Honeywell Process Studio User Guide
โฆษณา
โฆษณา
Uniformance
Process Studio
User Guide
Copyright, Notices, and Trademarks
© Honeywell International Inc. 2008. All Rights Reserved.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Honeywell, Experion, PlantScape, TotalPlant, Uniformance PHD, and Business FLEX are U.S. registered trademarks of Honeywell International Inc.
Other brand or product names are trademarks of their respective owners.
Release Information
Uniformance Process Studio Release: 220.1
Document Revision: 2
Document Revision Date: June 27, 2008
Document Number: pim5001
Document Revisions:
Rev PAR
2 n/a
2
Added an index.
1-91RFYY Provided definition of 'Enable performance optimization' property that is available in
Desktop Configuration >Application Defaults.
2 1-9GK85B Added an attention box: Enabling the Marker styles degrades Trend performance.
Honeywell Process Solutions
2500 W. Union Hills Drive
Phoenix, Arizona 85027 USA
ii Uniformance - Process Studio User Guide
Support and Other Contacts
United States and Canada
Contact: Honeywell Solution Support Center
Phone: 1-800 822-7673. In Arizona: 602- 313-5558
Calls are answered by dispatcher between 6:00 A.M. and 4:00 P.M.
Mountain Standard Time. Emergency calls outside normal working hours are received by an answering service and returned within one hour.
Facsimile: (602) 313-3293
Mail: Honeywell TAC, MS P13
2500 West Union Hills Drive
Phoenix, AZ, 85027
Europe
Contact:
Phone:
Honeywell TAC-EMEA
+32-2-728-2732
Facsimile: +32-2-728-2696
Mail: TAC-BE02
Hermes Plaza
Hermeslaan, 1H
B-1831 Diegem, Belgium
Pacific
Contact:
Phone:
Honeywell Global TAC – Pacific
1300-300-4822 (toll free within Australia)
+61-8-9362-9559 (outside Australia)
Facsimile: +61-8-9362-9564
Mail: Honeywell Limited Australia
Email:
5 Kitchener Way
Burswood 6100, Western Australia
India
Contact: Honeywell Global TAC – India
Phone: +91-20- 66039400
Facsimile: +91-20- 66039800
Mail: Honeywell Automation India Ltd.
56 and 57, Hadapsar Industrial Estate
Email:
Hadapsar, Pune –411 013, India
Uniformance - Process Studio User Guide iii
Support and Other Contacts
Korea
Contact:
Phone:
Honeywell Global TAC – Korea
+82-2-799-6317
+82-11-9227-6324
Facsimile: +82-2-792-9015
Mail:
Email:
Honeywell Co., Ltd
17F, Kikje Center B/D,
191, Hangangro-2Ga
Yongsan-gu, Seoul, 140-702, Korea
People’s Republic of China
Contact:
Phone:
Mail:
Email:
Honeywell Global TAC – China
+86- 21-52574568
Honeywell (China) Co., Ltd
33/F, Tower A, City Center, 100 Zunyi Rd.
Shanghai 200051, People’s Republic of China
Singapore
Contact:
Phone:
Global TAC – South East Asia
+65-6580-3500
Facsimile: +65-6580-3501
+65-6445-3033
Mail: Honeywell Private Limited
Honeywell Building
Email:
17, Changi Business Park Central 1
Singapore 486073
Taiwan
Contact:
Phone:
Global TAC – Taiwan
+886- 7- 536 2567
Facsimile: +886-7-536 2039
Mail: Honeywell Taiwan Ltd.
Email:
17F-1, No. 260, Jhongshan 2nd Road.
Cianjhen District
Kaohsiung, Taiwan, ROC
[email protected] iv Uniformance - Process Studio User Guide
Support and Other Contacts
Japan
Contact:
Phone:
Global TAC – Japan
+81-3-6730-7160
Facsimile: +81-3-6730-7228
Mail:
Email:
Honeywell Japan Inc.
New Pier Takeshiba, South Tower Building,
20th Floor, 1-16-1 Kaigan, Minato-ku,
Tokyo 105-0022, Japan
Elsewhere
Call your nearest Honeywell office.
World Wide Web
Honeywell Solution Support Online: http://www.honeywell.com/ps
Training Classes
Honeywell Automation College: http://www.automationcollege.com
Uniformance - Process Studio User Guide v
Support and Other Contacts vi Uniformance - Process Studio User Guide
Contents
1.
2.
Getting Started With Uniformance Process Studio ....................................... 13
1.1
Opening Uniformance Process Studio ................................................... 13
1.2
Introducing the Browser .......................................................................... 14
Overview of the Browser ...................................................................... 14
To connect to a data source ................................................................ 14
Entering usernames and passwords ................................................... 15
Handling an unsuccessful connection to a data source ...................... 16
Description of the browse structure for a PHD server ......................... 16
Applying filters and search criteria ....................................................... 17
Organizing tags/items into customized folders .................................... 17
Configuring a browse limit .................................................................... 17
1.3
To open a window to display process data ............................................ 18
1.4
Introducing the time control .................................................................... 19
Overview of the time control ................................................................ 19
What is "Current time"? ........................................................................ 19
Description of data refresh ................................................................... 20
To step forward and backward in time ................................................. 21
To automatically scroll data forward .................................................... 21
To use separate time settings for each window ................................... 22
To synchronize windows to the same time settings (Common Times) 22
1.5
Displaying data in Uniformance Process Studio .................................... 24
Displaying Data in a Trend ............................................................................... 25
2.1
Choosing a Trend format ........................................................................ 25
Single Y Axis (default) format .............................................................. 25
Strip Chart format ................................................................................. 25
Multiple Y Axis format .......................................................................... 26
XY format ............................................................................................. 27
Histogram format.................................................................................. 28
2.2
Interpreting the histogram ....................................................................... 29
2.3
Creating a Trend ..................................................................................... 31
To create a new trend window ............................................................. 31
To add tags/items................................................................................. 31
To replace a tag/item ........................................................................... 31
Uniformance - Process Studio User Guide vii
Contents
To delete a tag/item .............................................................................. 32
To save a trend for reuse ..................................................................... 32
2.4
Using direct entry to add tags/items ........................................................ 33
2.5
Working with time ranges ........................................................................ 35
To save a time range for reuse ............................................................ 35
To reuse a saved time range ................................................................ 35
To trend different time ranges in the same window ............................. 35
2.6
Viewing trend data value at hairline cursor position ............................... 36
Overview of hairline cursors ................................................................. 36
To view data value at a specific time/date ............................................ 36
To view data value at two different times ............................................. 38
To view statistics (min, max, mean, and SD) at hairline position ......... 39
2.7
Using the zoom ....................................................................................... 40
2.8
Adding annotations ................................................................................. 41
2.9
Changing the visual properties of a Trend .............................................. 41
To show/hide the properties table ........................................................ 41
To show X axis on top or bottom .......................................................... 41
To change style of trace line................................................................. 41
To change style of marker for indication of data points ........................ 42
To change color of trace line ................................................................ 42
To show Step instead of linear trace line ............................................. 42
To show a grid ...................................................................................... 42
To show/edit title ................................................................................... 42
2.10
Viewing and changing the scale of a Trend ............................................ 43
To view the scale of a trace .................................................................. 43
To change the scale ............................................................................. 43
To lock the range of the Y axis (Lock Scale) ........................................ 43
2.11
Description of data retrieval properties 'Frequency' and 'Method' .......... 44
3.
Displaying Data in a Multi-Trend ...................................................................... 47
3.1
Overview of MultiTrend features ............................................................. 47
3.2
To create a new MultiTrend .................................................................... 48
3.3
To save all MultiTrend charts or a single chart for reuse ........................ 49
3.4
To view the MultiTrend properties ........................................................... 49
3.5
To view a MultiTrend chart in a Trend window ....................................... 49
3.6
To display hairline cursors in a MultiTrend ............................................. 49 viii Uniformance - Process Studio User Guide
Contents
4.
5.
6.
Displaying Data in a Table ................................................................................ 51
4.1
Overview of Table features ..................................................................... 51
4.2
To create a table ..................................................................................... 52
4.3
To save a table to a workspace .............................................................. 52
4.4
To filter table data ................................................................................... 53
To delete a condition from a custom filter ............................................ 54
4.5
To perform manual input/edit of PHD data in a table ............................. 55
4.6
Viewing PHD tag/item configuration in a table ....................................... 56
Displaying Data in a Graphic ............................................................................ 57
5.1
Overview of Graphic features ................................................................. 57
5.2
To display an existing web page, HTML document, or HMIWeb graphic58
5.3
To navigate between graphics ................................................................ 60
5.4
To create a new HMIWeb graphic .......................................................... 61
5.5
To edit an existing HMIWeb graphic....................................................... 62
5.6
To create a new graphic based on an existing graphic .......................... 63
5.7
Adding a graphic to a workspace ........................................................... 64
5.8
Importing an existing Workcenter or Experion PKS graphic .................. 64
5.9
To print a graphic .................................................................................... 64
5.10
Drag/Drop between graphics and other Uniformance Process Studio applications ............................................................................................. 65
5.11
Opening Uniformance Process Studio graphics in Workcenter ............. 67
5.12
Working with the graphic time control..................................................... 67
Operating the Time Control .............................................................................. 69
6.1
Time Control fields and buttons .............................................................. 69
6.2
Common Times status ............................................................................ 72
6.3
Viewing/adjusting the time control properties ......................................... 73
To display the Time Control properties ................................................ 73
6.4
Relative time syntax ............................................................................... 76
Uniformance - Process Studio User Guide ix
Contents
7.
8.
Creating and Managing Workspaces ............................................................... 77
7.1
Introducing workspaces .......................................................................... 77
7.2
Creating the workspace tree structure .................................................... 79
To create a new workspace.................................................................. 84
7.3
Description of Workspace commands .................................................... 85
7.4
Rearranging the workspace tree structure .............................................. 87
To move items (drag/drop) ................................................................... 87
To copy items (copy/paste) .................................................................. 87
To select multiple items ........................................................................ 87
Guidelines for rearranging .................................................................... 87
7.5
Displaying workspace content ................................................................ 88
7.6
Sharing a workspace with another user .................................................. 88
To make a workspace available to another user .................................. 88
To import a workspace to a user's machine ......................................... 90
Managing Windows in Uniformance Process Studio ..................................... 91
8.1
Maximizing the viewing area ................................................................... 91
To minimize the ribbon ......................................................................... 91
To hide windows ................................................................................... 91
8.2
Creating and modifying tab groups ......................................................... 92
To rearrange tabs within a tab group ................................................... 93
To create a new tab group.................................................................... 93
To move a tab to a different tab group ................................................. 93
To create a new tab group through drag/drop ...................................... 94
8.3
Repositioning the Browser and Navigation windows .............................. 95
9.
Providing the Configuration for Uniformance Process Studio ..................... 97
9.1
Overview of configuration ........................................................................ 97
9.2
Configuring data sources ........................................................................ 98
Guidelines for configuring access to PHD through the remote API ... 101
9.3
Creating a custom time period .............................................................. 102
To create a custom time period .......................................................... 102
9.4
Changing the application defaults ......................................................... 103
To access the application defaults ..................................................... 103
Enable performance optimization ....................................................... 104
To create custom colors ..................................................................... 104 x Uniformance - Process Studio User Guide
Contents
9.5
To change the printer ........................................................................... 106
10.
Troubleshooting and Servicing Uniformance Process Studio ................... 107
10.1
Viewing logs .......................................................................................... 107
10.2
To re-initialize, remove, or edit invalid tags/items ................................ 108
Uniformance - Process Studio User Guide xi
Contents
– Uniformance Process Studio Main Window.................................................. 13
– Time Control Properties Dialog Box ........................................................... 73
– Example Workspace Tree Structure ........................................................... 78
– Repositioning the Browser and Navigation Windows ................................. 95
– Description of Time Control Fields and Buttons ............................................ 69
– Commands Used to Manage Workspaces .................................................... 85
– Definition of Data Source Configuration Fields .............................................. 99
xii Uniformance - Process Studio User Guide
1. Getting Started With Uniformance Process
Studio
1.1 Opening Uniformance Process Studio
Use the Start menu:
Start>All Programs>Uniformance>Process Studio>Uniformance Process Studio.
Or
Double-click the Uniformance Process Studio shortcut on your desktop.
The following figure describes the key features of the main window of the Uniformance
Process Studio.
Figure 1
– Uniformance Process Studio Main Window
Uniformance - Process Studio User Guide 13
1 Getting Started With Uniformance Process Studio
1.2 Introducing the Browser
1.2 Introducing the Browser
Overview of the Browser
The tag/item Browser window allows you to browse tags (and equivalent data items) from various data sources. The Browser accesses the Desktop Configuration to obtain the user's data source configuration.
The Browser makes use of a server database service for the request/return of data from a database. This service removes the need for clients to have specific database components installed.
Upon the initial connection to a data source, depending on the Desktop Configuration, you may be prompted to enter PHD and/or Windows usernames/passwords. Upon a successful connection, the credentials are cached and you do not need to enter them again until you start a new session of Uniformance Process Studio.
You can browse only one data source at a time; however, you can easily toggle between data sources. The Desktop Configuration contains the entries that allow you to add more data sources and to configure the default data source.
The Browser window lists the names of data items available in a selected data source.
You can apply filters and specify search criteria to locate data items of interest.
To connect to a data source
Step
1
Action
Initially, the default Data Source is automatically selected for browsing. If you want to browse a different data source, click the drop down arrow for Data
Source, and select the data source that you want to browse.
2
3
Click the Refresh button to contact the data source.
Result: The Browser retrieves a top level browsing structure from the data source and populates it in the „View In‟ field.
By default, the „All Items‟ category is selected, allowing display of all items stored on the data source.
Enter a search criteria in Item Name Like field to specify what you are looking for (for example, 3_FIC*).
ATTENTION
The Browser's default fetch limit is 1000 tags. Enter search criteria so that the Browser returns a manageable number of tags that you can go through to find what you need.
14 Uniformance - Process Studio User Guide
1 Getting Started With Uniformance Process Studio
1.2 Introducing the Browser
Step
4
5
Action
Click Fetch.
Result: Upon Fetch, the Browser contacts the selected data source and retrieves the tags/items. Depending on how the data source was configured, you may be prompted for PHD and/or Windows usernames and passwords.
Enter valid credentials and then click OK.
A connection to the data source is attempted.
If the connection is successful, the "Retrieving items" message is displayed.
After a successful fetch, the browse structure is displayed.
6
After the tag/item names are successfully displayed, you can drag/drop them to a Workspace to organize your tags in folders that make sense to you - or, you can drag/drop tags directly from the Browser o a Trend, MultiTrend, or
Table for data retrieval.
Entering usernames and passwords
Depending on how a data source was configured, you may be prompted for PHD and/or
Windows usernames and passwords when you attempt to connect to a data source.
A dropdown list for the username field displays the previously used Windows and PHD user names, as shown in the following example. Do not assume that a username is applicable to the field just because it is included in that field's dropdown list.
Uniformance - Process Studio User Guide 15
1 Getting Started With Uniformance Process Studio
1.2 Introducing the Browser
Handling an unsuccessful connection to a data source
If the connection was not successful, do the following:
Verify that you selected the correct Data Source.
Click the Refresh button to attempt another connection.
If prompted for user credentials, ensure that you enter valid user names and passwords.
If the connection is still not successful, look at the log.
REFERENCE
For instructions on how to view the log for Uniformance Process Studio, refer
to section 10.1, "Viewing logs"
Description of the browse structure for a PHD server
By default, the Browser retrieves all tags stored on the PHD server.
To reduce the number of tags that are displayed, select one of the folders available. Upon
Fetch, the Browser contacts the selected data source and retrieves the items that fall
under the selected folder.
The following folders are available, by default, for browsing a PHD server:
All Items
Displays all items stored on the selected data source (Default).
Parents
Displays items in subdirectories based on their assigned parent tag, including multiple nested parents (such as grandparents), from which they inherit tag definition field properties.
Collectors
Displays items in subdirectories based on the PHD interface (RDI or Link) that collects their data from a DCS or other system for storage in the PHD database.
Considerations when browsing PHD parent tags
If a PHD parent tag is inactive, the parent does not appear in the Browser's View in tree, even though the parent may have tags associated to it.
If a PHD parent tag is active, but does not have any PHD tags associated to it, then the parent does not appear in the Browser's View in tree.
16 Uniformance - Process Studio User Guide
1 Getting Started With Uniformance Process Studio
1.3 To open a window to display process data
Applying filters and search criteria
There are two levels of filtering available in the Browser:
Provide input in the Item Name Like field to limit the items returned from the data source.
Invoke the filter criteria option that is provided for each column in the Browser results grid view. This selection is persisted and applied to future sessions also.
By default, any tags/items that include the criteria somewhere in their name are returned.
For example, boiler1 retrieves Boiler123 and CPlant.Boiler1.
After a successful Fetch, the filtered tag/item names display.
Wildcard characters
For more specific searches, use wildcard characters:
* for multiple characters
? for single characters
Organizing tags/items into customized folders
You can organize tags/items into customized folders using the Workspace feature of
Uniformance Process Studio.
REFERENCE
Configuring a browse limit
The Browser limits the number of tags/items that can be fetched at any one time to 1000 by default. This default prevents requests for large number of tags/items that could result in performance issues. The Desktop Configuration contains an application default entry
(Maximum Item Browser results) that allows you to change the maximum number of tags/items the Browser return.
REFERENCE
For details on Desktop Configuration, refer to section 9.4, "Changing the application defaults".
Uniformance - Process Studio User Guide 17
1 Getting Started With Uniformance Process Studio
1.3 To open a window to display process data
1.3 To open a window to display process data
Step Action
1
Click on the Home tab and then click Trend.
2
3
4
Result: A new Trend window displays.
Drag/drop tags/items from the Workspace or from the tag/item Browser window to the Trend.
Result: The data displays in the Trend window.
Click on the Home tab and then click Table.
Result: A new Table window displays.
Drag/drop tags/items to the Table.
Result: The data displays in the new Table window.
TIPS
Click on Home whenever you want to open a new window.
When you close a window or when you exit Uniformance Process Studio, a dialog box displays for each open window to give you the opportunity to Save the window's context to a Workspace folder .
18 Uniformance - Process Studio User Guide
1 Getting Started With Uniformance Process Studio
1.4 Introducing the time control
1.4 Introducing the time control
Overview of the time control
The Time Control allows the user to set time related properties and to automatically play or step through data.
The Time Control user interface (shown in the following figure) displays in the status strip at the bottom of the window.
The default time format is Relative. The default time Period is two hours (From now-2h
To: now). You can change the properties of the Time Control to use Absolute time format. The following figure shows the appearance of the Time Control for both
Relative and Absolute time formats.
Figure 1
– Time Control User Interface
What is "Current time"?
"Current time" is a position in time between the start and end times. The user points to
"current time" through the use of the relative time slider or the absolute date/time pickers.
A Trend uses "current time" as the position of hairline cursor 1.
A Graphic uses "current time" as the time for data shown by alphanumerics, indicators, and so forth.
Uniformance - Process Studio User Guide 19
1 Getting Started With Uniformance Process Studio
1.4 Introducing the time control
Description of data refresh
The only automatic refresh in Uniformance Process Studio (UPS) is for graphics - to support elements that are NOT connected to a time control in a graphic page. These elements are updated at the rate configured for the graphic page. Other elements in a graphic page that ARE connected to a time control on the graphic page are updated when the user places the UPS Time Control in Play mode, or when the user clicks the UPS
Time Control's Refresh button.
The UPS Time Control requests a refresh of data only when the user clicks Play to place the Time Control into Play mode, or when the user clicks Refresh to demand a data refresh.
Because there is no automatic refresh in UPS, the user obtains the following benefits:
Data in the content windows is maintained until the user chooses to manually request an update.
The user can link all content windows to a single Time Control without imposing an unnecessary or unacceptable load on the server to update all content windows at regular intervals.
To select a time period from a list
Step
1
Action
On the Time Control, select the time period that you want from the Period drop down list:
Note: When you change the Period, other time properties also change, including the Refresh interval and Fast replay multiplier for Play mode, and the Large and Small step sizes.
You can view all time properties in the Time
Control Properties dialog box.
2
The 'From' and To' fields on the Time Control update to reflect your selection, and the data automatically updates to the selected time settings.
20 Uniformance - Process Studio User Guide
1 Getting Started With Uniformance Process Studio
1.4 Introducing the time control
To specify a time period through direct entry
Step Action
1
On the Time Control, click the Properties button.
2
3
Result: the 'Time Control Properties' dialog box appears.
For the From and To entries, select Absolute or Relative time format and then enter the time period of interest.
After completing your entries, Click OK.
Result: The Time Control reflects the specified time period.
Note: When you change the time period, other time properties also change, including the Refresh interval and Fast replay multiplier for Play mode, and the Large and Small step sizes.
REFERENCE
For descriptions of all the time control properties, refer to section 6.3,
"Viewing/adjusting the time control properties".
To step forward and backward in time
The step buttons on the Time Control move the "current time" backward or forward in time by the step size.
To move backward or forward by the small step size, click or , respectively.
To move backward or forward by the large step size, click or , respectively.
Note: You can configure step sizes through the "Large step size" and "Small step size" in
the Time Control Properties dialog box.
To automatically scroll data forward
Click Play to automatically scroll data forward in time.
Note: You can configure the automatic data refresh interval for Play mode through the
"Refresh interval" in the Time Control Properties dialog box.
Uniformance - Process Studio User Guide 21
1 Getting Started With Uniformance Process Studio
1.4 Introducing the time control
To use separate time settings for each window
After initial installation, the Common Times status of Uniformance Process Studio is active – meaning that each content window (Trend, MultiTrend, Table, and Graphic) uses the same time control and time properties.
Perform the following steps to deactivate Common Times mode and allow each Trend,
MultiTrend, and Table to use a separate local Time Control user interface that you can manipulate independently.
Step
1
Action
Click Common Times on the ribbon:
Result: Common Times is no longer highlighted.
With Common Times not active, each window has its own Time Control user interface shown in the status strip of the window.
To synchronize windows to the same time settings (Common Times)
The Common Times status provides a way to synchronize all windows to the same time settings - this can be helpful when you need to explore a significant event from different viewpoints.
The Common Times status causes all Trend, MultiTrend, Table, and Graphic windows to use the same Period, the same start and end times, and a single master Time Control user interface. Any manipulations that you make through this master Time Control user interface affect all of the windows.
Step
1
2
Action
Display the Trend, MultiTrend, Table, or Graphic that has the time settings you want to use.
Click Common Times on the ribbon:
22 Uniformance - Process Studio User Guide
1 Getting Started With Uniformance Process Studio
1.4 Introducing the time control
Action Step
Result: Common Times becomes highlighted. The master Time Control appears in the status strip of the main window. The time properties from the local Time Control of the currently selected window go to the master Time
Control. All windows now use the times of the single, master Time Control.
Note: When you close Uniformance Process Studio, the current Common Times status is
saved, and it is used as the default startup state when you reopen Uniformance Process
Studio the next time.
Uniformance - Process Studio User Guide 23
1 Getting Started With Uniformance Process Studio
1.5 Displaying data in Uniformance Process Studio
1.5 Displaying data in Uniformance Process Studio
REFERENCE
For details on the different types of displays that are available in Uniformance
Process Studio, go to the section of interest:
For this display type
…
Go to this section
…
Trend
Multitrend
Displays data in a selected trend format (Single Y Axis, Strip Chart,
Multi Y Axis, XY, or Histogram).
Displays data in a matrix of individual charts
– up to 25 charts in a 5x5 matrix, with up to 6 traces per chart.
Table
Graphic
Window
Displays data in a tabular display that supports a number of the display styles similar to the
Uniformance Excel Companion.
Allows conditional filtering of data.
Displays data in an HMIWeb graphic, or opens the HMIWeb
Display Builder.
24 Uniformance - Process Studio User Guide
2. Displaying Data in a Trend
2.1 Choosing a Trend format
Single Y Axis (default) format
Single Y Axis format shows all traces superimposed on one display with a common X-
axis and Y-axis.
The single Y axis trend window allows the user to display 32 traces.
Figure 2
– Single Y Axis Trend
Strip Chart format
Strip Chart format shows each trace on a separate strip with its own Y-axis, but with a
common X-axis.
Figure 3
– Strip Chart Trend
Uniformance - Process Studio User Guide 25
2 Displaying Data in a Trend
2.1 Choosing a Trend format
Multiple Y Axis format
Multiple Y axis format shows all traces superimposed on one display – the Y axis for
each trace is used, but still with a common X axis.
In the following example, the Y axis for each trace displays on the left side of the trend.
The user can click on any trace to display its corresponding Y axis in the same color on the right side of the trend.
Note: For users familiar with the Uniformance Desktop, this format is similar to the
Process Trend.
Figure 4
– Multiple Y Axis Trend
26 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.1 Choosing a Trend format
XY format
XY format plots traces against each other. The user selects a tag/item as the X axis and a
tag/item as the Y axis.
XY format plots values against common timestamps.
If a trace displays Aggregate data, then you can associate X and Y with different tags/items.
If a trace displays RAW data, then both X and Y show trace values for the same tag/item.
You can click on a trace to display its data points (as shown in the following figure).
Figure 5
– XY Trend
Uniformance - Process Studio User Guide 27
2 Displaying Data in a Trend
2.1 Choosing a Trend format
Histogram format
The Histogram format is used to display how a variable is distributed. The histogram condenses a data series into a visual by taking many data points and grouping them into logical ranges or bins.
On the ribbon is a field where the user can specify the number of bins and the resolution.
A chart lists general statistical information, such as normal distribution, mean, and standard deviation.
The user can plot a histogram for any trace that was added to a Trend.
Figure 6
– Histogram Trend
28 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.2 Interpreting the histogram
2.2 Interpreting the histogram
Histogram algorithm
The algorithm used to calculate the Histogram series values is as follows:
W is the width of a bar in a histogram, and
W = (Max - Min) / #Bar.
Counts[] is the heights of bars in a histogram if Unit is selected as Counts, and
Counts[i] = is the number of sample for ((i-1)W * V[j] < iW)
Where i = 1, 2, ..., #Bar, and j = 1, 2, ..., N.
If the Unit is selected as Percent, the heights of bars is
Percent[i], and
Percent[i] = Counts[i] / N
The Normal Distribution Curve (where area is equal to the histogram) is calculated by:
Where x ranges from Mean - 3Dev to Mean + 3Dev.
Uniformance - Process Studio User Guide 29
2 Displaying Data in a Trend
2.2 Interpreting the histogram
Histogram statistics box
Value
#Data
LSL
HSL
Mean
Description
Resolution. Number of data points within the sample per trace.
Low Standard Limit. Default is the Low Extreme value in the PHD Server tag configuration.
High Standard Limit. Default is the High Extreme value in the PHD Server tag configuration.
The Mean value:
Std Dev Standard Deviation (Dev):
Minimum ---
Maximum ---
Cp Process Capability
Cpk
HSL LSL
If both LSL and HSL are defined,
Cp
Mean LSL
6
Dev
If only LSL is defined,
Cp
3
Dev
HSL Mean
If only HSL is defined,
Cp
3
Dev
The Process Capability index is defined as the Cp for a centered process producing a similar level of defects - the ratio between permissible deviation measured from the mean value to the nearest specific limit of acceptability, and the actual one-sided 3 x sigma spread of the process.
As a formula, Cpk = either (HSL-Mean)/(3 x sigma) or (Mean-LSL)/(3 x sigma) whichever is the smaller (that is, depending on whether the shift is up or down).
30 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.3 Creating a Trend
2.3 Creating a Trend
To create a new trend window
Step
1
On the Home menu, click Trend.
Action
Result: The Trend window displays.
2
The view defaults to a Single Y Axis trend type.
To select a different type, click Type on the menu, and then select the type:
Single Y Axis
– Shows all traces superimposed on one chart with common X and Y axes
Strip Chart
– Shows each trace on a separate strip with common X and Y axes.
Multiple Y Axis
– Shows all traces superimposed on one display - each trace has its own Y axis, but a common X axis.
XY
– Shows traces plotted against each other.
Histogram
–Shows distribution frequency of variable.
To add tags/items
You can drag/drop single or multiple tags/items from the Browser window to a Trend,
MultiTrend, or Table window.
Alternatively, you can directly enter a tag/item.
REFERENCE
For instructions on how to directly enter a tag/item, refer to section 2.4,
"Using direct entry to add tags/items".
To replace a tag/item
Drag a new tag/item from the Browser or Workspace and drop it onto the existing tag/item name in the Trend properties table.
Uniformance - Process Studio User Guide 31
2 Displaying Data in a Trend
2.3 Creating a Trend
To delete a tag/item
Step
1
Action
In the trend properties table, select the row to be deleted.
Result: The row becomes highlighted.
2
Press the Delete key.
3
Click OK to confirm the deletion.
To save a trend for reuse
REFERENCE
For instructions on how to save a trend to a workspace, refer to section 7.2,
"Creating the workspace tree structure".
32 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.4 Using direct entry to add tags/items
2.4 Using direct entry to add tags/items
You can add a tag/item to a Trend, MultiTrend, Table, or Workspace by directly entering the tag/item name. Optionally, you can customize the tag/item with details that define
how you want the data retrieved. Table 1 describes the entries to customize a tag/item.
Step
1
Action
On a Trend, MultiTrend, or Table window, right-click and select
Items>New Item.
Result: The 'Specify Item Details' dialog box displays.
2
Enter the Item Name and other entries as needed.
Refer to Table 1 for descriptions of the entries.
3
Click OK.
Result: The tag/item is added.
Uniformance - Process Studio User Guide 33
2 Displaying Data in a Trend
2.4 Using direct entry to add tags/items
Table 1
– Description of Item Details
Item Detail Description
Item Name
Enumerated
Enter the name of the data item. Tag Name and Item
Name are used interchangeably.
If checked, enumeration (string) values display for the item/tag instead of ordinal (integer) values.
Minimum Confidence Specifies the default minimum confidence for data retrieved from the PHD server. The confidence values range from 0 to 100, where 0 represents no confidence and 100 represents complete confidence in the data.
Null Value Replacement Specifies how you want Null (bad) values indicated.
Units
Aggregate
Resample Interval
Data Source
Specifies the engineering unit conversion that you want performed. Note: The units must be a valid, predefined unit conversion.
REFERENCE:
For definitions of Resample Interval and
the various Aggregates, refer to Table 2
Specifies the PHD server from which to retrieve the tag/item data.
34 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.5 Working with time ranges
2.5 Working with time ranges
To save a time range for reuse
REFERENCE
For instructions on how to save a time range to a workspace, refer to section
7.2, "Creating the workspace tree structure".
To reuse a saved time range
Drag the saved time range from the workspace to the start/end times on the Time Control user interface.
If the start/end times are not visible on the Time Control, you can drag/drop it to the
Properties button on the Time Control.
If Common Times is NOT active, you can drop the time range onto an individual window that supports it, such as Trend.
To trend different time ranges in the same window
Step Action
1
Create a Trend (not a MultiTrend).
Apply an offset to the top axis
2
Right-click the trend window and select Axis> Secondary X Axis
(Top)> Configure
3
Select a relative or absolute offset and then click outside the box to enter it.
Note: The secondary X axis does not display until after you assign at least one trace to the top X axis.
Assign a trace to use the offset
4
Assign at least one trace to use the top X axis:
In the properties table, click on the cell within the Axis column and select Top.
Uniformance - Process Studio User Guide 35
2 Displaying Data in a Trend
2.6 Viewing trend data value at hairline cursor position
2.6 Viewing trend data value at hairline cursor position
Overview of hairline cursors
The user can display a maximum of two hairline cursors (vertical lines) on a trend. The vertical lines allow the user to view the data value at one specific time and at two different times.
Hairline 1 – default color is red
If you reposition Hairline 1, it changes the Time Control's "current time" (in either Local or Common Times mode).
Hairline 1 synchronizes across all trend windows when in Common Times mode.
Hairline 2 – default color is blue
Hairline 2 is manipulated through a local window in Local Times mode only.
The mouse can be used to reposition both hairlines, as needed.
In addition, you can use the slider on the Time Control to reposition Hairline 1.
A box shows the tag name, value, and timestamp of all traces at the position of the hairlines.
A straight line algorithm is used to interpolate between data points when the hairline is not over actual data points.
To view data value at a specific time/date
Step
1
2
Action
Display the trend that contains the trace(s) of interest.
Right-click on the trend and select Display>Hairline 1 or Hairline 2.
Result: A vertical line displays on right-side of the trend, and a box shows the tag/item names of all the traces and the timestamp at the position of the hairline.
Note: You can drag the box out of the way as necessary.
36 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.6 Viewing trend data value at hairline cursor position
Step Action
Move the hairline
3
Drag the vertical line to the position of interest.
4
5
Result: The box shows the data value and timestamp at the new cursor position.
Note: Changing the position of Hairline 1 changes the "current time" in the local or master Time Control.
If you want more precise movement, use the mouse wheel to move the cursor left and right between data points for the selected trace. If no trace is selected, then the cursor uses the first trace.
Alternatively, to move Hairline 1, drag the slider on the Time Control.
TIP
To synchronize other windows to this window's Hairline 1 position, click
Common Times, if it is not already highlighted in the ribbon.
Show the time/date of the current hairline position
6
Move the mouse cursor over the slider to display the time/date of the hairline.
Note: Current-time is a position in time between the start and end times.
7
8
9
Click the Properties button on the Time Control.
Result: The Time Control Properties dialog box displays.
For Current time, click Absolute.
Click OK.
10
11
Result: The time/date replaces the slider on the Time Control
Place your cursor in the time/date field on the Time Control and enter the time/date that you want
Alternatively, you can use the arrows on the Time Control to specify a time/date:
Click the large down arrow to display a calendar, and then select the date.
Click the small arrows to increment/decrement the time
– position your cursor in the field that you want to increment/decrement.
Uniformance - Process Studio User Guide 37
2 Displaying Data in a Trend
2.6 Viewing trend data value at hairline cursor position
To view data value at two different times
Step
1
2
Action
Display the trend that contains the trace(s) of interest.
On the Trend ribbon, click Hairline 1 and Hairline 2.
3
Result: Two vertical lines display on the Trend, and the box shows the names and timestamps at both hairline positions.
Drag the vertical line for Hairline 1 to the position of interest.
Result: The values appear in the box.
4
Drag the vertical line for Hairline 2 to the position of interest.
Result: The values appear in the box
38 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.6 Viewing trend data value at hairline cursor position
To view statistics (min, max, mean, and SD) at hairline position
The Trend allows the user to display summary statistics on the information between
Hairline 1 and 2. This can be used, for example, to compare the statistics before and after a process improvement was made.
Note: The Zoom function is not available when the Statistics function is enabled.
Step
1
2
3
Action
Display the Trend that contains the trace(s) and timespan of interest.
On the ribbon, click Hairline 1 and/or Hairline 2.
Move the Hairlines to the times of interest.
On the ribbon, click Statistics.
Result: A box shows statistics on the information between Hairline 1 and 2.
To update the statistics information
To update the statistics, click on the Trend window.
If you place the Trend in Play mode, the statistics do not get updated with the current time update. You must click on the Trend window to refresh the statistics.
After adding a tag/item to the Trend, the statistics for the new tag/item do not display automatically. You must click on the Trend window to display the statistics for the new tag/item.
Uniformance - Process Studio User Guide 39
2 Displaying Data in a Trend
2.7 Using the zoom
2.7 Using the zoom
Step
1
Action
Drag the cursor over the area to zoom
2
3
Drag the cursor again to zoom again. Continue zooming as needed.
To reset (clear) the zoom, right-click and select Reset Zoom.
Note:
The Zoom function is not available when Statistics is enabled. To use the Zoom, disable (uncheck) the Statistics box in the ribbon..
40 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.8 Adding annotations
2.8 Adding annotations
Step
1
2
Action
Display the Trend that contains the trace(s) and Period of interest.
Right-click the Trend window and select Annotation>New.
RESULT: An entry box and prompt message appear in the upper left corner of the trend.
3
4
Press the F2 key when the mouse is over the entry box.
Type your annotation and press the Enter key to enter it.
5
Drag the annotation to the position you want.
2.9 Changing the visual properties of a Trend
To show/hide the properties table
Click on the control that appears above the properties table and below the Trend.
To show X axis on top or bottom
Click on Axis in the Trend properties table, and then select Top or Bottom.
To change style of trace line
Click on Style in the Trend properties table and select from the drop down list (Dash,
Dot, DashDot, or DashDotDot).
Uniformance - Process Studio User Guide 41
2 Displaying Data in a Trend
2.9 Changing the visual properties of a Trend
To change style of marker for indication of data points
Click on Marker in the Trend properties table and select from the drop down list
(Rectangle, Circle, Triangle, or Diamond).
ATTENTION
Enabling the Marker styles degrades Trend performance.
To change color of trace line
Click on Color in the Trend properties table and select a color from the drop down list.
To show Step instead of linear trace line
Click on Step in the Trend properties table to display the trace line as steps between data points instead of linear lines.
To show a grid
On the Trend window, right-click and then select Display>Grid.
To show/edit title
Note: This procedure applies to a Trend and to each chart in a MultiTrend.
To display the trend title, right-click on the window or chart and then select
Title>Display.
To change the title, right-click on the window or chart and then select Title>Edit. Typein a title and press Enter or click outside of the port.
42 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.10 Viewing and changing the scale of a Trend
2.10 Viewing and changing the scale of a Trend
To view the scale of a trace
To display the scale of a particular trace, click on its name in the properties table.
To change the scale
Select the YRange property, located in the Trend's properties table for each trace, and set it to one of the following:
Auto Scale - Automatically rescales Y range to accommodate the displayed data.
Tag Range - Sets Y range equal to the tag/item high/low extremes.
Custom Range - Allows user to set minimum/maximum range.
To automatically rescale
To configure automatic rescaling for a particular trace, select its YRange in the properties table, and then select Auto Scale.
To rescale all traces in the trend, select Type>Auto Scale in the Trend ribbon.
To plot trace with its own scale (normalized Y axis)
Select YRange in the properties table, and then select Tag Range.
To manually change scale of trace distorted by a single outlier
Select YRange in the properties table, select Custom Range, and then enter a new
Minimum and/or Maximum value. Select the item in the properties table to display its
new YRange.
To lock the range of the Y axis (Lock Scale)
Right-click on the Trend window and select Axis>Lock Y Scale.
Uniformance - Process Studio User Guide 43
2 Displaying Data in a Trend
2.11 Description of data retrieval properties 'Frequency' and 'Method'
2.11 Description of data retrieval properties 'Frequency' and 'Method'
The following table describes the 'Method' and 'Frequency' properties that affect data retrieval for Uniformance Process Studio. You can change the 'Method' and 'Frequency' properties in Trend and MultiTrend, or through direct entry of a tag/item.
Trend (through the properties table on a per tag/item basis)
MultiTrend (through the ribbon on a per window basis)
Table 2
– Definition of Frequency and Method
Property Description
Frequency
Selects the time interval for sampling or reduction: 1S, 5S, 10S,
30S, 1M, 2M, 5M, 10M, 30M, 1H, 2H, 4H, 8H, 1D, 7D, or 30D.
Default is 10S.
Method
Selects a data sampling type (Raw or Snapshot) or reduction calculation (Average, Delta, First, Last, Maximum, Minimum,
RegressionConstant, RegressionDeviation, RegressionSlope,
Standard Deviation). The default method is Snapshot.
This method...
Provides this data…
Raw The actual sample that was stored with its timestamp
– no reduction is performed. This method does not include interpolation. If the actual sample is not there during the
"Frequency" (time interval), it returns the nearest actual sample.
Snapshot A value that is the interpolation between the raw data values within the Frequency time interval. Provides the raw data that exist at specific timestamps - other values are interpolated according to the
PHD tag configuration. Note: Tag configuration of Interpolation
Method (Linear or Step) affects all reduction results and Resample
Method (Sample at Interval or Average Around Interval) affects the results when resampled data are reduced.
<reduction> A value calculated from the raw values over the "Frequency" (time interval). Also referred to as Aggregate. Applies to floating or integer data.
Average
The average data over the time interval using time weighted averaging.
44 Uniformance - Process Studio User Guide
2 Displaying Data in a Trend
2.11 Description of data retrieval properties 'Frequency' and 'Method'
Property Description
Delta
First
Last
Maximum
Minimum
Regression
Constant
Regression
Deviation
Regression
Slope
Standard
Deviation
Value at start of time interval subtracted from value at end using time weighted averaging.
The first actual (raw) value at the start of the time interval.
The last actual (raw) value at the end of the time interval.
The maximum value over the time interval using time weighted averaging.
The minimum value over the time interval using time weighted averaging.
Y-intercept of the regression line using time weighted averaging.
Standard deviation of the regression line over the time interval using time weighted averaging.
Slope of the regression line over the time interval using time weighted averaging.
The standard deviation of the samples over the time interval using time weighted averaging.
REFERENCE - INTERNAL
For more information on PHD reductions, refer to the PHD System Manual
(pim0301), section "Data Resampling" and "Data Reduction Calculations".
Uniformance - Process Studio User Guide 45
2 Displaying Data in a Trend
2.11 Description of data retrieval properties 'Frequency' and 'Method'
46 Uniformance - Process Studio User Guide
3. Displaying Data in a Multi-Trend
3.1 Overview of MultiTrend features
MultiTrend allows the user to set up a set of small trends that typically cover a relatively
large number of tags/items, for routine process monitoring.
MultiTrend displays only aggregate (not raw) data.
Each MultiTrend can contain up to 25 charts. The example in the following figure contains four charts.
The maximum number of traces per chart is user configurable through Desktop
Configuration – the default limit is 6.
The maximum number of rows and columns is user configurable through Desktop
Configuration – the default limit is 5.
The maximum total number of trace points per MultiTrend is user configurable through the ribbon command "Max. Trace Point Count". The default limit is 2000 traces.
The MultiTrend automatically adjusts the Aggregate frequency based on the number of data points and the start and end times. For example, with 100 data points displayed for five days of data, the calculated frequency is (60*60*24*5) = 432000 seconds, or 1H12M
(1 hour 12 minutes). If you select a frequency of 2hrs, then there is no change.
Each MultiTrend displays as a tabbed window.
Figure 7
– MultiTrend
Uniformance - Process Studio User Guide 47
3 Displaying Data in a Multi-Trend
3.2 To create a new MultiTrend
3.2 To create a new MultiTrend
Step Action
Open a new MultiTrend window
1
On the Home menu, click MultiTrend.
Result: The MultiTrend window displays. The default layout is four charts.
Select layout
2
To select the layout, right-click on the MultiTrend window, select Layout, and then click the chart layout that you want.
Add tags/items
3
METHOD 1: Open the tag/item Browser window if not already present and drag/drop a tag/item to a chart in the MultiTrend window.
METHOD 2: Right-click a chart in the MultiTrend window and select
Items>New Item. Enter the item details into the dialog box and then click
OK.
4
Result: The trend for the tag/item displays in the chart.
Continue adding tags/items as needed.
Note: Multiple tags/items can be added to an individual chart.
Replace or remove tags/items
5
Right-click a chart and select one of the following commands:
Items>Edit
– to replace a tag/item
Items>Remove
– to delete a tag/item
48 Uniformance - Process Studio User Guide
3 Displaying Data in a Multi-Trend
3.3 To save all MultiTrend charts or a single chart for reuse
3.3 To save all MultiTrend charts or a single chart for reuse
REFERENCE
For instructions on how to save all of the MultiTrend charts or a single chart
to a workspace, refer to section refer to section 7.2, "Creating the workspace tree structure".
3.4 To view the MultiTrend properties
Right-click on the MultiTrend and select Display>Legend.
Result: The tag/item names, trace colors, and statistics appear in a box on each chart.
3.5 To view a MultiTrend chart in a Trend window
Double-click on any chart in a MultiTrend window to open a new Trend window containing the same tags/item(s).
3.6 To display hairline cursors in a MultiTrend
To display hairline cursors in a MultiTrend, right-click, and then select
Display>Hairlines.
Result: A vertical hairline cursor displays on all charts in the MultiTrend.
Note: If you reposition the hairline in one of the charts, it moves the hairline in all of the
other charts. It also changes the Time Control's "current time" (for local or master Time
Control).
Uniformance - Process Studio User Guide 49
3 Displaying Data in a Multi-Trend
3.6 To display hairline cursors in a MultiTrend
50 Uniformance - Process Studio User Guide
4. Displaying Data in a Table
4.1 Overview of Table features
The Table allows you to display data for a given timespan in a tabular form. The data table shows the following detailed data for each tag/item: timestamp value confidence factor
A table can be populated from a Trend or directly configured.
Each table displays as a tabbed window.
From a table, you can edit PHD data values and perform Manual Inputs.
You can apply a custom filter to any column of a table by entering one or more conditions. Data that meets the conditions is filtered from the table.
You can export a table to Microsoft Excel and to the Uniformance Excel Companion.
There are three table formats: standard, matrix, and merged.
Note: The data Table accepts a maximum of 10 tags.
Figure 8
– Table Example
Uniformance - Process Studio User Guide 51
4 Displaying Data in a Table
4.2 To create a table
4.2 To create a table
Double-click a tag/item in the Browser window – a new Table window is created and the selected tag/item is added to the table.
Or
Click on the Home tab and select Table to create a new Table window, and then add tags/items:
Drag/drop a single or multiple tags/items from the Browser or from a workspace onto the table.
Or
Right-click on a Trend and select Edit>Copy, then right-click on the table and select
Context>Paste.
Or
Right-click on the table and select Items>New Item. See Table 1 for definitions of
the optional entries to customize a tag/item.
4.3 To save a table to a workspace
REFERENCE
For instructions on how to save a table to a workspace, refer to section 7.2,
"Creating the workspace tree structure".
52 Uniformance - Process Studio User Guide
4 Displaying Data in a Table
4.4 To filter table data
4.4 To filter table data
Note: The filter is available only in the Standard type of Table.
Step
1
2
3
Action
In the table, select the Filter button on the column you want to filter.
Select Custom.
Enter your filter criteria into the dialog box.
4
Result: The filter statement appears at the bottom of the dialog box.
If you add more than one condition, select And Condition or Or Condition to specify the logic to be applied.
Uniformance - Process Studio User Guide 53
4 Displaying Data in a Table
4.4 To filter table data
Step Action
5
Result: AND/OR appears in the filter statement at the bottom of the dialog box.
Click OK.
Result: The indicator on the column's Filter button becomes solid black to indicate that a filter is present:
To delete a condition from a custom filter
Step
1
Action
In the Filter dialog box, click the button of the condition that you want to
2
3
delete.
Result: The condition becomes highlighted.
Click Delete Condition.
Click OK.
54 Uniformance - Process Studio User Guide
4 Displaying Data in a Table
4.5 To perform manual input/edit of PHD data in a table
4.5 To perform manual input/edit of PHD data in a table
Note: For an input/edit to be successful, the PHD tag/item must have either the Data Edit
flag or the Manual Input flag enabled in its tag configuration.
Step
1
Action
Double-click on any value in the table for the tag/item that you want to input/edit.
2
5
6
3
4
Or
Right-click on the table and select Manual Input.
Result: The 'Modify' dialog box displays.
Specify the date/time for which you want to enter a value. Note: A calendar is available under the drop down arrow.
Enter the value that you want.
Change the confidence factor, if needed.
Click Modify to send the change to PHD.
Click Refresh in the Time Control to update the table data.
Uniformance - Process Studio User Guide 55
4 Displaying Data in a Table
4.6 Viewing PHD tag/item configuration in a table
Figure 9
– Manual Input/Edit
4.6 Viewing PHD tag/item configuration in a table
To display the five pages (groups) of configuration parameters for all tags/items in the table: right-click>View>Item Info.
The configuration is shown in a tabbed form. Click on a page (group) to view the tag/item definitions.
REFERENCE
For descriptions of the fields, refer to the PHD User Guide, (pim0201), section "Tag Configuration Form".
56 Uniformance - Process Studio User Guide
5. Displaying Data in a Graphic
5.1 Overview of Graphic features
Uniformance Process Studio graphics are used to display process schematics, mimics, and trends. Figure 10 shows an example of a process schematic type of graphic. A time control within a graphic allows you to play back an event or review the state of a process or system at a particular point in time. You can synchronize the graphic to the
Uniformance Process Studio master Time Control by activating the Common Times status, or you can use the graphic's own separate time control. In Uniformance Process
Studio, the Graphic Window provides the means to
Open an existing HMIWeb graphic, a web page, or an HTML document.
Launch HMIWeb Display Builder to create new graphics or edit existing graphics.
Uniformance Process Studio graphics use the same HMIWeb technology as Honeywell
Workcenter and Experion PKS. You can launch HMIWeb Display Builder from within
Uniformance Process Studio if the licensed option is installed.
Figure 10
– Graphic Window Example
Uniformance - Process Studio User Guide 57
5 Displaying Data in a Graphic
5.2 To display an existing web page, HTML document, or HMIWeb graphic
5.2 To display an existing web page, HTML document, or
HMIWeb graphic
The Graphic Window functions as a container for HTML documents. To load such content into a Graphic Window, use any of the following methods.
Step
1
Action
Double-click a Graphic/URL item in a Workspace to open a new Graphic
Window containing the Graphic/URL.
Or
Step
1
Action
In the Home tab, click Graphic Window.
2
Click the Open button in the Graphic tab or inside the new empty Graphic
Window.
58 Uniformance - Process Studio User Guide
Step
5 Displaying Data in a Graphic
5.2 To display an existing web page, HTML document, or HMIWeb graphic
Action
3
Browse to the HTML file of interest and then click Open.
Or
Step
1
Action
In the Home tab, click Graphic Window.
2
In the Graphic tab, click Address Bar, to make the address bar visible if it is not already visible.
Uniformance - Process Studio User Guide 59
5 Displaying Data in a Graphic
5.3 To navigate between graphics
Step Action
3
Enter a URL in the Address field and click Go, or click on the button, browse to the HTML file of interest, and then click Open.
5.3 To navigate between graphics
If graphic pages are linked together with hyperlinks, then the Back and Forward
ribbon buttons perform a function similar to that of most web browsers.
You can create hyperlinks using the HMIWeb Display Builder.
REFERENCE
See the HMIWeb Display Builder Guide for detailed information on how to create hyperlinks. This Guide is available from the Help menu of the HMIWeb
Display Builder.
60 Uniformance - Process Studio User Guide
5 Displaying Data in a Graphic
5.4 To create a new HMIWeb graphic
5.4 To create a new HMIWeb graphic
Prerequisite: The Uniformance Process Studio installation must include the HMIWeb
Display Builder licensed option.
Step
1
Action
2
Click the Home tab,
Click on the Graphic Window button in the ribbon to create an empty graphic window.
3
4
Click the New button
Window.
in the ribbon or inside the new empty Graphic
Specify the name and location for the new graphic file and click OK.
5
6
7
Result: HMIWeb Display Builder opens and displays the new blank graphic file.
Add content to the display as needed.
REFERENCE
See the HMIWeb Display Builder Guide for detailed information on how to build graphic displays and use the various graphics objects. The Guide is available from the Help menu of the HMIWeb Display Builder.
REFERENCE
To use an existing Uniformance Process Studio graphic as a starting point for
a new graphic, see section 5.6
“To create a new graphic based on an existing graphic."
Click Save in HMIWeb Display Builder.
Result: Your changes are saved and automatically displayed in the Graphic
Window of Uniformance Process Studio.
When you finish this graphic building session, you may close HMIWeb
Display Builder: File>Exit.
TIP
HMIWeb Display Builder automatically opens each time you select the command to edit or create a graphic in Uniformance Process Studio.
Uniformance - Process Studio User Guide 61
5 Displaying Data in a Graphic
5.5 To edit an existing HMIWeb graphic
5.5 To edit an existing HMIWeb graphic
Prerequisite: The Uniformance Process Studio installation must include the HMIWeb
Display Builder licensed option.
Step
1
Action
Open the existing graphic in Uniformance Process Studio (see section 5.2).
2
3
Click the Edit button in the ribbon.
Result: HMIWeb display Builder launches and automatically loads the display. The graphic window icon changes from to to indicate that the graphic is open in HMIWeb Display Builder.
Make the required changes to the display in HMIWeb Display Builder and click Save.
Result: The Uniformance Process Studio graphic page automatically reloads to reflect the latest changes.
REFERENCE
See the HMIWeb Display Builder Guide for detailed information on how to build graphic displays and use the various graphics objects. This Guide is available from the Help menu of the HMIWeb Display Builder.
TIP
Switch to the Uniformance Process Studio Graphic Window to see a live copy of the most recent changes that you saved from HMIWeb Display Builder.
62 Uniformance - Process Studio User Guide
5 Displaying Data in a Graphic
5.6 To create a new graphic based on an existing graphic
5.6 To create a new graphic based on an existing graphic
Step Action
1
2
Open the existing graphic in Uniformance Process Studio (see section 5.2).
Click the Copy & Edit button on the ribbon.
3
4
Specify the name and location for the copy of the graphic file and click Save.
Use HMIWeb Display Builder to modify the display as needed.
5
REFERENCE
See the HMIWeb Display Builder Guide for detailed information on how to build graphic displays and use the various graphics objects. This Guide is available from the Help menu of the HMIWeb Display Builder.
Click the HMIWeb Display Builder Save or Save All button to save any changes to the display.
Uniformance - Process Studio User Guide 63
5 Displaying Data in a Graphic
5.7 Adding a graphic to a workspace
5.7 Adding a graphic to a workspace
You can add a Graphic to a workspace.
REFERENCE
See section 7.2, "Creating the workspace tree structure".
5.8 Importing an existing Workcenter or Experion PKS graphic
Uniformance Process Studio graphics use the same HMIWeb technology as the displays on Honeywell Workcenter and Experion PKS. It is possible to import some Workcenter and Experion PKS displays into Uniformance Process Studio.
Contact Honeywell TAC for information on the import of Workcenter or Experion PKS displays into Uniformance Process Studio.
5.9 To print a graphic
Step
1
2
Action
Click the Print button on the ribbon.
Adjust the print settings if required and then click the Print button.
64 Uniformance - Process Studio User Guide
5 Displaying Data in a Graphic
5.10 Drag/Drop between graphics and other Uniformance Process Studio applications
5.10 Drag/Drop between graphics and other Uniformance
Process Studio applications
The following table describes graphic objects that are drag and drop zones that you can use to transfer items and time range details to and from other Uniformance Process
Studio applications.
For example, you can drag an alphanumeric from a graphic to a Trend to trend the item represented by the alphanumeric.
TIP
Arrange your windows vertically or horizontally so that you can see the window you want to drag from and the window you want to drop to. See
section 8.2, "Creating and modifying tab groups".
Table 3
– Graphic Drag/Drop Zones
Graphic Drag/Drop Zone
Alphanumeric
Description
Drag from here to drag the item details of the alphanumeric.
Indicator Drag from here to drag the item details of the indicator.
Table Column Header Drag from here to drag the item details of the single column.
Uniformance - Process Studio User Guide 65
5 Displaying Data in a Graphic
5.10 Drag/Drop between graphics and other Uniformance Process Studio applications
Graphic Drag/Drop Zone
Table Header
Embedded Trend Legend Label
Embedded Trend Drag/Drop Zone
Time Control
Description
Drag from here to drag the item details of every column of the table.
Drop a single item here to add that item to the table as a new column.
Drop multiple items here to remove all of the existing columns of the table and create a new column for each of the dropped items.
Drag from here to drag the item details of the single trace.
Drag from here to drag the item details of every trace on the trend.
Drop a single item here to add that item to the embedded trend as a new trace.
Drop multiple items here to remove all of the existing traces on the embedded trend and create a new trace for each of the dropped items.
Drag from here to drag the current time range details of the time control.
Drop here to set the time control properties (start time, end time, current time, and large and small step sizes) to those of the dropped time range details. All graphic objects linked to the time control are refreshed using these details. In addition, if the
Common Times mode is in use, the master start/end times update to those of the dropped time range.
66 Uniformance - Process Studio User Guide
5 Displaying Data in a Graphic
5.11 Opening Uniformance Process Studio graphics in Workcenter
Graphic Drag/Drop Zone
Quick Trend Drop Zone
Description
Drop here to open a Trend window that shows the dropped item(s).
5.11 Opening Uniformance Process Studio graphics in
Workcenter
Uniformance Process Studio graphics are not currently supported in Workcenter.
5.12 Working with the graphic time control
When not in Common Times mode, a graphic uses the time control configured through the HMIWeb Display Builder.
When in Common Times mode, the time control within the graphic is driven by the master time control in the status strip of Uniformance Process Studio.
If a time control was not added to the graphic page when it was created in HMIWeb
Display Builder, then the Graphic Window does not allow you to toggle the use of
Common Times.
If you want to be able to use a graphic time control or the Uniformance Process Studio
Common Times (master) time control to move graphic elements through time, then you must use HMIWeb Display Builder to link the graphic elements (such as alphanumerics, indicators, trends, and tables) to a graphic time control.
REFERENCE
For details on how to use the graphic time control within displays, see the
HMIWeb Display Builder Guide. This Guide is available from the Help menu of the HMIWeb Display Builder.
Uniformance - Process Studio User Guide 67
5 Displaying Data in a Graphic
5.12 Working with the graphic time control
68 Uniformance - Process Studio User Guide
6. Operating the Time Control
6.1 Time Control fields and buttons
The Time Control is an user interface within Uniformance Process Studio that allows the user to set time-related properties.
REFERENCE
For an introduction to the Time Control, refer to section 1.4.
ATTENTION
When Common Times is inactive, the Time Control user interface resizes to fit the available space within each local content window. Reductions in size may remove some fields or buttons from the Time Control or may completely hide the local Time Control.
You can still change the properties through the Time Control Properties dialog box.
If a resize of the Time Control hides the From/To times object, you cannot drag a time range from the Time Control
– however, you can still drop onto the Properties button.
Simply increase the size of the content window to display the entire Time
Control user interface.
The following table describes fields and buttons on the Time Control user interface.
Table 4
– Description of Time Control Fields and Buttons
Field/Button Description
Period
Allows the user to select a Period to apply to the Time Control. The properties of a Period are start and end times, step sizes, and refresh interval.
From: and To:
(start and end times)
Indicates the start (From) and end (To) times (time range) used by the Time
Control to request data.
Uniformance - Process Studio User Guide 69
6 Operating the Time Control
6.1 Time Control fields and buttons
Field/Button
From: and To:
(start and end times),continued
Description
To change the From/To times (time range), right-click on it to display the Time
Control Properties dialog box, or select a different Period from the Period drop-down list, or click on the forward/ back buttons.
The user can use the From/To times to drag/drop the time control properties to a workspace or to other objects within Uniformance Process Studio that can use a time range. When you left-click on From/To times, it loads the time control properties (context) for drag/drop - when you release the mouse button, it drops the context.
The user can drag/drop onto the From/To times. Note: When you drop onto the Time Control, the Period changes to 'Custom'.
When Common Times is not active, the From/To times may not display, because the Time Control user interface reduces in size to fit into the available space of the local content window. In such a case, you cannot drag the From/To times, but you can drop a time range onto the Properties button.
Large Step
Back button
Moves the From (start) time, To (end) time, and "current time" together, back in time by the time increment specified in the Large Step property.
Small Step
Back button
Moves the From (start) time, To (end) time, and "current time" together, back in time by the time increment specified in the Small Step property.
Large Step
Forward button
Moves the From (start) time, To (end) time, and "current time" together, forward in time by the time increment specified in the Large Step property.
Small Step
Forward button
Moves the start, end, and current times together, forward in time by the time increment specified in the Small Step property.
Slider control
Moves the "current time" within the period identified by the From (start) and To
(end) times. When in Play mode, the slider moves automatically and appears grayed-out. See also: Play button.
70 Uniformance - Process Studio User Guide
6 Operating the Time Control
6.1 Time Control fields and buttons
Field/Button
Refresh button
Description
Requests an update of the data in the time range. For example, if you display a Trend with a time range of 'now-2h to now' and then go to a meeting for an hour, when you get back, the data is one hour old. Click Refresh to update the Trend data with the latest values.
Play button
Play Stop
Toggles between 'Play' and 'Stop'. 'Play' turns on play mode and increments forward through time at a predefined interval. 'Stop" turns off the Time Control automatic refresh.
When in Play mode, the slider moves automatically, and the time control appears grayed-out, except for the Stop button.
Properties button
Play mode increments forward at a normal or fast interval, depending on the configuration of the Time Control properties, as follows: normal -
If the Fast Replay property is set to “Normal refresh”, play mode increments at the Refresh Interval. Normal play mode continues incrementing if it reaches a relative end time of Now. fast -
If the Fast Replay property is set to “n times normal”, play mode increments at the fast interval, where 'n' is a specified multiplier. Fast play mode slows to normal refresh when it reaches a relative end time of Now.
When playing, and "current time" reaches the To:(end) time:
If Relative end time - playing continues at the refresh interval.
If Absolute end time - playing stops when it reaches the end time.
Displays the Time Control Properties dialog box, where the user can view/modify the time-related properties.
This button is also a drag/drop target - you can drag/drop a time range onto the Properties button. This is useful when the From/To times are not available as a drag/drop target, because the Time Control user interface was reduced in size to fit the space available in the local window.
Uniformance - Process Studio User Guide 71
6 Operating the Time Control
6.2 Common Times status
6.2 Common Times status
The Common Times status is present in the ribbon of each Trend, MultiTrend, Table, and
Graphic. The status determines whether all windows synchronize to the same time settings or each window has its own independent time settings.
Common Times has two states: active and inactive. Initially, Common Times is inactive.
Common Times mode:
Local Times mode:
When Common Times is active:
The Common Times status is highlighted.
There is one master Time Control user interface – it displays status strip of the main window.
All open windows share common time settings. For example, if you change the time period, then all windows automatically update to display the same time setting. Note:
A graphic must have an HMIWeb time control on its page to be able to respond to the Common Times status.
If you drop a time entry (a time range, time control, or saved content that has an associated time) onto a window, it does not have any effect - the master Time Control settings continue to be in effect.
When Common Times is inactive:
The Common Times status is not highlighted.
A separate Time Control user interface displays in the status strip of each window. Note: A graphic uses the time control configured through the HMIWeb Display Builder, if present.
The Time Control user interface resizes to fit the available space within the status strip of each window.
If you change the time settings of one window, it does not affect any other windows.
If you add a new window (such as Home>Trend), it displays with its own local Time Control user interface.
Note: When you close Uniformance Process Studio, it saves the current Common Times
status, and then uses it as the startup state when you reopen Uniformance Process Studio.
72 Uniformance - Process Studio User Guide
6 Operating the Time Control
6.3 Viewing/adjusting the time control properties
6.3 Viewing/adjusting the time control properties
The Time Control Properties dialog box (shown in the following figure) allows the user
to view and adjust the properties of the Time Control. Table 5 describes the properties.
Figure 11
– Time Control Properties Dialog Box
To display the Time Control properties
Click the Properties button on the Time Control user interface.
Or
Right or left-click on the From/To times on the Time Control user interface.
ATTENTION
If you make a data entry error, the appropriate field changes to a yellow background. Errors include incorrect relative time, and errors in a dependant time entry
– such as a start (From) time that is after the end (To) time.
Uniformance - Process Studio User Guide 73
6 Operating the Time Control
6.3 Viewing/adjusting the time control properties
Field
Period
From/
To
Table 5
– Description of Time Control Properties
Description
Allows the user to select a Period from the drop-down list. Properties of a Period are start and end times, large and small step-sizes, and refresh rate.
Allows the user to enter a time range and to select absolute or relative time format for the time range
– depending on the selection in the adjacent buttons.
Absolute:
These buttons increment/decrement the number at the position of the cursor.
This button displays a calendar to assist with date selection.
Relative:
This button allows you to select a relative time from the drop down list.
This button displays the Relative Time Builder dialog box to assist with simple relative time entry. REFERENCE:
For relative time syntax, see section 6.4.
74 Uniformance - Process Studio User Guide
6 Operating the Time Control
6.3 Viewing/adjusting the time control properties
Field
Current
Time
Description
The "current-time" is a position in time between the From:(start) and To:(end) times.
The user points to "current time" through use of the Relative time slider or the Absolute date/time pickers.
When you select Relative time format, you can manipulate "current time" using the slider
– the slider represents the approximate position between the start and end times.
Trends use "current time" as the position of Hairline 1.
Graphics use "current time" as the time for data shown by alphanumerics, indicators, and so forth.
Relative:
Absolute:
Refresh interval
Fast replay
Small step
Large step
OK button
Cancel button
Specifies how frequently Trends, MultiTrends, Tables, and Graphics refresh their data when the Time Control is in Play mode.
Specifies the multiplier that is applied to the Refresh interval when the "current time" is before the end time and the Time Control is placed in Play mode. This has the effect of speeding-up history replay by incrementing the "current time" at the faster-rate.
Specifies the time increment used for a small step forward or backward in time. The
Uniformance Process Studio Time Control user interface does not currently use Small step, but the Graphics time control uses it, and it can be used programmatically.
Specifies the time increment to be used for the large step button in the Time Control user interface to move forward or backward in time.
Applies the user's changes to the Time Control. When there are errors in the time entries, the OK button is disabled until the errors are resolved.
Closes the properties dialog box without applying the user's changes.
Uniformance - Process Studio User Guide 75
6 Operating the Time Control
6.4 Relative time syntax
6.4 Relative time syntax
76 Uniformance - Process Studio User Guide
7. Creating and Managing Workspaces
7.1 Introducing workspaces
A workspace is a collection of reusable items organized into folders in a tree structure, as illustrated in the following navigation pane example.
The navigation pane shows one project at a time.
A project is made up of one or more individual workspaces.
Each item that you store in a workspace has properties that are referred to as its
"context". To reuse a context item, you drag/drop it to a location that supports it.
Each workspace is represented in a <workspace_name>.xml file. Each project is represented in a <project_name>.dpr file.
You can create one or more projects and then load the project of interest, as needed.
Workspaces are selectable for viewing – one at a time – through buttons on the navigation pane.
Figure 12
– Navigation Pane Example
<project>
<workspace>
<folder>
<subfolder>
<context>
<folder>
<workspace>
<workspace>
Uniformance - Process Studio User Guide 77
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
Types of workspace content
Users can combine content in a Workspace in any way that suits their needs. The user can create a folder hierarchy, rename content, and repeat a particular content multiple times. You can add any of the following content to a workspace tree structure:
Trend Aggregate
MultiTrend
Table
Time Control properties
Graphic / URL
Link to external application or file, such as a Microsoft Word or Excel document
Tag/Item (may include item details)
Time Range
Data Source
Tag/Item (includes trend trace details)
Folder/Subfolder
Figure 13
– Example Workspace Tree Structure
78 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
7.2 Creating the workspace tree structure
You can explicitly add content to a workspace through the workspace right-click menu,
or some content can be added through Copy/Paste and drag/drop. Refer to the Table 6
for details.
Table 6
– Steps to Add Items to a Workspace
Workspace content
Content description To add items to a workspace
…
Folder/
Subfolder
Link
Graphic /
URL
Used to organize workspace content in a tree structure.
1) Right-click on the white background of the workspace and select Add>Folder or right-click on a parent folder and select Add>Sub Folder.
2) Type a new name for the folder.
Provides a link to an external application
(such as ModTag.exe) or a file (such as
Microsoft Word or
Excel document).
Result: The new folder is available in the workspace.
REFERENCE: For instructions on how to rearrange
your folders, see 7.4, "Rearranging the workspace tree structure ".
1) Right-click on a folder in the workspace and select
Add>Link.
2) Navigate to the location of the application or file and click Open.
Provides a link to a web page, an HMIWeb graphic, or an HTML document.
Result: The content is available in the workspace.
3) Rename the content appropriately, if needed.
1) Drag/drop the graphic to a workspace folder.
Result: The content is available in the workspace.
Uniformance - Process Studio User Guide 79
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
Workspace content
Content description
Graphic /
URL
(continued)
To add items to a workspace
…
OR
1) Right-click on the graphic window and select Copy
URL, then right-click a workspace folder and select
Paste.
Result: The content is available in the workspace.
OR
1) Right-click on a folder in the workspace and select
Add>URL.
2) Enter the URL of an HMIWeb graphic, a web page, or an HTML document, and then click OK.
Result: The content is available in the workspace.
OR
1) Display an HMIWeb graphic, a web page, or an
HTML document in a Graphic Window.
2) Click Address Bar on the Graphic ribbon to show the Address bar if it is not already displayed.
3) Drag/drop the Address: onto a folder in the workspace.
Tag Defines a tag/item reference, including trend trace details.
Result: The content is available in the workspace.
4) Rename the content appropriately, if needed.
1) Drag/drop a tag/item from the Trend properties table to a folder in the workspace.
Result: The content is available in the workspace.
2) Rename the content appropriately, if needed.
80 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
Workspace content
Tag
Content description
Defines a tag/item reference, including item details, if present:
- Minimum Confidence
- Aggregate
- Engineering Units
- Resample Interval
- Data Source
Time
Control
Time
Range
Defines an absolute or relative start time, end time, and large and small step sizes.
Defines a relative start time and end time.
To add items to a workspace
…
1) Drag/drop a tag/item from the Browser window onto a folder in the workspace.
Result: The content is available in the workspace.
OR
1) Right-click on a folder in the workspace and select
Add Tag or on a content window and select
Items>New Item.
2) Enter the Item Name and optionally specify item details that you want to save along with the Item
Name. REFERENCE: For descriptions of item
3) Click OK.
Result: The content is available in the workspace.
4) Rename the content appropriately, if needed.
1) Ensure that there is no content named Time-
Control already in the workspace
– if there is, rename it.
2) Drag/drop the From:/To: field on the Time Control to a folder in the workspace.
Result: The content is available in the workspace.
3) Rename the content appropriately, if needed.
1) Ensure that there is no content named TimeRange already in the workspace
– if there is, rename it.
2) Specify relative start time and end time in the Time
Control, if not already present.
3) Right-click a Trend window that is using the Time
Control and select Copy Timespan.
4) Right-click on a folder in the workspace and select
Paste.
Result: The content is available in the workspace.
5) Rename the content appropriately, if needed.
Uniformance - Process Studio User Guide 81
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
Workspace content
Aggregate
Content description
Defines a Reduction
Method and a
Resample Interval.
Data
Source
Trend
Defines a data source
(PHD Server).
Defines a Trend content window.
To add items to a workspace
…
1) Right-click on a folder in the workspace and select
Add Aggregate.
2) Select an Aggregate from the dropdown list.
3) If needed, enter a different Resample Interval in seconds. Default is 60 seconds.
4) Click OK.
Result: The content is available in the workspace.
5) Rename the content appropriately, if needed.
REFERENCE: For definitions of Aggregate and
Resample Interval, see 2.11, "Description of data retrieval properties 'Frequency' and 'Method' ".
1) Right-click on a folder in the workspace and select
Add Datasource.
2) Select a data source from the drop down list.
3) Click OK.
Result: The content is available in the workspace.
4) Rename the content appropriately, if needed.
Note: If not done already, change the name of the trend window to be a name other than the default
"Trend": a. Right-click on the trend window and select
Title>Rename Trend. b. Enter the new name, and then click OK.
Result: The name appears on the window tab.
1) Drag/drop the trend to a workspace folder.
Result: The content is available in the workspace.
82 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.2 Creating the workspace tree structure
Workspace content
Trend
Content description
(continued)
MultiTrend Defines a MultiTrend content window.
To add items to a workspace
…
OR
1) Right-click on the trend window and select Copy.
2) Right-click on a folder in the workspace and select
Paste.
Result: The content is available in the workspace.
Note: If not done already, change the name of the multitrend window to be a name other than the default
"MultiTrend": a. Right-click on the multitrend window and select Title>Rename MultiTrend. b. Enter the new name, and then click OK.
Result: The name appears on the window tab.
1) Drag/drop the multitrend to a workspace folder.
Result: The content is available in the workspace.
OR
1) Right-click on specific chart or anywhere on a
MultiTrend window and select Context>Copy (to copy a specific chart) or Context>Copy All (to copy all of the charts).
2) Right-click on a folder in the workspace and select
Paste.
Result: The content is available in the workspace
- If you selected Copy All, the MultiTrend saves to the workspace.
- If you selected Copy, the single chart saves to the workspace for redisplay in a Trend window.
Uniformance - Process Studio User Guide 83
7 Creating and Managing Workspaces
7.3 Description of Workspace commands
Workspace content
Table
Content description
Defines a Table content window.
To add items to a workspace
…
Note: If not done already, change the name of the table window to be a name other than the default
"Table": a. Right-click on the table window and select
Rename Table. b. Enter the new name, and then click OK.
Result: The name appears on the window tab.
1) Drag/drop the multitrend to a workspace folder.
Result: The content is available in the workspace
OR
1) Right-click on the table window and select
Context>Copy.
2) Right-click on a folder in the workspace and select
Paste.
Result: The content is available in the workspace.
To create a new workspace
Step
1
Action
Before you create a new workspace, save any changes made to the current workspace since the last time you opened Uniformance Process Studio:
Right-click on the white background of the workspace and select Save.
2
To create a new workspace, right-click on the current workspace's top blue bar and select Add Workspace>Add New Workspace.
3
Enter a name for the new workspace and click Save.
4
Drag/drop, copy/paste, or right-click to add content into the new workspace per your requirements, and then right-click on the white background of the workspace and select Save.
84 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.3 Description of Workspace commands
7.3 Description of Workspace commands
The following table describes the commands to manage workspaces.
Table 7
– Commands Used to Manage Workspaces
To perform the following commands:
Right-click on the orange title bar of an unopened workspace.
Or
Right-click on the top blue title bar of the currently open workspace.
Description Command
Add>Add New
Workspace
Add>Add Existing
Workspace
Rename Workspace
Displays the "Save As" dialog box, allowing you to navigate to a local directory or network share and create a new workspace
(<workspacename>.xml file).
Displays the "Open" dialog box, allowing you to navigate to a previously configured workspace (<workspacename>.xml file)
– on a local directory or network share - to add that workspace to the current project.
Displays the "Rename Group" dialog box where you can rename the workspace.
Remove Workspace
Send Workspace To
Displays the "Group Deletion" dialog box which prompts you to confirm deletion of the currently open workspace from the project.
Allows you to email or save a workspace file, so that you can share the content (such as a Trend) with other users.
REFERENCE: For details on how to share workspaces, see section
7.6, "Sharing a workspace with another user ".
Import Workspace
Displays the "Open" dialog box, allowing you to navigate to a workspace (<workspacename>.xml file)
– on a local directory or network share - to load that workspace and add it to the current project.
This command imports a workspace tree structure. Structure may contain content (such as a Trend) that was made available to you by another user through their use of the 'Send Workspace To' command.
REFERENCE: For details on how to share workspaces, see section
7.6, "Sharing a workspace with another user ".
Uniformance - Process Studio User Guide 85
7 Creating and Managing Workspaces
7.3 Description of Workspace commands
To perform the following commands:
Right-click on the white background of the currently open workspace.
Add>Folder
Adds a folder to the root of the workspace tree structure.
REFERENCE: For instructions on arranging folders, see
section 7.4, "Rearranging the workspace tree structure ".
Save
Clear
Saves the workspace tree structure to the
<workspacename>.xml file. The
„Save‟ command provides the user with the option of manually saving work for these reasons:
To be able to share it with other users (through the 'Send
Workspace to' command'.
As a best practice after performing a lot of changes, to ensure that your work does not get lost due to an unexpected abnormal closure of the application.
Note: User changes to workspaces do not get saved automatically until the related content window is closed
– such as a Trend, MultiTrend, Table, or Graphic. All workspaces are saved automatically when you close Uniformance Process
Studio.
Displays the "Reset Workspace" dialog box
– it prompts you to confirm that you want to purge (delete) of all the content in the workspace.
To perform the following commands:
Right-click on the bottom blue bar of the currently open workspace:
Send Workspace(s) to
Load Project
Sends a project (<projectname>.dpr) to an email address or a local or network location.
Displays the "Open" dialog box that allows you to navigate to a project (<projectname>.dpr)
– on a local directory or network location
– and then load that project into Uniformance Process
Studio and replace the current project.
Create New Project
Displays the "Save As" dialog box that allows you to navigate to a local or network location and create a new project
(<projectname>.dpr).
86 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.4 Rearranging the workspace tree structure
7.4 Rearranging the workspace tree structure
You can do the following to change the workspace tree structure:
To move items (drag/drop)
Drag/drop folders and subfolders to a new location.
Drag/drop content items from one folder to another.
To copy items (copy/paste)
Right-click Copy and Right-click Paste content items or folders to a new location
To select multiple items
To select consecutive items, click the first item, press and hold down Shift, and then click the last item.
To select nonconsecutive items, press and hold down Ctrl, and then click each item.
Guidelines for rearranging
A horizontal line indicates the location of the 'drag target' (see the following figure).
To create a parent/child relationship, drag/drop or copy/paste a folder into a folder.
You cannot rearrange individual content items within a folder.
The following figure shows the folder named "New Folder 3" dragged/dropped to its new location as a child in the parent folder named "New Folder 1".
Figure 14
– Folder Drag/Drop Example
Drag/Drop: Result:
Uniformance - Process Studio User Guide 87
7 Creating and Managing Workspaces
7.5 Displaying workspace content
7.5 Displaying workspace content
To display workspace content, the user double-clicks the content item to display it in a window, or drag/drops the item to a location that supports it.
To reuse content that has been saved to a workspace, do any of the following:
Double-click the item to open a new window,
Drag/drop the item to a supported location, or
Right-click>Copy/Paste the item from the workspace to a supported location.
7.6 Sharing a workspace with another user
In brief, the steps to share workspace content with another user are:
Create a workspace and save your content (such as a Trend) to the workspace.
Send the <workspacename>.xml file to the other user - through email or a shared network location.
The other user imports the <workspacename>.xml file into their Uniformance
Process Studio.
Note: You can share multiple workspaces through a single file by adding multiple
workspaces to a Project – then email the project (.dpr) file or place it on a shared resource. The other user opens their Uniformance Process Studio and loads the project.
To make a workspace available to another user
Step Action
1
2
3
Right-click on the workspace that contains the item to be shared.
Select Send Workspace To.
Select either Mail Recipient or My Computer:
Mail Recipient - to email a copy of the <workspacename>.xml file.
My Computer - to navigate to a location on the local drive or a network share where you want to save the <workspacename>.xml file
88 Uniformance - Process Studio User Guide
7 Creating and Managing Workspaces
7.6 Sharing a workspace with another user
Step
4
Action
If you selected Mail Recipient, enter the necessary email address and click
Send:
If you selected My Computer, navigate to the location where you want to save the workspace file and click Save.
Uniformance - Process Studio User Guide 89
7 Creating and Managing Workspaces
7.6 Sharing a workspace with another user
To import a workspace to a user's machine
ATTENTION
Importing a workspace retains the name of the currently open workspace, but replaces its content and tree structure with that of the imported workspace.
For this reason, you may want to create a new empty workspace and give it an appropriate name in preparation for the imported workspace.
Step
1
Action
If the .xml file was received as an email attachment, then save the attachment to the local drive or a network share.
2
3
At the recipient's machine, create a new workspace, if necessary.
Right-click on the top blue bar of the currently open workspace and select
Import Workspace.
4
Navigate to the <workspacename>.xml file that is to be imported, select the file, and click Open.
Result: The content of the current workspace is replaced with the content from the imported file.
90 Uniformance - Process Studio User Guide
8. Managing Windows in Uniformance Process
Studio
8.1 Maximizing the viewing area
You can use the following techniques to maximize screen real-estate in Uniformance
Process Studio:
Minimize the ribbon
Hide windows
To minimize the ribbon
Right-click the ribbon and select Minimize the ribbon.
Or
Double-click any ribbon tab.
Result: The ribbon minimizes to show only its tabs.
To view a minimized menu, click on its tab.
To hide windows
The Navigation and Browser windows can be set to Hide or AutoHide mode.
Right-click>Hide - The window remains completely hidden until you select the application on the Home menu.
Right-click>AutoHide - The window slides off the main window, but shows its title in an area along the outside of the main window. The window remains hidden until you move the mouse over the title.
You can click the push pin icon to toggle Auto-hide mode:
Click icon to "unpin" the window and allow it to auto-hide.
Click icon to "pin" the window and turn off AutoHide.
Uniformance - Process Studio User Guide 91
8 Managing Windows in Uniformance Process Studio
8.2 Creating and modifying tab groups
8.2 Creating and modifying tab groups
By default, content windows are stacked into a single tab group. You can create additional tab groups in various arrangements, as illustrated in the following figure.
Figure 15
– Tab Group Examples
Single tab group
Horizontal tab groups
Vertical tab groups
92 Uniformance - Process Studio User Guide
8 Managing Windows in Uniformance Process Studio
8.2 Creating and modifying tab groups
To rearrange tabs within a tab group
Drag the tab left or right:
To create a new tab group
Right-click the tab that you want to place into a new tab group, and then choose either
New Horizontal Tab Group or New Vertical Tab Group.
To move a tab to a different tab group
Right-click the tab and select Move to Next Tab Group or Move to Previous Tab
Group.
Uniformance - Process Studio User Guide 93
8 Managing Windows in Uniformance Process Studio
8.2 Creating and modifying tab groups
To create a new tab group through drag/drop
Drag a tab until you see a grey box that indicates the arrangement you want:
94 Uniformance - Process Studio User Guide
8 Managing Windows in Uniformance Process Studio
8.3 Repositioning the Browser and Navigation windows
8.3 Repositioning the Browser and Navigation windows
You can reposition the Browser and Navigation windows in Uniformance Process Studio
using arrow guides that appear when you drag the window (as shown in Figure 16).
The window freely flows horizontally or vertically as you drag it, and then repositions and resizes when you drop it. A gray box indicates the new position and size (as shown
Figure 16
– Repositioning the Browser and Navigation Windows
Uniformance - Process Studio User Guide 95
8 Managing Windows in Uniformance Process Studio
8.3 Repositioning the Browser and Navigation windows
96 Uniformance - Process Studio User Guide
9. Providing the Configuration for Uniformance
Process Studio
9.1 Overview of configuration
With access to the Options command (shown in Figure 17), users can customize the
following configuration of Uniformance Process Studio:
Application Defaults
Periods
Relative Times
Standard Times
Data Sources
Figure 17
– Accessing the Configuration
Uniformance - Process Studio User Guide 97
9 Providing the Configuration for Uniformance Process Studio
9.2 Configuring data sources
The configuration is saved to an .xml file.
CAUTION
Do not directly edit the configuration file or it may become unusable.
Always use the Options command to edit configuration.
Note: Table 8shows the default configuration supplied by Honeywell.
9.2 Configuring data sources
The initial installation of Uniformance Process Studio provides a default data source. To change data source configuration, perform the following steps.
Step
1
Action
In Uniformance Process Studio, click the button in the upper left corner, and then click Options.
2
In the resulting Options dialog box, expand Desktop Configuration, and then expand Data Sources.
3
Do one of the following:
Right-click Data Sources and then choose New Data Source
Click on an existing data source and then right-click Copy/Paste it to Data
Sources.
Click on DefaultPHD to modify the default data source.
4
Result: The data source property page is displayed.
Enter the configuration. Refer to the following table for definitions.
98 Uniformance - Process Studio User Guide
9 Providing the Configuration for Uniformance Process Studio
9.2 Configuring data sources
Field
General
Name
Table 8
– Definition of Data Source Configuration Fields
Definition Default
Description
Type
Server name
This is the unique name used to identify the data source. Where data sources are shown in the applications, this is the setting that is shown.
This setting is used to provide additional information for the user to identify the data source.
It is used in various tool tips and information boxes.
Specifies the type of data source that is being configured. This value affects what method is used to retrieve data and what other settings are prompted for on this form:
PHD
– PHD Server
OPC
– OPC HDA Server (future)
This is the name of the server used by applications to connect and retrieve data from a server. Either a server name or an IP address can be put into this box.
For a data source of type PHD, the value
PHD_HOST can be used to indicate that the
PHD_HOST environment variable should be used.
In this case, if the PHD_HOST system environment variable does not already exist, you must create it and set its value to be the host name of the server.
DefaultPHD or
PHDDataSource
<blank>
PHD
PHD_HOST
PHD Specific
Port
Specifies the port number used by applications to connect and retrieve data from the configured data source. Numbers in the range 1 to 65535 are valid for this field. If you clear the text in this box, the default setting is used.
The effective default depends on the selected PHD
API Type:
Port 3100 if PHD API Type is Api200
Port 3150 if PHD API Type is RemoteApi200
(Default)
Uniformance - Process Studio User Guide 99
9 Providing the Configuration for Uniformance Process Studio
9.2 Configuring data sources
Field
PHD API Type
Prompt for PHD username / password
Prompt for
Windows username / password
Definition
Specifies the PHD API to use when connecting to this data source:
Api200
– This type of API uses the local Windows logon account to connect to the named PHD
Server, which must be running release R200 or greater.
RemoteApi200
– This type of API allows the user to enter a Windows domain account
(domain\username and password) to connect to the named PHD Server (for example, because the local logon account is in a different and untrusted domain or behind a firewall).
Used if the named PHD Server has tag security implemented; and therefore will require the user to provide a PHD username and password for permission to access data.
False
– The user will not be prompted to authenticate against the PHD system. PHD access will be determined by the local Windows logon account.
True
– When an application first attempts to connect to this data source, the user will be prompted to enter a user name and password to authenticate against the PHD system.
Applies only to the PHD API type of
RemoteApi200.
Specifies whether the Process Studio user will be prompted to provide a Windows username and password to connect to this data source.
False
– When an application first attempts to connect to this data source, the user will not be prompted to enter a Windows username and password.
True
– When an application first attempts to connect to this data source, the user will be prompted to enter the user name and password of a valid Windows account recognized by the PHD
Server.
Default
Api200
False
False
100 Uniformance - Process Studio User Guide
9 Providing the Configuration for Uniformance Process Studio
9.2 Configuring data sources
Field
Browse server
Browse server
Port
Definition
Not implemented. Should remain blank.
Not implemented.
Default
<blank>
Note: If the value of a data source field is displayed in bold, it means that the value has been changed from the default setting.
Step
5
Action
(Optional) To test the connection to the data source, click Test Data Source.
6
Depending on the configuration, you may be prompted to enter user credentials. If prompted, enter the user credentials.
A message indicates whether or not the connection was successful.
If the connection was not successful, do the following:
Verify that you selected the correct Data Source.
Click Test Data Source to attempt another connection.
If you are prompted for user credentials, ensure that you enter valid user names and passwords.
If the connection is still not successful, refer to the log file at:
C:\Documents and Settings\ <logon username>\ Application Data\
Honeywell\ Common Desktop Framework\ CDF.log
7
After a successful connection test, click OK to close the Options window.
8
In the tag/item Browser window, the Data Source drop down list displays the data sources.
TIP:
The Test Connection does not cache any required user credentials, so the user must reenter them upon initial use of the tag/item Browser.
Guidelines for configuring access to PHD through the remote API
If you configure a data source of type RemoteAPI200 and set the PHD user name/password to False and the Windows user name/password to False, then you must enable anonymous access (blank logons) through a registry setting on the PHD Server.
The Browser in Uniformance Process Studio uses PHD security credentials to access tags/items from a PHD Server - unlike Tag Explorer in the legacy Uniformance Desktop, which used Oracle security through an Oracle ODBC connection.
Uniformance - Process Studio User Guide 101
9 Providing the Configuration for Uniformance Process Studio
9.3 Creating a custom time period
With anonymous access enabled, the 'Uniformance Remote API Server uses its service credentials to connect to the PHD Server. If you do not enable anonymous access, the
'Test Data Source' command succeeds and the Browser successfully displays tags/items for the data source, but when you attempt to add a tag/item for the data source to a content window (such as a Trend), it displays an "Access Denied" security error.
Registry setting on PHD Server to allow blank logons:
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\
RAPIServer\Parameters\ "PreventBlankLogons"=dword:00000000
Note: After you add the registry key on the PHD Server, you must restart the
'Uniformance Remote API Server' Windows service to have the change take effect.
REFERENCE
For more information, refer to the PHD System Manual (pim0301), section
"Some Registry Keys That May Be added By the System Administrator".
9.3 Creating a custom time period
To create a custom time period
Step
1
Action
In Uniformance Process Studio, click the button in the upper left corner, and then click Options.
2
In the resulting Options dialog box, expand Desktop Configuration, and then expand Periods.
3
4
Right-click Custom and then select New Period.
Enter the properties for the new period and then click OK.
REFERENCE: For definitions of the time-related properties, refer to section
6.3, "Viewing/adjusting the time control properties " in this guide.
102 Uniformance - Process Studio User Guide
9 Providing the Configuration for Uniformance Process Studio
9.4 Changing the application defaults
9.4 Changing the application defaults
To access the application defaults
Step
1
Action
In Uniformance Process Studio, click the button in the upper left corner of the main window, and then click Options.
2
In the resulting Options dialog box, expand Desktop Configuration, and then expand Application Defaults.
You may change the application defaults to suite your personal preference.
Figure 18
– Application Defaults
Uniformance - Process Studio User Guide 103
9 Providing the Configuration for Uniformance Process Studio
9.4 Changing the application defaults
Enable performance optimization
Under the Performance section of the Application Defaults is the "Enable performance optimization" property.
When set to True, the "Enable performance optimization" property causes the Trend to improve performance by reducing the amount of data displayed and or retrieved, as follows:
Aggregate data uses an adjusted sample frequency to request and return the configured maximum number of data points for a trace.
RAW data uses a down-sampling mechanism to reduce the number of data points displayed for a trace. The down-sampling mechanism returns first, last, maximum, minimum, and first null point within each sample.
The "Enable performance optimization" property is enabled (True) by default, and it only applies to the Trend - it does not apply to MultiTrend and Table.
To create custom colors
Step
1
Action
In the Application Defaults, select the item for which you want to create a custom color:
Border color,
Minimum confidence color, or
Trace colors
104 Uniformance - Process Studio User Guide
9 Providing the Configuration for Uniformance Process Studio
9.5 To change the printer
Step
2
Action
Click the drop-down arrow and select the Custom tab (see following figure).
Right-click on the one of the bottom 16 custom colors on the color selector.
3
Microsoft's color picker displays. Pick a color and click Add Color.
Result: The new custom color is selected.
5
Click OK to accept the configuration.
Uniformance - Process Studio User Guide 105
9 Providing the Configuration for Uniformance Process Studio
9.5 To change the printer
9.5 To change the printer
Perform the following steps if you want to print to a printer other than your machine's default printer.
Step
1
Action
Click the down arrow beside the Print button on the ribbon of the window you want to print.
2
3
4
5
From the dropdown menu, select Preview.
In the resulting Print Preview window, click File>Page Setup.
In the resulting Page Setup dialog box, click Printer.
Select the printer that you want and click OK.
106 Uniformance - Process Studio User Guide
10. Troubleshooting and Servicing Uniformance
Process Studio
10.1 Viewing logs
Step
1
2
Action
In the main window of Uniformance Process Studio, click the Desktop button, as shown in the following screen.
In the resulting dialog box, click Options, as shown in the following screen.
3
4
5
In the resulting Options dialog box, select Logs.
At the bottom of the Options dialog box, click View Log.
Result: The log displays in the Log Viewer window.
Click OK to close the Options dialog box.
Uniformance - Process Studio User Guide 107
10 Troubleshooting and Servicing Uniformance Process Studio
To re-initialize, remove, or edit invalid tags/items
10.2 To re-initialize, remove, or edit invalid tags/items
When tags/items have issues on load, invalid tag, or invalid data source, you get an error message and the tag/item is not added to the window or the Trend properties table – however, the window retains invalid tags/items in its context.
To remove the errors, do the following:
Perform the re-initialize command to attempt to connect and remove errors:
Right-click on the window and select Items>Re-Initialize Items.
Manually remove or correct invalid tags/items:
Right-click on the window and select Items>Edit or Remove
To correct a tag/item, select Edit and then select the tag/item to edit.
To delete a tag/item, select Remove, and then select the tag/item to remove.
108 Uniformance - Process Studio User Guide
Glossary
Collector
A software interface (and hardware, if needed) that performs data collection from a source system such as a DCS.
Common Times
Common Times is a status in Uniformance Process Studio that allows the user to toggle between a common (master) time control and Local time controls. Common Times mode locks and synchronizes the windows together. A single Time Control user interface is used to set time-related properties. When not in Common Times mode, the user can independently control time-related properties for data requested in each content window.
Context
Each item that you store in a workspace has properties that are referred to as its
"context".
Data Source
A historian (such as PHD) that collects and stores process data and supports data retrieval by clients like Uniformance Process Studio.
Link
A collector to a Honeywell Experion source system.
Mimic
A display that depicts a physical representation of a system and presents information at the level of physical function of a system. Mimic displays use pictorial realism to show important components or systems to help users detect and diagnose faults. Mimics may consist of line graphics and schematic symbols to represent process elements, or may consist of digital photographs of the process equipment overlaid with animated symbols.
Uniformance - Process Studio User Guide 109
Glossary
Parent
A PHD tag from which other PHD tags may inherit configuration.
Period
'Period' is the portion of time for which the user requests display of data. Also referred to as time span and time range
PHD API
Application Program Interface for PHD.
RDI
Real-time Data Interface. A type of collector for the PHD system used to collect data from a source system for storage in the PHD database. PHD includes several types of
RDIs, and others are available from Honeywell for many types of DCS, PLC, SCADA, and other real-time sources of data.
Remote API
Remote Application Program Interface for PHD. Supports access to a PHD Server through a firewall or in a domain that does not have a trust relationship with the domain where the client is located.
Ribbon
Uniformance Process Studio uses the ribbon instead of toolbars – this is similar to
Microsoft Office 2007. The ribbon helps you quickly find the commands that you need to complete a task. Commands are organized in logical groups which are collected together under tabs. Each tab relates to a type of activity, such Trend and Table. To reduce clutter, some tabs are shown only when needed. For example, the Trend tab is shown only when a trend window is open.
Tag/Item
A data item - a distinct value maintained in the PHD database. A PHD interface collects most tag values from a source system. A data item may be a calculated value or a manually entered value. Tag Name and Item Name are used interchangeably.
110 Uniformance - Process Studio User Guide
* 17
? 17
<reduction> .............................................. 44
Aggregate ................................................. 34
All Items ................................................... 16
Annotations ............................................... 41
Application Defaults
Change Printer .................................... 106
Create ............................................ 17, 103
Create Custom Colors ......................... 104
Average..................................................... 44
Browser..................................................... 14
Changing Trends....................................... 43
Charts
Save MultiTrend ................................... 49
Collectors .................................................. 16
Colors
Custom ................................................ 104
Common Times .................................. 22, 72
Configuration ............................................ 97
Configuring Data Sources......................... 98
Create MultiTrend .................................... 48
Create Tab Groups .............................. 65, 92
Current Time ............................................ 19
Index
Custom Time Period ............................... 102
Customize a Tag/Item ............................... 33
Data Source ............................................... 34
Connect to a .......................................... 14
Data Source Fields
API200 ................................................ 100
Browse Server ..................................... 101
Browse Server Port ............................. 101
Description ............................................ 99
Name ..................................................... 99
PHD API Type .................................... 100
PHD Password .................................... 100
PHD Username ................................... 100
Port ........................................................ 99
RemoteAPI200 .................................... 100
Server Names ........................................ 99
Type ...................................................... 99
Windows Password ............................. 100
Windows Username ............................ 100
Delta .......................................................... 44
Display
HMIWeb Graphic ................................. 58
HTML Document .................................. 58
Web Page .............................................. 58
Uniformance - Process Studio User Guide 111
Drag/Drop Zones
Graphic ................................................. 65
Enumerated ............................................... 34
Error Message ......................................... 108
Fetch ......................................................... 15
Fields and Buttons
Time Control ......................................... 69
Filter Data
Table ..................................................... 53
First ........................................................... 44
Formats
Histogram ............................................. 28
Multiple Y Axis .................................... 26
Single Y Axis ........................................ 25
Strip Chart ............................................. 25
XY ........................................................ 27
Forward and Backward ............................. 21
Frequency ................................................. 44
Frequency and Method ....................... 44, 82
Graphic
Adding .................................................. 64
Create New ..................................... 61, 63
Drag/Drop Zones .................................. 65
Features ................................................. 57
Honeywell International
Process Solutions
2500 West Union Hills Drive
Phoenix, AZ 85027
USA
Importing ............................................... 64
Print ....................................................... 64
Time Control ......................................... 67
Graphic Window ....................................... 57
Hairline...................................................... 36
Hide Windows ........................................... 91
Histogram .................................................. 28
Histogram Angorithm ............................... 29
Histogram Statistics .................................. 30
HMIWeb ................................................... 57
HMIWeb Graphic
Create New ............................................ 61
Display .................................................. 58
Edit ........................................................ 62
HTML Document
Display .................................................. 58
Invalid Tags/Items
Edit ...................................................... 108
Re-initial .............................................. 108
Remove ............................................... 108
Item Details ............................................... 34
Item Name Like......................................... 17
Last ............................................................ 44
Licensed Option ........................................ 62
Logs .................................................. 16, 107
Maximum ................................................. 45
Method ...................................................... 44
<reduction>........................................... 44
Average ................................................. 44
Delta ..................................................... 44
First ....................................................... 44
Last ....................................................... 44
Maximum ............................................. 45
Minimum .............................................. 45
Raw ....................................................... 44
Regression Constant ............................. 45
Regression Deviation ............................ 45
Regression Slope .................................. 45
Snapshot ............................................... 44
Standard Deviation ............................... 45
Minimum .................................................. 45
Minimum Confidence ............................... 34
Modify Tab Groups ............................ 65, 92
Multiple Y Axis ........................................ 26
MultiTrend
Create .................................................... 48
Description ........................................... 47
Hairline Cursors .................................... 49
Save Charts ........................................... 49
View Properties .................................... 49
View Trend Window ............................. 49
New Trends ............................................... 43
Null Value Replacement ........................... 34
Offset ........................................................ 35
Open a Window ........................................ 18
Opening ..................................................... 13
Parent Tags................................................ 16
Parents ....................................................... 16
Performance .............................................. 17
Period ........................................................ 20
PHD Data
Manual Input/Edit ................................. 55
Play ........................................................... 21
Printer
Change ................................................ 106
Properties
View MultiTrend................................... 49
Raw ........................................................... 44
Refresh ...................................................... 20
Regression Constant .................................. 45
Regression Deviation ................................ 45
Regression Slope ....................................... 45
Relative Time Syntax ................................ 76
Remote API ............................................. 101
Resample Interval ..................................... 34
Search ........................................................ 17
Uniformance - Process Studio User Guide 113
Single Y Axis ............................................ 25
Snapshot.................................................... 44
Specify Item Details ................................. 33
Aggregate .............................................. 34
Data Source ........................................... 34
Enumerated ........................................... 34
Item Name ............................................ 34
Minimum Confidence ........................... 34
Null Value Replacement ....................... 34
Resample Interval ................................. 34
Units...................................................... 34
Standard Deviation ................................... 45
Statistics .................................................... 39
Strip Chart ................................................. 25
Synchronize .............................................. 22
Tab Groups
Create .............................................. 65, 92
Modify ............................................ 65, 92
Table
Add ....................................................... 52
Create .................................................... 52
Description ............................................ 51
Filter Data ............................................. 53
PHD data ............................................... 55
Honeywell International
Process Solutions
2500 West Union Hills Drive
Phoenix, AZ 85027
USA
Save ....................................................... 52
View PHD Tag/Item Configuration ...... 56
Tag/Item Configuration ............................. 56
Time Control ............................................. 19
Fields and Buttons ................................. 69
Properties .............................................. 73
View/Adjusting ....................... 21, 73, 102
Time Control Field/Button
From and To .......................................... 69
Large Step Back Button ........................ 70
Large Step Forward Button ................... 70
Play Button ............................................ 71
Properties Button ................................... 71
Refresh Button ...................................... 71
Slider Control Button ............................ 70
Small Step Back Button ........................ 70
Small Step Forward Button ................... 70
Time Control Field/Button
Period .................................................... 69
Time Control Properties Field
Cancel Button ........................................ 75
Current Time ......................................... 75
Fast Replay ............................................ 75
From/To ................................................ 74
Large Step ............................................. 75
OK Button ............................................ 75
Period .................................................... 74
Refresh Interval .................................... 75
Small Step ............................................. 75
Time Period
Create Custom .................................... 102
Time Ranges ............................................. 35
Trend
Create .................................................... 31
Properties .............................................. 41
Trend Window
View MultiTrend .................................. 49
Trends
New, Viewing, Changing ..................... 43
Troubleshooting
Error Message ..................................... 108
Invalid Tags/Items .............................. 108
View Logs .................................... 16, 107
Uniformance Process Studio..................... 97
Units ......................................................... 34
Usernames .......................................... 14, 15
Viewing Trends ........................................ 43
Web Page
Display .................................................. 58
Wildcard ................................................... 17
Windows
AutoHide ............................................... 91
Hide ....................................................... 91
Workspace
Available to Another User .................... 88
Commands ............................................ 85
Create New ............................................ 84
Create Tree Structure ... 17, 32, 35, 49, 52,
64, 79
Display Content..................................... 88
Import .................................................... 90
Rearranging Tree Structure ....... 79, 86, 87
Save Table ............................................. 52
Sharing ............................................ 85, 88
Tree Structure .... 17, 32, 35, 49, 52, 64, 79
Types ..................................................... 78
Workspace Commands
Add Existing Workspace....................... 85
Add Folder ............................................ 86
Add New Workspace ............................ 85
Clear ...................................................... 86
Create New Project ............................... 86
Import Workspace ................................. 85
Load Project .......................................... 86
Remove Workspace .............................. 85
Rename Workspace ............................... 85
Save ....................................................... 86
Uniformance - Process Studio User Guide 115
ดาวน์โหลด
โฆษณา