Energy Tech Laboratories POOL & SPA 6310 Installation & Operating Instructions
Add to my manuals
24 Pages
advertisement
INSTALLATION & OPERATING
INSTRUCTIONS
Heat Pump
Pool & Spa
Heater
Model Series
5310, 6310 & 8320
R
C
LISTED
US
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
NOTE: The instructions in this manual are for the use of qualified individuals specially trained and experienced in the installation and maintenance of this type of equipment and related system components. Installation and service personnel are required by some states to be licensed. Persons not qualified shall not attempt to install, service, or maintain this equipment.
This manual should be maintained in legible condition and kept adjacent to the heat pump pool heater or in a safe place for future use.
Catalog No. 6000.551A Effective: 04-10-09 Replaces: 04-02-09 P/N 241363 Rev. 2
2
Water Chemistry
(Corrosive water voids all warranties)
For your health and the protection of your pool equipment, it is essential that your water be chemically balanced. The following levels must be used as a guide for balanced water.
Recommended Level(s) Fiberglass Pools Fiberglass Spas Other Pool & Spa Types
Water Temp. (Deg. F) pH
Total Alkalinity (PPM)
Calcium Hardness (PPM)
Salt (PPM)
Free Chlorine (PPM)*
Total Dissolved Solids (PPM)
68 to 88
7.3 to 7.4
120 to 150
200 to 300
6000 MAXIMUM
2 to 3
3000 MAXIMUM
89 to 104
7.3 to 7.4
120 to 150
150 to 200
6000 MAXIMUM
2 to 3
3000 MAXIMUM
68 to 104
7.6 to 7.8
80 to 120
200 to 400
6000 MAXIMUM
2 to 3
3000 MAXIMUM
*Free Chlorine MUST NOT EXCEED 5 PPM!
• Occasional chemical shock dosing of the pool or spa water should not damage the heater providing the water is balanced.
• Automatic chemical dosing devices and salt chlorinators are usually more efficient in heated water.
Unless controlled, they can lead to excessive chlorine level which can damage your heater.
• Further advice should be obtained from your pool or spa builder, accredited pool shop, or chemical supplier for the correct levels for your water.
3
C
ONTENTS
Water Chemistry
Warnings
Pay Attention to These Terms
Introduction
Installation Considerations
Electrical Connections
Water Connections
Pressure Drop
Controls & Indicator Lamps
(Analog Models)
System Start-Up
Controls (Digital Models)
Digital Controls Operating
Instructions
To Select Pool or Spa Mode
To Increase the Desired Water
Temperature (Pool or Spa Mode)
To Lower Desired Water Temperature
(Pool or Spa Mode)
To Select Temperature in °C or °F
System Start-Up
Seasonal Start-Up or
Annual Check
Summer Shutdown
Freeze Protection
System Drain-Down
Continuous Pump Operation
10
11
11
3
5
5
6
6
7
9
9
12
12
12
12
12
12
12
13
13
13
13
Maintenance
Air Coil Cleaning
Cabinet Care (optional)
Unplug Condensation Drain Holes
Troubleshooting
Service Call Verification
Power Supply
Water Flow
Time Clock Adjustment
Plumbing Diagrams
Wiring Diagram — 208V/230V
15
15
16
Single-Phase — Analog Models 18
Wiring Diagram — 208V/230V
Single-Phase — Digital Models 19
Wiring Diagram — 208V/230V
3-Phase — Analog Models
Wiring Diagram — 208V/230V
20
21 3-Phase — Digital Models
Installing a Remote Control
Device on Analog Heaters
Wiring
Heater Settings
Installing a Remote Control
Device on Digital Heaters
22
22
22
Wiring
Heater Settings
22
22
22
13
13
13
13
14
15
15
4
Warnings
—
Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:
Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
This manual, as well as the pool/spa heat pump pool heater itself, contains ANSI-approved product safety signs and labels. Please read these signs and labels, as they convey important safety information about hazards that may be potentially present in and around the heat pump pool heater.
CAUTION: Elevated water temperature can be hazardous. The U.S. Consumer Product Safety
Commission has these guidelines:
1. Spa water temperatures should never exceed
104°F (40°C). A temperature of 100°F (38°C) is considered safe for a healthy adult. Special caution is suggested for young children.
2. Drinking of alcoholic beverages before or during spa or hot tub use can cause drowsiness which could lead to unconsciousness and subsequently result in drowning.
3. Pregnant Women Beware! Soaking in water over
102°F (39°C) can cause fetal damage during the first three months of pregnancy resulting in the birth of a brain-damaged or deformed child.
Pregnant women should stick to the 100°F (38°C) maximum rule.
4. Before entering the spa or hot tub, users should check the water temperature with an accurate thermometer; spa or hot tub thermostats may err in regulating water temperatures by as much as
4°F (2.2°C).
5. Persons with a medical history of heart disease, circulatory problems, diabetes, or blood pressure problems should obtain a physician's advice before using pools or hot tubs.
6. Persons taking medications which induce drowsiness, such as tranquilizers, antihistamines, or anticoagulants, should not use spas or hot tubs.
CAUTION: Improper chemical content in a swimming pool or spa can damage the heat pump pool heater. DO NOT add pool chemicals to the skimmer.
This will damage the heat pump pool heater and could void the heat pump pool heater warranty.
ALWAYS follow the product manufacturer’s directions when adding any chemicals to your pool.
5
Introduction Installation Considerations
WARNING: This pool/spa heat pump pool heater is an electromechanical machine that incorporates a pressurized refrigerant gas in a sealed system.
ONLY trained and qualified service personnel are authorized to install or service this equipment.
Without proper training and knowledge of such equipment, any attempt to install or service the unit could result in serious injury or even death.
This manual contains important information on the use, maintenance and troubleshooting of your new heat pump pool heater. This unit must be properly installed, maintained and operated for optimal performance.
WARNING: Do not install the unit within 3 ft of fossil fuel burning heaters. Air intake along the sides of this heat pump pool heater could disturb the combustion process of the unit, and could cause damage or personal injury.
• Mount the unit on a level, sturdy base, preferably a concrete slab or blocks. The size of the base should be at least 3 ft by 3 ft.
• You must install the 4 black rubber sound isolation pads (each 2 inches square) that ship with the unit. The pads are stored securely with the unions and gaskets behind the control panel cover. Install pads under the 4 corners of the unit to reduce vibration and sound transmission to the base.
This heat pump pool heater is an extremely efficient, economical machine designed specifically for swimming pool heating. It is similar in design and operation to a typical residential air conditioning system. The unit employs a hermetic motor/compressor operating in a refrigeration cycle to extract heat from ambient air and deliver it to the circulating pool water.
CAUTION: The unit’s supporting base must be high enough to keep it completely free of standing water at all times.
Situate the heat pump pool heater carefully to minimize installation costs while providing maximum efficiency of operation, and to allow adequate service access, as follows:
As with all heat pump pool heaters, compared to other types of heaters such as gas or oil-fired, this heat pump pool heater has lower heating capacity on a
BTUH/hr basis. As a result, it will be required to operate longer to accomplish the desired results. It may, at certain times, operate as much as 24 hours per day.
However, this should not be of concern to the owner, because the unit is designed to operate continuously.
Even though it may operate continuously for many hours, it will still heat the pool with greater economy than other types of fossil fuel heaters.
• For unrestricted air intake and service access, position each side of the unit at least 1 ft (30 cm) from walls, pipes and other obstructions.
WARNING: This unit is designed for outdoor installation; DO NOT install it in an enclosed area such as a shed or garage.
Place a cover or blanket over the pool at night and other non-use periods. This will keep evaporation, the cause of main heat loss, to a minimum, and will greatly reduce pool heating costs. During warmer weather, the cover may be required only at night.
• Recirculation of cold discharge air back into the evaporator coil will greatly reduce the unit’s heating capacity and efficiency.
• This unit features an ‘up-flow’ discharge for quiet operation. Air is pulled up through the evaporator coil and discharged through the top grill. Allow at least 5 ft (1.5 m) clearance above the unit for unrestricted air discharge. DO NOT install the unit under a porch or deck. Refer to Fig. 1.
• To minimize water piping, locate the unit as close as possible to the existing pool pump and filter.
6
Fig. 1: Installation Clearances
• When installed in areas where freezing temperatures can be encountered, drain the water circuit to prevent possible freeze-up damage. See the
Freeze Protection Section.
Electrical Connections
NOTE: Refer to the National Electrical Code, Article
680, for general requirements for swimming pools and equipment, and to Article 440 for special considerations necessary for circuits supplying hermetic refrigeration motor/compressors.
• For high wind installation requirements, refer to the diagram on page 8.
• Locate the equipment disconnect means within 3 feet of the heater’s electrical enclosure, or as close to the heater as possible. Always satisfy applicable codes and standards.
Refer to the unit rating plate below the control panel for precise power requirements for your unit, and for ampacity and over-current protection requirements.
• In sizing power wiring, be especially aware of upsizing requirements necessary due to wiring distances. Always satisfy applicable codes and standards.
All wiring must be in accordance with the National
Electrical Code, NFPA No. 70, latest edition, and all applicable state and local codes. Wiring diagrams are located on pages 18 and 19.
• Electrical installation should be done by a licensed electrician only.
7
8
Model No.
5310
6310
8320
VAC in - Phase - Hz
Minimum Circuit
Ampacity (A)
38.2
208/230 - 1 - 60
208/230 - 1 - 60
208/230 - 3 - 60
208/230 - 1 - 60
208/230 - 3 - 60
33.45
25.45
37.45
33.3
Table A: Typical System Electrical Power Requirements
Maximum Breaker
Size (A)
50
60
50
60
60
This unit is pre-wired to work with external control systems, heat-on-demand options and other external time clock overrides. Refer to the external control system’s instructions, and page 22 of this manual, for installation information.
Water Connections
the purpose and, in either case, should be at least equal in size to the main pool/spa circulation piping.
CAUTION: The heat pump pool heater inlet and outlet connections are NOT interchangeable. They must be connected as instructed below.
WATER IN
WATER OUT
Fig. 2: Water Connections
1. Connect the heat pump pool heater in the return water line between the filter and the pool/spa. See the Plumbing Diagrams beginning on page 16.
2. Connect the filter outlet to the fitting marked
WATER IN at the bottom front of the unit.
4. In cold weather (freeze zone) areas, shutoff valves
(ball or gate type) must be installed at the unit inlet and outlet to facilitate service and cold weather drain-down.
5. Operate the pump and check the system for leaks.
3. Connect the fitting marked WATER OUT to the return piping to the pool/spa. Unit inlet/outlet connection fittings are 2-inch PVC unions.
Pressure Drop
Water connections from the unit to the main return line can be PVC pipe or flexible pipe approved for
For system pressure drop information, refer to Table B below.
Flow
(gpm)
40
50
60
10
20
30
5310
7
10
11
1
2
4
Pressure Drop (psi)
6310
6
9
10
1
3
11
Table B: Pressure Drop Across Heat Pump Pool Heater
8320
9
10
11
1
3
9
9
WARNING: Install a check valve and/or a Hartford loop AFTER the heat pump pool heater and
BEFORE any chlorinating devices. Install any automatic chemical feeders AFTER the heat pump pool heater. Improper installation of any type of auto- matic chemical feeders can result in serious damage to, or premature failure of, the heat pump pool heater and will void the heat pump pool heater warranty.
Defrost Switch: Prevents heat pump pool heater operation if ambient air temperature falls below a predetermined safe minimum (approximately 42° F).
Delay Timer: Prevents compressor from short cycling, which could damage or destroy the hermetic motor/compressor. Upon water temperature control satisfaction, or other circuit interruptions, this solid state device will prevent compressor restart for approximately 5 minutes.
Controls & Indicator Lamps
(Analog Models)
Refrigerant Low Pressure Control: Stops the compressor if refrigerant suction (low side) pressure falls too low as a result of a malfunction, loss of charge or extreme cold conditions.
Your analog heat pump pool heater incorporates safety controls and indicators to ensure its safe, reliable operation (for models with digital controls, see page
11).
Indicator Lamps: There are 6 indicator lamps located on the unit control panel (see Fig. 3 below):
Water Pressure Switch: Prevents operation when the pump is OFF. The unit requires 5 psi minimum pressure.
• Power (amber lamp): When lit, indicates power is applied to the unit.
Water Temperature Control: Pool/spa water temperature is controlled by the heat pump pool heater thermostat on the unit control panel, which contains a switch and 2 thermostats, one for setting a heat spa temperature and the other for a swimming pool temperature. The switch can operate an optional external control system, or can switch between thermostats for pool or spa.
NOTE: The heat pump pool heater will not run when the Remote position is selected on the Pool/Spa selector switch and there is no remote control system attached.
• Water Flow (green lamp): When lit, indicates normal water flow.
• Heat Demand (green lamp): When lit, indicates the actual water temperature is below the target water temperature.
NOTE: The heat pump pool heater will not run when the Remote position is selected on the Pool/Spa selector switch and there is no remote control system attached.
Fig. 3: Indicator Lamps — Analog Models
10
• Compressor Delay Active (amber lamp): Under
normal operation, when lit, indicates compressor anti-short cycle timer is active. The fan will run but the compressor will be OFF for 6 to 8 minutes.
4. Allow the heat pump pool heater to operate for a few minutes to stabilize operating pressures and to allow various component temperatures to normalize.
• Defrost Active (red lamp): When lit, indicates unit is in defrost mode. Defrost mode occurs when ice starts to form on the outside coil. The fan will continue to run but the compressor will stay OFF (not heating) until weather conditions improve.
5. Verify that the discharge air temperature is approximately 8°–10° cooler than the air entering the unit.
If not, see the Troubleshooting Section.
Controls (Digital Models)
• Low Pressure (red lamp): When lit, indicates failure in the refrigeration circuit. When this lamp is
ON, service is required. Call for service assistance.
Your heat pump pool heater incorporates digital safety controls and indicators to ensure its safe, reliable operation (for models with analog controls, see page
10).
System Start-Up
1. Verify that the Power lamp is ON and that the pool/spa pump is running and circulating properly.
Water Pressure Switch: Prevents operation when the pump is OFF. The unit requires 5 psi minimum pressure.
2. Verify that the control panel Spa-Remote-Pool switch is in the Remote (OFF) position; see Fig. 4 below.
3. Turn the control switch to either Pool or Spa to turn the system ON and raise the thermostat setting above the current water temperature. At this time the 2 green lamps should illuminate. The fan and compressor should start up and run simultaneously.
Digital Water Temperature Control: The pool water temperature is controlled by the heat pump pool heater’s digital control system, which gives you the option of two settings: one for the desired spa temperature and the other for the desired pool temperature.
Additionally, as mentioned earlier, the unit is compatible with most ‘2-wire’ and ‘3-wire’ control/automation systems.
Fig. 4: Selector Knobs — Analog Models
NOTE: The heat pump pool heater will not run when the Remote position is selected on the Pool/Spa selector switch and there is no remote control system attached.
11
Fig. 5: Digital Water Temperature Control
Defrost Sensor: Prevents unit operation if ambient air temperature falls below a predetermined safe minimum (approximately 42°–48°F, based on humidity).
The compressor will shut OFF but the fan will continue to run.
Delay Timer: Prevents compressor from short cycling, which could damage or destroy the hermetic motor/compressor. Upon water temperature control satisfaction, or other circuit interruptions, this solid state device will prevent compressor restart for approximately 5 minutes.
Digital Controls Operating
Instructions
System Start-Up
The electronic board has the capability of memorizing two different programmed temperature settings as follows (refer to Fig. 5):
1. Verify that the Digital Board is displaying a temperature and the pool pump is running and water is circulating properly.
• For a pool, maximum 95°F (35°C)
2. Verify that the Board is programmed so that the desired temperature of the Pool and Spa is higher than the displayed current water temperature.
• For a spa, maximum 104°F (40°C)
To Select Pool or Spa Mode
3. Allow the heat pump pool heater to operate for a few minutes to stabilize operating pressures and to allow various component temperatures to normalize.
To have access to either one of these programs, press the SET key until you see P _S and by pressing the
UP or DOWN key you can switch to POL or SPA.
4. Verify that the discharge air temperature is approximately 8°–10°F cooler than the air entering the unit. If not, see the Troubleshooting Section.
To Increase the Desired Water
Temperature (Pool or Spa Mode)
Seasonal Start-Up or Annual
Check
Push the SET key until you see POL or SPA. The programmed temperature will be displayed. Press the UP arrow to increase the temperature setting one degree at a time.
To Lower the Desired Water
Temperature (Pool or Spa Mode)
NOTE: At the beginning of the heating season, or whenever the pool water temperature is to be raised several degrees, the pool pump and heat pump pool heater may need to operate continuously for several days. During summer months, only a few hours per day may be necessary, or none at all.
Push the SET key until you see POL or SPA. The programmed temperature will be displayed. Press the
DOWN arrow to decrease the temperature setting one degree at a time.
1. Remove leaves, pine needles, etc., from the evaporator coil. Clean the coil by gently applying a mild solution of household liquid soap and water.
Once the control has been programmed to the desired pool water temperature, the programmed temperature will be displayed for approximately 5 seconds. Then the digital display will display the actual pool water temperature.
2. Gently rinse the coil with water; DO NOT use high pressure.
3. Backwash or otherwise clean the pool filter. If necessary, clean the skimmer basket and pump strainer.
To make the Board a Pool ONLY Board, call 800-
375-7378 for instructions.
To Select Temperature in °C or °F
Press the SET key until you see F _C. By pressing the
UP or DOWN key you can switch to °F or °C. Once the temperature display mode has been programmed it will be displayed for approximately 5 seconds, then the digital display will return to the actual pool water temperature in the mode that you have chosen.
NOTE: If the pool pump and heat pump pool heater shut OFF before the water temperature is raised to the desired level, you must lengthen the running time of both. To do this, reset the time clock dial for the longer running time, or manually operate the pump with the timer override switch. Since the heat pump pool heater capacity and efficiency are both greater at higher ambient air temperatures, run time should be set to take advantage of all daylight hours, when the air is generally warmer.
12
4. Set the valves to ensure proper water flow through the unit.
Summer Shutdown Maintenance
If you do not plan to use the heat pump pool heater during the summer months, secure and protect it as follows:
NOTE: The heat pump pool heater MANUFACTUR-
ER IS NOT RESPONSIBLE for maintenance adjustments.
1. Turn the unit circuit breaker or disconnect switch to
OFF.
2. Leave the valves set the way they are unless additional circulation is required. DO NOT stop all flow through the heat pump pool heater.
The following maintenance procedures are designed to keep your unit operating at a high level of reliability.
Maintenance must be performed on a periodic
basis to maintain warranty coverage and prevent system failures and performance degradation.
3. IMPORTANT: Remember to reset the valves before the next heating season, or the unit will not operate properly.
Freeze Protection
Air Coil Cleaning
Efficient operation depends on free circulation of air through the thin and tightly-spaced fins of the evaporator coil(s). The evaporator must be cleaned whenever it has a buildup of dirt or debris.
If the unit is installed in a location subject to freezing conditions, it is important to protect the water circuit from freezing, just as should be done for the pump and filter.
CAUTION: To clean the fins, spray gently with a garden hose. DO NOT pressure wash. Doing so will bend the fins and can void the warranty.
System Drain-Down
Cabinet Care (optional)
1. Turn the unit circuit breaker or disconnect switch to OFF.
The cabinet is designed for outdoor use and requires little care. However, you can clean it if you wish.
2. With the pool pump OFF, close the external shutoff valves and loosen the inlet and outlet water unions to allow water to drain. Use a Wet/Dry Vac or air pressure to remove excess water.
WARNING: Shut OFF electricity to the unit before cleaning.
3. Loosely Re-attach the unions.
Wash the cabinet with soap and water.
4. Cover the unit with a waterproof cover.
Unplug Condensation Drain Holes
Continuous Pump Operation
It is also possible in some areas to prevent unit freeze damage by operating the pump continuously during freezing weather. However, this results in significantly higher pump operating costs. Further, if a sustained power failure occurs, the unit MUST be drained anyway, or freeze damage could result.
The unit extracts humidity from the air as it passes through the coil, similar to the way a cold drink outside
“sweats” on a hot day. This condensation drains from the bottom of the unit.
1. Routinely check to be sure the condensation drain holes in the base of the unit are not plugged with dirt or debris.
2. If condensation becomes a problem, optional drain pans are available from your heat pump pool heater distributor or pool dealer.
13
Troubleshooting
coils, or any other obstruction to airflow will reduce performance.
If your unit does not operate, or simply does not heat your pool water, Fault Codes (digital models), or the indicator lamps (analog models) on the front control panel, can provide valuable clues as to what is wrong, and may even indicate precisely what the problem is.
Always observe these codes (or lamps) before calling a service representative. By reporting on the telephone the Fault Codes (or which lamps are ON or
OFF) that are showing, the service rep may be able to solve the problem without the expense of a service call.
•
• Is the pool blanket/cover being used?
Unblanketed pools can lose up to 10 degrees per night compared to 4 degrees or fewer when a blanket is used. Without a blanket, the total heat gained during the day can be lost overnight.
Are rapid heat losses occurring in some other way, such as high wind, spillage, rainfall, flow through solar panels at night, or a high water table?
B. UNIT IS NOT RUNNING
•
A. UNIT IS RUNNING, BUT NOT HEATING
Is water flow through the unit adequate? Check the unit for obstructions, such as a clogged filter pump strainer, a dirty filter, or valves not positioned correctly.
• Is the temperature display or control panel Power lamp ON? If not, the circuit breaker may be shut
OFF or tripped. Reset the breaker by switching it
OFF, and then back ON. Verify that the breaker is set and operating properly before calling for service.
• Is the ejected air from the unit 8°–10°F cooler than incoming air? If so, the unit is extracting heat from the air and transferring it to the pool.
• Is water condensing on the evaporator and internal copper pipes? This is also evidence of heat removal from the air. When the air is cool with low humidity, condensation may not be evident.
• How long has the unit been operating? During initial pool heating in cold weather, it may require a week to elevate the water temperature to a comfortable level. Normally, it takes about 4 days.
How many hours per day is the unit operating?
Remember that the heat pump pool heater only
operates while the pool pump is running. Set the time clock to permit 24 hour per day operation. After the desired temperature is reached, return the unit to normal operation of 8–10 hours per day.
• Is the thermostat setting and the Pool/Spa setting correct? Verify that the temperature has been properly set on the thermostat, and that it is high-
er than the current water temperature. On analog units, all 3 lamps should be illuminated and the fan should begin to run.
• Have you waited approximately 5 minutes for the time delay? After the unit has been running and then shut OFF for any reason, there is a delay before operation can begin again.
• Is the Heat Light or Heat Demand lamp ON? If not, then the thermostat setting is not higher than the temperature of the water. Raise the thermostat setting.
NOTE: The heat pump pool heater will not run when the Remote position is selected on the Pool/Spa selector switch and there is no remote control system attached.
NOTE: If the pool pump and heat pump pool heater shut OFF before the water temperature is raised to the desired level, you must lengthen the running time of both. To do this, reset the time clock dial for the longer running time, or manually operate the pump with the timer override switch. Since the unit capacity and efficiency are both greater at higher ambient air temperatures, run time should be set to take advantage of all daylight hours, when the air is generally warmer.
C. CONDENSATION SEEMS EXCESSIVE
Heat pump pool heaters can produce a large amount of condensation (water) during operation. If you suspect that the unit is leaking: a.
Use a pool chemistry test kit to confirm there is no chlorine in the condensation. Or,
• Is airflow through the unit being obstructed?
Restrictions such as shrubbery, tall grass, dirty
14
b. Shut the unit OFF and leave the filter pump running to see if the water stops dripping. If the water stops dripping, the unit is not leaking.
Service Call Verification
Water Flow
•
Before you make a service call, first determine if the problem is:
• Verify that the pool filter is clean to provide good flow.
Warranty Service
• Verify that valves are properly positioned to allow adequate water flow through the unit.
• Unit operation (power supply, water flow, or time clock adjustment)
NOTE: The MANUFACTURER IS NOT RESPON-
SIBLE for these adjustments.
• If the Water Flow lamp (analog models) on the control panel still does not light, and water is circulating in the pool, verify that all valves are positioned correctly.
Time Clock Adjustment
Power Supply
• Verify that all circuit breakers are reset and working properly.
Verify that the time clock is set to permit the unit to run long enough to heat properly.
• If the temperature display or the Power lamp on the control panel still does not light, contact the installing dealer, since it may be a power problem requiring an electrician.
Fault Code
OFF
LP & LP3
HP & HP3
FLo & FL3
FS
- -
Meaning of Code
The desired programmed temperature point is lower than 60°F (15°C).
Shortage of refrigerant gas in the unit or faulty low pressure control. The unit will show
(LP3) after 3 LP faults and shuts down the unit and pool pump for protection. If this occurs, you should call for service.
Low water flow in the unit or faulty high pressure control. Check water flow/backwash. The unit will show (HP3) after 3 HP faults. This will stop the unit for protection.
Possible causes:
• The filter is in backwash position.
• The filter pump is stopped.
• The filter is dirty.
• Shortage of water to pool pump.
• FIL parameter must be set to activate pool pump.
• Water pressure switch must be adjusted or it is broken.
• The unit is in the protection mode and will show (FL3), press any key to restart the unit.
FL3 code will stop the unit and pool pump.
Unit is in the defrosting cycle.
(The fan works but the compressor is stopped.)
Keypad is pressing down on both buttons. Replace keypad.
Table C: Control Board Fault Codes — Digital Models
15
Plumbing Diagrams
Water In
(from pool or spa)
Filter
Water Out
(to pool or spa)
Fig. 6: For systems with pumps of less than 2 HP (under 80 gpm), no external bypass is required. Connections are 2-inch unions. Plumb the heat pump pool heater AFTER the filter and BEFORE any chlorinators.
Water In
(from pool or spa)
Filter
Water Out
(to pool or spa)
Fig. 7: For systems with pumps of 2 HP or greater (over 80 gpm), an external bypass is required. Adjust the bypass valve to divert a minimum of 40 gpm through the heat pump pool heater. Connections are 2-inch unions. Plumb the heat pump pool heater AFTER the filter and BEFORE any chlorinators.
16
Fig. 8: Pool Piping for Heat Pump Pool Heater and Gas Pool Heater
UNITS UNITS UNITS
Fig. 9: Pool Piping for Heat Pump Pool Heaters, Multiple, Primary/Secondary
17
Wiring Diagram — 208V/230V Single-Phase — Analog Models
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
TORQUE SCREWS : 40 LB - IN
LEGEND
COMPRESSOR
C
R
S
Y
R
BL
M
COIL
[CONTACTOR,FAN RELAY]
LED
TER. STRIP
CAPACTIOR
LPS
HPS
M
R
T
WPS
LOW PRESURE SWITCH
HIGH PRESURE SWITCH
COMPRESSOR
CONTACTOR
FAN RELAY
T-STAT
WATER PRESURE SWITCH
C
D
A
B
E
F
L E D'S
POWER
HEAT
WATER
COMPRESSOR
DEFROST
L/P SWITCH
AMBER
GREEN
GREEN
AMBER
RED
RED
SPA / REMOTE / POOL
SWITCH
SHOWN IN POOL POSITION
BL
1
2
3
4
5
6
10
11
7
8
9
12
A
B
C
D
R
BK
14 10 11
PR BK
R
1
T SPA
2 3
2.
GR
FAN
MOTOR
BK
BK
BR
BK
R
R
240V 208V
BK
2 amp
FUSE
BK/W
TRANSFORMER
24 V
5
1
A
BK BK BK
C
3.
W
W
4
WPS
BK
F
1
T POOL
2.
2 3
9
BK BK
8
13 12
BL
LPS
BK
GY/BK BK
21
22
23
24
T
C
S
P
GY
R
R/BL
R/BL
BK/R
16
24 Volts AC
15
W
GY
GY
BL
POT 1
POT 2
TEMP. CONTROL
BOARD
N.O.
W
N.C.
1.
WATER SENSOR
BK/R
BK
7
O/R
B
BK
5
E D
BK BK BK BK
2
BK/GY
DEFROST
SWITCH
3
T
2
1
6
Delay Timer
P
BK/GY
3
R
M
W
W
W
O W
W
W
HAVE A QUESTION ?
CALL 800-375-7378
1.
2.
3.
NOTES:
SENSOR RATED @
75º 10.5K
77º 10K
84º 8.50K
T-STAT RATED @
75º 4.73K
77º 4.25
84º 2.44K
TRANSFORMER WIRED FOR 240V,
MOVE RED WIRE TO 208 TER. FOR
208V
WIRE COLOR CODE
BK BLACK
BL
BR
BLUE
BROWN
G GREEN
GY GRAY
O ORANGE
P PINK
PR PURPLE
R RED
T TAN
W WHITE
Y YELLOW
WIRING INFORMATION
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
LOW VOLTAGE
FACTORY STANDARD
FACTORY OPTION
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
USE TERMINALS 21 & 22 TO ATTACH 2 WIRE CONTROL SYSTEMS THAT HAVE THIER
OWN SENSORS FOR TEMPERATURE CONTROL.
USE TERMINALS 22 , 23 & 24 TO ATTACH 3 WIRE CONTROL SYSTEM THAT
UTILIZE OUR TEMPERATURE SENSOR FOR TEMPERATURE CONTROL.
TO ENGAGE AN EXTERNAL CONTROL SYSTEM PUT THE
POOL-REMOTE-SPA SWITCH IN THE REMOTE POSITION
REV
RAYPAK
082708
POOL HEAT PUMP
5310, 6310, 8320
DWG NUMBER
00-11029
18
Wiring Diagram
208V/230V
Single-Phase
Digital Models
C
R
COMPRESSOR
R
S
Y
BL
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
TORQUE SCREWS : 40 LB - IN
M
FAN
MOTOR
PR
T
BK
GR
COM
FR NC
NO
FR
R
BK
5
4
R BK
BL
R
O
BK
AC F1 F2 F3
240V
R
208V
BK
BK WS DS AS PS
TRANSFORMER
12V 12V
BK BK BK BK
20 19 18 17 13
HPS
12
11 9 7
10 8
O P
6
BL
W
R
BL
R
FUSE
1
2
3
15
16
24 V H. O. D.
W
REMOTE CONTROL
FIELD CONNECTIONS
21
22
23
24 P
T
C
S
FR
LPS
HPS
M
WPS
LEGEND
COIL
[CONACTOR, FAN &
POWER DEFROST ]
TER. STRIP
CAPACTIOR
FAN RELAY
LOW PRESURE SWITCH
HIGH PRESURE SWITCH
COMPRESSOR
CONTACTOR
WATER PRESURE SWITCH
1.
NOTES:
TRANSFORMER WIRED FOR 240V,
BLACK & ORANGE WIRE FOR 240V,
BLACK & RED WWIRE FOR 208V
R
BK
LPS
WPS
BL
BL
O/BK
O
P
M
WIRE COLOR CODE
BK BLACK
BL
BR
BLUE
BROWN
G GREEN
GY GRAY
O ORANGE
P PINK
PR PURPLE
R RED
T TAN
W WHITE
Y YELLOW
WIRING INFORMATION
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
LOW VOLTAGE
FACTORY STANDARD
FACTORY OPTION
HAVE A QUESTION ?
CALL 800-375-7378
2 WIRE REMOTE CONTROL
USE TERMINALS 21 & 22 TO ATTACH 2 WIRE CONTROL SYSTEMS THAT HAVE THIER
OWN SENSORS FOR TEMPERATURE CONTROL.
SET POOL TEMPERATURE TO OFF AND SET SPA TEMPERATURE TO 104
RAYPAK
POOL HEAT PUMP,SCROLL COMPRESSOR
DIGITAL CONTROL
REV 072606
DWG NUMBER
01-0669
19
1.
Wiring Diagram — 208V/230V 3-Phase — Analog Models
COIL
[CONTACTOR,FAN RELAY]
LED
TER. STRIP
CAPACTIOR
TO SLAVE #1
TO SLAVE#2
TO SLAVE#3
TO SLAVE#4
LEGEND
COMPRESSOR
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
TORQUE SCREWS : 40 LB - IN
R
Y
M
BL
BK BL R
L1
L2
L3
LPS
HPS
M
R
T
WPS
LOW PRESURE SWITCH
HIGH PRESURE SWITCH
COMPRESSOR
CONTACTOR
FAN RELAY
T-STAT
WATER PRESURE SWITCH
E
F
A
B
C
D
L E D'S
POWER
HEAT
WATER
COMPRESSOR
DEFROST
L/P SWITCH
AMBER
GREEN
GREEN
AMBER
RED
RED
21
22
23
24
T
C
S
P
GY
R
R/BL
R/BL
16
24 Volts AC
15
BK/R
W
12
11
10
9
14
SPA / REMOTE / POOL
SWITCH
SHOWN IN POOL POSITION
BL
1
2
3
4
5
6
10
11
7
8
9
12
A
B
C
D
R
BK
MASTER RELAY
13
4
8
3
7
2
6
1
5
14 10 11
R
PR BK
GR
FAN
MOTOR
BK
BK
BR
R
BK
208V 240V
3.
2 amp
FUSE
BK
TRANSFORMER
24 V
R
1
BK/W
BK
A
BK
5
BK
3 4 5
1
3 PHASE MONITOR
8
C
BK/GY
W
W
T
1
SPA
2 3
2.
4
WPS
BK
1
T POOL
2.
2 3
GY/BK
13 12
F
BK
9
BK
BK
BL
LPS
BK
8
GY
GY
BL
POT 1
POT 2
TEMP. CONTROL
BOARD N.O.
W
N.C.
1.
WATER SENSOR
BK/R
BK
7
O/R
B
BK
5
W
E D
BK BK BK BK
2
BK/GY
DEFROST
SWITCH
3
T
2
1
6
Delay Timer
P
BK/GY
3
R
M
W
W
W
O W
W
HAVE A QUESTION ?
CALL 800-375-7378
1.
2.
3.
NOTES:
SENSOR RATED @
75º 10.5K
77º 10K
84º 8.50K
T-STAT RATED @
75º 4.73K
77º 4.25
84º 2.44K
TRANSFORMER WIRED FOR 240V,
MOVE RED WIRE TO 208 TER. FOR
208V
WIRE COLOR CODE
BK BLACK
BL
BR
BLUE
BROWN
G GREEN
GY GRAY
O ORANGE
P PINK
PR PURPLE
R RED
T TAN
W WHITE
Y YELLOW
WIRING INFORMATION
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
LOW VOLTAGE
FACTORY STANDARD
FACTORY OPTION
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
USE TERMINALS 21 & 22 TO ATTACH 2 WIRE CONTROL SYSTEMS THAT HAVE THIER
OWN SENSORS FOR TEMPERATURE CONTROL.
USE TERMINALS 22 , 23 & 24 TO ATTACH 3 WIRE CONTROL SYSTEM THAT
UTILIZE OUR TEMPERATURE SENSOR FOR TEMPERATURE CONTROL.
TO ENGAGE AN EXTERNAL CONTROL SYSTEM PUT THE
POOL-REMOTE-SPA SWITCH IN THE REMOTE POSITION
REV
RAYPAK
POOL HEAT PUMP
3 PHASE 208 / 230 V 60hz
120808
DWG NUMBER
00-11047
20
Wiring Diagram — 208V/230V 3-Phase — Digital Models
BK BK BK BK
20 19 18 17 13
HPS
12
COMPRESSOR
USE COPPER CONDUCTORS ONLY
USE 75 ° C 600 V WIRE
TORQUE SCREWS : 40 LB - IN
R
Y
BL
GR
M
FR
R
BK
5
4
R BK
FAN
MOTOR
R
R
R
3
1
4 5
3 PHASE MONITER
8
PR
BK
BR
BL
R
R
BK
1.
240V 208V
R
BL
TRANSFORMER
12V 12V
AC F1 F2 F3
12~ 0 ~12
BK
BK WS DS AS PS
O P
11 9 7
10 8 6
BL
W
R
1
2
3
FUSE
2 amp
N
L3
L2
L1
LEGEND
COIL
[CONACTOR]
TER. STRIP
CAPACTIOR
SENSOR
FR
LPS
HPS
M
RS
WFS
FAN RELAY
LOW PRESURE SWITCH
HIGH PRESURE SWITCH
COMPRESSOR
CONTACTOR
REVERSING
SOLENOID
WATER FLOW SWITCH
1.
NOTES:
TRANSFORMER WIRED FOR 240V,
BLACK & ORANGE WIRE FOR 240V,
BLACK & RED WWIRE FOR 208V
21
22
23
24
T
C
S
P
R
BK
REMOTE CONTROL
FIELD CONNECTIONS
LPS
BL
BL
WFS
O/R
O
P
M
WIRE COLOR CODE
BK BLACK
BL
BR
BLUE
BROWN
G GREEN
GY GRAY
O ORANGE
P PINK
PR PURPLE
R RED
T TAN
W WHITE
Y YELLOW
WIRING INFORMATION
LINE VOLTAGE
FACTORY STANDARD
FIELD INSTALLED
LOW VOLTAGE
FACTORY STANDARD
FACTORY OPTION
2 WIRE REMOTE CONTROL
USE TERMINALS 21 & 22 TO ATTACH 2 WIRE CONTROL SYSTEMS THAT HAVE THIER
OWN SENSORS FOR TEMPERATURE CONTROL.
SET POOL TEMPERATURE TO OFF AND SET SPA TEMPERATURE TO 104
RAYPAK
POOL HEAT PUMP,SCROLL COMPRESSOR
DIGITAL CONTROL, 208/230V 3 Phase
60Hz
REV 040809
DWG NUMBER
0011099
21
Installing a Remote Control
Device on Analog Heaters
Wiring
Installing a Remote Control
Device on Digital Heaters
Wiring
For a 2-wire control, use the TOTAL and COMMON connections on the heat pump pool heater wiring block.
For a 2-wire control, use the TOTAL and COMMON connections on the heat pump pool heater wiring block.
For a 3-wire control, use the COMMON, SPA and
POOL connections on the heat pump pool heater wiring block.
For a 3-wire control, use the COMMON, SPA and
POOL connections on the heat pump pool heater wiring block.
Fig. 10: Heater Wiring Block — Analog Heaters
Heater Settings
Fig. 11: Heater Wiring Block — Digital Heaters
Heater Settings
1. To operate the heater using a 2-wire remote control device, simply switch the Spa-Remote-Pool knob to the Remote position and make sure the heater is enabled on the remote control device.
1. Make sure the heater is disabled on the remote control device. Then, push the SET key until POL is displayed. Push the DOWN arrow key until OFF is displayed. Wait until a temperature is displayed before beginning the next step.
2. To operate the heater using a 3-wire remote control device, simply switch the Spa-Remote-Pool knob to the Remote position and set the temperature for pool and spa.
2. Push the SET key until SPA is displayed, then push the UP arrow to 104°F. Wait until a temperature is displayed before beginning the next step.
3. Push the SET key until P_S is displayed, then push the DOWN arrow until POL is displayed.
Wait until a temperature is displayed before beginning the next step.
22
4. Finally, enable the heater on the remote control device. When there is a call for heat, the heater display will show SPA. When the heater is disabled, the display will show POL.
23
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project