“We didn`t invent clean power, we merely perfected it
“We didn’t invent clean power, we merely perfected it!”
INTRODUCTION
Always On™ UPS Systems Canada Inc. employs over 100 years of experience in the design and manufacture
of high quality UPS systems and Power Conditioning Products. Always On™ UPS systems incorporate highly
efficient Low-Pass Series and TVSS filters, which provide the protection required by today’s automated world
for all critical environments. We take a personal interest to ensure that our UPS systems and Power Quality
Products will continue to be manufactured to the highest degree of quality in our ISO-9001 Certified facilities.
Using Always On™ UPS products reduces the need for additional noise, spike and transient filters, as we
design this protection into every system we build. Always On™ is the only UPS manufacturer that incorporates
input and output filters providing all 10 levels of electrical protection.
Always On™ products, by increasing the reliability and life of your electronic equipment, increase up-time,
which allows for increased production resulting in increased profits.
All our products are manufactured in ISO-9001 Certified facilities, and are environmentally friendly, so much so
that we use “GES” (Green Energy Systems) as part of our model identification. Zero tolerance in our Quality
Assurance tests at all levels of production continues to eliminate failures in the field. We presently enjoy “0”
UPS failures in the field and *DOA’s are non-existent.
Always On™ UPS systems are approved for use by DND Canada, the US Military, US educational
departments, engineering consultants, the Canadian Coast Guard, GEAC, Ballard Generation Systems, health
authorities across North America, RCMP Forensics, the pulp and paper industry, Syncrude, Suncor and
numerous OEM’s across North America.
When you purchase Always On™ products, you receive:
CANADIAN MADE, ENERGY EFFICIENT, HIGH QUALITY COST EFFECTIVE PRODUCTS.
* Dead On Arrival
Available on our web site:
www.alwayson.com
Product Information and Specifications
UPS Selector
Manufacturer Cross-Reference
UPC Order Code Selector
Inside sales and engineering support is available on our toll-free telephone lines:
1-877-259-2976 (Sales ext. 451).
E-mail for support departments: [email protected], [email protected]
Version 13, 01, 23
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
Limousin II & The “Bull”
Always On™’s LIMOUSIN Series are transformer based UPS’s which provide lightning, surge,
spike, transient and noise protection and feature constant Automatic Voltage Regulation (AVR)
and blackout protection. They are designed for the home/office user to provide the maximum
protection at a competitive price. The Bull is not any ordinary power bar; with its automatic
voltage regulation (AVR) and its triple protection (spikes, noise, and transient suppression), it
can handle applications not suitable for other power bars.
Page 6
L Series (line-interactive true sine wave output)
Always On™’s L Series are line interactive UPS systems with a true sine wave output on all
modes of operation. They are ideal for commercial and industrial applications and range in size
from 800VA to 3kVA. All L Series systems provide voltage regulation, noise, surge and spike
protection, serial communication interface, network and modem protection, extended runtime
options and additional communication interfaces.
Page 7
N Series 1 ∅ (dual conversion on-line)
Always On™’s N Series are dual conversion true on-line UPS systems which provide the
attached loads with isolation from the utility or generator supply. At all times, the loads are
supplied power from the inverter, which is fed by the batteries and is designed for critical
applications. The wide input range (gen. mode) is designed into these systems while
maintaining output at 120VAC at 60Hz +/- 2%. The single phase systems are available from
700VA to 3kVA.
Page10
TN Series 1 ∅ (dual conversion on-line)
Always On™’s TN Series are dual conversion true on-line UPS systems which provide the
attached loads with isolation from the utility or generator supply. At all times, the loads are
supplied power from the inverter, which is fed by the batteries and is designed for critical
applications. The wide input range (gen. mode) is designed into these systems while
maintaining output at various voltage and frequency configurations. The single phase systems
are available from 5kVA to 20kVA.
Page 13
NX Series 3 ∅ (dual conversion on-line)
Always On™’s NX Series are dual conversion true on-line UPS systems which provide the
attached loads with isolation from the utility or generator supply and are designed for all critical
applications. These critical loads are supplied power from the inverter, which is fed by the
batteries. The NX Series is designed with a large input range and incorporates an output
isolation transformer. These UPS systems are available from 10kVA to 320kVA with three
phase input and three phase or single phase output with multiple voltage configurations.
Page 15
Software
Always On™ offers several different communication and connection options to manage your
UPS.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
4
Page 24
NFC Series Frequency Converters
(50, 60, or 400Hz selectable output frequency)
Always On™’s NFC Series Frequency Converters incorporate all the features of our dual
conversion true on-line UPS systems as well as the ability to lock the output frequency to
the three major standards. The dual conversion technology allows the load to be supplied
with 50Hz, 60Hz, or 400Hz, independent of the input. The NFC Series is designed with
large input range and incorporates an isolation transformer. These NFC systems are
available from 10kVA to 250kVA with three phase input and three phase output.
Page 25
Electrical Service Entrance TVSS Filter (ESE)
The Always On™ “ESE” TVSS filter is designed to protect your power grid. Installed at the
power panel, it provides protection against externally and internally produced power
aberrations, massive impulses, lightning induced effects and interference associated with
low frequency harmonics and situations caused by accidents and/or failures in the electrical
utility system. It is totally compatible with all operating loads including high frequency
power supplies and constant current loads controlled by electronic switches.
Page 27
PLC Low-Pass Series Filter
Always On™’s PLC filters are designed to provide noise, surge, spike, transient, and
overload protection to PLC power supplies and peripherals. Two different types are
available; AC only and AC/DC with data line protection to ensure clean operation and
transfer to all I/O interfaces, peripherals and power supplies. All systems include an onboard resettable breaker, and a three colour LED for easy operation identification and
diagnostics.
Page30
Engineered Solutions
Always On™ provides engineered solutions. From sensitive telecommunication equipment
to oil rig conditions, we can provide solutions to suit the needs of your environment.
Page 32
TF/ILF (Isolating Line Filter)
The Always On™ TTF/ILF combines a Low-Pass Series filter with a toroidal isolation
transformer. This unit provides attenuation of both normal and common mode noise and
eliminates any troublesome constant voltage which may exist between neutral and ground
in some electrical configurations. It is totally compatible with all operating loads, including
high frequency switching power supplies. It re-establishes the “0” volts ground reference
point on the secondary.
Page 33
Emergency Lighting (Aurora and Borealis Series)
Always On™ ELI’s are designed for installation between your AC power supply (utility or
generator) and your lighting equipment. It provides power to your equipment during major
power events such as blackouts and brownouts, over-voltage and under-voltage conditions.
The ELI provides a consistent supply of regulated AC power during these power events,
allowing you to ensure safety and lighting for the period required.
Page 34
Genie (AC Smart Distribution Panel / Cabinet powered by UPS)
The “Genie” is designed to supply AC power while protecting the multiple critical loads
supplied by the distribution (Genie) panel. The “Genie” incorporates the Always On™ SDB
breaker, which is specifically designed to clear in less than 1 second, eliminating multiple
load trips. The “Genie” replaces the required retrofitting of standard panels with fast-blow
fuses. A communication interface allows for a remote attendant.
Page 39
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
5
Home/Office/Commercial/Industrial
Limousin II
LIMOUSIN II
United Nation Standard Product & Service Code # 39121011
MODEL
GENERAL
LIMOUSIN II
Capacity
600VA
UPC Order Code
825433 00111
Voltage
INPUT
120V nominal (220V option), +/-25%
Frequency
50 or 60Hz +/- 5% (auto sensing)
Input socket
(1) IEC 320
Voltage (on battery)
Frequency (on battery)
OUTPUT
+/-10% of nominal
Waveform (On Battery)
Pulse Width Modulated (PWM)
4 milliseconds, including detection
Receptacles
(3) NEMA 5-15R (120V)
Spike Protection
PROTECTION
and FILTERING Overload Protection
Short Circuit
Type
BATTERY
6 hours (to 90% of full capacity)
Back up Time (Full load)
10-30 minutes
RS-232
LED Display
Normal / Backup / Overload
On Battery, Low Battery, Overload
Temperature range
ENVIRONMENT Humidity
Audible Noise
PHYSICAL
DATA
Fuse protection or immediate shutdown
Sealed, maintenance-free lead acid
Audible Alarms
SAFETY
APPROVAL
480 joules, 2ms
110% for 60 seconds and 130% for 3 seconds
Typical Recharge Time
Communications
INTERFACE
50 or 60Hz +/- 0.5Hz
Auto Voltage Regulation
Transfer Time
The Limousin II is a transformer-based UPS
that provides lightning, surge, spike, transient,
and noise protection. The Limousin II Series
provides for constant Automatic Voltage
Regulation (AVR) and blackout protection. It is
designed for the home/office user to provide
the maximum protection at a competitive price.
A shutdown/control software package,
communication cable and telephone/network
protection are all available with the Limousin II.
120VAC nominal +/-5% Simulated sine wave
o
0-40 C
0-95% non-condensing
<40dBA (1 meter from surface)
Safety
cUL, UL1778, CSA C22.2
EMI / RFI
FCC PART 15 CLASS B
Surge / Transient
IEEE C62.41 CAT.A
Net weight kg(lbs)
6.2(13.6)
Shipping weight kg(lbs)
6.7(14.9)
Dimension(mm)WxDxH
97x320x135
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Commercial Power Bar
“Bull”
Commercial Power Bar
Voltage Regulation, Noise, Spike
and Transient Protection
“BULL” Power Bar
United Nation Standard Product & Service Code # 39121009
Error! Not a valid link.Specifications are subject to change without notice to reflect upgrades
and improvement in technology.
ADVANCED FEATURES:
The Bull provides voltage regulation / variable
input voltage (+-10% output), electrical noise,
spike and surge protection, and IC chip design
and it operates at 95%+ efficiency.
It features overload protection with a resettable
breaker and output short protection with a
resettable breaker, as well as network
protection and fax / modem protection.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
6
Communications/Industrial
“L” Series (TRUE SINE WAVE)
Rackmount
DESCRIPTION:
Always On™’s L Series are line-interactive UPS systems with a true sine wave output in all modes. These systems are
ideal for commercial and light industrial applications and range in size from 800VA to 3kVA. All systems provide voltage
regulation, a serial communication interface, network and modem protection, extended runtime options and additional
communication interfaces.
APPLICATIONS:
Among other applications, the L Series can be applied to LAN file servers, personal computers, networks and
workstations, Automatic Teller Machines, telecommunications equipment, POS equipment, robotics, test equipment,
PLC’s, security and emergency systems and applications where additional runtime or SNMP are required.
ADVANCED FEATURES:
SMART “BOOST AND BUCK” LINE CONDITIONING:
The Always On™ transformer-based built-in line conditioning provides stable voltage when the utility supply fluctuates.
LIGHTNING, NOISE, SPIKE AND TRANSIENT PROTECTION:
The L Series offers lightning and surge protection, common mode and normal mode noise protection and Low-Pass
Series filters on the input and output.
NETWORK AND MODEM PROTECTION:
The Always On™ high end multi-component design provides ultimate protection and RJ11 and RJ45 connectivity.
INTELLIGENT COMMUNICATIONS INTERFACE:
RS-232 or dry contact interface ports act as the communication link between the computer and the UPS. Various
management software is available.
COLD START:
The cold start function allows start from battery when AC is not present.
AUTO RESTART:
This feature allows the UPS to restart automatically when the utility becomes available, provided the UPS has been
shutdown due to an extended blackout.
AUTO FREQUENCY DETECTION:
The automatic frequency sensing function will match the input and output frequency.
BATTERY REPLACEMENT:
User replaceable battery.
SNMP ADAPTER:
An optional SNMP adapter allows your network to easily manage the UPS, including remote control and status
monitoring.
CHARGING CURRENT WITH LOW RIPPLE AND LOW HARMONICS
A control circuit is used to provide a strict sine wave with low ripple and little harmonic distortion from the charging current.
VALUE ADDED:
Power Management and Shutdown Software, Communication Cable, Power Cable.
USB OPTION:
Available at time of order.
EXTENDED RUNTIME OPTIONS:
Additional battery banks are available for all models.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
7
“L” Series (TRUE SINE WAVE)
United Nation Standard Product & Service Code # 39121011
Specification
GENERAL
MODEL NO.
MAXIMUM CAPACITY
UPC ORDER CODE
GES-801L
800VA / 520W
825433 22100
NOMINAL VOLTAGE
INPUT
VOLTAGE RANGE
FREQUENCY RANGE
NOMINAL VOLTAGE
AUTO VOLTAGE REGULATION
CURRENT
6.6A
FREQUENCY
OUTPUT
POWER FACTOR
WAVE FORM (ON BATTERY)
LOAD CREST FACTOR
TRANSFER TIME
OUTLETS
4
BATTERY TYPE
BATTERY
QUANTITY
VOLTAGE
2
24VDC
RECHARGE TIME
FULL LOAD
BACKUP POWER TIME HALF LOAD
PENTIUM & 17" MON
≥ 8 MIN.
≥ 20 MIN.
≥ 41 MIN.
EXTENDED RUN TIME
OUTPUT SHORT
ABNORMAL VOLTAGE
PROTECTION
4x2
48VDC
≥ 8 MIN.
≥ 25 MIN.
≥ 90 MIN.
COMMON & NORMAL MODE NOISE SUPPRESSION
YES
LED DISPLAY
RS 232 / DRY CONTACT (OPTIONAL SNMP OR AS400)
NORMAL / BACKUP / LOW BATTERY / FAULT / CHECK BATTERY / BUCK / BOOST
ON BATTERY, LOW BATTERY, OVERLOAD, FAULT
0 - 40°C (32 - 104°F)
0 - 95% (NON-CONDENSING)
< 40 dBA AT 1 METER FROM UNIT
cUL, UL1778, CSA C22.2
FCC PART 15 CLASS B
IEEE C62.41 CAT.A
HUMIDITY
SAFETY
EMI / RFI
SURGE / TRANSIENT
UPS WxDxH mm (in.)
140x436x210 (5.5x17.2x8.3)
170x450x226 (6.7x17.7x8.9)
170x450x226
INTERNAL BATTERIES
(6.7x17.7x8.9)
EXTERNAL BATTERY BANK (if
applicable)
WEIGHT in kg (lbs)
MODEL NO.
UPC Order Code
RACK-MOUNT MODELS
4 + Hardwired
I/O SPIKE & TRANSIENT
PROTECTION
AUDIBLE NOISE
PHYSICAL DATA
25A
SINGLE LINE (2 wire RJ11) / NETWORK (UTP, RJ45) COMPATIBLE JACKS
OPERATING TEMPERATURE
SAFETY APPROVAL
GES-302L
3kVA / 1950W
825433 22500
I/O NOISE PROTECTION
AUDIBLE ALARMS
ENVIRONMENT
GES-152L
GES-202L
1.5kVA / 975W
2kVA / 1300W
825433 22300
825433 22400
120VAC (220 optional)
+ / - 25%
50 or 60 Hz auto-sensing + / - 5%
120VAC
+15% for 90 - 109VAC; -15% for 130 - 150VAC
8.33A
12.5A
16.6A
50Hz / 60Hz (Auto Detected) + / - 0.5%
0.5 - 1.0
TRUE SINE WAVE
3:1 (ON BATTERY)
2 - 4ms (Typical), including detection time
4
6
6
SEALED LEAD ACID - MAINTENANCE FREE
2
3
4
24VDC
36VDC
48VDC
≤ 2 to 4 Hours; Recovery = 90%, Typically
≥ 7 MIN.
≥ 7 MIN.
≥ 7 MIN.
≥ 17 MIN.
≥ 25 MIN.
≥ 25 MIN.
≥ 41 MIN.
≥ 70 MIN.
≥ 75 MIN.
Available
YES
YES
MODEM OR NETWORK
COMMUNICATION
INTERFACE
GES-102L
1kVA / 650W
825433 22200
14.5 (32)
15 (33)
25 (55.1)
30 (66.1)
GES-801LR
825433 22105
GES-102LR
825433 22201
GES-152LR
825433 22301
GES-202LR
825433 22401
483x381x133
(19x15x5.25) [3U]
28.4 (62.6)
483x381x89 (19x15x3.5) [2U]
WxDxH mm (in.)
WEIGHT in kg (lbs)
18 (35.3)
20 (44)
26.1 (57.5)
46 (101.4)
(including battery bank)
GES-302LR
825433 22501
483x381x178
(19x15x7) [4U]
46.4 (102.3)
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
OTHER VOLTAGES AND CONFIGURATIONS ARE AVAILABLE; FOR ORDER CODES, CONSULT MANUFACTURER.
EXTERNAL WRAP-AROUND BYPASS MODULES ARE AVAILABLE FOR ALL MODELS AND PERMIT UPS MAINTENANCE
WITHOUT POWER INTERRUPTION TO THE LOAD.
ADDITIONAL BATTERY BANKS ARE AVAILABLE FOR ALL MODELS.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
8
For 800VA to 3kVA UPS
2H
This graph is designed to aid in
sizing the UPS system based on
load and runtime and is suitable for
small loads only (i.e. 50VA to
1kVA). The horizontal axis is the
percent load of a UPS system and
the vertical axis is the runtime that
the UPS’s internal batteries will
provide. For runtimes exceeding
chart scale, please contact our
factory.
1H
40 MIN
30 MIN
RUNTIME
20 MIN
15 MIN
10 MIN
5 MIN
UPS LOAD LEVEL
10%
20%
30%
40%
50%
60%
80% 100%
Example: 30 minutes of back-up time are required to power a 200VA load.
Using the chart, find the back-up time required (i.e. 30 MIN) and move along the horizontal axis until you are placed
between the slanted lines. At this point, follow down the vertical lines to identify the UPS Load Level % (i.e. 30%). Divide
the load (i.e. 200VA) by the UPS Load Level % to identify the size of UPS required. Once calculated, round-up the
calculated number to the nearest UPS rating (i.e. 200 / 0.3 = 667). The minimum VA requirement is 667VA, so you roundup to an 800VA UPS system (GES-801L). The GES-801L will supply a minimum of 30 minutes to a 200VA load.
Additional Back-up Times (Battery Banks) for L Series
Load
Model
350W
500VA
490W
700VA
700W
1,000VA
1,050W
1,500VA
1,400W
2,000VA
2,100W
3,000VA
UPC Order Code
BBU-801LA
BBU-801LB
825433 60000
825433 60025
42 mins
70 mins
33 mins
45 mins
BBU-102LA
BBU-102LB
825433 60005
825433 60030
42 mins
70 mins
33 mins
45 mins
20 mins
30 mins
BBU-152LA
BBU-152LB
825433 60010
825433 60035
30 mins
25 mins
90 mins
17 mins
55 mins
13 mins
40 mins
BBU-202LA
BBU-202LB
825433 62300
825433 60040
72 mins
42 mins
90 mins
30 mins
50 mins
BBU-302LA
BBU-302LB
825433 62400
825433 60045
50 mins
40 mins
90 mins
27 mins
50 mins
Model
Cabinet Style
BBU-801LA
BBU-801LB
BBU-102LA
BBU-102LB
BBU-152LA
BBU-152LB
BBU-202LA
BBU-202LB
BBU-302LA
BBU-302LB
S cab
S cab
S cab
S cab
S cab
B cab
B cab
B cab
B cab
B cab
Dimensions (mm)
170W
170W
170W
170W
170W
260W
260W
260W
260W
260W
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 540D x 740H
x 540D x 740H
x 540D x 740H
x 540D x 740H
x 540D x 740H
18 mins
40 mins
Dimensions (in)
Weight
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
26.5 kg (58 lbs)
33 kg (73 lbs)
26.5 kg (58 lbs)
33 kg (73 lbs)
23 kg (51 lbs)
49 kg (108 lbs)
39.5 kg (87 lbs)
61 kg (134 lbs)
37 kg (81 lbs)
61 kg (134 lbs)
To meet your back-up time
requirements, we offer increased
back-up time by simply adding
additional battery cabinets. To
determine the battery bank part
number, locate the UPS model
number and runtime you want in the
tables below. For additional runtime
or for runtime calculations, please
contact our factory.
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
For more information or different runtimes, please contact CUSTOMER SERVICE toll-free at 1-877-259-2976, Ext. 451.
Standard 5-year pro rated warranty with 1-year replacement. Extended warranties available.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
9
Industrial/Commercial/Critical Loads
“N” & “TN11” Series
Single ∅ or Multi ∅ Input
Single ∅ or Multi ∅ Output
Rackmount
NEMA 12
Side Mount
DESCRIPTION: This dual conversion UPS system converts the incoming AC supply to DC. The DC power is used to
charge the batteries and supply the inverter. The inverter then inverts the DC power into AC power that, in turn, is
supplied to the load. This dual conversion isolates the line from AC supply and allows for wide input power variations on
both frequency and voltage. Systems in single phase output configurations range from 700VA to 20kVA.
APPLICATIONS: Among other applications, the N and TN11 Series can be applied to LAN file servers, personal
computers, networks and workstations, Automatic Teller Machines, telecommunications, laboratory and medical
equipment, test equipment, POS equipment, robotics, PLC’s, security and emergency systems and military & government
applications.
ADVANCED FEATURES: Features include utility input power factor correction, self-diagnosis, an LCD display, a static
bypass, smart power source monitoring and battery management, lightning, noise and surge protection, spike and
transient protection, cold start/auto restart, a user selectable frequency, a generator mode and intelligent communications
interface. SNMP and AS-400 adapters are available for network management. User replaceable batteries, emergency
power off control, an isolation transformer and maintenance bypass switches are standard on the TN11 and TN31 Series.
COMPLETE PROTECTION: The N and TN11 Series UPS’s are designed with comprehensive Spike, Transient and
Surge protection, which prevents destructive hardware damage and extends system life. The high end EMI/RFI filtering
design prevents electrical Common and Normal Mode noise from affecting computer operation, data or files, including
when the UPS is in Bypass Mode.
OPERATING VOLTAGES AND FREQUENCIES: The N and TN11 Series UPS’s are designed to function at wide voltage
and frequency variations. This wide input range makes the systems ideal for generator and problematic area applications.
Also available is a frequency converter option allowing the user to select the output frequency at 50 or 60Hz.
SELF-DIAGNOSIS AND INFORMATION INDICATORS: Each N and TN11 Series UPS is equipped with a
microprocessor that performs a self-diagnosis once a month to ensure continuous runtime. The microprocessor is able to
identify failures, display the failure on the LCD display and send audio and visual alarms (off site monitoring).
COLD START: This feature allows the N and TN11 Series UPS’s to be powered up when the utility is not present.
AUTO RESTART: This user selectable feature allows the UPS to restart automatically when utility becomes available,
provided it has been shutdown due to an extended blackout.
SMART POWER SOURCE MONITORING AND BATTERY MANAGEMENT: Via microprocessor-based electronics, the
N and TN11 Series UPS’s produce a strict true sine wave output regardless of the input. It also controls the on-battery
and low battery shutdown, which prevents full discharge, thereby extending the battery performance and battery life.
INTELLIGENT COMMUNICATION INTERFACE: Each N and TN11 Series UPS is equipped with a RS232 and dry
contact interface port, for which we provide various powerful management software programs. For the more complex
network environment, we support Simple Network Management Protocol (SNMP), AS400 and others.
REMOTE SHUTDOWN AND EMERGENCY STOP: Features include remote shutdown via communication port,
emergency stop via contacts. An optional push button control is available.
OPTIONAL EXTENDED RUNTIMES: To meet your back-up time requirements, we offer increased
back-up time by simply adding additional hot pluggable battery cabinet(s).
OPTIONAL USB: Available at time of order.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
10
“N” Series
TRUE SINE WAVE ON LINE UPS
N-SERIES
GENERAL
INPUT
OUTPUT
Single ∅ Input & Output
MODEL NO.
Maximum Capacity
UPC Order Code
Nominal Voltage
Voltage Range
Bypass Voltage
Phase
Frequency Window
Synchronization Window
Power Factor
Output Voltage
Voltage Regulation
Frequency Regulation
Voltage Distortion - THD
Max Current @ 120VAC
Transient Response
Overload Capacity
Crest Factor
Efficiency
Transfer Time
GES-701N
700VA/490W
825433 30100
5.8A
Outlets
BATTERY
PROTECTION
INTERFACE
ENVIRONMENT
CONFORMANCE
PHYSICAL DATA
RACK-MOUNT MODELS
Battery Type
Quantity
Voltage
Recharge Time
Advanced Battery
Management
Backup Time - Full Load
Extended Runtime
Output Short
Abnormal Voltage
Abnormal Frequency
I/O Noise Protection
I/O Spike and Transient
Telephone/Network
Display
Audible Alarms
Communications
Emergency Power OFF
Operating Temperature
Humidity
Audible Noise
Safety
Approval
Surge / Transient
EMI/RFI
Warranty
W x D x H mm (in.)
Weight in kg (lbs.)
MODEL NO.
UPC Order Code
WxDxH mm (in.)
Weight in kg (lbs.)
MODEL NO.
UPC Order Code
MARINE GRADE MODELS WxDxH mm (in.)
Weight in kg (lbs.)
Approval
2
24VDC
GES-102N
GES-152N
700VA - 3kVA
GES-202N
GES-302N
1000VA/700W
1500VA/1050W
2000VA/1400W
3000VA/2100W
825433 30200
825433 30300
825433 30400
825433 30500
120VAC (OPTIONAL 220VAC AVAILABLE)
60VAC/40% Load, 70VAC/70% Load, 80VAC - 144VAC/100% Load
+/-10%, +10/-15%, +15/-20% (User Selectable)
Single Phase (L-N-G)
45-65Hz (+/-2%, +/-5%, +/-7% - User Selectable)
+/- 3Hz
0.97
100/110/115/120/127VAC (User Selectable)
+/- 2%
+/- 0.25Hz (Battery or Free Run Mode)
<3% Linear Load, <5% Non-linear Load
8.2A
12.4A
16.5A
24.7A
4% (100% Load Change)
125% for 1 min. / 150% for 10 sec.
3:1
86% normally, > 98% (High efficiency mode)
Zero
10-(5-20R-US),
10-(5-15R),
6-(5-15R)
1-(L5-20R)
1-(L5-30R)
Sealed Lead Acid, Maintenance Free - Hot Swappable Cartridge
3
3
6
6
36VDC
36VDC
72VDC
72VDC
<4 Hrs to 90% Recovery
Auto Self-test, Temperature Compensated 3-Stage Charging, Load Dependent Discharge
9 min
10 min
8 min
12 min
8 min
Available
YES
YES
YES
Common & Normal Noise Suppression
YES
RJ11/RJ45
LCD / LED - Status, Readings and Setup Parameters
On Battery, Low Battery, Overload, Fault
RS232 / Dry Contact / (Optional: USB, SNMP, AS400)
YES - Via Normally Closed Contact
0 - 40 °C (32 - 104 °F)
0 - 95% (Non-condensing)
<40 dBA at 1 Meter
UL1778, CSA C22.2
UL, cUL, (Optional ABS [American Bureau of Shipping] see below)
IEEE C62.41 CAT.A
FCC Part 15
Two Year Factory Warranty (Optional Extendable Warranties Available)
155x410x238 (6.0"x16.5"x9.4")
225x425x360 (8.9"x16.7"x14.2")
13.5 (29.7)
16.2 (35.6)
17.0 (37.4)
31.6 (68.4)
32.5 (71.5)
GES-701NR
GES-102NR
GES-152NR
GES-202NR
GES-302NR
825433 30111
825433 30202
825433 30301
825433 30403
825433 30501
428x425x84 (16.9"x16.7"x 3.3") [2U]
428x635x84 (16.9"x25.0"x3.3") [2U]
18 (35.3)
20 (44.1)
25 (55)
31.6 (68.4)
32.5 (71.5)
GES-701N-ABS
GES-102N-ABS
GES-152N-ABS
GES-202N-ABS
GES-302N-ABS
825433 30112
825433 30231
825433 30232
825433 30233
825433 30234
155x410x238
260x555x700 (10.2x21.9x27.6)
(6.0"x16.5"x9.4")
30.5 (67.2)
20 (44.1)
42 (92.2)
47 (103.5)
ABS(American Bureau of Shipping), UL, cUL
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
INDUSTRIAL CONTAINERS ARE AVAILABLE (NEMA 12, NEMA 4, ETC.); CONSULT MANUFACTURER.
EXTERNAL WRAP-AROUND BYPASS MODULES ARE AVAILABLE FOR ALL MODELS, PERMITTING UPS MAINTENANCE WITHOUT POWER INTERRUPTION
TO THE LOAD.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
11
For 300VA to 3kVA UPS
2H
This graph is designed to aid in sizing the
UPS system based on load and runtime and
is suitable for small loads only (i.e. 50VA to
1kVA). The horizontal axis is the percent
load of a UPS system and the vertical axis is
the runtime. For runtimes exceeding chart
scale, please contact our factory.
1H
40 MIN
30 MIN
RUNTIME
20 MIN
15 MIN
10 MIN
5 MIN
UPS LOAD LEVEL
10%
20%
30%
40%
50%
60%
80% 100%
Example: 30 minutes of back-up time are required to power a 200VA load. Using the chart, find the back-up time
required (i.e. 30 MIN) and move along the horizontal axis until you are placed between the slanted lines. At this point,
follow down the vertical lines to identify the UPS Load Level % (i.e. 30%). Divide the load (i.e. 200VA) by the UPS Load
Level % to identify the size of UPS required. Once calculated, round-up the calculated number to the nearest UPS rating
(i.e. 200 / 0.3 = 667). The minimum VA requirement is 667VA, so you round-up to a 700VA UPS system (GES-701N).
The GES-701N will supply a minimum of 30 minutes to a 200VA load.
Additional Back-up Times (Battery Banks) for N Series
Load
350W
500VA
490W
700VA
700W
1,000VA
1,050W
1,500VA
1,400W
2,000VA
Model
UPC Order Code
BBU-701NA
BBU-701NB
825433 60300
825433 60325
28 mins
48 mins
17 mins
33 mins
BBU-102NA
BBU-102NB
825433 62600
825433 62610
30 mins
25 mins
50 mins
17 mins
33 mins
BBU-152NA
BBU-152NB
BBU-152NC
825433 62700
825433 62710
825433 62730
30 mins
25 mins
50 mins
100 mins
17 mins
33 mins
60 mins
13 mins
25 mins
40 mins
BBU-202NA
BBU-202NB
BBU-202NC
825433 62800
825433 62810
825433 60365
30 mins
150 mins
25 mins
100 mins
18 mins
60 mins
100 mins
BBU-302NA
BBU-302NB
BBU-302NC
825433 62900
825433 62910
825433 62920
30 mins
150 mins
25 mins
100 mins
18 mins
60 mins
100 mins
Model
BBU-701NA
BBU-701NB
BBU-102NA
BBU-102NB
BBU-152NA
BBU-152NB
BBU-152NC
BBU-202NA
BBU-202NB
BBU-202NC
BBU-302NA
BBU-302NB
BBU-302NC
Cabinet Style
S cab
S cab
S cab
S cab
S cab
S cab
B cab
S cab
B cab
B cab
S cab
B cab
B cab
Dimensions (mm)
170W
170W
170W
170W
170W
170W
260W
170W
260W
260W
170W
260W
260W
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 450D x 225H
x 540D x 740H
x 450D x 225H
x 540D x 740H
x 540D x 740H
x 450D x 225H
x 540D x 740H
x 540D x 740H
Dimensions (in)
Weight
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
6.75" x 17.7" x 9"
10.5" x 21.25" x 29"
6.75" x 17.7" x 9"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
6.75" x 17.7" x 9"
10.5" x 21.25" x 29"
10.5" x 21.25" x 29"
20 kg (44 lbs)
26.5 kg (58 lbs)
23 kg (51 lbs)
33 kg (73 lbs)
23 kg (51 lbs)
33 kg (73 lbs)
49 kg (108 lbs)
33 kg (73 lbs)
84 kg (185 lbs)
120 kg (264 lbs)
33 kg (73 lbs)
84 kg (185 lbs)
120 kg (264 lbs)
2,100W
3,000VA
14 mins
40 mins
60 mins
To meet your back-up time
requirements, we offer increased
back-up time by simply adding
additional battery cabinets. To
determine the battery bank part
number, locate the UPS model
number and runtime you want in the
tables below. For additional runtime
or for runtime calculations, please
contact our factory.
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
For more information or different runtimes, please contact CUSTOMER SERVICE toll-free at 1-877-259-2976, Ext. 451.
Standard 5-year pro rated warranty with 1-year replacement. Extended warranties available.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
12
“TN11” Series
Single ∅ Input (2 wire) & Single ∅ Output (2 or 3 wire)
TRUE SINE WAVE ON-LINE UPS
GENERAL
6kVA - 20kVA
Model No.
GES-602TN11
Maximum Capacity
UPC Order Code
TN11 SERIES
GES-103TN11
GES-153TN11
GES-203TN11
6kVA / 4.2kW
10kVA / 7kW
15kVA / 10.5kW
20kVA / 14kW
825433 40030
825433 40200
825433 40400
825433 40500
208 or 240VAC
Rated Voltage (Nominal)
170 - 276VAC
Voltage Range
INPUT
1 Ø (2 WIRE + GND)
Phase
45 - 65 Hz
Frequency Range
≤ 0.98
Power Factor
120, 120/240, 110/220VAC (other configurations available)
Voltage
± 2%
Voltage Regulation
1 Ø (3 wire + GND) [other configurations available]
Phase
Total Current @ 240VAC
25A
41.7A
62.5A
< 3% Linear Load; < 5% Rectified Load
THD
0.7
Load Power Factor
OUTPUT
1Hz / second
Slew Rate
± 4% (100% Load Change)
Transient Response
105% - 150% for 20 seconds
Overload Capacity
3:1
Crest Factor
> 85%
Efficiency (AC-AC)
Heat Dissipation
2494
4153
6227
Hard-Wired (other configurations available)
Outlets
Sealed lead acid - maintenance free
Battery Type
Voltage
240VDC
240VDC
240VDC
Full Load
> 10 Min.
> 4 Min.
> 8 Min.
> 4 Min.
Half Load
> 25 Min.
> 13 Min.
> 19 Min.
> 13 Min.
Available - Consult "Battery Banks"
EXTENDED RUN TIME
YES
Output Short
YES
Abnormal Voltage
PROTECTION
I/O Noise Protection
Common & Normal Mode Noise Suppression
I/O Spike & Transient
Protection
YES
RS-232 / Dry Contact / (Optional SNMP or AS400)
Communication
INTERFACE
LEDs and LCD Status Display
Display
On Battery, Low Battery, Overload, Fault
Audible Alarms
0 - 40°C (32 - 104°F)
Operating Temperature
ENVIRONMENT
0% - 90% (Non-Condensing)
Humidity
≥ 55 dBA at 1 meter from unit
Audible Noise
Safety/Approvals
SAFETY APPROVAL
UL1778, CSA C22.2, ABS(American Bureau of Shipping), UL, cUL
FCC Class A
EMI / RFI
IEEE C62.41 CAT.A
Surge / Transient
PHYSICAL DATA
240VDC
5 - 8 Hours; recovery = 90%, typically
Recharge Time
BACKUP POWER TIME
8303
0ms
Transfer Time
BATTERY
83.3A
50Hz / 60Hz ± 0.5% (Auto-Sensing)
Frequency Accuracy
WxDxH mm (in)
Weight in kg (lbs)
260x555x700
(10.2x21.9x27.6)
340x640x980
(13.4x25.2x38.6)
114 (251)
250 (551)
340x760x1160 (13.4x29.9x45.7)
255 (562)
265 (584)
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
OTHER VOLTAGES AND CONFIGURATIONS ARE AVAILABLE; FOR ORDER CODES, CONSULT MANUFACTURER.
AN EXTERNAL WRAP-AROUND BYPASS MODULE IS AVAILABLE FOR ALL MODELS, PERMITTING UPS MAINTENANCE WITHOUT POWER
INTERRUPTION TO THE LOAD.
INDUSTRIAL CONTAINERS ARE AVAILABLE (NEMA 12, NEMA 4, ETC.);
CONSULT MANUFACTURER.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
13
Additional Back-up Times (Battery Banks)
To meet your back-up time requirements, we offer increased back-up time by simply adding additional battery cabinets.
To determine the battery bank part number, locate the UPS model number and runtime you want in the tables below. For
additional runtime or runtime calculations, please contact our factory.
Load
UPC
60592
60600
60940
60941
60942
60943
60944
Cabinet
D
E
KA
KB
KC
KD
KE
UPC
60592
60600
60940
60941
60942
60943
60944
Cabinet
PD
PE
KA
KB
KC
KD
KE
6000VA
4200W
8000VA
5600W
10000VA
7000W
12000VA
8400W
15000VA
10500W
20000VA
14000W
20 mins
50 mins
60 mins
120 mins
170 mins
280 mins
410 mins
16 mins
40 mins
35 mins
90 mins
120 mins
200 mins
310 mins
15 mins
30 mins
30 mins
65 mins
90 mins
150 mins
260 mins
11 mins
18 mins
20 mins
45 mins
70 mins
130 mins
180 mins
12 mins
15 mins
33 mins
50 mins
90 mins
130 mins
7 mins
10 mins
20 mins
35 mins
60 mins
100 mins
Dimensions mm(inch)
Weight
235(9.25) W x 546(21.5) D x 552(21.75) H
400(15.7) W x 650(25.5) D x 1,020(40) H
815(32) W x 865(34) D x 1,930(76) H
815(32) W x 865(34) D x 1,930(76) H
815(32) W x 865(34) D x 1,930(76) H
815(32) W x 865(34) D x 1,930(76) H
815(32) W x 865(34) D x 1,930(76) H
80kg (177lbs)
353kg (777lbs)
629kg (1,387lbs)
758kg (1,671lbs)
885kg (1,951lbs)
1,022kg (2,253lbs)
1,277kg (2,815lbs)
For more information or different runtimes, please contact CUSTOMER SERVICE toll-free at 1-877-259-2976,
Ext. 451.
Batteries feature a standard 5-year pro rated warranty with 1-year
replacement. Extended warranties available.
Specifications are subject to change without notice to reflect
upgrades and improvement in technology.
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
14
Industrial/Commercial
“NX” Series Three ∅ In / Single or Three ∅ Out
NX31 and NX33
TRUE SINE WAVE ON-LINE UPS
Due to the increasing requirements placed by today’s users and technological advances
in present day electronics, the demand for an industrial UPS system with commercial
capabilities is required. Always On™ designed NX Series UPS systems to provide clean,
isolated, reliable and consistent power to all critical loads.
The NX Series UPS’s are dual conversion, on-line, three phase, intelligent systems for
centralized power protection and distribution. The “dual conversion” means AC utility is
converted into DC power which, in turn, charges the batteries and supplies the inverter,
which inverts the DC power back into highly regulated and isolated AC power. These
continuous three phase on-line UPS’s are available in models from 10kVA up to 250kVA.
For high power redundant applications, the NX Series UPS’s can be installed with up to eight units in parallel, achieving
N+1 redundancy. Isolated Parallel Redundant Operation (IPRO) is an optional feature of the NX Series, whereby the
systems are controlled in a true peer-to-peer configuration with redundancy in all critical elements and functions. This
advanced technology provides the greater system reliability and expansibility required for mission critical applications.
The NX Series UPS’s are also energy efficient. The models up to 40kVA are equipped with GES (Green Energy System)
to maximize savings on operating costs without compromising security. GES for IPRO configuration is a special firmware
package which allows significant reductions in energy consumption and operating cost during low load conditions.
Controls within the CPU monitor and distribute the load to maintain the maximum efficiency and reduce energy
consumption. The GES mode for IPRO is programmed to take care of load changes during the day or the degree of
redundancy required.
The NX Series UPS’s provide reliable and robust protection for mission critical installations from IT to telecommunications
and infrastructure applications such as airports, hospitals and financial companies.
Features and Benefits
Full Galvanic Isolation: Full Galvanic Isolation provides a completely isolated and referenced output. This isolation
protection provides a proven solution to problems created by induced voltages affecting the critical loads. Since the
output circuit to the load is completely isolated and no noise induced on the neutral can permeate to the loads, systems
operate in a more reliable fashion. Also, this type of protection increases the life span of equipment by eliminating noise,
which breaks down components.
Modular Design: Each major component (inverter, rectifier and static switch) on the NX Series are installed on slide-out
modules. This allows for quick repair (mean time to repair of >30 minutes) and easy field upgradeability.
High efficiency: Thanks to IGBT technology, the NX Series UPS’s provide high efficiency (up to 94.5%). This, combined
with IPRO, results in the most cost-efficient and reliable UPS solution in the industry.
Fully digital: DSP (Digital Signal Processor), flash memory and SVM strategy are the technology corner stones of the
new age of power quality and reliability.
Extremely flexible: The NX Series UPS offers tailor-made power protection to comply
with your individual installation requirements. Options include passive filter, a 6-pulse
rectifier (instead of the standard 12-pulse rectifier) for units under 80kVA and a Smart
Panel (SP). In addition, a comprehensive software suite can be added for mission
control and data protection.
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
15
“NX” Series Three ∅ In / Single or Three ∅ Out
NX31 and NX33
TRUE SINE WAVE ON-LINE UPS
10kVA - 250kVA
GENERAL DATA
Topology
True On-Line, Dual Conversion
Nominal output at PF=0.8
kVA
10
15
20
30
40
50
60
80
100
120
160
100% load, 0.8 PF
%
90
90
90
90
90
90
90
90
90
90
90
90
50% load, 0.8PF
True galvanic isolation from input to output
%
88
88
88
88
88
88
88
88
88
88
88
88
3,000
(0.89)
4,500
(1.3)
6,100
(1.8)
18,200
(5.3)
24,300
(7.1)
30,300
(8.9)
Overall efficiency
Heat rejection at 100% load, 0.9PF and
charged battery
Yes
BTU/hr
(kW)
Audible noise level (at 1 m)
dB (A)
UPS
Operating temperature
range
9,100
12,100
(2.7)
(3.6)
< 65 at 1m
o
o
-15oC to +50oC (5oF to 122oF)
Battery
0oC to 40oC (32oF to 104oF)
(VRLA)
Storage time is 6 months at 25oC (77oF) Higher temperatures reduce battery storage time
0% to 90%, non-condensing
Without Derating
<1,500m (5,000ft.) No derating
Type
Indoor (NEMA 1) [Drip shield available]
Safety
Internal dead front construction
Cooling
Forced air
Colour
Manufacturer colour (ivory)
Suitable for handling by forklift or overhead crane
Rigging
Installation
Mounting
Casters and leveling feet [Optional seismic rated mounting available]
Installation and maintenance access
Front access required for normal maintenance
Conduit access
Bottom entry standard [Optional top entry]
Standards
UL 1778, CSA 22.2, IEC 62040, FCC Class A, EN50091-1, -2 [Optional ABS or UL-924 available]
4kV contact / 8kV air discharge
Electrostatic discharge immunity
Stand-alone
Standard
Configuration
RECTIFIER
Configuration
12 pulse and harmonic filter
Voltage (Multitap configurable)
208/480/600, L-L VAC, 3 phase, 4 (or 3) wire + ground (-20% to +15% without battery discharge)
50 / 60 Hz +/- 7%
Frequency
Power Factor
0.8 at full load
Inrush current
Limited by soft-start circuit
Power walk-in:
20 seconds
Input
Output Voltage tolerance
Output
+/- 1%
DC ripple voltage
+/- 0.5%
DC ripple current
Nominal input current
(A)
Maximum Output DC Current @ 392VDC
Max. 5% of battery capacity expressed in amps
208/120
30
46
61
92
123
154
185
247
*
*
*
*
480/277
13
20
26
39
52
65
78
104
130
157
209
326
600/347
10
16
21
31
42
52
62
83
104
125
167
260
27
40
54
81
108
217
271
325
434
678
Current THD
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
135
162
12 Pulse Rectifier: 9%
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
16
75,800
(22.2)
(20 C to 25 C (68 F to 77 F) Higher temperatures reduce battery life expectancy
Relative Humidity
Enclosure
36,400
48,500
(10.7)
(14.2)
< 70 at 1m
o
UPS
Maximum Altitude
15,200
(4.4)
0oC to 40oC (32oF to 104oF)
o
Battery
Storage temperature
range
250
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
BATTERY
Nominal output at PF=0.8)
Battery compatibility
Number of cells
Voltage range
10kVA - 250kVA
kVA
Float voltage at 20oC (68oF)
Low voltage level
Minimum discharge voltage
Boost charge voltage
Maximum Charge Current (ADC)
Recharge time for 30 minute battery to 95% capacity
Battery ground fault detection
Automatic and manual battery test
INVERTER
Nominal output at PF=0.8)
kVA
DC voltage input range
Nominal output voltage (Multitap configurable)
Maximum output wattage (kW)
208/120VAC
Nominal Output
Current (A) (Linear
480/277VAC
Load)
600/347VAC
Inverter bridge
Output isolation transformer
Output power factor
Frequency lock range
Output waveform
Static
Load step 0% - 100% - 0%
Output voltage
tolerance
Load step 0% - 50% - 0%
100% unbalanced load (L-N)
100% linear load
Output voltage
distortion
100% non-linear load
Crest factor capability
100% balanced load
Phase displacement
100% unbalanced load
Free running
Output frequency
< 110%
110 - 125%
Overload capability
(on inverter)
125 - 150%
> 150%
Efficiency (100% Load)
10
15
20
30
5
8
10
16
10
15
20
30
8
22
10
8
12
33
14
12
16
44
19
15
100
120
160
250
21
27
32
43
54
10 times the discharge time (15 times for 40kVA)
Standard
Standard
65
86
135
50
60
80
100
120
285 - 415VDC
208/120 or 480/277 or 600/347, L-L VAC, 3 phase, 4 wire + ground
160
250
24
66
29
23
40
50
60
80
Sealed lead-acid [Optional NiCD or flooded]
174 Cells
295 - 410VDC
396VDC
320VDC
295VDC
410VDC
40
32
40
48
64
88
111
133
177
39
48
58
77
31
38
46
61
IGBT technology and Pulse Width Modulated
Standard
0.8
45 - 55Hz / 55 - 65Hz
True Sine Wave
+/- 1%
+/- 3%, recovering to within +/- 1% in 1 cycle
+/- 2%, recovering to within +/- 1% in 1 cycle
+/- 3%
< 2% THD maximum
< 3% THD maximum
Greater than 3:1
80
*
96
77
96
*
116
92
128
*
154
123
200
*
241
192
94%
94%
94%
94%
120o +/- 1%
120o +/- 2.5%
50 / 60Hz, +/-0.1% Synchronized with utility
Continuous
15 minutes
5 minutes
30 seconds
94%
94%
94%
94%
94%
94%
94%
94%
BY-PASS
Input configuration
Primary components
Voltage range
Frequency range
Efficiency
Common to rectifier [Optional dual input]
Full load rated static switch, Back-feed protection and Internal maintenance by-pass
+/- 20% of input voltage (line to neutral)
45 - 55Hz / 55 - 65Hz
99.50%
Inverter to bypass
0 ms
Transfers time
Bypass to inverter
0 ms
200% of UPS rating
30 seconds
Overload capability
400% of UPS rating
1 second
Short circuit capability (on by-pass)
1000% for 1/2 cycle (non-repetitive)
Yes
Isolation transformer
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
17
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
10kVA - 250kVA
EXTERNAL INTERFACE
Alarm contacts
Ethernet communications
Serial communication
Input signals
8 pre-defined contacts (COM, BATL, BACKUP, BYPASS, SS, FAULT, OVL, INVON)
SNMP adapter
RS-232 & RS-485
Emergency Power Off contacts provided (optional switch available)
FRONT PANEL CONTROLS, SIGNALS & ALARMS
Active mimic Diagram
LED display
Audile alarm
LCD Display
Push-Buttons
Represents the operational status of the UPS, with integrated LED's and power flow indicators.
Displays operational and fault conditions
Audible signal active when any alarm condition is present.
Display of UPS metering functions and event history
Inverter On, Inverter Off, Inverter Control, Up key, Down key, Enter key
OPTIONAL FEATURES
Marine approval
Emergency Lighting
Mounting options
Dual Input
Warranty
Redundant operation
Remote status Panel
Battery Cabinets
ABS (American Bureau of Shipping) Certified
UL-924, BMEC and CCMC
Seimic rated mounting, as well as certified is available.
Bypass and rectifer have separate inputs
Extended warranty and service packages available
N+1, A+B Buss system and IPRO (Isolated Parallel Redundant Operation)
Active mimic diagram w/ Stop Operation and Summary Alarms.
Additional matching battery cabinets to extend runtime
MECHANICAL DATA
NX-Series UPS
UPS Rating
(kVA)
W (Width)
Dimensions
D (Depth)
H (Height)
UPS
Weight
Floor Loading
10
15
20
30
40
50
60
80
100
120
160
250
550mm (21.7")
550mm (21.7")
550mm (21.7")
550mm (21.7")
550mm (21.7")
550mm (21.7")
550mm (21.7")
1,100mm (44.0")
1,100mm (44.0")
1,100mm (44.0")
1,100mm (44.0")
2,200mm (86.6")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
800mm (32.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
1,600mm (64.0")
380kg (838lbs)
415kg (915lbs)
450kg (992lbs)
580kg (1,279lbs)
650kg (1,433lbs)
710kg (1,565lbs)
850kg (1,874lbs)
920kg (2,024lbs)
1,050kg (2,310lbs)
1,300kg (2,860lbs)
1,600kg (3,520lbs)
2,700kg (5,953lbs)
864 kg/sq.m (177 lbs/sq.ft.)
943 kg/sq.m (193 lbs/sq.ft)
1,023 kg/sq.m (210 lbs/sq.ft)
1,318 kg/sq.m (270 lbs/sq.ft.)
1,477 kg/sq.m (303 lbs/sq.ft.)
1,614 kg/sq.m (330 lbs/sq.ft)
1,932 kg/sq.m (396 lbs/sq.ft.)
1,672 kg/sq.m (207 lbs.sq.ft.)
1,909 kg/sq.m (236 lbs/sq.ft.)
2,363 kg/sq.m (293 lbs/sq.ft.)
2,909 kg/sq.m (360 lbs/sq.ft.)
1,534 kg/sq.m (314 lbs/sq.ft.)
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
18
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
10kVA - 250kVA
Back-up Times (Battery Banks)
Full load runtime calculations for NX Series UPS systems from 8kW (10kVA) to 160kW (200kVA).
Load
4000W
5000VA
8,000W
10,000VA
12,000W
15,000VA
25 mins
90 mins
9 mins
40 mins
36 mins
80 mins
108 mins
4 mins
20 mins
23 mins
36 mins
76 mins
105 mins
40,000W
50,000VA
48,000W
60,000VA
64,000W
80,000VA
6 mins
12 mins
21 mins
33 mins
66 mins
92 mins
10 mins
18 mins
23 mins
40 mins
72 mins
12 mins
18 mins
24 mins
38 mins
16,000W
20,000VA
24,000W
30,000VA
32,000W
40,000VA
15 mins
18 mins
32 mins
46 mins
81 mins
108 mins
7 mins
10 mins
17 mins
28 mins
40 mins
72 mins
5 mins
10 mins
19 mins
24 mins
38 mins
Model
BBU-NX33D
BBU-NX33E
BBU-NX33KF
BBU-NX33KG
BBU-NX33KH
BBU-NX33KI
BBU-NX33KJ
Load
80,000W
96,000W
128,000W 160,000W
100,000VA 120,000VA 160,000VA 200,000VA
Model
BBU-NX33KG
BBU-NX33KH
BBU-NX33KI
BBU-NX33KJ
2 X BBU-NX33KI
2 X BBU-NX33KJ
Model
Cabinet Style
8 mins
13 mins
21 mins
33 mins
5 mins
10 mins
18 mins
23 mins
Dimensions
12 mins
18 mins
8 mins
13 mins
Weight
BBU-NX33D
D Cabinet
235 (9.25") W x 546 (21.5") D x 552 (21.75") H
117 kg (258 lbs)
BBU-NX33E
E Cabinet
511 kg (1,126 lbs)
400 (15.75") W x 682 (26.75") D x 1,008 (39.75") H
BBU-NX33KF KF Cabinet
1,314 (51.5") W x 850 (33.5") D x 1,945 (76.5") H
814 kg (1,791 lbs)
BBU-NX33KG KG Cabinet
1,314 (51.5") W x 850 (33.5") D x 1,945 (76.5") H
1,024 kg (2,258 lbs)
BBU-NX33KH KH Cabinet
1,314 (51.5") W x 850 (33.5") D x 1,945 (76.5") H
1,204 kg (2,649 lbs)
BBU-NX33KI
KI Cabinet
1,314 (51.5") W x 850 (33.5") D x 1,945 (76.5") H
1,398 kg (3,076 lbs)
BBU-NX33KJ KJ Cabinet
1,314 (51.5") W x 850 (33.5") D x 1,945 (76.5") H
1,764 kg (3,881 lbs)
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
For 250kVA and 320kVA UPS systems, contact factory for models.
NX-Series UPS Block Diagram
Rectifier
1
Inverter
2
Static Bypass
3
Maintenance Bypass
4
Output Isolation Transformer
5
Output to Load
6
Battery Bank
7
Battery Contactor
8
9
AC Utility
FB
Battery Fuses or Circuit Breaker
F1
AC Input Fuses or Circuit Breaker
F2
Optional AC Input Fuses or Circuit Breaker for Alternate Input
Lb
Battery Line
L In
Input Line
L In Alt Optional Alternate Input
9
Optional
Dual
Input
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
19
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
NX31 and NX33
10kVA - 250kVA
System Configurations
The standard configurations presented are intended only to illustrate the minimum number of enclosures required for each
system and our recommended installation arrangement. These enclosures are shipped as separate components.
Allow Min 60cm (2’)
Allow Min 60cm (2’)
Allow Min
1m (3’)
250 to 320kVA UPS system
60 to 160kVA system
10 to 50kVA UPS system
Allow Min
1m (3’)
Allow Min 60cm (2’)
Allow Min
1m (3’)
Dimensions:
2,200 mm (86.5”) W
812 mm (32”) D
1,600 mm (63”) H
Dimensions:
1,100 mm (43.25”) W
812 mm (32”) D
1,600 mm (63”) H
Dimensions:
550 mm (21.75”) W
812 mm (32”) D
1,600 mm (63”) H
Battery Cabinet Configurations
Allow Min 60cm (2’)
D Cabinet Dimensions:
235 mm (9.25”) W
546 mm (21.5”) D
552 mm (21.75”) H
Allow Min
1m (3’)
Allow Min 60cm (2’)
Allow Min
1m (3’)
Allow Min 60cm (2’)
E Cabinet Dimensions:
400 mm (15.75”) W
682 mm (26.75”) D
1,008 mm (39.75”) H
Allow Min
1m (3’)
K Series Cabinet Dimensions:
1,314 mm (51.5”) W
850 mm (33.5”) D
1,945 mm (76.5”) H
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
20
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
NX31 and NX33
10kVA - 250kVA
Features
Extension of battery life
Batteries are a critical part of every UPS solution, acting as the power supply in the event of an AC power failure.
Batteries are sensitive products that need to be handled and monitored continuously and carefully in order to increase
their lifetime and predictability. Always On™ includes superior battery management within the entire NX Series family and
is a comprehensive management and monitoring system that prevents batteries from overcharging and deep discharging.
Load dependent runtime indication and re-calibration procedures are standard features to optimize life cycle cost and
system reliability.
Features and Benefits:
The NX Series features a ”no surprises” automatic battery test, a deep calibration test, which provides battery
performance tracking, boost charging, which enables fast recharging of batteries and a temperature compensated battery
charger, which prevents overcharging. The load dependent end of the discharge voltage gives deep discharge protection
and the “no-load” shutdown maintains your battery’s operational life under no-load conditions.
UPS Monitoring and Management via SNMP
Data Protection & Monitoring:
The primary function of Always On™’s protection software is the safeguarding of data and the Operating Systems. Using
our software reduces the risk of system crashes and/or data loss. Always On™’s software provides event handling and
computer shutdown for all major operating systems to enhance security of critical data. Multi-vendor and multi-platform
environments, as well as client-server structures, are managed.
Direct access of remote UPS and active management of single modules in multi-unit configurations are the keys to
efficient and predictable power quality management. The SNMP Client/Agent structure, direct link, or remote connection
enables a network manager or facility engineer to permanently monitor and control local or remote Always On™’s UPS
systems and the equipment and processes they protect. Snap-in modules allow easy integration into the leading Network
Management Systems.
A real-time graphical display of critical UPS parameters and environment information of multiple decentralized UPS’s, as
well as statistical data and event log files, are available on every local computer display and network management system
or on the Internet. Additionally, UPS status information changes can be sent to such varied information carriers as SMS,
network management systems, e-mail or fax.
Options
Isolated Parallel Redundant Operation (IPRO)
Highest standard for reliability:
Power reliability is business reliability. Mission critical applications require the highest availability of power. Always On™’s
unique IPRO technology sets the highest standard for power reliability, and IPRO compatible NX Series UPS’s are field
upgradable. Additional units can be added to increase the total power output of a system or to create a redundant system
with no single point of failure. Decentralized bypass, redundant control electronics and redundant batteries offer perfect
load-sharing and fault-tolerant operations.
Protection:
Short circuit, over-temperature and over-voltage protection is built in to protect the NX Series UPS against any form of
misuse. Back-feed protection, complete protection circuits and excellent overload behaviour provide outstanding user
protection and application security, all in conjunction with full galvanic isolation on the output of every UPS system used in
the parallel operation.
Features and Benefits:
Up to eight NX Series units can be connected in a redundant-parallel system (N+1 redundant). It also features a
decentralized bypass, redundant control electronics, active-active system management and fault tolerant operation, as
well as a transparent fail over procedure in case of UPS failure or for maintenance and no single point of failure.
Drip Shield
The addition of a drip shield ensures that liquids and other debris do not enter your NX Series UPS through the top
cooling vents.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
21
“NX” Series Three ∅ In / Single or Three ∅ Out
TRUE SINE WAVE ON-LINE UPS
10kVA - 250kVA
Module Interior Layout
Rectifier
Module
Inverter
Module
IPRO TRUE REDUNDANT
SYSTEM
Each system component is
redundant; Rectifier, Batteries,
Inverter, Static Switch, Control
System.
Failure of one system
component still allows
redundancy on remaining
components.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Complete maintenance and
repair of one UPS while the
other UPS remains on-line with
total battery capacity available.
11)
12)
13)
14)
15)
16)
17)
18)
SOURCE 1
SOURCE 2
AUTO TRANSFER
SWITCH
3PH 3W+G
UPS1 INPUT
UPS2 INPUT
INPUT BREAKER
BYPASS
BREAKER
RESERVE
BREAKER
RECTIFIER
BREAKER
RECTIFIER
INVERTER
STATIC SWITCH
BATTERIES
BBU1
BBU2
UPS OUTPUT
3PH 3W+G
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
22
“NX” Series Three ∅ In / Single or Three ∅ Out
External Bypass Systems
TRUE SINE WAVE ON-LINE UPS
10kVA - 250kVA
A separate cabinet to allow for complete removal of the UPS system from the load, while still supplying the
load with conditioned power. Always On™ offers various systems which include isolation transformers for
different voltage configurations, distribution panels, electro-mechanical interlock protection to ensure proper
operation, rotary switch operation and transient voltage surge suppression.
Systems are supplied in a matching cabinet or wall mounted cabinet. These systems are recommended for
maintenance purposes to prevent accidental removal of power from the loads and to allow for complete power
removal from the UPS system for safety considerations.
Bypass with optional TVSS filter
Standard Bypass system
Rotary Bypass system
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
23
UPSmon Plus
Data and software protection
UPSmon Plus prevents your computer from crashing during a
power failure. If the UPS’s battery runs low, in the case of
power failure, UPSmon Plus will detect this and perform an
orderly shutdown of your computer before the battery runs out.
The auto-shutoff feature is also used to perform scheduled
shutdown and startup of your computer during normal
operations. With the use of your computer modem, UPSmon
Plus can send an event code to your pager to notify you of a
power related event on your system. A data recorder is also
featured that records power data in a graphic form to facilitate
analysis of power quality conditions.
UPSmon Plus
Communications: RS232 Bi-Directional
Operating Systems Supported: Microsoft Windows 95/98/ME/
NT/2000/XP
UPSmon Plus Network
Data and network software protection
UPSmon Plus Network lets you monitor and manage multiple
UPS’s through your TCP\IP network from a central location.
Using your network UPSmon Plus Network can auto-shutdown
an unlimited number of computers in the event of a power
failure. The e-mail and pager features can notify you of a power
event. The Redundant UPS monitoring feature permits two or
more redundant UPS’s to be monitored. If one redundant UPS
fails or is taken off-line for maintenance, UPSmon Plus Network
still monitors the back-up UPS and provides auto-shutdown
protection in the case of a power failure.
UPSmon Plus Network
Communications: RS232 Bi-Directional and TCP/IP
Operating Systems Supported: Microsoft Windows95/98/ME/
NT/2000/XP
Main UPS
management
screen
Main UPSmon
Software screen
Set actions
to trigger on
power events
UPS power
management
scheduler
Power Quality
data analysis
Individual UPS’s
status can also
be viewed
ACTIVITY MONITORING SOFTWARE REPORT SCREENS
.NetPower SNMP Adapter
Paging
setup
screen
UPSilon 2000
Data and software protection for the Network
UPSilon 2000 lets you monitor local UPS’s as well as remote
units by TCP/IP from your central location. UPSilon 2000 can
be configured to automatically send e-mails when an event
occurs such as a power outage. When an event occurs, it can
also call a pager with the use of a modem. The display is a real
time display of the graphical display of UPS status including
input/output voltage, frequency, load, temperature and capacity.
UPSilon 2000 will shutdown the system in a safe fashion before
the batteries run out and can also broadcast messages to
remote computers running ClientMate (included) and even send
them commands to shutdown.
INTEGRATED INTELLIGENT POWER MANAGEMENT (IIPM):
The IIPM packages are comprised of the SNMP Agent, an
SNMP adapter and onEvent. These are available to efficiently
control and manage the GES series UPS’s. Aside from running
on Windows 95/98/2000 and Windows NT, the excellent network
management features let you easily manage over the
Internet/Intranet using TCP/IP and Ethernet.
IIPM Features:
IIPM features remote monitoring and control via a TCP/IP
network and provides a hierarchical architecture to manage your
UPS’s. It also features notification via e-mail, pager, audible
alarm or broadcast and graceful graphics for monitoring and
displaying the real-time status of your UPS. IIPM also provides
remote shutdown, file saving and password protection.
UPSilon 2000
Communications:
RS232 Bi-Directional and TCP/IP
Operating System Supported:
Microsoft Windows products and
Linux
OPTIONAL: UPSilon for Unix
Specifications are subject to change without notice to reflect upgrades and
improvement in technology.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
24
Three ∅ In/Out
Industrial/Commercial
“NFC” Series
FREQUENCY CONVERTERS: 50, 60, or 400Hz Input Frequency / 50, 60, or 400Hz User Defined Output Frequency
The Always On™ NFC Series Frequency Converters are manufactured to provide clean,
regulated and controlled power at the customer specified voltage and frequency. Based
on the Always On™ NX Series, the NFC Series provides clean, isolated, reliable and
consistent power to all critical loads at the expected levels required.
The NFC Series Frequency Converters are intelligent, dual conversion, on-line, three
phase systems for centralized frequency conversion, power protection and distribution.
The “dual conversion” means AC utility is converted into DC power which, in turn,
charges the batteries and supplies the inverter, which inverts the DC power back into
highly regulated and isolated AC power supplied at a user defined frequency (50, 60, or
400Hz). This continuous on-line Frequency Converter is available in models from
10kVA up to 250kVA. This dual conversion prevents power aberrations from affecting
the connected loads.
The NFC Series Frequency Converters provide reliable and robust protection and frequency conversion,
allowing for reliable and protected power to be available for all specific and critical loads.
Features and Benefits
Frequency Conversion: This permits the user to configure a system with any input voltage (208, 480 or 600)
and input frequency (50, 60, or 400Hz) with any output voltage (208/120, 480/277 or 600/347) and output
frequency (50, 60 or 400Hz), independent of the input configuration.
Full Galvanic Isolation: Full Galvanic Isolation provides a completely isolated and referenced output. This
isolation protection provides a proven solution to problems created by induced voltages affecting the critical
loads. Since the output circuit to the load is completely isolated and no noise induced on the neutral can
permeate to the loads, systems operate in a more reliable fashion. Also, this type of protection increases the
life span of equipment by eliminating noise, which breaks down components.
Modular Design: Each major component (inverter, rectifier and static switch) on the NFC Series Frequency
Converters are installed on slide-out modules. This allows for quick repair (mean time to repair of >30
minutes) and easy field upgradability.
High efficiency: Thanks to IGBT technology, the NFC Series Frequency Converters provide high efficiency
(up to 94.5%). This, combined with IPRO, results in the most cost-efficient and reliable UPS solution in the
industry.
Fully digital: DSP (Digital Signal Processor), flash memory and SVM strategy are the technology corner
stones of the new age of power quality and reliability.
Extremely flexible: The NFC Series Frequency Converters offer tailor-made power protection to comply with
your individual installation requirements. Options include a passive filter, a 12-pulse rectifier and a Smart
Panel (SP). In addition, a comprehensive software suite can be added for mission control and data protection.
Optional Battery Banks: Always On™ has also allowed for the option of back-up time to be added to the
system to eliminate the need of purchasing a UPS system and a frequency converter. This runtime package
will allow for UPS-like operation at a user defined frequency (50, 60, or 400Hz).
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
25
Three ∅ In/Out
“NFC” Series
FREQUENCY CONVERTERS: 50, 60, or 400Hz Input Frequency / 50, 60, or 400Hz User Defined Output Frequency
10kVA - 250kVA
GENERAL DATA
Topology
True On-Line, Dual Conversion
Nominal output at PF=0.8
kVA
10
15
20
30
40
50
60
80
100
160
100% load, 0.9 PF
%
91
91
91
91
91.5
92
92
92.5
92.5
93
93
50% load, 0.9 PF
True galvanic isolation from input to output
%
89
89
89
89
89
91
Yes
91
91
91
92
92
3,070
(0.9)
3,510
(1.0)
4,440
(1.3)
6,480
(1.9)
8,870
(2.6)
10,200
(3.0)
11,900
(3.5)
15,700
(4.6)
18,400
(5.4)
29,700
(8.7)
44,360
(13)
Overall efficiency
Heat rejection at 100% load, 0.9PF and
charged battery
Audible noise level (at 1 m)
BTU/hr
(kW)
< 65 at 1m maximum
dB (A)
UPS
Operating
temperature range
Battery
o
o
o
o
o
o
o
-15 C to +50 C (5 F to 122 F)
o
o
o
o
0 C to 40 C (32 F to 104 F)
(VRLA)
Storage time is 6 months at 25 C (77 F) Higher temperatures reduce battery storage time
0% to 90%, non-condensing
o
o
<1,500m (5,000ft.) No derating
Type
Indoor (NEMA 1) [Optional drip shield available] [other configurations available]
Safety
Internal dead front construction
Cooling
Forced air (bottom to top)
Colour
Manufacturer colour (ivory)
Rigging
Installation
o
o
Without Derating
Enclosure
o
Battery
Relative Humidity
Maximum Altitude
o
Optimum 20 C to 25 C (68 F to 77 F) Higher temperatures reduce battery life expectancy
UPS
Storage temperature
range
< 67 at 1m maximum
o
0 C to 40 C (32 F to 104 F)
Mounting
Installation and maintenance access
Conduit access
Standards
Suitable for handling by forklift
Casters and Floor mounting brackets
Front access required for normal maintenance
Bottom entry standard [Optional top entry]
UL 1778, IEC 62040, FCC Class A, EN50091-1, -2
4kV contact / 8kV air discharge
Electrostatic discharge immunity
Standard
Configuration
Stand-alone
IPRO - up to 8 units may be paralleled for redundancy or capacity
Optional
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
“NFC” Series Frequency Converter Block Diagram
7
1
2
3
4
5
6
7
FB
F1
Lb
L In
Rectifier
Inverter
Output Isolation Transformer
Output to Load
Battery Bank
Battery Contactor
AC Utility
Battery Fuses or Circuit Breaker
AC Input Fuses or Circuit Breaker
Battery Line
Input Line
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
26
250
“TVSS”
POWER
PROTECTION
Products may not necessarily be as illustrated.
The Always On™ “ESE” TVSS filter is designed to protect, at the power panel, against externally and internally
produced power aberrations, massive impulses, lightning induced effects and interference associated with low frequency
harmonics and situations caused by accidents and/or failures in the electrical utility system. It is also totally compatible
with all operating loads, including high frequency power supplies and constant current loads controlled by electronic
switches.
APPLICATIONS:
Electrical Service Entrance filters protect the electronic and electrical equipment in the building by supplying power
protection at the main and sub-panel locations.
PROTECTION:
Our ESE’s offer high end protection for industrial and commercial environments and our specifically designed and tuned
circuitry provides protection against all potentially dangerous electrical aberrations. They eliminate and attenuate to safe
levels common and normal mode noise, massive surge impulses, indirect lightning strikes and their effects, interference
associated with low frequency harmonics, spikes and transients, as well as problems associated with electrical utility
failures caused by accidents, storms, etc.
Electrical and electronic equipment create their own power aberrations, which creates problems for other loads and
equipment ‘downstream’. These aberrations will travel down the power bus to the power panels, where they propagate to
other loads via other branch circuits.
By installing Always On™ ESE power panel protection devices, these problems will not occur.
Always On™ ESE Power protection offers TWO Methods of Protection
1) For all New Residential, Commercial and Industrial Construction:
The ESE protects electronic equipment in new buildings (security, environmental, networking, communications,
appliances, systems, etc.) from potentially destructive and disruptive externally generated power spikes and transients,
massive surges, indirect lightning strikes, low frequency harmonics and common and normal mode noise.
2) For all Commercial and Industrial Retrofits:
In commercial and industrial environments, the ESE offers the same features as above and protects ‘downstream’ branch
panels from externally and internally generated power aberrations such as spikes, transients, massive surges, low
frequency harmonics and common and normal mode noise.
STOP THE PROBLEMS BEFORE THEY CAN OCCUR. ELIMINATE ALL POTENTIAL PROBLEM CAUSING
AND DAMAGING POWER ABERRATIONS BY HAVING AN ALWAYS ON™ ESE FILTER INSTALLED.
FEATURES:
The ESE features self-diagnostics, LED indicators and removable fuses per phase, which eliminate DEDICATED and
costly 3 phase panel breakers.
OPTIONAL:
The ESE also features optional visual and audible alarms, form C contacts for remote monitoring, a surge counter, which
indicates the number of high energy, potentially damaging hits on a continual basis, and a flush mount container.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
27
“TVSS” POWER PROTECTION
SPECIFICATIONS
Frequency:
Voltages:
Phases:
Protection Modes:
Technology:
Insertion Loss:
Bandwidth:
Response Time
Standards:
50/60Hz
208, 240, 480, 600 (other voltages available)
Wye or Delta - Three phase and Single phase
10 for 3 ∅ wye, 6 for 3 ∅ delta, 5 for 2 ∅ wye
Bi-Directional Parallel
Nominal 60dB, [email protected]
10kHz-50MHz or 180Hz-50MHz
Constant / Instantaneous
Surge Current
Sink Current Capacity / Ø:
Operating Humidity:
Operating Temp:
Warranty:
Enclosure:
Weight:
Optional:
UL1449 Rev. 1998 (TVSS) Peak
60kA to 600kA per phase
25A
0-97% (non-condensing)
-40ºC to +65ºC
10 years
NEMA 12 (or Optional NEMA 4) Flange Mount
14”x12”x6” inches
13.6kg / 30lbs (Approx)
DC - Dry Contact (Form “C”) Communications
SC - Surge Counter (LCD Display)
FM - Flush Mount Container (DIM 12”x12”x6”)
FT - Fault Test Button
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Description of Model Number
208
Y
ESE 200K
Model Type
ESE
60K*
100K
120K
160K
200K
250K
300K
400K
500K
600K
60kA per Phase
100kA per Phase
120kA per Phase
160kA per Phase
200kA per Phase
250kA per Phase
300kA per Phase
400kA per Phase
500kA per Phase
600kA per Phase
(DC
SC
FM
FT - Optional
Configuration
Wye or Delta***
***Contact manufacturer
for more information on
Delta version
**Other voltage
options available
consult manufacturer
FOR ALL UPC ORDER CODES, VISIT
WWW.ALWAYSON.COM.
*Note: 60K version is for residential use and comes in the 240Volt / Y configuration only.
It is not recommended for commercial or industrial applications.
EXAMPLES:
MODEL
ESE
ESE
ESE
SURGE CURRENT
60K
250K
500K
VOLTAGE
240
480
600
Y or D OPTION
Y
D
Y
DCSC
MODEL #
ESE-60K-240Y (SHP)
ESE-250K-480D
ESE-500K-600Y-DCSC
Surge Current: 60K, 100K to 600K
208/240/480/600 VOLTS
Y - Neutral wire required (Wye type transformer)
D - Neutral wire not required (Delta type transformer)
DC - Dry Contact Communication
SC - Surge Counter
FM - Flush Mount Container
FT - Fault Test Button
Optional
Additional Cost
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
28
“TVSS” POWER PROTECTION
Reference Sheet for the Electrical
Service Entrance Filter Application
Residential (Smart Home) and Multi-residential Complexes
Model #
ESE-60K-240Y [2∅] (SHP)
ESE-100K-208Y [3∅] (other voltages available)
Panel Size
Up to 200A
Above 200A
Commercial (Office, Retail, etc.)
Model #
ESE-100K-208Y (DCSC) (Optional) [3∅] (other voltages available)
ESE-160K-208Y (DCSC) (Optional) [3∅] (other voltages available)
ESE-200K-208Y (DCSC) (Optional) [3∅] (other voltages available)
Panel Size
Up to 2000A
Up to 3000A
Above 3000A
Industrial
ESE Sizing Chart for Industrial Environments
1000A
Panel Size
2000A
3000A
4000A
5000A
Consult manufacturer for panels exceeding
5000A or 200hp connected. For further
specifications on our ESE’s, please visit our
website at www.alwayson.com or contact
customer service at [email protected]
or toll-free at 1-877-259-2976, Ext. 451.
ESE 100K
ESE 160K
ESE 200K
ESE 250K
ESE
Size
ESE 300K
ESE 400K
ESE 500K
ESE 600K
0
20hp
40hp
50
60hp
100hp
80hp
120hp
Total Horsepower
100
150
140hp
160hp
200
180hp
200hp
250
Base “ESE” size on panel size or Total Horsepower rating. (Use the larger of the “ESE’s” specified).
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
29
FOR ALL “PLC” APPLICATIONS
A/C POWER AND DATA LINE PROTECTION IN ONE CONVENIENT BOX
Today’s competitive markets require all industrial equipment to function at
maximum performance. Lower profits require higher yields or production.
This is achieved by maintaining production equipment to run at its optimum
level. Increased production means increased profits.
The Always On™ “PLC” 2+2 and 2+0 Transient Voltage Surge Suppressor
(TVSS) and data line filter will provide today’s users and OEM’s with the
ultimate protection required by today’s automated industries. Always On™
has 25 years in the noise suppression and power quality industry, providing
us the knowledge base required to remain on the cutting edge of the power
protection industry.
User resettable
breaker on all models
APPLICATIONS:
Among other applications, the PLC Protector can be applied to PLC’s, robotics, CAD/CAM, alarm systems, scanners,
controllers, medical equipment and virtually all microprocessor-based ”critical” equipment.
USERS:
Typical PLC Protector users include the oil industry, refineries, the pulp and paper industry, the textile industry, water and
sewer treatment plants, the petrochemical industry, the food processing industry and virtually all types of manufacturers.
FEATURES / BENEFITS:
Series Hybrid Design
Sine wave tracking TVSS technology ensures fast and immediate attenuation of the harmful spikes, transients and both
common and normal mode noise. The added data line filter ensures that the 2+2 Filter will protect the attached
network/communication link from all potential problems. The Always On™ 2+2 filter is the only filter that offers all modes
of protection on both the power line and the data line. The Always On™ 2+2 one-two punch will guarantee maximum
runtimes for your equipment, resulting in higher production and profits, while decreasing downtime and equipment repair
costs.
Suppression / Attenuation
The “cutting edge” technology contained in the Always On™ 2+2 and 2+0 filters allow normal mode noise attenuation up
to 85dB and for common mode noise attenuation up to 50dB. It filters bandwidths of 10kHz to 100MHz, with a total peak
surge current of 32,500 amps, while providing a response time of less than 1 nanosecond.
Functioning Indicator
The easily seen three colour LED informs the user of the working status of the Always On™ 2+2 and 2+0 filter.
Optional Communications
Form A, B or C contacts allow the user to monitor the status of the 2+2 or 2+0 filter from a remote location.
Mounting Options
The 2+2 and 2+0 come standard with J-Rail or an optional flange mounting is available.
Product Warranty
Always On™ 2+2 and 2+0 filters are warranted against failure for two years (exchange or repair warranty).
5-Year User Guarantee
Always On™ guarantees against electrical damage to the protected power supplies by power aberrations for 5 years.
Conclusion
The “PLC” 2+2 and 2+0 filters increase up-times to the maximum, which increases production and results in higher profits.
It also offers substantial savings through decreased down-time and decreased repair costs.
FOR ALWAYS ON™ UPC ORDER CODES, VISIT WWW.ALWAYSON.COM.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
30
TVSS AND DATA LINE FILTER
TVSS FILTERS THREE WIRE GROUNDED / TWO WIRE UNGROUNDED
DATA LINE FILTERS – THREE AND FOUR WIRE DATA BUS PROTECTION
NOW 4 TYPES OF HIGH END PROTECTION IN ONE BOX
A/C POWER CONDITIONING (IN BOTH THE TWO PLUS AND TWO PLUS TWO)
SURGE PROTECTION UTILIZING TVSS / HYBRID DESIGN
Specifications:
3 WIRE GROUNDED
2 WIRE UNGROUNDED
Operating Voltage
Power Rating
Amperage
Frequency
Protection Modes
Maximum Clamping Voltage
Noise Attenuation: normal mode
common mode
Filter Band Width
Total Peak Surge Current
Joules
Response Time
Indicators
Options
120VAC Single Phase
360VA/600VA/1200VA/1800VA
3/5/10/15
50/60Hz
L-N, L-G, N-G
150V
85dB @ 100kHz
50dB @ 5MHz
10kHz to 100 MHz
up to 32,500A
up to 750 joules
< 1 nanosecond
Status and fault LED
Dry contacts (for remote monitoring)
120VACSingle Phase
360VA/600VA/1200VA/1800VA
3/5/10/15
50/60Hz
L-N
150V
75dB @ 100kHz
10kHz to 100 MHz
up to 13,000A
up to 750 joules
< 1 nanosecond
Status and fault LED
Dry contacts (for remote monitoring)
DATA LINE PROTECTION (TWO PLUS TWO ONLY)
This solid state semi-conductor series offers surge protection for line to line and lines A, B, common and shield to ground.
It is designed for 3 wire and 4 wire data bus communications that require approximately 5VDC difference between line
and line. It is compatible with DeviceNet, Data Highway Plus, Modbus Plus, Genius Bus, Simatic Net, Profibus,
CompoBus/S, RS485, RS422, Twisted Pair, 3 Wire and Industrial Networks up to 100Mb/sec.
Strike Breakdown Voltage
Maximum DC Operating Voltage
Clamping Voltage
Maximum Surge Current
Maximum Capacitance
A-B Lines
Tested to UL497B
13V @ 100V/uSec, 10.5V @ 100V/Sec
9.6VDC
81V
DeviceNet
1kA
Includes 24VDC Bus protection
L-L 2.9pF, L-G 73pF
ORDERING INFORMATION:
PHYSICAL DATA (BOTH)
DIN RAIL/ FLANGE MOUNT CONTAINER
Operating Temperature: -40 to +60 C
Dimensions 110 x 75 x 110mm (4.375 x 2.75 x 4.375) inches
Weight 2kg / 4.5lbs
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Description of Model Number
PLC
Model
Style PLC
2+2
Model Type
2+2
2+0
120
15
AC
Voltage Current Rating AC Filter
3, 5, 10, 15
AC
120
240
DP
VOLTS
AMPS
120
120
120
120
220
220
220
220
3
5
10
15
3
5
10
15
UPC Order Codes
PLC 2 Plus
PLC 2 Plus 2
825433 70000
825433 71000
825433 70010
825433 71010
825433 70020
825433 71020
825433 70030
825433 71030
825433 70110
825433 71101
825433 70120
825433 71111
825433 70130
825433 71121
825433 70140
825433 71131
DCA
Data and VDC Filter Dry Contacts
DCA
DP (2+2 only)
DCB
DCC (2+0 only)
FOR MORE INFORMATION CALL CUSTOMER SERVICE TOLL-FREE AT 1-877-259-2976 Ext. 451.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
31
Always On™ UPS Systems Inc. is not your typical manufacturer. We provide engineered
solutions to fit unique applications and customer requests. Some of our engineered solutions
are shown below.
Side Mount UPS System
Din Rail UPS System
NEMA 4X UPS System
Pole Mount
UPS System
Bypass with Optional
TVSS Filter
PLC Communication
Interface
Rotary Bypass System
DC-UPS System
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
32
TTF/ILF-12015
WITH OPTIONAL BY-PASS SWITCH
The Always On™ TTF/ILF (Toroidal Isolating Line Filter) combines a low-pass series filter with a toroidal isolation transformer. The TTF/ILF
provides for total protection against all power aberrations and eliminates any troublesome constant voltages which may exist between neutral and
ground in some electrical configurations. It is totally compatible with all operating loads including high frequency switching power supplies.
Some optional features that can be added are the manual by-pass switch or an automatic bypass switch.
The manual bypass switch will transfer the load from UPS supplied power to a filtered and isolated AC utility upon user operated switching. This will
allow for removal of the UPS system without powering down or exposing your critical loads.
The automatic by-pass switch will automatically transfer the load from UPS supplied power in the event of a premature shutdown for whatever
reason without powering down your critical loads.
The TTF/ILF corrects ground fault problems and eliminates neutral voltages by re-establishing the “zero” volt ground reference point. It provides
excellent noise protection, eliminating problems caused by normal mode and common mode noise, as well as other electrical aberrations such as:
transients, spikes, surges harmonics and lightning induced voltages.
APPLICATIONS:
Computers, Laser Printers, Copiers, Point of Sale Terminals, Medical Instruments, PLC’s, Process Instruments, CAD/CAM/CIM & Robotics.
PROTECTS FROM:
Reverse Polarity, Spikes, Surges, Transients, RFI/EMI Interference, Common/Normal Mode Noise, Direct/Indirect Lightning Effects, and Voltage
between Neutral and Ground.
SPECIFICATIONS:
Frequency:
Voltage:
Amperage:
VA Rating:
Noise Protection Mode:
Technology:
Insertion Loss:
Band Width:
Response Time:
Standards:
Total Peak Surge Current:
Joules:
Leakage Current:
Operating Humidity:
Operating Temp:
Bypass Mode (TTF/ILF-12015-BP only):
Warranty:
Dimensions:
Weight:
Wall Mount:
50/60Hz
up to/240V; 1 ; Wye
15A @ 120V, 7A @ 220/240V
1,800VA Maximum
Normal Mode (L-N), Common Mode (L-G, N-G)
Dual Hybrid Series Filter/ Toroidal Isolation Transformer
Nominal 75dB, Mil-Std-220A @ 100kHz; Common Mode 120dB
Normal Mode: 10kHz - 100kHz; Common Mode: DC to 100MHz
Instantaneous
15A, 120VAC, CSA Certified
26,000A
Up to 600 Joules
Nominal <250mA (<90mA Hospital Grade)
0-97% (non-condensing)
0°C to +40°C
All outputs are powered via utility power.
5 Year
205x356x153 mm (12”x14”x6” Approximately)
20kg (44 lbs) Approximately
Standard (Tower model available)
TTF/ILF-12015 - 120VAC 15A Isolating Line Filter
UPC Order Code - 825433 00800
TTF/ILF-22007 - 220VAC 7A Isolating Line Filter
UPC Order Code - 825433 00850
TTF/ILF-12015-BP - 120VAC 15A Isolating Line Filter
w/ By-Pass Option
UPC Order Code - 825433 00810
TTF/ILF-22007-BP - 220VAC 7A Isolating Line Filter
w/ By-Pass Option
UPC Order Code - 825433 00851
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Surge / Transient Suppression: ANSI / IEEE C62.41-1992 - REV. 2 (Surge Test) TYPICAL: 120V Filter
Input:
Output (V)
N-G
L-L
L-G
L-N
Category A3 Ringwave 100kHz 6000V 200A
N/A
45V
47V
41V
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
33
AURORA SINGLE ∅ EMERGENCY LIGHTING INVERTER (ELI)
AURORA Series Emergency Lighting AC Inverters are among the most reliable central systems available for emergency
lighting and other demanding critical applications.
The AURORA Series Emergency Lighting AC Inverters are Dual Conversion, On-line, single-phase, intelligent systems for
centralized power protection and distribution. The Dual Conversion means it converts the incoming AC power to DC,
charges the batteries, then inverts the DC back into highly regulated isolated AC power. These continuous on-line
Emergency Lighting AC Inverters are available in models from 3kW to15kW.
The AURORA Series Emergency Lighting AC Inverters provide reliable and constant protection for life safety emergency
lighting, and infrastructure applications such as airports, hospitals, and residences.
FEATURES AND BENEFITS
These ELI’s provide full time self-diagnostics as well as two levels of audible alarms when the unit is operating in battery
mode. A manual test function has been incorporated into the input/test breakers that make battery testing a simple and
safe procedure. The internal bypass switch allows maintenance on the ELI’s to be performed without interruption of power
to the load.
The communications port, in conjunction with multi-platform monitoring and control software, enables the unit to be
connected to a local or networked computer system. Detailed operating information including voltages, currents, and
alarm status is available to the monitoring system.
Full Galvanic Isolation: Provides a completely isolated and re-reference output. This isolation protection provides a
proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is
completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable
fashion.
Fully digital: CPU control, flash memory, and PWM strategy are the technology corner stones of the new age of power
quality and reliability.
Extremely flexible: The AURORA Series offers tailor-made power protection to comply with your individual installation
requirements. Options include additional runtime, remote monitoring panel, and distribution panels. In addition, a
comprehensive software suite can be added for mission control and data protection-covers all your application needs.
IMBS: An internal maintenance bypass switch is standard with all AURORA single phase inverter units.
EMI suppression: An EMI filter is added to meet the international EMC limits to ensure that no noise will effect or
interfere with other equipment connected to the same AC source.
High frequency design: The inverter design incorporates high frequency, high efficiency Insulated Gate Bi-polar
Transistors (IGBT). A PWM wave, synchronized to the bypass input, triggers the IGBT’s, which invert the DC into AC
power required by the loads. This design decreases the number of required components, increases reliability and
performance while decreasing acoustic noise, size and weight.
Cold start function: The AURORA can be started without the utility AC supply being activated, or present at the input
terminal strip because our system is designed with current limiting circuitry, which allows startup of the AURORA on
battery DC power.
Intelligent charger: The AURORA will perform an automatic monthly recharge (boost charge) of the batteries as well as
automatically recharge (boost charge) the batteries when the battery voltage level decreases to approximately 2V/Cell. It
makes the batteries stay in good condition.
Intelligent battery test: The batteries are tested monthly automatically. When an abnormal condition (low charge rating,
or bad battery) is found the user will be informed immediately through alarms on the AURORA systems.
MTBF of cooling fans: Long cycling fans will operate at variable speeds necessary which is dependent on the load of the
inverter systems increasing the life expectancy of the fan motors.
OPTIONS
Output Circuit Breakers: Supports normally on or normally off circuit breakers.
Additional Run Times: These can be 30, 60, 90, or 120 minutes, other configurations are available.
EMBP: External Maintenance Bypass. This device allows the load power to be transferred from the inverter output to the
AC supply. Thus the inverter can be completely removed or repaired without interruption of power to the load.
RCMP: Remote Control and Monitoring Panel. This option provides remote alarms to indicate the inverter status.
SNMP: SNMP adapter to remotely control and monitor the unit via a network or the Internet.
RTS: Remote terminal strip
Consult manufacturer for other features and options.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
34
AURORA True Sine Wave On-Line
Single ∅ Emergency Lighting Inverter
AURORA 3KW to 15KW ELI 1Ø Input - 1Ø Output
Model
Capacity
Phase / Frequency
Rated Voltage
Voltage Range
Input
Input Current
3 kW
6kVA / 6kW
208 / 29 A
240 / 25 A
277 / 22 A
347 / 18 A
Output
208 / 14.4 A
240 / 12.5 A
277 / 10.8 A
347 / 8.6 A
208 / 60 A
240 / 53 A
277 / 45 A
347 / 36 A
208 / 74 A
240 / 64 A
277 / 56 A
347 / 45 A
208 / 113 A
240 / 98 A
277 / 85 A
347 / 66 A
208 / 24 A
240 / 20.8 A
277 / 18.1 A
347 / 14.4 A
208 / 36.1 A
240 / 31.3 A
277 / 27 A
347 / 21.6 A
208 / 48.1 A
240 / 41.7 A
277 / 36.1 A
347 / 28.8 A
208 / 72.1 A
240 / 62.5 A
277 / 54.2 A
347 / 43.2 A
50 Hz / 60 Hz ± 0.5%
< 3% Linear Load; < 5% Rectified Load
1 Hz / Second
± 4% (100% Load Change)
110% - 125% for 1 min then switch to bypass
125% - 150% for 10 sec then switch to bypass
3:1
> 85%
0ms
Hard-Wired
240 VDC
Yes
Yes
Common & Normal Mode Noise Suppression
Frequency
THD
Slew Rate
Transient Response
Overload Capacity
Crest Factor
Efficiency (AC - AC)
Transfer Time
Outlets
DC System
DC System Voltage
Output Short
Abnormal Voltage
Protection
I / O Noise Protection
I / O Spike & Transient
Protection
Communication
Interface
Display
Audible Alarms
Operating Temp.
Humidity
Environment
Audible Noise
Elevation
Safety
Safety Approval EMI / RFI
Surge / Transient
W x D x H in mm.
Physical Data
Weight in kg.
208 / 40 A
240 / 35 A
277 / 30 A
347 / 24 A
15 kW
20kVA / 23kW
208 / 240 / 277 / 347 VAC (Single Ø, 2 Wire + G)
± 2%
Voltage / Phase
Voltage Regulation
Maximum Current
5 kW
7.5 kW
10 kW
8kVA / 8kW
10kVA / 12kW
12kVA / 15kW
Single Ø (2 Wire + GND)
50 / 60 Hz
208 / 240 / 277 / 347 VAC
± 15%
Yes
130
RS 232 / Dry Contact / Optional SNMP or AS400
LCD Indicator Status Panel
On Battery, Low Battery, Overload, Fault
0 - 40°C
0% - 95% (Non-Condensing)
55 dBA At 1 Meter from Unit
3,500 meters maximum
UL1778, UL924, CSA, C22.2, CSA107.3, NFPA111
FCC Part 15 Class A
IEEE C62.41 Cat.A
1120 x 815 x 1800
450 x 725 x 1055
760
150
150
431
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Standard charger size: 3kW to 7.5kW is 5A / 10kW to 15kW is 10A.
Other voltage ratings and configurations are available; for order codes, consult manufacturer.
Consult manufacturer for available runtimes and more information.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
35
BOREALIS THREE ∅ EMERGENCY LIGHTING INVERTER (ELI)
BOREALIS Series Emergency Lighting AC Inverters are among the most reliable systems available for emergency
lighting and other demanding critical applications.
The BOREALIS Series Emergency Lighting AC Inverters are Dual Conversion, On-line, three-phase, intelligent systems
for centralized power protection. These continuous on-line Emergency Lighting AC Inverters are available in models from
8kW up to 48kW.
For redundant applications, the BOREALIS Series Emergency Lighting AC Inverters can be installed in parallel, achieving
isolated and redundant power protection. Isolated Parallel Redundant Operation (IPRO) is a feature of Always On™
BOREALIS Series Emergency Lighting AC Inverters, whereby the systems are controlled in a true peer-to-peer
configuration with redundancy in all critical elements and functions. This advanced technology provides greater system
reliability and expandability for mission critical applications.
The BOREALIS Series Emergency Lighting AC Inverters provide reliable and constant protection for mission critical
emergency lighting, and infrastructure applications such as airports, hospitals, and financial companies.
FEATURES AND BENEFITS
These ELI’s provide full time self-diagnostics as well as two levels of audible alarms when the unit is operating in battery
mode. A manual test switch has been incorporated into the input/test breakers that make testing a simple procedure. The
internal bypass switch allows maintenance on the ELI’s to be performed without interruption of power to the load.
The communications port, in conjunction with multi-platform monitoring and control software, enables the unit to be
connected to a local or networked computer system. Detailed operating information including voltages, currents, and
alarm status is available to the monitoring system.
Full Galvanic Isolation: Provides a completely isolated and re-reference output. This isolation protection provides a
proven solution to problems created by induced voltages affecting the critical loads. Since the output circuit to the load is
completely isolated and no noise induced on the neutral can permeate to the loads, systems operate in a more reliable
fashion.
Fully digital: DSP (Digital Signal Processor), flash memory, and multi-contact strategy are the technology corner stones
of the new age of power quality and reliability.
Extremely flexible: The BOREALIS Series offers tailor-made power protection to comply with your individual installation
requirements. Options include passive filter, 12-pulse rectifier, and distribution panels.
IMBS: An internal maintenance bypass switch is standard with all BOREALIS 3 phase inverter units.
EMI suppression: An EMI filter is added to meet the international EMC limits to ensure that no noise will effect or
interfere with other equipment connected to the same AC source.
High frequency design: The three phase BOREALIS design incorporates a full bridge three-phase inverter. This design
makes the BOREALIS perform better than other Emergency Lighting AC Inverters in the market when an unbalanced load
is connected.
Cold start function: The BOREALIS can be started without the utility AC supply being activated, or present at the input
terminal strip because our system is designed with current limiting circuitry, which allows Startup of the BOREALIS on
battery DC power.
Intelligent charger: The BOREALIS will perform an automatic monthly recharge (boost charge) of the batteries as well as
automatically recharge (boost charge) the batteries when the battery voltage level decreases to approximately 2V/Cell. It
makes the batteries stay in good condition.
Intelligent battery test: The batteries are tested monthly automatically. When an abnormal condition (low charge rating,
or bad battery) is found the user will be informed immediately through alarms on the BOREALIS systems.
MTBF of cooling fans: Long cycling fans will operate at variable speeds necessary which is dependent on the load of the
inverter systems increasing the life expectancy of the fan motors.
SNMP: SNMP adapter to remotely control and monitor the unit via a network or the Internet.
OPTIONS
Output Circuit Breakers: Supports normally on or normally off circuit breakers.
Additional Run Times: These can be 30, 60, 90, or 120 minutes, other configurations are available.
EMBP: External Maintenance Bypass. This device allows the load power to be transferred from the inverter output to the
AC supply. Thus the inverter can be completely removed or repaired without interruption of power to the load.
RCMP: Remote Control and Monitoring Panel. This option provides remote alarms to indicate the inverter status.
RTS: Remote terminal strip
Consult manufacturer for other features and options.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
36
BOREALIS True Sine Wave On-Line
Three ∅ Emergency Lighting Inverter
BOREALIS 8KW to 48KW ELI 3Ø Input - 3Ø Output
RECTIFIER
Input Voltage
Input Range
Input Frequency
Input Power Factor
Normal Input
Current(A) (Based on 208VAC)
Maximum Input
Current(A) (Based on 208VAC)
8kW
12kW
16kW
24kW
32kW
40kW
120/208V 277/480V 347/600V 3 phase 4 wire + G
± 15%
50 / 60 Hz +/- 7%
<1
31
47
62
93
124
155
186
39
58
78
116
155
193
232
40kW
48kW
25
30
6 PULSE : 30%
12 PULSE WITH FILTER : 9%
0% - 100% : 20 sec
98%
1%
0.50%
Current THD
Power Walk In (adjustable)
Efficiency
Voltage Regulation
Ripple Voltage
BATTERY
Battery Type
No. Of Cells
Voltage Range
Maximum Charge Current (ADC)
Battery Low Voltage
Battery Low Stop
INVERTER
DC Input Range
Wave Form
Output Voltage (Adjustable)
Crest Factor
Output Power Factor
Voltage Regulation 100% Unbalance Load
Frequency Lock Range
Output Frequency (Free Running)
Static
Output
48kW
8kW
12kW
5
7.5
8kW
16kW
24kW
32kW
Maintenance free Sealed Lead Acid
174
295 – 410VDC
10
15
20
320VDC
295VDC
12kW
16kW
24kW
32kW
40kW
285 – 415VDC
Sinusoidal
120/208V 277/480V 347/600V 3 Phase 4 Wire + G
3:01
0.8
+/-1%
45 – 55 Hz / 55 – 65 Hz
50 / 60 Hz + / - 0.1 Hz
+/- 1%
Voltage
recovering to within +/- 1% in 4 cycles
Load step 0% - 100% - 0%
Tolerance 100% unbalanced load (Ph-N)
+/- 2.5%
Phase Shift Under 100% Unbalance Load
120° + / - 6%
THD (Linear Load)
<2%
CONTINUOUS
< 110%
15 min
110 – 125%
5 min
Overload
125 – 150%
30 sec
150% - 170%
10 sec
> 170%
Efficiency (100% Load)
92%
92%
92%
92%
92%
Maximum Output Wattage (kW)
8
12
16
24
32
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
92%
40
48kW
92%
48
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8
37
BOREALIS True Sine Wave On-Line
Three ∅ Emergency Lighting Inverter
BOREALIS 8KW to 48KW ELI 3Ø Input - 3Ø Output
STATIC SWITCH
Voltage Range
Frequency Range
Efficiency
Transfer Mains -> Inverter
Inverter -> Mains
Time
Isolation With Output
8kW
12kW
16kW
24kW
32kW
+- 20% of input voltage (Line to Neutral)
45 – 55 Hz / 55 – 65 Hz
99.50%
0 ms
0 ms
YES
40kW
48kW
OVERALL CHARACTERISTICS
8kW
12kW
16kW
24kW
32kW
40kW
48kW
Overall Efficiency
90%
90%
90%
90%
90%
90%
90%
Maximum Heat Dissipation(kW)
0.79
1.18
1.58
2.37
2.93
3.47
4.17
Temperature
0 – 40°C (32 – 104°F)
Operating Environment Humidity
0% - 90% (non–condensing)
Altitude
<1500 m above sea level
Short Circuit
Yes
Lightning
MOV
Protections
EMC Filter
Input & Output
Galvanic Isolation
Between Input & Output
Indications & Alarms
LED, LCD, Buzzer
Dry Contact
Yes
Battery Start
Yes
Data Display By LCD
Yes
Audible Noise
< 65 dBA (AT 1 m)
Standards
UL 924, UL1778, NFPA111, CSA 107.1, CCMC, BMEC, FCC Part 15 Class A, EN50091-1,-2
550 x 812 x 1600
W x D x H (mm)
Physical Data
Weight(kg)
380
415
450
580
650
710
850
Specifications are subject to change without notice to reflect upgrades and improvement in technology.
Input, output voltages are 3phase 4 wire plus ground (wye) configuration.
Other voltage ratings and configurations are available; for order codes, consult manufacturer.
Consult manufacturer for available runtimes and more information.
Always On™ UPS Systems Canada Inc., #100 - 150 Campion Road, Kelowna, BC Canada V1X 7S8