Energy Management
Energy Meter
Type EM110
• Single phase energy meter
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Electro-mechanical display
• Energy readout on display: 6+1 digit
• Measurements on display: total kWh
• Direct current measurement up to 45AAC
• Self power supply
• Dimensions: 1-DIN module
• Protection degree (front): IP51
• Pulse output (by open collector PNP)
• Detects wrong current direction
• Certified according to MID Directive (option PF only): see “how to order” below
Product description
Single-phase energy meter with electro-mechanical data displaying; particularly indicated for active energy metering and for cost allocation in applications up to 45 A (direct connection), especially when energy reading is necessary during power down. Housing for
DIN-rail mounting, with IP51 front degree protection.
The meter is provided with pulse output proportional to the active energy being measured.
MID
Certified according to MID Directive, Module B and Module D of Annex II, for legal metrology relevant to active electrical energy meters (see Annex V,
MI003, of MID). Can be used for fiscal (legal) metrology.
How to orderEM110-DIN AV8 1 X O1 PF B
Model
Range code
System
Power supply
Output
Option
Measurement
Type Selection
Range code
AV8: 230VLN AC - 5(45)A
(Direct connection)
AV7: 120VLN AC - 5(45)A
(Direct connection)
System
1: 1-phase 2-wire
Power supply
X: Self power supply
-30% +20% of the rated measuring input voltage, 45 to 65Hz
Output
O1: pulse output
Option
PF: Certified according to MID Directive. Can be used for fiscal(legal) metrology.
Measurement
B: Only the total positive energy meter is certified according to MID. Negative energy is not measured.
Specification are subject to change without notice EM110 DS 130117 1
STANDARD
Not certified according to MID Directive. Cannot be used for fiscal (legal) metrology.
How to order EM110-DIN AV8 1 X O1 X
Model
Range code
System
Power supply
Output
Option
Type Selection
Range code
AV8: 230VLN AC - 5(45)A
(Direct connection)
AV7: 120VLN AC - 5(45)A
(Direct connection)
System
1: 1-phase 2-wire
Option
X: none
Power supply
X: Self power supply
-30% +20% of the rated measuring input voltage, 45 to 65Hz
Output
O1: pulse output
2 Specification are subject to change without notice EM110 DS 130117
EM110
Input specifications
Rated Inputs
Current type
Current range
Nominal voltage
Accuracy
(@25°C ±5°C, R.H. ≤60%,
45 to 65 Hz)
AV7
AV8
Energies
Start-up current:
Start-up voltage
Resolution
Energy
Energy additional errors
Influence quantities
Temperature drift
Sampling rate
1-phase loads, direct connection
5(45)A
230VLN AC (AV8 option),
120 VLN (AV7 option)
Display
Type
Energies read-out
Imin=0.25A; Ib: 5A, Imax:
45A; Un: 120VLN -30%
+30%
Imin=0.25A; Ib: 5A, Imax:
45A; Un: 230VLN -30%
+20%
Class 1 according to
EN62053-21 Class B
(Class B (kWh) according to EN50470-3)
20mA (AV7, AV8)
Self-consumption is not measured.
84V (AV7), 161V (AV8)
0.1 kWh
According to EN62053-21
≤200ppm/°C
4096 samples/s @ 50Hz
Max. and Min. indication
LEDs
Current overloads
Continuous
For 10ms
Voltage Overloads
Continuous
For 500ms
Input impedance
Voltage input 230VL-N
Voltage input 120VL-N
Current inputs: 5(45) A
4096 samples/s @ 60Hz
Electro-mechanical, h 5 mm
Total: 6+1 digit
Only positive energy is integrated
Max. 999 999.9
Min. 0.0
Flashing red light pulses according to EN50470-3,
EN62052-11, 1000 imp./ kWh (min. period: 90ms, max. frequency: 11 Hz)
Fix orange light: wrong current direction
45A, @ 50Hz
1350 A
1.2 Un
2 Un
> 750 Kohm
> 750 Kohm
< 0.5 VA
Output specifications
Static output
Purpose
Pulse rate
Pulse ON duration
For pulse output proportional to the active energy (kWh)
1000 pulses per kWh
30ms, according to
Pulse OFF duration
Output type
Load
EN62052-31
≥120ms, according to
EN62052-31 open collector PNP
V
V
ON
OFF
1 VDC; max. 100 mA
80 VDC max
Specification are subject to change without notice EM110 DS 130117 3
EM110
General specifications
Operating temperature
Storage temperature
Overvoltage category
Insulation (for 1 minute)
Dielectric strength
EMC
Electrostatic discharges
Immunity to irradiated
electromagnetic fields
Burst
Immunity to conducted
disturbances
Surge
Radio frequency
-25 to +65 °C, indoor,
(R.H. from 0 to 90% noncondensing @ 40°C)
-30°C to +80°C (R.H. <
90% noncondensing @
40°C)
Cat. III
4000 VAC RMS between measuring inputs and digital/serial output (see table) 4000 VAC RMS
4000 VAC RMS for 1 minute
According to EN62052-11
15kV air discharge;
Test with current: 10V/m from 80 to 2000MHz; Test without any current: 30V/m from 80 to 2000MHz;
On current and voltage measuring inputs circuit:
4kV
10V/m from 150KHz to
80MHz
On current and voltage measuring inputs circuit:
4kV;
According to CISPR 22
Standard compliance
Safety
Metrology
Approvals
EN62052-11
EN62053-21, EN50470-3
CE, MID (PF option only), cULus (AV7 option only)
Connections
Cable cross-section area
Other terminals
Measuring inputs: 6 mm 2 , with/without metallic cable ferrule; Max. screw tightening torque: 1.1 Nm
1.5 mm², Min./Max. screws tightening torque: 0.4 Nm
Housing
Dimensions (WxHxD)
Material
17.5 x 63 x 90 mm
Noryl, self-extinguishing:
UL 94 V-0
Included Sealing covers
Mounting DIN-rail
Protection degree
Front IP51
Screw terminals (cable inputs) IP20
Weight Approx. 75 g (packing included)
Power supply specifications
Self power supply
AV8
AV7
230VAC VL-N, -30% +20%
50/60Hz
120VAC VL-N, -30% +30%
50/60Hz
Power consumption ≤1.0W, ≤ 8VA
Insulation (for 1 minute) between inputs and outputs
Measuring input
Digital output
Measuring input
-
4 kV
Digital output
4 kV
-
4 Specification are subject to change without notice EM110 DS 130117
EM110
MID compliance (PF option only)
Accuracy
Operating temperature
EMC compliance
Mechanical compliance
0.9 Un ≤ U ≤ 1.1 Un; 0.98 fn ≤ f ≤ 1.02 fn; fn: 50 Hz; cosj: 0.5 inductive to 0.8 capacitive.
Class B
Considering listed Ib or In values
-25 to +55°C (-13°F to 131°F) (R.H. from 0 to 90% non-condensing @ 40°C)
E2
M2
Accuracy according to EN50470-3
kWh, accuracy (RDG) depending on the current
Percentage error limits for class index B
+1.5%
+1%
0%
-1%
-1.5%
PF=1 0.25A(I
PF=L0.5
or C0.8
0.05A(I min ref
)
) 0.5A(I
(0,1I
0.5A(I
(0,1I ref tr tr
)
)
) 5A(I n
) 5A(I n
)
)
Class 1 accuracy limits (Active energy)
5(45)A Start-up current: 20mA
45A(I max
)
45A(I max
)
Wiring diagrams
1-ph, 2-wire (F 315mA) Fig.1
1-ph, 2-wire Fig.2
Specification are subject to change without notice EM110 DS 130117 5
EM110
Wiring diagrams (cont.)
Pulse output Fig.3
Vdc Out GND Vdc GND Out
Open collector outputs: the load resistance (Rc) must be designed so that the closed contact current is under 100 mA (V on
is equal to 1 V dc). DC voltage (V off
) must be less than or equal to 80 V.
Front panel description
5
4
3
1
2
1. Display
Electro-mechanical type with total kWh indication
2. LED
LED proportional to kWh reading
3. Serial number and MID data
Area reserved to serial number and MID-relevant data in
PF versions
Dimensions
17.5
43
6
49
63
Specification are subject to change without notice EM110 DS 130117