Automatic transfer switch 4 226 82

Automatic transfer switch 4 226 82
Automatic transfer switch
4 226 82
Installation and user manual
26
42
82
E2
LIN
Q2
AD
LO
Q1
E1
LIN
S
RE
F
OF _
T
AU
Part. LE09477AA_EN-06/16-01 GF
NU
ME
ET
UT
A
OK
M
U
EN
N
MA
+
IR
M
CO
IE
-1
7-6
94
0
C6
Automatic transfer switch
4 226 82
EN
ENGLISH3
82
26
42
E2
LIN
Q2
AD
LO
Q1
E1
LIN
NU
ME
T
SE
RE
F
OF _
T
AUOK
NU
T
AU
2
ME
N
MA
+
IR
M
CO
IEC
1
-6-
47
9
60
WARNING
• Read carefully the manual before the installation or use, taking count of the informations of instruction sheet given
with to the product.
• These equipments have to be installed by qualified personnel, in compliance to local standards, to avoid damages or
safety hazards.
• Before any device maintenance operation, remove the supply from measuring inputs or isolate them cutting the supply
from other sources.
• Legrand assumes no responsibility if the device isn’t properly used, if installative informations aren’t respected or if the
device is tampered.
• Products described here below are subject to alterations and changes without prior notice. For this reason the catalogues data couldn’t have contractual value.
• Clean the instrument with a soft dry cloth; do not use abrasives, liquids.
• Due of presence of electrical connections, the safety standards have to be respected.
• The ATS is supplied with Legrand standard parameters. These couldn’t respect the necessity of the specific application/
installation. For this reason it is necessary to know the parameters and eventually to modify them in order to better
integrate the device to the plant.
SAFETY INSTRUCTIONS
This product should be installed in compliance with installation rules, preferably by a qualified electrician. Incorrect installation
and use can lead to risk of electric shock or fire.
Before carrying out the installation, read the instructions and take account of the product’s specific mounting location.
Do not open up, dismantle, alter or modify the device.
All Legrand products must be opened and repaired exclusively by personnel trained and approved by Legrand. Any unauthorized opening or repair completely cancels all liabilities and the rights to replacement and guarantees.
Use only Legrand brand accessories.
3
Installation and user manual
Automatic transfer switch
4 226 82
Index
1. General features6
1.1Description
6
1.2Applications
6
1.3Installation
6
2. ATS front panel description7
2.1 Selection keys 7
2.2
7
LEDs
2.3 IR Input
7
3. Operating mode8
3.1 Reset mode (OFF-RESET)
8
3.2 Manual mode (MAN)
8
3.3 Automatic mode (AUT)
9
4. Power-up9
5. Menu principale10
6. Password access11
7. Display pages12
8. Expandability15
9. Communication17
9.1 Limit thresholds (LIMx)
17
9.2 Remote-controlled variables (REMx)
18
9.3 User Alarms (UAx)
18
9.4 Counters (CNTx)
18
10.Keypad lock19
11.Programmation19
11.1 Parameter setting (setup) from frontal panel
19
11.2 Parameter setting (setup) with PC
20
11.3 Parameter setting with smartphone or tablet
21
11.4 IR port
21
12.Automatic test22
13.Menu23
4
14. Parameters24
14.1 Description of “utility” menu
24
14.2 Description of “general” menu
25
14.3 Description of “password” menu
25
14.4 Description of “battery” menu
26
14.5 Description of “Load changeover” menu
27
14.6 Description of “Voltage control line 1 S.Q1” menu
29
14.7 Description of “Voltage control line 2 S.Q2” menu
31
14.8 Description of “Communication” menu
32
14.9 Description of “Automatic test” menu
32
14.10 Description of “Programmable inputs” menu
33
14.11 Description of “Programmable outputs” menu
34
14.12 Description of “Miscellaneous” menu 34
14.13 Description of “Limit thresholds” menu
35
14.14 Description of “Counters” menu
36
14.15 Description of “User alarms” menu
36
14.16 Description of “Alarms” menu
37
14.17 Alarm properties
37
14.18 Alarm table
38
14.19 Alarm description
38
15. Function I/O40
15.1 Programmable inputs function table
40
15.2 Output function table
42
16. Commands menu43
17. Installation44
18. Terminals position44
19. Dimensions44
20. Technical characteristics45
5
Installation and user manual
Automatic transfer switch
4 226 82
1. General features
The automatic transfer switch has been designed for switching applications between two power sources (power grids or
generators). ATS has an LCD screen to provide a clear and intuitive user interface.
1.1 Description
••
••
••
••
••
••
••
••
••
••
••
••
••
••
128x80 pixel, backlit LCD screen with 4 grey levels.
5 keys for functions and setting.
4 LEDs for plant synoptic (source line and breakers status).
2 LEDs for alarm presence and AUTO mode active.
5-language text for measurements, settings and messages.
Programmable I/O functions.
Fully user-definable alarm properties.
Line 1: 3-phase + neutral voltage reading input (S.Q1).
Line 2: 3-phase + neutral voltage reading input (S.Q2).
100-240VAC power supply. Aux supply available at 12-24VDC.
Voltage thresholds with programmable hysteresis.
Front optical programming interface, galvanically isolated, which can be connected with USB and WiFi dongles.
6 programmable digital inputs (negative).
6 + 1 outputs:
-- 6 relays with NO contact 8A 250VAC.
-- 1 relay with changeover contact 8A 250VAC.
•• Storage of the last 100 events.
•• IP 40 front protection.
•• Compatible with App and SW ACU.
1.2 Applications
•
•
•
•
•
To check and to manage lines (line-to-line (U-U), line-generator (U-G) or generator-generator (G-G)).
Control of motorized circuit breakers or contactors.
Control of voltage source for three-phase, two-phase or single-phase systems.
Control of phase-phase and / or phase-neutral voltages.
Controls of undervoltage, overvoltage, phase loss, asymmetry, minimum frequency, maximum frequency.
1.3 Installation
• Install the unit following the instruction sheet attached to the product. Evaluate if the default configuration is in compliance with the desired one. Otherwise it is necessary modify the configuration. Check the wiring diagram supplied by
Legrand in order to correctly connect the unit and others Legrand devices.
• The ATS standard configuration guarantees the correct work of devices if wiring diagrams supplied are respected.
WARNING
The change of parameters, of input functions, of output functions etc... causes a functional change. This could cause
incompatibility with standard wiring diagrams. It is recommended to evaluate changes of parameters or functional
modes after having read the ATS user manual.
• At first power on, the OFF/RESET mode is activated on the ATS.
6
2. ATS front panel description
2.1 Selection keys
••
••
••
••
OFF button (F) – It selects the OFF operating mode.
AUT button (G) – It selects the automatic mode. Green AUT LED (D) lights (when selected).
MAN button (H) – It selects the manual operating mode.
▲ and ▼ keys (I) - Used to scroll through the display pages or to select the list of options in a menu. Simultaneously
pressing of ▼ and ▲ recalls up the main menu.
2.2 LEDs
••
••
••
••
••
AUT LED (green) (D) – It indicates the automatic mode active.
Alarm LED (red) (E) – Flashing, it indicates an active alarm.
Line 1 voltage status LED (green) (C) – It indicates the line voltage of source 1 S.Q1 is within the programmed limits.
Line 2 voltage status LED (green) (C) - It indicates the line voltage of source 2 S.Q2 is within the programmed limits.
Q1 status LED (yellow) (B) - If fixed, it indicates the open or closed state of the devices Q1 source line 1. If flashing, it
indicates a mismatch between the desired state of the breaker and its true state detected by the feedback input.
•• Q2 status LED (yellow) (B) - If fixed, it indicates the open or closed state of the device Q2 source line 2 breaker. If flashing,
it indicates a mismatch between the desired state of the breaker and its true state detected by the feedback input.
N.B. If the LED is on, the relative function is activated.
4 226 82
A
B
C
LINE 1
D
E
LOAD
Q1
AUT
RESET
MENU
OFF
_
AUT
OK
LINE 2
Q2
I
L
MAN
+
IR COM
MENU
IEC 60947-6-1
F
G
H
Fig. 1 - Frontal panel
2.3 IR Input
•• IR Input (L) – Connecting IR port to connect IR-USB or IR-WiFi dongle accessories. They allow the dialogue between ATS
and SW ACU or APP ACU.
7
Installation and user manual
Automatic transfer switch
4 226 82
3. Operating mode
With of OFF-RESET/MAN/AUT keys the desiderated operating modes can be selected and they will appear on the display.
Fig. 2 - OFF/RESET
Fig. 3 - MAN
Fig. 4 - AUT
The change of operating mode can be done by pressing the specific button for at least 0.5s. After this time, the new chosen modality will appear another display.
3.1 Reset mode (OFF-RESET)
•• In this mode the ATS looks over the lines status but it does not perform any changing actions.
•• Lines surveillance, measures display and status LEDs remain active. If the control of the switching devices is impulsive,
in OFF mode both open and close commands are disabled. If the command is in continuous mode, the behaviour can
be selected by P05.10.
•• Pressing the OFF-RESET button it’s possible to reset the retentive alarms, after removing alarm conditions.
To access the programming menu is necessary to activate the OFF mode.
3.2 Manual mode (MAN)
•• In MAN mode it is possible to manually control the devices. This operation could be done on devices Q1 and Q2 in functions of chosen line (line 1 or line 2). It is possible to select the switch to control by pressing the MAN key. On display
the device enabled (Q1 or Q2) appears. By pressing the ▲ or ▼ button it is possible to confirm the closing or opening
operation (the command will be received if the button is pushed for at least 300ms).
Fig. 5 - Q1 Selection
Fig. 6 - Q1 Closing
•• While devices opening-closing is enabled, the page scroll is locked. Pressing MAN several times it is possible to unlock
it and to move through other display pages.
•• If it is commanded the closing of an opened device while the other one is still closed, the ATS first of all opens the closed
device and then it closes the commanded one, interposing the programmed interlock time.
Voltage Line 1
Voltage Line 2
Q1 selected
Function selectable
with MAN
Page scroll locked
Fig. 7 - Manual mode (MAN)
Fig. 8 - Manual GEN mode
With an application Utility-Generator (U-G) or Generator-Generator (G-G), it is possible to manually control the switching
on and off of the generator in a manner similar to that above described, but moving on the page start / stop groups.
8
Voltage line 1
Voltage Line 2
Line 2
selected
Page scroll locked
Selectable function
with MAN
Fig. 9 - Generator manual mode
Fig. 10 - Start Generator manual mode
3.3 Automatic mode (AUT)
•• In automatic mode, the ATS checks permanently the lines and breakers status. Starting from the state of lines it performs
autonomously the closing/opening operations of breakers and the optional startup/shutdown of the generator set.
•• When the main line (S.Q1) exceeds the specified limits for a time higher the one set, the green LED C (line presence)
switches off giving a “threshold out” alarm. The ATS disconnects the load from S.Q1 and connects it to the S.Q2 (if it is
available and within admitted limits). After S.Q1 returns within the specified thresholds, the ATS moves the load on this
one after it has checked the stability and the quality of line. One time the changeover is finished, the ATS can provide
to the eventual cooling cycle of generator set (if it is programmed).
•• Automatic operating cycles vary both as a function of the type of application (Utility-Utility, Utility-Generator, Generator-Generator) and as a function of the type of devices used (motorized circuit breakers or contactors).
•• It is possible to program the unit to open the priority line S.Q1 before or after the secondary line S.Q2 has been made
available, through parameter P05.05 in the M05 “changeover” menu.
•• When the priority line S.Q1 turns within the established limits, the unit opens S.Q2 and switches the load on S.Q1. If on
S.Q2 is present a generator, the ATS provided to the eventual cooling cycle of it. It is possible also to lock the automatic
return to the priority line S.Q1 setting parameter P05.12. In this case it is necessary an external intervention to authorize
the turn of load to line S.Q1.
4. Power-up
•• The ATS can be supplied at 100-240VAC or 12-24VDC. In case of simultaneous presence of both power supplies, priority
is given to the AC power supply.
•• After first power-up the device normally starts in OFF/RESET mode.
•• During the normal work of ATS, if it switches off, when it will be switched on it comes to operating mode actives before
the switching off.
•• If it is necessary to modify this behaviour, the parameter P01.03 in the M01 “utilities” menu has to be changed.
•• The automatic transfer switch can be supplied with a second Vaux by means of the input “DC battery” from 12VDC to
24VDC. The same input could be used for the battery control, if it is activated. In this case it is necessary to set the correct battery voltage in the menu M05 “battery”.
•• During power-up all the LEDs blink in order to verify their operation.
9
Installation and user manual
Automatic transfer switch
4 226 82
5. Main menu
•• The “main menu” is made up of a group of graphic icons that allow to access to functions. In function of selected icon, a
description will be displayed on the display.
Fig. 11 - Main menu
The main menu allow the rapid access to measurements and settings.
•• Starting from main page, press ▲ and ▼ keys together. The menu screen is displayed.
•• Press ◄ or ► to rotate clockwise/counter clockwise to select the required function. The selected icon is highlighted
and the central part of the display shows the description of the function.
•• Press (AUT) OK to activate the selected function.
•• If some functions are not available, the correspondent icon will be disabled (shown with light grey colour).
•• Icons descriptions:
Enter password
L-L voltages
L-N voltages
Commands menu
Alarm status
Parameters Setup
Nominal data
Information page
Statistics
Input/output status
Battery status
Event log
Fig. 12 - Main menu
••
••
••
••
••
••
••
••
••
••
••
••
10
– Settings and access to the password inserction.
– View of L-L voltages.
– View of L-N voltages.
– View of alarm status.
– Nominal data.
– Statistic data of the ATS operation.
– Event log list.
– Battery status.
– Input/output status.
– Information page.
– Setup menu for parameter programming (see dedicated chapter).
– “Commands menu” (see dedicated chapter).
6. Password access
••
••
••
••
The ATS has a password function that at first switching on is not active in order to access to all parameters (M03
Password OFF).
N.B. In case of password activation/modify, it is recommended to make a copy of it to guarantee future access with desired privileges.
It is possible to define different level of password in order to permit different access to “settings/commands” menu in
function of access privileges.
If password is activated, in order to enter to protected data, it is necessary to insert the correct code.
To enable password management and to define numeric codes, see M03 “password” menu.
There are different access levels:
•• Password disabled (OFF)– The password is disabled. Complete access to all parameters (Default Legrand).
•• Password enabled (ON) – The password is enabled:
--Access without to insert password (Lev.1) The password is enabled but not inserted. This access allow the visualization only.
--User Level access (Lev.2) It allows the change of mode, the clearing of recorded values and editing of a limited
number of setup parameters.
--Advance Level access (Lev.3) Complete access to all parameters.
MENU
M01
M02
M03
M04
M05
M06
M07
M08
M09
M10
M11
M12
M13
M14
M15
M16
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
NO Password Lev 1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Password OFF
Password ON (liv2-liv.3)
Lev. 2
●
X
X
X
X
●
●
●
●
X
X
X
X
X
X
X
•• The default password for each level are the followings:
Password OFF default Legrand
Password mode
Password ON
Level
1
2
3
Full Access
Lev. 3
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Password
-
1000
2000
•• From normal viewing, press to recall main menu, select the password icon and press .
The display shows the screen below:
Fig. 13 - Enter password
Fig. 14 - Enter password level Ok
Fig. 15 - Enter Wrong password level
•• With keys ▲ and ▼ it is possible to change the selected digit.
•• With keys +◄ and -► it is possible move through the digits.
ATTENTION! To confirm the password it is mandatory to select
icon and to confirm with  OK.
If the code is confirmed with OK without going on key icon “ ”, the value won’t be accepted.
•• In function of level password “Level 2-User or Level 3-Advanced” the correspondent unlock message is shown.
•• Once unlocked the password, the access rights are valid until one of the followings conditions are verified:
-- A timeout period of two minutes elapses without any keystroke.
-- The device is reset (after quitting the setup menu).
-- The device is turned off.
•• To quit the password entry screen press  key.
11
Installation and user manual
Automatic transfer switch
4 226 82
7. Display pages
Voltage S.Q1
(Device Q1)
Voltage S.Q2
(Device Q2)
Contact status
device Q1
Contact status
device Q2
Fig. 16 - Synoptic
Fig. 17- Date/hour
S.Q1
S.Q2
Measure unit
Phases indication
Operative
Mode
Frequency
Fig. 18 - L-L voltage
Voltage
Phases indication
Frequency
Fig. 19 - L-N voltage
Active alarms
Fig. 20 - Alarms status
S.Q1 Voltage
threshold
S.Q2 Voltage
threshold
S.Q1 Frequency
thresholds
S.Q2 Frequency
threshold
Fig. 21 - Control Thresholds
12
LINE1
LINE 2
AUT mode commutation counter
AUT mode commutation counter
MAN mode commutation counter
MAN mode commutation counter
Alarms counter A03 A04
Alarms counter A03 A04
Time lapse with load supplied
Time lapse with load supplied
Time lapse with lines in the limits
Time lapse with lines in the limits
Time lapse with lines out the limits
Time lapse with lines out the limits
Total time with no supplied load
ATS total power down counter
Fig. 22 - Statistics
Minimum voltage
measured
Maximum voltage
measured
Actual voltage
Maximum voltage limit
Minimum
voltage limit
MAX and min
voltages reset
Fig. 23 - Battery status
Device model
indication
Expansion installed
indication
Power supply
Optical port
communication status
Fig. 24 - Expansion modules
Digital input
status
{
{
Output status
Fig. 25 - Input/Output status
Input
function
{
Fig. 26 - Inputs
13
Installation and user manual
Automatic transfer switch
4 226 82
7. Display pages
Output
function
{
Fig. 27 - Outputs
Free user text
Fig. 28 - Information page
Fig. 29 - System info
•• Note: some of the pages listed above may not be displayed if the relevant function is disabled. For example, if the limit
threshold function is not programmed, the concerning page will not be shown.
14
8. Expandability
•• The automatic transfer switch can be expanded with additional modules. It is possible to connect a maximum of 2
expansion modules at the same time.
•• The expansion modules provide additional resources in order to extend the checking and managing chances. These
ones can be parameterized and managed through the dedicated setup menus.
•• The supported expansions modules can be grouped in the following categories:
- communication modules
- I/O modules
•• Procedure To add an expansion module:
-- remove the power supply to automatic transfer switch (230VAC and auxiliary in DC, if present);
-- remove the protecting cover of one of the expansion slots;
-- insert the upper hook of the module into the fixing hole on the left of the expansion slot;
-- rotate right the module body, inserting the connector on the bus;
-- push until the bottom clip snaps into its housing.
Fig. 30
•• Once expansion modules are installed, the ATS recognize them when it will be powered on. It automatically recognises
the kind of mounted expansions modules showing it on display.
•• At switching on, if the device configuration has changed compared to the last saved, (one module has been added or
removed), the ATS asks the user to confirm the new configuration. In case of confirmation, the new configuration will be
saved and will become effective, otherwise the mismatch will be shown at every subsequent power-on of the system.
Fig. 31 - Configuration change
N.B. One time the module has been installed, the associated functions have to be set by the user.
15
Installation and user manual
Automatic transfer switch
4 226 82
8. Expandability
•• The I/O status (active/not active) is graphically shown in the following way:
- ACTIVE: with words in negative (white on black background)
- NOT ACTIVE: with words in positive (black on white background)
Fig. 32 ‐ I/O Active/Not active
•• The setup menus related to the modules are always accessible, even if the expansion modules are not physically fitted.
•• It is possible to add modules I/O of the same type; the setup menus are multiple and identified by a sequential number.
•• The following table shows how many modules of each group can be mounted at the same time.
MODULE TYPE
CODE
FUNCTION
MAX Nr.
COMMUNICATION
4 226 89
RS-485
1
4 226 90
4 STATIC
OUTPUTS
2
4 226 91
2
CHANGEOVER
RELAYS
2
4 226 92
2 INPUTS + 2
RELAYS NO
2
I/O
16
9. Communication
•• It is possible connect to the ATS a maximum of 2 communication modules, indicated as COMn. With M08 “communications” menu is possible the setting of COM ports.
•• The inputs and outputs are identified by a code and a sequence number. Example: the digital inputs are identified by
code INPx, where x is the number of the input. In the same way, digital outputs are identified by code OUTx.
CODE
DESCRIPTION
BASE
EXP
INPx
Digital Inputs
1…6
7…14
OUTx
Digital outputs
1…7
8…15
•• Internal variables (bit) are associated to inputs/outputs. For instance, it is possible to apply limit thresholds to the measurements done by the ATS. In this case, an internal variable named LIMx will be activated when the measurements will
go outside the limits defined by the user.
•• The following table shows all the I/Os and the internal variables managed by the automatic transfer switch with highlighting of their range (variables number per type).
CODE
DESCRIPTION
RANGE
LIMx
Limit thresholds
1…4
REMx
Remote-controlled variables
1…16
UAx
User alarms
1…4
CNTx
Programmable counters
1…4
•• Functions associated to the inputs are the 4 described in the above table.
•• LIMx: internal variable that identifies a limit value set by the user and managed by the ATS. Its status (active or not)
depends by out-of-limits of one measurement set by the user.
•• CNTx: internal counters that can count pulses coming from an external source (through a digital input INPx) or the
times that a certain condition has been verified.
Example: defining a limit threshold LIMx as count source, it will be possible to count how many times one measurement
has exceeded a certain limit.
•• REMx: allow the managing of remote variables.
•• UAx: allow the activation and managing of 4 programmable alarms.
9.1 Limit thresholds (LIMx)
•• The LIMx thresholds are internal variables whose status depends by out-of-limits of one measurement set by the user.
•• (example: phase to phase voltage L1-L2 higher than 400V).
•• The setting of thresholds value is calculated starting from a base value. Example: “400 V” adding a multiplicative factor
“x 1” →400 x 1 = 400V.
•• For each LIM, there are two thresholds: upper and lower.
N.B. The upper threshold must always be set to a value higher than the nominal one and the lower threshold must
always to be set to a value lower than the nominal one.
•• The control mode of thresholds can be done in 3 ways:
-- MIN function: when the value of selected measure is under lower limit, after the delay set, the threshold will be
activated. When the value of selected measure is over the upper limit, after delay set, the threshold will be restored.
-- MAX function: when the value of selected measure is higher than the superior limit, after the delay set, the threshold
will be activated. When the value of selected measure is under lower limit, after delay set, the threshold will be restored.
-- MAX+MIN function: when the value of selected measure is under lower limit or over the upper limit, after the delays
set, the threshold will be activated. When the value of selected measure comes back into the limits, the threshold will
be restored (if not retenitive).
•• The managing of limit can be done in 2 ways: with memory or without memory. In the first case the reset of the alarm
can be done only manually (retenitive); in the second case the reset of alarm is automatic, if the value comes back into
the limits. The setting can be done using the dedicated command in the “commands” menu.
•• See setup menu M13 “Limit thresholds”.
17
Installation and user manual
Automatic transfer switch
4 226 82
9. Communication
Type of measure
Upper threshold
Function
Measure value
Threshold delay
Lower threshold
Status of the limit
variable
Fig. 33 - Limit thresholds
9.2 Remote-controlled variables (REMx)
•• The automatic transfer switch, with an external supervision software, can activate outputs (OUTx) via Modbus protocol
RS 485 channel. This can be done by means of remote variables REMx.
•• To use this functionality, it is necessary to use Modbus external module.
9.3 User Alarms (UAx)
•• User can set a maximum of 4 programmable alarms (UA1…UA4).
•• Conditions that generates the alarm can be different:
- In association of one thresholds LIMX set
- Activation of digital inputs INPx.
•• For each alarm, the user can define a message that will appear on the alarm page.
•• Properties of alarms can be defined by the user in the same way that normal alarms.
•• When several alarms are activated at the same time, they are displayed sequentially, and their total number is shown
on the status bar.
•• To reset one alarm that has been programmed with latch, use the dedicated command in the “commands” menu.
•• For details on alarm programming and definition, refer to setup menu M15 “User alarms”.
9.4 Counters (CNTx)
•• This function allows, by selecting a control channel, to activate a counter (see chapter M14 “counters”).
•• It is possible to count:
- Impulses acquired from inputs INPx;
- The numbers of activations of outputs OUTx;
- The overcome of limits LIMx;
- Activation of known variables.
•• The description of counters CNTx can be customized with a test of maximum 16 characters.
•• The unit of measure of counters Umn can be customized with a test of maximum 6 characters.
18
10. Keypad lock
•• The automatic transfer switch keypad can be locked, avoiding not desidered command.
•• Once the keypad is locked, it will only be possible to view measures, but not to change operating mode or to operate in
MAN mode on devices. If the icon menu is shown and the keypad is locked, wait 2 minutes to return to main
page.
N.B. Any attempt to use the locked keys will cause the word “ACCESS LOCKED” to be displayed.
•• The activation of keypad lock can be made in the followings ways:
- With a programmable input (activate the function “keypad lock” );
- From frontal keys;
- With SW ACU.
•• To lock or unlock the keypad, press key ▲ and, while holding it down, press key ▼ three times without releasing it at
the end. Release then key ▲ and then press it 5 times, then release both keys.
•• When the keypad is locked, the display shows the word “KEYBOARD LOCKED”. If the keypad isn’t locked the display
shows the word “KEYBOARD UNLOCKED”.
11. Programmation
11.1 Parameter setting (setup) from frontal panel
•• To access to “parameters” menu and to modify them, it is necessary put the ATS in OFF mode, recall the “main” menu
(press ▲▼simultaneously), select the “setup” menu ( ) and confirm with (OK).
0,3 sec.
Fig. 34
Fig. 35
•• A table shown in the following picture is displayed.
Fig. 36 - Setup menu
•• Sliding menus Mxx it is possible to select sub-menus where are present all parameters associated to the function.
•• Select the required menu with keys ▲or ▼and confirm with •.
•• Press OFF to quit and return to the measurement viewing.
N.B. If the icon is not enabled (in grey color), it is necessary to check access privileges to modify parameters (see
chapter “passwords”).
19
Installation and user manual
Automatic transfer switch
4 226 82
11. Programmation
11.2 Parameter setting (setup) with PC
•• The managing of setting parameters can be done also using the PC Software “ACU configurator” (available to free
download on E-catalogue Legrand.
•• Using software ACU it is possible to transfer set-up parameters from ATS to PC, generating a file. It is also possible to
transfer to ATS a file with parameters from SW ACU.
•• It is possible to transfer parameters in 2 ways:
- Total transfer: all parameters are uploaded on ATS in one time
- Partial transfer: only menu with modified data will be uploaded to the ATS
•• The PC can be used also to define “information page” where to add informations, charachteristics, data etc...concerning
the application.
For more details refers to manual of Software ACU configurator.
Fig. 37 - Setup menu
20
11.3 Parameter setting with smartphone or tablet
•• The managing of setting parameters can be done also using the App for smartphone and tablet “ACU configurator”
(available to free download on Google Play and Apple iStore).
•• The connection between ATS and App is possible by means of WiFi dongle (Legrand).
•• The App permits to see alarms, to send commands, to read measures, to set parameters, to download events.
Fig. 38 - App
11.4 IR port
•• The parameters of the automatic transfer switch can be configured and consulted also through the front optical port,
using a USB or WiFi dongle.
•• Using this port it is possible to configure and to dialogue with the automatic transfer switch without the need to access
to the rear of the device or having to open the electrical panel. This connection is isolated from internal circuit ensuring
safety for the operator.
•• This port guarantees IP40 front protection.
•• Simply holding the USB/WiFi dongle up to the front panel, connecting the plugs to the connectors the device will be
connected. The recognition between devices will be shown by the green “LINK” LED on the programming dongle.
Fig. 39 - WiFi Dongle
21
Installation and user manual
Automatic transfer switch
4 226 82
12. Automatic test
•• The ATS allows to the user to program a periodical control of generator start.
•• The automatic test is a periodic test carried out at specific intervals (interval managed on from “setup” menu). This test
can be done only if the ATS is in AUT mode and the function has been enabled.
•• It is possible to decide in which days of the week the automatic test can be executed and at what time of the day (hours;
minutes). See menu M09 “automatic test”.
•• After starting, the generators runs for a definite time, after which it will stop.
•• Before of generator starting the message “T.AUT”’ is displayed.
Fig. 40 - Automatic test
•• The automatic test can be enabled/disabled also without opening the “Setup” menu, directly from keyboard in the
following way:
- Open the “AUTOMATIC TEST” page and press the keys AUT and ▲to enable the function, or the keys AUT and ▼to
disable it.
•• The automatic test can be stopped with the OFF-RESET key.
•• It is possible to simulate the lack of the priority line by SW in order to verify the behavior of the transfer switch system.
•• The simulation can be started either using the “commands” menu (command C.16) or via a digital input, for example
connecting it to a key switch, programming the function of the input to the execution of the command C.16.
•• The simulation consists in considering the priority line absent for 2 minutes (even if it is actually present). During this
time the main page shows the message “SIMUL xxx” with the countdown of the time.
•• The simulation will cause the start of the generator (if present) and a load transfer exactly as in the automatic cycle.
•• It is possible to stop the simulation at any time by passing in OFF mode.
N.B. Doing the simulation through commands menu, user must start from the OFF mode (which allows access to the
menu). Once selected and confirmed the C.16 command, exit the command menu. The unit will independently switch
to AUT mode and it starts the simulation.
22
13. Menu
The following table lists shows the available ATS menus:
CODE
M01
M02
M03
M04
M05
M06
M07
M08
M09
M10
M11
M12
M13
M14
M15
M16
MENU
DESCRIPTION
UTILITY
GENERAL
PASSWORD
BATTERY
CHANGEOVER
LINE 1 CONTROL
LINE 2 CONTROL
COMMUNICATIONS
AUTOMATIC TEST
DIGITAL INPUTS
DIGITAL OUTPUTS
MISCELLANEOUS
LIMIT THRESHOLDS
COUNTERS
USER ALARM
ALARM TABLE
Language, brightness, display pages, etc.
System nominal data
Password settings
Battery parameters
Load changeover settings
Valid limits for voltage line1 (S.Q1)
Valid limits for voltage line 2 (S.Q2)
Communication parameters
Automatic test mode, duration, period
Programmable digital inputs functions
Programmable digital outputs functions
Accessory functions
Customisable limit thresholds
Programmable generic counters
Programmable alarms
Alarms effect enabling
•• The access to the menu/sub-menu modify page is subject to the input of password (if the function is activated).
•• After highlighted the correct menu it is necessary press  to show the parameters.
•• Each parameter is shown with code, description and actual setting value.
Parameter code
Present setting value
Parameter
description
Fig. 41 - Set-up: parameter selection
•• To modify the setting of one parameter, select it and then press .
New value entered
Selected parameter
Maximum possible
setting
Graph bar of the
value-range
Factory default
setting
Minimum
possible setting
Fig. 42 - Set-up: editing page
•• The parameter setting can be modified with + ► and - ◄ keys. The screen shows the new setting, a graphic bar with
the setting range, the maximum and minimum values, the previous setting and the factory default.
•• Pressing + ► and ▲ the value is set to the maximum admitted, while with ▲ and - ◄ it is set to the minimum.
N.B. Pressing simultaneously + ► and - ◄ , the setting is set to factory default.
During the typing of a text string, keys ▲ and ▼ are used to select the alphanumeric character while + ► and - ◄ are
used to move the cursor along the text string.
N.B. Pressing keys ▲ and ▼ simultaneously will move the character selection straight to character “A”.
•• Press  to go back to the parameter selection. The entered value is saved.
•• Press OFF to save all the settings and to quit the setup menu. The controller executes a reset and returns to normal
operation.
•• In “SET-UP” mode, if the user does not press any key for at least 2 minutes, the system leaves automatically and goes
back to normal viewing without saving the changes done on parameters.
23
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
•• In menu “parameters” are described all parameters, their changes and it is defined the work mode of ATS. Menu is composed by 16 parts: from M01 to M16.
•• Each menu is composed by specific parameters Px that can be modified in function of needs.
•• For example, the definition of control characteristics of power sources can be definied by the customer using parameters of M05 “load changeover” menu and M06-M07 “voltage control line 1S.Q1 -voltage control line 2 S.Q2” menus.
•• With menus M06 and M07 it is possible to set nominal data for power sources such as nominal voltage, nominal frequency that could be used to set thresholds.
•• It is possible set a transformation ratio TV associated to the control inputs establishing criteria in M02 “general” menu. In
case a lower voltage is applied but proportional to that of plant, limits of measures will be real values of plant.
•• The ATS can be set to do voltage checks in three-phases lines with or without neutral, bi-phases or single-phase
(P02.07).
•• In case of lines three-phases or bi-phases it is possible to choose if monitor/control phase-phase voltage or phaseneutral voltage or both. (P02.06).
N.B. Nominal voltage set with P02.01 must be referred to phase-phase voltage.
•• In the followings tables are listed controls that could be done on each line.
14.1 Description of “utility” menu
M01 – UTILITY
••
••
••
••
••
••
••
P01.01
Language
P01.02
Set real time clock at power-on
P01.03
Power-on operating mode
P01.04
LCD contrast
P01.05
UoM
DEFAULT
RANGE
English
English
French
Spanish
Russian
Polish
OFF
OFF-ON
Previous
OFF mode
Previous
%
50
0-100
Display backlight intensity high
%
100
0-100
P01.06
Display backlight intensity low
%
25
0-50
P01.07
Time to switch to low backlighting
s
180
5-600
P01.08
Return to default page
s
300
OFF / 10-600
P01.09
Default page
Synoptic
(page list)
P01.10
Plant identifier
(empty)
String 20 chr.
P01.01 – Select display text language.
P01.02 – Active automatic clock settings access after power-up.
P01.03 – Start system in OFF mode after power-up or in same mode it was switched off in.
P01.04 – Adjust LCD contrast.
P01.05 – Display backlight high adjustment.
P01.07 – Display backlight low delay.
P01.08 – Default page display restore delay when no key pressed. If set to OFF the display will always show the last
page selected manually.
•• P01.09 – Default page displayed on power-up and after delay.
•• P01.10 – Free text with alphanumeric identifier name of specific plant.
24
14.2 Description of “general” menu
M02 - GENERAL
UoM
DEFAULT
RANGE
P02.01
Nominal plant voltage
VAC
400
50-50000
P02.02
TV Use
OFF
OFF-ON
P02.03
TV Primary
V
100
50-50000
P02.04
TV Secondary
V
100
50-500
P02.05
Phase sequence control
OFF
OFF
L1-L2-L3
L3-L2-L1
P02.06
Wiring mode
L1-L2-L3
L1-L2-L3-N
L1-L2-L3
L1-N-L2
L1-N
P02.07
Voltage control mode
L-L
L-L
L-N
L-L + L-N
P02.08
Nominal frequency
50HZ
50 HZ
60 HZ
••
••
••
••
••
P02.01 – Rated voltage of grid and generator. Set the line-to-line voltage for polyphase systems.
P02.02 – Using voltage transformers (TV) on voltage metering inputs.
P02.03 – Primary value of any voltage transformers.
P02.04 – Secondary value of any voltage transformers.
P02.05 – Enable phase sequence control. OFF = no control. Direct = L1-L2-L3. Reverse = L3-L2-L1.
N.B. Enable also corresponding alarms in case of a control parameter won’t be respected.
•• P02.06 – Choosing the type of connection, three-phase with/without neutral, two-phase or single phase.
•• P02.07 – Voltage checks performed on concatenated, phase voltages or both.
•• P02.08 – Rated frequency S.Q1/S.Q2
14.3 Description of “password” menu
M03 - PASSWORD
DEFAULT
RANGE
P03.01
Password enable
OFF
OFF-ON
P03.02
User level password
1000
0000÷9999
P03.03
Advanced level password
2000
0000÷9999
P03.04
Remote access password
OFF
OFF/0001÷9999
•• P03.01 – If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
•• P03.02 – With P03.01 enabled, levels password are enabled. It is necessary insert the correct value to activate the access
to user level (the password can be modified by customer). See “Password access chapter”.
•• P03.03 – As for P03.02, with reference to advanced level access.
•• P03.04 – If set to a numeric value, this becomes the code to specify via modbus to permit to send commands from a
remote control.
25
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
14.4 Description of “battery” menu
The input auxiliary supply “DC battery” is used mainly to feed the ATS with steady DC current. During the changeover operation, the auxiliary supply “DC battery” allows to guarantee the surveillance of changeover system and, in case of connection via Modbus, the exchange of data with supervision system. With this input it is also possible, in configuration U-G, to
check the level of charge of generator battery and to generate an alarm in case of anomaly (see menu “alarms” A01-A02).
Inside the “battery” menu, it is possible enable the check and set nominal values of acceptability thresholds.
M04 - BATTERY
UoM
DEFAULT
RANGE
P04.01
Battery rated voltage
V
OFF
AUTO
12
24
OFF
P04.02
MAX. voltage limit
%
130
110-140
P04.03
MIN. voltage limit
%
75
60-130
P04.04
MIN./MAX. voltage delay
s
10
0-120
••
••
••
••
P04.01 – Rated battery voltage. If set to OFF, it disables the alarm and the display of the battery status.
P04.02 – Battery MAX. voltage alarm intervention threshold.
P04.03 – Battery MIN. voltage alarm intervention threshold.
P04.04 – Battery MIN. and MAX. alarms intervention delay.
The battery voltage control can be done with of connection to the DC supply terminal block (ATS terminals 31 and 32).
31
+
32
+
GE
DC SUPPLY
12-24V=
3W
Fig. 43 - control voltage battery generator
26
14.5 Description of “Load changeover” menu
In the following menu are present mains parameters to identify the correct plant configuration and to define characteristics to manage and to check the changeover system.
M05 – LOAD CHANGEOVER
UoM
DEFAULT
RANGE
P05.01
Application type
U-G
U-G
U-U
G-G
P05.02
Priority line selection
-1-
-1- Line 1
-2- Line 2
P05.03
Line 1 → Line 2 interlock time
s
6.0
0.1…1800.0
P05.04
Line 1 ← Line 2 interlock time
s
P05.05
Breaker open mode
P05.06
Maximum operating switch
time (A03 – A04 alarms delay)
P05.07
Changeover type
P05.08
Opening pulse duration
P05.09
Closing pulse duration
P05.10
Continuous command in
RESET/OFF mode
P05.11
Load no powered maximum
time (A07 delay time)
P05.12
Inhibition automatic return
on priority LINE
P05.13
EJP mode
P05.14
EJP start delay
P05.15
EJP Changeover delay
P05.16
6.0
0.1…1800.0
OBP
OBP
OAP
5
1…900
Brk. Pul.
Brk. Pul.
Brk. Con.
Chg. Pul.
Chg. Con.
Contactors
s
10
0-600
s
1
0-600
NOC
OFF
NOC
60
OFF / 1…3600
OFF
OFF / ON
Normal
Normal
EJP
EJP-T
SCR
min
25
0-240
min
5
0-240
EJP re-switching block
ON
OFF/ON
P05.17
Changeover on closing failure
(only with open feedback)
OFF
OFF
1
2
1+2
P05.18
Minimum voltage coil pulse
duration
s
1.0
0.1 … 10.0
P05.19
Delay between minimum coil
and spring reload
s
0.2
0.1 … 10.0
P05.20
Closing retry
OFF
OFF
AUT AUT+MAN
s
s
27
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
M05 – LOAD CHANGEOVER
P05.21
Generator rotation interval
P05.22
Generator rotation hour
P05.23
Generator rotation minutes
UoM
DEFAULT
RANGE
OFF
OFF
1h-2h-3h4h-6h-8h12h1d-2d-3d
4d-5d-6d-7d
h
0
0...23
min
0
0...59
•• P05.01 – It defines the type of application
U-G = Utility to Generator
U-U = Utility to Utility
G-G = Generator to Generator
•• P05.02 – It defines which is the main line that is the line taking on the load when both sources are available.
•• P05.03 – Time from the opening of the Q1 device, after which the Q2 device closing command is given.
•• P05.04 – Time from the opening of the Q2 device, after which the Q1 device closing command is given.
•• P05.05 – OBP (Open Before Presence) means that, in automatic mode, the open command of a device is generated
when the line concerned goes beyond limits, irrespective of the status of the alternative line.
OAP (Open After Presence) means that, in automatic mode, the open command of a device is sent only after the alternative line is present within limits.
•• P05.06 – If, after sending an open or close command to a circuit breaker, this is not positioned correctly within this time
(feedback by means of OC contacts), alarms A03 or A04 are generated.
•• P05.07 – It defines whether open-close outputs must be continuously active (application with contactors or circuit breakers) or in pulse mode, i.e. activated until the device has been positioned as required. If in pulse mode, the command
is extended for a specified time (see P5.08 e P5.09) even after positioning completion.
•• P05.08 – Minimum duration of an opening command pulse. For the motorized circuit breaker application, it must be set
to a time long enough to allow the load of the springs. This time is considered also when working in continuous mode.
•• P05.09 – Duration of the closing command pulse.
•• P05.10 – It defines the behaviour of the open/close command outputs when working in continuous command mode
and the automatic transfer switch is in RESET/OFF mode. This parameter can be useful when working with contactors.
OFF – It opens the command outputs
NOC – No change on command output
•• P05.11 – If in automatic mode both sources are not available at the same time for a time exceeding P5.11, alarm A07
is generated.
•• P05.12 – If this parameter is enabled, after a transfer to the S.Q2, restoring to S.Q1 does not occur automatically when
the latter becomes available again, but it must be commanded in manual mode.
OFF – Disabled
ON – Enabled
•• P05.13 – Normal = This parameter is set in normal modality for default.In this modality the ATS manages in automatic
lines in function of quality and stability criteria set in menu “parameters”.
EJP (Effacement Jours Pointe) = in this modality, the ATS manage the lines in function of external signals that command the load transfer from the grid to the generator. This request is managed in two times using 2 programmable inputs set with the functions “Remote starting off load” and “Remote changeover” for EJP. When the starting of generator is
requested by means of closing of contact “remote changeover”, the starting generator delay starts (P05.14). At the end
the generator starts. After, when changeover command arrives, the ATS checks the status of generator and the load is
transferred. Load will be supplied by the generator until the changeover command input persists. When this command
lapses, the ATS prepares to transfer the load on the main line starting the cooling cycle of generator. The EJP function is
only enabled if the system is in automatic mode. The cutouts and alarms function as usual.
EJP-T = The EJP/T function is a simplified variation of the previous EJP, and in this case the engine start is controlled in
the same way, but a timer switches the load instead of an external signal. This function therefore uses only one digital
input, the starting input. The switching delay starts from when the programmable input INPx associated to the starting
command closes (parameter P05.15).
SCR = The SCR function is very similar to the EJP function. In this mode, the starting input enables genset starting as
for EJP, without waiting for start delay P05.14. The remote changeover input still has a switching go-ahead function
after “Changeover delay” P05.15.
•• P05.14 – Delay between the EJP start signal and the effective start signal sent to the generator.
28
•• P05.15 – Delay for switching the load from S.Q1 to S.Q2 in EJP and SCR mode.
•• P05.16 – If ON, in EJP , EJP-T and SCR mode, the load will not be switched back to the priority line in the case of a
generator failure, but only when the signals on the EJP inputs give a go-ahead.
•• P05.17 – If enabled, in case of closing failure of the switching device, in addition to the generation of the proper
feedback alarm (A03 or A04) the load is switched to the alternative source.
OFF = function disabled.
1 = check source S.Q1.
2 = check source S.Q2.
1+2 = check both S.Q1 and S.Q2.
•• P05.18 – In case of using of UVR in the changeover system controlled by ATS (parameter “UVR command” into menu
M11 “programmable outputs”) this parameter defines the period of deactivation of them to assure the immediate opening of devices)
•• P05.19 – Time between the opening pulse on the minimum voltage coil and the spring reload command.
•• P05.20 – In case of use of motorized breakers, this parameter defines in which operating mode the automatic transfer
switch must execute the closing retry cycle. The closing retry is executed in case the breaker fails to close because the
springs were not loaded. It consists of a complete opening and spring loading cycle, followed by the issuing of a new
closing command. If the breaker fails to close again, then the A03 or A04 feedback alarm are generated.
•• P05.21– P05.22 - P05.23 These parameters allow to implement a time rotation in G-G applications, switching the
priority between the two generators. P05.21 defines the rotation interval between the two generators. The time of the
day when rotation will occur is defined by P05.22 and P05.23. If the rotation interval exceeds 24h, then rotation always
occurs at the time stated every n days. Contrarily, if it is less than 24h, then it occurs at the time specified and every
n-hours. For instance, if you set time at 12:30 and rotation every 6h, there will be a changeover at 12:30, one at 18:30,
one at 0:30, etc.
14.6 Description of “Voltage control line 1 S.Q1” menu
In this paragraph control parameters, thresholds setting and control levels of power sources defining acceptability criteria
are described. In this menu is also possible set the insensibility level to micro interruptions using parameter P06.10 (standard value 100ms). This could be extended until 30s in case of disturbed lines.
P06.04
P06.05
V MAIN
P06.02
P06.01
LOGIC
STATUS
BREAKER
STATUS
P06.03
P06.06 P06.03
CLOSED
OPENED
Fig. 44
N.B. the insensibility to interruption is for default 100ms. With parameter P06.10 this time could be modify until 30s.
M06 –
VOLTAGE CONTROL LINE 1 S.Q1
UoM
DEFAULT
RANGE
P06.01 MIN voltage limit for trip
%
85
70-100
P06.02 MIN voltage restore
%
90
70-100
P06.03 MIN voltage delay
s
5
0-600
P06.04 MAX voltage limit for trip
%
115
100-130 / OFF
P06.05 MAX voltage restore
%
110
100-130 / OFF
P06.06 MAX voltage delay
s
5
0-600
continues...
29
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
M06 –
VOLTAGE CONTROL LINE 1 S.Q1
UoM
DEFAULT
RANGE
P06.07 Return of power in the limits delayed (when S.Q2 source not available)
s
10
1-6000
P06.08 Return of power in the limits delayed (when S.Q2 source available)
s
60
1-6000
P06.09 Phase failure threshold
%
70
60% - 80%
OFF
P06.10 Phase failure delay
s
0.1
0.1s-30s
P06.11 MAX Asymmetry limit
%
15
1% -20%/OFF
P06.12 MAX Asymmetry delay
s
5
0.1-900
P06.13 MAX frequency limit
%
105
100-120/OFF
P06.14 MAX frequency delay
s
3
0-600
P06.15 MIN frequency limit
%
95
OFF/80-100
P06.16 MIN frequency delay
s
5
0-600
P06.17 S.Q1 control OFF mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P06.18 S.Q1 control MAN mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P06.19 Time delay generator starter due
to a lack of S.Q1
s
OFF
OFF / 1-6000
P06.20 Generator cooling time
s
120
1-3600
•• P06.01 - P06.02 - P06.03 – The first two parameters define the minimum voltage threshold and the related hysteresis
upon restore. P06.02 cannot be set to a lower value than P6.01. P6.03 defines the intervention delay of this protection.
•• P06.04 - P06.05 - P06.06 – The first two parameters define the maximum voltage threshold and the related hysteresis
upon restore. P06.05 cannot be set to a value exceeding P06.04. Setting P06.04 to OFF will disable the maximum voltage control. P06.06 defines the maximum voltage intervention delay.
•• P06.07 – Delay for S.Q1 (Line 1) restores to the limit range, used when the line 2 (S.Q2) source is not available. Generally
shorter than P06.08, as there is the urgent need to supply power because the load is not energized.
•• P06.08 – Delay for S.Q1 (Line 1) restores to the limit range, used when the load can be connected to S.Q2 (line 2). Generally longer than P06.07, as the load is energized and consequently it is possible to wait longer before considering
voltage steadily restored.
•• P06.09 - P06.10 – Voltage threshold below which a phase loss intervention occurs, generally quicker than the drop.
The delay for the phase loss is specified by P06.10. This parameter has to be evaluate in function of load (example: damaging of engines in case of phase missing).
•• P06.11 - P06.12 – P06.11 defines the maximum threshold for unbalance between phases, referred to voltage rating,
and P06.12 defines the related intervention delay. This control may be disabled by setting P06.11 to OFF.
•• P06.13 – Max. frequency intervention threshold (it can be disabled).
•• P06.14 – Max. frequency intervention delay.
•• P06.15 – Min. frequency intervention threshold (it can be disabled).
•• P06.16 – Min. frequency intervention delay
•• P06.17 – Parameters and described characteristics are referred to ATS in AUT mode.
OFF = S.Q1 (line 1) voltage control in OFF mode disabled.
ON = Voltage control in OFF mode enabled.
OFF+GBL = Voltage control in OFF mode disabled, but the relay programmed with the global alarm function activates
or not depending on whether the voltage is respectively absent or present.
ON+GBL = Voltage control in OFF mode enabled, and the relay programmed with the global alarm function activates
or not depending on whether the voltage is respectively absent or present.
30
•• P06.18 – Parameters and described characteristics are referred to ATS in MAN mode.
OFF = S.Q1 (line 1) voltage control in OFF mode disabled.
ON = Voltage control in OFF mode enabled.
OFF+GBL = Voltage control in OFF mode disabled, but the relay programmed with the global alarm function activates
or not depending on whether the voltage is respectively absent or present.
ON+GBL = Voltage control in OFF mode enabled, and the relay programmed with the global alarm function activates
or not depending on whether the voltage is respectively absent or present.
•• P06.19 – Engine start delay when S.Q1 (line 1) fails to meet set limits. If set to OFF, the starting cycle starts when the
mains contactor opens.
•• P06.20 – Max. duration of the cooling cycle. Example: time between load disconnection from the generator and when
the engine actually stops.
14.7 Description of “Voltage control line 2 S.Q2” menu
M07 – VOLTAGE CONTROL LINE 2 S.Q2
UDM
DEFAULT
RANGE
P07.01
MIN voltage limit for trip
%
85
70-100
P07.02
MIN voltage restore
%
90
70-100
P07.03
MIN voltage delay
s
5
0-600
P07.04
MAX voltage limit for trip
%
115
100-130 / OFF
P07.05
MAX voltage restore
%
110
100-130 / OFF
P07.06
MAX voltage delay
s
5
0-600
P07.07
Return of power in the limits delayed
(when S.Q1 source not available)
s
10
1-6000
P07.08
Return of power in the limits delayed
(when S.Q1 source available)
s
60
1-6000
P07.09
Phase failure threshold
%
70
60 - 80
OFF
P07.10
Phase failure delay
s
0.1
0.1s-30s
P07.11
MAX Asymmetry limit
%
15
1 -20
OFF
P07.12
MAX Asymmetry delay
s
5
0.1-900
P07.13
MAX frequency limit
%
105
100-120
OFF
P07.14
MAX frequency delay
s
3
0-600
P07.15
MIN frequency limit
%
95
OFF
80-100
P07.16
MIN frequency delay
s
5
0-600
P07.17
S.Q2 control OFF mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.18
S.Q2 control MAN mode
OFF
OFF
ON
OFF+GLOB
ON+GLOB
P07.19
Time delay generator starter due to a
lack of S.Q2
s
OFF
OFF / 1-6000
P07.20
Generator cooling time
s
120
1-3600
Note: For details on the functions of parameters see the menu M06 – “voltage control S.Q1 (line 1)”.
31
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
14.8 Description of “Communication” menu
M08– COMMUNICATION (COMn, n=1…2)
P08.n.01
Node serial address
P08.n.02
Serial port speed
UoM
05
bps
P08.n.03
DEFAULT
19200
Data format
8 bit, even
P08.n.04
P08.n.05
Stop bits
Protocol
1
Modbus RTU
RANGE
01-247
(248 … 255 internal use)
1200
2400
4800
9600
19200
38400
57600
115200
8 bit –no par.
8 bit, odd
8 bit, even
7 bit, odd
7 bit, even
1-2
Modbus RTU
Modbus ASCII
•• Note: this menu is divided into 2 sections for communication channels COM1…2. The front IR communication port for
connection with SW ACU and APP via WiFi or USB has fixed communication parameters, so no setup is required.
••
••
••
••
••
••
••
••
••
P08.n.01 – Serial (node) address of the communication protocol
P08.n.02 – Communication port transmission speed.
P08.n.03 – Data format. 7 bit settings can be used for ASCII protocol only.
P08.n.04 – Stop bit number.
P08.n.05 – Select communication protocol.
P08.n.06…P08.n.08 – Not available.
P08.n.09 – Not available.
P08.n.10 – Not available.
P08.n.11…P08.n.13 – Not available.
14.9 Description of “Automatic test” menu
M09 – AUTOMATIC TEST
32
UoM
DEFAULT
RANGE
OFF
OFF / ON
P09.01
Enable automatic TEST
P09.02
Time interval between TESTS
7
1-60
P09.03
Enable TEST on Monday
ON
OFF / ON
P09.04
Enable TEST on Tuesday
ON
OFF / ON
P09.05
Enable TEST on Wednesday
ON
OFF / ON
P09.06
Enable TEST on Thursday
ON
OFF / ON
P09.07
Enable TEST on Friday
ON
OFF / ON
P09.08
Enable TEST on Saturday
ON
OFF / ON
P09.09
Enable TEST on Sunday
ON
OFF / ON
P09.10
TEST start time
h
12
00-23
P09.11
TEST start minutes
min
00
00-59
P09.12
TEST duration
min
10
1-600
P09.13
Automatic TEST with load
switching
OFF
OFF
Load
Dummy-Load
gg
•• P09.01 – Enable programmed periodical test. This parameter can be changed directly on the front panel without using
setup (see chapter “Automatic Test”) and its current state is shown on the relevant page of the display.
•• P09.02 – Time interval between one periodic test and the next. If the test isn’t enabled the day the period expires, the
interval will be extended to the next enabled day.
•• P09.03…P09.09 - It enables the automatic test in each single day of the week. OFF means the test will not be performed on that day.
N.B. The calendar clock must be set to the right date and time.
•• P09.10 – P09.11- It sets the time (hour and minutes) when the periodic test starts.
N.B. The calendar clock must be set to the right date and time.
•• P09.12 – Duration in minutes of the periodic test.
•• P09.13 – Load management during the periodic test:
OFF = The load will not be switched; the checks of correct start of genset are done.
Load = It enables switching the load from the mains to the generator. Dummy load = The dummy load is switched in,
and the system load will not be switched.
The configuration installed on ATS by Legrand ensures the correct work if standard wiring diagrams supplied are respected.
WARNING: the modify of parameters could generate incompatibility with supplied wiring diagrams. It is recommended
to not modify the original configuration.
Using expansion modules is possible to increase the amount of inputs available in order to do additional checks and
controls (this solution is recommended to avoid the change of work mode of inputs in case of specific applications).
14.10 Description of “Programmable inputs” menu
M10 – PROGRAMMABLE INPUTS
(INPn, n=1…14)
UoM
DEFAULT
RANGE
P10.n.01
INPn input function
(various)
(see Input functions table)
P10.n.02
Function index (x)
OFF
OFF / 1…99
P10.n.03
Contact type
NO
NO/NC
P10.n.04
Closing delay
s
0.05
0.00-600.00
P10.n.05
Opening delay
s
0.05
0.00-600.00
Note: his menu is divided into 14 sections that refer to 6 possible digital inputs INP1…INP6, which can be managed by
the ATS. Other inputs can be managed using the expansion modules.
•• P10.n.01 – It selects the functions of the chosen input (see “programmable inputs functions table”).
•• P10.n.02 – Index associated with the function programmed in the previous parameter P10.01 (“input function selection”).
Example: If the input function is set to Cxx “commands menu execution”, and if this input has to perform command C.07
in the commands menu, P10.n.02 should be set to value 7.
•• P10.n.03 – Select type of contact: NO (Normally Open) or NC (Normally Closed).
•• P10.n.04 – Contact closing delay for selected input.
•• P10.n.05 – Contact opening delay for selected input.
33
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
14.11 Description of “Programmable outputs” menu
M11 – PROGRAMMABLE OUTPUTS
(OUT1…15
P11.n.01
Output function OUTn
P11.n.02
Function index (x)
P11.n.03
Normal/reverse output
UDM
DEFAULT
RANGE
(various)
(see Output functions table)
1
OFF / 1…99
NOR
NOR / REV
Note: This menu is divided into 15 sections that refer to 7 possible digital outputs OUT1… OUT7 managed by the ATS ,
and others inputs managed using the expansion modules.
•• P11.n.01 – It selects the functions of the selected output (see “programmable outputs functions” table).
•• P11.n.02 – Index associated with the function programmed in the previous parameter P11.01( “output function selection”).
Example: If the output function is set to “Alarm Axx”, and it’s needed to energize this output for alarm A16, then P11.n.02
should be set to value 16.
•• P11.n.03 – It sets the state of the output when the function associated with the same is inactive: NOR = output deenergized, REV = output energized.
The configuration installed on ATS by Legrand ensures the correct work if standard wiring diagrams supplied are respected.
WARNING: the modify of parameters could generate incompatibility with supplied wiring diagrams. It is recommended
to not modify the original configuration.
Using expansion modules is possible to increase the amount of outputs available in order to do additional checks and
controls (this solution is recommended to avoid the change of work mode of outputs in case of specific applications).
14.12 Description of “Miscellaneous” menu
M12 – MISCELLANEOUS
UDM
DEFAULT
RANGE
h
P12.01
Service interval in hours
OFF
OFF / 1…99999
P12.02
Service interval operations
OFF
OFF/
1…99999
P12.03
Operative mode output
OFF
OFF
O
M
M–O
A
…
•• P12.01 – It defines the programmed maintenance period in function of customer needs, in hours. If set to OFF, this
interval is disabled.
•• P12.02 – It defines the programmed maintenance period in function of customer needs, in number of operations. If set
to OFF, this interval is disabled.
•• P12.03 – It defines in which operating mode the programmed output with the “operating mode” function is enabled.
Example: if this parameter is programmed for M –O, the “operating mode” output will be enabled when the automatic
transfer switch is in MAN or OFF mode.
34
14.13 Description of “Limit thresholds” menu
M13 – LIMIT THRESHOLDS
(LIMn, n = 1…4)
UoM
DEFAULT
RANGE
P13.n.01
Reference measurement
OFF
OFF(list measure)
CNTx
….
P13.n.02
Reference measurement source
OFF
OFF
LINE 1
LINE 2
P13.n.03
Channel no. (x)
1
OFF/1...99
P13.n.04
Function limit check
Max
Max
Min
Min+Max
P13.n.05
Upper threshold
0
-9999÷9999
P13.n.06
Multiplier upper threshold
x1
/100÷x10k
P13.n.07
Delay
0
0.0÷600.0
P13.n.08
Multiplier lower threshold
0
-9999÷9999
P13.n.09
Multiplier
x1
/100÷x10k
P13.n.10
Delay
0
0.0÷600.0
P13.n.11
Idle state
OFF
OFF-ON
P13.n.12
Memory
OFF
OFF-ON
s
s
Note: this menu is divided into 4 sections for the limit thresholds LIM1…4
•• P13.n.01 – It defines to which automatic transfer switch measurements the limit threshold applies.
•• P13.n.02 – If the reference measurement is an electrical one, this defines if it refers to the S.Q1 (line 1) or S.Q2 (generator).
•• P13.n.03 – If the reference measurement is an internal multichannel measurement, the channel is defined with this
parameter.
•• P13.n.04 – It defines the operating mode of the limit threshold.
Max = LIMn enabled when the measurement exceeds P13.n.05 multiplied P13.n.06. P13.n.08 multiplied P13.n.09 is
the reset threshold. Min = LIMn enabled when the measurement is less than P13.n.08 multiplied P13.n.09. P13.n.05
multiplied P13.n.06 is the reset threshold. Min+Max = LIMn enabled when the measurement is greater than P13.n.05
multiplied P13.n.06 or less than P13.n.08 multiplied P13.n.09.
•• P13.n.05 and P13.n.06 – It defines the upper threshold, obtained by multiplying value P13.n.05 (unitary) by P13.n.06
(coefficient useful for example with a TV).
•• P13.n.07 – Upper threshold intervention delay.
•• P13.n.08 - P13.n.09 - P13.n.10 – As P13.n.05, P13.n.06, P13.n.07 referred to the lower threshold.
•• P13.n.11 – It inverts the state of limit LIMn.
•• P13.n.12 – It defines whether the threshold remains memorized and is reset manually through command menu (ON)
or if it is reset automatically (OFF).
35
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
14.14 Description of “Counters” menu
M14 – COUNTERS (CNTn, n = 1…4)
UoM
DEFAULT
RANGE
P14.n.01
Count source
OFF
OFF
ON
INPx
OUTx
LIMx
REMx
P14.n.02
Channel number (x)
1
OFF/1...99
P14.n.03
Multiplier
1
1÷1000
P14.n.04
Divisional
1
1÷1000
P14.n.05
Description of the counter
CNTn
(Text – 16 characters)
P14.n.06
Measurement unit
Umn
(Text – 6 characters)
P14.n.07
Reset source
OFF
OFF-ONINPx-OUTx-LIMx-REMx
P14.n.08
Channel number (x)
1
OFF/1-99
Note: this menu is divided into 4 sections for counters CNT1..4. Using this function it is possible to count how many time
one event, associated to a LIMx and/or external command by means of inputs, occurs.
•• P14.n.01 – Signal that increments the count (on the output side). This may be a threshold is exceeded (LIMx), an external input is enabled (INPx), etc.
•• P14.n.02 – Channel number x with reference to the previous parameter.
•• P14.n.03 – Multiplier K. The counted pulses are multiplied by this value before being displayed.
•• P14.n.04 – Divisional K. The counted pulses are divided by this value before being displayed. If other than 1, the counter
is displayed with 2 decimal points.
•• P14.n.05 – Counter description. 16-character free text.
•• P14.n.06 – Counter unit of measurement. 6-character free text.
•• P14.n.07 – Signal that resets the count. As long as this signal is enabled, the count remains zero.
•• P14.n.08 – Channel number x with reference to the previous parameter.
14.15 Description of “User alarms” menu
M15 – USER ALARMS (UAn, n=1…4)
UoM
DEFAULT
RANGE
OFF
OFF
INPx
OUTx
LIMx
REMx
1
OFF/1...99
P15.n.01
Alarm source
P15.n.02
Channel number (x)
P15.n.03
Text
UAn
(text – 20 char)
P15.n.04
Breaker opening
OFF
OFF
1
2
1+2
Note: this menu is divided into 4 sections for user alarms UA1…UA4.
••
••
••
••
36
P15.n.01 – It defines the digital input or internal variable that generates the user alarm when it is activated.
P15.n.02 – Channel number x with reference to the previous parameter.
P15.n.03 – Free text that appears in the alarm window.
P15.n.04 – Line to open in case of this alarm.
14.16 Description of “Alarms” menu
•• When an alarm is generated, the display will show an alarm icon, the code and the description of the alarm in the language selected.
Fig. 45
•• If the navigation keys in the pages are pressed, the pop-up window showing the alarm indications will disappear momentarily, to reappear again after a few seconds.
•• The red LED near the alarm icon on the front panel will flash when an alarm is active. In the area of synoptic on the
display remains a flashing icon that represents the type of the alarm.
•• Alarms can be reset by pressing the key OFF.
•• If the alarm cannot be reset, the problem that generated the alarm must be solved.
•• In the case of one or more alarms, the behaviour of the automatic transfer switch depends on the properties settings
of the active alarms.
14.17 Alarm properties
he ATS has the possibility to manage and generate different types of user alarms (User Alarms, Uax) and for each one can
be associated different properties:
•• Alarm enabled – General enabling of the alarm. If the alarm isn’t enabled, it’s like if it doesn’t exist.
•• Only AUT – The alarm can be generated only when automatic transfer switch is in AUT operating mode.
•• Retained alarm – It remains in the memory even if the cause of the alarm has been eliminated.
•• Global alarm – It activates the output assigned to this function.
•• Q1 Locked– When the alarm is active, no commands are sent to Q1.
•• Q2 Locked – Like previous property, referred to Q2.
•• Siren – It activates the output assigned to this function, as configured in the alarm table.
•• Inhibition – The alarm can be temporarily disabled by activating an input that can be programmed with the Inhibit
alarms function.
•• No LCD – The alarm is normally managed, but not shown on the display. This property is associated only if the alarm is
not retenitive.
37
Installation and user manual
Automatic transfer switch
4 226 82
14. Parameters
14.18 Alarm table
●
●
●
A03
Timeout Q1 (line 1)
●
●
●
●
A04
Timeout Q2 (line 2)
●
●
●
●
A05
S.Q1 (line 1) wrong phase sequence
●
●
●
●
A06
S.Q2 (line 2) wrong phase sequence
●
●
●
●
A07
Timeout load not powered
●
●
●
A08
External battery charger failure
A09
Emergency
●
●
●
●
A10
Protection intervention Q1 (line 1) (trip)
●
●
●
●
●
●
A11
Protection intervention Q2 (line 2) (trip)
●
●
●
●
●
●
A12
Q1 (line 1) generator not available
●
●
●
A13
Q2 (line 2) generator not available
●
●
●
A14
S.Q1 maintenance hours elapsed
●
A15
S.Q2 maintenance hours elapsed
●
A16
S.Q1 Maintenance operations
●
A17
S.Q2 Maintenance operations
●
A18
Auxiliary voltage failure
●
●
●
●
●
NO LCD
●
●
SIREN
●
●
LOCK Q2
GLOB. AL.
●
Battery voltage too high
LOCK Q1
RETAINED
Battery voltage too low
A02
ENABLED
A01
INHIBIT.
DESCRIPTION
ONLY AUT
CODE
●
●
●
14.19 Alarm description
CODE
DESCRIPTION
ALARM EXPLANATION
A01
Battery voltage too low
Battery voltage beyond the lowest threshold for a time exceeding the time set.
A02
Battery voltage too high
Battery voltage beyond the highest threshold for a time exceeding the time set.
Q1 (Line 1) timeout
The Q1 changeover device did not perform the opening or closing operation within the max. time set. After alarm A03 generation, the opening or closing command is inhibited.
Alarms are generated only if at least one of the two power
sources S.Q1 or S.Q2 are present.
A04
Q2 (Line 2) timeout
The Q2 changeover device did not perform the opening or closing operation within the max. time set. After alarm A04 generation, the opening or closing command is inhibited.
Alarms are generated only if at least one of the two power
sources S.Q1 or S.Q2 are present.
A05
S.Q1 (Line 1) wrong phase sequence
The phase sequence recorded on S.Q1 (line 1) does not correspond to the one programmed.
A06
S.Q2 (Line 2) wrong phase sequence
The phase sequence recorded on S.Q2 (line 2) does not correspond to the one programmed.
A03
38
CODE
DESCRIPTION
ALARM EXPLANATION
A07
Load not powered timeout
The load has been without power for a time longer than the
maximum specified with P05.11, either because both source
lines (S.Q1 and S.Q2) were absent or because both Q1 and Q2
remained open.
A08
External battery charger failure
Alarm generated by an input with the function Battery charger
alarm, while at least one of the source lines source is in the correct limits.
A09
Emergency
Alarm generated by the opening of the external input with
Emergency function. Both Q1 and Q2will be opened.
A10
Intervention for protection CTR Q1
Q1 (Line 1) has tripped because of a plant protection( contact
CTR), signalled by activation of the input with function Line 1
breaker protection trip.
A11
Intervention for protection CTR Q2
Q2 (Line 2) has tripped because of a plant protection (contact
CTR), signalled by activation of the input with function Line 2
breaker protection trip.
A12
S.Q1 Line 1 generator not available
Alarm generated by the input Generator S.Q1 (Line 1) ready.
A13
S.Q2 Line 2 generator not available
Alarm generated by the input Generator S.Q2 (Line 2) ready.
A14
Maintenance hours S.Q1
Alarm generated when the maintenance hours for S.Q1 arrive
to zero. See M12 menu. Use the command menu to restore the
working hours and to reset the alarm.
A15
Maintenance hours S.Q2
Alarm generated when the maintenance hours for S.Q2 arrive
to zero. See M12 menu. Use the command menu to restore the
working hours and to reset the alarm.
A16
Maintenance operations S.Q1
Alarm generated when the number of operations for S.Q1 reach
the value sated in the menu M12. Use the menu commands to
restore the function and to reset the alarm.
A17
Maintenance operations S.Q2
Alarm generated when the number of operations for S.Q2 reach
the value sated in the menu M12. Use the menu commands to
restore the function and to reset the alarm.
A18
Auxiliary voltage failure
The device that manages the draw of auxiliary power supply
from one of the available lines (DPS-auxiliary contact) signals a
failure or improper operation.
A01
User alarms
The user alarm is generated by enabling the variable or
associated input in menu M15.
39
Installation and user manual
Automatic transfer switch
4 226 82
15. Function I/O
15.1 Programmable inputs function table
••
••
••
••
The following table shows all the functions that can be attributed to the INPn programmables digital inputs.
Each input can be set for an reverse function (NA – NC), delayed energizing or de-energizing at independently set times.
Some functions require another numeric parameter, defined in the index (x) specified by parameter P10.n.02.
See menu “M10 Programmable inputs” for more details.
The configuration installed on ATS by Legrand ensures the correct work if standard wiring diagrams supplied are respected.
WARNING: the modify of parameters could generate incompatibility with supplied wiring diagrams. It is recommended
to not modify the original configuration.
Using expansion modules is possible to increase the amount of inputs available in order to do additional checks and
controls (this solution is recommended to avoid the change of work mode of inputs in case of specific applications).
40
FUNCTION
DESCRIPTION
Disabled
Input disabled
Configurable
Free user configuration
Q1 closed (Feedback 1)
Auxiliary contact informing the automatic transfer switch
of the open/closed status of Q1 contact OC line 1. Wiring
mandatory.
Q2 closed (Feedback 2)
Auxiliary contact informing the automatic transfer switch of
the open/closed status of Q2 contact OC line 2. Wiring mandatory.
Q1 protection (Trip 1)
When the contact is closed, it informs the ATS of trip status
(CTR). It generates an alarm for Q1 intervention.
Q2 protection (Trip 2)
When the contact is closed, it informs the ATS of trip status
(CTR). It generates an alarm for Q2 intervention.
Transfer to secondary line (remote start on-load)
When closed, it causes changeover to secondary line even
if main line voltage is within limits.
It could be used to change priority between S.Q1 and
S.Q2. The secondary line circuit breaker remains activated
until this line remains within limits.
It can be used for EJP function.
Inhibit Return to main line S.Q1
In AUT mode, when closed, it inhibits the return to main
line after it has reverted to the limit range.
It is used to prevent the second power cut out due to retransfer from occurring automatically at an unforeseeable
time.
Start Generator
In AUT mode, when closed, it causes the generator to start
after the delay specified by P05.14. It can be used for EJP
function
Emergency
NC contact which, if open, it causes both circuit Q1 and Q2
open and it generates alarm A09.
Generator ready S.Q1
When closed it signals that the generator connected to
line 1 is available for use. If this signal is missing, alarm A12
is generated
Generator ready S.Q2
When closed it signals that the generator connected to
line 2 is available for use. If this signal is missing, alarm A13
is generated
External S.Q1 control
Line 1 voltage control signal from external device. Enabled, it indicates the voltage is within the limits
FUNCTION
DESCRIPTION
External S.Q2 control
Line 2 voltage control signal from external device. Enabled, it indicates the voltage is within the limits
Enable Load on S.Q1
It allows load connection on S.Q1, in addition to internal
controls.
Enable Load on S.Q2
Like previous, referred to S.Q2
Delay 1 bypass
Reset the delay presence on S.Q1
Delay 2 bypass
Reset the delay presence on S.Q2
Keypad lock
If closed, it locks all the functions from front keypad except
measure viewing
Lock Parameters
If closed, it locks the access to setup menus
Lock remote control
If closed, it locks write access through serial interface ports
Siren OFF
It disables the siren
Automatic test
Starts the periodic test managed by an external timer
Battery charger alarm
With the input enabled, it generates the alarm A08
External battery charger fault. The alarm is only generated
when there is main voltage
Alarms inhibition
If enabled, it disables the alarms that have the property
Inhibit alarms activated
Alarms reset
It resets the retained alarms for which the condition that
triggered the same has stopped
Command menu C(xx)
It executes the command from the commands menu
defined by index parameter (xx)
Key OFF simulation
Closing the input is the equivalent of pressing the key.
Key MAN simulation
Closing the input is the equivalent of pressing the key.
Key AUT simulation
Closing the input is the equivalent of pressing the key.
Automatic test inhibition
It inhibits the automatic test
LED Test
It makes all the LEDS on the front panel flash
Q1 closing
Close the Q1 in manual mode
Q1 opening
Open the Q1 in manual mode
Q1 toggling
Toggle the Q1 in manual mode
Q2 closing
Close the Q2 in manual mode
Q2 opening
Open the Q2 in manual mode
Q2 toggling
Toggle the Q2 in manual mode
Auxiliary voltage ready
NC contact which, if it is open, generates alarm A18. Used,
for example, in conjunction with the alarm relay of DPS.
Revision
In case of revision of the system, if enabled, causes:
. Switch in OFF mode
. Disabling alarms feedback A03 - A04
. Excitement of any undervoltage coils
41
Installation and user manual
Automatic transfer switch
4 226 82
15. Function I/O
15.2 Output function table
The configuration installed on ATS by Legrand, ensures the correct work if standard wiring diagrams supplied are
respected.
WARNING: the modify of parameters could generate incompatibility with supplied wiring diagrams. It is recommended to not modify the original configuration.
Using expansion modules is possible to increase the amount of outputs available in order to do additional checks
and controls (this solution is recommended to avoid the change of work mode of outputs in case of specific applications).
••
••
••
••
The following table shows all the functions that can be assigned to the OUTn programmable digital inputs.
Each output can be configured so it has a normal or reverse (NOR or REV) function.
Some functions require another numeric parameter, defined in the index (x) specified by parameter P11.n.02.
See menu M11 Programmable outputs for more details.
FUNCTION
DESCRIPTION
Disabled
Output disabled
Configurable
User configuration free
Close S.Q1 contactor/
circuit breaker
Command to close Q1
Open S.Q1 circuit breaker Command to open Q1and eventual springs charging
Close S.Q2 )contactor/
circuit breaker
Command to close Q2
Open S.Q2 circuit breaker Command to open Q2 and eventual springs charging
Open S.Q/ S.Q2
Open both Q1 and Q2.
UVR Coil S.Q1 (line 1)
It controls the UVR, opening Q1 before the spring load cycle
UVR Coil S.Q2 (line 2)
It controls the UVR, opening Q2 before the spring load cycle
S.Q1 generator control
Start /Stop remote control of S.Q1 generator
S.Q2 generator control
Start /Stop remote control of S.Q2 generator
Automatic transfer switch Automatic transfer switch in automatic mode, without alarms, ready to switch
ready
42
Global alarm
Output enabled in the presence of any alarm with the Global alarm propriety enabled
S.Q1 status
Output energized when there are all conditions to be able to connect the load to the S.Q1
S.Q2 status
Output energized when there are all conditions to be able to connect the load to theS.Q2
Siren
Actives the contact for the external siren
Operating mode
Output energized when the ATS is in one of the modes set with parameter P12.03
OFF mode
Energized when the automatic transfer switch is OFF
MAN mode
Energized when the automatic transfer switch is in MANUAL mode
AUT mode
Energized when the automatic transfer switch is in AUT mode
REM(x) remote variable
Output controlled by remote variable REMx (x=1..16)
LIM limits (x)
Output controlled by the state of the limit threshold LIM(x) (x=1..4) defined by the index
parameter
Dummy load
Output enabled when self-test with dummy load is running.
Load connected to S.Q1
Q1 closed
Load connected to S.Q2
Q2 closed
Alarms A01-Axx
Output energized with alarm Axx is enabled (xx=1…alarms number)
Alarms UA1..Uax
Output energized with alarm Uax is enabled (x=1…4)
16. Commands menu
•• The commands menu allows executing some operations like reading peaks resetting, counters clearing, alarms reset, etc.
•• If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration.
•• The following table lists the functions available in the commands menu, divided by the access level required.
CODE
COMMAND
ACCESS LEVEL
DESCRIPTION
C01
Reset maintenance hours S.Q1
Advanced
Reset maintenance interval hours S.Q1
C02
Reset maintenance hours S.Q2
Advanced
Reset maintenance interval hours S.Q2
C03
Reset maintenance operations
S.Q1
Advanced
Reset maintenance interval operations S.Q1
C04
Reset maintenance operations
S.Q2
Advanced
Reset maintenance interval operations 2
C05
Reset generic counters CNTx
User
Reset generic counters CNTx.
C06
Reset LIMx limits
User
Reset limits LIMx variable status
C07
Reset hours counter S.Q1/S.Q2
Advanced
Reset counter of presence / absence of S.Q1 and
S.Q2 in the respective limits
C08
Reset hours counter Q1/Q2
Advanced
Reset counter opening / closing Q1 and Q2
C09
Reset breaker operation
Advanced
Reset Q1/Q2 operations counter
C10
Reset events list
Advanced
Reset the list of historical events
C11
Reset default parameters
Advanced
Reset all the parameters in the setup menu to the
default values
C12
Save parameters in backup memory
Advanced
Copy the parameters currently set to a backup for
restoring in the future
C13
Reload parameters from backup
memory
Advanced
Transferthe parameters saved in the backup memory to the active settings memory
C14
Forced I/O
Advanced
Enable test mode so you can manually energize
any output.
In this mode the installer alone is responsible for
the output commands
C15
Reset A03 – A04 alarms
Advanced
Restore the opening and closing command of the
commutation devices after generating alarms A03
– A04
C16
Simulate line failure
Advanced
The device moves to AUT mode and simulates
the lack of the priority line for one minute. It then
switches the load with the automatic procedure as
programmed
•• Once the required command has been selected, press to execute it. The device will prompt for a confirmation. Pressing again, the command will be executed.
•• To cancel the command execution press RESET.
•• To quit command menu press RESET.
43
Installation and user manual
Automatic transfer switch
4 226 82
17. Installation
•• The automatic transfer switch is designed with IP40 protection.
•• Insert the device into the panel hole,
•• From inside the panel, for each four of the fixing clips, position the clip in its square hole on the housing side, then move
it backwards in order to position the hook.
Fig. 46 - Mounting
••
••
••
••
Repeat the same operation for the four clips.
Tighten the fixing screw with a maximum torque of 0,5Nm.
In case it is necessary to dismount the system, unloose the screws.
For the electrical connection see the Legrand wiring diagrams.
18. Terminals position
b
c
CODE
d
OUT 2
OUT 1
a
e
OUT 7
OUT 6
OUT 5
OUT 4
COM
OUT 3
INP 6
INP 5
INP 4
INP 3
INP 2
INP 1
OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
4 226 82
f
g
h
i
l
m
Fig. 47 - Rear view
DESCRIPTION
a
Line 1 voltage control (S Q1)
b
Line 2 voltage control (S Q2)
c
OUT1 - OUT2 - (NO) Programmable relay
d
AUX 240 VAC power supply
e
COM 1
f
COM 2
g
AUX DC 12-24 VDC power supply
h
Programmable inputs (INP xxx)
i
OUT3 NO/NC Programmable relay
l
OUT4 /5 NO/NC Programmable relay
m
OUT6/7 NO/NC Programmable relay
19. Dimensions
43,30
144
10
138
AUT
LOAD
Q1
RESET
MENU
OFF
_
AUT
OK
Q2
LINE 2
144
LINE 1
138
4 226 82
MAN
+
IR COM
MENU
IEC 60947-6-1
35
Fig. 48 - Dimensions
44
20. Technical characteristics
TECHNICAL CHARACTERISTICS
AC Supply : terminals 13, 14
Rated voltage Us
100 - 240VAC
110 - 250VDC
Operating voltage range
90÷264VAC
93,5÷300VDC
Frequency
45 - 66Hz
Power consumption/dissipation
3,8W – 9,5VA
Immunity time for microbreakings
≤50ms (110VAC)
≤250ms (220VAC)
≤25ms (110VAC)
≤120ms (220VAC)
Recommended fuses
}
(with expansion module)
F1A Type F
DC supply: terminals 31, 32
Battery rated voltage
12 o 24Vdc indifferently
Operating voltage range
7,5…33VDC
Maximum current consumption
230mA a 12VDC e 120mA a 24VDC
Maximum power consumption/dissipation
2,9W
Line 1 and Line 2 voltage inputs: terminals 1-4 and 5-8
Maximum rated voltage Ue
480 Vac L-L (277VAC L-N)
Measuring range
50-576 Vac L-L (333V Vac L-N)
Frequency range
45-65Hz
Measuring method
TRMS
Measuring input impedance
> 0,5MΩ L-N
Wiring mode
Single-phase, two-phase, three-phase with or without
neutral or balanced three-phase system.
> 1,0MΩ L-L
Measuring accuracy
Mains and generator voltage
±0,25% f.s. ±1digit
Real time clock
Energy storage
Back-up capacitors
Operating time without supply voltage
About 5 minutes
Digital inputs: terminals 15 - 20
Input type
Negative
Current input
≤8mA
Input “low” voltage
≤2,2V
Input “high” voltage
≥3.4V
Input delay
≥50ms
OUT1 and OUT 2 outputs: terminals 9,10 e 11,12
Contact type
2 x 1 NO
Rated current
AC1 - 8A 250VAC DC1 - 8A 30VDC
AC15 -1,5A 250VAC
Max rated voltage
300 Vac
Mechanical / electrical endurance
107 / 105 ops
continues...
45
Installation and user manual
Automatic transfer switch
4 226 82
20. Technical characteristics
TECHNICAL CHARACTERISTICS
OUT3 output: terminals 22, 23, 24
Contact type
1 changeover
Rated current
AC1 - 8A 250VAC DC1 - 8A 30VDC
AC15 -1,5A 250VAC
Max rated voltage
300 Vac
Mechanical / electrical endurance
107 / 105 ops
OUT4 and OUT 5 outputs: terminals 25,26,27
Contact type
2 x 1 NO + Common contact
Rated current
AC1 ‐ 8A 250Vac DC1 ‐ 8A 30Vdc
AC15 ‐1,5A 250 Vac
Max rated voltage
300 Vac
Mechanical / electrical endurance
107 / 105 ops
Maximum current at contact common
10A
OUT6 and OUT 7 outputs: terminals 28,29,30
Contact type
2 x 1 NO + Common contact
Rated current
AC1 ‐ 8A 250Vac DC1 ‐ 8A 30Vdc
AC15 ‐1.5A 250Vac
Max rated voltage
300 Vac
Mechanical / electrical endurance
107 / 105 ops
Maximum current at contact common
10A
Contact type
2 x 1 NO + common contact
Insulation voltage
AC Supply
Rated insulation voltage
Ui 250Vac
Rated impulse withstand voltage
Uimp 7.3kV
Power frequency withstand voltage
3kV
Line 1 and Line 2 voltage inputs
Rated insulation voltage
Ui 480Vac
Rated impulse withstand voltage
Uimp 7.3kV
Power frequency withstand voltage
3.8kV
OUT1 and OUT 2 outputs
Insulation type
Single between OUT1 and OUT 2
Double toward the remaining groups
Rated insulation voltage
Ui 250VAC
Rated impulse withstand voltage
Power frequency withstand voltage
Single
Double
Uimp 4,8kV
Rated impulse withstand
voltage
1,5kV
Power frequency withstand
voltage
OUT 3 output
46
Contact type
Ui 250Vac
Rated current
Uimp 7.3kV
Max rated voltage
3kV
TECHNICAL CHARACTERISTICS
OUT4-5 and OUT 6-7 outputs
Insulation type
Single between OUT4-5 and OUT 6-7
Double toward the remaining groups
Rated insulation voltage
Ui 250Vac
Single
Rated impulse withstand voltage
Power frequency withstand voltage
Uimp 4.8kV
Rated impulse withstand
voltage
1.5kV
Power frequency withstand
voltage
Ambient operating conditions
Operating temperature
-30÷70°C
Storage temperature
-30÷80°C
Relative humidity
<80% (IEC/EN 60068-2-78)
Maximum pollution degree
2
Overvoltage category
3
Measurement category
III
Climatic sequence
Z/ABDM (IEC/EN 60068-2-61)
Shock resistance
15g (IEC/EN 60068-2-27)
Vibration resistance
0.7g (IEC/EN 60068-2-6)
Connections
Terminal type
Plug-in / removable
Cable cross section (min… max)
0.2-2.5 mm² (24…12 AWG)
Tightening torque
0.5 Nm
Housing
Version
Flush mount
Material
Polycarbonate
Degree of protection
IP40 on front
IP20 terminals
Weight
680g
Certifications and compliance
Certifications obtained
EAC
Reference standards
IEC/EN 61010-1
IEC/EN 61000-6-2
IEC/ EN 61000-6-3
IEC/EN 60947-6-1
47
Installation and user manual
Automatic transfer switch
4 226 82
LEGRAND
Pro and Consumer Service
BP 30076 - 87002
LIMOGES CEDEX FRANCE
www.legrand.com
Installer stamp
Legrand reserves at any time the right to modify the contents of this booklet and to communicate,
in any form and modality, the changes brought to the same.