Voltage AC Transducer
Voltage AC Transducer
MT406
 Sinusoidal AC voltage measurements
 Voltage range measurements up to 500 VL-N
 Galvanic insulation between input and output
 Accuracy class 0.5
 Self powered
 Housing for DIN rail mounting
WWW.ISKRASISTEMI.SI
Page 1
DESCRIPTION
MT406 is intended for measuring and monitoring voltage in
electrical power network. Voltage input is electrically insulated
from the system by means of voltage transformer. The signal
is rectified, smoothed and amplified into an independent DC
current output.
APPLICATION
The MT406 voltage transducer is used for a permanent
monitoring of a single-phase voltage value. PLCs, PCs,
microprocessor control, indicators, alarms units etc. can be
operated by the output signal.
Voltage input can be connected either directly to low-voltage
network or shall be connected to network via a corresponding
voltage transformer (with standard 100V output).
TECHNICAL DATA
MEASURING INPUT
Standard nominal input voltage
(UN)
Measuring range limit values
Overload capacity:
Max. measured value (cont.)
Max. allowed value
Nominal frequency (fN)
Measuring frequency range
Consumption
57,7, 63.5, 69.3, 100, 110,
115, 120, 127, 220, 230,
240, 250, 380, 400, 415,
440, 500 V
0 ... 50 V to 0 ... 500 V
acc. to EN 60688
1,2 × UN
2 × UN ; 1 s, 10 times, 10
s interval
50, 60 Hz
fN ± 10 %
< 2 VA
MEASURING OUTPUT
Standard ranges IAN:
0 … 1 mA,
0 … 5 mA,
0 … 10 mA,
0 … 20 mA
10 V
RB max =10 V / IAN
Burden voltage:
External resistance:
Maximal output voltage
(open circuit current output)
< 25 V
Maximal output current
2 × IAN
Residual ripple
< 1 % p.p.
Response time
< 300 ms
The output may be either short or open-circuited. It is
electrically insulated from all other circuits.
ACCURACY (according to EN 60688)
Reference value:
Basic accuracy:
Reference conditions:
Output end value
Class 0.5
Voltage
Ambient temperature range
Frequency
Output burden
Additional error:
20 % … 100 % x UN
15 … 30°C
fN ± 2 Hz
RB max / 2
Temp influence:
Frequency influence:
Burden influence:
max. ± 0.3 % / 10 K
0,25 % / (Δ 5 Hz)
0,1 % / (Δ Rbmax / 2)
SAFETY:
Protection class:
Pollution degree
Installation category
Test voltage
Enclosure material
Enclosure protection
Page 2
acc. to EN 61010-1
II
2
CAT III 600V MT406 > 300Vac
CAT III 300V MT406 ≤ 300Vac
50 Hz, 1 min.
5200 V, measuring input versus
measuring output and other
surface
PC/ABS (acc. to UL 94 V-0)
IP 20 (acc to EN 60529)
WWW.ISKRASISTEMI.SI
COMPLIANCE WITH STANDARDS:
CONNECTION
Standard EN
Description
61010-1:2001
Safety requirements for electrical
equipment for measurement, control
and laboratory use
60688:1995/A2:2001
Electrical measuring transducers for
converting AC electrical variables into
analogue and digital signals
61326-1:2006
EMC requirements for electrical for
measurements, control and laboratory
use- Part 1:General requirements
60529:1997/A1:2000
Degrees of protection provided by
enclosures (IP code)
60068-2-1/ -2/ -6/
-27/-30
Environmental testing (-1 Cold, -2 Dry
heat, -30 Damp heat, -6 Vibration, -27
Shock)
UL 94
Tests for flammability of plastic
materials for parts in devices and
appliances
ORDERING
For ordering it is necessary to declare type of the transducer
(MT406), measuring range and output range.
Ordering code: MT406 - ab
MT406
ENVIRONMENTAL CONDITIONS:
Nominal temperature range
Operating temp. range
Storage temperature range
Average annual humidity
Altitude
Indoor use only
-10 … 15 … 30 … 55 °C
-20 to + 70 °C
-40 to + 70 °C
93% r.h.
2000 m
a
Measuring range:
MECHANICAL DATA
Dimensions
Mounting
Enclosure material
Flammability
Connection terminals
W45 × H75 × D105 mm
Rail mounting 35 × 15 mm
(acc. to EN 50022)
PC/ABS
Acc. to UL 94 V-0
2
4.0 mm solid wire
Weight
2.5 mm stranded wire
approx. 280 g
2
Non – standard versions
AMBIENT TESTS
Vibration withstand
Shock withstand
7g, 3 … 100 Hz, 1 oct/min
10 cycles in each of three axes
300 g, 8 ms pulse
6 shocks in each of three axes
b
Output signal:
Value
Code
0 … 57.74 V
1
0 … 63.5 V
2
0 … 69.3 V
3
0 … 100 V
4
0 … 110 V
5
0 … 115 V
6
0 … 120 V
7
0 … 127 V
8
0 … 220 V
9
0 … 230 V
A
0 … 240 V
B
0 … 250 V
C
0 … 380V
D
0 … 400V
E
0 … 415V
F
0 … 440 V
G
0 … 500 V
H
0…XV
X
0 … 1 mA
1
0 … 5 mA
2
0 … 10 mA
3
0 … 20 mA
4
Non - standard ratings are available on request.
ORDERING EXAMPLE
Measuring transducer MT406, with measuring
range 0 … 57.74V and output range 0 … 10 mA:
MT406 - 13
Printed in Slovenia Subject to change without notice Version 1.01 / Sep-2013 GB P 22.496.503