Emerson V150 Instruction Manual

Add to my manuals
32 Pages

advertisement

Emerson V150 Instruction Manual | Manualzz
Instruction Manual
Form 5276
March 2000
Basis Weight Actuator
Basis Weight Control SKF Actuator with PEAB
IC2000 Stepmotor Interface
Contents
PEAB IC2000 CONTROL
CABINET
WIRE ACCESS PLATE
(ADDITIONAL PLATE ON BOTTOM)
Introduction
............................... 1
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
.............................
Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actuator and Stepmotor Interface . . . . . . . . . . . . . .
Feedback Transmitter . . . . . . . . . . . . . . . . . . . . . . . .
Driver Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
3
3
System Description . . . . . . . . . . . . . . . . . . . . . . .
4
Installation
................................. 6
Valve and Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Start Up
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Adjustment
...............................
Limit Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stroking Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve Position Indicator . . . . . . . . . . . . . . . . . . . . . .
Maintenance
15
15
16
18
..............................
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Actuator . . . . . . . . . . . . . . . . . . . . . .
Mounting the Actuator on the Valve . . . . . . . . . . .
Replacing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Actuator Motor . . . . . . . . . . . . . . . . .
Replacing Modules . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the Transformer . . . . . . . . . . . . . . . . . . .
Field Installation of the Remote Station . . . . . . . .
19
20
21
21
21
22
22
22
22
22
23
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
PLUG-IN
ELECTRONICS
MODULES
SKF
ACTUATOR
COVER LATCH
LOCK
STEPPING
MOTOR
W5392 / IL
Figure 1. Basis Weight System with Vee-Ball Valve, SFK
Actuator and IC2000 Stepmotor Interface
Introduction
Scope of Manual
This instruction manual provides instructions for application and use of the SKF actuator and PEAB (Process instrument and Electro AB) IC2000 Stepmotor
Interface in a basis weight system. Refer to the separate instruction manual for valve instructions.
D101628X012
Specifications
Basis Weight Actuator
Table 1. Specifications
Actuator Sizes
J 20HT J 30HT or J 40HT
HT denotes High Torque
Enclosure Protection
Actuator/Motor: IP54
IC2000: IP55
Remote Station: IP40
Resolution (for 90 Degrees of Valve Rotation)(2)
Size 20HT: 5600 steps
Size 30HT: 8800 steps
Size 40HT: 11300 steps
Actuator Torque
0% Backlash Rating
Size 20HT: 180 NSm (1590 lbfSin)
Size 30HT: 380NSm (3360 lbfSin)
Size 40HT: 580NSm (5130 lbfSin)
Motor Torque Required
Size 20HT: 4.3 NSm (38 lbfSin)
Size 30HT: 5.7 NSm (50 lbfSin)
Size 40HT: 7.0 NSm (62 lbfSin)
Stroking Time(2)
Size 20HT: 20 to 1120 seconds
Size 30HT: 20 to 1760 seconds
Size 40HT: 20 to 2260 seconds
Stepping Speeds (programmable)
Slow: 5–1000 steps/sec
Fast : 600–1000 steps/sec
Gear Ratio(2)
Size 20HT: 1:56
Size 30HT: 1:88
Size 40HT: 1:113
Actuator Rotation
0 to 90 degrees
Motor Drive
Type: Bipolar, 20 KHz chopper
For Stepmotor Types: 2-phase, hybrid or permanent
magnet, 1mH to 10mH per phase, in 4, 6 or 8 wire
configuration
Current Adjustment: 2.1 to 3.0 A per phase, in 0.3 A
increments
Operation Modes: Half-step (default, for highest resolution) or full-step
Short Circuit Protection: Logic automatically interrupts motor currents when a phase-to-phase or
across-phase fault occurs. Power must be cycled to
reset the fault.
Maximum Distance from IC2000 to Actuator
40 m (132 ft) with 1.5 mm2 conductor
100 m (320 ft) with 2.5 mm2 conductor
Control Signal (Customer Supplied)(3)
Increase: Opens valve
Decrease: Closes valve
Slow Speed: Switches to the slow step speed
Temperature Range
Actuator: -20 to 60_C (-4 to 140_F)
IC2000: -20 to 50_C (-4 to 122_F)
Stepmotor: -20 to 40_C (-4 to 104_F)(5)
Power Requirements
IC2000: 117, 220, or 240 Vac at 50–60 Hz, 225 VA
Remote Station: 24Vdc(4)
Position Feedback
Transmitter Type: 4–20 mA, 2 wire transmitter, max
load 1 K ohm
Input Potentiometer: 1 K ohm over 320_ rotation,
Independent linearity +/– 0.5% of 320_ (+/–1.8% of
90_), Repeatability 0.1% over 90_
Approximate Weight
IC2000: 21 kg (47 lbs)
Size 20HT: 16 kg (35 lbs)
Size 30HT: 36 kg (80 lbs)
Size 40HT: 61 kg (135 lbs)
Remote Station: 1.4 kg (3.2 lbs)
Dimensions
See figure 2 and Bulletin 51.3:V150 (S1)
1. The pressure/temperature limits in this manual, and any applicable code or standard limitation, should not be exceeded.
2. SKF Crab Actuators using 50 tooth step motors in half-stepping mode have these characteristics for 0–90_ travel. The fastest stroking speeds are approximate. The torque falls off as
speed increases, and the motor may stall before the theoretical highest speed is reached.
3. Each control signal is normally asserted by pulling the input low through external relay contacts. The increase/decrease signals are optically isolated. The speed control input closes a
24 volt relay coil circuit. A factory option is available for Open-Collector logic supplied by 24 Vdc/8 mA from an external power supply.
4. When factory supplied, a bridge rectifier is mounted in the IC2000 to develop this from one of the power transformer windings. If field mounted, customer supplies the 24 Vdc power.
5. Free air ating at max current. Based on still air in motor without air sinks.
2
Basis Weight Actuator
Only personnel qualified through training or experience
should install, operate, or maintain this equipment.
Fast Input (pin 20a). Connect to 0v to run the internal
oscillator at the fast rate.
Do not attempt to install, operate, or maintain this
product without this instruction manual and the valve
instruction manual. If you have any questions concerning these instructions, contact your Fisher Controls
sales office or sales representative before proceeding.
Slow Input (pin 22a). Connect to 0v to run the internal
oscillator at the slow rate.
Specifications
Valve
Refer to the appropriate valve instruction manual for
specifications.
Rate Adjust Inputs (pins 24a, 24c, and 26a). The
speed of the internal oscillator is determined by external potentiometers connected across the appropriate
inputs. The normal values are 100K for the fast control
and 500K for the slow control, and these will give the
specified speed ranges. Higher values may be fitted to
reduce the minimum speed in each range.
Direction Input (pin 26c). Connect to 0v to reverse
the direction of motor rotation. This input should not be
changed when the ‘‘clock’’ input is low or while the motor is running above its start/stop speed.
Actuator and IC2000
See the Specifications table.
Driver Card
Internal Clock Output (pin 28a). This is the output of
the internal oscillator which will normally be connected
to the clock input of the drive (pin 28c). The output
consists of low–going pulses approximately 25mS
wide.
Description of Terminal Functions
Motor Phases 1A, 1B, 2A, 2B (pins 2, 4, 6, and 8 on
both rows). Connect one phase of the motor to 1A and
1B, and the other phase to 2A and 2B. To reverse the
direction of rotation relative to the direction input, interchange the connections to 1A and 1B.
+24 DC Out (pin 10, both rows). Use this output to
supply an external control module such as an indexer
card. The maximum current which may be drawn is
250 mA.
Logic Supply Inputs 1 and 2 (pins 12a and 14a).
When the drive is AC–powered, these two inputs are
connected to a center–tapped secondary on the power
transformer rated at 18–0–18 volts RMS. The center
tap is connected to power commom (pins 16 & 18,
both rows).
Motor Supply Inputs (pins 12c and 14c). For operation at a motor supply of 24v, these inputs may be driven from the same transformer secondary as the logic
supply. An extended secondary rated at
26–18–0–18–26 volts RMS is required for operation at
36v, with the motor supply inputs fed from the 26–volt
taps.
Clock Input (pin 28c). The motor will step following a
low–going pulse on this input, the step occurring on
the rising edge of the pulse. The input should remain
low for at least 10mS, It may be driven from an external
oscillator card or the internal oscillator in the drive. The
latter method is used in the IC2000
Energize Input (pin 30c). The motor will be energized
with this input connected to 0v. Link 4 may be fitted as
an alternative to making an external connection to 0v.
Note that the drive should not be de–energized when
the motor is running at speed.
External Reference Input (pin 32a). The motor current may be programmed by means of an external resistor connected between this input and signal 0v
(32c). A 1K resistor will give approximately half the
rated current. This input is used to control the standby
or “braking” current in the IC2000.
Signal 0V (pin 32c). Use this pin as a return connection for the current programming resistor.
Two internal fuses are fitted to the drive power supply
circuits. These are 20 mm quick–blow types and are
rated in the specifications table.
3
Basis Weight Actuator
Dimension
20HT
30HT
40HT
455
228
122
80
176
85
60
10.5
92
72
565
286
134
100
230
115
80
12.5
116
92
17.9
8.98
4.80
3.15
6.93
3.35
2.36
0.41
3.62
2.83
22.2
11.22
5.28
3.94
9.06
4.53
3.15
0.49
4.57
3.62
mm
A
B
C
D
E
F
G
H
K
L
306
155
90
50
120
50
35
8.5
63
46
A
B
C
D
E
F
G
H
K
L
12.0
6.10
3.54
1.97
4.72
1.97
1.38
0.33
2.48
1.81
Inches
L
B
F
G
K
H
D
C
E
A
E0010 / IL
Figure 2. Actuator Dimensions
System Description
The SKF actuator, IC2000 Stepmotor Interface, and
Vee–Ball valve is a control system intended for basis
weight control. The system requires a 117, 220, or 240
Vac power supply and a control signal (provided by the
customer) that consists of a contact closure for increase in valve position and a contact closure for decrease. The system consists of the following standard
and optional components.
The Vee–Ball Valve, a Design V150 or V200, is the
final control device that controls the amount of process
flow.
4
The SKF electrically operated actuator provides rotary
motion to open and close the valve. A stepping motor
in the actuator drives a ball screw. The linear motion of
the ball screw nut is transmitted to the valve shaft
through a rack and pinion arrangement and a
clamped, splined actuator–to–valve connection. Also
included in the actuator are a potentiometer (used to
provide a valve position feedback signal), limit
switches to shut off motor control signal when the travel limit is reached, a handwheel for manual operation
of the valve, and a valve rotation indicator. The handwheel can be operated only when no power is applied
to the actuator and Stepmotor Interface. The hand-
Basis Weight Actuator
COUPLING HOUSING
DESIGN V150 VALVE
MOUNTING
BRACKET
MOTOR MOUNTING
SCREWS
Terminal Blocks—All field connections including control signals are made to terminal block TB1, TB2 or
optional TB3 (see figure 9).
IC500 Interface Card—This card (key 3, figure 5) receives the control signal, which is sent from a customer–supplied control device, from the manual station
(key 4, figure 5), or from the optional remote station
(see figure 6).
STEPMOTOR
HANDWHEEL
INDICATOR
COVER
INDICATOR ASSEMBLY
W5393 / IL
Figure 3. SKF Actuator with Design V150 Valve
wheel is intended for use during power outages or
when ac power has been removed at the external circuit breaker box.
The PEAB IC2000 Stepmotor Interface contains the
circuit cards necessary to operate the actuator. The
Stepmotor Interface is provided with a lock to discourage unauthorized access. Keep the key in a secure
location where only authorized people can get it.
All of the circuit components are plug–in modules.
Each component is mounted to a faceplate that is visible from the front of the Stepmotor Interface. Use the
faceplate handle to pull the plug–in module (component) out of the cabinet. Connections between the
modules and the Stepmotor Interface are gold–plated
edge connectors.
Table 5 describes how each card within the IC2000 is
connected to the other cards. Each card has two columns of pins labeled 2a, 4a, and up to 32a (also 2c,
4c, and up to 32c). The table indicates that 2ca is 24 V
and 32ca is ground, which is connected to power common (terminal 10 on terminal block TB1).
See figure 14 for information in the Input Signal Wiring
section. Also see the External Control Signal portion of
the Wiring section.
Included as standard in the Stepmotor Interface are:
SD13 Driver Card—This card (key 1, figure 5) sends
pulses to operate the stepping motor. See the Driver
Card section.
Power Transformer– This 225 VA toroidal transformer, mounted on the power supply backplane (see figure 7), supplies internal power.
The inputs are optically isolated. The card has four
direct inputs, two for manual operation of the actuator,
and two for computer operation of the actuator. The
IC500 gates the internal oscillator to the driver card
when input is low. If there is no low input, a transistor
sets the current to the motor at the standby “braking”
value to provide stiffness (holds the valve in position).
See figure 5. The IC500 card includes screwdriver adjustments on the lower half of the front panel for actuator motor speed for both manual (MAN) and computer
(COMP) operation. Normally, a low speed is used for
computer operation, and a high speed is used for
manual operation.
The faceplate also has four LEDs on the interface
card. The LEDs allow you to verify that signals are
reaching the card. Different LEDs are provided for signals intended to open (INC) or close (DEC) the valve
in both manual (MAN) or computer (COMP) operation.
FT100 Motion Feedback Transmitter—This transmitter (key 5, figure 5) senses actuator feedback potentiometer resistance and provides a proportional 1 to 5
volt signal for internal use (valve position indicator)
and a proportional 4 to 20 mA dc signal for external
use (extra valve position indicator or input to a remote
computer).
Manual Station—This module (key 4, figure 4) allows
selection between manual and computer operation of
the actuator and valve. It also provides the means to
open or close the valve from the Stepmotor Interface.
It includes the digital valve position indicator (0–100%)
which is driven by the FT100 0–1 V output line.
For manual operation, press and release the local control button. Then, rotate the DEC–INC knob toward
DEC (decrease) to close the valve or toward INC (increase) to open the valve. If you turn the knob all the
way to DEC or INC, the knob will remain engaged, and
the valve will open or close until a limit switch stops
motor operation.
5
Basis Weight Actuator
INDICATOR BOX
ACTUATOR
1
OPTIONAL
REMOTE STATION
2
NOTES:
132 FEET (40m) MAX. WITH 1.5mm2 CONDUCTORS
1
320 FEET (100m) MAX WITH 2.5mm2 CONDUCTORS
MAX 1000 FT, (255m) WITH 0.75mm2 CONDUCTORS
2
A3754-4 / IL
Figure 4. Actuator and Controls
Note
For additional information on use of the
manual station when there is no remote
station, see the External Control Signal
portion of the Wiring section.
The Valve Position Indicator is a LED panel meter that
displays valve position from 0 to 100 percent. It is
mounted in the manual station.
The two additional options for remote position indication are the remote station described below and a customer-supplied, remote indicator that can be connected to the control box. See figure 6 and the
Optional Remote Position Indication portion of the Wiring section of Installation.
Remote Station (Optional)—This station (figure 6)
allows manual control of the actuator and valve from a
location up to 1000 feet (305 meters) from the Stepmotor Interface. Maximum allowable distance between
the Stepmotor Interface and the remote station depends on wire size. The limit is 1000 feet (305 meters)
for a wire size of 0.75 mm2 (approximately 18 AWG).
Operation of the remote station overrides operation of
the manual station located in the Stepmotor Interface.
When the system is equipped with this remote station
and is under computer control, the manual station in
the Stepmotor Interface cannot gain control of the system, until you first switch the remote station to MAN
(manual).
6
For manual operation of the valve from the remote station, turn the MAN–COMP knob to MAN (manual).
Then, press and release the remote control button.
Now you can rotate the DEC–INC knob toward DEC
(decrease) to close the valve or toward INC (increase)
to open the valve. If you turn the knob all the way to
DEC or INC, the knob will remain engaged, and the
valve will open or close until a limit switch stops motor
operation. If you wish to operate the valve in slow
speed from the remote station, press the remote control button and continue to press it while using the
DEC–INC knob.
Installation
Valve and Actuator
Normally, the actuator is shipped mounted on the
valve body. After you have wired the actuator, install
the valve in the pipeline by following instructions in the
separate valve instruction manual.
It is easier to determine the fully open and closed position of a valve when the valve is out of the pipeline. If
possible, check the operation of the actuator limit
switches and of the valve position indicator before
installing the valve in the line. Refer to the Adjustment
section to check the operation of the limit switches and
indicator.
If the actuator and valve have been purchased separately or if the actuator has been removed for maintenance, mount the actuator on the valve by following
the Mounting the Actuator instructions in the Maintenance section.
Basis Weight Actuator
1
E0011 / IL
Figure 5. IC2000 Control Cabinet Components
Required valve shaft rotation is not the same for all
valves. Design V150 and V200 valves require clockwise valve shaft rotation to open the valve; valves in
the 8500 Series require counterclockwise rotation to
open the valve. Before mounting the valve, check to
see that the actuator will provide the correct rotation to
open and close the valve. If the rotation is not correct,
change the rotation direction by changing the switch
Settings and jumper locations on the control cards.
Refer to the Settings section.
E0012 / IL
Figure 6. Remote Station
Always use the standard mounting position shown in
figure 17 and check for proper rotation before installing
the actuator on the valve. Other mounting positions
might provide incorrect valve rotation.
Wiring
CAUTION
WARNING
Incorrect valve shaft rotation can damage internal valve parts. To avoid such
damage, be certain that the actuator will
provide the correct rotation direction for
the valve you are using.
Never make adjustments to the drive
current or terminal connections while
power is applied. Personal injury or
property damage might result.
7
Basis Weight Actuator
A5966 / IL
Figure 7. Remote Station Dimensions
For assistance in wiring, refer first to the overall schematic in figure 8 which includes references to more
detailed wiring schematics that show specific sections
of the system. Also refer to figure 9 for a schematic of
the power transformer connections.
The Stepmotor Interface has a wire access plate on
top and bottom. Connect all wires through one of those
plates.
Note
Wire sizes are shown in the schematics in square millimeters (mm2). Approximate equivalents in AWG sizes
are:
mm2
AWG
0.50
20
0.75
18
1.5
16
2.5
12
Schematics for some special inputs (for example, input
from a Rolm computer) are not included in this instruction manual. If the schematics in this manual do not
appear to cover your equipment, determine the serial
number of the unit, and contact your Fisher Controls
sales office or sales representative.
Motor, limit switch, and feedback potentiometer wiring
is connected to the actuator before the unit is shipped.
The limit switch and feedback potentiometer wires are
provided with an appropriate connector at the actuator.
It is necessary to connect the other ends of these
wires to the Stepmotor Interface, as well as the alternating current power and connecting wires from your
computer or other controlling device to the Stepmotor
Interface.
8
It is necessary to drill holes in one of the
wire–access plates and provide connectors for the power supply wires and the
control wires from your computer or
controlling device.
WARNING
To avoid personal injury from electrical
shock, keep hands and tools out of the
Stepmotor Interface and away from the
terminal connections on the actuator
whenever power is applied to the control
box or actuator. Always disconnect power before making or checking electrical
connections.
Remove the screws and the appropriate wire access
plates. Drill the required size holes and install connectors that are appropriate for the installation location.
Replace the wire–access plate. Be sure to tighten the
connector and access plate securely.
Unlock the cabinet and open it. Then proceed to the
following instructions.
Basis Weight Actuator
Note
Motor
Refer to figure 10. Use the wire color codes and terminal numbers as shown in figures 9 and 10 when connecting motor wires to terminal block TB1.
Note
The wire color codes are subject to
change per availibility of cable. The connections should be verified at both ends.
Limit Switches
Limit switch LS1 and LS2 (figures 11 and 12) interrupt
the input commands when the valve reaches the fully
open (LS1) and fully closed (LS2) positions. Use the
wire color codes and terminal numbers in figures 10,
11 or 12 when connecting the wires to terminal block
TB1.
Valve Position Potentiometer
A potentiometer located behind the valve rotation arrow on the actuator is used to operate the FT100 and
the digital meter on the manual station (key 4, figure
4). Use the wire color codes and terminal numbers in
figure 15 when connecting the wires to terminal block
TB1.
Power Supply
Connect an ac power supply of the correct voltage
(117, 220, or 240 Vac as specified on your order) to
terminal block TB2 (figure 9). The terminal block has
different terminal connections for different supply voltages. Fuses F1, F2, and F3 are provided in a bag with
the actuator. Determine the correct fuse from figure 9.
1. Locate the correct fuse and install it in the correct
terminal.
At power up the Manual Station is in Remote Control mode, but will pass the remote INC/DEC signals to the IC500 MAN
(fast) inputs. (This provides a means to
drive the MAN (fast) from a Remote Station option.)
To select the slow preset speed, the COMP/MAN input
(TB1–14) must be held low. However, when TB1–14 is
low, the remote device always overrides any local attempt to gain control. (The local INC/DEC switch is
locked out.) If the Remote Station option is not being
used, TB1–14 can be controlled in several ways.
1. Remote Lockout: The COMP/MAN input may be
controlled by a third set of relay contacts on the remote device that are configured to close whenever the
remote device desires to be in command of the valve.
To provide a means of locking out the remote commands while operating the valve from the Manual Station, install a switch at the IC2000 cabinet (e.g. in one
of the blank front panels), to open this line to TB1–14.
Label this switch “Remote Lockout” at its open position, and open it before pushing the LOCAL request
button on the Manual Station front panel. When finished using the Manual Station, set the “Remote Lockout” switch back to the closed position. The next request for control by the remote device will then switch
the Manual Station back into remote mode.
2. Local Lockout: The COMP/MAN input may be controlled solely by a switch installed by the user at the
IC2000 cabinet. The switch should be wired to connect
TB1–14 to TB1–10 when closed. Label it “Local Lockout” at this position. When manual control is desired,
open this switch and press the LOCAL request button
on the Manual Station front panel. When finished using
the Manual Station, set the “Local Lockout” switch
back in the closed position, and the Manual Station will
immediately revert to remote mode.
5. Provide 24 Vdc power to the remote station.
3. “Dead Man” Switch: The COMP/MAN input may be
controlled by wiring the TB1–14 input to the normally
closed contact of the LOCAL request switch on the
Manual Station front panel. When the LOCAL request
button is released, the Manual Station will always be in
remote mode. The user will have to press and hold the
LOCAL request button with one hand and operate the
Manual Station INC/DEC switch with the other to move
the valve from the Manual Station.
External Control Signal
4. If you have specified the optional remote station,
refer to figure 18 for a wiring schematic.
Manual Station Input Wiring
IC500 Inputs
4 basic command signals are sent to the IC2000 (3
external and 1 internal) when using the Manual Station
module between the user’s signals and the IC500 interface module. See table 2.
The IC500 may be driven directly by remote INC/DEC
signals, bypassing the Manual Station. However, only
the slow input terminals of the IC500 are brought out
to the terminal block. Therefore, if local manual control
2. Connect ground to the terminal block.
3. Connect the neutral wire (ACC or ac common) to
terminal 4 and then connect the line to the appropriate
terminal (1, 2, or 3).
4. Be sure that terminal 7 on terminal block TB2 is
connected to ground (GND––yellow–green) on TB2.
9
Basis Weight Actuator
ONLY ONE OF
THESE INSTALLED
E0013 / IL
Figure 8. System Schematic (Contact Closure Input)
10
Basis Weight Actuator
Table 2. Manual Station Inputs
Manual
Station Input
Terminal
Type of Circuit
Assert By
Effect While Asserted
INC
TB1–15
24V optoisolated
grounding to TB1–10
Commands the actuator to run in the direction to open the
valve, provided “max. open” limit switch is not tripped.
DEC
TB1–16
24V optoisolated
grounding to TB1–10
Commands the actuator to run in the direction to close the
valve, provided “max. closed” limit switch is not tripped.
COMP/MAN
TB1–14
24V relay coil
grounding to TB1–10
LOCAL
Normally open, momentary
panel switch
24V relay coil
Push and release
Selects remote control of the IC2000 and the slow preset
speed. Locks out local requests for manual operation.
(When not asserted, the fast preset is selected.)
Latches the IC2000 in Local Mode and fast preset speed.
Can be released only by asserting the COMP/MAN input.
Table 3. IC500 Inputs
Manual Station
Input
Terminal
Type of Circuit
Assert By
SLOW/INC
TB1–18
24V optoisolated
grounding to
TB1–10
SLOW/DEC
TB1–19
24V optoisolated
grounding to
TB1–10
FAST/INC(1)
IC500–14a rack slot
K28
24V optoisolated
grounding to
TB1–10
FAST/DEC(1)
IC500–16a rack slot
K28
24V optoisolated
grounding to
TB1–10
Effect While Asserted
Commands the actuator to run in the direction to open the
valve, at the preset slow speed, provided “max. open” limit
switch is not tripped.
Commands the actuator to run in the direction to close the
valve, at the preset slow speed, provided “max. closed” limit
switch is not tripped.
Commands the actuator to run in the direction to open the
valve, at the preset fast speed, provided “max. open” limit
switch is not tripped.
Commands the actuator to run in the direction to close the
valve, at the preset fast speed, provided “max. closed” limit
switch is not tripped.
1. Non–field accessible.
is desired at the IC2000 cabinet, the Manual Station or
a customer-supplied interface card will be required.
to generate INC/DEC signals by comparing the position command to the valve position feedback, and an
The user is responsible for selecting the COMP (slow)
INC/DEC inputs, or the MAN (fast) INC/DEC inputs,
and insuring that only one set is used at a time. Asserting more than one of the IC500 inputs simultaneously may have unpredictable results. See table 3.
additional terminal block to accommodate the new
signal interface. A small reduction in resolution may
occur with this system, since some hysteresis must be
built in to the comparator to prevent “hunting” behavior. Contact the factory for help with this option.
Input Signal Options
Optional Remote Position Indication
You can use relay contacts or open collector transistor
outputs to control the standard IC500 interface module.
If you desire, use terminals 8 (positive) and 9 (negative) to supply a 4 to 20 mA dc signal for remote indication of valve position. Other indicators may be connected in series. Total load is 1000 ohm. See figure
18. At these terminals, a 4 to 20 mA dc signal represents 0 to 90 degree valve position.
To assert the inputs by applying a positive voltage signal from the controlling computer, you can request the
“ROLM OPTION” as a special build, and the additional
circuitry will be mounted in the IC500 card to accept
the positive signals. However, if using the Manual Station, the COMP/MAN signal must still be asserted by
pulling it low, since it closes a relay coil circuit.
A special construction is available to accommodate a
4–20 mA position command signal from a user system. This requires an input signal isolator, a positioner
Completing the Wiring
After completing the wiring, tighten the wire access
plate screws and connectors where they connect to
the access plate.
Complete the steps in the Settings section before
proceeding.
11
Basis Weight Actuator
Table 4. SD13 Card Functions
Link
Default
Setting
Position
Function
Comments
A–B
STANDBY
OUT
No standby
(braking)
current
selected
B–C
STANDBY IN
50% standby
(braking)
current
selected
*
D–E
HALF
Half-stepping
mode selected
(maximum
resolution)
*
E–F
FULL
G–H
ENERGIZE
H–I
DE-ENERGIZE
1
2
3
Full-stepping
mode selected
Motor
permanently
energized
Motor
energized via
control signal
Note
*
Settings
Before starting the actuator, use the following steps to
check to be sure that all switch and jumper selections
are correct for the desired action of your system.
1. Unlock and open the cover. Loosen the appropriate
captive screws.
2. Unplug the motor drive (key 1, figure 5). Locate the
jumpers on the card.
The programming links on the SD13 drive card allow
the user to tailor the operating mode to the application.
Table 4 describes the usage of the first 3 links in brief.
3. Make sure that the current limit jumpers are properly set. For size 20HT (2.4A), link 4 should be set to
short pins L-M; and for sizes 30HT and 40HT(2.7A),
link 4 should be set to short pins K-L.
4. Plug the motor drive back into the IC2000.
5. Unplug the IC500 module. On the side of the card
are two rows of jumper packages labeled A4 through
A7 and A1 through B3. A4 through A7 are set at the
factory; do not change these jumpers. The table in figure 16 indicates the correct jumpers that are to be
used on IC500 and FT100.
6. Look at the top of each jumper set. You can see a
strip of metal where there is a jumper and no metal
where there is no jumper. If the jumper location does
not match that required by figure 16, pull the jumper
assembly out of the card, invert the assembly, and re–
insert it in into the card.
12
For example, for the standard mounting position and
standard rotation, there should be a jumper at B1, A2,
and A3, and there should be no jumper at A1, B2, and
B3.
Jumpers A4, A5, A6, and A7 are set at
the factory and are not field selectable.
7. Plug the IC500 module back into the cabinet.
8. Unplug the FT100 module. For the FT100 card, the
jumper should be at A for reversed rotation (increasing
signal rotates valve shaft counterclockwise) and at B
for standard rotation (increasing signal rotates valve
shaft clockwise).
9. Plug the FT100 module back into the cabinet.
Tighten the captive screws, close and latch the cover.
Start Up
1. Be sure you have completed the Wiring section and
that you have set all switches and jumpers as described in the Settings section.
2. Check to be sure that the correct power supplies
and logic signal have been supplied.
WARNING
If the valve is out of the pipeline, keep
hands and tools away from the valve
when adjusting or stroking the valve.
The valve disk or ball opens and closes
with a shearing action that can injure
hands or damage tools.
3. Remove ac power at the external circuit breaker
box before using the handwheel. Use the handwheel
to carefully rotate the valve to the fully closed position.
Be careful to avoid rotating the valve ball or disk too
far into its seat. (If necessary, refer to the valve body
instruction manual to determine the fully closed position.):
a. As the valve reaches the fully closed position,
listen carefully to be sure the limit switch activates
when the valve reaches the fully closed position.
(The limit switches are located under the indicator
cover. You can hear a click as the limit switch is
activated.) If adjustment is required, refer to the
Adjustment section.
b. Repeat the process to check the limit switch at
the fully open position.
Note
Check the limit switch when you release,
or close, it. If the mounting screws are
Basis Weight Actuator
JUMPER
E0014 / IL
Figure 9. Transformer Schematic
over-tightened, the switch action may
not allow the switch to close after it has
been tripped.
4. Turn on power to the Stepmotor Interface.
5. Check to be sure the valve rotation indicator in the
Stepmotor Interface and in the optional remote station
show zero percent for 0 degrees of valve rotation (fully
closed) and 100 percent for 90 degrees of valve rotation (fully open). Refer to the Adjustment section for
adjustment instructions.
6. Adjust the stroking speed with the adjustments on
the IC500 card faceplate (key 3, figure 4). Clockwise
rotation of the adjustment increases the speed. If the
speed increases too much, the the torque will drop off
and cause the motor to stall.
With no pressure applied to the valve, apply a signal to
operate the valve in both directions (opening and closing) and in both the manual (MAN) and computer
(COMP) operating modes. As the valve ball or disk is
rotating, adjust speed until the motor operates smoothly and as quietly as possible. If the valve moves with a
jerky motion, continue to adjust the speed. Refer to the
Stroking Speed section for more information.
After the valve is in service, you can adjust the speed
again. If it appears that motor torque is too low, decrease stroking speed.
13
Basis Weight Actuator
E0015 / IL
MOTOR TERMINAL BOARD
Figure 10. Motor Connection Schematic
14
Basis Weight Actuator
(CABLE OD = 9.1mm)
NOTE:
LS1 & LS2 OPEN THE COMMAND CIRCUITS TO STOP THE ACTUATOR
AT THE LIMIT CONDITIONS.
E0016 / IL
Figure 11. Limit Switch Connection Schematic, 2 Limit Switches (Standard)
Adjustment
Limit Switches
The Basis Weight Assembly is standardly shipped with
2 limit switches. 4 limit switches can be wired by the
customer.
1. Mark the position of the actuator travel indicator
cover (figure 2) so that you can return it to the same
position after adjustment. Loosen the screws and remove the actuator position indicator.
2. Use the handwheel to position the actuator to 0 degrees rotation (fully closed). If necessary, refer to the
valve body instruction manual to determine the fully
closed position.
3. Loosen (slightly) the two screws on the limit switch
for 0 degrees rotation (LS2). Move the switch until you
can hear a click, which indicates that the switch has
been actuated.
4. Tighten the limit switch screws.
Note
Check the limit switch when you release,
or close, it. If the mounting screws are
15
Basis Weight Actuator
INSTALLED AT
FACTORY IN
DIN RAIL
(O.D. = 10.7mm)
E0017 / IL
Figure 12. Limit Switch Connection Schematic, 4 Limit Switches (Optional)
over-tightened, the switch action may
not allow the switch to close after it has
been tripped.
5. Use the handwheel to position the actuator to 90
degrees rotation (fully open).
6. Repeat steps 3 and 4 for the limit switch for 90 degrees rotation (LS1).
7. Replace the travel indicator cover and screws.
Stroking Speed
Stroking speed adjustments for the manual (MAN) and
automatic (COMP) modes are on the faceplate of the
16
IC500 card (key 3, figure 4). If it appears that motor
torque is too low, decrease stroking speed.
Note
In this manual, the default half-step increment is referred to as a step.
The two trim potentiometers (screwdriver adjustments)
on the front panel of the IC2000 are for setting each of
the selectable preset speeds. The slowest speed is
approx. 600 steps/second in Manual mode and
approx. 5 steps/second in Computer mode; this speed
is governed by trim potentiometer resistance. The
Fastest speed is about 20 seconds for full stroke in
Basis Weight Actuator
(PANEL ADJUST.)
VOLTAGE
AMP
CURRENT
DRIVER
(0–1 V)
(PANEL
ADJUST.)
(FACTORY
ADJUST.)
(FACTORY
ADJUST.)
INPUT TO
POSITION
INDICATOR
E0019 / IL
Figure 13. Valve Position Indicator Block Diagram
both modes, and is governed by the torque dropping
off enough that the motor stalls.
The stroking time is controlled by the frequency of the
internal oscillator. The oscillator triggers the stepper
motor drive card to provide properly phased currents
to the various windings of the stepper motor. The sequence of energization of the windings is designed to
move the rotor one motor step per oscillator pulse. In
this stepping mode, 400 positions are available per
motor revolution. The gear ratio of the specific actuator
then determines how many motor revolutions are required to produce 90 degrees of output shaft rotation,
providing the multiplier to determine the resolution of
the valve travel.
The shortest contact closure to which the IC2000/SKF
will respond depends on the setting of the computer
mode speed potentiometer and the time skew between
the user’s gating signal and the IC2000’s internal oscillator.
The output of the oscillator is an asymmetric pulse signal which is low for about 25 microseconds of the period. The stepper motor is guaranteed to move one step
if the signal to the driver card has been low for at least
10 microseconds prior to going high again. However,
there is no way to synchronize the DCS contact closures with the internal oscillator. So, the external contacts must be held closed for 10 microseconds longer
than the period of the oscillator to guarantee at least
one step movement of the motor. On occasion, this
length of contact closure will result in 2 steps movement (specifically when the contact closure happens to
occur simultaneously with the beginning of the oscillator low phase).
Therefore, if you had an oscillator set up for 10.1 steps
per second (99msec/step) and sent an Increment command that lasted 200 milliseconds, you would move
the valve 2 steps in the open direction.
17
Basis Weight Actuator
+24V
JUMPER IN B1 POSITION
INC
LIM
FAST
INC
DEC
LIM
FAST
DEC
SLOW
INC
SLOW
DEC
BRAKING CURRENT
1
SET
COMMON
FAST INPUT
DIRECTION
INPUT
SLOW INPUT
SD13
DRIVE
CARD
POWER
COMMON
+24DC
STOP CURRENT
STOP CURRENT
RETURN
RATE COMM
FAST RATE
SLOW RATE
SPEED
SETTINGS
NOTE:
1 SEE WIRING SECTION FOR TB1-14.
E0027 / IL
Figure 14. Overall Connection Schematic for IC500/Manual Station/SD13
Valve Position Indicator
The indicator is located on the manual station (key 4,
figure 4), and it shows 0 to 100 percent of valve travel
as the valve travels from 0 to 90 degrees rotation.
Another indicator is located on the optional remote station (figure 5).
To adjust the indicator (key 4, figure 4), proceed as
follows:
18
1. Position the valve at 0 degrees rotation (fully
closed).
2. The meter should now show zero percent. If it does
not show zero, rotate the zero screw on the FT100
station faceplate.
3. Position the valve at 90 degrees rotation (fully
open).
4. The meter should now show 100 percent. If it does
not show 100 percent, rotate the span screw.
Basis Weight Actuator
WITH THIS CONNECTION TO COMPUTER THE ACTUATOR
CAN ONLY RUN WITH SLOW SPEED.
CR1=INCREASE
CR2=DECREASE
NOTE:
IF THE MANUAL STATION IS INSTALLED, CONTROL CONFLICTS MAY OCCUR, SEE WIRING SECTION.
E0021 / IL
Figure 15. Control Connection Schematic without Remote Station and without Manual Station
5. Check the meter again at 0 degrees rotation to be
sure zero has not changed.
Maintenance
WARNING
Avoid personal injury from sudden release of process pressure. Before performing any maintenance operations:
D Shut off any line providing, electrical power or a control signal to the actuator and Stepmotor Interface. Be sure
the actuator cannot suddenly open the
valve.
D Use bypass valves or completely
shut off the process to isolate the valve
from process pressure. Relieve process
pressure on both sides of the valve.
Drain the process media from both sides
of the valve.
D Keep power off when working in the
Stepmotor Interface.
A brief troubleshooting guide is provided below. Following the troubleshooting guide are maintenance procedures that can be completed in the field. For other
maintenance, return the actuator to Fisher Controls.
Due to the care Fisher Controls takes in meeting all
manufacturing requirements (heat treating, dimensional tolerances, etc.), use only replacement parts supplied by Fisher Controls.
19
Basis Weight Actuator
1. STANDARD:
CONTACT CLOSURE OR
OPEN COLLECTOR LOGIC INPUTS
2. OPTIONS:
POSITIVE VOLTAGE PULSES
FOR OPTION, CONTACT FACTORY AND SPECIFY YOUR
INPUT.
ROTATION
(BOTH IN
STD
RIGHT
HAND
MTG)
CCW
B1
B2
B3
A
CW
B1
A2
A3
B
JUMPER SETTINGS
IC500
FT100
NOTE:
JUMPERS A4, A5, A6, AND A7 ARE NOT FIELD SELECTABLEUNLESS THIS OPTION HAS BEEN INSTALLED AT THE FACTORY.
E0020 / IL
Figure 16. Jumper Configurations
Troubleshooting
Table 5 describes how each card within the IC2000 is
connected to the other cards. Each card has two columns of pins labeled 2a, 4a, and up to 32a (also 2c,
4c, and up to 32c). The table indicates that 2ca is 24 V
and 32ca is ground, which is connected with power
common terminal 10 on terminal block TB1. See the
Wiring section for more information on the correct connections.
If the actuator will not operate,
1. Check to be sure that the power of the correct voltage is reaching the terminal block in the Stepmotor
Interface. Also check to be sure that the power supply
is connected to the appropriate terminal.
20
2. Check the fuses on terminal block TB2 and check
fuses FS1 and FS2 on the SD13 card. Replace fuses if
necessary.
3. Check the LEDs (light–emitting diodes) on interface
card IC500 light when a signal is applied to the control
box. The LEDs should turn on in response to an applied signal. If the LEDs do not turn on, no signal is
reaching the card. The limit switch may be open and
needing adjustment, the limit switches may be connected incorrectly on TB1, or jumpers A1–A3 and
B1–B3 may be in the wrong position. See figure 13.
4. Check to see if power is reaching the actuator. If
power is reaching the actuator, the handwheel will be
difficult to turn. If power is not reaching the actuator,
the handwheel will be easy to turn.
Basis Weight Actuator
Figure 17. Actuator/Valve Connection
Test Procedures
Checking the IC500 Card
Required equipment for these procedures are an extender card (see the parts list) and volt–ohm–millimeter or similar voltage–measuring device.
1. Remove the IC500 module (refer to the Replacing
Modules section).
Checking the SD13 Card
3. Check the dc voltage between 8c (PCOM) and 30a
(Ref.) at 2.7 A current limiting. (Be sure DIP switch 4
on the SD13 card is ‘‘on.’’ See the Settings section.)
1. Remove the SD13 module (refer to the Replacing
Modules section).
2. Install the extender card in place of the SD13 module. Plug the SD13 module into the extender card.
3. Install fuses. Use table 5 and the Driver Card section.
4. Be sure that terminal 7 on terminal block TB2 is
connected to ground (GND––yellow–green) on TB2.
5. Check the ac voltages on the SD13 card. There
should be approximately 8 Vac between 12a and 12c
and approximately 8 Vac between 14a and 14c.
6. Also check the following voltages:
2. Install the extender card in place of the IC500 module. Plug the IC500 module into the extender card.
4. Voltage between 8c and 30a should be 0.75 Vdc
with the motor not running and 1.50 Vdc with the motor
running.
5. Contact your Fisher Controls sales office or sales
representative if the measured voltages are not
approximately the values shown above.
6. Remove all power. Remove the extender card and
IC500 card. Re–install IC500 module.
Valve Maintenance
Voltage Between
Should Be
16a and 12a
18 Vac
16a and 14a
18 Vac
16a and 12c
26 Vac
16a and 14c
26 Vac
Note
Contact your Fisher Controls sales office or sales representative if the measured voltages are not approximately the
values shown in steps 5 and 6.
7. Remove all power. Remove the extender card and
SD13 card. Re–install the SD13 module and correct
fuses.
Refer to the appropriate valve body instruction manual
for information on valve maintenance. If it is necessary
to remove the actuator from the valve, refer to the Removing the Actuator instructions below.
Removing the Actuator
1. Remove alternating current power at the external
circuit breaker box. If necessary, disconnect conduit
connections and disconnect wiring from the actuator.
Then, proceed as follows.
2. Due to the need to determine the closed position of
the valve before re–connecting the actuator and valve,
remove the valve and attached actuator from the pipeline.
21
Basis Weight Actuator
WARNING
The valve ball or disk closes and opens
with a shearing, cutting motion. Avoid
personal injury from this motion by
keeping hands, tools, and other objects
away from the valve ball or disk.
3. Loosen the socket–head screws in the valve shaft
clamp (see figure 17). The valve shaft clamp is located
on the actuator where the valve shaft is connected to
the actuator.
4. Remove the cap screws that attach the valve body
to the actuator mounting yoke. If it is desired to remove the yoke from the actuator, remove the cap
screws and nuts that attach the mounting yoke to the
actuator.
Mounting the Actuator on the Valve
1. When maintenance is complete, attach the mounting yoke to the actuator if it was removed.
2. Refer to the valve body instruction manual for instructions on determining the fully closed position. Fully close the valve and keep it in that position until this
procedure is complete.
CAUTION
Incorrect valve shaft rotation can damage internal valve parts. To avoid such
damage, be certain that the actuator will
provide the correct rotation direction for
the valve you are using.
Required valve shaft rotation is not the same for all
valves. Design V150 valves require clockwise valve
shaft rotation to open the valve. Before mounting the
valve, check to see that the actuator will provide the
correct rotation to open and close the valve. If the rotation is not correct, change the rotation direction by
changing the switch settings and jumper locations on
the control cards. Refer to the Settings section.
Always use the standard mounting position shown in
figure 17 and check for proper rotation before installing
the actuator on the valve. Other mounting positions
might provide incorrect valve rotation.
3. Use the actuator handwheel to rotate the actuator
mechanism to the closed end of its travel (to the position it is to be in when the valve is fully closed).
4. While guiding the valve shaft clamp over the valve
shaft, place the actuator and mounting yoke on the
valve.
22
5. Check to be sure that the valve is still fully closed.
Then, tighten the socket head cap screws in the valve
shaft clamp. If the valve ball or disk has moved from
the fully closed position, remove the actuator from the
valve, fully close the valve and repeat steps 4 and 5.
6. Attach the mounting yoke to the valve with cap
screws.
Replacing Fuses
1. Remove alternating current power at the external
circuit breaker box.
2. Unlock and open the Stepmotor Interface.
3. Locate fuses. Fuses are in terminal block TB2 and
on the SD13 card.
4. Test the fuses and replace them if needed.
Replacing the Actuator Motor
1. Remove alternating current power at the external
circuit breaker box.
2. Remove the cover plate from the motor. The cable
was sealed to the motor with silicone rubber at the factory. Remove the seal. Note the wire–terminal connections so you can re–wire the new motor correctly. Disconnect and remove the wires from the motor.
3. Unscrew the four screws and nuts that attach the
motor to the actuator (figure 2). Remove the motor by
separating the two halves of the zero backlash coupler. Inspect the elastomer spider in the coupler; replace it if worn or damaged. Keep the coupler as you
may need to use it again during re-assembly.
4. Install the new motor. Make sure the coupling engages both the actuator and the motor output shaft.
Secure the motor with the four screws and nuts.
5. Connect the motor wires to the correct terminals as
you noted in step 2. Re–seal the cable to the motor or
provide another suitable cable connector.
Replacing Modules
1. Remove alternating current power at the external
circuit breaker box.
2. Unlock and open the cover of the Stepmotor Interface.
3. Unlock and open the Stepmotor Interface.
4. Loosen the four captive screws that secure the
module you wish to replace. Pull the module out of the
cabinet.
5. If you are replacing the IC500 or FT100 card, make
the appropriate switch and jumper settings on the replacement card. Refer to the Settings section.
Replacing the Transformer
1. If it is necessary to replace the transformer, remove
alternating current power at the external circuit breaker
box. Unlock and open the cabinet.
Basis Weight Actuator
2. Record the location of the wire connections on the
terminal block. Remove the transformer wires from the
terminal block.
3. Unscrew the mounting screw from the center of the
transformer and remove the transformer from the back
of the cabinet.
4. Be sure to remove insulation from the ends of the
transformer wires.
5. Attach the new transformer and connect the transformer wires to the terminal block (see figure 9). Make
sure the jumper between TB2-7 and TB2-Ground is
installed.
6. Close the cabinet, turn on power, and check operation of the system before returning it to service.
Field Installation of the Remote Station
Follow these steps to install a Remote Station to an
already exisitng IC2000 unit. See figure 18.
1. The IC2000 has no 24Vdc for external units, but a
power outlet is included. So, a Rectifier Bridge is included with the Remote Station.
2. Drill a 4.2 mm (0.165 inch) hole to the left of TB1.
Make a thread of 5mm and mount the Rectifier Bridge,
see figure 18.
3. Connect AC power input to the Rectifier from terminals 10 and 11 on TB2. Be sure to connect on the upper side of the terminal after the terminal fuse.
4. Install the Remote Station. Install a junction box
close to the Remote Station.
5. Install a multi-wire cable with a screen, having at
least 9 wires between the IC2000 and the junction box.
Connect the wires as shown in figure 18.
6. Connect wires 1 and 9 without terminals directly to
the Rectifier. Use the end connectors provided.
Parts List
A Fisher Controls serial number is assigned to each
basis weight control system. This serial number can be
found on a nameplate attached to the actuator mounting yoke. Refer to this serial number whenever corresponding with your Fisher Controls sales office or
sales representative about this equipment. When ordering replacement parts, also include the part number
from the Parts List section.
Description
IC2000 Control Cabinet
IC500 Module
FT100 module
SD13 Card
Limit Switch
Transformer RTR 17401
14 Pin female connector
14 Pin male connector
Terminal Block TB3
Terminal Block TB4
Remote Station
Manual Station Module
Extender Card
Motor
Size 20HT
Size 30HT & 40HT
Handwheel
Size 20HT
Size 30HT
Size 40HT
Housing Kit for Motor Coupling
Size 20HT
Size 30HT
Size 40HT
Valve Position Indicator Assembly
2 Limit Switch
4 Limit Switch
Elastomer Spider for Motor Coupling
Size 20HT
Size 30HT & 40HT
Part Number
12B0720X012
12B0723X012
12B0726X012
12B0721X022
11B9830X012
10B6819X032
11B9828X012
11B9829X012
17B5977X012
17B5977X022
12B0725X012
12B0724X012
12B9361X012
10B6807X032
10B6807X042
13B7129X032
13B7129X022
13B7129X012
13B7129X062
13B7129X052
13B7129X042
13B7130X012
13B7130X022
17B7755X012
17B7755X022
7. Install a multi-wire cable with a screen between the
computer and the junction box (see figure 18). If the
status information is fed to the computer, the cable
must have at least 6 wires. Otherwise, 3 are needed.
23
Basis Weight Actuator
INC
DEC
BRIDGE
RECTIFIER
DIRECTION
COMMON
DIRECTION
CONTROL
E0023 / IL
Figure 18. Control Connection Schematic with Remote Station
24
STATUS
SPEED
CONTROL
Basis Weight Actuator
TO + TERM.
OF BRIDGE
RECTIFIER
ON 24 VAC
SEL SLOW
PCOM
REM IND – 24V
SELECT
SLOW
DEC CMD FROM COMPUTER
DEC ( TO IC2000)
22a
INC ( TO IC2000)
PCOM
26a COMMON
28a MANUAL
30a COMPUTER
INC COMMAND FROM COMPUTER
24a
TO – TERM.
OF BRIDGE
RECTIFIER
ON 24 VAC
E0024 / IL
Figure 18. Control Connection Schematic with Remote Station Cont’d (Card 1 Schematic)
25
Basis Weight Actuator
Table 5. Control Cabinet Connection Table
FT100
MAN
IC500
SD13
Rack K58
Rack K36
Rack K28
Rack K3
DESIGNATION
TERMINAL
Edge Connector Pins
2ca
2ca
2ca
+24 VDC BUS
TB1/11
2ca
MOTOR PHASE 2A
TB1/2
4ca
MOTOR PHASE 2B
TB1/1
4a
8a
+15 VDC BUS
4ca
TRANSFORMER 24 VAC TO IC500
TB2/11
6ca
TRANSFORMER 24 VAC TO IC500 RET
TB2/10
6ca
MOTOR PHASE 1B
TB1/1
8ca
MOTOR PHASE 1A
TB1/1
POSITION SIGNAL TO MAN STN
FT100/TP1
+ 24 VDC FROM SD13 TO IC500
TB1/3
8ca
8a
10a
10ca
10ca
0-1V, 1-5V POSITION SIGNAL RET
10a
LIM SW CW (LS2)
TB1/12
12a
TRANSFORMER SEC 18 VAC
TB2/6
12c
TRANSFORMER SEC 26 VAC
TB2/5
LIM SW CCW (LS1)
TB1/13
12a
14a
1–5V POSITION SIGNAL (local)
14a
14a
TRANSFORMER SEC 18 VAC (1)
TB2/8
14c
TRANSFORMER SEC 26 VAC (1)
TB2/9
14a
8c
FAST INC MAN TO IC500
16,18ca
16a
16a
16a
18a
18a
20a
20a
FB POT WIPER
TB1/6
SLOW INC COMP TO IC500
TB1/18
FB POT CCW
TB1/5
SLOW DEC COMP TO IC500
TB1/19
20a
FAST CMD INPUT TO SD13
28a
22a
SLOW CMD INPUT TO SD13
22a
SLOW SPEED CMD TO MAN STN
TB1/14
24a
INC CMD INPUT TO MAN STN
TB1/15
24a
24a
RATE ADJ COMMON TO SD13
24c
24c
SLOW RATE ADJ TO SD13
26a
26a
FAST RATE ADJ TO SD13
26c
26c
DIR CMD INPUT TO SD13
DEC CMD INPUT TO MAN STN
28a
28a
30a
26
TB1/7
28c
26a
32ca
TB2/7
FB POT CW
FAST DEC MAN TO IC500
18a
20a
TRANSFORMER SEC 18, 26 VAC CT
32ca
4-20mA POSITION OUTPUT +
TB1/8
REM MODE INDICATOR
TB1/17
4-20mA POSITION OUTPUT –
TB1/9
30a
30a
STBY CURRENT SET SIGNAL TO SD13
30c
32c
STBY CURRENT SET RET TO SD13
32ca
TB1/16
POWER COMMON
TB1/10, FT100/TP0
Basis Weight Actuator
0.1 F
TP1
18K
82K
10K
CA3130
0.1 F
5.1K
CA3130
TIP29C
1000 F
200K
F
20K
4.7V
REF01
20K
20K
20K
3.3K
20K
R12
1K
1K
5.6V
TO MAN STN
INDICATOR
1K
JUMPER
200K
Rx1 (N.C.)
CCW
0.1K
Rx4
CW
JUMPER
A7805
0.1 F
7.33 F
A(CCW)
B(CW)
ACTION
JUMPER
BLOCK
E0025 / IL
Figure 19. Feedback Transmitter Schematic
27
Basis Weight Actuator
(8 X 0.5 mm2 )
(9.1 mm CABLE OD)
E0022 / IL
Figure 20. Feedback Potentiometer Connection Schematic
28
Basis Weight Actuator
FIELD WIRING SIDE
DRIVER CARD WIRING SIDE
FROM SD13
24VDC
SET
INC
SIGN
COMMON
DEC
DEC
CMD
D11
INC
DIRECTION
COMMAND
ASSERTED>
MOTOR CW
D12
DEC
CMD
D13
D15
INC
D14
E0026 / IL
Figure 21. IC500 Schematic
29
Basis Weight Actuator
E0018 / IL
Figure 22. Manual Station Schematic
30
Basis Weight Actuator
31
Basis Weight Actuator
Vee-Ball, Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
All other marks are the property of their respective owners.
EFisher Controls International, Inc. 1989, 2000; All Rights Reserved
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
For information, contact Fisher Controls:
Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
32
Printed in U.S.A.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement