advertisement
3-way IR flame detector
• Functional monitoring to the highest European standards in accordance with EN 54
• High sensitivity for fire detection in accordance
with EN 54-10 class 1
• Individual detector configuration via integrated
DIL switch
• Integrated contamination control and functional
monitoring of sensors
• Robust design and high chemical resistance
• Protection class IP67
Customized detection
The industrial detectors from the
UniVario product range are used for detecting rapid flame development and temperature changes. With their robust design, metal housing and high
IP67 protection class, they are perfect for use under the harshest industrial conditions.
ponent (EOL-UV, Part No. 808626.10) the detectors are monitored in terms of power supply, proper functioning and line faults.
Even intermittent interruptions and short circuits in the form of transfer resistance on the line, due to the detector being connected incorrectly for example, are immediately detected and reported as faults to the fire alarm control panel.
Functional reliability through selfmonitoring
The detectors have an internal monitoring function which checks at regular intervals that the existing sensors are working properly without faults.
The optical windows of the UniVario flame detectors are also checked at regular interval for contaminations. To increase security against false alarms, fire-specific signals are digitally processed internally in the detectors. This significantly reduces the risk of an alarm being triggered during a lightning storm, for example.
Type B two-detector dependency
For fire monitoring and direct notification to the fire department, the esserbus transponder can be easily programmed for type B two-detector dependency
(previously two-zone dependency) via the ESSER tools 8000 programming and service software in accordance with DIN VDE 0833-2. This ensures that the fire department is only notified if at least two fire incidents are reported by the connected UniVario detectors.
Easy mounting via the base principle
The system is mounted following the proven base principle. The detectors are mounted to the base using the supplied Allen screws. If a detector needs to be exchanged, it is simply removed from the base and replaced with a new detector.
Standard-compliant monitoring
The UniVario industrial detectors are monitored in accordance with
EN 54-13 in respect to the harmonized criteria of the European compatibility requirements for fire alarm systems.
With the esserbus transponder (Part
No. 808623.10) and end-of-line com-
Application examples
• Painting systems
• Engine testing facilities
• Wood industry
• Aircraft hangars
• Compression stations
Increased protection against:
• Solar radiation
• Halogen spotlights and various illuminants
• Welding flames
• Monitoring of fuel tanks and fuelling zones in outdoor areas
• Chip and semiconductor manufacturing
• Printing machines
• Chemical production
• Pumping stations
• Heat and power stations/Coal-fired power stations
Intelligent system integration
The UniVario range of industrial detectors are part of the ESSER fire alarm systems and have been tested and certified accordingly. They are integrated into the ESSER system via the esserbus transponder (Part No. 808623.10).
This component was specifically designed for connecting the UniVario detectors, and ensures that alarms and faults of any kind are reliably transmitted to the FACP directly via the zone input.
3 IR flame detector Part No. 782315
G1
G2
Transponder Part No. 808623.10
UBext.
esserbus or esserbus-PLus
EOL-UV
Part No. 808626.10
FACP
Connecting flame and heat detectors
Specifications
Operational voltage
Quiescent current
Alarm current
Ambient temperature
Protection rating
Housing
Specification
VdS approval
CE certificate
Spectral sensitivity
Monitoring area
Room height
9 V DC
Approx. 2.3 mA @ 9 V DC
Approx. 15 mA @ 9 V DC
-20 °C … +80 °C
IP67
Die cast aluminum
EN 54-10 cl. 1: 2002 / A1:2005; EN 54-13
G211041
0786-CPD-21055
2 µm ... 6 µm
Max. 650 m²
Max. 45 m
Order information
3-way IR flame detector (without base)
Standard base esserbus transponder
EOL-UV
For further order information, please refer to our fire alarm technology product catalog.
Part No.
782315
783313
808623.10
808626.10
Novar GmbH a Honeywell Company
Honeywell Life Safety Austria GmbH
Dieselstraße 2,
41469 Neuss, Germany
Lemböckgasse 49,
A-1230 Wien
Phone: +49 2137 17-0 (Administration)
Phone: +49 2137 17-600 (Customer Service Center)
Fax: +49 2137 17-286
Phone: +43 1 600 6030
Fax: +43 1 600 6030-900
Internet: www.esser-systems.com
Internet: www.hls-austria.at
E mail: [email protected]
E mail: [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project