Algorithmic system
Algorithmic system
for fire detection and control
aguilera
electronica
Contents
What are algorithmic central units?
Types of algorithmic central units
Control station
Telecontrol and remote control programme for installations
Connectivity
Algorithmic detectors and advantages
Modules of the algorithmic system
Special equipments
Complementary equipments
Software tools
2
3
4
5
6
7
8
9
10
11
1
What are
algorithmic
control panels?
2
Algorithmic, micro-processed control panels manufactured by AGUILERA ELECTRONICA
and certified according to the European standards EN 54-2 and EN 54-4,
with extensive operational capability that allows you to individually control all computers
that make up the installations for fire detection.
Common characteristics to all the series:
• Detection loops with independent microprocessor for the control of 125 groups each
one of them, to which are connected the detectors, push buttons, switches, input/output modules,
controls and any other element that makes up the installation.
Depending on the model of equipment, it can mean the control of more than 1000
independent points (one module of 8 inputs can monitor individually 8 identifiable
signals).
• Allows the connection of CLASS A loops: closed loop with independent isolators of
input and output, and CLASS B loops: open-loop output isolator.
Available in models for 1, 2 and up to 8 detection loops.
• Switched power supply, expected to cover the needs of both, of the central unit and
of the installation.
• Emergency battery charger.
• CPU module, where the installation is customized, the output manoeuvres are
scheduled and the information is managed.
Its main features are:
• Non-volatile memory of events, with capacity for 4000 events.
• Real time clock.
• Complete control of operation of all equipment that makes up the installation in
a manual or programmed form: resets, repositions, levels, connection / disconnection
of points, evacuation activations /deactivations, closing of lock-gates and firewalls.
• Delays can be schedules according to the EN54-2 norm.
• DAY / NIGHT modes automatically configured by using programmable timing.
• Output of warning to fire-fighters with programmable activation times: Time for
recognition and investigation time, according to the NEN2535 norm.
• Tests and test modes are built for each zone.
• It permits multiple working languages.
• Comprehensive management of historic lists between two dates and the status
of the zones.
• Graphical display of 240x64 points.
• Control keyboard.
• Illuminated signs and a local buzzer, for the presentation of the general service
states, alarm, fault, disconnection, test, power supply, evacuation manoeuvres’'92
status and others.
• Evacuation embedded outputs (monitored outputs), alarm (fire-fighters), prealarms
and faults.
• 2 communication ports series RS232 or RS485 Interface, user selectable.
• 1 serial communication port RS485 Interface, with ARCNET protocol, optional
to work with the Aguilera AE2NET network.
• Incorporated series printer port.
• Optional TCP network port, through an AE/ SA-TCP card, for remote control of
the central unit, via Ethernet networks.
Algorithmic central units
Algorithmic control panel of 1 loop AE/SA-C1
Panel for fire control with capacity for 1 loop of 125 equipments each, to
which the detectors, switches, modules for manoeuvres, for control and other
elements that make up the installation, all connect.
• Switched power supply of 27.2 Vdc at 2 A.
• Emergency battery charger with capacity for receiving two 12V /7Ah batteries.
• Dimensions: Height: 274 - Width: 322 – Depth: 123 mm
Algorithmic control panel of 2 loops AE/SA-C2
Panel unit for fire control with a capacity for a AE/SA-CTL of 2 loops of 125
equipments each, to which the detectors, switches, modules for manoeuvres,
for control and other elements that make up the installation, all connect and
with a capacity to control 250 devices.
• Switched power supply of 27.2 Vdc at 4 A.
• Emergency battery charger, where the central unit has the capacity to
receive in its interior, two 12V/ 7Ah batteries.
• Dimensions: Height: 410 - Width: 310 – Depth: 120 mm
Algorithmic control panel of 8 loops AE/SA-C8
Panels for fire control with bus for connecting with 1 to 4 cards AE /SA-CTL.
Each card controls two bidirectional algorithmic loops, with a capacity for
125 equipments each, to which the detectors, switches, modules for
manoeuvres, for control and other elements that make up the installation,
all connect.
• The control's panels capacity to control equipment is up to 1000 devices
and depending on the type it can mean controlling more than 3000 independent
points. For every 250 devices the central unit is equipped with an independent
microprocessor.
• Independently switched power supply of 27.2 Vdc at 4 A.
• Emergency battery charger, where the central unit has capacity for receiving
in its interior, two 12V/17Ah batteries.
• Dimension: Height: 500 - Width: 390 – Depth: 145 mm
Remote
controlled
unit
AE/SA-TCR
Remote controlled unit manufactured by AGUILERA ELECTRONICA,
developed for monitoring and remote management of the fire protection
facilities, based on our new algorithmic control panels.
This terminal allows to control "at a distance" via cable (RS-485) any
installation based on AE/SA-C1, AE/SA-C2 and AE/SA-C8 central units.
The connection is made in a network, through a RS-485 communication
channel. All the control panels show the general status of all the central
unitsexisting in the network and from any of them, any central unit can
be controlled.
It has an independent power source and capacity for two 7 Ah batteries.
3
Graphic Control Station
Europe III Graphic Control Station has been developed to
boost the capacity, management and presentation of information
for fire protection installations.
The system consists of a graphic software installed in the
Control Station computer and Algorithmic Control panel in the
series SA connected to the computer through a port RS-232,
RS-485 or TCP/IP.
Algorithmic control panels in the series SA are subordinated
to the management carried out from the Control Station, but
without loosing autonomy at any moment, even in the case
of loss of communication with the Control Station, each control
panel continues controlling is installation.
description
The system allows us to see detailed information of each element
in the installation in real time. This information is shown in several
windows: installation plan windows, system event window, sector
window…
We can act on the installation points from any window and through
the mouse: connect/disconnect points, request of information
about its state, activate/deactivate operation sequences, restore
the installation, reading of each detector state…
The installation can be represented through plans generated on
bit maps of any size and number of colours. The installation active
elements (control panels, points, sectors, sequences) can be
placed on this plans in such a way that the state changes are
immediately shown on them, and the Control Station user can
also have a global view of the state of each area in the installation
just with a quick look at the associated plan.
features
• Graphic representation of the whole installation allowing for the
use of key plans per fire sectors.
• Buttons for easier actions can be defined in each plan such as:
silencing warning tones, restoring alarms, changing the system
operation mode, skipping to specific plans…
• Skip to a plan associated to an automatic alarm configurable
by the user.
• Full operation of the system through the mouse or keyboard.
• Access to the Control Station functions by persons not involved
in the system can be limited though keys as well as assigning
each user his/her operation through the assignation of levels.
• Background list of each incidence produced in the installation
and its evolution.
• Symbols for active elements fully definable by the user.
• Operation under Windows environment.
• Easy and intuitive Software in order to customize the installation.
connectivity
Each algorithmic central unit is provided with communication
ports RS232 and RS485 in order to connect with the Control
Station.
If required, connection can be executed through protocol TCP/IP
through the existing net in the installation.
4
• Sound warnings for incidences through a sound card and system
speakers.
• Graphic bookshop editor which allows the Control System user
to make customized image bookshops, which will be used in
the Control Station for drawing the plan active elements.
Installation
panels remote
control software
System which allows for remote control and management of
fire detection installations. The remote control system provides
important advantages as well as remote maintenance of the
ones which are currently working.
The system allows for remote control of any installation, based
on the series SA central units. It consists of a control software
AGE44 which allows to show the front panel of the control
panel on the computer monitor and perform any action on the
panel as if we were in front of it.
It is especially intended for controlling: hotel chains, shopping
centres, car parks and facilities where remote control from a
different place where the control panel is located, is needed.
For example: place for the maintenance central unit,
headquarters, etc.
In the installation monitoring mode, any incidence produced
in one of the monitored control panel generates a warning
signal which allows us to connect with it for consults or
operations.
The system admits many possibilities for connection networks:
• Ports series, RS-232 and RS-485.
• AE2NET Network.
• Ethernet
• INTERNET via TCP/IP.
Remote
control of
installations
AGUILERA ELECTRONICA software development providing
control for the Fire Protection Installations based on Europe
III and/or Europe II Graphic Control Stations.
We are allowed to:
• Create and maintain an installation database, each one
managed by a control station.
• Monitor the state of installations defined in the database,
showing the state of each one in real time.
• Control any monitored installation in a remote way as if we
were in front of it.
Connection between applications and remote installations is
made by using TCP/IP communications. In this way, we have
access to installations provided with this type of communications,
independently from its geographical position.
5
Connectivity
fire detection network system
There are different classifications for the connection of the control and
supervising units which are part of the installation:
AE/SA-TCR
AE/SA-C8
Red AE2NET
AE/SA-C8
AE/SA-IDC
RS-485
Max. 1.200 m
AE/SA-III
AE/SA-TCR
AE/SA-III
AE/SA-C8
AE/SA-C2
AE/V-C485R
AE/SA-C8
AE/V-C485R
AE/V-C485R
Red ETHERNET
Tarjeta Red
Ethernet
ETHERNET Network
Connection of up to 128 central units via TCP/IP with an EUROPE III control
station, on a LAN network (local area network) or a WAN network (broadband
network) ETHERNET 10/100Mhz, as an ADSL line can provide.
Aguilera microserver RS-485-TCP/IP, model AE/V-C485R should be provided
to each central unit.
AE/SA-III
AE/SA-C8
AE/SA-C2
AE2NET Network
AE2NET network is based on ARCNET local network technology
The following characteristics stand out:
• Robustness and speed (312 Kbps).
• Interface: RS-485.
• Allows for simultaneous connection of series SA central units, relay stations
and many control stations, up to 31 nodes, which allows the capacity of
30000 equipments.
• Allows integration with control systems of other companies (open protocol).
• Each control station is to be provided with a communication interface AE/SAIDC.
AE/SA-C8
Red RS-485
Series RS-485 or RS/232 Networks
With this type of networks, top simplicity is achieved regarding configuration
and installation by using the communication ports the new central units are
provided with as standard.
• Interface RS-485: Up to 31-node connection on twisted pair or fibre optic.
• Interface RS-232: Direct connection via series with the central unit.
Convertidor
RS-485 / RS-232
Communication Interface
AE/SA-III
6
AE/SA-IDC
AE/SA-GAT
AE/SA-ILW
Multi-protocol module that permits
the integration of the algorithmic
control panel of Aguilera
Electrónica in different control
systems. Supported protocols:
Modbus/RTU, N2 Metasys,
Aguilera Electronica and ESPA
4.4.4
It has the following interfaces:
• RS232
• RS485
• RS485/ARCNET for connection
to the AE2NET network of
Aguilera Electronica.
Interface of communications
TCP/IP Multiprotocol module that
permits the integration of the
algorithmic control panel of
AGUILERA ELECTRONICA in
different control systems.
Supported protocols: Modbus /
RTU / TCP, N2 of Metasys and
ESPA 4.4.4
It has interfaces:
• RS232
• RS485
• Ethernet
The AE /SA- ILW gateway
converts the dump protocol,
Aguilera Electronica´s series,
to a LonWorks protocol. The main
use of the device is to connect
the central algorithmic units in a
LON network.
This equipment is based on the
3150 NEURON chip at 20 Mhz
with topology free at 778Kbit/s
(FTT-10). DIN rail mounting. The
serial communications are done
through one of the RS-232 ports
of the algorithmic control panel.
Algorithmic detectors
Smoke optical detectors
Aguilera Electrónica directionable optical detectors manage a smoke optical
detector. It is aimed at taking light measures diffusing smoke particles, evaluating
its density and increase percentage throughout the time, then, already analyzed
information is sent to the central unit and this central unit compares the results
obtained with the programmed parameters for each case and decides to send
the alarm signal.
At Aguilera Electrónica we have three types of algorithmic
optical detectors:
AE/SA-OP optical detector.
AE/SA-OPZ, optical detector with alarm warning device.
AE/SA-OPI, low-profile optical detector.
Heat detector
Aguilera Electrónica AE/SA-T algorithmic heat detector
manages two temperature parameters, a differential one
taking temperature increase measures in time, and a
fixed one controlling the room temperature detected at
every moment. Both differential and fixed parameters
are analyzed and sent to the control panel so that the
alarm warning is produced in accordance with the
programming carried out in each case.
Optical-heat detector
The optical/heat detector made by Aguilera Electrónica
AE/SA-OPT is a multi-sensor detector with double
technology managing a smoke optical sensor and a heat
optical sensor. The optical sensor is aimed at taking light
measures diffusing smoke particles and its increase
while the heat sensor takes measures for heat variations.
Both measures are analyzed and sent to the control
panel so that the alarm warning is produced if
programmed parameters for each case are reached.
Algorit Algorithms
Signal received by a smoke detector in clean air may vary due to pollution
effects, dirty environments or punctual presence of smoke (smokers’ room).
The range of smoke detectors in the Algorithmic system are provided with
the ALGORIT adjustment algorithms which compensate such drift in order
to maintain a more constant response value throughout the time, within
the permitted limits.
Through the combination of two independent sensors: photoelectric sensor
and temperature sensor, the multi-sensor detector AE/SA-OPT makes the
alarm decision through the processing of both signals, in a faster way.
These signal processes allow us to discriminate the non-wanted alarms
once and for all.
Advantages of
the detectors
• Solution for slow smoke: Present smoke
detectors have difficulties when detecting slow
smoke with no flames in closed rooms. The
origin of the problem is in the resistance the
air offers when coming out from the optical
chamber of the detectors, preventing from the
inflow of smoke, an indispensable function
for the smoke to be detected. Optical detectors
AE/SA-OP and OPT in this system, solve this
problem through the development of natural
ventilation based on an internal airwell
communicating the inside of the optical
chamber with the casing upper part not in
contact with the ceiling, creating the “chimney
effect” which makes the air exchange easier.
• Automatic adjustment of sensitivity:
Algorithmic application that compensates for
dusty and polluted environments maintaining
the margin between stand-by and alarm, to
acceptable levels; from such levels detectors
require to be cleaned or replaced.
• Intelligence shared with the central unit: In
this function the micro capacity for each
detector is used so that sampling is managed
and analyzed information is sent. In this way,
higher efficiency is achieved and
communications are more powerful and fluent.
• Hidden base: This new feature eliminates
the view of joints between the base and the
ceiling creating the idea of a suspended
detector.
• Detectors with alarm buzzer: They are
presented in two different options, with or
without built-in buzzer. The option with buzzer
is recommended for blind people’s houses
and bedrooms.
• Auto isolator: Each detector, manual call
point and modules in the system are provided
with auto isolator, a device that, in case of
short-circuiting in an equipment, disconnects
the equipment with such problem so that the
rest of the equipment is not affected.
7
Modules of the algorithmic system
Master modules
Adressable microprocessed unit controlling a loop with detectors, manual call
points and other conventional devices. Suitable for controlling areas of conventional
detectors or pushbuttons in places where intelligent detectors are installed.
The following models are available:
AE/SA-M: Suitable for an area of conventional detectors.
AE/SA-MC5 Suitable for an area of conventional detectors C5.
AE/SA-MDL Suitable for the control of a linear smoke detector.
Input Modules
Adressable microprocessed units manufactured in accordance with the standard
EN 54-18 managing information from digital inputs.
AE/SA-2EV: For controlling 2 monitored inputs
AESA-2E: For controlling 2 inputs
AE/SA-8E: For controlling 8 inputs
AE/SA-EM Mini module for 1 input
Output modules
Adressable microprocessed units manufactured in accordance with the standard
EN 54-18 managing information from outputs.
AE/SA-2SV: For controlling 2 monitored outputs
AE/SA-SE: Provided with 1 output and 1 input
AE/SA-SEV: 1 output and 1 watched input
AE/SA-SE230: Output with relay at 230V
AE/SA-32S: 32 outputs for synoptic
AE/SA-1SVM: Miniature module 1 monitored output
Loop insolator module
Microprocessed unit manufactured in accordance with the standard EN 54-17,
controlling the current in the loop and if it increases over the programmed
parameters, opens the line isolating the rest of the loop so that it continues
working.
AE/SA-AB Line isolator module
Algorithmic sounders
Sirens with low multi-tone consumption, certified in accordance with EN 54-3,
a microprocessed module for direct integration in the algorithmic loop is built-in.
8
AE/SA-AS1 Algorithmic sounder
AE/SA-ASA Algorithmic sounder with isolator
AE/SA-ASF1 Algorithmic sounder and beacon
AE/ASF1A Algorithmic sounder and beacon with isolator
Special equipments
Special equipments
Extinguishing Control Panel
AE/SA-PX2
• 2 monitored detection zones.
• Operating mode, programmable as:
• Double detection: Two alarms in one zone.
• Crossed detection: One alarm in every zone.
• Mixed: Two alarms in the panel.
• Monitored detection zone for push button to trigger the
fire extinction.
• Monitored entry zone for an extinction pause button.
• Buttons for extinguishing the fire and pausing extinction
built into the panel.
• 2 independent monitored inputs for pressure monitoring
or control of weighing and flow control.
• Monitored output for evacuation and for fire extinguishing
poster.
Power supplies
AE/SA-FA y AE/SA-FA2
Short-circuitable switched-mode power supply of 24Vdc
/ 5A and 2A manufactured according to the EN 54-4
standard.
Bitension 230/115 V AC, 50/60Hz. Equipped with luminous
indications on the general state of power supply, status
and charge of the batteries and of the output fuses, as of
EN 54-4 norm. They have 2 independent outputs protected
against short-circuits.
Equipped with a micro-processor card, which keeps
permanently the central algorithmic unit informed of its
status.
Batteries:
• AE/SA-FA (5A) has the capacity for 2 batteries 12V/17Ah.
• AE/SA-FA2 (2A) has the capacity for 2 batteries 12V/7Ah.
Address programmer
AE/SA-PRG
Portable device indicated for programming the identification
code number of each algorithmic device.
With a simple process we can:
• Record the direction of the device.
• Read the stored address.
• Individually inhibit /allow the flash of Led to the device.
The process of individual programming of each device
can also be carried out from the algorithmic central unit
itself.
negative
Algorithmic
loop
positive
Example for installation
• 2-thread loop cable: Positive and negative
• Connection of all the equipments in the same
loop
• Programming in the central unit. Control
operations: Evacuation and warning,
Sectorization, Transmission, Extinguishing
system, …
Algorithmic loop, acoustic signalling, negative,
positive, detector loop, batteries for fire
extinguishing systems with continuous weighting
system.
Acoustic
signalling
Extinguishing Extinguishing
release
stop pushbutton
Detector's loop
9
Additional equipment
10
Additional equipment
Repeater Panel
AE/SA-PR32
Panel manufactured by AGUILERA ELECTRONICA,
consisting of 32 LEDs for realtime representation of the
status of the installation, and the FULL-DUPLEX
intercommunication between the Repeater Panel and the
fire control panel. It’s ideal for nurses’ stations and other
surveillance areas.
Its main features are:
• 1 point within the loop.
• Programming of multiple installation points for each
indicator light.
• It allows individualized personalization of the text
associated to each indicator light.
• Alarm buzzer of the zones.
• Snooze alarm relay, with output via voltage free contacts
(NO and NC) and by voltage (24 V CC).
• Test push buttons for indicating lights, buzzer and relay.
• Blocking light switch for the buzzer and relay.
Wires
AE/MANG2R0HC
AE/MANG2RF30C
Wires 2X1,5 free of halogens (AE/MANG2R0HC)
It meets EN 50265, EN 50266, EN 50267, EN 50268, all
norms. The hose is halogen free, is flame retardant & does
not spread the fire. Mod.AE/MANG2R0H of 2 conductors
(2 x 1,5 mm2 ) shielded with an aluminium tape and
polyester cover, approved for the algorithmic system and
supplied in reels of 100 meters and on request, in larger
coils.
Fire-resistant wire (AE/MANG2RF30C)
Hose of identical specifications to the previous one.
It meets EN 50200 norm: fire resistant.
Optical detector
for ducts
AE/SA-OPIC
Equipment manufactured by AGUILERA ELECTRONICA,
formed by an AE/SA-OPI optical algorithmic detector and
a metal box, fitted with an alarm indication lamp, fitting for
the entrance of cables and fittings for probe ducts, which
take the samples from inside the ducts.
Software tools
Commisionning Software AGE 41
The objective of the commisioning software AGE41 is to
facilitate tuning and the maintenance of the installations based
on the central Algorithmic system.
Under a Windows environment, it allows us to:
• Determine what devices are connected to what control panel
and in each loop.
• Check the status of each one of them (rest, alarm and fault).
• Act over the outputs of these devices
• Export the structure of the channels to files, which the AGE42
customizer can read later.
• Obtain information on any incidents that are occurring at the
facility.
• Monitor the general overall functioning of the central unit,
using diagnostics.
• Reboot and download the statistical information stored in
the central unit.
In short, the program permits to check the status of a facility,
without the need for customized central units.
Customizer AGE 42
The AGE42 Customizer is software developed under the
Windows, which we can use to create new customizations, as
well as to edit and modify existing customizations.
This program allows us to perform, in a simple manner, the
following operations:
• Create new customisations, defining the texts to be assigned
to each of the zones and sectors of the installation.
• Capture the personalization of the connected central units.
• To dump the personalization of the connected central units.
• Import channel structures as created through the
implementation program AGE41
• Verify the data integrity of the personalization.
• Define the installation plans for their use in the "Europe III"
checkpoint, defining the active installation points, so that their
status changes are automatically reflected in the plans.
• List the personalization data from the screen and printer,
through various types of reports.
• Define sectors.
• To program automatic or manual control manoeuvres, in
terms of various logical combinations (And, Or, Multiple Or)
for any point, zone or sector of the installation.
11
Our commitment: services and guarantees
Projects
Grupo Aguilera offers engineering companies its support
in the detection, control and extinguishing of fires advising
on systems and covering for each building. The project
department develops
The system design and dimensioning, hydraulic
calculations, diffusers calibration and installation isometric
advising on the effectiveness of the units in each risk and
setting out the operating capacity .
Trainig
Aware of the need to know and control what we are doing,
apart from the technical support provided to the installations
where our products are used, Grupo Aguilera offers
training courses on our equipment performance, installation
and programming.
Customer service
At Grupo Aguilera each customer is important, we are
aware of the different needs for each customer, this is
the reason why our team of experts offers customized
service meeting your requirements.
Mantenance
Grupo Aguilera commits itself to offering services on
repair, reprogramming and original spare part supply after
the guarantee period.
Technical support
With the aim of guaranteeing the correct operation of
the installations, Grupo Aguilera Technical department
carries out the operation and start-up test of the units,
apart from collaborating with the installer in all the steps.
Once the system is installed with the suitable power and
water supply, and the hydraulic test has been previously
carried out, Grupo Aguilera technical staff carries out
the operation test and the start-up of the units.
Equipment guarantee
Grupo Aguilera guarantees the correct performance of
the equipments for 2 years since the delivery date: we
are responsible for the replacement and repair of the
equipments where anomalies or manufacturing faults are
observed and are delivered from our factory in Madrid.
8
te
o
m ic Sy
s
m
Al g
rit h
CENTRAL OFFICE
C/ Julián Camarillo, 26 - 2ª planta - 28037 MADRID • Tel: 91 754 55 11 - Fax: 91 754 50 98
GAS PROCESSING UNIT
Av. Alfonso Peña Boeuf, 6. P. I. Fin de Semana - 28022 MADRID • Tel: 91 312 16 56 - Fax: 91 329 58 20
GALICIA OFFICE
C/ José Luis Bugallal Marchesi Nº 9, 1º B - 15008 A CORUÑA • Tel: 98 114 02 42 - Fax: 98 114 24 62
CATALONIA OFFICE
C/ Rafael de Casanovas, 7 y 9 - SANT ADRIA DEL BESOS - 08930 BARCELONA
• Tel: 93 381 08 04 - Fax: 93 381 07 58
VALENCIA OFFICE
Avda. Mediterránea 46, San Juan de Enova - 46669 VALENCIA
• Tel: 628 92 70 56 - Fax: 91 754 50 98
ANDALUSIA OFFICE
C/ Industria, 5 - Edificio Metropol 3, 3ª Planta, Mod. 17. P.I.S.A. 41927 Mairena del Aljarafe - SEVILLA
• Tel: 95 465 65 88 - Fax: 95 465 71 71
www.aguilera.es • e-mail: comercial@aguilera.es
Edición 03/12