Data Sheet E85001-0560 -- Reflective Beam Detector

Data Sheet E85001-0560 -- Reflective Beam Detector
EDWARDS Catalog u Conventional Initiating
LIFE SAFETY
&
INCIDENT MANAGEMENT
Reflective Beam
Smoke Detector
Beam
Smoke
Detector
EC-50R/-100R
S3417
7260-1508:
0102
Test Station
Reflector
Overview
Operation
The EC-50R/-100R comprises a transmitter and receiver in a
single enclosure and is usually installed between 19 inches and
24 inches below the ceiling. The transmitter emits an invisible
infrared light beam that is reflected via a prism mounted directly
opposite and with a clear line of sight. The reflected infrared light
is detected by the receiver and analyzed. Smoke in the beam path
will reduce the received infrared light proportionally to the density
of the smoke. The detector analyzes this attenuation or obscuration of light and acts accordingly. Detectors are typically mounted
within ±30 feet (9.14 m) of a potential fire source. Consult your
Authority Having Jurisdiction for spacing requirements specific to
your locality.
Alarm Threshold: Alarm thresholds of 25%, 35% and 50%
obscuration can be selected to suit the environment, with 25%
the most sensitive setting. The factory default setting is 35 percent
and is used for most typical applications. If the received infrared
signal reduces to below the selected threshold for approximately
10 seconds, the fire relay is activated.
Standard Features
Trouble Alarm: If the infrared beam is obscured rapidly to a level
of 90% or greater for approximately 10 seconds, the Trouble relay
is activated. Typical causes of trouble include an object being
placed in the beam path, transmitter failure, loss of the prism, or
sudden misalignment of the detector. The Trouble relay will reset
within 2 seconds of the trouble being cleared.
• Coverage: 50R range 15 -160 ft (4.6 - 48.8 m);
100R range 160- 330 ft (48.8 - 100 m)
• Microprocessor controlled
• Automatic drift compensation
• Simple alignment
• Selectable alarm thresholds
• 24 Vdc operating voltage
• Latching or non-latching operation
• Low current consumption
• Optional Ground Level Test Station
Page 1 of 4
Fire Alarm: There are two modes to the operation of the fire
relay. Auto reset mode will reset the fire relay 5 seconds after the
received infrared signal has recovered to a level above the Alarm
threshold. Latching mode holds the fire relay active indefinitely
after an Alarm condition has occurred. To clear the latched mode,
power must be removed from the Detector for a minimum of 5
seconds.
Automatic Gain Control (AGC): The Detector monitors long
term degradation of signal strength caused by component aging
or build up of dirt on optical surfaces. By comparing the received
infrared signal against a standard every 15 minutes, the detector automatically compensates for signal differences of less than
0.7dB/hour. When the detector is showing AGC fault, detector is
still capable of generating an alarm, and will display both Alarm
and Trouble indications.
E85001-0560
D ATA S H E E T
Not to be used for installation purposes. Issue 1
An infrared signal is projected out of the transmitter optics to the
reflector placed at the opposite end of the detection zone. The
signal is reflected back to the receiver where it is analyzed for fire
and trouble. The EC-50R/-100R must be positioned correctly to
minimize the detection time. The maximum lateral distance either
side of the beam is found to be typically 30 feet (9.1 m) for satisfactory detection under flat ceilings, providing a total area coverage of 19,800 square feet (60 feet x 330 feet), or 1844 square
metres (18.3 x 100.6 m).
Smoke stratification may be overcome by mounting multiple beam
detectors at different heights, one of which will project an infrared
beam below the heat layer and into the smoke layer.
EC-50R detectors should be mounted between
15 and 160 feet (4.6 and 48.8m) from a single
reflector.
0.34"
(10 mm)
4”
(102 mm)
Reflective beam smoke detectors are ideal for large open areas
such as warehouses, hotel atriums, industrial plants and school
gymnasiums.
Mount the reflector(s) on a secure surface directly opposite the
detector. Ensure that there is a clear line of sight between the
detector and the reflector(s), and that no moving objects such as
doors or mechanical equipment interfere with the beam path. All
objects should be kept a minimum of 19 inches (483 mm) away
from the center of the detector beam down the entire length of the
beam path. Reflectors should not be mounted on glass or reflective surfaces.
4" (102 mm)
4" (102 mm)
Application
Reflector Positioning
4"
(102 mm)
Single
reflector
8" (204 mm)
0.34"
(10 mm)
EC-100R detectors should be
mounted between 160 and 330 feet
(48.8 and 100.6 m) from a group of
four reflectors.
Detection time will be longer in a building with a peaked roof if a
fire occurs at the fringes of the protected area. If in doubt conduct
appropriate smoke tests.
0.34"
(10 mm)
4”
(102 mm)
Test Filter: A test filter is supplied with the detector, which is used
to verify the alarm threshold. See the installation sheet for details
on testing and calibration.
Because of the reflecting properties of the beam, all objects must
be kept a minimum of 19 inches (483 mm) away from the centre
of the beam path down the entire beam length. If highly reflective
surfaces are close to the beam, then greater clearances should be
applied.
0.34"
(10 mm)
4"
(102 mm)
0.34"
(10 mm)
4"
(102 mm)
4”
(102 mm)
Connection between the test station and the detector is made
by means of a 2-wire data link cable. The test station requires a
10.2 - 30 Vdc power connection.
The recommended installation height is approximately 19 to 24
inches (483 to 610 mm) below the ceiling. However, in all installations the National Fire Standards for that country/state must be
consulted.
4”
(102 mm)
When the test station key is inserted and turned to the Test
position, the Power LED flashes to indicate that power is connected and that the 2-wire data link cable is correctly installed.
After several seconds in the test position, the test station initiates
an alarm at the detector head, which is indicated by the red
LED on the detector and the Alarm LED on the test station. Test
mode automatically times out after 20 seconds at which time the
detector returns to standby mode, regardless of the test station
keyswitch position.
8" (204 mm)
The optional Ground Level Test Station facilitates testing of a connected detector from safe and convenient location. The unit is key-operated with a two-position Test/Run switch and includes two dedicated
LEDs: one for Alarm indication and one for Power indication.
The ideal location and spacing of the Detector is critical in a properly installed and operating fire alarm system. It is recommended
that the detectors be located and spaced in accordance with the
National Fire Protection Association (NFPA) Standard 72 "The
National Fire Code". No liability will be accepted for applications
not conforming to NFPA regulations.
4”
(102 mm)
Test Stations
4"
(102 mm)
4"
(102 mm)
Group of four reflectors
Detector Spacing
Single Detector
Detector
19 to 24 inches
(483 to 610 mm)
60 ft. (18.3 m) max.
Detector positioning shown here is recommended for protected
areas with flat ceilings. Spacing may vary for areas with high or
sloped ceilings. In such cases, verify operation with smoke tests.
Page 2 of 4
Multiple Detectors
Ceiling
Detector
Detector
C
L
C
L
19 in. to 30 ft.
(483 mm to 9.14 m)
60 Ft max.
(18.3 m)
19 in. to 30 ft.
(483 mm to 9.14 m)
In some cases potential smoke layering may be overcome by
installing multiple beam detectors at different heights.
E85001-0560
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Typical Wiring
Dimensions
Detector
8.25"
(209.55 mm)
The field wiring interface is accessed through the back plate of the
detector head. The 8-pin connector is the interface to the field and
is numbered left to right. This diagram is an example for a single
reflective beam unit installed as the only device on a zone. The
correct operation for Fire and Trouble should always be verified.
Relays are shown in quiescent (standby) condition. Alarm and
End of Line resistor values are determined by the fire alarm control
panel and market standard practices.
Zone Wiring
POWER
SUPPLY
10.2 to 30 Volts DC (RED)
EC-50R/-100R
Fire Relay
Zone Wiring
0V (BLACK)
Alarm Resistor
NO (YELLOW)
(Not required for
North American Markets)
COM (BLUE)
Trouble Relay
COM (WHITE)
4.5"
(114.3 mm)
End of Line Resistor
NC (GREEN)
Test Station
CABLE ASSY.
APPROX 3 FT.
GROUND LEVEL
TEST STATION
TO BE LOCATED
WITHIN 330 FT. OF
THE JUNCTION BOX.
C
4.5" (114.3 mm)
BLUE
YELLOW
3.25" (82.55 mm) FIXING CENTERS
JUNCTION
BOX (JB)
YELLOW
EC-50R / EC-100R
-VE
+VE
RED
B
A
1.5" (38.1 mm)
COMMON
CONNECTIONS
WHITE
GREEN
BLACK
RED
YELLOW
BLUE
BLUE
8
7
6
5
4
3
2
1
2.75" (69.85 mm)
BLACK
2-WAY
CONN. 8-WAY CONNECTOR
Ground Level Test Station
ALARM
POWER
TEST
RUN
B A
Ø 0.2
FIXING HOLES
D
0.5" (12.7 mm)
GROUND LEVEL
TEST STATION (LLT)
0.34"
(10 mm)
Reflector
Detector Installation
When installing the detector on a wall supported with wood studs,
ensure the fixing points are secured directly to the supporting
stud. When installing the detector on a wall supported with metal
studs, mount a metal plate at least 1/8" (3.2 mm) thick across two
studs and secure the detector to the plate.
4”
(102 mm)
Install the detector to a secure surface not subject to movement or
vibration. Use the template provided to mark and install four fixing
points. Secure the rear mounting plate to the four fixing points
through the keyholes on the plate.
4"
(102 mm)
Page 3 of 4
E85001-0560
D ATA S H E E T
Not to be used for installation purposes. Issue 1
Engineering Specifications
L I F E S A F E TY & I NCI DE NT M AN AGEM EN T
Contact us...
Email:edwards.fire@fs.utc.com
Web:
Edwards-fire.com
EDWARDS is a UTC brand.
1016 Corporate Park Drive
Mebane, NC 27302
© 2016 United Technologies Corporation.
All rights reserved.
EC-50R
The projected beam type smoke detector
shall be listed to UL 268 and shall consist
of an integrated transmitter and receiver.
The beam detector shall operate between
a range of 15 and 160 feet (4.57 and 48.77
m). It shall feature automatic gain control,
which will compensate for gradual signal
deterioration due to dirt accumulation on
the lenses. The unit shall include a wall
mounting bracket. Testing shall be carried out using a calibrated test filter. It shall
be possible to test the detector without
direct access to it by means of a remotely
installed key-operated test station.
EC-100R
The projected beam type smoke detector
shall be listed to UL 268 and shall consist
of an integrated transmitter and receiver.
The beam detector shall operate between
a range of 160 and 330 feet (48.77 and
100 m). It shall feature automatic gain
control, which will compensate for gradual
signal deterioration due to dirt accumulation on the lenses. The unit shall include a
wall mounting bracket. Testing shall be carried out using a calibrated test filter. It shall
be possible to test the detector without
direct access to it by means of a remotely
installed key-operated test station.
Ordering Information
P/N
Description
EC-50R
EC-50R Reflective
Beam Smoke Detector
c/w test filter and one
reflector
2.0
(0.90)
EC-100R
EC-100R Reflective
Beam Smoke Detector
c/w test filter and four
reflectors
2.0
(0.90)
EC-LLT
Ground Level
Test Station
1.0
(0.45)
2390101
Replacement Reflector
for EC-50R/-100R
1.0
(0.45)
Beam Detector
Compatibility
All EDWARDS Fire Alarm
Control Panels
Power
Supply
10.2 Vdc to 30 Vdc (continuous power)
Current
Standby: Less than 4 mA
Alarm/Trouble: Less than 14
mA
Contacts
Alarm: Normally Open, rated
2A, 30 Vdc, resistive
Trouble: Normally Closed,
rated 2A, 30 Vdc, resistive
Signal Delay
Alarm and trouble: 10 seconds
Reset Time
>5 seconds (power down)
Dimensions
(HxWxD)
8.25 in x 5.1 in x 4.7 in
(21 cm x 13 cm x 12 cm)
Weight
1.5 lb (0.68 kg)
Operating
Environment
Temperature: 32° F to 100° F
(0° C to 37° C)
Humidity: 93%RH, Noncondensing
Beam
Coverage
Width: 30 ft (9.14 m) either
side of beam
Length, EC-50R: 15 ft to 160
ft (4.57 m to 48.77 m)
Length, EC-100R: 160 ft to
330 ft (48.77 m to 100 m)
Alarm
Thresholds
2.50dB (25%), 3.74dB (35%),
6.02dB (50%) obscuration
Optical
Wavelength
880nm
Agency
Listings
UL, ULC, CE
Test Station
Operating
voltage
10.2 to 30 Vdc
Off current
0 mA
On current
8 mA max (alarm)
Wiring Terminations
Suitable for #12 to #18 AWG
(2.5 mm² to 0.75 mm²) wire
size. Shielded twisted pair
recommended.
Operating
temperature
32 °F to 100 °F
Key reference
A126
Humidity
max 93% RH (non condensing)
Agency
Listings
UL, MEA, CSFM
E85001-0560
D ATA S H E E T
Not to be used for installation purposes. Issue 1
10-11-16
Page 4 of 4
Ship
Wt lb
(kg)
Technical Specifications