Smoke Vent Control Panel RZN 43xx-E Installation

Smoke Vent Control Panel RZN 43xx-E Installation
Instruction for use
Smoke Vent Control Panel RZN 43xx-E
Installation
Safety system protects human life and material assets!
A specialist company authorised by the manufacturer should carry out connection, installation and annual
service.
Green control diodes in the buttons must be alight all the time, otherwise see "Trouble shooting".
Repair power failure immediately. Emergency power supply available for 72 hours.
motherboard with rectifier card
and power supply plug-in unit
housing
instruction for use
Smoke vent control book
Geb
rauc
hsan
leitu
ng
cable ducts
transformer
cable duct
rail
keys
Fig.: RZN 43xx-E6
Introduction
D+H service and sales partners
Safety in the building not only comes from the product. Above all, safety
results from competence. All D+H service and sales partners are certified
and regularly trained specialist SHEV businesses. Working closely with
D+H Mechatronic AG as the manufacturer, they develop comprehensive
system solutions for SHEVs and natural building ventilation. With integral
customer support and continuous quality assurance in all phases of the
project: from sales advice, planning and project management through to
installation, commissioning, repair and service. The highest national and
international quality standards are therefore reliably fulfilled.
Installation and operation
The comprehensive network of D+H service and sales partners is at your
disposal to professionally install your system and commission it. Our partner
system guarantees that D+H products are installed exclusively by trained
and experienced fitters, in compliance with the technical guidelines and
specifications. Personal handover and training for users is included.
99.821.70 3.5/01/12
Maintenance and repair
Every building operator is responsible for ensuring that its safety equipment
works reliably. Regular and professional maintenance ensures that your
system is always operational. As specialist SHEV businesses, the D+H
service and sales partners are best qualified to carry out maintenance. By
taking out a maintenance contract, operators can prove at all times that they
have fulfilled their obligations.
Quality with guarantee
For all D+H SHEV systems, which have been installed by a D+H service and
sales partner and are regularly serviced, you will receive extended warranty
services. Ask your local D+H service and sales partner about this.
Always nearby
With the network of our own subsidiaries and exclusive partners, we are
represented nearly all over the world.
Are you looking for your local D+H partner?
Simply visit our website:
www.dh-partner.com
Content
Pictograph Explanation
Maintenance/ Guarantee/ Pictograph /Technical Data / Emergency Supply . . . 2
Motherboard / General Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Optional Functional Extension / Wiring plan / 230V Connection . . . . . . . . . . 4
Supply plug-in card VE 520 / VE 530 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Line plug-in card LE 513 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Group plug-in card GE 628 (-L) V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Servo plug-in card SE 622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Weather plug-in card WE 516. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Window-lock plug-in cardAE 525-AandAE 526-DG. . . . . . . . . . . . . . . . . . . 13
Trouble shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Examination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Smoke and heat vent alarm
OK
M
Vent button function “OPEN”
Vent/ smoke vent function “CLOSE”
Regulations for Hazard detection systems VDE 0833, Guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
ventilation systems, regulations from the local fire-authorities and from
energy supply company, for mains supply connection must be observed.
Fault
Battery fault
Charging voltage controller
Maintenance
Once a year by a specialist company authorised by the equipment
manufacturer.
Renew test badge.
Update logbook.
Window-lock group / fuse
Smoke-vent button / fuse
Smoke detector / fuse
The respective current D+H maintenance instructions should be followed.
A D+H authorised company has been specially trained by D+H for carrying
out this maintenance competently and will be automatically provided with
the latest maintenance instructions.
Following tests must be carried out during maintenance:
External examination and inspection of system components
Measuring of insulation resistances
Checking of all relevant power supply units.
Functional testing of connected system components.
Logging the competent execution of maintenance and identification
thereof in accordance with directions.
Ground fault
Check pins ground fault
Regulator for wind-force switchpoint
Regulator for signal storage time
Stroke-instantaneous value in per cent
Guarantee
Hysteresis
You will get 2 years guarantee for all D+H products from date of verified
handing over of the system up to maximal 3 years after date of delivery,
when mounting and starting has been carried out by a D+H authorized
distributor.
2
15
min
45
30
2
20
sec
60
40
D+H guarantee is expired, with connection of D+H components with
external systems or with mixing of D+H products with parts of other
manufacturers.
Regulator for Ventilation time
Regulator for OPEN running time
Automatic temperature control
Automatic weather control activated
24 V - Emergency Supply
Signal "rain"
Emergency power supply for 72 hours.
Use only VdS approved accumulators.
:
:
:
:
Fuse drive
Power supply
Important Regulations
RZN 4308-E
RZN 4316-E
RZN 4332-E
RZN 4364-E
Control panel O.K.
Signal "wind-force switchpoint"
2 x accumulator type 3 (12V, 7,0Ah ± 15%)
2 x accumulator type 4 (12V, 12Ah ± 15%)
2 x accumulator type 5 (12V, 18Ah ± 15%)
2 x accumulator type 6 (12V, 26Ah ± 15%)
AUTO
Weather automatic switched on
Technical Data
Type of control panel
Rated voltage
Rated power
Stand-by operating
Interfering emission
Resistance to jamming
Protection class
Temperature range
Ingress protection
Class of rating
- Monitoring
- Alarm / ventilation
Output voltage
Safe output
- running current of drives
- rated current of drives
Housing
colour of housing
Housing dimensions
2/16
RZN 43xx-E
RZN 4308-E
RZN 4316-E
230 VAC, 50Hz
230 VAC, 50Hz
240 VA
500 VA
ca. 10,4 W
ca. 11 W
DIN EN 55011; DIN EN 50081-2
DIN EN 61000-4 -2, -3, -4
I
-5 bis +40 °C
IP54
RZN 4332-E
230 VAC, 50Hz
1000 VA
ca. 16,2 W
RZN 4364-E
230 VAC, 50Hz
2000 VA
ca. 26 W
Continous duty
short-time duty
24VDC / residual ripple ≈ 48%
6,4 A
8A
sheet steel
RAL 7035; light grey
...-E6
500 x 500 x 210
...-E9
600 x 600 x 210
...-E14
600 x 600 x 210
12,8 A
16 A
...-E6
...-E9
...-E14
500 x 500 x 210
600 x 600 x 210
600 x 600 x 210
25,6 A
32 A
...-E6
...-E9
...-E14
600 x 600 x 210
600 x 600 x 210
600 x 800 x 250
51,2 A
64 A
...-E12 800 x 1000 x 300
...-E15 800 x 1000 x 300
...-E20 800 x 1000 x 300
99.821.70 3.5/01/12
Motherboard
for extension of control panel
(ribbon cable required)
optional functional extension by modules
slots E1 and E2
optional functional extension by modules
earthing
E1
8 9 10 11
E2
S
S
A + Z
N N S
- + t - L K Z
1 2 3 4 5 6 7
ERDA
S
S
A + Z
N N S
- + t - L K Z
1 2 3 4 5 6 7
1 2 3 4 5 6 7
8 9 10 11
1 2 3 4 5 6 7
8 9 10 11
1 2 3 4 5 6 7
8 9 10 11
8 9 10 11
1 2 3 4 5 6 7
8 9 10 11
1 2 3 4 5 6 7
1 2 3 4 5 6 7
VE
530
Trafo
F0,125A
Trafo
F3,15A
E3
+
F1,25A
+B
E4
Service
USB/PC
-
GK
VE
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
Bez.:
battery
connection
rectifier card GK
power supply
plug-in unit VE
fire recognition
element
(thermal maximum
detector) *
free slots for LE/ GE/ WE/ AE/ SE 622
* Monitoring the inner temperature of the controller. An emergency opening of the complete smoke and heat
ventilation system, under alarm conditions, will occur if the inner temperature exceeds 72°C, caused by the radiant
heat from a fire in the immediate vicinity of the installation location.
General plug-in
Rectifier card GK
Supply plug-in card
VE 520 / VE 530
1 x per control panel
up to an overall power of 32A
or
2 x per control panel
up to an total current of 64A
(2 motherboards).
VE
530
F0,125A
F3,15A
F1,25A
1 x per control panel
Monitoring of
- grid
- battery voltage
- battery charging voltage
- earth leakage protection.
Service
USB/PC
Stabilization GKS 567 *
GKS
567
to stabilize the output voltage when
connecting an external drive.
Output current
Output voltage
Residual ripple
NBE
566
N+
24V=
99.821.70 3.5/01/12
:
:
:
16A
24VDC ±10%
≤10%
Mains-battery-plug-in unit NBE 566
Stabilization GPS 566/32 *
to stabilize the output voltage when
connecting an external drive.
Output current
Output voltage
Residual ripple
:
:
:
32A
24VDC ±10%
≤10%
Stabilization GPS 566/64 *
to stabilize the output voltage when
connecting an external drive.
Output current
Output voltage
Residual ripple
:
:
:
64A
24VDC ±10%
≤10%
RZN 43xx-E
3/16
Optional Functional Extensions
Slot E1 / E2
AM 44-Z Alarm-cutoff module
for sirens, fire bells and flashing lights
TR 42
Cutoff relay module
for remote indication of fault or alarm
WFR 41 Weather-stepping-relay
for connecting of several D+H smoke
vent control panels on a wind/ rain
detector
Wiring plan (Paragon)
System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green / yellow)
this must not be used!
Cable and terminal boxes have to be labeled.
rain sensor
Slot LE
IM 44-E
Impulse module
Triggering of alarm and reset from BMS
or series connected smoke vent system
UM 41-Z Transmission module for RT 42-Z
Slot GE
AT 41
Drive at smoke
vent opening
SHEV control panel
4x 0,8 Ø
3x 1,5 mm²
see line lenghts and cross sections
Drive starting time-lag module
in conjunction with shading systems
to further ones
230 V, 50 Hz
Seperate electric circuit.
Mark fuses.
2x 0,8 Ø
2x 0,8 Ø
4x 0,8 Ø
external control
fire detector
FO 1362 or FT 1262
8x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
vent button
ca. 1,2 m above
upper edge
firm flooring
OK
smoke vent button
ca. 1,5 m above
upper edge
firm flooring
8x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
OK
Connection 230 V
*
*
4/16
RZN 43xx-E
RZN 4308-E = T 2 A
RZN 4316-E = T 2,5 A
RZN 4332-E = T 6,3 A
RZN 4364-E = T 10 A
Plan separate electric circuit.
Mark fuses.
Connecting cable: NYM-I 3x1.5
Connected load: RZN 4308E = 240 VA,
RZN 4316E = 500 VA,
RZN 4332E = 1 kVA,
RZN 4364E = 2 kVA.
99.821.70 3.5/01/12
Supply plug-in card VE 520 / VE 530
Supply plug-in card
VE 520 / VE 530
1 x per control panel
VE
530
F0,125A
VE 520
: Control panels up to 16 A
VE 530
: Control panels from 32 A
Functions:
F3,15A
Monitoring of
- Grid
- Battery voltage
- Battery charging voltage
- Earth leakage protection.
F1,25A
Service
USB/PC
Malfunction 1
Malfunction 2
LT Out 1
LT In 1
LT Out 2
LT In 2
Integrated Servicetimer
- Programmable interval
- 2 Malfunction outputs (e.g. for RT 45)
- 2 floating outputs for disconnecting the ventilation function
- Reset via PDA-Servicetool or BI-BT 2
1
2
3
4
5
6
Servicetimer:
An overdue maintenance of the system will be indicated by the control
panel after about ca. 14 to 16 months. If connected to "Malfunction 1" or
"Malfunction 2" the yellow LED in the RT 45 will start flashing.
A malfunction of the smoke vent system will be still indicated by the
extinction of the green LED in the RT 45.
The ventilation function OPEN can be interrupted for up to 2 groups via
the connections "LT In" and "LT Out" after the maintenance time is
expired. This function can be deactivated via the servicetool.
Attention: Reset of the service timer can be carried out by a
specialist company only, who has been authorized by the appliance
manufacturer.
X5
Vent button
LT 43 (-SD)
4
5
6
7
RM
X5 / VE
99.821.70 3.5/01/12
8
1
2
3
4
5
6
open
LT 43
–N
1
close
P
2
3
4
5
LT
RT
LE
L
open
close
close
3
P
close
alarm
2
alarm
1
control
6
control
5
-
4
line
LT In 2
3
LT In 1
2
LT Out 2
Malfunction 2
LT Out 1
Malfunction 1
1
LT In 2
5
LT Out 2
7
LT Out 1
4
LT In 1
6
Malfunction 1
1
8
RT 45
3
10kW
L
open signal (only -SD)
yellow
n.c.
-
2
n.c.
5
close
7
malfunction
4
malfunction
6
alarm
1
control
line
3
-
8
line
2
line
close
red
alarm
green
RT 45
–N
Interruption of the
vent button function
OPEN after the
servicetimer
elapsed
Smoke vent button
Malfunction 2
Connecting the
RT 45 malfunction LED
for displaying the
servicetimer
X5 / VE
6
7
MOT
GE
RZN 43xx-E
5/16
Line plug-in card LE 513
-
Detector Cables (Line):
The detector cables are monitored for short
circuit and break.
The opening device is automatically triggered
and opens up in the case of a fault, if DIP-switch
1+2 are set to ON.
Smoke vent button cable and cable from
automatic detectors:
- Weak current sheathed flexible cable YR 6 x
0.8
or
- Domestic wiring cable IY(ST)Y 4 x 2 x 0.6
line plug-in card for connecting of
maximum 14 fire detectors and 8
smoke vent buttons each
Functions:
line On/ Off
alarm/ fault
LE
513
F0,125A
F0,125A
ON
F1,25A
1
TEST
2
DIP-switch
factory setting
I
0
3
4
5
Encoding LE 513
Following functions can be encoded on the plug-in board using the DIP-switch.
DIP-switch 1 on ON =
In the case of a group fault (e.g. with broken motor line or missing end module) the control panel will be
switched to alarm i.e. the smoke vent opens.
DIP-switch 2 on ON =
In the case of a line fault (e.g. with interrupted button line or missing terminal resistor) the control panel will be
switched to alarm, i.e. the smoke vent opens.
DIP-switch 3 on ON =
Smoke detector alarm cannot be reset pressing the button in the smoke vent button once. DIP-switch 3 must be
switched to OFF if you want to carry out a remote reset of smoke detectors via the smoke vent button. Should only be
used if DIP-switch 4 and 5 = OFF.
DIP-switch 4 on ON =
Groups and lines connected in series will be released in the case of an alarm.
Important: Every previous plug-in slot for the triggering line and group must be occupied. Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
Dip-switch 5 on ON =
This line is released by a line connected in series.
Important: Every previous plug-in slot after the releasing line must be occupied! Both the lines must be
switched OFF/ON for “Smoke Detector Reset” at the control panel.
Connection RT 45 on LE 513 and connection GE 628 (-L) V2
fire
detector
smoke vent button
Vent button
operating
contact
type***
RT 45
LT 43 (-SD)
3
1
6
4
7
5
line
-
control
alarm
close
malfunction
n.c.
2x47kW
Mot. a
open
–N
P
close
OPEN signal
10kW
L
black
in
10kW
black
orange
zu
yellow
green
red
8
alarm
2
out
last
drives*
terminal module
EM 47 K
line
10kW*
1kW
alarm resistor
external
control
last
drive
Mot. b
-HS*
line
–
line
–
line
1
1
2
1
2
3
RM
VE
< optional >
RM
alarm
close
5
6
7
RT
LE
8
P
Mot. b
-HS*
first to
penultimate
drive
n.c.
close
malfunction
alarm
-
control
-
control
4
L
Mot. a
1
2
3
4
lenght of line and cross
sections, see page 9
LT
Mot.b
Malfunction 1
line
in
10kW*
X5
5
monitoring
7
Mot.a
4
open
6
close
1
OPEN signal (only -SD)
3
–N
2
LT 43
8
out
first to
penultimate
RT 45
branch
box by customer
5
6
7
MOT
GE
* For detailed information concerning the connection,
please refer to the instruction for use of respective drive.
6/16
RZN 43xx-E
99.821.70 3.5/01/12
Line plug-in card LE 513 (continuation)
Parallel connection of RT 45 on LE 513
red
1
6
4
7
5
2
8
3
1
6
4
7
5
alarm
close
malfunction
n.c.
line
line
-
RM
RT
LE
*
Terminal resistor for line monitoring:
They are secured in the control panel for transport.
Take them out and connect them in accordance with the plan.
The Terminal resistor must remain in terminal clamp L 1,2 if no fire
detector or external control is present.
**
Maximum total cut-off current
of connected drives:
RZN 4308-E =
8A
RZN 4316-E =
16A
RZN 4332-E =
32A
RZN 4364-E =
64A
No more than 10A on one group plug-in card.
malfunction
n.c.
malfunction
n.c.
Malfunction 1
RT 45
close
5
close
close
alarm
alarm
7
control
6
7
alarm
5
4
control
4
6
-
3
10kW
1
8
RT 45
n.c.
2
shunt connection
by customer
3
line
close
close
malfunction
alarm
1
line
alarm
5
close
7
control
4
control
6
–
1
line
-
3
–
2
2
10kW
8
line
first to
penultimate
smoke vent
button each
yellow
green
3
last smoke
vent button
each
yellow
green
red
8
alarm
2
control
RT 45
-
RT 45
line
Smoke vent button
2nd line
line
Smoke vent button
1st line
8
1
X5
VE
*** Fire detectors
Only D+H - approved detectors permissible.
**** Thermal fire recognition element,
optional, is required by some fire authorities.
99.821.70 3.5/01/12
RZN 43xx-E
7/16
Group plug-in card GE 628 (-L) V2
Group plug-in card GE 628 (-L) V2
- drives up to max. 10A can be connected to
a group plug-in card
- possibility of combination with further
groups
- adjustable ventilation time limitation and
OPEN-running time limitation
GE
628 V2
GE 628-L V2
for control of ventilation drives
M
F8,0A
2
High-Speed function:
All D+H drives with SHEV high-speed function
are supported. In daily ventilation operation, a
considerable noise reduction is achieved
through the reduced drive speed. In case of
SHEV the drives run - triggered through the
orange monitoring line - with a very high speed
to reach the OPEN position defined within 60
seconds at the most.
15
min
45
2
30
ON
20
sec
60
40
1
2
3
4
5
DIP-switch
factory setting
6
7
8
GE 628 V2
- for control of smoke and heat ventilation
drives in conjunction with the line plug-in
card LE 513
- Smoke and heat ventilation re-triggering
function
- group-fault display
- power failure-CLOSE function
91
0
Encoding GE 628 (-L) V2
GE 628 V2
DIP-switch 1 on ON
DIP-switch 2 on ON
GE 628-L V2
OPEN-running time limitation in ventilation operation
Only possible if DIP-switch 5 = ON (Storage operation in OPEN-direction).
Running time in OPEN-direction can be limited by using the potentiometer.
If the vent button is actuated in OPEN-direction, the drives/ NSHEVs run for
the duration of the running time.
Ventilation time limitation
Only possible if DIP-switch 4 = ON (memory mode in CLOSED-direction). Ventilation time can be
set by using a potentiometer.
The drives / NSHEVs will automatically close again, after the set time has expired.
DIP-switch 3 on ON
OPEN-retriggering
Only possible if DIP-switch 1 = ON (OPEN-running time limitation).
If DIP-switch 1 is switched to ON, the OPEN-running time limitation can be re-triggered again.
DIP-switch 4 on ON
Storage operation in CLOSED-direction
Press vent button
once briefly. > The drives / NSHEVs will close to their final position.
Tip operation in CLOSED-direction
The drives / NSHEVs will close as long as the vent button
is pressed.
DIP-switch 4 on OFF
DIP-switch 5 on ON
DIP-switch 5 on OFF
2
20
sec
60
2
40
15
min
45
30
Storage operation in OPEN-direction
Press vent button
once briefly. > The drives / NSHEVs will open to their final position.
Tip operation in OPEN-direction
The drives / NSHEVs will open as long as the vent button
is pressed.
DIP-switch 6 on ON
Group CLOSE in case of alarm
The drives/ NSHEVs will close in the case of alarm.
- no function -
DIP-switch 7 on ON
Power failure-CLOSE
Only possible if DIP-switch 4 = ON.
In the case of power failure, the drives/ NSHEVs.
will close.
- only function, if control panel
has emergency
power supply -
DIP-switch 8 on ON
Alarm re-triggering
During a period of 30 minutes, the smoke vent is triggered
at intervals of 2 minutes in accordance with VdS 2581.
- no function -
DIP-switch 9 on ON
The group plug-in card can be triggered in OPEN-direction via Az signals.
DIP-switch 10 on ON
The group plug-in card can be triggered in CLOSED-direction via Zz signals. (If for example a rain detector is connected,
the switch must be ON, otherwise no closing will take place.)
Attention:
When group-DIP-switch 8 is ON, the smoke vent is re-triggered during a period of 30 minutes at intervals of 2 minutes in accordance with VdS
2581, based on the set alarm direction (see DIP-switch 6). Therefor, the drive must be safeguarded against blockage in accordance with VdS 2580
Part 4.7. . All D+H drives meet this precondition. Otherwise DIP-switch 8 must be switched on OFF.
8/16
RZN 43xx-E
Group plug-in card GE 628 (-L) V2 (continuation)
Connection GE 628 (-L) V2
Vent button
Connection in case of line branch (GE 628 (-L) V2)
- Supply wires
Mot. a and Mot. b branch off parallel
- Monitoring is looped through
all the cables up to the group end.
drives*
LT 43 (-SD)
2x47kW
black
Mot. a
open
–N
P
close
OPEN signal
branch box
control panel
last
drive
Mot. b
-HS*
branch
box by customer
Mot. a
Mot. b
branch box
on motor
Mot. a
LT 43
P
first to
penultimate
drive
Mot. b
–N
close
open
-HS*
OPEN signal (only -SD)
1
2
3
4
LT
switch further
branchings
alike
Mot. a
Mot. b
branch box
on motor
lenght of line and cross
sections, see page 9
Connection examples (GE 628 (-L) V2)
monitoring
Mot.b
25m
Mot.a
L
branch box
Mot. b
Mot. a
monitored
7 6 5
L
black
orange
terminal module
EM 47 K
5
6
7
control
panel
MOT
M
M
M
M
M
M
M
M
3 x 2,5²
Example 1:
1 line
Simple wiring, however unfavourable for voltage drop:
All drives on one cable.
GE
* For detailed information concerning the connection,
please refer to the instruction for use of respective drive.
50m
50m
Cable for GE 628 (-L) V2
branch box
The smoke vent control panel is designed for opening smoke vent devices,
which operate by thermal lifting and through automatic fire recognition
devices (thermal detector, smoke detector). They are triggered either
automatically or manually by smoke detectors at an early stage of a fire and
remain in an opened position without further power consumption. In such a
case, the functional retention of the electrical system is only required at the
early stage of fire. Secured wiring with protection against mechanical
damage is required in accordance with DIN 18232 Part 2.7.2.4.
M
M
M
M
M
4 x 2,5²
M
M
M
3 x 2,5²
control
panel
Example 2:
2 lines
Control panel in the centre, one side wired as branch, the other one as
terminal line. 4 wires are required for each branch!
Control cable (Group):
Cable from the Smoke and heat vent control panel to connect the drive.
Drive lines have a monitoring wire in which fire recognition devices (thermal
maximal detector e.g. THE) can be looped-in:
- standard guidelines for line systems MLAR or safety line with function
retention ... E30, installed in accordance with DIN 4102*.
65m
40m
3 x 2,5²
M
M
M
M
M
M
M
M
4 x 2,5²
Cables through non-monitored areas:
An increased cable function retention time may be required when drive lines
are installed through areas of the building which are not monitored.
- standard guidelines for line systems MLAR or safety line with function
retention ... E90 installed in accordance with DIN 4102*.
Example 3:
* Please note: No type designation is given for these cables because of a
large variety on the market. Please consult your D+H distributor about
these.
2 lines on one side
Branch and terminal line in same direction.
Number of drives varies in accordance with lengths of lines. 4 wires are
required for each branch!
branch box
control
panel
200m
! The earth conductor must not be wired !
65m
65m
5 x 2,5²
branch box
total
consumption
3x 1,5 mm²
3x 2,5 mm²
*5x 2,5 mm²
**7x 2,5 mm²
1
2
3
4
5
6
120 60 40 30 24 20
200 100 65 50 40 33
400 200 130 100 80 65
600 300 200 150 120 100
7
17
28
56
85
8
15
25
50
75
9
13
22
44
67
cross section (mm²) = simple cable length (m) x total current
80
10
12
20
40
60
A
m
m
m
m
M
M
M
M
4 x 2,5²
Example 4:
M
M
M
M
4 x 2,5²
control
panel
3 lines
Three cable runs are provided because of the very long distances:
2 cable runs with 3 drives each over 65 m line as branch and 1 cable run with
2 drives over 200 m line. 4 wires are required for each branch.
* Connect in parallel 2 wires for each drive line.
** Connect in parallel 3 wires for each drive line.
RZN 43xx-E
9/16
Servo plug-in card SE 622
The servo plug-in unit SE 622 is used as interface
module between Building Management System
(BMS) or Central air conditioning plant (ZLT) and
D+H Smoke extraction and vent system RZN
43xx-E. The unit is to convert an analogue preset
value from the BMS into a drive stroke between 0100% in conjunction with D+H drive with option
"-SGI". Opening width can be steplessly
controlled, depending on the BMS input value.
For the function of the SE 622, two wires are
additionally required to the drive with position
indicator for actual value feedback.
622
Cable connection BMS - servo plug-in unit:
- provide 2 wires Ø 0,8 mm per servo plug-in
unit.
- one group plug-in unit is required per servo
plug-in unit.
- all connected drives must have the same
stroke.
- Safe closing of all drives when the setpoint
value from the BMS < 5 %.
Technical Data:
System requirements : RZN 43xx-E /
GVL 83xx-E
in conjunction with
D+H drive with
option "-SGI"
or ZA...-SG
Input (BMS)
: selectable 0 -10V
or
0 - 20 mA
or
4 - 20 mA
Input impedance
: voltage = 50 kΩ
current = 50 Ω
Hysteresis
: adjustable 2-10%
Output
:- 0 or 24VDC, only in
conjunction with
GE 628 (-L) V2
- 0-10 V current position
- max. 5 SE 622 per
control panel
Functional description
OPEN direction, after the power failure has been
resolved.
Please note: The drive is controlled
automatically, so there is a potential source of
danger of pinch or shear points in the area of the
drive. With the factory-setting “OFF“, the drive
must run to position „CLOSED“ after a power
failure, via a vent button with visual contact to the
drive. For this, the automatic operation of the
servo plug-in unit SE 622 must be switched OFF
beforehand.
10
3
11
4
5
6
7
-N
D+H Drives with the option "-SGI" are
equipped with a digital pulse generator. The
servo plug-in unit must know the total pulse
number of the drive so that the setpoint value
from the BMS can be equally distributed over the
opening width. For this purpose, there is an
operating mode “Measure opening width“.
The clamps 8 + 9 (-N + Auto I/O) must be bridged
on the plug-in slot of the servo plug-in unit for the
activation of this operating mode.
Auto I/O
Function:
Triggering is effected as analogue setpoint value
via a 2-wire circuit. Either current-controlled with
values 0 - 20 mA, 4 - 20 mA or voltage-controlled
with values 0 - 10V. This corresponds to an
opening width of 0 - 100%. BMS input is
electrically isolated from the D+H-system
voltage.
The servo plug-in unit compares the setpoint
value from BMS with the actual value of the drive
and operates the drive to the desired position,
using the group plug-in unit. The servo function
can be switched off at the plug-in unit or by
remote control. Then the drive group can be
manually opened or closed by built-in vent
buttons or external vent buttons LT. The actual
value can be checked on a digital display on the
plug-in unit. The feedback to the BMS is provided
as analogue signal with values 0 - 10 V.
The servo function is overridden in the case of an
alarm from the Smoke and heat vent system. The
function “Master CLOSE“, e.g. in the case of rain
or a timer, has a higher priority than the servo
function and can be activated by DIP-switch (5).
The drives are automatically closed in the case of
wire break or short circuit on the setpoint value
wire.
Power failure-synchronisation
After a power failure with the DIP switch No. 6
switched to ON, the drive will go to its position
CLOSED in order to be able to open again up to
the given value (e.g. 50% from the BMS) in the
8
9
SE 622
This operating mode is activated with reset button
(S4). The button (S4) must be activated for at
least for 7 seconds.
0
min. 7 sec.
Please note: In this mode, the drive will run over
the entire stroke length in the OPEN and in the
CLOSE direction. A stop is not possible at this
time.
The measured stroke will be saved in the SE 622.
The drives of type ZA...-SG are equipped with
an analogue position indicator. The servo
plug-in unit compares the set value of BMS
with the actual value of the drive, and directs
the drive to the desired position using the
group plug-in unit.
Attention! The SE 622 is not compatible with the
SE 621! (Observe connection diagram!)
RZN 43xx-E / GVL 83xx-E
Encoding SE 622
Attention!
Encode only, if unit is not plugged-in.
S2
Factory settings
(0 - 10 V)
ON
S2
1
2
3
4
S6
5
6
7
8
1
2
3
4
5
6
7
8
5
6
7
8
OFF ON
OFF
Input 0-20 mA
ON OFF
OFF
Input 4-20 mA
ON OFF
ON
Drive with "-SGI"
OFF
ZA...-SG
ON
Master CLOSE funct.
Power failure sync.
cti
4
Input 0-10 V
fun
3
no
SGI
S6
2
on
ON
SG
1
SGI
SG
ON
ON
S4
10/16 RZN 43xx-E
99.821.70 3.5/01/12
Servo plug-in card SE 622 (continuation)
Connection SE 622
black
black
0 - 10 V
0 - 20 mA
4 - 20 mA
orange
0 - 10 V
terminal module
EM 47 K
branch box
by customer
2x47kW
BMS
drive with -SGI
or ZA-SG
Mot.a
Mot.b
-HS
Mot.b
-SG(I)
monitoring
Mot.b
2
Mot.a
1
Mot.a
11
monitoring
10
close
9
open
-N
8
open signal
7
-SG(I)
6
Auto I/O
5
+SG(I)
4
-N
3
-BMS (in)
2
IN+N
1
open
7
+BMS (in)
6
-BMS (out)
+BMS (out)
5
close
Zz
4
SA1
3
K
2
SSt
1
-
-N
+N
+SG(I)
+SG(I)
-SG(I)
3
4
5
6
7
LT
E 1/2
SE 622
SGI
SG
0 - 10 V
MOT
GE 628 (-L) V2
RZN 43xx-E / GVL 83xx-E
Optional with manual control
black
black
orange
BMS
0 - 10 V
2x47kW
terminal module
EM 47 K
branch box
by customer
drive with -SGI
or ZA-SG
Mot.a
Mot.b
-HS
0 - 10 V
0 - 20 mA
4 - 20 mA
SGI
SG
0 - 10 V
Mot.b
Mot.a
-SG(I)
monitoring
+SG(I)
+SG(I)
-SG(I)
LT43U-W
open
monitoring
Mot.a
Mot.b
8
close
7
-N
6
open signal
5
-SG(I)
4
Auto I/O
3
+SG(I)
2
-N
1
-BMS (in)
close
7
IN+N
-BMS (out)
6
open
+BMS (out)
5
+BMS (in)
Zz
4
SA1
3
K
2
SSt
1
-
-N
+N
P
9
10
11
1
2
3
4
5
6
7
LT
E 1/2
SE 622
S
P
MOT
GE 628 (-L) V2
RZN 43xx-E / GVL 83xx-E
99.821.70 3.5/01/12
RZN 43xx-E
11/16
Weather plug-in card WE 516
516
Encoding WE 516
You can select an infinitely variable wind-force setting between 2 and 8 on
the Beaufort scale using the regulator on the plug-in unit.
As soon as the
wind force reaches the set value (time lag of a few seconds), the signal is
displayed on the plug-in card and, if available, on the control panel.
If the automatic weather control is ON, the system closes automatically. This
is given priority, even over an attempted opening by temperature control.
The wind signal remains active for an adjustable length of time to prevent
continuous actuator operation during gusty wind conditions. The regulator
on the plug-in unit
can be used to select the infinitely adjustable signal
storage time between 1 and 15 minutes.
- weather plug-in card for
- wind-/ rain transmitter
- central vent button
- temperature control
- Functions:
- weather automatic On/ Off
- operational control central
Open/ Close
- wind force sensitivity adjustable
- signal retention time adjustable
- wind/ rain indication Closed
Connection WE 516
WRG 82
P3
P4
S 1/2
S 1/1
W
3
5
7
6
8
wind
+
4
230VAC
9
wind
2
rain
1
–
R
6
7
3
5
ITR 79
4
2
1
LT 43-W
8
9
10
ZMP2
7
11
3
5
-
1
close
P
–N
–N
6
ZMP1
open
close
ZZ2
5
ZZ1
4
–T
wind
3
–N
rain
2
AZ
+
1
S
open
RTR 230 *
P
potential free
wind/rain indication to
further control panels
max. 60V / 1A
WE 516
Function WE 516
Automatic rain control:
If the automatic weather control is on, the system will close automatically when it starts to rain. A signal, if available, will be indicated on module/ plug-in unit
and on the control panel.
To test, place a moist finger on the surface. Clean rain detector electrodes and insulator with mild soap water in the case of dirt accumulation and rinse off
thoroughly.
Automatic temperature control:
Ventilation control is carried out by a room temperature controller, if available, and if the Automatic temperature control is switched on and if no wind / or rain
signal is indicated.
If a wind / or rain signal is present, this has priority and it will close the system.
Manual Control:
The system fully opens or closes fully by pressing the
or
button once briefly .
Pressing both buttons at the same time or pressing the “Stop” button on the operator panel stops the system at any intermediate position.
Manual control is only enabled if no wind, rain or temperature signal is being processed or if the automatic control has been deactivated.
12/16 RZN 43xx-E
99.821.70 3.5/01/12
Window-lock plug-in card AE 525-A
Tripping devices:
- window-lock plug-in card for triggering of
max. 30 window-lock units of type ABF 12
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
AE
525-A
Releases
cable 4 x 0,6
cable 4 x 1,5²
cable 4 x 2,5²
F0,125A
1
2
4
8 16 24 30
100
50 25
/
/
/
/ m
600 300 150 75 30 /
/ m
1000 500 250 125 60 45 30 m
F1,25A
cross section (mm²) = simple cable lenght (m) x no. of releases
400
F6,3A
TEST
I
0
fire
detector
Smoke vent
button
type*
RT 45
-
10kW*
last or
single
+
4
line
line
3
10kW*
1
6
4
+alarm
in
closed
2
+control
out
8
in
2
3
1
6
4
2
Function of DIP- switches:
S1-1 on ON
failure = alarm
S1-2
-no function-
1
2
RT 45
first or
penultimate
1
ABF 12
5
-
8
M
branch
box
+
out
DIP-switch
factory setting
1
OK
2
ON
Tripping devices
insert
bridge!
4
M
ABF 12
5
YR 0,8
8
9
A-
11
monitored
10
according to D+H table
for layout of cables
A+
4
StL
–
3
close
line
2
YR 0,8
+alarm
–
1
+control
line
10kW*
5
6
7
* fire detector
Only D+H approved
detector permissible
AE 525-A
RZN 43xx-E
Window-lock plug-in card AE 526-DG
Pressure gas generators:
- window-lock plug-in card for triggering of
max. 8 pressure-gas generators
- release via smoke vent buttons and/ or fire
detectors
- LE 513 is not required
AE
526-DG
Releases
cable 2 x 0,8 (2 x 2 x 0,6)
cable 2 x 1,5²
cable 2 x 2,5²
F0.125A
F0.125A
1
2
4
6
150 130 90 50
450 400 270 140
750 650 450 240
8
10 m
20 m
35 m
F1.25A
F6.3A
TEST
fire
detector
smoke vent
button
type*
RT 45
1
10kW*
last or
single
OK
2
DIP-switch
factory setting
out
in
out
8
in
2
3
6
4
1
6
4
Function of DIP- switches:
S1-1 on ON
failure = alarm
S1-2
-no function-
branch
box
RT 45
10kW*
1
close
line
3
+alarm
8
line
DG
2
+control
first or
penultimate
ON
pressure gas generator
(max. 8 pce.)
DG
according to
D+H table for
layout of cables
10kW*
monitored
10
+DG
4
StL
–
3
n.c.
line
2
+alarm
–
1
+control
line
YR 0,8
11
8
9
5
6
-DG
YR 0,8
7
AE 526-DG
RZN 43xx-E
99.821.70 3.5/01/12
RZN 43xx-E
13/16
Trouble shooting
Please check following points, if the smoke vent system fails to function satisfactorily or the green control LED in the button fails to lighten. Diagnosis must be
carried out in following order: 1st supply plug-in card VE, 2nd line plug-in card LE, 3rd group plug-in card GE, 4th window lock plug-in card AE, 5th smoke
detector and external control. Detected faults must be eliminated at once before the diagnosis is continued!
Symptoms
Causes
Remedy
Earth fault.
Eliminate earth fault.
Supply plug-in card VE
LED diode
lightens.
To test the function of the earth fault checkup, the diagnosis pins on the VE must be bridgeover.
If the LED does not light, it might be necessary to check the grounding and connect it correctly.
lightens.
LED diode
LED diode
fails to lighten.
Malfunction in accumulator.
Check accumulator, connection and fuse.
No 230V power supply available.
Call in-house electrician immediately for eliminating
power failure.
Line plug-in card LE
LED diode
lightens.
Line is disconnected.
Connect line.
LED diode
lightens.
Malfunction in smoke detector or
smoke vent button line.
For exact diagnosis proceed as follows.
1. Bridge diagnostic pin
against middle pin on line
plug-in card.
LED diode
LED diode
lightens.
Malfunction in smoke detector line.
2. Bridge diagnostic pin
against middle pin on line
plug-in card.
fails to lighten.
LED diode
lightens.
Check fuse, connections, cables, terminal resistor,
clamps, smoke detectors and external control.
Malfunction in smoke vent button line.
Check fuses, connections, cables, terminal resistors,
terminals and smoke vent buttons.
Malfunction in group.
Check fuses, connections, cables, and terminal resistor
on drive.
Malfunction in group.
Check terminal resistor or terminal module between
terminal 5 and 7.
Malfunction in group.
Check terminal resistor or terminal module between
terminal 5 and 6.
Group plug-in card GE
LED diode
lightens.
Pilot light OK extinguishes during closing
operation of drive, red LED diode
lightens, flap can't be closed.
Pilot light OK extinguishes during opening
operation of drive after approx. 20 seconds,
red LED diode
lightens.
Window-lock plug-in card AE
LED diode
lightens.
Malfunction in plug-in card.
For diagnosis proceed as follows.
1. Bridge diagnostic pin
against middle pin
on plug-in card
LED diode
LED diode
lightens.
Check fuses, connections, cables, terminal resistor,
terminals, smoke detectors and external control.
2. Bridge diagnostic pin
against middle pin
on plug-in card.
fails to lighten.
lightens.
Malfunction in smoke vent button line RT.
fails to lighten.
Malfunction in line to magnetic valve.
LED diode
LED diode
Malfunction in smoke detector line RM.
Check fuses, connections, cables, terminal resistor,
terminals and smoke vent buttons.
Check fuse, terminals and loop resistance.
Smoke detector
Detector cannot be reset, though
there is no smoke existing.
Detector is dirty or faulty.
Detector fails to respond, when
checked with smoke.
Defector is faulty or wrong type.
Exchange detector.
Exchange detector.
External control
Smoke vent is opens without external alarm;
smoke vent can be reset again.
External system gives possibly only short
contact by malfunction or has given alarm or
false alarm and has been unknown reset
again.
In case of repetition, disconnect contact.
Search for fault in external system.
Smoke vent opens without external alarm.
Smoke vent cannot be reset again.
Ensure, that contact in external system is
opened. If external alarm is not resettable by
malfunction, search there for malfunction.
Disconnect temporary perhaps, so that the
smoke vent remains operative.
Smoke vent is not opening, though external
system gives alarm.
Main contact is not closing
14/16 RZN 43xx-E
Search for interruption; check whether
contact in external system is really closing.
99.821.70 3.5/01/12
Examination
Every six months and after maintenance carried out by a specialist
engineer or trained staff.
- Eliminate any errors immediately
- Fill out the logbook
- Advise that the system is going to be taken out of operation before starting
the inspection
- Inform the operating company that the alarm is going to be triggered for
equipment testing purposes
- Interrupt or turn off remote alarm reporting or remote control
Visual inspection:
Check all appliances and cable connections for outer damage and dirt
accumulation.
Fire detectors, smoke vent buttons, smoke vents and so on must not be
impaired in their function by goods in storage or structural changes.
- Clamps and fastenings
Check connection terminals and fastenings of appliances that they are
securely seated.
- Drives and smoke vent
In the case of excessive dirt accumulation and load, clean and re-grease
outer mechanically moved parts.
Attention: Use only colourless fat-free Lusin A spray. Do not use any
grease so that dirt cannot stick.
- Automatic fire detectors
In the case of severe externally visible dirt accumulation or false alarms,
send them in for maintenance and install an exchange detector. Check
detectors individually with D+H-smoke detector tester.
Procedure in the case of alarm:
Do not carry out functional testing if
trigger plug-in card AE 526-DG is
installed for the control of 8 pressure
gas generators.
No possibility of functional testing. Triggering will lead to the destruction of
the pressure gas generators and sprinkler bottles as well as the emptying of
the CO2 cartouches. This will generate costs for exchange parts and the time
to install them. Shutdown of the system by a specialist company or trained
staff.
Please note: Always activate another smoke vent button or smoke detector
for each line with every new test.
1. Open smoke vent button.
2. Open the system first with vent button and then close it again.
3. Trigger smoke detector with D+H-smoke detector tester.
4. Response delay approx. 20 seconds
5. Red display LED in the smoke vent button must light up.
6. Smoke vent opening must open.
Closing after automatic release by smoke detector:
1. Wait until there is no more smoke in detector. Switch the line on / off at the
control panel with reset button.
2. Press concealed button
in smoke vent button; smoke vent closes.
3. Red display LED
in button and on line plug-in unit goes out.
Procedure in the case of alarm with external control:
1. Trigger external control, if available.
2. Smoke vent opening must open.
99.821.70 3.5/01/12
Closing after automatic triggering by external control:
1. Open contact in external system, e.g. by resetting the fire alarm system.
2. Press concealed button
in smoke vent button; smoke vent closes.
3. Red display LED
in button and on line plug-in unit goes out.
Check alarm display and balanced running of all drives up to final
position.
Emergency supply:
- Switch off main fuse at distribution box.
- Green control diode
in smoke vent buttons should not light up.
Repeat functional testing.
- Green mains indication diode
on control panel should not light up.
- Ventilation is out of service.
Accumulator:
Yellow display LED
on the central unit circuit board must light up.
- Check accumulator type.
- Contacts and housings must be clean and tight.
- Check fully charged accumulators that have not yet been used for correct
open-circuit and on-load voltage using D+H accumulator tester, in
accordance with the testing table:
- Measure the open-circuit voltage (alternatively using a digital
voltmeter); every accumulator must have between 13.5 and 13.9 V.
- Measure the on-load voltage. For this, open the system completely
twice via vent button. On the third time, measure the voltage during the
process.
The voltage of each accumulator must be at least 11 V. If the voltage of one
of the accumulators is less than 11V, both the accumulators must be
replaced.
Charging voltage:
-
Charging voltage is factory-set!
Disconnect accumulator for checking.
Substituded, connect 10 kΩ resistors to accumulator
output.
Compare voltage with table, using a calibrated 3½-digit digital
voltmeter and a calibrated thermometer.
Surrounding temperature in
battery height
15°C
16°C
17°C
18°C
19°C
20°C
21°C
22°C
23°C
24°C
25°C
26°C
27°C
28°C
29°C
30°C
31°C
32°C
33°C
34°C
35°C
Charging voltage
27,52 - 27,92 V
27,49 - 27,89 V
27,46 - 27,86 V
27,42 - 27,82 V
27,39 - 27,79 V
27,36 - 27,76 V
27,33 - 27,73 V
27,30 - 27,70 V
27,26 - 27,66 V
27,23 - 27,63 V
27,20 - 27,60 V
27,17 - 27,57 V
27,14 - 27,54 V
27,20 - 27,50 V
27,07 - 27,47 V
27,04 - 27,44 V
27,01 - 27,41 V
26,98 - 27,38 V
26,44 - 27,34 V
26,91 - 27,31 V
26,88 - 27,28 V
RZN 43xx-E
15/16
D+H Mechatronic AG
Georg-Sasse-Str. 28-32
22949 Ammersbek, Germany
Tel.: +4940-605 65 239
Fax: +4940-605 65 254
E-Mail: info@dh-partner.com
www.dh-partner.com
© 2010 D+H Mechatronic AG, Ammersbek
Technische Änderungen vorbehalten. /
Rights to technical modifications reserved.
99.821.70 3.5/01/12