EMI R-410A - S1CG/S1HG & S2CG/S2HG Installation & Operation Manual

Add to My manuals
40 Pages

advertisement

EMI R-410A - S1CG/S1HG & S2CG/S2HG Installation & Operation Manual | Manualzz

S1CG/S1HG Single-Zone

S2CG/S2HG Dual-Zone

Side-Discharge Ductless Split-System

Condensing Units for R410 Refrigerant

9,000

2.6

Capacities — Single-Zone Applications

S1CG or S1HG S1CG only

12,000 18,000 24,000 28,000 33,600

3.5

5.3

7.0

8.3

Capacities — Dual-Zone Applications

S2CG or S2HG

10.5

9,000

2.6

12,000

3.5

Units

Btuh kW

Units

Btuh kW

Installation, Operation and

Maintenance Manual

S1CG

S1HG

ECR International LLC

2201 Dwyer Ave

Utica, NY 13504 www.enviromaster.com

S2CG

S2HG

An ISO 9001-2000 Certified Company

P/N 240007754, Rev.

C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Contents

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Verify unit before installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Refrigerant Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Operation Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Operation and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Single-zone and Dual-zone Condenser Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Single-zone and Dual-zone Condenser Sequence of Operation,

Testing Defrost Operation Using Test Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Specifi cation and Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Test Unit Performance Data Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

EMI’s Product Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

NOTICE

Shipping Damage

Shipping damage MUST be reported to the carrier IMMEDIATELY.

Examine the exterior. Remove cover and examine compressor and piping for signs of damage.

Inspect each component for damage.

Concealed damage must be reported to the carrier within 15 days of the receipt of the shipment.

on the delivery receipt of all damage identifi ed and complete a carrier inspection report.

national’s Customer Service Department of all damage and is responsible for fi ling any necessary claims with the carrier.

Customer Service : (800) 228-9364

NOTICE

To the Installer

Retain this manual and warranty for future reference. Before leaving the premises, review this manual to be sure the unit has been installed correctly and run the unit for one complete cycle to make sure it functions properly.

To obtain technical service or warranty assistance during or aft er the installation of this unit, contact your local representative. For a local representative listing, visit our web site:

www.enviromaster.com

For further assistance call:

1-800-228-9364

When calling for assistance, please have the following information ready:

Model Number _____________

Serial Number _____________

Date of installation ___________ and is tested and rated in accordance with AHRI Standard 210/240-2008 and UL-1995.

Due to ongoing product development, product designs and specifi cations may change without notice. Please contact the factory for more information.

Comfort where it counts

2

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Read Before Proceeding

Recognize this symbol as an indication of important safety information.

WARNING

Completely read all instructions prior to assembling, installing, operating, or repairing this product.

Inspect all parts for damage prior to installed ONLY by qualifi ed installation personnel.

DANGER

Tampering with this unit is dangerous

. Tampering voids all warranties.

DO

NOT

att empt to modify or change this unit in any way.

DANGER

• Be connected to a properly grounded electrical supply with the proper voltage as stated on the rating plate.

• Have proper over current protection

(i.e. time-delay fuse/HACR Breaker) as listed on the rating plate.

Failure to follow these instructions can result in a fi re, explosion, or electrical shock causing property damage, personal injury, or death.

Safety Instructions

fi ed service personnel for proper installation, operation, and maintenance of the

EMI series high efficiency condensing unit. Read these instructions thoroughly and carefully before att empting installation or operation. Failure to follow these instructions may result in improper installation, operation, service, or maintenance, possibly resulting in fi re, electrical shock, property damage, personal injury, or death.

Read all instructions before using this unit. Install or locate this unit only in accordance with these instructions. Use this unit only for its intended use as described in this manual.

Check the rating plate on the unit before installation to make certain the voltage shown is the same as the electric supply to front panel only.

This unit must be connected only to a properly grounded electrical supply. Do not fail to properly ground this unit.

Turn off the electrical supply before servicing the unit.

Do not use the unit if it has damaged wiring, is not working properly, or has been damaged or dropped.

P/N 240007754, Rev. C [3/19/2010]

3

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Verify unit before installing

Product description

S2HG condensing units are air-cooled, vertiunits designed specifi cally to meet or exceed a 13 SEER rating.

09–24 condensing units will provide cooling and heating for a single air handler, as identifi ed on page 34 and page 35 .

Controls and components

(Factory-installed or supplied)

Compressor and fan motor contactor

Run capacitor

Low voltage terminal connections

H.P.S. (High pressure switch) with manual external reset

Heat pump hard start

Cooling operation down to 32°F standard on all units

Models 09–12 only:

– Large capacity suction accumulator

Solid-core fi lter drier

Thermostatically-controlled crankcase heater (heat pump only) and 24,000 (22) Btuh capacity condensing units will provide cooling and heating for two air handlers, as identifi ed on page 36 .

The S1CG/S1HG and S2CG/S2HG are quiet units that can be recommended for both commercial and residential applications.

Features

Installation of the S1CG/S1HG and

S2CG/S2HG condensing units is simplifi ed by a 24v control interconnection from the air handler.

Multiple units can be lined up in close proximity to an exterior wall.

Service valves are recessed to reduce tampering.

All 9,000-12,000 Btuh units are equipped with a Duratec Performance Package that includes an oversized suction accumula-

Thermostatically-controlled crankcase heater

• This feature energizes the crankcase heater only when needed, saving unnecessary power usage and increasing overall

• management and a factory-installed solid core fi lter drier.

A factory-installed crankcase heater is standard on S1HG 09 &12 (thermostatically controlled) and S2HG models, and is available as optional equipment on other models.

Comfort where it counts

4

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Verify unit before installing

(continued)

System options

Corrosion-resistant coil options (sea coast and harsh environment usage):

– Copper fi n/copper tube condenser coil

Low Ambient controls for cooling operation down to 0°F (standard equipment can operate down to 32°F)

Coated aluminum fin/copper tube condenser coil

Optional field-installed kit, when specifi ed, for cooling operation down to 0°F — kit includes control, louvers and wind baffle plus installation instructions

Low Ambient controls for operation down to 0°F (consult factory for availability)

Models 09–12 only:

– 115v (single-zone only — S1CG or

S1HG)

– Field-installed thermostatically-controlled crankcase heater for straight cool units (S1CG or S2CG) Recommended for operation below 60°F.

Installer-supplied items

Power wiring

Low Volt wiring (18 awg minimum)

Secure mounting pad or foundation

Refrigerant piping (if not purchased from

EMI)

High Volt Disconnect

Refrigerant for charging interconnect piping (see charge table on page 15 )

NOTICE

Low Ambient controls

are required when the system is asked to cool at outdoor temperatures below 32°F, this may cause damage to the compressor and coil, and may void the warranty. A field-installed low-ambient kit allows operation down to 0°F.

This is accomplished by cycling the condenser fan on and off. This will, in turn, maintain a constant low-side pressure, providing a steady cooling eff ect and keeping the air handler from frosting-up.

baffle, crankcase heater, outdoor fan cycling switch, and installation instructions.

P/N 240007754, Rev. C [3/19/2010]

5

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Mounting the Unit

Before installing, consider:

Locate the unit as close to the indoor section as possible. (see page 11 .)

S1CG/S2CG — If the unit is used for low ambient cooling down to 32°F, S1CG/

S2CG require CCH.

Avoid high traffic areas and prevailing wind locations.

Surface must be fl at and level.

Mount unit above typical snow fall level.

This is particularly important for heat pump applications (S1HG/S2HG).

2. In areas of heavy snowfall, condensers should be set above the maximum anticipated snow line (12" is usually adequate for most locations).

Unit Mounting Instructions

Model S1CG is shown for example in the following sequence.

NOTICE

Ensure free fl ow of air through the unit.

Air must not recirculate from discharge to intake — air is drawn through the coil and side discharged through the fan grille.

A minimum 48” clearance is necessary for the condenser discharge.

Rear intake (coil side) clearance is

12” minimum.

Consider how power will be run to the unit from the power source.

Refrigerant piping should be a direct line to the indoor unit.

mounting through the feet. This is highly recommended due to the vertical design of the unit.

1. Figure 1, Page 7 :

– Bullet 1 — Loosen the screws on left and right sides of the front panel. (Do not remove these screws.)

– Bullet 2 — Remove the screws on the front of the panel.

2. Figure 2, Page 7 :

Slide front panel forward to clear side screws and remove.

3. Figure 3, Page 7 :

Insert lag bolts through the holes in the bott om of the unit and tighten to secure.

4. Figure 4, Page 7 :

Insert lag bolts through the holes in the feet on the back of the unit and tighten to secure.

5. Replace the front panel, do not tighten the side screws at this time.

Site preparation

1. Place the unit on a fl at concrete surface or pad if on the ground. Roof mounting should use a built up platform to avoid intake of hot air from the roof.

Comfort where it counts

6

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Mounting the Unit

(continued)

Figure 1

Remove front panel screws

Figure 3

Bottom lag hole locations

D E

1 2

Figure 2

Remove front panel

A

C

E

Lag bolts

Compressor

Capacitor

B

D

Figure 4

Lag holes in feet

Filter drier

Accumulator

P/N 240007754, Rev. C [3/19/2010]

7

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Electrical Wiring

NOTICE

All electrical wiring must be run according to NEC and local codes.

1. Figure 5, Page 8 — Refer to the unit rating plate for voltage, minimum circuit ampacity and over current protection requirements.

2. Use only HACR type breakers or time delay fuses. Select the wire size according to the ampacity rating.

3. To access electrical connections and wiring diagram: a. Figure 6, Page 8 — Remove the screws on the side panel that covers

Figure 5

Rating plate location

4. to the back panel and denoted with electrical connections.

b. c. should already be loose (don’t remove them).

Slide the side panel out to access the high/low electrical connections and wire diagram.

d. Figure 7, Page 9 — Add water-tight strain relief fi tt ing to the high volt side before wiring, a split grommet fi tt ing has been factory installed in the low volt side.

Power should be run to a weather proof disconnect box usually within 3 feet of the unit.

Figure 6

Remove side panel screws

Comfort where it counts

8

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Electrical Wiring

(continued)

5. Figure 8, Page 9 — From the disconnect box, run the power through the 7/8” hole on the side of the unit and into the electrical box. Anchor with the strain relief fi tt ing.

Figure 7

Power entrances

6. Run wires to the high volt pigtail in the control box and att ach L1 and L2 connections. Also run green wire to ground wire.

7. Check wiring diagram for the required number of low voltage wires to be run between indoor and outdoor sections.

8. Figure 9, Page 9 — Connect the 24 volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and also refer to the wiring diagram on the indoor unit. Low volt interconnect should be at least 18 awg.

Figure 8

High voltage connections

9. See Figure 10, Page 10 and Figure 11,

Page 10 for completed wiring of S1CG and S2CG examples.

10. To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel.

11. Fasten all remaining loose screws.

Figure 9

Low voltage connections

Continued on next page

P/N 240007754, Rev. C [3/19/2010]

9

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Electrical Wiring

(continued)

Figure 10

Completed wiring, S1CG

Figure 12

Replacing side panel

Figure 11

Completed wiring, S2CG

Figure 13

Fasten loose screws

Comfort where it counts

10

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Piping

Tubing specifi cations

the inside unit as listed in Table 1, Page 11 . tions and are equipped with refrigerant valves and Schrader fi tt ings for charging and taking pressure readings.

P-trap installation

A P-trap is recommended when the suction riser is equal to or greater than show in Figure 14, Page 11 and Table 1,

Page 11.

When the condenser is installed above the air handler, the P-trap will help the return of oil back to the compressor.

CAUTION

It is recommended that a

fi lter drier

be installed in the liquid line, at the indoor unit on models without a factory-installed fi lter drier (i.e. 18K and larger).

Figure 14

P-trap placement (see Table 1,

Page 11 for dimensions H & P)

Table 1

S1CG/S2CG tubing specifi cations (see Table 14, Page 11 )

Model Max.

Length

Equivalent

Feet

Max.

Lift

“H”

09

Max.

Trap

Height

Liquid

Line

Suction

Line

“P” O.D.

O.D.

12

18

24

30

36

50’

(15 m)

100’

(30 m)

20’

(6 m)

15’

(5 m)

35’

(11 m)

20’

(6 m)

1/4" 1/2"

1/4" 1/2"

3/8" 5/8"

3/8" 3/4"

3/8" 3/4"

3/8" 3/4"

A P-trap may be fabricated using (2) street elbows and (2) regular elbow.

A prefabricated trap may be purchased from a wholesaler or distributor however the trap should be shallow as with the (3) elbow confi guration.

Each elbow is approximately 2 equivalent feet.

One P-trap is equal to approximately

12 equivalent feet.

P-traps are not required at the foot of the hot gas risers due to increased oil fl ow at higher temperatures.

P/N 240007754, Rev. C [3/19/2010]

11

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Piping

(continued)

CAUTION

• Avoid piping on wet and rainy days.

• Use only clean, refrigeration-grade copper tubing.

• Use tubing benders to guard against kinking.

• Be certain no burrs remain on the fi tt ings.

• Cap ends of lines until ready for connections.

• Be certain that plastic end caps remain in place when inserting through wall openings.

• Insulate the suction line.

• Isolate tubing from transmitt ing vibration to the building or unit and avoid contact with sharp edges.

• Wrap refrigeration valves with a wet rag “heat sink” to protect valves while brazing. (See Figure 16, Page 12 .)

Figure 15

Clean ends of tubing

Figure 16

Wet rag “heat shield over valves

Refrigerant piping

1.

2.

3.

Clean the ends of tubing and insert into fi tt ings ( Figure 15 ).

Protect valves by wrapping with a wet rag

“heat sink” before brazing ( Figure 16 ).

Use a shield to protect the paint as shown

Figure 17

Make a shield to protect paint

4.

5. from scrap metal.)

Braze tubing into fi tt ings.

Install all panels removed to this point.

Panels are required for proper air fl ow.

Comfort where it counts

12

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Processing

Charging the unit

1. Att ach manifold set, vacuum pump, &

Micron Gauge. ( Figure 18 ).

2. Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks (Figure 19).

3. Once certain of a good evacuation and leak free joints, back-seat the valves

(counter-clockwise) to open and allow factory charge to fi ll lines and indoor unit

(Figure 20, pg. 13).

Figure 18

Manifold set connections at unit

NOTICE

4.

Refer to refrigerant charge table for specifi ed charge.

Charge to proper weight, charge based on feet of interconnect (see tables on

page 15 ). Only add/remove 410A in liquid form.

5. Refer to charts beginning on page 17 to

“fi ne tune” the refrigerant charge to meet your conditions.

Figure 19

Manifold set up for evacuation

CAUTION

All systems require fi eld charge adjustments. Refer to the “Refrigerant Charge

Tables” for proper weight charge and to the supplied “Single-zone Operation

Charts” for proper system pressures and temperature at diff erent outdoor conditions. Superheat should be used for fi nal system charge.

A

C

Manifold

Micron gage

Figure 20

Charging

B

Vacuum pump

CAUTION

Charging should be done with a dial-acharge or weighed in with a scale.

When charging and checking pressures/ temperatures on system supplied with

Low Ambient Option, the fan cycle switch should be jumpered out of the circuit temporarily to obtain accurate data.

P/N 240007754, Rev. C [3/19/2010]

13

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Processing

(continued)

WARNING

It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods & equipment when installing or servicing this unit.

The units are delivered pre-charged with refrigerant for the condenser coil and the air handler. Charging of the fi eld installed piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconnect piping. Unit service valves are solid brass, for sweat connections.

CAUTION

Pressure test

all fi eld installed piping with nitrogen. Using a suitable vacuum pump, evacuate the tubing and indoor unit to 500 microns or less, with service valves remaining front seated (closed).

Before releasing the refrigerant from the condenser, be sure the manifold gauge set is closed so as not to lose vacuum when shutt ing down the pump.

Release refrigerant from the condensing unit by back seating the service valve. Allen wrenches are used to open the valve.

Replace valve caps. DO NOT back seat the valves past the snap fl anges that hold the valve core in place.

NOTICE

in electrical specifi cations and system combinations.

WLH09 = UNH09

WLH12

WLH24

WLC30

=

=

=

UNH12

UNH24

UNC30

WLC36 = UNC36

Comfort where it counts

14

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Processing

(continued)

NOTICE –

to fi nd charge adjustment

1. To fi nd the charge adjustment and system charge for any air handler and tubing length:

Line Adjustment = (Line Charge/FT) x Line Length

System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

Table 2

S1CG/S1HG refrigerant charge table

Condenser

S1CG9

S1CG2

Air handler pairing

CAH09

CAH12

S1CG8 CAH24

S1CG4

S1CG3

S1CG6

CAH24

CAC36

CAC36

S1CG9 WLH09/UNH09

S1CG2 WLH12/UNH12

S1CG8 WLH24/UNH24

S1CG4 WLH24/UNH24

S1CG3 WLC30/UNC30

.64 oz/ft

(59 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

Line charge per foot

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

Factory charge

39.5

33.75

65.25

63.0

97.5

80.0

39.5

33.75

65.25

63.0

97.5

Condenser

Air handler pairing

S1HG9 WLH09/UNH09

S1HG2 WLH12/UNH12

S1HG8 WLH24/UNH24

S1HG4

WLH24/UNH24

S1HG9 CAH09

Line charge per foot

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

.25 oz/ft

(23 g/m)

S1HG2

S1HG8

S1HG4

CAH12

CAH24

CAH24

.25 oz/ft

(23 g/m)

.64 oz/ft

(59 g/m)

.64 oz/ft

(59 g/m)

Factory charge

51.3

45.75

63.0

74.0

51.3

45.75

63.0

74.0

P/N 240007754, Rev. C [3/19/2010]

15

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Refrigerant Processing

(continued)

NOTICE –

to fi nd charge adjustment

1. To fi nd the charge adjustment and system charge for any air handler and tubing length:

Line Adjustment = (Line Charge/FT) x Line Length

System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

Table 3

S2CG/S2HG refrigerant charge table

Condenser

S2CG99

S2CG22

Air handler pairing

(2) WLHG09

(2) WLHG12

S2CG92 WLHG09+WLHG12

S2CG99

S2CG22

UNHG09

UNHG12

S2CG92 UNHG09+UNHG12

Line charge per foot

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

Factory charge

44/44

39/39

44/39

44/44

39/39

40/39

Condenser

S2HG99

S2HG22

Air handler pairing

(2) WLHG09

(2) WLHG12

S2HG92 WLHG09+WLHG12

S2HG99

S2HG22

UNHG09

UNHG12

S2HG92 UNHG09+UNHG12

Line charge per foot

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

.25 oz/ft

(23 g/m)

Factory charge

44/44

39/39

44/39

44/44

39/39

44/39

Comfort where it counts

16

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

Cooling Cycle

Model S1CG9000 & S1HG9000 with EMI's-WLH09 & UNH09 (R-410A Ref.)

Cooling Cycle

Model S1CG9000 & S1HG9000 with EMI's-CAHG09 (R-410A Ref.)

550

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

490

550

490

310

250

170

430

370

150

130

110

85 ° F

80 ° F

75 ° F

90

35

25

15

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

310

250

170

430

370

150

130

110

85 ° F

80 ° F

75 ° F

90

35

25

15

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

17

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Cooling Cycle

Model S1CG2000 & S1HG2000 with EMI's-WLHG12 &UNHG12 (R-410A Ref.)

Cooling Cycle

Model S1CG2000 & S1HG2000 with EMI's-CAHG12 (R-410A Ref.)

550

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

490

550

490

430

370

310

250

170

150

130

110

85 ° F

80 ° F

75 ° F

90

35

25

15

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

310

250

170

430

370

150

130

110

90

35

25

15

5

65

85 ° F

80 ° F

75 ° F

75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

18

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Cooling Cycle

Model S1CG8000 &S1HG8000 with EMI's-WLHG24 &UNHG24 (R-410A Ref.)

Cooling Cycle

Model S1CG8000 & S1HG8000 with EMI's-CAHG24 (R-410A Ref.)

550

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

490

550

490

310

250

170

430

370

150

130

110

85 ° F

80 ° F

75 ° F

90

35

25

15

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

310

250

170

430

370

150

130

110

90

35

25

15

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

19

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Cooling Cycle

Model S1CG4000 &S1HG4000 with EMI's-WLHG24 & UNHG24 (R-410A Ref.)

Cooling Cycle

Model S1CG4000 & S1HG4000 with EMI's- CAHG24 (R-410A Ref.)

550

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

490

90

35

130

110

25

15

5

65

310

250

170

150

550

490

430

370

85 ° F

80 ° F

75 ° F

75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

310

250

170

430

370

150

130

110

85 ° F

80 ° F

75 ° F

90

35

25

15

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

20

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Cooling Cycle

Model S1CG3000 with EMI's-WLCG30 & UNCG30 (R-410A Ref.)

Cooling Cycle

Model S1CG3000 with EMI's-CACG30 (R-410A Ref.)

550

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

490

550

490

430

370

310

250

170

150

90

35

25

15

130

110

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

430

370

310

250

170

150

90

35

25

15

130

110

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

21

Made in the USA

550

490

430

370

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Cooling Cycle

Model S1CG6000 with EMI's-CACG36 (R-410A Ref.)

Cooling Cycle

Model S1CG6000 with EMI's-WLCG36 (R-410A Ref.)

Room Temp ( °F)

Relative Humidity 50%

550

Room Temp ( °F)

Relative Humidity 50%

490

310

250

170

150

90

35

25

15

130

110

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

90

35

25

15

130

110

5

65

310

250

170

150

430

370

85 ° F

80 ° F

75 ° F

75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

22

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Heating Cycle

Model S1HG9000 with EMI's- WLHG09 & UNHG09 (R-410A Ref.)

Heating Cycle

Model S1HG9000 with EMI's- CAHG09 (R-410A Ref.)

Room Temp ( °F)

Relative Humidity 50%

380

350

Room Temp ( °F)

Relative Humidity 50%

380

350

130

110

90

70

20

10

50

30

0

10

260

230

320

290

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

230

130

110

90

320

290

260

20

10

70

50

30

0

10

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

23

Made in the USA

380

350

230

130

110

90

320

290

260

20

10

70

50

30

0

10

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Heating Cycle

Model S1HG2000 with EMI's- WLHG12 & UNHG12 (R-410A Ref.)

Model S1HG2000 with EMI's- CAH12 (R-410A Ref.)

380

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

350

320

290

260

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

70

50

30

20

10

0

10

110

90

230

130

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

24

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Model S1HG2000 with EMI's- WLHG12 & UNHG12 (R-410A Ref.)

Model S1HG2000 with EMI's- CAH12 (R-410A Ref.)

380

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

350

320

290

260

230

130

380

350

70

50

30

20

110

90

10

0

10

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

320

290

260

70

50

30

20

10

0

10

110

90

230

130

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

25

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Model S1HG8000 with EMI's- WLHG24 & UNHG24 (R-410A Ref.)

Model S1HG8000 with EMI's- CAH24 (R-410A Ref.)

380

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

350

320

290

260

230

130

380

350

70

50

30

20

110

90

10

0

10

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

320

290

260

70

50

30

20

10

0

10

110

90

230

130

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

26

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone Operation Charts

(continued)

Model S1HG4000 with EMI's- WLHG24 & UNHG24 (R-410A Ref.)

Model S1HG4000 with EMI's- CAH24 (R-410A Ref.)

380

Room Temp ( °F)

Relative Humidity 50%

Room Temp ( °F)

Relative Humidity 50%

350

320

290

260

230

130

380

350

70

50

30

20

110

90

10

0

10

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

320

290

260

70

50

30

20

10

0

10

110

90

230

130

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

27

Made in the USA

Cooling Cycle

Model S2CG & S2HG 9,000 BTU Circuit with EMI's-WLHG12 &UNHG12 (R-410A Ref.)

550

490

430

370

Room Temp ( °F)

Relative Humidity 50%

130

110

90

35

25

15

170

150

310

250

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Multi-zone Operation Charts

Cooling Cycle

Model S2CG & S2HG 12,000 BTU Circuit with EMI's-WLHG12 &UNHG12 (R-410A Ref.)

550

490

430

370

Room Temp ( °F)

Relative Humidity 50%

130

110

90

35

25

15

170

150

310

250

85 ° F

80 ° F

75 ° F

5

65 75 85 95 105

Outdoor Temp ( ° F)

Note: Minimum compressor superheat 5 ° F

115

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Comfort where it counts

28

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Multi-zone Operation Charts

(continued)

Heating Cycle

Model S2CG & S2HG 9,000 Circuits with EMI's- WLHG09 & UNHG09 (R-410A Ref.)

380

350

Room Temp ( °F)

Relative Humidity 50%

230

130

110

90

320

290

260

20

10

70

50

30

0

10

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

Heating Cycle

Model S2CG & S2HG 12,000 Circuits with EMI's- WLHG12 & UNHG12 (R-410A Ref.)

380

350

230

130

110

90

320

290

260

20

10

70

50

30

0

10

Room Temp ( °F)

Relative Humidity 50%

75 ° F

70 ° F

65 ° F

20 30 40

Outdoor Temp ( ° F)

50 60

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

P/N 240007754, Rev. C [3/19/2010]

29

Made in the USA

Starting the Unit

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Operation and Maintenance

9,000– 12,000 Btuh units

In low ambient cooling, if a crankcase heater is installed,

power the system 24 hours before attempting to start

the unit in cool weather

(below 60°F).

Test unit data sheet

Aft er doing a fi nal system check using the

Operation Charts (supplied on previous pages).

Record results on Test Unit Data Sheet on page 38 .

Before leaving

Remove gauge set, install caps. Mount all access panels and make sure they are properly secured.

Make fi nal visual inspection and repair any defi ciencies.

NOTICE

A hard start kit may be required for units in low voltage applications.

sections are the compressor bearing units of the system. It operates at the command of the the system operation will be described in the manual pertaining to the indoor section.

EMI units are designed and constructed for reliability and long life with minimal maintenance. You can assure peak operating passage into and through the coil. If debris collects on the air coil, it should be cleaned by “back-fl ushing” with a spray of water or vacuuming.

TURN OFF POWER SUPPLY

FIRST

. Outdoor units may be cleaned or waxed if desired. Use a non-abrasive car wax

(on metal surfaces only).

This unit is equipped with a permanently lubricated motor. Although oiling is not necessary, adding a few drops through the oiling ports twice yearly will extend the life of the motor. Do not over oil.

Panels should remain on the unit at all times.

Service should be performed by a

qualifi ed service agency only

.

Specifi c changes

All EMI products are subject to ongoing development programs so design and specifi cations may change without notice. Please consult the factory for more information.

Comfort where it counts

30

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone and Dual-zone Condenser Sequence of Operation

EMI Series condensers are designed to operate with EMI Series air handlers. Both the condenser (outdoor unit) and air handler (indoor unit) have a high volt service connection. Each is to be independently connected to the electrical service panel. (See the unit name plate for the reversing valve will energize (R & O heat pumps only) along with the compressor and outdoor fan (R & Y). When the indoor control is satisfi ed and the room temperature falls below the set temperature, the compressor and fan will indoor units are also connected to each other through a low volt interconnect wiring. A 24v transformer located in the indoor unit provides the low volt power source.

Straight cool condensers are designed to operate as a single stage cooling unit. Heat pump condensers are designed to operate as a single stage cooling two stage heating unit. For proper operation the unit must be matched with an appropriate EMI indoor unit with unit mounted controls and/or wall mounted thermostat. For two-stage heating operation the indoor unit must be equipped with an electric strip heater.

will prevent the compressor from re-starting for three minutes.

Heating operation

Heating operation requires that the control

(either unit mount or remote wall mount, heat pump thermostat) make a connection between low-Volt terminals “R” and “Y” only. When the indoor control is placed in heating mode, with the set point temperature above room temperature, the compressor and outdoor fan (R

& Y) will energize. When the indoor control is satisfi ed and the room temperature rises above the set temperature, the compressor and fan will

NOTICE

will prevent the compressor from re-starting for three minutes.

For remote wall mounted thermostat operation be sure to select EMI p/n

240008209 or a suitable 24v, two stage heating, heat pump thermostat.

Defrost controls with short cycle protection (heat pumps only)

designed to keep system operating at peek ef-

Condenser operation

The transformer located in the indoor unit provides 24v, low-volt control power to the the indoor and outdoor systems including a three minute, anti-short cycle timer (ASCT) compressor protection. across low-volt terminals “R” and “C”.

Heat pump condensers utilize a reversing valve the condenser coil free from frost and ice during the outdoor unit will act as either a condenser or an air handler there-by providing comfort cooling or heating to the indoor space. The reversing valve is energized in cooling. Should the valve fail to actuate, the system will default to the heating mode of operation.

precise switching sequence of the outdoor fan, reversing valve and indoor auxiliary heater.

Defrost initiation

Cooling operation, single- and dual-zone

Cooling operation requires that the control

(either unit mount or remote wall mount thermostat) make a connection between low-volt terminals “R” and “Y” along with “R” and “O”

(heat pumps only). When the indoor control is placed in cooling mode, with the set point temperature below the room temperature, the

P/N 240007754, Rev. C [3/19/2010] plate or the return bend of the condenser coil.

A defrost cycle will initiate after the sensor closes (approx. 30°F) and remains closed for the length of time selected on the control board

(either 30, 60 or 90 minutes)*.

*Factory sett ings 9–24k Btu = 90 minutes

At the start of the defrost cycle, the reversing valve will change from heating to cooling mode.

31 allowing pressure and temperature

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Single-zone and Dual-zone Condenser Sequence of Operation

Testing Defrost Operation Using Test Pins

to rise within the condenser coil to melt off any ice build-up. At the same time the unit will switch on the indoor electric strip heater to temper the cold air being discharged from

Figure 21

Defrost control board

(S1H shown)

the defrost-sensor opens (approx. 60°F) or a

10-minute maximum cycle time has elapsed.

Defrost times will vary depending on outdoor temperature and moisture conditions. When the defrost cycle is complete the unit will return to normal heating operation.

WARNING

Before removing the access panels to the unit make sure that all power is disconnected from the unit. Failure to do so could result in injury or electric shock.

DFT TST R and DF2

Defrost operation can be initiated using the test pins located on the circuit board of the condensing unit. “Defrost test operation” will be a time compressed version of the actual defrost cycle.

With the system “off ”, using two small alligator clips, jumper the following sets of test pins. “R and DF2” and “DFT TST”.

Defrost control board

Apply power to the indoor and outdoor units.

Place the indoor unit in heating mode with the set point temperature well above room temwill remain on during the entire defrost test operation.

proximately 20 seconds. At that point the unit will enter defrost mode for approximately 2 seconds. During this time the condenser fan will switch off , the reversing valve will energize and the defrost board will energize the indoor electric heat relay through the “W” terminal.

Aft er the two second defrost cycle is complete, the unit will switch back to heating operation

S2HG

NOTICE

If the condenser coil is heavily frosted up with ice, it is likely that the “Defrost

Sensor” is already closed. In this case the

“R and DFT” jumper can be eliminated.

To initiate defrost, momentarily jump pins marked “DFT TST” until the defrost cycle begins. The unit will remain in defrost mode until the condenser coil is defrosted and then it will return to heating mode. When testing is complete be sure to remove the jumper(s). DO NOT leave the unit in test mode with jumper(s) in place.

Low ambient operation

If the unit is equipped with low ambient fan control for cooling, the fan will remain off (while in cooling mode) until the condenser pressure run until the condenser pressure falls below peat until the jumpers are removed from the test pins.

mode (or when the reversing valve is energized).

In heating (reversing valve not energized), the fan will run continuous so long as the connection is made between “R” and “Y”.

Comfort where it counts

32

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Specifi cation and Dimensions

NOTICE

Performance data listed in this manual is subject to change without notice. For the most current unit/system performance data, please refer to the ECR International listing of certifi ed products in the AHRI directory, at www.ahridirectory.org.

Due to ongoing product development, designs, specifi cations, and performance are subject to change without notice. Please consult the factory for further information.

F

E

1/2” Diameter Lag Holes

C

D

G

A

B

A

Electrical connections

Easy access interconnects on back of unit

Table 4

Dimensional data, sound data and shipping weights

Model

S1CG/S1HG9

S1CG/S1HG2

S1CG/S1HG8

S1CG/S1HG4

S1CG3

S1CG6

S2CG/S2HG99

S2CG/S2HG22

S2CG/S2HG92

Note 1

Size

9

12

18

24

30

36

9 + 9

12 + 12

9 + 12

A

7

(178)

7

(178)

7

(178)

7

(178)

7

(178)

4

5

/

8

(117)

4 5 /

8

(117)

4

5

/

8

(117)

4 5 /

8

(117)

Mounting Dimensions

Inches (mm)

B

23 15 /

16

(608)

23 15 /

16

(608)

23 15 /

16

(608)

23

15

/

16

(608)

23 15 /

16

(608)

14

11

/

16

(373)

14 11 /

16

(373)

22

11

/

16

(570)

22 11 /

16

(570)

D

12 7 /

16

(316)

12 7 /

16

(316)

12 7 /

16

(316)

12

7

/

16

(316)

12 7 /

16

(316)

12

7

/

16

(316)

12 7 /

16

(316)

12

7

/

16

(316)

12 7 /

16

(316)

C

3

(76)

3

(76)

3

(76)

3

(76)

3

(76)

3

(76)

3

(76)

3

(76)

3

(76)

Unit dimensions

E

38

(965)

38

(965)

38

(965)

32

(813)

38

(965)

38

(965)

24

(610)

24

(610)

32

(813)

Inches (mm)

F

15

(381)

15

(381)

15

(381)

15

(381)

15

(381)

15

(381)

15

(381)

15

(381)

15

(381)

G

36

(914)

36

(914)

36

(914)

40

(1016)

44

(1118)

48

(1219)

44

(1219)

44

(1219)

44

(1219)

Sound level dBA

(note 1)

Shipping weight

Lbs (kg)

59

59

62

63

68

68

68

68

68

Sound levels are for cooling or heat pump for sizes up to 24 kBtuh, cooling only for larger sizes.

98

98

156

156

210

210

159

197

187

P/N 240007754, Rev. C [3/19/2010]

33

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Specifi cation and Dimensions

(continued) (see NOTICE on page 33 )

Table 5

Model #

S1CG9A

S1CG2A

S1CG9D

S1CG2D

S1CG8D

S1CG4D

S1CG3D

S1CG6D

S1CG electrical specifi cations

Volts/HZ/PH

115/60/1

115/60/1

208/230/60/1

208/230/60/1

208/230/60/1

208/230/60/1

208/230/60/1

208/230/60/1

Fan Motor

AMPS

1.4

1.4

0.8

0.8

0.8

0.8

1.8

HP

0.125

0.125

0.125

0.125

0.125

0.125

0.330

1.8

0.330

Compressor

RLA

7.5

9.9

3.9

5.2

5.9

8.0

11.6

LRA

27

43

43

47

53

20

74

11.5

79

Total amps

8.9

11.3

4.7

6.0

6.7

8.8

13.4

13.3

Min volt

104

104

197

197

197

197

197

197

S1CG

performance data: Matched with EMI Series Indoor Units

Table 6

Cooling systems with wall units

Condenser Wall unit Btuh

S1CG9 WLHG09 9,000

S1CG2 WLHG12 12,000

S1CG8 WLHG24 18,000

S1CG4 WLHG24 23,800

S1CG3 WLCG30 28,200

S1CG6 WLCG36 33,600

SEER

13.0

13.0

13.0

13.0

13.0

13.0

SHR

0.74

0.68

0.77

0.67

0.79

0.69

EER

12.2

11.9

12.0

11.4

11.7

11.6

Ref.

R410A

R410A

R410A

R410A

R410A

R410A

WLC/WLH

M.C.A.

10.8

13.8

5.7

7.3

8.2

10.8

16.3

16.2

HACR

BRKR

15

15

15

15

20

15

25

30

Table 7

Cooling systems with universal units

Condenser Universal Btuh

S1CG9

UNHG09 9,000

SEER

13.0

SHR

0.74

EER

12.2

S1CG2

UNHG12 12,000 13.0

0.68

11.9

S1CG8 UNHG24

18,000 13.0

0.77

12.0

S1CG4 UNHG24

23,800 13.0

0.67

11.4

S1CG3 UNCG30

28,200 13.0

0.79

11.7

S1CG6 UNCG36 33,600 13.0

0.69

11.6

Ref.

R410A

R410A

R410A

R410A

R410A

R410A

UNC/UNH

Table 8

Cooling systems with cassette units (_ _ = G or H)

Condenser Cassette Btuh

S1CG9 CAH_9 9,000

S1CG2

S1CG8

CAH_12

CAH_24

12,000

18,000

S1CG4 CAH_24 24,000

S1CG3 CAC_36 30,000

S1CG6 CAC_36 36,000

SEER

13.0

13.0

13.0

13.0

13.0

13.0

SHR

0.77

0.67

0.75

0.69

0.77

0.72

EER

11.4

11.5

12.7

12.1

12.4

11.5

Ref.

R410A

R410A

R410A

R410A

R410A

R410A

CAC/CAH

Comfort where it counts

34

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Specifi cation and Dimensions

(continued) (see NOTICE on page 33 )

Table 9

S1HG electrical specifi cations

Model # Volts/HZ/PH

S1HG9A

S1HG2A

115/60/1

115/60/1

S1HG9D 208/230/60/1

S1HG2D 208/230/60/1

S1HG8D 208/230/60/1

S1HG4D 208/230/60/1

Fan motor

AMPS HP

1.4

1.4

0.8

0.8

0.8

0.8

0.125

0.125

0.125

0.125

0.125

0.125

Compressor

RLA LRA

7.5

9.9

3.9

5.2

5.9

8.0

43

43

47

53

20

27

Total amps

8.9

11.3

4.7

6.0

6.7

8.8

Min volt

104

104

197

197

197

197

M.C.A.

10.8

13.8

5.7

7.3

8.2

10.8

S1HG

performance data: Matched with EMI Series Indoor Units

HACR

BRKR

15

20

15

15

15

15

Table 10

S1HG9

S1HG2

S1HG8

S1HG4

Heat pump systems with wall units

Condenser Wall unit

WLHG09

WLHG12

WLHG24

WLHG24

Cooling

Btuh

9,000

12,000

18,000

23,800

Heating

Btuh

9,000

11,400

17,600

20,600

SEER

13.0

13.0

13.0

13.0

HSPF

7.7

7.7

7.7

7.7

SHR

0.72

0.69

0.76

0.71

EER

12.8

11.8

11.9

11.9

COP

3.3

3.3

3.5

3.5

Ref.

R410A

R410A

R410A

R410A

Table 11

Heat pump systems with universal units

Condenser

S1HG9

S1HG2

S1HG8

S1HG4

Universal

Cooling

Btuh

9,000 UNHG09

UNHG12 12,000

UNHG24 18,000

UNHG24 23,800

Heating

Btuh

9,000

11,400

17,600

20,600

SEER

13.0

13.0

13.0

13.0

HSPF

7.7

7.7

7.7

7.7

SHR

0.72

0.69

0.76

0.71

Table 12

Heat pump systems with cassette units (_ _ = G or H)

Condenser Cassette

Cooling

Btuh

9,000

S1HG2000 12,000

S1HG8000 CAH_24 18,000

S1HG4000 CAH_24 24,000

Heating

Btuh

8,200

10,600

16,400

20,400

SEER

13.0

13.0

13.0

13.0

HSPF

7.7

7.7

7.7

7.7

SHR

0.74

0.67

0.76

0.69

EER

11.8

11.5

12.1

12.0

EER

12.8

11.8

11.9

11.9

COP

3.2

3.0

3.4

3.3

COP

3.3

3.3

3.5

3.5

Ref.

R410A

R410A

R410A

R410A

Ref.

R410A

R410A

R410A

R410A

WLC/WLH

CAC/

CAH

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single zone

35

UNC/UNH

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Specifi cation and Dimensions

(continued) (see NOTICE on page 33 )

Table 13

S2CG electrical specifi cations

Fan motor

Capacity Volts/HZ/PH

AMPS

9900 208/230/60/1 0.8

HP

0.125

9200 208/230/60/1 0.8

2200 208/230/60/1 0.8

0.125

0.125

Compressor

Circuit #1 Circuit #2

RLA LRA RLA LRA

3.9

20 3.9

20

3.9

5.2

20

27

5.2

5.2

27

27

Total amps

Min volt

M.C.A.

HACR

BRKR

7.8

8.8

9.8

197

197

197

8.7

10

11

15

15

15

S2CG

performance data: Matched with EMI Series Indoor Units

Table 14

S2CG cooling systems with two wall units

Wall units

WLHG09+WLHG09

WLHG12+WLHG12

Condenser

S2CG99

S2CG22

Btuh

18,000

24,000

SEER

13.0

13.0

WLHG09+WLHG12 S2CG92 21,000 13.0

SHR

0.73

0.68

0.70

EER

12.1

12.0

12.0

Ref.

R410A

R410A

R410A

Table 15

S2CG cooling systems with two universal units

Air handlers

UNHG09 + UNHG09

UNHG12 + UNHG12

UNHG09 + UNHG12

Condenser

S2CG99

S2CG22

S2CG92

Btuh

18,000

24,000

21,000

SEER

13.0

13.0

13.0

SHR

0.73

0.68

0.70

EER

12.1

12.0

12.0

Ref.

R410A

R410A

R410A

WLC/WLH

S2CG/S2HG

Dual zone

UNC/UNH

Comfort where it counts

36

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Specifi cation and Dimensions

(continued) (see NOTICE on page 33 )

Table 16

S2HG electrical specifi cations

Fan motor

Capacity Volts/HZ/PH

AMPS

9900 208/230/60/1 0.8

HP

0.125

9200 208/230/60/1 0.8

2200 208/230/60/1 0.8

0.125

0.125

Compressor

Circuit #1 Circuit #2

RLA LRA RLA LRA

3.9

20 3.9

20

3.9

5.2

20

27

5.2

5.2

27

27

Total amps

Min volt

M.C.A.

HACR

BRKR

7.8

8.8

9.8

197

197

197

8.7

10

11

15

15

15

S2HG

performance data: Matched with EMI Series Indoor Units

Table 17

Heat pump systems with wall units

Wall units

WLHG09+WLHG09

WLHG12+WLHG12

WLHG09+WLHG12

Condenser

S2HG99

S2HG22

S2HG92

Cooling

Btuh

18,000

24,000

21,000

Heating

Btuh

17,400

21,000

19,200

SEER HSPF SHR

13.0

13.0

13.0

7.7

7.7

7.7

0.73

0.68

0.70

EER

12.1

12.0

12.0

COP Ref.

3.2

R410A

3.2

R410A

3.2

R410A

Table 18

Heat pump systems with universal units

Air handlers

UNHG09 + UNHG09

UNHG12 + UNHG12

UNHG09 + UNHG12

Condenser

S2HG99

S2HG22

S2HG92

Cooling

Btuh

18,000

24,000

21,000

Heating

Btuh

17,400

21,000

19,200

SEER HSPF SHR

13.0

13.0

13.0

7.7

7.7

7.7

0.73

0.68

0.70

EER

12.1

12.0

12.0

COP Ref.

3.2

R410A

3.2

R410A

3.2

R410A

WLC/WLH

S2CG/S2HG

Dual zone UNC/UNH

P/N 240007754, Rev. C [3/19/2010]

37

Made in the USA

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Test Unit Performance Data Sheet

NOTICE

for use by a qualifi ed service professional in the event that there is a problem with the unit. In

Have this information ready when calling. Make sure to include the Model Number, Serial Number, and Date of installation.

order for our Technical Service Department to bett er serve you, please complete.

Call our Technical Support Department

@ 1-800-228-9364.

Model Number

Serial Number

Date:

Technician:

Mode: Cooling

Notes Indoor Section

Air handler Entering Air – DB

Air handler Entering Air – WB

Air handler Leaving Air – DB

Air handler Leaving Air – WB

Outdoor Section

Entering Air

Leaving Air

Temperature Split

Operating Pressures

Compressor Suction – PSIG

Compressor Discharge – PSIG

Power Input

Compressor – Volts

Compressor – Amps

OD Fan Motor – Volts

OD Fan Motor – Amps

ID Fan Motor – Volts

ID Fan Motor – Amps

Total Volts

Total Amps

Temperatures – Degrees F°

Compressor Suction

Compressor Discharge

Liquid Out Cond.

Liquid before Expansion

Suction out Air handler

Capacity Calculations

DB – Temp Split at evap.

Test Summary

Compressor Superheat

Sub Cooling

Comfort where it counts

38

P/N 240007754, Rev. C [3/19/2010]

S1CG/S1HG

Single-Zone,

S2CG/S2HG

Dual-Zone

• Installation, Operation and Maintenance Manual •

Notes

P/N 240007754, Rev. C [3/19/2010]

39

Made in the USA

WLC/WLH

High Wall Air Handler

EMI’s Product Line

Indoor Units

C assette

Air andler

UNC/UNH

Universal Floor or Ceiling

Air Handler

Outdoor Units

Side Discharge

Phone: 1-800-228-9364

Fax: 1-800-232-9364

Single Zone

Side Discharge

2201 Dwyer Ave

Utica, NY 13504