instruction manual - Professional Alarm
UniPOS
Fire Extinguishing Control Panel FS5200Е
Fire Extinguishing Control Panel
FS5200Е
INSTRUCTION MANUAL
Revision 6/02.11
Instruction Manual
Revision 6/02.11
Page 1
of 63
UniPOS
1.
2.
3.
4.
4.1.
4.2.
4.2.1.
4.2.2.
4.2.3.
4.2.4.
4.2.5.
4.2.6.
4.2.7.
4.2.8.
4.2.9.
4.2.10.
4.2.11.
4.2.12.
4.2.13
4.3.
5.
5.1.
5.2.
5.3.
6.
6.1.
6.2.
6.3.
7.
7.1.
7.2.
7.3.
8.
8.1.
8.2.
8.3.
8.4.
9.
9.1.
9.2.
9.3.
10.
10.1.
10.2.
10.3.
11.
11.1.
11.2.
11.3.
12.
12.1.
12.2.
12.3.
12.4.
Fire Extinguishing Control Panel FS5200Е
Table of contents
Terminology ...............................................................................................................
Technical Data...........................................................................................................
Contents of Delivery...................................................................................................
Installation and Arrangements....................................................................................
To Mount the Control Panel........................................................................................
Description of Inputs and Outputs. Periphery Devices Assembly .............................
Description and Mounting of Devices to L1, L2 and L3 Inputs...................................
Description and Mounting of Devices to Manual Release Input ................................
Description and Mounting of Devices Mode Select Input ..........................................
Description and Mounting of Devices Hold Input .......................................................
Description and Mounting of Devices On/Off Exting Input .........................................
Description and Mounting of Devices Low Press Input ..............................................
Description and Mounting of Devices Exting Output ..................................................
Description and Mounting of Devices Sounder S1 and Sounder S2 Outputs ............
Description and Mounting of Devices to Outputs OK1, OK andи OK3 Open
Collector Type.............................................................................................................
Description and Mounting of Devices to Rel Fire Output............................................
Description and Mounting of Devices Rel 1ST and Rel 2ST Outputs .........................
Description and Mounting of Devices to Rel Fault Output .........................................
Description and Mounting of Devices to RS485 Interface Terminals.........................
Power Supply Connection ..........................................................................................
General Information ..................................................................................................
Access Levels ............................................................................................................
Indications and Buttons for Control.............................................................................
Conditions of the Fire Extinguishing Control Panel.....................................................
Duty Mode ..................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage I.................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Fire Condition Stage II ...............................................................................................
Description.................................................................................................................
Indication ....................................................................................................................
Using the keypad........................................................................................................
Using the Switch for Mode Selection (Automatic/Manual/Disabled)……...................
Fault Condition............................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Disabled Component ..................................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Test Mode ..................................................................................................................
Description..................................................................................................................
Indication.....................................................................................................................
Using the Keypad .......................................................................................................
Information and Control Mode ....................................................................................
Description .................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Instruction Manual
Revision 6/02.11
4
6
8
8
8
8
11
12
12
13
13
14
14
15
15
15
16
16
16
16
17
17
18
20
21
21
21
21
21
21
22
22
23
23
23
25
26
26
26
27
28
29
29
29
30
30
30
30
30
31
31
31
31
32
Page 2
of 63
UniPOS
12.4.1.
12.4.2.
12.4.3.
12.4.4.
12.4.5.
13.
13.1.
13.2.
13.3.
13.4.
13.4.1.
13.4.2.
13.4.3.
13.4.4.
13.4.5.
13.4.6.
13.4.7.
13.4.8.
14.
15.
16.
17.
18.
19.
Fire Extinguishing Control Panel FS5200Е
Menu View Faults .......................................................................................................
Menu View Disables...................................................................................................
Menu View Test .........................................................................................................
Menu Statuses ...........................................................................................................
Menu System Functions .............................................................................................
Setup Mode ................................................................................................................
Description..................................................................................................................
Indication ....................................................................................................................
Using the Keypad .......................................................................................................
Using the Menus ........................................................................................................
Menu Fire Extinguishing Control Panel.......................................................................
Menu „CAN Parameters”.............................................................................................
Menu Inputs/Outputs ..................................................................................................
Menu Time Extinguishing............................................................................................
Menu Time Evacuation...............................................................................................
Menu Factory Settings................................................................................................
Menu Clear archive.....................................................................................................
Menu new Password...................................................................................................
Extinguishing Control Algorithm..................................................................................
Labour Protection Requirements ...............................................................................
Fire Extinguishing Control Panel Start Up .................................................................
Operation, Storage and Transportation .....................................................................
Warranty .....................................................................................................................
Appendixes ...............................................................................................................
Instruction Manual
Revision 6/02.11
32
33
34
35
36
44
44
45
45
46
46
48
54
56
56
57
57
57
57
59
59
59
59
60
Page 3
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Introduction
The fire extinguishing control panel FS5200Е is designated for fire protection, monitoring and
control of systems for active extinguishing.
After processing the signals from the automatic fire detectors and/or manual call points the control
panel it sends commands to the executive devices for extinguishing, sound-light signalers, air
conditioning and ventilation devices, it sends information to a repeater, PC or another intelligent
devices.
FS5200Еcould be used in – gas, powder, aerosol, water and other types of systems for active
extinguishing.
The fire extinguishing control panel is designed for extinguishing in one zone. It is possible up to
15 zones to be protected when the fire extinguishing control panel is connected in a network via
interface RS485 and a repeater FS5200R.
The fire extinguishing control panel could be connected and become a part of the Interactive Fire
Control System IFS7002 /UniPOS production/.
The fire extinguishing control panel FS5200Е is designed and produced in compliance with
standards EN 54-2:1997/ А1:2006/AC: 2009, EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003.
Some of its main features and possibilities are:
− adjustment of operating modes and parameters of each fire alarm line, output and input via
built in keypad;
− user oriented menu dialogue for easy and convenient operation;
− LCD for visualization of system checkup and set up modes;
− LEDs indication for early warning of a break down or extreme conditions;
− energy independent archive memory saving the event type, date and time, allowing for
detailed analysis of the actions of the authorized personnel and of possible problems in the
fire protection process of the area;
− user oriented test modes allowing for a total control of the site protected;
− built-in serial interface RS485 and CAN for connection to other fire control panels;
− compatible to random installation design, within the range of the available fire extinguishing
control panels resources.
All these are realizable via fire extinguishing control panel’s keypad and after a detailed
examination of the instructions set herewith.
1. Terminology
OUTPUT – monitored or relay output, programmed by the user to be activated during the different
stages of the extinguishing.
EVACUATION TIME – the time from occurring the situation for extinguishing to the moment of
switching on the extinguishing automatics. This time should be enough for the evacuation of the staff
from the premises. The evacuation time is user defined for the specific site. The evacuation time is
shown on the LCD display and it counts down the remaining time until the release of the extinguishing
automatics.
DISABLED LINE – the fire detecting line is switched off (not power supplied) and it is not
monitored for turned out fire detector and a fault condition. This feature is user defined. The indication
for a disabled line is common light indication and text messages on the LCD display.
DISABLED OUTPUT – the output is switched off (the executive device can not be activated) and
is not monitored for a fault condition in the monitored outputs. This feature is user defined. The
indication for a disabled monitored output is common light indication and text messages on the LCD
display.
DISABLE EXTINGUISHING – condition of the fire extinguishing control panel when regardless
the input actions the executive extinguishing device cannot be activated. Disable extinguishing is
Instruction Manual
Revision 6/02.11
Page 4
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
defined by “on” status of the monitored input “On/Off Exting” (See section 4.2.) or by the secret switch
on the front panel. The indication for disable extinguishing is an individual light indication.
HOLD EXTINGUISHING – condition of the fire extinguishing control panel when the release
signal to the executive extinguishing device is delayed. Hold extinguishing is defined by “on” status of
the monitored input „Hold”. Hold extinguishing could be controlled by a manual button if extra
evacuation time is needed and monitoring if the doors of the protected premise are tightly closed.
After the hold signal is cancelled the timer for the evacuation time is started automatically. After the
evacuation time expires the extinguishing executive device is switched on. The indication for hold
extinguishing is an individual light indication.
GROUNDS – non-system non-fatal fault condition, due to leakage to a grounded wire.
MONITORED INPUT – input that monitors the serviceability of the connection wires between the
fire extinguishing control panel and the executive devices. Follow the special diagram for connection.
(See section 5.2.).
MONITORED OUTPUT – a potential output that monitors the serviceability of the connection
wires between the fire extinguishing control panel and the executive device. Follow the special
diagram for connection. (See section 5.2.).
SHORT CIRCUIT IN A LINE, MONITORED OUTPUT OR MONITORED INPUT – non-system,
non-fatal fault condition, entered due to registered current value, exceeding a threshold value.
LINE IN TEST – a line, set in Test condition by the user. The line is switched on (supplied) and
reset (the power supply is switched off for 3 s) periodically every 60 s. The events registered in a line
in Test condition are not saved in the archive and do not trigger the outputs or the light and sound
signaling. The indication for a line in Test condition is a text message in the display field for the
respective line.
LOCAL SOUNDER – a sounder built-in the fire extinguishing control panel.
NON-FATAL FAULT CONDITION – fault condition that allows the fire extinguishing control panel
to continue operation. The non-fatal fault condition is not usually a system fault condition. The
indication is common light indication, local sound indication and text messages on the LCD display.
ACCESS LEVEL – access level to various indications and control functions (See section 5.1).
LOW BATTERY – non-system fatal fault condition due to full discharge of the backup batteries
upon interrupted power supply.
SUPPRESSED OUTPUT – a monitored or relay output, which should be activated (for the
respective Extinguishing stage) but it is switched off manually by the user.
FIRE DETECTING LINE (further in the text only LINE) – a combination of fire detectors,
physically connected by two-wire connection. Maximum 32 fire detectors could be connected in each
line.
FIRE CONDITION STAGE I – phase of Fire condition; upon activation of automatic fire detector
only in one line the fire extinguishing control panel enters Fire condition. It continues until the line is
manually reset by Reset Alarm. The indication for Fire condition stage 1 is common light indication.
Local sound signaling and text messages on the LCD display.
FIRE CONDITION STAGE II – phase of Fire condition when active extinguishing procedure is
started. The fire extinguishing control panel enters this stage in the event of:
а) Fire condition along both fire detecting lines;
Instruction Manual
Revision 6/02.11
Page 5
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
b) Manual button release for forced extinguishing.
The indication for Fire condition stage 1 is common light indication. Local sound signaling and
text messages on the LCD display.
INTERRUPTED LINE, MONITORED OUTPUT OR MONITORED INPUT – non-system non-fatal
fault condition entered when parameters lower than the threshold value are registered.
RELAY OUTPUT – a relay, potential-free switching outputs provided for controlling external
executive devices.
MANUAL RELEASE – condition entered by the fire extinguishing control panel in the event of
Fire condition stage II, regardless the status of the Fire detecting lines. The manual release is defined
by “on” status of the monitored input „Manual Release”.
MANUAL MODE – condition when the fire extinguishing control panel could release the
extinguishing devices only by manual release command. The manual mode is defined by “on” status
of the monitored input „Mode Select”. The mode indication is an individual light indication.
SYSTEM FAULT CONDITION – fault condition due to a fault in the fire extinguishing control
panel (system’s) component panel. The system fault condition could be fatal or non-fatal. The
indication is common light indication, local sound indication and text messages on the LCD display.
REMOVED FIRE DETECTOR /FD/ – non-system non-fatal fault condition entered when a
removed fire detector in a line is registered. In order this function to be utilized follow the special
diagram for connection (See section 5.2.).
LINE STATUS, MONITORED OUTPUT OR MONITORED INPUT– the current status of a line,
monitored output or input: duty mode; fire condition (only for the fire detecting lines); fault condition
(specifying the type of the fault condition).
FATAL FAULT CONDITION – fault condition that prevents the fire extinguishing control panel, or
the part of it related to the communication with the user, from continuing its operation. The fatal fault
condition is usually a system one, except Law Battery fault condition. The indication is common light
indication, local sound indication and text messages on the LCD display.
2. Technical data
Fire detecting lines
− For extinguishing control
− Without extinguishing control
− Maximum number of fire detectors in a line
− Type of the connecting line
− Maximum resistance of a loop
− Output resistance of the line
-
2
1
32
two-wire
100Ω
164Ω
2.1. Current thresholds in a line per default parameters for:
♦ 0÷3mA*
- interruption
♦ 3÷12mA*
- duty mode
♦ 12÷60mA*
- fire condition
♦ >80mA
- short circuit
− * It is possible the current in the lines for interruption, duty mode and fire condition to be
adjusted (13.4.2.1.).
2.2. Monitored outputs for control the fire extinguishing control panel performance:
Instruction Manual
Revision 6/02.11
Page 6
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
− Type
- balanced
2.3. Monitored outputs for the sound-light indication
− Type
− Electrical characteristics
- potential relay
- (24±3)V/0.5 A
2.4. Monitored output for the extinguishing devices
− Type
− Electrical characteristics
- potential relay
- (24±3)V/1.5A
2.5. Relay outputs for common purpose
− Type
− Electrical characteristics
- potential free, switching
- 3A/125VAC; 3A/30VDC
2.6. Relay output for fault condition
− Type
− Electrical characteristics
- potential free, switching
- 3A/125VAC; 3A/30VDC
2.7. Relay output for fire alarm
− Type
− Electrical characteristics
- potential free, switching
- 3A/125VAC; 3A/30VDC
2.8. Performance characteristics
− Control over the lines, the monitored inputs and outputs for fault condition (short circuit
and interruption) and automatic reset
− Control over the lines for removed fire detector and automatic reset
− Ability to set the evacuation time
− Ability to set the time when the extinguishing executive device is switched on
− Built-in sounder for fire alarm first stage – one tonal, discontinuous, can be switched off
− Built-in sounder for fire alarm second stage – one tonal, continuous, can be switched off
− Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
− Built-in real time clock
− Set of test modes and options for adjustment:
♦ Setting the clock;
♦ Check ups on light and sound indications;
♦ Test of the fire detecting lines;
♦ Adjustment of outputs and integrated external devices;
♦ Current measurement in the fire detecting lines;
♦ Programming of parameters and modes of operation;
♦ Remote programming of the parameters from distant operator control point;
− Energy independent archive of registered events by the fire extinguishing control panel
with the events type, date and hour – up to 100 events;
− Interfaces for communication with external devices - RS-485 and CAN 2.0
2.9. Indications of registered events
− Light indication
− Text message
− Sound signaling
- LED
- LED display 4 lines 20 characters per line,
Cyrillic, backlit
- built-in sounder
2.10. Power supply
2.10.1. Mains
− voltage
− frequency
- 220/230V
- 50/60Hz
2.10.2. Back up batteries
− battery type
− number of batteries
− connection
- led, gel electrolyte
- 2 pcs
- serial connection
Instruction Manual
Revision 6/02.11
Page 7
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
−
−
−
−
nominal voltage of the back up battery
nominal capacity C20
extreme discharge voltage
charge voltage
-
2x12V
(7-12)Ah
21V
28,2V
2.10.3. Consumption on back up batteries supply
− At 24V
2.10.4. Power supply to external devices
− Voltage
− Maximum current value (including current
of monitored outputs )
- < 120mA
- (24±3)V
- 2,5А
2.11. Dimensions
− Overall dimensions
- 450х355х115mm
2.12. Weight
− weight (batteries not included), maximum
- 6,6kg
3. Contents of delivery
3.1. Fire extinguishing control panel
− Fire detecting control panel FS5200Е
− Resistors 3,0kΩ/ 0,25W
− Resistors 1,5kΩ/ 0,25W
− Diode 1N4004
− Jumper for the back up batteries
− Fuse 4A
− CD (Instruction manual,Operator’s manual)
− Packing
- 1 pc.
- 11 pcs.
- 5 pcs.
- 1 pc.
- 1 pc.
- 2 pcs.
- 1 pc.
- 1 pc.
4. Installation and arrangements
When fire detectors and periphery devices are integrated in the fire extinguishing control panel,
avoid arranging wires in closed loops; it will reduce the control panel’s resistance to electro magnetic
interferences.
4.1. To mount the control panel
− unpack the control panel;
− put the dowels on the determined places for fixing the control panel;
− fasten the control panel to the dowels through the three holes provided on the chassis.
4.2. Description of inputs and outputs. Periphery devices assembly to the control panel.
All connections are to be made by means of terminals, mounted on the printed circuit board. Be
advised, that the total consumption of the voltage powering the external devices (terminal “+ 28V”)
plus the consumption of the monitored outputs shall not exceed 2.5A in heavy duty mode.
♦ “L1”, “L2” – Inputs for switching automatic Fire detectors. In Fire condition an
extinguishing procedure starts along both lines according to set up algorithm.
♦ “L3” – Fire detecting line input.
♦ “Manual Release” – Input with line status monitoring. The input sends a signal to the
control panel from a manual button to start the extinguishing procedure.
♦ “Mode Select” - Input with line status monitoring. The input sends a signal to the control
panel from a switch for the operating mode. The modes are Manual-Automatic and Manual.
“Hold” - Input with line status monitoring. The input sends a signal to the control panel
Instruction Manual
Revision 6/02.11
Page 8
of 63
UniPOS
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
Fire Extinguishing Control Panel FS5200Е
from a manual button or controlled contact for holding (delaying) the extinguishing
procedure.
“On/Off Exting” - Input with line status monitoring. The input sends a signal to the control
panel from a switch for disabling the extinguishing procedure.
“Low Press” - Input with line status monitoring. The input sends a signal to the control
panel from pressostat contact, balance or other device to show the extinguishing agents
draining.
“GND” – Terminal for sending GND potential to the periphery devices.
“Еxting” – Active level output with line status monitoring. The output switches the
extinguishing automation valves on.
“S2 Sounder” – Active level output with line status monitoring. The output switches the
sound-light indication on in Fire condition stage II.
“S1 Sounder” – Active level output with line status monitoring. The output switches the
sound-light indication on in Fire condition stage I.
“Rele Fire” – Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition of the control panel, registered by the fire detecting
lines.
“Rel Fault” – Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fault condition of the control panel.
“+28V” – Three terminals for supplying 28V voltage to the periphery devices as well as the
positive potential of the open collectors OK1, OK2 and OK3.
“OK1” – Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel has registered extinguishing reagent leakage.
“OK2” – Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 47k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel is in Disable Extinguishing Mode.
“OK3” – Output open collector /in active status it supplies GND potential, in non-active
status it has potential +28V via resistor 1k/0.125W/. The output controls relays, LEDs and
other devices, with total consumption not exceeding 100mA. The output is active when the
control panel is in manual Mode.
“Rel 2ST” – Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition stage II of the control panel.
“Rel 1ST” – Output, relay, potential free, the line status is not monitored. The output
controls the devices in Fire condition stage I of the control panel.
“CAN” – Terminals to connect the two-wire line of CAN interface. The connection with the
Interactive system IFS7002 /production of UniPOS LTD/ is executed via this interface. A
jumper is provided that shunts the line by 120 ohms. It is needed if the fire extinguishing
control panel is the final point in the interface line. The interface requires resistors 120
ohms to be mounted in both ends of the line.
“RS 485” – Terminals to connect the two-wire line of RS 485 interface. The connection
with a repeater, PC and other devices realized by exchange protocol - UniProtocol
/FS5200E interface/ is executed via this interface. As the case with CAN interface, a
jumper is provided here too with the same functions.
“┴” – Terminal to connect a third wire /screen/ of the interfaces cable.
Instruction Manual
Revision 6/02.11
Page 9
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
A
RS485 term
CAN
Rel
1ST
Rel
2ST
OK1
+28V
OK2
+28V
OK3
+28V
NC
NO
Jump Rel 1ST
Relay output in condition Fire Alarm Phase 2
Output Open Collector – Active in case of extinguisher leakage (+28V)
Output Open Collector – Active in case of extinguishind disable (+28V)
Output Open Collector – Active in manual mode (+28V)
NO NC C
REL Fault
NO
Relay output in Fault Alarm condition
NO
Rele
Fire
NC
Jump relay Fire
Relay output in condition Fire Alarm Phase 1
GND
NC
Jump Rel 2ST
Interface RS 485 (repeater, PC and other devices)
B
L
CAN term
Jump (CAN)
RS485
H
Jump (RS485)
Interface CAN (join to system IFS7002)
Relay output in Fire condition
3k
+ S2 Sounder
3k
+ S1 Sounder
Sounder Fire Alarm Phase 1
(28V/0,5A)
Sounder Fire Alarm Phase 2
(28V/0,5A)
1,5 k
1,5k
1,5k
Button for extinguishing delay
1,5k
Switch mode manual/manual-automatic
3k
Mode
Select
Switch for extinguishing disable
3k
Hold
3k
On/Off
Exting
Switch for monitoring
extinguisher leakage
3k
Low
Press.
FS5200E
+
Exting
Device Extinguishing
(28V/1,5A)
1N4004
1,5k
FD
3k
Fire Alarm Line 1
FD
3k
Fire Alarm Line 2
FD
3k
Fire Alarm Line 3
3k
1,5k
Manual
Release
Buttons manual
extinguishing activation
+ L1 -
FD
FD
+ L2 -
FD
FD
+ L3 -
FD
FD
Drawing1
Instruction Manual
Revision 6/02.11
Page 10
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
4.2.1. Description and mounting of devices to L1, L2 and L3 inputs
Connect a two-wire line at L1, L2 and L3 inputs for connection with the Fire detectors. The line
total resistance shall not exceed 100Ω. The recommended wire section depending on the lines length
is:
♦ To 500 m
-cable 2 х 0.5 mm2
♦ To 1000 m
-cable 2 х 1.0 mm2
♦ To 1500 m
-cable 2 х.1.5 mm2
It is recommended to make a check with a multicet before connecting the fire detecting line to the
fire extinguishing control panel. If the line is installed correctly (with mounted final resistor 3kΩ /
0.25W) between the plus and minus of the cable entering the fire extinguishing control panel the
measured resistance should be 3kΩ (+/-10%). Also when measuring both wires to ground the
multicet should show no connection or leakage.
Make the connection to the terminals – “+ Lx -” (where “x” is the line number). Observe the shown
polarity (Drawing 2).
First
detector
Last
detector
1N5819*
- Lx +
FS5200E
1N5819*
+OUT
5
+IN
FD80xx
-IN/OUT
2
RI/KL-
4
FD30xx
3k/0.25W
1
* Diode 1N5819 or similar
Drawing 2
Use automatic fire detectors FD3000 or FD8000 series or other compatible automatic fire
detectors. Mount resistor 3 kΩ / 0.25W on the last fire detector in the line.
Mount diodes, for example 1N5819 or similar in the shown direction if you are to use the fire
extinguishing control panel function to register Fault condition – removed fire detector.
Maximum 32 fire detectors could be mounted to one line regardless of their type.
When mounting the fire detectors take into consideration the specific technical characteristics of
the fire detector with the fire extinguishing control panel parameters for the current threshold in the
different conditions. Change the current threshold from Set up menu.
Current thresholds in a line with default parameters for the conditions:
♦ 0÷3mA*
- interruption
♦ 3÷12mA*
- duty mode
♦ 12÷80mA*
- fire condition
♦ >80mA
- short circuit
Mount fire detectors on Lines 1 and 2 in the premise where the extinguishing will be performed.
The first and the second line are in a logical dependence „I”; the fire extinguishing control panel enters
Fire condition stage II if only both lines are activated and the extinguishing algorithm is possible to be
executed.
Line 3 is only Fire detecting and it serves for fire protection of the adjoining premises to the
extinguished zone. When this line is activated it switches on the outputs for Fire condition stage I as
well as the common output for Fire condition. This line is not included in the extinguishing algorithm
logic. Line 3 can be assumed as a standard line of a Fire control panel.
Instruction Manual
Revision 6/02.11
Page 11
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
4.2.2. Description and mounting of devices to Manual Release input
Connect a two-wire line to the Manual Release input for connection with the manual release
buttons for extinguishing activation. It is possible to mount maximum three buttons. The line is
balanced and it is monitored for interruption and short circuit. Install resistors to the button terminals
as shown in the connecting diagrams to monitor the condition. Install resistor 3k to the last button if 2
or 3 buttons are mounted (Drawing 3).
Connecting diagram with 1 button
Button for manual
activation of the extinguishing
Manual
Release
FS5200E
3k/
1.5k/
0.25W
0.25W
Connecting diagram with 2 buttons
Button 1
Button 2
Manual
Release
FS5200E
1.5k/
0.25W
3k/
1.5k/
0.25W
0.25W
Connecting diagram with 3 buttons
Button 1
Button2
Button 3
Manual
Release
FS5200E
1.5k/
1.5k/
0.25W
0.25W
3k/
1.5k/
0.25W
0.25W
Drawing 3
When the contact is closed the fire extinguishing control panel accepts the button to be active.
4.2.3. Description and mounting of devices to Mode Select input
Connect a two-wire line to the Mode Select input for connection with a switch to select the fire
extinguishing control panel mode – Manual-Automatic or Manual. The line is balanced and it is
monitored for interruption and short circuit. Install the two resistors to the switch terminals as shown in
the connecting diagram to monitor the condition.
When the contact is closed the fire extinguishing control panel accepts Manual Mode; when it is
opened – Manual-Automatic Mode. Output Open collector type is activated in Manual Mode. That
output could be used as switch indication, if this option is provided.
Instruction Manual
Revision 6/02.11
Page 12
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Switch modes
Manual/Manual-automatic
Mode
Select
FS5200E
1.5k/
0.25W
4.2.4. Description and mounting of devices to Hold input
Connect a two-wire line to the Hold input for connection with a switch to activate hold
extinguishing function. The line is balanced and it is monitored for interruption and short circuit. Install
the two resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 4).
Switch
Extinguishing delay
Hold
FS5200E
3k/
1.5k/
0.25W
0.25W
Drawing 4
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set up
> Input/Outputs > Hold input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the
fire extinguishing control panel to accept Hold Extinguishing function.
4.2.5. Description and mounting of devices to On/Off Exting input
Connect a two-wire line to the On/Off Exting input for connection with a switch to disable
extinguishing. The line is balanced and it is monitored for interruption and short circuit. Install the two
resistors to the switch terminals as shown in the connecting diagram to monitor the condition
(Drawing 5).
Switch
Extinguishing disable
On/Off
Exting
FS5200E
3k/
1.5k/
0.25W
0.25W
Drawing 5
When the contact is closed the fire extinguishing control panel accepts Disable Extinguishing.
Output Open collector type is activated in Disable Extinguishing. That output could be used as switch
indication, if this option is provided.
Instruction Manual
Revision 6/02.11
Page 13
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
4.2.6. Description and mounting of devices to Low Press input
Connect a two-wire line to the Low Press. input for connection with a pressostat contact, balance
or other devices registering a Fault condition in the extinguishing installation. The line is balanced and
it is monitored for interruption and short circuit. Install the two resistors to the switch terminals as
shown in the connecting diagram to monitor the condition (Drawing 6).
Pressure
Low
Press.
FS5200E
3k/
1.5k/
0.25W
0.25W
Drawing 6
Set up the input active status: OPEN or CLOSED contact from menu System functions > Set
up > Input/Outputs > Low Press input.
Attention! The active status of the default parameters is OPEN contact of the switch in order the
fire extinguishing control panel to accept the function Leaked extinguishing agent or Fault condition.
4.2.7. Description and mounting of devices to “Exting” output
Connect a two-wire line to the Exting output for connection with a magnetic valve or other device
to activate the extinguishing automation. The line is balanced and it is monitored for interruption and
short circuit. Install a diode 1N4004 or similar to the executive device terminals in the direction as
shown in the connecting diagram as the valve winding resistance shall be in the range: 30Ω ÷ 3kΩ.
(Drawing 7).
Install a parallel resistor 3kΩ / 0.25W and a serial diode 1N5401 on the line if the winding
resistance is less than 30Ω (Drawing 8).
Connecting diagram if the winding valve active resistance is from 30 Ω to 3к Ω
+ -
Exting
FS5200E
Electromagnetic
valve
V
1N4004
Rv - 30 Ohms up to 3 k
Drawing 7
Connecting diagram if the winding valve active resistance is less than 30 Ω
Instruction Manual
Revision 6/02.11
Page 14
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Exting
FS5200E
+ -
3k/
0.25W
1N4004
Electromagnetic
valve
V
1N5401
Rv - < 30 Ohms
Drawing 8
Upon the output activation the supplied voltage (24±3)V is with load-carrying capacity of 1.5А.
The time for output activation could be set from 2 to 255 seconds from menu System functions >
Set up > Extinguishing time and it depends on the type of the used executive device. The default
setting is 10 seconds.
4.2.8. Description and mounting of devices to Sounder S1 and Sounder S2 outputs
Connect a two-wire line to the Sounder output for connection with sound and light signaling
devices. The line is balanced and it is monitored for interruption and short circuit. Install a resistor
3kΩ/0.25W to the signaling device terminals to monitor the condition (Drawing 9).
- Sx +
Sounder
FS5200E
3k/
0.25W
Drawing 9
Upon the outputs activation the supplied voltage (24±3)V is with load-carrying capacity of 0.5А.
The outputs are activated for Fire condition stage I and Fire condition stage II, respectively.
The fire extinguishing control panel provides the option for Sounder S1 output disable from menu
System functions > Disables > Disable S1 output .
4.2.9. Description and mounting of devices to outputs OK1, OK2 and OK3 open
collector type
OKx outputs send a signal to relays, LEDs and other devices to follow and monitor the fire
extinguishing control panel condition. The outputs are not monitored for the line status.
28V
+28V
47k
OKx
GND
Drawing 10
Upon activation of the outputs GND potential is supplied with load-carrying capacity of 0.1А.
The internal diagram of output Open collector type is presented on the drawing (Drawing 10).
4.2.10. Description and mounting of devices to Rel Fire output
Rel Fire is a potential free, relay output. The logic of the contact - Normally Open or Normally
Closed could be adjusted by means of a jumper. The output is not monitored. The output is activated
in Fire condition along one or both fire detecting lines.
Instruction Manual
Revision 6/02.11
Page 15
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
4.2.11. Description and mounting of devices to Rel 1ST and Rel 2ND outputs
Rel 1ST and Rel 2ND are potential free, relay outputs. The logic of the contact - Normally Open or
Normally Closed could be adjusted by means of a jumper. The outputs are not monitored. The
outputs are activated in Fire condition stage I and Fire condition stage II, respectively. The fire
extinguishing control panel provides the option to disable the activation of Rel 1ST and Rel 2ND outputs
from menu System functions > Disables > Disable Rel 1ST / Disable Rel 2ND.
4.2.12. Description and mounting of devices to Rel Fault output
Rel Fault is a potential free, relay output, as both relay contacts are possible Normally Open or
Normally Closed. The output is not monitored.
4.2.13. Description and mounting of devices to RS485 interface terminals
RS485 interface is designed to transmit information and to receive commands from FS5200R
repeater. The following connection configurations are possible:
− One fire extinguishing control panel and one repeater
− One fire extinguishing control panel and up to 6 repeaters
− Up to 15 fire extinguishing control panels and 1 repeater
− Up to 6 repeaters and up to 10 fire extinguishing control panels (If less than 6 repeaters
are installed they could be substituted by fire extinguishing control panels, i.e.
configuration of 3 repeaters and 13 fire extinguishing control panels, etc.)
FS5200R repeater receives information from all fire extinguishing control panels as it indicates
the occurred events by sound signaling, light indication and text messages. It is also possible a
remote fire extinguishing control panel to be reset.
RS485 interface could be used also for communication with other intelligent devices and PCs.
The connection between the devices along RS485 is parallel connection. Observe the
requirement potential A and B not to be crossed. The maximum distance between the end devices is
1000 meters. Jumper to shunt the line by 120 ohms has to be installed on the first and the last device
regardless the line length. On all other devices the jumper has to be removed (Drawing 11).
End device
FS5200x
120
120
А В
End device
FS5200x
FS5200x
J
120
А В
А В
RS485
RS485
RS485
RS485
RS485
А В
А В
120
120
FS5200x
J
FS5200x
Drawing 11
4.3. Power supply connection
Connect a feeding cable to the terminal with mains fuse, observing the following positions
(Appendix 3):
− P – power wire “Phase”;
Instruction Manual
Revision 6/02.11
Page 16
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
− N – power wire “Null”;
− Ground - safety ground wire.
The cable shall be double insulated and of 0,5mm2 section for the power supply wires, and of
1,5mm2 section for the safety ground wire.
The other end of the feeding cable is connected to the mains power supply by means of junction
box.
The mains power supply of the fire control panel shall be in a separate loop.
5. General information
5.1. Access levels
4 levels of access to the variable indications and control functions of FS5200Е are available.
5.1.1. Access level 1
All persons who would presumably find out and react to alarm upon fire condition or fault
condition have access to level 1.
The following actions are accessible:
− Displaying suppressed messages for Fire condition stage I, Fire Condition stage II, Fault
condition, Disabled components;
− Forced proceeding from phase Fire condition stage I to phase Fire condition stage II ;
− Suppressing the local sounder;
− Displaying the status of the lines and the monitored outputs (see section 12.5);
All light indicators are visible.
5.1.2. Access level 2
The personnel in charge of the fire protection have access to level 2; they shall be trained and
authorized to operate the fire control panel in the following conditions:
− Duty Mode;
− Fire condition stage I;
− Fire condition stage II;
− Fault condition;
− Disabled component;
− Information and adjustment.
To enter Access level 2, turn the key on the front panel of the fire extinguishing control panel into
position
.
The following features of the fire extinguishing control panel are accessible:
− All features accessible at Level 1;
− Switching off the outputs, activated upon fire condition;
− Exit of Fire condition;
− System functions of the fire extinguishing control panel except entering Set up Mode
(see section Error! Reference source not found.).
5.1.3. Access level 3
Accessible for personnel trained and authorized for:
− Reconfiguration of specific data – of the protected site or of the fire extinguishing control
panel – saved in the memory;
− Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this
sublevel the functions for reconfiguration of specific data for the protected site or the fire extinguishing
control panel are accessible.
Level 3, sublevel 3B is accessed when the fire extinguishing control panel is opened. The
following features are accessible:
− Replacing a burnt fuse;
− Adding, removing or replacing a module;
− Connecting fire detecting lines and executive devices.
Instruction Manual
Revision 6/02.11
Page 17
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
5.1.4. Access Level 4
Accessible for personnel trained and authorized by the Producer to repair the fire extinguishing
control panel and to modify the software.
Special means are required to enter this level.
5.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
function of the control buttons. Appendix 1 shows the front panel of FS5200 with the indications and
buttons for control.
Table 1
Conditions of the fire extinguishing control panel
All conditions The fire extinguishing control panel is power
supplied
Fire condition – Fire condition Stage I and Stage II
Fire condition – Fire condition Stage I
Fire condition – Fire condition Stage II
Manual Mode – a signal for manual mode of
extinguishing control is given
Manual Mode – a signal for manual mode of
extinguishing control is given
Disabled extinguishing – a signal disabling the
extinguishing is given
Extinguishing held – a signal holding the
extinguishing is given
Fire Condition and Fault Condition – the sound
indication is suppressed
Fire condition Stage I The fire condition stage I outputs are suppressed
Fault condition - All faults except for Battery Low
Fault condition – System Error and new
Configuration
Fault condition – Fault in mains supply or backup
battery
Fault condition – fault condition in monitored line
Fault condition – fault condition Low pressure in the
extinguishing installation
Disabled component Disabled line or monitored output
Fire condition Stage I
Fire condition Stage II
Instruction Manual
Revision 6/02.11
Indication
Indicator Power Supply –
continuous green light
Individual indicators for
Fire condition in the fire detecting
lines
Common indicator Fire condition
Stage I –
continuous red light
Common indicator Fire condition
Stage II –
flashing red light during the
evacuation time and continuous
red light after the automated
extinguishing is switched on
Indicator Manual Mode continuous yellow light
Indicator Manual-Automatic Mode continuous yellow light
Indicator Disabled Extinguishing continuous yellow light
Indicator Extinguishing Held - continuous yellow light
Indicator Stop Alarm - continuous
red light
Indicator Suppressed Outputs continuous red light
Common indicator Fault Condition
- continuous yellow light
Indicator System Error continuous yellow light
Indicator mains Supply Fault continuous yellow light
Indicator Monitored Line Fault continuous yellow light
Indicator Low Pressure Fault continuous yellow light
Indicator Disabled Component –
continuous yellow light
Local sounder – discontinuous signal: 4
sound impulses for 1 s, followed by 1 s
break
Local sounder – continuous signal
Page 18
of 63
UniPOS
Conditions of the fire extinguishing control panel
Fault condition - All faults except for Battery Low
Fault condition Low battery
Instruction Manual
Revision 6/02.11
Fire Extinguishing Control Panel FS5200Е
Indication
Local sounder – discontinuous signal: 1 s
sound, followed by 1 s break
Local sounder – discontinuous signal: 1 s
sound, followed by 3 s break
Page 19
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Table 2
Means of control
Condition of the fire
extinguishing
control panel
Access
level
Level 1
Access level 2 key
Level 2
Button Line Reset
Fire condition
Button
Fire condition, phase
Fire condition Stage I
Level 2
Level 2
Outputs
Fire condition, phase
Level 2
Fire condition Stage II
Button Alarm
Fire condition Stage I
or Stage II and Fault
condition*
Duty Mode, Fire
condition, Fault
condition*, Test and
Disabled component
Information and
Control Mode
Button Menu
Set up Mode
Button Down
Button Up
Button Cancel
operation
Status
Status
Output from Fire Condition stage I or Fire
condition stage II initiated on the display
- if outcomes for Fire condition Stage I are
activated – to suppress them;
- if outcomes for Fire condition Stage I are
suppressed – to activate them
- If the common output for fire condition is
activated – to suppress it;
- if there is no activated common output for
fire condition – to activate it
Level 1
To suppress/activate the local sounder
Levels 1
and 2
To enter Information and Control Mode
Levels 1
and 2
Level
3А
- To enter the selected menu;
- To execute the selected command;
- To save the modified parameter
Fire condition
Levels 1 and 2
To show on the display the next message for fire condition
Information and
Levels 1 - To show on the display the next element
from the menu;
Control Mode
and 2
- To move the cursor;
Level
Set up Mode
- To modify the selected parameter
3А
Levels 1 To show on the display the previous
Fire Condition
and 2
message for fire condition
Information and
Levels 1
- To show on the display the previous
Control Mode
and 2
element from the menu;
Level
- To modify the selected parameter
Set up Mode
3А
Information and
Levels 1 - To exit a function without saving changes
in the parameter; the command will not be
Control Mode
and 2
executed;
Level
- To exit the current menu and to move to
Set up Mode
3А
an upper hierarchy menu
* Not operating in Fault condition (fatal fault condition except New Configuration).
5.3. Conditions of the Fire Extinguishing Control Panel
The fire extinguishing control panel FS5200Е monitors the fire detecting lines and the monitored
outputs as it scans consecutively their status. Depending on the current the fire extinguishing control
panel could be in Duty Mode, in Fire condition or Fault condition (short circuit or interruption).
Instruction Manual
Revision 6/02.11
Page 20
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Depending on the measured parameters the inputs could be in Fault condition (short circuit or
interruption) or active status. Simultaneously the monitored outputs are followed constantly for in Fault
condition (short circuit or interruption).
The fire extinguishing control panel FS5200Е operates in eight main conditions: Duty Mode, Fire
condition Stage I, Fire condition Stage II, Fault Condition, Disabled component, Test Mode,
Information and Control Mode and Set up Mode.
At any time the fire extinguishing control panel could be in each one of these conditions or in
random combination of the conditions: Fire condition Stage I, Fire condition Stage II, Fault Condition,
Disabled component, Test Mode, Information and Control Mode.
Duty Mode, Set up Mode and Remote Control cannot be combined with another condition:
− the fire extinguishing control panel enters Duty Mode when it is not in any of the other
conditions;
− to enter Set up Mode and Remote Control the fire extinguishing control panel has to exit the
other conditions.
6. Duty Mode
6.1. Description
The fire extinguishing control panel is in Duty Mode, when it is not in any other of the rest eight
possible conditions.
6.2. Indication
6.2.1. LED and sound indication
In Duty Mode only the green LED indicator is activated
(Power supply) and the yellow
(Manual Mode – activated if only the fire extinguishing control panel is in Manual
indicator
Mode. The local sounder is off.
6.2.2. Text message
The display is divided into
panels. The last line shows the
condition of both Fire detecting
lines that shall be in Protection
status. The display also shows the
message Protection
and the
current astronomic time:
1 2 3
6.3. Using the keypad
The only accessible button in Duty Mode is
enters Information and Control Mode (p.12).
(Menu). Press it and the fire control panel
7. Fire Condition Stage I
7.1. Description
The fire extinguishing control panel enters Fire condition phase Fire condition Stage I, when
Instruction Manual
Revision 6/02.11
Page 21
of 63
UniPOS
-
Fire Extinguishing Control Panel FS5200Е
An automatic fire detector is activated only along one of the Fire detecting lines;
An automatic fire detector is activated along the first or the second or the third line
To exit this condition press button
7.2. Indication
7.2.1. LED and sound indication
In this condition:
- The indicator
- The indicator
at Access level 2
(Power Supply) illuminates in green light;
(Fire condition Stage I) illuminates in red light;
- The indicator of the respective line in Fire condition
illuminates in red light;
- If the outputs for phase Fire condition Stage I are suppressed by button
LED indicator of the button illuminates in continuous red light.
- If the sound indication is suppressed by button
illuminates in continues red light.
(Outputs), the
(Alarm) the LED indicator of the button
- The indicator
(Manual Mode) or the indicator
in yellow light depending on the selected mode of operation.
(Manual-Automatic Mode) illuminates
The local sounder produces discontinuous signal.
7.2.2. Text message
In this condition the display is
divided into two text fields. The top
one shows the condition of the
control panel, the bottom one – the
condition of the lines.
Example:
Fire
condition
is
registered along the first line. The
indicator of line 1 and the indicator
for Fire condition Stage I illuminate
in red light. The text message
shows the Fire condition stage and
the line in which the fire
extinguishing control panel is in
Fire condition.
1 2 3
Potential free relays Rele 1St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder
output S1.
7.3. Using the keypad
Button
Access
level
all
Button
(Alarm)
Instruction Manual
Revision 6/02.11
Operation
Press it to:
- suppress the local sounder;
- activate the local sounder if
the fire extinguishing control
panel is in Fire condition
Stage I or Fault condition
and the local sounder has
been suppressed by
previous pressing of the
same button.
Additional information
The button operation is
reversive i.e. press it once to
change the current condition
alternatively – suppressed or
activated local sounder.
The
LED indicator illuminates if the
active condition of the local
sounder is suppressed.
The
local
sounder
is
activated again:
Page 22
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
-
-
Button
(Outputs)
Button
(Line Reset)
2, 3 and
4
Press the button to:
− suppress
the
outputs
activated for phase Fire
condition Stage I
− to activate the suppressed
outputs, if any
when
the
fire
extinguishing
control
panel
enters
Fire
condition Stage II;
upon Fault condition.
Access level 2 is required to
for operation with this button. The
key on the front panel should be
in position
. The button
operation is reversive i.e. press it
once to change the current
condition
alternatively
–
suppressed or activated outputs.
The LED indicator illuminates if
the
active condition is
suppressed outputs.
Access level 2 is required to
2, 3 and
Press it to force the fire
4
extinguishing control panel to exit for operation with this button. The
Fire condition Stage I and to reset key on the front panel should be
the line that was in Fire condition
.
(the power supply is switched off for in position
3s).
all
Press it to enter Information
and Control Mode.
all
Press it to exit Information and
Control Mode. The main screen for
the current status Fire condition
Stage I is visualized.
Button
(Menu)
Button
(Cancel)
8. Fire Condition Stage II
8.1. Description
The fire extinguishing control panel enters Fire condition phase Fire condition Stage II, in the case
of:
а) fire condition along both fire detecting lines;
б) manual button activation for forced extinguishing.
In this phase the active extinguishing procedure is initiated.
In phase Fire Condition Stage II the following steps are formed connected with the algorithm of
the extinguishing procedure:
− Evacuation time;
− Activation of the devices to Release the extinguishing mixture
8.2. Indication
8.2.1. LED and sound indication
In Fire Condition Stage II and the fire extinguishing control panel in the evacuation step the LED
indicator illuminates in red flashing light
Instruction Manual
Revision 6/02.11
(Fire Stage II).
Page 23
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
In Fire Condition Stage II and expired evacuation time the fire extinguishing control panel
activates the extinguishing devices and the LED indicator
continuous light.
The indicator
(Manual Mode) or the indicator
yellow light depending on the selected mode of operation.
(Fire Stage II) illuminates in red
(Manual-Automatic Mode) illuminates in
The local sounder produces continuous signal. If the sound signaling is suppressed by button
(Alarm), the LED indicator of the button illuminates in continuous red light.
8.2.2. Text messages during the evacuation step and fire along both lines.
The display shows:
The message EVACUATION
and the remaining time for the
activation of the extinguishing
devices
message FIRE STAGE 2 and
information for the current status
of the lines:
Example: Fire condition along line
1 and line 2. The fire extinguishing
control panel is in evacuation
phase. The indicator for Fire
1 2 3
condition Stage II illuminates in
flashing red light. The individual
indicators for line 1 and line 2 are
illuminated too.
Text message for the phase of fire alarm, the remaining time for activation of the extinguishing
devices and the current status of the lines is visualized on the display. The local sounder produces
continuous signal. Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is
supplied to the sounder output S2.
8.2.3. Text messages during the evacuation step and manual button activation.
The display shows:
The message EVACUATION
and the remaining time for the
activation of the extinguishing
devices
message FIRE STAGE 2
Message showing manual
activation
and information for the current
status of the lines
1 2 3
8.2.4. Text messages when the extinguishing device is activated.
Instruction Manual
Revision 6/02.11
Page 24
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
The display shows:
The message ATTENTION
GAS! and EXTINGUISHING ON
indicating that the extinguishing
agent is released.
Information for the current status
of the lines:
This indication could be
suppressed by the screens in
Fire condition. The suppressed
messages could be displayed in
Information and Control Mode.
1 2 3
Example: Fire condition along line 1 and line 2. The fire extinguishing control panel is in phase to
start extinguishing procedure. The indicator for Fire condition Stage II illuminates in continuous red
light. The individual indicators for line 1 and line 2 are illuminated too. The display shows warning
messages and the condition of the fire detecting lines. The local sounder produces continuous signal.
Potential free relays Rele 2St and Rele Fire are activated. Voltage 28V DC is supplied to the outputs
S2 and Exting. .
Note: The entry of the fire extinguishing control panel in Fire condition along a new line (e.g. the
3 one) is indicated by the standard sound and light indication and text messages.
rd
8.3. Using the keypad
Button
Access
level
all
Button
(Alarm)
Button
(Outputs)
2, 3 and
4
Operation
Press it to:
- suppress the local sounder;
- activate the local sounder if
the fire extinguishing control
panel is in Fire condition
Stage II or Fault condition
and the local sounder has
been suppressed by
previous pressing of the
same button.
Additional information
The button operation is
reversive i.e. press it once to
change the current condition
alternatively – suppressed or
activated local sounder.
The
LED indicator illuminates if the
active condition of the local
sounder is suppressed.
The
local
sounder
is
activated again:
- when
the
fire
extinguishing
control
panel
enters
Fire
condition long a new line;
- upon Fault condition.
Press
the
button
to
Access level 2 is required to
suppress/activate the fire relay for operation with this button. The
key on the front panel should be
Rele Fire
in position
. The button
operation is reversive i.e. press it
once to change the current
condition
alternatively
–
suppressed or activated outputs.
The LED indicator illuminates if
the
active condition is
suppressed outputs.
Instruction Manual
Revision 6/02.11
Page 25
of 63
UniPOS
Button
(Line Reset)
Fire Extinguishing Control Panel FS5200Е
Access level 2 is required to
2, 3 and
Press it to force the fire
4
extinguishing control panel to exit for operation with this button. The
Fire condition Stage II and to reset key on the front panel should be
the lines that were in Fire condition
.
(the power supply is switched off for in position
3s).
8.4. Using the switch for mode selection (Automatic/Manual/Disabled)
Use the switch for mode selection
to prolong or cancel the
evacuation if it turns out that it is
not necessary the extinguishing
devices to be activated.
Turn the switch to the right,
to disable the
in position
activation of the extinguishing
devices.
In addition the indicators for
disabled extinguishing start to
illuminate in yellow light. The
1 2 3
display shows a text message for
the entered disable and the fire
condition stage.
Turn the switch to position Manual to enable the extinguishing and the evacuation time to be counted
down again.
9. Fault condition
9.1. Description
The fire extinguishing control panel enters Fault Condition when any of the events below have
been registered:
− Battery low – backup batteries discharged due to interruption of mains supply;
− Fault in a processor programme;
− Fault in the real time clock;
− Fault in the line – removed fire detector, short circuit or interruption;
− Fault in a monitored output – short circuit or interruption;
− Fault in a monitored input – short circuit or interruption;
− Signal for lack of extinguishing agent;
− Fault in the mains supply;
− Fault in backup battery supply;
− Short circuit to ground wire;
− Fault in the positive supply of the lines;
− Fault in the negative supply of the lines;
− Fault in the power supply of external devices.
Upon fault condition Short circuit to ground wire the following faults occur:
− Fault condition in a line (removed fire detector) – when the short circuit is to a fire detecting
line element;
− Fault condition in a monitored output (interruption) – when the short circuit is to a monitored
output element.
Fault condition is indicated by text messages on the display. The LEDs indicators provide
additional information.
Instruction Manual
Revision 6/02.11
Page 26
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
9.2. Indication
9.2.1. LED and sound indication
Upon Fault battery low LED indicator is not activated. The local sounder produces a
discontinuous signal (sound for 1s, followed by 3s break). The LCD display illumination is off.
All other fault conditions are designated by indicator
(Fault condition), illuminating in
continuous yellow light. Depending on the specific fault, the following indicators are illuminated too:
− Upon System error - indicator
(System error) in flashing yellow line;
− Upon Fault in a monitored line - indicator
interruption) in continuous yellow light;
(Fault – short circuit or monitored line
− Upon Fault in mains supply or Backup battery supply - indicator
in continuous yellow light;
(Fault in mains supply)
− Upon Fault in the extinguishing device or Extinguishing agent release - indicator
low pressure) in continuous yellow light;
(Fault
The local sounder produces a discontinuous signal. If the sound indication is suppressed by button
(Alarm),the LED indicator of the button illuminates in continuous red light.
9.2.2. Text messages
The fault conditions messages are displayed by priority as given in section 9.1.
The fatal system errors screens suppress all other messages. If more than one non-fatal faults
are registered, they are indicated by priority as the message with the highest priority suppresses the
rest of the fault messages.
Upon registration of a Fault condition, the relay REL Fault is activated, as it closes contact NO
and opens contact NC.
When the fire extinguishing control panel enters Fire condition the messages for Fault conditions
are suppressed. To view the suppressed messages enter Information and Control Mode.
Number ot the faults
Upon registration of a Fault
Type ot the faults
condition the fire extinguishing
control panel displays the respective
light indication and text messages:
-
the common indicator
for
fault
condition
is
illuminated
the specialized indicator
showing the type of the fault
condition is illuminated;
the total number of faults
and the type of the specific
fault are visualized on the
display;
1 2 3
Upon non-fatal faults when the fire extinguishing control panel is not in Fire condition, the
following information screens appear:
Instruction Manual
Revision 6/02.11
Page 27
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
∗ Faults in monitored outputs:
(The field “ЕEЕ” shows the number of the faults;
The field “Status” shows the monitored output
status, i.e. the type of the fault)
∗ Fault in the mains supply:
(The field “ЕEЕ” shows the number of the faults).
In this case the display illumination is off. To turn it
on press the button. 20s after the last pressing of
the button it is off again.
∗ Fault in backup battery supply:
(The field “ЕEЕ” shows the number of the faults).
Duty
17:05:34
Fault:ЕEЕ MONN Status
L1:Dut.L2:Dut.L3:Dut
Duty
17:05:34
Fault:ЕEЕ Flt Mn Power
L1:Dut.L2:Dut.L3:Dut
Duty
17:05:34
Fault:ЕEЕ Flt Battery
L1:Dut.L2:Dut.L3:Dut
∗ Fault in the power supply of external devices –
activated fuse:
(The field “ЕEЕ” shows the number of the faults).
Duty
17:05:34
Fault:ЕEЕ FltPower 28V
L1:Dut.L2:Dut.L3:Dut
∗ Short circuit to grounded wire:
(The field “ЕEЕ” shows the number of the faults).
Duty
17:05:34
Fault:ЕEЕ Fault Earth
L1:Dut.L2:Dut.L3:Dut
∗ Fault in the negative supply:
(The field “ЕEЕ” shows the number of the faults).
Duty
17:05:34
Fault:ЕEЕ FltPower -5V
L1:Dut.L2:Dut.L3:Dut
When the fire extinguishing control panel is in Fire condition, the fault messages are suppressed.
The suppressed messages could be seen in Information and Control Mode.
Upon fault in the Fire detecting line, the type of fault could be seen in the individual field of the
respective line, as the abbreviations mean:
„Sho” – Fault - Short circuit;
„Int” – Fault – interruption;
„ReD” – Fault – Removed fire detector.
9.3. Using the keypad
None of the buttons is active upon fatal fault condition (except for New Configuration).
For all other fault condition 2 buttons are being supported. Where the fire extinguishing control
panel operates in combination of other conditions, their buttons are active too.
Button
Access
Operation
Additional information
level
The button operation is
all
Press it to:
reversive
i.e. press it once to
suppress
the
local
sounder;
Button
change
the
current condition
activate
the
local
sounder
if
(Alarm)
the fire extinguishing control alternatively – suppressed or
activated local sounder.
panel is in Fire condition or
Fault condition and the local
The LED indicator illuminates
sounder has been
if the
active condition of the
suppressed by previous
local sounder is suppressed.
Instruction Manual
Revision 6/02.11
Page 28
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
pressing of the same button.
all
Button
(Menu)
The
local
sounder
is
activated again:
- when
the
fire
extinguishing
control
panel
enters
Fire
condition;
- new
Fault
condition
occurs;
Press it to enter Information
For detailed information how
and Control Mode. All occurred to view all faults in Information
faults could be viewed in Menu View and Control Mode see section
12.
Faults.
10. Disabled component
10.1. Description
The fire extinguishing control panel enters Disabled component after a manual operation,
disabling a fire alarm line or an output.
At access level 2 – Secret switch in position
and menu System Functions> Disables it is
possible the following inputs and outputs to be disabled:
> Disable Line 1 ;
> Disable Line 2 ;
> Disable Line 3 ;
> Disable Rel 1ST ;
> Disable Rel 2ST ;
> Disable Out. S1 .
Upon fire detecting line disable the power supply to the line is switched off and nor processing is
done.
Upon output disable, the respective output is not activated under any circumstances.
10.2. Indication
10.2.1. LED and sound indication
starts to illuminate.
If a component is disabled the indicator
No sound indication is supported for this condition.
10.2.2. Text messages
When a fire detecting line is
disabled it is indicated on the
display in the status of the line.
There is no text message for
disabled output.
All entered disables could be
viewed in Information and Control
mode.
Example: Disable for line 1 is
is
entered. The indicator
illuminated, in the line status there
is a text message “Dis”.
Instruction Manual
Revision 6/02.11
1 2 3
Page 29
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
10.3. Using the keypad
Button
Access
Operation
Additional information
level
all
Press it to enter Information
For detailed information how
and
Control
Mode.
All
entered
to
view
all entered disables in
Button
disables
could
be
viewed
in
Menu
Information
and Control Mode
(Menu)
see section 12.
View Disables.
11. Test Mode
11.1. Description
The fire extinguishing control panel enters Test Mode through manual operation setting a fire
alarm line to Test Mode. The condition is handled via Information and Control Menus.
Where a fire alarm line is set to Test Mode, the following changes take effect:
− Where Fire condition stage I or Fire condition stage II is detected in the line, sound and LEDs
indications are not triggered; i.e. the fire extinguishing control panel does not enter Fire
Condition;
- in Test Mode the line is reset, the power supply is interrupted every 64 seconds for a period of
3 seconds;
- from the possible faults along the line only the fault condition Short Circuit is processed.
11.2. Indication
11.2.1. LED and sound indication
This condition does not have specific LED and sound indication.
11.2.2. Text messages
Where a fire alarm line is set
to Test Mode, a text message
showing the status of the line
appears on the display.
All lines in Test Mode could
be viewed in Information and
Control Mode.
Example: Line 1 is set to Test
Mode. In the status of the line
there is a text message “Tes”.
1 2 3
11.3. Using the keypad
Button
Access
Operation
Additional information
level
all
Press it to enter Information
For detailed information how
and
Control
Mode.
All
lines
set
to
to
view
all lines set to Test Mode
Button
Test Mode could be viewed in Menu in Information and Control Mode
(Menu)
see section 12.
View Test.
Instruction Manual
Revision 6/02.11
Page 30
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
12. Information and Control Mode
12.1. Description
Information and Control Mode provides the user with the possibilities to display information
associated with the settings of the fire extinguishing control panel, and to enter control data.
The operation in this mode could be in combination with the following modes of the fire
extinguishing control panel:
- Duty Mode;
- Fire condition Stage I;
- Fire condition Stage II;
- Disabled component;
- Test;
- Fault condition
- Setup.
12.2. Indication
12.2.1. LED and sound indication
No specific LEDs or sound indication is provided for this Mode.
12.2.2. Text messages
The screens visualized on the display are organized in a tree structure, containing subordinate
menus (Appendix 2).
Information and Control Mode shows information in the first two lines of the display that are used
by Fire condition as a text field to indicate the first line in which the fire extinguishing control panel has
entered in fire condition.
Each screen has specific text message referring the operations that are performed in it. The
specific text messages are described for the respective screens. .
12.3. Using the keypad
Press the button
to enter Information and Control Mode from the screens of Duty Mode,
Fire condition, Fault condition, Test Mode and Disabled Component, thus their text messages are
suppressed. Where the fire extinguishing control panel operates in combination of Information and
Control Mode and Fault Condition, button
(Alarm) is active too. Where the fire extinguishing
control panel operates in combination of Information and Control Mode and Fire Condition, buttons
(Alarm) and
(Outputs) are active.
Transition to a lower hierarchy menu is performed by the means of button
upper hierarchy menu use button
; to revert to an
. To switch between elements of one menu use buttons
and
.
The screens containing specific information (information screens) or providing the possibility for
changing the parameters and executing the commands (command screens) are at the lowest level.
The button
is not active with the information screens as the other three buttons keep their
functions. A cursor appears when a screen for changing a parameter or a command screen is
activated. In this case the buttons has the following action:
− press the button
to save the changed parameter or to execute the selected command,
then the screen is deactivated and the cursor disappears (the different operation of the button
in some cases are specifically pointed);
− press the button
to deactivate the screen without saving the changed parameter or
without executing the respective command, and the cursor disappears;
− button
Instruction Manual
Revision 6/02.11
is active only in the screens for changing the parameter. Press it to:
Page 31
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
♦ move the cursor one position to the right. Upon reaching the last position of the parameter
the cursor returns to the first one;
♦ decrease the parameter to the next possible value. Upon reaching the minimal possible
value it turns to the maximum value of the class or the parameter;
− button
is active only in the screens for changing the parameter. Press it to increase by
one unit the class marked by the cursor or to increase the parameter to its next possible value.
In both cases upon reaching the maximum possible value it turns to the minimum value of the
class or the parameter.
12.4. Using the menus
When the Information and Control Mode is entered the first menu is displayed. It contains the
following subordinate menus:
− View Faults
− View Disables
− View Test
− Statuses
− System functions
12.4.1. Menu View Faults
The menu is accessible for all Access levels and contains information screens with suppressed
messages for fault condition.
From the current status of the fire
extinguishing control panel, press button
to enter the main menu. The cursor „>”
is positioned at the first point in the menu.
Press the button
once again to
visualize the screen for faults view.
1 2 3
If there are no faults a text message “No
Faults” appears on the display.
1 2 3
Instruction Manual
Revision 6/02.11
Page 32
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
If there are fault condition the display
shows information about the first fault. The
screen contains the following information:
- consecutive number of the fault;
- total number of the faults;
- type of the fault;
- status of the lines
To display the remaining faults (if more
and
than 1), use the buttons
To exit the menu – button
.
.
1 2 3
Example: Two fault conditions are registered: fault in the back up battery power supply and
and the specific indicator for
interruption of line 3. The common indicator for fault condition
power supply fault
are illuminated.
-
From the current status of the fire extinguishing control panel press twice button
display a screen with the first fault (fault in the back up battery power supply);
-
Press button
-
To exit the menu, use button
to
and the display shows the second fault (Fault interruption in line 3);
.
12.4.2. Menu View Disables
The menu is accessible for all Access levels and contains information screens with suppressed
messages for the entered disables.
From the current status of the fire
extinguishing control panel, press the button
to enter the main menu. The cursor „>”
is positioned at the first point of the menu.
Press once the button
and the cursor
moves to the second point in the menu.
1 2 3
Press the button
to visualize the
screen to view the entered disables.
If there are no disabled components the
following information screen is displayed.
1 2 3
Instruction Manual
Revision 6/02.11
Page 33
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
If there are disables all active disables
are displayed simultaneously on the screen.
To exit the menu – use the button
.
Example: All entered disables are visualized
on the screen: line1, line 2, line 3, the two
relays that are activated for fire condition
stage I and stage II and the sounder output
for fire condition stage I. As disables are
entered for the lines to the last line on the
display these disables are also shown in the
statuses of the lines.
1 2 3
12.4.3. Menu View Test
The menu is accessible for all Access levels and contains information screens showing the lines
in test.
From the current status of the fire
extinguishing control panel, press the button
to enter the main menu. The cursor „>”
is positioned at the first point of the menu.
Press button
until the cursor „>” moves
to point 03 of the menu.
1 2 3
Press the button
to display the
screen to view the lines in test.
If there are no lines in test a text
message “No Lines in Test” appears on the
display.
1 2 3
Instruction Manual
Revision 6/02.11
Page 34
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
If there is/are line/lines in test, their numbers
appear on the display. Information on the
changed status is provided on the fourth line
of the display.
To exit the menu use button
.
Example: The displayed screen provides
information that Line 1 and Line 2 are set to
Test Mode.
1 2 3
12.4.4. Menu Statuses
The menu contains information screen for the statuses of the fire alarm lines, the monitored
inputs and outputs. It is accessible for all Access levels.
From the current status of the fire
extinguishing control panel, press the button
to enter the main menu. The cursor „>”
is positioned at the first point of the menu.
Press button
until the cursor „>” moves
to point 04 of the menu.
1 2 3
Press the button
to display the
subordinate menu. It contains 11 elements,
which status could be seen:
- Line 1;
- Line 2;
- Line 3;
- ”Manual Release”;
- “Mode Select”;
- “Hold”;
- “On/Off”;
- “Low Press”;
- “Exting”;
- “Sound 1”
- “Sound 2”.
1 2 3
The cursor „>” is positioned at the first point of the subordinate menu.
The active buttons are:
and
for moving the cursor in the menu, button
enter the respective point from the menu and button
Instruction Manual
Revision 6/02.11
to
for exit.
Page 35
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Information screen containing the line
number and the current at that moment is
displayed for the status (current condition) of
the line. The current value in the line provides
information about its status.
1 2 3
The following statuses are possible for
the monitored inputs and outputs:
− Normal – for monitored input or output
in normal condition;
− Active - for monitored input or output
in active condition;
− Short - for monitored input or output in
short circuit;
− Interruption – for interrupted for
monitored input or output;
1 2 3
12.4.5. Menu System Functions
From the current status of the fire extinguishing control panel, press the button
main menu. The cursor „>” is positioned at the first point of the menu.
Press button
to enter the
until the cursor „>” moves to point 05 of the menu.
The menu contains the following
subordinate menus and functions (Appendix
2):
− Check LEDs and sound indicators;
− Clock Setup;
− Lines in Test
− Disables
− View Parameters;
− Setup;
− Fire counter;
− View Archive.
1 2 3
The subordinate menus are accessible at Access Level 2.
Press button
Instruction Manual
Revision 6/02.11
to enter the subordinate menu.
Page 36
of 63
UniPOS
12.4.5.1.
Fire Extinguishing Control Panel FS5200Е
Function Check LEDs and Sound
Indicators”
1 2 3
Press the button
. All LEDs
indicators are illuminated and the sounder
produces continuous signal.
Press button
to deactivate the
function.
Note: During the check the LEDs of the
system
error
indicator
and
the
are not
automatic mode indicator
illuminated.
1 2 3
12.4.5.2. Menu Clock Setup
The menu contains
functions:
− calendar date
− day of the week
− the time
− calibration index
the
following
1 2 3
Use the function Date to set or adjust
the current calendar date.
Upon activation of the function the
factory set date appears and the cursor
flashes on the first left digit of the date.
Admissible values are:
- for the date (two characters,
01÷31)
- for a month (two characters,
0÷12)
- for a year (four characters)
1 2 3
Use:
Instruction Manual
Revision 6/02.11
Page 37
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
•
button
– to change the calendar date;
•
button
– to move to the next character;
•
button
– to confirm the entered or set calendar date;
•
button
- to exit.
Use Function Day to adjust the
current day of the week. The field contains
the current day.
Upon activation a screen appears with the
entered current day of the week.
To change, save the data and to exit
the function, use:
• buttons
(Down) and
(Up) for
selecting the day (Monday, Tuesday, etc.);
• button
entered day;
(Menu) – to confirm the
• button
(Exit).
1 2 3
Use Function Time to set or adjust the
current time.
Upon activation of the function the
factory set time appears and the cursor
flashes on the first left digit of the hour.
Admissible values are:
- for hour (two characters, 00÷23);
- for minutes (two characters, 00÷59);
- for seconds (two characters, 00÷59).
1 2 3
Use:
•
button
(Down) – to change the value of the hour;
•
button
(Up) – to move to the next character;
•
button
(Menu) - to confirm the entered or adjusted date;
•
button
(Exit).
Instruction Manual
Revision 6/02.11
Page 38
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Use function Calibration to “accelerate/
delay” the clock. Each entered positive unit
(“+”) accelerates the clock at the rate of 10,7s
per month; each negative unit delays the
clock at the rate of 5,35s per month.
The maximum rate is е +5,5min per
month or -2,75min per month.
1 2 3
12.4.5.3. Fire Alarm Lines in Test
Use this menu to set each of the three
fire alarming lines in Test Mode or to exit that
mode.
Upon selection of Test FA Lines, a
subordinate menu is entered:
- Test Line 1
- Test Line 2
- Test Line 3
Use the buttons
and
to choose
the line to be set to test mode and confirm
1 2 3
with button
The displayed screen provides the
option for alternating change of the parameter
Test “ON/OFF”. If it is “ON”, then the
respective line is set to test Mode. Use the
buttons Up and Down for the change.
Confirm the change of the parameter with
.
button
A text message “Saved” appears for the
stored change.
The status of the line on the fourth line in
the display is changed to Tes.
1 2 3
For exit use button
12.4.5.4. Disables
The menu serves to disable/enable the
entered disable of fire alarm lines and some
outputs of the fire extinguishing control panel.
It contains the following functions:
− Disable Line 1
− Disable Line 2
− Disable Line 3
− Disable Rel 1ST
− Disable Rel 2ST
− Disable Output S1
Instruction Manual
Revision 6/02.11
1 2 3
Page 39
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
When the function to disable a fire alarm
line or an output from the fire extinguishing
control panel is selected from the subordinate
menu, a screen appears displaying the
current status of the disable in the specific
input/output. Use the buttons
and
for alternating change the parameter
Disable “ON/OFF”.
Confirm the change with button
,
thus it is stored and a text message “Saved”
appears on the display.
To exit use the button
1 2 3
.
illuminates in yellow light. It turns off when all entered disables are
The indicator
cancelled. If the disabled element is a fire alarm line, then the message on the fourth line of the
display is changed for the specific line. The text message Dis appears for the status.
12.4.5.5. Menu View parameters
The menu allows the current
parameters of the fire extinguishing control
panel to be viewed and contains the following
screens:
01 Lines parameters
02 Number of checks
03 Check removed FD
04 Input Hold
05 Input Low Press
06 Time Switch Extinguishing
07 Evacuation Time
08 Check Ground
09 RS485 Address
10 Software version
The active buttons in the menu and the
screens are
,
,
and
1 2 3
.
Screen Lines Parameters provides
information about the value of the current in
the lines (short circuit, interruption and fire
current).
1 2 3
Instruction Manual
Revision 6/02.11
Page 40
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Screen Number of Checks
In order the number of the false
activations to be reduced, the fire
extinguishing control panel provides the
option to setup a parameter indicating the
number of the activations of an automatic fire
detector within 60 seconds that would trigger
the fire extinguishing control panel for fire
condition. This screen provides information
about the parameter value.
1 2 3
Screen Check removed FD
The fire extinguishing control panel
recognizes the fault condition Removed Fire
Detector if the bases that are used are
diodes. Otherwise the function Removed Fire
Detector should be switched off.
1 2 3
Screen Input Hold
The screen provides information
about if the input ‘Hold’ is active or not and
the status of the contacts.
1 2 3
Screen Input LowPress
The screen provides information about
if the input ‘LowPress’ is active or not and
the status of the contacts.
1 2 3
Instruction Manual
Revision 6/02.11
Page 41
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Screen Time for Extinguishing
The screen provides information about
the setup time while the extinguishing devices
are switched. The time is in seconds.
1 2 3
Screen Evacuation Time
The screen provides information about
the setup time for evacuation. The time is in
seconds.
1 2 3
Screen Check Ground
The screen provides information if the
check for ground is switched.
1 2 3
Screen RS485 Address
The screen displays the setup network
address.
Instruction Manual
Revision 6/02.11
Page 42
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Screen Software Version
The screen provides information about
the software version.
1 2 3
12.4.5.6. Menu Setup
The configuration parameters of the fire extinguishing control panel are set in the menu Setup. It
is described in details in Setup Mode (section13).
12.4.5.7. Screen Fire Counter
The screen Fire Counter is part of the
menu System Functions.
The active buttons to enter and exit it
are
,
,
and
.
1 2 3
The screen provides information about
the entries of the number of times when the
fire extinguishing control panel has entered
Fire condition.
1 2 3
Instruction Manual
Revision 6/02.11
Page 43
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
12.4.5.8. Screen Archive
The screen Archive Counter is part of
the menu System Functions.
The active buttons to enter it, to move to
another entry in the archive and to exit the
screen are:
,
,
and
.
The information recorded in the archive
has the following structure:
- No. of the record;
- Total number of the records;
- Text of the event in the
archive (fire condition, initial
reset, activated input, etc.);
- Time of the record;
- Date of the record.
1 2 3
13. Setup Mode
13.1. Description
Set Up mode is used for setting the configuration parameters of the fire extinguishing control
panel. Access to the Set Up screen is provided through menu System Functions in Information and
Control Mode.
When the fire extinguishing control panel enters Set Up mode, it exits all other conditions and
saves the configuration in its energy independent memory.
Important: In Setup Mode the fire extinguishing control panel discontinues the service of its fire
alarm lines, inputs and outputs.
13.2. Indication
13.2.1. LED and sound indication
In Set Up mode only the green LED indicator
sounder is off.
(Power supply) is illuminated. The local
13.2.2. Text message
The text message shown on the display is specific for each menu, function or screen. The
screens with the respective text message for each of the setup parameter are given in the part
describing the operation in menu Setup.
13.3. Using the keypad
Setup Mode requires Access Level 3. It is necessary:
- The switch to be in position
- To enter a password.
;
The text messages in this mode are organized in a tree structure, of main and subordinate
menus.
Press the button
to enter Setup Mode from the screens of Duty Mode, Fire condition, Fault
condition, Test Mode and Disabled Component, thus their text messages are suppressed. Where the
fire extinguishing control panel operates in combination of Setup Mode and Fault Condition, button
(Alarm) is active too. Where the fire extinguishing control panel operates in combination of
Setup Mode and Fire Condition, buttons
Instruction Manual
Revision 6/02.11
(Alarm) and
(Outputs) are active.
Page 44
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Transition to a lower hierarchy menu is performed by the means of button
upper hierarchy menu use button
; to revert to an
. To switch between elements of one menu use buttons
and
.
The screens containing specific information (information screens) or providing the possibility for
changing the parameters and executing the commands (command screens) are at the lowest level.
The button
is not active with the information screens as the other three buttons keep their
functions. A cursor appears when a screen for changing a parameter or a command screen is
activated. In this case the buttons has the following action:
− press the button
to save the changed parameter or to execute the selected command,
then the screen is deactivated and the cursor disappears (the different operation of the button
in some cases are specifically pointed);
− press the button
to deactivate the screen without saving the changed parameter or
without executing the respective command, and the cursor disappears;
− button
is active only in the screens for changing the parameter. Press it to:
♦ move the cursor one position to the right. Upon reaching the last position of the parameter
the cursor returns to the first one;
♦ decrease the parameter to the next possible value. Upon reaching the minimal possible
value it turns to the maximum value of the class or the parameter;
− button
is active only in the screens for changing the parameter. Press it to increase by
one unit the class marked by the cursor or to increase the parameter to its next possible value.
In both cases upon reaching the maximum possible value it turns to the minimum value of the
class or the parameter.
Instruction Manual
Revision 6/02.11
Page 45
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4. Using the menus
Enter Setup Mode through menu System
Function.
1 2 3
Enter a password (four-digit number) to have
an access to the menu. The factory set
password is “0000”.
Use:
•
button
character;
•
button
(Up) – to move to the
next character;
•
button
(Menu) – to confirm the
entered password;
•
button
(Down) – to change the
1 2 3
(Exit).
The menu has the following subordinate menus
01 Fire Extinguishing
RS485 address (section13.4.1.1)
Control Panel:
RS485 On/Off (section 13.4.1.2)
Language (section 13.4.1.3.)
Check Ground (section13.4.1.4.)
02 CAN Settings
CAN On/Off (section 13.4.2.1.)
Text message (section 13.4.2.2.)
CAN speed (section 13.4.2.3.)
CAN Address (section 13.4.2.4.)
CAN AddressRem.Panel (section 13.4.2.5.)
CAN Rem.Inputs (section 13.4.2.6.)
Number FD FuncAnd (section 13.4.2.7)
03 Input/Outputs
Current fire alarm lines (section 13.4.3.1.)
Number of checks of lines (section 13.4.3.2.)
Check removed fire detector (section 13.4.3.3.)
Input Hold (section 13.4.3.4.)
Input Low Press (section 13.4.3.5.)
04 Extinguishing time
05 Evacuation time
06 Factory settings
07 Clear Archive
08 New password
13.4.1. Menu Fire Extinguishing Control Panel
The menu includes the functions for setting the parameters: network address, language and if
the function heck ground is active or not.
Instruction Manual
Revision 6/02.11
Page 46
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.1.1. The value of the parameter
Network Address defines uniquely the fire
extinguishing control panel within the
established network of remote control panels
and repeaters.
A screen for entry of the data
appears in setting (entry) of a network
address.
The permissible values of the network
address are from 0000 to 9999.
The value of the default parameter is
„1234”.
1 2 3
Use:
•
button
(Down) – to change the character;
•
button
(Up) – to move to the next character;
•
button
(Menu) – for confirmation;
•
button
(Exit).
When the parameter is changed and the new value is saved with the button
message “Saved!” appears!
Exit – [x]”.
13.4.1.2. To set ON or OFF RS485 Network
Parameter permits values ON of OFF
Active buttons :
•
to change - buttons
a text
and
;
•
to save the change - button
(„Menu”);
•
to exit press - button
(„Exit”).
13.4.1.3. The fire extinguishing control panel
supports menus and screens in two of three
languages:
- Bulgarian;
- English;
- Russian.
Use the buttons
(Down) and
(Up) for alternating change of the
language, confirm the new value of the
parameter using the button
button
and the
1 2 3
to exit it.
When the parameter is changed and the new value is saved with the button
a text
message “Saved!” appears!
Exit – [x]”. The fire extinguishing control panel is factory set to English
language.
Instruction Manual
Revision 6/02.11
Page 47
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.1.4. Function Check Ground
The screen provides the possibility to
indicate if check ground is being performed or
not. Check ground is disabled only if Zener
barriers or other devices that might cause
ground fault are used however that disable
does not have an effect on the functions of
the of the fire extinguishing control panel.
The factory setting of this parameter is Check
Ground ON.
The admissible values are – Check
Ground ON or OFF.
Use the buttons
button
(Down) and
1 2 3
(Up) to change alternatively the parameter, the
to confirm the new value and the button
to exit.
13.4.2. Menu “CAN Parameters”
Fire extinguishing Control Panel communicates in a network on CAN interface with the devices from
IFS7000 as transmitting and receiving information. It is necessary for the programable sofwear of the
panel to be 13.10 version or higher.
Functionallity:
• Connected in network, FS5200E operates with up to 8 Control panels (Remote control
panels) of series 7000.
• It is necessary for the local network to operate with at least 1 panel from series 7000;
• Only the panel from 7000 series is definedas the main panel;
• Information of Fire condition or Fault condition of FS5200E is accepted and indicated only
from panels 7000 series;
• Maximum number of devices on CAN network - up to 32 ( i.e maximum laden network can
be built of 8 panels series 7000 and 24 FS5200E panels.
Communication
Communication “FS5200E Æ IFS7000”
• In Fire condition of FS5200E, 3 types of conditions are transmitted and indicated
of all the panels series 7000:
FIRE Condition Stage 1;
FIRE Condition Stage 2 evacuacion;
FIRE Condition Stage 2 exting.ON
• In Fault condition of FS5200E the following conditions are indicated and
transfered into the panels series 7000:
Fault in Fire detector of Line 1;
Fault in Fire detector of Line 2;
Fault in Fire detector of Line 3;
Fault in Manual Release Mode;
Fault in Line Mode;
Fault in Line Disable Extinguishing;
Fault in Line Low Pressure;
Fault in Line Hold Extinguishing;
Fault in Exit Extinguishing;
Fault Exit Fire Stage 1;
Fault Exit Fire Stage 2;
Fault in Back up battery supply;
Fault in Mains supply
Communication ''5200E Å IFS7000”
Instruction Manual
Revision 6/02.11
Page 48
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
• Fire Extinguishing Control Panel 5200Е receives and uniquely distinguishes data
from activated inputs of up to 5 manual call points (FD7150), up to 8 automatic fire
detectors (FD71xx) and inputs of devices FD7203 within the systems series 7000.
Inputs can be configured to all of the Control Panels of type 7000 included into the
network.
• Fire Extinguishing Control panel 5200E receives and single-distinguishes data
from activated inputs of device FD7203. Inputs could be configured to all Control
Panels of series 7000, connected in the network.
• 4 inputs can be configured in the 5200E Control Panel, these inputs affect the
functions of the extinguishing algorithm.
Inputs are for the following functions :
- Manual Extingushing Activation (by means of a manual call point) or
automatic (by means of an automatic fire detector);
- Disable Extinguishing;
Switches to Manual / Manual Automatic Mode;
- Hold Extinguishing.
• In 5200E Fire condition can be reset from the display of panels series 7000. The
reset Panel transmitts information to all the panels of (7000 series) for resetting of Fire
Condition.
• Sound indicator can be suppressed from the IFS7002 display in case of Fire or
Fault Condition in the Extinguishing panel.
• In case of disconnected communication, the Control Panel FS5200Е registers
fault condition „Fault CAN” („Fault RS485”).
In the menu “CAN Parameters” set the
parameters for operating on CAN network,
together with 7000 serie (the programable
softwear of the panel should be 13.10 version
or higher).
Menu contains the following positions:
01. CAN On/Off
02. Text message
03. CAN speed
04. CAN Address
05. CAN AddressRem.Panel
06. CAN Rem.Inputs
07. Numb FD FuncAnd
1 2 3
13.4.2.1. To set ON or OFF CAN Network
Parameter permits values ON of OFF
Active buttons :
•
to change - buttons
and
;
•
to save the change - button
(„Menu”);
•
to exit press - button
Instruction Manual
Revision 6/02.11
(„Exit”).
1 2 3
Page 49
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.2. To enter text message.
The screen allows the user to enter a text
message for identifying the Control Panel
(name) within 20 characters - Cyrillic and
Latin. If an event occurs (Fault condition or
Fire Condition), the text is shown on the
display of the panels series 7000.
Active buttons:
•
to change the character –
•
to position the next character
•
to save the text - button
•
to exit - button
;
1 2 3
;
(„Exit”).
13.4.2.3. Set Up speed on CAN network
communication.
Enter in the screen the exchange rate of the
network.
Important : The speed entered for Panel
FS5200E must correspond to the speed,
entered for IFS7000 panels.
Parameter permits the following values: 40,
80, 100 или 160 kb/s.
Active buttons:
•
to change – buttons
•
to save the change - button
(„Menu”);
and
1 2 3
;
(„Exit”).
• to exit - button
Recommendation :
If the length of the wire network is longer than 500 meters, recommended speed is 40 kb / s.
13.4.2.4. Setting network address of
FS5200E panel.
Set the address of the Panel on the screen.
Address must be unique.
Admissible values: 01÷31.
Active buttons:
•
to change - buttons
•
to save the change - button
(„Мenu”);
•
to exit - button
and
(„Exit”).
;
1 2 3
Notice:
CAN address value has no connection with ''Master/Slave“ Setting.
Instruction Manual
Revision 6/02.11
Page 50
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.5. Inserting addresses of the Remote
Control Panels.
This option of the Menu permits entering the
addresses in the Remote Panels for
communication with FS5200E.
Мenu includes :
• 01 CAN Master Remote Panel 01;
• 02 CAN Remote Panel 02;
• 03 CAN Remote Panel 03;
• 04 CAN Remote Panel 04;
• 05 CAN Remote Panel 05;
• 06 CAN Remote Panel 06;
• 07 CAN Remote Panel 07;
• 08 CAN Remote Ranel 08;
1 2 3
In article 1 of the subordinate menu enter the
address of the ''Master“ panel. The panel is
required to be from series 7000.
Active buttons:
•
to change – buttons
to save the change - button
•
to exit - button
and
;
(„Мenu”);
(„Exit”).
1 2 3
In articles 02÷08 from the Menu, insert by
analogical order the addresses of the other
control panels series 7000, comminicating
with the Extinguishing Panel.
The addresses of the Remote panels are to
be entered in ascending order. (RP1, RP2,
RP8 ...).
Important: If the number of the control panels
series 7000 is less than 8, then in the spaces
for addressing panels, which are not in use
save Address "00" (entered by default)
Instruction Manual
Revision 6/02.11
1 2 3
Page 51
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.6. If devices of type FD7203, manual
or automatic detectors are also used as an
input of the fire Extinguishing Panel, their
paremetres must be set in FS5200E.
Four inputs of the Control Panel are possible
to be set :
• 01 Input Manual Activation;
• 02 Input Autom.Activation
• 03 Input Manual/automatic Mode;
• 04 Input Disable Extinguishing;
• 05 Input Hold Extinguishing.
13.4.2.6.1. Input Manual Activation includes
the opportunity for activation from manual call
point type FD7150, of system series 7000,
operating in a common network together with
Fire Extinguishing Control Panel. Insert data
for the address of the Control Panel, the
address of the loop and the address of the
manual call point. The admissible number of
manual call points that can be included is 5.
13.4.2.6.2. Input Automatic Activation
includes the opportunity for activation from
automatic fire detectors type FD71ХХ, of
system series 7000, operating in a common
network together with the Fire Extinguishing
Control Panel. Insert data for the address of
the Control Panel, the address of the loop
and the address of the manual call point in
the loop. The admissible number of automatic
fire detectors that can be included is 8. In
factory setting at least two of them are
connected in logical dependency ’’AND’’
(item.13.4.2.7).
13.4.2.6.3. Inputs „Mode Manual/Automatic”, „Disable Extinguishing” and „Hold Extinguishing” are to
be set by the same procedure.
Setting targets uniquely distinguishing which input, of what type FD7203 device, from which loop, and
of which Control Panel the command impact will come the the Extinguishing Panel and it includes the
following items:
o
o
o
o
o
01 On/Off.Rem.Input;
02 Number Remote Panel;
03 Number Loop;
04 Number Device 7203;
05 Number Input 7203.
Instruction Manual
Revision 6/02.11
Page 52
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.6.3.1. ON/OFF Remote input.
Admissible values of the parameter are : ''On''
and ''Off''
Аctive buttons :
•
to change – buttons
•
to save the change – button
(„Мenu”);
•
to exit - button
and
;
1 2 3
(„Exit”).
13.4.2.6.3.2. Address of the Remote Panel,
where the device FD7203 is situated.
Admissible values of the parameter are :
01÷31(i.e the addresses of Control Panels in
the network.
Аctive buttons :
•
to change – buttons
and
;
•
to save the change – button
(„Меnu”);
•
to exit - button
1 2 3
(„Exit”).
13.4.2.6.3.3. Number of a loop where the
FD7203 device is situated.
Admissible values of the parametre are 01
and 02.
Аctive buttons :
•
to change – buttons
•
to save the change – button
(„Мenu”);
•
to exit - button
Instruction Manual
Revision 6/02.11
and
(„Exit”).
;
1 2 3
Page 53
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.6.3.4. Number of the addressable
device FD7203.
Admissible values of the parametres are:
01÷125 (address of the device in the relevant
loop).
Аctive buttons :
•
to change – buttons
and
;
•
to save the change – button
(„Мenu”);
•
to exit - button
1 2 3
(„Exit”).
13.4.2.6.3.5. Number of the input of the
addressable device FD7203.
Admissible values of the parameter are 01,
02 and 03 (IN1, IN2 and IN3 of FD7203).
Аctive buttons :
•
to change – buttons
•
to save the change – button
(„Мenu”);
•
to exit - button
and
(„Exit”).
;
1 2 3
The procedure for inserting parametres for inputs ''Manual/AutomaticMode'',''Disable
Extinguishing'' and ''Hold Extinguishing“ is performed analogically according to the described in
articles 13.4.2.6.3.1.÷13.4.2.6.3.5. and operations.
Instruction Manual
Revision 6/02.11
Page 54
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.2.7. Insert the number of the automatic
fire detectors of type FD71XX, connected in
logical dependency „AND”.The inserted
number indicates how many fire detectors
should be be activated in order the control
panel to enter Fire Condition 2nd Stage .
13.4.3. Menu Input/Outputs
This menu includes the setting of the following parameters:
- current of fire alarm lines
- number of checks for accepting the signal for fire condition from a fire detector
- checking the lines for removed fire detector
- setting the input Hold
- setting the input Low Press
13.4.3.1. Function Current of Fire Alarm Line
The screen provides the option to set
the current value of the fire alarm lines when
interruption and fire condition is registered.
The interruption threshold could be set within
the range 3 to 12 mA, and for fire condition –
from 12 to 60 mA. The difference between
the two conditions provides the screen for
Duty Mode.
The factory setting is 3 and 12 mA for
interruption and fire condition respectively.
The active buttons are:
1 2 3
•
button
– to change the character (e.g.: 03, 04 ......);
•
button
(Up) – to pass from setting the current of interruption to setting the current of fire;
•
button
(Menu) – to confirm the changes;
•
button
(Exit) – to exit the function.
Instruction Manual
Revision 6/02.11
Page 55
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.3.2. Screen Number of Checks of Lines
Use this screen to set the number of
checks upon which the fire extinguishing
control panel registers a fire condition along a
fire alarm line. The possible values of this
parameter are 1, 2 and 3 checks.
The factory setting is 2 checks.
Use the buttons
and
to change alternatively the parameter, the
button
to confirm the new value and the
button
to exit.
1 2 3
13.4.3.3. Screen Check for Removed Fire
Detector
The value of this parameter determines if the
fire extinguishing control panel shall monitor
the fault condition – removed fire detector. If
this function will be used then diode should be
installed in the bases of the fire detectors as it
is shown in the diagram for connecting the fire
detectors. The factory setting is Check ON.
Use the buttons
(Down) and
(Up)
to change alternatively the parameter, the
button
to confirm the new value and the
button
to exit.
1 2 3
13.4.3.4. Setup Input Hold
Due to the specificity of the input Hold,
the active status for this function is OPEN
contact. it is provided the logic of the contact
to be turned in the case of not standard
installations as the active level could be with
Closed contact.
According to the standard this input
should function with active level OPEN
contact, otherwise the other option is an
exception.
The factory setting is active level with
OPEN contact.
Use the buttons
button
(Down) and
1 2 3
(Up) to change alternatively the parameter, the
to confirm the new value and the button
Instruction Manual
Revision 6/02.11
to exit.
Page 56
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.3.5. Setup Input Low Press
Due to the specificity of the input to
monitor the leaking of the extinguisher, the
active status for this function is OPEN
contact. it is provided the logic of the contact
to be turned in the case of not standard
installations as the active level could be with
Closed contact.
According to the standard this input
should function with active level OPEN
contact, otherwise the other option is an
exception.
The factory setting is active level with
OPEN contact.
Use the buttons
button
(Down) and
1 2 3
(Up) to change alternatively the parameter, the
to confirm the new value and the button
to exit.
13.4.4. Function Time Extinguishing
Use this function to set the time for
extinguishing. The specific value of the
parameter depends on the utilized automatic
devices. The factory setting is 10 seconds as
the admissible values are within the range
from 1 to 255 seconds.
The active buttons are
and
to
reduce/increase
the
time
for
extinguishing. To confirm the new value use
the button
, to exit – press button
1 2 3
.
13.4.5. Function Time Evacuation
Use this function to set the time for
evacuation The factory setting is 120 seconds
as the admissible values are within the range
from 1 to 255 seconds.
The active buttons are
and
- to
reduce/increase the time for evacuation. To
confirm the new value use the button
to exit – press button
Instruction Manual
Revision 6/02.11
.
,
1 2 3
Page 57
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
13.4.6. The function Factory Settings returns
the parameters of the fire extinguishing
control panel repeater to their default settings.
The specific values of the parameters are
given in the previous sections of the
instruction manual.
1 2 3
13.4.7. Function Clear Archive
This function allows the archive to be
cleared from the energy independent
memory.
Press the button
to activate the
function and to clear the archive.
Important: The fire counter is not cleared.
It is reset in a special mode (Access Level 4).
1 2 3
13.4.8. Function new Password
This function serves to change the
existing password for Access Level 3. The
admissible values are from 0000 to 9999.
The factory setting is „0000”.
1 2 3
14. Extinguishing Control Algorithm
The algorithm to control the outputs and the indication depending on the input influences and
the set parameters for the fire extinguishing control panel operation is shown on Drawing 12.
.
Instruction Manual
Revision 6/02.11
Page 58
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Algorithm for the procedures during decision for extinguishing in Fire Extinguishing Panel FS 5200E
Duty mode
Automatic control of the
extinguishing
No
Manual control of the
extinguishing
Fire in 1 or 2
fire alarm lines
Is it switched on
extinguishing manual
call point?
Yes
Fire Phase 1
Relay Fire Phase 1 - On
Sounder Fire Phase 1 - On
LED Fire phase 1 - On
Sound buzzer - 1Hz/4Hz
LCD – indication for line in Fire
No
Yes
Yes
Fault in the manual
call point line?
No
Sound buzzer
switched off
Yes
Is it pressed button for
sound suppression?
No
Relay Fire Phase 1 - Off
Sounder Fire Phase 1 - Off
Yes
EXTIGUISHING
Fire Phase 2
Relay Fire Phase 2 - On
Sounder Fire Phase 2 - 2 Hz
LED Fire Phase 2 - 1 Hz
Sound indicator - On
LCD – indication for Fire Phase 2
Is it pressed button for
outputs suppression
?
No
Relay Fire Phase 1 - Off
Sounder Fire Phase 1 – Off
LED Fire Phase 1 - Off
Sound buzzer - Off
LCD – Duty mode
No
Yes
Button
Reset Fire?
Is there fault in
disable extinguishing
line?
No
Fire
in another (1 or 2)
Fire alarm line
Yes
Button
Reset Fire?
Yes
No
No
Is there disable
extinguishing ?
Yes
Relay Fire Phase 1 – Off
Sounder Fire Phase 1 - Off
LED Fire Phase 1 - Off
Yes
No
Automatic
Time EVACUATION = Time
LCD- Time evacuation
Sounder Fire Phase 2 - On
MODE SWITCH
Button delay
extinguishing ?
Manual
Yes
No
Fire Phase 2
Relay Fire Phase 2 - On
LED Fire phase 2 - 1 Hz
Sound indicator - On
LCD indication for Fire Phase 2
No
Is it elapsed the
evacuation time ?
Yes
Sound indicator
switched off
Yes
Sound indicator – On
LCD- Attention Gas
Is it pressed button for
sound suppression?
SWITCH ON EXTINGUISHING
OUTPUT
LED Fire Phase 2 – light continuously
Extinguishing impulse = TimeЕхт
No
Relay Fire Phase 2 - Off
Sounder Fire Phase 2- Off
Yes
Is it pressed button for
outputs suppression
?
No
No
Relay Fire Phase 2 - Off
Sounder Fire Phase 2 - Off
LED Fire Phase 2 – Off
Sound buzzer - Off
LCD – Duty mode
Is it elapsed the time of
extinguishing impulse ?
Yes
Yes
Button
Reset Fire?
No
Indicator low pressure - On
Switch off the
extinguishing output
No
Is there pressure in
the system?
Yes
Button
Reset Fire?
No
Yes
18.01.2008 / М.Киров
Drawing 12
Instruction Manual
Revision 6/02.11
Page 59
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
15. Labour protection requirements
The installation and maintenance staff shall be well grounded in equipment’s mechanism and
operation, as well as in common technical safety regulations.
Connection to unearthed or to indirectly earthing mains supply is prohibited.
Troubleshoots are to be cleared after disconnecting the feeding cable from the mains supply.
The fire extinguishing control panel is designed for installing in premises with a normal fire
hazard, as per the Fire Precaution Technical Regulations in Building Construction.
16. Fire extinguishing control panel start up
Make sure that the connection to mains power supply is properly made.
Make sure that the periphery devices are correctly connected.
Place the fuse in the terminal with mains fuse, the display illuminates and appears text message
with the name of the producer, the initials of the control panel and the software version. Then the
display shall show the current time and date.
Connect the feeding cable and the backup batteries; the batteries shall be in a series connection.
Connect the red wire to the positive backup battery pole, and the blue wire – to the negative pole.
The overall voltage of both batteries shall not exceed 17.6V, otherwise the fire extinguishing control
panel will not recognize them.
Enter Set Up Mode and configure the common parameters and the lines parameters.
Upon exit of Set Up Mode the fire extinguishing control panel runs all system operations and
enters Duty Mode – the control panel is ready to fire protect the site.
17. Operation, storage and transportation
17.1 Operation and storage
The fire extinguishing control panel shall operate and be kept in closed premises, under the
following conditions:
17.1.1. Temperature
− storage
− transportation
− operational
- from
5°С to 35°C
- from minus10°С to 50°C
- from minus 5°С to 40°С
17.1.2. Relative humidity
− storage
− operational
- to 80%
- to 93%
17.2. Transportation
The fire extinguishing control panel shall be transported by vehicles, in factory packing, in the
above stated environmental conditions and at sinusoidal vibrations with acceleration amplitude not
more than 4,9m/s2 in frequency range 10 to 150Hz.
18. Warranty
The producer guarantees compliance of the device with EN 54-2:1997/ А1:2006/AC: 2009,
EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003.
The warrant period is 18 months from the
date of the purchase, providing that
− the conditions of storage and transportation have been observed;
− the startup has been done by authorized personnel only
− the requirements for operation stated herein have been observed.
UniPOS
47, “San Stefano” Str., 5800 Pleven, BULGARIA
phone +359 64 891111, +359 64 891 100, fax +359 64 891 110
e-mail: office_pleven@unipos-bg.com
Mladost 1, bl.79B, entr.2, ap.17, 1784 Sofia, BULGARIA
phone/fax +359 2 9744469, +359 2 9743925
e-mail: office_sofia@unipos-bg.com
www.unipos-bg.com
Instruction Manual
Revision 6/02.11
Page 60
of 63
UniPOS
Fire Extinguishing Control Panel FS5200Е
Аppendixes
Appendix 1
1 2
3
4
5
6
7
8
9
10
1 2 3
11
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
12
13 14
15
16 17 18 19 20 21 22 23 24
Front panel of fire extinguishing control panel FS5200E
Indicator Hold extinguishing
Indicator Fault in a circuit of signal wires
Indicator System Error
Indicator Fault in power supply
Common Indicator Fault Condition
Indicator Manual Mode
Indicator Power Supply
Indicator Disabled Component
Indicator Low Pressure
LCD display (4х20)
Indicator Automatic Mode
Indicator Fire condition stage II – Extinguishing
Switch – Automatic / Manual / Disable
Indicator Fire condition stage I
Individual indicators of the Fire detecting lines
Indicator Disable extinguishing
Button Reset
Button Menu
Button Down
Button Alarm with indicator Stop alarm
Button Up
Button Outputs with indicator Suppressed outputs
Switch – Access level
Button Cancel
Instruction Manual
Revision 6/02.11
Page 61
of 63
Duty mode
Instruction Manual
Revision 6/02.11
05 System functions
04 Status
03 View Test
02 View Disables
01 View faults
automatic
08 Archive
07 Fire counter
06 Set Up
05 View parameters
04 Disables
03 Test fire lines
02 Clock
01 Check indication
11 Status Output “Sound2”
10 Status Output “Sound1”
09 Status Output “Exting”
08 Status Input “LowPress”
07 Status Input “On/Off”
06 Status Input “Hold”
05 Status Input ”ModSelect”
04 Status Input ”ManRelea”
03 Status Line 3
02 Status Line 2
01 Status Line 1
Fire/Extinguishing
Password-access level 3
10 Software version
09 Network address
08 Check ground
07 Evacuation time
06 Time Extinguishing On
05 Input ”LowPress”
04 Input ”Hold”
03 Checks rem.detector
02 Checks number
01 Line parameters
06 Disable output S1
05 Disable Rel 2ST
04 Disable Rel 1ST
03 Disable Line 3
02 Disable Line 2
01 Disable Line 1
03 Test Line 3
02 Test Line 2
01 Test Line 1
04 Correction
03 Time
02 Day
01 Date
General menu of panel FS5200E
08 New password
07 Clear Archive
06 Default parameters
05 Evacuation time
04 Extinguish time
03 Input/Outputs
02 CAN parameters
01 Control panel
05 Input “LowPress”
04 Input “Hold”
03 Check removed detector
02 Number line checks
01 Current fire alarm lines
Menu CAN
Setting
04 Check “Ground”
03 Language
02 RS485 On/Off
01 RS485 Network address
UniPOS
Fire Extinguishing Control Panel FS5200Е
Appendix 2
Page 62
of 63
Instruction Manual
Revision 6/02.11
02 CAN Setings
07 Numb FD FuncAnd
06 CAN Rem.Inputs
05 CAN Addr.RemPanel
04 CAN Address
03 CAN Speed
02 Text message
01 CAN On/Off
08 CAN RemPanel08
07 CAN RemPanel07
06 CAN RemPanel06
05 CAN RemPanel05
04 CAN RemPanel04
03 CAN RemPanel03
02 CAN RemPanel02
01 CAN MasterPan01
05 Inp.Hold Ext.
04 Inp.DisableExt.
03 Inp.Mode Man/Aut
02 Inp.AutActivation
01 Inp.ManActivation
05 Num. Input 7203
04 Num.Device 7203
03 Loop Number
02 Number Rem.Panel
01 On/Off Rem.Input
05 Num. Input 7203
04 Num.Device 7203
03 Loop Number
02 Number Rem.Panel
01 On/Off Rem.Input
05 Num. Input 7203
04 Num.Device 7203
03 Loop Number
02 Number Rem.Panel
01 On/Off Rem.Input
08 Automat.FD71xx8
07 Automat.FD71xx7
06 Automat.FD71xx6
05 Automat.FD71xx5
04 Automat.FD71xx4
03 Automat.FD71xx3
02 Automat.FD71xx2
01 Automat.FD71xx1
05 Manual FD7150
04 Manual FD7150
03 Manual FD7150
02 Manual FD7150
01 Manual FD7150
UniPOS
Fire Extinguishing Control Panel FS5200Е
Appendix 3
Page 63
of 63