Cable Float Switch Cable Float Switch

Cable Float Switch Cable Float Switch
C able Float Switch
DESCRIPTION
PRINCIPLE
The Float Switches are made of molded,
chemical resistant polypropylene, that it was
serviceable, low-cost, and specially designed to
solve the long distance, multi-points level
detection, liquid with pump or granule instances.
Certainly, it's suitable for common liquid also.
CS1 Type float switch make use of micro switch
as contact component. The switch will have ON
or OFF contact signal output when the angle is
larger than 28L
CF Type float switch make use of mercury switch
as contact component. When liquid lift up to
contact float, the float will have variable angles.
The switch will have ON or OFF contact signal
output when the angle is larger than 10L
SPECIFICATION
Type
CS1-R A/B/C
CS1-P A/B/C
CF-S A/B/C
Float Material
Polypropylene
Polypropylene
SUS304
Cable Specification
Neoprene Cable
2
1mm x3C or 2C
PVC(VCT) Cable
2
1mm x3C or 2C
Silicon Cable
2
0.75mm x3C or 2C
Contact Rating
10A/250VAC, 15A/250VAC
Contact Form
2A/250VAC
1A, 1B or 1C
Operating Temp.
-10LC~80LC
0LC~60LC
Suitable S.G.
Weight Approx.
0LC~170LC
0.6
0.5
770g / 5M
480g / 5M
CONTACT FORM
CS1- A
N.O.
ON
CS1- C
SPDT
CS1- B
N.C.
GREEN
BLUE
ON
ON
BLUE
GREEN
BLUE
BROWN
ON
1 In Liquid
BLUE
BROWN
1 In Air
1
C able Float Switch
STRUCTURE & DIMENSION
1
CS1 TYPE
CF TYPE
CF TYPE
1
10
1. Silicon Cable
2. Material: SUS304
Enclosure IP68
3. Mercury Switch: 2A/250VAC
3
2
2
120
110
3
1. Neoprene Cable or
PVC(VCT) Cable
2. Material: PP
Enclosure IP68
3. Micro Switch: 10A/250VAC
4. Steel Ball: 15A/250VAC
4
f 90
f75
40
17.5
CS1 TYPE
DIMENSION OF WEIGHT
CS1-PP-W
CF-SUS-W
Type
Material
Weight
CS1-PP-W
P.P.
0.2kg
CF-SUS-W
SUS304
1.8kg
65
70
30
f10
f60
f65
FLOAT TYPE CODE
CF-SA-
CS1-RACable length
x6---0.6M 10--- 10M
03--- 3M 15--- 15M
05--- 5M Max. 20M
Cable length
x6---0.6M 10--- 10M
03--- 3M 15--- 15M
05--- 5M Max. 20M
A --- N.O.
B --- N.C.
C --- SPDT
A --- N.O.
B --- N.C.
C --- SPDT
Cable material
P --- PVC (VCT)
R --- Neoprene <HAR>H07RN
2
C able Float Switch
RUBBER CABLE CHEMICAL RESISTANCE
Liquids
Liquids
CS1-R CS1-P CF-S
Diesel
Acetic acid
(less than 10%)
Glycerine
Formaldehyde
(less than 40%)
Fuel-oil
Lactic acid
(less than 10%)
Washing agent
Nitric
(less than 10%)
Benzine
Hydrochloric acid
(less than 10%)
Formic acid
(less than 10%)
Sulfuric acid
(less than 30%)
Excellent
Acceptable
Not good
APPLICATION
Angle 28B62B
ON
Angle 10B62B
OFF
3
CS1-R CS1-P CF-S
C able Float Switch
RELATIVE DIMENSION FOR INSTALLATION
The float action length (a) must be less than the
distance between wall and cable (A) ; if not will
cause wrong action.
Keep inlet of pump (D) lower than the float (d) ,
to prevent damage from lack of water.
A
a
Float lowest level
d
Lowest level of pump
D
ATTENTION TO INSTALL
Keep a proper distance between installation
position and inlet of water pump, to prevent float
switch sucked by inlet of water pump.
Between installation position and inlet of water
should keep a proper distance to prevent
impacting water and cause wrong action. If it
can't be avoided, to install wave-resistance pipe
or wave-resistance plate for improvement.
4
C able Float Switch
HOW TO ORDER FL TYPE
Various types of muti-point products can be
selected depends on user's requirement.
For examples:
FL-B type is suitable for Corrosive liquid.
FL-A type is suitable for high temp liquid.(170 C )
FL-
-
-
Weight quantity
1~4
Weight material
C: P.P.
S: SUS304
DISTANCES OF CONTROL POINT
NO
-
Float quantity
1~4
Float material
C: P.P.
S: SUS
Housing
A: Aluminum
B: Plastic
NC
l 1: ____________mm
l 2: ____________mm
l 3: ____________mm
l 4: ____________mm
L: ____________mm
MODEL: FL-A
f200
f165
Flange 4"x5kg/cm
MODEL: FL-B
f 200
f 165
1/2"PF
Flange 4"x5kg/cm
2
1/2"PF
2
102
8- f19
102
14
l1
l1
14
8- f19
l2
l2
l3
l3
l4
l4
L
over 50mm
Tie
cable
fixed wire
f 8.7mm cable
lead weight
CS-PP-W
over 100mm
over 100mm
weight
65mm
SUS304
f 65mm
5
C able Float Switch
TYPE APPLICATION
The FL-B Type is suitable for install on the roof of tank and suspend floats in tank's
inside for pumping control with level alarms.
POWER
SOURCE
R
S
T
NO FUSE BREAKER
MAGNETIC SWITCH
Power
Switch
HH
HH
H
H
L
L
LL
LL
OL
U
V
W
MODEL: FL-B
HH(N.O.)
High Alarm
Pump On
H(N.O.)
Pump Off
L(N.O.)
Low Alarm
6
LL(N.C.)
High Alarm
Pump On
Low Alarm
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising