Growatt 33-40K TL3-US20160525 - Growatt New Energy Technology
Growatt 33000 TL3-US
Growatt 36000 TL3-US
Growatt 40000 TL3-US
Installation
SHENZHEN GROWATT NEW ENERGY TECHNOLOGY CO.,LTD
GROWATT USA Inc
19201 Parthenia Street,Unit E,Northridge,CA91324
TEL:844 650 1825
usaser vice @ ginverter . com
www . growatt - america . com
GR - UM - 075-A - 00
& Operation Manual
Table
1 Introduction
1.1 Validity
6
PV Module setting
7
Electric Arc hazards
1.2 Target Group
1.3 Storage of the manuals
1.4 Additional information
1.5 Symbols in this document
7.1 Arc-Fault Circuit Interrupter (AFCI)
7.2 Danger Information
7.3 Operation step
2 Safety
2.1 Intended Use
2.2 Qualification of skilled person
2.3 Safety instruction
2.4 Operation warnings
8
Commissioning
8.1 Display and message
8.2 Operation checking on the
Growatt TL3-US
8.3 Two independent MPPT
3 Product Descriptions
8.4 Communication
3.1 Growatt TL3-US
3.2 Type label
3.3 Size and weight
3.4 The advantage of the Growatt
9
Booting and shutdown
of the inverter
TL3-US inverters
4 Unpacking
9.1 Booting the Growatt TL3-US
9.2 Turn off the Growatt TL3-US
10
Maintenance
10.1 Checking the inverter
10.2 Checking the DC switch&AC switch
10.3 Cleaning the Inverter
5 Installation
10.4 Cleaning the Fan Guards
5.1 Safety instructions
10.5 Fan replacement
5.2 Selecting the Installation Location
10.6 Fuse replacement
5.3 Mounting the Growatt TL3-US
10.7 Inverter replacement
5.4 Electrical Connection
5.5 Grounding
5.6 Grid type
5.7 Growatt TL3-US WIRE BOX
5.8 RS485 Signal Wiring Connections
11
Decommissioning
11.1 Dismantling the Growatt TL3-US
11.2 Packaging the Growatt TL3-US
Introduction 1
1.1 Validity
12
This manual describes the assembly, installation,commissioning and maintenance
Trouble Shooting
of the following series GROWATT inverters:
12.1 Warnings(W)
12.2 Errors (E)
Growatt 33000 TL3-US
Growatt 36000 TL3-US
Growatt 40000 TL3-US
13
Specification
1.2 Target Group
This manual is for qualified personnel. Qualified personnel have received training
and have demonstrated skills and knowledge in the construction and operation of
this device. Qualified personnel are trained to deal with the dangers and hazards
involved in installing electric devices.
14
Spare Parts and Accessories
1.3 Storage of the manuals
Keep all Growatt manuals in a safe place for future reference.
15
Inverter installation plan
1.4 Additional information
15.1 Single inverter
15.2 Multi inverter
You can find further information on special topics in the download area at
Http://www.growatt-america.com
1.5 Symbols in this document
16
1.5.1 Warnings
Contact
A warning describes a hazard to equipment or personnel.
It calls attention to a procedure or practice, which if not correctly performed or
adhered to, could result in damage to or destruction of part or all of Growatt
equipment and/or other equipment connected to the Growatt equipment or
personal injury.
Symbol
Description
DANGER indicates a hazardous situation which, if not avoided,
will result in death or serious injury.
DANGER
1
Symbol
Description
DC current
WARNING indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
WARNING
Transformerless
CAUTION indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
CAUTION
NOTICE is used to address practices not related to personal
injury.
Earth Ground
NOTICE
INFORMATION that you must read and know to ensure optimal
operation of the system.
FCC certificate
INFORMATION
1.5.2 Markings on this product
UL1741 Standard for Safety for Inverters, Converters,
Controllers and Interconnection System Equipment for use with
Distributed Energy Resources. CSA C22.2 No.107.1,CSA C22.2
NO.14 - General Use Power Supplies.
Warning regarding dangerous voltage
The product works with high voltage. All work on the product must only
be performed as described in its documentation.
Beware of hot surface
The product can become hot during operation. Do not touch the
product during operation.
Observe the operating instructions
Read the product’s documentation before working on it. Follow all
safety precautions and instructions as described in the
documentation.
1.5.3 Glossary
AC
Abbreviation for "Alternating Current”
DC
Abbreviation for "Direct Current”
Energy
Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt
hours). The energy is the power calculated over time. If, for example, your inverter
operates at a constant power of 20,000 W for half an hour and then at a constant
power of 10,000 W for another half an hour, it has fed 15,000Wh of energy into the
power distribution grid within that hour.
AC current
2
3
Safety 2
Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an
instantaneous value. It displays the power your inverter is currently feeding into the
power distribution grid.
Power rate
Power rate is the radio of current power feeding into the power distribution grid and
2.1 Intended Use
The Growatt TL3-US is a PV inverter which converts the direct current (DC) of the PV
array to alternating current (AC) and feeds it into the power distribution grid.
A
B
C
D
E
F
the maximum power of the inverter that can feed into the power distribution grid.
Power Factor
Power factor is the ratio of true power or watts to apparent power or volt amps. They
are identical only when current and voltage are in phase than the power factor is 1.0.
The power in an ac circuit is very seldom equal to the direct product of the volts and
amperes. In order to find the power of a single phase ac circuit the product of volts
and amperes must be multiplied by the power factor.
PV
Abbreviation for photovoltaic
Wireless communication
The external wireless communication technology is a radio technology that allows
Symbol
A
Description
PV modules
B
DC load circuit breaker
C
Growatt TL3-US Inverter
D
AC load circuit breaker
E
Energy meter
F
Utility grid
the inverter and other communication products to communicate with each other. The
external wireless communication does not require line of sight between the devices.
The Growatt TL3-US takes current from PV array and converts it to alternating
current for the power distribution grid (F). Energy surplus may even result in the
energy meter (E) of your plant running backwards. The Growatt TL3-US is suitable
for indoor and outdoor use.
AC circuit breaker
Each inverter with an independent circuit breaker (three or four pole AC circuit
breaker) can securely disconnect from the grid safely.
·Do not share a single circuit breaker with more than one inverter.
· Do not connect the any local load between the inverter and the AC
circuit breaker.
CAUTION
4
5
PV modules
The PV modules used must be suitable for use with the Growatt TL3-US and must be
2.3.2 Electrical Connection Warnings
Make all electrical connections (e.g. conductor termination,
fuses, PE connection, etc.) in accordance with prevailing
regulations. When working with the inverter powered on, adhere
to all prevailing safety regulations to minimize risk of accidents.
approved by the module manufacturer.
The PV modules must be Monocrystalline silicon PV modules, Polysilicon PV modules
and thin-film PV modules with levels of protection and must not be grounded (can
not have anode or cathode lead from array going to ground)
· PV modules with large capacities relative to earth, such as thin-
WARNING
film PV modules with cells on a metallic substrate, may only be used
if their coupling capacity does not exceed 500 nF.
· Do not connect to any PV Modules that require the anode or the
cathode to be connected directly to Ground.
· Do not connect any energy sources other than PV modules to the
The components in the inverter are live. Touching live
components can result in serious injury or death
· Do not open the inverter with the exception of the wire box by
qualified persons.
· Electrical installation, repairs and conversions may only be
carried out by electrically qualified persons.
· Do not touch damaged inverters.
Growatt TL3-US.
CAUTION · Do not connect the any local load between the inverter and the AC
circuit breaker.
· The Growatt TL3-US is only used in the Grid-connected system.
2.2 Qualification of skilled person
This grid-tied inverter will only operates when properly connected to an AC distribution network. Before connecting the Growatt TL3-US to the power distribution grid,
you must contact the local power distribution grid company. This connection must be
made only by qualified technical personnel, and only after receiving appropriate approvals, as required by the local authority having jurisdiction.
DANGER
Danger to life due to high voltages in the inverter
· There is residual voltage in the inverter. The inverter takes 20
minutes to discharge.
· Wait 20 minutes before you open the wire box.
2.4 Operation Warnings
Anytime the inverter has been disconnected from the power
network, use extreme caution as some components can retain
charge sufficient to create a shock hazard; to minimize occurrence
of such conditions, comply with all corresponding safety symbols
and markings present on the unit and in this manual.
2.3 Safety instruction
The GROWATT TL3-US Inverters is designed and tested according to international
safety requirements (UL 1741/IEEE 1547); however, certain safety precautions must
be observed when installing and operating this inverter. Read and follow all
instructions, cautions and warnings in this installation manual. If questions arise,
please contact Growatt’s technical services at +86 (0)755 2747 1900.
Ensure all covers and doors are closed and secure during operation.
All operations regarding transport, installation and start-up,
including maintenance must be operated by qualified, trained
personnel and in compliance with all superseding codes and
regulations.
2.3.1 Assembly Warnings
· Prior to installation, inspect the unit to ensure absence of any
transport or handling damage, which could affect insulation integrity
or safety clearances; failure to do so could result in safety hazards.
·Assemble the inverter per the instructions in this manual. Use care
when choosing installation location and adhere to specified cooling
requirements.
· Unauthorized removal of necessary protections, improper use,
incorrect installation and operation may lead to serious safety and
shock hazards and/or equipment damage.
WARNING · In order to minimize the potential of a shock hazard due to
hazardous voltages, cover the entire solar array with dark material
prior to connecting the array to any equipment.
6
Systems with inverters typically require additional control (e.g.,
switches, disconnects) or protective devices (e.g., fusing circuit
breakers) depending upon the prevailing safety rules.
WARNING
Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk
of injury, do not touch the heat sink at the back of the PV-Inverter or
nearby surfaces while Inverter is operating.
Incorrect sizing of the PV plant may result in voltages being present
which could destroy the inverter. The inverter display will read the
error message “PV-Overvoltage!”
·Turn the rotary switch of the DC Disconnect to the Off position
immediately.
·Contact installer.
7
3 Product Description
3.2
3.1 Growatt TL3-US
F
E
Inverter Type Label
The type labels provide a unique identification of the inverter (type of product,
device-specific characteristics, certificates and approvals). The type labels are on
the right-hand side of the enclosure.
A
B
GROWATT
PV Grid Inverter
Model Name:
D
GROWATT XXXXXTL3-US
Range of input voltageMPP):
XXXVdc - XXXVdc
Max. input voltage:
1000Vdc
Max. input current of the MPP tracker:
C
36Adc/36Adc
Max. input short circuit current :
45Adc/45Adc
Nominal output power:
XXXXXW
Nominal grid voltage:
3/N/PE, 277Vac / 480Vac
Symbol
Range of grid voltage:
Description
422Vac - 528Vac
Operating grid frequency range(Hz) :
MIN.
59.3
Nominal
60.0
MAX.
60.5
A
LCD
B
LED
Grid voltage and frequency trip times :
C
Wire Box
Nominal output current:
D
Label
E
Fan air outlet
F
Flying rings
< 150mS
XX.XA
Max. output overcurrent protection: XXA
Output power factor : >0.99
Enclosure: Type 3R
Operation Ambient Temperature:
-25°C~+60°C (Derating above 45°C)
-13°F~+140°F (Derating above 113°F)
Inverter display
Symbol
Conforms to UL STD.1741 and UL STD.508C
Certified to CSA STD.C22.2 No.107.1 and CSA
STD.C22.2 No.14
Description
Tap symbol
NORMAL
FAULT
8
Inverter status
symbol
Explanation
Indicates display operation
(see Section 8).
Utility Interactive 3-Phase Inverter
Tested To Comply
With FCC Standards
FOR HOME OR OFFICE USE
4003184
Indicates inverter operation status
9
More detail about the inverter type label as the chart below:
3.3 Size and weight
Growatt 33000TL3-US/ 36000TL3-US /40000TL3-US
Label symbol
Growatt 33000TL3-US
Growatt 36000 TL3-US
Growatt 40000 TL3-US
Inverter Only
Range of input
voltage(MPP)
480V-800V
Max input voltage
1000V
520V-800V
570V-800V
Dimension
1000V
Weight
1000V
Height
Max input current
of MPP tracker
36A/36A
Max input short
circuit current
45A/45A
Nominal output
power
33000W/36660VA
45A/45A
45A/45A
36000W/40000VA
40000W/40000VA
277Vac/480Vac
3/N/PE
277Vac/480Vac
3/N/PE
277Vac/480Vac
3/N/PE
Range of grid
voltage range
422Vac~528Vac
422Vac~528Vac
422Vac~528Vac
operating grid
frequency
range(HZ)
Min Normal Max
59.3 60.0 60.5
Min Normal Max
59.3 60.0 60.5
Depth
36A/36A
Nominal grid
voltage
Min Normal Max
59.3 60.0 60.5
435 mm
790mm
265mm
50kg
17.1 inch
31.1 inch
10.4inch
110.2lb
Inverter with Packaging
Dimension
Weight
Length
Width
Heigth
950mm
550mm
430mm
37.4inch
21.7inch
16.9inch
56Kg
123.4lb
Grid voltage
and frequency
trip times
<150ms
<150ms
<150ms
Nominal output
current
40A
44A
48A
High efficiency
The CEC efficiency 98.5% , Max efficiency 98.8%.
Max output
current
44A
48A
48A
High power density
Smaller and lighter inverter , can be installed more
easily.
Max output
overcurrent
protection
55A
60A
60A
2 MPPTs
Dual independent MPP trackers and advanced MPPT
algorithms lead to optimal energy harvesting . Adapt to
different installations of strings or illumination variation.
Output power
factor
>0.99
>0.99
>0.99
Wide working range
Enclosure
Type 3R
Operating PV voltage range 200V~1000V.Wide range of
output power allows a variety of site designs, with an
emphasis on design flexibility and project yield.
ECO mode
Gets higher MPP precision and efficiency especially
under weak illumination.
AC Power Supply
Inverter can still be monitored and updated when PV
power turned off.
Operation Ambient
temperature
10
36A/36A
Width
3.4 The advantage of the Growatt TL3-US inverters
Functional features:
Type 3R
Type 3R
-25°C~+60°C (Derating above 45°C)
-13°F~+140°F (Derating above 113°F)
11
Unpacking 4
Intelligent
Integration
Integrated DC/AC Switch, DC/AC SPD (Class Ⅱ ),DC
Fuse in wire-box. Reduce space and save cost of
installation.
After opening the package, please check the contents of the box. It should contain
the following parts:
A
Independent
B
C
Support wire-box disassembly and assembly easily.
Wire-box
Flexible Communication
Comprehensive Protection
D
RS485/RS232/WiFi (OPT)/GPRS (OPT)/ETHERNET
(OPT).
For overvoltage, anti-island, DC insulation resistance
low, ground fault ,output short-circuit, overload,
overheat, etc
AFCI
Arc fault circuit interruption.
PID
Eliminate the power loss of PV modules caused by PID
effect.
String Monitor
Monitor the working status of each PV string.
G
F
G ro
Technical Characteristics:
Anti-corrosion paint
12
Anti-corrosion paint protection, to achieve a higher
reliability and life expectancy in complex application
field.
Patented inductor
Patented inductor design ensure lower-noise and perfect
performance.
AC switch
Intelligent management of output power.
DC link
Full film capacitor design on DC link, longer lifetime for
inverter.
LCL topology
E
LCL topology, higher quality of output power, adapt to
multiple parallel connection.
Inverter topology
New 3 levels invert topology, gets higher efficiency.
IGBT driver
Advanced IGBT drivers, effectively achieve short-circuit
and over-voltage protection for IGBTs.
I
J
H
w a tt
Item
Name
Quantity
A
Solar inverter
1
B
Mounting bracket
1
C
Hand shank
4(Opt.)
D
Expansion bolt
5
E
Safety-lock screws
6
F
Monitor software(disk)
G
Manual
H
External wireless
Opt.
I
PV cable Terminal
16
J
AC cable Terminal
5
Opt.
1
13
5 Installation
5.1 Safety instructions
Possible location for inverter under the ceiling:
· Before instructions, anyone includes qualified, trained personnel,
must make sure you have read the section 2.1, about the General
installation warnings.
WARNING
5.2 Selecting the Installation Location
Select the installation location based on the following considerations:
1) Select a well-ventilated location sheltered from direct sunlight and rain.
2) Choose a location that allows unobstructed airflow around the inverter.
3) Allow sufficient room around the inverter to enable easy installation and removal
from the mounting surface.
4) Height from ground level should be at least 3 feet.
5) Access panels on the front surface of the inverter allow inspection and maintenance of hardware; and must not be blocked. See Figure on pg. 18 for recommended
Minimum clearances around the inverter:
minimum clearances around the inverter.
6) Mount the Growatt TL3-US Inverter vertically as possible. For other mounting
orientations,please consult with Growatt.
7) Tilted mounting (±15° from vertical) is acceptable for the Growatt33000TL3-US/
36000TL3-US/40000TL3-US.
8) The inverter requires adequate cooling space, allowing at least 19.5 ”inches
( 50cm ) space above and below the inverter while 19.5” inch (50cm) space of right
and left.
9) The installation method and mounting location must be suitable for the weight and
dimensions of the inverter. Select a wall or solid vertical surface that can support the
PV-Inverter.
10) The location shall be away from strong electromagnetic interference.
11) The location shall not exceed Type3R standard according to ANSI/IEC_605292004.
14
15
Tilted mounting(+15° from vertical)is acceptable for the Growatt 33000TL3-US/36000
TL3-US/40000TL3-US following the picture blow.
50CM
90°
50CM
50CM
Clearances for multi inverters
0~90°
50CM
0°
DO NOT install the Growatt TL3- US into a small enclosure
5.3 Mounting the Growatt TL3-US
INFORMATION
16
General tools
Personal safety equipment such as gloves,
helmet, goggles, ear plugs, safety harness etc.
Step ladders.
Knife.
Tools for mechanical installation
Equipment for transporting and lifting the inverter.
Electric (hammer) drill.
Hammer.
Set of drill bits, wrenches, sockets and screw bits.
Socket driver, screwdriver.
Tape measure.
Spirit level.
Pencil or other marker.
Fastening screws, plugs, etc
17
Step 1:Drilling mounting holes for bracket
Step 3:Mounting the inverter on the wall
Use the mounting bracket as a template and drill 5 holes as illustrated in image
below, hole size: 10mm (diameter), 85mm (min. depth). Then insert the 4 expansion
bolts provided into the holes, make sure the bolts are paralleled with the outer
surface of the bracket.
Raise the Growatt TL3-US a little higher than the bracket. Due to the weight of the
inverter, additional tools may be required to hang the inverter using the right and left
fly rings on the top of the inverter. Make sure to maintain the balance of the Growatt
TL3-US during the process, as shown on figure below.
For Growatt 33000TL3-US/36000TL3-US/40000TL3-US, 5 holes
must to be drilled. The space between holes is 196.5mm, as
figure below.
4
5
3
INFORMATION
2
1
1
Inverter
2
Handles
3
Rings
4
Machine
5
Mounting Bracket
Knock off the plugs
Mounting
inverter
Step 4: Insert safety-lock screws
Insert the safety-lock screws into the two side holes of the mounting bracket to
fasten the inverter, as shown on figure below
2
2
Step 2: Installing the bracket
Place and hold the bracket onto the wall and screw on the nuts to fasten the bracket,
as the figure below.
5
4
3
2
1
1
Mounting Bracket
2
Expansion bolt
3
Plain washer
4
Spring washer
5
Expansion nut
1
2
2
1
Inverter
2
Soket Head Cap Screws
Knock Safey
Insert
off theScrews
plugs
Knock off the Bracket
Installing
plugs
18
19
Step 5:Check
5.4.2 Wiring Diagram with Over-Current Protection Device and
AC Disconnect
Check the upper straps of PV Inverter and ensure it is secured on to the bracket.
Check for secure mounting of the PV inverter by trying to raise it from the bottom.
The PV Inverter should remain firmly attached.
PV ARRAY
GROWATT TL3-US
AC SWITCH
ARRAY1
GRID
ØA
ØB
ØC
N
PE
5.4 Electrical Connection
5.4.1 Safety
ARRAY2
· Before instructions, anyone including qualified, trained personnel,
must make sure you have read the section 2.3, General Installation
Warnings.
WARNING
Electrical installations
· All electrical installations must be done in accordance with all
local electrical codes and the NATIOAL Electrical Code ®,
ANSI/NFPA 70. For installation in Canada the installations must be
done in accordance with applicable Canadian standards.
AC disconnect switch: 3-pole, with or without neutral block depending upon
chosen grid connection (3wire or 4Wire). Voltage and current rating depends on
the grid connection voltage and output power of the inverter being installed. The
fuse size or breaker is depending on the rating of output current.
5.5 Grounding
·Before connecting the inverter to the power distribution grid,
INFORMATION contact your local electric utility company. This connection may be
made only by electrically qualified persons.
AC Ground
Tools for electrical installation
·Hexagonal driver 3mm for securing the front cover and AC connector.
·Flat screwdriver 3mm for releasing spring terminals.
·Cable and wire strippers.
·Side cutters.
·Crimping tool and cable lugs.
INFORMATION ·Cable marking equipment.
·Digital multimeter (insulation tester) with DC and AC sensitive
current clamp, voltage measurement (max. 1000 VDC) and continuity testing functions.
GET
AC Grounding
The Growatt TL3-US must be connected to the AC grounding conductor of the power
distribution grid via the ground terminal (PE).
The AC input and AC output circuits are isolated from the enclosure and system
grounding, if required by Section 250 of the National Electrical Code, ANSI/NFPA 70.
Grounding Electrode Terminal (GET)
A grounding electrode terminal may be required to local regulations.
20
21
Growatt 33000TL3-US/36000TL3-US/40000TL3-US
5.6 Grid type
GRID standards:
3
8
Based on the local GRID standards, one may select different connection types. The
available configurations are shown as below:
1
480 Delta277 Wye
2
4
7
9
9
10
277 V
48
0
L1
0V
48
L1
V
6
L2
27
7
L3
7V
27
9
5
L2
1
DC Switch
2
AC Switch
Quick Connect
Terminal
Plug (ø51)
3
V
480 V
L3
When using the 480Delta, the Neutral of the Growatt TL3-US must connect to the
Earth of the grid. Contact Growatt if you want further information.
·Policies vary from one utility company to another. Consult with
a representative of the local utility company before designing and
installing a PV system.
INFORMATION
Grid type:
The Growatt TL3-US may only be used in TN-C/TN-C-S/TT/TN-S grid types, not
available for IT and Split phase types.
5.7 Growatt TL3-US WIRE BOX
· This chapter shows installation positions on attachment
specific-ations and standards.
INFORMATION
4
DC Fuse
5
Communication
Connection
6
DC Terminal
7
AC Terminal
8
The DC&AC SPD
9
Size of conduit:1-1/4 Inch
9
10
Plug (ø35)
10
Size of conduit:3/4 Inch
11
12
11
Protection Cover
12
RS 232 Port
WIRE BOX FIGRUE
Note : Fuse Sizing
In any electrical system, fuses are used to protect wiring and equipment from
excessive currents that can cause damage, heating or in extreme cases even fire. If
the fuse rating is too small it could be blown during normal operation. If the fuse
rating is too large, it cannot provide the needed protection. In PV systems, the
minimum and maximum size of the series fuse is determined by the electrical ratings
of the PV module as well as by UL and National Electrical Code (NEC) requirements.
Be sure to consult with your PV module manufacturer for appropriate fuse ratings.
The minimum size of fuses and conductors are calculated using the Short Circuit
Current Rating (Isc) of the PV module. The NEC requires that all fuses and
conductors be sized for a minimum of 1.56 times the Isc of the PV module used in the
system. The proper size PV string fuse is determined by calculating 1.56 x Isc (of the
PV module) and then rounding up to the next standard fuse size.
Example DC fuse rating: If the Isc of the PV module equals 9.6 Adc, then the fuse
size is determined by 1.56 x 9.6 = 14.98Adc. The next standard fuse size would be a
15A, 1000Vdc fuse.
Internal integrated DC & AC Disconnect
Integrated in the inverter and convenient for installation
Listed to UL 1741 for the United States and Canada
Simplified input wiring
Compact, low-cost design
22
23
Routing method
5.7.2 AC Cable Requirements
The cable must be rated in accordance with the local and national codes. The
requirements for the minimum conductor cross-section derive from these
directives. Influencing factors for cable dimension are the following: nominal AC
current, type of cable, cable length, routing method, cable bundling, ambient
temperature and maximum desired line losses.
The higher the ambient temperature, the higher the power losses; this will cause
the conductor cables to heat up during operation. If there are several cables in a
conduit, the temperature of all cables increases.
Use cables with a large cross section if there are several cables in one conduit.
E
C
D
·Use only solid or stranded wire but not fine stranded wire.
A
INFORMATION
B
Ambient temperature
Name
code
The higher ambient temperature, the higher power losses;
Detail
A
Conductor cross-section
See the Conductor cross section
in the flowing chart
B
Stripping insulation
12mm(0.47inch.)
85℃, the system will reduce the output power until the temperature drops under the
C
insulation
--
critical value. If this occasion happens often, it is necessary to check whether the
inverter is mounted at an appropriate place with good ventilation and not directly
exposure to the sunshine.
D
containment
--
E
AC cable terminal
--
Use cables with large cable cross-sections in installation sites with high ambient
temperatures.
The inverter will monitor its internal temperature, once the temperature exceeds
Temperature derating characteristics
Definition of Temperature derating characteristics in accordance to BS EN
50524:2009 For the purpose of self-protection routines can be implemented into the
inverter, which prevent a damage (current – power – temperature derating). Any selfprotection routine that causes derating must be described in tabular or graphical
form over the entire permitted operation range.
For growatt TL3-US, the grid impedance of the AC conductor cable must not
exceed 0.5 Ohm. Otherwise, the GROWATT TL3-US will disconnect at full feed
capacity due to excessive voltage at the feed-in point. AC conductor cable losses
should always remain under 1%. The details of conductor cross-section and the
maximum conductor cable lengths relative to GROWATT TL3-US are shown in the
following table.
REMARK:The figure of AC cable with terminal is shown in the figure above.
Power Rate ( % )
Figure:
Maximum cable lengths between the three phase inverter and the sub panel:
105%
100%
Model
95%
Conductor cross section
Maximum cable length
90%
85%
80%
Growatt 33000TL3-US
(AC connect cable)
#8~#4AWG(8.37~21.15mm²),
221°F(105°C)
25m(82ft) for #8AWG
65m(213.2ft) for #4AWG
Growatt 36000TL3-US
(AC connect cable)
#8~#4AWG(8.37~21.15mm²),
221°F(105°C)
23m(75.4ft) for #8AWG
60m(196.8ft) for #4AWG
Growatt 40000TL3-US
(AC connect cable)
#8~#4AWG(8.37~21.15mm²),
221°F(105°C)
20m(65.6ft) for #8AWG
53m(173.8ft) for #4AWG
75%
70%
65%
60%
55%
50%
-20℃ -15℃ -10℃ -5℃ 0℃
5℃ 10℃ 15℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃ 55℃ 60℃ 65℃
Temperature (℃)
33K TL3-US
24
36K TL3-US
40K TL3-US
25
5.7.3 Connecting the AC cable in the Wire box
3. Feed the conductors through the rubber grommet into the wire box.
·Open terminals fully before insertion of the conductor cables.
INFORMATION
· Before connecting, make sure the AC conductor cables are
disconnected from the AC breaker. Do not power while connecting!
DANGER
Knockthe
Feed
offconductors
the plugs
1. Open the wire box of the Growatt TL3-US.
4. Pull the conductors back slightly so as to seal the rubber grommet.
Knock
Pull theoff
Conductors
the plugs
2. Knock off the plugs on the wire box and install rubber grommets instead of the
plugs.
1
3
7
2
5
4
6
8
1
DC Switch
2
Plug of PVA(ø51)
3
Plug of PVB(ø51)
4
Rs232 Port
5
Plug of Communicate(ø35)
5. Connect the AC device grounding green-yellow conductor to the PE terminal,
black conductor to the terminal labeled N and the red wire conductors to the
terminals labeled L1(AC conductor A), L2(AC conductor B), L3(AC conductor C)
separately .
L1L2L3 N PE
6
Plug of AC
7
AC Switch
8
Earth
AC Terminal
Knock off the plugs
26
27
6. Tighten the cables with a torque of 2.0N.m (17.7lbf.in).
7. Check that all terminals have the correct wiring and that the cables are secure.
The AC cables are connected in the wire box.
5.7.4 DC cable requirements
·Only use solid wire or stranded wire
Model
Conductor cross section
Maximum cable length
Growatt 33000TL3-US
(DC connect cable)
#12(3.31mm²),
221°F(105°C)
10m(32.8ft) for #12AWG
26m(85.3ft) for #8AWG
Growatt 36000TL3-US
(DC connect cable)
#12(3.31mm²),
221°F(105°C)
9m(29.5ft) for #12AWG
24m(78.7ft) for #8AWG
Growatt 40000TL3-US
(DC connect cable)
#12(3.31mm²),
221°F(105°C)
8m(26.2ft) for #12AWG
20m(65.6ft) for #8AWG
5.7.5 Connecting the DC cable in the Wire box
High voltages on PV modules that are exposed to light
INFORMATION
Risk of death due to electric shock from touching a DC conductor.
Do not touch the DC conductor.
The DC Cable design refers to the conductors from the solar module to the input
High voltages in the DC cables
terminal of the inverter. When carrying out the cabling for the DC side, a few rules
Risk of death or serious injury from touching a DC cable.
DANGER
Only connect the DC cable from the PV module to the inverter
should be observed for optimal and fault-free operation, both with roof-mounted and
as described in this manual.
free-standing devices.
Before connecting, make sure the DC switch in the wire box is
Use cables with connectors which are contact-proof and designed to avoid
turned off and measure the voltage to ensure the array output is
connection confusion.
non-hazardous.
Cables should run through protective tubes or mounting frames to protect them
from weathering and UV radiation. Cables which are hanging freely or which lie on
WARNING
Danger of burning due to overheating
Observe the National Electrical Code® 2008, Section 690.35
stone or in water (> flat roof) are not allowed.
It is recommended to carry out insulation and resistance measurements after
every cable installation in order to locate any possible faults in this partial string,
which becomes more difficult to do later on the entire system.
PVB+
PVA+
The connection cables for all strings should be numbered to facilitate later fault
PVB-
PVA-
location.
DC Terminal
DC Terminal
In a large PV array the cross-section variants of the cables must be as few as
possible in order to facilitate mounting and to avoid faulty installations due to
confusion of cables. Here, cable losses should always remain under 1%.
REMARK:
The details of conductor cross-section relative to GROWATT TL3-US are shown in
The figure of conduit is shown in the right
the following table.
picture.Please press the cable into the PV
cable terminal before you connect the PV
cables .
28
29
RS485 BUS balance jumper:
· About the Wirebox DC connection of the Growatt TL3-US, please
In RS485 communication circuit, when the T/R+ and T/R- lines reach a certain length
refer to section 6 for more detail .
(>328 feet), the line itself has impedance. In order to balance the impedance of the
INFORMATION
RS485 bus line, you must install the jumper to the “ON” state in RS485 BUS balance
1. Knock off plugs on the wire box and Install rubber grommets instead of the plugs.
jumper of the remote inverter (last inverter before monitoring). So that the last
2. Push the DC conductors through the grommet in the wire box in order to pierce the
rubber grommet. Do not use sharp tools to pierce the rubber grommet.
inverter connects to the RS485 bus line while others stay in “ON” state.
The RS485 bus line is recommended not exceed 2,624ft when using the #20AWG
3. Pull the conductors slightly back in order to seal the grommet.
RS485 communication standard line. Shielded twisted pair cable (STP), impedance
4. Open the screw terminals completely by turning them counterclockwise using a flathead screwdriver.
100...150 ohm is recommended.
5. Connect the DC conductors to the MPPT1 and MPPT2 array terminals shown in
inverter per the specific array design.
TX
6. Tighten all conductor cables in the terminal blocks in the wire box with a torque of
1.2Nm (10.6lbf.in) for Growatt TL3-US PV strings.
RX
7. Verify that all connections are correctly terminated and tightened to the correct
torque. Pull on the conductor cables in order to make sure that it is attached tightly
enough in the terminal.
GND
8. Close the wirebox; the DC cables are now connected in the wire box.
·In order to improve the Anti-jamming capability of RS485 communication,
it is recommended that the GND terminal of the inverter which connects to
the ShineWebBox must be connected to the EARTH.
·Adopting shielded twisted-pair cable and effectively grounded.
·In strong electric field location one must use galvanized tube shielding
the twisted pair.
5.8 RS485 Signal Wiring Connections
NOTICE
code
Details
A
RS 485 stander connector
B
RS 485 BUS balance jumper
·The twisted pair should be away from the high tension line, high voltage
power line and other signal line.
Computer
line
B
485A
485B
ON
terminate the
daisy chain
OFF
TR+
TR+
TRTR-
ON
ON
OFF
OFF
OFF
485A
485B
GND
ON
A
OFF
ShineWebBox
GND
twisted pair
GND
Rs485 Bus Connection via RS485 standard connector: connect three RS-485 leads :
T/R+, T/R-, GND into position shown.
30
31
6 PV Module setting
Default PV Module setting chart:
A 2 bit switch is in the wire box of Growatt TL3-US which is used to set the PV
module.
Switch state
Wiring diagram
Since the Growatt TL3-US has two independent MPPTs, the solar panels can be
connected in two MPPT channels independent or just connected to MPPT A
S1
S2
OFF
OFF
channel.
In order to identifie which channel is taken, you have to set the PV module by the 2
bit switch.
You have to refer to the following information:
STATE 1
The location of the 2bit switch as follow:
S1
S2
ON
OFF
STATE2
S1
S2
OFF
ON
STATE 3
S1
S2
When set the Growatt TL3-US in parallel mode, you must
using the standard line to connect PVA+to PVB+, and
PVA - to PVB -.
ON
ON
STATE 4
32
The inverter has double MPPT’s, it is recommended for
each MPPT to work independently, do not use parallel
wiring at DC side (Parallel wiring can make 2 MPPT’s
become 1 MPPT, this can improve the efficiency in some
cases). If the MPPT’s are parallel wired at inverter it may
cause the AFCI trigger mistakenly.
33
7 Electric arc hazards
7.3 Operation step
7.1 Arc-Fault Circuit Interrupter (AFCI)
In accordance with the National Electrical Code R, Article 690.11, the inverter has a
system for the recognition of electric arc detection and interruption. An electric arc
with a power of 300 W or greater must be interrupted by the AFCI within the time
specified by UL 1699B. A tripped AFCI can only be reset manually. You can
deactivate the automatic arc fault detection and interruption (AFCI) via a
communication product in "Installer" mode if you do not require the function. The
2011 edition of the National Electrical Code R, Section 690.11 stipulates that newly
installed PV systems attached to a building must be fitted with a means of detecting
and disconnecting serial electric arcs (AFCI) on the PV side.
7.3.1 Turn the DC & AC Disconnect to position "O".
Wait for the display to go out.
7.3.2 Perform troubleshooting on the PV system:
7.2 Danger information
Check all PV strings for the correct open-circuit voltage.
7.3.3 After the fault is rectified, restart the inverter:
Turn the DC & AC Disconnect to position "I".
Danger of fire from electric arc
Only test the AFCI for false tripping in the order described
below.
Do not deactivate the AFCI permanently.
The inverter has double MPPT’s, it is recommended for each MPPT to work
independently, do not use parallel wiring at DC side (Parallel wiring can make 2
MPPT’s become 1 MPPT, this can improve the efficiency in some cases). If the
MPPT’s are parallel wired at inverter it may cause the AFCI trigger mistakenly.
If an "Error 112" message is displayed, the red LED is permanently lit and the buzzer
alarms, an electric arc occurred in the PV system. The AFCI has tripped and the
inverter is in permanent shutdown.
The inverter has large electrical potential differences between its conductors. Arc
flashes can occur through air when high-voltage current flows. Do not work on the
product during operation.
When the inverter error 112, please follow the steps:
34
7.3.4 If the AFCI self-test is successful:
The PV inverter switches into the "nominal" mode and the green LED is
permanently lit.
7.3.5 If the AFCI self-test is failed:
The following message appears on the display: "Error 114".
Please restart the system, repeat step 1 to step 3.
7.3.6 If the AFCI self-test continues to fail:
Turn the DC Disconnect to position "0" and switch off the AC disconnect switch
to the inverter; contact Growatt to solve this problem.
35
8 Commissioning
Detail
Position
A
Text line for displaying an event
High voltages in the PV system Risk of death or serious injury
due to electric shock.
B
Input voltage and current of MPPT A
Only electrically skilled persons may perform work on the PV
array.
C
Input voltage and current of MPPT B
D
PV array A and B, lighted when the array voltage is
above the start voltage(120V)
E
Current power
F
Daily energy
G
Total energy generated since the inverter was installed
H
Light when the array voltage is above the start voltage(120V)
I
Lighted when “H” is lighted and feed-in
J
Output phase of the line conductor, s J witch every 5 seconds.
The AC conductor cable is correctly connected.
K
Output voltage /current /frequency of the line conductor
The DC conductor cable is correctly connected.
L
DANGER
Under any condition! Make sure the maximum open circuit
voltage (Voc) of each PV string is less than 1000VDC.
WARNING
Requirements:
Graphical display of the inverter energy/power
M
8.1 Display and message
N
8.1.1 Graphic display
RS232 communication
RS485 communication
Internal wireless communication
External wireless communication
8.1.1.1 Graph
The inverter energy and/or power is shown as a graph on the display. The lower
right-hand bar of the graph represents the current unit of time: Day/h, week/day,
Year/y, Year/Y. The top bar of the graph represents the maximum value of the
graph values. The daily graph is displayed by default. You can knock the enclosure
lid three times to switch the current unit of time and the generation information.
36
37
8.1.1.2 Text line
The Text line is used for displaying an event. Include the information of setting
language, models, communication address and time. The “Power Rate” and
The graph shows recent 16 hours of power
generation and the maximum value power of the
“Power Factor” will cycle through display by default setting.
You can operate the settings as follows:
16 values.
a) Input setting code
Before setting the language, COM Address and time, you have to input the setting
code:
1) Knock on the enclosure lid
once at a time until the text line
The graph shows recent 7 days of power
cycles to the text
generation and the maximum value power of the 7
2) Knock on the enclosure lid
values.
twice and the text will display
Setting ...
Input 123 : 000
3) Knock on the enclosure lid
twice to let the higher number text
“000” flash. Then knock on the
enclosure lid once to change it
The graph shows recent 12 months of power
from “000” to “100”. For every
generation and the maximum value power of the
knock the highest number text will
12 values.
add 1, the range of number text is
Input 123 : 100
0~9. Then knock the lid twice to
verify it.
4) Then the middle number text
will flash:
Input 123 : 110
The graph shows recent 16 years of power
generation and the maximum value power of the
16 values.
5)Knock the enclosure lid once to
change it from “100” to “110” and
then again to change it from “110”
Input 123 : 120
to “120”. Then knock the lid twice
to verify it.
Then you can set the language, COM address and time.
38
39
b) Setting language
1)
Knock on the enclosure lid
once at a time until the text line
cycles to the text .
2)
Knock on the enclosure lid
twice and the text will show the
language .
3) You can choose the language
by knocking the enclosure once;
the language includes English,
Dutch, Spanish, French, and
Italian.
4)
Then you can knock the
enclosure three times to confirm
the language you have chosen.
And the text line change
Set language
Language:English
Setting ...
For the communicating, the inverter needs a communication
address. In multi system, the addresses of inverters must be
different from one to another.
Com Address : 001
As the Serial communication with the computer and the external
wireless communication using the same serial port, we have to
choose one.
The RS232 is communicating to computer so that the computer can
be connected to the inverter using our software tools.
Knock on the enclosure lid once every time until the text line cycles to the text as
shown below: The RS232 is chose by default in the inverter.
1) Knock on the enclosure lid
once at a time until the text line
cycles to the text as the right.
RS232
2) Knock on the enclosure lid
twice to cycles to external
wireless communication.
Exter wireless
3) Then knock on the enclosure
three times to confirm it. And the
text line change as shown below:
Setting ...
Set OK!
2) Knock on the enclosure lid
twice and the lower number text
"1" will flash: 001.
40
d) Switching the RS232 and the External wireless communication
INFORMATION
c) Setting Com Address
3) If you want to set the address
using more digits, knock on the
enclosure lid twice to let the
higher number text “002”
flashing. And knock the enclosure
lid once every time to change it
form: 0~9. So as the highest
number text. Usually, the inverter
COM address is within 0-32.
Set OK!
The Com Address is set!
Set OK!
You can knock the lid four times to quit the setting menu.
If you want to change it, knock on
the enclosure lid once at a time to
change it form: 0~9.
Setting ...
You can knock the lid four times to quit the setting menu.
The language is setting!
1)
Knock on the enclosure lid
once at a time until the text line
cycles to the text.
4)
You can knock on the
enclosure three times to confirm
the COM Address you have
chosen.
The External wireless communication is set!
Com Address : 005
You can knock the lid four times to quit the setting menu.
e) Setting date and time
Com Address : 015
1) Knock on the enclosure lid
once at a time until the text line
cycles to the text shown as the
right (time displayed can differ
depending on the inverter).
2012 /01 /0 1 00 :12
41
2) Knock on the enclosure lid
twice and cycles to the year
"2015", and the two lower
number "2015" will flash, then
you can knock once at a time to
change it.
3) Knock on the enclosure lid
twice and cycles to the month
"01", and it will flash. Then you
can knock once at a time to
change it.
2015 /01 /01 00 :12
2015 /12 /01 10 :12
4) Repeat to set the day and the
time.
2015 /12 /25 10 :12
5) Then knock on the enclosure
three times to confirm.
Setting ...
Set OK !
The date and the time is set!
You can knock the lid four times to quit the setting menu.
· You can set all above changes with Growatt software “ShineTool”
using a computer. More information please go to the site:
Http://www.growatt.com .
INFORMATION
Indicate which fuses are open.
For exmaple,”Fuse Open12”
represents the1st and 2nd fuse
are open.
Indicate which strings are
unusual. For exmaple,”String
Unusal 12” represents the1st and
2nd curents are unusal.
Reverse:12345678
Fuse Open:12345678
String Unusal:12345678
Indicate which strings are short.
For exmaple,”Str Short12”
represents the1st and 2nd strings
are abnormal.
Str Short:12345678
Indicate which strings are break.
For exmaple,”Str Break 12”
represents the1st and 2nd strings
are break.
Str Break:12345678
g) check the PID information
1) Knock on the enclosure lid
once at a time until the text line
cycles to the text as the right.
PID Info
2) Knock twice to enter,and the
soft version and PID information
are shown on the screen ;
FW:NCAa0001
knock once to quit.
f) check the string information
PID:
1) Knock on the enclosure lid
once at a time until the text line
cycles to the text as the right.
String Info
2)Knock twice to enter the
string information,shown as the
right on cycle;
FW:NCAa0001
Knock once to quit.
Str1: 025V 0.1A
800V 0.3mA
If there is error information, it will shown on the screen after software
version,cyclely;
...
Str8: 021V 0.5A
If there is error information,it will be shown after sofeware version one by
one,and shown with the string information on cycle;knock once to quit;
the following situation is the fault status that might happen.
42
Indicate which strings are reverse
connected. For exmaple,”PV12
Reverse”represents the1st and
2nd strings are reverse.
Knock once to quit.(The fowllowing is the probable status shown on the the screen)
Indicate which strings are reverse
connected. For exmaple,”PV12
Reverse”represents the1st and
2nd strings are reverse.
PV 12 Reverse
Indicate which strings are disconnected. For exmaple,”PV12
Disconnect”represents the1st
and 2nd strings are disconnect.
PV 12 Disconnect
Isulation resistance between the
DC input with respect to ground is
lower than limit.
ISO Error
43
BUS voltage of PID is abnormal.
BUS Volt Abnormal
Output of PID over voltage.
Output Over Volt
h) Other display
Knock on the enclosure lid once at a time and the text line cycles to
information about of the Growatt TL3-US:
Displaying the internal bus+
and bus- voltage
Displaying the PF value:
BUS+/-:XXXV/XXXV
The real-time power that has been feeding into the grid from the
inverter
Day
The energy fed into the electricity grid on this particular day. This
equals the energy generated from the inverter's start-up in the
morning to the current time.
PF(Over ): +X.X
PF( Under ): X.X
Displaying the power factor:
Power
Power Factor : X .X
Displaying the serial number of
the inverter:
SN:XXXXXXXXX
Displaying the module of the
inverter:
Model: GT00X0XXXX
Total
Measurement
accuracy
The total energy that the inverter has fed into the electricity grid
during its entire operating time.
The display values may be a little different from the actual values
and must not be used for billing purposes. The inverter's
measured values are required for the operational control and to
control the current to be fed into the electrical grid. The inverter
does not have a calibrated meter.
8.1.2 LED
Displaying the power type of the
inverter:
33000 TL3-US
Displaying the software version
of the inverter:
FW:XXX.X-XX.X
8.1.1.3 Power display
The power and energy of the inverter are displayed in three fields:
Power, Day and Total. The display is updated every five seconds.
44
45
The LED also represents the status of the inverter.
LED color /status
4. If the PV voltage input is above 120V, Growatt TL3-US should operate. And text
line of the LCD display as shown below:
Inverter status
SN:XXXXXXXXX
Green/constant
Operation
Red/constant
Fault– contact installer
Standby module
Red/flashing
Fans Fault-- contact installer
Software update
Model: GT00X0XXXX
33000 TL3-US
FW:XXX.X-XX.X
8.2 Operation checking on the Growatt TL3-US
Item
·About the LCD and LED, you can refer to the next section 6.2 for
details.
INFORMATION
Growatt
33000 TL3-US
Growatt
36000 TL3-US
Growatt
40000 TL3-US
Module:
PFU8M9S1
PFU8MAS1
PFU8MBS1
PV:
33000TL3-US
36000TL3-US
40000TL3-US
SN:
SN is the serial number of the inverter; every machine has its own serial
number, SN: 1234567890 for example.
FW:
FW is the software version of the inverter, FW:CT1.0-AT1.0 for example.
1.Remove all covers from the PV array.
2.Switch on the AC breaker.
3.Turn the DC Disconnect to position "I".
5. If the PV voltage input is between 200-250V, the Growatt TL3-US will work in a
standby status.
If the PV voltage is between 250V~1000V, the Growatt TL3-US will work in a normal
status. So you can check the input and output information as well as the status of the
Growatt TL3-US on the LCD.
6. Once the Growatt TL3-US is working in a normal status, before connected to the
grid.
It will take 60 seconds to check the inverter including the GFCI automatically.
The LCD text line's information as shown below:
Connect in 60s
46
47
7. When it counts to 0s, the inverter begins to connect to the grid.
The connecting diagram as follows:
Once it feeds to the grid successfully, the text line in the LCD text line's information
will show as shown below:
USB Port
USB to RS 232
Tramsmeter
Connect OK !
RS232Port
And the LED will turn to green.
The Growatt TL3-US feeds to the grid successfully!
The Growatt TL3-US includes dual input with independent MPPT, high speed and
precise MPPT algorithm for real-time power tracking and energy harvesting, as well
as transformerless operation for high performance efficiencies. The two MPPT
channel can track the maximum power point independently when inverter receives
two separate inputs from solar panel and the two independent MPPT have no impact
with each other.
8.4.2 Monitor the inverters
1) Monitor the inverters with RS485
ShineWebBox
Inverter
·Although the Growatt TL3-US can work two MPPT’s independently,
it is recommended to configure the two MPPT channels with the same
PV panels and power.
OFF
INFORMATION
2
Computer
line
TX
ON
8.3 Two independent MPPT
OFF
1
RX
GND
ON
twisted pair
RS 485 Balance jumper
8.4 Communication
Computer
OFF
TR+
TR-
ON
OFF
ON
ON
terminate the
daisy chain
About the software of ShineTool and the usage of it please download from the web:
www.growatt.com
OFF
ON
OFF
8.4.1 Using ShineTool to set the information of the inverter
line
ShineWebBox
This section is about the setting information of the inverter and the monitoring of the
inverters.
OFF
GND
twisted pair
Monitor 2~26 inverter wire diagram
48
49
Booting and shutdown of the inverter 9
About the RS485 connector and the connection, you can go back to the section 5.8
for details. The above figure shows the diagram of monitoring inverters with
ShineWeBox. Generally, the maximum number of the inverter is 26.
· In general, when using the RS485, every inverter must have
different com address. You can go back to the section 8.1.1.2 b for
details.
9.1 Display and message
· Make sure the Growatt TL3-US has connected DC and AC
conductor cables correctly according to the wiring diagram of
section 5.7.2.
· Under any condition! Make sure the maximum open circuit
WARNING voltage (Voc) of each PV string is less than 1000VDC;the AC string
is less than 300Vac.
More information about the ShineWeBox go to the web:
Http://www.growatt.com
When the PV input voltage is above 200V, the Growatt TL3-US can be powered on.
Turn the DC rotary switch from the off position “O” to the on position “I” as
shown in 8.2.
2) Monitor the inverters with External wireless.
The text line of the LCD must display the information as shown below in proper
sequence:
SN:XXXXXXXXX
Model:GT00X0XXXX
Shinepano
ON
1
2
Wireless
33000 TL3-US
FW:XXX.X-XX.X
The figure shows the wiring schematic of monitoring inverters with Zigbee and
SinePano. Generally, the maximum number of the inverters is 15. The
communication distance between the Zigbee and the ShinePano is 984 feet in the
open space.
The display will then cycle and the text line will display the information below
the LED will turn to red:
No AC Connection
· About the External Wireless section, you can go back to the
section 6.1.1.2 c for details.
In order to connect to AC grid you must turn on AC disconnect.
More information about the Zigbee and ShinePano go to the web:
Http://www.growatt.com
Once the Growatt TL3-US is operating in a normal status, before it’s connected to
the grid, it will take 60 seconds to check the inverter including the GFCI
automatically.
The LCD text line's information display as below:
Connect in 60s
50
51
Cleaning and maintainence 10
When it counts to 0s, the inverter attempts to connect to the grid. Once it
outputs power to the grid successfully, the text line in the LCD will display as
shown below:
10.1 Checking the inverter
Ask the installer to check for correct inverter operation at regular intervals.
Check whether there is any externally visible damage to the inverter.
Connect OK !
The LED will light green.
Booting the Growatt TL3-US successfully!
9.2 Turn off the Growatt TL3-US
If there is any externally visible damage to the inverter, contact the installer.
10.2 Checking the DC & AC disconnect switch
Once a year, turn the rotary switch from the "ON" position to the "OFF"
position 5 times in succession. This cleans the contacts of the rotary switch and
prolongs the electrical lifespan of the DC & AC Disconnect.
Turn the DC rotary switch from the ON position “I” to the OFF position “O” as
shown below.
Wait until the text line of the LCD displays as shown below:
PV Power Low
10.3 Cleaning the Inverter
If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using
only clean water and a cloth. Do not use any cleaning agents (e.g. solvents or
abrasives).
The LED will light red.
Iin this state, it is working in a standby, isolated from the DC power.
Turn off the AC connector until the LCD and the LED are powered off (NO
DISPLAY).
·Before any operation, please disconnect the DC switch and AC
switch, and wait for at least 10 min until the internal bus
capacitance discharge completely.
Shutdown the Growatt TL3-US successfully!
·For safety, do not open wire box until 20 minutes passed.
52
53
10.4 Cleaning the Fan Guards
Remove the screws inside the fan guards as shown below.
Check the fan guards are to ensure they are not dusty or dirt-clogged.
If the fan guards are dusty, clean them using a vacuum cleaner.
· Before any operation, please disconnect the DC switch and
AC switch, and wait for at least 10 min until the internal bus
capacitance discharge completely.
DANGER
10.5 Fan Replacement
DANGER
Remove the fans from the fan guards.
· It must be carried out by qualified, trained personnel and
incompliance with all prevailing local codes and regulations.
Before any operation, please disconnect the DC switch and AC
switch, and wait for at least 10 min until the internal bus
capacitance discharge completely.
Remove the screws on the fan guards as shown below.
Replace a new fan.
10.6 Fuse replacement
It must be carried out by qualified, trained personnel and in
compliance with all prevailing local codes and regulations.
Disconnect the wire connector of the fans using a flat head screwdriver as
shown below.
Before any operation, please disconnect the DC switch and AC
switch, and waiting for at least 10 min until the internal bus
capacitance discharge completely.
Open the wire box carefully.
Disconnect the DC switch and AC switch, and waiting for at least 10 min.
Check the broken fuse and remove it carefully.
54
55
Decommissioning 11
11.1 Dismantling the Growatt TL3-US
1) Disconnect the DC switch and AC switch;
2) Pull down the screws between the Growatt TL3-US and the wire box;
3) Taking the Growatt TL3-US, change a new one;
4) lock the screw between the Growatt TL3-US and the wire box;
Replace a new one.
5) Restart the DC Switch and the AC Swtich;
The Growatt TL3-US may fall down due if inappropriately disassembled.
Contusions or bone fractures due to the heavy weight of the Growatt TL3-US.
· Prior to disassembling the Growatt TL3-US, take its weight
of 110.2 lb. (50 kg) into account of the Growatt 33000TL3-US.
·Use suitable lifting technique when disassembling.
WARNING
·Before any operation, please disconnect the DC switch and
AC switch, and wait for at least 10 min until the internal bus
capacitance discharge completely.
Close the wire box.
Replace new fuse.
DANGER
10.7 Inverter replacement
6) It is recommended to use a drill with hex bit for installation ease.
· Before any operation, please disconnect the DC switch and
AC switch, and wait for at least 10 min until the internal bus
capacitance discharge completely.
2
1
Inverter has major irreversible damage or failure. For replacement of the host, the
operation is as follows; the inverter can be the host and can be removed from
terminal wire box when replacing the inverter to avoid having to disconnect and
reconnect all DC conductors.
3
4
INFORMATION
When the new inverter “host” replacement has been received, remove the
protection cover, the new inverter “host” docking with the wirebox.
56
Linked with Mounting
bracket and Inverter(Left)
2
Linked with Mounting
bracket and Inverter(Right)
3
Linked with Inverter
and Wirebox(Left)
4
Linked with Inverter
and Wirebox(right)
5
Linked with Inverter
and Wirebox(Left bottom)
6
Linked with Inverter
and Wirebox(Right bottom)
5
DANGER
· About the wire box and the Growatt TL3-US and how to
separate, please refer to section 11.1 for more details.
1
6
Socket head screw position
7) Using a crane to hold up the Growatt TL3-US carefully by the rings, to assist in
separating the Growatt TL3-US and the wire box.
57
Trouble Shooting 12
Normally grounded conductors may be ungrounded and
energized when a PV Isolation Low is indicated.
· Risk of electric shock.
· Test before touching.
DANGER
The Growatt TL3-US
Upward
The Wirebox
installation location
8) The wire box after removal of the Growatt TL3-US “host” will require the protective
cover to be installed for protection from harsh elements, pleas install protection
cover using lock screw as shown below.
4
2
3
· Work on the Growatt TL3-US must be carried out by qualified
personnel.
The system status is identified through warning or error signals displayed on the
LCD display and the LED. The following tables briefly describe the two types of
signals which may be displayed.
12.1 Warnings(W)
Warnings (W) identify the current status of the Growatt TL3-US. Warnings do not
relate to a fault and it does not affect the normal running of the Growatt TL3-US.
When a (W) with a number after it appears in the display, it indicates a Warning
Code and is usually cleared through an orderly shutdown/re-set or a selfcorrective action performed by the inverter.
See the (W) codes in the following table.
1
1
WireBox
2
Production Cover
3
Quick Connect Terminal
4
M4*6 Screws
Warning message
Description
Suggestion
Warning 100
The problem of fan(s)
See Note1 below the chart
Warning 101
Not choose the PID model
Contact Growatt
Warning 102
Not choose the string model
Contact Growatt
Warning 103
Reading EEPROM fail
Restart inverter
Warning 104
DSP and COM firmware
version unmatch
Contact Growatt
If you want to store the inverter in your warehouse, you should choose an
appropriate location to store the inverter.
Warning 105
Writing EEPROM fail
Restart inverter
The unit must be stored in original package and desiccant must be left in the
package to absorb any excess moisture.The storage temperature should be
always between − 40°F (− 40°C) and +140°F( + 60°C). And the storage relative
humidity should be always between 0 and 95%.
Warning 106
The problem of SPD
Contact Growatt
Install protection cover
11.2 Packaging the Growatt TL3-US
Pack the Growatt TL3-US. Use the original packaging or packaging that is suitable
for the weight and dimensions of the inverter for safe return shipping.
11.3 storage of inverter.
If there are a batch of inverters that require storage, the maximum stack height for
original carton is four.
After long term storage, local installer or service department of GROWATT should
perform a comprehensive test before installation.
Warning 108
Warning 109
StrUnusaul/Warning
StrFuseOpen Warning
11.4 Disposal
Dispose of the Growatt TL3-US in accordance with the disposal regulations for
electronic waste that apply at the installation site.
58
PID Warning
PV is short
Contact Growatt
BOOST drive abnormal
Contact Growatt
String current is not even/
Solar panel is unmatch
Contact Growatt
Fuse is damage
Contact Growatt
PID Warning
Contact Growatt
If the suggestions do not work, please contact to the Growatt.
Note 1: The Growatt TL3-US has three fans (one internal and two outside).
59
Error 112
AFCI test fail,
System PV circuitry exist Arc
Contact Growatt
Error 114
AFCI self-checking fail
Contact Growatt
WARNING: FAN 2
Error 117
Inverter relay fault
Contact Growatt
/
Error 121
Internal communication with slave
failed
Contact Growatt
Error 122
Internal bus over/under voltage.
Contact Growatt
StrReverse
Error
The grid is not connected to the
inverter
StrShort
Error
PV Insulation value is outrange
No AC
Connection
The grid is not connected to the
inverter
So, if the internal fan has Error, you should contact Growatt to replace the internal
fan, do not replace it by yourself!
PV Isolation
Low
PV Insulation value is outrange
Contact Growatt
If the outside fan(s) has problems, connect to the supplier or Growatt to replace by
qualified personnel.
Residual I
High
Redundant current is outrange
Contact Growatt
Output high
DCI
Output current DC bias is high
Contact Growatt
Errors (E) codes identify a possible equipment failure, fault or incorrect inverter
setting or configuration.
PV Voltage
High
PV input voltage is above 1000V
Check the solar panel
configuration and wiring
Any and all attempts to correct or clear a fault must be performed by qualified
personnel.
AC V
Outrange
The grid voltage is outrange
Check the grid voltage
by the LCD
AC F
Outrange
The grid frequency is outrange
Check the grid frequency
by the LCD
PV SW Set
Error
PV module set wrong
Check PV wiring and
refer to chart6:
PV MODULE SETTING
Growatt 33000TL3-US/36000TL3-US/40000TL3-US
Internal
Fan
Outside A
WARNING: FAN 1
WARNING: FAN 3
Outside B
WARNING: FAN 1,3
Fault Message
of LCD show
WARNING: FAN 1,2
/
WARNING: FAN 2,3
/
WARNING: FAN 2,3
WARNING: FAN 1,2,3
Once the internal fan of Growatt TL3-US has Error, the inverter can still operate; if
the outside fan(s) has Error(s), the inverter can still operate, but the power it feeds
back to the grid is limited to the temperature itself.
12.2 Errors(E)
Check the grid break
Contact Growatt
Check the grid break
Typically, the (E) code can be cleared once the cause or fault is removed.
Some of the (E) code Error as table shows below, may indicate a fatal error and
require you to contact the supplier or Growatt for replacement.
Error code
60
Meanings
Suggestion
Error 101
Internal communication with host failed Contact Growatt
Error 106
Redundant sample circuit of
Insulation values are different
Contact Growatt
Error 107
Redundant sample circuit of
GFCI values are different
Contact Growatt
Error 108
Internal power test fail
Contact Growatt
Error 111
IGBT drive fault
Contact Growatt
61
13 Specification
Specification of the Growatt TL3-US
Model
Specifications
Information
· If the input current supplied by the photovoltaic field
connected to the inverter is above the maximum usable value
and the input voltage is within the allowed range, the inverter
will not be damaged and still work normally.
Model
33000TL3-US
36000TL3-US
33000TL3US
36000TL3-US
40000TL3-US
Output data(AC)
Nominal output power
33000W/366
60VA
36000W/40000
VA
40000W/40000
VA
Nominal AC voltage
480V
480V
480V
AC voltage range
422-528VAC
422-528VAC
422-528VAC
Nominal AC grid frequency
60 Hz
60 Hz
60 Hz
AC grid frequency range
59.3-60.5 Hz
59.3-60.5 Hz
59.3-60.5 Hz
Max. output current
( cos φ=1)
44A
48A
48A
40000TL3-US
Specifications
Input data(DC)
Max. recommend PV
power
41250W
Max. DC power
33700W
367500W
40800W
Max. DC voltage
1000V
1000V
1000V
Start voltage
250V
250V
250V
Harmonics
<3%
<3%
<3%
DC nominal voltage
695V
695V
695V
Grid connection type
3/N/E
3/N/E
3/N/E
PV voltage range
200V-1000V
200V-1000V
200V-1000V
MPP voltage range
(Full load)
480-800V
520-800V
570-800V
Max. input current of the
MPP tracker A/tracker B
36A/36A
36A/36A
36A/36A
Max. input short circuit
current
50000 W
Power factor (cos φ)
> 0.99
> 0.99
0.8LG - 0.8LD (0.9LG - 0.8LG - 0.8LD (0.9LG 0.9LD at full power)
0.9LD at full power)
>0.99
0.8LG - 0.8LD
Efficiency
Max efficiency
98.80%
98.80%
98.80%
CEC-Weighted Efficiency
98.50%
98.50%
98.50%
MPPT efficiency
99.50%
99.50%
99.50%
45A/45A
45A/45A
45A/45A
trackers 2
2
2
DC reverse-polarity
protection
Yes
Yes
Yes
Max. number of parallel
strings
4
4
4
Input over voltage
protection
Class II
Class II
Class II
DC switch for each MPP
tracker
Yes
Yes
Yes
Number of MPP
62
45000 W
Protection devices
63
Model
33000TL3-US
36000TL3-US
Model
40000TL3-US
Specifications
33000TL3-US
Protection devices
40000TL3-US
General Data
AC switch
Yes
Yes
Yes
Cooling concept
Fan Cool
Fan Cool
Fan Cool
Arc detection(AFCI)
Yes
Yes
Yes
Enclosure rating
TYPE 3R
TYPE 3R
TYPE 3R
DC insulation measure
Yes
Yes
Yes
AC short circuit protection
Yes
Yes
Yes
Output over voltage
protection
Class II
Class II
Class II
String fuse type/size
15A/1000VDC
10*38mm
15A/1000VDC
10*38mm
15A/1000VDC
10*38mm
Features
Display
Graphic
Graphic
Graphic
InterfaceRS232/RS485/
Bluetooth/RF/Zigbee/Wi-Fi
yes/yes/opt/opt
/opt
yes/yes/opt/opt
/opt
yes/yes/opt/opt
/opt
Warranty:5years/
10years
yes/opt
yes/opt
yes/opt
General Data
Certificates and
approvals
64
36000TL3-US
Specifications
435*790*265m m
435*790*265m m
435*790*265m m
Dimensions(W*H*D)
17.1/31.1/10.4in
ch
17.1/31.1/10.4i
nch
17.1/31.1/10.4inc
h
Weight
50kg/110.2lb
50kg/110.2lb
50kg/110.2lb
Operation ambient
Temperature range
(Derating above
45°C/113°F)
–25°C ... +60°C
–13°F ... +140°F
(Derating above
45°C/113°F)
–25°C ... +60°C
–13°F ... +140°F
(Derating above
45°C/113°F)
–25°C ... +60°C
–13°F ... +140°F
(Derating above
45°C/113°F)
Noise emission
≤50dB(A)
≤50dB(A)
≤50dB(A)
Relative Humidity
0~100%
0~100%
0~100%
Altitude
≤2000m/6560ft
≤2000m/6560ft
≤2000m/6560ft
Self-Consumption
night
< 6 W(AC Power
Supply)
< 6 W(AC
Power Supply)
< 6 W(AC Power
Supply)
Topology
Transformerless
Transformerless
Transformerless
UL1741,UL1998,UL 508C,IEEE1547,FCC part 15(class B),
CSA C22.2 No.107.1,CSA C22.2 NO.14
DC Switch information
DC operating voltage
range
1000V
1000V
1000V
Maximum DC operating
current
36A per MPPT
36A per MPPT
36A per MPPT
Maximum DC shortcircuit current
36A per MPPT
36A per MPPT
36A per MPPT
AC Switch Information
AC operating voltage
range
690V
690V
690V
Maximum AC operating
current
80A
80A
80A
Short-circuit rating
Max. fuse
100A
100A
100A
65
Spare Parts and Accessories 14
If needed, you can order these from Growatt specialty retailer.
Model
33000TL3-US
36000TL3-US
40000TL3-US
Specifications
Tripping Limits and Tripping Times
Tripping limit
> 60.5Hz / <59.3 Hz
Tripping frequencies
60.45 Hz to 60.55 Hz / 59.28 Hz to 59.40 Hz
Tripping times
Max. 0.150 s / Max. 0.150 s
Tripping limit
50% / 88% / 110% / 120%
Tripping times
Max.0.16s / Max.2.00s / Max.1.00s / Max.0.16s
Nominal
frequency
60 Hz
Nomina l
Voltage
277 V
Tripping limit: ±2 % of nominal grid voltage
Tripping times: ±0.1 % of nominal trip time
Tripping frequencies: ±0.1 % of nominal
frequency
Accuracy
Name
Description
Growatt order number
Fans
Internal or External fans of
the Growatt TL-US
Growatt TL-US Fan
ShineWebox
Communication data logger
ShineWebox
ShinePano
Communication data logger
ShinePano
Zigbee
Communication interface
Zigbee
Growatt TL3-US Plug
Wire box Plug
Model
33000TL3-US
36000TL3-US
40000TL3-US
Specifications
Torque Values and Conductor Sizes
DC terminal
1.2Nm (10.6lbf.in)
#12~#8AWG(3.31~8.37mm2)
221°F(105°C) for each pole
AC terminal
2.0N.m (17.7lbf.in)
#8~#4AWG(8.37~21.15mm2)
221°F(105°C) for each pole
Attachment to the wall
mounting bracket
44 in-lb.(5 Nm)
safety-lock screws
53 in-lb.(6
Nm)
53 in-lb.(6 Nm)
53 in-lb.(6
Nm)
Wire box enclosure lid
53 in-lb.(6
Nm)
53 in-lb.(6 Nm)
53 in-lb.(6
Nm)
Fuse
SPD
DC input fuse of Growatt TL3-US
SPD of Growatt TL3-US
Growatt TL3-US Fuse
Growatt TL3-US SPD
*see National Electrical Code®, 310.16
66
67
15 Inverter installation plan
15.1 Single inverter
AC
Current BUSBar1
PV+ PV- PV+PV-
MPPTA
Web box
AC
DC
1~n
PV+ PV- PV+PV-
Growatt TL3-US
AC
DC
Growatt TL3-US
AC
1~n
DC
PV+ PV- PV+ PV-
PV+ PV- PV+ PV-
MPPTB
MPPTA
Note: The schematic only showed the Growatt TL3-US
68
Growatt TL3-US
PV-
AC
PV+
DC
PV-
Growatt TL3-US
PV+
Current BUSBar N
Web box
DC
Gr owatt TL 3-US
AC Dsiconnect
Transformer
Power meter
15.2 Multi inverter
MPPTB
MPPTA
MPPTB
MPPTA
MPPTB
MPPTA
MPPTB
Note: The schematic only showed the Growatt TL3-US
69
Contact 16
Growatt 33000 TL3-US default mode DC connection
If you have technical problems concerning our products, contact your installer or
Growatt. In order for better support, please provide information below:
Inverter type
Serial number of Inverters
Error code of Inverters
Display of inverters
Modules information
ON
Communication method
2
1
OFF
SHENZHEN GROWATT NEW ENERGY TECHNOLOGY CO.,LTD
PVA
70
Building B, Jiayu Industrial Park , #28, GuangHui Road, Shiyan Street,
Baoan District, Shenzhen, P.R.China
T 0755-29515888
F 0755-27472131
E ser vice@ginverter.com
W www.ginverter.com
ARRAY 2
ARRAY 1
GET
PVB
71