Index: WMGBMIC5000
INSULATION RESISTANCE METER
MIC-5000
MIC-5000 tester is designed to measure insulation resistance of power cables, transformers, motors and other electrically powered devices. Additionally the device allows for measurement of AC and DC voltages. Input circuits of the measuring devices are electronically protected from overloading, e.g. due to incorrect connection to the circuit being tested or incorrect use of input terminals.
Sonel S.A. ul. Wokulskiego 11
58-100 Świdnica, PL tel. +48 74 85 83 860 fax +48 74 85 83 809
www.sonel.pl
Standard accessories of the meter MIC-5000:
- Ni-MH battery package 7,2V 3Ah
- test lead with banana plug; 1,8m; 5kV; red
- shielded test lead with banana plug; 1,8m; 5kV; black
- test lead with banana plug; 1,8m; 5kV; blue
- „crocodile” clip K04; 5kV; black
- „crocodile” clip K05; 5kV; red
- „crocodile” clip K05; 5kV; blue
- pin probe with banana connector - black
WAAKU05
WAPRZ1X8REBB
WAPRZ1X8BLBB
WAPRZ1X8BUBB
WAKROBL20K04
WAKRORE20K05
WAKROBU20K05
WASONBLOGB2
- pin probe with banana connector - red
- carrying case L1
- hanging stramps
- cable for battery charger
- RS-232 serial transmission cable
- operating manual
- calibration certificate issued
by calibration laboratory
Optional accessories of the meter MIC-5000:
- software for creation of documentation from
electrical measurements „SONEL PE4”
- software for creation drawings and diagrams
„SONEL Schematic” + „SONEL PE4”
WAPROPE4EN
WAPROPE4SEN
- AGT-16P (triple phase socket adapter)
- AGT-32P (triple phase socket adapter)
- AGT-63P (triple phase socket adapter)
- USB1.1/RS232 adaptor
- USB key for software
WASONREOGB2
WAFUTL1
WAPOZSZE1
WAPRZLAD230
WAPRZRS232
WAADAAGT16P
WAADAAGT32P
WAADAAGT63P
WAADAUSBRS232
WAADAKEY1
MIC-5000
The most important features of MIC-5000 are:
· Insulation resistance measurement :
- test voltage selection between 250...5000V in 50V intervals, or predefined
250, 500, 1000, 2500, 5000V,
on-line insulation resistance measurement or leakage current,
automatic discharge of tested object’s capacitance after measurement of insulation resistance,
- direct measurement of one or two absorption coefficients,
acoustic determination of 5 seconds time intervals that facilitates to take time characteristics during insulation resistance measurement,
- saving measured value of test voltages and selected times T1, T2 and T3 ranging from 1... 600 seconds for the measurements of one or two absorption coefficients (DAR, PI or Ab1, Ab2).
indicator of the actual test voltage value during a measurement,
protection against live objects.
· AC/DC voltage measurement in range 0...600V.
· Memory of 999 measurement results with an ability to transfer the data to a PC.
· Automatic selection of measurement ranges.
· Powered by rechargeable battery pack:
included with the device an external power supply for automatic battery charging to ensure prolonged battery life and optimal working conditions,
- battery status indicator.
· AUTO-OFF function.
· Meter meets the requirements of the standard EN 61557.
Insulation resistance measurement
· test voltage can be set in the range between 250V and 5000V with 50V intervals
the range between 1sec and 600sec with accuracy ± 1sec measurement range according to EN 61557-2: R
ISOmin
...5,0TΩ; R
ISOmin
=U
ISOnom
/1mA
Range Resolution Accuracy
0,0...999,9k Ω
1,000...9,999M Ω
10,00...99,99M Ω
100,0...999,9M Ω
1,000...9,999G Ω
10,00...99,99G Ω
0,1k
0,1M
0,01G
Ω
0,001M
0,01M
Ω
Ω
Ω
0,001G Ω
Ω
±(3% m.v. + 20 digits)
100,0...999,9G
1,000...5,000T
Ω
Ω
0,1G Ω
0,001T Ω
· for measurements of limited , .
Minimum insulation resistance measured without limited converter current
Test voltage Range
250V
500V
1000V
2500V
5000V
250k Ω
500k Ω
1,0M Ω
2,5M Ω
5,0M Ω
DC voltage measurement
Range
0...600V
Resolution
1V
Accuracy
±(3% m.v. + 2 digits)
Electric security :
- type of insulation double, according to EN 61010-1 and IEC 61557
- measurement category
- measurement category for terminals and circuit 5kV:
CAT III 600V acc. to EN 61010-1 interpolated III 5000V
- protection class acc. to EN 60529 IP54
Rated operational conditions:
- operating temperature
≥
-10...+50°C
-0...+10% of the set value
- voltage fluctuation due to temperature changes better than
- converter output current
0,2%/°C min. 1,0mA for rated test voltage
1,0...3,0mA for 2500V
- measurement rate
- quality standard
1,0...1,4mA for 5000V approx. 1 measure/second
ISO 9001
AC voltage measurement
50Hz (sinusoidal shape with harmonic contents < 2%)
Range Resolution
0...600V
1V
„m.v.” - measured value.
Leakage current reading
Range
0...I
pmax
Resolution depending on range
Accuracy
±(3% m.v. + 2 digits)
Accuracy
+
I pmax
- maximum converter current 1,2 ± 0,2 mA,
Other technical data :
- power supply
- power supply adaptor
- minimum measurement time 5kV/1mA according to
EN 61557 (5s/25s)
- time to auto-off:
- mode R /I
L
- other modes
Ni-MH battery pack
100...240V
5h or 600 measurements
300 seconds
R - displayed insulation resistance value
DR - resistance measurement defined for a particular measurement v.5