Leading in Fire Detection Control Systems

Leading in Fire Detection Control Systems
Leading in
Fire Detection
Control Systems
2009 - 2010
e
Leading in Fire Detection Control Systems
Pages 6-41
Analogue Addressable
Pages 44-57
Conventional
Pages 60-69
Pages 72-81
Kentec offers first rate technical support facilities and
a dedicated team of highly trained personnel provide
direct telephone assistance; this is backed up by
regular technical e-mail bulletins, on-site and off-site
customer specific training.
Our management systems are ISO 9001:2008
approved and our policy for environmental
awareness was officially recognized in 2007 when we
gained our ISO 14001 certification from BSI. In 2004
Kentec achieved ‘Investors in people’ accreditation.
In 2008 Kentec was proud to be awarded the Royal
Warrant of Appointment by Her Majesty the Queen.
Pages 84-89
Kentec believes that the quality of our products
should be paramount; rigorous testing procedures
are employed at every stage of the manufacturing
process to ensure that all equipment is supplied
to the highest standards. For this reason we are
confident in offering an industry leading 3 years
warranty on all product that we supply.
Many of Kentec’s products are tested and approved
to international standards such as EN54, EN12094, UL
and FM.
Extinguishant
Kentec offers the most comprehensive range of
conventional, analogue addressable fire detection
and extinguishant control panels available. Our
custom build service is also highly regarded in the
industry and utilises our expertise in control panel
technology to design and build high quality product
to exacting customer specifications. More recently
we have further increased our range and launched
our Marine approved range of Analogue Addressable
control panels.
Miscellaneous
In keeping with our philosophy of in-house
production we have invested heavily in state of
the art manufacturing equipment for all areas of
the business, this has allowed us to react quickly to
customer requirements and market trends whilst
maintaining our position at the forefront of Control
panel design & manufacture.
Custom
Established over 24 years ago, Kentec Electronics
Ltd. has evolved into one of the world’s leading
independent fire control panel manufacturers. Over
the years the Kentec name has become synonymous
with World class product, great service and excellent
support. Based in the UK, Kentec is a truly global
supplier, exporting control equipment to over
70 countries Worldwide, and in many different
languages.
Analogue
Fire Detection
Control Equipment
Pages 6-41
Syncro AS Single or Two Loop Analogue
Addressable Fire Control Panels
Page 6-7
Syncro Guide
PC Graphics Software
Page 26-27
Syncro Multi Loop Analogue
Addressable Fire C/P’s
Page 8-11
Syncro Guide Repeater
Providing Repeater Facility for any
GUIDE System
Page 28-29
Syncro Response Analogue Addressable Fire Control
Panel Repeaters
Page 12-13
MIOU/LIOU
Multi Input/ Output Unit
(Standard and Light versions)
Page 30-31
Syncro Focus
Network LCD Repeater for
Syncro System
Page 14-15
Syncro I/O
A range of I/O boards and
enclosures
Page 32-41
Syncro View Serial LCD Repeater for
Syncro System
Page 16-17
Syncro Ident
Programmable LED
Indication Panels
Page 18-19
Syncro Matrix
Intelligent Fire Alarm Mimic
Display System
Page 20-21
Syncro Net
Syncro Network Interface
Page 22-23
Syncro Comms
Syncro Communications Module
Page 24-25
Syncro
AS
BS-EN54-2
BS-EN54-4
KM 73505
Single or Two Loop Analogue
Addressable Control Panel
Product Overview
Syncro AS is a versatile range of open protocol fire alarm
control panels compatible with existing Syncro fire alarm panel
technology.
Available with one or two detection loops capable of hosting
up to 126 devices (Apollo), 240 devices (Argus Vega) or 127
devices (Hochiki). Syncro AS uses leading edge microprocessor
based electronics to provide a flexible control system with high
reliability and integrity.
Features
16 zonal LED indicators
2 programmable sounder circuits
5 programmable inputs
Suitable for all small to medium sized fire detection systems,
Syncro AS control panels can be expanded and networked to
become part of much larger systems if the need arises,
therefore providing a future proof solution for any installation.
With its large graphical display and ergonomic button and
indicator layout, the Syncro AS control panel is simple and
straightforward to understand for installers, commissioning
engineers and end users alike.
3 programmable relays
(Also backward-compatible
with Series 90 detectors)
3A power supply
Large graphic display
Real time clock
Up to 512 additional programmable I/O
via Syncro I/O modules *
R
Config. Features
Comprehensive day/night mode facility
Programmable one touch test mode
Powerful and versatile cause & effect programming
Powerful, network wide cause and
effects *
Cause & effect wizard including:
Sensitivity adjustment and Drift
Compensation
Cause & effect action
Disablement configuration
Test mode configuration
Can be networked with Syncro control
panels *
Compatible with Focus and View
repeaters *
Supports Apollo, Argus Vega and Hochiki
protocols
Same look and feel as Syncro range
Stores 500 last events in event log
Dial up modem connection available
Compact, stylish enclosure
Installer friendly, removable equipment
chassis
Different language and character set
variants available
Fully EN54-2 and EN54-4 compliant
Printer option * **
* These items not available on Syncro AS Lite panel
** Can be fitted to M3 size enclosure only
Model No. #80161M2
Page 6
DS47.05.2009
Panels
Product Code
Protocol Zones Loops Printer Size (mm)
A80161M2
A80162M2
A80161M3
A80162M3
A80161M3P
A80162M3P
V80161M2
V80162M2
V80161M3
V80162M3
V80161M3P
V80162M3P
H80161M2
H80162M2
H80161M3
H80162M3
H80161M3P
H80162M3P
Apollo
Apollo
Apollo
Apollo
Apollo
Apollo
Argus Vega
Argus Vega
Argus Vega
Argus Vega
Argus Vega
Argus Vega
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
Hochiki
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
No
No
No
No
Yes
Yes
No
No
No
No
Yes
Yes
No
No
No
No
Yes
Yes
385 x 310 x 90 *
385 x 310 x 90 *
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 310 x 90 *
385 x 310 x 90 *
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 310 x 90 *
385 x 310 x 90 *
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
Specifications
* Flush versions are available to order (See price guide).
Lite Panels
Product Code
Protocol Zones Loops Printer Size (mm)
LA80161M2
LV80161M2
LH80161M2
Apollo
Argus Vega
Hochiki
16
16
16
1
1
1
No
No
No
385 x 310 x 90
385 x 310 x 90
385 x 310 x 90
Technical
Options
Construction
Finish
Colour - lid & box
Colour - controls plate & labels
Mains voltage supply
-
Mains supply fuse
Power supply DC rating
Aux 24V supply
Battery (24 hour standby)
Fault contact rating
Fire contact rating
Alarm contact rating
Sounder output rating
Detection loop
Detector protocols
-
Printer port
Serial expansion port
-
PC port
Network connection
-
Remote Silence input (SIL)
Remote fault input (FLT)
Remote reset input (RES)
Remote alert input (INT)
Remote evacuate input (CNT)
Download lead
Configuration
PC graphics
Modem
-
1.2mm sheet steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
Product Description
Code
K555
110 or 230V AC 50 or 60 Hz.
K560
(specify when ordering, default is 230V)
K547
1.6A 250V
K546
24V 3 Amps
Fused at 500 milliamps
K545
9Ah 12V (2 per panel) (non-networked)
30V DC 1 Amp
K556P
30V DC 1 Amp
30V DC 1 Amp
K232AS
Fused at 1 Amp each
400 milliamp output
K18002
Apollo (S90, XP95, Discovery),
Argus Vega or Hochiki ESP
Serial RS232
Serial RS485
(Compatible with all Syncro I/O modules)
Serial RS232
RS485 - Up to 64 panels via fully fault tolerant
optional network card
Switched -ve
Switched -ve
Switched -ve
Switched -ve
Switched -ve
Standard S187, X187LS economy
Via Loop Explorer PC utility
Via Guide or Guide Net systems
Optional dial up modem for remote diagnostics
(Can be fitted to M3 size enclosure only)
Fault tolerant Network interface card
16 channel input/output board
8 way relay extender board
6 way sounder extender board
4 way conventional detection
zone board
Modem module (PSTN)
(M3 size enclosure only)
Printer Module
(M3 size enclosure only)
Retrofit Vision Window Door
(M2 size enclosure only)
The manufacturer reserves the right to amend specifications without prior notice
Page 7
Syncro
BS-EN54-2
BS-EN54-4
KM 73505
Analogue Addressable
Fire Control Panels
Product Overview
Available with 2 or 4 detection circuits, each capable of hosting
up to 126 devices (Apollo), 240 devices (Argus Vega) or 127
devices (Hochiki). Syncro uses the most advanced
microprocessor technology to provide a control system of
extremely high integrity.
Syncro can be configured to suit all types of system, from the
most simple, to the highly complex. Its fully integrated and
secure network provides an intelligent interface for building
control.
Features
2 or 4 loop versions as standard
(for 6 - 8 loop versions see DS57 page
10-11)
Larger versions available (fits 24A/H SLAs)
A large area graphic display ensures that information is
presented in plain language with detailed extra help available
by pressing a ‘help’ button.
Syncro supports three of the most widely used communication
protocols produced by leading fire detector manufacturers and
employs daily calibration routines to ensure that the system is
always at optimum performance.
Loopless panel option (repeater)
(Also backward-compatible
with Series 90 detectors)
0, 16, 48, or 96 zone indicators
Option for Enable Control keyswitch
Fully supports Apollo, Argus Vega
& Hochiki protocols
R
Config. Features
Comprehensive day/night mode facility
Programmable one touch test mode
Network up to 64 panels/repeaters
Powerful and versatile cause & effect programming
4 programmable sounder circuits as
standard
Cause & effect wizard including:
4 amp power supply to EN54 part 4
Large graphic display
Cause & effect action
Disablement configuration
Test mode configuration
In built help and alarm information
screens
Complies with EN54-2/4
Real time clock
Supports Apollo, Argus Vega and Hochiki
loop powered sounders and beacons
Supports Apollo Ancillary Base Sounder
Supports Apollo Intelligent Beam
Stylish enclosure design
Soft-touch tactile buttons
2 programmable function buttons
3 programmable front panel mounted
LED’s
Thermal printer (optional)
Up to 512 programmable inputs/outputs
per panel via 2 wire RS485 serial link
(optional)
Simple Windows® graphical
configuration utility
Page 8
Model No. EN#6396403P
DS16.13.2009
Panels
2 Loop Panels
EN#6300203
EN#6316203
EN#6348203
EN#6396203
2
2
2
2
0
16
48
96
500 x 355 x 117
500 x 355 x 117
500 x 355 x 117
500 x 355 x 117
4 Loop Panels 4 Loop Panels
Larger Enclosure
Product Code Loops Zones Size (mm)
EN#6300403
EN#6316403
EN#6348403
EN#6396403
4
4
4
4
0
16
48
96
500 x 355 x 117
500 x 355 x 117
500 x 355 x 117
500 x 355 x 117
EN#6300415
EN#6316415
EN#6348415
EN#6396415
4
4
4
4
0
16
48
96
500 x 460 x 190
500 x 460 x 190
500 x 460 x 190
500 x 460 x 190
Specifications
‘#’ - replace with ‘A’ for Apollo protocol,
‘V’ for Argus Vega protocol or ‘H’ for Hochiki protocol.
Flush versions are available to order (See price guide).
For fitted printer add ‘P’ after stock code.
Options
Product Code Description
K552#
K555
K232SYN
K560
K547
K546
K545
K556P
506mm
Loop extension card (loops 3 & 4)
Fault tolerant Network interface card
Thermal printer kit (for retrofitting to non-printer models)
16 channel input/output board
8 way relay extender board
6 way sounder extender board
4 way conventional detection zone board
Modem module (PSTN)
‘#’ - replace with ‘A’ for Apollo protocol,
‘V’ for Argus Vega protocol or ‘H’ for Hochiki protocol.
361mm
Technical
Finish
Colour - lid & box
Colour - controls plate & labels
Detection circuits (Loops)
Zone LED’s
Display
4 sounder circuits
Fire contact
Alarm contact
Fault contact
Programmable relay 1
Programmable relay 2
Fire routing output
Fault routing output
Extinguisher output
Fault input
Reset input
Intermittent input
Continuous input
Silence input
Programmable input 1
Programmable input 2
Programmable input 3
Auxiliary 24V DC output
System fuse
Mains fuse
Operating Temperature
Operating humidity
Mains voltage supply
-
Battery (24 hour standby)
Day/night modes
Input delays
Output delays
2 programmable function
buttons
3 programmable indicators
Network (option)
Printer (option)
Download lead
-
Epoxy powder coated
BS 00 A 05 grey - fine texture
130mm
Model No. EN#6396414
RAL 7047 light grey - satin
2 or 4 (400mA each)
Bezel extends 15mm
0, 16, 48, or 96 (up to 500 software zones)
in each direction
240 x 64 pixels graphic LCD
Each fused at 1 Amp (total load 2 Amp)
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Flush Syncro Control Panel
Volt free 1 Amp 30V DC
Monitored-voltage reversing, fused at 500mA
Monitored-voltage reversing, fused at 500mA
Monitored-voltage reversing, fused at 1A
Volt free contact input signals fault
Volt free contact input resets panel
Volt free contact input pulses sounder outputs
Control
Volt free contact input for continuous sounders
Panel
Volt free contact input silences sounders
Volt free contact for any action required
Volt free contact for any action required
Volt free contact for any action required
Fused at 500mA
Wall
5 Amp self-resetting polyfuse
20mm 3 Amp
Flush mount cross section
-5 to +50 deg. C
Note: There is one size for all
To 95% (non-condensing)
standard flush Syncro control
110 or 230V AC 50 or 60 Hz.
panels. For the hole size we
(specify when ordering, default is 230V)
recommend that you allow
12Ah 12V (2 per panel) (non-networked)
5mm clearance all round.
2 with variable device sensitivity
Individual for each device selectable up to 2 minutes
Individual 2-stage to 10 minutes per stage
Programmable to carry out any cause & effect,
disablement or test action
Red/yellow/green to indicate any action
Up to 64 panels on 2 wires (S555 Network Card required)
40 column thermal
S187 (standard) or X187LS (economy)
The manufacturer reserves the right to amend specifications without prior notice
Page 9
Syncro
Analogue Addressable Fire
Control Panels 6 or 8 Loops
Product Overview
Available with 6 or 8 detection circuits, each capable of hosting
up to 126 devices (Apollo), 240 devices (Argus Vega) or 127
devices (Hochiki). Syncro uses the most advanced
microprocessor technology to provide a control system of
extremely high integrity.
Syncro can be configured to suit all types of system, from the
most simple, to the highly complex. Its fully integrated and
secure network provides comprehensive scalability.
A large area graphic display ensures that information is
presented in plain language with detailed extra help available
by pressing a ‘help’ button.
Features
6 or 8 loop versions as standard
96 zone indicators
Fully supports Apollo, Argus Vega & Hochiki
protocols
Network up to 32 6 or 8 loop panels
(Also backward-compatible
with Series 90 detectors)
8 programmable sounder circuits as standard
2 x 4 amp PSU’s to EN54 part 4
Large graphic display
In built help and alarm information screens
Complies with EN54-2/4
R
Syncro supports three of the most widely used communication
protocols produced by leading fire detector manufacturers and
employs daily calibration routines to ensure that the system is
always at optimum performance.
Config. Features
Comprehensive day/night mode facility
Programmable one touch test mode
Powerful and versatile cause & effect programming
Cause & effect wizard including:
Cause & effect action
Disablement configuration
Test mode configuration
Real time clock
Supports Apollo, Argus Vega and Hochiki
loop powered sounders and beacons
Stylish enclosure design
Soft-touch tactile buttons
2 programmable function buttons
3 programmable front panel mounted LED’s
Thermal printer (optional)
Up to 1024 programmable
inputs/outputs per panel via 2 wire RS485
serial link (optional)
Simple Windows® graphical configuration
utility
Wide choice of languages available
Model No. EN#63966S4P
Page 10
DS57.02.2009
Panels
Product Code
Loops Enable Zones Size (mm)
Control
EN#63966S4
ENS#63966S4
EN#63968S4
ENS#63968S4
No
Yes
No
Yes
6
6
8
8
96
96
96
96
500W x 650H x 137D
500W x 650H x 137D
500W x 650H x 137D
500W x 650H x 137D
Specifications
‘#’ - replace with ‘A’ for Apollo protocol,
‘V’ for Argus Vega protocol or ‘H’ for Hochiki protocol.
For fitted printer add ‘P’ after stock code.
Technical
Options
Finish
Colour - lid & box
Colour - controls plate & labels
Detection circuits (Loops)
Zone LED’s
Display
8 sounder circuits
-
2 x Fire contact
2 x Alarm contact
2 x Fault contact
2 x Programmable relay 1
2 x Programmable relay 2
2 x Fire routing output
-
2 x Fault routing output
-
2 x Extinguisher output
-
2 x Fault input
2 x Reset input
2 x Intermittent input
2 x Continuous input
2 x Silence input
2 x Programmable input 1
2 x Programmable input 2
2 x Programmable input 3
2 x Auxiliary 24V DC output
2 x System fuse
2 x Mains fuse
Operating Temperature
Operating humidity
Mains voltage supply
Battery (24 hour standby)
Day/night modes
Input delays
Output delays
2 programmable
function buttons
3 programmable indicators
Network
Printer (option)
Download lead
-
Epoxy powder coated
Description
Product
BS 00 A 05 grey - fine texture
Code
RAL 7047 light grey - satin
Loop extension card (loops 7 & 8)
K552#
6 or 8 (400mA each)
Thermal printer kit (for retrofitting
K232SYN
96 (up to 500 software zones)
to non-printer models)
240 x 64 pixels graphic LCD
16 channel input/output board
K560
Each fused at 1 Amp
(total load 2 Amp per bank of 4 circuits) K547
8 way relay extender board
Volt free 1 Amp 30V DC
6 way sounder extender board
K546
Volt free 1 Amp 30V DC
4 way conventional detection zone
K545
Volt free 1 Amp 30V DC
board
Volt free 1 Amp 30V DC
Modem module (PSTN)
K556P
Volt free 1 Amp 30V DC
Monitored-voltage reversing,
fused at 500mA
Monitored-voltage reversing,
‘#’ - replace with ‘A’ for Apollo protocol,
fused at 500mA
‘V’ for Argus Vega protocol or ‘H’ for Hochiki protocol.
Monitored-voltage reversing,
fused at 1A
Volt free contact input signals fault
Volt free contact input resets panel
Volt free contact input pulses sounder outputs
Volt free contact input for continuous sounders
Volt free contact input silences sounders
Volt free contact for any action required
Volt free contact for any action required
Volt free contact for any action required
Fused at 500mA
5 Amp self-resetting polyfuse
20mm 3 Amp
-5 to +50 deg. C
To 95% (non-condensing)
110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V)
12Ah 12V (4 per panel) (non-networked)
2 with variable device sensitivity
Individual for each device selectable up to 2 minutes
Individual 2-stage to 10 minutes per stage
Programmable to carry out any cause & effect,
disablement or test action
Red/yellow/green to indicate any action
Up to 32 6 or 8 loop panels on 2 wires
40 column thermal
S187 (standard) or X187LS (economy)
The manufacturer reserves the right to amend specifications without prior notice
Page 11
Syncro
Response
Analogue Addressable
Fire Control Panel Repeaters
Product Overview
Syncro Response is a full function repeater panel used to
compliment the Syncro control panel range. Syncro Response
uses the most advanced microprocessor technology to provide
a control system of extremely high integrity.
Syncro Response can be configured to suit all types of system,
to provide selectable event reporting and controls from each
panel on the network.
A large area graphic display ensures that information is
presented in plain language with detailed extra help available
by pressing a “help” button.
Features
0, 16, 48, or 96 zone indicators
Syncro networks support three of the most widely used
communication protocols used by leading fire detection
manufacturers.
Network up to 64 panels/repeaters
4 amp power supply to EN54 part 4
Large graphic display
Config. Features
In built help and alarm information
screens
Programmable one touch test mode
Complies with EN54-2
Powerful and versatile cause & effect programming
Real time clock
Cause & effect wizard including:
Stylish enclosure design
Cause & effect action
Disablement configuration
Test mode configuration
Soft-touch tactile buttons
2 programmable function buttons
3 programmable front panel mounted
LED’s
Thermal printer (optional)
Up to 512 programmable inputs/outputs
per panel via 2 wire RS485 serial link
(optional)
Simple Windows graphical
configuration utility
Model No. #6196003
Page 12
DS17.08.2009
Panels
Product Code Loops Zones Size (mm)
Construction
K6100003
K6116003
K6148003
K6196003
All steel enclosure
All steel enclosure
All steel enclosure
All steel enclosure
0
0
0
0
0
500 x 355 x 117
16
500 x 355 x 117
48
500 x 355 x 117
96
500 x 355 x 117
Flush versions are available to order.
For fitted printer add ‘P’ after stock code
Specifications
Options
Product Code Description
K232SYN
K560
K547
K546
K545
K556P
Thermal printer kit
(for retrofitting to non printer models)
16 channel input/output board
8 way relay extender board
6 way sounder extender board
4 way conventional detection zone board
Modem module (PSTN)
Technical
Finish
Colour - lid & box
Colour - controls plate & labels
Zones
Display
Alarm contact
Fault contact
Programmable relay 1
Programmable relay 2
Auxiliary 24V DC output
System fuse
Mains fuse
Operating Temperature
Operating humidity
Mains voltage supply
Battery (24 hour standby)
Day/night modes
Input delays
Output delays
2 programmable function buttons
3 programmable indicators
Printer (option)
Download lead
-
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
0, 16, 48, or 96
240 x 64 pixels graphic LCD
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Volt free 1 Amp 30V DC
Fused at 500mA
5 Amp self-resetting polyfuse
20mm 3 Amp
-5 to +50 deg. C
To 95% (non-condensing)
110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V)
12V 12Ah (2 per panel)
2 with variable device sensitivity
Individual for each input selectable up to 2 minutes
Individual 2-stage to 10 minutes per stage
Programmable to carry out any cause & effect, disablement or test action
Red/yellow/green to indicate any action
40 column thermal
S187 (standard) or X187LS (economy)
Note: Syncro Response is supplied complete with S555 network interface card fitted.
Note: If this panel is to be fitted to an existing system the main panel must be also be fitted with and S555
network interface card to enable communications. 6 & 8 loop panels have a network card fitted as standard.
The manufacturer reserves the right to amend specifications without prior notice
Page 13
Syncro
Syncro
Focus+
Focus
Network LCD Repeaters
Features
Product Overview
Large graphic display
This simple and attractive repeater
panel can be connected to any point
on a Syncro network to provide
additional display points as needed.
Simple connection to Syncro
network
24V DC powered
(230V AC available)
Using the same large format
graphics display as the main control
panel ensures that a clear and concise
indication is given at all times.
Small attractive enclosure
Configurable to display all
or any events
Simple to install
Volt free Alarm, Fire and Fault
contacts
Up to 63 repeaters can be
connected to a panel
Focus+ with full controls has the
following extra buttons:
A
Silence Alarm
Resound Alarm
Reset
1.2 KILOMETRES MAX.
Ideal for additional building
entrances, security desks or nurses
stations this unit provides an
economical alternative to a full
function repeater panel. (Syncro
Response) The repeater also acts as a
network booster and can be used to
extend cable runs beyond the
specified lengths as required.
B
NETWORK
NETWORK
NETWORK
NETWORK
NETWORK
NETWORK
PANEL 1
0 LOOP
PANEL 2
2 LOOP
PANEL 3
4 LOOP
PANEL 4
4 LOOP
FOCUS
PANEL 5
FOCUS+
PANEL 6
REPEATER
REMOTE
MONITORING
& CONTROL
ALLOWS DISTANCES
GREATER THAN
1.2 KILOMETRES
PC
GRAPHICS
SYSTEM
NETWORK
REPEATER
PANEL 9
SIGNAL
BOOSTER
PANEL 7
Note:
Signal booster is a Focus or Focus+
repeater used as a booster.
REPEATER
PANEL 8
Example of a Syncro high integrity network
Focus Model No. K69000M1
Page 14
Focus+ Model No. K691000M1
DS24.09.2009
Focus Units
Product Code
K68000M1
K69000M1
K68000F1
K69000F1
PSU
Weight
Build
750mA
750mA
2.5kg
4.0kg
2.5kg
4.0kg
Surface
Surface
Semi Flush
Semi Flush
PSU
Weight
Build
750mA
750mA
3.5kg
4.0kg
3.5kg
4.0kg
Surface
Surface
Semi Flush
Semi Flush
Size (mm)
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
Specifications
Focus+ Units
Product Code
K681000M1
K691000M1
K681000F1
K691000F1
Size (mm)
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
Syncro Focus/Focus+ PCB
24V
NET.
OUT
NET.
IN
PSU
FLT.
NC C
FAULT
FIRE
From
previous
panel on
network
24V
battery
backed
power
(2.3Ah for
24H standby)
ALARM
NO NC C NC NO C NC NO C
To normally
closed contact
on local PSU
To next
panel on
network
Technical
Construction
Finish
Colour - lid & box
Colour - controls plate & labels
Input voltage (24V DC model)
Input voltage (230V AC model)
Current consumption
Alarm current
Alarm contact rating
Fire contact rating
Fault contact rating
Display
Cable entry
Indicators
Battery Size
(24 hr. standby on 230V AC model)
Communications
Cable length
Network cable type
Operating temperature
-
1.2mm sheet steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
Ral 7047 light grey - satin
21V DC - 30V DC
230V AC +10%/-15%
80mA at 24V DC (in fault condition)
100mA at 24V DC
30V DC 1 Amp max.
30V DC 1 Amp max.
30V DC 1 Amp max.
240 x 64 pixel graphic LCD
20mm knockouts
5mm high brightness LED
2.3Ah 12V (2 per panel)
- Syncro system network protocol only
- 1200 metres to adjacent nodes
(subject to cable type)
(see technical manual)
- Belden 9271, Belden 9860, FP200 Gold
- -5°C to +40°C
NOTE: An K555 network card is required in the Syncro/Syncro AS panel in order to communicate
with these products. 6 - 8 loop panels have a network card fitted as standard.
The manufacturer reserves the right to amend specifications without prior notice
Page 15
Syncro
View
Local LCD Control
Panel Repeater
Product Overview
Designed and manufactured to the highest standards in a
quality controlled environment the Syncro VIEW fire alarm
annunciator provides a simple and convenient method of
extending the controls and indications of the Syncro fire alarm
control panel to other locations.
The large, graphic liquid crystal display and high brightness LED
indicators duplicate the indications on the Syncro fire alarm
control panel at up to 15 additional locations via a simple,
two-wire serial data connection.
Features
Up to 15 annunciators can be connected to
each Syncro, Syncro Response or
Syncro AS fire control panel.
Large liquid crystal display (240 x 64 pixels)
High brightness LED indications
Internal sounder
Replicates all Syncro panel controls
Simple, two-wire serial connection
The Syncro VIEW is available in either a 24V DC powered option
(which can be powered via an additional 2 cores from the Syncro
control panel/local 24V DC supply) or a 230V powered option
with local battery back up.
Syncro VIEW is housed in a small enclosure which is styled
similarly to the Syncro control panel and is ideal for installations
where a large control panel would be detrimental to décor such
as entrance halls.
Up to 15 Syncro VIEW annunciators can be connected to each
control panel on the Syncro network making VIEW ideal where
multiple points of indication and/or control are required such as
nurses stations or shop units.
Small, Syncro style enclosure
Removable electronics for easy installation
24V DC or 230V AC power options
Low power consumption
Multi language options
Connection monitored by Syncro fire
control panel
Model No. K67750M1
Page 16
DS43.03.2009
Equipment
Product Code Description
K67000M1
K67750M1
K67001M1
K67751M1
Specifications
PSU Size (mm)
Syncro View repeater panel
Syncro View repeater panel
Syncro View repeater panel c/w enable keyswitch
Syncro View repeater panel c/w enable keyswitch
750mA
750mA
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
330 x 255 x 90
Semi-flush versions are available to order
Syncro Control Panel
Syncro View #1
Comms
Aux 24V
Comms
In
Comms
Out
24V In
24V Out
Syncro View #15
Comms
In
Comms
Out
24V In
24V Out
Technical
Construction
Cable entry
Finish
Colour - lid & box
Colour - controls plate & labels
Mains supply (Mains models only)
24V supply (24V DC models only)
Mains supply fuse
Power supply rating
Maximum ripple current
Battery type (Yuasa NP)
Battery charge voltage
Battery charge current
Battery fuse
Maximum current draw from batteries
Quiescent current of panel in mains fail
Serial data connection
Maximum terminal capacity
-
1.2mmMild steel
5 x 20mm knockouts in top of box and 5 in rear
Epoxy powder coated
BS 00 A 05 grey - fine texture
Ral 7047 light grey - satin
230V AC +10% - 15% (20 Watts maximum)
21 to 30V DC
2 Amp, 20mm
28V 750mA total (including battery charging)
200 millivolts
Two 12 Volt 1.9Ah sealed lead acid in series
27.6VDC nominal
200mA maximum
200mA, 20mm, glass
95mA
0.03 Amps
2 core RS485 (Up to 1200 metres total cable length)
2.5mm²
The manufacturer reserves the right to amend specifications without prior notice
Page 17
Programmable,
LED Indication Panels
Features
8 and 24 LED versions available as
standard
Large versions available to special order
Up to 16 x 24 way Syncro Ident can be
connected to each fire panel
Programmable flashing or steady states
Red, yellow or green indications/ options
Common Fire, Fault and Disabled
indication
Customisable label identification tags
!
EW
Ident
N
Syncro
Product Overview
Syncro Ident panels provide a compact and attractive display
for up to 24 indications from a Syncro or Syncro AS fire control
panel.
As with all inputs and outputs on the Syncro system, each
indicator is fully programmable to indicate a variety of events
as well as being fully programmable via cause and effects to
operate in response to logically connected inputs. Each
indication defaults to a zonal fire indicator but may be
configured via the Loop Explorer configuration utility to
operate upon any event type or combination of inputs.
Requiring only a low current 24V power supply and a 2 core
data connection to the fire panel, Syncro Ident panels can be
installed quickly and easily to provide supplementary
information on the status of the fire alarm system with the
minimum of cost and effort.
The compact, slimline enclosure is unobtrusive and is ideal for
mounting in locations where a larger control and indication
unit would be unsuitable.
Each indication has a dedicated field for customized text to
provide a concise description of the indication.
Multiple Syncro Ident panels can be connected to the Syncro
serial bus to provide a diverse range of indications at multiple
locations.
Buzzer with silence control and re-sound
Lamp test control
Low power 24V DC supply
Connects to 2 wire Syncro RS485
data bus
Multiple language options
Model No. K6524L2
Page 18
DS60.01.2009
Panels
No. of LEDs
Product Code
K6508L2
K6524L2
8
24
Specifications
Size (mm)
385 x 310 x 60
385 x 310 x 60
Technical
Construction
Finish
Colour - lid & box
Colour - controls
plate & labels
LED colours
Supply Voltage
Data Connection
1.2mm mild steel
Epoxy powder coated
-
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
- Red, yellow or green
- 18 to 30V DC
- RS485 Syncro comms bus (Max 1200 metres)
Examples of Syncro Ident panel used to provide supplementary indications from the fire control panel
Syncro AS Fire
Control Panel
Fire
More Events
Power On
General
Disablement
Pre-Alarm
General Fault
On Test
Power Fault
Buzzer Silenced
System Fault
Delay Active
Re-Sound
Alarm
1
15:05 Tuesday 10 October 2006
KENTEC ELECTRONICS LIMITED
4
Fire in Zone
Exit
Enter
More
Fires
More
Events
?
2
3
1
Sounder
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Fault/Disabled
Silence Alarm
(Acknowledge)
Silence
Buzzer
Lamp
Test
Reset
Evacuate
Function
Plant Status
Zonal Fire Indicators
RS485
2 Core
Data Cable
Enable Control
2 Core
Power Cable
Fire Protection
Indicator
Lamp Test
Fire
Buzzer Silence
Power On
Power On
Fault
Fault
Disablement
Disablement
Fire Detection
Indicator
Fire Detection
Indicator
Model:
Model:
Lamp Test
Buzzer Silence
Lamp Test
Buzzer Silence
LT
Model:
Fire
1
2
3
4
5
6
11
I/O CHANNEL
7
8
9
10
Pre-Alarm
Fire Routing On
15
Enable
Control
I/O
24V 0V 0V 0V
Alarm
Silence
0V
Reset
Fault
More Events
COMMS IN
4
Exit
?
3
Power Fault
More
Events
2
System Fault
Sounder
Fault/Disabled
Enter
Fire Routing
Fault/Disabled
Fire
Silence Alarm
(Acknowledge)
Silence
Buzzer
Lamp
Test
Reset
Function
One
Power On
Function
Two
Fault
Disablement
0V 24V 0V
IN
More
Fires
Delay Active
General
Disablement
Re-Sound
Alarm
Disablement
General Fault
1
Buzzer Silenced
COMMS OUT OUT
Power On
Buzzer
Silence
KENTEC ELECTRONICS LIMITED
On Test
16
Lamp
Test
15:05 Tuesday 22 August 2006
Power On
13
14
Fire
Fire
12
Fire Alarm
Repeater
Fire Detection
Indicator
Fire Alarm
Mimic Display
Model:
Syncro Matrix
Syncro I/O
Syncro View
Disabled Refuge Alarms
Other RS485 compatible devices
The manufacturer reserves the right to amend specifications without prior notice
Page 19
Syncro
Matrix
Product Overview
Intelligent Fire Alarm
Mimic Display System
The Syncro Matrix system uses flexible, fibre optic light guides to
illuminate areas on a floor plan, laid over a high resolution grid.
This unique system dispenses completely with wiring and
enables indicators to be moved, removed or added on site
without the need for any wiring.
Features
Up to 504 LED’s can be controlled
from any Syncro or Syncro AS panel
Select up to 12 printed colours
(not including background and
building outline)
Available in a range of standard
enclosures to suit any applications
Bespoke sized units can be made
upon request
Choice of Red, Green or Yellow LED’s
All indicators can be configured to operate upon any event type
and at point, zone or group level via Kentec’s powerful and
intuitive Loop Explorer configuration programme. Syncro Matrix
can be supplied with or without LEDs and controls. Optional
LEDs indicate Power on, Fire, Fault and Disablement and
optional controls are for Alarm silence, Buzzer silence, Lamp test
and Reset.
Housed in attractive, slimline enclosures to match Syncro and
Syncro AS fire alarm panels and with high quality, full colour
or monochrome floor plans, Syncro Matrix provides a clear,
geographical indication of fire alarm activation enabling speedy
identification of the source of an alarm.
Available with or without controls
Same look and feel as Syncro range
Syncro Matrix can easily be upgraded
on site with minimal cost and effort
EN54-4 approved PSU (optional)
Configured via standard Loop
Explorer Software
View showing mimic mounted
on inner door
View showing LED grid
View showing internal layout
PSU optional
Page 20
M3 size Syncro Matrix
DS52.02.2009
Specifications
Panels
No.
LED’s
Standby Full Alarm Batteries for Batteries for
Current Current
24 hours
48 hours
0.026
0.052
0.78
24
56
88
0.09
0.18
0.36
0.88Ah
1.75Ah
11Ah
1.76Ah
3.5Ah
22Ah
Enclosure Size Options
Max. number of
Max. number of
Max. number of
Max. number of
LED’s = 24
LED’s = 56
LED’s = 88
LED’s = 56
Will house 1 x 8 Red LED Will house 1 x 8 Red LED Will house 1 x 8 Red LED Will house 1 x 8 Red LED
driver PCB and
driver PCB and
driver PCB and
driver PCB and
1 x 16 LED
3 x 16 LED
5 x 16 LED
3 x 16 LED
extension PCB’s
extension PCB’s
extension PCB’s
extension PCB’s
(Red, Green or Yellow)
(Red, Green or Yellow)
(Red, Green or Yellow) (Red, Green or Yellow)
Max. number of
LED’s = 504
Will house 1 x 8 LED
driver PCB (Red) and up to
31 x 16 LED
extension PCB’s
(Red, Green or Yellow)
Bespoke Size
S4
?
?
M3
S3
M2
303
185
385mm x 310mm
90mm Deep
400
515
400
400
303
225
500mm x 355mm
117mm Deep
385mm x 520mm
110mm Deep
500mm x 650mm
137mm Deep
Colour/Finish & Size
to suit your requirements
Technical
Mains supply (230V Versions only)
Mains supply fuse (230 V Versions only)
Power supply rating (230 V Versions only)
Max. ripple current (230 V Versions only)
Battery type (Yuasa NP)
(230 V Versions only)
Battery charge voltage
(230 V Versions only)
Battery charge current
(230 V Versions only)
Max. current draw from batteries
(230 V Versions only)
Quiescent current
Supply voltage (24V versions)
Supply current
Terminal capacity
Enclosure Size & mimic area
Construction
Finish
Colour - lid & box
Colour - controls plate & labels
Mimic
Enable keyswitch (if fitted)
Cabinet locks
Communications interface
Maximum distance from control panel
IP rating
Operating temperature
Number of indicators (standard models)
-
230V AC +10% - 15% (100 Watts max.)
T2A L250V Replace only with similar type
4 Amps total including battery charge 28V +/ 2V
200 millivolts
Two 12 Volt sealed lead acid (7Ah maximum)
- 27.6VDC nominal (temperature compensated)
- 1.5A maximum
- 3 Amps. With mains power source disconnected
-
See above
21 to 30V DC
See above
0.5mm2 to 2.5mm2 solid or stranded wire
See ‘Enclosure Size Options’
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
3mm Clear Anti-Glare Acrylic
Standard 901 key
M2/M3 - standard 801 key, S3/S4 - standard KT3001 key
RS485 – Syncro/Syncro AS serial I/O bus protocol
1.2Km using RS485 data cable
IP30
-5°C to +50°C
M2 size - up to 24, M3 and S3 size - up to 56, S4 size - up to 88
The manufacturer reserves the right to amend specifications without prior notice
Page 21
Syncro
Net
Syncro
Networking
Product Overview
The flexibility of the Syncro system can be further enhanced by
connecting control panels and repeaters together using a high
integrity network.
A simple 2-wire connection between each panel allows events
to be transmitted to other parts of the system to provide
indication or control on a system wide basis.
Using the Loop Explorer configuration programme, up to 64
nodes can be programmed to respond in a variety of ways to
any system events as required.
Features
Up to 64 nodes
High integrity protocol
Fully secure against short or open circuit
faults
Simple 2-wire loop connection
This flexibility extends the comprehensive cause and effect
programming capability of Syncro control panels to the entire
network allowing actions, test modes or disablements to be
started from any point.
The fault tolerance of the network is such that any single open
or short circuit fault will not result in any loss of information.
Multiple faults are isolated and the network breaks into smaller
networks which continue to work autonomously.
Supports open ended networks for
retrofit applications
Repeaters share network connection
Network wide test and disablement
functions
Network wide cause and effect logic
Flexible configuration options
Panels configurable to act on network
events or not as required
Apollo & Hochiki panels supported on
single network
Part No. K555
Page 22
DS23.07.2009
Flexible network configuration options using simple to follow PC
configuration programme
Specifications
Two core loop wiring ensures network integrity by
providing full isolation of faulty wiring segments.
2 Core
Control Panel
Control Panel
2 Core
(Not fitted
on open
ended
networks)
2 Core
Control Panel
Technical
Product code
Protocol
Connection
Current Consumption
Integrity
Indicators
Cable length
Cable type
Compatible panels
K555
RS485
Two wire loop
40mA
Full isolation of faulty nodes or wiring segments
Data In and Data Out communications status
1200 metres to adjacent nodes
(subject to cable type) (see technical manual)
- Belden 9271, Belden 9860, FP200 Gold
- Syncro/Syncro AS (required for networking)
Syncro Response/Syncro 6 & 8 loop, Syncro Focus (supplied with panel)
-
The manufacturer reserves the right to amend specifications without prior notice
Page 23
Syncro
Comms
Communications
Module (modem)
Product Overview
The K556 communications module enables service companies
to interrogate control panels remotely via a telephone link.
The communications module is simple to install and requires a
PSTN telephone line.
The module mounts on existing pillars in the control panel and
is supplied with all wiring and connections to enable speedy
installation and commissioning.
Features
View devices near calibration limits
Plan maintenance visits
Retrieve event log
Dial in and observe reported faults
Assist commissioning from remote
location
Offer value added service to customers
Check software version to see if updates
are available
Retrieve configuration
Avoid unnecessary call outs
Simple to install
Dongle protected access, for customers
security
Page 24
Once connected to the control panel via the Loop Explorer
software, users can upload configuration data and event logs
or take control of the system via the virtual panel interface.
This allows the panel controls to be operated as if the user was
standing at the panel.
The Loop Explorer configuration programme (version 3.0 or
higher) is used to dial into control panels but the dial up facility
will not be available unless the PC calling the control panel is
fitted with a registered dongle (part number B2158 for parallel
port or B2158USB for USB version).
DS31.06.2009
PC running Loop Explorer
Programme & fitted with Dongle
Public Telephone
Network
Specifications
Syncro Control Panel
fitted with Communications Module
Note: The Communications Module is compatible with Loop Explorer Software version 3 or above
and Syncro Control Panel Firmware version 3 or above.
Technical
Module part number
Size
Supply voltage
Current consumption
Connection
Dongle part number
-
K556P (PSTN)
190mm x 62mm x 40mm
21V to 30V DC
50 milliamps
PSTN
B2158 (parallel port)
B2158USB (USB serial port)
Note: One dongle required per user, to enable the
‘dial in’ facility within the Loop Explorer program
The manufacturer reserves the right to amend specifications without prior notice
Page 25
Syncro
GUIDE
Graphical User Interface
for fire Detection Equipment
Product Overview
Syncro fire control panels can send data to, and be controlled
by, the Guide system providing a single point of co-ordination
for all alarms.
The powerful 32 bit programme features a standard Windows
look and feel and runs under Windows® 2000 or XP.
The system is highly configurable in terms of the style of
presentation so that the end user can be presented with maps,
text, photographs, audio or a combination of all as required.
User profiles allow the system manager to control the facilities
available to each individual system user.
Virtual Panel - allows direct control
A comprehensive history logging and reporting system
allows analysis of events and trends to be identified to reduce
unwanted alarms.
Easy to programme and simple to use, Guide provides a cost
effective solution for fire alarm management at many levels.
Powerful Event log filtering
Features
Choice of text, graphic, event list
display when an event occurs
Versatile event analysis
Total history archive
Easy to programme
Secure system
Cost effective compared to
other systems
Simple to use
Unlimited map linking & zoom
facility
Support for 100’s of graphics
Display and control for multiple
panels
Event history explore and export
facility to text or HTML
documents
Page 26
DS18.10.2009
Range
Product Code Description
G1001
G1004
G1008
G1016
G1032
G1064
GUIDE software - Single panel package
GUIDE software - 4 panel package
GUIDE software - 8 panel package
GUIDE software - 16 panel package
GUIDE software - 32 panel package
GUIDE software - 64 panel package
Specifications
Note: Guide For use with Syncro Panels. Syncro 6 & 8 loop
panels are considered 2 panels in the packages above.
Technical
Recommended Minimum Notes
Processor
Intel Pentium 1Ghz
Operating system
Memory
Hard disk
Graphics
Windows® XP/Vista
256MB minimum
10GB minimum
1024 x 768 16M colours
Sound card
Loudspeaker
Monitor
Pointing device
Any PC sound card
Any PC speakers
Any that supports above
graphics driver
Mouse essential
Printer
Parallel port
Serial ports
Optional
Optional
One RS232 per network
CDROM drive
Any
Backup drive
CD Writer
The faster the better, 2Ghz
will provide future proofing.
Will operate under Windows® 2000
The larger the better.
>20GB would be better.
The driver must allow this mode with
large fonts. Separate Graphics card with
256MB graphics memory recommended
More convenient if built into PC.
17 inch minimum recommended,
the larger the better. (1024 x 768)
Third button and wheels are supported.
Touch screen option supported
Any type.
Required if parallel printer to be used.
Isolated converter supplied for
connection to fire alarm system.
Required for installation of software
and updates.
To back up history.
Note: Guide will be operating 24 hours a day for many years.
It may be desirable to include on site PC maintenance as part of the package.
Note: The Syncro panel to which the Guide system is connected must not have a printer fitted.
Fire Control
Panel
Fire Control
Panel
Dongle fitted
Guide System
RS485
Fire Control
Panel
The manufacturer reserves the right to amend specifications without prior notice
Page 27
Syncro
GUIDE
Repeater
Providing Repeater Facility
for any GUIDE System
Product Overview
Syncro GUIDE Repeater is an additional facility for the Syncro
GUIDE fire alarm management system.
GUIDE Repeater allows control and monitoring of the Syncro
fire control system to be repeated on dedicated computers
connected to the building Local Area Network.
GUIDE Repeater is highly configurable allowing replication of
the main GUIDE system or alternative information to be given
at the repeater
Features
Up to 16 GUIDE Repeaters may be
connected to a single GUIDE system
All control and monitoring options on
GUIDE are supported on the GUIDE
repeater
Choice of text, graphics, combined display
when an event occurs.
Easy to use
Allows graphical information of fire events
to be shown at alternative locations
Unlimited map linking and zoom facility
Display and control for up to
64-networked Syncro panels
Guide Repeater user interface
Page 28
DS45.02.2009
Range
Product Code Description
GR2001
GR2004
GR2016
Specifications
GUIDE Repeater - single repeater package
GUIDE Repeater - 4 repeater package
GUIDE Repeater - 16 repeater package
Technical
Recommended Minimum Notes
Processor
Intel Pentium 1Ghz
Operating system
Memory
Hard disk
Graphics
Windows® XP/Vista
256MB minimum
10GB minimum
1024 x 768 16M colours
Sound card
Loudspeaker
Monitor
Pointing device
Any PC sound card
Any PC speakers
Any that supports above
graphics driver
Mouse essential
Printer
Parallel port
Network
CDROM drive
Optional
Optional
One network port
Any
Backup drive
CD Writer
The faster the better, 2Ghz
will provide future proofing.
Will operate under Windows® 2000
The larger the better.
>20GB would be better.
The driver must allow this mode with
large fonts. Separate Graphics card with
256MB graphics memory recommended
More convenient if built into PC.
17 inch minimum recommended,
the larger the better. (1024 x 768)
Third button and wheels are supported.
Touch screen option supported
Any type.
Required if parallel printer to be used.
Required for installation of software
and updates.
To back up history.
LAN
Dongle fitted
RS485
Fire Control
Panel
Guide System
The manufacturer reserves the right to amend specifications without prior notice
Page 29
MIOU
LIOU (Lite Version)
Multi Input/Output Unit
Product Overview - MIOU
Occupying less than 20% of the space required by conventional
I/O units, the MIOU replaces the large and expensive enclosures
normally required for this application.
Features - MIOU
Multiple inputs and outputs at one
address
Opto isolated inputs
Volt free contact or switched voltage
outputs
Considerable space and cost saving over
discreet I/O units
Easy clip-on din rail mounting method
Compatible with Solo, Syncro AS and
Syncro control equipment
Low standby supply current
With 8 opto-isolated inputs and 8 volt-free relay contacts (relay
outputs individually selectable as normally open, normally
closed or switched voltage outputs), the MIOU will find a
multitude of uses in concentrated I/O applications.
Product Overview - LIOU
LIOU Lite provides 4 inputs and 4 outputs to a Hochiki analogue
addressable detection loop in a compact and cost effective
package.
The LIOU Lite can replace up to four addressable modules in
approximately the same space taken by one standard module
and is ideal for applications where a concentration of I/O is
needed in a limited space.
Hochiki ESP protocol
The modules can be addressed with the Hochiki, hand held
programmer in the range 1 to 127.
Features - LIOU
All inputs and outputs are fully configurable for any action and
for cause and effect via the Syncro Loop Explorer configuration
utility.
Four optically isolated inputs
Four volt free changeover relay contact
outputs
24V DC powered
Small footprint
Cost effective for concentrated
I/O applications
Built in short circuit isolator
Compatible with Syncro and Syncro AS
addressable fire control panels
Hochiki ESP protocol
The LIOU connects to the ESP loop as per all other ESP devices.
Consider the maximum number of sub-addresses when using
LIOU.
Each unit has an integral short circuit isolator which provides
further cost and space saving.
Note:
MIOU & LIOU are currently compatible with Solo, Syncro and
Syncro AS control panels only.
Note:
MIOU & LIOU support Hochiki ESP protocol only.
Note:
Inputs on MIOU & LIOU are not monitored.
Page 30
LIOU - Model No. K507
MIOU - Din rail mounting version (K559)
DS21.08.2009
Range
Product Code
Module
PSU Weight Size (mm)
K559 (Module Only)
H66000M2
H66750M2
MIOU
MIOU
MIOU
750mA
0.3kg
3.6kg
6.8kg
203(L) x 77(W) x 45(D)
385(L) x 310(H) x 90(D)
385(L) x 310(H) x 90(D)
K507 (Module Only)
HL66000M2
HL66750M2
LIOU
LIOU
LIOU
750mA
0.2kg
3.6kg
6.8kg
119(L) x 99(W)
385(L) x 310(H) x 90(D)
385(L) x 310(H) x 90(D)
Specifications
Technical - MIOU
Boxed unit battery capacity
Finish - lid & box
Colour - lid & box
Boxed unit IP rating
Module mounting
Communication protocol
Supply voltage H6600001
Supply voltage H6675001
Quiescent supply current
Input operated current
Output operated current
Input trigger resistance
Output contact rating
Switched -ve output
Minimum recommended PSU
Operating temperature
Device sub-address count
Address setting
-
2.6Ah 12V (2 per unit)
Epoxy powder coated
BS 00-A-05 grey - fine texture
IP30
Symmetrical or asymmetrical din rail
Hochiki ESP
24V DC
110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V)
10 milliamps
3 milliamps
18 milliamps
1k maximum
30V DC 1 Amp maximum
65 milliamps maximum per output
750 milliamps at 24V DC
-5 to +40 deg. C
17 (of 800 permitted in Syncro / Syncro AS panel)
Hochiki hand held programmer (see TB1010)
Boxed unit battery capacity
Finish - lid & box
Colour - lid & box
Module mounting
Communication protocol
Supply voltage
(K507 & HL6600M2)
Supply voltage (HL66750M2)
Mains fuse for HL67750M2
-
2.6Ah 12V (2 per unit)
Epoxy powder coated,
Quiescent supply current
Input operated current
Output operated current
Input trigger resistance
Output contact rating
minimum recommended PSU
Operating temperature
Device sub-address count
-
Technical - LIOU
Control Panel
BS 00 A 05 grey - fine texture
4 x 4mm holes in PCB
Hochiki ESP
21 to 30V DC
- 230V AC
- 20mm ceramic 2A/250V fast
acting
10 milliamps
3 milliamps
18 milliamps
1K maximum
30V DC/2A - 230V AC/0.5A
750 milliamps at 24V DC
-5 to +40 deg. C
17 (of 800 permitted in Syncro /
Syncro AS panel)
24V DC
LIOU/
MIOU
CHQ-DIM
FIRE
BREAK GLASS
PRESS HERE
CHQ-DRC
The manufacturer reserves the right to amend specifications without prior notice
Page 31
Syncro
iO
16 Channel
Input/Output Board
Product Overview
To add more I/O capability to the extensive options already
offered by the Syncro control panel, up to thirty two, sixteen
channel I/O boards may be connected.
The 16 channel boards may be mixed on the RS485 bus with 8
way sounder boards, 6 way sounder boards or 4 way
conventional detection zone boards to provide a very flexible
system of I/O to satisfy any requirement.
When using a simple two wire RS485 communications protocol,
these boards may be mounted locally to the control panel or
distributed on a bus up to 1200 metres long by using a suitable
cable.
Features
16 channels
Each channel configurable as input or
output
Inputs opto-isolated
Outputs open collector transistor
Simple 2 wire connection to control panel
Up to 32 boards supported per panel
(512 Input/Output Channels)
Inputs and outputs configurable as per
field devices
Full cause and effects on all inputs and
outputs
Multi drop RS485 communications
The flexibility of these boards is further enhanced by the fact
that each of the channels is configurable as either an input or
and output.
Each channel may also be configured to produce a variety of
input actions or respond to a variety of output types.
All channels can contribute to, or respond to, system wide cause
and effects logic.
Typical uses for I/O boards include geographical LED mimic
displays and plant alarm inputs.
Standard Syncro control panels contain fixings for one sounder,
relay, conventional detection or I/O board, which can easily be
connected using four small signal wires to the power and comms
bus within the panel.
Consideration must be taken as to the loading on the main
panel.
Can be used with other Syncro I/O
modules on the same panel
Compatible with Syncro AS panels
Part No. K560
Page 32
DS22.06.2009
Technical
Product code
Supply voltage
Quiescent current
consumption
Current per input
Current per output
Communications
Maximum distance
from panel
PCB size
Cable capacity
Operating temperature
Operating humidity
Specifications
- K560
- 21 - 30V DC
- 20mA
-
3mA (maximum)
100mA (maximum)
RS485 two wire
1.2Km (using correct type of cable)
-
190mm x 61mm
2.5mm per terminal
-10°C to +50°C
To 95% (non condensing)
For full technical and application details see the Syncro I/O Board manual
Syncro 16 Channel
I/O Board
SNDR.1
SNDR.2
SNDR.3
SNDR.4
1
FIRE
ROUTING
2
FAULT
ROUTING
4
EXTINGUISHER
OUTPUT
6
1.
3
5
Syncro
Main PCB
REMOTE
CONTROL
AND AUX.
INPUTS
INT
11
5.
SIL
12
0V
13
6. PR1
14
7. PR2
15
16
I/O
AUX
24V
OUT
0V
0V
0V
24V
COMMS
OUT
0V
NETWORK
OUT
To Next
I/O Board
24V Out to
next board
only if
powered
from
Power
Supply &
not
Aux.24V at
panel
TX
REMOTE PSU
CHARGER FAULT
EARTH FAULT
MAINS FAIL
RX
BATT. DISCONN.
24V
9
4. CNT
NETWORK
IN
BATT.LOW
2K2
10
COMMS
24V DC
EXAMPLE
OUTPUT
8
I/O
CHANNEL
8. PR3
ADDITIONAL
I/O BOARDS
0V
7
FLT
2. RES
3.
EXAMPLE
INPUT
COMMS IN
0V
24V
0V
IN
The manufacturer reserves the right to amend specifications without prior notice
Page 33
Syncro
iO
8 Way Relay
Extender Board
Product Overview
To further enhance the versatility of the Syncro fire alarm
system, additional relay output capability can be added using
Syncro relay boards.
These boards have 8 voltage free changeover relay contacts,
each of which can be individually programmed.
Up to 32 of these boards can be connected to the dedicated
RS485 communications bus in the control panel giving the
capability of up to 256 additional relay outputs.
Features
8 volt free changeover relay contacts
(1Amp 30V DC)
Relay operated indications
Remote connection to panel via RS485
serial bus
Common footprint to other Syncro I/O
board types
All outputs programmable for cause and
effects
Can be used with other Syncro I/O
modules on the same panel
Compatible with Syncro AS panels
The relay boards may be mixed on the RS485 bus with 16
channel I/O boards, 6 way sounder boards or 4 way
conventional detection zone boards to provide a very flexible
system of I/O to satisfy any requirement.
All outputs are configurable in the same way as devices
connected to the loops and all may be acted upon by cause and
effect logic.
These boards are typically used in applications which require
more than the four standard relay outputs such as signalling to
other systems or plant control.
Standard Syncro control panels contain fixings for one sounder,
relay, conventional detection or I/O board, which can easily be
connected using four small signal wires to the power and
comms bus within the panel.
Consideration must be taken as to the loading on the main
panel.
Part No. K547
Page 34
DS33.05.2009
Technical
Product code
Supply voltage range
Quiescent current
consumption
Operating current
(all outputs on)
Output contact rating
Communications
Max. distance from panel
PCB size
Fixing centres
Cable capacity
Operating temperature
Operating humidity
SNDR.1
SNDR.2
Specifications
- K547
- 21 to 30 volts DC
- 10mA
- 250mA
-
SNDR.3
30V DC 1 Amp
RS485 two wire
1.2Km (using RS485 data cable)
190mm x 61mm
51.5mm x 180mm
2.5mm per terminal
-5°C to +50°C
To 95% (non condensing)
SNDR.4
Syncro 8 Way
Relay Board
O/P 1
FIRE
ROUTING
NC
O/P 2
NC
FLT
O/P 3
2. RES
3.
REMOTE
CONTROL
AND AUX.
INPUTS
INT
NC
O/P 4
SIL
0V
NC
O/P 5
7. PR2
NC
O/P 6
COMMS
C
NO
ADDITIONAL
I/O BOARDS
NC
AUX
24V
O/P 7
NC
O/P 8
NETWORK
OUT
CHARGER FAULT
RX
0V
24V
0V
COMMS IN
TX
REMOTE PSU
EARTH FAULT
C
NO
OUT
MAINS FAIL
C
NO
NETWORK
IN
BATT. DISCONN.
C
NO
8. PR3
BATT.LOW
C
NO
6. PR1
24V DC
C
NO
4. CNT
5.
C
NO
EXTINGUISHER
OUTPUT
Syncro
Main PCB
C
NO
FAULT
ROUTING
1.
NC
Signal to
other Systems
30V DC Max.
1 Amp Max.
0V
24V
COMMS
OUT
0V
IN
24V Out to next
board only if
powered from
Power Supply & not
Aux.24V at panel
Data Out to
other Boards
The manufacturer reserves the right to amend specifications without prior notice
Page 35
Syncro
iO
6 way Sounder
Extender Board
Product Overview
To further enhance the versatility of the Syncro fire alarm
system, additional sounder output capability can be added
using Syncro sounder boards.
These boards have 6 monitored sounder outputs, each of
which can be individually programmed.
In addition to the sounder outputs each board has two general
purpose, opto-isolated inputs and two volt-free changeover
contact outputs.
Features
6 individually fused and monitored
sounder outputs
Fault and operated indications
2 opto-isolated general purpose inputs
2 volt free contact general purpose
outputs
Remote connection to panel via RS485
serial bus
Common footprint to other Syncro I/O
board types
All outputs and inputs programmable for
cause and effects
Can be used with other Syncro I/O
modules on the same panel
Compatible with Syncro AS panels
Up to 32 of these boards can be connected to the dedicated
RS485 communications bus in the control panel giving the
capability of 192 additional sounder outputs with 64 general
purpose inputs and 64 general purpose outputs.
The sounder boards may be mixed on the RS485 bus with 16
channel I/O boards, 8 way relay boards or 4 way conventional
detection zone boards to provide a very flexible system of I/O
to satisfy any requirement.
All inputs and outputs are configurable in the same way as
devices connected to the loops and all may contribute to, or be
acted upon by cause and effect logic.
These boards are typically used in applications that require
more than the four standard sounder outputs such as
replacement of existing conventional systems.
Standard Syncro control panels contain fixings for one sounder,
relay, conventional detection or I/O board, which can easily
be connected using four small signal wires to the power and
comms bus within the panel.
Consideration must be taken as to the loading on the main
panel.
Part No. K546
Page 36
DS34.05.2009
Technical
SNDR.1
SNDR.2
SNDR.3
Specifications
- K546
- 21 to 30 volts DC
- 30mA
- 260mA
- 10k
-
3mA maximum
1 Amp maximum
30V DC 1 Amp
RS485 two wire
1.2Km (using RS485 data cable)
190mm x 74mm
51.5mm x 180mm
2.5mm per terminal
-5°C to +50°C
To 95% (non condensing)
Polarised sounders max.
1 Amp. End of line
resistor fitted
SNDR.4
10K
Product code
Supply voltage range
Quiescent current
consumption
Full alarm current
consumption
Sounder current
monitoring resistor
Current per input
Current per sounder output
Output contact rating
Communications
Max. distance from panel
PCB size
Fixing centres
Cable capacity
Operating temperature
Operating humidity
S1
FIRE
ROUTING
S2
FAULT
ROUTING
Unused outputs must
be terminated with end
of line resistor to
prevent fault indication
S3
1.
S4
FLT
2. RES
Syncro
Main PCB
3.
REMOTE
CONTROL
AND AUX.
INPUTS
INT
4. CNT
5.
SIL
0V
10K
EXTINGUISHER
OUTPUT
Syncro
Sounder
Board
6. PR1
S5
Max. contact resistance
500 Ohms
S6
I/P1
7. PR2
I/P2
8. PR3
NC
COMMS
O/P 1
ADDITIONAL
I/O BOARDS
NO
AUX
24V
NC
O/P 2
NETWORK
IN
TX
CHARGER FAULT
EARTH FAULT
MAINS FAIL
BATT. DISCONN.
RX
0V
24V
0V
COMMS IN
OUT
REMOTE PSU
BATT.LOW
C
NO
NETWORK
OUT
24V DC
C
Signal to other systems
max. voltage 30V DC
max. current 1 Amp
0V
24V Out to next board
only if powered from
Power Supply & not
Aux.24V at panel
24V
COMMS
OUT
0V
Data Out to
other Boards
IN
The manufacturer reserves the right to amend specifications without prior notice
Page 37
Syncro
iO
4 Way Conventional
Detection Zone Module
Product Overview
To further enhance the versatility of the Syncro fire alarm
system, four conventional detection circuits can be connected
with up to 30 detectors per circuit.
Conventional control panels can be replaced with this simple
module and existing conventional systems can be interfaced
directly to modern analogue addressable control systems and
networks.
A fail safe mode ensures that the detection inputs will still
operate the sounder outputs and fire contact if
communication to the Syncro panel is lost.
Features
4 monitored detection zone inputs
2 monitored sounder outputs
Volt free fire contact
Volt free fault contact
Local power supply fault input
RS485 comms connection to Syncro Fire
Alarm Panel
Individual fault and operated indications
for inputs and outputs
Directly replaces a conventional control
panel when integrating into an analogue
addressable system
Can be used with other Syncro I/O
modules on the same panel
Compatible with Syncro AS panels
Up to 32 of these boards can be connected to the dedicated
RS485 communications bus in the control panel giving the
capability of up to 128 conventional zones with 64 sounder
outputs.
The detection zone boards may be mixed on the RS485 bus
with 16 channel I/O Boards, 6 way sounder boards or 8 way
relay boards to provide a very flexible system of I/O to satisfy
any requirement.
All inputs and outputs are configurable in the same way as
devices connected to the loops and all may be acted upon by
cause and effect logic.
Standard Syncro control panels contain fixings for one (four
way) Detection Zone board, Sounder board, Relay board or I/O
board, all of which can easily be connected using four signal
wires to the power and comms bus within the panel.
Consideration must be taken as to the loading on the main
panel.
Part No. K545
Page 38
DS35.05.2009
Technical
Product code
Supply voltage range
Quiescent current
consumption
Operating current
(all outputs on)
Output contact rating
Detection zone
monitoring resistor
Sounder circuit
monitoring resistor
Communications
Max. distance from panel
PCB size
Fixing centres
Cable capacity
Operating temperature
Operating humidity
SNDR.1
SNDR.2
Specifications
- K545
- 21 to 30 volts DC
- 70mA
- 250mA
- 30V DC 1 Amp
- 6k8
- 10k
-
SNDR.3
RS485 two wire
1.2Km (using RS485 data cable)
190mm x 74mm
51.5mm x 180mm
2.5mm per terminal
-5°C to +50°C
To 95% (non condensing)
SNDR.4
FIRE
ROUTING
Syncro 4 Way
Conventional
Detection
Zone Board
FAULT
ROUTING
EXTINGUISHER
OUTPUT
CP
D
Z2
CP
D
CP
D
Z3
D
D
CP
D
Z4
CP
D
CP
D
COMMS
S1
S
S
S
AUX
24V
S2
REMOTE
CONTROL
AND AUX.
INPUTS
4. CNT
5.
SIL
0V
6. PR1
7. PR2
8. PR3
ADDITIONAL
I/O BOARDS
FIRE
C
FAULT
NC
C
CHARGER FAULT
EARTH FAULT
MAINS FAIL
RX
0V
24V
0V
COMMS IN
NO
TX
REMOTE PSU
BATT. DISCONN.
S
NO
NETWORK
OUT
BATT.LOW
S
NC
NETWORK
IN
24V DC
S
EOL
D
EOL
D
INT
EOL
Z1
3.
EOL
FLT
2. RES
EOL
1.
Syncro
Main PCB
PF
0V
OUT
IN
24V Out to next
board only if
powered from
Power Supply & not
Aux.24V at panel
0V
24V
COMMS
OUT
0V
Data Out to
other Boards
The manufacturer reserves the right to amend specifications without prior notice
Page 39
DS46.01.2009
Syncro
iO
I/O Board Enclosure
Product Overview
A range of new enclosures designed to house Syncro I/O
modules with or with a power supply. The Syncro I/O enclosure
offers the installer the flexibility to create their own customised
I/O panel. The standard Syncro I/O enclosure can hold up to 3
Syncro I/O modules or 2, if a power supply is incorporated.
Equipment
Product Code Description
Features
Matching design & colour scheme for
Kentec new style control panel range
Easy to install
Incorporates Kentec’s “Quick Fit” lid &
equipment chassis
K16001M2
K16750M2
K16250M2
K16400M2
Plug-Ins
K560
K547
K546
K545
Syncro I/O enclosure without Charger
Syncro I/O enclosure c/w 750mA Charger
Syncro I/O enclosure c/w 2.5A Charger
Syncro I/O enclosure c/w 4.0A Charger
16 Channel Input/Output Board
8 Way Relay Extender Board
6 Way Sounder Extender Board
4 Way Conventional Detection Zone Module
Front panel mounted status led indication
Space for batteries
Choice of power supplies
16 Channel
Input/Output
Board (K560)
8 Way Relay
Extender
Board (K547)
6 Way Sounder 4 Way Conventional
Extender
Detection Zone
Board (K546)
Module (K545)
Choose any combination of I/O boards
2x I/O boards with PSU
3x I/O boards without PSU
Page 40
Model No. K16001M2
DS46.03.2009
Syncro
iO
Addressable Sounder
Controller Unit
Product Overview
Syncro addressable sounder controller units enable additional,
distributed power and control for sounder circuits in situations
where there are insufficient circuits at the fire alarm control
panel or where additional power is required to power heavily
loaded sounder circuits.
Sounder control modules for any of the protocols supported
by Syncro are available in a steel enclosure designed to match
the appearance of the Syncro fire alarm control panel.
Features
All units contain mains powered battery charger/power supply,
they have space for up to 7 Ah batteries.
Two, four or six way units available
Indicators are provided for power healthy and power fault
conditions and power fault conditions are signalled to the
Syncro fire alarm control panel as a sounder fault.
Integral power supply
Apollo, Argus Vega or Hochiki protocols
available
Robust steel enclosure matches Syncro
control panel styling
Space for 7Ah batteries
Power Healthy and Power Fault indicators
Technical
Panels
Size
Finish
Colour - lid & box
Colour - labels
Mains voltage supply
-
Mains fuse
Battery charge fuse
Battery
Operating temperature
Operating humidity
Protocol
-
500mm (W) x 355mm (H) x 108mm (D)
Epoxy powder coated
Product Code Protocol Sounder PSU
Outputs
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
A1725203
V1725203
H1725203
A1725403
V1725403
H1725403
A1725603
V1725603
H1725603
110 or 230V AC 50 or 60 Hz.
(specify when ordering, default is 230V)
3A, 1¼ inch
20mm x 5mm, 500 milliamp
7Ah 12V (2 per panel)
-5°C to +50°C
To 95% (non condensing)
Apollo XP95, Argus Vega or Hochiki ESP
Apollo XP95
Argus Vega
Hochiki ESP
Apollo XP95
Argus Vega
Hochiki ESP
Apollo XP95
Argus Vega
Hochiki ESP
2
2
2
4
4
4
6
6
6
2.5A
2.5A
2.5A
4.0A
4.0A
4.0A
4.0A
4.0A
4.0A
Model No. #1725203
The manufacturer reserves the right to amend specifications without prior notice
Page 41
Conventional
Fire Detection
Control Equipment
Pages 44-57
Sigma CP
EN54 Range Conventional
Fire Alarm C/P’s
Page 44-45
Sigma CP-R
Conventional Fire Alarm
C/P Repeaters
Page 46-47
K3000 Series
Conventional Fire Alarm C/P’s
Page 48-49
K3200 Series
Conventional Fire Alarm
C/P Repeaters
Page 50-51
Sigma
Economy Conventional
Fire Alarm C/P’s
Page 52-53
Sigma Matrix
Conventional Fire Alarm
Mimic System
Page 54-55
LCMU
Line Continuity Monitoring Unit
Page 56
Relay Boards
Single (RL1) and Four (RL4) Way
Relay PCB
Page 57
Sigma
CP
BS-EN54-2
BS-EN54-4
KM 73505
Conventional Fire Alarm
Control Panels
Product Overview
The Sigma CP range consists of a series of conventional fire
alarm control panels designed in accordance with European
standards BS EN54-2 and BS EN54-4 Fire Detection and Fire
Alarm systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zone control panels. All control
panels are available in two versions:
Features
Fully compliant with & tested to BS EN54-2
and BS EN54-4
2-wire and standard versions in 2, 4 or 8
zones
Compatible for use on BS5839: Part 1: 2002
installations
2-wire repeaters and ancillary boards
Fully programmable using simple menu
options
Adjustable sounder delay time
Sounder configuration options
Zonal sounder delay detectors only
Zonal sounder delay call points only
Coincidence input selection
Short circuit fire by zone
Non latching zones
Silent zones
Zone input delay
General panel configuration
I.S Barrier selection by zone
Sigma K11 range in which detectors and call points are wired on separate circuits to sounders
(two sounder circuits are provided).
Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables.
Commonly referred to as a two-wire system.
Wiring sounders to the detection circuits eliminates the need
to install sounder circuit cables and also offers the ability to
provide zoned or two stage sounder operation. (T series only)
All control panels have an integral, mains powered battery
charger and power supply designed in accordance with the
requirements of BS EN54-4.
Note: For 2-wire T series panels, compatible detectors and call
points must be used. All sounders must be polarised.
Note: Also available is the Sigma Ancillary Board (K580) which
is compatible with all Sigma CP and CP-R panels which have
operating software version V2.0 or above.
See DS39 (pages 46-47) for more details.
Note: Also available is the Sigma Sounder Board (K461) which
is compatible with all Sigma CP and CP-R panels which have
operating software version V3.0 or above.
See DS48 (page 77) for more details.
Simple, single board construction
Installer friendly
Compatible with wide range of detection
devices
Two monitored sounder outputs
3 Amp power supply
Auxiliary power output
Part No. K580
Page 44
Part No. K461
Model No. K11080M2
DS37.07.2009
Panels
Product
Code
Description
Standby
Current
Alarm
Current
K11020M2
K11040M2
K11080M2
T11020M2
T11040M2
T11080M2
K18002
2 zone control panel
4 zone control panel
8 zone control panel
2 zone, 2 wire panel
4 zone, 2 wire panel
8 zone, 2 wire panel
Tamper resistant
Vision Window *
0.065 Amps
0.075 Amps
0.093 Amps
0.065 Amps
0.075 Amps
0.093 Amps
N/A
0.1 Amps
0.21 Amps
0.55 Amps
0.15 Amps
0.3 Amps
0.63 Amps
N/A
Specifications
* Vision Window can be easily retrofitted to any Sigma CP panel
90
385
Zone Chart
General System Status
1
2
310
3
4
5
Fire In Zone
Fire
Power Fault
Power On
Sounder Fault/
Disablemen t
Delay On
General Faul t
Test Mode On
System Fault
Genera l
Disablement
Alarm/Faul t
Warning Silenced
1
2
3
4
System Mode
Zone Fault/Test/Disablement
Fire In Zone
5
6
7
8
Zone Fault/Test/Disablement
Enable Contro l
6
7
Silence/Sound
Alar m
Alarm/Fault
Warning Silenc e
Rese t
Lamp
Tes t
Mode
(+10 )
Selec t
(+1)
Ente r
8
Fire Alarm Contro l
Model: K11080M 2
BS EN54-2 : 199 8
BS EN54-4 : 199 8
KM 73505
Technical
Size
Construction
Finish
Colour - lid & box
Colour - controls plate & labels
Supply voltage
Mains supply fuse
Power supply DC rating
Maximum battery size
Fault contact rating
Local fire contact rating
Fire contact rating
Sounder output rating
Detection zone current
Detection zone EOL resistor
Active EOL
Sounder output EOL resistor
Cable capacity
Operating temperature
Operating humidity
-
385mm(W) x 310mm(H) x 90mm(D)
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
230V AC (+10%/-15%)
1.6 Amp 250V
24V 3 Amps
7Ah 12V (2 per panel)
30V DC 1 Amp
30V DC 1 Amp
30V DC 1 Amp
0.5A per output (max 1.6A over all outputs)
1.6 milliamps
6k8 5%
K14606K (optional)
10k 5%
2.5mm² per terminal
-5°C to +50°C
<95% (non condensing)
The manufacturer reserves the right to amend specifications without prior notice
Page 45
Sigma
CP-R
& Ancillary PCB
Conventional Fire Alarm
Control Panel Repeaters
Sigma CP-R
Product Overview
The Sigma CP-R Repeater is compatible with all Sigma CP
control panels which have operating software version V2.0 or
above.
Repeaters are available with 2, 4 or 8 zones and in mains
powered (K versions) or 24V powered (E versions).
Ancillary PCB
Product Overview
The Sigma Ancillary Board is compatible with all
Sigma CP and CP-R panels which have operating
software version V2.0 or above.
The board provides common fire, common fault,
coincidence and zonal fire, volt free contacts
allowing control of sub-systems, graphical
mimics and plant, remotely from the main panel
over a two wire data bus.
Mains powered Ancillary boards require only a
two core data cable from the main control panel.
24V DC versions require an additional two cores
for power either from the main panel or from
another 24V DC source.
A mixture of Ancillary boards, Sounder boards
or Repeaters up to a maximum of 7 of each type
can be connected to a control panel and each is
allocated an address from 1 to 7 using a binary
coded DIL switch.
The total length of the data cable from the main
panel to the last repeater must not exceed 1200
metres.
Ancillary PCB
Mains powered repeaters require only a two core data cable
from the main control panel. 24V DC versions require an
additional two cores for power either from the main panel or
from another 24V DC source.
A mixture of Repeaters, Ancillary boards or Sounder Boards
up to a maximum of 7 of each type can be connected to
a control panel and each is allocated an address from 1 to
7 using a binary coded DIL switch. The total length of the
data cable from the main panel to the last repeater must not
exceed 1200 metres.
Sigma CP-R
Features
Two wire serial connection
Up to 7 panels per system
230V AC or 24V DC powered versions
Full control over main panel
Volt free fire and fault contact outputs
Note: Also available is the Sigma Sounder Board (K461) which
is compatible with all Sigma CP and CP-R panels which have
operating software version V3.0 or above.
See DS48 (page 77) for more details.
Features
Two wire serial connection
Up to 7 boards per system
230V AC or 24V DC powered versions
Open collector zonal fault outputs
Volt free fire, coincidence and common
fault contact outputs
Part No. K580
Page 46
Model No. E01080M2
DS39.04.2009
Power Connection
Zonal Volt Free Contacts
Data Connection
+ 24V
DC
NO C NC NO C NC NO C NC
COINC
FAULT
FIRE
Z8
RELAY
RELAY
RELAY
FIRE
Specifications
+ - + Z7
FIRE
Z6
FIRE
Z5
FIRE
Z4
FIRE
Z3
FIRE
Z2
FIRE
Z1
FIRE
RS485 RS485
OUT
IN
K580 Sigma CP Ancillary PCB
OK
COMMS
FUSE
FAIL
PROCESSOR
RESET
ADDRESS
Address Switch
Processor Reset Switch
Equipment
Product
Code
Description
Supply
Voltage
Standby
Current
Alarm
Current
E01020L2
E01040L2
E01080L2
K01020M2
K01040M2
K01080M2
2 zone Sigma CP-R repeater panel
4 zone Sigma CP-R repeater panel
8 zone Sigma CP-R repeater panel
2 zone Sigma CP-R repeater panel with PSU
4 zone Sigma CP-R repeater panel with PSU
8 zone Sigma CP-R repeater panel with PSU
24V DC
24V DC
24V DC
230V AC
230V AC
230V AC
0.075 Amps
0.075 Amps
0.075 Amps
0.075 Amps
0.075 Amps
0.075 Amps
0.094 Amps
0.098 Amps
0.11 Amps
0.094 Amps
0.098 Amps
0.11 Amps
385 x 310 x 60
385 x 310 x 60
385 x 310 x 60
385 x 310 x 90
385 x 310 x 90
385 x 310 x 90
K580
K02000M2
K02750M2
K18002
Stand alone ancillary board
Boxed ancillary board
Boxed ancillary board with 0.75A PSU
Tamper resistant Vision Window *
24V DC
24V DC
230V AC
N/A
0.020 Amps
0.020 Amps
0.020 Amps
N/A
0.2 Amps
0.2 Amps
0.2 Amps
N/A
385 x 310 x 90
385 x 310 x 90
Size
(mm)
* Vision Window can be easily retrofitted to any Sigma CP-R panel
Sigma CP-R
Ancillary PCB
Technical
Construction
Finish
Colour - lid & box
Colour - Controls plate &
labels
Supply voltage (K models)
Supply voltage (E models)
Mains supply fuse
Power supply DC rating
Maximum battery size
Fault contact rating
Fire contact rating
Cable capacity
Operating temperature
Operating humidity
Technical
-
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
-
230V AC (+10%/-15%)
20-30V DC
1.6A 250V
24V 1 Amps
7Ah 12V (2 per panel)
30V DC 1 Amp
30V DC 1 Amp
2.5mm² per terminal
-5°C to +50°C
<95% (non condensing)
Size (PCB only)
Construction (boxed)
Finish
Colour - lid & box
Colour - controls plate & labels
Supply voltage (K02750M2)
Supply voltage (K02000M2)
Mains supply fuse
Power supply DC rating
Maximum battery size
Standby current
Full alarm current
Fault contact rating
Fire contact rating
Coincidence contact rating
Zonal contact rating
Cable capacity
Operating temperature
Operating humidity
-
155mm(W) x 136mm(H)
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
230V AC (+10%/-15%)
20-30V DC
1.6A 250V
24V 750mA
2.6Ah 12V (2 per panel)
20mA
190mA
30V DC 1 Amp
30V DC 1 Amp
30V DC 1 Amp
30V DC 1 Amp
2.5mm² per terminal
-5°C to +50°C
<95% (non condensing)
The manufacturer reserves the right to amend specifications without prior notice
Page 47
Series
3000
Conventional Fire Alarm
Control Panels
Product Overview
The K3000 Series exceeds the requirements of BS5839: Part 4:
1988 in several areas. Inclusion of zone isolate, zonal one man
test, zonal contacts, shop unit interface and zoned or two stage
alarm outputs are all standard features.
Features
Complies with BS5839: Part 4: 1988
Can be used on pre BS5839 type
systems
12 - 48 zones as standard more available
on request
Class change input
Common fire and fault contacts
Line continuity upon detector removal
Remote signal contact and isolate
A wide range of detectors are supported by the equipment,
ensuring that the K3000 Series control panels can be used
with existing installations without the need to change the
field devices. Front panel controls and indicators are kept to a
minimum to simplify user operation and to maintain clarity of
indication. High intensity, twin bar LED indicators are used on all
front panels. All panels are supplied with suitable power supply
and generous battery space to give extended battery standby if
required.
Ample cable entries and removable chassis assist in ease of
installation. All panels are available as true flush or surface
mounting and in two tone grey or cream and brown.
Other colours are available to special order. Arrangements can
be made for special badging or special finishes such as brass or
stainless steel.
K3000 Series control panels allow continued operation of call
points and detectors upon removal of a device from the detection line. This can be achieved either by fitting an active end of
line device or by using special line clamping bases.
Shop interface input
Zonal one man test
Zonal selection for operation with
intrinsically safe barriers
Zonal volt free contacts
Zone isolate facility
Compatible with most popular detectors
Option for plug-in two stage sounder
cards
Model No. K3024005
Page 48
DS01.10.2009
Specifications
Control
Panel
Wall
Flush mount cross section
Panels
Product Zones Standby Alarm Sounder Sounder Minimum
Current Current Load per Load
Battery
Code
Circuit
total
(24h standby)
PSU
E3012003
K3016005
E3016005
K3024005
E3024005
K3032007
E3032007
K3040007
K3048009
2.5A
4.0A
2.5A
4.0A
2.5A
4.0A
2.5A
4.0A
4.0A
12
16
16
24
24
32
32
40
48
0.2A
0.22A
0.22A
0.31A
0.31A
0.38A
0.38A
0.45A
0.52A
0.34A
0.38A
0.38A
0.45A
0.45A
0.52A
0.52A
0.59A
0.66A
1.0A
1.0A
1.0A
1.0A
1.0A
1.0A
1.0A
1.0A
1.0A
1.5A
1.5A
1.0A
1.5A
1.0A
1.5A
1.0A
1.5A
1.5A
7.0Ah
7.0Ah
7.0Ah
12.0Ah
12.0Ah
12.0Ah
12.0Ah
15.0Ah
17.0Ah
Weight Size (mm)
(approx)
8.6kg
11.0kg
11.0kg
11.5kg
11.5kg
20.0kg
20.0kg
20.5kg
24.0kg
500 x 355 x 108
570 x 420 x 110
570 x 420 x 110
570 x 420 x 110
570 x 420 x 110
600 x 700 x 140
600 x 700 x 140
600 x 700 x 140
700 x 1000 x 145
Flush mounting versions are available to order. All weights quoted are less standby batteries
Technical
Construction
Finish
Standard colour
Sounder outputs
Isolatable fire contact
Auxiliary alarm contact
Fault contact
Zonal contacts
Auxiliary DC output
Detection zone
monitoring resistor
Sounder circuit
monitoring resistor
Remote control inputs
-
Mains supply
- 230V AC (+10%/-15%)
Call points
Alarm threshold
Short circuit threshold
Maximum zone
quiescent current
Active end of line
Operating temperature
Operating humidity
-
1.2mm fully welded sheet steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
2 outputs each fused at 1 amp each (0.5A E3002001)
Volt free changeover 1A at 30V DC
Volt free changeover 1A at 30V DC
Volt free changeover 1A at 30V DC
Volt free normally open 1A at 30V DC
Fused at 500mA
6k8
- 10k
- Alarm input, Silence input, Reset input
(option for pulsed alarm input [Security Alert])
(other voltages upon request)
Require 470 OHM series resistor
100 to 900 Ohms
0 to 100 Ohms
1.6mA
- K1406K (optional)
- -5°C to +40°C
- To 95% (non condensing)
The manufacturer reserves the right to amend specifications without prior notice
Page 49
Series
3200
Conventional Fire Alarm
Control Panel Repeaters
& Remote Indicators
Twin Lamp Units
Product Overview
To provide visual and audible indication of an alarm
condition in areas where a high powered sounder is
inappropriate, twin lamp and buzzer units are available
with or without a buzzer mute keyswitch.
These units are equipped with two large area, high
brightness LED’s which flash alternately accompanied by
an internal high frequency buzzer. A volume control is
provided on all units which is set upon commissioning to
suit the environment.
K3200 Repeaters
Product Overview
All units may be mounted on a double gang flush back
box or to a purpose made surface enclosure.
The K3200 series repeater panel uses a similar
layout to the main control panel and is fitted
with the same high quality indicators. In their
discrete enclosure, they are well suited to areas
where space is limited and aesthetics are an
important consideration.
Twin Lamp Units
As well as zonal fire indicators, system fault,
system healthy and buzzer muted indicators
are provided. Controls are kept to the
practical minimum of lamp test and buzzer
mute. Subsequent alarm or fault conditions
whilst the buzzer is muted will resound the
buzzer to alert personnel to changing
conditions.
Features
Zonal fire indicators
Common fault and power on indicators
Lamp test push button
Internal buzzer with mute facility
Repeat panels are available as true flush or
surface mounting and in two tone grey or
cream and brown as standard. Other colours
are available to special order. Arrangements
can be made for special
badging or special finishes such as brass or
stainless steel. Special repeater panels can be
made to order.
K3200 Repeaters
Features
Zonal fire indicators
Common fault and power on indicators
Lamp test push button
Internal buzzer with mute facility
Buzzer resound facility
Model No. K3212001
Page 50
DS02.10.2009
Technical
Construction
Finish
Colour
Voltage
Power consumption (repeater)
Power consumption (twin lamp)
Operating temperature
Operating humidity
-
1.2mm fully welded sheet steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
20V - 30V DC
20mA per zone
40mA (max. buzzer volume)
-5 to +50 deg. C
To 95% (non condensing)
Specifications
Equipment
Repeater Panels
Product Code
Zones
K3212001
K3216001
K3224001
K3232003
K3240005
K3248005
12
16
24
32
40
48
Weight
3.5kg
6.0kg
6.0kg
8.0kg
10.5kg
10.5kg
Size (mm)
365 x 290 x 88
365 x 290 x 88
365 x 290 x 88
500 x 355 x 108
570 x 420 x 110
570 x 420 x 110
Flush mounting versions are available to order, see price guide
Equipment
Remote Indicator Units
A range of remote lamp indicators are available for locating concealed
positions in floor or ceiling voids. All units mount onto standard
electrical boxes (single gang square types, BESA round types) and are
compatible with most common detectors. Indication is from 5mm
LED, operating voltage 10 - 30 V DC and maximum current 25mA.
Product Code Description (all flush)
K14000
K14010
K14020
K14030
K14050
Square detector (Fire Detector Operated)
Round detector (Fire Detector Operated)
Square addressable (Fire Detector Operated)
Round addressable (Fire Detector Operated)
Square detector (stainless steel finish)
Remote Indicator Units
Equipment
Lamp & Buzzer Units
Product Code Mute Facility Construction Size (mm)
K1441024
K1442023
K1443024
K1444023
No
No
Yes
Yes
Flush
Surface
Flush
Surface
140 x 80
152 x 92 x 38
140 x 80
152 x 92 x 38
For flush mounting use 47mm deep double gang electrical box
Twin lamp & buzzer Units
The manufacturer reserves the right to amend specifications without prior notice
Page 51
Sigma
Economy Conventional
Fire Alarm Control Panels
Product Overview
The Sigma range of Control Panels has been designed with
economy in mind and are based on well proven, established
electronic circuitry.
Many features and facilities have been incorporated as standard
to aid operation, maintenance and testing, including one man
test and zone isolation functions.
Modern state-of-the-art production techniques such as surface
mount technology components, automatic component
placement and automatic testing are used to improve reliability
and reduce overall size.
Features
1 man zone test mode
1, 2, 4 and 6 zones
2 monitored sounder outputs
Fault volt free changeover contacts
The panel enclosure is a flame retardent ABS injection moulded
cover; this permits a design of smooth flowing lines to be used
which is both modern and functional.
The integral battery charger/power supply and generous battery
space combine to make the panels compact but with the
flexibility to provide long standby operation should it be
required.
Fire volt free changeover contacts
Fire contact disable function
Head removal monitoring
Option for fire contact on evacuation
Zone disable function
Remote evacuate input intermittent or
continuous
Sounder disable function
User-friendly and simple in operation
Auxiliary power output
Compact, lightweight design
Easy to install
Easy to service and maintain
Integral charger with reverse battery
polarity protection
Space for up to 7Ah batteries
Model No. K1004000
Page 52
DS11.09.2009
Specifications
Technical
Size
Packed size
Packed weight
- 315mm(W) x 235mm(H) x 84mm(D)
- 330mm(W) x 250mm(H) x 100mm(D)
- 1-2 zone panels = 3kg
Construction
Finish
Standard colour
Chassis
Mains supply
Standby Battery
Detection line voltage
Detection line
quiescent current
Short circuit threshold
Alarm threshold
Open circuit threshold
Operating temperature
Operating humidity
Call points
Sounder circuit end of line
Zone circuit end of line
Active end of line
-
4-6 zone panels = 3.2kg
Flame retardent ABS injection moulded
Light texture
Stone grey
1mm mild steel, powder coated, off white
230V AC (+10%/-15%)
7Ah 12V (2 per panel)
21-28V DC (optional 21.5V line)
2mA max per zone
-
0 - 40 Ohms
40 - 740 Ohms
>10K Ohms
-5°C to +50°C
To 95% (non condensing)
470 Ohm or 680 Ohm series resistor
20K Ohms
6k8 Ohms
LCMU (K1406K) (optional)
Available only as surface mounting unit
Panels
Product Code
E1001000
K1001000
K1002000
K1004000
K1006000
Number of zones
Sounder outputs
Zone disable function
One man test
Fire volt free changeover contact
Remote evacuate input
Sounder disable
Fire contact disable switch
Integral charger/PSU
Auxiliary fused output 24V
Head removal monitoring
Standby current
Alarm current
Fault volt free changeover contact
Fire contact on evacuation switch
1
250mA total
N/A
N/A
N/A
N/A
N/A
N/A
750mA
N/A
1
500mA total
2
500mA total
4
500mA total
6
500mA total
1A @ 30V DC
switched -VE
1A @ 30V DC
switched -VE
1A @ 30V DC
switched -VE
1A @ 30V DC
switched -VE
1.25A
100mA
1.25A
100mA
1.25A
100mA
1.25A
100mA
50mA
82mA
N/A
N/A
56mA
136mA
1A @ 30V DC
N/A
66mA
166mA
1A @ 30V DC
76mA
176mA
1A @ 30V DC
86mA
186mA
1A @ 30V DC
= Standard equipment
= Optional equipment (using LCMU)
N/A = Not Available
The manufacturer reserves the right to amend specifications without prior notice
Page 53
Conventional Fire Alarm
Mimic System
!
EW
Matrix
N
Sigma
Product Overview
The Sigma Matrix system uses flexible, fibre optic light guides to
illuminate areas on a floor plan, laid over a high resolution grid.
This unique system dispenses completely with wiring and enables indicators to be moved, removed or added on site without
the need for any wiring.
Features
Up to 320 LED’s can be controlled
Select up to 12 printed colours
(not including background and building outline)
Available in a range of standard
enclosures to suit any application
Bespoke sized units can be made
upon request
All indicators can be configured to operate via switched positive
or negative inputs providing compatibility with a wide range of
input/output boards. Sigma Matrix can be supplied with or
without common LEDs and controls. Optional LEDs indicate
Power on, Fire and Fault and optional controls are for Buzzer
silence and Lamp test.
Housed in attractive, slimline enclosures to match Sigma fire
alarm panels and with high quality, full colour or monochrome
floor plans, Sigma Matrix provides a clear, geographical
indication of fire alarm activation enabling speedy identification
of the source of an alarm.
Choice of Red, Green or Yellow LED’s
Available with or without controls
Same look and feel as Sigma range
Sigma Matrix can easily be upgraded
on site with minimal cost and effort
EN54-4 approved PSU (optional)
View showing mimic mounted
on inner door
View showing LED grid
View showing internal layout
PSU optional
Page 54
M3 size Sigma Matrix
DS59.01.2009
Specifications
Technical
Mains supply*
Mains supply fuse*
Power supply rating*
Maximum ripple current*
Battery type* (Yuasa NP)
Battery charge voltage*
Battery charge current*
Max. current draw from batteries*
Supply voltage (24V versions)
Terminal capacity
Enclosure Size & mimic area
Construction
Finish
Colour - lid & box
Colour - controls plate & labels
Mimic
Cabinet locks
Maximum distance from
control panel
IP rating
Operating temperature
Number of indicators
(standard models)
-
230V AC +10% - 15% (100 Watts max.)
T2A L250V Replace only with similar type
4 Amps total including battery charge 28V +/ 2V
200 millivolts
Two 12 Volt sealed lead acid (7Ah maximum)
27.6VDC nominal (temperature compensated)
1.5A maximum
3 Amps. With mains power source disconnected
18 to 30V DC
0.5mm2 to 2.5mm2 solid or stranded wire
See ‘Enclosure Size Options’
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
3mm Clear Anti-Glare Acrylic
M2/M3 - standard 801 key, S3/S4 - standard KT3001 key
1km with 1.5mm2 cable
- IP30
- -5°C to +50°C
- M2 size - up to 32, M3 and S3 size - up to 64,
S4 size - up to 96
* 230 V Versions onlys
Enclosure Size Options
Max. number of
LED’s = 32
Max. number of
LED’s = 64
Will house 1 x 32 LED
driver PCB
Will house 1 x LED
driver PCB and
1 x 32 LED
extension PCB’s
Max. number of
LED’s = 64
Max. number of
LED’s = 320
Max. number of
LED’s = 96
Will house 1 x 32 LED Will house 1 x 32 LED
driver PCB and
driver PCB and
2 x 32 LED
1 x 32 LED
extension PCB’s
extension PCB’s
Will house 1 x 32 LED
driver PCB and up to
9 x 32 LED
extension PCB’s
(Red, Green or Yellow) (Red, Green or Yellow) (Red, Green or Yellow) (Red, Green or Yellow)
(Red, Green or Yellow)
Bespoke Size
S4
?
?
M3
S3
M2
303
185
385mm x 310mm
90mm Deep
400
515
400
400
303
225
500mm x 355mm
117mm Deep
385mm x 520mm
110mm Deep
500mm x 650mm
137mm Deep
Colour/Finish & Size
to suit your requirements
The manufacturer reserves the right to amend specifications without prior notice
Page 55
DS20.08.2009
LCMU
Product Overview
Line Continuity
Monitoring Unit
To use this method of monitoring, the breaking connection
of the detector base must be fitted with a diode. To ensure
correct operation over a wide supply voltage range and
with up to 20 detectors removed, a Schottky type BYV-1060
is recommended. These devices are, however, very
sensitive to electrostatic discharge and extra care should
be taken when handling or cable testing.
It is also necessary to fit a 47uF capacitor to the detection
line terminals on some of the control panels (not K3000
series or Sigma CP). Extreme care should be taken when
fitting the capacitor in the panel as they are polarity
conscious. The LCMU itself is also polarity conscious and
the polarity is indicated in the normal manner i.e. black
wire is always negative. A wrongly connected LCMU will
produce a short circuit fault condition.
Features
Easy to install
No additional wiring point
Due to the use of surface mount technology components,
the LCMU is probably the smallest device of its kind on the
market. This enables the device to be fitted either within
the last device on a zone or in the back box, eliminating the
need for an additional wiring point.
Low cost
Sub-miniature design
Environmentally sealed
Technical
Size
Finish
Colour
Normal current
Fault condition current
Max. zone cable resistance
Panel capacitor
Operating voltage
Terminal connections
Max. detectors supported
Lead colours
-
25mm x 20mm x 8mm
Conformal powder coating
Blue
5mA at 28V
750uA 50V
20 ohms
47uF 50V
15V to 30V
Bootlace ferrules
20 per zone
K1406K - pink/black
K1406C - orange/black
K1406N - red/black
Panels
Product Code Description
K1406K
K1406C
K1406N
Line Continuity Monitoring Unit 6k8
Line Continuity Monitoring Unit 8k2
Line Continuity Monitoring Unit 5k6
Not required on
K3000 series or
Sigma CP panels
DETECTOR
DETECTOR
470R
470R
CALL
POINTS
CALL
POINTS
Z
47uF
Z
CONTROL
PANEL
Page 56
LAST DEVICE
ON ZONE
LCMU
DS26.07.2009
Relay
Boards
Single (RL1) and Four (RL4)
RL1 (S375) Single Way Relay PCB
Way Relay PCB
Product Overview
This simple board contains a single 24V DC relay, which can be
used for any extra low voltage switching applications.
It has two changeover contacts, an LED indicator to show when
the coil is energised and a polarising diode to prevent damage
to the power source by reverse polarity connection.
The contacts are suitable for switching a maximum of 30V DC
and 2 Amps. Voltages or currents that exceed these values
should not be connected under any circumstances.
The current consumption of the unit when operated from a
24V supply is approximately 25mA.
The PCB has four 4mm mounting holes, which will accept
the self adhesive standoffs supplied. The use of self adhesive
standoffs should be carefully considered however due to their
tendency to become detached over a period of time and a
more permanent fixing method is recommended.
RL4 (S376) Four Way Relay PCB
RL1- Single Way Relay
PCB (S375)
Product Overview
This simple board contains four 24V DC relays, which can be
used for any extra low voltage switching applications.
Each relay has two changeover contacts, and an LED indicator
to show when the coil is energised. The coils of the relays are
commoned to the positive supply and the relays can be
operated individually by switching a negative to the numbered
coil inputs.
The contacts are suitable for switching a maximum of 30V DC
and 2 Amps. Voltages or currents that exceed these values
should not be connected under any circumstances.
RL4- Four Way Relay
PCB (S376)
The current consumption of the unit when operated from a
24V supply is approximately 25mA per relay.
The PCB has four 4mm mounting holes, which will accept
the self adhesive standoffs supplied. The use of self adhesive
standoffs should be carefully considered however due to their
tendency to become detached over a period of time and a
more permanent fixing method is recommended.
NC
Features
COIL
C
L1
L1
RL1
RL1
NO NC
CONTACT 1
C
NC
NO
CONTACT 2
COIL
C
NO NC
CONTACT 1
C
NO
CONTACT 2
24V DC operated
LED indicator shows relay operated
AL 0V
NC C NO
ALARM
INPUT
ALARM
CONTACT
S1
S2
AL 0V
NC C NO
ALARM
INPUT
ALARM
CONTACT
S1
S2
Two changeover contacts per relay
X1
LK1
L4
R4
R3
RL3
C
NO
NC
RL4
C
NO
D4
R1
R2
RL2
RL1
NC
L3
D3
C
D2
NC
NO
SERIAL NUMBER
NO
L2
L1
D1
C
RELAY 4
2 Amp 30V DC contact rating
RL4
NC
RELAY 3
Small footprint
Example sounder interface
of two K3000S fire panels
RELAY 1
Spring leaf 2.5mm capacity terminals
RELAY 2
Built in suppression diodes
Low current consumption
1 NC C NO 2 NC C NO
RELAY 1
RELAY 2
3 NC C NO 4 NC C NO
RELAY 3
RELAY 4
The manufacturer reserves the right to amend specifications without prior notice
Page 57
Extinguishant
System Control
Equipment
Pages 60-69
Sigma XT
EN12094 Extinguishant
Control Panels
Page 60-61
Sigma XT+
Multi Area Extinguishant
Control Panels
Page 62-63
Sigma XT+
Extinguishant Coincidence Unit
Page 64-65
Sigma Si
Status Units for use with
Sigma XT/XT+
Page 66-67
Syncro XT+
Multi Area Addressable
Extinguishant Control Panels
Page 68-69
Sigma
BS-EN12094-1
KM 96761
Extinguishant Control Panel
XT
Product Overview
Designed and manufactured to the highest standards in a
quality controlled environment and with European EN12094-1
approvals, the Sigma XT extinguishant releasing panel offers
outstanding value and performance for all small to medium
fixed firefighting installations.
Features
Complies with EN12094-1
Three detection zones as standard
Any single zone or any combinations of
zones can be configured to release
Configurable first stage sounder delays
Configurable detection delays
Zero time delay upon manual release
option
Compatible with I.S. barriers
Non-latching zone input option to
receive signals from other systems such
as aspirating equipment
Configurable extinguishant delays up to
60 seconds in 5 second steps
Configurable extinguishant duration up
to 5 minutes in 5 second steps
With three detection zones as standard, extinguishant release
can be configured to activate from any combination of detection
zone inputs to allow (among other combinations) any two from
three type activations such as would be required for detection in
ceiling void, room and floor void applications.
The extensive configuration options of the Sigma XT allow the
functionality of the system to be extensively modified while still
complying with the requirements of the controlling standard for
the equipment (EN12094-1).
The panel contains a large LED display to enable easy
configuration and control which also displays the time
remaining until extinguishant release for added user safety.
The countdown timer is duplicated on up to seven remote status
units to provide local indication of the extinguishant system
status.
With all of the electronics mounted on a single, easily
removable, steel plate Sigma XT panels are both robust and easy
to install.
Sigma XT is supplied in an enclosure that matches the
design and colour of the Sigma CP range.
Countdown timer shows time remaining
until release
Supports up to seven, four wire status
indicators
Built in Extract Fan control
Programmable
Functions
Access Level 2
Test Zones 1 to 3
Disable Zones 1 to 3
Disable 1st Stage Alarms
Disable Pre-activated 1st Stage Relay
Disable Pre-activated 2nd Stage Relay
Disable Extract Fan Output
Disable Manual Release Input
Disable Extinguishant Sub System
Activate Extract Fan Output
Activate Alarm Delays
Access Level 3
Page 60
Sounder Delay
Coincidence Detection
Disable Panel Features
Zone Alarm Delays (Detectors)
Zone Alarm Delay (Call Points)
Configure Zone for I.S Barrier Use
Zone Short Circuit Alarm
Zone Non Latching
Zone Inputs Delay
Extinguishant Release Time Delay
Extinguishant Release Duration Timer
Extinguishant Reset Delay Timer
Model No. K11031M2
DS40.05.2009
Technical
Mains supply
Mains supply fuse
Finish
Colour - lid & box
Colour - controls plate & labels
Power supply rating
Maximum ripple current
Battery type (Yuasa NP)
Battery charge voltage
Battery charge current
Battery fuse
Maximum current draw from batteries
Quiescent current of panel in mains fail
R0V output
Sounder outputs
Fault relay contact rating
Fire relay contact rating
Local fire relay contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Zone quiescent current
Terminal capacity
Number of detectors per zone
Number of sounders per circuit
Detection circuit end of line
Monitored input end of line
Sounder circuit end of line
Extinguishant output EOL
No. of detection circuits
No. of sounder circuits
Extinguishant release output
Extinguishant release delay
Extinguishant release duration
SIL, AL, FLT, RST inputs
Zone normal threshold
Detector alarm threshold
Call point alarm threshold
Short circuit threshold
Head removal condition
Cabling
Monitored inputs normal threshold
Monitored inputs alarm threshold
Monitored inputs Short circuit threshold
Status unit/Ancillary board connection
Status unit power output
-
230V AC +10%/-15% (100 Watts maximum)
1.6 Amp (F1.6A L250V)
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
3 Amps total including battery charge 28V +/- 2V
200 millivolts
Two 12 Volt 7Ah sealed lead acid in series
27.6VDC nominal (temperature compensated)
0.7A maximum
20mm, 3.15A glass
3 Amps
0.095A
Fused at 500mA with electronic fuse
24V Fused at 500mA with electronic fuse
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
2mA maximum
0.5mma² to 2.5mm² solid or stranded wire
Dependent on type (maximum 32)
Dependent on type (max. 0.5A per sounder circuit)
6K8 5% ½ Watt resistor
6K8 5% ½ Watt resistor
10K 5% ¼ Watt resistor
1N4004 Diode
3
2 x 1st Stage, 1 x 2nd Stage
Fused at 1 Amp
Adjustable 0 to 60 seconds (in 5 second steps)
Adjustable 60 to 300 seconds (in 5 second steps)
Switched -ve, max resistance 100 Ohms
8K ohms to 1K ohm
999 ohms to 400 ohms
399 ohms to 100 ohms
99 ohms to 0 ohms
15.5 to 17.5 volts
FP200 or equivalent
8K ohms to 1K ohm
999 ohms to 100 ohms
99 ohms to 0 ohms
Two wire RS485 connection
Fused at 500mA with electronic fuse
Specifications
R0V SIL AL FLT RST
AUX
REMOTE
DATA POWER
24V
CONTROL
STATUS UNITS
S1
S2
S
S
S
S
6K8
S
Extract Fan Power
Releasing Solenoid
Extinguishant Low
Pressure Switch
470R
Remote Hold Switch
Extinguishant Released
Pressure Switch
470R
Remote Manual
Release Switch
470R
DIODE
S
O
L
6K8
S
6K8
S
6K8
To Status
Units
6K8
Releasing
Detectors
Peripheral
Detectors
10K
6K8
Remote
Control
Inputs
E
2nd Stage
Sounders
10K
6K8
1st Stage
Sounders
10K
Remote Auto/Manual
Select Switch
385 x 310 x 90
415 x 315 x 86
470R
Surface mounting panel
Flush mounting panel
6K8
Size (mm)
Shutdown Power
K11031M2
K11031F2
Description
Stop Air Conditioning
Product
Code
470R
Panels
Auxiliary Signalling Relays
S
NC C NO NC C NO
NO C NC C NO NC C NO NC C NO
ZONE 1 ZONE 2 ZONE 3 2ND
1ST
2ND
MODE MAN. HOLD REL EXTING. LOW EXTRACT FAULT
LOCAL
FIRE
SOUNDER STAGE
STAGE SELECT RELEASE
PRESS.
PRES.
RELAY
FIRE
RELAY
SWITCH
SWITCH
Sigma XT PCB
The manufacturer reserves the right to amend specifications without prior notice
Page 61
Sigma
XT+
Multi- Area Extinguishant
Control Panels
Features
Complies with EN12094-1
Product Overview
Sigma XT+ control panels are multi-area extinguishant control
panels complying with EN12094-1.
Up to 8 zones of conventional detection with up to 4
extinguishant areas are available.
Stand alone extinguishant control units are also available with
2 monitored inputs to receive initiating signals from remote fire
detection control panels or addressable modules.
Each extinguishant area has a comprehensive set of inputs and
outputs and is configurable via a simple programming interface.
All extinguishant areas may have up to 7, serially connected
Sigma Si status indication and control units or ancillary relay
boards connected via a simple 4 core cable.
2, 4 or 8 detection zones
1 to 4 extinguishant areas
Dual extinguishant outputs for each area
(configurable as Main/Reserve)
First and second stage sounder outputs
for each area
First and second stage volt free
changeover contacts for each area
The versatility of the control panel can be enhanced further by
the fitting of up to 7 Sigma CP Ancillary boards (K580) or Sigma
CP Sounder boards (K461) to the RS485 serial bus. See data
sheet DS39 (page 46-47) and DS48 (page 76-77).
For compatible status units see Sigma Si data sheet DS41 (page
66-67).
Released volt free contact per area
Fault volt free contact per area
Programmable extinguishant delays
Programmable output duration
Extract fan control
Countdown indicator shows time until
release in seconds
Mode select and manual release controls
per area
Monitored remote manual release input
Monitored remote Hold input
Monitored remote Mode select (door
interlock) input
Monitored remote Released pressure
switch input
Monitored remote Low Pressure switch
input
Monitored Abort input
Serial connection for Sigma Si status
units and ancillary boards. (K588)
Model No. K21082M3
Page 62
Sigma XT Ancillary
Board - K588
Sigma CP Ancillary
Board - K580
Sigma CP Sounder
Board - K461
DS50.02.2009
Specifications
Panels
Product Code Zones Areas Size (mm)
K21021M3
K21041M3
K21042M3
K21081M3
K21082M3
K21083M4
K21084M4
2
4
4
8
8
8
8
1
1
2
1
2
3
4
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 700 x 145
385 x 700 x 145
Technical
Mains supply
Mains supply fuse
Finish
Colour - lid & box
Colour - controls plate & labels
Power supply rating (1 & 2 area units)
Power supply rating (3 & 4 area units)
Maximum ripple current
Battery charge voltage
Battery charge current
Battery fuse
Current draw in mains fail condition
Max. current draw from batteries
-
Sigma XT+ module Aux 24V output
Sigma CP Aux 24V output
1st and 2nd stage Sounder outputs
Fault relay contact rating
Fire relay contact rating
Local fire relay contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Zone quiescent current
Terminal capacity
Number of detectors per zone
Number of sounders per circuit
Detection circuit end of line
Monitored input end of line
Sounder circuit end of line
Extinguishant output end of line
No. of detection circuits
No. of sounder circuits
Extinguishant release output
Extinguishant release delay
Extinguishant release duration
SIL, AL, FLT, RST inputs
Zone normal threshold (Allowable EOL)
Detector alarm threshold
Call point alarm threshold
Short circuit threshold
Head removal condition
Cabling
Monitored inputs normal threshold
(Allowable EOL)
Monitored inputs alarm threshold
Monitored inputs Short circuit threshold
Status unit/Ancillary board connection
Status unit power output
-
3 Amps total including battery charge 28V +/- 2V
4 Amps including battery charge 28V +/- 2V
200 millivolts
27.6VDC nominal (temperature compensated)
0.7A maximum
20mm, 3.15A glass
54 milliamps per module
3A (K21021, K21041, K21042, K21081, K21082)
4A (K21083, K21084)
Fused at 500mA with electronic fuse - 1 per extinguishant area
Fused at 2.5A - not available to user
21 to 28V DC Fused at 1A with electronic fuse
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
0mA minimum, 2mA maximum
0.5mm2 to 2.5mm2 solid or stranded wire
Dependent on type - typically 20
Dependent on type and current consumption - typically 20+
6K8 +/- 5% ½ Watt resistor
6K8 +/- 5% ½ Watt resistor
10K +/- 5% ¼ Watt resistor
1N4004 Diode
Two to eight. 21 to 28V DC
Dependent on model 21 to 28V DC
21 to 28V DC. Fused at 1 Amp
Adjustable 0 to 60 seconds (+/- 10%)
Adjustable 60 to 300 seconds
Switched -ve, min resistance 0 ohms, max resistance 100 Ohms
10K ohm to 2K ohm
1K ohms to 390 ohms
370 ohms to 150 ohms
130 ohms to 0 ohms
15.5 to 17.5 volts
FP200 or equivalent (max capacitance 1uF max inductance 1 mH
10K ohm to 2K ohm
-
2K ohms to 150 ohms +/- 5%
140 ohms to 0 ohms +/- 5%
Two wire RS485 connection (EIA-485 specification)
21 to 28V DC. Fused at 500mA with electronic fuse
230V AC, 50Hz +10% - 15% (100 Watts maximum)
1.6 Amp ( F1.6A L250V)
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
The manufacturer reserves the right to amend specifications without prior notice
Page 63
Sigma
XT+
Extinguishant
Coincidence Unit
Product Overview
The Sigma XT+ ECD coincidence unit has two fully monitored
inputs for connection to fire detection control equipment or
addressable control modules to provide an EN12094-1
compliant extinguishant control system.
Its many programmable features and extensive range of inputs
and outputs make the Sigma XT+ ECD coincidence unit
suitable for all extinguishing applications where a fully featured
control device is required.
Features
Complies with EN12094-1
Dual extinguishant outputs
First and second stage sounder outputs
Among the many features of the Sigma XT+ ECD are serially
connected status units for reduced wiring and reduced
installation cost, dual extinguishant outputs that may be
configured for main/reserve applications and a countdown
timer which displays the time until discharge of the
extinguishant in seconds.
All units are independently configurable via a simple, code
based programming interface to suit the desired application.
First and second stage relay contacts
Main reserve facility
Serial connection to status units
Discharge countdown time indicator
Model No. K21001M2
Page 64
DS55.02.2009
Example Schematic 1
Sigma CP
Ancillary
Board (S580)
Sigma CP
Sounder
Board (S461)
24V
Power Supply
KENTEC ELECTRONICS LTD
FUSE-T2A
250V HRC
Sigma CP-R
Repeater Panel
(Up to 7)
L
E
N
LOAD
28V DC
1. MAINS FAILED
2. BATT. DISCONN.
3. BATTERY LOW
4. EARTH FAULT
5. CHARGER FAIL
6. COMMON FAULT
L1 - MAINS FAIL
L2 - BATT DISCON.
L3 - BATTERY LOW
L4 - EARTH FAULT
L5 - CHGR. FAULT
REPLACE FUSE ONLY WITH 20mm
TIME DELAY TYPE T2A250V
L2
L1
Specifications
MODEL - ENS400
INPUT VOLTAGE - 230V AC
INPUT CURRENT - 2A
FREQUENCY - 50 - 60Hz
OUTPUT VOLTAGE - 28V DC
POWER RATING - 112W
24V
BATT.
1.
2.
3.
4.
5.
6.
L1 L2
L5 L4 L3
L3
L4
L5
EN54-4 : 1998
Up to 4 Sigma XT+ coincidence units may be fitted
Sigma XT+
Coincidence
Unit
RS485
Sigma XT+
Coincidence
Unit
230V
RS485
Sigma CP
Control Panel
RS485
Up to 7
Ancillary
Boards
K588
Ancillary
Board
Up to 7
Ancillary
Boards
K588
Ancillary
Board
Up to 7
Status
Units
System
Status &
Control
Up to 7
Status
Units
System
Status &
Control
Example Schematic 2
1
Loop
Module
Syncro
Control Panel
Loop
Module
Sigma XT+
Coincidence
Unit
Sigma XT+
Coincidence
Unit
230V
RS485
RS485
Up to 7
Ancillary
Boards
K588
Ancillary
Board
Up to 7
Ancillary
Boards
K588
Ancillary
Board
Up to 7
Status
Units
System
Status &
Control
Up to 7
Status
Units
System
Status &
Control
Technical
Product Code
Finish
Colour - lid & box
Colour - controls plate
& labels
Size
Areas
Mains supply
Mains supply fuse
Power supply rating
Power supply rating
(K21083, K21084)
Maximum ripple current
Battery type (Yuasa NP)
Battery charge voltage
Battery charge current
Battery fuse
Current draw in
mains fail condition
Maximum current draw
from batteries
Aux 24V output
-
K21001M2
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
- 385mm(W) x 310mm(H) x 90mm(D)
- 1
- 230V AC, 50Hz +10% - 15%
(100 Watts max.)
- 1.6 Amp ( F1.6A L250V)
- 4 Amps total including
battery charge 28V +/- 2V
- 4 Amps including battery charge
28V +/- 2V
- 200 millivolts
- 12 Volt sealed lead acid in series
- 27.6VDC nominal
(temperature compensated)
- 0.7A maximum
20mm, 3.15A glass
- 54 milliamps
- 4 Amps
- Fused at 500mA with
electronic fuse
1st and 2nd stage
- 21 to 28V DC Fused at 1A with
Sounder outputs
electronic fuse
Fault relay contact rating - 5 to 30VDC 1A Amp
maximum for each
Fire relay contact rating - 5 to 30VDC 1A Amp
maximum for each
Local fire relay
contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Zone quiescent current
Terminal capacity
- 5 to 30VDC 1A Amp
maximum for each
- 5 to 30VDC 1A Amp
maximum for each
- 5 to 30VDC 1A Amp
maximum for each
- 5 to 30VDC 1A Amp
maximum for each
- 0mA minimum,
2mA maximum
- 0.5mm2 to 2.5mm2 solid or
stranded wire
- Dependent on type and
current consumption
- 6K8 +/- 5% ½ Watt resistor
- 10K +/- 5% ¼ Watt resistor
- 1N4004 Diode
Number of sounders
per circuit
Monitored input end of line
Sounder circuit end of line
Extinguishant output
end of line
Extinguishant release output - 21 to 28V DC. Fused at 1 Amp
Extinguishant release delay - Adjustable 0 to 60 seconds
(+/- 10%)
Extinguishant release
- Adjustable 60 to 300 seconds
duration
Monitored inputs normal
- (Allowable EOL)
threshold
10K ohm to 2K ohm
Monitored inputs alarm
- 2K ohms to 150 ohms +/- 5%
threshold
Monitored inputs Short
- 140 ohms to 0 ohms +/- 5%
circuit threshold
Status unit/Ancillary
- Two wire RS485 connection
board connection
(EIA-485 specification)
Status unit power output
- 21 to 28V DC, Fused at
500mA with electronic fuse
The manufacturer reserves the right to amend specifications without prior notice
Page 65
Sigma
Si
& Ancillary PCB
Sigma Si
Extinguishant
Status Indicators
Product Overview
The Sigma Si range of status indicators provide detailed status
information for Sigma XT/XT+ extinguishant release control
equipment.
All models provide high brightness, LED indication of Manual Only,
Automatic and Manual, Hold operated, Disabled, Imminent and
Released conditions. Models are also available with zonal fire
indicators and a common fault indicator.
Sigma Si
Features
For systems where local control of the Automatic/Manual mode and
or a Manual extinguishant release control are required, units are
available with these controls fitted.
Certified compliant with BS EN12094-1 when
used with Sigma XT control equipment
All models have monitored inputs for the remote connection of
Automatic/ Manual mode and Hold switches.
High brightness LEDs
All units contain a large, LED display which shows a countdown of
the time remaining until the extinguishant is released in seconds.
Detailed indication of the status of the
control panel
Ancillary PCB
Monitored data connection
Countdown timer shows time remaining
until release
Manual only and Automatic & Manual mode
select keyswitch option
Four wire connection (data and power)
Protected dual action manual release switch
option
Robust, high quality enclosure
Easy access to terminals
Remote Auto/Manual door interlock input
(monitored)
Internal fault diagnosis indicators
The Sigma XT Ancillary Board is compatible with all Sigma XT control
panels which have operating software version SIGXT_11A.HEX or
above.
The board provides volt free normally open contacts allowing
control of sub-systems and plant remotely from the main panel over
a two wire data bus.
Mains powered, boxed Ancillary boards require only a two core data
cable from the main control panel. 24V DC versions require an
additional two cores for power either from the main panel or from
another 24V DC source.
Option for zonal fire and common fault
indication with buzzer
Remote Hold input (monitored)
Product Overview
Up to 7 Ancillary boards can be connected to a control panel and
each is allocated an address from 1 to 7 using a binary coded DIL
switch. The total length of the data cable from the main panel to the
last repeater must not exceed 1200 metres.
A mixture of status units and Ancillary boards, up to a maximum of 7
of each type, can be connected to the serial data bus.
Weatherproof IP65 versions available
Internal buzzer
Ancillary PCB
Features
Two wire serial connection
Up to 7 per system
230V AC or 24V DC powered
versions
Volt free relay outputs for fire
and extinguishing system status
Relay operated LED indicators
Model No. K911000M8
Page 66
Model No. K911113M8
Model No. S588
Model No. K911111M8
Model No. K911100M8
Model No. K911110M8
DS41.03.2009
HOLD MODE OUT IN
RS485
24V DC
Status
PCB
6K8
6K8
470R
470R
To next Status Unit if fitted
From previous status
unit or control panel
Specifications
To next Status Unit if fitted
From previous status
unit or control panel
Manual Only
Auto/Manual
Hold Activated
Disabled
256mm
Imminent
Released
available
on 10 lamp
units only
Fire Zone 2
Fire Zone 3
170mm
Fire Zone 1
Fault
Weatherproof Version
Model No. W911113W8*
Equipment
Product Code Description
K911000M8
K911000F8
K911100M8
K911100F8
K911010M8
K911010F8
K911110M8
K911110F8
K911113M8*
K911113F8*
6 lamp status unit surface
6 lamp status unit flush
6 lamp status unit with mode select keyswitch surface
6 lamp status unit with mode select keyswitch flush
6 lamp status unit with manual release surface
6 lamp status unit with manual release flush
6 lamp status unit with mode select keyswitch and manual release surface
6 lamp status unit with mode select keyswitch and manual release flush
10 lamp status unit with mode select keyswitch and manual release surface
10 lamp status unit with mode select keyswitch and manual release flush
W911000W8
W911100W8
W911110W8
W911113W8*
IP65 - 6 lamp status unit surface
IP65 - 6 lamp status unit with mode select keyswitch surface
IP65 - 6 lamp status unit with mode select keyswitch and manual release surface
IP65 - 10 lamp status unit with mode select keyswitch and manual release surface
K588
K03000M2
K03750M2
Stand alone ancillary PCB
Boxed ancillary PCB
Boxed ancillary PCB with 0.75A PSU
* Not suitable for Sigma XT+ / Syncro XT+ or Sigma XT+ ECU products
Ancillary PCB
Sigma Si
Technical
Size (PCB only)
Size (Boxed PCB)
Construction (Boxed)
Colour - lid & box
Technical
- 155mm (W) x 136mm (H)
- 385mm (W) x 310mm (H)
x 90mm (D)
- 1.2mm mild steel
- BS 00 A 05 grey - fine
texture
Supply voltage (K03750M2) - 230V AC (+10%/-15%)
Supply voltage (K03000M2) - 20-30V DC
- 1.6A 250V
Mains supply fuse
- 24V 0.75 Amp
Power supply DC rating
- 2Ah 24V (2 per panel)
Maximum battery size
- 30V DC 1 Amp
Contact ratings
- 2.5mm² per terminal
Cable capacity
- -5°C to +50°C
Operating temperature
- <95% (non condensing)
Operating humidity
Power supply
Maximum current draw
Max. number of status units
Quiescent current
Cable capacity
Monitored inputs end
of line resistor
Monitored inputs
normal threshold
Monitored inputs
trigger threshold
Monitored inputs
Short circuit threshold
Data connection
-
21 to 30 V DC
0.07A
7
0.033A
2.5mm² per terminal
6K8 0.5W Resistor
- 8K ohm to 1K ohm
- 700 ohms to 100 ohms
- 99 ohms to 0 ohms
- Two wire RS485 connection
(max 1200 metres)
The manufacturer reserves the right to amend specifications without prior notice
Page 67
Multi-Area, Addressable
Extinguishant Control Panels
!
EW
XT+
N
Syncro
Product Overview
Syncro XT+ control panels are multi-area extinguishant control
panels complying with EN12094-1.
p to 16 zones of addressable detection over 1 or 2 loops ensure
U
every detector is able to contribute to extinguishant release. Up
to 4 extinguishant areas are available.
Stand alone extinguishant control units are also available with
2 monitored inputs to receive initiating signals from remote fire
detection control panels or addressable modules.
Features
Complies with EN12094-1
16 detection zones
Each extinguishant area has a comprehensive set of inputs and
outputs and is configurable via a simple programming interface.
All extinguishant areas may have up to 7, serially connected
Sigma Si status indication and control units or ancillary relay
boards connected via a simple 4 core cable.
For compatible status units see Sigma Si data sheet DS41 (page
66-67).
Up to 4 extinguishant areas
Dual extinguishant outputs for each area
(configurable as Main/Reserve)
First and second stage sounder outputs for each
area
First and second stage volt free changeover
contacts for each area
Released volt free contact per area
Fault volt free contact per area
Programmable extinguishant delays
Programmable output duration
Countdown indicator shows time until release
in seconds
Mode select and manual release controls per
area
Monitored remote manual release input
Monitored remote hold input
Monitored remote mode select (door interlock)
input
Monitored remote released pressure switch
input
Monitored Abort input
Serial connections for Sigma Si status units and
ancillary boards. (K588)
Model No. #32162M3
Page 68
DS58.01.2009
Specifications
Panels
Product Code Loop Areas Size (mm)
#31161M3
#32161M3
#31162M3
#32162M3
#31163M4
#32163M4
#31164M4
#32164M4
1
2
1
2
1
2
1
2
1
1
2
2
3
3
4
4
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 520 x 110
385 x 700 x 145
385 x 700 x 145
385 x 700 x 145
385 x 700 x 145
‘#’ - replace with:
‘A’ for Apollo protocol,
‘H’ for Hochiki protocol
‘V’ for Argus Vega protocol
Technical
Mains supply
Mains supply fuse
Finish
Colour - lid & box
Colour - controls plate & labels
Power supply rating (1 & 2 area units)
Power supply rating (3 & 4 area units)
Maximum ripple current
Battery charge voltage
Battery charge current
Battery fuse
Current draw in mains fail condition
Max. current draw from batteries
-
Sigma XT+ module Aux 24V output
Syncro AS Aux 24V output
1st and 2nd stage Sounder outputs
Fault relay contact rating
Fire relay contact rating
Local fire relay contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Terminal capacity
Number of sounders per circuit
Monitored input end of line
Sounder circuit end of line
Extinguishant output end of line
Number of detection loops
Number of zones
No. of sounder circuits
Extinguishant release output
Extinguishant release delay
Extinguishant release duration
SIL, AL, FLT, RST inputs
Cabling
Monitored inputs normal threshold
Monitored inputs alarm threshold
Monitored inputs Short circuit threshold
Status unit/Ancillary board connection
Status unit power output
-
230V AC, 50Hz +10% - 15% (100 Watts maximum)
1.6 Amp ( F1.6A L250V)
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
3 Amps total including battery charge 28V +/- 2V
4 Amps including battery charge 28V +/- 2V
200 millivolts
27.6VDC nominal (temperature compensated)
0.7A maximum
20mm, 3.15A glass
54 milliamps per extinguishing module
3A (#31161M3, #32161M3, #31162M3, #32162M3)
4A (#31163M4, #32163M4, #31164M4, #32164M4)
Fused at 500mA with electronic fuse - 1 per extinguishant area
Fused at 2.5A - not available to user
21 to 28V DC Fused at 1A with electronic fuse
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
5 to 30VDC 1A Amp maximum for each
0.5mm2 to 2.5mm2 solid or stranded wire
Dependent on type and current consumption - typically 20+
6K8 +/- 5% ½ Watt resistor
10K +/- 5% ¼ Watt resistor
1N4004 Diode
1 or 2
16
Dependent on model 21 to 28V DC
21 to 28V DC. Fused at 1 Amp
Adjustable 0 to 60 seconds (+/- 10%)
Adjustable 60 to 300 seconds
Switched -ve, min resistance 0 ohms, max resistance 100 Ohms
FP200 or equivalent (max capacitance 1uF max inductance 1 mH
10K ohm to 2K ohm
2K ohms to 150 ohms +/- 5%
140 ohms to 0 ohms +/- 5%
Two wire RS485 connection (EIA-485 specification)
21 to 28V DC. Fused at 500mA with electronic fuse
The manufacturer reserves the right to amend specifications without prior notice
Page 69
Miscellaneous
Items
Pages 72-81
PSU
EN54-4 Approved Fire Alarm
Power Supplies
Page 72-73
PSU
EN54-4 Approved Switched Mode
Power Supply / Charger
Page 74-75
EN54-4
Conventional Sounder
Controller Units
Page 76
Sigma Sounder
Sigma CP Conventional
Sounder Controller Units
Page 77
Sigma DocBox
Document Enclosure
Page 78
Vision Window
Tamper Resistant Vision Window
Page 79
Hydrosense
Water Detection System
Page 80-81
PSU
BS-EN54-4
KM 73505
EN54-4 Approved
Fire Alarm Power Supplies
Product Overview
Syncro Power EN54-4 compliant power supplies provide a stable
and fully regulated, true 24V output for fire alarm system
applications under all power conditions.
The unique regulation techniques ensure that even when
running on standby batteries, a stable 24V supply is available
to all parts of the system ensuring that all 24V powered devices
connected are supplied with optimum power.
The powerful onboard micocontroller ensures that all battery
types are conditioned with optimum, temperature compensated
charging algorythms to maximise battery life and maintain
batteries in top condition.
Features
2.5A and 5.25A versions
Chassis only or enclosure mounted with
battery space
110V or 230V input
Regulated, true 24V output
Intelligent battery charging and temperature
compensation
Syncro Power EN54-4 compliant power supplies can be fitted
with an optional dual fused output monitoring module to
ensure compliance with European standards when supplying
fire control panels with an external power supply.
Enclosed units are available to match both Sigma and Syncro
equipment ranges and all are finished with matching livery and
provide power on and power fault indications.
House up to 26Ah batteries
Status indicators for monitored faults
Dual output option for powering fire alarm
control panels remotely
Chassis versions have same mounting points
Fully enclosed and robust construction
Boxed Power Supply
to match Sigma CP
and Syncro AS Style
Page 72
Boxed Power Supply
to match Syncro Style
DS61.01.2009
Specifications
Panels
Product Code
K25250M3
K2525003
K25400M3
K2540003
K2540015
PSU
Batteries Size (mm)
up to 12Ah
2.5 Amp
up to 12Ah
2.5 Amp
5.25 Amp up to 17.2Ah
5.25 Amp up to 12Ah
5.25 Amp up to 26Ah
385 x 520 x 110
500 x 355 x 117
385 x 520 x 110
500 x 355 x 117
500 x 460 x 190
Technical
Mains input supply voltage
Mains supply fuse
Finish
colour - lid & box
Load output voltage
Maximum load current
– K25400 models
Maximum load current
– K25250 models
Maximum ripple
Load fuse
Maximum current draw
from batteries
Battery charge output voltage
-
Battery charge current
Deep discharge prevention
Compatible batteries
- Two stage, constant voltage. 1.25 Amps maximum
- Battery disconnects at 19V
- Yuasa – NP7-12, NP12-12, NP17-12, NP24-12
Operating temperature
Common fault output
Battery disconnected output
Battery low output
Charger fault output
Earth fault output
Mains failed output
Fault output connector
Mains connector
Load connector
Battery connector
Front panel Power On indicator
Front panel Fault indicator
Power output
-
230V AC 50/60Hz or 110V AC 50/60Hz (link selectable)
250V, 3A, SB, 5mm X 20mm
Epoxy powder coated
BS 00 A 05 grey - fine texture
19- 30V DC +/- 1%
5.25 Amps continuous with maximum battery charge output of
1.25A
- 2.5 Amps continuous with maximum battery charge output of 1.0A
- 200 milliamps
- 5 Amp, self resetting Polyfuse
- 5 Amps
- 27.4V DC nominal at 20 degrees C
(temperature compensated from -5 to 45 degrees C
Powersonic – PS-1270, PS-12120, PS-12170, PS12260
-5 to 45 degrees C
Normally energised volt free changeover relay – 30V DC 1 Amp
Open collector 50 milliamps
Open collector 50 milliamps
Open collector 50 milliamps
Open collector 50 milliamps
Open collector 50 milliamps
14 way DIL header 0.1” spacing
3 way terminal, 7.62mm spacing, 2.5mm maximum cable size
2 way terminal, 7.62mm spacing, 2.5mm maximum cable size
2 way terminal, 7.62mm spacing, 2.5mm maximum cable size
Green LED
Yellow LED
Dual 24V supply terminals with EN54-4 clause 6.4 interface
The manufacturer reserves the right to amend specifications without prior notice
Page 73
PSU
BS-EN54-4
KM 73505
EN54-4 Approved Switched
Mode Power Supply/Charger
Product Overview
The S407/S406 power supply/battery charger has been
developed using switched mode technology to produce an
efficient and lightweight power unit for a host of fire alarm
applications.
Suited to almost any application, the S407/S406 is designed
to be a universal power source which will reduce spares stock
holding and increase serviceability of systems.
S407
The comprehensive monitoring features of the S407/S406
include true battery present detection, low battery voltage
warning, battery overcharge warning and low battery shut off.
Complies with EN54-4
These features combined with the temperature compensated
charger output will increase the service life of sealed lead acid
batteries.
Features
Fully enclosed construction
Small & lightweight
True 2.5 Amp continuous output
Comprehensive fault monitoring
The S407 and S406 power supplies are available as chassis only
versions for mounting into existing enclosures of various sizes
to suit different battery capacities.
Temperature compensated charger
Wide input supply voltage
Enclosed or chassis only versions
available
Low battery shut off to prevent deep
discharge of battery
S406
Features
Complies with EN54-4
Fully enclosed construction
Small & lightweight
True 5.25 Amp continuous output
S407 - 2.5 Amp PSU
Comprehensive fault monitoring
Microprocessor controlled
Temperature compensated charger
Wide input supply voltage
Enclosed or chassis only versions
available
Low battery shut off to prevent
deep discharge of battery
S406 - 5.25 Amp PSU
Page 74
DS19.08.2009
Formula
Battery Calculation
BS 5839-1:2002
C min = 1.25 (T1 I1 + D I2 /2)
Specifications
Where:
C min = Minimum capacity of the battery when new at the
20 hour discharge rate and at 20 °C in ampere-hours;
T1
= Total battery stand by period in hours;
I1
= Total battery stand by load in amperes;
I2
= Total battery alarm load in amperes;
D
= a de-rating factor. (1.75)
S407
Technical
Construction
Finish
Colour
Size
Weight
Supply voltage
Input voltage
Output voltage
Total output current
Battery charge current
Load current
Fault outputs rating
Mains fuse
Load fuses
Mains failed warning
Battery disconnected warning
Battery low warning
Battery overcharge warning
Earth fault warning
Common fault output
Operating temperature
-
Aluminium base - sheet steel cover
Epoxy powder coated
Black
226mm x 120mm x 55mm
0.9Kg
230V AC (+10%/-15%)
110 or 230V AC
27.5V DC (temperature compensated)
3.5 Amps (continuous)
1.25 Amps max.
2.5 Amps (with flat battery)
50mA max.
3 Amp 20mm HRC
3 Amp (self resetting)
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
-5 to +50 deg. C
-
Aluminium base - sheet steel cover
Epoxy powder coated
Black
226mm x 120mm x 55mm
0.9Kg
230V AC (+10%/-15%)
110 or 230V AC
27.5V DC (temperature compensated)
5.25 Amps (continuous)
1.25 Amps max.
4.0 Amps (with flat battery)
50mA max.
3 Amp 20mm HRC
5 Amp (self resetting)
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
Switched -ve output
-5 to +50 deg. C
S406
Technical
Construction
Finish
Colour
Size
Weight
Supply voltage
Input voltage
Output voltage
Total output current
Battery charge current
Load current
Fault outputs rating
Mains fuse
Load fuses
Mains failed warning
Battery disconnected warning
Battery low warning
Battery overcharge warning
Earth fault warning
Common fault output
Operating temperature
The manufacturer reserves the right to amend specifications without prior notice
Page 75
Sounder
Controller
Conventional Sounder
Controller Units
Product Overview
Conventional Sounder controllers enable additional, distributed
power and control for sounder circuits in situations where there
are insufficient circuits at the fire alarm control panel or where
additional power is required to power heavily loaded sounder
circuits.
The Sounder Controller Unit connects to conventional sounder
circuits and any faults on its outputs are transmitted to the fire
control panel via the incoming, triggering sounder circuit thus
maintaining full fault monitoring.
Features
Two four or six way units available
Integral power supply
Robust steel enclosure
Space for 7Ah batteries
Power Healthy, Power Fault and Sounder
Fault indicators
Full fault monitoring and integrity
maintained
All units contain a mains powered battery charger/power
supply. There is space for up to 7 Ah batteries.
Indicators are provided for power healthy, power fault and
sounder fault conditions and power fault conditions are
signalled to the fire alarm control panel as a sounder fault.
Panels
Product Code Description
PSU
K1725203
K1725403
K1725603
4.0A
4.0A
4.0A
2 Way Sounder Controller Unit
4 Way Sounder Controller Unit
6 Way Sounder Controller Unit
Technical
Size (mm)
Finish
Colour - lid & box
Supply voltage
Mains fuse
Battery charge fuse
Power output
Battery
Operating temperature
Operating humidity
-
500(W) x 355(H) x 108(D)
Epoxy powder coated
BS 00 A 05 grey - fine texture
230V AC (+10%/-15%)
3A, 1¼ inch
20mm x 5mm, 500 milliamp
24V at 2.5A
7Ah
-5°C to +50°C
To 95% (non condensing)
Model No. K1725203
Page 76
DS48.03.2009
Sigma
Sounder
Sigma CP Conventional
Sounder Controller Units
Product Overview
The Sigma CP Sounder Board is compatible with all Sigma CP
control panels which have operating software version V3.0 or
above.
The board provides 8 additional sounder outputs which can be
configured as zoned, 2-stage or common alarm.
All sounder outputs are open and short circuit monitored and
any faults on the sounder outputs will be announced at the
main fire alarm panel as a sounder fault.
A class change input is provided which, when activated by a
volt free contact closing, will switch all sounder outputs on.
Features
Mains powered units require only a two core data cable from
the main control panel. 24V DC versions require an additional
two cores from another 24V DC source which is suitably rated
to supply the total sounder current. 230V versions have their
own power supply which is rated to supply the full sounder
load of 4 Amps.
Two wire serial connection
Up to 7 sounder boards per system
230V AC or 24V DC powered versions
Zoned, 2-stage or common alarm
Up to 7 Sounder boards can be connected to a control panel
and each is allocated an address from 1 to 7 using a binary
coded DIL switch. Sounder boards may be connected to the
Sigma CP serial bus in addition to Sigma CP ancillary boards
and Sigma CP-R repeater panels.
All outputs monitored for open and short
circuit faults
The total length of the data cable from the main panel to the
last repeater must not exceed 1200 metres. Once Sounder
boards have been recognised by the main panel, a fault will be
announced at the main panel if any become disconnected.
Class change input facility
Individual open and short circuit fault
indicators
Fully monitored by main control panel
Up to 8 outputs with 0.5A available from each
Can be connected to serial bus with Ancillary
boards and repeaters
Boxed units in enclosure to match Sigma CP
control panels
Technical
Size (PCB only)
Size (Boxed PCB)
- 155mm (W) x 136mm (H)
- 385mm (W) x 310mm (H) x
Construction (Boxed)
Finish
Colour - lid & box
Supply Voltage (K04400M2)
Supply Voltage (K04000M2)
Mains supply fuse
Power supply DC rating
Sounder output rating
Class change input
Cable capacity
Operating temperature
Operating humidity
-
Power fault input for monitoring remote
power supplies
90mm (D)
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
230V AC (+10%/-15%)
20-30V DC
1.6A 250V
24V 4 Amp
0.5A per output
Volt free NOC
2.5mm² per terminal
-5°C to +50°C
<95% (non condensing)
Panels
Product Code Description
PSU
K461
K04000M2
K04400M2
24V DC
24V DC
230V DC
Stand alone sounder PCB
Boxed sounder PCB
Boxed sounder PCB
with 4 Amp PSU
Model No. K04400M2
The manufacturer reserves the right to amend specifications without prior notice
Page 77
DS42.03.2009
Sigma
DocBox
Sigma Doc Box
Product Overview
Another addition to the Kentec range, the document box is
designed to complement the design & colour of the Sigma CP
range of control panels. The standard version Document Box will
hold up to 50 A4 sheets of information on the Fire Detection or
other security systems within a premises. The deep version will
hold up to 100 sheets. The “Doc Box” also doubles up as a Key
Box providing 7 easily accessible formed key hooks inside the
enclosure.
Features
Matches design & colour scheme for
standard Sigma CP/XT & Syncro AS
control panel ranges
Easy to install
Key Lockable
Designed for versatility
Choice of small or large capacity
enclosure
Technical
Part Number
Size
- K16000L2 (Standard version)
- 385mm(W) x 310mm(H) x
Part Number
Size
- K16000M2 (Deep version)
- 385mm(W) x 310mm(H) x
Construction
Finish
Colour - lid &
box
Weight
- 1.2mm mild steel
- Epoxy powder coated
- BS 00 A 05 grey - fine texture
60mm(D)
Model No. K16000L2
90mm(D)
- 3.0Kg
Internal VIew
Page 78
DS56.02.2009
Tamper Resistant
Vision Window
Retrofit Tamper Resistant
Vision Window
Product Overview
The Tamper Resistant Vision Window is perfect for public
areas where restricted access is necessary to prevent
damage and unauthorised operation of the control panel.
The cover features a fully welded steel construction and
key lockable inner door making it robust and secure.
The Vision Window is available from stock, fully assembled,
and can be fitted on site in minutes by simply taking out
the hinge pins on the existing enclosure, removing the lid
before fitting the new Vision Window cover and hinge pins.
Control panels can also be supplied pre-fitted with the
Vision Window. This applies to any M2 size Sigma CP, Sigma
CP-R, Sigma XT or Syncro AS control panels. Please contact
our sales department for prices.
Features
Technical
2 minutes to fit on site
Product code
Size
Construction
Finish
Colour - lid & box
Colour - controls
plate & labels
Weight
Kit available from stock
Colour to match standard Control Panel
ranges
Special colours available on request
Fits any M2 sized Sigma CP, Sigma CP-R,
Sigma XT or Syncro AS panel
-
K18002
385mm x 310mm x 35mm
1.2mm mild steel
Epoxy powder coated
BS 00 A 05 grey - fine texture
RAL 7047 light grey - satin
- 2.0 Kg
Attractive design
Key lockable
Take out both hinge pins & remove lid
Product code: K18002
Fit the Vision Window, then re-fit both hinge pins
The manufacturer reserves the right to amend specifications without prior notice
Page 79
HydroSense
Product Overview
Hydrosense
Water Detection System
A hydrosense Water Detection System installed in vulnerable areas
will continuously monitor the potential hazards, around the clock,
year in year out. The system has the facility for 24 hour battery
standby in the event of power failures.
Features
Auxiliary alarm contacts
Monitored alarm outputs
Open and short circuit line monitoring
Simple controls
The Hydrosense system has an attractive and unobtrusive control
panel containing the alarm circuitry and power supply. The point
detection Hydrosense probes or Hydrowire continuous cables are
connected to the control panel via a simple two core leader cable
making installation quick and inexpensive. Upon detection of a
leak, the green alarm lamp on the control panel will flash
accompanied by a warning buzzer. The alarm may be extended to
a remote location by extension sounder/indicator units.
Disconnection of Hydrosense probes or a break in the Hydrowire is
immediately indicated on the control panel by the yellow line fault
indicator. This ensures that the integrity of the system cannot be
compromised without a warning.
Hydrosense Floor Mounting Probe K2101
This adjustable height probe is simply screwed into the floor and
adjusted to give the required detection level. An LED indicator
on the top of the probe gives a clear indication of which probe
has been activated and this may be extended to a remote lamp
location (e.g. above false floor level) using a remote indicator. The
probe is connected to the control panel wiring via a flexible cable
which plugs into the probe. This plug connection is monitored by
the line fault circuit of the control panel.
Zonal repeat contacts
Easy to install
Easy to service and maintain
Bright dual LEDs
Clean low profile appearance
Diagnostic fault LEDs
Lockable enclosure
Special colours and finishes available
Hydrosense Drip Tray Mounting Probe K2102
This probe has exactly the same facilities as the floor
mounting probe but has a bracket for mounting onto the side of
an air conditioning unit drip tray. The probe is then adjusted to
give the required detection level and plugged into the detection
circuit.
Hydrowire
Available as standard 5 and 10 metre lengths, Hydrowire is a
flexible cable which will continuously monitor large areas. When
even a small amount of water comes into contact with Hydrowire
it is absorbed by capillary action thereby triggering an alarm. After
the source of the leak has been removed, Hydrowire will dry out in
around 20 minutes for use again.
Unplugging or cutting the Hydrowire will be immediately
indicated on the control panel by the line fault indicator. Longer
runs can be made by simply plugging lengths of Hydrowire
together. Special lengths can be made to order. Each zone
requires a connection box and an end of line DIN plug.
Model No. K2004001
Model No. E2002000
Model No. K2101
Page 80
DS03.13.2009
Equipment
Product Code Description
E2001000
K2002001
E2002000
K2004001
E2004000
E2006000
K2008003
K2012003
K2101
K2102
K2103
K2104
K2105
K2106
K2110
K2111
K2112
S 9615/A
F/A/1W
Single zone control panel (ABS)
2 zone control panel
(metal)
2 zone control panel
(ABS)
4 zone control panel
(metal)
4 zone control panel
(ABS)
6 zone control panel
(ABS)
8 zone control panel
(metal)
12 zone control panel
(metal)
Floor mounted probe
Drip tray probe
Remote indicator
5 metre Hydrowire
10 metre Hydrowire
Hydrowire connection box
End of line plug
Leader cable 50M
Fixing clips (100)
Protection Cage for Floor Mounted Probe
Fire-Cryer® with water leakage alarm
Weight
Specifications
3.5 kg
5.0 kg
3.5 kg
5.1 kg
3.5 kg
3.5 kg
8.4 kg
8.6 kg
-
Larger control panels are available on request
Technical
Specifications common to ABS & Metal Control Panels
- 2 outputs each rated at 500mA
Sounder outputs
Isolatable remote contact - Volt free changeover 1 Amp at 30V DC
fused at 500mA
- Volt free changeover 1 Amp at 30V DC
Auxiliary alarm contact
- 500mA each
Sounder fuses
Hydrosense Probe:
- 2 Amp
System fuse
Maximum recommended
- 230V AC
Mains input
coverage
Maximum recommended
ABS Enclosure, 1, 2, 4 & 6 Zones
detectors per zone
Maximum distance between
- 315W x 235H x 84D
Size
probes for perimeter detection
- Flame retardant ABS injection
Construction
Sensor height above finished
- 1.25 Amp
Power supply
floor
- 7.0A/h
Battery capacity
Leader cable
- 2.8A/h
24 hour standby
Guidelines
Max. battery capacity - 7.0A/h
- Light texture
Finish
- Stone grey
Standard colour
Metal Enclosure - 2, 4, 8, 12, 16 & 24 Zones
Construction
Finish
Standard colour
2 & 4 zone size
8 & 12 zone size
16 & 24 zone size
Construction
Power supply
Zone 1.2mm fully welded sheet steel
Epoxy powder coated
2 tone grey
365W x 290H x 88mmD
500W x 355H x 107mmD
570W x 420H x 110mmD
1.2mm fully welded sheet steel
1.25 Amp (2 & 4 zone)
2.5 Amp (8, 12, 16 & 24 zone)
- Volt free normally open 1 Amp at 30V DC
- 4.0A/h (2 & 4 zone)
6.0A/h (8 zone)
230V AC
7.0A/h (12 zone)
12.0A/h (16 & 24 zone)
-
Zonal repeat contacts
Max. battery capacity
Hydrowire Cable:
Maximum recommended
length per zone
Recommended pitch between
cable for area protection
Minimum bend radius
- 20sq metres per
detector
- 20
- 3 metres
- 1mm - 3mm
- 0.5mm round 3A
- 50 metres
- 2 metres
- 150mm
Hydrosense Probes
Technical
Size
Indicator
Connection
Material
-
Star Lane, Great Wakering
Essex, SS3 0PJ. England
95mm (max.) 80mm (min.)H x 45mmD x 100mmW
Green LED
4 pin din flying lead (1 metre)
Black nylon
Tel: +44 (0)1702 216999
Fax: +44 (0)1702 216699
Email: sales@vimpex.co.uk
Web: www.vimpex.co.uk
The manufacturer reserves the right to amend specifications without prior notice
Page 81
Custom
Engineered
Solutions
Pages 84-89
The Custom Specialists
Our In-house Facilities
Page 84-85
Custom Engineered Solutions
Page 86-89
The Custom Specialists
Our In-house facilities...
Overview
One of the key areas of our business is the design and manufacture of bespoke equipment. Kentec has
considerable expertise in this field with over 20 years experience, so you can be certain that all custom
engineered product will be designed and built in accordance with your exact requirements and our
strict ISO 9001 approved quality procedures. Many in-house facilities are at our disposal from the
initial design process to sheet metal fabrication to painting and silk screening to panel construction.
We have full control at every stage allowing
us to offer industry leading delivery times
and with quality you can have confidence in.
In March 2009 we opened a new facility in
Dartford which now houses the metal
fabrication, paint and print shops, and has
more than tripled our overall size.
All custom built equipment is project
managed by our engineering
department, using the latest software to
produce electrical, mechanical and
construction drawings to the customers’
specifications.
At the heart of our sheet metal
fabrication department is a state of the
art Amada break press, which was
re-installed to the new unit in March
2009.
We also have a full range of bending,
cropping, studding and welding plant
equipment allowing us the capabiltiy to
produce single items or volume product.
Page 84
The powder coating department
features a semi automatic powder
coating plant. This was installed into
the new factory in March 2009 and
has increased our output some five
fold, whilst producing a better and
more consistent finish.
Our screen printing department also
doubled in size following the opening of
our new factory. Environmentally
friendly printing products are used to
screen a wide range of substrates.
Sub assemblies are produced from our
fully automated state of the art surface
mount production line.
We employ automatic test equipment to
ensure each and every board is built to
the same high standard and is fault free.
All panels supplied by Kentec are
manufactured and assembled in house
in the U.K. Before despatch all panels
undergo a rigorous testing procedure,
they are then given a final visual
inspection.
We have a dedicated area for the
construction of bespoke equipment.
Our skilled production engineers build
each unit using detailed information
from the engineering department.
Page 85
Custom
Custom Engineered
Solutions
Geographical floor plan
with LED indications.
Facilities
Expert design advice
Mechanical engineering design
Artwork and printing design
Documentation
Electrical engineering
Electronic engineering
Sheet metal fabrication
Powder coat finishing
Metal finishing
Silk screen printing
Wire looming
Electrical safety testing
Technical support
Analogue
Addressable
fire control panel
with plant controls.
Floor standing fire
detection control panel
with geographical floor
plan & plant controls.
Page 86
DS38.03.2009
From Concept . . . .
Conceptual drawing produced
and sent to client for approval
Specifications
543.0
Firemans Override
OFF
AUTO
398.0
GENERATOR
FAULT
ON
AUTO
LWR. GRD. SMOKE
CLEAR ASSIST
OFF
SHUT
On approval, parts are
engineered & sent to
sheet metal shop for
fabrication before
going to paint shop
(choice of finishes)
SHUT
GAS VALVE
SHUT
OFF
AUTO
ON
AUTO
STAIR
PRESSURISATION
ON
AUTO
BUILDING SMOKE
CLEAR ASSIST
OPEN
OPEN
ATRIUM LOUVRE
OPEN
WARNING
240V AC
ENCLOSED WITHIN
YOUR LOGO
NOTES:
MATERIAL:
FINISH:
18SWG MILD STEEL
35.0
EPC - WHITE
SCREENING - BLUE
REV
REVISION
A
DATE
R./C. NOTE No.
FOR APPROVAL
24.1.06
B
FOR INFORMATION
26.1.06
C
FOR INFORMATION
1.2.06
500.0
97.5
90.0
90.0
90.0
30.0
130.0
PROJECT:
45.0
SPECIAL FIREMANS CONTROL PANEL
C/W VISION WINDOW COVER
FASCIA DRAWING
TRIANGLE INTERGRATED FIRE
DATE:
SCALE:
24.1.06
DWN BY:
CHK BY:
PM
NTS
W/O No.
35.0
CLIENT:
DRAWING No.
31611
D4
REV:
C
130.0
K7903-01
L
L
L
L
L
L
L
L
N
80.0
355.0
CL
CL
Detailed electrical schematic diagrams are
produced for production and record purposes
12.0
7.0
18.5


E
WELD & FULLY CLEAN CORNERS, SURFACE TO BE FLAT, SMOOTH & SQUARE BEFORE FINISHING






NOTES:
































































REV
01

UNLESS OTHERWISE STATED ALL DIMENSIONS
IN MILLIMETRES, TOLERANCES AS FOLLOWS:









SPECIAL FIREMANS CONTROL PANEL
C/W VISION WINDOW COVER
INNER LID DETAIL


PROJECT:
MATERIAL: 18SWG MILD STEEL
FINISH: EPC - WHITE


REVISION
FOR PRODUCTION
REL/C.NOTE
No.
DATE
R31611/1
1.2.06
CLIENT:
DATE:
1.2.06
x.x = +- 0.3
x.xx = +- 0.05
W/O No.
31611
TRIANGLE INTERGRATED FIRE
SCALE:
NTS
DWN BY:
PM
CHK BY:
DRAWING No.
K7903-03
REV
01










































Silk screen artworks are generated
in house for use in our printing shop





















 





















Firemans Override














OFF
AUTO
GENERATOR
FAULT
SHUT
GAS VALVE
SHUT
SHUT
OFF
ON
STAIR
PRESSURISATION
Unit is then assembled, fully tested and
dispatched to address of your choosing!
AUTO
LWR. GRD. SMOKE
CLEAR ASSIST
OFF
AUTO
ON
AUTO
ON
BUILDING SMOKE
CLEAR ASSIST
AUTO
OPEN
ATRIUM LOUVRE
OPEN
OPEN
BLUE
S.P.
TRIANGLE
CLIENT:
1.2.06
DATE:
R31611/1
R.NOTE:
Dwg. No: K7903-02
CHK. BY
PM
DWN. BY
SCALE: 1:1 REV: 01
WARNING
240V AC
ENCLOSED WITHIN
. . . . To Product
Special Firemans Control Panel
The manufacturer reserves the right to amend specifications without prior notice
Page 87
Custom
Custom Engineered
Solutions
. . . . choose your finish
. . . . choose your colour
. . . . choose your specification
Applications
Smoke Damper Control Panels
Composite Relay Units
(c/w Resettable Latching Relay &
Firemans Switch)
Sprinkler System Indicator Panels
Pump Status Indicator Panels
Firemans Control Switch Panels
Analogue/Addressable Interface
Units (with or without integral
PSU)
Mimic Repeat Indicator Panels
(perspex/metal, metal only, black
& white or multi-coloured)
Page 88
Specifications
Bespoke Fire Alarm
Control Panel
housed in a special
compact enclosure
to suit customers
building layout.
Floor standing triple width
enclosure with glazed doors.
Unit features geographical
floor plan layouts and 3rd
party voice alert system.
The manufacturer reserves the right to amend specifications without prior notice
Page 89
Enhanced Training from Kentec
Due to the continuing success of the Regional Training Seminars that
have been running for the past two years, we have now committed and
published dates for 2010. Each course is split over two days, the first
comprises of the Syncro Foundation Course and the second day will
build upon the foundation course and provide additional training and
hands-on experience of networking, expansion cards and complex
systems.
For more information please visit our web site www.kentec.co.uk and
click on the ‘Training’ tab. Alternatively please contact Roger, our
training technician on 01322 222121.
Places are limited, sign up online today!
Are you ‘In the loop’?
Kentec’s popular ‘In the loop’ e-mail bulletin has now been a regular
feature for over four years, providing articles on a variety of subjects
including news about new products, enhancements to existing
products and many other subjects relating to our products and
services along with general industry information.
If you would like to be ‘In the loop’ you or a colleague can register for
free on our web site by visiting www.kentec.co.uk
For the more technical user we also produce the technically biased ‘In
the technical loop’ e-mail bulletin, which can also be subscribed to by
visiting www.kentec.co.uk
For back issues of either publication please visit our web site.
Marine approvals for Syncro ASM
Syncro ASM analogue addressable, fire detection systems are available
from Kentec Electronics Limited, for a wide range of marine fire alarm
system applications.
Syncro ASM fire control panels can be networked to provide scalable
fire alarm systems, suitable for many classes of vessel.
For more information please visit our web site www.kentec.co.uk and
click on the ‘Marine’ tab. Alternatively please contact our sales
department on 01322 222121.
How to find us?
Train
The nearest station is Dartford which is served by trains from Charing Cross, London
Victoria. Journey time approximately 40 minutes from Central London.
From M25 Clockwise
Leave M25 at Junction1b (signed Dartford & A225).
At the roundabout, take the third exit onto the A225.
Continue straight across the next roundabout and continue to a set of traffic lights.
Turn left at lights onto Darenth Road.
Turn right onto Powder Mill Lane.
Turn left into Fawkes Avenue. We are located on the right.
From M25 Anti-Clockwise
Leave M25 at Junction 2 (signed London, Canterbury, A2 (M2) & Dartford (A225).
At the roundabout, take second exit and follow slip road towards Junction 1b,
At roundabout take first exit onto the A225.
Continue straight across the next roundabout and continue to a set of traffic lights.
Turn left at lights onto Darenth Road. Turn right onto Powder Mill Lane.
Turn left into Fawkes Avenue. We are located on the right.
Kentec Electronics Ltd
Units 25-27 Fawkes Avenue Questor
Dartford Kent DA1 1JQ England
Tel: +44 (0)1322 222121 Fax: +44 (0)1322 291794
E-mail: sales@kentec.co.uk Web: www.kentec.co.uk
Certificate No. FM 32987
BS EN ISO 9001: 2008
Certificate No. EMS 518118
BS EN ISO 14001:2004
Certificate No.360
BS EN ISO 19001:2000
KM 73505
KM 96761
By Appointment to
Her Majesty The Queen
Supplier of Fire Detection Equipment
Kentec Electronics Ltd. Dartford
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising