T3 TIMER (Delay on Break)
T3 TIMER (Delay on Break)
T3K-AVG T M R-xxx
Timer Features:





Microcontroller based timing
Remaining/Elapsed Time
Display
Optional Password protection
for unit/range
Set time range from 0.01 sec to
999 hours
Digital setting with 1%
resolution, 1% Absolute
Accuracy, and 1% Repeat
Accuracy
Timer Function:
Input power must be applied before and
during timing. When the switch (S1) is closed,
the Relay (R) is energized (contacts transfer).
The time delay (SP) begins when switch is
opened (negative edge-triggered) and the
relay remains energized during timing. The
output de-energizes at the end of time delay.
Note: Closing the switch while timing will reset
the time delay while the output remains
energized. Losing power resets the time delay
and de-energizes the output.
TECHNICAL DATA
TIME DELAY
Range: Depends on the Time Unit
 0.01 - 9.99 seconds

1-999 seconds

1-999 minutes

1-999 hours
Repeat Accuracy: +/-1% or 20 ms,
whichever is greater
Reset Time: 5 ms max. (2 ms typical)
INPUT
OUTPUT
Operating Voltage:
120, 240 VAC; 12, 24 VDC ±10%
(Unfiltered input voltage to DC Models
must be full-wave rectified)
Power Consumption: 3 VA max.
Frequency: 50/60 Hz
ENVIRONMENTAL
Dielectric Breakdown: 2000 VAC, RMS
min. at 60 Hz between input and outputs
and 1000VAC between outputs
Polarity: DC units are reverse polarity
protected
Type: Relay contacts
General Form:
DPDT (Double Pole Double Throw), 2 form C
Note: Model T3K-AVGTMR-441 supports
SPDT (Single Pole Double Throw)
Rating: 7A max. Resistive at 250 VAC;
100 mA at 5 VDC min. load current
Life (Number of Operations):
Mechanical: 1 x 107
Electrical: 1 x 105
Storage Temperature: -50°C to 150°C
Operating Temperature: -20°C to 60°C
PROTECTION
MECHANICAL DATA – WIRING AND DIMENSIONS
Termination: 8-pin or 11-pin plug (depending on model)
Mounting type: Socket Mount
Dimensions: 1.790 x 2.887 x 2.412 in.
Unit: inch [mm]

(SPDT model)
8-PIN CONFIGURATION
(Polarity is shown for DC models)
11-PIN CONFIGURATION
FRONT VIEW
HOW TO ORDER
Timers:
12 VDC, 11 pin (DPDT Relay Out)
24 VDC, 11 pin (DPDT Relay Out)
120 VAC, 11 pin (DPDT Relay Out)
120 VAC, 8 pin (SPDT Relay Out)
240 VAC, 11 pin (DPDT Relay Out)
T3K-AVGTMR-466
T3K-AVGTMR-462
T3K-AVGTMR-461
T3K-AVGTMR-441
T3K-AVGTMR-465
Socket: All models require either an 8-pin or 11-pin socket listed below:
8 Pin Socket:
11 Pin Socket:
Sept. 2015
Rev 03
AVG-TMRSKT-8PIN
AVG-TMRSKT-11PIN
T3 Timer (Delay on Break)
AVG Automation
SIDE VIEW
P a g e |1
T3 TIMER (Delay on Break)
T3K-AVG T M R-xxx
Operation and Programming
Timer has two buttons and a 3 digit display for programming. The following button actions are used in programming:

Pressing Left (L) or ↑ button increments a value or moves from one parameter to another.

Pressing Right (R) or ↓ button decrements a value or selects a parameter for editing.

Pressing Both Left and Right (LR) button saves the displayed value and/or advances timer to next parameter.

Pressing Left (L) or Right (R) from the default display will prompt timer to scroll through programmed values.
View Programmed Values:



L or R
Button
Timer Type

Units of time
Setpoint
.

Programmed
Setpoint Limit
Firmware
version
Adjust Setpoint:


Both
LR
R
Button
Display
shows SP

Programmed
Setpoint Limit
Use L to increment
R to decrement
to desired value

Both LR
to save
Return to default
display
New Setpoint
Value
Programming Mode:
(Default
display)
1
Note:
If the Timer remains in an idle
state for more than 6 seconds,
it automatically returns to the
default display.

Both LR
2

R
Button
Both LR
3
If Password is
NOT set, timer
will proceed to
Step 4.
4

Setpoint Limit
New Setpoint
Value
Use L to increment
R to decrement
Programmed to desired value


Screen to input
password

R
button
L Button
5


R
button

Return to default
display
Both LR
to save
Go to Step 4
(Incorrect Password
 will return unit
to default display)
Password
Value
Unit of Time Options:
 Second (10ms) Resolution
Use R Button

Seconds
to scroll
 Minute

Hour
Current Unit
Press LR to select displayed (Go to Step 5)


Screen to input
password
Sept. 2015
Rev 03
Use L to increment
R to decrement
to correct Password
Both LR
to save
Use L to increment
R to decrement
to change Password
T3 Timer (Delay on Break)
AVG Automation

New Password
(Saving  will
remove password)
Both LR
to save

L to confirm R to discard
Password
Password
P a g e |2