1092 DTS CAT 4p de couv (GB

1092 DTS CAT 4p de couv (GB
XFFem / XFPem Range
Emergency tubular
fluorescent fitting
■
■
■
■
■
▼▼▼
TYPICAL
APPLICATIONS
Refineries
Petrochem/chemical
Painting/solvent areas
Range designed as part of XFF, XFP family
Polycarbonate tube, conforming to group llC
XFP version has automatic switch off on opening
1h30 battery duration in emergency mode
Red LED for battery charge control
Product characteristics
■
■
■
■
■
■
■
■
Marine grade aluminium alloy construction
Yellow polyurethane paint
Polycarbonate or glass tube
White painted sliding metal gear tray with G13 lampholder
Standard power supply 230V 50Hz (other versions – see Options)
One 3/4” NPT brass cable gland + One 3/4” NPT steel plug (XFFem)
One M20 nickel chromed brass cable gland (XFPem)
Set of 2 articulated brackets
CERTIFICATION STANDARD CENELEC EN 50014, 50018, 50019
EC TYPE EXAMINATION CERTIFICATE: under the new directive 94/9/EC:
LCIE 02 ATEX 6170X (XFR/Fem), 6171X (XFPem)
Ex II 2 G and D, IP66 T80°C for D
EExd llC T6 (XFRem, XFFem)
EExde llC T6 (XFPem)
Ingress Protection: IP66/67
Shock resistance: IK09 10 Joules (polycarbonate tube)
Glow wire test: 960°C
Please note
In solvent and spray painting
areas, glass tubes are
recommended
54
Z.I. - Avenue Henri Beaudelet B.P. 27 - 77831 Ozoir Cedex - France - Tel. +33 (0)1 64 40 27 26 - Fax +33 (0)1 64 40 20 11
Zone 1
+ zone 2
EEx “d”
Flameproof
Technical specifications XFRem, XFFem
Enclosure
End caps in marine grade aluminium alloy type
AS10GY30
Yellow polyurethane paint RAL 1003
Offshore option: 3 coats of paint
Extruded 2.5mm LEXAN polycarbonate tube, anti-UV
protected
7mm borosilicate glass tube
Ingress rating: IP66/67 (EN60529), neoprene gasket
Stainless steel screws
Options: One 3/4” NPT metal cable gland for
armoured cable type PAP (see page 124)
One M20 metallic cable gland for non-armoured cable
type PL (see page 125)
One M20 metallic cable gland for armoured cable type
PLP (see page 125)
Terminal block (plug in terminal block)
Protection class: I
Up to 10mm2 (rigid wire), 6mm2 (flexible wire)
Terminals supplied for P1, N, PE and 2, looping possible.
Teminal P1 is the battery charging terminal and
is permanently connected
Terminal 2 is connected via a switch to P1, to select
the function of the luminaire:
- contact closed: operates in maintained mode
- contact open: operates in non-maintained mode
Automatic battery switch off on opening
Lamps (supplied on request)
50
Rated voltages
T8 bi-pin G13 tubes, Ø 26 - coolwhite 4000°k (other
colour temperatures on request)
40
Temperature
Ambient temperature range: -20°C to +55°C
Surface temperature classification:T6 (gas),T80°C (dust)
Standard: ferromagnetic ballast – 230V 50Hz
Options: ferromagnetic ballast – 240V 50Hz –
220V 60Hz – 127V 60Hz
Single / dual tube electronic ballast: AC 220 to 240V
– 50 to 60Hz
7.2V 4Ah NiCd battery
Lumen output in emergency mode (1 tube lit):
40% for 18W, 33% for 36W
Battery duration in emergency mode: 1h30
LED for battery charge control
Photometric
data
110
25
50
75
100
125
150
175
200
80
70
60
100 90
80
70
60
50
40
0.68 H + 0.10 T
30
30
Fixing
20
Standard: 2 zinc chromed steel articulated brackets
(type DO23) for ceiling mounting
Options: 2 stainless steel brackets 304L (type DO24)
for ceiling mounting
Set of 2 U-bolts and brackets in zinc chromed steel
for pole mounting 1 1/4” (type DO25),
1 1/2” (type DO26), 2” (type DO27)
Set of 2 U-bolts and brackets in stainles steel 304L
for pole mounting 1 1/4” (type DO28), 1 1/2” (type
DO29), 2” (type DO30)
Power factor
0.75 with ferromagnetic ballast (with capacitor,
except 20W: 0.60)
0.98 with electronic ballast
Standard: One brass 3/4” NPT cable gland for nonarmoured cable – Ø 8/10mm
One 3/4” zinc chromed steel plug
0
10
1
100
90
20
110
25
50
75
100
125
150
175
200
10
80
70
60
50
100 90
80
70
60
50
40
40
0.63 G + 0.07 T
30
30
20
Photoelectric cell
Stainless steel anti-drip canopy 304L
Stainless steel shockproof kit 304L (factory fitted)
10
For 1000 lm, with 1 lamp
Other options
Cable entries
10
0
10
20
For 1000 lm, with 2 lamps
Installation and maintenance instruction leaflet NT 12em available on request
Note
Technical specifications XFPem
Technical specifications same as
XFRem, XFFem excepted:
Dimensions and
spare parts:
See XFF-XFR page 43
See XFP page 45
Terminal block (plug in terminal block)
Up to 6mm2 (rigid wire), 4mm2 (soft wire)
Terminals supplied for P1, N, PE and 2, looping not possible.
Teminal P1 is the battery charging terminal and
is permanently connected.
Terminal 2 is connected via a switch to P1 to select the
function of the luminaire:
- contact closed: operates in maintained mode
- contact open: operates in non-maintained mode
Protection class: I
Automatic battery and power supply switch off
on opening
Cable entry
Standard: One M20 nickel chromed brass
cable gland for non-armoured cable – Ø 8.5-16mm,
with safety harness
Options: M20 metal cable gland for armoured cable
type PEP (see page 127)
Installation and maintenance instruction leaflet NT 12em available on request
Reference
Without switch
With switch
Rating
(in W)
Nominal current
(in A)
XFR 120 em
XFR 140 em
XFF 220 em
XFF 240 em
1 x 18
1 x 36
2 x 18
2 x 36
0.15
0.20
0.30
0.40
XFP 120 em
XFP 140 em
XFP 220 em
XFP 240 em
110
100
90
Dimensions
(in mm)
A
B
780
1385
780
1385
565
1170
565
1170
Weight
(in kg)
Polycarb.
Glass
7.5
9.5
7.5
9.5
9.5
9.5
-
Classification
zone (1)
Polycarb.
Glass
IIC T6
IIC T6
IIC T6
IIC T6
IIC T6
IIC T6
-
* For glass tube version, add V to the reference (eg XFFem 220V)
(1) for immediate opening (no waiting periode), the temperature classification becomes T3
55