Switch Amplifier
Features
• 2-channel isolated barrier
• 230 V AC supply
• Dry contact or NAMUR inputs
• Latching relay output
• Line fault detection (LFD)
• Reversible mode of operation
Function
This isolated barrier is used for intrinsic safety applications. It has a latching relay (bistable operation) for level control, pump up/pump down, or other switch/logic applications. The device is set by an active signal on input I and is reset by an active signal on input II. The mode of operation of inputs I and II can be programmed.
Switch S3 is used to enable or disable line fault detection of the field circuit. During an error condition or loss of power, the form C changeover relays revert to their de-energized state and the LEDs indicate the fault according to NAMUR NE44.
When the wiring fault is corrected, the relay will revert to the state prior to the fault.
If the device is re-energized after power loss, the relays return to a factory-configured state.
Assembly
Front view
LED yellow:
Relay output ( Ι)
LED red:
LB/SC input Ι
LED yellow:
Relay output ( ΙΙ)
LED red:
LB/SC input ΙΙ
KFA6-SR2-Ex2.W.IR
Removable terminals blue
1
4
2
5
3
6
KFA6-SR2-Ex2.W.IR
S1
S2
S3
1
2
OUT CHK PWR
I II
7
10
13
8
11
14
9
12
15
LED green:
Power supply
Switch S1
(mode of operation input
Ι)
Switch S2
(mode of operation input ΙΙ)
Switch S3
(LB/SC-monitoring)
Removable terminals green
Connection
I
II
10 kΩ
400 Ω ≤ R ≤ 2 kΩ
10 kΩ
10 kΩ
400 Ω ≤ R ≤ 2 kΩ
10 kΩ
4+
5+
6-
1+
2+
3-
KFA6-SR2-Ex2.W.IR
7
8
9
I
10
11
12
II
14
15
230 V AC
Zone 0, 1, 2
Div. 1, 2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group www.pepperl-fuchs.com
USA: +1 330 486 0002 [email protected]
Germany: +49 621 776 2222 [email protected]
Singapore: +65 6779 9091 [email protected]
1
Technical data KFA6-SR2-Ex2.W.IR
General specifications
Signal type
Supply
Connection
Rated voltage
Power consumption
U r
Digital Input terminals 14, 15
207 ... 253 V AC, 45 ... 65 Hz
≤ 1.5 W
Input
Connection
Rated values terminals 1+, 2+, 3-; 4+, 5+, 6acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio ≥ 10 ms / ≥ 10 ms
Output
Connection
Output I, II
Contact loading
Energized/De-energized delay
Mechanical life
Transfer characteristics
Switching frequency
Galvanic isolation output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 signal ; relay
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load approx. 20 ms / approx. 20 ms
10
7
switching cycles
≤ 10 Hz
Input/Output
Input/power supply
Output/power supply
Output/Output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU
Low voltage
Directive 2014/35/EU
Conformity
Electromagnetic compatibility
Degree of protection reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
EN 61326-1:2013 (industrial locations)
EN 61010-1:2010
NE 21:2006
IEC 60529:2001
Ambient conditions
Ambient temperature
Mechanical specifications
Degree of protection
Mass
Dimensions
Mounting
Data for application in connection with hazardous areas
EU-Type Examination Certificate
Marking
Input
Voltage U o
Current I o
Power P o
Supply
Maximum safe voltage
Output
Contact loading
Maximum safe voltage
Galvanic isolation
Input/input
Input/Output
Input/power supply
Directive conformity
Directive 2014/34/EU
International approvals
FM approval
Control drawing
U m
U m
-20 ... 60 °C (-4 ... 140 °F)
IP20 approx. 150 g
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 on 35 mm DIN mounting rail acc. to EN 60715:2001
PTB 00 ATEX 2081
¬
II (1)G [Ex ia Ga] IIC
¬
II (1)D [Ex ia Da] IIIC
¬
I (M1) [Ex ia Ma] I
Ex ia
10.6 V
19.1 mA
51 mW (linear characteristic)
253 V AC (Attention! U m
is no rated voltage.)
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
253 V AC (Attention! The rated voltage can be lower.) not available safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
116-0035
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group www.pepperl-fuchs.com
USA: +1 330 486 0002 [email protected]
Germany: +49 621 776 2222 [email protected]
Singapore: +65 6779 9091 [email protected]
2
Technical data
UL approval
Control drawing
CSA approval
Control drawing
IECEx approval
Approved for
General information
Supplementary information
KFA6-SR2-Ex2.W.IR
116-0145
116-0047
IECEx PTB 11.0031
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperlfuchs.com.
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group www.pepperl-fuchs.com
USA: +1 330 486 0002 [email protected]
Germany: +49 621 776 2222 [email protected]
Singapore: +65 6779 9091 [email protected]
3
Technical data
Configuration
1
4
2
5
3
6
S1
S2
S3
1
2
OUT CHK PWR
7
10
13
8
11
14
9
12
15
S1
S2
S3
I II
KFA6-SR2-Ex2.W.IR
Switch position
S
1
2
3
Mode of operation
Output I (relay) energized
Mode of operation
Output II (relay) energized
Line fault detection
Function with high input current with low input current with high input current with low input current
ON
OFF
Operating status
Control circuit
Initiator high impedance/ contact opened
Initiator low impedance/ contact closed
Lead breakage, lead short-circuit
Factory settings: switch 1, 2 and 3 in position I
Input signal low input current high input current
Line fault
Position
I
II
I
II
I
II
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group www.pepperl-fuchs.com
USA: +1 330 486 0002 [email protected]
Germany: +49 621 776 2222 [email protected]
Singapore: +65 6779 9091 [email protected]
4
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project