Technical Data ISU Series Underceiling/Console

Technical Data ISU Series Underceiling/Console
Underceiling/Console
Split System Air Conditioners
Technical Data
ISU Series
Featuring
SAT-2 Controller &
Long Life Epoxy Coated Outdoor Coil
Nominal Cooling Capacity
8.6 kW – 15 kW
JULY 2008
ISU SERIES – UNDERCEILING OR CONSOLE SPLIT SYSTEM AIR CONDITIONERS
GENERAL
ISU – Indoor Unit.
OSA ✳RK – Outdoor unit, reverse cycle.
Quiet
The carefully designed fans ensure the ISU
units' emit minimal noise, while maintaining
the efficiency of the unit.
Application
Typically installed in office areas, shops,
restaurants, night clubs and other commercial
and public spaces where unobtrusive air
conditioning is required.
The Outdoor Unit is also very quiet with
a compressor/motor within a hermetically
sealed casing which in turn is mounted in an
acoustically insulated compartment.
Underceiling units are ideal for rooms with
limited or no ceiling space. Sloping ceilings
are not a problem as the units can still be
suspended level.
Circulates
The air discharge louvre is motorised to
distribute conditioned air high and low into
the room. If preferred, however, the motor
can be switched off and the louvre can be set
at a fixed angle. Left and right air distribution
is manually set to suit.
ISU/OSA systems are available for reverse
cycle (heat piump) applications.
The system includes a temperature sensing
head pressure control which enables the
system to compensate for outdoor ambient
temperatures below 20°C on cooling cycle,
and above 15°C on heating cycle. Design
The slimline low profile styling allows the
Indoor Unit to be suspended unobtrusively
under the ceiling, where it does not
use valuable office wall or floor space.
Alternatively, if it is more convenient the unit
can be mounted vertically as a console, e.g. under a window.
Accessible
The filter is easily accessible for periodic
cleaning via the indoor unit's hinge down/
removable return air filter panel.
Durable Outdoor Unit
The Outdoor Unit is built to withstand the
rigours of the weather, year in and year out.
The cabinet is made from the high quality
galvanised steel, finished with tough ovencured polyester powder coating and fixed
with stainless steel fasteners. The outdoor
coil fins are epoxy coated for extra protection
in corrosive environments, e.g. salt laden
sea air.
Refrigerant R410A
Each complete system uses refrigerant
R410A which is deemed to have zero ozone
depletion potential.
Efficient
These reverse cycle (heat pump) systems
are very efficient. For every 1 kW of power
consumed approx. 3 kW of heating is
created. The outdoor unit incorporates a high
efficiency scroll compressor. Heat exchange
coils incorporate inner grooved (rifled) tube
for better heat transfer.
Self Diagnostics
The Outdoor Unit's Controller (OUC) has a
display of LEDs to indicate faults and running conditions. A general fault indicator is
included for interface to external systems.
OPTIONAL ACCESSORIES
Outdoor Unit:
1. Fault indicating auxillary relay board.
2. Wall mounting brackets.
Technical Backup
Manufacturer's representation assures
quality technical backup, quick and efficient
parts and service.
The manufacturer operates a quality
management system that conforms to AS/NZS ISO 9001:2000.
SAT-2 CONTROLLER
The Outdoor Unit is designed to be
freestanding, or wall mounted with the
optional wall mounting brackets.
Features
• Cool / Dry / Fan modes.
• Heat / Auto modes
• Auto / High / Medium / Low fan speed
selection.
• Temperature setting range from 16°C
– 30°C.
• LED to indicate status of the unit
[Power On/Off].
• Room temperature display.
• Real time clock.
• 7 day timer – two start and/or stops per day
• On demand countdown run timer, up to 9 hours.
User Friendly
ISU unit's are supplied with a SAT-2
Controller. This thermostat has been
designed to maintain a high level of comfort
for room occupants. Emphasis has been
placed on providing controls that are
easy to use — despite the sophisticated
microprocessor system that runs it. Use of
the Auto and Timer function settings allows
you to 'set it and forget it'.
• Auto-Restart or No Restart after power
failure.
• Continuous or Intermittent selection of
fan run-on in dead zone.
• Backlit screen for ease of reading; changes
colour for each mode.
• Soft touch tab keys
• Battery backup (Lithium).
• Sleep function.
• Audible beep to acknowledge key entry or
wireless remote control.
• Low voltage control cable.
• Colour: white and light grey (Keypad - gold
and blue).
• Optional: Infra Red Remote controller
Remote return air sensor, Extended interface lead, Extra Wall Control plaque.
cooling capacity (kW)
ISU 90 / OSA 95
INDOOR COIL
E.A.T.
INDOOR
FAN
MODELS
Outdoor Indoor
Unit Unit
ISU Series
AIR
SPEED
l/s
HIGH
335
ISU 140 / OSA 140
HIGH
570
ISU 160 / OSA 160
HIGH
800
OUTDOOR COIL ENTERING AIR TEMPERATURE °C D.B.
27
31
35
39
23
W.B.
°C
D.B.
°C
Total
Sens.
Total
15
17
19
21
15
17
19
21
15
17
19
21
21
23
27
31
21
23
27
31
21
23
27
31
6.2
6.3
7.2
8.1
9.5
9.7
11.0
12.4
10.8
11.1
12.5
14.1
8.0
6.3
8.7
6.3
9.5
7.3
10.3 8.2
12.3 9.6
13.3 9.7
14.5 11.2
15.8 12.5
14.0 11.0
15.2 11.1
16.5 12.7
17.9 14.3
7.8
8.7
9.5
10.2
12.0
13.3
14.5
15.6
13.6
15.2
16.5
17.8
Sens.
Total
Sens.
Total
Sens.
Total
Sens.
7.7
8.2
8.9
9.8
11.8
12.5
13.6
15.1
13.5
14.3
15.5
17.2
7.2
7.9
8.6
9.3
11.0
12.1
13.2
14.2
12.5
13.8
15.0
16.2
5.7
5.9
6.7
7.6
8.7
9.0
10.3
11.7
9.9
10.2
11.7
13.3
6.3
7.5
8.2
8.9
9.6
11.5
12.5
13.7
11.0
13.1
14.3
15.6
5.4
5.6
6.7
7.4
8.2
8.6
10.2
11.4
9.4
9.8
11.7
13.0
6.3
7.0
7.0
8.7
9.6
10.7
11.4
13.4
11.0
13.0
13.0
15.2
5.4
5.5
5.5
7.0
8.2
8.4
9.6
10.8
9.4
11.0
11.0
12.3
6.1
6.1
6.8
8.0
9.3
9.4
10.4
12.3
10.6
10.7
11.9
14.0
Note: Allow for pipe length capacity
loss (refer overleaf).
E.A.T. = Entering Air Temperature
= Nominal Capacity (kW)
Total = Total Capacity (kW) Sens. = Sensible Capacity (kW)
43
Total Sens.
Indoor Air Flow Correction Factors @ nominal conditions
Total Capacity
Sensible Capacity
Indoor Air Flow (%)
Rated
-10%
1.0
0.975
1.0
0.950
-20%
0.95
0.89
+10%
1.025
1.050
heating capacitY (kW) – Reverse Cycle Systems
MODELS
Outdoor Indoor
Unit
Unit
ISU 90 / OSA 95R
ISU 140 / OSA 140R
ISU 160 / OSA 160R
INDOOR
ENTERING
– 5
AIR TEMP. N
°C D.B. G
outdoor coil ENTERING AIR TEMPERATURE (e.a.t.) °c d.b.
– 3
G
– 1
N
1
3
5
7
9
G
N
G
N
G
N
G
N
G
N
G
5.6 5.0
6.1 5.5
6.5
5.8
6.9
6.1
7.3
6.2
7.9
7.1
8.4
8.3
8.8 8.8
20
5.5 4.9
5.9 5.3
6.4
5.7
6.8
6.0
7.2
6.1
7.7
6.9
8.2
8.1
8.6 8.6
25
5.3 4.8
5.7 5.2
6.1
5.5
6.5
5.7
6.9
5.8
7.4
6.7
7.9
7.8
8.3 8.3
15
8.6 7.8
9.3 8.4
10.0 9.0 10.6
9.3 11.2 9.5
12.1 10.9 12.9 12.7 13.5 13.5
20
8.5 7.6
9.1 8.2
9.8
8.8 10.4
9.2 11.0 9.3
11.8 10.7 12.6 12.5 13.2 13.2
25
8.1 7.3
8.8 7.9
9.4
8.5 10.0
8.8 10.6 9.0
11.4 10.3 12.1 12.0 12.7 12.7
15
10.0 9.0
10.8 9.7
11.5 10.4 12.3 10.8 13.0 11.0
14.0 12.6 14.9 14.7 15.6 15.6
20
9.8 8.8
10.6 9.5
11.3 10.2 12.0 10.6 12.8 10.8 13.7 12.3 14.6 14.4 15.3 15.3
25
9.4 8.5
10.2 9.2
10.9 9.8 11.6 10.2 12.3 10.4 13.2 11.9 14.1 13.9 14.8 14.8
G = Gross Heating Capacity kW, based on nominal air flow.
N = Net Heating Capacity kW allowing for average defrost.
Note: Allow for pipe length capacity loss.
= Nominal Capacity (kW)
Pipe Length CAPACIty Loss
ON Cooling Cycle Due To Pressure Drop
Note: Loss percentage is approximate only. No allowance made for vertical piping or bends.
MODELS
Indoor Outdoor
Unit
Unit
ISU 90 / OSA 95
ISU 140 / OSA 140
ISU 160 / OSA 160
N
15
Interconnecting
Pipe Size OD (mm)
Liquid
Suction
10
16
10
19
13
22
5
2%
0.75 %
0.7 %
Equivalent Pipe Length (m)
10
15
20
4%
6%
8%
1.5 %
2.25 %
3%
2.1 %
3.4 %
4.7 %
Additional Pipe Length to allow per Bend
Suction Pipe Size OD
16 mm
19 mm
22 mm
Long 90° Radius (2 x pipe dia.)
0.30 m
0.43 m
0.46 m
30
12 %
5%
6.1 %
SOUND LEVELS
ISU Indoor Units
Sound Pressure Levels (SPL)
As measured in an anechoic chamber, 1 m below and to the side of the unit. No allowance for sound
reflection within a room. Add 13 dB to convert to Sound Power Levels (SWL).
MODEL
OCTAVE BAND FREQUENCY Hz
SPL
FAN
SPEED
AIR FLOW
l/s
dB(A)
LOW
240
44
41
44
46
36
29
22
MED
280
46
43
46
46
41
34
27
HIGH
335
50
47
49
49
45
39
32
LOW
380
43
44
44
43
36
28
19
MED
480
48
48
48
48
41
35
25
HIGH
570
53
50
52
52
47
41
32
LOW
650
55
53
53
54
49
43
35
MED
710
56
55
55
55
52
45
38
HIGH
800
58
56
53
58
54
47
40
2k
4k
2k
4k
125
250
500
1k
2k
4k
SOUND PRESSURE LEVELS (SPL) dB
INDOOR UNITS
ISU 90
ISU 140
ISU 160
Sound Pressure Levels (SPL) Within A Room
Indoor Units: Add the room reflection effect below to the
anechoic Sound Pressure Levels above to obtain Sound Pressure Levels within a room.
OCTAVE BAND FREQ. Hz
ROOM TYPE
125
250
SOFT
9
5
2
2
2
2
MEDIUM
10
6
5
4
4
4
HARD
13
12
10
9
9
8
125
250
500
1k
ROOM REFLECTION EFFECT
OSA Outdoor Units
Sound Power Levels (SWL)
MODEL
FAN
SPEED
SWL
OCTAVE BAND FREQUENCY Hz
dB(A)
500
1k
SOUND POWER LEVELS (SWL) dB
OUTDOOR UNITS
OSA 95
OSA 140
OSA 160
LOW
65
67
66
66
58
51
47
MED
65
69
67
66
60
54
49
LOW
67
73
68
65
61
56
49
MED
69
74
69
66
63
58
51
LOW
70
77
71
68
65
59
52
MED
71
77
73
69
66
60
52
Sound Pressure Levels (SPL)
Outdoor Units: Deduct 16 dB from Sound Power Level above to obtain Sound Pressure Level at 3 metres.
DIMENSIONS (mm)
Not to Scale
Indoor Units
Fig. 1 ISU 90, 140, 160 Underceiling/Console
FLOOR MOUNTING BASE
(REMOVABLE)
DRAIN EXIT POSITION
& STANDARD REFRIG.
PIPE EXIT
ALTERNATIVE
REFRIGERATION
PIPE EXIT
35
UNDERCEILING
MOUNTING
170
275
MOUNTING
CENTRE
(A – 100)
HANGING CENTRES
MOUNTING
BRACKET
MODEL
ISU 90
ISU 140
ISU 160
OPTIONAL
WALL
MOUNTING
(RECESSED)
Dim.A
1260
1860
1860
MOUNTING
BRACKET
MOUNTING
BRACKET
100
265
HINGE DOWN
FILTERS
Fig. 2
DRAIN
19 OD
685
A
OSA 95, 140, 160
Outdoor Units
MIN.CLEARANCE:OSA95:100;OSA140/160:150
MIN.CLEARANCE:
OSA95:100;
OSA140/160:150
750MIN.CLEARANCE
MODEL
OSA 95
OSA 140
OSA 160
2000MIN.CLEARANCE*
A
B
1035 665
1075 865
1125 970
C
400
420
420
ACCESS
PANEL
B
25DIA.
ELECTRICAL
CONDUIT
HOLES
REFRIG.
CONN’S
72
E
D
MTGCTR
12DIA.HOLE+SLOT
A
OVERALL
F
25DIA.
DRAIN
HOLE
E
217
225
225
F
235
200
200
G
349
375
375
NOTE
Materials and specifications subject
to change without notice due to the
manufacturer's ongoing research and
development programme.
OVERALL
25DIA.
DRAIN
HOLE
D
582
651
700
G
MTGCTR
C
OVERALL
27
SPECIFICATIONS SUMMARY
SPLIT SYSTEMS
Single Phase
Indoor Unit : Outdoor Unit :
1
Cooling Capacity *
kW
Heating Capacity * Three Phase
ISU 90KD
ISU 140KD
ISU 160KD
ISU 140KD
ISU 160KD
OSA 95RKS
OSA 140RKS
OSA 160RKS
OSA 140RKT
OSA 160RKT
8.6
13.2
15.0
13.2
15.0
kW
8.2
12.6
14.6
12.6
14.6
E.E.R. (Cooling)
3.04
3.37
2.88
3.37
3.10
Power Source *3
volts
230
230
230
400
400
m
40
50
50
50
50
2
Recom'd Max. Line Length
Max. Height Separation Between Indoor & Outdoor Units: ( Indoor Unit above Outdoor / Outdoor Unit above Indoor )
m
16/16
18 / 18
18 / 18
18 / 18
18 / 18
Running Amps (Total) / Ext'l Fuse
A
12.8 / 25
17 / 45
23 / 45
8.6,6.5,6.5 / 25
10.5,8,8 / 25
INDOOR
UNITS
Low
240
380
650
380
650
Air Flow (l/s)
Med
280
480
710
480
710
High
335
570
800
570
800
Sound Pressure dB(A)
(SPL)
*4
Low
44
44
41
41
41
Med
46
45
43
45
45
High
50
46
48
50
50
Holding Charge
d r y N i t r o g e n
Heat Exchanger Type
aluminium corrugated plate fins to expanded inner grooved copper tube
Indoor Fan Type
Weight
f o r w a r d c u r v e d c e n t r i f u g a l
kg
48
93
93
93
93
dB(A)
52
54
57
54
57
OUTDOOR UNITS
Sound Pressure (SPL) *5
Refrigerant
H F C - 4 1 0 A ( R 4 1 0 A )
Heat Exchanger Type
epoxy coated aluminium corrugated plate fins to expanded inner grooved copper tube
Outdoor Fan Type
propeller
Finish
g r e y p o l y e s t e r p o w d e r c o a t
Approx. Weight
kg
86
116
133
116
133
Notes:
Capacities are for close coupled systems. Allowance must be made for for pipe length, pipe size and bends.
*1 Cooling Capacity (net) to AS/NZS 3823 conditions: Indoor Entering Air Temperature 27°C D.B., 19°C W.B.; utdoor Entering Air Temperature 35°C D.B.
O
*2 Heating Capacity to AS/NZS 3823 conditions:
Indoor Entering Air Temperature 21°C D.B.; Outdoor Entering Air Temperature 7°C D.B., 6.1°C W.B.
*3 Voltage fluctuation limits: 1 phase 200–252 V a.c. 50 Hz; 3 phase 342–436 V a.c. 50 Hz.
*4 Sound Pressure Level (SPL) for Indoor Units measured in an anechoic chamber 1 m below and to the side of the unit.
*5 Sound Pressure Level (SPL) for Outdoor Units is measured 3 m from exhaust air fans.
Materials and specifications subject to change without notice due to the manufacturer's ongoing research and development programme.
temperzone limited
Head Office, Auckland : 38 Tidal Rd, Mangere, N.Z.
Private Bag 93303, Otahuhu, NEW ZEALAND. Email sales@temperzone.co.nz Website: www.temperzone.biz
RE
GISTERED
temperzone australia pty ltd
Available from
07/08 Pamphlet No. 2892
Head Office, Sydney : 7A Bessemer St
PO Box 6448, Delivery Centre, Blacktown, NSW 2148, AUSTRALIA. Email sales@temperzone.com.au
AUCKLAND
SYDNEY
MELBOURNE
Ph. 0-9-279 5250
Ph. (02) 8822-5700
Ph. (03) 9551-7422
Fax 0-9-275 5637
Fax (02) 8822-5711
Fax (03) 9551-8550
PERTH
Ph. (08) 9314-3844
Fax (08) 9314-3855
WELLINGTON
Ph. 0-4-569 3262
Fax 0-4-566 6249
ADELAIDE
Ph. (08) 8376-1505
Fax (08) 8376-1449
BRISBANE
Ph. (07) 3399-2544
Fax (07) 3399-2577
TOWNSVILLE
Ph. (07) 4773-9566
Fax (07) 4773-9166
CHRISTCHURCH
Ph. 0-3-379 3216
Fax 0-3-379 5956
SINGAPORE
Ph. SNG 6733 4292
Fax SNG 6235 7180
NEWCASTLE
Ph. (02) 4962-1155