Brochure - Power Electronics Australia
VARIABLE
SPEED DRIVE
SD500
•
•
•
•
•
Ranging from 0.75kW to 90kW, 200-230Vac and 380-480Vac
Intuitive control and comprehensive setting menu
High performance motor control
EMC and harmonic filters integrated across the range, optional dV/dt filter
Reliable and robust, electronics conformally coated and an operation temperature of up to 50°C
• Multiple modular accessories: Encoder, PLC, Ethernet, CAN open,
DeviceNet, LonWorks, I/O
• 3 year warranty and 24h service and replacement commitment
12-13
SD500 SERIES
04.
Power Electronics’ experience in heavy duty industries is transferred
to the lower power motor segment by offering competitive and
rugged designs. The SD500 VSD covers a power range from 0.75kW
to 90kW and it is available in four frame sizes that make it compatible
with a wide range of applications.
Smarter and more flexible than ever, with supreme software control,
the SD500 saves time and achieves superior results. The unit offers
high precision and powerful control, with multiple communication
protocols, maximum efficiency and motor protection. The SD500
series surpassed all expectations and is compatible with all budgets
and industrial applications.
ITS MULTIPLE ACCESSORIES
GIVE SD500 THE MOST
ADVANCED FEATURES FOR
PUMP AND MOTOR CONTROL
EASY TO USE
3
TRIAL D
US
D
ISION
IV
FOR IN
WARRANTY
IMMEDIATE DELIVERY
Discovering SD500
CONFORMAL COATING
All our modules are conformally coated according
to IEC61086-1: 2004,-3-1, protecting the micro
components that are vulnerable to dust, moisture,
pollution (PD3) and corrosive gases (3C3).
NEW MODULAR DESIGN FOR
ACCESSORIES
PLC module with additional I/O, Encoder Module, Ethernet
Communication Module, CanOpen, DeviceNet and
Lonworks, I/O Extension Module and Dynamic Brake Unit.
EMC/RFI FILTERS
AND HARMONIC
FILTERS BUILT-IN
HIGH OVERLOAD
CAPACITY
150% Overload capacity at 50°C or 110% at 40°C.
14-15
OPTIONAL dV/dt FILTER
The optional dV/dt filter 500-800V/µs allows
installation with up to 300m of unscreened output
cable.
REMOVABLE KEYBOARD
SD500 offers the possibility to install the display up
to 3m away from the drive. Install the SD500 IP54
display in the front door of the cabinet and you can
safely operate the unit.
SD500 SERIES
04.
BACKLIT
LCD SCREEN
MEMBRANE
KEYPAD
INDEPENDENT
MEMORY
EASY SETUP AND
PROGRAMMING
SD500 is featured with a graphic display illustrating
4 lines and 16 characters, and a membrane keypad
that allows the user to move across an intuitive set
of parameters that enhance programming during
commissioning and maintenance tasks.
STATUS INDICATION
LEDS
Give access to parameters groups
and subgroups.
+
Pressed together increases the value
or rolls up the available options.
+
Pressed together decreases the value
or rolls down the available options.
Allows the user to roll up in the list of
parameters.
Allows the user to roll down in the list of
parameters.
Pressed during 3 seconds allows the
user to move from one row to another.
Pressed fast allows the user to escape
the menu.
PARAMETER READING,
COPYING AND WRITING
FUNCTIONS ALLOW A QUICK
AND EASY PROGRAMMING
OF MULTIPLE UNITS
Allows the user to start the motor in
local control mode.
Allows the user to stop the motor
when it is running and to reset the
failures.
Allows the user to shift from local
control mode to remote control
mode.
LOW VOLTAGE / POWER ELECTRONICS
One step ahead
The SD500 is best in class by offering a precise control, operation temperature up to 50°C, 150% overload
capacity and built-in filters that assure you the best performance and motor lifetime.
16-17
16-16
ACCURATE, EFFICIENT AND FLEXIBLE CONTROL
GREATER PRECISSION IN
TORQUE/SPEED CONTROL
The encoder module allows you to run a
powerful and accurate close loop control
across the whole speed range, even
considering zero speed.
150%
SET POINT
900 rpm
0%
12
46
10
(rpm)
20
40 60
100 140 200t(s)
T(%)
Vin
LOW VOLTAGE RIDETHROUGH FOR
TEMPORALLY SHUTDOWNS
The SD500 will keep the motor and
application under control under low
voltage ride through events without
stopping the system.
V dc
I out
M speed
Vin
KINETIC ENERGY CONTROL
This function allows the drive to perform
a controlled stop if the input power is lost.
Vdc
I out
M speed
MULTIPLE PROGRAMMABLE I/O
The drive offers as standard 2 analogue inputs, 8 digital inputs, 2 output relays and 1 digital
output. Additionally, the I/O can be extended by installing the I/O module or the PLC module,
and can be programmed by the PLC software. It is suitable for applications such as: pump
control, irrigation scheduling, motorized valves operation…
SD500 allow the user to select the connection scheme of the digital inputs (NPN / PNP),
the connection to the thermistor sensor (PTC) and the termination resistor for RS485
communications (TR).
MOTOR AND DRIVE PROTECTIONS
The SD500 provides a full set of motor and drive protections: Over-voltage, low voltage,
motor thermal protection, overload and underload, phase loss, IGBT overtemperature,
hardware failure, motor phase loss, external brake module failure, communications failure,
reference signal loss, cooling fan failure and encoder error.
ACCURATE CONTROL, HIGH
RELIABILITY AND MAXIMUM
MOTOR CARE
LOW VOLTAGE / POWER ELECTRONICS
SD500 SERIES
04.
DV/DT FILTERS
The optional dV/dt filters reduces the voltage peaks and common mode currents
(CMC) to the motor. The SD500 dV/dt filters allows the user to install the motor with
unscreened cable up to 300m or screened cable up to 150m.
NO dV/dt FILTER
(3000-6000V/μs)
200ns
Peak Voltage: 3.6xVLINE
FrequencyCMC: 12.5MHz
dV/dt FILTER
(500-800V/μs)
5μs
Peak Voltage: 2.6xVLINE
FrequencyCMC: 200kHz
NOTE: 200m motor cable, 400 VAC
HARMONICS FILTERS
DC reactor built-in into the DC bus to reduce harmonics and improve the power factor.
DYNAMIC BRAKE
RESISTOR
(OPTIONAL)
B
P(+)
S
T
L1
L2
L3
U
V
W
PE
EMC FILTER
R
dV/dt FILTER (optional)
DC Fuse
N(-)
RECTIFIER
EMC/RFI FILTER
DC BUS
DYNAMIC BRAKE
Frames 1-4 built-in
Frames 5-6 optional
INVERTER
SD500 integrates built-in EMC filter Class 2 up to 22kW and Class 3 up to 90kW. For
other EMC classes, optional external filters can be installed. (According to EN 61800-3).
18-19
OPERATION TEMPERATURE UP TO 50°C
Power Electronics’ SD500 series can operate at temperatures up to 50°C, without
derating, enabling its use inside industrial cabinets or technical rooms under hot
conditions.
HEAVY 150% OR LIGHT 110% OVERLOAD
The SD500 match your application. Available with 150% overload for conveyors or
mills (heavy duty) and 110% overload for pumps and fans (light duty).
I (A)
1,5 x IHD = 1,1 x IND
IND
NORMAL DUTY 40ºC
HEAVY DUTY 50ºC
IHD
1 min
1 min
t (s)
5 min
10 min
IND = Current rating 40ºC
IHD = Current rating 50ºC
DYNAMIC BRAKE
SD500 drives offers built-in dynamic braking circuit for frames 1 to 4 and optional
external braking units for frames 5 and 6. Check our accessories list for external
braking resistors or external dynamic braking modules.
CONFORMAL COATING
The PCB coating protects the micro lead components that are vulnerable to dust,
moisture, pollution (PD3) and corrosive gases 3C3 build up, which can produce
conductive paths resulting in short circuiting. Power Electronics designs are
dedicated to harsh environments thus PCBs modules are fully coated with the
latest military and aerospace technology specifications (IEC61086-1:2004,-3-1).
LOW VOLTAGE / POWER ELECTRONICS
SD500 SERIES
04.
Energy saving
The Variable speed drive modifies the frequency delivered to the motor adjusting the motor load speed
to the instantaneous process demands. This leads to high energy savings and superior process control.
20-21
20-20
04.
SD500 SERIES
ENERGY SAVING
Depending on the type of load, the energy savings provided by the drive will vary
significantly. The following charts describe the most common load types, their application
and the relationship between the torque or power required.
QUADRATIC TORQUE APPLICATIONS
The highest savings are experienced in quadratic torque applications such as fans and centrifugal pumps.
In these applications the required power is proportional to the cubic of speed following the affinity laws.
Q1 n1
=
Q2 n2
H1
n1 2
=( (
H2
n2
THROTTLING CONTROL
BYPASS CONTROL
H
H2
H1
η1
η2
Q1 , Q2 : Fluid flow at operating points 1 and 2
H1 , H2 : Head at operating points 1 and 2
P1 , P2 : Power demand at operating points 1 and 2
n1 , n2 : Motor speed at operating points 1 and 2
P1
n1 3
=( (
P2
n2
VSD CONTROL
H
H
H1
H2
Q
η
η1
η2
Q2
Q1
n = 100%
Q
H2
Q
η
H2
Q2 Q1 Qb+Q2
n = 50%
Q2
Q
Q1
Q
As shown in the graphs, the throttling control and bypass control modify hydraulic losses to obtain a
different operation point for the desired flow. Typically they reduce the power absorbed by the motor but
if the pump’s hydraulic efficiency is reduced at low speed, it could be insignificant. However, variable speed
drives modify the performance curve of the pump, providing higher savings and better hydraulic response.
CONSTANT TORQUE APPLICATIONS
In case of constant torque applications such as compressors or conveyors, the power demand is proportional
to the speed. To illustrate that, we can focus on the example of a screw compressor regulated with a slide
valve control or with a variable speed drive control.
VSD CONTROL
100%
TORQUE (%Max. torque)
TORQUE (%Max. torque)
SLIDE VALVE CONTROL
90%
80%
70%
60%
50%
40%
20%
90%
80%
70%
60%
50%
40%
P1
30%
100%
30%
P2
20%
T start
10%
T start
10%
Wr
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
ROTOR SPEED (% Full speed)
T compressor 100%
T motor
T compressor 60%
P5
P4
P3
P2
P1
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
ROTOR SPEED (% Full speed)
T compressor 100%
T motor
LOW VOLTAGE / POWER ELECTRONICS
Pumping and
Ventilation
As an alternative to mechanical flow control, the use of variable speed drives in variable
flow systems, allows operators to dynamically change the operating range of their
equipment, in order to match their flow demand, at any time. Variable speed control
provides the minimum power consumption with minimum wear and tear of the hydraulic
and pneumatic components.
SD500 is designed for indoor operation under the harshest environments due to its
conformally coated electronics and high operating temperature range. Its design is
suitable for sewage treatment plants, water treatment plants, desalination plants,
pumping stations, tunnels and mines ventilating fans, etc...
SD500 offers a wide range of communication accessories and EMC filters that make it
compatible with all application worldwide and eliminates the restrictions on motor cable
length. The PLC module allows unlimited intelligence and provide multiple I/O that allow
the user to run multi-pump systems, set irrigation schedules, set PID control by pressure,
flow, level or any compatible sensor, set remote alarms, enable self-diagnostic functions,
control a jockey pump, and much more thanks to intuitive programming software.
22-23
SD500 SERIES
04
Motion
When accurate motion control is required, the SD500 offers the highest control features
thanks to its ultimate closed loop motor control with the optional encoder module. You
are able to perform a precise start, stop, back spin, spin control or shaft position control
that can accelerate the production process with maximum energy savings.
By using the SD500, you not only improve the production process but you will also
reduce mechanical wear and tear and the associated maintenance costs in your facility.
Precise control provides better product transportation removing product damage or
undesirable product spillage.
For processes that require accurate and powerful control, our variable speed drives can
manage high torque with exceptional dynamic response in milliseconds.
LOW VOLTAGE / POWER ELECTRONICS
Technical characteristics
INPUT
Power range
0,75kW - 90kW
Voltage power
200-230Vac (-15% a +10%), 380-480Vac Three phase (-15% a +10%)
Input frequency
50~60 Hz ±5%
Power factor (cos φ)
>96%
Input EMC/RFI Filter
0,75 to 22kW - C2 standard / 30kW or more - C3 standard[1]
Input rectifier technology
Diode
Harmonics filter
DC Reactance
Current THDi (%)
<37%
Overload capacity
Constant torque: 150% during 60 sec at 50ºC
Variable torque: 110% during 60 sec at 40ºC
Output frequency
0 to 400Hz [2]
Resolution of frequency set
Operation with digital signals: 0.01Hz
Operation with analogue signals: 0.06Hz (Maximum frequency: 60Hz)
Modulation frequency
Maximum 15kHz [3]
Control Method
V/F Control, Slip compensation, Open Loop Vector Control (sensorless),
Closed Loop Vector Control
OUTPUT
Lineal V/F, Quadratic, defined by the user
ENVIRONMENTAL
CONDITIONS
PROTECTIONS
Output cable length
USC 50m [4]
SC 25m
Optional dV/dt filter
500-800V/µs - USC 300m, SC 150m
Dynamic brake
Built-in frames 1 to 4. Optionl frames 5 and 6
Degree of protection
IP21, Display IP54
Operation temperature
Minimum -10°C, Maximum +50°C
Storage temperature
Minimum -20°C, Maximum +70°C
Relative humidity
<90%, non-condensing
Altitude
1000m
Power altitude derating (> 1000m)
1% per 100m; maximum 3000m
Vibration
5,9m/sec2 (=0,6G)
Ventilation
Air forced refrigeration
Overvoltage
Low Voltage
Overcurrent
Overcurrent detection
Overtemperature of the inverter
Motor thermal Protection
Phase loss protection
Overload Protection
Communication Error
Reference Signal Loss
Hardware Failure
Cooling Fan Fault
Pre-PID failure
Absence of motor Trip
External brake failure
Current Limitation
Overload
Underload
Encoder failure
Fan failure
Loss of keyboard commands
Loss of speed commands
INPUTS
/OUTPUTS
COMMUNICATION
24-25
Analogue inputs
1 input 0-10Vdc, ±10Vdc / 1 input 4-20mA / 0-20mA
Digital inputs
8 configurable inputs
PTC connection
Yes. With analogue or digital specific setup for PTC
Analogue outputs
1 0-10V output (Max. Output Voltage 10V, Max. Output Current 10mA)
1 0-20mA / 4-20mA output (Max. Output Current 20mA)
Relay output
1 Changeover programmable relay (250VAC, 5A; 30VDC, 5A)
1 Programmable normally open relay (250VAC, 5A; 30VDC,5A)
1 Programmable open collector transistor output (24VDC, 50mA)
I/O Extension module (optional)
3 digital outputs NO (250Vac/30Vdc, 5A), 3 digital inputs (selection of PNP/NPN,
0~25V), 1 voltage analogue input, 1 current analogue input (0~20mA) Internal
Impedance: 249Ω, 1 voltage analogue output (±10V, 10mA, 11 bits resolution), 1
current analogue output (0~20mA, 12 bits resolution)
PLC module
6 digital configurable inputs, 4 realy outputs expandable to 14
Encoder module
Liner driver or open collector, pulse train reference.
5/12/15V Isolated power supply
Standard Hardware
RS485 port
Standard Protocol
Modbus-RTU
Optional Hardware
Profibus-DP board, Ethernet board, LonWorks board, DeviceNet/CANopen board
Optional Protocols
Profibus, Modbus TCP, LonWorks, CANopen, DeviceNet
Wiring control
Alphanumeric display
4 Lines of 16 characters. Arrows to adjust parameters.
Independent memory.
Removable
Optional 1 m, 2m y 3m
Connection
RJ45
Status leds
LED ON: Power on the control board
LED RUN: Power on, the motor is powered by the SD500
LED FAULT: Flashing indicates the equipment is in fault
Display information
Status, DC Bus voltage, Motor current, Motor frequency, Motor speed,
Motor voltage, Torque, Temperature, Input/output, Signals status, PID
reference, Number of pumps
CONTROL
REGULATIONS
SD500 SERIES
04.
CE, cTick, UL[5], cUL[5]
NOTES [1] For other application categories, an optional external filter will be used. For additional information ask Power Electronics.
[2] The maximum frequency is 300Hz when selecting the open loop control in the programming parameters.
[3] The maximum allowable depends directly on the power of the drive.
Consult the SD500 Software and Programming manual for additional information.
[4] Motors with reinforced insulation withstand greater cable lengths. Consult Power Electronics.
[5] On process.
WIRING CONTROLS
FRAMES 1, 2, 3 AND 4 (0.75kW-22kW)
FRAMES 5 AND 6 (30kW-75kW)
RS485
PORT
NOTE
24VDC, 150mA
DI3
DI4
DI1
DI2
Common DI
Programmable Open
Collector Digital Output
DO1
Common
Analog Input
CM A01 A02
1
SP
3
Analog Output Current 0~20mA/4~20mA
Analog Common Signal
Analog Voltage Output 0~10V, 10mA
PE
Analog Input 0~20mA/4~ 20mA
Analog Current Output 0~20mA/4~20mA
Common Analog Signal
Analog Voltage Output 0~10V, 10mA
Analog Input 0~20mA/4~ 20mA
Analog Input ±10Vdc
Common DI
Supply for Analog
Input
DI7
DI8
PE
I1
2
Analog Input ±10Vdc
3
Supply for Analog Input
SP
Common DI
1
2
P5 P6 P7 P8 CM VR+ VR- V1
DI7
A1 C1 B1
S+ S- CM
Modbus
Communication
DI8
5G A01 A02
DI5
DI3
DI4
DI1
DI2
Common AI
I1
Q1 EG 24 CM P1 P2 P3 P4 CM
DI6
Programmable Relay RLY2
(250VAC, 5A/30VDC, 5A)
A2 C2 NC
Programmable Relay RLY1
(250VAC, 5A/ 30VDC, 5A)
24VDC, 150mA
Common DI
Open Collector
Programmable Digital
Output
S+ S- CM
Modbus
Communication
P5 P6 P7 P8 CM VR+ VR- V1
DI5
Programmable Relay RLY1
(250VAC, 5A/ 30VDC, 5A)
A1 C1 B1
Q1 EG 24 CM P1 P2 P3 P4 5G
DI6
RLY2 Programmable Relay
(250VAC, 5A/30VDC, 5A)
A2 C2 NC
RS485
PORT
Control cables must be shielded and grounded.
LOW VOLTAGE / POWER ELECTRONICS
Configuration table
Dimensions and weights
CONFIGURATION TABLE
SD5
016
2
2
SD500
series
Output current[1]
Rated Voltage
Protection degree
SD5
002
2A
2
200-230V
005
5A
4
380-480V
...
...
150
150A
2
IP21
[1] Verify the rated current of the motor nameplate to guarantee the compatibility with the selected drive.
Ø5,0
Ø9
,0
DIMENSIONS (mm) and WEIGHTS (kg)
Ø5,0
197,0
222,0
176,0
150,0
200,0
355,0
336,0
266,0
284,0
5,0
5,0
Ø9,0
127,0
FRAME 1
Ø6
,5
Ø6
,5
9,0
5,0176,0
9,0
FRAME 2
5,0
127,0
,0
295,0
280,5
250,0
451,5
385,0
353,0
462,0
8,0
8,0
Ø
281,0
,0
13
Ø
243,5
13
214,6
FRAME 3
6,5
243,5
312,8
300,2
300,1
370,3
370,1
FRAME 5
FRAME 6
242,8
26-27
8,0
8,0
10,0
10,0
312,8
Frame
Weight (kg)
Frame
Weight (kg)
1
5.5
4
30
2
10
5
41
3
20
6
63
663,4
570,0
594,0
639,4
12,5
242,8
13,0
Ø10,0
Ø2
0,
0
6,5
Ø10
,0
Ø2
0,
0
214,6
6,5
FRAME 4
6,5
Standard ratings
SD500 SERIES
04.
STANDARD RATINGS
200Vac - 230Vac (-15% a +10%)
Operation temperature 50°C
HEAVY DUTY
FRAME
CODE
I(A) Rated
SD5005 2 2
1
2
3
4
5
Motor Power
230Vca
Operation temperature 40°C
NORMAL DUTY
kW
HP
150%
Overload
(60s)
0.75
1
7.5
Motor Power
230Vca
I(A) Rated
kW
HP
110%
Overload
(60s)
6.8
1.5
2
7.5
SD5008 2 2
8
1.5
2
12
11
2.2
3
12
SD5012 2 2
12
2.2
3
18
16
3.7
5
18
SD5016 2 2
16
3.7
5
24
22
5.5
7.5
24
SD5024 2 2
24
5.5
7.5
36
33
7.5
10
36
SD5030 2 2
32
7.5
10
48
44
11
15
48
SD5045 2 2
46
11
15
69
60
15
20
69
SD5060 2 2
60
15
20
90
74
18.5
25
90
SD5075 2 2
74
18.5
25
111
90
22
30
111
SD5090 2 2
88
22
30
132
120
30
40
132
380Vac - 480Vac (-15% a +10%)
Operation temperature 50°C
HEAVY DUTY
FRAME
CODE
2
3
4
5
6
Motor Power
400Vca
kW
HP
150%
Overload
(60s)
kW
HP
110%
Overload
(60s)
0.75
1
4.4
4
1.5
2
4.4
1.5
2
6
5.4
2.2
3
6
2.2
3
9
8
3.7
5
9
3.7
5
13.2
12
5.5
7.5
13.2
12
5.5
7.5
18
16
7.5
10
18
16.5
7.5
10
25
23
11
15
25
I(A) Rated
1
Motor Power
400Vca
Operation temperature 40°C
NORMAL DUTY
SD5002 4 2
2.8
SD5004 4 2
4
SD5006 4 2
6
SD5008 4 2
8.5
SD5012 4 2
SD5018 4 2
I(A) Rated
SD5024 4 2
24
11
15
36
32
15
20
36
SD5030 4 2
30
15
20
45
40
18.5
25
45
SD5039 4 2
39
18.5
25
58
48
22
30
58
SD5045 4 2
45
22
30
67
61
30
40
67
SD5060 4 2
61
30
40
91
78
37
50
91
SD5075 4 2
75
37
50
112
100
45
60
112
SD5090 4 2
91
45
60
136
115
55
75
136
SD5110 4 2
110
55
75
165
150
75
100
165
SD5150 4 2
152
75
100
228
180
90
125
228
NOTES Rated power for standard AC 4 pole motors (1500rpm).
For other configurations contact Power Electronics.
Check the rated current of the motor plate to ensure compatibility with the chosen frequency converter.
LOW VOLTAGE / POWER ELECTRONICS
Accessories
dV/dt FILTERS
INPUT
ENVIRONMENTAL
CONDITIONS
Voltage power
200Vac-480Vac
dV/dt value
500V/µs - 800V/µs
Overload capacity
150% 60 sec
Ventilation power supply
Frames 1 and 2, no ventilation.
Frames 3, 4, 5 y 6, 230Vca Max. 18W
Temperature
-10°C to +50°C
Degree of protection
IP20
Class of protection
Class I
Relative humidity
<90%, non-condensing
230Vac (-15% a +10%)
FRAME
1
2
3
4
VSD
dV/dt FILTER
SD500522
SD50F0522
SD500822
SD50F0822
SD501222
SD50F1222
SD501622
SD50F1622
SD502422
SD50F2422
SD503022
SD50F3022
SD504522
SD50F4522
SD506022
SD50F6022
SD507522
SD50F7522
SD509022
SD50F9022
TOTAL HEIGHT (mm)
412
495
511
625
380Vac - 480Vac (-15% a +10%)
FRAME
1
2
3
4
5
6
28-29
VSD
dV/dt FILTER
SD500242
SD50F0024
SD500442
SD50F0044
SD500642
SD50F0064
SD500842
SD50F0084
SD501242
SD50F0124
SD501842
SD50F0184
SD502442
SD50F0244
SD503042
SD50F0304
SD503942
SD50F0394
SD504542
SD50F0454
SD506042
SD50F0604
SD507542
SD50F0754
SD5O9042
SD50F0904
SD511042
SD50F1104
SD515042
SD50F1504
TOTAL HEIGHT (mm)
412
495
511
625
819
896.4
SD500 SERIES
04.
CONNECTIONS BOX
FILTER
FRAME
REFERENCE
DIMENSIONS
W
D
H
1
SD5EB1
147
85
132
Total height
416
2
SD5EB2
195
100
145
500
3
SD5EB3
250
165
135
520
4
SD5EB4
280
205
135
597
5
SD5EB5
300
205
130
724
6
SD5EB6
370
205
138
801
D
H
W
DYNAMIC BRAKE UNIT
380-480Vac - FRAMES 5 y 6
VSD
DBU
SD506042,SD507542
SD509042, SD511042
SD515042
DIMENSIONS (WxDxH)
DBSD4075
DBSD4145
123x130x258
DISPLAY EXTENSION KIT
CODE
ACCESSORIES DESCRIPTION
SD5RC2
Display extender kit (2 meters)
SD5RC3
Display extender kit (3 meters)
LOW VOLTAGE / POWER ELECTRONICS
Communications
and Control
CODE
ACCESSORIES DESCRIPTION
SD5IO
Extension module Input/Output
SD5EC
Encoder module
SD5PLC
PLC module
SD5ET
Ethernet communication module
SD5DN
DeviceNet communication module
SD5DP
Profibus – DP communication module
SD5CO
CANopen communication module
SD5LW
Lonworks communication module
SD5STO
Safe Torque Off
STO - SAFE TORQUE OFF
STO - Safe Torque Off board allows to stop supplying alternating power to the stator stopping the motor by
its own inertia.
•
•
•
•
•
2 inputs (24Vdc, max. 10mA)
1 input (24Vdc)
Feedback terminals
VIEC/EN G1800-5-2
Safety level SIL2
EXTENSION MODULE INPUT/OUTPUT
Extension module allows increase standard analogics I/O, multiplying their benefits of multipump applications:
• 3 digital outputs NO (250Vac/30Vdc, 5A)
• 3 digital inputs (selection of PNP/NPN, 0~25V)
• 1 voltage analogue input
• 1 current analogue input (0~20mA) Internal Impedance: 249Ω
• 1 voltage analogue output (±10V, 10mA, 11 bits resolution)
• 1 current analogue output (0~20mA, 12 bits resolution)
• Scan time:
- Digital outputs: 1.5ms minimum
- Analogue output: Minimum 3ms
• Protection: IP20
• Cooling method: Self cooled
ENCODER MODULE
Encoder module allows closed loop control for applications that request:
•
•
•
•
•
•
Closed loop control
Pulse train reference
5/12/15V insulated power supply
Line driver open collector
200kHz Maximum input frequency
Signal loss detection
PLC MODULE
PLC module allows programming and expansion of digital and analogical inputs and outputs.
• Operation method:
- Stored program cyclic operation
- Role of Task Interruption
• Method of I/O control:
• Number of instructions: Basic: 29; Rev: 223
• Processor time: Basic instruction: 0.4μs/operation
• Program memory capacity: 2k
• 6 digital inputs
• 4 relay outputs
• Operating modes: RUN, STOP, PAUSE
• Self-diagnosis Functions: Watchdog timer, memory error detection, I/O error detection
• Recovery of memory after shutdown
• PID Control
• RS485 Communication: MODBUS protocol support
• External interrupts: 6
• Input filter: 0 ~ 1000ms
• RTC (Real Time Clock): year / month / day / hour / minute / second using KGLWIN
• Operating system KGL WIN
30-31
SD500 SERIES
04.
COMMUNICATION MODULES
Ethernet, Devicenet, Profibus, CANopen and Lonworks communication modules allow the user to easily
integrate the SD500 in multiple networks.
ETHERNET COMMUNICATION MODULE
•
•
•
•
•
•
•
•
•
Transmission Speed: 10Mbps, 100Mbps
Transmission Method: Baseband
Maximum distance between nodes: 100m
Maximum number of nodes: Hub Connection
Auto negotiation
Maximum frame size: 1500 bytes
Access Method to communications area: CSMA / CD
Checking Method for error frames: CRC32
Recommended Channel Connection: 3 channels
DEVICENET COMMUNICATION MODULE
• Power supply:
- Powered from the drive
- External power supply: 11~25VDC, 60mA
• Network topology: Free, Bus
• Transmission speed: 125kbps, 250kbps, 500kbps
• Maximum number of nodes: 64 (including the master)
• Supported media type: Explicit Peer to Peer Messaging
• Faulted Node Recovery (Off-Line), Master / Scanner, Polling
• Terminating resistor: 120Ω 1/4W Lead Type
PROFIBUS COMMUNICATION MODULE
•
•
•
•
•
•
•
•
•
•
•
Device Type: Profibus DP Slave
Auto baud rate
Sync mode
Freeze mode
Maximum input length: 8 words
Maximum output length: 8 words
Maximum data length: 16 words
Transmission speeds: 9.6K, 19.2K,
93.75K, 187.5K, 500K, 1.5M, 3M, 6M, 12M
Modular station
Maximum number of modules: 2
•
•
•
•
•
•
•
•
Power supply: Supplied from the inverter
Network Topology: Bus
Baud rate: 20kbps, 50kbps, 100kbps, 125kbps, 250kbps, 500kbps, 800kbps, 1Mbps
Maximum number of nodes: 64 (including the master)
Supported media type: PDO, SDO, Sync, NMT
Terminating resistor: 120Ω 1/2W Lead Type
PDO available: PDO1 (CiA 402 Drive control and Motion device profile)
Maximum Transmission Distance: 2500m (20kbps) - 500m (125kbps)
•
•
•
•
78kbps communication speed
Free/bus topology
Resistance built-in per topology
Max. 2700m (8858ft) connection distance (bus topology)
CANOPEN COMMUNICATION MODULE
LONWORKS COMMUNICATION MODULE
LOW VOLTAGE / POWER ELECTRONICS
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising