of control systems are offered
W control: Off the shelf control of air temperature (supply air
temperature, return air temperature, room temperature) via any
DDC controller, easy to setup
X control: Precise control of air temperature (supply air temperature,
return air temperature, room temperature) requiring
a preprogrammed DDC controller (for special applications)
1. W control (TS/TR/TROOM control):
Air temperature control via DDC controller
Room temperature is controlled as a function of the air handling
unit return air or supply air (customer selection). The DDC controller
is translating the temperature difference between set point
and return air temperature (or supply air temperature or room
temperature) into a proportional 0-10V signal which is transferred
to the Daikin control box (EKEQFCBA). This voltage modulates the
capacity requirements of the outdoor unit.
TTEXT
EXT
Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA
TTRR
TE T
-
C
DDC
DDC
TS
T
S
0-10V
TTEXT
EXT
Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA
By fixed evaporating /condensing temperature
A fixed target evaporating or condensing temperature can be set
by the customer. In this case, room temperature is only indirectly
controlled. A Daikin wired remote control (BRC1D52 or
BRC1E53A/B/C - optional) have to be connected for initial set-up
but not required for operation.
TEXT
+
TE TC
-
TS
T
S
TTROOM
ROOM
TR = Return air temperature
TEXT = Extraction air temperature
TE = Evaporating temperature
Option kit
EKEQFCBA
Possibility Z
EKEQDCB
EKFQMCBA*
Control your AHU just like a VRV indoor unit with 100% fresh air
Allows the possibility to control the AHU just like a VRV indoor
unit. Meaning temperature control will be focused on return air
temperature from the room into the AHU. Requires BRC1D52 or
BRC1E53A/B/C for operation. This the only control that allows
the combination of other indoor units to the AHU at the same time.
AHU
AHU
BRC1D*
BRC1E*
TTEXT
EXT
Control box
box
Control
EKEQMCBA (VRV
EKEQMCBA
(VRVIV)
IV)
EKEQDCB
(ERQ)
EKEQDCB (ERQ)
T
TR
+
T TC
TTOA
OA
OR
OR
TS = Supply air temperature
Possibility W
Possibility X
Possibility Y
TS
T
S
C
4. Z control (TR/TROOM control):
TRR
TTOA
OA
TE T
-
TTROOM
ROOM
3. Y control (TE/TC control):
Control box
Control
box
EKEQFCBA
EKEQFCBA
TTRR
+
TTOA
OA
TTROOM
ROOM
BRC1D*
BRC1D*
BRC1E*
BRC1E*
OR
OR
AHU
AHU
+
TTOA
OA
Precise air temperature control via DDC controller
Room temperature is controlled as a function of the air handling
unit return air or supply air (customer selection). The DDC controller
is translating the temperature difference between set point
and return air temperature (or supply air temperature or room
temperature) into a reference voltage (0-10V) which is transferred
to the Daikin control box (EKEQFCBA). This reference voltage will be
used as the main input value for the compressor
frequency control.
TOA = Outdoor air temperature
E
-
TS
TTROOM
ROOM
TROOM = Room air temperature
TC = Condensing temperature
Features
Off-the-shelf DDC controller that requires no pre-configuration
Pre-configured DDC controller required
Using fixed evaporating temperature, no set point can be set using remote control
Using Daikin infrared remote control BRC1D52 or BRC1E52A/B
Temperature control using return air temperature or room temperature (via remote sensor)
* EKEQMCB (for ’multi’ application)
185
Ventilation
0-10V
2. X control (TS/TR/TROOM control):
OR
OR
AHU
AHU
DDC
DDC
Z control: Control of air temperature (return air temperature, room
temperature) via Daikin control (no DDC controller needed)
Y control: Control of refrigerant (Te/Tc) temperature via Daikin
control (no DDC controller needed)
ERQ - Air handling application
ERQ - for smaller capacities
(from 100 to 250 class)
A basic fresh air solution for pair application
›› Inverter controlled units
›› Heat pump
›› R-410A
›› Wide range of expansion valve kits available
›› Perfect for the Daikin Modular air handling unit
The “Daikin Fresh Air Package” provides a complete Plug & Play Solution including
AHU, ERQ or VRV Condensing Unit and all unit control (EKEQ, EKEX, DDC controller)
factory mounted and configured. The easiest solution with only one point of contact.
ERQ-AW1
Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m³/min
Heating
Nom.
m³/min
Sound power level Cooling
Nom.
dBA
Sound pressure Cooling
Nom.
dBA
Heating
Nom.
dBA
level
Operation range Cooling
Min./Max.
°CDB
Heating
Min./Max.
°CWB
On coil
Heating Min.
°CDB
°CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Drain
OD
mm
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A
100AV1
125AV1
140AV1
4
11.2
12.5
2.81
2.74
5
14.0
16.0
3.51
3.86
6
15.5
18.0
4.53
4.57
3.42
3.94
Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m³/min
Heating
Nom.
m³/min
Sound power level Nom.
dBA
Sound pressure level Nom.
dBA
Operation range Cooling
Min./Max.
°CDB
Heating
Min./Max.
°CWB
On coil
Heating Min.
°CDB
°CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A
125AW1
200AW1
250AW1
5
14.0
16.0
3.52
4.00
3.98
4.00
1,680x635x765
159
95
95
72
54
8
22.4
25.0
5.22
5.56
4.29
4.50
10
28.0
31.5
7.42
7.70
3.77
4.09
186
3.99
4.56
4.15
1,345x900x320
120
106
102
66
50
52
105
67
51
53
-5/46
-20/15.5
10
35
R-410A / 2.087,5
4.0/8.4
9.52
69
53
55
15.9
19.1
26x3
1N~/50/220-240
32.0
6.2/12.9
15.9
1,680x930x765
187
171
171
240
185
185
78
57
58
-5/43
-20/15
10
35
R-410A / 2.087,5
7.7/16.1
9.52
19.1
8.4/17.5
22.2
3N~/50/400
16
25
Overview of expansion valves and control boxes
Integration of ERQ in third party air handling units
a wide range of expansion valve kits and control boxes
Combination table
Control box
ERQ100
ERQ125
ERQ140
ERQ125
3-phase ERQ200
ERQ250
VRV III
VRV IV H/P /
VRV IV W-series
VRV IV S-series
VRV IV H/R
VRV IV i-series
1-phase
EKEXV50
n1
EKEXV63
P
P
P
n1
EKEXV80
P
P
P
P
n1
EKEXV100
P
P
P
P
P
n1
EKEXV125
P
P
P
P
P
P
n1
EKEXV140
P
P
P
P
P
n1
EKEXV200
P
P
n1
EKEXV250
P
P
n1
EKEXV400
n1
EKEXV500
n1
Mixed connection with
VRV indoor units
Not possible
Mandatory
-
P (1 -> 3)
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
Possible (not
mandatory)
-
-
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
Mandatory
P (pair application): combination depends on the capacity of the air handling unit
n1 (multi application) - Combination of AHUs and VRV DX indoors (mandatory). To determine the exact quantity please refer to the engineering data book.
n2 (multi application) - Combination of AHUs and VRV DX indoors (not mandatory). To determine the exact quantity please refer to the engineering data book.data book
Control box EKEQFA can be connected to some types of VRV IV outdoor units (with a maximum of 3 boxes per unit). Do not combine EKEQFA control boxes with VRV DX indoor units, RA indoor units or hydroboxes
Capacity table
Cooling
EKEXV Class
50
63
80
100
125
140
200
250
400
500
Heating
Allowed heat exchanger capacity (kW)
Minimum
5.0
6.3
7.9
10.0
12.4
15.5
17.7
24.7
35.4
49.6
Standard
5.6
7.1
9.0
11.2
14.0
16.0
22.4
28.0
45.0
56.0
Allowed heat exchanger capacity (kW)
EKEXV Class
Maximum
6.2
7.8
9.9
12.3
15.4
17.6
24.6
30.8
49.5
61.6
Minimum
5.6
7.1
8.9
11.2
13.9
17.4
19.9
27.8
39.8
55.1
50
63
80
100
125
140
200
250
400
500
Saturated evaporating temperature: 6°C, SH: 5K
Air temperature: 27°C DB / 19°C WB
Standard
6.3
8.0
10.0
12.5
16.0
18.0
25.0
31.5
50.0
63.0
Maximum
7.0
8.8
11.1
13.8
17.3
19.8
27.7
34.7
55.0
69.3
Ventilation
•
•
•
•
Expansion valve kit
EKEQDCB EKEQFCBA EKEQMCBA
Z control W,X,Y control Z control
P
P
P
P
P
P
P
P
P
P
P
P
n1
Saturated condensing temperature: 46°C, SC: 3K
Air temperature: 20°C DB
EKEXV - Expansion valve kit for air handling applications
Ventilation
Dimensions
Unit
Weight
Unit
Sound pressure level Nom.
Operation range On coil
Heating Min.
temperature Cooling Max.
Refrigerant
Type / GWP
Piping connections Liquid
OD
EKEXV
mm
kg
dBA
°CDB
°CDB
50
63
80
100
125
140
401x215x78
2.9
45
10 (1)
35 (2)
200
250
400
500
12.7
15.9
R-410A / 2.087,5
mm
6.35
9.52
(1) The temperature of the air entering the coil in heating mode can be reduced to -5°CDB. Contact your local dealer for more information. (2) 45% Relative humidity.
EKEQ - Control box for air handling applications
Ventilation
Application
Outdoor unit
Dimensions
Weight
Power supply
EKEQ
Unit
Unit
Phase/Frequency/Voltage
mm
kg
Hz/V
FCBA
See note
ERQ / VRV
DCB
Pair
ERQ
132x400x200
3.9
MCBA
Multi
VRV
3.6
1~/50/230
The combination of EKEQFCBA and ERQ is in pair application. The EKEQFCBA can be connected to some type of VRV IV outdoor units with a maximum of 3 control boxes. The combination with DX indoor units,
hydroboxes, RA outdoor units, ... is not allowed. Refer to the combination table drawing of the outdoor unit for details.
187
Market leading
controls for 2016
Intuitive & user-friendly interface
Cross pillar integration
Cloud control
Smart energy management
Integration of Daikin and third party products
Mini BMS for medium
to large commercial buildings
›› Price competitive mini BMS
›› Cross-pillar integation of Daikin products
›› Integration of third party equipment
via WAGO or BACnet/IP
›› Connect up to 512 indoor units groups
more information on page 200
DCC601A51
Advanced centralised controller
with Cloud connection
›› Simply control your entire building centrally
›› Total solution concept (integration of Split, Sky Air, VRV, ventilation,
air curtains and hot water)
›› Stylish optional screen fits any interior
›› Cloud connection offers additional services
such as online control, energy monitoring, comparison of energy
consumption of multiple sites
›› Connect up to 32 indoor units
more information on page „Advanced centralised
controller with Cloud connection“ on page 198
Find out more on www.daikineurope.com
188
Control
Systems
Control Systems
Requirements tables per application Individual control systems
Wired / infrared remote controls
190
190
194
194
Centralised control systems
196
Centralised remote control /
Unified ON/OFF control / Schedule timer 196
Adapter DTA113B51
197
197
Advanced centralised controller
with Cloud connection
198
Mini building management system
200
200
Standard protocol interfaces
Modbus interface
RTD-20 Retail Economiser
DIII-net Modbus interface
KNX Interface
202
202
202
204
205
Wireless room temperature sensor
Wired room temperature sensor
Other integration devices
206
206
205
207
Control Systems
Options & Accessories Find out more about our control systems online:
www.daikineurope.com/commercial/needs/controls
189
Requirements tables per application
Requirement tables per application
Daikin offers various control solution adapted to the requirements of even the most
demanding commercial application.
›› Basic control solutions for those customers with few
requirements and limited budget
›› Integrating control solutions for those customers
that would like to integrate Daikin units into their
existing BMS system
›› Advanced control solutions for those customers
Shop
that expect Daikin to deliver a mini BMS solution,
including advance energy management
NEW
Unit control
BRC1E52A/B
BRC1E53A/B/C
Automatic control of A/C
Limited control possibilities for shop staff
Integrating control
RTD-20
1 remote
controller for
1 indoor unit
(group)
1 gateway for
1 indoor unit
(group)






Create zones within the shop
Interlock with eg. Alarm, PIR sensor
RTD-Net
KLIC-DI
Advanced control
EKMBDXA
1 gateway for 1 1 gateway for 1 1 gateway for
indoor unit
indoor unit
max. 64 indoor
(group)
unit(s) (groups)
& 10 outdoors




DCM601A51
1 unit for 32
indoor unit(s)
1 iTM for 64
indoor unit(s)
(groups) (1)











Integrate Daikin units into existing BMS via Modbus
DCC601A51


Integrate Daikin units into existing BMS via KNX

(2)
(2)

Integrate Daikin units into existing BMS via HTTP
Monitor energy consumption
Advanced energy management
Allows free cooling






Integrate Daikin products cross pillars
into Daikin BMS

(2)
(2)
Integrate third party products into Daikin BMS
Online control
Manage multiple sites
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via cloud control
Hotel
Unit control
BRC2/3E52C
Integrating control
RTD-Net
1 remote controller
1 gateway for 1
for 1 indoor unit
indoor unit (group)
(group)
Hotel guest can control & monitor basic functionalities from his room
Limited control possibilities for hotel guests
Interlock with window contact
Interlock with key-card
Integrate Daikin units into existing BMS via Modbus


(2)
(2)


DCS601C51
DCM601A51
1 gateway for 1
indoor unit
1 iTC for 64 indoor
unit(s) (groups)
1 iTM for 64 indoor
unit(s) (groups) (1)









Integrate Daikin units into existing BMS via KNX
Integrate Daikin units into existing BMS via HTTP
Monitor energy consumption
Advanced energy management
Integrate Daikin products cross pillars into Daikin BMS
Integrate third party products into Daikin BMS
Online control
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via BRP7A51 adapter
190
Advanced control
KLIC-DI







Requirements tables per application
Office
Unit control
BRC1E52A/B
BRC1E53A/B/C
1 remote
controller for
1 indoor unit
(group)
Automatic control of A/C

Centralised control for management
Local control for office workers
Limited control possibilities for office workers


Integrating control
EKMBDXA
DMS504B51
Advanced control
DMS502A51 /
DAM412B51
1 gateway for
1 gateway for
1 R/C for max.
1 gateway for
max. 64 indoor
128 indoor
64 groups, 128
64 indoor unit(s)
unit(s) (groups)
unit(s) (groups), indoor units, 10
(groups)
& 10 outdoors
20 outdoors (2)
outdoors









 (3)


DCS601C51
DCM601A51
1 iTC for 64
indoor unit(s)
(groups)
1 iTM for 64
indoor unit(s)
(groups) (1)









Integrate Daikin units into existing BMS via Modbus

Integrate Daikin units into existing BMS via HTTP

Integrate Daikin units into existing BMS via LonTalk

Integrate Daikin units into existing BMS via BACnet
Energy consumption read out
DCS302C51 /
DST301B51






Monitor energy consumption
Advanced energy management
Integrate Daikin products cross pillars into Daikin
BMS
Integrate third party products into Daikin BMS
Online control
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems)
(2) : extension needed to go to 256 indoor unit(s) (groups), 40 outdoors
(3) : ON/OFF only
NEW
Infrastructure cooling
Automatic control of A/C
Back-up operation
Duty rotation
Limited control possibilities in the infrastructure cooling room
If room temperature above max., then show alarm & start standby
unit.
If an error occurs, an alarm will be shown.
Unit
Integrating
Advanced
BRC1E53A/B/C
RTD-10
DCM601A51
1 remote
controller for
1 indoor unit
(group) (2)
1 gateway for
1 indoor unit
(group)
Up to 8
gateways
can be linked
together
1 iTM for 64
indoor unit(s)
(groups) (1)


















Control Systems
launch Spring
2016
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Infrastructure cooling functions only
compatible with indoor units connected to Seasonal Smart outdoor units.
191
Controllers
ONLINE
CONTROLLER
WIRED REMOTE CONTROL
BRC1E52A
INTELLIGENT
TOUCH MANAGER
DCM601A51
INFRARED REMOTE
CONTROLLER
192
Individual control systems
BRC1E52A/B
User friendly remote control with contemporary design
A series of energy saving functions that
can be individually selected
Graphical display of indicative
electricity consumption
(Function available in
combination with FBQ-D,
FCQG and FCGHQ)
Other functions
›› Up to 3 independent schedules can be set,
so the user can easily change the schedule himself
throughout the year (e.g. Summer, winter, mid-season)
›› Possibility to individually restrict menu functions
Easy to use: all main functions directly accessible
›› Easy setup: clear graphical user interface for
advanced menu settings
›› Real time clock with auto update to daylight
saving time
›› Permanent storage of settings and backup power
for clock for at least 48 hours
›› Supports multiple languages:
English, German, Dutch, Spanish, Italian, Portuguese,
French, Greek, Russian, Turkish, Polish (BRC1E52A)
English, German, Czech, Croatian, Hungarian,
Romanian, Slovenian, Bulgarian, Slovak, Serbian and
Albanian (BRC1E52B)
›› Temperature range limit
›› Setback function
›› Presence & floor sensor connection
(available on round flow and fully flat cassette)
›› kWh indication
›› Set temperature auto reset
›› Off timer
Temperature range limit avoids excessive
heating or cooling
Save energy by constraining the lower temperature
limit in cooling and upper temperature limit in
heating mode.
note : Also available in auto cooling/heating change over mode.
kWh indication keeps track of
your consumption
The kWh indication shows an indicative electricity
consumption of the last day/month/year. 1
1 for Sky Air FBQ-D, FCQG and FCQHG pair combinations only
BRC1E53A/B/C
User friendly remote control incl. infrastructure cooling functions
›› Replaces BRC1E52A/B in Spring 2016 and includes
following additional functionalities:
• Duty rotation and back-up for infrastructure
cooling
• Remote control save mode : screen turns off when
no person is changing mode or adjusting settings
• Demand control: decreases the power
consumption to 70 or 40 % when other large
applicances need to be switched on
• Selection of quiet mode function
for the outdoor unit
›› Choice between symbol or text display
›› Supports multiple languages:
BRC1E53A: English, German, French, Dutch, Spanish,
Italian, Portugese
BRC1E53B: English, Czech, Croation, Hungarian,
Romanian, Slovenian, Bulgarian
BRC1E53C: English, Greek, Russian, Turkish,
Hungarian, Slovak, Albanian
BRC2E52A / BRC3E52A
BRC2E52A
›› Symbol driven interface for intuitive control
›› Functions restricted to basic customer needs
›› Contemporary design
›› Energy saving thanks key card, window contact
integration and set point limitation (BRP7A51)
›› Flexible setback function ensures room temperature
remains within comfortable limits to ensure guest
comfort
Heat recovery type
Key card and
window contact
integration
BRC3E52A
Heat pump type
P1 P2
›› Flat backpanel for easy installation
›› Easy commissioning: intuitive interface
for advanced menu settings
›› 2 versions available:
• Heat pump type: temperature, fan speed, ON/
OFF
• Heat recovery type: temperature, mode, fan
speed, ON/OFF
›› Replaces existing BRC2C51 & BRC3A61
Adaptator
(BRP7A51)
Key card (field supply)
Window contact
(field supply)
193
Control Systems
Simplified wired remote control developed for hotel applications
Individual control systems
BRC1D52
Wired remote control
BRC1D52
›› Schedule timer:
Five day actions can be set as follows:
-- set point: unit is switched ON and normal
operation is maintained
-- OFF: unit is switched OFF1
-- limits: unit is switched ON and min./max. control
(cf. limit operation for more details)
›› Home leave (frost protection): during absence, the
indoor temperature can be maintained at a certain
level. This function can also switch the unit ON/OFF
›› User friendly HRV function, thanks to
the introduction of a button for ventilation mode
and fan speed
›› Immediate display of fault location and condition
›› Reduction of maintenance time and costs
›› Operating mode
›› Heat Recovery Ventilation (HRV) in operation
›› Cool / heat changeover control
›› Centralised control indication
›› Group control indication
›› Set temperature
›› Air flow direction
›› Programmed time
›› Inspection test / operation
›› Fan speed
›› Clean air filter
›› Defrost / hot start
›› Malfunction
Display
ARC4*/BRC4*/BRC7*
Infrared remote control
Operation buttons: ON / OFF, timer mode start / stop,
timer mode on / off, programme time, temperature
setting, air flow direction (1), operating mode, fan
speed control, filter sign reset (2), inspection (2)/ test
indication (2)
Display: Operating mode, battery change, set
temperature, air flow direction (1), programmed time,
fan speed, inspection / test operation (2)
ARC466A1
194
BRC4*/BRC7*
1. Not applicable for FXDQ,
FXSQ, FXNQ, FBDQ, FDXS, FBQ
2. For FX** units only
3.For all features of the remote
control, refer to the operation
manual
Individual control systems
ARCWLA / ARCWB
Siesta individual control systems
Overview controllers for Siesta Sky Air
Siesta Sky Air indoor units
Controllers
ACQ-D 4-way blow, ceiling mounted cassette
• Standard infrared remote control (ARCWLA) in box of
decoration panel ADP125A
• Wired remote control ARCWB
• Optional group controller R04084124324
AHQ-C ceiling suspended
• Standard infrared remote control in box of indoor unit ARCWLA
• Wired remote control ARCWB
• Optional group controller R04084124324
ABQ-C concealed ceiling
• Standard wired remote control (ARCWB) in box of indoor unit
• Optional group controller R04084124324
Overview of features
Feature
ARCWB
AHQ-C and ACQ-D / Standard for ABQ-C
-
3
Default range 16-30°C
Temperature setting
Optional range 20-30°C
Switch between °C and °F
Room temperature sensor on remote control
4
Cool / Fan dry / Heat / Auto
-
5
Sleep mode
-
6
Fan Speed selection
-
7
Delay timer
8
7-days programmable timer
9
Real time clock display
2
ARCWB
ON/OFF switch
10
Air swing selection
•
-
••
ON/OFF swing mode
Change swing option
(draft/soil prevention or
standard)
-
11
LCD display without backlight
-
12
Key lock
-
13
-
15
Error code indication
IR receiver to enable compatibility with infrared remote control
(disabled when lock function is activated)
Last state memory from indoor PCB
16
Silent mode
17
Turbo mode
•
•
14
-
18
Compressor test model (compressor force ON)
-
19
Daikin inverter error code
-
20
UART communication port (for Daikin protocol)
-
21
Backup battery
-
Specifications
›› Dimensions (length x width x height) ARCWB:
0.15 m x 0.21 m x 0.04 m.
›› ARCWB comes standard with a 10 metre cable,
which can be extended to maximum cable length
of 15 metres. ARCWB can only control one indoor
unit at a time; group control is only possible when
using option R04084124324.
- Standard
•
••
By dipswitch selection
1, 2 & 4 hours delay
195
Control Systems
1
Centralised control systems
Centralised control of the Sky Air and VRV system can be achieved via 3 user friendly compact remote
controllers. These controls may be used independently or in combination with 1 group = several (up to 16)
indoor units in combination and 1 zone = several groups in combination.
A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation,
enabling indoor units to be classified in groups per tenant (zoning).
The schedule timer programmes the schedule and operation conditions for each tenant and the control can
easily be reset according to varying requirements.
DCS302C51
Centralised remote control
Providing individual control of 64 groups (zones) of indoor units.
›› a maximum of 64 groups (128 indoor units, max. 10 outdoor units)
can be controlled
›› a maximum of 128 groups (128 indoor units, max. 10 outdoor units)
can be controlled via 2 centralised remote controls in separate
locations
›› zone control
›› group control
›› malfunction code display
›› maximum wiring length of 1,000m (total: 2,000m)
›› air flow direction and air flow rate of HRV can be controlled
›› expanded timer function
DST301B51
Schedule timer
Enabling 64 groups to be programmed.
›› a maximum of 128 indoor units can be controlled
›› 8 types of weekly schedule
›› a maximum of 48 hours back up power supply
›› a maximum wiring length of 1,000m (total: 2,000m)
DCS301B51
Unified ON/OFF control
Providing simultaneous and individual control of 16 groups
of indoor units.
›› a maximum of 16 groups (128 indoor units) can be controlled
›› 2 remote controls in separate locations can be used
›› operating status indication (normal operation, alarm)
›› centralised control indication
›› maximum wiring length of 1,000m (total: 2,000m)
196
Centralised control systems
DTA113B51
Basic solution for control of Sky Air and VRV
adapter - DTA113B51
›› Rotation function
›› Backup operation function.
BRC1E53A/B/C
Up to 4 units / 1 adapter
DCS601C51
Detailed & easy monitoring and operation of VRV systems (max. 64 indoor units groups).
third party controller (domotics, BMS, etc.) via http interface
Fire alarm
Ethernet
Forced OFF contact input
DIII-NET
Indoor units
HRV
DCS601C51
System layout
›› Up to 64 indoor units can be
controlled
›› Touch panel (full colour LCD
via icon display)
Control
›› Individual control
(set point, start/stop,
fan speed)
(max. 64 groups/indoor units)
›› Set back shedule
›› Enhanced scheduling function
(8 schedules, 17 patterns)
›› Flexible grouping in zones
›› Yearly schedule
›› Fire emergency stop control
›› Interlocking control
›› Increased HRV monitoring and
control function
›› Automatic cooling / heating
change-over
›› Heating optimization
›› Temperature limit
›› Password security: 3 levels
(general, administration
& service)
›› Quick selection and full
control
›› Simple navigation
Monitoring
›› Visualisation via Graphical User
Interface (GUI)
›› Icon colour display change
function
›› Indoor units operation mode
›› Indication filter replacement
›› Multi PC
Cost performance
›› Free cooling function
›› Labour saving
›› Easy installation
›› Compact design: limited
installation space
›› Overall energy saving
Open interface
›› Communication to any third
party controller (domotics,
BMS, etc.) is possible via
open interface (http option
DCS007A51)
Connectable to
›› VRV
›› HRV
›› Sky Air
›› Split (via interface adapter)
Control Systems
Languages
›› English
›› French
›› German
›› Italian
›› Spanish
›› Dutch
›› Portuguese
197
NEW Centralised control systems
Table
t
DCC601A51
Advanced
• Intuitive and user-friendly interface
centralised
controller
• Flexible concept for stand alone
and multi site applications
• Total solution thanks to
integration of 3rd party equipment
• Monitor & control your small
commercial building, no matter
with Cloud connection
2 solutions:
where you are
Local solution
›› Offline centralised control
Cloud solution
›› Flexible online control from any device (Laptop,
›› Stylish interface fits any interior
›› Monitor & control one or multiple sites
›› Benchmark the energy consumption of different
via stylish optional screen
tablet...)
installations
›› Energy consumption follow-up to comply
with local regulations
System layout
Local solution
Online control from any device
Alarm
Window
contact
Daikin supplied screen
(optional) (for local control)
Pulse input
Z380C-1A023A
or
Digital input
Local network
Daikin supplied router
(optional) 4G-N12
Table
t
DCC601A51
WAGO power
supply
CPU module
I/O module
Split,
,
VAM, ventilation,
air curtains
198
,
…
Centralised control systems NEW
Total solution
›› Total solution thanks to a large integration of
Daikin products and 3rd party equipment
›› Connect a wide range of Daikin units (Split, Sky Air,
VRV, Ventilation, air curtains)
From one to ∞ sites
›› Simply control your entire building centrally
›› Increased customer shopping experience by bet-
ter management of your shop comfort level
Daikin Cloud Services
LOCAL
CONTROL
›› Control your building no matter where you are
›› Monitor and control multiple sites
›› Installer or technical manager can remotely login
to the site in case of malfunctions for first
troubleshooting
›› Benchmark the energy consumption
of different installations
›› Manage & track your energy use
›› Monitor the long time operating units to keep
the consumption under control
DAIKIN CLOUD
SERVICE
Installer/
technical manager
Customer
User friendly touch control
›› Stylish Daikin supplied optional screen
for local control fits any interior
›› Intuitive and user-friendly interface
›› Full solution with simple control
›› Easy commissioning
Flexible
›› Inputs via digital and pulse input for 3rd party
equipment such as kWh meters, emergency
input, window contact, …
›› Modular concept allows your cloud to grow
with your business
›› Control up to 32 indoor unit groups , with a maximum of 32 indoor units
Pulse input
Digital input
Indoor uit
Functions overview
Languages
System layout
Local solution
Cloud solution
32
32
EN, FR, DE, IT, ES, NL, PT
N° of connectable indoor units
Multiple sites control
Basic control functions (ON/OFF, mode, filter sign, setpoint, fan
speed, ventilation mode, room temperature, …)
Remote control prohibition
Control Systems
Monitoring &
control
All devices ON/OFF
Group control
Weekly schedule
Interlock control
Set point limitation
Visualisation of energy use per operation mode
Error e-mail
Connectable to
DX split, Sky Air, VRV
VAM, VKM ventilation
Air curtains
199
Centralised control systems
Check on
https://www.youtube.com/
DaikinEurope
DCM601A51
Mini BMS
• Price competitive mini BMS
• Cross-pillar integration of Daikin products
• Integration of third party equipment
with full integration
across all product pillars
System overview
Web Access
CLOUD
Internet
Extranet
LAN
3G
HTTP
Integration of third
party equiqment
Full control of Daikin
HVAC-R portfolio
DCM601A51
ITM plus adaptor line
Max. 7
adapters
Di/Pi line
Fire alarm
Max. 200m
DCM601A52
Di/Pi port
kWh meter
Direct plug & play connection!
Split
I/O module
Pump
Sensor
Multi state objects
Elevator
200
Air handling unit
Alarm
I/O module
Fan
air curtain,
hydrobox,
Analog/digital/pulse objects
Lighting
indoor units,
air handling units
Refrigeration
WAGO
interface
Chillers and AHU
protocol
Fan coil units
BACnet/IP
Centralised control systems
User friendliness
›› Intuitive user interface
›› Visual lay out view and direct access to indoor unit
main funtions
›› All functions direct accessible via touch screen
or via web interface
Smart energy management
›› Monitoring if energy use is according to plan
›› Helps to detect origins of energy waste
›› Powerful schedules guarantee correct operation
Plug & play
throughout the year
›› Save energy by interlocking A/C operation with
other equipment such as heating
Flexibility
Split
Fan coils
Chillers and AHU
Refrigeration
›› Cross-pillar integration (heating, air conditioning,
applied systems, refrigeration, air handling units)
›› BACnet protocol for 3rd party products integration
›› I/O for integration of equipment such as lights,
BACnet/IP
protocol
pumps… on WAGO modules
›› Modular concept for small to large applications
›› Control up to 512 indoor unit groups via one ITM
and combine multiple ITM via web interface
Lighting
Lighting
Sensor
Pump
Fan
Sensor
Air handling
unit
Elevator
Alarm
WAGO I/O
Easy servicing and commissioning
Lighting
Pump
Fan
Sensor
›› Remote refrigerant containment check reducing
on site visit
›› Simplified troubleshooting
›› Save time on commissioning
Flexibility in size
thanks to the pre-commissioning tool
›› Auto registration of indoor units
64 up to 512 groups
Functions overview
Languages
Management
Control
Open interface
›› English
›› Web access
›› Individual control
›› Communication to any third
›› French
›› Power Proportional
›› Italian
›› Spanish
›› Dutch
›› Portuguese
Distribution (option)
›› Operational history
(malfunctions, …)
›› Smart energy management
›› Schedule setting (Weekly
party controller (domotics,
BMS, etc.) is possible via http
schedule, yearly calender,
open interface (http option
seasonal schedule)
DCM007A51)
›› Interlock control
- monitor if energy use
›› Setpoint limitation
is according to plan
›› Temperature limit
Control Systems
›› German
(512 groups)
- detect origins of
System layout
›› Up to 512 unit groups can be
controlled
energy waste
›› Setback function
›› Sliding temperature
WAGO Interface
›› Modular integration of 3rd
party equipment
Connectable to
- DX Split, Sky Air, VRV
- Chillers
(ITM plus Integrator + 7 iTM
- WAGO coupler (interface
Plus adapters)
between WAGO and iTM)
- Daikin AHU
(via POL638.70 controller)
- Di module
- Fan coils
- Do module
- Daikin Altherma Flex type
- Ai module
- LT and HT hydroboxes
- Ao module
- Biddle Air curtains
- Thermistor module
- WAGO I/O
- Pi module
- BACnet/IP protocol
201
Standard protocol interfaces
Modbus Interface
RTD
RTD-NET
›› Modbus interface for monitoring and control
of Sky Air, VRV, VAM and VKM
RTD-20 retail economiser
Control zones in shop applications
Zoning
Stockroom
Reduce energy costs for
non-comfort areas by
RTD-10
›› Advanced integration into BMS of Sky Air, VRV,
VAM and VKM through either:
- Modbus
- Voltage (0-10V)
- Resistance
›› Duty/standby function for server rooms
setting a different, wider
temperature band
Retail zone
Timer sets pre-trade,
RTD-20
›› Retail economisor
›› Advanced control of Sky Air, VRV, VAM/VKM
and air curtains
›› Clone or independent zone control
›› Increased comfort with integration of CO2 sensor
for fresh air volume control
›› Save on running costs via
- pre/post and trade mode
- set point limitation
- overall shut down
- PIR sensor for adaptive deadband
RTD-HO
›› Modbus interface for monitoring and control of
Sky Air, VRV, VAM and VKM
›› Intelligent hotel room controller
trade and post-trade
Kitchen
conditions
Individual control by the staff
Changing rooms
Custom settings to provide
a warmer zone for changing
rooms for maximum customer
comfort
Control options benefits
Optimize the operation of the air conditioning
without compromising occupant comfort
Without RTD-20
›› Pre-trade:
• AC either on (timer) or off
• whole store heated or cooled
›› Trading:
• achieving set-point
• staff could access controllers
• heat cool clash can occur
• door curtain not interlocked
• always trying to achieve set-point
›› Post-Trade:
• either on or off
With RTD-20
›› Pre-trade:
• De-stratification on start-up
• Heat/Cool protection enabled
• AC only comes on if internal
temp above 26°C or below 19°C
• achieving midpoint of 19-23°C
• controllers locked
• heat cool clash prevented
• door curtain interlocked
• learns store patterns & heats/
cools “enough” to reach set-point
›› Post-Trade:
• Heat/cool protection enabled
• Trade extension function
Integrate all essential store operations in one control
Optimize the operation of the air conditioning without compromising occupant
comfort.
Accumulated kWh
70000
Up to 35%
saving!
60000
50000
40000
30000
20000
Occupied year 1
10000
Occupied year 2
0
0
202
500
1000
1500
2000
2500 Accumulated heating + cooling degree days
Overview functions
Overview functions
Main functions
Dimensions
RTD-NET
HxWxD
RTD-10
mm
RTD-20
RTD-HO
100 x100 x 22
Key card + window contact

Set back function

Prohibit or restrict remote control functions (setpoint limitation, ...)


**

Modbus (RS485)




Group control




0 - 10 V control


Resistance control


IT application

Heating interlock


Output signal (on/defrost, error)

****
Retail application
Partitioned room control
Air curtain



***
***

(1): By combining RTD-RA devices
RTD-NET
RTD-10
RTD-20
RTD-HO
On/Off
Control functions
M
M,V,R
M
M*
Set point
M
M,V,R
M
M*
Mode
M
M,V,R
M
M*
fan
M
M,V,R
M
M*
Louver
M
M,V,R
M
M*
HRV Damper control
M
M,V,R
M
Prohibit/Restrict functions
M
M,V,R
M
M*
Forced thermo off
Monitoring functions
RTD-10
RTD-20
RTD-HO
M
M
M
M
Set point
M
M
M
M
Mode
M
M
M
M
fan
M
M
M
M
Louver
M
M
M
M
RC temperature
M
M
M
M
RC mode
M
M
M
M
nbr units
M
M
M
M
Fault
M
M
M
M
Fault code
M
M
M
M
Return air temperature (Average /Min/Max)
M
M
M
M
Filter alarm
M
M
M
M
Termo on
M
M
M
M
Defrost
M
M
M
M
Coil In/Out temperature
M
M
M
M
Control Systems
RTD-NET
On/Off
M : Modbus / R : Resistance / V : Voltage / C: control
* : only when room is occupied / ** : setpoint limitation / (*) if available
*** : no fan speed control on the CYV air curtain / **** : run & fault
203
Standard protocol interfaces
DIII-net Modbus interface
EKMBDXA
Integrated control system for seamless connection between
Split, Sky Air, VRV and small inverter chillers and BMS systems
›› Communication via Modbus RS485 protocol
›› Detailed monitoring and control of the VRV total solution
›› Easy and fast installation via DIII-net protocol
›› As the Daikin DIII-net protocol is being used, only one modbus interface is needed for a group of Daikin systems
(up to 10 outdoor unit systems).
VRV network
DIII- NET
EKMBDXA
VRV Outdoor unit
Biddle air curtain
*via EKEQ box
HRV
up to 64 units connectable per interface
Sky Air network*
Split network*
KRP928BB2S
Small inverter chiller network
Building
control
network
Fire alarm
Security
Power supply facility
Lighting
Pump
* Additional centralized controller might be required. For more information contact your local dealer.
Maximum number of connectable indoor units
Maximum number of connectable outdoor units
Communication
DIII-NET - Remark
Protocol - Remark
Protocol - Type
Protocol - Max. Wiring
length
Dimensions
HeightxWidthxDepth
Weight
Ambient temperature - operation
Max.
Min.
Installation
Power supply
Frequency
Voltage
204
EKMBDXA7V1
64
10
DIII-NET (F1F2)
2 wire; communication speed: 9600 bps or 19200 bps
RS485 (modbus)
m
mm
kg
°C
°C
Hz
V
500
124x379x87
2.1
60
0
Indoor installation
50
220-240
Elevator
Standard protocol interfaces
KNX interface
KLIC-DI
Integration of Sky Air and VRV in HA/BMS systems
Connect Sky Air / VRV indoor units to
KNX interface for BMS integration
Concept
light
shop
Domotica
shutter control
tv
Controller
Interface Daikin protocol/ KNX
KNX interface line-up
The integration of Daikin indoor units through
the KNX interface allows monitoring and control
of several devices, such as lights and shutters, from
one central controller. One particularly important
feature is the ability to programme a ‘scenario’
- such as “Home leave” - in which the end-user selects
a range of commands to be executed simultaneously
once the scenario is selected. For instance in
“Home leave” , the air conditioner is off, the lights are
turned off, the shutters are closed and the alarm is on.
KNX interface for
KLIC-DI Size 90x60x35mm
Advanced functionalities
Error management
Scenes
Auto switch off
Temperature limitation
Initial configuration
Master and slave configuration
•
VRV
•
Auto, heat, dry, fan, cool
Auto, heat, dry, fan, cool
2 or 3
Stop or movement
2 or 3
Swing or fixed positions (5)
•
•
•
•
•
•
Control Systems
Basic control
On/Off
Mode
Temperature
Fan speed levels
Swing
Sky Air
Communication errors, Daikin unit errors
•
•
•
•
•
•
205
Room sensors
Wireless room temperature sensor
K.RSS
Flexible and easy installation
›› Accurate temperature measurement thanks to flexible
placement of the sensor
›› No need for wiring
›› No need to drill holes
›› Ideal for refurbishment
Connection diagram Daikin indoor unit PCB (FXSQ example)
Power supply – X35, X13
Air sensor – X16A, X19
Rf Receiver
RF sender
Specifications
Dimensions
Weight
Power supply
Battery life
Battery type
Maximum range
Operation range
Communication
mm
g
m
°C
Type
Frequency
MHz
Wireless room temperature sensor kit (K.RSS)
Wireless room temperature receiver
Wireless room temperature sensor
50 x 50
ø 75
40
60
16VDC, max. 20 mA
N/A
N/A
+/- 3 years
N/A
3 Volt Lithium battery
10
0~50
RF
868.3
›› Room temperature is sent to the indoor unit every 90 seconds or if the temperature difference is 0.2°C or larger.
Wired room temperature sensor
KRCS01-1B
KRCS01-4B
›› Accurate temperature measurement,
thanks to flexible placement of the sensor
Specifications
Dimensions (HxW)
Weight
Length of branch wiring
206
mm
g
m
60 x 50
300
12
Other integration devices
Adapter PCBs
Simple solutions for unique requirements
Concept and benefits
›› Low cost option to satisfy simple control
requirements
›› Deployed on single or multiple units
Connectable to:
Split
(E)KRP1B*
adapter for wiring
KRP2A*/KRP4A*
Wiring adapter for
electrical appendices
KRP58M3
SB.KRP58M51
KRP58M51
Sky Air
VRV
• Facilitates integration of auxiliary heating apparatus, humidifiers, fans, damper
• Powered by and installed at the indoor unit


Remotely start and stop up to 16 indoor units (1 group) (KRP2A* via P1 P2)
Remotely start and stop up to 128 indoor units (64 groups) (KRP4A* via F1 F2)
Alarm indication/ fire shut down
Remote temperature setpoint adjustment
Cannot be used in combination with a central controller


•
•
•
•
•
• Low noise and demand control option for RZQ200/250C

• Low noise and demand control option for RZQG and RZQSG single phase
• Includes mounting plate EKMKSA1

• Low noise and demand control option for RZQG1 and RZQSG 3 phase

Some adapters require an installation box, refer to the option lists for more information
EKRORO
• External ON/OFF or forced off
• Example: door or window contact
EKRORO 3
• External ON/OFF or forced off
• F1/F2 contact
• Example: door or window contact
KRC19-26A
• Mechanical cool/heat selector
• Allows switching over an entire system between cooling/heating/fan only
• Connects to the A/B/C terminals of the unit
BRP2A81
Control Systems
Accessories
• Cool/heat selector PCB
• Required to connect KRC19-26A to a VRV IV outdoor unit
207
Options & accessories
AUTO-CLEANING PANEL
FILTERS
INTELLIGENT SENSORS
208
Options &
accessories
210
Indoor units
Outdoor units
210
212
Ventilation
214
Air handling units
215
Options & Accessories
Sky Air
209
Options INDOOR UNITS
Description
DCC601A51
Centralised controller with cloud connection
FCAHG-F
FCQHG-F
FCQG-F
FFQ-C
ACQ-D
FDXS-F9
FDBQ-B
FBQ-D




-



ARCWB
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
Wired remote control
BRC2E52C
Simplified remote control (with operation mode
selector button) (12)
BRC3E52C
Simplified remote control (without operation mode
selector button) (12)
DCM601A5A
Intelligent touch manager
Infrared remote control (heat pump)
DCS302C51
Centralised remote control (11)
DCS301B51
Unified ON/OFF control (11)
DST301B51
Schedule timer
BRC1D52
BRC1D528
BRC1E52A (3)(6) BRC1E52A (3)(6)
BRC1E52B (4)(6) BRC1E52B (4)(6)
BRC1E53A/B/C BRC1E53A/B/C




-







-







-



BRC7FA532F
(5)(10)
BRC7EB530W (8)
(9)(10)
BRC7F530W (8)
(9)(10)
BRC7F530S (8)
(9)(10)
-
BRC4C65
-
BRC4C65
BRC7FA532F (5)(10)




-
-
-





-
-
-





-
-
-

Adapter for wiring
-
-
-
-
-
-
-
-
Adapter for wiring (interlock for fresh air intake fan)
-
-
-
-
-
-
-
KRP1BA59
Adapter for external ON/OFF and monitoring/for
electrical appendices (1)
KRP1B57 (5)
KRP4A53 (5)
KRP1B57
KRP4A53 (5)
KRP1B57
KRP4A53 (5)
-
KRP4A54
-
KRP4A52 (14)
KRP2A51 (14)
Adapter for wiring (hour meter) (1)(7)(14)
EKRP1C11 (5)
EKRP1C11 (5)
EKRP1B2 (13)
-
-
EKRP1B2 (13)
-
-
-
-
-
-

KRP1H98 (5)(6)
KRP1B101
KRP1BA101
-
KRP1BA101
-
KRP1B101
KRP1BA101
-
-

-
-
-
BRP7A53
BRP7A53
-
-
BRP7A54
BRP7A51 (13)
DTA112B51
Interface adapter for Sky Air
-
Installation box for adapter PCB
NIM03 - R04084124324
Option PCB for group control
KRP1H98 (5)(6)
-
Digital input adapter (1)(13)(14)
BRP7A53
EKRP1B2A
Options PCB for external electrical heater,
humidifier and/or hour meter (7)
-
-
-
-
-
-
-

Mounting plate for adapter PCB
-
-
-
-
-
-
-
-




-

-

-
-
-
-
-
-
-
-



-
-

-
-



-
-

-
-
-
-
-
-
-
-
-

KRCS01-4
Remote sensor
Remote ON/OFF, forced OFF kit
KJB311A
Electrical box with earth terminal (3 blocks)
KJB212A
Electrical box with earth terminal (2 blocks)
KJB411A
Electrical box with earth terminal
Notes:
1) Installation box for adapter PCB is necessary;
2) Interface adapter for Sky Air series (DTA112B51) is necessary;
3) Including following languages: English, German, French, Italian, Spanish, Dutch, Greek, Russian, Turkish, Portuguese, Polish;
4) Including following languages: English, German, Czech, Croatian, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian;
5) Option not available in combination with BYCQ140*G;
6) Independently controllable flaps function not available in combination with RR and RQ models.;
7) Electrical heater, humidifier and hour meter are field supply. These parts should not be installed inside the equipment;
8) Sensing function is not available;
9) Independently controllable flaps function is not available;
10) With the infrared remote control, the individual flap control and automatic air volume control cannot be controlled;
11) Including following languages: pack 1: English, German, French, Dutch, Spanish, Italian, Portuguese with PC cable EKPCCAB3 in combination with the Updater PC software, you can additionally
change the language to : language pack 2: English, Bulgarian, Croatian, Czech, Hungarian, Romanian and Slovenian. Language pack 3: English, Greek, Polish, Russian, Serbian, Slovak and Turkish.;
12) Only possible in combination with simplified remote control BRC2/3E52C;
13) These options require mounting plate KRP4A96, maximally 2 optional PCBs can be mounted.
14) When installing electrical heaters, an optional PCB for external electric heaters EKRP1B2A is required for each indoor unit.
15) This option needs to be installed together with installation box KRP1B101/KRP1BA101.
210
Options INDOOR UNITS
FDQ-B
ABQ-C
FAQ-C9
FHQ-CB
AHQ-C
FUQ-C
FNQ-A
FVQ-C


-


-



BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
-
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
ARCWB
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C
BRC1D52
BRC1E52A (3)
BRC1E52B (4)
BRC1E53A/B/C


-


-





-


-





-


-



BRC4C65
BRC4C65
-
BRC7EB518
BRC7G53
-
BRC7C58 (10)
BRC4C65
-


-


-





-


-





-


-



-
-
-
-
-
-
-
KRP1B56
-
KRP1C64 (15)
KRP1B54
-
-
-
-
-
-
-
KRP4A51 (15)
KRP4A51 (15)
-
KRP4A51 (15)
KRP1B54
KRP4A52 (1)
-
KRP4A53
KRP4A54
KRP1B57
KRP4A52 (6)(14)
-
-
-
-
-
-
-
-
-
-

-
-
-
-
-
-
-
-
-
-
KRP4A93 (6)
KRP1D93A
-
KRP1B97
KRP1BA101
KRP4AA95
-
-

-
-

-
-
-
BRP7A54
BRP7A54
-
BRP7A51 (12)
BRP7A52
-
BRP7A53
BRP7A51 (12)
BRP7A52


-
-
-
-
-
-
-
KRP4A96
KRP4A96
-
-
KKSAP50A56 (35-50)
-
-
-
-


-


-


-
EKRORO3
EKRORO
-
-
EKRORO4
-
EKRORO5
-
-
-
-
-


-


-
-
-
-


-


-
-
-
-
-
-
-
-
-
Options & Accessories
FDQ-C
211
Options INDOOR UNITS
Description
Replacement long-life filter
FCQHG-F
FCQG-F
FFQ-C
ACQ-D
FDBQ-B
FBQ-D
FDQ-C
KAFP551K160
KAFP551K160
KAFQ441BA60
-
-
-
-
Standard
Standard
Standard
Standard
-
Standard
Standard
-
-
-
-
-
-
-
KDBHQ55B140 (5)
KDBHQ55B140 (5)
BDBHQ44C60
-
-
-
-
-
-
-
-
-
-
-
BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (3)
BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (3)
BYFQ60B3
BYFQ60C2W1W
BYFQ60C2W1S
ADP125A (10)
-
-
-
KDDQ44XA60
-
-
-
-
KDAJ25K140A
Drain pump kit
L-type piping kit (upward
direction)
Sealing member
of air discharge outlet
Decoration panel for air
discharge
Decoration panel
Fresh air intake kit (direct
installation type)
KDDQ55B140-1 (1)(2) KDDQ55B140-1 (1)(2)
+
+
KDDQ55B140-2 (1)(2) KDDQ55B140-2 (1)(2)
-
-
-
KDAP25A56A
(35-50 class)
KDAP25A71A
(60-71 class)
KDAP25A140A
(100-140 class)
-
KDBQ44B60
-
-
-
-
BRYQ140A
BRYQ140A
BRYQ60A2W (3)
BRYQ60A2S (3)
-
-
-
-
-
-
-
-
-
-
-
Air discharge adapter for
round duct
-
-
Panel spacer
-
Sensor kit (4)
Noise filter
- The BYCQ140DW has white insulations. Be informed that dirt is more visible on white insulation and that it is consequently not advised to install the BYCQ140DW decoration panel in environments
- To be able to control BYCQ140D/W/DG(F), the controller BRC1E is needed and cannot be combined with mini-VRV, multi and split non-inverter outdoor units.
Notes:
1) Option not available in combination with BYCQ140D*G*;
2) Both parts of the fresh air intake are needed for each unit;
3) This option is intended exlusively for usage in fine dust environments (clothing shops). Do not use this option in high humidity and/or greasy environments.;
4) Sensor kit not available with RR & RQ units;
5) For directly mounting the decoration panel on the unit, decoration panel option EKBYBSD is required.
OUTDOOR UNITS
Description
RZQG-L9V1
RZQG-L8Y1
RZQSG-L3/9V1
RZQSG-L(8)Y1
RZQ-C
AZQS-B8V1/BY1
-
-
-
-
KWC26B280
-
For twin
KHRQ22M20TA (2)
KHRQ22M20TA
(KHRQ58T) (2)
KHRQ22M20TA (2)
KHRQ22M20TA
(KHRQ58T) (2)
KHRQ22M20TA
-
For triple
KHRQ127H (2)
KHRQ127H
(KHRQ58H) (2)
KHRQ127H(2)
KHRQ127H
(KHRQ58H) (2)
KHRQ250H7
-
KHRQ22M20TA (x3)
-
Central drain plug
Refrigerant branch
piping
For double
KHRQ22M20TA (3x)
KHRQ22M20TA (3x)
KHRQ22M20TA (3x) (2)
KHRQ22M20TA (3x) (2)
twin
(KHRQ58T) (2)
(KHRQ58T) (2)
Demand adapter kit
SB.KRP58M51
KRP58M51
KRP58M51 (71 class),
SB.KRP58M51
(100-125-140)
SB.KRP58M51
(class 125-140)
KRP58M51
KRP58M51MK (V1)
Bottom plate heater (1)
EKBPH140L7
EKBPH140L7
-
-
-
-
Notes:
1) Bottom plate heater is only available for RZQG* models;
2) For combination of RZQ(S)G71-140 in combination with FCQG35-71F or FCQHG71F use the refrigerant branch piping mentioned between brackets
212
Options -
FDQ-B
ABQ-C
FAQ-C9
FHQ-CB
AHQ-C
FUQ-C
FNQ-A
FVQ-C
-
KAFP551K160
-
KAFJ95L160
-
-
-
KAFP501A56
(35-50 class)
KAFP501A80
(60-71 class)
KAFP501A160
(100-125 class)
-
-
K-KDU572EVE
KDU50P60 (35-60 class)
KDU50P140
(71-125 class)
-
-
-
-
-
-
-
KHFP5M35 (35 class)
KHFP5N63 (50-60 class)
KHFP5N160
(71-125 class)
-
-
-
-
-
-
-
-
-
KDBHP49B140
-
-
-
-
-
-
-
KDBTP49B140
-
-
-
-
-
-
-
-
-
-
-
-
-
KDDQ50A140
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KEK26-1A
-
-
-
KEK26-1A
-
Options & Accessories
INDOOR UNITS
213
Options & accessories
Ventilation
Dust filters
VAM
150FC
VAM
250FC
VAM
350FC
VAM
500FC
VAM
650FC
VAM
800FC
VAM
1000FC
VAM
1500FC
VAM
2000FC
EN779 Medium M6
-
-
EKAFV50F6
EKAFV50F6
EKAFV80F6
EKAFV80F6
EKAFV100F6
EKAFV100F6 x2
EKAFV100F6 x2
EN779 Fine F7
-
-
EKAFV50F7
EKAFV50F7
EKAFV80F7
EKAFV80F7
EKAFV100F7
EKAFV100F7 x2
EKAFV100F7 x2
EN779 Fine F8
-
-
EKAFV50F8
EKAFV50F8
EKAFV80F8
EKAFV80F8
EKAFV100F8
EKAFV100F8 x2
EKAFV100F8 x2
Model name
-
-
-
KDDM24B50
KDDM24B100
KDDM24B100
KDDM24B100
KDDM24B100 x2
KDDM24B100 x2
Nominal pipe
Diameter (mm)
-
-
-
200
200
250
250
250
250
-
-
BRYMA65
BRYMA65
BRYMA65
BRYMA100
BRYMA100
BRYMA200
BRYMA200
VH1B
VH2B
VH2B
VH3B
VH3B
VH4B / VH4/AB
VH4B / VH4/AB
VH5B
VH5B
Silencer
CO2 sensor
VH electrical heater for VAM
Individual control systems
Wired remote control
VAM wired remote control
Centralised control systems
VAM-FC
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52 1
BRC1E52A/B / BRC1D52 1
BRC301B61
-
-
-
VAM-FC
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
Centralised remote control
DCS302C51
-
-
-
Unified ON/OFF control
DCS301B51
-
-
-
Schedule timer
DST301B51
-
-
-
DCC601A51
DCC601A51
-
-
-
DCM601A51
DCM601A51
DCM601A51
DCM601A51
Modbus DIII adapter
Intelligent Touch Manager
EKMBDXA7V1
EKMBDXA7V1
EKMBDXA7V1
EKMBDXA7V1
BACnet interface
DMS502A51
-
-
-
LonWorks interface
DMS504B51
-
-
-
VAM150-250FC
VAM350-2000FC
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
Wiring adapter for electrical appendices
(note 7)
Others
KRP2A51
KRP2A51 (note 3)
-
-
-
Adapter PCB for humidifier
KRP50-2
KRP1C4 (note 4/6)
-
-
-
Adapter PCB for 3rd party heater
BRP4A50
BRP4A50A (note 4/5)
-
-
-
-
-
-
KRCS01-1
-
Remote sensor
Notes
(1) Cool/heat selector required for operation
(2) Unless otherwise specified DIII-net devices cannot be connected to the system
(3) Installation box KRP1BA101 needed.
(4) Fixing plate EKMPVAM additionally needed for VAM1500-2000FB.
(5) 3rd party heater and 3rd party humidifier cannot be combined
(6) Installation box KRP50-2A90 needed.
(7) For external control and monitoring (ON/OFF control, operation signal, error indication)
VH electrical heater for VAM
Supply voltage
Output current (maximum)
Temperature sensor
Temperature control range
Run on timer
Control fuse
220/250V ac 50/60 Hz. +/-10%
19A at 40°C (ambient)
5k ohms at 25°C (table 502 1T)
0 to 40°C / (0-10V 0-100%)
Adjustable from 1 to 2 minutes (factory set at 1.5 minutes)
20 X5 mm 250 m A
LED indicators
Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red
Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input
Vh electrical heater for vam
Capacity
Duct diameter
Connectable VAM
214
kW
mm
98mm X 181mm centres 5 mm ø holes
35°C (during operation)
100°C Pre-set
125°C Pre-set
1A 120V AC or 1A 24V DC
0-10VDC
vH1B
VH2B
VH3B
VH4B
VH4/AB
VH5B
1
100
VAM150FC
-
1
150
VAM250FC
VAM350FC
1
200
VAM500FC
VAM650FC
1.5
250
VAM800FC
VAM1000FC
2.5
250
VAM800FC
VAM1000FC
2.5
350
VAM1500FC
VAM2000FC
Options & accessories
D-AHU Professional
Construction type
Aluminium
Profile
Panel insulation
FP 50
FP 25
standard
standard
Anodized aluminium
option
option
option
option
option
option
option
option
option
option
option
option
Glass fibre reinforced nylon
standard
standard
standard
standard
Polyurethane foam density 45 kg/m3 thermal
conductivity 0.020 W/m*K fire reaction class 1
standard
standard
standard
standard
option
option
option
option
standard
Mineral wool density 90 kg/m3 thermal conductivity
0.037 W/m*K (referred to 20°C) fire reaction class 0
Grey Plastisol covered galvanized steel
External sheet
material
SP 45
standard
Aluminium with thermal break
Anodized aluminium with thermal break
Corner
SP 65
standard
standard
standard
standard
Pre-coated galvanized steel
option
option
option
option
Galvanized steel
option
option
option
option
Aluminium
option
option
option
option
AISI 304 stainless steel
option
option
option
option
standard
standard
standard
standard
option
option
option
option
option
option
option
option
Galvanized steel
Pre-coated galvanized steel
Internal sheet material Grey Plastisol covered galvanized steel
Aluminium
AISI 304 stainless steel
Aluminium
Base frame
Galvanized steel
Handle
Glass fibre reinforced nylon
Type
Hinge function type
(possibility to remove door)
Compression type
option
option
option
option
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
standard
standard
standard
standard
option
option
option
option
D-AHU Easy
Aluminium
Corner
Glass fibre reinforced nylon
Panel insulation
Polyurethane foam thermal conductivity 0.024 W/m*K
DS 50
DS 25
Standard
Standard
Standard
Standard
Standard (density 45 kg/m3)
standard (density 47 kg/m3)
External sheet material
Pre-coated galvanized steel (RAL 9002)
Standard
Standard
Internal sheet material
Galvanized steel
Standard
Standard
Base frame
Aluminium
Standard
Standard
Handle
Glass fibre reinforced nylon
Standard
Standard
Type
Compression type
Standard
Standard
Options & Accessories
Construction type
Profile
215
We’re here to help you!
Online and offline
http://literature.daikinpromoshop.eu
General catalogue
2016
-45°C
216
0°C
80°C
Tools and
platforms
218
220
Tools & Platforms
Literature overview
Supporting tools, software and apps
217
Commercial market - literature overview
for professional network
Solution
guides:
Reference
books:
Product
profiles:
VRV IV range
VRV IV
360° efficiency
Detailed VRV IV standards
and technologies benefits.
Main features and specs of
VRV IV product range
VRV IV i-series
i
Keep looking
you’ll never find me
Water-to-air heat pump
Main benefits,
application examples
and specs of VRV IV
i-series product range
VRV IV heat pumps for indoor installation
16-207
Detailed info on VRV IV Wseries, application
examples, technical system
design background
Second half 2016
VRV IV S-series
VRV IV heat recovery, heat pump, replacement
and water cooled
15-206
Keep looking
you’ll never find me
Compact VRV IV heat pumps
for residential and light commercial applications
16-209
Main benefits,
application examples
and specs of VRV IV
S-series product range
16-208
for installers
Infrastructure cooling
RELIABLE,
C
Replacement
technology
Replacement
Technology
Clear installer benefits
of VRV replacement
technology
› For
The quick and quality way of upgrading R-22 and R-407C systems
Product
flyers:
Real time clock
Supports multiple languages
› Restrict some of all functions on the remote
control to void misuse in e.g. hotels, shops, offices
Other features
› English, German, French, Spanish, Italian,
Portuguese, Greek, Dutch, Russian, Turkish
and Polishr (BRC1E52A)
› Built-in back-up power. When a power failure occurs,
all settings remain stored up to 48 hours
› English, German, Czech, Croation, Hungarian,
Romanian, Slovenian, Bulgarian, Slovak, Serbian,
Albanian (BRC1E52B)
› Backlight display
Specifications / Functions
Specifications
BRC1E52A / BRC1E52B
Dimensions (HxWxD)
3.120x120x19 mm40
Display size (HxW)
LCD
43.2x68.85 mm
Type
Full dot (160x255)
Colour
Fresh white
Cover for operation part
No
Max. wiring length
500m
Connectable indoor units
All VRV® and Sky Air® indoor units
Functions
BRC1E52A / BRC1E52B
Set sensor behavior
Energy saving
functions
—
Temperature range limit
—
Setback function
—
Set point auto reset
—
Off timer
Multilingual display
Timer
16-140
User friendly
remote control
with contemporary
design
Split, Sky Air, VRV, Chillers,
Refrigeration, Daikin Altherma
Detailed info on
BRC1E52A/B remote
control
Modbus
Interface
RTD modbus interface
Detailed info on RTD
controls and applications
RTD
BRC1E52A/B
English, German, Czech, Croation, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian
—
Clock (time display)
Real time clock with auto update to daylight saving time
Backlight
—
Contrast adjustment
—
Weekly schedule timer
3
Holiday function
—
Key lock
—
Restrict buttons
Built-in back-up power
Each menu individually
Each button individually (ON/OFF, operation mode selector, temperature adjustment, fan speed / air flow direction)
When a power failure occurs, all settings remain stored up to 48 hours
› Easy to use: all main functions directly accessible
Daikin Europe N.V.
server rooms, telecom shelters, laboratories, IT applications
15-214
—
Room temperature display
Access control Restrict menus
Memory
Clear installer benefits
why to choose Daikin for
infrastructure cooling
—
English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, Polishr
Help menu
Display
Infrastructure
cooling solution
Wired Remote Control
Possibility to individually restrict menu
functions/buttons
Real time clock with auto update to daylight saving
time
TINUOUS O
ON
RATION
PE
Focus
topics:
Naamloze Vennootschap Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)
FSC
ECPEN15 - 306
› Easy commissioning: intuitive interface for advanced
menu settings
› Optimise your air conditioning system by activating a
series of energy saving functions (temperature range
limit, setback function, off timer, …)
180 · 11/14
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from
or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.
The present publication supersedes ECPEN12-306. Printed on non-chlorinated paper.
› Keep track of your energy consumption with the
kWh indication showing an indicative electricity
consumption
› Set up to 3 independent schedules, so the user can
easily change the schedule himself throughout the
year (e.g. summer, winter, mid-season)
› Real time clock with auto update to daylight saving
time
Integration of Daikin portfolio in BMS system via Modbus
› Supports multiple languages
› Possibility to individually restrict menu functions
› When a power failure occurs all settings remain stored
up to 48 hours thanks to the built-in backup power
Product
catalogues:
15-306
› Indoor unit control
via 0~10 volt, dry contact
or resistance contact
VRV Catalogue
Sky Air Catalogue
Detailed technical
information & benefits
on Sky Air/Ventilation/
Biddle Air Curtain/Control
systems/AHU
› Retail applications
› Hotel applications
› IT applications
› Heating interlock
› Alarm signal
Detailed technical
information & benefits of
the VRV total solution
VRV
Product catalogue 2016
for professionals
15-308
Ventilation Catalogue
Ventilation
Product catalogue 2016
for professionals
Detailed info on
Ventilation products
Full
LIBRA
OF BIM RY
OBJEC
TS
FOR
16-100
Product
portfolios:
Product portfolio
Sky Air
Sky Air product
portfolio
Overview of Sky air
product range
VRV
Minimum running costs, maximum flexibility.
Fast installation, top reliability, perfect comfort.
16-200
Fresh air for the residential and commercial sector
Heat reclaim ventilation and air handling applications
VRV product portfolio
Product portfolio
VRV
Overview of VRV total
solution product range
Product Portfolio
Controls
16-203
Controls systems
portfolio
Overview of all Daikin
control systems
22
16-101
218
16-201
15-301
Tools and platforms
for your customers
Green Buiding Solutions
Commercial Solutions
Daikin offers solutions for
commercial applications
Commercial solutions
for small to large applications
Green building
solutions
Clear building owner/investor
benefits why to choose Daikin
for a green building, with
emphasis on BREEAM
365-days climate comfort for every business
15-216
15-100
Sustainable design
with Daikin HVAC-R systems
Reference
catalogue
Hotel Solutions
Daikin commercial
and industrial
references
Hotel solutions
for hotel owners
Heating - air conditioning - hot water - ventilation - refrigeration - control
15-218
14-213
Intelligent Touch
Manager
Mini Building Management System
SPLIT, SKY AIR, VRV, CHILLERS
The phase-out period for
R-22 is over.
Act now!
Avoid loss of business and replace your air conditioning
system now!
Intelligent Touch Manager
DCC601A51
15-302
16-303
Detailed benefits of
Intelligent Touch Manager
Detailed benefits of DCC601A51
and Daikin Cloud Service
Replacement technology
Clear building owner/investor
benefits of replacement
technology
15-215
Sky Air product leaflets
Concealed
floor standing
unit
FNQ-A, FXNQ-A
Designed to be concealed in walls
› Ideal for installation in offices, hotels and residential
applications
› Its low height enables the unit to fit perfectly beneath
a window
Concealed
ceiling unit
with medium
ESP
FBQ-D, FXSQ-A
Home leave
Home leave
Powerful mode
VRV product leaflets
Single page leaflet with the
main benefits and technical
specifications of each
individual Sky Air unit. Ideal for
quotations
Single page leaflet with the
main benefits and technical
specifications of each individual
VRV unit. Ideal for quotations
Optimum comfort guaranteed no matter the
length of ductwork or type of grilles
operation
› Discretely concealed in the wall, leaving only the
suction and discharge grilles visible
› Requires very little installation space as the depth is
only 200mm
› High ESP allows flexible installation
Powerful mode
Multi tenant
Multi tenant (FXSQ)
(FXNQ-A)
Cassette mini catalogue
Giving overview of our cassette
unit product solutions
(incl. Round flow cassette FCQ(H)G-F/FXFQ-A,
Fully flat cassette FFQ-C/FXZQ-A, FUQ-C/
FXUQ-A, ACQ-C)
16-110
› Top efficiency in the market
› Automatic air flow adjustment function measures the
air volume and static pressure and adjusts it towards
the nominal air flow, whatever the length of duct,
making installation easier and guaranteeing comfort.
Moreover, the ESP can be changed via the wired
remote control to optimize the supply air volume
› Slimmest unit in class, only 245mm
› Discretely concealed in the ceiling: only the suction
and discharge grilles are visible
› Low sound level
› Medium external static pressure up to 150Pa facilitates
using flexible ducts of varying lengths
› Reduced energy consumption thanks to specially
developed DC fan motor
› Flexible installation, as the air suction direction can be
altered from rear to bottom suction
› Standard built-in drain pump increases flexibility and
installation speed
› No optional adapter needed for DIII-connection, link
your unit into the wider building management system
Concealed ceiling unit
mini catalogue
Ceiling suspended, wall mounted, floor
standing units mini catalogue
(incl. FDXS-F(9), FBQ-D, FDQ-C, FDQ-B, FXDQ-M9,
FXDQ-A, FXSQ-A, FXMQ-P7, FXMQ-MA)
(incl. FXHQ-A,FHQ-C, FXAQ-A, FAQ-C, FXNQ-A, FNQ-A,
FXLQ-P, FVQ-C)
Catalogue giving overview of our
concealed ceiling unit product
solutions
16-106
Catalogue giving overview of our Ceiling
suspended, wall mounted and floor standing
product solutions.
16-101
Technical documentation:
All latest Daikin catalogues are available in
a convenient library on the internet:
www.daikineurope.com/support-and-manuals/catalogues
Tools & Platforms
Control systems
operation
Clear building owner/investor
benefits why to choose Daikin
for a hotel
219
Tools and platforms
Supporting
tools, software and apps
www.daikineurope.com/
support-and-manuals/
software-downloads
Software
Solutions seasonal simulator, simulate
& compare
With this software tool you can simulate and
the seasonal efficiency, the annual power
consumption and CO2 emission for a given climate,
load profile (cooling, heating, heat recovery,
covalent, bivalent...) and combination of systems.
With its intuitive and graphical appealing interface,
a simulation, comparison and ROI calculation can be
made in a matter of minutes.
Ventilation Xpress
Selection tool for ventilation devices (VAM, VKM).
The selection is based on given supply/extract
airflows (including fresh up), and given ESP of
the supply/extract ducting:
›› Determines size of electrical heaters
›› Visualisation of psychrometric chart
›› Visualisation of selected configuration
›› Required field settings mentioned in the report
Supporting tools
Building Information
Modelling
(BIM) support
EXPECTED
JUNE 2016
FOR SKY AIR
›› BIM is improving efficiency in the design
and built phase
›› Daikin is among the first
to supply a full library of BIM objects
for its VRV products
220
http://bimobject.
com/en/
product/
?freetext=daikin
Tools and platforms
Other interesting apps
Internet
Some of our most used apps:
Find our solution for different applications:
›› Error code app: quickly know the meaning of fault
codes for each product family
›› Load calculation tool: helps you to calculate
the heat and cool laod of your building
›› Astra: AHU design software
Supermarket
Technical
Restaurant
Hotel
Store &
shop
Home
Bank
Office
Industry
Sport &
Leisure
Online support
NEW Business portal
›› Experience our new extranet that
thinks with you at my.daikin.eu
›› Find information in seconds
via a powerful search
›› Customise the options so you
see only info relevant for you
›› Access via mobile device or desktop
my.daikin.eu
AT
C U S TO M E
›› Get more commercial details on our flagship
products via our dedicated minisites
www.daikineurope.com/
commercial/applications
www.daikineurope.com/
industrial/applications
›› See our references
ON
THE
R OA D
RS
HOTEL PORTA FIRA
www.daikineurope.com/references
Tools & Platforms
AT THE OFFICE
221
Europe’s
new energy label
Labelling to encourage intelligent choices
To enable consumers to compare and make
purchasing decisions based on uniform labelling
criteria, Europe has introduced energy labels. The
previous European energy label for air conditioners,
introduced in 1992, did its job for the time. In 2013,
Europe introduced a seasonal energy label. This
label allows end users to make even more informed
choices, since seasonal efficiency reflects air
conditioner efficiency over an entire season.
The energy label includes multiple classifications
from A+++ to D, reflected in colour shadings ranging
from dark green (most energy efficient) to red (least
efficient). Information on the label not only includes
the seasonal efficiency ratings for heating (SCOP) and
cooling (SEER), but also annual energy consumption
and noise levels.
The label
more in detail
Name of manufacturer
and product
SEER: seasonal efficiency
values for cooling
Classifications from A+++
(most energy efficient)
to D (least energy efficient
Design load for cooling
Seasonal efficiency ratings
for cooling (SEER)
Annual energy consumption
during a cooling season,
including auxiliary modes
Combination of indoor
and outdoor unit
SCOP: seasonal efficiency
values for heating
Classifications from A+++
(most energy efficient)
to D (least energy efficient)
Design load for heating
Seasonal efficiency ratings
for heating (SCOP)
Annual energy consumption
during a heating season,
including auxiliary modes
Sound power value
for indoor unit
Sound power value
for outdoor unit
To take the broad range of
conditions into account,
3 climate zones are used:
cold, average and warm
= colder climate (optional)
= average climate (compulsory)
orange = warmer climate (optional)
blue
green
222
Measuring conditions
Power supply
T1
V1
VE
V3
VM
W1
Y1
=
=
=
=
=
=
=
Conversion table
refrigerant piping
3~, 220V, 50Hz
1~, 220-240V, 50Hz
1~, 220-240V/220V, 50Hz/60Hz*
1~, 230V, 50Hz
1~, 220~240V/220~230V, 50Hz/60Hz
3N~, 400V, 50Hz
3~, 400V, 50Hz
inch
1
/4˝
3
/8˝
1
/2˝
5
/8˝
3
/4˝
7
/8˝
1 1/8˝
1 3/8˝
1 5/8˝
1 3/4˝
2˝
2 1/8˝
2 5/8˝
* For VE power supply only 1~, 220-240V, 50Hz data
mm
6.4 mm
9.5 mm
12.7 mm
15.9 mm
19.1 mm
22.2 mm
28.5 mm
34.9 mm
41.3 mm
44.5 mm
50.8 mm
54 mm
66.7 mm
is displayed in this catalogue.
F-gas regulation
For fully/partially charged equipment: contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit
construction, details can be found on the unit labels.
For non pre-charged equipment (Chillers: split chiller (SEHVX/SERHQ), condensing units and condenserless chillers + refrigeration
(LCBKQ-AV1, JEHCCU/JEHSCU and ICU): Its functioning relies on fluorinated greenhouse gases.
Measuring conditions
Air conditioning
1) Nominal cooling capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference
2) Nominal heating capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference
27°CDB/19°CWB
35°CDB
7.5m - 8/5m VRV
0m
20°CDB
7°CDB/6°CWB
7.5m - 8/5m VRV
0m
Applied systems
Cooling only
Heat pump
Water cooled
Cooling only
Heating only
Condenserless chiller
Fan coil units
Cooling
Heating
Evaporator: 12°C/7°C
Evaporator: 12°C/7°C
Condenser: 40°C/45°C
Ambient: 35°CDB
Ambient: 35°C
Ambient: 7°CDB/6°CWB
Evaporator: 12°C/7°C
Condenser: 30°C/35°C
Evaporator: 12°C/7°C
Condenser: 40°C/45°C
Evaporator: 12°C/7°C
Condensing temperature: 45°C / liquid temperature: 40°C
Room temperature: 27°CDB /19°CWB
Water inlet/outlet temperature: 7°C/12°C
Room temperature: 20°C
2 pipe: Water inlet temperature: 50°C (same water flow as in cooling mode)
4 pipe: Water inlet/outlet temperature: 70°C/60°C
Tools & Platforms
Air cooled
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value,
depending on the distance and acoustic environment (for measuring conditions: please refer to the technical databooks).
The sound power level is an absolute value indicating the “power” which a sound source generates.
For more detailed information please consult our technical databooks.
223
Keep looking
you’ll never find me
The city secret
Unseen in the best places
Our VRV IV i-series offers you a truly unique solution for installations where
you need a totally invisible system. It is compact and easy to hide indoors,
with only the grilles being visible outside. Split into two lightweight
components, the compressor can be installed at floor level in a storage room
or technical area, and the heat exchanger unit, which is only 400 mm high,
can be installed in a standard false ceiling. The VRV IV i-series has a patented
V-shaped heat exchanger which boosts efficiency. So your customer can
now enjoy all the power of a fully invisible VRV system.
Find out more at www.daikineurope.com/citysecret
Daikin Europe N.V.
Naamloze Vennootschap Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)
Daikin Europe N.V. participates in the Eurovent Certification
programme for Liquid Chilling Packages (LCP), Air handling units
(AHU) and Fan coil units (FCU), Check ongoing validity of certificate
online: www.eurovent-certification.com or using: www.certiflash.
com. Infrastructure cooling is not in scope for Eurovent.
ECPEN16 -100
500 · 02/16
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from
or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.
The present publication supersedes ECPEN15-114. Printed on non-chlorinated paper. Prepared by La Movida