Installation Instructions
MX4018
Hy2NC: Two Channel Wired Edge Sensor Converter
NOTICE: Use Hy2NC with WIRED gate edges manufactured for monitoring purposes. The
Hy2NC is not needed and WILL NOT WORK with wireless gate edges.
CAUTION
Wiring of automated gate operators must conform to NFPA and NEC standards a
nd
comply with all local codes. When the installation is compliant andcomplete, turn on
AC power at the source and at the control box.
CH1: Edge 10k (or 8.2k)
Color-coding on wires is a
non-issue.
Wired edges are not
polarity sensitive.
Red wires: Connect to
Power & SENSOR COM
P/N MX4018
Power
SENSOR COM
Mounting
holes
CH1
BL = CH1
YL = CH2
FLASHING GREEN
Actively Monitoring
CH2
•
CH2: Edge 10k (or 8.2k)
Channel 1 (Blue)
Hy2NC
•
•
•
•
EDGE 2
NC outputs
Channel 2 (Yellow)
Hy2NC, MX4018
Female quick disconnects (5x)
Installation Instructions
Tools required
•
•
•
CH1
SOLID RED = EDGE TRIP
FLASHING = FAULT CH2
Green
Flashing LED
Heartbeat
•
•
•
Wire stripper / cutter
Phillips head screwdriver
Drill & bits for mounting wired
gate edge sensors and adapter
Additional Items:
EDGE 1
Class 2 Device 10k & 8.2k Ohm
30V, 20 mA Max., NC Output
Parts List
Color-coding on wires is a
non-issue. Wired edges are
not polarity sensitive.
Self tapping screws (2x)
Conduit
Electrical Wire: 16 to 20 AWG,
Electrical junction box as
required by code
Wired Gate Edge with 10k
ohm (or 8.2k) resistor (UL 325
approved)
Multi-meter capable of reading
10KΩ
See Table 1. Troubleshooting Tips
on the next page. Red LEDs
Installation
To install the Hy2NC, 2 channel sensor adapter, take the following steps:
1. Install the wired gate edge per the manufacturer’s instructions.
2. Feed wires through low voltage conduit to the gate operator.
3. Access the gate operator’s Control Box.
4. Turn OFF all power to the Control Box.
5. Mount the Hy2NC in the Control Box using 2 self-tapping screws.
6. Crimp female quick connectors to incoming edge wires and connect to the appropriate Hy2NC channel
spade inputs.
7. Connect the blue and yellow wires to SENSOR inputs on the controller.
8. Connect one red wire to +24V and the other red wire to Common (SENSOR COM on HySecurity gate
operators. For HySecurity gate operator wiring diagrams and programming, see page 4.)
Test Gate Sensor and Gate Operation
1. Turn power ON. Access the User Menu and the menu item “PE” Photo Eye Align.
2. To temporarily supply power to the sensors, change PE to 1. See page 4, Table 3 for Menu mode tips.
3. Verify that the wired edge sensors are operational and the gate is working properly by applying pressure to
each WIRED edge. The red LED on the Hy2NC adapter should light and remain static, indicating an edge trip.
4. When you are assured that the gate operator and gate edges are functioning properly, cycle the gate open/
close (this resets Photo Eye Align mode, PE to 0), close the control box, and carefully replace the operator’s
cover. Secure the cover to the chassis.
www.hysecurity.com
© 2017
Page 1
P/N MX4018
D0774 Rev A
Troubleshooting
See Table 1 for tips and LED status explanations. For Troubleshooting display codes, refer to the product manual.
NOTE: For monitoring and powering purposes, all external entrapment protection sensors, connected to Smart Touch or Smart DC controllers,
must be wired to the SENSOR COM terminal. The Normally Closed sensors require power to operate. After installing the sensor wiring,
temporarily supply power to the sensors, by turning ON the Photo Eye Align mode (PE in the User Menu). For more information, refer to the
product manual or view HySecurity Product Manuals online.
CAUTION
Connect all contact and non-contact sensors to the same power source. Example, Do NOT connect photo eyes to +24VDC and
gate edges to +12VDC. (Incompatible electricity flow.) A FAULT 2 will appear.
Table 1. Troubleshooting Tips
LED
Status
Diagnostics
Resolution
1. Gate operator’s motor is not running. Check that power is ON and cycle test open
and close.
OFF
No power to the adapter.
GREEN
2. Retrace the red wires, power and COM (SENSOR COM on HySecurity operators),
from the adapter to the operator. Reseat wires, if necessary.
3. Use a multimeter to verify red wires have 12 VDC or 24 VDC. To provide temporary
power to the sensors, turn Photo Eye Align mode ON (PE in User Menu).
4. Check the blue and yellow wire connections between the sensing edge and the gate
operator. Re-install, if necessary.
ON (Static)
Powered /
Internal adapter fault
Replace adapter.
FLASHING
Powered / Normal operation
Active status. Monitoring. Normal Operation.
OFF
Normal operation
Sensing edge working properly. No resolution needed.
ON (Static)
Edge is tripped / Edge hit
occurred / Edge shorted
1. Resolve trip activation issue.
2. Check connections.
3. Use a multimeter to determine if sending edge is shorted. Replace it, if necessary.
4. Reset the gate operator.
RED
Faulty edge /
Open Edge
SLOW
Channel not in use (No wiring
connected)
FLASHING
Faulty edge /
Open Edge
FAST
Channel not in use (No wiring
connected)
FLASHING
1. Two resistive edges installed in parallel. (Only 1 edge can have 10K resistor if wired
in parallel.)
2. More than one edge is being recognized by the same sensor terminal on the
controller. Verify only one edge is connected to one sensor input terminal.
3. Damaged edge. Check with multimeter and replace it, if necessary.
1. Two resistive edges installed in series. (Only 1 edge can have 10K resistor if wired in
series.)
2. More than one edge is being recognized by the same sensor terminal on the
controller. Verify only one edge is connected to one sensor input terminal.
3. Damaged safety edge. Check with multimeter and replace it, if necessary.
The NC contact is not being recognized or triggered when the gate operator receives
an open command.
FAULT 2
Gate does not move
when Open/Close
command sent
UL 325 -2016 monitoring
requirements are not being met
1. RED flashing LED indicator slow or fast? See above.
1. Verify COM red wire connected to SENSOR COM.
2. Check SENSOR 1, 2 and 3 have been configured properly through the Installer
Menu.
3. See wiring diagrams for HySecurity operators on page 3 and page 4.
Automatic Slide Gate Scenario
NOTE: External entrapment protection sensors must be installed
wherever potential for entrapment exists. Per UL 325 - 2016 Standard of
Safety, the external entrapment sensors are monitored and must be
functioning properly before the gate operator enables momentary
control activation such as, push button open or close commands. For
more information, view online HySecurity Gate Safety.
3
Trailing End
Potential Zones for
Entrapment Protection
1. Draw-in zones
1
Draw-in Zones
Wired Edge sensors protect
areas of entrapment along posts
or walls
2
Leading End
2. Leading end
3. Trailing end
www.hysecurity.com
© 2017
Page 2
P/N MX4018
D0774 Rev A
HySecurity Gate Operators
Smart DC Control Box
Configuring Software for Monitoring with Hy2NC
NOTE: When installing a 10k WIRED edge sensor, the wired edge must be connected to an
interface adapter module (such as the Hy2NC) that produces an NC output.
Power switches
Turn off both
the DC and AC
switches.
CAUTION
Turn all power OFF at the Control Box. Note that all external entrapment protection
sensors must be wired to terminal SENSOR COM for power and monitoring purposes.
Smart Touch Control Box
CAUTION
SlideSmart DC: After wiring sensor
connections, turn gate operator ON. The gate
will move while the gate operator searches
for target (target magnet on the chain).
Power
toggle
switch
Smart Touch Controller
Access the Installer Menu
30V, 20 mA Max., NC Output
© 2017
10
INSIDE OBSTRUCTION
VEHICLE DETECTOR
11
OUTSIDE OBSTRUCTION
VEHICLE DETECTOR
12
SHADOW/RESET
VEHICLE DETECTOR
14
CH2
BL = CH1
8k to 10k
YL = CH2
CH2
FLASHING GREEN
Actively Monitoring EDGE 2
Page 3
S2 3 (EDGE CLOS)
SENSOR #2 TYPE
SENSOR
COM
15
16
COM
NO
DO NOT USE
17
SENSOR 2
18
DO NOT USE
19
SENSOR 3
20
DO NOT USE
21
CHARGER
AC LOSS
22
LOCK INTERLOCK
23
EMERG CLOSE
24
FIRE DEPT OPEN
STATUS
CH1
CH 2 Wires to
Edge Sensor
www.hysecurity.com
DISABLE EXIT DETECTOR
DISABLE CLOSE TIMER
9
LED
LIMIT
HySecurity
MX000585
VERSION
S/N
Smart Touch Controller
RADIO OPTIONS
WIEGAND
SOLID RED = EDGE TRIP
FLASHING = BAD EDGE
S2 0
SENSOR #2 TYPE
VEHICLE DETECTOR
Class 2 Device
FREE EXIT DETECTOR
SHADOW
RESET
8k to 10k
CH1
EDGE 1
8
VEHICLE DETECTOR
Power
SENSOR COM
INTERLOCK OPEN
TIME CLOCK OPEN
OUTSIDE
OBSTR
P/N MX4018
7
VEHICLE DETECTOR
The sensor does not become active
until a command is received by the
Controller and the motor runs. *
Female quick
disconnects provided
OPEN PARTIAL
SENSOR 1
Red wire SENSOR COM
Yellow wire
SENSOR connection
for CH 2
OPEN/CLOSE
6
INSIDE
OBSTR
Blue wire
SENSOR Connection
for CH 1
5
S1 6 (EDGE BOTH)
SENSOR #1 TYPE
VEHICLE DETECTOR
NOTE: Red wires
are interchangeable.
They are not polarity
sensitive.
REMOTE OPEN AND
RADIO CONTROL
FREE
EXIT
Red wire
Power +24V
CLOSE BUTTON
4
RS232
*NOTE: To temporarily power sensors and
check that the gate operator is monitoring the
sensors properly, turn on Photo Eye Align
mode. Access “Menu Mode” by pressing the
Menu button. See Table 3 on page 4.
po
we
r
OPEN BUTTON
DISPLAY
4. Select the appropriate sensor
setting (# 3 Edge Close, # 5 Edge
Open, or # 6 Edge Both). Example
shown in illustrations on pages 3
and page 4.
ory
2
3
USER 3
3. Press Next and scroll to the
SENSOR # TYPE (S1, S2, or S3) that
is associated with the gate edge
wiring (blue and/or yellow Hy2NC
wires).
ces
s
DC
STOP BUTTON
STOP/BUZZER
2. Simultaneously, press and hold
Reset and Open.
4V
+2
S1 0 RS485
SENSOR #1 TYPE
POWER
DRIVE
1
USER 2
1. With power ON, press the Menu
key twice to access the Installer
Menu.
p
Su
Po
24
VA
CA
c
Installer Menu Displays
USER 1
To configure the Hy2NC and connect
the WIRED edge sensor to a HySecurity
Smart Touch Controller or Smart DC
Controller, take the following steps:
r
we
Bo
MOTOR
NOTE: The SELECT, NEXT and PREVIOUS
buttons let you navigate within the Installer Menu.
If you are unfamiliar with reconfiguring menu
items, review the tables on page 4.
ply
Female spade
quick disconnect
provided
ard
DUAL GATE
RPM
COM
A
B
COM
OPEN
+24V
+24V
S1
COM
CH 1 Wires to Edge Sensor
P/N MX4018
D0774 Rev A
Smart DC Controller
Installer Menu Displays
S1 6 (EDGE BOTH)
SENSOR #1 TYPE
NOTE: If using a Build Year 1
HySecurity gate operator, the
settings will be different. You won’t
need the Hy2NC adapter. The gate
edge can be hooked up to the
SENSOR or EDGE terminal as a
NO output. For more information,
refer to your gate operator product
manual.
OPEN
CLOSE
PREV
NEXT
OPEN
MENU
STOP
S2 3 (EDGE CLOS)
SENSOR
#2 TYPE
SELECT
CLOSE
STOP
MENU
24VDC
COM
RESET
24VDC
COM
COM
COMMON
TERMINALS
RESET
COM
COM
12VDC
COM
12VDC
COM
NOTE: In 2012, location of
pins changed. Older boards
show pins swapped.
COM
PREV
NEXT
STOP
SELECT
OPEN
RADIO
Yellow wire
SENSOR
connection
for CH 2
Red wire SENSOR COM
The sensors do not become active
until the motor runs.
OPEN
CLOSE
OPEN
PARTIAL
EYE
SENSOR 2
OPEN
EYE
SENSOR 3
CLOSE
EXIT
EXIT
LOOP
LOOP
BLOCK
BLOCK
EXIT
EXIT
IN
IN OBS
OBS
LOOP
LOOP
OUT
OBS
OUT OBS
LOOP
LOOP
CENTER
CENTER
LOOP
LOOP
EDGE
SENSOR 1
EYE
SENSOR
COM
COM
USER RELAY 1nical
Electro-mecha
P/N MX4018
Power
SENSOR COM
Blue wire
SENSOR
Connection
for CH 1
USER2
+24V
EMERG
OPEN
COM
A
B
DUAL GATE
SHOW
LEDs
24V
COM OPEN +
DC
EDGE COM NO
8k to 10k
CH1
EDGE 1
Class 2 Device
30V, 20 mA Max., NC Output
SOLID RED = EDGE TRIP
FLASHING = BAD EDGE
CH1
Red wire
Power +24V
CH2
BL = CH1
8k to 10k
YL = CH2
CH2
FLASHING GREEN
Actively Monitoring EDGE 2
NOTE: Red wires are interchangeable.
They are not polarity sensitive.
Channel wires to Edge Sensor
Table 2: Installer Menu Settings for Edge SENSOR Inputs
Installer Menu Edge Sensor Settings 1, 2, or 3
UL 325 HySecurity Gate Operator
Build Year 2016
(BY set)
SlideDriver (fixed speed)
2
SlideDriver VFD
2
SlideSmart DC 15
2
SlideSmart DC 10
2
SwingRiser
2
SwingSmart DC
2
HydraSwing
2
HydraLift
2
#1
NOT USED
#3
EDGE CLOSE
#5
EDGE OPEN
#6
EDGE BOTH DIRECTIONS
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Table 3: Smart Touch and Smart DC Controller: Menu Mode Navigation Buttons
To access
Menu mode
To change data
appearing in the display
To navigate through
the Selections
To choose what appears
on the display
To navigate between
menu items
Press the Menu
button twice.
Press Select.
Two left characters blink.
Press Next or Previous.
Continue pressing Next to view all
selections.
Press Select.
Blinking characters
become static.
Press Next or Previous.
Advance - press Next
Previous - press Previous
Technical Support
For technical support, call your installer or authorized HySecurity distributor. Obtain the serial number of your operator
before calling. For the name of a distributor near you, contact HySecurity at 800-321-9947. For additional information,
refer to the HySecurity website.
www.hysecurity.com
© 2017
Page 4
P/N MX4018
D0774 Rev A
Was this manual useful for you? yes no
Thank you for your participation!