Installation Instructions MX4018 Hy2NC: Two Channel Wired Edge Sensor Converter NOTICE: Use Hy2NC with WIRED gate edges manufactured for monitoring purposes. The Hy2NC is not needed and WILL NOT WORK with wireless gate edges. CAUTION Wiring of automated gate operators must conform to NFPA and NEC standards a nd comply with all local codes. When the installation is compliant andcomplete, turn on AC power at the source and at the control box. CH1: Edge 10k (or 8.2k) Color-coding on wires is a non-issue. Wired edges are not polarity sensitive. Red wires: Connect to Power & SENSOR COM P/N MX4018 Power SENSOR COM Mounting holes CH1 BL = CH1 YL = CH2 FLASHING GREEN Actively Monitoring CH2 • CH2: Edge 10k (or 8.2k) Channel 1 (Blue) Hy2NC • • • • EDGE 2 NC outputs Channel 2 (Yellow) Hy2NC, MX4018 Female quick disconnects (5x) Installation Instructions Tools required • • • CH1 SOLID RED = EDGE TRIP FLASHING = FAULT CH2 Green Flashing LED Heartbeat • • • Wire stripper / cutter Phillips head screwdriver Drill & bits for mounting wired gate edge sensors and adapter Additional Items: EDGE 1 Class 2 Device 10k & 8.2k Ohm 30V, 20 mA Max., NC Output Parts List Color-coding on wires is a non-issue. Wired edges are not polarity sensitive. Self tapping screws (2x) Conduit Electrical Wire: 16 to 20 AWG, Electrical junction box as required by code Wired Gate Edge with 10k ohm (or 8.2k) resistor (UL 325 approved) Multi-meter capable of reading 10KΩ See Table 1. Troubleshooting Tips on the next page. Red LEDs Installation To install the Hy2NC, 2 channel sensor adapter, take the following steps: 1. Install the wired gate edge per the manufacturer’s instructions. 2. Feed wires through low voltage conduit to the gate operator. 3. Access the gate operator’s Control Box. 4. Turn OFF all power to the Control Box. 5. Mount the Hy2NC in the Control Box using 2 self-tapping screws. 6. Crimp female quick connectors to incoming edge wires and connect to the appropriate Hy2NC channel spade inputs. 7. Connect the blue and yellow wires to SENSOR inputs on the controller. 8. Connect one red wire to +24V and the other red wire to Common (SENSOR COM on HySecurity gate operators. For HySecurity gate operator wiring diagrams and programming, see page 4.) Test Gate Sensor and Gate Operation 1. Turn power ON. Access the User Menu and the menu item “PE” Photo Eye Align. 2. To temporarily supply power to the sensors, change PE to 1. See page 4, Table 3 for Menu mode tips. 3. Verify that the wired edge sensors are operational and the gate is working properly by applying pressure to each WIRED edge. The red LED on the Hy2NC adapter should light and remain static, indicating an edge trip. 4. When you are assured that the gate operator and gate edges are functioning properly, cycle the gate open/ close (this resets Photo Eye Align mode, PE to 0), close the control box, and carefully replace the operator’s cover. Secure the cover to the chassis. www.hysecurity.com © 2017 Page 1 P/N MX4018 D0774 Rev A Troubleshooting See Table 1 for tips and LED status explanations. For Troubleshooting display codes, refer to the product manual. NOTE: For monitoring and powering purposes, all external entrapment protection sensors, connected to Smart Touch or Smart DC controllers, must be wired to the SENSOR COM terminal. The Normally Closed sensors require power to operate. After installing the sensor wiring, temporarily supply power to the sensors, by turning ON the Photo Eye Align mode (PE in the User Menu). For more information, refer to the product manual or view HySecurity Product Manuals online. CAUTION Connect all contact and non-contact sensors to the same power source. Example, Do NOT connect photo eyes to +24VDC and gate edges to +12VDC. (Incompatible electricity flow.) A FAULT 2 will appear. Table 1. Troubleshooting Tips LED Status Diagnostics Resolution 1. Gate operator’s motor is not running. Check that power is ON and cycle test open and close. OFF No power to the adapter. GREEN 2. Retrace the red wires, power and COM (SENSOR COM on HySecurity operators), from the adapter to the operator. Reseat wires, if necessary. 3. Use a multimeter to verify red wires have 12 VDC or 24 VDC. To provide temporary power to the sensors, turn Photo Eye Align mode ON (PE in User Menu). 4. Check the blue and yellow wire connections between the sensing edge and the gate operator. Re-install, if necessary. ON (Static) Powered / Internal adapter fault Replace adapter. FLASHING Powered / Normal operation Active status. Monitoring. Normal Operation. OFF Normal operation Sensing edge working properly. No resolution needed. ON (Static) Edge is tripped / Edge hit occurred / Edge shorted 1. Resolve trip activation issue. 2. Check connections. 3. Use a multimeter to determine if sending edge is shorted. Replace it, if necessary. 4. Reset the gate operator. RED Faulty edge / Open Edge SLOW Channel not in use (No wiring connected) FLASHING Faulty edge / Open Edge FAST Channel not in use (No wiring connected) FLASHING 1. Two resistive edges installed in parallel. (Only 1 edge can have 10K resistor if wired in parallel.) 2. More than one edge is being recognized by the same sensor terminal on the controller. Verify only one edge is connected to one sensor input terminal. 3. Damaged edge. Check with multimeter and replace it, if necessary. 1. Two resistive edges installed in series. (Only 1 edge can have 10K resistor if wired in series.) 2. More than one edge is being recognized by the same sensor terminal on the controller. Verify only one edge is connected to one sensor input terminal. 3. Damaged safety edge. Check with multimeter and replace it, if necessary. The NC contact is not being recognized or triggered when the gate operator receives an open command. FAULT 2 Gate does not move when Open/Close command sent UL 325 -2016 monitoring requirements are not being met 1. RED flashing LED indicator slow or fast? See above. 1. Verify COM red wire connected to SENSOR COM. 2. Check SENSOR 1, 2 and 3 have been configured properly through the Installer Menu. 3. See wiring diagrams for HySecurity operators on page 3 and page 4. Automatic Slide Gate Scenario NOTE: External entrapment protection sensors must be installed wherever potential for entrapment exists. Per UL 325 - 2016 Standard of Safety, the external entrapment sensors are monitored and must be functioning properly before the gate operator enables momentary control activation such as, push button open or close commands. For more information, view online HySecurity Gate Safety. 3 Trailing End Potential Zones for Entrapment Protection 1. Draw-in zones 1 Draw-in Zones Wired Edge sensors protect areas of entrapment along posts or walls 2 Leading End 2. Leading end 3. Trailing end www.hysecurity.com © 2017 Page 2 P/N MX4018 D0774 Rev A HySecurity Gate Operators Smart DC Control Box Configuring Software for Monitoring with Hy2NC NOTE: When installing a 10k WIRED edge sensor, the wired edge must be connected to an interface adapter module (such as the Hy2NC) that produces an NC output. Power switches Turn off both the DC and AC switches. CAUTION Turn all power OFF at the Control Box. Note that all external entrapment protection sensors must be wired to terminal SENSOR COM for power and monitoring purposes. Smart Touch Control Box CAUTION SlideSmart DC: After wiring sensor connections, turn gate operator ON. The gate will move while the gate operator searches for target (target magnet on the chain). Power toggle switch Smart Touch Controller Access the Installer Menu 30V, 20 mA Max., NC Output © 2017 10 INSIDE OBSTRUCTION VEHICLE DETECTOR 11 OUTSIDE OBSTRUCTION VEHICLE DETECTOR 12 SHADOW/RESET VEHICLE DETECTOR 14 CH2 BL = CH1 8k to 10k YL = CH2 CH2 FLASHING GREEN Actively Monitoring EDGE 2 Page 3 S2 3 (EDGE CLOS) SENSOR #2 TYPE SENSOR COM 15 16 COM NO DO NOT USE 17 SENSOR 2 18 DO NOT USE 19 SENSOR 3 20 DO NOT USE 21 CHARGER AC LOSS 22 LOCK INTERLOCK 23 EMERG CLOSE 24 FIRE DEPT OPEN STATUS CH1 CH 2 Wires to Edge Sensor www.hysecurity.com DISABLE EXIT DETECTOR DISABLE CLOSE TIMER 9 LED LIMIT HySecurity MX000585 VERSION S/N Smart Touch Controller RADIO OPTIONS WIEGAND SOLID RED = EDGE TRIP FLASHING = BAD EDGE S2 0 SENSOR #2 TYPE VEHICLE DETECTOR Class 2 Device FREE EXIT DETECTOR SHADOW RESET 8k to 10k CH1 EDGE 1 8 VEHICLE DETECTOR Power SENSOR COM INTERLOCK OPEN TIME CLOCK OPEN OUTSIDE OBSTR P/N MX4018 7 VEHICLE DETECTOR The sensor does not become active until a command is received by the Controller and the motor runs. * Female quick disconnects provided OPEN PARTIAL SENSOR 1 Red wire SENSOR COM Yellow wire SENSOR connection for CH 2 OPEN/CLOSE 6 INSIDE OBSTR Blue wire SENSOR Connection for CH 1 5 S1 6 (EDGE BOTH) SENSOR #1 TYPE VEHICLE DETECTOR NOTE: Red wires are interchangeable. They are not polarity sensitive. REMOTE OPEN AND RADIO CONTROL FREE EXIT Red wire Power +24V CLOSE BUTTON 4 RS232 *NOTE: To temporarily power sensors and check that the gate operator is monitoring the sensors properly, turn on Photo Eye Align mode. Access “Menu Mode” by pressing the Menu button. See Table 3 on page 4. po we r OPEN BUTTON DISPLAY 4. Select the appropriate sensor setting (# 3 Edge Close, # 5 Edge Open, or # 6 Edge Both). Example shown in illustrations on pages 3 and page 4. ory 2 3 USER 3 3. Press Next and scroll to the SENSOR # TYPE (S1, S2, or S3) that is associated with the gate edge wiring (blue and/or yellow Hy2NC wires). ces s DC STOP BUTTON STOP/BUZZER 2. Simultaneously, press and hold Reset and Open. 4V +2 S1 0 RS485 SENSOR #1 TYPE POWER DRIVE 1 USER 2 1. With power ON, press the Menu key twice to access the Installer Menu. p Su Po 24 VA CA c Installer Menu Displays USER 1 To configure the Hy2NC and connect the WIRED edge sensor to a HySecurity Smart Touch Controller or Smart DC Controller, take the following steps: r we Bo MOTOR NOTE: The SELECT, NEXT and PREVIOUS buttons let you navigate within the Installer Menu. If you are unfamiliar with reconfiguring menu items, review the tables on page 4. ply Female spade quick disconnect provided ard DUAL GATE RPM COM A B COM OPEN +24V +24V S1 COM CH 1 Wires to Edge Sensor P/N MX4018 D0774 Rev A Smart DC Controller Installer Menu Displays S1 6 (EDGE BOTH) SENSOR #1 TYPE NOTE: If using a Build Year 1 HySecurity gate operator, the settings will be different. You won’t need the Hy2NC adapter. The gate edge can be hooked up to the SENSOR or EDGE terminal as a NO output. For more information, refer to your gate operator product manual. OPEN CLOSE PREV NEXT OPEN MENU STOP S2 3 (EDGE CLOS) SENSOR #2 TYPE SELECT CLOSE STOP MENU 24VDC COM RESET 24VDC COM COM COMMON TERMINALS RESET COM COM 12VDC COM 12VDC COM NOTE: In 2012, location of pins changed. Older boards show pins swapped. COM PREV NEXT STOP SELECT OPEN RADIO Yellow wire SENSOR connection for CH 2 Red wire SENSOR COM The sensors do not become active until the motor runs. OPEN CLOSE OPEN PARTIAL EYE SENSOR 2 OPEN EYE SENSOR 3 CLOSE EXIT EXIT LOOP LOOP BLOCK BLOCK EXIT EXIT IN IN OBS OBS LOOP LOOP OUT OBS OUT OBS LOOP LOOP CENTER CENTER LOOP LOOP EDGE SENSOR 1 EYE SENSOR COM COM USER RELAY 1nical Electro-mecha P/N MX4018 Power SENSOR COM Blue wire SENSOR Connection for CH 1 USER2 +24V EMERG OPEN COM A B DUAL GATE SHOW LEDs 24V COM OPEN + DC EDGE COM NO 8k to 10k CH1 EDGE 1 Class 2 Device 30V, 20 mA Max., NC Output SOLID RED = EDGE TRIP FLASHING = BAD EDGE CH1 Red wire Power +24V CH2 BL = CH1 8k to 10k YL = CH2 CH2 FLASHING GREEN Actively Monitoring EDGE 2 NOTE: Red wires are interchangeable. They are not polarity sensitive. Channel wires to Edge Sensor Table 2: Installer Menu Settings for Edge SENSOR Inputs Installer Menu Edge Sensor Settings 1, 2, or 3 UL 325 HySecurity Gate Operator Build Year 2016 (BY set) SlideDriver (fixed speed) 2 SlideDriver VFD 2 SlideSmart DC 15 2 SlideSmart DC 10 2 SwingRiser 2 SwingSmart DC 2 HydraSwing 2 HydraLift 2 #1 NOT USED #3 EDGE CLOSE #5 EDGE OPEN #6 EDGE BOTH DIRECTIONS ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Table 3: Smart Touch and Smart DC Controller: Menu Mode Navigation Buttons To access Menu mode To change data appearing in the display To navigate through the Selections To choose what appears on the display To navigate between menu items Press the Menu button twice. Press Select. Two left characters blink. Press Next or Previous. Continue pressing Next to view all selections. Press Select. Blinking characters become static. Press Next or Previous. Advance - press Next Previous - press Previous Technical Support For technical support, call your installer or authorized HySecurity distributor. Obtain the serial number of your operator before calling. For the name of a distributor near you, contact HySecurity at 800-321-9947. For additional information, refer to the HySecurity website. www.hysecurity.com © 2017 Page 4 P/N MX4018 D0774 Rev A
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement