ALT7 MEA - Firecom Inc.
FIRECOM
™ ALT­7 Technology Protecting Life®
Analog Loop & Telephone Module
Features u u u u u Microprocessor Controlled Low Power Consumption All Wiring Power Limited Space Saving Design Analog Addressable Signaling Line Circuit (SLC) • 126 Analog Addressable Devices • Style 4 or Style 6 SLC Wiring • Smoke Detector Alarm Verification • 4 Levels of Sensitivity u Firefighter/Warden Telephone Circuits • Style Y or Style Z Telephone Circuits • Supports 2­Wire Warden Phones & Jacks • Active Zone Indicators Description The ALT­7 Analog Loop and Telephone Module combines one analog addressable Signaling Line Circuit (SLC) and four Firefighter/Warden Telephone circuits. The SLC communicates with smoke detectors and other input and output modules over a twisted­pair wire. The SLC wiring can be configured as Style 4 (Class B) or Style 6 (Class A). Any combination of detectors and modules can be mixed on the SLC. Each detector is independently configurable to incorpo­ rate an alarm verification feature that reduces the number of "unwanted" alarms. Each detector may have a varying sensitiv­ ity setting that is based upon manual settings or changed in reaction to events or a time or weekly schedule. The ALT­7 polls each analog addressable device and reports their Alarm, Trouble, or Normal status to the COM­2 Communi­ cations Card located in the DAB­7 Motherboard of the DAN­7 Cabinet. Device status is then transmitted over the riser net­ work wires to the Fire Command Center (FCC) and other nodes in the system. Dirty detectors can be sensed and their status reported as a Trouble Maintenance condition. A 1.5A @ 24VDC auxiliary power output provides power for remote modules that require power in addition to the communications loop. Optional Degrade Mode programming allows input and output devices to continue to operate in the event of a failure of the microproces­ sor on the COM­2 card of the DAN­7. The Firefighter/Warden Telephone circuits can be configured as 4 Style Y (Class B) circuits or 2 Style Z (Class A) circuits. Each circuit can communicate with Firefighter Phone Jacks or up to three 2­wire Warden Stations. The telephone circuits are moni­ tored and controlled by the COM­2 Communications card in the DAN­7. When a Firefighter's phone is plugged into a jack or a handset "calls­in", a call­in signal is transmitted to Fire Com­ mand Center (FCC). The operator pushes a switch on a Display Control Module at the FCC to establish a communication ses­ sion between the telephone handset at the FCC and the "called­ in" phone. The FCC operator can communicate with up to five simultaneous Firefighter/W arden phones. Call progress tones are presented through the phone handset. When a phone "calls­ in", a ring­tone can be heard in the earpiece. If a call cannot be processed, a busy tone will be heard. Once the call is in progress, tones are removed. Activation indicators on the module indicate which circuits are in use and turned on. Upon command of the operator at the FCC, a Warden Phone or a handset plugged into a Firefighter Phone Jack can be enabled to page selected areas of the facility. A ground fault on any circuit is automatically detected, and a technician­invoked ground fault isolation test helps in the iden­ tification of the circuit that is presenting the ground fault condi­ tion.
Installation Application The ALT­7 is used to communicate to analog addressable smoke detectors and input/output modules, as well as to communicate with Firefighter Telephone Jacks and 2­wire Warden Phone Sta­ tions. Up to five phones can communicate at one time in the LSN 2000 system. The ALT­7 Analog Loop and Telephone Module installs in any of the eight Option Slots in a DAB­7 Motherboard of a DAN­7 Cabi­ net. Each motherboard is software programmable to allow up to 8 ALT­7 option cards. MEA CITY OF NEW YORK FIRECOM ™ , INC. 39­27 59th Street Woodside, NY 11377 718.899.6100 TEL 718.899.1932 FAX F I R E C O M I N C . C O M 72630 Rev 081101 1 of 2
Engineering Specifications The ALT­7 Analog Loop and Telephone Module shall contain one SLC capable of communicating to compatible Firecom Analog Addressable Devices (See Compatible Devices ). The SLC shall communicate with up to 126 detectors and/or modules. Any combination of devices shall be allowed on the loop. The ALT­7 shall also contain 4 Style Y (Class B) or 2 Style Z (Class A) telephone circuits. The selection of Style Y or Style Z shall be field selectable. Each phone circuit shall be capable of communicating to Firefighter Phone Jacks or 2­wire Warden Stations with confirmation LED. A ring tone shall be generated on all activated circuits until communications with the Fire Command Center has been established. Indicators on the ALT­7 shall denote circuits with active communication links. The DAB­7 Motherboard of a DAN­7 shall allow up to eight ALT­7 modules to be installed into its option slots. Wiring Connection 1 2 1 2 1 2 FIRECOM WS­100P SERIES FIRECOM WS­100P SERIES FIRECOM WS­100P SERIES 13 14 15
16 + 15 16 + AUX PWR 24VDC ­ + ­ + ­ ­ ­ ZONE 1 TEL 252 MAXIMUM OF 3 STATIONS ZONE 2 TEL 253 ZONE 3 TEL 254 ZONE 4 TEL 255 ALT­7 4 STYLE " Y " ( CLASS " B " ) TELEPHONE CIRCUITS Electrical Specifications 24VDC 80mA 24VDC @ 1.5A 135mA 12.24VDC 3mA 25mA 0.8 Microfarads 25 Ohms 0°C to 49°C 0% to 93% @ 32°C Ordering Information Model No. Part No. Description ALT­7 73275 Analog Loop & Telephone Module ­ 7 8 9 10 11 12 + 13 14
Operating Voltage Operating Current Aux Power SLC Max Loop Current Tel Zone Voltage Tel Zone Supv Current Tel Zone Alarm Current SLC or Tel Max Loop Capacitance SLC or Tel Max Loop Resistance Operating Temperature Operating Relative Humidity Range L2 L1 ADDRESSABLE DEVICE #1 AUX PWR 24VDC ­ ­ + 1 2 FIRECOM WS­100P SERIES FIRECOM FJ­100T L2
L1 ADDRESSABLE DEVICE #2 + 1 2 FIRECOM WS­100P SERIES FIRECOM FJ­100T L2 L1 ADDRESSABLE DEVICE LAST DEVICE L2 L1 L2 L1 + 1 2 FIRECOM WS­100P SERIES MAXIMUM OF 3 STATIONS FIRECOM P/N 73305 3.9K 1/2W RESISTOR ­ 7 8 9 10 11 12 + L2 L1 ADDRESSABLE DEVICE #1 + L2 L1 ADDRESSABLE DEVICE #2 L2 L1
L2 L1 + L2 L1 ADDRESSABLE DEVICE LAST DEVICE 1 2 3 4 5 6 1 2 3 4 5 6 + DAB­7 TB1 THRU TB8 STYLE 4 (CLASS B) SIGNALING LINE CIRCUIT (SLC) WIRING DAB­7 TB1 THRU TB8 STYLE 6 (CLASS A) SIGNALING LINE CIRCUIT (SLC) WIRING
ZONE 1 TEL 252 ­ ­ ZONE 2 TEL 254 ­ ALT­7 2 STYLE " Z" ( CLASS " A " ) TELEPHONE CIRCUITS Compatible Devices Model No. F900­450 F900­550 F900­650 F900­886 F900­AA­P F900­AA­N F900­AR­P F900­AR­N F900­750 F900­790 F900­805 F900­806 F900­820 F900­825 F900­830 F900­831 F900­920 F900­930 F900­940 F900­941 F900­942 F900­943 F1000­450 F1000­550 F1000­650 F1000­886 MIO­8 ARLY­8 ASPK­8 ATEL­8 CAZ­8 Part No. 75004 75003 75002 75059 75010 75041 75010 75041 75000 72044 70499 70500 70501 70502 70497 70498 71743 71744 75200 75199 75201 72030 75162 75160 75161 75163 70708 72678 72631 72677 72446 Description Heat Detector Ion Detector Photoelectric Detector Multi­Sensor Detector Photo Duct Detector Ion Duct Detector Photo Duct Detector w/Relay Ion Duct Detector w/Relay Isolator Dual Input Monitor Module Switch Monitor Module Priority Switch Monitor Module Switch Monitor I/O Module Sounder Control Module Mini­Priority Switch Module Mini­Switch Monitor Module Dual Input­Output Module Dual Input Monitor Module Addressable Manual Station Addressable Manual Station Addressable Manual Station Addressable Manual Station Discovery Heat Detector Discovery Ion Detector Discovery Photoelectric Detector Discovery Multi­Sensor Detector Multiple­Input Output Board Analog Relay Card Analog Speaker Card Analog Telephone Conventional Analog Zone Card It is our intention to keep the product information up to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information contact: FIRECOM, INC. FIRECOM ™ , INC. 39­27 59th Street Woodside, NY 11377 718.899.6100 TEL 718.899.1932 FAX F I R E C O M I N C . C O M 72630 Rev 081101 2 of 2 