- No category
advertisement
DEEP SEA ELECTRONICS PLC
704 AUTOMATIC MAINS FAILURE MODULE
OPERATING INSTRUCTIONS
Author:- John Ruddock
Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
England
Tel: +44 (0) 1723 890099
Fax: +44 (0) 1723 893303 email: [email protected]
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 1 -
<< This page is intentionally blank >>
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 2 -
TABLE OF CONTENTS
1 DESCRIPTION OF OPERATION .......................................................... 4
1.1 MANUAL MODE OPERATION.........................................................................4
1.2 AUTOMATIC MODE OF OPERATION.............................................................5
2 CONFIGURATION INSTRUCTIONS..................................................... 7
3 CONFIGURATION TABLES ................................................................. 8
4 TERMINAL DESCRIPTION................................................................. 12
5 SPECIFICATION ................................................................................. 13
6 SOLID STATE OUTPUTS................................................................... 14
8 TYPICAL CONNECTIONS.................................................................. 15
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 3 -
1 DESCRIPTION OF OPERATION
MODE
To initiate a start sequence in MANUAL, press the pushbutton, and the start sequence is initiated.
NOTE:- There is no Start Delay in this mode of operation.
If the pre-heat output option is selected this timer is then initiated, and the auxiliary output selected is energised.
After the above delay the Fuel Solenoid is energised, then the Starter Motor is engaged.
The engine is cranked for a 10 second period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for a 10 second period. Should this sequence continue beyond the 3 starting attempts, the start sequence will be terminated and Fail to Start will be illuminated. fault
When the engine fires, the starter motor is disengaged and locked out at 20 Hz measured from the
Alternator output. Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the Safety On timer is activated (which is fixed at 12 seconds), allowing Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
Once the engine is running, the Warm Up timer, if selected, is initiated, allowing the engine to stabilise before it can be loaded.
The generator will run off load, unless the mains supply fails or a Remote Start on load signal is applied, at which point the load will be transferred to the generator.
The generator will continue to run On load regardless of the state of the mains supply or remote start input until the Auto mode is selected.
If Auto mode is selected, and the mains supply is healthy with the remote start on load signal not active, then the Remote Stop Delay Timer begins, after which, the load is disconnected. The generator will then run off load allowing the engine a cooling down period.
Selecting STOP de-energises the FUEL SOLENOID, bringing the generator to a stop.
NOTE:- The safety on time (used for delayed alarms) is pre set to 12 seconds and can not be changed.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 4 -
1.2 AUTOMATIC MODE OF OPERATION
This mode is activated by pressing the confirms this action.
pushbutton. An LED indicator beside the button
Whether the start sequence is initiated by mains (utility) failure or by remote start input, the following sequence is followed:
To allow for short term mains supply transient conditions or false remote start signals, the Start
Delay timer is initiated. After this delay, if the pre-heat output option is selected then the pre-heat timer is initiated, and the corresponding auxiliary output (if configured) will energise.
NOTE:- If the mains supply returns within limits, (or the Remote Start signal is removed if the start sequence was initiated by remote start) during the Start Delay timer, the unit will return to a stand-by state.
After the above delays the Fuel Solenoid is energised, then one second later, the Starter Motor is engaged.
The engine is cranked for a 10 second period. If the engine fails to fire during this cranking attempt then the starter motor is disengaged for a 10 second rest period. Should this sequence continue beyond the 3 starting attempts, the start sequence will be terminated and
Fail to Start fault will be illuminated.
When the engine fires, the starter motor is disengaged and locked out at 20 Hz measured from the
Alternator output. Rising oil pressure can also be used to disconnect the starter motor, however it cannot be used for underspeed or overspeed detection.
After the starter motor has disengaged, the Safety On timer is activated, allowing Oil Pressure,
High Engine Temperature, Under-speed, Charge Fail and any delayed Auxiliary fault inputs to stabilise without triggering the fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing the engine to stabilise before accepting the load.
If the remote start is being used and has been configured to Remote start is on load, or the mains has failed, the load will be transferred to the generator.
On the return of the mains supply, (or removal of the Remote Start signal if the set was started by remote signal), the Stop delay timer is initiated. Once it has timed out, the load is transferred back to the mains (utility). The Cooling timer is then initiated, allowing the engine a cooling down period off load before shutting down. Once the Cooling timer expires the Fuel Solenoid is de-energised, bringing the generator to a stop.
If the mains should fail (or a Remote Start signal is re-activated) whilst the generator is Cooling down, the load will be immediately transferred to the generator.
Should the mains supply fall outside limits again (or the Remote Start signal be re-activated) during the cooling down period, the set will return on load.
NOTE:- The safety on time (used for delayed alarms) is pre set to 12 seconds and can not be changed.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 5 -
1.3 WARNINGS
Warnings are used to warn the operator of an impending fault
BATTERY CHARGE FAILURE, if the module does not detect a voltage from the warning light terminal on the auxiliary charge alternator, the icon will illuminate. (Either 8 Volts or 16 Volts depending on the configuration of Nominal DC Voltage).
Inputs 1 and 2 can be configured as warnings or shutdowns. The relevant icon will be illuminated when the input is active
1.4 SHUTDOWNS
Shutdowns are latching and stop the Generator. The alarm must be cleared, and the fault removed to reset the module. In the event of a shutdown the appropriate icon will be illuminated
NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains it will not be possible to reset the unit (The exception to this is the
Low Oil Pressure alarm and similar ‘delayed alarms’, as the oil pressure will be low with the engine at rest). Any subsequent warnings or shutdowns that occur will be displayed steady, therefore only the first-up shutdown will appear flashing.
NOTE:- The safety on time (used for delayed alarms) is pre set to 12 seconds and can not be changed.
FAIL TO START, if the engine does not fire after the pre-set 3 attempts at starting, a shutdown will be initiated.
The icon will illuminate.
LOW OIL PRESSURE, if the module detects that the engine oil pressure has fallen below the low oil pressure switch after the Safety On timer has expired, a shutdown will occur.
The icon will illuminate.
HIGH ENGINE TEMPERATURE if the module detects that the engine coolant temperature has exceeded the high engine temperature switch after the Safety On timer has expired, a shutdown will occur.
The icon will illuminate.
OVERSPEED, if the engine speed exceeds the pre-set trip (14% above the nominal frequency) a shutdown is initiated. Overspeed is not delayed, it is an immediate shutdown.
The icon will illuminate.
NOTE:- During the start-up sequence the overspeed trip level is extended to 24% above the normal frequency for the duration of the saftey timer to allow an extra trip level margin. This is used to prevent nuisance tripping on start-up.
UNDERSPEED, if the engine speed falls below the pre-set trip (20% of the nominal frequency) after the Safety On timer has expired, a shutdown is initiated.
The icon will illuminate.
Inputs 1 and 2 can be configured as warnings or shutdowns. The relevant icon will be illuminated when the input is active
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 6 -
♦ With the unit in Stop
mode, Configuration Mode is selected by operation of a small switch on the rear, left-hand edge of the PCB. This is partially hidden to prevent accidental operation.
Normal
Configuration
Configuration Mode is selected, the ‘Auto’ LED will commence rapid flashing, and all normal operation is suspended.
♦ The Stop
pushbutton can be used to select the LED ‘code’ that corresponds to the required function. The 5 left-hand LED’s will form the code. See configuration table over leaf.
♦ The
pushbutton will allow the user to change the associated value. The 3 righthand LED’s inform the user of the current setting for the chosen function. See configuration table over leaf.
♦ When the required parameters are displayed, pressing the Auto
button will save the new setting, and the process is repeated for each function change.
♦ When configuration is complete, the Configuration Mode Selector Switch should be returned to the ‘Normal’ position.
Parameter Value
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 7 -
3 CONFIGURATION
FUNCTIONS AND CONFIGURATION TABLE
Function
Pre-heat Timer { { { { O {
{
{
{
O
O
O
O
! 1
{
{
O
O
{
{
O
O
! 2
{
O
{
O
{
O
{
O
Value (Default in Bold)
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Used to pre-heat the engine prior to cranking. The output is active for the duration of the setting, prior to cranking.
Start Delay
{ { { O { {
{
{
{
O
O
O
O
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Used to give a delay between activating the remote start input, or a mains failure, and actually starting the engine.
Stop Delay
Mains Return Delay
{ { { O O {
{
{
{
O
O
O
O
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Used to give a delay between the mains returning and the system switching the load back to the mains. Used to ensure that the mains is steady before this action is executed.
Energise to Stop
Hold Timer
{ { O { {
{
{
{
{
O
O
O
O
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Used for the control of the engine stop solenoid. When the engine is to be stopped, the Energise To Stop output becomes active, closing the stop solenoid (fuel valve). When the engine comes to rest, the stop solenoid will remain energised for the period of the Energise To Stop Timer, to ensure the engine has come to a complete stop.
Warm-up Timer { { O { O
O
O
O
O
{
{
{
{
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Delay between the engine being available for use, and the closure of the generator load-switching device to allow time for the engine to warm before being loaded. This occurs after the 12 second safety on timer.
Cooling Timer { { O O {
O
O
O
O
{
{
{
{
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
0 Seconds
5 Seconds
10 Seconds
15 Seconds
20 Seconds
30 Seconds
60 Seconds
180 Seconds
Delay between opening the generator load-switching device and stopping the engine to allow time for the engine to cool down before being stopped. This is particularly useful when used in conjunction with turbo-charged engines.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 8 -
FUNCTIONS AND CONFIGURATION TABLE
Function
Nominal Frequency { O { { {
{
{
! 1
{
{
! 2
Value (Default in Bold)
{
50 Hz (O/S +14% /
Overshoot +24%)
O
60 Hz (O/S +14% /
Overshoot +24%)
The systems nominal frequency. Either 50 Hz or 60 Hz
Nominal DC Voltage
{ O { { O {
{
{
{
{
O
12V DC (CF 8V)
24V DC (CF 16V)
The generator battery voltage. Either 12 Volts or 24 Volts. It is used for the charge alternator failure level.
LOP Switch Contact
{ O { O { {
{
{
{
{
O
Close on Fault
Open on Fault
Configuration for the oil pressure switch. Either to close to battery negative on a fault, or open on a fault.
HET Switch Contact
{ O { O O
{
{
{
{
{
O
Close on Fault
Open on Fault
Configuration for the coolant temperature switch. Either to close to battery negative on a fault, or open on a fault.
Crank disconnect on
Oil Pressure
{ O O { {
{
{
{
{
{
O
Disabled
Enabled (2 Second
Delay)
If this is enabled, the starter motor will disconnect 2 seconds after the oil pressure switch detects oil pressure.
NOTE:-
Not suitable for all generators, due to the different monitoring points on lubrication systems.
Underspeed
Detection
{ O O { O {
{
{
{
{
O
Disabled
Enabled (U/S –20%)
If this is enabled, the unit will shut down the generator if the frequency falls below 20% of the nominal frequency.
Remote start function
{ O O O { {
{
{
{
{
O
Remote start
Simulated mains
Programmable input can be configured to one of the following.
♦
Remote start – If the input is active the generator will be started, and stopped if the input is deactive. Mains fail is allways active.
♦
Simulated mains – If the input is active the generator will not start in the event of a mains failure. E.G. if the generator is supporting a non 24 hour operation, a 24 hour timer can be used to prevent a mains failure from starting the generator and taking load.
Remote start on load
(ignore if simulated mains)
{ O O O O
{
{
{
{
{
O
Remote start is off load
Remote start is on load
The remote start input can be configured to one of the following.
♦
Remote start is off load – The generator will start and run off load when the remote start input is active.
♦
Remote start is on load – The generator will start, and the load transferred to the generator when the remote start is active.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 9 -
FUNCTIONS AND CONFIGURATION TABLE
Function
Auxiliary Input 1
Function
O { { { {
{
{
{
{
O
O
O
O
! 1
{
{
O
O
{
{
O
O
! 2
Value (Default in Bold)
{
Immediate Warning
Close on Fault
O
Immediate Warning
Open on Fault
{
O
{
O
Immediate Shutdown
Close on Fault
Immediate Shutdown
Open on Fault
Delayed Warning
Close on Fault
Delayed Warning
Open on Fault
{
O
Delayed Shutdown
Close on Fault
Delayed Shutdown
Open on Fault
Programmable input, can be configured to on of the following
♦
Immediate warning close on fault – If the input is activated at any time the unit will alarm and energise the common warning and common alarm output.
♦
Immediate warning open on fault – If the input is deactivated at any time the unit will alarm and energise the common warning and common alarm output.
♦
Immediate shutdown close on fault – If the input is activated at any time the generator will be shutdown and energise the common warning and common shutdown output. The generator can not be started.
♦
Immediate shutdown open on fault – If the input is deactivated at any time the generator will be shutdown and energise the common warning and common shutdown output. The generator can not be started.
♦
Delayed warning close on fault – If the input is activated and the saftey time has elapsed the unit will alarm and energise the common warning and common alarm output.
♦
Delayed warning open on fault – If the input is deactivated and the saftey time has elapsed the unit will alarm and energise the common warning and common alarm output.
♦
Delayed shutdown close on fault – If the input is activated and the saftey time has elapsed the generator will be shutdown and energise the common warning and common shutdown output.
♦
Delayed shutdown open on fault – If the input is deactivated and the saftey time has elapsed the generator will be shutdown and energise the common warning and common shutdown output.
Auxiliary Input 2
Function
O { { { O
{
{
{
{
O
O
O
O
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
Immediate Warning
Close on Fault
Immediate Warning
Open on Fault
Immediate Shutdown
Close on Fault
Immediate Shutdown
Open on Fault
Delayed Warning
Close on Fault
Delayed Warning
Open on Fault
Delayed Shutdown
Close on Fault
Delayed Shutdown
Open on Fault
Programmable input, can be configured to on of the following
♦
Immediate warning close on fault – If the input is activated at any time the unit will alarm and energise the common warning and common alarm output.
♦
Immediate warning open on fault – If the input is deactivated at any time the unit will alarm and energise the common warning and common alarm output.
♦
Immediate shutdown close on fault – If the input is activated at any time the generator will be shutdown and energise the common warning and common shutdown output. The generator can not be started.
♦
Immediate shutdown open on fault – If the input is deactivated at any time the generator will be shutdown and energise the common warning and common shutdown output. The generator can not be started.
♦
Delayed warning close on fault – If the input is activated and the saftey time has elapsed the unit will alarm and energise the common warning and common alarm output.
♦
Delayed warning open on fault – If the input is deactivated and the saftey time has elapsed the unit will alarm and energise the common warning and common alarm output.
♦
Delayed shutdown close on fault – If the input is activated and the saftey time has elapsed the generator will be shutdown and energise the common warning and common shutdown output.
♦
Delayed shutdown open on fault – If the input is deactivated and the saftey time has elapsed the generator will be shutdown and energise the common warning and common shutdown output.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 10 -
FUNCTIONS AND CONFIGURATION TABLE
Function
Auxiliary Output 1
Function
O { { O {
{
{
{
{
O
O
O
O
! 1
{
{
O
O
{
{
O
O
! 2
Value (Default in Bold)
{
Not used
O
{
Pre-heat
Engine Running
O
{
O
{
O
Common Warning
Common Shutdown
System in Auto
Common Alarm
Energise to Stop
Programmable output can be configured to one of the following.
♦
Pre-heat. - The output is energised for the period of pre-heat time prior to cranking, and between the cranking attempts.
♦
Engine Running. - The output is active after the saftey timer has elapsed.
♦
Common warning. - The output is active if there are any warning alarm active.
♦
Common shutdown - The output is active if there are any shutdown alarms active.
♦
System in auto. - The output is active when the system is in automatic mode.
♦
Common Alarm. - The output is active if there is any alarm condition.
♦
Energise to stop. - The output is energised when the engine is required to stop (normal or fault conditions), and will remain energised for the period of the Energise To Stop Timer, to ensure the engine has come to a complete stop.
Auxiliary Output 2
Function
O { { O O
{
{
{
{
O
O
O
O
{
{
O
O
{
{
O
O
{
O
{
O
{
O
{
O
Not used
Pre-heat
Engine Running
Common Warning
Common Shutdown
System in Auto
Common Alarm
Energise to Stop
Programmable output can be configured to one of the following.
♦
Pre-heat. - The output is energised for the period of pre-heat time prior to cranking, and between the cranking attempts.
♦
Engine Running. - The output is active after the saftey timer has elapsed.
♦
Common warning. - The output is active if there are any warning alarm active.
♦
Common shutdown - The output is active if there are any shutdown alarms active.
♦
System in auto. - The output is active when the system is in automatic mode.
♦
Common Alarm. - The output is active if there is any alarm condition.
♦
Energise to stop. - The output is energised when the engine is required to stop (normal or fault conditions), and will remain energised for the period of the Energise To Stop Timer, to ensure the engine has come to a complete stop.
O { O { {
{ { {
Mains Under
Voltage
(Trip / Return)
{
{
{
O
O
O
O
{
O
O
{
{
O
O
O
{
O
{
O
{
O
60V / 70V
70V / 80V
80V / 90V
90V / 100V
120V / 140V
140V / 160V
160V / 180V
180V /200V
If for example 180/200 is selected the generator will be started and the load transferred if any phase falls below 180V with respect to the neutral for the duration of the delay start timer. The load will be transferred back to mains when the mains voltage returns to 200V or higher for the duration of the mains return timer. (The system must be in Auto)
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 11 -
4 TERMINAL DESCRIPTION
PIN
No
DESCRIPTION
1
DC Plant Supply Input
(-ve)
2
DC Plant Supply Input
(+ve)
3
Fuel relay Output
4
Start relay Output
5
Auxiliary Output relay 1
6
Auxiliary Output relay 2
7
Charge Fail Input/ Excitation
Output
8
Low Oil Pressure Input
9
High Engine Temp Input
10
Auxiliary Input 1
11
Auxiliary Input 2
12
Remote Start Input
13
Mains loading Relay
Normally Open contact
14
Generator loading Relay
Normally Open contact
15
Functional Earth
16
Mains L1
Voltage Monitoring Input
17
Mains L2
Voltage Monitoring Input
18
Mains L3
Voltage Monitoring Input
19
Mains N
Voltage Monitoring Input
20
Alternator Input L1
21
Alternator Input N
CABLE
SIZE
NOTES
1.0mm
Connected to plant battery negative
1.0mm
Connected to plant battery positive
(Recommended Fuse 2A)
1.0mm
Used to operate the fuel relay.
1.0mm
Used to operate the cranking relay.
1.0mm
Configurable output.
1.0mm
Configurable output.
1.0mm
Must NOT be connected to plant supply negative if not used.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
0.5mm
Switch to negative.
1.0mm
Used to close the mains contactor / breaker
1.0mm
Used to close the generator contactor / breaker
1.0mm
Connect to a good clean earth point
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains L1 supply (AC)
(Recommend 2A Fuse Max.)
1.0mm
Connect to Mains N supply (AC)
1.0mm
Do not connect if not used. (2A Fuse)
1.0mm
Do not connect if not used.
NOTE:- For single phase mains monitoring the neutral should be connected to terminal
19, L1 should be connected to terminals 16,17 and 18.
NOTE:- For two phase mains monitoring the L2 should be connected to terminal 19, L1 should be connected to terminals 16,17 and 18. The voltage between the two phases must
not exceed 305 Volts.
NOTE:- All the outputs are solid state, rated at 1.2 Amps 8 Volts to 35 Volts DC, and switch to battery negative when active.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 12 -
5 SPECIFICATION
DC Supply: 8 Volts to 35 Volts DC Continuous.
Cranking Dropouts: Able to survive 0 Volts for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 Volts.
This is achieved without the need for internal batteries.
Max. Current: Operating 50mA
Standby 10mA
Alternator Input Range: 75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%)
Mains Input Voltage 15 – 277 Volts (ph-N) AC (+20%)
Alternator Input Frequency: 50 - 60 Hz at rated engine speed
(Minimum: 75V AC Ph-N)
(Crank Disconnect from 15V Ph-N @ 20Hz)
Overspeed +14% (+24% overshoot)
Underspeed –20%
Mains Frequency 50 – 60 Hz
Start Output: 1.2 Amp DC at supply voltage.
Fuel Output: 1.2 Amp DC at supply voltage.
Auxiliary Outputs: 1.2 Amp DC at supply voltage.
Dimensions: 125mm x 165mm x 28 mm
Charge Fail: 12 Volts = 8 Volts CF 24 Volts = 16 Volts CF
Operating Temperature Range: -30 °C to + 70
Applicable Standards
0
C
Compliant with BS EN 60950 Low Voltage Directive
Compliant with BS EN 50081-2: 1992 EMC Directive
Compliant with BS EN 61000-6-4: 2000 EMC Directive
Compliance to European Legislation
Registered Component for USA & Canada
Deep Sea Electronics plc reserve the right to change specification without notice.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 13 -
6 SOLID STATE OUTPUTS
DSE’s utilisation of Solid State Outputs gives many advantages, the main points being:
♦ No Moving Parts
♦ Fully Overload / Short Circuit Protected.
♦ Smaller dimensions hence lighter, thinner and cheaper than conventional relays.
♦ Less power required making them far more reliable.
The main difference from conventional outputs is that solid state outputs switch to negative (–ve) when active. This type of output is normally used with an automotive or plug in relay.
TYPICAL CONNECTIONS
Solid state output from DSE module
Fuel Solenoid (+ terminal) eg. Terminal 3 of 703/4 - FUEL
* Observe polarity when using relays fitted with integral diodes!
A
*
B
D
C
Battery positive (+)
A
B
C
D
Solid State Output Automotive 8 Pin Plugin relay Function from DSE Module Pin relay Pin
7 Fuel
85
30
87
2
1
3
To Positive supply via fuse
To Positive supply via fuse
To Fuel Solenoid
Example of relay pins connected to DSE solid state output to drive a fuel solenoid.
See overleaf for overall typical wiring diagram
NOTE:- The Close Mains Relay should be NORMALLY CLOSED when de-energised for fail safe reasons. Should the DC supply fail the mains will always be available. The output from the
DSE solid state output when energised will OPEN the relay therefore isolating the mains supply.
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 14 -
7 DIMENSIONS
Dimensions:
165mm x 125mm x 29mm
(6.5” x 4.9” x 1.2”)
Panel cutout:
149mm x 109mm
(5.9” x 4.3”)
Mounting Method:
4 x 4.2mm diameter holes suitable for M4 screws.
1 2
21 20
Fuel output
SSO
3
CONNECTIONS
Mechanical Interlock
Load
L1
N
L3
Alternator Output
L2
F 2A
Mains / Utility supply
L3
L2
L1
Electrical Interlock
G M
NOTE
*
Normally closed Normally open
+
Close gen relay
14
SSO
Close Gen output
* Close mains relay must be normally closed to ensure fail safe operation
Close mains relay
+
13
SSO
16 17 18 19
Close mains output
FUSES 2A
N
Start output
SSO
4
Auxiliary Outputs
SSO SSO
5 6 7 8
SSO = Solid state outputs
= External 'Automotive' or 'Plug-in' type relays
9
Auxiliary Alarm
Inputs
10 11
12
15
F2A F
+
Battery
Fuel
+
Starter motor
Crank
+
+ +
Charge alt
Terminals suitable for 22-16 awg (0.6mm
2
Tightening Torque = 0.8N-m (7lb-in)
-1.3mm
2
)field wiring
704 Operating Instructions Issue Issue 2 07/05/2003 3:50 PM JR - 15 -
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project