Professional fire detection systems are expected to provide more than reliable fire detection and signaling alarms to the fire department. Over time, the continuous progress in
technical units has led to many improvements in monitoring and control systems. At the
same time the specifications of the European standards are becoming more and more
demanding. These complex requirements towards control and monitoring of individual
parts of a unit was reason enough to redesign our assortment of esserbus transponders.
Essentially the new assortment consists of the so-called "alarm transponder" which is used
for both the connection of non-addressable detectors (point-type detectors, manual
detectors and special detectors) as well as for the operation of conventional alarm
signaling devices (signaling devices, signal flasher and combination alarm signaling
devices). Monitoring of the lines in accordance with the latest standards is ensured via
"EOL modules" (end-of-line modules).
The second part is formed by the "FCT" (fire control transponder) and the IQ8TAL being
loop-powered input and output transponders with a contact input and a floating relay
output for monitoring of contacts and transmission of technical alarms for equipment
monitoring.
These modules are for interfacing to other disciplines which are not a part of the fire detection system itself. Thanks to their intelligent concept they significantly expand the range of
monitoring and control functions as part of the building management.
esserbus transponders need ONLY ONE loop address per device.
3OHDVHEHUHIHUUHGWRWKHFRPSDELOLW\OLVWWREHGRZQORDGHGIURP
RXUUHVWULFWHGZHEVLWHDUHD
808600.230
esserbus transponder FCT Set 230 V
Approval:
Features
• 230 V AC operation with optional function monit•
•
•
•
•
•
•
•
oring
Comprehensive fail-safe function during failure of
the loop or mains voltage
Freely programmable relays
Monitoring contacts for monitoring of external
devices
Time-dependent control of relay outputs
Optional: relay outputs with programmable
impulse lengths
Reduction of amount of data via selectable software function
Integrated loop isolator
Optional IP protection base for usage in difficult
ambient conditions
VdS
The FCT is used for the monitoring and operation of fire control systems such as ventilation, pressure monitor pumps, extinguishing agent sprinklers, elevators and many more.
Time-dependent machine shutdowns can be carried out via two freely programmable
relays. The pluggable modules (up to two modules can be connected) are each equipped
with a contact input for operational feedback.
The comprehensive "fail-safe" function ensures that the transponder maintains full functionality and remains a self-sufficient activation device even if the fire alarm control panel
or field bus fails.
Using the 230 V version the mains voltage can be switched directly and be simultaneously
used to power the transponder. It is also possible to indirectly monitor the function of the
mains voltage using internal logic.
The FCT essentially requires an external voltage supply. For the operation on 12 V DC the
optional voltage converter (Part No. 781336) is required.
The esserbus transponder FCT 12-24 V or 230 V is used as a loop device for the IQ8Control or FlexES control fire alarm control panels. The tools 8000 programming software (as
of version V1.15.1) is necessary for the start-up.
Technical Data
Rated voltage
Rated frequency
Rated current
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Type of protection
CE certificate
- FCT control module
- 1x FCT electronic module
- surface mounted housing
www.esser-systems.com
230 V AC
50 ... 60 Hz
0.01 A
30 V DC/4 A, 230 V AC/4 A
max. 2,5 mm²
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30 (in housing)
IP55 (with IP-base composition 788655)
0786-CPD-20991
Transponders
esserbus
esserbus transponder FCT Set 12 - 24 V
808600.24
Approval:
1
VdS
As 808600.230, but 24 V operating voltage.
2
Technical Data
Rated voltage
Operating voltage
Rated frequency
Rated current
Contact load relay
Connection terminal
Ambient temperature
Storage temperature
Type of protection
CE certificate
10 ... 30 V DC / 10 ... 24 V AC
10 ... 30 V DC
50 ... 60 Hz
0.2 A
30 V DC/4 A, 230 V AC/4 A
max. 2,5 mm²
-5 °C ... 45 °C
-10 °C ... 50 °C
IP30 (in housing)
IP55 (with IP-base composition 788655)
0786-CPD-20991
3
4
5
IP base adapter for FCT
788655
IP FCT base adapter for extreme environmental conditions.
6
Technical Data
Type of protection
IP 55
7
8
9
IQ8FCT electronic module
804981
Pluggable electronic module for FCT expansion with another monitoring contact input.
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current
No. of detector/zone
Operation indicator
Alarm display
Connection terminal
8 ... 42 V DC
approx. 45 μA
approx. 9 mA
max. 127 per loop
green LED
red LED
max. 2,5 mm² (AWG 26-14)
IQ8TAL electronic module
804980
10
11
12
13
As 804981 but with TAL functionality (1 input / 1 output)
14
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Alarm current
No. of detector/zone
Operation indicator
Alarm display
Connection terminal
8 ... 42 V DC
approx. 45 μA
approx. 9 mA
max. 127 per loop
green LED
red LED
max. 2,5 mm² (AWG 26-14)
15
16
17
Transponders
808623
¬qw8/
esserbus
esserbus Alarm transponder 4 IN/2 OUT
Approval:
Features
• Conventional connection of standard fire detectors
and signaling devices
• Loop monitoring in compliance with EN 54-13
• Integrated line insolator
• Programmable relay outputs
• Programmable relay reset function
• Max. 100 transponders per fire alarm control
panel
• Max. 31 transponders per loop
• Max. 127 detector zones per loop
• Detector numbers per zone input of the
•
•
•
•
•
transponder:
Max. 30 conventional detectors (without SOC)
Max. 10 conventional detectors (with SOC)
Max. 10 Manual call points
Max. 10 Technical Alarm Modules (TAM)
Max. 5 audible alarm device (observe calculation
table in tools 8000)
VdS
The esserbus transponder functions as a device on the multifunctional primary line. The
connection of four zones with automatic standard detectors, manual call points (nonaddressable) or as well as special detectors is possible. In addition, two programmable
relay outputs are also available.
Both relay outputs of the transponder may be used to reset a connected third-party
detector. The reset function relates to the corresponding special detector, e.g. by switching
the appropriate input to GND or by a short interruption of the detectors supply voltage.
Therefore the control mode >Reset-Relay< as well as the desired relay operation mode
(normally closed or open) must be configured with the programming software tools 8000
from V1.15 and above. The relay output will be activated for the selected reset time (1 to
14 seconds) if the assigned input (G1 for relay 1 / G2 for relay 2) of the transponder is
reset. Refer to the detectors manual for the required reset time.
Monitoring via the EOL terminating devices (part no. 808624/808626) is required for the
connection of fire detectors and for the controlling of alarm signaling devices. The
enclosed resistors can be used to connect the floating contacts.
The esserbus alarm transponder requires an external voltage supply. An optional Voltage
Converter (part no. 781336) is also required for 12V DC operation. The esserbus alarm
transponder external voltage supply can be monitored during operation.
The EOL-I terminating device (part no. 808626) is to be used for standard-compliant
monitoring of detector zone inputs. The EOL-O (part no. 808624) is to be used for
standard-compliant monitoring of connected alarm signaling devices.
Technical Data
Rated voltage
Operating voltage
Quiescent current @ 12 V DC
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
CE certificate
Dimensions
8 V DC, max. 42 V DC
10 ... 28 V DC
approx. 12 mA
max. 120 mA @ 12 V DC
30 V DC / 1 A
10 °C ... 50 °C
25 °C ... 75 °C
IP 40 (in housing)
approx. 28 g
0786-CPD-20947
W: 82 mm H: 72 mm D: 20 mm
Installation Accessory Pack
Accessories
¬qw92
808624
Features
• Used for monitoring of control outputs with
conventional alarm signaling devices being
connected
• Additionally recognizes creeping interruptions and
short-circuits
• Loop monitoring in compliance with EN 54-13
www.esser-systems.com
788603.10
788600
788650.10
788601
788651.10
788612
781336
808624
808626
Module housing for snap-on mounting rail
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
Loop isolator for transponder
DC/DC converter output voltage
EOL-O Terminating Device
EOL-I Terminating Device
EOL-O Terminating Device
The EOL-O terminating device is mounted on the last control input device in the detector
zone and is used to monitor alarm signaling devices.
Transponders
¬qw;8
808626
esserbus
1
EOL-I Terminating Device
The EOL-I terminating device is mounted on the last device in the detector zone and is
used to monitor detector zone inputs.
2
3
Features
• Used for monitoring of detector zone inputs with
standard fire detectors being connected
4
• Additionally recognizes creeping interruptions and
short-circuits
¬qw+§/21J
• Loop monitoring in compliance with EN 54-13
808610.10
5
esserbus transponder 12 relays (8bit)
Approval:
Features
• Max. 100 transponders per fire alarm control
panel
• Max. 32 transponders per analog loop
• Max. 32 transponders per detector zone
VdS, CNBOP, BOSEC
The esserbus transponder works as a loop device on the multi-functional primary line.
With the 12 relays module, it is possible to expand the number of exits per control unit.
Depending on the control unit, it can be integrated or used with fire detectors in mixed
operation. The esserbus transponder can be optionally extended by adding the additional
isolator board 788612. esserbus transponder voltage supply: via the multi-functional
primary line. The esserbus transponder can be wired with an external switching voltage of
12V DC or 24V DC for the K1 to K12 relays. The external voltage supply of the transponder
can be programmed to be monitored in the customer data in the operating mode. In the
“floating” operating mode, no external switching voltage of the relays is necessary. 11
relays are freely programmable. The maximum line length from the transponder to the
external device is up to 1000 m.
6
7
8
9
Technical Data
Operating voltage
External power supply
Current consumption @ 12 V DC
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
10 ... 28 V DC
approx. 3 mA
30 V DC / 1 A (max. 3 A each transponder)
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 110 g
W: 150 mm H: 82 mm D: 20 mm
10
11
Accessories
12
788612
788600
788650.10
788601
788651.10
13
Loop isolator PCB
Surface mounting housing grey, similar to RAL 7035
Surface mounting housing white, similar to RAL 9003
Flush mounting housing grey, similar to RAL 7035
Flush mounting housing white, similar to RAL 9003
14
15
16
17
Transponders
808611.10
¬qw,§/21M
esserbus
esserbus transponder 32 LED
Approval:
VdS, CNBOP, BOSEC
The esserbus transponder works as a loop device on the multi-functional primary line. 32
outputs for direct LED control (e.g. indicator) are found on this esserbus transponder
module. There is one terminal screw per output on the switching mechanism. The module
can be extended by adding the additional isolator board 788612. esserbus transponder
voltage supply: via the multi-functional primary line. The esserbus transponder requires an
external switching voltage of 10 V DC to 15 V DC.
The external voltage supply of the transponder can be programmed to be monitored in
operating mode. The maximum line length from the transponder to the external device is
up to 100 m.
Features
• Max. 100 transponders per fire alarm control
panel
• Max. 32 transponders per analog loop
• Max. 32 transponders per detector zone
Technical Data
Operating voltage
Quiescent current @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 3 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 95 g
W: 150 mm H: 820 mm D: 20 mm
Accessories
¬qw.§/21S
808613.10
788612
788600
788650.10
788601
788651.10
Loop isolator PCB
Surface mounting housing grey, similar to RAL 7035
Surface mounting housing white, similar to RAL 9003
Flush mounting housing grey, similar to RAL 7035
Flush mounting housing white, similar to RAL 9003
esserbus transponder 4 IN / 2 OUT
Approval:
The esserbus transponder works as a loop device on the multifunctional loop.
Conventional automatic detectors and manual alarm units can be connected without
addressing.
This transponder provides four monitored inputs to connect dry contacts
(e.g. for technical alarms, pressure controller, elevator controls etc.).
Two dry relay outputs are available for control or reset functions.
The esserbus transponder needs an external switching voltage of 12 V DC or 24 V DC. The
external voltage supply of the transponders can be programmed with supervision in operating mode.
Features
•
•
•
•
Technical Data
Up to 31 esserbus transponders 4 zones / 2 relays
on one multifunctional primary loop
Max. 100 transponders per fire alarm control
panel
Max. 31 transponders per analog loop
Max. 127 detector zones per analog loop
• Detector numbers per zone input of the
transponder:
• Max. 20 conventional detectors (without SOC)
• Max. 10 conventional detectors (with SOC)
• Max. 10 Manual call points
• Max. 10 Technical Alarm Modules (TAM/TAL)
808621
www.esser-systems.com
VdS, CNBOP, BOSEC
¬qw6)
Operating voltage
Quiescent current @ 12 V DC
Current consumption @ 12 V DC
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 6 mA
approx. 120 mA
30 V DC / 1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
Equipment pack with 1k, 10k and 4k7 terminating resistor
Accessories
788603.10
788612
788600
788650.10
788601
788651.10
Module housing for C-mounting bar or top hat rail mounting
Loop isolator PCB
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
esserbus Transponder 4 IN / 2 OUT - Esser, Dutch
Transponders
772384
¬n8ue
esserbus
esserbus Transponder 4E 2S 808613.F0 with housing - ESSER,
French
1
2
3
¬qw/§/21V
808614.10
4
esserbus transponder 1 IN
Approval:
VdS, CNBOP, BOSEC
The esserbus transponder works as a lbus device on the multifunctional loop.
Conventional automatic detectors and manual alarm units can be connected without
addressing:
- up to 30 conventional detectors per zone without SOC
- up to 10 conventional detectors per zone with SOC
- up to 10 non-automatic or technical alarm devices per zone
5
6
7
External power supply is required for transponder operation. Optional voltage monitoring.
Features
Technical Data
• Max. 100 transponders per fire alarm control
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
panel
• Max. 31 transponders per analog loop
• Max. 32 transponders per detector zone
• Detector numbers per input of the transponder:
• Max. 10 Technical Alarm Modules (TAM)
8
19 ... 42 V DC
approx. 3 mA
max 120 mA
30 V DC/1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
9
10
Plug terminals are included
Accessories
¬qw0~
808615
11
788603.10 Module housing for C-mounting bar or top hat rail mounting
788612
Loop isolator PCB
esserbus communication transponder
With this esserbus transponder the extinguishing relay output 8010 can be integrated on
the bus of panel 8000 or IQ8Control, thus enabling several extinguishing zones to be
networked with each other. On each bus, a maximum of eight 8010 extinguishing relay
outputs can be operated and respectively a maximum of 16 communication transponder
per FACP8000 C/M or IQ8Control. All indicators and controls can be activated from the fire
alarm panel. The communication transponder occupies one address on the esserbus.
12
13
14
Technical Data
Features
• Max. 8 communication transponders per loop
Operating voltage
Quiescent current @ 12 V DC
Current consumption @ 12 V DC
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 3 mA
approx. 28 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 28 g
W: 72 mm H: 65 mm D: 20 mm
Mounting: in the housing of the 8010 extinguishing realy output
15
16
17
including loop isolator PCB (788612)
Transponders
808613.30
¬qw.§/41_
esserbus
esserbus transponder SST
Approval:
VdS
The esserbus transponder SIE is designed for operation as Standard Interface Extinguishing (SIE) for the analog loop (esserbus / esserbus-PLus) of the Fire Alarm System
8000 and IQ8Control.
An external switching voltage of 12 V DC or 24 V DC can be connected to the esserbus
transponder. The voltage converter (part no. 781336) is required for 12 V DC operation.
The transponder’s external voltage supply can be programmed with supervision in operating mode.
Technical Data
Features
• Max. 100 transponders per fire alarm control
panel
• Max. 31 transponders per analog loop
• Max. 127 detector zones per analog loop
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
19 ... 42 V DC
approx. 10 mA
max. 120 mA
30 V DC/1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
1 x additional equipment pack with 3,3 k and 680 R terminating resistor for SST
Accessories
788603.10
788600
788650.10
788601
788651.10
788612
781336
www.esser-systems.com
Module housing for C-mounting bar or top hat rail mounting
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
Loop isolator PCB
DC/DC converter output voltage
Transponders
808619.10
¬qw4§/21e
esserbus
esserbus FSA transponder for fire doors
Approval:
VdS
The transponder is suitable for usage for various applications: in stand-alone operation or
on the esserbus. In esserbus operation, the Series 9200 automatic fire detectors and those
of the IQ8Quad family (see feautures for types) can be used as detectors in door arrester
systems (FSA). In FSA transponder loop operation, the door arrester system status is
indicated on the fire alarm control panel.
For stand-alone operation, detectors of the IQ8Quad family are supported without loop
isolator (see features for types).
Features
For operation, the transponder requires an external supply voltage. It is possible to monitor
this voltage.
• Usage of series 9200 intelligent detectors (such
Technical Data
•
•
•
•
•
•
•
•
•
as OT, OTI, O²T detectors) as FSA detectors is
possible
Connection of IQ8Quad O detectors (Part no.
802371), TD Detectors (Part no. 802271), OT
detectors (Part no. 802373) and O²T detectors
(Part no. 802374) (DIBt-approved) as FSA
detectors is possible
FSA detectors programmable as devices in the
loop
Status indicator of door arrester system to the fire
alarm control panel
Actuation of the locking device also via the automatic fire detectors in non-FSA operation
Stand-alone operation of the FSA transponders is
possible
Usage of IQ8Quad O detectors (Part no. 803371),
TD detectors (Part no. 803271) and O²T detectors
(Part no. 803374) in stand-alone operation of the
FSA transponders to the standard detector group
is possible
Max. 100 transponders per fire alarm control
panel
Max. 32 transponders per analog loop
Max. 127 detector zones per analog loop
Operating voltage
External power supply
Quiescent current @ 12 V DC
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
2
3
4
5
8 ... 42 V DC
10 ... 28 V DC
approx. 6 mA (from UB ext)
max. 28 mA (from UB ext)
max. 30 V DC/1 A or 48 V DC/0,5 A
-5 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 70 g
W: 72 mm H: 65 mm D: 20 mm (PC Board)
Corresponding connection examples for FSA transponder operation in stand-alone operation or
as a device in the fire detection System 8000 can be found in the chapter containing automatic
door release systems.
Accessories
788612
788603.10
788600
788650.10
788601
788651.10
808625
1
Loop isolator PCB
Module housing for C-mounting bar or top hat rail mounting
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
EOL-Z
6
7
8
9
10
11
• Detector numbers per zone input of the
transponder:
• Max. 30 conventional detectors (without SOC)
• Max. 10 conventional detectors (with SOC)
• Max. 10 Manual call points
• Max. 10 Technical Alarm Modules (TAM/TAL)
12
13
14
15
16
17
Transponders
808622
¬qw7,
esserbus
esserbus transponder 4 IN/2 OUT for UniVario
Approval:
VdS
The esserbus transponder works as a loop device on the multifunctional primary line.
Input transponder with 4 monitored contact inputs for the activation of detectors from the
UniVario family of products. Two floating relay contacts for controlling functions are additionally available.
Technical Data
Features
• Max. 100 transponders per fire alarm control
panel
• Max. 31 transponders per analog loop
• Max. 127 zones per analog loop
• Max. 1 UniVario detector per zone input of the
transponder
• Max. 4 UniVario detectors per transponder, therefore max. 2 UniVario detectors with LED remote
indicator
¬qw?§/21¨
808630.10
Operating voltage
Quiescent current
Current consumption
Contact load relay
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
2 x EOL-Z (part no. 808625)
Accessories
788612
788600
788650.10
788601
788651.10
Loop isolator PCB
Housing surface mount, grey
Housing surface mount, white
Housing flush mount, grey
Housing flush mount, white
Refurbishment zone transponder RZT 8000
Approval:
VdS
The refurbishment zone transponder is a stand-alone participant on the esserbus for the
fire alarm system 8000 and IQ8Control fire alarm control panels. Individual automatic fire
detectors and manual call points (conventional technology) from other manufacturers can
be connected to the 4 zone inputs. The voltage of all 4 zones can be configured to 24 V via
the internal DC/DC module. An additional reset module is not required to operate thirdparty detectors.
The two relay outputs are available for general control purposes.
Features
Programmable with the programming software tools 8000 Version V2.40 or higher.
• Output current max. 125 mA per detector zone
• Optional use of the extended functionality of the 4
Technical Data
•
•
•
•
•
•
•
•
19 ... 42 V DC
approx. 6 mA
max. 120 mA
30 V DC/1 A
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
approx. 28 g
W: 82 mm H: 72 mm D: 20 mm
zone / 2 relays transponder. The detector states
prealarm or detector malfunction may also be
displayed.
Variable reset delay of the detector zone (0 to 15
seconds)
The detector zones can be operated in 2-zone
dependency
Two relays with programmable operating modes
Programmable surveillance of the external DC
power supply
Max. 100 transponders per fire alarm control
panel
Max. 31 transponders per analog loop
Up to 31 different esserbus® transponders can be
grouped as one detector zone
Up to 1,000 different control zones (e.g. relays)
can be programmed in a System 8000 or IQ8Control fire alarm control panel with the programming
software tools 8000
www.esser-systems.com
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Weight
Dimensions
10.5 ... 13.8 V DC
max. 1250 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
approx. 150 g
W: 150 mm H: 82 mm D: 20 mm
Whether or not a connection is possible must be individually checked in advance by the technical
sales department.
Accessories
788612
788600
788601
788650.10
788651.10
Loop isolator PCB
Housing surface mount, grey
Housing flush mount, grey
Housing surface mount, white
Housing flush mount, white
Transponders
808631.10
¬[email protected]§/21"
esserbus
Refurbishment zone transponder (RZT) / 12V - ESSER
As 808630.10, but rated voltage is 12 V DC, not configurable.
2
Technical Data
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Weight
Dimensions
10.5 ... 13.8 V DC
max. 1250 mA
-10 °C ... 50 °C
-25 °C ... 75 °C
approx. 150 g
W: 150 mm H: 82 mm D: 20 mm
Accessories
¬oA[*
783258
788600
788650
788601
788651
788605
788602
788603
esserbus transponder housing aP grey
esserbus transponder housing aP white
esserbus transponder housing uP grey
esserbus transponder housing uP white
Installation kit
C-rail
Module housing
3
4
5
6
MD1L Transponder - ESSER, French
Approval:
7
NF-SSI
Transponder 1 remote control line in plastic box. 1 remote line and positioning control.
Technical Data
¬oA\-
783259
1
8
Application temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
-10 °C ... 50 °C
-20 °C ... 70 °C
IP 65
ABS
Gris clair, RAL 7035
W: 260 mm H: 355 mm D: 67 mm
MD2L Transponder -ESSER, French
Approval:
10
NF-SSI
Transponder 2 remote control line in plastic box. 2 remote line and positioning control.
9
11
Technical Data
¬oAZ'
783257
Application temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
12
13
MD4L Transponder - ESSER, French
Approval:
-10 °C ... 50 °C
-20 °C ... 70 °C
IP 65
ABS
Gris clair, RAL 7035
W: 260 mm H: 355 mm D: 67 mm
14
NF-SSI
Transponder 4 remote control lines in plastic box. 4 remote lines and positioning control.
15
Technical Data
Application temperature
Storage temperature
Type of protection
Housing
Color
Dimensions
-10 °C ... 50 °C
-20 °C ... 70 °C
IP 65
ABS
Gris clair, RAL 7035
W: 285 mm H: 355 mm D: 67 mm
16
17
Transponders
772388.10
¬n8y§/21L
esserbus
Refurbishment zone transponder RZT 8000 w. housing - ESSER,
French
Approval:
NF-SSI
L’organe intermédiaire RZT 8000 (4 entrées, 2 sorties) est raccordé sur esserbus® ou
esserbus-Plus® pour les équipements de contrôle et de signalisation IQ8Control ou ECS
800. Les détecteurs automatiques et les déclencheurs manuels (de technologie conventionnelle) peuvent être connectés sur les 4 entrées.
Technical Data
Features
• Raccordement de détecteurs de la série 1100
(Universal det)
Operating voltage
Ambient temperature
Storage temperature
Type of protection
Dimensions
10.5 ... 13.8 V DC
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40
W: 189 mm H: 131 mm D: 47 mm
Livré en boîtier
Accessories esserbus transponders
¬ow-s
788612
Loop isolator for transponders
Loop isolator PCB to be mounted on esserbus transponders. To isolate short circuit failure
and wire break on the loop.
Technical Data
¬qw:5
808625
www.esser-systems.com
Operating voltage
Current consumption
Ambient temperature
Storage temperature
Type of protection
Weight
Dimensions
6 V DC
3 μA
-20 °C ... 50 °C
-20 °C ... 75 °C
IP 50 (with housing)
approx. 10 g
W: 32 mm H: 20 mm D: 10 mm
EOL-Z Module for detector groups
Terminating device for the monitoring of standard-inputs when using esserbus transponders (Part no. 808613.20, 808622, 808619.10).
The zener diode is sealed in the housing of the end-of-line (EOL) module.
Transponders
esserbus
1
Technical Alarm Modules
¬qQfm
804869
IQ8TAM technical alarm module for snap-on mounting
Approval:
VdS
The technical alarm module IQ8TAM is a bus device of the fire alarm system 8000 for
recognition, transmission and individual display of technical alarms.
Each IQ8TAM includes an integrated loop isolator, which opens in case of loop short circuit
to isolate the part of the loop between two loop isolators. A single wire break does not
effect the loop and all devices remain in operation. The module does not require external
voltage supply, as voltage is supplied by the field bus.
Features
• Max. 127 IQ8TAMs per analog loop
2
A remote LED indicator (e.g. Part No. 781804, 781814 and 801824)
can be connected to the LED-/LED+ terminal. The max. cable
length to the connected remote indicator is up to 100 m!
An external, monitored contact can be connected to the S-/S+
terminal. In case of an activation of this contact, the address and
programmed additional text of the corresponding technical alarm
module IQ8TAM will be displayed. To monitor this contact an
optional monitoring module (Part No. 804870) is required. The
max. cable length to the connected module is up to 250 meter.
3
4
5
6
7
The IQ8TAM activation is latching. To reset the IQ8TAM either the FACP or the corresponding zone is reset.
8
Technical Data
9
Operating voltage
Alarm display
Connection terminal
Ambient temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
8 ... 42 V DC
LED, red
max. 1,5 mm²
-20 °C ... 70 °C
-30 °C ... 75 °C
IP 30
PA 66 - plastic
grey, similar to RAL 7035
approx. 87 g
W: 25 mm H: 112 mm D: 99 mm
The module can either be mounted in an appropriate installation position in the housing of the
fire alarm panel or, for example, on a C-rail of a switch cabinet. Each module can be individually
connected or cascaded directly snap-on or on side connector block.
10
11
12
incl. 4 screw clamps and 1 resistor
13
14
15
16
17
Transponders
804870
¬qQgp
esserbus
Alarm and monitoring module for IQ8TAM
An external, monitored contact can be connected to the terminals of the IQ8TAM technical
alarm module for C-rail mounting with part no. 804869. In case of contact activation, the
address and the programmed additional text of the corresponding IQ8TAM technical alarm
module will be displayed.
For contact monitoring, the alarm and monitoring module for IQ8TAM (part no. 804870) is
required.
10K
The max. cable length to the connected module must not exceed 250 meters!
1K
IQ8TAM, max. 250 m line length
Inside wiring diagram for alarm and monitoring module
www.esser-systems.com
e.g.
pressure controller
Transponders
804868
¬qQej
esserbus
Approval:
• One contact input and one floating relay output
• Voltage supply via the field bus
• Test and reset function
• Higher IP protection
• Programmable inverse monitoring functionality of
•
•
VdS
The IQ8TAL Technical Alarm Module is a full-fledged loop device of the IQ8Control fire
detection system and it facilitates the detection and forwarding of technical alarms.
the contact input (1k resistance latent/10k resistance fire)
Powered by the FACP
Total cable length of the external contact up to
500 m
Integrated loop isolator
Max. 127 transponder TAL electronic modules per
analog loop
2
The IQ8TAL is equipped with an integrated loop isolator, a contact input and a relay output.
The relay can be optionally configured as a normally-closed contact or as a normally-open
contact. The IQ8TAL does not need a separate voltage supply.
3
In order to increase the IP protection class, the optional IP protection kit (Part No. 704965)
can be used.
4
The functionality of the Technical Alarm Module can be tested with the included key and the
alarm status can be reset directly at the IQ8TAL.
Features
•
•
1
IQ8TAL Technical Alarm Module
5
Technical Data
Operating voltage
Quiescent current @ 19 V DC
Contact load relay
Operation indicator
Alarm display
Connection terminal
Application temperature
Storage temperature
Type of protection
Housing
Color
Weight
Dimensions
8 ... 42 V DC
approx. 45 μA
30 V DC/1 A
green LED
red LED
max. 2.5 mm² (AWG 26-14)
-20 °C ... 70 °C
-30 °C ... 75 °C
IP 43 (in housing)
IP 55 (with optional IP Kit 704965)
PC/ASA plastic
blue, similar to RAL 5015
approx. 110 g
W: 88 mm H: 88 mm D: 21 mm
W: 88 mm H: 88 mm D: 57 mm (with surface-mounted
housing)
6
7
8
9
Please note that for surface mounting the mount housing (part no. 704981) must be used.
Compatible with all IQ8 Control systems with firmware V3.08 and tools 8000 V1.14 or superior.
- 2 x 10 k (terminating), 1x 10 k pre-assembled, and the rest included as additional package
- 1 x 1 k (alarm),
- 1 x 6 k 8 (inverse operation)
10
11
Accessories
704965 MCP Cover for small housing, transparent
704981 Surface mount housing for small MCP, blue
12
804867
IQ8FCT fire control transponder
Approval:
VdS
13
Same as IQ8TAL 804868 but with additional FCT software functionality.
Technical Data
Storage temperature
Type of protection
Color
Weight
CE certificate
-30 °C ... 75 °C
IP 43 (in housing)
grey, similar to RAL 7035
approx. 110 g
0786 – CPD – 20792
14
15
Accessories
Features
• Runtime monitoring
• Monitoring 2 states with an input
• Steady or impulsive triggering of relay output
• Max. 127 transponder FCT electronic modules per
704965 MCP Cover for small housing, transparent
704985 Surface mount housing for small MCP, grey
16
17
analog loop
www.esser-systems.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement