Pulsar PSBEN2024B - v1.1 Instruction


Add to my manuals
34 Pages

advertisement

Pulsar PSBEN2024B - v1.1 Instruction | Manualzz
PSBEN 2024B
v.1.1
PSBEN 27,6V/2A/2x7Ah/EN
Buffer, switch mode power supply unit.
EN**
Edition: 6 from 02.02.2015
Supercedes edition: 5 from 18.06.2014
LED Version
www.pulsar.pl
BLACK POWER
PSBEN2024B
TABLE OF CONTENTS
1. PSU FEATURES. ................................................................................................................................................................... 4
2. FUNCTIONAL REQUIREMENTS OF THE PSU COMPLIANT WITH THE EN 50131-6 STANDARD. ................. 5
3. TECHNICAL DESCRIPTION. ............................................................................................................................................ 6
3.1 GENERAL DESCRIPTION. ....................................................................................................................................................... 6
3.2 BLOCK DIAGRAM. ................................................................................................................................................................ 7
3.3 DESCRIPTION OF PSU’S COMPONENTS AND CONNECTORS. .................................................................................................. 8
4. INSTALLATION. ................................................................................................................................................................ 10
4.1 REQUIREMENTS. ................................................................................................................................................................ 10
4.2 INSTALLATION PROCEDURE. .............................................................................................................................................. 10
5. FUNCTIONS......................................................................................................................................................................... 12
5.1 CONTROL PANEL. .............................................................................................................................................................. 12
5.2 MAIN MENU. ...................................................................................................................................................................... 13
5.2.1 Voltage indicator „Uo”
........................................................................................................................ 13
5.2.2 Output current indicator „Io”
5.2.3 Failure history “FLh”
.............................................................................................................. 13
........................................................................................................................... 14
5.2.4 Current failures „FLc”
........................................................................................................................ 14
5.2.5 List of failure codes and information messages. ....................................................................................................... 15
5.3 PSU CONFIGURATION. ....................................................................................................................................................... 17
5.3.1 Battery test ON/OFF „tSt”
5.3.2 LED Display Dimmer „dIS"
.................................................................................................................... 18
.................................................................................................................. 19
5.3.3 Setting the communication address „Adr”
applies to cooperation with PowerSecurity. ............... 19
5.3.4 Setting the transmission speed „trS”
applies to cooperation with PowerSecurity. ...................... 20
5.3.5 Setting the parity of the transmission “trP”
applies to cooperation with PowerSecurity. .............. 21
5.4 ACOUSTIC INDICATION. ..................................................................................................................................................... 21
5.5 TECHNICAL OUTPUTS. ........................................................................................................................................................ 22
5.6 INPUT OF COLLECTIVE FAILURE EXT IN. ........................................................................................................................... 22
5.7 ENCLOSURE TAMPER INDICATION - TAMPER. ................................................................................................................. 23
5.8 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP. ................................................................................................... 24
5.9 PSU OVERLOAD. ................................................................................................................................................................ 24
6 RESERVE POWER SUPPLY CIRCUIT........................................................................................................................... 25
6.1
6.2
6.3
6.4
6.5
6.6
RUNNING THE PSU FROM THE BATTERY. ........................................................................................................................... 25
DEEP DISCHARGE BATTERY PROTECTION UVP. ................................................................................................................. 25
BATTERY TEST. .................................................................................................................................................................. 25
STANDBY TIME. ................................................................................................................................................................. 26
BATTERY CHARGING TIME. ................................................................................................................................................ 26
OPERATION WITHOUT A BATTERY. ..................................................................................................................................... 26
7. REMOTE MONITORING (OPTIONS: WI-FI, ETHERNET, RS485, USB)................................................................. 27
7.1
7.2
7.3
7.4
7.5
COMMUNICATION VIA THE USB-TTL INTERFACE. ............................................................................................................ 27
ETHERNET NETWORK COMMUNICATION. ........................................................................................................................ 27
THE WI-FI WIRELESS COMMUNICATION. ............................................................................................................................ 28
RS485 NETWORK COMMUNICATION. ................................................................................................................................. 29
„POWERSECURITY” PROGRAM. .......................................................................................................................................... 30
2
www.pulsar.pl
PSBEN2024B
BLACK POWER
8. TECHNICAL PARAMETERS. .......................................................................................................................................... 31
TABLE 13. ELECTRICAL PARAMETERS. ...................................................................................................................................... 31
TABLE 14. MECHANICAL PARAMETERS. .................................................................................................................................... 32
TABLE 15. SAFETY OF USE. ....................................................................................................................................................... 32
9. TECHNICAL INSPECTIONS AND MAINTENANCE. .................................................................................................. 33
3
www.pulsar.pl
PSBEN2024B
BLACK POWER
1. PSU features.
 EN50131-6 compliance, 1÷3 grades and II
environmental class
 mains supply of 230VAC
 uninterrupted voltage of 27,6VDC
 fitting battery: 2x7Ah/12V
 high efficiency 81%
 PSU current efficiency:
 0,58A – for grades 1 , 2 *
 0,23A – for grades 3 **
 2A – for general use ***
(see: chapter 3.1)
 low level of voltage ripple
 microprocessor-based automation system
 intelligent management of PSU’s output power level
 ‘SERIAL’ communication port with implemented
MODBUS RTU protocol
 remote monitoring (option: Wi-Fi, Ethernet, RS485,
USB)
 free program - ‘PowerSecurity’ for monitoring the PSU
operation parameters
 load current control
 output voltage control
 output fuse status control
 dynamic battery test
 battery circuit continuity control
 battery voltages control
 battery fuse status control
 battery charge and maintenance control
 deep discharge battery protection (UVP)
 battery overcharge protection
 battery output protection against short circuit and
reverse polarity connection
 jumper selectable battery charging current
0,2A/0,6A/1A/1,5A
 remote battery test (additional module required)
 START button for battery activation
 STOP button for disconnecting during battery-assisted
operation
 optical indication – LED panel
 output current readings
 output voltage readings
 failure codes with history
 optical indication of PSU overload OVL
 acoustic indication of failure
 adjustable times indicating AC power failure
 technical inputs/outputs with galvanic isolation
 EXT IN input of collective failure
 EPS technical output indicating AC power loss
 PSU technical output indicating PSU failure
 APS technical output indicating battery failure
 internal memory of PSU operating status
 protections:
 SCP short circuit protection
 OLP overload protection
 OHP overheat protection
 OVP over voltage protection
 surge protection
 against tampering: unwanted opening of the
enclosure or detachment from the mounting surface
 convectional cooling
 warranty – 5 year from the production date
4
www.pulsar.pl
BLACK POWER
PSBEN2024B
2. Functional requirements of the PSU compliant with the EN 50131-6
standard.
Functional requirements
EPS network absence
Low battery voltage
Protection against complete battery
discharge
Battery failure
No battery charge
Low output voltage
High output voltage
PSU failure
Surge protection
Short circuit protection
Overload protection
Output fuse activation
Battery fuse failure
EPS technical output
APS technical output
PSU technical output
Input of collective failure
Remote battery test
Tamper indicating enclosure opening
Tamper indicating detachment from the
mounting surface
Requirements of
EN 50131-6
Grade 1
Grade 2
Grade 3
PSBEN2024B
YES
YES
-
YES
YES
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
YES
YES
YES
-
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
5
www.pulsar.pl
PSBEN2024B
BLACK POWER
3. Technical description.
3.1 General description.
The buffer power supply is designed in accordance with the requirements of the EN 50131-6 standard,
grade 1÷3 and II environmental class. It is intended for an uninterrupted supply of alarm system devices requiring
stabilized voltage of 24VDC (+/-15%).
Depending on a required protection level of the alarm system in the installation place, the PSU efficiency
and the battery charging current should be set as follows:
* Grade 1, 2 - standby time 12h
Output current 0,58A + 1,5A battery charge
** Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – EN 50131-1 standard).
Output current 0,23A + 1,5A battery charge
- standby time 60h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – EN 50131-1 standard).
Output current 0,116A + 1,5A battery charge
*** General use – if the PSU is not mounted in an installation complaint with the EN-50131 standard, the
acceptable current efficiency amounts to:
1. Output current 2A + 0,2A battery charge
2. Output current 1,6A + 0,6A battery charge
3. Output current 1,2A + 1A battery charge
4. Output current 0,7A + 1,5A battery charge
Total current of the receivers + battery: 2,2A max.
In case of power decay, a battery back-up is activated immediately. The PSU is housed in a metal
enclosure (color: RAL 9005 - black) with battery space for a 2x7Ah/12V battery. It is fitted with micro switches
indicating unwanted door opening (front panel) and detachment from the mounting surface.
DOPTIONAL POWER SUPPLY CONFIGURATIONS:
(visualization available at www.pulsar.pl)
1. Buffer power supply PSBEN 27,6V/2x1A/2x7Ah/INTERFACE
- PSBEN 2024B + LB2 2x1A (AWZ585,AWZ586)+2x7Ah+INTERFACE
2. Buffer power supply PSBEN 27,6V/4x0,5A/2x7Ah/INTERFACE
- PSBEN 2024B + LB4 4x0,5A (AWZ574,AWZ576)+2x7Ah+INTERFACE
3. Buffer power supply PSBEN 27,6V/24V/2A/2x7Ah/INTERFACE
- PSBEN 2024B + RN25024 (27,6V/24V)+ 2x7Ah+INTERFACE
4. Buffer power supply PSBEN 27,6V/24V/2x1A/2x7Ah/INTERFACE
- PSBEN 2024B + RN25024 (27,6V/24V)+LB2 2x1A (AWZ585,AWZ586)+2x7Ah+INTERFACE
6
www.pulsar.pl
PSBEN2024B
BLACK POWER
3.2 Block diagram.
The PSU is manufactured based on a high-duty system of DC/DC converter. The microprocessor system is
responsible for full diagnostics of the PSU and battery parameters.
Fig. 1. Block diagram of the PSU.
7
www.pulsar.pl
PSBEN2024B
BLACK POWER
3.3 Description of PSU’s components and connectors.
Table 1. Elements of the PSU pcb (see Fig. 2).
Element no.
Description
PANEL – optical indication connector
PBAT; pin - configuration of battery protection UVP
 PBAT =
battery protection (disconnection) off
 PBAT =
battery protection (disconnection) on
TAC; pins J1, J2 - adjustable time lag of AC power failure indication
 J1=
, J2=
time lag T= 5s
 J1=
, J2=
time lag T= 140s
 J1=
, J2=
time lag T= 17m
 J1=
, J2=
time lag T= 2h 20m
Caption:
jumper on,
Operation without battery
(section 6.6)
jumper off
Disabling the time-based lock of the test.
(section 6.3)
– pin; battery charging current selection
, J2=
J3=
IBAT =0,2 A
, J2=
J3=
IBAT =0,6 A
, J2=
J3=
IBAT =1,0 A
, J2=
, J3=
IBAT =1,5 A
Caption:
jumper on,
jumper off
START – button (launching the PSU from a battery)
STOP – button (disconnection of the PSU during battery-assisted operation)
– pin; activation of the acoustic indication
- indication on
- indication off
Caption:
jumper on,
jumper off
VADJ
– potentiometer, DC voltage adjustment
IBAT
J1=
J1=
J1=
J1=
BUZZER – acoustic indicator
FBAT
– fuse in the battery circuit
Connectors:
~AC~ – AC power input
+BAT – DC power battery output
+AUX – DC power output (+AUX= +U, -AUX=GND)
EPS FLT – technical output of AC network absence indication
open
= AC power failure
close = AC power - O.K.
PSU FLT – technical output of PSU failure
open
= failure
close = PSU working correctly - O.K.
APS FLT – technical output of battery failure
open
= battery failure
close = battery O.K.
EXT IN – input of collective failure
VEXT pin – polarization of EXT IN circuit
Communication connector
LEDs – optical indication:
AC
– presence of the AC power
AUX
– DC output voltage
OVL
– PSU overload
PSU
– PSU failure
APS
– battery failure
EXT
– EXT IN input’s status
LB
– battery charge
OVP
– optical indication for activating the over voltage system
TAMPER – connector for the micro switch tamper
8
www.pulsar.pl
PSBEN2024B
Fig. 2. The view of the PSU’s PCB.
Table 2. PSU elements (see fig. 3).
Element no.
Description
Insolation transformer
PSU board (see Tab.1, fig.2)
TAMPER; micro-switch (contacts) of tamper resistance (NC)
FMAINS fuse in the supply circuit (230V/AC)
L-N power supply connector 230V/AC,
PE protective connector
Battery connectors: positive: +BAT = red, negative: - BAT = black
Tamper grip
Fig.3. The view of the PSU.
9
BLACK POWER
www.pulsar.pl
PSBEN2024B
BLACK POWER
4. Installation.
4.1 Requirements.
The PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and
required for a given country) for 230V/AC in and low-voltage installations.
As the power supply is designed for a continuous operation and is not equipped with a powerswitch, therefore, an appropriate overload protection in the power supply circuit should be provided. Moreover, the
user should be informed how to disconnect the power supply unit from the mains supply (usually by assigning an
appropriate fuse in the fuse box). The electrical system shall be made in accordance with applicable standards
and regulations. The power supply should operate in a vertical position in order to provide free and
convectional air flow through ventilating holes of the casing.
4.2 Installation procedure.
CAUTION!
Before installation, cut off the voltage in the 230V power-supply circuit.
To switch off power use an external switch in which the distance between the contacts of all poles in the
disconnection state is not less than 3mm.
1. Mount the PSU in a selected location. It is particularly important to bolt the tamper grip to the mounting surface.
The grip is located in the central part of the enclosure (see fig. 3 [7]) and guarantees indication in case of any
attempts of detaching the device from the mounting surface. Proper installation is one of the requirements of the
EN 50131-6 standard.
Fig. 4. Fixing a tamper grip.
2. Connect the power cables (~230VAC) to L-N terminals of the PSU. Connect the ground wire to the terminal
marked by the earth symbol: PE. Use a three-core cable (with a yellow and green PE protection wire) to make the
connection. Lead the cables to the appropriate terminals through the insulating bushing.
The shock protection circuit shall be performed with a particular care, i.e. the yellow and green wire coat
of the power cable shall stick to one side of the terminal - marked with the PE symbol on the PSU
enclosure. Operation of the PSU without the properly made and fully operational shock protection circuit
is UNACCEPTABLE! It can cause a device failure or an electric shock.
3. Connect the receivers’ cables to the +AUX, -AUX connectors of the terminal block on the PSU board.
4. If necessary, connect the device’s leads to the technical inputs and outputs:
- EPS FLT; technical output of AC power loss indication (alarm panel, controller, indicator, etc.)
- PSU FLT; technical output of the PSU failure.
- APS FLT; technical output of the battery failure.
- TAMPER; output indicating enclosure opening or detachment from the assembly surface.
- EXT IN; input of collective failure.
5. With the IBAT jumper determine the maximum battery charging current, in accordance with the battery
parameters.
6. With the PBAT jumper determine if the discharged battery disconnection system U<20V (+/-5%) shall be on or off.
The battery protection is on when the PBAT jumper is off.
7. Switch on the ~230V AC supply (red AC diode and green AUX diode should be on).
10
www.pulsar.pl
PSBEN2024B
BLACK POWER
8. Check the output voltage (the PSU voltage without load and without battery should amount to 27.5V ÷ 27.7V,
with a battery or during battery charging process: 22V÷27.6V). If the value of the voltage requires adjustment, it
should be set with use of the VADJ potentiometer, monitoring the voltage at the AUX output of the PSU.
9. Connect the batteries in accordance with the markings: +BAT red to 'plus', -BAT black to 'minus’. The LB diode
should be on during battery charging process.
10. Press the STOP button to activate or deactivate a dynamic battery test. Deactivating the test turns out the PSU
failure indication at the APS FLT output, but it does not affect the protection system against complete battery
discharge.
11. Check the current consumption of the receivers, taking into account the battery charging current, so as not to
exceed the total current efficiency of the PSU.
12. Once the tests are completed, close the PSU cover.
Table 3. Operation parameters.
Environmental class
Operating temperature
Storing temperature
Relative humidity
Sinusoidal vibrations during operation
Surges during operation
Direct insolation
Vibrations and surges during transport
II
-10ºC...+40ºC
-20ºC...+60ºC
20%...90%, no condensation
EN 50130-5
EN 50130-5
unacceptable
PN-83/T-42106
Table 4. Factory settings of the PSU.
Indication time of EPS network loss
Battery charging current
Battery presence
Battery test
5s
Deep discharge battery protection UVP
ON
ON
OFF
1
115.2k 8E1
Acoustic indication
LED display dimmer
Communication address
Transmission
0,6A
YES (battery present)
ON
11
section 5.5
section 6.5
section 6.6
section 5.3.1
section 6.3
section 6.2
section 5.4
section 5.3.2
section 5.3.3
section 5.3.4
section 5.3.5
www.pulsar.pl
PSBEN2024B
BLACK POWER
5. Functions.
5.1 Control Panel.
The PSU features a panel with buttons and LED display, enabling reading of all the available electrical
parameters. The panel buttons are used to select and confirm the parameters, which should be displayed.
Fig. 5. Control panel.
Table 5. The description of the buttons and LEDs of the LED panel.
Description
Additional
information
- moves the pointer on the screen
- next screen selection
- selection approval
- red LED – indicating 230V AC voltage
- red LED – indicating power supply overload
section 5.9
- red LED – indicating PSU failure
section 5.2.5
- red LED – indicating battery failure
- green LED – indicating power at the AUX output of the PSU
- three yellow LEDs indicating approximate battery charge level
12
www.pulsar.pl
BLACK POWER
PSBEN2024B
5.2 Main menu.
The PSU is equipped with a menu, which allows to preview the current electrical parameters. The diagram
explaining the menu structure is presented below.
Fig. 6. The menu of the display.
Table 6. The description of display symbols.
Symbol
Description
AUX output voltage [V]
Additional information
Factory setting 27,6V
Output current [A]
Failure history
Section 5.2.3
Current failures
Section 5.2.4
Voltage indicator „Uo”
The voltage indicator displays the measured output voltage at the AUX output. If the voltage drops below
26V (during operation with activated battery test) or exceeds 29.4V, the PSU will indicate a failure.
The resolution of voltage measurement is 0.1V and should be treated with caution. If a greater accuracy is
required, use a multimeter.
5.2.1
Output current indicator „Io”
The output current indicator displays the measured output current drawn from the AUX output.
If the current value is exceeded, the power supply unit will indicate failure.
The resolution of current measurement is 0.1A and should be treated with caution. If a greater accuracy is
required, use a multimeter.
5.2.2
13
www.pulsar.pl
PSBEN2024B
BLACK POWER
Failure history “FLh”
The PSU stores 30 last failures in non-volatile memory, which can be reviewed later.
In order to review the failures, use the "<" or ">" button to set the FLh parameter and confirm by pressing "OK".
The display will show the number of failure in the memory and its code. Pressing the "OK" button again will display
the next failure in the memory.
5.2.3
The memory of the new power supply remembers the events that are the result of the efficiency tests
carried out at the production stage.
- press „<” or „>” button to set the „FLh” parameter on the display
- press „OK” button
- number 1, indicating the number of failure in the memory (the highest priority),
will be displayed. Then, after one second, failure code will be automatically displayed
- press „OK” button
- the number 2, denoting the next number of failure in the memory, will be displayed.
Then, after one second, the next failure code will be automatically displayed.
- if the memory has more failures, pressing the "OK" button will result
in displaying subsequent codes
- the „- - -„ parameter on the display marks the end of the list of failures
5.2.4 Current failures „FLc”
In case of abnormal electrical parameters, the power supply provides optical and acoustic indication of the
failure via corresponding LED and a beeper (if not disabled).
The PSU can simultaneously indicate several failures. Thanks to this solution, codes of all failures and their
priority can be previewed in the FLc menu. In the FLc menu, each press of the "OK" button on the panel displays
the next error code that caused the failure. If there are multiple failures at the same time, pressing the "OK" button
will display the next code. The display order of failures is arranged by priority of importance. The first failures in the
display order are of the highest priority.
Section 5.2.5 summarizes all the failure codes that may occur during the power supply operation. The
individual codes are accompanied by appropriate optical indication on the panel, acoustic indication and activation
of the dedicated technical output.
14
www.pulsar.pl
PSBEN2024B
BLACK POWER
- press „<” or „>” button to set the „FLc” parameter on the display „FLc”
- press „OK” button
- the number 1, indicating the number of failure in the memory (the highest priority),
will be displayed. Then, after one second, failure code will be automatically displayed
- press „OK” button
- the number 2, denoting the next number of failure in the memory, will be displayed.
Then, after one second, the next failure code will be automatically displayed.
- if the memory has more failures, pressing the "OK" button will result in displaying
subsequent codes
- the „- - -„ parameter on the display marks the end of the list of failures
5.2.5
List of failure codes and information messages.
The PSU indicates the operation status with the appropriate code. The codes are divided into two
groups,marked with the initial letters "F" or "I”.
The codes beginning with the letter "F" indicate a failure. The codes that begin with the letter "I" indicate the
correct operation of the PSU or repaired fault, involving, for example, fuse replacement: "I03 - BAT fuse replaced”.
15
www.pulsar.pl
BLACK POWER
PSBEN2024B
Table 7. List of PSU failure codes.
Failure
code
Information
Technical
output
activation
Additional information
- No AC mains supply
- FMAINS fuse failure
- Blown FAUX fuse
- AUX output overload
- Blown FBAT fuse
- Short circuit in the battery circuit
- Short circuit in the AUX output circuit
- PSU overload
- Worn out battery
- Undercharged battery
- Battery not connected
F01
AC power fail!
EPS FLT
F02
AUX fuse fail!
PSU FLT
F03
BAT fuse fail!
APS FLT
F04
Output overload!
PSU FLT
F05
Battery fail!
APS FLT
F06
High AUX voltage!
PSU FLT
- Output voltage over 29.4V
F07
High battery voltage!
PSU FLT
- Battery voltage >28V
F08
Charge circuit fail!
PSU FLT
F09
Low AUX voltage!
PSU FLT
F10
Low battery voltage!
APS FLT
F11
Low battery volt. –
off!
APS FLT
F12
External input EXTi!
F13
F50-F54
F60
PSU cover opened!
Internal supply fail!
No communication
PSU FLT
PSU FLT
PSU FLT
- service codes
- no communication with LCD panel
F61-F64
Control panel fail
PSU FLT
- service codes
F65
Access unlocked
- The output voltage of the PSU set too low ,
below 26V
- Battery charging circuit failure
- Output voltage below 23,6V
(during buffer operation)
- the battery voltage has dropped below 23V
(during battery-assisted operation)
- the battery voltage has dropped below 20V
(during battery-assisted operation)
- Activation of the input of collective failure
EXT IN
- passwords unlocked
Table 8. List of PSU message codes.
Message
Description
code
I00
Power supply start-up
I01
AC power back
I02
AUX fuse replaced
I03
BAT fuse replaced
I04
Battery OK
I05
Battery test – START
I06
PSU cover closed
Table 9. Optical indication of failure with the PSU LED on the PCB of the PSU.
The number of
flashes of the PSU
Failure
Failure description
LED on the PCB of
code
the power supply
1
F06
High AUX voltage!
2
F07
High battery voltage!
3
F08
Charge circuit fail!
4
F09
Low AUX voltage!
5
F50-F54 Internal supply fail!
F60
No communication
6
F13
PSU cover opened!
16
Additional
information
Section 5.9
Section 5.5
Section 6
Section 5.6
www.pulsar.pl
BLACK POWER
PSBEN2024B
5.3 PSU configuration.
The PSU is equipped with a configuration menu that allows to configure the settings by changing or the
activation of some of its parameters. The figure illustrating the configuration menu structure is shown below.
Fig. 7. The PSU configuration menu.
Table 10. Description of symbols.
Symbol
Additional
information
Description
Battery test – „tSt”
On – battery test on
OFF – battery test off
LED display dimmer
On – dimmer ON
OFF – dimmer OFF
Communication address – „Adr”
1÷ 247 power supply address required at
the time of communication with the computer
1 – factory setting
Transmission – „trS”
Determines the speed of communication
9.6k
:
115.2k (factory setting)
Parity of the transmission – „trP”
Determines the method of communication
8N2
8E1 (factory setting)
8O1
17
Sections 5.3.1
Sections 5.3.2
Sections 5.3.3
Sections 5.3.4
Sections 5.3.5
www.pulsar.pl
5.3.1
BLACK POWER
PSBEN2024B
Battery test ON/OFF „tSt”
The "tSt" function allows to enable or disable the test of the battery (Section 6.3) connected to the power
supply. When activated, the battery test occurs automatically if it is not blocked by the control system (section 6.3).
- simultaneously press the „<,>” rightmost and leftmost buttons on the LED panel
- the „tSt” parameter will be displayed
- press „OK”
- the current settings will be displayed
- use the „<” or „>” buttons to in order to set the status
On – battery test on
OFF – battery test off
- approve your choice with the ‘OK’ button
- in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons on the LED panel
Deactivating/activating the test with the STOP button on the PCB of the PSU.
During mains-powered PSU operation press the STOP button on the main board and hold it for 3 seconds.
The device will confirm the activation/deactivation:

testing off – the tOF sign appears on the display
, single beep

testing on – the tOn sign appears on the display
, double beep
Deactivating/activating the test is stored in the memory even after unplugging the device from
mains. The battery failure indication at the APS FLT output is automatically switched off. The
battery protection system against deep discharged remains on, though.
18
www.pulsar.pl
5.3.2
BLACK POWER
PSBEN2024B
LED Display Dimmer „dIS"
LED display dimmer allows to dim the display if no buttons are pressed within 5 minutes.If the display is
in the blackout mode, pressing any button will "reactivate" the display.
- simultaneously press the „<,>” rightmost and leftmost buttons on the LED panel
- the „tSt” parameter will be displayed
- use the „<” or „>” buttons to display the „dIS” parameter
- press „OK”
- the current status will be displayed
- use the „<” or „>” buttons in order to set the status
On – dimmer on
OFF – dimmer off
- confirm by pressing „OK”
- in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.3.3
Setting the communication address „Adr”
applies to cooperation with PowerSecurity.
All power supplies are factory-set to address 1.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
Communication address allows to identify power supply units in the same communication network.
- simultaneously press the „<,>” rightmost and leftmost buttons
- the „tSt” parameter will be displayed
- use the „<” or „>” buttons to display the „Adr” parameter
19
www.pulsar.pl
BLACK POWER
PSBEN2024B
- press „OK”
- the current address of the PSU will be displayed
- use the „<” or „>” buttons in order to set the address
1÷ 247 – address of the PSU during the communication with the computer
- confirm by pressing „OK”
- in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.3.4
Setting the transmission speed „trS”
applies to cooperation with PowerSecurity.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
The PSU has preset transmission parameters of 115200 baud 8E1. However, if it is connected to the
network with differently defined parameters, make the appropriate changes to its configuration.
- simultaneously press the „<,>” rightmost and leftmost buttons
- the „tSt” parameter will be displayed
- use the „<” or „>” buttons to display the „trS” parameter
- press „OK”
- the information about the transmission speed will be displayed
- use the „<” or „>” buttons in order to set the required transmission speed,
- 9.6k
:
- 115.2k (factory setting)
- confirm by pressing „OK”
- in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
20
www.pulsar.pl
5.3.5
BLACK POWER
PSBEN2024B
Setting the parity of the transmission “trP”
applies to cooperation with PowerSecurity.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
The PSU has preset transmission parameters of 115200 baud 8E1. However, if it is connected to the
network with differently defined parameters, make the appropriate changes to its configuration.
- simultaneously press the „<,>” rightmost and leftmost buttons
- the „tSt” parameter will be displayed
- use the „<” or „>” buttons to display the „trP” parameter
- press „OK”
- the information about the parity of the transmission will be displayed
on the panel
- use the „<” or „>” buttons in order to set the required communication mode,
- 8N2
- 8E1 (factory setting)
- 8O1
- confirm by pressing „OK”
- in order to return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.4 Acoustic indication.
Emergency situations are acoustically indicated. The frequency and the number of signals depend on an
event type (see chapter. 5.2.5). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]).
Table 11. Acoustic indication.
Description
No.
1
2
3
4
5
6
7
1 signal per 10s, battery-assisted
operation
1 signal per 10s, mains operation
2 signals per 10s, battery-assisted
operation
Fast signals, battery-assisted operation
Continuous indication
1 signal
2 signals
Event
No 230V AC supply
Battery fault, undercharged battery
Low level of battery charge
The PSU will be disconnected due to the battery discharge
PSU failure [see chapter. 5.2.5]
Breaking the battery test
Activation of the battery test
21
www.pulsar.pl
PSBEN2024B
BLACK POWER
5.5 Technical outputs.
The PSU feature indication outputs, with galvanic isolation, which change their state if any of the following
events occur:

EPS FLT - output indicating AC power loss.
The output indicates 230V AC power loss. Under normal status (with 230V supply on) the
output is closed. In case of power failure, the PSU will switch the output into the open position after a
time lag set by the T AC jumpers (J1, J2).
J1=
, J2=
time lag T= 5s
J1=
, J2=
time lag T= 140s
J1=
, J2=
time lag T= 17m
J1=
, J2=
time lag T= 2h 20m
Caption:
jumper on,
jumper off

APS FLT - output indicating battery failure.
The output indicates a failure in the battery circuit. Under normal status (during correct operation) the
output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be
triggered by the following events:
- a faulty or undercharged battery
- battery voltage below 23V during battery-assisted operation
- battery fuse failure
- no continuity in the battery circuit

PSU FLT - output indicating PSU failure.
The output indicates the PSU failure. Under normal status (during correct operation) the output is close.
In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the
following events:
- low output voltage Uaux<23,6V
- high output voltage Uaux>29,4V
- high battery voltage Uaku>28V (during battery test)
- polymer fuse PTC activation
- exceeding the PSU nominal current
- failure in the battery charging circuit
- activation of the over voltage protection OVP
- enclosure opening - TAMPER
- internal damage of the PSU
- EXT IN input activation
The technical outputs have been implemented with galvanic isolation between the PSU’s systems and the
attached devices.
Fig. 8. Electrical diagram of the technical outputs.
5.6 Input of collective failure EXT IN.
The EXT IN (external input) technical input indicating a collective failure is intended for additional, external
devices that generate the failure signal. The voltage at the EXT IN input will save information about an incident in
the internal memory of the power supply and sending the signal about the failure to the PSU FLT output.
The EXT IN technical input has been implemented with galvanic isolation between the PSU’s systems
and the devices attached.
Fig. 9. Electrical diagram of the EXT IN input.
22
www.pulsar.pl
PSBEN2024B
BLACK POWER
The electrical diagram below shows the way of connecting external devices to the EXT IN input. Outputs
such as: OC (open collector), relay may be used as a source of the signal.
Fig. 10. Examples of connections.
In the option with tamper switches, the VEXT jumper must be on. It polarizes the EXT IN input circuit
therefore is required in such configuration.
The EXT IN input has been adjusted to cooperate with fuse modules that generate a failure signal in case
of a fuse fault in any of output sections (e.g. AWZ535, AWZ536). To guarantee a correct cooperation between the
module and the EXT IN input, the VEXT jumper must be on and the connections are to be made accordingly to the
diagram below.
Fig. 11. Example of a connection with the fuse module: AWZ535 or AWZ536.
5.7 Enclosure Tamper Indication - TAMPER.
The PSU is fitted with the micro switch tamper indicating enclosure opening and detaching from the
mounting surface.
The tamper cable is not connected to the terminal in the factory settings. In order to activate tamper,
remove the jumper from tamper terminal (Fig. 2 [14]) and plug in the tamper cable.
Each opening the enclosure and detaching from the mounting surface will generate a failure signal at the
PSU FLT and ALARM technical outputs and will save the event in the internal memory of the PSU.
23
www.pulsar.pl
PSBEN2024B
BLACK POWER
5.8 Overvoltage protection of the PSU output OVP.
In case of voltage exceeding 31V±0.5V at the switching regulator’s output, the system cuts off the
power at the outputs to protect the battery and the receivers from damage. The outputs will be battery-powered.
The activation of the protection system is indicated by the OVP yellow LED on the PCB board, and the PSU FLT
output.
5.9 PSU overload.
The PSU is fitted with the LED OVL (overload) on the PCB and
indicator on the LED panel,
informing about output overload. If the nominal current of the PSU is exceeded, the led turns on and the
microprocessor starts a specially implemented procedure. Depending on time and overload level,
microprocessor may disconnect the AUX output and switch into the battery-assisted operation. Restart will occur
after 1 minute.
PSU overload is indicated by the PSU FLT technical output.
24
www.pulsar.pl
PSBEN2024B
BLACK POWER
6 Reserve power supply circuit.
The power supply is equipped with intelligent circuits: charging and battery control circuit, whose main task
is to monitor the condition of the battery and its connections in the circuit.
If the power supply driver detects a malfunction in the battery circuit, appropriate signaling and change in the
APS FLT technical output take place.
6.1 Running the PSU from the battery.
The PSU has been equipped with two buttons on the PCB board which enable running or disconnecting
the PSU during battery-assisted operation.
 Running the PSU from the battery: press the START button on the main board and hold for 1s.
 Disconnecting the PSU from the battery: press the STOP button on the main board and hold for 5s.
6.2 Deep discharge battery protection UVP.
The PSU is equipped with the disconnection system and the discharged battery indication. If the voltage at
the battery terminals drops below 20V±0.2V will turn on the beep sound and disconnect the battery in the 15
seconds.
Re-connecting the battery to the power supply occurs automatically upon the appearance of the 230V AC mains
voltage.
The protection mode is off when the PBAT jumper is removed.
Caution.
Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its
capability of storing energy, lowers its capacity and shortens its durability.
6.3 Battery test.
The PSU runs battery test every 5 minutes. During testing, the control unit of the PSU measures the
electrical parameters according to the implemented measuring method.
A negative result occurs when the battery circuit continuity is interrupted or if the terminal voltage drops
below 24V
The battery test can be activated manually (see section 5.3.1), from the menu of the power supply or by
pressing the STOP button, for example to test the replaced batteries.
The PSU is protected against too frequent performing of the battery test, which could result in
undercharging. The protection involves blocking the ability to perform test for 60 seconds from the last activation.
n such case, the LED will display the „- - -„ symbol.
Temporary lock of the battery test can be disabled by putting the J1 jumper between J2 on the power
supply board (Fig.2 [2]).
The battery test will also be automatically locked when the PSU is in the operating mode, in which the
battery test is impossible. Such condition occurs, for example, during battery assisted operation or when the power
supply is overloaded.
25
www.pulsar.pl
BLACK POWER
PSBEN2024B
6.4 Standby time.
Battery-assisted operating depends on battery capacity, charging level and load current. To maintain an
appropriate standby time, current drawn from the PSU in battery mode should be limited. Characteristics for a
2x7Ah/12V SLA:
Grade 1, 2 - standby time 12h
Output current 0,58A + 1,5A battery charge
Grade 3 - standby time 30h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – EN 50131-1).
Output current 0,23A + 1,5A battery charge
- standby time 60h if the faults of the main power source are reported to the Alarm Receiving
Centre - ARC (in accordance with 9.2 – EN 50131-1).
Output current 0,116A + 1,5A battery charge
6.5 Battery charging time.
The PSU has a battery circuit charged with direct current. The current selection is done with use of the IBAT
jumpers. The table below shows how long does it take to charge a (fully discharged) battery up to min. 80% of its
nominal capacity.
Table 12. Battery charging time.
2x7Ah battery charging time
up to the capacity of 0,8*C
4h12m
6h18m
10h30m
31h30m
Charging
current [A]
1,5
1
0,6
0,2
Configuration of
IBAT jumper
J1=
J1=
J1=
J1=
, J2=
, J2=
, J2=
, J2=
, J3=
J3=
J3=
J3=
6.6 Operation without a battery.
In case of an expected PSU operation without an attached battery, make a necessary configuration of the
jumpers:
In this mode, the automation system allows adjustments of PSU’s output voltage without indicating a failure
connected with battery operation.
CAUTION. During operation without battery assistance the PSU does not perform any parameter
control that monitors its proper operation. Therefore, this mode ought to be chosen thoughtfully.
26
www.pulsar.pl
PSBEN2024B
BLACK POWER
7. Remote monitoring (options: Wi-Fi, Ethernet, RS485, USB).
The PSU has been adjusted to operate in a system that requires a remote control of the parameters in a
monitoring centre. Transmitting data concerning PSU status is possible due to an additional, external
communication module responsible for communication in Wi-Fi, Ethernet or RS485 standard. The USB –TTL
interface enables the connection between the PSU and the computer.
Different connection topologies, presented later in this chapter, are only a part of possible communication
schemes. More examples can be found in the manuals dedicated to individual interfaces.
When installing optional features in the power supply unit, power supply current consumption, used
for the calculation of standby time, should be taken into account (see section. 6.4).
7.1 Communication via the USB-TTL interface.
The easiest way of communication between the PSU and the computer is provided by the USB-TTL "INTU”
interface. This interface allows direct connection between the computer and the PSU and is recognizable by the
operating system as a virtual COM port.
Fig. 12. USB-TTL communication using the USB-TTL „INTU” interface.
7.2 ETHERNET network communication.
Communication in the Ethernet network is possible due to the additional interfaces: Ethernet „INTE” and
RS485-ETH „INTRE”, according to the IEEE802.3 standard.
The Ethernet „INTE” interface features full galvanic isolation and protection against surges. It should be
mounted inside the enclosure of the PSU.
Fig. 13. Ethernet network communication using the Ethernet „INTE” interface.
27
www.pulsar.pl
PSBEN2024B
BLACK POWER
The RS485-WiFi „INTRE” interface is a device used to convert signals between the RS485 bus and the Wi-Fi
network. For proper operation, the unit requires an external power supply in the range of 10÷30V DC e.g. drawn
from a PSU of the PSBEN series. The unit is mounted in a hermetic enclosure protecting against adverse
environmental conditions.
Fig. 14. Ethernet network communication using the RS485 „INTRE” interface.
7.3 The Wi-Fi wireless communication.
The Wi-Fi wireless communication can be implemented on the basis of additional WI-Fi ‘INTW’
and RS485-WiFi interfaces, operating within 2,4GHz frequency band, according to the IEEE 802.11 bgn standard.
The Wi-Fi “INTW” interface shall be mounted in a selected location inside the enclosure so that the
antenna is exposed to the outside.
Fig. 15. The Wi-Fi communication using WI-FI „INTW” interface.
28
www.pulsar.pl
PSBEN2024B
BLACK POWER
The RS485-WiFi „INTRW” interface is a device used to convert signals between the RS485 bus and the
Wi-Fi network. For proper operation, the unit requires an external power supply in the range of 10÷30V DC e.g.
drawn from a PSU of the PSBEN series. The physical connection of the interface takes place under galvanic
isolation. The unit is mounted in a hermetic enclosure protecting against adverse environmental conditions.
Fig. 16. The Wi-Fi communication using the RS485-WIFI „INTRW” interface.
7.4 RS485 network communication.
Another type of network communication is the RS485 communication using two-wire transmission path. To
achieve this kind of data exchange, the PSU should be equipped with the additional RS485 TTL "INTR" interface,
converting data from the PSU into the RS485 standard and the USB-RS485 "INTUR" interface, converting data
from the RS485 network to the USB. Offered interfaces are galvanically isolated and protected against surges.
Fig. 17. RS485 communication using the „INTR” and „INTUR” interfaces.
29
www.pulsar.pl
PSBEN2024B
BLACK POWER
7.5 „PowerSecurity” program.
The ”Power Security” program is available at www.pulsar.pl
Its detailed description can be found in the manual.
„Power Security” is a free computer program for viewing and analyzing the information sent from the PSU
installation spots. The main panel is presented below.
Fig. 18. „Power security” main panel.
It is possible to divide the main panel of the program into smaller areas, depending on the number of
monitored power supplies.
The program is equipped with manager mode, which allows the grouping of power supplies for easier
analysis and orientation.
The application enables both the visualization and analysis of the received data. Exceeding of the
acceptable parameters is indicated by red illumination of the appropriate area or by blinking of the indicator light.
Individual tabs allow monitoring the power supply parameters on the chart and failure memory along with the
information about the status of technical outputs and electrical parameters.
30
www.pulsar.pl
PSBEN2024B
BLACK POWER
8. Technical parameters.
Electrical parameters (Table 13).
Mechanical parameters (Table 14).
Safety of use (Table 15).
Table 13. Electrical parameters.
PSU type
Mains supply
Current consumption
PSU’s power
Efficiency
Output voltage
Output current
Output voltage adjustment range
Ripple voltage
Current consumption by the PSU systems
during battery-assisted operation
Battery charging current
Low battery voltage indication
Surge protection
Over voltage protection OVP
Short circuit protection SCP
Overload protection OLP
Battery circuit protection SCP and reverse
polarity connection
Deep discharge battery protection UVP
Indication of opening the cover of the power
supply or detachment from the ground
Technical outputs:
- EPS FLT; output indicating AC power failure
- APS FLT; output indicating battery failure
- PSU FLT; output indicating PSU failure
EXT IN technical input
Optical indication:
Acoustic indication:
FBAT fuse
FMAIN fuse
A, protection class 1÷3, II environmental class
230V AC 50Hz (-15%/+10%)
0,45 A
61 W
81%
22 V÷ 27,6 V DC – buffer operation
20 V÷ 27,6 V DC – battery-assisted operation
- for grades 1, 2:
Io = 0,58A + 1,5A battery charging
- for grade 3:
Io = 0,23A + 1,5A battery charging - (connection with
ARC required, compliant with 9.2 – EN 50131-1)
Io = 0,116A + 1,5A battery charging
- for general use:
Io = 2A + 0,2A battery charging
Io = 1,6A + 0,6A battery charging
Io = 1,2A + 1A battery charging
Io = 0,7A + 1,5A battery charging
24 V÷ 29 V
60 mV p-p max.
I = 22 mA
0,2A/0,6A/1A/1,5A – IBAT jumper selectable
Ubat < 23V, during battery-assisted operation
varistors
U>31V, disconnection of the output voltage (AUX+
disconnection), automatic return
Electronic – current limitation and / or FBAT fuse failure in the
battery circuit (requires fuse replacement)
Automatic return
Program - equipment
F3,15 A- current limiting, FBAT fuse (failure requires fuseelement replacement)
U<20,0 V (± 2%) – disconnection (-BAT) of the battery,
configuration with jumper PBAT
Micro switch TAMPER
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
- time lag, approx. 5s/140s/17m/2h 20m (+/-5%)
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
- type – electronic, max 50mA/30V DC, galvanic isolation
1500VRMS
Voltage ’on’ – 10÷30V DC
Voltage ’off’ – 0÷2V DC
Level of galvanic isolation: 1500VRMS
- LEDs on the PSU’s PCB,
- LED panel
 output current readings
 output voltage readings
 failure codes with history
- piezoelectric indicator ~75dB /0,3m, switchable via jumper
F 3,15A / 250V
T 0,5A / 250V
31
www.pulsar.pl
BLACK POWER
PSBEN2024B
Additional accessories (not included)
- USB-TTL ‘INTU’ interface; USB-TTL communication
- RS485 ‘INTR’ interface: RS485 communication
- USB-RS485 ‘INTUR’ interface; USB-RS485 communication
- Ethernet ‘INTE’ interface; Ethernet communication
- WiFi “INTW’ interface; Wi-Fi wireless communication
- RS485-Ethernet “INTRE’ interface; RS485-Ethernet
communication
- RS485-WiFi “INTRW’ interface; RS485-WiFi wireless
communication:
Table 14. Mechanical parameters.
Enclosure dimensions
Mounting
Battery space
Net/gross weight
Enclosure
Closing
Terminals
Notes
330 x 350 x 108 (WxHxD) [mm] (+/- 2)
See Fig. 3
2x7Ah/12V (SLA) max.
195 x 160 x 95mm (WxHxD) max
H
W
D
5,5/5,9 kg
Steel plate DC01 1mm, color RAL 9005 (black)
Cheese head screw x2 (at the front), lock assembly possible
Supply: Φ0,63÷2,50 (AWG 22-10)
Outputs : Ф0,51÷2 (AWG 24-12), BAT battery outputs: 6,3F-2,5, 30cm
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Table 15. Safety of use.
Protection class EN 60950-1:2007
Protection grade EN 60529: 2002 (U)
Insulation electrical strength:
- between input (network) circuit and the output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
Insulation resistance:
- between input circuit and output or protection circuit
32
I (first)
IP20
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
100 MΩ, 500V/DC
www.pulsar.pl
PSBEN2024B
BLACK POWER
9. Technical inspections and maintenance.
Technical inspections and maintenance can be performed after disconnecting the power supply from the
power network. The PSU does not require any specific maintenance; however, its interior should be cleaned with
compressed air if it is used in dusty conditions. In case of fuse replacement, use only compatible replacement
parts.
Technical inspections should be carried out not less frequently than once per year. During the inspection,
check the batteries and run the battery test.
4 weeks after installation, re-tighten all screw connections, see Fig. 2 [9].
33
www.pulsar.pl
PSBEN2024B
BLACK POWER
WEEE LABEL
According to the European Union WEEE Directive, waste electrical and electronic equipment should
be disposed of separately from normal household waste. Waste electrical and electronic equipment
must not be disposed of with normal household waste.
CAUTION! The power supply unit is adapted for cooperation with the sealed lead-acid batteries (SLA). After the operation
period they must not be thrown but recycled according to the applicable law
GENERAL WARRANTY CONDITIONS
1. Pulsar (manufacturer) grants a five-year quality warranty for the equipment, starting from the production date.
2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (selected by the manufacturer) if
the malfunction is due to the manufacturer. It includes manufacturing or material defects, provided that such defects have been
reported within the warranty period (point.1).
3. The equipment subjected to warranty should be brought to the place of purchase or directly to the main office of the
manufacturer.
4. The warranty applies to complete equipment, accompanied by a properly filled warranty claim with a description of the defect.
5. Should the claim be accepted, the manufacturer is obliged to provide warranty repairs, at the earliest convenience, however not
later that within 14 days from the delivery to the service centre of the manufacturer.
6. The repair period mentioned in point 5 may be prolonged, if there are no technical possibilities to carry out the repairs, or if the
equipment has been conditionally accepted, due to the breaking warranty terms by the claimant.
7. All the services are carried out at the service centre of the manufacturer, exclusively.
8. The warranty does not cover the defects of the equipment, resulting from:
- reasons beyond the manufacturer's control,
- mechanical damage,
- improper storage and transport,
- use that violates the operation manual or equipment’s intended use,
- fortuitous events, including lightning discharges, power failures, fire, flood, high temperatures and chemical agents,
- improper installation and configuration (failure to follow instruction).
9. The warranty is void in case of construction changes and repairs carried out by any unauthorized service center or in case of
damage or modifications to warranty stickers and serial numbers.
10. The liability of the manufacturer towards the buyer is limited to the value of the equipment determined according to the
wholesale prices suggested by the manufacturer on the day of purchase.
11. The manufacturer takes no responsibility for the defects that result from the damaging, malfunctioning or inability to operate
the equipment especially when resulting from failure to comply with the recommendations and requirements contained in the
manual.
Pulsar
Siedlec 150, 32-744 Łapczyca, Poland
Phone (+48) 14-610-19-40, Fax (+48) 14-610-19-50
E-mail: [email protected], [email protected]
http:// www.pulsar.pl, www.zasilacze.pl
34

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement